Node and Member

Loading

Members - Definition

Page 9
Robot Structural Analysis Professional 2023
Author: File: Structure.RTD
Address: Richmond Coach,Royston Project: K2198 Richmond Coach

Code Ly Lz
Member Name Components Section Type
group (m) (m)
1 Simple member1_1 1 (N/A) EQA 50x4 Simple member1 1.38 1.38
2 Simple member1_2 2 (N/A) EQA 50x4 Simple member1 0.59 0.59
3 Simple member1_3 3 (N/A) EQA 50x4 Simple member1 1.36 1.36
4 Simple member1_4 4 (N/A) EQA 50x4 Simple member1 2.69 2.69
5 Simple member1_5 5 (N/A) EQA 50x4 Simple member1 0.59 0.59
6 Simple member1_6 6 (N/A) EQA 50x4 Simple member1 1.18 1.18
7 Simple member1_7 7 (N/A) EQA 50x4 Simple member1 1.36 1.36
8 Simple member1_8 8 (N/A) EQA 50x4 Simple member1 2.69 2.69
9 Simple member1_9 9 (N/A) EQA 50x4 Simple member1 0.59 0.59
10 Simple member1_10 10 (N/A) EQA 50x4 Simple member1 1.18 1.18
11 Simple member1_11 11 (N/A) EQA 50x4 Simple member1 1.38 1.38
12 Simple member1_12 12 (N/A) EQA 50x4 Simple member1 0.59 0.59
13 13 (N/A) EQA 50x4 Simple member1 1.40 1.40
14 Simple member1_14 14 (N/A) EQA 50x4 Simple member1 1.40 1.40
15 Simple member1_15 15 (N/A) EQA 50x4 Simple member1 3.40 3.40
16 Simple member1_16 16 (N/A) EQA 50x4 Simple member1 1.40 1.40
17 Simple member1_17 17 (N/A) EQA 50x4 Simple member1 1.40 1.40
18 Simple member1_18 18 (N/A) EQA 50x4 Simple member1 1.24 1.24
19 Simple member1_19 19 (N/A) EQA 50x4 Simple member1 1.26 1.26
20 Simple member1_20 20 (N/A) EQA 50x4 Simple member1 1.18 1.18
21 Simple member1_21 21 (N/A) EQA 50x4 Simple member1 1.28 1.28
22 22 (N/A) EQA 50x4 Simple member1 1.24 1.24
23 Simple member1_23 23 (N/A) EQA 50x4 Simple member1 1.26 1.26
24 Simple member1_24 24 (N/A) EQA 50x4 Simple member1 1.18 1.18
25 Simple member1_25 25 (N/A) EQA 50x4 Simple member1 1.28 1.28

Steel Member Verification


STEEL DESIGN
----------------------------------------------------------------------------------------------------------------------------------------
CODE: British Standard BS 5950:2000
ANALYSIS TYPE: Member Verification
----------------------------------------------------------------------------------------------------------------------------------------
CODE GROUP:
MEMBER: 1 Simple member1_1 POINT: 1 COORDINATE: x = 0.00 L = 0.00 m
----------------------------------------------------------------------------------------------------------------------------------------
LOADS:
Governing Load Case: 4 1.2DL+1.2LL+1.2WL (1+2+3)*1.20
----------------------------------------------------------------------------------------------------------------------------------------
MATERIAL
STEEL 43-275 py = 275.00 MPa E = 205000.00 MPa
----------------------------------------------------------------------------------------------------------------------------------------
SECTION PARAMETERS: EQA 50x4

D=50 mm
B=50 mm Ay=200 mm2 Az=200 mm2 A=392 mm2
t=4 mm Iy=91600 mm4 Iz=91600 mm4 Ix=2050 mm4
T=4 mm Wely=2523 mm3 Welz=2523 mm3
Date : 30/06/23 Page : 10
Robot Structural Analysis Professional 2023
Author: File: Structure.RTD
Address: Richmond Coach,Royston Project: K2198 Richmond Coach

----------------------------------------------------------------------------------------------------------------------------------------
INTERNAL FORCES
Ft = -6.04 kN

----------------------------------------------------------------------------------------------------------------------------------------
CAPACITIES
Pt = 107.80 kN
Section class = 1
----------------------------------------------------------------------------------------------------------------------------------------
LATERAL BUCKLING PARAMETERS:

----------------------------------------------------------------------------------------------------------------------------------------
BUCKLING PARAMETERS:
About Y axis: About Z axis:

----------------------------------------------------------------------------------------------------------------------------------------
VERIFICATION FORMULAS:
Section check
Ft/Pt = 0.06 < 1.00 (4.8.2.2)
Member stability check
Not analyzed
----------------------------------------------------------------------------------------------------------------------------------------
LIMIT DISPLACEMENTS
Deflections (LOCAL SYSTEM):

uy = 0 mm < uy max = L/200.00 = 7 mm Verified


Governing Load Case: 1 DL1
uz = 0 mm < uz max = L/200.00 = 7 mm Verified
Governing Load Case: 6 1DL+1LL+1WL (1+2+3)*1.00
Displacements (GLOBAL SYSTEM):

vx = 0 mm < vx max = L/300.00 = 5 mm Verified


Governing Load Case: 6 1DL+1LL+1WL (1+2+3)*1.00
vy = 0 mm < vy max = L/300.00 = 5 mm Verified
Governing Load Case: 1 DL1
----------------------------------------------------------------------------------------------------------------------------------------
Section OK !!!

STEEL DESIGN
----------------------------------------------------------------------------------------------------------------------------------------
CODE: British Standard BS 5950:2000
ANALYSIS TYPE: Member Verification
----------------------------------------------------------------------------------------------------------------------------------------
CODE GROUP:
MEMBER: 2 Simple member1_2 POINT: 1 COORDINATE: x = 0.00 L = 0.00 m
----------------------------------------------------------------------------------------------------------------------------------------
LOADS:
Governing Load Case: 4 1.2DL+1.2LL+1.2WL (1+2+3)*1.20
----------------------------------------------------------------------------------------------------------------------------------------
MATERIAL
STEEL 43-275 py = 275.00 MPa E = 205000.00 MPa

Date : 30/06/23 Page : 11


Robot Structural Analysis Professional 2023
Author: File: Structure.RTD
Address: Richmond Coach,Royston Project: K2198 Richmond Coach

----------------------------------------------------------------------------------------------------------------------------------------
SECTION PARAMETERS: EQA 50x4

D=50 mm
B=50 mm Ay=200 mm2 Az=200 mm2 A=392 mm2
t=4 mm Iy=91600 mm4 Iz=91600 mm4 Ix=2050 mm4
T=4 mm Wely=2523 mm3 Welz=2523 mm3
----------------------------------------------------------------------------------------------------------------------------------------
INTERNAL FORCES
Fc = 4.92 kN

----------------------------------------------------------------------------------------------------------------------------------------
CAPACITIES
Pc = 103.49 kN
Section class = 4
----------------------------------------------------------------------------------------------------------------------------------------
LATERAL BUCKLING PARAMETERS:

----------------------------------------------------------------------------------------------------------------------------------------
BUCKLING PARAMETERS:
About Y axis: About Z axis:

Ly = 0.59 m pey = 2190.61 MPa Lz = 0.59 m pez = 2190.61 MPa


Ley = 0.47 m Fiy = 1312.54 MPa Lez = 0.47 m Fiz = 1312.54 MPa
Lam,effy = 30.39 py = 254.08 MPa Lam,effz = 30.39 pz = 254.08 MPa
ny = 0.07 Pcy = 95.61 kN nz = 0.07 Pcz = 95.61 kN
----------------------------------------------------------------------------------------------------------------------------------------
VERIFICATION FORMULAS:
Section check
Fc/Pc = 0.05 < 1.00 (4.8.3.2)
Member stability check
Fc/min(Pcy,Pcz) = 0.05 < 1.00 (4.8.3.3.1)
----------------------------------------------------------------------------------------------------------------------------------------
LIMIT DISPLACEMENTS
Deflections (LOCAL SYSTEM):

uy = 0 mm < uy max = L/200.00 = 3 mm Verified


Governing Load Case: 1 DL1
uz = 0 mm < uz max = L/200.00 = 3 mm Verified
Governing Load Case: 6 1DL+1LL+1WL (1+2+3)*1.00
Displacements (GLOBAL SYSTEM):

vx = 0 mm < vx max = L/300.00 = 2 mm Verified


Governing Load Case: 6 1DL+1LL+1WL (1+2+3)*1.00
vy = 0 mm < vy max = L/300.00 = 2 mm Verified
Governing Load Case: 1 DL1
----------------------------------------------------------------------------------------------------------------------------------------
Section OK !!!

STEEL DESIGN
Date : 30/06/23 Page : 12
Robot Structural Analysis Professional 2023
Author: File: Structure.RTD
Address: Richmond Coach,Royston Project: K2198 Richmond Coach

----------------------------------------------------------------------------------------------------------------------------------------
CODE: British Standard BS 5950:2000
ANALYSIS TYPE: Member Verification
----------------------------------------------------------------------------------------------------------------------------------------
CODE GROUP:
MEMBER: 3 Simple member1_3 POINT: 1 COORDINATE: x = 0.00 L = 0.00 m
----------------------------------------------------------------------------------------------------------------------------------------
LOADS:
Governing Load Case: 4 1.2DL+1.2LL+1.2WL (1+2+3)*1.20
----------------------------------------------------------------------------------------------------------------------------------------
MATERIAL
STEEL 43-275 py = 275.00 MPa E = 205000.00 MPa
----------------------------------------------------------------------------------------------------------------------------------------
SECTION PARAMETERS: EQA 50x4

D=50 mm
B=50 mm Ay=200 mm2 Az=200 mm2 A=392 mm2
t=4 mm Iy=91600 mm4 Iz=91600 mm4 Ix=2050 mm4
T=4 mm Wely=2523 mm3 Welz=2523 mm3
----------------------------------------------------------------------------------------------------------------------------------------
INTERNAL FORCES
Ft = -5.75 kN

----------------------------------------------------------------------------------------------------------------------------------------
CAPACITIES
Pt = 107.80 kN
Section class = 1
----------------------------------------------------------------------------------------------------------------------------------------
LATERAL BUCKLING PARAMETERS:

----------------------------------------------------------------------------------------------------------------------------------------
BUCKLING PARAMETERS:
About Y axis: About Z axis:

----------------------------------------------------------------------------------------------------------------------------------------
VERIFICATION FORMULAS:
Section check
Ft/Pt = 0.05 < 1.00 (4.8.2.2)
Member stability check
Not analyzed
----------------------------------------------------------------------------------------------------------------------------------------
LIMIT DISPLACEMENTS
Deflections (LOCAL SYSTEM):

uy = 0 mm < uy max = L/200.00 = 7 mm Verified


Governing Load Case: 1 DL1
uz = 0 mm < uz max = L/200.00 = 7 mm Verified
Governing Load Case: 6 1DL+1LL+1WL (1+2+3)*1.00
Displacements (GLOBAL SYSTEM):

vx = 1 mm < vx max = L/300.00 = 5 mm Verified


Governing Load Case: 6 1DL+1LL+1WL (1+2+3)*1.00
vy = 0 mm < vy max = L/300.00 = 5 mm Verified
Date : 30/06/23 Page : 13
Robot Structural Analysis Professional 2023
Author: File: Structure.RTD
Address: Richmond Coach,Royston Project: K2198 Richmond Coach

Governing Load Case: 1 DL1


----------------------------------------------------------------------------------------------------------------------------------------
Section OK !!!

STEEL DESIGN
----------------------------------------------------------------------------------------------------------------------------------------
CODE: British Standard BS 5950:2000
ANALYSIS TYPE: Member Verification
----------------------------------------------------------------------------------------------------------------------------------------
CODE GROUP:
MEMBER: 4 Simple member1_4 POINT: 1 COORDINATE: x = 0.50 L = 1.34 m
----------------------------------------------------------------------------------------------------------------------------------------
LOADS:
Governing Load Case: 4 1.2DL+1.2LL+1.2WL (1+2+3)*1.20
----------------------------------------------------------------------------------------------------------------------------------------
MATERIAL
STEEL 43-275 py = 275.00 MPa E = 205000.00 MPa
----------------------------------------------------------------------------------------------------------------------------------------
SECTION PARAMETERS: EQA 50x4

D=50 mm
B=50 mm Ay=200 mm2 Az=200 mm2 A=392 mm2
t=4 mm Iy=91600 mm4 Iz=91600 mm4 Ix=2050 mm4
T=4 mm Wely=2523 mm3 Welz=2523 mm3
----------------------------------------------------------------------------------------------------------------------------------------
INTERNAL FORCES
Ft = -17.14 kN

----------------------------------------------------------------------------------------------------------------------------------------
CAPACITIES
Pt = 107.80 kN
Section class = 1
----------------------------------------------------------------------------------------------------------------------------------------
LATERAL BUCKLING PARAMETERS:

----------------------------------------------------------------------------------------------------------------------------------------
BUCKLING PARAMETERS:
About Y axis: About Z axis:

----------------------------------------------------------------------------------------------------------------------------------------
VERIFICATION FORMULAS:
Section check
Ft/Pt = 0.16 < 1.00 (4.8.2.2)
Member stability check
Not analyzed
----------------------------------------------------------------------------------------------------------------------------------------
LIMIT DISPLACEMENTS
Deflections (LOCAL SYSTEM):

uy = 0 mm < uy max = L/200.00 = 13 mm Verified

Date : 30/06/23 Page : 14


Robot Structural Analysis Professional 2023
Author: File: Structure.RTD
Address: Richmond Coach,Royston Project: K2198 Richmond Coach

Governing Load Case: 1 DL1


uz = 2 mm < uz max = L/200.00 = 13 mm Verified
Governing Load Case: 6 1DL+1LL+1WL (1+2+3)*1.00
Displacements (GLOBAL SYSTEM):

vx = 0 mm < vx max = L/300.00 = 9 mm Verified


Governing Load Case: 6 1DL+1LL+1WL (1+2+3)*1.00
vy = 0 mm < vy max = L/300.00 = 9 mm Verified
Governing Load Case: 1 DL1
----------------------------------------------------------------------------------------------------------------------------------------
Section OK !!!

STEEL DESIGN
----------------------------------------------------------------------------------------------------------------------------------------
CODE: British Standard BS 5950:2000
ANALYSIS TYPE: Member Verification
----------------------------------------------------------------------------------------------------------------------------------------
CODE GROUP:
MEMBER: 5 Simple member1_5 POINT: 1 COORDINATE: x = 0.00 L = 0.00 m
----------------------------------------------------------------------------------------------------------------------------------------
LOADS:
Governing Load Case: 4 1.2DL+1.2LL+1.2WL (1+2+3)*1.20
----------------------------------------------------------------------------------------------------------------------------------------
MATERIAL
STEEL 43-275 py = 275.00 MPa E = 205000.00 MPa
----------------------------------------------------------------------------------------------------------------------------------------
SECTION PARAMETERS: EQA 50x4

D=50 mm
B=50 mm Ay=200 mm2 Az=200 mm2 A=392 mm2
t=4 mm Iy=91600 mm4 Iz=91600 mm4 Ix=2050 mm4
T=4 mm Wely=2523 mm3 Welz=2523 mm3
----------------------------------------------------------------------------------------------------------------------------------------
INTERNAL FORCES
Fc = 4.89 kN

----------------------------------------------------------------------------------------------------------------------------------------
CAPACITIES
Pc = 103.49 kN
Section class = 4
----------------------------------------------------------------------------------------------------------------------------------------
LATERAL BUCKLING PARAMETERS:

----------------------------------------------------------------------------------------------------------------------------------------
BUCKLING PARAMETERS:
About Y axis: About Z axis:

Ly = 0.59 m pey = 2218.85 MPa Lz = 0.59 m pez = 2218.85 MPa


Ley = 0.47 m Fiy = 1326.50 MPa Lez = 0.47 m Fiz = 1326.50 MPa
Lam,effy = 30.20 py = 254.39 MPa Lam,effz = 30.20 pz = 254.39 MPa

Date : 30/06/23 Page : 15


Robot Structural Analysis Professional 2023
Author: File: Structure.RTD
Address: Richmond Coach,Royston Project: K2198 Richmond Coach

ny = 0.07 Pcy = 95.73 kN nz = 0.07 Pcz = 95.73 kN


----------------------------------------------------------------------------------------------------------------------------------------
VERIFICATION FORMULAS:
Section check
Fc/Pc = 0.05 < 1.00 (4.8.3.2)
Member stability check
Fc/min(Pcy,Pcz) = 0.05 < 1.00 (4.8.3.3.1)
----------------------------------------------------------------------------------------------------------------------------------------
LIMIT DISPLACEMENTS
Deflections (LOCAL SYSTEM):

uy = 0 mm < uy max = L/200.00 = 3 mm Verified


Governing Load Case: 1 DL1
uz = 0 mm < uz max = L/200.00 = 3 mm Verified
Governing Load Case: 6 1DL+1LL+1WL (1+2+3)*1.00
Displacements (GLOBAL SYSTEM):

vx = 1 mm < vx max = L/300.00 = 2 mm Verified


Governing Load Case: 6 1DL+1LL+1WL (1+2+3)*1.00
vy = 0 mm < vy max = L/300.00 = 2 mm Verified
Governing Load Case: 1 DL1
----------------------------------------------------------------------------------------------------------------------------------------
Section OK !!!

STEEL DESIGN
----------------------------------------------------------------------------------------------------------------------------------------
CODE: British Standard BS 5950:2000
ANALYSIS TYPE: Member Verification
----------------------------------------------------------------------------------------------------------------------------------------
CODE GROUP:
MEMBER: 6 Simple member1_6 POINT: 1 COORDINATE: x = 0.00 L = 0.00 m
----------------------------------------------------------------------------------------------------------------------------------------
LOADS:
Governing Load Case: 4 1.2DL+1.2LL+1.2WL (1+2+3)*1.20
----------------------------------------------------------------------------------------------------------------------------------------
MATERIAL
STEEL 43-275 py = 275.00 MPa E = 205000.00 MPa
----------------------------------------------------------------------------------------------------------------------------------------
SECTION PARAMETERS: EQA 50x4

D=50 mm
B=50 mm Ay=200 mm2 Az=200 mm2 A=392 mm2
t=4 mm Iy=91600 mm4 Iz=91600 mm4 Ix=2050 mm4
T=4 mm Wely=2523 mm3 Welz=2523 mm3
----------------------------------------------------------------------------------------------------------------------------------------
INTERNAL FORCES
Fc = 10.00 kN

----------------------------------------------------------------------------------------------------------------------------------------
CAPACITIES
Pc = 103.49 kN

Date : 30/06/23 Page : 16


Robot Structural Analysis Professional 2023
Author: File: Structure.RTD
Address: Richmond Coach,Royston Project: K2198 Richmond Coach

Section class = 4
----------------------------------------------------------------------------------------------------------------------------------------
LATERAL BUCKLING PARAMETERS:

----------------------------------------------------------------------------------------------------------------------------------------
BUCKLING PARAMETERS:
About Y axis: About Z axis:

Ly = 1.18 m pey = 555.14 MPa Lz = 1.18 m pez = 555.14 MPa


Ley = 0.94 m Fiy = 481.04 MPa Lez = 0.94 m Fiz = 481.04 MPa
Lam,effy = 60.37 py = 200.44 MPa Lam,effz = 60.37 pz = 200.44 MPa
ny = 0.24 Pcy = 75.43 kN nz = 0.24 Pcz = 75.43 kN
----------------------------------------------------------------------------------------------------------------------------------------
VERIFICATION FORMULAS:
Section check
Fc/Pc = 0.10 < 1.00 (4.8.3.2)
Member stability check
Fc/min(Pcy,Pcz) = 0.13 < 1.00 (4.8.3.3.1)
----------------------------------------------------------------------------------------------------------------------------------------
LIMIT DISPLACEMENTS
Deflections (LOCAL SYSTEM):

uy = 0 mm < uy max = L/200.00 = 6 mm Verified


Governing Load Case: 1 DL1
uz = 0 mm < uz max = L/200.00 = 6 mm Verified
Governing Load Case: 6 1DL+1LL+1WL (1+2+3)*1.00
Displacements (GLOBAL SYSTEM):

vx = 1 mm < vx max = L/300.00 = 4 mm Verified


Governing Load Case: 6 1DL+1LL+1WL (1+2+3)*1.00
vy = 0 mm < vy max = L/300.00 = 4 mm Verified
Governing Load Case: 1 DL1
----------------------------------------------------------------------------------------------------------------------------------------
Section OK !!!

STEEL DESIGN
----------------------------------------------------------------------------------------------------------------------------------------
CODE: British Standard BS 5950:2000
ANALYSIS TYPE: Member Verification
----------------------------------------------------------------------------------------------------------------------------------------
CODE GROUP:
MEMBER: 7 Simple member1_7 POINT: 1 COORDINATE: x = 0.00 L = 0.00 m
----------------------------------------------------------------------------------------------------------------------------------------
LOADS:
Governing Load Case: 4 1.2DL+1.2LL+1.2WL (1+2+3)*1.20
----------------------------------------------------------------------------------------------------------------------------------------
MATERIAL
STEEL 43-275 py = 275.00 MPa E = 205000.00 MPa
----------------------------------------------------------------------------------------------------------------------------------------
SECTION PARAMETERS: EQA 50x4

Date : 30/06/23 Page : 17


Robot Structural Analysis Professional 2023
Author: File: Structure.RTD
Address: Richmond Coach,Royston Project: K2198 Richmond Coach

D=50 mm
B=50 mm Ay=200 mm2 Az=200 mm2 A=392 mm2
t=4 mm Iy=91600 mm4 Iz=91600 mm4 Ix=2050 mm4
T=4 mm Wely=2523 mm3 Welz=2523 mm3
----------------------------------------------------------------------------------------------------------------------------------------
INTERNAL FORCES
Ft = -5.75 kN

----------------------------------------------------------------------------------------------------------------------------------------
CAPACITIES
Pt = 107.80 kN
Section class = 1
----------------------------------------------------------------------------------------------------------------------------------------
LATERAL BUCKLING PARAMETERS:

----------------------------------------------------------------------------------------------------------------------------------------
BUCKLING PARAMETERS:
About Y axis: About Z axis:

----------------------------------------------------------------------------------------------------------------------------------------
VERIFICATION FORMULAS:
Section check
Ft/Pt = 0.05 < 1.00 (4.8.2.2)
Member stability check
Not analyzed
----------------------------------------------------------------------------------------------------------------------------------------
LIMIT DISPLACEMENTS
Deflections (LOCAL SYSTEM):

uy = 0 mm < uy max = L/200.00 = 7 mm Verified


Governing Load Case: 1 DL1
uz = 0 mm < uz max = L/200.00 = 7 mm Verified
Governing Load Case: 6 1DL+1LL+1WL (1+2+3)*1.00
Displacements (GLOBAL SYSTEM):

vx = 1 mm < vx max = L/300.00 = 5 mm Verified


Governing Load Case: 6 1DL+1LL+1WL (1+2+3)*1.00
vy = 0 mm < vy max = L/300.00 = 5 mm Verified
Governing Load Case: 1 DL1
----------------------------------------------------------------------------------------------------------------------------------------
Section OK !!!

STEEL DESIGN
----------------------------------------------------------------------------------------------------------------------------------------
CODE: British Standard BS 5950:2000
ANALYSIS TYPE: Member Verification
----------------------------------------------------------------------------------------------------------------------------------------
CODE GROUP:
MEMBER: 8 Simple member1_8 POINT: 1 COORDINATE: x = 0.50 L = 1.34 m
----------------------------------------------------------------------------------------------------------------------------------------
LOADS:

Date : 30/06/23 Page : 18


Robot Structural Analysis Professional 2023
Author: File: Structure.RTD
Address: Richmond Coach,Royston Project: K2198 Richmond Coach

Governing Load Case: 4 1.2DL+1.2LL+1.2WL (1+2+3)*1.20


----------------------------------------------------------------------------------------------------------------------------------------
MATERIAL
STEEL 43-275 py = 275.00 MPa E = 205000.00 MPa
----------------------------------------------------------------------------------------------------------------------------------------
SECTION PARAMETERS: EQA 50x4

D=50 mm
B=50 mm Ay=200 mm2 Az=200 mm2 A=392 mm2
t=4 mm Iy=91600 mm4 Iz=91600 mm4 Ix=2050 mm4
T=4 mm Wely=2523 mm3 Welz=2523 mm3
----------------------------------------------------------------------------------------------------------------------------------------
INTERNAL FORCES
Ft = -17.14 kN

----------------------------------------------------------------------------------------------------------------------------------------
CAPACITIES
Pt = 107.80 kN
Section class = 1
----------------------------------------------------------------------------------------------------------------------------------------
LATERAL BUCKLING PARAMETERS:

----------------------------------------------------------------------------------------------------------------------------------------
BUCKLING PARAMETERS:
About Y axis: About Z axis:

----------------------------------------------------------------------------------------------------------------------------------------
VERIFICATION FORMULAS:
Section check
Ft/Pt = 0.16 < 1.00 (4.8.2.2)
Member stability check
Not analyzed
----------------------------------------------------------------------------------------------------------------------------------------
LIMIT DISPLACEMENTS
Deflections (LOCAL SYSTEM):

uy = 0 mm < uy max = L/200.00 = 13 mm Verified


Governing Load Case: 1 DL1
uz = 2 mm < uz max = L/200.00 = 13 mm Verified
Governing Load Case: 6 1DL+1LL+1WL (1+2+3)*1.00
Displacements (GLOBAL SYSTEM):

vx = 0 mm < vx max = L/300.00 = 9 mm Verified


Governing Load Case: 6 1DL+1LL+1WL (1+2+3)*1.00
vy = 0 mm < vy max = L/300.00 = 9 mm Verified
Governing Load Case: 1 DL1
----------------------------------------------------------------------------------------------------------------------------------------
Section OK !!!

STEEL DESIGN
Date : 30/06/23 Page : 19
Robot Structural Analysis Professional 2023
Author: File: Structure.RTD
Address: Richmond Coach,Royston Project: K2198 Richmond Coach

----------------------------------------------------------------------------------------------------------------------------------------
CODE: British Standard BS 5950:2000
ANALYSIS TYPE: Member Verification
----------------------------------------------------------------------------------------------------------------------------------------
CODE GROUP:
MEMBER: 9 Simple member1_9 POINT: 1 COORDINATE: x = 0.00 L = 0.00 m
----------------------------------------------------------------------------------------------------------------------------------------
LOADS:
Governing Load Case: 4 1.2DL+1.2LL+1.2WL (1+2+3)*1.20
----------------------------------------------------------------------------------------------------------------------------------------
MATERIAL
STEEL 43-275 py = 275.00 MPa E = 205000.00 MPa
----------------------------------------------------------------------------------------------------------------------------------------
SECTION PARAMETERS: EQA 50x4

D=50 mm
B=50 mm Ay=200 mm2 Az=200 mm2 A=392 mm2
t=4 mm Iy=91600 mm4 Iz=91600 mm4 Ix=2050 mm4
T=4 mm Wely=2523 mm3 Welz=2523 mm3
----------------------------------------------------------------------------------------------------------------------------------------
INTERNAL FORCES
Fc = 4.89 kN

----------------------------------------------------------------------------------------------------------------------------------------
CAPACITIES
Pc = 103.49 kN
Section class = 4
----------------------------------------------------------------------------------------------------------------------------------------
LATERAL BUCKLING PARAMETERS:

----------------------------------------------------------------------------------------------------------------------------------------
BUCKLING PARAMETERS:
About Y axis: About Z axis:

Ly = 0.59 m pey = 2218.85 MPa Lz = 0.59 m pez = 2218.85 MPa


Ley = 0.47 m Fiy = 1326.50 MPa Lez = 0.47 m Fiz = 1326.50 MPa
Lam,effy = 30.20 py = 254.39 MPa Lam,effz = 30.20 pz = 254.39 MPa
ny = 0.07 Pcy = 95.73 kN nz = 0.07 Pcz = 95.73 kN
----------------------------------------------------------------------------------------------------------------------------------------
VERIFICATION FORMULAS:
Section check
Fc/Pc = 0.05 < 1.00 (4.8.3.2)
Member stability check
Fc/min(Pcy,Pcz) = 0.05 < 1.00 (4.8.3.3.1)
----------------------------------------------------------------------------------------------------------------------------------------
LIMIT DISPLACEMENTS
Deflections (LOCAL SYSTEM):

uy = 0 mm < uy max = L/200.00 = 3 mm Verified


Governing Load Case: 1 DL1
uz = 0 mm < uz max = L/200.00 = 3 mm Verified
Governing Load Case: 6 1DL+1LL+1WL (1+2+3)*1.00

Date : 30/06/23 Page : 20


Robot Structural Analysis Professional 2023
Author: File: Structure.RTD
Address: Richmond Coach,Royston Project: K2198 Richmond Coach

Displacements (GLOBAL SYSTEM):

vx = 1 mm < vx max = L/300.00 = 2 mm Verified


Governing Load Case: 6 1DL+1LL+1WL (1+2+3)*1.00
vy = 0 mm < vy max = L/300.00 = 2 mm Verified
Governing Load Case: 1 DL1
----------------------------------------------------------------------------------------------------------------------------------------
Section OK !!!

STEEL DESIGN
----------------------------------------------------------------------------------------------------------------------------------------
CODE: British Standard BS 5950:2000
ANALYSIS TYPE: Member Verification
----------------------------------------------------------------------------------------------------------------------------------------
CODE GROUP:
MEMBER: 10 Simple member1_10 POINT: 1 COORDINATE: x = 0.00 L = 0.00 m
----------------------------------------------------------------------------------------------------------------------------------------
LOADS:
Governing Load Case: 4 1.2DL+1.2LL+1.2WL (1+2+3)*1.20
----------------------------------------------------------------------------------------------------------------------------------------
MATERIAL
STEEL 43-275 py = 275.00 MPa E = 205000.00 MPa
----------------------------------------------------------------------------------------------------------------------------------------
SECTION PARAMETERS: EQA 50x4

D=50 mm
B=50 mm Ay=200 mm2 Az=200 mm2 A=392 mm2
t=4 mm Iy=91600 mm4 Iz=91600 mm4 Ix=2050 mm4
T=4 mm Wely=2523 mm3 Welz=2523 mm3
----------------------------------------------------------------------------------------------------------------------------------------
INTERNAL FORCES
Fc = 10.00 kN

----------------------------------------------------------------------------------------------------------------------------------------
CAPACITIES
Pc = 103.49 kN
Section class = 4
----------------------------------------------------------------------------------------------------------------------------------------
LATERAL BUCKLING PARAMETERS:

----------------------------------------------------------------------------------------------------------------------------------------
BUCKLING PARAMETERS:
About Y axis: About Z axis:

Ly = 1.18 m pey = 555.14 MPa Lz = 1.18 m pez = 555.14 MPa


Ley = 0.94 m Fiy = 481.04 MPa Lez = 0.94 m Fiz = 481.04 MPa
Lam,effy = 60.37 py = 200.44 MPa Lam,effz = 60.37 pz = 200.44 MPa
ny = 0.24 Pcy = 75.43 kN nz = 0.24 Pcz = 75.43 kN
----------------------------------------------------------------------------------------------------------------------------------------
VERIFICATION FORMULAS:

Date : 30/06/23 Page : 21


Robot Structural Analysis Professional 2023
Author: File: Structure.RTD
Address: Richmond Coach,Royston Project: K2198 Richmond Coach

Section check
Fc/Pc = 0.10 < 1.00 (4.8.3.2)
Member stability check
Fc/min(Pcy,Pcz) = 0.13 < 1.00 (4.8.3.3.1)
----------------------------------------------------------------------------------------------------------------------------------------
LIMIT DISPLACEMENTS
Deflections (LOCAL SYSTEM):

uy = 0 mm < uy max = L/200.00 = 6 mm Verified


Governing Load Case: 1 DL1
uz = 0 mm < uz max = L/200.00 = 6 mm Verified
Governing Load Case: 6 1DL+1LL+1WL (1+2+3)*1.00
Displacements (GLOBAL SYSTEM):

vx = 1 mm < vx max = L/300.00 = 4 mm Verified


Governing Load Case: 6 1DL+1LL+1WL (1+2+3)*1.00
vy = 0 mm < vy max = L/300.00 = 4 mm Verified
Governing Load Case: 1 DL1
----------------------------------------------------------------------------------------------------------------------------------------
Section OK !!!

STEEL DESIGN
----------------------------------------------------------------------------------------------------------------------------------------
CODE: British Standard BS 5950:2000
ANALYSIS TYPE: Member Verification
----------------------------------------------------------------------------------------------------------------------------------------
CODE GROUP:
MEMBER: 11 Simple member1_11 POINT: 1 COORDINATE: x = 0.00 L = 0.00 m
----------------------------------------------------------------------------------------------------------------------------------------
LOADS:
Governing Load Case: 4 1.2DL+1.2LL+1.2WL (1+2+3)*1.20
----------------------------------------------------------------------------------------------------------------------------------------
MATERIAL
STEEL 43-275 py = 275.00 MPa E = 205000.00 MPa
----------------------------------------------------------------------------------------------------------------------------------------
SECTION PARAMETERS: EQA 50x4

D=50 mm
B=50 mm Ay=200 mm2 Az=200 mm2 A=392 mm2
t=4 mm Iy=91600 mm4 Iz=91600 mm4 Ix=2050 mm4
T=4 mm Wely=2523 mm3 Welz=2523 mm3
----------------------------------------------------------------------------------------------------------------------------------------
INTERNAL FORCES
Ft = -6.04 kN

----------------------------------------------------------------------------------------------------------------------------------------
CAPACITIES
Pt = 107.80 kN
Section class = 1
----------------------------------------------------------------------------------------------------------------------------------------

Date : 30/06/23 Page : 22


Robot Structural Analysis Professional 2023
Author: File: Structure.RTD
Address: Richmond Coach,Royston Project: K2198 Richmond Coach

LATERAL BUCKLING PARAMETERS:

----------------------------------------------------------------------------------------------------------------------------------------
BUCKLING PARAMETERS:
About Y axis: About Z axis:

----------------------------------------------------------------------------------------------------------------------------------------
VERIFICATION FORMULAS:
Section check
Ft/Pt = 0.06 < 1.00 (4.8.2.2)
Member stability check
Not analyzed
----------------------------------------------------------------------------------------------------------------------------------------
LIMIT DISPLACEMENTS
Deflections (LOCAL SYSTEM):

uy = 0 mm < uy max = L/200.00 = 7 mm Verified


Governing Load Case: 1 DL1
uz = 0 mm < uz max = L/200.00 = 7 mm Verified
Governing Load Case: 6 1DL+1LL+1WL (1+2+3)*1.00
Displacements (GLOBAL SYSTEM):

vx = 0 mm < vx max = L/300.00 = 5 mm Verified


Governing Load Case: 6 1DL+1LL+1WL (1+2+3)*1.00
vy = 0 mm < vy max = L/300.00 = 5 mm Verified
Governing Load Case: 1 DL1
----------------------------------------------------------------------------------------------------------------------------------------
Section OK !!!

STEEL DESIGN
----------------------------------------------------------------------------------------------------------------------------------------
CODE: British Standard BS 5950:2000
ANALYSIS TYPE: Member Verification
----------------------------------------------------------------------------------------------------------------------------------------
CODE GROUP:
MEMBER: 12 Simple member1_12 POINT: 1 COORDINATE: x = 0.00 L = 0.00 m
----------------------------------------------------------------------------------------------------------------------------------------
LOADS:
Governing Load Case: 4 1.2DL+1.2LL+1.2WL (1+2+3)*1.20
----------------------------------------------------------------------------------------------------------------------------------------
MATERIAL
STEEL 43-275 py = 275.00 MPa E = 205000.00 MPa
----------------------------------------------------------------------------------------------------------------------------------------
SECTION PARAMETERS: EQA 50x4

D=50 mm
B=50 mm Ay=200 mm2 Az=200 mm2 A=392 mm2
t=4 mm Iy=91600 mm4 Iz=91600 mm4 Ix=2050 mm4
T=4 mm Wely=2523 mm3 Welz=2523 mm3
----------------------------------------------------------------------------------------------------------------------------------------
INTERNAL FORCES
Date : 30/06/23 Page : 23
Robot Structural Analysis Professional 2023
Author: File: Structure.RTD
Address: Richmond Coach,Royston Project: K2198 Richmond Coach

Fc = 4.92 kN

----------------------------------------------------------------------------------------------------------------------------------------
CAPACITIES
Pc = 103.49 kN
Section class = 4
----------------------------------------------------------------------------------------------------------------------------------------
LATERAL BUCKLING PARAMETERS:

----------------------------------------------------------------------------------------------------------------------------------------
BUCKLING PARAMETERS:
About Y axis: About Z axis:

Ly = 0.59 m pey = 2190.61 MPa Lz = 0.59 m pez = 2190.61 MPa


Ley = 0.47 m Fiy = 1312.54 MPa Lez = 0.47 m Fiz = 1312.54 MPa
Lam,effy = 30.39 py = 254.08 MPa Lam,effz = 30.39 pz = 254.08 MPa
ny = 0.07 Pcy = 95.61 kN nz = 0.07 Pcz = 95.61 kN
----------------------------------------------------------------------------------------------------------------------------------------
VERIFICATION FORMULAS:
Section check
Fc/Pc = 0.05 < 1.00 (4.8.3.2)
Member stability check
Fc/min(Pcy,Pcz) = 0.05 < 1.00 (4.8.3.3.1)
----------------------------------------------------------------------------------------------------------------------------------------
LIMIT DISPLACEMENTS
Deflections (LOCAL SYSTEM):

uy = 0 mm < uy max = L/200.00 = 3 mm Verified


Governing Load Case: 1 DL1
uz = 0 mm < uz max = L/200.00 = 3 mm Verified
Governing Load Case: 6 1DL+1LL+1WL (1+2+3)*1.00
Displacements (GLOBAL SYSTEM):

vx = 0 mm < vx max = L/300.00 = 2 mm Verified


Governing Load Case: 6 1DL+1LL+1WL (1+2+3)*1.00
vy = 0 mm < vy max = L/300.00 = 2 mm Verified
Governing Load Case: 1 DL1
----------------------------------------------------------------------------------------------------------------------------------------
Section OK !!!

STEEL DESIGN
----------------------------------------------------------------------------------------------------------------------------------------
CODE: British Standard BS 5950:2000
ANALYSIS TYPE: Member Verification
----------------------------------------------------------------------------------------------------------------------------------------
CODE GROUP:
MEMBER: 13 POINT: 1 COORDINATE: x = 0.00 L = 0.00 m
----------------------------------------------------------------------------------------------------------------------------------------
LOADS:
Governing Load Case: 4 1.2DL+1.2LL+1.2WL (1+2+3)*1.20
----------------------------------------------------------------------------------------------------------------------------------------

Date : 30/06/23 Page : 24


Robot Structural Analysis Professional 2023
Author: File: Structure.RTD
Address: Richmond Coach,Royston Project: K2198 Richmond Coach

MATERIAL
STEEL 43-275 py = 275.00 MPa E = 205000.00 MPa
----------------------------------------------------------------------------------------------------------------------------------------
SECTION PARAMETERS: EQA 50x4

D=50 mm
B=50 mm Ay=200 mm2 Az=200 mm2 A=392 mm2
t=4 mm Iy=91600 mm4 Iz=91600 mm4 Ix=2050 mm4
T=4 mm Wely=2523 mm3 Welz=2523 mm3
----------------------------------------------------------------------------------------------------------------------------------------
INTERNAL FORCES
Ft = -8.57 kN

----------------------------------------------------------------------------------------------------------------------------------------
CAPACITIES
Pt = 107.80 kN
Section class = 1
----------------------------------------------------------------------------------------------------------------------------------------
LATERAL BUCKLING PARAMETERS:

----------------------------------------------------------------------------------------------------------------------------------------
BUCKLING PARAMETERS:
About Y axis: About Z axis:

----------------------------------------------------------------------------------------------------------------------------------------
VERIFICATION FORMULAS:
Section check
Ft/Pt = 0.08 < 1.00 (4.8.2.2)
Member stability check
Not analyzed
----------------------------------------------------------------------------------------------------------------------------------------
LIMIT DISPLACEMENTS
Deflections (LOCAL SYSTEM):

uy = 0 mm < uy max = L/200.00 = 7 mm Verified


Governing Load Case: 1 DL1
uz = 0 mm < uz max = L/200.00 = 7 mm Verified
Governing Load Case: 6 1DL+1LL+1WL (1+2+3)*1.00
Displacements (GLOBAL SYSTEM):

vx = 0 mm < vx max = L/300.00 = 5 mm Verified


Governing Load Case: 6 1DL+1LL+1WL (1+2+3)*1.00
vy = 0 mm < vy max = L/300.00 = 5 mm Verified
Governing Load Case: 1 DL1
----------------------------------------------------------------------------------------------------------------------------------------
Section OK !!!

STEEL DESIGN
----------------------------------------------------------------------------------------------------------------------------------------
CODE: British Standard BS 5950:2000
Date : 30/06/23 Page : 25
Robot Structural Analysis Professional 2023
Author: File: Structure.RTD
Address: Richmond Coach,Royston Project: K2198 Richmond Coach

ANALYSIS TYPE: Member Verification


----------------------------------------------------------------------------------------------------------------------------------------
CODE GROUP:
MEMBER: 14 Simple member1_14 POINT: 1 COORDINATE: x = 0.00 L = 0.00 m
----------------------------------------------------------------------------------------------------------------------------------------
LOADS:
Governing Load Case: 4 1.2DL+1.2LL+1.2WL (1+2+3)*1.20
----------------------------------------------------------------------------------------------------------------------------------------
MATERIAL
STEEL 43-275 py = 275.00 MPa E = 205000.00 MPa
----------------------------------------------------------------------------------------------------------------------------------------
SECTION PARAMETERS: EQA 50x4

D=50 mm
B=50 mm Ay=200 mm2 Az=200 mm2 A=392 mm2
t=4 mm Iy=91600 mm4 Iz=91600 mm4 Ix=2050 mm4
T=4 mm Wely=2523 mm3 Welz=2523 mm3
----------------------------------------------------------------------------------------------------------------------------------------
INTERNAL FORCES
Ft = -2.66 kN

----------------------------------------------------------------------------------------------------------------------------------------
CAPACITIES
Pt = 107.80 kN
Section class = 1
----------------------------------------------------------------------------------------------------------------------------------------
LATERAL BUCKLING PARAMETERS:

----------------------------------------------------------------------------------------------------------------------------------------
BUCKLING PARAMETERS:
About Y axis: About Z axis:

----------------------------------------------------------------------------------------------------------------------------------------
VERIFICATION FORMULAS:
Section check
Ft/Pt = 0.02 < 1.00 (4.8.2.2)
Member stability check
Not analyzed
----------------------------------------------------------------------------------------------------------------------------------------
LIMIT DISPLACEMENTS
Deflections (LOCAL SYSTEM):

uy = 0 mm < uy max = L/200.00 = 7 mm Verified


Governing Load Case: 1 DL1
uz = 0 mm < uz max = L/200.00 = 7 mm Verified
Governing Load Case: 6 1DL+1LL+1WL (1+2+3)*1.00
Displacements (GLOBAL SYSTEM):

vx = 0 mm < vx max = L/300.00 = 5 mm Verified


Governing Load Case: 6 1DL+1LL+1WL (1+2+3)*1.00
vy = 0 mm < vy max = L/300.00 = 5 mm Verified
Governing Load Case: 1 DL1
----------------------------------------------------------------------------------------------------------------------------------------
Date : 30/06/23 Page : 26
Robot Structural Analysis Professional 2023
Author: File: Structure.RTD
Address: Richmond Coach,Royston Project: K2198 Richmond Coach

Section OK !!!

STEEL DESIGN
----------------------------------------------------------------------------------------------------------------------------------------
CODE: British Standard BS 5950:2000
ANALYSIS TYPE: Member Verification
----------------------------------------------------------------------------------------------------------------------------------------
CODE GROUP:
MEMBER: 15 Simple member1_15 POINT: 1 COORDINATE: x = 0.00 L = 0.00 m
----------------------------------------------------------------------------------------------------------------------------------------
LOADS:
Governing Load Case: 4 1.2DL+1.2LL+1.2WL (1+2+3)*1.20
----------------------------------------------------------------------------------------------------------------------------------------
MATERIAL
STEEL 43-275 py = 275.00 MPa E = 205000.00 MPa
----------------------------------------------------------------------------------------------------------------------------------------
SECTION PARAMETERS: EQA 50x4

D=50 mm
B=50 mm Ay=200 mm2 Az=200 mm2 A=392 mm2
t=4 mm Iy=91600 mm4 Iz=91600 mm4 Ix=2050 mm4
T=4 mm Wely=2523 mm3 Welz=2523 mm3
----------------------------------------------------------------------------------------------------------------------------------------
INTERNAL FORCES
Fc = 9.24 kN

----------------------------------------------------------------------------------------------------------------------------------------
CAPACITIES
Pc = 103.49 kN
Section class = 4
----------------------------------------------------------------------------------------------------------------------------------------
LATERAL BUCKLING PARAMETERS:

----------------------------------------------------------------------------------------------------------------------------------------
BUCKLING PARAMETERS:
About Y axis: About Z axis:

Ly = 3.40 m pey = 66.57 MPa Lz = 3.40 m pez = 66.57 MPa


Ley = 2.72 m Fiy = 199.56 MPa Lez = 2.72 m Fiz = 199.56 MPa
Lam,effy = 174.34 py = 52.87 MPa Lam,effz = 174.34 pz = 52.87 MPa
ny = 0.86 Pcy = 19.90 kN nz = 0.86 Pcz = 19.90 kN
----------------------------------------------------------------------------------------------------------------------------------------
VERIFICATION FORMULAS:
Section check
Fc/Pc = 0.09 < 1.00 (4.8.3.2)
Member stability check
Fc/min(Pcy,Pcz) = 0.46 < 1.00 (4.8.3.3.1)
----------------------------------------------------------------------------------------------------------------------------------------
LIMIT DISPLACEMENTS

Date : 30/06/23 Page : 27


Robot Structural Analysis Professional 2023
Author: File: Structure.RTD
Address: Richmond Coach,Royston Project: K2198 Richmond Coach

Deflections (LOCAL SYSTEM):

uy = 0 mm < uy max = L/200.00 = 17 mm Verified


Governing Load Case: 1 DL1
uz = 0 mm < uz max = L/200.00 = 17 mm Verified
Governing Load Case: 6 1DL+1LL+1WL (1+2+3)*1.00
Displacements (GLOBAL SYSTEM):

vx = 0 mm < vx max = L/300.00 = 11 mm Verified


Governing Load Case: 6 1DL+1LL+1WL (1+2+3)*1.00
vy = 0 mm < vy max = L/300.00 = 11 mm Verified
Governing Load Case: 1 DL1
----------------------------------------------------------------------------------------------------------------------------------------
Section OK !!!

STEEL DESIGN
----------------------------------------------------------------------------------------------------------------------------------------
CODE: British Standard BS 5950:2000
ANALYSIS TYPE: Member Verification
----------------------------------------------------------------------------------------------------------------------------------------
CODE GROUP:
MEMBER: 16 Simple member1_16 POINT: 1 COORDINATE: x = 0.00 L = 0.00 m
----------------------------------------------------------------------------------------------------------------------------------------
LOADS:
Governing Load Case: 4 1.2DL+1.2LL+1.2WL (1+2+3)*1.20
----------------------------------------------------------------------------------------------------------------------------------------
MATERIAL
STEEL 43-275 py = 275.00 MPa E = 205000.00 MPa
----------------------------------------------------------------------------------------------------------------------------------------
SECTION PARAMETERS: EQA 50x4

D=50 mm
B=50 mm Ay=200 mm2 Az=200 mm2 A=392 mm2
t=4 mm Iy=91600 mm4 Iz=91600 mm4 Ix=2050 mm4
T=4 mm Wely=2523 mm3 Welz=2523 mm3
----------------------------------------------------------------------------------------------------------------------------------------
INTERNAL FORCES
Ft = -2.66 kN

----------------------------------------------------------------------------------------------------------------------------------------
CAPACITIES
Pt = 107.80 kN
Section class = 1
----------------------------------------------------------------------------------------------------------------------------------------
LATERAL BUCKLING PARAMETERS:

----------------------------------------------------------------------------------------------------------------------------------------
BUCKLING PARAMETERS:
About Y axis: About Z axis:

Date : 30/06/23 Page : 28


Robot Structural Analysis Professional 2023
Author: File: Structure.RTD
Address: Richmond Coach,Royston Project: K2198 Richmond Coach

----------------------------------------------------------------------------------------------------------------------------------------
VERIFICATION FORMULAS:
Section check
Ft/Pt = 0.02 < 1.00 (4.8.2.2)
Member stability check
Not analyzed
----------------------------------------------------------------------------------------------------------------------------------------
LIMIT DISPLACEMENTS
Deflections (LOCAL SYSTEM):

uy = 0 mm < uy max = L/200.00 = 7 mm Verified


Governing Load Case: 1 DL1
uz = 0 mm < uz max = L/200.00 = 7 mm Verified
Governing Load Case: 6 1DL+1LL+1WL (1+2+3)*1.00
Displacements (GLOBAL SYSTEM):

vx = 0 mm < vx max = L/300.00 = 5 mm Verified


Governing Load Case: 6 1DL+1LL+1WL (1+2+3)*1.00
vy = 0 mm < vy max = L/300.00 = 5 mm Verified
Governing Load Case: 1 DL1
----------------------------------------------------------------------------------------------------------------------------------------
Section OK !!!

STEEL DESIGN
----------------------------------------------------------------------------------------------------------------------------------------
CODE: British Standard BS 5950:2000
ANALYSIS TYPE: Member Verification
----------------------------------------------------------------------------------------------------------------------------------------
CODE GROUP:
MEMBER: 17 Simple member1_17 POINT: 1 COORDINATE: x = 0.00 L = 0.00 m
----------------------------------------------------------------------------------------------------------------------------------------
LOADS:
Governing Load Case: 4 1.2DL+1.2LL+1.2WL (1+2+3)*1.20
----------------------------------------------------------------------------------------------------------------------------------------
MATERIAL
STEEL 43-275 py = 275.00 MPa E = 205000.00 MPa
----------------------------------------------------------------------------------------------------------------------------------------
SECTION PARAMETERS: EQA 50x4

D=50 mm
B=50 mm Ay=200 mm2 Az=200 mm2 A=392 mm2
t=4 mm Iy=91600 mm4 Iz=91600 mm4 Ix=2050 mm4
T=4 mm Wely=2523 mm3 Welz=2523 mm3
----------------------------------------------------------------------------------------------------------------------------------------
INTERNAL FORCES
Ft = -8.57 kN

----------------------------------------------------------------------------------------------------------------------------------------
CAPACITIES
Pt = 107.80 kN
Section class = 1

Date : 30/06/23 Page : 29


Robot Structural Analysis Professional 2023
Author: File: Structure.RTD
Address: Richmond Coach,Royston Project: K2198 Richmond Coach

----------------------------------------------------------------------------------------------------------------------------------------
LATERAL BUCKLING PARAMETERS:

----------------------------------------------------------------------------------------------------------------------------------------
BUCKLING PARAMETERS:
About Y axis: About Z axis:

----------------------------------------------------------------------------------------------------------------------------------------
VERIFICATION FORMULAS:
Section check
Ft/Pt = 0.08 < 1.00 (4.8.2.2)
Member stability check
Not analyzed
----------------------------------------------------------------------------------------------------------------------------------------
LIMIT DISPLACEMENTS
Deflections (LOCAL SYSTEM):

uy = 0 mm < uy max = L/200.00 = 7 mm Verified


Governing Load Case: 1 DL1
uz = 0 mm < uz max = L/200.00 = 7 mm Verified
Governing Load Case: 6 1DL+1LL+1WL (1+2+3)*1.00
Displacements (GLOBAL SYSTEM):

vx = 0 mm < vx max = L/300.00 = 5 mm Verified


Governing Load Case: 6 1DL+1LL+1WL (1+2+3)*1.00
vy = 0 mm < vy max = L/300.00 = 5 mm Verified
Governing Load Case: 1 DL1
----------------------------------------------------------------------------------------------------------------------------------------
Section OK !!!

STEEL DESIGN
----------------------------------------------------------------------------------------------------------------------------------------
CODE: British Standard BS 5950:2000
ANALYSIS TYPE: Member Verification
----------------------------------------------------------------------------------------------------------------------------------------
CODE GROUP:
MEMBER: 18 Simple member1_18 POINT: 1 COORDINATE: x = 0.00 L = 0.00 m
----------------------------------------------------------------------------------------------------------------------------------------
LOADS:
Governing Load Case: 4 1.2DL+1.2LL+1.2WL (1+2+3)*1.20
----------------------------------------------------------------------------------------------------------------------------------------
MATERIAL
STEEL 43-275 py = 275.00 MPa E = 205000.00 MPa
----------------------------------------------------------------------------------------------------------------------------------------
SECTION PARAMETERS: EQA 50x4

D=50 mm
B=50 mm Ay=200 mm2 Az=200 mm2 A=392 mm2
t=4 mm Iy=91600 mm4 Iz=91600 mm4 Ix=2050 mm4
T=4 mm Wely=2523 mm3 Welz=2523 mm3
----------------------------------------------------------------------------------------------------------------------------------------
Date : 30/06/23 Page : 30
Robot Structural Analysis Professional 2023
Author: File: Structure.RTD
Address: Richmond Coach,Royston Project: K2198 Richmond Coach

INTERNAL FORCES
Fc = 52.09 kN

----------------------------------------------------------------------------------------------------------------------------------------
CAPACITIES
Pc = 103.49 kN
Section class = 4
----------------------------------------------------------------------------------------------------------------------------------------
LATERAL BUCKLING PARAMETERS:

----------------------------------------------------------------------------------------------------------------------------------------
BUCKLING PARAMETERS:
About Y axis: About Z axis:

Ly = 1.24 m pey = 496.91 MPa Lz = 1.24 m pez = 496.91 MPa


Ley = 1.00 m Fiy = 449.71 MPa Lez = 1.00 m Fiz = 449.71 MPa
Lam,effy = 63.81 py = 193.61 MPa Lam,effz = 63.81 pz = 193.61 MPa
ny = 0.26 Pcy = 72.86 kN nz = 0.26 Pcz = 72.86 kN
----------------------------------------------------------------------------------------------------------------------------------------
VERIFICATION FORMULAS:
Section check
Fc/Pc = 0.50 < 1.00 (4.8.3.2)
Member stability check
Fc/min(Pcy,Pcz) = 0.71 < 1.00 (4.8.3.3.1)
----------------------------------------------------------------------------------------------------------------------------------------
LIMIT DISPLACEMENTS
Deflections (LOCAL SYSTEM):

uy = 0 mm < uy max = L/200.00 = 6 mm Verified


Governing Load Case: 1 DL1
uz = 0 mm < uz max = L/200.00 = 6 mm Verified
Governing Load Case: 6 1DL+1LL+1WL (1+2+3)*1.00
Displacements (GLOBAL SYSTEM):

vx = 1 mm < vx max = L/300.00 = 4 mm Verified


Governing Load Case: 6 1DL+1LL+1WL (1+2+3)*1.00
vy = 0 mm < vy max = L/300.00 = 4 mm Verified
Governing Load Case: 1 DL1
----------------------------------------------------------------------------------------------------------------------------------------
Section OK !!!

STEEL DESIGN
----------------------------------------------------------------------------------------------------------------------------------------
CODE: British Standard BS 5950:2000
ANALYSIS TYPE: Member Verification
----------------------------------------------------------------------------------------------------------------------------------------
CODE GROUP:
MEMBER: 19 Simple member1_19 POINT: 1 COORDINATE: x = 0.00 L = 0.00 m
----------------------------------------------------------------------------------------------------------------------------------------
LOADS:
Governing Load Case: 4 1.2DL+1.2LL+1.2WL (1+2+3)*1.20

Date : 30/06/23 Page : 31


Robot Structural Analysis Professional 2023
Author: File: Structure.RTD
Address: Richmond Coach,Royston Project: K2198 Richmond Coach

----------------------------------------------------------------------------------------------------------------------------------------
MATERIAL
STEEL 43-275 py = 275.00 MPa E = 205000.00 MPa
----------------------------------------------------------------------------------------------------------------------------------------
SECTION PARAMETERS: EQA 50x4

D=50 mm
B=50 mm Ay=200 mm2 Az=200 mm2 A=392 mm2
t=4 mm Iy=91600 mm4 Iz=91600 mm4 Ix=2050 mm4
T=4 mm Wely=2523 mm3 Welz=2523 mm3
----------------------------------------------------------------------------------------------------------------------------------------
INTERNAL FORCES
Fc = 49.61 kN

----------------------------------------------------------------------------------------------------------------------------------------
CAPACITIES
Pc = 103.49 kN
Section class = 4
----------------------------------------------------------------------------------------------------------------------------------------
LATERAL BUCKLING PARAMETERS:

----------------------------------------------------------------------------------------------------------------------------------------
BUCKLING PARAMETERS:
About Y axis: About Z axis:

Ly = 1.26 m pey = 487.80 MPa Lz = 1.26 m pez = 487.80 MPa


Ley = 1.00 m Fiy = 444.78 MPa Lez = 1.00 m Fiz = 444.78 MPa
Lam,effy = 64.40 py = 192.42 MPa Lam,effz = 64.40 pz = 192.42 MPa
ny = 0.26 Pcy = 72.41 kN nz = 0.26 Pcz = 72.41 kN
----------------------------------------------------------------------------------------------------------------------------------------
VERIFICATION FORMULAS:
Section check
Fc/Pc = 0.48 < 1.00 (4.8.3.2)
Member stability check
Fc/min(Pcy,Pcz) = 0.69 < 1.00 (4.8.3.3.1)
----------------------------------------------------------------------------------------------------------------------------------------
LIMIT DISPLACEMENTS
Deflections (LOCAL SYSTEM):

uy = 0 mm < uy max = L/200.00 = 6 mm Verified


Governing Load Case: 1 DL1
uz = 0 mm < uz max = L/200.00 = 6 mm Verified
Governing Load Case: 6 1DL+1LL+1WL (1+2+3)*1.00
Displacements (GLOBAL SYSTEM):

vx = 0 mm < vx max = L/300.00 = 4 mm Verified


Governing Load Case: 6 1DL+1LL+1WL (1+2+3)*1.00
vy = 0 mm < vy max = L/300.00 = 4 mm Verified
Governing Load Case: 1 DL1
----------------------------------------------------------------------------------------------------------------------------------------
Section OK !!!

Date : 30/06/23 Page : 32


Robot Structural Analysis Professional 2023
Author: File: Structure.RTD
Address: Richmond Coach,Royston Project: K2198 Richmond Coach

STEEL DESIGN
----------------------------------------------------------------------------------------------------------------------------------------
CODE: British Standard BS 5950:2000
ANALYSIS TYPE: Member Verification
----------------------------------------------------------------------------------------------------------------------------------------
CODE GROUP:
MEMBER: 20 Simple member1_20 POINT: 1 COORDINATE: x = 0.00 L = 0.00 m
----------------------------------------------------------------------------------------------------------------------------------------
LOADS:
Governing Load Case: 4 1.2DL+1.2LL+1.2WL (1+2+3)*1.20
----------------------------------------------------------------------------------------------------------------------------------------
MATERIAL
STEEL 43-275 py = 275.00 MPa E = 205000.00 MPa
----------------------------------------------------------------------------------------------------------------------------------------
SECTION PARAMETERS: EQA 50x4

D=50 mm
B=50 mm Ay=200 mm2 Az=200 mm2 A=392 mm2
t=4 mm Iy=91600 mm4 Iz=91600 mm4 Ix=2050 mm4
T=4 mm Wely=2523 mm3 Welz=2523 mm3
----------------------------------------------------------------------------------------------------------------------------------------
INTERNAL FORCES
Fc = 47.26 kN

----------------------------------------------------------------------------------------------------------------------------------------
CAPACITIES
Pc = 103.49 kN
Section class = 4
----------------------------------------------------------------------------------------------------------------------------------------
LATERAL BUCKLING PARAMETERS:

----------------------------------------------------------------------------------------------------------------------------------------
BUCKLING PARAMETERS:
About Y axis: About Z axis:

Ly = 1.18 m pey = 554.70 MPa Lz = 1.18 m pez = 554.70 MPa


Ley = 0.94 m Fiy = 480.81 MPa Lez = 0.94 m Fiz = 480.81 MPa
Lam,effy = 60.39 py = 200.39 MPa Lam,effz = 60.39 pz = 200.39 MPa
ny = 0.24 Pcy = 75.41 kN nz = 0.24 Pcz = 75.41 kN
----------------------------------------------------------------------------------------------------------------------------------------
VERIFICATION FORMULAS:
Section check
Fc/Pc = 0.46 < 1.00 (4.8.3.2)
Member stability check
Fc/min(Pcy,Pcz) = 0.63 < 1.00 (4.8.3.3.1)
----------------------------------------------------------------------------------------------------------------------------------------
LIMIT DISPLACEMENTS
Deflections (LOCAL SYSTEM):

uy = 0 mm < uy max = L/200.00 = 6 mm Verified


Governing Load Case: 1 DL1
uz = 0 mm < uz max = L/200.00 = 6 mm Verified
Date : 30/06/23 Page : 33
Robot Structural Analysis Professional 2023
Author: File: Structure.RTD
Address: Richmond Coach,Royston Project: K2198 Richmond Coach

Governing Load Case: 6 1DL+1LL+1WL (1+2+3)*1.00


Displacements (GLOBAL SYSTEM):

vx = 0 mm < vx max = L/300.00 = 4 mm Verified


Governing Load Case: 6 1DL+1LL+1WL (1+2+3)*1.00
vy = 0 mm < vy max = L/300.00 = 4 mm Verified
Governing Load Case: 1 DL1
----------------------------------------------------------------------------------------------------------------------------------------
Section OK !!!

STEEL DESIGN
----------------------------------------------------------------------------------------------------------------------------------------
CODE: British Standard BS 5950:2000
ANALYSIS TYPE: Member Verification
----------------------------------------------------------------------------------------------------------------------------------------
CODE GROUP:
MEMBER: 21 Simple member1_21 POINT: 1 COORDINATE: x = 0.00 L = 0.00 m
----------------------------------------------------------------------------------------------------------------------------------------
LOADS:
Governing Load Case: 4 1.2DL+1.2LL+1.2WL (1+2+3)*1.20
----------------------------------------------------------------------------------------------------------------------------------------
MATERIAL
STEEL 43-275 py = 275.00 MPa E = 205000.00 MPa
----------------------------------------------------------------------------------------------------------------------------------------
SECTION PARAMETERS: EQA 50x4

D=50 mm
B=50 mm Ay=200 mm2 Az=200 mm2 A=392 mm2
t=4 mm Iy=91600 mm4 Iz=91600 mm4 Ix=2050 mm4
T=4 mm Wely=2523 mm3 Welz=2523 mm3
----------------------------------------------------------------------------------------------------------------------------------------
INTERNAL FORCES
Fc = 44.40 kN

----------------------------------------------------------------------------------------------------------------------------------------
CAPACITIES
Pc = 103.49 kN
Section class = 4
----------------------------------------------------------------------------------------------------------------------------------------
LATERAL BUCKLING PARAMETERS:

----------------------------------------------------------------------------------------------------------------------------------------
BUCKLING PARAMETERS:
About Y axis: About Z axis:

Ly = 1.28 m pey = 469.00 MPa Lz = 1.28 m pez = 469.00 MPa


Ley = 1.02 m Fiy = 434.59 MPa Lez = 1.02 m Fiz = 434.59 MPa
Lam,effy = 65.68 py = 189.86 MPa Lam,effz = 65.68 pz = 189.86 MPa
ny = 0.27 Pcy = 71.45 kN nz = 0.27 Pcz = 71.45 kN
----------------------------------------------------------------------------------------------------------------------------------------

Date : 30/06/23 Page : 34


Robot Structural Analysis Professional 2023
Author: File: Structure.RTD
Address: Richmond Coach,Royston Project: K2198 Richmond Coach

VERIFICATION FORMULAS:
Section check
Fc/Pc = 0.43 < 1.00 (4.8.3.2)
Member stability check
Fc/min(Pcy,Pcz) = 0.62 < 1.00 (4.8.3.3.1)
----------------------------------------------------------------------------------------------------------------------------------------
LIMIT DISPLACEMENTS
Deflections (LOCAL SYSTEM):

uy = 0 mm < uy max = L/200.00 = 6 mm Verified


Governing Load Case: 1 DL1
uz = 0 mm < uz max = L/200.00 = 6 mm Verified
Governing Load Case: 6 1DL+1LL+1WL (1+2+3)*1.00
Displacements (GLOBAL SYSTEM):

vx = 1 mm < vx max = L/300.00 = 4 mm Verified


Governing Load Case: 6 1DL+1LL+1WL (1+2+3)*1.00
vy = 0 mm < vy max = L/300.00 = 4 mm Verified
Governing Load Case: 1 DL1
----------------------------------------------------------------------------------------------------------------------------------------
Section OK !!!

STEEL DESIGN
----------------------------------------------------------------------------------------------------------------------------------------
CODE: British Standard BS 5950:2000
ANALYSIS TYPE: Member Verification
----------------------------------------------------------------------------------------------------------------------------------------
CODE GROUP:
MEMBER: 22 POINT: 1 COORDINATE: x = 0.00 L = 0.00 m
----------------------------------------------------------------------------------------------------------------------------------------
LOADS:
Governing Load Case: 4 1.2DL+1.2LL+1.2WL (1+2+3)*1.20
----------------------------------------------------------------------------------------------------------------------------------------
MATERIAL
STEEL 43-275 py = 275.00 MPa E = 205000.00 MPa
----------------------------------------------------------------------------------------------------------------------------------------
SECTION PARAMETERS: EQA 50x4

D=50 mm
B=50 mm Ay=200 mm2 Az=200 mm2 A=392 mm2
t=4 mm Iy=91600 mm4 Iz=91600 mm4 Ix=2050 mm4
T=4 mm Wely=2523 mm3 Welz=2523 mm3
----------------------------------------------------------------------------------------------------------------------------------------
INTERNAL FORCES
Fc = 52.09 kN

----------------------------------------------------------------------------------------------------------------------------------------
CAPACITIES
Pc = 103.49 kN
Section class = 4
----------------------------------------------------------------------------------------------------------------------------------------

Date : 30/06/23 Page : 35


Robot Structural Analysis Professional 2023
Author: File: Structure.RTD
Address: Richmond Coach,Royston Project: K2198 Richmond Coach

LATERAL BUCKLING PARAMETERS:

----------------------------------------------------------------------------------------------------------------------------------------
BUCKLING PARAMETERS:
About Y axis: About Z axis:

Ly = 1.24 m pey = 496.91 MPa Lz = 1.24 m pez = 496.91 MPa


Ley = 1.00 m Fiy = 449.71 MPa Lez = 1.00 m Fiz = 449.71 MPa
Lam,effy = 63.81 py = 193.61 MPa Lam,effz = 63.81 pz = 193.61 MPa
ny = 0.26 Pcy = 72.86 kN nz = 0.26 Pcz = 72.86 kN
----------------------------------------------------------------------------------------------------------------------------------------
VERIFICATION FORMULAS:
Section check
Fc/Pc = 0.50 < 1.00 (4.8.3.2)
Member stability check
Fc/min(Pcy,Pcz) = 0.71 < 1.00 (4.8.3.3.1)
----------------------------------------------------------------------------------------------------------------------------------------
LIMIT DISPLACEMENTS
Deflections (LOCAL SYSTEM):

uy = 0 mm < uy max = L/200.00 = 6 mm Verified


Governing Load Case: 1 DL1
uz = 0 mm < uz max = L/200.00 = 6 mm Verified
Governing Load Case: 6 1DL+1LL+1WL (1+2+3)*1.00
Displacements (GLOBAL SYSTEM):

vx = 1 mm < vx max = L/300.00 = 4 mm Verified


Governing Load Case: 6 1DL+1LL+1WL (1+2+3)*1.00
vy = 0 mm < vy max = L/300.00 = 4 mm Verified
Governing Load Case: 1 DL1
----------------------------------------------------------------------------------------------------------------------------------------
Section OK !!!

STEEL DESIGN
----------------------------------------------------------------------------------------------------------------------------------------
CODE: British Standard BS 5950:2000
ANALYSIS TYPE: Member Verification
----------------------------------------------------------------------------------------------------------------------------------------
CODE GROUP:
MEMBER: 23 Simple member1_23 POINT: 1 COORDINATE: x = 0.00 L = 0.00 m
----------------------------------------------------------------------------------------------------------------------------------------
LOADS:
Governing Load Case: 4 1.2DL+1.2LL+1.2WL (1+2+3)*1.20
----------------------------------------------------------------------------------------------------------------------------------------
MATERIAL
STEEL 43-275 py = 275.00 MPa E = 205000.00 MPa
----------------------------------------------------------------------------------------------------------------------------------------
SECTION PARAMETERS: EQA 50x4

D=50 mm
B=50 mm Ay=200 mm2 Az=200 mm2 A=392 mm2
Date : 30/06/23 Page : 36
Robot Structural Analysis Professional 2023
Author: File: Structure.RTD
Address: Richmond Coach,Royston Project: K2198 Richmond Coach

t=4 mm Iy=91600 mm4 Iz=91600 mm4 Ix=2050 mm4


T=4 mm Wely=2523 mm3 Welz=2523 mm3
----------------------------------------------------------------------------------------------------------------------------------------
INTERNAL FORCES
Fc = 49.61 kN

----------------------------------------------------------------------------------------------------------------------------------------
CAPACITIES
Pc = 103.49 kN
Section class = 4
----------------------------------------------------------------------------------------------------------------------------------------
LATERAL BUCKLING PARAMETERS:

----------------------------------------------------------------------------------------------------------------------------------------
BUCKLING PARAMETERS:
About Y axis: About Z axis:

Ly = 1.26 m pey = 487.80 MPa Lz = 1.26 m pez = 487.80 MPa


Ley = 1.00 m Fiy = 444.78 MPa Lez = 1.00 m Fiz = 444.78 MPa
Lam,effy = 64.40 py = 192.42 MPa Lam,effz = 64.40 pz = 192.42 MPa
ny = 0.26 Pcy = 72.41 kN nz = 0.26 Pcz = 72.41 kN
----------------------------------------------------------------------------------------------------------------------------------------
VERIFICATION FORMULAS:
Section check
Fc/Pc = 0.48 < 1.00 (4.8.3.2)
Member stability check
Fc/min(Pcy,Pcz) = 0.69 < 1.00 (4.8.3.3.1)
----------------------------------------------------------------------------------------------------------------------------------------
LIMIT DISPLACEMENTS
Deflections (LOCAL SYSTEM):

uy = 0 mm < uy max = L/200.00 = 6 mm Verified


Governing Load Case: 1 DL1
uz = 0 mm < uz max = L/200.00 = 6 mm Verified
Governing Load Case: 6 1DL+1LL+1WL (1+2+3)*1.00
Displacements (GLOBAL SYSTEM):

vx = 0 mm < vx max = L/300.00 = 4 mm Verified


Governing Load Case: 6 1DL+1LL+1WL (1+2+3)*1.00
vy = 0 mm < vy max = L/300.00 = 4 mm Verified
Governing Load Case: 1 DL1
----------------------------------------------------------------------------------------------------------------------------------------
Section OK !!!

STEEL DESIGN
----------------------------------------------------------------------------------------------------------------------------------------
CODE: British Standard BS 5950:2000
ANALYSIS TYPE: Member Verification
----------------------------------------------------------------------------------------------------------------------------------------
CODE GROUP:
MEMBER: 24 Simple member1_24 POINT: 1 COORDINATE: x = 0.00 L = 0.00 m

Date : 30/06/23 Page : 37


Robot Structural Analysis Professional 2023
Author: File: Structure.RTD
Address: Richmond Coach,Royston Project: K2198 Richmond Coach

----------------------------------------------------------------------------------------------------------------------------------------
LOADS:
Governing Load Case: 4 1.2DL+1.2LL+1.2WL (1+2+3)*1.20
----------------------------------------------------------------------------------------------------------------------------------------
MATERIAL
STEEL 43-275 py = 275.00 MPa E = 205000.00 MPa
----------------------------------------------------------------------------------------------------------------------------------------
SECTION PARAMETERS: EQA 50x4

D=50 mm
B=50 mm Ay=200 mm2 Az=200 mm2 A=392 mm2
t=4 mm Iy=91600 mm4 Iz=91600 mm4 Ix=2050 mm4
T=4 mm Wely=2523 mm3 Welz=2523 mm3
----------------------------------------------------------------------------------------------------------------------------------------
INTERNAL FORCES
Fc = 47.26 kN

----------------------------------------------------------------------------------------------------------------------------------------
CAPACITIES
Pc = 103.49 kN
Section class = 4
----------------------------------------------------------------------------------------------------------------------------------------
LATERAL BUCKLING PARAMETERS:

----------------------------------------------------------------------------------------------------------------------------------------
BUCKLING PARAMETERS:
About Y axis: About Z axis:

Ly = 1.18 m pey = 554.70 MPa Lz = 1.18 m pez = 554.70 MPa


Ley = 0.94 m Fiy = 480.81 MPa Lez = 0.94 m Fiz = 480.81 MPa
Lam,effy = 60.39 py = 200.39 MPa Lam,effz = 60.39 pz = 200.39 MPa
ny = 0.24 Pcy = 75.41 kN nz = 0.24 Pcz = 75.41 kN
----------------------------------------------------------------------------------------------------------------------------------------
VERIFICATION FORMULAS:
Section check
Fc/Pc = 0.46 < 1.00 (4.8.3.2)
Member stability check
Fc/min(Pcy,Pcz) = 0.63 < 1.00 (4.8.3.3.1)
----------------------------------------------------------------------------------------------------------------------------------------
LIMIT DISPLACEMENTS
Deflections (LOCAL SYSTEM):

uy = 0 mm < uy max = L/200.00 = 6 mm Verified


Governing Load Case: 1 DL1
uz = 0 mm < uz max = L/200.00 = 6 mm Verified
Governing Load Case: 6 1DL+1LL+1WL (1+2+3)*1.00
Displacements (GLOBAL SYSTEM):

vx = 0 mm < vx max = L/300.00 = 4 mm Verified


Governing Load Case: 6 1DL+1LL+1WL (1+2+3)*1.00
vy = 0 mm < vy max = L/300.00 = 4 mm Verified
Governing Load Case: 1 DL1
----------------------------------------------------------------------------------------------------------------------------------------
Date : 30/06/23 Page : 38
Robot Structural Analysis Professional 2023
Author: File: Structure.RTD
Address: Richmond Coach,Royston Project: K2198 Richmond Coach

Section OK !!!

STEEL DESIGN
----------------------------------------------------------------------------------------------------------------------------------------
CODE: British Standard BS 5950:2000
ANALYSIS TYPE: Member Verification
----------------------------------------------------------------------------------------------------------------------------------------
CODE GROUP:
MEMBER: 25 Simple member1_25 POINT: 1 COORDINATE: x = 0.00 L = 0.00 m
----------------------------------------------------------------------------------------------------------------------------------------
LOADS:
Governing Load Case: 4 1.2DL+1.2LL+1.2WL (1+2+3)*1.20
----------------------------------------------------------------------------------------------------------------------------------------
MATERIAL
STEEL 43-275 py = 275.00 MPa E = 205000.00 MPa
----------------------------------------------------------------------------------------------------------------------------------------
SECTION PARAMETERS: EQA 50x4

D=50 mm
B=50 mm Ay=200 mm2 Az=200 mm2 A=392 mm2
t=4 mm Iy=91600 mm4 Iz=91600 mm4 Ix=2050 mm4
T=4 mm Wely=2523 mm3 Welz=2523 mm3
----------------------------------------------------------------------------------------------------------------------------------------
INTERNAL FORCES
Fc = 44.40 kN

----------------------------------------------------------------------------------------------------------------------------------------
CAPACITIES
Pc = 103.49 kN
Section class = 4
----------------------------------------------------------------------------------------------------------------------------------------
LATERAL BUCKLING PARAMETERS:

----------------------------------------------------------------------------------------------------------------------------------------
BUCKLING PARAMETERS:
About Y axis: About Z axis:

Ly = 1.28 m pey = 469.00 MPa Lz = 1.28 m pez = 469.00 MPa


Ley = 1.02 m Fiy = 434.59 MPa Lez = 1.02 m Fiz = 434.59 MPa
Lam,effy = 65.68 py = 189.86 MPa Lam,effz = 65.68 pz = 189.86 MPa
ny = 0.27 Pcy = 71.45 kN nz = 0.27 Pcz = 71.45 kN
----------------------------------------------------------------------------------------------------------------------------------------
VERIFICATION FORMULAS:
Section check
Fc/Pc = 0.43 < 1.00 (4.8.3.2)
Member stability check
Fc/min(Pcy,Pcz) = 0.62 < 1.00 (4.8.3.3.1)
----------------------------------------------------------------------------------------------------------------------------------------
LIMIT DISPLACEMENTS

Date : 30/06/23 Page : 39


Robot Structural Analysis Professional 2023
Author: File: Structure.RTD
Address: Richmond Coach,Royston Project: K2198 Richmond Coach

Deflections (LOCAL SYSTEM):

uy = 0 mm < uy max = L/200.00 = 6 mm Verified


Governing Load Case: 1 DL1
uz = 0 mm < uz max = L/200.00 = 6 mm Verified
Governing Load Case: 6 1DL+1LL+1WL (1+2+3)*1.00
Displacements (GLOBAL SYSTEM):

vx = 1 mm < vx max = L/300.00 = 4 mm Verified


Governing Load Case: 6 1DL+1LL+1WL (1+2+3)*1.00
vy = 0 mm < vy max = L/300.00 = 4 mm Verified
Governing Load Case: 1 DL1
----------------------------------------------------------------------------------------------------------------------------------------
Section OK !!!

Annex-1
SECTION ANALYSIS

Geometry description

Point no. Y Z

1 0 mm 0 mm
2 0 mm 50 mm
3 9 mm 50 mm
4 9 mm 64 mm
5 9 mm 74 mm
6 59 mm 74 mm

Date : 30/06/23 Page : 40


Robot Structural Analysis Professional 2023
Author: File: Structure.RTD
Address: Richmond Coach,Royston Project: K2198 Richmond Coach

7 59 mm 70 mm
8 13 mm 70 mm
9 13 mm 24 mm
10 9 mm 24 mm
11 9 mm 9 mm
12 100 mm 9 mm
13 100 mm 0 mm
14 0 mm 0 mm

General results

Area
A = 1653 mm2
Center of gravity
Yc = 34 mm
Zc = 23 mm
Perimeter
S = 448 mm
Base material
S275
E = 205000.00 MPa
den = 1835.49 kg/m3
WU = 3.03 kG/m
Principal system

Angle
alpha = 58.4 Deg
Moments of inertia
Ix = 44708 mm4
Iy = 1713021 mm4
Iz = 730205 mm4
Radii of inertia
iy = 32 mm
iz = 21 mm
Shear areas
Ay = 1180 mm2
Az = 1139 mm2
Elastic section moduli
Wely = 24964 mm3
Welz = 12860 mm3
Shear rigidity factors
Wy = 384 mm2
Wz = 780 mm2
Plastic section moduli
Wply = 45118 mm3
Wplz = 27311 mm3
Maximum distances
Vy = 57 mm
Vpy = 37 mm
Vz = 48 mm
Vpz = 69 mm
Central system

Moments of inertia
Iyc = 1000276 mm4
Date : 30/06/23 Page : 41
Robot Structural Analysis Professional 2023
Author: File: Structure.RTD
Address: Richmond Coach,Royston Project: K2198 Richmond Coach

Izc = 1442950 mm4


Iyczc = -438739 mm4
Radii of inertia
iyc = 25 mm
izc = 30 mm
Maximum distances
Vyc = 66 mm
Vpyc = 34 mm
Vzc = 51 mm
Vpzc = 23 mm
Arbitrary system

System position
yc' = 34 mm Angle = 0.0 Deg
zc' = 23 mm
Moments of inertia
Iy' = 1000276 mm4
Iz' = 1442950 mm4
Iy'z' = -438739 mm4
Radii of inertia
iyc = 25 mm
izc = 30 mm
First moments of area
Sy' = 0 mm3
Sz' = 0 mm3
Maximum distances
Vy' = 66 mm
Vpy' = 34 mm
Vz' = 51 mm
Vpz' = 23 mm

Date : 30/06/23 Page : 42


Robot Structural Analysis Professional 2023
Author: File: Structure.RTD
Address: Richmond Coach,Royston Project: K2198 Richmond Coach

Annex-2
SECTION ANALYSIS

Geometry description

Point no. Y Z

1 0 mm 0 mm
2 0 mm 50 mm
3 6 mm 50 mm
4 6 mm 111 mm
5 96 mm 111 mm
6 96 mm 105 mm
Date : 30/06/23 Page : 43
Robot Structural Analysis Professional 2023
Author: File: Structure.RTD
Address: Richmond Coach,Royston Project: K2198 Richmond Coach

7 12 mm 105 mm
8 12 mm 21 mm
9 6 mm 21 mm
10 6 mm 6 mm
11 100 mm 6 mm
12 100 mm 0 mm
13 0 mm 0 mm

General results

Area
A = 1908 mm2
Center of gravity
Yc = 33 mm
Zc = 52 mm
Perimeter
S = 602 mm
Base material
S275
E = 205000.00 MPa
den = 1835.49 kg/m3
WU = 3.50 kG/m
Principal system

Angle
alpha = -3.0 Deg
Moments of inertia
Ix = 32815 mm4
Iy = 3694734 mm4
Iz = 1737780 mm4
Radii of inertia
iy = 44 mm
iz = 30 mm
Shear areas
Ay = 1045 mm2
Az = 793 mm2
Elastic section moduli
Wely = 59428 mm3
Welz = 24946 mm3
Shear rigidity factors
Wy = 824 mm2
Wz = 574 mm2
Plastic section moduli
Wply = 76192 mm3
Wplz = 48132 mm3
Maximum distances
Vy = 70 mm
Vpy = 33 mm
Vz = 62 mm
Vpz = 54 mm
Central system

Moments of inertia
Iyc = 3689451 mm4
Izc = 1743063 mm4
Date : 30/06/23 Page : 44
Robot Structural Analysis Professional 2023
Author: File: Structure.RTD
Address: Richmond Coach,Royston Project: K2198 Richmond Coach

Iyczc = 101546 mm4


Radii of inertia
iyc = 44 mm
izc = 30 mm
Maximum distances
Vyc = 67 mm
Vpyc = 33 mm
Vzc = 59 mm
Vpzc = 52 mm
Arbitrary system

System position
yc' = 33 mm Angle = 0.0 Deg
zc' = 52 mm
Moments of inertia
Iy' = 3689451 mm4
Iz' = 1743063 mm4
Iy'z' = 101546 mm4
Radii of inertia
iyc = 44 mm
izc = 30 mm
First moments of area
Sy' = 0 mm3
Sz' = -0 mm3
Maximum distances
Vy' = 67 mm
Vpy' = 33 mm
Vz' = 59 mm
Vpz' = 52 mm

Date : 30/06/23 Page : 45


Robot Structural Analysis Professional 2023
Author: File: Structure.RTD
Address: Richmond Coach,Royston Project: K2198 Richmond Coach

Date : 30/06/23 Page : 46