GAQF.

EX4510 - Clean-agent Extinguishing System


Units

Clean-agent Extinguishing System Units


Ansul EX4510
1 STANTON ST
MARINETTE, WI 54143-2542 United States

PRE-ENGINEEREED UNITS

Sapphire® Models 570636 and 570637 Clean Agent Extinguishing System Units, stored pressure type, having nominal charging capacities of
40 (18) and 80 (36) lb (kg) of 3M™ Novec™ 1230 Fire Protection Fluid (FK-5-1-12) Clean Agent, respectively. The units are super-pressurized
to 360 psig (25 bar) with operating temperatures of 32°F (0°C) to 130°F (54°C). The units are designed for total flooding protection against
Class A surface burning, Class B flammable liquid and C fires occurring within an enclosure.

These system units are intended to be designed and installed in accordance with the Listee's Pre-Engineered System Installation Guide P/N
570527 dated May 15, 2003, revised September 1, 2010, and Ansul Bulletin No. 2015187a, Placement Indicator Switch, dated December 31,
2015 and Electric Actuator p/n 304205030 in Bulletin 2018265 dated April 18, 2019.

ENGINEEREED UNITS

IG-541 (Inergen) Clean Agent Extinguishing System Units, stored pressure type, having nominal storage capacities of 200, 250, 350, 425, 435
cu ft of IG-541 (Inergen). The units are pressurized to 2175 psig (150 Bar) at 70°F with operating temperatures of 32°F to 130°F. The units are
designed for total flooding protection against Class A surface burning, Class B flammable liquid and Class C fires occurring within an
enclosure.

A description of these extinguishing system units and the design and installation limitations are contained in the Listee's installation manual
P/N 416655-15 issued November 13, 2017, and Ansul Bulletin No. 2018056, Acoustic Nozzle, dated May 4, 2018. These installations require
the use of the Listee's flow calculation software 150 Bar Inergen Designer Version 2.1.2 for engineered or Inercalc Version 1.3.0 for balanced
engineered. Copies are available from the above Listee.

IG-541 (Inergen) Clean Agent Extinguishing System Units, stored pressure type, having nominal storage capacities of 575 cu ft of IG-541
(Inergen). The units are pressurized to 2900 psig (200 Bar) at 70°F with operating temperatures of 32°F to 130°F. The units are designed for
total flooding protection against Class A surface burning, Class B flammable liquid and Class C fires occurring within an enclosure.

A description of these extinguishing system units and the design and installation limitations are contained in the Listee's installation manual
P/N 430149-06 issued November 24, 2017, and Ansul Bulletin No. 2018056, Acoustic Nozzle, dated May 4, 2018, and Ansul Bulletin No.
2018234, ANSUL 3/4 in. Acoustic Nozzle, dated November 30, 2018. These installations require the use of the Listee's flow calculation
software 200 Bar Inergen Designer Version 5.1.3 for engineered. Copies are available from the above Listee.

Engineered IFlow Models 441380, 441373, 441419, 441417, 445912, 446834, 446714, 446836, 445913, 446835, 446715, 446837, 441428 and
441427 Clean Agent Extinguishing System Units, stored pressure type, having nominal charging capacities of 22.3, 22.3, 22.3, 22.3, 22.3, 22.3,
22.3, 22.3, 39.0, 39.0, 39.0, 39.0, 39.0 and 39.0 cubic meters of Inergen (IG-541) Clean Agent, respectively. The units are pressurized to 300 bar
with operating temperatures of -4°F (-20°C) to 130°F (54°C). The units are designed for total flooding protection against Class A surface
burning, Class B flammable liquid and C fires occurring within an enclosure.

These system units are intended to be designed and installed in accordance with the Listee's Engineered System Installation, Recharge and
Maintenance Manual, P/N 441435 Rev. 03 dated May 2019. These installations require the use of the Listee's flow calculation software, the
Tyco IFlow 300 Engineered System Flow Calculation Software Versions 2.0.0, 2.0.2, or 2.1. Copies are available from the above Listee, or Flow
Calculation Software Design Center(SDC) online interface version 2.0.3 Utilizing Iflow 300 Engineered System Flow Calculation Software
Version GSI 2.0.5.

Engineered Sapphire Models 570635, 570633, 570634, 570638, 570639, 570640, 570641, and 570586 Clean Agent Extinguishing System Units,
stored pressure type, having nominal charging capacities of 20, 50, 90, 140, 280, 390, 450, and 850 lb (9.1, 22.7, 40.8, 63.5, 127, 177, 204 and
386 kg) of 3MTM NovecTM 1230 Fire Protection Fluid (FK-5-1-12) Clean Agent, respectively. The units are super-pressurized to 360 psig (25
bar) with operating temperatures of 32°F (0°C) to 130°F (54°C). The units are designed for total flooding protection against Class A surface
burning, Class B flammable liquid and C fires occurring within an enclosure.
These system units are intended to be designed and installed in accordance with the Listee's Engineered System Installation, Recharge
and Maintenance Manual, P/N 570590-4 dated September 1, 2010, Main/Reserve Actuation Isolator Installation Manual Supplement, P/N
437276 dated March 31, 2010, Ansul Bulletin No. 2015187a, Placement Indicator Switch, dated December 31, 2015, Electrical Actuator p/n
304205030 in Bulletin 2018265 dated April 18, 2019, the Manual Bulletin p/n 16446, Halocarbon ATEX Components (Electrical Actuator &
Low-Pressure Switch), dated December 2021and the Sapphire Engineered System Flow Calculation Software Versions ANSL3.61b or TYCO
4.00.

Engineered Sapphire Models 442639, 570839, 442640, 442641, and 442642 Clean Agent Extinguishing System Units, stored pressure
type, having nominal charging capacities of 90, 210, 320, 370, and 476 lbs (41, 96, 144, 168, and 216kgs) of 3MTM NovecTM 1230 Fire
Protection Fluid (FK-5-1-12) Clean Agent, respectively. The units are super-pressurized to 360 psig (25 bar) with operating temperatures of
32°F (0°C) to 130°F (54°C). The units are designed for total flooding protection against Class A surface burning, Class B flammable liquid and
C fires occurring within an enclosure.

These system units utilize seamless pressure cylinders manufactured in India and are designed, constructed, and tested in accordance
with Indian Standard IS7285 (Part 2):2004. Pressure cylinders are not DOT-rated cylinders.

These system units are intended to be designed and installed in accordance with the Listee's Engineered System Design and
Installation Manual (India-UL Version), P/N 570805-02 dated September, 2015, Bulletin No. 2015187a, Placement Indicator Switch, dated
December 31, 2015, Bulletin No. 2018265, Electric Actuator (p/n 304205030), dated Apeil 18, 2019 and the Sapphire Engineered system Flow
Calculation Software Versions ANSL 3.81b or TYCO4.00.

Engineered FM-200® Models 442872, 442873, 442874, 442875, 442876, 442877, 442878, and 442879 Clean Agent Extinguishing System Units
utilizing DOT rated cylinders, stored pressure type, having nominal charging capacities of 8, 16, 32, 52, 106, 147, 180, and 343 L (17, 35, 70,
114, 233, 324, 396 and 756 lbs) of FM-200® Clean Agent, respectively.

Engineered FM-200® Models 442882, 442883, 442884, 442885, 442886, 442887, 442888, and 442889 Clean Agent Extinguishing System Units
utilizing TC rated cylinders, stored pressure type, having nominal charging capacities of 8, 16, 32, 52, 106, 147, 180, and 343L (17, 35, 70, 114,
233, 324, 396 and 756 lbs) of FM-200® Clean Agent, respectively.

The units are super-pressurized to 360 psig (25 bar) with operating temperatures of 32ºF to 130°C (0°C to 54°C). The units are designed for
total flooding protection against Class A surface burning, Class B flammable liquid and C fires occurring within an enclosure.

These system units are intended to be designed and installed in accordance with the Listee's Engineered System Installation, Recharge
and Maintenance Manual, P/N 442940 dated 2015-10-09, Rev. 0, Electric Actuator p/n 304205030 Bulletin 2018265 dated April 18, 2019, the
Manual Bulletin p/n 16446, Halocarbon ATEX Components (Electrical Actuator & Low-Pressure Switch), dated December 2021 and the FM-
200® Engineered System Flow Calculation Software Version TYCO 4.00.

Sapphire ® Clean Agent Extinguishing System Units containing 3M™ Novec™ 1230 Fire Protection Fluid (FK-5-1-12), stored pressure type,
having nominal storage capacities as shown below of Novec™ 1230 Fluid (FK-5-1-12). The units are pressurized to 360 psig (25 bar) at 70°F
with operating temperatures of 32°F to 130°F (0°C to 54°C). The units are designed for total flooding protection against Class A surface
burning, Class B flammable liquid and Class C fires occurring within an enclosure. A description of these extinguishing system units and the
design and installation limitations are contained in the Listee's installation manual P/N 570590, Rev. 5, issued September 14, 2020 - the
Bulletin 16445 for ANSUL SAPPHIRE corrosion resistant (CR) painted PESO containers for INDIA, dated December 2021, and the Manual
Bulletin p/n 16446, Halocarbon ATEX Components (Electrical Actuator & Low- Pressure Switch), dated December 2021. These installations
require the use of the Listee's flow calculation software ANSL 3.61b or TYCO4.00, or Software Design Center(SDC) online interface utilizing
Version 4.18W. Copies are available from the above Listee.

AGENT STORAGE CONTAINER ASSEMBLY


Weight of Agent (kg) Part No.

4 - 9.5 570635

7.5 - 18 303207300, 303207310

8 - 19 570633

15 - 36 303207301, 303207311

16 - 38 570634

17 - 40.8 422639, 422639CR

22.5 - 54 302207302, 302207312

26 - 62 570638

30 - 72 302207303, 302207313

40 - 96 570839, 570839CR
53 - 127 570639, 570651

60 - 144 442640, 570840, 302207304, 302207314, 442640CR

70 - 168 442641, 442641CR

73.5 - 176 570640, 570652

75 - 180 302207305, 302207315

90 - 208 442642, 570641, 570653, 302207306, 442642CR

171.5 - 386 570586, 570654

FM-200® Models Clean Agent Extinguishing System Units, stored pressure type, having nominal charging capacities as shown below of FM-
200® Clean Agent. The units are super-pressurized to 360 psig (25 bar) with operating temperatures of 32°F to 130°C (0°C to 54°C). The units
are designed for total flooding protection against Class A surface burning, Class B flammable liquid and C fires occurring within an enclosure.
These system units are intended to be designed and installed in accordance with the Listee's Engineered System Installation, Recharge and
Maintenance Manual, P/N 442940 dated September 14, 2020, Rev. 1, Manual Bulletin 2021121 dated December 15, 2021 the Manual Bulletin
p/n 16446, Halocarbon ATEX Components (Electrical Actuator & Low-Pressure Switch), dated December 2021, and the FM- 200® Engineered
System Flow Calculation Software Version TYCO4.00. Copies are available from the above Listee.

AGENT STORAGE CONTAINER ASSEMBLY


Weight of Agent (kg) Part No.

2.5 - 4.5 303.205.026

4-8 442872, 442882

7.5 - 15 303205300, 303205310

8 - 16 442873, 442883

15 - 30 303205301, 303205311

16 - 32 442874, 442884

17 - 34 303.205.035

22.5 - 45 302205302, 302205312

26 - 52 442875, 442885

30 - 60 302205303, 302205313

40 - 80 303.205.032

53 - 106 442876, 442886

60 - 120 303.205.033, 302205304, 302205314

70 - 140 303.205.034

73.5 - 147 442877, 442887

75 - 150 302205305, 302205315

90 - 180 303.205.036, 302205306, 442878, 442888

171.5 - 343 442879, 442889

Ansul Sapphire® Plus Clean Agent Extinguishing System Units, stored pressure type, having nominal charging capacities of 3MTM NOVECTM
1230 Clean Agent as indicated below. The units are super-pressurized to 70 bar at 20°C with operating temperatures of -18°C to 50°C. The
units are designed for total-flooding protection against Class A surface burning, Class B flammable liquid, and Class C fires occurring within
an enclosure.
These system units are intended to be designed and installed in accordance with the Listee's Engineered System Installation, Recharge and
Maintenance Manual, P/N 571000 dated August 1, 2019, the Bulletin 16445 for ANSUL SAPPHIRE corrosion resistant (CR) painted PESO
containers for INDIA, dated December 2021, the Manual Bulletin p/n 16446, Halocarbon ATEX Components (Electrical Actuator & Low-
Pressure Switch), dated December 2021, and the Sapphire 70 Flow Calculation Software Version 2.0.16 with calculation module Version 2.0.5
B5 April 30th, 2018, Copies are available from the above Listee, or the Suppression Design Center (SDC) online interface Version 2.0.3 utilizing
Sapphire 70 Flow calculation module Version 2.0.5 B5 April 30th, 2018.

AGENT STORAGE CONTAINER ASSEMBLY


Weight of Agent (kg) Part No.

4.5-21.0 303700001, 303700007


303700041, 303700047

9.0-42.0 303700002, 303700008


303700042, 303700048

10.5-47.5 303700025, 303700029


452148, 452148CR

14.0-63.0 303700003, 303700009


303700043, 303700049

18.0-84.0 303700004, 303700010


303700044, 303700050

24.0-112.0 303700026, 303700030


452149, 451249CR

36.0-168.0 303700005, 303700011


303700027, 303700031
4520150,452150CR
303700045, 303700051

45.0-210.0 303700065, 303700066

54.0-252.0 303700006, 303700012


303700046, 303700052
303700028, 303700032
452151, 452151CR

Ansul Sapphire® Plus Clean Agent Extinguishing System Units, stored pressure type, having nominal charging capacities of 3MTM NOVECTM
1230 Clean Agent as indicated below. The units are super-pressurized to 70 bar at 20°C with operating temperatures of -0°C to 65°C. The
units are designed for total-flooding protection against Class A surface burning, Class B flammable liquid, and Class C fires occurring within
an enclosure.

These system units are intended to be designed and installed in accordance with the Listee's Engineered System Installation, Recharge and
Maintenance Manual, P/N 571000 dated August 1, 2019, the ANSUL SAPPHIRE Acoustic Nozzle UL Listing and UL Verify, Bulletin No. 2019198,
dated February 2020, the Bulletin 16445 for ANSUL SAPPHIRE corrosion resistant (CR) painted PESO containers for INDIA, dated December
2021, the Manual Bulletin p/n 16446, Halocarbon ATEX Components (Electrical Actuator & Low-Pressure Switch), dated December 2021, and
with the Sapphire 70 Flow Calculation Software Version 2.0.16 with calculation module Version 2.0.5 B5 April 30th, 2018, Copies are available
from the above Listee, or the Suppression Design Center (SDC) online interface Version 2.0.3 utilizing Sapphire 70 Flow calculation module
Version 2.0.5 B5 April 30th, 2018.

AGENT STORAGE CONTAINER ASSEMBLY


Weight of Agent (kg) Part No.

4.5-20.3 303700013, 303700019


303700053, 303700059

9.0-41.0 303700014, 303700020


303700054, 303700060

10.5-45.5 303700033, 303700037


452148, 452148CR
14.0-60.8 303700015, 303700021
303700055, 303700061

18.0-81.0 303700016, 303700022


303700056, 303700062

24.0-108.0 303700034, 303700038


452149, 452149CR

36.0-162.0 303700017, 303700023


303700057, 303700063
303700035, 303700039
452150, 452150CR

45.0-202.5 303700067, 303700068

54.0-243.0 303700018, 303700024


303700058, 303700064
303700036, 303700040
452151, 452151CR

Last Updated on 2022-02-21

The appearance of a company's name or product in this database does not in itself assure that products so identified have been
manufactured under UL's Follow-Up Service. Only those products bearing the UL Mark should be considered to be Certified and covered
under UL's Follow-Up Service. Always look for the Mark on the product.

UL permits the reproduction of the material contained in the Online Certification Directory subject to the following conditions: 1. The Guide
Information, Assemblies, Constructions, Designs, Systems, and/or Certifications (files) must be presented in their entirety and in a non-
misleading manner, without any manipulation of the data (or drawings). 2. The statement "Reprinted from the Online Certifications Directory
with permission from UL" must appear adjacent to the extracted material. In addition, the reprinted material must include a copyright notice
in the following format: "© 2022 UL LLC"

You might also like