MATERIALS LIST FOR TRANSFORMERS ,& MDB's .

AL-MARINA CITY , ALMAHRAH

Unit Total Price


ITEM ITEM DISCRIPTION Spec.No Units Qty
Price($) ($)

200KVA Step Down Distribution Transformer 11/0.415kv , 3Ph , Dyn11 , 50Hz , ±2x 2.5% , Ground
1 PC'S 1 -
Mounted (ONAN) , H.V & L.V top Pushings

315KVA Step Down Distribution Transformer 11/0.415kv , 3Ph , Dyn11 , 50Hz , ±2x 2.5% , Ground ‫موجود في الموقع‬
2 PC'S 1
Mounted (ONAN) , H.V & L.V top Pushings ‫غير مطلوب‬

3 Flexible Various Removable Button Head 11kv ,25A Cutout Fuse Link PC'S 10 -

4 Flexible Various Removable Button Head 11kv , 40A Cutout Fuse Link PC'S 10 -

Switch geer Fuse Ring Main Unit (Oil or SF6) Insulation :- 11KV (12.5KV), 630A /200A , 50Hz,
5 20KA/3sec , outdoor type , Ground mounted, complete with all accessories (( Ring Cable Boxes, End Unit 1 -
Cap Boxes with insulations , Filled (Oil or SF6) & Fuses:

6 11KV , 40A Fuse suitable for FRMU PC'S 6 -

7 11KV (12.5KV) Surge arrester ,10KA, complete set with bracket mounted, European Sources KIT 6 -

Earthing set complete with:


50Meter copper conductor size 100mm2
8 Unit 30 -
CU rod 16mm2 *2200mm & CU clamps
25kg Bentonite: Moisture Retaining Clay
TOTAL

ENG./ YAAQOB ALBURIHI


MATERIALS LIST FOR TRANSFORMERS ,& MDB's . AL-MARINA CITY , ALMAHRAH

Unit Total Price


ITEM ITEM DISCRIPTION Spec.No Units Qty
Price($) ($)

MAIN DISTRIBUTION BOARDS FOR TOW TRANSFORMERS

LV, 3ph, AC Distribution boards unit complete including


- The distribution board should allow flexibility to connect switch disconnections, MCCB, MCB,
RCCB, RCD or direct cable.
- Internal connection should be through bus bars the bus bar rating should be at least 630A. and it
containing 1 input & 10 outputs:
1 - Main MCCB rating 400A , 36kA Unit 1
- Sup- 3P MCCB's Rating: 250A, 250A , 160A ,160A , 80A , 80A , 40A ,40A , 16A , 16A
- Minimum Number of ways is 25KA.
- High quality breakers preferably Schneider, ABB or equivalent.
- Enclosure- Base frame of 2mm, corner post of 2mm,Side panel sheets-2mm,Powder coated with
degree of protection IP67.

LV, 3ph, AC Distribution boards unit complete including


- The distribution board should allow flexibility to connect switch disconnections, MCCB, MCB,
RCCB, RCD or direct cable.
- Internal connection should be through bus bars the bus bar rating should be at least 800A.
- Main MCCB rating 630A , 36kA
2 - Sup- up- 3P MCCB's Rating: 250A, 250A , 160A ,160A , 80A , 80A , 63A , 63A , 32A, 32A Unit 1
- Sup- 1P MCB's Rating 16A, 16A , 10A , 10A, 6A ,6A,
- Minimum Number of ways is 16.
- High quality breakers preferably Schneider, ABB or equivalent.
- Enclosure- Base frame of 2mm, corner post of 2mm,Side panel sheets-2mm,Powder coated with
degree of protection IP67.

ENG./ YAAQOB ALBURIHI


MATERIALS LIST FOR TRANSFORMERS ,& MDB's . AL-MARINA CITY , ALMAHRAH

Unit Total Price


ITEM ITEM DISCRIPTION Spec.No Units Qty
Price($) ($)

DISTRIBUTION BOARD FOR ELECTRICAL GAME BARK

LV, 3ph, AC Distribution boards unit complete including


- The distribution board should allow flexibility to connect switch disconnections, MCCB, MCB,
RCCB, RCD or direct cable.
- Internal connection should be through bus bars the bus bar rating should be at least 400A.
- Main MCCB rating 250A , 36kA
3 - Sup- 3P MCCB's & 3P MCB's Rating 63A, 63A, 32A, 32A,32A, 32A , 20A ,20A,16A,16A Unit 1
- Sup- 1P MCB's Rating 16A, 16A , 16A , 16A,
- Minimum Number of ways is 14.
- High quality breakers preferably Schneider, ABB or equivalent.
- Enclosure- Base frame of 2mm, corner post of 2mm,Side panel sheets-2mm,Powder coated with
degree of protection IP67.

DISTRIBUTION BORD FOR ELECTRICAL CHALETS

LV, 3ph, AC Distribution board unit complete including


- The distribution board should allow flexibility to connect switch disconnections, MCCB, MCB, RCCB, RCD
or direct cable.
- Internal connection should be through bus bars the bus bar rating should be at least 200A-160A.
- Main MCCB rating 160A
4 Unit 3 -
- Sup- 3P 2MCCB's Ratings: 63A & Sup- 2P MCB's Ratings:12 MCB's of 25A & 10 MCB's 16A
- Fault level: at least 16 kA.
- Minimum Number of ways is: 24.
- High quality breakers preferably Schneider, ABB or equivalent.
- Enclosure- Base frame of 2mm, Side panel sheets-2mm,Powder coated with degree of protection IP67.

ENG./ YAAQOB ALBURIHI