CUSTOMER ABB ELEKTRIK SANAYI A.S. CUSTOMER ORDER 45515768 QUANTITY 1 VACUUM - CIRCUIT BREAKER TYPE VD4/W 36.12.25 SERIAL NUMBER 1VC1BL00043300 RATINGS Rated Voltage Ur 36 KV Rated insulation Voltage Us 36 KV Withstand voltage at 50 HZ - 1 min Ud 70 KV Impulse Withstand voltage Up 170 KV Rated frequency Fr 50/60 Hz Rated Normal current (40°C) Ir 1250 A Rated breaking capacity Isc 25 KA Rated short time withstands current (3s) Ik 25 KA Making capacity Ip 65 KA Operation sequence O-0,3S-CO-15S-CO Accessories C.B. Spring charging geared motor (-MAS) 125 V DC Shunt opening release (-MBO1) 110...127 V AC/DC Add shunt opening release (-MBO2) V Opening solenoid (-MBO3) V Shunt closing release (-MBC) 110...127 V AC/DC Undervoltage release (-MBU) V Locking magnet (-RLE1) V Add shunt opening release (-MBO4) V Accessories On Truck Locking magnet (-RLE2) 125 V DC Motor moving truck (-MAT) V Individual tests according to CEI 17-1/IEC 62271-100 Design and visual check OK
Mechanical and electrical operating tests
5 O/C operations at 5 O/C operations at 5 O/C operations at 5 O/C operating cycles 5 sequences O-t-C rated supply Voltage max. supply Voltage min. supply Voltage with -MC energized OK OK OK OK OK Power frequency voltage withstand test Main circuits 70 KV applied for 1 min Auxiliary circuits 1 KV applied for 1 sec Voltage drop test with 200A DC R S T Drop Voltage Measured (mV) 5.6 5.6 5.5 Max 8,0 mV Contact speed measured Closing speed 1.25 Range 1 - 1,5 m/sec Opening speed 1.41 Range 1,2 - 1,7 m/sec Main contacts simultaneity check 0.20 Max 2 ms Direct Envelope Comparison OK Max +/- 2mm from the standard Operating time at rated voltage applied Min. Vn Vn Max Vn Range Vn Closing Time 57 55 53 50 - 80 ms Opening Time 52 44 42 35 - 60 ms The circuit breaker has passed the tests Department Date Quality Result OAQ 29.08.2018 Passed