REFERENCED APPLICATION #1 SPACE HEATING & COOLING WITH DRY CONTACT REV. 00 10/09/2021
Dry Contact
LG Extension Cable for Wi-Fi Modem
(PWYREW000)
Pressure Gauge Thermostatic Mixing Valve Flow Sensor Wi-Fi Modem Cable Length 10m
LG
COOLING CIRCUIT
THERMOSTAT 1 THERMOSTAT 2
RS3
3RD PARTY ACCESSORIES
Buffer Tank
A water tank containing certain amount of water
that secures the required minimum water volume
1Ø 220-240V AC or 3Ø 380-415V AC
- Safety valve (3 bar) SUPPLY A motorized isolation valve that blocks the water
- Pressure sensor WI-FI flow into underfloor coil in order to prevent water
- Strainer (30 mesh) MODEM condensation during cooling mode.
- Flow sensor
Controlled by THERMA V with 230V power.
LG MAGNETIC Required operating time : less than 90s.
CONTACTOR 2 WAY
VALVE DDC (Direct Digital Controller)
LG CN_CC
A control device that uses the analogue or digital
TB1 4 / 6 signals from various devices and then process and
THERMA V
control the system based on the program written
CN_WF DIFFERENTIAL inside the controllers and has the capability to
EXTERNAL PUMP PRESSURE
VALVE sends the information to another controller.
DN25
DN25 Thermostat
MAKE UP WATER A control device that senses the temperature of a
room and performs actions so that the room's
SERVICE temperature is maintained near a desired setpoint.
THERMA V R32 MONOBLOC S VALVE Thermostat must be connected with Therma V,
Valve, Pump, and FCU where applicable.
MAGNETIC FILTER
(RECOMMENDED) BUFFER TANK
2 Way Valve for Thermostat
A isolation valve paired with thermostat to allow
whether water flows into the water circuit.
NOTE
1. This diagram should be used only for reference purpose. It does not contain all the required equipment and safety components in accordance with actual site conditions. Furthermore, please make sure to take into account the applicable standards and
laws for each country. LG Electronics disclaims any direct or indirect responsibility for any consequences arising out of any inaccuracies or consequential changes to this general scheme.
2. It is essential to ensure the minimum amount of water contained in the heating or cooling system.
3. Must fit the insulations on the entire water piping including valves and connections. If necessary, electrical heat tracing system can be installed or the heating system can also be filled with antifreeze (glycol) to prevent any frost damage.
4. In a cold climate region, water drainage from outdoor unit must be frost-proof.
REFERENCED APPLICATION #1 SPACE HEATING & COOLING WITH DRY CONTACT
DIP SWITCH SETTINGS
WIRING DIAGRAM
MAIN PCB (HYDRO)
SW1
MONOBLOC UNIT
ON
OFF
1 2 3 4 5 6 7 8
10 11 12 13 14 15 16 17 18 19 20
PUMP (C)
BR BL
N
WATER
3RD PARTY
DDC SW2
DRY CONTACT CONTROL SYSTEM
L
ON
MIX PUMP
THERMOSTAT 1
CN_CC
BR WH BL BR WH BL BR WH BL BR BL BR BL BR BL
Dry Contact
N OFF
1 2 3 4 5 6 7 8
LG THERMOSTAT 2
L
X : OFF / O : ON
PUMP (B)
N
WATER
DIP SW 1 1 2 3 4 5 6 7 8
MODBUS Master (Link to LG controller) X
Communication
L
MODBUS REGINE X
Function Unified Open Protocol O
W.TANK
HEATER
default setting X X X
N
VALVE (B)
DIP SW 2 1 2 3 4 5 6 7 8
3 WAY
CN_TH4
TB_SENSOR
SOLAR Control As Slave O
Heat pump installation (Heating or
cooling circuit only) X X
DEW Accessory
L
Heating only X
Heat Pump Cycle
3 WAY
CN_ROOM2
Remote Room Remote room air sensor is not
X
Air Sensor installed
(Accessory)
7
Heater Capacity
VALVE (A)
- L : on Voltage when Cooling is active (NO Valve) EXTERNAL Thermostat Thermostat is not installed X
L1
5
230 V AC
BR BR BL
N
3
MIXING
VALVE
L1
2
1
L
SW1
OFF
25 26 27
3rd Party
1 2 3 4 5 6
BOILER PUMP A2
A
TB_EXT
X : OFF / O : ON
L3
DIP SW 1 2 3
Always mode : Maintain low noise
MAGNETIC mode for target temperature X
CONTACTOR Low Noise Mode
Partial mode : Escape low noise
O
EXT
(Default 230 V AC)
Max mode X
21 22 23 24
BL BR WH BK
L2
default setting X X
L1
POWER
CN_MIX_OUT
N
SUPPLY
1Ø 220 ~ 240 V AC
L
NOTE
RS3
WIFI MODEM
1. The wiring cable size and Circuit breaker selection
CN_REMO
COMMON
HEATER1
HEATER2
3 PHASE
Power supply of
Main T/B R
CN_WF
Dry Contact
LG
COOLING CIRCUIT
Buffer Tank
A water tank containing certain amount of water
that secures the required minimum water volume
1Ø 220-240V AC or 3Ø 380-415V AC
- Safety valve (3 bar) A motorized isolation valve that blocks the water
- Pressure sensor flow into underfloor coil in order to prevent water
- Strainer (30 mesh) condensation during cooling mode.
- Flow sensor MAGNETIC Controlled by THERMA V with 230V power.
CONTACTOR
Required operating time : less than 90s.
2 WAY
VALVE Thermostat
LG
TB1 4 / 6 A control device that senses the temperature of a
room and performs actions so that the room's
TB2 21 / 22 / 23 / 24
THERMA V
TB3 25 temperature is maintained near a desired setpoint.
DIFFERENTIAL Thermostat must be connected with each 2 Way
EXTERNAL PUMP PRESSURE
VALVE Valve and FCU where applicable.
DN25
DN25 2 Way Valve for Thermostat
MAKE UP WATER A isolation valve paired with thermostat to allow
whether water flows into the water circuit.
SERVICE
THERMA V R32 MONOBLOC S VALVE Differential Pressure Valve
A self pressure regulating valve that provides
MAGNETIC FILTER constant differential pressure between supply and
(RECOMMENDED) BUFFER TANK
return headers.
NOTE
1. This diagram should be used only for reference purpose. It does not contain all the required equipment and safety components in accordance with actual site conditions. Furthermore, please make sure to take into account the applicable standards and
laws for each country. LG Electronics disclaims any direct or indirect responsibility for any consequences arising out of any inaccuracies or consequential changes to this general scheme.
2. It is essential to ensure the minimum amount of water contained in the heating or cooling system.
3. Must fit the insulations on the entire water piping including valves and connections. If necessary, electrical heat tracing system can be installed or the heating system can also be filled with antifreeze (glycol) to prevent any frost damage.
4. In a cold climate region, water drainage from outdoor unit must be frost-proof.
REFERENCED APPLICATION #2-1 SPACE HEATING & COOLING WITH THERMOSTAT
DIP SWITCH SETTINGS
WIRING DIAGRAM
MAIN PCB (HYDRO)
SW1
MONOBLOC UNIT
ON
OFF
1 2 3 4 5 6 7 8
10 11 12 13 14 15 16 17 18 19 20
PUMP (C)
BR BL
N
WATER
SW2
L
ON
MIX PUMP
BR WH BL BR WH BL BR WH BL BR BL BR BL BR BL
N OFF
1 2 3 4 5 6 7 8
L
X : OFF / O : ON
PUMP (B)
N
WATER
DIP SW 1 1 2 3 4 5 6 7 8
MODBUS Master (Link to LG controller) X
Communication
L
MODBUS REGINE X
Function Unified Open Protocol O
W.TANK
HEATER
default setting X X X
N
VALVE (B)
DIP SW 2 1 2 3 4 5 6 7 8
3 WAY
CN_TH4
TB_SENSOR
SOLAR Control As Slave O
Heat pump installation (Heating or
cooling circuit only) X X
DEW Accessory
L
Heating only X
Heat Pump Cycle
3 WAY
CN_ROOM2
Remote Room Remote room air sensor is not
X
Air Sensor installed
(Accessory)
7
Heater Capacity
VALVE (A)
230 V AC
BR BR BL
N
3
MIXING
VALVE
L1
EXTERNAL
2
PUMP
MAIN PCB (CYCLE)
TB1
1
L
SW1
OFF
25 26 27
3rd Party
1 2 3 4 5 6
BOILER PUMP A2
A
230 V AC / L3 DHW
TB_EXT
X : OFF / O : ON
L3
DIP SW 1 2 3
Always mode : Maintain low noise
mode for target temperature X
Low Noise Mode
Partial mode : Escape low noise
O
EXT
(Default 230 V AC)
L2
C H (On/Off)
(C/H) Peak Control Peak control : To limit maximum
O
current (Power saving)
230 V AC / L1 Cooling
TB2 & TB3
default setting X X
L1
CN_MIX_OUT
N
230 V AC MECHANICAL
L
THERMOSTAT
(3rd party)
NOTE
RS3 MAGNETIC
CONTACTOR 1. The wiring cable size and Circuit breaker selection
CN_REMO
COMMON
HEATER1
HEATER2
3 PHASE
Dry Contact
LG
THERMOSTAT
RS3
3RD PARTY ACCESSORIES
Buffer Tank
A water tank containing certain amount of water
that secures the required minimum water volume
1Ø 220-240V AC or 3Ø 380-415V AC
- Safety valve (3 bar) A motorized isolation valve that blocks the water
- Pressure sensor flow into underfloor coil in order to prevent water
- Strainer (30 mesh) condensation during cooling mode.
- Flow sensor MAGNETIC Controlled by THERMA V with 230V power.
CONTACTOR
Required operating time : less than 90s.
2 WAY VALVE 2 WAY VALVE
FOR COOLING FOR HEATING Thermostat
LG
TB1 4 / 5 / 6 A control device that senses the temperature of a
room and performs actions so that the room's
TB2 21 / 22 / 23 / 24
THERMA V
TB3 25 temperature is maintained near a desired setpoint.
DIFFERENTIAL In this application, Thermostat must be connected
EXTERNAL PUMP PRESSURE
VALVE with Therma V and interlocking operation with FCU
DN25
is required.
DN25
MAKE UP WATER Differential Pressure Valve
A self pressure regulating valve that provides
SERVICE constant differential pressure between supply and
THERMA V R32 MONOBLOC S VALVE return headers.
MAGNETIC FILTER
(RECOMMENDED) BUFFER TANK
NOTE
1. This diagram should be used only for reference purpose. It does not contain all the required equipment and safety components in accordance with actual site conditions. Furthermore, please make sure to take into account the applicable standards and
laws for each country. LG Electronics disclaims any direct or indirect responsibility for any consequences arising out of any inaccuracies or consequential changes to this general scheme.
2. It is essential to ensure the minimum amount of water contained in the heating or cooling system.
3. Must fit the insulations on the entire water piping including valves and connections. If necessary, electrical heat tracing system can be installed or the heating system can also be filled with antifreeze (glycol) to prevent any frost damage.
4. In a cold climate region, water drainage from outdoor unit must be frost-proof.
REFERENCED APPLICATION #2-2 SPACE HEATING & COOLING WITH THERMOSTAT
DIP SWITCH SETTINGS
WIRING DIAGRAM
MAIN PCB (HYDRO)
SW1
MONOBLOC UNIT
ON
OFF
1 2 3 4 5 6 7 8
10 11 12 13 14 15 16 17 18 19 20
PUMP (C)
BR BL
N
WATER
SW2
L
ON
MIX PUMP
BR WH BL BR WH BL BR WH BL BR BL BR BL BR BL
N OFF
1 2 3 4 5 6 7 8
L
FOR HEATING
N
WATER
DIP SW 1 1 2 3 4 5 6 7 8
(NC Valve) MODBUS
2 WAY VALVE Communication
Master (Link to LG controller) X
L
- L : on Voltage when Cooling is active Type Slave (Link to 3rd party controller) O
2 WAY VALVE
Antifreeze is not applied X
FOR COOLING Antifreeze Mode Antifreeze is applied (Adjustable
(NC Valve) anti-freeze temp.)
O
L
default setting X X X
N
VALVE (B)
DIP SW 2 1 2 3 4 5 6 7 8
3 WAY
CN_TH4
TB_SENSOR
SOLAR Control As Slave O
Heat pump installation (Heating or
cooling circuit only) X X
DEW Accessory
L
Heating only X
Heat Pump Cycle
3 WAY
CN_ROOM2
Remote Room Remote room air sensor is not
X
Air Sensor installed
(Accessory)
7
Heater Capacity
VALVE (A)
N
3
MIXING
VALVE
L1
EXTERNAL
2
PUMP
MAIN PCB (CYCLE)
TB1
1
L
SW1
OFF
25 26 27
3rd Party
1 2 3 4 5 6
BOILER PUMP A2
A
230 V AC / L3 DHW
TB_EXT
X : OFF / O : ON
L3
DIP SW 1 2 3
Always mode : Maintain low noise
mode for target temperature X
Low Noise Mode
Partial mode : Escape low noise
O
EXT
(Default 230 V AC)
L2
C H (On/Off)
(C/H) Peak Control Peak control : To limit maximum
O
current (Power saving)
230 V AC / L1 Cooling
TB2 & TB3
default setting X X
L1
CN_MIX_OUT
N
230 V AC MECHANICAL
L
THERMOSTAT
(3rd party)
NOTE
RS3 MAGNETIC
CONTACTOR 1. The wiring cable size and Circuit breaker selection
CN_REMO
COMMON
HEATER1
HEATER2
3 PHASE
Dry Contact
LG
THERMOSTAT
RS3
3RD PARTY ACCESSORIES
Buffer Tank
A water tank containing certain amount of water
that secures the required minimum water volume
1Ø 220-240V AC or 3Ø 380-415V AC
Thermostat
LG
A control device that senses the temperature of a
TB1 4 / 5 / 6 room and performs actions so that the room's
temperature is maintained near a desired setpoint.
THERMA V
TB2 21 / 22 / 23 / 24
TB3 25 In this application, Thermostat must be connected
3 WAY VALVE
(SWITCHING
with Therma V and interlocking operation with FCU
EXTERNAL PUMP
HEATING/COOLING) is required.
DN25
DN25 Differential Pressure Valve
MAKE UP WATER A self pressure regulating valve that provides
constant differential pressure between supply and
SERVICE return headers.
THERMA V R32 MONOBLOC S VALVE
MAGNETIC FILTER
(RECOMMENDED) BUFFER TANK
NOTE
1. This diagram should be used only for reference purpose. It does not contain all the required equipment and safety components in accordance with actual site conditions. Furthermore, please make sure to take into account the applicable standards and
laws for each country. LG Electronics disclaims any direct or indirect responsibility for any consequences arising out of any inaccuracies or consequential changes to this general scheme.
2. It is essential to ensure the minimum amount of water contained in the heating or cooling system.
3. Must fit the insulations on the entire water piping including valves and connections. If necessary, electrical heat tracing system can be installed or the heating system can also be filled with antifreeze (glycol) to prevent any frost damage.
4. In a cold climate region, water drainage from outdoor unit must be frost-proof.
REFERENCED APPLICATION #2-3 SPACE HEATING & COOLING WITH THERMOSTAT
DIP SWITCH SETTINGS
WIRING DIAGRAM
MAIN PCB (HYDRO)
SW1
MONOBLOC UNIT
ON
OFF
1 2 3 4 5 6 7 8
10 11 12 13 14 15 16 17 18 19 20
PUMP (C)
BR BL
N
WATER
SW2
L
ON
MIX PUMP
BR WH BL BR WH BL BR WH BL BR BL BR BL BR BL
N OFF
1 2 3 4 5 6 7 8
L
X : OFF / O : ON
PUMP (B)
N
WATER
DIP SW 1 1 2 3 4 5 6 7 8
3 WAY VALVE MODBUS Master (Link to LG controller) X
(SWITCHING Communication
L
default setting X X X
N
VALVE (B)
DIP SW 2 1 2 3 4 5 6 7 8
3 WAY
CN_TH4
TB_SENSOR
SOLAR Control As Slave O
Heat pump installation (Heating or
cooling circuit only) X X
DEW Accessory
L
Heating only X
Heat Pump Cycle
3 WAY
CN_ROOM2
Remote Room Remote room air sensor is not
X
Air Sensor installed
(Accessory)
7
Heater Capacity
VALVE (A)
N
3
MIXING
VALVE
L1
EXTERNAL
2
PUMP
MAIN PCB (CYCLE)
TB1
1
L
SW1
OFF
25 26 27
3rd Party
1 2 3 4 5 6
BOILER PUMP A2
A
230 V AC / L3 DHW
TB_EXT
X : OFF / O : ON
L3
DIP SW 1 2 3
Always mode : Maintain low noise
mode for target temperature X
Low Noise Mode
Partial mode : Escape low noise
O
EXT
(Default 230 V AC)
L2
C H (On/Off)
(C/H) Peak Control Peak control : To limit maximum
O
current (Power saving)
230 V AC / L1 Cooling
TB2 & TB3
default setting X X
L1
CN_MIX_OUT
N
230 V AC MECHANICAL
L
THERMOSTAT
(3rd party)
NOTE
RS3 MAGNETIC
CONTACTOR 1. The wiring cable size and Circuit breaker selection
CN_REMO
COMMON
HEATER1
HEATER2
3 PHASE
Dry Contact
Antifreeze is applied on primary circuit only LG Extension Cable for Wi-Fi Modem
Remark (PWYREW000)
(Therma V to PHE)
Pressure Gauge Thermostatic Mixing Valve Flow Sensor Wi-Fi Modem Cable Length 10m
LG
Buffer Tank
A water tank containing certain amount of water
that secures the required minimum water volume
1Ø 220-240V AC or 3Ø 380-415V AC
CN_WF
THERMA V TB_EXT_PUMP A2
DIFFERENTIAL
EXTERNAL PUMP_A EXTERNAL PUMP_B PRESSURE
DN25 VALVE
DN25
MAKE UP WATER
SERVICE
THERMA V R32 MONOBLOC S VALVE
NOTE
1. This diagram should be used only for reference purpose. It does not contain all the required equipment and safety components in accordance with actual site conditions. Furthermore, please make sure to take into account the applicable standards and
laws for each country. LG Electronics disclaims any direct or indirect responsibility for any consequences arising out of any inaccuracies or consequential changes to this general scheme.
2. It is essential to ensure the minimum amount of water contained in the heating or cooling system.
3. Must fit the insulations on the entire water piping including valves and connections. If necessary, electrical heat tracing system can be installed or the heating system can also be filled with antifreeze (glycol) to prevent any frost damage.
4. In a cold climate region, water drainage from outdoor unit must be frost-proof.
REFERENCED APPLICATION #3 SPACE HEATING WITH ANTI-FREEZE
DIP SWITCH SETTINGS
WIRING DIAGRAM
MAIN PCB (HYDRO)
SW1
MONOBLOC UNIT
ON
OFF
1 2 3 4 5 6 7 8
10 11 12 13 14 15 16 17 18 19 20
PUMP (C)
BR BL
N
WATER
SW2
L
ON
MIX PUMP
BR WH BL BR WH BL BR WH BL BR BL BR BL BR BL
N OFF
1 2 3 4 5 6 7 8
L
CN_ANTI_SW
X : OFF / O : ON
PUMP (B)
N
WATER
DIP SW 1 1 2 3 4 5 6 7 8
MODBUS Master (Link to LG controller) X
Communication
L
MODBUS REGINE X
Function Unified Open Protocol O
W.TANK
HEATER
SHORT PIN
Antifreeze is not applied X
SHOULD BE Antifreeze Mode Antifreeze is applied (Adjustable
DISCONNECT anti-freeze temp.)
O
L
default setting X X X
N
VALVE (B)
DIP SW 2 1 2 3 4 5 6 7 8
3 WAY
CN_TH4
TB_SENSOR
SOLAR RS3 Control As Slave O
Heat pump installation (Heating or
cooling circuit only) X X
DEW Accessory
L
Heating only X
Heat Pump Cycle
3 WAY
CN_ROOM2
Remote Room Remote room air sensor is not
X
Air Sensor installed
EXTERNAL EXTERNAL (Accessory)
7
PUMP_A PUMP_B
Backup heater is not used X X
Selecting Backup
Half capacity is used O X
N
6
Heater Capacity
VALVE (A)
N
3
MIXING
VALVE
L1
2
1
L
SW1
OFF
25 26 27
3rd Party
1 2 3 4 5 6
BOILER PUMP A2
A
MAGNETIC
TB_EXT
X : OFF / O : ON
L3
CONTACTOR DIP SW 1 2 3
Always mode : Maintain low noise
mode for target temperature X
Low Noise Mode
Partial mode : Escape low noise
O
EXT
(Default 230 V AC)
Max mode X
21 22 23 24
BL BR WH BK
L2
default setting X
POWER X
L1
SUPPLY
1Ø 220 ~ 240 V AC
CN_MIX_OUT
N
L
NOTE
WIFI MODEM
HEATER1
HEATER2
3 PHASE
Power supply of
Main T/B R
CN_WF
Dry Contact
LG Extension Cable for Wi-Fi Modem
(PWYREW000)
Pressure Gauge Thermostatic Mixing Valve Flow Sensor Wi-Fi Modem Cable Length 10m
LG
REMOTE ROOM
AIR SENSOR
RS3
3RD PARTY ACCESSORIES
RAD UFH
External Pump
An external water pump that circulates the water
inside piping when water circuit is segregated or
pump discharge head is insufficient to overcome
total system friction loss.
POWER SUPPLY
ZONE 2 ZONE 1 Magnetic Filter (Recommended)
A magnetic filter that collects metallic particle
caused by corrosion or erosion. It is strongly
recommended to install the magnetic filter to
MIXING
protect heat pump system.
ZONE
TEMP. Buffer Tank
1Ø 220-240V AC or 3Ø 380-415V AC
MODEM MIXING
CN_REMO
Mixing Valve
CN_WF
MIXING A motorized 3-way mixing valve throttling mixing
LG CN_MIX_OUT EXTERNAL
VALVE ratio of heated water and return water.
TB1 17 / 18 PUMP
TB1 1 / 2 / 3 Controlled by THERMA V with 230V power supply.
THERMA V
TB_EXT_PUMP A2
Operating times: 60-900 sec.
DN25
Differential Pressure Valve
A self pressure regulating valve that provides
DN25 DIFFERENTIAL constant differential pressure between supply and
PRESSURE
MAKE UP WATER
VALVE
return headers.
SERVICE
THERMA V R32 MONOBLOC S VALVE
MAGNETIC FILTER
(RECOMMENDED) BUFFER TANK
NOTE
1. This diagram should be used only for reference purpose. It does not contain all the required equipment and safety components in accordance with actual site conditions. Furthermore, please make sure to take into account the applicable standards and
laws for each country. LG Electronics disclaims any direct or indirect responsibility for any consequences arising out of any inaccuracies or consequential changes to this general scheme.
2. It is essential to ensure the minimum amount of water contained in the heating or cooling system.
3. Must fit the insulations on the entire water piping including valves and connections. If necessary, electrical heat tracing system can be installed or the heating system can also be filled with antifreeze (glycol) to prevent any frost damage.
4. In a cold climate region, water drainage from outdoor unit must be frost-proof.
REFERENCED APPLICATION #4 SPACE HEATING WITH 2ND CIRCUIT
DIP SWITCH SETTINGS
WIRING DIAGRAM
MAIN PCB (HYDRO)
SW1
MONOBLOC UNIT
ON
OFF
1 2 3 4 5 6 7 8
10 11 12 13 14 15 16 17 18 19 20
PUMP (C)
BR BL
N
WATER
SW2
L
ON
MIX PUMP
BR WH BL BR WH BL BR WH BL BR BL BR BL BR BL
N OFF
230 V AC 1 2 3 4 5 6 7 8
L
X : OFF / O : ON
PUMP (B)
N
WATER
DIP SW 1 1 2 3 4 5 6 7 8
MODBUS Master (Link to LG controller) X
Communication
L
MODBUS REGINE X
Function Unified Open Protocol O
W.TANK
HEATER
default setting X X X
DIP SW 2 1 2 3 4 5 6 7 8
3 WAY
CN_TH4
TB_SENSOR
SOLAR Control As Slave O
Heat pump installation (Heating or
cooling circuit only) X X
DEW Accessory
L
RAD UFH
VALVE (A)
TEMP. SENSOR
CN_ROOM2
Remote Room Remote room air sensor is not
X
Air Sensor installed
(Accessory)
7
Heater Capacity
VALVE (A)
N
3
MIXING
VALVE
MIXING
2
PUMP
230 V AC / mixing valve close (no mixing) MAIN PCB (CYCLE)
TB1
1
L
EXTERNAL SW1
PUMP
ON For 5/7/9 kW models,
RD BK WH
Controller
OFF
25 26 27
3rd Party
MIXING ZONE 1 2 3 4 5 6
BOILER PUMP A2
TEMPERATURE
A
SENSOR
TB_EXT
MAGNETIC X : OFF / O : ON
L3
CONTACTOR DIP SW 1 2 3
Always mode : Maintain low noise
X
POWER Low Noise Mode
mode for target temperature
L2
default setting X X
L1
CN_MIX_OUT
N
L
NOTE
WIFI MODEM
1. The wiring cable size and Circuit breaker selection
CN_REMO
COMMON
HEATER1
HEATER2
3 PHASE
Power supply of
Main T/B R
CN_WF
Dry Contact
In 2-remo control, RS3 MASTER shows a temperature measured by LG Extension Cable for Wi-Fi Modem
(PWYREW000)
Remark built-in sensor in RS3 SLAVE. (Temperature value measured by RS3 Pressure Gauge Thermostatic Mixing Valve Flow Sensor Wi-Fi Modem Cable Length 10m
MASTER is overriden.) LG
FCU UFH
3RD PARTY ACCESSORIES
External Pump
An external water pump that circulates the water
POWER SUPPLY
inside piping when water circuit is segregated or
pump discharge head is insufficient to overcome
total system friction loss.
RS3
MASTER Magnetic Filter (Recommended)
A magnetic filter that collects metallic particle
2-REMO
CABLE
BUILT IN COMPONENTS
Buffer Tank
- Plate Type Heat Ex.
- Water pump A water tank containing certain amount of water
- Expansion vessel (8 L) POWER that secures the required minimum water volume
CN_REMO
- Safety valve (3 bar) WI-FI SUPPLY for the system or stores heat energy which is
- Pressure sensor MODEM needed for defrosting and reducing start up load.
- Strainer (30 mesh)
- Flow sensor LG 2 Way Valve
MAGNETIC A motorized isolation valve that blocks the water
CONTACTOR 2 WAY flow into underfloor coil in order to prevent water
VALVE condensation during cooling mode.
LG
CN_WF Controlled by THERMA V with 230V power.
Required operating time : less than 90s.
TB1 4 / 6
THERMA V
SERVICE
THERMA V R32 MONOBLOC S VALVE
MAGNETIC FILTER
BUFFER TANK
(RECOMMENDED)
NOTE
1. This diagram should be used only for reference purpose. It does not contain all the required equipment and safety components in accordance with actual site conditions. Furthermore, please make sure to take into account the applicable standards and
laws for each country. LG Electronics disclaims any direct or indirect responsibility for any consequences arising out of any inaccuracies or consequential changes to this general scheme.
2. It is essential to ensure the minimum amount of water contained in the heating or cooling system.
3. Must fit the insulations on the entire water piping including valves and connections. If necessary, electrical heat tracing system can be installed or the heating system can also be filled with antifreeze (glycol) to prevent any frost damage.
4. In a cold climate region, water drainage from outdoor unit must be frost-proof.
REFERENCED APPLICATION #5 SPACE HEATING AND COOLING WITH 2 REMOTE CONTROLLERS
DIP SWITCH SETTINGS
WIRING DIAGRAM
MAIN PCB (HYDRO)
SW1
MONOBLOC UNIT
ON
OFF
1 2 3 4 5 6 7 8
10 11 12 13 14 15 16 17 18 19 20
PUMP (C)
BR BL
N
WATER
SW2
L
ON
MIX PUMP
BR WH BL BR WH BL BR WH BL BR BL BR BL BR BL
N OFF
1 2 3 4 5 6 7 8
L
X : OFF / O : ON
PUMP (B)
N
WATER
DIP SW 1 1 2 3 4 5 6 7 8
MODBUS
2 WAY Communication
Master (Link to LG controller) X
VALVE
L
MODBUS REGINE X
Function Unified Open Protocol O
W.TANK
HEATER
default setting X X X
RS3
N
MASTER
VALVE (B)
DIP SW 2 1 2 3 4 5 6 7 8
3 WAY
CN_TH4
TB_SENSOR
SOLAR SLAVE
Control As Slave O
Heat pump installation (Heating or
cooling circuit only) X X
DEW Accessory
L
Heating only X
Heat Pump Cycle
3 WAY
CN_ROOM2
Remote Room Remote room air sensor is not
X
Air Sensor installed
(Accessory)
7
Heater Capacity
EXTERNAL
VALVE (A)
230 V AC
BR BR BL
N
3
MIXING
VALVE
L1
2
1
L
SW1
OFF
25 26 27
3rd Party
1 2 3 4 5 6
BOILER PUMP A2
A
MAGNETIC
TB_EXT
X : OFF / O : ON
CONTACTOR
L3
DIP SW 1 2 3
Always mode : Maintain low noise
mode for target temperature X
Low Noise Mode
Partial mode : Escape low noise
O
EXT
(Default 230 V AC)
Max mode X
21 22 23 24
BL BR WH BK
L2
default setting X
POWER X
L1
SUPPLY
1Ø 220 ~ 240 V AC
CN_MIX_OUT
N
L
NOTE
WIFI MODEM
1. The wiring cable size and Circuit breaker selection
CN_REMO
COMMON
HEATER1
HEATER2
3 PHASE
Power supply of
Main T/B R
CN_WF
Dry Contact
LG
3RD PARTY
DDC / PLC
CONTROL SYSTEM Flexible Connection Shut Off Valve Magnetic Contactor Thermostat
POWER
1Ø 220-240V AC or 3Ø 380-415V AC
SUPPLY RS3
3RD PARTY ACCESSORIES
MAGNETIC
CONTACTOR External Pump
An external water pump that circulates the water
inside piping when water circuit is segregated or
pump discharge head is insufficient to overcome
TB3
26 / 27
total system friction loss.
LG CN_REMO
Magnetic Filter (Recommended)
TB_EXT_PUMP A2 A magnetic filter that collects metallic particle
THERMA V caused by corrosion or erosion. It is strongly
DIFFERENTIAL recommended to install the magnetic filter to
DN25 PRESSURE
EXTERNAL PUMP protect heat pump system.
BUFFER TANK VALVE
DN25 Buffer Tank
MAKE UP WATER A water tank containing certain amount of water
that secures the required minimum water volume
SERVICE for the system or stores heat energy which is
THERMA V R32 MONOBLOC S #2 VALVE MAGNETIC FILTER needed for defrosting and reducing start up load.
(RECOMMENDED)
SUPPLY RS3
TB3 26 / 27
MAGNETIC
CONTACTOR
LG CN_REMO
TB_EXT_PUMP A2
THERMA V
DIFFERENTIAL
DN25 PRESSURE
EXTERNAL PUMP
BUFFER TANK VALVE
DN25
MAKE UP WATER
SERVICE
THERMA V R32 MONOBLOC S #1 VALVE MAGNETIC FILTER
(RECOMMENDED)
NOTE
1. This diagram should be used only for reference purpose. It does not contain all the required equipment and safety components in accordance with actual site conditions. Furthermore, please make sure to take into account the applicable standards and
laws for each country. LG Electronics disclaims any direct or indirect responsibility for any consequences arising out of any inaccuracies or consequential changes to this general scheme.
2. It is essential to ensure the minimum amount of water contained in the heating or cooling system.
3. Must fit the insulations on the entire water piping including valves and connections. If necessary, electrical heat tracing system can be installed or the heating system can also be filled with antifreeze (glycol) to prevent any frost damage.
4. In a cold climate region, water drainage from outdoor unit must be frost-proof.
REFERENCED APPLICATION #6 SPACE HEATING WITH 3RD PARTY CONTROLLER (MODBUS)
DIP SWITCH SETTINGS
ON
OFF
1 2 3 4 5 6 7 8
SW2
MONOBLOC UNIT #1 MONOBLOC UNIT #2
ON
OFF
1 2 3 4 5 6 7 8
10 11 12 13 14 15 16 17 18 19 20
10 11 12 13 14 15 16 17 18 19 20
PUMP (C)
PUMP (C)
BR BL
BR BL
N
N
WATER
WATER
X : OFF / O : ON
L
L
DIP SW 1 1 2 3 4 5 6 7 8
MODBUS Master (Link to LG controller) X
MIX PUMP
MIX PUMP
Communication
BR BL BR BL BR BL
BR BL BR BL BR BL
N
N
Type Slave (Link to 3rd party controller) O
MODBUS REGINE X
Function Unified Open Protocol O
L
L
Antifreeze is not applied X
Antifreeze Mode Antifreeze is applied (Adjustable
PUMP (B)
PUMP (B)
O
N
N
anti-freeze temp.)
WATER
WATER
default setting X X X
L
L
DIP SW 2 1 2 3 4 5 6 7 8
Indoor Unit Type As Master X
Setting for Group
W.TANK
W.TANK
HEATER
HEATER
N
N
Control As Slave O
Heat pump installation (Heating or
cooling circuit only) X X
Accessory
L
L
Installation Heat pump + DHW tank are installed X O
Information Heat pump + DHW tank + Solar
O X
BR WH BL BR WH BL BR WH BL
BR WH BL BR WH BL BR WH BL
thermal system are installed
N
N
VALVE (B)
VALVE (B)
Heating only X
Heat Pump Cycle
3 WAY
3 WAY
Heating and cooling O
L1
L1
CN_TH4
CN_TH4
TB_SENSOR
TB_SENSOR
SOLAR SOLAR Remote Room Remote room air sensor is not
installed
X
Air Sensor
(Accessory)
DEW DEW Remote room air sensor is installed O
L
L
Backup heater is not used X X
Selecting Backup
AMBIENT AMBIENT Heater Capacity
Half capacity is used O X
N
N
9
9
VALVE (A)
VALVE (A)
Full capacity is used O O
3 WAY
3 WAY
Thermostat Thermostat is not installed X
L1
L1
8
8
Installation Thermostat is installed O
CN_ROOM2
CN_ROOM2
default setting X X X X X X X X
7
7
L
L
N
N
6
6
EXTERNAL EXTERNAL
VALVE (A)
VALVE (A)
2 WAY
2 WAY
PUMP PUMP
L1
L1
5
5
CN_ROOM1
CN_ROOM1
MAIN PCB (CYCLE)
4
4
L
L
SW1
BR BR BL
BR BR BL
N
N
3
3
ON For 5/7/9 kW models,
MIXING
MIXING
VALVE
VALVE
OFF there is no No.6 pin.
L1
L1
2
2
1 2 3 4 5 6
TB1
TB1
1
1
L
L
X : OFF / O : ON
DIP SW 1 2 3
Always mode : Maintain low noise
mode for target temperature X
RD BK WH
RD BK WH
Controller
Controller
25 26 27
25 26 27
3rd Party
3rd Party
Low Noise Mode
L N L N
B
B
Partial mode : Escape low noise
mode for target temperature O
Max mode X
BOILER PUMP A2
BOILER PUMP A2
A
A
Peak Control Peak control : To limit maximum
O
MAGNETIC MAGNETIC current (Power saving)
TB_EXT
TB_EXT
CONTACTOR CONTACTOR default setting X X
L3
L3
EXT
EXT
(Default 230 V AC)
THERMOSTAT
21 22 23 24
21 22 23 24
BL BR WH BK
BL BR WH BK
L2
L2
1Φ 220-240V AC
1Φ 220-240V AC
NOTE
TB2 & TB3
L1
SUPPLY SUPPLY
CN_MIX_OUT
CN_MIX_OUT
N
N
1. The wiring cable size and Circuit breaker selection
must comply with installation manual and
L
L
applicable local regulations.
CN_REMO
COMMON
COMMON
HEATER1
HEATER2
HEATER1
HEATER2
3 PHASE
3 PHASE
POWER POWER
Power supply of Power supply of
SUPPLY
Main T/B 1(L) 2(N) the 1 Phase Model
SUPPLY
Main T/B 1(L) 2(N) the 1 Phase Model
1Ø 220 ~ 240 V AC TB_HEAT_CONTACT 1Ø 220 ~ 240 V AC TB_HEAT_CONTACT
Main T/B R
CN_WF
POWER S T N the 3 Phase Model
POWER S T N the 3 Phase Model
SUPPLY SUPPLY
3Ø 380 ~ 415 V AC 3Ø 380 ~ 415 V AC
DWG NO. :
REFERENCED APPLICATION #7 SPACE HEATING WITH PARALLEL INSTALLATION (LG BECON) REV. 00 10/09/2021
Dry Contact
PI485 Gateway (PMNFP14A1)
LG A gateway device that communicates and controls
through the central controller. (converting LG
Pressure Gauge Thermostatic Mixing Valve Flow Sensor Wi-Fi Modem protocol to RS485 protocol)
It should be installed onto the outdoor unit.
LG
POWER
SUPPLY SPACE HEATING AREA
THERMOSTAT 1 THERMOSTAT 2
MAGNETIC
CONTACTOR 3RD PARTY ACCESSORIES
1Ø 220-240V AC or 3Ø 380-415V AC
CN_REMO
THERMA V
DN25
SERVICE DN25
THERMA V R32 MONOBLOC S #1 VALVE
MAGNETIC FILTER
(RECOMMENDED)
NOTE
1. This diagram should be used only for reference purpose. It does not contain all the required equipment and safety components in accordance with actual site conditions. Furthermore, please make sure to take into account the applicable standards and
laws for each country. LG Electronics disclaims any direct or indirect responsibility for any consequences arising out of any inaccuracies or consequential changes to this general scheme.
2. It is essential to ensure the minimum amount of water contained in the heating or cooling system.
3. Must fit the insulations on the entire water piping including valves and connections. If necessary, electrical heat tracing system can be installed or the heating system can also be filled with antifreeze (glycol) to prevent any frost damage.
4. In a cold climate region, water drainage from outdoor unit must be frost-proof.
REFERENCED APPLICATION #7 SPACE HEATING WITH PARALLEL INSTALLATION (LG BECON)
DIP SWITCH SETTINGS
WIRING DIAGRAM
MAIN PCB (HYDRO)
SW1
MONOBLOC UNIT #1 MONOBLOC UNIT #2
ON
EXTERNAL OFF
PUMP 1 2 3 4 5 6 7 8
10 11 12 13 14 15 16 17 18 19 20
10 11 12 13 14 15 16 17 18 19 20
PUMP (C)
PUMP (C)
BR BL
BR BL
N
N
WATER
WATER
SW2
L
ON
MIX PUMP
MIX PUMP
BR WH BL BR WH BL BR WH BL BR BL BR BL BR BL
BR WH BL BR WH BL BR WH BL BR BL BR BL BR BL
N
N
OFF
L N 1 2 3 4 5 6 7 8
L
L
X : OFF / O : ON
PUMP (B)
PUMP (B)
N
N
WATER
WATER
DIP SW 1 1 2 3 4 5 6 7 8
MODBUS Master (Link to LG controller) X
THERMOSTAT Communication
L
L
Type Slave (Link to 3rd party controller) O
(3rd party)
MODBUS REGINE X
Function Unified Open Protocol O
W.TANK
W.TANK
HEATER
HEATER
N
N
Antifreeze is not applied X
CN_TH4
CN_TH4
Antifreeze Mode Antifreeze is applied (Adjustable
O
anti-freeze temp.)
L
L
default setting X X X
N
N
VALVE (B)
VALVE (B)
DIP SW 2 1 2 3 4 5 6 7 8
3 WAY
3 WAY
Indoor Unit Type As Master X
L1
L1
Setting for Group
TB_SENSOR
TB_SENSOR
SOLAR SOLAR MAGNETIC Control As Slave O
Heat pump installation (Heating or
CONTACTOR X X
CN_ROOM2
CN_ROOM2
cooling circuit only)
DEW DEW Accessory
L
L
Installation Heat pump + DHW tank are installed X O
Information
AMBIENT AMBIENT Heat pump + DHW tank + Solar
thermal system are installed
O X
N
N
9
9
VALVE (A)
VALVE (A)
Heating only X
Heat Pump Cycle
3 WAY
3 WAY
Heating and cooling O
L1
L1
8
8
Remote Room Remote room air sensor is not
X
installed
POWER Air Sensor
(Accessory)
SUPPLY
7
7
Remote room air sensor is installed O
L
L
CN_ROOM1
CN_ROOM1
Backup heater is not used X X
1Ø 220 ~ 240 V AC Selecting Backup
Half capacity is used O X
N
N
6
6
Heater Capacity
VALVE (A)
VALVE (A)
Full capacity is used O O
2 WAY
2 WAY
Thermostat Thermostat is not installed X
L1
L1
5
5
Installation Thermostat is installed O
default setting X X X X X X X X
4
4
L
L
BR BR BL
BR BR BL
N
N
3
3
MIXING
MIXING
VALVE
VALVE
L1
L1
2
2
MAIN PCB (CYCLE)
TB1
TB1
1
1
L
L
SW1
BOILER PUMP A2
BOILER PUMP A2
TB_EXT
TB_EXT
ON For 5/7/9 kW models,
RD BK WH
RD BK WH
Controller
Controller
OFF
25 26 27
25 26 27
3rd Party
3rd Party
there is no No.6 pin.
B
B
1 2 3 4 5 6
EXT
EXT
A
A
X : OFF / O : ON
L3
L3
DIP SW 1 2 3
Always mode : Maintain low noise
mode for target temperature X
Low Noise Mode
Partial mode : Escape low noise
O
(Default 230 V AC)
THERMOSTAT
CN_MIX_OUT
CN_MIX_OUT
Max mode X
21 22 23 24
21 22 23 24
BL BR WH BK
BL BR WH BK
L2
L2
Peak Control Peak control : To limit maximum
O
current (Power saving)
COMMON
COMMON
HEATER1
HEATER2
HEATER1
HEATER2
3 PHASE
3 PHASE
TB2 & TB3
L1
N
N
TB_HEAT_CONTACT RS3 TB_HEAT_CONTACT RS3
L
L
CN_REMO
CN_REMO
NOTE
POWER POWER
Power supply of Power supply of
SUPPLY
Main T/B 1(L) 2(N) the 1 Phase Model
SUPPLY
Main T/B 1(L) 2(N) the 1 Phase Model
1. The wiring cable size and Circuit breaker selection
1Ø 220 ~ 240 V AC 1Ø 220 ~ 240 V AC
must comply with installation manual and
applicable local regulations.
CN_WF
CN_WF
Power supply of Power supply of 2. Make sure that Earth Leakage Circuit Breaker
POWER Main T/B R S T N the 3 Phase Model
POWER Main T/B R S T N the 3 Phase Model
SUPPLY SUPPLY (ELCB) should be installed for power supply line.
3Ø 380 ~ 415 V AC 3Ø 380 ~ 415 V AC
Dry Contact
LG Extension Cable for Wi-Fi Modem
(PWYREW000)
Pressure Gauge Thermostatic Mixing Valve Flow Sensor Wi-Fi Modem Cable Length 10m
LG
HOT WATER
POWER SUPPLY
THERMOSTATIC
RECIR. MIXING VALVE
PUMP (OPTION)
3 WAY
- Pressure sensor DN25 POWER
VALVE (A)
- Strainer (30 mesh) SUPPLY Recirculation Pump
WI-FI
- Flow sensor DN25 An external water pump that circulates the water
MODEM
inside DHW circuit.
Controlled by THERMA V with 230V power.
MAGNETIC
LG
LG CONTACTOR
Magnetic Filter (Recommended)
DN25
CN_WF A magnetic filter that collects metallic particle
THERMA V
TB_EXT_PUMP A2 caused by corrosion or erosion. It is strongly
DIFFERENTIAL recommended to install the magnetic filter to
EXTERNAL PUMP PRESSURE protect heat pump system.
DN25 VALVE
DN25 DN25
Buffer Tank
A water tank containing certain amount of water
MAKE UP WATER
that secures the required minimum water volume
for the system or stores heat energy which is
SERVICE
THERMA V R32 MONOBLOC S VALVE needed for defrosting and reducing start up load.
NOTE
1. This diagram should be used only for reference purpose. It does not contain all the required equipment and safety components in accordance with actual site conditions. Furthermore, please make sure to take into account the applicable standards and
laws for each country. LG Electronics disclaims any direct or indirect responsibility for any consequences arising out of any inaccuracies or consequential changes to this general scheme.
2. It is essential to ensure the minimum amount of water contained in the heating or cooling system.
3. Must fit the insulations on the entire water piping including valves and connections. If necessary, electrical heat tracing system can be installed or the heating system can also be filled with antifreeze (glycol) to prevent any frost damage.
4. In a cold climate region, water drainage from outdoor unit must be frost-proof.
REFERENCED APPLICATION #8 SPACE HEATING AND DHW WITH RECIRCULATION PUMP
DIP SWITCH SETTINGS
WIRING DIAGRAM
DHW TANK HEATING SYSTEM MAIN PCB (HYDRO)
SW1
MONOBLOC UNIT
ON
RECIRCULATION OFF
PUMP 1 2 3 4 5 6 7 8
10 11 12 13 14 15 16 17 18 19 20
PUMP (C)
BR BL
N
WATER
230 V AC SW2
L
ON
MIX PUMP
BR WH BL BR WH BL BR WH BL BR BL BR BL BR BL
N
For General Case OFF
1 2 3 4 5 6 7 8
3 WAY
L
VALVE (A)
X : OFF / O : ON
PUMP (B)
N
WATER
DIP SW 1 1 2 3 4 5 6 7 8
MODBUS Master (Link to LG controller) X
L For OSHA-3V Communication
L
MODBUS REGINE X
2 3 WAY Function Unified Open Protocol O
W.TANK
HEATER
3
6 VALVE (A) Antifreeze is not applied X
Antifreeze Mode Antifreeze is applied (Adjustable
O
anti-freeze temp.)
L
default setting X X X
N
VALVE (B)
DIP SW 2 1 2 3 4 5 6 7 8
3 WAY
CN_TH4
TB_SENSOR
SOLAR SENSOR Control As Slave O
Heat pump installation (Heating or
cooling circuit only) X X
DEW Accessory
L
Heating only X
230 V AC / space heating Heat Pump Cycle
3 WAY
CN_ROOM2
Remote Room Remote room air sensor is not
EXTERNAL X
installed
230 V AC / DHW heating Air Sensor
PUMP (Accessory)
7
Heater Capacity
VALVE (A)
N
3
MIXING
VALVE
L1
2
1
L
SW1
OFF
25 26 27
3rd Party
1 2 3 4 5 6
BOILER PUMP A2
A
MAGNETIC
TB_EXT
X : OFF / O : ON
CONTACTOR
L3
DIP SW 1 2 3
Always mode : Maintain low noise
mode for target temperature X
Low Noise Mode
Partial mode : Escape low noise
O
EXT
(Default 230 V AC)
Max mode X
21 22 23 24
BL BR WH BK
L2
default setting X
POWER X
L1
SUPPLY
1Ø 220 ~ 240 V AC
CN_MIX_OUT
N
L
NOTE
RS3
WIFI MODEM
1. The wiring cable size and Circuit breaker selection
CN_REMO
COMMON
HEATER1
HEATER2
3 PHASE
Power supply of
Main T/B R
CN_WF
Dry Contact
LG Extension Cable for Wi-Fi Modem
(PWYREW000)
Pressure Gauge Thermostatic Mixing Valve Flow Sensor Wi-Fi Modem Cable Length 10m
LG
MAGNETIC
LG CN_WF
CONTACTOR External Pump
DN25 An external water pump that circulates the water
TB1 13 / 14
TB_EXT_PUMP A2 inside piping when water circuit is segregated or
THERMA V
pump discharge head is insufficient to overcome
DIFFERENTIAL
PRESSURE total system friction loss.
EXTERNAL PUMP
DN25 VALVE
Magnetic Filter (Recommended)
DN25 DN25 A magnetic filter that collects metallic particle
MAKE UP WATER caused by corrosion or erosion. It is strongly
recommended to install the magnetic filter to
SERVICE protect heat pump system.
THERMA V R32 MONOBLOC S VALVE
Buffer Tank
MAGNETIC FILTER
BUFFER TANK A water tank containing certain amount of water
(RECOMMENDED)
that secures the required minimum water volume
for the system or stores heat energy which is
needed for defrosting and reducing start up load.
NOTE
1. This diagram should be used only for reference purpose. It does not contain all the required equipment and safety components in accordance with actual site conditions. Furthermore, please make sure to take into account the applicable standards and
laws for each country. LG Electronics disclaims any direct or indirect responsibility for any consequences arising out of any inaccuracies or consequential changes to this general scheme.
2. It is essential to ensure the minimum amount of water contained in the heating or cooling system.
3. Must fit the insulations on the entire water piping including valves and connections. If necessary, electrical heat tracing system can be installed or the heating system can also be filled with antifreeze (glycol) to prevent any frost damage.
4. In a cold climate region, water drainage from outdoor unit must be frost-proof.
REFERENCED APPLICATION #9 SPACE HEATING AND DHW WITH BOOSTER HEATER
DIP SWITCH SETTINGS
BR BL BR BL RD YL ON
DHW TANK HEATING SYSTEM
1(L) 2(N) 3(L) 4(N) 5 OFF
6
1 2 3 4 5 6 7 8
10 11 12 13 14 15 16 17 18 19 20
PUMP (C)
BR BL
N
WATER
POWER
SUPPLY SW2
L
1Ø 220 ~ 240 V AC
ON
MIX PUMP
BOOSTER
BR WH BL BR WH BL BR WH BL BR BL BR BL BR BL
N HEATER OFF
1 2 3 4 5 6 7 8
L
X : OFF / O : ON
PUMP (B)
DIP SW 1 1 2 3 4 5 6 7 8
MODBUS Master (Link to LG controller) X
3 WAY Communication
CN_TANK_HEATER
3 default setting X X X
6 VALVE (A)
N
VALVE (B)
DIP SW 2 1 2 3 4 5 6 7 8
3 WAY
CN_TH4
TB_SENSOR
SOLAR Control As Slave O
Heat pump installation (Heating or
cooling circuit only) X X
DEW Accessory
L
Heating only X
230 V AC / space heating Heat Pump Cycle
3 WAY
CN_ROOM2
Remote Room Remote room air sensor is not
X
installed
230 V AC / DHW heating Air Sensor
(Accessory)
7
Heater Capacity
VALVE (A)
N
3
MIXING
VALVE
L1
2
1
L
SW1
OFF
25 26 27
3rd Party
1 2 3 4 5 6
BOILER PUMP A2
A
MAGNETIC
TB_EXT
X : OFF / O : ON
CONTACTOR
L3
DIP SW 1 2 3
Always mode : Maintain low noise
mode for target temperature X
Low Noise Mode
Partial mode : Escape low noise
O
EXT
(Default 230 V AC)
Max mode X
21 22 23 24
BL BR WH BK
L2
default setting X
POWER X
L1
SUPPLY
1Ø 220 ~ 240 V AC
CN_MIX_OUT
N
L
NOTE
RS3
WIFI MODEM
1. The wiring cable size and Circuit breaker selection
CN_REMO
COMMON
HEATER1
HEATER2
3 PHASE
Power supply of
Main T/B R
CN_WF
Dry Contact
LG Domestic Hot Water Tank
(OSHW-200F/300F/500F)
Pressure Gauge Thermostatic Mixing Valve Flow Sensor Wi-Fi Modem A insulated stainless steel hot water tank with
2.4kW electric heating (230V).
LG
Drain Pressure Reducing Valve Drain Pan Cover Plate DHW Tank Sensor (PHRSTA0)
A temperature sensor for DHW tank. Cable length
12m.
UFH
DHW TANK FCU
HOT WATER
External Pump
POWER SUPPLY An external water pump that circulates the water
THERMOSTATIC
inside piping when water circuit is segregated or
MIXING VALVE
(OPTION)
2 WAY VALVE FOR 2 WAY VALVE FOR pump discharge head is insufficient to overcome
THERMOSTAT THERMOSTAT total system friction loss.
(OPTION)
Magnetic Filter (Recommended)
A magnetic filter that collects metallic particle
caused by corrosion or erosion. It is strongly
1Ø 220-240V AC or 3Ø 380-415V AC
2 Way Valve
TB2 21 / 22 / 23 / 24 A motorized isolation valve that blocks the water
LG TB3 25 MAGNETIC 2 WAY flow into underfloor coil in order to prevent water
DN25 VALVE
CONTACTOR condensation during cooling mode.
TB1 4 / 6
THERMA V Controlled by THERMA V with 230V power.
Required operating time : less than 90s.
EXTERNAL PUMP
DN25 Thermostat
DN25 DN25 A control device that senses the temperature of a
DIFFERENTIAL room and performs actions so that the room's
MAKE UP WATER PRESSURE
VALVE temperature is maintained near a desired setpoint.
SERVICE Thermostat must be connected with Therma V,
THERMA V R32 MONOBLOC S VALVE Valve, Pump, and FCU where applicable.
NOTE
1. This diagram should be used only for reference purpose. It does not contain all the required equipment and safety components in accordance with actual site conditions. Furthermore, please make sure to take into account the applicable standards and
laws for each country. LG Electronics disclaims any direct or indirect responsibility for any consequences arising out of any inaccuracies or consequential changes to this general scheme.
2. It is essential to ensure the minimum amount of water contained in the heating or cooling system.
3. Must fit the insulations on the entire water piping including valves and connections. If necessary, electrical heat tracing system can be installed or the heating system can also be filled with antifreeze (glycol) to prevent any frost damage.
4. In a cold climate region, water drainage from outdoor unit must be frost-proof.
REFERENCED APPLICATION #10 SPACE HEATING, COOLING, AND DHW WITH THERMOSTAT
DIP SWITCH SETTINGS
WIRING DIAGRAM
DHW TANK HEATING SYSTEM MAIN PCB (HYDRO)
SW1
MONOBLOC UNIT
For General Case ON
OFF
3 WAY 1 2 3 4 5 6 7 8
10 11 12 13 14 15 16 17 18 19 20
PUMP (C)
BR BL
N
WATER
VALVE (A)
SW2
L
L For OSHA-3V ON
MIX PUMP
BR WH BL BR WH BL BR WH BL BR BL BR BL BR BL
N OFF
2 3 WAY
3 1 2 3 4 5 6 7 8
VALVE (A)
L
6
X : OFF / O : ON
PUMP (B)
N
WATER
DIP SW 1 1 2 3 4 5 6 7 8
MODBUS
2 WAY Communication
Master (Link to LG controller) X
VALVE
L
MODBUS REGINE X
Function Unified Open Protocol O
W.TANK
HEATER
default setting X X X
N
VALVE (B)
DIP SW 2 1 2 3 4 5 6 7 8
3 WAY
CN_TH4
TB_SENSOR
SOLAR SENSOR Control As Slave O
Heat pump installation (Heating or
cooling circuit only) X X
DEW Accessory
L
Heating only X
230 V AC / space heating Heat Pump Cycle
3 WAY
CN_ROOM2
Remote Room Remote room air sensor is not
X
installed
230 V AC / DHW heating Air Sensor
(Accessory)
7
Heater Capacity
VALVE (A)
230 V AC
BR BR BL
N
3
MIXING
VALVE
L1
EXTERNAL
2
PUMP
MAIN PCB (CYCLE)
TB1
1
L
SW1
OFF
25 26 27
3rd Party
1 2 3 4 5 6
BOILER PUMP A2
A
230 V AC / L3 DHW
TB_EXT
X : OFF / O : ON
L3
DIP SW 1 2 3
Always mode : Maintain low noise
mode for target temperature X
Low Noise Mode
Partial mode : Escape low noise
O
EXT
(Default 230 V AC)
L2
C H (On/Off)
(C/H) Peak Control Peak control : To limit maximum
O
current (Power saving)
230 V AC / L1 Cooling
TB2 & TB3
default setting X X
L1
CN_MIX_OUT
N
230 V AC MECHANICAL
L
THERMOSTAT
(3rd party)
NOTE
RS3 MAGNETIC
WIFI MODEM
CONTACTOR 1. The wiring cable size and Circuit breaker selection
CN_REMO
COMMON
HEATER1
HEATER2
3 PHASE
Dry Contact
LG Extension Cable for Wi-Fi Modem
(PWYREW000)
Pressure Gauge Thermostatic Mixing Valve Flow Sensor Wi-Fi Modem Cable Length 10m
LG
DN25 BUILT IN
POWER SUPPLY
THERMOSTATIC PUMP
MIXING VALVE
(OPTION)
ON/OFF
SIGNAL 3RD PARTY ACCESSORIES
External Pump
1Ø 220-240V AC or 3Ø 380-415V AC
DHW TANK
An external water pump that circulates the water
SENSOR inside piping when water circuit is segregated or
BUILT IN COMPONENTS
TB_EXT_EXT BOILER
- Plate Type Heat Ex. CITY WATER SUPPLY pump discharge head is insufficient to overcome
- Water pump total system friction loss.
- Expansion vessel (8 L) 3 WAY
CN_REMO
NOTE
1. This diagram should be used only for reference purpose. It does not contain all the required equipment and safety components in accordance with actual site conditions. Furthermore, please make sure to take into account the applicable standards and
laws for each country. LG Electronics disclaims any direct or indirect responsibility for any consequences arising out of any inaccuracies or consequential changes to this general scheme.
2. It is essential to ensure the minimum amount of water contained in the heating or cooling system.
3. Must fit the insulations on the entire water piping including valves and connections. If necessary, electrical heat tracing system can be installed or the heating system can also be filled with antifreeze (glycol) to prevent any frost damage.
4. In a cold climate region, water drainage from outdoor unit must be frost-proof.
REFERENCED APPLICATION #11 SPACE HEATING AND DHW WITH EXTERNAL BOILER
DIP SWITCH SETTINGS
WIRING DIAGRAM
DHW TANK HEATING SYSTEM MAIN PCB (HYDRO)
SW1
MONOBLOC UNIT
For General Case ON
OFF
3 WAY 1 2 3 4 5 6 7 8
10 11 12 13 14 15 16 17 18 19 20
PUMP (C)
BR BL
N
WATER
VALVE (A)
SW2
L
L For OSHA-3V ON
MIX PUMP
BR WH BL BR WH BL BR WH BL BR BL BR BL BR BL
N OFF
2 3 WAY
3 1 2 3 4 5 6 7 8
VALVE (A)
L
6
X : OFF / O : ON
PUMP (B)
N
WATER
DIP SW 1 1 2 3 4 5 6 7 8
MODBUS Master (Link to LG controller) X
Communication
L
MODBUS REGINE X
Function Unified Open Protocol O
W.TANK
HEATER
default setting X X X
N
VALVE (B)
DIP SW 2 1 2 3 4 5 6 7 8
3 WAY
CN_TH4
TB_SENSOR
SOLAR SENSOR Control As Slave O
Heat pump installation (Heating or
cooling circuit only) X X
DEW Accessory
L
Heating only X
230 V AC / space heating Heat Pump Cycle
3 WAY
EXTERNAL
CN_ROOM2
Remote Room Remote room air sensor is not
X
230 V AC / DHW heating PUMP Air Sensor installed
(Accessory)
7
Heater Capacity
VALVE (A)
N
3
MIXING
VALVE
L1
2
MAGNETIC
1
L
CONTACTOR
SW1
OFF
25 26 27
3rd Party
1 2 3 4 5 6
BOILER PUMP A2
A
BUILT IN POWER
TB_EXT
X : OFF / O : ON
SUPPLY
L3
PUMP DIP SW 1 2 3
Always mode : Maintain low noise
1Ø 220 ~ 240 V AC mode for target temperature X
Low Noise Mode
ON/OFF SIGNAL Partial mode : Escape low noise
O
EXT
(Default 230 V AC)
Max mode X
21 22 23 24
BL BR WH BK
L2
default setting X X
L1
CN_MIX_OUT
N
L
NOTE
RS3
WIFI MODEM
1. The wiring cable size and Circuit breaker selection
CN_REMO
COMMON
HEATER1
HEATER2
3 PHASE
Power supply of
Main T/B R
CN_WF
Dry Contact
LG Extension Cable for Wi-Fi Modem
(PWYREW000)
Pressure Gauge Thermostatic Mixing Valve Flow Sensor Wi-Fi Modem Cable Length 10m
LG
- Safety valve (3 bar) 3 WAY An external water pump that circulates the water
CN_TH4
NOTE
1. This diagram should be used only for reference purpose. It does not contain all the required equipment and safety components in accordance with actual site conditions. Furthermore, please make sure to take into account the applicable standards and
laws for each country. LG Electronics disclaims any direct or indirect responsibility for any consequences arising out of any inaccuracies or consequential changes to this general scheme.
2. It is essential to ensure the minimum amount of water contained in the heating or cooling system.
3. Must fit the insulations on the entire water piping including valves and connections. If necessary, electrical heat tracing system can be installed or the heating system can also be filled with antifreeze (glycol) to prevent any frost damage.
4. In a cold climate region, water drainage from outdoor unit must be frost-proof.
REFERENCED APPLICATION #12 SPACE HEATING AND DHW WITH BACK-UP HEATER
DIP SWITCH SETTINGS
WIRING DIAGRAM
DHW TANK HEATING SYSTEM MAIN PCB (HYDRO)
SW1
MONOBLOC UNIT
For General Case ON
OFF
3 WAY 1 2 3 4 5 6 7 8
10 11 12 13 14 15 16 17 18 19 20
PUMP (C)
BR BL
N
WATER
VALVE (A)
SW2
L
L For OSHA-3V ON
MIX PUMP
BR WH BL BR WH BL BR WH BL BR BL BR BL BR BL
N OFF
2 3 WAY
3 1 2 3 4 5 6 7 8
VALVE (A)
L
6
X : OFF / O : ON
PUMP (B)
N
WATER
DIP SW 1 1 2 3 4 5 6 7 8
MODBUS Master (Link to LG controller) X
Communication
L
MODBUS REGINE X
Function Unified Open Protocol O
W.TANK
HEATER
default setting X X X
DHW TANK
N
SENSOR
VALVE (B)
DIP SW 2 1 2 3 4 5 6 7 8
3 WAY
CN_TH4
TB_SENSOR
SOLAR Control As Slave O
BACK UP HEATER (Example - HA061M E1) Heat pump installation (Heating or
X X
cooling circuit only)
DEW Accessory
L
CN_ROOM2
Remote Room Remote room air sensor is not
X
installed
230 V AC / DHW heating Air Sensor
1(L) 2(N) 3 4 5 6 7 8 (Accessory)
7
Heater Capacity
VALVE (A)
SUPPLY
1Ø 220 ~ 240 V AC
BR BR BL
N
3
TB4 (Accessory)
MIXING
VALVE
L1
2
E. HEATER
31 32
BK BK
SENSOR
1
B
L
SW1
5 V DC
A
OFF
25 26 27
3rd Party
1 2 3 4 5 6
BOILER PUMP A2
A
MAGNETIC
TB_EXT
X : OFF / O : ON
CONTACTOR
L3
DIP SW 1 2 3
Always mode : Maintain low noise
mode for target temperature X
Low Noise Mode
Partial mode : Escape low noise
O
EXT
(Default 230 V AC)
Max mode X
21 22 23 24
BL BR WH BK
L2
default setting X
POWER X
L1
SUPPLY
1Ø 220 ~ 240 V AC
CN_MIX_OUT
N
L
N
L
NOTE
RS3
WIFI MODEM
1. The wiring cable size and Circuit breaker selection
CN_REMO
COMMON
HEATER1
HEATER2
3 PHASE
Power supply of
Main T/B R
CN_WF
Dry Contact
LG Domestic Hot Water Tank (OSHW-300FD)
A insulated stainless steel hot water tank with
Pressure Gauge Thermostatic Mixing Valve Flow Sensor Wi-Fi Modem 2.4kW electric heating (230V).
Double coil : OSHW-300FD(300L)
LG
COOLING CIRCUIT
THERMOSTAT 1 THERMOSTAT 2
3RD PARTY ACCESSORIES
SOLAR
UFH
PUMP FCU
DHW TANK
External Pump
An external water pump that circulates the water
3 WAY inside piping when water circuit is segregated or
VALVE (B) pump discharge head is insufficient to overcome
HOT WATER total system friction loss.
POWER SUPPLY
THERMOSTATIC Magnetic Filter (Recommended)
MIXING VALVE 2 WAY VALVE FOR 2 WAY VALVE FOR A magnetic filter that collects metallic particle
RS3 DHW TANK THERMOSTAT THERMOSTAT caused by corrosion or erosion. It is strongly
SENSOR (OPTION)
recommended to install the magnetic filter to
protect heat pump system.
Buffer Tank
1Ø 220-240V AC or 3Ø 380-415V AC
- Plate Type Heat Ex. for the system or stores heat energy which is
CITY WATER SUPPLY
- Water pump
TB1 10 / 11 / 12
Thermostat
A control device that senses the temperature of a
room and performs actions so that the room's
temperature is maintained near a desired setpoint.
Thermostat must be connected with Therma V,
NOTE Valve, Pump, and FCU where applicable.
1. This diagram should be used only for reference purpose. It does not contain all the required equipment and safety components in accordance with actual site conditions. Furthermore, please make sure to take into account the applicable standards and
2 Way Valve for Thermostat
laws for each country. LG Electronics disclaims any direct or indirect responsibility for any consequences arising out of any inaccuracies or consequential changes to this general scheme.
A isolation valve paired with thermostat to allow
2. It is essential to ensure the minimum amount of water contained in the heating or cooling system. whether water flows into the water circuit.
3. Must fit the insulations on the entire water piping including valves and connections. If necessary, electrical heat tracing system can be installed or the heating system can also be filled with antifreeze (glycol) to prevent any frost damage.
4. In a cold climate region, water drainage from outdoor unit must be frost-proof. Differential Pressure Valve
A self pressure regulating valve that provides
constant differential pressure between supply and
return headers.
REFERENCED APPLICATION #13 SPACE HEATING, COOLING, AND DHW WITH SOLAR PANEL AND THERMOSTAT
DIP SWITCH SETTINGS
WIRING DIAGRAM
MAIN PCB (HYDRO)
SOLAR THERMAL SYSTEM
SW1
ON
OFF
SOLAR
1 2 3 4 5 6 7 8
PUMP
MONOBLOC UNIT
SW2
ON
3 WAY OFF
PUMP (C)
10 11 12 13 14 15 16 17 18 19 20
BR BL BR BL BR BL
N
WATER
VALVE (B) 1 2 3 4 5 6 7 8
L
X : OFF / O : ON
MIX PUMP
DIP SW 1 1 2 3 4 5 6 7 8
N
TB_SENSOR
SOLAR
BR WH BL BR WH BL BR BL
W.TANK
DIP SW 2 1 2 3 4 5 6 7 8
HEATER
DEW L
For OSHA-3V Indoor Unit Type As Master X
Setting for Group
AMBIENT Control As Slave O
L
CN_TH4
Heating only X
Heat Pump Cycle
Heating and cooling O
230 V AC / bypass (recirculation)
Remote Room Remote room air sensor is not
L
X
Air Sensor installed
DHW TANK (Accessory) Remote room air sensor is installed O
SENSOR
9
N
Selecting Backup
230 V AC / space heating Half capacity is used
3 WAY
O X
Heater Capacity
L1
8
default setting X X X X X X X X
BR BR BL BR WH BL
N
6
VALVE (A)
L1
VALVE
5
SW1
MIXING
VALVE
L1
EXTERNAL ON
2
1 2 3 4 5 6
1
L
X : OFF / O : ON
DIP SW 1 2 3
RD BK WH
Controller
25 26 27
3rd Party
O
A
O
current (Power saving)
default setting X X
EXT
(Default 230 V AC)
THERMOSTAT
L2
C H (On/Off)
(C/H)
230 V AC / L1 Cooling
TB2 & TB3
L1
NOTE
CN_MIX_OUT
N
230 V AC MECHANICAL
1. The wiring cable size and Circuit breaker selection
L
THERMOSTAT
(3rd party) must comply with installation manual and
applicable local regulations.
RS3 MAGNETIC
CONTACTOR 2. Make sure that Earth Leakage Circuit Breaker
CN_REMO
HEATER1
HEATER2
3 PHASE
POWER
Power supply of
SUPPLY
Main T/B 1(L) 2(N) the 1 Phase Model
1Ø 220 ~ 240 V AC TB_HEAT_CONTACT
POWER
SUPPLY
Power supply of
Main T/B R
CN_WF