You are on page 1of 2

Schneider Electric

P3U30 settings report


Date: 9/26/2023 2:48:16 PM

MainLocation Substation
Sublocation MTS CSI
Custom name Protected target
Device name Protection relay
Device type P3U30
Order code P3U30-5AAA1BCAA
Serial number WX223940098

www.schneider-electric.com
PROTECTION P3U30 settings report

VT supervision 60FL

VT supervision 60FL

Enable for 60FL ☑


60FL status -
Neg. sequence V2 0.0 [%]
Neg. sequence I2 0.0 [%]
V2> setting 28.9 [%]
I2< setting 20.0 [%]
Operation delay 0.10 [s]
60FL event on ☑
60FL event off ☑

Table 1 - FAULT LOG

Date hh:mm:ss.ms V2 value I2 value

[1] 2023-09-22 17:21:03.980 31.0 % 0.3 %