Manufacturer:
Test item:
Test Result: The test item passed / failed the test specification(s).
Other Aspects:
- This report consists of X pages and the attachment:
This test report relates to the test sample submitted and list of documents attached.
Approved by /
Tested by: Issued by:
Authorized Signatory:
TEST REPORT
TRF No. BIS_UPS/UPS & Invertor_IS 16242_V1.1
IS 16242 (part 1):2014 / IEC 62040- 1 : 2008
Uninterruptible power systems (UPS) –
Part 1: General and safety requirements for UPS
Report Reference No...................... : xxxxxxxx 001
Date of issue .................................... : (see cover page)
Total number of pages ...................... (see cover page)
Testing Laboratory ......................... :
Address ............................................ :
Manufacturer’s name ..................... :
Address ............................................ :
Test specification:
Standard ........................................... : IS 16242 (part 1) : 2014 /
IEC 62040-1 : 2008
Test procedure ................................. : Compliance Report
Non-standard test method…………..: N/A
Test Report Form No...................... : BIS_UPS/UPS & Invertor_IS 16242_V1.1
Test Report Form(s) Originator ........ : Bureau of Indian Standards
Master TRF ...................................... : 23/01/2015
Test item description ..................... :
Trade Mark ....................................... :
Manufacturer .................................... :
Model/Type reference ...................... :
Ratings ............................................. :
Other Documents Submitted……….:
Approved by /
Tested by: Issued by:
Authorized Signatory:
No. of
Total no. of
Total No. tests/ Page
Test Code Description Measurement/ testing applicable
of tests Req. No.
tests/ Req.
passed
General
EL 2200 Components (Cl.4.5) 10
Requirement
General
EL 2201 Power Interface(Cl.4.6) 04
Requirement
Marking Marking &
EL 2202 58
Requirements instructions(Cl.4.7)
Protection against
EL 2203 Electrical safety shock and energy 19
hazards(Cl.5.1)
Requirement for
EL 2204 Electrical safety 31
axillary circuits (Cl.5.2)
Protective earthing and
EL 2205 Electrical safety 22
bonding(Cl.5.3)
AC and D.C power
EL 2206 Electrical safety 13
isolation(Cl. 5.4)
Over current and earth
EL 2207 Electrical safety 10
fault condition(Cl.5.5)
Safety
EL 2208 Electrical safety 22
interlocks(Cl.5.6)
Clearances, Creepage
distances and
EL 2209 Electrical safety 60
distances through
insulation (Cl.5.7)
Wiring, connections
EL 2210 Wiring and supply - 12
General(Cl.6.1)
Connection to power
EL 2211 Wiring 12
(Cl.6.2)
Wiring terminals for
EL 2212 Wiring external power 09
conductors (Cl.6.3)
Mechanical
EL 2213 Enclosure (Cl.7.1) 02
properties
Mechanical
EL 2214 Stability (Cl.7.2) 04
properties
Mechanical Mechanical strength
EL 2215 12
properties (Cl.7.3)
Mechanical Construction
EL 2216 20
properties details(CL.7.4)
Resistance to fire
EL 2217 Fire safety 21
(Cl.7.5)
Mechanical
EL 2218 Battery location (Cl.7.6) 09
properties
Thermal Temperature rise
EL 2219 06
properties (Cl.7.7)
Insulation General provision for
EL 2220 05
properties earth leakage (Cl.8.1)
Measuring instruments
Insulating
EL 2227 for touch current tests 03
properties
( Annex D)
Thermal Temperature rise of a
EL 2228 01
properties winding ( Annex E)
Measurement of
Insulating clearance and
EL 2229 01
properties creepage distances
(Annex F)
Alternative method of
Insulating
EL 2230 determining minimum 18
properties
clearance ( Annex G)
Protection against
Mechanical Ingress of water and
EL 2231 01
properties foreign objects
(Annex H)
Backfeed Protection
EL 2232 Electrical Safety 07
test (Annex I)
Table of
EL 2233 Electrical Safety electrochemical 01
potentials (Annex J)
General Thermal controls
EL 2234 07
Requirements (Annex K)
General Reference loads
EL 2235 08
Requirements (Annex L)
Ventilation of battery
Mechanical
EL 2236 compartments 05
properties
(Annex M)
Certificate: It is certified that the above tests were performed and found to be passing/Failing in the
requirement tested.
...............................................................................
(Approving Authority)
Copy of trademark
No. of pages in
Attachment No. Attachment Description
Attachment
General remarks:
The test results presented in this report relate only to the object tested.
This report shall not be reproduced, except in full, without the written approval of the Issuing testing laboratory.
Testing ..........................................................................:
Date of receipt of test item ............................................ :
Date(s) of performance of tests .................................... :
Laboratory conditions ................................................:
Ambient Temperature ................................................... :
Ambient Humidity .......................................................... :
IP protection class ........................................................ : IPXX or Not rated, indoor use only ???
Altitude during operation (m) ....................................... : Up to 2000
Altitude of test laboratory (m) ....................................... : < 1000
Mass of equipment (kg) ............................................... :
Abbreviations that may be used throughout this test report:
PE/PB .............. : protective earth/protective bonding Pri ..................... : primary
CB .................... : circuit breaker sec .................... : secondary
(SW)PS ............ : (switching) power supply gnd ................... : ground
HV .................... : high voltage I/O ..................... : input/output
PCB .................. : printed circuit (wiring) board ii ........................ : installation instruction
TIW ................... : triple insulated wire PSU .................. : Power Supply Unit
B/I ..................... : built-in application (compliance shall be guarantee in host equipment)
F/B/S/R : Functional/Basic/Supplementary/Reinforced Insulation
Certificate: It is certified that the above tests were performed and found to be passing/failing in the
requirement tested.
...............................................................................
(Approving Authority
Cl. No. Test / Requirement name Test Code Test result/ observation Verdict
4.6 Power Interface* EL-2201-00
1.6.1/RD AC power distribution systems* EL-2201-01
Certificate: It is certified that the above tests were performed and found to be passing/failing in the
requirement tested.
...............................................................................
(Approving Authority
Certificate: It is certified that the above tests were performed and found to be passing/failing in the
requirement tested.
...............................................................................
(Approving Authority
Certificate: It is certified that the above tests were performed and found to be passing/failing in the
requirement tested.
...............................................................................
(Approving Authority )
2.3.2.4/RD EL-2204-10
Protection by other constructions .........................
2.3.3/RD Separation from hazardous EL-2204-11
voltages
2.3.4/RD Connection of TNV circuits to EL-2204-12
other circuits
2.3.5/RD Test for operating voltages EL-2204-13
generated externally
5.2.3 Limited current circuits* EL-2204-14
2.4/RD
2.4.1/RD General requirements EL-2204-15
Certificate: It is certified that the above tests were performed and found to be passing/failing in the
requirement tested.
...............................................................................
(Approving Authority )
Certificate: It is certified that the above tests were performed and found to be passing/failing in the
requirement tested.
...............................................................................
(Approving Authority )
Certificate: It is certified that the above tests were performed and found to be passing/failing in the
requirement tested.
...............................................................................
(Approving Authority )
Certificate: It is certified that the above tests were performed and found to be passing/failing in the
requirement tested.
...............................................................................
(Approving Authority )
Cl. No. Test / Requirement name Test Code Test result/ observation Verdict
5.6 Protection of personnel – EL-2208-00
Safety interlocks*
5.6.1 / 2.8/RD Operator protection*
2.8.1/RD General principles* EL-2208-01
Certificate: It is certified that the above tests were performed and found to be passing/failing in the
requirement tested.
...............................................................................
(Approving Authority)
Certificate: It is certified that the above tests were performed and found to be passing/failing in the
requirement tested.
...............................................................................
(Approving Authority)
10 N pull test
3.1.10/RD Sleeving on wiring* EL-2210-10
Certificate: It is certified that the above tests were performed and found to be passing/failing in the
requirement tested.
...............................................................................
(Approving Authority)
Type ................................................................
Rated current (A), cross-
sectional area (mm²), AWG .............................
3.2.5.2/RD DC power supply cords* EL-2211-05
Certificate: It is certified that the above tests were performed and found to be passing/failing in the
requirement tested.
...............................................................................
(Approving Authority)
Certificate: It is certified that the above tests were performed and found to be passing/failing in the
requirement tested.
...............................................................................
(Approving Authority)
Certificate: It is certified that the above tests were performed and found to be passing/failing in the
requirement tested.
...............................................................................
(Approving Authority)
Certificate: It is certified that the above tests were performed and found to be passing/failing in the
requirement tested.
...............................................................................
(Approving Authority)
Certificate: It is certified that the above tests were performed and found to be passing/failing in the
requirement tested.
...............................................................................
(Approving Authority)
Certificate: It is certified that the above tests were performed and found to be passing/failing in the
requirement tested.
...............................................................................
(Approving Authority)
Certificate: It is certified that the above tests were performed and found to be passing/failing in the
requirement tested.
...............................................................................
(Approving Authority)
Certificate: It is certified that the above tests were performed and found to be passing/failing in the
requirement tested.
...............................................................................
(Approving Authority)
Certificate: It is certified that the above tests were performed and found to be passing/failing in the
requirement tested.
...............................................................................
(Approving Authority)
Certificate: It is certified that the above tests were performed and found to be passing/failing in the
requirement tested.
...............................................................................
(Approving Authority)
Certificate: It is certified that the above tests were performed and found to be passing/failing in the
requirement tested.
...............................................................................
(Approving Authority)
Certificate: It is certified that the above tests were performed and found to be passing/failing in the
requirement tested.
...............................................................................
(Approving Authority)
Certificate: It is certified that the above tests were performed and found to be passing/failing in the
requirement tested.
...............................................................................
(Approving Authority)
Certificate: It is certified that the above tests were performed and found to be passing/failing in the
requirement tested.
...............................................................................
(Approving Authority)
Certificate: It is certified that the above tests were performed and found to be passing/failing in the
requirement tested.
...............................................................................
(Approving Authority)
Certificate: It is certified that the above tests were performed and found to be passing/failing in the
requirement tested.
...............................................................................
(Approving Authority)
Cl. No. Test / Requirement name Test Code Test result/ observation Verdict
D/RD Annex D, Measuring EL-2227-00
instruments for touch current
tests (see 5.1.4/RD)
D.1/RD Measuring instrument EL-2227-01
D.2/RD Alternative measuring EL-2227-02
instrument
Certificate: It is certified that the above tests were performed and found to be passing/failing in the
requirement tested.
...............................................................................
(Approving Authority)
Certificate: It is certified that the above tests were performed and found to be passing/failing in the
requirement tested.
...............................................................................
(Approving Authority)
Cl. No. Test / Requirement name Test Code Test result/ observation Verdict
F/RD Annex F, Measurements of EL-2229-00
clearances and creepage
distance (see 2.10/RD and
Annex G/RD)
Certificate: It is certified that the above tests were performed and found to be passing/failing in the
requirement tested.
...............................................................................
(Approving Authority)
Certificate: It is certified that the above tests were performed and found to be passing/failing in the
requirement tested.
...............................................................................
(Approving Authority)
Certificate: It is certified that the above tests were performed and found to be passing/failing in the
requirement tested.
...............................................................................
(Approving Authority)
Certificate: It is certified that the above tests were performed and found to be passing/failing in the
requirement tested.
...............................................................................
(Approving Authority)
Certificate: It is certified that the above tests were performed and found to be passing/failing in the
requirement tested.
...............................................................................
(Approving Authority)
Certificate: It is certified that the above tests were performed and found to be passing/failing in the
requirement tested.
...............................................................................
(Approving Authority)
Cl. No. Test / Requirement name Test Code Test result/ observation Verdic
t
L Annex L, Reference load* EL-2235-00
L.1 General* EL-2235-01
L.2 Reference resistive load* EL-2235-02
L.3 Reference inductive-resistive EL-2235-03
load*
L.4 Reference capacitive-resistive EL-2235-04
loads*
L.5 Reference non-linear load*
L.5.1 General* EL-2235-05
L.5.2 Test method* EL-2235-06
L.5.3 Connection of the non-linear EL-2235-07
reference load*
Certificate: It is certified that the above tests were performed and found to be passing/failing in the
requirement tested.
...............................................................................
(Approving Authority)
Cl. No. Test / Requirement name Test Code Test result/ observation Verdict
M Annex M, Ventilation of battery EL-2236-00
compartments*
M.1 General* EL-2236-01
Certificate: It is certified that the above tests were performed and found to be passing/failing in the
requirement tested.
...............................................................................
(Approving Authority)
Supplementary information:
1. An asterisk indicates a mark that assures the agreed level of surveillance.
Supplementary information:
Note(s):
Supplementary information:
Supplementary information:
Supplementary information:
Supplementary information:
Supplementary information:
Basic / supplementary:
Reinforced:
Supplementary information:
Supplementary information:
Supplementary information:
Supplementary information:
Supplementary information:
Supplementary information:
Supplementary information:
Basic / supplementary:
Reinforced:
Supplementary information:
Supplementary information:
Basic / supplementary:
Reinforced:
Supplementary information: