You are on page 1of 1

1 2 3 4 5 6 7 8 9 10

LOCATION

C-1 C-2 C-3 C-4 C-5 C-6 C-7 C-8 C-9


The copyrights of this drawing are the property os "HMV INGENIEROS LTDA." who is expnerated of any responsability if this drawing is altered or modified in its fundamental design by the project owner, by its agent or by third parties; or if the construction is not executed in agreement with the drawing. Partial or full reproduction or any use for purposes

DP-5.2
CT 2,4,6 DP-4.2
DP 4.2 EDB-5.2
CT 7,9,11
A
C-A DP-4.2 A
CT 20,22
400 mm x 80 mm 400 mm x 80 mm
Ø1 1/2" IMC EDB-5.2 200 mm x 80 mm
ELECTRICAL FACILITIES ELECTRICAL FACILITIES
Ø1 1/2" IMC TOP CABLE TRAY Ø1" IMC ELECTROMECHANICAL
TOP CABLE TRAY CABLE TRAY

600 mm x 80 mm 600 mm x 80 mm
ELECTROMECHANICAL ELECTROMECHANICAL
LOWER CABLE TRAY LOWER CABLE TRAY CT 13,15,17
DP-5.2
CONVENTIONS
Ø1 1/2" IMC

Ø1" IMC Ø1" IMC

Ø1" IMC

C-B

400 mm x 80 mm
ELECTRICAL FACILITIES Ø1" IMC
B TOP CABLE TRAY CT 2,4,6 B
CT 1,3,5 DP-5.2
400 mm x 80 mm DP-5.2
ELECTROMECHANICAL CT 7,9,11
400 mm x 80 mm LOWER CABLE TRAY DP-5.2
ELECTRICAL FACILITIES
TOP CABLE TRAY
CT 1,3,5
DP-4.2
600 mm x 80 mm
ELECTROMECHANICAL NOTES
LOWER CABLE TRAY

C-C

400 mm x 80 mm
ELECTRICAL FACILITIES
TOP CABLE TRAY

600 mm x 80 mm
CT 8,10,12 ELECTROMECHANICAL
LOWER CABLE TRAY CTO 8,10,12
DP-4.2 DP-5.2
IMC Ø2"
Ø1" IMC

C C
C-D

400 mm x 80 mm
400 mm x 80 mm
ELECTRICAL FACILITIES
ELECTRICAL FACILITIES TOP CABLE TRAY
TOP CABLE TRAY

Ø1" IMC Ø1" IMC Ø1" IMC Ø1" IMC Ø1" IMC CT 1,3
C-E CT 14,16,18 CT 1,3,5
EDB-5.4
CT 8,10,12 400 mm x 80 mm
DP-4.1 DP-5.1
400 mm x 80 mm DP-5.1 ELECTROMECHANICAL
CTO 8,10,12 ELECTROMECHANICAL CT 1,3,5 LOWER CABLE TRAY SPECIFICATIONS
DP-4.1 LOWER CABLE TRAY DP-4.1 EDB-5.4 DP-5.3
Ø1" IMC
CT 5
EDB-5.4

CT 6
EDB-5.4
CT 19,21,23
C-F DP-4.1
D D
400 mm x 80 mm
ELECTRICAL FACILITIES
400 mm x 80 mm TOP CABLE TRAY
ELECTRICAL FACILITIES
TOP CABLE TRAY 400 mm x 80 mm
600 mm x 80 mm
ELECTROMECHANICAL
ELECTROMECHANICAL
CABLE TRAY
600 mm x 80 mm LOWER CABLE TRAY
ELECTROMECHANICAL
LOWER CABLE TRAY

CT 1,3,5
C-G DP - 5.3
Ø1" IMC

400 mm x 80 mm 400 mm x 80 mm
ELECTRICAL FACILITIES ELECTRICAL FACILITIES
TOP CABLE TRAY TOP CABLE TRAY REFERENCE DOCUMENTS
1. 3418-ID-EL-DW-004-04: ELECTRICAL RACEWAYS - MACHINE &
COMPONENT SHOP
Ø1" IMC Ø1" IMC 600 mm x 80 mm Ø1 1/2" IMC Ø1" IMC 2. 3418-ID-EL-DW-013-01: CABLE TRAYS, CONDUITS AND EQUIPMENT
Ø1" IMC CT 13,15,17 Ø1" IMC 600 mm x 80 mm Ø1" IMC Ø2" IMC
CT 7,9,11 ELECTROMECHANICAL CT 2,4,6 CONNECTION MOUNTING DETAILS
E DP-4.1 ELECTROMECHANICAL E
CT 13,15,17 DP-4.1 LOWER CABLE TRAY LOWER CABLE TRAY DP-5.1 3. 3418-ID-EL-MC-006: LOAD CHART FOR ELECTROMECHANICAL
CTO 2,4,6 CT 7.9.11
DP-4.1 DP-5.1 EP-5 CT 2,4,6 EQUIPMENTS DISTRIBUTION PANELBOARDS
C-H DP-4 DP-4.1 DP-5.1 EDB-5.3 DP-5.3 4. 3418-ID-MC-DW-1204-01: MACHINE SHOP GENERAL HVAC PLANS,
CT 2 CT 4 ELECTRICAL PLANS
DP-4.1 Ø1 1/2" IMC
EP-4 200 mm x 80 mm EDB-5.4 EDB-5.4
CT 13,15,17
ELECTRICAL FACILITIES DP-5
EDP-4.1 CABLE TRAY Ø1" IMC
MS-105
MS-101 MS-101 200 mm x 80 mm Ø1" IMC AE - 1 AE - 2
CT 12-14
CT 5-7 CT 9.11 ELECTRICAL FACILITIES CT 1-3-5 CT 2-4-6
EP-5
EP-4 EP-4 CABLE TRAY KD-2CT EP-5 EP-5
7-9-11 CT 8,10,12 Ø1" IMC
EP-5 DP-5
Ø1" IMC Ø1" IMC DP-5
C-I
MS-105
MS-101 MS-101
CT 8-10
CT 1-3 CT 6-8 EP-5
EP-4 HOLDS
EP-4

F
LEVEL 1 - ELECTROMECHANICAL EQUIPMENT POWER SUPPLY - MACHINE SHOP & COMPONENT SHOP F
SCALE 1 : 100

CONVENTIONS NOTES ELECTROMECHANICAL PANELBOARDS LIST


TAG DESCRIPTION
EM 1. THIS DRAWING IS VALID ONLY FOR ELECTROMECHANICAL EQUIPMENT POWER
ELECTROMECHANICAL EQUIPMENT SUPPLY SYSTEM. DP-4 COMPONENT SHOP DISTRIBUTION PANELBOARD
POWER OUTLET, 440/254 V. DP-4.1 TRANSMISSION ASSEMBLY & DISASSEMBLY DISTRIBUTION PANELBOARD
EM 2. ELECTROMECHANICAL EQUIPMENT POWER SUPPLY SYSTEM INSTALLATION MUST BE
COORDINATED WITH OTHER SYSTEMS (COMMUNICATIONS, AIR CONDITIONING, DP-4.2 DISASSEMBLY & ASSEMBLY DISTRIBUTION PANELBOARD
ELECTROMECHANICAL EQUIPMENT
POWER OUTLET, 220/127 V. HYDROSANITARY SYSTEM, SECURITY, ETC). DP-5 MACHINE SHOP DISTRIBUTION PANELBOARD
3. ALL ELECTRICAL INSTALLATIONS MUST BE EXECUTED IN ACCORDANCE WITH NFPA DP-5.1 COMPONET SHOP DISTRIBUTION PANELBOARD
PHASE CONDUCTOR 70 - NATIONAL ELECTRICAL CODE (NEC) HANDBOOK 2020. DP-5.2 MACHINE SHOP DISTRIBUTION PANELBOARD
4. ALL BOXES, METALLIC CONDUITS, CABLE TRAYS, AND METALLIC STRUCTURES MUST DP-5.3 RECEIVING AREA 440 V. DISTRIBUTION PANELBOARD
GROUNDING CONDUCTOR BE GROUNDED.
G EDB-5.2 G
MACHINE & COMPONENT SHOP 220 V. DISTRIBUTION PANELBOARD
INTERMEDIATE METAL CONDUIT (IMC) 5. TO FACILITATE THE WIRING WORKS, BOXES SHALL BE INSTALLED AT EACH EDB-5.4 RECEIVING AREA 220 V. DISTRIBUTION PANELBOARD
ELECTRICAL METALLIC TUBING (EMT) HORIZONTAL CHANGE OF DIRECTION. ADDITIONAL BOXES THAT MAY BE REQUIRED EP-4 HVAC ELECTRICAL PANELBOARDS, PROVIDED BY HVAC SYSTEM
SHALL BE PROPOSED AND INSTALLED ON-SITE DURING THE EXECUTION. O 2022-05-06 ISSUED FOR CONSTRUCTION A.M.G M.D.P A.H.J A.C.M

ELECTROMECHANICAL CABLE TRAY EP-5 HVAC ELECTRICAL PANELBOARDS, PROVIDED BY HVAC SYSTEM
A 2022-02-22 ISSUED FOR CLIENT REVIEW A.M.G M.D.P A.H.J A.C.M
6. ONLY JOINTS AND CABLE SPLICING SHALL BE ALLOWED IN JUNCTION BOXES, NOT IN
CONDUITS. JUNCTION BOXES SHALL BE 4"x4" GALVANIZED METALLIC. REV. DATE MODIFICATION DRAWN BY DESIG. BY REV. BY APPR. BY
ELECTRICAL FACILITIES CABLE TRAY REVISIONS
7. ALL WIRING SHALL BE THHN/THWN 90°C TYPE, MULTICONDUCTOR TYPE FOR CABLE
ELECTROMECHANICAL TRAYS AND SINGLE CONDUCTOR FOR CONDUITS. SEE LOAD CHART IN REFERENCE 3.
CABLE TRAY WITH COVER
8. ALL ELECTRICAL INSTALLATIONS SHALL BE EXECUTED WITH TECHNICAL CRITERIA IN
ELECTRICAL DISTRIBUTION ORDER TO HAVE A SAFE AND AESTHETIC ELECTRICAL SYSTEM.
other than the project is strictly forbidden.

PANELBOARDS
9. ELECTRICAL CONDUIT SHALL BE EMT 3/4", WITH THE EXCEPTION OF THOSE
D:\HMV\BOGOTA\3418 MACORP\FORMATO B1 MACORP - HMV.rfa

INDICATED ON THE DRAWING. ALL CONDUITS EXPOSED TO DAMAGE OR HUMIDITY INGENIEROS


SHALL BE IMC TYPE.

10. CABLE TRAY SIZING IS BASED ON NEC 2020, SECTION 392.

11. ELECTROMECHANICAL EQUIPMENT SUPPLIER MUST PROVIDE A VISIBLE SWITCH OR PROJECT:


DISCONNECTOR DEVICE FOR MAINTENANCE WORKS.

12. EQUIPMENT SUCH AS MOTORS, FANS AND DRIVERS, EXPOSED TO VIBRATIONS MUST
MACORP NEW FACILITIES - GUYANA
INCLUDE A FLEXIBLE METAL CONDUIT 1,80 M LENGTH.

13. SOFT STARTERS AND VFD THAT MAY BE REQUIRED FOR ELECTROMECHANICAL DRAW SCALE: IDICATED PLOT SCALE: 1:1 DIM: mm
H LOADS, ARE NOT PART OF THE SCOPE OF THE ELECTRICAL SUPPLY. H
TITLE:

ELECTROMECHANICAL EQUIPMENTS POWER


BUILDING LOCATION

FORMAT B1: (1000 x 707)


SUPPLY – MACHINE & COMPONENT SHOP
SCALE 1 : 3000
FILE LOCATION:

DRAWING No.: SHEET: REV.

3418-ID-EL-DW-012-04 04 OF 08 0
1 2 3 4 5 6 7 8 9 10
TEMPLATE HMV: HMV-00-CD-TM-001 FILE: FORMATO B1 MACORP - HMV.rfa

You might also like