Professional Documents
Culture Documents
Richards MFG DS-25JD
Richards MFG DS-25JD
P925JD
D
15/25/28kV Deadbreak Junctions
Product Data Sheet
The 15/25kV Deadbreak Junction provides
multiple 600 or 900A 15/25kV Deadbreak
Bushing interfaces (IEEE 386, Interface 11)
connected to a common contact. Junctions
are commonly installed in enclosures
but also canC be mounted directly to an
underground structure such as the wall
of a vault. 8 7 6 5 4 3
C 8 7 6 5 4 3 2
Features A
D
< Injection Molded & Peroxide-Cured PROPRIETARY AND CONFIDENTIAL
THE INFORMATION CONTAINED IN THIS
DRAWING IS THE SOLE PROPERTY OF
<INSERT COMPANY NAME HERE>. ANY
APP
8 7 6 5 4 3
< Fully-Shielded/Deadfront
B
< Designed, Molded, and Tested in the
USA
8 7 6 5 4 3
B
DS-25JD [D] Richards Manufacturing, Inc. | 517 Lyons Avenue, Irvington, NJ 07111 | 973.371.1771 | www.richards-mfg.com 0622
P625JD
P925JD
15/25/28kV Deadbreak Junctions
Detail View
Installation
15/25kV Deadbreak Junction installation is covered by:
RP-II-JX
Threaded
IEEE 386
Related Products Contact
Interface 11
P625HIP-STUD P925HIP-STUD
15/25kV Aluminum Threaded 15/25kV Copper Threaded
Stud Stud
62LCN/62LCT 92LCN/92LCT
15/25kV Deabreak Elbow 15/25kV Deabreak Elbow Stack Height =
6" (152mm)
P6AL-X P9CU-X
Aluminum Compression Copper Compression
Connector Connector
P7ALCU-X
Copper-Top Compression Connector
Applications
Product Ratings
Outdoor Vaults Enclosures
Voltage Ratings
Direct Bury Submersible Maximum Voltage Rating – (phase to ground) 15.2kV
Corona Voltage Level – (partial discharge extinction voltage) 22kV
Production Testing AC Withstand – (1 minute) 42kV
Impulse-Withstand Voltage – (BIL) 162kV BIL
IEEE requires a Partial Discharge test and choice between AC
withstand and Impulse.
Continuous Current Ratings
Richards runs 3/3 tests on all Medium Voltage products Aluminum 600A
governed by IEEE 386. Copper 900A
100% Routine Electrical Test:
Short-Time Current Ratings
< Partial Discharge
Aluminum 25kA, 10c. and 10kA, 3s.
< AC Withstand
Copper 40kA, 10c. and 10kA, 3s.
< Impulse Withstand
The 15/25kV Deadbreak Junction is qualified to the following industry standards:
< IEEE Std 386: For Separable Insulated Connector Systems
< ANSI C119.4: For Electric Connectors
< IEEE Std 592: For Exposed Semiconducting Shields
DS-25JD [D] Richards Manufacturing, Inc. | 517 Lyons Avenue, Irvington, NJ 07111 | 973.371.1771 | www.richards-mfg.com 0622
P625JD
P925JD
15/25/28kV Deadbreak Junctions
Junction Dimensions - Bracket
Dimensional Chart
L1
Ø 9/16"
# Of Spacing L2 (14 mm)
L1 L2 L3
Positions (S)
S
4" 19" 8" 11"
3 L3
6" 27" 12" 15"
# Of Spacing L*
Positions (S) S
4" 7"
2
5" 4 5/8"
6" 9" 6" 3"
(127 mm (117 mm
(152 mm) (76 mm)
MAX) MIN)
4" 11"
3 7
/8"
6" 15" (22 mm)
Ø 9/16"
(14 mm)
4" 15"
4
6" 21"
* U Straps for 4” spaced Junctions are available with 5” hole to hole spacing. Contact factory for more information.
DS-25JD [D] Richards Manufacturing, Inc. | 517 Lyons Avenue, Irvington, NJ 07111 | 973.371.1771 | www.richards-mfg.com 0622