General specification for 11 KV switchgear

TYPE SINGLE BUSBAR

STANDARAD IEC

12 kV Rated Voltage

11kv Service voltage

75kV Peak withstand voltage

50Hz Rated Frequency

25 kA for 3s Rated Short Time withstand current

63kA Peak Withstand Current

1250A Rated Current of Main busbars

Up to 1250A Rated Current of Feeders (630A-1250A)

Busbar Configuration Single


Altitude of installation Up to 1000 m

No of panels : 4 incoming -2 spares- 5 transformer feeder -1


bus section unit
VDC 48V control Auxiliary voltage
Vacuum ABB VD4/P circuit breaker type

Mechanical Characteristics of the switchgear


PM Partition Class

IP4X (External), IP 2X between compartments Degree Of Protection

LSC2B Service Continuity

Vacuum Switching Medium

Withdrawable Construction of Switching Medium

Spring Charged Electrical/Mechanical Mechanism of Switching Medium

Front/Rear Cable Access

Bottom-Rear Cable Entry

RAL 7035 Standard Paint Finish


Free-standing Arrangement of switchgear
-5 to +50 Ambient operating temp.