TABLEOFCONTENTS

ARCHITECTURAL
LOCATIONMAP
VICINITYMAP
AR-01 FRONTPERSPECTIVE
REARPERSPECTIVE

GROUND FLOOR PLAN


SECOND FLOOR PLAN
ROOF PLAN
AR-02 FRONT ELEVATION
RIGHT ELEVATION
REAR ELEVATION

GROUND FLOOR REFLECTED CEILING PLAN


SECOND FLOOR REFLECTED CEILING PLAN
AR-03 LONGITUDINAL SECTION
CROSS SECTION
SCHEDULE OF DOORS AND WINDOWS

STRUCTURAL

GENERAL NOTES
FOUNDATION PLAN
ST-01 SECOND FLOOR FRAMING PLAN
ROOF FRAMING PLAN
ROOF TRUSS PLAN

SCHEDULE OF COLUMN
TYPICAL COLUMN DETAIL
TYPICAL FOOTING DETAIL
S1 LOCATION MAP FOOTING SCHEDULE
A1 FRONT-RIGHT PERSPECTIVE ST-02 SCHEDULE OF SLAB
TYPICAL SLAB DETAIL
SCHEDULE OF BEAMS
TYPICAL BEAM DETAIL

FOUNDATION PLAN
ST-03 SECOND FLOOR FRAMING PLAN
THIRD FLOOR FRAMING PLAN
ROOF FRAMING PLAN

PLUMBING/SANITARY

GROUND FLOOR WATER LINE LAYOUT


SECOND FLOOR WATERLINE LAYOUT
PL-01
GROUND FLOOR SANITARY LINE LAYOUT
SECOND FLOOR SANITARY LINE LAYOUT

ELECTRICAL

GENERAL NOTES
LEGEND
EL-01 GROUND FLOOR ELECTRICAL LAYOUT
SECOND FLOOR ELECTRICAL LAYOUT

S1 VICINITY MAP A4 REAR-RIGHT PERSPECTIVE

PRC NO:
SEAL: ENGINEER: 0194991 PROJECT TITLE: OWNER: SHEET NO:
VALIDITY:
07/13/2026
PTR NO: CALLSITA-END HOUSE EXTENSION
12578064J
ENGR. AUDWIN GAREY G. FESTIN DATE: Amanda Somera Ordonez AR - 01
LICENSED CIVIL ENGINEER 06/16/2023
TIN NO: LOCATION:
628-317-936-00000 BLK 1 LOT 59, PHIRST PARK HOMES TANZA
6.75

2.50 4.25 2.50 4.25 4.00 2.75

1.50 2.75 1.50 2.75 FIREWALL

GI GUTTER GI GUTTER GI GUTTER GI GUTTER

WALK-IN 2.15
2.25 2.25
CLOSET

4.00 4.00

1.75 1.75 1.85


FIREWALL

EXISTING EXISTING EXISTING


STRUCTURE STRUCTURE STRUCTURE

10.90 2.80 10.90 2.80

SLAB ON SLAB ON
4.10 GROUND 4.10 GROUND

A5 GROUND FLOOR PLAN A6 SECOND FLOOR PLAN A7 ROOFING PLAN

4.00 2.75 4.10 2.30 0.40 4.10 2.75 4.00

FIREWALL FIREWALL
FIREWALL
FIREWALL

0.20 0.20

3.88 3.88
3.28
EXISTING
EXISTING STRUCTURE
6.58 STRUCTURE 6.58

EXISTING
2.70 2.70 2.70
STRUCTURE

A8 FRONT ELEVATION A9 RIGHT ELEVATION A10 REAR ELEVATION

PRC NO:
SEAL: ENGINEER: 0194991 PROJECT TITLE: OWNER: SHEET NO:
VALIDITY:
07/13/2026
PTR NO: CALLSITA-END HOUSE EXTENSION
12578064J
ENGR. AUDWIN GAREY G. FESTIN DATE: Amanda Somera Ordonez AR - 02
LICENSED CIVIL ENGINEER 06/16/2023
TIN NO: LOCATION:
628-317-936-00000 BLK 1 LOT 59, PHIRST PARK HOMES TANZA
2.50 4.25 2.50 4.25

1.50 2.75 1.50 2.75

12mm THK
12mm THK MOISTURE MOISTURE 9mm GYPSUM
2.25 RESISTANT GYPSUM 2.25 RESISTANT BOARD
BOARD GYPSUM BOARD

4.00 4.00 4.00 2.75

FIREWALL

1.75 1.75

EXISTING EXISTING
STRUCTURE STRUCTURE
3.88
10.90 2.80 10.90 2.80

6.58

EXISTING
SLAB ON SLAB ON 2.70 STRUCTURE
4.10 GROUND 4.10 GROUND

A13 LONGITUDINAL SECTION

A11 GROUND FLOOR REFLECTED CEILING PLAN A12 SECOND FLOOR REFLECTED CEILING PLAN

1.20
1.20
MARK # OF UNITS DESCRIPTION
1.00 0.70 0.80

0,50 W2 0.50 W4
D1 1 Metal Door

1.25 W1
D1 D2
D2 2 Laminated
2.10 2.10 Wooden Door
.7
1.00
W3

0.30 W2 W1 1 Aluminum Sliding window with Sliding


Screen

W2 2 Aluminum Awning Window

W3 2 Aluminum Sliding Window with Sliding


Screen

W4 1 Aluminum Sliding Window With Sliding


Screen

PRC NO:
SEAL: ENGINEER: 0194991 PROJECT TITLE: OWNER: SHEET NO:
VALIDITY:
07/13/2026
PTR NO: CALLSITA-END HOUSE EXTENSION
12578064J
ENGR. AUDWIN GAREY G. FESTIN DATE: Amanda Somera Ordonez AR - 03
LICENSED CIVIL ENGINEER 06/16/2023
TIN NO: LOCATION:
628-317-936-00000 BLK 1 LOT 59, PHIRST PARK HOMES TANZA
GENERAL
1. CONSTRUCTION NOTES AND TYPICAL DETAILS APPLY TO ALL DRAWINGS UNLESS OTHERWISE 2.50 4.25 2.50 4.25
SHOWN OR NOTED. MODIFY TYPICAL DETAILS AS DIRECTED TO MEET SPECIAL CONDITIONS.
1.50 2.75 1.50 2.75
2. SHOP DRAWINGS WITH ERECTION AND PLACING DIAGRAMS OF ALL STRUCTURAL FOR
ENGINEER'S APPROVAL BEFORE FABRICATION. FTB 1 B2 B1
C2 C1
3. CONTRACTOR SHALL VERIFY ALL DIMENSIONS BEFORE ALL WORK IS TO BEGIN, CHECK WITH C2 F3
C1 F2

MECHANICAL AND ELECTRICAL CONTRACTORS FOR CONDUITS, PIPE SLEEVES, ETC. TO BE


EMBEDDED IN CONCRETE.

FTB 1

FTB 1
SLAB ON GRADE SLAB ON GRADE
2.25 2.25

B2

B1
4. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO PROVIDE ADEQUATE SHORINGS AND
BRACINGS OF THE STRUCTURE FOR ALL LOADS THAT MAYBE IMPOSED DURING CONSTRUCTION.
C2 F3 C2
5. IN CASE OF QUESTION ARISING FROM THE INTERPRETATION OF OR CONFLICT WITH OTHER 4.00 FTB 1 4.00 B2 B1
C1 F1 C1
DOCUMENTS, THE ATTENTION OF THE OWNER/ENGINEER SHALL BE CALLED IN WRITING.
CONCRETE & REINFORCEMENT

FTB 1
FTB 1
SLAB ON GRADE

B1
1. ALL MATERIALS AND WORKMANSHIP SHALL CONFORM WITH THE LATEST BUILDINGS

B1
1.75 1.75
CODE OF AMERICAN CONCRETE INSTITUTE (ACI-318).
2. ALL CONCRETE SHALL DEVELOP A MINIMUM COMPRESSIVE STRENGTH AT THE END OF TWENTY
EIGHT (28) DAYS WITH CORRESPONDING MAXIMUM SIZE AGGREGATE AND SLUMPS AS FOLLOWS: EXISTING C1 F1
FTB 1

C1 F1
EXISTING C1
B1
C1

MAX. SIZE OF STRUCTURE STRUCTURE


LOCATION STRENGTH AGGREGATES MAX. SLUMP

a. SLAB ON GRADE, 3000 PSi (20.685 Mpa) 1 in. (25mm) 4 in. (100mm)
CURBS, PAVEMENTS, 10.90 2.80 10.90 2.80
FOOTING,
WALL FOOTING
b. BEAMS, COLUMNS 3000 PSi (20.685 Mpa) 3/4 in. (19mm) 4 in. (100mm)
SUSPENDED SLAB
d. LEAN CONCRETE 2500 PSi (17.24 Mpa) 1 in. (25mm) 4 in. (100mm)
3. ALL REINFORCING BARS SHALL CONFORM TO PNS49 GRADE 275
FOR 12mm Ø AND SMALLER BARS AND GRADE 415 FOR 16mm Ø AND LARGER BARS.
4. IN GENERAL, THE LATEST EDITION OF ACI-315, MANUAL OF STANDARD PRACTICE DETAILING
REINFORCED CONCRETE STRUCTURES SHALL BE ADHERED TO UNLESS OTHERWISE SHOWN SLAB ON SLAB ON
OR NOTED.
5. MAINTAIN MINIMUM CONCRETE COVER FOR REINFORCING STEEL AS FOLLOWS:
4.10 GROUND 4.10 GROUND
CONCRETE DEPOSITED DIRECTLY AGAINST GROUND 75 mm
SUSPENDED SLABS 20 mm
SLAB ON GRADE 40 mm
WALLS ABOVE GRADE 25 mm
BEAMS & COLUMNS 40 mm
6. SPLICES SHALL BE SECURELY WIRED TOGETHER AND SHALL LAP OR EXTEND IN ACCORDANCE
WITH TABLE 1 (TABLE OF LAP SPLICE AND ANCHORAGE LENGHT) UNLESS OTHERWISE SHOWN ON
DRAWINGS, SPLICES SHALL BE STAGGERED WHENEVER POSSIBLE.
7. ALL ANCHOR BOLTS, DOWELS, AND OTHER INSERTS SHALL BE PROPERLY POSITIONED AND
SECURED IN PLACE PRIOR TO PLACING OF CONCRETE.
8. CONTRACTOR SHALL NOTE AND PROVIDE ALL MISCELLANEOUS CURBS, SILLS, STOOLS, EQUIPMENTS,
AND MECHANICAL BASES THAT ARE REQUIRED BY THE ARCHITECTURAL, ELECTRICAL, AND
MECHANICAL DRAWINGS.
9. ALL CONCRETE SHALL BE KEPT MOIST FOR A MINIMUM OF SEVEN (7) CONSECUTIVE DAYS IMMEDIATELY
AFTER POURING BY THE USE OF WET BURLAP, FOG SPRAYING, CURING COMPOUNDS OR OTHER
APPROVED METHODS.
S1 FOUNDATION PLAN S2 2ND FLOOR FRAMING PLAN
10. STRIPPING OF FORMS AND SHORES:
CONCRETE CURING
FOUNDATION 24 HRS.
SUSPENDED SLAB EXCEPT WHEN 8 DAYS
ADDITIONAL LOADS ARE IMPOSED
PEDESTALS, COLUMNS, WALLS 2 DAYS
BEAMS 21 DAYS
3.18 1.70 2.75
11. DEVELOPMENT LENGTH FOR ALL BARS SHALL BE A MINIMUM OF 60 BAR DIAMETER, UNLESS OTHERWISE NOTED.
RB2 RB2 RB1
C1
STRUCTURAL STEEL AND PLATES C1 C2 C1

1. ALL STRUCTURAL STEEL SHALL CONFORM TO ASTM (A-36) SPECIFICATIONS WITH MINIMUM YIELD STRENGTH, fy=250 MPa
2. ANCHOR & FASTENER BOLTS, ALL BOLTS SHALL CONFORM TO ASTM (A-307) SPECIFICATIONS.
2.25

RB1

RB1

RB1

RB1
3. WELDING RODS, ALL WELDING RODS SHALL BE MILD STEEL ELECTRODE, LOW HYDROGEN E7018 WITH
MINIMUM YIELD STRENGTH = 420MPa 4.00
C1 C1 C2
4.00 RB2 RB2 RB1
C1
FOUNDATION
2.25 1.75
1. FOUNDATION IS DESIGNED BASED ON NATIONAL BUILDING CODE OF THE PHILIPPINES FOR AN ALLOWABLE

RB1
SOIL BEARING CAPACITY OF 240 KPa.

RB1
1.75
2. FOUNDATION SHALL REST ON NATURAL SOIL, UNLESS OTHERWISE NOTED BY
THE ENGINEER, NO PART OF THE FOUNDATION SHALL REST ON FILL.

3. THE CONTRACTOR SHALL NOTIFY THE ENGINEER UPON COMPLETION OF FOUNDATION EXCAVATION FOR ACTUAL SOIL EXISTING C1
RB1
C1

CONDITIONS WHICH DO NOT CONFORM TO THE SOIL BEARING CAPACITY FOR PROPER REVISION. STRUCTURE
MASONRY WALLS
RIB TYPE
1. ALL MATERIALS & WORKMANSHIP SHALL BE IN ACCORDANCE W/ THE APPLICABLE STANDARD
& SPECIFICATIONS OF THE STRUCTURAL CODE OF THE PHILIPPINES & UNIFORM BUILDING CODE. 10.90 2.80 1.5mm C-PURLIN 2x4
2. MORTAR & GROUT FOR ALL CONCRETE MASONRY SHALL CONFORM TO ASTM 270 - TYPE N &
SHALL HAVE A MINIMUM OF 28 DAYS STANDARD CYLINDER COMPRESSIVE STRENGTH OF 17.5 MPa (2500 PSi).
3. ALL CHB SHALL BE LAID OUT WITH THE CELLS IN UNOBSTRUCTED VERTICAL CONTINUITY. 2 BACK-TO-BACK 5mm
ALL CELLS ESPECIALLY THOSE WITH REINFORCEMENT SHALL BE FILLED WITH MORTAR.
C-CHANNEL 2x6
4. REINFORCEMENT, AS TABULATED BELOW SHALL BE PROVIDED UNLESS OTHERWISE SPECIFIED IN THE PLAN.
BOLTED EVERY 500mm
5. ALL MASONRY WALLS SHALL BE PROVIDED W/ STIFFENER BEAM BLOCK & STIFFENER AS REQUIRED.
0.40
5.a. FOR HIGH WALLS & EVERY 3000 mm & COLUMN (BOLT) AT 3000 mm ON CENTER.
5.b. FOR DOORS & WINDOWS OPENING PROVIDE LINTEL BEAM SAME AS STIFFENER BEAM BLOCK. SLAB ON 0.20
4.10 GROUND

BLOCK
CHB REINFORCEMENTS
REINFORCEMENT
NOTES
RB1
THICKNESS (mm) HORIZONTAL VERTICAL
10mm Ø BARS @ EVERY 10mm Ø @ 600 mm O.C. A. MIN. LAP SPLICE = 300mm LONG
100 3RD LAYER OF CHB
10mm Ø BARS @ EVERY B. PROVIDE RIGHT ANGLE
125 10mm Ø @ 600 mm O.C.
3RD LAYER OF CHB REINFORCEMENT @ CORNERS

250
CONCRETE HOLLOW 4 - 12 mm Ø
BLOCKS
250

STIFFENER COLUMN
10 mm Ø TIES
@ 200 mm O.C. STIFFENER BEAM BLOCK S3 ROOF FRAMING PLAN S4 ROOF TRUSS PLAN

PRC NO:
SEAL: ENGINEER: 0194991 PROJECT TITLE: OWNER: SHEET NO:
VALIDITY:
07/13/2026
PTR NO: CALLSITA-END HOUSE EXTENSION
12578064J
ENGR. AUDWIN GAREY G. FESTIN DATE: Amanda Somera Ordonez ST - 01
LICENSED CIVIL ENGINEER 06/16/2023
TIN NO: LOCATION:
628-317-936-00000 BLK 1 LOT 59, PHIRST PARK HOMES TANZA
COLUMN SCHEDULE
LEVEL COLUMN MARK

300
SCHEDULE OF SLAB
SIZE
FOUNDATION LEVEL C1 200mm x 300mm REINFORCEMENT SHORT LONG
TO ROOF BEAM LEVEL MAIN BARS
8 - 16mm Ø SLAB THICKNESS DIAMETER SPAN SPAN LONG
SPAN
LATERAL TIES 200 MARK (mm) MAIN TEMP. TOP BARS BOT BARS TOP BARS BOT BARS
10mm Ø
3 @ 50mm BARS BARS
5 @ 100mm
REST 150mm TO CENTER
S-1 150 10 10 300 300 300 300 300 300 300 300 TWO WAY SLAB

200
SIZE S/4 TOP BARS S/4
FOUNDATION LEVEL C3 200mm x 200mm
TO ROOF BEAM LEVEL MAIN BARS

t
4 - 16mm Ø BEAM BEAM

200 TEMP. BARS


LATERAL TIES
S/5 BOTTOM BARS S/5
10mm Ø
1 @ 50mm S
3 @ 100mm TYPICAL DETAIL OF ONE-WAY SLABS
REST 150mm TO CENTER

S/4 MAIN TOP BARS S/4

t
BEAM
BEAM
MAIN BOT. BARS

S/5 S/5
S

TYPICAL DETAIL OF TWO-WAY SLABS

DEPTH

SCHEDULE OF BEAMS
THICKNESS BEAM STIRRUPS
DIMENSIONS STEEL REINFORCEMENTS
FLOOR BEAM 10mm
(mm) REBAR (UNLESS NOTED
LEVEL MARK LEFT MIDSPAN RIGHT
b h (mm) TOP BOT TOP BOT TOP BOT OTHERWISE)
3@50, 5@100, REST@150
GROUND FTB-1 300 300 16mm 2 2 2 2 2 2
SECOND B-1 250 300 16mm 3 2 2 3 3 2 3@50, 6@100, REST@150
FLOOR B-2 250 350 16mm 3 2 2 3 3 2
LENGTH LENGTH
3@50, 6@100, REST@200
ROOF RB-1 200 250 12mm 2 2 2 2 2 2

WIDTH WIDTH L1/4 L1/3 L2/3 SPLICE=40d L2/4

STANDARD
90° HOOK
TYPICAL SQUARE FOOTING DETAIL TYPICAL EDGE FOOTING DETAIL

.150 L1/5 L1/4 L2/4 L2/5

SCHEDULE OF FOOTING
L1 (CLEAR SPAN) L2 (CLEAR SPAN)

REINFORCEMENTS FOOTING DIMENSIONS


FOOTING MARK REMARKS
BAR-X BAR-Y LENGTH WIDTH DEPTH THICKNESS S4 TYPICAL BEAM DETAIL

F1 10-16mmØ 10-16mmØ 800 800 1000 300 EDGE FOOTING

F2 8-16mmØ 8-16mmØ 800 800 1000 300 CORNER FOOTING

F3 10-16mmØ 14-16mmØ 800 1200 1000 300 EDGE FOOTING

PRC NO:
SEAL: ENGINEER: 0194991 PROJECT TITLE: OWNER: SHEET NO:
VALIDITY:
07/13/2026
PTR NO: CALLSITA-END HOUSE EXTENSION
12578064J
ENGR. AUDWIN GAREY G. FESTIN DATE: Amanda Somera Ordonez ST - 01
LICENSED CIVIL ENGINEER 06/16/2023
TIN NO: LOCATION:
628-317-936-00000 BLK 1 LOT 59, PHIRST PARK HOMES TANZA
2.50 4.25 2.50 4.25

1.50 2.75 1.50 2.75

WEATHER PROOF DUPLEX OUTLET WEATHER PROOF DUPLEX OUTLET


W W

2.25 SPLIT TYPE AIRCON OUTLET 2.25 S2 SPLIT TYPE AIRCON OUTLET

WALL MOUNTED LIGHT WALL MOUNTED LIGHT

4.00 S2 4.00
DUPLEX OUTLET S2 DUPLEX OUTLET

1.75 CEILING MOUNTED LIGHT 1.75 CEILING MOUNTED LIGHT

S2 EMERGENCY LIGHT EMERGENCY LIGHT

EXISTING EXISTING
S2 2-GANG SWITCH S2 2-GANG SWITCH
STRUCTURE STRUCTURE
WIRING CONCEALED IN WALL OR CEILING WIRING CONCEALED IN WALL OR CEILING

10.90 2.80 10.90 2.80

SLAB ON SLAB ON
4.10 GROUND 4.10 GROUND

E1 GROUND FLOOR ELECTRICAL LAYOUT PLAN E2 SECOND FLOOR ELECTRICAL LAYOUT PLAN

2.50 4.25 2.50 4.25

1.50 2.75 1.50 2.75

2.25 2.25

4.00 4.00

1.75 1.75

EXISTING EXISTING
STRUCTURE STRUCTURE

10.90 2.80 10.90 2.80

SLAB ON SLAB ON
4.10 GROUND 4.10 GROUND

E1 GROUND FLOOR ELECTRICAL LAYOUT PLAN E2 SECOND FLOOR ELECTRICAL LAYOUT PLAN

PRC NO:
SEAL: ENGINEER: 0194991 PROJECT TITLE: OWNER: SHEET NO:
VALIDITY:
07/13/2026
PTR NO: CALLSITA-END HOUSE EXTENSION
12578064J
ENGR. AUDWIN GAREY G. FESTIN DATE: Amanda Somera Ordonez PL/EL - 01
LICENSED CIVIL ENGINEER 06/16/2023
TIN NO: LOCATION:
628-317-936-00000 BLK 1 LOT 59, PHIRST PARK HOMES TANZA