You are on page 1of 1

BASEMENT OF UNITED TOWER SYSTEM MATRIX

ACTUATE AUDIBLE ALARM SIGNAL & STROBE( NEAR RESPECTIVE & MASTER PANEL)
CONTROL UNIT REMOTE FIRE SAFETY

ACTUATE COMMON ALARM SIGNAL INDICATOR(RESPECTIVE & MASTER PANEL)


ANNUNCIATION CONTROL

TRANSMIT SUPERVISORY SIGNAL TO THE SUPERVISING STATION


ACTUATE AUDIBLE SIGNAL (NEAR UNDER GROUND RESERVER)
ACTUATE AUDIBLE SIGNAL (In & out of Central Equipment RM)

ACTUATE AC SHUTDOWN (AUTOMATICALY,IF AVALABLE)


EFFECT

TRANSMIT TROUBLE SIGNAL TO SUPERVISING STATION


ACTUATE AUDIBLE SIGNAL (In & out of Master Control RM)
ACTUATE AUDIBLE SIGNAL (INSIDE OF BANK-01 ROOM)
ACTUATE AUDIBLE MESSAGE (INSIDE EFECTED ARIA)

ACTUATE AUDIBLE SIGNAL (In & out of Studio)

ACTUATE AC SHUTDOWN (Master Control RM)


Release Gas (FM200) in Master Control RM
OPENED THE BANK ROOM MAIN DOOR

ACTUATE AC SHUTDOWN (Archive RM)


MAIN DOOR OPEN(AUTOMATICALY)

Release Gas (FM200) in Archive RM


RELEASE SPRINKLER SYSTEM
CAUSE

ACTUATE ARROW PATH


ACTUATE EXIT SIGN
ALARM INITIATING DEVICES BAESMENT(ANY ONE EXCEPT MCP) X X
ALARM INITIATING DEVICES BAESMENT(ANY 2/3 AND GROUP) X X X X X X X X
ACTUATE MANUAL CALL POINT IN BAESEMENT(BREAK GLASS) X X X X X X X
ALARM INITIATING DEVICES UNDER GROUND RESERVER X X X X
ALARM INITIATING DEVICES GROUND FLOOR(Any one) X X X X
ALARM INITIATING DEVICES GROUND FLOOR (ANY 2/3 AND GROUP) X X X X X
ALARM INITIATING DEVICES 7TH FLR (Central Equipment Rm, Cross Zone) X X X X X X X X X
ALARM INITIATING DEVICES 7TH FLR (Studio, Cross Zone) X X X X X X X X X
ALARM INITIATING DEVICES 7TH FLR (News Studio, Cross Zone) X X X X X X X X X
ALARM INITIATING DEVICES 7TH FLR (Master Control RM, Cross Zone) X X X X X X X X X
ALARM INITIATING DEVICES 8TH FLOOR(Any one) X X
ALARM INITIATING DEVICES 8TH FLOOR (General Alarm, Any Two) X X X
ALARM INITIATING DEVICES 8TH FLR (Archive RM, Cross Zone) X X X X X X
ALARM INITIATING DEVICES 9TH FLOOR(Any one) X X
ALARM INITIATING DEVICES 9TH FLOOR (General Alarm, Any Two) X X X