FREQUENCY TRANSDUCER MCFB4x

• Power Frequency Transducer

• Precision true RMS class 0,5 measurement, not affected by


any waveform distortion

• Up to two individual very fast analogue output signals


(<50mS), (optional)

• DIN96 Slave Indicator with frequency scale (optional)

Specifications Description
Monitored Voltage: 100-120V, 200-240V, The digitally controlled MCFB4x is for use in applications that require a very fast response,
380-415V, 440-460V, precision monitoring of the frequency. Ideal for systems for regulation and control of the
480VAC, 40-70Hz frequency on generators, motors and inverters.
(Fuse 0,5A)

Optional Separate 100-120V, 200-240V,


The MCFB4x is a precision frequency measuring transducer for AC voltage input.
Auxiliary Voltage AC: 380-415V, 440-460V,
480VAC, 40-70Hz The unit measures the voltage and current true r.m.s. value, and accuracy is independent of any wave
(Fuse 0,5A) form distortion. A green LED (ON) indicates the auxiliary supply presence.

Optional Separate 24-60VDC (Fuse 0,5A) LED status


Auxiliary Voltage DC: 110-220VDC (Fuse 1A) Power

Supply tolerance: +10%, -20% ON


Power rating: 5VA
Frequency range: 45-55Hz
(Other range on request) 55-65Hz
Up to two individual very fast analogue output signals (optional) proportional to the measured frequency
45-65Hz level (see page 2 for available outputs). The analogue output is isolated from both voltage input and
30-70Hz auxiliary power.
Analogue output 1: mA: Up to 20mA, max 500R
(see page 2 for V: Up to 10V, min 100kohm The standard model have one output signal, but optional model have two output signals.
available outputs) (other on request)
If an output is used for remote meter reading, we recommend 0-1mA for the slave indicator.
Analogue output 2: mA: Up to 20mA, max 500R
(see page 2 for V: Up to 10V, min 500ohm
available outputs) (other on request) It also includes an additional RJ12 output for a DIN96 Slave Indicator (optional).
Accuracy: Class 0,5
Temperature: -20 to +70ºC The noise-immune mA output is isolated from both voltage input and auxiliary power.
Humidity, relative: 0-95%
Weight: 0.6kgs The standard models takes the auxiliary supply voltage from the monitored voltage (terminal 1 & 2).
Front protection: IP21
Flammability: UL94-V0
It can also be delivered with optional separate AC or DC auxiliary voltage (terminal 26 & 27), but that must
be specified when ordering (see page 2 for ordering code for separate Aux. Supply).

Models O/P 1 O/P 2 Standard model Optional model


MCFB4A X - X -
MCFB4B X X - X
The unit meets EN 60255-27 Cat. III, Pollution degree 2 and the
relevant environmental and EMC tests specified in EN 60255-26
to comply with the requirements of the major Classification
Societies.

Related information:
The MCFB4x series are also available for panel mounting as
MPFE series.

Norway
Denmark
United Kingdom Page: 1 of 2
REF: Datasheet.MCFB4x - REV: 2.02/07.2022
www.megacon.com © All rights reserved to Megacon
ELECTRONIC CONTROL AND INSTRUMENTATION Megacon reserves the right to make any changes to the information at any time
FREQUENCY TRANSDUCER MCFB4x
Connection Diagram Analogue Output
Connection Diagram without optional slave instrument The output signals are proportional to the meter reading (see page
L1 1 for an overview of models and functions).
L2

L3
The signal is specifically intended as an input to a control system
for monitoring or control.
N ~
+ ~
-
Separate
Monitored AC or DC Add suffix from table below to type designation to specify output
Voltage
(*Note)
Aux.Supply
(Optional)
required:
1 2 3 4 26 27 5 6 7 8 9 10
Outputs 1 Outputs 2
O/P1 0 - 10mA O/P11 0 - 10mA
MCFB4x O/P2 0 - 20mA O/P12 0 - 20mA
O/P3 4 - 20mA O/P13 4 - 20mA
O/P4 N/A O/P14 N/A
12 13 14 15 28 29 16 17 18 19 20 21 22 23 24 O/P5 N/A O/P15 N/A
O/P6 N/A O/P16 N/A
O/P7 N/A O/P17 N/A
+ -
Analogue
+ -
Analogue
O/P8 0 - 10V O/P18 0 - 10V
output 1 output 2 O/P9 0,2 - 10V O/P19 0,2 - 10V
(standard) (optional) O/P10 4,3 - 20mA O/P20 4,3 - 20mA
Connection Diagram with optional slave instrument
L1 Connection
L2
Terminal type : Terminal Clamp and Screw
Wire max. : T1-T4,
L3
T26-T27: AWG 24-14,
N ~
+ ~
- T5-T10: AWG 12,
Separate
Monitored AC or DC
other terminals: AWG 24-12
Voltage Aux.Supply Screw Torque : 0.5Nm
(*Note) (Optional)
1 2 3 4 26 27 5 6 7 8 9 10
Overload
Voltage : 1.2 x Un continuous
2 x Un for 10secs
MCFB4x
RJ12 plug cable

Current : 2.5 x In continuous


12 13 14 15 28 29 16 17 18 19 20 21 22 23 24
5 x In for 1secs (max 25A)

Com. cable to
+ - + - slave indicator
Analogue Analogue Hz 65
output 1 output 2 55
(standard) (optional)
Optional DIN96 POW ER

MEA SURING

slave indicator
T RA NSDU CER

45

MFI96E

*Note: The standard models takes the auxiliary supply voltage from the monitored voltage (terminal 1 & 2).

Dimensions
75mm
Mounting : 35mm Rail Mount EN 60715
Dimensions : 100mm x 75mm x 110mm
100mm
85mm Slave Indicator
A B C Panel cut-out
DIN96 96 x 96mm 92 x 92mm 64mm Maximum panel
thickness 10mm

ORDERING INFORMATION (Example)


The MEGACON policy is one of continuous improvement, consequently Type : MCFB4B Optional Separate Aux. Supply:
equipment supplied may vary in detail from this publication. Add -SA for models with
Aux. Supply : 200-240VAC Separate AC Aux. Supply.
Input Voltage : 110V (Example: MCFB4B-SA)
Range : 45-65Hz Add -SD for models with
Analogue output 1 : O/P3: 4-20mA Separate DC Aux. Supply.
Analogue output 2 : O/P18: 0-10VDC (Example: MCFB4B-SD)

Norway
Denmark
United Kingdom Page: 2 of 2

www.megacon.com Innovation Beyond Tradition


ELECTRONIC CONTROL AND INSTRUMENTATION Uniquely MEGACON, simpler it can't be!