H1Z2Z2-K

08
standards: EN 50618

Single core flexible cable, suited for photovoltaic and solar systems, up to 1,8kV
HALOGEN-FREE CABLES AND CONDUCTORS

Technical data Construction


Temperature range: 1. Conductor: tinned fine wired copper conductor, class 5,
acc. to EN 60228
• fixed installed: -40°C up to +90 °C
2. Insulation: special LSOH compound
• min. cable temperature at bending/installation: -40 °C
3. Sheath: crossed linked special LSOH compound
• maximal operating temperature: 120 °C
• sheath colour: black, red or blue
• at short circuit of max. 5 s: up to 250 °C
Nominal voltage AC: U0 /U = 1,0/1,0kV
Core colour identification: natural colour – bright
Nominal voltage DC: U0 /U = 1,5/1,5kV
Max. voltage: Um = 1,8kV
Additional features:
Test voltage: 6,5kV
Ozone-resistant according to EN50396
Maximal tensile strength of Cu conductor:
UV-resistant according to HD605/A1
• during operation: 15 N/mm2
The cable is tested for durability according to EN 60216
• during installation: 50 N/m2
(indicated also in 2P fg 169/08.2007)
Minimal inner bending radius: 4D
Standard interpretation under continuous use temperature
(D = external cable diameter)
120°C for 20000h (= 2.3, years) continuous use temperature
Properties under fire: 90°C (= 30 years )
Flame retardant: acc. to IEC 60332-1 / EN 60332-1 (earlier
EN 50265-2-1) / VDE 0482-332-1
No flame propagation in vertical cable bundle: acc. to
IEC 60332-3 / EN 50266-1,-2 / DIN VDE 0482-266-2-4 (same
as DIN VDE 0472 part 804 test method C)
Halogen-free: acc. to IEC 60754-1 / EN 50267 -1,-2-1 / DIN
VDE 0482-267 -1,-2-1 (same as DIN VDE 0472 part 815)
Non-corrosive combustion gases: acc. to IEC 60754-2
/ EN 50267-2-2 / DIN VDE 0482-267-2-2 (same as DIN VDE
0472 part 813)
Low smoke density: acc. to IEC 61034-2 / EN 61034-2
(earlier EN 50268) / DIN VDE 0482-1034-2 (same as DIN VDE
0472 part 816) - visibility > 70%

CPR
Construction Products Regulation: Cable for general
use in construction in accordance with fire protection
regulations.
Harmonized standards: EN 50575:2014 i EN 50575:2014/
A1:2016
Reaction to fire: Eca
Dangerous substances: N.P.D.

140
08
Application
Single core flexible cables suited for photovoltaic and solar system with cross-linked polymer insulation and halogen free sheath.
Tested for more 25 years lifetime. These cables can be used up 1800V to earth. Cable suitable for the interconnection of the various
elements of photovoltaic systems, suitable for fixed installations outside and indoor, unprotected pipes. For direct, or indirect under-
ground wiring.

Dimensions -number of Conductor Insulation External diameter Conductor Current load Current load at Cable weight Packing*
cores x conductor cross- diameter thickness resistance at capacities at 20oC 60oC (in ground)
section 20oC
nominal approx. nominal max. max. nominal nominal approx.
N x mm2 mm mm mm Ω/km A A kg/km
1x4 2,5 0,7 6,6 5,0900 55 41 58,2 CUT
1x6 3,0 0,7 7,4 3,3900 70 52 79,4 CUT
1 x 10 3,9 0,7 8,8 1,9500 98 70 128,4 CUT

HALOGEN-FREE CABLES AND CONDUCTORS


1 x 16 5,0 0,7 10,1 1,2400 132 91 184,5 CUT
1 x 25 6,4 0,9 12,5 0,7950 176 118 276,8 CUT
1 x 35 7,7 0,9 14,0 0,5650 218 144 368,8 CUT
1 x 50 9,2 1,0 16,3 0,3930 276 178 557,0 CUT
1 x 70 11,0 1,1 18,7 0,2770 347 218 767,0 CUT
1 x 95 12,5 1,1 20,8 0,2100 416 258 989,6 CUT
1 x 120 14,2 1,2 22,8 0,1640 488 298 1232,8 CUT
1 x 150 15,8 1,4 25,5 0,1320 566 386 1540,0 CUT
1 x 185 17,5 1,6 28,5 0,1080 644 515 1833,0 CUT
1 x 240 20,1 1,7 32,1 0,0817 775 620 2450,0 CUT

*) Packing: CUT = cable in different lengths on drum or reel, possible cutting at required length

141