You are on page 1of 1

Circuit-Breakers for Motor Protection

Series 8523/8

Trip Response
Adjustment Trip time of motor protection switch at
range of motor
protection switch
3 4 5 6 7.2 8
times the setting current, 3-pin, from cold state.
A to A s s s s s s
0.1 to 0.16 15.0 9.0 6.5 4.8 3.7 3.2
0.16 to 0.25 16.0 10.0 6.8 5.2 4.0 3.6
0.25 to 0.4 16.0 9.7 6.5 5.0 3.8 3.3
0.4 to 0.63 17.0 10.2 7.3 5.7 4.4 3.9
0.63 to 1.0 17.5 10.2 7.2 5.5 4.2 3.8
1.0 to 1.6 17.0 10.0 7.1 5.6 4.4 4.0
1.6 to 2.5 18.0 10.3 7.5 5.9 4.7 4.2
2.5 to 4.0 18.4 11.5 8.1 6.4 5.0 4.6
4.0 to 6.3 19.0 12.0 8.5 6.7 5.3 4.9
6.3 to 9.0 18.2 11.5 7.9 6.0 4.5 3.8
9.0 to 12.5 19.0 11.5 8.0 6.0 4.6 4.0
12.5 to 16.0 19.5 11.5 7.5 5.4 4.0 3.3
16.0 to 20.0 20.0 11.5 7.8 5.7 4.2 3.5
20.0 to 22.5 20.0 10.4 7.0 5.0 3.7 3.2

11050E00 11051E00

1) Multiples of the nominal current


2) Tripping time
3) 2-pole
4) 3-pole
5) Electromagnetic release

E9/6 Components for System Solutions 2018-09-19·EK00·III·en