You are on page 1of 4

7/186 Industrial Power Engineering and Applications Handbook

inst. - instantaneous
7 Ud
1
(Off-delay) On
+
inst.
1
C

Off
trip
3
inst.

4
Figure 7.19 A typical scheme illustrating re-acceleration of a critical motor

7.19 Motors for thermal power authorities may sometimes stipulate norms and outline
their basic minimum requirements for the benefit of users
station auxiliaries and the manufacturers. In India, for instance, the Central
Electricity Authority (CEA) publishes manuals based on
These applications have considerably more stringent the actual feedback obtained from various thermal sites,
performance requirements than any other application. electricity companies, leading consultants and the NTPC
Circulating water pumps, boiler feed pumps, forced- (National Thermal Power Corporation), in addition to
draught (FD) and induced-draught (ID) fans, pulverizers motor manufacturers. Below are extracts from these
(ball mills) and condensate pumps are components in a manuals :
thermal power station that may require extra safety in a
standard motor to make it able to fulfil these requirements I Motors must be generally squirrel cage type and not
and withstand abnormal service conditions and system slip-ring.
disturbances. Abnormal operating conditions may be one 2 The preferred ratings for motors above 1104000 kW,
or more of the following: must follow the ‘Renard Series’, R-20, according to
I S 0 3, as shown in Table l.l(a).
High ambient temperature 3 The preferred synchronous speeds is as shown in Table
High humidity 7.7.
Dust-laden (coal dust and fly ash) environment 4 The enclosure and type of cooling is as shown in
Long continuous operation Table 7.8.
High fault levels 5 Space heaters: motors above 30 kW must be provided
Overvoltages, caused by a fast bus transfer with anti-condensation space heaters suitable for
Re-acceleration in some drives 240 V 50 Hz (or 60 Hz), a.c. supply. The space heaters
Voltage surges, caused by system disturbances or must switch ON automatically when the motor is out
switching operations (for HT motors). of service. Motors of 30 kW and below must be suitable
for connection to a 240 V, 50 Hz (or 60 Hz) a.c.
supply. Here also the windings must be connected
In a large power station, connected to a transmission automatically to the 240 V supply when the motor is
network through a power grid, system disturbances are a out of service.
common feature. For details see Section 17.5. 6 Terminals and terminal box
With a view to standardizing the basic requirements HT motors must be provided with phase-segregated
of an electric motor for essential services, electricity terminal boxes as illustrated in Figure 7.17.
Special-purpose motors 7/187

-
Y
F4
1 1
NL

‘6
1st motor (Off-delay) On
+
Off O/C
trip
inst.
I

1 1
);id,
2nd motor h2 13
I I
(On-delay) (Off-delay) On Off O/C
+ trip
inst.

inst. - instantaneous

Figure 7.20 A typical scheme illustrating re-acceleration of two motors (or two groups of motors) with a time gap

Table 7.7 Preferred speeds for thermal power station auxiliaries Table 7.8 Recommended enclosures and type of cooling for
power station auxiliaries
Auxiliury Synchronous
speed (rp.rn.) Enclosure Type of cooling
us in
Induced-draught fan (ID fan) 750, 1000 IEC 60034-6
Forced-draught fan (FD fan) 1000, 1500
Primary air fan (PA fan) 1500 1 TEFC IC 0141
Ball mill (coal crusher) 1000
2 TETV IC 0151
Vapour fan 1000, 1500
Boiler feed pump (BFP) 1500, 3000 3 CACA IC 0161
Condensate pump 1000, 1500 4 CACW ICW 37A 81 01
Circulating water pump (CW pump) 375,429,500 ICW 37A 9 1
7/188 Industrial Power Engineering and Applications Handbook

In HT motors the terminal box for space heaters impedance, because of the saturation effect, than at a reduced
and embedded temperature detectors must be voltage. The Zst at full voltage therefore would be slightly
separate from the main terminal box. higher than that calculated from the starting current, measured
at a reduced voltage. Hence the allowance for this. See also
The terminal box must be capable of withstanding Figure 27.2(b).
the system fault current for at least 0.25 second.
The terminal box must be suitable for being turned
through 180”, for bottom or top cable entry. 10 Frequency of start: The HT motors must be suitable
The terminal box must have the same degree of for two starts in quick succession when the motor is
protection as the motor. hot or three equally spread starts in an hour (not to be
For large motors, 1000 kW and above, if they are repeated in the second successive hour).
provided with star windings the three neutral end 11 Stresses during a fast bus transfer: A fast bus transfer
leads must be connected to a separate terminal box between the unit and station supplies is an essential
to enable mounting of CTs for differential protection. feature in a power station to maintain an uninterrupted
The neutral terminal box need not be phase power supply to the unit and station auxiliary services
segregated. (Figure 13.21). The changeover may be as fast as
7 Performance three or four cycles which is adequate to break before
Motors must be designed for an ambient temperature make in the modern interrupting devices and hence is
of 50°C. safe to adopt. The motors should, however, be suitable
HT motors must be generally wound with class F of withstanding excessive voltages on account of this
insulation and the temperature rise should not exceed up to 150% of the rated voltage for at least one second
the prescribed limits of class B insulation. LT motors during such bus transfers.
up to 250 kW, however, can be wound with class B
insulation. Nure The time gap between a fast bus transfer is so small that
it will not permit the various drives to slow down sufficiently to
The performance of the motors must conform to
affect their performance or the system if they are made to re-
IEC 60034- 12. accelerate (reenergize) on restoration of power.
8 Voltage and frequency variations
During start-up, the motors must be suitable for
In a fast bus transfer scheme, the phase angle is
accelerating to 80% of the rated voltage.
monitored through special relays (Section 16.11) which
Motors must run at full h.p. under the following
initiate the changeover, so that the self-induced e.m.f.
conditions:
of the motor does not slip too far in the phase angle,
Variation in frequency: f5%
A@, between the two voltages and the motor is not
Variation in voltage: f l O %
exposed to excessive overvoltages. At higher A 6 the
Combined variation in frequency and voltage: f10%
relays will block the transfer and protect the system
Motors must not stall due to a momentary dip in
voltage up to 70% of the rated voltage, i.e. from excessive voltages. If the fast bus transfer fails
to change over automatically, slow changeover takes
7’ to be more than T,./(0.625)’, i.e. 256% for a
place and the motor-induced e.m.f. is allowed to decay
1200 r.p.m. motor and TJ(O.605)’, i.e. 273% for a
by up to 40-20% before the bus transfer takes place.
1000 r.p.m. motor and less, as shown in Table 1.5.
For insulating and bracing the windings, such bus
Motors must run satisfactorily for 5 minutes at a
supply voltage of 75% of the rated value. transfers may occur up to 500 times in the total lifespan
of the motor.
12 Starting time and locked rotor withstand time
Nore This operating condition is, however, not specific for For motors with a starting time of up to 20 seconds,
it does not stipulate the frequency of occurrence of such a
contingency. It may be assumed that this condition will not with the minimum permissible applied voltage
occur more than once before thermal stability is reached. (80%), the locked rotor withstand time under hot
See also Section 3.7. In normal practice a motor meeting the conditions at rated voltage must be at least 2.5
other operating conditions noted above in all likelihood will seconds more than the starting time.
satisfy this requirement also without needing yet another For motors with a starting time of more than 20
derating. See also Example 7.1, seconds but within 45 seconds, at the minimum
permissible applied voltage (SO%), the locked rotor
9 Starting current withstand time, under hot conditions at rated voltage,
On DOL the I,, must not exceed 600% of I, but for must be at least 5 seconds more than the starting time.
boiler feed pumps it must be limited to 450% of I,, 13 Bearings: The bearings will preferably have an arrange-
subject to the tolerance stipulated in IEC 60034-1. ment for self-lubrication.
To determine the starting current, when the test is 14 Bearings must be insulated wherever necessary, to
conducted at a reduced voltage (1/& Vr ), prevent them from shaft currents (Section 10.4.5).
allowance must be made for the saturation effect 15 Over-speed: Motors will be designed to withstand
while estimating the value of I,, at the rated voltage. 120% of ff, for at least 2 minutes without any
See also Section 1.6.2(A) also (the important note mechanical damage.
on starting torque). 16 Noise level: Motors must conform to the requirements
of IEC 60034-9. A safe sound pressure level for a
Note At full voltage, the stator core will offer a lower human body to perform better, during an 8-hour
Special-purpose motors 7/189

Table 7.9 Sources emitting sound and their likely loudness


level

Noise level (dB) Sound source

0 Threshold of hearing
20 Rustling sound, whisper, homes
(quiet places)
40 Motor cars
60 Normal conversation
80 Street traftic
100 Light engineering workshop
120 Thunderllightning

working day, without undue fatigue, is considered at

-
90 dB as noted in Section 7.9. For recommended
values of sound level for airborne noise, refer to the
IEC publication. See also Table 7.9 for sources in s=1
Speed
day-to-day life that emit noise and their likely noise Slip at 80%
levels. voltage
17 Temperature detectors
HT motors must have a minimum six numbers of Figure 7.21 Determining the accelerating torque
resistance temperature detectors (RTDs) (See section
12.8).
All bearings of HT motors must be provided with minutes and can be assumed to occur once an hour. Also
embedded temperature detectors (ETDs). likely overloading by 20% for the same period in the same
18 Polarization index test duration. Only one contingency occurring at a time. The motor
Motors rated 7500 kW and less must be considered should also be capableof running, without stalling if the voltage
drops to 70% momentarily, say, for 25 cycles.
suitable for dielectric tests or operation only when
the polarization index or the value of the insulation Ambient temperature = 50°C
resistance (at 40°C) is at least the minimum Permissible starting = DOL in a squirrel cage or rheostat in
recommended values. a slip-ring motor
Motors rated above 7500 kW must have both the Desired starts = six equally spread starts per hour and
three consecutive hot starts not to
polarization index and the insulation resistance above be repeated for one hour
the minimum recommended values. Service factor = 1.1, alternatively 1.15
The recommended minimum value of the
polarization index for motors having class B or F Solution
insulation must be 2 when determined according to Deratings
IEC 60034- 18-1. (a) For +lo% voltage and frequency variation: 90%
(Section 1.6.2(C)).
Note The above recommendations are those of an electricity (b) For 50°C ambient temperature: 92% (Section 1.6.2).
authority of one country and may vary for other countries. (c) At 80% voltage, the full load torque of the motor will drop
to 0.73*, Le. 0.53 times the rated torque, as shown in
Table 1.5. Also the motor will tend to stall unless adequate
torque is available on the motor torque curve, i.e. Tpo
7.20 Selection of a special-purpose must not be less than 1/0.53 or 189%. The motor will thus
motor start to drop its speed until it reaches a point where a
motor torque of 189% of 450 kW is available. The motor
will now operate at a higher slip, causing higher slip losses.
Example 7.1 Assuming the mill torque at the reduced speed to be the
Select a suitable motor for a ball mill with the following load same as at 100% speed, then the kW requirement of the
details: mill
kW = 450 kW- N . T
r.p.m. = 400 through V-belts
Startina . = 40% rising to 100% at full load
- torque This will also decrease in the same proportion as the
(Figure 7.51). increase in slip. For a rough estimate, we may also ignore
G d of rotating masses = 10 000 kgm’ the higher slip losses for an equal reduction in the required
kW. However, due to the lower voltage the motor current
Supply system: will increase proportionately and will be IJ0.8 or 1.251,.
Voltage = 3.3 kV f 10% The motor will thus run overloaded by 25% for 20 minutes
Frequency = 50 Hz ? 3% which is likely, and not more than once an hour. The
frequency of occurrence must be known. A higher derating
Combined voltage and frequency variation not to exceed may be necessary if such a condition is frequent.
f 10%. Voltage may fall to 80% during running for about 20 (d) Overloading of 20% for 20 minutes per hour need not be

You might also like