A 4 3 2 1 EQUIPMENT FOUNDATION SCHEDULE 1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS OTHERWISE A
NOTED AND COORDINATES ARE IN MILLIMETERS UNLESS
MEMBER W L H EA T.O.C REMARK OTHERWISE NOTED.
17,000
EF01 3,830 1,515 625 1 EL.+ 5,125 INDOOR FDN. 2. FINISHED GROUND LEVEL (FGL) = EL.+4,500mm
6,000 5,500 5,500 EF02 5,175 1,515 650 1 EL.+ 5,150 INDOOR FDN. FINISHED GROUND FLOOR LEVEL(FGFL) = EL.+4,800mm
PN 3. CONCRETE STRENGTH
TN 1,970 600 2,900 53070 2,195 300405 600 1,930 5,500 EF03 1,050 1,000 150 1 EL.+ 4,950 INDOOR FDN. 1) f’c=30.0MPa : ALL BUILDINGS AND THEIR FOUNDATIONS, STACKS
EF04 1,400 1,400 300 1 EL.+ 5,100 INDOOR FDN. AND ASH SILOS (INCLUDING FOUNDATION)
400
2) f'c=24.0MPa : OTHER FOUNDATION
EF05 300 250 757 4 EL.+ 5,557 INDOOR FDN. 3) f’c=13.8MPa : PLAIN CONCRETE FOR ENCASEMENTS, THRUST
PS09
B HF01 2,000 1,000 500 1 EL.+ 5,000 OUTDOOR FDN. BLOCKS, ELECTRICAL DUCTS, LEAN CONCRETE BACKFILL, AND B
3 SIMILAR
PS01 1,300 600 700 3 EL.+ 5,200 OUTDOOR FDN.
WHERE, f’c=CYLINDER COMPRESSIVE STRENGTH AT 28 DAY
1,300
1,300
1,300
N 7,550,000 NS2-XB02-P0USG-171143
PS02 400 400 150 1 EL.+ 4,650 INDOOR FDN.
2,600
E 3,841,000 4. REINFORECING BAR STRENGTH
PS01 PS01 PS01 FLOOR DRAIN TYPE(TYP.) PS02 400 400 150 1 EL.+ 4,950 OUTDOOR FDN. 1) ROUND BARS
300
250
250
GRADE SR295, fy=300 MPa
145 1,250 PS11 SUMP PIT(TYP.) PS03 400 400 150 1 EL.+ 4,650 OUTDOOR FDN. 2) DEFORMED BAR
400
400
PS03 PS02 300x300x300
PS03 400 400 150 1 EL.+ 4,950 INDOOR FDN. GRADE SD390, fy=400MPa
1,550
1,400
PS09 400 1,580 200 857
1,630 400 3) MESH REINFORCEMENT
400
900
400200 900
TG1 TG1 TG1 PS04 400 400 150 2 EL.+ 4,950 INDOOR FDN. GRADE SD490, fy=500MPa
250
250150
PS05 400 400 150 2 EL.+ 4,950 INDOOR FDN. 5. CEMENT
400 200
A
C TRENCH(TYP.) TYPE OF CEMENT WILL BE TYPE 1 PORTLAND CEMENT FOR C
PS03 PS02 PS06 1,400 400 150 1 EL.+ 4,650 OUTDOOR FDN.
960
960
960
1,130
100(W)X150(H) PS13 400 GENERAL APPLICATIONS AND FOR SEAWATER APPLICATIONS
PS06 1,400 400 150 1 EL.+ 4,950 INDOOR FDN. PORTLAND BLAST FURNACE CEMENT OR EQUIVALENT ALONG
PS10 WITH WATERPROOFING COMPOUND SHALL BE USED.
150 250 PS07a 2,300 400 150 1 EL.+ 4,950 INDOOR FDN.
400
1,515
1,515
NS2-XB02-P0USG-171143 EF03
PS08 850 400 150 1 EL.+ 4,950 INDOOR FDN. CAST-IN-PLACE CONCRETE(NON PRESTRESSED)
987
200200 EF02
EF01 COLUMN WALL
PS10 PS09 1,250 400 150 2 EL.+ 4,650 OUTDOOR FDN. CONDITION OF EXPOSURE FOUNDATION
400 50
130
50
PS14 BEAM SLAB
83
PS04
520 400
477 400
PS05 PS14 PS10 1,000 400 150 2 EL.+ 4,950 INDOOR FDN. CONCRETE NOT
EXPOSED TO WATER - 40 20
D 1,020 3,830 1,150 2,915 5,175 PS11 300 300 150 1 EL.+ 4,650 OUTDOOR FDN. D
900
900
CONCRETE EXPOSED TO
400 1,580 200 250410
2,000
PS13 250 200 150 1 EL.+ 4,950 INDOOR FDN. EARTH OR WEATHER
2,300
75 40 40
GS1
850
180 (75) (75) (75)
8,000
(GROUND WATER
TG1
PS14 250 200 150 2 EL.+ 4,950 INDOOR FDN.
400
400
THK.200
1,530
PS05 PS08 1,260 1,050 600 OR SEA WATER)
PS04 TF01 1,000 1,000 300 1 EL.+ 4,800 OUTDOOR FDN.
TG1
400 635
400250400 1,580 CONCRETE CAST AGAINST
TG1
THK.200 PS07a PS07b TP01 1,700 1,000 300 1 EL.+ 4,800 OUTDOOR FDN. AND PERMANENTLY 75 75 75
250 1,000 EXPOSED TO EARTH
863
1,630 400 1,750 400 1,820 PS06 500 1,400
GIRDER & BEAM MEMBER LIST GROUND 7. CHAMFERED CORNERS OF CONCRETE COLUMN & WALL
: ALL EXPOSED CORNERS (ANGLE OF 90‘ OR LESS) OF
EL.+ 4,800 (T.O.C)
1,000
E
SUMP PIT 265400 2,010 1,400 MEMBER W H EA REINFORCED CONCRETE SHOULD BE CHAMFERED. (25mmX25mm)
E
300x300x100 8. FOR THE FOLLOWING ITEMS, SEE STANDARD DRAWINGS UNLESS
600 300 616 300
1,400
EF05 x 4EA 317 1,000 - MINIMUM CONCRETE COVER
250150 THK.150 DYKE WALL
LEGEND - HOOK, DEVELOPMENT AND SPLICES OF REBAR
1,500
7
(H=500) 2,675 1,400 1,425 EF04
NS2-XB02-P0USG-171143 9. MEMBERS WITHOUT DIMENSION
TG1 TG1 TG1 : SYMMETRICAL WITH RESPECT TO CENTER LINE
500
250 150
400
B EL.+ 4,800 (T.O.C)
250
250
400285
SLOPE
F F
1,000
(1/8)
(1/8)
2,400
2,400
TP01 N 7,567,000 EL.+ 5,100 (T.O.C)
E 3,849,000
2,521 1,700 1,279
EL.+ 5,125 (T.O.C)
REFERENCE DOCUMENTS/DRAWINGS
DOC/DWG NO. TITLE
EL.+ 5,150 (T.O.C)
NS2-UC07-P0ZEN-110001 SITE PLAN
2,850 2,900 250 5,500 2,350 2,900 250 NS2-UC07-P0ZEN-110002 PLOT PLAN
G NS2-VB00-P0ZEN-170001 DESIGN MANUAL FOR BUILDINGS & STRUCTRES G
EL.+ 5,557 (T.O.C)
NS2-UV01-P0ZEN-170102~11 STANDARD DRAWINGS
300 440
4 3 2 1
17,000
H H
SUMP PIT
6,000 5,500 5,500 (300x300x300)
FOR CONSTRUCTION
EL. +4,800 (T.O.C)
1,020 3,830 1,150 2,915 5,175 1,260 1,050 600 THIS DRAWING IS THE PROPERTY OF DOOSAN HEAVY INDUSTRIES VIETNAM.
300
IT IS NOT TO BE COPIED OR USED IN ANY WAY DETRIMENTAL TO THE COMPANY.
2,585 2,590 EL. +4,500 (G.L)
J EL.+ 5,125 (T.O.C) EL.+ 4,800 (T.O.C) EL.+ 5,150 (T.O.C) EL.+ 4,950 (T.O.C) 0 05.04.2019 FOR CONSTRUCTION C.M.CHOI S.H.PARK J.T.SEO J
SECTION - B Date
Rev. (DD.MM.YYYY) DESCRIPTION DRAWN CHKD. APPD.
Project
EL. +4,800 (T.O.C)
350
SCALE-
325
1 : 30
150
* REFER TO THE DRAWING NO. NS2-UV04-P0ZEN-170105 NGHI SON 2 BOT THERMAL POWER PLANT PROJECT
EL. +4,500 (G.L)
2 Owner
TN
PN
200
300
200
200
TG1
D16@200
150 500 150 150 500
DRAWING TITLE
300 700 300
SUMP PIT DETAIL(INDOOR) TRENCH DETAIL-1(INDOOR) TRENCH DETAIL-2(INDOOR) DYKE WALL SECTION DETAIL FIRE FIGHTING PUMP HOUSE
GROUND FLOOR FRAMING PLAN
SCALE- NONE SCALE- NONE SCALE- NONE SCALE- 1 : 20
M * REFER TO THE DRAWING NO. NS2-UV04-P0ZEN-170105 * REFER TO THE DRAWING NO. NS2-UV04-P0ZEN-170105 M
SCALE DRAWING NUMBER SHEET NO. REV. NO.
1/60 NS2-XB02-P0USG-171143 1 of 1 2
A1 (841 x 594)
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16