Optimized construction The need for busbars and cables in
The ACS800-04 has several benefits the cabinet has been minimized by that make it the optimal choice for having the incoming power termi- There are several other possibilities panel builders. nals on the top of the module. This to adapt the drive module to enables use of the optimal cabling customer needs as well. As examples No special EMC proof cabinets are route. are possibility of wall or floor needed. In ACS800-04 drives with mounting and possibility of chang- in-built EMC filtering, both radiated Maximised flexibility ing the outputs from left to right. and conducted emissions are Thanks to modular design ACS800- restricted to EN 61800-3 limits 04 offers wide variety of installation Naturally also the adaptive software without the need for any extra possibilities. Both bookshelf and other standard and optional hardware. mounting for optimised width and features of the ACS800 series are flat type mounting for optimised available. Innovative fixing mechanics which depth are available. minimize the number of bolts facil- itate the attachment of the drive Main standard hardware Accessories for the ACS800-04 module. Fixing of the control unit features: In-built options: and control panel is easy thanks to • Optimised design for cabinet • Brake chopper the DIN rail mounting and new type assembly • EMC filter: of mounting platform. • EMC compliant module • EN 61800-3, 2nd environment, • Modular design allowing wide unrestricted distribution The compact size with plenty of variety of variants • Common mode filters for built-in options minimizes both • Easy access to power terminals motor protection space requirements and the amount • Easy access and free location of • Analogue and digital I/O of assembly work needed. I/O terminals extension modules • Compact design • Fieldbus modules Easy cabling • Harmonic filtering choke inside • Pulse encoder interface module The easily accessible power termi- • Long life time cooling fan and • Various output busbar options nals with plenty of space around capacitors (ACS800-04M) them make power cabling for the • Extensive, programmable I/O • Flat type cabling pedestal ACS800-04 easy. Moreover, a • Inputs galvanically isolated enabling sideways mounting separate control unit enables easy • Three I/O and fieldbus extension (ACS800-04M) access to the I/O terminals. The slots inside control unit can be optimally sited • Large power terminals allowing Other options: inside the cabinet to enable access use of over sized or aluminium • Control panel and mounting to the I/O terminals without need- cable platform ing to open the drive module.
3AFE 64572504 REV E EN 17.10.2003 11
Cooling air flow requirements
Type Nominal No-overload Light-overload Heavy-duty Noise Heat Air flow
Icont.max : rated current available continuously without 1) 50% overload available if T amb < 25°C. Enclosure overloadability at 40°C. If Tamb = 40°C, max overload for 1 min is 37%. Degree of Protection: IP 00 IMAX : maximum output current. Available for 10 s at 2) 50% overload available if T amb < 30°C. Paint color: start, otherwise as long as allowed by drive tempe- If Tamb = 40°C, max overload for 1 min is 40%. NCS 1502-Y (RAL 90021/PMS 420C) rature. Note: max. motor shaft power is 150% Phd . 3) 50% overload available if T amb < 20°C. Typical Ratings: If Tamb = 40°C, max overload for 1 min is 30%. No-overload use Type Height Width Depth Pcont.max: typical motor power in no-overload use. 4) Higher value available if output frequency is mm mm mm above 41Hz. RDCU control unit *) 282 126 41 Light-overload use *) IN: continuous current allowing 110% IN for coming with every unit 1min/ 5 min at 40°C. PN: typical motor power in light-overload use. Bookshelf design Heavy-duty use Ihd : continuous current allowing 150% Ihd for Type Height Width Depth Weight 1min/ 5 min at 40°C. mm mm mm kg R7 1121 426 467 100 Phd: typical motor power in heavy-duty use. R8 1558 571 564 205 The current ratings are the same regardless of the Width with cable connection plate for output cables. supply voltage within one voltage range.
The ratings apply at 40°C ambient temperature.
At higher temperatures (up to 50°C) the derating is Flat type design 1%/1°C. Type Height Width Depth Weight mm mm mm kg R7 1152 631 259 100 R8 1589 779 356 205