S600+ Troubleshooting
Power Issue
Check the wiring connections at terminal block TB1 on the CPU back plate
and the wiring at the power source.

Check the power supply voltage.

Check the fuse on the CPU module.

If the power supply seems to be working correctly,


but the start up routine doesn't appear on the display,
check the fuse for damage.

If the problem persist and none of the check appear to solve


the problem, please contact your local sales representative to
return the unit.
Start up Issue
If RESETTING, RESTARTING, or the Startup menu does not appear on the
display:

Check the power supply voltage.

Check the fuse on the CPU module

After initialization, if the Startup menu appears instead of the Main menu, select
the Warm Start option. If a warm start does not occur:

Check jumper J2 on the CPU module. If it is in the closed (cold start) position,
then move it into the open (warm start) position to allow a warm start. This
also allows the unit to bypass the Startup menu in the future.

Check for a valid configuration. If no configuration is present, send and reflash


config File.

Check whether a Clear SRAM command has been issued.


Front Panel Lighting Issue
If the Front Panel display is not backlit:

Check connector (J2) between front panel and main board.

Check the display for text and numbers. If the screen is entirely blank, contact
your local sales representative or technical support.
Front Panel LED Issue
If the LED on the front panel indicates alarm and malfunction states:

If the LED is green, then the S600+ is functioning correctly.

If the LED is red, an alarm state exists.

If the LED is orange, power down the S600+, remove and reseat the boards,
and then re-apply power to the S600+.

Note: The LED is orange while at the Startup menu. If it is still orange when the
configuration is running, contact your local sales representative or technical
support.
IO LED Issue
If the red or green LEDs on the backplate of the I/O module do not blink while
the S600+ is operating:

Check the I/O module connections. Power down, remove and reseat the I/O
module, and then re-apply power.

Check the front panel display and LED. If they are not lit, you may have a
power issue.

Check with the person who configured the unit whether you have the correct
I/O module fitted.

Check the running configuration for any BAD TX or BAD RX messages. From
the Main menu, select TECH/ENGINEER > COMMUNICATIONS > SERIAL
PORTS > PORT 08.
IO Fail Message
If the front panel displays an I/O Fail message:

Check the jumper settings on the I/O modules.

Check the I/O field wiring connections.

Check that the I/O modules are seated and secured.


Serial Communication Issue
If you are experiencing troubles with a serial communications connection (RS-
232, RS-422, or RS-485):

Check to make sure power is applied to the S600+.

Check the wiring to the termination block or connector.

Check the communication port settings from the front panel display.

Check the Modbus address.

Check the setting of the termination resistor jumper.