You are on page 1of 3

3

Air density (γ): 1.20 kg/m


Installation type “B”: free inlet, ducted outlet
3
12000 m /h fan test chamber according to AMCA 210/05 fig. 12
Free field Lp(A) measurements at 1 m according to ISO 3746:2011

Unit type: Motor code: 211100G Motor Th.prot: YES IN


Test nr.: 2227 Motor power [W]: 120 Capacitor [μF]: 6
Date: 2017/02/15 Motor poles: 4 Unit max. abs. current [A]: 1,3
Power supply[V]: 230 1~ Mot. prot. class: IP44 Unit max. abs. power [W]: 300
Frequency [Hz]: 50 Mot. ins. class: F

ErP status: ErP 2018

400
AC1600

350

300 230 V@50 Hz


50 Hz unit limit

56,4
250
Pfs [Pa]

56,7
200

57,7
150

58,0 dB(A)
100

50

0
0 200 400 600 800 1000 1200 1400 1600 1800
Q [m3/h]

Data are not certified by AMCA


------------------------------------------------------------------------------------------------------------------------------------------------------------------
3
Air density (γ): 1.20 kg/m
Installation type “B”: free inlet, ducted outlet
3
12000 m /h fan test chamber according to AMCA 210/05 fig. 12
Free field Lp(A) measurements at 1 m according to ISO 3746:2011

Unit type: Motor code: 211100G Motor Th.prot: YES IN


Test nr.: 2227 Motor power [W]: 120 Capacitor [μF]: 6
Date: 2017/02/15 Motor poles: 4 Unit max. abs. current [A]: 1,3
Power supply[V]: 230 1~ Mot. prot. class: IP44 Unit max. abs. power [W]: 300
Frequency [Hz]: 50 Mot. ins. class: F

ErP status: ErP 2018


350
AC1600
300

250
Abs. power [W]

200

150

100

50 230 V@50 Hz

0
0 200 400 600 800 1000 1200 1400 1600 1800
Q [m3/h]

1,4
AC1600
1,2

1,0
Abs. current [A]

0,8

0,6

0,4 230 V@50 Hz

0,2

0,0
0 200 400 600 800 1000 1200 1400 1600 1800
Q [m3/h]
------------------------------------------------------------------------------------------------------------------------------------------------------------------
Setup for unit noise test

test chamber

microphone

duct

AHU

Noise test setup is according to ISO 3746:2011 Standard.


A microphone, placed at 1 meter from the unit and 1 meter from the ground, gets the
sound pressure levels in different unit operating conditions.
Test data are then mathematically revised in order to get the A-weighted free-field total
sound pressure levels Lp(A) of the unit.
The Lp(A) value in dB(A) is available on CMC documentation.
Add 11 dB(A) to the sound pressure level Lp(A) value to get the correspondent sound
power level Lw(A).