Case study fire

English

00:00:06 SPK_1

A team of 6 workers were roller painting in a confined space when a flash fire occurred.

00:00:12 SPK_1

One worker was killed and three others injured before work started.

00:00:25 SPK_1

An entry permit for painting and cleaning work in a confined space was applied.

00:00:30 SPK_1

The safety assessor conducted a gas test.

00:00:33 SPK_1

The results of the gas test showed that the confined space was safe for entry and he endorsed the
permit.

00:00:46 SPK_1

Two days before the incident, the worker started roller painting.

00:00:57 SPK_1

On the morning of the incident, a gas test was conducted.

00:01:01 SPK_1

No abnormalities were observed and the entry permit was endorsed.

00:01:05 SPK_1

The workers carried out vacuuming and clearing work using thinner, which was a flammable substance.

00:01:12 SPK_1

At noon, a second gas test was conducted.

00:01:15 SPK_1

Following the gas test, the quality of the painting in the confined space was inspected to assess the
quality of the work done.

00:01:22 SPK_1

The workers were then instructed to perform some touch ups to the paint job.
00:01:27 SPK_1

After the safety assessor conducted another gas test, the workers brought in drums of paint and
hardener into the confined space.

00:01:35 SPK_1

One of the workers makes the paint and hardener in the confined space for 5 minutes.

00:01:40 SPK_1

He then distributed the mixture into the empty drums.

00:01:43 SPK_1

The roller painting commenced.

00:01:45 SPK_1

30 minutes later a flash fire occurred.

00:01:48 SPK_1

Painting in a confined space had resulted in the death of 1 worker and injured three others.

00:01:54 SPK_1

What went wrong?

00:01:55 SPK_1

Accumulation of flammable vapors The activities in the confined space had accelerated the accumulation
of flammable solvent vapors in the confined space.

00:02:06 SPK_1

These activities include the mixing of paint and hardener in the confined space, distributing the mixture
into empty drums, drying of paint.

00:02:16 SPK_1

Adequate measures were not in place to eliminate the accumulation of flammable vapors.

00:02:21 SPK_1

No gas monitoring.

00:02:23 SPK_1

Portable gas detectors were not provided to monitor the concentration of flammable gases in the
confined space.
00:02:31 SPK_1

Lighting with exposed filament, electrical wires, not properly maintained light bulbs with exposed
filaments, and exposed electrical wires are sources of ignition.

00:02:42 SPK_1

No effective maintenance regime was in place to ensure that the lights and wires were in good condition.

00:02:49 SPK_1

Lessons Learned Risk Assessment Before starting any work in a confined space, always conduct a risk
assessment to identify safety and health hazards.

00:03:05 SPK_1

Measures to minimize risks should be implemented.

00:03:08 SPK_1

Avoid accumulation of flammable vapors.

00:03:13 SPK_1

Mix the paint and hardener outside and not in the confined space to avoid accumulation of flammable
vapors in a confined space.

00:03:23 SPK_1

Provide portable gas detectors.

00:03:25 SPK_1

Provide workers with suitable portable gas detectors to monitor the concentrations of flammable gases
or vapors while working in confined spaces.

00:03:35 SPK_1

The concentrations should not exceed 10% of their lower explosive limits.

00:03:40 SPK_1

Use flameproof lighting.

00:03:43 SPK_1

Flameproof lighting should be used in confined spaces.

00:03:46 SPK_1

Establish a regular maintenance regime to ensure that lighting and live wires remain in good condition.
00:03:53 SPK_1

Ventilation dilution or forced ventilation should be used to dilute solvent vapors to prevent accumulation
of flammable vapors within the confined space.

00:04:06 SPK_1

Use a stronger force to control airflow during increased painting activities.

00:04:12 SPK_1

Ideally, both exhaust and forced ventilation methods should be used together.

You might also like