Professional Documents
Culture Documents
Att 1 - Rev A1 - Cable Sizing
Att 1 - Rev A1 - Cable Sizing
DOC NO : SLON-GATHMGNO000-ELE-CAL-PHR-2006-00
REV : A1
CABLE ROUTE LOAD DATA CABLE DATA CABLE AMPACITY CABLE VOLTAGE DROP, Vd
A. SWITCHRACK #1
1 xx xx SWITCHRACK #1 xx JB AERATOR NEW #1 480 F 41.44 64.44 0.64 0.81 95.69 119.62 1 3C 2/0 - 480 0.256 0.000 190 0.72 137 Yes 13.07 2.72 5 Yes N/A N/A N/A N/A 3C-2/0 AWG ABOVEGROUND
B. JB AERATOR NEW #1
1 xx xx JB AERATOR NEW #1 xx AERATOR PUMP NEW #1 480 F 2.24 2.66 0.84 0.81 3.95 4.94 1 3C 12 - 20 5.209 0.000 9 0.72 7 Yes 0.60 0.13 5 Yes N/A N/A N/A N/A 3C-12 AWG ABOVEGROUND
2 xx xx JB AERATOR NEW #1 xx AERATOR PUMP NEW #2 480 F 2.24 2.66 0.84 0.81 3.95 4.94 1 3C 12 - 20 5.209 0.000 9 0.72 7 Yes 0.60 0.13 5 Yes N/A N/A N/A N/A 3C-12 AWG ABOVEGROUND
3 xx xx JB AERATOR NEW #1 xx AERATOR PUMP NEW #3 480 F 2.24 2.66 0.84 0.81 3.95 4.94 1 3C 12 - 20 5.209 0.000 9 0.72 7 Yes 0.60 0.13 5 Yes N/A N/A N/A N/A 3C-12 AWG ABOVEGROUND
4 xx xx JB AERATOR NEW #1 xx AERATOR PUMP NEW #4 480 F 2.24 2.66 0.84 0.81 3.95 4.94 1 3C 12 - 20 5.209 0.000 9 0.72 7 Yes 0.60 0.13 5 Yes N/A N/A N/A N/A 3C-12 AWG ABOVEGROUND
5 xx xx JB AERATOR NEW #1 xx AERATOR PUMP NEW #5 480 F 2.24 2.66 0.84 0.81 3.95 4.94 1 3C 12 - 20 5.209 0.000 9 0.72 7 Yes 0.60 0.13 5 Yes N/A N/A N/A N/A 3C-12 AWG ABOVEGROUND
6 xx xx JB AERATOR NEW #1 xx JB AERATOR NEW #2 480 F 13.81 21.48 0.64 0.81 31.90 39.87 1 3C 4 - 250 0.815 0.000 60 0.72 43 Yes 7.24 1.51 5 Yes N/A N/A N/A N/A 3C-4 AWG ABOVEGROUND
7 xx xx JB AERATOR NEW #1 xx JB AERATOR NEW #3 480 F 13.81 21.48 0.64 0.81 31.90 39.87 1 3C 4 - 180 0.815 0.000 60 0.72 43 Yes 5.21 1.09 5 Yes N/A N/A N/A N/A 3C-4 AWG ABOVEGROUND
C. JB AERATOR NEW #2
1 xx xx JB AERATOR NEW #1 xx AERATOR PUMP NEW #6 480 F 2.24 2.66 0.84 0.81 3.95 4.94 1 3C 12 - 20 5.209 0.000 9 0.72 7 Yes 0.60 0.13 5 Yes N/A N/A N/A N/A 3C-12 AWG ABOVEGROUND
2 xx xx JB AERATOR NEW #1 xx AERATOR PUMP NEW #7 480 F 2.24 2.66 0.84 0.81 3.95 4.94 1 3C 12 - 20 5.209 0.000 9 0.72 7 Yes 0.60 0.13 5 Yes N/A N/A N/A N/A 3C-12 AWG ABOVEGROUND
3 xx xx JB AERATOR NEW #1 xx AERATOR PUMP NEW #8 480 F 2.24 2.66 0.84 0.81 3.95 4.94 1 3C 12 - 20 5.209 0.000 9 0.72 7 Yes 0.60 0.13 5 Yes N/A N/A N/A N/A 3C-12 AWG ABOVEGROUND
4 xx xx JB AERATOR NEW #1 xx AERATOR PUMP NEW #9 480 F 2.24 2.66 0.84 0.81 3.95 4.94 1 3C 12 - 20 5.209 0.000 9 0.72 7 Yes 0.60 0.13 5 Yes N/A N/A N/A N/A 3C-12 AWG ABOVEGROUND
5 xx xx JB AERATOR NEW #1 xx AERATOR PUMP NEW #10 480 F 2.24 2.66 0.84 0.81 3.95 4.94 1 3C 12 - 20 5.209 0.000 9 0.72 7 Yes 0.60 0.13 5 Yes N/A N/A N/A N/A 3C-12 AWG ABOVEGROUND
D. JB AERATOR NEW #3
1 xx xx JB AERATOR NEW #1 xx AERATOR PUMP NEW #11 480 F 2.24 2.66 0.84 0.81 3.95 4.94 1 3C 12 - 20 5.209 0.000 9 0.72 7 Yes 0.60 0.13 5 Yes N/A N/A N/A N/A 3C-12 AWG ABOVEGROUND
2 xx xx JB AERATOR NEW #1 xx AERATOR PUMP NEW #12 480 F 2.24 2.66 0.84 0.81 3.95 4.94 1 3C 12 - 20 5.209 0.000 9 0.72 7 Yes 0.60 0.13 5 Yes N/A N/A N/A N/A 3C-12 AWG ABOVEGROUND
3 xx xx JB AERATOR NEW #1 xx AERATOR PUMP NEW #13 480 F 2.24 2.66 0.84 0.81 3.95 4.94 1 3C 12 - 20 5.209 0.000 9 0.72 7 Yes 0.60 0.13 5 Yes N/A N/A N/A N/A 3C-12 AWG ABOVEGROUND
4 xx xx JB AERATOR NEW #1 xx AERATOR PUMP NEW #14 480 F 2.24 2.66 0.84 0.81 3.95 4.94 1 3C 12 - 20 5.209 0.000 9 0.72 7 Yes 0.60 0.13 5 Yes N/A N/A N/A N/A 3C-12 AWG ABOVEGROUND
5 xx xx JB AERATOR NEW #1 xx AERATOR PUMP NEW #15 480 F 2.24 2.66 0.84 0.81 3.95 4.94 1 3C 12 - 20 5.209 0.000 9 0.72 7 Yes 0.60 0.13 5 Yes N/A N/A N/A N/A 3C-12 AWG ABOVEGROUND
2) TEMPERATURE CORRECTION FACTOR AND GROUP DERATING FACTOR ARE BASED ON IEC 60364-5-523.
3) CABLE AMPACITY, RESISTANCE, AND REACTANCE ARE BASED ON CATALOG CABLE TECHNICAL DATA.