Msheireb Downtown Doha Project – Phase 2

Building Management System

FCU IO Point Schedule


PROJECT: MSHIEREB DOWNTOWN DOHA PHASE II BUILDING MANAGEMENT SYSTEM - IO POINT LIST

PANEL REF. : FCU TYPE-1


FCU COOLING ONLY (W/O HEATER ) (TYPE 1) - SERVING TO BASEMENT (TYPICAL FOR
LOCATION : MS-FEC-2611-0 BMS Field Device Remarks Relays Fuses USED CABLE TYPE CABLE QTY
FCU-01 TO FCU-06,FCU-07,FCU-09 IN BASEMENTS)
CON
TOL

TYPEPoint Point Description Device Description UI BI BO UO AO


AT

SA BUS SPACE TEMPERATURE


ST

SA BUS NETSTAT NS-APR7102-0 BY JCI


IN : 1 SUPPLY AIR TEMPERATURE SIGNAL FROM TEMPERATURE SENSOR TE-6311M-1 BY JCI 1 22 AWG 2C TWISTED PAIR 1
IN : 2 FILTER ALARM VOLT FREE CONTACT TO DDC FROM DPS P233A BY JCI 1 22 AWG 2C TWISTED PAIR 1
IN : 3 MOTORISED CONTROL VALVE POSITION 0-10 VDC/4-20mA SIGNAL TO DDC BY JCI 1 22 AWG 2C TWISTED PAIR 1
UI

IN : 4 SPARE
IN : 5 SPARE
IN : 6 SPARE
IN : 7 CONDENSATE TRAY FULL BLOCK STATUS VOLT FREE CONTACT TO DDC BY MEP 1 22 AWG 2C TWISTED PAIR 1
DI
MS-FEC2611-0

IN : 8 FAN AIR FLOW STATUS VOLT FREE CONTACT TO DDC FROM DPS P233A BY JCI 1 22 AWG 2C TWISTED PAIR 1
FAN SATRT/STOP COMMAND RELAY OUTPUT BY JCI 22 AWG 2C TWISTED PAIR 1
OUT : 1 R F 1
DRAIN PUMP SATRT/STOP COMMAND RELAY OUTPUT BY JCI 22 AWG 2C TWISTED PAIR 1
DO

OUT : 2 SPARE
OUT : 3 SPARE
OUT: 4 FAN SPEED CONTROL 0-10VDC OUTPUT FROM DDC TO VFD BY JCI 1 22 AWG 2C TWISTED PAIR 1
OUT : 5 SPARE
UO

OUT : 6 SPARE
OUT : 7 SPARE
OUT : 8 MOTORISED CONTROL VALVE OUTPUT 0-10VDC OUTPUT FROM DDC TO VALVE ACTUATOR VG1000 BY JCI 1 22 AWG 2C TWISTED PAIR 2
AO

OUT:9 SPARE
DESCRIPTION UI BI BO UO AO
TOTAL POINTS USED 3 2 1 1 1
TOTAL POINTS SPARE 3 0 2 3 1
TOTAL CAPACITY 6 2 3 4 2
SPARE CAPACITY IN % 50 0 67 75 50

Page 1/16

Rev-0 Johnson Controls, Inc.


PROJECT: MSHIEREB DOWNTOWN DOHA PHASE II BUILDING MANAGEMENT SYSTEM - IO POINT LIST

PANEL REF. : FCU TYPE-5


SMALL & MEDIUM SIZE FCU FOR ICT ROOMS (TYPE 5) - SERVING TO CTR ROOMS
LOCATION : MS-FEC-2611-0, MS-IOM1711-0 BMS Field Device Remarks Relays Fuses USED CABLE TYPE CABLE QTY
(TYPICALL FOR FCU-10)
CON
TOL

TYPEPoint Point Description Device Description UI BI BO UO AO


AT

SA BUS SPACE TEMPERATURE


ST

SA BUS NETSTAT NS-ATD7002-0 BY JCI


IN : 1 SUPPLY AIR TEMPERATURE SIGNAL FROM TEMPERATURE SENSOR TE-6311M-1 BY JCI 1 22 AWG 2C TWISTED PAIR 1
IN : 2 MOTORISED CONTROL VALVE POSITION 0-10 VDC/4-20mA SIGNAL TO DDC BY JCI 1 22 AWG 2C TWISTED PAIR 1
IN : 3 RETURN AIR TEMPERATURE SIGNAL FROM TEMPERATURE SENSOR TE-6311M-1 BY JCI 1 22 AWG 2C TWISTED PAIR 1
UI

IN : 4 SPARE
IN : 5 SPARE
IN : 6 SPARE
IN : 7 SUPPLY AIR MOTORISED DAMPER OPEN/CLOSE STATUS VOLT FREE CONTACT TO DDC BY JCI 1 22 AWG 2C TWISTED PAIR 1
DI
MS-FEC2611-0

IN : 8 CONDENSATE TRAY FULL BLOCK STATUS VOLT FREE CONTACT TO DDC BY MEP 1 22 AWG 2C TWISTED PAIR 1
FAN SATRT/STOP COMMAND RELAY OUTPUT BY JCI 22 AWG 2C TWISTED PAIR 1
OUT : 1 R F 1
DRAIN PUMP SATRT/STOP COMMAND RELAY OUTPUT BY JCI 22 AWG 2C TWISTED PAIR 1
DO

OUT : 2 RETURN AIR MOTORISED DAMPER OPEN/CLOSE COMMAND RELAY OUTPUT BY JCI R F 1 22 AWG 2C TWISTED PAIR 1
OUT : 3 SUPPLY AIR MOTORISED DAMPER OPEN/CLOSE COMMAND RELAY OUTPUT BY JCI R F 1 22 AWG 2C TWISTED PAIR 1
OUT: 4 FAN SPEED CONTROL 0-10VDC OUTPUT FROM DDC TO VFD BY JCI 1 22 AWG 2C TWISTED PAIR 1
OUT : 5 SPARE
UO

OUT : 6 SPARE
OUT : 7 SPARE
OUT : 8 MOTORISED CONTROL VALVE OUTPUT 0-10VDC OUTPUT FROM DDC TO VALVE ACTUATOR VG1000 BY JCI 1 22 AWG 2C TWISTED PAIR 2
AO

OUT:9 SPARE
MS-IOM-1711-

IN : 1 FILTER ALARM VOLT FREE CONTACT TO DDC FROM DPS P233A BY JCI 1 22 AWG 2C TWISTED PAIR 1
IN : 2 RETURN AIR MOTORISED DAMPER OPEN/CLOSE STATUS VOLT FREE CONTACT TO DDC BY JCI 1 22 AWG 2C TWISTED PAIR 1
DI

IN : 3 FAN AIR FLOW STATUS VOLT FREE CONTACT TO DDC FROM DPS P233A BY JCI 1 22 AWG 2C TWISTED PAIR 1
IN : 4 SPARE
DESCRIPTION UI BI BO UO AO
TOTAL POINTS USED 3 5 3 1 1
TOTAL POINTS SPARE 3 1 0 3 1
TOTAL CAPACITY 6 6 3 4 2
SPARE CAPACITY IN % 50 17 0 75 50

Page 2/16

Rev-0 Johnson Controls, Inc.


PROJECT: MSHIEREB DOWNTOWN DOHA PHASE II BUILDING MANAGEMENT SYSTEM - IO POINT LIST

PANEL REF. : FCU TYPE-3


FCU WITH HEATER WITH WINDOW REED SWITCHES AND HEATER (TYPE 3)-SERVING TO
LOCATION : OFFICE AREAS (TYPICALL FOR FCU-01 TO FCU-06 & FCU-20 IN U01, U06, P08, P11 MS-FEC-2611-0, MS-IOM1711-0 BMS Field Device Remarks Relays Fuses USED CABLE TYPE CABLE QTY
BUILDINGS)
CON
TOL

TYPEPoint Point Description Device Description UI BI BO UO AO


AT

SA BUS SPACE TEMPERATURE


ST

SA BUS NETSTAT NS-APR7102-0 BY JCI


IN : 1 SUPPLY AIR TEMPERATURE SIGNAL FROM TEMPERATURE SENSOR TE-6311M-1 BY JCI 1 22 AWG 2C TWISTED PAIR 1
IN : 2 MOTORISED CONTROL VALVE POSITION 0-10 VDC/4-20mA SIGNAL TO DDC BY JCI 1 22 AWG 2C TWISTED PAIR 1
IN : 3 RETURN AIR TEMPERATURE SIGNAL FROM TEMPERATURE SENSOR TE-6311M-1 BY JCI 1 22 AWG 2C TWISTED PAIR 1
UI

IN : 4 SPARE
IN : 5 SPARE
IN : 6 SPARE
IN : 7 CONDENSATE TRAY FULL BLOCK STATUS VOLT FREE CONTACT TO DDC BY MEP 1 22 AWG 2C TWISTED PAIR 1
DI
MS-FEC2611-0

IN : 8 WINDOW REED SWITCH STATUS VOLT FREE CONTACT TO DDC BY JCI 1 22 AWG 2C TWISTED PAIR 1
FAN SATRT/STOP COMMAND RELAY OUTPUT BY JCI 22 AWG 2C TWISTED PAIR 1
OUT : 1 R F 1
DRAIN PUMP SATRT/STOP COMMAND RELAY OUTPUT BY JCI 22 AWG 2C TWISTED PAIR 1
DO

OUT : 2 ELECTRIC HEATER ENABLE RELAY OUTPUT BY JCI R F 1 22 AWG 2C TWISTED PAIR 1
OUT : 3 SPARE
OUT: 4 FAN SPEED CONTROL 0-10VDC OUTPUT FROM DDC TO VFD BY JCI 1 22 AWG 2C TWISTED PAIR 1
OUT : 5 SPARE
UO

OUT : 6 SPARE
OUT : 7 SPARE
OUT : 8 MOTORISED CONTROL VALVE OUTPUT 0-10VDC OUTPUT FROM DDC TO VALVE ACTUATOR VG1000 BY JCI 1 22 AWG 2C TWISTED PAIR 2
AO

OUT:9 SPARE
MS-IOM-1711-

IN : 1 FAN AIR FLOW STATUS VOLT FREE CONTACT TO DDC FROM DPS P233A BY JCI 1 22 AWG 2C TWISTED PAIR 1
IN : 2 FILTER ALARM VOLT FREE CONTACT TO DDC FROM DPS P233A BY JCI 1 22 AWG 2C TWISTED PAIR 1
DI

IN : 3 ELECTRIC HEATER STATUS VOLT FREE CONTACT TO DDC BY JCI 1 22 AWG 2C TWISTED PAIR 1
IN : 4 SPARE
DESCRIPTION UI BI BO UO AO
TOTAL POINTS USED 3 5 2 1 1
TOTAL POINTS SPARE 3 1 1 3 1
TOTAL CAPACITY 6 6 3 4 2
SPARE CAPACITY IN % 50 17 33 75 50

Page 3/16

Rev-0 Johnson Controls, Inc.


PROJECT: MSHIEREB DOWNTOWN DOHA PHASE II BUILDING MANAGEMENT SYSTEM - IO POINT LIST

PANEL REF. : FCU TYPE-3A


FCU WITH HEATER WITH WINDOW REED SWITCHES AND HEATER (TYPE 3A)-SERVING TO
LOCATION : RESIDENTIAL AREAS (TYPICALL FOR FCU-01 TO FCU-06 & FCU-20 IN N04, U07 MS-FEC-2611-0, MS-IOM1711-0 BMS Field Device Remarks Relays Fuses USED CABLE TYPE CABLE QTY
BUILDINGS)
CON
TOL

TYPEPoint Point Description Device Description UI BI BO UO AO


AT

SA BUS SPACE TEMPERATURE


ST

SA BUS NETSTAT NS-APR7102-0 BY JCI


IN : 1 SUPPLY AIR TEMPERATURE SIGNAL FROM TEMPERATURE SENSOR TE-6311M-1 BY JCI 1 22 AWG 2C TWISTED PAIR 1
IN : 2 MOTORISED CONTROL VALVE POSITION 0-10 VDC/4-20mA SIGNAL TO DDC BY JCI 1 22 AWG 2C TWISTED PAIR 1
IN : 3 SPARE
UI

IN : 4 SPARE
IN : 5 SPARE
IN : 6 SPARE
IN : 7 CONDENSATE TRAY FULL BLOCK STATUS VOLT FREE CONTACT TO DDC BY MEP 1 22 AWG 2C TWISTED PAIR 1
DI
MS-FEC2611-0

IN : 8 WINDOW REED SWITCH STATUS VOLT FREE CONTACT TO DDC BY JCI 1 22 AWG 2C TWISTED PAIR 1
FAN SATRT/STOP COMMAND RELAY OUTPUT BY JCI 22 AWG 2C TWISTED PAIR 1
OUT : 1 R F 1
DRAIN PUMP SATRT/STOP COMMAND RELAY OUTPUT BY JCI 22 AWG 2C TWISTED PAIR 1
DO

OUT : 2 ELECTRIC HEATER ENABLE RELAY OUTPUT BY JCI R F 1 22 AWG 2C TWISTED PAIR 1
OUT : 3 SPARE
OUT: 4 FAN SPEED CONTROL 0-10VDC OUTPUT FROM DDC TO VFD BY JCI 1 22 AWG 2C TWISTED PAIR 1
OUT : 5 SPARE
UO

OUT : 6 SPARE
OUT : 7 SPARE
OUT : 8 MOTORISED CONTROL VALVE OUTPUT 0-10VDC OUTPUT FROM DDC TO VALVE ACTUATOR VG1000 BY JCI 1 22 AWG 2C TWISTED PAIR 2
AO

OUT:9 SPARE
MS-IOM-1711-

IN : 1 FAN AIR FLOW STATUS VOLT FREE CONTACT TO DDC FROM DPS P233A BY JCI 1 22 AWG 2C TWISTED PAIR 1
IN : 2 FILTER ALARM VOLT FREE CONTACT TO DDC FROM DPS P233A BY JCI 1 22 AWG 2C TWISTED PAIR 1
DI

IN : 3 ELECTRIC HEATER STATUS VOLT FREE CONTACT TO DDC BY JCI 1 22 AWG 2C TWISTED PAIR 1
IN : 4 SPARE
DESCRIPTION UI BI BO UO AO
TOTAL POINTS USED 2 5 2 1 1
TOTAL POINTS SPARE 4 1 1 3 1
TOTAL CAPACITY 6 6 3 4 2
SPARE CAPACITY IN % 67 17 33 75 50

Page 4/16

Rev-0 Johnson Controls, Inc.


PROJECT: MSHIEREB DOWNTOWN DOHA PHASE II BUILDING MANAGEMENT SYSTEM - IO POINT LIST

PANEL REF. : FCU TYPE-4


FCU COOLING ONLY WITH WINDOW REED SWITCHES (TYPE 4)-SERVING TO OFFICE
LOCATION : AREAS (TYPICALL FOR FCU-07 TO FCU-19 AND FCU-21 IN U01, U06, P08, P11 MS-FEC-2611-0, MS-IOM1711-0 BMS Field Device Remarks Relays Fuses USED CABLE TYPE CABLE QTY
BUILDINGS)
CON
TOL

TYPEPoint Point Description Device Description UI BI BO UO AO


AT

SA BUS SPACE TEMPERATURE


ST

SA BUS NETSTAT NS-APR7102-0 BY JCI


IN : 1 SUPPLY AIR TEMPERATURE SIGNAL FROM TEMPERATURE SENSOR TE-6311M-1 BY JCI 1 22 AWG 2C TWISTED PAIR 1
IN : 2 RETURN AIR TEMPERATURE SIGNAL FROM TEMPERATURE SENSOR TE-6311M-1 BY JCI 1 22 AWG 2C TWISTED PAIR 1
IN : 3 MOTORISED CONTROL VALVE POSITION 0-10 VDC/4-20mA SIGNAL TO DDC BY JCI 1 22 AWG 2C TWISTED PAIR 1
UI

IN : 4 SPARE
IN : 5 SPARE
IN : 6 SPARE
IN : 7 CONDENSATE TRAY FULL BLOCK STATUS VOLT FREE CONTACT TO DDC BY MEP 1 22 AWG 2C TWISTED PAIR 1
DI
MS-FEC2611-0

IN : 8 WINDOW REED SWITCH STATUS VOLT FREE CONTACT TO DDC BY JCI 1 22 AWG 2C TWISTED PAIR 1
FAN SATRT/STOP COMMAND RELAY OUTPUT BY JCI 22 AWG 2C TWISTED PAIR 1
OUT : 1 R F 1
DRAIN PUMP SATRT/STOP COMMAND RELAY OUTPUT BY JCI 22 AWG 2C TWISTED PAIR 1
DO

OUT : 2 SPARE
OUT : 3 SPARE
OUT: 4 FAN SPEED CONTROL 0-10VDC OUTPUT FROM DDC TO VFD BY JCI 1 22 AWG 2C TWISTED PAIR 1
OUT : 5 SPARE
UO

OUT : 6 SPARE
OUT : 7 SPARE
OUT : 8 MOTORISED CONTROL VALVE OUTPUT 0-10VDC OUTPUT FROM DDC TO VALVE ACTUATOR VG1000 BY JCI 1 22 AWG 2C TWISTED PAIR 2
AO

OUT:9 SPARE
MS-IOM-1711-

IN : 1 FAN AIR FLOW STATUS VOLT FREE CONTACT TO DDC FROM DPS P233A BY JCI 1 22 AWG 2C TWISTED PAIR 1
IN : 2 FILTER ALARM VOLT FREE CONTACT TO DDC FROM DPS P233A BY JCI 1 22 AWG 2C TWISTED PAIR 1
DI

IN : 3 SPARE
IN : 4 SPARE
DESCRIPTION UI BI BO UO AO
TOTAL POINTS USED 3 4 1 1 1
TOTAL POINTS SPARE 3 2 2 3 1
TOTAL CAPACITY 6 6 3 4 2
SPARE CAPACITY IN % 50 33 67 75 50

Page 5/16

Rev-0 Johnson Controls, Inc.


PROJECT: MSHIEREB DOWNTOWN DOHA PHASE II BUILDING MANAGEMENT SYSTEM - IO POINT LIST

PANEL REF. : FCU TYPE-4A


FCU COOLING ONLY WITH WINDOW REED SWITCHES (TYPE 4A)-SERVING TO
LOCATION : RESIDENTIAL AREAS (TYPICALL FOR FCU-07 TO FCU-19 AND FCU-21 IN N04 AND U07 MS-FEC-2611-0, MS-IOM1711-0 BMS Field Device Remarks Relays Fuses USED CABLE TYPE CABLE QTY
BUILDINGS)
CON
TOL

TYPEPoint Point Description Device Description UI BI BO UO AO


AT

SA BUS SPACE TEMPERATURE


ST

SA BUS NETSTAT NS-APR7102-0 BY JCI


IN : 1 SUPPLY AIR TEMPERATURE SIGNAL FROM TEMPERATURE SENSOR TE-6311M-1 BY JCI 1 22 AWG 2C TWISTED PAIR 1
IN : 2 MOTORISED CONTROL VALVE POSITION 0-10 VDC/4-20mA SIGNAL TO DDC BY JCI 1 22 AWG 2C TWISTED PAIR 1
IN : 3 SPARE
UI

IN : 4 SPARE
IN : 5 SPARE
IN : 6 SPARE
IN : 7 CONDENSATE TRAY FULL BLOCK STATUS VOLT FREE CONTACT TO DDC BY MEP 1 22 AWG 2C TWISTED PAIR 1
DI
MS-FEC2611-0

IN : 8 WINDOW REED SWITCH STATUS VOLT FREE CONTACT TO DDC BY JCI 1 22 AWG 2C TWISTED PAIR 1
FAN SATRT/STOP COMMAND RELAY OUTPUT BY JCI 22 AWG 2C TWISTED PAIR 1
OUT : 1 R F 1
DRAIN PUMP SATRT/STOP COMMAND RELAY OUTPUT BY JCI 22 AWG 2C TWISTED PAIR 1
DO

OUT : 2 SPARE
OUT : 3 SPARE
OUT: 4 FAN SPEED CONTROL 0-10VDC OUTPUT FROM DDC TO VFD BY JCI 1 22 AWG 2C TWISTED PAIR 1
OUT : 5 SPARE
UO

OUT : 6 SPARE
OUT : 7 SPARE
OUT : 8 MOTORISED CONTROL VALVE OUTPUT 0-10VDC OUTPUT FROM DDC TO VALVE ACTUATOR VG1000 BY JCI 1 22 AWG 2C TWISTED PAIR 2
AO

OUT:9 SPARE
MS-IOM-1711-

IN : 1 FAN AIR FLOW STATUS VOLT FREE CONTACT TO DDC FROM DPS P233A BY JCI 1 22 AWG 2C TWISTED PAIR 1
IN : 2 FILTER ALARM VOLT FREE CONTACT TO DDC FROM DPS P233A BY JCI 1 22 AWG 2C TWISTED PAIR 1
DI

IN : 3 SPARE
IN : 4 SPARE
DESCRIPTION UI BI BO UO AO
TOTAL POINTS USED 2 4 1 1 1
TOTAL POINTS SPARE 4 2 2 3 1
TOTAL CAPACITY 6 6 3 4 2
SPARE CAPACITY IN % 67 33 67 75 50

Page 6/16

Rev-0 Johnson Controls, Inc.


PROJECT: MSHIEREB DOWNTOWN DOHA PHASE II BUILDING MANAGEMENT SYSTEM - IO POINT LIST

PANEL REF. : FCU TYPE-1


FCU COOLING ONLY (W/O HEATER ) (TYPE 1) - SERVING TO HOTEL AND RETAIL AREAS
LOCATION : MS-FEC-2611-0 BMS Field Device Remarks Relays Fuses USED CABLE TYPE CABLE QTY
(TYPICAL FOR FCU-07 TO FCU-19 AND FCU-21)
CON
TOL

TYPEPoint Point Description Device Description UI BI BO UO AO


AT

SA BUS SPACE TEMPERATURE


ST

SA BUS NETSTAT NS-APR7102-0 BY JCI


IN : 1 SUPPLY AIR TEMPERATURE SIGNAL FROM TEMPERATURE SENSOR TE-6311M-1 BY JCI 1 22 AWG 2C TWISTED PAIR 1
IN : 2 FILTER ALARM VOLT FREE CONTACT TO DDC FROM DPS P233A BY JCI 1 22 AWG 2C TWISTED PAIR 1
IN : 3 MOTORISED CONTROL VALVE POSITION 0-10 VDC/4-20mA SIGNAL TO DDC BY JCI 1 22 AWG 2C TWISTED PAIR 1
UI

IN : 4 SPARE
IN : 5 SPARE
IN : 6 SPARE
IN : 7 CONDENSATE TRAY FULL BLOCK STATUS VOLT FREE CONTACT TO DDC BY MEP 1 22 AWG 2C TWISTED PAIR 1
DI
MS-FEC2611-0

IN : 8 FAN AIR FLOW STATUS VOLT FREE CONTACT TO DDC FROM DPS P233A BY JCI 1 22 AWG 2C TWISTED PAIR 1
FAN SATRT/STOP COMMAND RELAY OUTPUT BY JCI 22 AWG 2C TWISTED PAIR 1
OUT : 1 R F 1
DRAIN PUMP SATRT/STOP COMMAND RELAY OUTPUT BY JCI 22 AWG 2C TWISTED PAIR 1
DO

OUT : 2 SPARE
OUT : 3 SPARE
OUT: 4 FAN SPEED CONTROL 0-10VDC OUTPUT FROM DDC TO VFD BY JCI 1 22 AWG 2C TWISTED PAIR 1
OUT : 5 SPARE
UO

OUT : 6 SPARE
OUT : 7 SPARE
OUT : 8 MOTORISED CONTROL VALVE OUTPUT 0-10VDC OUTPUT FROM DDC TO VALVE ACTUATOR VG1000 BY JCI 1 22 AWG 2C TWISTED PAIR 2
AO

OUT:9 SPARE
DESCRIPTION UI BI BO UO AO
TOTAL POINTS USED 3 2 1 1 1
TOTAL POINTS SPARE 2 0 2 3 1
TOTAL CAPACITY 5 2 3 4 2
SPARE CAPACITY IN % 40 0 67 75 50

Page 7/16

Rev-0 Johnson Controls, Inc.


PROJECT: MSHIEREB DOWNTOWN DOHA PHASE II BUILDING MANAGEMENT SYSTEM - IO POINT LIST

PANEL REF. : FCU TYPE-2


FCU WITH HEATER (TYPE 2) - SERVING TO HOTEL AND REATIL AREAS (TYPICAL FOR
LOCATION : MS-FEC-2611-0, MS-IOM1711-0 BMS Field Device Remarks Relays Fuses USED CABLE TYPE CABLE QTY
FCU-01 TO FCU-06 AND FCU-20)
CON
TOL

TYPEPoint Point Description Device Description UI BI BO UO AO


AT

SA BUS SPACE TEMPERATURE


ST

SA BUS NETSTAT NS-APR7102-0 BY JCI


IN : 1 SUPPLY AIR TEMPERATURE SIGNAL FROM TEMPERATURE SENSOR TE-6311M-1 BY JCI 1 22 AWG 2C TWISTED PAIR 1
IN : 2 MOTORISED CONTROL VALVE POSITION 0-10 VDC/4-20mA SIGNAL TO DDC BY JCI 1 22 AWG 2C TWISTED PAIR 1
IN : 3 SPARE
UI

IN : 4 SPARE
IN : 5 SPARE
IN : 6 SPARE
IN : 7 CONDENSATE TRAY FULL BLOCK STATUS VOLT FREE CONTACT TO DDC BY MEP 1 22 AWG 2C TWISTED PAIR 1
DI
MS-FEC2611-0

IN : 8 ELECTRIC HEATER STATUS VOLT FREE CONTACT TO DDC BY JCI 1


FAN SATRT/STOP COMMAND RELAY OUTPUT BY JCI 22 AWG 2C TWISTED PAIR 1
OUT : 1 R F 1
DRAIN PUMP SATRT/STOP COMMAND RELAY OUTPUT BY JCI 22 AWG 2C TWISTED PAIR 1
DO

OUT : 2 ELECTRIC HEATER ENABLE RELAY OUTPUT BY JCI R F 1 22 AWG 2C TWISTED PAIR 1
OUT : 3 SPARE
OUT: 4 FAN SPEED CONTROL 0-10VDC OUTPUT FROM DDC TO VFD BY JCI 1 22 AWG 2C TWISTED PAIR 1
OUT : 5 SPARE
UO

OUT : 6 SPARE
OUT : 7 SPARE
OUT : 8 MOTORISED CONTROL VALVE OUTPUT 0-10VDC OUTPUT FROM DDC TO VALVE ACTUATOR VG1000 BY JCI 1 22 AWG 2C TWISTED PAIR 2
AO

OUT:9 SPARE
MS-IOM-1711-

IN : 1 FAN AIR FLOW STATUS VOLT FREE CONTACT TO DDC FROM DPS P233A BY JCI 1 22 AWG 2C TWISTED PAIR 1
IN : 2 FILTER ALARM VOLT FREE CONTACT TO DDC FROM DPS P233A BY JCI 1 22 AWG 2C TWISTED PAIR 1
DI

IN : 3 SPARE
IN : 4 SPARE
DESCRIPTION UI BI BO UO AO
TOTAL POINTS USED 2 4 2 1 1
TOTAL POINTS SPARE 4 2 1 3 1
TOTAL CAPACITY 6 6 3 4 2
SPARE CAPACITY IN % 67 33 33 75 50

Page 8/16

Rev-0 Johnson Controls, Inc.


PROJECT: MSHIEREB DOWNTOWN DOHA PHASE II BUILDING MANAGEMENT SYSTEM - IO POINT LIST

PANEL REF. : PLANTROOM FCU TYPE-1


BASEMENT PLANTROOM FCU WITH 1 DUTY/1 STANDBY CONFIGURATION AND
LOCATION : MS-FEC-2611-0, MS-IOM1711-0 BMS Field Device Remarks Relays Fuses USED CABLE TYPE CABLE QTY
MOTORISED DAMPERS
CON
TOL

TYPEPoint Point Description Device Description UI BI BO UO AO


AT

SA BUS SPACE TEMPERATURE


ST

SA BUS NETSTAT NS-APR7102-0 BY JCI


IN : 1 SUPPLY AIR TEMPERATURE SIGNAL FROM TEMPERATURE SENSOR TE-6311M-1 BY JCI 1 22 AWG 2C TWISTED PAIR 1
IN : 2 MOTORISED CONTROL VALVE POSITION 0-10 VDC/4-20mA SIGNAL TO DDC BY JCI 1 22 AWG 2C TWISTED PAIR 1
IN : 3 SPARE
UI

IN : 4 SPARE
IN : 5 SPARE
IN : 6 SPARE
IN : 7 SUPPLY AIR MOTORISED DAMPER OPEN/CLOSE STATUS VOLT FREE CONTACT TO DDC BY JCI 1 22 AWG 2C TWISTED PAIR 1
DI
MS-FEC2611-0

IN : 8 CONDENSATE TRAY FULL BLOCK STATUS VOLT FREE CONTACT TO DDC BY MEP 1 22 AWG 2C TWISTED PAIR 1
FAN SATRT/STOP COMMAND RELAY OUTPUT BY JCI 22 AWG 2C TWISTED PAIR 1
OUT : 1 R F 1
DRAIN PUMP SATRT/STOP COMMAND RELAY OUTPUT BY JCI 22 AWG 2C TWISTED PAIR 1
DO

OUT : 2 SUPPLY AIR MOTORISED DAMPER OPEN/CLOSE COMMAND RELAY OUTPUT BY JCI R F 1 22 AWG 2C TWISTED PAIR 1
OUT : 3 SPARE
OUT: 4 FAN SPEED CONTROL 0-10VDC OUTPUT FROM DDC TO VFD BY JCI 1 22 AWG 2C TWISTED PAIR 1
OUT : 5 SPARE
UO

OUT : 6 SPARE
OUT : 7 SPARE
OUT : 8 MOTORISED CONTROL VALVE OUTPUT 0-10VDC OUTPUT FROM DDC TO VALVE ACTUATOR VG1000 BY JCI 1 22 AWG 2C TWISTED PAIR 2
AO

OUT:9 SPARE
MS-IOM-1711-

IN : 1 FILTER ALARM VOLT FREE CONTACT TO DDC FROM DPS P233A BY JCI 1 22 AWG 2C TWISTED PAIR 1
IN : 2 FAN AIR FLOW STATUS VOLT FREE CONTACT TO DDC FROM DPS P233A BY JCI 1 22 AWG 2C TWISTED PAIR 1
DI

IN : 3 SPARE
IN : 4 SPARE
DESCRIPTION UI BI BO UO AO
TOTAL POINTS USED 2 4 2 1 1
TOTAL POINTS SPARE 4 2 1 3 1
TOTAL CAPACITY 6 6 3 4 2
SPARE CAPACITY IN % 67 33 33 75 50

Page 9/16

Rev-0 Johnson Controls, Inc.


PROJECT: MSHIEREB DOWNTOWN DOHA PHASE II BUILDING MANAGEMENT SYSTEM - IO POINT LIST

PANEL REF. : PLANTROOM FCU TYPE-1


BASEMENT PLANTROOM FCU WITH 2 DUTY/1 STANDBY CONFIGURATION AND
LOCATION : MS-FEC-2611-0, MS-IOM1711-0 BMS Field Device Remarks Relays Fuses USED CABLE TYPE CABLE QTY
MOTORISED DAMPERS
CON
TOL

TYPEPoint Point Description Device Description UI BI BO UO AO


AT

SA BUS SPACE TEMPERATURE


ST

SA BUS NETSTAT NS-APR7102-0 BY JCI


IN : 1 SUPPLY AIR TEMPERATURE SIGNAL FROM TEMPERATURE SENSOR TE-6311M-1 BY JCI 1 22 AWG 2C TWISTED PAIR 1
IN : 2 MOTORISED CONTROL VALVE POSITION 0-10 VDC/4-20mA SIGNAL TO DDC BY JCI 1 22 AWG 2C TWISTED PAIR 1
IN : 3 SPARE
UI

IN : 4 SPARE
IN : 5 SPARE
IN : 6 SPARE
IN : 7 SUPPLY AIR MOTORISED DAMPER OPEN/CLOSE STATUS VOLT FREE CONTACT TO DDC BY JCI 1 22 AWG 2C TWISTED PAIR 1
DI
MS-FEC2611-0

IN : 8 CONDENSATE TRAY FULL BLOCK STATUS VOLT FREE CONTACT TO DDC BY MEP 1 22 AWG 2C TWISTED PAIR 1
FAN SATRT/STOP COMMAND RELAY OUTPUT BY JCI 22 AWG 2C TWISTED PAIR 1
OUT : 1 R F 1
DRAIN PUMP SATRT/STOP COMMAND RELAY OUTPUT BY JCI 22 AWG 2C TWISTED PAIR 1
DO

OUT : 2 SUPPLY AIR MOTORISED DAMPER OPEN/CLOSE COMMAND RELAY OUTPUT BY JCI R F 1 22 AWG 2C TWISTED PAIR 1
OUT : 3 SPARE
OUT: 4 FAN SPEED CONTROL 0-10VDC OUTPUT FROM DDC TO VFD BY JCI 1 22 AWG 2C TWISTED PAIR 1
OUT : 5 SPARE
UO

OUT : 6 SPARE
OUT : 7 SPARE
OUT : 8 MOTORISED CONTROL VALVE OUTPUT 0-10VDC OUTPUT FROM DDC TO VALVE ACTUATOR VG1000 BY JCI 1 22 AWG 2C TWISTED PAIR 2
AO

OUT:9 SPARE
MS-IOM-1711-

IN : 1 FILTER ALARM VOLT FREE CONTACT TO DDC FROM DPS P233A BY JCI 1 22 AWG 2C TWISTED PAIR 1
IN : 2 FAN AIR FLOW STATUS VOLT FREE CONTACT TO DDC FROM DPS P233A BY JCI 1 22 AWG 2C TWISTED PAIR 1
DI

IN : 3 SPARE
IN : 4 SPARE
DESCRIPTION UI BI BO UO AO
TOTAL POINTS USED 2 4 2 1 1
TOTAL POINTS SPARE 4 2 1 3 1
TOTAL CAPACITY 6 6 3 4 2
SPARE CAPACITY IN % 67 33 33 75 50

Page 10/16

Rev-0 Johnson Controls, Inc.


PROJECT: MSHIEREB DOWNTOWN DOHA PHASE II BUILDING MANAGEMENT SYSTEM - IO POINT LIST

PANEL REF. : PLANTROOM FCU TYPE-2

LOCATION : BASEMENT PLANTROOM FCU WITH 1 DUTY/1 STANDBY CONFIGURATION MS-FEC-2611-0 BMS Field Device Remarks Relays Fuses USED CABLE TYPE CABLE QTY
CON
TOL

TYPEPoint Point Description Device Description UI BI BO UO AO


AT

SA BUS SPACE TEMPERATURE


ST

SA BUS NETSTAT NS-APR7102-0 BY JCI


IN : 1 SUPPLY AIR TEMPERATURE SIGNAL FROM TEMPERATURE SENSOR TE-6311M-1 BY JCI 1 22 AWG 2C TWISTED PAIR 1
IN : 2 MOTORISED CONTROL VALVE POSITION 0-10 VDC/4-20mA SIGNAL TO DDC BY JCI 1 22 AWG 2C TWISTED PAIR 1
IN : 3 FILTER ALARM VOLT FREE CONTACT TO DDC FROM DPS P233A BY JCI 1 22 AWG 2C TWISTED PAIR 1
UI

IN : 4 SPARE
IN : 5 SPARE
IN : 6 SPARE
IN : 7 FAN AIR FLOW STATUS VOLT FREE CONTACT TO DDC FROM DPS P233A BY JCI 1 22 AWG 2C TWISTED PAIR 1
DI
MS-FEC2611-0

IN : 8 CONDENSATE TRAY FULL BLOCK STATUS VOLT FREE CONTACT TO DDC BY MEP 1 22 AWG 2C TWISTED PAIR 1
FAN SATRT/STOP COMMAND RELAY OUTPUT BY JCI 22 AWG 2C TWISTED PAIR 1
OUT : 1 R F 1
DRAIN PUMP SATRT/STOP COMMAND RELAY OUTPUT BY JCI 22 AWG 2C TWISTED PAIR 1
DO

OUT : 2 SPARE
OUT : 3 SPARE
OUT: 4 FAN SPEED CONTROL 0-10VDC OUTPUT FROM DDC TO VFD BY JCI 1 22 AWG 2C TWISTED PAIR 1
OUT : 5 SPARE
UO

OUT : 6 SPARE
OUT : 7 SPARE
OUT : 8 MOTORISED CONTROL VALVE OUTPUT 0-10VDC OUTPUT FROM DDC TO VALVE ACTUATOR VG1000 BY JCI 1 22 AWG 2C TWISTED PAIR 2
AO

OUT:9 SPARE
DESCRIPTION UI BI BO UO AO
TOTAL POINTS USED 3 2 1 1 1
TOTAL POINTS SPARE 3 0 2 3 1
TOTAL CAPACITY 6 2 3 4 2
SPARE CAPACITY IN % 50 0 67 75 50

Page 11/16

Rev-0 Johnson Controls, Inc.


PROJECT: MSHIEREB DOWNTOWN DOHA PHASE II BUILDING MANAGEMENT SYSTEM - IO POINT LIST

PANEL REF. : PLANTROOM FCU TYPE-2

LOCATION : BASEMENT PLANTROOM FCU WITH 2 DUTY/1 STANDBY CONFIGURATION MS-FEC-2611-0 BMS Field Device Remarks Relays Fuses USED CABLE TYPE CABLE QTY
CON
TOL

TYPEPoint Point Description Device Description UI BI BO UO AO


AT

SA BUS SPACE TEMPERATURE


ST

SA BUS NETSTAT NS-APR7102-0 BY JCI


IN : 1 SUPPLY AIR TEMPERATURE SIGNAL FROM TEMPERATURE SENSOR TE-6311M-1 BY JCI 1 22 AWG 2C TWISTED PAIR 1
IN : 2 MOTORISED CONTROL VALVE POSITION 0-10 VDC/4-20mA SIGNAL TO DDC BY JCI 1 22 AWG 2C TWISTED PAIR 1
IN : 3 FILTER ALARM VOLT FREE CONTACT TO DDC FROM DPS P233A BY JCI 1 22 AWG 2C TWISTED PAIR 1
UI

IN : 4 SPARE
IN : 5 SPARE
IN : 6 SPARE
IN : 7 FAN AIR FLOW STATUS VOLT FREE CONTACT TO DDC FROM DPS P233A BY JCI 1 22 AWG 2C TWISTED PAIR 1
DI
MS-FEC2611-0

IN : 8 CONDENSATE TRAY FULL BLOCK STATUS VOLT FREE CONTACT TO DDC BY MEP 1 22 AWG 2C TWISTED PAIR 1
FAN SATRT/STOP COMMAND RELAY OUTPUT BY JCI 22 AWG 2C TWISTED PAIR 1
OUT : 1 R F 1
DRAIN PUMP SATRT/STOP COMMAND RELAY OUTPUT BY JCI 22 AWG 2C TWISTED PAIR 1
DO

OUT : 2 SPARE
OUT : 3 SPARE
OUT: 4 FAN SPEED CONTROL 0-10VDC OUTPUT FROM DDC TO VFD BY JCI 1 22 AWG 2C TWISTED PAIR 1
OUT : 5 SPARE
UO

OUT : 6 SPARE
OUT : 7 SPARE
OUT : 8 MOTORISED CONTROL VALVE OUTPUT 0-10VDC OUTPUT FROM DDC TO VALVE ACTUATOR VG1000 BY JCI 1 22 AWG 2C TWISTED PAIR 2
AO

OUT:9 SPARE
DESCRIPTION UI BI BO UO AO
TOTAL POINTS USED 3 2 1 1 1
TOTAL POINTS SPARE 3 0 2 3 1
TOTAL CAPACITY 6 2 3 4 2
SPARE CAPACITY IN % 50 0 67 75 50

Page 12/16

Rev-0 Johnson Controls, Inc.


PROJECT: MSHIEREB DOWNTOWN DOHA PHASE II BUILDING MANAGEMENT SYSTEM - IO POINT LIST

PANEL REF. : PLANTROOM FCU TYPE-2


BASEMENT PLANTROOM FCU WITH 1 DUTY/1 STANDBY CONFIGURATION WITH SUPPLY
LOCATION : MS-FEC-2611-0 BMS Field Device Remarks Relays Fuses USED CABLE TYPE CABLE QTY
AND RETURN AIR PLENUM
CON
TOL

TYPEPoint Point Description Device Description UI BI BO UO AO

IN : 1 SUPPLY AIR TEMPERATURE SIGNAL FROM TEMPERATURE SENSOR TE-6311M-1 BY JCI 1 22 AWG 2C TWISTED PAIR 1
IN : 2 MOTORISED CONTROL VALVE POSITION 0-10 VDC/4-20mA SIGNAL TO DDC BY JCI 1 22 AWG 2C TWISTED PAIR 1
IN : 3 FILTER ALARM VOLT FREE CONTACT TO DDC FROM DPS P233A BY JCI 1 22 AWG 2C TWISTED PAIR 1
UI

IN : 4 RETURN AIR TEMPERATURE SIGNAL FROM TEMPERATURE SENSOR TE-6311M-1 BY JCI 1 22 AWG 2C TWISTED PAIR 1
IN : 5 SPARE
IN : 6 SPARE
IN : 7 FAN AIR FLOW STATUS VOLT FREE CONTACT TO DDC FROM DPS P233A BY JCI 1 22 AWG 2C TWISTED PAIR 1
DI
MS-FEC2611-0

IN : 8 CONDENSATE TRAY FULL BLOCK STATUS VOLT FREE CONTACT TO DDC BY MEP 1 22 AWG 2C TWISTED PAIR 1
FAN SATRT/STOP COMMAND RELAY OUTPUT BY JCI 22 AWG 2C TWISTED PAIR 1
OUT : 1 R F 1
DRAIN PUMP SATRT/STOP COMMAND RELAY OUTPUT BY JCI 22 AWG 2C TWISTED PAIR 1
DO

OUT : 2 SPARE
OUT : 3 SPARE
OUT: 4 FAN SPEED CONTROL 0-10VDC OUTPUT FROM DDC TO VFD BY JCI 1 22 AWG 2C TWISTED PAIR 1
OUT : 5 SPARE
UO

OUT : 6 SPARE
OUT : 7 SPARE
OUT : 8 MOTORISED CONTROL VALVE OUTPUT 0-10VDC OUTPUT FROM DDC TO VALVE ACTUATOR VG1000 BY JCI 1 22 AWG 2C TWISTED PAIR 2
AO

OUT:9 SPARE
DESCRIPTION UI BI BO UO AO
TOTAL POINTS USED 4 2 1 1 1
TOTAL POINTS SPARE 2 0 2 3 1
TOTAL CAPACITY 6 2 3 4 2
SPARE CAPACITY IN % 33 0 67 75 50

Page 13/16

Rev-0 Johnson Controls, Inc.


PROJECT: MSHIEREB DOWNTOWN DOHA PHASE II BUILDING MANAGEMENT SYSTEM - IO POINT LIST

PANEL REF. : PLANTROOM FCU TYPE-3


BASEMENT PLANTROOM FCU WITH 1DUTY/1STANDBY CONFIGURATION AND MOTORISED
LOCATION : MS-FEC-2611-0, MS-IOM1711-0 BMS Field Device Remarks Relays Fuses USED CABLE TYPE CABLE QTY
DAMPERS (FCU-9)
CON
TOL

TYPEPoint Point Description Device Description UI BI BO UO AO


AT

SA BUS SPACE TEMPERATURE


ST

SA BUS NETSTAT NS-ATD7002-0 BY JCI


IN : 1 SUPPLY AIR TEMPERATURE SIGNAL FROM TEMPERATURE SENSOR TE-6311M-1 BY JCI 1 22 AWG 2C TWISTED PAIR 1
IN : 2 MOTORISED CONTROL VALVE POSITION 0-10 VDC/4-20mA SIGNAL TO DDC BY JCI 1 22 AWG 2C TWISTED PAIR 1
IN : 3 RETURN AIR TEMPERATURE SIGNAL FROM TEMPERATURE SENSOR TE-6311M-1 BY JCI 1 22 AWG 2C TWISTED PAIR 1
UI

IN : 4 SPARE
IN : 5 SPARE
IN : 6 SPARE
IN : 7 SUPPLY AIR MOTORISED DAMPER OPEN/CLOSE STATUS VOLT FREE CONTACT TO DDC BY JCI 1 22 AWG 2C TWISTED PAIR 1
DI
MS-FEC2611-0

IN : 8 CONDENSATE TRAY FULL BLOCK STATUS VOLT FREE CONTACT TO DDC BY MEP 1 22 AWG 2C TWISTED PAIR 1
FAN SATRT/STOP COMMAND RELAY OUTPUT BY JCI 22 AWG 2C TWISTED PAIR 1
OUT : 1 R F 1
DRAIN PUMP SATRT/STOP COMMAND RELAY OUTPUT BY JCI 22 AWG 2C TWISTED PAIR 1
DO

OUT : 2 RETURN AIR MOTORISED DAMPER OPEN/CLOSE COMMAND RELAY OUTPUT BY JCI R F 1 22 AWG 2C TWISTED PAIR 1
OUT : 3 SUPPLY AIR MOTORISED DAMPER OPEN/CLOSE COMMAND RELAY OUTPUT BY JCI R F 1 22 AWG 2C TWISTED PAIR 1
OUT: 4 FAN SPEED CONTROL 0-10VDC OUTPUT FROM DDC TO VFD BY JCI 1 22 AWG 2C TWISTED PAIR 1
OUT : 5 SPARE
UO

OUT : 6 SPARE
OUT : 7 SPARE
OUT : 8 MOTORISED CONTROL VALVE OUTPUT 0-10VDC OUTPUT FROM DDC TO VALVE ACTUATOR VG1000 BY JCI 1 22 AWG 2C TWISTED PAIR 2
AO

OUT:9 SPARE
MS-IOM-1711-

IN : 1 FILTER ALARM VOLT FREE CONTACT TO DDC FROM DPS P233A BY JCI 1 22 AWG 2C TWISTED PAIR 1
IN : 2 RETURN AIR MOTORISED DAMPER OPEN/CLOSE STATUS VOLT FREE CONTACT TO DDC BY JCI 1 22 AWG 2C TWISTED PAIR 1
DI

IN : 3 FAN AIR FLOW STATUS VOLT FREE CONTACT TO DDC FROM DPS P233A BY JCI 1 22 AWG 2C TWISTED PAIR 1
IN : 4 SPARE
DESCRIPTION UI BI BO UO AO
TOTAL POINTS USED 3 5 3 1 1
TOTAL POINTS SPARE 3 1 0 3 1
TOTAL CAPACITY 6 6 3 4 2
SPARE CAPACITY IN % 50 17 0 75 50

Page 14/16

Rev-0 Johnson Controls, Inc.


PROJECT: MSHIEREB DOWNTOWN DOHA PHASE II BUILDING MANAGEMENT SYSTEM - IO POINT LIST

PANEL REF. : FCU TYPE-1A


FCU (WITH HEATER ) (TYPE 1A) - SERVING TO HOTEL & RETAIL AREAS IN P16 BUILDING
LOCATION : MS-FEC-2611-0 BMS Field Device Remarks Relays Fuses USED CABLE TYPE CABLE QTY
(TYPICAL FOR FCU-01 TO FCU-06)
CON
TOL

TYPEPoint Point Description Device Description UI BI BO UO AO


AT

SA BUS SPACE TEMPERATURE


ST

SA BUS NETSTAT NS-APR7102-0 BY JCI


IN : 1 SUPPLY AIR TEMPERATURE SIGNAL FROM TEMPERATURE SENSOR TE-6311M-1 BY JCI 1 22 AWG 2C TWISTED PAIR 1
IN : 2 MOTORISED CONTROL VALVE POSITION 0-10 VDC/4-20mA SIGNAL TO DDC BY JCI 1 22 AWG 2C TWISTED PAIR 1
IN : 3 FAN AIR FLOW STATUS VOLT FREE CONTACT TO DDC FROM DPS P233A BY JCI 1 22 AWG 2C TWISTED PAIR 1
UI

IN : 4 FILTER ALARM VOLT FREE CONTACT TO DDC FROM DPS P233A BY JCI 1 22 AWG 2C TWISTED PAIR 1
IN : 5 SPARE
IN : 6 SPARE
IN : 7 CONDENSATE TRAY FULL BLOCK STATUS VOLT FREE CONTACT TO DDC BY MEP 1 22 AWG 2C TWISTED PAIR 1
DI
MS-FEC2611-0

IN : 8 ELECTRIC HEATER STATUS VOLT FREE CONTACT TO DDC BY JCI 1 22 AWG 2C TWISTED PAIR 1
FAN SATRT/STOP COMMAND RELAY OUTPUT BY JCI 22 AWG 2C TWISTED PAIR 1
OUT : 1 R F 1
DRAIN PUMP SATRT/STOP COMMAND RELAY OUTPUT BY JCI 22 AWG 2C TWISTED PAIR 1
DO

OUT : 2 ELECTRIC HEATER ENABLE RELAY OUTPUT BY JCI R F 1 22 AWG 2C TWISTED PAIR 1
OUT : 3 SPARE
OUT: 4 FAN SPEED CONTROL 0-10VDC OUTPUT FROM DDC TO VFD BY JCI 1 22 AWG 2C TWISTED PAIR 1
OUT : 5 SPARE
UO

OUT : 6 SPARE
OUT : 7 SPARE
OUT : 8 MOTORISED CONTROL VALVE OUTPUT 0-10VDC OUTPUT FROM DDC TO VALVE ACTUATOR VG1000 BY JCI 1 22 AWG 2C TWISTED PAIR 2
AO

OUT:9 SPARE
DESCRIPTION UI BI BO UO AO
TOTAL POINTS USED 4 2 2 1 1
TOTAL POINTS SPARE 2 0 1 3 1
TOTAL CAPACITY 6 2 3 4 2
SPARE CAPACITY IN % 33 0 33 75 50

Page 15/16

Rev-0 Johnson Controls, Inc.


PROJECT: MSHIEREB DOWNTOWN DOHA PHASE II BUILDING MANAGEMENT SYSTEM - IO POINT LIST

PANEL REF. : FCU TYPE-2A

LOCATION : FCU COOLING (TYPE 2A) - SERVING TO BASEMENTS (TYPICAL FOR FCU-01 TO FCU-06) MS-FEC-2611-0, MS-IOM1711-0 BMS Field Device Remarks Relays Fuses USED CABLE TYPE CABLE QTY
CON
TOL

TYPEPoint Point Description Device Description UI BI BO UO AO


AT

SA BUS SPACE TEMPERATURE


ST

SA BUS NETSTAT NS-APR7102-0 BY JCI


IN : 1 SUPPLY AIR TEMPERATURE SIGNAL FROM TEMPERATURE SENSOR TE-6311M-1 BY JCI 1 22 AWG 2C TWISTED PAIR 1
IN : 2 MOTORISED CONTROL VALVE POSITION 0-10 VDC/4-20mA SIGNAL TO DDC BY JCI 1 22 AWG 2C TWISTED PAIR 1
IN : 3 SPARE
UI

IN : 4 SPARE
IN : 5 SPARE
IN : 6 SPARE
IN : 7 CONDENSATE TRAY FULL BLOCK STATUS VOLT FREE CONTACT TO DDC BY MEP 1 22 AWG 2C TWISTED PAIR 1
DI
MS-FEC2611-0

IN : 8 SPARE
FAN SATRT/STOP COMMAND RELAY OUTPUT BY JCI 22 AWG 2C TWISTED PAIR 1
OUT : 1 R F 1
DRAIN PUMP SATRT/STOP COMMAND RELAY OUTPUT BY JCI 22 AWG 2C TWISTED PAIR 1
DO

OUT : 2 SPARE
OUT : 3 SPARE
OUT: 4 FAN SPEED CONTROL 0-10VDC OUTPUT FROM DDC TO VFD BY JCI 1 22 AWG 2C TWISTED PAIR 1
OUT : 5 SPARE
UO

OUT : 6 SPARE
OUT : 7 SPARE
OUT : 8 MOTORISED CONTROL VALVE OUTPUT 0-10VDC OUTPUT FROM DDC TO VALVE ACTUATOR VG1000 BY JCI 1 22 AWG 2C TWISTED PAIR 2
AO

OUT:9 SPARE
MS-IOM-1711-

IN : 1 FAN AIR FLOW STATUS VOLT FREE CONTACT TO DDC FROM DPS P233A BY JCI 1 22 AWG 2C TWISTED PAIR 1
IN : 2 FILTER ALARM VOLT FREE CONTACT TO DDC FROM DPS P233A BY JCI 1 22 AWG 2C TWISTED PAIR 1
DI

IN : 3 SPARE
IN : 4 SPARE
DESCRIPTION UI BI BO UO AO
TOTAL POINTS USED 2 3 1 1 1
TOTAL POINTS SPARE 4 3 2 3 1
TOTAL CAPACITY 6 6 3 4 2
SPARE CAPACITY IN % 67 50 67 75 50

Page 16/16

Rev-0 Johnson Controls, Inc.