Technical Data Sheet for Dry Type Transformer

Description Proposed General Data Proposed


1) Manufacturer Intact Controls 1) Type Dry Type
2) Power 75KVA 2) Standard, Codes IEC-60076
3) Model Number IT3-75KE 3) Supply / Technical Specification

Enviromental Conditions General Characteristics


1) Place of Installation( Indoor/Outdoor/Under Shelter) Outdoor 1) Rated Power 75KVA
2) Altitude <1000m above Sea Level 2) Rated Primary Voltage 480V AC,Delta
3) Max. Ambient Temperature 50 Deg.C 3) Secondary Voltage at No Load 404VAC
4) Relative Humidity 91% 4) Rated Sec. Voltage at rated power at 0.8PF (Ph -Ph) 400V AC,Star+N
5) Special Conditions Presence of high salt content 5) Secondary Voltage At rated power at 0.8PF (Ph - N) 230V AC
& Vessal vibration/ Inclination 6) Rated Frequency 60Hz
6) Tropicalisation Yes 7) Number of Phase 3
7) Max. Temp. Rise 115 Deg.C 8) Vector Group Dyn11
8) Duty (Continuous/Intermittent ) Continuous 9) Rated Primary Current 90.21A(480V)
9) Degree of Protection NEMA-4X 10) Rated Secondary Current 108.25A(400V)
10) Climatic Environmental Class C2/E2 11)Winding Conductor Copper
Enclosure Type Type of Transformer
1) Type of Mounted ( Panel/Floor/Wall) Floor 1) Impregnated type Yes
2) Enclosure Colour RAL-7032(Powder Coated) 2) Cast resin ( Encapsulated ) type NA
3) Body of Enclosure Stainless Steel Grade:SS-304 3) Type of cooling ( ONAN, ONAF, AN, FN ) AN
4) Lifting Lugs Yes 4) Termination Busbars/Bolts
5) Hinged Door NA

Mode of Operation
1) Individual Yes
1U 1V 1W
2) Parallel Yes
11 1u

Primary Winding Primary


2u
1) Highest Voltage 1.1KV 2v

2) Primary Insulation Level 3KV 2w


1w 1v 2U 2V 2W 2N

Dyn11
Secondary

Secondary Winding
1) Highest Voltage 1.1KV Single Line Diagram - Dyn11
2) Secondary Insulation Level 3KV
3) Neutral Brought Out Yes

Insulation Systems
1) Class of Insulation F
2) Primary Winding Class F Insulation
3) Secondary Winding Class F Insulation
4) Uniform Insulation NA H
5) Oil Immersed Transformer NA
6) Oil Type NA

Electrical & Mechanical Characteristics


1) No Load Current 2.5% In
2) No Load Loss 556W
3) Load Loss at 75 Deg.C 1183W
4) Load Loss at 120 Deg.C 1355W
5) Impedance 4.0% W
6) Efficiency with power factor 1 @100% of Load 97.73%
D
7) Efficiency with power factor 1 @75% of Load 97.87%
8) Efficiency with power factor 0.8 @100% of Load 97.18%
9) Efficiency with power factor 0.8 @75% of Load 97.36% The Images,dimensions & weight shown herein indicative only & may subject to vary
depending upon material availability and design development.
Dimension & Weight

Width ( W ) Height ( H ) Depth ( D ) Weight Wheel Axle Base Bolt Size

810mm 960mm 650mm 323Kg.(Approx) NA NA