You are on page 1of 2

Earth Pits Testing

Area: STG Building Date: August 5,2020

Results after cleaning/water


Results
Sr.No. Earthing Pit Location filling
Ohm
Ohm
1 Aux Trafo-1 Pit-1 4 0.8
2 Aux Trafo-1 Pit-2 3.5 0.8
3 Aux Trafo-1 Pit-3 4 0.7
4 Aux Trafo-1 Pit-4 4.5 0.5
5 Aux Trafo-2 Pit-1 2.5 0.6
6 Aux Trafo-2 Pit-2 2.5 0.5
7 Aux Trafo-2 Pit-3 3.5 0.9
8 Aux Trafo-2 Pit-4 3 0.2
9 Aux Trafo-3 Pit-1 3 0.5
10 Aux Trafo-3 Pit-2 3 0.6
11 Aux Trafo-3 Pit-3 3 0.7
12 Aux Trafo-3 Pit-4 4 0.5
13 Aux Trafo-4 Pit-1 4 0.5
14 Aux Trafo-4 Pit-2 5 0.4
15 Aux Trafo-4 Pit-3 5 0.5
16 Aux Trafo-4 Pit-4 4 0.6
17 STG-1 NGR Pit-1 1.5 0.2
18 STG-1 NGR Pit-2 1 0.5
19 STG-1 NGR Pit-3 1.5 0.9
20 STG-2 NGR Pit-1 2 0.6
21 STG-2 NGR Pit-2 2 0.8
22 STG-2 NGR Pit-3 1 0.9
23 STG-1 Pit-1 0.5 0.4
24 STG-1 Pit-1 0.5 0.3
25 STG-2 Pit-1 0.4 0.2
26 STG-2 Pit-1 0.4 0.4
27 EDG-1 Pit-1 3.5 1
28 EDG-1 Pit-2 2 0.8
29 EDG-1 Pit-3 2 0.9
30 EDG-1 Pit-4 3 0.9
31 EDG-2 Pit-1 3 0.8
32 EDG-2 Pit-2 4 0.7
33 EDG-2 Pit-3 4.5 0.9
34 EDG-2 Pit-4 3 0.5
35 U1 LV Room panels Pit-1 2 1
36 U1 LV Room panels Pit-2 3 0.9
37 U2 LV Room panels Pit-1 2 0.8
38 U2 LV Room panels Pit-2 4 0.7

Any Other Remarks:

Checked By: Verified By:

Name/Designation: Name/Designation:

Signature: Signature:

You might also like