Product data sheet

Specifications

circuit breaker Compact NS100H -


TMD - 100 A - 3 poles 3d
29670

Discontinued

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Range of product Compact NS100...630

Product or component type Circuit breaker

Device short name Compact NS100H

Circuit breaker name Compact NS100H

Device application Distribution

Poles description 3P

Protected poles description 3t

Network type DC
AC

Network frequency 50/60 Hz

[In] rated current 100 A at 40 °C


100 A at 65 °C

[Ui] rated insulation voltage 750 V AC 50/60 Hz conforming to IEC 60947-2

[Uimp] rated impulse withstand 8 kV conforming to IEC 60947-2


voltage

[Ue] rated operational voltage 690 V AC 50/60 Hz conforming to IEC 60947-2


750 V DC conforming to IEC 60947-2

Breaking capacity code H

Breaking capacity 100 kA at 240 V AC 50/60 Hz conforming to NEMA AB1 HIC


35 kA at 600 V AC 50/60 Hz conforming to NEMA AB1 HIC
65 kA at 480 V AC 50/60 Hz conforming to NEMA AB1 HIC
10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
35 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2
50 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
10 kA at 600 V AC 50/60 Hz conforming to UL 508
85 kA at 240 V AC 50/60 Hz conforming to UL 508
65 kA at 480 V AC 50/60 Hz conforming to UL 508
100 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2

[Ics] rated service breaking 65 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2


capacity 70 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
100 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
25 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
5 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
17.5 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2

Suitability for isolation Yes conforming to IEC 60947-2

Utilisation category Category A

Trip unit name TM-D

Jun 9, 2022 1
Trip unit technology Thermal-magnetic

Trip unit rating 100 A

Protection type Short-circuit protection (magnetic)


Overload protection (thermal)

Pollution degree 3 conforming to IEC 60947

Complementary
Control type Toggle

Mounting mode Fixed

Mounting support Backplate

Upside connection Front

Downside connection Front

Mechanical durability 50000 cycles

Electrical durability 30000 cycles 440 V AC 50/60 Hz In conforming to IEC 60947-2


50000 cycles 440 V AC 50/60 Hz In/2 conforming to IEC 60947-2

Connection pitch 35 mm

Local signalling Positive contact indication

Long time pick-up adjustment Adjustable


type Ir

Long time pick-up adjustment 0.8...1 x In


range

Instantaneous pick-up Fixed


adjustment type Ii

Instantaneous pick-up 800 A


adjustment range

Height 161 mm

Width 105 mm

Depth 86 mm

Environment
Standards IEC 60947-2

Product certifications ASTA


ASEFA
LCIE
KEMA

IP degree of protection IP40 conforming to IEC 60529

IK degree of protection IK07 conforming to EN 50102

Ambient air temperature for -25…70 °C


operation

Ambient air temperature for -50…85 °C


storage

Packing Units
Package 1 Weight 1.737 kg

Package 1 Height 1.400 dm

Package 1 width 1.150 dm

Package 1 Length 1.700 dm

Contractual warranty
Warranty 18 months

2
Jun 9, 2022
Recommended replacement(s)
29670 is replaced by:

circuit breaker ComPact NSX100H, 70 kA at 415 VAC, TMD trip unit 100 A, 3 poles 3d
1x LV429670