Innovators in Protection Technology

Flush Mounting Version Din 96x96mm


with reduced depth enclosures
110 Vac/dc - 230 - 400 Vac

DIN 96x96 mm

High reliability

Reduced depth (60 mm)

Simple wiring

Wide range tripping characteristics (current/time)

Suitable for selectivity with other ELRs up or down stream

Fitted filters to comply with VDE and IEC Standards

High immunity to external disturbances

Automatic or manual reset available.


ELR-1E
EARTH LEAKAGE RELAY
FLUSH MOUNTING VERSION DIN 96X96 mm WITH REDUCED DEPTH ENCLOSURES.

ELECTRICAL CHARACTERISTICS

Description ELR-1E

110Vac/dc-230-400Vac (standard)
Auxiliary voltage supply or 24-48Vac/dc
or 12Vac/dc
Frequency 50 ÷ 60 Hz
Maximum consumption 4 VA
Tripping current setting range I∆N 0,025÷0,25A K=0,1 - 0,25÷2,5A K=1 - 2,5÷25A K=10 25÷250A*
Alarm current setting range
Tripping time setting range 0,02 ÷ 0,5 sec. K=1 - 0,2 ÷ 5 sec. K=10
Mechanical signalisation -
Output: changeover contacts Nr.1 5A 250V
Working temperature -10 + 60°C
Storing temperature -20 + 80°C
Relative humidity 90%
Insulation test 2,5 kV 60 sec.
CEI 41-1/IEC 255/VDE 0664/IEC 755/CEI 64.8/ EN 61008-1(1999-11)/EN 62020 (1999-09) /
Standards of reference
EN 61543 (1996-09) /EN61326-1(1998-04) / EN 61326/A1 (1999-05)-IEC 60947-2 ANNEX M
Wiring type Screw terminals / cross section cables 2,5 mm2
Terminal protection degree according with DIN 40050 IP20
Frontal protection degree IP52 (optional IP65)

Selectable fail safe for each output relay -

DIMENSIONS

18 56
96

ELR-.... Earth Leakage Relay

r.3
MEM.

1 1,5 0,2 0,3


0,1
0,5 2 0,4
0,05

92
96

0,25 2,5 0,5


90

ON ALARM TRIP 0,02


96

ΙΔn(A) t (sec)
alarm off alarm on
tx10 tx1
IΔx1 ΙΔ x0,1
ΙΔ x10
FS trip off
TEST RESET
FS alarm off

FAIL SAFE

92

20

TERASAKI ELECTRIC (EUROPE) LTD.


80 Beardmore Way Tel: +44 (0) 141 941 1940
Fax: +44 (0) 141 952 9246 ELR-1 DS
Clydebank Industrial Estate January 2016
Clydebank, G81 4HT, SCOTLAND web: www.terasaki.com