Professional Documents
Culture Documents
User Manual
Last Updated: May 13, 2020
Disclaimer
The software and related documentation, including this documentation, are protected by both United States
copyright law and international treaty provisions. Any unauthorized copying or reproduction is strictly
prohibited and subject to civil and criminal penalties. Please refer to the License Agreement (EULA) for
authorization to make a backup copy of the software. You may not sell this software or documentation or give
copies of them to anyone else.
Except as expressly warranted in the License Agreement (EULA), Bentley Systems, Incorporated disclaims all
warranties, expressed or implied, including but not limited to implied warranties or merchantability and fitness
for a particular purpose, with respect to the software, the accompanying written materials, and any
accompanying hardware. All results should be verified to the user's satisfaction. The contents of these written
materials may include technical inaccuracies or typographical errors and may be revised without prior notice.
2.1 Terminology
When discussing the use of the RAM Steel Column module, it is necessary to differentiate between a single
column segment and a vertical stack of column segments. To avoid confusion, the following terminology will be
used:
An individual column segment is referred to as a column.
A stack of column segments is referred to as a column line. A column line is an important concept in RAM Steel
Column both inside and outside the program. A column line is generated based on certain rules which have been
formulated for resolving scenarios where multiple columns diverge or converge at a junction. The rules have
also been so structured to allow easier column schedule generation. These rules are as follows:
a. A single stack of columns always forms a column line
b. A column line generally stops at a point where it cannot resolve which path it must go further. This occurs at
a junction where there are multiple columns (for example, two or more sloping columns frame down onto a
single column) . The rule in this situation is that the column line continues with the column which frames
closest to 180° angle with its top column in the column line compared to other columns at that level. In case
there is a tie the column line stops at that junction.
Figures 1 and 2 show different column line scenarios and each individual column line is shown in a different
color.
If the Framing Tables were previously built by the program and no changes have subsequently been made to the
database, the program will not repeat that process when RAM Steel Column is invoked, and RAM Steel Column
will be brought up directly. If certain criteria have been changed or if the model has been modified, the Framing
Tables must be rebuilt. Framing will be performed, after which the RAM Steel Column commands will be
available. This entire process is handled automatically by the program.
Note: Once a design is performed on a column line, all columns in the column line will be color-coded to indicate
their new design status. Columns are repainted on a column-by-column basis according to their individual
status.
Icon Description
Data Check
View Elevation turns the cursor into a target cursor. Click on a beam or wall in the
frame to be viewed in elevation.
View Column Plan displays a plan view with all levels compressed into one plan. This is
the same view as a 3D view looking vertical down on the structure.
Find Member displays the Find dialog used to highlight a column, beam, wall or brace of
the specified member number.
View Members displays the Member Options dialog to allow control over the display of
members on the screen.
View Extents displays the Select Extents dialog to allow control over what “extent” of
the model will be displayed on the screen.
View Nodal Loads turns on and off the display of nodal loads.
Display Wall Opening Numbers turns on and off the display of wall opening numbers.
View Zoom Fence is used for zooming in on a specified area. The desired zoom area is
enclosed by a rectangle drawn on the screen using the arrow cursor.
Icon Description
View Zoom Out incrementally zooms out on the area currently displayed on screen.
View Zoom Previous returns to the most recent (previous) zoom location.
Navigation Mode toggles between Pan mode and Rotate mode (used in conjunction
with the keyboard arrow keys).
Resolution Mode toggles between high, medium and low resolution, having reference
to the degree of complexity of the graphics used in the display of the structural shapes,
with low resolution being ‘stick’ graphics and high resolution being extruded, to-scale
shapes.
Non-Pertinent Member Mode toggles the view of the non-pertinent members. The
view toggles between, showing the non-pertinent members in the same resolution as the
pertinent members, showing the non-pertinent members at a low resolution as ‘sticks’
and hiding the non-pertinent members.
Reset Model clears some temporary graphics that may be displayed by the module.
Colors toggles between Model Colors, Design Colors and Interaction Colors (if
available).
Pen Colors provides the user with means to change the color of the member types as
they appear on the screen using the Pen Colors dialog box.
Scale Text displays a dialog to adjust the size of the text displayed on screen.
Increase Text Size increases the size of the text on the screen by a given increment.
Decrease Text Size decreases the size of the text on the screen by a given increment.
Icon Description
Show/Hide Braces.
Show/Hide Foundations.
Show/Hide Grids.
Show/Hide Slab/Decks.
Icon Description
Assign Bracing to assign the braced/unbraced condition for each axis at the top of the
specified columns.
Assign Splicing to assign the splice condition at the top of the specified columns.
Assign Trial Groups to assign Trial Groups to the specified column lines.
Icon Description
Freeze Design – Column Line to freeze the current design of the specified column line.
Freeze Design - All to freeze the current design of all column lines.
Clear Design – Column Line to clear the current design of the specified column line.
Clear Design – All to clear the current design of all column lines.
Icon Description
View Trial Groups to toggle the Trial Groups text on and off.
The Model Notes command opens a text file that may be used for entering any notes
that the user wishes to keep on the currently loaded model. The model notes file is
stored in the same directory as the model’s files and will have the format
modelname.txt. Model notes are made available by invoking the File – Model Notes
command.
2.10 Criteria
There are a number of criteria that can be specified by the user. By setting the criteria properly, designs can be
obtained that conform to the design philosophies of the engineer without requiring extensive member size
selection modifications. After a design has been performed, these criteria can be modified to further refine the
designs. Default criteria are set by the Defaults Utility in the RAM Manager but can be modified on a project-by-
project basis within the Column Design module.
If any criteria selections are modified after a model has been analyzed and designed, the optimized member
designs will be cleared from the database so that new optimized designs can be obtained based on the newly
specified criteria. Modifying the Design Defaults criteria and Bracing criteria also causes the Framing Tables to
be rebuilt (see Section 2.4 (on page 10)). Upon issuing the command to change a criteria item, a warning dialog
box will appear on the screen stating that proceeding with this command will clear all previously optimized
sizes. The command can be canceled at this time without affecting the database.
For small angles, it may be appropriate to suppress the splitting of the reaction, and apply the full reaction on the
nearest face. The magnitude of the angle to be considered in determining whether or not to split the reaction can
be specified by selecting the Criteria - Design Defaults command. If the angle between a column axis and a
beam axis is less than that specified, the total reaction will be applied to the side of the column to which the
beam frames; if the angle exceeds that specified, the reaction will be split between the adjacent sides. See Section
3.4.4 (on page 48), Moment Split, for an explanation of how the reaction is split.
If the option Skip-load the Live Load around the column is selected, the program will skip-, or pattern-, load
the Live Load around the column to create the worst design case of biaxial bending and axial loads. See Section
2.14 (on page 21), Design Loads, for more information.
2.10.4 Bracing
The RAM Steel Column Design program automatically determines the unbraced length based on user specified
criteria and the geometry of the framing at a column. Usually the unbraced length used in column design is the
length of the column. There are conditions, however, where this is not the case for e.g. the situation where there
are more than two columns attached to a joint and the bracing is missing in any direction.
Using the Criteria - Bracing command, the user may specify whether or not the presence of floor deck braces
the column. If so, the column is considered braced regardless of the configuration of the attaching beams
whenever the column is within the decked area.
The angle at which a beam is no longer considered to act as a brace for a given axis of the column is also
specified using the Criteria - Bracing command. If no beams frame into a column within the specified angle of a
given axis, the column is considered unbraced in that axis (unless braced by the deck).
For some Codes the allowable bearing of the base plate on the concrete is a function of the size of the plate
relative to the size of the support. Thus it is necessary to know the size of the concrete support in order to design
the base plate. Since that information is not currently available to the base plate design routines, the minimum
footing size can conservatively be specified in the criteria. If even the minimum footing is sufficiently larger than
the base plate, the footing size becomes irrelevant and the maximum permissible value of bearing on concrete is
used. Otherwise, the criteria can be changed to reflect the varying support conditions and the base plate designs
obtained for those columns.
2.11 Assign
While the Criteria commands are used to modify defaults on a project-by-project basis, the Assign commands
are used to override the default criteria on a column-by-column basis. Note that if the defaults are acceptable, it
is not necessary to invoke the Assign commands.
2.11.1 Bracing
The bracing condition determined by the program can be overridden on a column by column basis using the
Assign - Bracing command. For each axis (Major and Minor) there are three options:
• Global is used to specify that the Bracing conditions used for design are to be determined by the program
based on the model geometry and Bracing Criteria.
• Braced is used to specify that the Bracing conditions used for design are to be considered as braced,
regardless of the model geometry and Bracing Criteria.
• Unbraced is used to specify that the Bracing conditions used for design are to be considered as unbraced,
regardless of the model geometry and Bracing Criteria.
Note that to clear a previous assignment, invoke the Assign – Bracing command and assign the Global option.
In Single mode, select the column for which the Bracing assignment is to be assigned to the top of the column. In
Fence mode fence entirely all columns for which the Bracing assignment is to be assigned to the top of the
column. All assigns the Bracing assignment to the tops of all columns.
2.11.2 Splicing
Splice levels are taken into consideration by the Column Design module when selecting column sizes. Rather
than picking a different column size for each level, the program selects the same size for all levels between
splices, based on the controlling design case between the splices. A splice at a level indicates to the program that
the size can change between the level above and the level below; the lack of a splice indicates to the program
that the size must be the same for the level above and the level below. The assignment of splice levels is done
globally in the Story Data in the RAM Modeler. This can be overridden on a column by column basis using the
Assign - Splicing command. There are three options:
• Global is used to specify that the Splicing conditions used for design are to be determined by the program
based on the model geometry and the Story Data.
• Spliced is used to specify that the Splicing conditions used for design are to be considered as spliced,
regardless of the model geometry and the Story Data.
• Not Spliced is used to specify that the Splicing conditions used for design are to be considered as not spliced,
regardless of the model geometry and the Story Data.
Note that to clear a previous assignment, invoke the Assign – Splicing command and assign the Global option.
In Single mode, select the column (not the splice symbol) for which the Splicing assignment is to be assigned to
the top of the column. In Fence mode fence entirely all columns for which the Splicing assignment is to be
assigned to the top of the column. All assigns the Splicing assignment to the tops of all columns.
It is often useful to first design the columns with a splice specified at every level, then modify the splice level
assignments based on the results to determine the best splice locations, and redesign the columns.
For some configurations of geometry and material the program may override the Splicing assignments. See
Section 3.5 (on page 51), Column Splices.
2.12 Materials
In the RAM Modeler, columns can be laid out in steel, concrete or a user defined material (“Other”). When the
model is brought into the Column Design module, only the gravity steel columns are optimized and have sizes
assigned. However, gravity loads are calculated for concrete and “other” columns and can be obtained from the
Reports - Loads or the Reports - Loads Summary output reports.
Lateral steel columns will only be designed if no size was previously assigned to a column. This may be useful for
automatic preliminary sizing of lateral columns.
• Save the modifications to the model by selecting the Update Data Base button.
Selecting Update Data Base will store the column design information in the model and the column will be
“tagged” as User Size. If a column is tagged as a User Size, the program will no longer perform the optimization
algorithm for that column. Instead, it is analyzed for adequacy under the design loads. A column tagged as a User
Size will retain that flag until cleared with the Process – Clear Design command.
If changes in design criteria or any changes to geometry or loading in the RAM Modeler will affect the User
tagged columns, the User size can be cleared so that the program will recalculate the optimum column
configuration. If a user-selected column is inadequate, a warning is issued, but the design is still allowed. It is the
engineer's responsibility to determine whether or not to allow an over-stressed condition on member sizes that
have been specifically selected.
In most cases, making changes to the model in the RAM Modeler or to the design criteria specified in the Criteria
menu of the Column Design module will result in the previous optimum sizes being cleared from the database.
Making changes to beam designs may also affect the column sizes if the option to consider beam self-weight has
been selected in Criteria – Self-Weight in the Manager.
When the self weight criteria is turned on, the program will restrict a View/Update on a column line with
dependent column lines having columns tagged “cannot design.” This restriction will be lifted upon resolving
the “cannot design” tag on the dependent column. Refer to 2.15 for conditions which result in a “cannot
design.” Also refer to the on-line help for a more detailed description of the View/Update command or the
Tutorial for examples on using this command.
2.16 Copy
A special method of design is the Process – Copy command. It allows the user to assign the same column sizes to
one column line as are assigned to another. This is useful when it is desired to make similar column lines
identical. To use the Copy command, first design a column line. This can be done either by using the Process –
View/Update command or the Process – Design All command. Next, select the Copy command. With the target
cursor select the designed column (the Copy From column), then select the column to which the designs are to
be copied (the Copy To column). The designs and settings (splicing and bracing) will be copied to the column.
The target cursor changes, alternating between a Copy From cursor to a Copy To cursor, to help identify the
current step in the copy process.
The column lines must match in number of columns in the column line, type (standard or hanging), framing and
material for the copy command to be successful.
The Copy command does not create a link between the Copy From column and the Copy To column; a
subsequent change in the design of one is not automatically made to the other. The command merely copies the
current sizes, Fy (fy or py), and settings from one column line to another. For hanging columns, the single and
double angle parameters are also copied.
Designs may be frozen by selecting the Process – Freeze Design – All or Process – Freeze Design – Col Line
commands. Freezing a design on a member is similar to setting a User Size in that the program will never re-
optimize the design unless the User clears the design.
Members that have had their design Frozen or members that were previously assigned User Sizes in the View/
Update can be cleared by selecting the Process – Clear Design – All or Process – Clear Design – Col Line
commands. After designs are cleared, upon the next design the program will again perform an optimized design
on all cleared members.
In the RAM Structural System, its output and throughout the remainder of this manual these are referred to as
IBC, ASCE 7, BOCA, SBC, UBC, NBC of Canada, BS 6399, UK National Annex, Eurocode, China, Hong Kong, and NBC
of India, respectively. The sections of these codes applicable to the analysis performed by RAM Steel Column are
those dealing with roof and floor loads and the reduction of live loads. They are subject to certain assumptions
and limitations as outlined in the Technical Notes.
Note: You are free to select the steel design code independently of the Building Code. Refer to the Building Code
appropriate for the particular jurisdiction to determine the proper steel design code to select.
In the RAM Steel Column program, its outputs and throughout the remainder of this manual, these are referred
to as AISC 360-16 ASD, AISC 360-16 LRFD, AISC 360-10 ASD, AISC 360-10 LRFD, AISC 360-05 ASD, AISC 360-05
LRFD, ASD 9th, LRFD 3rd, CAN/CSA-S16, BS 5950, Eurocode, AS 4100, and IS 800-07 respectively. Because the
requirements of AISC 360-16, AISC 360-10, and AISC 360-05 are nearly identical they will often be collectively
referred to as AISC 360.
Note: Repeated reference is made throughout the program and the documentation to "Live Loads". In some
codes these loads are referred to as "Imposed Loads".
The Dead Load is the total dead load such as slab, deck, partitions, miscellaneous, etc. Member and slab self-
weights can be included in this value automatically. See Section 3.3.2 Self-Weight Calculations.
The Construction Dead Load, or Pre-composite Dead Load, is a temporary load and is that portion of the Dead
Load that is applied to the beam prior to composite action. It must be less than or equal to the Dead Load. This
value is only used in the RAM Steel Beam Design Module when designing unshored ("unpropped") composite
beams. This is in addition to the Construction Live Load described below. When a column is supported by a
composite beam, RAM Steel Column Design assumes that the full column load is applied to the post-composite
section; the column induces no Construction Dead Load on the pre-composite section.
The Live Load is the total live load appropriate for the particular building based on the applicable Building Code
and use of the building. Live Loads may be defined as Reducible, Storage, Unreducible, or Roof. Roof loads may
be treated as Reducible or Unreducible. Live Load Reduction is discussed in Section 3.3.8.
The Partition load is an additional Live Load; it is treated as an unreducible Live Load and will not be reduced. It
is in addition to the loads specified as Live Load. Partition loads are defined variously by the Codes, some as
Dead Load and some as Live Load. For those codes that define Partition loads as an unreducible Live Load, those
should be specified here. For those Codes that define Partition loads as a Dead Load or as part of the regular Live
Load, those should be included as part of the Dead Load or Live Load accordingly.
The Construction Live Load is a temporary load that is applied to the beam prior to composite action. It
represents the temporary load due to workers and equipment on the bare beam prior to composite action. This
load is combined with the Construction Dead Load when investigating the pre-composite beam. No Live Load
reduction is performed on this load. Its magnitude is independent of the Live Load value. This value is used only
in the RAM Steel Beam Design module when designing unshored ("unpropped") composite beams. It has no
impact on column designs.
The Mass Dead Load is the load that will be used in calculating the diaphragm mass properties used in RAM
Frame. It is not used in the design of gravity steel columns.
Snow loads, including varying drifting snow loads can also be applied. A current limitation in the program is that
Roof Live Loads and Snow Loads cannot be considered simultaneously. Both types of loads can exist
simultaneously in the model, but only one or the other will be considered. In the Criteria – Live Load
Reduction command in the RAM Manager there are two options: “Consider Snow Loads, Ignore Roof Live
Loads” and “Consider Roof Live Loads, Ignore Snow Loads”. This is used to specify which set of loads is to be
considered. If both types of load need to be considered, it may be necessary to design the members twice, once
with each option selected. Note that this limitation is only between Snow and Roof Live loads; Snow and
Reducible, Storage or Unreducible and Partition Live loads can be considered simultaneously by the program.
Surface load properties are assigned to the model by defining the boundaries of the load polygon. Virtually any
number of load polygons may be assigned to a given layout. Additionally, overlapping polygons are permitted.
The last polygon assignment will over-ride all previous assignments rather than be additive.
Polygon boundaries need not coincide with beam locations; boundaries can fall within a bay. Such changes in
loads will result in multiple uniform or trapezoidal loads generated on the beam and will be shown individually
on the Beam Output. Care should be taken in the RAM Modeler when laying down load polygons, especially those
whose sides should coincide with a beam line, so that extraneous minuscule loads are not generated on the
beam.
The self-weight of Concrete columns and beams is calculated using the value of Unit Weight for Self-Weight,
specified by the user in the Modeler. This value of Unit Weight is separate from the value specified for Unit
Weight used in the calculation of material properties (e.g., modulus of elasticity).
Note that self-weights are based on the center-to-center dimensions of beams and columns respectively. This
means that there is a duplication of self-weight at the joints. The program does not make any attempt to reduce
this.
θ
(A)
w cosθ
θ
(B)
w cos2θ
w cosθ sinθ
(C)
Figure 3:
In RAM Steel the impact of sloping members is manifested in the lengths of, and load on, beams in the RAM Steel
Beam module, and the height of the columns in the RAM Steel Column module.
In RAM Steel Beam the distributed surface loads and applied line loads are transformed to calculate the
component of the load that acts perpendicular to the length of the member as explained above. This is the load
considered in the design of the steel beams. Note that no axial load is considered in the design of beams in RAM
Steel Beam. Although all modeling of members and loads is performed in plan mode, the length of the beam,
length of unbraced segments and location of loads are all based on the actual beam length, considering the true
slope of the beam.
In RAM Steel Column the effect of the sloped floor feature is evident in the length of the columns, as shown in the
gravity steel column design report. Columns lengths are calculated based on both the story height and the
extension of the column above or below that height.
See Section 3.3.8 for information on the effects of sloping framing on Live Load reduction for Roof Live Loads.
Procedure Detail
A minimum of two closed polygons are first calculated by the program: a beam-loop polygon and slab-edge
polygon (these are indicated in the following figure (A) with red and green lines, respectively). Note that the
beam-loop polygon might be composed of beams, joists, or walls. Then the area between the slap-edge and
beam-loop polygons is partitioned into load polygons, which are used to distribute loads on slab edges (in the
following figure (B) ). These load polygons are generated in such a way that any angle between two beams (or
walls) is bisected outward. Finally, any loads (point, line or surface loads) detected on load polygons are
projected back onto beams.
(A) (B)
Figure 4: (A) Slab-edge and beam-loop polygons are shown in green and red colors, respectively; (B) Generated slab
edge load polygons
It is important to know that there must be at least one closed loop with beams (including joist and walls), and
one closed loop with slab edges. Otherwise, the program cannot construct load polygons and cannot process
loads on slab edges. For some ambiguous configurations, generated load polygons may not be acceptable (to
verify loads on edge beams it is recommended that you check the distributed loads found on beams in the RAM
Steel Beam module). An example of such a configuration is given in the following figure; the beams form a
concave loop but the slab edge doesn't extend into that area. Thus it is ambiguous as to how the slab edge load
and the load within the concave area should be distributed back to the beams. In cases like this it is suggested
that the slab edge be placed to more explicitly to identify the intent, or that surface loads be removed from these
areas and line loads manually applied to the neighboring members.
Loads (point, line or surface loads) found inside or on these generated slab edge load polygons are projected
back to beams (or walls). One-way distribution of loads is assumed, with the slab edge loads carried back to the
beam at right angles to the beam. Therefore, loads in the exterior corner of a slab will be ignored since there is
no beam to distribute the load back to at a right angle to the beam. For example, the highlighted portion of the
surface load in the following figure is ignored:
The calculation of opening slab edge load for each beam in the loop is not trivial due to the fact that an opening
can have practically any shape. The calculation of opening slab edge load for each beam requires identifying the
polygons, the loads on which are carried back to the beam. An opening slab edge load polygon for any beam is
obtained by finding the nearest point on the opening from the beam nodes (beam nodes lying on the beam loop).
These nearest points on the opening and the beam nodes are then used to form one or more closed polygons.
More than one load polygons are formed for a beam if the opening edge or corner sits on the beam itself. If there
are multiple points found on the openings which are equidistant from the beam nodes then the mid-point of the
extreme points found on the opening is considered as the nearest point. This mid-point considered also lies on
the opening.
Once the slab edge polygons (tributary area boundaries) are calculated for each beam in the beam loop, the
loads on each polygon are carried straight back to the associated beam as if the deck was laid perpendicular to
beam. Thus, the deck orientation originally assigned to the deck polygon has no influence on the load
distribution; for edges the load is always distributed in a direction perpendicular to the beam. The following
figure shows the opening slab edge load polygon for a few selected beams from beam loops shown in the
previous figure.
For some complex openings, if there is no direct perpendicular line back to a beam, there may be some portion
of the load in the opening slab edge polygon that does not get carried back to the beam, and is ignored.
It is important to recognize that when an opening of any size or placement is placed within a bay of framing
supporting one-way deck, the opening edges are defining the slab edge distances for all beams framing around
that opening, regardless of the distance from the beam to the opening. For that entire bay, all loads are
distributed as slab edge loads, and the normal one-way distribution is not applicable. For example, the following
figure shows an opening that only fills a small portion of the bay. This is improper modeling. The presence of the
opening within the beam loop indicates that all loads within that loop are to be treated as slab edge loading.
Therefore, the loads beneath the opening are distributed down to the bottom beam as if that was a long slab
edge overhang, not left and right to the adjacent beams as would be expected with one-way distribution. To get
the appropriate distribution, the opening should be framed with a beam near the bottom of the opening.
Tip: If no steel beam is intended to be framed there in the actual structure, the beam can be modeled as material
“Other”; it will then satisfy the need for a beam there without impacting the Takeoff values.
Penetrations (openings created in the RAM Modeler with the Layout > Slab > Penetrations command) have no
effect on loads. Their presence is ignored by the program when calculating member loads. Their purpose is to
limit the effective flange width of composite beams.
The user may limit the live load reduction on columns by specifying a Use Calculated Value, limited to a
Maximum of with the Layout > Columns > LL Reduction command in the RAM Modeler. The limit is assigned
on a column-by-column basis. If a limitation is assigned using this command, the program will use the more
stringent of the code required value and the user specified value. With this same command the user may also
assign an explicit value to use, which will override the calculated value. These assignments have no impact on
the design of the beams.
The requirements for live load reduction are different for each Building Code. They are outlined below by
Building Code.
L =L 0(0.25 + 15
K LL AT ) Equation 16-23
where
L = the reduced design live load per square foot of area, psf
L0 = the unreduced design live load per square foot of area, psf
AT = the tributary area, ft2
KLL = the Live Load element factor from Table 1607.11.1
For members supporting one floor, L shall not be less than 0.50L0 (this is a 50% reduction). For members
supporting two or more floors, L shall not be less than 0.40L0 (this is a 60% reduction). To be consistent with
the way the Live Load reduction is reported by the program for other Building Codes, the Live Load Reduction
value will be computed and given as a percent reduction, rather than as a multiplier.
The Live Load Reduction value is further limited to the user specified maximum, if any.
There is a special provision in the code (IBC 2018 Section 1607.11.1.2 Heavy live loads) for live loads greater
than 100 psf. In the program, this type of load is referred to as “Storage” live load and, for such loads a reduction
of up to 20% (if allowed by Eq. 16-23) is allowed on members carrying storage load from two or more levels.
The user must explicitly designate loads as Storage. Any live load designated by the user as Storage will be
treated as explained whether the load is greater than 100 psf or not, and any load not specified by the user as
Storage will not be treated as Storage even if it exceeds 100 psf.
Table 1607.11.1 gives values for KLL. Theoretically it is the ratio of the Influence Area to the Tributary Area:
Ai
K LL = AT
. Typically the value for columns is 4, and the value for beams is 2. With these values, the equation
gives the same reduction values as ASCE 7-95 and ASCE 7-93, which is what has been implemented for BOCA
Live Load Reduction. When there are large cantilevered areas contributing to the area supported by the
member, the values of 4 for columns and 2 for beams are considered unconservative. The table gives a value of 3
for edge columns with cantilever slabs, 2 for corner columns with cantilever slabs, and 1 for edge beams with
cantilever slabs. The Code does not give any indication as to what fits within the definition of cantilever slabs.
For example, it does not seem that a column supporting beams that carry a nominal slab edge would need to be
included under this classification. The table also specifies a value of 1 for cantilever beams.
The program determines both the tributary area and the influence area for each member. KLL is then calculated:
Ai
K LL = AT
To conform to the table values, which show integer numbers, the program will round the calculated KLL to an
integer value as well. This is done as follows:
The 0.15 tolerance for rounding up is to avoid unduly penalizing members that carry some nominal slab edge or
very short cantilevers.
For loads on the cantilever portion of a cantilever beam, KLL = 1.
KLL is calculated independently for both Reducible Live Loads and Storage Live Loads based on their respective
tributary and influence areas.
BOCA
For BOCA, the reduction of Reducible Live Loads is based on influence area rather than tributary area. The code
defines influence area as “...four times the tributary area for a column, two times the tributary area for a beam...”.
It is important to note that for all members regardless of configuration, the program first calculates the tributary
area, determines the portion of that area loaded by Reducible Live Load, then multiplies that area by four when
calculating the reduction for columns and by two when calculating the reduction for beams. The reduction is
limited to 50% for members receiving load from one floor only and is limited to 60% for members receiving load
from more than one floor (the reduced load is not less than 40% of the unreduced value). It is important to note
that the output lists the reduction factor as a percent by which the load can be reduced. No reduction is
permitted for members having an influence area less than 400 square feet.
There is a special provision in the Code (Section 1606.7.2.3) for live loads greater than 100 psf. The program
refers to this type of load as a Storage load and, for loads specified as Storage live loads, a reduction of up to 20%
is allowed on columns loaded by more than one level. No such reduction is made on beams even if they receive
load from more than one level. If the equation involving influence area indicates a lesser reduction, the reduction
is limited to the smaller amount. Note that in calculating the influence area, only the area loaded by Storage live
load is considered and is derived from the tributary area as explained above. The user must explicitly designate
loads as Storage. Any live load designated by the user as Storage will be treated as explained whether the load is
greater than 100 psf or not, and any load not specified by the user as Storage will not be treated as Storage even
if it exceeds 100 psf.
Roof live loads are reduced per Table 1607.3. However, any value of Roof live load can be input (not necessarily
20 psf) and the program will reduce it with the appropriate factor. For example, if a Roof live load of 30 psf is
assigned to a member carrying over 600 square feet of roof area, the load is reduced to 18 psf (30 psf times
0.60). It is assumed that the roof is flat or has a rise less than four inches per foot. The reduction is based on the
tributary area loaded by Roof live load.
No reduction is made on loads specified as Unreducible.
SBC
For loads indicated as Reducible, any member supporting 150 square feet or more of Reducible live load is
reduced at the rate of 0.08% per square feet (R = 0.08*Area). The reduction is limited to 40% for beams and
60% for columns. The reduction is further limited to that obtained by the equation R = 23.1(1+D/L).
There is a special provision in the Code (Section 1604.2-2) for live loads greater than 100 psf. The program
refers to this type of load as a Storage load and, for loads specified as Storage live loads, a reduction of up to 20%
is allowed on columns. No such reduction is made on beams. If the equations involving tributary area indicate a
lesser reduction, the reduction is limited to the smaller amount. The reduction is further limited to that obtained
by the equation R = 23.1(1+D/L). The user must explicitly designate loads as Storage. Any live load designated
by the user as Storage will be treated as explained whether the load is greater than 100 psf or not, and any load
not specified by the user as Storage will not be treated as Storage even if it exceeds 100 psf.
Roof live loads are reduced per Table 1604.6 with the reduction not to exceed that obtained by the equation R =
23.1(1+D/L). Any value of Roof live load can be input (not necessarily 20 psf) and the program will reduce it
with the appropriate factor. For example, if a Roof live load of 30 psf is assigned to a member carrying over 600
square feet of roof area, the load is reduced to 18 psf (30 psf times 0.60). It is assumed that the roof is flat or has
a rise less than four inches per foot. The reduction is based on the tributary area loaded by Roof live load.
No reduction is made on loads specified as Unreducible.
UBC
For loads indicated as Reducible, any member supporting 150 square feet or more of Reducible live load is
reduced per UBC Eq (7-1): R = 0.08(A - 150). The reduction is limited to 40% for members receiving load from
one floor only and is limited to 60% for members receiving load from more than one floor. The reduction is
further limited to that obtained by the equation R = 23.1(1+D/L).
There is a special provision in the Code (Section 1607.5) for live loads greater than 100 psf. The program refers
to this type of load as a Storage load and, for loads specified as Storage live loads, a reduction of up to 20% is
allowed on columns. No such reduction is made on beams. If the equations involving tributary area indicate a
lesser reduction, the reduction is limited to the smaller amount. The user must explicitly designate loads as
Storage. Any live load designated by the user as Storage will be treated as explained whether the load is greater
than 100 psf or not, and any load not specified by the user as Storage will not be treated as Storage even if it
exceeds 100 psf.
Roof live loads may be reduced per either Method 1 or Method 2 of Table 16-C. However, any value of Roof live
load can be input (not necessarily 20 psf) and the program will reduce it with the appropriate factor. For
example, if a Roof live load of 30 psf is assigned to a member carrying over 600 square feet of roof area, the load
is reduced to 18 psf (30 psf times 0.60) for Method 1. It is assumed that the roof is flat or has a rise less than four
inches per foot. The reduction is based on the tributary area loaded by Roof live load. The reduction is limited to
a maximum of 40% regardless of the number of levels from which the member receives load, and is further
limited to the value obtained by UBC Eq (7-2).
No reduction is made on loads specified as Unreducible.
NBC of Canada
For loads specified as Reducible, the live load on any member supporting 20 square meters or more of Reducible
live load is reduced per the equation in NBC Clause 4.1.6.9.3.
NBC Clause 4.1.6.9.2 is applicable for members supporting assembly loads of 4.8 kPa or more, or storage,
manufacturing, retail, etc. For Live Load Reduction purposes, the program classifies these types of loads as
Storage Live Load. For loads specified as Storage, the live load on any member supporting 80 square meters or
more of Storage live load is reduced per the equation in NBC Clause 4.1.6.9.2.
The user must explicitly specify loads as Reducible or as Storage in order for the corresponding reductions to be
performed. Any live load designated by the user as Storage will be treated as such whether the load is greater
than 4.8 kPa or not, and any load specified as Reducible will be treated as such (using the reduction in Clause
4.1.6.9.3) even if the load is greater than 4.8 kPa.
No reduction is made on loads specified as Unreducible or Roof.
It is important to note that the output lists the reduction as a percent by which the load can be reduced, rather
than as a load multiplier.
BS 6399
Imposed Loads are referred to in the program and documentation as “Live Loads”. Live Loads specified as
Reducible are reduced as allowed by BS 6399: Part 1: 1996 Clause 6, “Reduction in total imposed floor loads”, as
described below. Note that the UK National Annex to Eurocode 1 (NA to BS EN 1991-1-1:2002) uses this same
methodology.
For columns, Live Loads specified as Reducible are reduced by the greater of Table 2 and Table 3. In the
determination of Number of Floors used in Table 2, the user may specify that only floors carrying Reducible Live
Load be included in that number by invoking the Criteria > Live Load Reduction Command in the RAM
Manager as explained previously.
The Code explicitly requires that, when the Live Load is reduced, the Live Load Reduction Factor used on column
moments is that corresponding to the beam which creates the moment, while the Live Load Reduction Factor
used on column axial load is that corresponding to the column itself. As a simplification, the program only
reduces the column axial load; it does not reduce the column moments. Since beam Live Load Reductions are
small (generally about 2 to 5%), this is not likely to have a significant impact on the design, and is conservative.
Reducible Live Loads on beams are reduced per Table 3. Reductions for intermediate areas are calculated by
linear interpolation.
For transfer girders, the reduction of the point load from the column is that of the column itself, and the
reduction of the remaining Live Loads is based on the supported area not including that coming from the
column.
Live Loads specified as Roof loads are reduced based on the slope of the roof in the vicinity of the member per
BS 6399:Part 3:1988 Clause 4.3.1. If the slope is less than 30 degrees no reduction is taken. If the slope is greater
than 60 degrees the load is completely reduced (to 0.0). For intermediate slopes the percent reduction is
interpolated.
No reduction is made on Live Loads specified as Unreducible or Storage.
It is important to note that the output lists the reduction as a percent by which the load can be reduced, rather
than as a load multiplier.
Eurocode
Imposed Loads are referred to as Live Loads. Reducible Live Loads are those of Categories A to D. For loads
indicated as Reducible, any horizontal member supporting 10 square meters or more of Reducible live load is
reduced per EN 1991-1-1:2001 Eq (6.1):
5 Ao
αn = 7
Ψo + A
≤ 1.0
where
A = the tributary area
Ψo = specified in the RAM Manager Criteria > Eurocode Factors command
The Eurocode requires that for Categories C and D, the reduction factor αA be greater than or equal to 0.6. This is
not done automatically by the program, but can be accomplished by specifying a limit to the Live Load Reduction
of 40% in the Modeler using the Layout > Beams > LL Reduction command.
Storage Live Loads are those of Category E. The Live Load reduction on horizontal members is performed the
same as for Reducible Live Loads except that the Ψo factor is different, as specified in the RAM Manager Criteria
> Eurocode Factors command.
For vertical members supporting Reducible or Storage loads, the reduction is based on Eq (6.2):
2 + (n − 2)Ψ
o
αn = n
where
n = the number of stories supported by the member
Ψo = specified in the RAM Manager Criteria > Eurocode Factors command
No reduction is made on loads specified as Unreducible for either horizontal or vertical members.
No reduction is made on loads specified as Roof for either horizontal or vertical members.
It is important to note that the output lists the reduction factor as a percent by which the load can be reduced,
rather than a load multiplier.
China GB 50009-2001
For loads specified as Reducible, the live load on any beam supporting 25 m2 or more of Reducible live load is
reduced 10% (the reduction coefficient is 0.90) per Clause 4.1.2.1(1). This would be applicable to loads in Item 1
in Table 3.1.1.
For loads specified as Storage, the live load on any beam supporting 50 m2 or more of Storage live load is
reduced 20% (the reduction coefficient is 0.80) per Clause 4.1.2.1(2).
For loads specified as Reducible, the live load on any column is reduced per Table 4.1.2 as specified in Clause
4.1.2.2(1). As specified in that table, for a one-story column if the tributary area of the column is greater than 25
m2, the reduction coefficient is 0.90.
For loads specified as Storage, the live load on any column supporting 50 m2 or more of Storage live load is
reduced 10% (the reduction coefficient is 0.90) per Clause 4.1.2.2(2).
The user must explicitly specify loads as Reducible or as Storage in order for the corresponding reductions to be
performed.
IS 800-07
For columns, imposed loads specified as reducible are reduced per the requirements of Section 3.3.2. In the
determination of number of floors, you may specify that only floors carrying reducible live load be included in
that number by selecting Criteria > Live Load Reduction in the RAM Manager as explained previously.
Imposed loads specified as roof loads are reduced based on the slope of the roof in the vicinity of the member
per IS 875 (Part 2) Section 4.1
No reduction is made on loads specified as Storage, Unreducible or Roof.
It is important to note that the output lists the reduction as a percent by which the load can be reduced, rather
than as a load multiplier.
Note: BS 5950 : Part 1 Section 4.7.7 explicitly says that it is not required to pattern load the Live Load around the
column. For that Code the option may be deselected.
4 2
1 2 3 4
1 + + + + + Pos Only
2 + + + +
3 + + + +
4 + + + +
5 + + + +
6 + + +
7 + + +
8 + + +
9 + + +
10 - - - - - Neg + Pos
11 - - - -
12 - - - -
13 - - - -
14 - - - -
15 - - -
16 - - -
17 - - -
18 - - -
Unbalanced Moments (on page 43). For columns at the intermediate unbraced story levels where no moments
can be determined since no beams frame into either the top or bottom of a column stick, moments are based on
a linear interpolation of the column moments from the top and bottom braced point moments in the multi-story
column stack. Moments due to skip loading at the braced locations are similarly interpolated and assumed for
the intermediate unbraced column sticks within the multi-story column stack.
Typical multi-story column have moments at the braced stories but where a multi-story column with an
intermediate unbraced story has an applied moment resulting from a stub or a beam with an eccentric reaction
but has been released from bracing the story, the applied moment applied is used in lieu of an interpolated
moment for the story.
3.4.2 Reactions
The reactions loading each side of the column are calculated. If a beam is skewed with respect to the column, its
reaction is split into orthogonal components and added to the values from the appropriate sides of the column.
The split is based on the ratio of the angle.
For example, a skewed beam with a 10 kip reaction frames into the column between sides 1 and 2 at
an angle of 20° from side 1. The 10 kip reaction is split as follows:
90 ° − 20 °
R1: 90 °
× 10kips = 7.78kips
20 °
R2: 90 °
× 10kips = 2.22kips
Depending on the connection configuration and the angle at which the beam frames into the column, it may be
appropriate to suppress the splitting of the reaction and apply the full reaction to a single side of the column. The
user may specify the maximum angle at which reactions will not be split. If the angle between a given column
axis and the beam is greater than the angle specified the reaction will be split between the two adjacent sides; if
the angle is less than the angle specified the full reaction will be applied to the closest side.
concurrently (e.g., a positive live load is applied on one side of the column and a negative live load is applied on
the other). These additional combinations are not investigated by the program.
Table 3-2 shows the Load Cases that occur due to the various combinations of Load Conditions at the top and
bottom of the column. These are the Load Cases that are investigated by the program. References to Load Cases
in the output correspond to these load cases. Load Cases 1 through 17 are positive live load cases; Load Cases 18
through 34 are negative live load cases. Note that Load Cases 1 and 18 are the unskipped cases (i.e., the reactions
are applied to all sides simultaneously).
To determine the skip load condition for a given Load Case, refer to Table 3-2 for the Load Condition used for
that Load Case. Refer to Table 3-2 for that Load Condition to determine the reactions which are being applied.
For example, Load Case 6 uses Load Condition 2 at the top of the column and Load Condition 8 at the bottom of
the column (per Table 3-2). Load Condition 2 applies the positive live load reactions on sides 1, 2, and 3, but not
side 4; Load Condition 8 applies the positive live load on sides 3 and 4, but not sides 1 and 2 (per Table 3-1).
AISC 360
1.0DL
ASD
1.0DL + 1.0LL
1.0DL + 1.0LL roof
1.0DL + 0.75LL + 0.75LL roof
AISC 360
1.4 DL
LRFD
ASD 9th
1.0 DL
1.0 DL + 1.0 LL + 1.0 LL roof
LRFD 3rd
1.4 DL
1.2 DL + 1.6 LL + 0.5 LL roof
1.2 DL + 0.5 LL + 1.6 LL roof
CAN/CSA
1.4 DL
S16
1.25 DL + 1.5 LL + 0.5 LL roof
1.25 DL + 0.5 LL + 1.5 LL roof
0.9 DL + 1.5 LL + 0.5 LL roof
0.9 DL + 0.5 LL + 1.5 LL roof
Based on the Importance category, NBC of Canada may allow Live, Roof, and Snow loads to be
reduced or may require that the Snow loads be increased. The program does not apply these
factors. The loads should be input with the factors applied as appropriate.
BS 5950
1.4 DL
1.4 DL + 1.6 LL + 1.6 LL roof
1.0 DL + 1.6 LL + 1.6 LL roof
Eurocode All symbols indicated in this section are set by the engineer from the Eurocode Factors dialog in
RAM Manager.
γGj,supDL
Note: When Snow load is specified rather than Roof Live Load, LLsnow and ψ0,snow are used in
the above equations in place of LLroof and ψ0,roof, respectively.
AS 4100 Load combination template files were generated based on AS/NZS 1170.0:2002, Section 4.2
and Combinations of Actions for Ultimate Limit States. Section 4.2.2 Strength
AS/NZS
1170 The combinations included in RAM Steel Column are:
(a) [1.35G]
(b) [1.2G, 1.5Q]
(c) [1.2G, Su, ψcQ]
where
G = the Dead Load (“permanent action”)
Q = the Live Load (“imposed action”)
Su = the Snow Load (per Section 4.2.3(a))
ψc = the “combination factor for imposed action” and user
can provide in the RAM Manager Australia Criteria
dialog
The combinations are expanded as follows:
1.35DL
1.2DL + 1.5 LL
1.2DL + 1.5 LL + 1.5 LL roof
1.2DL + ψc LL + 1.5 LL snow
ψc is specified by the user in the RAM Manager Australia Criteria dialog (Available if AS/NZS
1170 is selected as the Live Load Reduction code in the RAM Manager Critera > Member Loads
dialog).
IS 800-07
1.0 DL
WSD
1.0 DL + 1.0 LL + 1.0 LL roof
IS 800-07
1.5 DL
LSD
1.5 DL + 1.5 LL + 1.5 LL roof
In cases where there is a stub cantilever at a level at which the column is not braced and there are significant
moments induced by other stub cantilevers or large eccentric reactions at adjacent levels, the assumptions made
in the determination of the column design loads may be inadequate. In such cases the design produced by the
program should be investigated for adequacy. Similarly, if a level with eccentric moments from beams framing in
has been assigned as unbraced by the user (overriding the program's assumption that beams that frame in brace
the column), the correctness of the design moments should be verified.
When the column above the joint has a K-factor (Le/L) of 2.0 in a given axis (i.e., the column acts as a “flagpole”),
the full moment is applied to the top of the column below the joint.
Design Code Channel Single Angle Double Angle Tee Round Bar Flat Bar
Design Code Channel Single Angle Double Angle Tee Round Bar Flat Bar
Note: Round bars, flat bars, built-up channels, and built-up tube shapes are not currently designed to the IS
800-07 design code.
adjacent sides. See Section 3.4.4 (on page 48), Moment Split, for an explanation of how the moment is split
between columns above and below.
If the option Skip-load the Live Load around the column is selected, the program will skip-, or pattern-, load
the Live Load around the column to create the worst design case of biaxial bending and axial loads. See Section
2.14 (on page 21), Design Loads, for more information.
3.14.3 BS 5950
The design yield strength is the yield strength according to the material grade as defined in Table 6 of
BS5950:Part1:1990 and in Table 9 of BS5950:Part1:2000. To assign a grade to a section the engineer assigns a
nominal yield strength (py) to the beam section. Based on the magnitude of the nominal yield strength the
section is assigned a grade from the table. If the nominal yield strength is within a range of yield strengths
indicated in the table then the associated grade is assigned to the section and the rules relating material
thickness to design yield strength are followed. If the nominal yield strength is not within a range of yield
strengths indicated in the table then the design yield strength is assigned the nominal yield strength value, and
no reduction is made for material thickness. The design yield strength will never be larger than the engineer
provided nominal yield strength.
3.14.4 Eurocode
For steel with nominal fy between 275 N/mm2 and 460 N/mm2 the design yield strength is adjusted to account
for material thickness. In Criteria > Design, the Eurocode Factors tab has an option to specify that the Design fy
rules be used based on either EN 1993-1-1 or EN 1993-1-1 UK NA.
EN 1993-1-1: For hot-rolled shapes, Table 3.1 of BS EN 1993-1-1:2005 rules per EN 10025-2 are used except for
S420 and S460, for which the rules of EN 10025-3 are used. For structural steel hollow sections the rules of
Table 3.1 of BS EN 1993-1-1:2005 rules per EN 10210-1 are used.
EN 1993-1-1 UK NA: For hot-rolled shapes, rules from Table 1.5 of BS EN 10025-2 are used. For structural steel
hollow sections the rules of Table A.3 of EN 10210-1 are used, except for S420 and S460 which use the rules for
Table B.3.
For steel with a nominal Fy not recognized by those tables, the section will be assigned a small yield strength
and fail in design. A large interaction value on a design is indicative of assigned yield strength outside the ranges
indicated above.
Both nominal and design Fy appear on all design output.
3.14.5 Australia
The design yield strength is a function of both the material and the element thickness properties of the section.
The user provided Nominal Yield Strength (Fy) is first mapped to an appropriate material according to Table 2.1
of the AS 4100-98 code. The material that is used is based on the material that most closely matches the yield
strength specified and the section shape.
The following materials are used based on the yield strength assigned to the member.
For steel with a nominal Fy outside of the ranges specified no steel material will be found and the section will be
assigned a small yield strength and fail in design. A large interaction value on a design is indicative of assigned
yield strength outside the ranges indicated above.
Each of these materials provides a different yield strength depending on the thickness of the elements (flange,
web etc). of a cross section being designed. The yield strength used in the final design is printed in the detailed
report output.
3.14.6 IS 800-07
The design yield strength, fy, is the value specified by the user. No reduction is made for thick sections.
CAN/CSA S16
Modulus of Elasticity E = 200,000 Mpa
Shear Modulus of Elasticity G = 80,000 Mpa
BS 5950
Modulus of Elasticity E = 205 kN/mm2
Shear Modulus of Elasticity G = 78.85 kN/mm2
Eurocode
Modulus of Elasticity E = 210,000 N/mm2
Shear Modulus of Elasticity G = 80,769 N/mm2
IS 800-07
Modulus of Elasticity E = 200,000 N/mm2
Shear Modulus of Elasticity G = 76,900 N/mm2
As described in the RAM Manager documentation the engineer can specify whether hollow structural sections
are of Class C (cold-formed non-stress-relieved) or Class H (hot or cold-formed stress-relieved). The engineer
can also indicate whether built-up flange sections are comprised of milled plate or flame cut plate. These
designations affect the axial capacity of the HSS and flange sections as specified in Section 13.3.1 of the design
specification.
3.16.2 BS 5950
The columns are designed according to the rules of Simple Construction described in section 4.7.7 of the BS5950
specification. In the event that the lateral torsional buckling capacity is to be calculated, lambda is always taken
as 0.5L/ry.
The bending capacity of Class 3 is considered to be the compression flange section modulus multiplied by the
design yield strength.
As described in the RAM Manager documentation the engineer can specify whether built-up flange sections are
comprised of milled plate or flame cut plate. This designation affects the axial capacity of the flange sections as
specified in footnote 2 of table 25 in the BS 5950 specification.
3.16.3 AS 4100
A following assumptions and criteria have been made in the implementation of the AS 4100 design code.
The program conservatively assumes the unbraced column length is not rotationally restrained at the ends of
the segment as discussed in 5.4.3.4 and 5.6.3(3).
No torsion is considered in the design.
Loads are assumed applied through the column shear centers at their ends.
Rolled sections other than tubes and pipes are assumed to be Hot Rolled (HR) per table 5.2. Tubes and pipes are
assumed cold formed (CF) per Steel Designer Handbook. All welded sections must be designated as either Heavy
Welded (HW) or Light Welded (LW) as selected by the user in the RAM Manager.
3.17.4 BS 5959
“Le>180” If the member slenderness exceeds 180 then no further design checks are performed.
“F>Pcx” or If the axial load exceeds the capacity of the section then no further design checks are
“F>Pcy” performed.
“Class 4” If a section contains a slender element it will be indicated as a class 4 section and no
additional design checks will be performed.
“Slender Web” If a section subject to shear has a web whose depth to thickness ratio exceeds the code
limit of 69ξ then no further design checks will be performed.
3.17.5 AS 4100
“N* > Nomx” or “N* > Nomy” Displayed when total axial load in the member exceeds the elastic critical
buckling resistance for the member in the plane of bending. This has
implications in the calculation of interaction values.
“DeltaBx > 1.4,” “DeltaBy > Displayed when the moment amplification factor exceeds the code specified
1.4” limit 1.4.
3.17.6 IS 800-07
“Slender” If a part of the cross section exceeds the slender section limits for flange or web.
b a
Maximum Plate Size
c
d
Minimum Plate Size
Figure 11:
The initial plate size (a, b) is calculated based on the supported steel column dimensions and the user specified
minimum dimensions from column side to edge of plate. The maximum base plate size that can fit on the support
is then calculated as a rectangle of equivalent proportions to initial plate size (c, d). This area (c, d) is defined as
the supporting area for bearing capacity determination.
3.18.3 Eurocode
Base plate design for the Eurocode is based on BS EN 1993-1-8:2005 section 6.2.5.
The critical moment location for the base plate is taken to be at the centerline of the flange. That is, the moment
arm is taken as the c distance plus one-half of the flange thickness.
For columns consisting of round and rectangular hollow sections, the bearing area is determined by calculating
the value for c and then calculating the associated area, analogous to the method described for I-shaped
columns.
γMO and Υc are specified in the Criteria > Eurocode Factors command of RAM Manager.
3.18.5 BS 5950
Base plate design for BS 5950:1990 is based on Clause 4.13.2, Empirical Design of Baseplates.
Base plate design for BS 5950:2000 is based on Clause 4.13.2, Effective Area Method.
The plate design py is based on the nominal yield strength specified and the plate thickness.
3.18.6 AS 4100
Base plates are not currently designed according to the AS 4100-98 design code.
3.18.7 IS 800-07
Base plates are not currently designed according to the IS 800-07 design code.
Lu: These are the unbraced lengths with respect to the X- and Y-axes used in design.
K: These are the effective length factors. K will be 1.0 for a column braced at both ends; it
will be 2.0 for a "flag pole" column (unbraced at the top of the column).
Braced Against Joist The RAM Steel Column Design module assumes that all gravity columns are braced
Translation: against joint translation.
Column These are the eccentricities of the beam-column connections. They are based on the
Eccentricity: user-specified criteria, and are used to calculate the unbalanced moment.
Axial: These indicate the total unfactored Dead, Live and Roof Loads associated with the controlling load
case. The Live Load and Roof Load are reduced, if allowed. The Live Load may be less than the
total Live Load due to skipping associated with the controlling load case. Likewise for the Roof
Load.
Pnx: This is the axial capacity about the column's major axis.
Pny: This is the axial capacity about the column's minor axisl.
Pn: This is the governing axial capacity based on all applicable limit states in Chapter E.
including the date and time it was created or last modified and the building and steel codes that were utilized in
the design process. It may also include the licensee Company name and a project description.
Lu: These are the unbraced lengths with respect to the X- and Y-axes used in design.
l/L: These are the effective length factors. I/L will be 1.0 for a column braced at both ends;
it will be 2.0 for a "flag pole" column (unbraced at the top of the column).
Braced Against Joist The RAM Steel Column Design module assumes that all gravity columns are braced
Translation: against joint translation.
Column Eccentricity: These are the eccentricities of the beam-column connections. They are based on the
user-specified criteria, and are used to calculate the unbalanced moment.
Shear: These indicates the total unfactored Dead and Live load shear associated with the controlling load
case. The shear is calculated as the sum of the end moments on the column divided by the column
length.
Lu: These are the unbraced lengths with respect to the X- and Y-axes used in design.
K: These are the effective length factors. K will be 1.0 for a column braced at both ends; it
will be 2.0 for a "flag pole" column (unbraced at the top of the column).
Braced Against Joist The RAM Steel Column Design module assumes that all gravity columns are braced
Translation: against joint translation.
Column These are the eccentricities of the beam-column connections. They are based on the
Eccentricity: user-specified criteria, and are used to calculate the unbalanced moment.
total Live Load due to skipping associated with the controlling load case. The same applies to the
Roof Load.
Braced Against Joist The RAM Steel Column Design module assumes that all gravity columns are braced
Translation: against joint translation.
Column These are the eccentricities of the beam-column connections. They are based on the
Eccentricity: user-specified criteria, and are used to calculate the unbalanced moment.
Design Fy: This is the yield strength adjusted for the thickness of the section used in the design of
the section.
Orientation: This is the orientation, in degrees, of the column web with respect to the global X-axis.
For example, if the web is parallel to the X-axis, the orientation angle is 0.0 degrees; if the
web is perpendicular to the X-axis, the orientation is 90.0 degrees.
Lu: These are the unbraced lengths with respect to the major and minor axes of the section
as used in design.
ke: These are the effective length factors. ke will be 1.0 for a column braced at both ends,
2.0 for cantilever column.
Braced Against Joist The RAM Steel Column Design module assumes that all gravity columns are braced
Translation: against joint translation.
Column Eccentricity: These are the eccentricities of the beam-column connections. They are based on the
user-specified criteria, and are used to calculate the unbalanced moment.
Section The section capacity includes the actual and allowable stresses for AS4100 and certain
Capacity: parameters used in the checking section capacity at the section. The nomenclature of the
variables is that used in the AS4100 Specifications.
The results of the interaction equations are shown for each of the Nominal Section Capacity,
Uniaxial Bending and Biaxial bending.
Member The member capacity includes the actual and allowable stresses for AS4100 and certain
Capacity: parameters used in the checking member capacity at the section. The nomenclature of the
variables is that used in the AS4100 Specifications.
δb or δs used to account for the p-δ effect described in Chapter 4.4 of the specifications.
The results of the interaction equations are shown for each of the Nominal Section Capacity, In-
plane Capacity, Out-of-plane Capacity and Biaxial bending.
Lu These are the unbraced lengths with respect to the X and Y axes used in design.
K These are the effective length factors. K will be 1.0 for a column braced at both ends; it
will be 2.0 for a “flag pole” column (unbraced at the top of the column).
Braced Against The RAM Steel Column Design module assumes that all gravity columns are braced
Joist Translation against joint translation.
Column These are the eccentricities of the beam column connections. They are based on the user
Eccentricity specified criteria, and are used to calculate the unbalanced moment.
along with the Formula reference. The Code limits the value to 1.0. The nomenclature of the variables is that
used in the IS 800-07 Specification.
Column Line This is the column line grid label. It represents the top co-ordinate or grid location of the top
Grid Label: column and top co-ordinate or grid location of the bottom column in a column line. If the top
columns top coordinates and bottom columns top coordinates are the same then only one is
listed in the label.
LC: This is the controlling load case number. Refer to the Technical Notes (on page 25) for a
description of the load cases.
Interaction This is the controlling interaction equation result with the corresponding formula reference.
Eq.: The acceptability of the column can be quickly determined from this value.
Angle: This is the orientation, in degrees, of the column web with respect to the global X-axis. For
example, if the web is parallel to the X-axis, the orientation angle is 0.0 degrees; if the web is
perpendicular to the X-axis, the orientation is 90.0 degrees.
Size: This is the designed column size. It is either the optimum size selected by the RAM Steel
Column module or the user selected size. If RAM Steel Column cannot compute the optimum
size from the trial groups then No Design is shown for the column size in the report.
Similarly, if the RAM Steel column encounters situation where it cannot design a column then
Cannot Design is shown for the column size in the report.
4.8.2 LRFD
Pu: This is the total ultimate design axial load for the controlling load case.
Mux: This is the total ultimate design moment about the strong axis for the controlling load case.
Muy: This is the total ultimate design moment about the weak axis for the controlling load case.
All column loads are unfactored loads. In cases where there is no size in the column i.e. none worked or cannot
design, then user would see an asterisk (*) tag assigned to the column and placed next to the self-weight. In
cases where there are applied moments to any column in the column line, a message saying “See column loads
report for applied moments” is printed after the entire column line report.
4.12.3 Bearing
Concrete f'c: Specified concrete strength.
Size of concrete support: Size of concrete support used in calculating allowable concrete bearing
strength.
Area of concrete support: Area of concrete support used in calculating allowable concrete bearing
strength.
Eff Area of support (A2): Area of the portion of the supporting surface that is geometrically similar to
and concentric with the loaded area.
Area Required for Bearing: Area of plate required by concrete for bearing.
Area of Plate (A1): Actual area of plate.
Square Root of (A2/A1): Used in calculation of allowable concrete bearing; limited to 2.0 maximum.
Allow. Factored Bearing For Allowable Stress Design, this is the allowable concrete bearing stress
Stress: based on ACI allowable values.
Actual Factored Bearing For Allowable Stress Design, this is the actual factored concrete bearing
Stress: stress.
Actual Bearing Stress: For Allowable Stress Design, this is the unfactored concrete bearing stress
used in sizing the plate thickness.
0.60Pp: For LRFD 3rd, this is the allowable design bearing load on the concrete.
Resistance moment, mRd: This is the moment capacity of the plate, mRd, per unit length of the yield line.
Actual moment: This is the actual moment in the plate per unit length of the yield line.
Design Fy: This is the yield strength used in the design of the base plate, considering Grade and thickness.
Br: This is the bearing strength of the concrete support.
4.12.7 BS 5950
The items indicated below appear only on the British outputs.
4.12.8 IS 800-07
The items indicated below appear only on the Indian outputs.
Column Line Grid This is the column line grid label. It represents the top co-ordinate or grid location of the
Label: top column and top co-ordinate or grid location of the bottom column in a column line. If
the top columns top coordinates and bottom columns top coordinates are the same then
only one is listed in the label.
Column Size: The size of column at the given location, used in calculating plate size.
Fy, fy, py: Yield strength of base plate.
N: Plate dimension parallel to column web.
B: Plate dimension perpendicular to column web.
tp: Plate thickness required for stresses, capacities, and increment criteria.
A.1 File
Menu Item Description
Model Status (on page 87) To show the current status of the Column designs.
File Save (on page 86) To Save the current designs, criteria, etc., to the
database
File - Notes (on page 87) To view or add notes pertaining to the current model.
Exit (on page 87) To exit the RAM Steel Column Design module.
Issuing the File - Exit or File - Open commands before the current database has been saved will cause a
message to be given warning the user that changes have been made since the last Save was invoked, and gives
the user a chance to save work before exiting. Select Yes if you want to save the changes to the database, No if
you want to discard the changes, or Cancel if you want to continue with the current database.
If the program crashes or otherwise abnormally terminates at any time before the database can be properly
saved, a message will be given the next time that database is opened indicating that a temporary backup file for
that database has been found. The backup file contains the database as it existed at the last Save, before the most
recent changes were made. The user is given the option to either open the database as it occurred at or just
previous to the time that the program terminated (using the Most Recent Database option) or to open the
backup database which contains the database as it existed at the time of the last Save (using the Backup
Database option). The user is also given the option to cancel opening either one.
If the Backup Database option is selected, any changes made since the last proper Save will be lost.
If the Most Recent Database option is selected, the user should carefully inspect the model. The most recent
database contains all or most of the changes since the last Save, but it may also contain whatever data errors or
corruption that may have caused the program to terminate. If the data is corrupted, exit without saving. This will
cause the most recent changes to be lost and the backup database to be restored to the database (the same as if
the Backup Database option had been selected initially).
Alternatively, select the Most Recent Database option and then save to a different name using the File - Save
As command. By doing this, both versions of the database will be available for further inspection or use if
necessary.
A.1.4 Exit
Selecting the File - Exit command will terminate execution of the Column Design module and return control to
the RAM Manager.
A.2 Criteria
Menu Item Description
Criteria - Steel Design Codes (on page 88) To display and/or modify the current Column or Base
Plate Steel Design Code for all columns and base plates
in the model.
Criteria - Design Defaults (on page 89) To display and/or modify the current Column Design
Defaults for all columns in the model.
Criteria - Trial Group Defaults (on page 90) To display and/or modify the current Trial Group
Defaults for all columns in the model.
Criteria - Bracing (on page 91) To display and/or modify the current Column Bracing
Defaults for all columns in the model.
Criteria - Base Plate (on page 91) To display and/or modify the current Base Plate
Design Defaults.
• “Limit States Design of Steel Structures.” CAN/CSA-S16-14. Canadian Institute of Steel Construction.
• “Limit States Design of Steel Structures.” CAN/CSA-S16-09. Canadian Institute of Steel Construction.
• “Limit States Design of Steel Structures.” CAN/CSA-S16-01. Canadian Institute of Steel Construction.
S16S1-05 Supplement No. 1 is also implemented.
• “Structural use of steelwork in building.” BS 5950 : Part 1. “Code of practice for design: rolled and welded
sections.” 2000. British Standards Institute.
• “Structural use of steelwork in building.” BS 5950 : Part 1, “Code of practice for design in simple and
continuous construction: hot rolled sections.” 1990. British Standards Institute.
• “Structural use of steelwork in building.” BS 5950 : Part 3, Section 3.1. “Code of practice for design of simple
and continuous composite beams.” 1990. British Standards Institute.
• “Eurocode 3 - Design of Steel Structures, EN 1993-1-1:2005.” European Committee for Standardization in
Design of Steel Structures (Eurocode 3).
• “Eurocode 4 - Design of Composite Steel and Concrete Structures, BS EN 1994-1-1:2004.” European
Committee for Standardization in Design of Composite Steel and Concrete Structures (Eurocode 4)
• “Steel Structures.” Australia Standard. Building Code of Australia. AS 4100-98. June 5, 1998. Includes
Amendments No 1-1992, No. 2 – 1993, No.3 – 1995 and Draft No.4 (Base plate code not currently available).
• “Indian Standard, General Construction in Steel - Code of Practice (December 2007),” IS 800:2007 published
by the Bureau of Indian Standards (Third Revision).
Click the Cancel button to exit the dialog without saving the changes made.
Make the code change by clicking OK. A warning will be given stating that making this change will result in
clearing all optimized sizes. Click Yes in this message dialog to complete the change and clear optimized sizes.
Clicking No will cancel the change and return you to the Criteria - Steel Design Code dialog.
For a complete explanation of how the eccentric moments are calculated and how the reactions are split, see the
Technical Notes chapter in the RAM Steel Column manual.
To change the angle, type the desired angle (0 - 45 degrees) in the edit box.
Click the Cancel button to exit the dialog without saving the changes made.
To accept the changes, click the OK button. A warning dialog box will appear stating that the columns must be
re-framed and redesigned with this new criteria. Clicking OK will initiate the re-framing process. Clicking Cancel
will terminate the command, returning you to RAM Steel Column.
I-shape
Rectangular Hollow Section
Round Hollow Section
Channel
Tee Section
Flat Bar
Round Bar
Single Angle
Double Angle
During the design process, columns will be selected only from the size groups indicated in the Trial Groups. The
optimum column sizes in each trial group is determined during design, and the trial group with the least weight
is selected as the column line design.
Up to three Trial Groups can be defined for each design. To select a trial group, click the check box above the trial
group so that it has a check mark in the box. Note that there are separate Trial Groups for Standard and for
Hanging columns.
For each shape within the Trial Groups, select the desired size group from the drop-down list. Click on the size
group to select it. It will appear in the trial group edit box. The sizes that appear in the lists are dependent upon
the sizes in the selected column design table. If a shape is not present in the table, the entry for that shape will be
blank.
Click Cancel to exit the dialog without saving the changes made.
To change the Trial Group Settings, click the OK button. A warning will be given stating that making this change
will result in clearing all optimized sizes. Click Yes in this message box to complete the change and clear
optimized sizes. Clicking No cancels the change and returns you to the Criteria - Trial Groups dialog.
Note: Change to criteria will not override trial groups assigned to a column line using the Assign - Trial Groups
(on page 96) command.
A.3 Assign
Assign - Trial Groups (on page 96)(3) To modify the column Trial Group
assignments on a column line basis.
Clicking the Cancel button will cause the dialog to close and return you to RAM Steel Column.
Making an assignment will cause the affected column line to be redrawn in yellow. Assigning bracing to an
optimized column will clear the optimized design. Frozen columns will maintain their design but will need to be
re-analyzed with the new bracing assignment.
Assign Bracing
Select Global, Braced or Unbraced, for both the major and minor axis. "Global" means that the bracing will be
determined by the global criteria.
Single: To assign bracing to one column, click Single. This will cause the dialog box to close and the target cursor
to appear. Click on columns with the target to make the assignment. The symbols on the screen will update to
indicate that the assignment has been made.
Fence: To assign bracing to a group of columns, click Fence. This will cause the dialog box to close and the
rectangle cursor to appear. Click and drag the rectangle to include the columns to which the assignment will be
made. The symbols on the screen will update to indicate that the assignment has been made. (HINT: When
assigning in Fence mode, it is often a good idea to be in plan or elevation to insure that only the desired columns
are fenced)
All: Clicking the All button will cause the dialog to close and the assignment made to all steel columns in the
model.
Clicking the Cancel button will cause the dialog to close and return you to RAM Steel Column.
Making an assignment will cause the affected column line to be redrawn in yellow. Assigning splicing to an
optimized column will clear the optimized design. Frozen columns will maintain their design but will need to be
re-analyzed with the new splicing assignment.
Assign Splicing
Select Global, Spliced or Not Spliced. "Global" means that the splicing will be determined by the column design
module.
Single: To assign splicing to one column, click Single. This will cause the dialog box to close and the target cursor
to appear. Click on columns with the target to make the assignment. The symbols on the screen will update to
indicate that the assignment has been made.
Fence: To assign splicing to a group of columns, click Fence. This will cause the dialog box to close and the
rectangle cursor to appear. Click and drag the rectangle to include the columns to which the assignment will be
made. The symbols on the screen will update to indicate that the assignment has been made. (HINT: When
assigning in Fence mode, it is often a good idea to be in plan or elevation to insure that only the desired columns
are fenced)
All: Clicking the All button will cause the dialog to close and the assignment made to all steel columns in the
model.
I-shape
Rectangular Hollow Section
Round Hollow Section
Channel
Tee Section
Flat Bar
Round Bar
Single Angle
Double Angle
During the design process, columns will be selected only from the size groups indicated in the Trial Groups. The
optimum column sizes in each trial group is determined during design, and the trial group with the least weight
is selected as the column line design.
The Default Trial Groups for all columns in the model are specified in the Criteria - Trial Group Defaults (on page
90) dialog.
How To:
Clicking the Cancel button will cause the dialog to close and return you to RAM Steel Column.
Making an assignment will cause the affected column line to be redrawn in yellow. Assigning trial groups to an
optimized column will clear the optimized design. Frozen columns will maintain their design but will need to be
re-analyzed.
If "Use Trial Group(s)" is selected, the trial group control below will become active. Click on the check boxes to
the left to select a trial group to assign. Select size groups to be included in a trial group from the drop down lists.
The sizes in the drop down lists are determined by the Steel Column Design table selected in RAM Manager.
Single: To assign trial groups to one column line, click Single. This will cause the dialog box to close and the
target cursor to appear. Click on column lines with the target to make the assignment. The text on the screen will
update to indicate that the assignment has been made.
Fence: To assign bracing to a group of column lines, click Fence. This will cause the dialog box to close and the
rectangle cursor to appear. Click and drag the rectangle to include the column lines to which the assignment will
be made. The text on the screen will update to indicate that the assignment has been made. (HINT: When
assigning in Fence mode, it is often a good idea to be in plan or elevation to insure that only the desired column
lines are fenced)
All: Clicking the All button will cause the dialog to close and the assignment made to all column lines in the
model.
Single: To reset trial groups for one column line, click Single. This will cause the dialog box to close and the
target cursor to appear. Click on column lines with the target to reset the trial groups. The text on the screen will
update to indicate that the change has been made.
Fence: To reset trial groups for a group of column lines, click Fence. This will cause the dialog box to close and
the rectangle cursor to appear. Click and drag the rectangle to include the column lines for which trail groups
will be reset. The text on the screen will update to indicate that the change has been made. (HINT: When
assigning in Fence mode, it is often a good idea to be in plan or elevation to insure that only the desired column
lines are fenced)
All: Clicking the All button will cause the dialog to close and all steel columns in the model to return to the trial
group default.
A.4 Process
Design All (on page 99)(1) To design all steel columns and
baseplates
Perform Design All Set this option to have RAM Steel Column perform a Design All operation immediately
Automatically upon completion of the Framing. If this option is selected, the other Column Design
After Framing module commands will be available upon completion of the Design All command. It is
not necessary to do this, as some command such as Process > View/Update and Print >
Single do not require that a Design All be performed. You may also select Process >
Design All manually after RAM Steel Column is open
A.4.2 View/Update
Selecting Process > View/Update opens the View/Update dialog for a selected column, which is used to view
the automated design of that column.
Each column line in the model is designed automatically for its least weight based on a number of user-defined
Assign (on page 91) and Criteria (on page 88). It also allows you to explore various design options and save the
resulting design back to the database.
Note: If sizes were previously assigned to a column line either from the Update Data Base command or—for
lateral column—by using the Assign - Size command in another RAM Structural System module, these sizes will
be analyzed for the existing loading conditions.
• The first tab, View/Update: Story - Analyze (on page 103), allows you to try various sizes or yield
strengths on a per column basis. Sizes and yield strengths can be selected to the final design. They will be
inserted into the Final Design section of the table, replacing the values that are already there.
• The second tab, View/Update: Story - Optimize (on page 104), provides a way to investigate shapes and
yield strengths on a per column basis. Sizes and yield strengths on this tab can also be selected to the final
design. They will be inserted into the Final Design section of the table, replacing the values that are
already there.
• The third tab, View/Update: Column Line Optimization (on page 105), allows you to investigate different
shapes and yield strengths per column line. The results of the optimization from this tab is displayed in
the Trial Groups Results section of the grid.
• To the right of the investigation tabs is the design warning box. This box lists warnings for the entire column
line.
The stop light in the Final Design box indicates the state of the final design. It is green when the design of the
entire column line passes and red when it fails. (Note that changes within the investigation tabs do not
impact the stop light.)
The Reset button resets the column line design to the design shown when the dialog first opened.
The Update Database button closes the dialog and saves the design as it is listed under the Final Design
columns in the table. Once a column design is saved, it will not change until it is cleared using the Process >
Clear command.
Cancel closes the dialog without saving the design.
Clicking in one of these cells selects the story and makes it the active story on the investigation tabs.
To the right of this information is the display of the Final Design. If the column line was optimized, these are the
sizes that the design engine determined to be the most optimum based on total weight (also displayed).
The interaction equation value calculated for each column is displayed beside the column size. Interaction
equation values > 1.0 are shown in red.
The sizes of Lateral Columns are shown in a dark red. This should not be confused with the bright red that
indicates design failure.
While it is currently not possible to change size or yield strength in the grid, clicking on either will transfer the
information to the investigation tabs. From there, sizes and yield strength can be saved and selected for the final
design.
During optimization, columns are sized based on these Trial Groups. The results of the design of each trial group
are shown in the right most part of the table.
The total weight of each Trial Group is listed below it.
Note that the number of columns displaying trial group results are equal to the number of trial groups assigned
to that column line.
To select a size from a trial group for further investigation on a per column basis, click on the size in the cell.
To select an entire trial group as your final design, click the heading above the column of sizes (i.e. "Select T.G.
1").
Upon entering the View/Update dialog the size and yield strength on the Story - Analyze tab reflects the selected
story.
The yield strength value can be changed by typing a new value in the edit box.
The size can be changed in one of two ways:
1. Click on any cell in the grid that contains a column size. This size will be transferred to the Story - Analyze
tab, even if the cell is not associated with the selected story.
2. Select a new size from the combo box.
When a new yield strength is entered or a size is changed by clicking in the grid, the View Results button and
Select buttons will be gray out until an Analysis has been performed (Click the Analyze button). This is also true
when changing the properties of double angles for hanging columns.
Selecting a new size from the combo box automatically kicks off the analyze process.
When results for an analysis is current, the resulting interaction equations are displayed at the bottom of the tab.
In cases where the analysis fails, a reason for the failure appears in red.
Clicking the View Results button displays the Column Design report for the size and yield strength chosen for
investigation.
Clicking the Select button transfers the current size and yield strength to the "Final Design" section of the table.
An analysis of the entire column line is then run to update the weight and interaction equation values for all
columns. If any design warning occur during this analysis, they will be listed in the Design Warning list box.
When this tab is selected, the shape and yield strength value on the tab reflects the selected story.
The yield strength value can be changed by typing a new value in the edit box.
The Shape combo box controls which shape will be considered during optimization. For Standard Column, the
combo box will contain the three relevant shapes while for Hanging Columns, all nine shapes will be available for
selection.
When a change is made to the tab, the Optimize button becomes available and the View Results and Select
buttons gray out.
Click the Optimize button to initiate the optimization process. The results of the optimization will be displayed in
the table below.
Clicking on a specific size will cause its interaction equation to be shown below the grid. It also makes the View
Results and Select buttons active.
Clicking the View Results button displays the Column Design report for the size and yield strength chosen for
investigation.
Clicking the Select button transfers the current size and yield strength to the "Final Design" section of the table.
An analysis of the entire column line is then run to update the weight and interaction equation values for all
columns. If any design warning occur during this analysis, they will be listed in the Design Warning list box.
When this tab is selected, the shape and yield strength value on the tab reflects the selected story.
The yield strength value can be changed by typing a new value in the edit box.
The Shape combo box controls which shape will be considered during optimization. For Standard Column, the
combo box will contain the three relevant shapes while for Hanging Columns, all nine shapes will be available for
selection.
Clicking the Optimize button will initiate the optimization of the column line.
Results are displayed in the Trial Group Results section of the table.
The column line weight of trial group design is listed at the bottom of the column.
The yield strength entered on the tab is shown to the far right.
To select a trial group design as your final design, click the column header "Select T.G. #" and this design will be
moved to the Final Design section of the table.
When a section is made, an analysis of the entire column line is then run to update the weight and interaction
equation values for all columns. If any design warning occur during this analysis, they will be listed in the Design
Warning list box.
A.4.3 Copy
In some cases it is desirable to override the optimum designs, making the sizes of similar column lines identical.
This can be done by using the Copy command. The Copy command copies sizes and yield strength from one
column line to another. If the column lines are incompatible (such as different number of levels) a warning is
given and the Copy is canceled. If the sizes being copied to the new column line are inadequate a warning will be
given allowing you to cancel the Copy.
To Copy the sizes from one column line to another
1. Issue the Process - Copy command
2.
With the "Copy From" target cursor select a column line that has the design that will be copied.
3.
With the "Copy To" target cursor select the column line that will receive the new design.
If the "Copy From" column line has not been design, a warning is shown and you are given the opportunity to
design the column line.
Once the design has been copied, the column line that received the design (the "Copy To" column line) the design
will be analyzed for that column line's loading. Because this column line is not considered to be user-defined, or
frozen, the columns will be painted blue of the design passes and red if it fails.
This process can be repeated, alternately selecting the Copy From column and the Copy To column lines.
The Copy command DOES NOT create a link between the Copy From column and the Copy To column; a
subsequent change in the design of one is not automatically made to the other. The Copy command merely
copies the current sizes and Fy from one column line to another.
A.5 Reports
Menu Item Description
Viewer File To have the reports saved to the report viewer file
format. This provides the ability to view the report
without running the any of the RAM Structural System
modules.
Column Design - Single (on page 108) To print a Gravity Column Design Report for a selected
level of a selected column.
Column Design - Col Line (on page 108) To print a Gravity Column Design Report for all levels
of a selected column.
Column Design - All (on page 109) To print a Gravity Column Design Report for all levels
of all columns.
Col Summary (on page 109) To print a Gravity Column Design Summary Report
Loads (on page 109) To print the Gravity Loads on Columns Report listing
all gravity loads on the selected column(s).
Load Summary (on page 109) To print the Column Load Summary Report which
summarizes the gravity loads on all column lines.
Takeoff (on page 110) To print the Gravity Column Design Takeoff Report
which lists the quantity and weight of each column
size in the design.
A.5.6 Loads
Selecting the Reports - Loads command will cause all
unsized columns to be designed, and a Gravity Loads
on Columns Report to be printed. The Gravity Loads
on Columns Report lists the gravity loads on each level
of each column in detail including dead load, each
category of live load, live load reduction factors,
maximum total load and minimum total load.
A.5.8 Takeoff
Selecting the Reports - Takeoff command will cause the Gravity Column Design Takeoff Report to be printed.
The Gravity Column Design Takeoff Report lists all gravity column sizes classified by steel grade, and the total
length and weight for each size listed. A piece count and total weight for the entire structure is also listed.
A.6 View
This toolbar is shared with the RAM 3DViewer. See the RAM 3D Viewer manual or help within 3D View for more
information on these commands.
A.7 Window
A.7.1 Close
To close an application or document, click in the upper-right corner of the window, or click Close on the
application or document Control menu.
A.7.2 Maximize
To enlarge an application or document window to fill the screen, click in the upper-right corner of the
window, or click Maximize on the application or document Control menu. To restore the window to its previous
size and location, double-click the title bar.
A.7.5 Toolbar
Contains buttons that give you quick access to many commands and features. To see the name of a button, point
to it with the mouse. To display or hide toolbars, use the Toolbars command on the View menu. To make an
anchored toolbar a floating toolbar, or vice versa, double-click a blank area on the toolbar.
A.7.7 Minimize
To reduce an application or document window to an icon, click in the upper-right corner of the window, or
click Minimize on the application or document Control menu. To restore the window to its previous size and
location, double-click the icon.
A.7.8 Restore
To restore a window to its previous size and location, click in the upper-right corner of the window, or click
Restore on the application or document Control menu.