Features
Auto-restart function
Group control(if connect with a group controller)
Auto-changeover
Compact design of indoor unit
Weekly timing(if connect with a weekly timer)
Haier Group
MANUAL CODE: SYJS-006 EDITION:2002.12.31.
CONTENTS
CONTENTS
Contents……..............................................…...………...…….1
1. Description of Products & Features…………………...…….1
2. Specifications…………………………. ………………...……3
3. Safety precaution…………………………..………………….9
4. Net dimensions of indoor and outdoor unit………………...11
5. Installation instructions ……………………. ………………..17
6. Parts and functions …………………………..…… ..……….28
7. Remote controller functions………………………….………31
8. Refrigerant diagram…………………………..……………....43
9. Electrical control functions……………………………………44
10. Diagnostic information(trouble shooting)…………….……51
11. Electrical data.........................................…………….……56
12. Exploded views and parts lists...............……………. ……67
13. Performance curves……………............................... ……87
14. Noise level charts.....……………............................... ……93
15. Air velocity distribution …………............................... ……94
-1-
DESCRIPTION OF PRODUCTS & FEATURES
Power: 03(230V/50Hz).04(240V/50Hz).12(115V/60Hz).13(230v/60Hz)
Product series
“H” refer to cooling and heating, ”C” refer to cooling only
Nominal cooling capacity (BTU/h), 42=42000BTU/h
Indoor and outdoor unit code: "B" Cassette type; "U" Outdoor unit
“H” means “Haier”
New code
A B 42 N A C A C A
Climate type: T1 (see table 1)
Design number (A stands for fix speed type)
Product type: A stands for heat pump type, refrigerant is R22
B stands for heat pump type, refrigerant is R407
M stands for cool only type, refrigerant is R22
N stands for cool only type, refrigerant is R407
Appearance character
Product series: one by one type
Applicable voltage: 2 stands for 220-240V/50Hz,4 stands for 220v/60Hz
N stand for 380V/50Hz
Cooling / Heating capacity,42=42000BTU/h
Product type : “B” stands for cassette type, “C” stands for convertible
type, ”D” stands for duct, “S” stands for split type, ”Q” stands for chiller
system, "E" stands for ceiling concealed type, “U” stands for outdoor unit
Air conditioner
-2-
DESCRIPTION OF PRODUCTS & FEATURES
-3-
SPECIFICATIONS
2 SPECIFICATIONS
Item Model HBU-14H03
Function Cooling Heating
Capacity BTU/h 14000 16000
Total power input W 1500 1500
EER or COP BTU/W 9.3 10.6
Dehumidifying capacity 10‐³×m³/h 1
Power source PH-V-Hz 1PH, 220V-230V, 50HZ
Running current/Starting current A 9.52/48.5 /
Power cable /
Unit model (color) AB142ACAAA/ WHITE
Fan Type × Number CENTRIFUGAL×1
Speed r/min 840/650/560
Air-flow(H-M-L) m³/h 830
Heat exchanger Type / Diameter TP2M/9.52
Flow 2/2
Indoor unit
Flow 2/2
Total area m² 0.534
Temp. scope 43-60
Dimension External mm×mm×mm 780×250×660
L×W×H Package mm×mm×mm 907×344×690
Drainage pipe (material , I.D./O.D.) PVC,32
Refrigerant control method Capillary
Defrosting Auto
Noise level H-M-L dB(A) 49/-/
Four way valve /
Weight (net / gross) kg 40/48
Refrigerant Type R22
Charge kg 1.95
Pipe Liquid mm 6.35
Piping
Gas mm 15.88
Connect method FLARED
Between Drop m MAX :5
I.U. & O.U. Piping length m MAX :15
-4-
SPECIFICATIONS
Flow 2/2
Total area m² 0.297
Temp. scope 43-60
Dimension External mm×mm×mm 810×288×680
L×W×H Package mm×mm×mm 900×406×760
Drainage pipe (material , I.D./O.D.) PVC,18/20
Refrigerant control method Capillary
Defrosting Auto
Noise level H-M-L dB(A) 52/-/46
Four way valve /
Weight (net / gross) kg 58/66
Refrigerant Type R407C
Charge kg 1.85
Pipe Liquid mm 6.35
Piping
Gas mm 15.88
Connect method FLARED
Between Drop m MAX :5
I.U. & O.U. Piping length m MAX :15
-5-
SPECIFICATIONS
Flow 3/3
Total area m² 0.62
Temp. scope 43-60
Dimension External mm×mm×mm 948×830×340
L×W×H Package mm×mm×mm 1050×979×440
Drainage pipe (material , I.D./O.D.) PVC,18/20
Refrigerant control method Capillary
Defrosting Auto
Noise level H-M-L dB(A) 58/-/50
Four way valve /
Weight (net / gross) kg 74/89
Refrigerant Type R22
Charge kg 2.5
Pipe Liquid mm 9.52
Piping
Gas mm 15.88
Connect method FLARED
Between Drop m MAX :15
I.U. & O.U. Piping length m MAX : 30
-6-
SPECIFICATIONS
Flow 3/3
Total area m² 0.62
Temp. scope 43-60
Dimension External mm×mm×mm 948×830×340
L×W×H Package mm×mm×mm 1050×979×440
Drainage pipe (material , I.D./O.D.) PVC,18/20
Refrigerant control method Capillary
Defrosting Auto
Noise level H-M-L dB(A) 58/-/50
Four way valve /
Weight (net / gross) kg 70/85
Refrigerant Type R22
Charge kg 2.5
Pipe Liquid mm 9.52
Piping
Gas mm 15.88
Connect method FLARED
Between Drop m MAX :15
I.U. & O.U. Piping length m MAX : 30
-7-
Type HBU-36H03 Appearance color (indoor/outdoor unit) White/white
Cold producing capacity 36000BTU Heat producing capacity 39000BTU
Cold producing coefficient 2.85w/w Heat producing coefficient 3.17w/w
Cold producing power 3700W Heat producing power 3600W
-3 3
Defrosting capacity 4.5×10 m /h Ratio of energy generating to consuming -------------
Package dimension of indoor unit 920x1325x370 mm Package dimension of outdoor unit 1050x440x1375mm
See to the
Installation motherboard dimension Layer restriction of laminated indoor and outdoor unit 4/2
installation figure
Net weight/gross weight of indoor unit 46/53 kg Net weight/gross weight of outdoor unit 88/108 kg
Maximum installation fall 30m Current-in side (indoor/outdoor) -------------
Allowable infusing quantity of refrigerant 3200g Maximum infusing quantity of refrigerant -------------
Cleanout frequency of filter Once per month Type of filter (filer screen) -------------
Filtration efficiency ------------- Dimension of filter (filter screen) -------------
Type of air compressor H23A46QDBEA Manufacturer of air compressor Bristol
Oil inpouring volume to air compressor 1480cc Type of air compressor protector 32HM65-112
Cut off valve type φ9.52; φ19.05 Four-way valve type STF-0408
Dimension of air-in grid shaking flake ------------- Quantity /space of air-in grid shaking flake 4
Length of maximum connecting pipe of unit 50m Total length of refrigerating pipe circuit (liquid /gas) -------------
Drainage pipe type PVC Length/ diameter of drainage pipe φ25(inside); φ32(outside)
Flow value of evaporator and condensator 10/8 Type /diameter of evaporator and condensator pipe TP2 Mφ9.52; φ19.05
Total fin quantity /its row number 2/1320;2/446 Thickness /space of fin 0.11/1.9
Fin coefficient ------------- Fin material kind Light foil
Type of capillary TP2 Y Diameter /length of capillary -------------
Protector type on control panel 3.25A Temperature sensor type 10KΩ 23KΩ 5KΩ
Real-time adjustment scope ------------- Consumed power capacity Indoor:130WOutdoor:60x2
Type of accessories on computer board See to attachment Type of segregator for gas and liquid 5.0L
Indoor: 590/490/420 Indoor: centrifugal/1
Rotating speed of air fan Type /quantity of air fan
Outdoor:840 Outdoor:axial-flow/2
Flow 5/5
Total area m² 0.92
Temp. scope 43-60
Dimension External mm×mm×mm 948×1225×340
L×W×H Package mm×mm×mm 1050×1375×440
Drainage pipe (material , I.D./O.D.) PVC,25/32
Refrigerant control method Capillary
Defrosting Auto
Noise level H-M-L dB(A) 64/-/-
Four way valve /
Weight (net / gross) kg 85/111
Refrigerant Type R22
Charge kg 3.82
Pipe Liquid mm 9.52
Piping
Gas mm 19.05
Connect method FLARED
Between Drop m MAX :30
I.U. & O.U. Piping length m MAX : 50
-9-
SAFETY PRECAUTIONS
3 SAFETY PRECAUTIONS
Please read these "Safety Precautions" first then accurately execute the installation work.
Though the precautionary points indicated herein are divided under two headings, WARNING and
CAUTION those points which are related to the strong possibility of an installation done in error
resulting in death or serious injury are listed in the WARNING section. However, there is also a
possibility of serious consequences in relationship to the points listed in the CAUTION section as well.
In either case, important safety related information is indicated, so by all means, properly observe all that is mentioned.
After completing the installation, along with confirming that no abnormalities were seen from the operation tests, please
explain operating methods as well as maintenance methods to the user (customer) of this equipment, based on the owner's
manual.
Moreover, ask the customer to keep this sheet together with the owner's manual.
WARNING
This system should be applied to places of office, restaurant, residence and the like. Appliaction to inferior
environment such as engineering shop could cause equipment malfunction.
Please entrust installation to either the company which sold you the equipment or to a professional contractor.
Defects from improper installations can be the cause of water leakage, electric shocks and fires.
Execute the installation accurately, based on following the installation manual. Again, improper installations can
result in water leakage, electric shocks and fires.
When a large air-conditioning system is installed to a small room, it is necessary to have a prior planned
countermeasure for the rare case of a refrigerant leakage, to prevent the exceeding of threshold concentration.
In regards to preparing this countermeasure, consult with the company from which you purchased the equipment,
and make the installation accordingly. In the rare event that a refrigerant leakage and exceeding of threshold
concentration does occur,there is the danger of a resultant oxygen deficiency accident.
For installation, confirm that the installation site can sufficiently support heavy weight. When strength is insufficient,
injury can result from a falling of the unit.
Execute the prescribed installation construction to prepare for earthquakes and the strong winds of typhoons and
hurricanes, etc. Improper installations can result in accidents due to a violent falling over of the unit.
For electrical work, please see that a licensed electrician executes the work while following the safety standards
related to electrical equipment, and local regulations as well as the installation instructions, and that only exclusive
use circuits are used.
Insufficient power source circuit capacity and defective installment execution can be the cause of electric shocks and
fires.
Accurately connect wiring using the proper cable, and insure that the external force of the cable is not conducted to
the terminal connection part, through properly securing it. Improper connection or securing can result in heat
generation or fire.
Take care that wiring does not rise upward, and accurately install the lid/service panel. Its improper installation can
also result in heat generation or fire.
- 10 -
SAFETY PRECAUTIONS
WARNING
When setting up or moving the location of the air conditioner, do not mix air etc. or anything other than the designated
refrigerant (please see nameplate) within the refrigeration cycle.
Rupture and injury caused by abnormal high pressure can result from such mixing.
Always use accessory parts and authorized parts for installation construction. Using parts not authorized by this
company can result in water leakage, electric shock, fire and refigerant leakage.
The position of indoor unit must be above the floor 2.5m.
CAUTION
Execute proper grounding. Do not connect the ground wire to a gas pipe, water pipe, lightening rod or a telephone
ground wire.
Improper placement of ground wires can result in electric shock.
The installation of an earth leakage breaker is necessary depending on the established location of the unit. Not
installing an earth leakage breaker may result in electric shock.
Do not install the unit where there is a concern about leakage of combustible gas.
The rare event of leaked gas collecting around the unit could result in an outbreak of fire.
For the drain pipe, follow the installation manual to insure that it allows proper drainage and thermally insulate it to
prevent condensation. Inadequate plumbing can result in water leakage and water damage to interior items.
- 11 -
NET DIMENSIONS OF INDOOR AND OUTDOOR UNIT
- 12 -
NET DIMENSIONS OF INDOOR AND OUTDOOR UNIT
75 362 270
45
92
18 122
2 40 5
104
30 35
90
660
131
113
170
32
270
48
30
70
660
Model: HBU-18HC03 Outdoor unit
110 480
190 265 30
170
200
680
220
75
400
65
150
100 100
810
580
288
NET DIMENSIONS OF INDOOR AND OUTDOOR UNIT
860-890 (天花板开孔)
(天花板开孔)
(悬挂位置)
860-890
780
950
840 55 840 55
295
240
260
180
180
160
135
155
20
50
30
安装所需位置
1000 以上
上
以
00
15
15
00以
上
上
00以
15
15
00以
上
NET DIMENSIONS OF INDOOR AND OUTDOOR UNIT
70
18
55
340
380
70
18
Screw Hole
(M10)
1024
70
Power Wiring Terminal
Power Wiring
840
Distribution Hole
25
- 15 -
NET DIMENSIONS OF INDOOR AND OUTDOOR UNIT
860-890
950
780
615
840 55 1230 55
295
300
50 280
220
220
155
135
160
20
30
260
1000mm
270
315
over
00
15
er
ov
ov
er
15
00
00
15
er
ov
ov
er
15
00
- 16 -
NET DIMENSIONS OF INDOOR AND OUTDOOR UNIT
70 30
18
52
380
340
88
18
Screw Hole
(M10)
950
25
- 17 -
INSTALLATION INSTRUCTIONS
5 INSTALLATION INSTRUCTIONS
Part name 1 Clamp 2 Washer 3 Clamp 4 Drain hose 5 Paper pattern 6 Screw(M5 size)
For installation
of
Shape paper pattern
Part name 7 Insulator 8 Insulator 9 Dry battery 10Sealing pad 11 Sealing pad 12 Sealing pad
[Other]
QTY 1 Piece 1 Piece 2 Piece 1 Piece 1 Piece 2 Piece
Operation
For gas pipe For liquid pipe R03, 7# Large size Medium size Small size Manual
Shape Ornament
panel
Remote
controller
- 18 -
INSTALLATION INSTRUCTIONS
260
260
2500 Over
5.3.3 Preparation
(1) Position of ceiling opening between unit and suspending bolt. Unit: mm
HBU-14
Ornament panel 630mm
210mm
335mm
Distance between Ceiling
Ornament panel
35mm
suspending bolts 460mm
HBU-18
260mm
Ceiling
Ornament panel
- 19 -
INSTALLATION INSTRUCTIONS
HBU-24,28
(Distance between suspending bolts)
890(Ceiling opening)
950(Ornament panel)
Refrigerant pipe
840(Indoor unit)
780
Suspending bracket
Suspending bolts
(160)
A (Distance between suspending bolts) Ceiling
A
840(Indoor unit)
890(Ceiling opening)
950(Ornament panel)
HBU-36,42
890(Ceiling opening)
1070 (Distance between suspending bolts) Note:
515 Dimension of ceiling opening marked with * can be as
large as 910mm, but the matching part of ceiling with
ornament panel shall be over 20mm.
780(Distance between suspending bolts)
860(Ceiling opening)
20 Over
515
(2) Cut an opening in ceiling for installation if necessary. (when ceiling already exists.)
Refer to paper pattern for dimension of ceiling hole.
Connect all pipings (refrigerant, water drainage), wirings (inter unit cable) to indoor unit, before
installation.
Cut a hole in ceiling, may be a frame should be used to ensure a smooth surface and to prevent
vibration. Contact your real estate dealer
(3) Install a suspending bolt.
(Use a M10 bolt)
To support the unit weight, anchor bolt shall be used in the case of already exists ceiling. For new
ceiling, use built-in type bolt or parts prepared in the field.
Before going on installing adjust space between ceiling.
<Installation example>
Roof
Anchor bolt
Long nut
50~100
Suspending bolt
Ceiling Note: All the above mentioned parts shall be prepared in field.
- 20 -
INSTALLATION INSTRUCTIONS
5.3.4 Installation
In the case of new ceiling
(1) Install unit temporally
Put suspending bracket on the suspending bolt. Be sure to use nut and washer at both ends of the bracket.
(2) As for the dimensions of ceiling hole, see paper pattern. Ask your real estate dealer for details.
Center of the hole is marked on the paper pattern.
Center of the unit is marked on the card in the unit and on the paper pattern.
Mount paper pattern 4 onto unit using 3 screws 5 . Fix the corner of the drain pan at piping outlet.
< After installation on the ceiling >
(3) Adjust unit to its right position. (Refer to preparation for the installation-(1))
(4) Check unit's horizontal level.
Watert pump and flating switch is installed inside indoor unit, check four corners of the unit for its level using
horizontal compartor or PVC tube with water. (If unit is tilting against the direction of water drainage, problem
may occur on floating switch, causing water leakage.)
(5) Remove the washer mounlting 7 , and tighten the nut above.
(6) Remove the paper pattern.
In the case of ceiling already exists
(1) Install unit temporally
Put suspending bracket on the suspending bolt. Be sure to use nut and washer at both ends of the
bracket. Fix the bracket firmly.
(2) Adjust the height and position of the unit. (Refer to preparation for the installation (1) ).
(3) Proceed with 3 and 4 of "In the case of new ceiling".
Scrtews at the piping outlet is fixed at the corner
of drain pan.
Level
Polythene pipe
(333~407kgf.cm)
90 0.5
45
6180~7540N.cm
A
9720~11860N.cm
Insulator (accessory) 7 19.05 22.9~23.3
spanner (990~1210kgf.cm)
(For liquid pipe)
Insulator (accessory) 6
Diameter of Pipe Tighten Torque
Piping joing Gas pipe (For gas pipe)
Liquid pipe Liquid Pipe 6.35mm 18 N. m
Flare nut
Gas Pipe 12.7mm 50N. m
- 21 -
INSTALLATION INSTRUCTIONS
1-1.5m
Use the self-provided stiff pipe and clip 2 with unit. Insert water pipe into water plug until it reaches the white tape.
Tighten the clip until head of the screw is less than 4mm from hose.
Wind the drain hose to the clip using seal pad 8 . Large size seal pad 10
Insulate drain hose in the room. (accessory)
Clip 2
Clip 2
(accessory)
500 below
Drain hose 1 (accessory)
220 280 below
75 below
500 below
Clip 2
(accessory)
(Note)
The slope of water drain hose (1) shall be within 75mm, don't apply too much force on it.
If several water hoses join together, do as per following proceedures.
Connect water hoses with a T joint.
Over 100
Specifieations of the water hoses shall meet the requirements for the unit running.
(2) Check if water drainage is smooth after installation.
Charge, through air outlet or inspecting hole, 1200ccd water to see water drainage.
After wiring
Check water drainage in cooling operation. See also 11 test run.
When wiring is not complete
Remove cover of control box, short connect "CHECK" terminal of the indoor unit, which is on the uper
part of indoor unit PCB. Connect 1PH power to terminal 1 and 2 on terminal block.
Note, in this operation, fan will be running.
Upon confirmation of a smooth water drainage, be sure to cut off power supply andremove short
connection of "CHECK" terminal. Indoor
1 2 3
Method of water charging
Self-provided stiff pipe Maintenance
H05RN-F 2
Connect with 4G 0.75mm
outdoor unit Terminal block
Water drainage port for
maintenance Inspecting hole
L N 1 2 3
(Drain water from
this hole) Outdoor
PCB on indoor Power
Indoor
Terminal
H07RN-F2
3G 4mm 1 2 3
H05RN-F 2
100mm Charge water from 4G 0.75mm
inspecting hole
5.3.7 Wiring
All supplied parts. materials and wiring operation must in appliance with local code and regulations.
Use copper wire only.
When make wiring, please refer to wiring diagram also.
All wiring work must be done by qualified electricians.
A circuit breaker must be installed, which can cut power supply to all system.
See Installation Manual of outdoor unit for specifications of wires, circuit breaker, switches and wiring etc.
Connecting of unit
Remove cover of switch box (1) , drag wires into rubber tube A, then, after proper wiring with other wires,
tighten clamp A. Connect wires of correct pole to the terminal block inside.
Wind seal (12) around wires. (Be sure to do that, or, dew may occur).
Upon connecting, replace control box cover (1) and (2).
<<WARNING>>
Connect wires of the sameDon't connect wires of the
Obscrve the following when connecting power supply terminal block: Don't connect wires of the
Don't connect wires of different specifications to the same specifications at two sides.same specifications at one side.
different specifications.
terminal block.
(Loose wire may cause overheating of circuit)
Connect wires of same specifications as shown in right Fig.
- 23 -
INSTALLATION INSTRUCTIONS
45
Fig. 3
2. Install ornament panel on indoor unit.
For indoor unit installation, please refer to Installation Manual. Fig. 2
Hook
(1) As shown in Fig . 7, match the position of Holding ring 1
swing flap motor with that of the indoor unit 2 Piping hole position
piping hole , so that ormament panel can be
placed on to indoor unit.
(2) Installation of ornament panel
1 Place the holding ring on swing flao motor 2
a b
50 100
- 24 -
INSTALLATION INSTRUCTIONS
Fig. 11 Fig. 12
- 25 -
INSTALLATION INSTRUCTIONS
380
256
288
140 500 140 115 580 115 185 580 185
2
Open the handle at low in gaugemanifold, operate
vacuum pump. If the scale-moves of gause (low) 2 Open Vacuum pump
reach vacuum condition in a moment, check 1 again.
3
Vacuumize for over 15min. And check the level
gauge which should read -0.1 MPa (-76 cm Hg)
at low pressure side. After the completion of
vacuumizing, close the handle 'Lo' in gaugemanifold
and stop the operation of the vacuum pump.
Check the condition of the scale and hold it for
1-2min. If the scale-moves back in spite of
tightening, make flaring work again, the return
to the beginning of 3 .
- 26 -
INSTALLATION INSTRUCTIONS
4
Open the valve rod for the 2-way valve to and
2way V.
angle of anticlockwise 90 degree.
After 6 seconds later, close the 2-way valve and 3way V.
male the inspection of gas leakage. 90°
Service port
4 90° for 6 sec.
6 2way V.
Detach the charge hose from the service port, open 6
2-way valve and 3-way. Turn the valve rod 3way V.
anticlockwise until hitting lightly. 6
3
7
To prevent the gas leakage, turn the service port's
cap, the valve rod'd cap for 2-way valve and 3-way's
a lottle more than the point where the torque increases
suddenly.
2way V.
8 3way V.
After attaching the each caps, check the gas leakage
around the caps. 7 Valve rod cap
If needing to remove the refrigerant gas when installation or repair , please refer to the
following procedures:
1. Cut off the power
2. (After confirming the power is cut off) pull the power cable plug terminals of the low-pressure
pressure-switch out.
3. (After confirming the power cable terminals of the low-pressure pressure-switch is cut off) After
powering on the unit again and switch to COOLING mode,perform refrigerant gas removing
according to the normal refrigerant gas removing procedure.
4. After finishing refrigerant gas removing , cut off the power , then insert the power cable terminals
of the low-pressure pressure-switch properly.
- 27 -
INSTALLATION INSTRUCTIONS
5.5 Pay special care to the following and check after installation
Item to the checked Unproper installation may cause Check
Is indor indoor unit firmly installed? Unit might fall down, make vibration or noise.
Is gas leakage dheck performed? This may lead to gas shortage.
Is unit properly insulated? Dew or water drop may occur.
Is water drainage smooth? Dew or water drop may occur.
Is power voltage meet that stipulated on the nameplate? Problem may occur or parts got burned.
Is wiring and piping correctly arranged? Problem may occur or parts got burned.
Is unit safely grounded? There might be a danger of electric shock.
Is wire size correct? Problem may occur or parts got burned.
Are there any obstacles on air inlet and outlet grill of This may cause poor cooling.
indoor and outdoor unit?
Is record made for piping length and refrigerant It is hard to control refrigerant charging
charging amount? amount.
- 28 -
PARTS AND FUNCTIONS
Indoor unit
Swing louver
(Air flow direction can be adjusted by using
the SWING button on the remote controller)
Back up switch
18 series
- 29 -
PARTS AND FUNCTIONS
Swing fender
(located in the outlet)
Refrigerant pipe
Cable line
Outlet Earthing line
Air filter
(located in the suction grill)
Remote Controller
Suction grill
24,28,36,42 series
Outdoor unit
Air Outlet
(blow out hot air when cooling
and cool air when heating)
14 series
- 30 -
PARTS AND FUNCTIONS
Air inlet
Compressor(inside of unit)
Air outlet
18 series
Air inlet
Air inlet
Air outlet
Air outlet
Compressor
(Inside of unit)
Compressor
(Inside of unit)
- 31 -
REMOTE CONTROLLER FUNCTIONS
SWING
Used to set auto fan AUTO FAN
direction.
Used to select fan speed:
LO, MID, HI, AUTO
ON OFF
MODE AM
PM
AM
PM
CLOCK
MODE
Used to set correct time. SLEEP
CLOCK SET Used to select sleep
mode.
TIMER SLEEP
TIMER
LOCK RESET
Used to select
TIMER ON, TIMER OFF, HOUR
TIMER ON/OFF.
Used to set clock and
timer setting.
LOCK RESET
Used to lock buttons Used to reset the controller
and LCD display. back to normal condition.
Cautions: Note:
On cooling only unit, heating mode is not available. 1. The above information is the explanation of
After replacing batteries, press ON/OFF, and display the displayed information therefore varies
becomes as follows: with those displayed in actual operation.
Operation mode: AUTO, Temp: 24 C 2. This type only has the relevant function and
Timer mode: No, Fan speed: AUTO display as indicated in the above figure.
REMOTE CONTROLLER FUNCTIONS
HEAT
DRY
FAN OPERATION
COOL AUTO
AUTO AM
ON
AM
OFF
SIGNAL SENDING
PM PM
TEMP.
SWING TEMP
ON
SWING OFF FAN
FAN SPEED CLOCK
LO MODE
MID
LOCK
CLOCK SET
TIMER SLEEP
HI AUTO TIMER OFF
AUTO LOCK RESET
TIMER ON
SLEEP
Clock set
When unit is started for the first time and after replacing batteries in remote controller,
clock should be adjusted as follows:
Press CLOCK button, "AM" or "PM" flashes.
Press or to set correct time. Each press will increase or decrease 1min. If the
button is kept depressed, time will change quickly.
After time setting is confirmed, press SET, "AM "and "PM" stop flashing, while clock
starts working.
Hints
After replacing with new batteries, remote controller will conduct self-check, displaying
all information on LCD. Then, it will become normal.
REMOTE CONTROLLER FUNCTIONS
When in use, put the signal transmission head directly to the receiver hole on the indoor unit.
The distance between the signal transmission head and the receiver hole should be within 7m
without any obstacle as well.
Don't throw the controller, prevent it from being damaged.
When electronic-started type fluorescent lamp or change-over type fluorescent lamp or wireless
telephone is installed in the room, the receiver is apt to be disturbed in receiving the signals so
the distance to the indoor unit should be shorter.
Be sure that the loading is in line with the " + " / " - " pole request as CLOCK SET
Note :
Use two new same-typed batteries when loading.
If the remote controller can't run normally or doesn't work at all,
use a sharp pointed item to press the reset key.
Hint : Remove the batteries in case unit won't be in usage for a long period.
If there is any display after taking-out just need to press reset key.
REMOTE CONTROLLER FUNCTIONS
GUIDE TO OPERATION
FAN operation
(1) Unit start
Press ON/OFF button, unit starts.
Previous operation status appears on display.
(Not Timer setting)
Power indicator on indoor unit lights up.
Hints
Remote controller can memorize settings in each operation mode. To run it next
time just select the operation mode and it will start with the previous setting.
No reselecting is needed.(TIMER ON/OFF needs reselecting)
REMOTE CONTROLLER FUNCTIONS
GUIDE TO OPERATION
TIMER SLEEP
LOCK RESET
Hints
Remote controller can memorize each operation status. When starting it next time,
just press ON/OFF button and unit will run in previous status.
REMOTE CONTROLLER FUNCTIONS
GUIDE TO OPERATION
LO MID HI AUTO
AUTO
In HEAT mode, warm air will blow out after a short period
of time due to cold-draft prevention function. Temp. setting+2 C
Temp. setting
In DRY mode, when room temp. becomes 2 C higher than
temp. setting, unit will run intermittently at LO speed On reaching temp. setting,unit
will run in mild DRY mode.
regardless of FAN setting.
Hints
As cold air flows downward in COOL mode, adjusting air flow horizontally will be much more
helpful for a better air circulation.
As warm air flows upward in HEAT mode, adjusting air flow downward will be much more
helpful for a better air circulation.
Be careful not to catch a cold when cold air blows downward.
It is harmful to your health in summer to go frequently in and out of places where temp.difference
is above 7 C . Temp. difference of 3-5 C will remove your fatigue.
More than this, unit's load can be reduced and power consumption cut down as well. So, you'd
better set a temp. diff of 3-5 C between indoor and outdoor temp. in COOL mode.
REMOTE CONTROLLER FUNCTIONS
GUIDE TO OPERATION
TIMER operation
Set Clock correctly before starting Timer operation(refer to page 6)
You can let unit start or stop automatically at following times: Before you wake up in the
morning, or get back from outside or after you fall asleep at night.
TIMER ON/OFF
(1)After unit start, select your desired operation mode.
Operation mode will be displayed on LCD.
Power indicator on indoor unit lights up.
Hints
After replacing batteries or a power failure happens, Time setting should be reset. Remote
controller possesses memory function, when use TIMER mode next time, just press SET
button after mode selecting if timer setting is the same as previous one.
REMOTE CONTROLLER FUNCTIONS
GUIDE TO OPERATION
TIMER ON-OFF
(1)After unit start, select your desired operation mode
Operation mode will be displayed on LCD.
Power indicator on indoor unit lights up.
SWING No indication
(louver stopped)
Comfortable Sleep
At night, before going to bed you can press down the SLEEP button
on the controller and the air-conditioner will run by the comfortable
sleeping mode to make you sleep more comfortable.
Press SLEEP button once to make the air conditioner have the
previous-set sleep time (first power-on is "1h"), the sleep symbol will
appear. Press time button / , you can choose the time in 1~8
hours. Each press of / , the time increases/reduces 1 hour and
"xh" appears in the humidity setting part, "OFF" appears in "TIMER AM
OFF
OFF" display part and timer-off time; press SLEEP button again to
cancel sleep function, the sleep symbol diappears.
TEMP
In cooling, dehumidifying mode ON
One hour after sleeping operation start, the temp. is 1 C higher than SWING OFF FAN
the setting one. After another hour the temp. rises 1 C and then run
continuously for another 6hrs' and then close. The actual temp. is MODE
higher than the setting one which is to prevent from being too cool
to your sleep.
CLOCK SET
TIMER SLEEP
In heating mode
One hour after start up, the temp. decrease 2 C lower than the LOCK RESET
setting one. After another hour decrease by more 2 C.
The temperature will automatically rise by 1 C after another 3hrs'
operation, and then automatically close after 3hrs' continuous
operation. The actral temperature is lower than the setting one which
is to prevent from being too hot to your sleep.
Note:
In AUTO mode, unit will run in SLEEP function according to the operation mode.
After setting SLEEP function, it is forbidden to calibrate clock.
If the set sleep-time does not reach 8 hours, the unit will stop operation automatically
after set time is complete.
Set "TIMER-OFF" function first, then set SLEEP, and press the sleep-set-performance;
set TIMER-ON function first, the sleep function can only be set before TIMER-ON; if set
the SLEEP function first, the TIMER function can not be set.
After setting SLEEP, press CLOCK button to show the time; press TEMP. button to
show the temperature; press again to change temperature.
When the set SLEEP time is 8 hours, connect it as shown in the following figure.
1 hr about 6 hrs
decrease 2 C
1 hr increase 1 C
decreases 2 C 1 hr
about 3 hrs
increase 1 C
1 hr
3 hrs increase1 C
SETTING T SHUT DOWN
SLEEP RUN BEGINS SLEEP RUN STOPS
Remote Control:
There is a telecommunication interface for remote control on the control panel of the
indoor unit. After the peripheral equipment have been installed in accordance with the
instruction manual of the selected remote control detector, the air conditioner will be
computerized and controlled from a far-away place.
15
REMOTE CONTROLLER FUNCTIONS
22
After air conditioner operated for a period, dusts were
25
gradually accumulated on the filter ,and the filter up/down
26 21
20
function can be used to clean the filter.
27
28 AUTO
19 1.Whether unit start or stop, continuously press FILTER
18
29 button 3 seconds,and enter into the filter up/down waiting
30 C 17
status (when unit stops,the yellow TIMER indicator flashes,
31
ON OFF 16
filter and clock displayed on the remote controller and no
32 15 others.Only the FILTER button and the temperature button
1 “ ” “ ” and time button “ ” “ ” are active).
TEMP
2 ON
OFF
14 2.Press temperature “ ” button or time “ ” button in filter
SWING FAN
3 up/down waiting status, the up/down mechanism makes
the filter to move downward and do not stop until reach
4 MODE FILTER 13
the maximum limit.
Note:
If the filter does not thoroughly back to the original position,only need to
operate several times repeatedly.
- 43 -
REMOTE CONTROLLER FUNCTIONS & REFRIGERANT DIAGRAM
TEMP 3.PLEASE
WHEN
REMOVE
THE REMOTE
THE BATTERIES
CONTROLLER
DISORDER AND RELOAD NEW'S
ON
180
22 58
8 REFRIGERANT DIAGRAM
Filter
Capillary tube
Heat exchanger
Heat exchanger
Compressor
Accumulator
- 44 -
ELECTRICAL CONTROL FUNCTIONS
e
Cooling
Blowing
Blowing
Ts-3
- 45 -
ELECTRICAL CONTROL FUNCTIONS
High speed
Ts 3
High speed
Ts 2 Medium speed
Medium speed Ts 1
rising
Temperature
Low peed
Ts
Low speed
b. During heating program applicable for cooling-heating type , conversion of wind speed
from the low to high won’t work until the present speed has continued for 3 minutes while
conversion from the high to low needs no time delay. The hart below is the sketch map of
conversion:
falling
Temperature
Low speed
Low speed Ts
Ts 1 Medium speed
Medium speed Ts 2
rising
Temperature
Ts 3 High speed
High speed
- 46 -
ELECTRICAL CONTROL FUNCTIONS
blowing fan runs at setting wind speed. This working area is defined as area A.
(2) Ts Tr Ts + 2 , the compressor and outdoor blowing fan run for 10 minutes then
pause for 6 minutes, while indoor blowing fan runs at low wind speed. This working
area is defined as area B.
(3) Tr < Ts, the compressor and outdoor blowing fan stop working while outdoor blowing
fan runs at low wind speed. This working area is defined as area C.
a. After dehumidifying program starting, the system converts between A, B and C areas
according to variations of room temperature with running mode being shown as the chart
below:
falling
temperature
Room
Area A
Area A Ts 3
Ts 1
Area B
rising
temperature
Room
Area B Ts
Ts 1
Area C
Area C
- 47 -
ELECTRICAL CONTROL FUNCTIONS
- 48 -
ELECTRICAL CONTROL FUNCTIONS
CN11
PC board A-
1
A+
2
- 49 -
ELECTRICAL CONTROL FUNCTIONS
Come to defrost
Compressor
Condition off or 55s?
E-Heat off for 30s?
for
compressor Return
OFF Operation indoor
fun motor
Return
4-way value
ON
Turn off compressor Return
outdoor fun
OFF
compressor
Compressor
ON ?
Turn off for
55s?
Return
Compressor Return
ON
Return
- 51 -
DIAGNOSTIC INFORMATION (TROUBLE SHOOTING)
Flash time of
compressor
No. Code Trouble contents (new)
running indicate
lamp
1 E0 10 drainage system trouble
2 E1 1 indoor temperature sensor broken
3 E2 2 indoor coil temperature sensor broken
4 E3 3 outdoor temperature sensor broken
5 E4 4 outdoor coil temperature sensor broken
6 E5 5 over current protect limit
7 E6 6 pressure protect
8 E7 7 three phase protect
Communication trouble between wired remote controller
9 E8 8
and indoor unit
10 E9 9 communication trouble between indoor and outdoor unit
- 52 -
Trouble Checkup result Possible reasons Corresponding solution
Unavailable voltage at input part of The power supply coil isn’t plugged
Plug the supply coil properly
circuit board well
Return to the controller manufacturer for
Unavailable voltage at one end of Damaged wave filtering component
repair
the fuse
No response after Damaged fuse Replace with a good one
power being Unavailable output from the The transformer isn’t plugged well or Plug the transformer well or replace with a
connected consequent pole of transformer is damaged good one
Damaged component on power Return to the controller manufacturer for
Improper output of 7805
supply unit of indoor board repair
Normal power supply for major Return to the controller manufacturer for
Damaged major chip
chip repair
Damaged connection cable between
Replace with a good connection cable
display board and indoor board
Indicator lamps do not light Connection cable between display
Display board does board and indoor board isn’t Connect the cable well
not make normal connected well
response
Damaged reception adaptor Replace with a good one
- 53 -
Remote control cannot be received Return to the controller manufacturer for
Damaged remote circuit or major chip
repair
10.2 Trouble shooting - Detailed for engineer
- 54 -
memory mode.
Unavailable power Return to the controller manufacturer for
Damaged chip IC6 of indoor board
breakdown memory repair
No output at 18 pin of 2803 Damaged 2803 Replace with a good 2803
No output of
four-way valve No output of relay JK7 on indoor
Damaged relay JK7 Replace with a good JK7
during heating board
program Available output of relay JK7 on Socket CN6 is not plugged well with Plug CN6 and the connection cable well
indoor board connection cable
- 55 -
conditions No output at 11 pin of 2803 of
Damaged 2803 Replace with a good 2803
indoor board
During heating program, No output of relay JK6 on indoor
the compressor does not Damaged relay JK6 on indoor board Replace with a good JK6
board
start when the
Available output of relay JK6 on Connection cable between compressor
temperature meet proper Plug the connection cable well
indoor board and JK6 isn’t plugged well
conditions
No output at collector of Q2 on
Damaged Q2 Replace with a good Q2
indoor board
During cooling program,
the compressor works No output of relay JK8 on indoor
Damaged relay JK8 on indoor board Replace with a good JK8
while outdoor blowing board
fan does not
Available output of relays on Socket CN6 is not plugged well with
Plug the connection cable well
indoor board connection cable
DIAGNOSTIC INFORMATION (TROUBLE SHOOTING)
Trouble Checkup result Possible reasons Corresponding solution
During heating program, It will automatically restore when
the compressor work while Too high temperature of indoor coil pipe
the temperature of indoor coil
outdoor blowing fan does causes overheat protection
pipe falls to 57
not
No output at collector of Q2 on
Damaged Q2 Replace with a good Q2
indoor board
During heating program, No output of relay JK8 on indoor
the compressor work while Damaged relay JK8 on indoor board Replace with a good JK8
board
outdoor blowing fan does Available output of relays on Socket CN6 is not plugged well with
not Plug the connection cable well
indoor board connection cable
Current transformer outputs Return to the controller
Damaged rectification diode D6-D7 etc.
normally manufacturer for repair
Transformer CT1outputs
Abnormal overcurrent Damaged transformer CT1 Replace with a good one
abnormally
detection
Inaccurate protection current Adjust the adjustable potentiometer
Return to the controller
Damaged major chip
manufacturer for repair
- 56 -
With timing indicator and
compressor indicator
extinguishing, the Damaged indoor temperature sensor Replace with a good one
operation indicator flashes
every second
With timing indicator and
compressor indicator
Damaged temperature sensor for indoor
lighting, the operation Replace with a good one
coil pipe
indicator flashes every
second
No output at 13 pin of 2803 on
Damaged 2803 Replace with a good 2803
indoor board
Water pump indicator No output of relay JK6 on indoor
Damaged relay JK4 on indoor board Replace with a good JK4
flashes every second board
(trouble for water Available output of relay JK6 on Socket CN5 is not plugged well with Plug the connection cable well
discharging) indoor board connection cable
Faulty connection cable to transmit float
Replace with a good one
feedback signal
DIAGNOSTIC INFORMATION (TROUBLE SHOOTING)
ELECTRICAL DATA
11 ELECTRICAL DATA
11.1 Wiring Diagram HBU-14H03
R: RED B: BLACK
W: WHITE BL:BLUE
BR: BROWN GR:GRAY
Y/G: YELLOW/GREEN
NOTE:
THE PART IN THE DASHED FRAME IS
OPTIONAL ELEMENT
0010570854
OUTDOOR WIRING DIAGRAM
R: RED B: BLACK
W: WHITE BL:BLUE
BR: BROWN GR:GRAY
Y/G: YELLOW/GREEN
- 57 -
ELECTRICAL DATA
HBU-18HC03
- 58 -
ELECTRICAL DATA
HBU-24H03
- 59 -
ELECTRICAL DATA
HBU-36H03 HBU-42HD03
- 60 -
+5 +12 D11 4148 B2B-XH-A(red )
R36 10K DL1
+5 4 27
2 R35 CN2
DOOR R33 1
R34 LM358 R31 10K R30 1K +12
R39 10K Q5 10K IC7
10K 8
+12 9013 3 Q3
+12
B4B-XH-A(red ) C19 +5 R_Receive
11.2.1 Indoor unit
R19 R20
24C01
4 5 CN6
R37 C25 103
R38 5.1K 0.033uF120
+5 Q2 +5 D10 RC1
R2 5.1K C26 103 1K
IC1 R3 5.6K 9013 R17
10K 10K 10K
C15 1 42
C14 SDA Vcc
2 41 C27 103 Q1
103 SCL Select3 R18
XT 3 40
Power Select4 JK1
103 4 39 5.6K
Down/Up Select5 JQ1aP-12V
5 38 9013 BUZ
1/60 OutdoorFan
6 37
Select1 Valve CN8
7 36 IC3 2803
Model: HBU-14H03
Select2 Tel-Out
8 35 1 18
IR Compressor I8 Q8 JK2
LF
9 34 2 17
B7B-XH-A(white )
R_Recive Tel-In Buzzer I7 Q7 JQ1P-12V
10 33 3 15 MF
CompDisp Low I6 Q6
CN12 11 32 4 16
TimeDisp Middle I5 Q5 HF
12 31 5 14
RunDisp High I4 Q4
13 30 6 13 B6P-VH
PumpDisp Crankcase-Heat PUMP I3 Q3
+5 14 29 7 12 JK3
R8 10K FM FM Door-Sign DOOR FM I2 Q2 JQ1P-12V
15 28 8 11
PUMP 16 Pump 3 I1 Q1 PUMP
27 9 10 +12
- 61 -
Float SlaveHeat GND VCC
17 26 B2P3(blue)
CN11 R7 1K TEST CT
18 25
RESET ExchTH +5
104 C9 19 24 R16 RC2 CN5
Xin RoomTH JK4
20 23 +5 JQ1aP-12V
B3B-XH-A(red ) Xout Energency
OSC 21 22 +5 10K
GND Vref
0.033uF120
L1
R9 +5 TMP87PH46 C23
1K 104 101K JQ1aP-12V B2P3(white)
4148 4.7UF/50V
D9 L2 JK5
+5 D6 D8 R13 10K 331K C12
DB1 R15 RC3
CN4
R10 +5 C8 compressor
10K R11 102
EX TH
CT1 20K-1% out FM
T600D R4 1K R5 1K 10K
C16 C13 TM TH JK6
R6 G41-1A 0.033uF120
IC2 D5 D7 C10 C11 L3 331K
104 C17 910欧-1% B4B-XH-A(white )
4.7uF/50V
103 C18 R12 10K R14 CN1
4.7UF/50V 103 L
RV 201 20K-1%
C7 102
470UF/16V Check
7805
+5 +12 FUSE
3 1
Vout Vin B3B-XH-A(white )
RTB-1.5-2P 3.15A/250V
D2
GND
D1 T1
LX102
C6 C3 C4 VR
C2
2
104
C5
104 C1 HBU-14H03 HBU-14HA03/R1
D4 D3 550NR-14D
LX 0010400701
100UF/16V 2200UF/35V 0.1uF/275V 0.1uF/275V
CN3 CN9
ELECTRICAL DATA
ELECTRICAL DATA
8.Electrical diagram
HBU-18HC03
1 2 3 4 5 6 7 8
FQV UWYC
PGCFJEFC
DEF
QHY
SRCY DL2
+12
CN13
LM358
R27
46 IC5 4 2 10K
+12
A R28 LM358 1 DL1
B DL3 7 5
+12 8 10K 8 3 LN +12
C DL4 +12
R29 C21 +5
D D 10K
C25 +12
Y.S.J D
104 104 C
DL5
C20 R30
CN12 104 CN7
1K
VDD
+5 1 RX 42 R37
10K CN4
C26 FM
R36 2 TX 41 103 Q3
10K
Q4 9014
3 40 IC3
R35 9014 JK7 R23
2803
10K 4 39 1 18
+12 I8 Q8
2 17 47 C22
5 38 3
I7 Q7
15
I6 Q6 0.01UF/275
4 16
R34 6 37 5
I5 Q5
14
1k I4 Q4
6 13 JK5
7 36 R31
7
I3 Q3
12 W.F.J OF
I2 Q2
8 11
R22 8 35 5.6K
9
I1 Q1
10 H.X.F V
GNDVCC
10K 9 34 N
Q6
9014 10 33 JK6
+12
CN5
11 32
C 12 IC1 31
+5
JK3
C
+5 13 30 R1
R32 10K HF
10K 14 29 10K
XT 15 28
R33
J14 LF
JK2
+5 16 27
103
C24
17 TEST 26 MF
RESET
R21
18 25 N
10K
19 XIN 24 JK1
20 XOUT 23 C9 CN8
GND VREF22
+5 102
21
JK4
TMP87C846
R8
1K +5
10K
R19
L1 CN9
+5
R14
C19 101K
10K PUMP
B CN11 103 B
C7
+5
104
10K R16
+5 4148 R13 CN2
R17 1K
DB1 D5 1K 1K 20K EX TH
R20 R18
L2
CT1
R24
+5
331K
C8
41
600D
C18
104
IC2
560
10K
R2
4.7UF/50V
28
C23
C17
C13
RV1 104
4.7UF/50V
101
2P
470UF/16V KFR-50QW/
OSC
7805 3.15A/250V
+5 +12
3 1
Vout Vin T1 L
A FUSE A
GND
D2 D1
VR
C1
C4 Title
2
C6 C5
104 C3 D4 D3 CN3 CN14 N
104
Size Number Revision
0.1UF/275V
A3
100UF/16V 2200UF/35V
Date: 6-Jun-2001 Sheet of
File: D:\111\2pqrÖ÷¿Ø°å\Kfr_50qw4.DDB
Drawn By:
1 2 3 4 5 6 7 8
- 62 -
ELECTRICAL DATA
1 2 3 4 5 6 7 8
R1
+5 RA1 33K
+5 10K R24
LN
IC6 SHY C11 R25
103 LED 10K/0.5W
5
6
4
3
IC1 S
D 7
EEPROM
2 TMP87PH46N +5
R26 D
93C46 +5 10K/0.5W
8 1 1 D0 VDD 42
330
IC4
D6
R2
10K
2 DI 41 R28 C10 4007
D5
XT 3 SK 40 TLP371 103
R23
2.2K 4007
103 4 CS 39 CA1 R21
N
TEST
GND VCC
17 26 BUZ JK5
PUMP
18 RESET 25 5.6K
+5
20 XOUT 23 1K
JK6 FM
GND VREF
+5
21 22 C8 Q1 CN4
+5 C23 102 R17 R35
9014
R8
104 Q4 47 C22
R7 9014
10K 0.01UF/275
1K
+5
C9 +5 R34
CN11 103 R11 +5 10K
R33
B 10K
C7
R13 10K Pin. high low B
R9 R12
+5
10K
R10 1K
C18
103
CHECK
R16
102 10K
+12
1
+12
41 cooling
and
heating
cooling
only
10K
+5
10K R30
1K
+12
8 4 R31
10K 40 with
outdoor
PCB
without
outdoor
PCB
C16
600D L1
R15
20K
R14
20K
3
IC7
2
39 wireless
remote
controller
wired
remote
controller
IC2 101K LM358
104
C17 TM TH C13 L3 Q3 R32 C21
28 auto-
restart
without
auto-
restart
4.7UF/50V 331K 9014 C20 10K
CN1 L2 104 104
4.7UF/50V 331K CN2
DL1
OSC C12
EX HT
4.7UF/50V
DL2
+5
7805 +12
3.15A/250V
3 1
LX
Vout Vin T1 FUSE L
A A
D2
GND
D1
C2 VR N
C1
C4
C6 C5
2
- 63 -
ELECTRICAL DATA
- 64 -
R/T CHART OF SENSOR R25=23K
300
K
290
280
270
260
250
Resistance
240
230
220
210
200
190
180
170
160
150
140
130
- 65 -
120
110
100
90
80
70
60
50
40
30
20
10
0
0 8 6 4 2 0 -8 -6 -4 -2 0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54 56 58 60
-2 -1 -1 -1 -1 -1
ELECTRICAL DATA
- 66 -
Resistance(K )
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
-20
-19
-18
-17
-16
-15
-14
-13
-12
-11
-10
-9
-8
-7
-6
-5
-4
-3
-2
-1
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
R/T CHART OF SENSOR R25 =5K
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
ELECTRICAL DATA
R/T CHART OF SENSOR R25 =10K
96
94
K
92
90
88
86
84
82
80
Resistance
78
76
74
72
70
68
66
64
62
60
58
56
54
52
50
48
46
44
42
- 67 -
40
38
36
34
32
30
28
26
24
22
20
18
16
14
12
10
8
6
4
2
0
0
2
4
6
8
-8
-6
-4
-2
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40
42
44
46
48
50
52
54
56
58
60
62
64
66
68
70
72
74
76
78
80
-18
-16
-14
-12
-10
-20
Temp.
ELECTRICAL DATA
EXPLODED VIEWS & PARTS LISTS
- 68 -
EXPLODED VIEWS & PARTS LISTS
15
16
10
17
18
20
19
12 13
21
11
14
8
6
7
23
22
5
24
4
3
2
- 70 -
EXPLODED VIEWS & PARTS LISTS
- 71 -
EXPLODED VIEWS & PARTS LISTS
- 72 -
EXPLODED VIEWS & PARTS LISTS
- 73 -
EXPLODED VIEWS & PARTS LISTS
- 74 -
EXPLODED VIEWS & PARTS LISTS
- 75 -
EXPLODED VIEWS & PARTS LISTS
- 76 -
EXPLODED VIEWS & PARTS LISTS
- 77 -
EXPLODED VIEWS & PARTS LISTS
- 78 -
EXPLODED VIEWS & PARTS LISTS
- 79 -
EXPLODED VIEWS & PARTS LISTS
- 80 -
EXPLODED VIEWS & PARTS LISTS
HBU-28HD03
24 compressor 0010700989 1
- 81 -
EXPLODED VIEWS & PARTS LISTS
- 82 -
EXPLODED VIEWS & PARTS LISTS
- 84 -
EXPLODED VIEWS & PARTS LISTS
- 85 -
EXPLODED VIEWS & PARTS LISTS
- 86 -
EXPLODED VIEWS & PARTS LISTS
HBU-36H03
19 compressor 0010750196 1
- 87 -
PERFORMANCE CURVES
13 PERFORMANCE CURVES
HBU-14H03
a Cooling capacity graph
7
6 20
5 22
Capacity(KW)
4 25
3 27
2 30
1 32
Indoor
0 DB( )
-5 5 15 25 35 43
Outdoor DB( )
b
EER graph
5
20
4
22
25
EER
3
27
30
2
32
Indoor
1 DB( )
-5 5 15 25 35 43
Outdoor DB( )
- 88 -
PERFORMANCE CURVES
HBU-18HC03
Cooling capacity graph
7.00
6.50 20
Capacity(KW)
6.00 22
25
5.50
27
5.00 30
4.50 32
4.00 Indoor
DB( )
-5 5 15 25 35 43
Outdoor temperature( )
EER graph
5.00
4.00 20
22
25
EER
3.00
27
30
2.00 32
Indoor
1.00 DB(
-5 5 15 25 35 43
Outdoor DB( )
- 89 -
PERFORMANCE CURVES
HBU-24H03
a Cooling capacity graph
10
9
8
7 20
Capacity(KW)
22
6
25
5
27
4
30
3
32
2
1
0
-5 5 15 25 35 43
Outdoor DB( )
b
4 20
22
25
EER
3
27
30
2 32
1
-5 5 15 25 35 43
Outdoor DB( )
- 90 -
PERFORMANCE CURVES
HBU-28HD03
12
10
20
Capacity(KW)
8 22
25
6
27
4 30
32
2
Indoor
0
DB( )
-5 5 15 25 35 43
Outdoor DB( )
EER graph
4
EER
Indoor
1 DB(
-5 5 15 25 35 43
Outdoor DB( )
- 91 -
PERFORMANCE CURVES
HBU-36H03
Cooling capacity graph
14
13
12 20
Capacity(KW)
11 22
25
10
27
9
30
8 32
7
Indoor
6 DB(
-7 5 15 25 35 43
Outdoor DB( )
EER graph
3.5
20
3 22
25
EER
2.5
27
2 30
32
1.5
Indoor
DB(
1
-7 5 15 25 35 43
Outdoor DB( )
PERFORMANCE CURVES
HBU-42HD03
a Cooling capacity graph
Cool capacity graph
18
16
14 20
Capacity(KW)
12 22
10 25
8 27
6 30
4 32
2
0
-7 5 15 25 35 43
Outdoor DB( )
b EER graph
5
4.5
4
3.5
EER
3
2.5
2
1.5
1
-7 5 15 25 35 43
Outdoor DB( )
- 93 -
NOISE LEVEL TEST CHART
HBU-14 HBU-18
HBU-24 HBU-28
HBU-36 HBU-42
- 94 -
AIR VELOCITY DISTRIBUTION
m/s m/s
0
4 2 1 0 1 2 4
22
22
25
25 2
27
27
0
4 2 1 0 1 2 4
- 95 -
AIR VELOCITY DISTRIBUTION
m/s m/s 2
0
4 2 1 0 1 2 4
22
22
2
25
25
27
27
0
4 2 1 0 1 2 4
- 96 -
AIR VELOCITY DISTRIBUTION
m/s m/s
0
4 2 1 0 1 2 4
22
22
25
25
27
27
0
4 2 1 0 1 2 4
- 97 -
Sincere Forever
Tel: 86-532-8938356
Web site: http: //www.haier.com