ECL-600 Series
®
LONMARK Certified 28-Point Overview
Programmable Controllers
The ECL-600 Series controllers are microprocessor-based
programmable controllers designed to control various building
automation applications such as air handling units, chillers, boilers,
pumps, cooling towers, and central plant applications. This series
supports up to two ECx-400 Series I/O extension modules.
®
These controllers use the LonTalk communication protocol and are
LONMARK certified as a Static Programmable Device, guaranteeing
compatibility and interoperability with other manufacturers’ LONMARK
certified controllers.
Recommended Applications
Model ECL-600 / 610 / 650
Air Handling Unit
Multi-Zone Application
Chiller
Boiler
Cooling Tower
Central Plant
Objects List
Objects Network Variable Input (General Usage)
Calendar Objects 2 NVI Changeable Type, 35
Special events per calendar 50 Up to 31 Bytes1
1. Any type of Fan-In function is supported in combination with the “FOR” loop
Schedule Objects 8 function.
Special events per schedule 10
Network Variable Output (General Usage)
PID Loop Objects 30 NVO Changeable Type, Up to 35
Constants 31
Boolean 124 Bytes
Enumeration 62
Hardware Input Network Variable
Numeric 56 nvoHwInput per Hardware Yes
Input
Variables
Boolean 124 Hardware Output Network Variable
Enumeration 54 nviHwInput per Hardware Yes
Numeric 56 Output
nciSetpoint Yes nvoHwInput per Hardware Yes
Output
Total Network Variables 254
Product Specifications
Power Supply Input Communications
Voltage Range 24VAC/DC; ±15%; Class 2 Communications LonTalk Protocol
Frequency Range 50/60Hz Transceiver FT 5000 Free Topology Smart
Overcurrent Protection Field replaceable fuse Transceiver
Fuse Type 3.0A Channel TP/FT-10; 78Kbps
Power Consumption 22 VA typical plus all external LonMark Interoperability Version 3.4
1
ECL-600 / ECL-610 loads , 65 VA max. Guidelines
Power Consumption 25 VA typical plus all external Device Class Static Programmable Device
1
ECL-650 loads , 68 VA max. LonMark Functional Profile
1. External loads must include the power consumption of any connected modules
such as an Allure Series Communicating Sensor. Refer to the respective module’s
Input Objects Open-Loop Sensor #1
datasheet for related power consumption information. Output Objects Open-Loop Actuator #3
Node Object Node Object #0
Real Time Clock Real Time Keeper #3300
Scheduler Scheduler #20020
Calendar Calendar #20030
Programmable Device Static Programmable Device
#410
0 to 10VDC
Range 0 to 10VDC
(40kΩ input impedance)
0 to 10VDC
Universal Outputs (UO) Range 0 to 10VDC
Source Current Maximum 60 mA at 10VDC
General (minimum load resistance
Output Type Universal; software configurable 200Ω)
Output Resolution 10-bit digital to analog converter 0 to 20mA
Output Protection Built-in snubbing diode to Range 0 to 20mA
protect against back-EMF, for Type Current source (jumper
example when used with a configurable)
12VDC relay
Output is internally protected HOA
against short circuits Hand-Off-Auto switch When equipped.
Load Resistance Minimum 200 Ω for 0-10VDC Supervision allows control logic
and 0-12VDC outputs to read the current HOA switch
and potentiometer settings
Threshold Configurable
Potentiometer Voltage Range 0 to 12.5VDC
Dimensions
7 .7 0 " [1 9 5 .5 8 ]
6 4 .6 8 (2 .5 5 )
2 .2 5 " [5 7 .1 5 ]
4 .7 0 " [1 1 9 .3 8 ]
6 .2 5 " [1 5 8 .7 5 ]
2 .0 3 " [5 1 .4 7 ] 2 .0 3 " [5 1 .4 7 ]
1. Controller NVO name = nvoHwInput_# (# = 01 to 16) Scheduler Object Configuration Properties: nvoVe28_54
I/O Module 1 NVO name = nvoHwInputX1_# (# = 01 to 12) Object Major Version (SCPTobjMajVer) UNVT_variable_enum_28to54
I/O Module 2 NVO name = nvoHwInputX2_# (# = 01 to 12) Object Minor Version (SCPTobjMinVer)
nvoVn01_07
UNVT_variable_numf_1to7
nvoVn08_14
UNVT_variable_numf_8to14
nvoVn15_21
UNVT_variable_numf_15to21
Hardware Output Calendar nvoVn22_28
36 x Open-Loop Actuator Object Type #3 2x Object Type #20030 UNVT_variable_numf_22to28