Professional Documents
Culture Documents
Idronics - 23 - NA - Heat Transfer in Hydronic Systems
Idronics - 23 - NA - Heat Transfer in Hydronic Systems
july 2018
july 2018
Caleffi NorthAmerica,
Caleffi North America, Inc.
Inc.
3883 W. Milwaukee
9850 South 54 StreetRd
th
Mark Olson
INDEX
1. INTRODUCTION
2. HEAT TRANSFER FUNDAMENTALS
3. HOW FLOW AND TEMPERATURE CHANGE INFLUENCE HEAT EXCHANGE
4. OPERATING TEMPERATURE OF HYDRONIC HEATING SYSTEMS
5. HEAT EXCHANGER FUNDAMENTALS
APPENDIX A: PIPING SYMBOL LEGEND
APPENDIX B: THERMAL MODELS FOR FINNED-TUBE BASEBOARD
APPENDIX C: THERMAL MODEL FOR A RADIANT PANEL CIRCUIT
Disclaimer: Caleffi makes no warranty that the information presented in idronics meets the mechanical, electrical or other code requirements applicable within a 10%
given jurisdiction. The diagrams presented in idronics are conceptual, and do not represent complete schematics for any specific installation. Local codes may
Cert no. XXX-XXX-XXXX
require differences in design, or safety devices relative to those shown in idronics. It is the responsibility of those adapting any information presented in idronics to
verify that such adaptations meet or exceed local code requirements.
Heat Transfer in Hydronic Systems
All hydronic heating and cooling systems move thermal Two fundamental concepts apply to all situations involving
energy (e.g., heat) from one location to another. In heat transfer:
heating applications, this movement takes place across
many components, starting at a heat source and exiting 1. Heat always moves from a material at some temperature
the hydronic system at the heat emitter(s). Between these to another material at a lower temperature.
“end points” of the system, several intermediate heat
transfer processes must occur. Examples include heat 2. The rate of heat transfer depends on the temperature
moving from combustion gases to water flowing through difference between the two materials. The greater this
a boiler, heat passing from one fluid to a different fluid difference, the higher the rate of heat transfer.
through a heat exchanger, and heat passing from water
inside a copper tube to aluminum fins attached to the To gain a better detailed understanding of how a hydronic
outer surface of that tube and finally into room air. system works, heat transfer needs to be classified.
A well-established scientific principal is that all heat
It’s important for those who design or troubleshoot transfer processes occur through one or more of the
hydronic systems to understand the physical processes following modes:
by which heat moves. That knowledge can help
them quickly identify factors that may constrict heat • Conduction
movement. Examples of such constrictions include scale • Convection
formation on a boiler’s heat exchanger, heat emitters • Thermal radiation
with insufficient surface area, or a thick rug placed over
a heated floor slab. CONDUCTION:
Conduction heat transfer takes place within solid
This issue of idronics discusses the fundamentals of heat materials. It’s the result of atomic vibrations within those
transfer as they apply to hydronic heating and cooling materials. The atoms in all materials having temperatures
systems. It also shows how the rate of heat movement above absolute zero (-458ºF) vibrate to some extent. The
in hydronic systems is influenced by flow rate and higher the material’s temperature, the more vigorous the
temperature change of water or water-based fluids. atomic vibrations.
Another concept called thermal equilibrium, which When heat is added to a solid material, the atomic
applies to all hydronic heating and cooling systems, vibrations become more energetic. These vibrations
will be described. The relationship between heat emitter spread out across trillions of atoms that are bonded
surface area and required water temperature for a given together, moving towards material at a lower temperature.
rate of heat transfer is also be examined.
The property that determines how well a material transfers
Heat transfer can be a complex subject from a theoretical heat by conduction is called its thermal conductivity. The
standpoint. Mathematical models that predict the higher a material’s thermal conductivity value, the faster
heat transfer performance of various heat emitters heat can pass through it, with all other conditions being
have been developed, and some are presented in the equal. The thermal conductivity of a material is usually
appendices. However, the primary objective of this issue determined by testing. The thermal conductivity of many
is not to dive deeply into the mathematical theory of heat materials is listed in references such as the ASHRAE
transfer. Rather, it’s to provide a solid understanding of Handbook of Fundamentals.
fundamentals, along with many practical applications of
those fundamentals. Such an understanding can help root Heat moving from the inner surface of a pipe to its outer
out potential performance problems at the design stage, surface is an example of conduction heat transfer. Heat
long before they reveal themselves as costly mistakes passing from tubing embedded in a concrete slab to
within installed systems. It can also help technicians the surface of that slab is another example. The warmth
quickly identify performance problems caused by heat felt on hands wrapped around a cup of hot coffee is the
transfer “bottlenecks,” rather than faulty equipment. result of heat conduction through the cup.
3
Figure 2-1 Where:
Q = rate of heat transfer through the material (Btu/hr)
k = thermal conductivity of the material (Btu/°F•hr•ft)
∆x = thickness of the material in the direction of heat
flow (ft)
∆T = temperature difference across the material (°F)
2
A = area heat flows across (ft )
Where:
Where: For example: The thermal conductivity of a specific polyur
4 k = thermal conductivity of the material (Btu/°F•hr•ft)
Q = rate of heat transfer through the material (Btu/hr) k = 0.015 (Btu/°F•hr•ft). Determine the R-value of a 2 inch
∆x = thickness of the material in the direction of heat flow (ft
k = thermal conductivity of the material (Btu/°F • hr • ft)
DRAFT (4-16-18)
5
Figure 2-4 87.8 ºF
74.5 ºF
3/8" oak flooring bonded to slab 70 ºF room air temperature
4" concrete slab nominal 1/2" tubing
30
Heat output (Btu/hr/sq. ft.)
25 PEX tubing
20
15
10
0
(water temp. - room air temp) (ºF)
6
The thermal conductivity of the tubing options is: Figure 2-6
7
140 ºF water (w/ plates)
Figure 2-8
8” o.c. tubing 140 ºF water (no plates)
82 82
78 78
74 74
70 70
3/4" plywood
4" fiberglass
70 ºF air temperature
3/4" plywood
4" fiberglass
70 ºF air temperature
Figure 2-9
only variable between the two models is the presence of
6-inch-wide by 0.024-in.-thick pre-formed aluminum heat
transfer plates in the upper graphic, and the absence of
any plates in the lower graphic.
8
The location of the 6-inch-wide
aluminum plates, placed on tubing Figure 2-10
tube wall
spaced 8 inches apart, is easily
seen as the bright yellow color, boundary layer of slow moving fluid limits convection
even though the plates and tubing velocity profile of fluid
are covered with ½” drywall. That Note low velocity near tube wall
fact that the drywall surface is
significantly warmer under the
plates compared to the gap
between the plates indicates that
the plates are effectively spreading
heat, by conduction, away from "core" of flow stream
the tubing. Contrast this with the
“striping” seen where the tubing
is present without the plates in the
lower part of the image. As was
the case with floor heating, the heat flows from water,
high thermal conductivity of the through boundary layer, tube
aluminum plates greatly enhances wall, into surrounding material
lateral heat diffusion across the
surface of the radiant ceiling panel.
The plates make the ceiling panel a Most people have experienced the increased “wind chill”
more efficient heat emitter, allowing it to deliver heat to effect as cold outside air blows past them, compared
the room at a relatively low water temperature. to how they would feel if standing in still air at the same
temperature. The faster the air blows past them the
CONVECTION: greater the rate of convective heat transfer between their
Convection heat transfer occurs as the result of fluid skin or clothing surfaces and the air stream. Although
movement. The fluid can be a liquid or a gas. When the person may feel as if the moving air is colder, it isn’t.
heated, fluids expand. This lowers their density relative Instead, they’re experiencing an increased rate of heat
to surrounding cooler fluid. Lowered density increases loss due to enhanced convective heat transfer. Achieving
buoyancy, which causes the warmer fluid to rise upward. the same cooling sensation from calm air would require a
Examples of the latter include warm air rising toward much lower air temperature.
the ceiling in a room, and heated water rising to the
upper portion of tank-type water heater. Both processes Convective heat transfer increases with increasing fluid
occur without circulators or blowers. As such, they are speed. This happens because a layer of fluid called the
examples of “natural” convection. “boundary layer,” which clings to surfaces, gets thinner
as the fluid’s velocity increases (see Figure 2-10).
Convection heat transfer is also responsible for moving
heat between a fluid and a solid. The thinner the boundary layer, the lower the thermal
resistance between the bulk of the fluid stream and the
For example, consider water at 100ºF flowing along a surface. Less thermal resistance allows for higher rates
solid surface that has a temperature of 120ºF. The cooler of heat transfer between the fluid molecules in the bulk
water molecules contacting the warmer surface absorb of the stream and the tubing wall.
heat from that surface. These molecules are churned
about as the water moves along. Molecules that have The relationship between convective heat transfer and
absorbed heat from the surface are constantly being fluid speed past a surface can be seen in many hydronic
swept away from that surface into the bulk of the water systems. For example, the faster water flows through a
stream and replaced by cooler molecules. One can finned-tube baseboard heat emitter, the higher it’s heat
envision this form of convective heat transfer as heat output, with all other conditions being the same. This
being “scrubbed” off the surface by the flowing water. effect is evident in the heat output rating data listed by
manufacturers of finned-tube baseboard. An example of
The speed of the fluid moving over the surface significantly such ratings, using numbers from a specific make and
affects the rate of convective heat transfer. model of baseboard, is shown in Figure 2-11.
9
DRAFT (4-16-18)
Figure 2-11
At a given water temperature, the heat output at a flow heat transfer is determined by the multiplication of flow
rate of 4 gallons per minute (gpm) will always be slightly rate times temperature drop. This is why the rate of
higher than at a flow rate of 1 gpm. This increase is due heat transfer in Figure 2-12 increases as the flow rate
toAta a givenboundary
thinner water temperature, the bulk
layer between the heatofoutput
the fluidat
aincreases,
flow rateevenof 4though
gallons
theper minute (gpm)
temperature will the
drop across
stream and the inner tube wall of the finned-tube element. heat emitter is decreasing. This will be discussed more
always be slightly higher than at a flow rate of 1 gpm. This increase is due to a thinner
in section 3.
boundary
One layer between
way to rationalize the bulk
the increase of the
in heat fluidwith
output stream and the inner tube wall of the finned-tube
increasing flow rate is to consider what happens to the From the standpoint of heat transfer only, there is no such
element.
average water temperature inside the heat emitter with thing as the water moving “too fast” through a finned-
changes in flow rate. Figure 2-12 shows an example. tube element. This is also true for other heat emitters,
such as the coil of an air handler, or a tubing circuit in a
As flow rate increases, the temperature drop along floor heating system. The faster the flow rate, the higher
One way to rationalize the increase in heat output with increasing flow rate is to consider what
the finned-tube element decreases. Since the inlet the rate of heat transfer.
temperature
happens toremains constant,
the average decreasing
water temperature
temperature inside the heat emitter with changes in flow rate.
drop implies a higher average water temperature in the Another example of increasing convective heat transfer
Figure
finned 2-12
tube. shows
Higher an example.
average water temperature, in any with increasing flow rate can be found in heat output
heat emitter, results in higher heat output. ratings for fan-coils. Figure 2-13 shows an example
of how heat output increases with increasing water
Never “judge” the rate of heat transfer from a heat flow rate through the coil of the air handler, while the
[insertbased
emitter figuresolely
2-12]on temperature drop. The rate of inlet water temperature and incoming air temperature
remain constant.
10
Heat output also increases as the air flow rate through the
Figure 2-13 air handler’s coil increases. This happens because faster
4500 air flow reduces the resistance of the boundary layer
between the bulk air stream and the surface of the coil.
4000
3500 The “non-linear” relationship between heat output and
flow rate seen in Figure 2-13 is a characteristic of
Heat output (Btu/hr)
The head loss created by fluid moving through the heat NATURAL VS. FORCED CONVECTION
emitter, in theory, increases with the cube of flow rate (e.g., When fluid motion is caused by a circulator, a blower or
if the flow rate is doubled, the head loss increases 23 = (8) any other powered device, the resulting convective heat
times). Thus, attempting marginal gains in heat transfer by transfer is called “forced convection.” When the fluid
selecting circulators that can maintain high flow rates will motion is strictly the result of buoyancy differences within
significantly increase the installation and operating cost the fluid, the resulting convective heat transfer is called
of the circulator. Velocity noise and erosion corrosion also “natural convection.”
become concerns at high flow rates. To avoid erosion
corrosion, the flow velocity in smaller copper tubes should The room side heat output of hydronic heat emitters
not exceed 5 feet per second. such as finned-tube baseboard and wall cabinet heaters
with internal coils (but no blower) is largely the result of
natural convection. Such heat emitters are appropriately
Figure 2-14 called “convectors.”
7000 between the water and the inner surfaces of the heat
emitter is forced convection.
6000
Heat emitters that use fans or blowers to force air
5000 through a heat exchanger are usually called fan-coils or
air handlers. The convective heat transfer that occurs
4000
on the room (air) side of these heat emitters is another
example of forced convection.
3000
11
speed of the fluid, and the physical properties of the
Figure 2-15 fluid (e.g. thermal conductivity, specific heat, density
and viscosity). In many cases, the value of (h) needs to
circulator be determined experimentally. Heat transfer textbooks
sometimes list values of h, or methods for determining (h)
DRAFT
for very specific and often simplified (4-16-18)
situations. The table
in Figure 2-16 shows how wide the range of (h) values
heat can be 2-16]
for specific situations.
source [Figure
Figure
DRAFT 2-16
(4-16-18)
situation range of convection
coefficient (h) (Btu/hr•ft2•ºF)
Natural convection is usually a “weaker” form of heat transfer in comparison to forced
natural convection 1-5
forced convection It’s the result of slower fluid motion
convection. created
involving air by buoyancy differences versus much
(inside surface of coil)
faster motion created by a circulator. The slower fluid motion increases the thickness of the
natural convection forced convection 2-100
boundary layer,
(ouside surface of coil) which creates greater involving
resistance to air
heat transfer between the bulk of the fluid
and the surface. convection involving 20-3000
water
differences versus much faster motion created by a
circulator. The slower fluid motion increases the thickness convection involving 500-5000
Forced convection versus natural convection boilingexplains why a small wall-mounted fan coil that's
water
of the boundary layer, which creates greater resistance to
onlythe
heat transfer between 18bulk
inches
of thewide
fluidcan
and provide the equivalent heat output of 10+ feet of finned-tube baseboard
the surface.
13
Although the human eye cannot see thermal radiation, Figure 2-20
there are devices that can detect it, and display an
image that uses colors to represent different surface
temperatures. Such an image is called an infrared
thermograph. Figure 2-19 shows an example of such an
image for a hot wood stove.
Figure 2-19
( )
temperature rather than
with convective heat transfer, since air is a fluid and is through tubing in the radiant surface. Page " 32 ⎝of " 128
The hr ⋅ ftsurface
average
2
⋅º F ⎠
present between the objects exchanging heat. To simplify temperature of the panel, as well as the relationship
estimating overall heat transfer rates, some references between it and the⎛ water temperature ⎞ in the2 tubing, are
Btu
provide hybrid heat transfer coefficients that combine the mA(∆ T ) =by
Q = influenced
highly ⎜ 2.0
the material (
100 ft (80º
⎟ “geometry” ) ofFhow − 70º F) = 2,
(
and
effects of radiant and convective heat transfer for typical the radiant panel ⎝is constructed. )
hr ⋅ ft 2 ⋅º FOther
⎠ references can
situations where the variation in conditions is limited. be used to estimateKeep the room sidethatheatthis
output of estimate
radiant based o
An example is a hybrid heat transfer coefficient (m) for in mind is an
floor, wall and ceiling panels based on specific panel
a heated floor, wall or ceiling panel that embodies the construction and the assumed
averagecommon building materials.
water temperature within It is a
effect of both radiant and convective heat output. Figure the embedded tubing.
2-21 lists some values of hybrid heat transfer coefficients
that embody both convective and radiant effects for Keep in mind that this is an estimate based on a typical range
Pago
commonly constructed interior building surfaces. assumed common building materials. It is also based on avera
where:
Q = rate of heat transfer into or out of the water stream Solution: DRAFT To(4-16-18)
use Formula 3-1, the density of water at its
(Btu/hr)
where: average temperature of 101ºF must first be estimated
8.01 = a constant based on the units used using Figure 3-2:
3
D = density of the When
fluid (lb/ft )
usingheat
Formula 3-1,into
the or
density
c = specific heat ofQthe = rate
fluid of transfer
(Btu/lb/ºF) out ofand
the specific heat of
water stream the water (or water-based anti-freeze
(Btu/hr)
Figure 3-2
solution)
f = flow rate of fluid = a should
through
8.01 bebased
the device
constant based
(gpm) ononthe average
theunits usedtemperature of the liquid during the process by which
∆T = temperature change of the fluid through the device (°F)
the fluid is gaining or losing heat.
D = density of the fluid (lb/ft3)
When using Formula 3-1, the density and specific heat of
c = specific
the water (or water-based heat of
antifreeze the fluid
solution) (Btu/lb/ºF)
should be
based on the average cold water only,
Fortemperature of the Formula
liquid 3-1 the
during simplifies to Formula 3-2:
f = flow rate of fluid through the device (gpm)
process by which the fluid is gaining or losing heat.
∆T = temperature change of the fluid through the device (°F)
For cold water only,Formula
Formula 3-2
3-1 simplifies to Formula 3-2:
Formula 3-2
q = 500 f (∆ T )
Page " 34 of " 128
where:
where:into or out of the water stream
Q = rate of heat transfer
(Btu/hr)
f = flow rate of water through the device (gpm)
500 = constant rounded off from 8.33 x 60
Q = rate of heat transfer into or out of the water stream (Btu/hr)
∆T = temperature change of the water through the device
(°F) f = flow rate of water through the device (gpm)
500 = constant rounded off from 8.33 x 60
∆T = temperature change of the water through the device (°F)
16
Formula 3-2 is technically only valid for cold water because the factor 500 is based on the
For example, what would the temperature drop of a water stream flowing 0.5 gallons per minute
have to be to deliver 50,000 Btu/hr to a load using water at an average temperature of 101 ºF?
DRAFT(4-16-18)
DRAFT (4-16-18)
Mathematically this is simple. Just put the given numbers into formula 3-1 and calculate.
3
D
DD===61.96
61.96
61.96lb/ft3lb/ft
lb/ft3
Btu
q 50,000
∆T = = hr = 201.5º F
The specific
Thespecific
The specificheat
heatheat ofcan
ofofwater
water water can be
canbebeassumed
assumed assumed
totoremain
remain1.0 to remain 1.0
1.0Btu/lb/ºF.
Btu/lb/ºF. 8.01cd( f ) ⎛ ft 3 ⋅ min ⎞ ⎛ Btu ⎞ ⎛ 61.96lb ⎞ gal
⎜⎝ 8.01 gal ⋅ hr ⎟⎠ ⎜⎝ 1 lb⋅º F ⎟⎠ ⎜⎝ ft 3 ⎟⎠ (0.5 min )
Btu/lb/ºF.
Puttingthese
Putting thesenumbers
numbersinto
intoFormula
Formula3-1yields:
3-1yields:
Putting these numbers into Formula 3-1 yields: If the 4.0 gpm flow
If the rategpm
4.0 used in the previous
flow rate usedexample wasprevious
in the reduced to 0.5 gpm, would
example was the
reduced
temperature tocircuit
drop of the 0.5 “automatically”
gpm, would the to
change temperature drop
201.5 ºF to deliver of the 50,000
the intended
( 8.01Dc) f)(∆
q q= =( 8.01Dc f (∆
TT ( 8.01×61.96
) =) =( 8.01× 61.96× 1.00 ) ×) 1.5
× 1.00 × 1.5× × (110− −92)
(110 92)= = 13,
13, 400Btu/ hr
400Btu / hr circuit “automatically”
Btu/hr heat output? change to 201.5ºF to deliver the
intended 50,000 Btu/hr heat output?
Formula
Formula3-1
Formula
3-1
3-1can
can
canbeberearranged
be rearranged
rearrangedtotodeterminedeterminethe
to determine
thetemperature
temperaturedrop dropororflow flow
the
Absolutely
ratethat
rate not!
that wouldbebe
would
temperature drop or flow rate that would be required for Absolutely not!
requiredforfora aspecific
required specificrate rateofofheat heattransfer.
transfer.
a specific rate of heat transfer.
While it is possible to operate very specialized industrial hydronic systems with a 201.5 ºF
While it is possible to operate very specialized industrial
For example, what is the temperature drop required to deliver heat at temperature
a rateofof50,000 drop, under specific conditions, those systems are very different from typical
For example,
For example, what is what the temperature drop required to drop
is the temperature deliver heat
requiredat a rate to 50,000hydronic Btu/hr,
Btu/hr, systems with a temperature drop in the range
hydronic space heating
averagesystems.
usinga adistribution
using
deliver distribution
heat at system asystem operating
rateoperating
of 50,000 with
with wateratatausing
water
Btu/hr, aflow flowraterate of4 4gpm?
gpm?Assume
a ofdistribution Assume the
of theaverage
200ºF, under There is no way that a practical or cost effective residential or
specific conditions, those systems
watertemperature
system
water temperature
operating isis101 101 ºFºF water at a flow rate of 4 gpm?
with light commercial
are very hydronic heating system
different fromcould typicaloperatehydronic
with this calculated 201.5 ºF drop
space-heating
Assume the average water temperature is 101ºF between the supply and
systems. return side
There is no of way
the distribution system.
that a practical or cost-effective
Solution:The
Solution: Thedensity
densityofofwater wateratat101 101ºFºFwas
waspreviously
previouslydetermined
determinedtotobebe61.96 residential
61.96lb/ft
lb/ft . After
3. 3After or light commercial hydronic heating system
Solution: The
rearrangingformula
rearranging density
formula3-1the 3-1thenumbers of water
numbersare at
areentered 101ºF
enteredand was
andcalculated.
calculated. previously Formula could
3-1 providedoperatea “what with this value
is required” calculatedbased solely 201.5ºF drop between
on a mathematical relationship of
determined to be 61.96 lb/ft3. After rearranging Formula the supply and return side of the distribution
the variables. It does not assure that the resulting numbers accurately describe a “what will be” system.
3-1, the numbers are entered and calculated. situation in a real system. When “what is required” values determined by calculation seem very
heat emitters (e.g., are they scaled or corroded), and the measured through a hydronic average water
distribution system, and temperature
if the accurately measured in the system
temperature was
drop from
the supply to return of that distribution system was 25.19 ºF, and if the accurately measured
condition of the external surfaces of the heat emitters 101ºF (e.g., so that the density is known to be 61.96
average 3),water temperature in the system was 101 ºF (e.g., so that the density is known to be
(e.g., are they bent or covered with dust, pet hair, etc.). lb/ft then the actual rate of heat delivery could be
61.96 lb/ft ), then the actual rate of heat delivery could be calculated using formula 3-1.
3
17
Figure 3-3 Figure 3-4
processing unit
heat source
to/from
to/from
load
flow meter
Temperature drop can be measured with any accurate LAMINAR VS. TURBULENT FLOW
temperature indicator. Devices that simultaneously read two It’s helpful to imagine liquids flowing through pipes as
sensors and give a direct reading of ∆T are also available. a stream containing millions of tiny “water particles.”
The path that any given water particle takes as it moves
The instantaneous rate of heat transfer, as well as the through the pipe is called a streamline.
total heat passing a given location in the system can
also be measured using a heat meter, such as shown in In some situations, the streamlines of all the water
Figure 3-4. particles are parallel to each other, like multiple lanes of
traffic on a major highway. The water particles near the
Heat meters combine an accurate flow meter with two center of the pipe move faster than those near the inner
calibrated temperature sensors. The latter are mounted pipe wall, but they don’t “change lanes.” This type of fluid
in special fittings that allow a very precise measurement movement, represented by Figure 3-5 is called laminar
of ∆T. flow. It can be pictured 3-dimensionally as multiple
concentric “layers” of liquid, each moving at a different
The sensors and flow meter send data to a processing speed, sliding past each other, as shown in Figure 3-6.
unit that calculates the instantaneous rate of heat
transfer, based on Formula 3-1. The processing unit also Laminar flow can be desirable or undesirable depending
integrates the heat transfer rate over time to determine on where it occurs in hydronic systems, and the design
the total amount of heat that has passed through the goals for the system. If the goal is to move fluid long
meter. The latter can be used to verify operation of the distances with minimal pumping power, laminar flow
system, or as the basis of billing a customer for the total is desirable. However, if the goal is to maximize heat
amount of heat used. Caleffi CONTECA heat meters are transfer from a flowing fluid to a tube wall or other solid
in conformance with the newly released ASTM E3137/ surface, laminar flow is very undesirable.
E3137M-17 heat metering standard.
18
The erratically shaped streamlines present during turbulent
Figure 3-5 flow create good mixing. A small quantity of fluid that’s
imaginary "fluid particles" close to the tube wall one instant could be swept into the
streamlines bulk of the fluid stream the next instant. This decreases
the boundary layer thickness, and significantly improves
convective heat transfer.
REYNOLDS NUMBER
It’s possible to predict if flow through a pipe will
be laminar or turbulent. It’s based on calculating a
dimensionless quantity called the Reynolds number of
Because the water particles move in parallel streamlines
the fluid (abbreviated as Re#). If the calculated Re# is
during laminar flow, there is very little mixing between
over 4000, the flow is turbulent. If it is below 4,000, the
them. This increases the thickness of the boundary layer
flow may be either laminar or turbulent. If the Re# is
between the bulk of the fluid stream and the inner wall of
below 2,300, the flow will be laminar.
the pipe. Thicker boundary layers decrease convective
heat transfer. DRAF
The Reynolds number for flow in a pipe can be calculated
using Formula 3-3:
Turbulent flow causes the streamlines of imaginary fluid
particles to bend and twist as the fluid moves down the
Formula 3-3:
pipe, as shown in Figure 3-7.
" Re# = vdD
Figure 3-7 µ
imaginary "fluid particles"
streamlines where: where:
v = average flow velocity of the fluid (ft/sec)
v = of
d = internal diameter average
pipe (ft)flow velocity of the fluid (ft/sec)
3
D = fluid’s density (lb/ft )
d = internal diameter of pipe (ft)
µ = fluid’s dynamic viscosity (lb/ft/sec)
D = fluid’s density (lb/ft3)
For example, determine the Reynolds number of water
at 140°F flowing µat=5fluid’s dynamicaviscosity
gpm through 3/4-inch (lb/ft/sec)
type M
copper tube. Is this flow laminar or turbulent?
turbulent flow streamlines
0.0007 serves as a check that the proper units are being used in Formula 3
0.0006 TEMPERATURE
TEMPERATURE DROP
DROP IN AIN A HYDRONIC
HYDRONIC SYSTEM
SYSTEM
Formula 3-1 indicates that, with all other factors and
DRAFT (4-16-18)
0.0005 TEMPERATURE
conditions DROP
being equal, the IN A HYDRONIC
rate SYSTEM
of heat delivery from
Formula 3-1 indicates
a stream of water that,
(orwith all other factors
solution and conditions
of antifreeze) being equal, the rate
is directly
0.0004 delivery from a stream
proportional to of
thewater (or solution of anti-freeze)
temperature drop that is directly
streamproportional to t
Formula
undergoes
temperature as3-1
drop it indicates
that passes that, with
through
stream undergoes aall
as other factors
ithydronic
passes and conditions
distribution
through a hydronic bein
distribution
0.0003 DRAFT (4-16-18)
system.
delivery fromviscosity
a stream
At 140 ºF the density of water is 61.35 lb/ft3. From figure 3-8 the dynamic of of water
water 140(or solution of anti-freeze) is directly
0.0002
The ∆Ttemperature
at which a hydronic circuit operates is always
as itdetermined, at any atime,
ºF is 0.00032 lb/ft/sec. The ∆T at whichdrop
DRAFT (4-16-18) that
a hydronicstream undergoes
circuit operates passes
is through
always hyd
0.0001 circuit’s ability to release heat.
determined, at any time, by the circuit’s ability to
0 release heat.
The inside At
diameter
The ∆T at which abehydronic circuit operates is always determin
50 100140 ºF of a density
the 3/4-inchoftype
150 200
M copper
water is 61.35tube 3is From
0.811figure
250lb/ft .Consider
inches.
3-8This must
theheating
a hydronic dynamic converted
viscosity
distribution to water
of
system 140
that’s releasing heat at a rate of 100
feet to match the stated units for Formula 3-3: circuit’s
Consider a ability to heating
hydronic release heat.
distribution system that’sat 9 gpm. The
ºFwater temperature
is 0.00032 lb/ft/sec. (ºF) into a space at 70 ºF air temperature when supplied with 180 ºF water
At 140 ºF the density of water is 61.35 lb/ft . From figure
3 releasing
3-8 theheat at
dynamic a rate of
viscosity 100,000
of these Btu/hr
waterconditions
140 into a space at
temperature drop of the circuit under is found using formula 3-1:
70ºF air temperature when supplied with 180ºF water at
ºF is 0.00032 lb/ft/sec. 3 Consider a hydronic heating distribution system that’s releasing hea
At 140ºF, the density ofThe water is 61.35 lb/ft . From Figure 3-8,
⎛ ft ⎞ diameter of a 3/4-inch type M copper 9 gpm.
tube The temperature
inches. Thisdrop
must of
be the circuittounder these
" d = ( 0.811 in ) ⎜ 1inside⎟ = 0.06758 ft into
is 0.811
a space at 70 ºF air
converted
temperature when supplied with 180 ºF wa
the dynamic viscosity of water
⎝ 12 in. ⎠ 140ºF is 0.00032 lb/ft/sec. conditions is found using Formula 3-1:
feet to match the stated units for Formula 3-3:
The inside diameter of a 3/4-inch type M copper tube is 0.811 temperature dropmust
inches. This of thebecircuit
convertedunder
Btu to these conditions is found using
The average
The inside diameter of flow velocity corresponding
a 3/4-inch type M copper to atube
flow is
rate of 5 gpm can
q be found using formula 100,0003-4.
hr
feet must
0.811 inches. This to matchbe the stated units
converted for Formula
to feet to match the ∆ T = 8.01cd( f ) = ⎛
3-3:
ft 3 ⋅ min ⎞ ⎛ Btu ⎞ ⎛ 60.7lb ⎞ gal
= 22.85º F
stated units for Formula
" d = 3-3:
⎛
0.811 in ⎜ 1 ft ⎞
( )
= 0.06758 ft ⎜⎝ 8.01 gal ⋅ hr ⎟⎠ ⎜⎝ 1 lb⋅º F ⎟⎠ ⎜⎝ ft 3 ⎟⎠ (9 min )
Formula 3-4: ⎝ 12 in.⎟⎠
( ⎛ 1 ft ⎞
) Btu
" d = 0.811
Theinaverage
⎜⎝ ⎟ = 0.06758 ft
12 in.⎠flow velocity corresponding to abased
flow rate of 5 gpm 100,000
can be found using formula 3-4.
∆T = on this qcalculation, the return water hr
= temperature = 22.8
0.408 from on
thethis 8.01cd( f ) the
distribution ⎛return ftwould
system 3
⋅ min ⎞ ⎛ Btu from
be: ⎞ ⎛ 60.7lb ⎞ gal
The averagev flow
⎛ average
= The
⎞ flow velocity corresponding
f corresponding to a flow based
of rate
180of-522.85
calculation,
gpm can 8.01 formula ⎟3-4.
be found⎜using water
⎜⎝ 1
temperature
⎟⎠ ⎜
the
3 ⎟
(9
distribution )
system w
⎜⎝ velocity
2 ⎟ to a flow rate = 157.15ºF ⎝ gal ⋅ hr ⎠ lb⋅º F ⎝ ft ⎠ min
d Formula 3-4:
⎠ 180-22.85 = 157.15 ºF
5 gpm can be found using Formula 3-4.
How would the output of this distribution system change if:
Formula 3-4: How would the output of this distribution system change if:
Formula 3-4:Where:
⎛ 0.408 ⎞ 1. The room temperature was reduced from 70ºF to 65ºF
v = averagev fluid = ⎜ velocity f
⎝ d 2 ⎟⎠ (ft/sec) based onconditions
this calculation,
beingthe return
with all other the
Page " 46water
same? of " 128temperature from the dis
d - exact⎛ 0.408
inside⎞diameter of pipe (inches) 180-22.85 = 157.15 ºF
v=⎜ 2 ⎟ f
Where: ⎝ d ⎠ 2. The supply water temperature was changed to 140ºF
f = flow rateWhere:through pipe (gpm)
v = average fluid velocity (ft/sec) with all other conditions being the same.
d = exact inside diameter of pipe (inches)
v = average fluid velocity (ft/sec) How would the output of this distribution system change if:
Where:pipe (gpm)
f = flow rate through Both changes can be estimated based on a fundamental
For 3/4” Type M copper
d - exact tubing
inside operating
diameter at (inches)
of pipe a flow rate of 5 gpm the average flow velocity is:
v = average fluid velocity (ft/sec) tenant of hydronic heating, specifically:
Page " 46 of " 128
For ¾” Type M copper tubing
f = flow rateoperating
through pipe at (gpm)
a flow rate of
d - exact
5 gpm, the average flow inside diameter
velocity is: of pipe (inches) The heat output of any hydronic distribution system
f = flow rate through pipe (gpm) will be approximately proportional to the difference
⎛ 0.408For⎞ 3/4” 0.408M⎞copper tubing
⎛ Type ft operating at abetween
flow rate ofthe supply
5 gpm water flow
the average temperature
velocity is: and the room
v=⎜ 2 ⎟ f =⎜ 2 ⎟ 5 = 3.1
⎝ d ⎠ ⎝ ( 0.811) ⎠ sec air temperature.
For 3/4” Type M copper tubing operating at a flow rate of 5 gpm the average flow velocity is:
If the room
If the room air temperature air temperature
was reduced from 70 ºFwas
to 65reduced from 70heat
ºF, the estimated ºF output
to 65150
ºF, the estimated heat output of the
of the
If the room air temperature was reduced from 70ºF to
distribution systemdistribution
would be approximately:
system
If the roomheat
65ºF, the estimated outputwould
air temperature
of thebedistribution
was approximately:
reduced from 70 ºF
system to 65 ºF, the estimated heat output of the
would be approximately: 130
distribution system would be approximately:
Btu r
q = 909 × (180 − 65) ≅ 104,500 te
hr − 65) ≅ 104,500 Btu 110 wa
q = 909 × (180 ply er
p at
Btuhr Su r nw
q = 909 × (180 − 65) ≅ 104,500 90 t u
hr
The circuit’s heat output increased because the ∆T between its supply water temperature and Re
The circuit’s heat
the room air temperature
output increased
increased. The
because
new ∆T
the ∆T between
for the system would the
be:
its supply water Thetemperature
circuit’s heat output
and theincreased
room air because
temperature∆T between 70 its supply water temperature and
0 10 20 30 40 50 60 70 80 90 100
increased.The The the room
new ∆Tair
fortemperature
the system increased. be:The new
wouldbecause ∆T for the system wouldofbe:
circuit’s heat output increased the ∆T between its supply%water designtemperature
heating loadand
the room air temperature Btuincreased. The new ∆T for the system
no would be: design
q 104,500
∆T = = hr = 23.88º F load load
8.01cd( f ) ⎛ ft 3 ⋅ min ⎞ ⎛ Btu ⎞ ⎛ 60.7lb ⎞ gal
⎜⎝ 8.01 gal ⋅ hr ⎟⎠ ⎜⎝ 1 lb⋅º F ⎟⎠ ⎜⎝ ft 3 ⎟⎠ (9 min ) Btu
q 104,500
∆T = = hr = 23.88º F
8.01cd( f ) ⎛ ft 3 ⋅ min ⎞ BtuBtu ⎛ 60.7lbAlthough
⎞ gal the value of the supply water minus return water
104,500
⎛ ⎞
q distribution ⎜ 8.01 galbased ⎟⎠ ⎜⎝ 1 lb⋅º Fhr
⋅ hrchanged
⎟⎠ ⎜ ⎟⎠ (9will
⎝ ft 3 ∆T
)
min be
Note that the ∆T
Note that the ∆T
∆T= of
of the
the = ⎝ changed
distribution system
system based
solely on a small change in the = 23.88º
room F for different hydronic systems using
different
solely on a small8.01cd( f )in the ft ⋅ min ⎞ ⎛ Btu ⎞ ⎛ 60.7lb ⎞different gal heat emitters, the relationship between supply
3
change ⎛ room air temperature.
air temperature. ⎜⎝ 8.01 gal ⋅ hr ⎟⎠ ⎜⎝ 1 lb⋅º F ⎟⎠ ⎜⎝ ft 3 ⎟⎠ (9 min )
22
However, not all hydronic systems meet the three Consider a 50-foot-long finned-tube baseboard, as
previously stated constraints. Many modern systems now shown in Figure 3-11.
use outdoor reset control to vary the water temperature
supplied to the distribution system. When this method of Imagine an experiment where the inlet water temperature
water temperature control is combined with a controller to the baseboard will be varied from 180ºF down to
that varies flow rate to maintain a fixed ∆T, the heat output 120ºF in increments of 20ºF. The flow rate at each inlet
from the distribution system decreases faster than it temperature will be adjusted to produce a nominal 20ºF
should based on outdoor reset control theory. temperature drop along the baseboard. The corresponding
heat output of the baseboard will then be calculated. The
This can be illustrated by determining the flow rates that results are shown in Figure 3-12.
would be necessary to maintain a constant ∆T as the
supply water temperature to the system decreases. As the supply water temperature decreases, with the ∆T
constrained to 20.1ºF, the heat output of the baseboard,
shown by the orange line, drops rapidly. For comparison,
Figure 3-11 the red line shows how the baseboard’s heat output
50 ft x 3/4" baseboard would normally decrease in proportion to the difference
(rated @ 600 Btu/hr/ft @200 ºF water) between the supply water temperature and the room air
temperature. This proportional relationship is the basis of
operation for many outdoor reset controllers (standalone
or integrated into boilers). At a supply water temperature
of 120ºF, and with the ∆T constrained to 20.1ºF, the heat
output of the baseboard is only about 55% of the output,
∆T constrained to 20.1 ºF based on the previously mentioned proportionality. This
suggests that heat output under the
combined effects of 1) reduced supply
water temperature based on outdoor
Figure 3-12
heat output based on holding reset, and 2) constrained ∆T, could result
∆T constrained to 20.1 ºF in inadequate comfort under partial load
conditions.
heat output being approx. proportional to (Ts-Tr)
assuming room temperature fixed at 70 ºF
WHY 20?
flow rate One misconception that has long been
20000 = 2.01 gpm
flow rates necessary to hold ∆T = 20.1 ºF
flow rate
= 1.45 gpm American hydronics market is unknown.
12000
Perhaps it came from the concept that
10000 if a system using water operates with a
8000 flow rate 20ºF temperature drop, the rate of heat
= 0.95 gpm delivery would be approximately 10,000
6000
Btu/hr per gpm of flow rate. While this is
4000 flow rate a close approximation to the rate of heat
= 0.50 gpm
2000 delivery, it all hinges on the word “if.” More
specifically, if the system operates with a
0
60 80 100 120 140 160 180
20ºF temperature drop, then each gpm
Supply water temperature (ºF) of water flow rate would transport about
10,000 Btu/hr.
50 ft x 3/4" finned-tube baseboard
23
For example, if a very high flow rate was maintained would be 7.3ºF. The heat output of the circuit increases
through a radiant floor tubing circuit, that circuit might with increasing flow rate because the average water
operate at a ∆T as low as perhaps 4ºF. That would temperature in the circuit is increasing. However, the
make the average water temperature in the circuit gains become smaller and smaller at higher flow rates.
only 2ºF lower than the supply water temperature. It
would also make the floor area served by the circuit It’s also possible to operate hydronic circuits at
relatively uniform in surface temperature. So, what’s temperature drops much higher than 20ºF. In Europe,
wrong with operating a circuit under this 4ºF ∆T? panel radiator systems are sometimes designed for a
From the standpoint of heat transfer, and achieving 20ºC temperature drop under design load conditions.
relatively uniform floor surface temperatures, there’s 20ºC converts to 36ºF. Using the higher ∆T allows the
nothing wrong. However, maintaining the high flow flow rates to each panel radiator to be reduced. If the
rate necessary for the low ∆T would require a larger ∆T was increased from 20 to 36ºF, the required flow rate
circulator that would use significantly more electrical would decrease to (20/36) = 56 percent of the flow rate
energy compared to that required to operate the system required at 20ºF. This may allow smaller tubing to be
at a higher ∆T. used to supply the radiator. It may also allow a smaller
circulator with a lower power motor to be used.
Figure 3-13 shows the ∆Ts that would occur in a
radiant floor heating circuit based on holding the inlet Figure 3-14 shows a thermograph of a panel radiator
temperature constant at 110ºF, and varying the flow rate operating with an estimated 40ºF ∆T between its supply
from 0.52 to 2.65 gpm. and return water temperature. The ∆T was estimated
based on the temperature scale and colors on the supply
At the 0.52 gpm flow rate, the circuit’s ∆T is almost and return piping.
26ºF. At the 2.65 gpm flow rate, the circuits flow rate
Figure 3-13
20
6000
Tin = 110 ºF Tout = 97.9 ºF 5000 15
∆T = 7.3 ºF
24
Figure 3-14
Notice the relatively even temperature gradient from the There are also applications in which very high ∆Ts are
top to the bottom of the panel radiator. This indicates possible in portions of a hydronic heating system. They
even flow distribution among the panels’ vertical flow typically involve the combination of a higher temperature heat
channels. source, such as a conventional boiler, and low-temperature
heat emitters, such as radiant floor
panels. Figure 3-15 shows an example.
Figure 3-15
low temperature Under design load conditions, this
heat emitters system supplies water at 180ºF to
105 ºF 90 ºF three Caleffi distribution stations. At
distribution distribution distribution station #1, this hot water
station station is mixed with return water from the
#1 #2
radiant panel circuits at 88ºF, to achieve
a supply water temperature of 105ºF.
180 ºF water
The radiant panel circuits served by
∆T = 92 ºF PEX or the distribution station operate at a ∆T
88 ºF water
PEX-AL-PEX
tubing 110 ºF of 105 - 88 = 17ºF under design load
conditions. The portion of the 88ºF
water not used for mixing returns from
master
the mixing manifold station.
mainfold
station
distribution
Although the radiant panel circuits
180 ºF
station operate at a typical design load
#3 temperature drop, the ∆T for the tubing
set carrying water between the boiler
manifold and distribution station #1
this 3-way thermostatic valve protects boiler operate at a ∆T of 180 - 88 = 92ºF.
from sustained flue gas condensation
At this ∆T, each gallon per minute
130 ºF
of water flow transports approximately
45,000 Btu/hr from the boiler manifold
VENT
to the distribution station. This allows
small diameter flexible tubing to carry
conventional a substantial rate of heat transfer. Low
boiler flow rates and small flexible tubing help
reduce installation cost.
25
4: OPERATING TEMPERATURE OF Precise analysis of energy flows in high thermal mass
HYDRONIC HEATING SYSTEMS hydronic systems must address transient system
response. The word transient implies that temperatures
The first law of thermodynamics can be expressed as and possibly flow rates within the system are changing
follows: significantly with time. This further implies that the
system’s thermal mass is absorbing or releasing heat.
Energy input = Energy Output + Energy Stored Transient system analysis is mathematically complex, and
as such, is usually done through computer simulation.
This principle of energy conservation is a widely used
“starting point” when analyzing physical systems involving A simplified analysis examines a system that is at or very
energy flow. It cannot be circumvented. Any analysis, close to steady state conditions. Steady state means that
method or product that claims to have “side-stepped” the the heat stored in the system’s thermal mass is neither
first law of thermodynamics is flawed. increasing or decreasing. Under steady state conditions,
the water temperatures and flow rates in various parts of
When this law is applied to hydronic heating systems, the system are not changing with time. Steady state analysis
the energy flows can be categorized as thermal energy produces “snapshots” of system performance, rather than
and electrical energy. Thermal energy (e.g., heat) is showing how operating conditions change over time.
the dominant form of energy in hydronic systems.
The electrical energy used in hydronic systems (other One of the most common “snapshots” of steady state
than those with electrically operated heat sources) is performance are when the system is operating at its
for operating the distribution system. In well-designed maximum heat conveyance rate. This is called “design
hydronic systems, electrical energy use is very small in load conditions.” Designers use this condition to size
comparison to thermal energy use. It is often treated equipment that can maintain specified comfort conditions
as insignificant, and as such, is not included in the when the building is losing heat at a maximum rate based
thermodynamic analysis of the system. In such cases, on the statistically lowest outdoor temperature, and
the first law can be limited to thermal energy flows in the assuming all zones in the system are operating.
system and stated as follows:
Because design load conditions assume steady state, the
Heat generated by the heat source = heat released thermal mass of the system is not included in the analysis.
The first law of thermodynamics now simplifies to:
from the system + heat stored within the system.
The ability of hydronic heating systems to store heat Rate of heat input by the heat source = rate of heat
varies significantly. Systems with high thermal mass release by the distribution system
components, such as a concrete floor slab with embedded
tubing, or a large thermal storage tank holding several The condition described by this relationship is called
hundred gallons of water, can store large quantities of thermal equilibrium. It’s a condition that all hydronic
heat. Systems with low metal and water volume store systems inherently try to establish and maintain. Assuming
minimal amounts of heat. that controls in the system do not intervene, and flow rates
remain steady, thermal equilibrium will eventually occur at
The way in which a hydronic heating system is operated any rate of heat input by the heat source. When it does, the
also affects how the heat it stores behaves. For example, temperatures in all parts of the system remain constant.
in a high thermal mass system operated with constant
circulation and outdoor reset control of supply water When a hydronic heating system begins operation from a
temperature, the influence of the stored heat is minimal cold start, the heat source is injecting heat to the system’s
under normal conditions. This type of system makes very fluid at a rate much higher than the rate of heat dissipation
gradual changes in its rate of heat output. However, if from the relatively cool distribution system. The fluid
the water flow through that system is turned on and off, temperature in all portions of the system increases under
and if the supply water temperature always remains close this condition. Assuming there is no interference by system
to the temperature required at design load conditions, controls, this increase in temperature continues until the
the influence of the thermal mass in determining room system “finds” it thermal equilibrium condition, where
temperature will be much greater. Wider swings in room the rate of heat input exactly matches the rate of heat
temperature are likely. dissipation. If there are no changes to the heat input rate,
or the ability of the distribution system to release heat, the
system remains at thermal equilibrium indefinitely.
26
If the rate of heat output at the heat source changes, or Assume that there are no controllers in this system, no
there’s a change in the distribution system, such as a zone pressure relief valve, and that all components used have
circuit turning on or off, thermal equilibrium is temporarily very high temperature and pressure ratings. Also, assume
disrupted. However, the system immediately seeks to that the room air temperature is 70ºF.
reestablish thermal equilibrium under the new operating
conditions. If the system’s thermal mass is small, thermal What average water temperature would be necessary in
equilibrium will be reestablished within a few minutes. the baseboard at thermal equilibrium?
Systems with high thermal mass take longer, in some
cases several hours, to reestablish thermal equilibrium Based on a detailed performance model for the baseboard,
conditions. the required average water temperature in the 20-foot-
long finned-tube baseboard would be 420ºF! It is possible
When the rate of heat input to the system increases, so to maintain water in a liquid state at this temperature,
do the water temperatures within the distribution system. but it requires a gauge pressure of 294 psi! This water
These temperature increases allow the distribution system temperature and its requisite pressure to maintain a liquid
to dissipate heat at a higher rate. When the rate of heat state is much higher than practical in any residential or
input decreases, so do the water temperatures within the light commercial hydronic system. Still, it represents a
system. The reduced temperature causes the distribution thermodynamic condition that the system is striving for.
system to dissipate heat at a lower rate. Fortunately, if this were a real system, one or more safety
devices, such as a boiler high limit aquastat or pressure
It’s important to understand that EVERY hydronic system relief valve, would interrupt the process long before it
always seeks to operate at thermal equilibrium. The reached such a dangerous condition.
conditions necessary for this to occur may not produce
the desired heat delivery. They may not allow the system Many hydronic systems operate in a similar manner. Each
to operate efficiently. They may not even allow the system time the heat source is turned on, the system’s water
to operate safely. Still, unless controllers within the temperature begins climbing toward thermal equilibrium,
system intervene, the system always strives to achieve but the operating controls on the system interrupt that
thermal equilibrium. progression when a specific temperature or pressure
condition is attained at which the designer wants the heat
Consider a hypothetical system with a 50,000 Btu/hr heat source to stop producing heat. A common example is
source and 20 feet of finned-tube baseboard, as shown the high limit controller on a boiler turning off the burner
in Figure 4-1. when the water temperature in the boiler reaches a set
“high limit” value, such as 190ºF. The system’s circulator
continues to operate, and thus heat continues to flow
Figure 4-1 from the thermal mass of the boiler to the distribution
20 feet finned-tube system. After a few minutes, the water temperature
50,000 Btu/hr
baseboard convector inside the boiler has dropped to perhaps 170ºF due to
heat disipaton heat dissipation, and the burner is turned back on. Each
boiler cycle represents an attempt by the system to reach
thermal equilibrium that is subsequently interrupted by
the high limit controller, so that operating conditions
remain safe and reasonably efficient.
Taverage = 420 ºF
(at thermal equilibrium Here’s another example: Imagine a hydronic floor heating
system that has eight parallel 350-foot circuits of ½” PEX
tubing embedded in a bare concrete slab. The system
is directly piped to a 50,000 Btu/hr boiler, as shown in
Figure 4-2. The boiler’s temperature limiting controller
has been set by the installer for 140ºF because that’s the
temperature the installer thinks the boiler should supply
to the distribution system. Also, assume that the load on
the system remains constant at 50,000 Btu/hr.
50,000 Btu/hr
When the system turns on, the boiler’s outlet temperature
heat input
climbs over a period of several hours and eventually
27
temperature at design load, and the
Figure 4-2 total heat output of the distribution
50,000 Btu/hr heat system at that same condition. This
dissipation
supply temperature information should be determined as
at thermal part of any accurate design process.
equilibrium = 99 ºF
Once a pairing of supply water
8 circuit of 1/2" temperature and corresponding
PEX, each 350 feet heat output from the distribution
long, embedded in system is established, a graph
concrete slab. can be created based on the heat
output of a distribution system
being approximately proportional
limit! to the difference between supply
controller! water temperature and room air
set for ! temperature.
140 ºF
Figure 4-3 shows this relationship
50,000 Btu/hr for a hypothetical distribution
boiler output system that’s designed to release
50,000 Btu/hr into a space at 70ºF
air temperature, when supplied with
180ºF water.
stabilizes at 99ºF. The burner remains in continuous The vertical axis of Figure 4-3
operation, but the water temperature leaving the boiler indicates the system’s heat output. The lower horizontal
doesn’t rise above 99ºF. The installer thinks there’s axis shows the difference between supply water
something wrong because the boiler is not reaching the temperature and room air temperature. This temperature
temperature (140ºF) that was set on the boiler’s difference can be thought of as the “driving ∆T” that
high limit controller. After several more hours of
continuous operation, the boiler’s outlet temperature Figure 4-3
remains at 99ºF. The installer now thinks that the design load condition
high limit controller is defective, removes it, and
heads to the wholesaler for a replacement. supply water temperature (ºF)
(assuming room air temp. = 70 ºF)
There’s nothing wrong with the boiler’s high limit 70 90 110 130 150 170 190
50000
heat dissipation from distribution system
28
“pushes” heat from the water out though the heat
Figure 4-4
emitters and into the room air.
10000
The yellow dot at the top right of the graph represents
design load conditions (e.g., a supply water temperature 9000
of 180ºF, and a corresponding heat dissipation of 50,000
8000
Btu/hr from the distribution system). The yellow dot in the
7000
For example, for the distribution system represented The greater the total surface area of heat emitters in a
in Figure 4-3 to release 20,000 Btu/hr, the ∆T between system, the lower the required supply water temperature.
supply water temperature and room air temperature
needs to be approximately 44ºF. If the room temperature LOWERING WATER TEMPERATURE
was 70ºF, the supply water temperature would need to be OF EXISTING SYSTEMS
approximately 44 + 70 = 114ºF. If the room temperature Many hydronic heating systems in pre-1980 North
was to be 65ºF, the necessary supply water temperature American buildings were designed when energy was
for the same rate of heat output would be 44 + 65 = 109ºF. relatively inexpensive. Boilers burning fossil fuels were
the dominant heat source, and their efficiency was
SUPPLY WATER TEMPERATURE of lesser concern than it is today. Designers typically
vs. HEAT EMITTER SURFACE AREA specified heat emitters, such as finned-tube baseboard,
The slope of the line of heat output versus the difference that required high supply water temperatures (180+ºF) at
between supply water temperature and room air design load conditions. High water temperatures allowed
temperature depends on the total surface area of the the heat emitters to be relatively small, which reduced
heat emitters in the distribution system. The greater the installation cost. Very few hydronic heating systems were
total surface area of heat emitter, the steeper the slope of designed around low-temperature heat emitters.
the line, as shown in Figure 4-4.
Today, these “legacy” distribution systems present
Steeper sloped lines imply greater heat output rates at a challenge when an older heat source needs to
lower supply water temperature. be replaced or supplemented by a modern lower
temperature heat source, such as a mod/con boiler or a
Figure 4-4 assumes that panel radiators are used as the hydronic heat pump.
heat emitters. The larger the panel radiator’s surface
area, the greater it’s heat output at a given supply water Although a mod/con boiler can produce the high water
temperature. temperatures required by older distribution systems,
they do so with a significant loss in thermal efficiency.
When a modern heat source such as a modulating/ High-temperature distribution systems do not create
condensing boiler or hydronic heat pump is used, a critical conditions that allow flue gases to condense inside the
design objective is to keep the required supply water boiler. Without flue gas condensation, a supposedly high-
temperature to the distribution system as low as possible. performance mod/con boiler will yield minimal efficiency
Doing so improves the thermal efficiency of the heat gains over a lower cost conventional boiler.
source, and thus minimizes the primary energy required.
29
Most hydronic heat pumps cannot reliably produce water For example, assume an existing building has a design
temperatures over 125ºF. Those that can reach higher heating load of 100,000 Btu/hr, based on maintaining
temperatures often do so with a major decrease in their an interior temperature of 70ºF. The existing DRAFT (4-16-18)
hydronic
coefficient of performance. distribution system uses standard finned-tube baseboard
DRAFTand (4-16-18)
requires a supply water temperature of 180ºF at
In summary, nearly all contemporary hydronic heat design conditions. Also assume
load conditions. that improvements
Also, assume to the building env
that improvements
sources perform better when matched with a distribution to the building envelope have reduced the design load
1. Reduce load from improvements
100,000 Btu/hr such
to 70,000 Btu/hr. The new supply wa
system that operatesthe
at adesign load temperature.
lower water of the building envelope
What from through
100,000 Btu/hr to 70,000 as added
Btu/hr. The new supply
follows are concepts better
insulation, and methods
windowsfor and
lowering the water
reduced waterdistribution
air leakage.
system
temperature under
to the designdistribution
existing load conditions can be estima
system
temperature of existing higher temperature hydronic under design load conditions can be estimated using
distribution systems. Formula 4-1:
2. Add heat emitters
ways to to the existing system. ⎛ 70,000 ⎞
The two fundamentals reduce the supply water Tnew = 70 + ⎜ × (180 − 70) = 147º F
temperature of any hydronic heating system are: ⎝ 100,000 ⎟⎠
1. ReduceCombinations
the design of these
load two building
of the approaches are also
envelope possible.
A graph of the supply water temperature versus outdoor
A graph of the supply water temperature versus outdoor tempe
through improvements such as added insulation, better temperature for both the existing building (e.g., with
windows and reduced air leakage. building
design (e.g.,
load of with design
100,000 load
Btu/hr), andof after
100,000
the Btu/hr),
envelopeand after th
Building envelope improvements reduce the designreduced heatingthe
improvements load
which of the building.
reduced
design load
the After
design
to 70,000 suchis shown in Figure 4
load
Btu/hr,
to 70,000
2. Add heat emitters to the existing system. Btu/hr, is shown in Figure 4-5.
improvements are made, the original hydronic distribution system can meet the reduced design
Combinations
load of these
while two approaches
operating at lowerare also possible.
supply In this example, reducing the design heating load from
water temperatures.
[insert figure 4-5]
100,000 Btu/hr to 70,000 Btu/hr reduced the required
Building envelope improvements reduce the design supply water temperature from 180ºF to 147ºF.
heating load of the building. After such improvements are
made, theThe change
original in supply
hydronic water system
distribution temperature depends on the change
can meet in design
180 ºF supply @ designheating
load load. The
(existing system)
newdesign
the reduced supply water
load temperature
while operating atcan be supply
lower Figure
determined based4-5on the same concepts used for
147 ºF supply @ design load
water temperatures.
(after envelope improvements)
outdoor reset control. It can be calculated using formula 4-1:ºF supply @ design load
180
The change in supply water temperature depends on (existing system)
190
the change in design heating load. The new supply
147 ºF
170supply @ design load
Formula 4-1:
water temperature can be determined based on the
Supply water temperature (ºF)
110
⎛ Q ⎞
Tnew = Tin + ⎜ new ⎟ × (TDe − Tin )
⎝ Qexisting ⎠ 150 90
70
130 70 60 50 40 30 20 10 0
Where: Outdoor temperature ( ºF)
Tnew = supply water temperature at design load after
Where: improvements (ºF)
building envelope 110
Tin = desired indoor air temperature (ºF)
Tnew =heating
Qnew = design supplyload
water temperature
after at design load after building envelope improvements (ºF)
building envelope
improvements (Btu/hr) 90
Tin = desired indoor air temperature (ºF) In this example, reducing the design heating load from 100,00
Qexisting = existing design heating load (before
Qnew =(Btu/hr)
improvements) the required supply
design heating load after building envelope improvements water temperature from 180 ºF to 147 ºF.
(Btu/hr)
70
TDe = existing supply water temperature at design load 70 60 50 40 30 20 10 0
Qexisting = existing
(before improvements) (ºF) design heating load (before improvements) (Btu/hr)Outdoor temperature ( ºF)
TDe = existing supply water temperature at design load (before improvements) (Btu/hr)
For example, assume an existing building has a design heating load of 100,000 Btu/hr, based
Page " 70 of " 128
30 on maintaining an interior temperature of 70 ºF. The existing hydronic distribution system uses
standard fin-tube baseboard and requires a supply water temperature of 180 ºF at design load
ADDING HEAT EMITTERS TO tubing that doesn’t have fins on it. The existing finned
LOWER SUPPLY WATER TEMPERATURE tube length will be designated as Le.
If reducing the building’s design heating load is not an
option, or does not lower the required supply water Step 3: Determine the desired (lower) supply water
temperature to the desired value, it will be necessary to temperature for which the system is to supply design
add heat emitters to the system. load output.
A wide variety of heat emitters could be added. For Step 4: Estimate the lower average circuit water
example, an existing high-temperature baseboard system temperature by subtracting 5 to 10ºF from the supply
could have more baseboard added to it, assuming water temperature determined in Step 3. In circuits with
sufficient wall space is available. Another option might more than 2 gallons per minute flow rate through the
be to change out some existing baseboard emitters with baseboard, assume the average water temperature will
new baseboard emitters that have higher heat output be 5ºF below the supply water temperature. In circuits
ratings. It may also be possible to add a different type of with less than 2 gallons per minute flow rate through the
heat emitter to the system. An example would be adding baseboard, assume the average water temperature will
panel radiators to an existing baseboard system. Another be 10ºF below the lower supply water temperature.
would be adding some areas of radiant panel heating
(floor, wall or ceiling) to the existing system. Step 5: Find the new average circuit water temperature
on the horizontal axis of the graph in Figure 4-6. Draw a
The choice of which type of heat emitter to add will vertical line up from this point until it intersects the red
depend on several factors, including: curve. Draw a horizontal line from this intersection to the
vertical axis of the graph, and read the heat output of the
1. Availability of different makes/models of heat emitters. finned tube at the lower average circuit water temperature.
2. Cost of the new heat emitters. This number is designated as qL. The green lines and
3. How difficult it is to integrate the new heat emitters into numbers in Figure 4-6 show how qL is determined for an
the building. average circuit water temperature of 115ºF.
4. Aesthetic preferences.
5. Floor coverings (in the case of radiant floor panels).
6. Surface temperature limitations (in the case of radiant Figure 4-6
panels).
7. The specific supply water temperature that is to supply Note: This graph is based on
standard residential finned-tube
design load output in the renovated distribution system. baseboard with 2.25" square fins and
3/4" tubing, operating at 1 gpm flow
Each project has to be evaluated individually based on rate. It does NOT include the 15%
these factors. heating effect factor allowance
included in some I=B=R rating tables.
ADDING MORE FINNED-TUBE BASEBOARD 900
One way to lower the required supply water temperature of
800 65 ºF air temperature
an existing baseboard system is to add more baseboard.
Heat output per foot (Btu/hr/ft)
entering baseboard
700
The following procedure can be used to calculate the
amount of finned-tube baseboard to be added to reduce 600
q = 146 Btu/hr/ft
the supply water temperature at design load to a pre- 500 L
determined value. It assumes that the baseboard being
added is the same make and model as the existing 400
baseboard. It also assumes that the existing baseboard
300
is a standard residential-grade product with nominal
2.25” square aluminum fins with an I=B=R rated output of 200
approximately 600 Btu/hr/ft at 200ºF water temperature. 115 ºF
100
Step 1: Accurately determine the building’s design heat load. 0
65 85 105 125 145 165 185 205 220
Step 2: Determine the total length of finned tube in the Water temperature (ºF)
existing distribution system. Do not include the length of
31
0
65 85 105 125 145 165 185 205 220
Water temperature (ºF)
Step 6: Determine the length of baseboard to be added In most buildings, adding this much baseboard is not a
Formula 4-2:
using Formula 4-2. practical solution, especially in kitchens or bathrooms.
Alternatives include using baseboard with higher heat
Formula 4-2: output or using other types of heat emitters to achieve
design load the necessary design load output.
Ladded = − Le
qL
One option is to consider adding “high output” finned-
Where: tube baseboard rather than standard baseboard. Figure
Ladded = length Where:
of finned tube of same make/model 4-7 shows the heat available from one model of high
baseboard to be added
Ladded =(feet)
length of finned-tube of same make/model output baseboard
baseboard to(shown as (feet)
be added the blue curve), and for
design load = design heating load of building (Btu/hr) comparison, standard residential baseboard (shown as
design loadat= the
qL = output of baseboard design heating
lower load
average
DRAFT of building
circuit
(4-16-18) the(Btu/hr)
red curve).
water temperatureqL(Btu/hr/ft)
= output of baseboard at the lower average circuit water temperature (Btu/hr/ft)
Le = total existing length of baseboard in system (feet) The steps of the previous procedure can be modified
For example: Assume a building
Le = total existinghas a calculated
length designinload
of baseboard toofdetermine
system 40,000
(feet) Btu/hr,
theand its
amount of high output finned-tube
For example: Assume a building has a calculated baseboard that is
distribution system contains 120 feet of standard residential finned-tube baseboard. The goal required to isreduce the supply water
design load of 40,000 Btu/hr, and its distribution system temperature to the system under design load.
to reduce
contains the feet
120 supplyofwater temperature
standard to 120finned-tube
residential ºF at design conditions, using more of the same
baseboard.The
baseboard. Assume
goaltheistemperature
to reduce drop
the ofsupply
the distribution
waterPagesystem
Steps is 10
1-4:
" 73 of ºF. Determine the
Same
" 128
temperature to 120ºF at design conditions, using more
amount of baseboard that must be added:
of the same baseboard. Assume the temperature drop of Step 5: Determine the output of high-output baseboard
the distribution system is 10ºF. Determine the amount of at the average circuit water temperature using Figure
baseboard
Solution: that must be added: 4-7 (or manufacturer’s literature for a specific make and
model).
Solution:
Step 1: The design load has been calculated as 40,000 Btu/hr. Step 6: The required length of high output baseboard to
Step 1: The design load has been calculated as 40,000 add to the system is found using Formula 4-3.
Btu/hr.
Step 2: The total amount of finned-tube in the system is 120 feet.
Step 2: The total amount of finned tube in the system is Figure 4-7
120 feet.
Step 3: The lower supply water temperature at design load will be 120ºF. high output standard
Step 3: The lower supply water temperature at design fin-tube fin-tube
baseboard baseboard
load will be 120ºF. 500 = 115ºF.
Step 4: The lower average circuit water temperature will be 120 - (10/2)
450 65 ºF air temperature
Step 4: The lower average circuit water temperature will entering baseboard
be 120 - (10/2) = 115ºF. 400
Step 5: The output of the finned-tube at an average circuit water temperature of 115 ºF is
Heat output (Btu/hr/ft)
determined
Step from Figure
5: The output of the 4-6 as 146
finned tubeBtu/hr/ft.
at an average circuit 350
water temperature of 115ºF is determined from Figure 4-6
300
as 146 Btu/hr/ft.
Step 6: The required additional length of baseboard is now calculated using Formula 4-2:
250
Step 6: The required additional length of baseboard is
now calculated using Formula 4-2: 200
150
⎡ Btu ⎤
100
design load ⎢ 40,000 ⎥
Ladded = − Le = ⎢ hr − 120 ⎥ = 154 ft
qL Btu 50
⎢ 146 ⎥
⎢⎣ hr ⋅ ft ⎥⎦ 0
65 75 85 95 105 115 125 135 145 155
Although it might be possible to add 154 feet of baseboard Water temperature (ºF)
to Although it might
the system, be possible
it would require to add
lots of 154 feet ofwall
available baseboard
space. to the system, it would require lots of
available wall space. In most buildings, adding this much baseboard is not a practical solution,
especially in kitchens or bathrooms. Alternatives include using baseboard with higher heat
32output or using other types of heat emitters to achieve the necessary design load output.
Formula 4-3.
Formula 4-3:
If the added length of high output baseboard cannot be accommodated, another option is to
Assume a building has a calculated design load of 40,000 Btu/hr, and its distribution system
contains 120 feet of standard residential finned-tube baseboard. The goal is to reduce the
supply water temperature to 120 ºF under design load conditions. Panel radiators are available
Solution: First, use Formula 4-4 to determine the output required of the new radiators.
in 24” x 72” size that can release 4,233 Btu/hr when operated at an average water temperature
of 115 ºF in rooms with 70 ºF interior temperature. How many of these radiator are necessary to
meet the design load?
Solution: First,
Solution: First, n = design
Quse
use Formula
required of the new radiators.
Formula load -toQ
4-4the
4-4 to determine design
determine
e =required
output load
the
of the - q L 6.
output
new radiators. ( )( )
= 40,000-
Le What type (of
146 )(120 )will
control = 22,
be480Btu
used to/ hrregulate heat
output to each zone of the distribution system?
Qn = design load - Q e = design load - ( q L ) ( Le ) = 40,000- (146 ) (120 ) = 22, 480Btu / hr There is no one best approach. Every situation must be
The number of radiators needed is then found as follows:
evaluated individually while weighing these factors to
The number of radiators needed is then found as follows: determine the best fit for that project.
The number of radiators needed is then found as follows:
22, 480Btu / hr 22, 480Btu / hr CONVERTING SERIES LOOPS
= 5.3 radiators = 5.3 radiators TO PARALLEL BRANCHES
4233
Btu / hr
Btu / hr
radiator 4233 Many residential hydronic systems have finned-tube
radiator
Page " 78 of " 128 baseboards connected in series or “split-series” circuits,
as shown in Figures 4-8 and 4-9.
The designer could either add 6 of these panel radiators,Page " 78 of " 128
or choose a slightly higher supply water temperature and When several heat emitters will to be added to a system
use 5 radiators. using series or split-series connected baseboards, they
should NOT be simply cut into the series circuit. Doing
Another option is to use panel radiators of different sizes, so could substantially increase the flow resistance of that
provided that their total output at the lower supply water circuit, which reduces flow, assuming the same circulator
temperature could meet the value of Qn. In this example, is used. Adding heat emitters in series also increases the
the 6 new radiators would be combined with the 120 feet temperature drop of the circuit. This reduces the heat output
of existing baseboard to provide the 40,000 Btu/hr design of heat emitters near the end of the circuit, especially when
load at a supply temperature of 120ºF. the supply temperature to that circuit is lowered.
A similar calculation could be made for fan-coils, air One approach is to make strategic cuts into the series
handlers or other heat emitters. circuit where it is easiest to access, and reconnect
the segments back into a parallel distribution system.
In the case of radiant panels, the
designer needs to determine the output
of each square foot of panel based on Figure 4-8
the lower average circuit temperature,
and the specific construction of the
panel. The total required panel area is Auxiliary
VENT
34
These cuts could make each room a separate parallel In this example the existing series circuit was divided into
circuit. They might also make a group of two rooms into four branch circuits. Supplemental heat emitters were
a new zone. added to each of these branch circuits. Two of the branch
circuits received additional finned-tube baseboard, and
One of the easiest ways to divide an existing series loop the other two received panel radiators. These heat emitter
or split-series distribution system into multiple parallel selections illustrate that multiple types of supplemental
circuits is by creating a homerun distribution system. Each heat emitters can be used depending on available wall
heat emitter, or grouping of an existing heat emitter and space, budget and aesthetic preferences.
a supplemental heat emitter, is supplied by a separate
circuit of PEX or PEX-AL-PEX tubing. This tubing is easy In some branch circuits, the supplemental heat emitters
to route through cavities or along framing. The homerun were added upstream of the existing baseboard. In others,
circuits begin and end at a manifold station. The concept they were added downstream of the existing baseboard.
is shown in Figure 4-10. The choice depends on the available wall space and
Figure 4-10
manifold
station
35
placement of the existing baseboard within each room.
Figure 4-11
Designers should estimate the water temperature in
the circuit at the location where the supplemental heat baseboard enclosure
emitter will be placed, and size it accordingly. 3/4" copper x 1/2" PEX-AL-PEX vent vent ell fitting
radiator valve
The ¾” copper tubing in the existing circuit was cut at
locations that preserved a reasonable amount of existing 3/4" finned-tube element
tubing, but also allow convenient transition to ½” PEX
or PEX-AL-PEX tubing. Adapter fittings for transitioning
from ¾” copper to ½” PEX or PEX-AL-PEX tubing are
readily available. The ½” PEX or PEX-AL-PEX supplies
thermostatic
and returns are routed back to a manifold station. That operator
manifold station should be equipped with individual
circuit-balancing valves that allow the flow rate through
each of the new branch circuits to be adjusted.
All four branch circuits in Figure 4-10 operate simultaneously 1/2" MPT
1/2" x 1/2" PEX-AL-PEX 1/2"
(e.g., they are not configured as individual zones). As adapter fitting PEX-AL-PEX
PEX-AL-PEX
such, this distribution system presents a constant flow tubing tubing
resistance. Due to the parallel versus series configuration,
that flow resistance of the modified distribution system is
likely to be lower than that of the original series circuit. This 90º turn as it passes through the valve, and flows into
should be verified by calculating the head loss or pressure the baseboard element. The other end of the finned-
drop of the branch with the greatest flow resistance using tube element can be equipped with a transition adapter
standard hydronic pipe analysis methods. If the head (straight or 90º) to convert from ¾” copper to ½” PEX or
loss and total flow rate through the modified distribution PEX-AL-PEX.
system is significantly lower than that of the original series
circuit, consider a replacement circulator that operates Another type of thermostatic radiator valve allows the
with reduced power input. valve body and actuator to be mounted within the
baseboard enclosure, while the adjustment knob is
A significant benefit of a parallel distribution system is mounted at normal thermostat height on the wall. The
that all branches receive water at approximately the same adjustment knob connects to the valve actuator using a
temperature. This is likely to boost the heat output of capillary tube, as seen in Figure 4-12.
some existing baseboards that were previously located
near the end of the series circuit.
Figure 4-12
CREATING NEW ZONES
Another advantage of parallel distribution systems is
the ease of creating multiple zones. If the existing series
circuit is converted to multiple branches, each of those
branches could be equipped with a thermostatic radiator
valve. These non-electric valves automatically modulate
to vary the flow rate in each branch in response to the
room temperature. As room temperature begins to drop,
the thermostatic valve opens to increase flow through
that branch circuit to boost heat output, and vice versa.
36
Figure 4-13 MODIFIED DISTRIBUTION SYSTEM
TRV existing baseboard added baseboard
TRV
TRV
pressure added
regulated panel
circulator radiator
1/2" PEX pr PEX-AL-PEX
tubing (typical)
manifold
station
thermostats
Figure 4-14
MODIFIED DISTRIBUTION SYSTEM
existing baseboard added baseboard
added
panel
radiator
pressure
regulated
circulator
1/2" PEX pr PEX-AL-PEX added
tubing (typical) panel
radiator
manifold
station
37
It’s also possible to use panel radiators with built-in necessary supplemental heat emitters. However, if the
thermostatic radiator valves. piping modifications to do this are comparable in cost/
time to creating two independent zones, then the latter is
Figure 4-13 shows how the distribution system can be arguably a better choice.
modified using thermostatic radiator valves to create a
distribution system with four independently controlled 4. Once all the supplemental heat emitters have been
zones. This adds flexibility for adjusting interior comfort selected, and the proposed modifications to the
conditions far beyond that of the original series loop system. distribution system have been sketched, always run a
flow and head loss analysis for the modified system. This
Another possibility is to install a low-voltage (24 VAC) is used to confirm sufficient flow to each branch, and to
manifold valve actuator on each circuit valve at the determine a suitable circulator for the modified system.
manifold station. These actuators are wired to four new
thermostats, one for each zone. This option is shown in 5. If an existing conventional boiler will be used as
Figure 4-14. the heat source for the modified system, which now
operates at significantly lower water temperatures, be
The systems shown in Figures 4-13 and 4-14 use valves sure the boiler is protected against sustained flue gas
for zoning. In Figure 4-13, non-electric thermostatic condensation by installing a thermostatic mixing valve
radiator valves regulate the flow through each parallel near the boiler, as shown in Figure 4-15.
branch circuit. In Figure 4-14, low-voltage manifold
actuators are attached to valves within the return
manifold. In both cases, the original circulator has
Figure 4-15
been replaced with a variable-speed pressure-regulated
circulator. These circulators automatically adjust their distribution
speed and power input as the valves open, close or closely system
modulate flow. This helps stabilize the differential pressure spaced
across the manifold station, and maintain consistent flow tees
rates within each zone circuit, regardless of what other
zones are operating. These modern circulators also have
significantly lower electrical energy consumption relative
to standard wet rotor circulators with permanent split thermostatic
capacitor (PSC) motors. mixing valve with
high Cv. Minimum
DESIGN GUIDELINES setting = 130 ºF
The modifications shown to convert a series baseboard
boiler
circuit into parallel branch circuits are just a few of many
circulator
possibilities. Each conversion situation must consider
the exact layout of the existing heat emitters, and
the practicality of modifying the system into parallel
branches. Designers should follow these guidelines.
existing boiler
1. Always determine what type of supplemental heat
emitter will be used in each room, and where it will be
located before modifying the piping.
38
5. HEAT EXCHANGER FUNDAMENTALS heat exchanger is almost always limited by the natural
convection at its outer surface.
Many hydronic heating and cooling systems need to
move heat from one fluid to another without mixing those Figure 5-1 illustrates a typical immersion heat exchanger
fluids. One example is heat moving from hot “system coil within a tank.
water” that passes through a cast iron boiler into cooler
domestic water that is being heated for showers, washing,
Figure 5-1 tank
etc. Another example is heat moving from an antifreeze
solution that flows through a solar collector to water
within a thermal storage tank. The fluids exchanging
heat may be at significantly different temperatures and immersion heat bouyancy-
pressures, and must be fully isolated from each other. exchanger coil driven natural
Such processes require a heat exchanger. hot fluid within tank convection
inlet
There are many types of heat exchangers. Nearly all of
them separate the fluids exchanging heat using metal
surfaces. Common materials used to separate the fluids
include copper, cupronickel, stainless steel, carbon steel
and titanium/stainless steel alloys. These metals all have
relatively high thermal conductivity, and thus present
minimal conduction resistance.
hot fluid
outlet
EXTERNAL vs. IMMERSION HEAT EXCHANGERS
The types of heat exchangers commonly used in hydronic
systems can be categorized as external or immersion.
39
All external heat exchanger designs create two pressure- when operated at the same inlet fluid temperatures and
tight cavities that separate the fluids exchanging heat. temperature drops. The larger heat exchanger will also
They also create an internal surface across which heat have a lower head loss than the smaller exchanger when
moves by conduction through the metal separating the operating at the same flow rate.
two fluids.
Small brazed plate heat exchangers, such as 3” x 8”
FLAT PLATE HEAT EXCHANGERS x 20 plates, are often used in residential domestic
Flat plate heat exchangers water-heating applications. Larger brazed plate heat
Figure 5-3
are the most commonly exchangers, such as 10” x 20” x 80 plates, are capable of
used heat exchangers in transferring heat at several hundred thousand Btu/hr, and
modern hydronic systems. are used in applications such as snowmelting or district
In smaller sizes, these heat heating for small commercial buildings.
exchangers are made by
stacking specially formed The specifications for brazed plate heat exchangers
stainless steel plates, as often list a certain rate of heat transfer. It’s very important
shown in Figure 5-3. to realize that this rating is based on specific entering
fluid temperatures and flow rates. For example, a certain
Courtesy of GEA PHE Systems
heat exchanger. Once brazed, the plates are permanently perimeter seal as well as
sealed in place, and cannot be disassembled for cleaning. internal seals between
Brazed plate heat exchangers are usually made in one adjacent plates. The stack
of three common plate sizes (3” x 8”, 5” x 12”, or 10” x of plates and gaskets are
20”). Other plate sizes such as 5” x 20” are sometimes capped at each end by
available. The thermal and hydraulic performance of thick steel plates capable
a brazed plate heat exchanger is determined by the of withstanding high
number of plates used. For example, a 5” x 12” x 40 pressures if necessary. The internal plates and end plates
plate heat exchanger has twice as many plates as a 5” x are held in alignment by a structural steel frame. This
12” x 20 plate unit. The 40-plate heat exchanger will be type of heat exchanger is called a “plate & frame” heat
capable of approximately twice the rate of heat transfer exchanger. An example is shown in Figure 5-4.
40
One benefit of plate & frame heat exchangers is that FLOW DIRECTION THROUGH HEAT EXCHANGERS
the frame is often built so that additional plates can In heat exchangers that operate with liquids, there are
be added to the stack if ever needed. An example two possible flow configurations:
would be when the rate of heat exchange has to be
maintained using a new heat source that supplies lower • Both liquids pass in the same direction through the heat
temperature hot water to the heat exchanger. Another exchanger.
would be when the rate of heat exchange needs to be • The liquids flow in opposite directions through the heat
increased to accommodate expansion of an existing exchanger.
heating system. It’s also possible, to disassemble a
plate & frame heat exchanger if required for cleaning When the two liquids move in the same direction, the
or maintenance. configuration is called “parallel flow.” When the two fluids
move in opposite directions, the configuration is called
Figure 5-5 shows the rear side of a large plate & frame “counterflow.”
heat exchanger used in a district heating application.
Notice that the threaded steel rods that hold the
Figure 5-6
plate stack together extend well beyond the rear end
plate. If more plates are to be added, the nuts on the Thot
treaded shafts are removed, allowing the end plate in
Tcold
in
Thot
in Thot
out
Tcold Tcold
in parallel flow out
Thot
in
ho
tf
Tcold luid
out
co
ld
flu Thot
id out
Tcold
in
Thot
in
Thot
out
Tcold
out counterflow Tcold
in
41
Figure 5-6 show how the temperature of the two liquid Recall from previous discussions that the rate of
streams would change as they flow through a heat conduction heat transfer is directly proportional to the
exchanger piped for parallel flow versus one piped for temperature difference between the outer surfaces of
counterflow. a material through which heat is passing. The higher
this temperature difference, the greater the rate of heat
In a parallel flow configuration, the temperature of the transfer by conduction.
cooler liquid absorbing heat can never meet or exceed
the temperature of the exiting hot liquid. All other factors Similarly, the rate of convective heat transfer is directly
being equal, the rate of heat exchange is limited by the proportional to the temperature difference between the
temperature of the exiting hot fluid stream. temperature in the bulk of the fluid stream (e.g., away
from the boundary layer), and the temperature of the solid
When a counterflow configuration is used, the leaving material the fluid is passing over. It’s also dependent on
temperature of the stream absorbing heat can be higher the convection coefficient between the fluid and surface.
than the leaving temperature of the stream providing heat.
These relationships suggest that the rate of heat transfer
The rate of heat exchange will always be higher when a between two fluids passing through any heat exchanger
heat exchanger is configured for counterflow operation. would depend on the temperature difference between the
two fluids. However, the temperature difference between
Counterflow should also be used with immersion heat the two streams is not the same at all locations on the
exchangers. Figure 5-7 shows how the flow through heat exchanger. Each fluid is either losing or gaining heat
an immersion coil heat exchanger that’s adding heat to as it passes through the heat exchanger, and thus the
the tank (on left) is piped so that flow is in the opposite temperature difference between the fluids varies depending
direction of natural convection currents inside the tank on where it is measured within the heat exchanger.
(e.g., flow is from top to bottom of coil).
Heat transfer theory defines a specific temperature
Another immersion heat exchanger that removes heat difference based on the fluid temperatures at all four
from the right side of the tank is also piped for counterflow connections of the heat exchanger. That difference
(e.g., flow is from bottom to top of coil). is called the log mean temperature difference, and is
defined by Formula 5-1.
RATE OF HEAT EXCHANGE
The rate of heat transfer between
two fluids passing through a heat Figure 5-7
check valves prevent
exchanger is dependent on several thermosiphoning
factors, including:
unpressurized
thermal storage tank vent
• The internal surface area that
separates the two fluids. air at
heat load
• The thermal conductivity and atmospheric
source
thickness of the plate material. pressure
• The convection coefficients
developed between each fluid and
the internal surfaces.
• The flow rate on each side of the
heat exchanger.
• The specific heat, density and
viscosity of each fluid.
• The insulation (if any) surrounding heat
the heat exchanger. input heat
coil extraction
• The direction of flow of one fluid
coil
relative to another.
• The “log mean temperature
general direction of flow
difference” between the two fluids. driven by natural convection
in vicinity of vertical coil
42
Figure 5-8 Figure 5-9
(∆T)
1
140 ºF 100 ºF
140 ºF 100 ºF
(∆ T )1 − (∆ T )2
LMTD = DRAFT (4-16-
⎡ (∆ T )1 ⎤
side absorbing heat
122 ºF 77 ºF
LMTD =
(Tho − Tci ) − (Thi − Tco ) the fluid at the other end, divided by the natural logarithm
paralle
⎡ (T − T ) ⎤ of the ratio of these two temperature differences. This is
Tho =(ºF)
temperature of the fluid supplying heat at theflow outletdirections
of the heat exchanger (ºF) fluids passing through the
side supplying heat
122 ºF 77 ºF
counterflow
LMTD =
(Tho − Tci ) − (Thi − Tco ) = (122 − 77 ) − (104 − 68 ) = 45 − 36 = 9 = 40.3º F
⎡ (T − T ) ⎤ ⎡ (122 − 77 ) ⎤ ⎡ 45 ⎤ 0.223
ln ⎢ ho ci ⎥ ln ⎢ ⎥ ln ⎢ ⎥
⎣ (Thi − Tco ) ⎦ ⎣( 104 − 68 )⎦ ⎣ 36 ⎦
104 ºF 68 ºF
122 ºF 68 ºF
parallel flow
side absorbing heat
side supplying heat
LMTD =
(Tho − Tci ) − (Thi − Tco ) DRAFT
=
(122 − 68(4-16-18)
) − (104 − 77 ) = 54 − 27 = 27 = 39.0º F
⎡ (T − T ) ⎤ ⎡ (122 − 68 ) ⎤ ⎡ 54 ⎤ 0.693
ln ⎢ ho ci ⎥ ln ⎢ ⎥ ln ⎢ ⎥
⎣ (Thi − Tco ) ⎦ ⎣ (104 − 77 ) ⎦ ⎣ 27 ⎦
Where:
Q = rate77
104 ºF of ºF
heat transfer through heat exchanger (Btu/hr)
U = overall heat transfer coefficient of the heat exchanger (Btu/hr/ft2/ºF)
Q = rate of heat transfer through heat exchanger (Btu/hr) U = overall heat transfer coefficient of the heat
LMTD = log mean temperature difference across the heat exchanger (ºF)
U = overall heat transfer coefficient of the heat exchanger (Btu/hr/ft2/ºF)
exchanger (Btu/hr/ft2/ºF) hc = convection coefficient for the fluid absorbing heat
A = area of surface(s) separating fluids inside the heat (Btu/hr•ft2•ºF)
exchanger (ft ) The value of “U” depends on the convection
2
hh = coefficients for each fluid,
convection coefficient asfluid
for the wellreleasing
as the thickness,
heat
LMTD = log mean temperature difference across the (Btu/hr•ft2•ºF)
heat exchanger (ºF)
shape, and thermal conductivity of the surfaces separating the fluids. If is defined by formula
d = thickness of wall separating the fluids (ft)
5-3. k = thermal conductivity of wall separating the fluids
The value of “U” depends on the convection coefficients (Btu/hr•ft•ºF)
for each fluid, as well as the thickness, shape and thermal
conductivity of the surfaces separating the fluids. It is The values of the convection coefficients hh and hc can
defined by Formula Formula
5-3. 5-3: vary widely depending on the fluid, its density, specific
heat and viscosity, as well as the fluid’s flow rate. These
Formula 5-3: 1 conditions need to be evaluated on both sides of the
U= heat exchanger. The theoretical determination of the
⎡1 d 1⎤ convection coefficients is mathematically complex. It
⎢h + k + h ⎥ is usually based on empirical correlations of operating
⎣ c h ⎦
Where:
44
U = overall heat transfer coefficient of the heat exchanger (Btu/hr/ft2/ºF)
conditions that are expressed in the form of dimensionless numbers,
Figure 5-11 such as the Reynolds number, Nusselt number and Prandtl number. Many
heat transfer textbooks summarize methods for estimating convection
ATD = 120-110 = 10 ºF coefficients for heat exchangers of specific types and geometries.
1
Typical values of U in water-to-water heat exchangers are in the range
120 ºF 110 ºF of 100 to 300 (Btu/hr/ft2/ºF).
difference” (ATD). Since all heat exchangers have two inlets and two
outlets, there are technically two approach temperature differences, as
shown in Figure 5-11.
Figure 5-12a
45
Figure 5-12b
Sizing and selection software allows
designers to enter values for flow rates,
temperatures, type of fluids being used and
required rates of heat transfer. The software
uses these inputs to select one or more
specific heat exchanger configurations that
can meet or slightly exceed the required
thermal performance. The software also DR
provides pressure drop or head loss
information, which is used for the hydraulic
design of FOULING
the circuitFACTORS
containing FOR HEAT EXCHA
the heat
exchanger.
FOULING FACTORS
The listed thermal and hydraulic performa
FOR HEAT EXCHANGERS
assumption
The listed thermal that theperformance
and hydraulic heat exchanger is fre
of heat exchangers is usually based on
accumulation
the assumption that theof heat
scaling on the surfaces t
exchanger
is free ofheat
any exchanger’s
internal scaling
thermaldebris.
or performance. F
A relatively thin accumulation of dirt or
scaling on keepthethesurfaces
surfacesthat
of heat exchangers cle
separate
the two fluids can significantly lower the
heat exchanger’s thermal performance.
For optimal performance and long life, it’s
The affect of scale accumulation is some
important to keep the surfaces of heat
exchangers Formula
clean. 5-4:
Formula 5-4:
1 1
Rf = −
U dirty U clean
47
Caleffi DirtMag separators are recommended if either In addition to external or immersion heat exchangers that
circuit passing through the heat exchanger contains may be in the system, the heat exchanger within the heat
components made of carbon steel or cast iron, both of source, be it a boiler, heat pump or other source, should
which can be a source of magnetite. DirtMag separators be kept as clean as possible to maximize heat transfer to
are also recommended if a circulator with a permanent system water and maintain high efficiency.
magnet motor (e.g., ECM) is used in either circuit. Figure
5-15 shows a Caleffi Dirtmag separator with the magnet
removed, and being “blown down” to eliminate iron oxide Figure 5-16
(magnetite) from the system. domestic water
heating subassembly
Figure 5-15
combination
buffer tank isolation/flush
valves
Figure 5-17
The combination isolation/flush valves allow the domestic Courtesy of Apollo Unlimited
water side of the heat exchanger to be isolated from the
remainder of the system. The hose bibs on the side ports
of these valves can be connected to a flushing assembly
that circulates a mild acid solution through the heat
exchanger to dissolve scaling caused by precipitation
of mineral salts. Once the scale has been dissolved and Figure 5-17 shows a severely corroded boiler heat
removed, fresh water can be passed through the heat exchanger. The scaling is the result of poor water
exchanger to remove any remaining cleaning solution. quality in combination with repeated thermal expansion
The isolation valves are then reopened to put the heat and contraction of the heat exchanger surfaces as the
exchanger back in service. boiler operates. This scale can significant reduce boiler
efficiency.
48
Figure 5-18 SUMMARY:
49
APPENDIX A: PIPING SYMBOL LEGEND
GENERIC COMPONENTS
3-way motorized
circulator mixing valve
blower compressor
filter
circulator w/ 4-way motorized
mixing valve
coil reversing!
valve
union
evaporator
circulator w/
internal check valve
evaporator
condenser
swing check valve comp. RV
TXV
spring-loaded
water-to-air
gate valve check valve
heat pump TXV
(in heating mode)
water-to-water
globe valves purging valve heat pump
blower (in heating mode)
ball valve
filter
pressure gauge
compressor
primary/secondary coil
fitting
pressure
relief
condenser
valve
reversing!
hose bib valve
drain valve pressure & comp. RV
TXV
temperature
relief valve
condenser
evaporator
diverter tee water-to-air
heat pump
cap metered (in cooling mode)
balancing
valve
TXV
water-to-water
heating mode heat pump
diaphragm-type (in cooling mode)
brazed-
expansion tank
plate
heat reversing
exchanger valve
evaporator
condenser
Comp.
solar collector
Modulating / condensing boiler
indirect water heater (with trim) solar water tank (with electric element)
50
APPENDIX A: PIPING SYMBOL LEGEND
CALEFFI COMPONENTS
Float - type
air vent inline check valve
3-way
thermostatic mixing valve
DIRTCAL
dirt
separators pressure-
reducing
valve distribution
(3/4") station
backflow
preventer
pressure-
reducing
valve HYDROFILL
NA10045
boiler tim kit
DISCALDIRTMAG DISCALDIRT multi-zone controls
air & dirt air & dirt
separator separator
NA10045
differential
pressure
bypass valve
zone valve
(3 way)
LEGIOMIX thermoelectric
zone valve
(2 way)
Hydro
Separator
Hydro
Separator
TANKMIXER motorized
ball valve
(2 way)
Hydro
Separator
motorized
THERMOSETTER
ball valve
adjustable
balancing (3 way)
valve
variable orifice
balancing
valve
solar
thermostatic
circulation
FLOWCAL radiator valve
station
balancing
valve
thermostatic
FLOWCAL
radiator valve
balancing
valve
dual isolation
SEP4 valve for
SEP4 fixed orifice panel radiators
SEP4 balancing
valve
high-temperature
solar 3-way thermostatic
QuickSetter high-temperature mixing valve
balancing solar DISCAL
valve w/ air separators
HydroBlock flowmeter isolar
mixing units
differential
high-temperature temperature
solar pressure controller
51
DRAFT (4-16-18)
DRAFT (4-16-18)
B = heat output of the baseboard at 200 °F average water tem
manufacturer’s literature* (Btu/hr/ft)
APPENDIX B: THERMAL MODEL FOR A FINNED TUBE The values 0.04, -0.4172, -2.3969319 and 1.4172 are all expo
APPENDIX B: THERMAL MODEL FOR A The values 0.04, -0.4172, -2.3969319 and 1.4172 are all
BASEBOARD
FINNED-TUBE BASEBOARD exponents.
Once the outlet temperature for a baseboard is determined, Fo
This appendix provides a detailed analytical model for Once the outlet the temperature for aand
inlet temperature baseboard
flow rate tois determined,
determine the total heat
Thisthermal
the appendix provides a detailedof
performance analytical model for thebaseboard
a finned-tube thermal performance
Formulaof a finned-tube
B-2 can use it along with the inlet temperature
baseboard
heat heat The
emitter. emitter. The model
model allows
allows thethetemperature
temperature of of
the the
water passing
and flowthrough
ratethe
to determine the total heat output.
water passing
baseboard through the
to be determined baseboard
at any tothe
location along beelement, based on the inlet water Formula B-2:
determined
attemperature,
any location along
room air the element,
temperature, fluid, and based
flow rate.on thetheinlet
When Formula
length of B-2: is
the baseboard
water temperature, room air temperature, fluid and flow
known the outlet fluid temperature can be calculated. Once the fluid outlet temperature is
rate. When the length of the baseboard is known, the
determined, it can be combined with the inlet temperature and flow rate to determine the" total
fluid outlet temperature can be calculated. Once the fluid
heat output
outlet of the heat emitter.
temperature is determined, it can be combined Where:
with the inlet temperature and flow rate to determine the Toutlet = outlet Where:
temperature of fluid leaving baseboard (ºF)
total heattemperature
The fluid output ofatthe heatlocation
a given emitter.
along a finned-tube baseboard can Tinlet = fluid
be found temperature at inlet of baseboard (ºF)
using
Formula B-1:
D = density of fluid within baseboard (lb/ft3)
The fluid temperature at a given location along a finned- c = specific Theat outlet = outlet temperature of fluid leaving baseboard (ºF)
of fluid within baseboard (Btu/lb/ºF)
tube baseboard can be found using Formula B-1: ƒ = fluid flowTinlet
rate through
= fluid the baseboard
temperature at inlet of(gpm)
baseboard (ºF)
Formula B-1:
Formula B-1: For example:D Assume
= density aoffinned-tube
fluid within baseboard
baseboard (lb/ftis )20 feet
3
long, located
c =inspecific
a roomheat
with a floor-level
of fluid air temperature
within baseboard (Btu/lb/ºF)
of 65ºF, and supplied with water at 4 gpm and 180ºF. The
baseboard’sƒ manufacturer
= fluid flow rate through the baseboard (gpm)
rates its heat output at 500
"
Btu/hr/ft when operating with 200ºF water and a flow rate
Where: of 1 gpm. Determine the heat output of this baseboard at
For example: Assume a finned-tube baseboard is 20 feet long
TWhere:
f = fluid temperature at some location L along length of the stated conditions, and compare it to the output if the
finned-tube element (ºF) level
flow rate were air temperature
reduced of 65 ºF, and supplied with water at 4 gpm
to 0.5 gpm.
TTroom = room air temperature entering the baseboard (°F) manufacturer rates its heat output at 500 Btu/hr/ft when opera
f = fluid temperature at some location L along length of finned-tube element (ºF)
Tinlet = fluid temperature at inlet of baseboard (ºF) The outlet temperature of DRAFT the baseboard can be
rate of 1 gpm. Determine the heat output of this baseboard at
(4-16-18)
DTroom = room air
= density oftemperature
fluid within entering (lb/ft3)(°F)
the baseboard
baseboard determined using Formula B-1:
cT=inletspecific heat of fluid
= fluid temperature within
at inlet baseboard
of baseboard (ºF) (Btu/lb/ºF) compare it to the output if the flow rate were reduced to 0.5 gp
ƒD==fluid flow rate through the baseboard (gpm)
density of fluid within baseboard (lb/ft3)
L = position along baseboard beginning from inlet (ft)
Bc == specific heat of of
heat output fluid within
the baseboardat
baseboard (Btu/lb/ºF)
200°F average water The outlet temperature of the baseboard can be determined u
temperature,
ƒ = fluid flow rate 1 through
gpm, from manufacturer’s
the baseboard (gpm) literature* (Btu/
hr/ft)
L = position along baseboard beginning from inlet (ft)
"
The total heat released from the baseboard can now be calculated using Formula B-2:
Figure B-1 heat output:!
Page 121
" of 128
"
a. 8,282 Btu/hr!
b. 6,522 Btu/hr"
Page 122
" of 128
"
180 ºF
Using the same formulas at the reduced flow rate of 0.5 gpm yields an outlet temperature
153.48ºF, and a total heat output of 6,522 Btu/hr. A comparison of the two operating condi
180 ºF
flow rate:! outlet temperature:!
a. 4 gpm! a. 175.79 ºF!
20 feet of fin-tube baseboard!
b. 0.5 gpm b. 153.48 ºF
52 rated at 500 Btu/hr/ft when!
" supplied with 200 ºF water at 1 gpm
"
The The
total heat
total heatreleased from
released from thethe baseboard
baseboard can
can now now be calculated
be calculated using Formula B-2:
using Formula B-2:
"
Using the same formulas at the reduced flow rate of 0.5 gpm yields an
Using the same formulas at the reduced flow rate of 0.5 gpm yields an outlet temperature of
outlet temperature of 153.48ºF, and a total heat output of 6,522 Btu/hr.
153.48ºF, and
A comparison ofathe
totaltwo
heatoperating
output of 6,522 Btu/hr. A comparison
conditions is shown inof Figure
the two operating
B-1. conditions
is shown in figure B-1.
By repeating these calculations, it is possible to plot heat output of
this baseboard as a function of flow rate. Figure B-2 shows the results
[insert figure B-1]
over a wider range of flow rate.
heat output:!
This graphs shows a rapid increase in heat transfer at low flow rates,
and a relatively slight gaina. in
8,282 Btu/hr! as flow rates rise above
heat transfer
approximately 2 gpm. b. 6,522 Btu/hr
A similar
180 ºFanalytical model for the thermal performance of a radiant
panel circuit is given in Appendix C.
flow rate:! outlet temperature:!
a. 4 gpm! a. 175.79 ºF!
20 feet of fin-tube baseboard!
b. 0.5 gpm b. 153.48 ºF
rated at 500 Btu/hr/ft when!
Figure B-2 supplied with 200 ºF water at 1 gpm
" 20 feet of fin-tube baseboard!
rated at 500 Btu/hr/ft when!
supplied
By repeating these withit is200
calculations, ºF water
possible at 1
to plot heat gpmof this baseboard as a function
output
of flow rate. Figure B-2 shows the results over a wider range of flow rate.
180 ºF
fixed
[insertsupply
figure B-2]
temperature
9000
7000
heat output (Btu/hr)
6000
5000
4000
3000
2000
1000
0
0 1 2 3 4 5 6 7 8
flow rate (gpm)
53
CIRCUIT and a corresponding circuit water temperature an
given as Formula C-3.
APPENDIX C: THERMAL MODEL FOR A RADIANT PANEL
Formula C-1 can be used to determine the outlet temperature of a specific radiant panel based
CIRCUIT
on its construction and the conditions under which it operates: Formula C-3
APPENDIX C: THERMAL MODEL
FOR A RADIANT
Formula PANEL
Formula
C-1 C-1:
can beCIRCUIT
used to determine the outlet temperature
Formulaof aC-3
specific radiant panel based
on its construction and the conditions under which it operates: ⎛ s ⎞ ⎛ qup + qdown ⎞
Formula C-1 can be used to determine the outlet "a =⎜ ⎟⎜ ⎟
temperature of a specific radiant panel based ⎛ on
al its ⎞ ⎝ 12 ⎠ ⎝ Tw − Troom ⎠
− ⎜⎜ ⎟
construction andC-1:
Formula f (8.01Dc) ⎟⎠
the conditions under which it ⎝operates:
" Tout = Troom + (Tin − Troom ) × e Where:
Formula C-1: s = tubing spacing (inches)
⎛ al ⎞ qup = upwardWhere: heat flux from panel (Btu/hr/ft2)
− ⎜⎜ ⎟⎟
qdown = downward heat flux from panel (Btu/hr/ft2)
Where: ⎝ f (8.01Dc) ⎠ s =tubing spacing (inches)
(
" Tout = Troom + Tin − Troom × e ) Tw = water temperature in circuit corresponding to the
above heat outputsqup = upward
(ºF) heat flux from panel (Btu/hr/ft2)
Where: Tout = fluid outlet temperature for baseboard (ºF) Troom = room air temperature corresponding to the
above heat outputsqdown =(ºF) downward heat flux from panel (Btu/hr/ft2)
Where: Tin = fluid inlet temperature to baseboard (ºF)
Tout = fluid outlet temperature for baseboard (ºF) Tw = water temperature in circuit corresponding to
Tin = fluid inletTroom = temperature
temperature of room air(ºF)
to baseboard entering baseboard (ºF)
For example, a radiant floor panel with 12” tube spacing
Tout = afluid
Troom = temperature = thermal outputairparameter
of room
outlet temperature entering for a specific
baseboard
for baseboard panel construction
(ºF)(ºF) creates an averageTroom =upward
room air temperature
heat output of 25corresponding
Btu/hr/ft2, to the
2
a = thermal output parameter for a specific panel with a corresponding downward heat loss of
Tin = fluid inlet temperature
l = length of radiant panelto baseboard
circuit (ft) (ºF) DRAFT (4-16-18)
2 Btu/hr/ft .
construction The average water temperature in the radiant panel circuit
l = lengthTroom c=
=
of radiantspecific
temperature
panel heat
of of fluid
room
circuit flowing
(ft)air entering through circuit (ºF)
baseboard based on its conditions
at these averageFortemperature
example, (Btu/lb/ºF)
A radiant
is 110ºF, and the roomfloor
airpanel with 12” tube s
temperature
c = specific heat
D = of
a = thermal fluid of
output
density flowing
fluid inthrough
parameter circuitonbased
for abased
circuit specific panel on temperature
above the panel
construction
it average (lb/ft3) is 70ºF. Determine the value
DRAFT of “a” for use
(4-16-18)
its average temperature (Btu/lb/ºF) in Formula C-3. of 25 Btu/hr/ft2, with a corresponding downward h
l = f = flow
length of rate through
radiant panel circuit (gpm)
(ft) Solution:
D = density of fluid in circuit based on its average
3) heat of(base temperature in the radiant panel circuit at these co
c = specific
temperature e = 2.71828
(lb/ft fluid flowing
of natural through
logarithm circuit based onSolution:
system) its average temperature (Btu/lb/ºF)
Solution:
f = flow rate throughofcircuit
D = density circuit based on it average temperature (lb/ft3) ⎛temperature
fluid in(gpm) above the panel is 70ºF. Determine
e = 2.71828 (base of natural logarithm system) ⎛ s ⎞ qup + qdown ⎞ ⎛ 12 ⎞ ⎛ 25 + 2 ⎞
f = flow ratethe
Once through
outletcircuit (gpm) for the panel is determined,
temperature a =it ⎜can ⎟be "
⎜ combined ⎟with = ⎜ the⎟inlet
⎜ ⎟ = 0.675
⎛ s⎝ 12
⎞ ⎛ q⎠up⎝+Tqwdown
− T⎞ room 12+ ⎠2⎝ 110
⎛ 12⎠⎞ ⎛ ⎝25 ⎞ − 70 ⎠
Once thee outlet temperature
temperature
(base and for
flowthe
ratepanel issystem)
determined,
to determine
" a = ⎜ ⎟⎜
the total heat output. ⎟ = ⎜ C-2⎟ ⎜ for this ⎟ = 0.675
= 2.71828 of natural logarithm ⎝ 12 ⎠ ⎝Use
Tw −Formula
Troom ⎠ ⎝ 12 ⎠ ⎝ 110 − 70 ⎠
it can be combined with the inlet temperature and flow
calculation.
rate to determine the total heat output. Use Formula C-2 Assume a radiant floor panel consists of a single 300-foot-
Once the outlet temperature for the panel is determined,long it can Assume a radiant
be combined withfloor
the panelspaced
inlet consists 12ofinches
a single 300-foot-long
Page of ½”1
" PEX
26
for this calculation. circuit of ½” PEX tubing,
Assume a radiant floor panel consists of a single 300-foot-long circuit
apart.
temperature and
Formula C-2: flow rate to determine the total heat When
output. operating
Use
12-inchesFormula at
C-2
apart. an
for average
this water temperature of
12-inches apart. WhenWhen
operating operating at anwater
at an average average wateroftempera
temperature 110ºF thi
Formula C-2: 110ºF, this panel’s average upward heat output is 25 Btu/
calculation. average
hr average
into a room upward
upward atheat heat
output
70ºF, and output
is 25 is 25
itsBtu/hr intoBtu/hr
downward a room into
heat a room
at 70ºF,
outputandisitsatdownward
70ºF, an
2.52.5 2.5
Btu/hr. Further
Btu/hr. Further assume
Btu/hr. Further assume thatthat
assume
the radiant
the the
that
panel circuit
radiant panel
radiant
is supplied
circuit
panel
with water a
circuit is supp
" is supplied
of 120ºF with
and flow water
rate at0.8a gpm.
of temperature
Determine: of 120ºF and flow
Formula C-2:
rateof of120ºF
0.8 gpm. andDetermine:
flow rate of 0.8 gpm. Determine:
Where:
a. The
a. The “a”“a”value
value ofof the
thepanel
panel
Page 125
" of b. 128
" The total heat transfer from the radiant panel
Toutlet = " outlet temperature of fluid leaving radiant panel b. The a. The
total “a”
heatvalue of the
transfer from panelthe radiant panel
(ºF) c. The
c. The total
totalupward heattransfer
transfer fromfrom the radiant
panel panel
b. The total heat transfer fromthe
upward heat
theradiant
radiant panel
Tinlet = fluid temperature at inlet of radiant panel (ºF)
D = density of fluid within baseboard (lb/ft3) Solution:c. TheThe total upward
value heat
of “a” cantransfer from the radiant
be determined from thepanel
Page 125
c = specific heat of fluid within baseboard (Btu/lb/ºF) " of 128
" given Solution: The value of “a” can be determined from the given data using Formula
data using Formula C-3:
ƒ = fluid flow rate through the baseboard (gpm)
Solution: The value of “a” can be determined from the given da
The value of “a” in Formula C-1 is based on the exact
construction of the radiant panel, including tube spacing, "
tubing embedment method, finish floor coverings and
underside insulation. This value can be determined It is necessary to determine the density and specific
It is necessary to determine the density and specific heat of the water at its ave
based on a known relationship between heat output and heat of the water at its average temperature before using
a corresponding circuit water temperature and room air Formula "
temperature
C-1. before
However, using the
Formula C-1. However,
average the average water
water temperature of temperatu
temperature. The relationship is given as Formula C-3. theiscircuit is not
not known known
at this point.atAsthis point. As an approximation,
an approximation, assume a temperature drop alo
20ºF. Under this assumption, the average water temperature would be 120-(20
It is necessary to determine the density and specific heat of the
density of water at 110ºF is 61.8 lb/ft3. The specific heat of water at this tempera
temperature before using Formula C-1. However, the average
lb/ºF. This data, along with the other stated and calculated numbers are now us
54 is not
C-1 known the
to determine at this point.
circuit’s outletAs an approximation,
temperature. assume a tem
20ºF. Under this assumption, the average water temperature w
assume a temperature drop along the circuit of 20ºF.
Under this assumption, the average water temperature
would be 120 - (20/2) = 110ºF. The density of water at
110ºF is 61.8 lb/ft3. The specific heat of water at this
temperature is 1.00 Btu/lb/ºF. This data,
DRAFTalong with the
(4-16-18)
other stated and calculated numbers, is now DRAFTused(4-16-18)
in
DRAFT
Formula C-1 to determine the circuit’s outlet (4-16-18)
temperature.
"
" "
The total heat output of the circuit can now be determined using Formula C-2:
The total heat output of the circuit can now be determined
TheThe
using
total
total heatheat
Formula
output
output
C-2:
ofcircuit
of the the circuit can be
can now now be determined
determined using Formula
using Formula C-2: C-2:
"
""
Finally, the total upward heat transfer can be estimated by multiplying the total heat transfer by
the ratio the
Finally,
Finally, of
theupward
total
total heat flux
upward
upward to transfer
heat
heat total heat
transfer flux.
can
can be estimated
be by multiplying
estimated the total heat transfer by
Finally, the total upward heat transfer can be estimated by multiplying the total heat transfer by
by multiplying the total heat transfer by the ratio of
the ratio of upward heat flux to total heat flux.
the heat
upward ratio flux
of upward
to totalheat
heatflux
flux.to total heat flux.
⎛ qup ⎞ ⎛ 25 ⎞
" Qup = Qtotal ⎜ ⎟ = 8043 ⎜ ⎟ = 7, 312Btu / hr
⎝ ⎛qup + qqupdown ⎠ ⎞ ⎝ ⎛25 +252.5 ⎠ ⎞
" Qup = Qtotal ⎜ ⎛ q = 8043⎞ ⎜ 25= 7,⎞312Btu / hr
qup⎜+ qdownup⎟⎠ ⎟ = 8043
" Qup = Q⎝total ⎝ 25 +⎛⎜ 2.5 ⎟⎠ = 7, 312Btu / hr
⎝ qup + qdown ⎠ ⎝ 25 + 2.5 ⎟⎠
END OF MANUSCRIPT
INSERT
END OFPRODUCT PAGES
MANUSCRIPT
END OF MANUSCRIPT
INSERT PRODUCT PAGES
INSERT PRODUCT PAGES
Page 128
" of 128
" 55
Page 128
" of 128
"
QuickSetter™
Balancing valve with flow meter
132 series CALEFFI
Function
The 132 series balancing valve accurately sets the flow rate of heating
and cooling transfer fluid supplied to fan coils and terminal units.
Proper hydronic system balancing ensures that the system operates
according to design specifications, providing satisfactory thermal
comfort with low energy consumption. The flow meter is housed in a
bypass circuit on the valve body and can be shut off during normal
operation. The flow meter permits fast and easy circuit balancing
without added differential pressure gauges and reference charts. The
threaded version is furnished with a hot pre-formed insulation shell to
optimize thermal performance for both hot and cold water systems.
Patent pending.
Product range
132 series Balancing valve with flow meter, threaded connections ½”, ¾”, 1”, 1 ¼”, 1 ½”, and 2" NPT female
132 series Balancing valve with flow meter, flanged connections 2 ½”, 3”, 4” ANSI 125
Flow meter
Body: brass brass
Bypass valve stem: brass, chrome-plated brass, chrome-plated
Springs: stainless steel stainless steel
Seals: peroxide-cured EPDM peroxide-cured EPDM
Flow meter float and indicator cover: PSU PSU
Performance
Suitable Fluids: water, glycol solutions water, glycol solutions
Max. percentage of glycol: 50% 50%
Max. working pressure: 150 psi (10 bar) 150 psi (10 bar)
Working temperature range: 14 - 230º F (-10 - 110º C) 14 - 230º F (-10 - 110º C)
Flow rate range unit of measurement: gpm gpm
Accuracy: ±10% ±10%
Flow rate correction factor: 20% - 30% glycol solutions: 0.9 20% - 30% glycol solutions: 0.9
40% - 50% glycol solutions: 0.8 40% - 50% glycol solutions: 0.8
Insulation
Material: closed cell expanded PE-X
Thickness: 25/64 inch (10 mm)
Density: - inner part: 1.9 lb/ft3 (30 kg/m3)
- outer part: 3.1 lb/ft3 (50 kg/m3)
Thermal conductivity (DIN 52612): - at 32°F (0°C):
0.263 BTU·in/hr·ft2·°F (0.038 W/(m·K))
- at 104°F (40°C):
0.312 BTU·in/hr·ft2·°F (0.045 W/(m·K))
Coefficient of resistance to water vapor (DIN 52615): < 1,300
Working temperature range: 32 - 212º F (0 - 100º C)
Reaction to fire (DIN 4102): class B2
--56
Dimensions
A C
3/4” all sizes C
D
CALEFFI
15
bar
D
7 E
6
5
4
3
2
A B
Code
Code A A B B C
C D D Wt (lb/
Weight
kg) (lb) Bolt Wt
132432A 1/2” 3 5/16 Code A B C D E circle
132432A ½” 3 5/16" 1 13/16"”
” 1 13/16 5
5 ¾"3/4” 2.0
2.0/0.9 dia (lb/kg)
132552A 3/4” 3 5/16 ” 1 13/16” 5 3/4” 1.8
132552A ¾” 3 5/16" 1 13/16" 5 ¾" 1.8/0.8 132060A 2 ½” 11 7⁄16" 6 31⁄32" 3 7⁄8" 7" 5 ½" 32/15
132622A 1” 3 3/8” 1 7/8” 6 1/4” 2.4
132662A 1” 3 3/8" 1 7/8" 6 ¼" 2.4/1.1 132080A 3" 12 7⁄32" 7 9⁄32" 3 7⁄8" 7 ½" 6" 40/18
132772A 1 1/4” 3 1/2” 2” 6 1/2” 2.8
132772A
132882A 1 1/2” 1¼” 3 ½"
3 5/8 ” 2" ”
2 1/4 6 6½"3/4” 2.8/1.3
3.4 132100A 4" 13 25⁄32" 7 29⁄32" 3 7⁄8" 9" 7½" 57/26
132882A 2” 1½”
132992A 3 3/4 5
3 ”/8" 221/2
¼"” 6 ¾"7” 3.4/1.5
4.4
132992A 2” 3 ¾" 2 ½" 7" 4.4/2.0
57
Advantages of balanced circuits Operating principle
Balanced circuits have the following principal benefits: The balancing valve is a hydraulic device that controls the flow rate of
the heating/cooling transfer fluid.
1. The system emitters operate properly in heating, cooling and The control mechanism is a ball valve (1), operated by a control
dehumidification, saving energy and providing greater comfort. stem (2). The flow rate is manually and properly set by use of the
2. The zone circuit pumps operate at maximum efficiency, reducing convenient onboard flow meter (3) housed in a bypass circuit
the risk of overheating and excessive wear. on the valve body. This circuit is automatically shut off during
3. High fluid velocities which can result in noise and abrasion are normal operation. The flow rate is indicated by a metal ball (4)
avoided. sliding inside a transparent channel (5) with an integral graduated
4. The differential pressures acting on the circuit control valves are scale (6).
reduced preventing faulty operation.
1 3
Control valve 15
2 7
5
6
5
3 4
6
7
6
5
4
3
2
3
2
5
7
6
5
4
3
2
2
3
4
Manual valve
5
6
7
--
58
Complete closing and opening of the valve Hydraulic characteristics at 100% open
1 1/4”
1 1/2”
The valve can be completely closed and opened. A slot on the control
1/2”
3/4”
∆p (psi) (psi) (bar) (feet of head)
stem indicates the valve position. When the control stem is turned
1”
2”
20 20 46.20
fully clockwise (the slot is 1.0
perpendicular to the axis Completely closed Completely open 10 10
23.10
200
100
0.2
0.5
(l/h) (gpm)
20
50
10
Completely closed Completely open
G
50
100
200
500
1000
2000
5000
10000
20000
Flow rate
Code Connection Full open Cv
(GPM)
132432A ½” NPT ½ – 1¾ 1.0
A B 132552A ¾” NPT 2.0 – 7.0 6.3
132662A 1” NPT 3.0 – 10.0 8.3
Insulation
132772A 1¼” NPT 5.0 – 19.0 15.2
The 132 series threaded 132882A 1½” NPT 8.0 – 32.0 32.3
version,is supplied with a hot
pre-formed insulating shell. This 132992A 2” NPT 12.0 – 50.0 53.7
system ensures perfect heat
insulation and keeps out water (feet of
∆p (psi) 2½” (psi) (bar) head)
vapor from the environment.
Additionally, this type of insulation 20 20 46.00
is ideal in cold water circuits as 1.0
it prevents condensation from 10 10
forming on the surface of the 2½” 20.00
0.5
valve body. 0.4
5 5 10.00
4 3” 4 0.3
9.00
3 3 0.2 7.00
5.00
2 2
Installation
0.1
3.00
Install the balancing valve in a location that ensures free access to 1 1
2.00
the flow meter shutoff valve, control stem and flow rate indicator. To 4” 0.05
1.50
ensure accurate flow measurement, straight sections of pipe installed 0.04
0.5 0.5
as shown is recommended. 0.4 0.4 0.03 1.00
0.3 0.3 0.02 0.70
2
3
4
5
6
7
2
3
4
5
6
7
0.01
3
2 2
0.30
0.1 0.1
0.005 0.20
5D 10D 0.05 0.05 0.003 0.11
2 00
3 00
4 00
100
(l/h) (gpm)
20
50
10
The valve can be installed in any position with respect to the flow
G
5000
10000
20000
25000
45000
90000
2
3
4
5
6
7
2 2
3 3
4 4
CALEFFI CALEFFI CALEFFI CALEFFI
5 5
6 6
7 7 7
7 7 7 7
7
6 6 6 6 6
6
5 5 5 5 5
5
4 4 4 4 4
4
3 3 3 3 3
3
2 2 2
2
3
4
5
6
7
2 2
2
3
4
5
6
7
Flow rate
Code Connection Full open Cv
(GPM)
132060A 2 ½” flange 30 - 105 87
132080A 3” flange 38 - 148 164
132100A 4” flange 55 - 210 242
--
59
2
3
3
4
4 CALEFFI CALEFFI
5 CALEFFI CALEFFI
5
6
6
7 7 7
7 7 7
6 6
6 6
5 5
5 5
4 4
4 4
3 3
3 3
2 2
2
3
4
5
6
7
2 2
2
3
4
5
6
7
QuickSetterTM
Pull - Adjust - Release
• Industry unique design; simply pull, adjust, and release for quick and accurate circuit balancing.
• No need for differential pressure tools or cross-reference charts.
• Built-in flow meter with memory pointer provides direct readout in GPM.
• Flow window scale never clouds; indicator ball travels within transparent isolated glass channel.
• Full range of pipe sizes from 1/2" to 2" NPT and 2-1/2" to 4" flanged to fit most commercial projects.
• Low lead models for plumbing applications are perfect for DHW recirculation.