Professional Documents
Culture Documents
AS3500 User Guide
AS3500 User Guide
August 2020
Copyright
©2020 by Honeywell International Inc. All rights reserved. Honeywell® is a registered
trademark of Honeywell International Inc. in the United States and/or other countries and
are used under license from Honeywell.
All other products mentioned herein may be trademarks of their respective companies and
are hereby acknowledged.
Disclaimer
The information in this document is subject to change without notice and does not
represent a commitment on the part of Honeywell. Honeywell makes no representations or
warranties with respect to the contents hereof and specifically disclaims any implied
warranties of merchantability or fitness for any purpose.
Honeywell reserves the right to revise this publication and to make changes from time to
time in the content hereof without obligation to notify any person of such revision or
changes. To the extent permitted by applicable law, Honeywell will not be liable to any
person or business entity for any direct, indirect, special, incidental, consequential or other
damages based on the use of this product, including, without limitation, any lost profits,
business interruption, or loss of programs or information, even if Honeywell has been
specifically advised of the possibility of such damages.
2
Table of contents
1 GETTING STARTED .................................................................................................................................. 9
1.1 About AS3500 .......................................................................................................................................................... 9
2.5 Push–buttons........................................................................................................................................................ 22
3 FEATURES .................................................................................................................................................. 23
3.1 Main features of the AS3500 meter........................................................................................................... 23
15.5 Minimum and Maximum calculation for power quality data ..................................................... 102
1 GETTING STARTED
The AS3500 polyphase meter is produced for current transformer connections in different
variants:
The meter conforms to the relevant specifications of the DIN, MID and IEC standards. The
meter is prepared for AMI application by using communication modules plugged into their
designated place on top of the meter.
1.2 Scope
This user guide describes the basic features, installation and configuration of the AS3500
polyphase meter, with the next firmware versions:
The meter is a technical measuring device in accordance with the Equipment and Product
Safety Act.
1.5 Warnings
This applies to all persons who may be involved in activities such as unpacking, inspecting,
testing, setting, cleaning, installing, commissioning, operating, maintaining,
decommissioning or disposing of the products.
The information provided in this user guide is intended to ensure that products are properly
installed and handled to maintain them in a safe condition.
Employers must ensure proper compliance with the health and safety legislation that
applies to them.
The purchaser or delegated contractor is responsible for the "putting into service" of any
Honeywell products that have been supplied as "non-connected". All related activities must
therefore be carried out with due regard to any applicable legislation, standards and good
practice.
Batteries
Depending on the meter’s version this may contain an internal lithium battery. This battery
is completely safe under normal conditions.
The battery must never be recharged, disassembled, heated above 100°C, incinerated,
or have the contents exposed to water.
CAUTION Fire, explosion or severe burns may result if these instructions are disregarded.
Honeywell would like to draw the user's attention to the international standard for lithium
batteries - IEC 60086-4 - which gives further information about the handling, storage,
transport and disposal of lithium cells.
Honeywell should be contacted by the user if difficulties arise in arranging proper disposal.
If possible, Honeywell will help the user identify safe disposal means.
However, a sudden change in temperature can cause condensation which if present can
compromise the safety and operation of the meter.
On installation, a meter that has been stored in cold conditions should be removed from its
packing and acclimatised at site temperature for at least one hour before connecting to the
mains supply to allow all traces of condensation to evaporate.
ESD precautions
Observe precautions for handling electrostatic discharge sensitive devices.
When handling electronic equipment, like the one described in this manual, always take
electrostatic discharge precautions.
Avoid touching connector pins and printed circuit boards on communications modules and
module peripheral equipment where the PCB is exposed.
Parts of the internal electronic circuits of these meters are, due to technical necessity,
connected to PHASE VOLTAGES.
CAUTION
Installation of a faulty module or module peripheral equipment may affect the main
meter functionality.
ATTENTION
Removal of the front cover invalidates the certification of the meters.
IEC standards
EN 62056-53 Electricity metering. Data exchange for meter reading, tariff and load
control. Part 53: COSEM application layer.
EN 62056-62 Electricity metering. Data exchange for meter reading, tariff and load
control. Part 62: Interface classes.
EN 62056-61 Electricity metering. Data exchange for meter reading, tariff and load
control. Part 61: Object identification system (OBIS).
MID standards
Meter approvals
The meter has the next approvals.
Waste certifications
WEEE Directive 2012/19/EC.
Waste electrical and electronic equipment directive.
Waste electrical products should not be disposed of with household waste.
Please recycle where facilities exist. Check with your local authority or retailer for
recycling advice.
2 TECHNICAL DATA
Electrical characteristics
3x100V … 3x110V;
3x220V … 3x240V;
Power consumption Voltage circuit: < 0,7W/0,8VA per phase (CT connection);
Current circuit: < 0,01W/0,01VA per phase (CT connection);
Display
LED
Energy LED One LED, who will light proportional with measured energy.
Buttons
Communication interfaces
Relays
Auxiliary relay
Real-Time Clock
Accuracy The time basis is derived from the internal oscillator with an
accuracy of <5ppm (<±0,5s/day).
Mechanical characteristics
Environmental characteristics
EMC compatibility
Other characteristics
Power supply Functional even with power loss on two phases or one
phase and the neutral.
Time backup for readout 4-5 years with an exchangeable battery (optional)
without mains power
2.2 Enclosure
The enclosure of the AS3500 meter meets or exceeds the following standards:
EN 50155;
The enclosure, mounting holes and terminal block comply with the DIN 43859 standard.
The dimensions of the meter and the attachment of the connection leads are as specified in
DIN 43857. The meter has a vibration-resistant design as per EN 50155 and meets the
requirements for IP54 protection class.
The meter cover is designed for user convenience and high security. The clear viewing
window is moulded of ultraviolet-stabilized, shatter-resistant polycarbonate. Cover
components provide a basic user interface to the meter.
Removing the terminal cover exposes the base assembly, including the wiring terminals.
The four meter screws can be individually sealed. Plastic pin seals and conventional wire
type seals can be used.
The two meter cover screws are located on the upper front of the meter. Sealing these
screws seals the main enclosure and limits access to the metering printed circuit board and
sensing elements. The configuration security key is located on the metering circuit board
and locks access to the meter configuration.
The two terminal cover screws limit access to the main terminals and auxiliary wiring
connections only. Therefore, the only terminal cover seals must be broken to access these
connections. To gain access to the main enclosure and metering components, all four seals
must be broken.
Different terminal covers are available for the AS3500 polyphase meter. For details about
terminal covers see section 19.5 Terminal cover options.
Main components of the meter, described in the above picture, are explained next:
The meter also has one seal for the demand reset push-button (position ③ from Fig. 2.) and
two seals for the terminal cover (position ② from Fig. 2.).
The communication module can be sealed also (position ⑤ from Fig. 2.). Additionally, the
push-button (position ⑥ from Fig. 2.) and the corner cover for the wired M-Bus interface
(position ④ from Fig. 2.) of the communication module are sealable.
Do not break the seal and remove the terminal cover of the meter without authorization.
Do not break the seal and remove the communication module of the meter
CAUTION
without authorization.
2.5 Push–buttons
The AS3500 meter is equipped with two push-buttons, on the front cover of the meter.
The function of the [A] push-button, position ④ from the Front view of the meter section, is
to manually alternate the display parameters.
The function of the [R] push-button, position ⑤ from the Front view of the meter section, is
to reset the maximum demand of the meter.
3 FEATURES
High accuracy
Digital measured data processing with a digital signal processor (DSP) and high sample
rate for accurate, flexible measured-value processing in all 4 quadrants.
Configuration
User-friendly readout and configuration tool alphaSET, enabling users to define their own
different function variants.
With the integrated load profile and the different electrical interfaces (CL0, RS485) the
meter can easily be connected to an AMI system without using additional data loggers.
By pressing the display push-button of the meter all billing data can be displayed even if the
main power is absent. Furthermore, all data can be readout by the optical interface.
Anti-tampering features
3-wires/4-wires applications
The same meter can be used for 3-wires or 4-wires applications and therefore the customer
can reduce his stock inventory.
The AS3500 meter is prepared for AMI application by using exchangeable communication
modules.
If phase and neutral conductor are not connected as described in the Connection diagrams
section the meter will display an alarm. All meter types of the AS3500 series are earth fault
protected; in that case, the meter can handle a voltage of 1,9xUn for more than 12h.
After pressing for 1s the alternate push-button, the LCD will be switched ON. The segment
test will be displayed first. After pressing the alternate push-button again the next data of
the standard data readout list will be displayed for about 10s.
The LCD will be switched OFF after one of the following events:
After pressing for 1s the alternate push-button, the LCD will be switched ON. After the
segment test will be displayed the standard data readout list of the meter can be read by the
optical port. At the end of the communication, the LCD will be switched OFF.
By using the exchangeable battery option the described features are available even if the
meter is not powered for 4 - 5 years.
Additionally, the basic requirements of the EDL21 specification of the FNN are fulfilled.
The AS3500 offers the possibility to measure the daily values of the active energy in both
directions. Two different solutions are supported:
On the LCD of the meter as well as the communication interfaces the attached daily values
(00:00-24:00) can be displayed and readout:
Using the optical or electrical interface the daily energy values (00:00-24:00) over the last
30 days can be readout.
On the LCD of the AS3500 meter, the current consumption and demand can be displayed
in import and export direction (unit in W). Additionally additional data, like current, voltage,
reactive demand, etc. can be displayed.
By configuration, the demand reset push-button can be used during the scroll mode to
reset special register to „0“ (example: 1.9.0 register to measure the energy consumption +A
in a specific time interval).
Therefore the end-user can measure energy consumption during a specific period.
For data security reasons the customer information on the LCS can be disabled. Different
possibilities are supported:
1. Disable customer-specific data on the LCD using formatted commands on the optical
or electrical interface. This feature is password secured;
According to the FNN specification, the EDL specific data (1d, 7d and 30d energy
registers) can be displayed by using a 4-digit PIN-code, which will be entered using
the alternate push-button or a lamp. In case this function is enabled the menu
“Std_data” and “Abl_data” are automatically disabled;
Using the PIN code mode the display of the meter is under normal condition in the
scroll mode. Pressing the push-button or using a lamp the PIN code menu will be
entered:
the first digit of the PIN code can be selected from 0 to 9 using a short press of the
push-button;
without pressing the push-button for 3s, the value will be overtaken and the next
digit will be displayed;
after entering the 4th digit, the correctness of the PIN code is checked by the meter:
3. Reset of customer-specific data on the LCD (1d, 7d and 30d energy registers).
pressing the demand reset push-button => reset of all daily values (1d, 7d, 30d);
for using the reset mode, a correct PIN code must be entered;
the PIN code can be read under the OBIS identifier 0.0.5;
the PIN code can be modified using a W5-command or the menu „Modify“ in the
configuration tool alphaSET;
By configuring the PIN-Code to „0000“ the meter display acts as described in chapter
6. Display control, which means that the 2 menus (“Std_data” and “Abl_data”) are
displayed.
All data programmed in the service list of the meter can be secured by the PIN code.
The service list data can be disabled on the LCD in case the PIN code is set to “0000”.
NOTE
AS3500
Requirements
AS3500
Requirements
External tariff control (2 tariffs). Integrated tariff clock, external control inputs,
integrated receiver.
use of two separate registers depending on the energy direction (with 4 decimals);
the decimals for the line loss energy register is independently configurable from the
energy register;
the copper loss constant is not stored in the meter. To get the final losses the energy
value of the meter has to be multiplied by the constant “R” entered in Ω unit.
use of two separate registers depending on the energy direction (with 4 decimals);
the decimals for the transformer loss energy register is independently configurable
from the energy register;
the iron loss constant is not stored in the meter. To get the final losses the energy
value of the meter has to be divided by the constant “X” entered in kΩ unit;
4 TARIFF CHARACTERISTICS
The meter possesses up to 6 potential-free inputs for tariff control. The control
voltage corresponds to the meter's rated voltages. The "voltage present" assignment
corresponds to T1 or T2, or T3 or T4, as required.
3. Communication interface.
The energy tariff control can be supported by formatted commands using one of
the communication interfaces.
duration of the maximum period: 15 min (configurable in the range of 1 ... 60 min);
input variables for the 4 maximum values are user-selectable, e.g. +P/Q1, +P/+Q/+S;
reactive demand;
apparent demand;
The calculation of the apparent demand is done at the end of the demand period.
3. Communication interface
The demand tariff control can be supported by formatted commands using one of
the communication interfaces.
the annual demand period is fixed from 01.01 until 31.12 of every year;
at 31.12 of every year, a demand reset will be executed automatically. The three
highest demand values will be stored as previous data (only over the last year) and
the current demand register will be reset;
on the meter display or over the optical or electrical interface the current demand
values and the historical data from last year can be displayed.
power failure
Integration period is ended.
Integration period is not ended.
power recovery
A new integration period is started, and terminated synchronously with the device
time.
Depending on the duration of the interruption, either the integration period
ongoing at the time of the power failure will be continued, or a new shortened
integration period will start. The end of the integration period is always specified
by the IP raster.
demand Reset
Ongoing integration period is ended, a new integration period is started with the
beginning of the new billing period
The reset is accepted as preparation, but not executed until the next time the time
filed in the device comes round (this does not apply for resets with the reset
push-button or through the optical interface)
External inputs
Communication interface
After resetting the control input the tariffs will be controlled by the internal tariff source
again.
the time basis is derived from the internal oscillator with an accuracy of <5ppm
(<+/- 0.5s per day);
in the event of interruptions in the mains power supply, the quartz will take over as
the clock's time basis;
the energy for the running reserve is supplied by an internal battery (about 5 years
backup time);
after the running reserve, has been exhausted, the device clock will start after power
up with the time and date information of the last power outage. If a device clock has
been integrated, the cursor labelled "Clk" will flash. An associated error identifier can
be readout;
time and date must be set manually by pressing the display and reset push-buttons
together, through the optical or electrical interface;
the real-time clock supplies the timestamp for all events inside the meter, such as
timestamp for maximum measurement, timestamp for voltage interruptions, etc.;
it has been specified that two-digit year figures from 90 up to and including 99 are
assigned to the twentieth century. Two-digit year figures in the range from 0 to 89
will be linked to the twenty-first century;
if the real-time clock stops running the meter can be set to a predefined tariff.
Battery backup
Internal battery
To keep the RTC of the meter running the AS3500 can optionally be equipped with an
onboard soldered battery, which is located on the PCB under the front cover of the meter. As
an additional option, this battery can be placed on a battery socket.
In case the internal battery gets empty, the meter can be configured to display the message
“bat” on the LCD (FW10.04).
External battery
As a further option the meter can be equipped with an external, replaceable battery which is
located on the right end of the terminal block (see Fig. 3. and Fig. 4.). With this external
battery the RTC running and readout without power feature works as listed below:
an internal supercapacitor (optional): keeps RTC running during power outage <1day;
internal battery: keeps RTC running during power outage >1day (up to 5 years);
external battery: support of readout without power, keeps RTC running in case the
supercapacitor (optional) and the internal battery is empty.
Using the external battery, the readout feature is available even after 4-5 years without
power.
ATTENTION
In case the external battery gets empty, the meter can be configured to display the message
“E-bat” on the LCD (FW10.04).
In case the internal and external battery is getting empty the meter is losing its time
and date information. This can be shown by an F.F.1 message.
ATTENTION
Optionally the meter can be switched to a predefined tariff (FW 10.04).
correcting the real-time clock using the alternate and demand reset push-buttons.
By using the synchronization input to synchronize device clock, a distinction must be drawn
between the following three cases:
The device clock can be continuously corrected using a control signal at the "External
measuring period" input. If the external control signal fails, the device clock will continue to
run with its own inherent accuracy. When the "integration period end" signal re-appears, the
device clock will immediately be corrected in the sense of "synchronization". If the deviation
at this juncture is greater, i.e. the end of the integration period specifiable with the device
clock lies outside the time window permissible under "synchronization", reference to the
"integration period end" signal arriving again, and then the device clock will be set. The
decision as to whether the device clock is to be set forwards or backwards is found by
rounding to the next time interval limit.
The time window inside which the device clock is synchronized has been agreed with a time
deviation of 1% of the period, with the time involved being the time between the reference
edge of the "integration period end" signal and the reference time of the device clock.
In this procedure, the „integration period end" signal supplies a pulse for correction (setting
or synchronizing) the device clock once or several times a day. If the signal is not received,
the device clock will continue to run with its own inherent accuracy until the signal re-
appears. If the second value is in the range between 0 and 29 when the signal for correction
arrives, then the device clock's second value will be set to "0", without any change to the
higher-order variables (minute, hour, date). If, however, this value is in the range between 30
and 59, then the second value will be set to "0" and the higher-order variables will be set to
the next minute on the rounding-up principle.
In this procedure, the "integration period end" signal supplies a pulse for correcting (setting
or synchronizing) the device clock only once a day. If the signal is not received, the device
lock will continue to run with its own inherent accuracy until the signal reappears. To
preclude malfunctions, a time window can be set (e.g. 22:55 to 23:05), inside which the
device clock will accept the "integration period end" signal at all. Also, the user has to set a
time which sets the device clock when the "integration period end" signal is detected (e.g.
23:00).
switching times:
For the "Holiday" day type, the meter incorporates a Holiday table, where a year's fixed and
movable Holidays can be entered. The parameters for the integrated clock can be read off at
the meter's display using a switching number.
Besides tariff control, the integrated clock timer is also used to form the maximum
integration period and the timestamps for the maximum demand, load profile and logbook
(i.e. 10).
Furthermore, it’s possible to configure additionally the time of the change (e.g.: from 02:00
to 03:00).
The future tariff table can be programmed with a fixed date (at 00:00), where the tariff table
will be activated automatically. The tariff table 1 will be overwritten and the internal tariff
control of the meter will only be done by this second tariff table.
4 seasons
4-day types
1 tariff contract
For every tariff register up to 15 monthly data are provided. The maximum number of tariffs
is defined by 8 energy tariffs.
4 seasons
4-day types
4 energy tariffs for 3 measuring quantities 4 energy tariffs for 3 measuring quantities
flexible assigned to the different day types flexible assigned to the different day types
1 demand tariff for 1 measuring quantity 1 demand tariff for 1 measuring quantity
flexible assigned to the different day types flexible assigned to the different day types
Example:
Measuring of active energy +A in 2 different contracts. Therefore the attached register will
be used.
Tariff contract 1:
1.8.1 Active energy, +A, tariff 1 of contract 1;
Tariff contract 2:
1.8.5 Active energy, +A, tariff 1 of contract 2;
The register 1.8.0 is the total active energy register and is always the same as the sum of the
4 tariff registers of both contracts.
Remote budget metering and prepayment control mean that all calculations and all
decisions are made in the central system. The meter only needs to be able to perform
connect/disconnect and arm commands for the disconnect relay and display prepayment
information.
all tariff data and billing formulas can be managed and controlled easily at a central
system;
The AS3500 meter provides up to 8 status register for the end consumer, which can be
displayed on the LCD. For security reason, the display of the register on the LCD are
secured by a 4-digit PIN code (see Enable/disable of customer-specific data on the LCD
section).
The below registers can be displayed and remotely updated by the central system
6 DISPLAY CONTROL
6.1 Display
The meter is fitted with an LCD (Liquid Crystal Display) that has the following format:
Symbol Description
Identifier.
Error indicator.
Measuring quantity.
Symbol Description
Phase indication.
The definitions for import and export of energy have been agreed in terms of the load
reference arrow system. For defining the transmission direction of active and reactive
power, the specifications of the load reference arrow system likewise apply. The arrow
system assumes that the power utility's contracting party is importing energy (+A) from the
supply grid.
The tariffs T1 to T8 and M1 to M4 switched on at any one time are continuously displayed.
Also, the following applies:
In the case of meters with an energy feature, the relevant symbols will flash when the
"electronic reversal disable" is active. The symbols for the measured variable involved have
been switched off if the power is below the device's start-up threshold.
Phase indication
The phase display indicates which phases are energized. The corresponding symbols are
switched off if there is no voltage at the dedicated phase. All active symbols will flash if the
three-phase voltages are not occurring in the sequence L1, L2 and L3.
All digits are separated by dots (OBIS separator or decimal point). Time (hour, minute,
second) is separated by colons, date (year, month, day) by the top dots of the colons.
Cursor field
The cursor field contains 10 configurable element positions and provides the assignments
for operationally important status information located under the display. The cursors
become visible when the assigned device status has materialized. In “Parameterization
mode”, all active cursors flash. The following abbreviations can be used under cursor
positions 1 to 10:
T1 – T8 Tariff information for energy, all active registers are declared on the rating plate.
M1 – M4 Tariff information for power, all active registers are declared on the rating plate.
RS The cursor concerned is activated when a voltage leads to a demand reset on the
input terminal assigned, or if the output terminal assigned is exhibiting active
state. The cursor activated will flash for if a reset disable has been activated.
CLK The cursor is continuously lidded when the internal device clock is controlling
the tariff. The cursor will flash if the running reserve of the device clock has
been exhausted and the device clock has not then been set.
TC The cursor is continuously lidded when the tariffs of the meter are controlled via
the communication interface of the meter.
Inp The cursor is continuously lidded when the tariffs of the meter are controlled via
the external control inputs of the meter.
Error symbol
This symbol indicates an error or warning of the meter (F.F, F.F.1, F.F.2).
The tariff source active at any time, plus the source for the meter's maximum reset, can be
called up into the display via the identifier C.70 as a two-digit numerical value.
The display can optionally be back lightened to be readable under dark reading conditions.
The back lightened display will be activated for 2 minutes by pressing the alternate or the
demand reset push-button.
This feature will be available even if the meter is not connected to the main power.
In case the meter is installed in a meter box, without having direct access for reading the
meter data, the AS3500 meter data can be read on the LCD by using a flashlight, which
should be lightened on the optical sensor of the optical interface.
With this flashlight, the reader has the same functionality as by using the alternate
push-button described in the following chapter.
pressing briefly (<2s) switches to the next list value or menu option;
pressing for longer (2s < t < 5s) either activates the menu options currently being;
pressing the alternate push-button for longer (>5s) returns user from any display
mode back into the scroll mode (rolling display);
pressing it for any length of time in operating display mode always causes a reset;
pressing it for any length of time in setting mode always causes the digit or value
being edited to be accepted;
Further principles:
the display control and the edit function for settable values are handled using
"single-hand operator control" in conformity with the stipulations of the VDEW -
Specification, i.e. it is not necessary to operate more than one control at any one
time.
description of the different values on the display in the various display modes can be
parameterized.
the default status for the display is the operating display. A change from the
operating display to the "Menu [A]-key" (i.e. call or load profile) or to the "Menu [R]-
key" (i.e. setting or high-resolution mode) is possible only through the "display test".
from a call, load profile, setting or test mode, user jump back into the operating
display through the end-of-list identifier, or automatically if no control is operated
within a defined time of 30 minutes, for example, or if the alternate push-button has
been pressed for longer than 5s.
the end of a list is designated in the display with the word "End" in the value range.
since in setting mode values can also be edited via the data interface, the interface
and the operator control functions are mutually (logically) interlocked.
scroll Mode.
display test.
Using a flashlight, which should be lightened to the optical interface, the alternate
push-button feature can be used if the meter reader has no direct contact to the meter
NOTE (ex. meter installation inside a sealed box)
All billing relevant data of the scroll list can’t be changed without breaking the certification
seal.
Additionally, it is possible to select data of the service list in the scroll mode too. This data
can be changed without breaking the certification seal.
A-button menu
The first value displayed in the menu list is the single-call menu option entitled "Std-dAtA".
Every time the user is pressing the alternate push-button briefly again, more menu options
as available will be displayed, e.g. the load profile "P.01" or the second alternate list “Abl-
dAtA”. For purposes of menu option selection, the alternate push-button must be held down
for at least 2s.
While a measured value is being displayed in this mode, it will be updated in the display
once a second.
The first value displayed in the call list is the Identifier and the content of the function error.
Every time the alternate push-button is pressed again, further data will be displayed. To call
up data more quickly, existing preceding values can be skipped and the value following the
preceding values can be displayed. User can do this by keeping the alternate push-button
pressed down for longer than 2s.
The fallback scroll mode can be adjusted from 1 minute to 2 hours. Extending the time limit
gives the user an option for testing the meter without any software tools since the LED will
flash either for +P, -P, +P/-P or Q1, Q2, Q3, Q4, etc., depending on the measured variable
being displayed (active or reactive power consumption).
The final value in the call list is the end-of-list identifier, which is designated in the display's
value range by the word "End".
Furthermore, the meter supports second standard data list (“Abl-dAtA”). The handling of
this list is the same as described in chapter 6.6.2 Standard mode (Menu Option "Abl-dAtA")
The main difference between this two lists is, that the “Abl-dAtA” list can be set without
breaking the certification seal (see chapter 11.2 Formatted commands)
If the alternate push-button is pressed for >2s, then for precise analysis of the day block
selected the day profile will be displayed in increments of the demand integration period,
provided no events have led to the demand integration period being cancelled or shortened.
The final value in the call list is the end-of-list identifier, which is designated in the display's
value range by the word "End".
The last value in the call list is the end-of-list identifier, which is designated in the display's
value range by the word "End" and which appears after the final load profile value of the day
selected. If the alternate push-button is pressed for >2s, the meter will switch back to the
day block previously selected from the date list.
R-button menu
The first value displayed from the menu list is the setting mode menu option, called "SEt".
Every time the alternate push-button is pressed briefly (<2s) again, any other menu options
available will be displayed, e.g. the high-resolution mode for test purpose, called "tESt". To
select a menu option, the alternate push-button must be held down for longer than 2s. The
final value in the call list is the end-of-list identifier, which is designated in the display's
value range by the word "End".
In the setting mode, settable parameters are entered using the reset push-button and/or
the alternate push-button. The values concerned can likewise be altered through the optical
or electrical interface. While date and time are being set, the Identifier concerned is shown
on the display.
To set the meter's date and time, the user has to press the reset push-button during the
display test. The current time will then appear in the display. User presses the alternate
push-button to switch to "Set date", and the reset push-button to enable the user to enter
the time.
For this purpose, the hours must be entered using the alternate push-button and confirmed
with the reset push-button. The user then enters the minutes and seconds. After the user
has confirmed the entry for the seconds, the complete time display will flash, and will not be
accepted until the user has pressed the set push-button. After entering the time, user can
enter the date to the meter in the same way. For all entries, the meter runs a plausibility
check, i.e. only valid values will be accepted.
After data and time have been set, the meter automatically assumes its correct set point
status, i.e. in the case of a clock timer function, the meter will autonomously switch to its
ongoing tariff. For reasons of possible incorrect operation, the reset disable is activated for 1
… 2 minutes at the end of this setting routine, to prevent a reset being triggered accidentally.
By configuration, it’s possible to disable the setting of time and date by using the push- buttons.
In the "Test" operating mode, the display will show the same data as in the scroll mode, but
rolling, and with the difference that energy registers are displayed in high resolution. Each time
the alternate push-button is pressed, further data will be displayed. If the alternate push-
button is held down for at least 5s, the meter will automatically switch to the operating display.
formatted command;
press the alternate push-button shortly (<2s) to switch to the "Std-data menu"
press the alternate push-button long (>5s) to switch to the "Abl-data menu"
The fallback scroll mode can be adjusted from 1 minute to 2 hours. Extending the time limit
gives the user an option for testing the meter without any software tools since the LED will
flash either for +P, -P, +P/-P or Q1, Q2, Q3, Q4, etc., depending on the measured variable
being displayed (active or reactive power consumption).
The final value in the call list is the end-of-list identifier, which is designated in the display's
value range by the word "End".
The final value in the call list is the end-of-list identifier, which is designated in the display's
value range by the word "End".
7 DEMAND RESET
The demand reset of all energy/demand register can be executed by:
1. A demand reset by pressing the reset push-button can be performed in the scroll
mode or the alternate mode ([A]-mode).
2. At every demand reset, a reset disable is activated, i.e. the "R” symbol in the display will
flash). The demand reset disable time can be parameterized from 1 minute to 4,5 hours.
1 ... button t1 0 0 0 0
3. A demand reset executed through an appropriate control input is operative only if the
demand reset disable time is not active.
5. If during an activated demand reset disable another reset is executed through the
optical or electrical data interface, then on the display all segments will be made to
show the letter “E” to indicate an incorrect operation.
6. The demand reset counting mechanism can run either from 0 ... 99 or from 1 ... 12, to
correspond to the months of a year. The number of the reset counting mechanism
simultaneously serves as an auxiliary identifier for the preceding values. During the
register reading list, the symbol “&“ or „*“ displays whether the demand reset was
activated by pressing the push-button or another medium (internal clock, formatted
command, control input).
1-1:1.2.1 0.134 kW
By use of the modulo 12 counter, the number of the counter refers to the month
NOTE
7. The counting of the historical data reset is counting with the highest reset counter at
first (see item 6). Optionally the meter can be programmed, that “*1 is always the last
demand reset. If there is the next reset, *1 value goes to *2 and so on.
8. Resetting via the data interface is protected by a password, and acts on both all
demand and energy tariffs.
9. The performance of a demand reset by the demand reset push-button of one of the
interfaces will be always done directly. Only by using an external demand reset input
the demand reset can be delayed, if it is configured.
10. During the test mode, every demand reset will be performed directly.
11. A demand reset can be carried out on a daily, monthly or yearly base (at 00:00).
12. A demand reset can be carried automatically after a season change (00:00).
13. After power-up, the AS3500 meter checks whether an automatic demand reset has to
be executed during the power outage time. In that case, the demand reset lockout
time will not be started
14. Optionally it is possible to configure the meter in that way, that only one demand reset
during one month is accepted by the meter
16. The 3 highest demand values per year can be calculated at 31.12. of the year.
The analogue measured variables obtained are digitized in the ASIC and fed to a
downstream digital signal processor, which uses them to compute the active or reactive
powers plus the corresponding energies, and forwards energy-proportional pulses to the
tariff module. By using both digital multiplication and integration, significant advantages
can be achieved in terms of measuring stability and flexibility.
The scanning frequency has been selected to ensure that the electrical energy contained in
the harmonics is acquired with the specified class accuracy.
The total system power is the sum of the phase powers (Ferraris principle):
P = P1 + P2 + P3
Q= Q1 + Q2 + Q3
𝐒 = √𝐏 𝟐 + 𝐐𝟐
The theft-resistant measurement applies to the registration of active energy only. Therefore,
reactive and apparent energy registers are calculated and signed normally. Instrumentation
values, including active energy +P and –P, are also signed normally. Therefore,
instrumentation can be used to investigate the meter service wiring, while the theft-
resistant measurement guarantees that active energy is properly registered.
The following figures show how the energy direction indicators appear for negative active
and reactive power when using standard measurement and theft-resistant measurement.
Optional the AS3500 meter provides a measurement without a reverse run lock. In that case
the register the three-phase register for +A or -A energy can be decremented if the three-
phase energy direction flow is changing.
in case of negative values of the register, the value will be subtracted by 9.999.999;
with the register without reverse run lock a demand and load profiling is possible;
9.1 Calibration
The AS3500 meter has been adjusted in the factory, with the calibration constants matched
to the software concerned. Subsequent calibration by the customer is not required.
If the user is switching over to call mode during the test mode, the identifier selected and
the corresponding measured value will remain on the display until a new call is made or the
power supply is interrupted. The measured-value display is continually updated.
If the user presses the parameterization key before this test, then the display values
selected will be retained in the display.
Display
Arrow in display "OFF": no energy is being measured. This applies for all 4 possible
energy types (+P, -P, +Q, -Q);
LED
The "Standstill" function and "energy-proportional pulse output" are indicated for each
energy type by a shared LED. "Standstill" is signalled by a steady-light at the LED. Energy-
proportional pulses occur as optical "momentary pulses", with a duration in the 80 ms
range.
10 LOAD PROFILE
By using the internal load profile storage the actual demand or energy over a selectable
period (1 ... 60 minutes) can be stored. At the end of the storage capacity, the oldest value of
the load profile will be overwritten by the actual one.
With the load profile memory approved by the PTB, load profile memory contents are
interrogated and output in conformity with the VDEW requirements. The contents of the
output data records are formatted in terms of their data structure in conformity with EN
62056-61.
measuring quantities: +P, -P, Q1, Q2, Q3, Q4, +Q, -Q, +S, -S;
> 100 days for 1 channel (15 minutes period) large load profile;
> 600 days for 1 channel (15 minutes period);
The size of the load profile storage decreases with the number of channels
NOTE
The following types of measuring values can be stored in the load profile storage:
Recorded profiles can be deleted using the "W5 " command defined to supplement
DIN EN 62056-21.
Erasing the load profile memory will automatically erase the logfile.
ATTENTION
If the meter does not support the OBIS Identifier requested, it will return this as an
echo response. The part contained in the reply telegram between the two brackets
(which function as separators) is omitted completely.
If in conjunction with the load profile readout there is no entry in the inquiry for the
OBIS identifier of a measured value, the meter will respond with all available
measured values in its profile.
If the meter does not incorporate an internal device clock, then the following data will
be output instead of the timestamp:
for the date of the string: "999999" (OBIS Format: D6);
for the time of the string: "999999" (OBIS Format: Z6);
The telegram formed as the reply corresponds to the form specified in OBIS. It
contains in the "Address" field of the first data record the OBIS Identifier of the first
load profile excerpt of the reply. This is followed, in accordance with the definition
specified in OBIS, by a header-specific number of bracketed additional values, to
which are appended the likewise bracketed elements of the load profile excerpt.
If in the interval specified there is more than one section of the load profile, then a
new header will be inserted for each such section. The formation of new profile
headers during load profile transfer is explained with the events and status changes
coded in the first 8 bits (Bits 7 to 0) of the profile status word. The timestamp in the
header it is not assigned to the transactions, but assign to the formation of the first
profile value.
The overall length of the telegram answered will depend on the size of the interval
desired. The timestamps in the reply telegram are of the "ZSTs13" type. The output of
the telegram's data always begins with the oldest interrogated value.
If the order includes a request for a time range for which there are no entries, the
meter will respond with "P.01 (ERROR)”.
If the order requests an identifier which the meter does not support, the meter will
merely supply the values for the Identifier it does know.
<- header of load profile entry -> <- Measured value of load profile ->
Bit Significance
b7 Power failure.
b5 Change of time/date.
The status bit „b4“ can be used for 2 different configurable applications.
Bit „b4“ is active after a demand reset and;
Bit „b4“ is active after a 1- or 2ph power outage;
The status bit „b3“ can be used for 2 different configurable applications.
Bit „b3“ is active after summer/winter time change and;
Bit „b3“ is active after a reverse run detection;
A status entry will be generated in case one of the status bits going from “0” to
“1” as well as “1” to “0” (FW10.04).
P.01 Readout of the load profile 1) If the user wants all the
completely available in the meter (;) measured values of the
Readout of
load profile to be read,
load profile
then "KZn" Identifier
are omitted.
P.01 Readout of the measured values with 4) The timestamp behind the
the OBIS Identifier "KZ(1..n)" in an semicolon displays the end
interval: of the interval for readout.
(ZSTs11 ; ZSTs11)(KZ1) .. (KZn)
The use of the R6-command for reading load profile data is optimized for remote metering.
The advantage of that command is:
11 SETTING PARAMETERS
The setting parameters can be changed by the optical or electrical interface without
breaking the certification seal. They are protected by:
password;
Display control:
scroll time for the operating display;
maximum dwell duration of value on the display;
all parameters of second display data list “Abl-dAtA”;
The reference time for external time correction via the control input with the
associated time window.
Property number.
Passwords:
for setting mode via data interface;
for OBIS write commands ("W5" commands);
Set commands:
read/set pulse constants;
set outputs;
set active energy tariff;
set active demand tariff;
read/set display PIN code;
Read/write of PQ data:
Read/write upper/lower PQ thresholds;
Read/Write PQ interval;
Read/Write power outage detection interval;
Reset commands:
demand reset;
reset of meter error state;
reset of power quality monitoring;
reset power quality supervision counter;
reset power loss counter;
reset terminal opening counter;
12 INPUTS / OUTPUTS
Optical interface
Electrical characteristics: as per EN 62056-21;
Protocol: as per EN 62056-21;
Baud rate: maximum 9600 baud;
CL0-interface
Electrical characteristics: DIN 66348;
Protocol: as per EN 62056-21;
Baud rate: maximum 19200 Baud;
Number of meters in one loop: maximum 4 units;
connector 23 RX + 20mA interface +;
connector 24 RX - 20mA interface -;
RS485 interface
Electrical characteristics: terminals brought out: RT+ (Data+), RT- (Data-)
By using the RS485 interface up to 32 meters can be connected with a line length of
1000 m. The used protocol corresponds to EN 62056-21. In that case, the IEC meter
address should be used for reading the meters. In the following figure describes the way to
use the RS485 interface in combination with different meter types.
The RS485 bus has to be terminated (active) at modem side. On all Honeywell modems, this
is already realized internally.
Electrical characteristics:
OFF at ≤ 40V;
ON at ≥ 60V;
ON delay, typically 8 ms;
The electronic outputs can be used as control outputs ( see chapter 12.3.1 Electronic
control outputs) or as pulse outputs (see chapter 12.3.2 Electronic pulse outputs).
alarm indication;
overload conditions;
alarm indication;
overload conditions;
Additionally, the relays can be controlled using the internal clock of the meter or a formatted
command by one of the meter interfaces.
The number of overload exceeds can be counted and/or stored in a logfile. The user can
define 2 different thresholds for up to 2 control outputs.
1. The format of the selectable overload threshold and the demand are the same.
2. At the begin of the period, the output contact will be opened (closed).
3. The output contact will be closed (opened) under the following conditions:
4. Example:
nominal voltage: 3x230/400V;
current: 6A;
overload threshold: 0,5kW;
13 COMMUNICATION MODULE
For Smart Metering or Commercial and Industrial applications, a communication module
will fit into a designated place on top of the AS3500 meter.
AM122
GSM/GPRS or LTE interface
AM322
Ethernet interface (coming soon)
AM540
PLC/OFDM and wired M-Bus interface
The interface between the meter and the communication module provides the following
feature set:
isolated communication interface to read the AS3500 meter data (Rx, Tx). The used
protocol is based on EN 62056-2;
2 terminals are provided by the meter in case a wired M-Bus communication is used;
customer interface using an RJ11 connector on the right side of the meter terminal cover
(optional);
AM540: G3-PLC module, which uses OFDM physical layer and the DLMS/COSEM
protocol with an optional wired M-Bus interface.
More details can be found in the specific user guides of the communication modules.
14 SECURITY
If there is a malfunction or an operator error, the error messages and/or diagnostic alarms
on the display will output a detailed error Identifier, which can be evaluated via the optical or
electrical interfaces. It can contain one or more error messages.
There is also an option for displaying the error message in conformity with the OBIS
Identifier Number system (Identifier "F.F"). Up to 4 groups of errors are supported. The
significance of the individual bits in each group can be selected on a manufacturer-specific
base. In the AS3500 meter, the following specifications for fatal errors apply, beginning
from the left:
If any error condition (F.F, F.F.1, F.F.2) will occur, an alarm indicator on the LCD will be
activated (see chapter 6.1 Display).
If an error of this kind occurs, the meter's certification will be cancelled, and the display will
be frozen ("F.F * * * * * * * * "). The error identifier can also be read out through the electrical
or optical interface.
0 0 0 0 0 0 0 0
If an alarm of this kind occurs, the display will be frozen ("F.F.1 * * * * * * * * "). An alarm of this
kind can likewise be read out through the electrical or optical interface.
0 0 0 0 0 0 0 0
Diagnostic messages
Error identification with OBIS Identifier F.F.2
If a diagnostic message of this type occurs, it is output on the display in a rolling depiction
with "F.F.2 * * * * * * * * ". A diagnostic message of this kind can likewise be read out through
the electrical or optical interface.
0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0
an alarm indicator will be activated (alarm indicator will be activated after every
detected warning or error, F.F, F.F.1, F.F.2);
this feature is available during a power outage (detection with time and date stamp
after next power-up);
the start date and time of the terminal cover removal detection will be stored
together with the end date and time of the event. It can be read out using the register
data list. The format will be: C.77.8 (start date and time; end date and time);
the counter (0 ... 99) and the error message will be reset by “Formatted commands”:
counter reset;
register reset;
demand reset;
the terminal cover opening alarm on the LCD (F.F.1 00010000) will be reset
automatically after a register data readout;
the terminal cover opening alarm on the LCD (F.F.1 00010000) will be reset
automatically if during the last 2 demand resets no additional opening occurred;
the terminal cover opening alarm on the LCD (F.F.1 00010000) will be reset
automatically in case the terminal cover is mounted again (10.04 and 10.05);
an alarm indicator will be activated (alarm indicator will be activated after every
detected warning or error, F.F, F.F.1, F.F.2);
this feature is available during the power outages (detection with time and date
stamp after next power-up);
the start date and time of the front cover removal detection will be stored together
with the end date and time of the event. It can be read out using the register data list.
The format will be: C.77.7 (start date and time; end date and time);
Additionally, the meter offers magnetic field detection. In case of such a tamper issue the
event is stored with time and date as described below:
start and end of a magnetic field detection with time and date stamp;
logfile entry with time and date stamp in case no communication between meter and
module happens (configurable timeout);
The same log Bit will be used for this event as well as for the terminal cover removal
detection.
NOTE
the logfile event Bit, as well as the F.F.1, will be cleared by using the “Reset error
status;
demand reset;
with every single or 3-phase power outage the total active energy register is stored in
the logfile;
Certified logfile
The logfile of the meter can be used as a „certified logfile“. It is not possible to delete the
logfile without breaking the certification seal. Therefore it is allowed to change the meter
LED and pulse output constants under the following conditions:
every change of the pulse constants will be registered in the logfile with;
the load profile storage has the same size as the load profile storage;
Logfile format
The operating logbook entries of the meter can be read out in accordance with the load
profile procedure:
the operating logfile is treated as a load profile. The Identifier "P.98" designates the
operating logbook of the VDEW Specification meter.
the operating logfile is read out using the "R5" formatted commands, which are
specified as follows to supplement DIN EN 62056-21: The "R5" command causes a
load profile formatted with OBIS to be output. The answer generated by the meter in
response is given as a self-sufficient telegram.
erasure of the operating logfile is performed using the "W5" command defined to
supplement DIN EN 62056-21. Erasing the logfile automatically causes the load
profile memory to be erased.
if a time range is requested in the order, but there are no entries for it, the meter will
respond with "P.98 (ERROR)”.
the status word describes the event or the status change which has led to the event
in the logbook. In the status bit, however, more than one status bit can be set to "1".
Which event entails which element information is defined in the next section.
<- header of load profile entry -> <- content of the logfile ->
P.98 Readout from the beginning of the The timestamp behind the
logbook record in the meter up to an semicolon designates the
end time end of the interval for
(;ZSTs11) readout.
error messages;
status information (wrong rotation field, power outage, etc., see chapter
14.10 Display of meter status information);
The following last 10 events can be displayed in the register data list:
OBIS ID: 96.77.1*vv - last 10 events with time and date stamp;
OBIS ID: 96.77.1 - counter of power outage L1;
OBIS ID: 96.77.3*vv - last 10 events with time and date stamp;
OBIS ID: 96.77.3 - counter of power outage L3;
OBIS ID: 96.73*vv - last 10 events with time and date stamp;
OBIS ID: 96.73 - counter of rotation field detection;
OBIS ID: 96.78*vv - last 10 events with time and date stamp;
OBIS ID: 96.78 - counter of magnetic field detection;
selectable IEC address for electrical and optical communication (only by sending the
IEC address a successful communication can be achieved;
Furthermore, flexible security protection is available. For optical and electrical interface,
separately the following parameters can be secured by different passwords: demand reset
push-button, terminal cover opening or hardware jumper.
A. Meter parameters
Identification x
Tariff source x
Demand reset x
Demand overload x
Baud rate x
Synchronization x
Power quality x
Display settings x
Display parameters x x
Pulse constants x x
Load profile/logfile x x
Energy/demand data x x
Password
x x
configuration
B. Formatted commands
Demand reset x
Reset PQ profile x
C. Reading commands
Logfile x
Load profile x
Profile of network
x
parameters
Hardware protection
The AS3500 meter can be configured by using one of its interfaces (electrical or optical).
The setting parameters are secured by a meter password and/or demand reset push-
button, terminal cover, IEC address.
Billing parameters can optionally be secured by a hardware jumper, which must be operated
as follows:
after opening the front cover of the meter, the user has access to the
parameterization button;
after setting the jumper (2 pins will be connected) the meter parameterization mode
is enabled. All cursors on the LCD are flashing;
after removing the jumper, the meter parameterization is disabled. Only the setting
parameters can be changed anymore (see chapter 11. Setting parameters);
0 0 0 0 0 0 0 0
8 energy tariff T1;
x reserved or not used;
1 energy tariff T8;
2 energy tariff T7;
4 energy tariff T6;
8 energy tariff T5;
x reserved or not used;
4 directional signal, reactive (+Q);
8 directional signal, reactive (+P);
x reserved or not used;
x reserved or not used;
Status of internal control signals (Status Word 3)
Interpretation of the status word with OBIS Identifier C.5:
0 0 0 0 0 0 0 0
x reserved;
8 voltage L1;
4 voltage L2;
2 voltage L3;
1 correct rotating field;
8 reversal disable, active (reverse warning);
8 start-up, active energy measurement;
4 start-up, reactive energy measurement;
4 terminal cover removal detection;
2 front cover removal detection;
1 magnetic field detection;
8 parametrization mode;
4 setting mode;
2 tariff source clock;
1 tariff source ripple control receiver;
1 contactor relay – switch off by communication;
2 contactor relay – switch off by load limiting function;
8 reset disable, manual;
4 reset disable, optical interface;
2 reset disable, electrical interface;
To manipulate the meter in most cases the terminal cover has to be opened. This event can
be stored with time and date stamp.
The opening of the certified front cover is detected in the same way as the terminal cover
opening.
In case a large magnet is used nearby the meter, this event will be detected.
Security concept
The tampering of the meter configuration is secured by different password levels and
additional by opening the terminal cover, which is normally sealed by the utility seal. For
details, see chapter 14.2 Terminal cover removal detection.
Logfile
All tampering issues, power outages, etc. can be stored with time and date stamp in the
logfile of the meter. For details see chapter 14.6 Basic logfile.
The duration of anti-creep conditions can be measured by the meter. This can be used as
an indication of meter manipulation.
The meter can be configured in that way that it always the total energy is measured, even in
the case of reverse energy flow. For details see chapter 8.2.5 Measurement without reverse
run lock.
The reverse energy measurement can be used to detect tampering. In that case the exact
“tampered energy value” is available.
If an invalid password is used more than a configurable maximum number of attempts, the
communication will be blocked by the meter until the next demand reset.
NOTE
15 INSTRUMENTATION MEASUREMENT
frequency;
All parameters can be displayed on the LCD or read out by the optical or electrical interface.
The activation/deactivation of the measurement can be done without breaking the
certification seal.
All instantaneous parameter can be assigned to the standard data readout list or in a
separate service list.
Every 1s the measured value is compared with the threshold. In case the value is below or
above the threshold a warning (F.F.3) can be generated, depending on the configuration.
The counter will be incremented only if the average measured value of the period is
above/below the threshold.
Furthermore, 2 logfile events and 2 relay contacts can be activated if 1 or more events will
be above or below the predefined threshold. Every 1s the measured value is compared with
the threshold. Only if all values inside the period are above/below the threshold, the counter
will be incremented.
>threshold 1a Counter 1a
<threshold 1b Counter 1b
>threshold 2a Counter 1a
<threshold 2b Counter 1b
>threshold 3a Counter 1a
<threshold 3b Counter 1b
>threshold 4a Counter 1a
<threshold 4b Counter 1b
>threshold 5a Counter 1a
<threshold 5b Counter 1b
>threshold 6a Counter 1a
<threshold 6b Counter 1b
>threshold 7a Counter 1a
<threshold 7b Counter 1b
>threshold 8a Counter 1a
<threshold 8b Counter 1b
>threshold 9a Counter 1a
<threshold 9b Counter 1b
use of EN 62056-21 protocol, identical to the readout of the load profile of the
billing data;
data storage depends on the size of the load profile of the billing data;
The status bits of the network parameter profile are designed as:
MG - Measurement disturbed;
The bit is set at the end of the interval if after initialization or after a power-up not all
values are calculated.
With every time and date change, the actual interval will be aborted.
SA - Power outage;
SW - Power up;
After every power up the bit will be set at the end of the interval.
counter for sags and swells, which increments if the value of each interval is exceeded;
measuring interval for PQ data are the same as for PQ profile (see chapter 15.3 Load
profiling of power quality parameters);
the minimum and maximum calculation is done between the duration of 2 following
demand resets;
all minimum and maximum data are available with time and date stamp;
the minimum and maximum measurement can be used with the following power
quality data;
voltage and current per phase;
frequency;
power factor per phase and total;
active, reactive and apparent power per phase and total;
Using this functionality, the meter can be used to control the network regarding power
quality data. For example, the maximum and minimum voltage and the maximum current
can be calculated.
total absolute 3-phase energy (/A/ = /A1/ + /A2/ + /A3/; /Ri/ = /Ri1/ + /Ri2/ + /Ri3/; …)
All energy quantities are counted in separate energy register (2x4 = 8 registers).
The total number of digits and the number of decimals is the same as for the 3-phase
energy quantities.
the tan φ is defined as the ratio of active energy divided by reactive energy
consumption;
the tan φ value can be displayed on the LCD or read out by the optical or electrical
interface;
if the current tan φ value exceeds the threshold the following events can be activated:
warning on the LCD;
control output will be activated;
16 INSTALLATION
As soon as the meter has been connected to the power supply, a corresponding indicator in
the display will show that the phase voltages L1 to L3 are present.
If the meter has started up, this will be indicated directly by an arrow in the display, and by
the energy pulse LED, which will flash in accordance with the pre-set pulse constant.
Scroll mode
As long as the alternate push-button is not pressed, the scroll mode will appear. Depending
on the version involved, this may consist of one value or several values, shown in a rolling
display mode.
Display check
When the alternate push-button is pressed, the first thing to appear is the display check.
All segments of the display must be present. Pressing the alternate push-button will switch
the display to its next value.
Error message
Fast run-through
If the alternate push-button is repeatedly pressed at intervals of 2s < t <5s, all the main
values provided will appear.
Phase failure
Display elements L1, L2, L3 are used to indicate which phases of the meter are energized.
Rotating-field detection
If the meter's rotating field has been inversely connected, the phase failure detection
symbols will flash.
Creep check
If the meter starts measuring, the energy pulse diode will blink according to the measured
energy. The relevant arrows (+P, -P, +Q, -Q) on the display are switched ON after 2-3s.
Anti-creep check
If the meter is in idling mode, the energy pulse diode will be continuously lit up. The relevant
arrows (+P, -P, +Q, -Q) on the display are also switched off.
If during the installation process of a 3x230/400V meter phase and neutral will be changed
the meter will respond on the LCD as follow:
In that case, the power of the meter should be switched off immediately and the installation
should be checked again. Otherwise, the meter can be damaged after 4h.
on the nameplate of the meter a specific symbol for single-phase application must
be printed;
for this application, the user must reconfigure the meter using the alphaSET tool
(otherwise error warning on the LCD will appear regarding missing phase 1 and 2);
17 USER PROGRAM
Reading and configuration tool alphaSET
The AS3500 meter can be readout, set and parameterized via the optical or electrical (CLO)
interface, in accordance with the EN 62056-21 protocol.
For this purpose, the user needs the alphaSET readout and setting tool, which can be used
to alter and readout the meter's register contents, load profile and logfile data and all
settings parameters. The program is a 32-Bit application and runs under Windows 7,
Windows 8, Windows 8.1 and Windows 10.
readout parameters
standard data list;
service list (second data readout list);
logfile;
load profile of billing data;
profile of instrumentation parameters;
complete meter configuration;
formatted commands
set time and date;
set pulse constant;
reset all counters;
reset profile of instrumentation parameters;
reset load profile of billing data;
reset register data;
19 APPENDICES
Front plate
AS3500 x x x x x x x x x x x x x x x x x x x x
CT standard connection W
3x220/380V (4-wires, 3-systems) F
3x230/400V (4-wires, 3-systems) 1
3x240/415V (4-wires, 3-systems) M
3x120/208V (4-wires, 3-systems) 9
3x127/220V (4-wires, 3-systems) B
3x58/100V (4-wires, 3-systems) 3
3x63/110V (4-wires, 3-systems) 4
3x100V (3-wires, 2-systems) 5
3x110V (3-wires, 2-systems) 6
3x120V (3-wires, 2-systems) D
3x220V (3-wires, 2-systems) E
3x230V (3-wires, 2-systems) L
5(6)A 2
1(6)A* 4
5(15)A A
5(10)A B
1,5(6)A C
Class 0,5S 5
Class 1 1
Class 2 2
Class C C
Class B B
Class A A
Quantity +P 1
Quantity +P, -P 2
Quantity +P, +Q 3
Quantity +P, Q1, Q4 4
Quantity +P, -P, +Q, -Q 5
Quantity +P, -P, Q2, Q3 6
Quantity +P, -P, Q1, Q2, Q3, Q4 7
Quantity +P, Q1 8
Quantity +P, +Q, -Q 9
AS3500 x x x x x x x x x x x x x x x x x x x x
AS3500 x x x x x x x x x x x x x x x x x x x x
Nominal frequency, 60 Hz 1
* on request
The meter supports two protocols for reading the meter data:
EN 62056-21 protocol;
DLMS/COSEM protocol;
EN 62056-21 protocol
Standard data readout list
The following table presents a sample of the standard data readout list of a meter with
active and reactive and demand measurement and 2 tariffs. The standard data readout list
contains all billing data.
Format on
OBIS identifier Length Designation
the display
Format on
OBIS identifier Length Designation
the display
All parameters of the standard data readout lists can be changed only by breaking the
certification seal of the meter.
ATTENTION
Format on the
OBIS identifier Length Designation
display
C.55 XXXXXX 6 The end date of the last 3-phase power outages.
The table below provides information on which single registers and OBIS Identifier can be
read or written. The "R5" and "W5" commands defined in conformity with EN 62056-21 are
used for this purpose:
Commands
OBIS identifier Significance Remarks
R5 / R6 / W5
Also, the "R5" command can be used to read out individually all the registers contained
in the readout list.
ATTENTION
Data format
The data format according to the EN 62056-21 protocol standard is defined as 8,n,1;
According to the EN 62056-21 protocol, the standard data readout list, as well as the
service list, is not protected by a password.
For security reasons two possibilities are provided to secure the meter reading data of the 2
lists:
In that case, the IEC address of the meter is used for all type of communications and
acts as a password
The AS3500 supports the possibility to disable the reading of the standard data
readout list as well as the service list.
In that case, the reading of the register data has to be done using the R5-commands,
which can be protected by a password. Using the R5.commands every single register
can be read out by using the OBIS identifier for addressing the register value.
DLMS/COSEM protocol
In addition to the standard EN 62056-21 protocol, the AS3500 meter provides optionally
the DLMS/COSEM protocol too. Therefore a second microcontroller is doing a protocol
conversion from EN 62056-21 to DLMS/COSEM
DLMS FW V1
Reading of single registers using the OBIS identification system;
Reading of billing load profile data;
Reading of power quality profile data;
Reading of logfile data;
Read and write time and date;
The DLMS/COSEM protocol can only be supported by the electrical interface of the
meter.
ATTENTION
identifiers for measuring values; these are starting with a number between 1 and 89;
identifiers for general-purpose objects; these are starting either with a “0”, a “C” or a
“96”;
The second number (“value group D”) stands for the measuring type, e.g. x.5 = “last average”
or 8 = “time integral 1”.
Below there is a list of all possible combinations, delivered by the meter. To shorten the list,
the tariff, if delivered, is represented by the placeholder “t”, this can be a cypher 0 ... 4.
Power measuring
Energy measuring
Instantaneous values
Supervision data
32.1.8 Spare
0.2.0(iiii)<CR><LF>
0.2.0 Program revision No. | |
| +-length 4 ASCII-chars
+------ OBIS identifier
0.2.0(iiiiiiii)<CR><LF>
0.2.1 Parameter set identification | |
| +-length 8 ASCII-chars
0.2.2 Time switch program no. +------ OBIS identifier
0.3.x(123456.12)<CR><LF>
0.3.0 LED pulse constant active energy | | ||
| | |+--- 2 decimals
0.3.1 LED pulse constant reactive energy | | +--- decimal dot
| +1 to 6 pre-dot cipher
+----------- OBIS identifier
0.3.3 Output pulse constant active energy
0.8.0(nn)<CR><LF>
0.8.0 Measurement period (the length of … in | |
minutes) | +----- 2 cyphers 01…60
+----------- OBIS identifier
0.9.0(nn)<CR><LF>
0.9.0 Number of days since the last reset | |
| +----- 2 cyphers 00…99
+----------- OBIS identifier
C.2.0(iiiiiiii)<CR><LF>
C.1.0 Meter serial number | |
| +-length 8 ASCII-chars
+------ OBIS identifier
C.2.0(nn)<CR><LF>
C.2.0 Number of parameterizations | |
| +----- 2 cyphers 00…99
+----------- OBIS identifier
0.x.0(123456)<CR><LF>
C.6.1 Battery usage timer | |
| +---- length 6 cyphers
C.7.0 Sum of total power failures of all 3 lines
+----------- OBIS identifier
0.x.0(123456)<CR><LF>
C.7.1 Sum of power failure, phase 1 | |
| +---- length 6 cyphers
C.7.2 Sum of power failure, phase 2
+----------- OBIS identifier
C.7.3 Sum of power failure, phase 3
C.56(123456)<CR><LF>
C.56 Total time of ALL power fails / battery use time | |
counter | +----- length 6 cyphers
+----------- OBIS identifier
C.63(mm:ss)<CR><LF>
C.63 Remaining time in the interval | |
| +------ minutes:seconds
+----------- OBIS identifier
C.65(hhhhhhhh)<CR><LF>
C.65 Parameter checksum | |
| +- checksum 8 Hex-chars
+----------- OBIS identifier
C.70(nn)<CR><LF>
C.70 Source of tariffs/demand reset | |
| +--- 2 HEX chars 00…FF
+--------- OBIS identifier
C.79 Tan φ Q4
C.80 Tan φ Q1
P.98 Logfile
F.F.2 Warnings
F.F.3 Warnings
F.F.4 Warnings
Changes
No changes were made to this user guide because it is the initial user guide of the AS3500
meter, in the new Honeywell format. This document is based on the existing document –
AS3500_PR_E, revision 1.6, 30.01.2015.
19.10 Abbreviations
Abbreviation Explanation
A Active energy
R1 Reactive energy QI
P Active power
Abbreviation Explanation
Q Reactive power
MD Maximum demand
PF Power factor