Esser IQ8Control Fire Panel and Tools 8000 Software

Important points:
1) Number of total devices per Zone = 32
2) Number of Total devices per loop = 127
3) Up to 32 zone and 32 output sectors can be assigned to a panel (99 zone and output
sectors with IQ8Control from firmware 3.08)
4) Up to 15 detector zones can be assigned to each detector zone sector
5) The detector zones to be programmed are not restricted to local fire alarm control
panels
6) Up to 15 control zones (100 controls zones for IQ8Control panels) can be assigned to
each output sector
7) Up to 100 control zones can be assigned to the sectors in each panel
8) Output sectors can only be programmed with control zones of the local FACP
9) Alarm or delay timers can be assigned to each output sector
10) the programmable output sector type depends on the alarm device that is used
11) Up to 9999 Detector and Control zones can be installed in a network.
12) Total 31 Network Devices can internetworked while using baud rate 500 kBd.
13) Total 16 Network Devices can internetworked while using baud rate 62.5 kBd.
14) If distance between two networked panels exceed 1km, a repeater should be used.
15) Total 2 repeaters can be used between two panels.
16) Max 8 communication transponders per analogue loop can be installed.
17) Max 16 communication transponders can be installed per FACP.
18) Max 32 ESSERBUS transponders per analogue loop can be installed.
19) Max 100 ESSERBUS transponders can be installed per FACP.
20) ESSERBUS PLUS analogue loop provides 42 V of voltage.
21) Total 7 ESSERBUS analogue loop modules can be connected to FACP.
22) Total 4 ESSURBUS PLUS analogue loop modules can be connected to FACP.
23) The ESSERNET micro module can cause interference with radio devices or TV receivers
so should be kept at distance of 10 m.