You are on page 1of 832

Electrical

Transmission and
Distribution
Reference Book

bY
Central Station Engineers
of the
Westinghouse Electric Corporation
EAST PITTSBURGH, PENNSYLVANIA
Copyright 1964
by Westinghouse Electric Corporation, East Pittsburgh, Pennsylvania
Fourth Edition: Fourth Printing
Printed in the United States of A,merica
_( _: ‘,

and Distribution

‘,,,’

-?-
This book is dedicated to the memory of
ROBERT D. EVANS
who contributed so greatly to the
transmission and distribution of electric power
and to the preparation of
the original edition of this book
Preface to fourth edition

Some thirty years ago a well-known electrical engineer was ordered


by his physician to take a complete rest. During this period, as a
diversion, he began to study transmission-line calculations. Out of
that came, in 1922, a book that was quickly recognized as a classic on
the subject because it was simple, practical, useful. The man was
William Nesbit; the book, “Electrical Characteristics of Transmis-
sion Circuits.”
In the two succeeding decades power-transmission systems grew
tremendously in complexity. Voltages were doubled, longer lines
were built, interconnections became more extensive, knowledge of
how to protect against lightning was greatly increased, and new
methods of calculating performances were adopted. With all this
grew the need for a new book on transmission lines, one of broader
scope that would meet the new conditions, but retain the entirely
practical viewpoint of its predecessor. Fourteen men, all connected
with the Central Station Engineering Group of the Westinghouse
Electric Corporation, undertook to produce such a book. All of these
men worked daily on actual problems such as are considered here.
With this background of experience and with the reputation of the
Nesbit book as inspiration, they presented in January, 1942 the first
edition of a book which they hoped would be useful to all concerned
with electric-power transmission as a practical reference book, helpful
in solving everyday problems.
In 1943 a second edition was brought out in which two chapters
that discussed the general features of the electrical distribution
problem were added at the end of the book. The third edition differed
from the second edition only in that the two chapters were introduced
just before the appendix.
A fourth and completely rewritten .edition is presented herewith.
It contains essentially the material of the previous three editions,
sometimes with new authors, and three new chapters-Excitation
Systems, Application of Capacitors to Power Systems, and Power
Line Carrier Application. As before, all of the authors are from the
Central Station Section or are closely associated with it. As was the
case with previous editions, this one also bears the imprint of two
outstanding engineers, who contributed so much to the transmission
of power, Dr. Charles L. Fortescue and Mr. Robert D. Evans. The
latter, before his recent death, was one of the active participants in
the previous editions. The name or names of the original authors
and the revising authors appear at the head of each chapter.
To conform to the original standards regarding the sign of reac-
tive power, the authors in the first edition of this book found it
necessary to change the curves and discussions from what they had
used in their previous publications. With the recent change in the
standards, the sign has again been changed so that the curves and
discussions now use lagging kvar as positive.
The material presented here is naturally the results of research
and investigations by many engineers. It is not feasible to list here
the names of the companies and individuals whose work has been
summarized. These acknowledgments are given in the individual
chapters. Much of the material used has been the result of cooperative
studies of mutual problems with engineers of electric-power com-
panies, the conductor and cable manufacturers, and the communica-
tion companies. The authors gratefully acknowledge the hearty
cooperation of those engineers whose work has assisted in the prepara-
tion of this book. Thetitle page photograph is reproduced by per-
mission of the Bureau of Reclamation, Grand Coulee, Washington.
The acknowledgments would be incomplete without giving recogni-
tion to the fine cooperation of the editorial staff of the Westinghouse
ENGINEER, in reviewing the material and making many helpful
suggestions to the authors and to Mr. Raymond W. Ferguson, who
assisted in editing the material.
A. C. MONTEITH
Vice President in Charge of Engineering
,
C. F. WAGNER
Consulting Engineer
September 1, 1950
Contents
Original Aulhor m and Revising Author
CHAPTER 1 General Considerations of Transmission . . . . . . . page 1
C. A. Powel n C. A. Powel

Symmetrical Components . . . . . . . . . . . page 12


J. E. Hobson n D. L. Whitehead

Characteristics of Aerial Lines . . . . . . . . . . page 32


Sherwin H. Wright and C. F. Hall n D. F. Shankle and R. L. Tremaine

4 Electrical Characteristics of Cables . . . . . . . . . puge 64


H. N. Muller, Jr. n J. S. Williams

5 Power Transformers and Reactors . . . . . . . . . page 96


J. E. Hobson and R. L. Witzke n R. L. Witzke and J. S. Williams

6 Machine Characteristics . . . . . . . . . . . . page 145


C. F. Wagner n C. F. Wagner

Excitation Systems . . . . . . . . . . . . . pdge 195


J. E. Barkle, Jr.

Application of Capacitors to Power Systems . . . . . . page 233


A. A. Johnson

9 Regulation and Losses of Transmission Lines . . . . . . page 265


G. D. McCann n R. F. Lawrence

10 Steady-State Performance of Systems Including Methods of


Network Solution . _ . . . . . . . . . . . . page 290
E. L. Harder n E. L. Harder

11 Relay and Circuit Breaker Application. . . . . . . . page 342


E. L. Harder and J. C. Cunningham 8 E. L. Harder and J. C. Cunningham

12 Power-Line Carrier Application . . . . . . . . . . page 401


R. C. Cheek

13 Power-System Stability-Basic Elements of Theory and


Application. . . . . . . . . . . . . . . . page 433
R. D. Evans and H. N. Muller, Jr. m J. E. Barkle, Jr. and R. L. Tremaine

14 Power-System Voltages and Currents During Abnormal


Conditions . . . . . . . . . . . . . . . . page 496
R. L. Witzke = R. L. Witzke
Original Author n and Revising Author
CHAPTER 15 Wave Propagation on Transmission Lines . . . . . . . page 523
C. F. Wagner and G. D. McCann a C. F. Wagner

16 Lightning Phenomena . . . . . . . . . . . . page 542


C. F. Wagner and G. D. McCann m C. F. Wagner and J. M. Clayton

17 Line Design Based on Direct Strokes . . . . . . . . page 5%


A. C. Nonteith m E. L. Harder and J. M. Clayton

18 Insulation Coordination . . . . . . . . . . . . page 610


A. C. Monteith and H. R. Vaughan n A. A. Johnson

19 Grounding of Power-System Neutrals . . . . . . . . page 643


8. B. Griscom n S. B. Griscom

20 Distribution Systems . . . . . . . . . . , . . page 666


John S. Parsons and H. G. Barnett n John S. Parsons and II. G. Barnett

21 Primary and Secondary Network Distribution Systems . . . page 689


John S. Parsons and H. G. Barnett m John S. Parsons and H. G. Barnett

22 Lamp Flicker on Power Systems . . . . . . . , . page i19


S. B. Griscom m S. B. Griscom

23 Coordination of Power and Communication Systems. . . . page 741


R. D. Evans n R. L. Witzke

Appendix . . . . . . . . . . . . . . . . page 784

Index . . . . . . . . . . . . . . . . . page 813


CHAPTER 1

GENERAL CONSIDERATIONS OF TRANSMISSION


Original Author: Revised by:
C. A. Powel C. A. Powel

T
HROLGH discovcry, invention, and engineering ap- Barrington to its present size involving as it does a cnpital-
plication, the engineer has made electricity of con- ization in the privately-owned powcr companies of some
tinually grcnter 11seto mankind. The invention of 17 billion dollars with an annual revenue of 4 billion dollars.
the dynamo first mntle engine power many tiines more The growth since the beginning of this century in in-
effective in relieving the toil and increasing the opportu- stalled generating capacity of all electric polver plants
nities and comforts not only of industry but also of the
home. Its scope, hoxever, was limited to relatively short
distances from the powr station because of the low voltage
of the distribution circuits. This limitation, for economic
reasons, kept, the general IN: of electricity confined to city
areas \\.herc a number of customers could be served from
the same power station. The nest step in the development
of the present-day electric systems was the invention of the
transformer. This invention was revolutionary in its effect
on the electric industry because it made high voltage and
long transmission distances possible, thus placing the
engine po\\-er, through the medium of the nlternating-
current generator, at the doorstep of practically everyone.
The first alternating current system in America using (a (b)
transformers was put in operation at Great Barrington in Fig. l-(a) Gaulard and Gibbs transformer for which George
Massachusetts in 1886. Mr. William Stanley, Westing- Westinghouse had secured all rights in the United States.
house electrical espert II-ho was responsible for the installa- (b) First transformer designed by William Stanley. The proto-
type of all transformers since built, it definitely established
tion, gives an account of the plant, part of which reads: the commercial feasibility of the alternating-current system,
“Before leaving Pittsburgh I designed several induction coils, 1884-1886.
or transformers as we now call them, for parallel connection.
The original was designed in the early summer of 1853 and contributing to the public supply has been from about 13
wound for 500 volts primary and 100 volts secondary emf. million kilowatts to 55 million kilowatts in 1948. Of this
Several other coils were constructed for experimental purposes. 55 million kilowatts the privately-owned utilities account-
“iit the north end of the village of Great Barrington was an old ed for 44 million kilowatts and government-owned ut,ilities
desertedr&her mill which I leasedfor a trifling sum and erected for 11 million kilowatts divided equally between the
in it a 2.5 hp boiler and engine that I purchased for the purpose. federal government and local governments. Thus, 80
After what seemed an interminable delay I at last installed the percent of the generating capacity of the country is pri-
Siemens alternator that 1\Ir. Westinghouse had imported from
vately owned and 20 per cent government owned.
London. It was wound to furnish 12 amperes of current with a
maximum of ,500volts. In the meantime I had started the con- With this 55 million kilowatts of generating capacity,
struction of a number of transformers in the laboratory and en- 282 billion kilowatt-hours, divided 228 billion kilowatt-
gaged a young man to canvass the town of Great Barrington for hours by privately-owned generation and 54 billion public,
light customers. Ke built in all at Great Barrington 26 trnns- were generated in 1948. The average use of the installed
formers, 10 of which were sent to Pittsburgh to be used in a capacity for the country as a whole was, therefore,
demonstration plant between the Union Switch and Signal Com- 282 000
pany’s factory* and East Liberty. p-5130 hours, and the capacity factor for the
“We installed in the town plant at Great Barrington two 50- 55
light and four 25-light transformers, the remainder being used in 5130
country as a whole -87G0= 58.5 percent.
the laboratory for experimental work. The transformers in the
village lit 13 stores, 2 hotels, 2 doctors’ ofices, one barber shop,
and the telephone and post offices. The length of the line from
This capacity factor of 58.5 percent is generally con-
the laboratory to the center of the town was about 4000 feet.” ceded as being too high. It does not allow sufficient margin
to provide adequate spare capacity for maintenance and
Our central-station industry today is, for all practical repairs. Fig. 2 illustrates how the spare and reserve
purposes, entirely alternating current. It can, therefore, capacity has shrunk in the past few years. 11 ratio of
be said to have grojvn from the small beginning at Great installed capacity to peak load of 1.15 to 1.20 is considered
*About two miles. necessary to provide a safe margin for emergencies. Such
1
General Considerations of Transmission Chapter 1

The average cost of all electricity used for residential


service has shown a steady downward trend since 1925
from 7 cents per kilowatt-hour to 3 cents in 1948. This is
all the more remarkable as since 1939 all other items mak-
ing up the cost-of-living indes have shown increases rang-
ing from 10 percent (for rents) to 121 percent (for food),
the average increase of all items being 69 percent. The
revenue from sales to residential customers accounts for
about 36 percent of the total utility revenue; to large
power customers about 29 percent; t,o small light ant1
power customers 27 percent, and to miscellaneous cus-
tomers (railroads, street lighting, etc.) 8 percent.
1. Sources of Energy
The sources of energy for large-scale generation of elec-
t,ricity are:
1. Steam, from (a) coal, (b) oil, or (c) natural gas
2. Water (hydro-electric)
3. Diesel power from oil
Other possible sources of energy are direct solar heat,
windpower, tidal power, shale oil, and atomic energy, but
none of these as yet has gone beyond the pilot-plant stage,
for the reason that coal and petroleum are still abundantly
OF KILOWATTS
available. But as fossil fuels become scarcer and more
expensive, there is every reason to believe that all of these,
OF KILOWATTS as well as petroleum manufactured from vegetable matter,
II/IIIlIIl may^ become useful and economical supplementary sources

1910 1920 1930 1940


I I I I I I
1950
ot energy.
The estimated reserves of coal and lignite in the United
ls6’ States are about 3000 billion tons. This constitutes almost
YEAR
99 percent of the mineral fuel energy reserves of the
Fig. 2-Trend in production of electricity, installed capacity, country; oil shale, petroleum and natural gas amounting
and sum of peak demands.
to little more than 1 percent.’
a margin in 1948 would have given a capacity-factor of By far the greater part of the electric energy generated
about 53 percent, instead of 58.5 percent. in this country is obtained from fuel, the 55 million kilo-

TABLE ~-PREFERRED STANDARDS FOR LARGE 3600-RPM ~-PHASE 60-CYCLE CONDENSING


STEAM TURBINE-GENERATORS
-
11ir-Cooled Hydrogen-Cooled Generators
Generator Rated for 0.5 Psig Hydrogen Pressure
Turhine-generator rating, kw 11500 15000 20000 30000 40 000 60000 no ooo*
Turhine capability, kw 12650 16 500 22000 33000 44 000 66 000 99 000 I
Generator rating, kva 13529 17647 23529 35294 47058 70588 105882
power factor 0.85 0.85 0.85 0.85 0.85 0.85 0.85
short-circuit ratio 0.8 0.8 0.8 0.8 0.8 0.8 0.8
Throttle pressure, psig 600 850 850 850 /850\orj1250\ /85O\orj 1250 \ Fl45Ojorjl4~50\ **
Throttle temperature, F 825 900 900 900 \9ooj \ 950/ \900( \ 95oj :1oooj \lOOO(
Reheat temperature, F 1000
Sumher of extraction openings 4 4 4 5 5 5 5 5
Saturation temperatures at, Is1 t 175 175 175 175 175 175 180 Ii.5
openings at “turbine-gen- 2nc1 235 235 235 235 235 235 245 240
erator rating” with all ex- 3rc1 285 285 285 285 285 28.5 305 300
traction openings in serv- 4tt 1 - 350 350 350 350 350 350 380 370
ice, F 5t11 410 410 410 440 440
Eshaust pressure, inches Hg abs 1.5 1.5 1 .5 1.5 1.5 1.5 1.5 I.5
Generator capability at 0.85 power factor am.I
15 psig hydrogen pressure, kvs 20 394 8i 058 40588 64117 81176 131764
Generator capability at 0.85 power factor ant
30 psig hydrogen pressure, kva 1
*A 10 percent pressure drop is assumed between the high pressure turbine exhaust and low pressure turbine inlet for the reheat machine.
**Them nre two different units; the first for regenerative cycle operation, and the second B machine for reheat cycle operation.
Chapter 1 General Considerations sf Transmission

Fig. 3-The first central-station turbo-alternator installation


in the United States-a 2000-kw turbine coupled to a 60-cycle
generator, 2000 kw, 2400 volts, two-phase, 1200 rpm-at the
Hartford Electric Light Company, Hartford, Connecticut,
1900. This turbine was about four times as large as any one
built before that time and caused much comment the world
over.

watts of installed capacity being made up of approximately


35 million kilowatts of steam turbines and one million
kilowatts of diesel engines. .1pprosimately 16 million kilo-
watts of the installed capacity are in hydro-electric stations.
Of the 282 billion kilowatt-hours generated by all means
in 1948, roughly 200 billion came from fuel; 76 percent
from coal, 14 percent from natural gas, and 10 percent
from oil.
2. Development of Steam Power
The modern steam-electric station can be dated from the
installation by the Hartford Electric Company in 1900 of
a 2000-kw unit (Fig. 3) which at that time was a large
machine. Progress in design and efficiency from then on
has been continuous and rapid. In 1925 the public utilities
consumed in their fuel-burning plants an average of 2
pounds of coal (or coal equivalent) per kilowatt-hour, AGE OF CAST STEEL--+L~;EoO&i~
whereas today the corresponding figure is 1.3 pounds per AGE OF
kilowatt-hour. This average figure has not changed mate- SUPER ALLOYS

rially in the last 10 years. It would appear that the coal Fig. 4-Progress in turbine generator design.
consumption curve is approaching an asymptote and that
a much better overall performance is not to be expected, average from 675 to 910 degrees. Generator losses in the
even though the best base-load stations generate power meantime have been greatly reduced from about 6 percent
for less than one pound of coal per kilowatt-hour. The in 1900 to 2 percent today, but these losses never did form
very high efficiency in the best base-load stations is a large part of the total, and their influence on the overall
obtained at a considerable increase in investment. It can- performance of the station has been minor.
not be economically carried over to the system as a whole The increase in maximum size of 60-cycle, two-and four-
for the reason that there must be some idle or partly idle pole generating units over the years since 1900 is shown in
capacity on the system to allow for peaks (seasonal and Fig. 4. The remarkable increase has been due to improved
daily), cleaning, adjustments, overhaul, and repairs. How materials and designs, particularly in large forgings, tur-
much one can afford to spend for the improvement of sta- bine blading, and generator ventilation.
tion efficiency above “normal” depends on the shape of In 1945 the American Society of Mechanical Engineers
the system load curve, the role of the station in that curve, and the American Institute of Electrical Engineers adopted
and the cost of fuel. standard ratings for turbine-generator units. These were
Most of the credit for the improvement in steam con- revised in November 1950 to include the 90 000 kw unit
sumption goes to the boiler and turbine manufacturers and are listed in Table 1. The machines are designed to
who through continuous betterment of designs and ma- meet their rating with 0.5 psi hydrogen pressure, but ex-
terials have been able to raise steam pressures and tempera- perience has shown that between 0.5 and 15 psi the output
tures. Between 1925 and 1942 the maximum throttle pres- of the generator can be increased one percent for each
sure was raised from 1000 psi to 2400 psi and the average pound increase in the gas pressure without exceeding the
from 350 to 1000 psi. In the same period the throttle tem- temperature rise guarantee at atmospheric pressure. In
perature was raised from 725 to 1000 degrees F. and the many locations operation at more than 15 psi gas pressure
4 General Considerations of Transmission Chapter 1

may be difficult because of codes regulating operation of is preferred, in which a single combination guide and
“unfired pressure vessels” at greater pressures, but serious thrust bearing is located below the rotor (Fig. 1, Chapter
consideration is being given to operation at 30 lhs. 6). Where the axial length of the machines is too great
For a hydrogen-air mixture to be explosive, the per- an additional guide bearing must be provided. In this
centage of hydrogen must lie between 5 and 75 percent. case the combination thrust and guide bearing is usually
The control equipment is designed to operate an alarm if located above the rotor and the additional guide bearing
the purity of the hydrogen drops below 95 percent. The below the rotor.
density meter and alarm system is in principle a small The advantages of the umbrella design are (a) reduction
constant-speed fan circulating a sample of the mixture. in overhead room to assemble and dismantle the unit
If the density varies, the drop of pressure across the fan during erection and overhaul, and (b) simplicity of the
varies and registers on the meter. single bearing from the standpoint of cooling and mini-
3. Development of Water Power
The great transmission systems of this country received
their impetus as a result of hydro-electric developments.
Forty years ago conditions favored such developments,
and in the early years of this century water-power plants
costing $150 per kilowatt or less were common. Steam
stations were relatively high in first cost and coal consump-
tion per kilowatt hour was three times as much as to-
day, and finally fuel oil was not readily available. As
undeveloped water-power sites became economically less
desirable, steam stations less costly and their efficiency
higher, and as oil fuel and natural gas became more gen-
erally available through pipe lines, steam stations rapidly
outgrew hydro-electric stations in number and capacity.
Today very few water-power sites can be developed at
such low cost as to be competitive with steam stations in
economic energy production. For this reason hydro-
electric developments of recent years have almost all
been undertaken by Government agencies, which are in a
position to include in the projects other considerations,
such as, navigation, flood control, irrigation, conserva-
tion of resources, giving them great social value.
As the water-power developments within easy reach of
the load centers were utilized and it became necessary to
reach to greater distances for water power, only large
developments could be considered, and stations of less
than 100 000 kw became the exception rather than the
rule, as witness Conowingo with 252 000 kw, Diablo with
YEAR
135 000 kw, Fifteen Mile Falls with 140 000 kw, Osage
with 200 000 kw, and many others. The developments Fig. J-Trend in maximum waterwheel generator ratings.
of recent years undertaken by various government agen-
cies have reached gigantic proportions, as for example mum amount of piping. The design also lends itself
Hoover Dam with 1000 000 and Grand Coulee with readily to a totally-enclosed recirculating system of
2 000 000 kw installed capacity. ventilation, which keeps dirt out of the machine and facili-
A natural corollary to the increase in station capacity tates the use of fire-extinguishing equipment. It also re-
has been a gradual increase in the size of the individual duces heat and noise in the power house.
generator units, the growth of which is shown in Fig. 5,
culminating in the Grand Coulee generators of 120 000 4. Combination of Water and Steam Power
kw at 120 rpm with an overall diameter of 45 feet. There are very few locations today where an important
Most of the multi-purpose hydraulic developments call market can be supplied entirely from water power be-
for large, slow-speed machines. For such conditions verti- cause of seasonal variations in river flow, but in most
cal units are used to obtain maximum energy from the cases a saving will be realized from combining water
water passing through the turbine. The rotating parts power and steam. The saving results from the combina-
are supported by a thrust bearing which is an integral tion of low’ operating cost of water-power plants with low
part of the generator. investment cost of steam stations. Moreover, hydro-
TWO general types of generator design are used as dis- electric units in themselves have certain valuable ad-
tinguished by the arrangement of the guide and thrust vantages when used in combination with steam units.
bearings. Where the axial length of the generator is They start more quickly than steam-driven units, pro-
short in relation to its diameter, the “umbrella” design viding a high degree of standby readiness in emergency.
Chapter 1 General Considerations of Transmission 5

They are well adapted to maintenance of frequency, and mission). The latter group in this particular study n-as
also to providing wattless energy at times of low water about $70 per kilowatt.
flow. And finally, hydro-pondage can be drawn upon to Curve A gives the total cost, of energy per kilowatt,
relieve steam plants of short-time peaks to save banking hour for a modern steam plant costing $95 per kilo\vatjt
estra boilers. with fixed charges at 12 percent and coal at 8-l a ton.
To what extent a water-power site can be developed Curve B gives the total cost of energy from the wnter-
economically involves a thorough investigation of indi- power plant having the capital cost indicated in Curve C.
vidual cases. An economic balance must be struck be- To obtain such a curve it is necessary to determine the
tween the steam and water power to give maximum amount of energy available at the various capacity fac-
economy. One might install enough generating capacity tors, the assumption being made that all hydro capacity
to take care of the maximum flow of the river during a installed is firm capacityi, that is, that the system load
short period. The cost per kilowatt installed would be can absorb all of the energy generated.
low but the use made of the equipment (capacity factor) Curve B shows the typically high cost of hydro-electric
would also be low. Or one might put in only enough gen- energy as compared with steam at high capacity factors
erating capacity to use the minimum river flow. In this and its low cost at low capacity factors.
case the cost of the development per kilowatt installed
would be high, but the capacity factor would be high 5. Transmission Liability
In a hydro-electric development the transmission be-
comes a large factor of expense and in comparing such
developments with equivalent steam plants, it is necessary
to include the transmission as a charge against the hydro-
electric plant. Figures of cost published on the Hoover
Dam-Los Angeles 287-kv line indicate that this trans-
mission costs over $90 a kilowatt, and other lines con-
templated will probably show higher costs.
Under certain conditions it may be more costly to trans-
mit electrical energy over wires than to transport the
equivalent fuel to the steam station. It has been shown3
that the cost of electric transmission for optimum load
and voltages can be expressed as a linear function of
power and distance, as follows:
0.61 X miles
For 5Oyc load factor: mills/kw-hr = 0.54+
100
0.35 X miles
For 90% load factor: mills/kw-hr =0.30+
100
It was also shown that fuel transportation can be ex-
pressed as a linear function of energy and distance, thus:
IO 20 30 40 50 60 70 80 SO 100 Railroad rates on coal
CAPACITY FACTOR-PERCENT $1.20+5+ mills per mile
Pipe-line rates on crude oil
Fig. 6-Cost of energy at various capacity factors of steam
and hydro-electric plants. $5.00+4 cents per mile per 100 barrels
For pipe-line rates on natural gas two curves were
given for estimated minimum and maximum inter-
also. Obviously between these two extremes lies an
ruptible contract rates
optimum value. The ratio of installed water-power ca-
$0 +12 cents per mile per million cubic feet
pacity to the peak load of the system that gives the mini-
$50+12 cents per mile per million cubic feet
mum annual cost of power supply has been referred to
as the “economic hydro ratio,” and it can be deter- The authors point out that a comparison between trans-
mined without great difficulty for any particular set of con- mission costs alone for gas, oil, and coal are likely to be
ditions. misleading because there is a wide difference in the costs
In a paper2 presented before the American Society of of the fuels at their source. There is also a considerable
Mechanical Engineers, Irwin and Justin discussed in an variation in the transportation costs above and below the
interesting and graphical manner the importance of average.
incremental costs on the economics of any proposed de-
t“Firm Capacity” or “Firm Power” in the case of an individual
velopment. Fig. 6, taken from their paper, shows in station is the capacity intended to be always available even under
Curve C the capital cost per kilowatt of installation for emergency conditions. “Hydro Firm Capacity” in the case of com-
various capacity factors. The costs were segregated in bined steam and hydro is the part of the installed capacity that is
items that would be the same regardless of installation capable of doing the same work on that part of the load curve to
(land, water rights, dams) and those that vary with the which it is assigned as could be performend by an alternative steam
amount of installation (power house, machinery, trans- plant.
6 General Considerations of Transmission Chapter 1

The equivalence between the fuels is given as: Long-distance direct-current transmission has also been
1 tonof coal . . . . . .._........ 25000000BTU considered. It offers advantages that look attractive, but
I barre1ofoi1...___..._,.......... G250000BTU present limitations in conversion and inversion equipment
1OOOcubicfeetofgas . . . . . . . . . . . . . . . 1OOOOOOBTU make the prospect of any application in the near future
unlikely.
6. Purpose of Transmission In many industrial applications, particularly in the
Transmission lines are essential for three purposes. machine-tool industry, 60 cycles does not permit a high
a. To transmit power from a mater-power site to a market. enough speed, and frequencies up to 2000 cycles may be
These may be very long and justified becauseof the sub- necessary. Steps are being taken to standardize frequen-
sidy aspect connected with the project. cies of more than 60 cycles.
b. For bulk supply of power to load centers from outlying
steam stations. These are likely to be relatively short. 8. Choice of Voltage
c. For interconnection purposes, that is, for transfer of Transmission of alternating-current power over several
energy from one system to another in case of emergency or miles dates from 1886 when a line was built at Cerchi,
in response to diversity in system peaks. Italy, to transmit 150 hp 17 miles at 2000 volts. The
Frequent attempts have been made to set up defini- voltage has progressively increased, as shown in Fig. 7,
tions of ‘Yransmission lines, ” “distribution circuits” and until in 1936 the Hoover Dam-Los Angeles line was put
“substations.” None has proved entirely satisfactory or in service at 287 kv. This is still the highest operating
universally applicable, but for the purposes of accounting voltage in use in the United States today, but considern-
the Federal Power Commission and various state com- tion is being given to higher values. An investigation was
missions have set up definitions that in essence read: begun in 1948 at the Tidd Station of the Ohio PO\\-er
Company on an experimental line with voltages up to
A transmission system includes all land, conversion structures
and equipment at a primary source of supply; lines, switching 500 kv.
and conversion stations between a generating or receiving point The cost of transformers, switches, and circuit breakers
sntl the entrance to a distribution center or wholesale point, all increases rapidly with increasing voltage in the upper
lines and equipment whose primary purpose is to augment, inte- ranges of transmission voltages. In any investigation in-
grate or tie together sourcesof power supply. volving voltages above 230 000 volts, therefore, t,he unit
cost of power transmitted is subject to the law of diminish-
7. Choice of Frequency ing returns. Furthermore, the increase of the reactance
The standard frequency in Xorth America is 60 cycles of the terminal transformers also tends to counteract the
per second. In most foreign countries it is 50 cycles. As gain obtained in the transmission line from the higher
a general-purpose distribution frequency 60 cycles has an voltage. There is, therefore, some value of voltage in the
economic advantage over 50 cycles in that it permits a range being investigated beyond which, under esisting cir-
maximum speed of 3600 rpm as against 3000 rpm. Where cumstances, it is uneconomical to go and it may be more
a large number of distribution transformers are used a profitable to give consideration to line compensation by
considerable economic gain is obtained in that the saving means of capacitors to increase the economic limit of
in materials of 60-cycle transformers over 50-cycle trans-
formers may amount to 10 to 15 percent. This is because
in a transformer the induced voltage is proportional to the
total flux-linkage and the frequency. The higher the
frequency, therefore, the smaller the cross-sectional area
of the core, and the smaller the core the shorter the length
of the coils. There is a saving, therefore, in both iron and
copper.
The only condition under which any frequency other
than 50 to 60 cycles might be considered for a new project
\vould be the case of a long transmission of, say, 500 OI
600 miles. Such long transmission has been discussed in
connection with remote hydro-electric developments at
home and abroad, and for these a frequency less than 60
cycles might be interesting because as the frequency is
decreased the inductive reactance of the line, 2rfL, de-
1
creases and the capacitive reactance, - increases,
27r$’
resulting in higher load limits, transmission efficiency, and
better regulation.
Full advantage of low frequency can be realized, how-
ever, only where the utilization is at low frequency. If the
low transmission frequency must be converted to 60
cycles for utilization, most of the advantage is lost because YEAR
of limitations of terminal conversion equipment. Fig. 7-Trend in transmission voltages in 60 years.
Chapter 1 General Considerations of Transmission 7

TABLE ~-FORM OF TABULATIONFOR DETERMININGVOLTAGESAND CONDUCTORSIZES


Based on the Transmission of 10 000 Kva for 10 Miles at 80 Percent Power Factor Lagging, GO-Cycle, 3-Phnsc
VOLT.kGE ANNU.~l.
COSDCCTORS DROP AT OPERr\TING COST
FULI, TOAD
.
Total I=R Loss

10 000 2 300
Iiva I Kva /,

-.
7 40.5 .; 1 2.5 1 RIO001 4, Ill= 11.0 t-L-l 100 $09 600 I 0 ,500 $1 600 $1 ZOO $120 300 $7 580 $12 A30 sin 100 S31i 310
‘) 720 0.0 45 2 8RO 001 7 2 I.? 4 14.0 24600 60600 0 500 1 600 1 non 106 800 6 410 10 680 28 fin0 45 R!W
, I l-10 I 14.3 I 71 /4520001 11.5 I4 n 17.;1 15500 69600 0500 1000 1.500 !)7 700 5 8Fo 9 7iO 4.5 200, GO 8:iO
-- .-- ____ -~~ ------
ii 4.0 6.41 7.0 19.500 71600 9700 2400 2200 IE;;; fi 330 IO ,540 ifi 100 32 970
Li 8.1 68105 9 700 7 I 600 8 700 2 400 2 200 .r $5740 !I .xjo 32 200 4i .Tan
12.9 7 0 14.S 0000 ilOO 9700 2 400 a 200 91 900 5 520 !I 190 5 1 200 Ii3 !1 IO
-- ______ ~~~~--
4.5 3 8 5.R 0700 74400 10000 3400 3000 101 400 Ii I)!)0 10 140 18 000 :%A230
!I 1 4.0 !I.7 4 son 74 400 10900 3400 3 000 ‘Jfi 300 5 700 !I GO 30 100 31 .%I)

TABLE ~-@JICK-~~TI!~ATIN~ DATA ON THE LOAD CARRYING


CAPACITY OF TRANSMISSION LINEst
power transmission than increase the voltage much above
- present practice.
Kw Which Can Be Delivered Based The basic principles underlying system operation as
on SO;0Regulation and 90°j0 regards voltages have been set forth in a report” \vhich
Dclivcrcd I,inc Voltage Power Factor lists the voltages in common use, the recommended limits
-
of voltage spread, and the equipment voltage ratings in-
Distance in ;lMes
tended to fulfill the voltage requirements of the level
13.2 kv-3-foot spacing
I- 5 10 1d
T
20 for which the equipment is designed. The report shoultl be
Stranded Copper carefully studied before any plans are made involving the
4 950 490 330 245 adoption of or change in a system voltage.
2 1 -loo TOO 470 350 In selecting the transmission voltage, consideration
4/o 3 000 1 500 1 000 750 should be given to the present and probable future voltage
of other lines in the vicinity. The advantages of being
10 20 30 40
33 kv---l-foot spacing able to tie together adjoining power districts at a common
Stranded Copper voltage frequently outweighs a choice of voltage based on
1 ?5000 2 500 1 TOO 1 250 lowest immediate cost.
2/o 6 700 3 350 2 200 1 TOO If the contemplated transmission is remote from any
d/O 8 350 4 180 2 800 2 100 existing system, the choice of voltage should result from a
300 000 11500 5 750 3 800 2 900
- complete study of all factors involved. Attempts have
66 kv-&foot spacing 40 60 80 been made to determine by mathematical expression,
~~
Stranded Copper
-I
based on the well-known Kelvin’s Law, the most economi-
2/o 6 250 4 180 3 140
cal transmission voltage with all factors evaluated, but
4/O 8 000 5 320 3 990 these are so numerous that such an expression becomes
300 000 9 150 6 120 4 590 complicated, difficult, and unsatisfactory. The only satis-
- factory way to determine the voltage is to make a complete
KIT Which Can Be Delivered Based study of the initial and operating costs corresponding to
on 107, Loss and Equal Voltage at various assumed transmission voltages and to various sizes
Sending and Receiving Ends of conductors.
Distance in Miles For the purposes of the complete study, it is usually
unnecessary to choose more than three voltages, because
40 1 80 120 160 a fairly good guess as to the probable one is possible with-
132 kv--16-foot spacing
Stranded Copper out knowing more than the length of the circuit. For
4/O 30 100 this preliminary guess, the quick-estimating Table 3 is
300 000 44 800 useful. This table assumes that the magnitude of pon-el
500 000 77 100 transmitted in the case of voltages 13.2, 33, and 66 kv is
320
based on a regulation of 5 percent and a load power factor
220 kv--2-bfoot spacing uf 90 percent,. In the case of 132 and 220 kv, the table is
Hollow Copper based on a loss of 10 percent and equal voltages at, the send-
500 000 119 000 ing and receiving ends of the line. The reason for this and
ACSR-X5 000 118 500
L the bases of the calculations are given in Chapter 9.
tData obtained from Figs. 19 and 22 of Chap. 9. A representative study is given in Table 2. It is assumed
8 General Considerations of Transmission Chapter 1

that it is desired to transmit over a single-circuit ten miles loss, leakage over insulators and the escape of energy
long 8000 kw (10 000 kva) at 80 percent power-factor lag- through the air between the conductors (known as
ging for 10 hours a day followed by 2000 kw (2500 kva) “corona’‘-see Chap. 3) appear. In addition to these
at 80 percent power-factor for 14 hours. The preliminary two losses, the charging current, which increases as the
guess indicates that 23, 34.5, or 46 kv are probably the transmission voltage goes higher, may either increase or
economical nominal voltages. Equivalent conductor decrease the current in the circuit depending upon the
spacing and the number of insulators are as given in power-factor of the load current and the relative amount
Table 4. Conductors of hard-drawn stranded copper are of the leading and lagging components of the current in
the circuit. Any change in the current of the circuit will
TABLE 4 -CONSTRUCTION FEATURES OF TRANSMISSION consequently be accompanied by a corresponding change
LINES IN THE UNITED STATES*
in the 12R loss. In fact, these sources of additional losses
Line Equivalent Sumber of may, in some cases of long circuits or extensive systems,
Length in Milts
Voltage 9L pacing Insulators materially contribute toward limiting the transmission
Max. Type** Av. Av. voltage. The weight of copper conductors, from which
their cost can be calculated, is given in Chap. 3. As an
13.8
insurance against breakdown, important lines frequently
34.5
60 35 25 100 8 are built with circuits in duplicate. In such cases the cost
115 40 25 100 F 11 of conductors for two circuits should not be overlooked.
138 40 25 140 10 8 12
230 133 4.5 260 15 1-l 20
10. Choice of Spacing
Conductor spacing depends upon the economic con-
employed, the resistance being taken at 25 degrees C. sideration given to performance against lightning surges.
The step-up and step-down transformers are assumed as If maximum reliability is sought, the spacing loses its
2.5x 10 000 kva,l2 500 kva at either end, and high-voltage relation to the operating voltage and then a medium
circuit-breakers are used in anticipation of future addi- voltage line assumes most of the cost of a high-voltage
tional circuits. transmission without the corresponding economy. (See
The costs of the pole line, right-of-way, building, and Chap. 17) In general a compromise is adopted whereby
real estate are not included as they will be practically the the spacing is based on the dynamic voltage conditions
same for the range of voltages studied. with some allowance for reasonable performance against
Assuming that the cost figures in the table are correct, a lightning surges.
34 500-volt line with No. 00 copper conductor is the most Table 4 shows typical features of transmission lines in
economical. The transmission loss will be 5 percent and the United States including their “equivalent spacing”
the regulation 7 percent at full load, which is deemed and the number of suspension insulators used. By equiva-
satisfactory. The voltage is sufficiently high for use as a lent spacing is understood the spacing that would give
subtransmission voltage if and when the territory de- the same reactance and capacitance as if an equilateral
velops and additional load is created. The likelihood of triangular arrangement of conductors had been used. It
early growth of a load district is an important factor in is usually impractical to use an equilateral triangular ar-
selection of the higher voltage and larger conductor where rangement for design reasons. The equivalent spacing
the annual operating costs do not vary too widely. is obtained from the formula D= +ABC where A, B,
and C are the actual distances between conductors.
9. Choice of Conductors
The preliminary choice of the conductor size can also 11. Choice of Supply Circuits
be limited to two or three, although the method of selecting The choice of the electrical layout of the proposed
will differ with the length of transmission and the choice power station is based on the conditions prevailing locally.
of voltage. In the lower voltages up to, say, 30 kv, ‘for It should take into consideration the character of the
a given percentage energy loss in transmission, the cross load and the necessity for maintaining continuity of
section and consequently the weight of the conductors service. It should be as simple in arrangement as prac-
required to transmit a given block of power varies in- ticable to secure the desired flexibility in operation and
versely as the square of the voltage. Thus, if the voltage to provide the proper facilities for inspection of the
is doubled, the weight of the conductors will be reduced apparatus.
to one-fourth with approximately a corresponding reduc- A review of existing installations shows that the appar-
tion in their cost. This saving in conducting material ent combinations are innumerable, but an analysis indi-
for a given energy loss in transmission becomes less cates that in general they are combinations of a limited
as the higher voltages are reached, becoming increas- number of fundamental schemes. The arrangements
ingly less as voltages go higher. This is for the reason vary from the simplest single-circuit layout to the in-
that for the higher voltages at least two other sources of volved duplicate systems installed for metropolitan serv-
*This table is based on information published in Electrical World ice where the importance of maintaining continuity of
and in Electrical Engineering. While it does not include all lines, it service justifies a high capital expenditure.
is probably representative of general practice in the U.S.A. The scheme selected for stations distributing power at
**SC-W -Single-circuit wood. bus voltage differs radically from the layout that would
SC-ST-Single-circuit steel. be desirable for a station designed for bulk transmission.
Chapter 1 General Considerations of Transmission 9

In some metropolitan developments supplying under- large that it is necessary to use current-limiting reactors
ground cable systems segregated-phase layouts have in series with the generator leads or in series with each
been and are still employed to secure the maximum of feeder. Sometimes both are required. Sketch (e) shows a
reliability in operation. However, their use seems to be double bus commonly used where reactors are in series
on the decline, as the improvement in performance over with each generator and each feeder. Bus-tie reactors
the conventional adjacent phase grouping is not suffi- are also shown that, with all generators in service, keep
ciently better to justify the estra cost, particularly in the short-circuit currents within the interrupting ability
view of the continuing improvement of protective equip- of the breakers. These bus-tie reactors are important
ment and the more reliable schemes of relaying available
today for removing faulty equipment, buses, or circuits.
Several fundamental schemes for bus layouts supplying
feeders at generator voltage are shown in Fig. 8. These
vary from the simplest form of supply for a small indus-
trial plant as shown in (a) to a reliable type of layout for
central-station supply to important load areas shown in
(4 and (0 t.
Sketch (a) shows several feeders connected to a com-
mon bus fed by only one generator. This type of con-
struction should be used only where interruptions to
service are relatively unimportant because outages must
exist to all feeders simultaneously when the bus, genera- I t
tor breaker, generator or power source is out of service (b) (cl (4
for any reason. Each feeder has a circuit breaker and a
disconnect switch. The circuit breaker provides protec-
tion against short circuits on the feeder and enables the
Q Q
MAIN BUS
feeder to be removed from service n-hile it is carrying
\
load if necessary. The disconnect switch serves as addi-
tional backup protection for personnel, with the breaker
open, during maintenance or repair work on the feeder.
The disconnect also enables the breaker to be isolated
from the bus for inspection and maintenance on the
breaker. Quite frequently disconnect switches are ar-
ranged so that when opened the blade can be connected
to a grounded clip for protection. If the bus is supplied
by more than one generator, the reliability of supply to
the feeders using this type of layout is considerably in-
creased.
With more than one generator complete flexibility is -2 A
obtained by using duplicate bus and switching equip-
ment as shown in (b). It is often questionable whether
the expense of such an arrangement is justified and it
should be used only where the importance of the service
warrants it. One breaker from each generator or feeder
can be removed from service for maintenance with com- (4
plete protection for maintenance personnel and without SYNCHRONIZING BUS
disrupting service to any feeder. Also, one complete bus
section can be removed from service for cleaning and main-
tenance or for adding an additional feeder without inter-
fering with the normal supply to other feeder circuits.
There are many intermediate schemes that can be utilized
that give a lesser degree of flexibility, an example of
which is shown in (c). There are also several connec-
tions differing in degree of duplication that are inter-
mediate to the three layouts indicated, as for instance in
(21). An analysis of the connections in any station layout
usually shows that they are built up from parts of the
fundamental schemes depending upon the flexibility and
reliability required.
The generating capacity connected to a bus may be so
tNELA Publications Nos. 164 and 278’20-Elec. App. Comm. Fig. g--Fundamental schemes of connections for supply at
give a number of station and substation layouts. generator voltage.
10 General Considerations of Transmission Chapter 1

because they not only limit the current on short circuit caused considerable trouble by electrocuting themselves
but also serve as a source of supply to the feeders on a in accessible bus structures.
bus section if the generator on that bus section fails. With stations supplying transmission systems the
Each feeder can be connected to either the main or auxil- scheme of connections depends largely on the relative
iary bus through what is called a selector breaker. A capacities of the individual generators, transformers and
selector breaker is similar in every respect to the feeder transmission circuits; and whether all the generatetl
breaker and serves as backup protection in case the feeder power is supplied in bulk over transmission lines or
breaker does not function properly when it should open whether some must also be supplied at generator voltage.
on a feeder fault. The bus-tie breakers can be used when The simplest layout is obtained when each generator,
one or more generators are out of service to prevent volt- transformer and transmission circuit is of the same ca-
age and phase-angle differences between bus sections pacity and can be treated as a single entity. Unfortu-
that would exist with the supply to a bus section through nately, this is seldom the case because the number of
a reactor. The phase angle between bus sections becomes generators do not equal the number of outgoing circuits.
important when a station is supplying a network system Even here, however, some simplification is possible if the
and should be kept to a minimum to prevent circulating transformers are selected of the same capacity as the
currents through the network. For a network supply at generators, so that the combination becomes the equiva-
least four bus sections are generally used so that the net- lent of a high-voltage generator with all the switching on
work can still be supplied in case one bus section should the high-voltage side of the transformer.
trip out on a fault. Sketch (e) shows only three bus sec- In Fig. 9, (a) shows the “unit scheme” of supply. The
tions, the main and auxiliary buses serve as one bus for power system must be such that a whole unit comprising
the feeders connected to that section. generator, transformer and transmission line can be
Sketch (f) shows a more modern design for central dropped without loss of customer’s load. The station
stations with the feeder reactors next to the bus struc- auxiliaries that go with each unit are usually supplied
ture, in contrast with (e) where the reactors are on the
feeder side of the breaker. This arrangement is possible
because of the proven reliability of reactors, circuit break-
ers, and dust-tight metalclad bus structures. Con-
tinuous supply to all feeders is provided through reactor
ties to a synchronizing bus should a generator fail. Bus-
tie circuit breakers are provided to tie solidly adjacent
bus sections for operation with one or more generators
out of service. Stations of this type would be expected
to have four to six or more bus sections especially if the
station supplies netnork loads. The synchronizing bus (0)
also serves as a point n-here tie feeders from other sta-
tions can be connected and be available for symmetrical
power supply to all feeder buses through the reactors. t
This is not the case for station design shown in (e) where (b)
a tie feeder must be brought in to a particular bus section.
For any type of generating-station design proper cur-
rent and potential transformers must be provided to sup-
ply the various types of relays to protect all electrical
parts of the station against any type of fault. Likewise,
current and voltage conditions must be obtained from’
current and potential transformers through the proper
metering equipment to enable the operating forces to put
into service or remove any equipment without impairing
the operation of the remainder of the station. A ground
bus must be provided for grounding each feeder when it
is out of service for safety to personnel. Also a high-
potential test bus is necessary to test circuit breakers,
bus work and feeders, following an outage for repairs or
maintenance, before being reconnected to the station.
Fire walls are generally provided between bus sections
or between each group of two bus sections to provide Lu
against the possibility of a fire in one section spreading to
the adjacent sections. The separate compartments within
the station should be locked and made as tight as possible
for protection against accidental contact by operating (4
personnel either physically or through the medium of a Fig. 9-Fundamental schemes of supply at higher than gener-
wire or any conducting material. Stray animals have ated voltage.
Chapter 1 General Consideration,s of Transmission

through a station transformer connected directly to the


generator terminals, an independent supply being pro-
vided for the initial start-up and for subsequent emer-
gency restarts.
Sketch (b) shows the case where conditions do not per-
mit of the transformers being associated directly with the
generators because, perhaps, of outgoing feeders at gen-
crater voltage, but where the capacity of the transmission
lines is such as to give an economical transformer size.
Here it may be desirable to include the transformer bank
as an integral part of the line and perform all switching
operations on the low-voltage side. Sketch (b) shows the
extreme of simplicity, which is permissible only where
feeders and lines can be taken in and out of service at
will, and (c) shows the other extreme where the feeders
and lines are expected to be in service continuously.
Sketch (d) shows an arrangement which is frequently ap-
plicable and which provides a considerable flexibility
Jvith the fewest breakers.
Figs. 8 and 9 include fundamental layouts from which
almost any combination can be made to meet local condi-
tions. The choice depends on the requirements of service
continuity, the importance of which depends on two fac-
tors, the multiplicity of sources of supply, and the type
of load. Some industrial loads are of such a nature that
the relatively small risk of an outage does not justify
duplication of buses and switching.
The same argument applies to the transmission line
itself. Figure 10 shows an assumed transmission of 100
miles with two intermediate stations at 33 miles from
either end. Sketch (a) is a fully-sectionalized scheme
giving the ultimate in flexibility and reliability. Any sec-
tion of either transmission circuit can be taken out for
maintenance without the loss of generating capacity.
Furthermore, except within that part of the transmission
where one section is temporarily out of service, a fault on
any section of circuit may also be cleared without loss of
load. Sketch (b) shows the looped-in method of connec- (a) (b)
tion. Fewer breakers are required than for the fully Fig. lo--Fundamental schemes of transmission. (a) Fully-
sectionalized scheme, and as in (a) any section of the sectionalized supply. (b) Looped-in supply. (c) Bussed supply.
circuit can be removed from service without reducini
power output. If, however, a second line trips out, part putting in an elaborate switching and relaying scheme.
or all of the generating capacity may be lost. Relaying Only a few fundamental ideas have been presented on
is somewhat more difficult than with (a), but not unduly the possible layout of station buses and the switching
so. Flexibility on the low-voltage side is retained as in arrangements of transmission circuits. The possible com-
(a). Sketch (c) is in effect an extension of the buses from binations are almost infinite in number and will depend
station to station. The scheme is, of course, considerably on local conditions and the expenditure considered per-
cheaper than that in (a) and slightly less than that in missible for the conditions prevailing.
(b) but can be justified only where a temporary outage
of the transmission is unimportant. Relaying in (c) is REFERENCES
complicated by the fact that ties between buses tend to
equalize the currents so that several distinct relaying 1. Briefing the Record, edited by J. J. Jaklitsch, Mechanical Engineer-
steps are required to clear a fault. ing, February 1948, p. 147.
2. Economic Balance Between Steam and Hydro Capacity, Trans-
A proper balance must be kept between the reliability
actions A.S.M.E., Vol. 55, No. 3. Also Electrical War& August
of the switching scheme used and the design of the line 30, 1932.
itself. Most line outages originate from lightning and a 3. Economics of Long-Distance Energy Transmission, by R. E.
simplification and reduction in the cost of switching is Pierce and E. E. George, Ebasco Services, Inc., A.I.E.E. Transac-
permissible if the circuit is built lightning proof. (See lions, Vol. 67, 1945, pp. 1089-1094.
Chap. 13.) On the other hand, if a line is of poor construc- 4. EEI-NEMA Preferred Voltage Ratings for A-C Systems and
tion as regards insulation and spacing, it would not be Equipment, dated May 1949. EEI Publication No. R-6. NEMO
good engineering to attempt to compensate for this by Publication No. 117.
CHAPTER 2

SYMMETRICAL COMPONENTS
Original Author: Revised by:
J. E. Hobson D. L. Whitehead

Stated in more general terms, an unbalanced group of n

T
HE analysis of a three-phase circuit in which phase
voltages and currents are balanced (of equal mag- associated vectors, all of the same type, can be resolved
nitude in the three phases and displaced 120” from into n sets of balanced vectors. The n vectors of each set
each other), and in which all circuit elements in each phase are of equal length and symmetrically located \Gth respect
are balanced and symmetrical, is relatively simple since to each other. A set of vectors is considered to be sym-
the treatment of a single-phase leads directly to the three- metrically located if the angles between the vectors, taken
phase solution. The analysis by Kirchoff’s laws is much in sequential order, are all equal. Thus three vectors of
more difficult, however, when the circuit is not sym- one set are symmetrically located if t.he angle between
metrical, as the result of unbalanced loads, unbalanced adjacent vectors is either zero or 120 degrees. Although
faults or short-circuits that are not symmetrical in the the method of symmetrical components is applicable to the
three phases. Symmetrical components is the method now analysis of any multi-phase system, this discussion will be
generally adopted for calculating such circuits. It was limited to a consideration of three-phase systems, since
presented to the engineering profession by Dr. Charles L. three phase systems are most frequently encountered.
Fortescue in his 1918 paper, “Method of Symmetrical Co- This method of analysis makes possible the prediction,
ordinates Applied to the Solution of Polyphase Networks.” readily and accurately, of the behavior of a power system
This paper, one of the longest ever presented before the during unbalanced short-circuit or unbalanced load con-
A.I.E.E., is now recognized as a classic in engineering liter- ditions. The engineer’s knowledge of such phenomena has
ature. For several years symmetrical components re- been greatly augmented and rapidly developed since its
mained the tool of the specialist; but the subsequent work introduction. Modern concepts of protective relaying and
of R. D. Evans, C. F. Wagner, J. F. Peters, and others in fault protection grew from an understanding of the sym-
developing the sequence netn-orks and extending the ap- metrical component methods.
plication to system fault calculations and stability calcula- Out of the concept of symmetrical components have
tions focused the attention of the industry on the simplifi- sprung, almost full-born, many electrical devices. The
cation and clarification symmetrical components offered in negative-sequence relay for the detection of system faults,
the calculation of power system performance under un- the positive-sequence filter for causing generator voltage
balanced conditions. regulators to respond to voltage changes in all three phases
The method was recognized immediately by a few engi- rather than in one phase alone, and the connection of in-
neers as being very useful for the analysis of unbalanced strument transformers to segregate zero-sequence quanti-
conditions on symmetrical machines. Its more general ties for the prompt detection of ground faults are interest-
application to the calculation of power system faults and ing examples. The HCB pilot wire relay, a recent addition
unbalances, and the simplification made possible by the to the list of devices originating in minds trained to think
use of symmetrical components in such calculations, was in terms of symmetrical components, uses a positive-
not appreciated until several years later when the papers sequence filter and a zero-sequence filter for the detection
by Evans, Wagner, and others were published. The use’ of faults within a protected line section and for initiating
of symmetrical components in the calculation of unbal- the high speed tripping of breakers to isolate the faulted
anced faults, unbalanced loads, and stability limits on section.
three-phase power systems now overshadows the other Symmetrical components as a tool in stability calcula-
applications. tions was recognized in 1924-1926, and has been used
The fundamental principle of symmetrical components, extensively since that time in power system stability
as applied to three-phase circuits, is that an unbalanced analyses. Its value for such calculations lies principally in
group of three related vectors (for example, three unsym- the fact that it permits an unbalanced load or fault to be
metrical and unbalanced vectors of voltage or current in represented by an impedance in shunt with the single-
a three-phase system) can be resolved into three sets of phase representation of the balanced system.
vectors. The three vectors of each set are of equal magni- The understanding of three-phase transformer perform-
tude and spaced either zero or 120 degrees apart. Each set ance; particularly the effect of connections and the phe-
is a “symmetrical component” of the original unbalanced nomena associated with three-phase core-form units has
vectors. The same concept of resolution can be applied to been clarified by symmetrical components, as have been
rotating vectors, such as voltages or currents, or non- the physical concepts and the mathematical analysis of
rotating vector operators such as impedances or admit- rotating machine performance under conditions of unbal-
tances. anced faults or unbalanced loading.
12
Chapter 2 Symmetrical Components 13

The extensive use of the network calculat,or for the a2= (~j1?O)(cj120)=~j240= -i j"",
determination of short-circuit, currents and voltages and (2)
for the application of circuit breakers, relays, grounding
transformers, protector tubes, etc. has been furthered by L4s shown in Fig. 1, the resultant of a2 operating on a
the development of symmetrical components, since each vector V is the vector Y” having the same length as I;,
sequence network may be set up independently as a single- but located 120 degrees in a clockwise direction from V.
phase system. A miniature network of an extensive power The three vectors l+jO, a2, and a (taken in this order)
system, set up with three-phase voltages, separate im- v:ov
pedances for each phase, and mutual impedances between
phases would indeed be so large and cumbersome to handle
as to be prohibitive. In this connnection it is of interest to
note that the network calculator has become an indispen-
sable tool in the analysis of power system performance and
in power syst,em design.
Sot only has the method been an exceedingly valuable
tool in system analyses, but also, by providing new and
simpler concepts the understanding of power system be-
havior has been clarified. The method of symmetrical
components is responsible for an entirely different manner
of approach to predicting and analyzing power-system
performance. Fig. l-Rotation of a vector by the operator 0.
Symmetrical components early earned a reputation of
being complex. This is unfortunate since the mathe- form a balanced, symmetrical, set of vectors of positive-
matical manipulations attendant with the method are phase-sequence rotation, since the vectors are of equal
quite simple, requiring only a knowledge of complex vector length, displaced equal angles from each other, and cross
notation. It stands somewhat unique among mathemat- the reference line in the order 1, a2, and a (following the
ical tools in that it has been used not only to explain exist- usual convention of counter-clockwise rotation for the
ing conditions, but also, as pointed out above, the physical
concepts arising from a knowledge of the basic principles TABLE ~-PROPERTIES OF THE VECTOROPERATOR“~"
have led to the development of new equipment and new l=l+joEe'O -: : r
schemes for power system operation, protection, etc.
Things men come to know lose their mystery, and so it is
with this important tool.
Inasmuch as the theory and applications of symmetrical
components are fully discussed elsewhere (see references)
the intention here is only to summarize the impor-
tant equations and to provide a convenient reference for
those who are already somewhat familiar with the sub-
ject.

I. THE VECTOR OPERATOR “a”


For convenience in notation and manipulation a vector
operator is introduced. Through usage it has come to be
known as the vector a and is defined as

(1)
This indicates that the vector a has unit length and is
oriented 120 degrees in a positive (counter-clockwise) -
direction from the reference axis. A vector operated upon
1+a2= ~,+j+~oo
by a is not changed in magnitude but is simply rotated in (~+a)(l+a2)=l+jO=@
(1-a) (l-a2)=3+jO=3d0
Position 120 degrees in the forward direction. For exam-
ple, V’=aV is a vector having the same length as the l+a -~+j.?!$~~i120
vector V, but rotated 120 degrees forward from the vector Ifa2=a= -
v. This relationship is shown in Fig. 1. The square of l-a
-= -a=~-j+=,i300
l--a*
the vector a is another unit vector oriented 120 degrees -

in a negative (clockwise) direction from the reference (l+a)Z=a= -$+jG2=$*0

axis, or oriented 240 degrees forward in a positive direc-


tion. (l+a2)Z=a2= -!-j~=,jP40
2 2
14 Sgmmetricul Components Chapter

vector diagram). The vectors 1, a, and a2 (taken in this


order) form a balanced, symmetrical, set of vectors of
negative-phase-sequence, since the vectors do not cross Eoo’Ebo’Eco’Eo
the reference line in the order named, keeping the same
Fig. 4-Zero-sequence components of the vectors in Fig.

El is the positive-sequence component of E,, written


as Eal. The positive-sequence component of Ek,, El,l, is
equal to a2E,,. The positive-sequence component of E,~,
Ecl, is equal to aE,l. EaI, Ebl, EC1form a balanced, sym-
metrical three-phase set of vectors of positive phase se-
quence since the vector E,l is 120 degrees ahead of EM
and 120 degrees behind E,l, as shown in Fig. 5.

E,,=aE,

t
Eb,‘a’E,
Fig. 2-Properties of the vector operator u.
Fig. 5-Positive-sequence components of the vectors in Fig. 3.
convention of counterclockwise rotation, but the third
named follows the first, etc. ES is the negative-sequence component of E,, lvritten
Fundamental properties of the vector a are given as Eaz. The negative-sequence components of Eb and E,
in Table 1, and are shown on the vector diagram of are, respectively, aE,:, and a2Ea2,so that Eav, Eb?, E,?
Fig. 2. taken in order form a symmetrical set of negative-sequence
vectors as in Fig. 6.
II. RESOLUTION AND COMBINATION OF All three of the zero-sequence-component vectors are
VECTOR COMPONENTS defined by E,, since Eao= EbO=Ed. Likewise, the three

1. Resolution of Unbalanced Three-Phase Voltages


Ebe’a%
A three-phase set of unbalanced voltagevectors is shown
in Fig. 3. Any three unbalanced vectors such as those in
Fig. 3 can be resolved into three balanced or symmetrical
sets of vectors by the use of the following equations:
El= w,+Eb+Ec) --3=,
El = 3 (E, + UEb+ UZE,) (3) EC2 =02Ep
Ez=+(E,+a2E,,+aE,) Fig. 6-Negative-sequence components of the vectors in Fig. 3.

positive-sequence vectors are defined by El, since Eal = El,


Ebl =a2E1, and Ecl=aEl. Similarly the three negative-
sequence vectors are defined by ES. Thus all nine com-
ponent vectors of the three original unbalanced vectors are
completely defined by E,, El, and E?; and it is understood
that EO,El, and E,, are the zero-, positive-, and negative-
sequence components of E, without writing Eaa,etc. The
three original unbalanced vectors possess six degrees of
freedom, since an angle and a magnitude are necessary to
Fig. 3-Unbalanced vectors.
define each vector. The nine component vectors also
possess six degrees of freedom, since each of the three sets
17, is the zero-sequence component of E,, and is like- of component vectors is described by one angle and one
wise the zero-sequence component of Eb and E,, so that magnitude; for example, the three positive-sequence
E,,= E, = E,,O= Ed. This set of three-phase vectors is vectors E,l, Ebl, and Ecl, are defined by the angular posi-
shown in Fig. 4. tion and magnitude of E,.
Chapter 2 Symmetrical Components 15

Note that all three sets of component vectors have the


same counterclockwise direction of rotation as was as-
sumed for the original unbalanced vectors. The negative-
sequence set of vectors cloes not rotate in a direction oppo-
site to the positive-sequence set; but the phase-sequence,
that is, the order in which the maximum occur with time,
of the negative-sequence set is a, c, b, a, and therefore
opposite to the a, b, c, a, phase-sequence of the positive-
sequence set.
The unbalanced vectors can be expressed as functions of
the three components just defined:
E,=E,,+E,,+E,,=E,+E,+E,
Eh=Et~+Ebl+Eb~=Eo+a*E~+aE~ (4)
Ec=Eti+EE,l+E,?= Eo+aEl+a2Ez
The combination of the sequence component vectors to
form the original unbalanced vectors is shown in Fig. 7.
In general a set of three unbalanced vectors such as
those in Fig. 3 will have zero-, positive-, and negative-

0.00 356

0.84 I
2@300 4
R I I I I I I I
0.8OL ’ I I
0.00 0.88 0.96 1.04 1.12 1.20

- Eb
%

Fig. 7-Combination of the three symmetrical component Fig. S-Determination of unbalance factor.
sets of vectors to obtain the original unbalanced vectors in
Fig. 3.
negative sequence voltage whereas the phase voltages are
of course more readily measured.
sequence components. Han-ever, if the vectors are bal-
anced and symmetrical-of equal length and displaced 120 2. Resolution of Unbalanced Three-Phase Currents
degrees from each other-there will be only a positive-
sequence component, or only a negative-sequence com- Three line currents can be resolved into three sets of
ponent, depending upon the order of phase sequence for symmetrical component vectors in a manner analogous
the original vectors. to that just given for the resolution of voltages.
Equations (3) can be used to resolve either line-to- Referring to Fig. 9:
neut’ral voltages or line-to-line voltages into their com-
ponents. Inherently, however, since three delta or line-
to-line voltages must form a closed triangle, there will be
no zero-sequence component for a set of three-phase line-
to-line voltages, and l&D=+ (Eab+Ebc+EcJ =O. The
subscript “D” is used to denote components of delta
voltages or currents flowing in delta windings.
In many cases it is desirable to know the ratio of the Ib
negatives- to positive-sequence amplitudes and the phase b -
angle between them. This ratio is commonly called the
unbalance factor and can be conveniently obtained from C
-AL
the chart given in Fig. 8. The angle, 0, by which En2
Fig. 9-Three-phase line currents.
leads Eal can be obtained also from the same chart. The
chart is applicable only to three-phase, three-wire systems,
since it presupposes no zero-sequence component. The The above are, respectively, the zero-, positive-, and
only data needed to use the chart is the scalar magnitudes negative-sequence components of I,, the current in the
of the three line voltages. As an example the chart can be reference phase.
used to determine the unbalance in phase voltages per-
missible on induction motors without excessive heating.
This limit has usually been expressed as a permissible
16 Symmetrical Components Chapter 2

Three delta currents, Fig. 10, can be resolved into com- I a-=I()+142
ponents : a
Ea9

(7) b
Eb9
Where 1, has been chosen as the reference phase current.

7iY!iL3
Fig. lo--Three-phase delta currents.
- EC
Three line currents flowing into a delta-connected load, ~=&+aI,ta21e zc
C- C’
or into a delta-connected transformer winding, cannot
have a zero-sequence component since 1,+1b+Z, must (b)
obviously be equal to zero. Likewise the currents flowing Fig. 11-Three unbalanced self impedances.
into a star-connected load cannot have a zero-sequence
component unless the neutral mire is returned or the neutral
point is connected to ground. Another way of stating this The sequence components of current through the im-
fact is that zero-sequence current cannot flow into a delta- pedances, and the sequence components of the line volt-
connected load or transformer bank; nor can zero-sequence ages impressed across them are interrelated by the fol-
current flow into a star-connected load or transformer bank lowing equations:
unless the neutral is grounded or connected to a return
E,=3(E,g+Ebg+EcY) =1oz,+112,+12z,
neutral wire.
El=~(E,,+aEb,+a*E,g) =I”z,+I,z,+I?z, (9)
The choice of which phase to use as reference is entirely
arbitrary, but once selected, this phase must be kept as the
E,=4(E,g+a2Et,+aE,,) =IoZ,+I,Z,+I~Z,
reference for voltages and currents throughout the system, The above equations illustrate the fundamental prin-
and throughout the analysis. It is customary in symmet- ciple that there is mutual coupling between sequences
rical component notation to denote the reference phase as when the circuit constants are not symmetrical. As the
(‘phase a”. The voltages and currents over an entire sys-. equations ,reve&l, both positive- and negative-sequence
tern are then expressed in terms of their components, all current (as well as zero-sequence current) create a zero-
referred to the components of the reference phase. The sequence voltage drop. If Z,=Zb =Z,, the impedances
components of voltage, current, impedance, or power are symmetrical, 2, = 2, =O, and Z,= 2,. For this con-
found by analysis are directly the components of the refer- dition,
ence phase, and the components of voltage, current, im- E,,= IoZO
pedance, or power for the other phases are easily found by El = 112, (10)
rotating the positive-or negative-sequence components of Ex = I,Z,
the reference-phase through the proper angle. The am-
biguity possible where star-delta transformations of volt- and, as expected, the sequences are independent. If the
age and current are involved, or where the components of neutral point is not grounded in Fig. 11(a), I,=0 but
star voltages and currents are to be related to delta volt- EO=IIZZ+12Z1 so that there is a zero-sequence voltage,
ages and currents, is detailed in a following section. representing a neutral voltage shift, created by positive-
and negative-sequence current flowing through the un-
3. Resolution of Unbalanced Impedances and Ad- balanced load.
mittances Equations (8) and (9) also hold for unsymmetrical
Self Impedances-Unbalanced impedances can be series line impedances, as shown in Fig. 11(b), where Eo,
resolved into symmetrical components, although the El, and Ez are components of E,, Eb, and E,, the voltage
impedances are vector operators, and not rotating vectors drops across the impedances in the three phases.
as are three-phase voltages and currents. Consider the Mutual Impedances between phases can also be re-
three star-impedances of Fig. 11(a), which form an unbal- solved into components. Consider .Zmbcof Fig. 12(a), as
anced load. Their sequence components are: reference, then
z,=g(&+zb+zc> Zmo= 4(2mb,+Zrm+Zmnb)
2, = &z*+aZb+a*Z,) (8) (11)
Z,=~(Zn+a*Zb+aZ,)
Chapter 2 Symmetrical Components 17

tive-sequence voltage drops, etc. Fortunately, except for


&symmetrical loads, unsymmetrical transformer con-
nections, etc., the three-phase systems usually encountered
are symmetrical (or balanced) and the sequences are in-
dependent.
Admittances can be resolved into symmetrical com-
ponents, and the components used to find the sequence
components of the currents through a three-phase set of
line impedances, or star-connected loads, as functions
of the symmetrical components of the voltage drops
across the impedances. In Fig. 11(a), let Ya=$, Yb=l
a Zb’
zmbc Ye=+, then
c
IC ZC
c’ e
J J Y,=+(Ya+Yb+Yc)
(b) Y,=$(Y,+aYb+u*YJ (1%
Fig. 12 Y,=+(Y,+a*Yb+aY,)
Cn) Three unbnlanceclmutual impedances. and
(t)) IJnbalnnced self and mutual impedances. I,= E,Y,+EIY,+EzY,
11=&Y,+E,Y,+EzY, UG)
Iz=EoYz+ElYl+EzYo
The components of the three-phase line currents and
the components of the three-phase voltage drops created Note, however, that Y, is not the reciprocal of Z,, as
I)y the mutual impedances will be interrelated by the defined in Eq. 8, Y, is not the reciprocal of Z,, and Y,
following equations: is not the reciprocal of Z,, unless Z,=Zb =Z,; in other
words, the components of admittance are not reciprocals
E,,= :(E,,~+Ebb’+Ecc’) =2IoZ,o-I1Z,,-I*Z,~
of the corresponding components of impedance unless
~l=~(E,,,+UE,~b,+u*Ecc’)= -I~z,,-I&o+21*2,* (12)
the three impedances (and admittances) under consid-
E, = +(E,,,+azEbg+aE,,,) = - IOZ,z+211Z,1 - I&T,,, eration are equal.
If, as in Fig. 12(b), both self and mutual impedances
are present in a section of a three-phase circuit, the sym- 4. Star-Delta Conversion Equations
metrical components of the three voltage drops across the If a delta arrangement of impedances, as in Fig. 13(a),
section are: is to be converted to an equivalent star shown in Fig.
13(b), the following equations are applicable.
Eo= W,,,+Ebb,+Ecc,)
=ro(z,+az,,)+I,(z,-z,,)+12(z,-z,,)
E, = ~(E,,~+aEbb*+a*E,,~)
=Io(z,-z,~)+I1(zo-~,,)+~*(~,+2~,*) (13)
Es= f(E,,,+a*E,,~,+aE,,,) . ~,--1_- zabxzbc (17)
yb Z,b+Zbc+Zcn
=lo(Z,-zZ,,)+I~(Z*+2~,*)+~2(~~-~,,)
z,- 1 _ zbcxzcca
Again, if both self and mutual impedances are sym- yc Z,b+Zb,+Z,,
metrical, in all three phases,
Eo= Io(Z,+‘2Z,,> =IoZ,
E, = II( 2, - Z,,) = II& (14)
E,=I,(Z,-Z,,)=I,Z,
Where Z,,, Z1, and Z2 are, respectively, the impedance
10 zero-, positive-, and negative-sequence. For this con-
dition positive-sequence currents produce only a positive-
sequence voltage drop, etc. Z,,, Z1, and 22 are commonly
referred to as the zero-sequence, positive-sequence, and zbc
negative-sequence impedances. Note, however, that this (a) (b)
is not strictly correct and that 21, the impedance to
Fig. 13-Star-delta impedance conversions.
positive-sequence currents, should not be confused with
21, the positive sequence component of self impedances.
Since Zo, Z1, and Z, are used more frequently than Z,,, When the delta impedances form a three-phase load,
L and Z2 the shorter expression “zero-sequence im- no zero-sequence current can flow from the line to the load;
pedance” is usually used to refer to Z. rather than 2. hence, the equivalent star load must be left with neutral
For a circuit that has only symmetrical impedances, both ungrounded.
self and mutual, the sequences are independent of each The reverse transformation, from the star impedances of
other, and positive-sequence currents produce only posi- Fig. 13(b), to the equivalent delta Fig. 13(a), is given by
18 Symmetrical Components Chapter 2

z,zb TABLE 2
Z,b = Z,,SZbf y-
0 Posit,ivc-SequenceLine-to-Line Voltage
(18) ReferencePhase As a Funct,ionof Positive Sequence
%,,,'z,,+&+z$ Line-to-Line Voltages
I3 Line-to-Scutral Voltage
zcz,
z,,=zc+z,+~ AB E,D=E.b=~/:j~,t’30=(1-aa’)E,
BC E,D = Eh = -jdZE,
- = (a2-u)El
c-4 EID = E, = 1/3E,d160 = (a - I),??,
An equivalent delta for a star-connected, three-phase BA E,D=Ebn=~/3Ele-1’50=(a?-l)E,
load with neutral grounded ca,unot be found, since xero- CB EID=E,b=jy’~El=(a--~2)E~
sequence current can flow from the line to the star load AC E,D=E.,=~SEI~-~30=(1-a)E,
and return in the ground, but cannot flow from the line
to any delta arrangement. If E,,, EbR, and E,,, form a negative-sequence set of
vectors, the vector diagram of Fig. 14(c) illustrates the
HI. RELATIONSHIP BETWEEN SEQUENCE relation between E2= E,,, and E2D, the negative-sequence
COMPONENTS OF LINE-TO-LINE AND component of the line-to-line voltages. Again, the nl-
gebraic relation expressing E2D as a function of E2 will
LINE-TO-NEUTRAL VOLTAGES
depend upon the line-to-line phase selected for reference,
Assume that E:,,, Eba, and E,,, are a positive-sequence as illustrated in Table 3.
set of line-to-neutral vectors in Fig. 14(a). The line-to-
line voltages will also form a positive-sequence set of TABLE 3

Negative-Sequence Line-to-Line Voltage


Reference Phase As a Function of Negative Sequence
Line-to-Seutral Voltage

AB END= Eab = d/:jE2c-~= = (1 - a)E:


BC E?D = Ebe =j&?E, = (a-a?)E?
c-4 END=E, = ~~E~r-i’~O= (az-l)E?
BA END=Eba= .\/zE2d150= (a-1)E2
CB END= E,b = --jd\/3E,
- = (a* -a)Ez
(a) AC END= E,, = t/3E2tiao = (1 -a’) E,

Since the line-to-line voltages cannot have a zero-se-


t quence component, EOD=O under all conditions, and Eo
is an indeterminate function of E,,D.
The equations expressing EID as a function of El, and

y :::-;A ENDas a function of Ez, can be solved to express El and


E, as functions of ElD and E2D, respectively. Refer to
Table 4 for the relationships;
TABLE 4

Reference
Phase
Ebc
E
E, =-@,--130 l-a
= -E,D E”D
E, =-z&30 1 -a=
= TE2D
(bl (cl AB
d/3 3
Fig. 14-Relationships between line-to-line and line-to- E a-a2
BC E, =j--$ = ~EID
neutral components of voltage.
E
El =D,-,150=--s-. a2-1 EPD
E? =xoj15~ = a-l
-END
(b) Positive-sequencerelationships. CA
43
3 E,D
3
(c) Negative-sequencerelationships. a2 - 1
BA
E,D
E, =73ci160 = a-l
3E,D J&J
E, v-z-““0 = -END
3
vectors. The relationship between the two sets of three- a2-a a-a2
CB E, = -j--$E =-E~D E2 =J~$ = 3Em
phase vectors is shown in Fig. 14(b). Although END(the
positive-sequence component of the line-to-line voltages) El =$,m = l-a2
TEln E2D
E,=--z-i=G3E2~ l-a
AC
will be numerically equal to ~~E1---E, is the positive-
sequence component of the line-to-neutral voltages (which
is equal in this case to E,,); the angular relationship be- Certain authors have arbitrarily adopted phase CB as
tween El and E1~ depends upon the line-to-line voltage reference, since the relations between the line-to-line and
taken as reference. The choice is arbitrary. Table 2 gives line-to-neutral components are easily remembered and
the relation between E1~ and E, for various line-to-line the angular shift of 90 degrees is easy to carry in com-
phases selected as reference, putations. Using this convention:
Chapter 2 Symmetrical Components 19

El= -j$
upon the phase selected for reference. I, is taken as refer-
El,, =j&E, ence for the line currents. Refer to Table 5.
.E2D
END= - j&?Ez (19) -
E2 =‘72
EoD=O Eo is not a function of EO~ Delta
Reference
The equations and vector diagrams illustrate the inter- Currerl t
esting fact that the numerical relation between the line-
to-line and line-to-neutral positive-sequence components ZZ
is the same as for negative-sequence; but that the angular 1,
shift for negative-sequence is opposite to that for positive-
sequence, regardless of the delta phase selected for refer- ZZ
ence. Also, a connection of power or regulating trans-
formers giving a shift of 0 degrees in the transformation -L
for positive-sequence voltage and current will give a shift
of - 0 degrees in the transformation for negative-sequence -1-d
voltage and current.
-I,
-
IV. SEQUENCE COMPONENTS OF LINE AND
If the current (-1,) is taken as reference, the relation
DELTA CURRENTS
are easily remembered; also, the j operator is convenien.
The relation existing between the positive-sequence to use in analysis.
component of the delta currents and the positive-sequence
component of the line currents flowing into a delta load
or delta-connected transformer winding, and the relation
esisting for the negative-sequence components of the cur- I,,=$ (20)
rents are given in Figs. 15(b) and 15(c). Although the
components of line currents are dz times the delta phase
selected for reference, the angular relationship depends V. STAR-DELTA TRANSFORMATIONS OF
VOLTAGE AND CURRENT
IO Each sequence component of voltage and current must
0-
be followed separately through the transformer, and the
‘f \
angular shift of the sequence will depend upon the input
c -
IC and output phases arbitrarily selected for reference. In
Fig. 16(a), the winding ratio is 12and the overall trans-
az 1,
formation ratio is N = $. Line-to-line or line-to-neutral
Ib
b -
voltages on the delta side will be N times the correspond-
(0)
ing voltages on the star side of the transformer (neglecting
impedance drop). If the transformer windings are sym-
metrical in the three phases, there will be no interaction
between sequences, and each sequence component of volt-
age or current is transformed independently.
To illustrate the sequence transformations, phases a and
a’ have been selected as reference phases in the two circuits.
Figs. 16(b), (cl, (4, and (e) give the relationships for the
three phases with each component of voltage and current
considered separately.
From the vector diagrams
El’ = NElej30

1
Iz’ = -12c-j30
(b) N
Fig. 15-Relationships between components of phase and Regardless of the phases selected for reference, both
delta currents. positive-sequence current and voltage will be shifted in
(b) Positive-sequence relationships. the same direction by the same angle. Negative-sequence
CC) Negative-sequence relationships. current and voltage will also be shifted the same angle in
20 Symmetrical Components Chapter 2

late around the delta such that I,= l,= I,= TO<, = ‘TO.
I1
The zero-sequence line-to-neutral voltages, E, and l?,’ are
entirely independent; each being determined by conditions
in its respective circuit. The transformation characteristics
for the three sequence currents and voltages, and the se-
quence impedance characteristics, for common connections
444
E’cg
- - -
of power and regulating transformers are given in Chap. 5.
The action of a transformer hank in the transformation of
zero-sequence currents must be given particular attention,
since certain connections do not permit zero-sequence cur-
rent to flow, others permit it to pass through t,hc bank
without transformation, and still others transform zero-
sequence quantities in the same manner as positive- or
negative-sequence quantities are transformed.

VI. THREE-PHASE POWER


The total three-phase power of a circuit can be expressed
in terms of the symmetrical components of the line cur-
rents and the symmetrical components of the linc-to-
neutral voltages.
P=3(E,I, cos e,+E,I, cos 81+E,I, cos 8,) (22>
(b) where 190is the angle between E” and 10, e1 the angle
between E, and II, & the angle between E, and I!. The
Ebc equation shows that the total power is the sum of the three
components of power; but the power in one phase of an
unbalanced circuit is not one-third of the above expression,
since each phase will contain components of polrer resulting
from zero-sequence voltage and positive-sequence current,
etc. This power “between sequences” is generated in one
phase and absorbed by the others, and does not appear in
the expression for total three-phase power.
Only positive-sequence power is developed by the gene-
rators. This power is converted to negative-sequence and
zero-sequence power by circuit dissymmetry such as occurs
from a single line-to-ground or a line-to-line fault. The
unbalanced fault, unbalanced load, or other dissymmetry
(d) (9) in the circuit, thus acts as the “generator” for negative-
Fig. 16-Transformation of the sequence components of cur- sequence and zero-sequence power.
rent and voltage in a star-delta transformer bank.
(h) Relationship of positive-sequence line-to-neutral and line-to- VII. CONJUGATE SETS OF VECTORS
line voltages.
(c) Relationship of positive-sequence currents. Since power in an alternating-current circuit is defined
(d) Relationship of negative-sequence line-to-neutral and line- as EP (the vector E times the conjugate of the vector I),
to-line voltages. some consideration should be given to conjugates of the
(e) Relationship of negative-sequence currents. symmetrical-component sets of vectors. A system of
positive-sequence vectors are drawn in Fig. 17(a). In
one direction, and the negative-sequence angular shift will
be eq~lal to the positive-sequence shift but in the opposite
direction. As previously stated, this is a general rule for all
connections of power and regulating transformers, wher-
ever phase shift is involved in the transformation.
Since zero-sequence current cannot flow from the delta
winding, there will be no zero-sequence component of I,‘.
If the star winding is grounded, I, may have a zero-se-
quence component. From the star side the transformer
bank acts as a return path for zero-sequence current (if the
neutral is grounded), and from the delta side the bank acts
as an open circuit to zero-sequence. For zero-sequence
current alone, I,= Ib = I,= I,, and a current will circu- Fig. 17-Conjugates of a positive-sequence set of vectors.
Chapter 2 Symmetrical Components 21

A
tained for the balanced part, of the system. The advantage
of the sequence network is that, since currents and voltages
of only one sequence are present, the three-phase system
can be represented by an equivalent single-phase diagram.
The entire sequence network can often be reduced by sim-
ple manipulation to a single voltage and a single im-
pedance. The type of unbalance or dissymmetry in the
circuit can be represented by an interconnection between
the equivalent sequence networks.
Ibz The positive-sequence network is the only one of the
three that will contain generated voltages, since alternators
c%,nbe assumed to generate only positive-sequence volt-
ages. The voltages appearing in the negative- and zero-
Fig. l&-conjugates of a negative-sequence set of vectors. sequence networks will be generated by the unbalance, and
will appear as voltages impressed on the networks at the
accordance with the definition that the conjugate of a given point of fault. Furthermore, the positive-sequence net-
vector is a vector of the same magnitude but displaced the work represents the system operating under normal bal-
same angle from the reference axis in the oppo.site direction anced conditions. For short-circuit) studies the internal
to the given vector, the conjugates of the positive-sequence voltages are shorted and the positive sequence netxork is
set of vectors are shown in Fig. IS(b). Sote that the con- driven by the voltage appearing at the fault before the
j rlgntes to a positive-sequence set of vectors form a negative- fault occurred according to the theory of Superposition and
sequence set, of vectors. Similarly, as in Fig. 18, the con- the Compensation Theorems (see Chapter 10, Section 11).
jugates to a negative-sequence set of vectors form a posi- This gives exactly the increments or changes in system
quantities over the system. Since the fault current equals
yo=Ibo= I,,
zero before the fault, the increment alone is the fault cur-
rent total. However, the normal currents in any branch
must be added to the calculated fault current in the same
(al branch to get the total current in any branch after the
fault occurs.
6. Setting Up the Sequence Networks
t
~oo=$,o=~co The equivalent circuits for each sequence are set up “as
(b)\
Fig. 19-Conjugates of a zero-sequence set of vectors. viewed from the fault,” by imagining current of the partic-
ular sequence to be circulated through the network from
t ive-sequence set. The conjugate of a zero-sequence set of the fault point, investigating the path of current flow and
\xxtors is another zero-sequence set of vectors, see Fig. 10. the impedance of each section of the network to currents
of that sequence. Another approach is to imagine in each
VIII. SEQUENCE NETWORKS network a voltage impressed across the terminals of the
network, and to follow the path of current flow through
5. General Considerations the net.work, dealing with each sequence separately. It is
One of the most useful concepts arising from symmct- particularly necessary when setting up the zero-sequence
ricnl components is that of the sequence network, which network to start at the fault point, or point of unbalance,
is an equivalent network for the balanced power system since zero-sequence currents might not flow over the entire
Imder an imagined operating condition such that only one system. Only parts of the system over which zero-sequence
sequence component of voltages and currents is present in current will flow, as the result of a zero-sequence voltage
t,hc system. As shown above for the case of balanced loads impressed at the unbalanced point, are included in the
(and it can be readily shown in general) currents of one zero-sequence network “as viewed from the fault.” The
sequence will create voltage drops of that sequence only, if two terminals for each network correspond to the two
:L power system is balanced (equal series impedances in all points in the three-phase system on either side of the un-
three phases, equal mutual impedances between phases, balance. For the case of shunt faults between conductors
rotating machines symmetrical in all three phases, all and ground, one terminal of each network will be the fault
hanks of transformers symmetrical in all three phases, point in the three-phase system, the other terminal will be
~tc.). There will be no interaction between sequences and ground or neutral at that point. For a series unbalance,
the sequences are independent. Kearly all power systems such as an open conductor, t,he two terminals will cor-
can be assumed to be balanced except for emergency con- respond to the two points in the three-phase system im-
ditions such as short-circuits, faults, unbalanced load, un- mediately adjacent to the unbalance.
balanced open circuits, or unsymmetrical conditions arising
in rotating machines. Even under such emergency unbal- 7. Sequence Impedances of Lines, Transformers,
anced conditions, which usually occur at only one point in and Rotating Machinery
the system, the remainder of the power system remains The impedance of any unit of the system-such as a
balanced and an equivalent sequence network can be ob- generator, a transformer, or a section of line---to be in-
22 Symmetrical Components Chapter 2

scrted in a sequence network is obtained by imagining unit distribute through each network in accordance with the
current of that sequence to be circulated through the distribution factors found for unit current. This follows
apparatus or line in all three phases, and writing the equa- from the fact that within any one of the three networks
tion for the voltage drop; or by actually measuring the the currents and voltages of that sequence are entirely
voltage drop when crwrent of the one sequence being in- independent of the other two sequences.
vestigated is circulated through the three phases of the These points will be clarified by detailed consideration
apparatus. The impedance to negative-sequence currents of a specific example at the end of this chapter.
for all static non-rotating apparatus will be equal to the
impedance for positive-sequence currents. The impedance IX. CONNECTIONS BETWEEN THE
to negative-sequence currents for rotating apparatus will SEQUENCE NETWORKS
in general be different from the impedance to positive
sequence. The impedance to zero-sequence currents for all As discussed in Part II, Sec. 3 of this chapter, any un-
apparatus will in general be different from either the im- balance or dissymmetry in the system will result in mutual
peclunce to positive-sequence or the impedance to negative- action between the sequences, so that it is to he expected
sequence. The sequence impedance characteristics of the that the sequence networks will have mutual coupling, or
component parts of a power system have been investigated possibly direct connections, between them at the point of
in detail and are discussed in Chaps. 3, 4, 5, and 6. unbalance. Equations can be written for the conditions
An impedance in the neutral will not appear in either the existing at the point of unbalance that show the coupling
positive-sequence network or the negative-sequence net- or connections necessarily existing between the sequence
n-ork, since the three-phase currents of either sequence add networks at that point.
to zero at the neutral; an equivalent impedance equal to As pointed out in Sec. 5, it is usually sufficiently accurate
three times the ohmic neutral impedance will appear in the to reduce a given system to an equivalent source and single
zero-sequence network, however, since the zero-sequence reactance to the point of fault. This in effect means that
currents flowing in the three phases, 10 add directly to give the system is reduced to a single generator with a fault
a neutral current of 310. applied at its terminals. Figs. 20(a) through 20(e) show
such an equivalent system with the more common types of
8. Assumed Direction of Current Flow faults applied. For example Fig. 20(a) is drawn for a three-
Ry convention, the positive direction of current flow in
each sequence network is taken as being outward at the
faulted or unbalanced point; thus the sequence currents are
assumed to flow in the same direction in all three sequence Nj@pF$J
networks. This convention of assumed current flow must
be carefully followed to avoid ambiguity or error even
though some of the currents are negative. After the cur- EQUIVALENT SYSTEM IN
k!F
rents flowing in each network have been determined, the L---%~.&-?L 1 N2
sequence voltage at any point in the network can be found x0
by subtracting the impedance drops of that sequence from rl
Fo

the generated voltages, taking the neutral point of the net-


work as the point of zero voltage. For example, if the im-
pedances to positive-, negative-, and zero-sequence be-
tween neutral and the point in question are 21, 22, and &,
respectively, the sequence voltages at the point will be
E, = E:,l -I,&
E, = - I222 (23)
E, = -I&,
n-here E,l is the generated positive-sequence voltage, the
positive-sequence network being the only one of the three
having a generated voltage between neutral and the point
for which voltages are to be found. In particular, if Z,,
22 and Z0 are the total equivalent impedances of the net-
works to the point of fault, then Eq. (23) gives the se- ‘+,I tfb

quence voltages at the fault. (4)


Distribution Factors-If several types of unbalance VECTOR DIAGRAM SHOWING VOLTAGES
AND CURRENTS DURING FAULT
are to be investigated for one point in the system, it is (3)
convenient to find distribution factors for each sequence SHORTHAND REPRESENTATiON
OF POSITIVE-, NEGATIVE-,
current by circulating unit sequence current in the ter-
AND ZERO-SEQUENCE NET-
minals of each network, letting it flow through the net- WORKS
work and finding how this current distributes in various (a)
branches. Regardless of the type of fault, and the mag- Fig. 20.
nitude of sequence current at the fault, the current will (a) Three-phase short circuit on generator.
Chapter 2 Symmetrical Components

EQUIVALENT SYSTEM EQUIVALENT SYSTEM

EOI
EOIF E al GROUND
\
-Go
\ Eaf
(b) (b)
POSITIVE-, NEGATIVE-, AND POSITIVE-, NEGATIVE-, AND
ZERO-SEQUENCE DIAGRAMS ZERO-SEQUENCE DIAGRAMS
FOR SYSTEM(a) (“a” PHASE) FOR SYSTEM (a) (‘a” PHASE)

Ebi

ECI
(d)
(d)
VOLTAGE VECTOR DIAGRAM VECTOR DIAGRAM SHOWING *,
ICl

SHORTHAND REPRESENTATION VOLTAGES AND CURRENTS SHORTHAND REPRESENTATION

Cd)
OF (b) DURING FAULT OF (b)
(b)

EQUIVALENT SYSTEM EQUIVALENT SYSTEM

POSITIVE-,NEGATIVE-,AND
ZERO-SEOUENCE DIAGRMS POSITIVE-, NEGATIVE-.AND
&IF
\ FOR SYSTEM(a)(‘b”PHASE) ZERO-SEQUENCE DIAGRAMS
FOR SYSTEM (0) (“a” PHASE)

EC1
(d)
EC, (d) VECTOR DIAGRAM SHOWING
SHORTHAND
VECTOR DIAGRAM SHOWING VOLTAGES AND CURRENTS
ECF
VOLTAGES AND CURRENTS REPRESENTATION SHORTHAND’REPRESENTATION
DURING FAULT
DURING FAULT OF (b) OF (b)
.
w Fig. 20 (e)
(b) Single-line-to-ground fault on ungrounded generator. (d) Line-to-line fault on grounded or ungrounded generator.
(c) Single-line-to-ground fault on generator grounded through (e) Double-line-to-ground fault on generator grounded through
a neutral reactor. a neutral reactor.
24 Symmetrical Components Chapter 2

!
(
a1 F -5 II
ii .,
F
I
(j

7
G(

FAULT s INGLE LINE-TO-GROUND FAULT


WEE-PHASE-TO-GROUNORU TT HREE-PHASE-TO-GRWNO SINGLE LINE-TO-CWUND FAULT
THRIYJGHIMPErJ&cE GROUND;~, SYSTEM
(b)

LINE-TO-LINE F&“LT THROUGH IMPEDANCE THREE-PN~SE-TO-GROUND FIULT WITH IMPEDINCE IN PnnSE 0


Ii1

DOUBLE LINE-TO-CROOND FAULT


(h)

(b)

,.,,,,,,,/, T, ,,,,,,/,
DOUBLE LINE-TO-GROUND FAULT THR‘WC” IMPEDANCE UNBALANCED STAR LOAD
(II
! 01 x Y Yl Y I 1) x Y
! b) z. ,) -
(. :)-
N

1)
)I

UNSA.C&NCEDDELTeiLo*0 ONE LINE OPEN ONE LlNE OPEN WlfH TWO LlNES OPEN TWO LINES OPEN. NOLINES OPEN.IMPEDANtES
UNGROUNDED SYSTEM IMPEDANCE Id$THER LINES IMPEDPINCE,~ Tl,lRD LlNE WA0 LINEB ~E~TRIL RETURN
(mL (nl
II X.Z.Y ($1 xh 01 x,2Y x 5.v
bl ,lb) .,.2b *>
. 2b
:I I:C) ,..2b ...2b
26

IMPEDANCE IN ONE LINE “NEPUAL SERIES IMPEDINCES lMPEOANCES IN ONE LINE EQUAL IMPEDANCES IN EQUAL IMPEDANCES IN “NEWAL SERIES IMPEDANCE
AN0 NEUTRAL RET”URN TWO LINES TWO LINES WITH IYPECANCE
IN NEUTRAL RETURN
(Ul IV)

Fig. 21-Connection of the sequence networks to represent shunt and series unbalanced conditions. For shunt unbalances
the faulted point in the system is represented by F and neutral by N. Corresponding points are represented in the sequence
networks by the letter with a sequence subscript. P, N, and Zrefer to the positive-, negative-, and zero-sequence networks,
respectively. For series unbalances, points in the system adjacent to the unbalance are represented by X and Y. N is again
the neutral.
Chapter 2 SymmetricalComponents 25

phase fault on the system. Part (1) shows the equivalent IF = VBIld (31)
system (2) the corresponding positive- negative- and zero-
sequence diagrams, and (3) the shorthand representation
EIF= E,l- IlFZl= ??kT!- (32)
z+z,
of the sequence diagrams. Part (4) is a vector diagram
showing graphically the relationship between the various EZF= -12,z,# (33)
1 2
voltages and currents. In the zero-sequence diagrams of
(2) and (3) a distinction is made between “neutral”, N, 12. Double Line-to-Ground Fault-Fig. 20(e)
and “ground”, G. In the positive- and negative-sequence
E,l E,I(Z,+Z~)
networks no such distinction is necessary, since by their IlF= z 7 (34
definition positive- and negative-sequence quantities are =%122+zlzo+zJ!o
z,+-=-
balanced with respect to neutral. For example, all pos- z*+z,

itive- and negative-sequence currents add to zero at the


system neutral so that the terms ‘neutral” and “ground” I2F= -&IIF=z 7 ,i”;“r;, 7 (35)
2 JO lJ2 Jl 0 J2 ‘0
arc synonymous. Zero-sequence quantities however, are - ZzE,,
not balanced with respect to neutral. Thus, by their IOFZ - -IlF z2
z,+z,
=
z,z,+z*z,+z~zo (36)
nature zero-sequence currents require a neutral or ground ZrZoE:,‘:ll
return path. In many cases impedance exists between E1F= E,l- I,FZl= - (37)
2122+ zLzo+ ZSZ”
neutral and ground and when zero-sequence currents flow a
voltage drop exists between neutral and ground. There- Z2ZoE:,*
Em = - z”FZ2= (38)
fore, it is necessary that one be specific when speaking of z,z,+z,z,+z,z,
line-to-neutral and line-to-ground zero-sequence voltages. Z&E,,,
They are the same only when no impedance exists between EOF= - I~FZ~= (39)
Z1Z~+Z,Z,+Z,Z,
the neutral and ground.
In parts (3) of Fig. 20(aj all portions of the network 13. One Line Open-Fig. 21(n)
within the boxes are balanced and only the terminals at I-L(Z,+Zo)
the point of unbalance are brought out. The networks as I1F = (W
z~zz+zlz~+z~z13
shown are for the “a” or reference phase only. In Eqs. (25)
- ZoE,l
through (29) the zero-sequence impedance, Z,, is infinite 197= (11)
for the case of Fig. 20(b) and includes 3Xo in the case of ZlZ? + z,zo +zzzo

Fig. 20(e). Fig. 21 gives a summary of the connections - Z?E,l


1°F = (42)
required to represent the more common types of faults Z,zy$-ZlZO+z2z”
encountered in power system work. Z:ZoE,,
Equations for calculating the sequence quantities at the El,- E,, = E,1- IlFZl= Z1Z,+Z,Z”+%2Z,
~ (43)
point of unbalance are given below for the unbalanced con- ZzZoE:,,
ditions that occur frequently. In these equations EIF, EBx- Es, = - IzFZ, = (JJ)
E?r, and E,,F are comp0nent.s of the line-to-neutral volt- z,z,+z,z”+z?zi
ages at the point of unbalance; I~F,I~F, and IOFare com- ZzZoE,1
E, - Eoy= - I,pZo = (45)
ponents of the fault current IF; Zl,Zz, and 2, are imped- Z,Z2+Z1Z,+Z2Zo

ances of the system (as viewed from the unbalanced


terminals) to the flow of the sequence currents; and E, is 14. Two Lines Open-Fig. 21(p)
the line-to-neutral positive-sequence generated voltage. Ed
I1F = I2F = IOF = z1+z2+20 (W
9. Three-Phase Fault-Fig. 20(a) IF = I, = 31OF (‘47)
IIF=IF+ Elx-E~y=E,~-Jl~Z~=Z
Ea1(Z,+Zd
+z +z (48)
1 2 0
1

10. Single Line-to-Ground Fault-Fig. 20(b) Ezx- Eqy= - I,FZ, = - y+zE;& (W


Jl 2 0

(25)
Eo,-EOy= -I,,FZ,,= -z ff;“;7 (50)
1 2 JO

(.G-tZo) 15. Impedance in One Line-Fig. 21(s)


EIF = E&l- I~FZ~= E,l (27)
z+Z,+Zo E,1(ZZo+ZZz+3ZoZz)
EalZz I1F = (51)
Es,= - IzpZx= - cw zzlzo+zz1z,+3z,z,zo+zzzzo
z1+z2+zo
E&-o ZZoE,l
I2F= - (52)
EoF= - I‘,FZ,,= -
Z1fZ*fZo :
(29)
ZZ&al
11. Line-to-Line Fault-Fig. 20(d) IOF= - (53)
ZZ,Zo+ZZ~Z,+3z,z,z,+ZZ,Zo
Ed (54)
I 1F 3 -12.$=----- (30)
z1+z2
26 Symmetrical Components Chapter 2

ZZzZnE,,l connections will have to be made through phase-shifting


E-EQ = - -~- (55) transformers. ?‘he analysis in the cases of simult,ancous
/,r%,+%%,%,,+%%1%::+3%,~‘,Za+%Z?Zo
faults is consitlcrably more complicated than for single
E,- j7,,, = _ .._~~_~~_-~~~~~!~~-.. (56) unbalances.
l,,f%(j= %%,%,+%z,z?+.?%~z~zo+%%~%~ So assumptions were made in the derivation of the rep-
Tf two or more Imbalances occur simultaneously, mutual rcsentation of the shunt and series unbalances of Fig. 21
coupling or connect ions will occur between the sequence that should not permit the application of the same prin-
nctn-arks at each point of unbalance, and if the unbalances ciples to simultaneous faults on multiple unbalances. In
arc not symmetricsal with respect to the same phase, the fact various cases of single unbalance can be combined to

TRANSFORMERS
SIMULTANEOUS SINGLE LINE-TO-GROUND SIMULTANEOUS SINGLE LINE-TO-GROUND SIMULTANEOUS SINGLE LINE-TO-GROUND
ON PHASE A AND LINE-TO-LINE BETWEEN FAULT AND OPEN CONDUCTOR ON PHASE A. THROUGH IMPEDANCE AND OPEN CON-
PHASES B AND G. DUCTOR ON PHASE A.
((1) (b) (c)

TRANSFORMERS
SIMULTANEOUS SINGLE LINE-TO-GROUND SIMULTANEOUS SINGLE LINE-TO-GROUND
SIMULTANEOUS SINGLE LINE-TO-GROUND
FAULT ON PHASE B AND OPEN CONDUCTOR FAULT ON PHASE C AND OPEN CONDUCTOR
FAULTS ON PHASES A AND B AT DIFFEREN;
ON PHASE A. ON PHISE A. LOCATIONS.
Cdl le) (f)

Fig. z&-Connections between the sequence networks for typical cases of multiple unbalances.
Chapter 2 Symmetrical Components 27

form the proper restraints or terminal connections to rep- 25000 KVA 20000 KVA
resent mult,iple unbalances. For example, the representa- q x=10% fb X=9%
tion for a simultaneous single line-to-ground fault on phase
‘~a” and a line-to-line fault on phases “6” and ‘<c” can be
derived by satisfying the terminal connections of Figs.
21(d) and 21(f). F ig. 21(d) dictates that the three net-
lvorks be connected in series, while Fig. 21(f) shows the @if; ;.$:,‘i,k;:~

positive- and negative-sequence networks in parallel. Both


of these reqllirements can be met simultaneously as shown
x+x$ ” $b
in Fig. 22(a). Simultaneous faults that are not sym- 44
25000 KVA FAULT 5000 KVA 15000 KVA
metrical to the reference phase can be represented by sim- x=6% (0) X=5% x=6%
ilar connections using ideal transformers or phase shifters
t
to shift the sequence voltages and currents originating in 14.5’X 15’
all of the unbalances except the first or reference condition. o-14’ 14’4 Cd0 IO’-0
The fault involving phase “a” is usually taken as the i- 4-
45’ 45’
rcfcrence and all others are shifted by the proper amount
))efore making the terminal connections rcquircd to satisfy
that particular type of fault. The positive-, negative-, and 110 KV LINE 66 KV LINE
zero-sequence shifts, respectively for an unbalance that is CONDUCTOR 4/O CU. CONDUCTOR 410 CU.
symmetrical to phase “a” are 1, 1, 1; “b” phase a?, a, 1; ALL GROUND WIRES 0.375 EBB STEEL
to ‘lc” phase a, a2, 1. A few multiple unbalances that may (b)
occur at one point in a system simultaneously are given in
Fig. 22, which also gives one illustration of simultaneous GENERATOR G, GENERATOR G,
faults at different points in a system with one fault not 37,500 KVA
50,000 KVA
symmetrical with respect to phase a. NEUTRAL GROUNDED THROUGH 4% REACT. NEUTRAL UNGROUNDED
To summarize, the procedure in finding voltages and x,, = 100% xd=b,%
currents throughout a system during fault conditions is: x’r,= 21 % X’d’ 25%
(1) set up each sequence network as viewed from the fault, x”,,’ 12”/ x”d= I7 96
X2’ 12; x2= 17%
(2) find the distribution factors for each sequence current
Xc= 6% xc= 5%
throughout its network, (3) reduce the network to as sim-
(c)
ple a circuit as possible, (4) make the proper connection
between the networks at the fault point to represent the Fig. 23-Typical system assumed for fault calculation.
unbalanced condition, (5) solve the resulting single-phase
(a) System single-line diagram.
circuit for the sequence currents at the fault, (6) find the (b) Line construction.
sequence components of voltage and current at the desired (c) Tabulation of generatorconstants.
locations in the system. The positive-sequence voltage to
be used, and the machine impedances, in step (5) depend
upon when the fault currents and voltages are desired; if (d) Fault current.
immediately after the fault occurs, in general, use sub- (e) Line currents, line-to-ground voltages, and line-to-
transient reactances and the voltage back of subtransient line voltages at the breaker adjacent to the fault.
reactance immediately preceding the fault; if a few cycles (f) Line currents, line-to-ground voltages, and line-to-
after the fault occurs, use transient reactances and the line voltages at the terminals of G’.
voltage back of transient reactance immediately before the (g) Line currents, line-to-ground voltages, and line-to-
fault; and if steady-state conditions are desired, use syn- line voltages at the 110 kv breaker adjacent to the
chronous reactances and the voltage back of synchronous 25,000 kva transformer.
reactance. If regulators are used, normal bus voltage can
17. Assumptions
be used to find steady-state conditions and the machine
reactance in the positive-sequence network taken as being (1) That the fault currents are to be calculated using
zero. transient reactances.
(2) A base of 50,000 kva for the calculations.
X. EXAMPLE OF FAULT CALCULATION (3) That all resistances can be neglected.
(4) That a voltage, positive-sequence, as viewed from
16. Problem the fault of j 100% will be used for reference. This
Let us assume the typical transmission system shown .66,000
is an assumed voltage of J 1/3 volts between
in Fig. 23(a) to have a single line-to-ground fault on one
end of the 66 kv line as shown. The line construction is line ‘(a” and neutral.
given in Fig. 23(b) and the generator constants in Fig. (5) That the reference phases on either side of the star-
23(c). Calculate the following: delta transformers are chosen such that positive-
(a) Positive-sequence reactance to the point, of fault. sequence voltage on the high side is advanced 30” in
(b) Negative-sequence reactance to the point of fault. phase position from the positive-sequence voltage on
(c) Zero-sequence reactance to the point of fault. the low side of the transformer.
28 Symmetrical Components Chapter 2

18. Line Reactances (Refer to Chap. 3) turning in ground; unit IK is 3/2 amperes in each of the
Positive- and Negative-Sequence Reactances of two ground wires with three amperes returning in the
the 110 kv Line. ground; unit I,,’ is one ampere in each of the three line con-
ductors with three amperes returning in the ground; and
For 4/O copper conductors x,=0.497 ohms per mile. unit I,’ is three amperes in the ground wire with three
zd=+(zd for 14 feet+& for 14 feet+xd for 28 feet). amperes returning in the ground.
= +(0.320+0.320+0.404) =0.348 ohms per mile.
x1=x2=x,+&, = 0.497+0.348 = 0.845 ohms per mile. These quantities are inter-related as follows:
Eo=Iozo(a) +Iczo<aa)+Idzow +Ihzow
Positive- and Negative-Sequence Reactances of E,o=Iozocag,
+IRzo(gj +IOI.w,nj +Ii’zo(m’) =0
the 66 kv Line. Ed= Iozo(aa,)
+IKZo(a’R)fIOIZOb’)+I$ZO(a’n’)
x,=0.497 ohms per mile. Eg’o=Iozo(ag~~
+Igzocgg,)+Io’zc,,,,,+Ig’zocg,,=O
xd=+(xd for IO feet+&! for 10 feet+xd for 20 feet)
where
= +(0.279+0.279+0.364) =0.307 ohms per mile.
xl=xz=x,+xd=0.497+0.307=0.804 ohms per mile. zOca)
= zero-sequence self reactance of the n circuit
=x,+x,-$(xd for 14 feet+x,i for 14 feetfxd for
Zero-Sequence Reactance+-Since zero-sequence 28 feet)
currents flowing in either the llO- or the BG-kv line will in- = 0.497+2.89 -2(0.348) = 2.69 ohms per mile.
duce a zero-sequence voltage in the other line and in all
three ground wires, the zero-sequence mutual reactances zg(~‘)= zero-sequence self reactance of the a’ circuit
between lines, between each line and the t1v-osets of ground =&,+x,-$(xd for 10 feet+xd for 10 feetfxd for
wires, and between the two sets of ground wires, must be 20 feet)
evaluated as well as the zero-sequence self reactances. In- =0.497+2.89-2(0.307) = 2.77 ohms per mile.
deed, the zero-sequence self reactance of either the 110- .z~(~)= zero-sequence self reactance of the g circuit
or the GG-kv line will be affected by the mutual coupling =$x,+x,-$(xd for 14.5 feet)
existing with all of the ground wires. The three conductors =$(2.79) +2.89-s(0.324) = 6.59 ohms per mile.
of the llO-kv line, with ground return, are assumed to form
one zero-sequence circuit, denoted by “a” in Fig. 24; the ,z~(~‘)
= zero-sequence self reactance of the g’ circuit
two ground conductors for this line, with ground return, =3x,+x,
form the zero-sequence circuit denoted “g”; the three con- =3(2.79)+2.89= 11.26 ohms per mile.
ductors for the 66-kv line, with ground return, form the
zero-sequence circuit denoted “a”‘; and the single ground zo(ap)= zero-sequence mutual reactance between the a
wire for the 66-kv line, with ground return, forms the zero- and g circuits
sequence circuit denoted “g’.” Although not strictly cor- =x,-$(xd for 12.06 feet+xd for 12.06 feet+xd for
rect, we assume t.he currents carried by the two ground 12.35 feet+xd for 12.35 feet+xd for 23.5 feet
wires of circuit “g” are equal. Then let: fxd for 23.5 feet)
=2.89-3(0.3303) = 1.90 ohms per mile.
,(-----;--->, ,,.- --------.*
j ~~(~~1)
= zero-sequence mutual reactance between the a
‘b- -----____-’: r .-_-_---__.
09’
/ and a’ circuits
Exe-$(xd for 60 feetfxd for 50 feet$xd for 70 feet
+xd for 46 feet-+&i for 36 feet+xd for 56 feet
-_----- --------

0) (< 0 0 a’ 0 )
for 74 feet+xd for 64 feet+zd for 84 feet)
(0 .------------s-mm--.* 0 0

-------------------J _ _____-__--------- -2 +xd


=2.89-3(0.493) = 1.411 ohms per mile.
Fig. 24-Z&o-sequence circuits formed by the 110 kv line (a);
the 66 kv line (a’), the two ground wires (g), and the single zO(ap*)
= zero-sequence mutual reactance between the a
ground wire (g’).
and g’ circuits.
=x,-$(xd for 75 feet+xd for 62 feet+% for 48 feet)
E0= zero-sequence voltage of circuit a =2.89-3(0.498) = 1.40 ohms per mile.
Ego=zero-sequence voltage of circuit g =O, since the
ground wires are assumed to be continuously z~(~‘$)= zero-sequence mutual reactance between the a’
grounded. and Q’ circuits.
EO’= zero-sequence voltage of circuit a’ ‘x,-$(xd for 15 feettxd for 18.03 feet+xd for
E,‘o= zero-sequence voltage of circuit .q’= 0, since the 18.03 feet)
ground - wire is assumed to be continuously =2.89-3(0.344) = 1.86 ohms per mile.
grounded.
I0 = zero-sequence current of circuit a Similar definitions apply for .?&rg) and Zo(,,f,. In each
I, = zero-sequence current of circuit g case the zero-sequence mutual reactance between two cir-
I,‘= zero-sequence current of circuit a’ cuits is equal to x, minus three times the average of the
I,’ = zero-sequence current of circuit g’ xd’s for all possible distances between conductors of the
two circuits.
It should be remembered that unit I0 is one ampere in The zero-sequence self reactance of the llO-kv line in
each of the three line conductors with three amperes re- the presence of all zero-sequence circuits is obtained by
Symmetrical Components 29
Chapter 2
,
j2OX jl4X j22.5%
letting I,, be zero in the above equations and solving for
E” Carrying out this rather tedious process, it will be
T.
foind that
EO
-li- = 2.05 ohms per mile.
0

The zero-sequence self reactance of the 66-kv line in


the presence of all zero-sequence circuits is obtained by
Eo
letting lo be zero in the equations and solving for 7. It
IO

will be found that


F = 2.25 ohms per mile.
0

The zero-sequence mutual reactance between the 66


and the llO-kv line in the presence of all zero-sequence
.r ‘_ ?

i56.5X
j21.0%
(Pe .‘? ::

z*= j2LOX

Fig. 26-Reduction of the negative-sequence network and the


negative sequence distribution factors.

1.0 j7.5% kva base and the networks set up as viewed from the
PI
fault. Illustrative examples of expressing these react-
antes in percent on a 50 OOO-kvabase follow:
Positive-sequence reactance of Gz=
(25)(j0=33.3%
(37 500)
Positive-sequence reactance of the 66-kv line=
(0.804) (40) (50 000) =36 (& ,
(66) (66) (10) .
- ‘.,

Z,= j26.4%
Positive-sequence reactance of the 1lo-kv line =
(0.845) (40) (50 000) = 14y
Fig. 25-Reduction of the positive-sequence network and the 0
positive-sequence distribution factors. (110) (110) (10)
Zero-sequence mutual reactance between the 66- and the
circuits is obtained by letting IO’ be zero and solving for IlO-kv line for the 30 mile section=
Ed
F. When this is done, it will be found that (0.87) (30) (50 000) = l8%
EX (W w9 (10)
-$with 1: = 0) = $(with lo = 0) = 0.87 ohms per mile.
The distribution factors are shown on each sequence
network; obtained by finding the distribution of one am-
19. The Sequence Networks pere taken as flowing out at the fault.
The sequence networks are shown in Figs. 25, 26, and Each network is finally reduced to one equivalent im-
27, with all reactances expressed in percent on a 50 QOO- pedance as viewed from the fault.
30 Symmetrical Components Chapter 2

j20% @ , j33.956 , j22.5% 20. Voltages and Currents at the Fault


& ‘Xgy.OX >i,,,“” >j6% 3 The sequence networks are connected in series to rep-
resent a single line-to-ground fault. The total reactance
j16% j77.596 ’ j25.8% 126.7% of the resulting single-phase netlvork is
2,~~+2,~~+2,~~=26.4~~+21.0~~+13.7~,=61.1~c.
jlOO%
Then : IOF=I1F=I2F=. -= 1.637 p.u.
361.1%
i 76.4% Y .
Since normal current for the GG-kv circuit (for a base
I
WV’ kva of 50 000)
.039 LjlSX
>j6% 50 000
jl6% j77.5% S j52.5% =p = 437.5 amperes.
e4/x&- 43X66
.sq .x’ +vv = J .071 lo=I1 =I, = (1.637)(437.5) =715 amperes.
‘. 1.0 POq j50%
,
No<‘? The total fault current =
.FO
1~+11+1~=4.911 p.u.=2145 amperes.
The sequence voltages at the fault:
i70.4%.
r .Vh--! E,=&,,-~~Z,=j100~0-j(1.G37)(26.-J-)~=j56.9%
=j21 700 volts.
1 il6X I i77.5% i46.5% 1?Ecv E2= -12Zz= -j(1.637)(21)%= -j34.-1oj,= -j13 100
volts.
Eo= -I,&= -j(1.637)(13.7)%= -j22.5%= -jS 600
volts.
E,,=Eo+El+Eg=O
E,,s=Eo+a2El+aEz=30 ZOO--j12 900
= 32 800 volts.
Ecg= Eo+aEl+a2E2= -30 200-j12 900
= 32 800 volts.
E,b=Eag-Ebg= -30 200fj12 900=32 800 volts.
Ebc = Ebg - E,, = 60 400 volts.
E,,= EC,-- Eag= -30 ZOO-j12 900=32 800 volts.

21. Voltages and Currents at the Breaker Adjacent


to the Fault
Using the distribution factors in the sequence net-
i55.12%
works at this point:
w II= (0.752)(1.637) = 1.231 p.u. =540 amperes.
.0388 j20.93%
Iz= (0.768)(1.637) = 1.258 p.u. =550 amperes.
j16X j82.2% .1022 I0 = (0.859) (1.637) = 1.407 p.u. = 615 amperes.
I,=lO+Il+lo= 1705 amperes.
~~=IO+a21~+aI~=70+j8.6=70.5 amperes.
I,=Io+aI~+a21~ =70-j&6=70.5 amperes.
jl5.2% The line-to-ground and line-to-line voltages at this
w
.141 point are equal to those calculated for the fault.
jl6% j82.2X
22. Voltages and Currents at the Breaker Adjacent
to Generator GI
The base, or normal, voltage at this point is 13 800 volts
r. ,c- ..,
line-to-line. or 7960 volts line-to-neutral.
L’ IS--l .. , j ,-l 50 000
The base, or normal, current at this point is
jl6% j97.4% j13.7% ~, &X 13.8
=2090 amperes. Since a star-delta transformation is
involved, there will be a phase shift in positive- and
negative-sequence quantities.
II= (0.684)(1.637)(2090)~-j30=2340 amperes
Z,=j13.7%
=2030-j1170.
Fig. 27-Reduction of the zero-sequence network and the Iz = (0.725) (1.637) (2090)@O = 2480 amperes
zero-sequence distribution factors. = 215O+j1240.
Chapter 2 Symmetrical Components 31

Io=O. _ Ih=IO+a21~+a1~=40.5+j9.35=41.6 amperes.


I,=lo+ll+lz=4180+j70=4180 amperes. I,=10+nlTl+n?lz=N..5-j9.35=41.6 amperes.
Ih=IO+a211+alz= -418O+jiO=4180 amperes.
The sequence voltages at this point are:
I,= Zo+aZl+a212 = --j140 = 140 amperes.
E,=jlOO%-j(O.68-1)(1.63’7)(21)%
The sequence voltages at this point are:
-j(-0.068)(l.63i)(20)~o=ji8.7~o
E1=(~j100a/,-j0.684X21X1.637~o)~-~30= -a276.5% =j50 000 volts.
=3045+j5270 volts. Ez= --j(O.i25)(1.637)(12)0j,
Ea=(-j0.725X12X1.637’%)~j30=-a14.2~0 -j(-0.043)(1.637)(20)%= -jl2.8’%
= 565-j980 volts. = -j8130 volts.
Eo=O. Eo= -j(O.O39) (1.637) (20)% = --j1.3y0 = --j825 volts.
Es, = El+ Ez = 3610fj4290 = 5600 volts. E,,=E,+E~+E,=j41000=41000volts.
Eba= a2E1+aEz= 3610 -j4290 = 5600 volts. Ebs=Eo+a2E1+aE2=50300-j21750=54800 volts.
E,,=aEl+a2E2=-7220=7220 volts. E,,=Eo+aE1+a~E2=-50 300-j21750=54800volts.
E,,,=+j8580=8580 volts. Eab= -503OO+j62750= 80400 volts.
E,,c= 10 830 -j4290 = 11 650 volts. Ebo= 100 600 = 100 600 volts.
E,,= - 10 830-j4290 = 11 650 volts. EC,= -50300-j62750= 80 400 volts.
23. Voltages and Currents at the IlO-kv Breaker
Adjacent to the 25 000 kva Transformer REFERENCES
The base, or normal, voltage at this point is 110 000 1. Method of Symmetrical Coordinates Applied to the Solution of
volts line-to-line; or 63 500 volts line-to-neutral. Polyphase Networks, by C. L. Fortescue, A.I.E.E. Transactions,
50000 V. 37, Part II, 1918, pp. 1027-1140.
The base, or normal, current at this point is
4$x110 2. Symme@icaZComponents (a book), by C. F. Wagner and R. D.
= 262 amperes. Evans, McGraw-Hill Book Company, 1933.
3. Sequence Network Connections for Unbalanced Load and Fault
The sequence currents at this point are: Conditions, by E. L. Harder, The Electric Journal, V. 34, Decem-
ber 1937, pp. 481-488.
I, = (-0.068)(1.637)(262) = -29.2 amperes. 4. Simultaneous Faults on Three-Phase Systems, by Edith Clarke,
I*= (-0.043)(1.637)(262) = -18.4 amperes. A.I.E.E. Transactions, V. 50, March 1931, pp. 919-941.
10 = (0.039) (1.637) (262) = 16.7 amperes. 5. Applications of Symmetrical Components (a book) by W. V. Lyon,
1,=1,+1,+1,= -30.9=30.9 amperes. McGraw-Hill Book Company, 1937.
CHAPTER 3

CHARACTERISTICS OF AERIAL LINES


Originul Authors: Revised by:
Sherwin H. Wright and C. F. Hall D. F. Shankle and R. L. Tremaine

I
S the design, operation, and expansion of electrical
power systems it is necessary to know electrical and
physical characteristics of conductors used in the con-
struction of aerial distribution and transmission lines.
This chapter presents a description of the common types
of conductors along with tabulations of their important
electrical and physical characteristics. General formulas
are presented with their derivation to sho\v the basis of the
tabulated values and as a guide in calculating data for Courlesy of Gmeral Cable Corporation
other conductors of similar shapes, dimensions, composi- Fig. 1-A typical stranded conductor, (bare copper).
tion and operating conditions.
Also included are the more commonly used symmetrical-
component-sequence impedance equations that are applic-
able to the solution of power system problems involving
voltage regulation, load flow, stability, system currents,
and voltages under fault conditions, or other system prob-
lems where the electrical characteristics of aerial lines are
involved.
Additional formulas are given to permit calculation of
approximate current-carrying capacity of conductors
taking into account such factors as convection and radia-
tion losses as influenced by ambient temperature, wind
velocity, and permissible temperature rise.

I. TYPES OF CONDUCTORS Courlesy OJ Allrminum company of America


Fig. 2-A typical ACSR conductor.
In the electric-power field the following types of con-
ductors are generally used for high-voltage power transmis-
sion lines: stranded copper conductors, hollow copper con-
ductors, and ACSR (aluminum cable, steel reinforced).
Other types of conductors such as Copper-weld and Cop-
perweld-Copper conductors are also used for transmission
and distribution lines. Use is made of Copperweld, bronze,
copper bronze, and steel for current-carrying conductors
on rural lines, as overhead ground wires for transmission Cow1e.s~ of .4lnmirrum Company OJ America

lines, as buried counterpoises at the base of transmission Fig. 3-A typical “expanded” ACSR conductor.
towers, and also for long river crossings.
A stranded conductor, typical of both copper and steel
conductors in the larger sizes, is shown in Fig. 1. A strand-
ed conductor is easier to handle and is more flexible than a
solid conductor, particularly in the larger sizes.
A typical ACSR conductor is illustrated in Fig. 2. In
this type of conductor, aluminum strands are wound about
a core +f stranded steel. Varying relationships between Courtesy of Anaconda Wire and Cable Company

tensile strength and current-carrying capacity as well as Fig. 4-A typical Anaconda Hollow Copper Conductor.
overall size of conductor can be obtained by varying the
proportions of steel and aluminum. By the use of a filler, ductor is known as “expanded” ACSR and is shown in
such as paper, between the outer aluminum strands and Fig. 3.
the inner steel strands, a conductor of large diameter can In Fig. 4 is shown a representative Anaconda Hollow
be obtained for use in high voItage lines. This type of con- Copper Conductor. It consists of a twisted copper “I”
32
Chapter 3 Characteristics of Aerial Lines 33

ors as shown in Fig. 7. Different relationships between


current-carrying capacity, outside diameter, and tensile
strength can be obtained by varying the number and size
of the Coppermeld and copper strands.
II. ELECTRICAL CHARACTERISTICS OE
AERIAL CONDUCTORS
Courtesy of General Cable Corporation The following discussion is primarily concerned with the
Fig. 5-A typical General Cable Type HH. development of electrical characteristics and constants of
.._.. ..- .._ ” .~ .._ “_ . r_____- _.______,.
---..l aerial conductors, particularly those required for analysis
of power-system problems. The constants developed are
particularly useful in the application of the principles of
symmetrical components to the solution of power-system
problems involving positive-, negative-, and zero-sequence
impedances of transmission and distribution lines. The
basic quantities needed are the positive-, negative-, and
Courtesy of Copperweld Steel Company
zero-sequence resistances, inductive reactnnces and shunt
Fig. 6-A typical Copperweld conductor. capacitive reactances of the various types of conductors
and some general equations showing how these quantities
are used.
1. Positive- and Negative-Sequence Resistance
The resistance of an aerial conductor is affected by the
three factors: temperature, frequency, current density.
Practical formulas and methods will now be given to take
into account these factors.
Temperature Ejfect on Resistance-The resistance
of copper and aluminum conductors varies almost cli-
rectly with temperature. While this variation is not strictly
linear for an extremely wide range of temperatures, for
practical purposes it can be considered linear over the
range of temperatures normally encountered.
When the d-c resistance of a conductor at a given tem-
perature is known and it is desired to find the d-c resistance
at some other temperature, the following general formula
Courtesg of Copperweld Steel Compnnu
may be used.
Fig. 7-Typical Copperweld-Copper conductors Rt2
-=-
lQ+tz
(1)
(a) Upper photograph-Type V Rt1 M+tl

(b) Lower photograph-Type F where


beam as a core about which strands of copper wire are Rtz = d-c resistance at any temperature tz degree C.
wound. The “I” beam is twisted in a direction opposite to Rtl= d-c resistance at any other temperature t1 degree C.
that of the inner layer of strands. M=a constant for any one type of conductor material.
Another form of hollow copper conductor is shown in = inferred absolute zero temperature.
Fiw 5. Known as the General Cable Type HH hollow cop- =234.5 for ann‘taled 100 percent conductivity copper.
pey’conductor, it is made up of segmental sections of cop- =241.5 for hard drawn 97.3 percent conductivity
per mortised into each other to form a self-supporting copper.
lmllow cylinder. Hollow copper conductors result in con- = 228.1 for aluminum.
ductors of large diameter for a given cross section of copper. The above formula is useful for evaluating changes in
Corona losses are therefore smaller. This construction also d-c resistance only, and cannot be used to give a-c resist-
produces a reduction in skin effect as well as inductance as ance variations unless skin effect can be neglected. For
compared with stranded conductors. A discussion of large small conductor sizes the frequency has a negligible effect
diameter conductors and their characteristics is given in on resistance in the d-c to 60-cycle range. This is generally
reference 1. true for conductor sizes up to 2/O.
Copperweld conductors consist of different numbers of Thevariations of resistance with temperature are usually
copper-coated steel strands, a typical conductor being illus- unimportant because the actual ambient temperature is
trated in Fig. G. Strength is provided by the core of steel indefinite as well as variable along a transmission line. An
and protection by the outer coating of copper. illustration of percentage change in resistance is when tem-
When high current-carrying capacities are desired as perature varies from winter to summer over a range of
well as high tensile strength, copper strands are used with 0 degree C to 40 degrees C (32 degrees F to 104 degrees F)
Copperweld strands to form Copperweld-Copper conduct- in which case copper resistance increases 17 percent.
34 Characteristics of Aerial Lines Chapter 3

Skin Eflect in Straight Round Wires- The resist-


ance of m-n-magnetic conductors varies not only with tem-
perature but also with frequency. This is due to skin effect.
Skin effect is due to the current flowing nearer the outer
surface of the conductor as a result of non-uniform flux
distribution in the conductor. This increases the resistance
of the conductor by reducing the effective cross section of
the conductor through which the current flows.
The conduct,or tables give the resistance at commercial
frequencies of 25, 50, and 60 cycles. For other frequencies
the following formula should be used.
T-Y=Krdc ohms per mile (2)
where
TY= the a-c resistance at the desired frequency
(cycles per second).
rdc = d-c resistance at any known temperature.
K = value given in Table 5.
In Table 5, K is given as a function of X, where
X= .063598

f =frequency in cycles per second.


P = permeability = 1.O for non-magnetic materials. 10-l n
10-Z 16
r mire= d-c resistance of the conductor in ohms per mile. + 10-3 15
slO+
Table 5 (skin effect table) is carried in the Bureau of y. 10-S
.E IO-6
i:
12
Standards Bulletin No. 169 on pages 226-8, to values of :10-'
510-8
II
IO
X= 100. To facilitate interpolation over a small range of .210-g
z 10-a
9

the table, it is accurate as well as convenient to plot a curve B lo-" ;


x 10-n 6
of the values of K vs. values of X. 2 lo-'3
1 IO-H :
Combined Skin Eflect and Temperature Eflect E' 10-K
p lo-'6 :
on Resistance of Straight Round Wires-When both
0 10-n
temperature and skin effect are considered in determining
0 IO 20 30 40 50 60
conductor resistance, the following procedure is followed. Amperes prCablp
First calculate the d-c resistance at the new temperature
using Eq. (1). Then substitute this new value of d-c re-
sistance and the desired frequency in the equation defining
X. Having calculated X, determine Ii; from Table 5. Then
using Eq. (2), calculate the new a-c resistance rf, using the
new d-c resistance for rdc and the value of K obtained from
Table 5.
E#ect of Current on Resistance-The resistance of
magnetic conductors varies with current magnitude as well
as with the factors that affect non-magnetic conductors Fig. S-Electrical Characteristics of Steel Ground Wires*
(temperature and frequency).
Current magnitude determines the flus and therefore the ductive reactance presented to zero-sequence currents is
iron or magnetic losses inside magnetic conductors. The influenced by the distribution of the zero-sequence current
presence of this additional factor complicates the determi- in the earth return path.
nation of resistance of magnetic conductors as well as any
tabulation of such data. For these reasons the effect of 2. Positive- and Negative-Sequence Inductive Re-
current magnitude will not be analyzed in detail. How- actance
ever, Fig. 8 gives the resistance of steel conductors as a To develop the positive- and negative-sequence induc-
function of current, and the tables on magnetic conductors tive reactance of three-phase aerial lines it is first necessary
such as Copperweld-copper, Copperweld, and ACSR con- to develop a few concepts that greatly simplify the
ductors include resistance tabulations at two current carry- problem.
ing levels to show this effect. These tabulated resistances First, the total inductive reactance of a conductor carry-
are generally values obtained by tests. ing current will be considered as the sum of two com-
Zero-Sequence Resistance-The zero-sequence re- ponents:
sistance of aerial conductors is discussed in detail in the *This figure has been taken from Symmetrical C@mponen& (a book)
section on zero-sequence resistance and inductive react- by C. F. Wagner and R. D. Evans, McGraw-Hill Book Company,
ante given later in the chapter since the resistance and in- 1933.
Chapter 3 Characteristics of Aerial fines

(1) The inductive reactance due to the flux within a radius of


one foot from the conductor center, including the flux
inside the conductor.
(2) The inductive reactance due to the flux external to a
radius of one foot and out to some finite distance.
This concept was first given in Wagner and Evans book on
Symmetrical Components2 and was suggested by W. A.
Lewis.‘8
It can be shown most easily by considering a two-con-
ductor single-phase circuit with the current flowing out in
one conductor and returning in the other. In Fig. 9 such a cir-
cuit is shown with only the flux produced by conductor 1 for
simplicity. Conductor 2 also produces similar lines of flux.
The classic inductance formula for a single round straight
wire in the two-conductor single-phase circuit is:
L=i+2 In 4 abhenries per cm. per conductor. (4)
where Fig. lo--Inductance due to flux between radius a and radius 6
(2 In k abhenries per cm.)
p = permeability of conductor material.
r = radius of conductor.
Dn=distance between conductor 1 and conductor 2. where i= inductance due to the flux inside the conductor.
Dr2 and r must be expressed in the same units for the above
equation to be valid. For practical purposes one foot is 2lnl= inductance due to the flux outside the conductor
used as the unit of length since most distances between ’ to a radius of one foot.
aerial conductors are in feet. In cable circuits, however,
the distance between conductors is less than one foot and 21nDy = inductance due to the flux esternal to a one foot
the inch is a more common unit (see Chap. 4). radius out to D12feet where D12is the distance
between conductor 1 and conductor 2.
From derivation formulas a general term such as 21n i
From Fig. 9 it can be seen that it is unnecessary to in-
represents the flux and associated inductance between clude the flux beyond the return conductor 2 because this
circles of radius a and radius Z, surrounding a conductor flux does not link any net current and therefore does not
carrying current. (See Fig. 10). affect the inductance of conductor 1.
Rewriting Eq. (4) keeping in mind the significance of the Grouping the terms in Eq. (5) we have:
general term 21n t, D12 abhenries per cm. per con-
L = %+dj+2hT ductor
(G)
L = ~+21n~+21nD~ abhenries per cm. per con- - -7-J
Ldueto L d,ue
ductor (5) flux out to flux
to a one external
ft. radi- to a 1
us ft. ra-
dius out
to Drzft.
Examining the terms in the first bracket, it is evident
that this expression is the sum of the flux both inside the
conductor I* and that external to the conductor out to
02
a radius of one foot 2lnl Furthermore this expression
( r>’
contains terms that are strictly a function of the conductor
characteristics of permeability and radius.
The term in the second bracket of Eq. (6) is an expres-
sion for inductance due to flux external to a radius of one
foot and out to a distance of D12,which, in the two-con-
ductor case, is the distance between conductor 1 and con-
ductor 2. This term is not dependent upon the conductor
characteristics and is dependent only upon conductor
spacing.
Fig. 9-A two conductor single phase circuit .(inductance) Equation (6) can be written again as follows:
36 Characteristics of Aerial Lines Chapter 3

Solid round conductor. ................................... 0.779a


Full stranding
7 ................................................... .0.72Ga
GMR in the first term is the condlictor “geometric mean 19....................................................0.758 a
radius”. It can be defined as the radius of a tubular con- 38. .................................................. .O.iBSa
ductor with an infinitesimally thin wall that has the same til....................................................O.i72 a
external flux out to a radius of one foot as the internal and 91....................................................0.77~~ a
external flux of solid conductor 1, out to a radius of one 127....................................................0.776 a.
foot. In other words, GMR is a mathematical radius Hollow stranded conductors and A.C.S.R.
assigned to a solid conductor (or other configuration such (neglecting steel strands)
as stranded conductors), which describes in one term the 30-two layer, .......................................... 0.82Ga
inductance of the conductor due to both its internal flux 26-twolayer...........................................0.809 a
54threelayer..........................................O.S10 a
z and the external flux out to a one foot radius 21nl . Single layer A.C.S.R. ............................... .0.35a-07Oa
0 ( r1 Point within circle to circle .................................... a
GMR therefore makes it possible to replace the two terms Point outside circle to circle. ........... distance to center of circle
Rectangular section of sides a and p ................ .0.2235(a+S)
which is entirely de-
CIRCULAR TUBE
pendent ‘upon the condu‘ctor characteristics. GMR is
expressed in feet. 1.00
Converting Eq. (7) to practical units of inductive
reactance,
2 = 0.2794-f log,, &+0.27946 log,, 4 0.95
60
ohms per conductor per mile (8)
where f =frequency in cps.
~ 0.90
GMR = conductor geometric mean radius in feet.
&=distance between conductors 1 and 2 in feet. 2
z
W
If we let the first term be called zn and the second term 0.85
zd, then
z=z.+zd ohms per conductor per mile (9)
where
0.80
xa= inductive reactance due to both the internal
flux and that external to conductor 1 to a radius
of one foot. _ ~
xd = inductive reactance due to the flux surrounding 0.756 0.2 0.4
’ 0.6 0.8 1.0
conductor 1 from a radius of one foot out to a INNER RADIUS
radius of D12feet. RATIO
OUTER RADIUS
For the two-conductor, single-phase circuit, then, the a* I/2 OUTSIDE DIAMETER
total inductive reactance is Fig. 11-Geometris Mean Radii and Distances.
.r=2(xD+xJ ohms per mile of circuit 00) PHASE o
since the circuit has two conductors, or both a “go” and
“return” conductor.
Sometimes a tabulated or experimental reactance with’
1 foot spacing is known, and from this it is desired to cal-
culate the conductor GMR. By derivation from Eq. (8)
G,\/IR = 1
feet. (11)
Antilog,o Reactancewith 1 ft spacing (60 cycles)
0.2794
When reactance is known not to a one-foot radius but out
to the conductor surface, it is called the “internal react-
ance.” The formula for calculating the GMR from the
“internal reactance” is:
physical radius
GMR = (12)
“Internal Reactance” (60 cycles) feet
Antilogi,, -
0.2794
The values of GMR at 60 cycles and xs at 25, 50, and ////////////////‘//////////////////
60 cycles for each type of conductor are given in the tables Fig. 12-A Three-conductor three-phase circuit (symmetrical
of electrical characteristics of conductors. They are given spacing).
Chapter 3 Characteristics of Aerial Lines 37

in these tables because they are a function of conductor Finally, considering only I, flowing in conductor c and
characteristics of radius and permeability. Values of xd returning by the same remote path g feet away.
for various spacings are given in separate tables in this &a=~d(ck)-xd(ea) (16)
Chapter for 25, 50, and 60 cycles. This factor is de-
nendent on distance between conductors only, and is not where xac is the inductive reactance associated with the
associated with the conductor characteristics in any way. flux produced by I, that links conductor a out to the return
In addition to the GMR given in the conductor char- path g feet away.
acteristics tables, it is sometimes necessary to determine With all three currents I,, Ib, 1, flowing simultaneously,
this quantity for other conductor configurations. Figure we have in terms of xs and xd factors:
11 is given for convenience in determining such values of Ea-Ec+’ = Ia(&+Zd(sk)) +I&d(bk) -%d(bn))

G&fR. This table is taken from the Wagner and Evans +rchd(ck) -xd(ca)). (17
book Symmetrical Components,page 138. Expanding and regrouping the terms we have:
Having developed 2, and 2,~in terms of a two-conductor, Ea--a’=~&,--bZd(t,a) -lcxd(c@
single-phase circuit, these quantities can be used to de- +[Irrxd(ak)+IbZd(bk)+leZd(ck)]. W3)
termine the positive- and negative-sequence inductive
reactance of a three-conductor, three-phase circuit. Since I,= -I,-Ib, the terms in the bracket may be
Figure 12 shows a three-conductor, three-phase circuit written
carrying phase currents I,, Ib, I, produced by line to ~ahd(ak) -Zd(ck)) +lbhd(bk) -xd(ck)) .

ground voltages E,, Eb, and E,. First, consider the case Using the definition of xd, 0.2794 &log?, thisexpression
Ivhcre the three conductors are symmetrically spaced in a
triangular configuration so that no transpositions are re- can be written
cluired to maintain equal voltage drops in each phase along
the line. Assume that the three-phase voltages E,, Eb, E,
are balanced (equal in magnitude and 120” apart) so that
Assuming the distances d(+, deck),and dcbk)to the remote
t,hey may be either positive- or negative-sequence volt-
ages. Also assume the currents I,, It,, I, are also balanced path approach infinity, then the ratios zs and ‘p
so that I,+Ib+ l,=O. Therefore no return current flows (ck) (ck)
in the earth, which practically eliminates mutual effects approach unity. Since the log of unity is zero, the two
between the conductors and earth, and the currents I,, terms in the bracket are zero, and Eq. (18) reduces to
I,>, I, can be considered as positive- or negative-sequence Ea - E,’ = Ia% - IbZd(ba) - Iczd(,,) (19)
currents. In the following solution, positive- or negative- since
sequence voltages E,, Eb, E,, are applied to the conductors xd(ba)=xd(ca)=xd(bc)=xd, and I,= -Ib-I,,
and corresponding positive- or negative-sequence currents E,-E,‘=Icr(xa+xd). (20)
are assumed to flow producing voltage drops in each con- Dividing the equation by I,,
ductor. The voltage drop per phase, divided by the cur- E,-EE,’
rent per phase results in the positive- or negative-sequence x1=x2= ----=z~fxd ohms per phase per mile (21)
inductive reactance per phase for the three-phase circuit. I,
TO simplify the problem further, consider only one current
where
Howing at a time. With all three currents flowing simul- x,=inductive reactance for conductor a due to the flux
taneously, the resultant effect is the sum of the effects pro- out to one foot.
tluced by each current flowing alone. xd=inductive reactance corresponding to the flux ex-
Taking phase a, the voltage drop is: ternal to a one-foot radius from conductor a out to
the center of conductor b or conductor c since the
E, - E,’ = laxaa+l,,xa~,+ Icx,c (13) spacing between conductors is symmetrical.
\vhcre
xX3.=self inductive reactance of conductor a. Thgefore, the positive- ,or negative-sequence inductive
x=b = mutual inductive reactance between con- reactance
_..----- - per
.. phase for a three-phase circuit with equi-
ductor a, and conductor b. lateral spacmg is the same as for one conductor of a single-
xac = mutual inductive reactance between con- phase-circuit as previously derived. Values of xB for vari-
ductor a and conductor c. ous conductors are given in the tables of electrical char-
acteristics of conductors later in the chapter, and the
In terms of x, and xd, inductive reactance spacing factor, values of xd are given in the tabIes of inductive reactance
%a= xa+xd(ak) (14) spacing factors for various conductor spacings.
where only I, is flowing and returning by a remote path e When the conductors are unsymmetrically spaced, the
feet away, assumed to be the point k. voltage drop for each conductor is different, assuming the
Considering only Ib flowing in conductor b and returning currents to be equal and balanced. Also, due to the unsym-
by the same remote path j feet away, metrical conductor spacing, the magnetic field external to
the conductors is not zero, thereby causing induced volt-
xnb=xd(bk) -Zd(bn) (15) ages in adjacent electrical circuits, particularly telephone
ivhere x& is the inductive reactance associated with the circuits, that may result in telephone interference.
-flux. . produced
^^ by Ib that links conductor a out to the return To reduce this effect to a minimum, the conductors are
path f ieet away. transposed so that each conductor occupies successively the
38 Characteristics of Aerial Lines Chapter 3

10 IE Ib Expressed in general terms,


5d==:(o.27Y4&-)(log d<l?)+log d<?J)+log d&

xd = + 0.279& log d1zdz3d31


I st SECTION 2nd SECTION 3rd SECTION
sd=0.2794-@f log Vtll2rE?3c/31
IO IC lb
1 A I - I
A
Ib xd= 0.2794& log GMD
- 2

k
3 where GMD (geometrical mean distance) = *a and
is mathematically defined as the nth root of an n-fold
Eo %’ E,,’ Ed* product.
I1 I II II For a three-phase circuit where the conductors are not
I
///////////////N////N/lllllllNllllllllll//// symmetrically spaced, we therefore have an expression for
Fig. 13-A Three-conductor three-phase circuit (unsymmet- the positive- or negative-sequence inductive reactance,
rical spacing). which is similar to the symmetrically spaced case except .x,1
is the inductive-reactance spacing factor for the GhID
same positions as the other two conductors in two successive (geometric mean distance) of the three conductor separa-
line sections. For three such transposed line sections, called tions. For xd, then, in the case of unsymmetrical conduct-
a “barrel of transposition”, the total voltage drop for each or spacing, we can take the average of the three indllctive-
conductor is the same, and any electrical circuit parallel to reactance spacing factors
the three transposed sections has a net voltage of very low xd = +(xd(12) +rd(23) +xd(31)) ohms per phase per mile
magnitude induced in it due to normal line currents.
In the following derivation use is made of the general or we can calculate the GMD of the three spacings
equations developed for the case of symmetrically spaced GMD = .\3/d,zd~3d31 feet (23)
conductors. First,, the inductive reactance voltage drop of
phase a in each of the three line sections is obtained. and use the inductive-reactance spacing factor for this
Adding these together and dividing by three gives the distance. This latter procedure is perhaps the easier of the
average inductive reactance voltage drop for a line section. two methods.
Referring to Fig. 13 and using Eq. (19) for the first line xn is taken from the tables of electrical characteristics of
section where I, is flowing in conductor 1, conductors presented later in the chapter, and xd is taken
NO.7
E, - E a’ = In& - Ibxd(12) - lc.xd(13).
NO.5
In the second line section where I,is flowing in conductor 2, NO.3
E: -E:’ = Inxa- I,,xd(z)- lerd(m. 1.0 NO.I
2fo
In the third line section where I, is flowing in conductor 3,
410
E,” -EL” = I&a - I,&(31) - 1,g~d(32). 300,000
Taking the average voltage drop per line section, we have 500,000
150,000
E =(E,-El)+@, -~a”)+(%“-%“‘) l,000,000
3Yg
3
=- 31,x, _ I b(xd(l?) +1-d;, fxd(31))
3
_Ic(Zd~12)+Zd(23)+Zd(31))

3 x-
‘l-8
x
$ 0.6
Since 5
t--
Is+Ib+I,=O, I,= - (IbfIc) ::
L
Zd(12) +zd(23) +xd(31) 0.5
E,,,=I,(x,+ 1.
3
Dividing by I,, we have the positive- or negative-sequence
inductive reactance per phase 0.4
2 3 4 5 7 IO 20 30 40
x1=x2= (&+xd) ohms per phase per mile EQUIVALENT CONDUCTOR SPACING-FEET

where Fig. 14-Quick reference curves for 60-cycle inductive react-


ance of three-phase lines (per phase) using hard drawn copper
xd = gxd(l2) +~d:2~) hd(313) ohms per phase conductors. For total reactance of single-phase lines multiply
per mile. (22) these values by two. See Eqs. (10) and (21).
Chapter 3 Characteristics of Aerial Lines

226,600
336,400
47 1,000
795,000
1,192,500
1,590,000

I 2 3 4 5 7 io 20 30 40
EOUIVALENT CONDUCTOR SPACING - FEET

Fig. Is-Quick reference curves for 60-cycle inductive react-


ance of three-phase lines (per phase) using ACSR conductors.
For total reactance of single-phase lines, multiply these
values by two. See Eqs. (10) and (21).
EQUIVALENT CONDUCTOR SPACING-FEET
94/2D
Fig. l7-Quick reference curves for 60-cycle inductive react-
I.1 ance of three-phase lines (per phase) using Copperweld con-
ductors. For total reactance of single-phase lines multiply
these values by two. See Eqs. (10) and (21).

from the tables of inductive-reactance spacing factors.


Geometric mean distance (GMD) is sometimes referred to
as “equivalent conductor spacing.” For quick reference
the curves of Figs. (l-l), (15), (IG), and (17) have been
plotted giving the reactance (x~+z~) for different con-
ductor sizes and “equivalent conductor spacings.”
Since most three-phase lines or circuits do not have con-
ductors symmetrically spaced, the above formula for posi-
tive- or negative-sequence inductive reactance is generally
used. This formula, however, assumes that the circuit is
transposed.
When a single-circuit line or double-circuit line is not
transposed, either the dissymmetry is to be ignored in the
calculations, in which case the general symmetrical com-
ponents methods can be used, or dissymmetry is to be con-
sidered, thus preventing the use of general symmetrical-
components methods. In considering this dissymmetry,
unequal currents and voltages are calculated for the three
phases even when terminal conditions are balanced. In
most cases of dissymmetry it is most practical to treat the
0.4
I 2 3 45 7 IO 20 30 40 circuit as transposed and use the equations for x1 and x2
EQUIVALENT CONDUCTOR SPACING-FEET derived for an unsymmetrically-spaced transposed circuit.
Some error results from this method but in general it is
Fig. 16-Quick reference curves for 60-cycle inductive react-
ance of three-phase lines (per phase) using Copperweld-
small as compared with the laborious calculations that
Copper conductors. For total reactance of single-phase lines must be made when the method of symmetrical compo.
multiply these values by two. See Eqs. (IO) and (21). nents cannot be used.
40 Charactekics of Aerial Lines Chapter 3

Positive- and Negative-Sequence Reactance of 00 00’


Parallel Circuits-When two parallel three-phase cir-
cuits are close together, particularly on the same tower, the
effect of mutual inductance betjveen the two circuits is
b0 Ob’
not entirely eliminated by transpositions. By referring to
Fig. 18 showing two transposed circuits on a single tower,
the positive- or negative-sequence reactance of the paral-
leled circuit is: CO oc
~dn,dx&n
21=x2 = 0.2794%f 3 logro Fig. l9-Arrangement of conductors on a single tower which
[ G~~IRconductor materially increases the inductance per phase.

-A 1oglo (li.,,)i~:ii;i:l:~~;db~,)”
ohms per phase per mile. (24)
1 ductors results in five to seven percent greater inductive
reactance than the usual arrangement of conductors. This
in which the distances are those between conductors in the has been demonstrated in several references.R
first section of transposition. 3. Zero-Sequence Resistance and Inductive Re-
The first term in the above equation is the positive- or actance
negative-sequence reactance for the combined circuits. The
second term represents the correction factor due to the The development of zero-sequence resistance and in-
ductive reactance of aerial lines will be considered simul-
taneously as they are related quantities. Since zero-se-
quence currents for three-phase systems are in phase and
equal in magnitude, they flow out through the phase con-
b b’ ductors and return by a neutral path consisting of the
earth alone, neutral conductor alone, overhead ground
wires, or any combination of these. Since the return path
often consists of the earth alone, or the earth in parallel
with some other path such as overhead ground wires, it is
necessary to use a method that takes into account the re-
00 OC sistivity of the earth as well as the current distribution in
t t/_
V’ the earth. Since both the zero-sequence resistance and
b0 _ 5 Ob’ inductive-reactance of three-phase circuits are affected by
2 these two factors, their development is considered jointly.
cd 00’ As with the positive- and negative-sequence inductive
FIRST SECTION
reactance, first consider a single-phase circuit consisting of
a single conductor groundecl at its far end with the earth
CO Ob’ acting as a return conductor to complete the circuit. This
permits the development of some useful concepts for cal-
00 00’
culating the zero-sequence resistance and inductive re-
actance of three-phase circuits.
Figure 20 shows a single-phase circuit consisting of a
b0 OC’
single outgoing conductor a, grounded at its far end with
SECOND SECTION
the return path for the current consisting of the earth. A
b0 00’
second conductor, b, is shown to illustrate the mutual
effects produced by current flowing in the single-phase cir-
cuit. The zero-sequence resistance and inductive reactance
co OC’
of this circuit are dependent upon the resistivity of the
earth and the distribution of the current returning in the
00 ob’ earth.
THIRD SECTION
This problem has been analyzed by Rudenberg, Mayr,
Fig. 18-Two parallel three-phase circuits on a single tower
showing transpositions.

mutual reactance between the two circuits and may reduce


the reactance three to five percent. The formula assumes
transposition of the conductor as shown in Fig. 18.
The formula also assumes symmetry about the vertical
axis but not necessarily about the horizontal axis.
As contrasted with the usual conductor arrangement as
shown in Fig. 18, the arrangement of conductors shown in Fig. 20-A single conductor single phase circuit with earth
Fig. 19 might be used. However, this arrangement of con- return.
Chapter 3 Characterzstics of Aerial fines 41

and pollaczek in Europe, and Carson and Campbell in this Rewriting Carson’s equations in terms of equivalent
country. The more commonly used method is that of depth of return, D,,
Carson, who, like Pollnczek, considered the return current z,=r,+O.OO159~+jO.OO4657f log,0 @&
to return through the earth, which was assumed to have
uniform resistivity and to be of infinite extent. ohms per mile. (W
The solution of the problem is in two parts: (1) the de-
termination of the self impedance z, of conductor a with z~~=0.00159~i-j0.004G5ijlog~0~ ohms per mile. (29)
Al)
(~rth return (the voltage between CLand earth for unit cur-
I~cnt in conductor CL),and (2), the mutual impedance zp, These equations can be applied to multiple-conductor
t)(;tn-ecn conductors n and b with common earth return circuits if r,, the GMR and d&brefer to the conductors as a
(the voltage between b and earth for unit current in a and group. Subsequently the GMR of a group of conductors
earth return). are derived for use in the above equations.
;\s a result of Carson’s formulas, and using average To convert the above equations to zero-sequence qunn-
]l(:ights of conductors nhovc ground, the following funda- tities the following considerations must be made. Con-
mental simplified equations may be written: sidering three conductors for a three-phase system, unit
.- zero-sequence current consists of one ampere in each phnsc
conductor and three amperes in the earth return circuit.
z,=r,+0.00159f+j0.004657f log,, CMR. To use Eqs. (28) and (29), replace the three conductors by
I a single equivalent conductor in which three amperes flow
ohms per mile (25) for every ampere of zero-sequence current. Therefore the
corresponding zero-sequence self and mutual impedances
per phase are three times the values given in Carson’s
2160 J ;
z,, = 0.00159f +jO.OO4657.f loglo d simplified equations. Calling the zero sequence imped-
nb ances zo and zOm,we have:
ohms per mile (26)
20=37-,+0.00477f+j0.01397$ log,, &R
rc = resistance of conductor a per mile. ohms per phase per mile. (30)
f =frequency in cps.
p=earth resistivity in ohms per meter cube. ,Qrn)=0.00477f+j0.01397”/” log,, 2
ab
GMR = geometric mean radius of conductor a in feet. ohms per phase per mile (31)
d,b = distance between conductors a and b in feet.
where f =frequency in cps.
A useful physical concept for analyzing earth-return r,=resistance of a conductor equivalent to the three
circuits is that of concentrating the current returning conductors in parallel. 3r, therefore equals the
through the earth in a fictitious conductor at some con- resistance of one conductor for a three-phase
siderable depth below the outgoing conductor a. This circuit.
ccluivnlent depth of the fictitious return conductor is rep- GMR=geometric mean radius for the group of phase
resented as D,. conductors. This is different than the GMR for
For the single-conductor, single-phase circuit with earth a single conductor and is derived subsequently
return now considered as a single-phase, two-wire circuit, as GMRclrcujt.
the self-inductive reactance is given by the previously de- d,b=distance from the equivalent conductor to a
rivedj0.2794%f loglo sR (See Eq. (8)) for a single-phase, parallel conductor, or some other equivalent
conductor if the mutual impedance between two
two-wire circuit, or jO.OO4657f log,, sR where D, is parallel three-phase circuits is being considered.
For the case of a single overhead ground wire, Eq. (30)
sllbstituted for D12, the distance between conductor a and gives the zero-sequence self impedance. Equation (31)
the fictitious return conductor in the earth. This expres- gives the zero-sequence mutual impedance between two
sion is similar to the inductive-reactance as given in overhead ground wires.
(‘arson’s simplified equation for self impedance. Equating
the logarithmic expressions of the two equations, Zero-sequence self impedance of two ground wires with
earth return
Using Eq. (30) the zero-sequence self impedance of two
j0.004657flog,o&~=j0.004657flog~o-- ground wires with earth return can be derived.
- GMR D,
20= 37-,+0.00477f+j0.01397j log,, __
I
or D,=21GO f? feet. GlMR
(27)
4 f ohms per phase per mile (30)
This defines D,, equivalent depth of return, and shows where T,= resistance of a single conductor equivalent to
that it is a function of earth resistivity, p, and frequency, f. the two ground mires in parallel. (r, therefore
Also an inspection of Carson’s simplified equations show becomes 2 where r, is the resistance of one of
that the self and mutual impedances contain a resistance
component O.O0159f, which is a function of frequency. the two ground wires).
42 Characteristics of Aerial Lines Chapter 3

GMR= geometric mean radius for the two ground transpositions. The expression for self impedance is then
wires. (GJIR therefore becomes converted to zero-sequence self impedance in a manner
*(GMR)2 cOnd,,etor
dxy2 or q/(G$IR) (dxy) analogous to the case of single conductors with earth
return.
where d,, is the distance between the two conductors Consider three phase conductors a, b, and c as shown in
5 and y.) Fig. 21. With the conductors transposed the current
Substituting ‘;; for r, and ~(GMR)(d,,) for GMR inEq.
(3O), the zero-seyuencc self impedance of two ground
wires with earth return becomes
zo= ~+0.004i7~+j0.01397~ log,, 2
D,
~(GMII) (dxy)
ohms per mile per phase. (32)
Zero-sequence self impedance of n ground wires with earth
return
Again using Eq. (30), the zero-sequence self impedance b
of n ground wires with earth return can be developed.
ze= 3r,+O.OO477j+jO.O1397j log,, gR
ohms per mile per phase. (30)
Since r, is the resistance of a single conductor equivalent to
n ground wires in parallel, then r, =5 n-here r, is the
n
-I
resistance of one of the n ground wires, in ohms per phase Fig. 21-Self impedance of parallel conductors with earth
return.
per mile.
GMR is the geometric mean radius of the n ground wires
as a group, which may be written as follows in terms of all divides equally between the conductors so that for a total
current of unity, the current in each conductor is one third.
possible distances,
The voltage drop in conductor a for the position in-
GMR= ‘q(GMR)” conductor (d~slsr)d~p,a.r)-d~ple,) dicated in Fig. 21 is
(d(s?s,)d(szp3)-d(gzen)(d(,,g,,d(gag?)-d(gJg.))
(d(,“g,)d(g,,gl)-d(6ng.-l) feet.
This expression can also be written in terms of all possible For conductor b:
pairs of distances as follows.

and for conductor c:


f+F+Y
The equation for zero-sequence self impedance of n ground
wires with earth return can therefore be obtained by sub-
in which z,,, zbb, and zCCare the self impedances of the’
stituting : for rC and Eq. (33) for GMR in Eq. (30). (: three conductors with ground return and z,b, ??bc,and zac
are the mutual impedances between the conductors.
Self impedance of parallel conductors with earth return Since conductor a takes each of the three conductor
positions successively for a transposed line, the average
In the preceeding discussion the self and mutual im- drop per conductor is
pedances between single cylindrical conductors with earth
return were derived from which the zero-sequence self and ~(z,,+Zbb+z~o+2z~b+2Zbc+22,3.
mutual reactances were obtained. These expressions were
expanded to include the case of multiple overhead ground Substituting the values of self and mutual impedances
wires, which are not transposed. The more common case given by Eqs. (28) and (29) in this expression,
is that of three-phase conductors in a three-phase circuit
which can be considered to be in parallel when zero-se- z,= f 3r,+9(0.00159f) +jO.O04657f 3 log,,- DE!
( GMR
quence currents are considered. Also the three conductors
in a three-phase circuit are generally transposed. This
factor was not considered in the preceeding cases for mul-
tiple overhead ground wires.
$2 log,, ds+2
ab
ohms per mile.
log,, ?+2
bc
log10
)I
In order to derive the zero-sequence self impedance of
three-phase circuits it is first necessary to derive the self
impedance of three-phase circuits taking into account ohms per mile.
Chapter 3 Characteristics of Aerial Lines 43

The ninth root in the denominator of the logarithmic term Zero-sequence self impedance of two idel2tical parallel cir-
is the GMR of the circuit and is equal to an infinitely thin cuits with earth return
tube which would have the same inductance as the three- For the special case where the two parallel three-phase
conductor system with earth return shown in Fig. 21. circuits are identical, following the same method of
GMRclrcult= ~(G~IR)R,,,d,,t,, dab2&c2dCa2 feet. derivation
mRelrcult= +(Gi\/lR)aCOndUCtOr (dabdbcdca)’ feet. D,
20= ~+0.00477j+~0.01397j log,, d(GLIR) (G;\ID)
G&IRc,rcu,t= YGMR conductor(~d,bdb,d..) 2 feet.
ohms per phase per mile (39)
By previous derivation (See Eq. (23)), GiCIDSeparatlo,,
in which GMR is the geometric mean radius of one set of
=SG&Zii feet.
conductors, (~(GR/lR)conductor(GMD)2separation ), and GMD
Therefore GMRClrcu,t= l’(G~IR)COndllCtOT(G~ID)fseparntlon is the geometric mean distance between the two sets of
rcet. (35) conductors or the ninth root of the product of the nine
possible distances between conductors in one circuit and
Substituting GMR,,,,,,, from equation (35) in equation conductors in the other circuit.
04, This equation is the same as ~(z~+z~~,,,J where z. is
z,=~+o.o0159j the zero-sequence self impedance of one circuit by equa-
tion (37) and ~0~~)is the zero-sequence mutual impedance
D, between two circuits as given by Eq. (38). For non-
+‘“‘oo4657j log” ~(G~IR),,,~,,~,,(GMD)?,,*,,,~,,, identical circuits it is better to compute the mutual and
ohms per mile. (36) self impedance for the individual circuits, and using
$(~o+zo~,,,,) compute the zero-sequence self impedance.
In equations (34) and (36), rC is the resistance per mile of
one phase conductor. Zero-sequence mutual impedance between one circuit (with
earth return) and n ground wires (with earth return)
Zero-sequence self impedance of three parallel conductors
with earth return Figure 22 shows a three-phase circuit with n ground
Equation (36) gives the self impedance of three parallel
conductors with earth return and was derived for a total Ql
l Q: Q:
current of unity divided equally among the three con-
ductors. Since zero-sequence current consists of unit cur-
rent in each conductor or a total of three times unit current 0a B
l’or the group of three conductors, the voltage drop for
zero-sequence currents is three times as great. Therefore
lXq. (36) must be multiplied by three to obtain the zero-
sequence self impedance of three parallel conductors with
cxth return. Therefore,
20 = r,+O.O0477f
lJ/GMR D,
+.m=w log10 Fig. 22-A three-conductor
return) and n ground
three-phase circuit (with earth
wires (with earth return)
eOndllCtOt.(GMD)‘~eparation
ohms per phase per mile (37)
wires. Equation (31) gives the zero sequence mutual im-
where ~GMR,,,d,,t,,(GMD)2,,Daratlon
istheGMR,L~~~I~
de- pedance between two conductors:
rivcclin equation
(35) or ~(GMR)3conductor dnb2dbc2dca2
Z()(m)=o.oo477j+jo.o1397j log,, 2
Zero-sequence mutual impedance between two circuits with nb

earth return ohms per phase per mile (31)


Using a similar method of derivation the zero-sequence where dabis the distance between the two conductors. This
mutual impedance between 2 three-phase circuits with equation can be applied to two groups of conductors if
common earth return is found to be d,b is replaced by the GMD or geometric mean distance
between the two groups. In Fig. 22, if the ground wires are
~O,rn)
= 0.00477f +jo.o1397j log,, SD considered as one group of conductors, and the phase con-
ductors a, b, c, are considered as the second group of con-
ohms per phase per mile (3% ductors, then the GMD between the two groups is
\+re GMD is the geometric mean distance between the
2 three-phase circuits or the ninth root of the product of GMD = 3i/dagldbgldc&l-dagndb~~d~~~ feet
the nine possible distances between conductors in one Substituting this quantity for d,b in Eq. (31) results in an
group and conductors in the other group. Note the simi- equation for the zero-sequence mutual impedance between
larity between Eq. (38) and Eq. (31) one circuit and n ground wires. This .+,,) is z,,(,~).
44 Characteristics of Aerial Lines Chapter 3

General Method for Zero-Sequence Calculations


-The preceding sections have derived the zero-sequence
self and mutual impedances for the more common circuit
arrangements both with and without ground wires. For
ohms per phase per mile. (40) more complex circuit and ground n-ire arrangements a
Zero-sequence impedance of one circuit with n ground wires
(and earth) return.
Referring to Fig. 20 the zero-sequence self impedance of
a single conductor, and the zero-sequence mutual im-
pedance between a single conductor and another single
conductor with the same earth return path was derived.
These values are given in Eqs. (30) and (31). As stated be-
fore, these equations can be applied to multi-conductor
circuits by substituting the circuit GMR for the conductor Fig. 23-Equivalent circuit for zero-sequence impedance of
GMR in Eq. (30) and the GMD between the two circuits one circuit (with earth return) and n ground wires (with earth
for d,b in Eq. (31). return).
First, consider the single-conductor, single-phase circuit
lvith earth return and one ground wire with earth return. general method must be used to obtain the zero-sequence
Referring to Fig. 20 conductor a is considered as the single impedance of a particular circuit in such arrangements.
conductor of the single-phase circuit and conductor b will The general method consists of writing the voltage drop
be used as the ground wire. for each conductor or each group of conductors in terms of
Writing the equations for E, and Eb, we have: zero-sequence self and mutual impedances with all con-
E, = Ia&.a+IbZm (41) ductors or groups of conductors present. Ground wire
conductors or groups of conductors have their voltage
Eb = I&n+IbZbb. (48 drops equal to zero. Solving these simultaneous equations
If we assume conductor Z,as a ground wire, then & = 0
since both ends of this conductor are connected to ground. for F of the desired circuit gives the zero-sequence im-
Therefore solving Eq. (42) for Ib and substituting this pedaice of that circuit in the presence of all the other zero-
value of lb in Eq. (41), sequence circuits.
. This general method is shown in detail in Chap. 2,
Part X, Zero-Sequence Reactances. Two circuits, one
To obtain z,, divide E, by I,, and the result is with two overhead ground wires and one with a single over-
2
head ground wire are used to show the details of this more
Za=Zaa-~ (43) general method.
Zbb Practical Calculation of Zero-Sequence Imped-
The zero-sequence impedance of a single-conductor, single- ance of Aerial Lines-In the preceding discussion a
phase circuit with one ground wire (and earth) return is number of equations have been derived for zero-sequence
therefore defined by Eq. (43) when zero-sequence self im- self and mutual impedances of transmission lines taking
pedances of single-conductor, single-phase circuits are sub- into account overhead ground wires. These equations can
stituted for zlla and %bband the zero-sequence mutual im- be further simplified to make use of the already familiar
pedance between the two conductors is substituted for z,. quantities r,, xn, and xd. To do this two additional quan-
Equation (43) can be expanded to give the zero-sequence tities, r, and x, are necessary that result from the use of the
impedance of a three-phase circuit with n ground wires earth as a return path for zero-sequence currents. They
(and earth) return. are derived from Carson’s formulas and can be defined as
zo2w follows:
20= ZO(Il)- - (44)
zwa r,=O.O0477f ohms per phase per mile.
Where zo= zero-sequence impedance of one circuit with n ze = 0.006985f log,, 4.6655 X 106Eohms -per phase per
ground wires (and earth) return. f
zO(n)= zero-sequence self impedance of the three- mile. (46)
phase circuit. It is now possible to write the previously derived equations
zotej=zero-sequence self impedance of n ground for zero-sequence self and mutual impedances in terms of
wires.
ra, ‘X,, xd, r,, and 2,. The quantities r,, za, zd are given
zocapj= zero-sequence mutual impedance between the in .the tables of Electrical Characteristics of Conductors
phase conductors as one group of conductors and Inductive Reactance Spacing Factors. The quantities
and the ground wire(s) as the other conductor r, and x8 are given in Table 7 as functions of earth
group. resistivity, p, in meter ohms for 25, 50, and 60 cycles per
Equation (44) results in the equivalent circuit of Fig. 23 second. The following derived equations are those most
for determining the zero-sequence impedance of one circuit commonly used in the analysis of power system prob-
with n ground wires (and earth) return. lems.
Chapter 3 Characteristics of Aerial Lines 45

zero-sequence impedance-one circuit (with earth return) Zero-sequence self impedance-n ground wires (with earth
but without grolrnd wires return)
z. = rc+0.004i7J”
20~~)
= 3r,+0.00477~+j0.01397~ log10 &
D.?
+j0.013!~i”f log,, ~
g(Gh’IR) COnd”Ct”T(G~ID)*sepnrat,on ohms per phase per mile (30)
ohms per phase per mile. (37)
where r0=T” ohms per phase per mile.
z,,= r,,+r,+jO.OOG9SJ” log,, 4.6G5GX 106:
J GMR =n&GNIR)n c”r,duetor(dalrr’L(~glgR
- - - 4kJ (b&~R
1 - - - dg2gn)(dg3gdg3q2
- - - dp3gn)(4mdgn$!z- - -4nw--lJ
+jo.2794& log10 -
1 GMR COlld”COX
zocgj=3$+r,i-jx,+j~(0.2i94)$ log,,, 4.665X lo@
-j2(0.2794i log,, GMD,,Darat,oJ f
.3 f 1
~,,=r,+r,+j(~~+x,-2x,1) ohms per phase per mile (47) +$“.2ig4)~ log” (G~R)~,,,du,t,,

\vhcre l’d = +(xd(uh) +Zd<hc)+Zd(ea))


:tncl :rCICCri,)
=xd from Table 6 for spacing czto h, etc.

.\[,llt~cll zero-sequence impedance hetween two circuits (with


elrrth retlrrn) but without ground wires
z0(gj = %,+r,+j(z,+*-“o.cd)
n n n
Z,,(,,,)= 0.00477”r+j0.01397jIoglo G&D ohms per ohms per mile per phase (51)
phase per mile. (33)
where xd=---- sum of 2dsSfor all possible distances
z,,,,,,)= r,+jO.O06985f log,, 4.6G5X 106p
I between all ground wires.)
-jO.O06985j log,, GiLID*
%ll) = r,j+.j(x,-3zJ ohms per phase per mile (43) or xd= ~ 2 (sum of xd’s for all possible distances
n(n-1)
Where zd is +(xd(aal) fZd(ah,)+Zd(nc))+2d,ba,)+Zd~bb,) between all possible pairs of ground wires).
+Zd(bc,)+Zd(cn,)+5d(cb,)+2d(cc’))
Zero-sequence mutual impedance between one circuit (with
%cro-sequence self impedance-one ground wire (with earth
earth return) and n ground wires (with earth return)
rdurn)
.zO(;IK)
= 0.00477f
L^,)(,$
=37-,+0.00477f+j0.01397~ log10&
conductor D, -____
+jO.O139if loglo 3n
ohms per phase per mile. (30) V &,&w&r - - d,,ndt,,nd,,,
ohms per phase per mile. (40)
a,(,,, = 3, at/-e.~U.UUUYO.,J IUg:,,4.6656X lo@
f 20~~~) = r,i-jO.OO6985f loglo 4.6656x lo6 p
1 f
+“‘oo6g85f 1og10(Gh~R)2,,,d”~t,,
-jO.OO6985j log,, ($Tagldb&cF1- - -dngnd,,gndcgn)’
a~(~)= 3r,+r,+j(x,+3x,) ohms per phase per mile. (49) Zocae)=r,+j(z,--kd) ohms per phase per mile (52)
G).o sequence self impedance-two ground wires (with earth 1
where Zd=-(Zd(nal)+xd(bgl)+2d(cgl)
return) 3n
--- +xd(nCn)+2d(bsn)+xd(cyn) 1.
=w = ~+0.00477~+j0.01397~ loglo D,
~/(G~IR),,,,,iuctordxy Zero-sequence impedunce-One circuit with n ground wires
ohms per phase per mile. (32) (and earth return,)

%:I =~+r,+j0.0069S5~loglo 4.665GX 10” : al*@&9


ZO=ZO(n)- ~ (44)
h4)
where zOCn)
=zero-sequence self impedance of the three-
phase circuit.
=zero-sequence self impedance of n ground
zoCg)
wires.
oilms per phase per mile (50) ~0~~~~
= zero-sequence mutual impedance between the
\Vllere three-phase circuit as one group of conductors
Q=xd from Table 6 for spacing between ground and the ground wire(s) as the other con-
wires, dxy. ductor group.
46 Characteristics of Aerial Lines Chapter 3

4. Positive-, Negative-, and Zero-sequence Shunt This equation shows the work done in moving a unit
Capacitive Reactance charge from conductor 2 a distance D12meters to the sur-
The capacitance of transmission lines is generally a face of conductor 1 through the electric field produced by
negligible factor at the lower voltages under normal oper- ql. Now assuming only conductor 2, having a charge q~,
ating conditions. However, it becomes an appreciable the voltage between concluctors 1 ancl 2 is
effect for higher voltage lines and must be taken into con-
sideration when determining efficiency, power factor, VIZ= 18X lo9 @ In $ volts. (55)
regulation, and voltage distribution under normal oper- 12
ating conditions. IJse of capacitance in determining the This equation shows the work done in moving a unit
performance of long high voltage lines is covered in detail charge from the outer radius of conductor 2 to conductsor 1
in Chap. 9, “Regulation and Losses of Transmission a distance D12 meters away through the electric field pro-
Lines.” duced by q2.
Capacitance effects of transmission lines are also useful With both charges q1 and q2 present, by the principle of
in studying such problems as inductive interference, light- superposition the voltage VIZ is the sum of t$he voltages
ning performance of lines, corona, and transient’s on power resulting from q1 and q2 existing one at a time. Therefore
systems such as those that occur during faults. VI2 is the sum of Eqs. (54) and (55) when both charges ql
For these reasons formulas are given for the positive-, and q2 are present.
negative-, and zero-sequence shunt capacitive reactance
for the more common transmission line configurations. The VI2 = 18 X lo9 q1 ln h+qz ln $ volts.
case of a two-conductor, single-phase circuit is considered r 12

to show some of the fundamentals used to obtain these Also if the charges on the two conductors are equal and
formulas. For a more detailed analysis of the capacitance their sum is zero,
problem a number of references are available. 2*4*5.
In deriving capacitance formulas the distribution of a ql+q2=0 or q2= --Ql
charge, q, on the conductor surface is assumed to be uni- Substituting -ql for qz in equation (56)
form. This is true because the spacing between conductors
in the usual transmission circuit is large and therefore the VI2 = 36 X 10gql In 5 volts. (57)
charges on surrounding conductors produce negligible dis- r
tortion in the charge distribution on a particular con- The capacitance between conductors 1 and 2 is the ratio of
ductor. -41~0,in the case of a single isolated charged con- the charge to the voltage or
ductor, the voltage between any two points of distances x 1
and 2/meters radially from the conductor can be defined as +c,= farads per meter. (58)
12
the work done in moving a unit charge of one coulomb from 36X log In *f
point PZ to point P1 through the electric field produced by
the charge on the conductor. (See Fig. 24.) This is given The capacitance to neutral is twice that given in Eq. (58)
because the voltage to neutral is half of VIZ.
1
C,= farads per meter. (59)
18X log In *f

The shunt-capacitive reactance to neutral (or per con-


1
ductor) is xcn= - or in more practical units
2rjc
CONDUCTOR I CONDUCTOR 2 x,,=O.O6837 log,,, *f megohms per conductor per
Fig. 24-A two conductor single phase circuit (capacitance).
mile. (60)
This can be written as
X en=0.0683: log,, ;+0.0683? log,,+
Vx,= 18X log q In s volts *
(53) megohms per conductor per mile 031)
where q is the conductor charge in coulombs per meter. where D12 and r are in feet and j is cycles per second.
By use of this equation and the principle of superposi- Eq, (61) may be written
tion, the capacitances of systems of parallel conductors can
be determined. x,,=x:+x; megohms per conductor per mile. (62)
Applying Eq. (53) and the principle of superposition to The derivation of shunt-capacitive reactance formulas
the two-conductor, single-phase circuit of Fig. 24 assuming brings about terms quite analogous to those derived for
conductor 1 alone to have a charge 41,the voltage between inductive reactance, and as in the case of inductive react-
conductors 1 and 2 is ance, these terms can be resolved into components as
shown in Eq. (62). The term xa’ accounts for the electro-
VIZ = 18X lo9 q1 In *$ volts. (54) static flux within a one foot radius and is the term
Chapter 3 Characteristics of Aerial Lines 47

where
0.0683 y log,, ‘, in Eq. (61). It is a function of the con-
--% sum of all xd’s for all possible distances
ductor outside radius only. The term zd’ accounts for the xd’= n(n-1)
electric flux between a one foot radius and the distance between all possible pairs of ground mires)
D,? to the other conductor and is the term 0.0683 s log,,, orxd’=- l (sum of all xd’s for all possible distances
n(n-1)
Dl2 in Eq. (61). Note that unlike inductive-reactance between all ground wires).
r (f) Zero-Sequence xc between one circuit (and earth)
\vhcre the conductor geometric mean radius (GMR) is and n ground wires (and earth)
,,scd, in capacitance calculations the only conductor radius X6(,,) = zd - 32: megohms per conductor per mile. (70)
used is the actual physical radius of the conductor in feet.
Zero-sequence 1
. . capacitive reactance is, like inductive- xd’= - (Zd)(na,) +xd’(i,g,) +xd’,,,,, * * * +r,;,:,,,,
rractance, divided into compocents 2,’ taking into account 3n
the ,clectrostatic flux within a one-foot radius, xd’ taking +xdl(bqn)+x;(cgn) 1.
into account the electrostatic flux external to a radius of (g) Zero-Sequence xc of one circuit with n ground wires
c,nc foot out to a radius D feet, and x,’ taking into account
xO)m2
th(: flux external to a radius of one foot and is a function xd = XII’(S)-- megohms per conductor per mile. (71)
of the spacing to the image conductor. XdW
, _ 12.30 Shunt Capacitive Reactance, xc, of Single-Phase Circuits
X0 -- log,, 2h megohms per mile per
f (Conductors a and b)
conductor (63) (h) xc of single-phase circuit of two identical conductors
\vhcrc h = conductor height above ground. x’=~(x:+x,/) megohms per mile of circuit. (72)
f =frequency in cps. xd’=xd’ for spacing between conductors.
a,,’ is given in the tables of Electrical Characteristics of
c*ontluctors, zd’ is given in Table 8, Shunt-Capacitive (i) xc of single-phase circuit of two non-identical con-
l&ctance Spacing Factor, and xl is given in Table 9, ductors a and b.
Zero-Sequence Shunt-Capacitive Reactance Factor. x’=x,I~,~+x,)~~~+2xd) megohms per mile of circuit. (‘73)
The following equations have been derived in a manner (j) x, of one conductor and earth.
similar to those for the two-conductor, single-phase case, x’ = x1 ++x,l megohms per mile. 04
making use of the terms x:,‘, xd’ and x:d. They are sum-
marized in the following tabulation. In using the equations it should be remembered that the
shunt capacitive reactance in megohms for more than one
Shunt-Capacitive Reactance, xc, of Three-Phase Circuits mile decreases because the capacitance increases. For more
(Conductors a, b, c) than one mile of line, therefore, the shunt-capacitive re-
(a) Positive (and negative) sequence xc. actance as given by the above equations should be divided
xi = xi =x:+x: megohms.per conductor’permile. (64) by the number of miles of line.
1 5. Conductor Temperature Rise and Current-
xJ=$sum of all three xd’s for distances between all
Carrying Capacity
possible pairs).
In distribution- and transmission-line design the tem-
=&L+x;;.c+ zdbc). See Table (8) perature rise of conductors above ambient while carrying
(65) current is important. While power loss, voltage regula-
(1)) Zero-Sequence xe of one circuit (and earth). tion, stability and other factors may determine the choice
Q’(~,= x:+x,‘-256 megohms per conductor per of a conductor for a given line, it is sometimes necessary to
mile. consider the maximum continuous current carrying capa-
(W
xd’=value given in Eq. (65). Table (9) gives z:. city of a conductor. The maximum continuous current
rating is necessary because it is determined by the mas-
(c) Zero-Sequence xc of one ground wire (and earth). imum operating temperature of the conductor. This tem-
x:(,1 =3x:(,)+x,‘(,) megohms per conductor per perature affects the sag between towers or poles and de-
mile. (67) termines the loss of conductor tensile strength due to
(d) Zero-Sequence xc of two ground wires (and earth). annealing. For short tie lines or lines that must carry
3 3 excessive loads under emergency conditions, the maximum
2 o’(,,=-x,l(,,+~J(~) --xd’ megohms per conductor per
2 2 continuous current-carrying capacity may be important
mire. 63) in selecting the proper conductor.
xd’= x~‘(~I~?) = xd’ for distance between ground wires. The following discussion presents the Schurig and FrickC
formulas for calculating the approximate current-carrying
(e) Zero Sequence xc of 11ground wires (and earth). capacity of conductors under known conditions of ambient
x;(,) =x:+?x:-“(“-l) -xd megohms per conductor per temperature, wind velocity, and limiting temperature rise.
71 n The basis of this method is that the heat developed in
mile (69) the conductor by 12R loss is dissipated (1) by convection
48 Characteristics of Aerial Lines Chapter 3

in the surrounding air, and (2) radiation to surrounding 1000


900 I I I I I I I I I I I
objects. This can he expressed as follows: 800 II I , I I / I I I I I
I I I I I I I I I I I I
I?R= (W,+W,).d watts. (75) 700

\vhere I = conductor current in amperes.


R = conductor resistance per foot.
It’, = Irntts per square inch dissipated by convwtion.
TV, = watts per square inch dissipated by radiat,ion.
A = conduct,or surface area in sqllare inches per foot
of length.
The lvntts per sqllare inch dissipated by convection, WC,
can be determined from the following equation:

7’,0.12”& At watts per square inch


w ~0.0128~/pn

c- (76)

\\here p=pressure in atmospheres (p= 1.0 for atmo-


spheric pressure).
v = velocity in feet per second.
T,= (degrees Kelvin) avcragc of absolute temper-
atures of conductor and air.
d = outside diameter of conductor in inches.
At = (degrees C) tcmpcrature rise.
This formula is an approximation applicable to con- 0’ IO’ 20’ 30” 40’ 50’ 60’
ductor diameters ranging from 0.3 inch to 5 inches or more AMBIENT TEMPERATURE “C
when the velocity of air is higher than free convection air
currents (0.2-0.5 ft jsec). Fig. 25-Copper conductor current carrying capacity in Am-
The watts per square inch dissipated by radiation, IV,, peres VS. Ambient Temperature in ‘C. (Copper Conductors at
can be determined from the following equation: 75 “C, wind velocity at 2 fps.).

,,,=3+(&~-(&)P]
watts per square inch (77) lOOOr
900
n-here E = relative emissivity of conductor surface 000
(E= 1.0 for “black body,” or 0.5 for average 700 I
: I
oxidized copper). EL’ ”
T = (degrees Kelvin) absolute temperature of con-
ductor.
To= (degrees Kelvin) absolute temperature of sur-
roundings.
By calculating (W,+ W,), -4, and R, it is then possible
to determine I from Eq. (75). The value of R to use is the
a-c resistance at the conductor temperature (ambient
temperature plus temperature rise) taking into account
skin effect as discussed previously in the section on pos-
itive- and negative-sequence resistances.
This method is, in general, applicable to both copper
and aluminum conductors. Tests have shown that alum-
inum conductors dissipate heat at about the same rate as
copper conductors of the same outside diameter when the
temperature rise is the same. Where test data is available
on conductors, it should be used. The above general 60.
\ I
Y
method can be used when test data is not available, or to
50
check test results.
The effect of the sun upon conductor temperature rise is .-
generally neglected, being some 3” to 8°C. This small 0’ IO’ 20. 30’ 40’ 50’ 60’
effect is less important under conditions of high tempera- AMBIENT TEMPERATURE ‘C

ture rise above ambient.” Fig. 26-Aluminum conductor current carrying capacity in
The tables of Electrical Characteristics of Conductors Amperes VS. Ambient Temperature in “C. (Aluminum Con-
include tabulations of the approximate maximum current- ductors at 75”C, wind velocity at 2 fps).
Chapter 3 Characteristics of Aerial Lines 49

TABLE ~-CHARACTERISTICS OF COPPER CONDUCTORS, HARD DRAWN, 97.3 PERCENT CONDUCTIVITY


,
‘-a JAI
Pizc Of Resistance 2, Shunt Capacitive
Conductor Ohms per Conductor per Mile lnductivc Resctnncr Rcactnnce
reakirlr Ohms per Conductor Mrqohms per
trc!nRtl Per AIile COIldUCt,Or
‘OWKIS At 1 Ft. Spacing Per Mile
25°C. (77°F.) 50°C. (122°F.) .it 1 Ft Soacinv
9- 50 =I 25 ( 50 1 60 ) 25 1 50' 1 60
d-e y,L cycles cycles cycles cycles cycles cycles cyclen
--~ ycles

Ii 0.1644 1 151 9 3001 300 0.03G8 0.0583’0.05940.06200.063- 0.0641 .06480.067 .06850.16660.333 0.400 0.216 0.10810.0901
170.15601.092 i 6701 220 0.0349 0 Oli30’0.06R80.06820.069. 0.071 .07180.0741 .07520.lH930.339 0.406 0.220 0.11000.091F
17 0.14701.029 ? 0401 130 0.0329 0.0801 .08000.0821 .08370.17220.344 0.413 0.2?& 0.11210.0934
:70.14210.w7 2 2301 090 0.0319 0.0731~0.07390.07600.077:
0.07800.07870.08070.081~ 0.085: .08590.08i, 08880.17390.348 0.417 0.226 0.11320.0343
I I
71,” 000 Ii0 13750 9lX 11 170 040 0.0308 0.083610.08420.08610.087 0.091 .09200.083 .09470.17590.3.52 0.422 0.229 0.11450.09.54
1,110 001) li 0. I273O.X!ll 27 020 940 0 0285 0.0975’0.09810.09970.100f 0.106l .10710.108' .10950 17990.360 0.432 0.235 ,0.11730.0977
51,” 000 17 ll.llfi?O 814 ?2 ,510 840 0.0260 0.11700.117.50.11880.119~ 0.1281 1283 0. 12'9 .13030.18450.369 0:143 0 241 0.12050.1004
,;“I, OOII !J 0. 16220.811 21 590 8-10 0.0256 0.11700.11750.11880.119~ 0.1281 :12830.129 .13030.18530.371 0.445 0 241 0.12060.1005
I i
.I.,” l)OO !)0.15390.770 19 750 7 336 0 142: 14260.143 .14430.18790.376 0.4.il 0.245 ,0.1?240.1020
IO0 000 .!I 0. 14.51 0. i26 17 3fiO li .I2 1 O.lciOl :1603O.lGl .161!10,19090.382 0.458 0 24!f ,O 12430.1038
:i.-d, 000 .‘J 0. 1.357 0. fai!? 15 590 5 706 0.1821 .18310.184 .18450.19430 389 0.406 0.2.54 ~0.121i90.10.58
::.iO 000 .20.17080.710 15 140 5 706 0.182, .18310.184 .18450.19180.384 ;0.460 0.251 ,0.125:30.1044

Z!,,f, Ol1” .9 0 12SiO (i2!1 4 891 610 0 019870.19500.19530.19610.196~ 0.213 .214 0.214
- 610 0.0208 0 19300.19530 19610.1961
:,c,o OIIO 20.1381O.(i37 :; % 4 801 0.213 214 0.214
L’.-,II 000 .!~0.1147O.Tri-I ii 360 4 076 540 0.018130 234 0 234 0.235 0.235 0.256 :256 0 2Si
L’.jo 000 2 0.144:10.600 11 130 4 076 540 0.019020.234 0.234 0.235 0.235 0.256 ,256 0.257
21, Iill" l/C , ,!I” lOi.iO 528 9 617 480 0.016680.276 0.277 0.277 0.278 0.302 .303 0 303
2, I Ii00 4,'C ) I20 IA80 k2 9 483 490 0.017500.276 0.277 0.277 0.278 0.302 ,303 0.303
2, I ,io,, 4/c I 7 0 173'30 52% 9 1.54 480 0.015700.276 0.277 0.277 0.278 ,303 0.303
lli7 800 3; LI 12 0.11830.4!)2 7 5.56 420 0.01.5.590.349 0.349 0.349 0.350 E"8? ,381 0.382
710 15480.46-l 7 366 2 736 420 0.014040.349 0.349 0.349 0.350 0.381 .381 0.382
7!O.l37!~0.414 5 926 2 17c 360 0.012520.440 10.440 0.440 0.440 0.481 ,481 0.481
7 0.12280.368 4 752 1 720 310 0.01113 0.555 ,0.355 0.555 0.555 0.606 ,607 0.607
iO.lO'J30.328 3 804 1 364 270 0.00992O.tiSO 0.699 0.699 0.699 0.765

30.16700.360 / 3 620 0.692 0.757


7 0 09740 292 3 04s 0.882 0.964
3 0, 1487 0 :320 2 913 0.955
1 0 2.58 3 003 0.945
7 0 08li70 260 , 2 433 858 1.216
3 0.13250.285 2 350 8JO 1.204
1 0.22!1 2 430 841 1.102
:30.11800.254 1 879 674 1.518
1 .0.204 1 970 667 170 0.00663 1.374 1.503
30.10~00.22rj 1 505 534 150 0.00638 1.750 1.914
'!I 1 591 s29 140 0.00590 1.733 1.895
i o.o!i35i%: 1 205 424 130 0.00568 2.21 2.41

1 0.162 1 280 420 120 0.00526 2.18 2.39


1 0.144 L! 1 030 333 110 0.00488 2.75 3.01
1 0.128 5 826 264 90 0 00417 3.47 3.80
- - 1.
li For conductor at 73”C., air at 25°C.. wind 1.4 miles per hour (2 it/xc), frequency=60 cycles.

carrying capacity based on 50°C rise above an ambient of perature may be obtained that approaches lOO’C, the con-
WC, (75°C total conductor temperature), tarnished sur- ductor manufacturer should be consulted for test data or
I’xc (E=O.5), and an air velocity of 2 feet per second. These other more accurate information as to conductor tempera-
conditions were used after discussion and agreement with ture limitations. Such data on copper conductors has been
t.hc conductor manufacturers. These thermal limitations presented rather thoroughly in the technical literature.7
arc based on continuous loading of the conductors.
The technical literature shows little variation from these III
TABLES OF CONDUCTOR
conditions as line design limits.’ The ambient air tem- CHARACTERISTICS
Iwature is generally assumed to be 25°C to 40°C whereas The following tables contain data on copper, ACSR,
1ho temperature rise is assumed to be 10°C to GO”C. This hollow copper, Copper-weld-copper, and Copperweld con-
gives a conductor total temperature range of 35°C to ductors, which along with the previously derived equations,
tOO”C. For design purposes copper or ACSR conductor permit the determination of positive-, negative-, and zero-
total temperature is usually assumed to be 75°C as use of sequence impedances of conductors for use in the solution
this value has given good conductor performance from an of power-system problems. Also tabulated are such con-
annealing standpoint, the limit being about 100°C where ductor characteristics as size, weight, and current-carrying
annealing of copper and aluminum begins. capacity as limited by heating.
Using Schurig and Frick’s formulas, Fig. 25 and Fig. 26 The conductor data (r,, z., 2,‘) along with inductive and
have been calculated to show how current-carrying capa- shunt-capacitive reactance spacing factors (zd, zd’) and
city of copper and aluminum conductors varies with am- zero-sequence resistance, inductive and shunt-capacitive
bient temperature assuming a conductor temperature of reactance factors (r,, r,, 5,‘) permit easy substitution in
75.C and wind velocity of 2 feet per second. These values the previously derived equations for determining the sym-
are conservative and can be used as a guide in normal line metrical component sequence impedances of aerial circuits.
d esign. For those lines where a higher conductor tem- The cross-sectional inserts in the tables are for ease in
Characteristics of Aerial Lines Chapter 3

TABLE ~-A-CHARACTERISTICSOF ALUMINUM CABLE STEEL REINFORCED


(Aluminum Company oflAmerica)

I
ra 2”
j I Reastanco XII Shunt Capacitive
Ceo- Ohms per Conductor per Mile Inductive Reartanrc Rcactarlce
/right metric Ohms per (‘onductor per .\llle Negohms per
ounda !&an I at 1 Ft. Sparmy Conductor
per Kadius 25°C. (i7”F.) 50°C. (122°F.) Ail (‘urrcnts per !vlilr
Mile at GO Small Currents Current Approx. at 1 I:t. SPdCillK
75% capacity:

-
c&Cl; - -

.-e 25 50
des cles 25 cycles 5
.-
0 7770 0520 380 I587 0588 0.591 0.1495 0 299 0 359
0 23io 0507 340 IGIE 0619 062 0 1508 0 302 0 362
9 6990.0493 3GQ 1652 0653 065, 0.1522 0 304 0 365
9 1600.0479 250 1691 0692 069, 0 1536 0 307 0 369
8 6210 0465 200 Ii.74 0735 073 0.1551 0 310 0 3i2
8 082 0.0450 160 17w 0784 0781 0.1568 0 314 0 3i6
111300054 3 0.1436190.08G21 293 700 000 40 200 7 5440.0435 110 084C 084’ .09240.09350 09570.09GI 0 1585 0 317 0 380 208 0 10400 086i
103350061 130 1384 70 13841.246 650 000 3i 100 7 0190.0420 060 0905 090 0 1603 0 321 0 385 ,211 0 10530 08i8
9.54 00054 3 0 1329 70 1329 1 196 600 000 34 200 6 4iQO 0403 010 098C 098 .10780.10880 11180.112t 0.1624 0 325 0 390 .214 0 10680 0890
90000054 3 0 1291 70 1291 1 162 566 000 32 300 6 1120 0391 970 104 104 .11450 11550 11750 118: 0 1639 0 328 0 393 216 0 10780 0898
Si45005-I 3 0 12i3 70 12731.146 550 000 31 400 5 9400 0386 950 107 107 .I1780 11880 12180 1221 0 1646 0 3?9 0 395 .21i 0 10830 0903
79500054 3 0 1214 i0 12141.093 500 000 28 500 5 3990.0368 900 118 118 .12880.13080.13580 137t O.lGiO 0 334 0 401 ,220 0 11000 0917

i950002G 2 0 Ii49 70 13G01.108 500 000 31 200 5 iioo.o3-5 900 117 117 .12880 12880. 0.1660 0 399 ,219 0 10950.0912
795 00030 2 0.1628190 097i 1.140 500 000 38 400 6 51iO 03j3 910 117 117 .12880.12880. 0 1637 0 393 .21i 0 10850 0904
715 50054 3 0 1151 70.11511 03fi 450 000 26 300 4 8590 0349 830 131 131 .14420.14520. 0.1697 0 407 ,224 0 11190 0932
il.5 50026 2 0 1659 i0 12901 051 450 000 28 100 5 1930.0355 840 131 131 .14420 14420 0.168i 0 405 ,223 0 11140 0928
71550030 2 0 1.544190 092Gl.081 450 000 34 600 5 8650 0372 840 131 131 .14420.14420 0.1664 0 399 ,221 0 11040.0920
66660054 3 0 1111 70.11111.000 419 000 24 500 4 5x0.033; 800 140 140 .15410.15710 0 lil5 0 412 226 0 1132 0 0943

400 OWJ 23 600 4 3190 0329 147 147 148 0.148 F .16180.16380.16780 1681 0 1726 0 345 0.414 228 0 11400 0950
400 000 25 000 4 6160 0335 147 147 0.147 .16180 16180 16180 1611 0.1718 0 344 0 412 227 0 11350 0946
400 000 31 500 5 2130 0351 147 147 ::: 0.147 .16180 16180 16180 1611 0.1693 0 339 0 406
380 500 22 500 4 lOQO.0321 154 155 155 0.155 0.16950.17150 li550.177i 0.1739 0 348 0 Iii 230 0 11490 095i
380 500 24 100 4 3910 0327 154 154 154 0.154 0.17000 17200.17200 li2( 0.1730 0 346 0 415
350 000 22 400 4 0390.0313 168 168 168 0.168 0.18490.18590.18690.185~ O.li51 0 350 0 420 232 0 11590 0965

556 500.30 2 0 13fi2 70 13620 953 350 000 27 200 4 5880 0328 730 168 168 168 0.1728 0 346 0.415 ,230 0 11490 095i
5w 00030 2 0.1291 70 12910.901 314 500 24 400 4 1220 0311 690 187 187 18i 0 li54 0 351 0 421 234 0 116iO 09i3
4ii 00026 ? 0 1355 70 10510.858 300 000 19 430 3 4620.0290 670 196 196 196 0.1790 0 358 0 430 23i 0.11860 0988
477 00030 i 0 1281 70.12610 883 300 000 23 300 3 9330 0304 196 196 196 O.li66 0 353 0.424 235 0 11760 0980
397 50026 2 0 123fi iO.09610 783 250 000 16 190 2 8850 0265 ii: 235 0.1836 0 367 0 441 244 0.12190 1015
397 50030 2 0 1151 iO.11510 806 25OMM 19 980 3 2770 0278 600 235 S1 0.1812 0 362 0 435 242 0 12080.1006

2 4420.0244 530 278 306 0.18i2 0 376 0 451 250 0 12480.1039


2 7740.0256 530 278 306 0.1855 0 3il 0 445 248 0.12380 1032
2 1780.0230 490 311 ,342 0.1908 0 382 0 458 254 0.1269 0.1057
2 4730.0241 500 311 0.342 0 1883 0 3i7 0 452 252 0.12580.1049
1 9360 0217 460 350 0.385 0 1936
-- - - - - --- - - -
0 387 0.465
~-
For Single Layer Conductors
OX-
R”t
AP-
pro%
75%
Ca- ~
pacit)
t -
__- -
2GFROO 6 IO 2109 70.07030 633 3/O 9 645 1 8020.0068 460 351 351 351 352 0.386 ,430 51170 ,552
4/O G 10 lRi8 10.187X0.563 210 8 420 1 5420 0081 340 441 ,442 444 445 0.485 ,514 .56: i0 592
3/o 6 10 1672 10.16720 502 l/O 6 675 1 2230 0060 3w 556 557 55s 560 0.612 ,642 69’7 0 723
2/O 6 10 1490 10.14900.447 I 5 345 9700 0051 270 702 702 704 706 0.773 806 .861 895
l/O 6 1 0.1327 10.13270.398 ; 4 280 769O.M)U 230 885 885 887 888 0 974 .Ol .12
1 6 10.1182 10.11820 355 3 480 6100.0041 200 12 .12 .12 12 1.23 .27 .E .38

4840 0041 180 .41 .41 41 1.55 .69


5660 0050 180 .41 .41 .41 1.55 65
3840 0043 160 .78 .78 .78 1.95 .07
3040 0043 140 .24 .24 .24 2.47 ,511
3560 0045 140 .24 .24 24 2.47 .55
2410 0041 120 .82 .82 3.10 .18
1910.0039 100 56 .56 ii 3.92 98
- -
l Based on copper 97 percent, aluminum 61 percent conductivity.
t For conductor at i6C., air at 25% wind 1.4 miles per hour (2 ft/sec), frequency=6O.cycles.
1 “Current Approx. 75% Capacity” is 75% of the “Approx. Current Carrying Capacity m Amps.” and is approximately the current which will produce 50°C. conductor temp. (25’C. rise) with
25% air temp., wind 1.4 luiles per hour.

TABLE ~-B-CHARACTERISTICSOF “EXPANDED” ALUMINUM CABLE STEEL REINFORCED


(Aluminum Company of ‘America)

Circular ___ - Ohms per Conductor per Mile


Mils
50°C. (122’F.)
Current Approx.
757” Capacity

-----__-__--A ~----
85000054 2 0.1255100.0834 4 0 118223 2 1.38534 ooO35371 7 200
1 1.50 000 54 2 0.1409 19 0 0921 4 0.1353 24 2 1 55 i24 M)o 41 900 9 070 (1)
1338 000 66 2 0 1350 19 O.lM) 4 0.184 18 2 1 75 840 WO 49 278 11 340
(1) Electrical Characteriitics not available until laboratory measurements are completed.
Chapter 3 Characteristics of Aerial Lines 51

TABLE Q-A-CHARACTERISTICS OF ANACONDA HOLLOW COPPER CONDUCTORS


(hnaconde Wire & Cable Company)
- -
I
Resistance
ra 2,
5,
Shunt Capacitive
Ohms per Conductor Inductive Rcactsnce Krnctnnce
c per Mile Ohms per Conductor ~IrRotlms per
prr AIile Conductor
heaking Weight at 1 Ft. Spacing ,‘CT 1Iile
strain 1Pounds , 25°C. (77°F.) 150°C. (122°F.) nt I Ft. Spacing
Pounds P‘er Llile ,

23 30
I
GO

__- I- _- --
/
cycles cycles
I cycles

x9n 500 28 1.650 38 000 0.0612 1395 1412 0.282 0.339


7.50 non 42 8: pi;; 1 15.5 34 200 0.0408 llG0 1017 0.323 0 388
R.50 000 50 0.1097 1.126 29 500 0.0406 I rl60 1621 0 324 0.389
fion no0 50 0.1053 1.007 27 .soo 0.0387 1020 lfi-14 0.329 0.395
5.x 000 50 0. I009 1.036 33 200 0.0373 960 16B3 0.333 0.399
.i I 0 000 50 0.0!)70 1.000 22 700 0.0360 YlO ID81 0.336 0.404
500 000 18 0.1558 1.080 ?I 400 0.0394. 900 16.30 0.320 0.:391
450 000 21 0.1353 I.074 19 300 0.0398 850 1630 0.32G 0.391

400 000 21 0.1227 1.014 17 200 6 642 0.0376 810


22 0 1211 1.003 16 300 6 331 0 0373 780
;sg ;gj 21 0.119G 0.930 IS 100 5 813 0 0353 750
3.&J no0 13 400 5 7i6 0.0311 1.237 n.1183,0 O!JSS
330 000 6 00.1444
1059 0.8GO
0.736 16 100 5 739 0.0233 2: I.248 ,o. 1241’0 10.34
321 000 22 0.1113 0.‘920 13 850 5 343 0.0340 700 0.1710 0.342 0.410 1.232 ~O.llG1~0 0968
300 000 18 0 1205 0 839 13 100 4 9x4 0.0307 670 0.217 0.1701 0.332 0.423 J.239 0995
300 000 13 0.1338 0.797 13 200 4 Y53 0.0289 660 0.1793 0.359 0.430 3.242 0.1212 0.1010
0.1194~0

300 000 12 0.1507 0.750 13 050 4 9.37 650 0.19640.19690.215 0.367 0.440 3.247 0.1234,o 1028
250 000 18 0.1100 0.76fi 10 IJ.50 4 155 600 0.238 0.239 0.260 ‘0’261
0 216 0.1833
0.1810 0.362 0.434 5.24.5 ‘0.122~ 0 1022
230 000 15 0.1214 0.725 11 000 4 148 590 0.237 0.238 0.259 0 260 0.1834 0.367 0.44c 2.24~) ‘0 1~40 1038
230 000 1% 0.1368 0.683 11 000 4 133 580 0.237 0.2.38 0.269 IO.260 0.1876 0.375 0.4x J.253 ~0.1%7’0 1O;iG
18 0.1005 0.700 9 300 3 521 530 0.281 0.282 0.307 10.308 0.18J5 0.371 0 44: 3 252 ,0.12380.1049
i:: 15 0.1109 0.663 9 300 3 510 520 0.281 0.282 0.307 ‘0 308 O.l88!J 0.378 0.45.: 3.2.X ,O. 1278iO. lnR5
4/O 14 0.1152 0.650 9 300 3 510 520 0.280 0.281 0.306 10:307 0.1898 0.380 0.4.5.. X2.57 IO. 1285NO. 1071
3/O 16 0.0961 0.606 7 500 2 785 460 0.354 0.353 10.387 IO.388 O.lY28 0.386 0.482 0.262 ‘0.13100 1091

310 15 0.0996 0 59.5 7 600 0.0214 460 0.1943 0.389 0.46f i).263 0.131GI0.1097
12 0.1123 0 560 7 600 0.0201 4 50 0.197G 0.39.5 0.474 3 208 0 13.38’0.1113
$1: 15 0 0880 0.530 5 9.50 0.0191 370 0.400 0 481 :X271 0.1357!0.1131
30 14 0.0913 0.515 6 000 0.0184 370 0.404 0.48’ 0 2i-L 0.1.368~0 1140
2io 13 0.0950 0.505 6 000 0.0181 370 D 27.5 ii. 1375 0 1146
125 600 14 0.0885 0.500 5 ti.50 0.0180 360 0 276 0.13780.1149
121 300 15 0.0836 0.500 5 400 0.0179 350 0 276 ,a13780 1149
119 400 12 0 0936 0.470 5 300 0.0165 340 O.280 0.1400 0 1187
- -
and .“Ctor at C.. air nt 25°C.. wind 1 miles p6 :r h XI, 1requency=60 cycles, average tarnished surface.

TABLE Q-B-CHARACTERISTICS OF GENERAL CABLE TYPE HH HOLLOW COPPER CONDUCTORS


(General Cable Corporation)

I
AP- 2,
ra Xfl Shunt Capacitive
Geo- gy;: Resistance Inductive Reactance Resctance
Break- met- rent Ohms per Conductor per Mile Ohms per Conduc- Alegohrns per
dS ing ric Csrry- tor per Mile ,5t Conductor per
Strength Mean ing Mite at 1 Foot
_ “-..nrl? Radius Capar-
Feet ) .itycZ’ , I 250c;
25 ;:;;; , ,&Oe, 1 d-c , “‘;P y2iF’), 60 2: F;,pare
cycles cycles cycles cycles cycles
.
0.302 0.1734 0.0867’0.0722
0.306 0.1757 0.0879’0.0732
0.310 0.0891~0.0742
0.314 10.1782
0.1805 0.0903 0.0752
~
an0 no0 1.820 0.137* 12 920 .34 550 0.0722 1390 1329 0.266 0.319 /0.1833 0.0917 0.0764
790 “00 l.ti50 0.131t 12 760 34 120 0.0646 133.5 13X5 0.277 0.332 10 itJo 0.0953 0 0794
750 000 1.730 0.13.3* I2 120 32 390 0 0691 1.325 1351 I 0 270 0.324 10 1864 0.0932 0 0777
700 000 1.686 0.130*11 310 30 230 0.0665 126.5 i370 0.274 0.329 !0.1891 0.0945lO.0788
fid0 no0 1 610 0.126* 10 500 28 070 0.0638 1304 0.279 0.335 i0.1924 0.0962!0.0802
I ix10 000 1.558 0.123* 9 692 2.5 910 0.0615 1410 0.282 0.338 iO.1947 0.0974,0.0811
.i:o on0 1.478 0.119* 8 884 23 750 0.0583 1437 0.287 0.34.5 IO. 198.5 0 0992~0.08ZZ7
.j I:! 000 1.400 n.J15* 8 270 22 110 0.0551 14G6 0.293 0.352 10.202 0.1012iO.0843
.x0 000 1.390 0.115* 8 07G 21 590 0.0347 100.5 12.59 0.1200 I0 12fiOlO 0.3.53 0.203 ‘0 1014lO.O84,5
.XJO 000 I .2fi8 0 lost 8 074 21 590 0.0494 978 12390.12600.1260;0. ’ 0 3f3.5 0.20!) ‘0 1047’0 0872
300 000 1 100 0.130t 8 068 21 590 0.0420 937 12580.12590.12600 0.3% 0.21Y ‘0 109810 0915
500 on0 1 020 0 144t 8 063 21 590 0.0384 9 1.i 1258 0.1259 0.12Go:o 0.3!)6 0.223 ~0.1124,0.0937
.4.io on0 1.317 O.lll* 7 268 ID 430 0.0518 CJ.39 0.3.59 0.207 ,o. 1033~0.0861
430 000 1.188 0.1057 7 286 19 430 0 O-182 YlO 1390~0.1400
1400 0.1401 0.1401;o.
0.1‘400l0
.400 no0 1.218 O.lOR* 6 460 17 270 0.0478 864 1575 0.1576’0.1576’0.
.400 000 1.103 O.lOOt 6 458 I7 270 0.0428 838 1574 0.1575’0.1575’0. 0.382 0.21’3 0.1097 O.OY14
nan 000 1.128 0.102* 5 653 15 110 0.0443 790 0.378 0.218 0.10890.0907
:m 000 1.014 0 096t 5 S50 15 110 0.0393 764 0.393 0 225 0.1127 0.0939
:wo 000 1.020 0.096* 4 845 12 950 0 0399 709
:1no 000 0.919 0 091t 4 843 12 950 0.0355 687
50 000 0.914 0 OYl* 4 037 IO 7YO 0.0357 ti26
L’;,o 000 0.818 0 08fit 4 036 10 790 0 0Xl.i 606 0.230 i).“.il’ o.“;,z 0.2.z 0.232 0.1748 0 3.50
230 on0 0 76fi o,o!l4t 4 034 IO 7YO O,OL’!J2 694 0.230 0 2.X 0.232 0.252 0.252 0.1787 0 3.57
“1-t ,x,0 0. Ii30 0 (J9Xt 3 4.W !I 205 ,0.0243 524 0.21;s 0 L’Y3 ,0.2Y3 0.2Y3 10.2Y4 0.1879 0.376
I 0 0 7*33
:i, 0 0 608
210 0.500

Notes: *Thickness at cd&es of interlocked segments. tThickness uniform throughout.


(1) Conductors of smaller diameter for given cross-wct,ional area also available; in the naught sizes, some additional diameter expansion is possible.
(2) For conductor at. 75°C.. air at 25°C.. wind 1.4 miles per hour (2 ft/aec), frequency=60 cycles.
52 Characteristics of Aerial Lines Chapter 3

TABLE 4-A-CHARACTERISTICSOF COPPERWELD-COPPER CONDUCTORS


(Copperweld Steel Company)

Size of Conductor
- rcz ra XII
:opper
WOX. Resistance Resistnuce InductiveReactance Cap&ve
1rrent Ohms per Conductor Ohms per Conductor Ohms per Cooductor enrtaoce Megohms
quiva- rrying per Mile at 5O’C. (122°F.) per Mile per Conductor
umber and Diameter lent per .Mile at 25”C.(77”F.)
of Wires pacity Small Currents Current Appror. 7.57, of One ft. Sparmq per Mile
Komina
Dcsig-
nation
.“r utside
hm-
eter
irculilr
Ilk or
.W.G.
it 60 Capacity” AwaKe Currcllts ox! ft. Ppacmg

Copper uches 25 5o 1 6o 25 / 5o 6’ 25 50 fi0


cyclev cycles cycles cycles / cyrlrs cyrl?n TIC3 cycles cycles
-- _ / I
350 E ‘x .15i6” 2x. 1576” ) 788 420 ! 7 409 I 0 0220
350 EK ,x.i47n~~ Sr.1470” j.735 850 6 536 0 0245
350 v :x li51" 9x. 1893” I.754 430 6 57s 0.0226

300 E “L. 1459” 2x. 1459” 3.729 7i0


300 EK Ix. 13Rl” 5,. 1381” I.680 , 960
300 v Ix 1621” Ox. 1752” I 698 I 730

250 E Tn. 1332” 2x 1332” I 666 I 920 I 5 292 I 0 01859


250 EK Ix. 1242” 5x 1242” I 621 ’ 840 4 669 0.0207
250 v Ix. 1480” 9x 1600” I 637 420 ,I 699 0.01911

4/O E 7x. 1225” 2x. 1225” I.813 I 730 4 479 0 01711 261 0 1306 0 1088
4/OC Ix. 1944” 5a.lY44” i 640 4 168 0.01409 265 0 1324 0 1103
4/O EK 1x.1143” 5x 1143” :: 2;: i 370 3 951 0 01903 266 0 1331 0 1109
4/o v 3x. 13fil” 9x.1472” 3 586 i 000 3 9:; 0 0175f 264 0 1322 0 1101
4/O F Ix. 1833” fix. 1833” 3.550 ! 290 3 750 0.0155E 269 0 1344 0.1120

3/O E 7x.1091” 2x 1091” 0 545 i 800 3 552 0.01521 0 346 0.353 0.359 0.361 0.3i6 0 391 0.402 0 407 0.212 0 423 0 ,508 270 0 1348 0.1123
3/O .J 3x. 1851” 4x. 1851” 0 555 i 170 3 732 0.0115f 0.344 0.356 0 36i 0.3i2 0.377 0 308 0.419 0.428 0 225 0.451 0 541 268 0 1341 0.1118
3/o G 2x. 1731” 2x. 1731” 0 519 1 860 3 305 0 01254 400 0 344 0.356 0 365 0.369 0 37i 0.397 0.416 0 423 0.221 0.443 0 531 2i3 0 1365 0.1137
Ir.lOlB” 4x. 1018” 0 509 3 370 3 134 0 0169; 420 0 346 0.348 0 350 0.351 0.378 0 382 0.386 0 386 0 206 0 412 0 4!15 274 0 1372 0.1143
g”, ;” 3x. 1311” 9x.1311” 0.522 ! 220 3 154 0 0156f 410 0 345 0 352 0.360 0 362 0 3i7 0.390 0 403 0.408 0 210 0 420 0 504 2i3 0 1363 0 1136
3iOF lx. 1632” 6x. 1632” 0.490 ) 880 2 9i4 0.0138t 410 0.344 0.351 0 356 0.358 0.3i7 0.388 0.397 0.401 0.216 0.432 0.519 27; 0.1385 0.1155

2lnK 4x. 1780” 3x. 1780” 0 534 7 600 3 411 0.0091: 360 0.434 0 447 0.459 0.466 0 4i5 0.499 0.524 0.535 0.237 ‘0.475 0 570 271 0 13550 1129
2/O .J 3x.1648” 4x. 1648” 0 4Y4 j 430 2 960 0.0102: 350 0.434 0.446 0.457 0.462 0.4i5 0.498 0 520 0.530 0 231 10 463 0 555 277 0 1383 0.1152
2/O G 2x. 1542” 5x. 1542” 0.463 I510 2 622 O.Olll< 350 0.434 0.445 0.456 0 459 0 475 0.497 0.518 0.525 0.22; 0 454 0.545 281 0 14060 1171
3Y 1080” 9u 1167” 0 465 3 846 2 502 0.0139: 360 0.435 0.442 0.450 0.452 0.476 0.489 0.504 0 509 0 216 0..&32 0 518 2Rl 0 1404 0 lli0
% lx. 1454” 6x. 1454” 0.436 3 094 2 359 0.0123: 350 0.434 0.441 0.446 0.448 0.4ij 0.487 0.497 0 501 0.222 0.444 0.533 285 0 142i 0.1159

l/OK 4x. 15R.5” 3x. 1585” 0.475 I490 2 i03 0.0081: 310 0.548 0 560 0 573 0.579 0,599 0.625 0.652 0 664 0 243 0.487 0.584 2i9 0.1397 0.1164
l/OJ 3x. 1467” 4r.146i” 0.440 1 970 2 346 0 OOYl> 310 0 548 0 559 0 570 0.576 0 599 0.624 0.648 0.650 0 23; 0.474 0 569 285 0 1423 0.1136
l/OG 2x. 1373” 5x. 13i3” 0.412 3 563 2 OiSl 0 0099t 310 0.548 0 559 0 568 0.573 0.599 0.623 0.645 0 654 0 233 0.466 0 559 289 0 1447 0 1206
l/OF 1x.1294” 6x. 1294” 0.388 j 536 1 8iOl 0 0109! 310 0.548 0,554 0 559 0.562 0.599 0.612 0.622 0 62i 0.228 0.456 0 54; 294 0.1469 0 1224

1N 5x. 1546” 2x 1546” 0.464 5 410 2 541 0 00631 280 0.691 0.705 0.719 0.726 0 755 0.787 0 818 0.832 0 256 0 512 0 614 281 0.1405 0.1171
1X 4x. 1412” 3x 1112” 0.423 1 900 2 144 0 0072: 268 0 1438 0.1198
1 .I 3r: 1307” 4x 1307” 0.392 3 000 1 861 0.0081: ;;; 0.691 0.704
0.703 0.716
0.714 0.722
0 719 0 755 0.784
0 783 0.813
0.808 00.825
820 0.243
0 249 0 498
486 0.598
0 583 293 0 1465 0.1221
1G 2x. 1222” 5x 1222” 0 367 6 956 1 649 0.0088: 260 0.691 O.iO2 0.712 0.716 0.755 0.781 0.805 0 R15 0 239 0 478 0 5i3 298 0 1488 0.1240
IF 1x.1153” 6x. 1153” 0.346 5 266 1483 O.W98( 2io 0.691 0.698 0.704 0.705 0.755 0.769 0.781 0.786 0.234 0.468 0.561 302 0.1509 0.1258

2P fir. 1540” lx 1540” 0.462 6 870 48i 0.0050 250 0.871 0.886 0.901 0.909 0.962 0.988 1.024 1.040 0.268 0 536 0.643 281 0.1406O.lli2
2N 5x. 137i” 2x. 137i” 0.413 2 680 015 0.00561 240 0.871 0.885 0.899 0.906 0.952 0.986 1.020 1.035 0.261 0 523 0.627 289 0.1446 0.1205
4x. 1257” 31 1257” 0.377 9 730 iO1 0 0064. 240 0 8il 0.884 0.896 0.902 0 952 0.983 1 014 1.028 0 253 0 510 0 612 296 0.1479 0.1232
;7 3x llfi4” 4.x 1164” 0 349 7 322 4i6 0 0072’ 230 0.8il O.SR3 0.894 0 899 0 952 0.982 1010 1.022 0 249 0.498 0 598 301 0.15060.1255
2 :\ la. 1690” 2x 1699” 0 36R 5 876 356 0 OOi6: 240 0 869 0.875 0 880 0 R82 0 950 0.962 0.973 0.9i9 0 247 0 493 0 592 298 0 1489 0.1241
2G 2x. 1089” 5u.1089” 0 327 5 62fi 3oi 0 ooiw 230 0.871 0.X32 0 892 0.896 0 052 0.980 1.006 1 016 n 245 0 4R9 0 587 306 0 1529 0.12i5
2F lx, 102fi” 6x. 1026” 0.308 4 233 li6 0 0087: 230 0.871 0.878 0.884 0.885 0.952 0.967 0.9i9 0.985 0 230 0 479 0,575 310 o 1551 0.1292

3P Rx. 1371” lx 13il” 0 411 973 0 0044! 220 1.098 1.113 1 127 1.136 1.200 1.239 1.273 1296 0 274 0 54i 0 65i 290 o 1448 0.1207
3N 5x 122R” ax 122R” 0 3fiR 598 0 00501 210 1.098 1 112 1 126 1 133 1.200 1.237 1.273 1289 0 26i 0 534 0 641 298 0.148i 1.1239
RK -kc 1120” 3x 1120” 0 336 349 0.0057, 210 1.098 1.111 1 123 1.129 1.200 1.233 1267 1.281 0 261 0 522 0 626 304 0 1520 0.1266
35 3r 1036” 4x. 1036” 0 311 lil 0.00641 200 1.098 1.110 1.121 1.126 1.200 1.232 1.262 1275 0 255 0 509 0 611 309 o 1547 0.1289
3A lx. 1513” 2x. 1513” 0.326 075 O.O06i! 210 1.096 1.102 1.107 1.109 1.198 1.211 1.225 1229 0.252 0 505 0.606 ,306 0.1531 0.12X

4P 6x.1221” lx. 1221” 0.366 1 420 564 0.0039’ 190 1.385 1.400 1 414 1 423 1.514 1.555 1.598 1.616 0.2RO 0 559 0.671 298 0 1489 0.1241
4N 5x. 1092” 2.x. 1092” 0.328 8 460 26i 0 0045 180 1.385 1.399 1.413 1.420 1.514 1.554 1.593 1 til0 0.2i3 0 546 0 655 .306 0 15280 1274
2x. 1615” lx. 1615” 0 348 7 340 191 0 00561 190 1.382 ,1.389 1.398 1399 1.511 1.529 1.544 1542 0 262 0 523 0.62$ .301 0.1507 0.1256
iA” 1x.1347” 2x. 1347” 0.290 3 038 853 0 0060 180 1.382 1.388 1393 1.395 1.511 1.525 1.540 1.545 0 258 0.517 0.62( 314 0.1572 0.1310

5P 6x. 1087” lx lOS7” 0.326 9 311 240 0 0035: 160 1.747 1762 1.776 1 785 1909 1.954 2.00 2 02 0 285 0.571 0 68: 306 0.1531 0.1275
5D 2x 1438” lx. 1438” 0.310 ll 0% 944 0.0050 160 1.742 1.749 1.756 1 i59 1.905 1.924 1.941 1939 0 268 0 535 0 64i ,310 0.1548 0.1290
5A lx. 1209” 2x. 1200” 0.258 3 193 676 0.0053, 160 1.742 1.748 1.753 1.755 1.905 1.920 1.936 1.941 0 264 0.528 0.634 ,323 0.1614 0.1345

fiD 2x 1281” lx 1281” 0 2x 4 942 749 0.0044’ 140 2.20 221 2.21 2.22 2.40 2.42 2.44 2.44 0.273 0547 06% 318 0.1590 0 1325
SA lx 1068” 2x. 1068” 0.230 2 5S5 536 0 0047’ 140 2.20 2.20 2.21 2 21 2.40 2 42 2.44 2.44 0.2iO 0 540 0 64f ,331 0.16550.13i9
6C lx, 1046” 2x. 1046” 0.225 2 143 514 0 0046 130 2.20 2.20 2.21 2.21 2.40 2.42 2.44 2.44 0.271 0.542 0.651 333 0.1663 0.1386

IIIIIiIIII
I I I I I I I I ’I I
7D 2x, 1141” 1x.1141” 0.246 4 022 594 0.0040 2.77 2.78 2.79 279 3.03 3.05 307 3.07 0.2-9 0,558 0.67(
7A lx. 1266” 2x.0895” 0.223 2 754 495 0.0044 2.77 2.78 2.78 2.78 3.03 3.05 3.07 3.07 0.2i4 0.548 0.651

2x. 1016” lx.lOlfi” 0.219 3 256 471 0 0035 3.49 3.50 3.51 3.51 3.82 3.84 3.86 3.86 0285 0.570 0 68,
I; 1x.1127” 2x. Oi97” 0.199 2 233 392 0.0039 3.49 3.50 3.51 3.51 3.82 3.84 3 86 3.87 0.280 0560 0.67:
lx. 0808” 2x.OS3p 0.179 1 362 320 0.0037 3.49 3.50 3.51 3.51 3.52 3.84 3.86 3.86 0.283 0.565 0.67!
955 D 2x.0608” 1x.0808” 0.174 1 743 298 0.0028
a51, 1, 1. 1. I. I. I
4 91 4 92 4 92 4 93 5 37 5 39 5 42
I. I. I. I,
5 42 0 297 0 593 0 71: 1.351 /0.175410.1462

*Based on a conductor temperature of 75’C. and an ambient of 25°C.. wind 1.4 miles per hour (2 ft/sec.). fre uency=60 cycles, average tarnished surface.
**Resistances at 50°C. total temperature. based on an ambient of 25°C. plus 25% rise due to heating effect o“t current. The approximate magnitude of current necessary to produce the
25” C. rise is 757r, of the “Approximate Current Carrying Capacity at 60 cycles.”

finding the appropriate table for a particular conductor. Aluminum Cable Steel Reinforced, represents stranded
For these figures open circles, solid circles, and cross- paper.
hatched circles represent copper, steel, and aluminum con- The authors wish to acknowledge the cooperation of the
ductors respectively. The double cross hatched area in the conductor manufacturers in supplying the information for
insert for Table Z-B, Characteristics of “EXPANDED” compiling these tables.
Chapter 3 Characteristics of Aerial Lines 53

TABLE 4-IS--CHARACTERISTICS OF COPPERWELD CONDUCTORS


(Copperweld Steel Compnny)

ra
Resistance
Ohms per Conductor
per hide
at WC. (i7”F.)

30% Conductivity
-
i/U" 19 No. 5 0 910 /624 !900
i5 5i0 66 910 9 344 0 09758 fi20 0 306 0 316 0 326 0 331 0.363 0 419 0 4i6 0 499 0 261 0 493 0 592 0 233 0.111% 0 OOil
13, IG" I 9 No. R 0 Xl0 19x ROO 15 830 J5 530 7 410 0 OORi5 540 0 386 0 396 0.406 0 411 0 45X 0 513 0 580 0 605 0.267 0 505 0 fi06 0 241 0 12OG0 1005
:':i/:L?" I 9 No. 7 0 i21 395 500 Ii 740 45 850 5 Rii 0.00601 470 0.486 0.496 0 506 0 511 0.577 0 643 0.710 0 737 0 2iR 0 517 0 ti?l 0 250 0 124X 0.1010
‘~,>/:gy" I !I so. 8 0 642 313 ioo I1 040 37 690 4 660 410 0 613 0.623 0 633 0 638 0 728 0 i99 0 Ri? 0 902 0 2% 0 529 0 635 0 254 0 1249 0 1074
!I/lii" I !I No. !I 0 5i2 248 800 !5 500 30 610 3 696 360 0 773 0.783 0 793 0 798 0 917 0 995 1 075 1 10R 0 285 0 541 0 619 0 “lx 0 13300 1109
3, 'I" 7 so. 4 0 613 292 200 !4 7x0 29 430 4 324 410 0.656 0.684 0 672 0 676 0,778 0 824 0 370 0 8Ri 0 281 0 533 0.6-10 0 261 0 13Ofi 0 10%

‘I/W’ i No. 5 0 54fi 231 700 IO 470 21 650 3 429 360 0 827 0 835 0 843 0 847 0 981 1 030 1 090 1 0119 0 257 0 54.5 0 654 0 2G9 0 1347 0 II22
] ! 2” 7 so. R 0 IXfi lR3 800 IF 890 20 460 2 719 310 1.042 1 050 1.058 1 062 1 237 1 290 1 343 I 364 0 293 0 55; 0 668 0 X3 0 13’iX 0 1157
7,lli” i No. 7 0 433 145 700 13 910 16 890 2 157 270 1315 1.323 1 331 1.335 1 560 1.617 I 675 1 69i 0 299 0 5fi9 0 OR3 0 ?Sli 0 142!1 0 II!)1
:3/S” i x0. R 0 355 115 fioo I1 440 13 890 1 710 230 1.658 1666 1.674 1 678 1967 2 03 2 09 2 12 0 305 0 581 0 697 0 29I 0 14il 0 1221;
, I,‘:<“” 7 No. 9 0 343 91 650 9 393 11 280 1 356 200 2 09 2 10 2.11 2.11 2 48 2 55 2 61 2 Ii4 0 311 0 592 0 ill 0 303 0 1512 II 1281)
S/Ii, 7 No. 1’ 0 306 72 680 7 758 9 196 1 076 170 2.64 2 64 2.65 2 66 3.13 3 20 3 27 3 30 0 31ti 0 604 0 725 0 311 0 1553 0 1294
3 ?I<>.5 3 No. 5 0 392 99 310 9 262 11 860 1 46i 220 1926 1.931 1.936 1.938 2.29 2 31 2 34 2 35 0 289 0 545 0 654 0 293 0 141350 1221
:, No Ii 3 so. 6 0 349 iR i50 7 639 9 754 1 163 190 2.43 2.43 2.44 2 44 2 85 2 91 2 94 2 95 0 295 0 5.56 0 664 0 301 0 1506 0 1255
:, No 7 3 No. 7 0 311 62 450 6 291 7 922 922 160 3 06 3 07 3 07 3.07 3 63 3 B6 3 70 3 71 0 301 0 56X 0 682 0 310 0 154i0 1289
:/ No x 3 X0.8 0 2i7 49 530 5 174 6 282 731. 0 00323 140 3 86 3 87 3.87 3.87 4 58 4.61 4 65 4 GA 0 307 0 580 0 696 0 318 0 1589 I) 1321
:I No !I 3 No. 9 0 247 39 280 4 250 5 129 550 0 00288 120 4.87 4.87 4.88 4 88 5 78 5 81 5 R5 5 86 0 313 0 591 0 i10 0 326 0 lG“!l 0 135X
:, SC> 10 3 .uo. 11 0 220 31 150 3 509 4 160 460. 0 00257 110 6.14 6.14 6.15 6.15 7 28 7 32 7 36 7 38 0 319 0 603 0 724 0 334 0 16il 0 1392
- -

40% Conductivity
- -
; ‘4”
I 9 No. 5 0 910 628 900 i0 240 9 344 0 01175 690 0.229 0.239 0 249 0 254 0.272 0 321 0.371 0 391 0 236 0.449 0 539 0 233 0 1165 0 09il
,,l,lli” 9 No. 6 0 810 498 800 I1 600 ..,,,. 7 410 0 01046 610 0.289 0.299 0 309 0.314 0.343 0 396 0.450 0.4i2 0 241 0.461 0 553 0 241 0 12060 I005
9, :x” : 9 No. 7 0,721 395 500 I4 390 5 877 0.00931 530 0.365 0.375 0.385 0 390 0.433 0.490 0.549 0.573 0 247 0.473 0 567 0.250 0 12480.1040
2IJ2” 9 No. II 0 642 313 iO0 18 380 4 660 470 0 460 0.470 0 480 0.485 0.546 0 608 0 672 0.698 0.253 0 485 0 582 0 258 0 12X9 0 lOi
!I/lli” t 9 No. 9 0 572 24R so0 !3 390 .._. 3 696 410 0.580 0.590 0.600 0 605 0 688 0.756 0.826 0.853 0 259 0.496 0 595 0 266 0 1330 0.1109
5/R” 7 No. 4 0 613 292 200 !2 310 4 324 470 0.492 0.5M) 0.508 0 512 0.584 0 624 0.664 0.680 0 255 0.489 0.58i 0 261 0 13060 1088
‘)/IV’ 7 No. 5 0 546 231 ml 18 510 ..., 429 0 OOiO5 410 0.620 0.628 0.636 0.640 0.736 0 780 0.843 0.840 0.261 0 501 0 601 0 269 0.134iO 1122
i 12” 7 No. 6 0 486 183 800 15 330 i19 0 00628 350 0.782 0.790 0.798 0.802 0.928 0 975 1 021 1.040 0 267 0.513 0.615 0 278 0 13880 1157
;/Iv 7 No. 7 0 133 145 ioo 12 670 15; 0.00559 310 0.986 0.994 1.002 1.006 1.170 1.220 1.271 1.291 0.273 0.524 0 629 0 286 0.1429 0 1191
:3/V’ 7 No. A 0 3x5 115 ii00 IO 460 710 270 1.244 1.252 1.260 1264 1 476 1530 1 584 1.606 0.279 0.536 0 644 0 294 0 1471 0 1226
I, :I?‘, 7 No. 9 0 343 91 650 R 616 356 230 1 568 1 576 1.584 1.588 1.861 1.919 1.978 2 00 0 285 0.548 0.658 0 303 0 1512 0 1260
5, lli” 7 No. 1’ 0 306 72 680 i 121 Oi6 200 1.978 1986 1.994 1.998 2.35 2 41 2.47 2.50 0 291 0.559 0.671 0 311 0 1553 0 1294
:I so. R 3 No. 5 0 392 99 310 8 3i3 467 0 00621 250 1.445 1450 1.455 1.457 1.714 1738 1762 l.ii2 0 269 0.514 0.617 0 293 0 14650 1221
11St,. fi 3 No. Ii 0 349 78 750 6 934 163 0 00553 220 1.821 1.826 1.831 1 833 2.16 2.19 2 21 2.22 0.275 0 526 0.631 0 301 0 15060 1255
:I St,. i 3 No. 7 0 311 62 450 5 732 922.4 0.00492 190 2.30 2 30 2.31 2.31 2.73 2.75 2.78 2 79 0 281 0.537 0.645 0 310 0 154iO 1289
3 No. s 3 No. 8 0 277 49 530 4 730 731.: 0 00439 160 2.90 2.90 2.91 2.91 3.44 3.47 3.50 3.51 0 286 0.549 0.659 0 318 0.15R90 1324
3 No. !, 3 No. 9 0 247 39 280 3 898 580.1 0.00391 140 3.65 3.66 3.66 3 66 4 33 4 37 4.40 4.41 0.292 0 561 0 673 0 326 0.16290 1358
3 so. 10 3 No. II 0.220 31 150 3 221 460 ( 0.00348 120 4.61 4 61 4.62 4 62 5.46 5 50 5.53 5.55 0.297 0 5i2 0 687 0 334 0.1671 0 1392
3 NI,. 1’ 3 No. 1: 0.174 19 590 2 236 289.2 0.00276 90 7.32 7 33 7.33 7.34 8.69 8.73 8.77 8 78 0.310 0 596 0 i15 0 351 0 1754 0 1462
- -
l Il:rscd on cotlductor temperature of 125°C. and an ambient of 25°C.
‘*Resistance at 75°C. total temperature, based on an ambient of 25°C. plus 50°C. rise due to heating effect of current.
The approximate magnitude of current necessary to produce the 50% me is 75% of the “Approximate Current Carrying Capacity at GOCycles.”

TABLE ~-SKIN EFFECT TABLE


- -
9 K X K X K X K
_-
0.0 1.00000 1.0 1.00519 2.0 1.07816 3.0 1.31809
0.1 1.00000 1.1 1.00758 2.1 1.09375 3.1 1.35102
0.2 1.00001 1.2 1.01071 2.2 1.11126 3.2 1.38504
0.3 1.00004 1.3 1.01470 2.3 1.13069 3.3 1.4199!)
04 1.00013 1.4 1.01969 2.4 1.15207 3.4 1.45570
0.5 1.00032 1.5 1.02582 2.5 1.17538 3.5 1.1!)202
0 (i 1 .00067 1 6 1.03323 2.6 1.20056 3.6 1 52879
0 7 1.00124 1.7 1.0420.5 2.7 1.22753 3.7 1.56587
0.8 1.00212 1.8 1.05240 2.8 1.25620 3.8 1.60314
0.9 1.00340 1.9 1.06440 2.9 1.28644 3.9 1.64051
- -
54 Characteristics of Aerial Lines Chapter 3

TABLE 6--INDUCTIVE REACTANCESPACINGFACTOR(2;) OHMSPER CONDUCTOR


PERMILE
25 CYCLES

SEPARATION

5 16171819 I 10 I 11
--~
,. ,.,,A” xd at FUNDAMENTA .L
1329
._.. 25 cvcles EQUATIONS
td ,=O. li64 logto d
.1,,r, Y.“““Y d =separation. feet. 2, =z,=r,+j(x,+
.08921
nnvo
0.0899
n nn-ro 2, =r,+r,+.W+x,- -2J

j g:;;;: 50 CYCLES
11
1 12 0.1212
0.1256 SEPARATION
.,
;I34 0.1297
1 0.1334 Inches
1; ; : ;j4f;; Feet
1_ ^ ..-^ 0l11213141~/~17/ 8/Q 10 11
17 “.143Z . -- --. --
18 0.1461 0 -0.2513-0.1812- -0.1402 -0.1111 -0.0885- -0.0701-0.0545 -0.0410 -0.0291 a.0184 -0.0088 Xd at
19 0.1489 0 0.0081 0.0156 0.0226 0.0291 0.0352 0.0410 0.0465 0.0517 0.0566 0.0613 0.0658
20 O.ld15 t 0.0701 0.0742 0.0782 0.0820 0.0857 0.0892 0.0927 0.0960 0 0992 0.1023 0.1053 0.1082 50 cycles
21 0.1<539 3 0.1111 0.1139 0.1166 0.1192 0.1217 0.1242 0.1267 0.1291 0.1314 0.1337 0.1359 0.1380 m=O.2328 lcrg,o cf
22 0.1563 4 0.1402 0.1423 0.1443 0.1463 0.1483 0.1502 0.1521 0.1539 0.1558 0.1576 d= xtioll. feet.
23 0.1585 0.1644 0.1661 0.1677 0.1693 0.1708 0.1724 0.1739 0.1754 0.1769
24 0.1607 ; EE 0.1826 0.1839 0.1853 0.1866 0.1880 0.1893 0.1906 0.1918 0.1931
2.5 0.1627 7 0.1968 0.1980 0.1991 0.2003 0.2015 0.2026 0.2037 0.2049 0.2060 0.2071
26 0.1647
27 0.1666
28 0.1685 60 CYCLES
-
29 0.1702 11 0.2425
30 0.1720 12 0.2513 SEPARATION
31 0.1736 13 0.2594
3:
27 lO:i% ::
n 17.59 i:z$iFeet Inches

16
.- 0.2804
^ .^^_ \‘O 10 11
-__-
849 -0.0221 -0.0106 xd at
0.073 5 0.0789
;!?I n1.___
I_. 1% 4 0.1299 60 cycles
0.1631
_ _^__ 0.1657
^ _^^_ x,!=O.2794 l?&e d
V.lY.5.5 d=separarlon,
0.2157
0.2347
0.2511

; TABLE~-ZERO-SEQUENCE RESISTANCE AND INDUCTIVE REACTANCE


FACTORS (re,xe) *
Ohms per Conductor per Arile

FREQUENCY

25 Cycles

re All 0.1192

*From Formulas: tThia is an average value which may


re=O.O047G4/ be rlsed in the absence of definite in-
formation.
ze=0.006985/ IORIO 4 G65 600;
where /=freqllency
p=Reuistivity (meter, ohm)
Chapter 3 Characteristics of Aerial Lines 55

TABLE %-SHUNT CAPACITIVE REACTANCE SPACING FACTOR (xi) MEGOHMS PER co~~uc~o~ PER MILE
25 CYCLES
SEPARATION
INCHES
Feet ~
0
-- x,'at FUNDAMENTAL
0
1 0 25 cycles EQUATIONS
2 0.0494
:I 0.078: zd’=.I640 logosd x;=x:=x,I+x:
4 0.098i d=separation, feet.
,j 0.114t x; =x:+x:-2x:
,; 0.1271
7 0.138f
g 0.1481
9 0.156:
,a 0.164(
1, 0.170:
12 0.17% SEPARATION
,:j 0.1821
,*I 0.187! Inches
1.j 0. 192)
16 0.197‘
17 0.201’
, y II. 20.5: 0 xd’ at
I!, 0.209 0
‘2,) 0.213: ; 0.024 50 cycles
“1 0.2161 3 0.039 &,‘=0.08198 logm d
L’L’ ” ““0 4 0.049, d=separation. feet:
L’:j 0.;23: 5 0.057:
“1 0.2’26: 6 0.063;
I.5 0. z”!,: 7 0.069:
“,j 0, 2321 8 0.074(
L17 0.234 9 0.078:
“H 0 ,237: 60 CYCLES
10 0.0821
“!I 0.%39 11 0.08.5,
:x, 0,242 12 0.088. SEPARATION
:I, 0.244 13 0.091:
32 0 246 14 0.0941 Inches
XI 0.2491 15 0.096.
34 0.251 ‘eet
35 0. 253
16 0.098 0 1 2 3 4 5 6 7 8 9 10 11
17 0.100’ ~ -~ ~
:I(; 0. 2:55
:<7 0.257
18 0.102’ 0 -0.0737-0.0532-0.0411-0.0326 -o.--o.o2o6-o.o16o -o.o120 -0.0085-0.0054-0.0026 x: at
19 0.104 1 0 0.0024 0.0046 0.0066 0.0085 0.0103 0.0120 0.0136 0.0152 0.0166 0.0180 0.0193
:x3 0.259’
:%!I II. 260
20 0.106 2 0.0206 0.0218 0.0229 0.0241 0.0251 0.0262 0.0272 0.0282 0.0291 0.0300 0.0309 0.0318 60 cycles
21 0.108 3 0.0326 0.0334 0.0342 0.0350 0.0357 0.0365 0.0372 0.0379 0.0385 0.0392 0.0399 0.0405 r/=0.06831 lo&o d ’
10 0. “62 22 0.1101
41 0.;64 4 0.0411 0.0417 0.0423 0.0429 0.0435 0.0441 0.0446 0.0452 0.0457 0.0462 0.0467 0.0473 d=separation, feet.
23 O.lllN 5 0.0478 0.0482 0.0487 0.0492 0.0497 0.0501 0.0506 0.0510 0.0515 0.0519 0.0523 0.0527
,42 0 ,266 24 0.113
‘43 0 267 6 0.0532 0.0536 0.0540 0.0544 0.0548 0.0552 0.0555 0.0559 0.0563 0.0567 0.0570 0.0574
25 0.1141 7 0.0577 0.0581 0.0584 0.0588 0.0591 0.0594 0.05913 0.0601 0.0604 0.0608 0.0611 0.0614
.I4 I,. 269 26 0.1161
.45 0.271 8 0.0617
.l(l 0.272, 27 0.117: 9 0.0652
47 0.274
28 0.1181 10 0.0683
48 0.275’ 29 0.119’ 11 0.0711
,I0 0.277 30 0.121 12 0.0737
31 0.122 13 0.0761
32 0.123 14 0.0783
33 0.124 15 0.0803
R4 0.125 16 0.0823
35 0. 126 17 0.0841
36 0.127 18 0.0858
:37 0.128 19 0.0874
38 0.129 20 0.0889
39 0.130 21 0.0903
40 0.131 22 0.0917
41 0.132 23 0.0930
42 0.133 24 0.0943
43 0.133 25 0.0955
44 0.134 26 0.0967 TABLE 9-ZERO-SEQuENcE SHUNT CAPACITIVE REACTANCE FACTOR
45 0.135 27 0.0978
46 0.136 28 0.0989 Ze’
47 0.137 29 0.0999 Megohms per Conductor per Mile
48 0.137 30 0.1009
49 0.138 31 0.1019
32 0.1028 FREQUENCY
33 0.1037 Conductor
34 0.1046 Hei;g;u4$ve
35 0.1055 Feet 25 Cycles 50 Cycles 60 Cycles
36 0.1063
37 0.1071
38 0.1079 :8 0.040
0.727 0.320
0.363 0.267
0.303
39 0.1087 20 0.788 0.394 0.328
40 0.1094
41 0.1102 2 0.875
0.836 0.437
0.418 0.348
0.364
42 0.1109 40 0.936 0.468 0.390
43 0.1116 % 0.984
1.023 0.492
0.511 0.410
44 0.1123
45 0.1129 i: 1.084
1.056 0.542
0.528 Ei
46 0.1136
47 0.1142
48 0.1149 1:: 1.109
1.132 0. 555
0.566 0.472
:::FZ
49 0.1155
12.30
ze’=--log,0 2h
f
where h=height above ground.
f = frequency.
56 Characteristics of Aerial Lines Chapter 3

TABLE 10-STANDARD BAROMETRIC


IV CORONA PRESSURE AS A FUNCTION OF ALTITUDE
With the increased use of high-voltage transmission lines Altitude, Pressure, Altitude, Pressurr,
and the probability of going to still higher operating volt- feet in. Hg. feet in. Hg.
ages, the common aspects of corona (radio influence and
corona loss) have become more important in the design of - 1000 31.02 4 000 25.84
- 500 30.47 5 000 24.59
transmission lines.
6 000 23.9s
In the early days of high-voltage transmission, corona 0 29.92 8 000 22.22
was something which had to be avoided, largely because of 1000 28.86 LO 000 20.58
the energy loss associated with it. In recent years the RI 2000 27.82 15 000 16.88
(radio influence) aspect of corona has become more im- 3000 26.81 20 000 13.75
portant. In areas where RI must be considered, this factor
might establish the limit of acceptable corona performance.
Under conditions where abnormally high voltages are standard conditions (29.92 in. of Hg. and 77°F) the air
present, corona can affect system behavior. It can reduce density factor equals 1.00. The air density factor should
the overvoltage on long open-circuited lines. It will atten- be considered in the design of transmission lines to be built
uate lightning voltage surges (see Sec. 29 Chap. 15) and in areas of high altitude or extreme temperatures. Table
switching surges. l7 By increasing Jhe electrostatic cou- 10 gives barometric pressures as a function of altitude.
pling between the shield mire and phase conductors, co- Corona in fair weather is negligible or moderate up to
rona at times of lightning strokes to towers or shield wires a voltage near the disruptive voltage for a particular con-
reduces the voltage across the supporting string of insu- ductor. Above this voltage corona effects increase very
lators and thus, in turn, reduces the probability of flash- rapidly. The calculated disruptive voltage is an indicator
over and improves system performance. On high-voltage of corona performance. A high value of critical disruptive
lines grounded through a ground-fault neutralizer, the in- voltage is not the only criterion of satisfactory corona
phase current due to corona loss can prevent extinction of performance. Consideration should also be given to the
the arc during a line to ground fault.28 sensitivity of the conductor to foul weather. Corona in-
creases somewhat more rapidly on smooth conductors than
it does on stranded conductors. Thus the relative corona
6. Factors Affecting Corona characteristics of these two types of conductors might
At a given voltage, corona is determined by conductor interchange between fair and foul weather. The equation
diameter, line configuration, type of conductor, condition for critical disruptive voltage is:
of its surface, and weather. Rain is by far the most im-
portant aspect of weather in increasing corona. Hoarfrost Eo=go 6% T m log, D/r (i93)
and fog have resulted in high values of corona loss on ex- where:
E, = critical disruptive voltage in kv to neutral
perimental test lines. However, it is believed that these
g,=critical gradient in kv per centimeter. (Ref. 10 and 16 use
high losses were caused by sublimation or condensation of g,=21.1 Kv/cm rms. Recent work indicates value given in
water vapor, which are conditions not likely to occur on an Sec. 10 is more accurate.)
operating line because the conductor temperature would T =radius of conductor in centimeters
normally be above ambient. For this reason, measure- D = the distance in centimeters between conductors, for single-
ments of loss made under conditions of fog and hoarfrost phase, or the equivalent phase spacing, for three-phase
might be unreliable unless the conductors were at operat- voltages.
ing temperatures. Falling snow generally causes only :a m=surface factor (common values, 0.84 for stranded, 0.92 for
moderate increase in corona. Also, relative humidity, tem- segmental conductors)
perature, atmospheric pressure, and the earth’s electric 6 =nir density factor
field can affect corona, but their effect is minor compared
to that of rain. There are apparently other unknown factors The more closely the surface of a conductor approaches
found under desert conditions which can increase corona.lg a smooth cylinder, the higher the critical disruptive volt-
The effect of atmospheric pressure and temperature is age assuming constant diameter. For equal diameters, a
generally considered to modify the critical disruptive volt- stranded conductor is usually satisfactory for 80 to 85 per-
age of a conductor directly, or as the x power of the air cent of the voltage of a smooth conductor. Any distortion
density factor, 6, which is given by: of the surface of a conductor such as raised strands, die
burrs, and scratches will increase corona. Care in handling
& 17.9b conductors should be exercised, and imperfections in the
459+“F (W surface should be corrected, if it is desired to obtain the
best corona performance from a conductor. Die burrs and
where die grease on a new conductor, particularly the segmental
Z,= barometric pressure in inches of mercury type, can appreciably increase corona effects when it is
“F = temperature in degrees Fahrenheit. first placed in service. This condition improves with time,
taking some six months to become stable.
The temperature to be used in the above equation is gen- StrigeP concluded that the material from which a con-
erally considered to be the conductor temperature. Under ductor is made has no effect on its corona performance. In
Chapter 3 Characteristics of Aerial Lines 57

Curve l-l.4 in. HH copper. 6=0.88. Ref. 19. Corona loss test
made in desert at a location where abnormally high corona loss is
observed on the Hoover-Los Angeles 287.5~kv line, which is strung
with this conductor. Measurement made in three-phase test line.
4 This particular curve is plotted for 6 =0.88 to show operating con-
dition in desert. All ot,her curves are for 6 = 1.00.
Curve 2-Same as curve 1, except converted to 6 = 1.00.
Curve 3-1.4 in. HH copper. Ref. 12. Corona loss test made in
California. Comparison with curve 2 shows effect of desert condi-
tions. Measurements made on three-phase test line. 30-foot flat
-0 spacing, 16-foot sag, 30-foot ground clearance, iO0 feet long.
Curve 4-1.1 in. HH. Ref. 13. Measurements made on three-phase
test line, 22-foot flat spacing, 16-foot sag, 30-foot clearance to
ground, 700 feet long.
Curve 5-1.65 in.. smooth. Ref. 12. This conductor had a poor sur-
face. Measurements made on three-phase test line, 30-foot spac-
ing, 16-foot sag, 30-foot ground clearance, 700 feet long.
Curve 6-1.65 in. smooth aluminum. Ref. 27. Reference curve ob-
tained by converting per-phase measurement to loss on three-phase
line. Dimensions of line not given.
Curve 7-1.04 in. smooth cylinder. Ref. 23. In reference this con-
ductor is referred to as having an infinite number of strands.
Plotted curve obtained by conversion of per-phase measurements
9
to three-phase values, using an estimated value for charging kva,
to give loss on a line having 45-foot flat configuration.
Curve 8-1.96 in. smooth aluminum. Ref. 23. Refcrcnce curve gives
three-phase loss, but line dimensions are not given.
Curve 9-1.57 in. smooth. Ref. 23. This conductor was smooth and
clean. Reference curve gives per-phase values. Plotted curve is
for 45-foot flat spacing.

r
3 f Fig. 27-Fair-Weather Corona-Loss Curves for Smooth Con-
'("L-L ductors; Air Density Factor, 6 = 1.

imIllst,rial areas, foreign material deposited on the con- opment of three formulas(10~14~16) generally used in this
cIuc:tor can, in some cases, seriously reduce the corona per- country (Reference 18 gives a large number of formulas).
I‘ornmnce. (Reference 28 gives some measurements made The Carroll-Rockwell and the Peterson formulas are con-
in an industrial area.) sidered the most accurate especially in the important 10~
Corona is an extremely variable phenomenon. On a con- loss region (below 5 kw per three-phase mile). The Peter-
tl~~c:~,or energized at a voltage slightly above its fair weather
son formula, when judiciously used, has proved to be a re-
corona-starting voltage, variations up to 10 to 1 in corona liable indicator of corona performance (see Sec. 9) for
loss and radio-influence factor have been recorded during transmission voltages in use up to this time. Recent work
fair weather. The presence of rain produces corona loss on on corona loss has been directed toward the extra-high-
:Lc*ontluctor at voltages as low as 65 percent of the voltage voltage range and indicates that more recent information
XI. \vhicah the same loss is observed during fair-weather. should be used for these voltages.
‘I’llus it is not practical to design a high-voltage line such Fair-weather corona-loss measurements made by a num-
tlmt it will never be in corona. This also precludes ex-
ber of different investigators are shown in Figs. 27, 28, and
pressing a ratio between fair- and foul-weather corona, 29. All curves are plotted in terms of kilowatts per three-
*kc the former might be negligibly small. phase mile. The data presented in these curves has been
If a conductor is de-energized for more than about a day, corrected for air density factor, 6, by multiplying the test
(:orona is temporarily increased. This effect is moderate voltage by 1/h2j3. Some error might have been mtroduced
(‘omparcd to that of rain. It can be mitigated by re-ener- in these curves because in most cases it was necessary to
gizing a line during fair weather where such a choice is POS- convert the original data from per-phase measurements.
sible. The conversions were made on the basis of voltage gradient
at the surface of each conductor. The curves should be
7. Corona LOSS used as an indicator of expected performance during fair
Extensive work by a large number of investigators has weather. For a particular design, reference should be made
been done in determining corona loss on conductors oper- to the original publications, and a conversion made for the
ated at various voltages. This work has lead to the devel- design under consideration. The relation between fair-
Characteristics of Aerial Lines Chapter 3

Curve l-l.4 in. ACSR. Ref. 12. Conductor was washed with gaso-
line then soap and water. Test configuration: three-phase linf>,
30-foot flat spacing, 16-foot, sag, 30-foot ground c.lrar:lnc*r, 700 fret
long.
Curve 2-1.0 in. ACSR. Ref. 11. Conductor wveathercd by esposurc
to air without continuous energization. Test configur:ktion: threc-
phase line, 20-foot flat spacing, iO0 feet long.
Curve 3-1.125 in. hollow copper. Ref. 14. JVashed in same mannel
as for curve 1. Test configuration: three-phase line, 22-foot Rat
spacing.
Curve 4-1.49 in. hollow copper. Ref. 14. \Yashed in same manner
as for curve 1. Test configurntion: three-phase line, 30-foot f1:lt.
spacing, 16-foot sag, 30-foot ground clearance, 700 feet long.
Curve 5-2.00 in. hollow aluminum. Ref. 14. \Yashcd in same man-
ner as for curve 1. Test configuration: three-phase line, 30-foot.
flat spacing, 16-foot sag, 30-foot ground cleurnncc, TOOfeet long.
I-
Curve 6-l .09 in. steel-aluminum. Ref. 22. Reference curve is aver-
age fair-weather corona loss obtained by converting per-ph:kse
measurements to three-phase values, for a line 22.9 foot flat, spat-
ing, 32.8 feet high. This conductor used on 220-kv lines in Swetlen
which have above dimensions.
,- Curve 7-1.25 in. steel-aluminum. Ref. 22 App. A. Plotted curve
obtained by estimating average of a number of fair-weather per-
phase curves given in reference and converting to three-phase loss
for line having 32-foot flat spacing, 50-foot average height.
Curve 8-1.04 in. steel-aluminum, 24-strand. Ref. 23. Plotted curve
I-
obtained by conversion of per-phase measurements to three-phnsc
values, using an estimated value for charging kva, to give loss on n
line having 45-foot Aat configuration.
Curve 94.91 in. Hollow Copper. Ref. 11. Conductor washed.
i- Test configuration: three-phase line, 20-foot flat spacing, TOOfeet
long.

d
0 IC)O I Fig. 28-Fair-Weather Corona-Loss Curves for Stranded Con-
K"L-L ductors; Air Density Factor, 6 = 1.

and foul-weather corona loss and the variation which can sion line should be operated at a voltage well below the
be expected during fair weather is shown in Fig. 30 for voltage at which the loss begins to increase rapidly under
one conductor. fair-weather eonditions. Operation at or above this point
Corona loss on a satisfactory line is primarily caused by can result in uneconomical corona loss. A very careful an-
rain. This is shown by the fairly high degree of correlation alysis, weighing the annual energy cost and possibly the
between total rainfall and integrated corona loss which has, maximum demand against reduced capitalized line cost,
twen noted.(2’j26r41) The corona loss at certain points on a; must be made if operation at a voltage near or above the
trunsmission line can reach high values during bad storm knee of the fair-weather loss curve is contemplated.
conditions. However, such conditions are not likely to oc- Corona loss on a conductor is a function of the voltage
cur simultaneously all along a line. Borgquist and Vre- gradient at its surface. Thus the effect of reduced con-
them expect only a variation from 1.G to 16 k-w per mile, ductor spacing and lowered height is to increase the corona
with an average value of (5.5 kw per mile, on their 380-kv loss as a function of the increased gradient. On transmis-
lines now under construction in Sweden. The measured sion lines using a flat conductor configuration, the gradient
loss on their esperimental line varied from 1.6 to 81 kw per at the surface of the middle phase conductor is higher than
mile. The calculated fair-weather corona loss common in on the outer conductor. This results in corona being more
the U.S.A. is generally less than one kw per mile, based on prevalent on the middle conductor.
calculations using Reference 16. Where radio-influence
must be considered, the annual corona loss will not be of 8. Radio Influence (RI)
much economic importance20, and the maximum loss will Radio influence is probably the factor limiting the choice
not constitute a serious load. of a satisfactory conductor for a given voltage. The RI
Corona loss is characterized on linear coordinates by a performance of transmission lines has not been as thor-
rather gradual increase in loss with increased voltage up to oughly investigated as corona loss. Recent publications
the so-called “knee” and above this voltage, a very rapid (see references) present most of the information available.
increase in loss. The knee of the fair-weather loss curve is RI plotted against voltage on linear graph paper
generally near the critical disruptive voltage. A transmis- is characterized by a gradual increase in RI up to a vol-
Chapter 3 Characteristics of Aerial Lines

Curve l-4/0.985/15.7* (Smooth) Ref. 25. 6 not given, but assumed


1.10, which is average value for Germany. Rcfcrcnre curve ob-
tained by converting single-phase measurements to three-phnsc
values on the basis of surface gradient. Dimensions of line used in
making conversion are not given.
Curve 2--4/0.827/15.7* (stranded aluminum-steel). Ref. 25. 6 =
1.092. See discussion of Curve 1.
Curve 3-3/0.985/11.8* (Smooth). Ref. 26. 6 = 1.092. Refcrcncc
curve gives single-phase measurements versus line-to-ground volt-
age, but it is not clear whether actual test voltngc or equivalent,
voltage at line height is given. Latter was used in making the ron-
version to three-phase. If t,his is wrong, curve is approximately
15 percent low in voltage. Convcrtetl to flat configuration of 45
feet.
Curve 4-2/1.00/17.7* (Stranded aluminum-steel). 6 = 1.01. Ref. 12,
App. A. Reference curve gives per-phase mrasurcmcnts versus
gradient. Converted to three-phase corona loss on line of 42.5-foot
average height, 39.4-foot flat configuration.
Curve 5-2/1.25/17.7* (Stranded aluminum-steel) 6 not given, prob-
ably close to unity. Ref. 12. Reference curve, which gives three-
phase corona loss, was converted from per-phase mcasuremmts.
Dimensions 42.5 feet average height, 39.4 feet, flat configuration.
This conductor was selected for USCon the Swedish 380-kv system.
Original author probably selected a worse fair-weather condit,ion
than the writer did in plotting curve 4, which could account for
their closeness.
Curve 6-2/1.04/23.7* (Stranded aluminum-steel). 8 not given. Ref.
13. Plotted curve is average of two single-phase fair-weather
curves, converted to three-phase loss for 45-foot Rat configuration.
See Curve 7.
Curve 7-2/1.04/15.7* (St,randed aluminum-steel). 6 not given. Ref.
13. Plotted curve is average of two single-phase fair-weather
curves, converted to three-phase loss for 45-foot, Hat configuration.
Data for curves 6 and 7 were taken at same time in order to show
effect of sub-conductor separation.
*Bundle-conductor designation-number of sub-conductors/out-
side diameter of each sub-conductor in inches/separation between
adjacent sub-conductors in inches.
Fig. 29-Fair-Weather Corona-Loss Curves for Two-, Three-, and Four-conductor Bundles; Air Density Factor, 6 = 1.00.

tage slightly below the minimum voltage at which meas- range of communication services likely to be encountered,
urable corona loss is detected. Above t,his voltage, the should be known. An evaluation of these factors in terms
increase in the RI is very rapid. The rate of increase in RI of their effect on various communication services must take
is influenced by conductor surface and diameter, being into consideration many things. These are available signal
higher for smooth conductors and large-diameter con- intensities along the line, satisfactory signal-to-noise ra-
tluctors. Above a certain voltage, the magnitude of the tios, effect of weather on the RI factors and on the im-
RI field begins to level off. For practical conductors, the portance of particular communication services, number
lcvcling off value is much too high to be acceptable, and and type of receivers in vicinity of the line, proximity of
\\hcre RI is a factor, lines must be designed to operate be- particular receivers, transfer of RI to lower-voltage cir-
low the voltage at which the rapid increase starts during fair cuits, the general importance of particular communication
\v&her. Figures 32 and 33 are characteristic RI curves. services, and means for improvement of reception at indi-
The relation between fair- and foul-weather corona per- vidual receiver locations.21 For extra-high-voltage and
formance is shown in Fig. 32. double-circuit high-voltage lines the tolerable limits of RI
Xn evaluation of RI in the design of a high-voltage line might be higher because the number of receivers affected,
must consider not only its magnitude, but its effect on the the coupling to lower voltage circuits, and the coupling to
various communication services which require protection. receiver antennas is reduced. Also fewer lines are required
-\mplitude-modulated broadcasting and power-line carrier for the same power handling ability, and wider right-of-
arc the most common services encountered but other serv- ways are used which tend to reduce the RI problem.
ices such as aviation, marine, ship-to-shore SOS calls, po- Although RI increases very rapidly with increased gradi-
lice and a number of government services might also have ent at the surface of a conduct,or, theoretical considerations
to be considered. of the radiation characteristics of a transmission line as
In determining the RI performance of a proposed line, spacing is reduced, indicate that the RI from a transmission
the magnitude of the RI factors for the entire frequency line will not be seriously affected by reduced spacing.42
60 Characteristics of Aerial Lines Chapter 3

Standard radio-noise meters35J6can measure the aver-


age, quasi-peak, and peak values of the RI field. The aver-
35 age value is the amplitude of the RI field averaged continu-
ously over s second. For quasi-peak measurements, a cir-
cuit having a short time constant (0.001-0.01 sec.) for
charging and a long time constant (0.3 to 0.6 sec.) for dis-
charging is used, with the result that the meter indication
3c l-
is near the peak value of the RI field. Aural tests of radio
reception indicate that quasi-peak readings interpreted in
terms of broadcast-station field strengths represent more
accurately the “nuisance” value of the RI field. The peak
25,- value is the maximum instantaneous value during a given
!i period. The type of measurements made must be known
s before evaluating published RI information or misleading
: conclusions can be drawn.
2 2c)- The lateral attenuation of RI from a transmission line
Q
depends on the line dimensions and is independent of volt-
$ ----CLEAR age. At distances between 40 and 150 feet from the outer
Y conductor, the attenuation at 1000 kc varies from 0.1 to 0.3
I!j- db per foot, with the lower values applying generally to
OVERCAST, high-voltage lines. Typical lateral attenuation curves are
HOARFROST,’
shown in Fig. 34. Lateral attenuation is affected by local
FOG
conditions. Because of the rapid attenuation of RI later-
I( ally from a line, a change of a few hundred feet in the loca-
tion of a right-of-way can materially aid in protecting a
communication service.
9. Selection of Conductor
4S-
In the selection of a satisfactory conductor from the
standpoint of its corona performance for voltages up to
230 kv, operating experience and current practice are the
best guide. Experience in this country indicates that the
400 500 60C) corona performance of a transmission line will be satisfac-
tory when a line is designed so that the fair-weather
K”L-L
corona loss according to Peterson’s formula,.‘6 is less than
Fig. 30-Corona Loss on 1.09 Inch Stranded Aluminum-Steel one kw per three-phase mile. Unsatisfactory corona per-
Conductor under Different Weather Conditions. This con-
ductor is in use on the Swedish 220-kv system. Note variation formance in areas where RI must be considered has been.
in fair-weather corona loss and the relation between fair- and reported for lines on which the calculated corona loss is in
foul-weather corona loss. Plotted curves obtained by convert- excess of this value, or even less in the case of medium high-
ing per-phase measurements to three-phase values for a line voltage lines. Figure 31 is based on Peterson’s formula and
having 32-foot flat spacing, 50-foot average height. No cor-
rection made for air density factor. Ref. 22, App. A.
indicates satisfactory conductors which can be used on
high-voltage lines. For medium high-voltage lines (135 kv)
considerably more margin below the one kw curve is neces-
The conductor configuration, the number of circuits, and sary because of the increased probability of exposure of re-
the presence of ground wires affect the radiation from the ceivers to RI from the line, and a design approaching 0.1
line with a given RI voltage on the conductors. Very little kw should be used.
is known about the radiation characteristics of transmis-
sion lines and caution should be exercised in applying data 10. Bundle Conductors
not taken on a line configuration closely approximating the A “bundle conductor” is a conductor made up of two or
design under consideration. more ‘(sub-conductors”, and is used as one phase conduc-
The RI field from a transmission line varies somewhat tor. Bundle conductors are also called duplex, triplex, etc.,
as the inverse of the radio frequency measured. Thus serv- conductors, referring to the number of sub-conductors and
ices in the higher-frequency bands, (television3’, frequency- are sometimes referred to as grouped or multiple con-
modulated broadcasting, microwave relay, radar, etc.) are ductors. Considerable work on bundle conductors has
less apt to be affected. Directional antennas which are been done by the engineers of Siemens-Schuckertwerkez7
generally used at these frequencies, on the average, in- who concluded that bundle conductors were not economi-
crease the signal-to-noise ratio. The lower signal strengths, cal at 220 kv, but for rated voltages of 400 kv or more, are
and wider band-widths generally found in the high-fre- the best solution for overhead transmission. Rusck and
quency bands can alter this picture somewhat. Frequency- Rathsman46 state that the increase in transmitting capac-
modulated broadcast is inherently less sensitive to RI ity justifies economically the use of two-conductor bun-
because of its type of modulation. dles on 220-kv lines.
Chapter 3 Charscteristics of Aerial Lines 61

360

320

60 - SEA LEVEL

40

CONDUCTOR DIAMETER IN INCHES


664
,!!I 2 Ii/! I/O 3/04/o
!I !
250 350 500 I COPPER-THOUSANDS OF CIRCULAR MILLS OR AWG
750 1000
1: II:!! !
6 4 2 I I/O 3/o 4/o IACSR-MCM OR AWG
300 397.5 500 666 795 1033.5 1272 1590

~SOLIO~ - I2 STRANDS - c 29 STRANDS -NUMBER OF STRANDS IN


- 6 STRANDS -----3- I6 STRANDS - OUTSIDE LAYER

Fig. 31-Quick-Estimating Corona-Loss Curves. Curves based on Peterson’s formula with a few check points from the
Carrol and Rockwell paper for comparison.

The advantages of bundle conductors are higher disrup- where the symbols have the same meaning as used in Eq.
1ivc voltage with conductors of reasonable dimensions, re- (79a). This equation is the same as equation (79a), except
t111c:od surge impedance and consequent higher power capa- that surface factor, m, and air density factor, 6, have been
Ijilitics, and less rapid increase of corona loss and RI with omitted. These factors should be added to Eqs. 80 and 81
increased voltage .23,27*28 These advantages must be weighed for practical calculations. For a two-conductor bundle, the
:tgainst increased circuit cost, increased charging kva if it equation for maximum gradient at the surface of a sub-
cannot be utilized, and such other considerations as the conducto? is:
l:trgc amount of power which would be carried by one cir-
cuit. It is possible with a two-conductor bundle composed e(lS-B/S)
9=
of conductors of practical size to obtain electrical charac- 2rlog& (80)
t&tics, excepting corona, equivalent to a single conductor
11~to eight inches in diameter. where :
‘l’hcoretically there is an optimum sub-conductor separa- S = separation between sub-conductors in centimeters.
ti~ii for bundle conductors that will give minimum crest
gtndicnt on the surface of a sub-conductor and hence high- Because of the effect of the sub-conductors on each
(‘St disruptive voltage. For a two-conductor bundle, the other, the gradient at the surface of a sub-conductor is not
sc’parntion is not very critical, and it is advantageous to uniform. It varies in a cosinusoidal manner from a maxi-
iisc a larger separation than the optimum which balances mum at a point on the outside surface on the line-of-cen-
the reduced corona performance and slightly increased cir- ters, to a minimum at the corresponding point on the inside
cuit cost against the advantage of reduced reactance. surface. This effect modifies the corona performance of a
;\ssuming isolated conductors which are far apart com- bundle conductor such that its corona starting point cor-
I):ucd to their diameter and have a voltage applied be- responds to the voltage that would be expected from calcu-
t\vcen them, the gradient at the surface of one conductor lations, but the rate of increase of corona with increased
is given by:
voltage is less than for a single conductor. This effect can
g=e (79b)
be seen by comparing curve 6 of Fig. 28 with curve 2
of Fig. 29. Cahen and Pelissier21*24concluded that the
rlog,D/r
corona performance of a two-conductor bundle is more
accurately indicated by the mean between the average
62 Characteristics of Aerial Lines Chapter 3

I I
II I
700
1 !.
02600
$ I I I I I I I I I II,
I I

80
60

I iI
f

300 /,I

,I/
1
/I I I
200
IO
8 8
6 6 too

2 .K VL- L

Fig. 33-Fair-Weather Radio-Influence Field from a Trans-


mission Line as a Function of Voltage. Measurements made
opposite mid-span on the 230-kv Covington-Grand Coulee
“: Line No. 1 of the Bonneville Power Administration. RI values
KILOVOLTS are quasi-peak. 1.108 inch ACSR conductor, 27-foot flat spac-
Fig. 32-Radio influence and corona loss measurements made ing, 41-foot height, test frequency-800 kc.
on an experimental test line. Ref. 26.

and maximum gradient at the surface of a sub-conductor,


which is given bv:
g=e(l+~lS)
2rlog& (81)
If it is desired to determine the approximate disruptive
voltage of a conductor, g,,=21.1 I+; kv per centi-
4
( -b301)
meter rms can be substituted for g and the equations solved
for e, in kv rms. This value neglects air density Factor
and surface factor, which can be as low as 0.80 (consult
references 10 and 16 for more accurate calculations).
380 kv Systems using bundle conductors are being built
or under consideration in Sweden, France, and Germany.
0 ,

Curve I-Average lateral attenuation for a number of transmission


lines from 138- to 450-kv. 0 X n 0 are plotted values which apply
to this curve only. Test frequency 1000 kc. Ref. 21. 2
Curve 2-Lateral Attenuation from the 220-kv Eguzon-Chaingy line
in France. Line has equilateral spacing, but dimensions not given.
Distance measured from middle phase. Test frequency--868 kc. I I 1 I
Ref. 21. '0 40 80 120 160 200
Curve 3-Lateral Attenuation from 230-kv Midway-Columbia Line HORIZONTAL DISTANGE FROM OUTSIDE CONDUCTOR-FEET
of the Bonneville Power Administration. Conductor height 47.5 Fig. 34-Lateral Attenuation of Radio Influence in Vicinity of
feet, test frequency 830 kc. Ref. 42. High-Voltage Transmission Lines.
Chapter 3 Characteristics of Aerial Lines 63

25. Recherches Esperimentales sur lc Comportemcnt des Conduc-


REFERENCES teurs des Lignes a 400 KV, F. Cahen, R. Pelissicr, Bull. &c.
1. I,ine Conductors-Tidd 500-kv Test Lines, by E. L. Peterson, Fran~aise des Electriciens, 6th Series, Vol. IS So. 99, Dec. 19-I!).
1). 11. Simmons, L. F. Hickernell, 11. E. Noycs. AIEE Paper 26. ,\Iecnnisme de 1’Effet de Couronne sur les Lignes de Transport
47-214. d’Energie en Courant Alternnt,if, 1~. Pelissier, D. Rcnnudin
2, ,~~~mnrc/ricol C~mpor~et~./s,(a book), by C. F. \I-ngncr and R. D. Bull. Sot. Fran&se rles Electriciens, 6th Series, Vol. 9, Feb. l!)-lL).
I:varis. 11cGraw-Ilill Book Company, 1933. 27. Bundelleitungen, W. v. Mnngoldt, F. Busemann, A. Bucrklin,
3. 1tctlucing Inductance on Adjacent Transmission Circuits, by G. hlarkt, F. I. Kromer, Siemens-Schuckcrtwerke, A. G. pam-
II. 13. D\vight, Elcclrical TVorZd, Jan. 12, 1924, p 89. phlet, Berlin-Siemensstadt, 1942.
‘1. electric Power Trunsmission (a book), by L. F. Woodruff. John 28. 400-KV Transmission Lines with Special Reference to Multiple
\Vilcy and Sons, Inc., 1938. Conductor Lines (Bundelleitungen), British Intelligence Objcc-
5, ~lecl~~ccrl Trunsmis.sion of Power andSignals (a book), by Edward tives Sub-committee, Final Report So. 1833, Item So. 33, S.O.
\V. Kimbark. John Wiley and Sons, Inc., 1949. Code-No. 51-8275-33, Technical Information and Documents
6. Ihating and Current Carrying Capacity of Bare Conductors for Unit 40, Cadogan Square, London S.W.l England.
Outdoor Service, by 0. R. Schurig and C. W. Frick, General 29. Drehstromfernuebertragung mit Bundelleitern, G. Markt, B.
fllcclric Review Volume 33, Number 3, March 1930, p l-12. atengele, Elektrotechnik und Mnschinenbau, 1932, page 293.
7. lfy-Therm Copper-An Improved Overhead-Line Conductor, 30. Die Wirtschaftliche Bemessung von Bundelleitcr-Leitungen
by L. F. I~Iickernell, A. A. Jones, C. J. Snyder. AIEE Paper 49-3, Elektrotechnik und ,Ifaschinenbuu, 1935, page 410.
8. /&chid Chnractcristics of Trunsmissior~ Circuits, (a book), by 31. 500-KV Experimental Station at Chevilly: Use of Bundle Con-
\\‘. Scsbit, Westinghouse Technical Night School Press, 1926. ductors; Corona Effects; Clearances, P. Ailleret, I”. Cthen, Conf.
!I. IIcsistancc and Rcactancc of Commercial Steel Conductors, by Int. des Grands Res. Electr. a Haute Tension (CICRE), 1948,
Prof. H. 1~. Dwight, Eleclric Journu1, January 1919, page 25. paper No. 410.
10. l)ic~lcctric Phenomena in High-Voltage Engineering (Book) F. 32. Relative Surface Voltage Gradients of Grouped Conductors,
\\‘. Peek, Jr. .\IcGraw-Hill Book Co. Inc. Sew York, 1929. M. Temoshok, A.Z.E.E. !!‘runsactions Vol. 67, Part II, pages
l l. Corona Loss ~Ieasurements on a 220-KV BO-Cycle Three-Phase 1583-9.
l:spwimental Line, J. S. Carroll, L. H. Browr, D. P. Dinapoli, 33. Discussion of Reference 32 by C. F. Wagner, A.Z.E.E. Trunsuc-
21.I.E.E. 7’raUsnclio7~s Vol. 50, 1931, pages 36-43. lions Vol. 67, Part II, page 1590.
12. Corona I.osscs from Conductors I.4-inch Diameter, J. S. Carroll, 34. Three-Phase Multiple-Conductor Circuits, E. Clarke, A.Z.E.E.
13. Cozzens, T. 11. Blakeslee, A.I.E.E. Transactions V’ol. 53, Trunsacfions, Vol. 51, 1932, page 809, Appendix C by S. Crary.
1!)3-4,pages 1727-33. 35. llethods of Measuring Radio Noise 1940--A report of the Joint
13. Corona Losses at 230 XV with One Conductor Grounded, J. S. Coordination Committee on Radio Reception of EEI, SE.\L%,
Carroll, 1). AI. Simmons, A.I.E.E. Transactions Vol. 54, 1935, and RllA.
pages 8-48-7. 36. Proposed American Standard Specification for a Radio Soise
14. Empirical ;1Iethod of Calculating Corona Loss from High-Volt- Meter-O.015 to 25 megacycles. Oct. 1949 (Published for one
age Transmission Lines, J. S. Carroll, AI. M. Rockwell, A.I.E.E. year trial use).
Trunsuctions Vol. 56, 1937, page 558. 37. Television Interference Seldom Comes from Power Systems, F.
15. Corona Loss Xleasurcments for the Design of Transmission L. Greene, Electrical Works, Jan. 16, 1950, pages 55-9.
Lines to Operate at Voltages between 220-KV and 330-KV. J. 38. Effect of Radio Frequencies of a Power System in Radio-Re-
S. Carroll, B. Cozzens, A.I.E.E. Transactions Vol. 52, 1933, ceiving Systems, C. V. Aggers, W. E. Pakala, W. A. Stickel,
pages 55-62. A.Z.E.E. Tmnsactions, Vol. 62, 1934, pages 169-72.
16. Development of Corona Loss Formula (discussion of reference 39. Measurements Pertaining to the Coordination of Radio Recep-
15), \V. S. Peterson, A.Z.E.E. Transactions Vol. 52, pages 62-3. tion with Power Apparatus and Systems, C. i\l. Foust, C. W.
17. New Techniques on the Anncom-Electric Analog Computer, E. Frick,A.I.E.E. TrunsaclionsVol,62,1943,pages284-91,disc. 458.
L. Harder, J. T. Carleton, AIEE Technical Paper 50-85. 40. Radio Interference Suppression in Canada, H. 0. .\Ierrimnn,
18. I<:i:inncues Verlustgesetz der Wechselspannungskorona, H. Prinz, AIEE paper No. 47-140.
Uiss. Veroff. Siemens-Schuckertwerke A.G.-Vol. XIX, July 41. Results of Tests Carried out at the 500-kv Experimental Station
26, l!LlO. of Chevilly (France), Especially on Corona Behavior of Bundle
19. Ijesert ~Ieasurements of Corona Loss on Conductors for Opera- Conductors, F. Cahen, A.I.E.E. Trunsaclions, 1948, Vol. 67,
1ion above 230 KV, W. S. Peterson, B. Cozzens, J. S. Carroll, as Part II, pages 1118-25.
presented AIEE Convention Pasadena, Calif., June 12-16, 1950. 42. Radio-Noise Influence of 230-KV Lines, H. L. Rorden, A.Z.E.E.
26. Transmission of Electric Power at Extra High Voltages, Philip ?‘runsaction, Vol. 66, 1947, pages 677-8: disc. 682.
Sporn, .4. C. illonteith, A.I.E.E. Trunsuctions, Vol. 66, 1947 43. Radio Influence from IIigh Voltage Corona, G. R. Slemon, AIEE
pages 1571-7, disc. 1582. paper No. 49-60.
21. Progress Report on 500-KV Test Project of the American Gas 44. Comparative Investigation of D.C.- and A.C.-Corona on T\vo-
and Electric Company-Corona, Radio Influence, and Other Conductor Transmission Lines (In German), It. Strigel, 1Vis-
Factors. Philip Sporn, A. C. Monteith, as presented AIEE senschuftliche Veroeftentlichungen Aus Den Siemens-Werken, Vol.
Convention, Pasadena, Calif. June 12-16, 1950. 15, Part 2, 1936, pages 68-91.
%. The Swedish 380-KV System, W. Borgquist, A. Vrethem, see 45. The Swedish 380 KV System, A. Rusck, Bo G. Rathsman, Elec-
:L~SO Appendix, A. B. Henning, S. Skagerlind, CIGRE paper 412, trical Engineering, Dec. 1949, pages 1025-g.
1948 session, June 24 to July 3, Conference Internationale des 46. Series Capacitor and Double Conductors in the Swedish Trsns-
Grands Resesux Electriques a Haute Tension. mission System, A. Rusck, 130 G. Rathsman, Electrical Engineer-
23. Influence, sur 1’Effet de Couronne, du Diametre et du Profil des ing, Jan. 1950, pages 53-7.
Cables des Lignes Aeriennes a Tres Haute Tension, F. Cahen, R. 47. Effect of Earthing on Corona Losses, Conductor Diameter rind
Pelissier, Revue Generale de I’Eleclricite’, Vol. 58, pages 279-90. Length of Insulator Strings, The Brown Boveri Review, Vol.
*4. L’emploi de Conducteurs en Faisceaux pour L’Armement des XXXV Nos. 7/8, July/August, 1948, pages 192-201.
Lignes a T&s Haute Tension, F. Cahen, R. Pelissier. Bull. Sot. 48. The Transmission of Electric Power (a book), by W. A. Lewis,
Fruncaise des Etectriciens, 6th Series, Vol. VIII, No. 79, 1948. (1948 Lithoprinted Edition) Illinois Institute of Technology.
CHAPTER 4

ELECTRICAL CHARACTERISTICS OF CABLES


Original Author: Rwised by:
H. N. Muller, Jr. J. S. Williams

ABLES are classified according to their insulation as


paper, varnishccl-cambric, rubber, or asbestos, each
c of these materials having unique characteristics
\vhich render it suitable for particular applications. Be-
cause cables for power transmission and distribution are
cornposed of so many different types of insulation, con- (a) Single-conductorsoli~l,~omp:~c~t-Iollrl(l
conductor.
ductors, and sheathing materials, the discussion here must
be limited to those cable designs most commonly used.
Reasonable estimates of clcctrical characteristics for cables
not list4 can be obtained in most cases by reading from
the table for a cable having similar physical dimensions.
Pnpcr can be wound ont,o a. conductor in successive lay-
ers to achicvc a requiretl dielectric strength, and this is the
insulation generally used for cables operating at 10 000
volts and higher. Paper insulation is impregnated in dif-
ferent ways, and accordingly cables so insulated can be (b) Three-conductorbelt&, compact-sectorconductors.
sub-divided into solid, oil-filled, or gas-filled types.
Solid paper-insulated cables are built up of layers of
paper tape wound onto the conductor and impregnated
with a viscous oil, over which is applied a tight-fitting,
estrudcd lead sheath. Multi-conductor solid cables are
also available, but the material shown here covers only
single- and three-conductor types. Three-conductor cables
are of either belted or shielded construction. The belted (c) Three-conductorshicldcd, compact-sectorconductors.
assembly consists of the three separately insulated con-
ductors cabled together and wrapped with another layer of
impregnated paper, or belt, before the sheath is applied. In
the shielded construction each conductor is individually
insulated and covered with a thin metallic non-magnetic
shielding tape; the three conductors are then cabled to-
gether, wrapped with a metallic binder tape, and sheathed
with lead. The purpose of the metallic shielding tatie
around each insulated conductor is to control the electro- (d) Single-conductoroil-filled, hollow-strandedconductor.
static stress, reduce corona formation, and decrease the
thermal resistance. To minimize circulating current under
normal operating conditions and thus limit the power loss,
shielding tape only three mils in thickness is used, Solid
single-conductor cables arc standard for all volt,ages from
1 to 69 kv; solid three-conductor cables are standard from
1 to 46 kv. Sample sections of paper-insulated single-con-
ductor,three-conductorbelted,andthree-conductorshielded (e) Three-conductoroil-filled, compact-sectorconductors.
cables are shown in Fig. l(a), (b), and (c) respectively. Fig. l-Paper-insulated cables.
Oil-filled paper-insulated cables are available in single- or Courtesy of General Cable Corporatzon
three-conductor designs. Single-conductor oil-filled cable
consists of a concentric stranded conductor built around an oil channels composed of helical springs that extend
open helical spring core, which serves as a channel for the through the cable in spaces normally occupied by filler
flow of low-viscosity oil. This cable is insulated and material. This construction is shown in Fig. l(e). Oil-
sheathed in the same manner as solid cables, as a compar- filled cables are relatively new and their application has
ison of Figs. l(a) and I(d) indicates. Three-conductor oil- become widespread in a comparatively short time. The oil
filled cables are all of the shielded design, and have three used is only slightly more viscous than transformer oil, and
64
Chapter 4 Electrical Characteristics of Cables 65

remains fllGc1at all operating temperatures. The oil in the


cLLt,le an(1 its connected rcscrvoirs is maintained under
m,,,lcrLLtc pressure so that during load cycles oil may flow
ljC1t,vc>enthe cnblc and the reservoirs to prevent the devel-
,l,,nl(~~lt of voids or excessive pressure in the cable. The
,jI.~~~cnt,ic)nof void formation in paper insulation permits
t I,(%1,~ of grcatlv reduced insulation thickness for a given
,,p~~r:~tingVoltAge. Another advantage of oil-filled cables is
ll,;Lt oil {vi11seep orit, through any crack or opening which
,llBvclops in the sheath, thereby preventing the entrance of
\\.:tt,cr at, the dcfectivc point. This action prevents the
c,cac*llrrcnce of a fault caused by moisture in the insulation,
:Ln~lsince operating records show that this cause accounts
for :Lsignificant percentage of all high-voltage cable faults,
it is intlcctl a real advantage. Single-conductor oil-filled
,.:,I~~(:s:w usetl for voltages ranging from 69 to 230 lw; the
Ils~l:tl wnge for three-conductor oil-filled cables is from 23 Courtesy 01 Genernl Cable Corporation,
1,) (i!) Is. Fig. 3-Cross-section of high-pressure pipe-type gas-filled
( ias-filled cables of the low-pressure type hare recently cable. Oil-filled pipe-type cable may have a similar cross-
t)wome xtnndard up to 46 kv. The single-conductor type section.
employs construction generally similar to that of solid
~::~t)lcs,except that longitudinal flutes or other channels are Compression cable is another high-pressure pipe-type
provitlctl at the inner surface of the sheath to conduct cable in which oil or nitrogen gas at high pressure is intro-
rlit,rogcn along the cable. The three-conductor design em- duced within a steel pipe containing lead-sheathed solid-
ploys channels in the filler spaces among the conductors, type single-conductor cables; no high-pressure oil or gas is
IIIIII:~ like those provided in oil-filled three-conductor introduced directly inside the lead sheaths, but voids with-
(,:I1)1(x The gas is normally maintained between 10 and 15 in the solid-type insulation are prevented by pressure
I)IHII~~ISper square inch gauge pressure, and serves to fill exerted externally on the sheaths. This construction is
:tll cAlc voids and exclude moisture at faulty points in the sketched in Fig. 4.
slicath or joints. During recent years there has been a trend toward the
modification of cable conductors to reduce cost and im-
prove operating characteristics, particularly in multi-con-
ductor cables. Referring to Fig. 5, the first departure from
concentric round conductors was the adoption of sector-
shaped conductors in three-conductor cables. More re-
cently a crushed stranding that results in a compacted
sector has been developed and has found widespread use
for conductor sizes of l/O ,4.W.G. and larger. Its use in
Courtesy of the Olxnile-Callender Cable Company
smaller conductors is not practical. The principal advan-
tages of such a conductor are: reduced overall diameter for
Fig. 2-High-pressure pipe-type oil-filled cable. a given copper cross-section; elimination of space between
the conductor and the insulation, which results in higher
Iligh-pressure cables, of either the oil- or gas-filled vari-
(\ty, are being used widely for the higher range of voltages.
‘I‘tw physical and electrical characteristics are fairly well
1\11o\vn,but their specifications are not yet standardized.
‘1’1~11sr~1application calls for pressure of about 200 pounds
I)~Ysclllare inch, contained by a steel pipe into which three
sin&conductor cables arc pulled. The immediate pres-
WOOof the iron pipe makes difficult the calculations of
(‘iwuit impeclance, particularly the zero-sequence quanti-
tiw. Alost high-pressure cables are designed SO that the
oil or gas filler comes into direct contact with the conduct,or
ills\llation; in oil-filled pipe-type cables a temporary lead
sllwt II can be stripped from the cable as it is pulled into the
StWI pipe; in gas-fillet1 pipe-type cables the lead sheath sur-
I‘~)(lnding each conductor remains in place, with nitrogen
illtr~Aucct1 both inside and outside the sheath SO that no
‘lift‘erential pressure develops across the sheath. Examples
of oil- and gas-filled pipe-type cables are shown in Figs. 2
and 3. Fig. 4-Cross-sectional sketch of compression cable.
Electrical Characteristics of Cables Chapter 4

concentric-strand type, they may also be compact-round,


annular-stranded, segmental, or hollow-core.

I. ELECTRICAL CHARACTERISTICS
The electrical characteristics of cables have been dis-
cussed comprehensively in a series of articles’ upon which
much of the material presented here has been based. This
chapter is primarily concerned with the determination of
the electrical constants most commonly needed for pon-er-
system calculations, particular emphasis being placed on
quantities necessary for the application of symmetrical
components.2 A general rule is that regardless of the com-
plexity of mutual inductive relations between component
parts of individual phases, the method of symmetrical
components can be applied rigorously whenever there is
symmetry among phases. All the three-conductor cables
inherently satisfy this condition by the nature of their con-
struction; single-conductor cables may or may not, although
usually the error is small in calculating short-circuit cur-
rents. Unsymmetrical spacing and change in permeability
resulting from different phase currents when certain meth-
ods of eliminating sheath currents are used, may produce
dissymmetry.
Those physical characteristics that are of general inter-
est in electrical application problems have been included
along with electrical characteristics in the tables of this
section.
All linear dimensions of radius, diameter, separation, or
distance to equivalent earth return are espressed in inches
in the equations in this chapter. This is unlike overhead
(4 transmission line theory where dimensions are in feet; the
use of inches when dealing with cable construction seems
appropriate. Many equations contain a factor for fre-
quency, f, which is the circuit operating frequency in cycles
per second.
1. Geometry of Cables
The space relationship among sheaths and conductors in
a cable circuit is a major factor in determining reactance,
capacitance, charging current, insulation resistance, dielec-
tric loss, and thermal resistance. The symbols used in this
chapter for various cable dimensions, both for single-con-
(h) ductor and three-conductor types, are given in Figs. 6 and
Photographs in this figure furnished by the Okonite-Callender Cable Company
7. Several factors have come into universal use for defining
the cross-section geometry of a cable circuit, and some of
Fig. 5-Cable conductors. these are covered in the following paragraphs.‘,?
Geometric Mean Radius (GMR)-This factor is a
(a) Standard concentric stranded. property usually applied to the conductor alone, and de-
(b) Compact round.
(cl Non-compact sector. pends on the material and stranding used in its construc-
(4 Compact sector. tion. One component of conductor reactance” is normally
(cl Annular stranded (rope core). calculated by evaluating the integrated flux-linkages both
(f) Segmental. inside and outside the conductor within an overall twelve-
(6) Rope stranded. inch radius. Considering a solid conductor, some of the flus
(11)ITollow core. lines lie within the conductor and contribute to total flux-
linkages even though they link only a portion of the total
electrical breakdown; low a-c resistance due to minimizing conductor current; if a tubular conductor having an infi-
of proximity effect; retention of the close stranding during nitely thin wall were substituted for the solid conductor, its
bending; and for solid cables, elimination of many lon- flux would necessarily all be external to the tube. A theo-
gitudinal channels along which impregnating compound can retical tubular conductor, in order to be inductively equiv-
migrate. While most single-conductor cables are of the alent to a solid conductor, must have a smaller radius so
chapter 4 Electrical Characteristics of Cables 67

,LEAD SHEATH
LEAD SHEATH GMRB,, which applies to the group as though it were one
INSULATION comples conductor. This procedllre is illustrated later in
Eq. (18).
Geometric Mean Distance (GMD)Spncings among
conductors, or between conductors and sheaths, are impor-
tant in determining total circuit rcactnnce. The total flus-
linkages surrounding a conductor can be divided into two
components, one extending inward from a cylinder of 1%
inch radiusas discussed in the preceding paragraph, and the
other estending outward from this cylinder to the current
return path beyond which there are no net flus-linknges.3
\ -, The flus-linkages per unit conductor current between the
SINGLE-CONDUCTOR CABLES
EQUILATERALLY SPACED
THREE-CONDUCTOR CABLE 12-inch cylinder and the return path are a function of the
separation between the conductor and its return. The re-
PHASE C
turn path can in many cases bc a parallel group of wires. so
that a geometric mean of all the separations between the
conductor and each of its returns must be used in calcula-
tions. Geometric mean distance, therefore, is a term that
can be used in the expression for external flus-linkages, not
only in the simple case of two adjacent conductors where it
is equal to the distance between conductor centers, but also
in the more complex case where two circuits each composed
of several conductors are separated by an equivalent GRID.
The positive- or negative-sequence reactance of a three-
phase circuit depends on separation among phase conduc-
SINGLE-CONDUCTOR CABLES
tors. If the conductors are equilaterally spaced the distance
UNSYMMETRICALLY SPACED, BUT PERFECTLY TRANSPOSED from one conductor center to another is equal to the GND
among conductors for that circuit. Using the terminology
Fig. 6-Geometry of cables. in Fig. 6,
t.hat the flus-linkages present inside thesolid conductor but GMD3,=S for an equilateral circuit.
:tIwnt \vithin the tube will be replaced by additional link- The subscript here denotes that this G>ID applies to sepa-
:~gc>s Ixt\vcen the tube surface and the limiting cylinder of rations among three conductors. If the conductors are
t\\x!lvc-inch radius. A solid copper conductor of radius d/2 arranged other than equilaterally, but transposed along
(xn Ix: replaced by a theoretical tubular conductor whose their length to produce a balanced circuit, the equivalent
r:ttlirls is O.i7'3 (l/2. This equivalent radius is called the geo- separation may be calculated by deriving a geometric mean
nw~xic mean radius of the actual conductor, denoted herein distance from the cube root of three distance products3 (see
I)y GAIII,, where the subscript denotes reference to only a Chap. 3):
single actual conductor. This quantity can be used in re- GMDx, = YSa,, . S,,c. S,, (1)
:w~.:tnc*e calculations without further reference to the shape
or rnakc-up of the conductor. The factor by which actual The component of circuit reactance caused by flux outside
radius must be multiplied to obtain GMRI, varies with a twelve inch radius is widely identified as “reactance
spacing factor” (zd) and can be calculated directly from
the GMD:
f GM% ohms per phase per mile. (2)
xd = 0.2794 --lo&,-
60 12
When the equivalent separation is less than twelve inches,
as can occur in cable circuits, the reactance spacing factor
is negative so as to subtract from the component of con-
ductor reactance due to flux out to a twelve-inch radius.
The zero-sequence reactance of a three-phase circuit may
Fk Y-Typical sector shape of conductor used in three-con- depend on spacing among conductors and sheath as well as
ductor cables. among conductors. A distance that represents the equiv-
alent spacing between a conductor or a group of conductors
stranding or hollo\v-core construction as shown in Chap. 3, and the enclosing sheath can be expressed as a GMD. Also,
Fig. 11. Sometimes in calculations involving zero-se- the equivalent separation between cable conductors and
quence renctnnces, simplification may result if the three the sheath of a nearby cable, or the equivalent separation
conductors comprising a three-phase circuit are considered between two nearby sheaths, can be expressed as a GMD.
cu a group and converted to a single equivalent conductor. Because these and other versions2 of geometric mean dis-
This requires the use of a new GMR, denoted here as tance may be used successively in a single problem, care
68 Electrical Characteristics of Cables Chapter 4

must be taken to identify and distinguish among them dur- Because of the various possible combinations of con-
ing calculations. ductors and sheaths that can be taken in a three-conductor
Geometric Factor-The relation in space between the belted cable, several geometric factors are required for com-
cylinders formed by sheath internal surface and conductor plete definition. Two of these factors, the ones applicable
external surface in a single-conductor lead-sheathed cable to positive- and to zero-sequence electrical calculations, are
can be expressed as a “geometric factor.” This factor is shown in Fig. 9.
applicable to the calculation of such cable characteristics
as capacitance, charging current, dielectric loss, leakage 2. Positive- and Negative-Sequence Resistance
current, and heat transfer, because these characteristics Skin Efiect-It is well known that the resistance of a
depend on a field or flow pattern between conductor and conductor to alternating current is larger than its resistance
sheath. The mathematical expression for geometric factor to direct current. The direct-current resistance in cables
G in a single conductor cable is can be taken as the resistance of solid rod of the same
length and cross-section, but increased two percent to take
G=2.303 log,, $ (3) into account the effect of spiraling of the strands that com-
where : pose the conductor. When alternating current flows in the
conductor there is an unequal distribution of current, with
ri = inside radius of sheath. the outer filaments of the conductor carrying more current
CL= outside diameter of conductor. than the filaments closer to the center. This results in a
Geometric factors for single-conductor cables can be ‘read higher resistance to alternating current than to direct cur-
from Fig. 8. Geometric factors for three-phase shielded rent, and is commonly called skin effect. The ratio of the
cables having round conductors are identical, except for two resistances is known as the skin-effect ratio. In small
heat flow calculations, to those for single-conductor cables. conductors this ratio is entirely negligible, but for larger
The shielding layer establishes an equipotential surface conductors it becomes quite appreciable, and must be con-
surrounding each conductor just as a lead sheath does for sidered when figuring the 60-cycle resistances of large con-
single-conductor cables. The heat conductivity of the
three-mil shielding tape is not high enough to prevent a TABLE ~-DIMENSIONS AND 60-CYCLE SKIN-EFFECT RATIO OF
temperature differential from developing around the shield STRANDED COPPER CONDUCTORSAT 65’C.
circumference during operation: this poses a more complex -
problem than can be solved by the simple geometric factors 1nner Diameter of Annular
Conductor Round !stranded Conductor, inches
given here. Size -

(Circular
Concentric-Stranded
-
0.50
- I -
0.75

Mils) Diameter ( )uter ( )uter


Ratio I Iatio I Zatio
inches I Xam. I1iam.
-- .- -
211 600 0.528 1.00 ....
250 000 0.575 1.005
300 000 0.630 1.006
400 000 0.728 1.012 ,....
500 000 0.814 1.018 I0.97 1.01 .....
600 000 0.893 1.026 1.04 1.01
800 000 1.031 1.046 1.16 1.02 1.28 1.01
1000 000 1.152 1.068 1.25 1.03 1.39 1.02
1 500 000 1.412 1.145 1.52 1.09 1.63 1.06
2 000 000 1.631 1.239 1.72 1.17 1.80 1.12
2 500 000 1.825 1.336 1.91 1.24 2.00 1.20
3 000 000 1.998 1.439 2.08 1.36 2.15 1.29
- - -

ductors. Some skin-effect ratios are tabulated in Table 1


for stranded and representative hollow conductors.’
Proximity E#ect-The alternating magnetic flux in a
conductor caused by the current flowing in a neighboring
conductor gives rise to circulating currents, which cause an
apparent increase in the resistance of a conductor. This
RATIO t phenomenon is called proximity effect. The increase in
Fig. S-Geometric factor for single-conductor cables, or resistance is negligible except in very large conductors.
three-conductor shielded cables having round conductors. Proximity effect can, however, become important under
NOTE: This is approximately correct for shielded sector-conductor certain conditions of cable installation, When cables are
cables if curve is entered with the dimensions of a round-conductor laid parallel to metal beams, walls, etc., as is frequently the
cable having identical conductor area and insulation thickness. case in buildings or ships, proximity effect increases the
This geometric factor is not applicable for heat-flow calculations in apparent impedance of these cables appreciably. Booth,
shielded cables. See Sets. 5 and 6. Hutchings and Whitehead have made extensive tests on
chapter 4 Electrical Characteristics of Cables

I.2

I.4

I.6
c G, FOR THREE-CQNDUCTOR BELTED CABLES pT! L
1.8
.O

9 3.6
!i
w
m

t/T

D CABLE? (

0.0

0.6 I I I I I (1 11 ’
0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2x) 2.2 2.4

RATIO +

Fig. 9-Geometric factor for three-conductor belted cables having round or sector conductors.

‘OTE: For cables having sector conductors, enter the curve with the dimensions of a round-conductor cable having identical conductor
area and insulation thicknesses. Multiply the resultant geometric factor by the sector correction factor given above.
(G1 is calculated for three-phase operation; GO is calculated for single-phase operation, with three conductors paralleled and re-
turn in sheath. See Sets. 5 and 6.)
70 Electrid Characteristics of Cables Chapter 4

the impedance and current-carrying capacity of cables, as


they are affected by proximity to flat plates of conducting w
z 0.09 (ok-6 IN SPACING BETWEEN SHEATHS
and magnetic material. Figures 11 and 12, taken from this 2 (b)-3IN. SPACING BETWEEN SHEATHS
work, illustrate forcefully that prosimity effect can be 2 0.08
E - REACTANCE AT 50 CYCLES
significantly large. Although these tests were performed --- RESISTANCE AT 50 CYCLES
0 0.07
at 50 cycles it is believed that the results serve to indicate
effects that would be experienced at 60 cycles. The results
in an actual installationof cables close to metal surfaces are
inHuenced so greatly by the material involved, and by the

I I I I I III III

0.0 I

“‘0 I 2 3 4 5 6 7 B 9 IO
DISTANCE FROM STEEL PLATE - INCHES

Fig. Il.-Increase in cable resistance and reactance caused


by proximity to steel plate for single phase systems (cable
sheaths are insulated).

terials will contribute lowest losses. Some practical pas-


sibilities, drawn from experience in the design of switch-
gear, transformers, and generators, are listed here:
a. The magnetic plate can be shielded by an assembly of
laminated punchings, placed between the cables and
the plate, so that flux is diverted from the plate and
into the laminations. The laminations normally have
low eddy-current losses and they must be designed so
that flux density is not excessive.
b. The magnetic plate can be shielded with a sheet of
conducting material, such as copper or aluminum,
placed so that the magnetic field acts to build up

or ’ ’ ’
0 0.04 0.00 0.12 0.16 0.20

RATIO + (a)-61N. SPACING BETWEEN SHEATHS


(b)-3lN. SPACING BETWEEN SHEATHS
Fig. lo-Geometric factor for three-conductor shielded cables cc)- I IN. SPACING BETWEEN SHEATHS
having sector conductors, in terms of insulation thickness T
and mean periphery P. - REACTANCE AT 50 CYCLES
--- RESISTANCE AT 50 CYCLES

structural shape of the surface, that calculation and pre-


diction is difficult.
The additional losses caused by placing a metal plate or
other structural shape close to a cable circuit arise from
both hysteresis and eddy-current effects within the plate.
Hysteresis losses are large if the flux density within the plate
is high throughout a large proportion of the plate volume.
i\ material having high permeability and very high re- z 0.04
sistivity would promote hysteresis loss, because flux devel- (r
oped by cable currents could concentrate within the low- “0 DO3
reluctance plate, and because the action of eddy-currents l-
2 0.02
to counteract the incident flux would be comparatively
small in a high-resistance material. Eddy-current losses iii
” 0.01
depend on the magnetic field strength at the plate, and z
-
also upon the resistance of the paths available for flow “‘0 I 2 3 4 5 6 7 8 9 IO
within the plate. DISTANCE FROM STEEL PLATE- INCHES

Because the factors that affect hysteresis loss and those Fig. 12-Increase in cable resistance and reactance caused
that affect eddy-current loss are interdependent, it is seldom by proximity to steel plate for three-phase systems (cable
easy to theorize on which material or combination of ma- sheaths are insulated).
Chapter 4 Electrical Characteristics of Cables 71

counteracting circulating currents within the con- and


ducting sheet: these currents considerably reduce the 0.200
magnetic field strength at the plate. The conducting ohms per phase per mile, for lead sheath.
rs=(To+TJ(To-TJ
sheet must have sufficient cross-sectional area to ac- (6)
commodate the currents developed. in which
c, The magnetic material can be interleaved with con-
S = spacing between conductor centers in inches.
drlcting bars that are bonded at the ends so that cir-
T, = outer radius of lead sheath in inches.
culating currents develop to counteract the incident
Ti = inner radius of lead sheath in inches.
magnetic field as in (b).
(1, The magnetic plate can be replaced, either entirely or Thus the total resistance (r:,) to positive- or negativc-
partially, by a non-magnetic steel. Non-magnetic sequence current flow in single-conductor cables, including
steel has low permeability and high resistivity when the effect of sheath currents, is
compared with conventional steel plate: these char-
:icteristics do not act in all respects to reduce losses, ra = r,+ -ohms
xm2rs per phase per mile. (7)
t)rlt, the net effect is often a loss reduction. Xon-mag- XIII2+ rs2
netic: steel is of particular benefit when the structure where re is the alternating-current resistance of the con-
near the cable circuit partially or entirely surrounds ductor alone including skin effect at the operating frc-
intlividual phase conductors. quency. Eq. (7) applies rigorously only when the cables arc
‘l%(: effect of parallel metal on reactance is much larger in an equilateral triangular configuration. For other ar-
I.t1:ln on resistance as Figs. 11 and 12 indicate. These rangements the geometric mean distance among t,hree
fiKllrcs also show that the magnitude of the increase in im- conductors, GIMD~,, can be used instead of S with results
I1,~(l:mccis independent of conductor size. Actually, when sufficiently accurate for most practical purposes.
l:lrg:(:cables approach very close to steel, the resistance in- The sheath loss in a three-conductor cable is usuall>
,:r(xmrnt,s become higher and the reactance increments be- negligible except for very large cables and then it is im-
,Y),~c somewhat lower. The curves of Figs. 11 and 12 are portant only when making quite accurate calculations. In
t):ts(:(I on tests performed at approximately two-thirds of these largest cables the sheath losses are ahollt 3 to 5 per-
m:1simllm current density for each cable used. The incre- cent of the conductor loss, and are of relatively littlc
m(:n~sin resistance and reactance do not, however, change importance in most practical calculations. When desired
grwt,ly with current density; the variation is only about the sheath loss in three-conductor cables can be calculated
I pwcent per 100 amperes. In three-phase systems the from the equivalent resistance,
mitltllc cable of the three is influenced less than the outer
44160(&)”
ones by the presence of the parallel steel. This variation ?-= r (r +T.)Z X 1O-6 ohms per phase per mile. (8)
:tg:bin is less than variations in materials and has not been so I
:tcc:o~mtedfor in Figs. 11 and 12. These curves cover only a where
1’~ sprcific cases, and give merely an indication of the im- r, is sheath resistance from Eq. (6).
port,:mceand magnitude of proximity effect. More detailed r, and ri are sheath radii defined for Eq. (5).
information can be found in the reference listed.4 1
l’rosimity effect also has an important bearing on the &=-==(d+2T), and is the distance between
43 conductor center and sheath (9)
c:lll.ront-carrying capacity of cables when installed near
sl~(:l plates or structures. This subject is discussed in the center for three-conductor
Swl ion on current-carrying capacity. cables made up of round con-
Sheath Currents in Cables-Alternating current in ductors.
1IWwntluctors of single-conductor cables induces alternat- d = conductor diameter.
iw volt,nges in the sheaths. When the sheaths are contin- T = conductor insulation thickness.
110115 :tntl bonded together at their ends so that sheath cur- For sector-shaped conductors an approximate figure can
1’(‘11t s I~:LJ~ flow longitudinally, additional I*R losses develop be had by using Eq. (8), except that cl should he 82 to SG
ill 11~Sheath. The common way to represent these losses is percent of the diameter of a round conductor having the
l)Y incwasing the resistance of the conductor involved. For same cross-sectional area.
“ingl(!-contlrlctor cables operating in three-phase systems, Example I-Find the resistance at 60 cycles of a ‘750000
IhiS increment in resistance can be calculated by the fol- circular-mil, three-conductor belted cable having 156 mil
1°\\iw equation, the derivation of which is given in refer- conductor insulation and 133 mil lead sheath. The overall
vII(!(:s:I.:! diameter of the cable is 2.833 inches and the conductors are
GU2r8 sector shaped.
r=----ohms per phase per mile. (4)
x,? + T,2 From conductor tables (see Table 10) the diameter of an
lrwc .r,,, is the mutual reactance between conductors and equivalent round conductor is 0.998 inches. From Eq. (9),
slle:lth in ohms per phase per mile, and r, is the resistance 1
&=-&0.998(0.84)+2(0.156)]
of tlw sheath in ohms per phase per mile. These two quan-
tities can be determined from the following equations: = 0.664 inches.
Since the overall diameter is 2.833 inches,
G = 0.2i9-I & log,, s ohms per phase per mile. (5)
0 I rO= 1.417 inches
72 Electrical Characteristics of Cables Chapter 4

and here. The ratio of actual resistance as installed to the d-c


Ti = 1.284 inches. resistance of the conductor itself based on data obtained in
laboratory tests is shon-n in Fig. 13. The increased resist,-
From Eq. (C,),
0.200 ante is due to conductor skin effect, conductor proximity
effect. in the presence of steel pipe, and to I?R loss in the
“= (2.701)(0.133) pipe itself. In preparing Fig. 13, the pipe size assumed for
=0.557 ohms per phase per mile. each cable size was such that 60 percent of the internal pipe
Substituting in Eq. (8), cross-sectional area would have been unoccupied by cable
44160(0.664)ZX 10-6 material: choosing a nearest standard pipe size as a prac-
tical expedient does not affect the result appreciably. The
’ = 0.557C2.701)”
conductor configuration for these tests lens a triangular
=O.O04f9 oh& per phase per mile.
grouping, with the group lying at the bottom of the pipe.
From Table 6 it, is found that r,, the conductor resistance, If, instead, the conductors were to be laid in an approx-
including skin effect is 0.091 ohms per phase per mile. The imately flat cradled arrangement,, some change in resist-
total positive- and negative-sequence resistance is then, ance would be expected. Actual tests on the flat arrange-
r, = 0.091+ .005 = 0.096 ohms per phase per mile. ment produced variable results as conductor size was
Sheath currents obviously have little effect on the total changed, some tests giving higher losses and some lower
alternating-current resistance of this cable. than the triangular. If a maximum value is desired, an
Theoretically some allowance should be made for the estimated increase of 15 percent above the resistance for
losses that occur in the metallic tape on the individual con- triangular configuration can be used. Field tests have been
ductors of shielded cable, but actual measurements indicate made on low-voltage circuits by Brieger14, and these results
that for all practical purposes these losses are negligible are shown in Table 2.
with present designs and can be ignored in most cases. The
resistance to positive- and negative-sequence in shielded 3. Positive- and Negative-Sequence Reactances
cable can be calculated as though the shields were not Single-Conductor Cables-The reactance of single-
present. conductor lead-sheathed cables to positive- and negative-
Three Conductors in Steel Pipe-Typical values for sequence currents can be calculated from the following
positive- and negative-sequence resistance of large pipe- equation, which takes into account the effect of sheath
type cables have been established by test?, and an empir- currents.
ical calculating method has been proposed by Wiseman f GMDs, xx,3
that checks the tests quite closely. Because the calcula- x1=22=0.2794 - log,, ~-
GMRI,
60 xm2+ rs2
tions are complex, only an estimating curve is presented ohms per phase per mile. (10)
or
X1=x2=&+xd- xGZ ohms per phase per mile. (11)
m 9
The conductor component of reactance is
12
x,=0.2794 -f log,, -GMR1, (12)
60
where
GMR1,=geometric mean radius of one conductor.
The separation component of reactance is
f tog,, ~GMDzc
xd = 0.2794 6o (13)
12
where
GMD3, = geometric mean distance among
three conductors (see Eq. 1).
The component to be subtracted’ because of the effect of
sheath currents is composed of terms defined by Eqs.
(5) and (6).
Three-Conductor Cables-Because negligible sheath
a current effects are present in three-conductor non-shielded
0
cables, the reactance to positive- and negative-sequence
5
a currents can be calculated quite simply as:
s1=22=0.2794
GM&,
-f loglo GMR1,
60
CONDUCTOR SIZE, MCM ohms per phase per mile (14)
Fig. 13-Positive-sequence resistance of high-voltage cables or
in steel pipe (estimating curve). x1=x2 = z,+zd ohms per phase per mile (15)
Chapter 4 Electrical Characteristics of Cables 73

TABLE Z-IMPEDANCE OF THREE-PHASE120/208 VOLT CABLE CIRCUITSIN FIBRE AND IN IRON CONDIJITS.~
positive- andNegative-Sequence Impedance, Ohms per Phase per Mile at 60 Cycles.
Phase Conductor Duct Material Cable Sheath Resistance Reactance
Size Conductor Assembly
(4 inch) (Phase Conductors) (Ohms at 25°C.) (Ohms)
500 MCM Uncabledz Fibre Non-leaded 1 0.120 I 0.189
(I per phase) Lead 0.127 0.188
Iron Non-leaded 0.135 0.229
. Lead 0.156 0.236
Cabled’ Fibre _ Non-leaded 0.125 0.169
Iron _ Non-leaded 0.135 0.187
Cabled’ Fibre Non-leaded 0.136 0.144
Iron Non-leaded , 0.144 , 0.159
0000 AWG Uncabled& Fibre Non-leaded 0.135 0.101
12per phase) Iron Non-leaded 0.144 0.152
Lead 0.143 0.113
Cabled6 Fibre _ Non-leaded 0.137 0.079
Iron Non-leaded 0.137 0.085

Zero-SequenceImpedance, Ohms Per Phase Per Mile at 60 Cycles.


-
Cable Sheath
Phase Conductor Neutral Conductor Conductor Duct Material (Phase Resistance Reactance
Size Size Assembly (4 inch) Conductors) (Ohms at 25°C.) (Ohms)
__
500 MCM 0000 A WC Uncabledl Fibre Non-leaded 0.972 I 0.814
(I per phase) (1 conductor, bare) Lead 0.777 0.380
_- Iron _ Lead 0.729 0.349
500 MCM Uncabled* Iron Non-leaded 0.539 0.772
(1 conductor, bare) Cabled8 Fibre Non-leaded 0.539 0.566
-_ Iron Non-leaded 0.534 0.603
000 AWG Cabled’ - Fibre Non-leaded 0.471 0.211
(3 conductors, bare) Iron Non-leaded 0.433 I 0.264
--
0000 AWG 0000 AWG Uncabledj Fibre Non-leaded 1.015 0.793
(2 per phase) (I conductor, bare) Iron Non-leaded 0.707 0.676
Lead 0.693 I 0.328
0000 AWG Uncableds Fibre Non-leaded . 0.583 0.475
(2 conductors, bare) I Iron Non-leaded 0.629 0.538
.-
500 MC&l Cabled6 Iron Non-leaded 0.497 0.359
(1 conductor, bare) - I
’ .\Iatwial taken from “Impedance of Three-Phase Secondary Mains in Non-Metallic and Iron Conduits,” by L. Brieper. EEI Bulletin. Vol. 6. No. 2. pg. 61. Feb-
rllllry 1938.
’ Asvernbly of four conductors arranged rectangularly. in the sequence (clockwise) A-B-C-neutral. while being Pulled into the duct; conductors may assume a rsn-
“‘m1 c(Migumtion after entering the duct.
’ .inJenrbly aa in note 2. except that conductors are-cabled in position.
’ Assembly of three phase conductors arranged triangularly with three neutral conductors interposed in the spaces between phase conductors. All conductors are
Wi~llVl in position,
’ Assernhly of six phase conductors arranged hexagonally, in the sequence A-B-C-A-B-C. with either one or two neutral conductors inside the phase conductor group.
‘l“lia ilrmnwment is maintained only at the duct entrance: a random configuration may develop within the duct.
’ Assembly 8s in note 5. except that conductors are cabled in position.

\Vhere: For shielded three-conductor cables the reactance to


GMD3, = S = geometric mean distance among positive- and negative-sequence currents can be calculated
three conductors, and the remaining values are as as though the shields were not present, making it similar to
defined in Eqs. (12) and (13). belted three-conductor cable. This is true because the
effect on reactance of the circulating currents in the
l’or sector-shaped conductors no accurate data on change shielding tapes has been calculated by the method used for
iI1 reactance because of conductor shape is available, but determining sheath effect.s in single-conductor cables and
k. Simmons can be quoted as authority for the statement proves to be negligible.
that the reactance is from five to ten percent less than for Three Conductors in Steel Pipe-Conductor skin
round conductors of the same area and insulation thick- effectandproximityeffectsinfluence theapparent reactance
ness. of high-voltage cables in steel pipe. Because the detailed
74 Electrical Characteristics of Cables Chapter 4

calculation of these factors is complex, a curve is supplied of these inductive effects cannot always be identified in-
in Fig. ld that serves for estimating reactance within about dividually from the equations to be used for reactance cal-
five percent accuracy. The curve is drawn for triangular culations because the theory of earth return circuits3, and
conductor grouping, with the group lying at the bottom of the use of one GMR to represent a paralleled conductor
the pipe. If the grouping is instead a flat cradled arrange- group, present in combined form some of the fundamental
ment, with the conductors lying side by-side at the bottom effects contributing to total zero-sequence reactance. The
of the pipe, the curve results should be increased by 15 resistance and reactance effects are interrelated so closely
percent. A calculating method that accounts in detail for that they are best dealt with simultaneously.
Cable sheaths are frequently bonded and grounded at
several points, which allows much of the zero-sequence
return current to flow in the sheath. On the other hand,
when any of the various devices used to limit sheath current
are employed, much or all of the return current flows in the
earth. The method of bonding and grounding, therefore,
has an effect upon the zero-sequence impedance of cables.
An actual cable installation should approach one of these
three theoretical conditions:
1 Return current in sheath and ground in parallel.
2 All return current in sheath, none in ground.
3 All return current in ground, none in sheath.
Three-Conductor Cables-Actual and equivalent cir-
cuits for a single-circuit three-conductor cable having a
solidly bonded and grounded sheath are shown in Fig. 15
(a) and (c). The impedance of the group of three paralleled
conductors, considering the presence of the earth return
but ignoring for the moment the presence of the sheath, is
given in Eqs. (16) or (17) in terms of impedance to zero-
sequence currents.
z, =r,+r,+j0.8382
f D,
gj log,, GMR1,
ohms per phase per mile (16)
or
2, = T,+Te+j(za+z,- 22d)
ohms per phase per mile. (1’7)

TABLE 3-EQUIVALENT DEPTH OF EARTH RETURN (De), AND EARTH


IMPEDANCE (r, AND 2.), AT 60 CYCLES
CENTER TO CENTER SPACING BETWEEN CABLES, INCHES -
Equivalent Equivalent Equivalent
Fig. 14-Positive-sequence reactance of high-voltage cables Earth Depth of Earth Earth
in steel pipe (estimating curve). .,.

1--((
Resistivity Earth Return, D, Resistance Reactance
(meter-ohm: )- - re XC
the variable factors in this problem has been presented by inches feet ohmspermile dims per mile)
.-
Del Mar’. Table 2 contains information14 useful in esti-
1 3.36~10~ 280 0.286 2.05
mating the impedance of low-voltage (120/208 volt) cables 5 7.44x103 620 0.286 2.34
in iron conduit. 10 1.06~10’ 880 0.286 2.47
50 2.40~10~ 2 000 0.286 2.76
4. Zero-Sequence Resistance and Reactance 100 3.36~10’ 2 800 0.286 2.89
When zero-sequence current flows along the phase con- 500 7.44x10’ 6 200 0.286 3.18
ductors of a three-phase cable circuit, it must return in 1000 1.06~10~ 8 800 0.286 3.31
either the ground, or the sheaths, or in the parallel combi-
nation of both ground and sheaths.2 As zero-sequence cur-
rent flows through each conductor it encounters the a-c
5 000
.lO 000
-
2.40~10~
3.36~10~
20 000
28 000
0.286
0.286 3- 3.60
3.73

resistance of that conductor, and as it returns in the ground where :


or sheaths it encounters the resistance of those paths. The r,=a-c resistance of one conductor, ohms per
zero-sequence current flowing in any one phase encounters mile.
also the reactance arising from conductor self-inductance, r,=a-c resistance of earth return (See Table 3),
from mutual inductance to the other t&o phase conductors, ohms per mile. 3
from mutual inductance to the ground and sheath return D,= distance to equivalent earth return path, h
paths, and from self-inductance of the return paths. Each (See Table 3), inches. I
chapter 4 Electrical Characteristics of Cables 75

GMR,,=geometric mean radius of the conducting


path made up of the three actual conductors
taken as a group, inches.
= +(GMR,,)(S)? for round conductors. (18
GMR1,= geometric mean radius of an individual
conductor, inches.
(I,+,+Ibo+I,,) + (I,+Ig )=o x,=reactance of an individual phase conductor
at twelve inch spacing, ohms per mile.
7//,////t77t/,/,//////////N/////m//////h/~~ x,= reactance of earth return.
EARTH
----a D,
ACTUAL CIRCUIT
=0.8382 $ log,, 12 ohms per mile. (Refer to
(ONETHREE-CONDUCTOR CABLE)
(0)
Table 3). (19)

, ohms per mile.


GMDI, = geometric mean distance among conductor
centers, inches.
=S= (df2T) for round conductors in three
conductor cables.
The impedance of the sheath, considering the presence of
the earth return path but ignoring for the moment the
(IO +h+,+Ico)+(31,+Ig)=0
0 presence of the conductor group, is given in terms of im-
I I h,,
////// I
//T//////f/
pedance to zero-sequence currents:
-. EARTH 211,
2. =3r,+r,+j0.8382 $ log,, - ohms per
rofri
ACTUAL CIRCUIT
(THREE SINGLE-CONDUCTOR CABLES) phase per mile. (20)
(b) or
z.=3r,+r,+j(3x.+xe) ohms per phase per
mile. (21)
- IO
where :
/
(REPRESENTS THREE CONDUCTORS) zm I r.=sheath resistance, ohms per mile.
I
0.200
J
--- : = (To+ri) (T, - ri) for lead sheaths.
Ti = inside radius of sheath, inches.
r, = outside radius of sheath, inches.
n/,/,//m+ ,,,,//,,/ LTV77
,,,,,,,,,,,,,,, Am7mm/ x. = reactance of sheath, ohms per mile.
-k3 EARTH
=0.2794 & log,, s ohms per mile. (22)
0 I
EQUIVALENT CIRCUIT The mutual impedance between conductors and sheath,
(IMPEDANCES EXPRESSED IN ZERO SEQUENCE TERMS) considering the presence of the earth return path which is
(Cl
common to both sheath and conductors, in zero-sequence
terms is
20.
.~=r,+jO.8382 & log,, -
rofri

ohms per phase per mile. (23)


or
z,=r,+j(3xs+x,) ohms per phase per mile. (24)
The equivalent circuit in Fig. 15(d) is a conversion from
the one just above it, and combines the mutual impedance
into a common series element. From this circuit, when
-1 EARTH both ground and sheath return paths exist, total zero-
go
sequence impedance is:
MODIFIED EOUIVALENT CIRCUIT
(IMPEDANCES EXPRESSED IN ZERO-SEOUENCE TERMS)
(4
Fk. 15-,4,-tual and equivalent zero-sequence circuits for =zO-, ohms per phase per mile.
three-conductor and single-conductor lead-sheathed cables. (25)
76 Elect&d Characteristics of Cables Chapter 4

If current returns in the sheath only, with none in the The mutual component of impedance is:
ground : z, = 0.286+j3.87
&I= (2, - 4 + (2, - .Gn> If all current returned the sheath, and none in the
=.zc+z,--22, (26) ground,
f ro+ri z0=1.27+j4.18+3.68+j3.87-0.57-j7.74
==r,+3r,+jO.8382 G log102(GR/IR3cj ohms per = 4.38+j0.31=4.39 ohms per mile.
phase per mile. (27) If return current may divide between the ground and
= r,+ 3r,+j(z:, - 2~ - 32,) ohms per phase per sheath paths,
mile. (0.286+j3.87)2
(28) zo= 1.27+j4.18- 3.68+j3,87
If current returns in ground only with none in the sheath, = 1.27fj4.18+1.623-12.31
as would be the case with non-sheathed cables or with = 2.89fj1.87 = 3.44 ohms per mile.
insulating sleeves at closely spaced intervals, the zero-
sequence impedance becomes: The positive-sequence impedance of this cable is:
zo= (z,--z,)+z, ZI = 0.987 + jO.203 ohms per mile.
=zc ohms per phase per mile. (29) Therefore the ratio of zero- to positive-sequence resistance
The zero-sequence impedance of shielded cables can be is 2.9, and the ratio of zero- to positive-sequence reactance
calculated as though the shielding tapes were not present is 9.2.
because the impedance is affected only slightly by cir- Zero-sequence impedance is often calculated for all
culating currents in the shields. return current in the sheath and none in the ground, be-
The equivalent geometric mean radius (GMR,,) for cause the magnitude of the answer is usually close to that
three-conductor cables having sector conductors is difficult calculated considering a paralleled return. The actual
to calculate accurately. The method used to calculate nature of a ground-return circuit is usually indefinite, since
values of GMRS, for the tables of characteristics is of it may be mixed up with water pipes and other conducting
practical accuracy, hut is not considered to be appropriate materials, and also because low-resistance connections
for explanation here. As an alternate basis for estimations, between sheath and earth are sometimes difficult to
it appears that the GMR,, for three sector-conductors is establish.
roughly 90 percent of the GMRsc for three round conduc- Single-Conductor Cables-Fig. 15 also shows the
tors having the same copper area and the same insulation actual and equivalent circuits for three single-conductor
thickness. cables in a perfectly transposed three-phase circuit, where
Example 2-Find the zero-sequence impedance of a the sheaths are solidly bonded and grounded. The im-
three-conductor belted cable, No. 2 A.W.G. conductor (7 pedance expressions applying to single-conductor cables
strands) with conductor diameter of 0.292 inches. Con- differ in some respects from those for three-phase cables:
ductor insulation thickness is 156 mils, belt insulation is
78 mils, lead sheath thickness is 109 mils, and overall f
z,=r,+~,+j0.8382 (;olog ~ D,
10 GMRsoohms
--
cable diameter is 1.732 inches. Assume D, = 2800 feet and per phase per mile. (30)
resistance of one conductor=0.987 ohms per mile at 60
cycles. Distance between conductor centers is: or
zc=rc+~,+j(xa+x,-2xd) ohms
S=O.292+2XO.156=0.604 inches. per phase per mile. (31)
GMR of one conductor is (see Chap. 3, Fig. 11): where :
GMRI,=0.726X0.146=0.106 inches. rc= a.c. resistance of one conductor, ohms per
GMR of three conductors is: mile.
GMR3,= ~(0.106)(0.604)*=0.338 inches. r, = a.c. resistance of earth (see Table 3)) ohms
per mile.
The conductor component of impedance is D, = distance to equivalent earth return path (see
(r,=O.987, r,=O.286): Table 3), inches.
2800X 12 GMR3,= geometric mean radius of the conducting
z, = 0.987+0.286+jO.8382 log,, o 338
oath made up of the three actual conduc-
= 1.27+j4.18=4.37 ohms per mile. tars taken as-a group, inches.
This would represent total zero-sequence circuit impedance = IY(GMR~(GMDJ”
if all current returned in the ground, and none in the x, = reactance of an individual phase conductor
sheath. at twelve-inch spacing, ohms per mile.
For the sheath component of impedance: x.,= reactance of earth return.
0.200 D, ohms per mile.
___ = 1.13 ohms per mile =0.8382 & log,,
‘“=(1.)(0.109) ii
2X2800X12 (See Table 3.)
2.=3X 1.13+0.286+j0.8382 log,0
1.623 f log,,
xd= 0.2794co ohms per mile.
=3.68+j3.87 ohms per mile
Chapter 4 Electrical Characteristics of Cables 77

CMD3, = geometric mean distance among conductor in Table 2. Some special tests of the zero-sequence im-
centers, inches. pedance of high-voltage pipe-type cable have been mndc
= US;,,, . Asho
’ s,, . but the results are not yet of a sufficiently ivide scope to
f De be generally usable.
zs= r,+r,+j0.8382 ro log,, ___
1 GMRX, Ohms
5. Shunt Capacitive Reactance
per phase per mile (32)
Shunt capacitive reactances of several types of cables
~~=r~+r~,+j(~~+~,-222d) ohms per phase are given in the Tables of Electrical Characteristics,
per mile (33) directly in ohms per mile. In addition, shunt capacitance
where : and charging current can’be derived from the curves of
GMRss = geometric mean radius of the conducting geometric factors shown in Figs. 8 and 9, for any cable
path made up of the three sheaths in parallel whose dimensions are known. The geometric factors given
in these curves are identified by symmetrical-component
terminology.
=;;!(F)(GMD,.;>:.
The positive-, negative-, and zero-sequence shunt capxc-
rs = resistance of one sheath, ohms per mile itances for single-conductor metallic-sheathed cables are
0.200 all equal, and can be derived from the curves of Fig. 8.
= (To+ ri) (T, _ ri) for k%d sheaths. Three-conductor shielded cables having round conductors
are similar to single-conductor cable in that each phase
ri=inside radius of sheath, inches. conductor is surrounded by a grounded metallic covering;
r, = outside radius of sheath, inches. therefore the positive-, negative-, and zero-sequence values
x9= reactance of one sheath, ohms per mile are equal and are dependent upon the geometric factor
24 relating a conductor to its own shielding layer. The
=0.2794 (% log,, ~
ro+ri’ geometric factor for three-conductor shielded cables having
sector-shaped conductors is approximately equal to the
& =r,+j0.8382 i. log,, CAI; _ ohms geometric factor, G, applying to round conductors. HOK-
3c 3s
per phase per mile. ever, if the sector shape of a shielded cable is known, then
(34) the curve in Fig. 10, based on insulation thickness and
or
mean periphery of insulation, is recommended as giving
z~=r,i-j(~,+~,--2~) ohms per phase per
mile. more accurate values of geometric factor.
(35) For single-conductor and three-conductor shielded ca-
where :
bles (see Fig. 8),
GMD3c--3s= geometric mean of all separations between
sheabhs and conductors. microfarads per phase per
= (GMD#. mile. I 38)

From the equivalent circuit of Fig. 1.5, total zero- ~l~=~2’=~oo’=- 1.79G megohms per phase per mile. (39)
wqucnce impedance when both ground and sheath paths f.k
csist is: 0 323f.k.k~
2 II,= Iz*= I,,,= . IoOOG- amperes per phase per
z0= zc- 5 ohms per phase per mile. (25)
ZS mile. (40)
If current returns in t,he sheath only, with none in the
Three-conductor belted cables having no conductor
ground:
shielding have zero-sequence values which differ from the
.?I= 2, + 2, - 22,” ohms per phase per mile cw positive- and negative-sequence; the appropriate geo-
G&IRS, metric factors are given in Fig. 9;
=r,+r,+O.8382 log10Gi\/IR3, o~;;;;phast?
(36) microfarads per phase per mile. (41)
=r,+r,+j(x,-xZ,) ohms per phase per mile. (37)
If current returns in the ground only:
c =O.O892k
0 ___r microfarads per phase per mile. (42)
-TO
zo= (Z,-&JfZ,
=z, ohms per phase per mile. (2% 0.59761
g,-f=zq'=- megohms per phase per mile. (43)
Cables in Steel Pipes or Conduits--When cables are f-k ’
installed in iron conduits or steel pipes, the zero-sequence 1.79Go
megohms per phase per mile. (44)
resistance and reactance are affected by the magnetic "O'= f.k
material because it closely surrounds the phase conductors ~ =I =0.97f-k-kv
and forms a likely return path for zero-sequence current. 1’ 2’ amperes per phase per mile. (4.5)
so method of calculating this zero-sequence impedance is 1OOOGl
available, but some rather complete results are available Io,=0.323j-k-kv
amperes per phase per mile. (46)
from field tests on installed low-voltage cables, as shown lOOOG,,
78 Electrical Characteristics of Cables Chapter 4

When three-conductor belted cables have sector-shaped TABLE S-MAXIMUM POWER FACTORS* OF CABLE INSULATION
ronductors, the geomebric factor must be corrected from
t,he value \vhich applies to round conductors. This cor- Tcmperaturc Oil- Gas-
of Cable Solid Filled Fillccl
rection factor is plotted in Fig. 9, ancl its use is explained Paper
(Deg. C.) (low-prcssurr~ (lo\\--prcssurc~
below the curve.
In the foregoing equations, 25 to 60 0.009 0.0060 0.009
Cl, C?, rind C0 are positive-, negative-, and zero- i0 0.015 0.0075 0.013
sequence capacitances. 80 0.021 0.0090 0.018
Q’ and ~0’ are positive-, negative-, and zero- 85 0.025 0.0097 0.022
Xl',
90 0.030 0.010~5 0.027
sequence capacitive renctances.
II,, I?, and IO, are positive-, negative-, and zero- *The power factor of new cable is usually below tbevc values by a wide ~nnrgin.l~
seqlience charging currents.
ku = line-to-line system voltage, kilovolts.
X;=dielectric constant, according to the values in II. TABLES OF ELECTRICAL
Table 4. CHARACTERISTICS
It, is important to note that in converting shunt capaci- The 60-cycle electrical characteristics of the most usual
tive reactance from an ‘Lohms per phase per mile” basis sizes and voltage classes of paper insulated cable are con-
to a total “ohms per phase” basis, it is necessary to divide tained in Tables 6 through 11. In each case the positive-,
by the circuit length: negative-, and zero-sequence resistances and reactances
Xc’ are tabulated, or else constants are given from which these
x’,r = ohms per phase. (47)
I, length in miles’ quantities can be calculated. Also, included in these
tables are other characteristics useful in cable work, such
6. Insulation Resistance. as typical weights per 1000 feet, sheath thicknesses and
The calculation of cable insulation resistance is difficult resistances, conductor diameters and GMR’s, and the type
because the properties of the insulation are generally of conductors normally used in any particular cable.
predictable only within a wide range. The equations pre- In each of these tables the electrical characteristics have
sented below are therefore quite dependent upon an been calculated by the equations and curves presented in
accurate knowledge of insulation power factor. the foregoing pages. Where sector-shaped conductors are
For single-conductor and three-conductor shielded used, some approximations are necessary as pointed out
cables, previously. In Table 6 the positive- and negative-sequence
1.79G reactance for sectored cables has arbitrarily been taken
T1’= Tt’ = T”’= . lo6 ohms per phase
f.k~COS 4 7.5 percent less than that of an equivalent round-conductor
per mile. (4%
cable, in accordance with Dr. Simmons’ recommendations.
The equivalent GMR of three conductors in sectored
For three-conductor belted cables, cables is necessarily an approximation because the GSIR of
1‘f= T,>'
= 0.597Gl one sector cannot be determined accurately. This condi-
. lo6 ohms per phase per mile.
f~lc~COS4 tion arises since the shape of sectors varies and a rigorous
(49) calculation is not justified. The variation in sector shapes
I .79Go probably is greater than any error present in the approsi-
r”‘=-j.k.cos 4 . lo6 ohms per phase per mile. (50)
mation given in the tables. The reactances calculated
In these equations, from these approximate GMR’s are sufficiently accurate
for all practical calculations.
rl#, 7-f, and rot are positive-, negative-, and zero-
Table 7 for shielded cables is similar in form to Table 6
sequence shunt resistances.
and where sectored cables are listed the same approxima-
1~= dielectric constant (see Table 4).
tions in GMR and reactance apply. Table 8 for three-
cos +=power factor of insulation, in per unit.
conductor oil-filled cables is similar to both Tables 6 and
In Table 5 are listed maximum values of insulation 7 and the same considerations apply.
power factor, taken from specifications of the Association In these tables for three-conductor cables, the zero-
of Edison Illuminating Companies15. These standard sequence characteristics are calculated for the case of all
values will very probably be several times larger than return current in the sheath and none in the ground. As
actual measured power factors on new cables. pointed out in the discussion of zero-sequence impedance,
this is usually sufficiently accurate because of the indefinite
TABLE ~-DIELECTRIC CONSTANTS OF CABLE INSULATION nature of the ground return circuit. Where ground must
be considered or where there are paralleled three-phase
Insulation Range of k Typical k circuits, the impedance must be calculated as illustrated
Solid Paper 3.0-4.0 3.7
in the examples given.
Oil-Filled 3.0-4.0 3.5
From the quantities given in these tables of three-con-
Gas-Filled 3.0-4.0 3.7 ductor cables, the overall diameter of any particular cable
Varnished Cambric 4.0-6.0 5.0 can be calculated.
Rubber 4.0-9.0 6.0 o=2.155(d+27’)+2(t+L) (51)
Chapter 4 Electrical Characteristics of Cables 79

TABLE 6-60-CYCLE CHARACTERISTICS OF THREE-CONDUCTOR BELTED PAPER-INSULATED CABLES


Grounded Neutral Service
-
POSITIVE
NEGATIVE-
SEQ.
&
ZER PE

-
I SHI<;\TH

6 1 io0 0.184 2.50 0.067 0.185 6300 0.184 10.66 11 fflO 8.i 2 Ii’,

i
1910
2390
0.232
0.292
1.58
0.987
0.084
0.106
0.175 5400
4700
0.218
0.262
8.39
6.99
Elm
3.27i
10 200
9 on0
!10
!)O
.> .‘i
5. ii)
1 2 820 0.332 0.786 0.126 L? E 4300 0.295 6.07 D.256 8 -100 95 1.7li
0 3 210 0.373 0.622 0.142 0.152 4000 5.54 3.246 7 !I00 9.i 1. Ii4
3 160 0.323 0.495 0.151 0.138 2800 g::g 5.D6 5400 9.3 1.8’
Oil: 3 650 0.364 0.392 0.171 0.134 2300 0.520 5.46 ::;:: 4 500 !I 3 1 Ii!)
0000 4x90 0.417 0.310 0.191 0.131 2000 0 3.55 4.72 3.237 4 000 100 1.47
2cjO000 4900 0.456 0.263 0.210 0.129 1800 0.387 4.46 3.224 3 Ron 100 1.40
300000 5660 0.497 0.220 0.230 0.128 1700 0.415 3.97 0.221 ;;; 1 .L’;1
350 000 6310 0.190 0.249 1500 0.436 3.73 3.216 %i:: 1.1s
400000 7080 ;:;;t . 0.166 0.265 Z: :;i 1500 0.467 3.41 3.214 2900 11; 1.08
500000 8310 0.642 0.134 0.297 0.123 1300 0.517 3.11 2600 110 0 !XlR
6OnOOO 9 800 0.700 0.113 0.327 0.122 1200 n.567 2.74 ;::i': 11.X 0.877
750000 11800 0.780 0.091 0.366 0.121 1100 0.623 2.40 3.194 zI :g 120 0.X1
70 1 680 0.184 2.50 0.067 0.192 6700 0 192 3.322 12 500 !I0
in
70
ii
40
22 2030
2600
0.232
0.292
1.58
0.987
0.084
0.106
0.181
0.171
5800
5100
0.227
0.271
9.67
8.06
6.39
3.298 11 200
9 800
!JO
0.2
2. R!)
2. lli
l.SO
70 40 1 2930 0.332 0.786 0.126 0.161 4700 0.304 5.83 ;: ;;; 9 200 9.3 1.1s
3440 0.373 0.622 0.142 0.156 4400 5.06 D.256 8600 100 1.48
;II :i 0:; 3 300 0.323 0.495 0.151 0.142 3500 X:% 5.69 0.259 6700 ‘J.3 1 7:s
70 40 000 3 890 0.364 0.392 0.171 0.138 2700 5.28 D.246 5 100 9.5 1 63
70 40 0000 4530 0.417 0.310 0.191 0.135 2400 ::;P; 4.57 D.237 4 cl00 100 1.41'
70 40 2.50 000 5 160 0.455 0.263 0.210 0.132 2100 0.3;6 4.07 0.231 4200 ;g 1.27
7n 40 3ooono 5 810 0.497 0.220 0.230 0.130 1900 0.424 3.82 1. ?I)
70 40 350000 6470 0.539 0.190 0.249 0.129 1800 0.455 3.61 EIi :' 7"! 1Ok 1.14
70 40 400000 7240 0.572 0.166 0.265 0.128 1700 0.478 3.32 0.218 3400 110 1.0;
70 40 500000 8660 0.642 0.134 0.297 0.126 1500 0.527 2.89 0.214 :;; O.!llX
7.i 40 600000 9 910 0.700 0.113 0.327 0.125 1400 0.577 2.68 0.210 ",%i 0 8.5.5
75 40 750000 11920 0.780 0.091 0.366 0.123 1300 0.633 2.37 0.204 2 500 120 0 7.58
-- .-
105 35 6 2 150 0.184 2.50 0.067 0.215 8500 0.218 8.14 0.342 1.5000 9.3 1.68
100 55 2470 0.232 1.58 0.084 0.199 7600 0.250 6.86 13 600 9.5 1.76
9,s 50 l 2900 0.292 0.987 0.106 0.184 6100 0.291 5.88 iE:o' 11300 95 1.63
90 45 1 3280 0.332 0.786 0.126 0.171 5400 0.321 5.23 0.270 10200 100 1.48
90 0 3660 0.373 0.622 0.142 0.165 5000 4.79 9 600 100 1.39
85 2; 3480 0.323 0.151 0.148 3600 ET2 5.42 EZ !I.5 1.64
85 'r 0:: 4080 0.364 Xi 0.171 0.143 3200 0.343 4.74 0.254 ii % 100 1 .43
85 g 0000 4 720 0.417 0.310 0.191 0.141 2800 0.380 4.33 0.245 8300 100 1.34
85 45 250000 5370 0.263 0.210 0.138 2600 0.410 3.89 7 800 103 1.21
45 300000 6050 E; 0.220 0.230 0.135 2400 3.67 i%: 7400 105 1.13
2 45 350 000 6830 0.539 0.190 0.249 0.133 2200 E% 3.31 0.225 7000 110 1.04
83 45 400000 7480 0.572 0.166 0.265 0.131 2000 0.493 3.17 0.221 6700 110 1.00
85 45 5ooono 8 890 0.642 0.134 0.297 0.129 1800 0.542 2.79 0.216 6200 115 0.885
8.5 45 6Onooo 10 300 0.700 0.113 0.327 0.128 1600 2.51 0.210 5800 120 O.i98
85 4.5 75nooo 12 340 0.780 0.091 0.366 0.125 1500 ",:E:: 2.21 0.206 5400 123 0.707
7
130 63 2450 0.184 2.50 0.067 0.230 9600 0.236 7.57 0.353 16300 95 1.69
12.5 65 2 2900 0.232 1.58 0.084 0.212 8300 0.269 6.08 0.329 14 500 100 1. >I)
115 60 2 3 280 0.292 0.987 0.106 0.193 6800 5.25 0 302 12 500 100 1.42
110 55 1 3 560 0.332 0.786 0.126 0.179 6100 F%;: 4.90 0.280 11400 100 1.37
110 5.s 0 4090 0.373 0.622 0.142 5700 4.31 10 700 105 1.23
105 55 3870 0.323 0.495 0.151 :: :i‘i 4300 k% 4.79 8%: 100 1.43
10.5 55 0::: 4390 0.364 0.392 0.171 0.151 3800 4.41 0.263 ; % 100 1.34
105 53 0000 5 150 0.417 0.310 0.191 0.147 3500 Et: 3.88 0.254 6600 105 1.19
105 55 250000 5830 0.455 0.263 0.210 0.144 3200 0.428 0.246 6200 110 1.08
105 5.5 300000 6500 0.497 0.220 0.230 0.141 2900 E 5 600 110 1.03
105 5i 350000 7160 0 539 0.190 0.249 0.139 2700 Xii EE 5 200 110 0.978
105 5.j 400000 7980 0.572 0.166 0.265 0.137 2500 0.513 ~~~~ 0.230 4900 115 0.899
105 55 500000 9430 0.642 0.297 0.135 2200 0.563 2.53 0.224 4300 120 0.800
10.5 55
I-
600000 10 680 0.700 :: Et! 0.327 0.132 2000 0.606 2.39 0.218 3 900 120 0.758
105 55 750000 12 740 0.780 0.091 0.366 0.129 1800 0.663 2.11 0.211 3 500 125 0.673
170 85 2 4350 0 292 0.987 0.106 0.217 8600 4.20 0.323 15 000 110 1.07
165 80 1 4640 0.332 0.786 0.126 0.202 78M) EE 3.88 0.305 13 800 110 1.03
160 75 4990 0.373 0.622 0.142 0.193 7100 0.409 3.62 12 800 110 1.00
155 75 0: 5600 0.419 0.495 0.159 0.185 6500 0.439 Ei 12 000 115 0.918
1R.j 75 000 6230 0.470 0.392 0.178 0.180 6000 0.476 ;:"9; 11300 115 0.867
155 75 0000 7 180 0.528 0.310 0.200 0.174 5600 0.520 2.64 Zi 10 600 120 0.778
l5.j 250000 7840 0.575 0.263 0.218 5300 2.50 0.256 10 200 120 0.744
155 :i: 300000 7480 0.497 0.220 0.230 :: E 5400 EZ:: 2.79 0.254 7 900 0. 833
155 350000 8340 0.539 0.190 0.249 0.152 5100 0.536 2.54 0.250 7200 2; 0.784
1.55 :i 400000 9030 0.572 0.166 0.265 0.149 4900 0.561 2.44 0.245 G 900 120 0.758
15.S 75 fjooooo 10 550 0.642 0.297 4600 0.611 0.239 6 200 125 0.680
1% 75 600000 12 030 0.700 :: :i 8: ::2” 4300 0.656 t:;t 0.231 5700 130 0.620
165 7.i 750000 14 190 0.780 0.091 EE 0 139 4000 0.712 1.77 0.226 5 100 135 0 538
- -
‘A-c resistance based upon 100% conductivity at 65% including 2% allowance for stranding.
‘CMR of sector-shaped conductors is an approximate figure close enough for most practical applications.
‘For dielectric constant=3.7.
'Baaed upon all return current in the sheath; none in ground.
‘See Fig. 7.
‘The following symbols are used to designate the cable types; SR-Stranded Round; CS-Compact S&Or.
80 Electrical Characteristics of Cables Chapter 4

TABLE 7-60-CYCLE CHARACTERISTICS OF THREE-CONDUCTOR SHIELDED PAPER-INSULATED CABLES


Grounded Seutral Service

POSITIVE &
NEGATIVE ZERO-SEQUEXCE
SEQUENCE

2o.i 3 860 0.232 1.58 0.248 8200 0.328 5.15 0.325


1!11) 4 260 0.292 0.987 0.226 6700 0.365 4.44 0.298 i%:
183 4 740 0.332 0.786 0.210 6000 0.308 3.91 0.285 6000

180 5 090 0.373 0.141 0.201 5400 0.425 3.65 0.275 5400 110 1.01
17.; 4 790 0.323 0.151 0.178 5200 0.397 3.05 0.268 5200 105 1.15
17.5 5 510 0.364 O.lil 0.170 4800 0.432 3.48 0.256 4800 110 1.03
173 G 180 0.417 0.191 0.166 4400 0.468 3.24 0.249 4400 110 0.975

Ii.5 F 910 0.455 0.263 0.210 0.158 4100 0.408 2.95 0.243 4100 115 0.897
17.5 7610 0.407 0.230 0.156 3800 0.530 2.80 0.237 3800 115
173 8 480 0.530 Ei 0.249 0.153 0.561 2.53 0.233 3600 120 Ei
17; 9 170 0.572 0.166 0.265 0.151 Ei 0.585 2.45 0.228 3400 120 0.761

17.5 10 710 0.642 0.134 0.207 3100 0.636 2.19 0.222 3100 0.684
175 12 230 0.700 0.113 0.327 z:E 2900 0 681 1.98 0.215 2900 :3: 0.623
175 14 380 0.780 0.091 0.366 0.139 2600 0.737 1.78 0.211 2600 135 0.562

5 590 0.?92 0.087 0.106 0.250 8300 0.418 3.60 0.317 8300 115
i”;J 5 860 0.332 0.786 0.126 0.232 7500 0.450 3.26 0.298 7500 115

250 6 440 0.373 0.622 6800 0.477 2.99 0.290 6800 120 0.788
240 6060 0.323 0.495 Z:2: X:%t 6600 0.446 3.16 0.285 6600 :;; 0.890
240 6 620 0.364 0.302 0.171 0.188 6000 0.480 2.95 0.285 6000 0.851
240 7 480 0.410 0.310 0.191 0.181 5600 0.515 2.64 0.268 5600 120 0.775

8 070 0.447 0.263 0.210 0.177 5200 0.545 2.50 0.261 5200 120 0.747
8 990 0.490 0.220 0.230 0.171 4000 2.29 0.252 4900 125 0.600
9 720 0.532 0.190 0.249 0.167 4600 ET: 2.10 0.249 4600 125 0.665
10 G50 0.566 0.166 0.265 0.165 4400 0.633 2.03 0.246 4400 130 0.620

240 500 000 12 280 0.635 0.297 0.159 1.82 0.237 3900 13.5 0.562
240 600 000 13 610 0.600 0.327 0.154 1.73 3700 135 0.540
750 000 15 830 0.767 0.366 0.151 1.56 ;:;;g 3400 140 0.488
240

353 8 ,520 0.288 0.622 0.141 0.239 9900 0.523 2.40 0.330 9900 130 0.594
345 08 9 180 0.323 0.159 0.226 9100 0.548 2.17 0.322 9100 135 0.559
345 9 900 0.364 K% 0.178 0.217 8500 0.585 2.01 0.312 8500 135 0.538
345 OEEI 9 830 0.410 0.310 0.191 0.204 7200 0.594 2.00 0.290 7200 135 0.563

345 250 000 10 470 0.263 0.210 0.197 6800 0.628 1.90 0.280 6800 135 0.545
345 300 000 11290 ES 0.220 0.230 0.191 6400 0.663 1.80 0.273 6400 135 0.527
345 350 000 12 280 0.532 0.190 0.249 0.187 6000 0.693 1.66 6000 140 0.491
345 400 000 13 030 0.566 0.166 0.265 0.183 5700 0.721 1.61 E!i 5700 140 0.480

345 500 000 14 760 0.134 0.297 0.177 5200 0.773 1.46 0.257 5200 145 0.441
34.5 600 000 16 420 0.113 0.327 0.171 4900 0.819 1.35 0.248 49M) 150 0.412
345 750 000 18 860 0.091 0.366 0.165 4500 0.879 1.22 0.243 4500 155 0.377

‘A-c resistance based on 100% conductivity at 65°C. including 2Yo allowance for stranding.
ZGMR of sector-shaped conductors is an approximate figure close enough for most practical applications.
XFor dielectric constant=3.7.
‘Based on all return current in the sheath; none in ground. ..
%ee Fig. 7.
EThe following symbols are used to designate conductor types: SR--Stranded Round; CS-Compact Sector.

in which, according to Fig. 6, those given for the calculation of sequence impedances in
D = outside diameter in inches. the sections under Electrical Characteristics. Since
d = diameter of individual conductor in inches. 12
T = conductor insulation thickness in inches. x,=0.2794 -f log,, -
60 GM&c
t = belt insulation thickness in inches (when present). ohms per phase per mile
L = lead sheath thickness in inches. (12)
f 24
This equation refers to cables with round conductors. For x,=0.2794 -log,, -
sectored cables there is no exact rule, but a close approxi- 60 ro+Ti

mation can be obtained by using an equivalent cable with ohms per phase per mile (22)
round conductors and calculating the diameter D by Eq.
(1 l), and then subtracting 0.3 to 0.4 times the round con- zd=O.2794 k log,, $ ohms per phase per mile (13)
ductor diameter d, depending upon the shape of the sector.
A set of calculated constants is given in Table 10 for and r, and r, are conductor and sheath resistances respec-
single-conductor cables, from which the positive-, negative- tively, the derivation of the equations given with Table 10
and zero-sequence characteristics can be quickly deter- becomes evident. Table 12 gives the one other quantity,
mined by using the equations given at the foot of the %d, necessary for the use of Table 10. These reactance
tabulation. These equations are derived directly from spacing factors are tabulated for equivalent cable spacings
chapter 4 Electrical Characteristics of Cables 81

TABLE 8-60-CYCLE; CHARACTERISTICSOF THREE-CONDUCTOR OIL-FILLED PAPER-INSULATED CABLES


Grounded Neutral Service
-
POSITIVE &
‘SHEATH
lEGATIVE SEC,

5 590 0 323 0.495 0.151 0.185 GO30 0.406 3.56 0 265 6030 11.5 1.02
0:: 6 150 0.364 0.392 0.171 0.178 5480 0.439 3.30 0.2.56 5480 11.5 0. !I70
0000 6 860 0.417 0.310 0.191 0.172 4840 0.478 3.OG 0.243 4840 113 0.018
250 000 7 680 0.455 0.263 0.210 0.168 4570 0.508 2.72 0.238 4570 125 0.820
300 000 9 090 0.497 0.220 0.230 0.164 4200 0.539 2 58 0.232 4200 12.5 0.788
350 000 9 180 0.539 0.190 0.249 0.160 3900 0.570 2 4-I 0.227 3900 123 0. 792
400 000 9 900 0.672 0.166 0.265 0.157 3G90 0.595 2.33 0 223 3G90 123 0 i29
500 000 11 ,550 0.64% 0.134 0.297 0.153 3400 0.646 2.04 0.217 3400 135 0 036
GM) 000 12 900 o.ioo 0.113 0.327 0.150 3200 0.691 1.94 0.210 3200 13.5 O.GO8
750 000 15 660 0.780 0.091 0.366 0.148 3070 0.703 1.73 0.202 3070 140 0.548
-
G 360 0.323 0.495 0.151 0.195 6700 0.436 3.28 0.272 6700 115 0.928
0:: 6 940 0.364 0.392 0.171 0.188 6100 0.468 2.87 0 285 GlOO 125 0 826
0000 0.410 0.310 0.191 0.180 5520 0.503 2.67 0.256 5520 12.5 0.i88
250 000 i %i 0.447 0.263 0.210 0.177 5180 0.533 2.55 0.247 5180 125 O.iGl
300 000 9 690 0.490 0.220 0.230 0.172 4820 2 41 0.241 4820 125 0.729
350 000 10 100 0.532 0.190 0.249 0.168 4490 EE 2.If.i 0.237 4490 135 0,658
400 000 10 820 0.566 0.166 0.265 0.165 4220 0.623 2.08 0.232 4220 135 0 639
500 000 13 220 0.635 0.134 0.297 0.160 3870 0.672 1.94 0.226 3870 135 0 603
GO0 000 13 930 0.690 0.113 0.327 3670 0.718 1.74 0.219 3670 140 0.542
750 000 1B 040 0.767 0.091 0.366 33.50 0.773 1.6“ - 0.213 3350 140 0.510
1 000 000
--
00 8 240 0.376 0.495 0.147 0.234 8330 0.532 2.41 0.290 8330 135 0.839
000 8 830 0.364 0.392 0.171 0.208 7560 0.538 2.32 0.284 7560 139 0 I342
0000 9 660 0.410 0.310 0.191 0.200 6840 0.575 2.16 0.274 6840 13.5 0.618
250 000 10 330 0.447 0.263 0.210 0.195 6300 0.607 2.06 0.266 6500 13.5 0.597
300 000 11540 0.490 0.220 0.230 0.190 6030 0.640 1.85 0.260 6030 140 0.543
350 000 12 230 0.532 0.190 0.249 0.185 5700 1.77 0.254 5ioo 140 0.327
400 000 13 040 0.566 0.166 0.265 0.181 5430 ::,“;i 1.55 0.248 5430 140 0.513
,500 000 I4 880 0.635 0.134 0.297 0.176 5050 0.750 1.51 0.242 5050 150 0.460
600 000 16 320 0.690 0.113 0.327 0.171 4740 0.797 1.44 0.235 4740 150 0.442
750 000 18 980 0.787 0.091 0.366 0.165 4360 0.854 1.29 0.230 4360 155 0.399
1 000 000
-
1.1-c resistance based on 100% conductivity at 65°C. including 2% allowance for stranding.
‘(iAIR of sector-shaped conductors is an approximate figure close enough for most practical applications.
JFor dielectric constant=3.5.
‘Ikued on all return current in sheath; none in ground.
See Fig. 7.
‘The following symbols are used to designate the cable types: CR-Compact Round; CS-Compact Sector.

from 0.5 to 36.0 inches, which should cover the range met same insulation thickness is used for both grounded and
in practice. For all spacings less than 12 inches, 2d is ungrounded operation, but in cables rated 7000 volts and
ncgntive. above, a greater thickness of insulation is recommended
The constants calculated in this manner apply to one for a given-voltage class when cable is operated with an
three-phase circuit of single-conductor lead-sheath cables, ungrounded neutral. A good approximation of the elec-
:lssuming all zero-sequence return current to be in the trical characteristics of these higher voltage cables when
sllcaths, none in the ground. operated with other than a solidly grounded neutral, can
The GO-cycle characteristics of single-conductor oil- be had by referring in each specific case to the next higher
filled cables are given in Table 11. This table is similar in voltage class listed in the tables.
form to Table 10 and the impedance characteristics are The constants of several typical cables calculated by the
tlctermined in precisely the same way. Here again the methods outlined are listed in Table 13. These typical
sequence constants apply to one three-phase circuit of cases are included to be used as a check on the general
three cables with zero-sequence return current assumed to magnitude of cable constants when making calculations for
be all in the cable sheaths. Single-conductor oil-filled a specific case. Representative sizes and types of cable
cables have hollow conductors (the oil channel forms the have been chosen to cover as many types of calculation as
core), consequently Table 11 includes cables of the two possible.
most common inside diameters, 0.5 and 0.69 inches.
In each of the tabulations, the voltage class listed in the III. TABLES
OF CURRENT CARRYING
first column refers specifically to grounded-neutral opera- CAPACITY
tion. Frequently cable systems are operated with other One of the most common problems in cable calculations
than a solidly grounded neutral. In low-voltage cables the is that ef determining the maximum permissible amperes
82 Electrical Characteristics of Cables Chapter 4

TABLE 9--60-CYCLE CHARACTERISTICS OF THREE-CONDUCTOR GAS-FILLED PAPER-INSULATED CABLES


(SHIELDED TYPE)

- - -
Grounded Neutral Service
- -
I POSITIVE
N EGATIVE
&
SEQ
I ZERO-SEQLXNCE
I-
--
SHEATH

I
z
3.O’
g;:
130 2 3 800 0.292 0.987 0.106 5100 0.321 4.86 0.289 5100 110 1.29
130 1 4 320 0.332 0.786 0 126 4600 0.354 4.42 0.274 4600 110 1.21

130 0 4 010 0.288 0.622 0.135 0.172 4500 0.326 4.52 0 39 4500 110 1.30
130 4 440 0.323 0.151 0.165 4200 0.355 4.34 0.207 4200 110 1.28
130 0:: 4 970 0.364 EX 0.158 3800 0.392 3.90 0 24.5 3800 110 1.17
130 0000 5 620 0.417 0.310 :: ;:: 0.156 3500 0.437 3.58 0.234 3500 110 1.09

130 250 000 6 180 0 455 0.2fi3 0.210 0.153 3200 0.462 3.41 0 230 3200 110 1.05
130 350 000 7 530 0 539 0.190 0.249 0.146 2800 0.521 3.05 0 222 2800 110 0.953
130 500 000 9 540 0.642 0.134 0.297 0.141 2400 0.600 2.70 0 210 2400 110 0.834
140 750 000 12 900 0.780 0.091 0.366 0.137 2200 0.715 2.21 0.198 2200 115 0.707

1;jO 1 000 000 16 450 0.900 0.070 0.430 0.134 2000 0.810 1.80 0.193 2000 125 0.5;s

2 4 670 0.292 0.987 0.224 6900 0.376 4.17 0 302 fin00 110 1.06
5 120 0 332 0.786 0.215 6300 0.410 3 ,82 0.286 6300 110 1.01
:, 5 300 0.288 0.622 0.211 6200 0.398 3.62 0.302 6200 110 1.00

00 5 360 0.323 0.495 0.151 0.188 0.412 3.56 0.281 5800 110 1.02
000 5 910 0.364 0.392 0.171 0.178 “5%: 0.445 3.31 0.271 5300 110 0.971
0.191 0.175 4800 0.488 3.08 0.258 4800 110 0.922
8 0000
250 000
6
7
570
160
0.417
0.455
0.310
0.263 0.210 0.171 4500 0.520 2.92 0.249 4500 110 0 883

8 540 0.539 0.249 0.163 4000 0.575 2.64 0 240 4000 110 0.816
it% E 10 750 0.642 :: :i: 0.297 0.155 3500 0 6,55 2.36 0 230 3500 110 0 i-11
750 000 14 650 0.780 0.091 0.147 2900 0.760 1.84 0.218 3000 125
1 000 000 18 560 0.900 0.070 ::% 0.144 2600 0.850 1.49 0 210 “GO0 140 k%
-_ --
6 900 0.288 0.622 0.131 0.242 8400 0.477 3.00 0.320 8400 110 0.794
7 300 0.323 0.495 0.147 0.233 7900 0.509 2.69 0 310 7900 110 0.763
8 200 0.364 0.392 0.165 0.222 7300 0.545 2.58 0.284 7300 115 0.730

8 660 0.310 0.191 0.201 6700 0.570 2.43 0.281 6700 115 0.707
9 380 0.263 0.210 0.195 6300 0.604 2.32 0 270 6300 115 0 685
11200 0.190 0.249 0.185 5600 0.665 1.95 0.264 5600 125 0.587
12 790 0.134 0.297 0.175 4800 0.745 1.63 0.251 4800 135 0.500

0.767 0.091 0.366 0.165 4200 0.847 1.32 0 238 4200 150 0.409
0.898 0.070 0.430 0.158 3700 0.930 1.13 0.234 3700 160 0.353

- - -
X.%-C resistance based on 100% conductivity at 65’C. including 2% allowance for stranding.
2OhIH of sector-shaped conductors is an approximate figure close enough for most practical applications.
3For dielectric constsnt=3.7.
~Haued on all return current in sheath: none in ground.
%x Fir. 7.
6The following symbols are used to designate conductor types: SR-Stranded Round; CR-Compact Round; CS-Compact Sector.

per conductor for any given cable. The limiting factor iq multipliers to the tables presented for paper-insulated ca-
cable applications is not always the maximum permissible bles. The value for varnished cambric-insulated cables can
insulation temperature. Sometimes regulation, efficiency, be obtained by multiplying the value given in the tables
economy, etc., may dictate the maximum permissible am- for paper insulation by 0.91, the resulting figure being
peres. However because temperature rise is most often the accurate to within five percent of the calculated value.
controlling factor, the calculations of current-carrying Similarly, carrying capacities for rubber insulation can be
capacity are usually based upon this limitation. determined with the same degree of accuracy by applying
In Tables 14 through 19 earth temperature is assumed to a factor of 0.85 to the figure given for an equivalent paper-
be uniform at 20 degrees Centigrade. These tables were insulated cable. For special heat-resisting rubber this
taken from a publication*6 of the Insulated Power Cable factor becomes 0.95.
Engineers Association and give maximum allowable am- Circuits are frequently installed with each duct con-
peres per conductor for representative cable types. Cor- taining three cables. The current capacity of these cir-
rections for earth temperatures other than 20 degrees cuits will be less than that tabulated here for one cable
Centigrade are given within the tables. per duct, but will be somewhat higher than the capacity
Special conditions may make it advisable to calculate a of an equivalent shielded three-conductor cable of the
cable temperature problem in detail,10j11 taking into same conductor size and voltage rating..
account variable loading, “hot spots” along the cable The number of overhead power cables is a small per-
route, and other factors not contemplated in making up centage of the number in ducts, and for this reason space
the tabulated information. does not permit inclusion of loading tables for cables in air.
Approximations can also be obtained for the current- Unfortunately there is no simple correction factor or curve
carrying capacities of other types of insulation by applying that can be used to translate the figure for cables in ducts
Chapter 4 Electrical Characteristics of Cables 53

TABLE lo-60-CYCLE CHARACTERISTICS


OF SINGLE-CONDUCTOR CONCENTRIC-STRAND
PAPER-INSULATEDCABLES
Grounded Ncutrnl Service
- - - -
T
-

r. 2-r r,
-

6
c
2
: ’ i i
:
; a i
( f
I : ?
i B ;
: I I c
- _- _- _-
:

560 0 lR4 0.06i 0.628 0.489 2 50


ii 670 0 232 0 OR4 0 602 0 4i5 1.58 220 I 340 0.232 0.084 0 602 0 412 I 58
60 RR0 0 292 0.106 0.573 0.458 0 987 215 1 500 0 292 0.106 0 4OR 0 osi
60 990 0.332 0.126 0.552 0.450 0.786 210 1610 0.332 0.126 i :a:
I 0 400 0 776
60 (110 0373 0 141 0.539 0.622 3.61 !250 200 0 1710 0.373 0 141 0.539 0.397 2 59
60 0: I270 0.418 0.159 0 524 0.495 3.34 !040 195 1940 0.418 0.159 0 524 0 301 2 32
60 000 I510 0 470 0 178 0 512 0.425 0.392 3 23 !840 185 0:: 2 100 0.470 O.liB 0.512 0 3% 2 2-I
60 0000 I 740 0 528 0 200 0.496 0.414 0.310 2.98 1650 : 180 0000 2300 0.526 0.200 0.496 0 3x0 2 14
u
60 250 000 I 930 0 575 0.221 0.484 0.408 0.263 2.Sl 1530 175 250 000 2500 0.575 0.221 0 484 0 37 0.263 2 06
60 3.50 000 2490 0.681 0.262 0.464 0.392 0.190 2.31 1300 175 350 000 3 110 0.681 0 262 0 464 0 h6fj 0. 190 1 9x
60 500 000 i 180 0.814 0.313 0.442 0.3i8 0.134 2.06 1090 175 500 000 3 940 0.814 0 313 0.352 0 134 1 51
60 750 000 4380 0.998 0.385 0.417 0.358 0.091 1.65 885 175 750 000 5240 0.998 0.385 ii :i2 7 0.336 0.091 1.26
60 1 000 000 5560 1.152 0.445 0.400 0.344 0.070 1.40 800 1 175 1 000 000 6350 1.152 0.445 II 400 0.325 1 15
60 1 500 000 3000 1.412 0.543 0.374 0.319 0.050 1.05 645 175 1 500 000 8810 1.412 0 546 0.374 0 305 0.90
60 ? 000 000 1190 1.632 0.633 0.356 0.305 0.041 0.89 555 t 175 2 000 000 1080 1.632 0.633 0 356 0,294 0.ii:
_- -- - --
75 600 0.154 0 067 0.628 0.481 2.50 5.80 1810
75 720 0.232 0 OR4 0.602 0.467 1 58 5.23 I020
is
75
930
1040
0.292
0.332
0.106
0.126
0 573 0.453
0.445
0.987 4.31 i300 295 2 l 920 0.292 0.106 0.3x3 D.QYi 2 16
0.552 0.786 4.03 2990 285 1 2010 0.332 0.126 0 380 O.iY6 2 12
1170 0.373 0 141 0.539 0.436 0.622 3.i9 36iO 275 0 2 120 0.373 0.141 0.539 0 3ii 0 622 2 05
2 0: I320 0.418 0.159 0.524 0.428 0.495 3.52 2450 265 2250 0.418 0 159 0.524 0 375 0.495 ‘2 02 90
000 I570 0.470 0.420 0.392 3.10 2210 260 02 2 530 0.470 O.liR 0.512 0 370 0.392 1 35 iooo 95
2 0000 I800 0.528 EL! i::; 0.412 0.310 2.87 3010 250 0000 2 740 0.528 0.200 0.496 0 366 0.310 1 i9 5350 95
b

75 250 000 I 990 0 575 0.221 0.484 0.403 0.263 2.70 1860 : 245 250 000 2930 0.575 0 221 0.484 0 361 0.263 1 72
75 350 000 2 550 0.681 0 262 0.464 0.389 0.190 2.27 1610 240 350 000 3 550 0.681 0 262 0.464 0.352 0.190 1 51
75 500 000 1340 0 814 0.313 0.442 0 375 0.134 1.89 (340 240 500 000 4300 0.814 0.313 0.341 0.134 1 38
i5 i50 000 4 5iO 0 998 0.385 0.417 0.352 0.091 1.53 LO60 I 240 750 000 5630 0.998 0.385 X2 i 0.325 0.091 1 15
75 000 000 5640 1.152 0.445 0.400 / 0.341 O.OiO 1.37 980 I 240 1 000 000 6910 1.152 0.445 0.400 0.313 0 070 1 01 ?‘;OO
75 500 000 3090 1.412 0 543 0.374 0.316 0.050 1.02 805 1 240 1 500 000 9460 1.412 0.546 0 374 0 296 0.050 0 901 “360
75 ! 000 000 3300 1.632 0.633 0.356 0.302 0.041 0.87 685 1 240 2 000 000 1790 1.632 0.633 0.356 0 285 0.041 0 69’ 2070
lzo
-- i- -- -- - -. -
740 0.184 0 067 0.628 0.456 2.50 4 47 jiO0
115
110
890
1 040
0.232
0.292
0.084
O.lOF
0.573
0.573
0.447
0 439
1.58
0 987
4.17 5540
4520
395 0 2900 0.373 0.141 0.5390.352 0.622 1 51 9150
3.85 385 3 040 0.418 0.159 0.524 0.350 / 0.495 1 48 9420
110 1160 0.33: 0.12E 0.552 0.431 0.786 3.65 1100 370 0:: 3 190 0.470 0.178 0.512 0.347 0.392 1 46 761’0
355 0000 3380 0.528 0.200 0.496 0.344 0.316 1 43 6870
I05 0 1270 0.373 0.141 0.539 , 0.425 0.622 3.4i 3600
100 1520 0.41C 0.151 0.524 0.420 0.495 3.05 3140 350 250 000 3 590 0.575 0.221 0.484 0.342 0.263 1.39 6410 100
100 0:: 1710 0.47( 0. lifi 0.512 0.412 0.392 2.91 2860 345 350 000 4230 0.681 0.262 0.464 0.366 O.lQC 1 24 5640 105
95 0000 I8iO 0.52: 0.20[ 0.49E , 0.406 0.310 2.74 2480 345 500 000 5040 0.814 0.313 0 442 0.325 0.134 1 15 4940 105
<
345 750 000 6430 0.998 0.385 0.417 0.311 0.091 0 9i 4250 110
90 250 000 2080 0.571 0.221 0.484 I 0.400 0.263 2.6: 2180
90 350 000 2 620 0.681 0 262 0.464 I 0.386 0.190 2.2( 1890 345 1 000 000 7 780 1 152 0.445 0.400 0.302 0 07c 0 86 3750
!I0 500 000 3 410 0.814 0.313 0.441 0.369 0.134 1.8: 1610 345 1 500 000 0420 1.412 0.546 0.374 0.285 o.osc 0 ifl 3210
90 750 000 4650 0.991 0.385 0.41i 0.35c 0.091 1.4! 1350 I 345 2 000 000 2830 1.632 0.633 0.356 0.274 0.041 0.61 2830
90 1 000 000 5350 1.15: 0.44: 0.4Of I 0.339 0.070 1.2; 1 - -- -- -
90 1 500 000 8 160 1.41: 0.542 0.374 I 0 316 0.05a 1.0: 1
90 2 000 000 103iO 1.632 0.663 0 35f b 0 302 0.041 0.8; I 475 000 3910 0.470 0.178 0.512 0 331 0.392 1.20 ERQO 105
150 ‘390 0.184 0.06i
-.
0.62f I
- -- 460 00004080 0.528 0.200 0.496 0.329 I 0.310 1.19 8100 105
0.431 2.50 3.6: 7780
150 1010 0.232 O.Of3 0.60: , 0.42E 1.58 3.2: 6660 , ,450 250 000 4290 0.575 0.221 0.484 0.326 0 263 1 16 i5iO 105
140 1 150 0.292 O.lOf 0.57: I 0.417 0.987 3.01 5400 / 445 350 000 4990 0.681 0.262 0.464 0.319 / 0 19c 1 05 6720 110
140 1330 0.332 0.12f 0.55: , 0.411 0.786 2.91 4920 , 445 500 000 5820 0.814 0.313 0.442 0.31c , 0.134 0.93’ 5950 115
445 750 000 7 450 0 998 0.385 0.417 0.29t 0 091 0.80 5130 120
135 0 1 450 0 372 0 141 I 0.4Of 0.622 2.8: 4390 ,
130 1590 0.415 0.155 Ez I 0.403 0.495 2.7( 3890 , 445 1 000 000 8680 1.152 0.445 0.4oc 0.29c , 0 Oil 0.75 4610 120
125 02 1760 0.47( 0.17f 0 51: , 0.395 0.392 2 5! 3440 , 445 1 500 000 1420 1.412 0.546 0.275 0 051 0.61 3930 130
I20 0000 1960 0.528 0.2Of 0.49t , 0.381 0.31c 2.2s 3020 I 445 2 000 000 3910 1.632 0.633 K 0.264 0.041 0.54 35?0 135
I20 250 000 2 250 0.57! 0.221 0 4%I 0 383 0.263 2.ll 2790 , - --
I15 350 000 2 730 0.681 0.26: 0.46: I 0.371 O.lQC 1.9( 2350 L 650 350 000 6720 0.681 0.262 0.464 0.291 0.191 0 ii 4590 120
I15 500 000 3 530 0.81( 0.31: 0 44: , 0.361 0.134 1.6% 2010 , 650 500 000 7810 0.814 0.313 0.442 0.284 0.134 0 69 i680 125
115 750 000 4 790 0.998 0.3% 0 41i 0.341 0.091 1.3! 1670I 650 750 000 9 420 0 998 0.385 0.417 0.275 0 091 0 61 6700 130
0940 1.152
I15 1 000 000 6000 1.15: , 0.41! 0.40( 0.331 0.07c 1.2: 1470I
650 I 000 000 0.44: 0.40( 0.267 0.0x 0 55 6060 13.5
II5 1 5oa 000 6250 1.41: 0 54: 0.374 I 0.311 0.05c 0.9; 1210,
II5 2 000 000 1’0480 1.63: , 0 662 0.35f , 0 297 0.041 O.i< 1055 /
650
650
1 500 000
2 000 000
3 680 1.412
6320 1.632
0.54E
0 633
0 374
0.35e
0.25E ,
0.2.R ,
0.05(
0.041
0.M
0 43
5250
4i10
140
145
- - - - - - - - - - -
Positive- and Negative-Sequence Impedances: 1 Conductors are standnrd concentric-stranded. not cmnpact round.
*A-c Resistance based on 1007” conductivity at 65T. including 2 7’0 alloaanrr for strandinr.
(a) Neglecting Sheath Currents; ‘For dielectric conskmt=3.7.
zl=z2=r,+j(xa+xd).
(b) Inclu$ng Shea;h Currents; Zero-Sequence Impedance:
(Based on all return current in sheath; none in ground)
zI=zZ=rc+ Ei+j(xa+n-&i) zo=r.+r.+l(x.-x.)
Where x,,, = (i8+xd).
Note: xd is obtained from Table 12.
84 Electrical Chnrncteristics of Cables Chapter 4

TABLE ll-60-CYCLE CHARACTERISTICS


OF SINGLE-CONDUCTOR OIL-FILLED (HOLLOW CORE)
PAPER-INSULATEDCABLES
Grounded Seutral Service

i
I-
INSIDE DI.1WETEROFSPRINGCORE- 0.5 INCHES
- - T INSIDE DIAMETER OF SPRIWG CORE = 0.69 ISCFIES
-
2s I- L. $
=a re
ki
2 z a
$ ; m z : 2
E
5;
Em
ge
z u
2 >aa.
: 2:
22
02
;.T j 22
‘t 1z.e Id
:s;: :h ;O :
12
'E r: ;T :&
$$ so $ ‘22
;2 22 sg 3s:
I& ,3n
ti- ;2 ;z PI” c:
:; .gs ET ;$ $
,j:
pz.2 so g”+ ; 2m
1+ 2 z:$
jd ^ 2: ; LZ 17"
0; jS gg 2.7 0 J?c 12
-
$z cu :rno. 'Cf
- -2’ c
-__ s2am
-CL
00 ).I!% Ilo ooc
ooa
on00
39H0
I090
4 320
O.i36
0 76X
0.807
0.345
0 356
0 373
0
0
0
431
427
421
I 333
1331
1 32X
I 392
) 310
i:E
I. 130
j240
ioio
I900
110
110
oooc
250 000
4860 0.921
5 090 0 956
5 290 0 983
0 439 0.399
0.450
0.460
0 398
0.396
0 320
0 3li
0 315
n 392
0 310
0 263
ooi
I.985
) 9i5
1450
1350
1230
115
I15
115
250 000 4650 0.837 0.381 0 418 1 325 I.263 L.057 I700 115
350 000 5 950 1 050 0 483 0.390 0 310 0 IRR I. 99i IO00 I20
350 000 5 IS0 0.918 0.408 0 410 I 320 ). IX8 I.009 1470 II5 500 000 6700 I 145 0 516 0.3R2 0.304 I 850 I700 I20
10 6 100 1.0% 0.44R 1 312 1 I.33 1070 750 000 8080 1.2X6 0.295 i I!; 125
;; 500 000 0 399 1 905 I?0 0.550 0.374 1 759 1410
750 000 7310 1.1x0 0.505 0.3x4 I.302 I. 0x9 I.838 3620 I?0 1000 ooc 9440 1.416 0 612 0.360 0 258 0 ok7 I 688 1140 130
1000 000 8630 1.310 0.550 0.3i4 1.294 1 068 I.752 3380 I25
1500 000 1970 1.635 0.692 0.346 0 276 0 047 1 601 1750 135
1 500 000 1090 1.547 0.639 0 356 1.281 1.048 1.649 2920 130 2 000 ooc 4450 1.835 0.763 0.334 0 266 0.038 I.533 2510 140
2 000 000 13 750 l.i60 0.716 0 342 I.270 I 039 I.550 25iO 140 -~ -
oooc 6 590 0 956 0 450 0 398 0 295 0 310 1 i60 5950 125
- ~___ - 250 OOC 6 800 0 983 0.460 0 396 0 294 0 263 3 i.52 5790 125
0000 .5 720 0.307 0 373 0 421 1.305 1310 1.805 3850 z 350 ooc 7 340 1 050 0 483 0.390 0.290 0 188 3 i-29 5540 125
250 000 5 930 0.x37 0 381 0.418 I 303 I 263 3.793 500 120 500 ooc 8320 1.145 0 516 0.382 0 284 0 132 3 669 5150 130
350 000 6 390 0.918 0.406 0 410 1 298 1 188 3.730 5090 12.5
500 000 7480 1.028 0.44E 0.399 3.291 1.133 3.692 5600 125 750 OOC 9790 1.286 0.550 0.374 0 277 0 089 Cl 606 1770 135
1060 1 416 0 612 0.360 0 2io 0.067 0 573 4430 135
2 750 000 8 950 1 1X0 0 ,501 0.384 3.283 3.625 5040 : E ::I 3900 I.635 0 692 0 346 0 260 3920 145
130 0 490
1 000 000 10350 1 310 0 55C 0.374 3.276 i: 2: D 568 4700 135 2 000 ooc 6610 1 X35 0.763 0.334 0 251 i ::A 0.440 3580 150
1 500 000 12 960 1.547 0 631 0.356 3.265 3.048 3.500 4110 140 -- -- -
2 000 000 15530 1.760 0 ilf 0.342 3.255 3.039 0 447 3710 145 OOO( 7390 0.956 0.45c 0 39F O,i86 0.310 6590 130
- -- - -
250 OOC 7610 0.983 0.46C 0 39F 0 285 0.263 i: iii: 6480 130
8 170 1.05C 0 483 0 391 0 281 0 188 0 649 6180 130
ODOC 6 480 0 807 0.372 0 421 0.295 0.310 0.758 7410 125 % ooil 9180 1.145 0.51E 0 3% 0 276 0.132 0.601 5790 135
250 000 6 700 0 837 0.381 0 418 0.293 0 263 0.746 7240 125
330 000 7 460 0.918 0 4OF 0.410 D. 288 0 188 0.690 6820 130 750 001 0660 1.28E 0 55c 0 374 0 269 0.089 0 545 5320 i40
500 oat X310 1.028 0.44f 0.399 D. 282 0.133 0.658 6260 / 130 2010 1.4IE 0.61: 0 36C 0 263 0.067 0 519 4940 140
: %i K 4450 1.63: 0.69: 0 34t 0 253 0 047 0 462 4460 145
P 750 ooc 9800 1.180 0 50: 0.384 0.274 0.089 0.592 5fi80 , 135 2 000 001 6820 1.831 O.i6: 0 336 0 245 0.038 0.404 4060 155
1 000 ooc 11 270 1 310 0.55c 0.374 0 268 0.068 0.541 5240, 140 -- -- -
I 500 ooc 13720 1.547 0 356 0.257 0.048 0.477 467C1 145 250 001 8560 0.983 0.46C 0.39f 0 275 0.263 0 596 72la 135
2 000 ooc 16080 1.760 % 0 342 0.248 0.039 0.42i 417c, 150 9140 1.05c 0.4% 0 39c 0.2i2 0.188 6860 135
;i; !!I 0 280 1.14( 0.51( 0 38: 0.267 0 132 i i;": 6430 140
- __- - -- - > 750 001 I1 770 l.?Rf 0.55( 0.37. 0.261 0.089 0.492 5980 145

250 ooc 7 600 0 837 0 381 0 418 0 283 0.263 0.660 798C 130 1 000 001 13 110 1.4lf 0.61: 0.36( 0.255 0 067 0.469 5540 145
350 ooc 3390 0.918 0.401 0 110 0.279 0.188 0.611 752c 135 1 500 001 15 840 1 63: 0 69: 0 341 0 246 0 047 0 4?1 4980 150
500 ooc 9270 1.028 0.44l 0 399 0 273 0.133 0.585 69-s 135 2 000 001 18840 1.83! 0.76: 0.33. 0.238 0.038 0 369 460C 160
750 ooc 0840 1.180 0.5oi 0.384 0.266 0.089 0.532 632C 140 __- -
5:
(0 750 001 15360 1.281 0.551 0.37. 0.238 0.089 0.369 761C 160
1 000 ooc L2 340 1.310 0.551 0.374 0.259 0.068 0.483 588C 14.5 1 000 001 16790 1.41( 0.61: 0 361 0 233 0.067 0.355 714c 160
1 500 ooc 15090 1.547 0.63! 0 356 0.246 0.048 0 433 519a 1.50 :
>
2 000 ooc 18 000 1.760 0.711 0.342 8.241
-
0.039 0.391 471c
- ‘i -
1.55
-
2 000 00’ 12990 1.83!
-
0.76:
-
0.33‘ 0.219 0.038
-
0.315 596C
-
170

‘A-r Resistance based on 1OO7o conductivity at tX°C. including 270 allowance for stranding. Above values calculated from “A Set of Curves for Skin Effect in Isolated
Tubular Conductors” by .4. W. Ewan. G. E. Review. Vol. 33, April 1930.
ZFor dielectric constant = 3.5.
SC&&ted for circulirr tube as given in S~mmelrica~ Components by Wagner & l?,vans, Ch. VII, page 138.

Positive- and Negative-Sequence Impedances: Zero-Sequence Impedance:


(a) Neglecting Sheath Currents; (Based on all return current in sheath; none in ground)
zl=zz=r,+jk+x,~). z~=r~+r.+j(x.-xX.)
(b) Including Sheath Currents:
z1=z2=ro+- ‘21 ‘a +j
x&-l-r:
Where x,,, = (x.+x,J. ,
Note: xd is obtained from Table 12.

to a reasonable figure for cables in air. The current-carry- IV. CABLES IN PARALLEL
ing capacities of cables in air have recently been revised The problem of current division among paralleled cables
by the IPCEA and are now available in the cable manu- is frequently encountered, because in many circuits more
facturers’ catalogs. than one cable per phase is installed in order to carry the
In the discussion on proximity effect it was mentioned total current. Also, mutual effects may develop between
that where cables are installed parallel to steel plates, the cable circuits which are adjacent throughout their length
extra losses arising from proximity to the plate may affect but which terminate on separate busses. Depending upon
the current-carrying capacity. This reduction in carrying the type of circuit, the cable type and configuration, and
capacity is given by the curves of Fig. 19 which are taken the system conditions being investigated, the problem may
from the test values presented by Booth. take any of several forms.
Chapter 4 Electrical Characteristics of Cables 55

TABLE lZ-REACTANCE SPACING FACTORS (Q)*, OHMS PER MILE AT 60 CYCLES

.-
-
In. Xd In. Xd In. In. zd In. xd In. 2d In. Xd In. Xd
-.
2.75 -0.179 5.25 -0.100 7.75 -0.053 10.5 -0.016 15.5 0.031 20.5 0.065 27.0 0.098
0.50 -0.385 3.00 -0.169 5.50 -0.095 8.00 -0.049 11.0 -0.011 16.0 0.035 21.0 0.068 28.0 0.103
0.75 -0.336 3.25 -0.159 5.75 -0.089 8.25 -0.045 11.5 -0.005 16.5 0.039 21.5 0.071 29.0 0.107
1.00 -0.302 3.50 -0.149 6.00 -0.084 8.50 -0.042 12.0 0.0 17.0 0.042 22.0 0.074 30.0 0.111
1.25 - 0.274 3.75 -0.141 6.25 -0.079 8.75 -0.038 12.5 0.005 17.5 0.046 22.5 0.076 31.0 0.115
1.5O -0.252 4.00 -0.133 6.50 -0.074 9.00 -0.035 13.0 0.010 18.0 0.049 23.0 0.079 32.0 0.1 I!)
1.i5 -0.234 4.25 -0.126 6.75 -0.070 9.25 -0.032 13.5 0.014 18.5 0.053 23.5 0.082 33.0 0.123
-0.217 4.50 -0.119 7.00 -0.065 9.50 -0.028 14.0 0.019 19.0 0.056 24.0 0.084 34.0 0.126

1-
2.00
2.25 -0.203 4.75 -0.112 7.25 -0.061 9.75 -0.025 14.5 0.023 19.5 0.059 25.0 0.090 35.0 0.130
2.50 -0.190 5.00 -0.106 7.50 -0.057 10.00 -0.022 15.0 0.027 20.0 0.062 26.0 0.094 36.0 0.133
-
J logto 5,s where S is spacing in inches.
*zd=O.2704 60

SENDING BUS RECEIVING I31


rt is difficult to anticipate in detail the problems met in a bc
1 1 j--LENGTH IN MILES
prnctice, but the examples outlined here indicate methods ------4 P
,I[ solution that can be modified to fit actual circumstances.
hlmost any problem involving paralleled cables can be
rapresented by simultaneous equations of voltage drops
caused by self and mutual impedances but such equations
often become numerous and cumbersome. Therefore in Ib’
:tpproaching most problems it becomes desirable to search b’ ” -
:tt)out for one or more simplifying assumptions so that the
problem can be reduced to simpler terms, still without
introducing errors large enough to invalidate the solution.
ITor example, when paralleled cable circuits connect a
gcncrnting source to a balanced load, it is usually permis-
sible to assume that the total current in each phase is com-
posed only of the respective positive-sequence component:
this assumption is based on the unsymmetrical cable-cir-
cuit impedances being much smaller than the symmetrical E. Eb Ec i I
load impedances. f I
Three outlined examples of calculations on paralleled ////////////////////N///////////////////lll//N////// 1 I
wbles are included here, but they assist only by illustrating (ZERO CURRENT IN EARTH RETURN PATH)
gcncrnl methods, since there are so many different, and
Fig. 16-Equivalent circuit for parallel cables, with open-
more complex, cases to be found in practice. circuited sheaths and no net ground-return current (see
Example 3).

h TABLE 13-60-CYCLE CONSTANTS OF TYPICAL CABLES IN OHMS PER PHASE PER MILE

r POSITIVE- AND NEGATIVE-


SEQUENCE
ZERO-SEQUENCE
(ALL&yTUHFN IN

DESCRIPTION RESIS fi- REACTANCE 1

CP%.E il
z-
82
ZjE
2;
sin!&-Conductor. 1000 AMCM. 30/64 in. Insulation; M in. Sheath 0.070 0.114
‘l%rre Cshlrs spaced 4 in. horizontally.
~~inulc-Condt~ctor, 500 MCM. 9/64 in. Insulation; 6/64 in. Sheath 0.134 0.162 0.302 1.87 0.081 2 440
‘hrre Cables spaced 3. 3. 6 in ..... .... .......... .... .........
SinRk-Conductor Oil-Filled 750 MCM. inside diam. 0.50 in. 650 mil 0.089 0.221 0.422 6 300 0.631 0.115 6 300
Inslllntion: 9/64 in. Sheah. Three Ciblbles spaced 13 in. horizontall:
sinKlc-Conductor 250 MCM. 6/64 in. insulation; 7/64 in. Sheath 0.263 0.239 0.181 2 270 0.960 0.381 2 270
‘rhWe Shentha in contact and 4/O Copper Neutrirl Wire.
.
r’lrep-qonductor belted; Sectored. 500 MC&l. 7/64 in. Conductor III- 0.134 0.13.; 2.53 0.231 4 670
~~ll~fwn. 4/f% in. &It. 7.5/64 in. Sheath, .. ..... .. ......... ...
‘l“lrcc-Cunductor Type H. Sectored. 500 MCM. 13/64 in. Insulation 0.134 0.133 0.156 2 10 0 226 3 400
s/64 in. Sheath. .... ........................................

Thr*Conductor Oil-Filled Type H. Sectored 500 MCM. 225 ivIiL In 0.134 0.135 0.160 1.94 0.226 3 870
s”lation. 8.5/64 in. Sheath ..... :. ...... .: .... ...... .... .....
‘Conductor temperature 65°C.; Sheath temperature 50°C.
86 Electrical Characteristics of Cables Chapter 4

TABLE 14-CURRENT CARRYING CAPACITY OF THREE-CONDUCTOR BELTED PAPER-INSULATED CABLES


Sumher of Equally Loaded Cables in Duct Rank

C0ndW2- ONE THREE SIX NINE TKELYE


I I I I
tar Condllc-
Size t”T Per Cent Load Factor
A\VC ty,,e,
IOOo”rCM 30 / SO 1 75 / 100 1 30 i 50 I 7.5 I 100 1 30 I 50 / 73 I 100 I 30 1 50 1 73 I 100 I 30 1 r,O / 7.5 I 100

.-\XIPERES PER CONDUCTOR2


___~

-
6 80 78 75 81 78 79 74 72 6.5 58 76 R!) Ill s4
4 1% 1Oli 109 98 108 102 96
73 2 104 97 it 34 84 74 100 90 79 69
2 143 13!) 134 128 139 133 124 115 136 127 115 108 !) .5 130 117 101 80
1 164 161 153 146 130 132 l-11 130 156 145 130 ::A 122 108 148 133 113 100

18!) 184 177 168 184 17.5 162 149 180 166 149 134 175 159 l-10 122 170 I;,? 130 11.4
218 211 "OR 192 211 201 183 ’ 170 208 190 170 1.52 201 181 158 138 19.5 173 148 128
2so ‘I? 2.3% 219 242 2?!1 211 ID3 287 217 193 172 !?09 206 379 l.ifi 2'13 I !I7 167 143
286 270 "Ii4 249 276 260 240 218 270 246 218 1!J4 261 234 202 li6 23-L 21.3 18!1 163
2.x 31fi 305 2!11 273 .303 288 263 ?39 207 271 230 212 288 258 221 l!)? 270 24-I ?Oc, 177
300 3.X 340 324 304 3-10 32 1 292 264 3x2 301 264 234 321 283 24.5 211 310 271 227 19;
350 3!U 376 357 334 375 353 320 288 366 390 288 25.5 331 311 xc, 229 341 2!lli 248 211
400 424 406 383 359 406 380 344 300 395 35s 309 272 380 334 ‘28.5 244 Xi 317 "Ii4 224

487 465 4R!) 408 465 433 390 348 451 403 348 433 378 320 273 417 :x7 "!I6 251
r,?‘i 517 487 450 Ii17 480 430 383 501 444 383 480 416 3ao 2!)8 462 393 ,323 273
618 581 550 SO5 5X5 541 482 427 566 500 427 541 466 390 331 5 1!I 439 330 302
(I.07 nt 10-c. ".!U al: 3'pgja ,
:1.07 at 10°C :, 0I.!12 *t 3O'C. (I.07 nt 10°C. o.op a t3 (1.07 at 10°C. 0.0% at 3O'C. ,
1.07 at 1OT. 0.02 at 30°C.
0.83 :a 40°C. 0.73 at 5, 0.9 at 40°C 0 .73 at 5O'C)3 0.83 at 40% 0.73 a,t:, 0.83 at 40~0. 0.73 at 5,PC," 0.x1 nt ‘WC:. 0 73 at 5OT)1
-
7,x0 Volts Copper Temperntore 83°C
-
81
107
140
80
105
137
77
101
132
74

1%
79
104
136
76
100
131
72
94
122 113
::
78
103
134
74
06
125 113
ii: E 102
77
100
130
71
92
ll!)
64
82
103
57
73
93
7.;
!I8
127
69
89
114
60
77
99
53

:t
161 156 150 143 156 149 138 128 153 142 128 115 149 136 1’0 105 14.5 130 112 98
186 180 174 165 180 172 156 146 177 163 148 131 172 155 136 120 167 14!1 128 111
214 206 198 188 206 196 181 166 202 186 166 148 196 177 1.53 135 191 169 145 125
243 2.36 226 214 236 214 206 188 230 211 188 168 223 200 174 152 217 192 163 141
280 270 258 243 270 2.55 235 214 264 241 213 190 'jj 229 198 172 247 218 184 159

311 300 287 269 300 283 2,59 23.5 203 266 235 208 282 252 217 188 273 240 200 174
340 336 320 300 33.S 316 288 260 326 296 259 230 315 279 210 207 304 263 223 190
385 36'0 351 328 369 346 315 283 359 323 282 249 345 305 261 224 333 289 242 206
417 399 378 353 308 373 338 303 388 348 303 267 371 317 2iR 230 360 30!) 257 220

476 454 429 399 4.54 423 381 341 440 392 340 298 422 369 312 267 406 348 288 245
534 508 479 443 507 471 422 376 491 436 375 327 469 408 343 291 4.51 384 315 267
607 576 540 497 573 532 473 41.3 555 489 418 363 529 455 381 323 .507 428 350 29.5
(I.08 at 10°C. 0.w at 30°C. (1.0X at IfPC. 0.92 nt 30°C. (1.08 at 10°C. 0.92 at 30°C. (1.08 at 1O’C. O.!l2 at 30°C. (1.04 at 10~~. n.w at 30-c.
0.83 at 40%. 0.72 at 5OT)J 0.83 at 4O"C. 0.72 at 50°C)~ 0.83 nt 4OT. 0.72 at 5OT)3 0.83 at 4O'C. 0.72 at 50°CXs 0.83 at 41l'C. 0.72 at 5OW'
-

-
78
102
132
77
!I9
120 12%5
ii”6 71
92
119
;:
129
74
9s
123
ii
11.5 106
Ei ;::
126 123
Fig 112!i; :A
no
i?J
88
72
03
120
65
85
108 ii:
57 .50

Ei
15 1 147 142 135 146 140 131 120 144 140 128 112 99 136 122 107 92
175 170 103 155 169 161 130 138 166 153 123 161 146 128 112 1.X 1.39 120 104
200 I!)4 187 177 194 184 170 156 189 175 139 183 166 14.5 127 158 135 117
230 223 214 202 222 211 195 178 ,217 199 158 210 189 165 143 :a: 180 153 132
266 257 245 232 2.53 242 222 202 ‘i-19 228 179 240 21.5 187 158 233 !205 173 149
?A0 205 284 271 255 281 268 245 221 276 251 220 196 266 239 177 22.5 189 163
300 330 317 301 283 316 297 271 24.5 307 278 244 215 295 264 194 248 208 178
3.50 365 34!) 332 310 348 327 297 267 339 305 266 235 324 289 211 271 227 193
400 304 377 357 333 375 352 319 2X6 365 327 285 251 349 307 224 290 241 206
449 429 406 377 428 399 3.39 321 414 396 319 280 306 346 293 250 370 32s 269 220
502 470 450 417 476 443 396 352 459 409 351 306 438 380 319 273 420 358 294 249
572 543 510 468 540 499 444 393 520 458 391 341 494 425 356 302 471 309 326 27.5
11.00 at 10°C. 0.90 at 30°C. (I.09 at 1O’C. 0.00 at 3O’C. 1ooc. 0.00 at 309C. (1.00 at 1ooc. O.!lO’ 3OT
0.79 at 40°C. 0.67 at 5"T13 0.70 at 4ooc. 0.66 at 5OT)" (k7oi 40°C. 0.66 at 50%) 0.70 at 4vc. 0.68 a, OYX 1
-
1 The folloainr symbols arc used here to desianate conductor types:
S-Solid copper. SR-standard round concentric-stranded. CS-compact-sector stranded.
2 Current rat&s are based on the folloainX conditions:
a. Ambient earth temperature= 20°C.
b. 60 cycle slternatina current.
c. Ratings include dielectric loss. and all induced a-c losses.
d. One cable per duct. all cables equnlly loaded and in outside ducts only. .
a Multiply tabulated currents by these fsctors when earth temperature is other than 20°C.

Example d--Type of Circuit.: A three-phase GO-cycle load current (positive-sequence only), and its magnitude /
cable circuit connected between a sending and a receiving is known. The cable conductors can be of different sizes,
bus, using single-conductor unsheathed cables, and having and their spacings can be entirely unsymmetrical.
two paralleled cables per phase. Problem: To find the division of load current among all 1
Conditions: The current flowing into the sending bus conductors.
and out of the receiving bus is nearly balanced three-phase Circuit: Refer to Figure 16.
Chapter 4 Electrical Characteristics of Cables 87

TABLE l&CURRENT CARRYING CAPACITY OF THREE-CONDUCTOR SHIELDED PAPER-INSULATED CABLES


I I Number of Equally Loaded Cables in Duct Bank

OSE I THREE
I
SIX
I
NINE
I
TWELVE

Per Cent J.oad Factor

I I AMPERES PER CONDUCTOR’

- - - - -
YI 87 81 75 89 83 66 a7 78 60 84 7.i ,i-l 31;
119 114 104 ‘95 116 108 it 85 113 102 77 IOY Yfi 83 72
153 144 13Y 121 149 136 120 107 144 12!l !I7 13!) 123 1o.k !)O
172 163 149 136 168 153 136 121 162 145 1OY 1.X 138 lli 100

196 185 It39 154 190 173 154 137 183 164 141 122 178 1.X 131 112
225 212 193 175 218 1’?8 174 IS6 211 167 162 139 203 177 I.48 12i
258 242 220 198 249 225 19s 174 241 212 182 157 232 202 168 14.1
295 276 250 223 285 2.57 224 196 275 241 205 176 26.5 227 lS9 162

325 305 276 246 315 283 245 215 303 265 221 193 2Yl 2.50 177
364 339 305 272 351 313 271 236 337 2!)3 246 211 322 Zifi 1!)4
397 369 330 293 383 340 293 2s 366 818 267 227 350 301 208
429 396 3s4 314 413 366 313 273 3’34 340 283 242 376 320 222

:;I,,, 483 446 399 350 467 410 350 303 444 381 318 269 419 368 24i
lillll 534 491 437 385 513 450 384 330 488 416 346 2!13 465 3YO Xi!,
751, CS 602 551 485 426 576 502 423 365 545 464 383 323 51; 432 21):s
10x .91 *t 30°C .Ol nt 3 *t lOT 13 “OC.
b’,g 4OT .:: :i yzgjd ‘($g 10-c
4OQC :o”.71 at 5ov2i~
-
(1.08 at
O.R’L *t
IVC
40% .71 at 5 g:c”iz
-
$:801: *t 4OT :o” : S’UT)’

23 000 Volts
- - Copper Tempera tu1
- ‘e 77°C
T
156 1.50 I 143 I 134 145 1 132 117 1O.S 140 125 107 84 134 119 100 ( 88.-
177 170 162 152 164 j 149 132 117 159 140 12 1 105 124 133 112 i 97
200 192 172 192 182 149 186 169 147 132 178 158 136 118 173 14Y 126 i lo!1
227 220 IY7 221 208 170 212 193 168 149 202 181 156 134 lY6 172 14-1 12.3
262 25 1 223 2.54 238 193 242 220 191 169 230 206 175 150 222 195 162 I:<!1
301 289 251 2Yl 273 219 278 250 215 1YO 264 2.33 lY7 16Y 2.55 221 182 l.ii
334 3 13 277 321 239 308 275 236 207 290 258 216 184 279 242 19’) 170
373 349 306 354 263 341 302 259 227 320 283 232 202 309 266 21i 181;
405 370 331 384 283 369 327 280 243 347 305 255 217 335 285 233 l!JY
434 4OY 356 412 302 396 348 298 260 374 323 273 232 359 303 24i i 211
492 465 ‘401 443 391 333 288 424 363 302 257 400 336 27.5 ’ 230
x3 516 440 489 428 365 313 464 396 329 279 441 367 PYY 248
6 16 583 495 550 479 402 347 520 439 364 306 490 408 329 276
*t 10°C. O.!,” at 3OT. (1.09 at IODC. 0.90 at 3”OC, (1.09 at 1wc. 0 90 at 3o*c. (1.00 *t 10°C 0.00 at 300<’
‘b% at 4OT. 0.67 at 5oT): 0.79 *t 40% 0.67 *t 5OOCJJ 0.79 at 4OT. 0.66 *t SO”C3 0.79 at 40012.’ 0.6s 3t soocia
-
Volts Copper Temperature 70%

lY3 185 171 149 129 111 164 142 119’ ::; ‘
21Y 209 lY4 170 145 126 185 161 134 1
2.50 238 220 193 165 141 209 182 1.X? ’ 1’28
288 275 251 219 186 160 238 205 li0 144
316 302 276 240 202 174 262 222 187 157
352 335 304 264 221 l!)O 288 244 203 171
384 32Y 28.5 238 204 311 263 184
413 E;t 352 303 254 216 334 28” ;;; l!J.i
442 393 337 281 238 372 313 236 2 13
487 430 367 304 259 406 340 27i 232
548 481 409 337 284 452 377 304 I 253
(1.10 *t 1ooc 0.89 at 3OT. (1.10 at 1OT. 0.88 *t 3OT. (1.10 at 10°C. 0.89 nt 3ooc.
0.76 at 4O’T : 0.61 at 5O”CJJ 0.75 *t 4OT. 0.58 *t 50%,3 0.74 at 40°C. 0.56 at SOT,3

The followinp symbols are used here to designate conductor types:


S-solid copper. SR-standard round concentric-stranded, CS-compact-sector stranded.
Cllrrcnt rntinse are hnsed on the following conditions:
a. Anibxnt earth temperature=20°C.
1). 60 cycle alternating current.
C. Ratings include dielectric lous. and all induced 3-c losses.
51. One cable per duct, all cables equally loaded and in outside ducts only.
.\lllltlply tabulated currents by these factors when earth temperature is other than 2OT.

Applying these assumptions leads to a set of three simul-


taneous equations relating three currents:
Modified equations:

Simplifying assumptions: It is apparent that E,,=E,,*,


E,,*=.zEb”, and E,, = E,,,; therefore these voltages can be
climinated by subtraction. Also if one ampere positive
Sequence current is assumed to flow through the overall
circuit, then I,,,=l.o-I,,, lh,,=a2-lhS, and IcS,=a-I,,.
88 Electrical Characteristics of Cables Chapter 4

TABLE~GCURRENT CARRYINGCAPACITYFORTHREE- ground return path may be ignored with very small error:
CONDUCTOR OIL-FILLED PAPER INSULATEDCABLES
(amperes per conductor)* 2%~= Z(rc+js,)
where
Rated Line Voltage-Grounded Xcutral
---.__ I = circuit length in miles.
Circular 51ils. 34 500 1 46 000 / 69 000 I-,=&-C. resistance of conductor a’, ohms per mile.
or A.W.G. z, = reactance of conductor a’, to a twelve inch radius,
JIasirnurn Copper Tcmpcritt,urc-Deg. C. ohms per mile.
(B.& S.)
75 7.5 7.5 12
______ =jo.2794 log,,
GMRl of conductor a’, inches
0 168
00 190 i!iO Z,,*, Zb,, .ZI,,*,Z,,, and Z,,, are determined similarly, based
000 210 210 210 on the respective conductor characteristics.
0000 240 240 240 12
250 000 26-5 265 26.5
Z,,,,*= Z.jO.2i94 log,, G, = b(- z,r) where S,,,,, is the axial
300 000 295 295 295 spacing in inches between conductors a’ and a”. The re-
350 000 320 320 320 maining mutual impedance are calculated similarly, using
400 000 342 342 342
the appropriate spacing for each.
500 000 382 382 380
600 000 417 417 412
A series of more complex examples of the above type of
700 000 445 415 440 problem is described by Wagner and Muller.8
750 000 460 460 455 Example I-Type of circuit: A three-phase GO-cycle
cable circuit connected between a sending and a receiving
Deg. C. Corrrction Factor for Various Earth Temps. bus, using two dissimilar three-conductor lead sheathed
10 1.08 1.08 1.08
cables in parallel.
20 1.00 1.00 1.00 Conditions: Each cable contains three conductors that,
30 0.90 0.90 0.90 by the nature of the cable construction, are symmetrically
40 .70 .79 .79 transposed so that the flow of positive- or negative-
sequence currents will cause no zero-sequence voltage
757” losd factor assumed.
Ratings include dielectric loss and extra a-c. losses such as sheath and pror- drops. Therefore, the sequence networks are not interde-
imity loss.
Abovevaluesapply specifically to sector shaped conductors. For round con- pendent and an impedance value of each sequence may be
ductors multiply
*Applies
by 0.99.
to three similar loaded cnbles in a duct bank; for six loaded cables
calculated and used independently.
in B duct bank, multiply above values by 0.88. Problem: To find the zero-sequence impedance of the
entire cable circuit, and to determine how zero-sequence
After substituting the proper self and mutual impedance current divides between cables.
values as defined later, these equations can be solved by the
method of determinants for current distribution, based on abc abc
LENGTH IN MILES
a total of 1.0 ampere positive-sequence current in the cir-
cuit. To obtain actual currents, the distribution factors
must be multiplied by the actual load current in amperes.
Apparent conductor impedances: Using the current-
distribution factors for each conductor to solve the com-
plete voltage drop equations, an (‘apparent” impedance for
each phase of the circuit can be calculated. This apparent ING
impedance is valid only for the particular current division
calculated : I/,/,/////1////,,,,1,/1
EARTH
Apparent impedance of phase a (0)
ACTUAL CIRCUIT

Apparent impedance of phase b

Apparent impedance of phase c

I I m
///N////////////////////////////////7///
EARTH
Supplementary equations: The original assumption of (b)
positive-sequence current flow through the circuit pre- EOUIVALENT CIRCUIT, WITH ALL QUANTITIES
cludes the existence of any net ground return current. This EXPRESSED IN ZERO-SEOUENCE TERMS

assumption simplifies the determination of the various Fig. i7-Actual and equivalent zero-sequence circuit for two
self and mutual impedances, because the effects of a parallel three-conductor lead-sheathed cables (see Example 4).
Chapter 4 Electrical Characteristics of Cables 89

TABLE 17- BJRRENT CARRYING CAPACITY OF THREE-CONDUCTOR GAS-FILLED PAPER-INSULATED CABLES


Number of Equally Loaded Cables
1
ONE THREE SIX NINE TWEI VE
I I I I ’
Per Cent Load Factor

30 I 50 / 73 / 100 1 30 1 50 1 75 1 100 1 30 / 50 1 75 1 100 I 30 1 50 / 75 1 100 I 30 1 50 / 75 j 100

APPROXIMATE AMPERFS PER CONDUCTOR=

Copper Tempernture 81°C

144 129 112 97


162 145 125 109

203 19.5 182 176 196 183 164 141 122


234 224 215 202 225 211 187 162 139
270 256 245 230 258 241 212 182 157
308 395 281 2fil 295 275 241 205 176

341 327 310 200 325 305 276 246 283 215 303 265 224 103
417 397 375 346 397 369 330 293 340 255 366 31'8 267 227
513 487 450 418 483 446 399 350 410 303 444 381 318 269
643 606 x2 514 6O2 551 483 426 502 365 545 464 383 323
(1.0X *t IOT. 0.91 at 3OT. (1.08 at 10°C. 0.91 at 30% 10°C. 0.91 at 30% (I.08 at loOc. O.!Jl at 3O’C.
0.82 8t 40-c. 0.71 .tt 5ww 0.x2 at 40% 0.71 at 5O'C)S 4ov. 0.71 at 5OT)S 0.82 at 4O'C. 0.70 at 51lW~

I
-- per Temperature 77°C

156 150 143 134 149 141 130 117 145 132 117 105 140 125 107 119
177 170 162 152 170 160 145 133 164 149 132 117 159 140 121 133

200 192 183 172 192 182 166 149 186 169 147 132 178 158 136 118 173 149 126
227 220 210 197 221 208 189 170 212 193 168 149 181 134 196 172 144
262 251 238 223 254 238 216 193 242 220 191 169 Ez 206 ::: 1:o 222 195 162
301 289 271 251 291 273 246 219 278 250 215 190 264 233 197 I69 255 221 18’2

334 315 298 277 321 299 270 239 308 275 236 207 290 2.58 216 184 270 242
405 331 384 356 318 283 369 327 280 243 347 305 255 217 335 28.5
492 :z 2% 401 461 427 379 335 443 391 333 288 424 363 30% 257 400 336
616 583 Xl 495 577 528 465 407 550 479 402 347 520 439 364 306 490 408
.90 at 31OT (I.09 at 10% 0.90 at 30%. (1.09 at 1ooc
.67 at 5(,TiS 0.80 at 4OT. 0.67 at 5O"C)3 0.79 at 4OT
'.90 a
.67 a, :5”$gjs (;$I 1oYz
4OT
'LOOB t3 O°C.
.66 &It5 OWJ (;:g
1O'C. 0
40°C. 0

34 300 Volts Copper Temperature 70°C

203 194 166 148 187 169 147 130 180 156 135 116 172 149 125 108
230 220 187 168 212 191 166 147 203 178 152 132 194 169 141 121
262 250 212 191 240 216 1811 166 231 203 173 148 220 191 160 134
302 289 240 215 276 246 213 188 264 230 195 168 250 215 179 131
266 235 304 271 233 206 290 252 212 183 27.5 233 196 16.3
316 280 363 323 277 240 346 300 250 214 327 276 228 193
376 333 439 386 328 285 413 354 295 250 390 329 269 226
457 402 540 469 397 340 505 430 354 298 475 396 320 268
(1.10 at 1ooc. 0.89 *t 30% (1.10 at loOc. 0.89 at 30% (1.10 at 10% 0.89 at 3O’C.
L I 0.76 at 4OT. 0.61 at 5O'C)3
I
0.76 nt 40% 0.60 at 50'03
I 0.76 at 40% 0.60 at 5OT)
(1.10 it 10% 0.83 at 3O’C
I 0.75 at 4ooc. 0.58 at 506~
(1.10 at 10°C. O.RS nt 3oor.
0.74 at 40°C. 0.56 at SOoC)Z

’ ‘l’hc following symbols are used here to designate conductor types:


SR-standard round concentric-stranded. CS-compact-sector stranded.
’ Current ratings are based on the following conditions:
u. Ambient earth temperature- 20°C.
b. 60 cycle alternating current.
c. Rntinw include dielectric loss, and all induced a-c losses.
d. One cable per duct. all cables equally loaded and in outside ducts only.
’ ~lultiply tahnlated currents by these factors when earth temperature is other than 20°C.

Circuit: Refer to Fig. 17. The three actual conductors Modified equation :
in each cable have been reduced to one equivalent con-
cl~~c:t,orin this figure, and all impedances are to be ex- Zo*[(Z,, - Z,,,,~)(Z,~Z,~~
- z3sfs,,)+ (A-,,,- Z,,,,*) (z,*z,~* - z2s’s*,)
I~~WXY~ in zero-sequence terms considering the earth as a + (Z& - Z,,,,,) (Z,~~Z,~,~~ - Z,,,,Z,,,) + (Z,,,,, - Z,,,,)
rcllrrn path for each circuit. (z,~~,~~z,~,~*
- Z,~~,~Z,~~)
+ (Z,,,,, - Z,,,,,,) (Z, ,,,z;,,*,- Z<<,f,Z,,)
(‘omplete voltage drop equations: + (Z,~~,~~- Z,y) (z,~yz,~,~~- Z‘~~,~~Z,~) ] = (Z;, - Z,,,,,)
(Z,~Z,~~ - Ps,,,,) + (Z,,,,, - Z,,,,) (Z,yZ,y - z,yz.-)
E, = Z”,Z, + zo,*z,,,,,+ I,fZ,,,, + Z,,~Z,,,f, + (z,y~ - Z,,,,,) (Z,~~,~Z,~,~~ - Z,,,,,*Z,*)
Eo= Io,%c,i,+I~~,.z~+I;Zs,,+ IgZ<r
0 = Z”,Z,,,,+ I,, z,,y + I,,&*+ z,,*z,*,,, This equation furnishes a solution for Z,,, from which ZCr
0 = zo~z,*,~~+ Zo*~Zc~~,~~
+ I,,&,,*+ I,,~&~ follows directly. To find the zero-sequence impedance of
the entire circuit requires that one of the complete voltage
‘1’1~voltage drop E. can be eliminated by subtraction and drop equations be solved for Ea. Then
11~ sheath currents can be solved in terms of cond&tor
“urrents by using the last two equations only. Also, it is
convenient to assume that the total zero-sequence current
Z,=Eo =~=Eo,
Zo~fZo,, 1.0
ohms.
‘lo\ving into the sending bus is one ampere, which makes
I”,, = 1.o - zo,. Supplementary equations: The equations necessary to
determine each impedance value are shown here: every
‘lfter making these changes, the following single equation impedance must be expressed in zero-sequence terms, with
results: the effect of earth as a return path included.
90 Electrical Characteristics of Cables Chapter 4

TABLE W-CURRENT CARRYING CAPACITY OF SINGLE-CONDUCTOR SOLID PAPER-INSULATED CABLES

I Number of Equally Loaded Cables in Duct Rank

THREE SIX NINE TWELVE


I I
Per Cent Load Factor

30 ) 50 j 75 / 100 1 30 / 50 ( 75 1 100 1 30 1 30 / 75 / 100 1 30 ( 50 j is ( loo

AMPERES PER CONDUCTOR’

7.500 Volts
-
0 1 IF 113 109 103 115 110 103 113 107 90 111 104
13fi
'34
134 149 142 135 132 144 134 149 140 116 147 122
Ii 202 I!)6 1% 175 109 189 175 196 183 I.5 1 I!)2
222
178 1.58
1 234 226 214 201 230 218 201 226 210 172 204 181

0 270 262 245 232 266 251 231 212 261 242 219 196 256 234 208 184
311 300 283 262 30'3 290 270 241 303 278 250 224 2Y5 268 238 208
Oil: 356 344 32-L 300 356 333 275 348 319 285 255 340 308 270 236
0000 412 3Y.5 371 345 408 380 % 314 3YS 364 325 290 3!)0 352 307 269

250 4.x 438 409 370 4‘ln 418 370 344 437 400 356 316 427 386 336 2Y4
300 512 401 4.59 423 499 4B4 420 380 486 442 394 349 474 428 371 325
3.50 561 537 500 460 546 507 4;77 403 532 483 429 379 518 466 403 352
400 fiO7 ,580 R-10 496 393 548 4Y3 445 576 .i22 461 407 560 502 434 378
500 fXl% fX0 611 501 679 626 560 504 659 597 524 459 641 571 490 427

000 772 735 fi79 621 7.57 696 621 557 733 663 579 506 714 632 542 470
700 84G 804 741 677 827 758 674 604 802 721 629 5r8 779 688 587 508
7.50 881 837 771 702 860 78Y 700 627 835 750 651 568 810 714 609 526
800 !I14 86fi 7Y7 725 892 817 725 865 776 674 588 840 740 630 544
1000 1037 980 898 816 1012 922 816 2: '380 874 756 657 950 832 705 606 ;

1250 lli6 1108 1012 914 1039 914 809 1104 981 730 1068 841 673
IROil 1300 12”4 1110 1000 1146 1000 1220 1078 22; 794 1178 1032 ;;; 731
17.X 14’0 1352 1204 1080 1240 1078 E;: 1342 1166 992 851 1280 1103 919 783
2000 134ti I 1442 1300 1162 1343 1162 1019 1442 1260 1068 Y14 138.5 1190 986 839
(1.07 at IO’C ( 2 nt 30' 0.83 (1.07 at 1O’C. fI.0 2 at 3ooc. 0.83 (1.07 at 1ooc. O.!U at 3ooc. 0.83
at iOT. h at 5ov ~(y;~~O at40%0 .73 *t 5owr at 40°C. 0.73 at 50°C)'

15 000 Volts Copper Temperature. 81°C


- - 5

113 110 105 100 112 107 100 110 104 Y6 87 108 101
: 14Y 138 131 147 140 131 1:; 144 136 125 114 142 132 1:: iii
2 195 :z 180 170 193 183 170 157 189 177 lfil 146 18fi 172 154 137
1 226 218 208 195 222 211 195 17Y 218 204 185 167 214 197 175 157
256 248 23-1 220 252 239 220 203 247 230 209 188 242 223 198 177 :
0: 2'37 287 271 254 295 278 253 232 287 265 239 214 283 257 226 202
000 34.4 330 31' "Yo 341 320 293 267 333 306 274 245 327 296 260 230
0000 399 384 361 335 392 367 335 305 383 352 315 280 374 340 2Y8 263 /

250 440 423 396 367 432 404 367 334 422 387 345 306 9 372
300 ‘l!lO 470 439 408 481 449 406 369 470 429 382 338 2; 413 ,"E
350 53!) ;;y 481 444 527 491 443 401 514 468 416 367 501 450 391
400 586 .52" 480 572 530 478 432 556 506 447 395 ,542 485 41Y
600 6ti9 MY 592 s-13 655 fjO5 542 488 636 577 507 445 618 551 474

fiO0 746 710 656 fiO1 727 668 598 537 705 637 557 488 685 608 521 452
700 810 772 712 652 790 726 647 581 766 691 604 528 744 659 564 488
750 840 7Y7 736 674 851 7.53 672 602 795 716 625 54-i 772 684 584 505
800 869 825 762 6Y6 830 780 695 622 823 741 646 565 707 6C4 522
1Oiml WI 939 86-I 785 968 882 782 697 933 832 724 631 i% 7Y4 67.5 581
1230 1130 1067 97d 864 1102 1000 883 784 1063 941 816 706 1026 759 650
1500 12.50 1176 1072 Y66 1220 1105 972 856 1175 1037 892 772 1133 828 707
1750 1368 1282 1162 IO-14 1330 1198 1042 919 1278 1124 Y58 824 1230 886 755
2000 1464 1368 1233 1106 1422 1274 1105 870 1360 1192 1013 869 1308 935 795
(1.08 low c 0.82 (l.OE I &I“4;!;c-o: 2 at 30' 0.82 (1.08 at 10-Z. 2 at 30' 0.82 (1.08 2 *t 30 0.82
WC ‘0. HF5% at at 5ov st 4OT.O at 50-z at 50~

23 000 Volts Copper Temperature. 77°C


- -
2 186 181 172 162 184 175 162 150 180 169 154 140 178 164 147 132
1 214 207 197 186 211 200 185 171 206 193 176 159 203 187 167 150
0 247 239 227 213 244 230 213 196 239 222 197 182 234 2lF 192
283 273 25s 242 278 263 243 221 275 263 225 205 267 245 217
0% 326 314 296 277 320 302 252 315 290 250 233 307 247
0000 376 3fj2 340 317 367 345 2: 288 360 332 297 265 351 % 281
280 412 396 373 346 405 380 346 316 396 365 326 290 386 351 307
463 444 416 386 422 382 349 438 404 360 319 428 389 340
$2 508 488 466 422 :z 461 418 380 481 442 393 347 468 424 369
400 ,548 525 491 454 536 408 451 409 5iil 478 423 373 507 458 398
500 627 600 559 514 615 570 514 464 597 546 480 423 580 521 450
600 605 663 616 566 684 632 568 511 663 603 520 466 645 577 496
700 766 729 675 620 744 680 617 554 725 574 503 703 627 538
750 797 702 643 779 717 641 574 754 :x: 527 732 650 558
800 826 :x: 726 665 808 743 663 595 782 706 f% 759 674 576
1000 946 898 827 752 921 842 747 667 889 797 692 %i 860 759 646
1250 1080 1020 035 848 957 845 751 1014 904 781 676 980 858 725
I.500 1192 1122 1025 925 ?% 1053 1118 $J!
926 818 993 855 1081 940 7Yl
1750 1296 1215 1106 994 1256 1130 991 875 1206 1067 911 E 1162 1007 843 72i
2000 13YO 1302 1180 1058 1352 1213 1053 928 1293 1137' 967 831 1240 1073 893 761
(l.O! 1O’C. 0. 0 at 301 0.80 (LO! 1 at 1O’C. f 0 at 30( 0.80 0.80 D at 30' 0.80
4OT. 0.6 at SOY at 4O'C.O at 5001 at 50°f

Continue
Chapter 4 Electrical Characteristics of Cables 91

TABLE 18-CURRENT CARRYING CAPACITY OF SINGLE-CONDUCTOR SOLID PAPER-INSULATED CABLES


(Continued)

Number of Equally Loaded Cables in Duct Bank

THREE SIX NINE TWELVE


C’IINd;~t~~ I I I
,$& Per Cent Load Factor
OF
MCI1 30 / 50 I 75 1 100 1 30 ( 50 1 75 1 loo 1 30 / 50 ( 75 / 100 I 30 / 50 1 75 / loo

AMPERES PER CONDUCTOR’

34 500 Volts Copper Temperature. 70°C

227 221 209 197 225 213 197 182 220 205 187 169 215 I!)!) 177 158
260 251 239 224 255 242 224 205 249 234 211 1YO 24.5 226 200 170
239 290 273 256 295 278 256 235 288 268 242 217 282 259 230 204
341 330 312 201 336 317 201 267 328 304 274 246 321 2Y3 259 230
380 367 345 322 374 352 321 294 364 337 303 270 356 324 286 253
4”2 408 382 355 416 390 356 324 405 374 334 298 3!15 359 315 278
464 446 410 389 4.5.5 426 388 353 443 408 364 324 432 392 343 302
502 484 451 419 491 460 417 379 478 440 390 347 466 421 3G8 323
5i5 551 514 476 562 524 474 429 547 500 442 302 532 479 416 364
644 616 573 528 629 584 526 475 610 556 491 433 593 5.32 4.59 401
710 673 626 577 690 639 574 517 669 608 535 470 649 580 500 435
736 702 651 598 718 664 595 535 696 631 554 486 675 602 518 450
765 730 676 620 747 690 617 555 723 654 574 503 624 465
875 832 766 701 852 783 698 624 823 741 646 564 % 706 iii 520
994 941 864 786 967 882 782 696 930 833 722 628 898 790 670 577
1098 1036 949 859 1068 972 856 760 1025 914 788 682 988 865 730 626
1192 1123 1023 925 1156 1048 919 814 1109 984 845 730 1066 92’3 780 668
1275 1197 1088 981 1234 1115 975 860 1182 1045 893 770 1135 985 824 704
1418 1324 1186 1072 1367 1225 1064 936 1305 1144 973 834 1248 1075 893 760
(1.10 *t 1OT. 1 *t 300 0.76 (1.X 10°C. / 9 at 300 0.76 9 at 30’ 0.78
at 40%. 0 at 5OOC 4ooc. 0 I at 509c at 509(

46 000 Volts Copper Tempernture. 65°C

279 270 256 240 274 259 239 221 268 249 226 204 262 241 214 191
322 312 294 276 317 299 274 251 309 287 259 232 302 276 244 217
352 340 321 346 326 299 274 336 313 282 252 329 301 266 236
394 380 358 E 385 364 332 304 377 349 313 280 367 335 295 260
433 417 392 365 425 398 364 331 413 341 304 403 366 321 283
469 451 423 393 391 356 446 :7: 367 326 433 394 344 307
534 512 482 444 459
522 % 441 400 506 464 412 365 4Y2 444 386 339
602 577 538 496 589 546 494 447 570 520 460 406 553 497 430 377
663 633 589 542 645 598 538 486 626 569 502 441 605 542 468 408
689 658 611 561 672 622 559 504 650 590 520 457 629 562 485 422
717 683 638 583 698 645 578 522 674 612 538 472 652 ,582 501 436
816 776 718 657 794 731 653 585 766 691 604 528 740 657 562 487
927 879 810 738 732 654 865 777 675 589 834 736 626 541
IO20 968 887 805 900
992 %i 799 703 951 850 73.5 638 914 802 679 585
1110 1047 0.59 867 1074 976 762 1028 915 788 682 987 862 726 623
1184 1115 1016 918 1144 1035 % 805 1094 970 833 718 1048 913 766 6.56
1314 1232 1115 1002 1265 1138 994 875 1205 1062 905 778 1151 996 830 708
i at 300 0.72 i at 300 0.72 (1.1” at 10-2. 0.87 at 30°C. 0.70
at 5ooc at 50’< at 40% 0.51 at 5O’C)2

69 000 Volts Copper Temperature, 60°C

- -
395 382
428
489
413
470
%
441
387
418
477
;:::
446
333
358
406
305
328
370
%2
461
348
375
425
312
335
379
279
300
337
365
394
447
332
358
405
293
31.5
3.54
259
278
312
54 5 524 490 532 496 450 409 513 471 419 371 497 448 391 343
599 573 536 495 582 543 490 444 561 514 45.5 403 542 489 425 372
623 597 556 514 605 562 508 460 583 417 563 506 439
644 617 575 531 626 582 525 475 603 533
554 z: 430 582 523 453 iii
736 702 652 599 713 660 592 533 683 622 547 481 660 589 508 442
832 792 734 672 742 664 595 772 698 610 535 741 489
018 872 804 733 814 724 647 848 763 664 580 812 529
984 942 865 788 876 776 692 913 818 711 618 873 563
1066 1008 924 840 931 822 732 972 868 750 651 927 592
1163 1096 1001 903 1013 892 791 1060 942 811 700 1007 635
(1.X i nt IOT. 0.85 nt 30% 0.67 I at 1O’C. ( 5 at 30’ 0.66 (1.13 1O’C. 0.84 at 30°( :. ,I.65 (1.14 at IO’C. 0.84 at 30% 0.64
*t 4ovz. 0.42 at 5O’C)~ *t ‘IOT. 0. at 5ooc 4O’C. 0.36 at 5O’C )* *t 4ooc. 0.32 at 5O”C)Z
92 Electrical Characteristics of Cables Chapter 4

%,,= l~r,+r,+.~(x,+x,-2xd)] ohms, where I= circuit TABLE 20-SUGGESTED WITHSTAND IMPULSE VOLTAGES
I
FOR CABLES WITH METALLIC COVERING*
length in-miles, and the other terms are defined !

I r:
1
as for Eq. (19). Solid-Paper Oil-Filled Paper
Z,,, is defined similarly. Basic Insulation Insulation
Insulation Impulse
Z,,= Z[:3r,+r,+j(3z,+xe)] ohms, where the terms are Class Insulation xulation ‘ithstand lsulation ?thstand
defined as for Eq. (23). kv Level for ‘hicknesz Voltage hicknrss Voltage
Z,,, is determined similarly. Equipment mils kv mils kv 1
.- j
Z,,,,= l[r,+j(3~~+~,)] ohms, where the terms are 1.2 30 i8 94 .
defined as for Eq. (26). 2.5 45 78 04 .
5.0 60 04 113 . 1
Z,,,,,, is determined similarly.
8.7 75 141 16D .
Z,,,,, = Z,,,,, = Z,*,,t = Z[r,+j(x,- 3xJ] ohms, where 15 110 203 244 110 132 1
23 150 266 310 145 174
Xd= 0.2794 log,, 2, using for S the center-to-center 34.5 200 375 450 190 228 i
46 250 46'3 563 225 270 ’
spacing between cables,3 in inches. 350 688 825 315 378
69
A more general version of the above type of problem, 115 550 480 575
covering those cases where the cables are not necessarily 138 650 560 672 j
bussed together, is described by Cheek.” 161 750 648 780
230 1050 925 1110 1
Example S-The use of complex GMR’s and GMD’s -
will very often reduce a complicated problem to workable *Based on recommendations by Halperin and Shanklin.le 1
terms. The use and significance2 of these factors should be
studied thoroughly before attempting a solution by this Circuit: Four paralleled cables similar to the three-
method (see Chap. 3). conductor belted cable described in Example 1, and ar-’
ranged in a duct bank as illustrated in Fig. 18.
TABLE 19%CumENT CARRYING CAPACITY FOR SINGLE- Problem: To find the overall zero-sequence impedance’
CONDUCTOR OIL-FILLED PAPER-INSULATED CABLES
of the circuit, with sheaths and ground in parallel, or with!
(amperes per conductor) *
return current only in the sheaths.
Rated Line Voltage-Grounded Neutral GMR of three conductors,
- GMRs,= 0.338 inches (from example 1).
Circular A\Iils. 34500 ] 46000 1 69000 1 115000 1 138000
-
or A.W.G.
LIaximum Copper Temperature-Deg. C. p-5s”~55”~5.---i
(B.& S.) - -
75 75 75 70 70
_-
0 256 . .... .
00 287 286 282
000 320 310 300 .. .
0000 378 367 367 347 335
250000 405 395 390 365 352 (a) Cable configuration.
300000 450 440 430 402 392
350000 492 482 470 438 427
400000 528 512 502 470 460
592 568 522 r OF ONE CONDUCTOR
500000 592 530
ND. OF CIRCUITS
600000 655 650 628 585 578
700000 712 710 688 635 630 CONDUCTOR BRANCH
750000 742 740 715 667 658
800000 767 i65 740 685 680
1 000 000 872 870 845 775 762
1 250 000 990 982 955 875 852
1 500 000 1 082 1 075 1043 957 935
1 750 000 1 165 1 162 1 125 1030 1002
2000000 1 240 1 240 1 200 1 100 1070
- 1 -GROUND1 1
Deg. C. Correction Factor for Various Earth Temps. BRANCH 1 J nn
.- I
10 1.08 1.08 1.08 1.08 1.09
20 1.00 1.oo 1 .oo 1.oo 1.00
30 0.90 0.90 0.90 0.89 0.89 0.600
40 .79 .79 .79 .77 .77 (r 0 tr.)(r
101 -r.)(NO.OF SHEATHS)
T
75% load factor assumed.
Ratings include dielectric loss and skin effect. (b) General equivalent circuit.
Ratings based on open-circuited sheath operation; i.e.--no sheath loss con-
sidered. Fig. 18-Four three-conductor cables in a duct bank
*Applies to three similar loaded cables in a duct bank; for six loaded cablea in
a duct bank, multiply above values by 0.91. Example 5).
Electrical Characteristics of Cables 93
Chapter 4

G>~R of the four conductor groups, I” SPACING


GMRI,=‘$(0.338)4(5)6(10)4(15)2=3.4’i9 inches. I
-
EC1uivaIent spacing of three conductors to their sheath, I I / I/-
s,,q =0.812 inches.

(;>ID among the conductors and the sheaths.--------,


/
- A 29,n :,,L,”
~>lII(~,-as) = 1~(0.812)4(5)“(10)4(15)2 -T.r)r)v ,~,~,Lcz,. 9k +3”SPAClNG / 1.0 SO. IN. CABLE,
I OUTER CONDUCTORS
From Fig. 18(b), resistance of the sheath branch, o5: 92
i 0.2 SO. IN. CABLE
f: MIDDLE CONDUCTORS
0.600
=0.848 ohms per mile. p0 90
(l.y7-2\ in i n4114‘1 5% ,X/6”SPAC,NG / / 1 (
,‘dv,\v.-““I\-,
ti,68’ I” ’ ’ ’ ’ ’ ’ ’
9

Also fronl- ~16;.
v:- LU\LIJ,
lQfK\ AAL.
%pedance of the ground-branch :0’2345678
IO
DISTANCE OF CABLES FROM STEEL PLATE-INCHES
2800X 12
= 0.286+jO.838 log Fig. 19-Effect of steel plates on current-carrying capacity of
:l” 4.330 single-conductor cables. Three phase system; flat config-
=0.286+j3.260 ohms per mile. uration.

0
0 100 200 300 400 500 600
INSULATION THICKNESS, MILS

Fig. 20-Summary of some impulse tests on paper-insulated cables


(based on information piesented by Foust and Scottl3).
Kay:
8 An unpublished test, solid insulation (The Okonite
’ Davis and Eddy,12 1 x ‘0 negative wave, high density Company).
Paper, solid insulation (Simplex Wire and Cable Co-). 9 Foust and Scott, 1.5 x 40 positive wave, regular density
1 “e’d and L e ’ c h senring,lT negative wave, solid insulation. paper, solid insulation.
3 “e’d and Leichsenring, positive and negative waves, Oil- 10 Foust and Scott, combination regular and medium den-
fbd ‘nsu’at’on. sity paper, solid insulation.
’ “e’d and Leichsenring positive wave solid insulation. 11 Foust and Scott, high density paper, solid insulation.
s *n unpublished test, regular density’paper, oil-filled in- 12 Foust and Scott, medium density paper, solid insulation.
r”‘at’on (General Cable Corporation). 13 Foust and Scott, 1.5 x 40 positive wave, combination reg-
6 Faust and Scott, average of five tests 1 x 10 positive wave ular and medium density paper, solid insulation.
regular density paper, solid insulatibn (General Elect& 14 Foust and Scott, 0.5 x 40 positive wave, regular density
Co.). paper, solid insulation.
’ An unpublished test high density paper, oil-filled insu- 15 Foust and Scott, 0.5 x 5 positive wave, regular density
lation (Genera’ Cabli Corporation). paper, solid insulation.
94 Electrical Characteristics of Cables

The zero-sequence impedance with sheath and ground 6. A-C Resistance of Large Size Conductors in Steel Pipe or Con.
in parallel, duit, by R. J. Wiseman, -4.Z.E.E. Transactions, Vol. 67, 1943,
pp. 1745-1758.
0.848(0.28G+j3.260) +. 247+jo,oigi 7. Reactance of Large Cables in Steel Pipe or Conduit by W. A.
z”=0.848+(0.286+.j3.260) ’ Del Mar, A.I.E.E. Transactions, Vol. 67, 1948, pp. 1409-1412.
= 1.022+jO.275 ohms per phase per mile. 8. Unbalanced Currents in Cable Groups, by C. F. Wagner and
H. N. Muller, Jr., The Electric Journul, Vol. 35, October 1938,
The absolute value of this impedance is 1.06 ohms per p. 390.
phase per mile. 9. Zero-Sequcncc Impedances of Parallel Three-Conductor Cables,
The zero-sequence impedance considering all return by It. C. Cheek, Electric Light and Porter, October 1948, p. 74.
current in the sheath and none in the ground, 10. The Temperature Rise of Cables in a Duct Bank, by J. H.
Neher, A.I.E.E. Technical Paper 49-134, April 1949.
2, = (0.247fj0.0797) f0.848 11. Determination of Cable Temperature by &leans of Reduced
= 1.095Sj0.0797 ohms per phase per mile. Scale Models, by Andrew Ccmant and Joseph Stichcr, A.I.E.E.
The absolute value of this impedance is 1.1 ohms per phase Transactions, Vol. 65, 1946, pp. 47.5482.
12. Impulse Strength of Cable Insulation by E. W
per mile, or substantially the same as with the sheath and
W. N. Eddy, A.Z.E.E. Trunsactions, Vol. 59, July
ground in parallel. In this case the effect of high sheath 13. Some Impulse-Voltage Breakdown Tests on Oil-T
resistance is minimized by the fact that four sheaths are Insulated Cables, by C. M. Foust and J. A. SC
paralleled. Transacfions, Vol. 59, July 1940, p. 389.
14. Impedance of Three-Phase Secondary Alains in Nonmetallic
Iron Conduits, by L. Brieger, E.E.I. Bulletin, February 1
V. IMPULSE STRENGTH OF CABLES 15. Specifications for Impregnated Paper-Insulated Lead-Cover
Power-transmission circuits are often made up of cables Cable: “Solid” Type (7th and 8th editions), “Oil-Filled” Ty
and overhead-line sections connected in series, and this (4th edition), “Low-Pressure Gas-Filled” Type (1st edition)
prepared by Association of Edison Illuminating Companies.
construction may impose lightning-surge voltages on the
16. Current Carrying Capacity of Impregnated Paper, Rubb
cable insulation. Even when circuits are totally under- Varnished Cambric Insulated Cables (1st edition), camp
ground, it is possible that cable insulation will be stressed The Insulated Power Cable Engineers Association, Pub1
by transient overvoltages caused by switching operations. No. P-29-226.
For these reasons the impulse strength of cable insulation 17. The Behavior of High Tension Cable Installations Under
is information of some value for predicting cable perform- Effect of Voltage Impulses, by C. H. Held and H. W. Lei
ance in an actual installation. senring. Paper No. 207, C.I.G.R.E., Paris, June-July 1939.
No industry-wide standards have been established for 18. Impulse Strength of Insulated-Power-Cable Circuits, by Herm
cable impulse strength. Test data from various sources is Halperin and G. B. Shanklin, A.Z.E.E. Transactions, Vol. 63
available,12*13and some of these results for paper-insulated 1944, p. 1190.
Books
cables are shown in Fig. 20. Several variables are inherent
40. Electric Cables, by W. A. Del Mar, McGraw-Hill Book Corn
in the curves, so that the spread of the test points is wider pany, 1924.
than might be obtained with uniformly controlled test 41. Electrical Characteristics of Transmission Circuits, by W
conditions. The factors not yet completely investigated Nesbit, Westinghouse Technical Night School Press, East
include the effect of normal insulation aging, the relation burgh, Pa., 3rd edition, 1926.
between actual voltage gradient within the insulation and 42. Underground Systems Reference Book, NELA Publication N
the average gradient, wave shape and polarity of the test 050, 1931.
impulse voltage, and grade or compounding of insulation. 43. Symmetrical Compon,ents, by C. F. Wagner and R. D. Ev
Using 1200 volts per mil average stress as a safe ivith- McGraw-Hill Book Company, 1933.
stand impulse strength for paper-insulated cables, as sug- 44. Impregnated Paper Znsululion, by J. B. Whitehead, John Wile
& Sons, 1935.
gested by Halperin and Shanklin,18 the withstand voltages
45. Electric Power Transmission and Distribution, by L. F. W
for representative cables may be listed as in Table 20. ruff, John Wiley & Sons, 1938.
46. The Principles of Electric Power Transmission, by H. Waddic
REFERENCES Chapman & Hall, 1939.
47. The Transmission of Electric Power, Vols. I and II, by W.
1. Calculation of the Electrical Problems of Underground Cables, Lewis, Illinois Institute of Technology, 1948.
by D. M. Simmons, The Electric Journal, Vol. 29, May to Impedance and Capacitance
November, 1932. (The first article in this series contains a com- 60. Formulas and Tables for the Calculation of Mutual and Se
prehensive bibliography for 1932 and before.) Inductance, Messrs. Rosa and Glover, Bureau of Standar
2. Symmetrical Components by C. F. Wagner and R. D. Evans Scientific Papers, No. S169, 1916; also So. S320, 1918.
(a book), McGraw-Hill Book Company, 1933. 61. Proximity Effect in Cable Sheaths, Dwight, A.Z.E.E. Tran
3. The Transmission of Electric Power, Vols. I and II, by W. A. tions, September, 1931, p. 993.
Lewis (a book), Illinois Inst.itute of Technology, 1948. 62. Calculation of the Electrical Problems of Underground Cab1
4. Current-Rating and Impedance of Cables in Buildings and D. M. Simmons, The Electric Journal, Vol. 29, May,
Ships, by H. C. Booth, E. E. Hutchings, and S. Whitehead, July, October and November 1932, pp. 237, 283, 337,
1.E.E. Journul, Vol. 83, October 1938, p. 497. and 527.
5. Problems in the Measurement of A-C Resistance and Reactance 63. Calculations of Inductance and Current Distribution in
of Large Conductors, by E. E-1.Salter, A.I.E.E. Transactions, Voltage Connections to Electric Furnaces, by C. C. Le
Vol. 67, 1948, pp. 1390-1396, ,A.Z.E.E. Transactions, Vol. 51, December 1932, p. 903.
Chapter 4 Electrical Characteristics of Cables

Resistance and Reactance of Three-Conductor Cables, by E. H. 113. The Temperature Rise of Buried Cables and Pipes, by J. H.
64.
Salter, G. B. Shanklin, and R. #J. Wiseman, A.I.E.E. Transuc- Neher, A.I.E.E. Transuc~ions, Vol. 68, Part I, 1949, p. 9.
liens, Vol. 53, December 1934, p. 1581. 114. The Temperature Rise of Cables in a Duct Bank, by J. H.
impedance Measurements on Underground Cables, by R. I. Neher, A.I.E.E. Transactions, Vol. 68, Part I, 1949, p. 541.
65.
\V&b and 0. W. Manz, Jr., A.I.E.E. Transactions, Vol. 55, April 115. Transient Temperature Phenomena of 3-Conductor Cables, by
1936, p. 359. F. 0. Wollaston, A.I.E.E. Transuclions, Vol. 68, Part II, 1949, p.
lrnpcd:mce of Three-Phase Secondary Mains in Nonmetallic and 1284.
66.
iron Conduits, by L. Brieger, E.E.I. Bulletin, February 1938. 116. The Thermal Resistance Between Cables and a Surrounding
r;nbalanced Currents in Cable Groups, by C. F. Wagner and H. Pipe or Duct Wall, by F. I-I. Buller and J. H. Neher, A.I.E.E.
67. Y --

$. Muller, Jr., The Electric Journal, Vol. 35, October 1938, p. 390. Trunsuclions, Vol. 69, Part I, 1950, p. 342.
68. Current-Rating and Impedance of Cables in Buildings and 117. Heat Transfer Study on Power Cable Ducts and Duct Assem-
Ships, by H. C. Booth, E. E. Hutchings, and S. Whitehead, blies, by P. Greebler and G. F. Barnett, A.I.E.E. Transactions,
[,fl.fl. Journal, Vol. 83, October 1938, p. 497. Vol. 69, Part I, 1950, p. 357.
.-
Ijo. _t+oblcms in the Measurement of A-C Resistance and Reactance 1nsululion
,~f Large Conductors, by E. H. Salter, A.I.E.E. Trunsuctions, 140. The Behavior of High Tension Cable Installations Under the
VI,]. 67, 1948, p. 1390. Effect of Voltage Impulses, by C. H. Held and H. W. Leichsen-
70. l(,~:Lc~t,:mceof Large Cables in Steel Pipe or Conduit,, by W. A. ring. Paper No. 207, C.I.G.R.E. Paris, June-July, 1939.
1),~1hlar, A.I.E.E. Transactions, Vol. 67, 1948, p. 1409. 141. Impulse Strength of Cable Insulation by E. JV. Davis and W.
71. ,\-C R&stance of Large Size Conductors in Steel Pipe or Con- N. Eddy, A.I.E.E. Transuclions, Vol. 59, July 1940, p. 394.
,lriit, by R. J. Wiseman, A.I.E.E. Transactions, Vol. 67, 1948, 142. Some Impulse-Voltage Breakdown Tests on Oil-Treated Paper-
,,. 17.15. Insulated Cables, by C. M. Foust and J. A. Scott, A.I.E.E.
72. %cro-Sequence Impedances of Parallel Three-Conductor Cables, Trunsuctions, Vol. 59, July 1940, p. 389.
by R. C. Cheek, Electric Light and Power, October 1948, p. 74. 143. Impulse Strength of Insulated-Power-Cable Circuits, by Her-
73. A-C Resistance of Segmental Cables in Steel Pipe, by L. Meyer- man Halperin and G. B. Shanklin, A.I.E.E. Transactions, Vol.
hoIT and G. S. Eager, Jr., A.I.E.E. Trunsuclions, Vol. 68, 1949, 63, 1944, p. 1190.
[,. Ylti. 144. Power Factor Measurements on Poly-phase and Multiconduc-
71. ‘I’ranspositions and the Calculation of Inductance from Geo- tor Cable Using Single-Phase Bridges, by E. W. Greenfield,
III(~Iric: Mean Distances, by W. B. Boast, A.I.E.E. Trunsuctions, A.I.E.E. Transactions, Vol. 69, Part II, 1950, p. 680.
Vol. till, Part II, 1950, p. 1531. General
Characteristics of Oil-filled Cable, Shanklin and Buller,
T,~in&ratures in Electric Power Cables Under Variable Load- A.I.E.E. Trunsaclions, December, 1931, p. 1411.
ing, by E. A. Church, A.I.E.E. Transactions, September, 1931, 151. Oil-filled Cable and Accessories, Atkinson and Simmons,
p. !182. A.I.E.E. Transactions, December, 1931, p. 1421.
Calculation of the Electrical Problems of Underground Cables, 152. 120 kv Compression-Type Cable, by I. T. Faucett, L. I.
I)Y I). M. Simmons. The Electric Journal, Vol. 29, August Komives, H. W. Collins, and R. W. Atkinson, A. I.E.E. Trans-
antI September 1932, pp. 395 and 423. actions, Vol. 61, September 1942, p. 652.
Thermal Transients and Oil Demands in Cables, by K. W. 153. 120 kv High-Pressure Gas-Filled Cable, by I. T. Faucett, L.
Miller and F. 0. Wollaston, A.I.E.E. Transactions, March I. Komives, H. W. Collins, and R. W. Atkinson, A.I.E.E.
I !U:l, Vol. 52, p. 98. Transactions, Vol. 61, September 1942, p. 658.
t’:conomicnl Loading of Underground Cables, by E. A. Church, 154. Low-, Medium-, and High-Pressure Gas-Filled Cable, by G. B.
:I.I.E.E. Transactions, Vol. 54, November 1935, p. 1166. Shanklin, A.I.E.E. Transactions, Vol. 61, October 1942, p. 719.
Current-Rating and Impedance of Cables in Buildings and 155. Cable for Power Transmission and Distribution, by C. T.
Ships, by H. C. Booth, E. E. Hutchings, and S. Whitehead, Hatcher, Electric Light and Power, September 1946, p. 38, and
f.&.E. Journal, Vol. 83, October 1938, p. 497. October 1946, p. 72.
M:rsimum Safe Operating Temperatures for 15 kv Paper-In- 156. High-Pressure, Gas-filled Cable Impregnated with Extra-High
sulated Cables, by C. W. Franklin and E. R. Thomas, A.I E.E. Viscosity Oil, by Joseph Sticher, G. H. Doan, R. W. Atkinson, and
Tmnsaclions, October 1939, Vol. 58, p. 556. Louis Meyerhoff, A.I.E.E. Transactions, Vol. 68, Part I, 1949,
l.o:rtl Rnt.ings of Cable, by Herman Halperin, A.I.E.E. TRZ~S- p. 336.
cc/ions, Vol. 58, October 1939, p. 535. 157. Specifications for Wire and Cable with Rubber and Rubber-
l~:~~ouomicalLoading of High-Voltage Cables Installed in Un- Like Insulations, 1st edition, 1946, prepared by Insulated
~hmund Subway Systems, by E. R. Thomas, A.I.E.E. Power Cable Engineers Association.
‘I”‘~mclions, 1939, Vol. 58, p. 611. 158. Specifications for Varnished Cambric Insulated Cable, 5th
l~o:rd Ratings of Cable-II, by Herman Halperin, A.I.E.E. edition, 1946, prepared by Insulated Power Cable Engineers
‘I”‘~~~~~~ctions,Vol. 61, p 931, 1942. Association.
(:riidc for Wartime Conductor Temperatures for Power Cable 159. Specifications for Impregnated Paper-Insulated Lead-Covered
in Service (committee report), A.I.E E. Transactions, Vol. 63, Cable: “Solid” Type (7th and 8th editions, 1947), “Oil-Filled”
September 1943, p. 606. Type (4th edition, 1947), “Low-Pressure Gas-Filled” Type
Current Carrying Capacity of Impregnated Paper, Rubber, (1st edition, 1948), prepared by Association of Edison Illumi-
am1 . Varnished Cambric Insulated Cables (1st edition), com- nating Companies.
ml~ti by The Insulated Power Cable Engineers Association, Biblioaruvhies
l’ublication No. P-29-226, 1943. 180. Calculation of the Electrical Problems of Underground Cables,
Determination of Cable Temperature by Means of Reduced by D. M. Simmons, The Electric Journal, Vol. 29, May 1932,
Scale Models, by Andrew Gemant and Joseph Sticher, A.I.E.E. p. 237.
Tr~~wctions, Vol. 65, 1946, p. 475. 181. Underground Systems Reference Book, NELA Publication
Thermal Characteristics of a 120 kv High-Pressure, Gas-Filled No. 050, 1931, Appendix II.
Cable Installation, by W. D. Sanderson, Joseph Sticher, and 182. Rating of Cables in Relation to Voltage, (Bibliography on
M. H. McGrath, A.I.E.E. Transactions, Vol. 67, Part I, 1948, Dielectrics) by D. M. Simmons, A.I.E.E. Transactims, Vol.
P. 487. 41, 1922, p. 601.
CHAPTER 5

POWER TRANSFORMERS AND REACTORS


Original Authors: Revised by:
J. E. Hobson and R. L. Witzke R. L. Witzke and J. S. William1

I
N this chapter are included the fundamental theory, and the rms value of this voltage is
operating practices, pertinent application data, and
some of the physical characteristics of power trans- E =%y&n,x 1OV volts
p 42
formers and reactors. No attempt is made to give a com-
= 4.44fnlAB,,,,X 1O-8 volts (3
plete exposition of the material. It is expected that the
listed references will be consulted for a more detailed con- where, f =frequency in cycles per second. -
sideration of each section. Although the fundamental the- n =cross sectional area of magnetic circuit il
ory presented here holds also for distribution transformers, square centimeters (assumed uniform).
the standards of operation and present practices regarding B nlllx=maximum flux density in the core in line
distribution transformer application are not included in per square centimeter.
this chapter. Grounding transformers are included since Similarly, the rms voltage induced in the 5’ winding by th
they are ordinarily associated with power systems. flux is given by
E, = 4.44fnqAB,,, X 10-a volts. (4
I. THEORY Thus it is evident that a sinusoidal flux linking a coil in
duces in it a voltage which is also sinusoidal and whit:
1. Fundamental Cowiderations lags the flux by 90 electrical degrees.
Before going into the various problems involved in the To apply the above principle to the operation of a tram
application of transformers and the methods used in ana- former, refer again to Fig. 1 and consider the S winding a
lyzing their effect on system operation, it is well to review open and let a sinusoidal voltage be impressed on the j
briefly the fundamental theory of transformer action. winding. The current, I,, that flows in the P windin
Two windings on a common magnetic core are pictured under this condition (I,=O) is called the exciting curren
in Fig. 1. Let the number of turns in the P winding be nl, and sets up an alternating flux about that winding, whit
consists of two parts: a mutual flux whose path is who11
in the core and which, therefore, links both windings, an
a leakage flux whose path is partly in air and which link
only the P winding. The ratio of the leakage flux to th
mutual flux depends on the relative reluctance of thei
respective paths, which in turn is a function of the saturr
E ES tion of the core and the magnitude of the current. It :
convenient to consider the voltage induced in the P wine
ing, by the flux linking it, as made up of two component!
one produced by the linkages resulting from the mutuj
flux and the other produced by leakage flux. In the 01
dinary commercial transformer the leakage flux is sma
Fig. l-Two-winding transformer. and can be neglected for the present. Then, if the small i.
drop in the winding is also ignored, the voltage induced i
and the number of turns in the X winding be Q. Assume the P winding by the mutual flux can, with close approl
that there is a flux in the core which links both windings imation, be set equal and opposite to the impressed voltagl
and is a sinusoidal function of time. If, as assumed, the latter is sinusoidal, then the mutut
+= f&3X sin wt flux must also be sinusoidal and the induced voltage
(1)
given by Eq. (3),
Then the voltage induced in the P winding at any instant
by the flux is E, = 4.44fnlAB,,X 1O-8 volts.

eP= -721*X 10e8 volts (2) By hypothesis, all of the mutual flux which has jut
dt been considered in connection with the P winding mu!
= -nlw@,, cos wtX 1O-8 volts also link the S winding. Hence, a voltage is induced in tf
where w=27rf S winding, which is expressed by Eq. (4),
hence, ep= - 2rfnl&, cos wt X IO-* volts E, = 4.44fnzAB,,x 1O-8 volts.
96
chapter 5 Power Transformers and Reactors 97

If the circuit connected to the S winding is closed, a stated, the total flux linking either winding can be divided
current, I,, flows and, in the manner already described in into two components, a leakage flux whose path is wholly
connection with the P winding, sets up a mutual and leak- or partly in air and a mutual flus most of which lies in the
:,gc flux about the winding. The direction of this current iron core. Furthermore, the mutual coupling between cir-
is such that the mutual flux produced by it opposes that cuits must have an energy component to furnish the iron
,,r&ced by the P winding and it, therefore, tends to loss in the magnetic circuit. With the above considerations
Il,~llify the flux in the core. Consideration of the energies in mind the equivalent circuit representing the two coupled
involved shows that an additional component, I,‘, must be windings in Fig. 1 can be derived2.
L,ddcdto the current in the P winding before the S winding The equivalent circuit is shown in Fig. 2(a), where the
is closed, such that the magnetomotive force acting on mathematical artifice of an idea1 transformer2 is introduced
the magnetic circuit remains unchanged after 5 is closed. to preserve actual voltage and current relationships at the
fn other words, the resultant flux in the core produced by terminals, and to insulate the two windings. The ideal
t,hc combined action of the currents flowing in the P and 8 transformer is defined as having no losses, no impedance
\vintlings must equal the mutual flux present when the S drop, and requiring no exciting current. The ratio of
\\,intiing is open. Therefore, transformation for the ideal transformer is N, where
nJ,=nJ, -nJa, (5) N,? . (91
rcmcmbering that the flux caused by I. is opposite that
co:mscdby I, which accounts for the negative sign. In
:L w&designed transformer, the exciting current is small
in comparison to the normal load current I’,, hence me can
:Lssumethe total current, I,, in the P winding to be equal
to l’r, and obtain

‘I’hc leakage flux produced by I, induces a voltage in the


S winding opposing that produced by the mutual flux.
IIowever, it is small as in the case of the P winding, and,
if neglected along with the resistance drop, permits writing
~.hcrelation between the P and S voltages as
(b)

‘I’hc seven equations developed above summarize the


general relationships between the flux, the induced volt-
:~gcs,and the primary and secondary voltages and currents
involved in transformer action. However, they are based
on a number of assumptions that, in analyzing the opera-
I.ion of the transformer or of the system to which it is con-
nccted, cannot always be made. A more rigorous develop-
mont that takes into consideration the effects of exciting
“urrent, losses, and leakage fluxes is therefore required.
Referring again to Fig. 1, and considering instantaneous
currents and voltages, the classical equations for the
(!()hpled circuits are
IppLu 1s
00 oa’

EPX E,%
di di I I
e.=M-p-~sis-~s-’
dt dt (e)
\vhcre Rp and Rs are, respectively, the effective resistances Fig. 2-Equivalent circuits for two-winding transformer.
of the primary and secondary windings: Lp and LS are the (a) Equivalent circuit in ohms, with magnetizing current con-
“(‘h-inductances of the primary and secondary windings: sidered.
:‘nd 111is the mutual inductance between the two windings. (b) Equivalent circuit in ohms, with all impedances on the primary
voltage base.
‘rl~e positive direction of current flow in the two windings
(c) Equivalent circuit in ohms, with the magnetizing branch
is taken such that the fluxes set up by the two currents neglected.
‘vilf be in opposition. (d) Equivalent circuit in ohms, with the leakage impedance re-
The coefficients Lp, Ls, and M are not constant but vary ferred to the secondary voltage base.
with the saturation of the magnetic circuit’. As previously (e) Equivalent circuit in percent.
98 Power Transformers and Reactors Chapter 5

The shunt resistance branch in 2~ represents the iron


losses and the shunt reactive branch
path for the no load, or exciting current, of the transformer.
The variation in M during the cycle of instantaneous cur-
rent and voltage variation is ignored, and a mean value is
used. The branches, Zr = Rpfjw and, 2s = Rs

+j are essentially constant, regardless of in-


stantaneous current variations, since their corresponding
leakage fluxes lie mostly in air. Zp and 2s are components
of the leakage impedance between the P and S windings
such that
1 LP
zps = z-p+--zs * (10)
N2 (b)

Zps is defined as the leakage impedance between the P Fig. 3-Equivalent circuit and corresponding vector diagram
for two-winding transformer.
and S windings, as measured in ohms on the P winding
with the S winding short-circuited. Actually it is not
possible3 to segregate Zrs into two parts, Zr associated and currents are identified there. The primary and second-
with the P winding and Zs associated with the S winding ary leakage impedances Zp and Zs are shown separately,
by any method of test; for example, Zr, the portion of and the primary and secondary resistances Rp and RS are
Zrs associated with the primary winding, varies with ex- also indicated. Ih and I, represent the core-loss component
citation and load conditions. It is customary, in many and the magnetizing component respectively of the exciting
calculations involving the equivalent circuit, to make current I,. The vector diagram in Fig. 3(b) is drawn for
a 1 :l ratio of transformation and for a load of lagging power
zp=izg=4zp3 * (11) factor. The power-factor angles at the P winding terminals
and the S winding terminals are designated in the diagram
The ideal transformer can be shifted to the right, as in as BPand 0s respectively.
Fig. 2(b), to get all branches of the circuit on the same
voltage base. Since the impedance of the shunt branch is II. ELECTRICAL CHARACTERISTICS
large compared to Zrs, it can be omitted for most calcula-
tions involving transformer regulation, and the equivalent 3. Transformer Impedances
circuit becomes that of Fig. 2(c). A notable exception to The turns ratio of a two-winding transformer determines
those cases where the shunt branch can be disregarded is the ratio between primary and secondary terminal volt-
the case of the three-phase core-form transformer excited ages, when the transformer load current is zero. However,
with zero-sequence voltages. This will be discussed in when load is applied to the transformer, the load current
detail later. encounters an apparent impedance within the transformer
The form of the equivalent circuit given in Fig. 2(c) can which causes the ratio of terminal voltages to depart from
be changed to show the leakage impedance referred to the the actual turns ratio. This internal impedance consists
secondary voltage, by shifting the ideal transformer-to of two components: (1) a reactance derived from the effect
the left, as in Fig. 2(d). For this condition Zsr, the leakage of leakage flux in the windings, and (2) an equivalent
impedance between the P and S windings as measured in resistance which represents all losses traceable to the flow
ohms on the S winding with the P winding short-circuited, of load current, such as conductor 12R loss and stray
is related to Zps as follows: eddy-current loss.
Impedance drop is conveniently expressed in percent,
and is the impedance-drop voltage expressed as a percent-
age of rated terminal voltage, when both voltages are
The equivalent circuit using percentage impedances, referred to the same circuit; in three-phase transformer
percentage voltages, and currents in per unit is given in banks, it is usually appropriate to refer both impedance-
Fig. 2(e). An ideal transformer to maintain transformation drop voltage and rated voltage to a line-to-neutral basis.
ratios is not required. Percent impedance is also equal to measured ohmic im-
pedance, expressed as a percentage of “normal” ohms.
2. Transformer Vector Diagram Normal ohms for a transformer circuit are defined as the
The vector diagram illustrating the relationship between rated current (per phase) divided into rated voltage (line-
the terminal voltages, the internal induced voltages and to-neutral).
the currents in the transformer of Fig. 1 can be drawn Representative impedance values for distribution and
directly from the equivalent circuit for the transformer. power transformers are given in Table 1; for most purposes
This circuit is repeated in Fig. 3(a) and the various voltages the impedances of power transformers may be considered
Chapter 5 Power Transjormers and Reactors 99

TABLE 1 -TRANSFORMER IMPEDANCES TABLE ~-TRANSFORMER IMPEDANCES (Continued)


(a) Standard Rcactances and Impedances for Ratings (b) Standard Range in Impedances for Two-Winding
500 kva and below (for 60-cycle transformers) Power Trsnsformcrs Rated at 55 C Rise
(Both 25- and GO-cycle transformers)

2.5
-
Rated-Voltage

15
Class in kv

25 69 High- Low-
T- Impedance Limit in Percent

Single- --
Voltage Voltage Class
pt,ase Aver- Avcr- 1iver- Aver- Aver- Aver- Aver- Aver- OA Class
Winding Winding
K-f:1 age age age age age age age wxe Insulation Insulation ow FOA
I{atirrg* I& Im- Re- Im- Re- Im- Re- Im- OA/FA’ FOW
Class Class
act- ped- act- ped- act- ped- act- ped- kV
OA/Ff pOA*
kV
ante ante ante ante ante ante ante ante
Cl,’ Min. hlax. Min.
_---
/O %
-- --Yo %
--
% %
--
% %
15 15 4.5 7.0 6.75
3 1.1 2.2 2.8 0.8
10 1.5 2.2 2.4 1.3 4.4 5.2
25 15 5.5 8.0 8.25 12.0
25 2.0 2.5 2.3 1.7 4.8 5.2
.jO 2.1 2.4 2.5 2.1 4.9 5.2 6.3 6.5
34.5 15 6.0 8.0 9.0 12.0
100 3.1 3.3 3.2 2.9 5.0 5.2 6.3 6.5
500 4.i 4.8 I 5.0 4.9 25 6.5 9.0 9.75 13.5
5.1 I 5.2 - 6.4 6.5
.
*I?<,r three-ptxm transtorrners use )5 ot me three-phase kV% ratmg. and enter
fillIll! with rated line-to-line voltages. 46 25 6.5 9.0 9.75 13.5
34.5 7.0 10.0 10.5 15.0
:Lsequal to their reactances, because the resistance com-
poncnt is so small. The standard tolerances by which the 69 34.5 7.0 10.0 10.5 15.0
impedances may vary are f 73 percent of specified values 46 8.0 11.0 12.0 16.5
)‘oI.t,wo-winding transformers and f 10 percent for three-
92 34.5 7.5 10.5 11.25 15.75
\virltIing, auto, and other non-standard transformers.
69 8.5 12.5 12.75 18.75
The percent resistance of transformers is less consistent
:tmong various designs than is the impedance, and though 115 34.5 8.0 12.0 12.0 18.0
t.ho curves in Fig. 4 show definite values for transformer 69 9.0 14.0 13.5 21.0
resistance, considerable deviation from these figures is 92 10.0 15.0 15.0 23.25
possible.
Transformers can be designed to have impedances within 138 34.5 8.5 13.0 12.75 19.5
closer tolerances than mentioned above, or impedances 69 9.5 15.0 14.25 22.5
outside the normal range, but usually at extra cost. 115 10.5 17.0 15.75 25.5
A guide to the impedances of three-winding transformers
161 46 9.5 15.0 13.5 21.0
is given below (this guide does not apply to auto-trans-
92 10.5 16.0 15.75 24.0
formcrs). 138 11.5 18.0 17.25 27.0
(1) Select a kva base equal to the kva rating of the
196 46 10 15.0 15.0 22.5
92 11.5 17.0 17.25 25.5
161 12.5 19.0 18.75 28.5

230 46 11.0 16.0 16.5 24.0


92 12.5 18.0 18.75 27.0
161 14.0 20.0 21.0 30.0
*The impedances are expressed in percent on the self-cooled rating of 0. A/F.% arld
OA/FA/FOA
- ^ _ _ .
Uehnrtlo” Of trsnstormer cI&sses:
OA-Oil-immersed. self cooled OW-Oil-immersed. water-cooled.
OA/FA-Oil-immersed, self-cooled/forced-air-cooled.
OA/FA/FOA-Oil-immersed, self-cooled/forced-air-cooled/forced oil cooled.
FOA-Oil-immersed, forced-oil-cooled with forced air cooler.
FOW-Oil-immersed, forced-oil-cooled with water cooler.
Note: The through impedance of B two-winding autotransformer can be
estimated knowing rated circuit voltages, by multiplying impedance obtained from
this table by the factor (T).

largest capacity winding, regardless of voltage rating. All


impedances will be referred to this base.
(2) Select a percent impedance between the medium-volt-
I I I I II I I I I II age and the high-voltage circuits (ZM&), lying between
500 1000 2000 5000 10000 20000 50000
SINGLE-PHASE TRANSFORMERS KVA the limits shown for two-winding transformers in Table 1.
1000 2000 4000 I0000 20000 40000 100000 (3) The percent impedance between the medium-voltage
THREE-PHASE TRANSFORMERS KVA and low-voltage circuits (ZMI,%) may lie between the limits
Fk a--Percent resistance of transformers, based on OA kva of 0.35 (ZM,%) and 0.80 (ZM&~). Select a value of ZML%
ratings. lying within this range.
100 Power Transformers and Reactors Chapter 5

(4) Having established Znnye and Z~iLa/o, the percent at a specified power factor is reduced to zero, with the
impedance between the high-voltage and low-voltage cir- primary impressed terminal voltage maintained constant.
cuits (Zn,%) is determined as follows: Percent regulation can be calculated at any load and any
power factor by an approximate formula:
&IL% = l.lO(ZMH%+Z.\IL%) (13)
When impedances outside the above ranges are required, Regulation =
a suitable transformer can usually be supplied but probably
at increased cost. (14)
where :
4. Regulation “Regulation” is a percent quantity;
The full load regulation of a power transformer is the r = percent resistance
change in secondary voltage, expressed in percent of rated =load losses in klv, at rated kva x 1OO
secondary voltage, which occurs when the rated kva output rated kva

r A
-
DO PERCENT POWER FACTOR 95 90 8070 50’ ’ -
_,REGULATION CHART 1 IILL

.I

\
\
\ .2
\
\
\
\
\
.3

.’

L
-2.0 DIRECTIONS:-A STRAIGHT :5 ‘1 - : - ,!
-2 I EDGE PLACED ACROSS THE - I : - lo
*\ .I
. ’ RESISTANCE AND REACTANCE - : .+”
-2.2 SCALES WILL GIVE INTERCEPTS- - : lo- I .I
\
. ON THE”A”AND”B” SCALES, THE - . - -
: 7: . _ .!I .3
-2.3 SUM OF WHICH WILL GIVE THE . ‘.‘\
- PERCENT REGULATION FOR THE. 6 : 1 -O ,
-2.4 RESPECTIVE POWER FACTORS. - - :’ I ’ 1:
‘\
-2.5 E.G.,AT 1.0% RESISTANCE AND. - -
-
.
L2 \
.I
. 10.0% REACTANCE,THE REGULA-m . : 11
-2.8 TION WILL BE’ -8 . g- 1;
,.4
AT 100% P.F. 1.0+.5=1.5X _ - : . l3 .!
-2.7
11 80%” u6.8+.3=7.I% . -.3
-2.8 -7 c :
18 50% u II 9.2+.’ =9.3x . . . 1213. “ I#(
If, .2
-2.9 -9 -‘I.
-3.0
- L314 I!
-3.1 I5 .I.:
. COPYRIGHT 1911 BY J.F. PETERS . : -
-3.2 COPYRIGHT 1921 BY H.L. COLE -8 - -I2 . It -.4
.6
ii
DO PERCENT POWER FACTOR 95 SO 8070 50 -i- F-
-
Fig. S-Chart for calculating regulation of transformers.
Chapter 5 Power Transformers and Reactors 101

impedance kva loss; that is, all losses incident to magnetization at full
z = percent impedance = x 100
rated kva voltage with the secondary circuit open. Load losses are
12R loss caused by load current, eddy-current loss induced
2 = percent reactance = dzz _ r2 by stray fluxes within the transformer structure, and
p=cos e similar losses varying with load current.
g=sin e No-load losses are measured at rated frequency and
rated secondary voltage, and can be considered as inde-
e=power factor angle of load (taken as positive when pendent of load. Load losses are measured at rated fre-
current lags voltage). quency and rated secondary current, but with the second-
The full-load regulation of a transformer can be de- ary short-circuited and with reduced voltage applied to
termined for any power factor from the chart in Fig. 5; the primary. Load losses can be assumed to vary as
this chart is based on Eq. (14). the square of the load current.
Typical regulation for three-phase transformers at full
load and various power factors is shown in Table 2. These 6. Methods of Calculating Efficiency
Conventional Method-This method is illustrated
TABLE ~-APPROXIMATE REGULATION FOR 60-CYCLE below for a transformer having 0.50 percent no-load loss
THREE-PHASE TYPE OA TRANSFORMERS AT FULL LOAD
and 1.0 percent load loss at full load. Percent no-load loss
Lagging is determined by dividing the no-load loss in watts by 10
Percent Regulation
Insulation
Class
Power - - times the kva rating of the transformer, and the percent
Factor 1000 10 000 100000 load loss (total minus no-load) is determined bv dividing
kv
Percent kva kva the load loss in watts by 10 times the kva rating of the
_- -- kva
transformer. Note that the no-load loss remains con-
15 80 4.2 3.9
90 3.3 3.1 stant regardless of the load whereas the load loss varies
100 1.1 0.7 directly as the square of the load.
Percent load.. . 100.00 75.00 50.00 25.00 (1)
34.5 80 5.0 4.8 Percent load loss.. 1.00 .562 .25 ,062 (2)
90 4.0 37 Percentno-loadloss.. .50 .50 .50 .50 (3)
100 1.2 0.8 Sum of (2) and (3). 1.50 1.062 .75 .562 (4)
Sum of (1) and (4). 101.50 76.062 50.75 25.562 (5)
69 80 6.1 5.7 5.5 Dividing 100 times
90 4.9 4.4 4.2 (4) by (5). . 1.48 1.40 1.48 2.20 (6)
100 1.4 0.9 0.6 Subtract (6) from 100 98.52 98.60 98.52 9i.80 (efficiency)

138 80 7.7 7.2 7.0 Slide-Rule Method-This method is illustrated for


90 6.2 5.6 5.4 the same transformer.
100 1.8 1.2 0.9 Percent load ............... loo.00 75.00 50.00 25.00 (1)
Percent no load loss. ....... .50 .50 .50 .50 (2)
230 80 9.7 9.4 Percent load loss. .......... 1.00 .562 .25 .062 (3)
90 7.6 7.3 Sum of (2) and (3). ........ 1.50 1.062 .75 .562 (4)
100 1.7 1.3 Sum of (1) and (4). ........ 101.50 76.062 50.75 25.562 (5)
Note: These fipures apply :ansformers, at
2
loadscorrespondingto their ( At this point the operations are continued on the slide
rule, and are described here for the full load point only:
figures also apply, but less accurately, to transrormer
banks made up of three single-phase transformers; in this 1. Set 1.5 (sum of no-load and load losses) on D scale.
casethe table should be entered with the three-phase bank 2. Set 101.5 over this on the C scale.
kvn rating. 3. Now starting at the right end of scale D, read the
The regulation of three-winding transformers can be first figure (i.e., 1) as 90, the next (i.e., 9) as 91, the
calculated directly from transformer equivalent circuits, if next (i.e., 8) as 92, etc., until 98.52 is read under
the impedance branches and loading for each circuit are the left end (i.e., 1) of scale C. This 98.52 is the per-
known. The regulation of four-winding transformers may cent efkiency at full load.
also be calculated using formulas developed by R. D. This procedure is repeated in a similar manner for other
Evans.4 loads.
NOTE-If the sum of the percent no-load and load loss
5. Definition of Efficiency at full load is 1 percent or less, the first figure at the right
The efficiency of a transformer, expressed in per unit, is end of D scale (i.e., 1) is read as 99 percent and the second
the ratio of real power output to power input; figure (i.e., 9) is read as 99.1, the third figure (i.e., 8) is
Output = 1 _ Losses read as 99.2, etc.
Efficiency = ___ (15) If the sum of the percent no-load and load loss is greater
Input Input’
than 1 percent as in the case illustrated above, the right
Total losses are the sum of the no-load losses and load end is read as 90 percent. In calculating the values for the
losses. No-load losses are eddy-current loss, hysteresis other points, judgment will indicate whether 90 or 99 is
loss, 12R loss caused by exciting current, and dielectric to be used as the first figure on the right end of scale D.
102 Power Transformers and Reactors Chapter 5

Chart Method-The chart in Fig. 6 may be used to


calculate transformer efficiency at various loads. The pro- L= Fe=L
-ti Cl1 v% (17)
cedure is described in the caption below the chart.
where:
7. Loss Ratio and Product L=per unit kva load at which transformer operates
Maximum operating efficiency for a transformer results most efficiently.
when the no-load (constant) losses equal the load (variable) Cu = load losses at rated load, kw.
losses. This condition will likely occur at some load less Fe = no-load losses, kw.
than rated kva: R = loss ratio =load loss at rated load
CuXL2=Fe (16) no-load loss *

EFFICIENCY CHART
- .o .Ol
I-114 FULL LOAD 3/4 l/2 l/4 -
.9 - - *9 - 3 - .9

F .I - - .B
.8 - .B - .B
-, .I-
.? - - - .7 99.5-
- *? .7
+ .2 - $6
46 - - .6 - $6
-99.5
99.5- - .2-

L .3 -99.5 -99.5 - ** 99.0-


.4 -
- .4 - .4 - .3
.3 -
- .4 - .3 - .3 - .2 1 .3-
.2 -
- 2 - .2 - .2 _ *’ 98.5-
: 0 -3 -
- .5 -I .I - -99.0 -0 -
- .I - .I --J -
- Ii --I’4 -
z- 2 99.0- -99.0 - 99.0 - .9 -2 -
- 5
= .6tJ7 .9 - - .8 -2 -
- .9 - .9 98.0-
= : .8 - - .7 -3 -
-2.5-
- 5 - -
r .7a .-7 - .8 .B - .6 -s =
- 5
- .I - .7 -98.5
z 5 .6 - -ii _
97.5- &S--
- .8s
6 98.5- - .6 - .6 - .4 -L 1
2 cb
.4 - -98.5 -98.5 - .3
- .9
,. - .2
.3 - - .4 - .4 - .?-
97-o-
- .I
.2 - - .3 - .3
- 1.0
-98.0
.I - - .2 - .2
- .9 - .8-
r 1.1 98.0- - .I - .I
_ .8 98.5-

.9 -
- 98.0 -98.0 - .7
y I.2 - .9-
.8 -
- .9 - .9 - .6

97.7-
1.3 -97.8 -97.8 -97.5 96.0-
7 ,- 7

COPYRIGHT 1911 BY J.F. PETERS

Fig. 6-Chart for calculation of efficiency. Directions: A straight-edge placed between


the known full load copper loss and iron loss points will give intercepts on the efficiency
scales for various loads.
Chapter 5 Power Transformers and Reactors

0
TRANSFORMER RATING-WA
(a) SINGLE-PHASE

3 4 5
4 6 IO 20 40 60 100
TRANSFORMER RATING -MVA
(b) THREE-PHASE
Fig. 7-Relation between transformer loss ratio and the most
efficient loading. Fig. S-Typical values of product of percent losses (percent
full-load copper-loss times percent iron loss). For OA/FA
‘1’1~ relation between loss ratio and most efficient trans- or OA/FA/FOA units use OA rating to evaluate product. For
FOA and FOW units use 60 percent of rated kva to evaluate
former loading is shown in Fig. 7. The range through product.
which loss ratio may vary in normal transformer designs is
shown by Table 3.
The product of percent no-load and load losses is a quan- Cu = kfi xv’% kw (19)
tity that has become standardized to the extent that it is 100 ‘*
predictable with fair accuracy for large power transformers. where:
TABLE 3 .
Normal Limits of Loss Ratio, R
P =product of the percent va:lues of no-load and
I Loss Ratio, R = (G/Fe)
Voltage Class OA, OW FOA*+ load losses, (ygx(q-).
kv OA/FA” FOP*
OA/FA/FOA* kva = transformer rating.
,I(i wtl below. l.i5 to 3.25 1.4 to 2.4 8. Typical Efficiency Values
Ii!) 10 138, incl., . 1.50 to 2.75 1.2 to 2.0
~\hc 138................. 1.25 to 2.00 1.0 to 1.8 Conventional transformer efficiency is given on the basis
of losses calculated at (or corrected to) 75 degrees C and
*hcd on lossev at OA rating.
**Hlixed on losses st 60 percent of FOA or FOW rating.
TABLE 4--APPROXIMATE VALUES OF EFFICIENCY FOR 60-CYCLE,
Fig. 8 shows typical values of the product of percent losses, TWO-WINDING, OA, THREE-PHASE POWER TRANSFORMERS
as :L function of transformer size and voltage rating. TO (Full load, unity power factor, at 75°C)
"stirnatevalues of no-load and load losses for a particular I Voltacre Class
~Unsformer rating it is first necessary to select values Of kva
IWS ratio R and loss product P from Table 3 and Fig. 8. 15 kv 34.5 kv 69 kv 138 kv 161 kv
‘when the respective loss values, in kilowatts, are given 2000 98.97 98.89 98.83 98.56 98.47
h!lo\\: 10 000 99.23 99.22 99.17 99. 12 99.11
50000 I 1 99.47 1 QQ.45 1 99.44 / '.)9.4-l
(18) Note: These figuresapply also to OA/FA and OA/FA/FOA transformers. at
loads corresponding to their OA ratings.
104 Power Transformers and Reactors Chapter 5

unity power-factor load unless otherwise specified. Table 4 Shell-form construction for single-phase transformers
(rives approximate values for GO-cycle power transformers consists of all windings formed into a single ring, with
it full load, unity power-factor, and 75 degrees C. magnetic punchings assembled so as to encircle each side
of the winding ring, as in Fig. 10. The mean length of turn
III. TRANSFORMER CLASSIFICATIONS is usually longer than for a comparable core-form design,
while the iron path is shorter.
9. Forms of Construction. In the design of a particular transformer many factors
Core-form construction for single-phase transformers such as insulation stress, mechanical stress, heat distribu-
consists of magnetic steel punchings arranged to provide tion, weight and cost must be balanced and compromised5.
a single-path magnetic circuit. High- and low-voltage coils It appears that, for well-balanced design, both core-form
are grouped together on each main or vertical leg of the and shell-form units have their respective fields of applica-
core, as shown in Fig. 9. In general, the mean length of bility determined by kva and kv rating.
turn for the winding is comparatively short in the core- In the larger sizes, shell-form construction is cmite appro-
form design, while the magnetic path is long. priate; the windings and magnetic iron can be assembled

\ /

.x . - _ ^ ,, ,,- ..-. 7zu!.-.“.

Fig. 9-Core-form construction. Fig. lo-Shell-form construction.


Chapter 5 Power Transformers and Reactors

for small and medium size transformers, portable sub-


stations can provide spare capacity on short notice.
If transportation or rigging facilities should not be
adequate to handle the required transformer capacity as
a single unit, a definite reason of course develops for using
three single-phase units.
11. Types of Cooling
Basic types of cooling are referred to by the following
designations.6
OA-Oil-Immersed Self-Cooled-In this type of
transformer the insuiating oil circulates by natural convec-
tion within a tank having either smooth sides, corrugated
sides, integral tubular sides, or detachable radiators.
Smooth tanks are used for small distribution transformers
but because the losses increase more rapidly than the tank
surface area as kva capacity goes up, a smooth tank trans-
former larger than 50 kva would have to be abnormally
large to provide sufficient radiating surface. Integral
tubular-type construction is used up to about 3000 kva
and in some cases to larger capacities, though shipping
restrictions usually limit this type of construction at the
larger ratings. Above 3000 kva detachable radiators are
usually supplied. Transformers rated 46 kv and below
1:~. 11-Assembly of 1.5 000 kva three-phase transformer,
may also be filled with Inerteen fire-proof insulating liquid,
showing “form-fit” tank being lowered into position. instead of with oil.
The OA transformer is a basic type, and serves as a
()I1:t steel base structure, with laminations laid in horizon- standard for rating and pricing other types.
r,:llly to link and surround the windings. A close-fitting OAIFA-Oil-Immersed Self-Cooled/Forced-Air
I,:& member is then dropped over the core and coil assem- Cooled-This type of transformer is basically an OA unit
hly and welded to the steel base, completing the tank with the addition of fans to increase the rate of heat trans-
assembly and also securing the core to the base member. fer from the cooling surfaces, thereby increasing the per-
‘I’his “form-fit” construction is shown in Fig. 11; it is more missible transformer output. The OA/FA transformer is
compact than can be achieved by assembling a core form applicable in situations that require short-time peak loads
unit, within a tank, and the flow of cooling oil can be to be carried recurrently, without affecting normal ex-
(lilocted more uniformly throughout the interior of the pected transformer life. This transformer may be pur-
coil assembly. chased with fans already installed, or it may be purchased
with the option of adding fans later.
10. Comparison of Single-Phase and Three-Phase
Units for Three-Phase Banks
.\ three-phase power transformation can be accomplished
41 her by using a three-phase transformer unit, or by inter-
cLotmcctingthree single-phase units to form a three-phase
Ijlink. The three-phase unit has advantages of greater
c~flicicncy, smaller size, and less cost when compared with
:LI):mk having equal kva capacity made up of three single-
\)ll:lse units.
\l’hen three single-phase units are used in a bank, it is
Possible to purchase and install a fourth unit at the same
l(~(Uion as an emergency spare. This requires only 33
Wccnt additional investment to provide replacement ca-
Picity, whereas 100 percent additional cost would be re-
rluircd to provide complete spare capacity for a three-phase
‘Init. However, transformers have a proven reliability
l1igl~erthan most other elements of a power system, and
for this reason the provision of immediately available spare
Wacity is now considered less important than it once was.
‘rl~rce-phase units are quite generally used in the highest
Of circuit ratings with no on-the-spot spare transformer
‘apacity provided. In these casesparallel or interconnected Fig. 12-Installation view of a 25 000 kva, 115-12 kv, three-
circuits of the system may provide emergency capacity, or, phase, 60 cycle, OA/FA transformer.
106 Power Transformers and Reactors Chapter 5
11
The higher kva capacity attained by the use of fans is and a second rating based on forced circulation of air by
1I
dependent upon the self-cooled rating of the transformer fans or blowers.
and may be calculated as follows:
i
For 2500 kva (O-4) and bclon: IV. POLARITY AND TERMINAL MARKINGS j
kva (FA) = 1.15xkva(OA). (20) 12. Single-Phase Transformers 9
For 2501 to 9999 k~a (Oh) single-phase or 11 999 .!
Primary and secondary terminals of a single-phase trans-
kva (O-4) three-phase:
former have the same polarity n-hen, at a given instant of ,:
kva (F’a) = 1.25Xkva (OX). (21) 1
time, the current enters the primary terminal in question
For 10 000 kva (Oil) single-phase and 12 000 and leaves the secondary terminal. In Fig. 13 are illustrated 2
kva (O-4) three-phase, and above:
kva (FA) = 1.333 x kva (OA). (22)
These ratings are standardized, and are based on a hot-
4 Hz HIEs
ES
H2
1

test-spot copper temperabure of 65 degrees C above 30


degrees C average ambient.
OA/FOA/FOA-Oil-Immersed Self-Cooled,‘Forced-

2
Oil Forced - Air Cooled,‘Forced - Oil Forced - Air
Cooled-The rat,ing of an oil-immersed transformer may
be increased from its Od rating by the addition of some
combination of fans and oil pumps. Such transformers
XI
ER
x2
El x2
EP
XI

are normally built in the range 10 000 kva (0.1) single- In I,

phase or 12 000 kva (OA) three-phase, and above. In- XI Xl .I

creased ratings are defined as two steps, 1.333 and l.GG7 ‘;


;
times the OA rating respect’ively. Recognized variations of X2
these triple-rated transformers are the OA/FA/FX and the
“2 ‘1
OA4/FA/FOA types. Automatic controls responsive to oil I

temperature are normally used to start the fans and pumps ES


in a selected sequence as transformer loading increases. HI
FOA-Oil-Immersed Forced-Oil-Cooled With (a) (b) Is
SUBTRACTIVE POLARITY ADDITIVE POLARITY
Forced-Air Cooler-This type of transformer is intended
for use only when both oil pumps and fans are operating, Fig. 13-Standard polarity markings for two-winding trans-
under which condition any load up to full rated kva may formers.
be carried. Some designs arc capable of carrying excitation
current with no fans or pumps in operation, but this is not single-phase transformers of additive and subtractive po-
universally true. Heat transfer from oil to air is accom- larity. If voltage is applied to the primary of both trans-
plished in external oil-to-air heat exchangers. formers, and @ace& leads connected together, HI to Xl
OW-Oil-Immersed Water-Cooled-In this type in Fig. 13(a) and HI to XB in Fig. 13(b), a voltmeter across-
of water-cooled transformer, the cooling water runs through the other pair of terminals [Hz and X, in Fig. 13(a) and
coils of pipe which are in contact with the insulating oil of Hz and X1 in Fig. 13(b)] indicates a voltage greater than
the transformer. The oil flows around the outside of these E, if the transformer is additive as Fig. 13(b), and less than
pipe coils by natural convection, thereby effecting the E, if the transformer is subtractive as Fig. 13(a).
desired heat transfer to the cooling water. This type has Sdditive polarity is standard for all single-phase trans-
no self-cooled rating. formers 200 kva and smaller having high-voltage ratings
FOW-Oil-Immersed Forced-Oil-Cooled Wi;h 8660 volts (winding voltage) and below. Subtractiire po-
Forced- Water Cooler-External oil-to-water heat ex- larity is standard for all other single-phase transformers.6
changers are used in this type of unit to transfer heat from
oil to cooling water; otherwise the transformer is similar 13. Three-Phase Transformers
to the FOA type. The polarity of a three-phase transformer is fixed by
AA-Dry-Type Self-Cooled-Dry-type transform- the connections between phases as well as by the relative
ers, available at voltage ratings of 15 kv and below, contain locations of leads, and can be designated by a sketch
no oil or other liquid to perform insulating and cooling showing lead marking and a vector diagram showing the
functions. electrical angular shift between terminals.
Air is the medium which surrounds the core and coils, The standard angular displacement between reference
and cooling must be accomplished primarily by air flow phases of a delta-delta bank, or a star-star bank is zero
inside the transformer. The self-cooled type is arranged degrees. The standard angular displacement between ref-
to permit circulation of air by natural convection. erence phases of a star-delta bank, or a delta-star bank,
AFA-Dry-Type Forced-Air Cooled-This type of is 30 degrees. The present American standard for such
transformer has a single rating, based on forced circulation three-phase banks is that the high-voltage reference phase
of air by fans or blowers. is 30 degrees ahead of the reference phase on the low
AAIFA-Dry-Type Self-Cooled/Forced-Air Cooled voltage, regardless of whether the bank connections are
-This design has one rating based on natural convection star-delta or delta-star.6 The standard terminal markings
Chapter 5 Power Transformers and Reactors 107

V. STANDARD INSULATION CLASSES


“3
HIGH LOW
VOLTAGE
14. Choice of Insulation Class
VOLTAGE H2
HI The standard insulation classes and dielectric tests for
poxver transformers are given in Table 5. The insulation
class of a transformer is determined by the dielectric tests
lvhich the unit can Jvithstand, rather than by rated operat-
ing voltage.
On a particular system, the insulation class of the
connected power transformers may be determined by the
ratings and characteristics of the protective devices in-
stalled to limit surge voltages across the transformer
Jvindings. Ratings of the protective devices Jvill in turn
depend upon the type of system, its grounding connections,
and some related factors. For example, Iv-hen the system
neutral is solidly grounded so that a grounded neutral (SO
DELTA-DELTA OR STAR-DELTA OR percent) arrester can be used, an insulation level corrc-
STAR-STAR CONNECTION DELTA-STAR CONNECTION sponding to the arrester rating may be chosen rather than
an insulation level corresponding to the system operating
(b) LINE-TO-NEUTRAL VOLTAGE VECTOR DIAGRAMS voltage. Many transformer banks having a star-connected
I?ib. Id-Standard polarity markings and vector diagrams for three-phase xvinding, vGth the neutral permanently and
three-phase transformers. solidly grounded, have an impulse strengt,h corresponding
to a lower line-to-line classification than indicated in Table
5 (See Chap. 18 for a more detailed discussion of this
for a three-phase, two-winding transformer are illustrated subject).
in l;ig. 14. -41~0included are the vector diagrams for delta-
clclta, star-star, star-delta and delta-star connected trans- 15. Dielectric Tests
I’ormers. The phase rotations are assumed to be HI-H%-H3 The purpose of dielectric testing is to sholv that the
:1ntl x,-,Y?-x,. design, workmanship, and insulation qualities of a trans-
Icig. 15 summarizes the phase angles that can be obtained former are such that the unit will actually meet standard
I)ct\vccn high- and lorv-voltage sides of star-delta and delta- or specified voltage test limits. Below is a description of
the various dielectric tests Ivhich may be applied to polver
transformers :
E og LAGS EA6BBY 30’ Eag LEADS EAG BY 30’ (1) The standard impulse test consists of applying in
c --Ii, x,--c A --‘H3 X,*- 0
succession, one reduced full wave, two chopped waves, and
one full wave.
o--b B---o
(a) A full wave is a 1.5X-20 microsecond wave, usually of
negative polarity for oil-immersed transformers, or positive
polarity for dry type, and of the magnitude given in
Eag LAGS E,,BY 150’
Table 5.
(b) A reducedfull wave is a 1.5X40 microsecond wave, having
a crest value betmeen 50 and 70 percent of the full wave
crest.
(c) A choppedwaveis formed by connecting an air gap to cause
voltage breakdown on the tail of the applied lvvave.The
Eaq LAGS EAG BY 90’ Eag LEADS Eric BY 90’
crest voltage and minimum time to flashover are specified
in Table 5.
(2) The standard applied-potential test consists of apply-
ing a low-frequency voltage between ground and the mind-
ing under test, Tvith all other windings grounded. The
l%. Is-Angular phase displacements obtainable with three-
standard test voltage magnitude is listed in Table 5, and
phase star-delta transformer units. its specified duration is one minute.
(3) The standard induced-potential test in general con-
sists of applying between the terminals of one winding a
star, three-phase transformers built with standard connec- voltage equal to twice the normal operating voltage of that
tions and terminal markings. In this Figure A, B, and C winding. A frequency of twice rated or more is used for
rcl)rcsent the three phases of the high-voltage system, this test, so that the transformer core will not be over-
\\herens a, b, and c represent the three phases of the low- excited by the application of double voltage. The duration
voltage system. Phase rotations A-B-C and a-b-c are of the test is 7200 cycles of the test frequency, but not
:lSSumed longer than one minute. Commonly used test frequencies
108 Power Transformers and Reactors Chapter 5

TABLE ~-STANDARD INSULATION CLASSES AND DIELECTRIC


TESTS FOR DISTRIBUTION AND POWER TRANSFORMERS
(Taken from Table 11.030 AELI Standard C57.11-1948 for Transformers, Regulators and Reactors.)
-
Impulse Tests
Rated Voltage Between Terminals Low Frequency -
of Ponder-Tmnsformers (a) Tests Oil-Immersed Transformers Oil-Immersed Transformers
500 kvn or Less Above 500 kva
- - - -
Insulil- FUll FUll
tion Single-Phase 3-Phase Oil-Im- Chopped Wave Chopped Wave
Dry Bnve (e‘ ) P v’nve (c)
Class mersed
For Y- For Delta- ‘Ihe
‘YP~ (b: Min Time Min Time
Deltaor Y-
Connection Connection to to
Connected Kv KV Kv Kv
on a-Phase on 3-Phase Flash- Flash-
kv rms Crest Crest Crest Crest
System (0) System over over
kv rms (cl kv rms kv rms Microsec. hIicrosec.
kV kv rms
_-
1.2 0.69 0.09 (cl 1.2 10 4 3G 1.0 30 54 1.5 45
2.5 2.5 15 10 54 1.25 45
5.0 “iii9 2.89 (d 5.0 19 12 G9 1.5 GO “ii 1.6 i5
8.66 5.0 5.00 (d 8.66 26 19 88 1.6 75 110 1.8 95
15 8.66 15.0 15.0 34 31 110 1.8 95 130 2.0 110

25.0 14.4 25.0 25.0 50 175 3.0 150 Ii5 3.0 150
34.5 19.9 34.5 34.5 i0 230 3.0 200 230 3.0 200
46.0 26.6 46.0 46.0 95 290 3.0 250 290 30 250
69.0 39.8 69.0 69.0 140 .. 400 3.0 350 400 3.0 350

92 53.1 92 92 185 . 520 3.0 450 520 3.0 450


115 66.4 115 115 230 . 630 3.0 550 630 3.0 550
138 i9.7 138 138 275 750 3.0 650 750 3.0 650
161 93.0 161 161 32.5 865 3.0 750 865 3.0 750

196 113 196 196 395 .. 1035 3.0 900 1035 3.0 900
230. 133 230 230 460 . 1210 3.0 1050 1210 3.0 1050
287 166 287 287 575 1500 3.0 1300 1500 3.0 1300
345 199 345 690 1785 3.0 1550 1785 3.0 - 1550
Notes: (a) Intermediate voltage ratings are placed in the next higher insulation class unless otherwise specified.
(b) Standard impulse tests have not been established for dry-type distribution and power transformers. Present-day values for impulse tests of such apparatu
*re *s follows:
1.2 kv class. 10 kv: 2.5 class. 20 kv: 5.0 class. 25 kv: 8.66 kv class. 35 kv: 15 kv class. 50 kv. These values applv to both chopped-wave and full-
WV&Y62tests.
(c) Y-connected transformers for operation with neutral solidly grounded or grounded through an impedance may have reduced insulation at the neutrnl. When
this reduced insulation is below the level required for delta operation, transformers cannot be operated delta-connected.
(d) These apparatus are insulated for the test voltages corresponding to the Y connection, so that a single line of apparatus serves for the Y and delta applica-
tions. The test voltages for such delta-connected single-phase apparatus are therefore one Step higher than needed for their voltage rating.
(e) 1.5X40 microsecond WBYB.

are 120 cycles for 60-cycle transformers, and 60 cycles f.or should the neutral class be lower than that given in Column
25-cycle transformers. 2, Table 6.
Combinations and modifications of the tests described (c) If the neutral of a transformer is connected to ground
above are contained in transformer standard publications, through the series winding of a regulating transformer, the
for example ASA C57.22-1948, and these publications neutral insulation class must be at least as high as the
should be consulted for detailed information. maximum raise or lower voltage (phase to neutral) of the
regulating transformer. In no case should the neutral class
16. Insulation Class of Transformer Neutrals be less than that given in Column 3 of Table 6.
Transformers designed for wye connection only with the (d) A transformer grounded through the series winding
neutral brought out may have a lower insulation level at of a regulating transformer and a separate neutral imped-
the neutral than at the line end. The following rules are ance shall have a neutral insulation class at least as high
included as a guide in selecting the permissible neutral as. the sum of the maximum raise or lower voltage (line
insulation level : to neutral) of the regulating transformer and the maximum
(a) A solidly grounded transformer may have a mini- dynamic voltage across the neutral impedance during sys-
mum neutral insulation class in accordance with column tem short-circuit conditions. In no case should the neutral
2 of Table 6. insulation class be less than that given in Column 3 of
(b) A transformer grounded through a neutral imped- Table 6.
ance must have a neutral insulation class at least as high (e) If the neutral of a transformer is connected to ground
as the maximum dynamic voltage at the transformer neu- through a ground fault neutralizer, or operated un-
tral during system short-circuit conditions. In no case grounded but impulse protected, the minimum neutral
Chapter 5 Power Transformers and Reactors 109

TABLE ~-MINIMUM INSULATION CLASS AT TRANSFORMER winding. The initial current is assumed to be com-
NEUTRAL pletely displaced from zero.
- - (b) The duration of the short circuit is limited to the fol-
(1) (2) (3) (4) lowing time periods. Intermediate values may be
Grounded determined by interpolation.
Grounded
Winding Grounded Through
Solidly or
Insulation Through Ground Fault Symmetrical Current Time Period
Through
Class at Regulating Neutralizer or in Any Winding in Seconds
Current
Line End Transformer Isolated but 25 times base current 2
Transformer
11mpulseProtected 20 times base current 3
_- .-
16.6 times base current 4
1.2
2.5
14.3, or less, times base current 5
5.0 Same as Line E Ind “2. Where kva is mentioned in paragraph 3 the following
8.GG
is intended:
15 8.66 8.66 8.66
8.66 8.66 15
When the windings have a self-cooled rating, the kva
25
34.5 8.66 8.66 25 of the self-cooled rating shall be used. When the
48 15 15 34.5 windings have no self-cooled ratings, the largest kva
G9 15 15 46 obtained from the ratings assigned for other means
02 15 25 69 of cooling by the use of the following factors shall
115 15 25 69 be used:
138 15 34.5 92
161 15 34.5 92 Type of Transformer Multiplying Factor
19G 15 46 115 Water-cooled (OW) 1.0
230 15 46 138 Dry-Type Forced-Air-Cooled (AFA) 0.75
287 15 69 161 Forced-oil-cooled (FOA or FOW) 0.60
345 - 15 69 -
196
“3. For multi-winding transformers:
The base current of any winding provided with es-
insulation class shall be in accordance with Column 4 of ternal terminals, or of any delta-connected stabiliz-
Table 6. ing winding without terminals, shall be determined
from the rated kva of the winding or from not less
VI. TEMPERATURE AND SHORT-CIRCUIT than 35 percent of the rated kva of the largest
STANDARDS. winding of the transformer, whichever is larger.

17. Temperature Standards “In some cases, the short-circuit current, as limited by
transformer impedance alone, will exceed 25 times base
The rating of electrical apparatus is inherently deter- current. It must be recognized that such cases can occur
mined by the allowable operating temperatures of insu- with transformers manufactured according to these stand-
lation, or the temperature rise of the insulation above ards and that the transformers built under these standards
ambient temperature. For transformers and voltage reg- are not designed to withstand such short-circuit current.”
ulators with Class A insulation, either air or oil cooled,
Under short-circuit conditions the calculated copper
t>hcrating is based on an observable temperature rise (by temperatures for power and distribution transformers shall
r&stance or thermometer) of 55 C above an ambient not exceed 250 C where Class A insulation is used assuming
I’cmperature at no time in excess of 40 C, and the average
an initial copper temperature of 90 C, or 350 C where
(luring any 24-hour period not exceeding 30 C. Trans- Class B insulation is used assuming an initial copper
formers and other induction apparatus are designed to
temperature of 125 C.
limit the hottest-spot temperatures of the windings to not
more than 10 C above their average temperatures under
continuous rated conditions. The limits of observable VII. TRANSFORMER TEMPERATURE-TIME
temperature rise for air-cooled transformers with Class B CURVES
insulation is 80 C by resistance measurement. 19. Constant Load
18. Short-Circuit Conditions A “heat run” of a transformer on test is made to deter-
mine the temperature rise of the various parts at rated
A proposed revision to American Standard C57.12-1948
load. If the test were made by applying only rated load,
(section 12.050) reads in part:
with the transformer at room temperature, thirty hours or
“1. Transformers shall be capable of withstanding with- more would be required before stationary temperatures
out injury short circuits on any external terminals, were reached. Such a process would be quite inefficient of
with rated line voltages maintained on all terminals time, energy, and in the use of testing facilities. Accelerated
intended for connection to sources of power, heat runs are made by closing radiator valves, etc., and
provided : applying loads in excess of rated load until the expected
(a) The magnitude of the symmetrical current in any wind- temperatures are reached. Radiation restrictions are then
ing of the transformer, resulting from the external short removed, the load reduced to normal, and the test con-
circuit, does not exceed25 times the basecurrent of the tinued until stable temperatures are reached.
110 Power Transformers and Reactors Chapter 5

It is evident that the temperature-time characteristics temperature rise, that is, T and TF are defined as before
of a transformer cannot be obtained from the accelerated but refer to the top-oil specifically. Further, the final top-
heat-run data. Information is secured from the heat run, oil temperature rise TF is not directly proportional to the
however, which permits the temperatures to be calculated losses for all types of transformers as Eq. (23) would
under assumed load conditions. Exact calculations are indicate, but is more correctly represented by the relation
quite involved, but sufficiently accurate results can be W m
obtained by the use of an approximate method due to TF= TF(II) (28)
S. 13. Griscom for estimating the temperatures reached Total loss at full load >
under variable load conditions, changing ambient tempera- where:
tures, etc. Certain simplifying assumptions can be made m =0.8 for type OA transformers.
that permit a quick estimate of the expected temperatures. =0.9 for type OA/FA transformers.
Let L = transformer load in kva. = 1.0 for type FOB transformers.
IV = total losses (in kw) at load L. TF~I~)=final top-oil temperature rise at full load in
TF = final temperature rise at load L in degrees C above degrees C.
the temperature at t = 0.
The use of this relation when substituted in Eq. (23)
M = thermal capacity in kw hours per degree C.
indicates that for other than the type FOX transformer the
k = radiation constant in kw per degree C. radiation constant k :and the time constant H are not
T = oil temperature rise in degrees C at time t above completely independent of load but vary according to a
the temperature at t = 0.
small fractional power of the total loss. However for con-
H = thermal time constant in hours.
venience in calculations this variation in k and H is nor-
t = time in hours.
mally overlooked and the values obtained from Equations
If the heat radiated is directly proportional to the (23) and (27) for the full load condition are taken as
temperature rise of the transformer above the ambient, the constant. The error introduced by the procedure is not
radiation constant can be obtained from the heat run data large compared to that normally expected in transient
for W and TF: thermal calculations.
To determine the temperature rise curve for any load L
k=; (23) therefore, the radiation constant k under full load condi-
tions is first determined from the heat run data using
where the temperature at t=O is taken as ambient. Eq. (23). The thermal capacity M is dependent on the
Since the total heat generated is equal to the heat thermal capacities of the various parts of the transformer.
radiated plus the heat stored (heat consumed in raising the For convenience it can be assumed that the transformer
temperatures of the various parts) parts can be separated into three elements: the core and
coils, the case and fittings, and the oil. Although the core
W=kT+Mz (24) and coils are of copper, iron, and insulation the specific
heats of those elements do not vary widely. Since, also,
This equation can be solved for T, giving there is a reasonably constant proportion of these elements
in different transformers, a single weighted coefficient of
T=$ l-& (25) thermal capacity for the coils and core is warranted. The
*( > following relation is accordingly suggested:
or
M= ko[0.06 (wt. of core and coils)
T=TF 1-e-i (29
( > +0.04 (wt. of case and fittings)
where
+0.17 (wt. of oil)] (29)
H = F = the transformer time constant in hours. (27) Here the coefficients of the last two terms are also weighted
to make further allowance for the fact that all parts of the
This derivation may be broadened to show that Eq. case and fittings and the oil are not at a uniform tempera-
(26) is equally correct for the case where the oil temper- ture. The values of k and M found as above may be
ature rises T and TF are those above the temperature at substituted in Eq. (27) to obtain H. The value of TF for
1= 0, whether the value then is the ambient temperature or the desired load L is determined next by substitution of
otherwise. heat run data in Eq. (28). The quantity W for the load L
The foregoing discussion has been based on the assump- may be evaluated by the relation
tion that the temperature throughout all parts of the trans-
K L 2
former is the same. This, of course, is not the case. When w= x (full load copper loss)
Full load kva
the transformer load is increased, the copper temperature 1
is above that of the surrounding parts, and when the load + (no-load loss) (30)
is decreased, the copper tends to be more nearly the same 1
temperature as the surrounding parts. Also, the top and The quantities H and TF may now be substituted in Eq.
bottom oil are at different temperatures. Eq. (26) is (26) from which the top-oil temperature-rise curve may be
therefore commonly taken as referring to the top-oil plotted directly.
Chapter 5 Power Transformers and Reactors

For exampk, a 6000-kva, three-phase, self-cooled, 40


24 OOO-5040volt transformer has the following full load
nerformance data as supplied by the manufacturer:
Iron loss= 10 920 watts.
Copper loss=43 540 watts.
Total = 54 460 watts.
Top-oil rise = 40 C (from heat-run test data).
LV copper rise=46.3 C.
HV copper rise=43.3 C.
Wt. of core and coils = 25 000 pounds.
Wt. of case and fittings= 18 000 pounds.
Wt. of oil= 17 400 pounds.
From this information the time constant H may be evalu-
:II c:tl and the expression for T obtained for the load L equal
to the rated load.
W 54.46
- = 1.36 kw per degree C.
“‘=a= 40

‘U = &o[0.06X25 000+0.04x18 000+0.17x17 4001

= 5.18 km hours per degree C.

I[=!f=.5.‘“=3 81 hours
li 1.36 ’ ’
y= l’& - e--1/H) =J;O(l- &/3.81)~

‘l’hc full load top-oil temperature rise curve shown in Fig.


16 was calculated from this relation.
To plot the top-oil temperature-rise curve for half-load Fig. 16-Top-oil temperature rise versus time, for a typical
conditions for this transformer the same time constant H transformer.
is used as found above.
From Eq. (28) : termined during the heat-run. The average copper tem-
perature rise above ambient at full load is required by
(0.5)2X43.54+ 10.92 y 1g 2 c
T~=40 . . standards not to exceed 55 C for class A insulation. The
54.46 > use of that value to obtain the apparent copper gradient
will generally lead to overly pessimistic results since the
T=19.2 actual value of the average copper temperature rise is
normally below the limit. Therefore it is advisable to use
The curve represented by this equation also appears in the value measured on the heat run and obtained from the
I$. 16 manufacturer.
The rise of the hottest-spot copper temperature above For any load L, the hottest-spot copper gradient may be
h top-oil temperature is known as the hottest-spot cop- calculated from the relation
wr gradient and at full load may be estimated from the 1.6
r&ttion L
GH(L)=GHW)X (32)
full load kva
Grrct,, =Gc(r,,+A. (31) From the performance data of the transformer previously
\vlicrc: cited:
Gn(h) = hottest spot copper gradient at full load in Gccrl, =46.3-40= 6.3 C for the LV winding.
degrees C. GH([,) = 6.3+ 10 = 16.3 C.
Gccri, =apparent copper gradient at full load in
degrees C. The hottest-spot copper temperature for full-load is thus
A= 10 C for type OA and OW transformers. 16.3 C above the top-oil temperature. For, say, half-load,
= 10 C for type GA/FA transformers. Eq. (32) must be used to obtain
=5 C for type FOA and FOW transformers GH(L)= 16.3X(O.5)‘-6=5.4 C.
with directed flow over coils.
It is not feasible in a study of this kind to keep track of
The apparent copper gradient at full load (Go& is the short time variations of copper or hottest-spot tempera-
difference between the average copper temperature rise ture, and it is suggested if it is desirable to show roughly
snd the top-oil temperature rise, both of which are de- how this varies, a time constant of 15 minutes be used.
112 Power Transformers and Reactors Chapter 5

TEMPEkATURE I!
t

I 1

6 6 IO 12 2
NOON

Fig. 17--Step-by-step graphical calculation of temperatures under changing load conditions.


- - - -
20. Variable Load I ha1 Oil
Temp. Hottest-
A step-by-step analysis using Eqs. (28) to (32) can be Final ambient spot
made to consider conditions of variable load, changing Load Loss tOil Rise plus 3radient
ambient temperatures, etc. The method of approach is Time Ambieni t (ma) 1zq. (30) 1Eq. GW final rise Eq. (32)
.- .- -- _- .-
based on the fact that the initial rate of change of tempera- 12 29c 2 15.7 14.x 43.7c 2.8C
ture is the slope of a line joining the initial and final tem-
peratures, the two temperatures being separated by a time
2 AM
4
[I 29
28
2
2
15.7
15.i
14.7
14.7
43.7
42.7
2.8
2.8
interval equal to the thermal time const,ant of the trans- 6 27 3 21.8 10.2 46.2 5.4
former. As before TF is calculated from heat run data and 8 29 4 30.2 24.9 53.9 8.5
the total loss W for each load condition through the use of 10 31 5 41.1 31.9 62.9 12.2
Eq. (28). The loss W is obtained from Eq. (30). The final 12 33 6 54.5 40.0 73.0 16.3
top-oil temperature is then found by adding TF to the 2 PM 35 6 54.5 40.0 75.0 16.3
4 37 6 54.5 40.0 ii.0 16.3
ambient temperature. Since the load is varying, the final
6 34 5 41.1 31.9 65.0 12.2
temperature cannot be reached for each load condition and 8 32 4 30.2 24.9 56.9 8.5
the step-by-step analysis must be employed to obtain the 10 30 3 21.8 19.2 49.2 5.4
top-oil temperature curve. Points on the hottest-spot
temperature time curve may then be obtained by adding
12 29 - 2 - 15.7 - 14.i - -13.7 - 2.8

the hottest-spot copper gradient Gn for each load to the


top-oil temperature at the time corresponding to the load VIII. GUIDES FOR LOADING OIL-IMMERSED
for which the gradient was calculated. Gn is obtained in POWER TRANSFORMERS
the same manner as previously outlined.
To illustrate the step-by-step method, the oil tempera- 21. General
ture-time curve for the 6000-kva transformer previously The rated kva output of a transformer is that load which
described will be calculated, starting with an oil tempera- it can deliver continuously at rated secondary voltage
ture of 55 C for an assumed load cycle as tabulated in the without exceeding a given temperature rise measured
adjacent column. under prescribed test conditions. The actual test tempera-
Figure 17 illustrates the use of the calculated data in the ture rise may, in a practical case, be somewhat below the i
graphical step-by-step process to plot the curve of top-oil established limit because of design and manufacturing 3
I
temperature with time and the manner in which the hottest- tolerances. 1
spot gradients are added to obtain the hottest-spot tem- The output which a transformer can deliver in service {
perature-time curve. The accuracy can be increased by without undue deterioration of the insulation may be more
using shorter time intervals. or less than its rated output, depending upon the following 1
i
Chapter 5 Power Transformers and Reactors

design characteristics and operating conditions as they


exist at a particular time6:
(1) Ambient temperature. 160
(2) Top-oil rise over ambient temperature.
(3) Hottest-spot rise over top-oil temperature
(hottest-spot copper gradient).
(1) Transformer thermal time constant.
(5) Ratio of load loss to no-load loss.

22. Loading Based on Ambient Temperature


;\ir-cooled oil-immersed transformers built to meet es-
tablished standards will operate continuously with normal
life expectancy at rated kva and secondary voltage, pro-
viding the ambient air temperature averages no more than
30 C throughout a 24-hour period with maximum air
~(ampcrature never exceeding 40 C. Water-cooled trans-
formcrs are built to operate continuously at rated output
\vith ambient water temperatures averaging 25 C and
never exceeding 30 C.
When the average temperature of the cooling medium is
difTerent from the values above, a modification of the trans-
former loading may be made according to Table 7. In

TABLE ~-PERCENT CHANGE IN KVA LOAD FOR EACH DEGREE


CENTIGRADE CHANGE IN AVERAGE AMBIENT TEMPERATURE
0-I ’ ’ ’ ’ ’ ’ ’ ’ ’
Air above 30 C nvg. Air below 30 C nvg. 0 40 80 120 160 200 240
Type of Coolirlg Or or PERCENT RATED KVA
Water rtbove 25 C avg. Water below 25 C avg.
Fig. E-Hottest-spot copper rise above top-oil temperature
Self-cooled -1.5L%,perdeg.C +l .O% per deg. C as a function of load, for various values of full load copper rise.
\Vater-cooled -1.5 +1.0
Forced-Air-Cooled -1.o* +0.75* 2.2
Forwd-Oil-Cooled -1.o* +0.75*
*Based on forced-cooled rating.

cases where the difference between maximum air temper-


atllre and average air temperature exceeds 10 C, a new
temperature that is 10 C below the maximum should be El I I l\l\
rlsed in place of the true average. The allowable difference
between maximum and average temperature for water-
cooled transformers is 5 C.
I I IN\
23. Loading Based on Measured Oil Temperatures I-
1.2
The temperature of the hottest-spot within a power
transformer winding influences to a large degree the de-
trrioration rate of insulation. For oil-immersed transform-
~1’st,he hottest-spot temperature limits have been set at TOP OIL TEMPERATURE IN DEGREES C
105 C maximum and 95 C average through a 24 hour
Wriod; normal life expectancy is based on these limits. Fig. 19-Loading guide based on top-oil temperature.
The top-oil temperature, together with a suitable tem- CA) OA, OW, OA/FA types.
perature increment called either hottest-spot copper rise (B) OA/FA/FOA, FOA, FOW types.
Ouer top-oil temperature or hottest-spot copper gradient, is
often used as an indication of hottest-spot temperature. A conservative loading guide, based on top-oil tempera-
:lllolvable top-oil temperature for a particular constant tures, is given in Fig. 19.
load may be determined by subtracting the hottest-spot
copper gradient for that load from 95 C. The hottest-spot 24. Loading Based on Capacity Factor
CoPPergradient must be known from design information Transformer capacity factor (operating kva divided by
for accurate results, though typical values may be assumed rated kva) averaged throughout a 24-hour period may be
for estimating purposes. If the hottest-spot copper grad- well below 100 percent, and when this is true some com-
ient is known for one load condition, it may be estima- pensating increase in maximum transformer loading may
ted for other load conditions by reference to Fig. 18. be made. The percentage increase in maximum loading
114 Power Transformers and Reactors Chapter 5

TABLE %-PERMISSIBLE TRANSFORMERLOADING BASED ON TABLE 9--PERMISSIBLE DAILY SHORT-TIME TRANSFORMER


AVERAGE PERCENT CAPACITY FACTORS* LOADING BASED ON NORMAL LIFE EXPECTANCY
-
Percent Increase Maximum SIaximum Load In Per Unit of Transformer Rating’“’
Above Rat,ed kva Percent
Increase, Period of 04/FA/FOA,‘C’
Type of Cooling For each Percent By OA, OW OA/FAch’
Increased II1, FOA
Which Capacity Factor Regardless of
Is Below 100 Capacity Factor Loading, Average’“’ Initial Load, In Per Unit of
Hours
Self-Cooled 0.5 ~ 25 Transformer Rating
Water-cooled 0.5 25 0.90 0.70 0.50~0.90/0.70 0.50; 0.90 o.io 0.50
Forced-Air-Cooled 0.4 20 - __~
Forced-Oil-Coolf,tl 0.4 20 0.5 1.59 1.77 1.89 1.45 1.58 Gq 1.36 1.47 1.50
operatmg kva
1 1.40 1.54 1.60 1.31 1.38 1.50; 1.24 1.31 1.34
'Here. percentcapwlty factor is equal to rated kY3 X100. averaged through- 2 1.24 1.33 1.37 1.19 1.23 1.261 1.14 1.18 1.21
cut n ?4-hour period. 4 1.12 1.17 1.19 1.11 1.13 1.15,1.0!) 1.10 1.10
8 1.06/1.08/1.0801.06~1.0711.07~/1.0511.0S~1.06
as a function of capacity factor, based on a normal trans- ,.
temperatures of 30C for air and 25C fur water are assun~ed through-
former life expectancy, is given in Table 8. ^ L^LI^

25. Loading Based on Short-Time Overloads


Short-time loads which occur not more than once during
any 24-hour period may be in excess of the transformer
rating without causing any predictable reduction in trans- theoretical conditions and limitations described in Table
former life. The permissible load is a function of the aver- 10(b). These conditions were chosen to give results con-
age load previous to the period of above-rated loading, taining some probable margin, when compared with most
according to Table 9. The load increase based on capacity conventional transformer designs. For special designs, or
factor and the increase based on short-time overloads can- for a more detailed check on some particular unit, the
not be applied concurrently; it is necessary to chose one hottest-spot copper temperature can be calculated by the
method or the other. method shown in section 19, and the probable sacrifice in
Short time loads larger than those shown in Table 9 transformer life can then be estimated from Table 11.
will cause a decrease in probable transformer life, but the
amount of the decrease is difficult to predict in general 26. Limiting of Load by Automatic Control
terms. Some estimate of the sacrifice in transformer life The loading of a transformer can be supervised by con-
can be obtained from Table 10(a) which is based on the trol devices to insure that hottest-spot copper temperatures

TABLE 10(a)-PERMISSIBLE SHORT-TIME TRANSFORMER LOADING, BASED ON REDUCED LIFE EXPECTANCY

Following 50 percent or less of rated kva@ 1 Following 100 percent of rated kvacb’

Type of Period of Increased Probable Sacrifice In Percent of Normal Life Caused By Each Overload
-
Cooling Loading Hours 0.10 1 0.25 / 0.50 / 1.00 / 0.10 1 0.25 / 0.50 / 1.00

blaximum Load In Per Unit Of Transformer Rating

0.5 2.00 2.00 2.00 2.00 1.75 1.92 2.00 2.00


OA 1.0 1.76 1.91 2.00 2.00 1.54 1.69 1.81 1.92
2.0 1.50 1.62 1.72 1.82 1.35 1.48 1.58 1.68
CG 4.0 1.27 1.38 1.46 1.53 1.20 1.32 1.40 1.48
8.0 1.13 1.21 1.30 1.37 1.11 1.20 1.28 1.35
24.0 1.05 1.10 1.15 1.23 1.05 1.09 1.15 1.23

0.5 1.97 2.00 2.00 2.00 1.67 1.82 1.94 2.00


1.0 1.66 1.79 1.90 2.00 1.47 1.60 l.il 1.81
OA/FA@’ 2.0 1.39 1.51 1.59 1.68 1.29 1.41 1.50 1 58
4.0 1.21 1.31 1.38 1.45 1.18 1 28 1.35 1.43
8.0 1.11 1.19 1.26 1.33 1.10 1.18 1.26 1.33
24.0 1.05 1.09 1.15 1.22 1.05 1.09 1.15 1.21

0.5 1.78 1.92 2.00 2.00 1.56 1.70 1.80 1.90


OA/FA/FOA’“’ 1.0 1.53 1.64 1.73 1.82 1.39 1.50 1.59 1.69
2.0 1.32 1.42 1.49 1.57 1.26 1.36 1.43 1.51
FE:, 4.0 1.18 1.26 1.33 1.40 1.16 1.25 1.32 1.39
8.0 1.10 1.17 1.24 1.31 1.10 1.18 1.24 1.31
24.0 _.--
I n.; 1.14 1.20 1.05 1.09 1.14 1.20
(a) More basically. following a top-oil rise of 25 C for OA and ( rise for OA, A/FOAsnd 3A units.
(h) More husicntly. following B top-oil rise of 45 C for OA and ( rise for OA, A/FOA and 3A units.
CC) Based on the FA kva rating.
(d) Baaed on the FOA kvn rating.
Chapter 5 Power Transformers and Reactors 115

TABLE 10(b)-CONDITIONSAND TRANSFORMERCHARACTERISTICS LIGHTNING


ASSUMEDINTHE PREPARATIONOFTABLE IO(a)

0.4 OA/FA/FOA
OA/FA FOA
OW
FOW
Hottest-spot rise (C) 6.5 65 65
Top-oil rise (C) 45 45 40
Time constant at full load
(hours) 3.0 2.0 1.5
Ratio of full load copperto iroo
loss 2.5 3.5 5.0
Ambient temperature=30 C.
,\Inximum oil temperature
= 100c.a Fig. 20--Single-line diagram of CSP power transformer,
Rlaximum hottest-spot copper
temperature = 150 C.
.\lnximum short-time loading IX. THE COMPLETELY SELF-PROTECTED
=200 percent.b TRANSFORMER
(n) Basedon provision for oil expansion, and inert gas above the oil.
(b) Short-time loading for one-half hour or more. Terminals or tap-changers A power transformer design may include protective de-
might in some cases impose a limit lower than 200 percent.
vices capable of preventing damage to the unit when it is
subjected to electrical conditions that would probably
damage conventional transformers. Also, standard switch-
TABLETS--PROBABLE SACRIFICEIN TRANSFORMERLIFE ing, metering, and voltage regulating functions may be
CAUSEDBY PROLONGEDHOTTEST-SPOTCOPPERTEMPERATURE
included within a power transformer assembly. When
1 0.10 1 0.25 j 0.50 1 1.00 these protective, switching, and metering features are all
Period of combined at the factory within a single unit,, as indicated
High Temperature In DegreesCentigrade in Fig. 20, it may be designated a CSP power transformer.
Temperature, To SacrificeXot bIore Than The
hours Lightning Protection-Coordinated arresters are in-
Above Perc$nt of Xormal Life stalled to protect both high- and low-voltage circuits from
0.5 132 142 150 lightning or other voltage surges.
1.0 124 134 142 150
2.0 117 126 134 142
4.0 111 119 126 134
8.0 105 112 119 126
24.0 99 1 104 109 115

are always within a permissible range and duration. This


control may be accomplished with a thermal relay respon-
sive to both top-oil temperature and to the direct heating
effect of load current. The thermostatic element of this
relay is immersed in the hot transformer oil, and it, also
carries a current proportional to load current: in this way
the temperature of the element is geared to the total tem-
pcrature that, the transformer winding attains during oper-
xtion. The relay can be arranged to close several sets of
contacts in succession as the copper temperature climbs
with increasing load: the first, contacts to close can start
fans or pumps for auxiliary cooling, the next contacts can
warn of temperatures approaching the maximum safe limit,,
:lntf the final contacts can trip a circuit breaker to remove
load from the transformer.
Loading by copper temperature makes available the
short-time overload capacity of a power transformer, so
that emergency loads can be carried without interruption
of power service, and so that peak loads can be carried
without the use of over-size transformers.’ The thermal
relay can be coordinated with each transformer design to
_~I..
\rnlch it is applied, and it can inherently follow unpre-
dictable factors that affect permissible safe loading for a Fig. 21-Fully assembled 3000 kva, 33-4.16 kv CSP power
particular installation. transformer.
Power Transformers and Reactors Chapter 5

vided in the high-voltage winding. Tap-changing-under-


load equipment for the secondary circuit may be built into
the transformer housing.
Metering-Watthour meters and ammeters are usually
supplied for circuit metering.
CSP transformers are available in kva ratings up to
3000, primary voltages up to 69 kv, and secondary voltages
up to 15 kv. The units may be used to supply distribution
circuits from high-voltage lines in either industrial or elec-
tric utility applications; if one unit is used individually on
a radial circuit, a by-passing switch can be supplied across
the low-voltage circuit breaker to permit withdrawal and
maintenance of the breaker without a service interruption.

X. AUTOTRANSFORMERS
27. Two-Winding Autotransformer Theory
The single-phase two-winding autotransformer contains
a primary winding and a secondary winding on a common
core, just as a conventional two-winding transformer does.
However, in the autotransformer the two windings are
Fig. 22-Installation view of 1500 kva, 13.2-4.33 kv CSP power interconnected so that the kva to be transformed by actual
transformer. magnetic coupling is only a portion of the total kvn trans-
mitted through the circuit to which the transformer is
Internal Fault Protection-Fusible protective links connected. Autotransformers are normally rated in terms
of high interrupting capacity are connected between the of circuit kva, without reference to the internal winding kva.
high-voltage bushings and the winding, so that the supply The autotransformer circuit shown in Fig. 24 contains
circuit can be cleared from internal transformer faults.
Overload Protection-A thermal relay, responsive to
copper temperature (see section 26), operates to trip the
secondary circuit breaker before damaging temperatures
develop in the winding.
Relaying-Overcurrent relays normally are provided in
the low-voltage circuit to protect for secondary faults.
Circuit Breaker-Load switching is accomplished by
a circuit breaker in the low-voltage circuit of the trans-
former.
Voltage Regulation-Standard no-load taps are pro-
Fig. 24-Circuit for a two-winding autotransformer.

a primary winding P which is common to both low- and


high-voltage circuits, and a secondary winding S which is
connected directly in series with the high-voltage circuit.
Under no-load conditions, high-side circuit voltage E’, will
be the sum of the primary and secondary winding voltages;
low-side circuit voltage E, will be equal to the primary
winding voltage. The relation between primary and sec-
ondary winding voltages will depend upon the turns ratio
z between these windings.

“=+?a
E,
-= =l+Z=N. (33)
E, Es
%N-1. (34)
n1
Here N is the overall voltage ratio between high- and low-
Fig. 23-Portable substation rated 2000 kva,‘72 000/24 OOO- voltage circuits.
2.5/4.33/5.0/7.5 kv, shown in operation at a substation site. When the transformer is carrying load current, the
Chapter 5 Power Transformers and Reactors 117

primary ampere-turns should essentially balance the


secondary ampere-turns (noting that Ils=Is) :
nJ, = nJs = nJ, (35)

I,’ = n’Ip (36)


nc2

I,=Is+Ip=I~+nzI,‘=NI,‘=N~I~,~Ip. (37)
nl Q N-l
The total circuit kva is given by E,XI, or E,‘XI,’
(expressing voltages in kv), but the winding kva is given
b) DETERMINATION OF IMPEDANCE TEST
by E,XIP or ; E,xIs. The ratio between winding
0
kva (Up or Us) and circuit kva (UC) is, referring to equa-
tion (37)
up E,XIp
-=-= Ip N-l
(33)
UC E&XI, N I = iv’
( N-lP )
For example, an autotransformer rated 1000 kva, with 51
circuit voltage ratio of 22 kv to 33 kv N =g = 1.5 has m
( 22 )
equivalent two-winding kva of
(b) EOUIVALENT OF TEST CIRCUIT

I:N
The reduced rating of transformer parts required in an
autotransformer make it physically smaller, less costly,
and of higher efficiency than a conventional two-winding
unit for the same circuit kva rating. In the example just
cited, the autotransformer would theoretically be only as
large as a 333-kva conventional transformer, and this re- N=I+$
tluced kva would in practice furnish a fairly accurate basis
for estimating the cost of the lOOO-kva autotransformer. (c) CONVENTIONAL EQUIVALENT CIRCUIT
Total losses in the autotransformer would be comparable Fig. 25-Equivalent circuits for a two-winding autotrans-
to those in a 333-kva conventional transformer, so that former.
efficiency based on circuit transmitted power would be
quite high. From this, the conventional form of equivalent circuit is
An autotransformer will introduce series impedance, as shown in Fig. 25(c), where
well as current and voltage transformation, in the circuit
where it is connected. The series impedance may be evalu- z * = N-l 2xz PS. (41)
atcd by referring to Fig. 25(a); here the low-voltage circuit ( N >
terminals are short-circuited, so that the impedance meas- Sequence equivalent circuits for the three-phase two-wind-
ured at the high-voltage terminals will be equal to the series ing autotransformer are presented in the Appendix.
circuit impedance attributable to the autotransformer. The circuit impedance of an autotransformer is smaller
Sate that the circuit in Fig. 25(a) is exactly the same as the than that of a conventional two-winding unit of the same
circuit that would be used to measure the leakage impe- rating, as is evident from Eq. (41). This low series im-
dance if Zsp were defined as the ohmic impedance measured pedance, though advantageous in its effect on transformer
:rcross the secondary winding with the primary winding regulation, may allow excessive short-circuit currents
short-circuited. A circuit providing correct circuit voltage during system fault conditions. Often the through imped-
and current ratios, and also correct through impedance, is ance will be less than four percent based on the autotrans-
shown in Fig. 25(b). Two conversions may now be made, former nameplate kva rating, which means that three-
the first to move the series impedance to the low-voltage phase short circuit current could exceed the maximum
side, and the second to express impedance in terms of Zps. of twenty-five times normal rated current for two seconds
as permitted by standards. For this reason autotrans-
za=$2z; =$zsp. (39) formers, like voltage regulators, cannot always protect
themselves against excessive fault current; reactors or
Zsp= ; %ps= (N- l)%ps. other connected circuit elements may have to be relied on
(40)
0 for this protection.
118 Power Transformers and Reactors Chapter 5 1

28. The Three-Winding Autotransformer *,= nl(l+td+n?(l+t2)E


E,‘=E,+ (42)
Three-phase autotransformers for power service are 1 nl(l+td a*
usually star-star connected with the neutral grounded, and
in most of these cases it is desirable to have a third winding nl = turns on primary winding, not considering taps.
on the core delta-connected so as to carry the third har- R= turns on secondary winding, not considering
monic component of exciting current. This winding could taps.
be very small in capacity if it were required to carry only tl = fractional part of n1 included in primary winding
harmonic currents, but its size is increased by the require- tap (+ tlnl indicates additional turns)
ment that it carry high currents during system ground t2= fractional part of nZ included in secondary wind-
faults. A widely used rule sets the delta-winding rating at ing tap. (+tznz indicates additional turns).
35 percent of the autotransformer equivalent two-wind- If E, is assumed constant at 1.0 per unit based on normal
ing kva rating (not circuit kva rating). rated low-side circuit voltage, three cases are possible:
Since it is necessary in most cases to have a delta-con- (1) Taps in secondary winding only:
nected tertiary winding, it is often advantageous to design
this winding so that load can be taken from it. This re- E,‘=l+;+tz3 (43)
sults in a three-winding autotransformer with terminals to nl
accommodate three external circuits. The equivalent cir- In this case the transformer volts per turn remain 1
cuit for this type of transformer is given in section 59 of normal. The percent change in E,’ is: 1
this chapter.
29. Autotransformer Taps AE& = tr---- n2 100. (44)
nl+n2
It is frequently necessary to place taps in the windings
of an autotransformer to regulate either or both circuit (2) Taps in primary winding only:
voltages. It is not advisable to place taps adjacent to the
line connections for voltages above 22 000 volts, because (45)
extra insulation is necessary on turns adjacent to the line
terminals. If taps were placed at the ends of the winding, The transformer volts per turn are times their
additional padding would be required throughout the
tapped section. Furthermore, taps placed adjacent to the normal value. The percent change in EJ is:
line, where the most severe voltage stresses occur, con- tl x n2
stitute a weakness that can be avoided by placing the taps A&‘= -- -100. (46)
l+tl nlfn2
in the middle of the winding as shown in Fig. 26. Taps
(3) Taps in both primary and secondary windings:
E,‘=l 1 n2 1 t2-t1~%
4 m l+tl 121

As in case (2), the transformer volts per turn are


1
times their normal value. The percent change in
6)1+11
E,’ is:
0 NORMAL TAP E: 3
4
AE;=tz--tlx~l()(). (4%
l+tl nl+n2

If El is assumed constant at 1.0 per unit based on normal


rated high-side circuit voltage, and E, is allowed to vary,
ElY
three more cases are possible:
(4) Taps in secondary winding only:
&L?L-A!- n2t2
(4%
0 a nl+n2 nl+lzzXnl+n41+t2)

Fig. 26-Autotransformer taps. nltnz times


The transformer volts per turn are
nl+n2(l+t2) >
their normal value.
may be placed in either the primary (common) winding, The percent change in E, will be:
or in the secondary (series) winding, or in both windings:
however, some tap combinations are more desirable than AE,=-& n2 100. (50)
others, if the transformer materials are to be used most nl+n2U+t2)
effectively.
(5) Taps in primary winding only:
The low-side and high-side circuit voltages may be
related, under no-load conditions, by an equation which m nl n2tl
(51)
E,=------ -
takes account of both primary and secondary taps: nl+~+nl+n2xnl(l+tl)+na
chapter 5 Power Transformers and Reactors 119

%f%
Transformer volts per turn are times D a
%(l+tl)+nz
b .b
their normal Vahe.
The percent change in E,’ is: c c

AE,=tln1(lSh)Sn2
n2 100.

(6) Tups in both primary and secondary:


E,2!L+zx n2(4 - t2)
(53)
nlfn2 nl+n2 n1(l+t~)+n2(l+Q)’
nlfn2
777 Y
Transformer volts per turn are
( nl(l+tl)+nz(l+tz) )
times their normal value. The percent change in Ed is:
n2(t1--2) (a ) STAR -DELTA (b) INTERCONNECTED-STAR
100. (54 GROUNDING-TRANSFORMER GROUNDING TRANSFORMER
‘~‘=nl(l+tl)+n2(l+tz)
WINDINGS DRAWN PARALLEL
lf the transformer were designed for constant volts per ARE ON THE SAME CORE

furn (t2= -tlz), then the percent change in E, would be:


a b
A,?, = tlX 100. (55)
lt is often advisable to specify a tap combination which
,,qll allow the autotransformer to operate at practically .
(:()rist,nnt volts-per-turn, regardless of tap position. As
;
inclicated in some of the cases above, a tap change in
c)rily one Gnding may be less effective than would normally
1)~ anticipated, because of the nullifying effect of the
:tccompanying change in volts-per-turn. Also, a significant
incrcnse in volts-per-turn at some tap setting would be
rcllccted in a magnetic core of larger size than otherwise
ncccssary.
30. Autotransformer Operating Characteristics
An autotransformer inherently provides a metallic con- (c) SCHEMATIC WINDING ARRANGEMENT OF AN INTER-
ncction between its low- and high-voltage circuits; this ia CONNECTED-STAR GROUNDING TRANSFORMER OF THE
lnilike the conventional two-winding transformer which THREE-PHASE CORE-FORM CONSTRUCTION
isolates the two circuits. Unless the potential to ground
ol’ each autotransformer circuit is fixed by some means,
Ihc low-voltage circuit will be subject to overvoltages
originating in the high-voltage circuit. These undesirable
(4fcct,scan be minimized by connecting the neutral of the
:ultotr:msformer solidly to ground. If the neutral of an
:urtotransformer is always to be grounded in service, an
intluccd potential shop test is more appropriate than an
:Wied potential test, because it represents more closely
11~ field operating conditions; building a grounded auto-
tr:msformer to withstand a full-voltage applied potential
((‘St mould not be economical because of the excess insula-
ticll near the neutral.
‘1’0 summarize the preceding discussion, the autotrans-
former has advantages of lower cost, higher efficiency, and
h(‘ttcr regulation as compared with the two-winding trans-
former; it has disadvantages including low reactance which
In:lY make it subject to excessive short-circuit currents, the
ari’:Lngement of taps is more complicated, the delta tertiary
*‘l;lY have to carry fault currents exceeding its standard
(d) EOUIVALENT CIRCUIT OF AN INTERCONNECTED-STAR
rating, the low- and high-voltage circuits cannot be iso- GROUNDING TRANSFORMER
bed , and the two circuits must operate with no angular
Phase displacement unless a zig-zag connection is intro- Fig. 27-Star-delta and zig-zag grounding transformers.
duced. The advantages of lower cost and improved effi-
Power Transformers and Reactors

ciency become less apparent as the transformation ratio Table 12-“K” FACTORS FOR DETERMINING EQUIVALENT
increases, so that autotransformers for power purposes are TWO-WINDING 55 C KVA OF GROUNDING TRANSFORMERS*
usually used for low transformation ratios, rarely exceeding
Star-Delta Zig-Zag Connection
2 to 1. Time
Rating ‘;I;‘- ;:;tkq,3f~~v~ 46 kv 1 69 kv 1 92 kv
XI. GROUNDING TRANSFORMERS
Ka, For A Three Phase Unit
A grounding transformer is a transformer intended solely
for establishing a neutral ground connection on a three- 10 seconds 0.064 0.076 1 0.080 0.085 0.092
phase system. The transformer is usually of the star-delta 1 minute 0.170 0.104 0.110 0.113 0.118 0.122
2 minutes 0.240 0.139 0.153 0.160 0.167 0.174
or interconnected-star (zig-zag) arrangement as shown in 3 minutes 0.295 0.170 0.187 0.196 0.204 0.212
Fig. 27. 4 minutes 0.340 0.196 0.216 0.225 0.235 0.245
The kva rating of a three-phase grounding transformer, 5 minutes 0.380 0.220 0.242 0.253 0.264 0.275
or of a grounding bank, is the product of normal line-to-
K1, For A Single Phase Unit (One of three in a bank)
neuh-al voltage (kv) and the neutral orgrozbnd amperes that
the transformer is designed to carry under fault conditions 1 minute 0.057 0.033 0.03i 0.040 0.043 0.046
for a specified time. A one-minute time rating is often used 2 minutes 0.080 0.046 0.051 0.055 0.060 0.064
for grounding transformers, though other ratings such as 3 minutes 0.098 0.057 0.064 0.068 0.074 0.080
those suggested in AIEE Standard for “Xeutral Grounding 4 minutes 0.113 0.065 0.073 0.078 0.084 0.091
Devices” (No. 32, May 1947) can be specified depending 5 minutes 0.127 O.Oi.7 0.082 0.088 0.005 0.102
*These valuev are cnlculated on the basis that the initial uve~we winding tem-
upon the probable duty to be imposed on the unit in perature is not over 7.5’2. that the heat from load lossev is nil stored in the tram+
service. former. and that the final
ards. The values are applicable
temperature will not
only for groundinp
ruceed VZLIUBY
trsnsformers
permitted by stand-
designed to have
Rated voltage of a grounding transformer is the line-to- 100 percent impedance.

line voltage for which the unit is designed.


When operated at rated three-phase balanced voltage, classes of grounding transformers; the table includes values
only exciting current circulates in the windings of a ground- for both three-phase and single-phase units, though the
ing transformer. Current of appreciable magnitude begins single-phase type is uncommon.
to flow in the grounding circuit only when a fault involving Conventional power transformers may be connected to
ground develops on the connected system. serve solely as grounding transformers, but the current and
Grounding transformers, particularly the zig-zag type, time ratings for grounding service are open to question
normally are designed so that rated neutral current flows depending upon the form and details of construction. When
when a solid single-line-to-ground fault is applied at the these modified ratings are desired, they should be obtained
transformer terminals, assuming supply voltage to be fully from the transformer manufacturer.
maintained. This is equivalent to loo-percent zero-sequence Star-Delta Impedances-The impedance to zero-
voltage impressed at the transformer terminals resulting in sequence currents in each phase of a solidly-grounded star-
the circulation of rated neutral current. Transformers so delta grounding bank made up of single-phase units is
designed are said to have loo-percent impedance based on equal to Zrs, the ohmic leakage impedance between one
rated kva and rated voltage. primary (star) . winding and the corresponding secondary
Sometimes a resistor or other impedance is connected (delta) winding:
in the transformer neutral, and in these cases it may be ZO=ZPS
desirable to specify that the grounding transformer shall
have less than the conventional 100 percent impedance. Percent zero-sequence impedance is normally expressed ir
Equivalent circuits for star-delta and zig-zag grounding terms of short-time kva and line-to-line voltage:
transformers with external neutral impedance are includ- ZPS x UG
ed in the Appendix. Zo%= (59’
Because a grounding transformer is a short-time device, 10 x kv2
its size and cost are less than for a continuous duty trans- In a three-phase star-delta grounding transformer 20 ma:
former of equal kva rating. The reduced size can be estab- be smaller than Zps by an amount depending on the forn
lished in terms of an “equivalent two-winding 55 C kva” of core construction: a typical ratio of 20 to Zps is 0.85
U, by applying a reduction factor K to the short-time though variation from this value for different design’
rated kva of the grounding transformer, and this reduced is likely.
kva can be used for a price estimate. Zig-zag Impedances-The impedance to zero
U, = Uo X KS for a three-phase grounding unit. (56) sequence currents in each phase of a solidly groundec
zig-zag bank can be derived on a theoretical basis b:
U, = 3 Uo X Kl for a bank of single-phase grounding
reference to Fig. 27(d).
units (57)
Eo=IoXZp~--ep+ep. 030
where
U, = equivalent two-winding ,55C kva, three-phase. El
T=Zo=Zps.
UC= (line-to-neutral kv) X (rated neutral amperes). 0
Values for K are listed in Table 12 for various types and Percent zero-sequence impedance for the zig-zag connec
chapter 5 Power Transformers and Reactors

t,ion
_~ is normally expressed in terms of short-time kvs and 31. The UT Mechanism
line-to-line voltage: Figure 28 illustrates schematically the operation of the
ZPSX cc type UT mechanism for changing taps under load. Taps
Z,% = from the transformer winding connect to selector switch-
10xkv2
es 1 through 9. The selector switches are connected to
load transfer switches R, S, and T. The connections for
XII. TAP CHANGING UNDER LOAD the tap changer positions are shown on the sequence
The modern load tap changer had its beginning in 1925. chart of Fig. 28. The sequence of switching is so coordi-
Since that time the development of more complicated nated by the tap changing mechanism that the transfer
t,ransmission networks has made tap changing under load switches perform all the switching operations, opening
,norc and more essential to control the in-phase voltage of before and closing after the selector switches. All arcing
l,olvcr transformers, and in other cases to control the phase is thusarestricted to switches R, S, and T, while switches
ar,glc relation. Tap-changing-under-load equipment is ap- 1 to 9 merely select the transformer tap to which the load
nlicd to power transformers to maintain a constant second- is to be transferred.
LLryvoltage with a variable primary voltage; to control the When the tap changer is on odd-numbered positions, the
secondary voltage with a fixed primary voltage; to control preventive auto-transformer is short-circuited. On all even-
tlrc flow of reactive kva between two generating systems, numbered positions, the preventive auto-transformer
,,r adjust the reactive flow between branches of loop cir- bridges two transformer taps. In this position, the rela-
crrits; and to control the division of power between branches tively high reactance of the preventive auto-transformer
of loop circuits by shifting the phase-angle position of to circulating currents between adjacent taps prevents
(r:msformer output voltages. damage to the transformer winding, while its relatively
Various types of tap-changing equipment and circuits low impedance to the load current permits operation on
:u-c used depending upon the voltage and kva and also this position to obtain voltages midway between the
~rpon whether voltage or phase angle control is required. transformer taps.
ITntlcr-load-tap-changers are built for 8, 16, and 32 steps,
\vit,h the trend in recent years being toward the larger 32. The UNR Mechanism
n~rmber of steps so as to give a finer degree of regulation. Fig. 29 shows schematically the diagram of connections
‘t’hc usual range of regulation is plus 10 percent and minus and sequence of operations of the type USR tap changer.
IO percent of the rated line voltage, with plus and minus The operation of the selector and transfer switches is es-
‘ii percent and plus and minus 5 percent being second and actly as described for the type UT tap changer. But the
third, respectively, in popularity. The 32 step, plus and type UNR tap changer also has a reversing switch which
minus 10 percent, tap-changing-under-load equipment has reverses the connections to the tapped section of the
such wide acceptance as to be considered standard for winding so that the same range and number of positions
many types of transformers.

AUTO TRANSFORMER
PREVENTIVE
\
AUTOTRANSFORMER
REVERSING
,’ ,
SWITCHES

TRANSFER
T
SWITCHES- (, n I,
--R-+ s -’ I
1

;xI^ SELECTOR
I
swlTcHEs
SEQUENCE OF OPERATION
SEQUENCE OF OPERATION

O= SWITCH CLOSED
Fi& 28-Seventeen position, single-phase, Type UT tap Fig. 2!3--Seventeen position, single phase, Type UNR tap
changer. changer.
122 Power Transformers and Reactors Chapter 5

can be obtained with one-half the number of tap sections,


or twice the range can be obtained with the same number
of taps. The reversing switch is a close-before-open switch
which operates at the time there is no voltage across (a)
its contacts. A

33. The URS Mechanism


8: --- B
/
The type URS load tap changer is applied to small power
transformers and large distribution transformers. The 9
transfer switches are eliminated, and each selector switch I
serves as a t,rnnsfer switch for the tap to which it is con-
nected. The schematic circuit diagram and operations YP
0
sequence chart is shown in Fig. 30.

REVERSING SWITCH- Fig. dl-Power interchange between systems:


sm (a) Two systems with tic.
(h) Vector diagram of voltages during interchange of power.
(c) Introduction of an in phase voltage, BC, to correct for exces-
sive voltage drop.

kilowatts must go over the tie line to B. An increase in


generator outDut bv A must be accomDanied bv a corres-
ponding decreise in”output (increase in input) b; B if there
I SEPUENCE OF OPERATION I
is to be no change in system frequency. The transmission
of Dolyer from A to B results in a difference in marrnitude
between terminal voltages and also a shift in phasl angle,
as illustrated in Fig. 31 (b). .-IO is the terminal voltage at
9, BO is the terminal voltage at B, .4B is the vectorial volt-
age drop from A to B, created by the flow of load current I,
and 0 is the phase-angle difference between terminal volt-
ages. In actual practice the phase angle is not always appa-
rent, but the drop in voltage, AB’, is often objectionable. An
attempt to maintain satisfactory terminal voltages at A
and B will often result in undesirable circulation of reactive
kva between the svstems. The flow of Dower from -4 to B.
or vice versa, is ditermined by the governor settings. Thl
flow of reactive power over the interconnecting line is
O=SWITCH CLOSED determined bv the terminal voltages held bv the machine
Fig. 30-Thirty-three position, single-phase, Type URS tap excitations at A and B. Excessive voltage drop between
changer. the systems can be readily corrected by transformer taps
of a fixed nature or by tap-changing equipment, introduc-
Physically, the stationary selector switch contacts are
SERIES
arranged in circles, one for each phase. The moving s&- TRANSFORMER
a a’
lector switch contacts, as they rotate about a center shaft,
both select the taps and make contact with them. The I I
reversing switch operates when the selector switches are b b’
on position 17, at which time there is no current through
the reversing switches and therefore no arcing on them.
The URS tap changer, like the other load tap changers,
can be equipped for hand operation, remote manual opera-
tion, or for full automatic operation under the control
of relays.

XIII. REGULATING TRANSFORMERS FOR


VOLTAGE AND PHASE ANGLE CONTROL
Consider two systems A and B in Fig. 31 connected by a I I ,
single transmission circuit. A and B may both be generat- I
ing units, or one of them may be a generating unit and the EXCITING
other a load. Should A generate 10 000 kilowatts in excess TRANSFORMER
of its own load. there can be but one result.~I the
~~ 10
~- 000
-~~ Fig. 32-Regulating transformer for voltage control;
chapter 5 Power Transformers and Reactors 123

ing an in-phase voltage, BC, to compensate for the voltage delta power transformation in that the angle of phase shift
drop and bring the terminal voltage at B to a desired value. of current and voltage is not fixed but depends on the
Figure 32 is a simplified sketch of a regulating transformer tap position. Figure 34 is a schematic diagram of a typical
for voltage control, usin,v an exciting autotransformer xvith regulating transformer for phase angle control.
automatic tap changing equipment indicated by the arron-s.
Consider three systems interconnected with each other a
a’
8o that the interconnections from A to B, from B to C, and
from C to A form a closed loop, as in Fig. 33 (a). An

B
A

4 (4 c
Fig. 34-Regulating transformer for phase-angle control.

In general the distribution of real power flow over the


various interconnections found in loop circuits can be con-
trolled by regulators for phase-angle control. The flow of
reactive kva can be controlled by regulators for voltage
control. The preceding statements follow from the fact

bB0 *TtB 0
that transmission-circuit impedances are predominantly
reactive. The voltage regulator introduces a series in-phase
voltage into the loop, and quadrature current (reactive
(b) (cl 4 kva) is circulated around the loop since the impedances
Fig. 33-Power interchange with three interconnected are reactive. The regulator for phase-angle control intro-
systems. duces a quadrature series voltage in the loop resulting in
the flow of currents lagging the impressed voltage by nearly
ctnt,ircly new element enters, and adjustment of governors 90 degrees, or the circulation of in-phase currents (kw).
\viII not entirely control the flow of power over any one For the case of correcting the voltage for line drop, a
OI t,hc interconnecting lines. An attempt to adjust load on simple voltage control equipment can be used. This simply
I 110tic between two systems results in a change of load on adds or subtracts a voltage in phase with the system volt-
I.IIOother two tie lines. With the tie line from B to C open, age. For the case of phase-angle control, the equipment
;tntl with power transmitted from A to B, the terminal can be identical except the voltage selected to add or sub-
volttlges of A and C will be equal and in phase, with no tract is in quadrature. As the earlier discussion showed,
power being transmitted from A to C, or vice versa (see there are cases where both voltage and phase angle control
Fig. 33 (b)). There now exists between B and C a difference
SERIES
in voltage and a difference in phase angle. If the tie line
1)ctwecn B and C is closed under these conditions there is a a
rctlistribution of power flow between A and B, a part going 1
wcr the line from A to B, and a part of the power going
from rl to B over the lines A-C and C-B (seeFig. 33 (c)).
‘UK distribution of power, both kw and reactive kva be-
I.\\oen the various lines is determined solely by the relative
ilnPcclances of the interconnecting lines.
1f at the time of closing B-C an adjustment of trans-
former taps were made, or a regulating transformer for
vo1t:lge control were inserted in the loop, it would be
Possible to make the voltage at C equal in magnitude to
t1l:it at B but it would not have the same phase relation-
ship. There would still be a flow of power from A to C
ml from C to B.
Conditions similar to that just described occur on inter-
“onnccted systems involving loop circuits. To control the
circu1ation of kw and prevent overloading certain lines it
is often necessary to introduce a quadrature voltage, any
place in the loop, by the use of a regulating transformer Fig. 35-Regulating transformer for independent phase-angle
for phase-angle control. This differs from the usual star- and voltage control.
124 Power Transformers and Reactors Chapter 5

ample, refer to F-7 in Table 7 of the Appendix, which is


the regulating transformer for phase-angle control shown
in Fig. 34.
For positive-sequence, neglecting regulator impedance:
-..

where a = tan-‘&n
For negative-sequence neglecting regulator impedance:
E: = Ne-jaE2 = 2/l f3n2e-jaE2 (63)
1
I~=-E-j~12= d&3n2ti.lr (06)
N
For zero-sequence, neglecting regulator impedance:
Ed = E, (67)
r:=I” ((33)
For this regulator zero-sequence voltage and current
are not transformed; IO flows through the regulator as
though it were a reactor.
Fig. 36-Regulating transformer for voltage control, rated
20 000 kva, 12.47 kv, plus or minus 10 percent. It happens with several connections of regulating trans-
formers that zero-sequence voltages and currents are not
transformed at all, as in F-7; or are transformed with a
are required. There are a number of combinations of con- different transformation ratio than for positive- or nega-
nections to accomplish this, one of them being shown in tive-sequence quantities as in G-l. This phenomenon, and
Fig. 35. Where the voltage and phase angle bear a close the use of the sequence equivalent circuits for regulating
relation, one mechanism may suffice. However, where com- transformers has been discussed in papers by Hobson and
pletely independent control is desired, two mechanisms Lewis2, and by ,J. E. Clem.8
with two regulating windings and one series winding, or
with one regulating winding and two series windings are
necessary. If it is desired to close the loop, and the flow
XIV. EXCITING AND INRUSH CURRENTS
of both real and reactive power over the various lines If normal voltage is impressed across the primary ter-
forming the loop must be controlled, the economical loca- minals of a transformer with its secondary open-circuited,
tion for the control equipment is at the point of lowest a small exciting current flows. This exciting current con-
load to be transferred. This may dictate the location in a sists of two components, the loss component and the mag-
loop, unless when in tying several companies together the netizing component. The loss component is in phase with
boundary between systems determines the location. The the impressed voltage, and its magnitude depends upon the
voltage to be added or the phase-angle shift that must no-load losses of the transformer. The magnetizing com-
be obtained can be determined by calculation, considering ponent lags the impressed voltage by 90 electrical degrees,
the impedances of the tie line and the load conditions in and its magnitude depends upon the number of turns in
the loop. When such calculations become involved, the the primary winding, the shape of the transformer satura-
use of the network calculator provides a quick and accur- tion curve and the maximum flux density for which the
ate tool for obtaining the solution. transformer was designed. A brief discussion of each of
Several common connections used for regulating trans- these components follows:
formers providing voltage control, phase angle control, or
combined voltage and phase angle control, are tabulated 34. Magnetizing Component of Exciting Current
in the Appendix under Equivalent Circuits of Power and If the secondary of the transformer is open, the trans-
Regulating Transformers. The equivalent circuits of the former can be treated as an iron-core reactor. The dif-
regulating transformers to positive-, negative-, and zero- ferential equation for the circuit consisting of the supply
sequence are given. It should be noted that the equivalent and. the transformer can be written as follows:
circuits for phase-angle control regulators involve an ideal
transformer providing a phase shift of voltage and current. e=Ri+nl- d+ (69) j
Positive-sequence voltage and current are always shifted dt
by the same angle in the same direction. The angular shift where, e = instantaneous value of supply voltage I
for negative-sequence voltage and current is always equal i= instantaneous value of current
to the angular shift for positive-sequence, but is in the oppc- R=effective resistance of the winding 1I
site direction. Zero-sequence currents and voltages do not 4 = instantaneous flux threading primary winding
undergo an angular shift in being transformed. For ex- 721=primary turns i
I
Chapter 5 Power Transformers and Reactors 125

xormally the resistance, R, and the exciting current, i, energized. Under steady-state conditions this component
are small. Consequently the Ri term in the above equa- is equal to zero; the magnitude of & is discussed in
tion has little effect on the flux in the transformer and can, Sec. 38.
for the purpose of discussion, be neglected. Under these From Eq. (72) it can be seen that the normal steady-
conditions Eq. (69) can be rewritten: state flux is a sine wave and lags the sine wave supply
voltage by 90 degrees. The supply voltage and the normal
(70) flux are plotted in Fig. 37 as a function of time.
If there were no appreciable saturation in the magnetic
If the supply voltage is a sine wave voltage, circuit in a transformer, the magnetizing current and the
flux would vary in direct proportion, resulting in a sinu-
e=d/ZE sin(ol+X), (71) soidal magnetizing current wave in phase with the flus.
However, the economic design of a power transformer re-
,\hcrc, E = rms value of supply voltage quires that the transformer iron be worked at the curved
w=2nf part of the saturation curve, resulting in appreciable sat-
uration. Under this condition the magnetizing current
Sllbstituting in Eq. (70) is not a sine wave, and its shape depends upon the satu-
ration characteristics (the B-H curve) of the transformer
&‘E sin(ot+X) =n$$ magnetic circuit. The shape of the current wave can be
determined graphically as shown in Fig. 38. In Fig. 38(b)
Solving the above differential equation, are shown the impressed voltage and the flux wave lagging
+= -GE cos(wt+X)+& (72) the voltage by 90 degrees. For any flux the corresponding
value of current can be found from the B-H curve. Fol-
wnl
lowing this procedure the entire current wave can be
d/ZE plotted. The current found in this manner does not con-
In this solution, -~ cos (wt+X) is the normal
wnl sist of magnetizing current alone but includes a loss com-
stclady-state flux in the transformer core. The second ponent required to furnish the hysteresis loss of the core.
tctrrn, &, represents a transient component of flux the However, this component is quite small in comparison to
magnit,ude of which depends upon the instant at which the the magnetizing component and has little effect on the
tmnsformer is energized, the normal maximum flux and maximum value of the total current.
the residual flux in the core at the time the transformer is A study of Fig. 38 shows that although the flux is a sine
wave the current is a distorted wave. An analysis of this
IMPRESSED STEADY STATE current wave shows that it contains odd-harmonic com-
5 ponents of appreciable magnitude; the third harmonic
component is included in Fig. 38. In a typical case the
harmonics may be as follows: 45 percent third, 15 percent
fifth, three percent seventh, and smaller percentages of
higher frequency. The above components are expressed in
percent of the equivalent sine wave value of the total
exciting current. These percentages of harmonic currents
will not change much with changes in transformer terminal
voltage over the usual ranges in terminal voltage. In Fig.
39 are shown the variations in the harmonic content of the
Fig. 37--Impressed voltage and steady-state flux. exciting current for a particular grade of silicon steel.

IMPRESSED
- VOLTAGE

COMPONENT OF
EXCITING CURRENT

(0) TRANSFORMER 8-H CURVE (b) VOLTAGE, FLUX AND CURRENT WAVES

Fig. 38-Graphical method of determining magnetizing current.


Power Transformers and Reactors Chapter 5

92

go 20 60 100 MO 160 220 260 300 400


70 80 90 100 PERCENT OF NORMAL EXCITING CURRENT
PERCENT OF EQUIVALENT SINE WAVE
Fig. 40-Exciting current vs. terminal voltage. The above
curve applies for one particular design of transformer: the
Fig. 39-Harmonic content of exciting current for a particular
shape of the curve may vary considerably depending upon the
grade of silicon steel.
grade of steel and the transformer design.

35. Loss Component of Exciting Current inal voltage. For example, IO&percent terminal voltage
The no-load losses of a transformer are the iron losses, results in 200-percent exciting current.
a small dielectric loss, and the copper loss caused by the
exciting current. Usually only the iron losses, i.e., hys- 37. Typical Magnitudes of Exciting Current
teresis and eddy current losses, are important. These The actual magnitudes of exciting currents vary over
losses depend upon frequency, maximum flux density, and fairly wide ranges depending upon transformer size, volt-
the characteristics of the magnetic circuit. age class, etc. In Table 13 are given typical exciting
In practice the iron losses are determined from labora- currents for power transformers. The exciting currents
tory tests on samples of transformer steel. However, the vary directly with the voltage rating and inversely with
formulas given below are useful in showing the qualitative the kva rating.
effect of the various factors on loss.
TABLE 13
Iron loss = Whf W, (73) TYPICAL EXCITING CURRENTVALUES FOR SINGLE-PHASE
Wh = KJBx,,, watts per lb POWER TRANSFORMERS
We= K,fzt2Bzm,, watts per lb (In percent of full load current)
Wh = hysteresis loss The following values should be considered as very approximate for
We = eddy current loss average standard designs and are predicated on prevailing perform-
j= frequency ance characteristics. Test values will as a rule come below these
t = thickness of laminations
values but a plus or minus variation must be expected depending
upon purchaser’s requirements. Should closer estimating data be
Bm,, = maximum flux density
required, the matter should be referred to the proper manufacturer’s
Kh, K,, and x are factors that depend upon the quality design engineers.
of the steel used in the core. In the original derivation of Voltage Class (Full Insulation)
the hysteresis loss formula by Dr. Steinmetz, z was 1%. Three-phase
For modern steels 5 may have a value as high as 3.0. The KVA 2.5 Kv 15 Kv 25 Kv 69 Kv 1138Kv 161 Kv 230Kv
~--~--
iron loss in a GO-cycle power transformer of modern design 500 3.7% 3.770 3.876 4.97,
is approximately one watt per pound. The ratio of hys- 1 000 3.3 3.3 3.6 4.3
teresis loss to eddy current loss will be on the order of 3.0 2500 3.1 3.2 3.8
with silicon steel and K with oriented steel. These figures 5000 ._. 2.8 3.1 2.5’j’, 4.1 $‘J
should be used as a rough guide only, as they vary con- 10 000 3.0 3.1 2.4 3.6 4.0$&o*
siderably with transformer design. 25000 _. 2.2 2.4 3.1 3.9 3.5 *
50 000 .. 3.1 3.9 2.8 *.
36. Total Exciting Current *Reduced Insulation. j
As discussed above, the total exciting current of a trans-
former includes a magnetizing and a loss component. The 38. Inrush Current 4
economic design of a transformer dictates working the iron When a transformer is first energized, a transient ex-j
at the curved part of the saturation curve at normal volt- citing current flows to bridge the gap between the
age; hence any increase in terminal voltage above normal ditions existing before the transformer is energized
mill greatly increase the exciting current. In Fig. 40 the the conditions dictated by steady-state requiremen
exciting current of a typical transformer is given as a For any given transformer this transient current depe
function of the voltage applied to its terminals. The upon the magnitude of the supply voltage at the instant
exciting current increases far more rapidly than the term- the transformer is energized, the residual flux in the core,
chapter 5 Power Transformers and Reactors 127

and the impedance of the supply circuit. Often the mag-


nitude of this transient current exceeds full-load current
and may reach 8 to 10 times full-load current. These high
inrush currents are important principally because of their
effect on the operation of relays used for differential pro-
tection of transformers.
ln studying the phenomena that occur when a trans-
former is energized it is more satisfactory to determine the
plus in the magnetic circuit first and then derive the cur-
r(;nt from the flux. This procedure is preferable because
the flux does not depart much from a sine wave even
though the current wave is usually distorted.
The total flux in a transformer core is equal to the nor- VOLTAGE
mal steady-state flux plus a transient component of flux,
as shown in Eq. 72. This relation can be used to determine (Cl) PRIMARY CLOSED AT ZERO VOLTAGE-ZERO RESIDUAL FLUX.
the transient flux in the core of a transformer immediately
1/ZE
sftcr the transformer is energized. As ~ represents the
wnl
(rest of the normal steady-state flux, Eq. (72) can be
rewritten, TRANSIENT FLUX mTOTAL FLux
4= -An cos bt+X)+$bt (74)

.
,\t t=o,
40= -dh cos X+&o (75)
\v here +. = transformer residual flux
-4m cos X=steady-state flux at 1=0
. . .
dto= rnitial transrent flux.
111the above equation the angle X depends upon the
instantaneous value of the supply voltage at the instant
/ STEADY-STATE
b the transformer is energized. If the transformer is ener-
gized at zero voltage, h is equal to 0, whereas if the trans- VOLTAGE
former is energized where the supply voltage is at a posi-
tivc maximum value, X is equal to 90 degrees. Assume that (b) PRIMARY CLOSED AT ZERO VOLTAGE-
60% POSITIVE RESIDUAL FLUX.
a transformer having zero residual flux is energized when
the supply voltage is at a positive maximum. For these con- Fig. 41-Transformer flux during transient conditions.
ditions 4. and cos X are both equal to zero so +to is also
cc111slto zero. The transformer flux therefore starts out assumed for illustration only. Flux waves for any other
~~ntlcrnormal conditions and there would be no transient. initial conditions can be calculated in a similar manner
1lowever, if a transformer having zero residual is energized using Eq. (74).
:rt, zero supply voltage the following conditions exist:
39. Determination of Current Inrush
x=0
After the flux variation has been determined by the
-4, cos x= -$*
method described, the current wave can be obtained
+o=o graphically as shown in Fig. 42. In the case illustrated
ho = dh it was assumed that a transformer having zero residual
Substituting in Eq. (74) flux was energized at zero supply voltage; the flux there-
fore is equal to twice normal crest flux. For any flux the
c$= -dm CO6(ot)f$h (76) corresponding current can be obtained from the trans-
The flux wave represented by Eq. (76) is plotted in former B-H curve. Although the maximum flux is only
pig. 41a. The total flux wave consists of a sinusoidal flux twice its normal value, the current reaches a value equal
\vave plus a d-c flux wave and reaches a crest equal to to many times the maximum value of the normal trans-
twice the normal maximum flux. In this figure the tran- former exciting current. This high value of current is
sient flux has been assumed to have no decrement. if loss reached because of the high degree of saturation of the
is considered the transient flux decreases with time and the transformer magnetic circuit.
%st value of the total flux is less than shown. In Fig. 41 In the above discussion loss has been neglected in order
(b) similar waves have been plotted for a transformer to simplify the problem. Loss is important in an actual
having 60 percent positive residual flux and energized at transformer because it decreases the maximum inrush cur-
zero supply voltage. Sixty percent residual flux has been rent and reduces the exciting current to normal after a
128 Power Transformers and Reactors Chapter 5

lNRUSH CURRENT

COA-4 CURRENT
la) TRANSFORMER S-H CURVE tb) FLUX WAVE AND INRUSH CURRENT WAVE

Fig. 42-Graphical method of determining inrush current.

period of time. The losses that are effective are the resist- TABLE 14-APPROXIMATE INRUSH CURRENTS TO 60-CYCLE
ance loss of the supply circuit and the resistance and stray POWER TRANSFORMERS ENERGIZED FROM THE HIGH-VOLTAGE
SIDE
losses in the transformer. Figure 43 is an oscillogram of a
typical exciting-current inrush for a single-phase trans- Transformer Core Shell
former energized at the zero point on the supply voltage Rating Kva Form Form
wave.g The transient has a rapid decrement during the 2000 5-8
first few cycles and decays more slowly thereafter. The 10 000 4-7 2.5-5
damping coefficient, R/L, for this circuit is not constant 20 000 2.0-4
because of the variation of the transformer inductance Note: The crest inrush currents are expressed in per unit of crest full-load
current.
with saturation. During the first few current peaks, the
degree of saturation of the iron is high, making L low. The inrush currents to single-phase, 60-cycle transformers can
inductance of the transformer increases as the saturation be obtained from the data in Table 14. The values given
are based on the transformer being energized from the
high-voltage side at the instant the supply voltage passes
through zero. Energizing a core-form transformer from
the low-voltage side may result in inrush currrents ap-
proaching twice the values in the table. The per unit
inrush current to a shell-form transformer is approximately
the same on the high- and low-voltage sides.
The inrush currents in Table 14 are based on energizing
a transformer from a zero-reactance source. When it is
desired to give some weight to source reactance, the inrush
current may be estimated from the relation
~i!i- (77)
1fIoX
Fig. 43-Current inrush for a particular transformer ener- where
gized at zero voltage. 10= Inrush current neglecting supply reactance in
per unit of rated transformer current.
decreases, and hence the damping factor becomes smaller X=Effective supply reactance in per unit on the
as the current decays. transformer kva base.
40. Estimating Inrush Currents
XV. THIRD-HARMONIC COMPONENT OF
The calculation of the inrush current to a power trans- EXCITING CURRENT
former requires considerable detailed transformer design
information not readily available to the application en- 41. Suppression of the Third-Harmonic
gineer. For this reason reference should be made to the Component
manufacturer in those few cases where a reasonably ac- AS discussed in connection with Fig. 39, the exciting
curate estimate is required. An order of magnitude of current of a transformer contains appreciable harmonic
Chapter 5 Power Transformers and Reactors 129

current. The third harmonic is by far the largest harmonic interference, as affected by transformer connections, is
component, being as high as 40 to 50 percent of the given in Chapter 23, Sec. 11.
equivalent sine-wave exciting current.
If the flux in a transformer magnetic circuit is sinusoidal, 42. Effect of Transformer Connections
the esciting current must contain a third-harmonic com- The application of the above principles will be illustrated
ponent. If this component cannot flow, because of trans- by consideration of a number of typical connections. In
former or system connections, the flux will contain a third- Fig. 44 is shown a three-phase transformer bank connected
llarmonic component. The third-harmonic flux will, in
turn, induce a third-harmonic voltage in the transformer TABLETS-INFLUENCEOFTRANSFORMER
CONNECTIONSON
windings. The magnitude of the third-harmonic voltage THIRD-HARMONICVOLTAGESANLJ
CURRENTS
induced in a transformer winding, when the third-harmonic
current is suppressed, will vary between 5 and 50 percent I 1 TRANSFORMER 1
SOURCE CONNECTION COMMENTS
depending upon the type of transformers used. with single- PRIM. 1 SEC.
phase transformers or with three-phase shell-form trans-
formers the third-harmonic voltages may be as high as 50 II 1 A 1 A ) SEE NOTE I
percent of the fundamental-frequency voltage. In a three-
phase core-form transformer the reluctance of the third-
harmonic flux path is high (see Sec. 56); consequently the
third-harmonic flux in the transformer magnetic circuit is A &. II (I I,5
small even if the third-harmonic component of the exciting UNGROUNDED
current is suppressed. The third-harmonic voltage induced (SMALL CAPACITANCE .TO & 4 ” ‘1 1.5
is therefore small, usually not more than five percent. GROUND, NO GROUNDED
In a three-phase system, the third-harmonic currents of GENERATORS OR GROUNDED /I, n 01 II 3
each phase are in phase with each other and hence con- TRANSFORMER BANKS) I I I
stitute a zero-sequence set of currents of triple frequency.
I,ikebvise, the third-harmonic voltages will constitute a
zero-sequence set of voltages of triple frequency. Thus,
nlt,hough a third-harmonic voltage may be present in the
lint-to-neutral voltages, there can be no third-harmonic
component in the line-to-line voltage. The paths permit-
ting the flow of third-harmonic currents are determined
hy the system and transformer zero-sequence circuits.
5 It has been shown that third harmonics must occur in
either the exciting current or the voltage of a transformer.
The exciting current will take the shape imposed by the
particular connections used. It is always preferable to GROUNDED
have at least one delta-connected winding in a three- (GROUNDED GENERATORS OR
phase transformer bank. The delta connection will furnish GROUNDED TRANSFORMER
:L path for the flow of third-harmonic currents and will BANKS OR LARGE CAPACI-
minimize the third-harmonic current in the external cir- TANCE TO GROUND)
(Gts. This is very desirable because third-harmonic cur-
rcnt,s in the external circuits may, under some conditions,
cause telephone interference. A discussion of telephone

TRANSFORMER
POWER SOURCE
TRANSMISSION LINE

,-. Note:
1. The third-harmonic
third-harmonic component
2. The third-harmonic
may cause. interference
component

component
of the exciting
will be present in the transformer
of the exciting
due to possible coupling
current

current
with parallel
is suppressed and so a
line-to-ground voltages.
flows over the line and
telephone circuits.
3. The delta-connected winding furnishes a path for the third-harmonic exciting
currents required to eliminate the third-harmonic voltages. No third-harmonic cur-
rent will flow in the line between the source and the transformer and very little third-
(b) harmonic will be present in the system voltage.
4. The delta-connected winding furnishes B path for the third-harmonic exciting
currents required to eliminate the third-harmonic voltages. Very little third-
harmonic current will flow in the line and very little third-harmonic will be present
in the system voltage.
5. If the capacitance-to-ground of the circuit connected to the transformer
secondary is large. appreciable third-harmonic current can fiow in the secondary
windings. This factor will help decrease the magnitude of the third-harmonic volt-

O*
ages but may cause interference in telephone lines paralleling the secondary power
circuits. The same comments would apply if other ground sources are connected
to the secondary oircuit. Resonance with the secondary capacitance may produce
high harmonic voltages.
(d)
7 7 6. Some third-harmonic current can flow in the secondary windings if other
ground ~ouroes are present on the secondary side of the transformer bank. The
Fig. 44-40 nnections which influence the flow of third-har- magnitude of this current will depend upon the impedance of the ground sources
relative to the delta circuit impedance and is usually too small to cause trouble
monic exciting current. from telephone interlerence.
130 Power Transformers and Reactors Chapter 5 ’

to a transmission line, the line in turn being connected


to a power source. If the star-star connection in Fig. 44(a) db = 20 logi,&& (78)
is used the third-harmonic component of the exciting cur-
rent is suppressed and a third-harmonic component n-ill where P, the sound pressure, is expressed in dynes per
therefore be present in the line-to-neutral voltages. With square centimeter. Transformers designed to have sound
the primary neutral and the generator neutral grounded, levels below standard levels are available, but at extra cost
as in Fig. 44(b), a path is furnished for the third-harmonic because the magnetic material is worked at an induction
exciting currents. If the impedance of this path is low, below normal.
little third-harmonic voltage will be present on the system. It is quite difficult to predetermine a sound level n-hick
However, if the line is long and is closely coupled with will prove satisfactory in the surroundings where a new
telephone circuits, telephone interference may result. If transformer is to be installed. Local conditions affect sound
the transformer bank is close to the power source no tele- transmission, reflection, and resonance to a great degree, :
phone interference should result from the use of this and these factors are hard to evaluate prior to transformer
connection. installation.
When a delta-connected winding is present in the trans-
former such as in Fig. 44(c) and (d), the delta connection XVII. PARALLEL OPERATION
furnishes a path for the third-harmonic currents required OF TRANSFORMERS
to eliminate the third-harmonic voltages. If the primary
is ungrounded or the generator is ungrounded, no third- 43. Single-Phase Transformers
harmonic current will flow in the line. If the primarv is Transformers having different kva ratings may operate
grounded and the generator is also grounded, a little third- in parallel, with load division such that each transformer :
harmonic current can flow over the line. With this connec- carries its proportionate share of the total load. To achieve
tion the magnitude of the third-harmonic current in the accurate load division, it is necessary that the transformers :
line depends upon the relative impedances of the supply be wound with the same turns ratio, and that the percent
circuit and the delta circuit. This current is usually too impedance of all transformers be equal, when each per- ;
small to cause any troublesome interference. centage is expressed on the kva base of its respective trans-
The same general comments apply when three-winding former. It is also necessary that the ratio of resistance to
transformers are used. If one winding is delta connected, reactance in all transformers be equal, though most power
little or no third-harmonic current will flow in the supply transformers will likely be similar enough in this respect
circuit and little or no third-harmonic voltage will be to permit calculations based on only the impedance
present on the system. magnitude.
In Table 15 is given a summary of a number of typical The division of current between transformers having
transformer connections with a brief description of the unequal turns ratios and unequal percent impedances may
effect of the connections on the third-harmonic currents be calculated from an equivalent circuit similar to the one
and voltages. shown in Fig. 45. Either percent impedances or ohmic

I
XVI. TRANSFORMER NOISE 2 I:N -c

Transformer noise is a problem because of its disturbing


effect upon people. Noise may arise from several sources
of force induced vibrations, including 00

(1) Magnetostriction, the small change in dimensions Ea


of ferromagnetic materials caused by induction. 1
(2) Magnetic forces tending to pull jointed core mem-
bers together.
(3) Magnetic forces acting between two conductors,
or between a conductor and a magnetic member.
Fig. 45-Equivalent circuit for parallel connection of single-
(4) Fans, pumps, or other transformer auxiliaries. phase two-winding transformers.
The most persistent of these sources of noise is magneto-
striction, which depends upon flux density and cannot be impedances may be used in an equivalent circuit for paral-
eliminated by tight core construction. The only means of leled transformers. The circuit in Fig. 45 contains ohmic
reducing magnetostrictive force now at hand is to reduce impedances and actual turns ratios; this method is perhaps
flux density in the core. more appropriate when the circuit involves unequal turn
Noise arising from any of the sources listed above may ratios, because the use of percent values in this type of
be amplified by mechanical resonance in the tank or fit- circuit involves extra complications. Solution of this cir-
tings, and careful design is necessary to avoid such re- cuit, with a load current In assumed, will indicate the
inforcement of the original sound. division of current between transformers. Also, solution
Standard@ have been established for permissible sound of this circuit with total load current set equal to zero will
pressure levels for various types of transformers, in terms indicate the circulating current caused by unequal trans-
of decibels referred to 0.002 dynes per square centimeter: former ratios. For satisfactory operation the circulating
Chapter 5 Power Transformers and Reactors 131

current for any combination of ratios and impedances r;;_


prolxLbly should not exceed ten percent of the full-load aI:/N2 = oa”

rated current of the smaller unit.


31ore than two transformers may of course be paralleled,
and the division of load may be calculated from an es-
tended equivalent circuit similar to the one in Fig. 45.
44. Three-Phase Transformer Banks
The same considerations apply for the parallel operation
of symmetrical three-phase transformer banks as have been
orltlined for single-phase transformers. In addition it is
ncc:essary to make sure that polarity and phase-shift be-
t,\veen high-voltage and low-voltage terminals are similar
for the parallel units. A single-phase equivalent circuit
Inay bc set up on a line-to-neutral basis to represent one
$ase of a balanced three-phase bank, using the theory of Fig. 47-Equivalent circuit for a single-phase three-winding
Symmetrical components. transformer paralleled with a two-winding unit.
When t,hree-phase transformer banks having any con-
sitlcrnble degree of dissymmetry among the three phases 47. Division of currents may be calculated from this cir-
:LI‘Cto be analyzed, it is necessary either to set up a com- cuit, if the load currents I,’ and 1:’ are assumed.
I)lcte three-phase equivalent circuit,, or to interconnect Parallel operation of two such transformers is not usually
c>cllGvalentsequence networks in a manner to represent the satisfactory, since a change in tertiary load will alter the
~~nhalancedportion of the circuit according to the rules distribution of load between the other two windings. If
of symmetrical components. the impedances are proportioned to divide the load prop-
erly for one load condition, the load division between tmns-
45. Three-Winding Transformers fo’rmers at some other loading is likely to be unsatisfactory.
Currents flowing in the individual windings of parallel An exception is the case wherein the a” circuit of Fig. 4T
three-winding banks can be determined by solving an represents a delta tertiary winding in a three-phase bank,
cbcluivalent circuit, such as that shown in Fig. 46. The with no load connected to the tertiary; in this instance the
transformers can be made to divide currents similarly at
all loads.
It is possible to design a three-winding transformer so
that the load taken from the tertiary winding does not
seriously affect load division between t’he paralleled wind-
ings of the two transformers. If the impedance 2~ is made
equal to zero, then current division at the a’ terminals Iv-ill
be determined by 2s and Z only, and this impedance ratio
10 n-ill remain independent of tertiary loading. It is difficult
oc= to obtain zero as the value for Zp, particularly if this
clI winding is of high voltage; however, values near zero can
be obtained with special design at increased cost. Such a
design may result in a value of .ZT which is undesirable
for other reasons.

XVIII. TRANSFORMER PRICES


47. Two-Winding Type OA Transformers
Estimating prices for Type OA, oil-immersed, self-cooled,
60-cycle, two-winding transformers are given in Fig. 48.
Fig. 46-Equivalent circuit for parallel connection of single- The estimating prices per kva are based on net prices as of
phase three-winding transformers. December 1, 1949. As prices change frequently, the curves
should be used principally for comparing the prices of
terminal loads, as well as winding ratios and impedances, different voltage classes, comparing banks made of single-
affect the division of currents among the windings of a phase and three-phase units, etc.
three-winding transformer, so all these factors must be If the insulation level of the low-voltage winding is 15
known before a solution is attempted. kv, or higher, the prices in Fig. 48 should be corrected in
accordance with Table 16. Price additions are also required
46. Three-Winding Transformer in Parallel With when the rating of either the high- or low-voltage winding
Two-Winding Transformer is 1000 volts and below.
The equivalent circuit for a three-winding transformer Transformers designed for star connection of the high-
Paralleled with a two-winding transformer is given in Fig. voltage winding may be built with a lower insulation level
132 Power Transformers and Reactors Chapter 5

TABLE 16-ADDITIONS TO BE MADE TO PRICES IN FIG. 48


WHEN LOW-VOLTAGE WINDING INSULATION LEVEL IS 15 KV OR HIGHER
: Winding
i- -
Price Addition in Percent

Insulation
ChSS
Basic
Impulse
501 to
Single-Phase Equivalent ,55C kva
Self-Cooled Rating
3501 to
-
ioot to 113501mx I
I
.-
501 to
3-Phase Equivalent 55 C kva
Self-Cooled Rating
3601 to 7001 to
KV Levels-kv 14001 to 27001
IS00 i-000 13500 above 3600 7000 14000 27000 .nd hove
._
%/2’% 0% 0% OY* 3%X lW5 0% 0% 0:;
7 3 2 1 7 4 3 2 1
10 6 5 4 10 7 6 5 4

10 9 8 14 11 10 9 s
17 16 15 21 18 17 16 15
24 23 21 29 26 24 23 21

34 32 30 28 37 34 32 30 28
42 39 36 34 42 39 36 34
46 44 41 46 44 41
- - - -
at the neutral end than at the line end of the winding. 48. Multi-Winding Units
Table 17 summarizes the possible savings in cost with these If a multi-<Finding transformer is designed for simul-
designs. Reference should be made to section 16 for a taneous operation of all windings at their rated capacities,
discussion of the minimum insulation level that should be the price of the unit can be estimated from the curves
used at the transformer neutral. given for two-winding transformers by using an equivalent

TABLE 17-PRICE REDUCTION FOR GROUNDED NEUTRAL SERVICE

Winding Insulation Insulation* Price


Class at Class at Reduction
Line End Seutral End Percent
69 15 0
92 15 3.0
92 25-69 1.5

115 15 5.0
115 25-69 2.5
115 92 1.0

138 15 6.0
138 25-46 5.0
I
THREE-PHASE BANK RATING-WA 138 69-92 3.0
(a) SINGLE-PHASE UNITS 138 115 1.5
100 287\KV GLASS
161 15 7.0
161 25-46 5.5
161 69-92 3.5
161 115-138 2.0

196 15 9.0
196 25-G 7.5
196 69-115 4.5
196 138-161 2.5

230 15 10.0
230 25-69 7.5
230 92-138 5.0
230 161 3.0

II II II III II II IIJ
2’ 287 15 12.0
0.75 I 2 4 6 IO 20 40 60 100
287 25-69 9.0
TRANSFORMER RATING-WA 287 5.0
42-138
(b) THREE-PHASE UNITS
287 -
161-196 - 3.0
Fig. 48-Curve for estimating prices of oil-immersed, 60-cycle, *Reference should be mn<de 1m ye&on 16 for a discmsion of Ininirnurn permissible
two-winding, type OA power transformers. neutral insulation levels.
Chapter 5 Power Transformers and Reactors 133

two-winding capacity equal to the sum of the rated ca- transformer cost, where the Oh rating used to determine
pacities of the various windings divided by two. If a the base cost is equal to the highest rating of the force-
multi-winding transformer is not designed for simultaneous cooled or specially-cooled unit. The kva ratings listed in
operation of all windings at their rated capacities, the price the second column of Table 15 are the highest ratings of
of t,hc unit can he estimated from the curves given for forced-cooled units; for example, the kva rating listed for
two-winding transformers, using an equivalent two-winding OA/FA/FOA transformers is the FOX value.
c:lpacity equal to
I<quivalent=d+Q(B-A) (79) XIX. REACTORS
Where rl = $(Sum of the simultaneous loadings). 50. Application of Current-Limiting Reactors
B=$(Sum of the maximum rated capacities of Current-limiting reactors are inductance coils used to
the various windings). limit current during fault conditions, and to perform this
Tn addition, 5 percent must be added for three-winding function it is essential that magnetic saturation at high
transformers; 7.5 percent for four-winding transformers; current does not reduce the coil reactance. If fault current
ant1 10 percent for five-winding trttnsformers. is more than about three times rated full load current, an
iron core reactor designed to have essentially constant
49. Estimating Prices for Other Types of Cooling magnetic permeability proves overly expensive, therefore
l’able 18 is a summary of the approsimate cost of three- air core coils having constant inductance are generally used
pl~:w power transformers employing auxiliary cooling sys- for current-limiting applications. A reactor whose induc-
tams. All cost figures are expressed in per unit of 0-1 tance increased with current magnitude would be most
effective for limiting fault current, but this characteristic
TABLE ~&RELATIVE COSTOF THREE-PHASE TRANSFORMERS has not been practically attained.
WITH SPECIAL COOLING
IVAN cost is in per unit, based on the cost of an OA transformer hav-
ing :I rating equal to the maximum of the special unit being consid-

llree-
Phase Insulation Class--IiL
BLtIllC
1ating
IVA"' 15 34.5 69 192 /1151138 161~196~230
1 1.081.071.05’1.05~1.051.061.081.06~1.07

OA/FA/FO 20 0.7~0.750.770.780.i9~0.810.8b0.830.83
50 0.i30.730.75~0.770.800.81’0.810.82
100 0.720.i410.750.i60.78~0.810.80

FOA 20 0.660.670.710.730.750.770.780.810.82
50 0.640.680.700.710.750.790.810.82
100 0.660.670.670.680.710.i50.75

ow 2 1.051.030.990.991.031.071.02,0.970.91
5 0.910.920.920.920.930.970.960.930.91
10 0.850.840.900.880.900.890.930.910.90
20 0.820.840.8i0.880.890.880.910.900.90
50 0.870.860.850.850.840.880.870.87
100 0.850.850.850.820.820.850.81

FOW 20 0.600.610.650.670.690.710.710.740.75
50 0.590.620.640.650.690.730.710.72
100 0.600.610.620.620.65~0.69t0.69
I ’
(:L)0.4/F.4-Oi I-Immersed Self-Cooled/Forced-Air-Cooled.
O.~/FA/FA O-Triple-Rated, Self-Cooled/F orced-Air-Coolcd/Forced-Oil-
Cooled.
FOA-Force~l-Oil-Cooled with Forced-Air-Coolers.
O~~+il-lmmerscd Water Cooled.
orced-Oil Cooled wit,h Water Coolers.
cb) ~~~‘~~L~4 ratings tabulated for OA/FA and OA/FA/FOA units we the FA
nnd the FOA ratings respectively.
(~1.Example: The cost of a 15 kv OA/FA three-phase unit rated 10 000 kvn
(F.4) is equal to 0.00 times the cost oi B 15 kv OA three-phase unit rated 10 000
ha. Fig. 49-Oil-immersed air-core reactor.
Power Transformers and Reactors Chapter 5

Oil-immersed reactors can be applied to a circuit of any


voltage level, for either indoor or outdoor installation. The
advantages of oil-immersed reactors also include:
1. A high factor of snfcty against flashover.
2. Xo magnetic field outside the tank to cause heating
or magnetic forces in adjacent reactors or metal
structures during short-circuits.
3. High thermal capacity.
Dry-type reactors depend upon the surrounding air for
insulation and cooling. Because of the required clearances
and construction details necessary to minimize corona,
these reactors are limited to 34.5 kv as a masimum insula-
tion class. Free circulation of air must be maintained to
provide satisfactory heat transfer. These coils should not
be surrounded with closed circuits of conducting material
because the mutual inductance may be sufficient to produce
destructive forces when short-circuit current flows in the
coil. Structures such as I-beams, channels, plates, and
other metallic members, either exposed or hidden, should
also be kept at a distance from the reactor even though
they do not form closed circuits. A side clearance equal to
one-third the outside diameter of the coil, and an end
clearance of one-half the outside diameter of the coil will
produce a temperature rise less than 40 C in ordinary
magnetic steel. For the same size members, brass will have
about the same rise, aluminum abollt one and one half
times, and manganese steel about one-third the rise for
ordinary magnetic steel. Reinforcing rods less than three-
fourths inch in diameter which do not form a complete
electrical circuit are not included in these limitations, be-
cause the insulation clearances from the reactor should be
sufficient to avoid undue heating in such small metal parts.
In order to avoid excessive floor loading due to magnetic
forces between reactors the spacing recommended by the
manufacturer should be observed. Sometimes this spacing
can be reduced by use of bracing insulators between units
or using stronger supporting insulators and increasing the
strength of the floor. This should always be checked with
the manufacturer since bracing increases the natural period
of vibration and may greatly increase the forces to be
resisted by the building floors or walls.
51. Reactor Standards
The standard insulation tests for current-limiting re-
actors are summarized in Table 19.
Dry-type current-limiting reactors are built with Class
B insulation and have an observable temperature rise by
resistance of 80 C with normal continuous full-load current.
Dry-type and oil-immersed current-limiting reactors are
designed mechanically and thermally for not more than
33% times (3 percent reactive drop) normal full-load
Fig. JO-Dry-type air-core reactor. current for five seconds under short-circuit conditions.

Air core reactors are of two general types, oil-immersed 52. Determination of Reactor Characteristics
(Fig. 49) and dry-type (Fig. 50). Oil-immersed reactors When specifying a current-limiting reactor, information
can be cooled by any of the means commonly applied to should be included on the following:
power transformers. Dry-type reactors are usually cooled 1. Indoor or outdoor service.
by natural ventilation but can also be designed with forced- 2. Dry- or oil-immersed type.
air and heat-exchanger auxiliaries where space is at a 3. Single-phase or three-phase reactor.
premium. 4. Ohms reactance.
Chapter 5 Power Transformers and Reactors 135

TABLE19-STANDARDDIELECTRICTESTS
FOR CURRENT-LIMITING REACTORS
-
Low Frequency Impulse Tests
Testscb’ (Oil Type) (‘)
-
Insulation
Chopped Wave
Class kv Dry - - Full
(2) (Ii1 Type TYW ?vIin. Time WaW?
kv rms (cl Voltqe o Flnsh-
kv rms kv crest t kv crest
cwer in fi:jl
1.2 12 12 54 1.5 45
2,s 17 25 69 1.5 60
5.0 21 30 88 1.6 i5
20 40 6 ‘0 100 200 400 600 1000 2000 40006000
8.66 29 40 110 1.8
I5 0 36 60 130 2.0 REACTOR RATING-KVA

Fig. Sl-Curve for estimating prices of single-phase, 60-cycle,


23.0 GO 85 175 3.0 dry-type current-limiting reactors.
3-4.5 80 115 230 3.0
46.0 105 290 3.0 250
,
69.0 160 ‘ml 3.0 350 13kKV CLASS1

92.0 210 520 3.0 450


115.0 260 630 3.0 550
138.0 310 750 3.0 650
161 .O 3G5 865 3.0 750

l!)G 0 425 1035 3.0 900


230.0 485 1210 3.0 1050
2S7.0 590 1500 3.0 1300
3-45 0 I 690 - li85 3.0 1550

(a) Intermediate voltage ratings are placed in the next higher insulation class
unless specified otherwise.
(h) Turn-to-turn tests are made by applying these low-frequency test voltages.
nt a suitable frequency. across the reactor terminals: dry-type reactors for
olltdoor service require a turn-to-turn test voltage one-third greater than the
tabulated values.
(c) No standard impulse tests-have been established for dry-type current-
limiting reactors.
‘L ’ -0.1- 0.2 0.4 0.6 I 2 4 6 IO 20
REACTOR RATING MVA
5. Continuous current rating, amperes.
6. Reactor rating in kva. Fig. 52-Curve for estimating prices of single-phase, 60-cycle,
oil-immersed current-limiting reactors.
7. Voltage class.
8. Circuit characteristics:
(a) Single-phase or three-phase. tion of one percent for each 100 amperes, or fraction thereof,
above 600 amperes.
(b) Frequency.
(c) Line-to-line voltage. Estimating prices for single-phase, 60-cycle, oil-immersed
(d) Type of circuit conductors. current-limiting reactors are given in Fig. 52 for insulation
classes between 15 and 138 kv. For current ratings above
Standardization of current ratings and ohmic reactances 800 amperes make a price addition of two percent for each
for current-limiting reactors is not yet completed, but 100 amperes, or fraction thereof, above 800 amperes.
wmi-standard values are available and should be used Estimating prices for BO-cycle, oil-immersed, self-cooled
\vhcre feasible in the preparation of reactor specifications. shunt reactors may be estimated by adding 10 percent to
the prices given in Fig. 48 (a) for two-winding transformers.
53. Reactor Prices
The estimating prices included in this section should be
TABLE 20-PRICE ADDITIONS FOR DRY-TYPE REACTORS
used for comparative purposes only because reactor prices RATED BELOW 300 AMPERES
arc subject to change from time to time.
Estimating prices for single-phase, 60-cycle, dry-type Current Price
current-limiting reactors are given in Fig. 51 for kva rat- Rating Amperes Addition Percent
ings between 10 and 5000. Reactors for use in 1201 to
250-299 5
13 800 volt circuits may be estimated from the curve 200-249 10
l:lMed “15 kv and below.” The prices given apply to 150-199 15
single-phase reactors with current ratings between 300 and 125-149 2’2
600 amperes. For current ratings below 300 amperes, price 100-124 29
additions must be made in accordance with Table 20. When 75- 99 36
the current rating exceeds 600 amperes make a price addi- 50- 74 43
136 Power Transformers and Reactors Chapter 5

XX. EQUIVALENT CIRCUITS FOR SINGLE


PHASE TRANSFORMERS 0

Representation of a transformer by an equivalent circuit EP

is a commonly used method for determining its perform-


ance as a circuit element in complex power and distribution
networks. Without the simplifications offered by the use
of such equivalent circuits the handling of transformers
with their complex array of leakage and mutual imped-
ances would be a formidable problem.
For the purposes of calculating short circuit currents,
voltage regulation, and stability of a power system, the
normal magnetizing current required by transformers is (a)
neglected. Thus Figs. 2(c), (d), or (e), as the choice may
be, will adequately represent a two-winding transformer
for calculation purposes.
For three-, four-, and in general multi-winding trans- IP
a0 - “2
formers, an equivalent network can be always determined NI ‘y
that will consist only of simple impedances (mutual imped- EP
“3
ances eliminated) and accurately represent the transformer ] NZ’T

as a circuit element. The impedances which can be most


readily determined by test or by calculation are those
between transformer windings taken two at a time, with
other windings considered idle; therefore the impedances
in an equivalent circuit can well be expressed in terms of
zp=1/2
[
zps + ZP4-ZST ] Zs=l/2 [+zsT+ZPS-ZPT]
N:
these actual impedances between the transformer windings Zr=l/2 zpT+-zsT-zps
taken two at a time. [ NI: I

The number of independent impedances required in an


equivalent circuit to represent a multi-winding transformer
shall be, in general, equal to the number of all possible
different combinations of the windings taken two at a time.
Thus, one equivalent impedance is required to represent
a two-winding transformer, three branch impedances for a
three-winding transformer, and six independent branch
impedances to represent a four-winding transformer.
Equivalent circuits for the two-winding transformer and
auto-transformer are presented in sections 1 and 27, re-
\L/
spectively. The following sections discuss the equivalent
Zp% = t/2
1zp,x + Zpr% -

circuits for three-winding and four-winding transformers. z&=112[~Zs~%+Zpsr -h%]


54. Equivalent Circuits for Three-Winding Trans- ZTY = I/+,,% +$zsa -Zps%]
former
The equivalent circuit for a transformer having three Fig. 53-Three-winding transformer.
windings on the same core is shown in Fig. 53, where the
(a) winding diagram.
magnetizing branches have been omitted. The number (b) equivalent circuit in ohms.
of turns in the P, S, and T windings are nl, n2, and n3, (c) equivalent circuit in percent.
respectively. The equivalent circuit is shown in Fig. 53
(b) with all impedance in ohms on the P winding voltage
base and with ideal transformers included to preserve Note that Zp and 2s as defined and used here differ
actual voltage and current relationships between the P, from Zp and 2s in Eq. 10. The equivalent circuit ex-
S, and T windings. On the P winding voltage base: pressed in percent is given in Fig. 53 (c) with all imped-
ances referred to the kva of the P winding.
1
z,=g ZPS+ZPT--ZST
( NT )
1
2s = 3 --zsT+zPs-ZPT (80)
N2,

( 1 $&T%+zP,g,-zPT%
zT= a ZPT+-ZST-ZPS >
N: )
Z,% = f ZPT%+$zYT% -Zps%)
(

The quantities can be expressed in percent on any arbi-


trary kva base, Uo, by multiplying each impedance by
Chapter 5 Power Transformers and Reactors 137

UC
the ratio up. The notation used is defined as follows:
Up = kva of the P winding.
Us = kva of the S winding.
UT = kva of the T winding.
ZFs =leakage impedance between the P and S wind-
ings as measured in ohms on the P winding with
the S winding short-circuited and the T winding
open-circuited.
ZF9~O=leakage impedance between the P and S wind-
ings, with the T winding open-circuited, ex-
pressed in percent on the kva and voltage of the
P winding.
Zrr=leakage impedance between the P and T wind-
ings as measured in ohms on the P winding with
the T winding short-circuited and the 5’ winding
open-circuited.
z,& = leakage impedance between the P and T wind-
ings, with the X minding open-circuited, ex-
pressed in percent on the kva and voltage of the
P winding.
Zsr = leakage impedance between the S and T wind-
ings as measured in ohms on the S winding with
the T winding short-circuited and the P winding
open-circuited.
~~~7~ = leakage impedance between the S and T wind-
ings, with the P winding open-circuited, ex-
pressed in percent on the kva and voltage of the
S winding. Fig. 54-Four-winding transformer.
The equations given in Fig. 53 (b) and Fig. 53 (c) for (a) winding diagram.
%r,,Zp70,etc., are derived from the relationships: (b) equivalent circuit.
%ps=ZpfZs ZPs%==P%+fZS%
3
%pT=Zp+ZT ZPT%=ZP%++ZT% (82) here again the magnetizing branches are omitted. The
branches of the equivalent circuit are related to the leak-
age impedances between pairs of windings as follows:
IdSO

Zp = R&XP
Zps = RpsfjXps = Rp+Rs+j(Xp+Xs) 033)
ZPS+$$~T-ZPT-K
Zps% = Rps%+.iX~~% etc., 1
\vhorc XPs is the leakage reactance between the P and S
Cndings (with T open-circuited); and RPS is the total Z,= $ $2Z~~++2Z~~-$Z~~- K
( 1 2 1 )
cffcctive resistance between the P and S windings, as
measured in ohms on the P winding with S short-circuited
and T open-circuited. Rps% and Xrs$$ are the respective
(lunnt,ities expressed in percent on the kva and voltage of
Z,=+
(- 1
-ZTV+ZPV-ZPT-K
Ni
Z,=dKlK2+Kl
034)

the I’ winding. zf =~K~K,+K~


The equivalent circuits completely represent the actual
transformer as far as leakage impedances, mutual effects where, K&Q-+=-
between windings, and losses are concerned (except ex- ZefZf
citing currents and no load losses). It is possible for one 1 1
of t,llc three legs of the equivalent circuit to be zero or KI = ZPTf -zsv - ZPS - -,ZTV
Nf N,
neg:ut,ive.
K~=ZPT+$~ZSV-ZPV-$ST
SK Equivalent Circuits for Four-Winding Trans- 1
former The windings will ordinarily be taken in the order that
The equivalent circuit representing four windings on makes K1 and Kz positive so that Z, and Zr will be posi-
the same core, shown in Fig. 54 (a) is given in Fig. 54 (b) tive. The leakage impedances are defined as before; for
luring ohmic quantities. This form’is due to Starr11,12and example, Zrs is the leakage impedance between the P
138 Power Transformers and Reactors Chapter 5 ’

and S windings as measured in ohms on the P winding ed. If the bank is connected star-delta, with the star point
with the S winding short-circuited and with the T and grounded, the zero-sequence impedance viewed from the
V windings open-circuited. The equivalent circuit in per- star-connected terminals for shell-form units, or banks of
r ’ three single-phase units, is equal to the positive-sequence
cent has the same form as Fig. 54 (b), omitting the ideal
, transformers. impedance; the zero-sequence impedance viewed from the
delta-connected terminals is infinite.
Z,%=3 Zps%fZ~%-+sv%--K%), etc. The.imp.edance to the flow of zero-sequence_._. currents
-- in
( s three-phase-..- core>&&
--. -- ..-Is_‘~m~&~n~~y’&ver than the
-.___- , . _“__ .-: .---. .---..
posrtlve-sequence impedance. Figure 55 illustrates m
‘,_ K~%=Z~T%+~SV%-ZPSYD-~ZTV%, etc. (85) therells-Go ~~~r~-~~-~~~-zero-seouence exciting flux in
T
such a unit, except in the insulating medium, or in the
Similar equations, derived from Eq. (84), apply for the tank and metallic connections other than’the core. The
other quantities in the equivalent circuit. flux linkages with the zero-sequence exciting currents are
therefore low, and the exciting impedance to zero-sequence
XXI. SEQUENCE IMPEDANCE currents correspondingly low. Although the exciting im- ,
CHARACTERISTICS OF THREE-PHASE pedance to positive-sequence currents may be several
TRANSFORMER BANKS thousand percent, the exciting impedance to zero-sequence
currents in a three-phase core-form unit will lie in the range
56. Sequence Equivalent Circuits from 30 to 300 percent, the higher values applying to the
The impedance of three-phase transformer banks to largest power transformers. Low exciting impedancg
positive-, negative-, and zero-sequence currents,‘and the under zero-sequen;e_conditionsYZXlected ln-@e !
sequence equivalent circuits, are given in the Appendix, du~&%-~the through impedances to, zeroy&uence cur-
under Equivalent Circuits for Power and Regulating rent
-I’-- flow.
“’ A star-star grounded, three-phase, two&%&@
Transformers. The equivalent circuits were developed unit of the core-form ded autotrans-
by Hobson and Lewis2’13. The same notation as defined former of the three-p
in the early part of this chapter is used to denote leakage characteristic, as if it had a tertiary winding of relatively :
impedances in ohms and in percent. high reactance. In small core-form units this characteristic 1
The impedance to negative-sequence currents is always is particularly effective and can be utilized to replace a.
equal to the impedance to positive sequence currents, and tertiary winding for neutral stabilization and third har-
the equivalent circuits are similar except that the phase monic excitation. I
shift, if any is involved, will always be of the same magni- The zero-sequence exciting impedance is affected by the 1
tude for both positive- and negative-sequence voltages magnitude of excitation voltage, and it is also affected by 1
and currents but in opposite directions. Thus, if the phase tank construction. For example, the zero-sequence excit- 1
shift is +cu degrees for positive-sequence, the phase shift ing impedance of a 4000-kva, 66 OOO-2400-volt unit was I
for negative-sequence quantities will be -a! degrees. measured to be 84 percent at normal voltage before the!
The impedance of a three-phase bank of two-winding core was placed in the tank; it was measured to be 36 i
transformers to the flow of zero-sequence currents is equal percent at normal voltage after the core and coils were
to the positive-sequence impedance for three-phase shell- placed in the tank. In this case the tank saturated but
form units (or for a bank made up of three single-phase acted as a short-circuited secondary winding around the
units) if the bank is star-star with both star points ground- transformer, tending to limit the area of the flux return
path to that between tank and windings. The zero-
sequence exciting impedance is measured by connecting
b C
the three windings in parallel and applying a single-phase
IO voltage to the paralleled windings.
The zero-sequence exciting impedance of three-pdq
core-form units is generally much lower than the positi%

u&s.. .The exciting impedance to zeresequence


has been denoted by Zss, ZPs, etc., where the
script refers to the winding on which the
exciting impedance is measured in ohms. Following tl
same notation, Zs&o is the exciting impedance of the
winding to zero-sequence currents expressed in percent c
d 6 the kva of the S winding. The number of branches require
Fig. 55-Zero-sequence exciting currents and fluxes in a three- to define an equivalent circuit of three-phase two- or mult
phase core-form transformer. winding transformers is the same in general as has been d
Chapter 5 Power Transformers and Reactors 139

scribed for single phase transformers. A notable exception to


this will exist in the formulation of the zero-sequence im-
pedance of core form transformers with grounded neutral.
ln this case an extra impedance branch must be provided in
the equivalent circuit, this branch being always short-
Circuited to the neutral bus, and having a value dependent
,,pon the zero-sequence excitation impedances of the wind-
irIgs as well as the grounding impedance in the transformer
neut,ral. If-the three-phase bank connections are unsym-
mctrical-~s.~~-~hec~~seofthe.__--
open-delta
.- - -.. connection, mutual
,oupling ~111exist b+rcen,,.the. sequence networks.
- -_-_.-_- (a)
57. Derivation of Equivalent Circuits
In the derivation of equivalent circuits for three-phase
tr:msformers and banks made up of three single-phase
t I:insformers, it is convenient to represent each winding of
tllc transformer by a leakage impedance and one winding
,)f an ideal transformer. This method may be used in the
,l~~vclopment of circuits for two- and three-winding (b)

tr:msformers.
TWO magnetically-coupled windings of a single-phase
transformer having n1 and nz turns, respectively, are shown
scnhcmatically in Fig. 56(a). The customary equivalent
c*ircrlit used t,o represent such a single-phase transformer is
shown in Fig. 56(b) in which ZA and 2~ are components
of t hc transformer leakage impedance, with a more or less zA+z,* =PS
:Irt)itrary division of the leakage impedance between 2~ (cl
:rnd Zg, Zw is the so-called “magnetizing shunt branch.”
Since the numerical value of ZM is very large compared to
%,, and Zn, for most calculations Fig. 56(b) is approx-
imated by Fig. 56(c) where ZM is considered infinite.
Either of these circuits has serious deficiencies as a device
b representing the actual transformer; the voltage and cur-
rrnt transformation effected by transformer action is not (d)
rrpresented in the equivalent circuit, and the circuit
terminals a and a’ are not insulated from each other as in
the actual transformer. These disadvantages are evidenced
particularly when analyzing transformer circuits wherein
several windings or phases are interconnected. To over-
come these deficiencies it is expedient to use the equivalent
circuit shown in Fig. 56(d) which combines the circuit of
l$. 56(b) with an ideal transformer. The ideal trans-
former is defined as having infinite exciting impedance
(zero exciting current) and zero leakage impedance, and
scrvcs to transform voltage and current without imped-
‘uN’~ drop or power loss; the ideal transformer thus re-
stores actual voltage and current relationships at the
tminnls a and a’. The circuit of Fig. 56(e) is obtained
from Fig. 56(d) by converting the impedance ZB to the E,’
v()lQe base (by multiplying ZB by the square of the
voltage ratio). This process may be thought of as “sliding
the ideal transformer through” the impedance ZB. If the
cs(~iting, or no load, current may be neglected (ZM con-
sidered as infinite) the circuit of Fig. 56(e) becomes
Il‘ig. 56(f).
Finally, if Z M I‘s considered infinite, the circuit of Fig.
j6(f) becomes Fig. 56(g), in which the two parts of the
leakage impedance, ZA and ZB, combine into the complete Fig. 56-Steps in the derivation of the equivalent circuit of a
leakage impedance Zps, where two-winding transformer.

ZPS=ZA+ZB @f-3)
14u rower ~‘ransJ0rmer.sand Keaclors mapter 5 1

In most developments the circuit of Fig. 56(g) will be ePand e, represent the voltages across the P and S wind-
found most convenient, although in some cases it becomes ings of the ideal transformers.
desirable to have part of the leakage impedance associated Assuming positive-sequence voltages E,,, Eb., and E,,
with each winding, and the circuit of Fig. 56(f) may be applied to the terminals abc, and a three-phase short-
used. circuit at the a’b’c’ terminals, the following relations can be
To be perfectly definite, 2~s is understood to mean the written:
leakage impedance, as measured in ohms, with the S wind- EL= EL,= EL,=0 nL = nJs
ing short circuited, and voltage applied to the P winding.
When the test is reversed, with voltage applied to the S e, = IxZ, I, = n’I* (88)
winding, and the P winding short circuited, the impedance n”2
is denoted by 2s~. It is obvious from the development
given that, when 2~ may be considered infinite,

58. Derivation of Equivalent Circuit for Star-Delta Designating the circuits connected to the abc and a’b’c’
Bank terminals as circuits 4 and 5, respectively,
In Fig. 57 each transformer winding is represented by an zIs=Ey=zp+ ?! 2zs+s (89) ;
impedance and one winding of an ideal transformer, the a 0 722
transformer having nl turns in the P winding and nz turns Z45 is defined as the impedance between circuits 4 and 5
in the S winding. The windings shown in parallel are in ohms on the circuit 4 voltage base. ZPS is the imped- :
assumed to be on the same magnetic core. The voltages ante between the P and S windings as measured by apply-
ing voltage to the P winding with the 5’ winding short- I
circuited.
With positive-sequence voltages applied to the abc ;
terminals and the a’b’c’ terminals open circuited,
4
Ebg= a2Eag E& = a2E&
EC,= aE,, EL, = aE&
e, = 3e, = EL, - E& (90) i
711
E.,=e,=z(ELg-aEL)
I ! J I
“p =2&.(1-a) =fi?!!E&~-i~.
N’‘15-n, Ice n2

1;
I
1%
LettingN=z E&=NE,,@.
(a) SCHEMATlC DIAGRAM &hi’
As positive-sequence quantities were used in this analy
;~-%2~~Lj~;
ZPS sis, the final equation can be expressed as follows:
E/ = NE1ci30, (91
where E: and El are the positive-sequence voltages t
ground at the transformer terminals.
(b) POSITIVE-SEOUENGE EOUIVALENT CIRCUIT The above relations show that the line-to-ground volt
ages on the delta side lead the corresponding star-sid
voltages by 30 degrees, which must be considered in
complete positive-sequence equivalent circuit for the tram
former. A consideration of Eqs. (88) will show that th
currentsI:, Id and I,’ also lead the currents I,, Ib an
I, by 30 degrees.
(c)NEGATIVE - SEOUENCE EOUIVALENT CIRCUIT
I, = 3,
n2
ZPS

i(---r” 7:; = I-tEi30s


N
(d) ZERO-SEQUENCE EPUIVALENT CIRCUIT I1
I[=-,j30.
Fig. 57-Equivalent circuits of a star-delta transformer bank. N .
Chapter 5 Power Transformers and Reactors 141

The complete positive-sequence circuit in Fig. 57(b)


therefore includes the impedance Zps and an ideal trans-
former having a turns ratio N and a 30-degree phase shift.
A similar analysis, made with negative-sequence volt-
ages and currents, would show that
I2
I~=-E-i30a (93) @
N
E> = NE, c- j30. (94)
The positive- and negative-sequence circuits are there- *b
fore identical excepting for the direction of the phase -
shifts introduced by the star-delta transformation. Eb:f
The zero-sequence circuit is derived by applying a set of 7
zero-sequence voltages to the abc terminals. In this case
Eag=Ebg=Ecg=Eo
I*=Ib=I,=Io I
Eng= ep+ZJ,.
e. - I,ZS = 0 because no zero-sequence voltage can IE
be present between line terminals. (95)
Ix=3B *
n2

ep=?!eR= ?! 21,Zs o
0
B;,=::[ (;;CL.+Zp]=IaZps (a) SCHEMATIC DIAGRAM

a’
Z. = ; = ‘y = Zps, which is the same impedance as
was obatained with positive-sequence voltages
9 and currents. (96)
If zero-sequence voltages are applied to the a’b’c’ ter-
minals, no current can flow because no return circuit is
present. The zero-sequence impedance of the transformer
bank is therefore infinite as viewed from the delta side. (b) POSITIVE-SEQUENCE EQUIVALENT CIRCUIT

59. Derivation of Equivalent Circuit for Autotrans-


former with Delta Tertiary

a0A
The basic impedances of an autotransformer with a delta
tertiary may be defined in term’s of the leakage impedances
between pairs of windings, with the third winding open
circuited. The impedance between the primary and
secondary, or common and series, windings of the trans-
former in Fig. 58(a) may be obtained by applying a voltage
across the P winding with the S winding short circuited, (c) NEGATIVE-SEQUENCE EOUIVALENT CIRCUIT
and the T winding open circuited. Referring to Fig. 59,

ea= 1 IZS ep=.5=-2IZ


0nl n1 R2

E=e,+IZp

cw
\ d

(d) ZERO-SEQUENCE EQUIVALENT CIRCUIT

Fig. 58-Equivalent circuits of a three-winding autotrans-


Similar relations can be derived for the impedances former.
142 Power Transformers and Reactors Chapter 5

Eag=ep-(la)-Ia)ZP
=ep+IJp( 1---A)
=I XZs+nl”ZP
n (lfn1)’

[z,+z”
2
IL,
z45=y=(1~n1)*
1 &2

(101)
Representing the circuit transformation ratio (l+n~) by
N’,
z 46 = PS (102)

The impedance between circuits 4 and 6 may be oh-


tained by applying positive-sequence voltages to ter-
Fig. .59-Representation of the primary- to secondary-wind- minals abc, with terminals a’b’c’ open and u”b”c” shorted
ing impedance of an autotransformer. circuited. In this case:
et = IxZT Ix = Ih2
between the P and T, and S and T windings, resulting in
the set of equations
(103)
ZPS=?*+ZP E,,=e,+IJP

ZPT=$+ZP
2 (98)
=I*
E
[z2+2,
ZT
1
24s=~=-+Zp=ZpT.
ZST=
0; *zT+zs.
Ia n2

With positive-sequence voltages applied to terminals


These equations can be solved for the individual winding a’b’c’, terminals abc open and terminals u”b”c” short
impedances ZP, 2s and 2~. circuited,
et = IxZ~
zp=+ Z,,fZp,-2
[ 1 lfnl
-et= - !I!? ?l,‘ZT
eDSee=
(99) n2

z,=+
cc; >2ZsT+n;zpT-n;Zpy
1.
n2 ( )

E&=e,+e,-I:(Zp+Zd
=-1;Kc )2zT+zp+zs
1
The impedances among circuits 4, 5 and 6 can be de-
rived in terms of the impedances between windings, using
the same procedure as employed in the derivation of the
impedances of the starTdelta bank in section 58.
z66
=(-lfnl12ZT+Zp+z
712
S.

With positive-sequence voltages applied to terminals Expressing ZP, Zs and ZT in terms of impedances be-
abc, terminals a’b’c’ short circuited and terminals a”b”c” tween windings as given in Eq. (99) :
open circuited, the following relations can be written:
.&=(lhh)ZPT+
E&=E&=E&=O e, = nlep

I:-I,+nJ;=O ,+I, The above equation is the impedance between circuits


1+nl 5 and 6 in ohms on the circuit 5 voltage base. As 245 and
e,+e,-(I,‘-I,).Zp-II,‘Zs=O. Z46 are ohmic impedances on the circuit 4 base, it is con-
venient to express the circuit 5 to circuit 6 impedance on
Eliminating e, and I’, from the above equation: the same base. Dividing by (1 +n,) 2,
121
e,(l +nd = +pp+zs) -IaZ, -=- Z56 ZPT ZST
--ZPS
1 (l+nl)* l+nl+nl(l+nl) (l+n1)2

(100)
Chapter 5 Power Transformers and Reactors 143

The transformer can be represented by the positive- The second ideal transformer therefore has an N” turns
sequence equivalent circuit in Fig. 58(b). The relations ratio and a 30 degree phase shift.
between the impedances in the equivalent circuit and the Negative-Sequence Circuit-A similar analysis
impedances between circuits can be expressed as follows: made with negative-sequence voltages would show that
Zhll+ZH1=245 the impedances in the equivalent circuit are the same as in
the positive-sequence circuit, and that the terminal volt-
z&I+z,, = 246 (107) ages are related as follows:
Ez’= N’E,
Ei’ = N”E, tf GO. (113)
The positive- and negative-sequence circuits are there-
(108) fore identical excepting for the direction of the phase shift
introduced by the star-delta transformation.
Zero-sequence circuit-The zero-sequence character-
istics of the transformer can be obtained as follows:
1. Apply zero-sequence voltages to terminals abc with

1
z + ZST terminals a’b’c’ connected to ground and the delta opened.
pqy2-ZpT This permits evaluation of the zero-sequence impedance
ZPS+ZPT----- (109) between circuit 4 and circuit 5.
2. Apply zero-sequence voltages to terminals abc with
the delta closed and terminals a’b’c’ open circuited.
3. Apply zero-sequence voltages to terminals a’b’c’ with
the delta closed and terminals abc open circuited.
z = N’-1 2 The general procedure in writing the necessary equa-
46 ZPS
( N’ )
tions is similar to that followed in the positive-sequence
z46 = ZPT
analysis given above, and the zero-sequence analysis in
(110)
section 57. It will be found that the zero-sequence im-
,756= ;\i’zPT + &ST- (iv’- 1)zPS pedances in the equivalent circuit shown in Fig. 58(d) are
the same as the positive-se’quence quantities, that is,
2z45 ZHO = ZHl

ZPT = z46
ZMO = Z&l1 (114)
(111)

ZST= (N’- 1) $+&z,,-z,,

In the above equations ZH~, ZJI~, ZL~, 245 and ZM, are in
1 ZLO = ZLl

If the neutral of the autotransformer is ungrounded, the


zero-sequence equivalent circuit is altered considerably as
ohms on the circuit 4 (abc terminals) voltage base. Z56 is shown in Fig. 60. In this case zero-sequence current flows
in ohms on the circuit 5 (a’b’c’ terminals) voltage base.
%rJsand Zpr are in ohms on the P winding voltage base
and Z:Sr is in ohms on the S winding voltage base. N’ is
(Mined as lfnr, which is the ratio of line-to-line or line-
to-neutral voltages between circuit 5 (a’b’c’ terminals)
ml circuit 4 (abc terminals).
The phase shifts between circuit voltages can be de- Fig. 60-Zero-sequence equivalent circuit of an ungrounded
t crmined by applying positive-sequence voltages to ter- three-winding autotransformer.
minals abc with the other two circuits open circuited.
bnder these conditions, between terminals abc and a’b’c’ without transformation.
Eilg=ep E&=ep+es Current in the S winding is balanced by circulating cur-
EL,= (l+nr) EaK= N’E,,, which shows that the one rents in the tertiary, with no current flow in the P winding.
The zero-sequence impedance is therefore determined by
ideal transformer has an N’ ratio but no phase
the leakage impedance between the S and T windings.
shift.
Applying zero sequence voltages to the abc terminals, with
et= E,J’ - Ebs)’= E,pl’( 1 - a2) the a’b’c’ terminals connected to ground and the tertiary
et= n2ep= GE,, closed,
E I?= n2 I,=Ia’= -zx
w - E,, =F3E,,e-j30 (112)
l-a2
et= IxZ~
Defining3 N”,
eB=nlet= - 3 21.‘z*
E,:’ = N”E;iGe-j30. R2 0 n2
144 Power Transformers and Reactors Chapter 5

sidering the autotransformer with delta tertiary (case D-l


in Table 7), the ecluivalent circuit impedances can be
obtained from the impedances between circuits as follows:

Percent Quantities-The manufacturer normally es-


presses transformer impedances in percent on 8 kva base
corresponding to the rated kva of the circuits involved.
The resulting impedances will all be in percent on the
These percent vnlucs can be converted to ohms by the
circuit -1 kva base.
familiar relation

(11G) REFERENCES
%= impedance in ohms. 1. Electric Circuits-Theory and Applications, by 0. G. C. Dnhl
(a book) Vol. I, p. 34, McGraw-Hill Book Company, Inc., Sew
ZcO = impedance in percent. York.
kva = :&phase kva rating of circuit. 2. Regulating Transformers in Power-System Analysis, by J. E.
Hobson and W. A. Lewis, .4.Z.E.E. Tmn.snclion.s, Vol. 58, 1939,
E = line-to-line circuit voltage in kv.
p. 874.
Using the nomenclature employed in the derivations, 3. Fundamental Concepts of Synchronous Machine Rcnrtsnces,
by B. R. Prentice, il.Z.E. E. ?‘runsaclions, Vol. 56, 1937, pp. l-
7, = lOZ4s% Ed3 22 of Supplement.
A 15 , where
u4 4. Simplified Computation of Voltage Regulation with Four \Vind-
Eq=line-to-line voltage, in kv, of circuit 4. ing Transformers, by R. D. Evans, Electricnl En,gitzeering,
October 1939, p. 420.
CT4= three-phase kva rating of circuit 4. 5. Surge Proof Transformers, by H. V. Putman, -4.Z.E.E. Trans-
Z,,% = impedance between circuits 4 and 5 in per cent on xtions, September 1932, pp. 5X-584 and discussion, pp. 584-
kva rating of circuit 4. 600.
6. American Standards for Transformers, Regulators, and Re-
Zd5=impedance between circuits 4 and 3 in ohms on actors. American Standards Association, AS4 CSi, 1918.
the circuit 4 voltage base. 7. Loading Transformers by Copper Temperature, by H. V. Put-
Similar relations can be written for the other impedances man and W. M. Dnnn A.Z.E.E. Z’ransackm, Vol. 58, 1939,
involved. pp. 504-509.
8. Equivalent Circuit Impedance of Regulating Transformers, by
It should be noted that the impedances, as used in this
J. E. Clem, $.Z.E.E. Transactions, Vol. 58, 1939, pp. 871-873.
chapter and in the Appendix, are expressed in terms of the 9. Theory of Abnormal Line to Neutral Transformer Voltages, by
voltage or kva rating of the circuit or winding denoted by C. W. LaPierre, A.Z.E.E. Z’ransaclions, Vol. 50, 1Inrch 1331,
the first subscript. For example 245 is in ohms on the cir- pp. 328-342.
cuit 4 voltage base, whereas Z64 would be in ohms on the 10. St,andsrds for Transformers NE&IA Publicat,ion So. 48-132,
circuit 5 voltage base. These impedances can be converted September 1948.
from one circuit base to another as follows: 11. An Equivalent Circuit for the Four-Winding Transformer, by
F. M. Starr, General Electtic Review, March 1933, Vol. 36, pp.
150-152.
246
12. Transformer Engineering, by L. F. Blume, et al, (a book), John
Wiley and Sons (1938).
13. Equivalent Circuits for Power and Regulating Transformers, by
(117)
J. E. Hobson and W. A. Lewis, Eleclric .lournnl Preprint,
.January 1939.
The equivalent circuits can be based directly on percent 14. J. and P. Transformer Book, by Stigant, 6th Edition, 1935,
quantities as shown in Table 7 of the Anoendix. Con- Johnson and Phillips, London.
CHAPTER 6

MACHINE CHARACTERISTICS
()riyitllll dulhi-:
C. F. Wagner

EFORE the growth of the public utilities into -their

B present enormous proportions with large generating


stations and connecting tie lines, machine perform-
:Ln(:cwas largely judged in terms of the steady-state char-
:~&xistics. The cmcrgence of the stability problem gave
,.jsc: to the analysis of the transient characteristics of
r,l:tcahines and was largely responsible for our present
I,llc,\vledge of machine theory. A further contributing urge
\Y;LSthe need for more accurate determination of short-
(*irc:rlit currents for the application of relays and circuit
t,rrnkcrs.
The variable character of the air gap of the conventional
s:Jictnt,-pole synchronous generator, motor, and condenser
\vil.ll its concentrated field windings requires that their
analysis follow a different line from that for machines such
:IS induction motors, which have a uniform air gap and
tlistributed windings. Blonde1 originally attacked this
problem by resolving the armature mmf’s and fluxes into
t,\ro components, one in line with the axis of the poles and Fig. a--Cut-away view of conventional waterwheel generator.
I tic, other in quadrature thereto. When the study of the
t,r:rnsic:ntsassociated with system stability was undertaken this conception was quickly rc%cognizedas an invnl~~r~ble
too11*2. Since that time the method has been estcncled by
subsequent invest’igators,3-g notably Dohert,y and Sickle,
who introduced into t,he industry several new const:tntS,
such as transient reactance and subtransient reactance to
describe machine performance under t,rnnsicnt, conditions.
This chapter treats of the charnctcristics of synchronous
and induction machines in the light of the tdevc~lopment of
the past twenty-five years. It {vi11 consitler steatly-state
and transient conditions for both salient pole :tn(.l cylin-
drical rotor machines under both txd:~llccttl ancl r~nt):Jnncetl
conditions. There follows a discussion of the character-
istics of induction motors uncler such transient c*on(lit ions
as might contribute to the short-circuit currc:nt ot' :L sy.?tem
and might influence the choice of a circuit breaker.

I. STEADY-STATE CHARACTERISTICS OF
SYNCHRONOUS MACHINES
The two general types of synchronous machines are the
cylindrical rotor machine or turbine generator wliic*li has
an essentially uniform air gap and the salient-pol(> gc’ner-
ator. Figs. 1 to 5 illustrate the outward appc~a~~ncesand
cross-sectional views of typical modern macliincx
Typical saturation curves for a tiydrogc~n-coolc~~lturbine
generator, a waterwheel-generator and a synchronous con-
denser are shown in Figs. 6, 7, an(1 8 respectively.
Because of the necessity of matching the speed of water-
Fig. l-cut-away view of umbrella-type waterwheel wheel-generators to the requirements of the waterwheels
generator. it is difficult to standardize units of this type. IIowever,
145
146 Machine Characteristics Chapter 6

Fig. 5-Hydrogen-cooled frequency changer set installed on


the system of the City of Los Angeles, 60 000 kva; 600 rpm;
50 cycle-t1 500 volts; 60 cycles-13 200 volts.

rent. Depending upon the application, either the field


current for rated voltage in the air gap or the actual field
current for rated voltage, including saturation, is used.

1. Unsaturated Cylindrical-Rotor Machine Under


Steady-State Conditions
Fig. a--Steam turbine generator installed at the Acme Sta- The vector diagram of Fig. 9 is the well-known diagram
tion of the Toledo Edison Company, 90 000 kw, 85-percent
power factor, 85-percent SCR., 13 800 volt, j-phase, 60-cycle.
of a cylindrical-rotor machine. Consistent with the policy
of this book, familiarity with this diagram is assumed. Let
great strides have been made with large 3600-rpm con- it suffice merely to indicate the significance of the quan-
densing steam turbine-generators. These find their great- tities. The vectors e, and i represent the terminal voltage
est application in the electric utility industry. Table 1 of to neutral and armature current, respectively. Upon add-
Chap. 1 gives some of the specificationsZo for these ing the armature resistance drop, ri, and armature leakage
machines. reactance drop, xli’to et, the vector er is obtained, which
The concept of per-unit quantity is valuable in compar- represents the voltage developed by the air-gap flux a,
ing the characteristics of machines of different capacities which leads el by 90 degrees. This flus represents the net
and voltages. However, care must be exercised in the case flux in the air gap. To produce this flux a field current, It,
of generators to use the same reference value for field cur- is required. The current It can be taken from the no-load

Fig.
Chapter 6 Machine Characteristics

ov I I /I I I I I I
0 .5 1.0 1.5 2.0 2.5 3.0 3.5 4.0
FIELD AMPERES-PER UNIT PER UNIT FIELD AMPERES

Fig. 6--Saturation curves for typical hydrogen-cooled turbine Fig. S-Saturation curves for typical hydrogen-cooled con-
generator. denser.

field current If; it is the voltage taken from the air-gap line
of the no-load saturation curve for the abscissa corre-
sponding to Zr. The side Z1B of the triangle, since it is pro-
portional to Ai and consequently proportional to the arma-
ture current, can be viewed as a fictitious reactance drop.
It is called the drop of armature reactance and is desig-
nated x&i. The reactance drops z& and x,,i can be com-
bined into a single term called the synchronous reactance
9 drop and there results
xd=x,+z, iI)
It follows from the foregoing that the internal voltage, ei,
is equal to the vector sum of et, ri and j s,ii. The field
current, Zr, can be determined for any condition of loading
(neglecting saturation, of course) by merely calculating
ei and taking Zr from the air-gap line of Fig. 10.
At no load the axis of the field winding, the line OC, leads
the terminal voltage by 90 degrees. At zero power-factor,
1.5 2.0 2. the vector diagram reduces to that shown in Fig. 11, which
FIELD AMPERES-PER UNIT
shows that, except for the effect of the resistance drop, the
foregoing statement would still be true. As ri is only about
Fig. 7-Saturation curves for typical waterwheel generator. one or two percent in practical machines, the statement

saturation curve of Fig. 10 as being the current required


to produce el. But, the armature current produces an mmf
by its so-called armature reaction, which is in time phase
with it and in terms of the field can be expressed as Ai. To
produce the net mmf represented by the current, It, the
field current must be of such magnitude and the field
structure must adjust itself to such position as to equal Zr.
In other words, Zr has now such position and magnitude
that Zr and Ai added in vectorial sense equals I,. The
triangle OAB, formed by drawing A B perpendicular to i or
Ji and OB perpendicular to OC, is similar to the triangle
OX’; OB has the same proportionality to OC and AB to
:li as ei has to It. Neglecting saturation, OB, designated
as ei, is thus the open-circuit voltage corresponding to the Fig. g-vector diagram of cylindrical-rotor machine.
148 Machine Characteristics Chapter 6

a NO LOAD done, it can be seen that x:,i can likewise be thought of as


SATURATION cuRvE arising from the two components of i in the form of z,,&
and z,,i,, respectively, in leading quadrature to id and i,.
In
--- the case of.a_cylir?dyical.rot,or machine, X~,Jand z,,are
both- equal to x, but a case will soon be developed for whi&
they are not equal.
The synchronous react’ance, x,1, can be obtained most
conveniently from the no-load curve and the full-load zero
power-factor curve. In Fig. 10 OJ is the field current
required to circulate full-load clurent under short-circuit
conditions, the terminal voltage being zero. In this case
all of the internal voltage (the ri drop can be neglected
justifiably) must be consumed as synchronous reactance
drop (xdi) within the machine. If there were no saturation,
the internal voltage can be determined by simply reading
the terminal voltage when the short-circuit is removed,
RATED-CURRENT
SATURATION CURVE
maintaining the field current constant ‘X&ti@h%e. This
voltage wolrld in Fig. 10 be equal to nB. Thus the un-
saturated synchronous reactance per phase is equal to the
phase-to-neutral voltage ilB divided by the rated current.
When the saturation curve is csprcssed in per unit or per-
cent it is equal to AB; but where expressed in generator-
FIELD CURRENT
terminal voltage and field amperes, it is equal to p(100)
fz
Fig. IO-No-load and full-load zero power-factor character- Ifsi .
istics of a generator. in percent or F m per unit.
fg
2. UnsaturatedSalient-PoleMachineUnderSteady-
State Conditions
If
Ai Given the proper constants, the performance of an un-
saturated
_-. salient-pole machine at zero power-factor% the
same as for a uniform air-gap machine. For other power-
It
factors, conditions are different. A vedor diagram for such
machines is shown in Fig. 12. As before e, and i are the

/
6

it
Fig. ll-Vector diagram of cylindrical-rotor generator at zero
power-factor. Fig. 12-Vector diagram of salient-pole machine.

can be accepted as true for all practical purposes. How- terminal volt,age to neutral and the armature current,
ever, as the real load is applied to the machine the angle 6 respectively, and er is the ‘Lvoltage behind the leakage
increases from zero and the lead of OC ahead of et increases reactance drop.” The flux@ is required to produce ei. This
from 90 degrees to 90 degrees plus 6. The angle -__6 is a real
~.- flux can be resolved into two components +pdand aQ. The
angle; it can be measured without much difficulty-. flux @d is produced by If and Aid, the direct-axis com-
--T~isc~~~i‘i--~~~-~orne purposes to resolve the reac- ponent of Ai, and a1 is produced by Ai,, the quadrature-
tions within the machine into two components, one along axis component of Ai. Here the similarity ceases. Because
the axis of the field winding and the other in quadrature of the saliency effect, the proportionality between the
thereto. In Fig. 9, the armature current is divided into mmf’s and their resultant fluxes is not the same in the two
the two components, id, and, i,, in which the subscripts are axes. When saturation effects are neglected +d canbe re-
significant of their respective components. When this is garded as made up of a component produced by If acting
Chapter 6 Machine Characteristics 149

FUNDAMENTAL COMPONENT the projection of BF upon OG is equal to r,ii,i so that OG


becomes equal to rrl, the fictitious internal voltage, which
is proportional to If.
~r)$qx
The armature resistance is usually negligible in deter-
mining either the angle 6 or the excitation and for this case
ft sin fi=r,i,=r,i cosC++6) (2)
Cpon expanding the last term and solving for 6
(4 (b) .r,i cos $h
tan 6 = _____ 13)
Fig. 13-Flux resulting from a sinusoidal mmf in e,+x,i sin I$
(a) direct axis, From Fig. 14, the internal voltage
(b) quadrature axis.
fd=ft cos 6+x,& sin ($+6) (4)
alone and a component produced by Aid. The component The unsaturated synchronous rcactnnce, ~~1,can be de-
,,roduced by If can be rkgardkd as producing the internal termined from the no-load and full-load zero power-factor
v(jltage c,l. The mmf produced by Aid has a general sinu- curves just as for the machine with uniform air gap. The
soit1a.ldistribution in the direct axis as shown by Fig. 13(a). quadrature-axis synchronous reactance is not obtained so
‘~11~: resultant flux because of the variable reluctance of the
air gap has the general shape indicated. It is the sinusoidal
c:omponcnt of this flux that is. effective in producing the
x,,,, id drop shown in Fig. 12.> Tn the quadrature asis, the
component of mmf is hkewis& smusoidal in nature as shown
in Fig. 13b, and gives rise to the distorted flux form. In
proportion to the mmf the sinusoidal component of flus is
mllcshless than for the direct axis. The effect of this com-
poncnt is reflected in the z,, i, drop of Fig. 12. --In general
L,,, is much smaller than x,d.
‘l’hc armature re&%ance and leakage reactance drops
~a11also be resolved into its two components in the two
ascs much as z,i of Fig. 9 was resolved. When this is done
1.1~internal voltage ed can be obtained by merely adding
ri,l and ri, and then j zq i, andj xd id to the terminalvoltage
* c,. The notat,ion ed is used to differentiate the internal
voltage in this development from that used with the
cylindrical rotor machine theory. .
Another form of the vector diagram of the machine is FOR SIGNIFICANCE OF QUANTITIES IN PARENTHESES REFER TO FIG.18
presented in Fig. 14, which shows much better the relation
I)ol,ween those quantities that are most useful for calcula- Fig. 15-Determination of internal angle, 6, and excitation
1ion purposes. If from B the line BP of length z,i is drawn of a saturated salient pole machine when loading is known.
pc>rpendicular to i, then since angle CBP is equal to 4+6,
the distance BC is equal to CC~~ cos (++6), or zgig. By easily but fortunately there is not as much need for this
comparing this line with the corresponding line in Fig. 12, quantity. It can be determined from a test involving the
it, (‘an be seen that the point P determines the angle 6. This determination of the angular displacement of the rotor as
rclnt’ion provides an easy construction for the determina- real load is applied to the machine and the use of Eq. C2),
Lion of the angle 6 having given the terminal voltage, the which gives
:u’mature current, and the power-factor angle, 4. Further, f, sin 6
(5)
x”=i cos (q5f6)
F
or it can be determined by means of a slip test. The slip
test is described in the A.I.E.E. Test Code for Symhronous
0 MachinesLo of 1945 for a determination of sd. The test for
the determination of Z~ is identical except t,hat the mini-
mum ratio of armature voltage to armature current is used.
3. Saturation in Steady-State Conditions
: -.----
Short-circuit ratiolis
~~.~_ a term used to give a measure of the
relative strengths of the field and armature ampere turns.
It._.--
is defined-as the rgtis of tho field current required to
produce rated armature voltage at no load- to the fi&l
Fig. ll-Det ermination of internal angle, C, and excitation of current required to circulate rated armature current \mth
*n unsaturated salient-pole machine when loading is known. the armature short-circuited. In Fig. 10 the SCR is equal
- -r
150 2 Machine Characteristics Chapter 6
‘.

becomes determinable from Eq. (1) or from the triangle


to F. When no saturation is present it is simply the just discussed.
la1
reciprocal of the synchronous impedance, 2d. The foregoing analysis is not strictly correct, as it neg-
It is impossible to specify the best specific SCR for a lects certain changes in saturation in the pole structure.
given system. In the past it has been the practice in Eu- The leakage from pole to pole varies approximately pro-
rope to use somewhat smaller SCR’s than was the practice portional to the field current and the point T was deter-
in this country. In recent years, however, the trend in this mined upon the basis that this leakage was proportional
country has been toward smaller values. The Preferred to the field current MS. The increased field leakage at the
Standards for Large 3600-rpm Condensing Steam Turbine- higher excitation produces greater saturation in the field
GenerntorszO specifies SCR of 0.8.,,&,,; poles and this in turn increases the mmf required to force
The desire for smaller SCR’s springs from the fact that the flux through the pole. The net effect is to increase the
the cost is smaller with smaller SCR. On the other hand, field current over that determined by the method just
static stability is not as good with smaller SCR. Reguln- discussed causing the two curves to separate more at the
tion is also worse but both of these effects are alleviated in higher voltages.
part by automatic voltage regulators. For most economical The concept of the determination of the curve of rated
design a high SCR machine usually has a lower xd’. There- current at zero-power-factor by the method just described
fore, both because of its lower xd’ and higher WR2 a high is valuable and in an attempt to retain the advantages of
SCR has a higher transient stability. This is not usually this method the concept of Potier reactance, xp, is intro-
a significant factor particularly in condensing turbine ap- duced. The Potier reactance is the reactance that, used in
plications, because transient stability is not of great im- a triangle of the general type described, will just fit be-
portance in the systems in which they are installed. It tween the two curves at rated voltage. It can be deter-
may be quite important for hydro-generators; the Boulder mined from test curves, see Fig. lG, by drawing DE equal
Dam machines, for example, are designed for SCR’s of
2.4 and 2.74.
The effects of saturation arise primarily in the deter-
mination of regulation. Tests indicate that for practical
purposes both the cylindrical rotor and the salient-pole
machine can be treated similarly. Consideration will be
given first to the characteristics for zero-power-factor load-
ing. Fig. 11 shows that for zero power-factor, the ri drop
of the machine is in quadrature to the terminal voltage
and internal drop and can have little effect upon regulation.
It will therefore be neglected entirely.
The determination of the rated-current zero-power-
factor curve can be developed as follows. Take any ter-
minal voltage such as MN of Fig. 10. The voltage behind
leakage reactance is obtained by adding to this voltage the
leakage reactance drop, SR, which gives the line PQ. The
distance PR then gives the field current necessary for
magnetizing purposes. In addition, however, field current
is required to overcome the demagnetizing effect of the
armature current. This mmf is represented on the curve
by the distance ST, giving MT as the field current required,
to produce the terminal voltage OM with rated current
in the armature. Other points on the rated-current
zero-power-factor curve can be obtained by merely Fig. 16-Zero power-factor characteristics of generator.
moving the triangle RST along the no-load saturation
curve. to OA and then EF parallel to OB. The distance FG is
Upon sliding’the triangle RST down to the base line, it then the Potier reactance drop. Potier reactance is thus a
can be seen that the total field current required to circulate fictitious reactance that gives accurate results for only one
rated current at short circuit which is represented by the point, the point for which it is determined. For most ma-
point 4, can be resolved into the current OD necessary to chines it is sufficiently accurate to USCthe one value ob-
o&&%i& leakage reactance drop and the current DA re- tained at rated voltage and rated current. Potier reactance
quired to overcome demagnetizing effects. Neither leakage decreases with increased saturation. Sterling Beckwithlg
reactance nor the field equivalent of armature current are proposed several approximations of Potier reactance, the
definite quantities in the sense that they can be measured two simplest are:
separately. They may be calculated but their values are 2,=x*+0.63~xd’-x,)
dependent upon the assumptions made for the calculations.
Synchronous reactance, zd, is a definite quantity and is and
equal to the distance A0 expressed in either per unit or 2, = 0.8 xd’.
percent. When either XI or x8 is assumed, then the other For other loads at zero-power-factor, the conventional
Chapter 6 Machine Characteristics 151

method is to divide the lines BA and FD of Fig. 16 in


proportion to the armature current. Thus for three-fourt.hs / ‘I.-, LOAD
rated current the regulation curve would be the line H.1 in ATION CURVE
which RH and FJ are three-fourths of BA and FD, \

respectively.
For power-factors other than zero, several methods are
available to determine the regulation. They all give sur-
prisingly close results, particularly at lagging power-
factors. The problem may take either of two forms; the
tlctermination of the terminal voltage when the load cur-
rent, load power-factor, and excitation are given, or the
determination of the excitation when the load current, load
power-factor, and terminal voltage are given. The resist-
ance drop is SO small that it is usually neglected. FACTOR RATED

(a) Adjusted Synchronous Reactance Method*-


This method utilizes the no-load and the rated-current
zero-power-factor curves. To obtain the excitation at any
other power-factor for rated current, an arbitrary excita-
tion is chosen such as OC of Fig. 17. -The no-load voltage

NO LOAD SATURATION CURVE


0 FIELD CURRENT
80% POWER
FACTOR Fig. IS-Determination of excitation, including the effects of
saturation.
b’
.’
the point F. The vertical distance OF is then the terminal
/ voltage for the particular excitation. Following this pro-
cedure another excitation is chosen and the construction
repeated from which the dotted line is obtained. The inter-
section of the line with the normal voltage gives the excita-
tion for the desired power-factor at rated load. If the
machine is not operating at rated current, the zero-power-
factor curve corresponding to the particular current should
be used.
(b) General Method-For lack of a better name this
method has been called the ((General Method.” It is based
upon the assumption that saturation is included by reading
the excitation requirements from the no-load saturation
curve for a voltage equal to the voltage behind the Potier
reactance drop.
The method is described in Fig. 19 with all terms ex-
pressed in per unit. The voltage, e,,, is the Potier internal
voltage or the voltage behind the Potier reactance drop.
P~WEFWACTO
ANGLE

Fig. 17-Determination of regulation curves for power-factors


other than zero by the “adjusted synchronous reactance
method.”

C.4 is then regarded as an internal voltage and the distance


JB as an internal drop of pure reactance, which is laid off
in proper relation with the terminal voltage as indicated
hy the power-factor of the load. The construction is as
follows: The adjusted synchronous reactance drop AB is
hid off to m ak e an angle with the X-axis equal to the
power-factor angle. A line equal to the distance AC is then Fig. 19-Determination of field current for round rotor
scribed from the point A until it intercepts the Y-axis at machine with saturation included by adding s in phase
_-
“Uescribed m Method (c) Para. 1.540 in Reference 10. with ep.
152 Machine Characteristics Chapter 6

The tlistancejk represents the synchronous reactance drop,


~,,i. If there were no saturation the synchronous internal
voltage would be Ok. When using per unit quantities
t,hroughout this is also equivalent to the field current.
This method includes the effect of saturation by simply
adding sI the increment in field current for this voltage in
escess of that required for no saturation, to Ok in phase
with e,,, giving as a result, Oh. When per unit quantities
are not used the construction is a little more complicated.
It involves the construction of ep separately so that s can
be obtained in terms of field current. This quantity is then
added to the diagram for no saturation in terms of the field
current. In Fig. 18, first lay off from the terminal voltage,
On, and t,hen the Z, drop ac at an angle with the horizontal
KW - PER UNIT
equal to t,hr power-factor angle. Oc then represents e,,. I3y
scribing this back to the ordinate and reading horizontally,
the excitation corresponding to this voltage is obtained.
The effect of saturation is introduced by the distance s.
The field current required if there were no saturation is
obtained by the construction Oj andjk where Oj repwscnts
the excitation, ap, required to produce the terminal voltage
at no load and jk the excitation, ot, for the synchronous
reactance drop, read from the abscissa. These vectors
correspond to et and jk, respectively, in Fig. 19 escept
that they are in terms of field current. If kh, equal to the
saturation factor, s, is added along a line parallel to Oc,
the total excitation Oh is obtained. .9
(c) Round Rotor Potier Voltage Method*-This
Fig. 20-Reactive power capacity of steam turbine generator
method is the same as (b) except that the effect of satura-
20 000 kw, 23 529 kva, 0.85 p.f., 0.8 SCR, at 0.5 psig hydrogen.
tion s, in Fig. 18 is, for the sake of simplicity laid off along
012, making om the desired excitation. As can be seen, sending voltage held at a const,ant value ed. As shown in
there is little difference between those two methods. This Chaps. 9 and 10 the power circle of a line of such character-
method gives the best overall results, especially at leading 2
power factors. The particular name of this method was istics has its center in the negative reactive axis at %- and
assigned to distinguish it from the next method. xd

(d) Two-Reaction Potier Voltage Method-This edet


its internal voltage, ed, must be such that its radius, -,
method is similar to that of (c), except that the two-reac- xd
tion method of construction shown in Fig. 14 is used to passes through the point of rated real power and rated
determine the excitation before including the saturation reactive power. Actually, however, the center is usually
factor s. Fig. I.5 shows the entire construction, For the located at a point equal to (SCR) times (rated kva). This
sake of comparison with other methods, the construction is to take care of saturation effects. Since, however, with
is also shown in Fig. 18. The construction is the same as
no saturat,ion ?- is equal to SCR, it can be seen that for
(c) except that the line Oq is made to pass through the xd
point ginstead of k. This arises because X~is smaller than xd., this condition both relations reduce to an equivalence.
The leading kvar capacity (underexcited) of air-cooled
4. Reactive Power Capacity condensers is usually about 50 percent of the lagging kvar
The capacity of a synchronous machine to deliver re- capacity but for hydrogen-cooled condensers about 42
active power is dependent upon the real power that it percent.
delivers. Two limitations from the heating standpoint are
recognized: (1) that due to the armature, and (2) that due II. THREE-PHASE SHORT CIRCUIT
to the field. Figure 20 shows the reactive power capability In addition to its steady-state performance, the action
of a standardized 3GOO-rpmsteam turbine-generator. Real of a machine under short-circuit conditions is important.
power is plotted as abscissa and reactive power as ordinate. The presence of paths for flow of eddy currents as provided
All the curves are arcs of circles. The line centering abont by the solid core in turbine generators and by the damper
the origin represents the limit imposed by the condition of windings in some salient-pole machines makes the treat-
constant armature current whereas the other arc by con- ment of these machines, from a practical viewpoint, less
stant field current. With regard to the latter, the generator complicated than that for salient-pole machines without
can be likened to a simple transmission line of pure react- damper windings. For this reason the three-phase short-
ance, zd, with the receiver voltage held at a constant value, circuit of these types of machines will be discussed first.
et, the terminal voltage of the generator, and with the Armature resistance will be neglected except as it influences
*Described as Method (a) Para. 1.520 in Reference 10. decrement factors.
Chapter 6 Machine Characteristics 153

5. Three-phase Short-Circuit of Machines with .q.- 5 Voltoge from air-gap line corresponding
current Paths in Field Structures id : to no-load
..
excitation /
I %
xd
Consideration will be given to a simultaneous short- = Steody-stote value
circuit on all phases while the machine is operating at
no-load normal voltage without a voltage regulator.
The general nature of the currents that appear is shomn
in Fig. 21. They can be divided into two parts:
a. An alternating component in the armature and as-
soc.i:lted,n-ith it an unidirectional component in the field.
I’~(w two components decay or decrease together with the

TIME

Fig. 22--Symmetrical component of armature short-circuit


current (three-phase short circuit from no-load rated volt-
age). Values are rms.

tion is important only as it affects the field current neces-


sary to produce normal voltage at no load. The steady-
state value of short-circuit current is thus equal to the
line-to-neutral voltage read from the air-gap line for the ,,
value of field current required to produce normal voltage
divided by the synchronous reactance in ohms.
Transient Component-If the cswss of the symmet-
rical component of armature currents over the steady-state
component be plotted on semi-log paper, it can be seen
that this excess, except for the first few cycles, is an es-
ponential function of time ithe points lie in a straight line).
Estending this straight line back to zero time and adding
Fig. at--Three-phase short circuit in salient-pole machine the steady-state component, the so-called transient com-
with damper windings. ponent, id’, or armature current is obtained. This compo-
nent is defined through a new reactance, called the transient
same time constants. The alternating armature component reactance by means of t,he expression
c:m be regarded as being produced by its associated uni-
% id’ = erated
__
tlircctional component in the field. All phase components
of the alternating current are essentially the same except x’d

I hat they are displaced 120 electrical degrees.* ? The manner in which this quantity is related to the es-
1). An unidirectional component in the armature‘&.rd’an poncntial and steady-state terms is shown in Fig. 22.
alternating component in the field or in the damper wind- In discussing this component, the presence of the
ings. In this case, likewise, the alternating current in the damper-winding currents of salient-pole machines and
field winding can be regarded as produced by the uni- rotor ‘%dy currents of turbine generators can, for the
(lircctionnl component in the armature. moment, be neglected. Before short-circuit occurs the flux
associated with the field windings can be broken up into
6. Alternating Component of Armature Current two components (see Fig. 23), a component Cpthat crosses
This component can in turn be resolved into several the air gap and a component ai, a leakage flux that can
components, the r.m.s. values of which are shown in Fig. be regarded as linking all of the field winding. Actually,
22. They are: of course, the leakage flux varies from the base of the pole
:L The steady-state component to the pole tip. The flux ~91is so weighted that it produces
1). The transient component the same linkage with all the field turns as the actual leak-
c. The subtransient component age flux produces with the actual turns. It is approximately
proportional to the instantaneous value of the field current
loach of these components will be discussed separately. 1r. The total flux linkages with the field jvinding are then
Steady-State Components-The steady-state com- those produced by the flux (@++.I). As the field structure
ponent, as its name implies, is the current finally attained. rotates, a balanced alternating voltage and current of nor-
Ijecause of the demagnetizing effect of the large short- mal frequency are produced in the armature. Because the
circuit current, the flux density within the machine de- armature resistance is relatively small, its circuit can be
creasesbelow a point where saturation is present. Satura- regarded as having a power-factor of zero. The symmet-
*The machine used in this case was a salient-pole machine. As rical current thus produced develops an mmf that rotates
wi’l be seen later such machines also contain a second harmonic synchronously and has a purely demagnetizing, as con-
ConWonent of curlent. This type of machine was chosen to show trasted with cross magnetizing, effect on the field fluxes.
more clearly the presence of field and damper currents. It is a well-known fact that for the flux linkages with a
154 Machine Characteristics Chapter 6

possible to increase the exciter voltage instantaneously to


an amount that would produce this steady-state field cur-
rent, then this component of short-circ!lit current would
remain sustained. It is important tk”@%$p the significance
of this !#l%. l’here is always a constant proportionality
between the alternating current in t,he armature and the
unidirectional (often called direct-current) component of
current in the field winding, whether the operating condi-
tion bc steady-state or transitory.
The initial value of armature current, as stated, grad-
ually decreases to the steady-state and the induced current
in the field winding likewise decreases to its steady-state
magnitude. The increments of both follow an exponential
curve having the same time constant. Attention will next
be given to considerations affecting this time constant.
If a constant direct voltage is ~%&l$ifiKapplied to the
field of a machine with the armature open-circuited, the
current’ builds up esponentially just as for any circuit hav-
Fig. 23-Air-gap and leakage fluxes at no load. ing resistance and inductance in series. The mathematical
expression of this relation is:
circuit to change instantly, an infinitely large voltage is
necessary and the assumption is justified that, for the tran-
03)
sition period from the no load open-circuited condition to
the short-circuited condition, the flux linkageswith the field in which
winding can be regarded as constant. This is equivalent to
e, is the exciter voltage.
saying that the flux (+++I) remains constant. In order
rf is the resistance of the field winding in ohms.
that this flux remain constant in the presence of the de-
T&, is the open-circuit transient time constant of the
magnetizing effect of the armature current, it is necessary
machine or of the circuit in question in seconds.
that the field current If increase to overcome the demag-
t is time in seconds.
netizing effect of the armature current. If If increases then
@I, which is proportional to it, must likewise increase. It The time constant is equal to the inductance of the field
follows then that @ must decrease. Consideration of the winding divided by its resistance. In the case of the short-
steady-state conditions has shown that the air-gap voltage, circuited machine, it was shown that at the first instant
et, is proportional to the air-gap flux +. The armature the flux linkages with the field winding remain the same
as for the open-circuit condition, but that the direct com-
current for short-circuit conditions is equal to z. If + and
ponent of field current increases to s times the open-
consequently el had remained constant during the trsnsi- xd’
tion period, then the transient component of short-circuit circuit value before short-circuit. Since inductance is
current would be merely the no-load voltage before the defined as the flux linkages per unit current, it follows
short-circuit divided by the leakage reactance and the then that the inductance of the field circuit under short-’
transient reactance would be equal to the armature leakage I
reactance ~1. However, as just shown, the air-gap flux circuit must equal 5 times that for the open-circuit con-
decreases and, therefore, the armature current is less. ,It dition. The short-c?cuit transient time constant that is
follows then that the transient reactance must be greater the time constant that determines the rate of decjy of thl
than the armature leakage reactance. It is a reactance transient component of current must then equal
that includes the effect of the increased field leakage
occasioned by the increase in field current. Td’ = “T’d,, in seconds
Under steady-state conditions with no saturation, the xd
armature current can be viewed as produced by a fictitious The component of armature current that decays with
internal voltage equal to 2d id whose magnitude is picked /
this time constant can then be expressed by 1I
from the air-gap line of the no-load saturation curve for
the particular field current. At the first instant of short-
circuit, the increased armature current, id’, can likewise be
viewed as being produced by a fictitious internal voltage When t is equal to Td’ the magnitude of the component/
behind synchronous reactance, whose magnitude is x&d’ or has decreased to e-l or 0.368 times its initial value. This.
erated
xd---- if the short-circuit be from rated voltage, no load. instant is indicated in Fig. 22.
xd’ ’ Subtransient Component-In the presence of d
This voltage provides a means for determining the initial er windings or other paths for eddy currents as in tu
value of the unidirectional component of field current by generators, the air-gap flux at the first instant of s
picking off the value of If on the air-gap line of the no-load circuit’ is prevented from changing to any great ext
saturation curve corresponding to this voltage. If it were This results both from their close proximity to the air
Chapter 6 Machine Characteristics 155

and from the fact that their leakage is much smaller than only one can equal zero at a time. Therefore at times of
that of the field winding. Consequently, the initial short- three-phase short-circuits, the alternating component of
circuit currents of such machines are greater. If this excess current in at least two and probably all three phases must
of the symmetrical component of armature currents over change from zero to some finite value. Since the armature
tlrc transient component is plotted on semi-log paper, the circuits are inductive, it follows that their currents cannot
straight line thus formed can be projected back to zero change instantly from zero to a finite value. The “theorem
time. This zero-time value when added to the transient of constant flux linkages” must apply to each phase sepa-
,,,mPoncnt gives the subtransient current, id”. This sub- rntely. The application of this theorem thus gives rise to
l,.arl,sicnl current is defined by the subtransient reactance in an unidirectional component of current in each phase equal
the csprcssion and of negative value to the inst,antaneous values of the
alternating component at the instant of short circuit. In
&ted
id” = - this manner the armature currents are made continuous as
Xd)’
shown in Fig. 24. Each of the unidirectional components
Tlrc subtransient reactance approaches the armature leak-
LLgcdiffering from that quantity only by the leakage of the
&rmPcr windings.
Since the excess of the armature currents represented
1)~ t,he subtransient components over the transient com-
lroncnts are sustained only by the damper winding cur-
rents, it would be expected that their decrement would be
tlotcrmined by that of the damper winding. Since the
SYMMETRICAL
copper section of this winding is so much smaller than COMPONENT
t,hat of the field winding, it is found that the short-circuit
srrbtransient time constant, Td”,’ is very small, being
:J)out 0.05 second instead of the order of seconds as is Fig. 24-The inclusion of a d-c component of armature
(*tr:uacteristic of the transient component. The component current whose existence is‘necessary to make the armature
of armature current that decays with this time constant is current continuous at the instant of short circuit.
(id” -id’) and can be expressed as a function of time as
in the three phases decays exponentially with a time con-
(i:’ -id’) E stant T,, called the armature short-circuit time constant.
The magnitude of this time constant is dependent upon
Thus the time in seconds for this component to decrease the ratio of the inductance to resistance in the armature
9 t,o 0.368 times its initial value gives Td” as indicated in circuit. As will be shown the negative-sequence reactance,
Fig. 22. ~2, of the machine is a sort of average reactance of the
Tests on machines without damper windings show that armature with the field winding short-circuited, so that it
becauseof saturation effects, the short-circuit current even is the reactance to use in determining T,. There exists then
in this case can be resolved into a slow transient component the relation
and a much faster subtransient component. The influence
of current magnitudes as reflected by saturation upon the T,= -inx2 seconds (8)
transient and subtransient reactance is discussed in more 2+,
dcLai1under the general heading of Saturation. in which rB is the d-c resistance of the armature. The
quantity 27rf merely converts the reactance to an induc-
7. Total Alternating Component of Armature Cur- tance.
rent The maximum magnitude which the unidirectional
‘l’lrc total armature current consists of the steady-state
v:rllrc and the two components that decay with time con- PROJECTION AXIS FOR PHASE b
Sl:IIlts Td’ and Td”. It can be expressed by the following \’
~‘~lllation
-- 1 -- t
$,,=(i;‘-i:)~ Td”j-((ii-&)E Td’+id

‘Ilrc quant,ities are all expressed as rms values and are equal
l)ut displaced 120 electrical degrees in the three phases.
8. Unidirectional Component of Armature Current
To t)his point consideration has been given to flux link-
ages with the field winding only. The requirement that
tlrcse linkages remain constant at transition periods de- (a) (b)
termined the alternating component of armature current.
Fig. 25-Representation of instantaneous currents of a three
Since these components in the three phases have a phase phase system. (a) Three separate vectors projected on x-axis,
displacement of I20 degrees with resnect to each other. Cb) Single vector projected on three axes.
156 Machine Characteristics Chapter 6

component can attain is equal to the maximum of the The short-circuit time constant is affected in a similar
alternating component. Therefore, manner
xd’fxext .
ide(max.) = fi 5 (9)
TdIE-.--.- Tdf, m seconds
xd+&t

A symmetrical three-phase set of currents can be repre- For the armature time constant, the esternal reactance
sented as the projection of three equal-spaced and equal must be added to the negative-sequence reactance of the
length vectors upon a stationary reference, say the real machine and the external resistance to the armature resist-
asis. They can also be represented as the projection, as it ance of the machine. The espression then becomes
rotates, of one vector upon three stationary axes, spaced
x2fxext
120 degrees. These axes can conveniently be taken as in seconds
shown in Fig. 25, as the horizontal-axis and two axes hav- Ta=27r.0r,+T,,t)
ing a 120-degree relation therewith. Since the initial mag- Because of the much lower ratio of reactance to resistance
nitude of the unidirectional components are the negatives in external port,ions of circuits, such as transformers or
of the instantaneous values of the alternating components transmission lines, in the vast, majority of cases T, for
at zero time, then the unidirectional components can be faults out in the system is so small as to justify neglecting
represented as the projection of a single vector onto the the unidirectional component of current.
three equal-spaced axes. This fact is used at times to
determine the maximum magnitude which the unidirec- 11. Short Circuit from Loaded Conditions
tional component can attain. By its use it is unnecessary The more usual case met in practice is that of a short-
to await a test in which the maximum happens to occur. circuit on machines operating under loaded conditions. As
This method is in error, however, for machines in which before, the short-circuit current in the armature can be
zg” and Ed” are radically different. divided into two components, a symmetrical alternating
component, and a unidirectional component.
9. Total RMS Armature Current Alternating Component--The alternating compo-
The rms armature current at any instant is nent in turn can be resolved into three components: (1)
steady state, 12) transient, and (3) subtransient. Each of
d/idc2 + cc2
these components will be discussed individually.
The minimum current thus occurs in the phase in which The load on the machine affects the steady-state com-
the unidirectional component is zero and the maximum ponent only as it influences the field current before the
occurs when the unidirectional component is a maximum, short circuit. The field current can be determined by any
that is, when maximum dissymmetry occurs. Since the of the methods discussed under the heading of “Steady-
maximum value that the unidirectional component can State Conditions.” Saturation will be more important than
attain is +‘2 %, then for the no-load condition. The steady-state short-circuit
XA current is then equal to the line-to-neutral voltage read
from the air-gap line for the field current obtained for the
loaded condition divided by xd.
In the discussion of the determination of the transient
Of course, a rms value as its name implies, is an average component from the no-load condition, it was stated that
quantity and is usually taken over a cycle or half cycle the quantity that remained constant during the transition
of time. The foregoing expression assumes that both the period from one circuit condition to another, is the flux
alternating and the unidirectional components do not de- linkages with the field winding. For the short-circuit from
crease, because of the natural decrement, during the first loaded conditions this same quantity can be used as a basis
cycle. In reality the decrement is usually sufficient to* for analysis. Consideration will be given first to a load
make the effect noticeable. In applying circuit breakers before short circuit whose power factor is zero, lagging,
it is usual to use a factor 1.6 instead of 1/?. This factor and whose current is &L. The flux linkages before short
includes a small decrement. circuit will be determined by a superposition method,
obtaining first the linkages with the field winding for zero
10. Effect of External Impedance armature current and any terminal voltage and then the
If the short-circuit occurs through an external imped- flux linkages with armature current, idT,, and zero terminal
ance ~,,~+j x,,~, and r,,, is not too large, their effect can voltage. The total flux linkages is the sum of the two
be introduced by merely increasing the armature constants values so obtained.
by these amounts. Thus the components of short-circuit Let $1 be the flux linkages with the field winding at
current become no-load at rated voltage. For any other terminal voltage
e rated such-as et, the flux linkages tc, will be equal to
ii’ =
xd”+&t

&ted erated
id’=---.-- Cl21
xd’+%xt
By definition the transient reactance of a machine is ’
id =
eairgap *t no lOad
(13) equal to the reactance which, divided into the line-to-
xd+%xt neutral rated voltage, gives the transient component of :
Chapter 6 Machine Characteristics 157

short-circurt current at no-load normal voltage. If this circuit current i’ can be determined by dividing these
short-circuit current is designated as idI, then linkages into the total flux linkages just determined. This
gives
&ted
idll = - (17) J/
i’ = - = et+xd’idL
xd’
(19)
xd’$l xd’
,it the instant of short-circuit from no-load at rated volt-
age, the flux linkages with the field winding, &, remain er3ted

constant. The demagnetizing effect of the armature cur- The numerator of this quantity can be regarded as an
,.cnt is overcome by an increase in the field current. Thus internal voltage, ed’, which is equal to the terminal voltage
the armature current &‘I with its associated field current plus a transient reactance drop produced by the load
which is always proportional to it, can be regarded as pro- current.
ducing the flux linkages $1 with the field winding. For any When the power factor of the loads considered is other
other armature current, id’, assuming always that the than zero lagging, the vector sense of current and terminal
armature is short-circuited, the flux linkages with the field voltage must be introduced. This can be accomplished by
computing cd’ for the operating condition in the same man-
winding are equal to 2,: $1. Combined with Eq. (17),
xd’kh
i,/, can be eliminated giving +=id’-. While this
erated
c\xprrssion was derived from considerations applying only
t,e t,hc instant of transition, its application is more general.
‘rhc only necessary considerations that must bebsatisfied
:~rcthat the armature be short-circuited and that the field
cllrrcnt contain a component of current to overcome the
&magnetizing effect of the armature current. But these
conditions are always satisfied even under steady-state
contlitions of short circuit, so, in general, it is permissible
1.0replace id’ in this expression by i&. The flux linkages
with the field winding for the steady-state short-circuit
xd’$l
condition thus become idL---.
&ted
By application of the superposition theorem, the total
flux linkages with the field winding can then be regarded
as the sum of the flux linkages produced by the terminal
9
voltage, namely A$1 and th ose by the armature cur-
ersted
xd”,h
rent with zero terminal voltage, namely idr,-. If the
&ted REACTANCE IN PERCENT
armature current lags the voltage by 90 degrees, then the Fig. 27-Machine internal voltage as a function of reactance.
linkages are directly additive, and there results for the Full-load rated voltage.
flux linkages with the field
ner that edwas determined in Fig. 14, except that xd should
be replaced by xd’. The voltage ed’ should then replace
et+xd’ &, in (19). However, for nearly all practical pur-
$1
= (et+xdlidL)-. (18) poses it is sufficiently accurate to replace ed’ by the amph-
&ted
tude of a quantity ei’, which is usually referred to as the
Since the flux linkages with the field winding produced voltage behind transient reactance to distinguish it from
hY a unit of current id under short-circuit conditions is similar internal voltages for which leakage, synchronous
qua1 to xA then the transient component of short- or subtransient reactance is used. The construction for
&ted this quantity is shown in Fig. 26 and to assist in the ready
evaluation of the amplitude the curves in Fig. 27 are
provided. The transient component of short-circuit current
is then

The subtransient component of short-circuit current is


obtained in a manner similar to the transient component
except that the subtransient reactance is used in the calcu-
‘k 26-Construction for the determination of internal volt- lation of the internal voltage ei”. For loads of zero-power-
ages ei’ and ei”. factor lagging the subtransient reactance drop, xd”&
158 Machine Characteristics Chapter 6

cnuscd by the armature current is directly additive to the


terminal voltage and for zero-power-factor leading directly
subtractive. For other power-factors ei” can be obtained
from Fig. 27 by using zd”. The subtransient component of
short-circuit current is then
zd - zrl
ib = --et+ cos (27rjt+a- 1207
x&d’

Unidirectional Component-In the three-phase +z cos (27rjt+cr- 120°)


short-circuit from no load, the unidirectional component
2, - xd’
of current was introduced to prevent a non-continuous --et,-% cos (47rft+cr-120’) I.
transition of the instantaneous value of current from the 2x62,
no-load to the short-circuit condition. The unidirectional &+zd’
--et,-& cos (crf 120”) (23)
current performs a similar role for the short-circuit from 2x;x,
loaded condition. Before the short-circuit the armature . xd-xd’
current is equal to Ida and has some position with reference z,=-e,~-h cos (27rft+a+ 120”) A
xdxd’
to et such as shown in Fig. 28. The subtransient com-
+;cos (27rft+a+ 120”)
e’f 2, - xd’ \ /
------et,-% cos (47rft+a+120°)
2x:x,
xq+zd’
------et,-: cos tcr--120’). (24)
2x:x,
Where
I
et = Terminal voltage before short-circuit.
r2+xd’x
Td’ = qT&. (25;
r2+xllxq ,
2xd’x,
T,= (26)]
hd’+xq)’

c =Angle which indicates point on wave at -which:


short-circuit occurs.
The instantaneous field current, Id, is
Fig. 28-Showing that idofor a short circuit from load is equal
to the negative of 1/2 times the difference between i” and i.
Where
xd-&,’
Id= ------If
x*’ C
E
-c
Td’-6
1
-Gi cos 27gt + If (2

ponent, i”, lags ei” by ninety degrees so i” and Ida will be It = Initial value of field current.
determined with respect to each other. The 42 times the
vector difference between these two quantities (since they III. UNBALANCED CONDITIONS
are rms magnitudes) gives the unidirectional component
necessary to produce smooth transition. The magnitude 13. Phase Currents for Unbalanced Short Circui
of this quantity varies between this amplitude and zero As explained in the chapter relating to Symmetric
depending upon the point in the cycle at which short- Components, the unbalanced operating conditions of
circuit occurs. rotating machine can for most purposes be described
Other Considerations-Time constants are not influ- terms of three characteristic constants: the positive-!
enced by the nature of loading preceding the short-circuit. quence impedance, the negative-sequence impedance, a
Total rms currents can be determined by the relations the zero-sequence impedance. The short-circuit currer
already given. can be resolved, as before, into the steady-state, transiel
and subtransient components. The difference betwe
12. Three-Phase Short Circuit of Salient-Pole Ma- these components decreases exponentially as before. T
chine without Damper Windings components of armature current and the time constar
For most applications it is sufficiently accurate to treat for the different kinds of short-circuits are given below f
the salient-pole machine without damper windings just as stiort-circuits at the terminals of the machine.
other machines. It must be recognized, however, that this For three-phase short-circuit: I
is only an approximate solution. Among other complica- I, I
i”= fi- i’=e’
tions, in reality a strong second harmonic is present in the
armature current. Doherty and NickleG have developed xd” xd’

expressions for the armature currents for a three-phase For terminal-to-terminal short circuit, the a-c componeI
short circuit from no load. These are given below. of the phase currents are given by
Chapter 6 Machine Characteristics 159

;,, _ dei” +, _ dei' up bv the armature current. If the axis of the short-
Y --
circuited field winding lines up with the axis of pulsating
Xd”+X:! Xd’+XZ
. d3Ci X,l’ + x:n ;, field t,hen the current is large and if the rotor is moved
z=- T,,’ = l’ r (29) through 90 electrical degrees then the clu-rent is much
Xd+X? Z,If~” smaller. The first position corresponds to the case of a
in which ~41is the negative-sequence impedance of the transformer in which the secondary winding is short-
,n:lc:hinc circuited, the field winding in this case corresponding to
I?,)r terminal-to-neutral short circuit, the a-c components the secondary winding of the transformer. This is the
()f the phase currents are given by position in which the subtransient reactance, zd”, is deter-
mined. It is equal to one-half of the voltage from terminal-
to-terminal divided by the current. For the second position
the field winding is in quadrature to the pulsating field
i= 3ei Z<,‘+xZ+x” and consequently no current flows in the field winding.
Td’ = T ;I3 (30)
z~i+z2+zo Q+Z2+xo The armature current is then determined by the magnetiz-
in \vhich x0 is the zero-sequence impedance of the machine. ing characteristics of the air gap in the quadrature axis.
‘rllc subtransient time constant, Td”, does not change sig- The subtransient reactance, z~“, is determined when the
rlificantly with different conditions and, therefore, the field is in this position and is equal to one-half the quotient
sing]c value is used for all conditions. The unidirectional of the voltage divided by the current. The reactance fw
,Oomponents and the rms values are determined just as intermediate positions varies between these two amounts
,l~!sc:rit)edunder the general subject of “Short Circuit from in accordance with the curve shown in Fig. 29.
l,&.” The above values of ei, ei’ and ei” will naturally
l,c those values corresponding to the particular load
c:ondition.
The ratio of the phase currents for terminal-to-neutral
t.0t,hree-phase short circuits can be obtained from Eq’s (30)
:tt~tl (28). Thus, for the phase currents
‘i’crminal-to-neutral short circuit 32d”
Three-phase short circuit =x~“+Q+x~
0.6
‘I’hc negative-sequence impedance, x2, is usually equal to
s,~“, but for many machines x0 is less than xd”. For
t lrcse cases, the terminal-to-neutral short-circuit currz
%-&ater th~~~~~~ph~~~-sh~~~~~i~c~it current. The’
-----.__-
Kcnerator s&i&Zls reqmrefliXBi6~ nibchine be. braced
only for currents equal to the three-phase values. In order
Ihat the terminal-to-neutral current not exceed the three- 0.2 -
--’ COPPER DAMPERS
[chasecurrent a reactor should be placed in the neutral of
the machine of such value as to bring the zero-sequence
impedance of the circuit equal to z~“. Thus, the neutral
rwctor, x,, should be OO 30 60 so 120 150 160
ANGULAR POSITION OF ROTOR IN DEGREES
I
x,~-(x~“-x~) Fig. 29-Relation between subtransient and negative-se-
3 quence reactance.
14. Negative-Sequence Reactance When a set of negative-sequence currents is made to flow
‘I’hc negative-sequence impedance of a machine is the through the armature with the field short-circuited and
irnpodance offered by that machine to the flow of negative- rotating in its normal direction, then the field winding
s(‘(llwnce current. A set of negative-sequence currents in takes different positions successively as the armature field
tllc armature creates in the air gap a magnetic field that rotates with respect to it. The nature of the impedances
rl)Mes at synchronous speed in a direction opposite to that in the two extreme positions, that is, where the field wind-
of the normal motion of the field structure. Currents of ing lines up with the magnetic field and where it is in
cl()ul)le frequency are thereby established in the field, quadrature with it, should be somewhat the same as Q”
UN] in the damper windin g if the machine has one. The and xq”, the only signnificant difference being the fact that,
in%innry component of the impedance is called the nega- in the determination of xd” and xq”, currents of normal
(ivc-sequence reactance and the real component the nega- frequency were induced in the field, whereas, in the nega-
‘i\-c-sequence resistance. These will be discussed sepa- tive-sequence case the currents are of twice normal fre-
r:‘tely, in the order mentioned. quency. One would expect therefore that the negative-
If a single-phase voltage is applied across two terminals sequence reactance x2 is some sort of a mean between xd”
of a salient-pole machine without dampers while its rotor and LX,,“,and such is the case. According to the AIEE test
is stationary, the resulting current is dependent upon the code,‘O the definition of negative-sequence reactance is
Position of the rotor with respect to the pulsating field set equal to “the ratio of the fundamental component of re-
160 Machine Characteristics Chapter

active armature voltage, due to the fundamental negative- where I equals the root-mean-square armature current j
sequence component of armature current, to this compo- the short-circuited phase; and E equals the root-meal
nent of armature current at rated frequency.” A rigorous square open-circuit voltage between terminals before tl
interpretation of this definition results in x2 equal to the short-circuit is applied or the no-load voltage corresponl
” + Xd” ing to the field current at which I is read.
arithmetic mean X,1 However, several different defi- In general, the same arguments can be applied to 0th
a *
nitions can be given for x2. That this is possible is depend- types of machines such as turbine generators and salien
ent largely upon the fact that when a sinusoidal set of pole machines with damper windings when the paramete
negative-sequence voltages is applied to the armature the xd” and x4” are used. For such machines the differen
r
currents will not be sinusoidal. Conversely if the currents between x4” and xd” is not great. l?he values for x9”,ar
are sinusoidal the voltages mill not be. xd” of a machine with copper dampers are given in Fig. 2
In Table 1 are shown expressions” for x2 based upon For such machines the difference between xz based on tl
different definitions. This table is based on a machine different definitions of Table 1 will become inconsequentir
without damper windings for which x9” is equal to x,, and In addition, for turbine generators, saturation introduc
zd” is equal to xd’. In this table variables of much greater magnitude than those just co
sidered. For these machines negative-sequence reactan
can be taken equal to xd”.
Method of Test-In addition to the method impli
For each test condition it is possible to establish definitions by the AIEE Code and the ASA whereby x2 is defined
based on whether fundamental or root-mean-square cur- the arithmetic mean for zd” and x9/‘, x2 can be determih
rents are specified. For example, in the first definition if directly from test either by applying negative-sequen
the fundamental component of armature current is used voltage or by the method shown in Fig. 30.
in calculating x2 then the expression in the first column
should be used, but if the root-mean-square figure of the
resultant current is used then the expression in the second
column should be used.
In order to orient one’s self as to the relative importance
of the different expressions, figures have been inserted in
the expressions given in Table 1 for a typical machine
having the constants xd’ = 35%, x, = 70%, and xd = 100%.
The magnitudes are tabulated in the righthand columns
of Table 1. From the standpoint of practical application,
the negative-sequence reactance that would result in the
proper root-mean-square current for method (3) would
appear to be the most important. However, the method I,=0 Ib=I I,=-I
of test to determine this quantity involves a sudden short-
Ea=O Ee=E EC=-E EA$= ?#O+dE--aE)=q
circuit and from this standpoint proves rather inconveni-
ent. On the other hand, the figure for x2 obtained from
the use of the root-mean-square values in a sustained
single-phase short-circuit current [method (4)], is nearly If ~=COS-I&, where P= wattmeter reading,
equal to this quantity. When the resistance is negligible E
this negative-sequence reactance is equal to then, zt=----(sin
4.31
++j cos 4) =r,+jz,

x2=---zd (31) Fig. 30-Determination of the negative-sequence impedar


I of symmetrically-wound machines.

TABLE ~-DEFINITIONS OF NEGATIVE-SEQUENCE REACTANCE

Kumerical Values
Analytical Expressions xd’=%% 2,=70ojo xd= 100%
Definition
Funda- Funda- Root-Mean-
mental Root-Mean-Square mental Square

(1) Application of sinusoidal negative-se- 2xCJ’xc,, 44


quence voltage XtJ+2d’
(2) Application of sinusoidal negative-se- Zq+xd’ 74
quence current 2
(3) Initial symmetrical component of sudden JG 48
single-phase short-circuit current
(4) Sustained single-phase short-circuit current d.rd’.rq 47
(5) Same as (4) with 50% external reactance 50
Zq+5d’
(6) A.I.E.E. and A.S.A.
2
chapter 6 Machine Characteristics 161

\Vith the machine driven at rated speed, and with a single- induces the voltage E, in the stator and SE, in the rotor.
phase short-cu’cuit apphed .between two of its terminals In the rotor the impedance drop is
(neutral excluded) the sustamed armature current and the
voltage between the terminal of the free phase and either T,I*-kjSX,I, (32)
of the short-circuited phases are measured. The reading since the reactance varies with the frequency of the cur-
of a smgle-phase wattmeter with its current coil in the rents in the rotor. The rotor current is therefore deter-
short-circuited phases and with the above mentioned volt- mined by the equation
age across its potential coil is also recorded. The negative-
ycqllence impedance equals the ratio of the voltage to the SE, = r,I,+ jsx,I,
current so measured, divided by 1.73. The negative- Or
sequencereactance equals this impedance multiplied by the
ratio of power to the product of voltage and current. E,=:r,+jx,l, (33)

15. Negative-Sequence Resistance It follows from this equation that the rotor circuit can be
The power associated with the negative-sequence cur- completely represented by placing a circuit of impedance
rent can be expressed as a resistance times the square of :+jr, across the voltage E,. The total power absorbed by
the current. This resistance is designated the negative-
sc(lucnceresistance. For a machine without damper,wind-
?J must be the sum of the rotor losses and the useful shaft
ings the only source of loss is in the armature and field s
rcsist,ances,eddy currents, and iron loss. The copper loss
in the armature and field is small as is also the iron and power, SO that, resolving y into the resistances r, and
&ly loss in the armature, but the iron and eddy loss in l-s
the rotor may be considerable. Copper damper windings ST,, the power absorbed by r, represents the rotor cop-
provide a lower impedance path for the eddy currents and
l-s
lrintlcr the penetration of flux into the pole structure. The per loss. The power absorbed by -r, represents the
relatively low resistance of this path results in a smaller S
negative-sequence resistance than if the flux were per- useful shaft power.
mitted to penetrate into the rotor. For higher resistance Neglecting r. and the real part of z,, the only real power
tlnmper windings the negative-sequence resistance increases is that concerned in the rotor circuit. hssume that the
to :I point beyond which the larger resistance diminishes induction motor drives a direct-current generator. .%t
the current in the rotor circuits sufficiently to decrease small slips the electrical input into the stator is equal to
tt1c loss. the copper loss, i.e., the 12,r, of the rotor plus the shaft
Induction-Motor Diagram-The nature of the neg- load. With the rotor locked, the shaft load is zero, and the
ative-sequence resistance is best visualized by analyzing total electrical input into the stator is equal to the rotor
tlrc phenomena occurring in induction motors. In Fig. 31 copper loss. At 200-percent slip, i.e., with the rotor turning
at synchronous speed in the reverse direction, the copper
Iqr,
loss is I?r,, the electrical input into the stator is 2,
l-2 -I$.,
and the shaft load -r,I: or - A negative shaft
2 2 .
load signifies that the direct-current machine instead of
functioning as a generator is now a motor. Physically that
is just what would be expected, for as the slip increases
from zero the shaft power increases to a maximum and
Fig. 31-Equivalent circuit of induction motor. then decreases to zero for loo-percent slip. A further in-
crease in slip necessitates motion in the opposite direction,
is given the usual equivalent circuit of an induction motor which requires a driving torque. At 200-percent slip the
in which electrical input into the stator is equal to the mechanical
r8 = stator resistance. input through the shaft; half of the copper loss is supplied
ze=stator-leakage reactance at rated frequency. from the stator and half through the shaft. This is the
r,= rotor resistance. condition obtaining with respect to the negative-sequence
zp=rotor-leakage reactance at rated frequency. in which the rotor is rotating at a slip of 200 percent rela-
%=shunt impedance to include the effect of magnetiz- tive to the synchronously rotating negative-sequence field
ing current and no-load losses. in the stator. Half of the machine loss associated with the
En= applied voltage. negative-sequence current is supplied from the stator and
la=stator current. half by shaft torque through the rotor.
I rcrotor current. The factors of fundamental importance are the power
S=slip. supplied to the stator and the power supplied to the shaft,
which can always be determined by solving the equivalent
The justification for this diagram is shown briefly as circuit involving the stator and rotor constants and the
follO\~~:The au-gap
. flux created by the currents I. and I, magnetizing-current constants. A more convenient device,
162 Machine Characteristics Chapter
supplied to the stator, which, in turn is equal to the lc
absorbed by the negative-sequence resistance. Therefor
the total decelerating power is equal to the positiv
sequence power output plus the loss in the negativ
sequence resistance.

0
B1
(a)
zm

I
The assumption was made that the stator resistan
and the losses in the magnetizing branch were neglectc
For greater refinements, the stator resistance and the 10s:
jxs jX, in the magnetizing branch can be taken into considerati

u!c
L A by substituting them in the equivalent circuit and reduci
that circuit to simple series resistance and reactant
2 wherein the resistance becomes the negative-sequence 1
sistance and the reactance the negative-sequence reactan,
(b) The ratio of the negative-sequence shaft power to the l(
in the negative-sequence resistance is then equal to t
ratio of the power loss in 5 for unit negative-sequer
2
current in the stator to r2. This ratio can be obtained eas
by test by measuring the shaft torque and the negati7
Fig. 32-Development of negative-sequence resistance and sequence input when negative-sequence voltages only4
reactance from equivalent circuit of induction motor. applied to the stator.
(a) Negative-sequence diagram for induction motor; Cb) neg- While this analysis has premised induction-motor CC
lecting armature and no load losses; (c) simplified network- struction, the conclusions can also be applied to synch
negative-sequence resistance and reactance.
nous machines.
Method of Test-While r:! and x2 can be determined
since s is constant and equal to 2 for the negative-sequence, applying negative-sequence voltage from another sou
is to reduce the equivalent network to a simple series im- of supply to the armature, the following method has 1
pedance as shown in Fig. 32 (c). The components of this advantage that the machine supplies its own negati
impedance will be called the negative-sequence resistance sequence voltage. Two terminals of the machine uric
r2, and the negative-sequence reactance x2. The current test are short-circuited and the machine driven at ral
flowing through the negative-sequence impedance is the frequency by means of a direct-current motor. The equ
current flowing through the stator of the machine, and the alent circuit and vector diagram for this connection ;
power loss in r2 is equal to the loss supplied from the stator shown in Fig. 33. The positive-sequence power per@
of the machine and the equal loss supplied through the at the terminals is equal to the product of El and 11 a
shaft. the cosine of the angle 4. This power is positive. Howev
The total electrical effect of the negative-sequence re- the negative-sepence power output per phase is equal
sistance in system analysis problems is obtained by in- the product of E2, 12, and the cosine of the angle betwc
serting the negative-sequence resistance in the negntive- Et and IZ, and since I, = -IL, and El = ES, the negati
sequence network and solving the network in the usual
manner. All three of the sequence currents are thus af-
fected to some extent by a change in the negative-sequence
resistance. The total electrical output of a generator, not
including the shaft torque developed by negative-sequence
current, is equal to the total terminal power output plus
the losses in the machine. However, the negative- and
zero-sequence power outputs are merely the negative of
their losses. In other words, their losses are supplied by
power flowing into the machine from the system. There-
fore, the contribution of the negative- and zero-sequences
to the electrical output is zero. The total electrical output
F
reduces then to that of the positive-sequence and to include
the positive-sequence armature-resistance loss it is neces-
sary only to use the positive-sequence internal voltage in
the calculations. Or viewed differently, since there are
no internal generated voltages of the negative- or zero-
sequence, the corresponding internal power must be zero.
In addition to this electrical output, which produces a in which
torque tending to decelerate the rotor, there also exists the P.=shaft input.
negative-sequence shaft power supplied through the rotor. P,+, = friction and windage loss.
It was shown that this power tending to decelerate the Fig. 33-Negative-sequence resistance of a synchron
rotor is numerically equal to the negative-sequence power machine.
chapter6 Madhe Charucteristics 163

seqllence w-r output is the negative of the positive- end-connection fluxes. The departure from this ideal con-
seq,~encepower output, Tvhich, of course, must follolv since diGon introduced by chording and the breadth of the phase
(he output of the mnchine is zero. A negative output is belt determines the zero-sequence reactance.
,,,L,iva’ent to a posltlve input. This input is equal to r?li The zero-sequence resistance is equal to, or somen-hat
per @se. 7 heref_2re, the positive-sequence terminal out- larger than, the positive-sequence resistance. In general,
pr,t per phase is ~12, and adding to this the copper loss due however, it is neglected in most calculations.
to I,, gives the-,totalshnft power due to the positive- Method of Test-The most convenient method for
L;ccl~l(~nceX3 3(rJ:+TJi). test of zero-sequence impedance is to connect the three
sow from Fig. 32(a), if z, be neglected, the negative- phases together, as shown in Fig. 34, with the field short-
yc,,I,~~~~e input per phase is equal to

from which it follows that

rz=~+rB. (34)
2
‘1s shown previously the negative-sequence shaft po\\*r
,,fSrphase is equal to ;I;, which on substituting ; from
Rotor at synchronousspeed
(3.1) rctlucC3 t0 But since r, = rl, the espression
CT2- T,)Ti. (or blocked)
fl)r the negative-sequence shaft power per phase can also Zero-sequence impedance,
‘,I: written (Tz-~$$ Incidentally, from this the rotor E
‘I)SSOS are equal to 2(r~---JIi. Therefore the total shaft ZO'TJ
irl’)\lt, into the alternating-current_ machine is equal J,o Fig. 34-Connection for measuring zero-sequence imped-
J[r2~~+rl~f+ (~-r$i] and, since I1=IZ, reduces to 6d:. ance.
Including the effect of friction and windage, PCF+Wj,and
c~tlling P, the total input into the alternating-current circuited. This connection insures equal distribution of
nurclline from the driving tool, current between the three phases. For this reason it is
preferable to connecting the three phases in parallel. The
T =p,-p(F+W) E
2 61;
(35) zero-sequence impedance is then equal to ZO=- as in-
31
and, since I,=--= where 1 is the actual measured phase dicated in the illustration.
:3
current, IV. PER UNIT SYSTEM
T2=[p.-p(F+W)‘I (36) The performance of a whole line of apparatus, regardless
212 of size, can often be expressed by a single set of constants
The foregoing neglects the effects of saturation. Tests on when those constants are expressed in percentages. By
nltlicnt pole machines with and without dampers verify this is meant that the loss will be a certain percentage of
Ihc fact that the loss varies as the square of the negative- its kilowatt rating, its regulation a certain percentage of
xoc’rlt;ncecurrents. The loss for turbine generators, on the its voltage rating, etc. The advantage of this method of
ol.hcr hand, varies as the 1.8 power of current. representation extends to a better comparison of perform-
ance of machines of different rating. A 100-volt drop in a
16. Zero-Sequence Impedance transmission line has no significance until the voltage base
‘1’1~ zero-sequence impedance is the impedance offered is given, whereas, as a percentage drop would have much
10 fhc flow of unit zero-sequence current, i.e., the voltage significance.
t1l.o’)across any one phase (star-connected) for unit current A disadvantage of the percentage system is the confusion
it1 ~ch of the phases. The machine must, of course, be that results from the multiplication of percentage quanti-
disconnected for otherwise no zero-sequence current can ties. Thus, a 20-percent current flowing through a 40-
flow. percent reactance would by simple multiplication give 800
‘l’he zero-sequence reactance of synchronous machines is which at times is erroneously considered as SOO-percent
Wit,c variable and depends largely upon pitch and breadth voltage drop, whereas, the correct answer is an g-percent
fllctors. In general, however, the figures are much smaller voltage drop.
than those of positive and negative sequences. The nature The per unit system4 of designation is advanced as pos-
of the reactance is suggested by considering that, if the sessing all the advantages of the percentage system but
urmature windings were infinitely distributed so that each avoids this last mentioned disadvantage. In this system
pliase produced a sinusoidal distribution of the mmf then the rating quantity is regarded as unity. Any other amount
t’~e mmfs produced by the equal instantaneous c&rents of the-quantity is expressed as a fraction of the rated
Of the three phases cancel each other and produce zero amount. It is the same as the percentage system except
‘e’d and consequently zero reactance except for slot and that unity is used as a base instead of 100. The foregoing
164 Machine Characteristics

multiplication example would in the per unit system be ‘V’


E
expressed as follows: A 0.20 per unit current flowing r- et++&
through a 0.40 per unit reactance produces an 0.08 per
unit voltage drop, which is correct. But & = ed- xdid -jxqiq
A further advantage of the percentage and per unit and k=E cos 6-jE sin 6
systems lies in the elimination of troublesome coefficients.
However, this is not an unmixed blessing as a definite Upon substituting & and E in equation (37), there resul
disadvantage of the use of the per unit system lies in the
-j [ed - Xdid -jXqiq]
loss of the dimensional check.

V. POWER EXPRESSIONS +ji[E cos O-jE sin O]

It is frequently necessary to know the manner in which Equating reals


the power output of a machine varies with its excitation
and internal angle. A particular application of this knowl- i,= - xq(x.+2c) E sin 8
i,+-
edge is the stability problem. Several simple cases will X&c X0
be considered. x.E sin 0
=
17. Machine Connected through Reactance to In- x,xc+xqx.+xqx,
finite Bus and also Shunt Reactance across its And equating imaginaries
Terminals, Resistance of Machine Neglected
The schematic diagram for this case is shown in Fig. id= x.+x0
-[ed-xdid] --kcE COS o
35(a), which also shows the significance of the various x.xc
symbols to be used in this discussion. The reactances x,, = (x.+xJed-x.E cos 8
x0 and the one indicated by the dotted lines represent the X.Xc+ldX.+XdX,
branches of an equivalent g circuit, for which the resistance
components are neglected. For the purposes of determin- The power output, P, is equal to the sum of the products 01
ing the power output of the generator the reactance shown the in-phase components of armature current and termin&
dotted can be neglected. The vector diagram which ap- voltage, namely
plies is Fig. 35(b). The total machine current is equal to i, P=iq(ed-Xdid)+id(Xqiq)
=ediq+ (Xq-Xd)idiq
= [edi- (Xq-Xd)id]iq
ed
The power is then obtained by calculating i, and id fro
(39) and (40) and inserting into (41). If E and ed are e
pressed in terms of rms volts to neutral and reactant
ohms per phase, then the above expression gives the p
in watts per phase; but if the emf’s are expressed in t
of the phase-to-phase volts the expression gives total p
On the other hand, if all quantities are expressed in
then the power is also expressed in p.u. where
I_!t ’ f x.diA equal to the kva rating of the machine. If ed’ rat
ed is known then ed should be replaced by ed’ and
wherever they appear in Eqs. (40) and (41).
For the special case of a machine with cylindrical
in which x, = xd, the expression reduces immediately
I (b) P=edio
Id i,Eed sin e
=
~.x.2+xqx. + xqx.3
Fig. 35-Machine connected to infinite bus through a re-
actance. Another interesting special case is that for which t
shunt reactance is not present or x.= co. Then
which from the internal and external currents one can
obtain*
zq-jid=$8+2L .
5
edE Sin 6+
ed-E
x +xd
0
(Xd -Xq)E2
COS e E

Sin 28
1xcfxq
-
sin 6

And inserting the equivalents of b. and ii Xo+Xd %Xd+X.) (X,+X,)

Andifx,=Oandx.=a, then
f?dE Sin e+ (Xd- Xq)E2 Sin 28
P=
*The symbol caret over a quantity indicates a phzisor quantity. Xd 2XdXq
chapter 6 Machine Characteristics 165

ed
bdid

id
“, I.

Eo

0. k$,
0
0
III 0 (II) II (1 IIIllY
rid
OO 20 40 60 60 100 120 140 160 180
e IN DEGREES Fig. 37-Vector diagram of salient-pole machine including
~18. 36-Power-angle diagram of a salient-pole machine- effect of series resistance.
excitation determined to develop rated kva at W-percent
power factor. xd=1.15; x,=0.75. / et cos e+riq+xdid-ed=O (46)
In Fig. 36 is shown a power-angle diagram of a salient- From (45)
ljol(: machine whose excitation is determined by loading at iq=bq(et sin efrid) (47)
full kva at 80-percent power factor.
:\n expression frequently used to determine the maxi- Substituting (47) into (46)
mum pull-out of turbine generators is the following
7-2
et COS e+& sin e+--id+%&-ed=O
Pull-out in kw =g(rsting of generator in kva) 5, 2,

from which

1 (4%
wllcre OC is the field current for the particular operating
contlition and OD is the field current for the rated-current
zc’ro-power factor curve for zero terminal voltage (see Fig.
17). ‘This expression is based upon the maintenance of
id=-
r2+xdx, 1
x’qed-ret sin e-xqet cos e

mtotl terminal voltage up to the point of pull-out. At and substituting in (47)


pull-out the angle 6 of Fig. 15 is equal to 90 degrees. Since
the extent of saturation is measured by the voltage behind
the Potier reactance drop, it can be seen from Fig. 15 that
i q =----
1
++xd&
red+x& sin e-ret
1 (49)
cos 0

for 6 equal to 90 degrees this voltage is less than rated The power output, P, is equal to the sum of the products
voltage, and that therefore little saturation is present. of the in-phase components of i and et, or
From Eq. (44) since zd =x, and 0 = 90 degrees, the pull-out P=iqet cos 8+i& sin 8 (50)
is @. But edis proportional to OC on the air-gap line and Upon substituting (48) and (49) this reduces to
%d
Z,I is likewise proportional to OD on the air-gap line.
Examination of Eq. (44) shows that even if the excita-
tion is zero (ed=O) the power-angle curve is not equal to
p=et
++xd& c
ed(r ~0s e+x,sin 0) +‘ye, sin 2f3--et
1I-.\
zero, but equal to (zd-$LT sin ze. This results from the The power input into the machine is equal to P plus ri2.
d” The expression for this quantity does not simplify and it
(!llccts of saliency. Note that it disappears for uniform is better to calculate it through the intermediate step of
rrir-gap machines for which zd=xQ. Advantage is some-
evaluating ri2, which is equal to r(ii+ii).
l.imcs taken of this relation in the case of synchronous The foregoing expressions apply to the steady-state con-
condensers to obtain a somewhat greater capability in the
ditions. In stability problems it is necessary to determine
k:ltling (under-excited) kva range. With some excitation the average power from instant to instant. In general for
systems (see Chap. 7, Excitation Systems) it is possible to this purpose it is permissible to neglect both the unidirec-
obt.uin negative excitation. The excitation Voltage, edt in tional component of currents and the subtransient com-
Eq. (4-l) can be-somewhat negative without producing an ponent of the alternating current, leaving only the transient
unstable power-angle diagram. By this device the leading component. These latter are determined by the instanta-
kva range can be increased as much as 15 or 20 percent. neous value of ed’. It follows then that the power expres-
18. Inclusion of Machine Resistance or External sions are simply those derived for the steady-state condition
Resistance with ed replaced by ed’ and xd by zd’.
If the machine is connected to an infinite bus through a
resistance and reactance circuit, the external resistance VI. EFFECT OF CHANGE IN EXCITATION
and reactance can be lumped with the internal resistance Field forcing in certain industrial applications and con-
and reactance and the following analysis used. The vector siderations of system stability require that the voltage
diagram for this case is shown in Fig. 37 for which increase in response to a sudden need. This increase is
et sin e+rid-x&=0 (45) brought about automatically either by means of the same
166 Machine Characterislics Chapter 6

control that produced the increase in load or through the the field circuit. The beauty of the per unit system is
use of a voltage regulat,or. It is necessary, therefore, to be exemplified in the analysis of this problem. In p.u. the
able to predetermine the effect of an increase in esciter differential equation for the field circuit takes the following
voltage upon the output of the synchronous machine. In form
general, significant changes in exciter voltage never require dr,,’
less than about one-tenth of a second to bring about the ex= ed+ T&,--- (52)
dt
change. By the time this effect has been felt through the
synchronous machine, which has a time constant of ahout In this equation e, represents the esciter voltage or the
a second, it will be found that the result is always slow voltage across the field if there is no external field resistor
when compared to the subtransient and unidirectional in the field circuit. The unit of e, is that voltage required
components of the transients associated with the change. to circulate such field current as to produce rated voltage
In other words, variations in exciter voltage are reflected at no load on the air-gap line of the machine. The term edi
only in the transient components. As an example, suppose is the synchronous internal voltage necessary to produce
it is desired to calculate the armature current of a machine the instantaneous value of armature current for the given’
for a three-phase short-circuit while it is operating at no armature circuit regardless of what it may be. Its unit is
load with a voltage regulator set for rated voltage. rated voltage. It is synonymous with field current whefi
Immediately after the inception of the short circuit there unit field current is that field current necessary to produce,
is a slight lag in the regulator until its contacts and relays rated voltage at no load on the air-gap line. It will be seen
close. The exciter voltage (and voltage across the field of then that the use of ed is merely a convenient way of
the main machine) then rises as shown in the upper curve specifying the instantaneous field current during the tran-,
of Fig. 38. The bottom curve refers to the armature cur- sient conditions; it is the field current, necessary to produce
the armature current existent at that instant. As shown
previously, ed’, is proportional to the flux linkages with the
field winding. It is the quantity that, during the transition !
period from one circuit condition to another, remains con-
stant. The foregoing equation has its counterpart in the
more familiar forms
LAG IN REGULATOR
+- (53)

or
(54) i

To familiarize the reader with (52)) suppose that normal .{


exciter voltage is suddenly applied to the field winding at 4
no load. Since the armature is open-circuited ed’ and ed ;
are equal and the equation can be written 4;
(55) 4
TIME
Fig. 38--Illustration showing relative importance of different 4
components of armature short-circuit current and response When steady-state conditions are finally attained 2 is 1
of transient component to the exciter voltage. ,
equal to zero and ed=ex. This states that since eX= 1.0, 1
rent, the dotted line showing the nature of transient com- ed must also equal 1.0, that is, the excitation is equal to-j
ponent if there were no regulator, the exciter voltage the normal no-load voltage. It will attain this value ex- i
remaining constant. The line immediately above shows ponentially with a time constant T&.
how the transient component changes as a result of the Another esample. Suppose the synchronous machine i
change in exciter voltage. To approximately the same to be short-circuited from no-load and to be operating a
scale, the cross-hatched area shows the increment in cur- without a regulator. At any instant the armature cur- 3
rent caused by subtransient effects. The blackened area rent, i, is equal to ed’/zd’. But since ed, which can be
shows how the unidirectional component would contribute regarded as the instantaneous field current required to
its effect. This component is quite variable and for a produce i, is equal to xd i, then eliminating i between
short-circuit on the line might be entirely completed in a these equations
cycle or less. In any event regardless of its magnitude it
xd
can be merely added to the transient and subtransient ed = 7ed’ (56)
component. It is independent of the exciter voltage. xd

19. Fundamental Equation Then equation (52) takes the form


Being restricted to the transient component, the effect of 1 =;$e,‘+T&,~
exciter response can then be defined entirely by effects in
chapter 6 Machine Characteristics 167

or if it is to be expressed in terms of armature current name, has been called by the author “the follow-up meth-
od.” It is a method that can be applied to any problem
l=xdi+T’ x 4e (57) involving a simple time constant.
do ddt’ To demonstrate the method, consider a simple resist-
The sustained magnitude of i, is then ance-inductance circuit to which the voltage, E, is applied.
Let the differential equation for this circuit be
i=- 1
xd E=RI+L$ 6%
Tlrc initial magnitude of i, since ed’ remains constant
during the transition and is initially equal to 1, is where the symbols have the customary significance.
Dividing through by R, there results
i=- 1
xd’
(W
T]rc homogeneous equation for (57) is
0=x
The coefficient of $$ is called the time constant of the
d i+T’ x @
do d dt
circuit and will be designated by T, giving
E
(58) %=I+T$f
E T
‘~11~si changes from 3 to i exponentially with a time dI (61)
-=- z-l
dt T
constant equal to :dTio.
In this expression E is the steady-state current that I
In all problems involving a transition from one circuit
c:onclition to another the one quantity (when subtransient approaches for the instantaneous value of E. I is the
c+fcc:t,sare neglected and the time constant in the quadra- instantaneous magnitude of current. If the current at
I,IIWaxis is zero) that remains constant within the machine any instant is plotted by the point a (Fig. 40) and the
is the flux linkages with the field winding, which in turn E
corresponding value of E for that instant is plotted as
is reflected in the quantity ed’. It is necessary, therefore,
to calculate ed’ for the circuit condition preceding the the point b (Fig. 40) displaced horizontally by a time T,
transition. All the discussion of the following cases as-
snmes that this point is understood and that ed’ is known
for the beginning of the transient period.
Several cases will now be discussed.
20. Three-phase Short Circuit of Unsaturated Ma-
chine
The problem is to determine the transient component
of short-circuit current in response to the exciter voltage
gifen in Fig. 39. This is most quickly and conveniently
found by a graphical method, which, for want of a better
Fig. IO-Construction derivation of “Follow-up Method.”

then the vertical distance between a and b gives the nu-


merator of (61) and the horizontal distance the denomina-
tor. The slope of the line between a and b is equal to ‘i.
If an interval of time At is chosen following the instant
under consideration and E is assumed constant over the
interval then the change in I during the interval, AI, is
dI
equal to -At. The final value of current for the interval
dt
E
is then given by the point c. If - at an instant Al later is
R
then plotted and the line drawn from c then the value for
AI for the second interval is obtained. Following such
procedure it is possible to construct the complete curve
Fig. 39-Illustration of “Follow-up Method.” for I. The construction is illustrated in Fig. 39, in which
168 Machine Characteristics Chapter 6

the curve marked lZ is the instantaneous magnitude of E


i=1 Starting from this value the actual magnitude of
xd”
from time t=O. Plot g displaced to the right a time T.
i is obtained as a function of time.
Let li be the initial value of I at t = 0. Divide the time into
intervals of length At. Draw the line ab, then cd, ef, etc. 21. Unsaturated Machine Connected to Infinite Bus
The accuracy will be greater the smaller the intervals and As stated previously the subtransient and unidirectional
can be increased somewhat for a given element width by components of current are not of importance in the sta-
bility problem. For this application it is desirable to de-
using I--: instead of T for the distance by which the termine how cd’ varies as this influences the power output
steady-state curve which I tends to approach, is offset of the machine and in turn dictates the degree of accelera-
horizontally. tion or deceleration of the rotor. The circuit shown in
Xow returning to the problem in hand. The differential Fig. 35(a) is typical of a setup that might be used for an
equat,ion governing the case is given by (52). The esciter analytical study to determine the effect of exciter response
voltage e, is assumed given and expressed in p.u. For a in increasing stability limits. Another case of considerable
three-phase short circuit at the terminals of the machine importance is the action of a generator when a heavy load,*
ed is equal to zdi and ed’ =zd’i. Therefore Eq. 52 becomes such as a large induction motor, is connected suddenly
across its terminals or across the line to which is is con-
e,=sd+dT;o$ (62) nected. In starting the motor the line voltage may drop
an excessive amount. The problem might be to determine
Dividing through by zd the amount to which this condition could be ameliorate‘d
, by an appropriate excitation system. Since reactive kva
2 =;+‘L di
TAO, is more important than the real pcmer in determining
(63)
Xd xd regulat’ion, the motor can be represented as a reactor and
The construction dictated by this equation and the the circuit in Fig. 35(a) utilized. Having determined the
manner in which ed’ varies, the power in the case of the
follow-up method is shown in Fig. 41. 2 is plotted against stability problem and t,he terminal voltage (ed’-rd’i) in
xd
the case of the voltage problem, can be calculated easily.
Equation (52) must be used again to determine the manner
in which ed’ varies in response to changes in exciter voltage
and phase position of the rotor with respect to the infinite
bus. The instantaneous armature current can be found in
terms of the rotor angle 19and ed’ by replacing ed and zd of
Eq. (40) by ed’ and xd’, respectively, giving
id= (XsfXc)ed’-XsE COS 0
(64)
X.&+zd’x,+Xd’Xc

The synchronous internal voltage, cd, is equal at any


instant to
ed=ed’+(Xd-Xd’)id (65)
and upon substituting (64)

= (XsXc+XdXs+XdXo)ed’-XJ;S(Xd-Xd’)E COS 8

XsXc+Xd’Xa+Xd’Xc

Substituting this expression in (52), there results.


X,Xc+XdXs+XdX,
e,= ed’-
&X,+Xd’X.s+Xd’Xc

X,(Xd-Xd’)
E cos 13+T;ods (66)
&X,+Xd’X.+Xd’Xo

which can be converted to


x, (Xd - Xd’)
Fig. 41-Transient component of short-circuit current, i’, as E cos d=edr+Tdrd$ (67)
XsXcfXdXafXdXc
influenced by excitation.
in which
x&+x,,‘&,+xd’&
time, its zero being displaced an interval ‘$Ti, from refer- Td’ = Tdo’ (68) i
XsXofXdXsfXdXc

ence zero. The initial value of i is determined through ed’ The time constant Td’ is the short-circuit transient time
which was 1.0 at t =O. This makes the initial amount of constant.
Chapter 6 Machine Characteristics 169

If 0 were constant or if its motion as a function of time From this point the follow-up method can be used as
,vere known then the whole left-hand side could be plotted before. After ed’ is determined as a function of time any
(displaced by the time Td’) and treated by the follow-up ot,her quantity such as terminal voltage can be obtained
method a~ the quantity that ed’ tends to approach. Un- readily,
fortunately 0 is not in general known beforehand, and it is
ncccssary t0 calculate 0 simultaneously in small increments 23. Saturation
in a simultaneous solution of cd’ and 0. The magnitude of In analyzing transient phenomenon of machines in the
0 is determined by the electro-mechanical considerations unsaturated condition, the theory was built around the
discussed in the chapter dealing with System Stability. In concept of the transient internal voltage, ed’, a quantity
solving for ed’ a progressive plot of the left-hand side can evaluated by using the transient reactance, xd’. In the
he made or (67) can be transformed to the following form presence of saturation it was found that for steady-state
conditions by the introduction of the Potier reactance:
x, (see Sec. 3) the proper regulation was obtained at full
load zero’power-factor. The use of x, and e,, also resulted in
and the increment calculated from the equation satisfactory regulation for other power-factors. In extend-
ing the analysis into the realm of transient phenomenon.
ep will continue to be used as a base from which to intro-
duce additional mmf into the field circuit to take care of
;\ shunt resistance-reactance load such as an induction saturation effects. The treatment will follow quite closely
motor is not much more difficult to solve numerically but the same assumptions as were used in determining the
t,lr(:expressions become too inv&ed for analytical solution. steady-state regulation according to the Two-Reaction
lt is necessary only to calculate id in terms of ed’ and 8 just Potier Voltage method of Sec. 3(d).
:~swas done before and then follow the same steps as used With this assumption the fundamental Eq. (52) for the
for the reactance load. field circuit becomes
22. Unsaturated Machine Connected to Resistance- e,=ed+(s due to e,)+Td,,% (761
Reactance Load
.\ case not too laborious to carry through analytically As before ed represents, neglecting saturation, the voltage
is that for which a resistance-reactance load is suddenly behind the synchronous reactance of the machine or what
applied to a synchronous machine. Let reXtand xext be the is equivalent the field current required to produce the
cstcmal resistance and reactance. The addition of a sub- instantaneous ed’, including the demagnetizing effect of
script t to machine constants indicates the addition of T,,~ the instantaneous armature current. The total field cur-
or .crutto the respective quantity. The equations of Sec. 17 rent is obtained by adding s to ed. In some cases it is found
I hrn apply to this case, if et in the equations is made equal simpler to convert all of the right hand side to the single
to zero and Ed replaced by Zdt, etc. variable e,, but in others it is simpler to retain the variable
Following the same procedure as previously, there re- in the form of ed’. Two applications of this equation will
Slllls from Eq. (48) when ed and zd are replaced by ed’ be discussed.
:ultL z& and et is equal to zero. Machine Connected to Infinite Bus-The circuit
shown in Fig. 35(a) is the one under discussion and for
id= X,t
ed’ (71) which Eq. (66) applies for the unsaturated condition. This
r:+x-hqt
equation can be expanded to include saturation, in accord-
‘l’lrc field current or its equivalent, the synchronous in- ance with Eq. (76), to the following
tcrnnl voltage, is then %&+xdx.+xd& x&d---d’)
e,= ed’ - E cos 8
ed=ed’+bdt-xi&d &,~c+~d’~.+~d’& &&+~d’~,+~d’~o

xqt
=ed’+(xdt-x&j ed’ +(s due to eP)+Ttdd
r’t+&xqt do dt ’
This can be converted to
(72)
ded’ e,- (s due to e,) x&d-xd’) E COS 6
-d (78)
Substituting this expression in (52) there results that -iii-= T’do + (x.xc+ xd&+xdxc) Td’ Td
xdtxqt+< ded’ in which Td’ is defined from Eq. (68). Before (78) can be
ex= 2 ed’+ TL---
used it mill be necessary to determine ep in terms of ed’.
x;txqt+rt dt
The components of current, i, and ‘id, can be determined
jvhich can be converted to
from (39) and (40) by replacing ed, by ed’ and xd by zd’.
Td ,ded Thus
~‘k=ed’+Td-$ (74) xsE sin 0
in Which
do
i,=
x.xo+2&+2q2, (7%
xd’txqt+$ (X.+X&d’-GE COS e
Td=
id-

Td6. (75) W)
xdtxqtfr~ &&+xd’x,+xd’& ’
170 Machine Characteristics Chapter 6

The direct-axis component of eP is equal to assumption that is usually made in stability studies tha
e*d= Q’ - (Xd’ -x,)i,, where quick response excitation is installed, ed’ may b
regarded as constant.
Machine Connected to Resistance-Reactant
Load-This case is the same as that considered in Sec. 2
and the quadrature-axis component of e, is except that saturation effects are to be included. Upo
epq= bk-4G including the saturation term s into Eq. (74) there result
that
= x,(x,--z,)E sin 0
(82)
wLfZ,~,f5,Z,
The amplitude of e,, is then equal to
e,=dK in which
(83)
While this quantity does not simplify greatly, it does not (8t
appear so formidable after numerical values are inserted.
e,, can thus be calculated for any instantaneous value of It is well to recall again that this analysis neglects sut
e,,’ and the s corresponding thereto substituted in Eq. (78). transient effects and assumes that the time constant in t1
Equation (78) provides a means for computing increments quadrature axis is zero. If in Eqs. (48) and (49) et is mad
of change in ed’ for use in step-by-step solution. Thus equal to zero, ed is replaced by ed’ and the correspondin
changes in reactance associated with ed’ are made, and i
addition the subscripts are changed to indicate total r~
actances, Then
As s becomes small and saturation effects disappear, the
solution relapses into the same type as used when satura-
tion is negligible (Eq. 66), for which the follow-up method
is frequently applicable.
The relations just developed are useful in estimating the
extent to which ed’ varies in system stability problems. The total current is then
Fig. 42 shows the results of calculations on a system in
which a generator is connected to a large network, repre- (B!
sented as an infinite bus, through a reactance equal to j0.6.
The voltage eP is
/
xiao.45 ep= id-
Xp~0.40 5 E-0.91
Xq’0.65 / >!
/ % a
xd= 1.1, T&,=6, ,+=3.0
/ 6
Uljon substituting ed’ from (90) into (85) and using (81
also there results that
-d(s;t+r,‘hl:+r:+S due to e )
x P
Zdt&,t+T:

1.0 0
I.16
1.0 0.05
-0
a As can be seen from Fig. 43 the solution of this equatic
I.14 0.5 0.05 lends itself well to the follow-up method. On the righ
hand side the assumed exciter response curve, e,, is plottl
as a function of time. Multiplying this quantity by tl
0
coefficient of e,, the term epmis obtained. This is the vail
I.121 ’ ’ ’ ’ ’ ’ ’ ’ ’ J
0 0.1 0.2 0.3 0.4 0.5 eP tends to attain if there were no saturation effects. 1
TIME IN SECONDS in the follow-up method, the zero of time from which tl
Fig. 42-Effect of rate of response upon ed’ as a line-to-line instantaneous curve of e, is drawn, is displaced to the 1~
fault represented by the three-phase shunt load j0.2 is applied an amount Td’ minus half the interval of time chosen
to generator which had been operating at 90 percent power- the step-by-step solution. Along the ordinate of ePa cur
factor. 20 percent of air-gap mmf required for iron at rated s1equal to the second term is plotted in which s is obtainl
voltage. from the no-load saturation curve shown in (b). For al
instantaneous value of ep, s1 is plotted downward from e
A line-to-line fault is assumed applied to the connecting as the construction progresses. So starting from the initj
transmission line on the high tension bus at the generating value of e,, of which more will be said later, a constructit
end which is equivalent to a three-phase short circuit line is drawn to a point for which s1 was the value cork
through a reactance of j0.2 ohms. The curves justify the sponding to the initial value of eP. For the second inter\
Chapter 6 Machine Characteristics

xq i cos 0
tonb=
et+xqi sin 4

LMACHINE OVERALL
CONSTANTS CONSTANTS

XP xPl=xP+xexl
*it= XL +xext
Xb 1.0 (c)-VECTOR DIAGRAM
Xd xdt’ Xd+Xext FIELD CURRENT OR FOR MACHINE ALONE
xq *qt= *q+xert EXCITER VOLTS
r rt. r +reXt
(b)-SATURATION CURVE
(a)-DEFINITIONS OF MACHINE

INITIAL VALUE OF ep
/

s z s WHEN rt =o

CALCULATE $j FROM (Cl FOR INITIAL LOAD


eb REMAINS CONSTANT DURING TRANSITION
FROM ONE OPERATING CONDITION TO THE
NEXT
5, FOR INTERVAL”2

INITIAL VALUE OF eP= 5, FOR INTERVAL” 1


-l,At !-- ! ’ AAt’- !
= $T&-u WHEN r,=o
= I I I 2
0 TIME 0 TIME -

Fig. 43-Graphical determination of terminal voltage as polyphase series resistances, rext and reactances xext are suddenly
applied.

SIis taken for the value of F, at the end of the first interval sudden disconnection of a loaded generator from the bus
or, to be slightly more accurate for an estimated average throwing its load upon the remaining units or the starting
v:~lueof ePfor the second interval. And so the construction of an induction motor by direct connection to a generator.
proceeds. For the latter case, if the capacity of the induction motor
1%~the same reasoning whereby ePwas obtained in Eq. is a significant fraction of the kva of the generator, a severe
(W)the terminal voltage et can likewise be obtained, giving drop in voltage results. Thus a 500-hp motor thrown on
et=idx2cxt+~2ext a 3300-kva generator produces an instantaneous drop in
voltage of the order of 13 percent. The effective impedance
of the induction motor varies with slip and to be rigorous
this variation should be taken into consideration. It is
W(l substituting ed’ from (90) usually sufficiently accurate to use the blocked rotor re-
actance for the motor impedance up to the speed corres-
et= X2& +r*,*t
4 x&+ri
ep (92) ponding to maximum torque in calculating the factor which
determines ePa,in terms of e,. Beyond the slip correspond-
‘lhis permits of the calculation of et from eP after the ing to maximum torque, the effective impedance varies
ecristruction has been completed. rapidly to the running impedance. Simultaneously with
1)uring the transition from one operating condition to the increase in impedance the lagging kva likewise drops
th nest, only ed’ remains constant; eP changes. It is es- off which results in a considerable rise in voltage. This
“crrli:~l therefore that ed’ be computed for the initial operat- effect is clearly shown in Fig. 44 taken from some tests
ing condition. The conventional construction shown in made by Anderson and Monteith.*O As running speed is
l’i!& 43(c) can be used. This determines the initial value approached the generator voltage rises, the excitation be-
cf cd’for the nelv operating condition from which the initial ing too high for the particular loading. To form a better
“rrlrie of ePcan be computed by Eq. (90). idea of the magnitudes involved in such calculations, Fig.
Common cases for which these calculations apply are the 45 shows curves of terminal voltage as an induction motor
determination of regulation for loads suddenly applied to equal in horse power to 20 percent of the kva of a generator
a generator. Instances in which this can occur are the is suddenly thrown upon an unloaded generator for differ-
172 Machine Characteristics Chapter t

3500 1200 240 : problem generally and have plotted the results in curvl
uz form.
3 100 1000 200 Fzj The analysis has been carried out for both self-escitec
i and separately-excited exciters. The results for the forme
2700 600 I60
I- %
are plotted in Fig. 46, and for the latter in Fig. 47. Thes,
:
2 2300
z
= 600
2 curves are plotted in terms of the four parameters: (I
I20 2
5 ? magnitude of load change (2) XA,,, (3) Td,, and (4) rat,
P
1900 O400 80 F of exciter response, R. The response is defined in th,
P
chapter on Excitation Systems. It is shown by Hnrde
1500 200 40 (I and Cheekz2 that variations in xq, saturation factor of th,
E generator and power factor between zero and 60 percen
1100 0 03
E have little effect upon the maximum drop. The assumef
value of zd for these calculations was 120 percent. AI
Fig. 44-Performance of 3333 kva, 0.6 power-factor, 3600 rpm, accurate figure for maximum voltage drop can be obtainec
1.7 short-circuit ratio generator as a single 500-hp induction- for values of %dother than I20 percent by first expressin
motor pump is started. Induction-motor starting torque reactances and the applied load on a new kva base, sucl
equal to full-load torque and pull-out torque equal to 2.8
full-load torque. Full lines represent operation with fixed that xd on the new base is 120 percent, and then applyin
excitation and dotted lines under regulator control. the curves. For example, suppose a load of 1500 kva (ex
pressed at full voltage) of low power factor is to be applie,
to a 3000-kva generator having 30-percent transient re
actance and 150-percent synchronous reactance. Suppos
that the generator time constant is 4.0 seconds and th
exciter has a nominal response of 1.0. To determine th
drop, express the transient reactance and the applied loal
on the kilovolt-ampere base upon which xd is 120 percent
The base in this case will be 3000~ 120/150 =2400 kva
On this base the transient reactance 54’ is 30 X 2400/3000 =
24 percent, and the applied load is 1500/2400=62.5 per
cent. If the exciter is self-excited then from the curves a
Fig. 46, the maximum voltage drop is 15 percent for 62.5
percent load applied to a generator having 24-percent tran
sient reactance, a time constant of 4.0 seconds, and al
exciter of 1.0 nominal response. This same maximum drol
70 would be obtained with the machine and load unde
0 0.2 0.4 0.6 0.6 1.0
consideration.
TIME-SECONDS
The initial load on a generator influences the voltag
Fig. 45-Terminal voltage of a 500 kva, SO-percent power- drop when additional load is suddenly applied. As show]
factor engine-type generator Cxd= 1.16, xq =0.59, xd’ = 0.30, in Fig. 48, a static or constant-impedance initial load re
13 percent saturation) as a lOO-hp induction motor is con- duces the voltage drop caused by suddenly applied loac
nected. However, a load that draws additional current as voltaf
decreases may increase the voltage drop. Such loads ti
ent rates of response of the exciter. Ordinarily one is be referred to as “dynamic” loads. For example, a runnir
primarily interested in the minimum voltage attained dur- induction motor may drop slightly in speed during tl
ing the accelerating period and so the calculations have voltage dip so that it actually draws an increased currer
been carried out to only 1.0 second. The curves show con- and thereby increases the maximum voltage drop. Tl
ditions for constant excitation and for exciters with 0.5 and dynamic initial load curve of Fig. 48 is based on an initi;
1.0 ratios, respectively. load that draws constant kilowatts and power factor as tf
voltage varies.
24. Drop in Terminal Voltage with Suddenly-
Applied Loads
VII. CONSTANTS FOR USE IN STABILITY
When a relatively large motor is connected to a gener-
PROBLEMS
ator, the terminal voltage may decrease to such an extent
as to cause undervoltage release devices to operate or to The stability problem involves the study of the electrc
stall the motor. This situation arises particularly in con- mechanical oscillations inherent in power systems. 2
nection with the starting of large motors on power-house fundamental factor in this problem is the manner in whit
auxiliary generators. The best single criterion to describe the power output of the generator varies as the position (
this effect when the generator is equipped with a regulator its rotor changes with respect to some reference voltage
to control the excitation is the maximum drop. The pre- The natural period of power systems is about one seconc
vious section describes a method whereby this quantity Because of the series resistance external to the machine
can be calculated. However, the problem arises so fre- the time constant of the unidirectional component of am:
quently that Harder and CheekzzJ3 have analyzed the ature current is usually so small as to be negligible i
Chapter 6 Machine Characteristics

I ! ! ! ! ! !tfv-v!--r

Fig. 46-Maximum voltage drop of a synchronous machine WITH SELF-EXCITED EXCITER as affected by (a) magni-
tude of load change, (b) x’,, Bst, (c) T’do and (d) rate of exciter response. xd’ on curves refer to saturated or rated-voltage
value. Assumptions used in calculations: xd’= 1.07 x d’ aat; xd=I.20; x,=0.75; no-load saturation curve/air gap line normal
voltage = 1.2; time lag of regulator =0.05 second; added load is constant impedance of 0.35 pf.; initial load zero.
Chapter 6

Fig. 47-Maximum voltage drop of a synchronous machine WITH SEPARATELY-EXCITED EXCITER as affected by
(a) magnitude of load change, (b) x’d .,,,t. (c) Tdo’ and (d) rate of exciter response.
Chapter 6 Machine Characteristics 175

Further consideration of this constant is given in Part


XIII of this chapter.
26. Network Calculator Studies
For most problems the synchronous machine can bc
represented by its transient reactance and a voltage equal
to that behind transient reactance. For the rare case for
which salient-pole theory is required, the follo\ving pro-
cedure can be followed. It is impossible to set up the tn-o
renctances in the two axes by a single reactor, but if the
reactance, xQ, is used and a new voltage, cQ&introduced as
representing the internal voltage, both position of the rotor
and the variations in ed’ can be carried through quite
simply.
Fig. 49 shows a vector diagram similar to Fig. l-1 in
INITIAL LOAD-PER CENT u? which epdis included. This voltage is laid off along cd and
ed’ and terminates at the point a. The reading of power
Fig. 48--Effect of type (whether dynamic or static) and initial at eq,-Jis the same as the actual output of the machine. -1s
load, assumed at 0.80 power factor, upon the maximum volt- the exciter voltage changes ed’ and esd likewise change.
age drop when loo-percent low-power-factor load is suddenly
applied to an a-c generator.

comparison with this natural period. The subtransient


component is likewise so small that its effects can be
ncglccted. There remains then only the transient com-
l)oncnts, those components associated with the time con-
stants of the field winding, that are important.
25. Representation of Machine
The transient stability problem is primarily concerned
with the power-angle relations during system swings fol-
loiving a disturbance. Because of the dissymmetry of the
two axes, it is necessary theoretically to take this dissym-
metry into consideration. However, in most cases an
impedance is in series externally to the machine so that Fig. 49-construction of eQdfor network calculator studies.
the difference in reactances in the two axes becomes a
smaller proportion of the total reactance. The results of
c::rlculations presented in Chap. 13 show that for most The incremental changes in epdcan be obtained as follon-s.
practical purposes it is sufficiently accurate to represent From Fig. 49 it is evident that at any instant
the unsymmetrical machine with a symmetrical machine eqd= ed’+ (x9-xd’)id (94)
having the same xd’. -
From Eq. (52)
In spite of the close agreement of salient-pole with
cylindrical-rotor results, a few cases arise for which it is ded’ 1
-$-=z,(&-ed)
rrccessary to use salient-pole theory. Relations for calcu-
l:r( ing the power output have been given in Sets. 10 and 17 and
:md for computing the change in internal voltages in Sec.
22(:1). It is shown in the latter section that if the exciter
is of the quick-response type, the voltage ed’ can, for all
lmrctical purposes, be regarded as constant. Methods for where Aed’ is the increment of ed’ in the increment of time
lhc inclusion of these factors into the stability calculations At. From Fig. 49 there results also that
have also been treated in Chap. 13. ed=epd+ (xd-x&d (96)
11knowledge of the inertia constant, H, is a requisite for so that
tl~ determination of the acceleration and deceleration of 1 r 1
Ihe rotor. It represents the stored energy per kva and can ex-ee,d-((2d-X&d &. (97)
1~ computed from the moment of inertia and speed by the
follo\ving expression In network calculator studies of system stability, e,,
e,,d, and id are known at any instant. From Eq. (94) it is
H=0.231WR2(rpm)210-6
(93) evident that the increment of egdis equal to the increment
kva in ed’. Thus
\Vtlere H = Inertia constant in kw-sec. per kva.
WR2= Moment of inertia in lb-ft2.
Ae,d=&-
L cl0L
ex-ee,d-((Zd-xp)id 1
-1
At (98)
176 Machine Characteristics Chapter 6

This method can be applied regardless of the number of of unidirectional and negative-sequence currents. The crest
machines involved in the study. value of the negative-sequence current, iz, is fiiz and the
To obtain the initial value of eqd, calculate ed’ from
crest value of i” is G I,’
the steady-state conditions before the disturbance. cd’ is
the quantity which remains constant during the instant In the case of neztive-sequence currents, part of the
representing the change from one operating condition to loss is supplied by the shaft and part is supplied through
another. The proper eqd is obtained by changing the the armature. The loss associated with the circulating
magnitude of eQduntil Eq. (94) is satisfied. currents in the rotor as developed in Section 15 is approz-
To include the effect of saturation, break the reactance imutely equal to 2(rz-rl)i$ Assuming for the moment that
xq, which represents the machine, into two components the loss varies as the square of the current and neglecting
5, and (z,--zP), the latter being next to the voltage e,d. the differences due to the frequencies in the two cases, the
The voltage at the junction of these two reactances is eP, loss for the unidirectional components of current is
the voltage behind x,. The effect of saturation will be
included by adding the saturation factor s taken from the
no-load saturation curve (see Fig. 17) for eP,to the excita-
tion obtained by neglecting saturation. This corresponds
to method (d) of Sec. 3 for steady-state conditions. Eq.
(98) then becomes Actually, however, the loss varies more nearly as the 1.8
power of the current so that the expression becomes
Aeqd=$
do II
e,-e,d-(xd-x,&-s
1
At. (99) \

27. Armature Resistance Now considering the effect of frequencies. Since the
For most stability studies the loss associated with the depth of current penetration varies inversely as the
resistance of the armature is so small as to be negligible. square root of the frequency, the resistance varies directly
The exception to this rule is the case for which a fault as the square root of the frequency. The loss for the uni-
occurs near the terminals of a generator. directional component is then
The losses in an a-c generator during a three-phase short
circuit can be large enough to affect significantly the rate (101) j
at which the rotor changes angular position. This is of
particular importance for stability studies. Two of the
most important factors determining this effect are the loca- 36
tion of the fault and the value of the negative-sequence
resistance. The latter is difficult of evaluation particularly --
3.77 j i
for turbo-generators-the type of machine in which the I
effect is greatest. One must rely almost entirely upon cal- 1 I
I
culations, which are extremely complicated. For a-c board 2.6 : .I4
studies of system stability it is convenient to represent the I
machine losses by means of a resistance placed in series in
the armature. The value of this resistance should be chosen 2.4 .I2
so that its loss, with the reactance of the machine repre-
sentcd by xdl, be equivalent to that of the machine under u)
actual conditions. An approximate evaluation of this $2.0 .I0
J
equivalent resistance will be developed for a turbo-
generator.
Let the initial value of the subtransient component of
short-circuit current be designated, i”. The components
of the unidirectional current have a maximum value fii”
and are related in the three phases in a manner as discussed
in Sec. 8. The sum of the unidirectional components in all
three phases produce anessentially sinusoidal wave of mmf
that is stationary with respect to the armature. This sta-
tionary mmf develops a flux that in turn generates currents
having a frequency of 60 cps in the rotor. This effect is
similar to that produced by negative-sequence currents in
the armature except that the latter produce a sinusoidal
wnf wave that rotates at a speed corresponding to 60 cps
in a direction opposite to the rotation of the shaft and TIME IN SECONDS
ultimately generates circulating currents in the rotor hav- Fig. 50-Development of req of a turbo-generator for the CC
ing a frequency of 120 cps. The magnitudes of the mmf dition of a three-phase short circuit across the terminals
waves in the two cases are equal for the same crest values the machine for various duration of the short circuit.
(;hapter 6 177

The loss associated with this current is

To form an idea of the order of magnitudes of these


losses, let
x:‘=o.oo. T,=0.09.
x:=0.15. Ti=0.6.
x3=1.25.
T2=0.035.
?-I= 0.005.
The results of the calculations are shown in Fig. 50. The
upper dashed curve is the loss associated with the uni-
direrFtiona1 component and the lower dashed curve the load
_- losses. The full line represents the total losses. The cur-
WITHOUT DAMPERS
1 I h
rent flowing in the generator as represented on the board
1
is constant and equal to 7. The equivalent resistance,
Oo .05 JO .I5 .20 .25 .30 .35 xd

TIME IN SECONDS req, to be inserted in series with xd’ must be such that the
(a) integrated loss over any interval must be the same as that
in Fig. 50. The dot-dash curve in Fig. 50 gives the values
of I-,~ obtained by this method.
Figure 51 gives similar values of req for other types of
machines. The curves in Fig. 51(a) were calculated for
short circuits at the terminals of the machines, those in
Fig. 51(b) are for three-phase short circuits across the
terminals of a transformer connected in series with the
machine.

VIII. UNBALANCED SHORT CIRCUITS ON


MACHINES WITHOUT DAMPER WINDINGS
Because of the dissymmetry of salient-pole machines
without damper windings, the armature currents at times
of three-phase short-circuits, as shown in Sec. 12, contain
second-harmonic components. For unsymmetrical short-
circuits, such as from terminal-to-terminal, the wave forms
TIME IN SECONDS
of currents and voltages become even more complex. Both
(b) odd and even harmonics are present.
Fig. 5l-Typical equivalent resistance, res, for different types 28. Terminal-to-Terminal Short Circuit
of machines.
In particular consider a salient-pole machine in which
(:L) for three-phnse short circuit across the terminsls used
(1)) for three-phase short circuit across the terminals of a series-
saturation is neglected and which is operating at no load
connected transformer of 10 percent impedance. to which a short-circuit is suddenly applied across two
terminals. The short-circuit current5 in these phases is
then
Since the unidirectional current decreases exponentially
with a time constant T,, the loss as a function of time is (105)
i=(x,+xd’)+(xq-xd’) cos2(!hft+$O)
1.81
~/z(rz - 7-l) e- E in which &, indicates the phase position during the cycle
(102) at which the short-circuit occurred.
(%I”) l.B *
It will be observed that this can be resolved into two
ln addition to the losses associated with the unidirec- components
tional current, the load losses as reflected by TI can also be
significant for a three-phase fault across the terminals. V3 It sin (27rfL+&
(106)
xcglecting the sub-transient component, the a-c com- First: (xq+xd’) + (xq-xd’) cos 2 (2?rftf4o)
ponent of short-circuit for a three-phase short circuit from 4 If sin &
no-load is (107)
Second: (xg+xd')+(xq--xd') cos 2 (2rfl+$O)
[(+-$-&+$I. (103)
The first component is shown in Fig. 52(a) for a typical
machine and consists of odd harmonics only. The second
Machine Characteristics Chapter 6

xd’+d5gG
Thus &eady-state
= &II
x,1+ d\/2skdl
sin (2~jL+&)
(108)
[(xq+xd’)+(xq-E,,‘) 00s 2 ca?rfl-+)]
With the assistance of Fig. 52 it Gil be seen from Eq.
(105) that the maximum amount of the odd harmonic
component is equal to e. The masimum value of
the total current is dependent upon the instant during
the cycle at which short-circuit occurs and reaches a
maximum of G.
Xd’
Assuming no decrement for either the odd or evenA
harmonics

TOTAL

+--+--- 271
ARMATURE CURRElYT FIELD CURRENT 4

Fig. 52-Armature current and field current in a synchronous 3


machine when a terminal-to-terminal short circuit is sud-
denly applied. 2

Xd’ = 0.30 xd=l.l x,=0.75 A,=90” I

0
component is sholvn in Fig. 52(b) for &= +90” and con-
-I
sists of even harmonics only. The latter component is de-
pendent upon the instant during the cycle at which the -2
short-circuit occurs and may vary anywhere between the
-3
values given and the negative of those values in accordance
lvith the coefficient, sin 40. Figure 52(c) gives the total -4
current, the sum of Figs. 52(a) and 52(b). 2

The units chosen are the p.u. in which for the machine Y
4 ’
operating at no-load at rated circuit voltage If would be 5 (bl \ I \
g0
equal to 1.0 and in this case the current i is given in terms
of crest magnitude of rated phase current. -I
The components of armature current shown in Figs.
5
52(a) and 52(b) have associated with them the field cur-
rents shown in Figs. 52(d) and 52(e), respectively, the for- 4
mer consisting only of even harmonics and the latter only
3
of odd harmonics. In Fig. 52(f) is shown the total field
current. The average magnitude of this current is equal to 2

xd+lhzz I
---If. (Cl
Xd’-t~ 0

The odd-harmonic component of field current and its as- -I


sociated even harmonic in the armature decay to zero with
time. The even harmonics of the field and their associated -2

odd harmonics of armature current decay to constant, Fig. 53-Wave form of voltage across terminals of a water-
steady-state amounts. Their initial values are in excess of wheel generator without damper windings for a terminal-to-
their steady-state magnitudes by the amount the average terminal short circuit from no-load. xq/xd’ =2.5.
of 1f is in escess of its steady-state amount, If. The steady- (a) Initial value of odd harmonic component (decays slowly);
state value of i is then equal to the initial amount of the (b) initial value of even harmonic component for sin @,rl (decays
odd-harmonic component multiplied by rapidly). Its magnitude varies between that given and ita
negative dependingupon the point during the cycle at which
xd’+dgz short circuit occurs. It may be zero.
Xdfd/Z,Zdl (c) Total initial value for sin GO= 1
Chapter 6 Machine Characteristics 179

The rms total current is equal to t,hc square root of the m[L+eb Soa28+4b2cos40+6b3cos66+---4
Slun of the squares of those components. It must be re-
membered that the unit of current is the crest of rated
terminal current. When expressed in t.erms of the rated
,.,I1,ycurrent the above figures must be multiplied by ~‘2.
‘The voltage from the short-circuited terminals to the v,
froc terminal, neglecting decrements, is equal to e--31dK[sin0+3bsin36+5b2sin56+---3 1
,~,,-P,,=Q,= --3frK[sin(27rfl+&)+3bsin3(2?rfl+&) +3Id sin OC[Z!b cos 2 8 t4 b2 Cos 4 6 +---I /T i
+5b2 sin 5(27rfl+&)+. .]
+3If sin +[2b cos 2(27rfI+&)
+4bZ cos 4(2~rfl++) + .] ClW
in which
Fig. 55-Equivalent&rcuit to which Fig. 54 may be reduced.
K=G7z
(113) b=-%G7z-1
dGJxd’+ 1
1/x&d’+ 1
ant1 h has its previous significance.
I,ike the short-circuit current this voltage can likewise
bc resolved into two components that together with the at times of unbalanced short circuit, that resonance occur
t,otnl voltage are plotted in Fig. 53. The maximum possible between the reactance of the machine and the load
voltage, that which occurs when sin & is equal to unity, is with the possibility that dangerously high voltages might
result. Considering a purely capacitive load such as an
eab(maxlmnm 23-l
ror max. OuX Ilnkagea) -iIf
(114)
-
unloaded transmission line, the schematic diagram is shown
( ) in Fig. 54 and the equivalent circuit in Fig. 55 for the
When sin &=O, the even harmonic component is equal condition of a terminal-to-terminal short circuit. The emf
IO zero and for this case the maximum voltage is applied to the circuit is equal to the open-circuit voltage
for the same short-circuit condition. The oscillographic
results of tests made on a particular machine as terminal-
to-terminal short circuits are applied for different amounts
‘l’hc corresponding line-to-neutral voltages for the termi- of connected capacitance are shown in Fig. 56. Resonance
n:J-to-terminal short-circuit are ?,$ of the above figures. will occur near points for which the quantity *=n2,
In all of these expressions the crest value of rated line-to-
nclltral voltage has been used as a base. When the rms where n represents the integers 1, 2, 3, etc., and also the
ligure is used, the above quantity must be multiplied order of the harmonic. The nature of this resonance phe-
hy a. nomenon is illustrated more clearly by the curve of Fig. 57,
For a terminal-to-neutral short circuit, neglecting de- in which is plotted the maximum voltage during short-
crrments, the short-circuit current is circuit in per unit.
To orient one’s self with regard to the length of line
3If [cos (2njt + 4”) - cosr$o] involved in these considerations, the figure in miles which
‘=(Zd’+S,,+Zg)+(Zd’-ZR) COS2(27Tjt+I$o)
(116) appears below each oscillogram of Fig. 56 represents ap-
proximately the length of single-circuit 66- or 220-kv
21. Unsymmetrical Short Circuits Under Capa- transmission line that, with a generator having the char-
citive Loading acteristics of the one used in the test, is required to satisfy
When a salient-pole machine without damper windings the given value of xc/a. These figures were arrived
is loaded by a highly capacitive load,12vl3 there is danger, at by assuming a generator capacity of 25 000, 75 000, and
200 000 kva for 66-, 132-, and 220-kv lines, respectively.
For smaller machines the length will decrease in proportion.
The possibility of the existence of such resonant condi-
tions can be determined for other types of loads and other
types of faults by setting up the network for the system
and replacing the machine by the reactance m. This
circuit should be set up for the positive-, negative-, and
zero-sequence networks and the networks connected in
accordance with the rules of symmetrical components. Any
condition for which the impedance as viewed from the
machine is zero or very small should be avoided.
Since the danger of these high voltages arises from the
Fig. 54-sch ematic diagram of a three-phase, salient-pole
ttissymmetry of the machines, it can be eliminated effec-
alternator to which a three-phase bank of capacitors and a tively by the installation of damper windings. Fig. 58
terminal-to-terminal short circuit are applied simultane- presents oscillographic evidence of the voltages existing
ously. for machines equipped with different types of dampers as
chapter 6 Mnchine Characteristics

(d)

[iid. 57-Experimental values of crest voltages (twelfth cycle)


from terminal a to b when switch in Fig. 54 is closed. Unit of
voltage is crest of terminal-to-terminal voltage before short
circuit. sq/sd’=2.2. Machine without damper winding.

I,cyminal-to- terminal short circuits and capacitive react-


:m(‘(‘s arc applied simultaneously. While a continuous
or’ connected damper winding is most effective, a non-

c*onnccted damper minding having a ratio of s, equal to


:II, lcnst 1.35 will be found adequate for practically all
~)llrposcs.

IX. DAMPER WINDINGS


‘UN atltlit,ion of copper damper Tvindings to machines
~Ncctivcly simplifies the characteristics of the machines
:IS vicw&l estcrnally in that harmonic effects are largely
c4irninated. However, the addition of other possible cir-
I’llits for crlrrcnt flow complicates the internal calculations.
‘1‘1~~ir~fIllcnc:e of dampers can in most cases be evaluated
(h)
in 1wrns of their effect’4 upon the subtransient reactances Fig. %-Effect of damper windings.
hi I IN: two ases. Terminal-to-terminal short circuit:
(8) X0 dampers.
3k Types of Damper Windings (b) Connected copper damper.
ILmper windings are of several general types. (c) Connected high resistance damper.
Connected Dampers-These consist essentially of (d) Xon-Connected copperdamper.
\viritlings similar to a squirrel-cage or an induction motor. Terminal-to-neutral short circuit:
‘rllcy are continuous between poles as shown in Fig. 59 in (e) So damper.
\Gh (a) sholvs t,he connection between poles for a SLOW- (f) Connected copper damper.
~cd machine and (b) shows the additional bracing re- (g) Connected high resistnncc damper.
wirccl in the form of an end ring for higher speed ma- (h) Ken-connected copper dumper.
c*llincs. Tn this type of damper, xq” and Q” have nearly
thc same magnitudes. in Fig. 60. They are somewhat cheaper than connected
Non-connected Dampers-The dampers in each pole dampers but at the expense of no longer being able to
i:lcp:~r~ inclepcndent from those in adjacent poles, as shown make x~” and xd” equal.
182 Machine Characteristics Chapter 6
~.. __--.”..,.__._-__ __..
connected in series to slip rings. By connecting a variable
resistor externally to the slip rings t,he starting character-
istics can be varied at will.
The general characteristics of damper windings will be
discussed under the following heads.
31. Balancing Action and Elimination of Voltage
Distortion
One of the earliest needs for damper windings arose from
the use of single-phase generators and, later, phase bal-
ancers. Such machines if unequipped with damper wind-
ings have characteristics which resemble closely those of
a three-phase machine without damper windings when a
single-phase load is drawn from it. Voltage distortion
similar to that discussed under unbalanced short-circuit%
occurs. In addition, if this condition persists the currents
that flow in the body of the pole pieces, produce excessive
heating. The addition of damper windings provides t: low-
resistance path for the flow of these currents and prevents
both wave distortion and excessive heating. Because ‘of.
(b) the steady character of the load, damper windings in
single-phase machines and phase balancers must be heavier
Fig. 59-Connected damper windings:
than those in three-phase machines.
(a) Slow-speed machine. The best criteria of a polyphase machine to carry un-
(b) High-speed machine. balanced load are its negative-sequence reactance and
resistance. The former reflects its ability to prevent un-
balancing of the voltage and the latter its ability to carry
the negative-sequence current without undue heating of
the rotor. These properties are particularly important for
such fluctuating loads as electric furnaces. Not only do
the dampers reduce voltage unbalance but also reduce
wave form distortion.
32. Negative-Sequence Reactance and Resistance
As discussed previously the negative-sequence reactance
and resistance of a machine are both affected by the damper
windings. Table 2 shows the effect of different types of
windings upon a lOO-kva generator12 and Table 3 upon a
5000-kva synchronous condenser.14 Both of these tables
represent test results.

TABLE ~-CONSTANTS OF A SYNCHRONOUS GENERATOR AS


AFFECTED BY TYPE OF DAMPER WINDING (100 KVA,
2300 VOLTS, 25.2 AMPERES)
- - - -
I,
Type Xd’ Xq dXd’X0 Tad
.- __-
No damper. 0.260 0.577 0.388 0.028
Fig. 60-Two types of non-connected damper windings.
,, t /2d1)19)i
.- --
Xd” Xq _- .-
Special Dampers-h this classification fall such
Connected
dampers as double-deck windings, which are in effect a Copper. 0.157 0.146 0.151 0.Q3 0.036
double winding, one of high resistance and low reactance Connected
and the other of low resistance and high reactance. The Everdur. 0.171 0.157 0.164 0.92 0.063
principal uses of this type are in motors where the com- Non-connected
bination provides better starting characteristics. At low Copper. 0.154 0.390 - 0.245 2.53 0.037
speeds the high reactance of the low-resistance winding
forces the current to flow through the high-resistance wind-
ing, which produces a high torque. At higher speeds the 33. Damping Effect
low-resistance winding becomes effective. Another type of In the early days when prime movers consisted mostly
special winding is one that is insulated from the iron and of reciprocating engines the pulsating character of the
chapter 6 Machine Characteristics 183

TABLE ~-CONSTANTS OF A SYNCHRONOUS CONDENSER As ratio is greater than 1.35 and less than 1.35 add 2 and 3
AFFECTEDBY TYPE OF DAMPER WINDING (5000 KVA, percent, respectively, to the price of the machine. In con-
4000 VOLTS, 721 AMPERES)
sideration of the many complicated problems involved in
x*= : (xd"+zq") the selection of a damper winding it would appear, in view
T2
of the low increase in cost of the connected damper, that
TYPC
Test Calculated Test Cdculnted if any damper winding is thought necessary, the connected ’
0.69
type should be used.
?;,, ,l:LIrrpcr. 0.045 0.0‘40 0.75
co ,,,, e,:ted copper. . 0.026 0.029 0.195 0.215
L’(,,,,,,! ctcd brass. 0.045 0.044 0.195 0.215 X. SELF-EXCITATION OF SYNCHRONOUS
(;. ,,,, cc:td Evertlur. 0. 12 0.125 0.20 0.215 MACHINES
-
to,.cllle made parallel operation difficult. This was success- When a synchronous machine is used to charge an un-
f,,lly solved by damper windings in that the damper wind- loaded transmission line whose charging kva is equal ap-
ing allsorbetl the energy of oscillation between machines proximately to the kva of the machine, the machine may
:LI1dprevented the oscillations from becoming cumulative. become self-excited and thevoltage rise beyond control.
>lorc recently in consideration of the stability problem The conditions that must be satisfied for this phenomenon
I,,,v-resistance damper windings have been advocated for to occur are made manifest by determining the machine
tl,(! same reason. While a low-resistance damper winding characteristics for a constant inductive reactive load.
\vill decrease the number of electro-mechanical oscillations
f,,llowing a disturbance this effect in itself is not impor-
t:lrl~l4 in increasing the amount of power that can be
t,r:lnsmitted over the system.
‘1’1~general influence of damper windings, their negative-
s(:(lucnce resistance and reactance, and also their purely
tl:Lmping action, upon the stability problem, is discussed
ill more detail in Chap. 13. \

34. Other Considerations Affecting Damper Wind-


ings

A-AD \
Synchronous generators feeding loads through trans- xpi \ ’
mission lines having a high ratio of resistance to reactance
t,ontl to set up spontaneous hunting.15 This tendency is
greater at light loads than at heavy loads, the criterion at
which it tends to disappear being when the angle between

x
tlw transient internal voltage and the load voltage equals
111~impedance angle of the connecting impedance. There
r~c~tlnot be any periodic impulse, such as the pulsating
Iorcllle of a compressor, to initiate this phenomenon but I hi / I
iI, may very well aggravate the condition. Damper wind-
ings arc very effective in suppressing such inherent hunt-
in:: conditions and also alleviate hunting produced by M
I)Gotlic impulses, although the latter phenomenon is usu-
:llly climinnted by altering the natural frequency of the
s~slom by changing the fly wheel effect of the generator
1)~mot,or or both. Synchronous motors connected through LKL T 0
a

K N
lli!$i rcsistnnce lines or cables also develop spontaneous I--
Ai -(
llllnt,ing but not so frequently as they are always provided
\\.itli :L damper winding. Fig. Cl-Construction of regulation curves for induction
loading.
Grits capacitors in decreasing the effective series react-
a~‘(! increase the ratio of resistance to reactance and thus
t(‘n(l to increase the likelihood of spontaneous hunting. In Fig. 61 the line OAGrepresents the no-load saturation
ln general, where beneficial effects can accrue with the curve. Suppose the machine is loaded with a three-phase
“se of damper windings, the benefits are greater for con- reactor equal to z, ohms per phase. To determine the
nected or continuous dampers than for non-connected regulation curve for this impedance, that is, a curve of
tl;uVers. Mechanically there is no choice as both types terminal voltage plotted against field current, proceed as
‘~‘1 be made equally reliable. The non-connected winding follows: Choose an armature current such that z,i*, the
l(‘n(ls itself somewhat easier to the removal of a pole but terminal voltage, is approximately rated voltage. This
“Ot to sufficient extent to constitute a consideration in the voltage is given by the distance BD in Fig. 61. By adding
‘lloice of type to install. A ratio of zq” to Zd” as low as *In this discussion, the terminal voltage is regarded as the terminal-
abollt 1.35 can be obtained with non-connected and 1.1 to-neutral value. When terminal-to-terminal voltage is used the volt-
‘vitll connected dampers. Damper windings for which this age drops considered will have to be multiplied by 4.
184 Machine Characleristics Chapter 6

to this distance the x,i drop, D-4, the voltage behind Potier
reactance denoted by the point A is obtained. The mag-
netizing current to produce this voltage is given by the
distance OB. In addition to this, however, the field current
Ai is required to overcome the demagnetizing effect of the
armature current. For normal current, Ai is the distance
KN in the Potier triangle, ONN. In conclusion, to produce
the terminal voltage F, the field current OC is necessary.
The triangle BAC is a sort of Potier triangle, in which
the Potier reactance is replaced by a reactance equal to
(x,+ze). Thus by drawing any line HG parallel to CA and
GJ parallel to AF, the intersection with the vertical from
H determines the terminal voltage for the excitation H.
When the load consists of balanced capacitors having a
reactance xc in which xc is greater than xp, the impedance
as viewed from the voltage behind Potier reactance is ca-
pacitive and the armature current is magnetizing instead
of demagnetizing. This case can be treated in a manner
similar to t,hat for an inductive-reactance load with some
modifications as is shown in Fig. 62. In this figure the
distance CF represents the terminal voltage produced by
the esternnl drop ~,a’. Since the current leads the terminal
voltage by ninety degrees the voltage behind Potier react-
ance for the assumed armature current is found by sub-

0 FIELD CURRENT

Fig. 63-Regulation curves for constant capacitive load of


such values as to give the loads at rated voltage indicated on
the curves. HG parallel to Oq. Point q represents excitation
and internal voltage, neglecting saturation, to produce rated
terminal voltage with loo-percent capacitive current.

tracting the drop x,i giving the distance CD or B.4. To


produce this voltage the magnetizing current OB is re-
quired but since the armature current is magnetizing to
the extent of Ai, the actual field current necessary is only
OC. This determines F as a point in the regulation curve. i
For other field currents such as the point H, draw HG :
$ parallel to CA until it intercepts the no-load saturation
curve at G. Then draw GJ parallel to A F. The intersection
with the vertical from H determines the point J.
‘-Fig. 63 depicts the regulation curves for different sizes of
capacitors. The number assigned to each curve represents
the percent kva delivered at rated voltage.
The angle CYin Fig. 62 is equal to tan --l c-x&. At
(X
A.
z
zero excitation it can be seen that if this angle is sufficiently
small, intersection with the no-load saturation curve is
possible, but as Q: increases a point is finally reached at
which intersection is impossible and the solution fails.
This signifies that when this point is reached self-excitation

\I
does-not occur. This critical condition occurs when the

N C
-Ai -
Ii
E
slope (xc - x,)i
Ai
equals the slope of the no-load saturation
curve. In discussing the significance of X,~use was made of
FIELD CURRENT it was pointed out that DA is the current
Fig. 10, where ..a..,--
Fig. 62-Construction of regulation curves for capacitive necessary to ov&rMne the demagnetizing effect, Ai, of the
loading. armature current. The distance AB is the synchronous

L
chapter 6 Machine Characteristics 185

reactance drop xdi and DC the Potier reactance drop.


Thus the slope of the no-load saturation curve is equal to
xdi-xpi
~ The condition for self excitation is then that
W40 ni *
2’
2 (xc-x& (Xd- x,)i
5
Ai < Ai
a.30 Or

6 Xe<Xd (117)
2 St,ated otherwise, the machine will become self-excited if
2
0.20
5 the kvs of the machine as defined by E is less than the
I
z
-.10 !i charging kva of the line E. Since xd is, except for special
2
cases, of the order of 120 percent, danger may threaten
1.0, when the charging kva requirements of the line exceed
2
I approximately 80 percent of the kvn of the machine.
0
0 5 IO 15
TEdhUNAL KV
XI. CAPACITANCE OF MACHINE WINDINGS
A knowledge of the capacitance to ground of machine
windings is necessary for several reasons, among which are:
(a) Grounding of Generators. This is discussed in con-
siderable detail in the chapter on Grounding. The ca-
pacitance to ground of the windings must be known so
that the associated resistance can be selected.
(b) System Grounding. The capacitance must be
known so that the contribution of this element to the
ground current can be determined for single line-to-
ground faults. The contribution to the fault current for
this condition is equal to 43 27rfGEX lows where f is the
MVA
system frequency, E the line-to-line voltage and Co the
Fig. 64-Capacitance to ground of TURBINE-GENERATOR capacitance per phase in microfarads.
windings for 13 200-volt machines in microfarads per phase. (c) System Recovery Voltage. The capacitance of the
For other voltages multiply by factor K in insert.
rotating machines may be an important element in the
determination of the system recovery voltage. It is cus-

KVA
Fig. 65-Capacitance to ground of SALIENT-POLE GENERATORS AND MOTORS in microfarads per phase.
186 Machine Characteristics Chapter 6

capacitance per phase to ground in microfnrnds and E is


the applied voltage from \\-intling to groimd.
Figures 64 to 67 provide basic data calculated for West-
!$ 0.016 inghouse turbine generators and salient-pole generators
2
0. and motors. The generator data was obtained from refer-
El ence 23 and the motor data from some unpublished ma-
a 0.012 terial of Dr. E. L. Harder. This information should be
2 typical of other machines to within about +_ 50 percent.
2 In general, it should be borne in mind that these character-
i? istics vary greatly between machines of different designs.
p 0.006
0 Fortunately, however, not very great accuracy is required
5 for the applications cited above.
50.004
XII. NATURAL FREQUENCY OF SYNCHRONOUS J.
MACHINE CONNECTED TO INFINITE BUS
00
0 100 200 300 400 500 A synchronous machine connected to an infinite bus
HORSE POWER possesses a natural period of oscillation which is given in,
the ASX C50-1943 Rotating Electrical ?\Iachinery
Fig. 66-Capacitance to ground of 2300-volt SYNCHRONOUS
MOTORS in microfarads per phase to ground. For voltages Standards as
between 2300 and 6600, the capacitance will not vary more 35 200 P,Xf
than f 15 percent from the values for 2300 volt. fn=- - cycles per minute (113)
(rpm) J- WR2
where P, is the synchronizing power in kw per degree dis-
tomary to represent the machine capacitance in this
placement,
work by placing one-half of the total capacitance to
f is the system frequency.
ground at the machine terminal. For details of this type
When given an angular displacement, the machine oscil-
of calculation refer to the chapter on Power-System
lates with this frequency and finally subsides unless sub-
Voltages and Currents During Abnormal Conditions.
jetted to periodic impulse of proper magnitude. It is not
(d) Charging Kva. Tn testing the insulation of ma-
within the scope of this work to discuss this subject in its
chines, particularly in the field, it is sometimes necessary
entirety, but merely to derive the above expression.
to know the approximate charging kva of the windings
If an incremental displacement A0 be assumed, the cor-
so that a transformer of sufficiently high rating can be
responding synchronizing power is
provided beforehand to do the job. This is required
either for normal routine testing, for testing at time of LIP= P,AO in kw (114)
installation or for testing after rewinding. The charging and A0 is in degrees. From the Stability Chapter it can be
kva per phase is equal to 2rfCoE?X 10e6 where Co is the seen that the acceleration of the rotor is
180 f
a = -...-2- AP in deg/sec2
kva ZZ
0.04
I
rf
= -----AZ’ in rad/sec2
(kva) Ii
where the kva refers to the rating of the machine and H
the inertia constant. Substituting H from Eq. (93)
E
a 0.024
a=% (Wn’:(rpmj2AP in rad/sec2 (116)

and substituting AP from Eq. (114)


7r106
fPr A0 (117)
“‘OX (WZ?)(rpm)?
= - KA0. (118)
K= -%f. fP= (119) ;
0.231 (11~R2)(rpm)2’ 8
0
0 100 200 300 400 500
The sign of P, is actually negative as an increment in A0 {
HORSEPOWER
produces a torque which tends to return the machine to the
3
Fig. 67-Capacitance to ground of 2300-volt INDUCTION -operating angle. Thus, I< is positive. Now
MOTORS in microfarads per phase. For voltages between
2300 and 6600, the capacitance will not vary more than fY(A8)
a=-= -KAB.
?I 15 percent from the values for 2300 volts. Ia2
chapter 6 Machine Characteristics 187

current equal to rated value is called the “rated-current


A8 = A sin 27rfJ reactance.”
(121) X knowledge of these two values of xd’ is not sufficient
then substituting this relation into Eq. (120) for all applications for which zd’ is required. The ratcd-
- (27rfn)2 A sin 27rf,l= -Kd sin 27rfnt current xd’, because of lower excitation, lends itself more
readily for determination from test. The rated-voltage 2.d’
from which is that required for short,-circuit studies. Saturation within
the machine is a minimum for the former and a masimum
f2E
n for the latter. The rated voltage value is sometimes called
27r .
the “saturated value” and is the value usually given by the
S,~hstitut,ing K from Eq. (119) designer. Certain applications, such as stability studies,
demand a quantity determined under conditions for which
f,, = g&g cycles per set (122) the terminal voltage is near rated voltage and the armature
current is likewise near its rated current. Fig. 68 obtained
whic*h converts to Eq. (113). from data presented by Kilgore16 shows how the reactances
of typical machines of different classes vary if three-phase
short-circuits were applied from rated voltage no load, the
XIII. TYPICAL CONSTANTS AND CQSTS
current being altered by introducing different esternal
130th the voltage and the current at which a machine reactances in the armature circuits. The rated-current
operates affect certain of the principal constants through figure is used as a base for all the curves. The particular
t,hc variability of the permeability of the iron. In this reactance on the curves for rated current is the one that
sclnse,these so-called constants are not iq reality constant. would have greatest utility for stability and regulation
Consider the transient reactance, z~‘. If three-phase short- problems. No specific name has been assigned to this
circllits arc applied to a machine from no load, the react- quantity.
:Lnccsso obtained vary with the excitation. Two of these Similar considerations apply to the subtransient react-
cllwntities have been given special designations. Thus the antes, with this difference, that the rated-current reactance
rcw:tance obtained when the excitation is such as to pro- xd” is obtained from the same test as that for which the
t111ccrated voltage at no load before the short-circuit is rated-current reactance of xd’ was obtained. In this case
cnllcd the “rated-voltage reactance” and the reactance rated current refers to the transient component and not
obtained when the excitation is reduced so as to produce the subtransient component of current. Fig. 69 shows how
from no load a transient component of the short-circuit

2J I.1
w 5
3 TURBINE GENERATORS EINE GENERATOR
I- 1.0
;:
= 0.9 E
2 0.9
?I 3
z 1 0.6
2, 0.6 ii
0 0 I 2 3 4 5 6 7 6 9 IO $ 0.7 012345676

SALIENT-POLE GENERATORS
AND MOTORS
1 ~~~ERATOR, ,

2 012345676

x
SALIENT- POLE F
#$ I.1 n SALIENT-POLE MACHINES
SYNCHRONOUS CONDENSERS

TRANSIENT COMPONENT OF
0 I 2 3 4 5 ARMATURE CURRENT IN PER UNIT
TRANSIENT COMPONENT OF
ARMATURE CURRENT IN PER UNIT Fig. 69-Saturation factors for subtransient reactance.
“Rated current” value used as base. All reactances from
Fig. 68-&t uration factors for transient reactance. Three- three-phase short circuits without external reactance. Satu-
Phase short circuits from rated voltage no load. Current ration factors for salient-pole machine with damper winding
limited by series reactance. is equal to unity.
188 Machine Characteristics Chapter 6

X,1” varies with the transient component of current, all


points being obtained from three-phase short-circuits with
no external reactance, the cllrrent being altered by the
escitntion before the short-circuit.
In general, it is unnecessary to make this distinctionfor
the negative-sequence reactance. The AIEE codelo sug-
gests determination of x2 by means of the method discussed

0.601
0.60 , , , , , , , , , I I

gg 0.50
0.50
22
0 0.40
PER UNIT ARMATURE CURRENT
d
; 0.30 Fig. 72-Variation of x0 for turbine generators.
5
3 0.20

B 0.10
B
pp 0.10

0.01
0.0.
0
’ 20000’ ’ 40000’ ’ 60000’ ’ 00000’ 1100000
’ ’ 120000
I
KVA
Fig. 70-Normal unsaturated transient reactance (xd”‘) for
waterwheel generators. 7
6

under Negative-Sequence Reactance, the current during


the sustained terminal-to-terminal short-circuit being
limited to the rated current.
The normal value of I’d,, designed into waterwheel gen-
erators varies with the kva capacity and speed. These
values are plotted in curve form in Fig. 70. To obtain
lower values than those indicated usually involves an RATING IN THOUSANDS OF KVA
increased cost.
The angular relations within the machine are determined Fig. 73-Open-circuit transient time constants of a-c gen-
erators and motors.
to a large extent by x,. The variation, by test, of x, for
several salient-pole machines*2*17is shown in Fig. 71.

ARMATURE CURRENT IN PER UNIT 2 I


Fig. 71-x, for salient-pole machines.
A = 7500 kva generator without damper winding. 0
0 20 40 60 00 100 120 140
B= 750 kva generator without damper winding. RATING IN THOUSANDS OF KVA \ i
C = 33 1 kv:t motor with damper winding removed.
D = 100 kva generator with damper winding. Fig. 74-Open-circuit transient time constants of turbine i
generators.
1
The zero-sequence reactance, as evidenced by Fig. 72 the wide variation of Td’,, with the size of the unit the
taken from Wright’s paper,” is not affected to any great curves of Figs. 73 and 74 taken from a paper by Hahn
extent in the region for which it has greatest use. and Wagner,‘* are also included.
For practical purposes the effect of saturation upon the Table 4 gives both the range of typical constants that
open-circuit transient time constant Td’,, and the sub- are characteristic of normal designs and also an average
transient short-circuit time constant Td” can be neglected. that can be used for general purposes when the’specific
In general, Td’ varies I7 in the same manner as zd’, so that value of a particular machine is not known. The negative-
,
the relation Td’=zTd’,, is still maintained. Because of sequence resistance is that obtained at a negative-sequence
current equal to rated current. It must be kept in mind
chapter 6 Machine Characteristics 189

that the loss assocrated therewith varies as the second


Power of i, for snhent-pole machines either with or without
damper windings and as the 1.8 power of it for turbine
g’,,~crators. Column (0) in Table 4 refers to the a-c re- I

,,ist:rncc, or, (which includes the effect of load losses) and


,,,l,rmn (10) the d-c resistance, T,,.
‘f’hc inertia constant, II, which is discussed in Chap. 13
-
is likc\vise given in Table 4. The general variation of H of
t,,r.\,ogcnerators and the corresponding figures for water-
,vhccf gcnerntors are given in Fig. 75. The effect upon H

IO

c -
8

- -

THOUSANDS OF KVA
(a)
,

- -

>

- -

THOUSANDS OF KVA !A
Ibj
Fig. 75-Inertia constants. - - -
(:L) I~rgr turbine generators, turbine included. n
(11) fxge vertical type waterwheel generators, including allow-
:LIICCof 15 percent for waterwheels. - -

of incrcnsing the short-circuit ratio and changing the ”


P’)\vcr-factor is given in Fig. 76. The WR2 represented
‘9 the curves of Figs. 75 and 76 are those obtained -

Ir()m a normally designed machine in which no particular


4
cfT()rt has been made to obtain abnormally high H. When
m%nitudes of WR2 in excess of these are desired a more
cxPcnsive machine results. The additional cost of the
additional WR2 is about proportional as shown in Fig. 77.
The cost per kva of water-wheel generators depends
“Pan its kva and speed. The extent of this variation is
shown in Fig 78 Machines of higher short-circuit ratio I

OrPower-factor are more expensive in the proportion shown


Machine Characteristics Chapter 6

; 60
0
0
z 50

: 40
zi
Fj 30
s
g 20
2
z IO
E
E 0
a. 1.0 1.4 1.6 2.2 2.6 3.0
SHORT CIRCUIT RATIO

Fig. 79-Effect of short-circuit ratio upon cost (Normal 1.0


short-circuit ratio and 0.8 power-factor used as base). A
SHORT CIRCUIT RATIO

20 -
Fig. 76-Effect of short-circuit ratio upon H.

\
16 I,, I
1

111
OO 20, 40 60 60 100
PERCENT INCREASE IN H

Fig. 77-Effect of increasing H above the normal values given


by Fig. 75.

46

THOUSANDS OF KVA

Fig. W--Cost of synchronous condensers including exciter


and autotransformer.

in Fig. 79. Naturally these figures will vary from year to


year with the cost of materials and labor.
The condenser cost per kva including the exciter, pilot
exciter, and auto-transformer is plotted in Fig. 50. The
exciter kw varies with the size of the unit, ranging from
1.2, 0.7, and 0.32 percent for a 1000, 5000, and 50 OOO-kva
unit, respectively.
The cost of normal exciters for water-wheel generators
varies from 7 to 13 percent of the cost of the generato]
alone for slow speeds, and from 2.5 to 6 percent for high
speeds. The larger figures apply for units of about 300C
kva and the smaller figures for machines of about 50 OOC
I ! I I kva. Direct-connected pilot exciters cost approximately

0 IO 20 30 40
J
50
30 percent of that of the exciter.

THOUSANDS OF KVA XIV. INDUCTION MOTORS


Fig. 78-Cost of waterwheel generators including direct-con- The equivalent circuit of the induction motor is shown
nected exciters only. l--s
in Fig. 31. The loss in the resistor -rr represents the
(0.8 power-factor and 1.0 short circuit ratio) s
CO.9power-factor and 1.1 short circuit ratio) shaft power and since the circuit is on a per phase basis,
(1.0 power-factor and 1.25 short circuit ratio) the total shaft power is thus
chapter 6 Machine Characteristics 191

example of this case is the phenomena that, occurs during


Total shaft, power = ?(3&2) in watts (123) the interval between the transfer of power-house auxiliaries
from one source to another. In the second case, the tmn-
=- 7:6 ~(3rir2) in hp. (124) sicnt is determined by reactions involving both the stator
and rotor and the duration is quite short. Examples! of
‘rllc rotor copper loss is (3r,i,?). Therefore, neglecting this case, are the sudden energization of an induction motor
,~tllcr losses, the efficiency is: or sudden short circuit across its terminals.
total shaft power 35 Contribution to System Short-Circuit Current
Efficiency =
total shaft powerfrotor copper loss In the calculation of system short circuits only synchro-
1 -s nous machines are usually considered but in special cases
!9 where induction machines constitute a large proportion of
c-----=l-...,$. (125) the load, their contribution to the short-circuit current
$+1 even if its duration is only a few cycles may be large enough
c to influence the choice of the breaker from the standpoint
‘rll~~s, the efficiency decreases with increasing slip. For of its short-time rating, that is, the maximum rms current
10 percent slip the efficiency is 90 percent, for 90 percent the breaker can carry for any time, however small.
slip the efficiency is 10 percent. Similarly, the rotor copper As a first approsimation the short-circuit current sup-
ll)ss is directly proportional to slip; being 10 percent for plied by an induction motor can be resolved into an alter-
10 percent slip and 90 percent for 90 percent slip. nating and a unidirectional component much like that for
The total shaft power can also be expressed in terms of a synchronous machine. The initial rms magnitude of the
t,or‘ques. Thus, alternating component is equal to the terminal voltage
to neutral divided by the blocked rotor impedance per
‘[‘it :tl shaft horse power = ~o(Ti”Ib”)(‘pm).,..(l--s). phase. The time constants are namely,
for the alternating component,
(126)
(blocked rotor reactance per phase in ohms)
I~:cll~ating(124) and (126), the torque is in cycles.
2a (rotor resistance per phase in ohms)
(3Trir2) in watts for the unidirectional component,
T=7.04 l lb ft. (127)
(w-dsyn. Sin per unit
(blocked rotor reactance per phase in ohms) in cycles
‘l’hc equivalent circuit of Fig. 31 can be simplified con-
2~ (st,ator resistance per phase in ohms)
sitlcrably by shifting the magnetizing branch to directly
:tcross the terminals. The resultant approximate circuit Fig. 82 shows the short-circuit current of a 25-horse-power,
is shown in Fig. 81. This approximation permits of 550-volt squirrel-cage motor. The dotted line in the upper

JXs 3 JXr

Fib. Sl-Approximate equivalent circuit of induction motor.

I’~LtivcIy simple determination of i,, SO that Eq. (127)


1Worncs
-
7.04E2 s
lb ft. (128)
T= (rpm) 8yn. 3

LIost, transients involving induction motors fall within


one of two categories; first, those in which the machine is
(lisconnected from the source of power and, second, those
in which the machine remains connected to the source of
Power. In the first case the transient is determined largely Fig. 82--Short-circuit currents in armature of squirrel-cage
hY changes in magnetization and may be quite long. An induction motor.
192 Machine Characteristics Chapter 6 ’

curve indicates the computed value of the envelope of the r, 1.02 xg.00 x,=.00 rr =.02

alternating component of short-circuit current. The am-


plitude shoivs a substantial check but the computed time
.oLTA:~gl-$YFJ ?rL=3’o
constant was low. This can probably be attributed to using
the a-c resistance of the rotor rather than the d-c resistance.
The dotted line in the lower curve is the computed value of
the unidirectional component which checks quite well.
Wound-rotor motors, operated with a substantial amount
of external resistance, mill have such small time constants
that their contribution to the short-circuit can be neglected. TO,ROUE = Td

36. Electra-Mechanical Starting Transient


Fig. 31 shows the conventional diagram of an induction
motor. In the present discussion the per unit system of t 0.5 / / \---Y \I TORQUE’T
\I I I I
if
units will continue to be used, in which unit current is the ln 0.4 / ,
/ CALCULATED TOROUE ‘%
current necessary to develop the rated power at the rated / /-\ POINTS NEGLECTING
MAGNETIZING INRUSH
voltage. The unit of both power and reactive volt-amperes 1
will be the rated kva of the motor and not the rated power TIME dt/dw /

either in kilowatts or horse power. This convention is


consistent with the choice of units for the impedances. At 0. I
rated slip the volt-amperes input into the stator must be
0
1-S 0 04 a.0 1.2 I .6 TORQUE
equal to unity but the power absorbed in the resistor-r,
s 0 I 2 3 4 5 6 7 8 dt/dw AND TIME

will be less than unity and will be equal numerically to Fig. 83-Illustrating calculation of speed-time curve of an
the ratio of the rated power of the motor to the rated kva. induction motor upon application of full voltage.
The unit of shaft torque requires special comment. The
shaft power can be expressed as
l-s
Shaft Power in kw = kvarsbd Izrr- (129) T in per unit=ei
s *
In terms of torque the shaft power is equal to
Shaft Power in km The crosses close to the torque curve in Fig. 83 were
computed by this expression.
=. 746T
inibft 2drpm),,dl-s)~ (13o) In Fig. 83 is also shown the torque requirements of a
33 000 particular load such as a blower. Upon applying voltage
Equating, there results that to the motor the difference between the torque developed
by the motor and that required by the load is the torque
33 000 available for acceleration of the rotor. To convert to accel:
T in lb ft= kVarated I$ (131)
W0.746) b-pm) synch. eration it is convenient to introduce a constant, H, which
is equal to the stored energy in km-sec. per kva of rating’
If unit torque be defined as that torque required to pro-
at synchronous speed. H may be comnuted bv means of
duce a shaft power equal to rated kva at synchronous
Eq.<93). WR* must, of course, include the WRiof the con- 1
speed, then from (130), the unit of torque is netted load.
33 000 Suppose that one per unit torque is applied to the motor’
2dO.746) (rpm)synch.
kvarated which means that at synchronous speed the power input’
into acceleration ,of the rotor is equal to rated kva, and
and equation (131) in per unit becomes suppose further that the rotor is brought to synchronous.
speed in one second. During this interval the acceleration ’
T in p.u. = I$. 032) is constant (1 per unit) and the power input increases’
s linearly with time so that at the end of one second the:
For the purpose of determining the nature of electro- stored energy of rotation is (s kva) in kw-sec. Thus 1 per ;
mechanical transients upon starting a motor from rest, the unit of torque produces 1 per unit of acceleration if the
first step involves the calculation of the shaft torque as a inertia is such that s kva of stored energy is produced ix?
function of the speed. Either the conventional method of one second. From this it can be seen that if the inertia is I
the circle diagram or expression (132) can be used. In such that at synchronous speed the stored energy is H
using the latter method it is only necessary to solve the then to develop this energy in one second, the same acceler
network of Fig. (31) and substitute the solution of I, there- ation but a torque 2H times as great is required. Therefore
from into Eq. (132). A solution of a typical motor is shown there results that
in Fig. 83. For most motors the magnetizing branch can be
neglected, for which case the torque expression becomes
Machine Characteristics 193

u,2500
e 250011
Ablccelerntion can be expressed as ‘5 and its reciprocal f-I
92000
B 2000
I:
“’
as &’ Thus from (134) I: 1500
dt 2H 2
> 1000
(135)
dw T-TL 2
2 500
‘Ihis function is likewise plotted in Fig. 83. The utility of 0
l,lris form of the expression may be seen at once from the 8
a 0 IO 20 30 40 50 60 70
TIME-CYCLES
f:,,.t that $ is known as a function of w and the time to
Fig. %-Decay of residual voltage% of a group of power house
rc:lch any value of w can be determined by a simple c auxiliary motors.
integration. Thus
210
t= g dw (136)
i( )
l<y summing up areas (such as indicated by the shaded
portion) in a vertical direction, the time to reach any
spcctl is obtained. The curve of time so obtained is
pl(jt,tcd in Fig. 83.
The following formula can be used to form an approxi-
rnt1.c idea of the time required to accelerate a motor:
\vtrose load varies as the square or cube of the speed, to
h:tlf speed
Time to half speed= H(rsSnr)2in seconds (137)
rre2t
All of the above units must be expressed in per unit. Re-
member also that 2. should include any external react-
:mce in the stator back to the point where the voltage
0
may be regarded as constant and et should be that con- 200 300 400 500 700 1000 1500
nl,:tnt voltage. HORSEPOWER

37. Residual Voltage Fig. 85-Typical time constants for 2300-volt squirrel cage
induction motors.
If an induction motor is disconnected from its supply, it
rotates for some time, the rate of deceleration being de- appears at the open terminals of the machine. If the volt-
tcrmined by the inertia of its own rotor and the inertia of age source is reapplied when the source voltage and residual
lhc load and also by the nature of the load. Because of voltage of the motor are out of phase, currents exceeding
the inductance of the rotor, flux is entrapped and voltage starting values may be obtained.

I I I I I I I
1
20 40 60 100 200 400 600 1000 2000 4000 6000 lot
MOTOR SIZE IN HORSEPOWER

Fig. SC-Approximate variation of price with voltage and horsepower of squirrel-cage


induction motors. These values apply approximately for 8 poles or less for 60-cycle
motors. Most economical used as base price.
.

c’
194 M’achine Characteristics Chapter 6

Figure 84 shows the decay of a group of power-house 9. Two-Reaction Theory of Synchronous Machines, II, by R. H.
ausiliary motorsz5. The group had a total rating of 2500 Park, A.I.E.E. Transactions, Vol. 52, June 1933, p. 352.
kw of which the largest was 1250 hp. This curve includes 10. A.I.E.E. Test Code for Synchronous Machines. A.I.E.E. Publi-
not only the effect of magnetic decay but the reduction in cation So. 503, June 1945.
11. Discussion, by C. F. Wagner, A.I.E.E. Transactions, July 1937,
voltage due to decrease in speed. The open-circuit time
p. 904.
constant for individual 2300-volt machines is given in Fig. 12. Unsymmetrical Short-Circuits in Wat,cr-Wheel Generators
85. There is a great variance in this constant between Under Capacitive Loading, by C. F. Wagner, A.Z.E.E. Transac-
different designs but these curves give an idea of the mag- lions, Sovember 1937, pp. 1385-1395.
nitude for squirrel-cage induction machines, 13. Ovcrvoltages on Wat,er-Wheel Generators, by C. F. Wagner,
The Electric Journnl, August 1938, p. 321 and September 1938,
38. Cost of Induction Motors p. 351.
The price of induction motors of a given rating varies 14. Damper Windings for Wntcr-Wheel Generators, by C. F. Wag-
with the voltage. As the rating increases the most eco- ner, A.Z.E.E. Transaclion.s, Vol. 50, March 1931, pp. 140-151.
nomical voltage also increases. To form a basis of judg- 15. Effect of Armature Resistance Upon Hunting of Synchronous
Rlachines, by C. F. Wagner, A.I.E.E. Transactions, Vol. 49,
ment of the effect of voltage upon size the curve in Fig. 86
July 1930, pp. 1011-1024.
was prepared. 16. Effects of Saturation on Machine Rcactances, by L. A. Kilgore,
b
A.I.E.E. Transactions, Vol. 54, 1935, pp. 545-550.
17. Determination of Synchronous Machine Constants by Test,
REFERENCES by S. H. Wright, A.Z.E.E. Tmnsnclions, Vol. 50, 1931, pp.
1. Power System Transients, by V. Bush and R. D. Booth, 1331-1350.
A.I.E.E. Tmnsaclions, Vol. 44, February 1925, pp. 80-97. 18. Standard Decrement Curves, by W. C. Hahn and C. F. Wagne;,
2. Further Studies of Transmission Stability, by R. D. Evans and A.I.E.E. Transactions, 1932, pp. 353-361.
C. F. Wagner, A.Z.E.E. Transactions, Vol. 45, 1926, pp. 51-80. 19. Approximating Potier Reactance, by Sterling Beckwith,
3. Synchronous Machines-1 and II-An extension of Blondel’s A.I.E.E. Transaclions, July 1937, p. 813.
Two Reaction-Theory-Steady-State Power Angle Chnracter- 20. Auxiliary Power at Richmond Station, by J. W. Anderson
ist,ics, by R. E. Doherty and C. A. Xckle, A.I.E.E. Transac- and A. C. Monteith, A.I.E.E. Tronsaclions, 1927, p. 827.
tions, Vol. 45, 1926, pp. 912-942. 21. Preferred Standards for Large 360%RPM a-Phase 60-Cycle
4. Synchronous Machines-III. Torque Angle Characteristics Condensing Steam Turbine-Generators, AIEE Standards Nos.
Tinder Transient Conditions, by R. E. Doherty and C. A. 601 and 602, May 1949.
Nickle, A.I.E.E. Transactions, Vol. 46, 1927, pp. 1-14. 22. Regulation of A-C Generators With Suddenly Applied Loads,
5. Synchronous IMachines, IV, by R. E. Doherty and C. A. Xickle, by E. L. Harder and R. C. Cheek, t1.Z.E.E. Transnclions, Vol.
A.I.E.E. Transactions, Vol. 47, No. 2, April 1928, p. 457. 63, 1944, pp. 310-318.
6. Synchronous Machines, V. Three-Phase Short Circuit Syn- 23. Regulation of A-C Generators with Suddenly -4pplied Loads-
chronous Machines, by R. E. Doherty and C. A. Nickle, II, by E. L. Harder and R. C. Cheek, A.I.E.E. Transactions, 1950.
A.Z.E.E. Transactions, Vol. 49, April 1930, p. $00. 24. Practical Calculation of Circuit Transient Recovery Voltages,
i. Definition of an Ideal Synchronous Machine and Formula for by J. A. Adams, W. F. Skeats, R. C. Van Sickle and T. G. A.
the Armature Flux Linkages, by R. H. Park, General Electric Sillers, A.Z.E.E. Transactions, Vol. 61, 1942, pp. 771-778.
Reoiew, June 1928, pp. 332-334. 25. Bus Transfer Tests on 2300-Volt Station Auxiliary System, by
8. Two-Reaction Theory of Synchronous Machines-I, by R. H. A. A. Johnson and H. A.- Thompson, presented before AIEE
Park, A.Z.E.E. Transactions, Vol. 48, No. 2, July 1929, p. 716. Winter Meeting, Jan. 1950.
CHAPTER 7

EXCITATION SYSTEMS
.4uthor:
J. E. Barkle, Jr.

RIOR to 1920 relatively little difficulty was en- on the bus. It usually had sufficient capacity to carry the

P countered in the operation of electrical systems, and


operating engineers had little concern about system
stability. As the loads grew and systems expanded, it be-
excitation requirements of the entire station for at least an
hour.
Motor or turbine drive was also used in the individual-
came necessary to operate synchronous machines in paral- exciter system, but it was not long before it was realized
lcl, and difficulties encountered were not well understood. that direct-connection of the exciter to the generator shnf t
111certain areas it became necessary to locate generating offered an excellent answer to the many problems encoun-
slations some distance from the load centers, which in- tered with separately-driven exciters and this system grew
volved the transmission of power over long distances. It rapidly in popularity. The standby excitation source \vas
soon became apparent that system stability was of vital usually a spare exciter, either motor- or turbine-driven,
importance in these cases and also in the operation of large and in case of trouble with the main exciter, transfer was
interconnected systems. accomplished manually.
In 1922, a group of engineers undertook solution of the Pilot exciters had not been used up to that time. The
.jtability problem to determine the factors involved that exciters were invariably self-excited. In the common-bus
most affected the ability of a system to transfer power from system without a floating battery, the bus was operated
one point to another. The results of these studies were at constant voltage supplied by compound-wound d-c gen-
presented before the AIEE in a group of papers* in 1924, erators. Thus, practically constant voltage was obtainecl
and it was pointed out that the synchronous machine ex- on the bus and control of the individual a-c generator field
citation systems are an important factor in the problem of voltage was accomplished by using a variable rheostat in
tlctermining the time variation of angle, voltage, and power each field as shown in Fig. I. When a standby battery was
quantities during transient disturbances. E. B. Shand
stressed the theoretical possibility of increasing the steady- EXCITER SHUNT FIELDS
state power that could be transmitted over transmission
lines through the use of a generator voltage regulator and
:tn excitation system with a high degree of response so that
operation in the region of dynamic stability would be pos-
sible. It was not recommended that this region of dynamic
stability be considered for normal operation, but. that it be
considered additional margin in determining permissible
power transfer.
Improvement of the excitation systems, therefore, ap-
peared to be at least one method of increasing the stability
limits of systems and preventing the separations occurring
(luring transient conditions. Greater interest in the design
of excitation systems and their component parts developed,
‘1
:md esciters with higher speeds of response and faster, 1
WKC accurate generator voltage regulators were soon
introduced to the industry.
Early excitation systems were of many different forms
IT1
JS
- sr
(lcpending principally upon whether the main generators
were small or large in rating and whether the installation
‘WS a steam or hydroelectric station. The two broad
classifications were those using a common excitation bus
and those using an individual exciter for each main gen-
erator. The common exciter bus was generally energized
l)Y several exciters driven by motors, turbines, steam en-
gines, waterwheels, or combinations of these to provide a
main and emergency drive. Standby exciter capacity was A-C GENERATOR
i
FIELDS
provided in the common-bus system by a battery floated Fig. l-Common-exciter-bus excitation system using flat-
*dJ.E.E. Transac&ns, Vol. 43, 1924, pp. 16-103. compounded exciters and a-c generator field rheostats.
195
196 Excitation Systems Chapter 7

floated on the common bus, however, the esciters were to be excited. This resistanceshall be determined at a tempers
shunt-wound to prevent polarity reversal by reversal of ture of:
the series-field current. The a-c generator-field rheostat (a) 75C for field windings designed to operate at rating with a
required in the common-bus system was a large and bulky tempernture rise of 60C or less
device, which had considerable loss and required a great (b) IOOC for field windings designed to operate at rating with a
deal of maintenance. Control of voltage was under hand- temperature rise greater than 6OC.
regulation. For rotating exciters the temperature of the exciter field winding
In the individual-exciter system, the exciter was a shunt- should be considered to be 7X.
wound machine with field control enabling it to opernt,e as Rated-Load Field Voltage-Rated-load field voltage is the volt,-
a variable-voltage source. The exciter usually operated at age required across the terminals of the field winding of an
voltages between 30 and 100 percent, lower field voltages electric machine under rated continuous load conditions with the
field winding at:
being obtained with a generator-field rheostat so that the
exciter could operate slightly saturated and be stable. (a) 75C for field windings designed to operate at rating with
The generator voltage regulators in use at that time were a temperature rise of 60C or less
(b) 1OOCfor field windings designed to operate at rating with
predominantly of the continuously-vibrating type. The
a temperature rise greater than 60C.
fact that these regulators were not suitable for use with
the new exciters with fast response and high ceiling voltages No-Loud Field Voltage-Xo-load field voltage is the voltage
prompted the development of new types of regulators.* required across the terminals of the field winding of an electric
machine under conditions of no load, rated speed and terminal
In the past 25 years, there have been many developments voltage, and with the field minding at 25C.
in escitation-syst,em design and practices. There is an
unceasing search among designers and users alike to find In the definitions of rated-load and no-load field voltaie,
ways of improving excitation-system performance through the terminals of the field winding are considered to be such
use of various types of d-c generators, electronic con- that the brush drop is included in the voltage in the case
verters, and better controlling devices. The ultimate aim of an a-c synchronous machine having slip rings.
is to achieve an ideal in rate of response, simplicity, reli- Excitation System Stability-Excitation system stability is the
ability, accuracy, sensitivity, etc. The achievement of all ability of the excitation system to control the field voltage of the
of these ideals simultaneously is a difficult problem. principal machine so that transient changes in the regulated
-1 review of the common excitation systems in use at the voltage are effectively suppressed and sustained oscillations in the
present time is presented in this chapter. The design and regulated voltage are not produced by the excitation system
characteristics of each of the component parts are dis- during steady-load conditions or following a change to a new
cussed, along with the methods of combining these parts steady-load condition.
bo form an escitation system having the most desirable Exciter Response--Exciter response is the rate of increase or
features. Methods of calculating and analyzing excitation decrease of the exciter voltage when a change in this voltage is
system performance are also included. demanded.
Main-Exciter Response Rati-The main-exciter response ratio
is the numerical value obtained when the response, in volts per
I. DEFINITIONS second, is divided by the rated-load field voltage; which response,
if maintained constant, would develop, in one-half second, the
In discussing excitation systems, a number of terms are same .e%itation voltage.-time area as attained by the actual ex-
used, the meaning of which may not be entirely clear. The citer. The response is determined with no load on the exciter,
following definitions are proposed for inclusion in the new with the exciter voltage initially equal to the rated-load field
edition of the American Standards Association, Publication voltage, and then suddenly establishing circuit conditions which
C42, “Definitions of Electrical Terms”. would be used to obtain nominal exciter ceiling voltage.
Kzcitation System-An excitation system is the source of field Note: For a rotating exciter, response should be determined
current for the excitation of a principal electric machine, includ- at rated speed. This definition does not apply to main exciters
ing meansfor its control. having one or more series fields or to electronic exciters.
hn excitation system, therefore, includes all of the equip- In using the per-unit system of designating esciter volt-
ment required to supply field current to excite a principal ages, several choices are available from which to choose
electric machine, which may be an a-c or d-c machine, and the unit.
any equipment provided to regulate or control the amount First, the rated voltage of the exciter would appear to be
of field current delivered. the fundamental basis, but for system analysis it has very
Exciter Ceiling Voltage-Exciter ceiling voltage is the max- little utility.
imum voltage that may be attained by an exciter with specified Second, for specification purposes it has become‘standard
conditions of load. For rotating exciters ceiling should be de- through the adoption by the AIEE and ASA to use the ’
termined at rated speed and specified field temperature. rated-load field voltage as unity. It should be noted that ;
Nominal Exciter CeiZeiling Voltage-Nominal exciter ceiling rated-load field voltage is the voltage formerly referred to
voltage is the ceiling voltage of an exciter loaded with a resistor as “nominal slip-ring” or “nominal collector-ring” voltage.
having an ohmic value equal to the resistance of the field winding Third, the exciter voltage necessary to circulate the field
*A symposium of papers on excitation systems was presented current required to produce rated voltage on the air-gap i
before the AIEE in 1920 and gives details of equipment and practices line of the main machine. For analytical purposes this is j
in use at that time. See AIEE Transactions, Vol. 39, Part II, 1920, the one most generally used and is the one used in the 1
pp. 1551-1637. analytical work in Chap. 6. Under steady-state conditions, 1
Chapter 7 Excitation Systems 197

no saturation, and using this definition, exciter voltage, voltage-time curve of the exciter as determined under the
f&l current and synchronous internal voltage become specified conditions. Reginning at the rated-load field volt-
eqUd . age, point a, the straight line UCis drawn so that the area
Fourth, the slip-ring voltage necessary to produce rated under it, abc, during the one-half second interval from zero
voltage at no load or no-load field voltage is sometimes, but time is equal to the area under the actual voltage-time
rather infrequently used. This definition includes the small curve, abde, during the same interval. The response used
amount of saturation present within the machine at no load. in determining response ratio is the slope of the line UCin
Exciters for turbine generators of less than 10 000 kilo- volts per second;
wtts capacity are rated at 125 volts, and t.hose for larger 100 volts
(Inits arc generally rated 250 volts. Some of the large units = 200 volts per second.
placed in service recently have exciters rated 375 volts. 0.5 second
The vast majority of exciters in use with all types of syn- The rated-load field voltage is 200 volts, and the response
chronous machines greater than 10 000 kilowatts in capac- ratio, obtained by dividing the response by the rated-load
ity are rated 250 volts. On this rating the rated-load field field voltage, is 1.0. The work can also be done by express-
voltage is of the order of 200 volts or 80 percent of the ing the voltages as per-unit values.
exciter rating. The exciter voltage required to produce the The half-second interval is chosen because it corresponds
field current in the main machine corresponding to rated approximately to one-half period of the natural clcctro-
voltage on the air-gap line is usually about 90 volts or mechanical oscillation of the average power system. It is
:3(i percent of the exciter rating. Using this value as 1.0 the time during which the exciter must become active if
l,er unit exciter voltage, the rated-load field voltage is it is to be effective in assisting to maintain system stability.
approximately 2.2 per unit.
The nominal exciter ceiling voltage is defined above and
II. MAIN EXCITERS
can be interpreted as being the maximum voltage the ex-
citer attains with all of the field-circuit resistance under The main exciter is a source of field current for the
control of the voltage regulator short circuited. On a 250- principal electric machine. Thus, any d-c machine that
volt escitcr, the ceiling voltage is usually about 300 to 330 might be used to serve this purpose can be called a main
volts, which is 120 to 132 percent of the exciter rated exciter. Seldom are storage batteries used as main esciters.
voltage, or 3.3 to 3.7 per unit. The relative values of these With a main generator of any appreciable size, the diffi-
ctlutntities are shown graphically in Fig. 2. culties encountered in finding room for the battery, in
The construction of the response line in accordance with maintaining the charge, and in keeping the battery in good
the definition for determining main-exciter response ratio operating condition are such as to make it impractical.
is also included in Fig. 2. The curve aed is the actual Many other types of d-c machines have been developed

I I I I
RATED-LOAD FIELD VOLTAGE
I Ibl I I I I I I

TIME IN SECONDS

Fig. 2-Construction for determining main-exciter response ratio showing relative values of important quantities for 250-
volt main exciter.
198 Excitation Systems Chapter ‘7

to a high degree of specialization for use as main exciters and an emergency supply, and automatic quick-transfer
that offer many operating and maintenance advantages to the emergency supply is provided in case of failure of
over a battery. the normal supply. In some cases, dual prime movers are
Main exciters, in general, can be grouped into two classi- used such as a motor and a steam turbine, the turbine
fications; i.e., rotating and non-rotating d-c machines. The taking over the drive when the motor power supply fails.
most common form of rotating main exciter is the more or The driving motor can be connected directly to the main
less conventional d-c generator. The term “conventional” generator terminals through an appropriate transformer.
is used with reservation since a d-c generator built for the It is then subject to voltage disturbances on the main
purpose of supplying excitation for a synchronous machine system.
has incorporated in it many features to improve reliability The motor is apt to be subjected to voltage disturbances
and reduce maintenance not found on d-c generators used regardless of the source of its power supply, and it is nec-
for other purposes. Aside from these special features, the essary to construct the m-g set so that it can withstand
theory of operation is the same as the conventional d-c these disturbances without affecting the excitation of the
generator. A new form of rotating exciter that has made main a-c generator. The inertia constant of the m-g set
its appearance in recent years is the main-exciter Rototrol. and the pull-out torque of the motor must be high enough
The Rototrol or rotating amplifier is very different in its to assure that the speed of the set does not change appre- 4
operation from the conventional main exciter. The major ciably or the motor stall during momentary voltage dips.
static or non-rotating form of main exciter is the electronic The response ratio and ceiling voltage of the exciter must
exciter. take into consideration any speed change that may occur.
Each of these d-c machines, in regard to its application In arriving at values for these various factors, it is neces-,
as a main exciter, is discussed in detail in the sections sary that some time interval and voltage condition for the
that follow. system disturbance be chosen. A common requirement is
that the exciter m-g set be capable of delivering maximum
1. Prime Movers for Main Exciters forcing excitation to the generator field during a sy&em
Rotating main exciters are of either the direct-connected disturbance when the motor voltage is 70 percent of normal
type or the separately-driven type. A direct-connected for a period of one-half second. Based on this criterion,
main exciter is one coupled directly to the shaft of the main characteristics of the exciter m-g set have become fairly
generator and rotates at the same speed. A modification well standardized as follows:
is the geared or shaft-driven exciter, driven through a gear Inertia constant of the entire m-g set, H = 5.0.
by the shaft of the main generator. Problems of gear main- Pull-out torque of driving motor, P,,, = 500 percent.
tenance are introduced, but this enables the two machines Response ratio of main exciter &en operating at rated
to operate at different speeds. A separately-driven main speed, R = 2.0.
exciter is usually driven by a motor, the complete unit Nominal exciter ceiling voltage when operating at rated
being called an exciter m-g set, or it can be driven by some
speed, E,,, = 160 percent.
other form of prime mover such as a steam turbine or a
hydraulic turbine. When an exciter m-g set is used with a synchronous
Loss of excitation of an a-c generator generally means condenser, the logical source of power for the motor is the
that it must be removed from service. Hence a reliable system that energizes the condenser. In this respect, the
source of excitation is essential. If the main exciter should use of exciter m-g sets with synchronous condensers does
stop running while the main generator is still capable of not involve many complications.
operating, blame for the resultant outage would be placed Direct-Connected Exciter-The most reliable prime
on the main exciter. Considerable expense, therefore, can mover for the main exciter is the same prime mover that
be justified to provide a reliable source of power to drive, drives the a-c machine being excited. This was realized
the main exciter. The type of drive accepted as reliable many years ago when main exciters were first coupled to
depends upon the type of synchronous machine being ex- the shafts of the generators. The reliability of this form of
cited; that is, whether it be a generator or a synchronous drive is obvious and no elaboration is necessary. However,
condenser. in the case of high-speed turbine generators, early installa-
Exciter M-G Set-The exciter m-g set can be driven tions experienced trouble in operation of the d-c exciters at
by a synchronous or induction motor. Direct-current mo- high speeds. These difficulties have been completely over-
tors have been used in some cases. The synchronous motor come by adequate design of the exciter, special features
drive is undesirable, because of the possibility of transient being included for operation at 3600 rpm. Direct connec-
disturbances on the motor supply system causing insta- tion of the main exciter is widely accepted in the utility
bility. Induction motors are ordinarily applied where the industry.
exciter m-g set is used. In any event, the motor must be
specially designed to drive the main exciter through any 2. Conventional Main Exciters i
form of system disturbance. Conventional main exciters, in general, can be classified
Power supply for the motor is, of course, important. The according to their method of excitation, being either self-
exciter m-g set might be classed as an essential auxiliary excited or separately-excited. In the former the field wind-
for operation of the generator, and may receive its power ing or windings are connected across the terminals cf the
from the auxiliary power-supply system. Most essential machine through variable resistors and in the latter the
auxiliaries have a dual power supply comprising a normal field windings with their resistors are connected to a source
Chapter 7 Excitation Systems

EXCITER
TERMINALS

EXCITER
SHUNT FIELD
RHEOSTAT
(01

EXCITER
SHUNT FIELD
RHEOSTAT
- I

CONSTANT EXCITER
VOLTAGE TERMINALS
SOURCE

0 I I 0
CURRENT PER FIELD CIRCUIT=if
tb)
Fig. I-Steady-state operating points for unloaded and loaded
Fig. ~-TWO common forms of shunt-excited main exciters. self-excited and separately-excited machines.
(a) self-excited.
(b) separately-excited. particular constant-resistance load for which the line odD
represents the saturation characteristic, the operating point
of essentially constant voltage such as a small auxiliary is likewise the intersection with OA, namely b. If some
fl:lt-compounded exciter, called a pilot exciter. The basic resistance is inserted in the field circuit so that its resist-
connections of these two forms of main esciter are shown ance line is changed to OB, then the operating point is c for
in Figs. 3(a) and (b). the no-load condition and d for the constant-resistance load
The curve oca in Fig. 4 represents the no-load saturation condition. In this manner of changing the exciter field
curve of a conventional d-c generator that might be used resistance, any exciter voltage within limits can be ob-
as a main exciter. An examination of the curve reveals that tained.
for values of voltage less than approximately 7.5percent of Should the field resistance be increased so that the resist-
rated armature voltage substantially all of the field current ance line coincides with the air-gap line, the output voltage
is expended in forcing magnetic flux across the air gap of theoretically can establish itself at any value between zero
the machine. In this region the voltage output is directly and the point where the no-load saturation curve begins to
proportional to the field current, and a line drawn coincid- bend away from the air-gap line. Operation in this region
ing with the straight portion of the curve is called the air- is unstable unless some artificial means of stabilizing is
flap line. Above the straight-line portion of the curve, the provided.
voltage output is no longer proportional to the field cur- On the other hand, if the machine were separately-
rent, and a given percentage increase in voltage output excited by a pilot exciter, the field current is determined
requires a greater percentage increase in the field current. by the intersection of the resistance line with the pilot-
lYndcr this condition, the machine is saturated and a exciter voltage line. Thus in Fig. 4, for the resistance line
grcatcr proportion of the field ampere-turns are used in OA and the constant pilot-exciter voltage e,, the field cur-
forcing flux through the magnetic circuit. rent of the exciter is determined by the intersection at f,
The field windings of the main exciter are frequently and the terminal voltages for no-load and constant-resist-
divided into two or more parallel circuits and in the present ance load are at points g and h, respectively.
discussion the field current is always referred to as the
current in one of the parallel circuits. For either the self- 3. Calculation of Response of Conventional Main
or separately-excited exciter, the terminal voltage is varied Exciters
1)~simply changing the resistance of the field circuit. The
field resistance line OA in Fig. 4 is drawn so that its slope It will be observed that the definition of exciter response
is equal to the resistance of the field, that is, the ordinate is based upon the no-load voltage build-up curve. This
at any point divided by the field current is the total resist- may differ in several essential points from the load condi-
ance of one circuit of the field winding. At,no-load, the tion which will be discussed later. For the present, the
intersection of the no-load saturation curve with the line response will be calculated for the no-load condition and
0‘4 determines the operating point, namely a. For the mill be applied to a self-excited machine.
200 Excitation Systems Chapter 7

If
e, = terminal voltage of the exciter and also the voltage
across its field circuit
ir=ficld current per circuit in amperes
TY= total resistance of each field circuit in ohms
$=flux linkages per circuit of the field winding in
1OW lines-turns
‘SATURATION CURVE) kuex
then there exists for the field circuits the following equa-
tion:
CEILING VOLTAGE , /

where each term is expressed in volts. This expression can


be rewritten in the following form
drC/ .
(2)
dt=ex-rfZf
FORCING VOLTAGE, e = e, -f-f if
The flux linkages, $, can be regarded as made up of two ON SELF-EXCITED MACHINE
components; first, those produced by the useful flux in the
air gap and, second, those produced by the leakage fluses. FORCING VOLTAGE FOR SEPARATELY- \
EXCITED EXCITER = e, -rf if
The first component is proportional to the no-load terminal
voltage as this is the flux which produces that voltage. The
designer can give the useful flux at any particular voltage
or it can be obtained from the design constants of the
machine. Multip!ying this flux in 10e8 lines by the turns,
N, linked by the flux, which is equal to the number of
turns per pole times the number of poles per circuit, gives
if
the total linkages due to this component. These linkages
may be designated as k,e,, where, to be specific with respect Fig. J-Forcing voltages and flux linkages concerned in cal-
to the particular voltage concerned, we may write culating response.

total useful flux linkages number of poles


per pole at rated voltage )C per circuit Equation (2) states that the time rate of rise of $ is pro-
k,= ( ) portional at any instant to a forcing voltage which is equal
(3)
rated voltage to the vertical distance between the terminal-voltage curve
The leakage component is more complex as not all of the and the straight-line curve of resistance drop at any given
leakage flux cuts all of the turns. If there mere no satura- field current. It shows that the flux within the machine
tion effects in the pole pieces and yoke, the leakage fluses will increase so long as (e,--r&f) is positive, that is, until
would be proportional to the field current. If, however, the point of intersection of the two curves, as shown in
the leakage fluxes are specified at some definite current Fig. 5, is attained. Beyond this point (e,-r&r) be-
such as that required to produce rated voltage at no load, comes negative. If, for any reason, the flux within the
then the leakage at higher currents will be less than pro- machine extends beyond this point, it will decrease.
portional to the current and at lower currents will be more
than proportional to that at the specified point. Inasmuch
as the leakage flux is only about 10 percent of the useful
flux, considerable error is permissible in the leakage com-
ponent without affecting the result significantly. The
leakage flux may be said to contribute the flux linkages
k&f to the total. The coefficient kl can be defined by re-
questing from the designer both the flux linkages per pole
at rated voltage due to the useful flux and the total flux
linkages per pole at rated voltage. The coefficient kl is
then
Total #
per pole at - +toper pole flus
useful d”:)(~gT.f.t) (~)
( rated voltage at rated voltage
k,=
if at rated voltage
The total flux linkages per circuit are then
$=k,e,+klif (5)
Fig. 6-Graphical determination of response of flux linkages
These quantities are illustrated in Fig. 5. IJ with time.
Chapter 7 Excitation Systems 201

In other words, the in&section is a stable operating as a function of time by taking corresponding points from
point. Fig. 5. The simplest method for obtaining the area is to
Equation (2) can be transformed to divide the region into a large number of increments and
then sum them progressively on a recording adding
dt=L
e,-rrir machine.
from which If the machine is separately cscited, the variable ter-
ff /-* minal voltage P, in the expression for the forcing voltage
should be replaced by the voltage e, of the pilot exciter
and the forcing voltage then becomes (e,-rrif), which is
illustrated in Fig. 5. The difference in these forcing volt-
uy choosing particular values of ir from Fig. 5, it is pos- ages shows why separately-excited exciters are usually
faster in response.
siblC to plot # as a function of __ or g shown in Fig. When systematized, it is found that this calculation is
e,-rrtic
^ . . d4 ~,
6. From Eq. (7) it can be seen that t can be obtained as quite simple, as will be illustrated by an esample. Let it he
a function of 9 by simply obtaining the area of the vertical desired to determine the exciter response for the separately-
strata of increments, starting from 1c,corresponding to the excited machine mhose characteristics are given in Fig. 7.
starting value of e,. After 1c,is obtained, e, can be plotted In Table 1, columns (I) and (2), tabulate the terminal
voltage and field currents from Fig. 7. Columns (3) and
(4) are simply steps in the determination of the total # of
160 column (5). Columns (6) and (7) are likelvise steps in the
I50 determination of 2 of column (8). From this point a

140
choice may be made of two procedures. If the graphical

130
method is used, plot the value of g from column (8) as

120
ordinate against the value of # from column (5) as abscissa

0.0107 O.OlO7
0.0 I37 0.0244
0.0 I43 0.0367
0.0 I45 0.0532
0.0 I50 0.0682
0.0 I 55 0.0031
0.0 I60 0.0997
0.01 65 0.1 I62
0.0 I72
0.0177
0.0 I66
0.1 334
0.151 I
0.1697
/I
0.0 I 96 0.1 093
0.0200 0.2 I 0 I
.0223 0.2324
242 0.2566

0
0 2 4 6 0
FIELD CURRENT PER CIRCUIT
Fig. 7-Example for calculation of response of exciter.
167 kw, 125 volts, 1200 rpm, 6 poles
Separatelyexcited--e. = 125volts
Three circuits-two polesper circuit
Ceiling voltage-165 volts.
if nt ceiling voltage=8.16 amperesper circuit
Resistanceper circuit = 15.3ohms
Two field windings=0.8 ohms
External resistanceper circuit =8.5 ohms
Total external resistance=2.8 ohms
# per pole nt 125volts due to useful flux = 18
Total + per pole at 125 volts =20.3
k, = (20.3 - 18)2 = 1 05 Fig. S-Auxiliary curves for calculation of response for exam-
4.4 . ple given in Fig. 7.
202 Excitation Systems Chapter 7

TABLE 1
- -
(4) (‘3 (7) (8)

klif e.-rfif -=- 1 dt


- --
es-riif 4

0.288X(1
--
) 1.05X(2 ;- __-
(3) + (4) 15 3x(2) 125-C(6) rec. of (7) from (5) from (8) (9) x (10) .x(11)-
100 3.30 28.8 3.5 32.3 50.5 74.5 0.0134 0
110 3.70 31.7 3.9 35.6 56.6 68.4 0.0146 3:3 0.014 0:;;& 0.0462
120 4.14 34.5 4.3 38.8 63.4 61.6 0.0162 3.2 0.01.5-L 0.0403 0.0955
130 4.66 37.5 4.0 42.4 71.3 53.7 0.0186 3.6 0.0174 0.0626 0.1581
140 5.34 40.3 5.6 45.0 81.7 43.3 0.0231 3.5 0.0208 0.0728 0.2309
1.50 6.26 43.2 6.6 49.8 05.8 29.2 0.0342 3.9 0.0287 0.112 0.343
155 6.80 44.6 7.1 51.7 104.0 21.0 0.0476 1.9 0.0409 0.078 0.421
160 7.46 46.1 7.8 53.9 114.0 11.0 0.091 2.2 0.0603 0.152 0.573
-
A
giving the curve shown in Fig. 8. Time can then be de- excited exciters or the ceiling voltage in the case of self-
termined by integrating this curve. One method of doing excited exciters. The former is usually accomplished by
this is by means of the table constituting the insert of this paralleling the field circuits placing at the same time re-
figure. This is found by dividing $J into increments of sistors in series to limit the current. Thus, if the parallela
unit width, except for the first element for which A# is are doubled, the number of poles and likewise $ per circuit ’
only 0.8. This is done to obtain convenient divisions. are halved. It is necessary to add more resistance to the
Increments of time At are enumerated in the first column. external circuit so that the resistance per circuit remains
The second column represents time, the summation of the the same. In Eq. (7) the only change is that 1c,is one-
At column. On the other hand, the same integration can be half and, therefore, the terminal voltage rises twice as
accomplished in tabular form. Continuing in Table 1, fast.
column (9), the difference of successive values of 1c/from
column (5), constitutes the base of increments of area of 4. Calculation of Response Under Loaded Con-
ditions
curve $ in Fig. 8. Likewise, column (lo), the mean of
Most of the cases for which the exciter response is desired
successive values of column (8), constitutes the mean of are concerned with sudden changes, such as short circuits,
elementary areas. The product of these two values tabu- in the armature circuit of the synchronous machine. Asso-
lated in column (11) is the increment of time. Column ciated with these changes one usually finds that the field i
(12) is merely a progressive summation of (11) and gives current of the alternator has increased a considerable ;
actual time. By plotting column (1) against column (12), amount, perhaps in excess of the armature current rating
the response curve is obtained. of the exciter. Because of the high inductance of the field
For higher speeds of response, the eddy currents pro- circuit of the synchronous machine, the armature current
duced in the solid yokes can retard the buildup of the flux. of the exciter can usually be regarded as remaining sub-
The extent to which this is effective is given by the curve stantially constant at this increased value during fhe period
for which the response is desired.
(r When current flows in the armature, the phenomenon of
armature reaction must be taken into consideration except
for those machines that have a compensating winding. The
function of the compensating winding, which is wound into
the pole face of the field winding, is to annul the effect of
the cross-magnetizing mmf of armature reaction. However,
for machines without compensating windings, the mmf of
0
CALCULATED NOMINAL RESPONSE-UNITS armature reaction produces an mmf that varies linearly
Fig. 9-Correction factor to be applied to calculated response from the center of the pole piece, one side being positive
to include effect of eddy currents, according to W. A. Lewis.’ and the other side negative. This effect is shown in Fig.
10 (a) in which MN represents the maximum magnetizing
in Fig. 9 by W. A. Lewis’. This curve supplies a correction mmf at one pole edge and PQ represents the maximum
to be applied to calculated responses. demagnetizing mmf at the other pole edge. Fig. 10 (b)
Separately-excited exciters are usually, but not neces- represents a section of the no-load saturation curve in
sarily, faster in response than self-excited exciters. They whic’h 0 represents the generated voltage on the vertical
do, however, have other advantages, such as being more co-ordinate and the field mmf on the horizontal co-ordinate.
stable at low voltages, voltages at which self-excited ex- If A and C are so laid off that OA and OC equal MN and
citers may have a tendency to creep. Improvement in PQ, respectively, from Fig. 10 (a), then because of the
speed of response can be obtained by two general methods; linearity of QN of Fig. 10 (a), the abscissa of Fig. 10 (b)
(1) decreasing the time constant of the field circuit, and (2) between CA represents the mmf distribution along the pole
increasing the pilot-exciter voltage in the caseof separately- face. Further, since the generated voltages are propor-
Chapter 7’ ‘1x,. .. Excitation Systems 203

NO LOAD /
SATURATION CURVE

FOR CONSTANT
ARMATURE CURRENT

TERMINAL VOLTAGE FOR


CURRENT

(a) I RESISTANCE LINE

ii
SECTION TAKEN Fig. 11-Load saturationcurves for exciter assuming constant
armature current.

machine is very much smaller under load than under no


load. In calculating the flux linkages in accordance with
Eq. (5), the distortion curve should be used fore,. Except
for these two changes, the load response can be calculated
in the same manner as the no load response.
For separately-excited exciters, the forcing voltage re-
mains unaltered by the loading on the machine as it is
independent of the terminal voltage. The armature resist-
REACTION AT EDGE OF ance can be regarded as part of that of the main field wind-
POLE. [MN FROM (O)] ing. There remains only the distortion effect to consider
which amounts to only several percent. For machines with
compensating windings, this effect is negligible.

Fig. lo--Effect of armature reaction in reducing total flux


5. Effect of Differential Fields on Response
across gap. (a) Shows distribution of armature mmf; (b) Sec- Differential windings are provided to reduce the exciter
tion of no-load saturation curve. voltage to residual magnitude or below. They consist of a
small number of turns wound on each pole, so connected
tional to the air-gap fluxes, the section of no-load satura- that the mmf produced thereby is opposite to that of the
tion curve shows the effect of the superposed armature main windings. Fig. 12 (a) shows schematically such an
mmf upon the density of air-gap flux across the pole. The arrangement. If the differential windings are not opened
higher mmf does not increase the flux on the right-hand when the regulator contacts close to produce field forcing,
side as much as the lower mmf decreases the flux on the the differential circuit reduces the response of the exciter.
left-hand side. As a result, the total flux and consequently The extent to which this is effective may be calculated
the generated voltage are decreased from the value indicated as follows: Let
1)~ CA to that indicated by FG, which is obtained by
integrating the area under the curve DOB and drawing FG a=number of parallel paths in the main winding.
so that the two triangular areas are equal. The extent to b = number of parallel paths in the differential winding.
which the average flux or voltage is decreased can be in- c=number of turns per pole of the main winding.
dicated by a “distortion curve,” such as shown by the d = number of turns per pole of the differential winding.
dotted curve of Fig. 11. This effect is most pronounced in N = total number of poles of exciter.
the region of the knee of the saturation curve as at both
i, = current per circuit of main winding.
higher and lower field currents, there is a tendency to add
on the one side of the pole just as much flux as is subtracted id = current per circuit of differential winding.
on the other. The terminal voltage is reduced still further The resistors R, and Rd in series with the combined main
l)Y the armature resistance and brush drops, resulting in a and differential windings, respectively, may be included in
load saturation curve for constant current, such as shown the calculation by increasing the actual resistances in each
in Fig. 11. of the main and differential circuits by aR, and bRd, re-
From this same curve it can be seen that for a given field spectively. With these increases the resistances of each of
resistance line, the forcing voltage (~-r&r) for a self-excited the main and differential circuits will be designated by the
204 Excitation Systems Chapter 7

If (10) and (11) are inserted in (8) and (9), then


MAIN WINDINGS
ex=(Ra+r.,)(i+~id)+Rbid+d~ (12)

e, = Ra(i+$) + (Rb+r&+$ $ (13)

ex ~~ multiplying (13) by 2, $f can be eliminated by


subtracting from (12). The current id can then be solved
in terms of i. Upon substituting the expression for id
1 into (12) there is finally obtained that
. DIFFERENTIAL WINDINGS

(a)
l-r4 !i l+R ;+”
c rd ( rd> I- i+g (14)
-e, =
A d m clt
in which .A.
4=1-g j--rm+f$-a)!?] (15)
Iim
Equation 14 shows that the ordinary flux-linkage curye
for the exciter and conventional method of calculation can ’
beusedif the coefficient of i be used as the resistance of each
circuit, i be the current read from the saturation curve, and
the voltage across each circuit be multiplied by the co-
1id efficient of e,. In other words, the calculations should be
carried out as though the differential winding were not
present, except that instead of using the expression
lb) (e,-r&r) todetermine the forcing voltage, e, should be mul-
Fig. 12---Schematic diagram for main and differential
windings. tiplied by (l--2)/ A, and rr by [ I+R(;+$)]/A.

symbols r, an d rd, respectively. Referring to Fig. 12 (b) 6. Three-Field Main Exciter


the following equations can be written The three-field main exciter shown schematically in Fig.
eI =R(ai+bid)+r i +g 13 is of conventional construction so far as mechanical
63) details and armature winding are concerned, but it is built
lnrn dt
with three electrically independent shunt fields. Field 1
G=R(ai mfbi d )+r i +a co is connected in series with a variable resistance across the
dd dt
in which $ and $d are the flux linkages in each of the MAIN
two respective circuits. EXCITER
If all the field flux cuts all turns, then

J/=$X (flux per pole in lo-* lines)


REVERSIBLE
VARIABLE
$d = $JX (flux per pole in lo-* lines) VOLTAGE

or
(10)
STABILIZING SELF-EXCITED
If it be assumed that the two windings be replaced by FIELD RHEO ‘I
another winding having the same number of turns and ,i
circuit connections as the main windings, then the in-
stantaneous mmf of this winding is the same as that of
LOW-ENERGY
the combination if its current, i, is D-C SOURCE
MECHANICAL
INTERLOCK #
. . d. BETWEEN :a
‘&=a,---ad 2.:
c RHEO ARMS (”
from which Fig. 13-Schematic diagram of three-field main exciter. Field8
1 is self-excited and provides base excitation, field 2 is a1
&Cifdid *(ll) separately-excited controlling field, and field 3 is a small
C capacity battery-excited stabilizing field.
chapter 7 Excitation Systems

main terminals of the exciter and operates in the manner


of the self-excited field discussed in See. 1. Field 1 provides
the base excitation for the machine. Field 3 is a small
separately-excited shunt field that obtains its energy from
a station battery or any other source of substantially
constant d-c voltage. It is capable of supplying 5 to 10
percent of the normal total excitation requirements of the
main exciter, and its purpose is to provide exciter stability
at low voltage output under hand control. Field 3 is used
only when the esciter speed of response or range of voltage
output makes it desirable. Field 2 is a shunt field that is
excited from a reversible variable-voltage d-c source under
control of a voltage regulator. This field also provides for
stability of the exciter when the voltage regulation is under
control of the voltage regulator.
Fields 1 and 3 have rheostats in their energizing cir-
cuits. These are usually motor-operated under manual
control. The rheostat arms are mechanically connected
together so that resistance is added in one field circuit as
it, is removed from the other. Thus, when the self-energized ” ~-*
1 d
shunt field is carrying a high excitation current, the sepa- CURRENT IN SELF-EXCITED FIELD
ratcly-excited field 3 carries a negligible current. The Fig. 14-Equivalent no-load saturation curve of three-field
combined effect of fields 1 and 3 is shown in Fig. 14 and main exciter showing effect of stabilizing field 3. Field 2 is
can be esplained by assuming that the current in field 2 is open-circuited.
zero. When the field rheostat is adjusted to give a voltage
output greater than that represented by the distance Oc, in the opposite direction. Thus, manual control of voltage
A]] cscitation is supplied by field 1, and the relation between is possible over the complete range necessary.
tlic exciter terminal voltage and the total field ampere- When the voltage of the main esciter is under the control
turns is represented by the line ab. Operation in this region of a voltage regulator that varies the magnitude and polar-
is the same as a self-excited exciter. If the resistance in the ity of voltage applied to the separately-excited field 2.
circuit of field 1 were increased to give a value of ampere- the manually-operated field rheostat in field 1 circuit is set
turns less than Od in Fig. 14, and if field 1 were the only to provide some base amount of excitation. This setting
field excited, the machine would be unstable as pointed is determined by the operator, but is generally high enough
out in Sec. 1. to supply sufficient field current to the a-c generator field
To obtain a terminal voltage less than Oc, such as Of, to mainta,in steady-state stability. The current in field 3
the resistance in the self-excited field circuit would be in- is usually negligible with such asetting of the rheostat when
creased to reduce the ampere-turns produced by that field the generatoris carrying any load. The polarity and magni-
to Oj. These ampere-turns would cause a generated volt- tude of the voltage applied to field 2 are then regulated so
age eclual to Oh. However, at the same time the current that the flux produced by field 2 either aids or opposes the
in field 1 is reduced, the current in field 3 is increased, flux produced by the base excitation in field 1, thus, either
and the generated voltage due to field 3 being energized increasing or decreasing the exciter terminal voltage. Since
is rrprescnted by hJ The ampere-turns of the two fields the effect of field 1 is that of a conventional self-excited
:tntl the generated voltages add so that the distance Of is machine, a small amount of energy input to field 2 can
t,lic total terminal voltage. Since the current in field 3 is control the output voltage over a wide range. The opera-
controlled by the amount of current in field 1 through the tion of the three-field main exciter is made stable by sepa-
mechanical coupling of the field-rheostat arms, the total rate means for the two conditions of operation: by a
tciminnl voltage can be plotted as a function of the ampere- separately-excited stabilizing field under manual control,
turns in field 1 alone and is represented by the curve ebb and by the voltage regulator controlling the input to field
in Fig. 14. If the field-resistance characteristic of the self- 2 under regulator control.
excited field is plotted on the same curve, there will always The three-field main exciter has an advantage over the
he a positive point of intersection between the resistance single-field separately-excited main exciter described in
line and the saturation curve ekab and stable operation can Sec. 1 in that control of the exciter terminal voltage is
he obtained for any voltage greater than Oe. The voltage not completely lost if any trouble should occur in the
Wrcsented by Oe is usually less than 10 percent of the separately-excited field circuit. The trouble might involve
raxi voltage of the esciter. Operation at smaller values the variable-voltage source for field 2 or the voltage regu-
\vould not ordinarily be necessary except in the case of a lator that controls it, but even though the current in the
synchronous-condenser csciter. Smaller terminal voltages field should become zero, the exciter will continue operating
are obtained by holding the current in the self-excited field at a terminal voltage determined by the setting of the
to zero and reducing the current in separately-excited field rheostat in the self-energized field circuit. The only effect
3. Excit,er polarity can be reversed by reversing both on the a-c generator would be a change in its internal
field circuits when the currents are zero and building up voltage which would cause a change in reactive loading of

,
L
206 Excitation Systems Chapter 7

the machine. Under similar circumstances of failure Fith terminal voltage, the total useful flux at any later instant
the single-field esciter, the source of excitation for the a-c of time is
gencrntor field would be lost and a shut-dolvn of the unit 4’ = K(Nlil’ +:V&’ + N&‘). (17)
would be necessary.
The change in total flux per pole is the difference between
7. Calculation of Response of Three-Field Main these two values,
Exciter 4 = qS- $0 = K(Nlil+ N&+N&). (18)
X method of calculating the response of a single-field
The basic formula for the self-inductance of any of the
esciter is given in Sec. 2. The method uses step-by-step field circuits is
integration to take into account the saturated condition
L=Ndlo-8
of the exciter. If additional fields are present, damping ----henrys,
currents flow in those fields during voltage changes. Their i
effect is to reduce the rate of change of flux in the exciter and since the flux is expressed as Maswells per pole times
iron paths. The following analysis presents a means of 108, the self-inductance of the circuit of field 1 becomes
replacing the assembly of several fields with one equivalent
L 1 = p4N1x - pI(N 2X.
field so that the response can be calculated. -- 1 (19) *
il
The specific fields involved in the three-field main exciter
are the self-excited field 1, the battery-excited field 3, and The time constant of the field circuit is the total self-
the separately-excited field 2 as shown in Fig. 13. The inductance divided by the tot’al resistance,
three fields are wound to form a single element to be
mounted on the field pole, so that the mutual coupling is t _ LI _ PKN12X
Gw
high and can be assumed to be 100 percent with small ’ RI 7’
error. Also, the same leakage coefficient can be applied to Equations similar to Eq. (19) can be written for self-in-
each of the fields. In the following symbols the subscript ductances Lz and L, and similar to Eq. (20) for time con-
indicates the particular field to which the symbol applies. stants t2 and t8.
Thus, N1 is the turns per pole of field 1, Nz the turns per The voltage applied to each of the field circuits is
pole of jield 2, etc. &J
absorbed in Ri drop in the circuit resistance and -VTz drop
P = Number of poles, assumed to be connected in series.
N = Number of turns per pole in the field winding. in the circuit inductance. The voltage equations at any
$J’=Total useful flux per pole in Maxwells times 108. instant of time are
& = Initial useful flux per pole in Maxwells times 108. E,’ = c$’ = Rlil’+N1XPp4’ (21)
4 = Change in flux per pole = 4’ -do. Eat= R2i2’+ N,XPpqS (22)
i’ = Total amperes in field circuit.
i,,=Initial amperes in field circuit. EBI= R&s’+ NJPp$‘. (23)
i = Change in amperes in field winding = i’-iO. During the initial steady-state conditions, when the total
L = Inductance of field winding in Henrys. useful flux is constant and p&=0,
K = Flux proportionality constant CO= c+~= Rho+ NJPpdu (24)
Maxwells X lo8 per pole
E,o = R&o+ N,XPp&, (25)
= Ampere turns per pole
leakage flux GO = R&o+ NMPAT (26)
X = Flux leakage factor = 1 +
useful flux Subtracting the two sets of voltage equations, a set in
c = Voltage proportionality constant terms of changes from steady-state conditions is obtained.
terminal volts Since the voltage E,’ is supplied from a constant-potential
=Maxwells X lo8 per pole source, Ei - EaO = 0.
R = Resistance of the complete field circuit, ohms. cc+= Rli, + N,XPp+ (27)
t = Time constant of complete field circuit, seconds. E, = R2i2+NJPp+ (2%
E,’ =Terminal voltage applied to field 1.
0 = R3i3f N&Ppb (29
Et0 = Initial value of terminal voltage.
Et = Change in terminal voltage = E; - E,,. KN, KNz
If Eqs. [27), (28), and (29) are multiplied by -
Ez’ =Voltage applied to field 2. RI ’ ??
,?&=Initial value of voltage applied to field 2.
and E’ respectively, and added, the result obtained after
EZ= Change in voltage applied to field 2. RP ’
E3’ =Fixed voltage applied to field 3. substituting from Eqs. (18) and (20) is
d
p = Differential operator z 11
-----@i- &&=~+(tl+t2+tdP~. (30)
PNJ 2
The initial or steady-state value of total useful flux per
pole is Rearranging the terms in Eq. (30);
~o=K(N,~,o+N~~~o+NE~Eo>. (16)
~,=[(l-&)+(t1+t2+tdP]dk (31)
When the field currents are changed to force an increase in
Chapter ‘7 Excitation Systems 207

JVhen solved, Eq. (31) expresses 4 and hence the terminal


Eliminating : by using Eq. (40)
voltage as a function of time if saturation and the con- e
sequent change in constants are neg!ected.
The three fields on the exciter can be assumed to be E (42)
replaced with a single equivalent self-escited field as shown
in Fig. 15. The quantities referring to the equivalent Equations (38) and (31) can be solved only if saturation
is neglected. However, for a small interval of time, it can
be assumed that the machine constants do not change, and
the change in flux calculated by either equation will be the
same. If at the end of the first time interval, the machine
constants are appropriately adjusted to new values
applicable to the next small interval of time, the flux
change can be calculated for the second interval and will
he the same by either equation. Thus, the flux rise cnl-
culated from the equation for the single equivalent field
by using the normal step-by-step methods that take into
account saturation will be the same as the actual flus rise
Fig. 156-Self-excited single-field equivalent of three-field main
with the assembly of several fields. The various time
exciter. constants for the machine in the unsaturated condit,ion
may be used to determine the constants of the equivalent
ficltl arc designated by the subscript e. The field has field.
applied to it a voltage equal to the terminal voltage c+’ The above equations can be generalized to the case of a
machine having any number of the three types of fields
plrw an equivalent voltage E,’ supplied by the regulator.
Iking stcndy-state conditions, considered. Letting t,, E, and N, refer to all coils to which
regulator voltages are applied, and t, and N, refer to all
Eeofc40 = R,&o+N,XPp4o. (32) coils which are self excited, Eq. (31) in the general form
i\t any instant of time, becomes

El+@‘= R,i,‘+N,XPp$‘. (33) ~~=[(l-c~&J+Pq#J (43)


Subtracting Eq. (32) from (33)
where 8t= sum of time constants of coils of all types. The
E,+cc$= R,i,+N,XPpqS. (34) sum of the time constants should also include a value for
Using the relations the frame slab, which acts as a short-circuited turn, and
eddy currents in the slab cause a delay in the flux rise.
q5= KN,i, (35) For d-c machines of the size used as main exciters, the
frame-slab time constant may approach 0.2 second.
L e= PdNeX = pKN,ZX (36) The constants of the equivalent self-excited field are
20 determined from the following:
t =PKNA t,=Zlt (44)
e (37)
R,’
N,-.L
IQ. (34) reduces to t, (45)
cN.
(38) L, is determined by Eq. (36)
Equation (38) is of the same form as Eq. (31), and by Re+f (46)
comparing similar terms, it is derived that e
te=t1+12+t3 (39) and the regulator voltage to be applied

Ne=$te. (47)

The self-inductance of the equivalent field is given by If no self-excited fields are present in the machine, the only
Eq. (36), and the resistance is requirements to be satisfied are given by Eqs. (44) and
(47). Any value of N, can be used provided the appro-
Re=$. (41) priate value of R, is calculated from Eqs. (36) and (46).
e When no self-excited fields are present, the equivalent
The applied regulator voltage is field is not self-excited and has applied to it only the
regulator voltage.
Ee=$$. If no regulator-controlled fields are present, the require-
2 ments to be met are given by Eqs. (44), (45), (46), and
208 Excitation Systems Chapter 7

(47), and the equivalent field is a self-excited field with no The excitation requirements, therefore, are greater for
regulator voltage applied. slow-speed generators. The main-exciter Rototrol has not
Using this equivalent single-field representation of the been built in capacities large enough to supply the excita-
multiple-field main exciter, the volt,age response can be tion requirements of large slow-speed a-c generators. Fur-
calculated by the step-by-step method of Sec. 2. The volt- thermore, as the Rototrol rated speed is decreased, its
age E is determined by the source of voltage under regu- excitation requirements also increase and a larger control-
lator control. For example, if the regulated field is a self- ling energy is required. The combination of these factors
excited field, the voltage E becomes equal to the exciter has largely restricted the use of the main-exciter Rototrol
terminal voltage at each instant of time. to direct-connection with 3600-rpm turbine generators.
A 210-kw, 250-volt, 3600-rpm main-exciter Rototrol is
8. Main-Exciter Rototrol illustrated in Fig. 16, and to all outward appearances it is
The most recent development in the field of rotating a conventional type of d-c machine. The mechanical de-
main exciters is the adaptation of the Rototrol rotating tails such as the enclosure, brush holders, commutator,
amplifier as a main exciter. Any generator is in fact a etc., are of conventional 3GOO-rpm exciter construction,
“rotating amplifier” in that a small amount of energy input but the electrical connections are quite different. The
to the field is amplified to a large energy output at the armature winding is of the lap form but has no cross
generator terminals. However, the name rotating amplifier connections, and there are a number of specially-connected
has been specifically applied to a form of rotating machine field windings to provide the high amplification factor.
possessing an unusually large amplification factor. In such A detailed discussion of the theory of operation of the
machines, the change in input energy to the field is a small Rototrol is beyond the scope of this chapter, and can be
fraction of the resulting change in energy output of the found in the References. The discussion here will be con-
armature. In the ordinary d-c generator, the change in fined to a description of the operating principle as it applies
field energy required to produce loo-percent change in to use of the Rototrol in excitation systems.
output energy is usually within the range of 1 percent to A schematic diagram of the main-exciter Rototrol is
3 percent of the machine rating. Thus, the amplification shown in Fig. 17 (a), and the equivalent schematic diagram
factor might be between 30 and 100. In the case of the is shown in Fig. 17 (b). The Rototrol can be built with one
Rototrol, the amplification factor can exceed 10” depending or more stages of amplification, and the main exciter Roto-
upon the design of the machine. trol is of the two-stage type. The field connected between
The main-exciter Rototrol is not adaptable at present to terminals F3-F4 is called the control field, and windings
use with generators operating at less than 1200 rpm. The appear on only the two south poles, 1 and 3. The circuit
principal field of application is with 3600-rpm turbine gen- between terminals F5-F6 energizes a field similar to the
erators. The two-stage main-exciter Rototrol can be built control field, and it also appears on only the two south
with sufficient capacity to supply the excitation require- poles. This field operates in the same manner as the con-
ments of the largest 3600-rpm generator, but when used trol field in controlling the Rototrol terminal voltage but
with 1800- or 1200-rpm generators, the maximum rating it is called the limits field. The control fikld is energized
of generator is restricted. In any event, the Rototrol is by the voltage regulator and normally has control of the
direct-connected to the generator shaft. voltage output. However, the limits field is energized by
The slower the speed of a generator, the larger the physi- devices that restrict the maximum or minimum voltage
cal size. For a given voltage output, the reduction in speed output, so that the limits field can, under certain condi-
is compensated by an increase in the total flux, requiring a tions, overcome the effect of the control field. The output
larger volume of iron to maintain the same flux density. terminals are Ll-L2, and it should be noted that the circuit
,I.. .,_,, ._. I between the brushes of like polarity energizes additional
*.
field windings that are compensating and forcing fields and
also serve as series fields. The windings energized by the
circuit between terminals Fl-F2 are shunt-field windings
used for tuning purposes as discussed later. As far as ex-
ternal circuits are concerned, the main-exciter Rototrol can
be represented as shown in Fig. 17 (c): the control field is
energized by some exciter-voltage controlling device, the
limits field is energized by a device for limiting the max-
imum or minimum output or both, and the line terminals
supply voltage to the load in series with the series field.
The. operation of a conventional self-excited d-c gener-
ator is unstable when the field-resistance line coincides with
the air-gap line of the saturation curve as shown in Sec. 1.
Although this characteristic is undesirable in the self-
excited generator, it is an important part of the Rototrol
principle. Reasoning identical to that in Sec. 1 can be
applied to a series-excited generator where the self-excited
Fig. 16-A 2lO-kw, 250-volt, 4-pole main-exciter Rototrol for winding is in series with the load and both the load and
direct-connection to generator shaft at 3600 rpm. the field can be considered as a shunt across the armature.
Chapter 7 Excitation Sosterns

COMPENSATING

L FIRST STAGE LSECOND STAGE

(b)-EQUIVALENT CIRCUIT OF TWO-


STAGE MAIN-EXCITER ROTOTROL

F2 LI c5 F3

LEGEND

----- SHUNT FIELD


--- COMPENSATING AND FORCING FIELDS SERIES FlELDS TERMINALS
- COMPENSATING FIELDS 1
--- LIMITS FIELD
---- CONTROL FIELD
- INDICATES DIRECTION OF CURRENT
+ INDICATES DIRECTION OF FLUX DUE TO CONTROL FIELD kkCIRCUIT REPRESENTATION OF MAIN-
e INDICATES DIRECTION OF FLUX DUE TO LOAD CURRENT EXCITER ROTOTROL
@ 0 BRUSH POLARITY FROM CONTROL FIELD EXCITATION
0 @ BRUSH POLARITY INDUCED BY ARMATURE REACTION
THIS REACTION IS THE RESULT OF THE CURRENT FLOWING
IN THE ARMATURE BETWEEN THE POSITIVE BRUSHES

(al-SCHEMATIC DIAGRAM OF ROTDTROL EXCITER


SHOWING ALL FIELDS EXCEPT INTERPOLE FIELDS
Fig. 17-Two-stage main-exciter Rototrol, complete schematic diagram and equivalent representations.

The series-field current then is directly proportional to the It is particularly significant that under steady-state
armature voltage in the same way as the shunt-field current conditions, the self-excited field of the Rototrol furnishes
in the self-excited shunt-wound machine. all of the ampere-turns required to generate the terminal
The Rototrol is operated on the straight portion of its voltage. However, the control field forces the change in
saturation curve and the adjustments necessary to meet ampere-turns required to stabilize the machine or to change
this condition are termed tuning of the Rototrol. This is and establish the terminal voltage required for a new load
usually done by adjusting the resistance of the load or an condition. The ampere-turns of the self-excited field and
adjustable resistance in series with the load, but can also those of the control and limits fields are superimposed, and
be done by varying the air gap between the field poles and the algebraic sum of the ampere-turns on all of the Roto-
the rotor surface, which shifts the position of the air-gap trol fields determines the terminal voltage.
line. Thus, the series-field circuit is tuned so that the
resistance line of the circuit coincides with the air-gap line. 9. I)Porating Principle of the Main-Exciter Roto-
Exact coincidence of the resistance line with the air-gap
line cannot always be obtained by these two means so a The fundamental principle by which a small amount of
small-capacity shunt field is provided to serve as a vernier energy in the control field forces a large change in Rototrol
adjustment. The resistance of the shunt-field circuit is output is that of unbalancing the ampere-turns on two
adjusted to change the position of the terminal voltage- poles of like polarity; in. this case, two south poles. A
series-field current relation to tune the machine perfectly. current in a given directron in the control field will weaken
210 Excitation Systems Chapter 7

(a) SIMPLIFIED WINDING-DEVELOPMENT DIAGRAM OF TWO-STAGE RoTOTROL


SHOWING CURRENT FLOW WITH CONTROL FIELD ENERGIZED

DIRECTION OF CIRCULATING
BRUSH POLARITY FROM ASSUMED CURRENT BETWEEN
CONTROL FIELD EXCITATION POSITIVE BRUSHES

MAGNETIZING EFFECT ,
OF LOAD CURRENT
FORCING FIELD

DIRECTION LOAD CURRENT


OF CURRENT
FORCING
FIELD FLUX

FSI 1 F4
(b)- ROTOTROL EXCITER CONTROL FIELD WINDING (~1 ROTOTROL EXCITER FORCING FIELDS CONNECTED
IN SERIES BETWEEN THE POSITIVE BRUSHES

DIRECTION OF CIRCULATING
DIRECTION OF DIRECTION OF CIRCULATING DIRECTION OF CURRENT BETWEEN THE
LOAD CURRENT, CURRENT BETWEEN POSITIVE LOAD CURRENT NEGATIVE BRUSHES

MAGNETIZING
DIRECTION OF LOAD EFFECT OF
CURRENT LOAD CURRENT

BRUSH POLARITY
‘INDUCED BY ARMATURE

OMPENSATING FIELDS COMPENSATING


FIELD FLUX
IZING EFFECT OF
RRENT IN MMPEN-
I

(d)- ROTOTROL EXCITER FORCING AND COMPENSATING FIELDS b)RoToTRoL


EXCITER
C~MPEPJSAT~IUGFIELDS CONNECTED
CONNECTED IN SERIES BETWE’EN THE POSITIVE BRUSHES IN SERIES BETWEEN THE NEGATIVE BRUSHES

b FLUX DUE TO LOAD CURRENT


-0 FLUX DUE TO CONTROL FlELD BEING ENERGIZED

Fig. 18-Principle of operation of two-stage Rototrol.


Chapter 7 Excitation Systems 211

one sollth pole and strengthen the other, and by virtue of reaction caused by current between t,he positive brushes,
the form of the armature winding, causes a difference in holding to a minimum the voltage difference between the
pol:irity between two brushes of like polarity. Current- ncgat,ive brushes and minimizing the armature reaction
tlircction arrows and corresponding flux-direction arrows that would oppose the control field.
are shown in Fig. 17 (a), and the operation can be under- A group of compensating fields are also connected in
st,)otl best, by describing the sequence of events for a given series in the circuit between the negative brushes, ant1
oprr:lting condition. serve a purpose similar to that of the compensating fields
.i current is shown flowing in the control field in Fig. between the positive brushes. These are shown in Fig. 1s (c).
~8 (1,). The current is in a direction to cause an increase in All of these currents and fluxes are summarized in Fig.
t 11cterminal voltage of the Rot,otrol and produces fluses as li (a), which shows all of the field windings and the current
sho\vn by the fl~~x arrows to strengthen south pole 1 and and flux arrows for the assumed condition. Tracing the
\vc:&rn south pole 3. Reversing the polarity of the voltage circuit of the load current reveals that the load current
appliccl to the control field would reverse the effect and must flow through the forcing and compensating fields.
(::L~~~c a decrease in terminal voltage. The resulting un- The coils are wound on the field poles in such a direction
t&nce of the south-pole fluxes causes a phenomenon that that the load current cancels so far as any magnetizing
is srlppressed in the usual d-c generator; and that is the effect is concerned, while the magnetizing effects of the
Ilnt&nce of voltage generated in the armature when the unbalance currents add. This is verified in the circuits of
magnetic flux clensit,ies in the field poles are unequal. The Figs. 18 (c), (d), and (&).
(#cct of the unbalanced south poles on the armature wind- In addition to the field windings described above, a set.
ing can bc analyzed by assuming the unbalanced fluxes are of commutating-polewindings are included in the Rototrol.
the only ones present in the machine. These windings produce the proper mmf in the commutat-
?‘hc winding-development diagram of Fig. 18 (a) is drawn ing poles to assist commutation of the current in the
for the control-field flux in the direction shown in Fig. 18 (b). armature.
So far as the control-field flux is concerned, pole 1 is a south The overall effect of current in the control field is sholvn
pole and pole 3 is a north pole; thus, the flux direction in Fig. 17 (b), the equivalent circuit of the two-stage main-
llnder pole 1 is out of the paper and under pole 3 is into exciter Rototrol. The Rototrol is represented as three
1he paper in Fig. 18 (a). For clockwise armature rotation, separate generators; two of them are two-pole machines
I hc conductor moves under poles 1,2,3, and 4 in that order, and the third is a four-pole machine. The difference in
so the current directions in the armature conductors are as potential between the two positive brushes caused by cur-
shown. The result is that the positive brush under pole 1 rent in the control field is represented as a two-pole gen-
is raised to a higher potential than the positive brush under erator excited by the control field and is the first stage of
pole 3. The relative polarities of the two positive brushes amplification in the Rototrol. The output of this machine
are, therefore, as indicated by the encircled polarity marks. is fed into the field of the four-pole generator which is the
l?urther analysis shows that the positive brush of higher second stage of amplification. The four-pole field windings
potential is always under the south control-field pole for are the forcing fields of the Rototrol. Current flowing in
t,he conditions of Fig. 18. the first-stage machine sets up an armature reaction rep-
The potential difference between the two positive brushes resented by a two-pole armature-reaction generator. The
is used to energize another special field called the forcing armature reaction is represented by a field exciting this
field, as shown in Fig. 18 (c). For control-field current in generator and the compensation for armature reaction be-
the direction shown, the fluxes produced by the forcing- tween the positive brushes is another field on this same
field windings are in a direction to increase the flux densi- machine. The mmf’s produced in the armature-reaction
ties in all four poles as shown by the open-headed flux and compensating fields are in opposition.
U-ows, which is in the direction to increase the terminal The armature reaction establishes a potential difference
voltage of the machine. With the opposite control-field between the negative brushes as shown, and the current
polarity, the forcing-field mmf’s decrease the flux densities. flowing between these brushes energizes additional com-
The forcing-field current also flows through the armature pensating windings on all four poles. Two of these wind-
\\intling as shown in Fig. 18 (aj. The two conductors in a ings appear as compensating windings on the armature-
wmmon slot u&r poles 2 and 4 carry currents in opposing reaction generator since they further compensate for the
(lirections. The conductors under poles 1 and 3, however, armature reaction produced by the current between the
carry currents in a common direction. Thus, an armature positive brushes. The remaining two compensating wind-
r(%t,ion is developed which is in the direction to weaken ings compensate for the armature reaction caused by the
north pole 2 and strengthen north pole 4. The effect is current flowing between the negative brushes, this arma-
similar to that caused by current flow in the control field, ture reaction being in opposition to the control field exciting
except that the unbalance in generated voltage appears the first, stage.
between the two negative brushes with polarities as shown
‘)Y the encircled marks in Fig. 18 (d). The resulting current 10. Series-Field Effect in Main-Exciter Rototrol
flow between the two negative brushes would cause an The definition of main-exciter response ratio given in
:lrmature reaction in opposition to the control field, greatly Part I does not apply to main exciters having series fields.
rr(lucing its effectiveness if compensation were not pro- Thus, the response ratio of the main-exciter Rototrol can-
vided in some way. The compensating windings in series not be stated in the conventional manner. As stated in
\\ith the forcing fields in Fig. 18 (d) oppose the armature Sec. 7, the series field of the Rototrol supplies all of the
212 Excitatio’n Systems Chapter 7

ampere-turns necessary to generate the terminal voltage in the generator field winding. The induced current is in
rmtler steady-state conditions. The response-ratio defini- the same direction as the current alreatly flowing in the
tion also states that t,he test for voltage response should he field circuit and serves to maintain constant flux linkages
macle under conditions of no load on the exciter, which with the field winding. This occurs when the generator
would seriously hamper the rate of voltage build-up in the voltage is low, and if the induced current were sustained
Rototrol, because there would be no mmf produced by the at its initial value, the internal voltage of the generator
series field. would he at a high value when the fault is removed. The
,\s shown in Chap. 6, Part IT, a short circuit at the function of a quick-rcsponsc excitation system is to in-
terminals of an a-c generator induces a large direct current crcasc the exciter voltage as rapidly as possible under such
conditions, in order to keep the field current at as high a
A-C
L
!jUPPL;Y value as possible. The same effect t,akes place, although
to a smaller extent, when a load is suddenly applied to the
generator terminals. Removal of a fault or sudden reduc-
tion of the load causes an induced current in the opposite
direction due to removal of the armatlrre demagnetizing A
effect. Thus, a current of appropriate magnitude is induced
AUXILIARY in the field winding of an a-c generator when there is any
TRANSFORMER change in the terminal conditions, but this current cannot
be sustained by conventional main excit’ers because their
voltage cannot ordinarily be increased fast enough.
The main-esciter Rototrol benefits directly from this
r-- induced current through its series-field winding and im-
HI mediately increases the mmf produced by that winding.

I
H3

a RI
H2
I
I RECTIFIER
SIX-PHASE
SHAFT-DRIVEN
ALTERNATOR
R4 FIELD
AFI

ALTERNATOR

TERMINALS
1 TRANSFORMER
R2 t
AF2

, RI R5 R3 R6
R4 R2
R3 t l l

R3
1
R4
1
RI
R5
<,
,
I
AUX
TRANSF
/ \

&L---A (L---, .--- ANODE


BKRS

I
IGNITRON
GROUNDING TUBES
,,, SWITCH
-IIS
GROUNDING
;‘i”
JEGATIVE I POSITIVE NEGATIVE POSITIVE
IERMINAL TERMINAL 6 b
TERMINAL TERMINAL t
7
Fig. 19-Simplified circuit of electronic main exciter supplied Fig. 20--Simplified circuit of electronic main exciter supplied 1
from the a-c generator terminals through a rectifier trans- from a six-phase alternator direct-connected to the main 1
former. generator shaft.
1
Chapter 7 Excitation Systems 213

FIELD-FLASHING The Rototrol terminal voltage is raised to a value that can


BREAKER, sustain the induced current. If the induced current is
caused by a short circuit, it gradually decays in magnitude,
SIX-PHASE
and the Rototrol voltage follows the decay in current. The
ALTERNATOR
result is that the Rototrol terminal voltage follows a mag-
FIELD nitude dependent largely upon the induced current, in the
generator field winding, and it cannot be duplicstcrl in a
RI- voltage-response test with the exciter unloaded.
R3
R5 The series-field effect in the Rototrol is a desirable phe-
nomenon in improving the response of the escitntion sys-
tem and in aiding to maintain system stability. It ennblcs
the main exciter to anticipate the change in a-c generator
THYRATRON excitation voltage required. As the series-field mmf is fol-
RECTIFIER S6 lowing the induced current, the voltage regulator delivers
TRANSFORMER energy to the control field to increase further the Rototrol
terminal voltage. There issome timedelay before thecontrol-
90
1 QR
field current is effective in changing the terminal voltage,
whereas the series-field effect is substantially instantaneous.

4
MOTOR
s4 s3 OPER 11. Electronic Main Exciters

3
RHEO
~2 S3 54 S5 S6 OL Power rectifiers of the ignitron type have been used for
many years in industrial applications and have given reli-
able and efficient performance. Their use as main exciters
for a-c synchronous machines has been limited, principally
THYRATRON because they cost more than a conventional main exciter.
TUBES The electronic main exciter, however, offers advantages
over rotating types.
An electronic exciter consists essentially of a power recti-
fier fed from an a-c source of power and provided \vith the
necessary control, protective, and regulating equipment.
The coordination of these component parts presents prob-
(0) lems that must be solved in meeting the excitation require-
ments of a large a-c generator.
FDRE = FIELD DISCHARGE RESISTOR
The output of a rectifier is only as reliable as the source
of a-c input power. Thus, this a-c source might be con-
sidered a part of the rectifier, and so far as service as an
SIX-PHASE
.$LE;NATOR CT]
excitation source is concerned, it must be reliable. Three
sources have been used in operating installations:
1. A-c power for the rectifier taken directly from the term-
inals of the a-c generator being excited.
2. A-c power taken from a separate a-c supply that is essen-
tially independent of the a-c generator terminals.
3. A-c power taken from a separate generator which supplies
power to the rectifier only, and which has as its prime mover the
same turbine that drives the main a-c generator.
In the first of these, the electronic main exciter is self-
excited, since its power supply is taken from its own out-
put, and in the second and third forms, it is separately-
PERMANENT-
excited.
MAGNET A-C SI When power for the rectifier is supplied by a high-voltage
GENERATOR source such as the generator terminals, a rectifier tmns-
former must be used to reduce the voltage to the proper
magnitude for the rectifier. The transformer is connected
W delta on the high-voltage side and sis-phase star on the
Fig. 21-Two methods of supplying excitation for the six- secondary side. No transformer is required when the sis-
phase alternator. phase shaft-driven generator is used as a power source.
(a) Self-excitation using a t,hyratron rectifier supplied from six- since the generator can be designed for the proper voltage.
phase alternator terminals through a rectifier transformer. A A simplified circuit diagram of an electronic exciter and
voltage regulator is used to hold the alternator field voltage
approximately constant. The battery is used to flash the (b) Separate-excitation using a three-phase permanent-magnet
alternator field to start operation. generator and dry-type
._ rectifiers.
214 Excitation Systems Chapter 7

rectifier transformer is shown in Fig. 10. The delta primary


of the transformer can be energized from the terminals of
the main a-c generator, from the plant auxiliary power
supply, or from some other independent source. The recti-
fier comprises three groups of two ignitron tubes each, the
two tubes of each group being connected to diametrically
opposite phases of the six-phase transformer secondary
through a two-pole, high-speed anode circuit breaker. Thus
if a breaker is opened, both tubes of a group are deener-
gized. Each pole of the anode breaker is equipped with a
reverse-current trip attachment and the breaker is auto-
matically reclosed. If an ignit.ron arc-back should occur,
the breaker is automatically opened at high-speed and
reclosed when the arc-back has been cleared. Should aA
second arc-back occur within a short time, the anode
breaker again opens and locks in the open position to
permit inspection of the unit.
The simplified circuit diagram of the electronic exciter
Fig. 22-Installation photograph of electronic main exciter. supplied from a six-phase alternator is shown in Fig. 20.

R3 X

AUX TR

R4 R2 R5

FIL l-R BIAS RECTOXES


- +
t

RCS-REGULATOR CONTROL SWITCH IN POSITION FOR MANUAL CONTROL

Fig. 23-Method of controlling release of the thyratron firing tube to regulate the main-exciter voltage. The firing control
circuit for ignitron tube 6 is shown.
Chapter 7 Excitation Systems 215

so far as the main-exciter rectifier is concerned, the details


of the circuit are the same as Fig. 10. A complication is
introducetl, however, since it is necessary to provide for
cscitation of the six-phase alternator. Two methods of
accomplishing this are shown in Fig. 21. In the method
of Fig. 21 (a), the excitation is provided through a six-phase
tllyratron rectifier, which receives its power input from the
same source used to supply the main-exciter rectifier. A
permanent-magnet a-c generator is used as the power sup-
ply in Fig. 21(b). It consists of high-quality permanent
magnets mounted on the same shaft with the main a-c
generator to serve as the rotor and a conventional three-
phase armature winding on the stator. The output of the
permanent-magnet generator is rectified by a three-phase
bridge-type selenium rectifier and fed directly into the field
of the six-phase alternator. While the shaft-driven gener-
ator in Fig. 20 is shown with six phases, it can be a standard
three-phase unit in which case a rectifier transformer would
t)c required to convert the ignitron rectifier input to EA-FIRING TUBE ANODE VOLTAGE
six-phase. EGG-CRITICAL GRID VOLTAGE OF FIRING TUBE
Each group of two ignitron tubes with its anode breaker, Eonc-PHASE SHIFTED A-C GRID BIAS VOLTAGE
cathode-disconnecting switch, firing tubes and associated E,-FIXED POSITIVE GRID BIAS
control circuit is located in one of three individual com- E2-VARIABLE NEGATIVE GRID BIAS
EG-TOTAL GRID BIAS VOLTAGE
partments of the main rectifier cubicle as shown in Fig. 22. CC-ANGLE OF GRID DELAY
Ignitron Firing Circuit and D-C Voltage Control
-The firing circuit for each ignitron tube is of the anode- Fig. 24-Control grid voltages applied to thyratron firing tube.
firing type as shown in Fig. 23. A thyratron tube is con-
nected in parallel with the ignitron through its igniter. give a total grid-bias voltage represented by Ec and vary-
The thyratron is made conductive when its anode voltage ing the negative bias determines the point at which the
is positive with respect to its cathode and its grid is re- total grid voltage becomes more positive than the critical
leased. Current then passes through the ignitron igniter grid voltage Ecc of the firing tube releasing the tube for
which initiates a cathode spot and fires the ignitron. If the conduction. The ignitron is then made conductive by cur-
ignitron should fail to conduct for any reason, the thyra- rent in the igniter and remains conductive for the remain-
tron attempts to carry the load current but is removed der of the positive half-cycle of anode voltage. The angle
from the circuit by the thyratron anode breaker. cr in Fig. 24 is defined as the angle of grid delay.
The magnitude of the output voltage of the electronic The use of a positive and negative grid bias in this
exciter is varied by controlling the point on its anode volt- manner provides for a wide range of control of the angle
age wave at which the ignitron tube is made conductive. of grid delay, and consequently, for a wide range of control
This point is determined by releasing the control grid of of the exciter output voltage. When the exciter voltage is
the firing thyratron, which is cont,rolled by a sine-wave under control of the automatic electronic regulator, the
grid transformer, a Rectox supplying a fixed positive bias, manually-controlled negative bias Ez is replaced by a
a Rectox supplying variable negative bias for manual con- variable negative bias voltage from the regulator.
trol, and an electronic regulatorsupplyingvariablenegative
bias for automatic control. The circuits of these devices 12. Electronic Exciter Application Problems
are shown in Fig. 23. Modern a-c generators have proven their capability of
The grid circuit of the thyratron firing tube can be continuous operation over long periods without being shut
traced from the cathode of the thyratron through the down for maintenance. It is necessary, therefore, that
ignitron to rheostats RPB and RNB and through the grid main exciters and excitation systems be capable of similar
transformer to the control grid of the thyratron. The volt- operation and that wearing parts be replaceable without
age El appearing across rheostat RPB is a positive grid requiring shutdown or even unloading. The ignitron and
bias, while the voltage EPappearing across RNB is a nega- thyratron tubes in the electronic exciter are subject to
tive grid bias. The sine-wave voltage ECACimpressed on deterioration and eventual failure and replacement, and it
the grid of the thyratron is delayed almost 90 degrees from is essential that such a failure and consequent replacement
the anode voltage and is connected in series with the be sustained without interfering with excitation of the
positive and negative biases. These voltages are shown a-c generator.
in Fig. 24. In its usual form, the electronic main exciter is designed
Rheostats RPB and RNB are initially adjusted to give so that it can supply full excitation requirements continu-
the desired values of positive and negative grid-bias volt- ously with two of the six ignitron tubes out of service.
ages. Manual control of the exciter voltage is obtained by With all six tubes in service, the capacity is approximately
changing the setting of rheostat MVR which varies the 150 percent of the requirements. Furthermore, the over-
negative bias. The bias voltages El, E2 and ECAC add to load capacity of the ignitron tubes is such that the rectifier
216 Excitation Systems Chapter 7

can supply full escitation for a short time with only two
of the six tubes in service. Should a tube failure occur, the
ignitron anode breaker, grounding switch, and firing-tube
anode breaker are opened enabling replacement of the /
/
ignitron or firing thyrstron of any group without disturb- /
ing the continuous operation of the remaining two tube /
groups. /
z /
For the electronic exciter to be completely reliable, it 2 /
must be provided with a reliable source of a-c power. When 2 / RECTIFIER
z a b
self-excited from the terminals of the main a-c generator, cz
-CEILING
/ VOLTAGE
the input to the rectifier is subject to voltage changes t” I

during system disturbances. Thus during nearby faults 3


5
on the system when it is desirable to increase the generator ,i EQUIVALENT
excitation as much as possible, the rectifier voltage output / RESPONSE
may be low due to the low a-c voltage. To compensate for LINE
the low voltage, the rectifier can be designed for a voltage
ACTUAL
output much higher than that required during normal
RESPONSE
operation; that is, the rectifier may be designed to produce /
/

normal ceiling voltage when the a-c input voltage is $5 d


0 0.5
percent of normal. Under normal load conditions the volt-
TIME IN SECONDS
age is reduced to that required by control of the firing
point. This method of compensation requires a larger Fig. 25-Response of the electronic main exciter.
rectifier transformer and means that the firing is delayed
longer during normal operation. fore, the actual rate of voltage increase exceeds 10 per unit
When separate-excitation is used to supply power to t.he per second.
rectifier, the input is no longer subject to variation during
disturbances on the main system. It is possible that a III. PILOT EXCITERS
disturbance in the system supplying power to the rectifier
may cause a disturbance in the excitation of the a-c gen- When the main exciter of an a-c synchronous machine is
erator and a consequent disturbance on the main system. separately-excited, the d-c machine which supplies the
This is overcome by making the rectifier power supply as separate excitation is called a pilot exciter. A main exciter
reliable as possible. Since the same philosophy applies to can be supplied with excitation from more than one source,
the system used to supply the powerhouse auxiliaries, as is the three-field main exciter, which has a self-excited
this system can be used to supply the rectifier. The field and two separately-excited fields, but the sources of
shaft-driven three- or six-phase alternator, however, separate excitation are still considered as pilot exciters.
offers the most reliable solution. It is also possible to Older excitation systems used a storage battery as a pilot
use duplicate supply with automatic changeover during exciter, but maintenance problems soon prompted its re-
disturbances in the normal supply, but this is not justi- placement with rotating types of d-c machines. Two gen-
fied normally. eral classifications of pilot exciters are constant-voltage and
variable-voltage types. The constant-voltage type is used
13. Response of the Electronic Main Exciter where control of the main exciter voltage output is by a
The ignitron rectifier has the ability to increase or de- rheostat in the exciter’s separately-excited field circuit, and
crease its voltage output with substantially no time delay. the variable-voltage type is used where the pilot-exciter
Compared with the rate of voltage build-up of other types voltage must vary to give variable voltage on the exciter
of d-c machines, it might be considered instantaneous. If field.
the response ratio of the electronic exciter were expressed
in accord with the definition given in Part I, it would
14. Compound-Wound Pilot Exciter
convey a false impression. The line Oa in Fig. 25 represents The most common form of constant-voltage pilot exciter i
the actual voltage response of the electronic exciter. The is the compound-wound d-c generator. The circuit diagram
line ab represents the ceiling voltage. The line Oc is drawn SERIES
FI EL0
so that the area Ocd is equal to the area Oabd under the
actual response curve during the O.bsecond interval. Ac-
cording to the definition, the rate of response is the slope
of the line Oc, which implies that the exciter voltage has SHUNT
I
not reached its ceiling value at the end of a 0.5-second FIELO TERMINAL
VOLTAGE
interval.
If the distance Oa is set equal to 1.0 per unit, then the
distance dc almost equals 2.0 per unit. The rate of voltage
build-up is dc divided by 0.5 second or 4.0 per unit per
second. The actual time required for the voltage to in-
crease from 0 to a is much less than 0.1 second, and there- Fig. 26-Compound-wound conventional pilot excite;.
Chapter 7 Excitation Systems 217

is shown in Fig. 26. The pilot exciter is invariably a 125- of a period of changes by reason of progress in the develop
volt machine with a self-excited shunt field and a series- ment of regulating and excitation systems. Efforts havcl
cxciterl field, adjusted to give substantially flnt-compound- been directed part,icularly toward t,he development of mom
ing. Thus, regardless of t,he load on the pilot excit,er, reliable, more accurate, more sensitive, and quicker-acting
the magnitude of its terminal voltage is practically con- systems. Consequently, there are now many different es-
stant. citation systems in use, each filling a specific need of the
The compound-wound pilot exciter is normally mounted industry.
(,I, t.hc shaft of the main exciter, and where the main exciter The preceding sections have discussed the various types
is direct-connected, the a-c generator, main exciter, and of main and pilot exciters in use at present. The remainder
l)ilot csciter all rotate at the same speed. A rheostat, either of the chapter will be a comprehensive discussion of the
finder the control of a voltage regulator or under manual application of these d-c machines in excitation systems in
control, is connected in series with the output circuit of the conjunction with various types of generator voltngc
lji1ot exciter to regulate the voltage applied to the field of regulators.
t1ic main exciter. Four types of voltage regulators are being used to con-
trol the excitation of synchronous machines:
15. Rototrol Pilot Exciter 1. Direct-acting rheostatic type
‘The Rototrol, described in Sec. 8 as a main exciter, is 2. Indirect-acting exciter-rheostatic type
:tlso used as a variable-voltage pilot exciter. Depending 3. Impedance-network or static-network type
~ipon the excitation requirements of the main exciter, the 4. Electronic type.
]<ototrol pilot esciter may be of either one or two stages of Each of these are described in their application in varioiis
:Lmplification. Generally, when the main exciter and Roto- types of excitation systems in the order named.
1rol pilot exciter are direct-connected to the generator shaft
;md operating at 3600 rpm, the pilot exciter has a single 16. The Direct-Acting Rheostatic Regulator
stage of amplification. When the pilot exciter is operated The Silverstat generator voltage regulator is a common
:tt a speed lower than 3600 rpm, such as 1800 or 1200 rpm, and widely used form of the direct- and quick-acting rheo-
it. is of the two-stage type. static type of regulator. It is specifically designed for the
The single-stage Rototrol is a stabilized series-excited automatic voltage control of small and medium size gen-
d-c generator as shown in Fig. 27. The control field is a erators. For generators rated above 100 kva, the Silverstat
or SRA regulator is available in five sizes, the largest being
SERIES used with generators as large as 25 000 kva. h typical SR;l
FIELD regulator of medium size is shown in Fig. 28 (a).
The direct-acting rheostatic type of regulator controls
the voltage by the regulator element varying directly the
CONTROL regulating resistance in the main exciter field circuit. The
FIELD different sizes of SR-1 regulators are suitable for the nuto-
matic voltage control of constant-speed, one-, two- 01
three-phase a-c generators excited by individual self-excited
exciters. The exciter must be designed for shunt-field con-
LIMITS trol and self-excited operation, with its minimum operating
FIELD
voltage not less than 30 percent of its rated voltage. Each
regulator is designed for and limited to the control of
Fig. 27-Equivalent circuit of single-stage Rototrol pilot one exciter.
exciter. Where a-c generators are operated in parallel and are
within the range of application of this regulator, the prac-
s(>parately-excited shunt field. The principal difference tice is to provide each generator with an individual esciter,
l)ctween this and a conventional series-excited d-c genera- with the exciters operated non-parallel. Each generator
1or is the fact that the Rototrol is operated in the unsat- and its exciter is provided with an individual regulator and
timtcd region, that is, on the air-gap line. Under steady- suitable cross-current compensation provided between the
state conditions, the sustaining series field supplies prac- regulators.
ti(,ally all of the ampere-turns required to maintain the Sensitivity-The sensitivity of a generator voltage
1iototrol terminal voltage. The input to the control field regulator is the band or zone of voltage, expressed as a
:lcts as a stabilizing force to hold the voltage at any point percentage of the normal value of regulated voltage, within
on the straight-line portion of the saturation curve. which the regulator holds the voltage with steady or grad-
ually changing load conditions. This does not mean that
the regulated voltage does not vary outside of the sensi-
IV. GENERATOR EXCITATION SYSTEMS
tivity zone, but does mean that when the regulated voltage
In the ten-year period following 1935, two basic types of varies more than the percentage sensitivity from the regu-
generator voltage regulators filled substantially all needs lator setting due to sudden changes in load or other system
Of the electrical industry. These were the indirect-acting disturbances, the regulator immediately applies corrective
exciter-rheostatic regulator and the direct-acting rheo- action to restore the voltage to the sensitivity zone.
static regulator. Excitation systems are now in the midst Regulator sensitivity must not be confused with overall
218 Excitation Systems Chapter 7
.--
i ‘.*$
-I ! regulation, which involves not only regulator sensitivity
but also the time constants of the machines and the char-
i
actcr and magnitllde of the voltage changes. The magni-
tude and rate of load change determine how far the voltage
deviates out.side of t,he regulator sensitivity zone, and the
time constants of the machines chiefly determine the time
required to restore the voltage to the sensitivity zone. For
these reasons only sensitivity can be specified so far as the
voltage regulator is concerned and not overall regulation,
which involves factors over which the regulator has no
control.
The rated sensitivity of the SRA voltage regulators
depends on the size of the regulator. The SRA-1 and
SRX-2, the two smaller sizes, have rated sensitivities of
plus or minus 2% and 1% percent, respectively. The A
larger SRA-3, SRA-4 and SRA-5 regulators are rated at
plus or minus x of 1 percent sensitivity.
17. Operation of the Direct-Acting Rheostatic
Regulator
The silver-button assembly, Fig. 28 (b), provides the
means for changing the resistance in the exciter shunt-field
circuit under control of the regulator. This basic assembly
consists of a group of spring-mounted silver buttons so
arranged that the butt,ons are separated from each other

SILVER
MUTTONS

hhAGNET
REGULATOR
COIL \ /ARM
I/
ii
RMATURE

PUSHER
/

VOLTAGE
4DJUSTING
3HEOSTAT

RRI-

(b)
Fig. 28-(a) SRA-4 Silverstat generator voltage regulator. Fig. 29--Schematic internal diagram of SRA-3 Silverstat i
(b) Silver-button assembly of Silverstat regulator. regulator.
Chapter 7 Excitation Systems 219

normally, but can be closed or opened in sequence by a voltage is necessary. For a given value of regulated voltage
suitable driver having a travel of a fraction of an inch. The and load on the machine being regulated there is a corrts-
springs or leaves that carry the silver buttons are insulated ponding value of regulating resistance required in the field
from each other and each leaf is connected to a tap on a circuit; and a corresponding position of the moving arm
resistance element as shown in Fig. 29. Varying amounts and silver buttons that gives this value of resistance. Undcl
of the resistance are short circuited by closing of the silver- such conditions the magnetic pull on the moving arm is
I)ut,ton contacts. One or more of these basic elements are balanced against the spring pull at that position of its
used in regulators of different sizes, four being used in the travel. When there is a change in lo&d on the machine
SR=\-4 regulator illustrated in Fig. 28 (a). being regulated, a corresponding change in voltage results,
The cont,rol element of the regulator is a d-c operated and the voltage is restored to its correct value by the
device. A spring-mounted armature is centered in the air moving arm and silver buttons taking a new position.
gap of the electromagnet as shown in Fig. 29. In regulating Since the pressure on silver contacts determines the resist,-
a-c voltage, a full-wave rectox rectifier is used to convert ante of the contacts, an infinite number of steps of regulat,-
the a-c to d-c for energizing the control element. ing resistance are obtained. If the required value of exciter
A typical excitation system under control of an SRA field resistance should lie between two of t,he tapped points
r,clglll:ltor is shown schematically in Fig. 30. The regulating of the regulating resistance, the pressure of the silver con-
tacts changes to provide the correct intermediate value
EXC SHUNT
of resistance.
The fixed resistance in the esciter field circuit in Fig. 30
is used when it is desired to limit the exciter shunt-field

I 3
current when the maximum or ceiling current is such as to
interfere with the best performance of the voltage regulat-
ing equipment. The exciter shunt-field rheostat and the
generator field rheostat are provided primarily for control
of the generator escitation when the regulator is not in
service. Excitation current in the generator field can be
TRANS regulated by changing the esciter output voltage or by
holding the exciter voltage constant and changing the gen-
r-P COMPEN- erator field resistance. When the voltage regulator is in
,,,,. ,.” ._-

REGULATING
RESISTANCE

REGULATOR 2
COIL
I

Fig. 30--Self-excited main exciter controlled by Silverstat


regulator. The compensating resistance is used to provide
cross-current compensation during parallel operation of a-c
generators or to provide line-drop compensation.

r&tance is connected directly in the exciter shunt-field


(‘ircuit. At one end of the travel of the moving arm, all of
the silver buttons are apart from each other, placing max-
imum resistance in the field circuit. At the other end of
1.1~~ travel, the buttons are closed and the resistance is
short circuited. The moving arm can hold the resistance
:ktdany intermediate value and, since the travel is short,
~11the resistance can be inserted or removed from the field
(:il.cuit quickly. The speed of operation of the regulating
element depends upon the magnitude and rate of change
Of the operating force. With a sudden drop in a-c voltage
of 10 to 12 percent, the time required for the regulator to
remove all resistance from the exciter shunt-field circuit is
-
“PDroximately 0.05 second or 3 cycles on a GO-cycle basis. sea* -, ,,*A‘.mArm.s&a,*u”s-r- .,.

The regulating action of the SRA regulator is that of a Fig. 31-Silverstat regulator damping transformer and rectox
Sen&atic device that operates only when a correction in rectifier assembly.
220 Excitation Systems Chapter i’

operation and controlling the generator voltage, the exciter lated as shown in Fig. 30. The current transformer is
shunt-field and generator field rheostats are ordinarily connected to an adjustable resistance in the a-c supply
turned to the “all ollt” position so that the regulator has circuit to the regulator operating element. The adjustable
full control of the excitation voltage. resistance permits adjustment of the compensation to suit
Damping-To stabilize the regulated voltage and pre- the application. The current transformer is connected in
vent excessive swinging under various conditions of excit.a- one generator lead, while the potential transformer that
tion change, a damping effect is introduced into the regu- operates the regulator is connected to the other two leads.
lator coil circuit, by means of a damping transformer as Thus the phase relationship is such that for lagging re-
shown in Fig. 30. The damping transformer is illustrated active kva, the voltage drop across the compensating re-
in Fig. 31. ‘I’he use of this device eliminates the need for sistance adds to the a-c voltage energizing the regulator
dashpots or similar mechanical anti-hunting devices. and subtracts in the case of leading reactive kva. This
The damping transformer is of a special type having a action tends to cause the regulator to lower excitation for
small air gap in the laminated-iron magnetic circuit. One lagging reactive kva and raise excitation for leading reac-
winding is connected across the field of the generator whose tive kva. In this manner each generator tends to shirk A
voltage is being regulated, and the other winding is con- reactive kva, and the wattless power is automatically
nected in series with the voltage regulator coil. When there divided in proportion among the paralleled a-c generators.
is a change in escitation voltage as a result of the regulating In many applications, reactance in the form of power
action of the regulator, energy is transferred by induction transformers, bus reactors, etc., exists between paralleled
from one winding to the other of the damping transformer. a-c generators. If each generator is excited by an individ-
This energy introduced into the circuit of the regulator ual exciter under control of an individual voltage regu-
coil acts by reason of its direction, magnitude, and time lator, and if the reactance is such as to cause from four
relation to electrically damp excessive action of the moving to six percent reactive drop between the two generators,
arm, preventing the moving arm from carrying too far the then stable operation and proper division of the wattless
change in regulating resistance and consequent change in component can usually be obtained without using cross-
generator excitation. Since the damping transformer oper- current compensation between the regulators. This is be-
ates only when the excitation of the generator is changing, cause the reactance produces an effect similar to that ob-
it has no effect when the regulated voltage is steady and the tained where cross-current compensation is used.
regulator is balanced.
Parallel Operation-As is true with most generator 18. Indirect-Acting Exciter-Rheostatic Regulator
voltage regulators, the SRA regulator can control only one In recent years the increase in capacity of generating
exciter at a time. Where several a-c generators operate in units, the extension of transmission systems, and the inter-
parallel and all the generators are excited from one common connection of established systems, have reached a point
exciter, a single Silverstat regulator can be used, provided where quick-response excitation is valuable for improving
the exciter is of a size that is within the range of application stability under fault conditions and large load changes. On
of this type of regulator. However, where a-c generators applications of this kind the type BJ regulator is particu-
operate in parallel, the usual practice is to provide each larly adapted to the control of a-c machines employing
one with an individual exciter controlled by an individual quick-response excitation. The B.J regulator is of the
regulator. This scheme of operation requires that the ex- indirect-acting exciter-rheostatic type for the automatic
citers be operated non-parallel, and it is necessary to supply control of medium and large size a-c generators.
a means of assuring proper division of reactive kva between The indirect-acting exciter-rheostatic type of generator
the generators. The division of the kilowatt load among voltage regulator controls the voltage of an a-c machine by
paralleled a-c generators is dependent upon the power varying the resistance in the field circuit of the exciter that
input to each generator and is controlled by the governor excites the a-c machine. The exciter is preferably sepa-
of its prime mover. Thus the division of kilowatt load is rately-excited from a pilot exciter or other source. If the
practically independent of the generator excitation. How- exciter is self-excited, its minimum operating voltage must
ever, changes in the field excitation of paralleled a-c gen- not be less than 30 percent of its rated voltage if stable
erators do affect the reactive kva or wattless component operation is to be obtained. When lower voltages are
of the output, and the division of the reactive kva is directly necessary, the main exciter must be separately-excited.
affected by the operation of the voltage regulators. A schematic wiring diagram of the BJ generator voltage
Thus, wattless current circulates between the paralleled regulator and its auxiliary contactors is shown in Fig. 32.
a-c generators unless some provision is made whereby the This diagram in conjunction with the simplified schematic
generators are caused to properly divide the reactive kva. of Fig. 33 is used to describe the operation of the device.
This is accomplished by means of cross-current compensa- The main control element of the regulator is energized
tion, which functions to cause each generator to shirk from two single-phase potential t,ransformers connected .to m
wattless current by means of a slight droop in the regulated the a-c machine leads. Two sets of contacts are on the
voltage with increase in the wattless component of current. moving lever arm of the regulator element shown in Fig.
The effect of the small droop required is usually negligible 32, namely, the normal-response contacts R-L and the
under operating conditions as found in actual practice. quick-response contacts AR-AL. The normal-response
For three-phase a-c generators with. the SRA regulator, contacts control the rheostat motor contactors NR and
the compensation is obtained by a standard current trans- NL, to raise or lower the a-c machine voltage, respectively-
former connected in one lead of each generator being regu- The quick-response AR and AL contacts control the high:
chapter 7 Excitation Systems 221

speed contactors QR and QL, which arc the “field forcing nckhcr the normal-response contact,s R-L nor the qrrick-
UP)’ and “field forcing down” contactors, respectively. response contacts AR-AL are closed. Should the a-c volt-
\l:hen contactor QR in Fig. 33 is closed, all external resist- age fall below normal by a small amormt, tlepentling upon
:rn(;c is shorkd out of the main-exciter field circuit, and the sensitivity setting of the regulator, the normal-response
!&en (2L is opened by energizing its coil, a block of resist- contact R will close, energizing the rheostat motor control
;knc’<lis inserted in t,he field circuit. contactor NR. The contacts NR energize the rhcostnt
Normal Response--When the a-c voltage is normal, motor which then turns t,he rheostat in a direction to
t,h(! rcgulat,or lever arm is balanced and in this position remove resistance from the exciter field circuit, thereby
increasing the voltage applied to the exciter field.
TO CT The rheostat-mot,or control contactor NR has three con-
tacts that close in independent circuits simultaneously.
The one circuit is that just described which operates the
rheostat motor. The second is the circuit of the anti-
hunting winding NH of the regulator main control clement
and the third set of contacts complete a timing-condenser
circuit. The anti-hunt device operates to increase the gap
distance between the contact faces of the regulator contacts
R and L, thereby opening the circuit at the R contacts.
This change in position of the R contact is equivalent to
changing the regulator setting to a lower voltage so far as
the raise contacts are concerned, and to a higher voltage
so far as the lower contacts are concerned. Where the
deviation from normal voltage is small and within the
I- recalibration effect of t,he anti-hunt device, the immediate

Fig. 32--Schematic diagram of the BJ regulator controlling the voltage of a separately-excited main exciter.

R,=SHUNT FIELD FIXED R


R,,=FIELO FORCING-UP R
I?,~=FIELO FORCING-DOWN R
R,,44OTOR-OPER SHUNT FIELD
RHEO CONTROLLED BY
REGULATOR NORMAL-RESP
CONTACTS
FIELO ROr’OIFF FIELD FIXED R
OR = REGULATOR BUICK-RAISE
FORCING CONTACTOR
OL. REGULATOR OUICK-LOWER
FORCING CONTACTOR

Fig. 33-Main-exciter circuits:under control ,of BJ,regulator in iFig. 32.


222 Excitation Systems Chapter 7

result of the closing of the contacts on contactor NR is to the circuit of the anti-hunt, device QH, which operates to
cause the opening of the regulator R contact, which in turn spread t,he AR ancl LL contacts in the same manner m
opens the circuit to the coil of contactor NR, to stop the described for the NH device and the R and L contacts,
motor of the esciter field rheostat and thus stop the rheo- Therefore, if the deviation from normal voltage is \vithin
stat moving arm. However, contactor NR does not im- the recalibration effect of the QH anti-hunt device, the
mediately open due to a time-delay circuit around its coil field-forcing-up contactor closes and opens rapidly while
that maintains the coil voltage. Thus the rheostat arm is the rheostat arm approaches t,he required new position. If
permitted to move a definite distance, for example, from the deviation from normal voltage is greater than the
one button to the next on the rheostat faceplate, and at recalibrated setting of QH anti-hunt device, the field-forc-
the end of its time delay, contactor NR opens to stop the ing-up contactor closes and remains closed until the a-c
rheost,at motor and deenergize the anti-hunt device. voltage is brought within the recalibrated setting.
After the rheostat motor stops, it is desirable to provide As the a-c voltage comes within the setting of the AR
some time delay to allow the a-c machine voltage to reach contacts and they no longer close, the normal response’
its final value. Such delay is obtained by a dashpot on the contacts R take control and by notching the rheostat:
anti-hunt device that prevents the regulator contacts from return the a-c voltage to normal. Since the rheostat moves
immediately returning to their normal position. After this at maximum speed while the quick-response contacts are
time delay has expired and the contacts have returned to closed, it takes only a minimum of additional movement
their normal position, the normal response contact R again after the normal-response contacts take control to return
closes if the a-c voltage has not returned to normal. This the voltage to normal.
starts another cycle of operation such as just described and When the main exciter has a differential field as shown
these cycles continue until the normal value of regulated in Fig. 33, a contact in the QR contactor opens the differ-
voltage is established. ential-field circuit. In this way, the damping effect of the
Where the original voltage deviation is large enough the differential field in slowing the exciter response is removed.
regulator contacts remain closed continuously even though
the anti-hunt device changes the cont,act setting. In this 19. Sensitivity of the BJ Regulator
case the regulator arm is caused to follow the change in The rated sensitivity of the BJ generator voltage regu-
contact position made by the anti-hunt device, and the R lator is plus or minus x of one percent. The sensitivity is
contact and the contactor NR remain closed. This causes adjusted by varying the spacing between the regulator
the rheostat motor to run continuously until the a-c volt- contacts R and L. The quick-response contacts are set to
age is within the zone for which the anti-hunt device is set, a wider spacing than the normal-response contacts so that
at which time the notching action takes place to bring the larger deviations from normal voltage are required to close
voltage to normal. them. The usual range of settings of the quick-response
By means of the continuous or notching action of the contacts is from plus or minus 255 percent to plus or minus
rheostat, dependent upon the magnitude of the voltage 10 percent, the setting depending somewhat on the setting
change, time is allowed for the a-c voltage to come to rest of the normal-response contacts and upon the operating
between each voltage correction as the voltage approaches conditions of the particular installation.
its normal value. The action of the dashpot is also such The main coil of the control element in Fig. 32 consists
that the time required for the contacts to remake is longer of a voltage winding energized by a d-c voltage, rectified
as the lever arm approaches the normal voltage position. from the three-phase a-c source being regulated. Thus, the
This results in a decreased motor speed as the rheostat arm coil is energized by a voltage equal to the average of the
moves nearer to its new position, preventing overshooting phase voltages and the regulator holds this average voltage
of the rheostat position and bringing the a-c voltage to within the rated sensitivity zone. The level of the regu-
normal in a minimum length of time. lated voltage is set by adjustment of the voltage-adjusting
When the a-c voltage rises above the regulated value, rheostat; resistance being added in series with the regulator
an action similar to that described for low voltage takes voltage coil to increase the level of the regulated voltage,
place, except that the regulator contact, L closes energizing and resistance being removed to decrease the level of the
the rheostat motor control contactor NL, which operates regulated voltage. The normal range of adjustment is
the rheostat motor in a direction to increase the resistance approximately plus or minus 10 percent from the normal
in the exciter field circuit. generator voltage.
Quick Response-When a large drop in voltage occurs,
such as might be caused by a large block of load being 20. Cross-Current Compensation with BJ Reg-’
thrown on the system or by a fault, the normal-response ulator
contacts R on the regulator close, followed by closing of the When cross-current compensation is required to give the’
quick-response contacts AR. Contacts AR close the circuit voltage regulator a drooping characteristic, one compen- 1
to the high-speed field-forcing-up contactor QR, which sator and one current transformer are required, connected.
short circuits all of the external resistance in the exciter as shown in Fig. 32. The compensator is designed to supply j
field circuit, applying full exciter voltage to the field circuit. a compensating voltage in two phases of the three-phase /
This causes the a-c machine voltage to start to return to regulator potential circuit. This insures applying a bal-1
normal very rapidly by forcing action. anced three-phase voltage to the regulator element, which;
When the field-forcing-up contactor QR closes,an aux- would not be the case if only one leg was compensated.
iliary contact on this contactor closes at the same time in The vector diagram of the compensating circuit is shown,1
Chapter ‘i Excitation Systems 223

TO

/ VOLTAGE
REG

El
I2
EZ IR
IX

Fig. 34-Vector diagram of cross-current compensation used


with BJ regulator. Circuit shown in Fig. 32.

in Fig. 34, the potential transformer secondary voltages


being represented by I&, E,, and E13. The current applied
TI” I

VECTOR DIAGRAM OF SYSTEM


to the autotransformer of the compensator in Fig. 32 is
taken from the secondary of a current transformer in phase Fig. 35-Principle of line-drop compensation.
2 of the a-c circuit. Two compensating voltages are pro-
duced; one between terminals Xl-X2 designated as EZ on and RI are proportioned to and in phase with the corres-
the vector diagram and the other between terminals Yl-Y2 ponding values of line reactance and resistance voltage
designated as ER on the vector diagram. Voltages ER and drops, the regulator controls the voltage as if it were
Ez are 120 degrees apart in time phase and, therefore, can connected by pilot wires to the load center.
bc added to a three-phase set of voltages without unbalanc- In general, since the reactance component XI of the line
ing it. predominates, it is necessary to compensate mainly for this
The vector diagram shows Ez and ER for zero power component of the line drop, the resistance component RI
factor, under which condition maximum compensation is having a relatively small effect.
obtained. As the power factor approaches unity, these Parallel operation of a-c generators, each under the con-
voltage vectors swing through an arc of 90 degrees and trol of a voltage regulator, requires a droop in regulated
give zero compensation at 100 percent power factor. At voltage with an increase in wattless load. On the other
zero power factor, vectors Ez and ER add directly to vec- hand, reactance line-drop compensation requires a rising
tors Ezl and E13,respectively. For power factors greater characteristic for the regulated voltage with an increasing
than zero, only a proportionate component of these volt- mattless load. In order to compensate for reactive cross
:~gesEz and ER add directly to voltages Ezl and E13. The current between machines and for complete line drop’when
addition of these compensating voltages to the line voltages machines are operating in parallel in the same station, three
:LSthe’load increases or the power factor changes gives the current transformers and two compensators with suitable
regulator element a high voltage indication resulting in a auxiliary equipment must be used for each machine. In
reduction or droop in regulated voltage. Usually the com- any event, the XI line-drop compensation must never
l)onsator should cause from four to six percent droop in exceed the XI cross-current compensation; i.e., there must
voltage at zero power factor full load on the a-c generator. be a net droop in regulated voltage with increase in watt-
less load.
21. Line-Drop Compensation with BJ Regulator Complete line-drop compensation is not always neces-
The wide use of interconnected power systems has elim- sary, and a simple compromise solution is available to
inated to a large extent the need for line-drop compensa- provide approximate line-drop compensation and reactive-
tion. However, it is sometimes desirable to regulate for a droop compensation. The RI-drop compensation is set to
constant voltage to be maintained at some point on the approach the XI drop of the line for some average power
system external to or distant from the station where the factor. When ,the RI-drop compensation is so set, the
s-c machine and its regulator are located. The principle XI-drop compensation can be adjusted independently to
1~ which this is accomplished is shown by the circuit and provide the required cross-current compensation, and there
vector diagrams of Fig. 35. is no interference between the two compensators.
The voltage regulator is to maintain the voltage Ez
constant. If it were possible to supply the regulator with 22. Synchronous Condenser Excitation with BJ
Pilot wires so that it could measure the voltage at the load Regulator
center, the regulator could adjust the excitation of the The type BJ generator voltage regulator can also be used
generator to maintain Ez constant. Since in actual practice to control the excitation of a synchronous condenser. The
it is impractical to use pilot wires, the regulator potential circuit is essentially the same as that shown in Figs. 32
“inding is energized from the generator bus voltage El, and and 33.
the two components XI and RI are subtracted from it When the excitation of a synchronous condenser is in-
artificially
. by the compensation. The resultant voltage Ez creased above a certain value, the condenser furnishes a
Is then supplied to the regulator. If the components XI lagging (overexcited) current to the system thereby caus-
224 Excitation Systems Chapter 7

ing the voltage to rise. Tn a similar manner, decreasing the later. Tf the synchronous condenser load is gradually in-
excitation lowers the voltage. Thus, when a generntor creased, the current-limiting contact in series with the R
voltage regulator is applied to a synchronous condenser, contact of the regulator opens the “raise” control circuit
it regulates the line voltage to a constant value by varying and prevents any further increase in excitation. At the
the excitation of the condenser, provided the condenser same time, a second contact of the current-limiting device
has sufficient corrective rkva capacity. energizes the “lower” control circuit of the regulator, caus-
It is often necessary that the condenser furnish leading ing the excitation and load current to be reduced to the
(underescited) rkva as well as lagging (ovcrcxcitcd) rkva, safe limiting value. This protection against a gradual in-
and it is necessary to reduce the excitation to an extremely crease in load operates in the normal-response R-L circuits
low value. Where the minimum value is less than 30 per- of the voltage regulator.
cent of the main exciter rated voltage, it is necessary to use In the case of a sudden increase in load current, an
a separately-excited main exciter. In many cases it is instantaneous overcurrent relay set to pick-up at a higher
necessary to reverse the excitation voltage to obtain full value of current than the current-limiting device closes its
leading rkva capacity from the condenser. This is accom- contacts. One set of contacts initiates a timing cycle, and
plished by the differential field in the conventional main the other set deenergizes an auxiliary relay. Deenergizini
exciter, and by reversing the pilot exciter voltage in the the auxiliary relay allows the contacts of the voltage-
case of the Rototrol pilot exciter. regulating element to remain in control for the time setting
In the operation of a synchronous condenser under ab- of the timing relay, thus permitting the use of both normal-
normal conditions, a situation may occur where the con- and quick-response escitation for stability purposes under
denser does not have sufficient corrective rkva capacity to fault conditions.
handle all, or the most severe, system requirements. At Control of the excitation is automatically returned to the
such a time, the regulator in trying to hold the line voltage voltage-regulator control element when the overload dis-
overexcites the condenser, causing it to carry excessive appears. Should the decreasing overload remain for a time
current and become overheated. To protect against this below the setting of the instantaneous overcurrent relay
condition, a current-limiting device is used to limit the but within the setting of the current-limiting element, the
masimum excitation voltage to a level that does not cause latter maintains control to prevent increase in excitation.
damage due to continuous overloading of the condenser.
When the BJ regulator is used to control the excitation 23. Impedance-Type Voltage Regulator
of a synchronous condenser, a time-delay current-limiting The excitation system shown in Fig. 36 employs a main-
device is used. The equipment is designed to recognize two exciter Rototrol to supply excitation to the a-c generator.
conditions; first, the case of a slowly rising load current to With the high degree of amplification obtainable with a
a predetermined limiting or unsafe value, and second, a Rototrol, the energy requirements of the control field are
sudden increase in load current such as might be caused sufficiently small that they can be supplied by instrument
by a system fault. transformers. The intelligence transmitted to the control
Protection against overcurrent is provided by a current- field of the Rototrol as a function of the generator terminal
operated device having its operating coil energized by the voltage is determined by the voltage-regulator potential
line current and having its main contacts connected in unit, voltage adjusting unit, and automatic control unit.
series with the main control contacts of the voltage regu- These voltage-regulator devices consist entirely of imped-

I I EP

AUTO.
CONTROL J

:II
EN EP
MINIMUM
VOLTAGE
ADJUSTING
UNIT

1 ;i
Fig. 36-Block diagram of the impedance-type voltage regulator as used in a main-exciter Rototrol excitation system.‘!
A
Chapter 7 Excitation Systems 22s

sncc elements and from this consideration the combination Potential Unit-The voltage-regulator potential unit,,
cf devices in Fig. 36 is referred to as an impedance-type shown schematically in Fig. 3’i, consists of a potential
or static-type voltage regulator. transformer, a filter reactor and a set of resistors. The
The voltage regulator potential unit is energized by the output voltage of the potential unit is directly proportional
gcner:btor line-to-line voltage and the currents of two to the positive-sequence component of the generator ter-
nhases. Its output is a single-phase a-c voltage, applied minal voltage, and therefore, the voltage regulator is not
to the series connection of the voltage adjusting unit and affected by generator voltage unbalance and regulates to
the automatic control unit. The automatic control unit is constant positive-sequence voltage. The circuit is a nega-
:L voltage-sensitive device, the output of which is a d-c tive-sequence voltage-segregating filter so connected that
voltage. The polarity and magnitude of this d-c voltage the negative-sequence voltage is subtracted from the line
;uc determined solely by the magnitude of the impressed voltage which, in the absence of a zero-sequence component,
a-c voltage. The output of the automatic control unit is yields positive-sequence voltage.
the control signal that energizes the control field of the The primary of the filter or mutual reactor is energized
main-exciter Rototrol. by the phase 1 and 3 current transformers. The flus
When the generator output voltage is exactly at the produced thereby induces a voltage in the secondary wincl-
rc,gulsted value, the output voltage of the automatic con- ing which is added vectorially to the phase-3 drop in the
trol unit is zero. If the generator voltage increases above
t,hc regulated value, the d-c output voltage is in the direc- Es1
t,iun to decrease the excitation voltage, working through \
the Rototrol exciter. When the generator voltage falls
below the selected value, the d-c output voltage of the
automatic control unit is in the direction to increase the
a-c generator excitation.
When the voltage regulator is not in service, manual
control of the a-c generator excitation is by means of the
man~ral control unit. To guarantee synchronous machine
steady-state stability, that is, insure adequate excitation
for all kilowatt loads, a minimum excitation unit is used.
‘I’he minimum excitation unit used with the Rototrol ex-
cimt’ion systems is of a form that provides a variable
minimum limit depending on the kilowatt load.
/
II
13 E23

(a)

ER= E,,+E,

(b)
(a)
@ ER
*, = -h+Ex,
ER ER /
EC
62

I = +EXI
Ex2 Exa 62

R ‘52

\:A- ERS En LOCUS-


\
Ex3
ER= E,2 + E,
(b)
(cl
Fig. 37--Impedance-type regulator potential unit.
Fig. 3S-Vector diagrams showing how cross-current com-
(a) Schematic diagram. pensation is obtained with the potential unit of the imped-
(b) Vector diagram. ance-type regulator.
226 Excitation Systems Chapter 7

resistor RC, the sum being proportional to the negat,ive-


sequence voltage at the gcnerntor terminals. This negative-
sequence voltage is the component of the three-phase volt-
age that represents the unbalance in voltage resulting from
INSULATING
load unbalance. It is subtracted vcctorinlly from the gen- TRANSFORMER
erator voltage to give the desired positive-sequence voltage
across the terminals Vll and V12. VII0
The potential unit can also provide compensation for
parallel operation of a-c generators when each machine is
equipped with a voltage regulator. Reactive-droop com-
VI20
pensation is obtained by adjustment of the resistance RC
in the potential unit in Fig. 37. The vector relations of
the generator line currents and terminal voltages are shown
in Fig. 38 (a). If the ohmic value of the resistor RC is 100
percent, the voltage equation of the circuit and the vector

(0)
diagram are those shown in Fi g. 37. If the ohmic value of
RC is reduced to 50 percent, the vector diagram becomes
that shown in Fig. 38 (b). En and El2 no longer are iden-
tical, although for unity power factor their difference in
magnitude is of negligible proportion. The difference vec-
tor EC can appropriately be called the reactive-droop
compensator voltage. Assuming a given lagging power
factor generator load, the vector diagram of Fig. 38 (c)
shows how the generator terminal voltage E,, must vary
for the automatic control-unit input voltage ER to remain
.---------------
--- _
A.
constant. As the generator load increases, EC also increases E+L

and El2 must decrease, since ER remains constant in mag- E


nitude. Thus the generator voltage is given a drooping E-i
characteristic with increase in lagging power factor load.
Voltage Adjusting Unit-The voltage adjusting unit
in Fig. 36 is a rheostat that enables the operator to set the
a-c generator regulated voltage at any value within a band
of plus or minus 10 percent of the rated generator voltage.
By means of the voltage adjusting unit, the resistance
between the generator terminals and terminals Vll and
V12 of the automatic control unit can be changed, causing I P-

L-.
a directly proportional change in voltage drop in the cir-
I ’
lrl 1
cuit. The drop requires a change in a-c generator voltage
to produce the regulator balance-point voltage across the
terminals Vll and V12. ‘cl 1 kh lrh
!
Automatic Control Unit-The automatic control AMPERES
unit is the voltage-sensitive element of the impedance-type Fig. 39-Impedance-type regulator automatic control unit.
voltage regulator. It measures the voltage to be regulated (a) Circuit diagram.
and delivers energy to the main-exciter control field only (b) Intersecting impedance characteristics of saturating reactor,
when necessary. The voltage-sensitive circuit in Fig. 39 and capacitor.
consists essentially of two parallel-circuit branches; one
containing a capacitor and the other a saturating reactor. dry-type rect,ifiers, which are connected with additive re.
The voltage-current characteristic curves of the capacitor lation in series through a resistor and smoothing reactors.
and saturating reactor are shown in Fig. 39 (b). The curve The control field of the Rototrol is connected between a-
of the reactor indicates that its current increases more mid-tap on the resistor and the opposite side of the rectifier,
rapidly than voltage, and the currents through the two circuit. When the applied voltage is
branches of the circuit are equal at only one value of volt- and the capacitor and reactor currents are equal in
age where the characteristics intersect. This point of inter- tude, the output currents of the rectifiers are
section is called the balance point of the two impedances.
‘The operation of the voltage regulator depends upon the
fact that when the voltage increases above this point, the of the Rototrol control field and no current flowsin th
current in the reactor is greater than the current in the Should the a-c voltage become low, however, th
capacitor. When the voltage decreases below the balance current of the capacitor circuit is large compared
point, the capacitor current is the greater. of the reactor circuit raising the potential of term1
The output of the reactor circuit and the output of the above that of ACT, and causing current to flow in
capacitor circuit are rectified by single-phase full-wave trol field in a direction to increase the excitation voltage
chapter 7 Excitation Systems 227

r&c the a-C voltage. For an increase in a-c voltage, the


direction of current flow in the control field would be
reversed causing a reduction in excitation voltage. Thus
,j.ith normal U-C voltage applied to the automatic control
urrit, t,hc control-field current is nearly zero and any dcvi-
ation in a-C voltage causes a corrective current to flow in
the control field.
‘The current in the control field of the Rototrol is directly
,,roportional to the horizontal difference between the ca-
I,:Lcitor and saturating reactor volt-ampere characteristics
in Fig. 30 (b). Examination of the curves shows that the
com,rol-field current is approximately proportional to the
iTHREE-LEGGED
SATURATING
REACTOR

O-LEAD

O-LAG
Fig. 41-Schematic diagram of the impedance-type minimum
excitation unit and vector diagram showing how variable
minimum limit is obtained.

The schematic diagram and vector diagram of the min-


imum-excitation unit is shown in Fig. 41. A saturable
reactor with coils on the three legs of a B-shaped core
-200 -100 0 100 200 300
is used. The two outside legs are connected in parallel,
-300
AUTOMATIC CONTROL UNIT OUTPUT such that at any given instant, both windings produce an
MILLIAMPERES a-c flux in the same direction through the center leg of the
Fig. 40-Typical output curve of automatic control unit as core. The winding on the center leg is the d-c control coil.
function of a-c voltage. The d-c current in this winding controls the saturation of
the iron core, thereby controlling the inductance and react-
change in a-c voltage for small changes. The control-field ance of the two outer a-c windings. When the d-c control
c:llrrcnt as a function of the a-c voltage applied to the current is low, saturation of the core is slight, and the
:ultomatic control unit is shown in Fig. 40. Maximum cur- reactance of the a-c coils is high; and when the d-c current
rent in the direction to raise the Rototrol terminal voltage is high, the core has a higher degree of saturation and the
occurs when the a-c voltage is approximately 85 percent reactance of the a-c windings is low.
of the balance-point voltage. The small current output of The center-leg winding is energized by the main-exciter
the :uitomatic control unit is sufficient to control the Roto- Rototrol output voltage as shown in Fig. 36. When the ’
t ml output over the entire range of the Rototrol capability. a-c generator is operating at normal voltage and the excita-
Minimum Excitation Unit-Like other units of the tion voltage is normal, the current in the reactor control
irnncdnnce-type voltage regulator, the minimum-excitation winding is relatively high, and consequently the reactance
unit normally used is comprised of impedance elements. of the a-c windings is low. A substantial amount of a-c
The minimum-excitation unit establishes a minimum current is allowed to flow through the reactor windings
Point or limit below which the excitation of the a-c gen- under this condition. The relatively high a-c current
cmtor cannot be lowered. The minimum point can be a through resistor Rl causes a large voltage drop such that
fixed limit or a variable limit. On machines that carry the a-c voltage appearing across X-Y is relatively small.
considerable real or kilowatt load it usually is desirable to When the voltage is low across the,series circuit composed
make the minimum limit vary approximately directly pro- of the saturating reactor, capacitor and rectifier, current
portional to the kilowatt load, thereby maintaining a mar- in the series circuit is substantially zero. However, because
gin of excitation current above that at which the machine of the impedance characteristic of this series circuit, there
would pull out of synchronism. Since the -main-exciter is a voltage at which the series-circuit current begins to
Rototrol is limited to use with 3600-rpm turbine gener- increase rapidly with small increases in voltage.
ators, the minimum excitation unit is of the variable-limit If for some reason system conditions should cause the
type. voltage regulator to introduce current into the control field
228 Excitation Systems Chapter 7

of the Rototrol to reduce the excitation voltage, the current


in t,he reactor control winding is also reduced. The re-
actnncc of the a-c windings increases, and the current
through resistor Rl is reduced, causing less voltage drop
in the circuit and increasing the voltage across X-Y. If
the volt>nge across X-Y rises to the conducting point of the
series circuit, a-c current increases sharply in this circuit,
and this current rectified is supplied to the minimum ex-
citation control field of the Rototrol exciter. The minimum
excitation control field is the limits field in Fig. 36. The
direct current supplied to the minimum excitation control
field is in the direction to raise the excitation voltage, and
the minimum excitation unit thus begins to regulate for a
preset minimum excitation voltage to keep the circuit of
the unit balanced. When system conditions cause the auto- -I
CURRENT
matic control unit to increase the excitation above that
provided by the minimum excitation unit, the regulator (a)
again takes control and holds the voltage for which it
is adjusted.
The variable minimum excitation limit is obtained by
the compensating circuit shown in the left-hand portion of
Fig. 41. The voltage El? across terminals Vl-V2 is held
constant by the automatic control unit under balanced
load conditions. A compensating voltage that is a function
of line currents 12-11is added vectorially to El2 such that
the a-c voltage applied to the saturating reactor is equal
to EC. The currents 1, and Iz in the vector diagram of
Fig. 41 are drawn for the unity power factor condition and
the resulting magnitude of EC is represented by the vector
drawn with a solid line. If the magnitudes of the line
currents are held constant and the power factor changed
to 70 percent lagging, the voltage ERzl is shifted such that
the magnitude of EC becomes that represented by the
dotted vector. Thus, the magnitude of the voltage EC is CURRENT
dependent on the magnitude of the in-phase component
Fig. 42-Volt-ampere characteristics of individual compo-
of the line current, and hence varies with the kilowatt load nents of minimumexcitation unit and combined volt-ampere
on the generator. The locus of the magnitude of EC for a characteristic. c
particular magnitude of current at various power factors
is represented by the semi-circle as shown. Therefore, since (n) Effect of RZ omitted.
the voltage input to the saturating reactor is a function of (b) Effect of Rl included.
the kilowatt load, the voltage across X-Y applied to the
series circuit also varies with kilowatt load. The minimum of O-300 milliamperes, and the other giving an operating
excitation limit becomes a variable quantity dependent range of O-750 milliamperes. The unit having the larger
upon the kilowatt load of the generator. operating range is used with the main-exciter Rototrol.
The individual and combined volt-ampere character- Manual Control Unit-The manual control unit used
istics of the saturating reactor, capacitor and resistance with the main-exciter Rototrol excitation system of Fig. 36
(equivalent resistance of the reactor, rectifier and load) is a bridge-type circuit as shown in Fig. 43. Such a circuit
are shown in Fig. 42 (a). As the voltage across X-Y is is required to reverse the direction of current in the control
increased, the combined characteristic shows that the cir- field as required to raise or lower the Rototrol voltage. In
cuit conducts practically no current until the voltage E1 is addition, the unit is a d-c voltage regulator in itself, main-
reached. The current then undergoes a large increase to taining essentially constant main-exciter voltage and con-
the value 11. When the volt-ampere characteristic of the stant a-c generator voltage for a given load.
resistor Rl is included, the combined characteristic ismodi- The bridge circuit consists of two fixed resistors, a
fied to that shown in Fig. 42 (b). The sudden large increase potentiometer and two selenium rectifiers connected as
in current shown when voltage E1 is reached in Fig. 42 (a) shown. The main exciter terminal voltage is applied across:
is eliminated, but the current increases rapidly and linearly two terminals of the bridge and the control field of the
with increase in voltage in the range above E,. The prac- Rototrol is connected across the other two terminals. Thd
tical operating range of the unit is determined by the exciter terminal voltage is adjusted by changing the posi-,l
intersection of the capacitive reactance line Xo with the tion of the potentiometer. The selenium rectifiers form the,
saturating reactor line Xs. Two ratings of minimum-ex- controlling element of the bridge circuit since the voltagil
citation units are available; one giving an operating range drop in this leg of the bridge is practically independent oft
9i
Chapter 7 Excitation Systems

EN MAIN EXCITER EP
TERMINAL VOLTAGE
---INDIRECT ACTING EXCITER RHEOSTAT1
TYPE “EJ-30” REGULATOR

CYCLES- y 3,O 6,O 9,O 120 150 180 2iO 240 270 300
Fig. 43--Schematic diagram of the impedance-type regulator
manual control unit. SECONDS-O + I 1; h & i & d, d; b

Fig. 44-Voltage-recovery performance of main-exciter Roto-


the current through the rectifiers, and will remain sub- trol excitation system compared with performance of con-
stantially constant. Thus the voltage E, in Fig. 43 can be ventional main-exciter system under control of BJ regulator.
considered constant. Approximately 20 percent of generator rated amperes at 0
percent lagging power factor added at zero time.
For a given setting of the potentiometer, the bridge
circuit is balanced when the voltage El is equal to Ez and
nndcr this condition there is no current in the Rototrol cause approximately 20 percent of rated generator amperes
control field. If the main exciter voltage should increase to flow in the circuit. The rapid recovery of the voltage
for any reason, the current through the bridge increases, under control of the impedance-type regulator and mnin-
which increases the voltage drop El so that MCR is positive exciter Rototrol is an important factor in maintaining
\vith respect to MCL. Current then flows in the control system stability, particularly during the period of over-
field in a direction to reduce the exciter voltage until the shoot when the generator voltage is greater than 100
bridge circuit is again balanced. For a drop in. exciter percent.
voltage, the control field current would be in the raise The main-exciter Rototrol excitation system has the
direction. Thus, the a-c voltage may be adjusted for any advantage of a voltage regulator without moving parts,
value from zero to maximum, and the manual control unit without contactors, and requiring no large motor-operated
holds the excitation voltage constant. main-exciter field rheostat. The overall performance of the
system shows marked improvement in voltage dip and
24. Main-Exciter Rototrol Generator Excitation recovery time when compared with a conventional main-
System exciter excitation system. The system also eliminates the
The Rototrol with its two stages of amplification can be use of any pilot exciter.
built with large power output capabilities while the control
field energy requirements are sufficiently small to be sup- 25. Rototrol Pilot Exciter with Single-Field Main
plied by instrument transformers. Also, since the Rototrol Exciter
is a high-speed machine with air-gap dimensions the same The simplest form of an excitation system using a Roto-
as any other form of d-c machine, it can be direct-connected trol pilot exciter is shown in Fig. 45. When the speed of
10 the shaft of a turbine generator. The direct-connected rotation of the main a-c generator is 1200, 1800 or 3600
main-exciter Rototrol is a step toward simplification of rpm, the main exciter and Rototrol pilot exciter can be
turbine generator construction, operation and maintenance direct-connected to the generator shaft. A second possi-
1)~completely eliminating the pilot exciter. The circuit of bility is to have the main exciter mounted on the shaft of
the main-exciter Rototrol excitation system is that shown the a-c generator and the Rototrol separately-driven by a
in Fig. 36. small motor, the m-g set having sufficient inertia to carry
The effect on the main-exciter Rototrol of induced field through system disturbances without appreciable speed
current caused by changes in generator load was discussed change. This arrangement might be used where the gen-
in Sec. 10. Evidence of the importance of this effect and erator speed is less than 1200 rpm. A third arrangement is
illustration of the comparative performance of the main- to have the main exciter and the Rototrol pilot exciter
exciter Rototrol excitation system is given in Fig. 44. The driven by a motor and operating at 1200 or 1800 rpm.
solid line shows the time variation of the a-c generator The latter arrangement is applicable with a generator of
voltage under control of an impedance-type regulator and any speed.
a main-exciter Rototrol, and the dashed-line curve shows In the conventional excitation system, the pilot exciter
the variation under control of an indirect-acting exciter- is a constant-voltage generator. The Rototrol pilot exciter
rheostatic type of regulator and a conventional main ex- is a variable voltage pilot exciter and the method of operat-
citer with 0.5 response ratio. In each case, a three-phase ing the excitation system of Fig. 45 is essentially no differ-
reactance load was suddenly applied to the generator to ent than the operation of conventional exciter-rheostatic
“30 Excitation Systems Chapter 7
systems, except that no regulator-controlled, motor-oper- SELF ‘-ENERG.
MAIN EXCITER
ated csciter-field rheostat is used. Variable voltage is sup- ROTOTROL <SERlm ES FLD.
CONTROL &V-l-,
plied to t,he main-esciter field by the Rototrol pilot exciter,
which is connected directly to the field and is under the
control of the voltage regulator automatic control unit or
the manual control unit.
The voltage regulator potential unit, voltage adjusting
unit, automatic control unit and the manual control unit
are those described in Sec. 23.
The Rototrol pilot exciter used in this escitation system
can provide either one or two stages of amplification,
depending on the energy requirements of the main-exciter
shunt field. The Rototrol can easily be constructed to
provide rates of response and ceiling voltage equal to or A
in excess of those obtained with conventional d-c machines.

SELF-ENERG. Fig. 46-Excitation system with Rototrol buck-boost pilot


exciter and three-field main exciter.

citation in the main exciter, and the excitation provided


by field 2 adds to or subtracts from this base excitation
to vary the output voltage. Thus the Rototrol must be
capable of bucking or boosting the main exciter base ex-
citation to give the necessary range of main exciter voltage.
The Rototrol-excited field of the main exciter also acts as
a stabilizing field under regulator control.
All of the voltage regulator component parts in Fig. 46
are those described in Sec. 23. The manual control unit is
not required, since manual control is obtained by operating
the main exciter as a self-excited exciter with a stabilizing
field, and voltage control is by means of the shunt-field
Fig. 45-Excitation system with Rototrol pilot-exciter and rheostat.
single-field main exciter controlled by impedance-type Since the main exciter base excitation is supplied by the
regulator. self-excited field, complete excitation is not lost or is the
continuity of the load disturbed upon the occurrence of
The excitation system shown in Fig. 45, therefore, provides any trouble in the Rototrol buck-boost pilot exciter fir-
performance characteristics at least equal to those obtained cuits or in any part of the impedance- type voltage regu-
with conventional excitation systems. lator elements. Even in the event of a short circuit or open
The Rototrol pilot exciter in Fig. 45 supplies all the circuit in the pilot exciter output circuit, the preset base
excitation requirements of the main exciter. In this respect excitation remains rheostat controlled and undisturbed.
this system is identical with exciter-rheostatic systems If a circuit failure occurs when the a-c generator is carrying
using pilot exciters. The essential advantage is the elim- a load other than that used to determine the rheostat
ination of the comparatively complicated exciter-rheostatic
regulator with its moving parts and elimination of the MAIN EXCITER _._--
SHUNIT FIELDS UISIK.
motor-operated main-exciter field rheostat. As is the case -- I C.T TRANSE
with the excit,er-rheostatic excitation system, loss of the 71 .-.J”$ , 1 \
r-4 ‘: 5ch ,-hi
pilot exciter through a short circuit or open circuit causes
loss of excitation on the a-c generator.
26. Rototrol Buck-Boost Pilot Exciter
The buck-boost Rototrol excitation system using a two-
or three-field main esciter, as shown in Fig. 46, offers a
number of advantages over the single-field main exciter
system described in Sec. 25. In the system of Fig. 46, the
Rototrol pilot exciter operates in a different manner from
that in Fig. 45.
The operation of the three-field main esciter was de-
scribed in Sec. 6. The Rototrol buck-boost pilot exciter I J
supplies the proper voltage to field 2 of the main exciter
Fig. 47--Excitation system for hydroelectric generator with )
to control the output voltage. Briefly, the excitation pro- motor-driven Rototrol buck-boost pilot exciter and three-
vided by field 1 is set by the operator to give a base ex- field main exciter.
Chapter ‘7 Excitation Systems 231

setting, the a-c generator continues to carry its kilowatt excitation system must he capable of supplying full es-
load, but at a different power factor. citation to the generator field. With the system shown in
Fig. 47, this is accomplished by building sufficient inertia
27. Rototrol Excitation for Hydroelectric Gener- into the Rototrol m-g set to carry it through such disturb-
ators ances with very little change in speed even under severe
it is impractical to direct-connect the Rotot,rol to the forcing conditions.
&aft of a waterwheel generator, because of the multiplicity
(If speeds and sizes involved. The Rototrol pilot exciter, 28. Rototrol Excitation for Synchronous
therefore, must he driven by a small motor, introducing Condensers
the prohlem of a reliable power supply for the driving The Rototrol escitation system for synchronous con-
motor. The three-field main exciter and Rototrol huck- densers is similar to that shown in Fig. 47 for waterwheel
t,oost pilot exciter excitation system of Fig. 46 is readily generators. However, in the usual case, the main exciter
&ptnble to use with slow-speed generators and is shown for the condenser is also motor-driven so t,hat the motor
in Fig. 47. supply circuit has to be modified to supply sufficient power
During start-up of the generator when no outside source for the motor-generator set. Electrically, the circuit is the
of supply is availahle for driving the Rototrol motor- same as Fig. 47, hut the main and pilot exciters arc
generator set, the main exciter is operated as a self-excited normally on the same shaft and driven by a large motor.
machine and provides excitation for the main generator. Where some form of current limit is desired as discussed
As soon as a-c voltage is available, the Rototrol can he in Sec. 22, a static current-limit device can he used with
stnrtcd and the voltage regulator placed in service, or the Rototrol excitation system. The circuit of the current-
operation can he continued under hand control with the limit unit is similar to that of the minimum escitation unit
operator controlling excitation with the self-excited shunt shown in Fig. 41. The rectified a-c load current of the
field rheostat. condenser is used to energize the center or control winding
Under short-circuit conditions on the a-c system, the of the three-legged reactor, and to control the magnitude
TO DAMPING
TRANSFORMER y I I I I O-24
1
VARIABLE
NEGAT IVE
BIAS i
I
o-t . 25
+

I 1 REFERENCE 1 1 1
- VOLTAGE -

II 1

SL Ii L

-t

Y3GT

A-C GENERATOR
VOLTS
POTENTIAL
FROM
TRANSF.
M TI T2
i
Fig.48-&h ematic diagram of the electronic generator voltage regulator. The variable output appearing across terminals
24 and 25 can be used to control the 5ring point of an electronic main exciter or can be adapted to control a Rototrol
excitation system.
5
i
i
232 Excitation Systems Chapter 7 :

of the volt.age applied to the series reactor-capacitor- to the grid of the BVGGT tube. The grid circuit of the
rectifier circuit. At a certain magnitude of a-c current, GVGGT tube can he traced from the grid through resistor
the series circlIit begins conducting a rapidly increasing R7 to the cathode. The variable negative d-c voltage out-
current, which is applied to the limits field of the Rototrol. put of the regulator is obtained across the load resistor R9
The current in the limits field is in the direction to lower of the 6V6GT tube and applied to the grid circuits of the
the excitation voltage. Should the control field be con- thyratron firing tubes in Fig. 23.
ducting current in the raise direction, the combined effect Under balanced conditions when the a-c generator volt-
of the two fields is such that the excitation voltage is held age is equal to the regulated value, the grid of the 5693
constant at the limiting value. Time delay can be provided tube is established at a particular bias voltage depending
in the limiting circuit to enable full forcing of the condenser on the magnitudes of the reference voltage and the rectified
escitation during transient overloads. a-c voltage. This grid bias establishes the current in the
5693 tube and the drop across IU, which in turn establishes
29. Electronic-Type Voltage Regulator the grid bias of the GVGGT tube. Current in the 6V6GT
I%zctronic-type voltage regulators are available in many tube is thus fixed, as is the drop across load resistor R9.
dif’frrent forms, a typical one being shown in Fig. 48. This The voltage output is constant as long as the a-c generator a
particular regulator is used with the electronic main exciter voltage is equal to the regulated value.
in Fig. 23, but it can be modified for use with Rototrol Should the a-c generator voltage increase above the
escitntion systems. normal value, the differential connection of the rectified
A d-c voltage proportional to the average three-phase generator voltage and the reference voltage makes the grid
a-c generator voltage is obtained from a three-phase bridge- bias of the 5693 tube more negative than previously, which
type rectifier, the output of which is applied to a voltage- reduces the current in the tube and in resistor R7. The
adjusting rheostat and a modified Wein bridge-type filter. lower voltage drop across R7 reduces the negative bias
The bridge, comprising resistors RI, R2, Rs and R4, capac- voltage on the grid of the GVGGT tube and causes an
itors Cl and C%’and potentiometers P2 and PS, filters the increase in current through the tube and load resistor R9.
3GO-cycle ripple voltage in the d-c output of the rectifier. Thus, the negative voltage output across terminals 24 and
Thus, the output of the bridge circuit, which is the input 25 is increased. Reference to Fig. 24 shows that the in-
to the regulator, is a smooth d-c voltage. The bridge-type crease in negative-bias voltage on the thyratron firing
filter provides a high degree of filtering without adding tubes causes an increase in the angle of grid delay, which
unduly long time constants to the regulator input circuit. reduces the main-exciter voltage. In a similar manner, low
The generator voltage regulator consists of two d-c a-c voltage causes the grid bias of the 5G93 tube to be less
amplifiers and a reference voltage. Regulation is obtained negative than previously, which causes a reduction in the
by comparing the rectified generator terminal voltage with voltage across terminals 24 and 25 and a consequent
the reference voltage. The first d-c amplifier is a high-gain reduction in the thyratron firing tube angle of grid
voltage amplifier using a 5693 tube, which is an industrial- delay.
type tube with characteristics the same as a type GSJ7 c
i.
tube. The output of the voltage amplifier is fed into a REFERENCES /G
power amplifier using a GV6GT tube. The high-gain volt- .yi
r’ :g,
age stage gives the regulator its high degree of sensitivity 1. Quick-ResponseExcitation, by W. A. Lewis, The Eleclnc
and the power amplifier supplies the variable negative bias Journal, Vol. 31, August 1934, pp. 308-312.
voltage for controlling the thyratron firing tubes in Fig. 23. 2. Determining the Rstio of Exciter Response,by A. vnn Siekerk,
A full-wave rectifier (5Y3GT tube) is used to supply the The Electric Journal, Vol. 31, September 1934, pp. 361-364.
plate voltage of the 5693 tube. The rectified output of 3. The Exciter-Rheostatic Regulator, by A. G. Gower, Jr., The ‘C
Electric Journal, Vol. 32, February 1935, pp. 73-75. !J
transformer 1’1 is fed into a two-section condenser input
4. The Generator Rheostatic Regulator, by A. G. Gower, Jr., The
filter giving a smooth d-c voltage with polarities as indi- Electric Journal, Vol. 32, April 1935, pp. 143-144.
cated. The d-c reference voltage is obtained from the 3. Recent Developments in Generator Voltage Regulators, by C.
voltage drop across a type VR-105 voltage regulator tube R. Hanna, K. A. Oplinger and C. E. Valentine, A.I.E.E. Trans-
connected in series with resistor R6 across the d-c power adions, Vol. 58, 1939, pp. 838-844.
supply. The reference voltage is also a smooth d-c voltage G. Static Voltage Regulator for Rototrol Exciter, by E. L. Harder
that remains constant for wide variations of supply voltage. and C. E. Valentine, A.Z.E.E. Transactions, Vol. G-1, 1945, pp.
The rectified generator voltage is connected differentially 601-606.
n-ith the reference voltage and applied to the grid circuit 7. The Multistage Rototrol, by M. M. Liwschitz, A.I.E.E. Tram-
of the 5693 tube. This circuit can be traced from the grid aclions, Vol. 66, 1947, pp. 564-568.
of the tube through the grid resistor R5 to the negative side 8. Two-Stage Rototrol for Low-Energy Regulating Systems, by
A. W. Kimball, A.I.E.E. Tt-ansaclions, Vol. GG, 1947, pp. 1507-
of the rectified generator voltage; from the positive side of
1511.
i he rectified generator voltage to the positive side of the 9. Rototrol Excitation Systems, by J. E. Bnrkle and C. E. Valen-
wference voltage; and from the negative side of the refer- tine, A.I.E.E. Tranmtions, Vol. 67, 1948, pp. 529-534.
ence voltage to the cathode of the 5693 tube. The amplified 10. IMain Exciter Rototrol Excitation for Turbine Generators, bY
voltage from the 5693 tube appears across the load resistor C. Lynn and C. E. Valentine, A.I.E.E. Transactions, Vol. 67,
tz?’ with polarities as shown and this voltage drop isapplied 1948, pp. 535-539.
CHAPTER 8

APPLICATION OF CAPACITORS TO POWER SYSTEMS


Aulhor:
A. A. Johnson

The shunt capacitor affects all elect,rical equipment and


I. SHUNT CAPACITOR FUNDAMENTALS
circuits on the source side of where they are installed. If
HE function of a shunt capacitor applied as a single the capacitor kvar is small, say ten percent of the circuit

T unit or in groups of units is to supply lagging kilovars


to the system at the point where they are connected.
.I shunt capacitor has the same effect as an overexcited
rating, it is usually sufficient to make an analysis on the
circuit involved for the application. However, where the
capacitor kvar is large, its effect on each part of the system
synchronous condenser, generator or motor. It supplies back to and including the source should be considered.
the kind of kilovnrs or current to counteract the out-of- In determining the amount of shunt capacitor kvar re-
phase component of current required by an induction quired, it must be recognized that a voltage rise increases
motor as illustrated in Fig. 1. the lagging kvar in the esciting currents of transformer
and motors. Thus, to get the desired correction some addi-
ES Z=R+jX =F EM I, tional capacitor kvar may be required above that based on
-
initial conditions without capacitors. If the load includes
m : -0 synchronous motors, it may be desirable, if possible, to
-FEEDERS IND
MOT increase the field currents to these motors.
GEN xc’ Shunt capacitors are applied in groups ranging from one
1= SHUNT CAPACITOR
capacitor unit of 15 kvar to large banks of these standard
units totaling as much as 20 000 kvar. Many small banks
EM of 4.5 kvar to 360 kva are installed on distribution circuits.
Banks of 520 kvar to about 3000 kvar are common on
distribution substations of moderate size. Larger banks of
1, 5000, 10 000 and 15 000 kvar are in service in a number of
Q-- larger substations. Usual voltage ratings of capacitor
banks star> at 2400 volts and range upward for groups of
capacitors connected in series for 36 kv. Consideration is
Fig. l--Shunt Capacitors supplying kvar required by an in- being given to voltages up to and including 138 kv. This
duction motor. is feasible provided the bank is sufficiently large in kvar.
Shunt capacitors applied on the load end of a circuit
slIpplying a load of lagging power factor have several 1. History
(‘l’fects, one or more of which may be the reason for the
Shunt capacitors were first applied for power-factor
:Ipplication:
correction about 1914. Their use, however, was limited
I. Reduces lagging component of circuit current,.
during the next twenty years because of high cost per
2. Increases voltage level at the load.
3. Improves voltage regulation if the capacitor units are
kvar, large size and weight. P$?$‘to 1932 all capacitors
properly switched. employed oil as the dielectric. At about this time the in-
4. Reduces PR power loss in the system because of reduction troduction of chlorinated aromatic hydrocarbon im-
in current,. pregnating compounds (askarels) and other advances in
5. ReducesZ*Xkilovnr loss in the system because of reduction the capacitor construction brought about sl’@$?eductions
in current. in size and weight. As shown by Fig. 2 the present weight
f~. Increasespower factor of the source generators. per kvar is less than 5 pounds compared with over 20
7. Decreases kva loading on the source generators and cir- pounds in 1925.
cuits to relieve an overloaded condition or releasecapacity Before 1937 practically all capacitors were installed in-
for additional load growth. doors in industrial plants. Extensive utility use started
3. By reducing kva load on the source generators additional after the appearance of outdoor units, which eliminated
kilowatt loading may be placed on the generators if tur-
bine capacity is available. steel housings and other accessories. By 1939 capacitor
9. TO reduce demand kva where power is purchased. Correc- costs had been reduced almost proportionately with weight
tion to 100 percent power factor may be economical in and they had been proved in service. Starting in 1939 and
somecases. continuing to the present, capacitor use has increased
10. heduces investment in system facilities per kilowatt of phenomenally year by year, as shown in Fig. 2. The
load supplied. acceptance of capacitors has been due to the following:
233
234 Application of Capacitors to Power Qstems Chapter 8

7. Due to the large volume of production (luring the war and


since, the economics of using cnpscitors is fnvornble.

2. Capacitor Failure Rates


To evaluate the operation and ecaonomics of shunt
capacitors, it is helpful to predict the number of unit
failures that may occur. Sot only cl0 unit failures mean
the loss of the units but also, unc!cr certain conditions a
unit failure may damage other good units. Prediction of
failures can he based on past experience, such as given in
Curve A, Fig. 4. This clwve gives cumulative unit failures
per 1000 units in service regardless of how or where they
are installed or how they are protected. Curve 13 repre-
sents unit failures of small groups of capacitors distributed
over a system lvithout, lightning prot c>c*tionand subject to

‘is10 1918 1926 1934 1942 1950


YEAR
Fig. 2--Evaluation of the size and use of Shunt Capacitors.

1. Reduction in selling price.


2. Improved design and manufacturing methods resulting in
0
small size ant1 weight. 0 I 2 3 4 5 6 7 8 9 IO
3. Development of outdoor, pole-type units and standardized
YEARS IN SERVICE
mounting brackets.
4. Reduction in failures. Fig. 4-Failure rate of shunt capacitors.
5. Better understanding of system benefits that xcrue from
their use. c
A-Average of all types of installntions.
6. By force of circumstances, during the war emergency of
1939 to 1945, manufacturing facilities for capacitors lvere B-Average of unprotected, exposed instnll,ztions.
more available than other means of supplying kilovnrs. C-Average of well protected larger installations.
Also less critical material was required for capacitors thnn
for other kvnr generators.
other hazards. In view of the benefits a performance as
given by Curve I3 has been considered economical and
satisfactory. Curve C represents performance of large
banks of capacitors where careful attention has been given
to operating conditions and protective devices. For such
performance each unit should be inspected and tested at
the installation to weed out units damaged in transporta-
tion. Individual capacitor fuses are also essential
for best performance as discussed later under Capacitor
fusing.

3. Fundamental Effects
To illustrate the effects of shunt capacitors, assume that
a lOO-kva circuit or piece of apparatas has to carry 100 kva
at various power factors. By adding shunt capacitors at
the load, the kva from the source is reduced materially.
Fig. 3-Cut-away view of 25 kvar 2400 volt outdoor capacitor The lower the load power factor, the more effective the
unit. capacitors are. This situation is illustrated in Fig. 5.
Chapter 8 Application of Capacitors to Power Systems 235

gests. (If the load should be 10 000 kva at 70 percent


power factor, then adding 4000 lcvar of wpacitors permits
the km to be increased from fO’)O t,o S700 nithollt incrcns-
ing the circuit loatling above IO 000 kva. The load kva can
thus be incrrnsetl to 12 400 kva at 70 percent power factor.)
(4)
Shunt capacitors can be vicwcd in two lights. &Adding
INCREASE IN LOAD KVA capacitors releases circuit capacity for more load, and
adding capacitors relieves overloaded circuits.
The capacitor kvnr per kva of load increase, Fig. 5(E), is
of particular interest, because multiplying this quant,ity by
the cost per capacitor kvnr, the product is the average cost
of supplying each additional kva of load. This cost, neglect-
ing other advantages of the capacitor, can be compared
with the cost per kvs of increasing the transformer or
supply circuit rating. Thus if the load power fwtor is 70
percent and a capacitor kvar of 40 percent is added, the
capacitor kvar per increase in kva of the load is 1.65. If
capacitor cost is $7.00 per kvar, then the increase in
ability to supply load is obtained at a cost of 1.65 timrs
J7.00 or $11.55 per kva. The incremental cost of adding
transformer capacity may be much greater per kva 07
increased capncit,y.
The same data apply equally well to any equipment
other than transformers in which current might constitute
a limiting factor such as generators, cables, regulators, as
well as transmission and distribution lines.
In the example taken (Fig. 5) as the load through the
transformer approaches unity power factor, smaller and
smaller incremental gains in load are obtained for in-
cremental increases in capacitor kvar. The incremental
capacitor kvar required for an increment in kva of the load
is Fig. 5(F). Expressed mathematically, the ordinate in this

0
3I 90% F! F.
I
OF LOAD
,

CAP. KVAR IN % OF CIRCUIT KVA

Fig. 5-Fundamental effects of shunt capacitors on power


circuits.

Increasing the capacitors lessens the current carried by


tI)c supply circuit from the source (Fig. 5(D) ), up to the
Illtimate point at which capacitors supply al1 of the kilo-
VW required by the load and the circuit supplies only the
IciIon-att component. Icor a constant load in the circuit
adding Garious amounts of capacitors allows the useful
,, I, I I ; 60 eo too
IwI to be increased. By adding 40 kva of capacitors to a CAPACITOR KVA IN PERCENT OF CIRCUIT KVA
‘00-k~~ load of 70 pcrccnt power factor the load can be Fig. &Reduction in losses in the source circuit to shunt
i~~~~~~:wd from 100 kva to about 124 kvn,‘as Pig. 5(C) sug- capacitors.
236 Application of Capacitors to Power Systems Chapter 8

d (Cap. kvar) A I5 OOO-kva,70 percent power factor load is supplied over


curve is equal to These curves I5 miles of 33-kv circuit. Without shunt capacitors the
d (Increase in load kva)’
show that the final increment is attained at much greater generators must supply 19 900 kva at a power factor of 62
expense than the initial increment. percent, whereas with the use of 6000 kvar of capacitors the
Capacitors applied to a given load reduce the I*R and generator power factor is raised to 82 percent. The 6000
1*X loss in the supply circuit in accordance with Fig. 6 capacitor kvar reduces the loading on the generator by
For a 70 percent power factor load with 40 kvar of capaci- 5850 kva, which is almost equal to the capacitor kvar. The
tors added for each 100 kva of circuit capacity, the I*R and 12R loss in the circuit is reduced by about 800 kw (1900-
1% loss will be 59 percent of its former value. This loss in 1100) and the PX losses are reduced by about 1600 kvar
the particular circuit supplying the load can be calculated (4000-2400). Curves are also shown for half load or 7500
directly and may be a big factor, particularly if the circuit kva at 70 percent power factor.
impedance is high. The resistance and reactance losses are In the case cited, it is desirable to switch part or all of the
also reduced in all circuits and transformers back to and capacitors off during light-load periods. The voltage and
including the source generators. power factor at the generating end determine whether
To illustrate the effect of shunt capacitors applied to a switching in steps should be applied. As Fig. 7 indicates A
large load, the curves in Fig. 7 are shown where it is as- the voltage at the generator would have to vary from 13.8
sumed that the load bus voltage is maintained constant at kv at full load with 6000 kvar of capacitors to 12.1 kv at
4160 volts and the generator voltage varies with load. half load with 6000 kvar of capacitors, assuming a constant
voltage of 4160 at the load. By providing 3 steps of
4160 V capacitors and removing 4000 kvar from the system at i/z ’
13.6 KV
LOAD load, the remaining 2000 kvar gives a voltage of 12.9 kv at
15 MILE-33 KV
4/O ACSR
the generator; removing all capacitors from service, a
wt generator voltage of 13.4 kv is required for 4160 volts at the
15,000 KVA 15,000
1% KVA SHUNT
5% 5% T CAP. load.
P
GEN. KVA LOAD KVA LOAD P.F. CAI? KVAR 4. Voltage Drop
19,900 15,000 70 % 0
9,300 7,500 70 % 0 The voltage drop in feeders or short lines can be ex-
> l5- pressed approximately by the relation
Y
3 14-
Voltage drop = RI,+XIx (1)
2 where R is the resistance, X the reactance, I, the power
J 13-
?
component of the current, and 1, the reactive component
. l2-
E
0
ES ER
II- 7000 R X -LOAD=I.O PER UNIT
-FULL LOAD 1 1 /I 1 SOURCE’-
-I
-SHUNT CAPACITOR ~
I 1 I I I I/ I -,I.-lL=HL d1
L 1.0 - 6000 (a) Y
a’ c I JLAG
5 0.0 -
$
0.6 -

OA- VOLTAGE AT LOAD - ER


O&VOLTAGE AT SENDING END WITHOUT CAPACITOR-Es
OC- VOLTAGE AT SENDING END WITH CAPACITOR-Es
(b)
Fig. S-Effect of shunt capacitors on voltage drop in source
circuit.

as shown in Fig. 8. If a capacitor is placed in shunt across


the end of the line, the drop immediately decreases or the
voltage rises. The new voltage drop becomes approxi-
mately :
-0 2 4 6 0 IO Voltage drop = RI,+XI,--XI, (2)
SHUNT CAPACITOR KVAR X 1000
where I, is the current drawn by the capacitor. Thus if 10
Fig. 7-Effect of various amounts of shunt capacitors at full be made sufficiently large, both the RI, and the XI, drops
and half load on a practical system problem. can be neutralized. This expression also shows that if the
Chapter 8 Application of Capacitors to Power Systems 237
Es=l.05 ER
90, I , , ,

60 60

50

v/ Y / /
60
A/ /I/ A’

PERCENT CIRCUIT REACTANCE X PERCENT CIRCUIT REACTANCE X PE RCENT CIRCUIT REACTANCE X

Fig. 9-Shunt Capacitors required for various power factor loads to give 0, 5 or 10 percent voltage drop in the source cir-
cuit. All percent values are referred to full load kva as 100 percent base.

voltage drop is compensated at full load with permanently illustrate their use, assume a 20-mile, 33-kv line of 2/O cop-
connected capacitors, then at light loads I, and I, become per conductors which steps down through a 10 OOO-kva,T-
smaller and the line is over-compensated because I, is percent reactance transformer to 13.8 kv. Assume the full
(lcpendent only upon voltage and not upon load. Regula- load is 10 000 kva at 80 percent power factor. Also assume:
tion of the line is practically unchanged by the capacitor line impedance 9.62+j15.36 ohms or 0.0%36+jO.142 per
I)ecausethe capacitor effects an increase in voltage both at unit on 10 OOO-kva base; transformer impedance 0.008+
light load and at full load. At light loads the voltage rise jO.07 per unit; total impedance 0.096+jO.212 per unit.
might be so much in excess of normal as to represent an 0.096
‘indesirable or even intolerable condition; a solution is to Therefore, ratio R/X=0.212=0.45. Referring to Fig. 9
Provide manual or automatic switching to add or remove for R/X ratio of 0.45 and a circuit reactance of 0.212 per
8rOUPs of capacitors as desired. unit, the shunt capacitor kvar required for a 10 percent
The curves of Fig. 9 show the amount of shunt capacitor voltage drop on the line is 0.54 per unit. In this case 1.0
kvar required for loads of three power factors and for 0, 5 per unit is 10 000 so 5400 kvar of shunt capacitors are
and 10 percent voltage drop over the supply circuit. TO necessary. These data and the capacitor kvar required
238 Application of Capacitors to Power Systems Chapter 8

for 0 and 5 percent voltage drop are given in the following 6. Standard Ratings and Tests on Capacitors
table. In adtlition, calculated losses in the circuit are given, Tal)le 2 gives the standard ratings of capacitor units for
as wtll as the pwvcr factors nt the scntling (Es) and rc- indoor and outtloor typc,x. Table 3 gives t hc Standard
cei\.ing (I:‘n) cntls of t,he circrlit with t!he wlccted capwit;ol ratings of indoor and outdoor hor~sctl capacitors. Table 4
kvar in use. To give a more complete view of the llse of gives the factory test voltage \\hicti are npplicd to c,,-aci-
Fig. !) c~wves the shunt capacitor kvar required for 3OOO- tom.
kva %I-percent power factor 10x1 is included in Table 1. The average operating loss for capacitors, in kw, is one-
third of one percent of the kvar rating. Each capacitor has
TABLE I-DATA FOR 20 MILE 33 Kv LINE WITH TRANSFOR- a built-in high resist,ance device which automatically dis-
MATION TO 13.8 Kv LOAD BvS charges the capacitor for safety. The ambient temperature
Capncitors Percent TABLE ~-STANDARD RATINGS FOR INDOOR AND OUTDOOR
At, tlw T,o;~cl I Circuit I Potvcr Factor At HOUSED CAPACITORS BANKS
VOLTAGE AND KVAR RATINGS

4800-i200-7060
230 V 460-575 v 2400~-lIti v 12,4iO-13,800 V A
15 30 30 tioo* !I0 600'
30 GO 45 900 * 180 900”
45 00 GO 1500* 360 1500*
Es =E,c 1.Ol 5,050 194 94.0 Ic:td 58.9 lead 60 120 90 2100* 540 2100'
Es = 1.os EEL 0.50 2,500 156 0;. 9 1:1g on. 2 lag 00 1so 13.’ 2;00* 7’0 2iOO'
E=l.lO E 0.02 100 234 ii 5 lag 81 0 13R 135 270 180 3300* 1080 3300*
180 360 270 4200* 12GO 4200*
270 ,540 360 1440 5100"
For 5000 kva the circuit reactance is 0.106. The ratio 360 720 540 lSO0
R/X remains const,ant for all loads. Thus the capacitor 540 1080 $20 21G0
kvnr can he determined, for a given voltage drop in the 630 1260 1080 2520
circllit, for any part of full load by using the per unit I I 1260
reactance based on the partial load. *Using 25 KV.4R Units

5. Overvoltage on Capacitors TABLE ~-FACTORY TEST VOLTAGES ON CAPACITORS i’


Capacitors arc designed for operation on circuits whose
Voltage Terminal-to-
average voltage over a 24-hour period does not exceed the
Rating of Terminal
rntetl voltage by more than 5 percent. The variations Cnpnciton 3 Test Voltage Indoor
above the average may go to 115 percent in the case of 230, -~
#X3, and 575 volt capacitors, or 110 percent in the case of 230 500 3000
higher voltage unit)s. For short periods of time, shunt 460 1000 so00
capacitors can safely withstand higher voltages. For 575 1200 5000
2 400 so00 10 000
example, during the starting of large induction motors the
4 160 9000 19 000
voltage rating of capacitors applied in shunt with the
4 800 10 000 26000
motor may be as low as 67 percent of the voltage applied 7 200 15 000 26 000
to the motor, which means that the voltage applied to the 7 9GO IG 600 26000
capacitor is 150 percent of its rating. The maximum
momentary voltage, such as in welding applications, should
not exceed Ifi.5 percent of the rated voltage.
12 4i0
13800 I
25000
28SOO
.4pplication period: 3600 ryrles-
34000
34000
or 60 cydes.
I 34000
34000

TABLE 2 -STANDARD CAPACITOR RATINGS limit covering a11 capacitors is 40°C; for outdoor open
mounted units it, is .%‘C and for housed lmits between
I-__ Outdoor T,vpe 40°C and 50°C depending on rack type.
~-
Volts KVAR T Phase Volts KYAR Phlt%
230 5-7x l&3 230 1, 255, 5, 7,!4 1& 3
II. CAPACITOR ON INDUSTRIAL PLANT
4GO 10 & 15 l&3 460 5, 10 & 15 l&3 CIRCUITS
575 10 85 15 lh3 575 .5, 10 & 15 l&3
2 400 15 & 25
A capacitor can be installed in shunt with any load of
l&3 2400 10, 15 & 25 l&3
4 160 15 & 25 l&3 4160 10, 15 $ 25 l&3
lowpowerfuctor to supply the magnet,izing current required
4 800 15 & 25 l&3 4800 15 & 25 l&3 by the load. The load may be a single motor, or it may be
7 200 15 & 25 1 7200 15&25 1 a large industrial plant. The capacitor can be chosen to
7 060 15 & 25 i 7960 15&25 1 supply the magnetizing current under peak load conditions,
12 470 15 1 12470 15 1 or it can be chosen only large enough to supply the reactive
13 800 ( 15 1 13800 15 1 kva hours accumulated over the month. It can be located
Note: 25 KV.IR Units are only single phase at the service entrance, thus removing magnetizing current
Chapter 8 Application of Capacitors to Power Systems 239

fr()~nthe utility system only; or units can be applied to the 1. R%ere loads shift radically as to feeders.
individual loads, thus removing magnetizing current from : 2. Where motor voltages 3re low such as 230 volts.
the plant circuit also, reducing their loss, and increasing If the power flows from t,he service entrance to various
their load capacity, and better maintaining voltage at the widely-separated parts of the plant and if the loads shift
l0UlS. about a great deal from one feeder to another, the corrcc-
The selection of the capacitor size, and its location is tion may be needed first in one part of the plant and late
,[cpcntlcnt8 on what is to be accomplished. This varies with in another. A centrally-located group capacitor in this
case would be an advantage since it would tend to be the
same distance from the loads at all times.
If a group capacitor remains connected during light
loads the voltage rise is less if this capacitor is installctl at
or near the transformer hank since the reactance of the
plant circuits does not contribute to voltage rise. In this
case, application of capacitors to individual motor w01~lcl
represent a larger investment because of the diversity
factor. It, therefore, would be better for the operator to
switch off portions of the central capacitor t,o meet the
varying load conditions. Esceptions lvill arise n-here
feeders are long and where the gain from intlivitlual load
application warrants the greater initial investment in
capacitors. Recause of the higher cost of low-voltage
capacitors their application to 230-volt motor circuits may
more than double their cost. This gives considerable acl-
vantage to group installation if this can be on the primary
side, 2400 to 7200 volts. Capacitors placed aheatl of the
main bank of transformers do not benefit the transformers;
no transformer kva is released. Thus, use of the 230-
volt capacitors on the feeders or near the motors is frc-
quently warranted.

9. Localized Correction
Capacitors should be placed as near the load as possible
or near the ends of feeders for three main reasons:
1. Losses are reduced in the circuits between the loads and
the metering point.
2. Voltage is raised near the loads, giving better motor per-
Fig. IO-Enclosed indoor bank of 2400/4160 volt shunt capaci- formance.
tor units with protective screen removed. This is one step 3. Capacitor kvar can be reduced automatically as the load
voltage control with a RCOC oil contactor. drops off by installing some of the capacitors direct on
loads so they are switched off with the loads.
the power rates, and local conditions. An outdoor bank of The first point can be evaluated easily by investigating
capacitor units is shown in Fig. 10. the length of the circuits, and the transformations, if any.
Whatever gains are found in released transformer capacity
7. Location of Capacitors
and reduction in losses in transformers and circuits are
Many factors infltlence the location of the capacitor such added gains.
:LJthe circuit,s in the plant, the length of the circuits, the The effect of the capacitor is to raise the voltage per-
\‘:ll%ttion in load, the load factor, types of motors, distribu- manently at any given point where it is connected. This
l.iw of loatls, constancy of load distribution. voltage boost, superimposed on the normal voltage, is
‘Uw capacitors can be locatcci% many ways as follows: practically constant from no load to full load on the feeder.
01) Group correction--nt primary of trnnsformer.
(1)) &oup correction--at secondary of transformer. 10. Rates and Capacitor
(C) Group correction-out in a plant, 8s for example for one For the purpose of analyzing the different types of rates
buil~ling. a typical application can be considered, such as an in-
((1) T,ocnlizedcorrection on smnll feeders. dustrial plant with a day load averaging 960 kw and 67
(e) Lwrlizetl correction on branch motor circuits. percent powe: factor, with peak loads running up to 1200
if) Localized correction tlirect on motors, or groups of motors kw and 75 percent power factor. It is obvious that a lnrgt,
and switched with the motor. magnetizing current is drawn from the line, and con-
siderable savings can be made by supplying this mugnetiz-
8. Group Correction
ing current with capacitors. The size of the capacitor or
The two principal conditions under which group correc- the merits of their use can only be determined by systema-
tion is better are: tic analysis.
240 Application of Capacitors to Power Systems Chapter 8

One of the following conditions may exist. 960 kvv at 67 percent power factor. Assuming this is to he
(a) Power factor is not consiclerctl in the rates. brought up to 95 percent power factor, 720 kva of capaci-
(I)) Power factor is taken into account in demand charge. tors are required as follows:
(c) Power factor is checked by test and used to determine 960 kw
-- = l-L30 kva
energy charge thereafter. 67 percent
(d) Power factor is determined by the ratio of kw hours and
rkva hours and is used in different ways to calculate the Reactive kva at, 67 percent power factor
~lemnnd charge or energy charge or both. = t/iZjiCF6B = 1(X3.‘, kvar
(a) If power factor is not taken into account in the rate
titrrlcture, the capacitor can be used only to secure savings kva at 95 percent power factor =@? = 1010 kva.
.t
in the plant, such as to reduce current in circuits, reduce
lo:& on transformers, and to reduce loads on customer- Reactive kva at 9.5 percent power factor
operated generators. The capacitor should usually he =2/1010”-960?=315.
located near the loads of low power factor. The size can be Capacitor required is 1035 minus 313 which equals 729
determined by calculating the reactive kva. l<y using a kvar.
capacitor large enough to supply all or part of this reactive (d) A method commonly encountered in industrial
kva, the current in the circuit is reduced to the desired plants takes into account monthly power factor obtained
figure. by integrating kw hours and rkvs hours. &suming the
(b) If the rates include a kvs demand charge, the kva can plant mentioned above is billed for 322 250 kn- hours, and
he reduced by raising the power factor tlrlring the demand that the reactive kva hours equals 346 000. This ratio
peak. With a demand of 1200 kw at 73 percent power amounts to a power factor of 68 percent.
1200
factor the kva demand is -= lGO0 kva. Assuming that rates indicate that it will be worthwhile
0.75 to reduce this rkva hours to a point corresponding to 95
If the power factor is raised to 95 percent the demand kva percent power factor.
1200
is - = 1260 kva. The size of the capacitor required to kva hours at 95 percent power factor = E+g 000
0.95
accomplish this is determined from the reactive kva at the
Reactive kva hours at 95 percent power factor
two values of power factor as follows.
= d339 0002 -322 2.50’ = 106 000
Reactive kva at 75 percent power factor
=d1600’- 1200”= 1060 Using 730 hours per month the capacitor kvar required
339 000 - 106 000
Reactive kva at 9.5 percent power factor equals or 319 where the kvar meter has
730
=d12602-1200*=387 no ratchet so that full credit results even if the power
Kvar rating of capacitor is 1060 minus 387 which equals
200
673 kva.
The reduction in the kva demand from lGO0 to 1260 may I
result in either a reduced kva demand charge, or it may
reduce the energy charge depending on the rate structure.
Some rates involve several energy charges for successive
blocks of power, the size of the blocks depending on the
kva demand. For example:
Size of block = (70) X (kva demand).
1st block-% per kw hour
2nd block-lxc per kw hour
3rd block-lc per kw hour
Additional Zdc per kw hour
In this case the energy cost is reduced by a decrease in
kva demand, because if the blocks are smaller, the lower
rat,e applies to a larger proportion of the energy consumed.
(c) Sometimes a check is made on the average power
factor under day load conditions, and the billing there-
after based on this check until some future check is made. PER CENT RATED CURRENT
The energy charge, or the net billing is adjusted up or down Fig. 11-Self excitation of induction motor with various
according to this power factor. In such cases it is neces- amounts of shunt capacitors when supply breaker is opened.
sary to determine how this check is to be made, and under A-Capacitor current less than motor current ut no load rated :
what conditions, in order to install capacitors to raise the voltage.
power factor as high as warranted by the expected savings. B-Capacitor current equal to motor current at no load and rated ‘1
Such a capacitor usually is made proportional to day load voltage.
requirements. In the case above, the day load averaged C-Capacitor current equal to 100 percent.
chapter 8 Application of Capacitors to Power Systems 241

factor is leading at times. When the meter has a ratchet


t,hc Capacitor must he large enough to build up nccumli-
latcd kvar-hours while the power factor is not leading.
Detail analysis of the load and its variations at each
nlsnt, taking into consideration the type of rates, should
1)1)matlc to obtain the greatest benefit from using capaci-
l,),‘s. In some cases part of the capacitors may have to be
,j,vit~:tiecloff durin, 17light load periods to prevent excessive
v,,ll ;tgc on plant circuits.
11. Capacitors on Induction Motor Terminals
Qpacitors frequently arc installed across the t,erminals
,,f induction motors and switched with the motor. The
:unc)rint of kvar SOconnected should be limited to values
t,\I:Lt,do not cause excessive voltage at the motor due to self-

-
TABLE ~-MAXIMUM CAPACITOR KVAR FOR USE WITH OPEN
TYPE THREE PHASE 60 CYCLE INDUCTION MOTOR

livnr **
I 1800’
RP5I

Kva.r
-7
-
*c
1200*
RPM

KVU
-.
**
900*
RPN

Kvar **
i20*
RP;zI

KVX
- -
** Kvar
600*
PM

**
Fig. 12-180 kvar, group-fused,
installation.
pole-mounted capacitor

-- - .- -_ -- - --
low, a large reduction in feeder current or kva can be
2 5 9 4 I1 4 12 5 17 5 23 7.5 28
2.5 9 5 11 5 11 7.5 16 7.5 21 10 26
obtained as indicated by the curves in Fig. 5. If the load
5 !I 5 10 5 11 7.5 15 10 20 12.5 24 power factor is high, shunt capacitors cannot materially
5 9 7.5 I) i .i 10 10 14 10 19 15 22 change feeder loading. Where voltage is the limiting fac-
7 5 ‘9 10 9 10 10 10 13 12.5 1s 15 21 tor, the capacitor kvar to decrease voltage drop is de-
IO 11) IO !I 10 10 12.5 12 15 16 17.5 19 pendent not only on load power factor but also on the
12.5 !I 12.5 s 12.5 9 15 12 20 15 22..5 17 ratio of resistance to reactance of the distribution feeder.
I !5 9 15 8 15 9 17.5 11 22.5 14 25 16
I7 5 9 17.5 8 17.5 8 20 11 27.5 13 30 15 12. Application Factors
22..5 9 22.3 8 22.5 s 25 10 35 12 37.5 14 In applying shunt capacitors to distribution circuits,
25 9 27.5 8 27.5 8 30 9 40 11 4i.5 13
certain system data are required.
32.5 9 35 8 35 8 37.5 9 47.5 11 55 13
1. Determine variation, preferably by graphic instru-
12.5 9 42.5
- -8 42.5
-8 45 9 60 -
10 L67.5 12
ments, of kw and kva on each feeder for a typical 2-l-
hour period at both minimum and maximum daily
loads. Usually the minimum reactive kva determines
w:it,ation when the breaker is opened, as Fig. 11 shows. the am=- of--Ged%$iiitors to apply without
‘1’:tble 5 gives the maximum recommended capacitor kvar automatic control. This gives. about unity polier
for direct connection to the terminals of induction motors factor at minimum load. In certain cases more fixed
t&n from the 1047 National Electrical Code. capacitor kvar can be applied where voltage condi-
tions at light load permit and where leading power
III. CAPACITORS ON DISTRIBUTION factor is not objectionable.
CIRCUITS 2. Obtain actual voltage measurements on the feeder
during full load and light load at a sufficient number
Shimt capacitors offer a convenient and practical means of points to determine the ‘optimum location for
of rclicving lines and source equipment of wattless current. capacitors. Fixed shunt capacitors raise the voltage
‘l’lwy can be installed in relatively small banks and placed level at the point where they are applied on a given
i~:tr t,he load points. They usually arc arranged in three- circuit by practically a constant value as given by
1~1~~~banks of 45 kvar or more and are distributed over XI, in Eq. 2.
tlw system at distribution voltage, usually 2400 volts and
1% in accordance with local requirements. A 180 kvar in- To calculate the voltage at various points on the
st:tllation is shown in Fig. 12. At present it is not econom- feeder the circuit characteristics and the load dis-
ical to apply capacitors on the secondary side of distribu- tribution must be known. Where the individual loads
tion transformers because of the much greater cost. are not known, it is reasonable to assume they are
lVlwc the transformers are expensive, such as network proportional to the installed transformer capacity for
‘iruts, secondary capacitors may be justified. minimum and maximum feeder load. To simplify
‘h capacity of a distribution feeder can be limited by calculations single-phase loads can be grouped to-
(!irrrcnt or by voltage drop. Where current is the limiting gether to form balanced three-phase loads and ad-
factor, the effect of capacitors in reducing the current is jacent three-phase loads can be grouped to simplify
dependent upon load power factor. If the power factor is the calculations.
242 Application of Capacitors to Power Systems Chapter 8

3. It is dcsirablc to supply the kvar required by the load


as close to the load as possible to reduce feeder
losses. Therefore, capacitor units should be located
at load centers or near the ends of feeders. Ideally
each load point, would have the exact amount of
capacitor kvar to supply the necessary load kvar.
This, however, is not possible because standard size
units rnllst be used. Also it is more economical to use
the large size units, namely, 15 or 25 kvar. Over-
TTTT
(b) TTT
(c)
compensation of feeder branch circuits with capnci-
tors to obtain a higher voltage results in increased
copper losses because at lower and lower leading
power factors, the current increases. ,i[C BREAKER

4. Calculate the released feeder capacity in kw and kva


for the capacitor kvsr installed. This may involve
capacitors installed at several locations on a given
feeder. Released substation, transmission, and gen-
erator capacity is also immediately available.
5. Calculate the reduction in kw losses and the reduc-
tion in kvar losses in the feeder. The effect on all
equipment back to and including the source genera-
TTT
X 2X 4X-KVAR
tor should also be evaluated when the total capacitor (d) (e)
kvar become appreciable relative to the total source
circuit or system reactive kva. Fig. 13--Schematic arrangements for switching large ca-
pacitor banks.
6. Summarize the tangible effects namely, the released
feeder capacity, the released capacity back to and
including the source generator, the reduction in breakers are provided for controlling two steps, the third
losses, t,he effect on voltage, etc. and evaluate the step being controlled by the main breaker. Figure 13(d)
economics to determine whether or not capacitors are is a scheme in which three groups of capacitors properly
justified. Also compare the cost of capacitors with proportioned provide seven equal steps. Switch 1 gives
other ways of doing an acceptable job, such as con- ‘/7 of the total; switch 2 gives ‘/i; switches 1 and 2 give 3/~,
struction of a new feeder, installation of voltage regu- and so on far all three switches giving the full capacity of
lators, raising the distribution voltage, etc. the bank. The disadvantage to this scheme is that during
From the above brief summary on applying shunt the switching process, large changes of capacitor kvar are
capacitors to distribution systems, it is evident that no made to get from one kvar to another. The worst condition
fixed rules can be stated regarding the location of capaci- is changing from “/7 to J/T of the total kvar where switches
tors nor can the tlcgree of importance of each of their 1 and 2 must be opened, thus, disconnecting all capacitors
elrects be stated. Each case is different and requires a before closing switch 3, or switch 3 must be closed putting
complete study in more detail than has been given in this all of the capacitors in service before switches 1 and 2 are
general discussion. opened. If the voltage change during these changes can be
tolerated, then seven steps in capacitor kvar can be ob-
tained with three circuit breakers. Figure 13(e) is another
IV. LARGE CAPACITOR BANKS
scheme where one automatic circuit breaker supplies a
Shunt capacitors have been applied at substations and number of non-automatic breakers which control equal
at the ends of primary feeders in banks ranging in size up amounts of capacitor kvar. Each non-automatic breaker
to about 20 000 kvar. The usual large sizes are between has a high-capacity fuse that will clear a faulted capacitor
5 000 and 10 000 kvar. A capacitor bank can he switched group ‘ihead.of tripping the main supply klreaker. There
all in one step, but general practice is to provide switching are many combinations of the use of automatic breakers,
so that a large bank is connected to the system as needed non-automatic breakers and high-capacity fuses for capaci-
in several equal steps. Three equal steps are quite common tor banks that can be applied, depending upon the operat-
although more or less steps are used, depending on the ing requirements and economics.
voltage change per step and the variation in load.
Several typical layouts for switching large capacitor 13. High Voltage Banks
banks are shown in Fig. 13. Fig. 13(a) is for one group of Supplying kilovars direct to high-voltage circuits is often
capacitors switched by one automatic circuit breaker. desirable to meet certain system requirements even though :
Fig. 13(b) shows four automatic breakers controlling four a greater portion of the system is benefited by placing the ;
equal steps in a large capacitor bank. The circuit breakers capacitor nearer the load and on lower voltages. For many
must be capable of handling short circuit currents. Figure years, transformers were used to step down the voltage to
13(c) shows three equal steps where one automatic breaker the range of the capacitor unit ratings. A few years a;o
supplies the entire bank and trips for short circuits in any the practice of connecting low-voltage capacitors in series
one of the three groups of capacitors. Two non-automatic parallel groups and directly to the high-voltage line Was
Chapter 8 Application of Capacitors to Power Systems 243

ostatAishcd because they are more economical than the use when a unit becomes short circuited for any reason, the
of high-voltage cnpacit.ors or transformers ant1 lowroltage current through the fuse is limited. With individual fuses
,,llits. One of the first such installation consisted of six a faulty unit can be located without resorting to the risky
,l.r~)~~ps
,- of’ 2 M-volt outdoor capacitor units operating in procedure of searching for the source of noise or arcing,
ScSr,ic~~on the phase t,o neutral voltage of a 24-kv circuit. or making inconvenient tests. It is also easy to make R
l<& group of 2400-volt units consisted of lo-15kvar check and determine if all units in the bank are operating
properly. The fuses can be omitted but at a sacrifice in the
protection to the capacitor bank.
The number of units in parallel in a single group is im-
portant. Several things affect this. First the number should
be sufficiently large to insure that t,he fuse on a single unit
blows when the unit becomes short circuited and the fuse
is called upon to carry the total phase current. Second,
t,he voltage on the remaining units in a group should not,
become excessive with t,he operation of one fuse in a gro~~p.

- Tf the number of parallel units is too small, the current1


through t,hc fuse may be so low that it lvill not blow, or

T/ e2
e.
take too long in doing so. An arc of 50 amperes inside a
capacitor unit may rupture its case if allowed to cont,inue
for a long time and such a rupture may endanger other
units in the bank. After considering the size of fuses that
- I
must be used to avoid operation on sn-itching transients,
and taking into account the arc energy required to rupture
the capacitor case, it has been established that the current
Mx through the fuse when a unit becomes shorted should

-T
GROUP X
T eX

I -i
NEUTRAL
I%!. 14--Connection for fused capacitor units for one phase
of a three phase bank. Symbols apply to Eqs. (3) to (11).
X--Sunher of capacitor groups in series.
M-Xormal nunher of cupttcitor units per group
N-Kumt)er of units out of one grunt>.
e, --Actud voltage across group 1.
co,-Rated voltllgc a~!ross group 1.
e, --Korrnl~l system voltage to neutral.

units in parallel, and these 150 kvar groups were supported


1111 ins(IIators to take care of the line to ground voltage.
Q;llrc 1-I shows ho\v capacitor units are assembled for one
piusc: of a hank.
I Ilit ially, operation of capacitor units in series WLLS
looked
l~l)on :LSrisky due to the ever-present possibility of sub-
iwhg capacitors to overvoltage as a result of changes in Fig. 15-6000 kvar 34.5 kv outdoor capacitor bank with bus-
v(jlt:kge distribution either due to a change in impedance of mounted fuses.
wtions of the phase leg or due to grounds at some point
~1 the assembly. Most of these risks are minimized or never be less than 10 times the normal capacitor current
clrltircly eliminated, however, when proper thought is given through the fuse.
10 sl~h factors as fusing, number of units in parallel, It is also desirable to avoid voltages in excess of 110 per-
(‘()llnection of one bushing of capacitor to the insulated cent on t,he remaining units in a group following the opera-
I)l:ltform on \vhich it rests and means of detecting un- tion of one fuse. This assumes that in the case of the
‘l~~la~~~e conditions before the unbalance becomes esces- minimum size bank not more than one fuse operation is
Si\c. ICtachcapncitor unit in a high-voltage bank d10dd permitted. To accomplish this, periodic checks are
be Provided with a fuse of the indicating type. These fuses necessary.
need not be of high interrupting capacity because there The amount of current that flows through a fuse when a
are always two or more capacitor groups in series, and, unit is shorted is also affected by the number of series
244 Application of Capacitors to Power Systems Chapter 8

groups and whether or not the neutral of the capacitor


bank is grounded. 1 IN SERIFS
Tables G and 7 show the recommended minimum num-
ber of fused capacitor units that should be used in parallel
for a given number of groups in series in each phase leg, for
ungrounded or grounded-wye connections respectively

TABLE ~-UNGROUNDED WYE CAPACITOR CURRENT AND


VOLTAGE RELATIONSHIPS WITH SHORTING AND REMOVAL
OF ONE UNIT IN ONE PHASE LEG

Current Voltage on
Number Minimum During Fault Remaining
Groups Units per Through Fuse Units in Group
Series Group Times Normal Percent

1 4 12.0 109
2 8 12.0 109
3 9 11.6 109.5
4 9 10.8 110
5 10 11.5 110 4
6 10 11.2 110 PERCENT UNITS REMOVED FROM GROUP
7 10 11.0 110
Fig. 16-Ungrounded wye connected shunt capacitor bank,
8 10 10.9 110
Curves give the percent overvoltage across the remaining
9 11 11.9 Less than 110 units in a group.
10 11 11.8 Less than 110
11 11 11.7 Less than 110
12 11 11.6 Less than 110 periodic checks of fuses are necessary to avoid abuse of
13 11 11.6 Less than 110 good capacitors as result of a faulty one. The voltage
14 11 11.5 Less than 110 across the remaining capacitors can be determined from
15 11 11.5 Less than 110 Tables 6 and 7, the curves of Figs. 16 and 17 or calculated
16 11 11.5 Less than 110 from the equations given below. For all equations the
system impedance up to the capacitor bank was neglected.
TABLE ~-GROUNDED WYE CURRENT AND VOLTAGE RELA- Refer to Fig. 14 for identification of symbols in the fol-
TIONSHIPS WITH SHORTING AND REMOVAL OF ONE UNIT lowing equations. The equations simplify quickly; all units
IN ONE PHASE LEG have the same volt,age rating.
Current Voltage on
Number Minimum During Fault Remaining
Groups Units per Through Fuse Units in Group
Series Group Times Normal Percent
1 1 Line Fault
2 6 12 109
3 8 12 109
4 9 12 109
5 9 11.2 109.8
6 9 10.8 110.0
7 10 11.7 109.4
8 10 11.4 119.5
9 10 11.2 Less than 110
10 10 11.1 Less than 110
11 10 11.0 Less than 110
12 10 10.9 Less than 110
13 10 10.8 Less than 110
14 11 11.8 Less than 110
15 11 11.8 Less than 110
16 11 11.7 Less than 110

based on meeting the previously discussed requirements.


All capacitor units are assumed to be the same voltage
and kvar rating.
Very often large banks contain many more than the PER CENT UNITS REMOVED FROM GROUP .
minimum number of units in parallel. When this is the Fig. 17-Grounded wye-connected shunt capacitor bank
case, more than one fuse can operate and still not seriously Curves give the percent overvoltage across the remammnl
raise the voltage across remaining units. In such cases units in a group.
Chapter 3 Application of Capacitors to Power Systems 245

14. Ungrounded Neutral Capacitor Bank


Normal voltage across group 1 is
elN =
(9)

The current in the fuse of a completely short-circuited


capacitor unit in group 1 of one bank of two similar banks
\Vith IVYunits removed from group I, the voltage e1across wit,h the neutrals solidly connected and ungrounded in
the remaining units is terms of normal current in one capacitor unit is

(10)

lVith Ni units removed from group 1 the voltage shift of The current in the neutral connection between two sim-
the neutral of the capacitor bank eNOis ilar banks of capacitors, with N units out of group 1 in
one bank, in terms of the normal current through one
capacitor is
eNo=
(5)

The current through the fuse for a completely short-cir-


cuited capacitor unit in group 1 in times normal operating
current is 17. Protection of Large Banks of Shunt Capacitors
The usual types of protection for large capacitor banks
are :
1. Individual capacitor fuses.
2. Capacitor group (or bank) fuses.
3. Overcurrent relays or trip coils to trip a bank circuit
breaker.
15. Grounded-Neutral Capacitor Bank 4. Potential transformers connected acrosseach phaseor each
Normal voltage el across group 1 is same as for un- seriesgroup per phaseof ungrounded wye banks to trip the
bank circuit breaker on phase or group voltage unbalance.
grounded neutral bank as given in Eq. (3). This schemecan be used for delta or wye grounded-neutral
With N, units removed from group 1 the voltage el across banks that have two or more groups in series.
the remaining units is 5. Potential or current transformers connected between the
neutrals of two or more wye ungrounded banks to detect
unbalance in one bank and operate a relay to trip a single
breaker through which all banks, in the protective scheme,
are supplied.
6. Potential transformer placedbetween the neutral and
ground of a wye ungrounded bank connected to a grounded
The current through the fuse of a completely short-cir- system to operate a relay and trip the bank breaker on a
cuited capacitor unit in group 1 in times normal operating shift in the neutral voltage.
current for a grounded-neutral capacitor is Large capacitor banks can be connected in wye un-
grounded, wye grounded or delta. However, the wye un-
$+&+. . .+g
grounded connection is preferable from a protection stand-
Ir=(M,) ;’
x
(8) point. Individual single-phase 15- and 25-kvar capacitor
%2+.. . .+- $ units are protected usually by a fuse whether inst,alled in
L 2 x I an outdoor or indoor bank for any type of capacitor con-
nection. For the wye ungrounded system of connecting
single capacitor units in parallel across phase-to-neutral
16. Two Identical Capacitor Banks with Neutrals voltage the fault current through any fuse is limited by
Solidly Tied Together and Ungrounded the capacitors in the two sound phases. In addition the
The normal voltage across any group of capacitors in an ground path for harmonic currents is not present for the
installation consisting of two similar groups with the ungrounded bank. For wye grounded or delta-connected
neutrals tied solidly together and ungrounded is el as given banks, however, the fault current can reach the full short-
by Eq. (3) for any bank. With iV1 units out of group 1 in circuit value from the system because the sound phases
one bank the voltage across the remaining unitsingroup l.is cannot limit the current. Thus, with the wye ungrounded
446 Applicatioti of Capacitors to Power Systems Chapter 8

cmnection smaller fuses and less material are needed for


protecting the capacitors. With two or more groups of
capacitors in series per phase, the short-circuit current is
limited by the capacitors in the unfaulted group. The
capacitor hank should have a protective tlevicc to dis-
connect the bank from the system if individual units bc-
P-3 BREAKER

come defective thereby callsing a bad unbalance of capaci-


tor kvar among the three phnscs.
Two protective schemes for wye connected ungroundctl
hanks for all voltage classes are sho\vn in Fig. 18. The
scheme shown in Fig. 18(a) is preferred because the potcn-
tial transformers serve the dual purpose of protecting
against unbalance(1 cxpacitor kvur per phase leg as iyell as

I. POWERCIRCUIT
TO BREAKER
TRIP COILS

SHUNT TRIP CAPACITOR


USES

/
Fig. 19-Delta-connected, fused capacitor units usually used
at 2400 volts or less.

providing a discharge path to dissipate quickly charges


left on capacitor units when the supply is disconnected. A
current or potential transformer connected betn-een the
neutral points of two equal parts of a grorlp of capacitors
provides protection for unbalanced kvar per phase as
shown in Fig. 18(h). In addition, however, two potential
transformers connected in open delta should be Ilsed on
OWER CIRCUIT automatically controlled banks across the supply leads
to the group to provide a fast discharge path when the
TRIP COILS
capacitors are de-energized. One of the potential trans-
formers can also be used for an indicating lamp to show
when the group is energized.
A delta-connected bank of capacitors, Fig. 19, usually
SHUNT TRIP
applies to voltage classes of 2400 volts or less. Individual
capacitor fuses are provided for each unit). If the bank is
controlled automatically, potential transformers should be
INDIVIDUAL CAPACITOR
applied across each phase leg to provide fast discharge
when the group is de-energized. The individual capacitor
units have a very high resistance provided across the termi-
nals inside the case to discharge the capacitors in five min-
utes after being disconnected from the source. This time
of five minutes is considered to be too long for banks
that are controlled automatically because when t,he group
is switched on again before the charge is dissipated high

Q
transient switching currents result. In special cases such
V as for indoor capacitor banks, it can be compulsory that
(b) potential transformers be applied for rapid dissipation of
Fig. 18-Two protective schemes for large banks of un- charges remaining on capacitor units.
grounded wye-connected capacitors.
18. Capacitor Fusing
(a) Residual voltage trip in event of unbal:tnce among the three
phases due to failure of capacitor units. General-Each capacitor unit contains a large area of
(b) Residual voltage trip in event of unbalnrxe between the two insulation and the probability of unit failures must -be
3-phase groups of capacitors. Current flow between the two recognized even though the record is good, as shown in
groups can also be used for protection. Fig. 4. When the number of units in a single installation
chapter 8 Application of Capacitors to Power Systems 247

usually does not result in case rupture or damage to other


units.
Large capacit,or banks are generally on circuits capable
of producing high fault current, and additional problems
are crcntcd due to the close association of large numbers
of capacitor units.
The ability of a short-circuited capacitor to pass currrnt
is limited by the current-carrying capacit,y of the thin
aluminum foil that forms the electrode surfaces. If these
foils are allowed to carry heavy fault current, the foil
may act as its own fuse. This has considerable bearing
on the fusing problem because a fault within a capacitor
can melt the foil rather easily and the fault tends to clear
and sometimes restrike. The presence of other capacitors
in parallel with and discharging into the shorted capacitor
increases the tendency to melt the fault clear. Cnder cer-
tain conditions the arc restrikes each half cycle, thus al-
lowing the atljaccnt capacitors to be repetitively charged
and discharged. This may damage the current-carrying
connections of some adjacent units and cause simultaneous
or later failure. The current a capacitor unit can pass
before case rupture is likely to occur is shown in Fig. 20.
If the fault current in a capacitor is limited to a few hun-
dred amperes, the pressure builds up slowly and many
cycles of current flow may be endured before case rupture
takes place. When the current exceeds about 3000 am-
peres a rupture results in mechanical damage to adjacent
units and often in short-circuited bus connections; the
greater the short-circuit current the more violent the case
rupture.
If the arc in a capacitor unit is allowed to persist until
the case is ruptured, other units and parts in the bank may
be damaged either mechanically or by consequent arcs.
It is, therefore, desirable to provide adequate protection
against short-circuited capacitor units. The function of
this protection is:
(a) To protect the circuit and capacitor bank so as to mini-
\ mize the chance of an outage.
(b) To protect other capacitors in the bank against electrical
damage due to current transients.
8 (c) To protect the other units in the bank from mechanical
2 damage due to a unit case rupture.
CURRENT IN AMPERES RMS 60 CYCLES
(d) To minimize the hazard to the operators and maintenance
IQ. 20-Capacitor fault current and its relation to case personnel.
rupture. Protection Inherent in R&kers---Breakers with
(‘urve A--Where fault currents arc cleared in a time to the left of overload protection, and adequate interrupting rating pro-
this c:urve t,hc C:LWis not likely to rupture. tect the circuit, bitt usually do not protect the capacitors
(~urvc I3-Where f:hult currents are on for LI time to the right of this against damage in case of a short-circuited unit, unless
wrve the c:tse is likely to rupture with sufficient force to dnmitge supplemented by individual capacitor fuses, or relay means
other units. to trip the breaker as a result of current or voltage un-
,\rw AB--Fault currents in this areit may open case seams. This
balance. Use of breakers alone, however, does not remove
WC~may be used for fuse selectivity with remonnble safety.
the hazard associated with a bank where unit fault cur-
rents are high.
is large the probability of a unit failure of insulation is A breaker should be considered primarily as a switching
greater. The removal of faulted units is important for device and circuit protective device, and not as protection
Ihe protection of the remaining good units. against high fault current within an individual capacitor
:\bout sixty-five percent of existing capacitor kvar on unit. It may, however, be considered as back-up protec-
utility systems are “pole type” and usually total about 180 tion in case the individual unit protection or other pro-
kvar per installation. These are usually on circuits where tection fails.
the fault currents are moderate and group fusing has been Group Fusing-A short-circuited capacitor is in re-
Satisfactory. When a capacitor unit becomes shorted, it ality a conducting path having time-melting character-
248 Application of Capacitors to Power Systems Chapter 8

istics, which has a bearing on the maximum size of the (f) They permit uninterrupted use of the capacitor bank since
group fuse. The size of the group fuse is also determined a faulty unit need not take the bank out of service.
by the normal current of the bank and harmonic currents. Table 7 shows there is a minimum number of capacitor
In general, the following rules are recommended for units required in parallel per group to give sufficient cur-
group fusing: rent for positive operation of an individual fuse on a failed
(a) It is preferable not to apply group fuses greater than 55 unit. Likewise there is a masimum safe number of indi-
amperes in rating (on a 100 per cent rating basis.) vidually fused capacitors that can be placed in parallel
(b) The circuit is protected adequately by group fusesif they per group because if a unit fails all other parallel units dis-
have sufficient interrupting capacity. charge their stored energy, at high current, through one
(c) To minimize the danger of mechanical damage, group fuse to the fault. If too many units are in parallel per
fuses should be supplemented with individual fuses when group, the current is high enough to cause mechanical
the unit fault current is expected to exceed3000 amperes, rupture of the fuse with the possibility of damage to other
even though the group fuse interrupting rating is ade-
quate for the expected fault current. 100
Large banks of capacitors have been installed with dc-
pendence placed solely on group fuses or breakers. Where 5C
fault currents are high, the failure of one unit is likely to
damage other units in the bank, thereby multiplying the 25
damage considerably. Other units may also fail at a later
date when the reasons are not immediately apparent.
Some of these large capacitor banks without individual IC
fuses are wye connected with the neutral ungrounded, or
are made up of series groups, so that the problem of high F
fault currents does not exist. Unbalance in these cases is
detected by voltage transformer and relay schemes so as
to trip the breaker under abnormal conditions such as 2.5
z
might occur if a unit becomes short-circuited. The objec-
z
tion to this arrangement is that it is difficult to identify a
Y
defective unit and there is the possibility of electrical m ~
damage to parallel units before the breaker de-energizes z
the bank. Individual capacitor fuses give indication of a w
z 0.5
blown fuse and give electrical as well as mechanical pro- t=
tection to parallel units.
Individual Fuse-The individual fuse rating is de- 0.25
pendent upon the normal current rating of the capacitor
unit, harmonic currents and the number of times in rapid
succession a fuse must carry discharge current from a good 0.1
capacitor unit to a defective unit. To provide for the later
requirement, the current rating of the fuse is usually at 0.05
least twice the current rating of the capacitor.
Individual fuses are used primarily to remove units 0.025
following failure of the dielectric. Since only one fuse is
used with each unit, this fuse is not expected to clear for
ground faults within the unit. Relaying should be pro-
0.01
vided where possible to detect ground faults even though
their occurrence is very rare.
Individual capacitor fuses should be used, particularly AVAILABLE CURRENT IN AMPERES
in large hanks, so that a faulted unit is disconnected Fig. 21-Typical type BAG capacitor fuse characteristics for
promptly from the circuit for a number of reasons: use with housed units where the fault current is less than
15 000 amperes from the system.
(a) Their current rating is small and coordinated with the Fuse A-4160 volt delta connected 15 kvnr units.
time-current characteristics of the capacitor. 4160 volt ungrounded wye 15 kvar units.
(b) They indicate the defective unit. 7200 and 7960 volt ungrounded wye 15 kvar units.
(c) They reduce to a minimum the chance of unit case rup- Fuse B-2400 volt delta connected 15 kvar units.
ture and subsequent mechanical damage. 2400 volt grounded wye 15 kvax units.
(d) They remove a short-circuited unit before the inside foil 4160 volt delta connected 25 kvar units.
material is fused to the point where repetitive clearing 2775 volt ungrounded wye 15 kvar units.
creates high transient current in adjacent units. 4160 volt ungrounded wye 25 kvar units.
(e) They protect units against transient currents set up by 7200 and 7960 v. ungrounded wye 25 kvar units.
parallel arcs in the bank such as bus flashovers, roof bush- Fuse C-2775 volt ungrounded wye connected 25 kvar units.
ing flashovers, or failures in potheads or accessories, or Fuse D-2400 volt delta connected 25 kvar units.
arcs in short-circuited units in the bank. 2400 volt grounded wye-connected 25 kvar units.
Chapter S Application of Capacitors to Power Systems 249

energy to blow the fuse on the faulted unit. If it mere not


for the current from the parallel units the system short-
circuit current would have to be limited to about 3000
amperes to prevent rupture of the capacitor case. The
discharge current from the parallel capacitors is high in
magnitude as shown in Fig. 28 and reaches half value in
&I$ 0.02 second or less.
Where the fault current exceeds 15 000 amperes from
the system, individual capacitor current limiting fuses
(CLC) are used, the characteristics of which are shown on
Fig. 22.
(b) Housed Banks (Ungrounded Wye)
IIoused banks for circuit voltages of 4800 volts and
above are usually wye connected with the capacitor neutral
ungrounded, whether or not the source neutral is grounded.

AVAILABLE CURRENT IN AMPERES

Fig. 22-Typical type CLC current limiting fuse characteris-


tics for use where the fault current is high or in excess of
15 000 amperes from the system.
Fuse E-2400 volt delta connected 15 kvar units.
2400 volt grounded wye 15 kvnr units.
Fuse F-2400 volt delta connected 25 kvar units.
2400 volt grounded wye 25 kvar units.

units. Therefore, on large banks of capacitors, when the


number of units in parallel per group exceeds two or three
t,imes the minimum required number, special considera-
tion should be given to the application particularly with
regard to arrangement. Where such limitations are in-
volved, the bank can be divided into two or more parts
\vhcre there are two or more groups in series. Lower
voltage units with a fewer number in parallel per group
with more groups in series may be a solution also.
Individual Fuse Characteristics AVAILABLE CURRENT IN AMPERES
(a) Housed Banks-2400- and 4160-volt delta-connected Fig. 23-Typical UT fuse characteristics used on ungrounded
and 2400-volt wye-connected grounded-neutral. wye-connected outdoor capacitor banks.
Housed banks usually contain indoor-type individual Fuse G-4160 volt 15 kvar units
unit fuses. Where the fault current is less than 15 000 7200 volt 15 kvar units.
amperes type BAC fuses are used, the characteristics of Fuse H-2775 volt 15 kvar units.
which are shown in Fig. 21. Actually the discharge cur- 4160 volt 25 kvar units.
rent from the good capacitor units operating in parallel 7200 volt 25 kvar units.
Ivith the faulted unit supplies a considerable portion of the Fuse I-2775 volt 25 kvar units.
250 Application of Capacitors to Power Systems Chapter 8

This arrangement limits fault current and the type MC ous and involved, but their operation is accurate, reliable,
fuses are us~rl, the characteristi:s of which arc shown on and thoroughly proved by many applications.
Fig. 21. Where the need for capacitor kvar follows a fixed
schedule, the capacitors can be switched by a t,ime relay
(c) Outdoor Struc:tur:tl Type Banks (Delta or Grounded
WJT) that initiates on or 08 at predetermined times.

Where the fault current is likely to be high as for a delta 20. Inrush Current
conncctctl or grounded wye, outdoor bank current limiting When the first step of a capacitor bank is energized, it is
individual fuses (CLC) are desirable. This applies to possible for a large instantaneous current from the system
delta conncctcd 2400 volt banks, wye connected 2400 volt to flow. Curves in Fig. 24 show for several line-to-line
and delta conncctcd 4160 volt banks of capacitors. The
characteristics of the fuses are the same as for similar
indoor banks as shown on Fig. 22.
((1) Outdoor Structural Type Banks (Ungrounded Wye)
Outdoor structural type hanks for voltages of 4800 volts
and above are usually wye connected with t,he neutral of
the capacitjor ungrounded, whether or not the source
neutral is grounded. This arrangement limits fault current CURRENT FROM
and permits fuses of lower interrupting rating. The charnc-
teristics for these fuses are given on Fig. 23.
19. Automatic Control for Capacitor Banks 5;
zz
The intelligence required to switch banks of shunt n 7000
capacitors automatically depends upon the reason for 1
t,hcir use. If they are used primarily to control voltage,
then the capacitors can be switched on when the voltage
is low or off when the voltage is high, and a voltage relay
supplies the control. If the system voltage is regulated
by other means and t,he capacitors arc used for power-
factor correction, then the load kvar or total current must
be used as the means for control.
It is always desirable to use t,he simplest type of control
that will accomplish the desired result. Current control
is commonly used where the voltage is regulated by other
means and the power factor is practically constant through
wide variations in load. Kvar control is used where t,he
load po\ver factor varies over a wide range as the load
changes.
Whether the control is accomplished by volt,age, cur-
rent, or kvar, the control systems are similar. In addition
to the master control relay, other devices are required in
the control scheme such as time-delay relays, control
switches, etc. For one-step automatic control the master
relay energizes the “closing” element of a time-delay relay,
and if the master-relay contacts stay closed for the time
required for the time-delay relay contacts to make, then
the operating circuit is energized and the capacitor breaker 4000 8ooO
closes. CAPACITOR KVAR (3 PHASE BANK)
A similar process in reverse trips the capacitor breaker. Fig. 24-Inrush current from system when energizing capaci-
For a two-step control the sequence is the same as for tor bank.
one-step control except that auxiliary contacts on the No.
1 breaker set up the circuits for the control of the second voltages the maximum rms inrush current for different
step. If the No. 1 breaker is closed, the circuit is set up system short-circuit currents available at the capacitor
to either trip No. 1 or to close No. 2. The sequence of terminals. This current can be calculated using the fol-
operation is the same in all cases, that is, No. 1 breaker lowing formula:
always closes first and trips last.
For more than two-step control, each additional break-
er, by means of auxiliary contacts, sets up the control cir-
I=&-[l+J$g (12) ,
cuits for the next operation whether it be to add or re- Where ELC is line-to-ground operating voltage on the!
move capacitor kvar. The control circuits become numer- capacitor bank. I
!
Chapter 8 Application of Capacitors to Power Systems 251

XC is the capacitive reactance in ohms of one being energized and that portion of the bank already
phase to neutral of the capacitor bank. energized. This value of L is difficult to determine ac-
XL is the inductive reactance in ohms per phasecurately, but, due to inductance in the capacitor leads and
of t,he source. bus structure, the estimated L is usually a low value rather
The above formula applies to delta-connected capacitor than a&&one, thus giving a current that is too high and,
I&;S if X,: is determined as the reactance of the equivalenttherefore, on the safe side. The 1.2 fat:t,or is applied to
l;r~c-to-ncutr:tl capacitor kvar. The current values are account for some feed in from the system and also possible
for the first step of a bank. If one or more steps in the current unbalance due to unequal pole operation of the
C8aLpacitor hank are already energized, then the masimum breaker.
I1e& current that flows into the next, capacitor group to be The inrush current and frquency when a bank of
C,nc:rg~zedis tletcrmined largely by the momentary dis- capacitors is energized in parallel with one or more
c;]~:~rgcfrom those capacitor units already in service. esisting banks is given in Fig. 25. To illustrate its use
assume a 13%kv, three-step capacitor installation con-
‘l’hc breaker controlling the last step in a bank of capaci-
101‘sis the one that is subjected to maximum peak current sisting of three 2520-kvar banks, two being energized and
the third step to be energized. The percent capacitive
\v)lcLnthis step is energized. The peak currents if no charge
is on the step being energized, can be determined approsi- reactance for each step on 2520 kvar is 100. The two
m:~t,elyby using the following equation: capacitor steps already cncrgized in parallel are 50 ptr-
cent on 2520 kva. These two steps in series with the one
1penk= (1.2) (4) (13) step to be energized are 150 percent. So the X, for use
with Fig. 25 is 150 percent. Now assume that each capnci-
If the st,cp being energized is fully charged, the peak tor step has a series inductive reactance of O.OOSGohm in
inrllsh current can be about twice this value. ELM is rms all of its leads between the capacitor units and a common
line-to-neutral voltage applied to the capacitors. C is the point on the bus which is 0.01 percent expressed on 2520
total cspncitancc per phase of the capacitors already ener- kvar. Two such units in parallel plus one in series gives
giz(L(l combined with the capacitance of the step being 0.01.5 percent XL for use with Fig. 25. I-sing this data the
cwqizetl. For :L three step bank with two steps energized XL (X,/100) equals 0.0225 which for slyitching in the
:~rltl with the third step being energized then third 2520 kvar step of capacitors allo\vs a masimllm peak
inrush current of about 69 times normal rms rated current
c= l of each step or 69 X 105, or 7250 amperes. The frequency
(14) of this current is about 6000 cycles. If the inductive
&+$
1 2 ‘3
reactance of the leads is less than 0.0076 ohm, the masi-
For delta-connected banks the equivalent single-phase-to- mum inrush current is greater than 7250 amperes.
grollnd capncit,or kvnr must be used as t,hough the bank Where the inrush current when switching banks of
was wyc connected. I, is the inductance between the step capacitors is excessive, it can be limited by the insertion

XL(IOO/Xe) %

NOTE 1. THESE CURYES APPLY FOR 60 CYCLES SYSTEMS.

NOTE 2. IF THE CbPICITOR IS FULLY CHARGED AN0 TtiE


SWITCH CLOSED WHEN SYSTEM VOLTAGE IS OPPOSITE TO

TWICE THAT OWEN BY THIS CHART. THE CHART APPLIES


FOR ENERGlZlNG DISCHARGED .CAPACITORS.
XL AND Xc ARE IN t ON THE SWITCHED CAPACITOR

Fig. 25-Magnitude and Frequency of transient inrush current when energizing a bank in parallel with one existing
. bank.
252 Application of Capacitors to Power Systems Chapter 8

FIXED L The voltages of Table 8 are brought about by the fact


15X IO-6 HENRY that 100 percent voltage is left on L4phase, the first phase
10,000 to open. The very instant A phase opens, a charge
Dcs2r-: of 50-percent voltage is left on phases B and C because the
instantaneous voltage across these two phases is 50 per-
v) 0000
cent. The neutral point of the capacitor bank remains at
360 KVAR 360 KVAR
192,4mlF 192 ,UF
a potential of 50 percent above ground, which appears
z i T across the capacitance to ground. The sltbsequent voltage
k!
a applied across B and C when R or C clears is 173 percent,
7 6000 half of which is across B capacitor and half across C capaci-
s tor. But the 50-percent charge left on these two phases,
kf
ADDED L
\\-hen A opened, is still present and adds or subtracts from
Q
2 4000 OHMS AT half of 173 percent giving a net of 37 percent or 137 per-
Y
60 CYCLES cent. Similar analyses can be made for delta-connected
ZTi capacitors.
a 2000 o”.Ol The voltage across the contacts of the circuit breaker is
0.1 important because if the recovery rate or the magnitude is
too great, restriking occurs across the contacts. Such re-
striking cause switching surges that may produce peak
0’
0 0.2 0.4 0.6 0.0 I .o voltages of several times the normal peak voltage to
RESISTANCE-OHMS ground. Special consideration should be given to this
Fig. 26-Test results indicating the effect of reactance and problem in each case. The problem is more acute at volt-
resistance on limiting energizing inrush current. ages above 15 kv. Careful adjustment of the breaker can
make an otherwise unsatisfactory condition one which is
of reactance or resistance into the circuit. Reactance is acceptable. Special treatment with respect to the oil flow
much more effective than resistance. The curves in Fig. in the breaker grid during interruption usually solves the
26 give the results of tests showing the effect of adding problem. In extreme cases it may be necessary to limit
resistance or reactance in reducing the peak inrush cur- restriking on de-energizing by inserting in series or parallel
rent. D-c voltage was used to charge one group of capaci- with each phase of the capacitor circuit a suitable resistor
tors; the voltage was then removed and Iv-hen the switch just prior to the operation of the circuit breaker to de-
was closed between the two groups, the peak current was energize the bank. A careful analysis of the problem
measured. should be made for each application; laboratory and field
tests may be necessary.
21. Voltages When Switching Off Capacitors
Since the current goes out at normal current zero when 22. System Harmonic Voltages
de-energizing a bank of shunt capacitors, the rms voltages Since the reactance of a capacitor varies inversely as the
resulting can be calculated. The voltages to ground, re- applied frequency relatively small harmonic voltages cause
covery voltage across circuit breakers, and the line-to- relatively large current-wave distortion. Capacitors are
line and line-to-neutral voltages across the capacitors are therefore built to permit combined harmonic and GO-cycle
important. The voltages of Table 8 expressed in percent kvar to equal not more than 135 percent (AIEE Standard)
of normal peak line to neutral voltage are obtained when of the capacitor nameplate rating. The kvar loading of a
the supply system is grounded solidly and does not suffer capacitor expressed as a fraction of its rating with har-
neutral displacement while switching a wye-connected monic voltages applied can be obtained as follows:
ungrounded capacitor bank. For a normal breaker open- KVA= E12+3E3?+5ES2+. . where all voltages are
ing, one phase is interrupted first even for a well adjusted expressed as a fraction of the rated voltage. If only one
breaker, at current zero, and 90 degrees later the other harmonic is present, it can have a value of
two phase currents are interrupted simultaneously at
E = 1.35-E:
~-
current zero by the clearing of either B or C breaker con- N (15)
tact. J n

TABLE 8
where n is the order of the harmonic.
The standard margins in capacitors are usually more
Percent of than sufficient for the amounts of harmonic voltages
Peak Voltage present in most systems and, therefore, very little trouble
is experienced. The principal cause of harmonic currents
Phase of Wye Connected Bank A B C in capacitors is the magnetizing requirements of system
___--
Sequence of Opening.. 1st 2nd 2nd transformers. If the transformers are operated near their
hlasimum E to Ground after Opening. . 150 87 87 rated voltages, the harmonic voltages are limited to
Maximum E across Corresponding Breaker minimum values. Capacitors do not generate harmonic
Pole................................. 250 187 187 voltages.
Maximum Voltage across Capacitor Leg Harmonic frequencies usually encountered are the third
Following Interruption. 100 37 137 and fifth. The capacitor has lower reactances to higher
Chapter 8 Application of Capacitors to Power Systems 253

frequencies and therefore allows proportionately larger sizes of capacitor banks, the discharge current reaches half
clrrrrnts. Figure 27 shows the amount of total rms current, value in about 0.02 second, or less. Breakers normally
fun~lnmcntal and one harmonic, which standard capacitors applied with capacitor banks are capable of handling
can WL’I’V, depending on how much total rms voltage, these currents.
flrndament~al and harmonic, exists at the same time. For
example, suppose the fifth harmonic and the fundamental
24. Harmonics and Coordination with Telephone
arc present, and the total rms voltage is 105 percent. Then
Circu$.-
The principal cause of harmonic voltages and currents
220, , , , , , ( , , , ( , ) , in capacitors is the magnetizing requirements of trans-
, 1
formers. Because of the lower impedance of capacitors at
higher frequencies, the harmonic currents may become so
high as to endanger the life of the capacitor, or cause
excessive fuse blowing, or overheating of breakers and
16 switches. The standard margins built into capacitors,
which were mentioned previously, are usually sufficient
so that for the amount of harmonic voltage present in
160
most systems no undue amount of trouble is esperienced.
For the transformer magnetizing current the third hnr-
140 manic components and their multiples are supplied usually
by circulation around the delta connected windings. The
higher harmonics are usually so small that they give no
120 appreciable trouble as long as the transformers are operated
m near their rated voltage.
5
a ,001 ’ ’ ’ ’ ’ ’ ’ ’ ’ ’ ’ ’ ’
I I An unbalanced fault on a system supplied by water-
100 105 110 115 wheel generators without damper windings may produce
harmonic voltages. By resonance or partial resonance with
RMS MEASURED VOLTS IN ?&OF RATED VOLTAGE
capacitors these voltages can be magnified. While the
Fig. 27-Permissible harmonic currents. For 135 percent kvar duration of the fault might not be sufficiently long to
for different fundamental voltages without exceeding ther- injure the capacitor, it may result in blowing of capacitor
mal limits. fuses all over the system. This hazard is reduced by proper-
ly designed damper windings and system arrangement.
t,he total current the capacitor can carry is 161 percent. Considerable study has been given the effects of shunt
This is made up of about 102-percent rated amperes at capacitors on the inductive coordination of power systems
fundamental frequency and about 125-percent rated -
:lmperes at fifth harmonic. The corresponding voltages I20,000
are 1OZpercent fundamental and 25-percent fifth har-
monic. u-i
Q
Breakers applied with shunt capacitors must have ‘,
sufficient continuous current-carrying capacity to handle ; 100,000
expected harmonic currents along with the rated-frequency 5
current. is THREE-PHASE FAULT
s 80,000
23. Discharge Current 0 -IO00 MCM BUS CON.DlJCTOR
When a capacitor is short circuited, either at its termi- f - - 500 II II
~1s or through a length of feeder, it discharges its stored 3
“ncrgy determined by i 60,000
::
Stored energy= l ClP (16)
$
If the short circuit occurs at the instant the voltage on the 2 40*ooo
capacitor is a maximum, then the stored energy is a maxi- 2
mum. The stored energy is dissipated in the resistance of
the circuit which includes the capacitor and the feeder up
to the short circuit. The peak current, the frequency of the
current and the time constant of the circuit can be calcu-
lated for a given situation. Figure 28 shows the peak value
ot current calculated for various lengths of bus consisting 0’ I I I I
0 50 100 150 200
of single-conductor cables with an equivalent delta spacing
LENGTH OF BUS-FEET
of four feet. The peak current is high in magnitude but
since the frequency is high and the time constant of the Fig. 28-Peak current supplied to a three phase fault through
circuit low, the current decreases rapidly. For all practical various lengths of bus from shunt capacitor banks.
C 1

254 Application of Capacitors to Power Systems Chapter 8

and exposed t,elephone circuits at noise freqllencies. These of conditions is directly proportion.al to the voltage on the
studies have bcon carried on by the *Joint Subcommit,tct: air-gap line of the generator corresponding to the excitation
on Development and Rcsenrch of the Edison Electric Tn- current. Therefore, as more shunt capacitors are added
stitut,e and I{ell Telephone System. The results of their to a system, the power factor of the generators increase
preliminary study of the problem were inch&xl in an and consequently the exciting current decreases. As the
article published m the August, 1938 issue of the Edison exciting current is decreased, the voltage on the generator
Electric Instit,utc Bulletin. It, has been found that t)hc use air-gap line rlecreascs. The static stability limit is therefore
of capacitors may bc either detrimental or beneficial from proport’ional to generator exciting current. Generally on
the inductive coordination standpoint, depending on the turbo-generators, if the operating power factor at full load
particular conditions in each case. Advance planning by is no greater than 95 percent 1~Lgging, experience has shomn
the power and communication industries has reduced the that the operation is safe. In some cases generators are
number of trouhlcsomc situations to a small percentage of operated between 95 percent lagging and 100 percent
the capacitor installations. Where capacitors have resulted power factor with satisfactory performance. Few, if any,
in increased noise, it has generally been practicable to generators are operated consistently at power factors in
improve conditions by rclntivcly simple measures applied the lead unless the generators are designed specifically for
to either the power or communication systems or both. such service. Hydra-generators may also be affected by
A summary of the available measures is included in the shunt capacitors, but usually thesc generators are so far
article mcntionetl above and in Chap. 23 of this book. removed electrically from capacitors that the generators
are affected more by other factors such as the character-
25. Portable Capacitors istics of transmission lines and the sending of power over
Portable capacitor units such as shown in Fig. 29, are relatively long distances.
effective in relieving overloaded facilities until more per- Any generator, regardless of its prime-mover, may be
manent changes in the system can be made. Two single- affected by systemshunt capacitors and therefore the prob-
lem should always be taken into consideration. This is
particularly important where large amounts of shunt ca-
pacitors are planned for systems where generators are
already operating at high power factors. X few power
systems have this problem now and more will probably
have the problem as future plans are made to get better
overall system economy by taking advantage of the char-
acteristics of shunt capacitors. This problem also has a
direct bearing on how much capacitor kvar can be per-
manently connected through minimum-load periods with
few generators in service and how much capacitor kvar can
be installed with switching to provide needed kvar during
maximum load periods and maximum generation.
27. Surge Protection of Shunt Capacitors
On circuits exposed to lightning it is recommended that
lightning arresters be provided on all delta-connected ca-
Fig. 29-Portable capacitor bank. pacitors either housed or hanger type large or small banks.
Likewise arresters are recommended for all wye-connected
phase mobile capacitor units can be used to reduce the capacitor banks where the neutral is ungrounded. Where
overload on open-delta banks of transformers occasioned the capacitor bank is switched, it is best practice to provide
by the failure of one transformer of a three-phase delta- arresters on the capacitor side of the circllit breaker.
connected bank. In the open-delt,a application the most A capacitor bank connected in mye with the neutral
effective use of the capacitors is to plan twice as much grounded has the ability of sloping off the front and reduc-
capacitive kvar across the phase lagging the open side of ing the crest of traveling waves, so that it affords added
the delta as is placed across the open side. lightning protection to the capacitor bank itself and to
transformers and other adjacent equipment. Thus there
26. Capacitors and System Stability is some question as to whether or not arresters are needed.
Shunt capacitors reduce the static stability limits of In addition, for those surges where arresters are required
generators (and systems) because they reduce the field there is also some hazard to the arrester because the ca-
currents used for a given km load and terminal voltage. pacitor discharges through the arrester when the arrester
The effect is noticed by an increase in generator power operates. When the capacitors are connected to a bus with
factor as more and more shunt capacitors are added. Ac- transformers and other circuits, arresters are required to
tually many factors are involved in determining the static protect this other equipment whenever the capacitor bank
stability limits of generators, some of which are difficult is disconnected. The arresters are therefore available and
to evaluate. However, the effect of shunt capacitors can in service at all times. Where t,he capacitor bank is the
be determined rather directly. only load on a transformer winding the arresters can be
The static stability limit of a generator for a given set omitted if the transformer is rcmovcd from service when
Chapter 8 Application of Capacitors to Power Systems 255

all capacitors are disconnected. Where the capacitors are the kva rating for 3000 kva units to about 13 percent for
S,,pplietl from a third winding of the transformer, arresters very large unit,s of 50 000 t,o 100 000 kva. For capacitors
m:1y bc required on this winding if all of the capacitors are the losses arc about one-third of one percent of the kvn
10 he orit of service at times. rating. The no-load losses of air-cooled synchronous con-
Jcrorn a surge-protection point of view for greatest safety densers are about 60 percent of the full-load losses and fol
to the: arrcstcrs, wye-conncctcd capacitor banks should be hydrogen-cooled synchronous condensers about 10 pcr-
ol,,lr:ltrtl ~mgrolmtletl. For best surge protection of the cent; therefore, at fractional loads the losses of the syn-
,;lp:Gt,ors, the neutral should he grounded and arresters chronous condenser are not in proportion to the output in
~,~ovitlecl.There are other problems n-ith capacitor banks, kva. For a capacitor, however, the losses are proportional
IllI\\-cver, which make the wye-grounded bank undesirable. to theT%r connected to the system.
‘J’llc gro~~ntled-ncutr:ll bank provides a path for the third 6. A comparison of the cost of synchronous condensers
or rcsitlunl harmonics, thereby increasing the probability and capacitors involves an evaluation of the losses. Figure
of communication interference; if a capacitor unit becomes 30 gives an idea of the relative cost of air-cooled outdoor
sllortocl, where there is a single unit between line and
~1~~ll(ral,the fault current can exceed the ability of the fuse
(0 (.lcar before the capacitor unit is ruptured.
1,ightning arresters protecting high-voltage capacitor
i,:mks above 15 kv arc subjected to switching sllrges, when
111~capacitors are switched, whether or not the capacitor VITHOUT
IXLII~neutral is grounded. With restriking across breaker
c~ontacts,which may occur, the arresters may be damaged.
‘I’llrrctfore it is necessary to provide means of limiting the
t~rilting in the breaker to protect the arresters. The
s(Jlllt,ion in a given case may require special field tests to
tI(,tcrmine the proper adjustment of the breaker or to
tlctcrminc what changes are necessary.
28. Capacitors Versus Synchronous Condensers
In large units synchronous condensers constitute a com-
pct,itor of shunt capacitors. The following points should
IIC conaiclcretl in comparing these two types of equipment. LOSS EVALUATED /
1. h standard synchronous condenser is capable of sup- A-AT $150 PER KW
plying kvars equal to its rating to the system as well as E-AT $250 PER KW
:It)sorbing them to an extent equal to 50 percent of its
r:~t,ing. For those applications requiring these chnracter-
islics, the comparison should be on a basis of the synchro-
nous condenser against the capacitor at full kvar plus a
slllmt reactor of 50 percent kvar. IO 20 30 40 50
2. The fineness of control of the synchronous condenser
MVA RATING
cLannotbe duplicated by the capacitor unless a large num-
I)clr of switching steps are used. Fig. 30-Approximate relative cost of shunt capacitors and
synchronous condensers. (Capacitors connected in ,wye and
3. An instantaneous drop in terminal voltage, within switched in five steps. Costs do not include mai!n circuit
practical limits, increases the kvar supplied to the system breaker, land space, foundations, or space parts, but do
in the case of a synchronous condenser whereas a similar include freight, automatic control, erection, capacitor fuses,
c411angc in the case of capacitors decreases the kvar supplied coolers on synchronous condensers, and so forth.)
to the system. In this regard the synchronous condenser
IUS greater stabilizing eRect upon system voltages and synchronous condensers and capacitors. Three evaluations
likewise tends to maintain synchronism between machines. for losses were assumed 0, $150, and $250 per kw. The low
Its mechanical inertia, in general, has a further stabilizing losses of the capacitors should not be evaluated as highly
cf’fect upon the other synchronous machines comprising as those for the synchronous condenser because, as just
the system. By reason of these same characteristics, a mentioned, at fractional loads the losses decrease more
synchronous condenser reduces the effects of sudden load rapidly than for the synchronous condenser.
changes or rapidly varying loads, such as drop in system 7. Capacitors lend themselves to distribution at several
voltage occasioned by starting of a large motor or operation locations throughout the system, which is difficult to do
Of large welders. economically with small synchronous condensers. Thus,
4. For short periods the synchronous condenser can capacitors can be located at points closer to the load and
steeply kvar in excess of its rating at normal voltage, be more effective.
\vl~ercasthis is not the case for capacitors. 8. The kvar rating of a capacitor installation can be
5. The losses of synchronous condensers are much increased or decreased as the loads and system require-
great,er than thosd of capacitors. For synchronous con- ments dictate, which is impractical with synchronous con-
densers the full load losses vary from about 3 percent of densers. Capacitors can be installed easily. By moving
2.56 Application of Capacitors to Power Systems Chapter 8

capacitors from point to point as required, the installation A series capacitor in an a-c circuit introduces negative
of other equipment such as transformers, may be deferred. or leading reactance. Current through this negative re-
Icoundations are less important than for synchronous actance causes a voltage drop that leads the current by
condensers, and auxiliaries are fewer and simple. 90 degrees. This drop is opposite from that across an
8. A fnihlre of a single fused unit in a bank of capacitors inductive reactance. Thus a series capacitor at rated fre-
affects only that unit and does not jeopardize operation quency compensates for the drop, or part of the drop,
of the entire bank. A failure in a condenser removes the through the inductive reactance of a feeder. The effects
entire ability to produce kva. On the other hand, failure of this compensation are valuable in two classes of appli-
of a synchronous condenser is less likely to occur than cations: one, on radial feeders to reduce voltage drop and
failure of a single unit in a bank of capacitors. light flicker; and, two, on tie feeders to increase the ability
10. Synchronous condensers add to the short-circuit of the feeder to transfer power and help the stability of
current of a system and may increase the size of breakers the system.
required. This is rarely, if ever, the case with shunt ca-
pacitors. On the other hand, breakers used in the switching 30. Effects on Radial Feeders
large banks of capacitors may involve large currents of The action of a series capacitor to reduce voltage drop
short duration. In general, however, these currents fall is illustrated in Fig. 31. The voltage drop through a feeder
\vithin circuit-breaker ratings dictated by the power is approximately
system.
IR cos OfIX, sin 0 (17)
29. Capacitors and Synchronous Condensers where R is feeder resistance, XL feeder reactance, and 0 the
Ranks of shunt capacitors have been used in conjunction power-factor angle. If the second term is equal to or
with synchronous condenser where fluctuating loads of low
power factor are prevalent or where the steps in the ca-
pacitor bank were too coarse to give the desired fineness Es
of voltage control. In this way the economy of using shunt ES ER

capacitors for part of the kvar correction can be had by (a) <G,
using one or several steps of capacitors with breakers. I-

\Vhere the voltage of the bus is controlled by the com-


bination of capacitors and condenser, the master control
would be from the bus voltage. It is more likely though
that the bus voltage will be controlled by other means such
as a tap-changing-under-load supply transformer, and that
the object of using the kvsr corrective equipment is for
power-factor regulation. In such cases the control of the IR COSe
kvar must be accomplished by a power-factor regulator. I(XL-Xc) Sinv-4 e

Fig. al---Voltage vector diagrams for a circuit of lagging


V. SERIES CAPACITORS FUNDAMENTALS power factor (a) without and (b) with series capacitors. The
series capacitor increases the receiving-end voltage, thus
Like the shunt capacitor, the series unit has application reducing voltage drop.
on transmission and distribution lines. Behavior of the
shunt capacitor is generally well understood and can be
accurately predicted. The same is not always true of the greater than the voltage improvement desired, a series
series type. Many questions are still unanswered and capacitor may be applicable. The magnitude of the second
many problems are still unsolved. However, developments term is a relatively larger part of the total voltage drop
and experience of recent years are bringing new knowledge where power factor is low and where the ratio of feeder
and maturity to the science of applying series capacitors to resistance to reactance is small. With a series capacitor
improve conditions on distribution and transmission lines. inserted, Fig. 31(b), the voltage drop becomes
Constructionwise, shunt and series capacitors are iden-
tical. In fact, should the need for a series capacitor dis- IR cos B+I(XL-X,) sin 0 (18)
appear, the capacitor units can be removed and reinstalled
as shunt units. The two types differ in their method of or simply IR cos 0 when X, equals XL. In most applica-
connection. The shunt unit is connected in parallel across tions the capacitive reactance is made smaller than feeder
full line voltage. The series unit is connected in series in reactance. Should the reverse be true, a condition of over-
the circuit and hence conducts full line current. While compensation exists. Overcompensation has been em-
the voltage on a shunt installation remains substantially ployed where feeder resistance is relatively high to make
constant, the drop across the series bank changes instan- I(XI,- Xc) cos e negative. However, overcompensation
taneously with load, as with any series device. It is this may not be a satisfactory condition if the amount of ca-
characteristic, which produces an effect dependent on load, pacitance is selected for normal load, because during the
that makes the series capacitor extremely valuable in cer- starting of a large motor the lagging current may cause an
tain applications by compensating for line series inductive excessive voltage rise, as shown by Fig. 32. This is harmful
reactance. to lights and introduces light flicker.
Chapter 8 Application of Capacitors to Power Systems 257

Step voltage or induction voltage regulators, also, are not


sufficiently rapid to follow sudden voltage fluctuations.
The voltage dip cannot be prevented by shunt capacitors
or regulators as the dip itself is used to initiate the
correction.
32. Effects on Tie Feeders
Fig. 32-The high lagging current due to motor starting Series capacitors can be applied to tie feeders to increase
rapidly raises the receving-end voltage of a circuit which is power-transfer ability and improve system stability rather
over-compensated with series capacitors. than t6Gprove voltage regulation as on radial feeders.
The vector diagrams and Eq. (17) and Eq. (18) still apply
The power factor of the load current through a circuit but the emphasis is now on power transfer and stability.
must be lagging for a series capacitor to decrease the volt- For simplicity, assume the feeder impedance consists only
age drop appreciably between the sending and receiving of inductive reactance. Since the effect of resistance is
ends. If power factor is leading, the receiving-end voltage small in most tie-feeder circuits, it can be neglected with-
is decreased by the addition of a series capacitor, as indi- out materially affecting the results. Referring to Fig. 34,

Fig. 33-When the load power factor is leading, a series ca-


pacitor is undesirable because it decreases the receiving end
voltage. Fig, 34-Vector diagram for a tie feeder in which resistance
effects are neglected.
cated by Fig. 33. If the power factor is near unity, sin 0
and consequently the second term of Eq. (18) are near the simplified equation for the amount of power transferred
zero. In such cases, series capacitors have comparatively through a tie feeder is:
little value.
When properly applied, a series capacitor reduces the ESsin
P=EaXLcosPe(COS
0)= F sinfl (lOi
impedance of a line and thereby raises the delivered volt-
ngc. This increases the kva capacity of a radial feeder and, where /3 is the angle between the sending (Es) and receiv-
for the same delivered load kva, siightly reduces line cur- ing (E,) voltages. With a series capacitor, the expression
rent. A series capacitor, however, is not a substitute for for power transfer is
line copper.
p= Ed% sin p (20)
31. Light Flicker XL-X,

Series capacitors are suited particularly to radial circuits Therefore, for a given phase-angle difference between the
where light flicker is encountered due to rapid and repeti- voltages, the power transfer is greater with a series ca-
tive load fluctuations, such as frequent motor starting, pacitor. Thus by making possible a greater interchange
varying motor loads, electric welders, and electric furnaces. of power, the normal load transfer and the synchronizing
:1 transient voltage drop, which causes light flicker, is power flowing during transient conditions are increased,
reduced almost instantaneously in the same manner as thereby helping stability. This is illustrated in Fig. 3.5,
voltage drop due to a slowly increased load. To predict
:~ccurately the reduction in voltage flicker by series ca-
I)acitors, the current and power factor of the sudden load
increment must be known. It is obvious that to improve
voltage conditions or reduce light flicker at a given load
point the series capacitors must be on the source side of
that point. The series capacitors must compensate for line
inductance between the source and the point, where it is
desired to reduce light flicker. This sometimes makes the
application of capacitors difficult because one feeder from
a bus with several feeders may have a fluctuating load that
Produces sufficient voltage change on the bus to cause light
flicker on all feeders. To use series capacitors to reduce
the flicker, they must be installed in the supply circuit
or circuits to the bus. Angle B-Degrees
Shunt capacitors cannot be switched fast enough to Fig. 35-The power-transfer ability of a tie feeder may be
Prevent light flicker. In fact, an attempt to use shunt increased from curve (a) without series capacitors, to curve
capacitors for this purpose might aggravate the situation. (b) with series capacitors.
258 Application of Capncitors to Power Systems Chapter 8

which shows that for the same angle, a series capacitor the beneficial effect of series capacitors. Applications to
effects a 40-percent increase in power-transfer sbility- radial circuits supplying loads of 70 to 90 percent power
and also the maximum power that can be transferred. factor are most likely to be succesSfu1.
Furthermore, to transfer the same amount of power The application of series capacitors differs materially
through the tie feeder, angle fl is smaller, which aids from that of shunt capacitors. Where voltage correction
stability of the system. is the primary function of shunt capacitors the correction
.I series capacitor on a radial feeder is ineffectual unless is obtained by raising the power factor of the load. To
the load power factor is lagging. This is not as important determine the shunt capacitor kvar required, the most
in most tic feeders as can be seen from Eqs. (19) and (20). important data needed are the magnitude of the load, its
Power transfer is affected primarily by the angle between power factor and the impedance of the source circuit.
the sending and receiving voltages and not as much by While similar data are required for voltage correction with
power factor. series capacitors, the effect of series capacitors is to reduce
the reactance of the source circuit. Series capacitors affect
33. System Power Factor Improved power factor to a limited extent as compared with shunt
The lagging kilovars supplictl by a series capncit,or im- capacitors because usually the kvar in a series capacitor is
prove system power factor, just as a shunt capacitor or an much smaller, being one-fourth to one-half of the shunt
overexcited synchronous machine, but to a much smaller capacitor kvar for the same change in load voltage. In
extent. In effect, the capacitor compensates for the I’SL addition, the series capacitor contriblltes its kvar to the
“lost” in the feeder reactance. The amount of compcnsa- system as the square of the load current.
tion varies, of course, as the square of the current since
the kilovars supplied equal PX,. At half load, for example, 35. Determination of Capacitor Rating
only one-quarter rated kilovars is provided. A three-phase circuit containing a series capacitor con-
sists of line resistance, line inductive reactance, and ca-
34. Relative Effect of Power-Factor Correction pacitive reactance. The kva ratings of these components
;I shunt capacitor improves load voltage by nerltralizing are 3I?R, 312XL, and 3PX,. These values as a percent of
part of the lagging current in a circuit, thereby reducing the total circuit rating are useful in considering the useful-
the line current and voltage drop. A series capacitor im- ness of series capacitors. The percent rating is obtained
proves load voltage more effectively by compensating by dividing the kva rating of each element times 100 by
directly for part of the feeder reactance, which causes the the total circuit kva rating (&%‘,I) which must be known.
voltage drop. Consequently, the same voltage correction The percent rating of the capacitor equals 300 IS,l&E’,
is obtained with a smaller rating of series capacitors than (or 173 1X,/E,) where I is full-load rating of the circuit
shunt, usually in the ratio of one half to one fourth. Hom- and E, is the load line-to-line voltage.
ever, because the amount of power-factor correction in- Calculation of kva ratings as a percent of circuit rating
creases with capacitor kvar rating, the shunt capacitor can be extended to voltage. The voltage drops, IR, IXL,
corrects power factor to a greater extent. and ILYy, times lC0, are divided by the circuit voltage
For example, on a 10 OOO-kvacircuit having a load power rating E,/d% The percent of the capacitor again equals
factor of 80 percent and an R/X ratio of 0.3, 1100 kilovars 173 IXC/ER. Consequently, the percent ratings of each
of series capacitors are required to limit the voltage drop component on a kva base and on a voltage base are iden-
to 10 percent. This capacitor raises the source power factor tical. Therefore, a series capacitor rated 20 percent on the
from about 74 to about 78 percent. If a shunt capacitor base of circuit kva is also rated 20 percent on the base of
is used in this circuit to obtain the same volt’age correction, circuit voltage. These ratings mean that at full load, the
3800 kilovars are required, but the source power factor is capacitor “consumes” 20 percent of rated circuit kva and
raised from 74 percent to 91 percent lagging. the voltage drop across its terminals is 20 percent of rated
To increase materially the source power factor as well circuit voltage.
as improve voltage, shunt capacitors at or near the load The rating of a series capacitor (kilovars, voltage, and
offer the best solution. Usually shunt capacitors must be current) for a radial feeder depends on the desired voltage
switched in one or more groups to keep wit,hin desired regulation, the load power factor, and the amount of resist-
voltage limits as load varies. Shunt capacitors do not ance and reactance in the feeder relative to each other and
reduce light flicker because they cannot be switched on to the circuit rating. The capacitor kilovar rating can be :
and off fast enough to counteract rapid fluctuations in determined for 80 or 90 percent load power factor and 5 i
voltage. or 10 percent circuit voltage drop from data given in the 1
curves of Fig. 36. To use these data, the feeder rating is :
taken as 100 percent kva’and all other figures are calculated 4
VI. APPLICATION OF SERIES CAPACITORS
in percent on this base. For example, assume a 10 OOO-kva i
In general, series capacitors are applicable to radial feeder having an inductive reactance of 20 percent and a :
circuits supplying loads of about 70 to 95 percent lagging ratio of resistance to reactance of 0.3 supplying a load 1
power factor. I3elow 70 percent, shunt capacitors are more whose power factor is 80 percent. From Fig. 3A, to limit $
advantageous (unless the power factor changes over such the voltage drop to 5 percent at full load, the series ca-
a wide range, making it impossible to switch shunt ca- pacitor must be rated 20 percent of the circuit rating. This
pacitors fast enough to supply the kvar required by the is 20 percent of 10 000 kva or 2000 kilovars. The capacitor
load). Above 95 percent, the small value of sin 0 limits voltage rating is also 20 percent of the rated circuit voltage.
Chapter 8 Application of Capacitors to Power S@ems 259

rather than load transfer may dictate the capacitor rating


for a tie-feeder application.
36. Arrangement of Capacitor Units
When the kilovar, voltage, and current ratings of the
bank are known, capacitor units are arranged in series-
parallel connections to obtain the desired values. S&es
connect,ion builds up the voltage rating and parallel con-
nections the current rating. Each bank must be “tailored”
to fulfill the rey&%nents of that specific application.
Capacitor banks can be assembled for any current rat-
ing and for almost any voltage rating, standard or non-
standard. If the voltage across the bank is less than 230
volts, it may be economical to install a series step-up trans-
former to permit using st,andard capacitor units of higher
voltage and lower cost.
37. Location of Capacitors
In general, a series capacitor can be located at any
IO 20 30 40 convenient place on a feeder provided that certain reqllire-
Circuit Reactance-Percent on Circuit Rating
ments are met. First, the voltage level at the output
Fig. 36-Kilovar and voltage ratings of a series capacitor for a terminals of the bank must not be too high for the line
radial feeder may be determined for many cases from these
curves. insulation and lightning arresters; and second, a capacitor
on a radial feeder must be located between the source and
Thus if the circuit is rated 20 000 volts, phase to neutral, the loud whose voltage is to be improved. Where a radial
the wpacitor is rated 4000 volts. If a voltage regulation circuit has a number of tapped loads distributecl through-
of 10 percent is permissible, only 1100 kilovars (at 2200 out its length, the best location of the series capacitor is
volts) are required. Had load power factor been 90 per- at about one third of the electrical impedance of the feeder
cent,, 2200 kilovars (at 4400 volts) would be necessary for from the source bus. If a feeder is long, two banks of
*?-percent regulation and 900 kilovars (at 1800 volts) for capacitors may be preferable as more uniform voltage is
IO-percent regulation. obtained t,hroughout the circuit. Where short-circuit cur-
Other factors being equal, the ratio of R/XT, has a large rent is high, it may be advisable to locate the capacitor
cf’fect on capacitor rating, as Fig. 36 indicates. Higher so that fault current through the protective gaps and
mtios require more capacitors; this is seen vectorially in switches is a minimum.
Fig. 37. A series capacitor located in a substation can be con-
The current rating of the capacitor equals that of the nected in each phase on the neutral ends of wye-connected
circuit bccausc the bank must be able to carry rated circuit transformer windings to permit use of a lower voltage class
in the capacitor insulation. However, this practice raises
the voltage-to-ground level of the transformer windings.
This must be checked carefully. The effectiveness of a
series capacitor is independent of whether it is connected
on the neutral ends or on the line ends of the transformer
windings. /
Fig. 37-Radial feeders having a higher ratio of resistance to
reactance (for the same percent reactance) necessitate more VII. PROTECTION OF SERIES CAPACITORS I’
capacitors.
38. Protection During Line Fault
current continuously. In addition, when circuits supply For most circuits in which series capacitors are applied,
relatively large motors, the capacitor must be able to carry the currents and correspondin, m capacitor voltages during
temporarily the starting current of the largest motor plus fault conditions are several times the maximum working
the current of other loads already in service. The total of value. As standard capacitor units can withstand about
the transient and steady-state currents through the ca- 200 percent of their rated working voltage for brief periods
Wcitors should not esceed 1.5 times rated. without damage to the dielectric, it is necessary to use
The rating of a series capacitor applied to a tie feeder capacitors with continuous current ratings equal to 50 per-
is determined from a st,udy of the power-transfer and cent of the maximum current that may flow during a fault,
stability requircmcnts. No definite rules can be stated, or to use a voltage-limiting device. For a given reactance,
1Nlt in general, the capacitive reactance of a series ca- the cost of capacitors increases approximately as the square
P:witor is less than (probably not more than 70 percent) of the rated current so that it is more economical to use
the inductive reactance of the tie line. If the maximum capacitors whose ratings are based on the working current
transient current during a system disturbance is grcatcr and to limit the voltage that can appear across their
than about 1.5 times rated current, stability requirements terminals by means of auxiliary apparatus.
-

260 Application of Capacitors to Power Systems Chapter 8

Care must be used that the voltage rating of the series


capacitor and its associated protective equipment is made
high enough so the capacitor is not by-passed during work-
ing loads. On radial circuits to insure availability of thn
series capacitor during motor starting currents, when its
effects are most useful, the capacitor rating must be at
least 67 percent of the greatest motor inrush current that
may be imposed on the line plus other operating load.
With protective devices set to by-pass the capacitor at
2OO-percent rating, the capacitor remains in service during
sllch transient loads.
The device used to protect a series capacitor during a
fault should limit the voltage rise to about twice the rated
value even for a short time. The capacitor must therefore
be by-passed during the first half cycle of fault current.
A propwly designed gap (shown in Fig. 38) fulfills this
A B

BRONZE
CASTING
Fig. 39-A typical series capacitor on a distribution circuit.
GRAPHITE
ELECTRODE
cleared. This is necessary to enable the series capacitors
GRAPHITE
ELECTRODE to provide system stability. If the capacitors are not re-
inserted within a cycle or less, their full benefit cannot be
realized and their usefulness on tie lines would be reduced
materially both electrically and economically.
39. Protection Against Continuous Overload
Standard series capacitors should not be used for con-
PORCELAIN tinuous operation at an average more than 105 percent of
INSULATOR
their rated voltage. Consequently, average working cur-
rent through a series capacitor should not exceed the rated
working current by more than five percent. The short-
circuit protective device is not designed to function at less
STEEL FRAME than 200 percent of the rated current; therefore, it is some-
Fig. 38-Special gap for parallel protection of series capacitors. times desirable to provide overload as well as short-circuit
protection. The overload protective device should have
requirement and materials can be selected to give a stable an inverse time-current characteristic that can be co-
arc and a low arc drop without repetitive restriking. Under ordinated with the capacitor to allow momentary overloads
most conditions, some means must be provided for shunt- but not continuous ones. Series capacitors have a 30-
ing this gap and transferring the arc current to another minute rating of 1.35 times rated current and a 5-minute
path. After the circuit current again falls to normal, the rating of 1.5 times rated current. X thermally operated
by-pass equipment must open to transfer current back switch can also be used for this purpose.
through the capacitor. This commonly is done with a This special type of protection usually is not warranted
thermal or magnetic contactor or by an automatic circuit except on large series capacitor banks. The absence of
breaker that closes to by-pass the gap and capacitor and overload protection on small distribution installations fur-
opens some time after the fault has cleared to restore the ther emphasizes the need for care in choosing the contin-
capacitor to service. If the installation consists of two or uous current rating.
more groups of capacitor units in series within a bank,
each can be protected by its own parallel gap. 40. Dielectric Failure Protection
Where the insulation class of the series capacitor is low, Dielectric failure protection rarely is used except on 3
for esample, where 230-volt capacitor units are used and largebanks. This also is a feature that is sacrificed on small f
the gap must break down at 460 volts, it is not possible distribution series capacitors in the interest of simplicity ,f
to set the gap for sufficiently low breakdown voltage. In and low first cost.
such instances, a trigger circuit is used to initiate the Dielectric protection is a means of detecting a faulted
break-down of the gap. capacitor unit in a series-capacitor assembly. In an un-
On large series capacitors in transmission tie lines special fused capacitor bank a short-circuited capacitor may SUS-
gaps or special high-speed circuit breakers or both may be tain an internal arc, which causes gas to be generated in
required to protect the capacitors and re-insert them into the unit. Continued operation causes the internal pressure
the circuit within a half cycle or a cycle after the fault is to reach a value that rupture the case and possibly damage
chapter 8 Application of Capacitors to Power Systems 261

other units and equipment. If the units are equipped with The sub-synchronous frequency is dependent on t,he
individual fuses-and they should be-a fuse operation to relative sizes of the motor and the capacitor. The capacitor
remove a faulted unit increases the reactance of the bank rating is determined by the circuit rating (other conditions
%ntl operation at the rated current of the original bank remaining the same, the ratings are proportional). Con-
,ubjects the remaining units to overvoltage. Protection sequently, the resonant frequency is related, indirectly, to
is afforded by detecting with proper relaying when the the rating cf the motor in proportion to that of the feeder.
currents become unequal in two equal branches of the This frequency is usually 20 to 30 cycles for a GO-cycle
cLlpacitor. When the unbalance in current exceeds the motor whose rating equals half the circuit rating.
sclccted value, the capacitor is by-passed until the de- As the motor size decreases with respect to the capacitor
fcctive unit is replaced. and circuit ratings, its reactance increases. During reso-
nance, capacitive and inductive reactance are equal. Ue-
41. Circuit Relaying cause capacitive reactance increases with decreasing fre-
On radial circuits, fault-protection relaying usually is quency, the sub-synchronous resonant frequency is lower
not affected by the addition of series capacitors. Fault when the motor requires a smaller proportion of the circuit
(:llrrcnts practically always considerably exceed twice rated rating. A motor requiring less than five percent of the
clllrent. Consequently the parallel gap breaks down on circuit rating can be resonant at a sub-synchronous fre-
the first half cycle of fault current. This happens faster quency of five cycles or less if it starts under load.
than most types of relays operate and thus relay and The most common method of preventing sub-synchro-
circuit-breaker operations are the same as without capaci- nous resonance is to damp out this frequency by placing
tors. Relaying of line-to-ground faults is accomplished a resistor in parallel with the capacitor. While the resist-
usually by residual or neutral current, which is not affected ance to use can be calculated, the results thus obtained are
greatly by a series capacitor. Fault-protective relaying on -usually one half to one tenth the values that experience
a tie feeder, however, may be affected considerably by the proves necessary. Calculations are inaccurate because of
installation of a series capacitor. Detailed studies must be the difficulty of giving precise consideration to such vari-
made for each case prior to installation of the capacitor. ables as inertia of the motor and load, starting load, speed
of acceleration, the type of starter, and other load on the
circuit. For example, load elsewhere on the circuit, when
VIII. OPERATING PROBLEMS
a motor is started, reduces the possibility of sub-synchro-
Along with the desirable characteristics of series capaci- nous resonance by providing a damping effect similar to
tors, there is the possibility of undesirable phenomena, t,hat of parallel resistance.
usually involving some kind of resonance, which until re- The resistance should be as high as possible in order to
cently has deterred the installation of large banks of series hold to a minimum its continuous losses, which are equal
capacitors even where they otherwise could solve difficult to the square of the voltage across the capacitor bank
system problems. Tn many cases the difficulties can be divided by the resistance. It is common practice, then, to
anticipated and suitable precautions taken to make an apply resistors that are adjustable over a predetermined
installation practical. range, particularly in the larger installations.
Three major phenomena may be encountered in a circuit When low ohmic resistance is used, the resistor can be
employing a series capacitor: sub-synchronous resonance of disconnected after the motor reaches full speed and the
:Lmotor during starting, ferro-resonance of a transformer, risk of resonance has passed. Switching could be accom-
and hunting of a motor during steady-state operation. plished manually or by remote control over a pilot wire
One, two, or all of these may occur. or power-line carrier channel with electrically-operated
switching equipment.
42. Sub-synchronous Resonance During Motor Sub-synchronous resonance can also be avoided by use
Starting of parallel resistors across only two phases of a three-phase
When an induction or a synchronous motor is started, series capacitor. Such a solution is permissible where the
(tile latter as an induction motor) through a series capaci- omission of resistors from one phase does not unbalance
tor, t,he rotor may lock in and continue to rotate at a speed the voltage appreciably. The amount of unbalance is de-
Mow normal or synchronous. This condition is known as termined by the resistance. The higher the resistance, the
srlb-synchronous resonance. It is caused by the capacitor, less the unbalance. Rut the resistance necessary, not the
whose capacitive reactance in conjunction with the induc- degree of unbalance, determines the ohmic value. At least
tive reactance of the circuit and motor establishes a circuit one such installation is in service and is operating satis-
resonant at a frequency below that of the power supply. factorily.
The rotor, in effect, acts as a stable asynchronous gener- Sub-synchronous resonance can exist only during motor
ator. It receives power at rated frequency from the stator starting. Hence, resonance can be prevented by inserting
windings and transposes it to the sub-synchronous fre- resistance in series in the supply leads to the motor instead
quency, which it returns to the circuit containing the ca- of in parallel with the capacitor. A contactor is required
pacitor. This circuit, being resonant, imposes a minimum to short circuit the series resistance after the motor reaches
Of impedance to the sub-synchronous voltage and conse- full speed. If the circuit contains only a few motors such a
quently conducts a large current. A motor operating under scheme may be more economical than a single large resist-
these conditions may be damaged by excessive vibration ance in parallel across the capacitors. To be effective, the
or heating. series resistance must be in the stator circuit of the motor.
262 Application of Capacitors to Power Systems Chapter 8

Resistance in the rotor circuit of a slip-ring motor does not circuit. The possibility that the gap alone can prevent
give the desired damping but, affects primarily the amount ferro-resonance is checked by oscillographic tests after the
of slip between the sub-synchronous frequency and the capacitor is installed.
frequency of the current through the rotor circuit. If tests indicate that the gap is inadequate, fcrro-reso.
If motors are started infrequently, sub-synchronous res- nance can he eliminated by shunting the capacitor with 8
onance can be avoided without using resistance by short resistor or by having a cert,ain minimum load on the trans..
circuiting the capacitor during st,arting. If a temporary former side of the capacitor when the bank is energized,
unbalance is tolerable, the same result can be achieved in Of course, a parallel resistor applied to prevent sub-syr,-
some cases by short circuiting only one phase of the bank, chronous resonance of motors also prevents ferro-resonance
which simplifies the switching equipment. of transformers.
The reactance of a capacitor is inversely proportional In some cases, such as 2400- or 4160-volt circuits, the
to frequency, while that of an inductor is directly propor- voltage rating of a series bank would be very low (and its
t,ional. Hence, in a series circuit consisting of capacitance cost high) if installed directly in the line. To permit appli-
and inductance the voltage drop across the former in- cation of a capacitor having a higher voltage rating, a
crcascs as frequency is reduced. Therefore, a condition of transformer in series with the line is sometimes employed
sub-synchronous resonance in a power circuit causes an to step the voltage up from the required drop in the line
increase in the voltage drop across the capacitor. This to the capacitor rating. Such transformers must be de
voltage may be large enough to cause the protective gap signed carefully to prevent ferro-resonance.
in parallel with the capacitor bank to flash over, thus short A series capacitor, when installed in a long circuit sup-
circuiting the capacitor. This halts the resonant condition plying a transformer of abnormally high steady-state
and permits the motor to accelerate normally to full speed. exciting current, may resonate during normal operation
After a time delay the capacitor is automatically restored at a frequency corresponding to a harmonic component
to the circuit. This sequence of operations may make it of the exciting current. Fluctuating loads may cause such
possible in some installations (particularly where motors resonance even though it does not appear when the trans-
are started rarely) to use the gap alone to prevent sub- former is energized. Resonance in this case is eliminated
synchronous resonance and perhaps eliminate the need for by a parallel resistor, by changing the transformer winding,
parallel resistors. However, heavy-duty gaps in series with or by replacing the transformer with another having a
resistors to dissipate the energy stored in the capacitors normal exciting current.
may be required.
The gap is set to break down at twice rated current 44. Hunting of Motors During Normal Operation
(twice rated voltage) at rated frequency. Consequently, Hunting of a lightly-loaded synchronous motor can be
during sub-synchronous resonance at half rated frequency caused by disturbances such as switching of power circuits
the gap flashes over at rated current since the capacitive and changes in load or excitation of the motor itself. Such
reactance is doubled. The lower the frequency the smaller hunting cannot be directly attributed to resonance. The
the current required to break down the gap. principal factor in predicting hunting is the ratio of feeder
In general, the possibility of sub-synchronous resonance resistance to total feeder reactance (including the series
should be checked for all circuits in which the largest motor capacitor) between the power source and the motor ter-
requires more than five percent of the circuit rating. Es- minals. If the ratio is less than one and is not negative,
periencc indicates that standard motors rated less than hunting is unlikely. .Violent hunting of a synchronous
ten percent of circuit rating encounter no difficulty if motor was encountered upon application of a series ca-
started at no load. In fact, motors rated up to 20 percent pacitor in one instance because the ratio of feeder resistance
usually accelerate satisfactorily if started at no load and to reactance was approximately four.
across the line. I-Towever, when high-inertia loads are in- A synchronous motor, when fed through a long line
volved, the circuit must be checked for sub-synchronous excessively compensated by a series capacitor, may hunt
resonance even if the power requirement of the largest if started during periods of light load. Such hunting is
motor is as low as five percent of the circuit rating. avoided if the power-factor angle of the load (after the
motor is started) is equal to or greater than the impedance
43. Ferro-Resonance in Transformers angle of the circuit (including the capacitor). The tang-
A transformer bank when energized draws a high tran- ent of this impedance angle is the ratio of total circuit re
sient exciting current. If a series capacitor is in the circuit, actance (feeder reactance minus capacitor reactance) to
it may create a resonant condition that causes the high feeder resistance.
current to continue. This is known as ferro-resonance. Hunting is not limited to synchronous motors. Series
Ferro-resonance is cured automatically in most cases by capacitors should not be applied to circuits supplying
the parallel gap. The magnetizing inrush current is prob- either synchronous or induction motors driving reciprocat-
ably of sufficient magnitude and low enough in frequency ing loads such as pumps or compressors. In addition to
to cause a voltage drop to appear across the capacitor (and problems of sub-synchronous resonance, the motors once
across the gap) high enough to break down the gap. As started may hunt, causing objectionable light flicker. The
the transient period approaches its end, the current in the frequency of hunting is sometimes equal to, or a direct
gap decreases. The steady-state current through the gap multiple of, the frequency of power pulsation, which i
for a short period is usually too small to maintain the arc further aggravates the situation. A cure for hunting may i
and therefore the gap clears, restoring the capacitor to the be the installation of a heavy flywheel to increase the 1
!
a
.d
chapter 8 Application of Capacitors to Power Systems 263

tion of the capacitors, the voltage at the bus dropped from


12 000 volts at no load to 10 000 at full load. The full-load
voltage is now about 11 300 volts. Furthermore, voltage
conditions at the tapped point (Fig. 42), xvhich was prc-
viously used only as an emergency supply to a nearby
town, are so improved that this source now provides evcry-
day power service.
The scrics capacitor compensates for 57 percent of the
total circuit reactance up to the 1l-kv steel-plant bus. This
decreases by over 50 percent the magnitude of the change
in voltage level dllring periods of heavy load and also
130

120

110 9
0

Fig. 40-10 000 Kvar series capacitor in 66-kv line showing 100 7
large capacitor housings with somewhat smaller housings for 90
“M
2
parallel resistor units. 73
130 >

\ (b) \ \ _
-0
rotating mass. However, this solution may enhance the \ \
possibility of sub-synchronous resonance, which is equally
~~ndcsirable.

IX. 10 OOO-KVAR SERIES CAPACITOR


Midnight 10 PM 8PM 6PM
.I 10 OOO-kvar series capacitor is in service on a GG-kv Fig. 42-Voltage conditions at tapped load point ia‘l before
latlial circuit having a rated load of 500 amperes. Each and (b) after the 10 000-kvar, 66-kv series capacitor was
phase of this capacitor bank consists of 240 standard 1% installed.
kvar, 2400-volt units, divided into 3 groups connected in
sorics. Each gxwlp, which contains SO units in parallel, reduces flicker voltage. However, the capacitor compcn-
is protected by its own gap and accompanying by-pass sates for 100 percent of the total reactance up to the
thermal switch. tapped load point. As a consequence the change in voltage
This series capacitor, Fig. 40, was installed because the level is reduced even more (about 80 percent) than at the
tlcsired voltage improvement is obtained more efficiently steel-mill bus. Furthermore, the sudden fluctuations at
:wl at less cost than by any other method. The principal the tapped point are almost entirely eliminated.
function of the bank is to improve the voltage level and In addition to the furnace load the steel plant has
&crease flicker voltage at a steel plant where the bulk of several motors, the largest being a 4000-hp wound-rotor
the load consists of four 10 OOO-kva electric-arc furnaces. induction motor. A 400-ohm resistor across the capacitor
The heaviest load normally encountered is approximately gives sufficient damping for successful motor starting and
37 000-kva at about 78 percent power factor. The change prevents self-excitation or sub-synchronous resonance.
in voltage conditions effected by the series capacitor is Such phenomena sometimes occur when large motors
shown in Fig. 41, which indicates that the fluctuations are (relative to the circuit rating) are started through a feeder
reduced and the average voltage level during periods of containing a series capacitor. The resistor, because of its
peak load is increased &out 10 percent. Before installa- continuous losses, is undesirable but esperience has in-
130 dicated that it is essential for successful motor starting.
120
This large series capacitor has been successful. Had a
synchronous condenser been installed at the load instead of
110 i! a series capacitor, the initial cost would have been at least
100
9
I
doubled and the continuous losses would have been much
L I I
“M greater. The installed cost of such a capacitor is estimated
I I I I I I A90 m
to be about sixteen dollars per kilovar.

X. PROGRESS OF SERIES CAPACITORS


About 100 installations of series capacitors arc in service
I I ’ 100 on power circuits throughout the United States. The
best results are obtained where there are no relatively large
I I 90
SAM ZAM 1AM motors and where the capacitive reactance provided by
Fig. 4l-Voltage conditions at the steel-mill bus (a) before the series capacitor is less than the inductive reactance of
and (b) after the series capacitor was installed. the circuit up to the principal load point.
Application of Capacitors to Power Susterns

Good results have been obtained with capacitors in 9. Current Control Broadens Capacitor Application, A. D. Caskey,
circuits supplying electric-arc furnaces, one of the worst Electric Light and Power, Vol. 18, February 1940, pp. 49-51.
types of industrial loads. Series capacitors are ideal for 10. Seventeen Systems Report Smooth Capacitor Performance
M. C. Miller, Electrical Workd, Vol. 113, January 27, 1940 pp:
resistance-welding devices where they can reduce the kva
289, 339-340.
demand by 50 to 75 percent. Welders can be provided 11. Facilities for the Supply of Kilowatts and Kilovars, Hollis K.
with built-in capacitors. If a series capacitor is applied to Sels and Theodore Secly, A.I.E.E. Transactiorhs, Vol. 61, May
an existing welder, modifications to the welding trans- 1942, p. 249.
former must be made to prevent excessive current flow. 12. Kilowatts, Kilovars, and System Investment, J. W. Butler,
While most of the improper operations of series capaci- A.I.E.E. Transactions, Vol. 62, March 1943, pp. 133-137.
tors are due to the fact that circuits with series capacitance 13. Mobile Capacitor Units for Emergency Loading of Transformers
resonate at some frequency, some trouble with protective in Open Delta, H. B. Wolf and G. G. Mattison, A.I.E.E. Tram-
devices has been encountered. But with new developments actions, Vol. 62, February 1943, pp. 83-86.
and information and experience gained on recent applica- 14. The 13,500 KVAR Capacitor Installation at Sewport X’ews,
E. L. Harder and V. R. Purrack, Southeastern Aleeting of
tions, more reliable performance is now expected. Some
AIEE, Roanoke, Va., November 16, 1943.
types of equipment should not be supplied through series 15. Analysis of Factors Which Influence the i\pplication, Opera-
capacitors because of difficulties that at present cannot be tion, and Design of Shunt Capacitor Equipments Switched ia
overcome. Overcompensation except in very special cases Large Banks, J. W. Butler, AIEE Great Lakes District lleeting,
should be avoided as it produces undesirable results. Minneapolis, Minn., September 27-29, 1939.
Twenty years ago shunt capacitors were used to a very 16. Extending the Use of Shunt Capacitors by Means of Automatic
limited extent. Today thay have been universally ac- Switching, W. II. Cuttino, AIEE Summer Meeting, St,. Louis,
cepted as practical, reliable, and economical solutions to Missouri, June 26-30, 1944.
many problems involving voltage level, power-factor cor- 17. Tests and Analysis of Circuit Breaker Performance When
rection, equipment loading, etc. Many shunt capacitors Switching Large Capacitor Banks, T. W. Schroeder, E. W.
Boehne, and J. W. Butler, A.I.E.E. Transacfions, Vol. 62,
rated over 5000 kva and a few over 10 000 kva are in
1943, pp. 821, 831.
operation. Cndoubtedly the same evolution is now in 18. Automatic Switching Schemes for Capacitors, W. H. Cuttino,
process with series capacitors. Several series capacitors A.I.E.E. l’ransactions, Vol. 66, 1947.
rated over 1000 kva and one installation of 10 000 kva 19. Power Capacitors (Book), R. E. Alarbury, McGraw-Hill Book
have been installed. Perhaps the “ice” has been broken Co., Inc., New York, N. Y., 1949.
and other large installations will follow. Experience gained 20. The Why of a 25-KVAR Capacitor, i\I. E. Scoville, General
on the 10 OOO-kva installation certainly indicates that Electric Review, Vol. 52, No. 5, ?vIay 1949.
large series capacitors applied carefully are economical Series Capacitors
and successful in operation. Still further progress is likely 21. Series Capacitors, R. E. Marbury and W. H. Cuttino, Electric
to result from studies now being made on the application Journal, ?\larch 1936.
of large series capacitors to extra-high-voltage transmis- 22. Analysis of Series Capacitor Application Problems, J. W. Butler
and C. Concordia, A.I.E.E. Transactions, Vol. 56, 1937, p. 975.
sion lines. A large series capacitor is now being installed
23. Series Capacitors for Transmission Circuits, E. C. Starr and
and tested in a 230-kv line in the Pacific Northwest.
R. D. Evans, A.I.E.E. Transactions, Vol. 61, 1942, p. 963.
24. Characteristics of 400-Mile 230-KV Series Capacitors, B. V.
Hoard, A.I.E.E. Transactions, Vol. 65, 1946, p. 1102.
REFERENCES 25. Design and Protection of lO,OOO-KVA Series Capacitor for
Shunt Capacitors 66-KV Transmission Line, A. A. Johnson, R. E. Marbury,
J. M. Arthur, A.I.E.E. Transactions, Vol. 67, 1948.
1. Capacitors Reduce Losses and Raise Voltage, W. H. Cuttino 26. 10 000 KVA Series Capacitor Improves Voltage in 66-KV Line
Southern Power and Industry, October 1941. Supplying Large Electric Furnace Load, 13. M. Jones, J. M.
2. Use the Right Capacitor with Induction hlotors, J. B. Owens, Arthur, C. M. Stearns, A. A. Johnson, A.I.E.E. Transactions,
Factory Managenlenl and Maintenance, May 1945. Vol. 67, 1948.
3. Safe Capacitor Selection for Power Factor Improvement, J. E. 27. Design and Layout of GG-KV 10 OOO-KVA Series Capacitor
Barkle, Power, April 1943. Substation, G. B. Miller, A.I.E.E. Transactions, Vol. 67, 1948.
4. Uses of Capacitors, R. E. Marbury, Eleclric Journal, Vol. 33, 28. New Series Capacitor Protective Device, R. E. LIarbury and
July 1936, pp. 303-306. J. B. Owens, A.I.E.E. Transactions, Vol. 65, 1946, p. 142.
5. Capacitors-Design, Application, Performance, hl. C. Miller, 29. Self-Excitation of Induction Motors with Series Capacitors,
Electric Light and Power, Vol. 16, October 1938, pp. 46-50. C. F. Wagner, A.I.E.E. Transactions, Vol. 60, 1941 p. 1241.
6. Shunt Capacitors Reduce KVA Loads, C. &I. Lytle and S. H. 30. Steady-State and Transient Stability Analysis of Series Capaci-
Pollock, Electric Lighl and Power, Vol. 15, November 1937. tors in Long Transmission Lines, Butler, Paul, Schroeder,
pp. 52-54. A.I.E.E. Transactions, Vol. 62, 1943, p. 58.
7. Capacitors Defer $135,000 Investment in Synchronous Unit, 3;. Series Capacitors Approach Maturity, A. A. Johnson, West@-
J. F. Roberts, Electrical West, Vol. 83, October 1939, pp. 42-43. house ENGINEER, Vol. 8, July 1948, pp. 106-111.
8. Shunt Capacitor Application Problems, J. W. Butler, General 32. Application Considerations of Series Capacitors, A. A. Johnson,
Electric Review, Vol. 43, May 1940, pp. 206-212. Westinghouse ENGINEER, Vol. 8, September 1948, pp. 155-156, ;
CHAPTER 9

REGULATION AND LOSSES OF TRANSMISSION LINES


()riginal Author: Recisrd by:
G. D. McCann R. F. Lawrence

T
HIS chapter deals with p&lems relating to the Neglecting the capacitance a transmission line can be
performance of transmission lines under normal trcatcd as a simple, lumped, constant impedance,
operating conditions. The analytical expressions for Z = R +jX = zs = rs + jxs
currents and voltages and the equivalent circuits for trans- Where
In&ion lines are first developed for “short” lines and for
z = series impedance of one conductor in ohms per mile
“long” lines (where the effects of distributed line capaci-
T* = resistance of one conductor in ohms per mile
tance must be taken into account). A simplification is pre-
x* = inductive reactance of one conductor in ohms per
sented in the treatment of long lines that greatly clarifies
mile
their analysis and reduces the amount of work necessary
s = length of line in miles
for calculations. Problems relating to the regulation and
lossesof lines and their operation under conditions of fixed The corresponding “per phase” or equivalent single-phase
terminal voltages are then considered. The circle diagrams circuit is shown in Fig. 1 together with the vector diagram
are developed for short lines, long lines, the general equiv-
alent ?r circuit, and for the general circuit using ABCD Z=ts=(r+jx)s
constants. The circle diagrams are revised from the previ-
011seditions of the book to conform with the convention
for reactive power which is now accepted by the American
Institute of Electrical Engineers, so that lagging reactive
mER +-+c-$
power is positive and leading reactive power is negative.
When determining the relations between voltages and cur- I
I
I
I
I

rents on a three-phase system it is customary to treat them


on a (‘per phase” basis. Th e voltages are given from line EQUIVALENT TRANSMISSION
to neutral, the currents for one phase, the impedances for CIRCUIT TO NEUTRAL
one conductor, and the equations written for one phase. Fig. l-Equivalent circuit and vector diagram for short trans-
The three-phase system is thus reduced to an equivalent mission lines.
single-phase system. However, vector relationships be-
twcen voltages and currents developed on this basis are relating the line current and the line-to-neutral voltages at
applicable t,o line-to-line voltages and line currents if the the two ends of the line.
impedance drops are multiplied by d/3 for three-phase The analytical espression for this relationship is given
systems and by 2 for single-phase two-wire systems. by the equation:
Most equations developed will relat,e the terminal con- Es=ER+ZI (1)
ditions at the two ends of the line since they are of primary
importance. These terminals will be called the sending end Throughout this chapter, the following symbols are used:
and receiving end with reference to the direction of normal J$--is a vector quantity
flow of power, and the corresponding quantities designated ,!is the absolute magnitude of th,e quantity
by the subscripts 5’ and R. E-is the conjugate of the vector quantity

2. Long Transmission Lines


I. EQUIVALENT CIRCUITS FOR The relative importance of the charging current of the
TRANSMISSION LINES line for all types of problems varies directly with the volt-
1. Short Transmission Lines age of the line and inversely with the load current. To
appreciate this fully it is necessary to consider the analysis
For all types of problems it is usually safe to apply the of “long” lines.
short transmission line analysis to lines up to 30 miles in A “long” transmission line can be considered as an in-
length or all lines of voltages less than about 40 kv. The finite number of series impedances and shunt capacitances
importance of distributed capacitance and its charging connected as shown in Fig. 2. The current IR is unequal to
current varies not only with the characteristics of the line Is in both magnitude and phase position because some
hut also with the different types of problems. For this current is shunted through the capacitance between phase
reason no definite length can be stipulated as the dividing *These quantities can be obtained from the tables of conductor
Point between long and short lines. characteristicsof Chap. 3.
265
266 Regulation and Lossesof Transmission Lines Chapter g

in which
Z=zs and Zr=c.
s

01)
SENDING RECEIVING
END END
(12)
Fig. Z-Diagram representing long transmission lines.
The values of the hyperbolic functions can l)c nbt:liIlcd
and ncllt,rnl. The relationship between Es and En for a from tablcs2 or charts3 or from evaluation of their equiv-
“long” line is different from the case of the short line be- alent series expressions
cause of the progressive change in t,hc line current due to cash (s$)=cosh 6’=(if;+;+;+....) (13)
the shunt capacitance. If Es and En are considered as
pl-iasc-to-ncutr:ll volt~agcs and 1s and IIt arc the phase cur-
rcwts, IJie classical equatjions relating t,hc sending-end volt-
ages and currents to t,lic receiving-end quantities are:

Es = En cash (~sl/zz/) +lR 5 sinh (~6) (2)


tl- !4
IS =% sinh (sd/z2/) +ln cash (sV&) (3)
J i ,~1,,?.. ‘2’
,.,,, “,
The susccptancc, 1~,her&o?ore has been used most fre-
quently in these expressions. However, with the advent of
the new form of tables giving characteristics of conductors,
the shunt-capacitive reactance is obtained as a function of
the conductor size and equivalent spacing. The reciprocal
of y, which is Z’ is therefore a more convenient quantity to
use. For this reason the concept of shunt-capacitive re-
actance is used throughout this chapter. Eqs. (2) and (3)
then become :

-i-1,6? sinh s s (4)


(4)

Is=% sinh (s&)+1, co& (84;) (3,

where z is the series impedance of one conductor in ohms


per mile, z’ is the shunt impedance of the line in ohms per
mile, s is the distance in miles.
2 = -jd( 10) 6
x’* = capacitive reactance in megohms per mile.
Equations (4) and (5) can be written conveniently in
terms of the conventional ABCD constants.4 For the case
of a transmission line the circuit is symmetrical and D is
equal to A. (Refer to Chapter 10, Section 21 for definition
of ABCD constants.)
Es = AER+BIR (6)
IS = CER+DIR= CER+AIR (7)
ER=AEs-BIs (8)
IR= -CEsfDIs= -CEs+AIs (9) l/4 l/2 3/4 I
LINE LENGTH -WAVE LENGTHS
where 1
Fig. 3-Variation of the real and imaginary components of A, 1
A=cosh (s&)=cosh ,/I WV B, and C for a 795 000 circular mils ACSR, 25-foot equivalent
spacing, transmission line.
*This quantity can be obtained from the tables of conductor char- r =0.117 ohm per mile.
ucteristics in Chap. 3. It is given in megohms in tables as it is then x =0.7836 ohm per mile.
of the same order of magnitude as the inductive reactance. x’ =0.1859 megohm per mile.
Chapter 9 Regulation and Lossesof Transmission Lines 267

sinh (s&)=sinh 0=(0+~+~+~+. . . .) (14)

Expressed in terms of their equivalent serieaexpansions,


the ABC constants become
24
40 320Zf4
+.**
1 (15)

362 880Zt4+ * ’ ’ 1
(16)
Fig. 4-Equivalent k circuit for representing
sion lines.
long transmis-

f..*

The series are carried out far enough so that the ABC
1
(17) By equating like coefficients of the equivalent Eqs. (1s)
and (6)
Z,,=B (20)
constants can be determined to a high degree of ac-
(~t~r:~cy.However, for lines approaching one quarter wave l+$=A WI
\~@h, t,he series do not converge rapidly enough. In such eFI
:Lwse it is better to d&ermine the ABC constants for the Giving for the equivalent impedance Z&
Iinc: in two sections and combine them as described in
(:hnpter 10, Table 9. (22)
The ABC constants can be determined easily for any
Iwgth of line by an evaluation of the cash and sinh func-
Expressed in terms of the corresponding hyperbolic
I ions using the hyperbolic and trigonometric functions.
functions and their equivalent series the equations for the
The procedure is outlined briefly here.
impedances are
e=s $==a+jg
-\i-
nhcre o! and /3 are in radians. (23)
cash 0= cash a cos /3+j sinh CYsin p
sinh e=sinh 01cos p+j cash 01sin /3
where:

p - .$-a
sinh a=------
2 23 z4 (24)
+
Figure 3 shows the variation of the ABC constants as a 30 240Zt3 - 1 207 600Zt4+ ’ ’ ’
function of line length for the line of Fig. 18. The real and
imaginary parts of A, B, and C are shown for a complete 4. Equivalent T of a Transmission Line
wave length. Another equivalent circuit for a transmission line is
3. The Equivalent 7r of a Transmission Line shown in Fig. 5. The equations for the impedances of this
circuit are
There are several equivalent circuits that represent the
above transmission line equations and thus can be used --___- 1723
for the representation of transmission lines. One such 20 160Z’3
circuit is the equivalent 7r shown in Fig. 4. (25)
Referring to this figure the equations relating the
terminal conditions for this circuit are
z:=;=zt l-$+&-1;;2;z,3
(
127Z4 \ (26)
+
604 800.T4-. * ‘)

(‘9) Fig. 5-Equivalent T circuit for representing long transmis-


sion lines.
268 Regulation and Losses of Transmission Lines Chapter 9

5, Comparison of the Equivalent r vs. ABCD Con- 22


stants ~ = 0.0056-j0.003-1
242’2
The choice of the use of the equivalent x vs. ABCD con- This term is thus about 0.6 percent of one (the first term).
st.ants in calculating transmission-line constants is largely a For the third term in the expression for ZT.
matter of personal preference. However, each offers cer- 2”
tain advantages over the other. When the network calcu- ___ = 0.00 11-jO.OOOG7
lator is to be used, it is necessary to set up an actual circuit 1202”
in the form of the equivalent 7r. The equivalent r affords a which is about 0.1 percent of one (t,he first, t,erm).
better physical picture of transmission-line performance For all the rest of the const,unts the term is less than
and makes the comparison between long and short lines 0.1 percent.
and the effect of charging current easier to visualize. Since these terms vary with the fourt,h power of the
On the other hand, when a problem is to be solved length of the line, they decrease rapidly for lines less than
analytically, the use of ABCD constants has a definite ad- 300 miles in length and can be neglected. l+‘or instance for
vantage over the equivalent r because of the availability a 150-mile line the terms are one-sixteenth as large as for
of the jndcpendent check: AD-X= 1. This is pertic- a 300-mile line.
lllarly desirable when other circuits are to be combined Thus the above transmission line constants can be ex-
with the transmission line circuit. pressed sufficiently accurately by the following equations
The equivalent ir or ABCD constants can be used to rep- which were derived from Eqs. (151, (lG), (17), (23), (24),
resent any line, section of line, or combination of lines and (25), and (26) by neglecting all but the first two terms of
connected equipment. Either one represents accurately all each series expression.
conditions at the two terminals of the system. The equiv-
alent circuit or -4BCD constants being considered here per- A=(,-&)++$ (27)
tains only to a single line or line section. The general
equivalent circuit and general ABCD constants, if so
B=Z~,=lOOrS(l-$&)
desired, can be determined by the combination of the
equivalent circuits for the rest of the system as discussed in
Chapter 10. +j1002s l-&+& (2%
( )
6. Expressions for Transmission Line Constants by
First Two Terms of Their Series C=$[(l--$$)+j&jln’ (29)
When considering the accuracy with which transmission
line circuit constants need be determined, it should be z:,= -j?g(l-&,)fj&]lO’ (30)
realized that the resistance, inductance, and capacitance of
a line can rarely be known to within 3 or -1 percent and
probably never within one per cent. This is due to con- zT=50rs( 1 -g&)
ductor sag, its variation with different spans, and the varia-
tion that exists in conductor spacing together with the +j5oxs 1 - &+& (31)
effects of temperature @on conductor resistivity and sag. ( )
For this reason equations for the above circuit constants
that are accurate to within 0.5 percent should be satis- ZT’= -jf$(l+$&)-j&]lO” (32)
factory.
The effect of neglecting all but the first two terms of the In these equations:
series in the above expressions can best be shown by con- S = length of line in hundreds of miles.
sidering an actual line. For a 300-mile line with 250 000 x and r are in ohms per mile, and x1 in megohms per mile.
circular mil stranded copper and a 35-foot spacing the
third term in all of the above series expressions is larger 7. Simplified Method of Determining the Imped-
than normal. ances of the Equivalent T Circuit for Transmis-
For this line, from the conductor tables of Chap. 3 sion Lines
r=O.257 ohms per mile The following method greatly simplifies the determina-
tion of the impedances of the equivalent s circuit and still
z=~,+~,~=O.487+0.431=0.918 ohms per mile
enables them to be determined to within 0.5 percent for
x’=~:,‘+zd’=0.111+0.106=0.217 megohms per mile all practical power transmission lines.
2 = rsfjxs = (7’7.1fj275.4) ohms Equations (28) and (30) can be expressed in the follow-
Z’= -p-.-z
2’106
-j723.3 ohms ing form:
s z,, = 100rSK,+j100xSK, (33)
Z
-= 77.1 fj275.4
= -0.3SO7+jO.1066 Z’ea= -j2$(/f,+j&J104 (34)
Z’ - j723.3
$0.1335~jO.08117 where
(35)
For the third term in the series expression for A
Chapter 9 Regulatzbn and Losses of Transmission Lines 269

(3’7)

p .‘“t S-R t+--+ J I I I


Esamination of the above equations shons that for a
given line, the factors K,, K,, and k, differ from 1 by a
term that is proportional to the square of the lengt,h of the
line. However, a study of the characteristics of lines which
it is economical to build and that have been built in the
Ynitod States reveals that for a given length the variance
of these correction factors from a mean is very slight. In
:Ldtlit,ion, it is only the lines wit,h smaller conductor sizes
;tntl equivalent spacings for which the correction factors
vary appreciably.

TABLE l.-MINIMUM CONDUCTORSIZES AND SEPARATIONSFOR


WHICH THE MEAN VALUES OF THE CORRECTIONFACTORS
ARE APPLICABLE TO AN ACCURACYOF WITHIN ONE-
HALFOF ONEPERCENT"'
.., . ’ ’ ’ ’ ’ ’ ’ ’ ’ ’ ’
Jxngth of Line 0 40 00 120 160 200 240 260
in LIiles 50 7.5 150 200 300 LENGTH OF LINE IN MILES
G.lI.1). (ft.) 3 G G 10 14
Fig. 6-Correction factors for the equivalent T transmission
C!onrwr Cables 6 2 0 300 000 500 000 line impedances and ABC constants at 60 cycles.
;\.C.S.R. 1 1 000 500 000 i95 000 S =length of line in hundreds of miles.
An IIollow r = conductor resistance in ohms per mile.
Cu. Cnhle 00'2' 00 00 300 000 500 000 z = inductive reactance in ohms per mile.
Gen. Cnhle x’=capscitive reltctance in megohms per mile.
Twe T-TIT OOO(2) 000 000 300 000 500 000
(I) Conductor sizes are in cir. mils or AWG. be expressed to sufficient accuracy as parabolic equations
0) Smallest sizes made. of the type 1 -KS2. In Table 2 are tabulated the COP
rection factors expressed in this form. The curves con-
Table 1 gives minimum conductor sizes and spacings for structed from these equations conform closely to the curves
various lengths of line for which the use of mean correction of Fig. 6. Table 2 shows that K, can be considered as 1 up
fxtors will give sufficient accuracy. For lines up to 300 to 50 miles, K, as 1 up to 75 miles, and k, as 1 up to 100
miles in length with conductor sizes and spacings equal to miles. Since in practically all cases the individual sections
or greater than given by this table, the use of mean values of line to be considered are not over 100 miles long, the
for K,, Kx, and lc, gives an accuracy of within 0.5 percent. correction factors can be neglected entirely if an accuracy
The correction factor k, is never greater than about 0.005 of better than 1M percent is not desired. The largest
and can be neglected. Thus, the shunt impedance .Z& deviation from unity is in K, which at 100 miles is only
can bc considered as a pure capacitor. 1.4 percent.
In Fig. 6 are plotted the curves for K,, IL, and k, as a Example l-As an example of the use of this method
function of line length. The values on these curves con- in determining the equivalent r of a transmission line, con-
form to those of the most common type of line construc- sider a three-phase, 60-cycle, 230-mile line of 500 000
tion that is used for a given line length. Thus, in most circular mil stranded copper conductors at an equivalent
cases the use of these values will give an accuracy con- spacing of 22 feet.
siderably better than 0.5 percent. The factors can also From the Tables of Chap. 3

TABLE 2--EXPRESSIONSFOR THE CORRECTIONFACTORSFOR T = 0.130 ohms per mile


THE EQUIVALENT ?r IMPEDANCES x=0.818 ohms per mile
x’=O.1917 megohms per mile
Correction Values for Line Lengths up to
Factors 50 illi. / 75 Mi. 1 100 Mi. / 200 Mi. 1 300 Mi. From the curves of Fig. 6 for a 230 mile line
Iir
Ii, 1 1 K,=0.931
L K, = 0.964
1l- 1 I l-0.0035 s*
k,= 0.982
I;, 0
S is t.he length of the line expressed in hundreds of miles. From Eqs. (33) and (31) or Fig. 6
270 Regulation and Losses of Tmmmission Lines Chapter 9

Z,,=(0.130)(230)(0.931~+j(0.818)~230)~0.964) R=rt X’XS


= (27.5fjlSl.l) ohms
fi----J

Z:, = -jl635 ohms LAGGING WWER FACTOR LEADING POWER FACTOR


The equivalent circuit for this line is shown in Fig. 13.

8. Adaptation of Simplified Method of Determining


Equivalent B to Determining ABC Constants
The foregoing method can bc adapted with an acceptable
tlegree of accuracy to determining the ABC constants of a
transmission line. The $BC constants of the line should be
dctcrmined by a more accurate method if the line is to be
combined with other circuit elements. Eq. (2i) can be (a) FOR KNOWN RECEIVING END CONDITIONS
written as follows:

where
Since K, is the same form of correction factor as K, (Eq.
(35)), a new curve for the correction factor can be plotted
as shown in Fig. 6. The constant A is readily obtained
from the correction factor I(, and Eq. (39). The constant
B is equal to Z,, and is determined through the use of the (b) FOR KNOWN SENDING END CONDITIONS
correction factors K, and & of Fig. 6.
From Eqs. (16) and (17) it can be seen that Fig. 7-Vector diagrams for determining voltage regulation of
short lines.
c- B _ Bxlo- C--10)
ZZ’ xx’ --jrxJ to-line voltages are applied to the following voltngc equa-
where tions the impedance drop must be multiplied by d/s for
r=conductor resistance in ohms per mile. three-phase lines or by 2 for single-phase lines.
x=inductive reactance in ohms per mile. In the following equations, (41) through ((il), the sign of
x’ = capacitive reactance in megohms per mile. the power factor angle 4, depends upon whether the current
Example I(a)-Determine the ABC constants of the is lagging or leading. For a lugging power factor, 4 and sin 4
transmission line of example 1. are negative; for a leading power factor, 4 and sin 4 are
From the curves of Fig. 6, for a 230-mile line positive. The cos of 4 is positive for either lagging or leading
current.
R, = 0.897
EIR= &R = reference
From the curve for K, of Fig. 6 and from Eqs. (39) and Z=I cos q5~fjl sin 4~
(40) Z=R+jX=rs+jxs
O.130(1-0.897)
A =0.897 +j,,,,, Es= ER+IZ (41)
or
=0.89i+j0.0164 ES = (rr,+TR cos q5~- 1,X sin 4~) +j(FX cos +R
B = Z,, = 27.8fj181.4 ohms (from example 1) +I R sin $R) . (4%
1n magnitude

= -0.00000639+j0.001156

II. REGULATION AND LOSSES If the IR and 7X drops are not over 10 percent of ER,
ES can be determined for normal power-factors to within a
9. Analytical Solution for Voltage Regulation of half percent by neglecting its quadrature component.
Short Lines from Known Receiver Conditions Then
The commonest type of regulation problem is one in ES=ERfIR cos +*-TX sin +a (44)
which it is desired to determine the voltage drop for known The voltage regulation of a line is usually considered
receiving-end conditions. For the solution of this problem as the percent drop with reference to ER.
it is more convenient to make ER the reference vector as
shown in Fig. 7(a). Unless denoted by the subscript L all Percent Reg. = “‘(2 -ER)
voltages will be taken as line-to-neutral voltages. If line- R
Chapter 9 Regulation and Lossesof Transmission Lines 271

For exact calculations formula (43) can be used with and sending-end voltage, or sending-end power factor and
Eq. 45. receiver-end voltage, and it is desired to determine the
Using the approsimate formula (44) Eq. 45 can be unknown voltage for given load GUIrents. Such problems
written - can not readily be solved by analytical methods. For
instance, if it were desired to determine the receiver voltage
Percent Reg. = ly(r cos +a--l: sin 4~) (46) from known load power factor, sending end volt,age, and
R
current, it would be necessary to solve for ER in Eq. (43)
The load in kva delivered t,o the receiving end of a by squaring both sides of the equat,ion and obtaining a
three-phase lint is given by the equation quadratic equation for ER. This is somewhat cumber-
& ,l _ 3E,,I _ ~3E’J some. Trial and error methods assuming successive values
1000 1000 of one of the two unknown quantities, are often more con-
venient. Also, it is sometimes found easier to solve such
where E,. is the line voltage at the rccciving end.
problems by graphical means. The more important prob-
‘1’1~ rcgulntion expressed in terms of the load and the line-
lems of this type can he solved by use of the Regulation
[~lirie voltage (*an he written
and Loss Chart as shown in Sec. 28(d) of this chapter.
100 OOO(kva) (s) COS +R-Z
l’crcent Reg. = -----((T sin CbR)(@)
i3; 12. Taps Taken Off Circuit
‘I’llcse equations show that the amount of load that can Quite frequently the main transmission circuit is tapped
IK transmitted over a given line at a fixed regulation varies and power taken off at more than one point along the (sir-
inversely with its length. Using the regulation calculated cuit. For such problems it is necessary to solve each in-
from these equations to determine the receivefend voltage dividual section in succession in the same manner as dis-
\vill give this quantity to x percent if neither the resist- cussed above, starting from a point at which sufficient
ancc nor reactive drops exceed more than 10 percent of the terminal conditions are known.
tcrminnl voltage. The percentage variance of the regula-
tion from its own correct value, however, may be great, 13. Resistance Losses of Short Transmission Lines
tlcpcnding upon its actual magnitude and for this reason The total Rf? loss of a t,hree-phase line is three times the
such equations are not accurate for determining load limits product of the total resistance of one conductor and the
for fised rcgulntions. square of its current.
Example 2-The use of these equations can be illus- Loss = 3RI? in watts. (53)
trated by calculating the regulation on a three-phase line In percent of the delivered km. load
five miles long having 300 000 circular mil stranded copper 173rsI
conductors at an equivalent spacing of four feet and carry- Percent Loss = - (54)
ing a load of 10 000 kva at 0.8 power-factor lag and a EL Cm 6R
n>c*eiverline voltage of 22 000 volts. It is sometimes desired to determine the amount of
~=0.215 ohms per mi and x=0.644 ohms per mi. power that can be delivered without esceeding a given
Applying Eq. (48) percent loss. This is given by
Pcrccnt Reg. = KW= .i?;: cof? 4R(OjgLoss)
(35)
““““~;~;~o;~)(i)[(0.215)(0.8)-(0.644)(-0.6)] 100 ooors
Reg. = 5.87, This equation shows that the amount of power that can
be transmitted for a given percent loss varies inversely
10. Voltage Regulation of Short Lines from Known with the length of the line and directly with the loss.
Sending-End Conditions
To calculate the receiving-end voltage from known 14. Regulation of Long Lines from Known Receiver
s4ing-end conditions it is more convenient to use Es as Conditions
Ihe reference vector as shown in Fig. 7(b). For this case The effect of charging current on the regulation of
Es =Es = reference transmission lines can be determined from the equivalent
En= Es-IZ (49) r circuit. In Fig. 8(a) are shown the vector diagrams for
the case of known load conditions. The voltage drop in
ljlR=(~s-7Rcos~s+~Xsin~s) -j(TXcos$s+fRsin&) the series impedance Z,, is produced by the load current
(50)
IR plus the charging current 2 flowing through the shunt
(51) impedance at the receiver endeif the line. For a given line
xeglecting the quadrature component of &: this latter current is dependent only upon the receiver
lYR=i?i,-7R cos &+rX sin +S (52) voltage EB.
There are two methods of taking this charging current
11. Problems Containing Mixed Terminal Condi- into account. One of these is to determine first the net
tions
current that flows through Z, together
Sometimes problems are encountered in which mixed
terminal conditions are given, such as load power factor with its angle &. Using the equivalent
272 Regulation and Losses of Transmission Lines Chapter Q

15. Regulation of Long Lines from Known Sending-


End Conditions
For this case the equivalent current flowing through
Z& can be determined as the difference between 1~ and
Z& the current in the shunt reactance at the sending end
of the equivalent circuit. The vector diagram and equa-
,.AGG,NG POWER FACTOR LEADING POWER FACTOR tions for this case are shown in Fig. 8 (b).
16. Effect of Line Capacitance on Regulation Ex-
pressed in Terms of a Correction Factor
As an alternative method the voltage relations can be
determined in a form equivalent to adding a correction
factor to the terminal voltage instead of to the current.
This method has an advantage in that an average value
can be taken for this correction factor which is a function
only of the length of the line.
Referring to the vector diagram of Fig. 8(a) for known
receiving-end conditions and lagging power-factor, it -is
seen that the vector equation for the sending-end voltage
Es-h + ‘.q LJ Es can be written in the following form in terms of the
(al FOR KNOW” RECElVlNG END CONDITIONS
load current IR and receiving-end voltage ER if the cur-
rent Ia’ is expressed in terms of ER:

+j +$%R+XwP~ cos C$R+ReqI~ sin 4~ (56)


(
When the ;;adrature component of Es is neglected, its
magnitude can be expressed as

From the same considerations that enabled average


values to be taken for the correction factors of the equiv-
alent x impedance discussed in Sec. 7 an average value

can be assumed for 3 in Eq. (57).


lb) FOR KNOWN SENDING END CONDITIONS w-l
Fig. S-Vector diagrams for determining voltage regulation of X-2
z’=o.0201s2 (58)
long lines. 89
where S is the length of the line in hundreds of miles. An
series impedance Z,, and this current instead of the load approximate expression can thus be obtained for the regu-
current all of the analytical expressions developed for lation of long lines similar to that of Eq. (46).
short lines are applicable. The equivalent terminal con- -
ditions to use are shown in Fig. 8 (a). _ App. 70 Reg. = F(R.., co&a-X,, sin&) - 2.01~9~(59)
Example ~-AS an example of the use of this method R

consider the line of example 1, operating at a line voltage Similar analysis can be applied to problems involving
at the receiver end of 110 kv delivering a load current Ia known sending end conditions. A comparison of Eqs.
of 50 amperes at 0.9 power-factor lagging. (59) and (46) shows that when 2, is used for long lines,
En= (1lO,OOO+jO)/~3=63,5OO+jO the equations are of the same form with the exception of
the correction factor (- 2.01S2). For lines up to 100 miles
IR = 50e-j25~8’= 5O[cos ( - 25.8”) +j sin( - 25.8’)]
in length short line formulas can usually be applied to a
=45-j21.8 amps good degree of accuracy by merely adding this term to the
z, -& llo o”o+.io result. This, of course, neglects the correction factors %
R Z:, d(-j1635) = +j3”’ amps and K, for Z,,.
~,=~a~Z~=45-j21.8+j38.8=45+j17=48.1~”0.’~
17. Determination of Voltage at Intermediate
Z,=27.8+j181.4=183.5~~*~~~*~ Points on a Line
Es = 63 500+ (48.1%“.70”) (183.5~“~~~~“)
The voltage at intermediate points on a line may be
=61~7OO+j8640 calculated from known conditions at either terminal by
*Sirw of negative angle is (-), of positive angle is (+). simply setting up the equivalent circuit for the line be
Chapter 9 Regulation and Losses of Transmission Lines 273

tween the terminal and the intermediate point. For the


line thus set up any of the methods given above may be
used.
18. Resistance Losses of Long Lines
The effect of charging current on line losses can be
treated as in Sec. 14 for regulation. Referring to Fig. 8 REFERENCE
tlrc loss can be considered to be due to the current
Fig. 9-Diagram for determining the vector equation for
I,.,,=IR+IR’=b-zS’ flowing through the equivalent power.
resistance (f&J.
Thus in terms of the load current
For leading or capacitive power factor, 4 is negative and
Loss = 3&,(lnfln’)2 watts (60) the imaginary component will be negative. h complete

1 watts (61) discussion of the direction of the flow of reactive power is


given in Chap. 10, Sec. 2.
20. Current and Power Equations and Circle Dia-
III. CIRCLE AND LOSS DIAGRAMS grams for Short Lines
Equations for line currents, power, and resista&&%es Using the above notation the per phase power at either
can be expressed as funct#ions of the terminal voltages and end of a line is given by the product of the line-to-neutral
system constants. Such equations and graphical repre- voltage and the conjugate of the current at the particular
scntations of them are found convenient not only for the end in question. If Is is chosen as positive for current
more common types of performance problems but also in flowing into the line, positive sending-end power indicates
corm&ion with system stability. The graphic form of power delivered to the line; and if In is taken as positive
t,he power and current equations are very similar and are for current flowing out of the line, positive receiving-end
known as “circle diagrams. ” Of these the power circle power indicates power flowing out of the line.
tlingram is the most important. In the past this diagram Referring to Fig. 1:
has been primarily limited in its use to transmission sys- Is=IR=I
terns. However, it is thought that if its simplicity and the
clarity with which it depicts system performance are Ps+jQs=Esf
Mter understood, it will be applied more frequently to PR+.i&~ = Ed
both transmission and distribution problems. The current can be expressed in terms of the terminal
voltage as follows:
19. Vector Equations for Power
I=-%-E~ ulso p=Es-ER
In previous editions of this book, lagging reactive power (63)
NM considered as negative and leading reactive power
Z 2
positive. This conformed to the standard adopted by the Thus
American Institute of Electrical Engineers at that time. ES-@S-ES&
Ps+jQs= g
The convention has now been adopted as standard by the
Institute that lagging reactive power be considered as - ERER+ER~s
positive and leading reactive power negative. Using this PR+&?R=
2
notation the vector expression for power can be written as
the product of the voltage and the conjugate of the If ER be taken as
-- the reference,_then Es=Es@ and
current. EJJs=Ei; EJZR=ESEREis; ERi?R= Ei; and E~i?s =E$S
P+jQ= Ef (6 e-j*. The expressions for sending- and receiving-end power
become --
This can be shown with reference to Fig. 9.
I?: EsEReie
E = ,!?cos e,+jE sin 8, P,+jQs=2--7 034)
I=I COSOifj? sin Bi --
ESERc-je
f=f COSOi-j1 sin 0i P,+jQ,= -F+ z (65)
EP=E (cos e,+j sin e,)? (cos ei-j sin 8i)
The sending and receiving end real and reactive power is
=.ET [(cos 8, cos Bi+sin ee sin eJ+j(sin 8, cos Bi the sum of two vector quantities. Furthermore, if the
--OS 8. sin ei)] voltages Es and ER are held constant, there is only one re-
since, cos (e,--ei) = cos 8, cos Bifsin 8, sin 8i maining variable, 0. The interpretation of Eqs. (64) and
and sin (e,-ei) =sin ee cos ei-cos 8, sin Bi (65) in the form of power circle diagrams is an important
concept. Its simplicity is self evident by referring to Eq.
El=Ei: cos (t?,-di)+jEI sin (0,-&) (64) and Fig. 10. F;.
,. *
Let 4 be 8,--Bi; then for lagging or inductive power
factors 4 is positive and The first term %, is plotted as shown on Fig. 10 and is
P+jQ= El=,!?1 cos ++$!?I sin 4. the vector to the center of the sending end circle diagram.
274 Regulation and Losses of Transmission Lines Chapter 9

the coordinates of the diagram are per-phase real volt-


amperes and per-phase renct,ive volt-amperes. When ex-
pressed in kilovolts, t,he coordinates become thousands of
kilowatts and thousands of reactive kilovolt-amperes,
Total three-phase power is three times the per-phase
power. All of the espressions -- for power written contain

-‘\ CENTER OF
products of Ei, Ei, or EsER. When given in terms of
line-to-line voltages, they are all three times as great as
when line-to-neutral voltages are used and thus the
equations then represent total three-phase power.
Referring to Fig. 10 for the operating condition indi-
cated by the given angle 0 the point A of the power circle
diagram shows the value of Ps and Qs being delivered to
the line at the sending end and the point B the value
LAGGING of PR and Qn drawn from the line at the receiver end. The
VOLT AMPERES difference between Ps and PR is the Rp loss of the line
t itself for this operating condition.
\ REAL The value of Q at each end is the reactive power which
POWER must be supplied to the line in the case of the sending end
\ or drawn from the line in the case of the receiving end in
order to maintain the chosen terminal voltages. At the
receiving end the reactive power drawn by the load itself
RECEIVING END - at the particular load power factor may not be equal to
that required to maintain the desired voltage. If a syn-
chronous condenser is used at the receiving end, the dif-
ference must be supplied by the condenser to maintain the
voltage.
It will be noted that for a given network and given
voltages at both ends there is a definite limit to the amount
of power which may be transmitted. If the angle 0 is
increased beyond this point, the amount of power trans-
Fig. lo--Power circle diagram for short lines. mitted is reduced. The critical value of 0 for this condition
-- was shown by Eq. 66 to be 0 = y. The only way the power
EsEnG limit may be increased for a given network is by increasing
The second term - -, + which is the radius of the circle
the voltage at either or both ends. Increasing the voltage
is added to this first term so that the resultant is the send- at one end increases the radius of both circles in direct
ing end real and reactive power. A complete sending end proportion and moves the center at that end only away
circle diagram is obtained by first determining the-- center from the origin, along a line connecting the original center
jp EsERG to the origin, proportional to the square of the voltage at
of the circle from -&, and second, the radius - ------) that end. Where the network is subject to change, changes
z z in network constants will also change the power limit.
letting 8 = 0. Referring to Fig. 10 and Eq. (GG), it is evident that a
The receiving-end circle diagram is obtained in the same decrease in the magnitude of 2 will result in an increase in
manner. the power which may be transmitted. Thus any change
Equations (64) and (65) can be reduced in general terms which decreases the series impedance such as the addition
to Cartesian coordinate form in which the real and reactive of parallel circuits will increase the power limit.
parts are separated. However, it is simpler to insert the Since the conjugate of the phase current, in amperes, is
proper numerical values in the vector and conjugate form the per-phase power in volt-amperes at either end divided
and solve by polar and Cartesian coordinates, from which by the phase voltage at the same end, either the sending-
the circle diagrams can then be plotted. end or receiving-end power circles, when placed in the
If Eq. (65) is reduced to Cartesian-coordinate form it proper quadrants, can be used to represent the locus of the
can be shown that the maximum power that can be re- current with a proper change in scale of the coordinates.
ceived over the line is obtained when 0 is equal to Referring to the sending end circle diagram of Fig. 10,
y = tan-’ I, the angle of the line impedance. The expres- Ps+jQs=Ef and for the point A, Q, is positive lagging
r reactive power. Therefore the imaginary component of the
sion for the maximum receiv+g power -- is conjugate of the current is positive; the imaginary com-
2
PR max= -%R+Ea. ponent of the current is negative. If the power circle dia-
w9
22 z grams are rotated about the real power axis so that the
It can also be seen from Fig. 10 that PR is maximum when ce+rIof the sending-end circle is in the fourth quadrant
O=y. ES
will then be the vector to center), and the center of
When the line-to-neutral voltages are expressed in volts, (- Z
Chapter 9 Regulation and Losses of Transmission Lines 273

the receiving end circle is in the second quadrant, then the gether with the quantities for laying out the diagram.
po~\cr circle diagrams properly represent the current circle Since the coordinate of t,he center of the po\ver circlrs
tli:Lgrams if the appropriate change in scale of the coor- depends only on En which is fised, a11the circles bar-c t,he
,linates is made. Lagging rcact,ivc current is negative and same center but different radii corresponding to the diffor-
Icacling reactive current is positive. ent values of sending end voltages.
LEthe sending-end circle is used the current is referred Examination of this figure shows, for example, that the
to t,hc sending end voltage as the reference vector and the maximum load at 0.9 power factor lag lvhich can be carried
~~,~ortlinatcsshordd be divided by the sending end voltage. by the line at 5 percent regulation without react,ive power
1;0r instnncc, if the sending-end power diagram were con- correction is that indicated by point A or about 2600 k\v.
~1r\rctctl rising line-to-lint voltngcs in kilovolts resulting in If it is desired to transmit a load of 5000 km indicated by
po\vcr coordinates given in thousands of total three-phase point R, the regulation ~oultl be about 11 percent, \vithout
Iti[ovnlt-ampores, the power coortlinates should he divided rkva correction. To reduce the regulation for this load to
/)v .J3 times the line-to-line sending end voltage in kilo- 5 percent would require that the receiver and load concli-
volt,s giving current coordinates in thousands of amperes. tions be that indicated by the point C, and it, is evident
LEthe receiving end circle is used, the current is referred to that about 2100 lagging reactive kilovolt-amperes must be
the rccciving end voltage as reference. For the current supplied to the receiver end of the line to attain this contli-
~:i~~:lcdiagrams the angle 0 still, of course, refers to the tlon by having capacitors or a synchronous condenser
:tnglc between the two terminal voltages. supply that amount of lagging reactive kilovolt-amperes.
For a study of the performance of a system it is some-
f irncs form1 convenient to plot on the power circle diagram 21. Current and Power Equations and Circle Dia-
:1family of circles corresponding to various operating volt- grams for Long Lines
:tgcs. The most common case is one in which the line is to Representing long lines by their equivalent 7r circuit as
operate at a fixed receiver voltage and it is desired to de- shown in Fig. 6 results in modifying the form of the simple
tcrminc the line performance for various sending-end volt- short line equivalent circuit by the addition of the shunt
ages. For such a case the receiver diagram is usually all capacitive resctances at each end
that is needed. z& = z;, e-joo”= -jar&
Example 4-An example of this type of problem is
sho~vn in Fig. 11. There the line constants are given to- Thus the equations for the terminal currents have an
additional term as shown in Fig. 8.
7

ANGLE FOR
- IO
LAGGING LOAD
_ POWER FACTOR
The sending- and receiving-end power is determined in
the same manner as for the short line.
A
REAL POWER Ps+.iQs= EsIs

Rewriting Eq. (69) in a slightly different form

/,o’ t-J 1 t-i \RECEIVER Similarly for receiving end power:


>
F ‘Cl RCLES
- -40
2
2
A comparison of Eq. (70) xvith (64), and (71) with (65)
shows them to be of the same form consisting of a fised
RECEIVING vector with a second vector constant in magnitude but
CIRCLES variable in phase, added to it. The power circle diagram
Fig. 1I-Family of receiver power circles for a 15-mile line with
can be plotted as shown in Fig. 12. The circle diagram is
No. 0000-19 strand-copper conductors and 4-foot equivalent most easily obtained by the numerical and vector substitu-
spacing. tion for the voltages and impedances. The center and the
Receiver voltztgc ER = 22-h line-to-line. radius of the circle can then be calculated by reduction
T=0.303 ohm per mile. using a combination of polar and Cartesian coordinates.
z = 0.665 ohm per mile. Example 5 illustrates the method and shows the power
Z = zs = 10.94 ohms. circle diagrams which are obtained in Fig. 13.
276 Regulation and Losses of Transmission Lines Chapter 9

LAGGING

END CIRCLE

Fig. la-Power circle diagram for long lines.

In Eqs. (70) and (71) the terms

are not a function of the angle 0 and therefore add directly


to the “short line” fixed vector so that the effect is to shift Fig. 13-Equivalent circuit and power circle diagram for a 230-
the center of the power circles in the direction of volt- mile line with 500 000 circular mil. stranded copper conductors
amperes only. The presence of the shunt reactances and an equivalent spacing of 22 feet.
decreases the amount of positive reactive volt-amperes put Operating voltages; EY = 230-kv, El, =200-kv, line-to-line.
For this line T =0.130 ohms per mile.
into the sending end of the line for a given amount of real
z =0.818 ohms per mile.
power and increases the positive volt-amperes delivered at
z’=O.1917 megohms per mile.
the receiving end. This decreases the amount of leading From curves of Fig. 6 for 230 miles
reactive volt-amperes which would have to be absorbed by K, =0.931
synchronous condensers or capacitors for a given load K,=O.964
condition. It does not affect the real power conditions for k,=0.982
a given operating angle or the load limit of the line. These Z,, = (27.8+j181.4) ohms; Z’,, = -j1635 ohms.
factors are determined entirely by the series impedance of
the line. Example S-Fig. 13 shows the power circle diagram :
Referring to Fig. 12, if the radius of the receiving-end constructed for an actual line.
circle for 0=0 were plotted with the origin as the center, The power circle diagrams are obtained from Eqs. (70) i
the vector would be at an angle y with the real power axis. and (71). If line-to-neutral voltages in kv are used, the ‘,
The angle indicated on Fig. 12 is therefore equal to y, results must be multiplied by three to obtain real and re- :\
the angle of the equivalent series impedance. The max- active power in mw and mvar. If the line-to-line voltages
imum real power that can be delivered over the line occurs in kv are used, the results are three-phase power in mw
when 6 = y. and mvar.
The current circle diagrams for the sending- and re-
ceiving-end currents can be obtained as discussed in Sec. Vector to center = z+$
20. The sending-end current diagram is obtained from the ea
sending-end power circle and is referred to the sending= (230)’ (230)*
end voltage vector as reference. The receiving-end current, =27.8-jl81.4++jl635
diagram is obtained from the receiving-end power circle and c (230)~ (230)*
is referred to the receiving-end voltage, 183.4e-‘8’.“8”+1635e’D~
Chapter 9 Regulation and Losses of Transmission Lines 377

= 2g8C~81.w+32,4 e-noo CENTER OF


w A SENDING END
=43.6+j281-$2.4 = 43.6fj2.51.6 \ CIRCLE DIAGRAM
--
EsERG
Radius of the sending end circle = - ~ for O=O.
2,”
=- 230x200 = - 251 pJ8” = - 38.0 -j248
27.8-j181.4
ps+jQs (for e=O) =43.G+j251.6--3&O-j248=5.6+j3.6
Similarly for the receiving circle:
- -
Vector to center= -‘F-F
‘w
- (200)2 (200)zeq
--= -33.0-j190.5
= 27.8-j181.4 +jlG35
--
Es&
for 0 = 0, Radius = -z--=38.O+j248
ze,
and PR+jQa= -33.0-j190.5+38.0+j248=5.0+j57.5
Figure 13 shows the power circle diagrams plotted-from
the calculated results given above. Suppose it is desired to
deliver a load of 100 mw at 0.9 power factor lagging;
i.e., P+jQ= lOOfj48. From the curves of Fig. 13, for a POSITIVE
delivered power of 100 mw the angle 0 is 23.5”. The fol- REAL POWER
lowing values from the circle diagrams are Ps+jQs = 108
+jll and PR+jQR = lOO+j20. These values are indicated Fig. 15-Power circle diagram for the general equivalent ?r
on the diagram of Fig. 14. The arrow indicates the direc- circuit.

SENDING END RECEIVING END ceiving-end power can be written directly from equations
Es=230 KV Er =200 KV (70) and (71).
(72)

and PR+jQR= ( -~-!%)+“s~~i” (‘73)


SY NCHiONOUS
CONDENSER
The construction of the power circle diagrams is the
Fig. 14-Recorded values of power flow as obtained from
” Fig. 13 and Example 5.
same as for the long lines as shown in Fig. 12. In the case
of the general equivalent r, 2s’ replaces Z,,’ at the sending
lion of positive real power flow. Inductive lagging re- end and Zs’ replaces Z,,’ at the receiving end. The effect
active power in the same direction is positive and is the of resistance and reactance in the shunt branch at the
value in parenthesis. These designations and nomencla- sending or the receiving end can be visualized better if the
ture follow present-day network calculator practice. impedance is expressed in Cartesian coordinate form.
At the receiving end there is a deficit of lagging reactive Referring to Eq. (72), the second quantity in the first term
power. A synchronous condenser operating overexcited becomes
would be required to supply 28 mvar. If the condenser is
considered as a load the direction of the arrow can be
reversed with a minus sign in front of the value for the
reactive power. The synchronous condenser is then taking This quantity is added to the “short line” vector to center,
negative, or leading reactive power. -2
ES
22. Current and Power Equations and Circle Dia- ti,,’
grams for the General Equivalent T Circuit
This point as applied to the sending end circle diagram
The circle diagrams are applicable to the study of the is illustrated in Fig. 15. The complete vector to center is
performance of an overall system. Such a system can be E E2 as the sum of the two individual vector
represented by an equivalent R circuit of the form shown shown as ,+G,
in Fig. 15. For such a case the shunt impedances usually ze, ZQ
are not equal and have resistance components introduced quantities, and as the sum of the vector F and the Car-
by the presence of other equipment containing resistance. 6,
If the shunt impedances take the complet,ely general EiRs’ E;x;
tesian coordinates ~ and j--=----.
form of Zs’ and Zs’, the equations for sending- and re- 37;” .W
278 Regulation and Losses of Transmission Lines Chapter 9

Referring to Fig. 15 and Eq. (74) the effect of resistance As shown by Fig. 16 this is equivalent to the formula for
is to shift the center of t,he circle in the direction of in- the loss on the-transmission line alone except for the terms
crcssecl positive real power. A positive reactance shifts the Q
-=--lZk and SBA which represent the losses in the
ccntcr in the direction of increased positive reactive power; GY GlY
a negative reactance shifts the center in the direction of resistance components of t,he shunt impedances .Z& and
decreased positive reactive power. Z&.
In the case of the receiving-end circle diagram, the effect As was the case for the previous power equations, if
of resistance is to shift the center of the circle in the line-to-neutral voltages are used, the loss is on a per
direction of increased negative real power. A positive phase basis; and if line-to-line voltages arc used the total
reactnncc shifts the center in the direction of increased three-phase loss is represented.
negative reactive power; a negative reactance shifts the An equation for the load which can be delivered at a
center in the direction of decreased negative reactive given percent line loss on lines regulated by synchronous
power. capacity is important in determining their performance.
The current circle diagrams for this case can be dc- Upon the assumption of equal sending- and receiving-end
&mined as discussed in Sets. 20 and 21. voltages a very simple approximate equation can be de-
rived which gives an accuracy of a fraction of a percent over
23. Loss Diagram the practical operating range of loss and regulation. When
Although the resistance loss can be taken from the power
circle diagram, it can be obtained more accurately and .QJ&
loss is expressed as a percentage of PRI this equation is:

conveniently from the Loss Diagram.


r doss= Ps - PR
PR=
y. TJoss
(loo+% Loss) a
A corresponding equation for QR is
[ 1 (77)

For the case where the transmission line alone is being


considered 08)
--
LOSS=$R-'%(I2 cos 19-x sin IjJ) PR in Eq. (77) is, of course, independent of the load
- power factor and from Eq. (78) the required amount of
synchronous capacity to maintain equal sending- and
-/-EFfR-E+(R cos 0+X sin 0) receiving-end voltages for the delivered load PR can be
- -- obtained by subtracting the reactive kva of the load
from &a.
24. Current and Power Relations in Terms of the
The graphical representation of this equation is given in ABCD Constants
Fig. 16. In many cases it is desirable to use ABCD* constants
because of the desirability of the check AD-BP= 1. This
is particularly true where there are several combinations of
circuits including transmission lines, series impedances and
shunt impedances. Expressions for sending and receiving
end power can be obtained readily and the circle diagrams
can be drawn.
Es=AER+BIR (79)
Is=CER+DIR (80)
ER=DE,-BIs (81)
IR= -CEs+AIs (821
Solution of the above equations for IS and IR gives:

Fig, 16-The transmission line loss diagram (when solving for (84) !,
general equivalent r loss, substitute R,, for R and zeg for 2).

For the general equivalent r circuit, the equation for


Ps+jQs = Esfs
loss is =E 2 fj-ES&
s s, __
B B
--
,E& -EsEd (85)
s ^
B B
(76)
*For definition of ABCD constants see Chap. 10 Sec. 21.
Chapter 9 Regulation and Losses of Transmission Lines 279

Further discussion of the use of ABCD constants and


power angle diagrams is given in Chapter 10, SW. 2 I.

-- IV. TYPICAL TRANSMISSION


= e~2 dA+EnESt-ie
_____ LINE CHARACTERISTICS
R- (86)
B l3
In any detailed analysis of power flow, voltage regulation,
\\hc!re and losses involving a transmission line circuit, each line
A=Al+j.4*=xEj"; LA,-jA,=Xe-j should be considered individually with regard to its
B=B,+jE&=R@ fi = Bl - jB, = Be-i0 specific characteristics. However, for rough approsimn-
tions there are certain rules of thumb that apply to an
D=DlfjD2=D~i6 fi = D, - jD, = DE-i6 “average” line and that can be used for orientation
The sending- and receiving-end power can be obtained reasons.
A study was made of recently constructed transmission
readily from solution of Eqs. (85) and (SG) by numerical
lines in the United States in the voltage range from 69 to
sllbstitution using polar and Cartesian coordinates. Eqs.
230-E&d Table 3 shows the results. This table is a good
(35) and (86) take the familiar form (see Sec. 20) of a fixed
representative cross section of existing lines and gives im-
vector plus a vector of constant magnitude but variable in
portant characteristics of typical lines. The conductor
phase position. The circle diagram construction is shown
sizes, spacings, and type of tower construction represent
iti Fig. 17. The maximum real power that can be de-
the most common usage. For the middle value of spacing,
the characteristics of the aluminum conductor and its
REACTIVE copper equivalent are given to illustrate the difference
POWER between types of conductors. In previous years, copper
conductors were used more frequently although the present
trend seems to be toward the use of ACSR conductors.
The spacings given were modified slightly in some in-
stances so as to follow a smooth curve of spacing vs.
voltage for the different types of constructZion. Regarding
the type of construction, it appears that the particular
ENDlNG END ClRCL
locale dictates the material used. As a matter of fact, in
certain sections of the world reinforced concrete poles are
used because of the unavailability and high cost of either
steel or wood.
LAGGING The GO-cycle series reactance in ohms per mile is given
VOLT AMPERES
REAL for each line in the table. The average of these values is
POWER 0.7941 ohm per mile, which indicates that the rule of
approximately 0.8 ohm per mile for a transmission line is
applicable. Frequently, it is desired to know the per-
cent reactance per mile of a line and for convenience this
value is also given. The percent reactance varies directly
with the kva base so that for some base other than 100
mva, the percent reactance can also be determined con-
- ) veniently.
As previously mentioned, the use of susceptance is less
at present because of the manner in which tables of con-
ductor characteristics are given. The shunt-capacitive
reactance in megohms per mile is therefore included in this
table. The susceptnnce can be determined by taking the
reciprocal of the shunt-capacitive reactance. The suscept-
Fig. 17-Power circle diagram in terms of ABCD constants. ante is in micromhos per mile. Shunt-capacitive react-
ance varies inversely with the distance in miles.
The average value of the shunt capacitive reactances in
livered occurs when e=p, which is the angle of the con- Table 3 is 0.1878 megohm per mile. A good rule is that 0.2
stant B. The angle /3 is indicated on Fig. 17. megohm per mile may be used for the shunt-capacitive
A breakdown of Eqs. (85) and (86) into their Cartesian reactance. It is significant to note that regardless of the
coordinate form gives the equation for loss in the form voltage, conductor size, or spacing of a line, the series
Loss=Ps-PR= reactance and shunt-capacitive reactance are respectively,
-- approximately 0.8 ohm and 0.2 megohm per mile.
& The charging kva per mile of line is a convenient value
~(BD,+B*D,)+E~~B,A,+B?A~)-2E”E~~ co”
for reference and is given in column 9 of the table. This
(87) value varies with the voltage of the line. Some convenient
Regulation and Losses of Transmission Lines Chapter 9

TABLE 3. TYPICAL TRANSMISSION


-
LINE CHARACTERISTICS AT 60 CYCLES
Reactance Per Phase Shunt,- Surge-
Conductor R csist- Per ;\lile Capacitive Three Surge Impedance
Circuit Size ante at Reactance Phase mped. Loading
\‘oltage Thousands Tower Equiv. WC Ohms 7. on 100 >regohms ‘hargin ante (SIL) in
Ii-4 of Cir. .\lils Construc- Spacing Per Phase Mva, Three Per Phase Cva PC Ohms ‘three Phase
L-L or AWG tion* Feet Per Mile Ohms Phase Base Per 1Iile Arile L-S Ii\\,

li!) 2/o cu SC-w** 8 0.481 O.i843 1.64 0.1822 26.1 3i8 12 600
ti9 336.4 ACSR DC-ST 11 0.306 0.7420 1.55 0.1750 2i.2 360 13 200
G!) 4/o cu SC-W 14 0.303 0.8112 1.70 0.1902 25.0 393 12 100
69 336.4 ACSR SC-W 14 0.306 0.7712 1.61 0.1822 26.1 37.5 12 700
G!) 336.4 ACSR SC-ST 19 0.306 0.8083 1.69 0.1913 24.9 393 12 100

1 I*5 336.4 ACSR DC-ST 13 0.306 0.7622 OX6 0.1800 i4.7 370 35 700
1 I.5 4/o Cl1 SC-W 17 0.303 0.8348 0.631 0.1960 Gi.5 404 32 700
115 336.4 ACSR SC-W 17 0.306 0.7948 0.601 0.1880 i0.4 386 34 200
Il.5 336.4 ACSR SC-ST 22 0.306 0.8261 0.624 0.1956 67.6 402 32 800

138 397.5 ACSR DC-ST 15 0.259 0.7636 0.401 0.1809 105. 371 51 200
138 250 cu SC-W 18 0.257 0.8317 0.436 0.19.52 9i.G 404 4i 100
135 397.5 ACSR SC-W 18 0.259 O.i857 0.412 0.1864 102. 382 49 800
138 397.5 .4CSR SC-ST 24 0.259 0.8206 0.430 0.1949 9i.i 399 47600

161 397.5 -4CSR DC-ST 17 0.259 0.7788 0.300 0.1847 140. 379 68 400
161 250 Cu SC-W 19 0.257 0.8383 0.323 0.196s 132. 406 63 800
161 397.5 ACSR SC-W 19 0.259 O.i923 0.305 0.1880 138. 386 67200
161 397.5 ACSR SC-ST 25 0.259 0.8256 0.318 0.1961 132. 402 64 400

230 i95 ACSR DC-ST 22 0.1288 0.7681 0.145 0.1821 291. 374 141000
230 500 HH-Cu SC-W 25 0.1260 0.7436 0.140 0.1800 294. 365 145 000
230 795 ACSR SC-W 25 0.1288 0.7536 0.148 0.1859 285. 381 139 000
230 795 ACSR SC-ST 31 0.1288 0.8097 0.153 0.1923 27s. 394 134 000
Avg. 0.7941 Avg. 0.1878 .4vg. 386
*DC-ST-double circuit-steel tower
SC-W -single circuit -wood
SC-ST --sin& circuit -steel tower
**Two-crossarm construction forming triangular configuration.
All other SC-W are H frame construction.

rules are given for estimating charging kva in the following resistance; i.e., Es=ER+TR. Surge-impedance loading in
discussion. itself is not a measure of maximum power that can be
The surge impedance of a transmission line is numeri- delivered over a line. Maximum delivered power must take
r, into consideration the length of line involved, the impe-
tally equal to C’ It is a function of the line inductance
tl dance of sending- and receiving-end equipment, and in
and capacitance as shown and independent of line length. general all of the major factors that must be considered
A convenient average value of surge impedance is 400 ohms. with regard to stability. The relation of surge-impedance
As shown in the table, this value is more representative of loading to line length, taking into account the stability
the larger stranded copper conductors than it is for the consideration, is covered in Chap. 13, Part IX.
ACSR conductors. Compared to the average value of 3% Following is a summary of approximations that may be
ohms from the table, 400 ohms is a good approximation. applied to transmission lines for estimating purposes:
Surge-impedance loading in mw is equal to 1. Series reactance of a line=O.S ohm per mile.
WL-d2 2. Shunt-capacitive reactance of a line = 0.2 megohm per mile.
Surge Impedance 3. Surge impedance of a line=400 ohms.
and can be defined as the unit power factor load that can 4. Surge-impedance loading, (SIL) in mw = 400
(km.-d*
orinkw=
be delivered over a resistanceless line such that the 12X
is equal to the charging kva of the line. Under this condi- 25(kvL-L)*.
tion the sending-end and receiving-end voltages and cur- 5. (a) Charging kva for a hundred miles of line is 20.5 percent
rents are equal in magnitude but different’ in phase posi- of the SIL.
tion. In the practical case of a line having resistance, the
(b) Charging kva of a line is also = 5000
magnitude of the sending-end voltage is approximately
equal to the magnitude of the receiving-end voltage plus where L = line length in miles,
the product of the magnitude of the current and the line kvL-L = line- to-line voltage in kilovolts.
Chapter 9 Regulation and Losses of Transmission Lines 281

for purposes of exposition. Generally the surge-impedance


loading should be considered at the receiving end because
the delivered load is usually the quantity of most interrst.

V. 60-CYCLE TRANSMISSION LINE


REGULATION AND LOSS CHARTS
The voltage regulation and efficiency of a transmission
line or distribution feeder are fundamental properties of
its performance. In determining these quantities for es-
isting systems or in designing new systems to meet given
load requirements, it is thought that the charts presented
here will save a great deal of time and labor that would
in many c&&& necessary if analytical methods were used.
For low voltage lines without synchronous or static
capacitors, voltage regulation is usually the more impor-
tant consideration. For instance, in the design of a line
to carry a certain load one wishes to determine the proper
transmission voltage and conductor size. Based on an assum-
ed allowable regulation several voltages and conductor sizes
will be found to transmit the load, the final choice being
based upon economics for which the line efficiency is de-
DISTANCE IN MILES sired. The performance of higher voltage regulated lines,
Fig. IS-Distribution of voltage and current along a 300-mile
however, is determined primarily by the line loss.
transmission line, 795 000 circular mils, ACSR conductor, 25- The charts presented here were developed with these
foot equivalent spacing. two points of view in mind. Quite frequently it is desired
-Voltage to obtain quickly an approximate solution. The Quick
_.____. Current Estimating Charts afford a simple method for such cases.
r =0.117 ohm per mile For more accurate calculations the Regulation and Loss
x =0.7836 ohm per mile Chart is provided. It is important to be able to consider
x’ = 0.1859 megohm per mile more than just the line itself. The transformers are often
the determining factor in the choice of the proper line volt-
The effect of the distributed capacitance of a transmis- age. The Regulation and Loss Chart is constructed so that
sion line on the voltage and current distribution along the from the knowledge of the equivalent impedance of a
line is illustrated in Fig. 18. The calculated results are system its performance can be determined.
based on a transmission line 300 miles in length, 230 kv,
795 000 circular mils, and 25-foot equivalent spacing. The 25. Quick Estimating Charts
LOO-percentsurge-impedance loading of the line is 139 000 In Figs. 19 and 20 are plotted curves showing the power
kilowatts. The current corresponding to this load at 100 which can be transmitted at five percent regulation to-
percent voltage is 348 amperes. The voltage and current gether with the corresponding percent line loss for various
:u-cshown as a function of the line length for 100 percent, voltages and conductor sizes. These curves afford the
:iO percent surge-impedance loading at the middle of the rapid estimation of such problems as the regulation for a
line and for zero delivered load. The voltage at the middle known load, the load limit of a line for a given regulation
of the line was maintained at 230 kv and Es and ER were and the determination of voltage and conductor size for the
:Jowed to vary depending upon the load condition. transmission of a given load at a given regulation. Fig. 21
i1t loo-percent surge-impedance loading, the voltages is an aid for interpolation between the values of power
I(,=240 kv and En= 219 kv. The current is a constant factor given on the curves.
vnlue of 348 amperes. If the surge-impedance loading is The curves of Fig. 22 give the power which can be trans-
:lssumed at the receiving end of the line, the magnitude of mitted for various conductors and voltages at a line loss of
the current is slightly different at the sending end because five percent. These curves are most useful in determining
of line resistance. The amount of this difference depends the performance of lines regulated by synchronous or static
Won the ratio of line reactance to resistance and the length capacitors.
of the line. Based on the calculated voltages of Es and ER, Charts Based Upon Regulation-- Fig. 19 applies
the regulation of the line is 9.5 percent. The value ,of specifically to stranded copper conductors, but it can be
regulation as determined from the product of the magni- used for copperweld-copper conductors with an accuracy
tude of the current and the resistance is also 9.5 percent. of two to three percent. Fig. 20 applies to ACSR con-
For 50-percent surge-impedance loading the current is a ductors. The load which can be transmitted over a line
minimum value at the middle of the line. If the surge- at a fixed regulation varies inversely with its length so that
%edance loading is taken at the receiving end, the cur- for a given line the actual load is the value read from the
rent decreases to a minimum at the receiving end. In Fig. 18 curves divided by the line length. For 220 to 440-volt lines
Surge-impednnce loading is taken in the middle of the line the values on the curves are given in kilowatts times hun-
282 Regulation and Losses of Transmission Lines
22 1.0 I.0 5.0 6.0 4.9 Percent Lass Percent Lms
(4 4.8 1.8 4.5 1.1 1.3 3.9 3.7 3.1 3.2
L 0.9 5.) 5.0 1.6 4.0 3.1 34 3.0 2.8 2.5 2.1 1.9 1.1 1.4

Conductor S,ze

5 Percent Loss
2 1.0 5.0 5.0 5.0 4.9 4.9 ,.a Percent
4.8 Loss
4.7 4.9 1.3 ,.z 4.1 3.1
~ 0.9 5.6 5.2 4.9 4.4 4.2 3.9 3.6 3.4 3.2 2.8 2.5 2.2 1.9
0f 0.8 6.5 6.1 9.9 4.9 4.5 4.1 3.1 ,4 3.1 2.6 2.3 z.1 1.8
e4wl / I I I I / I I 1 1 /
; j I I I I I , I I/
I I

Conductor Size Conductor SW

Fig. 19-Quick Estimating Charts Based Upon 5 Percent Reg-


ulation--Stranded Copper Conductors.
Percent Loss
The curves give load in kilowatts x miles or kilowatts X hundreds
of feet which can be received at 5 percent regulation together
with corresponding line loss.
For a given length of line, power is equal to value read from curves
divided by length of line.
Power for other regulations is approximately equal to values
cs Reg
read from curves multiplied by ___
5
For power factors other than given in charts, multiply values read
from curves for unity power factor by fractions given in Fig. 21.
Percent loss for other regulations and power factors than found on
charts are given by equation
(Kw Load) 2x (Power Factor):
(Percent Loss)z = (Percent LOSS)~X----
(Kw Load) 1 (Power Factor):
For single phase lines divide power read from charts by 2 and
percent loss by ~‘3.

Conductor Size
Chapter 9 Regulation and Losses of Transmission Lines

Percent Los.

Conductor Sm Conductor Sm

Percent Loss

Conductor Size

1%. lo-Quick Estimating Charts Based Upon 5 Percent Reg- dreds of feet. For higher voltages they are in kilowatts
ulation-A.C.S.R. Conductors.
times miles.
‘I’hc curves give load in kilowatt x miles which can be received For each voltage a common equivalent conductor spac-
:‘I 5 p(‘rc*ent regulation together with corresponding line loss. ing is assumed and the curves are drawn so that it is pos-
1’~ :1given length of line, power is equal to value read from curves sible to interpolate to a good degree of accuracy for other
IliMd by length of line. voltages than those given. In addition the relationship
l’o~r for other regulations is approximately equal to values read
that the power is proportional to the square of the volt-
frl)rn curves multiplied by -% Reg age may be used. Since the percent loss does not vary
r,
., - more than about a tenth of one percent for each conductor
[‘or power factors other than given in charts, multiply values read
rrorrr curves for unity power factor by fractions given in Fig. 21.
size in each set of curves, mean values are given as
p(rccnt loss for other regulations and power factors than found on shown.
“‘r:lrts are given by equation For the same line voltage, conductor, equivalent spac-
ing, and regulation half as much load can be transmitted
(Kw Load)z (Power Factor):
(l’erc’ent LOSS)~= (Percent Loss)r X on a single-phase two-wire line as for a three-phase line.
(Kw Load) 1’ (Power Factor): For this reason the curves can be used to good accuracy
‘or single phase lines divide power read from charts by 2 and for this kind of line by simply dividing by two the load
percent loss by &j. read from them. For this single-phase load the percent
284 Regulation and Losses of Transmission Lines Chapter g

Charts Based Upon Loss-Tn Fig. 22 (a) arc plotted


curves for short lines which show the power in kilowatts
h&e&&- COPPER EPUIVALENT FdR A.C.S.R. --I
times miles which can be transmitted under two condi-
tions. The solid curves are based on five percent loss and
equal receiving- and sending-end voltages. These are us+
ful for lines where little regulation can be allowed such as
on interconnected systems. The dotted curves are for the
maximum power which can be transmitted at the given
load voltage and five percent loss. For this condition the
regulation varies but in no case does it exceed about five
percent,.
Fig. 22 (b) is for higher voltage lines long enough that
distributed capacitance of the line need be considered.
Only the condition of equal sending and receiving end
voltages is considered here since regulation does not greatly
effect the power for the conductors and spacings practical
to use. For all of these curves an arbitrary coordinate sys-
tem has been used for the abscissa beneath whic.h is
plotted the correct sizes for the various conductors. The
curves here are based on 10 percent loss.
Equation (77) was used for determining the curves for
equal voltages at both ends of the line and its examination
shows that, for the practical range of losses, power for
other values of percent loss are very nearly that read from
70 Loss
I I I I I I I lllllllllllll IY, the curves multiplied by -. If greater accuracy is
5or 10
0.2 ’ 1 1 ’ 11 1111”l”““’ ’ “1
1.0 0.9 0.8 0.7
desired the factor loo’~~~oss of Eq. (77) can be used.
POWER FACTOR-LAGGING 0
Fig. 21-Effect of power factor on load that can be carried at Eq. (55) was used for the curves based on the maximum
a fixed regulation. power at five percent loss. For this case power is directly
Curves apply specifically for three foot equivalent spacing and five porportional to loss. For both sets of curves it is propor-
pcrccnt reguhttion, but cnn be used with good accuracy for normal tional to the square of the receiving-end voltage.
spacing and regulation range. The power which can be transmitted over a single-phase
line is one half that of a three-phase line of the same equiv-
loss will be that read from the charts divided by [fi alent spacing and line-to-line voltage. Thus Fig. 22(a) can
(or 1.732)]. be used to good accuracy for single-phase lines by dividing
Curves are presented for three common power factors: the values read from the curves by two.
unity, 0.9 lag, and 0.8 lag. It is difficult to interpolate for
other power factors, however, especially between unity 26. Examples of the Use of the Quick Estimating
Charts
and 0.9. To facilitate this the curves of Fig. 21 are pro-
vided showing the effect of power factor on the load that Example 6(a)-Determine the maximum load at
can be transmitted at a fixed regulation in terms of that unity power factor and five percent regulation which can
at unity power factor. The curves apply specifically to be transmitted over a three-phase five-mile line having
stranded copper conductors at a three foot equivalent. 300 000 cir mil stranded copper conductors and operating
spacing and for five percent regulation, but they will give at a load line voltage of 22 kv.
an accuracy within 10 percent for conductor spacings up to From the unity power factor curves of Fig. 19 for this
20 feet and for the same copper equivalent in other com- conductor size and voltage, 100 000 kw times miles is ob-
mon conductors. The error however may be as high as 100 000
tained. The load is then-- - 20 000 kilowatts. The
25 percent for spacings as small as 8 inches. 5
The Quick Estimating Curves can also be used for other percent loss read from the curves is 4.2.
values of regulation if the approximation is made that the Example6(b)-What is the load for this line at, this
load which can be transmitted varies directly with the regulation but 0.95 power factor lag? Referring to Fig.
regulation. 21 it is seen that for this conductor size 0.58 as much load
After having determined the load for other power fac- can be transmitted at 0.95 power factor as at, unity.
tors or regulations than those for which the curves are Thus the load is 20 000X .58 = 11 600 kilowatts. The
drawn, the percent loss can be determined from the re- percent loss as determined from Eq. (88) is .i
lation 11 600(1)2 /
(Percent Loss), = (Percent Loss)1 Percent Loss = (4.2) 2. ooo(.g5)2 = 2.7y0
“;
X --
(Kw Load)2 X (Power Factor): Example 6(c)-What load can be transmitted over thiSY
(88)
(Kw Load)1 (Power Factor): line at, unity power factor but. 15 percent regulation? ’
chapter 9 Regulation and Losses of Transmission Lines 285

Fig. 22-Quick Estimating Charts Based Upon Percent Loss.


‘hc solid curves are based on percent loss and equal receiving-
& sending-end voltages. The dotted curves are for the maximum
Pc\ver which can bc received at a given receiving-end voltage and
Wrcent loss.
For the curves of Fig. 22 (a) line capacitance has been neglected
‘md power for a given length of line is value read from curves divided
IV line length in miles. Loss base is 5 percent.
fn Fig. 22 (b) line capacitance has been taken into account and the
data is thus a function of line length. Loss base is 10 percent.
For all curves:
Fcr other values of percent loss multiply power read from curves
by tPALoss for (a) and v for (b).
5
For single-phase lines divide power read from charts by 2.

02 f E
Conductor Size
(b)
286 Regulation and Losses of Transmission Lines Chapter g

r
Since the use of the chart requires a knowledge of y and
The answer is (20 OOO)$= 60 000 kw 4J additional curves are provided to facilitate their deter,
mination. One of these is a cosine curve for determining 0
Go Ooo 12.6%
The percent loss is C-&.2)== from the power factor. For obtaining y from a knowledge
of the resistance and reactance of t,he line, tangent and
cotangent curves are plotted so that Y can be obtained
Example 7-Determine the conductor size and voltage from the ratio x/r or r/x. However, a simpler means is
necessary to transmit 10 000 kw at 0.9 power factor lag for provided for standard conductors, by the set of curves at
a distnncc of ten miles. the top and bottom of the main portion of the chart. These
This corresponds to 100 000 (kw times miles). Referring curves give y for various conductors as a function of
t,o the 0.9 power factor curves for both copper and ACSR equivalent spacing. The resistance of the conductor per
conductors for this load, it is seen that the following lines mile is necessary, and it is given for each conductor. The
can be used: values on the chart are for a conductor temperature of
50°C.
Strandetl Copper ACSR Although the chart is developed primarily for problems
involving known receiver voltage and power factor, it can
Volt,ngc Cond. Size 70 Loss Cond. Size 70 Loss
also be used for problems where the sending-end voltage
33 000 300 000 cir mil 2.5 636 000 cir mil 1.9 and receiving-end power factor and either load current or
44 000 so. 0 4.0 No. 0000 3.7 sending end kva are known. This is the commonest ‘type
GF 000 so. 4 4.5 x0. 2 5.0 of problem involving mixed terminal conditions.

28. Use of the Regulation and Loss Chart for Short


If it were desired to allow a ten percent regulation in-
Lines
stead of five percent, the value of kilowatt miles to refer
to on the curves would then be 50 000 instead of 100 000. (u) Regulate ‘on f rom Known Load Conditions-to
The use of the Quick Estimating Charts based upon calculate regulation when receiving-end (or load) voltage,
line loss is quite similar. For instance, if the line of ex- power factor, and current or kva are known:
ample 6 were equipped with capacitors so that regulation (1) Determine p =r+4 where the sign of 6 is dependent,
would not be excessive, examination of Fig. 22 shows that upon whether the current is leading or lagging.
116 000 4, the power factor angle, can be obtained from the
it could deliver a maximum of ~ = 23 200 kw at cosine curve.
( 5 >
five percent loss. y, the impedance angle, can be obtained by reading it
from the conductor curves or by calculating T/X or x/r
27. Regulation and Loss Chart whichever is less than one and reading from the cor-
responding curve. T and x are the conductor resistance
Several valuable voltage regulation charts have been
and reactance in ohms per mile.
developed. Perhaps the best known of these are the (2) Calculate percent 21 where
Dwight7 and fiIershon8 charts. The chart shown in Fig.
23 provides a means of solving not only regulation but Percent zI= (43 rs I) lOO= 100 000 rs (kva).
loss problems to a high degree of accuracy. It is just as EL cos y E2L cos y
simple in its use as any of the previous ones, but has the for three-phase lines (89)
distinct advantage that it is based upon an exact solution = (2 rs I) 100 = 200 000 rs (kva)
of the vector diagram for any circuit which can be repre-
sented by a single lumped impedance. For this reason EL cos y EzL cos y
problems involving the determination of the load which for 2-wire single-phase lines 0394
can be transmitted for a given regulation can be solved EL is the line voltage in volts. s is the length of the
much more accurately than from charts based upon ap- line in miles.
proximations. (3) For the calculated values of p and percent Z2 read
The chart is developed on the principle that for a given percent regulation from curves of const,ant regulation.
difference in magnitude between the sending-end and re-
ceiving-end voltages, the impedance drop (21) is fised (b) Load Limitationfor Fixed Regulation-To de- 1
6
termine load limit for a given value of regulation:
entirely by the angle p = r+q5 where ( y = tan-‘? 7) is the (1) Determine p as in above and from chart for given’
value of regulation and p read the corresponding4
impedance angle of the line and r$ is the power factor angle. ‘*
percent ZI.
For lagging power factors 4 is negative and for leading
power factors 4 is positive. Thus, corresponding to vari-
ous values of percent regulation, the corresponding percent
ZI can be plotted as a function of the angle p. These are for three-phase lines
the set of curves on the chart for voltage drops from 0 to
15 percent and voltage rises from 0 to 5 percent. The = F,%ZIPi cosY
value of the percent (ZI) is the same whether p is positive 200 000 7-s
or negative. It depends only upon its magnitude. for single-phase 2-wire lines (9Oa)
Impedance Angle 7’
for ACSR Conductors

Impedance Angle 7

Solid curves for stranded copper


conductors.
Dashed curves for composite coppa-
copperweld conductors.

Fig. 23-Regulation and Loss Chart for transmission lines.


288 Regulation and Lasses of Transmission Lines Chapter

(c) Line Eficiency-The line loss in percent of the Reading from the chart for this percent ZI and p 141.1
load kva is given by the equation the regulation is found to be 5.0 percent.
Percent Loss = 7ORI = To ZI cos y
Example B(b)--Determine the maximum kva that c
(91) be transmitted over this line at the same power factor f
where cos y can be read off its cosine curve from the known a regulation of no greater than 5 percent. Reading frc
value of y. The loss can be determined in percent of the the chart for 5 percent regulation and p of 41.2’, the perce
load in kilowatts by dividing the value obtained from ZI is found to be 6.54.
Ey. (91) by the power factor. If it is desired to determine Using Ea. (90) :
Y ..,

the percent loss for a given regulation, the percent 21 can Load in kva = (652) (33 000)“(0.390)
be obtained without the use of Eq. (89). It is simply (100 000) (0.303) (10)
necessary to determine p and for this angle and the given =9140
regulation to read the (percent 21) from the chart.
(d) Use of Chart for Known Sending-End Voltage Load in kw = (9140) (0.9) = 8230.
and Receiving-End :Power Factor-The chart can be Example 8(c)-As an example of the calculation
used to as good accuracy as desired for problems of this efficiency for the above case using Eq. (91) :
nature. As a first approximation the regulation, in percent Percent loss = (6.52) (0.390) = 2.55.
of the sending-end voltage, can be obtained as outlined in
Example 8(d)--For this same line operating at
(a) when the sending-end line voltage is used in Eq. (89).
sending-end line voltage fEsr,) of 33 kv and a sending-e
Either the line current or the load kva expressed in terms
load of 9140 kva but a receiving-end lagging power fat
of the sending-end voltage can be used. The load (or
of 0.9, determine the line voltage at the load end.
receiving-end) voltage can be calculated from this regula-
As shown in Example 8(a) :
tion and the sending-end voltage. This first approximation
will usually give the load voltage to an accuracy of about The value of percent 21 determined as a first apprl
one percent, but the percent accuracy of the regulation imation by using the sending-end voltage and kva
may be much worse depending upon its magnitude. Eq. (89) is
.4 more accurate value can, however, be very easily Percent ZI = 6.52
obtained by the following method of successive approxi- and p=y++=41.2’
mations. Using this first determined value of load volt- Thus as a first approximation
age and then each successive value obtained, recalculate Percent Reg. = 5
the regulation. One or two such steps will usually give
very good accuracy. When calculating the percent ZI in &,=%=31.42 kv.
this process it is not necessary to solve Eq. 89 each time.
As a second approximation
The new value of percent ZI can be obtained by dividing
the first value calculated by the ratio of the load voltage Percent ZI= (1.05) (6.52) = 6.85
to the sending-end volt,age. This type of problem is illus- reading from the chart for percent ZI = 6.85 and p =41
strated in Example 8(d). Percent Reg. = 5.20
It is, of course, obvious that the load limit for known
sending-end voltage, load power factor, and regulation EL= -=31.35
ESL kv.
1.052
can be determined as in 28(b) after the load voltage is
As a third approximation
calculated from the regulation and sending-end voltage.
Percent ZI= (1.052)(6.52) =6.87
29. Examples of the Use of the Regulation and Loss Percent Reg. =5.25 (as closely as can be read from
Chart chart)
Consider a three-phase line ten miles long with No. 0000 EL= -=31.34
EsL
stranded-copper conductors at an equivalent spacing of kv.
1.0525
six feet and operating at a line voltage of 33 kv at the load
end. 30. Use of Regulation and Loss Chart for Long Lil
Example 8(a)-For rated voltage at the receiving end AS shown in Sec. 16, methods of calculating regulat
and a 9140 kva load at 0.9 power factor lag, determine the for short lines can be applied to lines up to 100 mile:
regulation. length to a good degree of accuracy by simply adding
Referring to the impedance angle curves for stranded correction factor (-2.OW) to the percent regulat
copper conductors at the bottom of the chart, the im- where S is the length of the line in hundreds of miles.
pedance angle for this conductor and spacing is y=67.2’. If greater accuracy is desired, the chart can be u
Cos y is 0.390 and the conductor resistance is 0.303 ohms with the equivalent load current and power factor
per mile. Reading from the cosine curve the power factor tained as described in Sec. 14. Using this method b
angle for 0.9 power factor is 4=26’, and the sign is regulation and efficiency can be determined.
minus p=y++=67.2’--26’=41.2”
From Ea. (89): 31. Determination of Effect of Transformers
percent ZI = (100 000)(0.303)(10)(9140) Line Performance
(33 ooop (0.390) The chart can be used as described in Sec. 28 for
= 6.52 termining regulation and efficiency of transformers
chapter 9 Regulation and Losses of Transmission Lines 289

though the transformer charts in Chap. 5 are simpler. In The total impedance is
considering the performance of a line and transformers Percent Z = (2.37fj7.16) +2(0.7+j5)
together, however, the chart can be used to advantage. = 3.77+i17. I6
The impedance of the transformers can be combined with
that of the line into a single impedance. These impedances
cun he expressed either in ohms or in percent on some
cOmmon kva base. Transformer impedance is usually Reading from the chart for this ratio
given in percent. It can be expressed in ohms by the y = 77.7”
p0uation cos y=o.219
For 0.9 power factor += -26”
p=51.7
The transmission line impedance in ohms can be trans- From Eq. (94)
formed to a percent basis by the equation
Percent ZI = (&) (s) = 15.94
z z (ohms) (kv4
(Dercent) = (93)
E2Lcw) (10) The regulation read from the chart for this percent ZI
~hc transmission line resistance can be read directly from and the calculated value of p is
the chart and the reactance obtained from the chart Regulation = 10.5%
hy rending the line impedance angle y from the chart and The loss in percent of the load in kw is from Eq. (Olj
the ratio of r/X or x/r for this angle.
For problems of this type it is usually easier to use the
impedance in percent. After having obtained the total
equivalent percent R and percent X, the equivalent angle
7 can be read from the curves for the ratio of R/X or
x/R. The percent ZI can be calculated from the equation
REFERENCES
rcrcent ZI = (% Rz = %R) (rated load) (actual load) cg41
Principles of Electric Power Dansmission, by L. F. 1Voodruff
(rated load)
cos y
(a book), John Wiley & Sons, Inc. Second Edition, p. 106.
Example ~-AS an example of the calculation of a Tables of Complex Hyperbolic and Circular Functions, bp Ken-
problem of this type consider the 10 mile, 33 kv, 300 000 nelly (a book), Harvard University Press.
cir mil stranded copper line found adequate for the Chart Atlas of Complex Hyperbolic and Circular Functions, by
(10 000 kw= 11 111 kva) load at 0.9 power factor lag of Kennelly (a book), Harvard University Press.
l&ample 7. Transmission Line Circuit Constants, by R. D. Evans and
H. K. Sels, The Electric Journal, July 1921, pp. 3Oi-390 and
Assume that it has transformers at each end rated at
August 1921, pp. 356-359.
12000 kva with 0.7 percent resistance and 5 percent re- 5. Circle Diagram for Transmission Lines, by R. D. Evans and
actance, and let us calculate the total regulation and loss H. K. Sels, The Electric Journal, December 1921, pp. 530-536
of the system. and February 1922, pp. 53 and 59.
Reading from the chart 6. Some Theoretical Considerations of Power Transmission, by
C. L. Fortescue and C. F. Wagner, A.Z.E.E. Transactions, V. 43,
The line resistance is (0.215)(10) = 2.15 ohms
1924, pp. 16-23.
T/X for the line impedance angle of 71.6” is 0.330 A Chart for the Rapid Estimating Of’AIternating Current Power
The line reactance is g= 6.51 ohms Lines, by H. B. Dwight, The Electric Journal, July 1915, p. 306.
Electrical Characteristics of Transmission Circuits, by MXiarn
The percent impedance of the line on a 12 000 kva Nesbit (a book), Westinghouse Technical Night School Press.
base is from Eq. (93). Third Edition, pp. 43-45.
The Transmission of Electric Power, by W. A. Lewis (1948
PercentzL=(2.11i+j6’51)(12Ooo)=2.37+j7.16 Lithoprinted Edition of Book), Illinois Institute of Technology.
(33)*(w
CHAPTER 10

STEADY-STATE PERFORMANCE OF SYSTEMS INCXSJDING


METHODS OF NETWORK SOLUTION
Oricjhd Aulhor: Revised by:
E. L. Harder E. L. Harder

A
POWER system must generate, transmit, and then is particularly well suited to regulation and apparatus
distribute electric power to the desired points, reli- loading studies. The met,hod of Driving Point and Trans-
ably and in good condition. The electrical perform- fer Admittances or Impedances is well suited to power
ance of the system as dealt with in this chapter is the flow or stability studies on multiple-entrance systems, and
measure of how well it performs this task and is espressed the General Circuit Constants, RBCD, or the equivalent
by such quantities as voltage regulation, loading of lines Pi and T are similarly advantageous for the transmission.
and equipment, efficiency and losses, and real and reactive type network having two significant terminals.
power flow. Stability, of vital importance also, is dealt These methods of network representation and solution
\vit,h in Chap. 13. constitute a highly developed science with extensive pres
The key to the determination of such system quantities ent literature. However, as they constitute the heart of
is the network solution, or determination of currents and the problem of steady-state performance of systems as Well,
voltages throughout the system for any prescribed con- as of many other system problems, a large part of this
ditions. From the network solution can be determined all chapter will he devoted to them. In general, the most
of the essential electrical characteristics that, are dependent commonly used methods will be outlined ant1 illustrated
upon the fundamental-frequency currents and voltages. by examples. For further information a bibliography of
Network solution is based on Kirchoff’s two laws: selected references is included.
Network solution, once accomplished largely by analyt,-
First, that the vector sum of all the voltages acting
ical methods, is now performed to an increasing estent by
around any closed loop is zero.
a-c and d-c network calculators. However, many problems
And second, that the vector sum of all the currents
are still solved analytically and also a thorough knowledge’
flowing to any point is zero.
of methods of network representation and solution is as’
In the course of applying these elementary principles essential as ever to the system designer. Fortunately, how-
to the solution of thousands of linear networks for many ever, the calcrllator has removed the enormous burden of
years, various investigators have found several powerful routine calculation and has made it economically possible
theorems that follow directly therefrom, such as the super- to solve complicated systems. Analytic methods are still
position theorem*, the reciprocal theorem, and Thevenin’s largely used for the simpler studies or where network
theorem. These theorems not only assist in visualizing the calculators are not available.
phenomena taking place in the circuits, but also greatly
simplify and systematize the work of solution for thespecies
of networks to which they apply. I. NETWORK REPRESENTATION
The method of symmetrical components, given in Chap.
2 is a highly developed special application of the super- 1. Single-Line Diagram. Fig. 1
position theorem, taking advantage of the symmetry of In dealing with power systems of any complexity, one ’
the several phases of the usual polyphase power system. of the first essentials is a single-line diagram, in which each .,
The direct use of KirchoWs Laws can be designated as polyphase circuit is represented by a single line. Stripped
“Solution by Equations,” to distinguish it from “Solution of the complexity of several phase wires, the main power
by Reduction” in which portions of a system are progres- channels then stand out clearly, and the general plan of
sively replaced by simpler equivalents until a single branch the system is evident. Most power companies maintai
remains. This latter makes use of the superposition theorem up-to-date single-line diagrams of their systems.
in treating one emf at a time. Also, it utilizes equivalent This diagram is a short-hand or symbolic representatio
circuits, many of which are now available. of the principal connections, showing the equipment in its
Thevenin’s theorem and the superposition theorem have correct electrical relationship and usually having indicated
provided direct methods for obtaining solutions in net- on it, or in supplementary tabulations, data essential
works of several fixed emfs, with enormous simplification. the determination of the impedance diagram. The reco
Solutions of networks can be expressed in many forms, mended symbols for apparatus are given in Table 1(
each one being particularly adaptable to certain types of In addition, auxiliary symbols, Table l(b), are inscrib
networks or certain problems. Thus, the expression of so- near the devices in question, to indicate the winding c
lutions 8s “Self and Mutual Drops and Current Division” nections and the grounding arrangement, if any, at t
290
chapter 10 Steady-State Performance of Systems Including Methods of Network Solution 291

TABLE l(a)-GRAPHICAL SYMBOLS FOR DIAGRAMS”-EQUIPMENT SYMROLS

NAME -COMPLETE * NAME JE LINE COMPLETE *

,c. GENERATOR OR MOTOR+ JOUBLE THROW SWITCH

YNCHRONOUS CONVERTER
45 IIL CIRCUIT BREAKER,
SINGLE THROW

,REGT CONNECTED UNITS


BASIC SYMBOL O-0 4lR GlRCUtT BREAKER

(Use particular symbols ond join


ok here shown.)
‘wO-WINDING TRANSFORMER+ ‘USE
BASIC SYMBOL

THREE-wINDING TRANSFORMER+ RESISTOR

\“TOTRANSFORMER+ REACTOR.-..

CAPACITOR
;URRENT TRANSFORMER

LIGHTNING ARRESTER
7OTENTIAL TRANSFORMER

POTHEAD CABLE TERMINAL


INDUCTION VOLTAGE REGULATOR

DRY RECTIFIER
DISCONNECTING OR KNIFE SWITCH

AIR BREAK SWITCH, HORN GAP, MERCURY ARC RECTIFIER


GROUP OPERATED

*The “Complete” symbol is intended to illustrate the method of treatment for ony desired polyphose combination rother than -to show the
exact symbol required. Use symbol f m) for windings of opparatus as required, and connect to suit porticulor Case.
+ Inscribe winding connection diagram symbol from Table lb.
0 For complete lists see American Standards 232.3-1946,232.12-1947

rout ml. The use of these auxiliary symbols is illustrated and its implications are discussed in detail here.
in lcig. 1. The complete specification of real- and reactive-power
Similar diagrams showing circuit breakers and dis- flow in a circuit requires:
connecting switches are used as power-system operating First, an indication of the direction spoken of, i.e., a
(Jiagrsms. Or they can be marked with suitable symbols to reference-positive direction.
show the relay (See Chap. 11) or lightning protection. Second, numerical values and associated signs. The
numerical values give the magnitude of the real- and
2. The Sign of Reactive Power reactive-power components respectively. The associated
The + sign used with the reactive-power terms in the signs show whether they flow in the reference-positive
lo& of Fig. 1 d esignate lagging-reactive power in accord- direction or not.
ance with the standard notation approved by the AIEE Third, there must be a convention as to whether it is
Standards C ommittee on .Jan. 14, 1948 and recommended lagging-reactive power or leading-reactive power, the di-
for adoption to the American Standards Assn. and the rection and magnitude of which is being specified.
m. S’mce this is a change from the convention used in Lagging-reactive power is that which is generated or
editions 1 to 3 of this book the history of this standard supplied by an over-excited synchronous machine or by a
292 Steady-State Performance of Systems Including Methods of Network Solutioll,

TABLE 1(b) - GRAPHICALSYMBOLSFOR DIAGRAMS- WINDING 4-10,000 KVA HYDRO-GEN.


CONNECTIONSYMBOLS
I fik,000+j6200)KVA (5O,OOO+j37,500) UVA
NAME SYMBOL

TWO-PHASE, THREE-WIRE L 110 KV, 15 FT. EO. SPACING


50 MILES NO. 2/O COPPER
’ 2-31,250 KvA
STEAM TURSD
GENERATORS
TWO-PHASE, FOUR-WIRE + 3-10,000 KVA
TRANS. UNITS
A
IN EACH LINE
THREE-PHASE, DELTA (OR MESH) n
a>

THREE-PHASE, Y (OR STAR) Y


THREE-PHASE, Y (OR STAR) WITH NEUTRAL
BROUGHT OUT AND GROUNDED
%
THREE-PHASE,
GROUNDED
Y (OR STAR) WITH NEUTRAL
THROUGH A RESISTOR
---f-7
THREE-PHASE, ZIG-ZAG
?-
THREE-PHASE, T L.

static capacitor and used by inductive loads such as induc-


tion motors, reactors, and under-excited synchronous
machines.
According to the convention recommended by AIEE in
lW~,and used throughout this book the positive sign for
reactive power indicates that lagging-reactive power is
flowing in the reference-positive direction. The vector 3-10,000 KVA & A A .f 3-16,666 KVA
relationship for power is therefore:
P+jQ = Ef, the symbol + designating conjugate.
For example if E is taken as reference, E =E and if (10,000+i7OOO) KVA 2-25,000 KVi
I=p-j1” is a lagging current, fl and 7’ being positive STEAM TURBO GENERATORS
quantities, the real power is 1’ =Ep and the lagging-
reactive power is Q = iZ’. Fig. l-Single-line diagram of a power system.
The espression,
p+jQ=EJ=E(l’+jf”) =~~-/-j~~' P+jQ=li2Z
results in the proper sign for the P and Q terms, whereas The form PfjQ =E2Y is then erroneous and gives the
EI would give the right values but the wrong sign for the wrong sign for Q.
Q term. With this new convention, and taking E as refer- For the conventional transmission line, with this concept
ence, the power vector P+jQ lies along the conjugate of (lagging-reactive power positive) the center of the sending-
the current vector. Consequently current and power circle end power-circle diagram lies in the first quadrant and the
diagrams lie in conjugate quadrants. center of the receiving circle in the third quadrant.
Historical Summary-Originally there was one school The other school of thought used leading-reactive power
of thought, typified by Evans, Sels?, and others, that used as positive, lagging-reactive power as negative. This had
the positive sign for lagging-reactive power for the same the theoretical advantage of throwing current and power
reasons that it has now finally been adopted. The principal circle diagrams into the same quadrant, but the disadvan-
reasons were these. Like real power, lagging-reactive power tage that lagging-reactive power, the reactive commodity
is generally used in the load and must be supplied at some usually dispatched by power-system operators, was then
expense in the supply system. It is thus the commodity a minus quantity. This concept is consistent with the
dealt with by the practical power-system designer, and mathematical forms: -
dispatched by the operators. This concept is consistent Power associated with a voltage E and a current I is:-
mathematically with the following forms:
Power associated with voltage E and current I is: P+jQ= EI
Power flowing into an admittance Y due to a voltage
P+jQ=EP E is:
and power in an impedance Z to a current I is: P+jQ =E2Y 1
Chapter 10 Steady-State Performance of Systems Including Methods of Network. Solution 293

The form P+jQ=?*Z is then erroneous and gives the 20 zb


2.82+j32.3 OHMS 24.05+j43.05 OHMS
lvrong sign for Q. vvv 4,
The latter school, (lending-reactive power positive) won A ..- a..7 -
-7 ‘-‘- j1.25X10-4MHOS j1.25XIO~4MHOS 48
out, for the time being, on the basis of the theoretical
-jSOOO OHMS -j8000 OHMS
considerations, and on August 12, 1941 the American
r! ZC
Standards Association approved this convention as an izm
r T
industry standard, C42-1941, Section 05.21.050. The first 7 9 v ?
tlrrec editions of this book followed this standard conven- zt!O
tion. However, the convention was never followed by
&em-planning and operating people to any extent. They
continued to dispatch lagging-reactive power which they
called simply “reactive,” and to mark on their flow charts
the direction in which lagging-reactive power flowed. They
could not be converted to selling a negative amount of
leading-reactive power for positive money, but preferred
to sell a positive amount of lagging-reactive power.
A majority of engineers have now come to consider
lagging-reactive power as the commodity being dealt with.
The ATEE Standards Committee recognizing this fait
acwmpli recommended to ASA in 1948 adoption of the
convention making lagging-reactive power positive. This
reference book has, starting with the fourth edition, 1950,
heen changed to conform with what will undoubtedly be
the smndard from now on, namely, lagging-reactive power
.
D, 9.75+j57.9 OHMS
e eat ers and writers can materially aid in eliminating VAP :
confusion by discontinuing all use of the term leading- *“j1.25:10-4 ’ :
z
I
reactive power which after all is simply an unnecessary MHOS
name for the negative of lagging-reactive power. Such a
5

n_Ki
10
z j2.08 XIOw4
MHOS MHOS
j2.08 X 10e4

term is no more necessary than a name for the negative


of real power. Eventually if this is followed the adjective
“lagging” can be dropped, as reactive power will always
ei

z
+
a
.- $1:
+ v
-j4980 OHMS
T ?
-j4980 OHMS

i
mean lagging-reactive power.
D
3. Impedance Diagram. Fig. 2
The second essential in analytic study of a power system Fig. 2-Impedance diagram of a system shown in Fig. 1.
is the impedance diagram, on which are indicated on a
common basis, the impedances of all lines and pieces of
4. Determination of Impedances
equipment related to the problem. Because of the sym-
metry of phases it is usually sufficient to represent only In general, accurate cable and overhead-line impedances
one phase--called the reference phase, or a phase. Under can be obtained from the tabulations of Chaps. 4 and 3, in
balanced conditions of operation, the currents and volt- terms of the wire size and spacing. Average apparatus
ages in the other two phases are exactly equal to those in a constants are given in the tabulations of Chap. 6, Machine
phase and merely lag behind the a phase quantities by 120 Characteristics, and Chap. 5, Power Transformers and
ant1 240 electrical degrees. Hence, when the a phase quan- Reactors. More accurate figures, if required, can be ob-
tit.ics have been determined, the others follow directly. tained from name-plates or direct from the manufacturer
Even when unbalances, such as a line-to-ground fault, of the equipment. The impedances of lines and trans-
or one-wire-open, occur at one or two points of an otherwise formers in Fig. 2 have been obtained, for example, from the
balanced polyphase system, the impedance diagrams for tables of Chaps. 3 and 5 based on the data given in Fig. 1.
the reference phase are sufficient, if use is made of the Representation of Loads-The necessary representa-
method of symmetrical components as outlined in Chap. 2. tion of loads in the impedance diagrams depends upon
The impedance diagram, corresponding to the system the use intended. In short-circuit studies, loads are most
shown in Fig. 1, is given in Fig. 2. Generator impedances frequently neglected. In stability studies, they must gen-
are not shown as they do not enter into the particular erally be considered. Several methods of representing loads
problem. All impedances on this diagram have been ex- are as follows :
Pressed in ohms, and admittances in mhos, on a llO-kv a. Shunt impedance that draws the same kilowatts and
base. Actually there are several choices, such as percent reactive kva at normal voltage as is drawn by the
or per unit on various kva bases or ohms on voltage bases actual load.
other than llO-kv. The relations between these several b. An impedance circuit, which, for any conditions of
methods, and factors affecting the choice are discussed voltage is adjusted to draw the desired amount of
subsequently. real and reactive power.
294 Steady-State Performance of Systems Including Methods of Network Solution Chapter 10

c. In network calculator studies, the use of a “sourcc”t x = 1000(0.44)'=,


1000(kv)2 22 ohms

xljustetl, in phase angle and mngnit,ude, to draw the ’ l.Oj*(kvs)


1.05Xl~O .
desired rcnl xxi reactive powr from the system. This ohmic value can be converted to percent by Eq. (12)
(1. Given any characteristics of variation of real and Shunt Reactors hnve 100-percent volt,uge drop acrosg
re:wtiw power with voltage, the load can be con- them when connected to normal voltage, or have loo-per-
verted to impedance at the cspected voltage, this cent impedance based on the kva drawn from the system
impedance used in determining the system voltages, at normal voltage.
and then the load impedance corrected to the new Series Reactors-The reactance of a series reactor iy
voltage if such correction is warranted. frequently expressed in percent, but the kva of its parts
Conversion of Load Kw and Reactive Kva to is given. Thus, if a G-percent reactor is desired in a circuit
Ohms Or MhfW-Loads given in kilowatts and reactive having a rating of 10 000 kva, three-phase, the reactor
kva can be converted to impedance or admittance form by rating Iv-ill be 600 kva, three-phase (6 percent of 10 000
that following equations: kva). Three 200-kva single-phase reactors might be used.
These would ordinarily be rcferrctl to as three 20%kva
Let I’ = kw (three-phase) G-percent reactors, whereas actually they constitute i
Q = reactive kva lagging t(three-phase) three-phase reactance in the circuit having O-percent re-
ZL-~ = line-to-line voltage in kv at which the conver- actance on a 10 OOO-kva base. Care must, be t,aken, therc-
sion is to be made. fore, to determine the reactance value on the through or
Z = vector impedance value, ohms line-to-neutral. transmitted kva base, or 10 OOO-kva base in the esimplc
Y = vector admittance value, mhos, line-to-neutral. cited. The relation between reactor kva, and through kva
i: = lOOOE?L-r, 1000E2r,-~, are as follows:
--=P-jQ P2+Q2 V'+.iQ) Reactor three-phase kva rating = a
Through or transmitted kva rating=.4
lOOO(kv)" Percent reactance on the transmitted kva bnse=X
ohms, line-to-neutral (1)
kw - j reactive kva (lagging)
y= P-jQ kw-j reactive kva (lagging)
Then (3;’
1OOOE”~-r, = 1000(kv)2 Given the reactor three-phase kvs rating, a, the through
mhos, line-to-neutral (2) kva rating is
For example, at 13.8 kv a load of 10 000 kva at 80
(4)
percent power factor lugging may be expressed as:
P=8000 kw Q = +GOOOreactive kva The reactor has a reactance of X percent on the kvn base A.
In the case cited above of a GOO-kvn, (i-percent reactor,
The impedance required to represent it is:
Eq. (4) gives A =7X600 = 10 000. Whence, the reactor
7'= 1000(13.8)* ohms,
--(8OOO+j~OOO)=15.2+jl1.4 has a reactance of ci percent on a 10 OOO-kva base.
' (G000)2+~8000)2
,., I
line-to-neutral The standard reactance tolerance of current-limiting
and the admittance is: reactors is -3 percent to $7 percent for single-phase and
-3 percent to +lO percent for three phase. The rated
,=SOOO-j6000 reactance is generally used in system calculations unless
= 0.0420 --jO.O315 mhos, line-to-neutral.
1000(13.8)2 test figures are available.
Y and Z as given above are the admittance or impedance 5. Conversions. Percent to Ohms and Ohms to
values to be used in the single-phase impedance diagram in Percent t
which only the reference phase and neutral are represented. Method I-Tf a base kva (three-phase) and kv (line-
Shunt Capacitors are built to a tolerance of -0 to to-line) are selected, the corresponding normal or base
+lO percent of their rated kva, +5 percent being the
current, line-to-neutral voltage, and impedance values can
average. It is generally sufficiently accurate to consider be immediately determined.
the reactance to be 100 percent based on 105 percent of They are:
the rated kva base. kva
Series Capacitors-The determination of reactance Normal Current 1, = ___
d/,(kv)
amperes m
of a series capacitor can best be explained by esample.
Suppose ten standard 15-kva single-phase, 440-volt, shunt- Normal Voltage E = 1000&v) volts
capacitor units have been used in parallel in each phase, (line-to-neutral) n 42
or a total of 150 kva per phase. The capacitive reactance
presented in series in each phase is then: En ohms per phase,
Normal Impedance 2, = 7 line-to-neutral. (8) 1
LL
tThe “sources” arc voltage regulator-phase shifter circuits from a
main power bus and can be readily adjusted to either draw or feed *If the ratio of actual to rated kva is known, it should be used in
the desired quantities of real and reactive power. place of 1.05.
tQ is positive for lagging reactive kva. t(Note: Per TJnit is percent divided by 100).
chapter 10 Steady-State Performance of Systems Including Methods of Network Solution 295

l+om thcsc rc!ations any percent impedance can he con- and “turns ratio” are often used loosely as synonymous
\verted to ohms. terms, until more precise or important, calculations are
percent impedance being made for which it is desired to be quite accurate.
ohms = (normal impedance) Then the question sometimes arises as to whether imped-
100
=z,
cg) 6.0
ances should be transferred to the voltage base on the
other side of a transformer on the basis of its voltage ratio
or its turns ratio. It is actually the turns ratio that wmts
and should be used as will be shown later in this section.
(*onverscIy any ohmic figure can hc converted to percent.
The turns ratio is the same as the nameplate voltage ratio
but cliffcrs from the terminal voltage ratio under load.
11Isoin approximate calculations it is frequently assumed
that for all parts of the system of the same nominal voltngc
Method 2-The magnit,llcIe of Z,, from (S), (T), and the same transformation ratio can be used to t,hc tlcsirctl
((;) (‘a11IX: substituted in (!I) anI1 (IO) ant1 gives direct voltage base. This is a rough approximation and becomes
,,,,nvcrsions: exact only if the transformer turns ratios between pa& of
t,he system at the same nominal voltage are all unity.
(11) Earring this, one correct procedure is to select some one
point of the system as a base and transform all other
(12) impedances to this base by multiplying by the square of
the intervening turns ratios. Once all impedances are on
I”or os:tItlple, a 1.5OOO-ltva,I3.f$-kv t;o(Xi-kr- transformer a common base they can all be transformed by a single
l~ml< 1l:LSa rP:L~t:lnc*eof 8 pcrcwit, on the I .j 000-kva has?C multiplier to any other voltage base.
I.(+ it, be wclllircd to determine its impedance in ohms on When impedances are in percent on a given kva base the
:1(j(i-kv IXLSC. percent refers to a given normal voltage. Thus strictly t’wo
?;oI~:LI cuncnt : conditions must be fulfilled in sequence for percent im-
pedances to be used in network solutions. First,, the normal
voltages t,o which the percentages refer must be in the same
ratios as transformer turns ratios throughol~t the system.
Second, the normal voltage used in converting the answers
from percent to amperes and volts must be the same as t:hc
(Xi 000 normal voltages on which the percent impedances are
E,,=- = 38 100 volts, line-to-neutral.
+‘jj based. Otherwise approximations are involved. These
approximations can be eliminated by suitable transforma-
Sormal impedance:
tions beyond the scope of this chapter except for the
z =38 100 following general method.
I, ~ = 29 1 ohms per phase, line-to-neutral. Where doubt exists as to the correct direct transformn-
131
tion of percent impedance, the impedance of each element
‘I’r:msformcr impedance = S percent of 20 I can be converted to ohms. The ohmic values can be con-
=23.3 ohms per phase at 66 kv. verted to a common base as described above and combined.
‘I’he direct dcterminntion from (11) is, The result can be reconverted to percent on any desired
‘I’ransformrr impedance kva and voltage base. This is the general procedure by
=8((i6)Z(10) which rules for direct percent-impedance transformations
=23.3 ohms per phase. are derived.
15 000
The pitfall of ignoring near-unity turns ratios extends to
The first method is longer, but gives other information voltage also. Suppose a 13%kv generator feeds through
wwrally required in the problem, and has some advantage step-up and step-down transformers to a 13%kv distribu-
ill visualizing the procedures. tion system and that impedances have been expressed on
the distribution system voltage base. Suppose further that
6. Conversions to a Different Kva Base there is a resultant 1:l.l step-up turns ratio between the
From (I 2) it is apparent that for a given ohmic imped- generator and the distribution system. Then a generator
:MX the percent impedance varies directly with the kva operating at 13.8 kv would be at 13.8X 1.1 = 15.18 kv on
I)nseselected. Thus lo-percent impedance on a 10 OOO-kva the 13%kv voltage base of the distribution system, and
IUC becomes loo-percent impedance on a 100 OOO-kva must be so treated in the calculations. Similarly, for cal-
h:lse. When using percent impedances, all percentages
._ __--_-. culations in percent, the same machine must be treated
should
_2_ be expressed on the same.lC base. as operating at 110 percent voltage. The theoretical basis
upon which all such transformations rest, and examples of
7. Conversions to a Different Voltage Base their correct use is given in the following paragraphs.
Tn system studies if impedances are expressed in ohms From an energy or power standpoint, no change is made
it is desirable to convert them all to a common voltage base if all voltages are multiplied by a const,ant, N, all currents
so that transformer turns ratios need not be considered in divided by N, all impedances multiplied by N”, and all
the subsequent calculations. The terms “voltage ratio” admittances divided by N2. When two circuits are sepa-
296 Steady-State Performance of &stems Including Methods of Network Solution Chapter 10

(TTjf---yZL (1q5)(10)(13’8)“4
50 000 .
571 ohms
at 13.8 kv

ACTUAL TRANSFORMER The transformer reactance in ohms is:


(0) ACTUAL CIRCUIT (9)(10)(13.8)2
=0.343 ohms at 13.8 kv.
50 000
LEAKAGE IMPEDANCES The line impedance is, from Chap. 3.

@+kg@!qZL 9.75fj57.9 ohms at IlO-kv. [See Fig. 4(c)]

IDEAL TRANSFORMER EXC,T,NG 110 KV 15 FT. Eauw, SPACING


IMPEDANCE d; I’ 75 MILES 500 MCM cu. x
(b) TRANSFORMER REPLACED BY IDEAL TRANSFORMER 8 IMPEDANCES 50,000 KVA 50,000 KVA
TURBO-GEN. 9X REACT,
(a) SINGLE-LINE DIAGRAM
13,800

Nyp$--$~~Q*L v-5
&--WV
jO.571 j0.343 0.154+jO.910

I
IDEAL TRANSFORMER L-----,------,,-,---
(b) IMPEOANCE DIAGRAM
(c) TRANSFORMATION N
110,000 ALL IMPEDANCES IN OHMS AT 13.8 KV
VT j36.2 j21.7 9.8+j57.9
&--+-WV v-vv
f
L -a-- -----m----_____
(c) IMPEDANCE DIAGRAM
ALL IMPEDANCES IN OHMS AT 110 KV
o.l5 0.09 0.04+jO.239
cd) TRANSFORMER OMITTED
9 IO- vvv
I-e.oe z *0.04+jo.479
Fig. 3-Power invariant transformation. I ‘0.48
I- ------------_-___ PER UNIT
(d) IMPEDANCE DIAGRAM
rated by an ideal transformer* of turns ratio N, such an ALL IMPEDANCES IN PER UNIT ON A 50,000 KVA BASE
operation performed on the quantities on one side of the Fig. 4-Problem illustrating the expression of ohms on vari-
transformer with a corresponding change in the trans- ous voltage bases and the relation to percent on a kva base.
former ratio, has the advantage of bringing the currents
and voltages on the two sides to an equality. A direct The shunt impedances of this line are high (line CD’ Fig.
connection can be made and the ideal transformer can be 2) and will be neglected for simplicity in this problem.
omitted from the diagram (see Fig. 3). Solutions can be Use of Generator Voltage Base-If the current in
made with the quantities on the fictitious or transformed the generator is desired, it will be most convenient to
voltage base, and they can be reconverted to actual express all impedances on the generator voltage base. The
quantities whenever desired. generator and transformer impedances are already on this
.\n actual transformer differs from an ideal transformer base. The line impedance is converted to it by multiplying
in two respects only. It has primary and secondary resist- by the square of the turns ratio, usually taken as the
ances and leakage reactances, which are no different than nameplate voltage ratio corresponding to the taps in use.
the same impedance connected externally. Its primary Thus the line impedance is:
and secondary ampere-turns differ by a small quantity
of exciting ampere-turns that excite the core. A shunt (9.75fj.V.g) E 2=0.~M+j0.910 ohms at 13.8 kv. :;
branch can be connected which draws the requisite exciting ( )
B
current if important in the particular problem. The impedance diagram of Fig. 4(b) results, in which .$
Example---As an example consider the circuit of Fig. 4, all impedances are expressed in ohms on a 13.8-kv base. $
a generator, transformer and high-voltage line with a three- The fault current in the generator is then: P.
::
phase short circuit at the end. Suppose the short-circuit
currents are to be determined. This problem will also illus- I= poo -= 4350 amperes.
trate that calculations can be made interchangeably with d/3(1.830)
impedances in ohms on any voltage base or in percent on The current flowing in the line is:
any kva base.
The generator reactance (assumed 15%) in ohms is
from (11):
*A transformer having zero exciting current and zero leakage Use of Line Voltage Base-A similar result would be
impedance. obtained if the generator and transformer reactances had
Chapter 10 Stead+Ytate Performance of Systems Including Methods of Network Solution 297

l,ccn converted directly from percent to ohms at llO-kv. Transformer Differential Protection--h typical es-
The impedance diagram, Fig. 4(c) would then result, the ception is the differential protection of a transformer bank.
fault current being calculated directly for the line and Here the currents on opposite sides of the transformation
are purposely compared and measures must be taken to
rccl,uring a conversion multiplication by z to deter- correct for the shift if the devices used are sensitive to
( * )
mint the current in the generator. phase angle.
use of Percent on a Kva Base-A third method of SequenceVoltagesand Currents-Positive-sequence
an1)roach is to convert the line impedance to percent on voltages and currents are shifted the same as the reference
tL I<V;L base, and “work in percent.” A convenient base or a phase in progressing through a symmetrical trans-
will be 50 000 kvn since two of t,he impedances are already formation. Negative-sequence voltages and currents, if
kno\vn on this base. The line impedance is, from Eq. (12) : present, are shifted the same amount as the reference phase
(!,.‘i5f.j5T.9)(50 000) but in the reverse direction. Zero-sequence voltages and
= (~.o+j2xo)‘;r, on 50 OOO-kvabase. currents are not shifted in progressing through a trans-
(10)(110)2
rlhc impedance diagram Fig. 4(d) results, the percentages formation.
\,c;ing shown as decimal fractions or “per unit” to facilitate Ideal Transformation-The shifts referred to have to
do with the ideal transformer only, deleted of all letkagc
compruation.
impedance and exciting current. That is, they depend only
111this case the current is:
on how many turns of primary and secondary are used
I= 28 = 2.08 per unit or 208 percent of the normal on each core and horn these are grouped to form the phases
current, corresponding to the selected kva on the primary and secondary sides. Symmetry with respect
base. to a, 6, and c phases is assumed.
Regulating Transformers-A symmetrical three-
‘This normal current is: phase bank of regulating transformers may involve both
ratio and phase-angle transformation. Suppose that in
=2000 amp. at 13.8 kv progressing through a particular bank of this type, a
1”=~3(lF80061 110) or 262 amp. at 110 kv phase-angle advance of 10 degrees exists in the reference
‘lhc generator and line currents are, therefore, 208 percent phase. Then, in progressing through the transformer in
of 2000 and 262 or 4350 and 5-E amperes respectively, the same direction, positive-sequence quantities (currents
which agree with the preceding calculations. and voltages) are advanced 10 degrees, negative-sequence
The base selected obviously is immaterial. Had a quantities retarded 10 degrees, and zero-sequence quantities
100 OOO-kvabase been used, the impedances in Fig. 4(d) not shifted at all.
would all be doubled and the resulting percent currents Standard Angular Shifts-The angular shifts of
halved. Rut the normal currents to which these percent- reference phase for various transformer connections are
ages refer would be twice as great, and thus the same given in Chap. 5, Sec. 13. The American Standard* is a
rilimber of amperes would be obtained. 30-degree advance in phase in progressing through either
a star-delta or a delta-star connected transformer from/a
8. Phase Shifts in Transformer Banks lower to a higher voltage. When carried out consistently,
In addition to magnitude transformation, the voltage of this will permit interconnections at various system volt-
1hc reference phase in general undergoes a shift in angular ages without difficulty in phasing. However, at present
position. For balanced conditions, that is, considering practically all possible connections are in use throughout
I)ositivc-sequence quantities only, this is generally of no the industry.
significance. For example, in the problem just worked out,
11~:clrrrcnt in the reference phase of the line may or may 9. Loop Systems That Close
riot, have been in phase with the reference or a phase Transformations of magnitude or angle in a system in-
(‘Itrrent in the generator. If the transformer were delta- volving one or more loops can be treated similarly to a
tk\lta, the currents would have been in-phase; if delta-star radial system provided that:
11~ would have been 30 degrees out-of-phase, using the a. The product of the magnitude transformation ratios
irslial conventions. for the reference phase, taken in a common direction
1Iowever, it should be recognized that an angular trans- around each closed loop is unity.
formation has been made whenever the single-phase circuit b. The sum of the reference phase angular shifts taken
or impedance diagram is used for the calculation of currents in a common direction around each closed loop is zero.
~(1 voltages in a circuit including a star-delta connected
If each transformation ratio is expressed vectorially as
transformer bank. The following statements should aid in
Ntjs, including angular significance in the term “vector
dctcrmining the treatment required in any particular case.
transformation ratio,” then a and b above can be combined
Radial Systems-In radial systems, the angle trans-
into the single requirement:
formation is not usually significant as few phenomena
invo1ve comparisons of the phase angles of line currents c. The product of the vector transformation ratios
On opposite sides of a transformation. Since currents and around each closed loop is lci”.
vo1tagesare shifted alike, power or impedance determina- If the requirements a and b, or c are fulfilled, then the
tion at any one point in the circuit is unaffected by the circuits of the system can be divided into zones separated
ang1etransformation. *ASA Standards C-57.
298 Steady-State Performance of Szfstems Including Methods of Network Solution Chapter 10

I: N,& 1: N2& In Zone 3


A *II+
If’ = I* (14)
a +
c--------‘l r------- - r---------T E,‘=E, (15)
In Zone 2
I

In Zone 1
pIfi\iS = It Iiv3cJea
E (18)
D (0) SINGLE LINE DIAGRAM
d,E je3

The Zone 1 quantities may also be expressed as follows,


illustrating the general met,hod to be followed when the
zone in question is separated from the reference zone by
several transformations.

-----
J L------------m-~: INE 3;
_---
(b) IMPEDANCE DIAGRAM
The power at any point, s, for example, can be cal-
culated without transforming. For:

Pd+jQJ* = E,‘f,’ = $Pe (~~NZE+~“)= E,P, (20)


( >
and
Fig. 5-Ratio and angular transformations. P,+jQ, = E,P. (21)
These are the same. In other words the transformations
from each other by transformations. One zone, usually
described thus far and ordinarily used in analytical work
the one of greatest interest in the particular problem, can
are power invariant. They differ from transformations to
be taken as the reference zone.
a model scale for setting on a network calculator, in which
E~~r@e--For example, in Fig. 5 currents in various
power must obviously be scaled down.
parts of the system are to be determined for a balanced
three-phase fault on the 132-kv line. 10. Loop Systems That Do Not Close
There is one closed loop in which: :
If the product of vector transformation ratios around a
closed loop is not unity, special consideration needs to be :
given. This case will be sub-divided into three parts, viz- /
(a) product of ratios not unity, (b) sum of angular shifts 7
= 1 cl0 not zero, and (c) product of ratios not unity and sum of ;
(13)
angles not zero.
Therefore, the reference-phase impedance diagram can Product of Ratios Not Unity-Many transformers j
be prepared from the single-line diagram without showing are provided with taps in one or more windings. With star i
any transformations. or delta connected windings, use of these taps changes the
Let Zone 3 be taken as the reference zone and all im- ratio only, without affecting the angular shift through the 16
pedances expressed in ohms on 132-kv base. The fault transformer. Thus, by far the largest number of cases of ‘.$
current, It, and the distribution of currents I, and I, are non-unity vector transformation ratio around closed loops :
now readily determined. So also are the voltages through- falls in this category of ratio discrepancy only.
out the network. It is recognized that in Zone 3 these are Example-h example is shown in Fig. 6, in which two
the actual reference phase currents and voltages. In Zones circuits A and I3 differ in capacity, the taps having been
1 and 2 they are the actual quantities transformed to the increased on the B circuit to make it carry more of the load. :
Zone 3 base, and hence, must be transformed to their own The power factor of the portion of load that can be thus
respective bases to obtain the actual quantities. Since they shifted from B to A depends on the impedance phase angles
are all positive-sequence currents and voltages, that is, of the A and B circuits being nearly pure wuttless for pure
normal balanced three-phase quantities, the actual cur- reactive circuits, and pure watts for pure resistive circuits.
rents and voltages of the reference phase, which have been Thus, for 60 degrees impedance angle circuits the shifted
indicated on the single line diagram, are as follows: *SeeSection2.
fJ-&er 10 Sleady-State Performance of Systems Including Methods of Network Solution 299

for example A, unity by transforming the voltages of Zone


1 in the ratio ~8~“0’ and currents and impedances by
t,he corresponding factors. This leaves an uncompensated
or remnant ratio to be accounted for in B, which may be
represented as an autotransformer, Fig. 6(b).
In a-c network calculator studies, small auto-transform-
ers of the remnant ratio are used and no further consider-
ation need be given. For analytic studies the simplest
method is to neglect the remnant transformation mtio,
provided great accuracy is not required. The order of
magnitude of the circulating current can be estimated by
dividing the inserted voltage by the loop impedance to see
(0) SINGLE LINE DIAGRAM
whether it can be neglected in the problem at hand. For
example, if the remnant ratio is 1.05 the inserted voltage is
of the order of 0.05 per unit under normal load conditions.
If the loop impedance is 0.50 per unit the order of magni-
tude of circulating current is ‘g =O.lO per unit.
If this cannot be neglected the following approximation
is suggested in cases where the remnant ratio is close to
i L-- ---+L-cLc-I---L-L+--Ai unity. The accuracy of the method is indicated later by
@iKI---------J L--~ONE& IL.O_N~_~~~~J an example.
132: 138
IDEAL AUTOTRANSFORMER a. Treat as though the ratio were unity and determine
the resulting shunt voltage at the location of the
(bl IMPEDANCE DIAGRAM ON ZONE 2 BASE auto-transformer.
WITH REMNANT TRANSFORMATION INDICATED
b. Determine the resulting series voltage introduced,
138-132 6
in this case = 132 = 4.5 percent of the shunt
132
voltage, and in phase with it.
c. Determine the current circulated in the network by
the action of this series voltage alone, setting the
generator emf, E, equal to zero. Determine the volt-
i 0.9745-jO.O329=$” ,
h=O . B976- jO.0643 J ’ ages for this condition also.
-- d. Superpose this set of circulating currents on the cur-
(C) CIRCUIT CALCULATED WITH SERIES EMF ZERO rents previously calculated. Superpose the voltages
similarly. The resulting solution is in error only by a
correction factor of the second order which usually
can be ignored, as will be shown subsequently.
e. Where several such auto-transformers are required
to “close” the impedance diagram, the circulating
currents can be calculated separately, treating the
ratios of the others as unity at the time. All of the
resulting circulating currents can then be superposed.
The resulting voltages can likewise be superposed.
(d) CIRCUIT CALCULATED WITH SHUNT EMFS ZERO;
SERIES EMF ACTING ALONE. e =0.0443-io.0015 This approximation is based on the concept that the
auto-transformer could be replaced by a shunt load that
Fig. 6-Product of ratios around a closed loop not unity. draws the same current from the system as the main section
of the auto-transformer and a series emf that impresses
load is at about 50 percent power factor. The amount in series the same voltage as the short extension of the
sllifted is nearly constant, and not a percentage of the auto-transformer. With this substitution, the solution by
Md load. Thus, at no load, there is a circulation over superposition is exact. If the auto-transformer introduces
ttlC two lines. five-percent voltage in series and the impedance to the
Suppose that the network of Fig. 6 is to be solved, and resulting circulating current is 50 percent, then ten-percent
it is desired to work on the Zone 2 basis. Zone 3 can be current will flow. With five-percent voltage this amounts
readily transformed to this basis as explained in a preced- to 0.5-percent load, which is supplied from the system to
ing section. However, no transformation can be found for the shunt winding of the auto-transformer, thence, to the
Zone 1 that will result in both transformer ratios being series winding and back into the system, as PX and 12R
“nity. The best that can be done is to make one of them, losses of circulation. As this load drawn by the shunt
300 Steady-State Performance of Systems Including Methods of Network Solution Chapter 10

winding is quite small, O.&percent in the case just cited, series voltage e, and is a good approsimation to the exact
it is most frequently ignored. solution of the circuit of Fig. G(a) and (b) as will be shown
In general, introduction of the series voltage raises the by comparison with Fig. i(b).
voltage on one side of the auto-transformer and lowers it The Exact Solution for the currents and voltages in Fig.
on the other side, as compared with the voltage that would 6(b) can be obtained by writing Kirchoff’s Law for the
be present if the auto-transformer were not there. Thus,
if the series voltage is five percent, the shunt voltage TABLE ~-COMPARISON OF RESULTSBY APPROXIMATEAND
applied to the auto-transformer will differ by not over EXACT METHODSOFSOLUTIONWHEN PRODUCTOF
VECTORTRANSFORMATIONRATIOS IS NOT UNITY.
five percent from that calculated with the auto-transformer (REFER ALSOTO FIG.?').
removed. A correction of five-percent in the shunt voltage
would change the series voltage from five-percent to 4.75
percent. This small correction usually is not required. 70 Diff.
13y Approximate Method By Exact Method
Thus, the steps as outlined from a to d above will usually =- Diff.
be sufficiently accurate. Exact
Vector i Vector Scalar Xl00
Example-A comparison of the esact solution (by +
equations-see Sec. 13) and the approximation in the 0.672-j0.522 0.851 0.686-j0.536 0.870 2.18
case of Fig. 6 will illustrate the procedure and indicate 0.672 - j0.522 0.851 0.670-j0 521 0.849 0.24
the degree of accuracy to be expected. Assume a set of 0.312-j0.188 0.364 0.316-jO.191 0.369 1.36
constants as follows, in per unit on the generator kva base. 0.360-j0.333 0.490 0.371-jo.345 0.507 3.35
0.360-j0.333 0.490 0.355-jo.330 0.485 1.03
Assume the voltage to be maintained constant on the
0.967~jO.036 0.968 0.965-jO.037 0.966 0.21
generator bus. 0.917-jO.066 0.919 IIO.916-jO.067 i 0.918 0.11
A =jO.lO E=l+jO
B =jO.lO drops around each of the three loops and setting up a fourth
c=0.10+j0.173 equation stating that the total ampere-turns on the perfect
D=o.lo+jo.173 transformer are zero.
F=jO.lO IIB -IzB +13(o) 4-E” =E
G = 0.9OSjO.50 (22)
Following the steps suggested above, the series voltage -IlB +Iz(A+B+C+D)-I3D +E”(O.O%) =0
is first set equal to zero and the solution using the generator (23)
voltage alone is obtained, Fig. 6(c). The series voltage is II(O) - IzD +Is(D+F+G) -E”(1.045) =0
4.5 percent of 0.9745-jO.0329 or equal to 0.0443-jO.0015 (24)
and is directed to the right. Then, setting the generator
voltage equal to zero and applying the series voltage alone, I1 fIZ(0.045) --13(1.045) +E”(O) =o
the solution of Fig. 6(d) is obtained. Adding vectorially (25)
the corresponding quantities in these two solutions, the
superposed solution, Fig. 7(a), is obtained for the simul- The .solution of these simultaneous equations with the
taneous application of the generator voltage, E, and the numerical values of the impedances -4 to G substituted,
is given in Fig. 7(b). Table 2 shows the error in various
quantities by the approximate method. The voltages are
within 0.2 percent. The largest current error is 3.35 percent
E=l.O+jO in I,. The sum of errors in I, and Im are about 4.5 percent.
This is necessary since these two currents are taken the
same in the approximate solution and differ by 4.5 percent
Ip=O.359~.3332=1m
+ e OGXZ&b
in the exact solution.
Sum of Angular Shifts Not Zero-Regulating trans-
I’ 0.9667-jO.O360=$” $0.9174-jO.0664 j
formers or regulators as well as special connections of trans-
(a) APPROXIMATE SOLUTION OBTAINED BY SUPERIMPOSING THE formers can introduce angular shift. If the net shift around
RESULTS OF THE SHUNT AND SERIES EMF’S, FIG. 6.(c) ANO (d) a closed loop is not zero but is small, the treatment is
,A c similar to that for ratio discrepancies except that the series
voltage is introduced at right angles to the shunt voltage.
On the a-c network calculator, transformers cannot be
used to obtain a shift since the circuits are single phase. .)
0.355-jO.3308I, Power sources must be used to introduce the necessary
series voltages.
Sum of Angular Shifts Not Zero and Sum Of i
Ratios Not Unity-The series voltage can be introduced ;
(b) EXACT SOLUTION BY SOLUTION OF THE EOUATIONS at any desired angle, corresponding to the net vector trans- : 4
Fig. 7-Comparison of exact and approximate solutions of formation ratio, and the currents superposed as outlined i
Fig. 6. above, with appropriate phase relations.
chapter IO Steady-State Performance of Systems Including Methods of Network Solution, 301

II. NETWORK SOLUTION


11. Network Theorems**
The Superposition Theorem states that each emf
nroduces currents in a linear network* independently of
those produced by any other emf. It follows that the (b)
cmfs and currents of a given frequency can be treated
independently of those of any other frequency, and of
transients. The superposition theorem is a direct result of
the fact that the fundamental simultaneous differential
equations of the network are linear. (See any standard
hook on Differential Equations.) (See Sec. 13.)
The Compensation Theorem states that if the im-
ncdance of a branch of a network be changed by an
amount AZ, the change in current in any branch is the
same as would be produced by a compensating emf -Ml,
acting in series with the modified branch, I being the origi-
,,J current in t,hat branch. By compensating emf is meant
,),i(: which, if it were inserted, would neutralize the drop
through AZ. This theorem follows directly from the Fig. S-Methods of notation used in network solution.
superposition theorem.
The Reciprocal Theorem states that when a source arrow is to represent a rise or a drop. In system calcula-
of electromotive force is connected across one pair of tions it is generally used as the rise in voltage. While
terminals of a passive+ linear network and an ammeter is this decision is arbitrary, once made, it must be adhered
connected across a second pair of terminals,‘then the source to consistently.
of electromotive force and the ammeter can be inter- Finally a vector value must be assigned to the voltage
changed without altering the reading of the ammeter or current. It can be expressed as a complex number, or
(provided neither the source nor receiver has internal in polar form or graphically and gives the magnitude and
impedance). This follows from the fact that in Eq. (56), relative phase of the quantity with respect to some ref-
if all emfs are zero except EZ and Ea for esample, then if erence. A symbol, such as I,, can be used to designate
this vector quantity.
&423 &A,2
Ez=O, Iz=., while if Es = 0, 13= - The known vectorial voltages or currents must be asso-
D ’ ciated with the reference arrows in a manner consistent
so that if E3 = E2, I3 = I, for the conditions of the theorem. with the conditions of the problem. For example, suppose
Kate that A23=A32. the problem in Fig. S(a), is to determine the currents that
would flow with the two voltage sources 180 degrees out
12. Reference Current and Voltage Directions of phase, and 100 volts each, rms, 60-cycle. Then if E,
To specify uniquely a vector current or voltage in a is taken as lOO+jO, E, must be taken as - lOO+jO. Had
circuit, some system must be adopted to label the points the arbitrary reference-direction arrows been taken as in
between which the voltage is being described or the branch Fig. 8(b), then for the same problem a consistent set of
in which the current flows. This system must also indicate voltages would be:
the reference or positive direction. Two common methods
E, = lOO+jO, E, = lOO+jO
~c: the use of reference or positive direction arrows and
tlic double subscript notation. Ordinarily the reference-direction arrows for shunt voltages
ReferenceDirectionArrows-Fig.S(a)and(b)-When are directed from the neutral to the phase conductor as
:L network is to be solved to determine, for example, the in Fig. S(a).
cMcnt flow for a given set of impressed emfs, the network Summarizing then, the complete specification of a
sliould first be marked with arrows to indicate the reference quantity in the reference-direction-arrow system involves
Positive direction of each current and voltage involved. three elements:
‘hse can be drawn arbitrarily, although if the predom-
a. The reference-direction arrow, drawn arbitrarily.
inant directions are known, their use as reference-direction
b. An agreement, consistently followed as to what the
arrows simplifies later interpretation. reference-direction arrow means; particularly whether
The use of open voltage-arrowheads and closed current-
the voltage arrow means the voltage of the point
“Promheads will avoid confusion in numerical work, where
above the tail or the drop from tail to point.
the E and I symbols are not used.
c. A vector to represent the magnitude and relative
It must be decided at this point whether the voltage
phase of the quantity with respect to a reference.
**See~1~0Thevenin’s Theorem, Sec. 18.
*A linear network is one in which eachimpedanceis linear; that is, Suggested convention: For voltages, the vector quantity
hU 5 Straight line relation betweencurrent and voltage drop. shall indicate the voltage of the point of the arrow above
Passive network is onehaving no internal emfs as distinguished the tail, that is, the rise in the direction of the arrow. It
frOrn
+Aan active network. then is also the drop from point to tail.
302 Steady-State Performance of Systems Including Methods of Network Solution

Mesh Currents and Voltages-Refer to Fig. 8(c)- Referring to Fig. S(c).


The “mesh current” system involves a somewhat different E,-I,(Z,+Z)+I,Z=O (32) ;
point of view. Here each current is continuous around a r,z-I,(ZfZ,) -E,=O (33) 1
mesh and several currents may flow in the same branch.
(1T,and I, flow in 2.) The branch current is the vector sum Referring to Fig. 8(d) or 8(e).
of all the mesh currents in the branch, taken in the refer- E,,-I,,Z,-I,,Z=O (34) j
ence direction for the branch current. If such a network It,Z-It,Z,-E,,=O (35)
can be laid out “flat,” it is most convenient to take the I,t-It”-Itr=O
reference direction for mesh currents as simply “clockwise” (36)
for example. Or circular arrows can be used as shown in In the double-subscript system, the voltages and cur-
Fig. 8(c). The example of solution by equations in Sec. 9 rents could of course be indicated on the figure. They have ’
illustrates the use of “mesh currents.” been purposely omitted in Fig. 8(d), however, to emphasize 1
The same reference directions can be conveniently used that the specification of these quantities in Eqs. (34) and I
for mesh emfs, which are the vector sum of all emfs acting (3.5) is perfectly definite from the subscripts alone.
around a particular mesh, taken in the reference direction. Also, the inclusion of reference-direction arrows on the
Double-Subscript Notation-Fig. 8(d)--A double- diagram, even when the double-subscript system is used,
subscript notation is sometimes used and is of course may aid in writing equations, although they are not
equivalent to the drawing of reference arrows. Here again strictly required. If used, they must be consistent with
an arbitrary decision must be made as to what is intended. the double-subscript system. That is, each arrow must
Suggested Convention. Refer to Fig. 8(d). be directed from the second subscript toward the first for
Ist means the current from s to t. voltages, and from the first subscript toward the second
E,, means the voltage of s above n for currents. Fig. 8(e) illustrates such a diagram con-
It is apparent then that E,.= -E,,; Iat= -It,, etc. sistently labeled.
Setting up Equations-If the work is analytical, by
the method of equations, the equations must be set up 13. Solution by Equations
consistent with the reference direction arrows, regardless Representation-A network of n meshes can be
of the values of any known currents or voltages. Consistent represented as having n independent currents, II to I,,
equations for Figs. 8(a), (b), (c), (d), are as follows, using as shown in Fig. 9. The branch currents are combinations
Kirchoff’s Laws (See Sec. 1): The voltage equations are of these. See Branch Currents below.
written on the basis of adding all of the voltage rises in a Mesh Impedances are defined generally as: ZP4= :
clockwise direction around each mesh. The total must of voltage drop in the reference direction in mesh q per unit
course be zero. The current equations are written on the of current in reference direction in mesh p. The curved
basis that the total of all the currents flowing up to a point arrows indicate reference directions in each mesh. In
must equal zero. Arrows and double subscripts have the general
meanings given in the “suggestions” above. =%Q
=zw
Referring to Fig. 8(a).
The impedances Z,, and Z,, are called self and mutu al 4
E,--I,Z,-IZ=O (26) impedances.
-I,Z.-E.+IZ=O (27) Specifically in Fig. 9.
I.-I-I,=0 (28) (First subscripts i and c indicate inductive and capacitil
Referring to Fig. 8(b). reactances respectively.)
E,-I,Z.-IZ=O (29) Zll=R,fRb+j(Xia+Xib-XC8-XCb) (3
-I,Z,+E,+IZ=O (30) ZIZ= -Rb-j(Xib-Xob) (3:
I,-I-I,=0 (31) z13=0 (3’
Ra Xi0 XC0 Rc Xic xc, MAGNETIC
zl-mm-lcr

Xid,Rd

Xie,Re

Rk Xik )&k
(a)
Fig. 9-General flat network.
Chapter 10 Steady-State Performance of Systems Including Methods of Network Solution 303

.&=O (40) The cofactor of a term in a determinant is the minor


Etc. determinant obtained by eliminating the row and column
Z??=fZbfR,+nd+n,+j(Xib+Xi,+Xid-Xob-Xcc) containing that term, this minor being prefixed by a +
- sign depending on whether the sum of column num-
(41)
,!!??n= -jxide (42) E’,r and row number is even or odd respectively. In (57)
the first subscripts define columns, the second rows. Thu;
[The polarity marks signify that the mutual flux links the cofactor of a term has a + sign if the sum of sub-
the two windings in a manner to produce maximum volt- scripts on the term is even. Since Z,, = Z,,, it can be shown
agrs at the same instant at the marked ends of the wind- that A,, = A,,.
ings. See Fig. 9(b).] In (56), the term involving El is the current that flows
ZN= -R, (43) in mesh p if all emfs are set equal to zero except El. Simi-
Zzs = 0, etc. (44) .&A,~
larly, the term --= is the current that flows in mesh p
212= z21 (45) D
213= ZSI etc. if E2 alone acts and El, Es, etc., are equal to zero.
(46) Specifically:
Mesh Em&-Reference-positive directions for branch
cmfs, E,, Eb, etc., are shown by arrows associated there-
(5s)
wit ti.
.\ mesh emf is the sum of the branch emfs acting around where D is given by (57)
t.liat particular mesh in the reference direction. And :
The same reference direction will be used for mesh emfs
as for mesh currents. Azl= $~;: : :;j
Specifically in Fig. 9. (59)
. .
El=E,--E, (47) . .
E2= -EC (48) . .
E2= -E,, (49) ZlnZS, . . . zm
Ed=EdfEfSEo (50) /zlIzsl~ * *Z”Il
Etc. ZlSZS,. * *ZIIS
E,=E, (51) A%=+.. . (6’3)
. .
Equations-Kirchoff’s Law states that the voltage . .
chop around each closed mesh must equal the emf im-
pressed in that mesh. Z&n. . zm

~1z11+~2z21+13231+~ - *+I,Z,1=E1 (52) ZllZal~ . . Z”1


212232. . . zn2
IlZI2 + I2Z*2+ 1&-s,+ . ..+I,Z,2=E2 (53) A23=-.. .- (61)
~IZIS + 12-z,, + 13-G + . *.+I,Z,2=Es (54) . .
. .
.
ZlnZsn. . . Z,, Etc.

I~Z~,+I2Z2,,+13Zzn+. . . +I,Z”, =& (55) Branch Currents can now be obtained by combina-
tion. The vector sum of all mesh currents flowing in a
Mesh Currents*--Equations (52) to (55) can be
branch is the branch current.
solved for the mesh currents II to I,. The solution for
Specifically with reference to Fig. 9.
wrcnt in any particular mesh, p, is:
I,=I1 (62)
I =EI&I &A,2 E,A,,
P --+--+T+...+yP (56) It,=I1--I2 (63)
I,= I2 (‘34)
where D is the determinant of coefficients Im=14-12 (65)
)Z11Z21&1~ . . Z” II Etc.
Z12Z22Z32~ * *zn2
D = Z,,Z,,Z,,. . . Zn3 (57)
Branch Voltages-The branch voltages, E,, E,,,
. . . etc., or the voltages between any two conductively con-
. . . nected points in the network, as E,,, can be obtained by
, . . vectorial addition of all voltages, both emfs and drops
z,,,z?,,z:J”. ’ ‘Z ,111 through any path connecting the two points.
The voltage drop from x to y, Dxy, and the voltage of
and A,,, is the cofactor of Z,,, in the determinant (57).
point x above point y, Exy, are the same.
*‘l’h e method of determinants is used to state the solution here. (Note that drop is measured from first subscript to sec-
IIOwcver, any method of solving the simultaneous equations (52) ond. The voltage of the first subscript is measured above
’ (55) for the unknown currents I, to I. may be used. the second.)
304 Steady-State Performance of Systems Including Methods of Network Solution Chapter I6

D,,=E,.=I,R,+jr,(xi,-X,,) (fm one of these meshes per unit of emf impressed in the other.
D,,=E,,=IdRd+jI,lXid-jl,~~;d, (67) Thus the voltage Ez is -0.1 of El and likewise the current
Dwz=Ew.= -E,fI,,,R,, (68) in mesh 1 resulting from E2 is -0.1 of the current in mesh
2 due to El.
D,,=E,,=I,R,fjl,(Xi,-X,,)fIdRd
SjIdXid -jIeXidc* (@a 14. Solution by Reduction
Note that General-The currents flowing in a network of known
Dxz = Dx, -k&z (70) impedances, caused by a given set of applied emfs, can be
Exz=E,z+Ex,. (71) determined by the method of superposition (See Sec. 11).
Example of Solution by Equations-(a) Given the First the solution (currents in all branches of interest) is
impedances and emfs of a network, Fig. 10, required to obtained considering one emf acting with all, others set
equal to zero. Following the same procedure for each emf
in turn, a number of current solutions are obtained. By
the principle of superposition, the current in any branch,
when all emfs are acting at once, is the sum of currents in
.29+j5.66 VOLTS*Eb
that branch caused by each emf acting independently with
the others set equal to zero. The principle of superpositior
presupposes a linear network. The same reference direc.
tions must be adhered to for all solutions if the super.
position is to be a simple vector addition of the severa’
current solutions.
Fig. lo--Example of a solution by equations. The solving of a network involving several emfs is thur
reduced to the more fundamental problem of solving t
find the currents. Note: The headings (b), (c), etc., refer network with one impressed emf. This can be accomplishec
to the corresponding paragraphs b, c, etc., in which the by the method of reduction.
method and equations are given.
Eo=jlOO Za=j30
(b) Mesh Impedances -0 0
zn=o+j(7.55+136) =o+j143.55
212= ZZl - jl13.0
&=5+j(150.5-2.65) :5+j147.85
(c) Mesh Emfs
El= 2.9 +j56.6
E, = -0.29 -j5.66
(d) Equations. It is unnecessary to write these out
completely since only the solutions are desired. However
for completeness they are:
Ir(o+j143.55) $12( -j113.0) = 2.9+j56.6
Il( -j113.0 )+12(5+j147.85) = -0.29-j5.66 (a)
(e) Mesh Currents
D _ Ofj143.6 -jll3.0
- -j113.0 5fj147.9 = -8400fj718
An&fj147.9
An=&= +j113 h
An = O+j143.6
I /EAl &An
1
D+T-

Eo,
(WITH dEd.0,
=(2.9+j56.6)(5+j147.9)+(-0.29--j5.66)(jl13)
-84OO+j718 -84OO+j718
%ccj
z9 I 100

J2.9+j56.6)(jl13)+(-0.29-j5.6G)(+jl43.G)
e
zeh
h Llllzl Zaa

-84OO+j718
= 0.662fj0.034
-84OOSj718
v
fm Zn
(e)

Note that the term ‘<= $ is the ‘<transfer admit-


Fig. II-Solution by reduction. Bridge network current dl
tance” between meshes 1 and 2, or is the current in either tribution.
chapter 10 Steady-State Performance of Systems Including Methods of Network Solution 305

solution by Reduction consists of replacing portions In all cases, the equivalent circuits are equivalent only
of network, SUC~I as Fig. 11(a), by simplor equivalent sec- insofar as the labeled t,erminals are concerned. For es-
tioI]S, Fig. 11(b, (4 d), until a simple series circuit results, ample, when a star with mutuals is reduced to a star
Fig, I I (e), which includes t,he impressed emf and one im- without mutuals, the potential of the center point is not
pedance branch. The current is readily calculated. Then, the same in the equivalent.
,ising current distribution factors obtained in the course Delta and star forms used in general netlvorks are iden-
,~freductionl a reverse process is carried out, expanding the tical with Pi and T forms used in specialized transmission
nc.twork to its original form and determining the division forms of networks. See Fig. 15. The difference is simply
,)f ,mrents in the process. The methods and equivalent in the manner of drawing the circuit. Thus the star-delta
circuits for carrying out this procedure in general are given and delta-star transformations are at once, T to Pi and
in the subsequent paragraphs. Pi to T transformations. The arrow between parts of the
The’Network Equivalents will first be given. Network figures indicates that the figure on the left is being trans-
c~~nstantscan be expressed ‘either in admittance or im- formed to the figure on the right. It is assumed then that
pedance form. Some transformations are more readily the currents are determined for the figure on the right
performed in impedance form, such as adding impedances and the equations under the figure on the left are for
in series, or delta-to-star transformations. Others are more determining the resulting currents (or voltages) in it.
,:,~nvcniently performed in admittance form, such as ad-
tiing admittances in parallel, or star-to-delta transforma- 15. Transformations in Impedance Form
ti~ns. For more complicated transformations, it is best to a. Impedances in Series (Fig. 13)
ronvert constants to the most convenient form for the
p:nticular transformation. For simpler ones, it is usually Zl
- - -A
preferred to use one form or the other throughout the @lE e2E ‘E
problem. Fig. 13-Impedances in series.
The common transformations are presented in both
forms. The more complicated and unusual ones only in the
form best suited. Impedances (symbol 2) are reciprocals
-- 21 21
e1=Zl+Z2-Z
of admittances (symbol Y) and vice versa.
‘l%at is -- 22 22
““=Zl+Z,-Z
Z,=f (72)
1 b. Impedances in Parallel (Fig. 14)--“The parallel
Y,=i of two impedances is the product divided by the sum.”
(.73)
1

E
0,
CURRENT DIVISION DIAGRAMS
+-$kJ -A
7- 7-2 I-

I -
‘21
Fig. 14-Impedances in parallel.

(0) SIMPLIFIEO CIRCUIT OIAGRAM

b--6&y%-c

“I PARALLEL EXPANSION II (d) DELTA-STAR TRANSFORMATION


Fi& 12-Solution by reduction. Bridge network current dis-
tribution. Fig. 15-Pi and delta; T and stars or Y are the same.
.a
3
4
i:

306 Steady-State Performance of Systems Including Methods of Network Solution Chapter 10 ‘z

Suggested order of calculation (80) I, = I,, - Isb (101) z:rt, = Dz,&

D=&+z* zb = lab - Ibe (102) zbc = I)-%,-%


1, = zbc - I,, (103) Z,, = DZ,Z,
il =% = current in Z, per unit current in 2. (81)
iz= 1 -il =current in Zz per unit current in 2. (82)
(~‘1and ~‘2are current distribution factors.) Alternative forms of the transformation formulas fol-
z = ilZl (83) lows :
c. Delta to Star Transformation or Pi to T (Fig. (104)
16)-“The star impedances are the product of adjacent z =Num. Z,Zb
ah -=Z.+Zb+T (105) J
delta impedances divided by the sum of all delta imped- Z, c
ances.”
(106) 9
b-c “WC (107) 1

IO
e. Star with Mutuals to Star without Mutuals
I
20
(Fig. 18)
- i
a

Fig. 16-Delta to star-impedance form.

(84)

(88b)
Ibc=-+++$I, (89a) zb =‘+ (85)
Fig. Is-Star with mutual5 to star without mutuals-im-
= - iabzbficazc (89b) pedance form.

I c3 036) ZA=Zn+Zbc--Zab-Zca (108)


ZB=Zb+Zen-Zbc-Znb (109)
= -ibcIc+iabz,, (gob) D =Zab+Zbc+Zca (87) &=Z,+Zab-Zen-Zbc (110)
Suggested order of calculation* Polarity marks require that with all reference directions
D=Z,,,+Zb,+Z,, (87) from center outward as shown, all self and mutual drops i
z,b
are from center outward. That is, it is understood that i
jab = - (91) with the polarity marks as shown, the voltage drop from
n
the center to a will be written:
z, = z&b (92)
D,, = I,Z,+IbZab+IeZea 4
(93)
and the numerical (vector) values and signs assigned to S
(94) z&b and Z,, must be such as to make this true. It follows :
that Zab is defined as the voltage drop from n to a divided 4
(95)
by the current from n to b that causes the drop.
z, = Z,& (96) Special case: Star with one mutual between two branches
(&, ii,,, i,;, are current distribution factors.) to star without mutual. (Fig. 19.)
d. Star to Delta Transformation or T to Pi(Fig. 17)

bye _ b&IiI?t$c
6 d
a a
Fig. 19-Star with one mutual to star without mutual-
impedance form.
Fig. 17-Star to delta-impedance form. z, = z, i-Zbc

*Then after I., Ih, and I, have been found, I,., Iab, and I~o can be &,= Z,,-Zbo
determined using Eqs. (Sb), (89b), and (gob). &=z, -z,,c
Chapter 10 Stea&State Performance of Systems Including Methods of Network Solution 307

f. Two Self Impedances and a Mutual Trans-


formed to an Equivalent Star or T. Or the Equiv-
alent Circuit of a Two-winding Transformer (Fig.
20)
i21
o-3 fC 0-c Fig. 22-Admittances in parallel.

c. General Star to Mesh Transformation, or


“Elimination of a Junction” (Fig. 23)
3

Fig. 20-Two
an equivalent
self impedances and a mutual
star or T. Or the equivalent
winding transformer.
transformed
circuit
to
of a two
2
\ 1 I2

y2
y3
13

---\

ZI = ZII - z12 (114)


z, = 222- zn (115)
NOTE: This transformation involves bringing b and d to the
s:ln~cpotential and is permissible only when these potentials are
riot otherwise fixed. Strictly, the form on the right is equivalent
to that on the left with switch S closed. However, if the closure
9 n
of S would not alter the current division, it can be considered Fig. 23-General star to mesh transformation, or elimination
of a junction-admittance form.
c,losedand the equivalent circuit used. The resulting potentials
fi:,,,,,and Eed will be correct but the potentials EC. and Edb, which
are definite in the equivalent, are actually indeterminate in the NOTE: A network can be solved by eliminating one junction
original circuit and must not be construed as applying there. point after another until a single-branch mesh remains.
SW note under e for meaning of polarity marks, considering b RULE : “A mesh branch is the product of adjacent star
anti rl as point n. branches divided by the sum of all star branches.”
The mesh contains n/2 (n - 1) branches, where n is the number
This is the familiar equivalent circuit of a two-minding of star branches.
t,ransformer, provided all impedances have first been
placed on a common turns basis. In this case 212 is the 11=z21+131+“‘+~n1 (130) y,,=y w3
exciting impedance and Z = Zl+Zz the leakage impedance.

16. Transformations in Admittance Form 12=1112+132+. . . +znz (131) Y,,2g (127)


a. Admittances in Series (Fig. 21) etc. etc.

^a YI y2 a Y,,,Jg
c ^ zp = zI,+zz,+~ . . +I,, (132) (125)
- - -
el EC0 eeEca Eta
f D=Y1+Yz+Ys+...+Yn (120)
Eta
Fig. Zl-Admittances in series. In which the positive reference direction for any mesh
current I,, is toward terminal q.
YZ y= YlY2 Suggested order of calculation.
“‘=ylf-
(117)
y1+ yz
(W
D=Y,+Y,+Y,+ .-. +Yn (133) ;=lcz (137)
YI
C2=Ylf2 (118)
(134) Y2,+Lk2Ya (138)
Suggested order of calculation.
D= Yl+Yz (119) y12~5$ly* (135) Y?4=y=k2Y4 (139)
Y2
e1= - (120)
D
Y,,=y=k,Y, (136) etc.
ea=l-el (121)
Y= YIel, or Y2e2 (122) etc.

b. Admittances in Parallel (Fig. 22) d. Star to Delta or T to Pi(Specia1 case of c) (Fig. 24)
j,A5--=K! (124) Y= YI+Y2 (123) I, = I,, - Z,b (144) (l-10)
y1+y2 Y
Y* Yz Y,,=5$
+=~lf~=~ (125) zb = z,b - 1, (145) (141)
308 Steady-State Performance of Systems Including Methods of Network Solution Chapter 10
4
Particular attention is directed to certain relationships, 4
b
The total current input resulting from a particular ap- i
plied emf is obtained by dividing it by the driving-point j
impedance* at that pair of terminals. Thus, when the ‘:
driving-point impedances, Z,, and Zdd, at the impressed 4
voltage terminals have been determined, and the unit i
current divisions developed, the network is solved. This
is illustrated by Cases 1 and 2, which differ only in magni. t
tude of the applied voltages. The resulting currents in I’
Fig. al-Star to delta-admittance form. these two cases are obtained from the same basic network
solution.
(1-E) y,,= !c$ (142)
I, = Ibc - I,, Solution- a. Eliminate the mutual as per Eqs. (lll-
113) and combine impedances in series forming 2,.
D=Y,+Y,,+Yc 113)
Suggested order of calculation same as for general z-h =j20 -jlO =jlO
transformation. (c) Zk = j30 -j10 =j20
2, =j1o+j30 =j40
e. Delta to Star Transformation, or Pi to T (Fig. 25)
b. Let Ed =0 and replace star Z,, Zd, Zh by its equiva-
Ibc b lent delta from Eqs. (97-100).
c
D =.$+-$& = -j(O.O5+0.20+0.10) = -j0.35
ieh =( -jO.35) (j20) (jl0) =j70
Z& = (-jO.35) (j20) (j 5) =j35
Zdh = (-jO.35) (j 5) (jl0) =j17.5
c. Parallel the branches Zde and Zr also, .Zdh and ZI, of
Fig. 2%Delta to star-admittance form. Fig. 11(c), obtaining Fig. 11(d).
D = Zrf Zd, =j45
I& = -i,,I,+i,Jb (151) Y,= DY,,Y,,, (147)
&fQ??,, 78
IbC= -in,Jtn+icaIo (152) YL,= D yab ytx (148) D .i45 ’
I,,= -ibcro+in,,In (153) Y, = D ybc ye, (149) ide= l-O.% = 0.22 (in Z,,)
1 Zm=0.22Xj35=j7.77
where i&b= __ (154) D=&+&++- (150) (Parallel Zdh and Z,)
DY,b nb CB
D=Zk+Zdh=j20+jl7.5=j37.5
1
ibo=L)Ybc (155) Zdh j17.5
&&Z--E--- = 0.468
D j37.5
1 &h=l-z&=0.532 (in Zdh)
(156)
2c”=DYcn Z,=O.532Xj17.5=j9.333
17. Examples of Solution by Reduction d. Zm+Z,=Zm,=j17.10
A power-distribution system network is solved by the Parallel Z,, with Z,h = Z,
method of reduction in Sec. 20. D=Z,,+Z,~=j17.10+j70=j87.10
The following example is also given showing the method z j17.10
when two sources of emf are present. ieh=F=j87.10 ----=0.196 (through Z&)
Solve for the currents in the network of Fig. 11(a) by
i,, = 1 -i& = 0.804 (through Z,,)
the method of reduction for applied voltages as follows: Z0=i,,Z,,=0.804Xj17.10=j13.74
Case 1. E,= O+jlOO volts ,/
.a.
Ed = 50fjO volts e. The impedance viewed from E, terminals is: *,:
Case 2. E, = 30 +j40 volts Z,,= Z0+Z,=j13.74+j40 = j53.74
Ed = 10 fj60 volts
f. Current Division for unit current in at (a).
Obtain unit current division and total current division
as indicated in Tables 4(a) and 5. The symbol (i) has been used for current division
The method generally is to resolve the network for one factors.
applied voltage at a time, with the other one set equal Let prime symbols be used for the currents in terms of
to zero. one ampere total input to the network.
-4fter solutions have been obtained for each applied *Driving-point irnpedauce is that impedtince measuredlook&
voltage acting independently, these solutions are super- into any pair of terminals of a passive network with all other ter-
posed to obtain the current flow with both applied volt- minals terminated in a specified manner. In this case all other
ages acting simultaneously. terminals are short-circuited.
chapter 10 Steady-State Performance of Systems Including Methods of Network Solution 309

i,‘=l.O=ia’ In a similar manner, for Voltage applied at (d), the


i’&=ieh=0.196 driving-point impedance Zdd and the current division and
‘I
z mn = 0.so-k transfer admittances can be obtained. These are given in
i'k =itmnik =0.504X0.468 =0.375= i,’ Tables 3 and 4. It is essential that the same reference
i’dh=i’mniclh=0.804X0.532=0.429 directions be maintained for all current divisions, in order
if’=ilmnif =O.SO4XO.78=0.625 that the solutions for applied voltages at different terminals
ildc=i'mnidc=0.sO-lX0.22=0.179 can be superposed.
i,‘=O.196+0.179=0.375 The current divisions of Table 5 for the conditions in-
i~'=O.ll)fj+O.420=0.625=i~' dicated in the second and third columns are obtained
&'=0.429-0.179=0.250 directly from the basic network solution Tables 3 and 4.
The six currents i,‘, i,‘, if’, id, id’, it,’ are given in Table For example with E, = O+jlOO,
,~(a) and constitute the current division corresponding to
tinit current entering the network at a. Figs. 12(a) to Cc) z&a pd. 14
illustrate the steps in dividing the current. (or 1,=&Y,,= --j0.01861(j100) = 1.861)
g, Transfer admittances. See Table 4(b).
Multiplying by the unit current division correspond-
y,,=L ___l = -jO.OlSSl ing to current in at a, the currents I, to If, for 1.861 am-
z:,, j53.74 peres in at a, are determined.
Y&h= it,’ Y,, = jO.01163 This method is particularly advantageous when many
Y,,=i,‘Y,,= jO.00698 different combinations of applied voltages are to be applied
etc. to the same network. It is also convenient to obtain the
Note: The transfer admittance, Y3b, is the current in transfer admittances, as shown in Table 4(b). These are
branch (b) in the reference direction per unit the currents in the various branches corresponding to unit
voltage impressed in branch (a) in the reference voltages applied at the respective driving points. It is
direction. necessary only to multiply by any actual single applied
voltage to obtain the corresponding current division. There
TABLE 3
is a check here, for the reciprocal theorem states that the
current at (d) for unit voltage applied at (a) must be the
Viewed From Impedance
same as the current at (a) for unit voltage applied at (d).
ES z,, =j53.74
Ed I Zd* =jl9.54 18. Solution by Thevenin’s Theorem
Thevenin’s Theorem2 is useful in analyzing a net-
TABLE 4(a) xvork or part of a network when its reactions at a particular
pair of terminals are of prime importance. Through its
Unit Unit Current Division
use, a complicated network consisting of several emfs and
current
in at a h C d e f
impedances can be replaced by a simple series circuit of one
~___--_______ emf and one impedance supplying the pair of terminals of
a 1.0 0.625 0.375 0.250 0.375 0.625 interest. The theorem can be stated as follows:
tl 0.001 0.545 -0.455 1.00 -0.455 0.545 With respect to any single external circuit connected to any

TABLE 4(b)-TRANSFER ADMITTANCES (See note under g)

Current Division (Amperes)


Unit Voltage at

a -j0.01861 / -joboll / -jO.i0698 / -.jO.“,465 1 -.jO.~O698 -1 -,‘,,,63


d / -jO.O0466 ) -jO.O2790 ) +jO.O2328 / ->O. 05118 ) +jO.O2328 1 ->O ‘02790

TABLE 5.

Condition Current Division (Amperes)


Case
E. Ed I. Ib I, Id I. Ii
W-P
1 o+j100 0 1.861* 1.163 0.698 0.465 0.698 1.163
0 50 +jo -jO ,233 -jl .395 +jl.164 -j2.559 * +jl. 164 -jl.395
_ O+jlOO
~____~ 5O-tjO 1.861-j0.233 1.163 - jl .395 0.698+j1.164 0.465 - j2.559 0.698+jl. 164 1.163 -jl ,395-.
‘2 3iGjzT.r 0 746-jO.5.59* 0.466-j0.349 0.280-jO.210 O.lSS-jO.139 o.aso-jo.210 0.466-j0.349
0 10 i-j60 0.280-jO.047 1.674-j0.279 -1.397fjO.233 3.071-jO.512* -1.397fjO.233 1.674-j0.279
30 +j40 10 +j60 I ,026 - jO.605 2.140-j0.628 -1.117+jO.O23 3.257-j0.651 -1.117+jO.O23 2.140 -jO. 628
*Total current for which the distribution is shown in that horizontal line.
310 Steady-State Performance of Systems In&ding Methods of Network Solution Chapter 10

given pair of terminals of a network, the network can be the circuit of Fig. 26(a), so far as the terminals 2, y are
replaced by a single branch having an impedance, Z, equal concerned. E, is as measured with the terminals X, 1) open
to the impedance measured at these terminals looking into circuited in Fig. 26(b). 2 is as measured in Fig. 26(c) by
the network (when all the network emfs are made zero) and applying any voltage E’ of the frequency under consider-
containing a single emf, E,, equal to the open-circuit voltage ation to z, y and measuring the corresponding vector cur-
of the network across the given pair of terminals. rent I’ wi-viththe emfs El, EP and Es short circuited. Z is
The term emf as used here has a broader meaning than the vector quotient P/I’.
electromotive force. It is any voltage in the network that An Example of the use of this theorem is found in the
remains constant while the impedance connected to t,he calculation of short-circuit current on a loaded system.
output terminals is varied. Thus, the voltage of a battery The equivalent circuit of the system, up to the point of
of negligible internal impedance is an emf, while the voltage fault, consists of an emf, E,, and an impedance, 2. E,
drop in an impedance is not, unless the current is held is the voltage at the point of fault before the fault and is
constant. (See later paragraph). A generator having regu- usually a known system operating voltage. Z is the im-
lation is segregated into an emf and an internal impedance, pedance looking into the system at, the point of fault with
back of which the voltage is constant for the particular all emfs set equal to zero. The short-circuit current is then:
problem and hence can he treated as an emf.
I = $. Thus, it is unnecessary to determine the generator
The General Case is illustrat,ed by Fig. 26. The emfs,
El, E,, and EJ can be of any single frequency. If more internal voltages. At a given operating voltage E,, and
than one frequency is present, the emfs of each frequency fixed generating capacity, increased load tends to increase
must be treated separately, as the equivalent circuit will short-circuit current by lowering 2, the driving-point im-
not usually be the same for different frequencies. The pedance at the fault with all system emfs set equal to zero.
impedances may be composed of resistances, inductances The method applies equally well to a network in which
and capacitances, but must be linear within the accuracy certain fixed currents are forced to flow, as by current
necessary for the problem at hand. A linear impedance is transformers. Examination of the equations of a network
one that satisfies Ohm’s Lam, E = 12, 2 being a constant. having fixed current input reveals its identity with a net,-
With these considerations as a basis, Thevenin’s The- work of fised emfs. For esample, consider the circuit of
orem states that the circuit of Fig. 26(d) is equivalent to

(a) NETWORK WITH LOAD DRAWN


FROM TERMINALS x,y.

(a)

(bl EOUIVALENT EMF DETERMI-


NATION, SAME NETWORK AND
EMF’S, NO CURRENT DRAWN
FROM TERMINALS x,y

(b)

(0) (b)
Fig. 27-Application of Thevenin’s Theorem in a network of
fixed input currents.
(c) NETWORK IMPEDANCE
MEASUREMENT OR CALCULATION
Fig. 27(a). The equations that involve the known input
currents are:
-r,.4-r,(A+c+D)+I,C+~,D=O (157)
+I,B-I,(B+E+C)+I,C+I,,,E=O (1.58)
The equations involving E, and E, in Fig. 27(b) are:
Eo E (d) EOUIVALENT NETWORK
0 IL-I,,(.l+c+n)+I”c+r,n=o
Y (159)
(d)
+I&-I”(B+E+C)+I,C+I,“E=O (IGO)
Fig. 26-Determination of equivalent network by means of
Thevenin’s Theorem. Equations for the remainder of the network are the same
Chapter 10 Steady-State Performance of Systems In&ding Methods of Network Solution 311

for Fig. 27(a) or (b). Tt is apparent, that (157) and (158) he calculated. The current Z!, is obtained by subtracting
LLr(:identical \vith (1.59) and (160) respectively, if: the load at 5 from I,, and then the drop from 5 t,o 6 can
be computed. Knowing the drops from 2 to 3 and 2 to 6,
E, = - I,A (161)
for the assumed current division, the drop from 3 to 6 is
E, = - I,R (162) obtained by subtraction. This drop divided by the imped-
ln other words, the terms - I,‘4 and -I$ can be treated ancef gives the current Ir. Now the balance of the currents
:,s cmfs in applying Thevenin’s Theorem, and the per- can be obtained, that is, Id and Zk. However unless a
f~)rmnnce at terminals 2, y treated through the use of perfect guess has been made, the drop 3-4-7 will differ
oljcn-circuit voltage and driving-point impedance. The from the drop 3-6-7, and an arbitrary voltage, AE, must be
l:tttor is obt,ained with the input-current terminals, that included to make the voltages around the loop add to Zero.
is, the a, b, and c leads from the current transformers, So far an esact solution has been obtained for the case of
ol)cn circuited in Fig. 27(a), or the equivalent emfs, E, certain load currents, a particular generator voltage and
:& Et,, of Fig. 27(h) set equal to zero. a voltage AE. However, the solution is desired without
:I more complete discussion is given in Reference AE. To obtain it a solution is next obtained for -AE
I\‘umber 2. acting alone. According to the conditions of the problem
the load and generator currents are fixed so that these
19. Solution by Circulating Currents branches are considered open circuited when computing
A ladder-type network common where transmission and the currents caused by -AE alone. This solution is there-
distribution circuits parallel each other as in a-c railway fore quite simple and gives rise to a set of currents I,‘.
clcctrification3 is represented in Fig. 28. The example is, Id’, . . . Ik’, which are the “circulating currents” for which
15,000 KVA
the method is named.
4/O COPPER 4 FT. EOUIV. SPACING
Now let these two solutions be superposed; that is:
I,“=I,fl,
Ii’ = Id+ Id’ etc.
The resulting solution does not involve AE since the AE
of the first solution is canceled by the -AE of the second
solution. It is therefore an exact solution for the load
currents assumed. The voltage drops from the generator
to the several load points can now be computed, since the
currents are known. Also, from the new load voltages, and
LOAD KVA 5000 6000 2000 from the load currents that have been held fixed through-
POWER FACTOR (LAGGING) 60% 80% SO% out the solution, new load kvas and power factors can
Fig. 28-A general ladder-type network. be computed.
The net result is an exact solution for a set of conditions
however, for a three-phase system. Suppose it is desired that differs more or less from those originally assumed.
to determine the current division and regulation for the While this can be used as a basis for asecondapproximation
particular loading condition shown, without making a gen- it is more generally considered the engineering answer.
cral solution of the network. This problem lends itself to The loads are usually not known exactly; the solution
the method of circulating currents. obtained provides an exact reference point in the region
The voltages at the load buses must first be assumed of the loads assumed, and thereby provides a tangible
and the kva loads converted to currents. The sum of the basis for engineering judgment.
three load currents How in the generator and constitute There is much to be said for this type of solution as a
111~current I, in Fig. 29. These load currents and the system design tool, since it capitalizes experience and fore-
generator current are assumed to be fixed for the balance knowledge of the order of magnitude of the answer. As
of the problem. an example the network of Fig. 28 has been solved for the
The division of I, between I, and I, is next assumed. loads indicated thereon.
HOW the voltage drops from 1 to 2, 2 to 5 and 2 to 3 can Example of Method of Circulating Current-The
i0.635 0.53+il.l76 network diagram, Fig. 29, is obtained from the single-line
diagram as outlined in Sets. 2 and 3. The 15 OOO-kva
transformer impedance should be converted to ohms on a
34.5-kv base and then multiplied by ( 13.8/33)2 to convert
to the 13.8-kv base at the load. The resulting diagram
is on the load-voltage base, a conversion being necessary
to change to or from the generator-voltage base, which is
also nominally 13.8 kv. Thus with the generator at 13.8
kv, the corresponding voltage to be applied in Fig. 29 is
LOAD KVA 5000 6000 2000
13.8(34.5/13.8) (13.8/33) = 14.42 kv or 4.5 percent above
POWER FACTOR (LAGGING) 60% 80% 80 x normal. In an actual case transformer resistances should
Fig. 29-Impedance diagram for the system of Fig. 28. Show- be included as these are significant in regulation and
ing the method of circulating currents. loss calculations.
312 Steady-State Performance of Systems Including Methods of Network Sol&on Chapter 10

As a first approximation, assume the regulation in step- Find the impedance as viewed from AE with load and
up and step-down transformers to total 10 percent with an generator branches taken as constant current branches,
additional 10 percent in lines. Allowing for a 4.5 percent i.e., open circuited for this calculation. Apply a voltage
above normal voltage at the generator, the loads should be AE’=negative of the AE required to close the mesh in the
converted to currents based on approximately 85 percent above calculation.
voltage or 11 700 volts. The load currents are given in the 2, = 0.53 +j 1.176
following tabulation. Z" = +.i 1.91
Location...................... 5 6 7 Total Zh = 3.03 +j 6.37
Load kva. .. . 5000 6000 2000
Load Current Amps.. 245 295 98 638
743256 = 3.56 +j 9.456
Zf = +j 1.91
In the current distribution calculation which follows, the D = 3.56 +j11.366
current I, must be guessed, or taken arbitrarily. Later 1/D = 0.0251 -j 0.0801
a circulating current is determined, which, added to the Zf = +j 1.91
arbitrarily assumed value, gives the correct current. It
is advantageous to guess as close as possible so that the
Z,,‘D = z&,~ = O.l53O+j 0.0479
ic=l-inqnn = 0.8470-j 0.0479
correcting circulating current is small. In fact if the guess =
is sufficiently close, the labor of calculating the distribution Zf +j 1.91
of circulating current can be saved. z par = O.O915+j 1.618
zd = 0.53 +j 3.086
I* = 638 Zk = 3.03 +j 6.37
1, = 300 =
z 3.6515fj11.074
I,=I,-I, = 338 0.0269 -j 0.0814
l/Z
I6 = 245 -AE=AE’: 8.0 - j579.8
Ih=Ie-16 = 55 IL = AE’/Z = -46.98 - j16.25
I, = 338 Id'= -Ik' = 46.98 +jlG.25 1
zc = 0.53 +j1.176 LWJ = O.l53O+j 0.0479
I,Z, = 179 +j397 I,' 6.41 +j 4.74
I, = 300 I:=+1,‘: -40.57 -jll.51
z = +j1.91 I,‘= -I,’ = - 6.41 -j 4.7-1
1e.G = +j573 -II)’= -I,’ = - 6.41 -j 4.74
Ill = 55 The currents from the arbitrary distribution (requiring
Zh = 3.03+j6.37 AE to close) and the circulating currents contributed by
IhZh = 166.5 +j350 AE'= - AE, are now combined to get the actual current di-
I,Z, = +j573 vision for the load currents assumed. The circulating cur-
D 266 rents are distinguished by prime symbols, the total division
= 166.5 +j923
by double-primes. Fig. 30 illustrates this superposition.
I,Z, = 179 fj397
Ial’ = I, = 638 +jO
IfZf = - 13.5 fj526
Zf = +j1.91 I, = 300 +jO
If = 275 +j7.1 1, = - 6.4 -j4.7
I, = 338 I,” = 293.6 -j4.7
Id=/,-If = 63 -j7.1 I, = 338 +jO
Ih = 55 IO = 6.4 +j4.7
If = 275 +j7.1 I,” = 314.4 +j4.7
Ih+If = 330 +j7.1 Ih = 55 +jO
16 = 295 Ill' = - 6.4 -j4.7
= 35 +j7.1 It = 48.6 -j4.7
Ik Ih
Zd = 0.53+j3.086 If = 275 +j 7.1
Id = 63 -j7.1 If' = - 40.6 -j11.5
IdZd = 55.3 +j190.7 If” = 234.4 -j 4.4

zk = 3.03+j6.37 Id = 63 -j 7.1
Ik 35= +j7.1 Id’ = 47.0
fj16.3
IkZk '. 60.8
= +j244.5 Id" = 110.0+j 9.2
IfZf = - 13.5 fj526 Ik = 35 +j 7.1
D 367 47.3 +j770.5 Ik’ = - 47.0
-j16.3
031,= IdZd 1 55.3 +j190.7 I," =- 12 -j 9.2
AE = - 8.0 +j579.8 Check of Drops Around Loops. This solution can be
Solution for Circulating Current. checked by checking voltage drops ground each loop.
chapter 10 Steady-State Performance of Systems Including Methods of Network Solution

33a+jo 63-j7.1
2 - 3
c-

h- + k-
245+jO 295+jO 96tjo
to) ARBITRARY DIVISION AND VOLTAGE AE REQUIRED TO CLOSE

KV L-N
Fig. Il-Graphical determination of the load voltage E6 in
(b) CURRENTS DUE TO 4E'.-AE
Fig. 28.
1. The load current Ia is along the reference line.
2. Draw circle of radius 8330 volts on which Eg must terminate.
3. Draw construction line at the load power factor (80 percent)
along which ES must lie.
4. Construct the voltage drop vector, Dr25, and move it parallel
to itself, with one end following the generator voltage circle,
until the other end falls on the load voltage construction line.
5. E. and Es can then be drawn in and their vector values scaled
1 -ii--~-K-1 Off.
LOAD CURRENT 245+jO 295+jO 98+jO
LOAD VOLTAGE 12,022 11,473 11,547 it?, = - 1307.4 + 8248
REG. BELOW 13,800 V. 12.82% 16.66% 16.32% =6941 volts L-N
KW + j REACTIVE KVA 408I-j306l 4757-j3424 l574-jll68
LOAD KVA 5101 5861 1960 = 12 022 volts L-L
POWER FACTOR (LAG.) 80.0% 81.2% 80.3% =87.12 percent of 13 800
(c) SUPERPOSITION. OF (al AND (b) =83.33 percent of 14 427
Fig. 30-Solution of the network of Fig. 28 by the method of Es=6941X(0.8+j0.6)
circulating currents. Es = 5553+j4165
Calculate the drop from generafor bus to load point 5. Check of Voltage Drop from 1 to 5.
I, = 638.0 +jO Eb= 5553+j4165
7 = 0.53+j1.811 Dlzs= 347+j1716
;,“z, = 338.1 fj1155.4 E,= 59OO+j5881
I,“.& = 9.0 +j560.8 = 8330.4 L-N
D 126 = 347.1 +j1716.2 14428 L-L
Regulation-Determination of Load Voltages. The The remaining load voltages are readily determined as
magnitude of the generator voltage is known, but not its follows :
nhase position. The phase position of the load voltage Eg = 5553 +j4165
ES is known but not its magnitude. It is at an SO-percent IhSZh = 177.2 +j295.3
power factor position with respect to IS. The drop from Es = 5375.8 +j3869.7
generator to load point 5, DIz6, is known vectorially with = 6624 L-N
1s as reference. Thus the magnitude, Eb, can be deter- = 11 473 L-L
mined by the solution of a quadratic equation as shown = 83.14% of 13 800
below, or graphically as indicated in Fig. 31. 79.52yo of 14 427
E6=E6(0.8+j0.6) Es = 5375.8 +j3869.7
~%+D,zb=& Il&PZk = 22.2 -j 104.3
ET = 5353.6 +j3974.0
= 6667 L-N
= 11 547 L-L
= 83.68yo of 13 800
= 80.04yo of 14 427
314 Steady-State Performance of Systems Including Methods of Network Solution Chapter 10

Load Power Calculations. 30. This scheme is used most commonly in expressing
current distributions. The solution can also be expressed
E, =( 5.553 +j4.165)kv
as a tabulation of self and mutual drops and cllrrent divi-
31, = 735 -jO ^__-.-
sion, or in the form of driving point and transfer imped-
P5+jQ5= (4081 +j3061)kva ances or admittances. General circuit constants such as
= 5101 kvs the ABCD constants or Pi and T equivalents can also be
at 80.00 percent power factor lagging. used to express the solution of certain types of networks.
E6 = (3.375 fj3.8G9)kv The following paragraphs describe these several methods
316 = 885 -jO of representing solutions and their uses.
PG+jQe = (4757 +j3424)kva 20. Method of Self and Mutual Drops
= 5861 kva
at 81.16 percent power factor lagging. The method of self and mutual drops constitutes one
of the most useful means for fully describing the action
Ei =( 5.354 fj3.974)kv of a complicated network in the form of a table of system
37, = 294 -jO constants. It is applicable principally to single-source sys-
PT+$&= (1574 +jllGS)kva terns or to systems in which all of the generator voltages
= 1960 kva can be taken equal and in phase. However, its use can be
at 80.31 percent power factor lagging. extended to multiple-source systems provided that either:
a. All sources but one are treated as negative loads,
Generator Output Power. b. The emfs of the several sources are fixed in magnitude
= ( 5.900 +$.SSl)kv and phase position with respect to each other.
E$ The method will be described with respect to the single-
31, = 1914 -jO
source system, and the multiple-source system treated as
P,+jQ,= (11293 fjll256)kva an extension.
= 15 945 kva ASingle-Source System Without Shunt Branches
at 70.82 percent power factor lagging. other than the loads, is shown in Fig. 32(a). Each of the
loads draws current through the network causing voltage
Loss Calculation.
drop from the generator bus g to the bus on which it is
Pb+jQs= 4081 4j3061 connected. Each load likewise causes voltage drops to the
Ps+jQs= 4757 +j3424 other loads, known as mutual drops. As these drops are
P,+jQ,= 1574 -t-j1168 proportional to the load current, they can be determined
Total of TAoads= 10 412+.?7653 by finding first the drop resulting from unit load and mul-
P,+jQ,= 11 293fj’ll 256 tiplying by the value of load. Accordingly, the following
Losses = 881 +-i3603 definitions will be found of use.
Kw Line 1Joss=881/11 293 Z,, is the voltage drop from g to a caused by unit load
= 7.80 percent of generator current drawn from the network at a. It is called the self /
output. drop constant.
Z,b is the voltage drop from g to b caused by unit load
Tn an actual case transformer resistances must be in- current drawn from the network at a. It is called the
cluded in the diagram as these are significant in regulation mutual drop constant.
and loss calculations. Transformer iron losses must be NOTE that the self and mutual drop constants Z,, and Z.b as
added to the copper losscts thus determined to obtain the defined and used here in Sect. 20, differ from the self and mutual
total loss. impedancesdefined and used in Sections 13 nnd 21. The 2 with
The solution given in Fig. 30 is exact for the conditions double subscript is used in each case to conform with accepted
shown on the figure, which differ slightly from the original terminology.
assumptions of Fig. 28. However, the total load is off In both cases current is admitted at g and the unit load
only 1.3 percent and the regulation values therefore apply referred to is the only load. Obviously, the self and mutual
closely for the original conditions. In a practical problem drops have the dimensions of impedance but the term drop
it is not significant that the answer does not apply exactly will be retained to distinguish from the terms self and
to the original load assumptions. If the work is done with mutual impedance that are used otherwise. For unit loads
a calculating machine so that several significant figures at other points the self and mutual drops are similarly
can be carried, losses can be computed as the difference defined. Thus associated with the network of Fig. 32(a)
between input and output power, as shown. are the nine drops:

III. REPRESENTATION OF NETWORK


SOLUTIONS AND THEIR USE IN SYSTEM
PROBLEMS
The first subscript denotes the point at which unit cur-
Network solutions can be represented in a variety of rent is drawn; the second denotes the point to which the
ways. For example a diagram can be labeled with all drop is measured. However, in all cases mutual drops
pertinent information obtained in the solution as in Fig. between the same two points are equal. That is:
Chapter 10 Steady-State Performance of Systems Including Methods of Network Solution

Q1

-IaZac -Zac
$+i$

c 7 (d) LOAD AT a ONLY. (g) UNIT CURRENT DRAWN AT a.


(a) SINGLE l?NE DIAGRAM.

-Ibzbc -zbc

(b) IMPEDANCE DIAGRAM WITH (a) LOAD AT b ONLY. (h) UNIT CURRENT DRAWN AT b.
LOADS Ia,Ib,Ic.

(c) NO LOAD CONDITION. (f) LOAD AT c ONLY. (i) UNIT CURRENT DRAWN AT c.
Fig. 32-A single-source system without shunt branches. Illustrating the method of self and mutual drops.

TABLE 6--CURRENT DIVISION

(‘nit Land Current

at
ZGA ZCD ICC IDC ICA ZCB ZAL3
-
.A 0.6e7-j0.013 0.197-jo.003 0.136+jo.o16 0.197~j0.003 0.243-jO.003 0.09O+,jO.O16 -0.090-jO.016
- 13 0.556-j0.021 0.264-jO.002 O.lSl+jO.O23 0.264-jO.002 -0.04O+jO.O17 0.481 +jO.O04 0.516-30.004
c 0.445-jo.029 0.329-jO.000 0.226fjO.020 0.329-jO.000 -0.323fjO.037 -0.122-jO.008 0.122+jO.O08
D ,- O.OSO+jO.O05 0.911-jO.013 0.029-fjO.008 -O.OSg-jO.013 -0.044-jO.001 -0.016-jO.004 0.016+j0.004

z&b = Zba 063) The resulting tabulations of current division and self
z,,=zcs (164) and mutual drops, as illustrated in Tables 6 and 7 for the
zbc = Zob (16.5) network of Fig. 33, are the basic network solution. They
The drops can be calculated or measured on a network TABLE 7
c:&lator. Unit, current, is drawn from one of the points Self and Mutunl Drops
of interest,, for example load point a of Fig. 32(a), and the
Voltage Drop to
voltage drops from the reference bus, g, to each of the load Unit
Points a, 0, and c measured or calculated. These are the Load At A B c 11
I I I
self and mutual drops Z,,, Z&b, and Z,,, respectively. The
cwent division for this condition should likewise be z AA I ZAB I ZAC I ZAD
recorded. A 1.28+j2.08 ) 1.1O+jl.71 0.916+j1.3451 O.lO+jO.lg
This process is repeated in turn for the other cardinal ZBA Z BB ZBC ZHD
load points b and c. Mutual drops must, check according B l.Og2+j1.712 2.447+j3.554 1.2OOfj1.808 0.126fjO.263
to Eqs. (163-165). If the solution is to be used for a study ZCA Z zcc ZCU

Of short circuits and relaying, it is generally necessary to C O.gl+j1.3G 1.203;;1.82 1.49-tj2.28 0.151+jO.328
include many cardinal points that are not strictly load &A ZDB ZDC ZDO
points, but are line junctions, etc. D !! ].096+jO.196 0.125fjO.261 0.154fjO.326 0.440+j0.897
316 Steady-State Performance of Systems Including Methods of Network Solution Chapter l(

drops corresponding to the simultaneous loading condition


as stated in the following equation.
Let D, be the total drop to a typical point p.
D,=11Z1,+ZzZ2,+...+ZnZnp (167
Or the voltage at p may be expressed
E, = E,’ -I,.&, - IA,, - . . . -I,&, (168
where E,’ is the voltage at p with no load on the system4
The superposition theorem applies strictly to a fize
network and may appear to preclude the possibility c
connecting loads to various terminals. Fig. 32 illustrate
the philosophy under which this problem is brought withi
the scope of the superposition theorem. Part (a) is th
network with all loads connected, and (b) is the correi
ponding impedance diagram with loads replaced by th
load voltages E,, Eb, and E, and the load currents I,, Z
and I,. The load voltages can be viewed as emfs as far t
relations within the portion of network from g to a-b
are concerned. Part (g) illustrates unit current drawn at (
1.44+j3.02 e
WY) I According to the definition, the drop to a is Z,,; hem
9W 4.75 MILES
!!lJ starting with zero voltage on the generator bus the voltae
-+S
at a must be -Z,,. Similarly the voltages at b and c mu:
is* 2.6O+j3.59 g
pjti be -Zab and -Z,,, respectively. Thus unit load at a ca
5.4 MILES
be viewed as produced by zero generator voltage and t
voltages -Z,,, -Znb and -Z,, acting at 6, b, and
ALL IMPEDANCES ARE IN OHMS ON II KV BASE respectively, in the same network as Fig. 32(g). Parts (i
and (i) illustrate the corresponding voltages required 1
Fig. 33--Single-line diagram of a typical ll-kv subtransmis- produce unit load current at b and c, in this same networ
sion system.
It is at once apparent that if all voltages and curren
of Fig. 32(g) are increased in the ratio Is/l, the resultir
can be used in many of the problems of interest in the emfs are those required to produce current I, at a and zel
performance of systems; that is, regulation, short-circuit load current at the other two points. This condition
currents, losses, loading of lines and equipment, phase shown in Fig. 32(d), and the corresponding conditions fc
angles, circulating currents, stability, etc. loads at b and c are shown in 32(e) and 32(f) respective!
Current Division-To determine the current division Part (c) is simply the no-load condition illustrating 10s
for any particular loading condition the current division emfs equal and opposite to the generator emf, producir
corresponding to unit load current at a point is multiplied zero load currents in the same network.
by the actual load current at that point. When this has If now the four solutions of the same network, as givt
been done for each load point the resulting currents are in (c), for the no-load condition and in (d), (e), and (f) fi
superposed giving the current division for the simultaneous loads at a, b, and c respectively, are superposed, tl
loading condition. resulting solution for the general case, Fig. 32(b),
Let I,, be the total current from p to q, where pq is obtained. Thus:
some particular branch of a network.
E,= E,‘-I,&,- I&,,,- I,&, (16
Then in a network of n cardinal load points, if II, Zz, . . . ,
Eb=Eb’- z,z,b - IbZbb -z&b (I7
I, are the load currents drawn from the network, the E, = E,’ - I,,??,, - I$,,, - I& (17
current from p to q is:
And in this case, as shown in Fig. 32(c):
I,,= IJl.,,+Izz2.,,+~ . * -tZJ”.,, (166)
E,’ = Eb’ = E,’ = E, (17
where I,.,, is the current in any branch pq caused by unit
current drawn at n. Example-Single-Source System. Without Shunt Bra&
Thus, once the basic current divisions have been deter- Other Than the Loads-As an example of the use of tl
mined for unit loads at the cardinal points, the current method, suppose a general solution is desired for the systt
in any branch can be readily determined for any given of Fig. 33. Also the improvement in regulation at pair
load condition. B, C, and D, when 2500 kva of capacitors are added
Regulation-In a similar manner, to determine the regu- each of these points, is to be determined for a particu:
lation under a condition of simultaneous loads at several condition. The network is solved by the method of redi
of the cardinal points, the self and mutual drops for unit tion. See Sets. 14-17. It is first reduced to a single bran
load at a point are first multiplied by the actual load at by employing several series or paralleling operations a
that point. When this has been done in turn for each load, *The voltage at the sourcepoint from which drops are rneasw
the resulting drops are superposed to obtain the voltage is assumedto remain constant.
Chapter 10 Steady-State Performance of Systems Including Methods of Network Solution 317

Convert Delta .4BC to Star*


z&B** = 2.60 fj3.59
ZB-C = 2.60 +j3.59
zc-A = 1.44 +j3.02
D=sum = G.64 +j10.20
l/D = 0.04483 --jO.O6886
ZA-B = 2.60 fj3.59
iAB = Z&D = 0.3638 -jO.OlSl
&-A = 1.44 +j3.02
ZA = ZCdAi*= = 0.5785 fj1.0724
G l/D = 0.04483 - j0.0688G
ZB-C = 2.60 +j3.59
iBc = ZB-c/D = 0.3638 -jO.OlSl
Z&B = 2.60 +j3.59
zB = Z.&BZ’BC= 1.0109 +j1.2590
l/D = 0.04483 --jO.O6886
&-A = 1.44 +j3.02
iCA= Zc-A/D = 0.2725 +jO.O362
ZB-C = 2.60 +j3.59
ZC =zB&A = 0.5785 +j1.0724

6 6 iI G G

Fig. M-Reduction of the system of Fig. 33 with respect to


terminals G and B.

a delta-to-star conversion. Current distribution factors,


symbol i, obtained in the course of this reduction are used
later in the current distribution calculation. The steps
of reduction are illustrated in Fig. 34. The steps in the
subsequent current distribution calculation are illustrated
in Fig. 35, the network being expanded in reverse order, to
its original form. Fig. 35(c) shows the current distribution
for a one ampere load at B. The mutual drops are then
obtained by calculating the voltage drop from generator to
each load point, using the impedance diagram Fig. 33 and
current diagram Fig. 35(c).
This procedure is repeated in turn for unit current at
each of the load points, and the results tabulated as in
Tables 6 and 7. The symbols ZAA, 2~s have been included
in Table 7 to identify the drops, but this in general is
not necessary.
Typical Calculation of Self and Mutual Drops and Current
Division. Unit Load at B
Combine a and c in Series.
a = 0.47 +j 1.00
C = 4.05 +.i 5.90
a+c = 4.52 +j6.90
l’arallel b with aft.
a+c = 4.52 +j6.90
b = 7.78 +j9.04
D=sum = 12.30 fjl5.94
1/D = 0.03034 - jO.03932 Fig. 35-Current distribution in the network of Fig. 33 for
a+c = 4.52 +j6.90 unit load at B.
ib = (a+c)/D = 0.4075 +jO.O321
*Seeequations (87)-(96).
b = 7.78 sj9.04 **Z,-B is used here for impedance of branch from A to B to
il=parallel b with (a+c) = 2.8802 +j3.9335 distinguish it from ZAB, the drop to B for unit load at A.
318 Steady-State Performance of Systems Including Methods of Network Solution Chapter 10

Refer to Fig. 36 and Combine d and k in Series. zh= -Ic = 0.4446+jO.O205


d = 1.85 +.i3.15 ib = 0.4075+jO.O321
k = 0.5’79 +j1.072 IGC = ibIb = O.lSOS+jO.O226
n=d+k = 2.429 4j4.222 IcD=Jh-I~c= 0.2641-jO.0021

Series h and 1. Mutual Drops.


h = 2.88 ICA = 0.5554-jO.0205
+j3.03
1 = 0.579 +i1.072 d = 1.85 +j3.15
p=h+l = 3.459 +j5.002 ZBA = 1.0921fj1.7116
I CC = 0.1805fj0.0226
Parallel n and p. b = 7.78 +j9.04
n = 2.429 +.j4.222 ZBC = 1.2000+j1.8075
P = 3.450 fj5.002
I GD = 0.2641-jO.0021
D = sum = 5.888 +jn.224 a = 0.47 +j1.00
l/D = 0.04917~io.07703
ZBD = 0.1262+jO.2631
P = 3.459 +35.002
i, = p/D = 0.555-l - jO.0205 The current division and self- and mutual-drop factors
n = 2.429 +j4.222 from these calculations are tabulated in Tables 6 and 7,
r = pn/D = 1.4356 +j2.29.51 together with similar factors for unit loads at A, C, and D.
&=1-i, = 0.4446 +jO.O205 Regulation-Tables 6 and 7 are considered to be the
basic network solution. Their use in the regulation problem
Series r and m. will now be outlined.
r = 1.4356 +j2.2951 The chief problem is to express the several load currents
m = 1.011 +j1.259 in proper phase relationship t,o a single reference voltage,
z BB = 2.4466 +j3.5541 either the voltage at one of the most important load points
or the generator-bus voltage.
Current Division*. Refer to Figs. 35 and 34. If they are expressed with respect to the generator-bus
IA= -in = -0.5554+jO.O205 voltage, a simple deduction of vector drops from this
IB = 1.0000+j0.0000 voltage gives the load point voltages so that the load
Ic= -i, = -0.4446-jO.0205 power factors and kva can be checked and a correction
-iCA = -0.2725--jO.O362 made if necessary.
IA = -0.5554fj0.0205 If there is considerable drop in the system but the im-
-iCAIA = 0.1521+jo.o145 portant load voltages are nearly alike, it is preferable to
use one of these load voltages as reference. The generator-
iBC = 0.3638-.iO.O181 voltage phase position can then be determined graphically
IB = 1.oooo
+~o.oooo or by the solution of a quadratic equation as outlined in
iBdB = 0.3638-jO.0181 the example of the circulating current method Sec. 19. A
__ simplified modification of this method is given below. In
I AB = 0.5159-jO.0036
either method the proof of the assumptions lies in the
=-Z'CAIA+~BCIB
check of load kva and power factor and corrections can
-iAB = -0.3638+jO.O181 be applied if the assumed values prove to be far enough
IB = 1.oooo+jo.oooo off to affect materially the regulation values and currents
- iABIB = -0.3638+jO.O181 of interest.
iCA = 0.2725+.jO.O362 The present problem is to calculate the regulation for the
= -0.4446~jO.0205 system of Fig. 33 under normal heavy load conditions,
Ic
Case 1, Table 8, and also with several capacitor banks
iCAIC = -0.1204--0.0217 added as indicated in Case 2, Table 8.
IBC = -0.4842-jO.0036 A practical problem now arises that is not immediately
= -~ABIB+&AIC evident from Eq. 168. The load power factors given fix
-z’BC = -0.3638+jO.O181 the positions of the currents with respect to the final load
IC = -0.4446-jO.0205 voltages, (E, in this equation) not with respect to the
-iBdC = 0.1621--jO.O006 generator or “no load” voltage E’,. Thus the phase rela-
tions between the generator voltage and the drops cannot
iAB = 0.3638-jO.0181 be determined directly. A further difficulty exists in con-
IA = -0.5554fjO.0205 verting the loads from kva to amperes since the load
iABlA = -0.2017+j0.0175 voltages are not yet known.
ICA = -0.0396fjO.0169 A straightforward method of approach would be as
follows. First assume that all load voltages are equal to,
= -iBCICfiABIA
and in phase with, the generator voltage. Convert load
*Seeequations (88b), (89b), (90b). kva’s to vector currents with this voltage as reference.
Chapter 10 Steady-State Performance of Systems Including Methods of Network Solution 319

TABLE ~-REGULATION WITHOUT CAPACITORS (CASE 1) AND WITH CAPACITORS (CASE 2)


Resulting Drops to
AS-
Load
sumrd Amperes B C D
CRSC - -
Regu- *
At kvn-p.f. l&ion Volts ;neg.
-9
Volts 6Reg Volts %Rf%
-
I B 2500 - 90 y. 11.0% 130.1- j63.1 543.5+j309.1 271.4+j161.0 32.9fj26.2
Lag
c 4500 - 85 yo 13.0 yo 226.6 -j140.3 526.1 +j240.7 656.3fj304.9 s1.2+j52.9
LWZ
D 11 ZOO-85% 9.0% 539.3 - j333.7 154.9+j102.6 190.9+j123.8 539.ifj341.0
Lag - - -
1224.5fj652.4 19.4 1118.6+j589.7 17.7 653.8+j420.1 10.5
Total voltage drop
All :!265kva -90.4% 4L254kvn -84.9% 1 1 Ollkvn-83.4%
Calculated load
Lag LWZ Lag
=zz=== ZZ = -
2 B 2500-90% 570 122.1 fj76.6 26.4fj622.0 S.Ofj313.3 -4.7fj41.6
plus 2500-O%t
=2655-84.7%
Lead
c 4500-857, 5% 207.5+j7.0 236.7+j384.0 293.6+j481.3 29.9+j69.3
plus2500-O~~/ot
=3827-99.90/o
Lead
D 11 ZOO-85yc 2.5% 503.4-j179.9 110.7+j109.7 137.4fj137.6 384.7 fj376.3
plus 2500 -U% t
=lO 110=94.20/,
Lag - - I-
373.8+j1115.7. 6.7 439.o+j932.2 7.8 209.9+j48i.2 7.1
Total voltage drop
All
Calculated load
2609kva-82.8y0 : S715kvn-99.9% !$635kva-91.6%
- - Lead -
Lead - Lag
For Case 1 use Eg=6438.6+j600; For Case 2 Ez=6403.6+j900.
tcapacitors (6466.5 volts L-N)
*Based on load voltages-all in phase-taken as reference, but below the generating bus voltage of 11.2 kv by the “assumed regulation”
values.

Then calculate and deduct the drops to determine the reactive drop to the loads. The example will make this
load voltages corresponding to this first approximation of clear. The magnitude of generator voltage is a given
the currents. The currents used will not have quite the quantity. It is apparent that when the drops to various
right phase positions or magnitudes, when associated with load points are deducted from this generator voltage, the
t,hese load voltages, to agree with the loads and power load voltages obtained are close to the reference phase and
factors specified. hence the load power factors are close to those for which
However, with these load voltages a new set of load a solution is desired. Thus the resulting generator voltage,
currents can be calculated, the drops recalculated and a load currents, and drops are now sufficiently accurate to
second approximation to the load voltages determined. complete the regulation calculation. An exact answer is
This process is highly convergent and the second approx- obtained for a set of loads differing slightly from those
imation would ordinarily be sufficient. In fact by making assumed. The example will make this clear.
two judicious guesses, one an estimate of regulation to each As the loads are given in kva and power factor, it is
lOad point and the second an estimate of phase shift from necessary to estimate the load voltages to convert the
generator to load, the first approximation is nearly always loads to currents. The load voltages are all assumed to be
sufficient and but a single calculation is required. This is in-phase, as a first approximation, and below the normal
the procedure followed in the subsequent paragraphs. voltage of 11.2 kv by the “assumed regulation” values
The assumed regulation to the load points is a straight- listed in Table 8. Load currents are calculated on this basis
forward estimate from experience or from the quick esti- using load voltage as the reference axis. For example the
mating tables of Chap. 9. However, the treatment of the load current at C is for Case 1:
phase-angle estimate bears some further explanation. First
the load voltages are assumed to be in phase. Making use
of the regulation estimates the vector load currents can be
calculated with this common load voltage phase as a refer- = 226.6- j140.3 amperes.
ence. The vector drops can be calculated and consist of in- Voltage drops are computed according to Eq. (167), the
phase and out-of-phase drop components. The generator component and total drops being as shown in the table.
voltage is now selected leading the reference by the average A rough check of the drops at the critical locations, B
320 Steady-State Performance of Systems Including Methods of Network Solution Chapter 10

and C, indicates that for normal load conditions, Case 1, Case 2 of Table 8 illustrates the great improvement in
the approximat,e in-phase drops are 1224 and 1118 volt)s, regulation possible by the use of shunt capacitors. They t
or approximately 19.0 and lT.2 percent of normal line-to- may have to hc partially switched off at light load to $
neut,rnl voltage. The ‘Lassumed regulations” could be cor- prevont overvoltages under that condition. Comparing ,;
rected at this point but as this repetition would not add the reduction in drops caused by capacitors at D, with the (
to the exposition, it is omitted. reductions caused by capacitors at B and C, it can be seer. ”
Up to this point a reference axis in phase with the load that the capacitors are much more effective at the latter i
voltages has been used, the load voltages being taken all two points which arc farther from the generating station.
in phase. This was most convenient for converting loads Single-and Multiple-Source System Having
to currents as the power factors were known with respect Shunt Branches Other Than Loads-Figs. 36(a) and
to the load voltages. Now it is necessary to determine the (b) give a simple illustration of a system having shunt
generator voltage with respect to this reference so that the branches other than loads, namely charging capacity of
calculated drops may be deducted from it to find the actual high-voltage lines or cables. In this case the no-load volt-
load voltages. The phase position of the generator voltage ages E,’ and Eb’ of Fig. 36(c) differ from point-to-point in
does not need to be determined exactly. However after the system and also differ from the generator bus voltage
the load voltages are computed, the load power will be E,. If there are several sources, a similar condition exists.
computed and the regulation will be exact for the loads However, in either case the no-load voltages can be deter-
thus computed rather than for the actual given loads. mined by measurement on a network calculator or by
Such a result is usually an adequate engineering answer calculation and these form the base from which drops are
as the “given ioads” are seldom accurately known. However deducted to determine voltages under load conditions by
it is desirable to start with a generator voltage as near as Eqs. (169) to (171). If the generator emfs vary in phase
possible to that corresponding to the assumed load voltage or magnitude for different parts of the study, the no-load
so that the computed loads will be close to the given loads. voltages must be changed accordingly.
This is accomplished as follows. Fig. 36(f) shows the arrangement of the network for
Noting that the out-of-phase drop is approximately 600 calculation or measurement of Z,, and Zsb. Sufficient
volts for B and C, the generator bus voltage is arbitrarily voltage is applied between a and the bus of no-voltage to
taken 600 volts ahead of the load voltage or reference. The draw one ampere, all generator emfs being short circuited.
drops, as deducted from this voltage, give load voltages The voltage required, using the reference direction shown
quite closely in phase with those used and hence the load in Fig. 36(f), is -Z,,. It is thus necessary to amend the
power factors are nearly correct. As the generator voltage definitions of Z,, and Z&bgiven previously to the following:
magnitude is 6466.5 volts, line-to-neutral, the in-phase Z,, is the vector voltage drop from g to a caused by unit
component must be d(6466.5)2- (600)2 = 6438. Whence current drawn from the network at a, with all generator
the generator bus voltage is 6438fj 600. emfs set equal to zero.
The load voltages should now be calculated and the Or it is the incremental vector drop in voltage at a
loads checked to see that they do not differ too far from per ampere drawn from a, with all generator emfs fixed
the assumptions. A typical check follows, for Case 1, load in magnitude and position and all other load currents
at B. held constant.
E, = 6438 +j 600 Z&b is the vector voltage drop from g to b caused by unit
DB = 1224 +j 652 current drawn from the network at a, with all generator
emfs set equal to zero.
EB = 5214 -j 52
The voltages and currents in Fig. 36(f) and (g) are
EB = (5.214~j0.052)kv labeled in accordance with these definitions. Increasing
3fn = 390.3+j189.3 in ratio of actual load currents, parts (d) and (e) are
PB-I-~QB = (205O+j 970)kva obtained. Part (c) is the no-load condition. The super-
z.2 2265 kva position of (c), (d), and (e) results in currents identical
at 90.4 percent power factor lagging. with part (b). Consequently, the voltages E, and Eb in ’
, H.V.
‘LINE J,

LOAOS
km 0EO b Eb

h ibl IMPEDANCE DIAGRAM WITH (c) NO LOAD CONDITION. Id) LOAD AT o ONLY.
lo) SINGLE LINE DlAGRiM LOAOS I0 AND lb.

(*I LOAD AT b ONLY. (f) UNIT LOAD AT a. (0) UNIT LOAD AT 0.

Fig. 36-Single-source system having shunt branches other than loads,


Chapter 10 Steady-State Performance of Systems Including Methods of Network Solution 321

T,:Lrt (b) must be the superposition of the corresponding c. Expand the network developing the current division
c,,,:mtitiCs in Cc), (d), and (r), as stat,ed in Eq. (168) based on one ampere drawn out at the selected load
ge~~ernlly. Specifically point. This current division is part of the general
E, = E;,’ - I,Z:,, - I,,.& (1’73) solution.
d. Calculate t,he voltages of other load points above the
E,, = EL,’- IaZ;,,, - li,Zt,~, (17-l)
bus-of-no-voltage, or neutral bus. These arc negn-
It is apparent that the case of no shunt branches is tives of the mutual drops.
sjmply a special case of the situation with shunt branches. e. Perform a, b, c, and d for other load points in turn.
:\ISO the case of one emf is a special case of that wit,h f. With the load points all open circuited apply the
s~~~~c~ral. However, without shunt branches it is customary generator emfs to be used in the study and determine
t,o apply enough voltage at the generator to cause one am- the no-load voltages.
pcrc in a short circuit at the load point and determine the g. Load voltages and current distribution throughout
t~lops through the network from generator to load points the network may now be determined for any loading
to obtain the constants Z,,, ZRh, etc. With shunt branches condition corresponding to the generator emfs from
I)r(xant this is no longer a series circuit from generator to which the no-load voltages were developed. The
10acipoint. In this case the voltage must be applied at voltage at any load point p is given by Eq. (168).
111cload point and the generator emfs short circuited, or The current in any branch, p-q is given by Eq. (166).
(:lsc an indirect, method employed as described below. XOTE: Alternative methods are outlined in the following
With several emfs and shunt branches the network con- paragraphs.
Stants can be obtained by short circuiting one load terminal More Than One Source-As Negative Loud-If
at a t,ime, after first having measured the no-load voltages the generator emfs do not remain constant throughout a
IS’,‘, El,‘, . . ., E,‘. Referring to Eqs. (173) and (174) this study, the network can be solved by treating all sources but
gives the condition: one as load points. Determination of voltage and current
E,=O (175) conditions on the system for any loading conditions are
Ib=o (176) then determined by using as the no-load voltages, those
produced by the one selected source alone. These n-ill be
(177) directly proportional to this one source voltage and hence
can be varied for different conditions of the problem if that,
z =.%,‘-Eb source voltage changes. A condition of the system is then
nb (178)
1, completely specified by the selected source voltage and the
currents drawn at all other sources and load points.
Similarly by short circuiting b, the other constants are Changes in the Network-When a transformer is
obtained.
removed or a line opened, it iS of course desirable to deter-
z =&‘-En mine the effects without completely solving the new result-
ba (179)
Ib ing network. Assume that the branch to be omitted or
Eb’ added connects between two of the cardinal points, a and c!
Z,,b=- (180) of Fig. 37 for which network constants and current division
Ib
factors are known. A solution is desired with the branch ac
Both measurements, that is, the no-load voltages and removed. By solution is meant the voltage at any cardinal
:Jso the voltages and currents with one terminal short point and the current in any branch corresponding to a
cxircuited, must be made with the same generator emfs. particular load condition on the network. Thus the solution
IIo\vcver, it is immaterial what emfs are used SO that they of the changed network for a given load condition is iden-
may be taken all in phase and equal for the purpose of tical with the solution of the original network for the same
obtaining the system constants. This results in a different load condition plus two additional loads. One of these
set of no-load voltages for computing system constants added loads is drawn at each end of the branch to be
than the actual no-load voltages used in the system studies removed from the original network. These added loads are
I)ut simplifies calculation in some cases. equal and opposite to the current in the branch so that the
Summarizing, the general solution of a multiple source total current drawn by the branch and added load is zero.
system with shunt branches consists of: Suppose the load condition being solved for is I,,, Ic, Id
a. Self and Mutual Drops. and the corresponding current in ac is I:,,. When loads
b. Current Division. I,’ and I,’ (equal to -I,‘) are added, they cause additional
and for each set of emfs to be used in the study current in the branch ac:
c. No-load voltages.
A suggested procedure for calculating these data is as AI,,= I:,‘I,.,,- 7,‘Ic.x (181)
follo\vs. If a network calculator is used, the labor of re-
ciuctions is eliminated. The total of branch and added load must equal zero.
a. Apply voltage at one load point with generator emf I,,+ I,‘(I,..,- T,..,,) +I,’ =O (182)
short circuited and other load points open circuited.
1). Reduce the resulting network to a single branch whence: I,’ = _ -2: I (153)
viewed from the selected load point. This branch 1+1,,.,,-f,.,,
is the self drop. and I,‘= -I, (184)
322 Steady-State Performance of Systems Including Methods of Network Solution Chapter IO

the loads I,’ and -I,’ were added at a and c respectively,


instead of connecting the impedance Z.
p co; , A branch 2 can be removed by adding an impedance

Iac
I
branch, -2, as alternative to the method previously
given.
Example of Changing a Network-A partial solu-
b c d tion of the network of Fig. 38 follows:
l-4-4
*b
EC

*d
Z;,,=2.5 ohms I,.,, = -0.25 amperes
(0) ORIGINAL NETWORK
Z,, = 1.75 ohms ln.ha= 0.75 amperes
Z,, = 2.875 ohms I,.:,, = 0.375 amperes
Ic.b3= 0.375 amperes

10,
IL=- ItI a . ac-lea

Ib 1, Id
(b) ORIGINAL NETWORK WITH ADDED LOAOS-
MAKING IT EQUIVALENT TO CHANGED NETWORK I
(a) (bl

Q 0
t-7
lb ic Id 0 c
lb IC Id
(c) CHANGED NETWORK 2
(d) '
Fig. 37-Adding loads to a network to make it equivalent to
the network with a branch removed. Fig. 38-A simple network showing loads and distribution
factors.
Thus to solve the changed network for a given set of loads
it is merely necessary to solve the original network instead, From this solution the currents and voltage drops for
using the two added loads determined by Eqs. (183) and the load condition, Fig. 38(d), are obtained.
(184). Iba=2X0.75+3X0.375=2.G25 amperes
Adding a Branch Between a and c. Refer to Fig. 1,,=2x(-0.25)+3X0.375=0.625 amperes
37 (a)-Suppose a branch is to be added between a and c D,=2~2.5+3X1.75=10.25 volts
having impedance 2. It can be simulated in the original D,=2~1.75+3~2.875=12.125 volts
network by loads equal to what the branch would carry
if there. Referring to Fig. 37(b) a branch would carry: Now consider the changed network Fig. 39(a) under the
same load condition. Solving directly:
(185) Ib’:, = 2 amperes
Id, = 0 amperes
where primes refer to the condition after the branch is DL=2X2f5X1=9 volts
added. Dd=3X3f5X1=14 volts
E: = E, - I,‘Z,,i- I,:.??,, (186) However, suppose it were desired to obtain these data
EL = E,- I:.Z,,+ I:&, (187) from the solution of the network, Fig. 38. Then using
I,,-E&-EC I, Z:,,-22,,+Zx Eq. (1.83):
‘I
z
(188) Iac
z n
E,--E, -= I),-D, *,‘= -l+In...-I,!.,c
r: = (1W 0.625
z,,-22,,+2,,+2 .&,-2Z~c+zx+~ =-- = - 1.C,6amperes
I-0.25-0.375
That is, the effect on the voltages and currents in Fig. I,‘= -I,’ = 1.66 amperes.
37(a), of adding a branch of impedance, 2, between a
and c, while holding the generator emf and the load Fig. 39(b) shows these loads added to the network loads
currents lb, fC, and Id constant, is exactly the same as if of 2 and 3 amperes at a and c.
Chapter 10 Steady-Slate Performance of Systems Including Methods of Network Solution 323

‘fit
2
(a) 3
2[&ii,
-1.666
(b)
Fig. 39-Network of Fig. 38 changed by the removal of branch
IX
a c and its equivalent. (01 INTERMEDIATE LOAD

Z,‘,=O.33X (-0.25)+4.66X0.375= 1.66 amperes.


Thus it is seen the added loads and the current in branch
(1~total zero, and can be eliminated.
‘I’lut is : Z:,+Z:=1.66-1.66=0
r-%
,+---++b
Proceeding with the solution.
(8-m) Ix mix
Ida=0.33X0.75+4.66X0.375=2.0 amperes (b) EQUIVALENT LOADS AT o R b
Dz’ = 0.33 x2.5+4.66X 1.75 = 9.0 volts
Dd=O.33X1.75+4.66X2.875= 14.0 volts.
All of these agree with the direct solution. I,’ could also
h(: obtained from the consideration of adding a -3 ohm
Ixmch from a to c. Eq. (189) gives
DC-D,
r;=
zl,-z,o+Zcc+Z
12.125- 10.25
= - 1.66 amperes. (cl CURRENT DIVISICN TO
=2.5-3.5+2.875-3 INTERMEDIATE LOAD
and the remaining solution is the same as above. Fig. do--Current division for a simple network with a single
Intermediate Loads-It frequently happens that reg- intermediate load.
ulation and current division are required at loads con-
nected along branches intermediate between two cardinal the network as the actual condition [Fig. 40(a)].
points, such as the load at z, a fractional distance, m, along The currents in branch ab are determined as sho\vn
impedance branch 2 from a to b, Fig. 40. in Fig. 40(c), in which I,L, is as determined from the
To determine regulation at x proceed as follows: equivalent loading, Fig. 40(b).
a. Replace I, by two loads (1 -m) I, at a and ml, at General Solution for Intermediate Point-The
b, as shown in Fig. 40(b). From these and the other intermediate load location is to be treated as a new car-
loads on the system, the voltages at a and b can be dinal point of the network for which self and mutual drop
dctcrmined and a circulating current lab found. constants and current division factors are required.
b. Permit the currents (1 -m) I, and ml, to flow over The self drop constant is obtained by recalling that for
the branch to point 2 and into the load. This will unit load at 2, Fig. 40, the drops to a and b are
not alter the drop from a to b since the two added (193)
D,=(l-m)Z,,+m&,
drops introduced into this branch are equal and
opposite. DL,= (1 -m)Z,b+m%bb (194
whence:
(l-m)I,mZ=mI,(l-m)Z (190) Z,,=(l-m)D,+mDb+m(l--m)Z (195)
Kor will it alter the circulating current I,b that or Z,,=(l-m)2Z,,+2m(l--m)Z,~~
causes the drop through Z and absorbs the voltage +m*Zbb+m(l -,m)Z (196)
difference between a and b. The drop can now be
calculated from either a or b to the load point, tak- The mutual drop constant to a typical point, p, is
ing into account both circulating and load com- Z,,=(l-m)Z,,+m& (197)
ponents of current. The current in any branch pq caused by unit current
D&,=(1-m)I,mZ+I,bmZ (191) drawn at 2 is (except for branches ax and bz):
Or the voltage at z is: I x.p~=(l-m)In.pq+mIb.~~ (198)

E,=(l-m)E,+mEb-I,m(l-m)Z (192) For branches a~: and xb


C. The use of equivalent loads at a and b [Fig. 40(b)]
results in the same currents in all other branches of I x.bx=(l-m)za~bbmlb.ab-m (198b)
324 Steady-State Performance oj Systems Including Methods of Network Solution Chapter 10

While for point, Y, external to branch ab, e. The current in any section of one of the circuits of
branch ab consists of the vector sum of the circulating
Iy.*x = I,.,ll =Jy.& (198c) component as determined in (d), and the reintroduced
Several Intermediate Loads-If the branch ab con- equivalent load currents flowing up to the inter-
sists of several parallel mutually coupled circuits such as mediate loads.
the trolley rail circuits of a four-track railroad, and con-
tains several intermediate loads, the procedure is quite 21. Circle Diagram of Transmission Systems
similar to the above. Refer to Fig. 41. Because of its importance to both the light and power
and the communication industries, the transmission type
network has been widely studied. A useful body of data is
available for simplifying the calculations and expressing
the performance of such networks. The fundamental ideas
involved are extremely simple, and the reader should not
be misled by the large accumulation of formulas tabulated
for special cases. These merely signify that the field has
been well explored, whereas only one or two of the formulas
may be required in any particular problem.
The general transmission-type network including shunt
loading, is one having only input and output terminals of
importance, designated for convenience as the sending and
receiving ends. The type dealt with in this chapter is
considered to be passive (having no internal emfs), and
b linear (made up of linear impedance branches and voltage
transformations),
For such a network the sending-end voltage and current
depend solely on the receiving-end voltage and ‘current,
IX and the impedances and voltage transformations of the
Fig. 41-More complex network having several intermediate intervening network.
load points. The transmission problem is briefly the determination of
the performance of the transmission-type network. This
Let 2 be the total impedance a to b. performance is most commonly expressed in two forms.
Let z be the impedance of each component circuit. a. Equations expressing the sending-end voltages and
Let M, M’, M” be the mutual impedances between currents in terms of the receiving-end voltages and
component circuits. currents, and vice versa.
It is assumed that these impedances are uniform b. The power equations or loci, the graphical representa-
throughout the section. tions of which are known as the power circle diagrams.
The procedure is as follows for determining voltage at One circle gives the locus of sending-end power and
the load I,, and current distribution. one the locus of receiving-end power, as the angle
between sending and receiving voltages is varied.
a. Divide each load inversely as the impedance to the
two adjacent points a and b, to obtain total equiva- A third form is sometimes used.
lent loads. From these and the other network loads c. The current equations expressing the sending-end or
the voltages E, and Eb can be determined. The total receiving-end currents in terms of the voltages at the
circulating current I,b can also be found. two ends. The current locus for fixed voltages and
b. Determine the voltage at z while the loads are re- varying angle between them is the current circle
moved to a and b. It is: diagram.
E, = (1 -m)E,+mE,, Power Circle Diagram-The power-circle diagram is
(199) derived mathematically in Chap. 9. The treatment in this
C Now reintroduce the equivalent load currents letting chapter applies the diagram to general system problems.
them flow over the circuits to their respective loads. Condensed tables are presented for determining the circle
In the case shown there are four added drops, result- diagrams from general circuit constants. First, however,
ing in a voltage at the load I,: a brief review of the power-circle diagram will serve to
E,=(l-m)E,+mEh-(I-m)I,mz-(l-n)I,mM point up the important power system design and operating
- (1 -p)I,mM’- (1 -q)I,mM’ information which it provides.
(200)
The fact that real and reactive power fed into and out
d The circulating current lab should be divided between of a transmission line can be plotted as a function of the
the four circuits as though the loads were not present, sending- and receiving-end voltages only is itself an ex-
If the mutual impedances are nearly equal it may be tremely important concept. Stated differently, once the
sufficiently close to assume g of the total in each voltage magnitudes at the two ends of the line have been
circuit. Otherwise a solution by equations may be fixed, there exists for each angle between these voltages,
required. See Sec. 13. one and only one possible value for each of the four quan-
Chapter 10 Steady-State Performance of Systems Including Methocls of Network Solution 325

I I
POWER CIRCLE DIAGRAM
220 KV LINE

8=10,247 + j57,682

SENDING END POWER CIRCLE FOR ER’i27,020


AND Es=l29,917 VOLTS (NORMAL LOAD) H
50 000

AND E,=l37,523 VOLTS (EMERGENCY LOAD)

40 000

30 000

20 000

-----.

LAGGING REACTIVE KVA 0


---- - _
I PLIED BY CONDENSER s
* IOOOD
2
w
>
5
2l C
a
s
ci
s:
J-IO OO(

-20 OO(

-30 OO(

/
-40 OO(
I-

AND E,=l29,917 VOLTS (NORMAL LOAD)

-50 OO(

\A.-979 5-j

-60 001 1
-10 30 0
REAL POWER (KILOWATTS-SINGLE PHASE)
Fig. 46-Typical power-circle diagram.

tities, input real and reactive power, and outpuk real and three power quantities are uniquely determined.
reactive power. Or, if one of these is fixed, say delivered If the voltages of the two ends of the line are fixed in
real power, this determines the angle and thus the other magnitude and the angle between them varied, then for
326 Steady-State Performance of Systems Including Methods of Network Solutzbn Chapter 10

each angle there will be a discreet value of input real and For this angle and these voltages note that 27 595 kw
reactive power. If these are plotted, one against the other, enters the line and 25 835 kw leaves it at the receiving end,
on a set of coordinate ases having real power as abscissa the loss being 1760 kw. At the sending-end lagging reactive
and rcnctive power as ordinate, the locus of such points as kva is negative and hence flows opposite to the reference
the angle betn-een voltages is varied is a circle. Thus this positive direction. That is, lagging reactive kva flows out
plot of real power vs. reactive power for fixed line voltages of the line, 7620 kva. This must be absorbed by the system
and varying angle, is called a power circle diagram. What at the sending end of the line, in inductive loads or by
has been said of input real and reactive power applies under-excited machines. At the receiving end lagging r+
equally well to output real and reactive power. Hence, active kva is positive and hence flows in the reference
for a given pair of terminal voltages there are two circle direction for that end which is out of the line, 2270 kva.
diagrams, a sending-end circle and a receiving-end circle. In general this may be more or less than the lagging r+
For other voltages there are other circles. The fact that active requirements of the load and the difference must be
these diagrams are circles makes them easy to draw. Hom- absorbed or supplied locally. For example, if the load were
ever the important point is that the input and output real 25 835 kw at 83.26 percent power factor lag as plotted at
and reactive powers are uniquely determined by the ter- E, requiring 17 258 lagging reactive kva, the difference of
minal voltages and the angle between them. In a sense 14 988 kva would have to be supplied by a synchronous
this places definite restrictions on the use of lines. Or from condenser operating in its over-excited range, or an
another viewpoint it makes it possible to predetermine the equivalent.
amount of synchronous-condenser capacity that is required If the load is increased to an emergency load of 52 335
to supply a given load over a given line. kw at 84.78 percent power factor lagging, the correspond-
These points may be made more clear by reference to ing points on the circles are at J and K. It is assumed that
Fig. 46 which shows the sending-end and receiving-end the sending-end voltage has been raised to 137 523 volts
power-circle diagrams for two values of sending-end voltage L-N for this condition. The condenser must now supply
and one value of receiving-end voltage, i.e. for two com- 52 461 kva of lagging reactive, as the line supplies a nega-
binations. Thus there are four circles. The method of tive amount or actually draws lagging reactive.. Note that
plotting these circles and the derivation has been given in to supply this load with the lower sending voltage would
Chap. 9, and will be summarized shortly for the general have required considerably more than the 52 4Gl kva from
case. That need not concern us here. Suffice it to say that the condenser.
there are such plots. What do they show? Other circles could be drawn for different receiver volt-
The coordinates of the plot are real power as abscissa, ages and these would show the variation of synchronous-
positive to the right and lagging-reactive power as ordinate, condenser capacity requirements within the limits of
positive upwards. The two sending end circles, have their permissible variation of receiver-end voltage.
centers at R and 13’ in the first quadrant. The positive Thus the circle diagram presents a complete graphical
reference direction at the sending end is into the line. Thus picture of the line performance under all conditions of
positive real or reactive power flow into the line at this end. terminal voltages and angles and hence provides the nec-
The t\vo lower circles having centers at A, in the third essary information for design and operation of the system,
quadrant, are the receiving-end circles. At the receiving particularly with relation to voltages, provision of reactive
end the positive reference direction is out of the line. Thus capacity, and real power flow.
positive real and reactive power from the receiving circles Transmission Equations: Constructing the Circle
indicate real or reactive power out of the line and a nega- Diagram
tive sign of reactive power indicates that lagging reactive Generally the following steps are involved in determin-
power flowed into the line at the receiving end. ing the transmission characteristics of a system from one
Note first there is a maximum power that can be deliv- point to another.
cred, for example 57 771 kw for one set of voltages, ER= a. The network must be reduced to a simple equivalent
127 020 and Es = 129 917 volts L-N. This is of course an from which the constants for plotting the circle dia-
absolute limit and well beyond a practical operating limit. grams can be obtained. The simple equivalent can be
It has been stated that with fixed voltages there exists expressed as a T or a Pi circuit or by giving the
for each angle between them, one and only one possible coefficients of the current and voltage equations,
value of each of the four power quantities. This is shown called the ABCD constants. Table 9 gives the nec-
on the diagram, for example, for an angle of 23’20’59”, and essary formulas for determining the ABCD constants
for the voltages E~=127 020, Es=129 917 volts L-N. directly from networks of various forms. The T and
Note that the angles are measured out from reference Pi equivalents can be obtained by reducing the net-
lines, marked Line for 8=0, whose construction will be work as outlined in Sets. 13-17, or as indicated by
described later. The angle B, by which the sending-end the definitions of these constants which are to follow. I
voltage leads the receiving end voltage is measured out Table 10 gives the transformations from Pi to T and ;
ccw for the upper or sending circles and cw for the lower to ABCD forms. This table also includes transforma- !
or receiving-end c.ircles. Thus this specific angle fixes the tions to admittance and impedance constants that
points F and G on receiving and sending circles respec- are coefficients of the power equations as shown in
tively. These are referred to as corresponding points, since the table.
they correspond to the same angle and hence give sending- b. The Current and Voltage Relations if needed can be’
and receiving-end conditions that occur simultaneously. written directly from the T, Pi or ABCD constants
Chapter 10 Steady-State Performance of Systems Including Methods of Network Solution 327

TABLE 9-GENERAL CIRCUIT CONSTANTSFORDIFFERENTTYPESOF NETWORKS~


- I- Equations for general circuit constants in terms of constants
Net- of component networks
work Type of Network -
.ultlbCr A= B= C= I D=
.-
1 jeries impedance ES ER 1 2
z
.-
0 Y
I -
2 jhunt admittance 1

.-
I +ZTYT
3 rrandormer YT
a

--
I:N
33. Transformer Ratio
1
Yv
0
-- -
Cosh v’?% /Z/ Y Sinh J/z Y
=z l,?,
4 Transmission line ( Same as A
zz+-.)

5 General network aABCD(ER

General network and trans-


6 former impedance at receiv- Es AIB,CIDI Al
ing end
General network and trans-
7 kdmer impedance at sending AI SCIZTS

General network and


8 transformer impedance AISCIZTS 31+‘41ZTR +
at both ends-referred DlZTS fClZTRZTl >
to high voltage
--
General network and
transformer impedance
at both ends-transform- TS TR t
0 .4lBlClDl t--+5
ers having different ratios +---I
Ta and 7’s referred to low Es ZTS ZTR ER 3)
voltage

General network and shunt ~1 AIB,CIDI lm-


10 admittance at receiving At +&YR CI+DIYR i DI
end

General network and shunt


11 admittance at sending Al Bl c*+ALYd DI +BIYs
end

General network and


12 shunt admittance at 111
+&YH Bl
both ends
-.
Two general networks in
13
series AIAZ +ClBz BlAz +DIBz

Two general networks


14 in series with intermc-
diate imoedance ZI‘ 41Cz+C1Dz+
c’IC1Z
BICI +DID? +
DlC’rZ

Two general networks in AzBzCzDl B1.42 +DIBz +


15 series with intermediate us I
BIB21
shunt admittance
1
AdAdz + Cd&h +
16 Three general networks CtJ% Cz(Adz +CdQ DA)
in series +&(AICZ+ +D:,(rl~Cz +CIDZ) +Dz(BL’z +
CID21 DID?)

1; Two general networks in paral- BIB,!


lel B,+B,!
-
..
- TABLE lo-CONVERSION FORMULAS FOR TRANSMISSION TYPE NETWORKS
To Convert From

ABCD Impedance Equivalent Pi


-- --
A= ABCD Constants 1 +zI’n
p, +ias PR+jQR
B= Es = AER+ BZR Z
1s= CER+ DIN
c'= ER =DES- BZs 1
Q--I-l~
ZR= - CEs+AZs z;;
D= ZU IfZYs Fig. 42
271
- -- -- -- -- -
1I’,, = A -& 1 t&Y
E Z,,Z,r-z:, YR+;
ZR +zS + ~‘ZR&

1I’,? =
-- 1 -__- Z,, -- 1
B Z,*Z,r- zz.
L’ Z
I122 D -p, +io2 -p,+ia,
= Zl, 1+ YZR
x Z,,Z,r -z:, ZlL +.&I + Y~aZs
- -- -- -- -
s:,, = D 1 +zYs
c Impedance YR-tyB+z:YItys
ZR++?

Constants Fig. 43
2:,* = 1 1 1
7
E E, = z,,z,+z,,z, 1 It+l~n+%~‘lo’~ 1
I 2 A
c
E, = z,,z,+z2*z1 : ISZYR
YR+~S+LYRYS
r zs++
- -- _- --
Y R= A -1 z,, -z,2 ___-__I’zy F‘s+jQs PR+jOft
B z,,z,2 -z:,
i zK+zY + YZRZS
I
2:= B z,,zy2-z:,
zn Equivalent Pi
F Y a= D-1 z,, -zn
B z,,z, -z:, Fig. 44
- -- - - -- -
J P s+iOs
Zl I)- 1 Z,, ---LIZ -- p,+IQu
c
c 1
k
ZS 2,
-5

.; I c I Equivalent T
Z,? ES Y ER
r:
Z5 A-1 m

c ZP2
-a* Fig. 45
- - - -
Chapter 10 Steady-State Performance of Systems Including Methods of Network Solution 329

TABLE 11-CURRENT AND VOLTAGE RELATIONS IN as shown in Table 11. Frequently these are not
TRANSMISSIONTYPE NETWORKS needed.
A. For I~RCD Constants-Reference Fig. 42.* c. The Power Expressions are given in Table 12 in terms
ES = AER+BIK (201a) of the T, Pi, or ABCD constants and also in terms of
Is = CER + DIR (201b) admittance and impedance coefficients, which are
ER = DES - BIs (2Olc) described in a later paragraph. The power convention
IR= -CEs+AIs (201d) used in this text is:
R. For Equivalent Pi-Reference Fig. 44. P+jQ= El (212)
Es = (1 +ZYd&+ZIn (202a)
Is=(YR+Ys+ZYRYS)ER+(1+ZYs)IR (202h)
for which a positive value of Q is lagging reactive
ER=(~+.ZY~)E~--ZZ~ (202c) power, and P and Q of the same sign indicates lagging
In=-(YR+Ys+ZYRY~)ES+(~+ZYR)IS (202d) power factor (see Sec. 2). At the sending end, denoted
C. For Equivalent, T-Reference Fig. 45. by the subscript, S, the positive direction is into the
ES=(1+ZSY)ER+(ZI1+ZS+YZRZS)lR (203a) network. At the receiving end, denoted by R, it is out
Is=YER+(I+ZRY)IR (203b) of the network. See Figs. 42, 44, 45 which are part of
ER=(~+ZRY)ES-(ZR+ZS+YZRZS)~S (203~) Table 10. With the generalized impedance or admit-
IIt= -YEs+(l+ZsY)ls (203d) tance form, Fig. 43, the reference-positive direction
1). For Admittance-Reference Fig. 43. for current and power at each terminal is into the
I, = Y,,E, + Y,,Ez (203e) line or network.
I? = Y,,E, + Y,,Es (203f) d. The Power Circle Diagrams can be determined from
E. For Impedance-Reference Fig. 43. the data in Table 12 as outlined at the bottom of the
E, = ZJ, +Z,,I, ww table. The detailed data for plotting the circles can
E, =Z,,I, +z,J? (203h) be obtained from the supplement’ary Table 12A,
*Firrs. 42 to 45 rue part of Table 10. explained in the next paragraph.

TABLE 12-POWER EQUATIONS AND DATA FOR PLOTTING CIRCLE DIAGRAMS

Sending Circle Receiving Circle


Derived
From / Vector to Center, C, 1 Radius Vector Rse Vector to Center, CR Radius Vector RR0

ABC’D pY+jQs= 3&^ Y PR+jQR= -3&?- R +SE,E,dJ


Ref. Fig. 42 B B B
(204) (205)

Equiv. Pi f's +jQs = EB -iER&t+je PR +j&R = -3($+PR)%


Ref. Fig. 44

Imped. Form
Equiv. Pi Ps +jQs = -~R&&Ie PR +jQR =
Ilc+. Fig. 44 (207a)
(206a)
3(1 +iRP)E; 3EREsc+~e 3(1 fis3)E; + x&&de
Equiv. ? I'S +$A3 = - &t+jQ~ =
hf. Fig. 45 ia +iy + l%,is -iR+iS+t&& -i,+i,+i%& i~+iy+Pi~is
12081 (209)

Atlmitt,ancc Pz+jQ, = 3 ji*& +3Y,2E,Els+~e P, +jQl = 3 3,,E1 +3Y&,$e-je


Ref. Fig. 43
z (210) (211)
- -
321, -3.&ZELEZefle 3% p 3.&E,E, ,--lo
Impedance Pz+jQ,= - _ Ei: ^_ ^ PI +jQl = --+ ^
hf. Fig. 43 z,,z,, - g22 Zdn -z*2 i,,i,, -i,, 1 z,,z,, -z,2
(210a) (211a)

UNITS
Table gives P and Q in megawatts (mw)., and megavolt amperes (mva) for ER and Es in kv line-to-neutral, or it gives P and Q in watts
and volt-amperes for Es and ER in volts, lme-to-neutral.
‘~0 use volts or kv line-to-line, omit factor 3 throughout the tabulation.
Impedances and admittances are in ohms or mhos per phase, line-to-neutral.
0 is the angle of Err in advance of ER or the angle of E, in advance of El.
^ Symbol designating conjugate of a vector.
To DRAW CIRCLE DIAGRAM-FIG.~~
l. Calculate “vector to center” and locate center Cs or Ca.
” Cakuhte radius VCCtOr for 8=0 (do=&= 1). ‘Cd it f&30 or Rat.
3. Add 1 and 2 to obtain real and reactive power for sending and receiving voltages in phase.
Plot this as “Power for e =O” on the diagram. WRO =C~fRno. Wso =Cs+Rso.
4. Draw the circle through the ‘“Power for 8 =0” point. Draw the reference radius vector from the center to the “Power for fJ=O” point,
to serve as. the reference from which angles are measured.
5. Corresponding sending and receiving conditions are found at the same angle on the corresponding circles.
330 Steady-State Performance of Systems Including Methods of Network Solution Chapter 10

TABLE 12A---CONSTANTS FOR PLOTTING POWER CIRCLE DIAGRAMS


Refer Fig. 47
(I, m, l’, TTX’,TZ,6, are to be obtained from the relations given)

Receiving Circle Sending Circle Radius Position of Radius


Form of* Constants Vector for 0 =0
Constants Constant
System
Constants 1+jm l’+jm’ n 01,

A BCD d 6 1 h
T = tan-’ &, B = bl +jb,
Ref. Fig. 42 B B B

Equiv. Pi
tan-’ E, Z =r+jz
Ref. Fig. 44

Imped. Form
Equiv. Pi tan-’ f, Z = r +jx
Ref. Fig. 4-L

tall--i ;
Equiv. T 1+8,3 1 +i,P 1 2
Ref. Fig. 45 i,+i,+Pi,i, i,+is+E;i,is ZR +zs + YZRZS where
ZR+ZS+YZRZS =b,+jb,
*For admittance and impedance convtants the reference direction is into the network at both ends. Thus the receiving circle is in the same quadrant as the sending
circle and the 1 and m constants do not apply. Use the method of Table 12 for plotting the circles in this case.

Construction of power circles.-For the occasional from an upward vertical radius by the angle, &,. See
user it is convenient to list directly the coordinates of the Fig. 47.
centers and the radii of the circles, together with the Corresponding sending and receiving conditions are
location of the reference line from which angles are to be found at the same angle 0 on the two corresponding circles.
measured. For this purpose the six constants 1, m, n, OI,, An alternative method of construction is listed in the
1’ and m’ are defined and used. When working with ABCD five steps under Table 12, which eliminates the necessity of
constants these have the definitions:- measuring angles. An “initial radius vector for 0 =0” is
added to the “vector to the center” to get the coordinates
1
-=n (213) of a point (i.e. the vector power) corresponding to 0=0.
B This fixes both the radius and the reference line for
6, = tan-l % where B = bl+jbz measuring angles.
(214)
2 Power-Angle Diagrams-From the circle diagram the
A power expressions as a function of angle can be written
z=lfjm (215) directly. They are, for three-phase power in kw on kvar,
and voltages in kv, L-L;-
I3 --
jij = l’+jm’. cw
Ps=l’~~+nEaES sin (&&,) (217)
For other forms of expression of the transmission network Qs = m’Ei -nERES cos (e- 6,) (218)
--
the definitions of these six constants are given in Table PR= -li?i+nERES sin (oft&) (219)
12x. --
QR= -mEi+nEREs cos (0+&J (220)
Having defined these six constants, the circles can be
constructed as follows. Refer to Fig. 47. The scales used Power plotted vertically against 0 plotted horizontally
for kw and reactive kva must be the same. Line-to-line is thus a displaced sine wave known as a power angle dia-
voltages are used, giving three-phase kw and reactive kva. gram. Its use in stability calculations is described in
If line-to-neutral voltages are used to determine the cen- Chapter 13.
ters and radii of sending and receiving circles, the ex- Use of Equations vs. Circle Diagrams-If only
pressions in Fig. 47 must be multiplied by three. one condition were of interest, for which the voltages
Center of sending circle is at --1’ Es2 kw, m’ ES’ kvar. and intervening angle were known, the sending and re-
Radius of sending circle is nEREs. ceiving power quantities could be calculated directly,
The reference line for angles in the sending circle is clock- using the power expressions of Table 12. However,
wise from a downward vertical radius by the angle, &,. if the power transmitted is to be determined for a
See Fig. 46, Angles 0 of sending-end voltage in advance of number of angular positions, as in stability studies, the
receiving-end voltage, are measured ccw from this refer- circle diagram is advantageous. Also if the voltages and
ence line. power are known and the angle and reactive requirements
Center of the receiving circle is at --li?a2 kw, -rni?R’ are to be determined the circle diagram becomes indis-i
kvar. -- pensable. More particularly a diagram having several;
Radius of the receiving circle is nEREs. circles corresponding to different voltages constitutes a
The reference line for angles in the receiving circle is cw chart of the real and reactive powers that can be tram?-’
.‘T
4I
Chapter 10 Steady-State Performance of Systems Including Methods of Network Solution

EQUIV. PI OF NETWORK

IMPEDANCE IN OHMS ON 110 KV BASE

SENDING
49.9 + j 153.6 CIRCLE
FOR
Es=116 KV
EA = II0 KV

RADIUS VECTOR

90 MILES IIO-KV LINE WITH


[IO 000+ j5000) KVA LOAD AT CENTER

‘VECTOR TO CENTER

MW

REAL POWER

RECEIVING
CIRCLE
FOR
E s :I16 KV
i.q =I10 KV

6 = ANGLE OF E,
IN ADVANCE OF E,

E, -110 KV

Fig. 47-Power circle diagram for line AED Fig. 48 and used for example of plotting diagram.
332 Steady-State Performance of Systems I &uding Methods of Network Solution Chapter 10

mitted for various voltages and angles. As such it finds


extensive use both in system operation and design.
Interpretation of Power Circle Diagrams-Power
circle diagrams for a particular system are given in Fig.
47. They have been drawn in accordance with the in-
structions at the bottom of Table 12. Likewise their con-
struction from the six constants 1, m, n, &,, I’, n’, given in
Table 12A is indicated. This system consists of ninety
miles of IlO-kv line with a load of 10 000 kw and 5000
lagging reactive kva tapped on at the middle. The load Fig. 48-Ideal phase shift transformation.
is treated as a fixed impedance. Points p and p’ convey
the following information, “With a receiver voltage of 110
phase shift factor is removed from the equivalent single-
kv and a sending voltage 116 kv, if 34 000 kw (34 mega-
phase circuit before calculating the ABCD constants so
watts) are supplied at the sending end, then 500 leading
that Eq. (221) is applicable.
reactive kva must be supplied at the sending end and
Admittance Constants (or Driving Point and
20 000 kw and 9000 leading reactive kva will be delivered
Transfer Admittances) are coefficients of the network
at the receiving end. That is, 9000 kva of lagging reactive
current equations.
must be supplied at the receiving end. 13 500 kw and 8500
reactive kva will be consumed in the system, including II = Y&+ Yw’h (222)
line losses and reactive plus the intermediate load. In- I? = Yz,E& YnE, (223)
cidentally the sending-end voltage is only 20 degrees ahead
of the receiving-end voltage and the operation will there- AS indicated in Fig. 43 the positive direction is taken
fore be stablet.” Obviously contained in this informa- into the network at both ends. This permits ready ex-
tion are the answers to a variety of questions that might tension to more than two terminals. In the following
be asked. definitions current in a terminal is understood to be in
ABCD Constants are coefficients of the current and the positive direction unless otherwise stated. The defi-
voltage equations (201a) to (201d) given in Table 11. nitions indicate the extension to more than two ter-
They apply to the transmission-type network having minals. In general:
sending-end and receiving-end terminals, and have the Yn is the current in terminal 1 per volt applied at ter-
following physical significance. minal 1 with all other terminals short circuited.
A is t,he voltage impressed at the sending end per volt Ylz is the current in terminal 2 per volt applied at ter-
at the open-circuited receiver. It is a dimensionless volt- minal 1 with all other emfs short circuited, or vice
age ratio. versa. It will usually be negative for transmission-
B is the voltage impressed at the sending end per am- type systems with positive direction into network
pere in the short-circuited receiver. It is the transfer at both ends, etc.
impedance used in network theory. It is also equal to The power equations as obtained from (222) and (223)
the voltage impressed at the receiving end per ampere are :
in the short-circuited sending terminals. Pl+jQ, =&1^1= Pm%&+ ~,,E,-& (224)
C is the current in amperes into the sending end per
PdjQ2 = Et72 = P&P%+ ~&d% (225)
volt on the open-circuited receiver. It has the dimen-
sions of admittance. For a Three-Terminal System (as in a three-machine
D is the current in amperes into the sending end per problem) the current equations are:
ampere in the short-circuited receiver. It is a dimen-
I1 = YllEl + Y2lE2+ Y31E3 (226)
sionless current ratio.
Table 9 gives the ABCD constants for many types of Iz = YlzEl+ YzEz+ Y,,E, (227)
networks. Table 10 gives the transformations to Pi, T, I, = Y&+ Y23E2 + Yd3~ (228)
admittance and impedance forms. Chap. 9 illustrates
the use of ABCD constants in a stability example. The corresponding power equations are:
For passive networks, as dealt with here, Pl+iQ, = Elf1 = ~~lEl~l+ ~wSJ%+ Ed& (2264
AD-BC=1 (221) P&j&, = Ezfz = P,,E,i%+ Y&&+ ~32&i% (227a)
This affords a valuable check on the calculations. If the P3+jQ3 = E3f3 = P,,E,i!$+ Pz3E3&+ pS,E,8, (228a)
single-phase network used involves phase shift, it is not The extension to more than three terminals is apparent.
strictly passive. A case in point is an ideal phase-shift Self and Mutual Impedances are coefficients of the
transformer Fig. 48. As shown AD-BC is numerically network voltage equations given generally in Eqs. (52)-
one but includes a double angle term. This single-phase (55). Writing these for the transmission-type network,
representation of a three phase transformer receives which can in general be reduced to a number of meshes
power at one time phase and passes it on at another time equal to the number of significant terminals:
phase, although the total power flow is continuous in
the three-phase transformer it represents. Usually the El = ZlJl + ZZlI2 (229)
1Referto Chap. 13 for criteria of stability. Ez=ZJ~+ZzIx (230)
Chapter IO Steady-State Performance of Systems Including Methods of Network Solution 333

Zll is the voltage in terminal 1 per ampere in terminal 1,


with all other “significant terminals” open circuited.
zrZ is the voltage in terminal 2 per ampere in terminal 1,
with all other “significant terminals” open circuited.
Etc.
SOTIC that the self and mutual impedances Zll and Z12 as
,l&etl and used in Section 13 and in this Section 21, differ from
tllc self and mutual drop constants defined and used in Section
20. The Z with double subscript is used in each caseto conform
with accepted terminology.
The power equations are obtained from (229) and (230).
P1-t.m = EJ1= z*,~,t,+2*1IJ1 (231)
P,fjC~?=E,P2=z,,r,~~+z,,I,l, (232)
For a three-terminal system the voltage and power
c(ll~ations arc given below. The extension of admittance
01 impedance constants to any number of terminals is
apparent.
El = 211~1+22112+231~3 (233)
Ez = Z,J~+Zd~+Z~J~ (2%
E, = Zd~+&J~+&I3 (235)
Fig. 49-Network of Fig. 2 reduced to an equivalent Pi for each
PI+& = E,I^l = Z,,Z,r^,+Z2?11271+23113P1 (236) line.
P,+& = E,lz = Z,,I,f,+Z?21?~~++23213~~ (237)
Px+.&?x= Eafs= Z,,r,f,+Z,,l,f,+Z,,r,f, Case Ib.
(238)
Given: 1. Received kw and reactive kva.
2. Receiving-end voltage.
IV. REAL AND REACTIVE POWER FLOW To Find: 1. Sending-end voltage.
2. Sending-end kw and reactive kva.
It is well known that in a system in which impedances
3. Required generation at sending end.
xc largely reactive, real power flow is controlled by phase
4. Losses.
angles and reactive flow by voltage magnitudes. Ordi-
narily the adjustments of real power flow are made by II. Three generating stations along one main intercon-
throttle or gate adjustments (governor settings), although nection. no closed loops, intermediate substation. A,
the flow in a closed loop can be controlled by a regulating B, C, 0; Fig. 1.
transformer capable of introducing a phase shift. Similarly Case IIa.
reactive flow is usually controlled by generator field ad- Given: 1. Voltages at all but D.
justment (regulator setting) but in a closed loop, trans- 2. Real power flow.
former tap adjustments can be utilized. To Find: 1. Remaining Power Quantities.
Quantitatively the real and reactive power over a trans- 2. Voltage at D to hold stated voltage at in-
mission circuit or interconnection can be determined from termediate Substation C.
the power circle diagrams. These diagrams give the real Case IIb.
and reactive power at the sending and receiving ends of an Given: 1. Voltages at all but intermediate substa-
interconnecting line or network, in terms of the voltages at tion C.
tlic two ends and the angle between them. The method 2. Real power flow.
fill be explained by examples, starting with a simple two- 3. Load at C, real and reactive.
station system with an interconnection, and covering in To Find: 1. Remaining power quantities.
all, the following conditions: 2. Voltage at intermediate substation C.
22. Examples of Real and Reactive Power Flow. III. Closed Loop System.
Refer to Fig. I, or the equivalent network Fig. 49. Case IIIa. Find voltage to close under given load and
I. Two Stations with Interconnection (Station A to power flow conditions. (To determine regulator require-
station B). ments.)
Case Ia. Case IIIb. Find power which flows if loop is closed and
Given : 1. Sending-end and Receiving-end Voltages. flow held constant in rest of the loop.
2. Received Power. Case I. Two-Source System-Stations A and B, Fig.
To Find: 1. Received reactive kva. 1, and the 50-mile line connecting them, will be used for
2. Transmitted kw and reactive kva. illustration. The remainder of the system shown will be
3. Required kw and reactive kva to be sup- considered as disconnected. It may be desired to find the
plied by generators at each end. required voltages of the A and B buses, and the angle be-
4. Losses (kw and reactive kva). tween them, to transmit a desired real and reactive power.
334 Steady-State Performance of Systems Including Methods of Network Solution Chapter 10

Or it may be necessary to find what real and reactive cuit method because they can more clearly visualize the
polvei- can be transmitted for different voltages and angles. problem by this method. As a result both methods are used
In either case the power circle diagram is an ideal method and some examples of both methods will bc given. The
of espressing the performance of the interconnection. Two stability problem of Chap. 13 is treated exclusively by the
cases will be considered illustrative of the two forms in method of ABCD constants. This polver flow problem ha
which the problem may appear. been treated by the equivalent circuit method.
Cuse la. Two Station System, ,4 and B. See Fig. 49.
Reducing the :Vclwork
Fixed. Voltages and receiver real power.
Sending end Station ~4 The first step is the reduction of the network between
Receiving end Station B A and B, Fig. 2, to an equivalent Pi, shown in Fig. 49. As
the equivalent circuits between other buses will be needed
The given conditions are: in subsequent cases, they also must be obtained. I\ typical
Sending-end voltage E’s=110 kv L-L reduction follows for the section from ~1 to B, the steps
Receiving-end voltage &=llo kv L-L being shown in Fig. 50.
Received power 20 Megawatts Convert the T netlvork a, 0, and c to an equivalent Pi
Load at A 10 000 kw, 6200 lagging reactive kva using Eqs. (105.)-(107).
(lO.O+jG.2) mva
Load at B 50 000 kw, 37 500 lagging reactive kva Z,= 2.82fj32.3
(5O.O+j37.5) mvn Zb = 24.05+j43.05
Z,= - jSOO0
It is required to find the real and reactive power that
Zs’=Z,,=Z:,+Z,+Z,Z,/Z~
must be generated at Stations A and B. This requires
=2158-j12 778
determination of the reactive power received from the
M=Zlrc=Z,,+Zc+Z~Z,/Z,
line, and the real and reactive power at the input end.
= -4940 -jlS 050
From the line power quantities and the local loads, the
Z=z,b=z:,+zh+z,Zb/z,
required kw and wattless generation can be determined.
= 2fii(3+ji5.19
General Comments
Parallel ill and iV to obtain Za’
This is a characteristic problem of transmitting between
buses whose voltages are fixed by load requirements.
Wattless capacity in condensers or generators must be
&‘= .!!I
ilrliv
___
+N
= - 418 -j5700
available at the proper locations because the fixed voltages
Plotting the Circle Diagram
determine the ivattless flow over the line.
Tap-changing-under-load transformers permit main- From the constants Zs’, Z, Za’ of the equivalent Pi, the
taining the generator bus voltage while raising the effective data for plotting the pomer circle diagrams for line AB
sending-end voltage to transmit wattless. No-load taps can be obtained, using Eqs. (20Ga) and (20ia) of Table
can be used to a rather limited extent if the power flow is 12. In the folloGng calculations Es and ,%‘I<are expressed
in one direction with not too much variation from maxi- in kv, line-to-line which gives the power, calculated as
mum to minimum. E2/Z, in the dimensions of megavolt amperes; that is,
This problem is often further complicated by the fact megawatts (mlv) and reactive megavolt-amperes (reactive
that the load bus voltage must be scheduled during the mva). With the power* calculated as PfjQ = El, the ASA
day, being somewhat more under heavy load conditions. standard, a positive value of Q indicates lagging reactive
The stability of the interconnection is not investigated power in the chosen reference direction for 1.
in this chapter: Refer to Chap. 13 for examples of stability Sending-end Circle-from equivalent Pi in impedance
determinations. form
Es=110 kv, I?.&= 110 kv
Obtaining the Circle Diagram Center
The method of obtaining the impedance diagram, Fig. cs= i+& .E;
2, from the single-line diagram, Fig. 1 has already been ( s)
described in Sec. 3 and 4. To obtain the circle diagram =50.9930+j141.9209
from the impedance network from A to B two general
methods of approach can be used. The intervening net- Radius vector for 8=0
mork can be reduced to an equivalent Pi and the circle dia- Rso= 29
gram determined therefrom as shown in Table 12. Or
A BCD constants can be written for the sections of the in- = - 50.8369 -j142.8429
terconnection, from Table 9. These can then be combined Power for 19= 0
to obtain ABCD constants for the complete interconnec-
tion as shown also in Table 9. The circle diagram data can Wso=Cs+Rso
then be determined from the overall ABCD constants, =0.1561 -jo.9220
using the formulas of Tables 12 or 12a. Some prefer the The sending circle has been drawn in Fig. 51 by plotting
ABED constants because the method is systematic, and the center, the power for 8=0, and drawing the circle
has a check for each step. Others prefer the equivalent cir- *The term power is usedgenerally meaningreal and reactive power.
Chapter 10 Steady-State Performance of Systems Including Methods of Network Solution

2.82+j32.3 24.05+j43.05
A00 08

-j8000 -jSOOO
T T

26.76+i75.19

8=0, E,=E,=IIOKV
* *
Fig. 50-Steps in the reduction of line AB to an equivalent Pi.

through the latter point. The sending power for any


:tnglc, of Es in advance of Ea, is a point on the circle, an
angle 19counter-clockwise from the radius for 0 = 0.
Receiving-end Circle-from equivalent Pi in imped-
ancc form.
Es= 110 kv, &=llO kv
Center Fig. Jl-Power circle diagram for line AB.

The local loads at A and B are respectively: (See Fig. 1)


= -50.6821 -j140.7363
PLA+~QLA= lOfj6.2 mva
Radius for f?= 0 -- PLB +jQ,, = 50 fj37.5 mva
RROA2
z The required generation at A is therefore:
= 50.8369+3’142.8429 PG~+~QGA=PLA+~QLA+PsA+~QsA
Power for 0=0 = 31 -jO.S mva
WRO=CR+RRO or 31 mw and 0.8 lagging reactive mva. i.e., underexcited.
=0.1548+j2.1066 The required generation at B is
The receiving circle is located in a similar manner to the PGB+~QGB=PLB+~QLB-(PRB+~QRB)
scncling circle. The receiving power for any angle 8, of Ea =3O+j44.5 mva
in advance of ER, is a point on the circle an angle 0 clock-
\\-& from the radius for 0 =O. The corresponding sending or 30 mm and 44.5 lagging reactive mva.
and receiving power for a given transmission condition The line losses are:
over the line, are points on the two circles for the same P~+j&~=Ps+j&s-(PR+~&R)
angle 8. = 1+jO mva
Interpreting the Circle Diagram For the or 1 mw and no reactive mva.
Particular Problem-Case la. The 12X~ lagging reactive power consumed by the line
is balanced by the E2/Xc leading reactive power consumed
From the conditions of the problem, the received power
by its shunt capacity.
is 26 mw which is found at point 1, on the receiving circle,
For accurate values of losses, PR+~QR and Ps+jQs can
Pig. 51. Laying off the same angle 8, on the sending circle,
be calculated for the angle fI involved. Transformer iron
the point 1, is located giving the corresponding real and
losses must also be added.
reactive power at the sending-end.
From this example it can be seen that if a particular
PsA+j&SA=21.0-j7.0 mva kilowatt load is transmitted over a line with fixed terminal
PRn+jQRB = 20.0 --j7.0 rnva voltages, the input and output reactive power quantities
336 Steady-State Performance of Systems Including Methods of Network Solution Chapter 10

are determined by the line, and must be provided for in P,+j&,=Ps.l+j&s.~-(p~~+jQ~~)


the machines at each end. = 1.5+jO.S
CaseIb, Two-Slation Syslem, -4 and B, Fig. 1. Fixed re- or 1.5 mm and 0.5 lagging reactive mva.
ceiver voltage and real and reactive power.
The required sending-end voltage of 124 kv could be
Sending end Station A
provided by a step up transformer at A having a rated high
Receiving end Station B
voltage of 115 kv and equipped with f 10 percent tap-
The given conditions are; changing-under-load equipment, giving it a range of from
Reccving-end voltage En = 110 kv, L-L 126.5 kv down to 104.5 kv. This would provide for tram+
Received power (20fjl5) mva, or 20 mw, 15 lagging mitting only a reduced load in the reverse direction unless
reactive mva. the transformer at B were similarly equipped.
Load at A (lO+jS.Z) mva. This problem illustrates that to transmit a desired
Load at B (5O+j37.5) mva. amount of wattless as well as real power over a line with
To be determined: fixed receiver voltage, the sending voltage must be under
Sending-end voltage. control of the operator or automatic means, since the re-
Sending-end real and reactive power. quired value depends on the wattless to be transmitted.
Line Losses Case II. Three Generating Stations Along One Main
Generation required at sending end. (The generation Interconnection, and Intermediate Substation-
at B must obviously be 3O+j22.5 mva.) The methods used in analyzing a two-station system can
Receiving-End Circle (Refer to Fig. 51) be easily extended to a multi-station system in Tvhich the
The center of the receiver circle is the same as deter- stations are all connected along one main transmission
mined in Case Ia since the receiver voitage is again, 110 channel. Such a system is illustrated for example by Fig.
kv. The received power, (2O+jl5) mva is plotted as point 1 and Fig. 49 with line AED omitted. Because in this case
2a on the diagram. The receiver circle passes through power can flow over only one path, any two stations and
point 2a. Scaling or calculating the radius to this point it the line connecting them can be treated as a two-station
is found to be &= 171 mva, scalar--value. But the scalar system, independent of the other stations and lines. For
ERES instance, the system of Fig. 1 with line AED omitted
value from Eq. (207a), Table 12 is --=- Whence solving merely adds more stations and lines to the two-station sys-
z *
for the sending voltage tem of Example I, and part AB can be solved as before.
-- Besides the addition of another generating station, the
E =J$-Q71X79.3=124 kv new system has the added complication of a substation
’ ER 110 between stations B and D. Since there are no generators
Sending-End Circle. at C to maintain the voltage, the voltage on the substa-
Es = 124 kv, &= 110 kv tion bus is determined by the voltages at the adjacent sta-
tions and by the real and reactive kva load on the substa-
Center, CS tion bus.
The vector to the center for 110 kv has previously been There are in general two problems concerning the volt-
drawn. Increase it in the ratio (124/110)* to obtain the age at an intermediate substation such as C. First, the
new center for 124 kv. voltage at one of the adjacent stations may be fixed, and
Radius Vector for 0=0, Rso it is desired to maintain a given voltage at the substation
The radius vector for 8 = 0, for ,??a= 110 kv, and Es = 110 by varying the voltage at the other generating station.
kv has previously been obtained. Increase it in the ratio The problem is then to find the generating-station voltage
(110X 124)/(110X 110) to obtain the new radius vector and determine the power and kva flow in both lines. This
at 8=0 for Es=124 kv, Ea=llO kv. problem can be solved by setting up a circle diagram for
Power for 8=0 the line from the substation to the fixed-voltage station
and determining the kva flow. This kva is subtracted from
Wso = Cs+Rso =7.4916+j19.3214
the load on the substation to give the kva that must be
From the center and power at 8=0 the new sending furnished by the other line. Using this kva, the circle dia-
power circle can be drawn. The received power point 2a gram for the other line can be set up and the desired gen-
occurs at the angle 0,. Laying off BZ along the sending erating bus voltage can be found as in the case Ib just pre-
circle the sending power point 2s is located. Thus: ceding.
PsA+j&sA=21.5+j15.5 mva Second, the voltage at both generating stations may be
fixed, together with the real power flow over each line sec-
And since the load at A is tion, and the voltage at the substation must be deter-
Pu+&A = lO+j6.2 mva mined. This can be done by a cut-and-try process, using
The required generation is: the circle diagrams of the two lines and varying the sub-
station voltage until the sum of the reactive kva’s trans-
P~A+~QGA=PsA+~QsA+PLA+~QLA mitted to the substation is equal to that required by the
=31.5+j21.7 mva substation load.
or 31.5 mw and 21.7 lagging reactive mva Each of these two operating conditions will be illustrated
The losses are: in the following example.
Chapter IO Steady-State Performance of Systems Includin,g Methods of Network Solution

c’mc IIn. Multistation System with Intermediate Substa-


tion--No Closed Loops-Fixed S&station Voltage
Sending End ReceivingEnd
Line AU A B
Line BC B C
Lint DC D C
‘lllc given conditions arc as follows, line AB being as-
,~,nncd to operate under the same conditions as case Ib.
Generated = 31.5Sj21.7 mva
Load = 10 +j6.2 mva
Transmitted = 21.5+j15.5 mva
Voltage = 124 kv.
Load = 50 +j37.5 mva
Received over ,4B = 20 +jl5 mva
Transmitted over BC= G.O+j? mva
Generated = 36+j?mva
Voltage =llO kv
Load = 18.3+ji.O mva
Voltage = 108 kv
Load = lO.O+j7.0 mva
‘To bc determined:
Transmitted reactive over BC
Generated Reactive
Received P+jQ over BC
POINTS I Et2 CORRESPOND
Received P+jQ over DC POINTS 384 CORRESPOND
Voltage
Transmitted P+jQ ltjj+H++-ll20{ / i / 1
Generated P+jQ
RE’CEIViNG II I I I
Solution : CIRCLE CIRCLE DIAGRAM
_ ,6o FOR LINE B-C
Line RC, sending circle (B) for Es = 110 kv, En = 108 kv (Cl
Center (Refer to Fig. 52)
Em’108 KV /

Radius vector for 0=0 Fig. 52-Power circle diagram for line BC.
&, = wERES
-= -33.5978-$99.5234
2 Line DC, Receiving Circle (C) for ER= 108 kv, Es =?
Power for 0 = 0 Refer to Fig. 53.
lvso = CS+ Rso = 0.6222fjl.2652 (Point 5,_Fig. 52) Center CR=-;&+ E;
1Ae BC, Receiving Circle (C) for Es = 110 kv En = 108 kv ( R)
Center = -26.27321j142.2751
The received power over line DC can be determined
Load at C= 18.3fj7.0 mva
Received over BC = 6.O+j.5.0 mva
Radius for 0 = o Received over DC=12.3+j2.0, which is plotted as
point 1 of Fig. 53.
Scaling from the center to this point the radius of the
=33.5978+3’199.5234=202.3324 receiving circle is found to be 147.9 mva, from which
we can solve for Es. --
Power for 8 = 0
?VRo = CRfRno =O.SlOS+j5.9698 BR = 147.9= E+-
--- 108ES
z 80.1
Line BC circles are plotted in Fig. 52 from these data,
the section near the origin being enlarged. From the send- E =147.9X80.1
S = 110 kv
ing circle the transmitted power of 6 mm is accompanied 108
by transmitted lagging reactive power of 0.6 mva (Point Line DC, sending circle (D) for Es = 110 kv, ,I&= 108 kv
2, Pig. 52). From the receiving circle, for the same angle Center
01,the received power at C is found to be 6.O+j5.0 mva,
as closely as the chart can be read (Point 1, Fig. 52).
338 Steady-Stale Performance of Systems Including Methods of Network Solution Chapter 10

Case IIb. Multistafion Sysfem with Intermediate Substa-


tion-No Closed Loops-Substation Voltage lo Be De-
termined
-S Ii t 1 1160 !? - I
The generating-station voltage magnitudes are assumed
to be fixed. As the methods of combining loads and of de-
termining losses are simple and have been outlined in the
previous cases, this case is confined simply to determining
the voltage of the intermediate subst,ation and the reactive
power flow over the lines. The real power flow is assumed.
Given :
Voltage at B= 110 kv
Voltage at D = 116 kv
At C
Load at C 18.3+j7.0 mva
Received over BC G.O+j? mvn
Received over DC 12.3+j? mva
To be determined:
At B Transmitted power over BC
At C Voltage
I
POINTS I82 CORRESPOND
I I II
Received reactive over each line
POINTS 3 Et4 CORRESPOND At D Transmitted power over DC.
A cut-and-try method is employed, based on assuming
values of voltage at C until a value is found that results
in a total received reactive power equal to the reactive load
at C (+j7.0 mva). Obviously after a few trials a curve of
received reactive power versus voltage-at-C can be plotted
and the proper voltage read from this curve. Or after two
trials the increment of reactive per increment in voltage
Fig. 53-Power circle diagram for line CD. noted, so that the third trial is simply a check. Assume, to
start with, a voltage of 109 kv at C. Circle centers and
= 20.9354+j146.2781 mw. radii can be found by ratioing from values calculated in
Case IIa.** Refer to Table 13.
Radius vector for 0=0 The second trial gives a sufficiently close value of total
&)=-~%& reactive (fj6.2 mva compared with the desiredfj7.0
z mva) and the circles corresponding to this trial are used to
= -220.6011 -j146.6527 mw. determine the power quantities. Thus, drawing the cor-
Power for 8=0
responding sending circles, and using points 3 and 4 on
Fig. 52 and 3 and 4 on Fig. 53.
IVSO= CS+ Rs” = 0.3343 -jO.3746 mm.
The sending circle can now be plotted and laying off the
At B Transmitted over BC 6 -j5.2
angle f$, the same as for the receiving circle the sending-end At C Voltage is 111 kv
power is found to be 12.4-j1.8 mva, at point 2. Received over BC 6 -jO.5
Now recapitulating, Received over DC 12.3fj6.7
At B Transmitted over BC 6.O+jO.6 mva Load Assumed 18.3 fj7.0
Generation otherwise required 3O.O+j22.5 mva At D Transmitted over DC 12.3+j2.5
Generation required 36.O+j23.1 mva
At C Received over BC 6.O+j5.0 mva **Obtaining Circle Centers and Radii by Ratioing-General:
Received over DC 12.3+j2.0 mva
In working graphically, after one sending and receiving circle ’
have been drawn for a given intervening network, all further :
Load at C 18.3+j7.0 mva work can be done by simple scalar ratios and graphical con-. ’
Losses in line BC* 0 -j4.4 mva struction using the following relationships.
or 0 mw and -4.4 lagging reactive mva, i.e., 4.4 lagging
a. The center of a receiving circle is always along the same
reactive mva is supplied net by the line.
line through the origin, the distance to the origin being
At D Transmitted over DC = 12.4-j1.8 mva proportional to Ei.
Load at D = lO.O+j7.0 mva
b. The center of a sending circle is always along the same
Generation at D = 22.4+j5.2 mva line through the origin (not necessarily the same as in a)
Losses in line DC=O.l -j3.8 mva* or
the distance to the origin being proportional to E&
0.1 mw and -3.8 lagging reactive mva.
C. The scalar value of the radius is proportional to Es I&.
‘See divcrrssionof losses in case la. d. The radius for 0 = 0 is always parallel to the first one drawn.
Chapter 10 Steady-State Performance of Systems Including Methods of Network Solution 339

TABLE 13
Case IIa Case IIb, Trial 1 Case TIb, Trial 2
-
l{C Receiving Circle, (C)
110 110 110
2 &= 108 109 111

3 - 32.99-j193.55 - 33.60-j197.15 - 3-k.%-j204.45


&‘%
4 Radius for 0~0, RRO=B = 33. SO+jl99.52 33.9 fj201.37 34.53 4j205.06

5 Power for 0 =o, TVRO= CK+ko = *................. 0.31+j 4.22 - 0.32+ j0.61
6 Reactive corrcs. to 6 mw, from circle .................. +j 3.2 -j 0.5
[I(,’ Receiving Circle, (C)
7 Es= 110 116 116
s &= 108 109 111
9 Center, CR= -(j+-&jEf= - 20.27-j142.27 - 20.65-j144.92 - 21.42-j150.25

10 Radius for 0 =O, ZZno=F = 20.60 +j146.65 21.93+j156.08 22.33+jl5S.95


D
11 Power for 8 =O, WRO = CR +RRO . .._...__._,._.... 1.34fj 11.16 0.98+-j 8.67
12 Reactive corres. to 12.3 mw, from circle . . . . . . . . . .._...... +j 9.3 +j 6.7
13 Reactive received at C, Sum of 6 and 12 .. .. . . +j 12.5 +j 6.2

Case III. Loop System, Three Generating Stations, Case Illa. Loop System, Given Power Flow, Find Voltage
TWOIntermediate Substations, Fig. I*-Powerflowin Across Open Point
the complete loop system of Fig. l* is next considered. A
method for calculating the effect of a regulator for con- Given Conditions.
trolling phase angle and voltage ratio is given. This meth- For the system external to line AD we shall use the
od in general consists of breaking the system at one voltages and power flow conditions described in Fig. 54
point and treating it as several stations along one line up which have been arrived at:
to the point of closing. The voltage required to close the For line AB from case Ia, Circle Fig. 51.
loop can then be determined and also the circulating For line BD from case IIb, Circle Figs 52 and 53.
current that flows if the loop is closed without this Load at E = lO.O+j5.0.
voltage. Voltage at E will be taken as 111 kv for converting loads
The simpler problem is to calculate the voltage required to impedances.
to close the loop for a given power flow condition, as this
is simply an extension of Case II, above. The voltage re- Required to Find.
quired to close the loop gives the necessary setting of a The voltage between A and A’.
regulating device to produce the assumed power flow. There are a number of ways to go about this problem.
It must be remembered that up to the point of closing
t)hc loop there is complete and independent control of real
and reactive power flow over each line section connecting
two generating stations. This assumes that permissible
voltage or stability limits are not exceeded. For example,
the generator voltages and throttles at A and B can be set
to produce a desired real and reactive power over this line.
Then holding the voltage and speed at B fixed, so as not to
affect the flow over line AB, the generator voltage and
throttle at D can be adjusted to give the desired flow in the
BD section. Now if the voltages and speeds are held fixed
at A, R, and D by suitable adjustments at those points,
then the connection of a line from D to E and the passage
of any amount of power over it under the control of a
regulator in the line will have no effect on that part of the
loop external to line AD.
Thus the problem reduces to a consideration of the flow
in the section A to D only when the magnitudes and phase
positions of the voltages at those two points have been
Previously fixed by the required conditions elsewhere in
the loop.
*Fig. 49 also shows the system except for loads. Fig. 54-Power flow condition for Case IIIa.
340 Steady-State Performance of Systems Including Methods of Network Solution Chapter 10

The one selected involves the following steps: c. The voltage at -4’ is:
a. Assume a voltage at E and determine the power con- ,4
sumed by the open line. Add this to the load at E to Ea’=E “’ 9
EZfZs’
obtain the total load received over line DE. 113.5(2158-j12 778)
b. Find the voltage at E at which this load can be re- =26.76+j75.19+2158-jl2 778
ceived. = 114.18-jO.4Oi= 114.2 kv.
c. Determine the voltage at A’, and the angle between Taking Ea= 110~”
it and the voltngc at A. Angle of A in advance of R, Case Ia, = eaa = 8.15”
Proceeding with the calculations in this sequence: Angle of B in advance of C, Case IIb, =&o = 1.76”
Angle of D in advance of C, Case IIb, = t&,o=4.14’
a. The input power at E to the open-ended line EA’ is Angle of D in advance of E, Case IIIa, = BnE= 3.23”
obtained from the impedances, Fig. 49. Angle of A’ in advance of E, Case IIIa, = BdE= 0.17”
ps+jQs-
EI e Angle of A in advance of A’ =edA
is’ Zf2R’ e.:A=t)AD+eRC-eDC+~DE-eiE=8.830
Thus, since EA= 110 kv and EA’= 114.2 kv
3
“:
:
1112 1112
= -418+j5700f215S+j12 700
= 0.0049--j3.0877 mva
Load at E = lO.O+j5.0 mva and a regulator having a setting such as to result in a :;
Open line EA’ = O.O-j3.1 mva vector ratio of .I
Power received from DE = lO.O+j1.9 mva 1:0.963 &8~330
b. The circle diagram for line DE is given in Fig. 55. closes the loop with the power flow as indicated. For any
By trial it is found that with a receiver voltage at other desired power flow in the various sections of the
E of 113.5 kv the received power is lO.O+jl.9 mva loop the requisite regulator setting can be similarly cal- :,
as clesired and the corresponding sending power at culated. Thus by taking the extreme conditions of flow 7:
1) is 10.0 -jO.5, within the accuracy of the graphical one way and then the other, the range required of the :’
construction. regulator can be determined.
CaseIIIb. Loop ClosedWithout Regulator
Given Conditions.
The load E, for simplicity is converted to an impedance
on 111 kv base.
Voltage at A = 110 kv
Voltage at D = 116 kv
Angle of D in advance of A = - 5.77”
To Be Determined.
Power flow in Line AD.
With the conditions stated as above the problem is easily
solved by determining the circle diagram for the complete
line AD. The load impedance at E is shown on Fig. 56
together with the reduction to an equivalent Pi. The circle

FOR LINE D-E

Fig. 55-Power circle diagram for line DE. Fig. 56-Reduction of line AD.
Chapter 10 Steady-State Performance of Systems Including Methods of Network Solution 341

diagram for the line DA is given in Fig. 47. Using the REFERENCES
given voltages and angle it is found that 1. “Network Theorems,” Electrical Engineers Handbook, by Harold
power transmitted at D over DL4 = - l.Ofj6.5 Pender and Knox LIcTlwain, Vol. V., Communication and Elcc-
Power received at A over DA = - 11fj6.2 tronics, Section 3, Art. 6, pp. 3-11.
2. “Thevenin’s Theorem,” by E. L. Harder, Electric Journal, Vol.
From the circle diagram of a line connecting two points 35, No. 10, p. 397, October 1938.
of known voltage and phase angle the effect of a regulator 3. “Power Supply for Main Line Railway Electrification,” by E. I,.
Harder and P. A. hlcGee, ?‘ransaclions AIEE, Vol. 52, No. 2,
at one end can be determined by multiplying the voltage
p. 364.
at that end by the vector ratio of the regulator and using 4. ‘LAnnlyticnl Solution of Networks,” by R. D. Evans, Electric
the value thus obtained as t,he voltage at that end of the Journal, Vol. 20, No. 4, p. 149, April 1924, and No. 5, p. 107,
line. 1May 1924.
It is hoped, that while it has not been possible to cover 5. Symmelrical Components, by C. F. Wagner and R. D. Evans
all conditions, a study of the methods used in the cases (a book), &lcGraw-Hill Book Company, Inc., New York, 1933.
given will point the may to the solution of most other cases. 6. “Circuit Diagram for Transmission Line,” by R. D. Evans and
H. K. Sels, The Electric Journal Dec. 1921, pp. 530-536 and Feb.
1922, pp. 53 and 59.
CHAPTER 11

RELAY AND CIRCUIT-BREAKER APPLICATION


Oriphal Authors: Reuiscd by:
E. L. Harder and J. C. Cunningham E. L. Harder and J. C. Cunningham

T
HE function of relays and circuit breakers in the normal current, voltage, and other rating factors required
operation of a power system is to prevent or limit to select the proper breaker for each location. These fac-
damage during faults or overloads, and to minimize tors are discussed, and methods of calculating the fault cur-
their effect on the remainder of the system. This is ac- rent and interrupting rating are given.
complished by dividing the system into prot,ectivc zones
separated by circuit breakers, such as are shown in Fig. 1. I. GENERAL PHILOSOPHY AND BASIC
During a fault, the zone which includes the faulted appa- RELAY ELEMENTS
ratus is de-energized and disconnected from the system.
In addition to its protective function, a circuit breaker is As mentioned the system is divided into protective zones
also used for circuit switching under normal conditions. as shown in Figure 1, each having its protective relays for
The relay application problem consists of selecting a determining the existence of a fault in that zone and hav-
relay scheme which will recognize the esistence of a fault ing circuit breakers for disconnecting that zone from the
within a given protective zone, and initiate circuit-breaker system. It is desirable to restrict the amount of system
operation. This problem is considered from a system disconnected by a given fault; as for example to a single
point of view. The operating characteristics of protectJive transformer, line section, machine, or bus section. How-
schemes for generators, transformers, lines, and buses are ever, economic considerations frequently limit the number
discussed in their relation to overall system performance. of circuit breakers to those required for normal operation
Reference is made to other publications, particularly and some compromises result in the relay protection.
Silent Sentinels’, for the operating characteristics and con- The relays operate usually from currents and voltages
nections of individual relays. It is proposed here only to derived from current and potential transformers or po-
give the general features which will determine the type of tential devices. A station battery usually provides the
scheme to be used. circuit breaker trip current. Successful clearing depends
The circuit-breaker application problem consists pri- on the condition of the battery, the continuity of the wiring
marily of determining the interrupting requirements, and trip coil, and the proper mechanical and electrical

TRANSFORMER DIFFERENTIAL

GENERATOR
DIFFERENTIAL

BUS DIFFEREN

FE&ER eu’s DIFFERENTIAL AT SUBSTATION

Fig. l-Typical system showing protective zones.


342
Chapter 11 Relay and Circuit-Breaker Application

operation of the circuit breaker as well as the closing of the failure of the circuit breaker, or blown fuses in trip cir-
relay trip contacts. cuits (if used). Only a small part of the total failures occur
In event of failure of one of these elements, so that the in the protective relay itself. Thus close attention to the
fault in a given zone is not cleared by the first line of de- initial design, installation, testing, and maintenance of all
fense, relays and circuit breakers, some form of back-up of the accessory equipment, as well as of the protective
protection is ordinarily provided to do the nest best thing. relay proper, are needed to assure successful operation.
‘This means, first of all, to clear the fault automatically, if The application of protective relays properly requires
at all possible, even though this requires disconnection of evaluation of several factors, namely:
3 considerable portion of the system. Once cleared, the The requirements of the power service and desired function-
system can generally be rather quickly restored; whereas ing of the system during fault conditions to produce this
if the fault hangs on, the line may be burned down, or result.
apparatus damaged beyond repair, or the entire system The currents, voltages, temperatures, pressures, or other
may be shut down for an extended period. The measures indicators at time of fault which provide the fundument~d
taken to provide back-up protection vary widely depend- basis of discrimination.
ing on the value and importance of the installation and the The characteristics of available or standard relay elements.
consequence of failure. These will be discussed in a sepa- The schemes in which they are used.
rate s&ion. A wide variety of characteristics are now available op-
Some utilities in measuring the performance of trans- erating in response to the prime quantities themselves, or
mission line relay protection analyze all relay trip opcra- to various functions of these prime quantities, such as
tions as shown in Table 1. The numbers shown are typical power, phase angle, power factor, current comparison,
of a system operating 3000 miles of 1IO-kv line. power comparison, impedance, reactance, modified re-
This is only an analysis of faults for which the relay actance, current ratio, or phase-sequence component.
tripped or should have tripped. For each of these there In each case the response may be instantaneous, mean-
were several cases where the relays should not have ing no intentional delay, or the operation may depend in a
t,ripped, and did not. Thus the total number of discrim- predetermined manner on the electrical quantities and
inations made by the relays is possibly five to ten times time of duration.
TABLE~-RELAY OPERATIONS
2. Basic Relay Element@
The more commonly used relay elements and their un-
Per Cent derlying principles of operation are shown in Fig. 2. The
Correctand desired. ... ..... ..... ...
.92.2 schemes in which the elements are used are much more
Correctbut undesired. . .. ........ .
5.3 numerous. The more common ones will be described under
Wrongtripping operations. ... .... ..... 2.1 the application headings, such as generators, transformers,
Failuretotrip......................................... 0.4 and buses.
Instantaneous Elements-For instantaneous re-
as great as the trippings. The percentage failures are sponse to current or voltage the solenoid element, Fig. 2(a),
correspondingly less on this larger basis. is most common, appearing individually or as the instan-
However, Table I has been presented at this point to taneous attachment with the induction-type overcurrent
bring out the following factors that enter into a highly relay. The beam element, (b), with spring or weight bias
successful protective relay system: is used where low burden is desirable, as when setting for
1. Good equipment, relays and instrument transformers. low ground currents with low-ratio bushing current tmns-
2. A system design that can be protected and correct applica- formers. The polar element, (j), is of far lower burden
tion of relays to provide the possible protection. than the nonpolar types and has come into widespread use
3. Good maintenanceprimarily to assurethat all the accessories since 1935 as the receiver relay of directional-comparison
are operative. carrier equipments, and is the basic element when supplied
The correct but undesired trippings are cases where the from networks or electronic devices. For example, it ap-
relays have done what should be expected from their pears as the operating element in a pilot wire relay, in a
characteristic curves and settings and the fault conditions phase-comparison carrier relay, in linear-coupler bus pro-
involved. There may have been system changes since their tection, and in supervision of pilot wires.
application, or incorrect initial application, or application Because of its higher pick-up to drop-out ratio and less
with foreknowledge that certain conditions would un- accurate setting the clapper-type element, (c), is used less
avoidably operate the relays, but this was necessary to frequently for the primary protective functions but is
secure tripping in other desired cases. widely used as an auxiliary relay.
It is important to bear in mind that simple standard Induction Elements-The induction-disk element,
system design plans can be better protected. Distance (d), continues to be most widely used, its reliability and
measuring and carrier or pilot-wire types of relaying are inherent time characteristic giving it great flexibility for
much less subject to disqualification by system changes co-ordinating relays in series or co-ordinating with fuses or
than are over current types. direct-trip devices. A variety of characteristics are avail-
Wrong tripping and tripping failures, together with all able from the definite-minimum-time, which is ideal for
causes of failure to clear faults, are found to stem largely securing definite time steps between relays, to the very
from human errors, such as leaving the trip circuit open inverse which provides faster tripping with the same mar-
after test, or to open circuited trip coils, or mechanical gins when the fault current drops considerably from one
,
344 Relay md Circuit-Breaker Application Chapter 11

Fig. 2-Relay elements.


NOTES:
(a) Operating characteristics show typical order of magnitude (c) All current relays are also voltage relays by suitable no. of
only; varies with type of relay and adjustments. turns and external series impedance since I = E/Z.
(1,) Subscript ,, indicates setting or balance point value. (d) “Instantaneous” is defined as “no intentional delay.”

Schematic Operating Characteristics’s) Schematic Operating Characteristicsw


(a) (f> (I) Example: Connected as direction.
al element (quantities in paren.
theses applied to respective poles)
for watt characteristics. 4 is made
zero.
‘l-1)

Sulcnoid, “Instantaneous,” cd)AC Operates for I>l”cb).


or DC. adjust by t5ps on coil or by
initial plunger position.
Multiple pole induction cup or
disk. Each pole produces a torque
product in conjunction with its
adjacent poles and lessor torques in
I conjunction
removed, etc.
with those one pole Contacts
region.
close for I in unshaded
“pen in shaded region.
Torque expression
t-, , , , I I T = KEI cos 8.
Oo I e 314 5
Balance hcam. AC or DC, “In- operates for [>Io.
stantnneous.” adjust by cod taps,
and core screw (airgaps in mag-
netic circuit).

A;Cmature or clapper type,--,4C or


* “I”starltsrle”us,” usually (cl)
fixeil settings by design. Primarily PHASE SHIFTER
auxiliary voltage relay.

Induction disk or cup directional Contacts close for I in unshaded


element as in e or f, with phase region, open in shaded region.
shift, +, applied to voltage, E. Torque Expression
+ is the phase shift angle. T=K,??? cos (S-4).

&WE CbMPiNSATOR

Induction disk inverse-time over- Operates for I greater than I”.


current element-AC-Current is
supplied to the lower pole, and by Times shown are maximum. Re-
inductive coupling to the upper lays adjustable for times down to
pole, directly, or through a torque 0.1 or 0.05 times those shown.
compensator (saturating trans- 1 Inverse, low energy
former). The upper pole induces
currents in the disk. Torque is 3 Very inverse, low energy
produced by the reaction between 3 Standard energy definite min-
these currents and flux from the imum time
lower pole. Adjust current setting 4 High-speed, no torque compen-
by coil tap and time setting by sator
contact travel.

Genera

CONTACTS

Inductor-loop high-speed direc-


tional element. Current induced in
the loop by transformer action
LOWER
from the voltage winding reacts
with flux crossing the gap of the
Induction disk directional element. Vector diagram of E and I. current electromagnet to produce
Current induced in the disk by the Contacts close for I in unshaded torque.
upper pole reacts on flux from the region, “pen in shaded region.
lower pole to produce torque. Watt characteristic adjusted
for
Torque expression q5=0 T =Kl?l co.9 0. Front
con-
1 Lag loop to bring lower pole flux T =Kl?f cm 9 tacts close for I in unshaded area.
in phase with upper pole current Back contacts close for I in shaded
at unity power factor of Band I. where K is a constant. .9 is the
power factor angle. area.
Relay and Circuit-Breaker Applicalion 345

Fig. 2-Relay elements-Continued


schematic Operating Characteristid” ichematic Operating Characteristics”’

REAR FRONt
R

iFi=

,... I
Current tripping characteristics
r,q,t pull” on front of beam over- with fixed voltage. Contacts close
J,~~I~Iw~ “voltage pull” on rear of circle). Examples: for I in unshaded :weil. Balnnce
~,(~;,tn. Adjust halance point by point rrt
,~l,rrcnt-coil taps and core YC~W $ =%I <80 trips.
PHASE SHIFTER IF NEEDED
(:rir-g:rp xdjustment). -c QT
nduction impeda.nro element E” h cos (S-6)
$ =%$>%” does not trip. julling against KEI cos (0 -4).
Or z=picos (B-4).

Cj)

PIVOT Right) Contacts close for Z in


mshaded area. Balance point at
Z=f =K cos (8-e).
Idc OR Iac
p,,l:u element DC (or AC is used Operates for Idc or Ino greater
lv~tII rectifier), “instantaneous” than lo.
~ypr, current in the operuting coil
~wkcs the moving armature a ki 40
twth pole. It is drawn toward the I,
with pole of the permanent mng- zg30
net. $$
;p20
?g
IAl& IO
s
Oo 20 40 60 80
FAULTCURRENT TM” RELAY
AMPS
Contacts close for currents above
curve corresponding to relay set-
ting.
(Left) three minding transformer
differential relay. (Damping mw-
net not S~OWII). Adjust by taps on
Iligh-speed balance-beam modified Displaced circle impedance char- LOPERATING ELiCTRO MAGNET operating winding. (Also see Fir-
imoedsnce element. Adiust im- acteristic relay trips for all faults ure 5)
Idwce radius of circle: ZO, by for which impedance, 2, seen by
wwnt coil taps, E. and core screw relay falls within circle.
(xir gap). Adjust angle of line To, z~, and 4 are adjustable.
along which center is shifted by Balance point locus:-
taps on resistor, RQ. Adjust im- z =&@ +&“.
wdnnce z~ by which center is for all values of a.
shifted by taps on current trans-
former, CT., and on resistor R,.

TYPICAL POWER VECTOR DIAGRAM 12 AMPS


AL
T Operates in 0.1 to 0.2 sec. on heavy
(14 +0
faults. Contacts close for currents
Induction-type ratio-differential in unshaded areas. (12 and IS
relay for generator and transformer approx. in phase.) Scale shown is
protection. for a 10 percent differential gener-
ator relay.

In,duction type power relay. Oper-


ptlng torque is product of current
Ilrduced in disk by upper pole and P +jQ = E f (P =m COS 0)
Rlll from lower pole. Contacts close for P+jQ in un-
1. Lag loop to bring lower pole shaded region with timing as in-
flux in phase with upper pole dica
current at unity power factor
of E and I.
100 200 300 400
X TAP VALUE CURRENT

Induction type phase balance relay


(contact normally spring cen-
tered). A second disk on same shaft
1 on typical time lever settings. balances IS vs I,,.
346 Relay and Circuit-Breaker Application Chapter 11

Fig. 2-Relay elements-Continued


Schematic Operating Characteristic+ ! !Schematic Operating Characteristicg.~

where
I< -RRoS-Rl
Combined pan.-seq.-wrrent and 2R,
weighted zero-seq.-current filter. The internal voltage is:
E, ="R,(f,+Klo).
The internal impedance is:
Z=R,+Ro+z
where z is the impedance of in-
dicated wdg. of Y-wdg. reactor. OPERATINGPoLAR’Z’NG RESTRAINING
High speed 4 pole inductiw-(,>;I- Current tripping churncteristic
inder type directional starting unit. with fixfxl voltage. Contacts close
for It in the unshaded area. Bal-
El? aill B

OPERA
ING

High speed 4 pole induction cyl- Bda~~e polnt. z cos (e+my =K.
THREE WINDING REACT inder ohm unit (blinder).
ZERO TOROUE
Contacts dohe for Z in the un-
shaded arca.

Shown for “A” element. Contacts


(x) POLARIZING

clohe to right for I,,2 in unshaded


region. For fault on phase A-grd
I,,2 is in approx. position shown by ESTRAININ G
OPERAF
full line; for a fault on B-grd 01 ING
C-grd it is as shown by dotted
lines. Other two phases &nilar.
P 1
POLARIZING
-XI
Phase selector rel:~y (selects faulty Balance point Z cos (0 -90”) =K.
phase for single line-to-ground High speed 4 pole induction cyl- Contacts close for Z in unshaded
fault). inder reactance unit. area.
,
chapter 11 Relay and Circuit-Breaker Application 347

Fig.2-Relay elements-Continued Jvindings 1 and 2 tapped for different current-transformer


Operating Characteristics(“) ratios.
Referring to Figure 2 (o), the differential current pro-
duces lower-pole flux which acts in the operating direction
on disk currents produced by the upper pole which is trans-
former fed from the same differential current. The rc-
straint torque, giving the ratio-differential characteristics,
is produced by the through current in coils 2-3, which
supply disk current by transformer feed to the upper pole,
and by lower-pole flux produced by the same through cur-
45” Characteristic Relay
First contacts close for I, in un- rent.
shaded arca. Shown for balanced The induction disk provides a tripping-time-propnrtion-
three phase conditiow. Urdcr any
conditions rcl:~y torque is real part al-to-impedance characteristic as shown in Figure 2(z).
of Multiple Electromagnets or Disks-Two elcctro-
T=(P-.V)/450
P =b,f1 magnets on the disk provide for balancing mechanical
iV = E&. torques with no phase angle effects (see (p)). When these
are both current electromagnets, the relay is the regulnt-
ing-transformer differential relay which balances t,hc cur-
rent in the shunt esciting winding against the thro~~gh line
current. For example in a + 10 percent regulating trans-
former, it operates when the shunt current exceeds about
1.5per cent of the through current. When both electromng-
nets are voltage energized, the voltage-differential relay
results. When one is voltage (actually responsive ICE?)
and one is a product element, EI cos (e-4), a balance oc-
curs when I cos (e-4) = KE. This impedance charactw-
istic is shown in current and also in an R-X plot in (~2).
A second disk on the same shaft provides space for tn-o
more electromagnets. This structure is used as the phase-
balance relay for motor protection, whose characteristics
are shown in (p). It is used for the 3-winding-transformer
differential relay, using one operating electromagnet and
three restraint electromagnets, (n). JJ7ith two current-
input windings on each electromagnet and Ivith two re-
lays per phase the multirestraint bus differential relay
rrlny location to the next. The more inverse characteristic results. Its used will be described later.
:ilso co-ordinates better with fuses. Multiple-Pole Cylinder or Disk Elements-The
The induction disk serves as a directional element, (e), multiple-pole cylinder or disk element is illustrated in (f).
or, when used with a spring, as a watt element, (1), the The example shows how it would be energized to act as a
drctric torque being proportional to EI cos 0, where 0 is single-phase directional element having torque propor-
the power-factor angle. Either of these can, of course, he tional to EI cos 0. This element also serves as a polyphase-
wrrent polarized instead of voltage polarized for use in directional element by the connection, (q). The multiple-
wormd relaying when a bank-neutral current is available. pole element is flesible making possible a variety of other
The relative phase of voltage and current can be shifted combinations.
I)Y int,ernal or external phase-shifting devices to produce Four-Pole Induction-Cylinder Elements-These
m:Gmum torque for power factors other than unity, as in high-speed elements serve a variety of purposes as shown
(c/). For example, the directional element for ground re- in Figure 2(u), (v), (w), and (x). The element (u), desig-
l:l.ving usually has its maximum torque for current lagging nated a mho element, operates with torque E” cos (O-4)
lllc voltage by 60 or 70 degrees to provide maximum restrained by torque proportional to E2. It produces the
twqrws for the fault conditions. A pure watt characteristic circular-impedance-tripping locus passing through the
is rwd with the 30 and 00 degrees connections for phase origin or relay location, the same as shown for the induc-
‘lircctional relays,\the phase shift being provided by using tion disk in (nz). Or with either element, the circle can be
111~voltage of a different phase from the current. With shifted from this position by current compensation, 121,~
the ‘JOdegree connection this shift is too much, and the in the restraining circuit, as indicated. A dircctionnl-
voltage is advanced about 45 degrees by a phase shifter to starting unit, (v), is obtained using current times shifted-
Provide a maximum-torque position for a current 45 de- quadrature voltage for operating and the product of two
greeslagging. delta voltages for restraint. This results in maximum
The disk is provided also with an electromagnet, CO), torque for current 30 degress ahead of the quadrature
Producing ratio characteristics for use as a differential re- voltage or about 60 degrees lagging the unity-power-factor
laY for generators or transformers. The generator-differ- position.
ential relay is shown in (0). The transformer relay has The special impedance characteristic, (w), obtained, by
I

348 Relay and Circuit-Breaker Application Chapter li

12 operating against EI CDS(8+20 degrees) is used to re- the faulted phase only is in phase with the zero-sequence
strict the tripping area to assist other relays in differenti- current. Individual overcurrent elements in the thr,
ating heavy load swings from faults. A reactance element, phases could not be used for this selection as all three
(x), is obtained similarly with the phase-shift devices ar- would pick up for a single line-to-ground fault on many
ranged so that the maximum-torque line is along the x solidly-grounded systems.
(reactance) axis.
Inductor-Loop Element-The inductor loop, (h), pro- II. PROTECTIVE SCHEMES
vides a very high speed and very reliable directional ele-
ment which has been used for many years now in high- Protective schemes may be conveniently classified as
speed distance measuring relays. follows:
Balance-Beam Element-The basic balance-beam im- 1. Apparatus Protection
pedance element is shown in (i), a balance occurring for 2. Bus Protection
E/1= &. For higher impedances than 2” (current rela- 3. Line Protection
tively lower) t,he contacts remain open; whereas for lower
impedances (relatively higher currents) they close quickly. Thus, in Fig. 1, generator and transformer protection’
Since the balance is mechanical, the phase angle between come under the “:1pparatus” classification; generator
voltage and current is of minor consequence, and t,he trip- buses, high-voltage buses, and substation buses, under the
ping characteristic, plotted on an Iz and X diagram is second classification; and high-voltage transmission lines
substantially a circle. and feeders under “Line Protection.”
Modified-Impedance Characteristic-The circu- The relay application chart, Table 2, has been included
lar characteristic may be shifted by some circuits auxiliary for ready reference in determining the operating principlea
to the element as shown in (Jr), in order to provide better and application of various specific relay types referred to
discrimination between fault currents and load and swing throughout this chapter.
currents on long, heavily-loaded transmission lines. The
shifting imparts a directional characteristic to the relay in 3. A-C Generators
addition to narrowing its tripping region to more nearly Most a-c generators above 1000 kva and many smaller
just, that required for faults. machines are equipped with differential protection ar-
Networks and Auxiliary Circuits-It may be ranged to trip if the current)s at the two ends of each phase
noted that in discussing fundamental relay elements cer- winding differ. This scheme is shown in Fig. 3.
tain auxiliary circuits external to the mechanical relay Smaller machines are sometimes operated without dif-
have been introduced: in (g), the phase shifter; in (j), the ferential protection, but if paralleled with larger machines
Rectox; and in (k), a full fledged network to produce in the
relay element proper, the desired currents. This is a trend
of which we shall certainly see more as time goes on, as ,I ,CURRENT TRANSFORMER
static circuits are devised to produce a simple current out-
put proportional to the desired function of the various line
currents and voltages.
Sequence-Segregating Networks, I,+ K&--The PECENTAGE
method of symmetrical components has been the key DIFFERENTIAL
that has unlocked the door to a number of the aforemen- RELAY
tioned possibilities, some of which are illustrated in (T),
(s), and (1). The positive- and zero-sequence network in
(T) is commonly used in pilot-wire relaying, where it is RESTRAINING
desired to compare over the wires only one quantity, which WINDINGS
is a good measure of the fault current irrespective of what
kind of fault it may be, that is A-B, A-Grd, ABC. The
relay can be given almost independent and widely different
settings for phase faults and ground faults, using the single
relay element. For example, it may be set for one ampere
- TYPICAL PHASE ONLY SHOWN
of ground fault to provide the requisite sensitivity, but for
ten amperes of 3-phase current to avoid operation on loads. Fig. 3-Connections for one phase using the percentage differ- j
A negative-sequence directional element is shown in (s). ential relay for generator protection. ’ a1,
It is an adequate directional element for ground faults on
reasonably well-grounded systems, and requires only two or with a system, they may be arranged to trip off on ?>i
potential transformers rather than three as with usual reversed flow of power into the machine.
residual-directional relays. , For differential protection the Type CA normal-
Another novel application, (t), is the phase-selector re- induction, ratio-type relays are used in the larg
lay to determine which phase is faulted. This information jority of cases, their speed (about 0.1 second relay ti
is necessary in single-pole tripping and reclosing schemes. severe faults) being adequate to prevent serious burn1
It is predicated on the knowledge, from symmetrical- the iron in nearly all cases. However, a high-speed gen:
components theory, that the negative-sequence current in erator-differential relay, Type HALg, is available providin
chapter 11 Relay and Circuit-Breaker Application 349

1-C),clI e prot,cr:tion and is being used with 100 per cent suc- lower impedance grounding the differential relay protects
cessin :Lnumber of important applications. closer to the neutral. With higher impedance grounding,
‘1hc relay is usually arranged to trip the generator, field the limit of protection for ground faults is farther from
circ,iitq and ncutrnl circuit breakers (if any) simultaneously the neutral end, and for an ungrounded machine, the
l,v :1 biannually-reset, lockout relay in new installations. differential protection is ineffective against ground faults.
I;;.cXc,r,c>ntly the relay also trips the throttle and admits The protection afforded for phase-to-phase, double-phase-
(;( )$for fire prcvcntion. For example it may be required to to-ground, or three-phase faults is relatively unaffected by
(.,,,,rt1inate with other high speed relays or to reduce the the method of grounding. A complete discussion of the
,.t~,~,~l;to the systems. methods of grounding is given in Chap. 19.
If :1 +je-winding gencrntor (or equivalent) is con- Solidly Grounded and Low Resistance or React-
,,,,,.t(:d to n do~iblc bus through two breakers, a current ance Grounded Machine-If the generator is solidly
l,:lrlsformer matching problem is introduced. The cur- grounded, or grounded through a reactor or resistor, draw-
rt,,,t transformers in the connections to the busses may ing at least full-load current for a ground fault at a line
Iti:lrr.ylarge currents from one bus to the other in addition terminal, the usual 10 percent differential relay operates
t,, the gfnerator current. Thus, matching is not assured for practically any short circuit within the machine and
1,yit1entic:ll current transformers as in the simpler case of for grounds to within 10 percent of the neutral, or closer
rig. 3, and consequently, the Type HA relay is pre- if the ground current is higher.
1,,rr(~1for this case because of its superior discriminating Ungrounded, and Potential-Transformer-
,1,i:tlilic5. Grounded Generators-are thosegroundedonly through
‘1tic Type CO relay is also used for generator differential the natural capacitance from the metallically connected
1,r(j1ection. It provides straight differential protection, as windings, buswork, and cables to ground. The potential
,:c,ritrastetl with percentage differential, the diagrsm being transformer from neutral to ground, if properly appliedt,
1111: s:lme as Fig. 3 without the restraining coils. Its setting serves as a measuring device only. To insure that this is
iiiust, 1~ cbonsiderably coarser than that of the CA relay be- so, it must be liberally designed so that under no condition
(‘:IIISCthere are no restraining coils to desensitize it when will its exciting current become appreciable compared with
1ligtl through-fault currents are flowing. the charging current to ground. Otherwise, ferro-rcso-
Double-Winding and Multiple-Winding Gener- nance may occur. I7sually a full line-to-line rated trans-
otors-The differential protection scheme of Fig. 3 does former will suffice. The potential transformer and a volt-
nut tlctect turn-to-turn short circuits within the winding age relay such as the SV (instantaneous) or CV (inverse
t~ocausethe entering and leaving currents of a phase re- time) may be used to initiate an alarm or optionally to
main equal. Double and multiple winding machines pro- trip. Or, on lower voltages, a static voltage unbalance
vide a means for obtaining such protection in the larger, indicator may be used connected directly to the primary
tnorc important generators. The currents in the parallel circuit. Such an instrument is the Type G. These devices
1~rnnches,become unequal when turns are short circuited supplement the generator differential protection to provide
in one branch. The differential relays, Type CA or HA, indication or tripping for ground faults. Light resistance
ca:tnbe arranged to detect shorted turns, grounds* or grouncling as covered in the next section is generally pre-
phase-to-phase faults, by placing one current transformer ferred to ungrounded operation.
in 1ho neutral end of one of the parallel windings, and one Light-Resistance-Grounded Generators - This
of t1o11bleratio at the line end in the combined circuit. The scheme and an associated protective arrangement is il-
choice of schemes depends somewhat on the facility with lustrated in Fig. 29 of Chap. 19. Indication from a volt-
\vhich leads can he brought out and the necessity of over- age relay, connected in parallel with the resistor as shown,
1:mping the generator breaker. With hydrogen cooling or from a current relay, such as the Type BG, connected
:~(lditional leads can be brought out through the necessary in series with the resistor, may be used to sound an alarm
g:ls-tight bushings only with considerable difficulty, and or to trip, depending on the application. Combinations
lis~ia1lythere is no space for transformers inside the hydro- of sensitive alarm and coarser trip, or of alarm and time-
@ii compartment. delay trip, have also been used. The latter gives time
&ect of the Method of Grounding-The method to transfer the load to another machine at the hazard of
of grounding the generator neutral affects the protection operating with a fault on one phase.
:Ifforded by differential relays. For example, if sufficient This scheme was designed primarily for the unit station
grounding impedance is used so that a ground fault at the arrangement in which a generator and step-up transformer
Re*~(%rat.or terminals draws full load current, then for a are operated as a unit without an intervening bus. How-
f:ni1t at the’midpoint of the winding, where the normal ever, it can also be used where an intervening bus carries
voltage to ground is half as great, the fault current will be the station service transformer and one or two short feeder
YQroximately one-half the full load current. When a cables. A limited amount of selectivity is possible by the
ground fault occurs 10 percent from the neutral end of the use of a polarized relay, such as the CWP-1, which obtains
\vinding, the fault current, being limited largely by the most of its energy from a potential coil in parallel with the
nerrtml impedance, is about 10 percent of full load current. grounding resistor. Such a relay used in the station-service
This corresponds to the sensitivity of a 10 percent differ- feed, for example, can detect a ground on that circuit.
ential relay and, therefore, represents the limit of protec- Field Protection-While a large number of machines
tion for phase to ground faults with such a relay. For still operate without any protective relays to function on
‘With the same limitations as for a single winding generator. tSee also Light-Resistance-GroundedGenerators.
350 Relay and Circuit-Breaker Applicataon Chapter 1)
;z
TABLE ~-RELAY APPLICATIONCHART

/I I I

CM

COH llAlnlolnlnl I
.-/?-..I

“‘l ! !! CWP-1 1
D-3

HCZ
HO
HKB
HO-2 0
HQS
HPS
HR
HR-1
HRC 0 I IIY
$

chapter 11 Relay and Circuit-Breaker Application 351


TABLE 2-RELAY APPLICATIONCHART-continued

HRK +7 I i ini i 11 IT-~ II I I..Y


nnn
I
VI”
HRP
HV-3 : HV-3
HX OB “X
HXS
HY

HZ-I
HZ-3
HZM

JD

PG
PS-1, PS-2, PS-:
RB
RC
RF
RS, RSN

SG
SGR-1
SGR-12
SM-1. SM-3

TD

TG-1
TH
TK
TR
TS
TSI

TSO-2
TSO-3
TSP
TT-1
TV
1
352 Relay and Circuit-Breaker Application Chapter 11,Y

loss of field, t,here is a trend to more general use of equip- an emergency overload for a half hour could seriousll, ----J
ment for this purpose. On some systems where loss of damage the trnnsformcr without reaching an oil tempera,
field would cause serious low voltage and danger of in- ture which might be reached daily after several hours of
stability but where the system is operated in a way which moderate load. The thermal relay responsive to copper
can tolerate the loss of one machine, automatic means are temperat,ure will permit the overload to be carried, if safe,
being provided to disconnect the machines on loss or par- but, will protect the transformer otherwise.
tial loss of field. Fault-detecting relays include percentage and straight
Fairly common is the use of a d-c under-voltage relay, differential schemes similar to generator-protective rs
a Type D-2 d’Arsonva1 relay in series with a resistor, con- lays but include provisions for the magnetizing inrush
nected across the slip rings for field short circuit detection; current and for transformer ratio and phase shift. Also
also a similar element across the field ammeter shunt for transformers are often included with the transmission linl
undercurrent or open field detection. These do not pro- into a single protective zone. This is particularly true of
vide complete protection, and there are a number of instal- the smaller sizes such as network transformers. Many
lations of reactive power relays used at the generator small power transformers (600-3000 kva) are provided
terminals in conjunction with under voltage to trip for any with internal protective links that act like a single-opera-
field reduction which would cause serious low voltage. tion breaker as the fusible element whips through the oil
On many closely knit metropolitan systems loss of field in the top of the tank thereby disconnecting the trans-
has been found to be not serious if immediately corrected. former in event of internal trouble. Others are fused to
The operator attempts to restore the field, the generator provide disconnection from the line in event of transformer
in the meantime operating at somewhat reduced load as failure.
an induction generator. If he cannot restore field within A typical application of the CA relay to a star-delta con-
a few minutes, he must trip the line circuit breaker to avoid nected transformer bank is shown in Fig. 4. Seglecting
injurious rotor heating.
Field Ground Detection-Some form of field ground
detection is ‘frequently provided. It is considered most
important to detect the first ground because a second
could short circuit part of the field winding causing un-
balance and vibration which could wreck the machine.
The a-c scheme provides complete coverage for solid
grounds. The d-c scheme gives nearly complete coverage,
complete if the main field rheostat is varied. In some in-
stances vibration detector9 are used if the machine is known
to be operating with a ground on its field. This will trip
the unit instantly in event a second ground occurs. The
over-all protection scheme frequently includes armature
and bearing temperature indication and sometimes alarms.
Less frequently field temperature indications are provid-
ed. The voltage regulators are sometimes equipped with
over- and under-voltage protection, and, of course, over-
speed protection is provided.
In addition to the protection described, generators can
be equipped with over- or under-voltage, frequency, over-
speed, and loss of field, and temperature responsive
devices.
4. Transformer Protection j
Power-transformer protection in general includes over- ‘RESTRAINING 7
load devices to protect the transformer and fault-detect- WINDINGS -’
ing devices to protect the system and limit damage in Fig. G-Differential protection of a grounded star-delta trans-
event of fault in the transformer. former bank with CA relays. Note that the current trans- ’
In the first category is the thermal relay immersed in formers are connected star on the delta side and delta on the ’
the transformer oil but energized from a current trans- star side.
former so that it responds to the copper temperature.
This relay, obtainable only on new transformers, has exciting current, the top phase line current on the right
alarm contacts to announce the approach of dangerous hand side is made up of the difference of two transformer
temperatures, and tripping contacts that close if an unsafe currents or the difference of the two top phase line cur-
temperature is reached. rents on the left hand side. Consequently, it is compared
Oil temperature indicators perform a somewhat similar with this difference current obtained by connecting the
function though less effectively. For large power trans- left hand current transformers in delta. These two cur-
formers the order of magnitudes of copper and oil time- rents are not exactly equfil, even with a perfectly sound
constants are 5 minutes and 7 hours respectively. Thus, transformer bank, because of the magnet)izing current.
Chapter 11 Relay and Circuit-Breaker Application 353

Magnetizing Inrush-While under steady operat- THREE WINDING TRANSFORMER


h
ing conditions, the magnetizing current amounts to only / \
5 or 10 percent, it may rise to several times full load cur-
rent when a transformer is first energized, and decay
,.Llt]ler slowly from this value; that is, it may be as much
L1sfull loat1 current even a full second after the transformer
is first energized. This magnetizing inrush current is fully
displaced and hence, contains a large d-c component.23
~~~~inrush current is greatest if the switch is closed at the
zcr~)point of the voltage wave. Its magnitude depends
nlso on the residual escitation and on the leakage reactance
in the supply circuit and transformer primary. Data for
determining the value of the magnetizing inrush is given
in Chap. 5. Ordinarily the residual flux density is low YPE CA-4 RELAY
,\llen the transformer is first energized. However, when a
,s(!v(>rcfault occurs near a transformer at a time when its OPERATING WINDING
fills tlcnsity is masimum (voltage zero), and if t.he fault is
int~~rrupted an odd number of half cycles later, the residual
fills nt the instant of re-energizing may approach normal
density. As this requires the fault to start and stop at
zero voltage, it is seldom fully realized. RESTRAINING WINDING
The rate of decay of th , magnetizing inrush current Fig. 5-Single line diagram showing the arrangement of cir-
&pen& on losses and is part)icularly slow when a large cuits when using the CA-4 relay for the differential protection
ilank is paralleled with one already operating and quite of a three-winding power transformer.
near to a large generating station.?O The d-c component,
which flows at first over the supply circuit, transfers to a Type CA-4 reIay for this purpose has three restraining
circulating current between the two transformer banks, coils to be associated with the three transformer windings
rind this dies out very slowly because of the high L/R ratio. as shown in Fig. 5.
For example, when the magnetizing current has dropped Regulating Transformers-Regulating transformers
to 50 percent of fuli load in a 60-cycle transformer having for voltage and phase-angle control constitute a special
0.2,s percent primary resistance, the reactance to resist- problem because of the change in ratio taps during opera-
ance ratio is 200/.25 or 800/l. The corresponding L/R tion. Figure 6 illustrates the most modern differential re-
ratio or time constant which determines the rate of decay lay protection for such a unit. A Type CAM relay, Fig.
of the d-c component is 2.1 seconds. 2(p), having one disk and two electromagnets is arranged
The Type CA normal-speed differential relay most to trip if the current in the shunt-exciting winding of the
commonly used for transformer protection has a 50-per- regulator greatly exceeds the proper proportion of the
cent differential characteristic and 2.5-ampere minimum series-line current. For example with a+ 10 percent volt-
trip. It is prevented from operating during the magne- age regulator, a typical relay would operate for any cur-
tizing inrush by the large restraint, the inverse time char- rent in the shunt winding greater than 11.5 percent of the
ncteristic, and the braking action of the direct current on
the induction disc. It is found adequate in all but the
extremely rare cases where one large bank is paralleled
with another.
When the differential relay cannot, because of its in-
llcrent characteristics, avoid tripping on the magnetizing
inrush, a timing device can be used, which desensitizes
the protection during the timing interval by requiring a
chop in voltage in addition to operation of the differential
rclny to produce tripping during the inrush period. This
device, known as a magnetizing-inrush tripping suppres-
sor,’ is used primarily with high-speed differential relays
or with pilot-wire relays when a transformer is included STAR-SERIES
as a part of the line. CONNECTED
POT. TRANS
High-speed transformer differential protection (Type
HA relay) is required in certain circumstances to coordi- OTHER
PHASES
nate with other high-speed system protection, particularly SIMILAR
Lvherestability is critical. It must be used with the trip-
Ping suppressor as outlined above. This unit is therefore
built as an integral part of the Type HA transformer relay. LOADING RESISTOR
Three-Winding Transformers are protected in the
same manner as two winding transformers except that the Fig. 6-Typical large regulating transformer protection.
%
354 Relay and Circuit-Breaker Application Chapter 1f

line current. This provides sensitive protection for the are used in the simple differential scheme, Fig. 10(a), With‘
shunt transformer. In addition normal two-winding trans- low-resistance leads to minimize the current transforQer
former-differential protection is applied around the entire requirements. The formula specifying the requirement ,-,f
unit, providing overlapping protection with the bus and iron cross section, turns and lead resistance for nonsatur%
line protection and guarding the series transformer. It is tie@ is:
difficult to provide complete protection to the series tmns- ES
R=4.44 IT
former and tapped regulating windings. Optimum use is
made of ground protection, for example as shown in Fig. 6.
However, the possibilities of this protection vary with the where T is the short-circuit current d-c time constant in
arrangement of windings and whether groundecl or not. cycles. I, is the a-c exciting current in the secondary, s+,
Remote Trip for Transformer Faults-Becawe of lected as the threshold of saturation. It would be taken
the high record of reliability of large power transformers, a as less than the relay setting by a suitable factor of safety,
circuit breaker between the high-voltage side of the trans- E. is the required secondary rms, a-c voltage corre.,
former and the line frequently cannot be justified, purely sponding to I. on the a-c saturation curve of the current
for protection of the transformer, and the transformer is transformer. This determines the needed iron cross set-
very little hazard to the line. However, an intermediate tion and turns, or the iron if turns are fixed.
measure costing much less than the high-voltage circuit I is the crest value of symmetrical subtransient current,
breaker is frequently provided to trip the remote circuit secondary amperes.
breaker (or breakers) necessary to clear in the event of a R is the secondary circuit resistance in ohms, including
transformer fault. The transformer differential relay is the transformer winding and leads up to the relay (or
sometimes used to initiate a remote trip signal over a car- point at which all current transformers are paralleled.)
rier or pilot wire channel, particularly if the channel is The a-c flux is neglected. It is usually relatively small
already available for some other purpose. Another meth- as the ratio of maximum d-c flux to a-c flux is 27rT or 37.7
od is to close a fast, spring-operated high-voltage grounding for a B-cycle d-c time constant.
switch in response to the relay indication. This trips the For R =0.5 ohm, I= 100 amperes, T =6 cycles, and
ground relays at the other terminals of the line, at the ex- taking IS as one ampere, in considering a &ampere relay
pense of some added shock to the system. setting, E, becomes 1332 volts. A current transformer
which would generate this voltage at 1.0 ampere exciting ’
5. Bus Protection current is very large. Thus, this is a bull-by-the-horns
The advantages of bus protection in clearing faults solution, and the size, weight, and cost can be afforded only
rapidly from a system are well recognized by the industry in the most important installations. However, it does
and the provision of relay protection for major station provide the possibility of instantaneous tripping without
busses has been standard practice for a number of years. any time delay.
The problems involved in such protection are also quite A method18 has been developed for calculating with
well known. One of the principal problems is the satura- reasonable engineering accuracy, the time-to-saturate with
tion of current transformers by the d-c transient compo- offset currents, and the time and current settings required
nent of the short-circuit current as in Fig. 7. In severe to prevent misoperation with time-delay overcurrent re-
lays and usual current transformers.
Induction Type Overcurrent Relays-On busses :
of moderate time constant, say 0.1 second or less, and with :
somewhat better than average current transformers, satis- ‘.
factory protection can be obtained with a straight differ- 1;
ential scheme, Fig. 8, using a fast induction element,. A 4
small ratio of maximum to minimum fault is favorable to .z
this application. Relaying times of the order of 3 or 4 :$
cycles for maximum faults and up to 8 or 12 cycles on “8
minimum faults can be obtained in some cases. As men- II
tioned, the performance can be predicted.‘* However, i
Fig. 7-False differential current caused by d-c saturation of the time delays involved in less favorable cases are fre Xr t
current transformers during the condition of an asymmetri-
cal short circuit. The d-c time constant for the case shown is
quently so long as to point the need of a better solu-
0.14 sec. The incoming transformers are assumed not to sat- tion.
urate. Thus the error current of the outgoing transformer is Even on substation busses having a d-c time constant
the differential current through the relay. as short as 0.01 second, false tripping has been experienced
with 300/5 bushing current transformers and standard
cases the d-c transient! component may require 100 times induction relays in the connection of Fig. 8, with 4 ampere
as much flux capacity in the transformer as is required by tap, 0.5 time lever, giving 0.15 second time at 10 times tap,
the a-c component to completely prevent saturation. and with a fault current of 13 000 amperes. While this has
There are a number of successful solutions to this prob- been overcome by changing to 120015 current transform-
lem, as well as the fault-bus scheme, 11~16
which completely ers, nevertheless present practice would be to install ratio-
avoids it. One is the use of large current transformers differential relays in these cases, providing both greater
which will not be saturated by the d-c component. These sensitivity and greater safety factor.
chapter 11 Relay and Circuit-Breaker Application 355

CIRCUITS primary currents, a ratio of five volt,s per 1000 amperes


being commonly usecl. These voltages, which add up to
zero for through faults:und to a value proportional to t,he
fault current for internal faults are joined in a series loop
to the relay as shown in Fig. 10. The? 1 percent tolerance

CIRCUITS I

TO MULTI-CONTACT
+--
TRIPPING RELAY
Fig. S-Bus-differential-current relay scheme.

Multirestraint Ratio Differential Relays-Relays17 RELAY COIL


I,:~vc:been developed which will not operate falsely even
\YIIP~used with normal sized current transformers which +-- TO MULTI-CONTACT
TRIPPING RELAY
s:tlnrate due to the d-c component of current. These are
mult,irestraint relays, connected as in Fig. 9; however, their Fig. IO-Linear-coupler bus-protection scheme.
~~~cccss is due also to exploitation of variable percentage
&racteristics, and the tendency of the d-c component to within which the mutual inductances are held commer-
tmtko, rather than drive, the induction disk. cially, limits the maximum possible false differential to 2
So small part of this development is the reduction of percent. Thus the minimum setting of 4 percent allows a
I he operating limits to a few simple rules which insure safe 2:l factor of safety. Solenoid elements, Fig. 2(u), are used
:1pplication. This relay scheme provides operation gen- for settings down to about 1500 amperes on a G-circuit bus,
erally in from three to six cycles and can be set as low as and polar elements, Fig. 2(j), with saturating transformer
one percent of the maximum through-fault current. and Rector; for lower settings.
Linear Coupler Scheme-The multirestraint relays Impedance Schemes-Busses having reactors in a
just described may, of course, be used when the setting majority of the feeders and possibly in the bus-tie circuits
cloesnot need to be as low as one percent of the maxi- provide the possibility of protection by impedance re-
mum-through-fault current. However, on busses where a lays.13 Impedance or modified-impedance elements can
setting of four percent or more of the masimum through- be used, see Fig. 2, (i) and (I?). For a fault on the bus, the
fault provides the requisite sensitivity, a simpler and faster maximum impedance measured is that of the arc which is
scheme (one cycle) can be used known as linear-coupler taken as about 300 to 500 volts per foot for current above
bus protection.21*27 The linear coupler is an air-core mu- 500 amperes. Considering the possible arc length during
tual inductance used directly in the primary circuit in the the first few cycles of fault, a maximum arc voltage can be
same manner as a current transformer except that the computed and this, divided by the minimum fault current
secondaries are usually connected in series, as shown in gives the greatest fault impedance encountered for in-
1%. IO, instead of in parallel as are current transformers, ternal faults, that is, for faults on the protected bus. Pro-
lq!g. 8 vided this impedance is smaller than the impedance from
‘I6 secondary induced voltages are proportional to the the relay to a fault anywhere beyond the reactors, a basis
of discrimination exists and the impedance scheme can be
,CIRCUIT NO used.
‘t RELAY NO.1 REILAY NO.2 Two relay arrangements are used. When the bus tie
123456
PERATING WINDING
circuits include reactors, separate impedance relays can
ELEMENT NO.1 be used on each generator or transformer feed to the bus,
ELEMENT NO.2 operation of any of which will trip the bus. This arrange-
ELEMENT NO.3
ment is most feasible when the generators and transformers
are matched, acting as a unit, and the generators on the bus
RAINING WINDING are either high and low pressure units of a single combina-
PER ELEMENT tion or are treated as a single generator. The other ar-
rangement requires totalizing all of the main feeds to the
bus and the use of a single set of impedance relays. The
grouped main sources provide the possibility of a large
Fig. 9-p ro t ec t-ion of a six-circuit bus using two multi-re- false differential current for through faults. on. one
. of .these
. .
. _
straint relays per phase. main circuits. The voltage is also low under this condition
Relq and Circuit-Breaker Application

if the source circuits are not equipped with reactors. on the protective relay has become increasingly more di& i
Usually a fast induction relay, Fig. 2(d), is used together cult. However, developments in the protective relaying ati i
with adequate current transformers in the main feeds so have kept pace with the requirements. Through the intr% :,
that it will not operate for through faults on those feeders. duction of improved relaying principles and better use of I
Combined impedance and fast-induction-element opera- the old principles, high-speed action can be obtained on the !
tion is then required to trip the bus. complicated systems of today with better overall results
Directional relays can be used in a variety of ways, than that previously possible on the simple radial systems.
either as the basic protection, tripping when fault current Starting with the induction-type overload and reverse ’
flows into and not out of the bus,2r or as an adjunct for load relay in about 1901, which used power for discriminb
determining which of several bus sections included within a tion, the directional overcurrent relay with inverse-time .,I
common differential protective zone is in trouble.13 characteristics was introduced in 1910. Later, in 1914, the
Fault Bus-For new and certain existing segregated definite minimum time characteristic was added. This sim-
phase busses, the fault-bus scheme”*16provides a distinctly plified the relay coordination problem and is still used in
difierent mode of attack to the bus protection problem. the greater proportion of overcurrent relays today. The
All metal parts to which the bus may flash are connected first impedance-, or distance-measuring relay, the type CZ,
together and grounded through a current transformer and was ?ntroduced in 1922.
r&y. This construction lends itself particularly well to Shortly after this the importance of speed in fault clear-
metal-clad switch-gear. The entire cubicle or switchhouse ing, particularly with inter-connected systems, was begin-
is insulated from ground except for the ground connection ning to receive merited attention and in 1929 the high
through the current transformer The simplicity of this speed impedance relay, type HZ, operating in one cycle
scheme is strongly in its favor where the construction per- and using the balance beam principle, was introduced31. At
mits its use. However, it is sometimes difficult to secure about the same time, circuit breaker operating times were
overlapping protection with the adjacent system elements. lowered from about 24 cycles to 8 cycles.
Summary of Bus Protection-While personal pref- The reductions of overall fault clearing times that could
crence, experience, and factors peculiar to a particular be realized by these progressive changes in the arts2 are
installation play a large part, some of the general factors shown in Fig, 11.64Starting with times up to 2 seconds for
t’hat lead to the selection of one or the other of the several the slow-speed relays and 24 cycle breakers, the change to
schemes are described below. One-cycle operation, sim- high-speed relays brought the time down to about 27 cycles hi
plicity, and savings in cable costs, as compared with the with about one second in the end zones.
multirestraint scheme, are favorable to linear couplers. Decreasing the circuit-breaker operating time to 8 cycles
Quite adequate speed (3-6 cycles), the use of existing further lowered the overall clearing time to 8 to 10 cycles
current transformers, the use of current transformers for about 80 percent of the line length but left times of
which can be used for certain other purposes also (such as about 27 cycles in the end zones.
back-up protection), simple application rules, and ability In about 1935 carrier current relaying passed out of the
to set for minimum faults one percent of maximum- experimental stage51js”5254 and reached general acceptance,
through-fault sometimes eliminating need of separate making available uniform high speed action throughout
ground relay, are all favorable to the multirestraint sys- the entire section. Shortly later, in 1938, the Type HCB
tem. relay 62based on symmetrical component principles made ;
Existence of reactors and the cost or difficulty which one-cycle operation practical over two a-c pilot wires.
would otherwise be involved of installing current trans- Summarizing, and referring to Fig 11, with 8 cycle break- i
formers on all feeders, favors impedance schemes. ers the total clearing time is under 0.2 seconds for pilot- I:
The fault-bus scheme is limited to cases where the struc- wire or carrier current relaying, 0.2 seconds (with 0.5 set- :.;
ture can be insulated from ground, but in these cases its onds for the end zones) for high speed distance relaying ,l
simplicity is favorable. and 0.2 to 2.0 seconds or longer for overcurrent protection, 1
Simple time-delay over current frequently involves ex- depending on the layout.
cessive delay, but if used with ordinary current trans-
formers, it may be lowest in cost.
The directional schemes are used to good advantage by I, 24-CYCLE
INDUCTION
BREAKERS
TYPE RELAYS
some and have the advantage of securing fast operation 120
with ordinary current transformers, but are considered less 1
favorably by others because of the number of contacts to 90
t 1
be co-ordinated for correct operation.
In most cases, spring-operated, manually-reset auxiliary 6 60 _ 1
tripping relays are used, unlatched electrically by the main >
differential relays. These trip the necessary circuit :30-i &f/ggg&ry;
breakers and provide lockout.
6. Transmission Line Protection I I I I
20 30 40 50 60 70
As systems have grown in extent and complication, from 0 PER CENT OF CXSTANCE
the simple radial systems of the early 1900’s to the looped Fig. Ii-Reduction of fault clearing time obtainable throug
and interconnected systems of the present, the task imposed the use of higher speed circuit breakers and relays.
chapter 11 Relay and Circuit-Breaker Application 357

r----y-
66 KV--+ 6

4KV

33 K” TRANSMISSION
OR OlSTRl0UTlON

I I
05
P I3 0 KV
u E--

i 2300 VOLTS r-'----'-7

Fig. 12-Composite power system illustrating typical protective problems and their solution.
A cross section view of the industry today shows all of ular utility, to substations in the various towns and com-
these relay and circuit breaker types and speeds to be in munities. A looped 33-kv circuit may use directional over-
current operation. Although speeds of new oil circuit current relays, Type CR, set with selectively higher time
breakers appear to have stabilized at 8 cycles except for settings each way around the loop, as shown in Fig. 12.
special cases, there appear to be distinct fields for both nor- Impedance relays, preferably the step-type HZ, or alter-
mal-speed and high-speed relays. natively the normal-speed impedance relays, Type CZ,
may be used as in the 33-kv loop on the right. Impedance
7. Protection of a Typical System relays are particularly desirable if interconnections are con-
A composite diagram showing the typical transmission templated as shown dotted. Loops involving short lines of
line conditions in many of the large systems is given in Fig. 33- or 13.3.kv lend them:elves well to pilot wire protec-
12. For example the main transmission lines are shown as tiorP3 as in the center right.
22@kv, although they may be from 66 to 287-kv, bringing Induction-type overcurrent relays, usually with instan-
in power from a remote hydro plant or interconnectingwith taneous trip attachments for operation at the higher cur-
an adjacent system. These lines are equipped with the rents, will be found on a majority of the radial feeders and
finest and fastest protection, high-speed distance, or car- 4-kv or 2.3-kv primaries. Network feeders are cleared at
rier-pilot relays. 54 Balanced-line protection36 may also be the load end by the network relays, essentially a reverse
used if the lines are paired although high-speed distance or power form of protection.
carrier relays are required to secure fast operation with one
line out of service. 8. Relay Symbols
The 33-kv circuits, often looped or interconnected, carry Relay symbols are useful in illustrating the form of pro-
bulk power out through the territory served by the partic- tection used for each element of a system. With modifying
358 Relay and Circuit-Breaker Application Chapter 1
:
notations as to relay types and settings, these symbols Relative Number of different kinds of faults-a
compress the otherwise complicated picture of complete The relative numbers of different types of faults vary wide- f
system protection into a form that can be readily visual- ly with such factors as relative insulation to ground and 8
ized. The standard symbols arc given in Table 3. Their between phases, circuit configuration, the use of ground ;JI
USChas been illustrated in Fig. 12. wires, voltage class, method of grounding, speed of fault ;
clearing, isokeraunic level*, atmospheric conditions, qual- I
TABLE Q-RELAY SYMBOLS ity of construction and local conditions. Thus the figures
given below serve merely to indicate the order of prev%. -
(01 SYMBOLS FROM THE AS A STANDARDS.
lence and emphasize that there are usually a great many
more line-to-ground faults than faults of other types.
~1 Three-Phase Faults 5 percent
‘Two-Line-to-Ground Faults 10 percent
Line-to-Line Faults 15 percent
Line-to-Ground Faults 70 percent
POWER DIRECTIONAL
Total 100 percent
BALANCED OR
DIFFERENTIAL CURRENT e 10. Overcurrent Protection
OVER FREOUENGY
The general plan of coordination with overcurrent relays
UNDER FREQUENCY cctrr on a radial system is shown in Fig. 13. The time shown in
OVER TEMPERATURE cf, each case is the fastest operating time for a fault at the lo-
BALANCED PHASE cpk PHASE ROTATION
cation of the next device in sequence. At lighter generat-
ing capacity the fault currents are reduced and all operat-
PILOT WIRE (CURRENT PILOT WIRE (DIRECTIONAL
DIFFERENTIAL) COMPARISON)
I --ew I

L
I
8
I
I
CARRIER PILOT
kcl
I
--

Where the operation of o relay is conditional


current (residual or zero sequence) this shall
upon the flow of ground
be indicated by prefixing
:c. -i-O---Customers
1
Load
Ferder
the ground symbol thus:-
Residual Overcurrent *I+---+ Directional Residual Overcurrent +I-
Other prefixes such OS @ ond @ to indicate operotion on positive
or negative phose sequence quontities, ond suffixes to indicate the
relay types, inclusion of instontoneous trip attachments, etc. moy be
added ot the discretion of the user,

(b) FREOUENTLY USED VARIATIONS OF THE STANDARD SYMBOLS.


OVERCURRENT GROUND WITH INSTANTANEOUS ATTACHMENT #w-I
GROUND DIRECTIONAL WITH INSTANTANEOUS ATTACHMENT Fig. 13-Coordination of overcurrent protection on a radial
DIRECTIONALLY CONTROLLED -4w I power system.

POWER DIRECTIONAL WITH INSTANTANEOUS ATTACHMkNT


DIRECTIONALLY CONTROLLED *4/w+- I ing times increase, but because of the inverse time charac-
BUS CURRENT DIFFERENTIAL e--x-- teristics of the relay the margins between successive relays
BUS GROUND DlFFERENTlAL
also increase.
?f- Relays used with feeder circuit breakers must be coor-
F
dinated with fuses of distribution transformers and with
the main and branch line sectionalizing fuses.83 Several
9. Fault Frequency and Distribution characteristic curve shapes are available in different de-
About 300 disturbances (or one per ten miles) occurred signs of the induction-type overcurrent relays as illustrated
per year in a typical System operating 3000 miles of 1lo-kv in Fig. 14. These provide latitude in selecting the relay
circuit. This system used mostly overcurrent and direc- that coordinates be& with the fuse curves at the current
tional relays, and in n 4-year period experienced 2800 relay involved.
operations of which The definite minimum time characteristic provides a
92.2 percent were correct and desired ready means for coordinating several relays in series with
5.3 percent mere correct but undesired only an approximate knowledge of the maximum current,
2.1 percent were wrong tripping operations and results in relatively small increase in the relay time as
0.4 percent were failure to trip the fault current is lowered. It is used in the majority of
overcurrent relay applications. The inverse and very in;
The faults were as follows: verse characteristics are sometimes more favorable where
Lightning 56 percent close coordination with fuses is required. They also make
Sleet, Wind, Jumping Conductors 11 percent it_ possible to take advantage of the reduction of maximum
Apparatus Failure 11 percent fault current as distance from the power source increases.
Close-in on Fault 11 percent Several relays in series can be set for the same time for
Miscellaneous 11 percent *Number of storm-days per year
chapter II Relay and Circuit-Breaker Application 350

I iii \‘\i i i i i i i i i i i i i i i i I

Percent of Pick Up Current


Fig. Il-Characteristics of various induction type overcurrent relays.

(a) Type COH. (c) Inverse-low energy relay, Type CO.


(b) Very inverse-lowenergyrelay, Type CO. (d) Standard, definite minimum time, Type CO relay.

futilts immediately beyond the relay and still provide the Trip Time for Bkr. # 1
rccluisite 0.25 second or more margin for fault beyond the
nest relay because of the lower current value for fault in
that location. For esample the timing on curve (b), Fig.
II, doubles when the current is reduced from 700 percent
to 400 percent of pick-up value. Several settings of 0.3 scc-
ond at 700 percent could be used in series, while still having
0.3 second margin between successive relays if the fault
current dropped-in the ratio 7 to 4 between successive loca-
tions.
The choice of relays is also influenced in certain cases by
the lower burden of the “low energy” and “very inverse”
types. Fig. 15-Time-distance curves of the Type CZ relay. The slope
of the curve is changed by varying the resistance in series with
11. Normal-Speed Impedance Relay* the potential coil. The minimum operating time with zero
The t,ime-distance tripping characteristic of the Type voltage on the relay is about % sec.
cz normal-speed directional distance relay is illustrated in
Fig. 15, which shows a number of line sections in series. adjusted to trip in approximately x second for a fault at
This may equally well be a loop, the two ends of the section the next bus, except as will be noted.
shown being at the same supply point. The tripping time It is essential that for a fault near bus 4, breaker No. 3
of the relay increases in direct proportion to the distance be tripped in preference to breaker No. 1. Thus the oper-
from the relay to the fault, except that the minimum time ating time of relay No. 1 must exceed that of relay Ko. 3
is about & second for a fault at the relay. Each relay is for fault at location No. 4 by one circuit breaker operating
*The trend is toward the high-speed impedancerelay describedin time plus margin. For 8-cycle breakers a reasonable break-
%c. 12 even for intermediate voltage transmissionlines. er time plus margin is 0.4 second.
360 Relay and Circuit-Breaker Application Chapter 1

The operating time for faults anywhere on the system r&y. The third-zone impedance element, which operates k,
can be readily determined by drawing the straight lines when either of the other two elements operate, is used to
representing the relay times, using whichever criterion start the timer that closes first a second-zone timing con-
rules in each case; that is, 0.75 second at the next bus or 0.4 tact Tz, and later a third-zone timing contact, 2”s.
second above the next relay at the second bus. The partic- Thus for a fault in the first 90 percent of the section
ular time values mentioned are typical only. The relay known as zone 1, the contacts D and Z1 operate, giving i&
tripping time is independent of current magnitude once the mediate high-speed tripping in one to three cycles, as in&
ovcrcUrrentl setting has been exceeded and timing thereby cated in the timing chart of Fig. 16. While the other el+
initiatctl. Thrls variations in the amount and location of ments also operate their action in zone 1 is Unimportant
connected generating capacity, or switching lines out, does because the circuit breaker has already been tripped. Thus
not materially affect the coordination of the distance type in zone 1 the tripping time is that of elements 21 and 0:
relays over the remainder of the system. For the second zone, which extends approsimately to the
The normal-speed type CZ relay is not usually employed middle of the next section, contacts D, Zz and Ts in series
on lines shorter than those in which at least 5 volts sec- do the tripping, provided the fault lasts for the time setting
ondary rewdt at the relay for a fault at the other end of the Tz. If the fault is in the nest section it will be cleared by
line. As the relay is normally subjected to full voltage and the proper breaker in advance of TZ operation, although
must tliscriminate on values between zero and that for a back-up protection is provided by the second zone setting
faUlt at, the other end of the line, the operating forces ap- &ending into the nest section. This also provides opera-
proach the frictional forces below this limit. tion for bus faults if they are not previously cleared by bU&
protective relays.
12. High-Speed Impedance Relays, HZ and HZM The third zone, corresponding to tripping through the
The high-speed distance type relay has the step type contacts of elements D, 23, and Ts, completely overlaps the
time-distance characteristic illustrated in Fig. 16, obtained next section, providing complete back-up protection. It
must of course be timed selectively with the Tz timing of
TRIP TIME FOR the next section.
BRE&ER The flexibility of this arrangement in molding its char-
acteristic to various section lengths and breaker and relay
times is apparent. The highly successful operation of sev-
eral thousand such relays in service indicates that for prac-
tical systems, which of course depart in many nays from
the simple ideal case represented in Fig. 16, the flexibility
is sufficient to secure in general the operation outlined.
For good operation the line should be electrically long
Fig. 16-Time-distance curves of the Type HZ step type, high
enough so that there will be at least 5 percent voltage at
speed distance relay. When carrier current is added the time the relay for a fault at the next bus, although in special
is reduced to that shown dotted. cases successful operation can be obtained somewhat below
this limit.
In some cases the CZ characteristic lends itself better to
coordination with other back-up protection, but the high
speed of the Type HZ first-zone element is desired. For
this purpose these two elements have been combined and
make available the time-distance curve shown in Fig. 18. d
Fig. 17-Contact circuit for producing the stepped time-dis-
tance characteristic shown in Fig. 14.
Z,--First Zone Imphxe Element Contnct.
&--Second Zone Impednnce Element Contact.
Z3-Third Zone Impxhnce Element Contact.
7’2, Ts, timer cont,nctshaving sepnrntelyadjustAle time settings.
D-Directionnl element contact.

by separate directional, impedance, and timing elements


with contacts connected as shown in Fig. 17. There are a Distance -
total of three balance-beam type impedance elements, each Fig. 18-Typical time-distance characteristics of the HCZ re-. I:
arranged with a current operating winding at one end of lay. Note the slope of the CZ element necessary for different ?
the beam and a voltage restraining winding at the other. length sections to secure selectivity.
When the ratio vf voltage to current falls below the im-
pedance settmg of the relay high-speed action closes the ModiJied Impedance Relay, Type HZM.41 The operat-
contacts. ing characteristic of the standard type HZ impedance relay
The Impedance elements 21, 22, and ZS are set for suc- is nearly independent of the phase angle between current
cesslvely greater distances. The directional element closes and voltage. That is its “reach”-vs.-angle characteristic is
only for faults in the desired tripping direction from the a circle centered at the origin as shown in Fig. 19. This
chapter 11 Relay and Circuit-Breaker Application 361

vector drawn from the origin, A, to a point on the line


L-L’. This line bisects O-O’ pcrpentlicularly. The no-load
points, corresponding to zero angle between machines are
at infinity either way along L-L’, whereas the 180 degree
out-of-phase condition is at the intersection, C. All inter-
mediate loads are somewhere along the line L-L’, the point
I, corresponding to power flow A to B and point L’ to
power flow from B to A.
The large circle with center at the origin, A, represents a
pure impedance characteristic, as in Fig. 2(i). The smaller
circle having the same “reach” beyond B is a modified im-
pedance characteristic, Fig. 2(k). It can equally well trip
for all faults on the protected line but is less likely to trip
for very heavy loads or load swings. Successively heavier
loads are represented by progressing through points L, D,
and E along the load locus. The modified characteristic
taken with directional element,, trips for faults or loads in
the cross-hatched area F, while the pure impedance ele-
ment trips also in the areas G and G’. Thus the modified
characteristic permits heavier loads without tripping.
When carrier relaying is used so that tripping requires
~;ig. l9-Modified-impedance characteristics provides im- closure of the relay at each end of the line, the small circle,
proved selectivity between heavy load swings and line faults. for the relay at A can be advantageously shifted further to
the right, so that the combined action of this relay and its
mate at the other end of the line limits carrier tripping to
&racteristic provides adequate discrimination between the restricted zone between the two arcs at H and H’. The
loat and faults in a majority of cases. However, increased back-up protection must be given sufficient timing to ride
INS,:is being made of the Type HZ11 relay having the modi- through swings or eliminated entirely except for a high-set,
tic&impedance characteristics shown in Fig. 2(k) for the long-time element.
prot,cction of long or heavily-loaded lines. It is necessary The modified impedance element provides for indepen-
I h:lt the relays permit the maximum expected steady or dent adjustment of the radius of the circle and the location
saving loads without tripping. On long or heavily-loaded of the center as shown in Fig. 2(k) and hence makes pos-
tints, and especially if high-speed reclosing is used, it be- sible the superior discriminating characteristics needed for
c*omcsmore and more difficult for the relays to distinguish long or heavily-loaded lines as outlined before.
hctween heavy swing loads and fault conditions. The
modified-impedance relays provide the improved discrimi- 13. Carrier Pilot Relaying
nnt.ion necessary in these cases. A pilot channel such as that obtainable by carrier cur-
Their operation can best be shown by plotting on a sin- rent over the power circuit, or by a microwave beam, pro-
glc diagram the impedances corresponding to three things. vides the possibility of simult.aneous high speed tripping of
1. Faults on the protected line. both circuit breakers in one to three cycles for faults
2. Heavy load swing conditions. throughout the entire section. The significance of fault-
3. The relay characteristics. clearing speed on system stability is treated fully in Chap.
These are shown for a simple case in Figure 19. Con- 13. However there are, altogether, a number of reasons
sidering the simplified case of a two-machine system with why carrier-current relaying has been employed in prefer-
:111 impedances having the same R/X ratio, let the system ence to other systems. These are:
irnpcdnnce be laid out on a resistance-reactance chart as
1. Stability-Simultaneous clearing improves system stability
tlic line OJBO’ representing the impedance from one ma- and increases the loads that can be safely carried over
I,hine to the other. The transmission tine being studied is a parallel interconnecting lines.
tic-line constituting the section AB, shown heavy, of this 2. Quick Reclosing53-Simultaneous tripping is essential to
Ma1 impedance. If R and X axes are drawn through A, fast reclosing, the combination being particularly effective
as shown, the impedance with respect to these co-ordinate in increasing stability with single tie lines.
:WS are those seen by the relays at A. Thus, the locus of 3. Shock to System-System shock, evidenced by voltage dips
impedances seen by the relay at A for a solid fault on the and dropping of synchronous load is lessened by fast
Protected line consists of the line A-B, having impedances clearing.
from zero up to the full line impedance. 4. System Design Flexibility-Desirtl,le system arrangements
that can not be relayed with sufficient speedsotherwise, are
It can be shown that if the generator voltages at the two
possible with carrier relaying.
ends of the system are equal in magnitude and are at first 5. Growth of Faults-The more serious three-phase and dou-
irr phase, then are moved out-of-phase, resulting in load ble-ground faults generally originate as line-to-line or single-
transfer over the line A-B, the impedance locus viewed ground and with sufficient speed of clearing the spreading
from A is along the line L-L’. That is, the impedance seen to other phasesis greatly reduced.
t)Y a relay at A, for the load condition, is the impedance 6. Ground Relaying Improved-On systems where high-speed
36‘2 Relay and Circuit-Breaker Application Chapter II

ground relaying is not feasible otherwise, carrier pilot re- Corresponding second and third zone ground over-current :;
laying provides an ideal solution. elements, Fig. 2(b), are provided. The carrier control has ‘j
7. Out-of-Synchronisn*-The carrier channel provides means the net effect of eliminating all second-zone time delay for :
for preventing operation of protective relays by power faults within the protected section. This is aCCOmplished
swings or out-of-synchronism conditions, yet clearing by closing of the contact RR, Fig. 17, whenever a fault is ;
faults during such conditions. present and carrier is stopped because the direction of flow f
8. Simz&zneous Faults-The added basis for discrimination :
makespossiblesuperior relay performanceunder simultane- is “inward” at each end of the line.
ously occurring faults. The mechanism is indicated generally in Fig. 20. Occur- 7
9. Joint Use-From an economic point of view joint use of the rence of a fault anywhere within reach of the third zone r+
carrier channel for point-to- point communication, or for lays, closes Z3 starting carrier and setting up a circuit so
control or remote metering, may indicate the use of carrier that the receiver relay will close if carrier is removed by
pilot where the relaying requirements alone do not justify it. some other action. If the fault is internal, D and & close,
Carrier relaying operates on the principle of tripping stopping carrier transmission from either end of the line,
quickly all terminals through which power flows into a line The receiver relays, RR, immediately complete the trip
provided fault power does not flow out at any other ter- circuit. If the contact circuit RR is opened manually the
minal. If fault power flows out at any terminal, that tcr- carrier can be cut out and a stepped-distance relay scheme
minal continues to transmit a straight telegraphic carrier remains. Thus the carrier is thought of as simply eliminat-
signal over the line, which is picked up by all other termin- ing the time delay in the end zones, indicated by the shad-
als on that particular line and prevents tripping. No time ed areas in Figure 16. The stepped-distance elements and
delay is necessary for internal faults since tripping for ex- an inverse-time ground current element provide the back-
ternal faults can be prevented by the carrier signal. Since up protection in this system.
carrier is not transmitted for internal faults, the short cir- Phase Comparison System-The phase comparison
cuiting of the carrier channel by the fault is of no conse- system differs functionally in that the current directions
quence. or phases at the two ends of the line are compared rather
Directional Comparison System-The type HZ or than the power directions. Networks are used to derive a
HZM directional comparison system utilizes the stepped single-phase function of the line currents as in the pilot-
impedance elements, Fig. 2(i) or (k-), as its basic actuating wire relay. This function may be referred to simply as the
elements, (see section on High-Speed Impedance Relay). “current” at each end of the line since it is a measure of the
*Can also be accomplishedwithout carrier,J* with somedifferences. several phase currents.

’ CARRIER ,--STOP-J
t ---,---~ CURRENT t
23 z3
1+-START-’ TRANSMITTER- L-START-*~
I RECEIVER
RELAYS
Fig. 20-Carrier current relay system including relays, carrier current transmitter-receivers, coupling capacitors, and chokes.
Dotted lines indicate symbolically the carrier controls
MO-Master Oscillator REC-Receiver
PA-Power Amplifier LTU-Line Tuning Unit
chapter II Relay and Circuit-Breaker Application 363

If the currents at the two ends of the line are in phase “R” RELAY
CURRENT
and of fault magnitude, carrier is transmitted on alternate
half cycles of current from either end of the line, resulting
in substantially continuous carrier on the line from one end
or t,he ot’her. For an internal fault the current at one end of
tlic line reverses or remains below the fault detector setting
so that carrier is sent only half of the time. The relay is ar-
r#,nged
‘ SO that this produces tripping.
Figure 21 shows (heavy) the relative positions of the
locally and remotely transmitted carrier pulses for internal
180 120 60 0 60 120 180
RELAY TUBE
T
‘I
ANGLEOF I,( 12’0’

93R
)I/ ANGLEOF I’, f II2 = 180”
OPERATING “I
VOLTAGE FROM
TRIGGER CIRCUIT
Fig. 22-Typical overall characteristics of the Type HKB car-
rier relaying system.

A few of the factors considered in determining whether


WAVE DIAGRAMS to use one or the other of these systems are the following:
INTERNAL FAULT EXTERNAL FAULT Favoring the Phase Comparison System
1. Can be added for high-speed protection with any existing
A’ relay schemefor back-up.
2. No potential transformers are required. Low-tension
8’ potentials are sometimes adequate for back-up relays.
3. Inherently trip proof on out-of-step conditions. (Out-of-
C e LOCAL CARRIER e C’ step blocking relays are included in the other scheme if
D ---c-(t)- DISTANT CARRIER- D’
needed.)
RECTIFIED CARRIER 4. Not subject to trip by induced ground current from a
E E’
uuu
AT RECEIVER
I I I j-l parallel line.
(RESTRAINING VOLTAGE)
5. Back-up relays entirely separate. Can take either high-
F’ speedor back-up out of service without affecting the other.
Favoring the Directional-Comparison System Using Stepped-
G’ Distance Relays
Ii -TRANS. SEC.VOLTAGE H’ 1. More generally, applicable to multi-terminal lines.
2. Provides better discrimination between loads (tapped from
I w RELAY CURRENT I’ lines) and faults. When transformers are tapped along the
RELAY TRIPS RELAY DOES NOT TRIP lines, it is not desired to trip the line for faults on the low-
tension feeders.
Fig. Zl-Relay tube circuit and typical wave diagrams of type 3. Can trip with fault currents less than twice load currents.
HKB carrier relaying system. 4. More flexible for system changes.
However, on many lines either system is entirely applic-
faults (left) and external faults (right). Local pulses of op- able and might equally well be used.
crating voltage are applied to the relay tube every half Fig. 20 shows the complete equipment required for a
cycle. For the internal fault the pulses of restraining volt- carrier current relay system. Relays shown are of the di-
age caused by the carrier occur in the opposite half cycle rectional-comparison type. The carrier components are
from the operating pulses. Hence pulses of plate current the same with the phase-comparison type relays.
occur and result in tripping. For the external fault, re- (a) The relays; practically the same as for high-speeddistance-
straining pulses occur during both half cycles, and since type protection except with the addition of the receiver relay,
these pulses are, by design, greater than the operating directional auxiliary relays, and out-of-step elements which are
pulses, no trip current results. With the entering and leav- housed together. The Type HZ relay is shown in Fig. 23.
ing line currents not quite in phase, some relay current (b) The carrier current transmitter-receivers operated from
flows. However, as shown in Fig. 22, a substantial phase the station battery and with an output of 5 to 40 watts at 50 to
difference can be tolerated without causing tripping. 150 kilocycles when keyed. The outdoor set contains line-tuning
equipment for matching through the coupling capacitor to the
In this system, the carrier portion is purely pilot protec- high tension line. When the set is located indoors it is connected
tion. Back-up protection must be added as an entirely by coaxial cable to the line tuning equipment in a separate
separate entity. Stepped-distance relays, or simply direc- housing located near the coupling capacitor.
tional-overcurrent relays, are used for back-up protec- (c) The coupling capacitor. The connections to ground, and
tion. to the potential device if used, are through radio-frequency
364 Relay and Circuit-Breaker Application

including the relays, Carrier Set, COUphg capacitor, choke


and installation, costs considerably more than the terminal
equipment required with pilot-wire protection. However
the cost of the pilot-wire circuit increases almost directly
with the length of line; consequently there is an economic
dividing line between carrier-current and pilot-wire appli-
cations. The average dividing line is at about 10 miles but
it varies widely with such factors as: the availability of ex-
isting pilot-wire circuits, the number of other pilot wire
services with which the cost of the pilot cable can be
shared, the inductive exposure conditions which determine
the test voltage of the pilot cable, and the cost and con,-
plexity of the necessary carrier-current channel.
The ideal pilot-wire relay systems should:
1. Require only two pilot wires.
2. Provide complete phase and ground protection with a
single relay at each terminal.
3. Permit wide variations in current transformer performance.
4. Be suitable for use over leased telephone circuits.
5. Not operate incorrectly when the system is out-of-
synchronism.
6. Provide adequate insulation between the pilot wires and
the terminal equipment.
7. Have provisions for dealing readily with longitudinal
induced voltages in the pilot circuits or with differencesin
station ground potential.
Fig. 23-The Type HZ high-speed, three-zone impedance re- 8. Have provision for supervising the pilot wires.
lay. The relay is arranged for use either as a conventional 9. Operate at high speed.
step-type distance relay for phase-fault protection, or in the
directional comparison scheme of pilot-wire or carrier-cur-
rent relaying.
A number of d-c or a-c pilot wire schemes based on di-
rectional comparison or on current differential have been
used to a limited extent. For example an arrangement
chokes. Thus, at carrier frequency, the coupling capacitor is similar to the carrier-current protection described has been
simply a series capacitor between the carrier set and the high- used with pilot wire. However by far the greatest number
tension line.
(d) The tuned carrier-current choke or wave trap, of sufficient of pilot-wire relay applications employ the Type HCB re-
capacity to carry the line current but imposing a high impedance lay thereby meeting all of the above requirements.
to carrier current of the frequency used. Its purpose is to prevent The arrangement is shown in Fig. 24. At each end of the
loss of the carrier energy into other sections, so that ample signal line a voltage proportional to positive-sequence curreni
strength is available in the protected section.

Microwave Relaying-Either the directional-com-


parison or phase-comparison systems of relaying can be
used over microwave channels as well as power-line carrier
channels without significant alteration. However, because
the microwave channel is not subjected to line faults it
does not necessarily have to be used in a blocking manner,
but is suitable also for transfer tripping.
14. Pilot-Wire Relaying
d
Pilot wire relaying is to the short transmission line what
carrier current protection is to the long one. It provides
uniform simultaneous tripping of the circuit breakers at
R’RESTRAINING COIL
both ends of a section, with all that such operation implies 0 ‘OPERATING COIL
D.C. RECTOX FED COILS ON A POLAR ELEMEN
in the way of increased stability, lessened shock and dam-
*Positive-sequence and zero-sequence segregating network. The secondary Cur
age to the system, and simplified coordination with other rents are fed in. An internal voltage is produced proportional to II+KIo. TIJ'
relay protection. In short high-voltage lines, discrimina- network 88 viewed from the relay element terminals
an internal impedance. A saturating transformer.
has this internal voltage MU
not shown, ia used betwee’
tion is often impossible with distance type relays; pilot re- the network and the relay element.

laying by wire or carrier becomes the only method of dis-


Fig. 24-Alternating current pilot wire scheme using th
crimination not based on time delays. HCB relay. Simplified schematic. Only two wires are reqU~@
The cost of carrier-current protection is practically un- and continuous supervision of them can be obtained as show
affected by the length of the line. The terminal equipment, dotted.
chapter 11 Relay and Circuit-Breaker Application 365

With Matched Transformers


Normal Load and Thru Fault

E-
i?. + +-
E
+ +Currents= Thru Fault
+ -Currents= Internal Fault
N k’

Fig. 25-Typical operating characteristics of the HCB relay for a phase A to ground fault with the currents through the
two terminals 30 degrees out of phase, and a 2000-ohm pilot wire.

istics. Each relay contains a filter segregating the positive-


and zero-sequence currents and combining the right
amount of each into a single relaying quantity. Thus, by
selecting the proper relay tap, tripping is obtained at any
desired ground-fault current and phase-fault current. This
reduction to a single differentiating quantity makes com-
parison over only two pilot wires possible. The ability to
trip correctly even with badly mismatched current trans-
formers is illustrated in Fig. 25. The vector positions of
the sequence currents for various types of faults are illus-
trated in Fig. 32.
15. Ground Relaying
Overcurrent and directional relaying used for ground
protection usually follows the same schemes as employed
for phase protection. That is, the overcurrent ground re-
lays for a radial system may be progressively timed, as in
Fig. 13. For loop systems the directional element is added,
polarized either by zero-sequence voltage or by a trans-
former bank neutral current which is proportional to zero-
sequence voltage. This results in progressive timing as in
the loop circuit of Fig. 12. Stepped-distance relaying is
likewise used but with limitations which will be dis-
cussed.
There are a number of differences between ground and
phase relaying.
Fk. 26--The Tqrpe HCB pilot-wire relay. The relay has a sin- (a) The zero-sequence impedance of the average trans-
Ble operating el ement, which functions for all types of phase mission line is 2 to 5 times its positive-sequence impedance,
and ground faults. while the zero-sequence impedance of the source, compris-
ing frequently only the transformer-bank impedance, may
and a constant times the zero-sequence current is derived. be lower than the positive-sequence impedance of the
The relay has variable-percentage differential character- source. Therefore as the fault is moved along the line, the
366 Relay and Circuit-Breaker Application

ground-fault current falls off more rapidly than the phase- used if the line terminates at the far end in a transformer that 1
fault current and current magnitude can be used more for mill not pass residual current. <
discrimination, at least where ground \I-ircs are used. Reactance Relayin&-has an inherent, advantage Over
(b) Usually there are many more sources of ground cur- impedance relaying for ground fault protection in that the
rent t,hnn of phase current!. This improves the selectivity relay measurement, is generally much less affected by fault 4
obtainable with overcurrcnt ground relays. resistance. If the currents supplied from the two ends of i
(c) A system may have several unconnected portions of the line are not in phase, the fault resistance does appear to 4
zero-sequence network, in which case a ground fault in one the relay to have some reactance. Nevertheless, the error &
section does not draw ground current from other parts. in distance measurement caused by fault resistance is gen- 8
This makes the coordination of ground relays simpler than erally much less with a reactance element than with an 4
that of phase relays. impedance element.
(d) Fault resistance is likely to be much higher for For ground relaying it is desired that the relay measure ,!
ground faults than for phase faults on the higher voltage the zero sequence reactance from the relay to the fau1t.a’
lines. At currents of 1000 amperes or more the arc voltage It may be noted that the ratio of line-to-neutral voltage at {
is 300 to 500 volts per foot so that a lOOO-ampere line-to- the relay to zero-sequence current is:
line fault through a 5-foot arc involves a fault resistance of En
approximately 2500 volts divided by 1000 amperes or 2.5 -= ~oZ”+llZ1+rzZz
ohms. Compared with this, pole grounds, which may be IO IO L
the fault impedance for a ground fault, are usually in the where IO, II, 1~ are the sequence current at the relay and
5 to 50-ohm range. A wire on the ground can have almost 20, 21, 2~ the sequence impedances from relay to fault.
any fault resistance. Being unaffected by load current, a Thus the zero sequence impedance can be measured as-
ground-current relay can be set lower than a line-current z = E,- ILZ~-- 1222 IoZo
relay. Thus it can be set low enough to operate even 0
lo =lo
though the fault current is choked down considerably by
fault resistance. The positive and negative sequence voltage drops from 1
(e) The zero-sequence mutual reactance between two relay to fault are deducted from the line to neutral voltage,
parallel lines is important, although positive-sequence mu- E,, by compensators and the resulting voltage divided by :
tual reactance is usually unimportant. The zero-sequence IO is a measure of the zero sequence impedance. A react-
mutual reactance leads to circulating residual currents in ance element using this voltage and current willmeasure
one line for a fault in the other, even though the lines are the zero sequence reactance as desired.
part of two separate systems. It also interferes some- The type HXS ground reactance relay operates on this
what with distance-type ground relaying, although principle, three elements being used to provide stepped-
methods are available for compensating this effect in some distance protection. As there is zero-sequence current only ;
cases.3?‘35
for fault conditions, no separate fault detector is required. ,
Another factor of importance is that the fault, rather Only one HXS relay is used for all three phases, the voltage
than the supply end of the line, is the source of zero- of the faulty phase being connected to it by a type HPS
sequence voltage. That is, the zero-sequence voltage ta- faulty-phase selector relay illustrated in Fig. 2(t).
pers down from the fault towards the relay as outlined in To provide a single high-speed step, as for example whe
Sec. 23 and illustrated in Fig. 30. existing relays provide adequate backup protection, tl
These factors lead to difficulties in applying impedance HXL relay is used in conjunction with the HPS pha
or other distance measuring relays for protection against selector. This provides one ground reactance step, usual
ground faults. While they have been used in some cases set about 75 percent of the line length, and a load-loss fe
where conditions are favorable and where discrimination ture which opens the second breaker instantly after tl
would be even more difficult by other means, their use is first breaker opens. The load-loss feature utilizes thri
limited. overcurrent elements to recognize by the closing of at lea
Overcurrent Ground Relaying-The vast majority one back contact and one or more front contacts that
of ground relaying is essentially overcurrent, with direction fault is present and the far breaker is open. Under norm
where needed. The more common elements follow: load conditions all three front contacts are closed.
Type CO-Induction-overcurrent relay with instantaneous- Negative-Sequence Directional Relaying-T1
trip attachment. The instantaneous trip is set below the max- negative-phase-sequence directional element can frequen
imum ground current in the line for a fault at the next bus. ly be used to advantage with an overcurrent ground relr
Nonsimultaneous closure of the circuit breaker poles during load to obtain selective clearing of ground faults. This resul
switching may result in momentary ground current sufficient to from three facts-
operate the instantaneous ground relays, where the relays are
set sensitively. This has been avoided by connecting a residual- 1. Only two potential transformers are required.
voltage-relay contact in series with the trip circuit. The latter 2. On solidly-grounded systems the negative-phase-sequen
does not operate during load switching operations. voltage at the relay may be of larger magnitude than d
As above but with induction-directional element, Fig. 2(e), zero-sequence voltage at that point, hence, a more posit?
controlling the induction overcurrent element. The directional relay operation can be obtained.
element may be polarized either by residual voltage, Type CR, 3. The negative-sequence directional element is not affecti
or bank-neutral current if available, Type CRC. by zero-sequence mutual induction from parallel transd
Instantaneous-overcurrent elements, such as the SC, can be sion circuits.
chapter 11 Relay and Circuit-Breaker Application 367

Current-Voltage Product Relaying is also used for feeding that bus are cleared at their remote ends, w&h
ground protection. As the fault is moved away from the some time delay. This is the most common form of back-
relay, not only does the zero-sequence current at the relay up protection.
drop quite rapidly, but also the zero-sequence voltage (or Overcurrent relays are frequently used for back-up pro-
the bank neutral current which is proportional to it) de- tection on lines eqllipped with high-speed distance, or
cre:lStS. This makes the product of these two quantities pilot-wire or carrier relays. These also provide protection
an effective discriminating function. It is utilized in the for the immediate line while the primary protection is taken
tJrP(:~CW and CWC relays. See Fig. 2(e). out of service for the testing.
In many cases relays at one station, A, Fig. 27, cannot
16. Back-up Protection reach through the bus of the next station, B, to a fault at
:\s mentioned earlier, in the event of failure of the proper
circuit brcakcrs to clear a fault, it is desirable to have some
forIn of back-up protection to remove the fault from the
syst,em in the next best way that can be arranged within
economic limits. The measures employed in present-day
,,r:lctice vary a11the way from complete duplication of re-
lLLvs,circuit breakers, and tripping sources at one extreme
to ,I() back-up at all at the other extreme. The measures
,,sc~tlin each case are somewhat a matter of opportunism as
to what can be done conveniently, but more a matter of
j,l&ment and evaluation of the following factors:
1. Technical means by which back-up could be provided.
2. Importance of the section being backed up. That is, con-
sequenceto the system of failure of the primary protection,
if one or the other of the various back-up possibilities is in
use.
L-d.AJ-L
3. Cost of Providing back-up protection in various ways.
4. Probability of faults, of the failure of primary protection,
or of equipment failures that would cause costly or time
consuming repairs if the primary protection should fail. Fig. 27-Problem of back-up
83
protection.
5. Consequencesto the industrial processesor other loads
being served if service is lost, momentarily, or for a long
time. the ends of the lines beyond. This is especially true if there
is generation on the bus at station B, or if the lines beyond
To make these considerations more concrete a few ex- are very long, or both. Consideration is then given to some
amples may be cited. If a line fault hangs on due to a cir- form of protection that will clear all other circuit breakers
cuit, breaker failure and is not cleared, the first hazard is on bus B, if one fails to open for a fault. One scheme in
that the line may be burned down resulting in a time-con- use is to have the relays of each circuit breaker on bus B
suming repair job. The second is that the continued fault not only trip their circuit breaker, but also energize a time-
may cause the whole system to pull out of step and result delay relay. This relay will trip all circuit breakers on the
in a complete shut down of an entire city area or large sys- bus, through the bus-auxiliary lock-out relay, if the pro-
tem. Provision of back-up may remove one or both of tective relay does not open its contacts within a reasonable
these possibilities depending on the circumstances. time, indicating that the fault has been cleared. This takes
ln an indoor station the failure of some piece of equip- care of circuit breaker or trip-coil failure. Relay failure is
ment to function properly, thereby leaving a fault un- backed up assuming that there is more than one relay ele-
cleared, may result in a fire or explosion with extensive ment that should trip. However, it does not guard against
(lamage, which might have been avoided or minimized had battery failure or instrument-transformer or lead failures.
somesecondary means of clearing been in use. Sometimes the back-up relays can be connected to different
Xeedless to say these considerations estend far beyond transformers than the primary protection but the only pre-
Protective relays, into maintenance, testing and safety caution normally taken with respect to the battery is good
Practices, air versus oil switchgear, building construction, supervision.
Protection of lines against lightning and other hazards and Experience indicates that it is better economy to apply
quality of major equipment. All of these should eventually back-up relays to protect against other equipment failures
I)eweighed to obtain the most favorable over-all service for than merely to back-up another relay, while using all the
tt~etime, effort and cost involved. same accessories.
ln a system of transmission lines protected by overcur- On some generator busses a partial-differential back-up
rent or distance-measuring relays, the relays for each cir- is used to trip the complete bus section for feeder faults not
Gt breaker can frequently be set to provide primary pro- cleared by the proper circuit breaker. The main sources,
tection for the immediate line section and back-up protec- such as generators, transformers, and bus ties are totalized
tion for the next line section, as indicated by the character- to operate these back-up relays. The relays are usually
istics of Fig. 13 15 16 and 18. Then in event of the failure overcurrent and are given enough time to select with the
Of a circuit bre:ke; td clear for any reason, all other lines main feeder protection.
368 Relay and Circuit-Breaker Application

In some very important stations complete duplicate sets process damage, resulting from sustained operation at low
of relays are used, operated from separate transformers to voltage. However, where continuous operation is more im-
provide the back-up function. Also in certain large gener- portant than motor protection this feature is eliminated or _
ating stations, with double circuit breakers separating ma- used for alarm only.
jor bus sections with power concentrations of the order of Thermal-alarm devices applied directly on the motors
200 OOO-kw load, the back-up partial-differential circuit are becoming increasingly popular in attended stations
not only uses separate current transformers but trips the where the operator can determine from the ammeters op
other circuit breaker of the double-breaker combination. other indications, the source of trouble.
The partial-differential protection can often be arranged so
that it backs up generator, reactor, and bus protection as 18. Power House Auxiliaries
well as feeder protection. The power house is the heart of any electric system and
Since carrier, pilot-wire or distance protection is some- its funct,ioning rests on the motors which drive its fans,
times rcquircd to obtain 100 percent selective primary pro- pumps, gates, and other auxiliaries. IIence reliability is
t&ion, it is not always possible to obtain selective action paramount, and in addition to provision of a most suitable
of the back-up relays. There is some trend in the case of power supply and spare units for certain auxiliaries, much
pilot-wire protection of short-line sections to cut the back- attention has been given to the relay protection. A recent
up relays in automatically nhcn the supervision relays in- survey of United States practices8 resulted in the following
dicate that the pilot wires are inoperative. Some use is be- recommendations, attendance being assumed.
ing made of carrier in a somewhat similar philosophy, to The 2300-volt motors should use long-time-delay phase-over-
block certain back-up elements when carrier is being re- current relays for overload and internal motor faults, set at
ceived. approximately 150 percent of rated current. They also should be
equipped with instantaneous overcurrent relays for short-circuit
17. Motor Protection protection set above maximum-inrush current. If the auxiliaries
For the larger motors which are equipped with protec- are transferred, the instantaneous relay must be set above 8.
higher inrush current.
tive relays, the protection supplied varies with the impor- On essential motors* the time-tlelny overload relays may be
tance of the service and whether automatic or not and used for alarm purposes only, and the instantaneous relays used
whether attended or non-attended. to trip. In this casethe time-delay relays can be set more sen-
Many motors 500 horsepower and larger, and some sitively than 150 percent of rated current.
smaller ones are protected by long-time (geared, 40-sec- Low voltage motors (208, 440, 550 volts) should use a thermal
ond) induction-type overcurrent relays set in the neighbor- device for overload protection, and an instantaneous-trip device
hood of 150 percent of maximum-load current, but with for short-circuit protection.
timing to permit the st’arting inrush of several-hundred- In addition, the report notes the desirability of eliminat-
percent current for several seconds. A typical case might ing undervoltage protection except for alarm purposes, so
be 600 percent for ten seconds for an across-the-line-started that the loss of auxiliaries due to system disturbances will
induction motor, although these figures vary widely, de- be minimized.
pending on the application, and must be determined in
each individual case. These relays will operate for a stalled 19. Industrial Interconnections
motor, for internal motor faults, or for a heavy over- When a line is tapped to an industrial plant having gen-
load. eration, it is common practice to segregate essential loads
The overcurrent relays are usually provided with instan- for operation from the plant generator and dump others in
taneous-trip attachments set above the motor-starting event of a line outage. If the same line is tapped for other
current to trip quickly for severe faults in starter, leads, or plants, the problem arises of separating the plant under
motor. consideration from the line under conditions hazardous to
Thermal relays are frequently provided in addition to its operation. One scheme in successful use on many indus-
the overcurrent relays, to provide more sensitive overload trial interconnections consists of separation based on any
protection. Having a time constant of several minutes as of three indications provided power flow has reversed and
contrasted with seconds for the overcurrent relay, they fol- is toward the power company. The three indications are:
low the motor temperature more closely. They will not under frequency, undervoltage, or generator overload. i;,
protect the motor under stalled conditions, however, where Any of these occurrences, provided power flow is away from _
the motor ventilation is missing; the overcurrent relay pro- the plant, is taken as sufficient cause for separating and at
vides this function. the same time dumping nonessential loads so that the re- “1
In automatic applications, and where st,arting in reverse maining plant load may be brought within the capacity of ‘,:
would be serious, a phase rotation relay is used which the plant generation. iI
IS
closes contacts lo permit a starting only if the phase se- The relays normally employed are: ,.n
,i
quence is correct and voltage is present on all three phases. Induction-type overcurrent for generator overload.
This does not gllard against phase unbalances which might Induction-type under-frequency relay.
occur during operation, however. For this purpose, a Induction-type undervoltage relay.
phase-balance current relay, Fig. 2(p), is provided in many Iligh-speed-type three-phase directional relay.
automatic schemes to trip if the 3-phase currents become The generator overload relay is directional controlled so
excessively unbalanced. Time-delay under-voltage protec- *Essential motors are in this case defined as those motors whose
tion is frequently applied to guard against over-current or failure results in the shut-down of generating capacity.
chapter 11 Relay and Circuit-Breaker Application 369

tl1ut it \vill not start timing unless direction in the intercon- the importance of the service. However, the major calibrn-
nrcti(jn has reversed. t,ion tests are generally scheduled for periods more of the
Dirrc*t.ion:tl relays are also used, Ivithout the voltage, fre- order of sis months to LUW.years. One year is a qllitc com-
(l,lcn(:y, or current fault detectors, for this purpose. mon period. There is a d&led feeling that too frcq~l(~nt,
testing may cause more harm from mistakes and inntlvcr-
20. Three Terminal Lines tent damage thtin the good that is accomplished. The t,csts
l,incs having three or more terminals”* are generally vary from the over-all or primary test in \vhich current is
m,,rc difficult to protect than two-terminal lines. Alternat- passed through the primary of the current brsnsformer,
ing crlrrent pilot wire protection is applicable in many and the circuit breaker tripped by the resulting relay ac-
,,LLst>salthough the limiting values of pilot-wire capacitance tion, to much less complete checks. A quite usual procc-
:Lntl resistance are less per terminal than for two-terminal dure would be to remove the relays from service and test
lill(:s. C,arrier schemes, particularly of the blocking type and calibrate on a load box, and to check the instrument
LIrc apphcable to multi-terminal lines. However, sequen- transformers for continuity and grounds. The instrument,
t,i:ll operation of circuit breakers occurs if fault current of transformer-relay circuit, is grounded at only one point,!‘” so
EIrjprcciable magnitude flows out at one terminal for an in- that the intentional ground can be lifted for this test. If
tcrn:J fault near another terminal. The first-zone imped- feasible the circuit breaker may be tripped by closing the
:LI1(:cclement nearest the fault, acting independent of car- relay contact.
ri(br, opens the first circuit breaker, after which carrier is
st,oppcd by the directional elements permitting clearing of 23. Relaying Quantities and How They Are Ob-
(/IL’ other circuit breakers. tained
The prime requisite of all protective relaying is a funda-
21. Out-of-Step Protection mental basis of discrimination, which has been variously
Practically all utilities,“O except those consisting of steam referred to as a discriminating function or quantity, an op-
stations connected rigidly together electrically, have ex- erating principle, or a relaying quantity. This discriminat-
I)cbricnccdsystem instability. Most utilities have experi- ing quantity must be one to which a protective relay can be
~:ncctlsome undesired operation of fault-protective relays made to respond, and one which separates the desired trip-
:ts :t result of system instability. Quite a number of utilities ping values from the desired non-tripping values.
:LItcampteither to block line relays from tripping because of The common discriminating quantities, such as current,
out-of-step conditions, or to set the relays so that tripping voltage, time, impedance, direction, and power are well
\vill occur at a preselected point. Out-of-step blocking in known, and the methods of obtaining them from current
conjunction with carrier relaying is the method most com- transformers, potential transformers, and potential devices
monly employed. are generally understood and described elsewhere.1.32 Ko
Synchronous frequency changers interconnecting two general treatment of this subject can be given here. How-
systems may suffer mechanical damage to shafts and cou- ever, some of the more important characteristics of these
plings if permitted to operate with t,he systems out-of-step. quantities will be briefly outlined. Some special considera-
‘1‘1~resulting power pulsations may be close to the natural tion will be given the newer sequence quantities arising
hcquency of the two-mass system composed of the two from the method of symmetrical components, given in
rotors with connecting shaft. Out-of-step relays are avail- Chap. 2.
:tble which detect a slip cycle by the power reversal at high Voltages and Currents During Fault Conditions-
yurrent and can be set to trip after two or three slip cycles, Ten different faults of four kinds can occur at one point on
or before serious torque oscillations build up. the system:
Quick clearing of faults by modern 8-, 5-, and 3-cycle cir-
cuit breakers and high-speed relays is well accepted as a three-phase ABC
line- to-line XB BC CA
measure of prime importance in improving system stability
:mcl reducing damage and permanent outages. Case after double line-to-
ground ABC BCG CAG
(‘:Lsccould be cited where these improvements have been
single line-to-
Wrlized as circuit breakers and relays have been mod-
prnized up to present-day standards. High speed reclosing ground AG BG CG
1~s been made possible by simultaneous operation of cir- When one of these four kinds of faults occurs along the
cuit breakers at the two ends of a transmission line by car- line, the voltage and current relations at the relay are
rier-current or pilot-wire relaying. This measure is gener- somewhat as shown in Fig. 25. For a three-phase fault the
:LIIY accepted as economically of greatest benefit in improv- currents are balanced and lag the line-to-neutral voltages
ing stability and service reliability. Three-polegl reclosing by the impedance angle of the line. In an average high-
has been most widely used. However, there are a number voltage line this angle is about 60”. The addition of fault
of applications of single pole reclosingg2 which further en- resistance tends to lower it. For line-to-line fault, say BC,
hance the stability by leaving the sound phases in service the current in line B lags the collapsed BC voltage by a line
\vhile the faulted ones are opened and reclosed. impedance angle of about 60’. For a two-line-to-ground
fault, for example BCG, a similar situation pertains, except
22. Testing and Maintenance that the line-to-neutral voltages B and C also collapse to an
Itoutine tests are made by many companies at quite fre- extent depending on how solidly the system is grounded.
quent intervals such as one to three months, depending on Consider two easily visualized cases. If the system is
370 Relay and Circuit-Breaker Application Chapter 11

Normal Conditions
Phase to Phase Fault Between
B and C Phases

Two Phase to
\ Ground Fault

*b

Fig. 28-Typical unbalanced conditions of current and voltage occurring during various types of fault on a three-phase
system with an angle of sixty degrees. Load current flow neglected for fault conditions.

grounded through a very high impedance (Zo very high), closes for current from approximately 90” ahead to 90” be-
the currents will be nearly the same as for a line-to-line hind the voltage applied to its potential coils. For a three-
fault escept for a small added ground current. However, phase fault on a 60” impedance-angle line the current lags
the fault will establish the mid-point between B and C behind its unity power factor position by 60”. With a 30’
phase voltages as ground potential. Another example is connection it lags the reference or polarizing voltage used
the case Z1 = Z2 = 2, for all parts of the system. For this on the directional element by 30”. Fault resistance (plus
case the phases are independent and the three-phase sys- any modification of the relay characteristics by lagging)
tem acts exactly like three independent single-phase sys- brings the fault current nearly to the maximum torque po-
tems. The two-line-to-ground fault BCG, is the same as sition. For the other kinds of faults on different phases the
the three-phase fault except that phase A voltage is not current is shifted one way or the other, but the wide closing
collapsed, and only load current flows in phase A. The ma- band of the relay allows for this variation. The 30” connec-
jority of systems fall between these two limits. tion uses star currents and delta voltages.
For a single line-to-ground fault on phase A, the cor- The same system is followed in naming other connec-
responding line-to-neutral voltage collapses and the phase tions, although the relay used, including its phase-shifter :
=1current lags the line-to-neutral voltage of phase A by the if any, does not always have a closing zone for current from ,’
impedance angle of the line-ground-return circuit including -90” to +90” with respect to voltage.
the fault impedance. If Z0 = Z1 =Z, throughout the system The 60” Connection uses delta currents and voltages; the i.
this fault will not influence the other two phases. If 20 is IA- In current being used with the phase CA voltage. A
higher than Zi, corresponding to high impedance ground- relay with a closing zone approximately +90” to -90” is
ing, the condition of ungrounded operation or full displace- used. Delta-connected main or auxiliary current trans- 2
ment of the voltage triangle is approached. formers are needed to obtain the delta currents.
Single-Phase Directional Element Response- The 90” Connection uses star currents and delta voltages; ,j,
Considering the different kinds of faults, and also their oc- the phase A current being used with the phase CB voltage. s
currence with symmetry to A, B, or C phases, the angle In this case, however, a 45” voltage advancing phase- :i,
between voltage and current for a fault on the line varies shifter is employed with the relay element giving it for star
over rather wide limits. In using a single-phase directional currents a closing zone approximately from 13~’ ahead to
element, as in the CR, CZ, or HZ relay, a particular voltage 4.5’ behind the delta voltage. For a three-phase fault on a
must be associated with a particular current. 60” impedance-angle line the phase A current leads the
SO” Connections. One of the common “connections” as-
sociates the phase A current with the phase CA voltage *Other directional elements may have their closing zone shifted
and is known as the 30” connection, because at unity power as much as 45’ in the leading or lagging direction. The element used
factor under balanced three-phase conditions the current with the 30’ connection may be a watt type or may have its closing
leads the voltage by 30”. A watt-type* directional element zone shifted 10’ to 20’ in the lagging direction.
chapter 11 Relay and Circuit-Breaker Application 371

pl,s~e CB voltage by 30”, and a small fault resistance THREE- IE-TO-L11 GLE LIN DOUBLE LINE-

nb ”
,,.ould swng lt toward 45” leading. The closing zone ex- PHASE -GROUN TO-GROUND
tends 90” either side of this position and affords optimum
opportunity for the relay to give correct directional indica- --I=
n
tion with other kinds of faults.
[~7~unllyany of these three connections gives correct di- POS.
rfctional mdicatlon although in individual cases advan- r P r P r P SEQ.
1 I I
NET.
tagcs can be found for one or the other, depending on such
fLlctors as the impedance angle of the line, the possible
fault impedance, and the likelihood of an undesired
amount of directional element operation caused by leading
I *

1
I
m x

lCjatlcurrents near the directional boundary. For distance ”


(,arrier relaying using single-phase directional elements the
NEG.
(ioo connection using delta currents is preferred since the r -N SEQ.
same delta current is used on the impedance element. If t
NET.

x
TABLET-SEQUENCE POWERRESPONSEOF THREE-PHASE DIREC-


TIONAL ELEMENTS
- T

oz
TORQUE VECTORS ”

rt-2
FOR NIEEDED
RELATIC”
.V OLTAGE THREE-Pk GE
s
us &
c PURE RESISTANCE
SEE: NOTE SHIFT TOROIJI E r -2
ZERO
SEQ.

mx
32 -F OR 60’ t
it* ** > POS. I
SEP. !
sIYSTEM
SEE NO’TE NET.

zz STBR x
A A 0’ - -60’ P+N+Z ~
A -6 60’ 1 0’ PL-6o”+NL+600 -2
A C 120’ / +60* PL-120’+NL-l2d+Z 3ws SHO \CTUAL fi IVE DIF INS OF SEQUENCE
-.
A -A 180’ - 120’ -P -N -Z >OWER (VOLT-AMPERES AT SYSTEM IHPEDANCE PHASE ANGLE)
A B 240. 1 180’ PL-240a+NL-120°+Z ‘OR A SYSTEM OF THE SAME IMPEDANCE PHASE ANGLE
A -C 300’ ,, 240’ PL+60n+Nf-600-Z THROUGHOUT.
IELT, STAR I LINE’ I LINE’ IL~NE*+(NEG.I L~NE*+(PARALLEL
CA A *30’ I J NONE -30’ PL-309cNL+30’ P +NEG. SEQ. a ZERO SEQ. OF NEG. B ZERO
CA -B “90” 1 1 NONE 30’ (P-N) L-90’ NETWORKS NETWORKS) SEQ. NETWORKS)
CA c 150’ J I NONE 90’ PL-150°+NL-2100
N NONE SYSTEM* SYSTEM * SYSTEM *
CA -A 210’ 7 / NONE 150’ PL-2lO+NL-150’
CA 0 270’ f t NONE 2 I 0’ PL+90°+NL-90° Z NONE NONE SYSTEM* SYSTEM *
CA -C 330’ / \ NONE -90’ PLf30e+NL-30*
*Line refers ta the line impedance from relay r la fault x of the par-
IELT, )ELTI
ticular sequence. System refers ta the impedance from generator to r
CA %+A 0” - - NONE -60° P+N
of the particular sequence.
CA A-0 “60’ \\ / NONE 0’ PL-60°+NL+60*
CA -B+C 120’ / i NONE 60° PL-120°+NL+120~ b) IMPEDANCE WHICH DETERMINES ANGLE OF POWER AT THE
CA C-A 180’ 6 - NONE 120’ -P-N SELAY. (ANGLE OF SEOUENCE CURRENT BEHIND CORRESPONDING
CA -A+B 240’ f /’ NONE IBO’ PL+120°+NL-120’ SEQUENCE VOLTAGE.)
CA B-C 300’ ,, 4, NONE 240’ PL+60’+NL-60’
AL CONNECTIONS Fig. 29-Diagrams showing the relative directions of positive-,
negative- and zero-sequence power during fault conditions.
(3) - - (4) -60’ P+N&oE,-a ?oEe The Chart (b) indicates what part of the system fixes the pow-
er factor for each sequence.
(2) - - NONI -60’ P+N

zAI,E,- A
(2) (4) (4) NONI -0 oIPE, impedance element operation is caused by a line-to-ground

1 (I)

*These are the commonly


4 +30’

used 30”. 60”. and 90” connections.


(P-NIL-90°
fault its associated directional element is influenced by
fault current. This overcomes any possible load current
effect.
**Other phusea connected
(‘1 A “rw two-elerrrx,t
symmetrically
90” connection
in sequence A. B. C.
giving the desirable P-N torque.
Three-Phase Directional Element Response-The
(L’l Two-wattmeter
(31 ‘r wo _wattmeter
conncetion
connection.
with zero-sequence current removed by a filter. same connections are used with three-phase directional
“1 f’arasitic torques. elements*. In this case another factor influences selection
Note: Torque is the real part of the expression in the last column. P =Eifl.
.V =I& Z = E&. If the ayntem were pure resistance throughout all E’s and of the connection. Table 4 shows the functions of sequence
I*s would be in phase, or phase opposition. For faults. N and Z would be
negative at the relay. and P positive, but all three power terms would be pure power to which various connections respond. As shown in
scalars.
Wxe.&ms
The arrows show the vector position
for this Idealized pure resistance
(not magnitude) of the torque
system case. taking into acccnmt
Figs. 29 and 30, positive-sequence power flows toward
that the values of N and Z nre negative as shown in Fig. 29. If instead of being
Pure resistance the syste”, were pure 60” impedance angle throughout the
the fault; negative- and zero-sequence power flows away
effect would be to rotate nil currents negativelv 60”, leaving all voltapes from the fault, since the fault is the source of negative-
““chanaed. As the power terms are of the form Ef thiv will rotate si”Glarly all
the P. ,V. and Z quantities and hence the torque vectors. The real COLII- and zero-sequence voltage. Therefore the positive-sequence
Ponents of these vectors are the toruues. Hence conclusions can he draw” IL*
t” whether the torqrlea associated &th P, N. and Z are additive and how *This discussion relates to three independent single-phase elements
I”“& voltage phase shift is needed for optimum condition on a aystern of given
‘mpedance a”gh% on the same shaft. No three-phase rotating field is involved.
Relay and Circuit-Breaker Application Chapter 11

current lagging 60”. Also the negative-sequence torque? is


masimum for current lagging 130” and hence gives 50 per-
cent of the masimum possible assistance to positive-se,
quence torque for 60” system-impedance angle. As the
system-impedance angle is likely to be above GO”, this is
THREE-PHASE FAULT quite favorable. The zero-sequence torque is also in the
right direction though not masimum.
:, E,-E, 1 The delta-voltage, star-current, 30” connection has ad-
1 z,=j s=Tqy verse negative-sequence torqlle, lvhile the 90’ connection
LINE-TO-LINE
1 (SINCE E&*01/ FAULT (PHASES b-c) is ideal in this respect, the positive- and negative-sequence
torques have their maximums in the same direction for
90” lagging current. The usual 45” voltage-phase-shifter
brings the maximum torque to a desirable point and maxi-
mum assistance is secured from the negative-sequence
torque.
( DOUBLE LINE-TO- The delta-voltage, delta-current, GO”connection, like the
1 ‘E,-I,Z,+I,Z;\ ! ; GROUND FAULT (b-c-g)
I I I corresponding star-star connection, has good negative-se.
t
quence torque in the proper direction for a GO”impedance-
angle system. It has no zero-sequence torque. ;LIasimum
I=+=- positive-sequence torque occurs for a GO”impedance angle
E2 Ei5I without using a phase-shifter.
t I 11-12
’ SINGLE LINE-TO-
In addition to symmetrical connections, one unsym-
I
I 1 GROUND FAULT
metrical connection is worthy of note in that it is capable
,
I of securing the desirable P-N accurately. It uses the B
minus C current with the C:1. voltage and the -4 minus C
current with the CB voltage. It has maximum torque for a
E;*E,-I, Z,=-(E;+E;) 90” impedance-angle system and hence can be used to ad-
vantage with a 45” voltage advancing phase-shifter simi-
larly to the better known 90” connection of three elements.
Impedance Measurement-Referring to Fig. 30, the
0S INDICATES SOURCE
difference between El and Et at the relay is the positive-se-
Fig. 30-Simplified equivalent system showing the sequence quence drop from the relay to the fault plus the negative-
voltage distribution during fault conditions. sequence drop back to the relay. Recognizing that 2~ = Z1
for the line, it can be readily shown that the line impedance
minus the negative-sequence power at the relay (P-N) to the fault is:
is more positive for a fault out on the line than is (P+N), z J&-E,
and hence provides a better fault directional indication, 1 11-I,
having higher torques for fault currents in relation to
those due to load currents. This applies for three-phase, line-to-line, or double line-
In table 4 the “connections” are shown in the first three to-ground faults. For line-to-ground faults a higher im-
columns, and the resulting three-phase torque on the ele- pedance than Zlismeusured by the ratio(El-E2)/(II-12).
ment in the last column. The relative phase positions of From Eq. (1) the delta connection is derived
the torques produced by positive- and negative-sequence Ib = I, + a*11+ UIz (2)
power are shown in the 4th, 5th, and Gth columns, taking I,=Io+aIl+a21~ (3)
into account that when the impedance angles are the same Ib-Io=(u2-.)(Il-12) (4)
throughout a system, the values of N and 2 are opposite to Eb-E,=(a2-u)(El-Ez) (5)
P under fault conditions. The positive-sequence torque E,,--i-7, ErEzzZ
vector is drawn in the position of the conjugate of the cur- (a
==11-12 l
rent vector to produce maximum torque, the horizontal
axis being the unity power factor position. Thus for the The last expression shows that for fault at a given Ioca-
star-voltage, star-current, 0’ connection maximum torque tion the delta voltage divided by the delta current is the
is for unity power factor. If a watt responsive element line impedance Z1 for three-phase, line-to-line and double
is used the voltage must be retarded 60” by a phase-shifter line-to-ground faults. As shown previously a higher value
to obtain maximum torque for current lagging 60”. is measured for line-to-ground faults.
The star-voltage, star-current, GO’ connection* can be Lewis and Tippett32 give the fundamental basis for dis-
obtained with the phase n current associated with the tance relaying in the most comprehensive paper on this
negative of the phase B-to-neutral voltage, the other subject. Among other things it is brought out that use of
phases being symmetrically connected. This is perhaps the delta current and delta voltage on the impedance element,
best star-current, star-voltage connection as no phase shift for example the A minus B current with the BA voltage, as
is required to get maximum positive-sequence torque with IThis refers to torque due to negative-sequence currents and
*This is not the commonly referred to 60” connection. voltages. Actually it is torque in the positive direction.
chapter 11 Relay and Circuit-Breaker Application 373

outlined in the preceding paragraph, avoids a 15 percent pedance type and rcq”ire a special potential transformer
ditiercnce in distance measured for line-to-line and three- connection. The star series transformer connection for ob-
phase faults, which is present if only one line current (star taining zero-sequence voltage is shown in part (g). Parts
crlrrcnt) is used. (h) and (i) are three-winding-reactor type current filters
Use of Sequence Quantities*-In using sequence whereas parts (j) and (k) use an auxiliary current trans-
q,lLlntities the point of view should be developed, first, that former to produce the reactive drop due to B minus C cur-
the fault is the source of negative- and zero-sequence volt- rent in a single-winding reactor. Note: The Type CRS
ageand power, and that negative- and zero-sequence power negative-sequence directional relay uses filters (d) and (i)
(volt-amperes at system impedance angle) flow away from for negative-sequence voltage and current respectively.
tllc fault at the relay location; second, that the sequence Parts (I), (m), (n), and (0) are all impedance-type cur-
V,Ilt;Lge is measured with respect to the bus-of-no-voltage rent filters, (1) and (m) being suitable only when there is no
,jI’ point n in the particular scqucnce network considered. zero-sequence current; (n) and (0) are not affected by zero-
‘l’l,(:sc relations are hrollght out in Figs. 29 and 30. sequence current, but require double the number of current
Sequence Voltage Distribution During Faults- transformers.
ln Fig. 30 the voltage gradients are shown very generally. Part (p) is a zero-sequence current filter, which is merely
Ii,)r a three-phase fault the voltage tapers off from the gen- the neutral connection of star-connected current trans-
c!r:ltor to the fault. For a line-to-line fault the positive- formers.
s(:(\nencevoltage tapers off until, at the point of fault, it A combination positive- and zero-sequence current-
,8cl~& the negative-sequence voltage, which in turn tapers segregating filter is illustrated in part (cl). This filter IS
to ZCTO back at the generator neutral, or point back of used in the Type HCTZ pilot-wire relay.“? The relative
\vhictl thcrc is no impedance to negative-sequence current. weighting of zero and positive seqllence is determined by
111some cases this may be an infinite bus. the relative magnitude of Ro and RI. For esumple, if it is
For a double line-to-ground fault the positive-sequence desired that the same internal voltage Ei be produced by
v~ltnge again tapers off to the point of fault where it equals one-tenth as much zero-sequence current as positive-se-
the negative- and zero-sequence voltages. These taper to quence current, the zero-sequence weighting factor k must
zero in going back through the network until a point of no be set equal to 10. Then the required value of R, may be
voltage of the respective sequence is reached. determined as follows:
;\t a line-to-ground fault the positive-sequence voltage is
R. = $kR1 = 6.6iRl
t,hc negative of the sum of the negative- and zero-sequence
voltages and these taper to zero back through the network. The relative phase positions and magnitudes of various
It is well to note that if the zero-sequence impedance is sequence quantities of the reference or A phase vary with
high (high-impedance grounded system), the zero-sequence the type and phase of the fault. The response of a com-
voltage is nearly equal to the normal positive-sequence or bination filter varies accordingly. Fig. 32 illustrates the
line-to-neutral voltage for a line-to-ground fault, and ap- relative positions and magnitudes of the vectors compris-
prosimately half as much for a double-line-to-ground fault ing the quantity I,+kIo on a system for which the ground-
where the generated voltage divides between the positive- fault current is one-tenth of the phase-fault current, and
:md negative-sequence networks, thereby applying about using a zero-sequence weighting factor of k = 15. The II
half voltage to the zero-sequence network. As a result on vectors have been magnified somewhat in the line-to-
lightly grounded systems all zero-sequence and residual ground fault diagram to make them visible; their actual
voltages and currents are approximately half as much for
double-line-to-ground as for line-to-ground faults.
Sequence-Segregating Filters-Sequence currents *
:md voltages may be segregated from the corresponding
* I, c
line currents and voltages by segregating networks or fil- C
tws. The methods of obtaining zero-sequence currents or klo
voltages are already well known as these quantities are a-b-c b-c b-c-g O-9
simply one-third of the corresponding residual quantities.
‘l’Ypic%l sequence-segregating networks are given in Fig.
8 1. The performance of each network is expressed by giv- -$- FF7
II
ing its equivalent circuit*12 and also by giving the equations
of operation.
l’olyphase networks for segregating positive- and nega-
7
b-9
“1,

tive-sequence voltage are shown in parts (a) and (b), and


are useful for operating a polyphase device in response to
pither of these quantities. The positive-sequence filter is
& useful for obtaining a balanced three-phase supply
fr()m an unbalanced (or single-phase) supply. The remain-
o-b I o-b-g C-9
ing filters shown all have single-phase output.
I’arts (c) and (d) are auto-transformer type voltage- Fig. 32-Vectors comprising the relaying quantity II+KZ,J
sWegat,ing networks and parts (e) and (f) are the all-im- shown for K=+15. Z, vectors magnified in line-to-ground
‘Ibfer to Chnpt. 2. fault cases.
2RI,
h’i =2RI
“=R+r+z
E = 2ZRI,
xy R+r+Z
(i) Kegntive-sequence-current segregating filter and relay

ACTUAL ClRC”,T EOUIVALENT C,RC”,T

(a) Polyphase positive-sequence-voltage segregating filter (j) Positive-sequence-current segregating filter

r 2R _
Same as (j) except b and c leads crossed
as shown dotted
I,=I,,=aI,,
I, = I?, =a212, Ei =2R12 ~ i* =R+jR/,&
I,,=0 (k) Negative-sequence-current segregating filter

s
If R is pure resistance, then:
r =0.5R and X =O.SGGR.
Si.’0 .’b ”c lc
Ei = jd-sRI,
Z* =&R&3”‘= 1.5R+jO.s@R
\Vhen It is pure resiskmce, then
ACTUAL ClRC”,T EQUrvALENT
ClRC”lT r = 0.5R nntl X = O.SGGR
1) POlYph3Se IlCg3t ive-scqrterlce-volt:Ige segregating filter (Same as positive-sequence I) Pas.-seq.-current segregsting filter. For use only where there is no zero sequence.
filltar csc*cl)t for intcrchnnge of b and c 1c:ds)

m) Keg.-seq.-current segregatin g filter. For use only \vhc,rca there is no zero seq.

1‘7.
‘A>.=Z’[ x =-3!!K[
%+z’ ’
E:i = -3111,
Z’ =&ReJ30’ = 1.5R+j0.86CiR
If R is pure resistance, tlwn
r=O.SR lllld S=0.8(iliK
I
Ei =3Re-,“0’12
z* = ~/:j&“O”
Z* =0.5ri'+jO.259R
\Vhcn li is pure resistance, then: If IL! is pure resistance, then:
r =O.SR and S =O.BMR T = 0.58 and S = 0.8UiR
(Sole: l~equiws Spc~c.i:d Poterl-
tial Transformer Connection)
(e) Positive-sequence-voltage segregating filter

Note that if R is open circuited


I,=310 &.=3Z'I,

Z* =0.5k+jO.28DR
IVhen R is pure resistance, then: Note: Residual or neutral cur
r=O3R and S=0.866R rent, is three times the zero
(Sate: ltequires Special Poten- sequence current. (I. =310)
tial Transformer Connection) (p) Zero-seq.-current segregating filter (Neutral or star-connected current transformers
(f) Kegative-sequence-voltnge segregating filter
I = -~&~,+~V&I+K&)~O=
Z+Z’

Ei=$h’o
z*=o = -2R*(l,+liloj -’
KT”A,L ClRC”lT EOUNALEHT CIRCUIT
(g) Zero-seq.-voltage segregating filter (otherwise cxllctl star-scrics transformer con- Z* = R,+Ro+z
ACTUALClRC”lT EO”I”ALENT ClRC”lT z = Self in~pcdanc*c of indicated wind
ncction)
ing of three-winding reactor.
(q) Comt)ined pas-seq.-current, and weighted zero-seq.-current segregating filter
R**=Reference impedance of filter.
Z=Impedance of equivalent circuit
of filter.
General Equations and Nomenclature Z’= Imnedance of connected burden
x = Polarity marks.
1 x =-2RlL Ei = -2RI, E =E,+aEb+a% z ~z”+aza+cl~zc
E,=Internal voltage of equivalent cir.
I I
E,,=
-gr, z=R+z
z+z’ 3 3 cuit of filter.
I,= Current in burden.
E =Eo+a%+a& z =Za+a%+aL
2 2 E,,=Voltage at burden terminals, tak.
3 3
- I-

z = Self impedance of indicated wind- ine into account reeulation in the


ing of three-winding reactor as E =Ea+Eb+Ec z =zo+zb+zc filter. For maximum power out.
would be measured with other 0 1 0 1 put from a given filter make

two windings open circuited. Z’=.?. For maximum power out-
Note: A three-winding reactor is a= -O..S"+jO.866 a'= -KS--j0.866 put from a given filter feeding in-
used having a mutual reactance Ei to a pure resistance ‘burden
R/& between each of the b and c Z*=z+z’ E,,=ZsZ'=E, " (Z’= R’) make
zi-z’
phase windings and the metering R’=Z.
circuit winding. N-Current transformer or potential
(h) Positive-sequerl~e-rurrellt scgregat ing filter and relay transformer ratio as indicated.
Fig. 31-Typical sequence segregating networks.
*More generally Z is the inwedance mensured on the terminnls z, y with the burden Z’ disconnected zero lenkage impedance and zero exciting current.
and tile awlied voltnues E.:.. Eb, E. set e<unl to eero (or npplied currents I.. Ib, I. nmle zero **IL. the reference iwpedance of the filter 18uy be any vector vslue or II pore resistamx. The othr
by 0~” circuiting correspondingleadsin t I mecase of current tiltera). This includes in the proper filter iropadances must take corresponding values IIS indxated by their defining equations.
manner tile impedances of the potential or auxiliary current transformers. The values of Z They are resistances and reactanwa as indicated by the symbols on the diagram* only when
given Rbore are bnwrl on tlbe we of idwl potcnlinl nod nllxilinry current transformers having tlw rcfcrencu ioi~wdance. II. is rurc rcuibtance.
376 Relay and Circuit-Breaker Application Chapter 11
‘1%
length being one-fifteenth of the 1~1,vector. The combina- cral time-delay reclosures. In the event of a tripout after ‘h.,.
tion, Il+klo, is the discriminating quantity used in the the third reclosure the line is locked out until the relay is
Type HCR pilot-wire relay which in effect totalizes the reset manually. However if the line LLhol(ls,” even on the i
two ends of t.he circuit. It, is a single quantity having, for a third “try,” the reclosing relay resets automatically, and is
majority of systems, a much greater value for fault condi- prepared to repeat the same performance at a later
tions than for load conditions and thus is an ideal discrim- time.
inating quantity. For a feeder sectionalized by a number of fuses, the re-
placement of a fuse involves a service trip. However, an
24. Reclosing opening and reclosing operation interrupts the current be-
Many of the faults occurring on power systems are tmn- fore any fuses blow, and if the fault is transient, the service
sient in nature and if the circuit is opened momentarily, trip is avoided.
permitting the arc to become estinguished, the circuit can “Single-shot” reclosing which is also widely used may be
be reclosed successfully. The necessary power-off time for accomplished by the Type SGR-12 rcclosing relay. As
deionization of the arc is given in Chapt. 13. For example, shown by Logan’s data, it takes care of the large propor-
Logan and MileP have found that on the Georgia power tion of cases. Also a self-reclosing single-pole circuit
system the number of successful reclosures is as follows. breaker is used principally on single-phase feeders to per-
Kumber of trip-outs.. . . . . form the single-shot reclosin, m function without the use of
10090 lOOy&
Successful reclosures relays. Multiple-shot fuses are also used but require de-
1st immediate. ...... layed action of subsequent fuses and necessitate refilling
8400 83.25%
2nd 15-45 seconds. . . . . . manually after each operation.
1084 10.05%
On tie lines or single lines serving important industrial
3rd 120 seconds.. . . . . . . 143 1.42%
loads reclosing is used for quite another purpose, namely,
Circuit lockouts. . . . . . . . . . 553 5. 28y0
to keep the systems from going out-of-step or to prevent
This knowledge is used in a variety of ways. Many ra- loss of essential loads. This phase of the problem is cov-
dial distribution feeders are provided with reclosing relays. ered in Chapt. 13.
-1 very common arrangement, using the Type RC reclosing
relay shown in Fig. 33, provides for one immediate and sev-
III. CONTROL SCHEMES
* ,.,“” . To secure the system benefits expected from the circuit
breakers and protective relays, it is essential that the con-
trol scheme used result in prompt and reliable tripping of
the circuit breaker when the relays indicate a fault within
their protective zone. Two factors are involved: a reliable
source of control power, and a scheme that permits the
breaker to trip free in spite of all manual or automatic
closing agencies.
A control battery provides the most reliable source of
tripping energy, and is connected to the shunt-trip coil ’
by the protective relay contacts as shown in Fig. 34. As ’

BUS

CIRCUIT BREAKER
/
I/ BATTERY

L-TRIP COIL

-RELAY CONTACTS.

.-- ~ “. . ,,, I ‘CURRENT TRANSFORMER

Fig. 33-The Type RC reclosing relay. A single instantaneous Fig. 34-A protective relay and circuit breaker. When the
plus several time-delay reclosures can be initiated with this breaker opens, the auxiliary switch interrupts the trip circuit
relay. to prevent burning of the relay contacts.
Chapter 11 Relay and Circuit-Breaker Application 377

the circuit breaker opens, the trip circuit is broken by an breaker remains open after the circuit breaker has once
auxiliary switch linked to the circuit breaker. closed in and tripped out. This situation continues until
the control switch is restored to neutral or t.he closing con-
25. Electrically Trip-Free Scheme tact of the automatic device opens.
Fig. 35 shows a typical circuit-breaker control scheme,
one of the several commonly used, known as the X-Y relay 26. Mechanically Trip-Free Arrangements
scheme. A station battery provides power for closing and If a circuit breaker is to be closed manually against a
possible fault, it should be mechanically trip-free from the
POS closing linkage. The mechanically trip-free feature pro-
I vides somewhat faster tripping for three reasons. First,
the circuit breaker contacts can be tripped free anywhere
in the closing stroke without waiting for the closing current
to be cut off before acceleration towards the open position
can start. Second, with the contacts tripped free from the
closing solenoid the mass to be accelerated is less. Third,
because of eddy currents the flux in the closing solenoid
does not decay immediately when the circuit is opened;
thus there is appreciable magnetic retardation in the open-
ing of a mechanically non-trip-free breaker which has just
e B Y been closed.
High-speed reclosing requires that the circuit breaker be
NEG mechanically non-trip-free so that the contact motion can
Fig. 35-The X-Y scheme of circuit breaker control using a
be arrested before the full open position and the breaker
battery. closed again. To meet this need without encountering de-
layed opening if the reclosure takes place on a permanent
C-Closing contact of control switch.
T-Tripping contact of control switch.
X-Closing contactor or relay.
CC-Closing coil of main circuit breaker. SERIES TRIP
Y-Releasing contactor or relay. 1stontaneous or
rith Inverse Time
P-Typical protective relay contact. .imit (ITL) ITL
B-Auxiliary switch (closed when main circuit breaker is closed). Ittachment.
TC-D-C shunt trip coil of main circuit breaker.

rRANSFORMER TRIP COIL


tripping. The control switch merely controls the applicn- TRIP
t,ion of battery power to the closing solenoid or shunt-trip lnStcntOneOuS
coil as desired. The protective relay, when it operates, ap- or (ITL) I&
ITL
plies battery power to the shunt trip coil. 550 v
The X-Y relay scheme prevents pumping and makes the 440 v A-C
circuit breaker electrically trip-free. The closing contact of PROTECTIVE 2oo v SUPPL’(
CAP;;/;OR ET; RELAY
the control switch picks up the X relay that energizes the 100 v
closing solenoid of the circuit breaker. As the circuit
/
breaker reaches its closed position, an auxiliary switch B TRIP COIL NEON LAMP
energizes the Y relay that seals in through its own front
c80ntacts. The Y relay contacts shunt the X relay, which
opens and interrupts current to the circuit breaker closing
solenoid.
If the circuit breaker trips automatically when it is
closed in on a fault, it will open and will not reclose even
though the operator holds the control switch in the closing
position. The X relay remains shunted by the Y relay un-
til the control switch is returned to the neutral position.
The trip-free relay scheme’ provides a similar action
through the use of a specially designed contactor for con-
trolling the heavy current to the breaker-closing solenoid.
The moving contact assembly of this contactor is tripped
free from the operating armature by a release coil energized
by an auxiliary switch when the circuit breaker reaches its TR’PP’NG
TRANSFORMER 1 TaTECTlVE RELAY
closed position. Thus even though the closing contact of
the control switch or of an automatic closing device re-
mains closed, thereby holding the operating armature
closed, the circuit to the closing solenoid of the circuit Fig. 36-A-C tripping schemes.
fault,, a mechanism has been designed that is mechanically
trip-free on the secxondopening but not on the first,, except
when the circuit, breaker is initially closed.
27. A-C Tripping
Tn less important locations, tvhere the cost and main-
tcnnnco of a control battery is not justifiable, vnriolIs forms
of a-c tripping are employed for the smaller, lower voltage
circuit breakers. Some of the more desirable of these are
shown in Fig. 36.
The series-trip and transformer-trip schemes are used
where the accurate magnitude and timing characteristics
of :L protective relay arc not required. The transformer
t,rip is used where the primary voltage or current is too
great for the series trip.
The capacitor trip and a-c shunt trip require a source of
a-c cbontrol power. The capacitor trip is much to be pre-
ferred in most casts because its ability to trip is not im-
paired by the momentary drop in voltage at the time of a
fault. The a-c supply is taken from the source side of the -“_ __., . .._. - I _ .

circuit breaker so that the capacitor is charged before the Fig. 37-Low-voltage distribution panelboard.
circuit breaker is closed. R-c shunt tripping can be used
only where the reduction of voltage at time of fault on the against overloads and short-circuits. Separate protective
protected circuit will not prevent tripping by some trip- eqliipment is required for utilization devices such as
ping agency. motors.
The circuit-opening relay scheme and the tripping-trans- For more important and higher capacity circuits, metal-
former scheme are similar to the transformer-trip scheme enclosed, drawout assemblies of air circuit breakers, as in
in that the line current transformer supplies the trip-coil Figs. 38 and 39, are used. Typical applications are found
energy. However, a protective relay is added and must be in main feeders of the lighting and utility circuits de-
supplied by the same or by a different current transformer. scribed above, and for the low-voltage power circuits of
The trip coil imposes a heavy burden on the current trans- such buildings as well as industrial plants and generating
former, and there is a definite lower limit to the primary stations. These breakers may be operated either manually
current at which tripping can be secured. The relay must, or electrically (under some conditions only electrical op-
of course, be set above this value. eration is recommended) and may be obtained with direct-
acting series overload trips or relays which will give selec-
IV. APPLICATION OF CIRCUIT BREAKERS -.-. II- .
‘cl”---“-
The application of circuit breakers to power and lighting
circuits involves the choice of the type of breaker and its
mounting or housing as well as determination of the specific
ratings required for the particular service.
28. Typical Circuit Breaker Construction and
Practice
Low Voltage Circuit Breakers-Circuit breakers
intended for service on a-c circuits up to 1500 volts and
d-c circuits up to 3000 volts are classified as low-voltage
t,reakers.108 For such service air breakers have many ad-
vantages and are generally used in preference to oil
breakers. They are inherently fast in operation, free from
firehazard, require little maintenance on repetitive service,
and, because of the low voltage, are simpler, more com-
pact, and easier to handle than oil breakers.
For low-capacity branch lighting and utility circuits
such as are found in commercial and public buildings,
small, molded case ‘Lthermal-breakers” are grouped in
panelboards such as that shown in Fig. 37. Such breakers
are usually operated manually and are available in ratings
up to a maximum of 600 amperes load current and 25 000
amperes interrupting current. They provide automatic Fig. 38-1600 ampere, 600 volt, Type DB-50 air circuit breaker ‘r
inverse-time overload t,ripping to protect circuit wiring -50,000 amperes interrupting capacity.
Chapter 11 Relay and Circuit-Breaker Application

Fig. 41-Typical metal-clad drawout switchgear for 13.8 kv


indoor service.

For indoor service at, from 1.5 to 15.0 kv and up to 500


mva interrupting duty, magnetic-t,ype air breakers in
metal-clad assemblies have become predominant, although
metal-clad oil breakers are also used under aclvcrse atmos-
pig. 39-Typical installation of low-voltage, metal-enclosed
pheric conditions. A typical breaker and assembly are
switchgear. shown in Figs. 40 and 41. ,Ilt.hough int,crrupting time and
space required arc the same for medium voltage air and
ti\.(l isolation of a faulty circuit. The metal-enclosed gear oil breakers, the freedom from oil-fire hazard and lower
is fac+ory assembled and tested ancl provides maximum maintenance on repetitive service are distinct advantages
wii:tbility, safety and ease of maintenance with minimum of the air breakers. Many such breakers arc used, both
illt,crrllption to service. These breakers may be used to for power and lighting feeders and to control individual
provide control as well as running overload and short- large indust,rial or powerhouse-auxiliary motors.
circllit protection for individual motor circuits. For indoor service at interrupting ratings above 500
Even where unusllal atmospheric conditions are en- mva, and for any rating at voltages between 15 and 34.5
wuntered (see Sec. 30), low voltage air breakers may be
11sct1 if they are mounted in suitable sealed enclosures.
Power Circuit Breakers - Medium Voltage -
Circuit bronkcrs intended for service on a-c circuits above
1300volts are clnssified as power circuit breakers.

; ,, .^^ ” .._._I__.^ x- __.. ., __ _

Fi& 40-Magnetic type :ai r.circuit breaker-4160 volts, 150- Fig. 42-Compressed air circuit breaker in station cubic :le-
mva interrupting capacity; type 50-DH-lW 15-H kv insulation class.
380 Relay and Circuit-Breaker Application Cha.pter 1.1

,%j
kv, compressed-air breakers mounted in station cubicles tions both normal load and interrupting kva arc relatively +T
have become standard. A typical unit is shown in Fig. 42. low, and such factors as fire hazard, space requirements, ,,3
Circuit-breaker practice in outdoor substations is more appearance and rapid maintenance may not be critical. ;,
varied than in indoor service because there is a greater For such service frame-mounted oil breakers with open ?.
range in the requirements. In rural and outlying substa- buses and disconnecting switches are frequently used be f$
cause of lower cost. A typical installation is shown in Fig
43.
For suburban and urban outdoor service up to 15 kv and ’
up to 5OO-mva interrupting duty the many advantages of
metal-clad oil-less switchgear (freedom from oil-fire ha%
ard, compactness, appearance, ease of maintenance and
flexibility) have resulted in the use of such gear for the

Fig. 43--Installation view of outdoor 23 kv, 250 000 kva, oil


circuit breakers.

Fig. 45-34.5-kv, lO$O-mva, frame-mounted, oil circuit


breakers.

majority of these substations. The metal-clad gear is


usually throat connected to the transformer(s) although
roof bushings are sometimes used, especially with single-
phase transformers. A typical installation is shown in Fig.
44. The cost comparison between open gear and metal
clad varies with the voltage and kva rating, the type of
open structure used, the cost of real estate, the labor facili-
ties of the utility, and the method used in estimating over-
head and fixed charges.
Oil circuit breakers are used where severe atmospheric
conditions are encountered, either frame mounted or in
metal-clad structures.
For outdoor service at interrupting ratings above 500
mvn and for all interrupting ratings at voltages between
15- and 34.5-kv, oil breakers are essentially standard. A
typical installation is shown in Fig. 45.
High-Voltage Breakers-Almost all circuit breakers
Fig. 44-Typical outdoor coordinated unit substation. rated above 34.5 kv are mounted outdoors and are oil
chapter 11 Relay and Circuit-Breaker Application 351

Standard values of rated voltage are based on operation


at altitudes of 3300 feet or less. Standard equipment may
be operated at higher altitudes if the maximum operating
voltage is not more than the maximum design voltage
times a correction factor, as follows:
Altitude in Feet Voltage Correction Factor
3300 1.00
4000 0.98
5000 0.95
10000 0.80
Operation at altitudes other than those listed is covered in
AIEE $113 but operation above 10 000 feet should be given
special consideration because of possible influence of alti-
tude on interrupting capacity.
Rated ImpuZse Withstand Voltage-Impulse mt-
ings of standard power circuit breakers are listed in AS;1
C 37.6. A correction (the same as that given above for
rated voltage) should be made for the effect of altitude
above 3300 feet on impulse strength. No such ratings are
given for low-voltage air breakers because such breakers
are seldom exposed to impulse voltages. When necessary,
impulse strength could be taken as the crest of the GO-cycle
test voltage.11o
The surge protection of the system should be coordi-
nated with the impulse strength of the breaker, both across
the open contacts and to ground. Attention should also
be given to increase in surge voltage because of reflections
Fig. 46-230-kv, 3500-mva, floor-mounted, oil circuit breaker. which occur at breakers when their contacts are open,
especially where cables are involved.lo4
hrcakers of the grounded metal-tank type. Pneumatic Frequency-Standard power circuit breakers are
operut,ing mechanisms predominate and these can be ar- rated at 60 cycles. Service at other frequencies must be
ranged to give 2O-cycle reclosing. A 230-kv installation is given special consideration. Although standard GO-cycle
shown in Fig. 46. power circuit breakers are given corresponding continu-
Some csperimcntsl installations have been made of air- ous-current ratings for 25-cycle service,‘Oj other ratings
I)&, and oil-poor breakers at high voltage and a table of (e.g. interrupting capacity) must be checked and acces-
ratings for such breakers has been included in the stand- sories must be made suitable. Low-voltage breakers are
:trtls as a guide for development. At the present time it is listed for GO-cycle service and for direct current. Service at
(lificult to produce and install an oil-less outdoor breaker other frequencies requires special consideration.
having current transformers and potential devices to com- Rated Continuous Current-This rating is based
pete economically with conventional oil breakers. There on operation of the circuit breaker or switchgear assembly
is also the hazard of fragile porcelain structures. SO far where the ambient temperature (measured outside the
there is no definite indication of the place such breakers enclosure where such is supplied) does not exceed 40°C and
will fill in normal practice. the altitude does not exceed 3300 feet. Operation in higher
ambient temperature must be given special consideration.
29. Standard Ratings of Circuit Breakers Molded-case, thermal-trip, low-voltage circuit breakers
The standard ratings of the several classes of circuit are calibrated on the basis of an ambient temperature of
I)rcakers arc defined in ASA, XIEE, NEMA, and Under- 25°C. Operation in ambient temperatures other than
Witers Laboratories standards. lo5-111It is not the 25°C will affect the tripping characteristic and must be
intcnt,ion here to review these ratings in detail, only to taken into consideration. Standard equipment may be
(liscuss the principal factors involved in the selection of a operated at higher altitudes by reducing the continuous
(*ircuit breaker for a particular application. current rating in accordance with the following table.
Rated Voltage-In general a circuit breaker is given Altitude in Feet Current Correction Factor
a rated voltage which designates the maximum nominal
Wtem voltage for which the breaker is intended and also 3300 1.00
:I n~aximum design voltage which designates the maximum 4000 0.996
Wrat~ing voltage for &ich it is intended. For certain 5000 0.99
10000 0.96
lo\v-Voltngc breakers this distinction is not made and rated
volt:~ge should bc taken as maximum. Standard voltage Rated Interrupting Current-Rated Interrupt-
ratings of power circuit breakers are in terms of three- ing Mvu-Operating Duty-Interrupting Time-The
phase line-to-line voltage. rated interrupting current of a power circuit breaker is
382 Relay and Circuit-Breaker Application Chapter 11:

has(xd on the rms total current in any pole of the breaker


at the time the breaker contacts part. (Xote that this time
may be considerably shorter than the interrupting time.)
The correct value of rated interrupting current for an op-
erating voltage other than rated value can be calculated by
the following formula:
Amperes at operating voltage =amperes at rated volt-
rated voltage
age X Operating voltage should, of
operating voltage.
course, not, exceed the maximum design voltage. Also, no
matter how low the voltage, the rated interrupting current 60

is not increased above the rated maximum interrupting


current. Standard rating tahWos give the value of rat,ed
interrupting current at rated voltage as well as the rated
2.5 IO 20 30 40 50 60
maximum interrupting current and the corresponding
INT. AMPS. X 1000
operating voltage. Over this range of voltages the product
of operating voltage and current is constant and this pro-
duct times a phase-factor is called rated interrupting mva. X ZERO SECONDS SHALL BE INTERPRETED To MEAN NO INTENTIONAL T,ME DELAx

For 3-phase circuits the factor is 1.73, for 2-phase circuits ** 15 SECONDS OR LONGER.
2.0, and for l-phase circuits 1.0. However, standard Fig. 47-Breaker rating factors for the usual reclosing duty
breakers are rated only on a three-phase basis and rules cycles.
are provided (given later in this chapter) for determin-
ing the equivalent three-phase interrupting ratings. C. The Breaker Rating Factors for the Usual Reclosing Duty
The above values of rated interrupting current are based Cycles are obtained by reference to Figure 47. This gives the
on specified conditions of circuit recovery voltage, breaker percentage rating factor for the duty cycle in question at t,llc
performance, and also on standard operating duty. For rated interrupting current at the circuit voltage of the system to
which the breaker will be applied.
power circuit breakers rated 50 mva and higher (“oil-tight
or oil-less”) this consists of two unit operations (CO) sepa- D. The breaker interrupting ratin g at the specified reclosing
rated by a l&second interval. Each unit operation consists duty cycle is obtained by multiplying the rated interrupting
of breaker closing followed by its opening without inten- amperes by the rating factor.
tional time delay. This standard operating duty is desig- Example: Determine the interrupting rating of a 34.5 kv,
nated by the expression, CO+15 sec.+CO. For power IOOO-mva breaker used at 23-kv on Reclosing Duty Cycle I.
circuit breakers rated 25 mva and lower (“non-oil-tight”) 1. Breaker Interrupting Rating on Standard Duty Cycle:
the standard operating duty consists of two unit opera- 17 000 Amperes at 34.5-kv
tions separated by a two-minute interval (CO+2 min. + 25 000 Amperes at 23 kv
2. Figure 1, Curve A, gives a rating factor of 91.5 percent at
CO). For any other operating duty the standard inter-
25 000 amperes for reclosing duty cycsle I.
rupting ratings should be reduced in accordance with rules 3. Breaker Interrupting Rating on Duty Cycle I at 23 kv
given in NEMA standards.lo” The following revision of the = Rating Factor, 91.5 percent X25 000 Amperes= 22 900
current rules is now being recommended by AIEE to ASA. Amperes.
NEMA STANDARDS-RECLOSING DUTY CYCLE FAC- E. Breaker Rating Factors for Other Than the Usual Re-
TORS FOR OIL-TIGHT AND OIL-LESS POWER CIRCUIT closing Duty Cycles
BREAKERS-REVISION OF 11/17/49 1. The standard for the number of opel,ations is two (2).
Additional operations increase the duty on the contacts and
SC-6-90 BREAKER RATING FACTORS FOR RECLOSING
therefore a rating factor is applied to enable circuit breakers
SERVICE (Rev.)
to meet standards of interrupting performance. (See SG6-40,
A. The interrupting ratings of power circuit breakers may be Par. C)
reduced for operating duty cycles other than the standard, CO (a) For Three Operations--Use mean factor between 2 and
+13 Sec.+CO (See SG6-40, Par. B) to enable them to meet the 4 operations, (Standard and Duty Cycle I).
standard of Interrupting Performance. (See SG6-40, Par. C)
Kate: Such factors do not apply to highly repetitive duty at or Example: Of15 Sec.+CO+15 SY.+CO
near the continuous rating of the breaker. y0 Factor=97 for 20 000 Amperes
B. For purposes of this section, the following duty cycles shall (b) For Five Operations-Use Factor obtained by re-
bc considered as representing the Usual Duty Cycles for Rc- ducing that for 4 operations (Duty Cycle I) by difference
closing between 2 and 4 opemtions.
Reclosing Duty Cycle IO+15 Sec. **+CO+l5 Sec.** Example: Of15 Sec.fCOfl5 Sec.+CO+15 Sec.
+CO+l5 Sec.**+CO fCOfl5 Sec.+CO
Reclosing Duty Cycle II 0+0 Sec.*+CO % Factor = 94 - 6 = 58 for 20 000 Amperes
Reclosing Duty Cycle III 0+0 Sec.*+C0+15 Sec.** 2. The standard for the interval between operations is 15
fCOfl5 Sec.**+CO seconds. Reducing this interval increases the interrupting
*Zero seconds shall be interpreted to mean no intentional time duty and therefore a rating factor is applied to enable
delay. breaker to meet standards of interrupting performance.
**15 seconds or longer. (See SG6-40 Par. C)
chapter 11 Relay and Circuit-Breaker Application 353

(a) For Two Operations-Reduce 100 percent factor for the interruption of current,s from 2: percent to 100 per-
15 secondshy an amolmt, etlual to proportionate part of the cent of the rat,cd value.
reduction for zero interval ns determined by the ratio of the The interrupting ratsing of low-voltage air circuit hrenkcm
times.
is based on the rms tot’al short-circuit current which \vo1&1
Esnmplr: Of5 Sec.+CO occur at the end of x cycle at the breaker location if the
%Factor=lOO-g%(lOO-91)=96for20000 line terminals of the breaker mere short-circuited. The
.Imperes impedance of the breaker which interrupts t,he circuit
(h) For Four Operations-Multiply the factor for Duty should not be included in calculating the interrupting duty.
Cycle I 1)~the :Lppropriate factor determined under para- Also, for three-phase a-c circuits the breaker rated inter-
gr:lph 2 (a) for each interval less than standard. rupting current should be chosen on the basis of the WY-
l~xnmple: Of5 Sec.+C0+5 Sec.+CO+S Sec.+CO age of the currents in the three phases. For single-phase
% Factor=94X96X%X96=83 for 20 000 circuits the average current which would occur for three
Amperes successive short-circuits should be used. For average sys-
((,) For Three or Five Operations-Use combination of tems the average 3-phase or l-phase rms total current will
Rule 1 and Rule 2 (a) applied for each interval. be equal to 1.25 times the initial subtransient symmetrical
Example: 0+5 Sec.+C0+5 Sec.+C current.
To Factor = 97X 9GX 96 = 89 for 20 000 Am- Low-voltage air breakers for d-c service are also applied
peres on the basis of the short-circuit current without the breaker
:1. The usual instantaneous reclosing cycles are Duty Cycles in place; however, the maximum current is measured.
II :mtl III. V:wintions we in the number of operations. The standard rated interrupting current of lolv-voltage
(:L) For Three Operations-Use mean between factors for air circuit-breakers is based on a standard operating duty
Duty Cycles II and III. designated 0+2 min+CO. The breaker opens the circuit
Example: 0+0 dec.fCOfl5 Sec.+CO and, after a 2-minute interval, is reclosed on the fault,
5%F:ictor=E$E= 89.5 for 20 000 Am- lvhich it opens without purposely delayed action.
For other interrupting duty the standard interrupting
peres rating should be multiplied by factors given in Table 6.
(1)) For Five Operations-Use factor by reducing that for
4 operations (Duty Cycle III) by difference betbveen2 and TABLE 6**-OPERATING DUTY FOR RECLOSING SERVICE
4 operations. FOR LARGE AIR CIRCUIT BREAKERS
Example: 0+0 Sec.+CO+l5 Sec.+CO+l5 Sec.+CO
+I5 Sec.+CO Percent;tgeof
7. Factor=85-(94-85) =76 for 20 000 Duty Cycle Published Inter-
amperes rupting Rating

The reclosing duty cycle factors for breakers rated 25 B-O+2 min.+CO.. 100
C-0+2min.+CO+2 min.+C0+2 min.+CO.. 70
mva and below (non-oil-tight circuit breakers) are given in
D-O+30scc.+CO+30sec.+C0+30se~.+CO.. GO
‘I’ahlc 5. *E-O+0 sec.+CO+O sec.+CO+O sec.+CO. 25
TABLE 5*-RECLOSING DUTY CYCLE FACTORS FOR NON OIL- F-300 cycles CO+15 min. intervnls 30
TIGHT OIL POWER CIRCUIT BREAKERS *G-O+Osec.+C0+30 sec.+CO+S5 sec.+CO. 30
H-O+15sec.+CO+30sec.+CO+73src.+CO.. 40
Percentttgeof I-O+60 sec.+CO+60 sec.+CO. 70
Standnrd Inter- J-O+15 sec.+CO.. GO
Duty Cycle rupting Capac- *Zero secondv shall be interpreted to mean no intentional time delay.
ity Rating **Copied from X7-63 of NEMA std. 46-109.
SoTE-Denting factors are not available for automatic reclosing service on
IS--CO+2 min.+CO. d-c circuits. Circuit breakers designed for tbe purpose are ordinnnly requirrd.
100
C-CO+2 rniri.+CO+2mir~.+CO+2min.+CO TO
I)--Co+3Osec.+C:0+30 sec.+C0+30sec.+CO GO This table does not apply to molded-case breakers be-
cause they are not used on reclosing service.
*‘I<:-(:O+O scc.+CO+O sec.+CO+O sec.+CO.. 25 Rated Momentary Current-The maximum rms
F-300 cycles CO at 15-min. intervds. 30 total current (including the d-c component) through a
**C--CO+0 sw.+C0+30 sec.+C0+75 scc.+CO 30 breaker, measured during the maximum cycle, should not
exceed the rated momentary current. For power circuit
JJ-CO+15sec.+CO+30sec.+CO+75sec.+CO 40 breakers this rating applies to each pole of the breaker
I--CO+80 scc:.+CO+GO sec.+CO.. 70
*J--co+15 sec.+co. _.
taken individually and for the worst condition of asym-
GO
metry.
NOTE-The standard operating duty (duty cycle) for non oil-tight oil power
“rCllit breakers is Z-CO operations with B Z-minute interval. Rated Four-Second Current--A four-second cur-
*Reproduced from NEMA 46-116 SGG-90.
**Zero seconds shall be itierpretei to mean no intentional time delay. rent rating is given for power circuit breakers based on the
rms total current measured or calculated at the end of one
The interrupting time of a power circuit breaker is the second. For standard breakers it is numerically equal to
maximum interval from the time the trip coil is energized the rated maximum interrupting current, and l/1.6 times
at normal control voltage until the arc is extinguished. the momentary current. For normal circuits this means
This time is published for standard power breakers for that the permissible duration of the maximum permissible
384 Relay and Circuit-Breaker Application Chapter 11 i

fault current is four seconds. No current rating is given 30. Selection of Circuit Breakers for Specific Sys- ’
tern Conditions 1
for times longer than four seconds but less than continu-
ous. General-The great majority of circuit breakers are ,I
No similar short-time rating is given for low-voltage applied as three-pole, gang-operated breakers in three .;
breakers because such breakers are normally equipped with phase power systems which are ungrounded or grounded at
direct acting series overload trips. the neutrals of generators or transformers. Consequently
Rated Making Current--This rating is given to the standard ratings of most circuit breakers are given
power operated power circuit breakers only. No provision on this basis. For such an application it is sufficient (in so
is made for manual closing of oil-less breakers or for oil far as rating is concerned) to select a breaker such that
breakers above 250 mva. It is essentially a design require- none of its standard ratings will be exceeded under any I
ment to preclude welding of contacts or other undue dam- condition of system operation.
age when a breaker closes on a fault. It is required that For example, the voltage rating should include allow-
the breaker ‘lbe immediately opened without purposely ances, where applicable, for such factors as line voltage
delayed action.” regulation, shunt or series capacitance, overexcited or ‘:j
The values of momentary and making-current rating for overspeed operation of synchronous machines, line-drop- I 1:
present standard breakers have been so selected that these compensation of tap changers or feeder voltage regulators ‘$8 t
ratings will not normally limit application of the breakers and the operation of transformers on tap positions other 4::
when they are applied in accordance with the recom- than the nominal values. Both voltage and continuous cur- “,
mended “simplified procedure,” which will be described rent ratings should take into account future load growth and
later in this chapter. An exception may occur where the contingencies associated with circuit or apparatus
motors produce a large portion of the fault current. outages. The various ratings associated with interruption
Breakers may also be applied on the basis of decrement of faults should include allowances for increase in genera-
curves or detailed calculations and, under unusual condi- tion, addition of parallel circuits or transformers, and any
tions or in existing installations, momentary current may other system changes which would increase interrupting
be the limiting rating of the breaker. duty. The calculation of fault currents and their inter-
Rated Latching Current -This rating is distin- pretation in terms of interrupting ratings will be con-
guished fromratedmaking current in that the breaker must sidered separately in Sec. IV.
latch when it closes on a fault of the specified rms total System frequency will usually be substantially constant .t
current magnitude. Thus delayed tripping is permissible at 60-cycles. Operation at other frequencies or at varying
within this rating if the magnitude, duration, and opera- frequency requires special consideration.
ting duty are within the short-time and interrupting rat- The interrupting time of the circuit breakers themselves ‘%,.
ings. For present standard power circuit breakers the is subject to choice in few cases. Considerations of transi- I)I
latching current rating is numerically equal to both the ent stability may dictate one or another type of relaying ,:-
four-second rating and the maximum interrupting current system in order to obtain sufficiently fast clearing. How-
rating. However, the latching current is measured during ever, considerations of system operation and stability may
the maximum cycle whereas the interrupting rating is or may not call for fast reclosing, and a choice should be
measured at the time the contacts part and the four- indicated.
second rating is measured at the end of one second. Determination of Equivalent Three-Phase Volt-
Reclosing Time-For outdoor reclosing oil-circuit age and Interrupting Ratings-The standard rat-
breakers standard and fast reclosing times are shown in ings of most power circuit breakers are given in terms
Table 7. These values apply only to breakers which have of three-pole breakers for three-phase systems. These volt-
a continuous current rating of 1200 amperes or less when age ratings are based on the line-to-line voltage of the
operated in conjunction with an automatic reclosing circuit, and the interrupting ratings are given in a,mperes
device. and approximate three-phase kva. In order to select the
proper I-, 2-, 3-, or d-pole circuit breaker for special ser-
vices on three-phase circuits, and for use on two-phase
TABLE 7*-RECLOSING TIME FOR OUTDOORRECLOSING and single-phase circuits, the equivalent three-phase
OIL CIRCUIT BREAKERS (60-CYCLE BASIS) breaker rating can be determined from Tables 8, 9, and
10.
Reclosing First, the three-phase voltage rating of the breaker type
Ruted Voltage Time-Cycles must be equal to or greater than the voltage determined
Standard Fast from column 5 of the tables.
Second, make a tentative breaker selection on the basis
7,5to23kvincl.(under500mva) _...,.,.,.,, 30 30 of equivalent three-phase kva in accordance with column
15 to 23 kv incl. (500 mva and higher). 45 30 6 of the tables. If the computed equivalent three-phase
34 5 to 69 kv incl. (500 mva itnd higher). 45 20
115 to 230 kv incl. (500 mva and higher). 30
kva is more than 95 percent of the approximate kva rating
20
of the breaker type a further check must be made.
NOTE I-These
maintained
time values ~swme rated control
at the mechanism. In c8m the control
voltage or operating pressure
voltage or pressure drops to
cases the product of rated voltage times rated inte
90 percent of rated voltaae or pressure, the reclosing times will be increased to 110
percentof that tabulated.
current times 1.73 (standard three-phase ratin
NOTE II-Reclosing time for oil-less breakers has not yet been standardized. equal or exceed the equivalent three-phase kva c
*This table was reproduced from NEMA standard 46-116 X6-95.
in column 6,
Chapter 11 Relay and Circuit-Breaker Application 385

TABLE ~-DETERMINATION OF EQUIVALENT THREE-PHASE VOLTAGE AND INTERRUPTING RATINGS FOR THREE-PHASE SYSTEMS
-
Select a breaker whose np-
proximate 3-phasekv-a. intcr-
Select IL breaker whose volt- rupting rrrting is equal to “1
Typical System Connections Type of rage.rating is qua1 or greater grcster than the value LU de-
Line than the fquivalent 3-phnse termined,below.
No. SyYtenl ;~;f;~y (\J) 8s determined I =Required interrupting CUT-
rent nt service v0ltnac.t
v8 =Equivalent &phase volt-
ape ns obtained from ndjacent
col”“l”.
--
3-mire
grounded
or J-wire 1 pole in Greatest wire to wire 0.87 I x 1.73 va
with neutral voltage I
ne”tiYIl wire
grounded
or not

3-wire
grounded
or 4-w& 1 pole in Greatest wire to wire 0.87 I x 1.73 v,**
with outside voltage
neutral
gr”““dE!d
or not

3.wire
arounded Independent
cl~lt4;wire 1 pole 1.15 times greatest wire to I x 1.73 Vn
breaker wire voltwe*
neutral in an
vroundcd outside
or not wire

3-wire 2 poles
grounded in outside Greatest wire to wire I x 1.73 v3
or 4-wire nnd neutral vo1tnue
with wire
neutral respectively
wounded
or not

3-wire
grounded 2 poles
or 4-wire single- I x 1.73 v1
with phase
neutral outside
grounded wire
or not

3 wire
grounded
Gx&e,t,“,“twire to wire I x 1.73 v1
,t‘kwLre
neutrnl
grounded
or not

3-wire
grounded
or 4-wire
with 4 poles
neutral
grounded
or not

2 poles
3-wire un- single-
grounded phase
circuit

Greatest wire to wire I x 1.73 v1


3-wire un- 3 poles voltage
grounded

t This value must not exceedthe mnximum current interrupting rating listed in breaker interrupting tables.
* SeeNIXA rule SCX-210reuurding exceptions for 8 cycle breakers. In such in&awes use Line 6.
** ‘fheuerecommendationsapply to isolated feedersonly. Where possibility of phaseto phasefaults exist refer to Line 3 for applicntion.
386 Relay and Circuit-Breaker Application Chapter 11
TABLE ~-DETERMINATION OF EQUIVALENT THREE-PHASE VOLTAGE AND INTERRUPTING RATINGS FOR TWO-PHASE SYSTEMS

Select R breaker whose ap.


proximnte
rupting
Z-phase. kv-a. int*,.
rntmp i.s equal
._.op
Select a brenkcr whose volt.
.4ge ratinK is equal or greater greater than the value BS de-
Line Type of termined below.
No. Typical System Connections System than the equivalent S-phase
voltage (VZ) as determined be- 1 =Reqnired interrupting cur-
low. rent at service v0itage.t
v, =Equivalent 3-phase volt-
age ns obtained irom adjacent
column.
--

R-wire 2 polea
wounded any two Greatest wire to wire *I x 1.73 VI
1 or not wires voltage
Generator +-%i%

a-wire
2 grounded 3 poles Greatest wire to wire *I x 1.73 v1
or not voltap3

-_ .

3
e
Generator
4-wire un-
grounded

-.
2-2 pole

_
I x 1.73 VI

4-wire un- 4 poles I x 1.73 VI


4 grounded

Generator
_

5 5-wire 1 pole
grounded any “out- 0.87 I x 1.73 v,
or not side wire”

6 5-wire 2 poles
grounded any “out-
side wire” 0.87 I x 1.73 vi
or not
and neutral

.
?

5-wire 2 poles
grounded d-c. any
“outside 0.87 I X 1.73 VI
or not
wires”

8 5-wire 4 pole.7
grounded all “out.side Greatest wire to wire
I x 1.73 v1 I.,
or not wires” voltage

-
* I is the current in one of the outside wires.
t This value must not exceed the maximum current iuterrupting rating listed in breaker interrupting tab&.
Chapter 11 Relay and Circuit-Breaker Application 3%

TABLE 10 -DETERMINATION OF EQUIVALENT THREE-PHASE VOLTAGE AND INTERRUPTING RATINGS FOR SINGLE-PHASE SYSTEMS
- - -

Sclcct a hrenkcr whosr np-


roximate 3.phavz, kv-a. inter-
opting rst,ing is equnl or west-
Select a brcskcr whose volt. r than the value as determined
J,ine No. of $4ge rating is equal or areate dew.
No. Typical Syntrm Connectioov Breaker t han the erruivnlent 3-phase =Rquired interrrlptina cur-
Poles ,oltage (VZ) ~9 determined he- ent at service v0ltnw.t
;: 31”. 1s =Eqnivalent 3-phase volt-
.ae as obtained from adjacent
olumn.
-- --

2-wire 1.73 times wire to rrollnd


0.87 I x 1.73 vx
1 one side (based on NEA1.A rule
voltnge SGO-“05)
wounded

-- -

2
Z-wire
one side
1.73 times wire to gr”\lnd
grounded voltnge

- -_ -- --

a-wire nn- wire to wire rol tLEL’ I x 1.73 v1


:3 wounded

-. --

3-wire
neutral 1 pole in 1.73 times higher
4 may or neutrsl 0.87 I x 1.73 v.,
line to neutral voltage
may not he circuit

-. - grounded
-_ --

3-wire
neutral 1 pole either 1.73 times rewective
5 may or “outside 0.87 I x 1.73 vs
line to neutral voltage
may not be wire”*
grounded
-. -. -_ -.

3-wire
neutral 2 outside Greatest wire to wire
G nmy or IX 1.73 Va
wires voltage
may not he
grounded
- - - -_ -_

a-wire
neutral Greatest wire to wire
7 may or 3 I x 1.73 vs
voltaL!e
mny not he
grounded
- - - - -
* Where 1 phase, 3-wire system has unequal voltages to neutral and 2 single-pole breakers are used in the outside wires. the lower voltage breaker must he interlocked
t0 prevent its tripping for “outside wire” faults, until the higher voltage breaker has first cleared the fault. unless both breakers are selected on high-voltage basis.
t This vnlue musl not exceed the maximum current interrupting rating listed in breaker interrupting tables.

Third, the short-time current rating and the interrupting at this time to give specific limits for capacitive switching.
capacity current limitation must not be exceeded. As an approximate guide special consideration should be
The fault current may be calculated by one of the meth- given when one desires to switch 69-kv cables which ex-
ods described in the next section, and should be checked for ceed 9 miles in length or 115- and 13%kv cables longer
all types of faults. than 7 miles.
Switching of Capacitive Current-When circuit Another problem to be considered is that a large mo-
breakers are used to switch the charging current of lines mentary current may flow when one capacitor bank is
or cables or to switch capacitor banks, abnormally high switched in parallel with another capacitor bank. This
voltages can be produced by restriking in the breaker. current is a function of the capacitance involved and the
Experience lo1has indicated that transient voltages which inductance of the leads connecting the two banks. This
result from such restriking will seldom exceed 2.5 times current may be calculatedlO and should not exceed the
normal line-to-neutral crest voltage on circuits having momentary rating of the circuit breaker.
effectively grounded neutrals. There is relatively little Conditions Aflecting Construction or Protective
hazard to either the breakers or to other apparatus on such Features-There are unusual conditions which, where
circuits. There are insufficient data on ungrounded or they exist, should be given special consideration in the
impedance-grounded systems to draw conclusions. selection and design of the apparatus. Among such un-
Lightning arresters may be damaged if the voltages usual conditions are:
developed are sufficient to cause them to discharge and if, (1) Expogure to damaging fumes or vapors, excessive or
in addition, the line capacitance is large. Because of the’ abrasive dust, explosive mixtures of dust or gases, steam,
random nature of the phenomena involved it is not possible salt spray, excessive moisture, or dripping Vater, etc.;
388 Relay and Circuit-Breaker Application Chapter 11

(2) Exposure to abnormal vibration, shocks or tilting; (b). All circuit breakers subjected to fault currents
(3) Exposure to excessively high or low temperatures; in excess of their interrupting rating shall be elec-
(4) Exposure to unusual trnnspoi-tation or storage conditions; trically operat,ed.
(5) Unusual space limitations ; (c). Where cascading is proposed, recommendations
(6) Unusual operating duty, frequency of operation, difficulty shall be obtained from the manufacturer in order to
of maintenance, etc.
insure proper coordination between circuit breakers.
31. Requirements for Low-Voltage Air Circuit (d). The operation of breakers in excess of their in-
Breakers in Cascade Arrangement* terrupting rating is limited to one operation, afler
“When a plurality of low voltage air circuit breakers are which inspection, replacement, or maintenance may be
connected in series in a distribution system, and the required.”
breakers beyond those nearest to the source arc applied
in the following correlated manner, they are said to be in a In calculating the short circuit current through each
cascade arrangement. step in (al), (a2), and (a3) above it is permissible to include
“In this cascadearrangement, breakers toward the source the impedance of all circuit elements (including breaker
are provided with instantaneous tripping for current values trip coils) between the line terminals of the breaker in
which may obtain for faults beyond other breakers nearer question and the source, but not the impedance of the
the load. Hence, breakers in the series, ot,her than the breaker for which the interrupting current rating is being
breaker closest to a fault may trip and interrupt loads on determined. For example, the impedance of breakers in
other than the fault circuit. Such arrangements are used the first two steps may be inchlded in the calculation to
only where the consequent possible sacrifice in service con- determine the fault current to which the breakers in the
tinuity is acceptable. Where continuity of service is third step will be exposed. Holyever, the impedance of the
desired, selective tripping arrangements of fully rated third-step breakers should not be included.
breakers are required. Where continuity of service is not
important, properly selected breakers may be applied in 32. Selective Tripping of Low Voltage Air Circuit
cascade. Breakers*
“Properly selected air circuit breakers may be applied to
“The following requirements shall be observed: low voltage circuits to obtain selective tripping. The fol-
(a) Cascading shall be limited to either two or three lowing requirements shall be observed :
steps of interrupting rating. (a) Each air circuit breaker must have an interrupt-
(1). The interrupting rating of the breaker or ing rating equal to or greater than the available short
breakers nearest the source of power shall be equal circuit current at the point of application.
to at least 100 percent of the short-circuit current (b) Each air circuit breaker, except those having in-
as calculated in accordance with section 29. stantaneous trips (such as the one farthest removed
The breaker or breakers in this step shall be equip- from the source of power), must have a short-time
ped with instantaneous feattfres set to trip at a rating equal to or greater than the available current
value of current that will give back-up protection at the point of application.
whenever the breaker in the nest lower step carries (c) The Dime-current characteristics of each air cir-
current greater than 80 percent of its interrupting cuit breaker at all values of available overcurrent
rating. shall be such as to insure that the circuit breaker
(2) The breaker or breakers in the second step nearest the fault shall function to remove the over-
shall be selected so that the calculated short circuit current conditions, and breakers nearer the source
current through the first step plus motor contribu- shall remain closed and continue to carry the remain-
tion in the second step, will not exceed 200 percent ing load current.
of their interrupting rating. The breaker or (d) To insure that each breaker shall function to
breakers shall be equipped with instantaneous trip meet the requirements of paragraph (c) above, the
set at a value of current that will give back-up pro- time current characteristics of adjacent breakers must
tection whenever the breaker in the next lower step not overlap. The pickup settings and time delay
carries current greater than 80 percent of its inter- bands of both the long-time and short-time delay e!e-
rupting rating. For the second step of a two step ments must be properly selected.
cascade the breaker or breakers shall have an in- (e) Manually operated circuit breakers shall be
stantaneous trip setting above the starting inrush limited to applications in which delayed tripping re-
current of the load. quirements do not exceed 15 000 amperes or 15 times
(3) The breaker or breakers in the third step shall the coil rating, whichever is greater.
be selected so that the calculated short circuit cur- (f) The time-current characteristics of a breaker in
rent through the first step, plus motor contribution a selective system shall be such that up to four
of the second and third steps, will not exceed 300 breakers may be operated selectively in series, when
percent of their interrupting rating. The breaker required. One of these breakers shall be a load
or breakers shall have instantaneous trips set above breaker equipped with an instantaneous trip element.
the starting inrush current of the load. NOTE: Attention is directed to the fact that operation of
‘Taken in part from the current proposed revision of NEMA selective tripping requires coordination with the rest of the
Standards 46-log-not applicable to molded-case breakers system; as for instance, the low voltage side of a trans-
Chapter 11 Relay and Circuit-Breaker Application 389

TIME
Fig. 48-Typical fault on a three-phase a-c system.

former bank requires that in the application of relays or EX of Fig. 48. In this diagram OX is the line of zero cur-
Inscs on the high side, proper coordinating steps should be rent and 0 represents the time at which the fault has oc-
taken.” curred. The current to the left of OY is the load current
prior to the fault. The short-circuit current wave is un-
V. FAULT CALCULATIONS
symmetrical with respect to the OX axis immediately after
In order to determine the momentary and interrupting the short circuit, but during increasing increments of time
duty on circuit breakers and to make preliminary relay it approaches a position of symmetry. This asymmetry
settings it is necessary to predict the fault currents that is dependent upon the point of the voltage wave at which
may occur at each circuit breaker location. This infor- the short circuit occurs. It is possible, by short circuiting
mation is sometimes available from tests or from previous at different points on the normal voltage wave, to secure
calculations on adjacent circuits, but must frequently be short-circuit current waves ranging anywhere from those
calculated for a new system or extension. The rigorous symmetrical about the OX axis to those totally asymmet-
determination of short-circuit currents as a function of rical. CD is a curve passing through the maxima of the
time involves too laborious a calculation to be pra,ctical. wave of the total current, and EF is a curve passing
Thus, some approximation is required, and a degree of through the minima. AB is a curve cutting the vertical
judgment must be used in the application of any method everywhere midway between CD and EF.
proposed. In the following paragraphs several such meth- The wave of total current with crests along curves CD
ods will be discussed, including the simplified procedure and EF and with ordinates measured from the axis 09
suggested by the AIEE Protective Devices Committee. can be resolved into two components, namely:
In using any of these calculating procedures it is neces- 1. A direct-current component.
sary to determine the system impedance as viewed from 2. An alternating-current component.
the point of fault, and the current distribution for differ- The direct-current component is determined at any in-
ent kinds of faults. Such calculations for relatively simple stant by the ordinate GH of the curve AB, at the time X.
systems or parts of systems can be made directly. The The alternating-current component is a wave with a crest
network solutions described in Chap. 10 and the method value at any time equal to the difference between the or-
of symmetrical components given in Chap. 2 are helpful dinates of the curves CD and AB. This difference at the
in such calculations. The calculation of faults by these time X has the value HJ. The rms values of this alter-
methods on many modern interconnected systems may nating-current component are shown on curve ST. At any
become entirely too involved. Such systems can be rep- instant, this component is considered to have the same
resented in miniature on an a-c or d-c network calculator. rms value as an alternating wave of constant amplitude
Fault currents can be determined from calculator readings with crest value one-half the distance between curves CD
in a relatively short time. A description of an a-c network and EF at that instant.
calculator is given in Sec. 35 of Chap. 13. A d-c network The rms value of the total current wave under short circuit
calculator can be used for studies where either resistance at any instant is the square root of the sum of the squares
or reactance alone is sufficient to represent the system. of the direct-current component and the rms value of the
Network calculators are also used in studies of load-cur- alternating-current component at that instant. The rms
rent distribution, voltage regulation, transient overvol- values of this total current are shown on the curve RT.
tage, and transient and steady-state stability. The rms value of the total current at the time of parting
of the circuit-breaker contacts determines the interrupting
33. Components of Fault Current rating of a power circuit breaker.
Before discussing specific methods of fault calculation
for circuit-breaker and relay application the current com- 34. Simplified Procedure for Calculating Short-
ponents of a typical fault on an a-c system will be reviewed Circuit Currents for the Application of Circuit
briefly. A more complete analysis is given in Chap. 6. Breakers and Relays
The current in one phase for a three-phase fault on an A simplified procedure for the calculation of short-cir-
a-c system is shown as a function of time by the curve cuit currents has been presented in reports 114--L16 sponsored
390 Relay and Circuit-Breaker Application Chapter 11

TABLE U-REACTANCE QUANTITIES AND MULTIPLYING FACTORS FOR APPLICATION OF CIRCUIT BREAKERS
+*

-- 2’
>Iulti- Synchronous
Gcnc~rators & Induction “’
plying
Factor Condensers LIachines

A. Circuit Breaker Interrupting Duty

1. General case
g-cycle or slower circuit breakers*. . .... .. ....... ... ..
5-cycle circuit breaker. . . . . .. subtransient** transient neglect
a-cycle circuit breaker...........................................
2-cycle circuit breaker. . .

2. Special case for circuit breakers at generator voltage only. For short-circuit
calculations of more than 500,000 kva (before the application of any
multiplying factor) fed predominantly direct from generators, or through
current-limiting reactors only
g-cycle or slower circuit breakers*. . 1.1
5-cycle circuit breakers. 1.2 subtransient** transient neglect
3-cycle circuit breakers. . 1.3
2-cycle circuit breakers. . 1.5

3. Air circuit breakers rated 600 volts and less. . . . 1.25 subtransient subtrAnsient subtransient

B. Mechanical Stresses and Momentary Duty of Circuit Breakers


1. Generalcase..................................................... 1.6 subtmnsicnt subtransient subtransient

2. At 5 000 volts and below, unless current is fed predominantly by directly


connected synchronous machines or through reactors. . 1.5 subtransient subtransient subtransient
* As old circuit breakers are slower than modern ones. it might be expected a low multiplier cc d be used % h old circuit breakers.
--
however, modern cwcult breakers
are likely to be more effective than their slower predecessors, and, therefore, the applicatia procedure ;h the older circuit breakers should be more conservative
than with modern circuit breakers. Also, there is no assursnce that a short circuit will not mnge its cl xcter and initiate a higher current flow through n circuit ,
breaker while it is opening. Consequently the factors to be used with older and slower circuit zakers well my be the same as for modern eight-cycle circuit breakers.
** This is hasad on the condition that any hydroelectric generators involved have amortisseur indings. F hydroelectric generators without arnortisseur windings. D
vnlue of 75 percent of the transient reactance should be used for this calculation rather tha :he subtrnr :nt value.

by the Protective Devices Committee of the AIEE. This ing and momentary currents should be used to select the
method has been found satisfactory and is intended for circuit breaker.
general use by the industry as a simplified method of ap- The factors given in Table 11 represent the ratio be-
proximating the magnitude of fault currents. However, tween the rms total current at the instant of contact part-
other more rigorous methods should be used when re- ing and the initial value of rms symmetrical current. In
quired. determining these factors it was assumed that circuit
The new method is based upon the determination of an breakers should be installed which would permit the use
initial value of rms symmetrical current (a-c component) of high-speed relays at some later date, and the time of
to which multiplying factors are applied for application contact parting was selected on this basis. Contact parting
purposes. In the determination of this current, the follow- times of 4,3,2, and 1 cycles I\-ere assumed for 8-, j-,3-, and
ing symbols are used: 2-cycle breakers.
E = line-to-neutral voltage. Note that the total fault current calculated above may
X1 = positive sequence reactance viewed from the point in some cases divide between two or more circuits. It is
of fault, including transient or subtransient direct- necessary to determine the maximum fault current that
axis rated voltage reactance of machines as speci- must be interrupted by each breaker under any circuit
fied in Tables 11 and 12 in ohms per phase. condition (see example).
X0 = zero-sequence reactance. For most apparatus and circuits the resistance may be
Ro = zero-sequence resistance. neglected as a justifiable approximation. For underground
cables and very light aerial lines the resistance may be as
(a) Circuit Breaker Application-(l) Determine great as the reactance. For these elements the impedance ,j’
the “highest value of rms symmetrical current for any type should be used instead of the reactance. Unless it consti- A$ .)
of fault” equal to E/XI or 3E/(2X,+Xo), whichever is tutes a major part of the total circuit impedance this im-
greater, except that when RO is greater than 2.23X1 no pedance may be added arithmetically to the reactance of
consideration need be given to the latter expression. This the rest of the circuit without appreciable error.
value should be taken for the masimum connected syn- (b) Overcurrent Protective Relays-In approximat-
chronous capacity. (2) Multiply this current by the ing the settings of overcurrent relays, the fault currents for .
proper factors from Table 11. (3) The resulting interrupt- two conditions should be determined :
Chapter 11 Relay and Circuit-Breaker Applicatio,n 391

1. The masimum initial symmetrical current, for maxi- TABLE 12


mum connected synchronous capacity as determined by
E/-Y1 or 3E/(2X,+Xo), whichever is greater, except that, Use Following
Reactancein Determining S,
!&en ROis greater than 2.23X1, no consideration need be
given to the expression 3E/(2X,+.Y0). Type of Rel:tJ Multi- Synch. Synch. Indw-
2. The minimum symmetrical current for minimum con- plying Gen. or AIot,or tion
Ilpcted synchronous capacity as determined by 0.866E/X1, Factor Cond. 1I:whine
___~
or 3E/(2Ly,fXo) for reactance grounded systems. In par- 1. High-speed Current Actuated
ticlllar situations, allowance should he made for remote Relays. 1.0 subtr. subt,r. subtr.
fault locations and fault resistance. 2. Time Over-Current Relays. 1.0 trans. trans.
Ground, distance, balanced, and other types of relays
require special consideration. erators would have a subtransient reactance of 24 percent
For each of these conditjons use machine impedances on their own base. The 13%kv transformers would have
ant1 multiplying factors in accordance with Table 12. an impedance of about 11 percent according to Table 1 of
(c) Example-In order to illustrate the use of the above Chap. 5. The combined positive-sequence impedance of
method of calculation, circuit breaker ratings for several all four generators and transformers, viewed from the 13S-
locations in the system shown in Fig. 49 will be determined. kv bus is thus 35 percent on 200 mva or 17.5 percent on 100
‘I%: approximate impedance data references in Sec. 37 will mva. The zero-sequence impedance would bc that of the
be used. transformers alone or 5.5 percent on 100 mva.
FromTable 4 of Chap. 6, Part XIII, the waterwheel gen- From Tables 2 and 6 of Chap. 3 each transmission cir-
cuit has a positive-sequence reactance of 0.77 ohms per
4-50 MVA 13.8 KV, 3ph WATER WHEEL mile. For the two 40 mile circuits in parallel the reactance
GENERATORS WITH DAMPERS is 8.1 percent on 100 mva. From Table 14 of this chapter
( HIGH RESISTANCE GROUNDING)
the zero-sequence reactance may be estimated at 24.3 per-
n
cent on 100 mva.
The lOO-mva step-down transformers will also have an
impedance of 11 percent on their kva rating or a net for the
two of 5.5 percent on 100 mva.
The turbine-generators (see Table 4 of Chap. 6) will be
taken as 9 percent each on 50 mva or a total of 4.5 percent

r 40 MILES 136 KV
DOUBLE CIRCUIT
on 100 mva for the four units.
The above impedances may be combined into the equiv-
alent circuit shown in Fig. 50.
For a fault at A in Fig. 49 the 3-phase fault will govern
STEEL TOWERS breaker interrupting duty because of the limiting effect of
397.5 MCM ACSR 26 ST
EOUIV, SPACING 15 FT
NON-MAGNETIC POSITIVE NEGATIVE ZERO
SEQUENCE SEOU ENCE SEOUENCE

HYDRO
D
2-100 WA STATION
r-

J 17.5 J 17.5

I38 KV J5.5
BUS t
-i- J 8.1 J 8.1

138 KV 524.3
BUS

55.5

13.8 KV J5.5
BUS f

2.0 OHM

4
5
GROUNDING
RESISTOR

4-50 MVA, 2 POLE, 138 KV, 3 PH


TURBINE GENERATORS
Fig. 50-Equivalent circuit for system of Fig. 49. Impedances
Fig. 49-Hypothetical system for example. in percent on 100 mva.
392 Relay and Circuit-Breaker Application

the generator grounding resistor and the delta-connected


transformers. This fault is -
1.0
0.239
= 4.2 per unit = 420 mva.
Since this is less than 500 mva the general case of Table 11
applies and an S-cycle breaker of 420 mva interrupting rat-
-4b &=I*= 1.89
ing would be adequate. For normal interrupting duty I,= 2.21
(CO+15 seconds+CO) a standard 500-mva breaker could
be chosen without further analysis since the calculated in-
terrupting mva does not exceed 95 percent of the breaker
rating.
If we desire to provide instantaneous single-shot reclos-
ing on this feeder-breaker the interrupting current rating
l-4
must be calculated. The interrupting rating of a 500-mva
hrcnkcr at 13.8 kv is 21 000 amperes. According to Fig. 47 -
reclosing duty cycle II requires reduction of this rating to I,=IZ= 1.89 1,=1*=0.735
21 000X0.94 = 19 700 amperes. The calculated fault level
of 420 mvn is equal to I7 600 amperes, so a standard 500- 10 = 2.21 10’0.41
mva breaker would still be adequate. Regardless of the
interrupting duty the momentary rating required would be +hh
1.6X 17 GOO=28 200 amperes.
I, ~12=Io=5.25
For a fault at B, E/Xi=& =25.5 per unit or 2550 II ’ 15.7
mva. However, the portion’of the fault contributed by Fig. 51-Current distribution for a fault on 138-kv bus at
generator B does not go through breaker B. This is steam station-currents in per unit on lOO-mva base.

os = 5.5 per unit or 550 mva. Thus E/X1 for breaker B is It is apparent that ground faults will govern interrupting
2000 mva. Since this value is greater than 500 mva and duty.
all standard 13.8-kv breakers have 8 cycle interrupting .4 fault at D will produce the same fault currents but
time, breaker B should have an interrupting rating of breaker D will carry I1 = 12= 3.36 and IO= 3.0-I. IA = 9.76
1.1 X 2000 = 2200 mva. This is less than 95 percent of 2500 per unit. For such a fault the required interrupting duty
mvn and a standard 2500-mva breaker may be chosen for a 5 cycle breaker is 9.76X 1.1 = 10.7 per unit or 1070
without further study. mva.
A fault at C will give the highest fault current on any of In order to be safe it is also necessary to considefa fault
the main 13.8-kv breakers. The three-phase fault will gov- at D with breaker C open. See Fig. 52. The total fault
ern as before. Although it is an abnormal condition, the 3.0
now becomes = 12.5 per unit or
greatest fault current will flow when breaker D is open. 0.0965+0.0965+0.0465
For this condition X1 is 4.0 percent and E/X1=25.0 per 1250 mva but part of I0 does not pass through breaker D.
unit or 2500 mva. Since this fault is produced predom- In the breaker IA=4.16+4.16+2.40=10.72. The re-
inantly by the 13.8-kv turbine-generators the 1.1 multi-
plier is required for 8-cycle breakers and the duty exceeds
that of the largest standard 13.8-kv breaker. In view of
the close margin between the breaker rating and the cal- -
culated duty a more accurate check would be in order as
I,=12=2.60 I,zIpO.78
suggested in Sec. 30. If such a check still indicated duty in
excess of 2500 mva it would be necessary to increase the X, IO = 1.76 1,=0.32
by modification of generator design or the addition of cur-
rent-limiting reactors.
In order to determine the interrupting duty on the 138-
kv breakers at the steam station it is necessary to consider
both three-phase and single-line-to ground faults as well as
several fault locations and switching conditions. With all - 1.~~0.32

breakers closed E/X,= - ‘.’ = 13.9 per unit or 1390 mva


0.0719
for a three-phase fault and
3E =---.-- 3.0
IO’ 1.76
T IO
,.I6

2XlfXO Z(O.0719) +0.0465


= 15.7 per unit or 1570 mva for a line-to-ground fault. The
current distribution for such a fault is shown in Fig. 51.
The transformer and line circuits have been shown sepa-
rately in order to study different fault locations. The Fig. 52-Current distribution for single-line-to-ground fault
smallest 138-kv breaker is rated 1500 mva and 5 cycles. at 138-kv terminals of transformer with 13%kv breaker open.
Chapter 11 Relay and Circuit-Breaker Application 393

D.C. COMPONENT A.$vpCPMPONEN7


TYPE Of FAULT
L-G L-L 3* 1-t

40

30
TIE0 LINES ARE FOR
- 20- EN? POLE MACHINES
HOUT DAYPERWINMNGS
30- _ IO
9 20
-!b’5-
6
xi
1
zo- 28 I5
6 2 j
_ IO
c
-
I5 -
9
5 z-E
- 6

: - 1 4
z2 -
210, 6-;
9 3
t 5-
56

%l 4-

56 2
I- _
z - 3-
5-
z _
2 -
4- 3

_ 2- I,

3- _ 1.0
PO
- 1.5-
0.6

0.1
2-
r-
0.6

a5

9
3 SEC.-Ta.O.lbSEC.

6
0.1

7
Q,;+tPlaz %'
z
k
6
z
0.3 :
5
z

‘t III
0.4 E 4

REACTANCES REFER TO SYSTEM WV-A. B’= “--

USE SU8TRANSIENT REACTANCE Of MiMINES 3


w..
FOR THREE-PHASE SHORT- CIRCUITS, X=X,
FOR LINE-TO-LINE S,,ORT-CIR”“T’ “-” L “m w-i”’
FOR LINE - TO- GROUNDSMORT-(

Fig. 53-Short-circuit decrement curves for similar parallel machines.


quirc,d interrupting rating for this condition would be basis of the system as shown. If additional generation or
1.1x 10.72= 11.80 per unit or 1180 mva which is greater lines were contemplated the 1500 mva rating might be ex-
than the value calculated in the previous study. Thus a ceeded and such changes would have to be considered
1300.mva breaker would be adequate for breaker D on the Reclosing would not normally be used on these breakers
394 Relay and Circuit-Breaker Application

For breaker E a fault at E with all breakers closed (k) All generators are assumedto have an open-circuit trsn- ~~
required an interrupting rating of 1.1 (4.52+4.52+4.84) sient time constant (T’,+J of 5 seconds and an armature v-
= 15.2 or 1520 mva. If breaker F were open such short-circuit time constant of 0.15 second.
a fault would require an interrupting rating of (1) A subtransient time constant of 0.05 second was used for .!
all curves.
3.0 .;
1.1 = 161 per unit or lGl0 mva. The short-circuit current from a synchronous machine .,
0.07i+0.077+0.05
Breaker E would probably have instantaneous single shot consists of an a-c and a d-c component. The n-c compo-
reclosing. A standard 1500-mva breaker would be good nent in general can be resolved into a transient Component
for only 1425 mva for such reclosing duty (see Fig. 47). having a relatively large time constant and a subtransient
:Uthough it might be possible to reduce the interrupting component having a relatively small time c$nstant. The
duty of the system to 1425 mva by increasing the trans- values of these constants are such that during the first
former impedance, a reasonable amount, some allowance one-tenth second the transient component changes very
should be made for future addition of generators or tmns- little, but t.he subtransient component disappears almost
mission lines. Thus a 3500-mva breaker would probably entirely. Because of this relation it is possible to plot the
be chosen for the assumed system. two a-c components on one set of curves as shown by the
“a” curves of Fig. 53. The numbers of these curves refer
35. Short-Circuit Calculations for Similar Parallel to the combined external reactance (exclusive of loads) and
Machines machine subtransient reactance. A subtransient time con-
It is intended that the simplified procedure given in Sec. stant of 0.05 and a transient open circuit time constant of
34 be used for normal circuit-breaker applications and for 5.0 were used in the preparation of these curves, but the
preliminary relay settings. In some special cases it may be effect of other time constants can be included by reading
desired to make a more accurate analysis of current decre- vertically from the intersection of the horizontal line cor-
ment such as to take into account abnormal machine time responding to the particular time constant and the inclined
constants or to obtain relay currents a relatively long time line corresponding to the particular time. The dotted lines
after the fault has occurred. show the transient component only of a-c current.
When all of the machines which contribute to a fault These curves are intended primarily for turbine-gener-
have similar reactances and time constants, are equally ator systems as indicated by assumption (g). The assumed
loaded, and are symmetrically located with respect to the relation between transient and subtransient reactance is
fault the group of machines can be represented as a single Xd’ = ( 1.4Xd”+.02) per unit. The curves may be used
equivalent generator. The fault current can then be calcu- with fair accuracy for salient pole generators with dampers.
lated with relative accuracy by the methods described in For salient pole machines without dampers the curves may
Parts II, III and VI of Chap. 6 in which the effects of in- be used with the following adjust,ments: \
dividual machine characteristics, loads, external impedance (a) Calculate the total system reactance to the poinbof fault
and change of excitation can be included. using the subtransient reactance of the machines, and then
A somewhat easier analysis may be made by the use of subtract 5 percent.
short-circuit decrement curves which have been pub- (b) Enter the curves with the above modified value of react- :
lished 117~118and are reproduced in Fig. 53, if the assump- ante. (For example if the system reactance is 25 percent
tions bn which they are based hold for the system under use the curve marked 20.)
consideration. These are: (c) The proper a-c component of current will be approximately
midway between the dotted and solid portions of the
(a) Transient chnmcteristics of alternating-current generators curves of 53(a) in the short time periods where a distinc-
of normal design determined from oscillogmph tests. tion is made.
(t)) That the effect of capacitance and resistance is neglected, (d) The proper d-c component of current is given by the ::
except in so far as decrementsare concerned,which effects dotted curves of 53(b).
nre inclucled by average decrement factors.
(c) That the contact resistance at short circuit is zero. With the above general qualifications the curves may be
(d) That the alternating-current generators are carrying full used to calculate three-phase, line-to-line or single-line-to-
load at 80 percent power factor previous to short circuit. ground faults. The following symbols are used:
(e) That the short circuit is established at the point of voltage Xl= percent positive-sequence impedance viewed from the _
wave corresponding to the maximum possible instantane- point of fault, based on the total synchronous kva.
ous current. Xz=negative-sequence impedance viewed from the point of 5
(f) That the effect of automatic generator voltage regulators fault. jk
is neglected. X0= zero-sequenceimpedance viewed from the point of fault. ‘i:
(g) All reactance up to and including 15 percent is considered T,= time constant of direct-current component. :‘:,
within the generator. For values of reactancegreater than TL’= short-circuit subtransient time constant.
that the difference is considered external. T’do= open-circuit transient time constant.
(11)All machine emfs are assumedto be and remain in phase. For a three-phase fault use the curves of Fig. 53 (a) and
(i) The load is assumedto be located at the machine terminals (b) for which X=X1 and read the components of current I
and the fault to occur on an unloaded feeder.
on the ordinate scales designated 3-phase. The a-c and
(j) The actual system subjected to fault may be represented
by a single equivalent generator of the sametotal rating as components may be combined into the rms total cm-r
the synchronous apparatus of the system and an equiv- for maximum asymmetry by the formula,
alent external reactance. kll, total=d/i*~+id~.
Chapter 11 Relay and Circuit-Breaker Application 395

~;ig. 53(c) may be used to perform this calculation by lay- chapter and a table of equivalent circuits is given in the
ing off the components along the two axes and reading the appendix.
rms tot,al current on the circular scales. Feeder Voltage Regulators-The impedance of sin-
,A line-to-line fault is read in a similar manner except gle-phase induction regulators referred to the through kva
the curves are used for which X=X1+X2 and the magni- of the circuit varies with regulator position from approsi-
t,& of current is read on the ordinate scale headed L-L. mately 0.7 percent at maximum buck or boost position to
For single-line-to-ground faults enter the curves with approximately 2.5 percent at points midway between the
,y =X1+X2+X0 and use the ordinate scale headed L-G. neutral and masimum positions. At the neutral position
the curves of Fig. 53(b) are plotted against a basic time the impedance is approximately 1.5 percent.
sc:alc corresponding to T,=O. 15 sec. If the d-c time con- The impedance of polyphase induction regulators does
stant is known to be different, read vertically from the not vary greatly with regulator position and lies between
intersection of the horizontal line corresponding to the 1.0 percent and 1.5 percent on the circuit kva base.
&sired time and the inclined line corresponding to the For line voltages not exceeding the 15 kv insulation class
desired time constant. level, single-core step regulators are used when the line
current does not exceed 400 amperes. Two-core step regu-
36. The Internal Voltage Method lators are used for higher current circuits to reduce the
For critical relay and circuit-bre&ker applications where current handled by the tap changer to JO0 amperes.
synchronous machines are dissimilar and unsymmetrically Two-core four-winding construction is used where the
l,j,*at,ed with respect to the fault, a more accurate short- line voltage exceeds the normal 15 kv insulation class level.
cnircuitanalysis can be made by means of the Internal Volt- The impedance of plus or minus 10 percent regulators in
,JYCMethod. This method lends itself to the use of a net- single-phase and balanced three-phase circuits is given in
work calculator and can be used to include the effect of a Table 13.
cohangein the excitation of the machines. Because of the
limited application of this method of calculation the reader T.4BLE 13 - IMPEDANCE OF FEEDER REGULATORS-PERCENT ON
is referred to a series of articles by C. F. Wagner, entitled CIRCUIT KVA BASE-PLUS OR MINUS 10 PERCENT REGLXATION
“Decrement of Short-Circuit Currents,” which appeared
in the March, April, and May 1933, issues of the Electric Max. hlin. Keutml Pos.
.lownal. Induction
Sirlgle-phase. . . . 2.5 0.7 1.5
37. Approximate Impedance Data for Fault Calcu- Three-phase. .. 1.5 1.0
lations Step-Type
In fault calculations, impedance data applicable spe- Single-core. . . . . 0.4 0
cifically to the apparatus and circuits under consideration Two-core, three-winding. I 0.7 O.-l
Two-core, four-winding. .I 1.1 0.5
should be used whenever possible. Such data can usu-
:~lly he obtained from the manufacturers for existing ap-
paratus and can be calculated with the aid of tables referred Aerial Lines-The characteristics of aerial lines are
to below for overhead lines and cables. The necessity for given in Chap. 3.
accurate data is particularly important for circuit elements When the conductor size and spacing of an aerial line
which have a major influence on the fault magnitude. cannot be determined and a rough value of impedance is
For estimating fault currents on proposed new circuits, known to be satisfactory, the reactance of lines above 15 kv
and for approximate data on the less important elements class can be taken as 0.8 ohms per mile without serious
of existing circuits, the following references and tables are error. The resistance of such lines will usually be negligible
olrorcd as typical of present-day practice. from the standpoint of circuit breaker and relay applica-
Synchronous Generators, Motors, and Con- tion. For lines rated 15 kv and below conductor size and
densers--Table 4 in Chap. 6 lists both average values and spacing vary greatly and typical figures should not be used.
the probable range of the several impedances and time con- If the actual line data cannot be obtained (and an approxi-
st’ants of GO-cycle three-phase synchronous machines. In mate figure is known to be satisfactory) the conductor size
most simplified fault calculations subtransient reactance is and spacing may sometimes be estimated on the basis of
llsed to represent the positive-sequence impedance of syn- thermal and regulation limits of the circuit.
cllronous machines, and its relation to the other imped- The zero-sequence reactance of aerial lines can be esti-
ancesis assumed on the basis of typical designs. Exceptions mated from the positive-sequence reactance by the USC of
to this assumption are noted in Sec. 34. The effect of ex- Table 14. This approsimation is sufficiently accurate for
ternal impedance on the time constants is discussed in Sec. most circuit breaker applications, but when greater ac-
10 of Chap. 6. curacy is required refer to Chap. 3 and other references
Induction Motors-The effect of induction motors on given in that chapter.
the short-circuit current is discussed in Chap. 6. Cables-The impedance of single- and three-conductor
Power and Distribution Transformers-Typical cables is given in Chap. 4.
impedance values for distribution and power transformers The effect of iron conduit in increasing the reactance and
are given in Table 1 of Chap. 5. The relation between the resistance of cables has been investigated by L. Breiger of
positive- and zero-sequence impedances for each of the the Consolidated Edison Co. with both laboratory and
principal types of transformers is also discussed in this field tests.‘*4 These tests show that if the cables are held
396 Relay and Circuit-Breaker Application Chapter 11

TABLE 14-APPROXIMATE RATIO OF X0 TO X1 FOR TRANSMISSION Bus Conductors-The reactance of most busbar arm
LINES AND CABLES rangements for low or medium voltage circuits is of the
- -
order of 50 microhms per foot. Values for practical cir-
Aver- hvep
age Rang e -r lnnge cuits range from 30 to about, 70 or 80 microhms. In lo,,,.
WC
-- _- voltage circuits bus reactance may be an appreciable l-,ae
Single-circuit Aerial IDouble-circuit Aer- of the circuit impedance. For example 50 feet of bus at 5(1
Transmission Line ial Transmission microhms per foot will cause a drop of 50 volts at 20 m
(without ground Line (with non- amperes.
wires or with magnetic ground
Fig. 541z6gives the 60-cycle reactance per conductor pet
magnetic ground wires). 3 2-4
wires).. . 3.5 2.5-3 .5: rhree-phase Cables 3-5
foot of two rectangular bars in a single phase circuit,.
Single-circuit Aerial : jingle-phase Cables. 1 . . The reactance per phase of a transposed three-phase
Transmission 1,ine bus may also be obtained from Fig. 54 by replacing 4
(with non-mng- by an equivalent spacing equal to the cube root of thC
netic ground product of the three distances between phase conductors,
wires). 2 1.7-2 .7
%WI”.= $‘s1s2s3.If the bus is not transposed, the reactancf
-
corresponding to the minimum spacing should be used
in close triangular arrangement,, the reactance is increased for circuit breaker applications in order to obtain tht
by only about 10 percent because of the iron conduit. In maximum current in any pole. For other applications ii
many cases, however, cables lie at random in the conduit may be desirable to use the equivalent spacing in ordel
and the reactance may be increased by as much as 50 per- to determine the average reactance per phase.
cent. The reactance of bus runs composed of several closeIS
For circuit breaker applications, in the absence of spe- spaced bars per phase may be determined approximate13
cific information, the reactance of iron conduit circuits by considering each phase group as a solid conductor hav.
may be taken at from 40 to 45 microhms per foot for one ing the same overall dimensions. This approximation wil
conductor per phase and 20 to 25 microhms per foot, for give values of reactance accurate within about 5 percent il
two conductors per phase. For non-magnetic duct, cor- the distance s is more than twice the equivalent a. For tht
responding figures are 35 to 40 microhms per foot for one arrangement in Fig. 55 the error is 15 percent for s = 8 inch,
conductor per phase and 18 to 22 microhms per foot for
two conductors per phase. The increase in resistance
caused by the iron conduit is not sufficient to justify con-
sideration in circuit breaker applications.

“I

2 3 4 5 6 7 8

t
a 60
is
g 50

t
a40 DISTANCE d IN INCHES
2
Fig. 55-Reactance voltage drop in each three-phase bus caused
by one ampere of balanced three-phase current.

es and 6 percent for 30 inches. A more accurate method of


calculation is given in Reference 126.
The reactance of irregularly shaped conductors can be
determined from Figs. 56 and 57 and similar data published
by bus bar manufacturers, such as References 131 to 133.
A rough approximation may be obtained by the method
described in the preceding paragraph.
Low-Voltage Air Circuit Breakers (600 Volts and
Below)-The reactance of low-voltage air circuit breakers
with series trip coils may be an appreciable part of the tod
circuit impedance when the full-load rating of the breaker
l/IrrIII I I II 1 i j j
0 0.2 0.4 0.6 0.8 1.0 1.2
is small compared with the remainder of the system. Cm
1.4 I.60
S should be taken to make sure that trip coils are included o?
a+b all three poles of a breaker before using the values in thd
Fig. 54-Reactance of rectangular bar conductors. accompanying table. If only two coils are used, one-third I
Chapter 11 Relay and Circuit-Breaker Application

l-
: 50
t:
a
240
ln
8 30
=
0 v.1 0.2 0.3
s RATIO r/a
I 20 I 2 3 4 5 6 7 8 IO 12 14
RATIO s/a RATIO t/a
(a) lb) (cl

Fig. 56-Reactance of square tubular bus bars.


(a) Reactance of thin square tubes.
(b) Increase caused by round corners.
(c) Increase caused by thickness of tubes.

of the single-coil impedance should be used in calculating breakers, which have interrupting ratings of 50 000,
the masimum pole current in a three-phase fault, and the 25 000, and 15 000 amperes respectively at 600 volts or
impedance should be omitted entirely in calculating a sin- below.
glc line-to-ground fault. The resistance per pole of AB-10 thermal breakers is
Values of series trip coil impedances are given in Table given in Table 16.
15 for Westinghouse DA 50, DB 25, and DB 15 air circuit The reactance of the main current-carrying loop of an
air circuit breaker can not readily be separated from the
influence of the bus or cable to which it is connected. It
may be calculated along with the bus or neglected.
Current Transformers-The reactance of the smaller
mound current transformers in a low-voltage circuit may
be appreciable when fed from a relatively heavy supply

TABLE 15-D-C RESISTANCE AND 60-CYCLE REACTANCE OF


600 VOLT AIR CIRCUIT BREAKER SERIES TRIP COILS*

Full Load
Ampere
T DA-50 7- DB-15 and DB-25

Resistance Reactance Resistance Reactance


Rating
n ohms 25°C in ohms n ohms 25°C in ohms

15 0.063 0.21 0.039 0.110


20 0.028 0.11 0.021 0.063
25 0.022 0.065 0.014 0.040
35 0.011 0.041 0.007 0.020

50 0.0042 0.015 0.0036 0.0090


70 0.0033 0.0080 0.0017 0.0053
90 0.0022 0.0063 0.0010 0.0034
100 0.0011 0.0039 0.00083 0.0025
125 0.00086 0.0030 0.00048 0.0017

150 0.00067 0.0023 0.00042 0.0013


175 0.00052 0.0017 0.00027 0.00088
200 0.00034 0.0012 0.00024 0.00072
225 0.00034 0.0012 0.00017 0.00057
250 0.00021 0.00076 0.00017 0.00057

350 0.00013 0.00043 0.000079 0.00033


400 0.00013 0.00043 0.000050 0.00023
500 0.000069 0.00019 0.000031 0.00017
CONDUCTOR SPACING D BETWEEN CENTERS -INCHES 600 0.000069 0.00019 0.000031 0.00017
Courtesy of Aluminum Co. of Ammicn, copyright ozun~r.
*If only two seri~atrip cmls are usedUYBfs of thesevaluesin calculating n three-
Fig. 57-Reactance of channel bus. phawe fault: neglect entirely for single-line-to-ground faults on three-phase circuits.
398 Relay and Circuit-Breaker Application Chapter 11

TABLE 16-RESISTANCE PER POLE OF AB-10 BOO-VOLTTHERMAL Bibliography of Relay Literature, 1940-1943, AIEE Relay Com- r
CIRCUIT BREAKERS mittee. A.Z.E.E. Transactions, Vol. 63, 1944, October section, pages
705-09.
(iO()-r\.\lrEREFRAME Bibliography of Relay Lite&ure, 1927-1339, AIEE Relay Corn-
mittee. 9.I.E.E. TxuNL~~~~u, Vol. 60, 1941, pages 1435-47.
Full-Load Resistance Full-Load Resistance
Ampere Rating in Ohms Ampere Rating in Ohms Books on Relaying
____ -___
225 0.00024 50 0.00297 1. Silent Sentinels (a book), Westinghouse Electric Corporation
250 0.00022 70 0.00130 1949.
275 0.00018 90 0.00084 2. Relay Systems, Theory and Application (a book), by I. T. Man-
300 0.00016 100 0.00080 seth and P. H. Robinson, RIcGmw-Hill Book Co., Inc., 1935.
325 0.00014 125 0. ooOG3 Bus and Apparatus Protection
11. The Fault Ground Bus, Its Use and Design in Brunot Island
350 0.00012 150 O.OOOG3
Switch House of the Duquesne Light Co., by R. hl. Stanley
400 0.000096 175 0.00050
and F. C. Hornibrook, A.I.E.E. Transections, Vol. 49, Jan.
450 0.000078 200 0.00036
1930, pages 201-212.
500 0.000064 225 0.00030
12. Protecting Frequency Changers from Out-of-Step Conditions,
525 0.000060
by L. N. Crichton, The Electric Journal, Vol. 34, Feb. 1937,
pages 71-76.
550
13. Relay Protection for Station Buses, by W. A. Lewis and R. M.
GO0
Smith, The Electric JOUS-d, Vol. 34, Nov. 1937, pages 457-458.
14. Harmonic Current-Restrained Relays for Differential Protec-
T tion, by L. F. Kennedy and C. D. Hayward, A.I.E.E. Trans-
IOO-AMPEREFRAME ~O-~PERE FRAME
actions, Vol. 57, May 1938, pages 262-271.
Full-Load Resistance Full-Load Resistance 15. Relay Protection for a Large Regulating Transformer, by W.
Ampere Rating in Ohms Ampere Rating in Ohms C. Marter, Tile Electric Journal, Vol. 36, March 1939, pages
87-88.
50 0.0036 15 0.0105 16. Bus Protection, A.I.E.E.-E.E.I. Committee Report, A.Z.E.E.
i0 0.0025 20 0.0100 Transactions, Vol. 58, May 1939, pages 206-211.
90 0.0018 25 0.0070 17. Considerations in Applying Ratio Differential Relays for Bus
100 0.0015 35 0.0032 Protection, by R. M. Smith, W. K. Sonnemann and G. B.
1 50 0.0028 Dodds, A.Z.E.E. Transactions, Vol. 58, June 1939, pages 243-
252.
18. Current Transformers and Relays for High-Speed Differential
TABLE 17-IMPEDANCE OF CURRENTTRANSFORMERS Protection, with Particular Reference to Off-Set Transient
Currents, by E. C. Wenta and W. K. Sonnemann, -4dI.E.E.
\Vestinghouse Rated i- Ohms
Trunsactions, Vol. 59, Aug. 1940, pages 481-488.
Type Current 19. A High Speed Differential Relay for Generator Protection, by
Impedance Resistance
.- W. K. Sonnemann, A.Z.E.E. Transactions, Vol. 59, Nov. 1940,
CT 2.5 50 0.008 ...... pages 608-612.
100 0.002 ...... 20. Prolonged Inrush Currents with Parallel Transformers Affect
200 0.0005 ...... Differential Relaying, by C. D. Hayward. A.I.E.E. Technical
400 0.00001 Paper 41-65.
21. Linear Couplers for Bus Protection, by E. L. Harder, E. C.
WE 200 0. OOOG 0.0003 Wentz, W. K. Sonnemann, E. H. Klemmer. A paper presented
400 0.0002 0.00009 at the A.I.E.E. Winter Convention, Jan. 1942.
22. Predicting Performance of Bus Differential Systems, by E. C.
CT 5.0 50 0.014 0.008 Wentz and W. K. Sonnemann, Westinghouse Engineer, Feb.
100 0.0035 0.002 1942, page 28.
200 0.00095 0.0005 23. The Effect of Direct Current in Transformer Windings, by
400 0.00032 0.00015 E. L. Harder, Electric Jo~vL~, Vol. 27, Oct. 1930, page 601.
-
24. Bus Protection Independent of Current Transformer Charac-
teristics, by G. Steeb, A.I.E.E. Technical Paper i\;o. 41-99.
circuit. Approsimute values for specific Westinghouse cur-
25. System Protection Analysis Precedes Oswego Design, by G.
rent transformers are given in Table 17. The limiting ef-
Steeb, Electrid World, Vol. 116, Nov. 1, 1941, page 57.
fect of secondary burden has been neglected for the sake of 26. Vibration Protection for Rotating Machinery, R. L. Webb,
simplicity. C. S. Murray. A.Z.E.E. Transactions, Vol. 63, July 1944, pages
534-7.
REFERENCES 27: Linear Couplers. Field Test and Experience at York and
Middletown, Pa., E. L. Harder, E. H. Klemmer and R. E.
RELAYING Neidig. A.Z.E.E. Transactions, Vol. 65, Mar. 1946, pages 107- f
For a more complete Bibliography refer to Silent Sentinels or to 13.
d
the Bibliographies OJ ll~e Relay Literature as follows: AIEE Relay 28. Motoring Protection for A-C Generators, L. L. Fountain. )
Bibliographies. Westinghouse Engineer, Vol. 6, November 1946, pages 190-91.
Bibliography of Relay Literature, 1944-1946, AIEE Relay Com- 29. Relay Protection of Power Transformers, A.I.E.E. Relay Corn-
mittee. A.I.E.E. Transactions, Vol. 67, 1948, pages 24-7. mittee. A.Z.E.E. Transactions, Vol. 66, 1947, pages 911-15.
Chapter 11 Relay and Circuit-Brenker Application 399

30. Recommended Prnct,ices for the Protection of Electrical Ap- E. L. Harder and M. A. Bostwick, The Electric Journal, Vol.
parat,us, A.I.E.E. Relay Subcommit tee. A.I.E.E. Transactions, 35, Nov. 1935, pages 443-448.
Vol. 52, 1933, pages 607-13. 63. Ratio Ditferentinl Protection of Transmission T,incs, by 11.
30.1 Relay Protcctioll for Lnrgc Rrguluting Transformers, W. E. M. Smith and hl. A. Bostwick, A.I.E.E. Technical Paper, So.
iLInrter. Electric Journal, Vol. 36, Alarch 1939, pages 87-8. 39-154, Aug. 1939.
30.2 Current Transformer Excitation under Transient Conditions, 64. An Improved A-C Pilot Wire Relay, by J. II. Neher and A. d.
D. E. Marshall, P. 0. Lungguth. A.I.E.E. Transactions, Vol. McConnell, A.I.E.E. Technical Paper, No. 40-127, July 1940.
48, 1929, pages 1464-74. 65. Pilot Wire Circuits for Protective Relaying-Espericncr and
Practice, A.I.E.E. Relay Committee. A.Z.E.E. Trunsudious,
Transmission Line Protection (except carrier and pilot wire) Vol. 62, May 1943, pages 210-14.
31. High-Speed Relays Increase System St,ability, by S. L. Golds- 66. Protection of Pilot Wire Circuits, E. L. Harder, >I. A. Best,-
borough, TILe Electric Jour7~nl, Vol. 27, July 1930, pages 400- wick. A.Z.E.E. Trunsuctior~s, Vol. 61, September 1942, pages
401. 645-51.
32. Fundamental Basis for Distance Relaying on Three-Phase 67. Protection of Pilot Wires from Induced Potentials, It. B. Killcn,
Systems, by W. A. Lewis and L. S. Tippett. A.I.E.E. Trans- G. G. Law. A.Z.E.E. Transactions, Vol. 65, 1946, >Iay section,
actions, Vol. 66, 1947, pages 694-709. pages 267-70.
33. A Sew High-Speed Distnncc Relay, by S. L. Goldsborough
and W. A. Lewis, A.I.E.E. Paper 32M1, Presented Winter Instrument Transformers
Convention, Jan. 26, 1932. Abstract, Electrical Engineming, 71. Current Transformer Excitation Under Transient Conditions,
Vol. 51, March 1932, pages 157-160. by D. E. Marshall and P. 0. Langguth, A.Z.E.E. Trunsnctior~s,
34. High Speed Distance Relay (Type HCZ Relay), by L. N. Vol. 48, Oct. 1929, pages 1461-1474.
Crichton, The Electric Jourd, Vol. 32, Dec. 1935, pages 537- 72. What the Tests Show (Refers to Indianapolis Tests on Break-
542. ers, Relays and Potential Devices), by P. 0. Lnngguth and
35. A Xew Distance Ground Relay, by S. L. Goldsborough and R. M. Smith, The Ekctric Journal, Vol. 30, hIarch 1933, pages
R. &I. Smith, A.I.E.E. Z’ransaclio~as, Vol. 55, June 1936, pages 98-101.
6O7-iO3; Disc. Vol. 55, Nov. 1936, pages 1255-1256. 73. Capacitor Potential Devices, by P. 0. Langguth, Tlte Eleclric
36. High Speed Balanced-Current Relays for Parallel Lines, by Journnl, Vol. 31, March 1934, pages 107-109, 112.
S. C. Leyland, Z’he Electric Jourd, Vol. 33, Aug. 1936, pages 74. Overcurrent Performance of Bushing Type Current Tmns-
347-350. formers, by C. A. Woods, Jr. and S. A. Bot,tonari, A.Z.E.E.
37. A System Out-of-Step and Its Relay Requirements, L. N. Tmnsnctions, Vol. 59, Sept. 1940, pages 554-560.
Crichton, A.I.B.E. Transactions, Vol. 56, Oct. 1937, pages 75. Transient and Steady State Performance of Potential Devices,
1261-1267; Disc. Vol. 57, May 1938, pages 284-286. by E. L. Harder, P. 0. Langguth and C. A. Woods, Jr.,
38. High-Speed Relaying Experience and Practice, A.I.E.E. Com- A.I.E.E. Transactions, Vol. 59, Feb. 1940, Pages 91-102.
mittee Report, A.Z.E.E. Transactions, Vol. 58, Nov. 1939, 76. Rating of Potential Devices and Suggested ,\Iaterial for :I
pages 588-592. Standard, by J. E. Clem and P. 0. Langguth, A.I.E.E. Tech-
39. Out-of-Step Blocking and Selective Tripping with Impedance nical Paper, No. 40-94, June 1940.
Relays, by H. R. Vaughan and E. C. Sawyer, A.I.E.E. Truns-
uctions, Vol. 58, Dec. 1939, pngcs 63i-646. General Relaying
40. An Improved Polyphase Directional Relay, by Bert V. Hoard, 81. Building a New Power System, by F. S. Douglass and A. C.
A.I.E.E. Paper 41-62. blonteith, The Electric Journal, Vol. 30, Feb. 1933, pages 55-59.
41. A Distance Relay with Adjustable Phase Angle Discrimination. 82. Planned Protective System, by A. C. i\Ionteith and W. A.
S. L. Goldsborough. A.I.E.E. Transections, Vol. 63, 1944, Lewis, Electrical World, Vol. 106, Sov. 21, 1936, pages 40-42.
pages 835-838. 83. Coordination of Fuse Links, hfethod of Comparing Fuse Links
and Relays for Sect,ionalization and Protection, by E. &I. Ad-
Carrier-Current Relaying kins, Electrical World, Vol. 107, March 13, 1937, pages 877, 952.
51. One Cycle Carrier Relaying Accomplished, by P. Sporn and 84. Pennsylvania Railroad New York-Washington-Harrisburg
C. A. hluller, Electrical World, Vol. 105, Oct. 12, 1935, pages Electrification-Relay Protection of Power Supply System, by
26-28. E. L. Harder, A.Z.E.E. Transactions, Vol. 58, June 1939, pages
52. A Faster Carrier Pilot Relay System, by 0. C. Traver and E. 266-276.
H. Buncker, A.Z.E.E. Trtmsactions, Vol. 55, .June 1936, pages 85. Sensitive Ground Protection for Radial Distribution Feeders,
689-696; Disc. Vol. 55, Nov. 1936, pages 12.52-1254. by L. F. Hunt, and J. H. Vivian, A.I.E.E. Transactions, Vol.
53. Carrier Relaying and Rapid Reclosing at 110 Kv, by R. E. 59, Feb. 1940, pages 84-90.
Pierce, 11. E. Powers, E. C. Stewart and G. E. Hcberlein, 86. Factors Contributing to Improving Electric Service by LIenns
A.Z.E.B. TTUTLSUC~~OTLS, Vol. 55, Oct. 1936, pages 13’20-1129. of High-Speed Switching and Utilization of Stored Energy, by
64. A New High-Speed Distance-Type Carrier Pilot Relay System, J. T. Logan and John H. bliles, A.I.E.E. Transactions, 1941,
by E. I,. Harder, B. E. Lenehan and S. L. Goldsborough, page 1012.
A.I.E.E. Trunsactions, Vol. 57, *Jan. 1938, pages 5-10; Disc. 87. Principles and Practices of Relaying in the United States, by
Vol. 57, May 1938, pages 291-294. E. L. Harder and W. E. Marter. A.I.E.E. Tramactions, 1948,
55. A New Carrier Relay System, T. R. Halman, S. L. Golds- pages 1005-22.
borough, H. W. Lensner, A. F. Drompp. A.Z.E.E. Trans- 88. Protection of Power House Auxiliaries, A.I.E.E. Relay Com-
actions, Vol. 63, 1944, August issue, pages 568-72. mittee. A.Z.E.E. Transactions, Vol. 65, 1946, pages 746-751,
Disc. pages 1115-1116.
Pilot-Wire Relaying 89. Protection of Three-Terminal Lines. M. A. Bostwick, E. L.
61. D-C Pilot-Wire Loop Protects 66 Kv. Cable Circuits, by J. H. Harder. Westinghouse Engineer, Aug. 1943, pages 76-79.
Neher, Electrical World, Vol. 101, Mar. 25, 1933, pages 384- 90. Interim Report on Operation and Application of Out-of-Step
. 387. Protection. A.I.E.E. Relay Committee. A.Z.E.E. Trans-
62. A Single-Element Differential Pilot Wire Relay System, by actions, Vol. 62, Sept. 1943, pages 567-73.

i
400 Relay and Circuit-Breaker Application Chapter 11

91. Nine Year’s Experience with Ultrahigh-Speed Reclosing of FAULT CALCULATIONS


High-Voltage Transmission Lines, Philip Sporn, C. A. Muller. 114. System Short-Circuit Currents by W. M. Hanna, H. A. Trav-
.4 .I.E.E. Transczlions, Vol. 64, 1945, May section, pages 225-8. ers, C. F. Wagner, C. A. Woodrow, and W. F. Skeats, A.I.E.E. s
4
92. High-Speed Single-Pole Rcclosing, .J. J. Trainor, J. E. Hobson, Transactions, Vol. 60, page 877.
H. 37. ;\Iuller, Jr. A.I.E.E. Transactions, Vol. 61, February 115. New Fault-Current-Calculating Procedure Recommended to 4
1942, pages 81-7. Industry, Electrical Engineering, Vol. 60, page 596. ,:I
93. Grounding of Instrument-Transformer Secondary Circuits, 116. Simplified Calculation of Fault Currents, an A.I.E.E. Corn-
j
A.I.E.E. Relay Subcommittee, A.I.E.E. Transnchms, Vol. 66, mittee Report, Ekclricd Engineering, November 1948. :t
1947, pages 419-20. 117. Standard Decrement Curves, By W. C. Hahn and C. F. Wag- ~
94. High-Speed Relaying Expcricnce and Practice. A.I.E.E. Relay ner, A.I.E.E. Transactions, Vol. 51, 1932, page 353.
,:
Committee. A.Z.E.E. Transactions, Vol. 58, 1939, pages 58% 118. Decrement of Short-Circuit Currents, by C. F. Wagner, Electtie
.j
91. Journal, March, April and May 1933.
119. Symmetrical Components, by C. F. Wagner and R. D Evans 2
(a book) McGraw-Hill Book Company, 1933.
120. Sequence Network Connections for Unbalanced Load and ”
CIRCUIT BREAKERS Fault Conditions, by E. L. Harder, Electric Journal, Vol. 34, .;.
Dec. 1937.
100. A Brief Review of Switchgear and Circuit Breaker Practice 121. Thevenin’s Theorem, by E. L. Harder, Eleclric Journd, Vol. 35,
in the United States, by hl. H. Hobbs, A.I.E.E. Transuctions, Oct. 1938.
Vol. 67, Part II, page 893. 122. Calculation of Fault Current in Industrial Plants, by Raymond ,
101. The Interruption of Charging Current at High Voltage, by C. R. Schulze, Electticul Engineering, June 1941.
W. M. Leeds and It. C. Van Sickle, A.Z.E.E. Transactions, 1947. 123. Enclosed Bus-Bar Electrical Distribution Systems for Indus-
102. The 13,500 KVAR Static Capacitor Installation at Newport trial Plants, by E. T. Carlson, B.I.E.E. Transuclions, Vol. 60,
News, by E. L. Harder and V. R. Parrick, A.Z.E.E. Trans- page 297.
actions, 1944. 124. Impedance of Three-Phase Secondary Mains in Nonmetallic
103. Power Circuit Breaker R.atings, by R. C. Van Sickle, A.Z.E.E. and Iron Conduits, by L. Brieger, EEI Bulletin, Feb. 1938.
Trunsactions, Vol. 60, page 882. 125. Formulas and Tables for the Calculation of Self and Mutual
104. Surge Protection of Cable Connected Equipment, by R. L. Inductance, by E. B. Rosa and F. W. Grover, Scientific Paper
Witzke and T. J. Bliss, A.I.E.E. Paper 50-83. No. 169, Bureau of Standards.
105. American Standards for Alternating-Current Power Circuit 126. Reactance Values for Rectangular Conductors, by H. B.
Breakers, C37.4 and C37.5-1945, C37.6-1949, C37.7 and C37.8- Dwight, Electric Journal, June 1919.
1945, c37.9-1945. 127. Inductance and Reactance of Rectangular Bar Conductors, by
106. Report on Guiding Principles for the Specification of Service 0. R. Schurig, General Electric Review, May 1933.
Conditions in Electrical Standards, A.I.E.E. No. lB, 1944. 128. Calculations of Inductance and Current Distribution in Low-
107. Air Circuit Breakers, A.I.E.E. No. 20, 1930. Voltage Connections to Electric Furnaces, by C. C. Levy, -
108. Low-Voltage Air Circuit Breakers, Proposed A.I.E.E. No. 20A, A.I.E.E. Transactions, Vol. 51, page 903.
1946. 129. Current Carrying Capacity of Bare Conductors, by H. W.
109. Power Circuit Breaker Standards, NEMA 46-116. Papst, Electrical World, Sept. 21, 1929.
110. Large Air Circuit. Breaker Standards, NEMA 46-109. 130. Reactance of Square Tubular Busbars, by H. B. Dwight and
111. Standard for Branch-Circuit and Service Circuit Breakers, T. K. Wang, A.Z.E.E. !i”ransactions, Vol. 57, page 762.
Underwriters Laboratories No. 489. 131. Alcoa Aluminum Bus Conductors, Aluminum Company of :
112. Standards for Switchgear Assemblies, A.I.E.E. No. 27, 1942. America.
NEMA No. 44-92. 132. Chase Electrical Handbook, Chase Brass and Copper Company. ‘.i
113. Power Switchgear Assemblies Standards. 133. Anaconda Copper Bus Conductors, Publication C-25.
CHAPTER 12

POWER-LINE CARRIER APPLICATION


nulhor:
R. C. Cheek:

ever, the greatly increased application of carrier equipment


I. INTRODUCTION of the past decade has resulted in virtual saturation of this
ARRIER equipment has been used on the power band on most interconnected power systems, and many
systems of this country since the early 1920s. At new channels have been established at frequencies as high
c first, carrier was used for voice communication only, as 200 kc and as low as 30 kc. The practical limits to es-
but its applications subsequently expanded to include a tension of the frequency band will probably be established
wide variety of functions such as protective relaying, tele- by excessive losses at the high-frequency end of the
metering, supervisory control, and others. Today, carrier spectrum, and by the bulkiness and complexity of coupling
is indispensable to the operation of most power systems. and tuning equipment and the difficulty of obtaining suf-
Power-line carrier offers rapid and dependable communica- ficiently broad tuned circuits at the lower-frequency end.,
tion for interoffice business and for load dispatching. Car-
rier relaying permits high-speed clearing of all types of II. CARRIER APPLICATIONS
faults, with an attendant increase in stability limits and
permissible line loading. Carrier provides economical 2. Carrier Communication1~“~3~8
channels for the telemetering of continuous load informa- Power-line carrier communication systems differ in the
tion to dispatchers for efficient system operation. Carrier
method of calling, the power supply, or in the modulation
channels are used for the remote supervision and control of
system, but any given assembly can be classified as simples
many important substations and for automatic load con- or duplex, depending upon its operation.
trol of numerous large generating units. A simplex system is one in which transmission can pro-
The application of carrier equipment for the transmis-ceed from one station only at any given instant. In sim-
sion of high-frequency signals over a GO-cycle power trans-
plex communication all stations on a channel operate on a
mission system involves many problems that most com- single frequency. Transmission and reception cannot take
munication engineers do not have to face. The configura- place simultaneously on the same frequency at one station,
tion and layout of these systems is invariably dictated by
because the transmitter blocks the local receiver and may
GO-cycleconsiderations, and short taps and spur lines that
even damage it permanently unless the receiver is de-ener-
can play h&‘Got with carrier-frequency transmission are gized during transmission periods. The simplex system
included without regard to their effect upon such high fre-
therefore requires means for turning off the receiver and
quencies. The power system communications engineer energizing the transmitter during transmission.
must nevertheless take the GO-cycle system as it exists and Requiring,only a single carrier frequency, simples equip-
ur;l’-t
make the carrier equipment operate satisfactorily betweenment lends’%elf readily to applications in extensive car-
the required points, drawing heavily upon his experience,rier-communication systems involving more than two
and ingenuitv to stav within his usuallv limited b%$&.‘-rterminals. It is economical of space in the carrier-fre-
The -process of applying carrier to power lines is still
quency spectrum because the san$ frequency is used at all
largely empirical, because the complexity of the usual transmitting points. ?%%&~~f~the spectrum is a serious
power system makes the exact calculation of all the effects
problem on many power systems today, and this factor
practically impossible. However, an appreciation of the alone is often sufficient to justify its application.
fundamental principles involved and the use of the prac- A duplex system is one in which transmission can take
tical data that have been gathered through the years place simultaneously from both stations, as in ordinary
usually permit the characteristics of a proposed carrier telephone service. In the duplex system, the first of two
channel to be predicted with adequate accuracy. frequencies is used for transmission at one station,
In this chapter, a review of the major applications of
the second for reception. At the other station, the first
power-line carrier is followed by discussion of some of the
frequency is used for reception, the second for transmis-
fundamental considerations in the transmission of high- sion.
frequency energy over power systems. The remainder of Duplex operation normally is limited to two terminals
the chapter provides data on the practical application ofper channel, unless communication is desired between a
Power-line carrier channels. central office and several other stations not requiring
intercommunication. Its major advantage, one that in the
1. Carrier Frequencies minds of some users outweighs any disadvantages, is its
For many years the band of frequencies from 50 to 150 ability to provide two-way conversation without the
kilocycles was considered the normal carrier band. How- switching operations required by the simplex system.
401
402 Power-Line Carrier Application Chapter 12

3. The Single-Frequency Manual-Simplex System


Tn the single-frequency manual-simplex system, shown
diagrammatically in Fig. 1, “send-receive” switching oper-
ations are performed by the speaker with a pushbutton on
the telephone handset. Although provision can be made
for complete operation over a two-wire extension, a control
circuit separate from the speech circuits generally is re-

Fig. l-Basic units of manual simplex communication assem-


bly with code-bell calling.

qlured. The need for d-c control circuits and the fact that
a special telephone instrument with a “push-to-talk” hut-
ton is necessary preclude any simple method of extending a
manual-simplex telephone channel through a conventional
private-branch-exchange board.
This sytem is the simplest of the carrier-communication
systems in terms of the amount of equipment required and
in ease of adjustment after installation. For dispatching
and other applications where users are accustomed to
handling push-to-talk handsets, it is an entirely adequate
system.
4. The Two-Frequency Duplex System Fig. 3-Typical two-frequency duplex assembly. Panel units,
top to bottom, are transmitter, audio amplifier, blank test-
The basic units of a two-frequency duplex assembly are meter unit, superheterodyne receiver, audio hybrid and
shown in Fig. 2. A photograph of a typical complete signalling units, switch and fuse unit, high-voltage power
supply, low-voltage power supply, and voltage-adjusting
autotransformer unit.
ITRANSMITTER l- TO LINE
-
TUNER unit. It is this unit that makes it possible for the trans-
mitter and the receiver to operate continuously during the
conversation, without switching operations, with a con- ,’
ventional two-wire telephone extension.
The purpose of the hybrid unit can best be understood
by considering what would happen to a two-frequency
duplex channel if an attempt were made to operate into
two-wire telephone extensions at each end without hybrid
units. With such a system, the audio output of the re
ceiver would be connected directly to the input terminals
RECEIVER
of the audio amplifier and would modulate the transmitter
t- output. This signal would be received at the distant sta-
tion, amplified by the audio amplifier, and transmitted
Fig. 2-Basic units of two-frequency duplex communication back to the first station, where it would be amplified again
assembly with code-bell calling. and retransmitted. An oscillatory circuit would thus exist,
and the outputs of the receivers at both stations would be
assembly is given in Fig. 3. Aside from the fact that the an audio howl of a frequency equal to the natural fre
transmitter and receiver operate on different frequencies, quency of the complete loop. TRis howl would make the
the most important difference between this system and the circuit useless for communication purposes.
manual simplex system is the addition of the audio hybrid The audio hybrid unit prevents this howl by reducing the
Chapter 12 Power-Line Carrier Application 403

amount of receiver output that reaches the audio amplifier *


TO LINE
inpUt terminals to a value insufficient for continuous oscil- TUNER
lation. The unit contains a three-winding transformer
connected between the telephone line and the t,ransmitter
and receiver terminals as shown in Fig. 4. The balancing
n&n-ork must be a group of resistors, capacitors, and in- I
CALLING
clclctors connected in a network whose impedance matches AMPLIFIER
UNIT
I
HYBRID _ II I
UNIT

AUDIO OUTPUT Fig. 5-Basic units of multi-station two-frequency duplex


2-WIRE
communication assembly with code-bell calling.
EXTENSION p

Fig. h-Typical hybrid coil and connections. The components


of the balancing network are chosen to match the input
ber of stations on a channeL The basic units are sho\vn in
impedance of the telephone extension as nearly as possible Fig. 5. Two transmitters and two receivers are inchldecl in
over the voice-frequency band. each assembly, but other units, such as power supplies and
amplifiers, are not duplicated.
closely the impedance of the telephone line and associated The transmitter and receiver used at a given station tle-
cclrlipment, as viewed from the hybrid unit terminals, over pend upon the point of origin of the call. Designating the
the hancl of audio frequencies transmitted by the carrier two frequencies as F1 and Iilf, for example, all stations
c>clllipment. Examination of Fig. 4 shows how a typical would normally receive on I”,. A station originating :t call,
Ilybrid transformer is intended to accomplish its function however, transmits on F,. The F1 transmitter is selected
of placing the signal from the receiver upon the telephone by the calling party by the simple act of picking up the
line without producing a corresponding signal voltage telephone handset. The closing of the d-c circuit through
across the input terminals of the transmitter audio ampli- the hook switch operates a relay, which causes the con-
fier. The receiver output is fed into the hybrid transformer tactor unit to apply the output of the audio amplifier to
:lt the junction of two identical windings. These two wind- the audio terminals of transmitter F1. Simultaneously the
ings are in series with identical impedances, so that the contactor unit energizes the transmitter and applies the
rrcciver output current divides equally between the two. output of receiver F? to the audio hybrid unit,. t\t the
‘I’he ampere turns in the two windings balance or neutralize called station, the reception of the carrier signal from the
each other, leaving no ampere turns to be balanced by cur- calling station on receiver F1 operates a relay whose con-
rent in the third winding. The voltage across this third tacts open to prevent the transfer from transmitter F: to
winding is therefore theoretically zero as far as the effect transmitter F1 from being made by the contactor unit
of signals from the receiver is concerned. when the called party replies. Transmitter F1 and receiver
For a signal from the telephone line, however, the cur- Fz at the calling station and transmitter Fz and receiver F1
rents in the two identical windings are in essentially the at the called station remain energized throughout the con-
same direction, some flowing through the receiver output versation. When the conversation is completed, the hang-
transformer and the remainder flowing through the bal- ing up of the telephones at both stations returns conditions
ancing network. A corresponding voltage therefore ap- to normal, with all stations receiving on F1.
pcnrs across the terminals of the third winding.
It is essential that telephone extensions used with duplex 6. The Single-Frequency, Automatic-Simplex
:lssrmblics be properly terminated and be free of discon- System
tinuities. Received signals transmitted along an extension Single-frequency automatic simplex is the most versatile
and reflected from such discontinuities back toward the of all the power-line carrier-communication systems. The
(‘:lrrier set appear to the hybrid unit as normal signals to number of stations on a given channel is not limited to two,
be transmitted and may make it impossible to achieve a as is the case with the usual two-frequency duples system;
satisfactory balance with any type of balancing network. it permits a single conversation among several stations on
The determination of the proper balancing network and the channel, and it permits operation with two-wire tele-
the adjustment of audio levels after installation are usually phone extensions and through PI3& boards without re-
the major problems in the application of two-frequency quiring balance of a hybrid unit.
rbles equipment. Modern automatic-simplex equipment eliminates ob-
jections to “send-receive” switching because this function,
5. The Multi-Station Duplex System accomplished automatically, is so rapid and quiet that the
The multi-station duplex system provides the advan- user often is unable to detect its occurrence. In up-to-date
tages of duplex communication between any two of ‘a num- automatic-simplex equipment, the transfer is made so
404 Power-Line Carrier Application Chapter 12 ‘4

OUTGOING CdlRRlER
TRANSMITTER -
TO
TUNER

1IC
JCOMING
ARRIER

clRINGING
UNIT CONTROLLED

I RECEIVER

Fig. 6-Basic units of automatic simplex assembly with code-


bell calling.

rapidly that after every slight pause, or even between


words, a party speaking can be interrupted.
A typical assembly for automatic-simplex communica- Fig. 7-Typical automatic simplex communication assembly.
tion is shown in the block diagram of Fig. 6. In addition Units top to bottom, at left, superheterodyne receiver, switch
to the units used in the two-frequency duplex assembly, and fuse panel, and high-voltage power supply. At right,
transmitter, audio amplifier, hybrid and signalling unit,
automatic-simplex operation requires an electronic-trans- electronic transfer unit, bias-controlled audio amplifier, and
fer unit and a receiving audio-amplifier unit. The latter two low-voltage power supplies.
provides a convenient place to block receiver audio output
without disabling the radio-frequency portion. ring, the desired party being indicated by a code made up
The transmitting audio amplifier in the stand-by condi- of long and short rings. The calling party transmits the
tion is unblocked and ready to amplify voice signals from code by turning a hand generator or by applying a voltage
the telephone line. Reception of a carrier signal blocks the to the line with a push-button on his telephone instrument.
amplifier, so that once reception has started, no transmis- All telephones on the system ring in accordance with the
sion can occur until the equipment returns to the stand-by transmitted code.
condition. On the other hand, if an outgoing voice signal In the voice ca22ing system, the call is placed by simply
reaches the amplifier from the telephone line with the speaking the desired party’s name into the telephone trans-
stand-by condition in effect, it causes the entire receiver to mitter. Loudspeakers with individual amplifiers are pro-
be blocked so that no signal can be received until conditions vided at all telephone extensions to call the desired party.
return to stand-by. The switch from transmit to receive The loudspeaker is disconnected when the telephone in-
and vice versa requires that the equipment pass through strument is picked up. Calling by voice is supplemented
the stand-by condition in each direction. in some installations, especially those where ambient noise
The electronic-transfer unit is the key unit in the auto- level is high, by a high-frequency audio tone, which is j
matic-simplex assembly. It switches the equipment auto- applied to the loudspeaker for a few seconds at the time :
matically from stand-by to transmit or receive as required. the calling party picks up his telephone instrument. ’
A typical automatic simplex assembly is shown in Fig. 7. In the automatic bell calling system, the bells on the
telephone instrument or instruments at the opposite ter-
7. Calling Systems minal are rung automatically when the calling party picks 3
A number of different systems of establishing a call over up his hahdset. The ringing continues for R few seconds
a carrier channel are in general use. The most important and then is cut off automatically. To repeat the ring the
are the following: code-bell calling, voice calling, automatic calling party must hang up the telephone instrument and
bell calling, and dial selective calling. remove it again, or close the hook switch manually and
Code-bell calling is the system of calling often used on then release it. Because this system provides no means
rural party lines in which all telephones on a given circuit of indicating which telephone dn an extension should be
..I

if

chapter 12 Power-Line Carrier Application 405

nns,Veretl, it is used only on point-t,o-point carrier systems esist!s. The quantities most often telemet,ercd on power
!{.hcreonly one extension is used at each end of t’he channel. syst,cms are electrical qiinntitJics, usually kilowatts and
.1 c:lrrier channel linking two PBS boards provides an kilovars; but hot-spot temperature, water level, tap-
idctL1application for the automatic bell calling system. changer position, and many other quantities can be
ln dial sdectiae calling, the desired number is dialed in telemetered.
tl,c convcntional.dial-telephone manner. Each carrier set Some telemetering systems are intended for operation
inclrl(les its own line-selector unit, which receives incoming over metallic conductors only. Among these are the
,/ii,1 plilses and applies ringing voltage to the wanted ex- torque-balance and the slide-wire systems. Others are
tc,nsion. Each of these selector units is in itself a complete adapt,able for use either over metallic conductors or carrier
,,rir:lte a~~t,omatic-telephone eschnnge. The automatic- channels. These latter syst,ems are generally based upon
sirn,,l(:~ carrier system with selective calling provides the principle of converting the indication to be telemetered
nearly every operating feature found on modern dial-tele- into pulses of a definite character, a variation in the tele-
phone systems, such as a busy signal, a revertive or ring- metered quantity being reflected as a variation in some
/jack signal, local intercommunication, executive right-of- characteristic of the transmitted pulse.
,,.:Lyor preferential service, and a disconnect signal. In the impulse-rate system, the frequency or rate of the
pulses varies in proportion to the magnitude of the tele-
8, power Supply for Communication Assemblies metered quantity. A reference or base rate of impulsing
,\ltc:rnating current at 120 or 240 volts generally has represents a magnitude of zero; impulse rates above the
t,fs(9 119x1to supply carrier-communication equipment. base rate represent positive increments in the quantity,
.\I, lwations remote from generating sources, automatically and impulse rates below the base rate represent negative
st:irting motor-generator sets or converters have been used increments.
1,) provide power for the carrier set during emergencies or In the impulse-duration system, the frequency of the
111)onloss of normal a-c supply. This practice still is fol- pulses is constant. The duration of the pulse during a
lwwl on long-haul channels using relatively high-powered complete pulsing cycle is proportional to the magnitude
(~cll~iprncnt. Modern developments, however, have pro- of the telemetered quantity.
vitletl cqllipment capable of operating directly from 125- The pulse telemetering systems are well suited to opera-
01 250-volt station bat,teries, making it possible to provide tion over carrier channels. The fact that the intelligence
Ilnint,crruptctl communication more economically, and transmitted takes the form of simple pulses makes it pos-
without the maintenance problems associated with rotat- sible to use in many applications a simple carrier assembly
ing equipment and accompanying control devices. in which an unmodulated carrier is turned on and off by a
pair of contacts controlled by the telemetering device. No
0. Carrier Relaying special modulation schemes are necessary with these sys-
Carrier-relaying systems and their application have been tems, and the accuracy of the received information is
tliscussed in Chap. 11. A typical system is shown in Fig. 20 independent of variations in the attenuation of the channel
of that chapter. The application of the carrier equipment, over which it is transmitted.
:LSopposed to tJhe application of the relays themselves, is
Ixtsicxlly the same as that for other carrier applications. 11. Impulse-Duration vs. Impulse-Rate Systems
‘I’hc problems are greatly simplified, however, by the fact Impulse-duration systems are adaptable to telemetering
that, rcluying channels are alwavs limited to the extent of a much wider variety of quantities than is the impulse-rate
:Lsingle lint section and include iine traps at each terminal. system, which is generally suitable only for the telemeter-
‘1’he relaying system normally requires use of the channel ing of electrical quantities, primarily kilowatts and kilo-
011lytluring an actual fault, and the equipment is free for vars. The Bristol Metameter system, for example, can be
()thw applications for the remainder of the time. The sys- supplied with measuring elements for the telemetering of
Irm is always arranged so that the relays can interrupt pressure, liquid level, and a number of other mechanical
:~ny auxiliary functions in progress when a fault occurs. or hydraulic readings. The impulse-duration receiving
:I form of voice communication often termed ‘(emergency instruments have the additional advantage that they
(‘ommunicat,ion” is usually inherent,ly available in carrier can be easily adapted t,o retransmission of individual or
(“lrlipment provided for relaying. Such communication is totalized quantities.
limited to the line section being protected, and since it is The impulse-rate system, however, has a number of
:1“I~llsh-to-talk” system it is not suited to use with lengthy advantages in those applications to which it is suited. A
(‘stonsions or PBX boards. A rudimentary calling system, complete impulse-rate system, including a suitable record-
Ilsing the carrier itself as a calling signal, is usually em- ing instrument, generally costs less than a corresponding
Ployed. Bccnuse of these and other limitations, the com- impulse-duration system. The accuracy of the impulse-
n~llnictation function provided by carrier-relaying assem- rate system is not nffccted by reasonable variations in the
blics should not be considered in the same category \vith duration of the rcon” and “off” periods of the impulse, an
[‘hat provided by assemblies designed specifically for important, consideration in applications where the tele-
“)~~munication purposes, metering signal must be received and re-transmitted at
several point,s along its channel. Careful attention must,
lo. Carrier Telemetering3 be paid to the operating times of mechanical relays, and
Telemetering is the indicating or recording of a quantity to the time-lag in audio-relay circuits, when impulse-dura-
at a location remote from that at which the quantity tion signals are passed along in this fashion. Also, large
406 Power-Line Carrier Application Chapter 12

variations in signal level due to changes in attenuation generator or a group of generators on a system in such a
affect the accuracy of impulse-duration systems opernt ing day as to maintain the system frequency and to regulate
on audio tones to an extent depending upon the flatness the interchange of power with other systems in accordance
of the receiver avc (automatic-volume-control) charnc- with a predetermined plan.
teristic. The frequency of a system or a group of interconnected
systems is constant if the governor settings on all the prime
12. Power-Line Carrier Telemetering Assemblies movers cause the generators to produce exactly the amount
The chnnncl requirements for impulse telemetering sys- of power required to supply the total load. If some of the
tems arc relatively simple; and because transmission alone load is suddenly lost, that part of the prime mover output
or reception alone is us~dly required, the assemblies used initially supplying the dropped load is absorbed in accel-
for telemetering purposes are often correspondingly sim- erating all the units on the system, and a rise in system
ple. If n single set of impulses is to be transmitted from a frequency occurs. Under these conditions, the output of
given point, the assembly often consists of a single fre- one or more of the prime movers on the system must be
quency-shift carrier transmitter with a self-contained, a-c reduced to restore the frequency to normal, and then
power supply. The carrier-frequency output of the trans- increased slightly to maintain normal frequency.
mittcr is controlled directly by the impulse-forming de- In the operation of large interconnected systems or
vice, which shifts the output back and forth between the power pools, it is the practice for one large generating
mark and space frequencies as its contacts close and open. station to regulate its output on the basis of system fre-
At the receiving end of such a channel, a frequency-shift quency, reducing the governor settings of one or more
receiver is used to receive the carrier signal. The receiver prime movers if the system frequency is high and increas-
operates a relay which in turn keys the impulse receiver. ing the settings if the frequency is low, without regard to
In applications where more than two or three quantities tie-line loads or total interchange of power with other
are to be telemetered from a single point simultaneously, systems. This type of operation is called fl& frequency
it is common practice to use audio-tone transmitter units control. The other systems in the interconnected group
to modulate the carrier-frequency signal. One tone fre- regulate prime-mover outputs on the basis of the inter-
quency is used for each telemetered quantity, and the car- change of power among systems. For these other systems,
rier wave is left on continuously. The telemetering as- there are several possible types of operation, most of which
are based on regulating to produce a pre-det,ermined net
tie-line loading when frequency is normal, but allowing the
tie-line loading to depart from the pre-determined value
when the frequency is off normal.
The basic quantity used to govern the operation of auto-
matic load controllers is the net power interchange of the
system, which is combined with system frequency in most
types of control. In the usual arrangement, net inter-
change is obtained by totalizing individual interchange
readings at the dispatching office and combining the result
with frequency in an automatic load controller located at
that point. The controller generates ‘<raise” and “lower”
impulses that must be transmitted to the regulating sta-
tion. Power-line carrier is often used as a medium for
transmitting these signals.
14. Carrier Assemblies for Load-Frequency Control
The channel requirements for load-frequency control are
similar to those for telemetering two quantities, since two
types of impulses must be transmitted. A common ar-
rangement is the use of a single carrier transmitter modu-
lated by two audio-frequency tones, one for “raise” im-
pulses and one for “lower” impulses. At the receiving end
Fig. S-Typical tone telemetering assembly with carrier re-
ceiver and eight tone receivers, and carrier transmitter with
of such a channel, a single carrier receiver operates into
two tone transmitters. This assembly is capable of receiving a corresponding pair of tone receivers. An alternate sys-
eight simultaneous telemetered indications on one carrier t,em is the use of two frequency-shift channels, one for
frequency and transmitting two simultaneous indications on “raise” and one for “lower” impulses.
another. It is frequently desirable to arrange the system so that
sembly of Fig. 8 is used to receive eight separate telemeter- any one of several generating stations can b:called on to
ing tones on a single carrier frequency and transmit two act as the regulating station for the system. In this case
other tones on another. the usual arrangement is for each such station to be
equipped with an identical carrier-receiving assembly,
13. Load-Frequency Control tuned to the frequency of the load-control transmitter at
Load-frequency control is the control of the output of a the dispatching ofice. Any one of the stations can then
Chapter 12 Power-Line Carrier Application 407

be placed on automatic control by the station operator, in The high impulsing speed of the supervisory system and
accordance with the orders of the dispatcher. the requirement that the relative duration of the “on” and
“off” periods be preserved make it undesirable to use more
1j. Carrier Supervisory Control7 than one relaying point to retransmit mechanically super-
Supervisory control is a system of controlling and super- visory impulses received from a distant point.
vising from a central point to operation of equipment at There are two types of Visicode supervisory control, one
()nc or more remote locations. Control and supervision of in which all the equipment to be controlled is located at a
several separate pieces of equipment are accomplished with single point, and one in which the equipment is in several
r&~tively few condllctors or channels, In the Visicode groups at different locations. These two types arc referred
supervisory-control system, which is the system considered to as the single-station and multistation systems, respec-
iI1 the subsequent discussion, only a single pair of wires or tively.
A fundamental requirement of the multistation system
is that a control or supervision function in progress be-
tween the dispatching office and a controlled station not
be interfered with by supervisory signals from other con-
trolled stations. This requirement is met l)y assigning
different group codes to each station and arranging each
station so that reception of a group code not associatetl
with it locks out the supervisory equipment at that statlion.
Each station must he able to receive all signals transmittetl
from any other station. In this way synchronism of im-
pulses and successful lockout are assured, because the
impulsing of any station is governed by impulses sent
simultaneously from other stations.
When supervisory control is operated over a carrier
channel provided for its exclusive use, impulsing of an
otherwise unmodulated carrier signal normally is used. Fol
this type of operation the transmitters and receivers at all
locations operate on the same frequency, ant1 all stations
Fig. 9-Typical Visicode supervisory control desk. receive each other. Modifications of this arrangement are
made in some cases to combine the supervisory system
a single carrier channel is required. A typical Visicode with other functions. In these cases supervisory control
control desk is shown in Fig. 9. is usually operated over an audio-tone channel, a single
In the Visicode supervisory-control system, supervision tone receiver and transmitter being provided for super-
and control of many individual units of equipment are visory in the carrier assembly at each location involved.
obtained by selective relay systems. These automatically
generate and receive impulses in coded groups to perform 17. Combined Functions on a Carrier Channe13e4J
the functions of selecting the apparatus to be controlled, Many of the functions of power-line carrier that have
performing the desired operation, and indicating that an been described can be performed simultaneously over a
operation has taken place. The latter function is per- single carrier channel, and usually several carrier channels
formed whether the operation is initiated through the on the same line can make joint use of coupling and tuning
supervisory system or not. equipment. Such efficient use of carrier equipment often
justifies an investment in the apparatus that might not
16. Channel Requirements of Supervisory-Control be justifiable for a single function alone.
Systems Many functions that require the transmission of intelli-
The rate of impulsing of supervisory equipment is from gence in the form of impulses, such as telemetering and
9 to 14 impulses per second, comparable to the speed of load control, can be performed simultaneously over a single
impulsing of a telephone dial. This rate of impulsing is carrier frequency by modulating the carrier with audio-
considerably higher than the highest rate of any standard frequency tones. Each tone frequency is in effect a sepa-
impulse telemetering system. The fastest such system in rate carrier channel itself, using the radio-frequency carrier
use has a maximum impulse rate of approximately 3.5 per channel as its “conductor”. At the receiving end of such a
second. In an impulse-rate telemetering system, it is nec- channel, separate tone receivers are operated from the out-
essary only that the channel preserve the rate of impulsing. put of the radio-frequency receiver, each individual tone
The relative duration of the “on” and “off” periods is receiver being tuned to receive one particular audio tone
not, important. and reject the others.
In the supervisory-control system the duration of the If continuous telemetering and simultaneous emergency
“on” period is approximately twice that of the “off” pe- communication are desired on a relaying channel, audio
riod. This relation must be preserved in order to allow tones below 500 cycles can be used for several simultaneous
Proper sequential relay operations, some of which occur telemetering functions, the audio frequencies above 500
during the “on” period and some of which occur during cycles being used for speech. A filter is used to eliminate
the “off” period of the impulse cycle. the tone frequencies from the speech at the sending and
Power-Line Carrier Application

continuous functions, such as telemetering or load con-


trol.
’ In multistation supervisory-control systems, all Stations :i
must receive all signals. ConGnuous carrier functions can- -3
not be combined with multistation supervisory control on ti
single-frequency carrier channels, and certain combina- !i
tions of multistation supervisory control with relaying and $
communication equipment are not practical. Among these 3
is the combination of supervisory control with multistation ;$
automatic simplex communication, and any combination .i.
of supervisory control with relaying that involves the use 4*
of carrier transmitters outside a protected line section, -iz
operating on the same frequency as those within the line ‘_
section.
18. Modulation Systems
Three different modulation systems are available for use
in power-line carrier applications. These are the amplitude
modulation, the frequency modulation, and the single-
sideband systems9~10~11. Of these, amplitude modulation is
by far the most widely used. In amplitude modulation
(a-m) the amplitude or intensity of the transmitted wave
is varied in accordance with the waveform o$ the intelli-
gence to be transmitted. A mathematical analysis of the
frequency components of the resulting signal shows that
they include the carrier wave itself, unchanged in magni-
tude, frequency, or phase, plus so-called sideband corn- +
ponents, two for each frequency contained in the modulat-
ing wave. These sideband components appear at frequen-
cies equal to the carrier frequency plus each modulating
frequency (upper sideband components) and carrier fre-
quency minus each modulating frequency (lower sideband
components). It is the beating of these sideband compo-
nents with the carrier in the detector of an a-m receiver
Fig. 10-A carrier assembly for simultaneous voice communi- that results in the reproduction of the original intelligence
cation (emergency type), reception of two telemetered indi-
at the receiving point.
cations, and phase-comparison relaying. Top to bottom,
carrier transmitter, two tone receivers, modulator, double- The bandwidth occupied by an a-m signal is twice the
carrier receiver, phase-comparison relay control unit, switch frequency of the highest-frequency modulating signal, and
and fuse panel, and high-pass filter for removing telemetering the tuned circuits of an a-m receiver must be sufficiently
tones from speech. broad to accept this bandwidth without appreciable atten-
uation at the extreme frequencies.
receiving ends. Speech intelligibility is not perceptibly Since sideband components occur in pairs, one group
affected by the elimination of the speech frequencies below above the carrier frequency and one below, it is evident ‘I’
500 cycles, because practically all the intelligibility is fur- that each sideband group contains all of the intelligence of
nished by the frequencies above this figure. The carrier the original signal. This indicates the possibility of halving
assembly shown in Fig. 10 is intended for relaying, emer- the bandwidth required for transmission by suppressing .,’
gency communication, and simultaneous reception of two one complete set of sideband components before trans- ):’
telemetering tones. mitting the signal. Furthermore, since the carrier wave ‘-
With supervisory-control equipment, any number of itself carries no intelligence and requires a large portion of ‘d$ ,i;.
quantities can be telemetered one at a time. Each tele- the transmitted power, it is evident that an appreciable ‘$
metering function is made a point on the supervisory saving in power can be made by partially or completely g
system, and the dispatcher selects the quantity he desires eliminating the carrier wave at the transmitter, emphasiz- ‘:1% k’
to read. Communication can be made a point on the ing or regenerating it at a low power level in the receiver. !,A,.
-7
supervisory system of single-station supervisory systems, This is done in the single-sideband system, in which one
and such supervisory systems can operate over relaying set of sideband components is suppressed and the carrier
carrier channels. is partially or completely suppressed at a lowYeve1 in the
Single-station supervisory-control systems on point-to- transmitter. If the original peak power used in the trans-
point carrier channels can be used in almost any desired mitter (as an a-m transmitter) is concentrated in the in-
combination with relaying, telemetering, load control, or telligence-bearing components of a single sideband, and
communication. Two-frequency carrier channels are re- if the receiver used has only the necessary bandwidth (half
quired for the combination of supervisory control with the bandwidth required for a-m service), there is a gain in ’
chapter 12 Power-Line Carrier Application 409

,ignal-to-noise ratlo of nine db in favor of single-sideband in which E, and I, arc the sending end voltage and current,
transmission. Thus, single&l&and transmission offers respectively.
the equivalent of increasing the original carrier power i?, and 1, are t,he recaeiving end voltage and cur-
eight times, and rcqllircs only half the bandnitlth required rent, respect,ively.
iIF. the a-m system. Z, is the characteristic impedance as defined in
“,r]lc frequency-modulation (f-m) system is also used in the next paragraph.
po,~c:r-line carrier work. In this system the amplitude or cr+j@ is the propagation constant, to be defined
i,,tcIlsity of the transmitted signal is constant and the later.
frecl~lcncy varies above and below a reference frequency I is the distance from the receiving end, in the
ill a(:(:ord:mce with the intelligence being transmitted. units of length used to define cr+jfl.
T]~Cdeviation ratio, dcfincd as the ratio of the maximum
,]cI):lrtrlre of the frequency from the reference value to the 20. Characteristic Impedance
rna~in~~lmfrequency contained in the modulating signal, Equations (la) and (lb) show that when a voltage is
js a measure of the gain in signal-to-noise ratio of an f-m applied to the sending end of the line, the voltage at any
,+stcrn over an a-m system of the same power. The f-m point on the line actually consists of two voltages, one a
systclm provides marked Increases in signal-to-noise ratio voltage traveling from the sending end of the line toward
:,s the deviation ratio is increased. However, the minimum the receiving end, the other traveling from the receiving
],&\vidth required by frequency modulation is the same end back to the sending end. The former will be designated
:,s that for a-m transmission of the same intelligence, and as E+, the latter as E-. Each of these voltages is accom-
if :L tlcvistion ratio large enough to give a worthwhile panied by a corresponding current, I+ and I-, respectively.
ill(~r(~ase in signal-to-noise ratio is used, the a-m bandwidth The ratio of either voltage to its corresponding current at
nlwt he exceeded. any point in the line is a constant 2, which is independent
‘I’tic frequency-shift system is a special form of frequency of the line length but is a function of the series resistance,
~n,~tlutation that is used for telegraphic functions such as the series inductance, the shunt conductance, and the
t&~mctcring. In this system two closely-spaced frequen- shunt capacitance of the line per unit of length. This
(:i(xsare used. A continuous carrier wave of constant am- constant is the characteristic impedance of the line and
plitudc is shifted back and forth between the two frequen- can be expressed as
(4cs,one frequency denoting a “mark” and one a “space”
in the transmission of the impulses. By using highly stable
crystal oscillators for the transmitted frequencies, and cor-
rcspondingly stable and highly selective circuits in the where R=resistance in ohms per unit length.
rclccivers, it is possible to place the mark and space fre- L=inductance in henrys per unit length.
cluencieswithin 0.06 per cent of each other in the carrier G = shunt conductance in mhos per unit length.
spectrum. Even with this spacing, the equivalent f-m C=shunt capacitance in farads per unit length.
deviation ratio with the slow-speed keying required by and w = 27rj where j is the frequency in cycles per second.
Practical impulse-telemetering systems is extremely high,
In actual practice at high frequencies, such as those used
with the result that a properly-designed frequency-shift in carrier transmission, the quantities jwL and jwC are so
~ system can provide substantial gains in signal-to-noise
large by comparison with R and G that the latter can be
ratio with a small transmitted bandwidth.
neglected and the characteristic impedance expressed
simply as
III. PROPAGATION OF CARRIER ON IT
TRANSMISSION LINES (3)
19. Propagation Between Two Phase Conductors or by applying conventional formulas for L and C as
Practically all textbooks on transmission give the clas-
sical solution for steady-state voltage and current at any 2, = 276 log,,: (4)
Point along a two-wire linerlJ3. This, solution is approxi-
Wtely valid for carrier propagation between two phase where D is the distance between conductors and d is their
(‘Onductors of a transposed three-phase power line, because diameter in the same units. Ordinary high-voltage trans-
transpositions tend to nullify the effect of the presence of mission lines show characteristic impedances of 600 to 900
t]lc third conductor. The solution is based on the assump- ohms between any pair of phase wires. Table 3 of Chap. 9
tion that the line is composed of an infinite number of gives line-to-neutral surge impedances of a number of
resistors and inductors in series, with an infinite number typical lines. The single-phase surge impedances are twice
of capacitors and resistors shunting the line at equally- the values shown in this table.
spaced points. This solution can be written as follows:
21. Propagation Constant
Further study of the solution for a two-wire line shows
that the phase and magnitudes of the voltage and current
traveling toward the receiving end change as they progress
along the line. The forward voltage and current at any
point can be expressed as
410 Power-Line Carrier Application Chapter 12
E+=E;&=+W'A~ (5a) tion of the conductor surface and the twisting of the
I+= ~:e(a+'B'AI strands in an actual line.
(jb)
Most of the literature on power-line-carrier transmission _
where El+ and II+ are t,he values at some intermediate reports measured values of attenuation in excess of figures ’
point on the line at a distance AZ toward the receiving end. calculated from theoretical considerations. The differences /i
Likewise, the voltage and current traveling in the opposite in these cases appear too great to be accounted for by ex- <
direction, E- and I-, change as they progress along the petted errors in the determination of skin effect. For this ’
line, for reason, it is the usual practice in power-line-carrier applica- *.
~-=~;~-(~fl@)Al tion to use attenuation figures based on measurements on
(6a)
~-=~;E-b+lW (Gb) actual lines, rather than calculated figures. A table of
The quantity ar+j@ is the propagation constant of the line, approximate attenuation figures is given in a later section
which can be expressed as of this chapter.
a+jp=~zY=~(R+jwL)(G+jwC). (7) 24. Line Input Impedance
The real part of ol+j@ is an exponent that expresses the The reverse voltage and current expressed by the second
reduction of the amplit,udes of the forward and reverse terms of Eqs. (la) and (lb) result from reflection of the
voltages and currents as they appear at various points forward voltage and current at the receiving end of the line.
along their respective directions of travel. The imaginary Equation Cl) shows that if the line is terminated at the
part expresses the phase shift, of the voltages and currents receiving end in an impedance equal to’its characteristic
that results from the finite time required for the waves to E,
impedance, Zc, so that r = Z,, there is no reverse voltage or
travel from one point to another on the line. r
current; i.e., no reflection at the receiver terminal. Under
22. Standing Waves these conditions the input impedance 2; at the sending end
The forward and reverse voltages (and currents) aid and of the line is the surge impedance Z,, and the ratio of total
oppose each other at various points along the line, depend- voltage to total current everywhere along the line is equal
ing upon their respective phase positions. The total volt- to Z,. Also, if the line is sufficiently long, the second terms
age and the total current therefore exhibit maxima and of Eqs. (la) and (lb) are at the sending end negligible in
minima at equally spaced points separated by a distance magnitude by comparison Jvith the first terms, even
that is a function of the frequency, giving rise to the though the line is not terminated in Z,. In this case also
phenomenon of standing waves. The magnitudes of the the input impedance is 2,. This latter condition is often
maxima and minima are a function of the amount of energy approached in practical carrier applications on isolated
reflected from the receiving end of the line. untapped lines. Carrier transmitters and receivers do not
Standing waves increase the losses in a line as compared ordinarily provide a termination equal to the surge im-
with the losses obtained without reflection or standing pedance of a line, but most carrier channels are sufficiently
waves. They also result in increased radiation of energy long that the input impedance of an isolated line is for
from the line and other usually undesirable effects. practical purposes the characteristic impedance.
il special case that must be considered is that of short
23. Attenuation tap or spur lines that bridge a line over which carrier
The attenuation of a proposed channel is of prime im- energy is to be transmitted. The input impedance of such
portance in carrier application, because it determines the a line may be extremely low under certain conditions and
fraction of the transmitted energy available at the receiv- may constitute practically a short circuit across the carrier
ing end to overcome noise and interfering voltages. channel.
If, as in practical open-wire lines at carrier frequencies, Consider, for example, the Case of a low-loss line, open-
the shunt conductance G is negligible and R is small com- circuited at the receiving end, one quarter wavelength long
pared to jwL, the real part of the propagat,ion constant at a certain frequency. Voltage of this frequency applied
(Eq. 7) can be expressed as to the input terminals, upon arriving at the receiving end,
is reflected toward the source unchanged in magnitude and
a=,$-nepers per unit of length polarity, and has travelled a total of one-half wavelength
c by the time it reaches the source. It is exactly 180 degrees ,;
out of phase with the voltage being impressed at that :!
4.34R instant and practically neutralizes it. It is impossible, f
01= Tdecibels per unit of length. @b) therefore, to establish an appreciable voltage across the 3
c
input terminals of a low-loss quarter wavelength line, be- 2
The resistance R is the resistance of the conductors per cause the reflected voltage always opposes any voltage tha
unit of length at the frequency in question. Calculation of may be impressed. Such a line therefore appears as prac
R is difficult for the usual transmission line using stranded tically a short circuit at the particular frequency at wh
conductors, because common skin effect formulas apply it is a quarter wavelength long.
accurately only to round conductors. Formulas for The same phase relations apply for a line that is any o
stranded conductors have been developed, and these give multiple of a quarter wavelength long. The greater
good results for unweathered surfaces and straight parallel number of quarter wavelengths, however, the greater
strands, but arc subject to errors depending on the condi- total attenuation of the voltage along the path from
chapter 12 Power-Line Carrier Application

source to t,he oprn end and hack again, so that less and less
of the inptlt voltage is nc~~trnlixed and the line appears to
have progressively greater input impedance at the min-
im,lm points as its length is increased.
on the other hand, if an open-circuited low-loss line is
half ivave-length long, cllrrent arriving at the receiving
(,,,d is reflected with reversed polarity. Upon returning to
the sending end a full cycle after having entered the line,
this ~~crsed current directfly opposes the current entering
ttlc line and practically neutralizes it at all instants of time.
Thus, it is impossible to establish an npprcciable current at 0
c.-
the:inpllt terminals of such a line rcgnrdlcss of the voltage
aI,p]ietl. In other words, the input impedance of a half
N
,,.a&cngth open-ended line is cstremely high. The input
irnpCtlanCe of a line that is a multiple of a half wave in
~~~~~~~~~ depends upon the attenuation of the current wave
:Ll,,ngthe path from sending end to receiving end and back
:,g:lin. The longer $he line t,he lower is this impedance.
In t,he case of an open-ended lint of a given length, as the
frr~l~~cncyis varied over the normal carrier band from 50 to
I.;() kc, the input, impedance of the line oscillates between
rn:lsirna and minima at frequencies for which the line is
haIf wave and odd-quarter-wave resonant, respectively.
LINE LENGTH-WAVE LENGTHS
.\t, a given frequency, as the length of a practical line is
itlcreased, similar maxima and minima occur, but each Fig. la-Input impedance Zi of a typical line with various
sllcccetling maximum ant1 minimum point is closer to the capacitive reactance terminations.
s~~rgcimpedance of the line. This is illustrated in Fig. I 1,
termination is to make the line equivalent to a somcwhnt
longer line terminated in an open circllit. For csample,
Fig. 12 shows the input impedance of a line of 730 ohms
characteristic impedance as a function of length for various
capacitive reactance terminations.
25. Propagation on Ground-Return Circuits
The equations for the propagation of energy over a cir-
cuit consisting of a single isolated conductor lvith ground
return correspond exactly in form with Eqs. (la) and (lb)
for a two-wire circuit. In ground-return carrier transmis-
sion on power lines, however, the phenomena are com-
plicated by the presence of the other conductors and the
ground wires, because induced currents flow in these
paths as a result of their coupling with the conductor to
which the energy is initially applied. The equations for
this case are much more complicated.
Chevallier has given a symmetrical-component treat-
ment of ground-return carrier transmission on three-phase
lines14. He resolves the applied line-to-ground voltage into
LINE LENGTH-WAVE LENGTHS
positive-, negative-, and zero-sequence components and
“iti. It-Envelope of the minimum and maximum input uses corresponding propagation constants and charac-
impedance Zi at 100 kc of a line with attenuation of 0.186 db teristic impedances with each. .His results show that the
per wavelength (0.1 db per mile). presumably unused phase conductors actually play an im-
portant role as return conductors in line-to-ground trnns-
\vllich sho\vvsthe envelope of the input impedance of an mission. In practical cases, at a distance of 50 miles or so
W’n-ended line, having an attenuation of 0. I db per mile from the terminals on long lines without ground wires, the
at 100 kc, as the length is increased. amount of carrier current that flows in the ground is
In Power systems a line actually terminated in an open negligible, in comparison with that returning to the source
“iUit at carrier frequencies is rarely encountered. A much via the two opposite conductors in parallel.
more common case is that of short spur or tap lines term- The general equations derived by Chevallierinclude both
inated in power transformers, which at carrier frequencies the forward and reverse components of voltage and current
“sUall~ appear as a shunt capacitance of several hundred for voltage applied in any manner to the line; i.e., phase-
to several thousand ohms. The effect of a capacitance to-phase, phase-to-ground, or otherwise. Of greatest in-
412 Power-Line Carrier Application

terest is the case of line-to-grolmd coupling on long or and negative-sequence terms at a certain distance from the
properly terminated lines, in which reverse voltage and coupling point, and propagation takes place almost en- !
currents can be neglected. The equations are simplified tirely between the coupled phase and the other two. The s
in this cnsc, and with carrier voltage Es npplicd between return current divides equally between the latter.
phase one and ground, as shown in Fig. 13, the voltages to It has been noted that the attcauation per unit of dis- 2
tance is greater on short line-to-ground channels than on 3
long line-to-ground channels*. Equations (9) and (10) 1
provide at least a partial explanation of these results. j
2
At the receiving point the current in the tlvo uncoupled 1
phases causes a loss of energy in the terminating imped, ::
antes of these phases beyond the receiving point. This i
loss and the corresponding loss in the terminating imped, ;
antes on the opposite side of the transmitting point account ‘!
LINE
TRAP
for the extra attenuation noticed in long line-to-ground ;
channels as compared with phase-to-phase channels, i
according to Chevallier’s results.
Fig. 13-Configuration assumed in discussion of propagation
on ground return circuits. The impedances 2, may be lumped 26. Characteristic Impedance of Ground-Return
impedances or may be a continuation of the transmission Circuits
line.
The characteristic impedance of a circuit consisting of a ’
single conductor with ground return is
ground on phases 1, 2, and 3 at a distance 2 from the
transmitting point are:
(11)
(9a)
where h is the height of the conductor above ground and 7
is its radius in the same units. Typical values for phase-
(9b) to-ground carrier channels range from 400 to 600 ohms, :;
The characteristic impedance of a transmission-line con- -
Ex= E2. NC) ductor with ground return is not greatly affected by the I
and the corresponding currents arc: presence of the other conductors.
&2 E, 22’
E,E-~= (lOa) IV. NOISE VOLTAGE ON TRANSMISSION
20 1+2x’ E-ko=+Zil+2Z’)
LINES
I22 E, 1 2’
E-koz-~ -EsckE
1+2z, (lob)
Za 1+22’ Since signal-to-noise ratio is the main criterion of the
performance of a carrier transmission system, the noise
level present at the receiving end of a carrier channel is
In which equally as important to successful operation as the attenu-
lrO= zero-sequence propagation constant (propagation ation of the transmission path. The most important noise ,.
constant for voltage applied to all three phases in in a carrier system is that which originates in the power c
parallel, with ground return). system itself; atmospheric noise is negligible, except that _,
Z0 = zero-sequence characteristic impedance (character- caused by nearby lightning strokes. The normal noise in a
istic impedance of all three phases in parallel, with transmission system is the result of the presence of innum-
ground return). erable small arcs in dirty or defective insulators, poor
k = Positive- or negative-sequence propagation con- joints, and the like. This condition is aggravated by wet
stant (propagation constant for a three-phase car- weather, and is sometimes accompanied by corona dis-
rier frequency wave; i.e., square root of the product charge during such periods, with the result that noise
of line-to-neutral impedance and line-to-neutral usually increases to several times its normal amount. n’oise
admittance.) also varies with the time of day under good weather con-
2 = Positive- or negative-sequence characteristic im- ditions. Superimposed upon this normal or steady noise
pedance, line to neutral. is the noise caused by switch operatitxx, faults, etc.
7,-g zo+z2 27. Types of NoiselSJ1’22
J -2, z+z2
Z~=Load impedance (to neutral) on phases 2 and 3 at Noise from whatever cause can be classified under tMo
coupling point. See Fig. 13. general headings: random noise and impulse noise. Ran-
dom noise has a continuous frequency spectrum, containing
The first term in each of these equations is a zero-se- all frequencies in equal ptl;nounts. At th.? output of a receiver
quence term. The attenuation of the zero-sequence terms it produces a steady his$?g or %&irfg sound. The rms
is high on lines without ground wires, because of the high amplitude of this type of noise at the output of a receiver i?
resistivity of the ground return path. These terms become proportional to the square root of the bandwidth of the
negligible on long lines in comparison with the positive- receiver; i.e., the noise power is proportional to the band;
chapter I2 Power-Line Carrier Application 413

,vidth. The average and peak amplitudes are also pro- tremely limited, and no typical figures for “quiet” or
portional to the square root of the bandwidth. “noisy” lines have been established.
Impulse noise is of far greater importance in carrier sys- Figure 14 shows the results of one set of measurements
tems. It is produced when discrete, well-separated pulses made during fair weather on a 132-kv line that can be
exist at the mput terminals of a receiver. If the pulses are classified only as “relatively noisy” for carrier. These
irre$ar, the frequency spectrum is continuous and de- measurements were made with a Stoddart Type URM-6
pends only slightly upon frequency. If the impulses are
,iniform and regularly spaced, the spectrum contams
,liscrcte frequency components separated by a frequency I32 KV
,,crrcsponding to the repetition rate. Power-line noise is BUS
csscntially a com.bination of these two types of impulses, PHASE Y
since basic repetition rates of 60 and 120 cycles are dis-
cernible along with random discrete pulses, all of irregular
sn+tude.
28. Response of a Receiver to Impulse Noise**
I---LINE TRAP
TUNED TO
115 KC
DRAIN
~“,“,“,,‘~~~;R

NOISE
METER
t i i 1

COIL r-r
When a sharp impulse is applied to the input terminals of
a rccciver, the signal at the detector input is a damped
,,s~;illntion having the natural resonant frequency of the
1)rcccdingtuned circuits. The envelope of this oscillation, I Illal\l4l I I I 1
which represents the output of the receiver after detection,
CO.05 \, * ,, p h \,,\I , , , ,
rises to a peak value at a certain time and then decays to
zero. The greater the number of tuned circuits and the
Krcater their Q, the more slowly the envelope of the oscil-
l&on rises to a maximum and the lower its peak value;
i.~:.,the peak output is proportional to receiver bandwidth.
[lowever, the total area of the output signal envelope, and
licnce the average output, are independent of these factors.
In practice, if the impulses are sharp and well separated,
the rms output is independent of the shape of the impulses
:md is dependent only upon their areas, the gain of the
receiver, and the square root of the receiver bandwidth. I i Y‘\i i j / /
If the impulses are not well separated, so that in a receiver
of a given bandwidth the resulting wave trains overlap, the
responseof the receiver simulates that for a combination of
mndom noise and impulse noise. In some applications the
peak output is of major importance, whereas in others the
average or the rms output is the critical factor.
Thus, in specifying the characteristics of noise on trans-
mission lines, it is necessary to state not only the relative O.OOll
20
’ 60
’ too
’ ’
140
’ 180
’ ’ 220
’ ’ 260 ’
:bmounts of random and impulse noise in a given band- FREOUENCY-KILOCYCLES
width, but also the peak values of the impulses (or their Fig. ll-Noise voltages as a function of frequency on a rela-
statistical distribution) and the duration and spacing of tively noisy 132-kv line. The rise in the vicinity of 115 kc is
tllc individual impulses. In order to evaluate the effect of probably accounted for by the presence of the line trap.
this noise upon a given receiving system, it is necessary to
know the receiver bandwidth and gain and the particular noise meter. The curves show that the peak values of noise
Wplicntion involved. The number of tuned circuits and on this line are far in excess of the average values, indicat-
tlicir Q determine the receiver bandwidth at a given ing that average-reading instruments do not give a true
frequency. indication of the probable interfering effects of noise for all
applications. A graphic record of quasi-peak values* over
29. Measurement of Carrier-Frequency Noise on an extended time, including periods of rainy weather, gave
Power Lines the curves of Fig. 15, which indicate a relatively great
The accurate measurement of all the characteristics of increase in the noise under some conditions, with maxi-
carrier-frequency noise on transmission lines requires a mum quasi-peak values exceeding 100,000 microvolts for
considerable amount of equipment, including a noise meter approximately 3 percent of the time.
of definite bandwidth, capable of measuring peak impulse
*Quasi-peakreadingsare basedon a fast detector output circuit
amplitudes, and an oscilloscope to indicate the spacing and chargingtime and a slow dischargingtime, and henceare a function
tlle duration of the impulses. In order to be significant, of the peak amplitudes as well as the spacingof the impulses. The
readings should be taken over a period of time sufficient times are chosen so that the quasi-peak readings are approximately
to include both fair and rainy weather. As a result, actual proportional to the interfering properties of impulse noise in aural
test data of this type on carrier-frequency noise is ex- rcccption of a-m signals.
Power-Line Carrier Application

Cathode-ray oscilloscope patterns of the output of the i


detector of the noise meter used are shown in Fig. 16 Y$;
These indicate irregularity in the pulses, even with l/30: 2:
second exposures. The five-second esposure shows that ‘$
although the basic system frequency is present in the am- .:;
plitudes, the pulses occur almost at random throughout j”
the cycle. It must be remembered that these pulses have ‘I’
undergone a smoothing and rounding effect as a result of (,.
the action of the tuned circuits in the noise meter and that ?A
the actual pulses at the input of the meter were sharper c
and of shorter duration than those shown in the photo. :.‘.
graphs.

V. COUPLING AND TUNING EQUIPMENT


AND CIRCUITS
In the early days of power-line carrier it was universal ’
practice to couple the carrier equipment to the power line
by a method known as antenna coupling. In this method
the carrier equipment was connected to an isolated con-
ductor, several spans long, on the same tower with the
NOISE VOLTS PHASE WIRE TO GROUND AT 160KG circuit to which coupling was to be effected. Eventually
(QUASI PEAK)
it was realized that the energy which found its way into
Fig. 15--Quasi-peak noise voltages at 160 kc taken over two the power line was transferred mainly through the capa-
extended periods on the same 132-kv line. Both periods citance between the antenna and the line, and this led to
included rainy as well as fair weather. the development of compact capacitor units for coupling
purposes. Such coupling capacitors are safer, easier to in-
stall, and are a more efficient coupling means than anten-
nas. They also have the advantage that they can be used
simultaneously in conjunction with potential devices to
supply a voltage proportional to line voltage for the opera-
tion of protective relays and indicating instruments.

Fig. 16-Oscilloscope patterns of carrier noise at 85 kc with Fig. 17-Typical carrier coupling capacitor. This unit is rate:
l/30 second and 6 second exposures. at 115 kv and has a total capacitance of .00187 mfd.
chapter 12 Power-Line Carrier Application 415

30, Characteristics of Coupling Capacitors TABLE ~-CHARACTERISTICS OF TYPICAL COUPLINGCAPACITORS


1i typical carrier coupling capacitor is shown in Fig. 17.
The capacitor element proper is contained in a cylindrical Low Frequency Imp&o
Avcrnge Averngc Cap-
,,orcclain housing with cast metal ends. The capacitor Test R1IS liv Test Crest.
System Coupling ncitanceof Tap _
kV,
elements consist of a large number of individual working Voltage Capncit- for In-Phase ‘I’en +) or (-1
One
Poten in1Device 1Iinute Yecontls 1.5x-Iops
s,ctions in series. Each working section is made up of an l<V ancc
:,,<sernl)lyof special paper and foil, non-inductively wound mfd. mfd.
III-Y \\‘e t Full n-nvc
:rrl(Jimpregnated.
lntlivitlual capacitor units are made up in several dif- 46 ,004 .0205 110 100 250
69 .00275 .0225 165 I45 350
[,blent voltage ratings, and one or more such individual
92 .002 ,020s 215 190 450
,8:lpacitor units can be used in a stack to make up the
,Oompletecoupling capacitance. The stack is mounted on 115 .00187 0225 265 230 550
:1[netal base that contains a grounding switch, a protective 138 .00137 .0225 320 275 650
g:lp, and a carrier drain coil. These are connected as shown 161 .00125 .0225 3TO 315 i50
ill Fig. 18. The purpose of the drain coil is to ground the
230 ,00091 .0225 525 445 1050
257 oooi5 .0225 655 555 1300
Note: If in-phase potential device is Used. tot31 capacitance for carrier is tall
capacitance in series with coupling cspncitance. If in-phase potential device LY not
used, tnp cspacitance is short-circuited.

ties of the capacitor string. A variable-reactance trans-


former is provided for adjusting the phase angle of the
derived voltage, and a voltage-adjusting transformer is
provided for adjusting its magnitude. The potential device
is connected to the capacitor through a carrier-frequencz!
choke coil that isolates the device from the capacitor at
carrier frequencies.

Kg. 18--Schematic of carrier coupling capacitor without


potential device.
(1) Coupling Capacitor
(2) llulti-Unit Coupling Capacitor
(3) BaseHousing
(9) Carrier Apparatus Grounding Switch
(10) Carrier Apparatus Protective Gap
(11) Carrier Drain Coil

(,:Ipacitor terminal opposite the line terminal at 60 cycles


~(1 at the same time offer a high impedance at the carrier
fl~c~clucncy.The grounding switch is used to by-pass the l- ---+ _______ --_1___- -1
(Irain coil, providing a means of directly grounding the
(*:Lpacitorduring inspection and maintenance of the COUP- Fig. 19-Schematic of carrier coupling capacitor with poten-
ling and tuning equipment. The gap protects the drain tial device. A larger base than the one shown in Fig. 17 is
roil from excessive surge voltages during normal operation. used when the potential device is included.
The capacitances of typical coupling capacitors of vari- (1) Coupling Capacitor
ous standard voltage ratings are shown in Table 1, along (2) Multi Unit Coupling Capacitor
\vith typical impulse and low-frequency test voltages. A (3) BaseHousing
typical power factor for coupling capacitors at carrier (4) Transformer Grounding Switch
freWencies is 3 percent. (5) Transformer Protective Gap
(6) Variable Reactance Transformer
1-1diagram of a coupling capacitor with a potential (7) Voltage Adjusting Transformer
tlevice included in the base housing is given in Fig. 19. (8) Power Factor Correction Capacitor
The potential device is essentially a transformer connected (9) Carrier Apparatus Grounding Switch
across a portion of the capacitance of the lower or base (10) Carrier Apparatus Protective Gap
unit, deriving therefrom a voltage proportional to line (11) Carrier Drain Coil
voltage in accordance with the potential dividing proper- (12) Carrier Choke Coil
416 Pouxr-Line Carrier Agplicnlion Chapter 12 f._

_, ..-. ” .i
Fig. 20-Typical 400-ampere carrier line trap. (Type P-400).

31. Characteristics of Line Trap@


21 line trap is a parallel resonant circuit tuned to offer a
high impedance at a specific carrier frequency and inserted
in series with one of the conductors of a transmission line. 50 70 90 I10 130 150
Line traps have negligible impedance at power frequencies FREQUENCY. KC
and therefore do not affect normal power current. Fig. 22-Resonant impedance of typical 400- and SOO-ampere
A previous discussion in this chapter pointed out the line traps. The difference in impedance is due to the different
deleterious effect that short spur or tap lines may have inductances used in the two ratings.
when bridged across a carrier channel. Such lines can be
isolated from the carrier system by the insertion of line current of the conductor into which it is inserted. This
traps in series with one or more conductors of the spur line coil is wound on a porcelain cylinder, which also serves 1~
at its junction with the main line. Loops that offer alter- a housing for the adjustable capacitor unit used to tune
nate paths to the carrier current can be broken up by use the coil to resonance at the desired frequency. A lightning
of line traps. A line trap is always used at each end of a arrester is provided across the trap to protect the capacitor
line section to which carrier relaying is applied. Their unit from damage due to surges.
major purpose in this application is to prevent a nearby Manufacturers have standardized on 400 and 800 am-
fault on an adjacent line section from short-circuiting the pere ratings for line traps, and single- and double-frequency
carrier channel and interrupting the transmission of a
100
blocking signal to the opposite end of the line. In general, 111111~11111111111
line traps provide a means of raising signal levels by con- IMPEDANCE SINGLE I ii PHASE ANGLE SINGLE
fining the major portion of the carrier energy to its in-
tended path and by isolating sources of high attenuation
from the carrier circuit.
A typical carrier line trap is shown in Fig. 20. This unit
is rated at, 400 amperes at 60 cycles. The main coil is a
heavy copper cable, capable of carrying the full power

LINE MAIN COIL


.LINE
TERMINAL TERMINAL
ARRESTER

I I I I I I-

I IIIllw&
LPHASE ANGLE
VARIOMETER Q DOUBLE FREQ --
-i+ o-I!+ TUNING
o~~~~-~~~‘~ ~‘~~~’ -0
-It- 95 96 96 100 I02 104
-i+ 24
CAPACITORS PERCENT OF RESONANT FREQUENCY .A
Fig. 21--Schematic of double-frequency line trap. Fig. 23-Resonance curves of typical single- and double’ “:4
(Type PDF-400). frequency line traps. fj
chapter 12 Power-Line Carrier Application

models are available in both ratings. h schematic diagram


for a double-frequency trap is shown in Fig. 21. The ex-
t,,rnal appearance of a double-frequency trap is the same
as that of a single-frequency trap of the same rating, be-
cLIL1se the extra circuits used to obtain the double-resonance
,tr,racteristic are contained inside the main coil, which is
tt,c same in both cases.
The resonant impedances of typical 400- and 800-ampere
lint traps over the 50-150-kc band are given in Fig. 22.
‘fhc difference in the two curves results from the difference
in the inductances of the coils used in the two ratings.
Figure 23 gives resonance curves for typical 400- and 800-
:,nrpcre single-and double-frequency traps.
When a line trap is used to isolate a low-impedance
,;irellit, the losses are not reduced to zero but to a value
that, is a function of the characteristic impedance of the
(a;lrrier channel and the impedance of the trap in the vi-
,*irrit,y of resonance. Figures 24 and 25 are curves of the
~OSSCS in typical single- and double-frequency traps re-
spcctively when a line-to-ground channel of 500 ohms
&racteristic impedance is grounded through them.
f,osses in practical applications are somewhat less, de-
[)cntling upon the actual impedance of the offending cir-
cuit or device, and the losses shown by these curves should
be tjaken as limiting values.
A single line trap at the end of a line-to-ground coupled
channel does not materially reduce interference to channels
on the same or nearby frequencies on lines beyond the trap,
lwause it does not interrupt the current in the two un-
94 96 98 100 102 104 106
PERCENT OF RESONANT FREQUENCY
Fig. 25-Losses in typical 400- and boo-ampere double-fre-
quency line traps when a line-to-ground carrier channel of
500 ohms characteristic impedance is short-circuited through
them.

coupled phases. Two line traps, one in each phase conductor


of an interphase coupled channel, are more effective in this
regard. Even in this case, however, there is usually suffi-
cient unbalance in the system at carrier frequencies to cause
appreciable current in the unused conductor, with resulting
interference to channels beyond the trap location. The
installation of a line trap in each of the three phases of a
line is the only effective way of isolating a channel for the
purpose of reducing interference, regardless of the method
of coupling used. For this method to be successful, there
must be no important sources of coupling between circuits
on opposite sides of the line traps. This means that these
lines must extend in opposite directions from the trap loca-
tion and must not be paralleled by untrapped lines. The
degree of interference reduction obtained then is a function
of the resonant trap impedance, the characteristic imped-
ance of the lines in question, and the amount of coupling
that remains between the ends of the circuits on opposite
sides of the line traps.
6
32. Tuning Devices
PERCENT OFRESONANT FREQENCY
Fig. 24-&, sses in typical
The load resistances presented by power-transmission
400- and 800-ampere single-fre-
quency line traps when a line-to-ground carrier channel of
lines at carrier frequencies range from 400 to 900 ohms,
5oo ohms characteristic impedance is short-circuited through and the reactances of coupling capacitors, which are effec-
them. tively in series with this load, are apprcciablc and must be
418 Power-Line Carrier Application Chapter 12

TO COUPLING CAPACITOR TO COUPLING CAPACITORS


t t t

IMPEDANCE
MATCHING
TRANSFORMER
r--------

Fig. 28-Schematic diagram of an interphase single-fre.


50-55 OHM quency line tuner.
CABLE INPUT
Fig. 26-Circuit diagram of single-frequency phase-to-ground
line tuner. Switch S2, Gap SG3, and Drain Coil are omitted if
included in coupling capacitor assembly.

compensated for if maximum coupling efficiency and a


resistive load condition for the carrier transmitter arc to
be obt,ained. This compensation can be provided by plac-
ing in series with the capacitor an inductance that can be
adjusted so that its reactance cancels the reactance of the
coupling capacitance at the carrier frequency. The pri-
mary purpose of a line tuning unit is to furnish an adjust-
able inductance for this purpose. This inductance usually
takes the form of a tapped main coil, which furnishes large
steps in inductance, in series with a variometer that pro-
- - _

Fig. 29-A typical interphase line tuner.

vides a continuous range between’ tap values. Line tuners


also include an impedance-matching transformer for trans-
forming the characteristic impedance of the line to a
value that properly terminates the coaxial cable commonly
used between the carrier assembly and the line.
A schematic diagram of a typical single-frequency tuner,
used to couple the carrier energy to a single phase con-
ductor, is shown in Fig. 26. Figure 27 is a typical tuner
of this type. Ground is used as the return circuit with this
tuner. A protective gap is provided to prevent over-
voltages from damaging the tuning inductances. The
grounding switch is used to ground the lead from the
coupling capacitor during inspection or adjustment of
the tuner.
A phase-to-phase tuning unit is shown in Figures 28 and
29. In this unit two identical inductance coils and variom-
Fig. 27-Typical single-frequency phase-to-ground tuner. eters are provided, one set for each capacitor. The
chapter 12 Power-Line Carrier Application

impedance-mat,ching transformer is balanced to ground by


II1cansof a center tap on the line side.
33. Multi-Frequency Tuning
lt is often necessary to provide for the coupling of more
than one carrier frequency to a line at a given location. In
sucll cases a worthlvhile economy can be effected by the
,lSe of a multi-frequency tuning system, which permits a
+gle coupling capacitor to be tuned to two separate $
c:lrricr frequencies.
:I schematic diagram of a two-frequency tuner for line-
to-ground couplin, v is given in Fig. 30. The equipment
Ml
,:onsistS essentially of two single-frequency tuners, in series

TO COUPLING CAPACITOR

Fig. 31-A typical two-frequency line-to-ground tuning


assembly of the type shown in Fig. 30.

the same coupling capacitor. Correspondingly, the branch


that is to be tuned to the higher frequency requires more
inductance than normal because the reactance of the asso-
ciated trap circuit is capacitive. If the two frequencies are
L2
too close together, the additional reactances presented by
F2 the wave traps are so high that the overall series circuits
cannot be tuned to resonance at the desired frequencies
t= with ordinary tuning inductances. The separation required
between the two frequencies depends upon the capacitance
Fig. 30-Two-frequency line-to-ground tuning system with of the coupling capacitor and the inductance range avail-
separate coaxial leads for each frequency. able in the tuning inductances, but in general, the higher
frequency must be at least 25 percent greater than the
with en& of which a parallel-resonant trap circuit has been lower for satisfactory tuning with tuning inductances of
:~tltlcd. l(;ach trap circuit is tuned to the carrier frequency the usual range. When the frequencies are too close to
whic:h is to hc passed through the tuning inductance in permit tuning as above, it is sometimes possible to obtain
lhc opposite branch. Thus, if a frequency 8’1 is to be series resonance at the lower frequency by adding a fised
p:~ed through inductance L1, the trap circuit in series capacitor in series with the trap circuit to neut,rnlize some
\vith the opposite branch is tuned to F1 to prevent the of the excess inductive reactance obtained. This is the
wrricr energy from being lost in that branch. Likewise, purpose of the fixed capacitors Cl and C? shown in Fig. 30.
the trap circuit in series with the first branch is tuned It must be kept in mind that losses in the trap circuits
to the opposite frequency FS to prevent loss of energy increase rapidly as the frequency separation is reduced,
from source two. X photograph of a typical two-frequency however, so that every effort should be made to locate the
tuner ut,iIizing the system just described is shown in channels in the spectrum with sufficient separation to avoid
Fig. 31. this espedient.
The trap circuits have appreciable reactance at fre- This system of multi-frequency tuning can bc extended
(lllencies off resonance, and for this reason the main series theoretically to handle as many separate frequencies as
inductances cannot be finally tuned until the trap circuits desired. For example, Fig. 32 illustrates a three-frequency
lwe been individually adjusted to the proper frequencies. system. In this case the trap circuits in each series leg are
.-It frequencies below resonance, a trap circuit has induc- tuned to the frequencies of the opposite two legs. From a
tive reactance that increases as the resonant frequency is practical standpoint, however, it is generally inadvisable
approached. The branch that is to be tuned to the lower and uneconomical to attempt to tune a single capacitor to
frequency, therefore, requires less inductance for overall more than two frequencies. The complexity of the tuner
series resonance than a single-frequency tuner used with and the difficulty involved in tuning it successfully to three
Power-Line Carrier Application
jI
TO COUPLING quency, the LICl circuit shows a net capacitive reactance, 6
t
CAPACITOR This reactance is tuned in combination with Lz to parallel ~4
resonance at a frequency intermediate between the upper ::
and lower frequencies desired. Below this parallel resonant Yg
frequency, therefore, the LlClL combination appears in- ,:

$
ductive, the magnitude of the inductive reactance depend.
ing upon the intermediate frequency chosen. By varying
this frequency by adjusting L?, the net inductive reactance
of the LICIL, combination in series with the main tuning ,,
inductance L can be made to tune the entire circuit to
series resonance at the lower frequency.

c!
Ic
If the double-frequency tuning scheme described ahova
is used for coupling two transmitters to a line at a single
location, trap circuits must be used at the transmitter out-
put circuits to avoid the loading of one transmitter by the
output circuit of the other when both work into a single
coaxial cable.
34. Omission of Outdoor Tuning Equipment
On many carrier channels the terminal equipment is
capable of operating through much greater attenuation

IIT than that introduced by the line itself. In such cases some
economy in installation can be effected and greater con-
venience in making tuning adjustments can be provided
by eliminating the usual outdoor tuning equipment and

r
Fig. 32-Three-frequency tuning of a single coupling capac-
supplying equivalent units in the carrier assembly. In
such cases the coaxial cable is usually connected directly
to the coupling capacitor at the line terminal, as shown in
itor. Fig. 34. Some reduction in the resultant losses in the
cable, due to the impedance mismatch at the junction of
different frequencies nearly always outweighs any saving the cable and the capacitor, can generally be effected by
effected in equipment. using an impedance matching transformer at the coupling
*Another tuning circuit, which is series resonant to two capacitor, as shown in Fig. 35. Such a transformer can
frequencies and requires only a single co-axial lead, is make the terminating impedance equal in magnitude to the
shown in Fig. 33. The procedure for adjusting this circuit
is to short-circuit the LlC, combination and adjust L to
series resonance with C at the higher of the two frequencies. 1 COUPLING
With the short circuit removed, and with Lz disconnected, CAPACITOR
L, and C, are then tuned to series resonance at the same COAXIAL CABLE
frequency. L, and C1 then effectively short circuit L, at m
the upper frequency, and its inductance, regardless of its z
value, has no effect at this frequency. At any lower fre- DRAIN
COIL

-i =
C1 COUPLING
Fig. 3kOmission of outdoor tuner and matching trans.
former. ,“+(
L2
f$

Fig. 35-Omission of outdoor tuner, matching transforme


Fig. 33-A two-frequency tuning system requiring only a used to match absolute value of line and coupling capacity
single coaxial lead. impedance to coaxial cable impedance.
chapter 12 Power-Line Carrier Application 421

surge impedance of the cable, but it cannot compensate for the terminating impedance in either of these systems. .\
the capacitive component of the combined line and conventional line tuner is not, in all cases, adequate to
co,lplirl~ capacitor impedance. compensate for the reactances t,hat may be encountered,
~11~loss in a given length of coaxial cable in such instal- nor are the impedance-matching transformers usually in-
lations is dependent upon the frequency involved, the cluded in such tuners always capable of transforming the
re;ictance of the collpling capacitor, and the surge imped-
:,,Ice of the line, as well as upon the characteristics of the 700
,.o:rsial cable itself. The curves of Fig. 36 show the meas-
gf300
I-
CO’JPLlNd
::-500
CAPACITANCE Y
12 z 400
b .^ Li
IU ’ c ’ z 300
2 ii
08 b-200
0
2
5’5 z 100
54
-I 0
2 CABLE LENGTH, FEET

’ Fig. 37-Input resistance and capacitance CR -jX,) at 100 kc


of various lengths of coaxial cable operating directly into
CABLE LENGTH, FEET 900-ohm resistive load through coupling capacitances shown.
No impedance matching transformer used (Fig. 34).
Fig. 36--Measured attenuation at 100 kc of various lengths of
coaxial cable operating directly into 900-ohm resistive load
through coupling capacitances shown. No impedance match- resistive component to the proper load resistance for the
ing transformer used (Fig. 34). transmitter. Both the resistive and reactive components
become very low as the length of the cable is increased up
urccl db Ioss at 100 kc with various lengths of a typica to a quarter wave. The input capacitance and resistance at
coaxial cable, operating into a 900 ohm line through 100 kc of a coaxial cable terminated in various capacitances
coupling capacitors of several different ratings. These and a 900-ohm line are shown in Fig. 37.
curves apply for the case where no matching transformer is
35. Carrier Coaxial Cable
wed at the coupling capacitor. For the case where a
matching transformer is used, F. M. Rives15 has published It was common practice in the past to locate the carrier
similar data, giving the maximum length of coaxial cable transmitter and receiver relatively close to the coupling
Permissible for given db losses at several different fre- capacitor and tuner, and to connect the assembly directly
to the tuning inductance without impedance transforma-
TABLE 2 tion at the tuner, as shown in Fig. 38. In such installations
I
RecommendedMaximum Cable Lengths in
HIGH IMPEDANCE
Feet from Coupling Capacitor 3 jll$ ,SECONDARY
to Terminal Equipment
Coupling Matching Transformer Used Without
(::lp:witnnc:e Tuning Equipment
Ulid.
For I-db Attenuation For 2-db Attenuation
50 kc 85 kc 150 kc 50 kc 85 kc 150 kc
-------
.OOOi5 150 180 200 300 350 410 Fig. 38-Use of insulated aerial lead between carrier trans-
,001 200 230 250 390 430 600 mitter and outdoor tuner.
.0012 240 270 300 430 500 750
.0015 260 300 340 500 600 800 the lead between the carrier assembly and the tuner oper-
,002 360 390 460 680 800 1000 ates at line impedance level, and unless this lead is sup-
.003 450 450 475 900 1000 1000
ported aerially and is well insulated, losses resulting from
_ ,006 800 800 800 loo0 IO00 loo0
shunt conductance to ground becomes excessive in lengths
over 100 feet or so.
rluencies with various coupling capacitances. Table 2 is Modern developments in solid-dielectric cables have re-
tLilw from Rives’ paper. sulted in practically complete abandonment of the practice
The reactive and resistive components of the input im- of making the connection between the set and the tuner
pedance at the transmitter end of the coaxial cable vary through a high-impedance lead. The losses in such cables,
radically with the frequency, the length of the cable, and when they are properly terminated, is only about 0.5 db
422 Power-Line Currier Application

per 1000 feet at carrier frequencies, and they can be run


through conduit or buried directly in the ground without
effect upon their performance.
The specification for a typical coaxial cable used in
power-line carrier work is as follows: L
The center conductor consistsof a single-conductor O.IOBinch
diameter (No. 10) soft-drawn, tinned copper wire. This con-
ductor is covered with a continuous coating of 60 percent low-
capacity rubber insulation making the outside diameter approx-
imately 0.450 inch. Over this is a copper braid, equivalent in
cross-section to the center conductor, made up of No. 30 tinned
II
copper wire. Over this is a lead sheath 3/64inch thick with K k
percent antimcny. The outside diameter does not exceed 0.6 T +
inch. The high-frequency loss does not exceed 0.32 decibel at (a) LINE TO GROUND (bl INTERPHASE
50 kilocycles, nor 0.60 decibel at 150 kilocycles. The surge im- 4 ”
petlance is approximately 60 ohms. (~1 INTERCIRCUIT

The measured characteristics of coasial cable manufac-


tured to these specifications were found to be as follows: A
B
Surge impedance. (il. 1 / -OO”29’ ohms c ti i
Propagation constant. .0.568
Attenuation at 150 kc. .0.429 db/lOOO feet A
Resistance. . . . . . .3.9 1 ohms/1000 feet s
Inductance. . . . . . ,110.l mh/lOOO feet c
z
Shunt conductance.. . . . . .519 micromhos/ 1000 feet
Shunt capacitance. . . . . . .0.0295 mfd/lOOO feet ti+
Similar coaxial cables with synthetic rubber or plastic
jackets, instead of lead, are also widely used. The elec-
trical characteristics are about the same.
36. Methods of Coupling II
There are a number of different ways of utilizing one or
T 7
more conductors of a three-phase power line as conductors
for carrier-frequency currents. Some of these are illustrated ‘d) ~~~~~~~~~~,!+~
in. Fig. 39. The simplest of these, and by far the most pop- (e) BUS COUPLING
ular, is to use a single conductor of the power line as one Fig. 39-Methods of line coupling.
leg of the carrier circuit, with ground as the return path
(Fig. 39a). This system, commonly called “line-to- and electromagnetic coupling between an open or grounded
ground,” “phase-to-ground,” or “single-phase ground- conductor and the two unaffected conductors to transfer
return” coupling, requires less coupling equipment (cou- enough energy around such a discontinuity to maintain 8
pling capacitors and tuners) than any of the other methods usable communication signal, provided the conductor iz
shown, and it is universally used for short-haul, point-to- not opened or grounded closer than several hundred feel
point channels, such as for relaying. On lines not provided from the carrier terminal, and also provided that the
with ground wires, the attenuation of a circuit using this channel normally operates with sufficient margin to takt
method of coupling is higher than an equivalent length of care of the increased signal-to-noise ratio. The secondarj
circuit using line-to-line coupling, particularly if ground of the impedance-matching transformer used in the inter
characteristics are unfavorable. Line noise is also some- phase system is usually center-tapped and grounded, ant
what greater. However, modern practice favors line-to- if one of the conductors is grounded close to the terminal
ground coupling for all except the longest and most im- the output transformer may be partially short-circuited
portant carrier channels. resulting in a reduction of signal strength.
The coupling system shown in Fig. 39b is variously
termed “line-to-line,” “phase-to-phase,” or “interphase” 37. Inter-Circuit Coupling
coupling. This system was at one time used almost ex- If a double-circuit transmission line exists between car
clusively in preference to line-to-ground coupling for com- rier terminals, consideration can be given to several meth
munication channels and most telemetering channels of ods of coupling that increase carrier-circuit reliabilitl
any length, but in recent years has given way to some under abnormal system conditions. One of these is inter
extent to line-to-ground coupling. At first glance this circuit coupling, shown in Fig. 39c. With this type o
system appears to have the advantage that one of the con- coupling either circuit can be taken out of service and al
ductors can be grounded at any point without interrupting three phases can be grounded at any point without inter
the continuity of the carrier channel. However, in the rupting the continuity of the carrier circuit. In inter
line-to-ground system there is often sufficient electrostatic circuit coupling, connection is made to one phase of onI
chapter 12 Power-Line Carrier Application 423

circuit and to a different phase of the other. When both


lines are in service and are bussed at both ends, this type
of coupling is equivalent to interphase coupling. Inter-
,irc\,it coupling can be used only on a double-circuit line
that cannot be sectionalized between carrier terminals.
38. Double-Circuit Ground-Return Coupling
$%;:I NG .$$$DE;
Jn double-circuit ground-return coupling, Fig. 39d, the
cILrricr signal is coupled to the same phase of the two cir- Fig. 40--Suspended by-pass arrangement.
cuits, and these operate in parallel under normal condi-
tions with ground return. With this type of coupling either is energized. It should never be used to by-pass disconnect
line can be taken out of service or sectionalized between switches or circuit breakers, or to pass signals from a line of
terminals without interrupting the carrier channel. In one voltage to a line of another voltage, except at trans-
fLICt,some installations use this type of coupling in which a formation points, because the ungrounded coupling’capac-
I,,“tion of the intervening path between the terminals is a itor can supply dangerous amounts of charging current
,i~~gIe-circuit line. It is generally possible with this type from the energized side of an open switch or breaker to the
(,f coupling to ground one of the two circuits for main- apparently de-energized line.
l,cnance without interrupting carrier service, provided the The simplest by-pass assembly suitable for general
Kround is not applied directly at the coupling capacitor application as a short by-pass is that shown in Fig. 41.
lo&ion. Even in the latter case, if there is sufficient mar-
gin between the capability of the carrier sets and the
normal attenuation of the circuit, it is often possible to
keep the carrier channel in service.
39. Bus Coupling
Where it is desired to couple the carrier signal to several
I ransmission lines simultaneously at a given location, bus
c*oupling, Fig. 39e, is sometimes used. This system of
caorlplingcan be used either phase-to-ground or phase-to- LINE
TUNERS
phase. It, is subject to several disadvantages, among them
1.11cfact that the opening of any circuit breaker on a given
line between the two terminals, even at the terminals
themselves, interrupts the carrier channel over that line. Fig. Il-Conventional short single-frequency by pass. One
Also, if there are more than a few circuits connected to the tuning inductance can be omitted in some cases.
IHIS,it may be impossible to locate a carrier frequency that
~tn provide satisfactory operation under all system Two coupling capacitors and a single tuning assembly,
switching conditions, and the number of line traps re- consisting of two tuning inductances, are used. The con-
cluired to isolate offending lines may eliminate the apparent nections between the inductances and the capacitors are
economic advantage of bus coupling. made with insulated aerial leads. No coaxial cable is em-
ployed. Since the leads between the ca,pacitors and the
40. By-Passing of Carrier Signals tuning inductances operate at a high. r-f potential, they
Carrier by-pass assemblies are used to provide a path for must be extremely well insulated to prevent excessive
carrier energy around transformers, switches, circuit losses due to shunt conductance. This system is not
Ijrcakers, or other discontinuities that may exist in a car- recommended for installations where the coupling capac-
rier channel. By-pass assemblies consist essentially of one itors are separated by more than 100 feet. The tuning
or more coupling capacitors and associated line tuning inductances should be located as nearly midway between
Mits. The capacitors are tuned to series resonance at the the coupling capacitors as possible.
frequency or frequencies to be passed around the discon- For higher frequencies, or with lower-voltage lines where
t.inuity. The following discussion specifically shows by- coupling capacitors of relatively higher capacitance are
Nssing arrangements used with channels coupled line-to- used, a single tuning inductance is often sufficient to tune
ground, but it should be understood that similar arrange- both capacitors to resonance.
ments utilizing twice the number of capacitors and tuning
inductances can be applied on interphase channels. 42. Long By-Passes
The most efficient of the commonly used by-pass arrange-
41. Short By-Passes ments is that shown in Fig. 42, in which a tuning induc-
The simplest type of by-pass assembly is that shown in tance and impedance-matching transformer are located at
Fig. 40, consisting of a single coupling capacitor and a each coupling capacitor, and coaxial cable is used as the
single line tuner, both suspended in the line. This simple link between them. With this arrangement the distance
sYstem is suitable only for by-passing transformers, regula- between the coupling capacitors can be as much as several
tors, and other such equipment that normally provides volt- thousand feet, depending upon the losses in the coaxial
age on both sides of the by-pass assembly when either side cable at the frequency involved.
424 Power-Line Carrier Application Chapter 12

1
III
---I- llh ---r
COUPLING 1

T CAPACITOR
T
TUNING
INDUCTANCE

MATCHING
COAXIAL CABLE
TRANS I
1 1
1 I

Y
Fig. 42-Conventional long by-pass.

This type of by-pass actually amounts to two ordinary Fig. 44-Three-way by-pass.
line tuning srrangcments connected to operate into each
other. If a carrier assembly is to be coupled into the line at Consideration has been given to the use of band-pa=
the by-pass point, as might be desired on a multi-station by-pass circuits, such as that shown in Fig. 45. In this caSe
communication system, the coaxial cable from each tuner the coupling capacitors form a portion of the series arms of
is brought into the carrier assembly and connected to the a simple “T” section band-pass filter. Many other such
low-impedance transmitter output tap usually provided arrangements are possible.
for operation into two such cables in parallel. This arrange-
ment is shown in Fig. 43.
This by-pass arrangement may be extended into a three-
way system, as shown in Fig. 44, to pass signals from one
line into two others. There is an inherent impedance mis-
match in such a system at the junction of the three cables,
as a result of the fact that each cable is terminated in one
half its surge impedance. In addition to the 3-db loss in
each direction due to the division of power between the
two paths, there is a loss of about 0.5 db due to the
mismatch at the junction.
43. Multi-Frequency By-Passes Fig. 45-Band-pass by-pass system.
All the multi-frequency tuning schemes shown in Figs. 30
to 33 can be applied in by-pass assemblies, so that more VI. METHODS OF ESTIMATING CARRIER-
than one frequency can be passed. The arrangement shown CIRCUIT ATTENUATION
in Fig. 30 is the easiest to tune and is the one most com-
monly used in such cases. 44. The Decibel
The decibel is a convenient unit for expressing the ratio
between the power levels at two points in a communication
system. This is because the actual ratios are often so large
I I
I that their use is inconvenient on this account alone, and
also because it is necessary to multiply the input and out-
-I-
put power ratios for each individual component of the
system to obtain the overall ratio. Losses and gains in
decibels for individual components of a system can be
added directly to give an overall loss or gain for the
system.
The decibel is defined as 10 times the common loga-
rithm of the power ratio, the ratio always being expressed
as the quotient of the larger power by the smaller power;
i.e.,
Pl
db = 10 log,, p, If P, > Pz (12a)
OI-

db = 10 log,, g if Pp > PI. (i2b)


Fig. 43-By-pass with carrier terminal. 1
Chapter 12 Power-Line Carrier Application 425

The rat,io of two voltages or of two currents can be ex- TABLE 3-APPROXI~MATE LOSSESIN COAXIAL CABLE
pressed in decibels as follows, pror:idcd that the impedances
q/ the circuits in which these coltages or currents exist are Frequency, kc I Loss, db per 1000 ft.
the same:
20 0.2
db = 20 log,,; (13) 50 0.32
100 0.5
I* 150 0.6
db = 20 10g,,~. (14) 300 0.9

Convenient decibel figures to remember are that a 2 to 1


power ratio is 3 db, 3 to 1 is 4.S db, and 10 to 1 is 10 db. impedance matching transformer is provided for this pur-
From these figures the number of decibels corresponding to pose in the tuning unit. The losses in typical coaxial cable
I-to-l, 5-to-l, G-to-l, 8-to-l, and 9-to-1 ratios and any as a function of frequency when properly terminated are
tlccimal multiples of these ratios can be estimated quickly shown in Table 3. Typical losses in coaxial cable operating
tjy simple mental addition. directly into a 900-ohm line without impedance matching
or tuning are shown in Fig. 3G.
45. Decibel Rating of Carrier Assemblies Losses in Tuning and Coupling Equipment--It,
It is common practice to rate carrier transmitter-receiver is possible to calculate accurately the losses in a tuning and
assemblies in terms of the maximum number of decibels of coupling circuit, provided that the Q’s of the tuning in-
attenuation through which two similar assemblies can ductance and the coupling capacitor and the characteristic
operate satisfactorily. Actually these ratings are based on impedance of the line are known. However, it is usually
the assumption of noise levels at the receiving location permissible for estimating purposes to assume a loss of one
that can reasonably be expected on a normal power sys- db for a simple tuner-capacitor combination working into
tom, and the decibel rating has been assigned on the basis an open-wire line.
of providing a satisfactory but undefined signal-to-noise Losses in tuning and coupling equipment working into a
r:tt,io. This practice in rating carrier equipment unduly circuit of low characteristic impedance, such as a combina-
penalizes it when applications on relatively quiet systems tion of several lines in parallel, or a power cable, are great,-
are contemplated, because most equipment is capable on er. -ln increase in coupling loss of one db can be assumed
rllliet lines of operating through much more than its rated for each additional line at a transmitting point. In the
at,tcnuation. As more is learned about the nature and the case of power cables, an accurate calculation is desirable.
rnagnit,ude of carrier-frequency noise on power systems, it The db attenuation of a single line tuner and coupling
is reasonable to expect that more informative ratings based capacitor, applied to a power cable or other circuit of char-
lipon the transmitter power and the receiver sensitivity and acteristic impedance Z,, is
the response of the latter to noises of a given character and
magnitude will come into practice.
Zc+Rc(l+Q,l&~)
db = 10 log,,
2,
46. Losses in a Carrier Circuit in which R, is the resistive component of the coupling
The most common sources of attenuation in a power-line capacitor impedance at the frequency considered, and Qc
(wrier circuit arc: and QL are the Q’s of the capacitor and the tuning induc-
1. Losses in coaxial cable between carrier assemblies tance, respectively. A Q of 50 to 80 is typical for tuning
and tuning units. inductances in the 50-150-kc band. For estimating pur-
2. Losses in tuning and coupling equipment. poses, a Q of 30 can be used for coupling capacitors.
3 Lossc~ in by-pass equipment. The coupling loss for receiving is independent of the
i: Ijosses in straightaway transmission lines. number of branch circuits at the coupling point, since in
5. Losses due to discontinuities in transmission lines. this case the carrier equipment is the terminating device
0. IJosses due to division of energy (a) in long branch for the coupling circuit. For estimating purposes, a re-
circuit,s at transmitting points, and (b) in long ceiver coupling loss of 1.0 db can be used.
branch circuits remote from transmitting points. The attenuation figures given above are based on single-
7. Losses due to low impedance presented by untrapped frequency line-to-ground coupling and for estimating pur-
spur lines. poses can be doubled for interphase coupling. In the latter
8. Losses due to simultaneous propagation over alter- case, however, the characteristic impedance of the line is
nate paths. greater and the actual difference in attenuation is some-
what less.
The total attenuation in decibels for an entire circuit is The losses in two-frequency tuners are higher than those
the sum of the decibel losses for each part of the circuit. A in simple single-frequency tuners. No accurate figures can
(liscussion of the attenuation that can be expected from be given, because the additional losses depend critically
each of the above sources follows. upon the Q’s of the inductances and the separation of the
Losses in Coaxial Cable-In practice an attempt is two frequencies involved. For a separation of 25 percent
‘Ually made to match the characteristic impedance of the or more of the higher frequency, a loss of 2 db at each fre-
transmission line to the impedance of the coaxial cable quency can be used for estimating purposes on line-to-
used between the carrier assemblvY and the tuning unit. An ground channels, or 4 db on interphase channels.
426 Power-Line Carrier Application

Losses in By-Pass Equipment-The losses in by- ing purposes regardless of the frequency, the line voltage,
passing equipment are at least twice those of coupling or the method of coupling.
equipment at a carrier terminal because two sets of COU- Losses Due to Discontinuities in a Line-Any series
pling capacitors and tuners are involved. An interphase or shunt impedance or physical condition at a given point
by-pass involves four times as much coupling equipment as in a line that causes the impedance seen looking into the
a line-to-ground terminal, and the losses in this case can line just ahcad of the point in question to be different from
be assumed to he about four times as great, or 4 db. Losses the characteristic impedance of the line up to that point
in the coaxial between the two tuners must be added to constitutes a discontinuity in the line. Discontinuities
these figures. give rise to reflections and standing waves that cause in-
A factor that can increase the apparent loss in by-pass creased losses in the line up to the discontinuity. In addi-
on a phase-to-ground circuit is that the carrier energy in a tion to these losses there may be losses in the device caus-
phase-to-ground channel tends to use the idle phases of ing the discontinuity, with the net result that a discon-
the line as a return path. Since only the phase to which the tinuity is a source of additional attenuation in a carrier
carrier is directly coupled is normally by-passed, the open- channel.
ing of a by-passed circuit breaker interrupts the return When a discontinuity as defined above exists close to a
path offered by the other two phases, and a greater in- transmitting point, so that a large fraction of the reflected
crease in attenuation than that indicated by the loss energy returns to the transmitter, the line does not present
figures previously given may be experienced. This is par- its surge impedance as a load to the transmitter and may in
ticularly true of phase-to-ground channels on lines not fact present an impedance that is highly reactive in nature.
provided with ground wires. In such cases it is necessary to compensate for the reactive
In circuit-breaker by-pass installations involving long portion of the line impedance by proper adjustment of the
coaxial cable runs, it is occasionally found that the attenua- line tuner and to match the resulting resistive component
tion of the overall circuit is greater when the breakers are of the load, which may be higher or lower than the char-
closed than when they are open. This can be explained as acteristic impedance, by adjustment of the taps of the im-
a case of attenuation due to simultaneous propagation pedance-matching transformer in the tuner. Although the
over alternate paths, to be discussed presently. A remedy losses in the short section of line up to the discontinuity
usually effective in this case is to reverse the phase of the are greater than if the line were properly terminated, the
current traveling through the by-pass circuit by reversing increase is not serious except in extreme cases, and the only
the connections to the impedance matching transformer in major loss, if any, is that in the device causing the dis-
one of the tuners. continuity.
Losses in Transmission Lines-The attenuation of a On the other hand, when a discontinuity exists at an
straightaway transmission line at carrier frequencies is intermediate point in a channel, sufficiently far from the
subject to many factors, such as the voltage of the line, transmitting point so that essentially the characteristic
which affects its construction and its insulation level, the impedance of the line is presented to the-transmitter, the
type and the condition of the conductors and the insulat- loss in the line resulting from reflection at the discontinuity
ors, the presence or absence of ground wires, the method of may be considerable.
coupling used, weather conditions, and so forth. For this Thevenin’s theorem (see Chap. 10) suggests a general
reason the attenuation figures given in Table 4 are neces- method of calculating the loss due to any discontinuity,
either shunt or series, that exists in a carrier channel at a
TABLE ~-APPROXIMATE CARRIER ATTENUATION OF OVERHEAD
SERIES DlSCONTlNUllY SHUNT DISCONTINUITY
POWER CIRCUITS

Approximate Attenuation db per Mile


Line
Phase-to-PhaseCoupling Phase-to-GroundCoupling
Volta@ :-
kv 20 50 100 150 300
kc kc kc kc kc
.~- -~-
230 .03 .05 ,075 .107 .2 .04 ,062 ,094 .13 .25 Zd=Rd+jXd it,,‘&, +jx,,
138
115
,041
.05
,065
,075
.09
,102
.12
,135
,215
.27
.051 ,081
.062 ,094
,113
.130
.15
.16
.27
.34
\1Rd2+xdP
2C,

69
34.5
,055
,073
.08
.lO
.lI
.13
,145
.I8
.29
.38
.069 ,100
,094 ,125
,137 .I8
.22
.36
.47
t2=lot+Xd) ,~
13.8 .12 .15 .18 / .215( .45 1
.I5 1 .19 122
16 .27 .56
db = 20 log ,. ?!L
+
sarily only approximately correct. The figures for phase-
to-ground coupling are 1.25 times those given for inter- (2zc+Rd)‘+x,,’
phase coupling. On short lines (up to 50 miles) the attenu- db’20 loglo
2%
ation may be greater, and on long lines it may be less, but
the factor of 1.25 represents a good average. ‘The figure of Fig. 46-Derivation of equations
0.1 db per mile is frequently used for preliminary estimat- shunt discontinuities in a long line.
Chapter 12 Power-Line Carrier Application 427

point sufficiently remote from the transmitter. If the line trapped lines radiate from an intermediate point in a car-
were open circuited just ahead of the discontinuity, the rier channel, or from a receiving point, there is a loss due
voltage that would exist at the open circuited terminals to reflection as well as a loss due to division of the energy
lvould be twice the voltage that would exist across the line among the circuits. Treatment of this case as a shunt
if it were continuous; i.e., if there were no discontinuity. discontinuity, by methods previously outlined, yields the
I;urthermore, if the line were short circuited at the trans- results given in Table 6.
mitting point, the impedance seen looking into the open-
circuited terminals back toward the remote source would TABLE ~-LOSSES DUE To LONG BRANCH CIRCUITS REMOTE
FROM TRANSMITTING POINTS
l)e the characteristic impedance of the line. The system up
to the discontinuity can be represented therefore by a volt- 1 additional Circuit 3.5 db
age equal to twice the voltage that would exist with no dis- 2 additional Circuits 15.0db
continuity, in series with a resistance equal to the char- 3 additional Circuits 8.0 dh
acteristic impedance of the line. If the discontinuity is a N additional Circuits 20 log,, y db
series impedance, it is placed in series with the char- ( )
acteristic impedance of the line beyond the discontinuity.
lf it is a shunt discontinuity, it is placed across the char- Losses Due to Short Untrapped Branch Lines-
acteristic impedance of the line, and the combination is As contrasted with the long branch lines just considered,
applied to the terminals of the equivalent network. These short untrapped spur lines (in general, lines less than 50
connections are illustrated in Fig. 46. The resulting loss, miles in length) may present shunt impedances differing
which includes the loss due to reflection as well as that in radically from the characteristic impedance of the lme. If
the device causing the discontinuity, is then expressed for the terminating impedance and the length of a spur line
a series discontinuity as are known accurately, it is feasible to calculate the im-
pedance such a spur line presents at its input terminals at
,jb=20,oglot’!2z~+n~)z+~dz (16) a given frequency. This impedance can then be considered
22, as a shunt discontinuity and treated by the method previ-
and for a shunt discontinuity as ously given. Fig. 12 shows the absolute value of the input
impedance of a, typical line (Z,= 730 ohms, attenuation
WC+2Rd)2+-IXd2 0.186 db per wavelength) as a function of various capaci-
db = 20 log,, 07)
2dRd2+X,2 ’ tive reactance terminations.
In both of these equations Data on the carrier frequency impedance of power trans-
formers and other terminating devices are not generally
Rd= Resistive component of impedance of discon-
available, however, and it is not usually possible to calcu-
tinuity late the input impedance of a spur line. If after installa-
and Xd= Reactive component of impedance of discon-
tion of the equipment a carrier frequency cannot be chosen
tinuity. that will maximize the spur-line impedance, it may be
In the derivation of these equations it is assumed that the necessary to install line traps to isolate the spur line from
characteristic impedance of the line is the same on both the carrier channel. In this case the effect of the spur line
sides of the discontinuity. upon the attenuation is reduced to a low value, depending
Losses Due to Long Bratzch Circuits-When a upon the characteristics of the line trap.
carrier transmitter is coupled to a power system at a point Losses Due to Simultaneous Propagation Over
from which several long untrapped transmission lines radi- Alternate Paths-A carrier channel that includes two
ate, the load impedance presented to the carrier equipment alternate paths may suffer attenuation due to out-of-phase
is the parallel of the characteristic impedances of the lines arrival at a common point of signals traveling over the two
involved. The impedance matching transformer in the line paths. The magnitude of this attenuation is highly vari-
tuner can usually be adjusted so that this impedance is able, depending upon the nature of the two paths, their
transformed to load the transmitter properly, so that there relative individual attenuations, and the frequency used.
is no reflection loss. However, the division of the energy Limiting attenuation figures can be established, however,
for certain cases in which one or both of the alternate
TABLE ~--LOSSES DUE To LONG BRANCH CIRCUITS AT paths are long (over 50 miles).
TRANSMITTINGPOINTS
If both paths are long, there is a loss of 0.5 db at the
1 additional circuit 3.0 db branch point due to reflection. The relative amplitudes
2 additional circuits 4.8 db and the phase of the two signals arriving at the junction of
3 additional circuits 6.0 db the paths determines the additional attenuation. Specific
N additional circuits 10 log,0 (Nfl) db cases are as follows:
Equal Amplitudes, In-Phase Arrival-Reflection losses
among the several circuits in effect constitutes an attenua- of 0.5 db at junction and at branch point due to impedance
tion of energy along the desired path. If the characteristic mismatch. Total attenuation from branch point to junc-
impedances of all the lines involved are the same, the losses tion 1.0 db plus attenuation of one path.
at a transmitting terminal in this case are as shown in Equal Amplitudes, Out-of-Phase Arrival-Cancellation
Table 5. It should be noted that these losses are correct of voltage at junction, infinite attenuation. This is an
for a transmitting terminal only. If one or more long un- unlikely condition because two long alternate paths having
428 Power-Line Carrier Application Chapter 12

exactly the same attenuation are rarely encountered. The 47. Example of Calculation of the Total Attenua-
attenuation may still be large in practical cases, however, tion of a Typical Carrier Circuit
as pointed out below. The typical system of Fig. 48 will be used to illustrate
Unequal Amplitudes, In-Phase Arrival-Maximum loss the application of the principles just discussed in estimat-
at junction 3.5 db. Total maximum loss 3.5 db at branch ing the attenuation of a carrier channel. In this example
point due to reflection and division of energy, plus 3.5 db a 100 kc line-to-ground-coupled carrier channel is to be
maximum at junction, plus attenuation of shorter path. established between Stations A and C, and the losses are
These maximum losses are based on complete attenuation to be estimated for transmission in each direction.
of the signal in the longer path. At Station A there are three long circuits on the 13g-kv
Unequal Amplitudes, Out-of-Phase Arrival--Minimum bus in addition to the circuit over which carrier is to be
loss at junction 3.5 db, increasing with decreasing differ- transmitted. These cause a loss of 6 db because of division
of the energy among the total of four circuits (Table 5).
They also cause an additional coupling loss because the
coupling circuit is working into a load impedance lower
than normal line characteristic impedance. This additional
coupling loss is estimated at 1 db for each additional
circuit, or 3 db, plus the normal 1 db coupling loss.
All line losses are estimated from Table 4. -
‘The branch circuit loss at Station B is 6 db, as given by
Table 6, because this station is remote from the trans-
mitting point.
The by-pass loss at Station C is twice the loss of a ter-
minal coupling circuit, or 2 db, plus 0.5 db loss for 1000
feet of coaxial cable at 100 kc (Table 3).
The loss in the trap on the short line out of Station C
is approximately 0.5 db, as shown in Fig. 24 for a 400-
ampere trap terminated in zero impedance.
There is an alternate path between Station C and Sta-
tion D which has approximately 7 db greater attenuation
than the direct path. From Fig. 47 the maximum possible
loss, which would occur with out-of-phase arrival of the
signals at Station D, is estimated as 8.5 db. To this must
be added a loss of 3 db due to division of energy between
the alternate paths at Station C, plus a reflection loss of
0.5 db at this point, a total attenuation of 12.0 db due to
DIFFERENCE IN ATTENUATION OF PATHS,06 the presence of the alternate route. Thesz figures do not
Fig. 47-Loss due to out-of-phase arrival of signals at a
include the 5.5 db attenuation of the direct path, which is
junction of two long alternate paths. This curve gives loss at added separately.
the junction only and does not include the loss at the branch- The long line extending beyond Station D serves as a
ing point or the loss in the paths themselves. The junction is terminating impedance for the circuit. Most modern car-
assumed to be terminated by a single line which is a contin- rier transmitter-receiver assemblies present an impedance
uation of the channel.
of 5 to 10 times the load impedance into which they are
intended to work, and as a result they do not serve to
ence in attenuation of the two paths, as shown in Fig. 47. terminate a line in its characteristic impedance. If the line
To these losses must be added 0.5 db loss at the branch beyond Station D were not present, there would be a slight
point due to reflection and 3 db due to division of energy, gain in voltage received at Station D because of the high
plus the attenuation of the shorter path. terminating impedance.
If both paths are short and of unequal length, the atten- There is an estimated 1 db coupling loss for receiving at
uation may be very great, particularly if one of the paths Station D, plus 0.25 db coaxial cable loss. The total atten-
is a half wavelength longer than the other. uation of the channel for transmission from Station A to
In general, if the frequency cannot be adjusted after Station D is the sum of all the losses discussed. These are
installation to avoid out-of-phase arrival at a junction, it summarized and added in Fig. 48, giving a total attenua-
may be necessary to resort to the use of line traps to elim- tion of 52.2 db for the channel.
inate alternate paths. A long alternate path, when trapped For transmission from Station D to Station A, there is
at one end only, reduces to the case of a single long branch a 4.8 db loss at Station D due to division of energy among
circuit, for which the attenuation is 3.5 db. A short alter- the three lines on the bus, and an increase of 2 db in the
nate path may require trapping at both ends for reduction coupling loss. The additional loss due to the alternate path
of the attenuation to an acceptable value, because a trap in this case is 8.5 db at Station C. At Station A, one of the
installed at one end only may reduce the situation to that branch lines can be considered as a continuation of the
of a short untrapped spur line, for which the attenuation main line. The other two branch lines cause 6 db attenua?
may still be excessive. tion, partly due to reflection and partly due to division of
Chapter 12 Power-Line Carrier Application 429

LONG LINES
(OVER 50 MILES)
50 MI
66 KV
(OVER 50 MILES)

40 WI+-- LONG -LINE


66 KV

I STATION 0
STATION

(OVER 50 MILES)

CO-AXIAL CABLE
CO-AXIAL CABLE
CO-AXIAL CABLE

STATION A STATION D
SUMMARY OF LOSSES TO STATION D TO STATION A

1. CO-AXIAL CABLE LOSS AT STATION A 0.25 db 0.25 db


2. COUPLING LOSS AT STATION A I .o I .o
3. ADDITIONAL COUPLING LOSS CAUSED BY BRANCH CIRCUITS 3.0
4.BRANCH CIRCUIT LOSS AT STATION A 6.0 6.0
5.LOSS IN 50 MILE I36 KV LINE 5.7 5.7
6.BRANCH CIRCUIT LOSS AT STATION B 6.0 6.0
7. LOSS IN 75 MILE I36 KV LINE 6.5 6.5
6.BY-PASS LOSS AT STATION C 2.0 2.0
S.CO-AXIAL CABLE LOSS AT STATION C 0.5 0.5
IO.LOSS IN TRAP ON SHORT LINE AT STATION C 0.5 0.5
I l.LOSS DUE TO ALTERNATE PATH FROM STATION C TO
STATION D (MAXIMUM) 12.0 6.5
IL.LOSS IN 40 MILE 66 KV LINE 5.5 5.5
I3.COUPLING LOSS AT STATION D 1.0 3.0
14. BRANCH CIRCUIT LOSS AT STATION D 4.6
15. CO-AXIAL CABLE LOSS AT STATION D 0.25 0.25
TOTAL ATTENUATION 52.2 db 52.5 db

Fig. 48-Typical system assumed for example of calculation of losses, and summary of attenuation in each direction.

cncrgy. The coupling loss for receiving is estimated as 1 alternate paths, and other causes of high attenuation are
(11).All other losses in the channel are the same as for eliminated from the channel by means of line traps. A
transmission from Station A to Station D. The total atten- clean, well-trapped channel delivers a reliable signal at the
uation of the channel for transmission from D to A is receiving point on any carrier frequency that may be
therefore 52.5 db. available for use, regardless of system switching conditions.
As a result of the crowding of the carrier frequency
spectrum on most interconnected power systems in this
GENERAL CONSIDERATIONS IN APPLYING country, it is seldom that any appreciable latitude is avail-
J CARRIER SYSTEMS able in the choice of a frequency for a new channel. Where
a choice is available, however, it is sometimes possible to
48. Trapped Channels vs. Broadcast Systems install carrier equipment on a system with little or no
From the discussion just given of the sources of attenu- trapping and to experiment with different frequencies until
ation to carrier in a power system, it is evident that SUC- one is found which permits successful transmission between
‘_ cessful operation of a proposed carrier channel on a speci- the carrier terminals under all anticipated system switch-
ted frequency can be assured only if spur lines, short ing conditions. In this case the carrier energy is “broad-
1;
430 Power-Line Carrier Application

cast” throughout the polver system, and the signal deliv- TABLE ~-RATIO BETWEEN MINIMUM SIGNAL RESPONSE ;
ered to the intended receiving point is inherently weaker AND MAXIMUM INTERFERENCERESPONSEON CARRIER
RECEIVERSFOR VARIOUS APPLICATIONS ---
and less reliable than that deliver& over a clean channel.
-’
Frequently it is impossible to find on a complicated system tI<eycd tGtrrier
a frequency that permit,s sllccessful operation of a ‘(broad- Carrier Relaying or Tone *Voice
cast” type of channel. In this case it is necessary to seek Tele- Supervisory Telemetering Communicat,ion
out the sources of high attenuation and to isolate them one meterirlg Control
t)y one until a workable channel is obtained on an available
15 db 20 db 15 db 15 db
frequency. for ~1single minimum on
It is clear, therefore, that a trapped channel is preferable received tone, nutomatic simplex
to a broadcast type of channel from the standpoint of (15+20 log,0 N) db systems.
reliability, ease of application, improved signal-to-noise for multiple tones, 10 db
ratio, and reduced interference to neighboring systems. where N is the tolernble for
number of tones. short periods
49. Frequency Assignments and Separations on other systems.
One of the most important problems in the application 20 db good
of carrier equipment is the determination of the minimum 30 db excellent
frequency separation required between channels on the tReceiver
imum signal.
sensitivity set SO that receiver detector is barely saturated on min.

same system and the assignment of frequencies to new *Receiver sensitivity set YOthat minimum signal is ilt lower end of LLYC rongo,
On automatic simplex systems. no treater transfer unit r-f sensitivity should b
channels in a manner that permits maximum conservation usedthan that required to give reliable operation on minimum signn!.
of the available spectrum space.
In general, it is advisable to assign the lower frequencies non-operation of a receiving relay is the criterion of the
in the spectrum to long-haul communication and tele- effect of interference, it is necessary only to allow a reason-
metering channels, and to use the higher frequencies, which able margin of safety for relay drop-out in specifying the
are attenuated more rapidly, for short channels. Relaying maximum interference level. A 2 to 1 ratio is a reasonable
channels in particular are well suited to operation on the margin for telemetering purposes. If the telegraph receiver
higher frequencies because they are always trapped at both sensitivity is set so that the minimum espected value of
ends and extend over only one line section. There are the desired signal just causes saturation of the detector
cases of successful application of relaying systems on iden- plate current, the maximum response of the receiver to an
tical frequencies on well-separated line sections on the interfering signal should not exceed half the relay drop-out
same power system. current. In the usual saturated-detector type receiver,
The frequency separation required between carrier chan- this ratio is 12 to 15 db.
nels on a power system is a function of a number of factors, Although the same type of equipment is used for relaying
such as the selectivity of the receivers employed, the rela- purposes and frequently for supervisory control, the con-
tive strengths of desired signals and interfering signals at sequences of an incorrect relay operation;n these applica-
a receiving point, the type of modulation used, and the tions are more serious and hence an additional factor of
purposes for which the channels are applied. The last safety of 5 db has been allowed in Table 7 for these
factor determines approximately the signal-to-interference functions.
ratio that can be tolerated. For these reasons no generally In tone telegraph service, such as tone telemetering, the
applicable figures for required separations can be given and carrier signal is normally on continuously, and the receiver
each case must be considered individually. sensitivity setting is not so critical, provided that the re-
Other factors being equal, single sideband channels can ceiver operates on the flat portion of the avc (automatic
be spaced closer together in the spectrum than channels volume control) characteristic over the entire range of
using other types of modulation. This results primarily variation in signal strength. The maximum signal-to-
from the increased receiver selectivity permissible in the interference ratio that can be tolerated for a received car-
reception of single sideband signals. The narrow band- rier modulated 100 percent by a single tone is the same &9
width occupied by single sideband channels is also an that for keyed carrier reception, or 13 db, because the’ e
important factor in determining required frequencysepara- saturation characteristics of tone receivers are similar to’ f
tions between them and other types of channels, although those of saturated-detector carrier receivers. Additional 2.:
the selectivity of the receivers used in the other channels margin must be allowed for modulation by more than a:#
is the limiting factor in determining the permissible re- single tone, however, because the permissible percentage ..-:
duction of the separation in this case. of modulation by each tone is reduced as the number of
The signal-to-interference ratio acceptable in a given tones is increased. This is equivalent to a reduction of
type of service is to some estent a matter of opinion, and signal strength at the input of the tone receivers, and their
in addition it depends critically upon the adjustment of sensitivities must be increased accordingly. Hence a for-
the equipment in most applications. Hence it is difficult to mula which provides an allowance for additional tones is
set down specific figures for various cases. Discussion of a given in Table 7.
few of the considerations involved, however, will aid in It is difficult to give actual figures for voice communica-
establishing acceptable figures for a given application, and tion circuits, because there are widely different opinions M
Table 7 can be used as a guide. to what constitutes a “usable” channel or a “good” chmy
In telegraph-type channels, in which the operation or nel. Although it is possible to convey intelligence over a
Chapter 12 Power-Line Carrier Application 431

voice channel in lvhich the signal-to-interference ratio is any transmitter of the new channel nnd any receiver of the
nenrly unity, a ratio of 10 db is about the minimum that original chnnnel is 10 (II). Wh3t is the n~inin~un~ frequency
cirn be tolerated for any length of time. A 20-db ratio is separation required to give a 20 db signal-to-interference ratio
considered good and a 30-db ratio escellent by most users. in the original channel?
~1,~ Ilature of the interference also is a factor on communi- The signal to interference ratio at the input terminals
cLlti()n channels. For esample, the psychological effect of of the receiver is minus 30 db (10 db difference in trans-
s,,~!~~~~h interference of a given level is greater than that of mitter power and JO-db difference in attenuation). Thcre-
i,,tc~lfercnce of other types at the same level. fore 50 db of interference rejection is required for a 20-db
ln alltomatic simples channels, there must be adequate signal-to-interference ratio. According to Fig. 49, signals
,n:lrgin between the response of the receiver to the desired
signal and its response to the interfering signal when the
,l~zsi& signal is absent, to permit reliable operation of the
trLL~~sfcrunit. In such systems the receiver sensitivity
sl,o~~l~l1~ set so that desired signals just cause operation
,),, tllcx flat portion of the avc characteristic when allowance
is Ill;~tle for maximum attenuation. A minimum of 10 db
tli~f’~~~~c:nc~c between response to interference and response
I(, srlrtl signals should then be allowed. Because of residual
:1vc a&on, this requires about 15-db attenuation of the
illtcrference in typical receivers. Hence, automatic simplex
c;ll:mnels should not, be expected to operate reliably with
smaller signal-to-interference ratios than 15 db.
‘~‘llc first step in the process of estimating required fre-
(l~~enc’yseparation is to calculate the relative strengths of
tl~ desired and undesired signals at the receiving point or
poir~ts. This can be done by methods outlined in the sec-
\ions of this chapter devoted to estimating attenuation.
‘l’hc relative carrier powers of the signals at the receiver
WCthe original transmitter carrier outputs reduced by the
:tt,tcnrmtion of the respective paths of the signals to the
receiving point in question. This establishes a signal-to- I I I I\A/I I I I I 1
01 ’
interference ratio at the receiver input terminals. The 85 90 95 100 105 110 115
difference between this ratio and the required signal-to- FREQUENCY-KILOCYCLES
intcrfercnce ratio must be made up by the selectivity of Fig. 49-Typical a-m receiver selectivity curve.
I he rcc*eiver. The separation required for this purpose can
l)c tlt>tcrmined by reference to the selectivity curve of the at 108 kc and at 92 kc are attenuated by this amount when
rcxcc4vcrat the particular frequency in question. Consider- the receiver is tuned to 100 kc. Allowing 3 kilocycles for
:tIion must be given to the bandwidth of the interfering sideband components of the interfering signal, the mini-
sign:ll. This depends upon the type of service for which it mum separation of the carrier frequency of the new channel
is employed and the modulation system used. For ex- from that of the original channel is 11 kc above it or 11 kc
:unple, an interfering a-m voice communication signal below it. These are safe figures for either duplex or auto-
occupiesa bandwidth extending approximately 3 kilocycles matic simplex channels, provided that in the latter case
011each side of the carrier frequency and requires corre- the receiver sensitivity is adjusted properly. By a similar
sl)()ntlingly greater separation from the desired signal than process, the separation required to provide a 20-db signal-
:1 (‘arrier signal which is keyed for telemetering purposes to-interference ratio in the new channel can be estimated.
ml occupies a band of only a few cycIes on each side of the Either the figures so obtained or those previously calcu-
(‘:uGtr frequency. If the interfering channel is a single lated, whichever are the larger, determine the separation
si(lchand voice channel, its bandwidth extends three kilo- required to maintain a minimum of 20-db signal-to-inter-
Wles below the carrier frequency if the lower sideband is ference ratio in both channels.
I’sed, or three kilocycles above it if the upper sideband is
tr:insmitted. The suppression of the unused sideband can 50. Signal-to-Noise Ratio
‘R assumed to be a minimum of 20 db. Minimum tolerable signal-to-noise ratios for various
‘l’he following is an example of the use of the principles carrier applications parallel closely the values of minimum
“is~~~ctl in determining required frequency separation for signal-to-interference ratios given in Table 7, provided that
z1typical case: the proper characteristic of the noise (e.g. peak amplitude,
011;1 loo-kc voice communication channel having SO-db at- average amplitude, etc.) is considered in establishing these
telUtion under extreme conditions, transmitter carrier power ratios for each application. The receiver bandwidth also
is 25 Ivvatts and n receiver having the selectivity curve of Fig. must be considered in most applications, because noise
*9 is used: A new a-m voice channel is to he added to the response is usually a function of bandwidth.
‘ystem. The transmitters in the new system will have a cnr- In keyed-carrier telemetering applications, the average
rier output of 2.5 watts and the minimum attenuation between rectified noise output of the receiver is a measure of the
432 Power-Line Carrier Application

interfering properties of the noise. For impulsive inter- REFERENCES


ference with pulses separated sufficiently to prevent over- Carrier Equipment and Applications
lapping of the resulting wave trains, the nvernge output is 1. “hlodern Power-Line Carrier Equipment,” E. L. Harder,
independent of the receiver bandwidth, and hence band- Westinghouse ENGINEER, July 1944, pp 98-104.
lvitlth does not enter into the picture in such applications. 2. “Power-Line Carrier Communication,” R. C. Cheek, mesting-
The area of the impulses is the major determining factor. house ENGINEER, September, 1947, pp 151-154.
The same comments apply to carrier relaying, although 3. “The Applications of Power-Line Carrier,” R. C. Cheek, Power
in this case trouble from noise is not likely to be encoun- Plan/ Engineering, Nov. 1945, pp 76-81.
tered. Because of the limited extent of carrier relaying 4. “A Versatile Power-Line Carrier System,” H. W. Lensner and
channels, and the fact that they are always trapped at both J. B. Singel, AZEE Tmnsaclioxs, Vol. 63, 1944.
ends, signal-to-average-noise ratios at receiving points are 5. “A Simple Single-Sideband Carrier System,” R. C. Cheek,
IVeslinghouse ENGINEER, Sovember 1945, pp 179-153.
practically always far above the 20-db minimum. -1 pos-
6. “A New Single-Sideband Carrier System for Power Lines,” B. E.
sible esception is the case of three-terminal lines in which Lenehan, AIEE Transactions, Vol. 66, November 1947.
one leg of the circuit is approximately an odd number of 7. “The Combination of Supervisory Control with Other Functions
quarter wavelengths at the frequency used. on Power-Line Carrier Channels,” R. C. Cheek, W. A. Derr,
For supervisory control by keyed carrier, the 20-db ratio AIEE Z’ransactions, Vol. 64, May, 1945, pp 241-246.
given by Table 7 should be maintained between minimum 8. “Power-Line Carrier,” F. S. Mnbry, Inrlustrial Electronics Refer-
signal and average noise. ence Book, Chapter 25, pp 442-456, dohn Wiley & Sons, New
In tone telegraphic functions (e.g. telemetering) the nar- York, 1948.
row bandwidth of the tone receivers reduces their response Modulation Systems
to random noise to negligible amounts. In addition to this 9. “Frequency Modulation for Power-Line Carrier Current,” E. W.
factor, the wave trains resulting from impulsive noise with Kenefake, AZEE Transaclions, Vol. 62, 1943, pp 616-620.
GO-or 120-cycle pulse-frequency overlap to a considerable 10. “A Comparison of the Amplitude Modulation, Frequency
estent in tone receivers of the usual narrow bandwidth. filodulation, and Single Sideband Systems for Power-Line Car-
Under these conditions the average rectified noise output rier Transmission.” R. C. Cheek, AIEE Transactions, Vol. 64,
is less than that obtained with broadly tuned circuits. The May 1945, pp 215-220.
actual reduction is a function of the bandwidth of the tone 11. “Power-Line Carrier Modulation Systems,” R. C. Cheek, We&
receivers, which in turn is usually a function of the tone inghouse ENGINEER, March 1945, pp 41-45.
frequency itself. However, the formula given in Table 7 can Transmission Theory and Carrier Channel Application
be used as a guide to the maximum permissible signal-t,o- 12. Communication Engineting (book), W. L. Everitt, McGraw-
noise ratio, and the additional noise reduction due to over- Hill Book Co., New York, 1937.
lapping of the wave trains can be taken as a safety factor. 13. Electrical Transmission of Power and Signals (book), Edward
In carrier communication applications, the type of sys- W. Kimbark, John Wiley & Sons, New York, 1949.
tem used determines which noise characteristic is most 14. “Propagation d’ondes haute frequence le long d’une ligne
important. In automatic simplex systems, operation of triphasee symetrique,” A. Chevallier, Rev. Gen de I’Electricite,
the transfer unit occurs when the peak value of the noise Vol. LIV, January 1945.
15. “Application of Carrier to Power Lines,” 5 M. Rives, AZEE
equals the r-f sensitivity setting of the unit. Although
‘l’ransactions, Vol. 62, 1943, pp 835-844.
momentary operation of the transfer unit on extremely 16. “Power-Line Carrier Channels,” M. J. Brown, AIEE Trunsuc-
high isolated peaks occurring not oftener than once or lions, Vol. 64, May 1945, pp 246-250.
twice a minute should not be objectionable, the signal-to- 17. “Operation of Power-Line Carrier Channels,” H. W. Lensner,
peak-noise ratio for noise peaks occurring more frequently AIEE Transactions, Vol. 66, November, 1947.
should not exceed the 15 db shown in Table 7.
Noise and Noise Measurement
Quasi-peak noise levels are representative of the inter-
fering effects of noise in duplex and manual simplex carrier 18. Survey of Existing Information and Data on Radio Noise Over
the Frequency Range l-30 MC/S. H. A. Thomas, R. E. Burgess,
communication channels. The figures of Table 7 can there-
Special Report No. 15, Radio Research, Department of Scientific
fore be used as the maximum permissible signal-to-quasi-
and Industrial Research, National Physical Laboratory, Lon-
peak noise ratios in these systems for various grades don, 1947.
of service. 19. “Selective Circuits and Static Interference,” Bell System Tech- ,
Because it is not ordinarily possible to reduce apprecia- nical Journal, Vol. 4, 1925, pp 265-279.
bly the noise level present at a given receiving point in a 20. “Frequency-Modulation Noise Characteristics,” M. G. Crosby,
carrier system, the only practical way to improve signal- Proceedings IRE, Vol. 25, 1937, pp 472-514.
to-noise ratio is to raise the signal level at the receiving 21. “An Experimental Investigation of the Characteristics of Cer-
point. It is not usually feasible to raise signal levels by tain Types of Noise,” K. G. Jansky, Proceedings IRE, Vol. 27,
increasing the transmitted power, because appreciable 1939, pp 763-768. ,.
22. “A Study of the Characteristics of Noise,” V. D. Landon, Pro- 4
gains in terms of decibels require inordinately large in- 1
ceedings IRE, Vol. 24, 1936, pp 1514-1521. %
creases in power. For example, to raise the signal level 23. “Methods of Measuring Radio Noise,” Joint Committee on ,.,,:i
from a IO-watt transmitter by 20 db requires an increase Radio Reception of EEI, NEMA, and RMA, EEI Publication &
to 1000 watts, or 100 times the original power. A much G9, NEMA Publication No. 107, February 1940.
more practical solution is to reduce the channel attenuation 24. “Proposed American Standard Specification for a Radio Noise
by judicious application of line traps to eliminate short Meterd.15 to 25 MC/S.” ASA Sectional Committee on Radio-
taps or spur lines and alternate paths. Electrical Coordination, ASA C 63.2-1949.
CHAPTER 13

POWER-SYSTEM STABILITY
BASIC ELEMENTS OF THEORY AND APPLICATION
Original Authors.. Revised by:
R. D. Evans and H. N. Muller, Jr.* J. E. Barkle, Jr. and R. L. Tremaine

T
HIS chapter presents a general introduction to the machines, particularly with certain systems connected
power-system stability problem including definitions through high-reactance tic lines, that it was difficult to
of basic terms, useful physical and analytical con- maintain synchronism under normal conditions and that
ccpts, methods of calculation of steady-state and transient the systems had to be separat,ed in the event of faults or
stability problems for simplified systems, and the extcn- loss of excitation. Various emergency conditions occa-
sions necessary for the application of these principles to sionally made it necessary to operate machines and lines
practical systems. Short-cut methods for estimating per- at the highest practicable load; under these conditions
missible transmission-line loading, and the transient sta- stability limits were found by experience. Subsequently, it
bility performance of common systems are presented. became apparent that many of the interruptions to service
Means of improving system stability are discussed. Ex- were the result of disturbances that caused loss of syn-
amples of steady-state and transient stability calculations chronism between various machines and that, by modify-
appear throughout the chapter. ing the system design, layout, or operation, it was possible
On commercial power systems, the larger machines are to provide a better standard of service.
of the synchronous type; these include substantially all of The early analytical work on system stability was di-
the generators and condensers, and a considerable part of rected to the determination of the power limits of syn-
the motors. On such systems it is necessary to maintain chronous machines under two conditions: first, the pull-out
synchronism between the synchronous machines under of a synchronous motor or generator from an infinite bus;
steady-load conditions. Also, in the event of transient and second, the pull-out or stability limit for two identical
disturbances it is necessary to maintain synchronism, machines, one acting as a generator and the other acting as
otherwise a standard of service satisfactory to the user will a motor. However, the principal developments in system
not be obtained. These transient disturbances can be pro- stability did not come about as an estension of synchro-
duced by load changes, switching operations, and, particu- nous-machine theory, but as the result of the study of long-
larly, faults and loss of excitation. Thus, maintenance of distance transmission systems.
synchronism during steady-state conditions and regaining The modern view of the stability problem dates from the
of synchronism or equilibrium after a disturbance are of 1924 Winter Convention of the American Institute of
prime importance to the electrical utilities. Electrical Electrical Engineers when a group of papers? called atten-
manufacturers are likewise concerned because stability tion to the importance of the problem and presented the
considerations determine many special features of appara- results of the first laboratory tests* on miniature systems
tus and under many conditions importantly affect their proportioned to simulate a power system having a long
cost and performance. The characteristics of virtually transmission line. Another important step was taken in
every element of the system have an effect on stability. It 1925 when the first field tests 4~5on stability were made on
introduces important problems in the coordination of elec- the system of the Pacific Gas and Electric Company.
trical apparatus and lines in order to provide, at lowest Much additional practical information9 on the problem
cost, a system capable of carrying the desired loads and of was obtained by transient recording apparatus, first in-
maintaining a satisfactory standard of service, both for stalled on the system of the Southern California Edison
steady-state conditions and at times of disturbances. Company. Initially the studies of the problem were re-
The problem of system stability had its beginning when stricted principally to the determination of whether cer-
synchronous machines were first operated in parallel or in tain layouts, proposed for the longer transmission projects,
synchronism. It was early recognized that the amount of were actually capable of transmitting the desired amount
power that can be transferred from one synchronous of power under steady-state conditions. Subsequently, it
machine to another is limited. This amount of load is was found that the more important phase of the problem
known as the stability limit, and when it is exceeded, the was in the determination of system layouts and loads that
machine acting as a generator ‘(over speeds” and the would insure satisfactory operating characteristics at times
machine acting as a motor “stalls.” of various transient disturbances arising from load changes,
As power systems developed, it was found with certain switching operations, and circuit faults with their subse-
*H. N. Muller, Jr. was the original author of “System Stability- quent isolation. During the ten-year period from 1924 to
Examplesof Calculation,” which has been included in Chapter 13 in 1933, the theory of system stability was carefully investi-
this revision. tAIEE Transactions, vol. 43, pp. 16-103, 1924.
433
434 Power-System Stahility Basic Elements of Theory and Application Chapter 13

gnted. During this work there were proposed many new +O LAGGING
methods of improving t,he stability of systems as dis- REACTIVE POWER
CIIPSC~in t,he latter part of this chapter. Since that time
considcrnble esperience has been obtained with methods
of analyzing stability and with new methods of improving
stability, \vith the result that the subject is now considered
to lx: on :I basis that is satisfactory from the standpoint of SUPPLY
t,lwory ant1 plwticc. CIRCLE
CENTER
-2
ES
087

ACTIVE PO WER

I. BASIC CONCEPTS OF STABILITY


1. Essential Factors in the Stability Problem RECEIVER
CIRCLE
Tlic: essential factors in t,he stnhility problem are illus- CENTER
trated in connection with the two-machine system shown
srhem~ticdly in Fig. 1. The various elements cf the sys-

INERTIA INERTIA

INTERNAL VOLTAGE

-Q LEADING
REACTANCE REACTIVE POWER

Fig. 2-Elementary power-circle diagram for line reactance X,


voltages E. and E,, system of Fig. 1.
Fig. l-Basic diagram for the two-machine stability problem.

PM-Prime mover. 2. Power-Circle Diagrams and Power-Angle Dia-


G-Synchronous generator. grams
S-Rcactancc lint. The performance charact,eristics of the simple tn-o-
-If--Synchronous motor. machine power-transmission system, Fig. 1, are readily
SI,--Sh:~ft> lo:d. shown by power-circle diagrams and powwangle diagrams
as given in Figs. 2 and 3 respectively. The riiagrnms are
tern, prime mover, synchronous generator, reactance line, based on methods described in Chap. 9 nncr are reducible
synchronous motor, and the shaft load, are indicated. to the simple form shown because they depend, in t’he
There are seven essential factors affecting stability. These absence of loss, merely upon the four factors E,, E,,, 0 and
are of two kinds, mechanical and electrical. The essential Y. The equation relating power transfer in a three-phase
mechanical factors are: system is as follows:
--
1. Prime-mover input torque. PsE*sin fl
2. Inertia of prime mover and generator. (1)
x
3. Inertia of motor rind shaft load.
4. Shaft-loatl output torque.

The essential electrical factors are:


1. Internal voltage of synchronous generator.
2. Reactance of the system including:
a. Generntol
b. Line
c. Xotor.
3. Internal voltage of synchronous motor.

In the foregoing discussion, losses have been ignored and


this is permissible since losses do not affect the phenomena
except to introduce damping for which allowance can easily 0
e; 8’ 0; 90” 0; 8” e; 180’
be made after the character of the system oscillations is
ANGLE 8
understood. To introduce damping at the outset would
obscure the character of the essential phenomena i&olved. Fig. 3-Elementary power-angle diagram, system of Fig. 1.
;: .t : 2’1 (.’ ,:
Chapter 13 Power-System Stability Basic Elements of Theory and Application 435

where: A power-transmission system operating under specified


circuit and transmitted load conditions is said to he st:&le if,
-/‘= three-phase power transferred in watts. when displaced from these conditions by any small zrbitrnry
EE = internal voltage of generator (line-to-line volts). forces, the system upon removal of these forces develops re-
E,,, = internal voltage of motor (line-to-line volts). storing forces tending to return it to the origin4 conditions.
S = reactance betwtcn generator and motor internal
voltages, ohms per phase. The arbitrary displacement can be made in several ways,
O=nngle by which the internal voltage of generator the most convenient of which is a small arbitrary increase
leads the internal voltage of motor. in the angular displacement.

When per-unit vnllles of voltages and reactance are used 4. Application of the Criterion of Stability
in Eq. (l), the power transferred is obtained as a per-unit The application of the definition of stability and the
cluantity referring to the kva base being used. Thus, the criterion of stability will now be considered in connection
three-phase power flow in kilowatts would be the per-unit -: with the system of Fig. 1. Examination of Figs. 2 and 3
value multiplied by the kva base. shows that solutions are obtained for the points corre-
sponding to the power I” at the angle 0’ nnb also to the
3. Meaning of Stability Terms . power P” at the angle 0”. In the absence of loss, the
The t,erms “stabilit,y” and ‘<maintenance of synchro- amounts of sending and receiving power are equal and P’
nism” arc quite frequently used interchangeably. How- .: and P” are equal.
cvcr, a system consisting of a synchronous generator, a In applyink the criterion of stability, the system is as-
rcnct,ance line, and an intluct,ion motor ,-.may become un- sumed to be subjected to a slight arbitrary reduction in
stable but cannot lose synchronism. Nevertheless: system c angle between +@rnal voRZ@5~~ from- 0’ to 0,’ in Fig. 3,
stability is, ordinarily, of importance only when it denls.~ a& the power transferred from the generator to the motor
--.
with the conditions of stable operation between synchro- 1s corres@iiditiglly reduced from P’ to PI’. The input and
nous machines. The problem is of importance, primarily output torques, Fig. 1, remain constant and are equal to
from the standpoint of the masimum amount of power each other and to P in Fig. 3 since the system is assumed
that can be transmitted without instability being incurred to have no loss. The prime-mover input power P is now
rmder steady-state conditions or as a result of circuit greater than the electrical output power PI’, resulting in
changes or faults. The terms “stability” and “power limit” acceleration of the generator rotor which tends to increase
are also frequently used interchangeably. However, a the angle between the sending and receiving ends of the
simple system consisting of a generator, a reactance line, system. At the receiving end, the electrical input to the
and a resistance load has a definite power limit without motor PI’ is now less than its mechanical output P and
having a stability limit. this difference in power decelerates the motor, which also
Stability can be formally defined as follows: tends to increase the angle between the sending and receiv-
Stability when used with reference to a power system, is ing ends. Thus the arbitrary reduction of the angle be-
th:Lt attribute of the system, or part of the system, which tween the internal voltages of the generator and motor
en:lhlcs it to develop restoring forces between the elements from 0’ to 01’ reduced the electrical power transferred
thereof, equal to or greater than the disturbing forces so as through the system and resulted in the development of
to restore n state of equilibrium between the elements.* restoring forces tending to increase the angle between the
Stability applies to both steady-state and transient con- internal voltages and return the system to the original
ditions on a power system. The distinction between them angle 0’. Since losses have been omitted, the angle between
tlepends upon whether the stability applies to a condition the internal voltages would oscillate about the value O’,
t,hat includes a transient disturbance. Certain automatic but in a practical system where losses are always present,
devices, such as voltage regulators, have a bearing on the this oscillation would be damped and the system would
stability conditions. If such devices are used this fact eventually return to the original angle.
should be indicated as follows: steady-state stability with Next, assume that the system is subjected to a slight
automatic devices. arl%%iy movement increasing the angle from 0’ to 8,‘.
Stability limit for a system with synchronous machines Under this condition the output of the generator P2’ is
can be considered the same as the power limit, and is @eater than its input, which corresponds to I’. The dif-
defined as: ference in input and output decelerates the generator and
thus tends to reduce the angle between the sending and
A Stability Limit is the maximum power flow possible receiving ends. Similarly, since losses are neglected, the
through some point in the svstem when the entire system or
the part of the system to which the stability limit refers is op- input to the motor is greater than its shaft load with the
erating with stability.* result that the motor accelerates and thus tends also to
reduce the angle between the sending and receiving ends.
Criterion of Stability-There are several criteria for The arbitrary displacement of the system, by a small
the determination of the conditions establishing stability amount from the solution at the angle 0’ in such a direction
that are needed in connection with the analysis of as to increase the angle, creates restoring forces to return
complicated systems. These criteria can be stated as the system to the original operating point.
follows: It has been shown that if the system operating at the
*American Standard Definitions of Electrical Terms, MA-C42- angle 0’ is subjected to small disturbing forces, then regard-
1941. less of the direction of the small disturbing forces, when
436 Power-System Stability Basic Elements of Theory and Application Chapter 13

these forces are removed the system develops restoring which gives the maximum power in watts when the volt-
forces in such a direction as to return the system to the ages are expressed as line-to-line volts and the reactance
original angle between the internal voltages of the gener- as ohms per phase, or the masimum power in per unit
ator and motor. Therefore, the mathematical solution when per-unit voltage and reactance are used. If the cri-
corresponding to the power P’ and the angle 8’ constitutes terion of stability is applied, (1) for all load conditions
3 stable operating point, since any tendency for the system with the power and angle less than those corresponding to
to drift away from the operating point 0’ devclopes acle- the SO-degree limit, the system Gil be inherently stable; ’
quntc restoring forces. whereas (2) for all loads at angles greater than 90 degrees
Critical Point in System Oscillation-Consider nest the system will be unstable. The 90-degree loacl point for
the operation at the point defined by the angle 0” and the a system without loss is the critical load or the maximum
power P”. Assume the condition with the angle 6” in- value of all steady-state operating points that are inher-
creased to 02”. Under this condition tha output of the ently stable.
generator and input of the motor are decreased to P?“, so There is a single steady-state stability limit for specified
that the output of the gene&or is less than its input, and circuit, impedance, and internal voltage conditions, It
the input, of the motor is less than its orltput or shaft load. follow, therefore, that if the ercitation of either or both
Thaw circumstances prodlIce forces that accelerate the machines is changed so as not to correspond to the internal 1,
generator and decelerate t,he motor, and increase further voltages assumed, the stabilit,y limit will be correspond-
the angle by which the gcnerntor lentls the motor. The ingly changed. Loss of field results, of course, in reducing
changes in force are such as to augment the change in the synchronizing po\ver to zero. Y’l’e_ma@n~. that loses
angle with the result that the system pulls out of step, that its excitation pulls out of synchronism with the ot%z@Z
: .-------. -
is, the system becomes unstable. Apply next this same c&G& n&lines and operates as an i$dti&on m%chme.
criterion for the condition of a slight reduction in the angle Whether the system is stable or unstable :g.cornbinati&
below 0”. For 0,” the electrical output of the generator is of synchronous and induction machines is determined in
greater than its mechanical input and the electrical input part by the characteristics of the induction machines.
to the motor is greater than its mechanical output or shaft
load. The change in the angle between internal voltages 6. Transient-Stability Limit
in the system slows down the generator and speeds up the Transient stability refers to the amount of power that
motor. Both of these changes cause the system to reduce can be transmitted with stability when the system is sub-
still further the angle between the internal voltages. Thus jected to an “aperiodic disturbance.” By aperiodic disturb-
the solution corresponding to the angle 0” and the power ance is meant one that does not come with regularity and
P” is said to bc an unstable solution since a slight depar- only after intervals such that the system reaches a condi-
ture from that point sets up forces to augment the change tion of equilibrium between disturbances. The three prin-
in that same direction instead of restoring the condition to cipal types of transient disturbances that receive consider-
the original point of solution. However, in the case of ation in stability studies, in order of increasing importance,
movement back from the point corresponding to the angle are :
t?“, the system further reduces the angle and moves in the
1. Load increases.
direction of the stable operating point at 0’. The system
will develop forces causing it to move in the direction of 0’ 2. Switching operations.
for all angles between 0” and 8’. 3. Faults with subsequent circuit isolation.
Thus the point corresponding to the angle 0” is the The basic power-angle diagrams give an adequate picture
crSiZi1 j&&t i% Gjiteti oscillation for given internal volt- of the stability phenomena encountered in each of these
ages, reactance, and power-flow conditions. If the system disturbances.
has a stable solution at B’, it can withstand system dis- Load Increases can result in transient disturbances
turbance that causes it to oscillate on either side of this that are important from the stability standpoint if (1) the
angle up to 8”. If-. that
.;
angle is exceeded, the system will total load exceeds the steady-state stability limit for spe-
lose synchronism. If that angle is not reached, the system
will oscillate about 0’ and because of losses it will come
into equilibrium at that angle.
5. Steady-State Stability Limit
For the simple two-machine transmission system illus-
trated in Fig. 1, the steady-state stability limit is given by
the maximum power obtained from either the power-circle
diagram or the power-angle diagram of Figs. 2 and 3. The
steady-state stability limit of a system without loss occurs
at the angle of 90 degrees between sending and receiving
ends as shown by these diagrams or as readily obtained
from Eq. (1). The steady-state limit for a three-phase
system is given by Z=Z=; ANGLE 0
(2) Fig. 4-Power-angle diagram for analyzing load increases. .a
Chapter 13 Power-System Stability Basic Elements of Theory and Application 437

cific voltage and circuit reactance conditions, or (2) if the for switching operations can be investigated in a similar
load increase sets up an oscillut,ion that causes the system manner using the equal-area criteria3 that have been sp-
to swing beyond the crilicnl point from which recovery plied for the determination of the transient limit for load
\voultl be impossible, as pointed out previously. Consider increases. In the case of switching operations there are,
a system operating under the conditions shown in Fig. 4 however, two power-angle diagrams that require consider-
,\.ith the load P1 at the angle & and the prime-mover input ation: (1) the power-angle diagram for the initial condition,
:mtl shaft outpllt nbr~lptly increased to P,. Because of the (2) the power-angle diagram for the final condition,
inertia of the rot,nt,ing mschincs, the internal voltages of that is, the condition after the switching operation has
the gcnerntor and motor do not immediately swing to 0?, taken place. Figure 6 (a) indicates a system with two lines
\vhich would permit t,rnnsfcr of power Ps. Instead, the initially in service; Fig. G (b) shows two power-angle dia-
initial differences of power input and output are used in grams, Curve I applying to the initial circuit-condition
:~~~celt:ratingthe generator and in decelerating the motor and Curve II applying to final circuit-condition. The
rottating elements. Both of these changes cause the rotors diagram shows the transmitted power P, the initial opcrat-
t,o tlcpurt from synchronous speed and to increase th& ing condition at the angle 6 and the power PI, and the
angular differences. Thus when the system reaches &, the final operating condition at & and P2. The moment the
gcncrntor is trnvcling above synchronous speed and the switching operation takes place the electrical output is
motor below synchronous speed. The difference in the reduced from PI to Z”. This change produces an increment
st,ored energy cannot instantly be absorbed and as a result power of magnitude (P-P’), which is available for ac-
the system overshoots 02 and reaches some larger angle celerating the generator and decelerating the motor, both
as &, such that the shaded area cde is equal to t!he area ubc. changes tending to increase the angle between the sending
Seglecting losses, these two areas can be taken as equals. and receiving machines. Thus, the two machines depart
Thr: oscillation will not exceed the angle 03, and because
of losses in an actual system, equilibrium will ultimately be
reached at B2. In the case illustrated in Fig. d the system Xf
oscillates to the angle 03, which is greater than 90 degrees UEr
but is stable because enis less than 0+ the critical angle for -/u-..
the load Ps. With a somewhat larger total load or with a F
greater increment of load, the maximum point reached in (a) EQUIVALENT CIRCUIT
Ihe oscillation would be greater than 03 shown in the dia-
gram. With increasingly severe conditions, a point is
reached where the critical angle is equaled and this repre-
sents the transient limit for the load increase. The amount
of load increase that a system can withstand depends upon
t,he steady-state limit of the system and the initial operat-
ing angle. Figure 5 shows the total permissible sudden
increase in amount of power that can be absorbed with
stability, espresscd as a percentage of the steady-state
stability limit of a system without loss and plotted as a
function of the angle between internal voltages.
Switching Operations-The transient-stability limits

+ 100 ANGLE 9
5 lb) POWER-ANGLE DIAGRAM
i
Fig. 6-Power-angle diagram for analyzing transients due to
switching operations.

from synchronous speed, accelerating and decelerating


forces increasing the angle from B1 to &. At this point
the generator rotor is traveling above synchronous speed
and the motor rotor below synchronous speed with the
result that both rotors tend to overshoot t& and to reach &,
such that the area abc is equal to the area cde. At 03, the
energy stored above and below synchronous speed has been
absorbed and since the instantaneous power output of the
ge,nerator and input of the motor are greater than the
prime-mover input and shaft loads, respectively, restoring
z
forces are developed that cause the system to oscillate
g
0.0 about & and reach a condition of equilibrium because of
0 20 40 60 00
losses in a practical system.
INITIAL ANGLE -DEGREES
The amount of power transferable without loss of syn-
Fig. 5-Permissible load increase vs. initial-angle curve. chronism depends upon (1) the steady-state stability limit
438 Power-System Stability Basic Elements of Theory and Application Chapter 13

for the condition after the switching operation takes place from P to P’, the difference in power (P-P’) heing ab-
and upon (2) the difference betn-een initial and final stendy- sorbed in accelerating the generator and decelerating the
state operating angles. The stability limits for switching motor. For the severe type of fault shown, the system
operationsare lower for the larger amount of the final circuit would pull out of step if the fault were not promptly
reactance and for the greater percentage change in the cleared. Assume, however, that the fault is cleared by
circuit reactance. the time the system swings to 0%. At this point, transfer is
Faults and Subsequent Circuit Isolations--The made to the final circuit condition, Curve III. The power-
t,hird and most important type of transient disturbance angle diagram shows that the power out,put of the gencr-
arises from npplicat,ion of faults and the subsequent circuit ator esceeds the input, with the result that the generator
changes required to isolate the fault. For such disturh- rotor is decelerated and that the motor is accelerated.
antes three or more circuit conditions require considera- However, because of the energy stored in the machine
tion: (1) the initial condition, immediately prior to the rotors above and below synchronous speed the system
fault, (2) the condition during tiw fault, and (3) the condi- continues to swing to some larger angle, such as On’, so
tion subsequent to the isolation of the fault. Additional that the area defyis equal to the area nbcd. Thus, OR’is the
conditions are required to cover the cases in which the fault maximum point reached in the system oscillation using
is isolated in two or more steps, such as would be produced the same equal-area criteria discussed in connection with
by the disconnection of a line section by sequent,ial swilch- ot,her types of transient disturbances. The system oscil-
ing. hdditional steps would be required to take care of lates about the angle O3and because of losses will ultimately
the case of a high-speed reclosing breaker, which first dis- come to equilibrium at that an&
connects a faulted line and suppresses the arc, and sub- If the severity of the fault is increased, as indicated by
sequently restores the line to the original circuit connec- the reduction in amount of power that can be transmitted
tion. However, the procedure to be followed in the more during the fault condition, or if the duration of the fault is
complicated cases will become evident from consideration increased as indicated by a larger 02, or if the power-angle
of the simpler case. diagram for the final condition has a lower maximum, the
Consider a transmission system similar to Fig. 6 (a) but largest angle during the system oscillation is increased
with one line subjected to a fault at an intermediate point. beyond 03’ and under some conditions would reach the
The power-angle diagram for the case with the two lines critical an& O4for the transmitted power under the final
in service is indicated in Fig. 7 by the Curve I, which circuit condition. When this condition is met the transient-
stability limit for the condition is said to be reached.
The nature of transient disturbances incident to faults
can be examined further in connection with t’he use of
quick-reclosing breakers as illustrated in Fig. 8. Two cases
are considered, namely, a single-circuit ~5s~ shoxn in (a)
and a double-circuit case shown in (b). In hot,h cases, the
faulted line is de-energized to suppress the arc in the fault
and reclosed after an interval for the purpose of insuring
stability. These switching operations provide a succession
of power-circuit conditions and a corresponding set of
power-angle diagrams as can be seen by a detailed esnm-
01 w32 e; 84 180’ ination of Fig. 8. The conditions necessary for maintaining
stability are also stated in terms of the stored-energy
ANGLE 8 relations as shown by corresponding areas on the power-
Fig. 7-Power-angle diagram for analyzing transient disturb- angle diagram.
ances due to faults with subsequent circuit isolation. See No method has been given for the determination of the
Fig. 6 (a). angles, 8, in Fig. 7, or & and 03 in Figs. 8 (a) and (b),
which define the condition for which the fault is removed
intercepts the line of transmitted power at the angle 81and or the circuit switched. From a practical standpoint the
the power PI. Upon application of the fault the amount of circuit change is not made in accordance wit,h the angular
power transferable from one end to the other is reduced. difference between the sending and receiving ends; instead
If t,he fault were a zero-impedance fault on all lines the it is made as a function of time measured from fault appli-
polver transmitted would be reduced to zero. However, if, cation, the duration being that required for the operation
as is usually the case, the fault is not a zero-impedance of protective relays and circuit breakers. This time can
fault on all lines, some power can be transmitted from the be calculated by a step-by-step process to determine the
sending to the receiving ends. This case is assumed in the changes in accelerating force, the changes in velocity, and
diagram of Fig. 7 and is indicated by the Curve II passing the changes in angles. Thus, the determination of the
through the points b and c. The power-angle diagram for angle-time relations constitutes one of the important steps
the final condition with the faulted line switched out of in transient-stability calcu!ations and will receive consider-
service is shown by the Curve III that passes through the able attention in subsequent sections.
line of transmitted power at the angle & and the power Pa. For a power system with machines of assumed constant
Upon application of the fault, the power output of the internal voltages, with circuits of assumed reactances, and
generator and the power input to the motor are reduced with losses neglected, there is only one steady-state limit.
Chapter 13 Pour-Syste’m Stability Basic Elenlents of Thor?! and Application

F= FAULT APPLIED
C= FAULT CLEARED
= RECLOSURE

180.
ANGLE 8
(a) SINGLE-CIRCUIT CASE

Fig. 9-The mechanical model (set up for a system with two


F= FAULT APPLIED generators and an intermediate synchronous condenser).
C= FAULT CLEARED
operating angle. The transient limit for the simplest con-
R = RECLOSURE
dition involving a fault on a system with subsequent circuit
isolation depends upon the initial operating angle, the
severity of the fault and its duration, and the stability limit
for the system after the fault is cleared. It becomesnecessary,
therefore, when givinga transient-stability limit of a system
to define the conditions under which the limit applies.
7. The Mechanical Analogy of a Power-Transmis-
sion System
The definitions of stability given in Sec. 3 and the sub-
\’
sequent discussions have been given in terms of equilib-
rium of the power-transmission system. Equilibrium phe-
nomena are ordinarily visualized in terms of a static system
ANGLE 0
in mechanics. However, the discussion of the familiar
lb) TWO-CIRCUIT CASE static systems cannot directly be applied to the compli-
Fig. S-Power-angle diagram for reclosure. cated electro-mechanical system employed in power trans-
(+-Single-circuit cnse mission. Furthermore, the actual system involves dynamic
Curve I for normal circuit rather than static equilibrium. To circumvent this diffi-
Curve II for fault condition (21-G) culty a mechanical analogy, which has properties corre-
For stability, areas (1 plus 2) 5 area 3 sponding to the actual dynamic electro-mechanical system,
(b)--Two-circuit cake has been devised.
Curve I for two lines (normal) The most convenient means of visualizing the basic phe-
Curve II for one line (normal) nomena of a power-transmission system is the mechanical
Curve III for fault (2L--G) analogy developed by S. B. Griscom6 and shown in Figs. 9
For stability, area 1 s areas (2 plus 3)
and 10. The mechanical analogy or mechanical model, as
the device is more commonly called, consists essentially of
However, for the transient-stability calculations there are two rotatable units mounted on a common shaft and pro-
many conditions depending upon the character of the vided with lever arms, lvhich are connected at their outer
transient under consideration. For example, for load in- ends by a spring. One of these rotatable elements is desig-
creases, the transient-stability limit depends upon the nated as the generator element and the other as the motor
initial load and the increment of load. For the switching element. Each of these elements is provided with means
.operation,
. the transient limit depends upon the stability for applying
. 1.torque in such a way as to stretch the spring
limit for the final circuit condition and upon the initial connecting the lever arms.
440 Power-System Stability Basic Elements of Theory and Application Chapter 13 ’

the spring connection between the other two rotatable


elements.
The mechanical model has been-used for the calculation
of actual stability problems but the a-c network calculator
method is more convenient. Thus, the mechanical model
is now employed in its original function of providing the
best qualitative method of visualizing the essential phe-
nomena in the power-system stability problem. Sufficient
EC information has been given to enable one mentally to set
GENERATOR up the mechanical model for the corresponding system
ELEMENT Ed condition and to study its performance for various steady-
INERTIA state and transient conditions. While an actual model is
of considerable assistance, the mechanical analogy is useful
even though no model is available. It is suggested that
the mechanical analogy should be considered in connection
with the entire discussion of this chapter, particularly in
connection with multi-machine problems, such as those
- - involving an intermediate synchronous condenser, since
Pm =v SIN 0 it frequently happens that some particular point is more
- - readily grasped from the consideration of the model than
EC EM
P mox l - x ,9*90* of the actual system.

Fig. lo-The mechanical analogy for power-system stability. II. REPRESENTATION OF SYSTEM FOR
Mechanical Xlodel Power-Transmission System
STABILITY CALCULATIONS
1. Radial distance from pivot to Line voltage at corresponding In discussing methods for calculating stability, it is
any point on spring. point. convenient to consider first the case involving two syn-
2. Length of spring. Line reactance drop. chronous machines, and, subsequently, those involving
3. Tension of spring, propor- Line current. three or more machines. In the previous part the stability
tional to its length. phenomena were discussed in terms of the two-machine
4. Torque of either arm=prod- Active ponyer. system reduced to its elements with the electrical system
uct of the length of the arm represented by two internal voltages and one reactance
and component of spring ten-
between them. In practical systems, even‘for the two-
sion perpendicular to arm.
5. Product of the length of the Reactive power.
machine case, it is necessary to consider other factors,
arm and component of spring such as:
tension along the radius at 1. Representation of system-impedanceelements.
any point.
a. Series branches with resistance.
6. Angle between any two points Phase displacement of voltages b. Shunt branches.
on the spring. at the corresponding points of 1. Shunt capacitance.
the system. 2. Shunt loads.
3. Faults.
The correspondence between the various mechanical and 2. Initial operating conditions.
electrical factors of the mechanical model and the power- 3. Representation of machines including the effects of regu-
transmission system is shown in connection with Fig. 10. lators and exciters.
The mechanical model is stationary for the normal syn-
chronous frequency, and the power-flow relations are rep- 8. Representation of System-Impedance Elements
resented by torques. Movement of the model corresponds A typical layout for a two-machine transmission system
to oscillations of the power system with respect to normal is shown in Fig. 11. This system is assumed to have series
synchronous speed. Thus, the model shows only the resistances, shunt capacitances, shunt loads, maintained
changes in movement that are significant from the stand- voltages at sending and receiving buses, and to be sub-
point of stability. The mechanical model has a power limit jected to an unbalanced fault at point F on line 2, which
occurring at an angle of 90 degrees between the lever arms is subsequently disconnected to isolate the fault.
of a two-machine system. The model is also proportioned In a practical system it is frequently necessary to con-
so as to simulate transient conditions as well as steady-load sider the effect of resistance and of shunt capacitance,
conditions. The mechanical model can be extended by the since these are always present in transmission lines. Since
addition of rotatable elements and additional springs so voltage is normally maintained on the sending and receiv-
as to simulate complicated power systems. For example, ing buses, it is convenient to obtain the equivalent con-
a transmission system with an intermediate synchronous stants for the intervening part of the system. This can be
condenser can be represented by the aid of the third ele- done by the use of the generalized equivalent A network
ment of Fig. 9 with the addition of a spring from the lever or the general circuit constants for the transmission line as
arm of the third element to the appropriate point on described in Chaps. 9 and 10. In either case, it is possible
chapter I3 Power-System Stability Basic Elements of l’heory and Application

fSJ T.L”I + TSD


PM G M
SL

,,;i_: , -&
,-

Fig. 11-Typical two-machine stability problem.


iiotntion: SeeFig. 1; also the following:
?‘.,,-Step-up transformer.
‘I’,,,--Step-downtransformer.
Y’.L.#l, ‘i”.L.#2-Transmission lines.
B,, I(,-Breakers.
F-Fault. LEAD REACTIVE KVA IN PERCENT LAG
E., E,-Voltages at rcgulutcd buses.
L-Shunt load. Fig. 12-Reactive Kva-Voltage characteristics of typical loads.

Curve Description Reactive Iiva Base


to derive power-circle diagrams and power-angle diagrams 60 kva
A lOO-kvn synchronous motor
on the basis of the network intervening between buses, 80 percent power-factor
wlrich have maintained voltages E, and E,. When loss is B lOO-kva synchronous motor 100 kvn
taken into account there is a difference between the sending 100 percent power-factor
and receiving power, as can be seen from Fig. 14. For this c 15-hp induction motor, 80 percent 5 kva
mason, power-angle relations for the two ends are no longer load, 90 percent power-factor
jdentical as assumed in Sec. 3. The method of taking this D lOOO-kw synchronous converter 1000 kva
f:tct into account will be discussed subsequently in Sec. 23, E Transformer magnetizing Value at 100 per-
&p-by-Step Procedure. kva cent voltage
When loss or intermediate loads are present in a power
transmission system, the maximum amounts of power at a large number of small shunt loads; instead, it is permis-
the sending and receiving ends occur at different angular sible to use a single composite load curve. To determine
displacements. If under steady-state conditions the prime- such a load characteristic an effort should be made to
mover input corresponds to maximum input to the motor, obtain the segregation of the principal types of load carried
two interesting phenomena occur if the shaft load is slightly by the system under the conditions for which the stabi1it.y
increased. The motor slows down in any event, but the characteristics are to be investigated. Table 1 gives a
generator (I) may pull out of step with the motor and typical segregation of peak loads.
overspeed or (2) may stay in synchronism with the motor
TABLET-SEGREGATIONOFTYPICALSHUNTLOADS
and slow down with it, depending upon the relative inertias
of generator and motor. These phenomena, while of con- Induction Motor.. 60y0
Synchronous Motor. 10%
siderable theoretical interest*, are of !ittle practical inter-
100% Power-Factor.. .57,
cst, except as indicative of margins, because the important
80% Power-Factor.. ,574
load condition corresponds to the maximum delivered Synchronous Converter.. 5y0
power and that is not dependent upon the relative inertia Lighting and Heating. . . 25%
characteristics.
By combining the real and reactive components of loads
9. Representation of Shunt Loads from segregations similar to that of Table 1 and with
On a system that contains only two large synchronous reactive kva variations similar to those of Fig. 12, it is
machines requiring individual consideration, the various possible to arrive at a composite load characteristic curve,
other loads may have different characteristics from the such as shown in Fig. 13, which includes 15 percent exciting
standpoint of changes in real and reactive components kva. This figure shows the variations in both the real and
with change in voltage. It is usually permissible to assume reactive components of load with change in voltage using
for small synchronous motors and induction motors that the real component at normal voltage as reference. The
the kilowatt load is independent of the voltage. Synchro- dotted curve of Fig. 13 shows the variation for a constant
nous-converter load is assumed to vary in proportion to shunt-impedance load. Figure 13 also shows points on the
the square of the voltage. Lighting load is often assumed power-voltage and reactive kva-voltage curves for 100 per-
to vary as the square of the voltage, but it is more accurate cent and 90 percent voltage obtained from tests on the
to assume that the change is according to the 1.8 power Brooklyn Edison Company’s system?. These tests showed
of the voltage ratiosz. The changes in reactive kva with for a 10 percent reduction in voltage that the power was
voltage are widely different for these different typical reduced to 87 percent and the reactive kva to 80.6 percent
loads, as shown in Fig. 12. of the corresponding values at normal voltage. These are
From a practical standpoint, it is not feasible to consider tSystem Load Swings, by Bauman, Manz, McCormack, and
*For further study of thesephenomenaseeReference10 or 36. Seeley,AIEE Transactions, Vol. 60, 1941, p. 541, Disc., p. 735.
Power-System Stability Basic Elements of Theory and Application Chapter 13

20 in parallel, connected from the point of fault to the


neutral. Thus the stability problem involving an un-
balanced fault at a single location is reduced to one involv-
ing an equivalent three-phase symmetrical system. The
original balanced network gives the desired positive,
sequence quantities at all points when this equivalent
impedance is connected to itt.
The physical interpretation of this method of handling
unbalanced faults is helpful:. The power and reactive kva
consumed in the negative- and zero-sequence networks are
generated in the machines as positive-sequence quantities
and are transmitted through the system to the fault loca-
tion. There these quantities are converted by the asym-
metry of the fault to negative- and zero-sequence quanti-
KILOWATTS IN PERCENT ties which are fed back into the system and consumed as
LAGGING REACTIVE KVA IN PERCENT RI2 and XI? for negative- and zero-seqlrence except for
the effect produced by negative-sequence torques in ma-
Fig. 13-Variation of composite load with voltage.
chines. As pointed out in Chap. 6, the negative-sequence
-Composite load based on Fig. 12. input to the rotor of a machine is consumed half in l&J,2
- - -Const,ant impedance. losses and half in negative-sequence torques. These
0: : -0 (Bauman , JIanz, ,\IcCormack and Seeley.) Normal torques tend to drive the machine in a direction opposite
kilowatts equal 100 percent.
to that of its normal rotation. The accurate method of
considering this effect is, of course, to modify appropriately
to be compared with 81 percent, which would be obtained the mechanical input to the machine. The negative-
\vith a constant-impedance load of the corresponding power sequence resistance for typical machines is given in Table
factor. The variations in load voltages usually are not 4 of Chap. 6.
great because they are maintained by local generators and
synchronous condensers equipped with voltage regulators. 11. Determination of Initial Operating Conditions
This fact permits the relatively crude approximation of Frequently in stability studies only part of the initial
constant-impedance loads to give satisfactory results for operating conditions are defined or are known. Conse-
the majority of cases. quently, to determine the initial conditions, calculations
and frequently additional assumptions are necessary.
10. Representation of Faults Usually the delivered power and maintained voltages at
In this discussion of stability, symmetrical systems only sending and receiving buses are known. 41 addition, the
have received consideration. However, the majority of characteristics of the transmission line, step-up and step-
faults on power systems are not balanced three phase. As down transformers are known, although sometimes the kva
a consequence, the individual phase voltages are consider- capacity of the latter must be adjusted. For the deter-
ably unbalanced, and the voltage of neither the faulted mination of the initial operating conditions the use of the
nor unfaulted phase (or phases) is a measure of the voltage power-circle diagram is frequently advantageous because
available for through power transmission. Instead, the the bus voltages are usually known or can be assumed
positive-sequence voltage is the representative quantity. since they are subjected to relatively narrow variations.
In Fig. 21 of Chap. 2, interconnections between the se- A particular method of using the power-circle diagram to
quence networks are given for various types of faults at assist in the determination of the initial operating COP
a single location. When the sequence networks, as viewed ditions will now be described in connection with the system
from the point of fault, are thus interconnected to represent outlined in Fig. 11. The operating conditions of that part
a particular type of fault, correct positive-sequence volt- of the transmission system, including step-up and step-
ages and currents will exist at all points in the positive- down transformers, between the sending and receiving
sequence network (the original balanced network). Since buses whose voltages E, and E, are maintained, can con-
only the positive-sequence quantities are to be used, all of veniently be shown by the power-circle diagram of Fig. 14. +,
the interconnected network except the positive-sequence The center of the receiving circle for the transmission line -6’
network can be reduced to a single impedance*, which with transformers is plotted at the point C, and of the g
simplifies calculations. This impedance is, as the above sending-end circle at the point C,. The positions of the ,$
discussion shows, a function of the negative- and zero- .:.
sequence impedances as measured from the point of fault, tThis method is actually applicable to all types of unbalance%
and varies with the type of fault. Thus, for a single line- including open conductors and multiple faults at separate locations.
to-ground fault this impedance is (&+&) connected from For example, for the case of two conductors open, the equivalent
impedance is the sum of the negative- and zero-sequence imped-
the point of fault to the neutral of the system; and for a
ances as viewed from across the open, connected across the opm Of
&Zo the positive-sequence network, i.e., an impedance between two
double line-to-ground fault, it is - , that is, ZZ and
( &+Zl > points of the positive-sequence network. Referring to Chap. 2, Fig.
21 (p), impedances (X, to Y,) plus (X0 to Yo) connected fromXi to Yi*
*Appendix III of Reference 5 and Reference 27. $Page 324 of Reference 27.
Chapter 13 Power-System Stability Basic Elements of Theory and Application 443

+ Q LAGGING kva computed on the basis of the terminal voltage and


REACTIVE POWER equivalent machine reactance. The internal voltage in
magnitude and phase position becomes immediately avail-
able from the circle diagram, since the receiver conditions
for the generator must equal the sending-end conditions
for the line. The phase position is given by the angle Ba
measured between the radius g-s and the line of centers
g-o. Since terminal conditions at s must be satisfied, the
magnitude of the internal voltage of the generator is given
by the relation:
E _ distance g to s E
(3)
g-distance g to o ’
Similarly, the internal voltage of the synchronous motor
can be obtained from its real and reactive-kva input and
its terminal voltage. The center of the sending circle for
the motor is located at the point m. The phase position of
the internal voltage with respect to the terminal voltage
is given by the angle 8,. The magnitude of the internal
voltage of the motor is:
E =d fstance m to r E
m distance m to o ’
(4)
The effect of shunt load, such as shown at the receiver
bus in Fig. 11, can be taken into account in several ways.
For example, the shunt load can be added to the trans-
mission system and considered as a part of it. Another
method is to subtract the shunt load from the receiver,
which assumption would modify the input to the syn-
chronous motor by the amount shown graphically by
changing the load point from T to rl. The effect of this
shunt load on the magnitude and phase position of the
LEADING internal voltage of the motor can readily be computed
-0 REACTIVE POWER
for the load at ~~ in a manner similar to that previously
Fig. 14-Diagram illustrating the use of power-circle diagrams described for the load at T.
to determine initial conditions of internal voltagesand overall The method of using the circle diagrams illustrated in
angles on a system with maintained terminal voltages. Fig. 14 provides a convenient method of obtaining the
internal voltages of machines both in magnitude and phase
radii of these circles for zero difference in phase position position. The total difference in angle between these volt-
between sending and receiving voltages are shown as the ages is, of course, equal to the sum of the machine and line
reference position for the angle 8. For a typical operating angles, that is, the sum of 8,, 6 and 8,. This method of
condition the receiver load is represented by a point in the using the power-circle diagram is particularly applicable
receiver circle at r and at the angle 6 with respect to the for those problems in which the voltages are maintained at
zero position of the radius vector. The corresponding sending or receiving buses or at other points in the system
sending-end power and reactive-kva quantities are shown through the use of voltage compensators.
at the point s also at the angle 0 with respect to the zero
position of the radius vector for the sending-end circle. 12. Representation of Machines
The output of the synchronous generator supplying the Previously, it has been indicated that a synchronous ma-
transmission line is completely defined by the real and chine can be represented in stability studies by an appro-
reactive kva and terminal voltage. If the equivalent re- priate reactance and a corresponding internal voltage.
actance of the generator is known, the internal voltage can Two reactances are commonly used, viz. :
readily be computed from the terminal conditions in the
1. An equivalent synchronous reactance for steady-state sta-
usual manner. It is a simpler matter usually to plot parts
bility.
of another circle diagram for the synchronous generator 2. Transient reactance for transient stability.
considering it as a reactance line for which the receiver
conditions are completely defined. Ordinarily, the resist- The internal voltages associated with these reactances are
ance loss is negligible in comparison with the reactive kva determined from the terminal voltage and the voltage drop
Mh the result that the center of the generator circle due to the load currents flowing through the machine re-
diagram is located on the Y-axis. The center of the re- actance.
ceiver circle for the generator is located at the point g, In the case of steady-state stability, the value used for
which is numerically equal to the generator short-circuit the equivalent synchronous reactance depends upon the
1
444 Power-System Stability Basic Elements of Theory and Application Chapter 13 ’

method of calculation being used. This is discussed in de-


tail in Sec. 14 where methods of steady-state stability cal-
culation are described.
In transient-&ability studies, the internal voltage is the
vector sum of the terminal voltage and the transient-re-
actance voltage drop due to the load currents just prior to
the disturbance.

III. STEADY-STATE STABILITY


CALCULATIONS
In this part the general problem of steady-state stabil-
ity calculation is discussed in detail and specific examples
h[riven to illustrate each method of calculation. Particular Fig.15-Vectordiagramforsalient-polesynchronousmachioe
attention is given the problem of calculating the power based on two-reaction method.
limit of the synchronous generator connected to a system. Et-Terminal volt,nge (phase-to-neut,ml-rms).
The power limit in this case is commonly called the “pull- Ed--Excitation voltage due to flus in direct axis.
out poner” or the “pull-out torque.” I-Armat,ure current (line-rms).
The pull-out power as discussed herein refers to a steady- 8-Displacement :mgle.
st,ate stability condition, which is initially of a transient +-Power-factor angle.
character but must be endured long enough to bring it into
the classification of steady-state stability. Tripping of a
loaded generator, loss or reduction of the excitation of a (8)
generator, or the tripping of a tie line supplying power to
the system illustrate that pull-out power or maximum where xd and x, are direct- and quadrature-axis synchro-
power output of the generators involved is important. The nous reactances. Equation (5) is based on the relations in
pull-out power of a generator is calculated from the inher- the quadrature axis for which excitation voltage Ed is pro-
ent characteristics of the generator, which are governed by vided by flux in the direct axis. Equation (6) is based on
such factors as air-gap length, demagnetizing effect of the the relation in the direct axis for which there is no excita-
stator on the rotor, degree of saturation, reactance, and tion voltage, as is almost invariably the case. The cor-
short-circuit ratio. For modern machines if the short-cir- responding current equations are given by (7) and (8).
cuit ratio is specified, the other factors usually have a fairly The expression for three-phase power in terms of terminal
definite range of values, so that short-circuit ratio is the and excitation voltages can be obtained by eliminating I
best single index of inherent steady-state stability of a gen- and C/Jfrom Eqs. (5), (6), and (8) with the result
erator. --
The power equations in the following sections are written p=xEtEdsine+3Eigixq)sin 20
in terms of single-phase quantities. Thus, when the voltages xd Q d

are written as line-to-neutral volts and the reactances as ohms which becomes
per phase, the power oblained from the equations is single- --

phase power. It should, of course, be multiplied by three to p _ EtEdsin e+EZ(xd-x,) sin 28

obtain the three-pha,y power. If all line-to-neutral voltages xd 2xdxq

are multiplied by 43 and expressed as line-to-line volts, the when the voltages are expressed as line-to-line voltages.
equations give three-phase power directly. The equations can All voltages are line-to-line values in the remainder of this
be used without alteration when the work is done using section. The power limit for a single salient-pole ma-
per-unit values. c_hine connected to an infinite bus of maintained voltage
Et can be obtained directly from Eq. (9). In a salient-pole
13. Effect of Saliency on Steady-State Stability
machine the steady-state power limit is reached at an an-
The steady-state performance of a system containing gle considerably less than 90 degrees. For the non-salient
unsaturated salient-pole machines can be calculated by the pole machine the quadrature-axis reactance X~ is equal to
two-reaction method discussed in Chap. 6, particularly in the direct-axis reactance xd, which relation reduces the
connection with Figs. 12, 14, and 15. These diagrams are maximum power from Eq. (9) to the familiar form pre- .I
similar to that of Fig. 15 of this chapter, except that the viously derived for the transmission line and given in *’
notation has been changed from machine form to circuit Jj&,
Eq. (2). --
form. For this diagram the relations of voltage and cur-
rent in terms of the machine angles were previously de- p-EtEd
xd
rived or may be written by inspection as follows:
Ed=Et cos O+xdf sin (e++) (5) With two identical salient-pole synchronous machines at
0= -Et sin B+z,I cos (/3++) equal excitation, one acting as a generator, and the other
(‘3 as a motor, the terminal voltages and currents are m
I Ed-Et ~0~ e phase causing the angle Cpto be zero. The power relation
=xd sin (e++) (7) for this condition can be stated in terms of the terminal
Chapter 13 Power-System Stability Basic Elements of Theory and Application

voltage as given in Eq. (11) or in terms of the excitation


voltage as given by Eq. (12).

p=!3 tan fl (11) MAINTAINED


2, VOLTAGES
Ei sin 28 .7 EOUAL TO 100%
P= 2 (12)
.6
2, cos2 fl+z sin? 19
( ) .5
The maximum power that can be delivered by a system
.4
consisting of two identical salient-pole machines directly
connected and operating at equal excitation is obtained .3
from Eq. (13).
.2
f> = w:F (e, xd, xq) (13)

for which the value of the function F (0, xd, x,) is plotted
OO
I I I
1.0
I I
2.0
I I
3.0
I I
4.0
I 11
5.0
I
I 0
,in Fig. 16. As a matter of interest the total angle between
RAT,o2 = DIRECT-AXIS SYNCHRONOUS REACTANCE
synchronous machine rotors, 28, at the point of pull-out is ONE HALF LINE REACTANCE
XL

Fig. 17-Effect of machine reactanceon power limits of trans-


mission system with identical machines and fixed excitation.
Curves plotted in terms of the reactance xd and xe of each
machine and XL of one-half of line.

terminal voltage and the direct-axis synchronous reactance


only, using Eq. 13 with xq=xd, gives 42.3 kw. Using the cor-
rection factor obtained from Fig. 16, the stability limit con-
sidering the effect of saliency was calculated to be 52 kw.
Actual tests made on these machines gave 52 kw.
The effect of saliency on the power limit of a transmis-
sion system is illustrated in Fig. 17. In this case the trans-
mission system is assumed to consist of two identical ma-
chines, one operating as a generator and the other as a
motor, with equal fixed excitation adjusted to maintain
100 percent, terminal voltages as indicated in the insert of
the figure. The power limits for such a system can con-
veniently be espressed in terms of the limit of the line
RATIO xd alone. In Fig. 17 the solid-line curve is plotted for non-
xq salient pole machines, i.e., with z, =zd; the dotted-line
Fig. 16-Effect of saliency on power limit and total displace- curve is plotted for a salient-pole machine for the rela-
ment angle for two identical machines operating at equal tively large ratio of &r/z, equal to four. The effect of
fixed excitation adjusted to maintain constant terminal volt- saliency is small even for a ratio of zd/zq as high as four.
age. Saliency effect plotted as ratio of power limit for various For ratios of &r/x, between one and four the values will lie
ratios xd/xq to values based on xd alone.
relatively close to the solid-line curve as the curve for
saliency correction given in Fig. 16 suggests.
~SO plotted in this figure. It will be noted that for The foregoing discussion has presented sufficient for-
r,,=~d, Eq. (13) is identical in form with that previously mulas to permit the analysis of the difference in stability
derived for the steady-state stability limit and that the limits resulting from the saliency effect obtained by the
maximum power occurs at an angle of 90 degrees between two-reaction method in comparison with the results ob-
t’he two machines and with an internal voltage equal to & tained by using the direct-axis reactance only. The re-
t,imes the terminal voltage. By using the internal voltages actances of synchronous machines given in Table 4 of
and the total reactance the same power expression would Chap. 6 show that the ratio of zd/x, varies from one to an
be obtained as previously given in terms of terminal volt- upper limit of approximately four. Under practical oper-
age and the reactance of a single machine. Figure 16 is also ating conditions this ratio is greatly reduced because of
useful as indicating the correction in the stability limit, the effects of saturation. Furthermore, the power systems
which must be made because of the effect of saliency. for which the steady-state stability limits are important
Example 1. Two salient-pole machines directly connected, almost invariably involve circuit elements that introduce
three-phase, 2200 volt, 210 kva, operated at 1150 volts to impedance between the machines and which result in an
avoid effects of saturation, with reactances of xd=31.4 ohms, important reduction in the effective ratio of the direct- and
x,=8.83 ohms. The stability limit as determined from the quadrature-axis reactances.
446 Power-System Stability Basic Elements of Theory and Application Chapter 13

14. Effect of Saturation on Steady-State Stability chine at the pull-out point. This method of solution is de-
The effect of saturation on the equivalent synchronous scribed belo\C along &th some simplified methotls of Cal&-
reactance and corresponding internal voltage of synchro- l&ion. The results obtained by using the variolls methods
nous machines is generally much more important than that are compared over a range of conditions to illustrate those
of saliency. These effects from the stability standpoint are casts where the simplified methods can be used with ac-
determined from the terminal voltage, power and reactive ceptable accuracy.
kva output, and the excitation characteristics of the ma- Potier voltage Method-This method is best under-
chines as determined by test, or by recognized methods of stood if the analysis is considered on the basis of the two
calculating the regulation of synchronous machines as dc- existing operating contlit,ions: the initial operat,ing condi-
scribed in Chap. 6. tion, and the pull-out operat,ing condition. In Fig. 18 (a)
There are several methods of including the effects of is illustrated a generator C connected through its o\vn re-
saturation in the determinat,ion of pull-out power of a gen- sctance 5, to a terminal bus, which in turn is connected to
c&or. The most accurate of these uses the voltage behind an assumed infinite bus in the system through the equiva,
Potier reactance, E,,, to ndjllst the saklrntion of the ma- lent external reactance x0. The reactance s, is the react-
ance of t,he system betlvecn the generator terminals and
the infinite bus reduced to a single equivalent reactance,
The internal voltage of the generat,or is represented by
Ei”b
The vector diagram for the system during the initial op
erating conditions prior to pull out is given in Fig. 18 (b),
It is necessary, of course, to express all vector quantities on
a common base, and the most convenient method of doing
so is to use the per-unit system with the generator rating a.s
a base. This is equivalent to referring to all voltages in
terms of the generator field escitation required to produce
them. The generator rated voltage, current, and kva are
used for the base in expressing the voltages, currents, and
reactances, respectively, as per-unit quantities. On this
basis, 1.0 per-unit power converted to kilowatts is equal to
the generator kva rating.
Referring to Fig. 18 (b), the following equations can be
written. The infinite bus voltage E, is the generator ter-
minal voltage minus the drop through the external react-
ance,
E,=E,-Ix, (14)
The voltage behind Potier reactance E, is equal to the ter-
minal voltage plus the Potier reactance drop,
E,=E,+Ix, (15)
(b) The internal voltage Eint of the generator is equal to the
terminal voltage plus the drop through the generator in-
saturated synchronous reactance,
Ei,t=Et+IXd (16)
The saturation curve of the generator is shown in Fig. 19
plotted in per unit. Rated generator voltage is used as 1.0
per-unit voltage, and the field current nccessnry to produce
rated voltage on the air-gap line is 1.0 per-unit field cur-
rent. The saturation s is the difference between the ex-
citation required t,o produce E, on the no-load saturation
curve and the excitation required to produce E, on the air-
gap line. The excitation voltage i%, which is equivalent to
the total field current under the initial load condition, is
the internal voltage plus the saturation,
Fig. il-Vector diagrams for initial-load and pull-out condi-
tions. Ex=Eint+S (17)
(a)-Equivalent representationof gerwator and external system.
(b&Vector diagram of system with generator loaded with rated _ The
. power transferred from the generator to the infinite
bus is
kilowatts,power factor and voltage.
(c)-Vector diagramat pull out with B increased to 90 degrees and
E. and E, equal to initial-load values in (b).
chapter 13 Power-System Stability Basic Elements of Theory and Application 447

I,= E’int-Er
(22)
xd+xe

E,‘= E,+I’x, (23)

E,,‘= Er+I’(xe+~,) P-1)

A method of successive approximations must be used to


determine the value of s” which leads to the correct solu-
tion of the vector diagram. First, a value is assumed for s,
and Eqs. (20), (al), (22), and (24) are used to calculate
E,‘. The actual value of 8’ is found from the saturation
curve at a voltage equal to Ep’ and is compared with the
assumed value. The assumed value is then adjusted until
the actual value found by repeating the calculation of I!?,’
is equal to the assumed value. Usually, two approximn-
tions yield a sufficiently accurate answer. When the cor-
rect values of sf and IZ’int are found, the pull-out power
can be calculated by

(25)

or --
P mnx=E,‘I’ cos 4’ cw
The application of the Potier voltage method is illus-
trated with an example in which G in Fig. 18 (a) is a
60 OOO-kw, 70 588-kva, 13 800-volts, 0.85-power factor,
hydrogen-cooled turbine generator. The saturation curve
EXCITATION IN PER UNIT of the generator is shown in Fig. 19. The equivalent sys-
Fig. 19--Saturation curve of 60 OOO-kilowatt, 13 800-volt, 0.85-
tem reactance x, is 0.25 per unit on the generator rating of
power factor generator used in the example of steady-state 70 588 kva. During the initial load conditions, the gen-
stability calculations. erator is assumed to be carrying 60 000 km at 0.85 lagging
power factor with its terminal voltage E, maintained at
where rated value. The initial load data can be written as fol-
lows, using the generator rating as a base:
5, = Q, the generator unsaturated synchronous react-
ance. Et= 13 800 volts= l.O+jO.O= 1.0 /o” per unit.
8 = Angle between E, and Eir,t. km output =60 000 kw=0.85 per unit.
kva output = 70 588 kva = 1.O per unit.
The generator power output is, of course, also found from 1=0.85--j0.527=1.0 i-31.8” per unit.
the equation 4=31.8O.
P=EJ cos cp (19) x,=0.25 per unit.
Under the hypothesis of constant excitation in the tran- The required generator constants can be determined
sition from the initial load condition to the pull-out condi- from the saturation curve:
t,ion, the excitation voltage ,??,remains constant. The in-
finite bus voltage E, is also assumed to remain constant, so xd=1$=E=1.30 per unit
that these twovoltages and the reectances xg, CC,,and x, and I!3 .
the angle 0 are the only quantities known at the time of where
~111out, and the internal voltage at pull out E’int must be Ifsi = Field current required to produce rated arma-
determined. ture current with a three-phase short circuit at
The vector diagram of the system at the time of maxi- the generator terminals.
mum power transfer is given in Fig. 18 (c). The excitation If, = Field current required to produce rated voltage
voltage E, is used as the reference vector and is equal in on the air-gap line.
magnitude to the value calculated for the initial load con-
dition. The angle 0 is 90 degrees, so the infinite bus voltage The Potier reactance x, is determined from the Potier volt-
E, lags E, by that angle. Expressions for the remainder age triangle as shown in Fig. 19 and is -
of the vector diagram are x,=0.11 per unit.
jpint=Ex-&y (20) Referring to the vector diagram in Fig. 18 (b) and using
I’(x~+x,) = E’int- E, r-21) Eqs. (14), (15), and (16),
448 Power-System Stability Basic Elements of Theory and Application Chapter 13

E,= (1 .O+jO.O) - (0.85 -jO.527) (j0.25) The pull-out power for the assumed conditions is found
=0.8682-jO.2125=0.894 --/-13.77” from Eq. (25)
y = 13.77”
~,=(1.0+j0.0)+(0.85+0.527)(j0.11) f.lnlrlx= (2.20g)(o.8g4) = 1 274 per unit
= 1.058fj0.0935 = 1.062 /5.06” 1.30+0.25 *
Ei~~=(1.0+j0.0)+(0.85-j0.527)(j1.30)
or from Eq. (26) where
= 1.685+jl.105 = 2.015 -/33.25’
e--y=33.250 c#i=68.0”--64.6”=3.40”
8=33.25”+13.7i”=17.02° Pm,, = (0.830) (1.538) cos 3.40” = 1.274 per unit
From the saturation curve at a voltage equal to J!?~= The pull-out power in kilowatts is
1.062 per unit, the saturation s’ is 0.254 per unit, and from
Eq. (17) Pm;,,= (1.274) (70 588) = 89 930 kw.
Ex = 2.015+0.254 = 2.269 Many different initial operating conditions might be
The above results can be used in Eq. (18) as a check to de- used to represent the system in a practical calculation. In
termine the accuracy of the calculations thus far: the above example, where the generator terminal voltage
was assumed as 1.0 and the kw load as 0.85, the margin ob-
p = (2.OW (0.894 Yin 4i 02” tained between the operating condition and the pull-out
1.30+0.25 ’ condition was 1.274-0.85 or 0.424 per unit which is equiv-
=0.8504 per unit. alent to 29 930 kw. The generator kw load, therefore, could
The vector diagram for the pull-out condition is shown be increased approximately 50 percent before the machine
in Fig. 18 (c), and using EX as a reference, the following would pull out of step with the system. There may be
quantities are knojvn: other considerations such as turbine capability or generator
Ex = 2.269 ,/oo = 2.2694jO.O heating that limit the load to some value below the maxi-
E,=0.894 /-90”=0.0-j0.894 mum permissible power from the stability standpoint. If
e=900 other initial operating conditions are assumed, the excita-
tion voltage is, of course, changed, and the pull-out power
Esnmination of the vector diagram reveals that ,!?,’ can be differs from that obtained in the above example.
estimated by drawing the line A%, assuming s’ equal to Synchronous Reactance Method-In this simpli-
zero, i.e., Elint=Ex. The location of point C can be found fied method of steady-state stability calculation, the gen-
from erator is represented by a reactance equal to the unsatu-
AT= ‘2 (AZ) rated synchronous reactance, xd, and an internal voltage
e equal to the voltage behind unsaturated synchronous re-
The vector m is equal to E,‘, the voltage behind Potier actance, as determined by the initial load conditions. This
reactance, and can be used to determine a value for the voltage, Ed, is the same as Eint determined in Eq. (16). It
first approximation of s’. Following this procedure, s?’ is is evident, therefore, that this method of calculation does
assumed to he 0.10 per unit. From Eqs. (20), (21), (22) not take into account the increase in Eint caused by the re-
and (24), duced saturation when the pull-out point is reached, and
the masimum power so obtained is less than that given by
E’int.= (2.269+jO.O) -0.10
the Potier voltage method. The maximum power equa-
=2.169+jO.O=2.169 /O”
I’(xd+xe) = 2.169+jO.894 = 2.3z/22.4’ tion becomes
I,=2:169+j0.894 pm,,= -EY!!!L
~1.3O+jO.25 xd+%

=0.577--j1.400=1.514 /-67.6’ where Ed= E,+Ixd


E,‘= (0.0 --jO.894) + (0.577-j1.400) (j0.36)
=0.504--jO.G86=0.852 /-53.73” calculated for the condition prior to pull out.
From the saturation curve at E,‘=0.852 per unit, L!!?= From the calculations in the example above,
0.057 per unit which shows that the first approximation E,, =i?, = 2.015 per unit
was too high. A lower value, therefore, should be assumed E,=0.894 per unit
for the second approximation, but observe that decreasing _ (2.015)(o’8g4) = 1 162 per unit
p mu?.
--
the value of s” slightly increases the value of E,‘. Thus, 1.30+0.25 ’
3’ is assumed as 0.06 per unit for the second approxima-
tion. Short-Circuit Ratio Method-The short-circuit ratio
E’int = 2.209+jO.O= 2.20 /oo (SCR) of a generator can be obtained from the saturation ;
I’(xd+x,) = 2.209+jO.894 = 2.385 /22.0’ curve f
I’=0.577+1.425=1.538 /-68.0’ SC&g (27)
E,‘=O.513-jO.686=0.857 l-53.2” fs1
S’ (from saturation curve) =0.06 where
E,‘= (O.Ofj0.894) + (0.577 --j1.425) (j0.25) If”1 = Field current required to produce rated voltage
=0.356-jO.750=0.830 /-64.6’ on the no-load saturation curve.
Chapter 13 Power-System Stability Basic Elements of Theory and Application 449

If,i = Field current required to produce rated arma- In this method, therefore, a certain amount of correction
ture current with a three-phase short circuit at for saturation at pullout is obtained, but it is a constant
the generator terminals. approximation, whereas the true saturation is variable
depending on the operating conditions.
In this method of calculation, the generator reactance CC,is Internal voltage is calculated for the initial operating
represented by the reciprocal of the generator short-circuit
conditions from
ratio,

and the magnitude of the internal voltage at the pull-out


1
The quantity So is roughly equivalent to the generator point is assumed equal to the value so calculated. The
maximum power equation is
unsaturated synchronous reactance, differing only in the
fact that it takes into account a certain amount of satura-
tion. The saturation included is that existing at rated
voltage on the no-load saturation curve, and if this value
of saturation is designated &,I, it can be shown that
. Applying this method to the example, the short-circuit
1 ~- 1 ratio is found from the saturation curve and Eq. (27),
SCR=“”
4) l+S,,
SCR=g=O.892
2’oL 5.= 1.121 per unit
E~~~=(1.0+~0.0)+(0.85-j0.527)(j1.121)
= 1.59l+jO.953 = 1.856 /30.9”
p max= (1’854)(o’8g4) = 1 209 per unit
1.121+0.25 ’

I I I I

POTIEA VOLTAGE METHOD

0.4 - POTIER VOLTAGE METHOD


-- - i AIR-GAP VOLTAGE METHOD
. SHORT-CIRCUIT RATIO METHOD
0.2 - SYNCHRONOUS REACTANCE METHOD--
0.2

0
0 35 .90 .95 1.0 .95 .90 .85 .80
.85 .90 .95 1.0 .95 .90 BO
UNDEREXCITED -I+ OVEREXCITED UNDEREXCITED --I- OVEREXCITED
POWER FACTOR POWER FACTOR

Fig. 20-Comparison of four methods of calculating pull-out Fig. 21-Comparison of four


methods of calculating pull-out
power. power.
se = 0 per unit x, =0.25 per unit
Initial load equal to 60 000 kw or 0.85 per unit at various power Initial load equal to 60 000 kw or 0.85 per unit at various power
factors with terminal voltage Et equal to 13 800 volts or 1.0 factors with terminal voltage EL equal to 13 800 volts or 1.0
per unit. per unit.
0.4 - I I I ,
1 I I I I I I
LbAD ‘RF: =‘.65 LEAdING-
.2 x, = .25 P.U.
0’ ’ I I I I I I I I I
0 .I0 .20 .30 .40 50 .60 .?O .00 .90 1.00
0
0 .I0 .20 .30 .40 .50 .60 .70 .80 .90 1.00
1.0

0.8
0.6
0.6
04 LOAD I? F: ;.95 LEAOING-
x,=0
0.2 I

0
0 .I0 .20 .30 .40 .50 .60 .70 .00 .90 1.00 II I II II I I / / 1
‘0 .I0 .20 .30 .40 SO .60 .70 .00 .90 1.00

a 0.0
I
B
3 0.6
8
& 0.4
0’
1 0.2
$
a 0
0 .I0 .20 .30 .40 SO .60 .i’O .80 .90 1.00

1.6

I?)

0.6

0 .I0 .20 .3 0 .40 .50 .60 .?O .80 .90 1.00

0
0 .20 .30 .40 SO .60 .?O .00 .90 1.00

0’ 0.4 LOAD LAGGING-


iI 0.2 X,= .25 RU.
I I
x,*0 2
0.6 0
0 .I0 .20 .30 40 .50 .60 .70 .60 .90 1.00
INITIAL LOAD-PER UNIT

- POTIER VOLTAGE METHOD


----- AIR-GAP VOLTAGE METHOD
O-
0 .I0 .20 .30 .40 50 .60 .70 .80 .90 1.00 --- SHORT-CIRCUIT RATIO METHOD
---- SYNCHRONOUS REACTANCE METHOD
INITIAL LOAD-PER UNIT
Fig. 22-Comparison of four methods of calculating pull-out power.
Each curve is calculated for an initial-load condition of
various kilowatts at the indicated power factor with the terminal voltage equal to 1.0 per unit.
chapter 13 Power-System Stability Basic Elements of Theory and Application 451

Air-Gap Voltage Method--The use of the air-gap line closelv with the Potier-voltage._ method over the range of
voltage t0 represent the internal voltage of a generator in a conditions studied.
,tc~:ldy-state stability st,udy is b:wxl on the fact that there A4summary of a large number of calculations of pull-out
;s ,,sl~ally little saturation esisting at the time of pull out. power for the sample machine is given in Fig. 22. To ob-
‘rile air-gap line voltage which is used is that voltage read tain the data in each curve the generator power factor and
oII the air-gap line at a value of escitation equal to that re- terminal voltage mere held constant for the initial load con-
C,,li~.(:~lfor the initial load condition. When espressed in dition. while the generator load in kilowatts was varied.
,,C‘rrlnit, this voltage is equal to the excitation voltage E, Study’ of these c&es shows close agreement between the
,rl,t:lincd in Eq. (17). The unsat,urnted synchronous react- four calculating methods over the range of conditions in-
:lI1(b~r,~ is used to represent the generator reactance zK. cluded. Of Darticular interest is the fact that the result
‘1’11(1s,if there is any saturation in the machine at pull out, obtained by’the short-circuit ratio method exceeded that
1llis rncthod uses a voltage which is too high by the amount obtained by the air-gap voltage method at low leading
,,f the: ssturnt,ion to represent the internal voltage. The power factor and reduced load.
,I1:1simum pwvcr equation for this method is Extension of the Potier-Voltage Method-The Po-
. tier-voltage method as described above may appear to be a
EintZr
Pmnx = __ long and tedious procedure when a large number of condi-
2dfG tions are beinrr%,studied. The equations can. however. be
\VllW modified for certain specific conditions and the calculations
are then greatly simplified.
Ei,,t=&=Voltage read on air-gap line at the field
Frequently, it is desired to know the magnitude of field
excitation required to produce the ter-
current or excitation voltage that must be maintained to
minal voltage under conditions of load.
prevent a generator from pulling out of synchronism. It
In the example above, E, \~as found to be 2.269 per unit, has been shown that the pull-out power is a direct function
:lnd the maximum power is of the excitation voltage less the saturation. ‘4 generator
will pull out of synchronism when carrying a given kilo-
pmax
I = (2’2sg)‘o~8g4)
= 1,309 per unit. watt load if the excitation voltage is reduced below a cer-
1.30+0.25 tain minimum value. -4 curve of pull-out power as a func-
Comparison of Methods-Results obtained by cal- tion of excitation voltage is easily derived by the Potier-
collating the pull-out power for a given kilowatt load at voltage method.
various power factors using the four methods are com- The first steD in the txocedure is to assume a value of
pared in Figs. 20 and 21. The 60 OOO-kw generator de- pull-out power; P,,,, and L determine the magnitude of in-
&bed in the example above was used in making the calcu- ternal voltage required to deliver that power by solving
lations. In all cases, the generator nns assumed to be car- Eq. (25) for E’int:
rying 60 000 kilowatts at the specified power factor and
with the terminal voltage maintained at rated value during jpint = P,.,,
-=y.Td+z,) (28)
11x initi,aJ load condition. In the transition to the pull-out E,
point, the infinite-bus voltage was assumed constant at the Referring to the vector diagram in Fig. 18 (c), two equa-
w111ecalculat,ed for the initial load condition. Figure 20 tions can be written:
show the results \vith t,he external reactance z, = 0, and in -
Fig. 21, x,=0.25 per unit.
-jE,+jI’(~,+z,) =E’int+jO (2%
In all cases, the air-gap voltage method gives the highest I&‘= -jE,+jz’(z,+zp) (30)
value of pull-out power. This is to be expected since this
method assumes no saturation at pull out and uses a volt- Solving for I’ in Eq. (29) and substituting in Eq. (30),
:~gchigher than actual to represent the generator internal
\oltagc. The synchronous-reactance method, on the other
hand, assumes that the saturation at pull out is equal to the
saturation existing under the initial load condition and, Letting
consequently, represents the generator internal voltage by
K=- &+G (31)
a voltage lower t,han the true value. The synchronous- Z+G3
reactance method, therefore, gives the lowest results in all
cases. The actual value of pull-out power must be between Ep’= dEf2int K2+E:(K- 1)2 (32)
the values obtained by these two methods, since one meth-
(~1considers no saturation while the other considers a high In terms of the pull-out power, Eq. (32) converts to
value of saturation.
The Potier-voltage method and the short-circuit ratio E,l=~p~(z,,+2.)2+Ej!s- 1)2.
method give results within the limits set by the air-gap r
voltage and synchronous-reactance methods. Based on Using Eq. @8), therefore, the internal voltage is deter-
modern synchronous machine theory, the results of the mined, and E,‘, the voltage behind Potier reactance, is de-
l’otier-voltage method are more accurate, because the sat- termined by using either Eq. (32) or Eq. (33). The satura-
uration at pull out is adjusted to the proper value. The tion 3’ is_then read from the saturation curve at a voltage
short-circuit ratio method gives results that compare equal to E,’ and added to the internal voltage to obtain the
Power-System Stability Basic Elements of Theory and Application 1
452 Chapter 13 ‘,

excitation voltage as in Eq. (17). As pointed out previous-


ly, it is desirable that all calculations be done using per-
unit values. When this is done, the excitation voltage ob-
tained is in reality the per-unit field current required by the
machine. The actual value of field voltage required can he
obtained by multiplying the field current by the field re-
sistance properly adjusted to take into account tempera-
ture effects.
As an example, this procedure can be applied to t,he
GOOOO-kw generator used above, and the field current de-
termined for a maximum power of 1.25 per unit with the
infinite bus voltage Ei, equal to 1.0 per unit and the ex-
ternal reactance equal to 0.25 per unit. From Eq. (28),

E~,,=~(l.30+0.25)=1.937 per unit.

K=0.11+0.25
=0.2323.
1.30+0.25
From Eq. (32)
E,‘= 1/(1.937)2(0.2323)2+(1.0)~(0.2323- 1.0)2
=0.890 per unit.
From the saturation curve, s’ is 0.074 per unit, and the re- FIELD CURRENT IN PER UNIT
quired excitation voltage or field current is 1.937+0.074=
2.011 per unit. One per unit field current on this generator 0.5
is 332 amperes, so that the field current required would be
668 amperes, and the field voltage would be this current 1.0
multiplied by the field resistance.
I.5
The results of a number of calculations of this type on
the sample machine are plotted in Fig. 23 for three values 2.0. \
of external reactance, to illustrate the manner in which the
data can be presented. Because these curves give the value 2.5
of field current for pull out, it is obvious that the generator
3.0
3.25
Fig. 24-Estimating curve for determining the pull-out power ,
3.00
/ of an AIEE-ASME standardized turbine generator as a func- i
tion of kva load and power factor. <
2.757
2.50
1.0 per unit kva load = generator rated kva.
1.0 per unit Pull-out Power =generator rated kva.
.E
‘i
,

I-
1.0 per unit field current = field current required for rated voltage i
12.25 on air-gap line. ,
I>
,j
z2.00 Find the point corresponding to the initial kva load on the :‘;
upper ordinate and trace horizontally to the proper power
factor line. Drop vertically to read field current on the ,.g<
f 1.75
abscissa and to intersect with proper external-reactance
I I I I I I/IA4 P curve. Pull-out power is read on the lower ordinate. For 0.85 ’
aw 1.50
p.u. initial kva load at 1.0 pf., the pull-out power is 1.05 per ‘i
5 unit and the field current is 1.72 per unit as found by follow-
0 1.25
ing the dotted arrows. See text regarding accuracy of curves.
0

should be operated so as to maintain the field current high


enough above the value indicated for the load being carried
to provide sufficient pull-out margin. Methods of control-
ling the minimum excitation under voltage-regulator con-
.25 trol and assuring sufficient field current for all kilowatt
loads are discussed in Chap. 7.
Estimating Curves-The ASME-AIEE standardized
PULL-OUT POWER IN PER UN11 designs of turbine generators are described in Chap. 6.
Fig. 23-Variation of pull-out power as generator field current These generators are designed for a rated power factor of
is changed; calculated by Potier-voltage method with infinite 0.85 and a nominal short-circuit ratio of 0.80. The curve
bus voltage Er= 1.0 per unit. in Fig. 24 has been prepared for the purpose of quick-esti-
Chapter I3 Power-System Stability Basic Elements of Theory and Application 453

mating the pull-out power for these machines. The pro-


cedure for using the curve is explained in the caption.
In using the curves of Fig. 24, the conditions for which
they are plotted should be considered. The upper curves
of kva vs. held current for various power factors are plotted
for 100 percent generator terminal voltage. The lower
curves of pull-out power vs. field current for various ex-
tcrnal reactances arc plotted for 100 percent voltage on
t,llc infinitje bus. The infinite-bus voltage and generator
terminal voltage are equal only when the external reac-
tance 2, is zero. Therefore, the curves give correct results
,vllen the generator is connected directly to the infinite
1,~s with no external reactance and with the terminal
voltage at rated value. Fig. 2.5-Vector diagram of salient-pole generator for tran-
For values of external reactance other than zero, the sient stability.
gcncrntor terminal voltage is more or less than 100 percent,
&pending on the power factor of the load current. The E, I-Terminal voltage and armature current (phase-to-neutral).
upper curves do not give the correct value of field current
for these conditions, but the results are of acceptable ac- Ei,t--Internal voltage, the voltage back of direct-axis transient
curacy for small variations in generator terminal voltage. reactance zd’.
‘The pull-out power obtained for conditions with external Ed’-Voltage due to flux in the direct axis.
reactance, however, should be considered as approxi-
O-Displacement angle between rotor position and terminal
mations.
voltage.
The curve is also closely applicable for quick-estimating
the pull-out power of turbine generators in general, espe- #-Displacement angle between internal voltage and terminal
cially those having normal characteristics. If the per-unit voltage.
field current is determined for the load being carried, the
lower set of curves of pull-out power vs. per-unit field cur-
rent can be used to determine the pull-out power with in-
creased accuracy for non-standardized generators. the same as the direct-axis transient reactance, but for lam-
inated rotors it varies from approximately 50 percent
IV. TRANSIENT-STABILITY CALCULATIONS- greater than the direct-axis transient reactance to a value
TWO-MACHINE SYSTEMS approaching the quadrature-axis synchronous reactance.
To generalize on the quadrature-axis transient reactance
In this part, system components entering into transient- of turbine generators is impractical because of the complex
stability calculations and the step-by-step method of mak- character of the magnetic circuits in such machines.
ing transient-stability calculations are discussed. The power-angle curve, used in transient-stability stu-
dies of systems with salient-pole machines, consists of a
15. Effect of Saliency on Transient Stability fundamental component and a second-harmonic com-
The transient performance of a system containing sali- ponent. From Eq. (9) when modified for transient condi-
ent-pole machines can be calculated by the two-reaction tions, since x4’ is greater than xd’, the maximum power iS
method discussed in Chap. 6. A vector diagram for the seen to occur for angles greater than 90 degrees. This con-
t\vo-reaction method expressed in circuit notation is shown dition is to be contrasted with that shown for steady-state
in Fig. 25. This is the most commonly used diagram since conditions using synchronous reactances. The difference,
in stability studies salient-pole machines are usually en- of course, follows because the sign of the second-harmonic
rountered and for these the quadrature-synchronous and term is dependent upon the difference between the direct-
tllc quadrature-transient reactances are equal, i.e., 2, =x4’. and quadrature-reactances as Eq. (9) shows.
‘Ihe power output can be expressed in terms of the ter- In stability studies it is rather difficult to carry out ana-
minal voltage, current, the angle 0’, and Ed’, which cor- lytical calculations using the two-reaction method* on sys-
responds to the actual flux in the direct axis, The expres- tems with more than two machines. As a practical matter,
sions are identical with those given in Eqs. (5) to (13) in- it is sufficiently accurate to use a method based on the
clusive, with the exception that transient reactance xd’ round-rotor theory in which the machine is represented by
must be substituted for synchronous reactance xd and that the direct-axis transient reactance and an internal voltage
Ed’ must be substitut,ed for Ed. equal to the terminal voltage plus transient-reactance drop
The range of transient-reactance values is given in Table for the condition immediately preceding the transient.
4 of Chap. 6. In salient-pole machines the quadrature-axis This transient-reactance drop and the corresponding in-
transient reactance is considerably higher than the direct- ternal voltage Eint are shown in Fig. 25. Under ordinary
axis transient reactance. conditions, there will not be any large difference in the
For commercial salient-pole machines the ratio of x,’ to magnitude of the internal voltage Eint and the voltage Ed’
‘d’ is usually greater than 2.0. For turbine generators the due to flux in the direct axis. Consequently, the funda-
quadrature-axis transient reactance is for solid rotors about *See Sec. 37 of this chapter for a discussion of such a method.
454 Power-&stem Stability Basic Elements of Theory and Application Chapter 13 i

Eg’ 1.120 Xt=0.06 INFINITE


Xi= 0.254 x,=0.547 INERTIA
x;, * 0.400 SYSTEM
xt XL xt j 0.6
3
z 0.7
5
K 0.6
5
g 0.5
1.60 dl-, 0.4

z 0.3

P
0.2

‘0 0.1 (x2 0.3 0.4 0.5 0.6 CL? 0.6 0.9 1.0
MAXIMUM PERMISSIBLE SWITCHING TIME-SECONDS.

Fig. 27-Effect of saliency on permissible switching time-


simultaneous clearing of line-section with double line-to.
ground fault at sending end of system shown in Fig. 26.

A-Two-reaction theory.
B-Round-rotor theory.
3
ANGLE IN ELECTRICAL DEGREES

Fig. 26-Effect of saliency on transient stability for system of the duration of fault using both the round-rotor and two-
shown in insert with both lines in service.
reaction methods. These curves show that there is little
A-Power-angle diagram based on initial load of 0.833 per unit- difference in the stability limit or the permissible switching
two-reaction theory. time, but the values are somewhat greater when calculated
B-Power-angle diagram based on same initial load-round-rotor by the two-reaction method. If salient-pole machines were
theory using same direct-axis transient reactance and cor- used at both ends of the system, the effect of saliency would
responding internal voltage. be of greater importance. However, for the majority of
problems the round-rotor method is satisfactory because it
mental component of the power-angle curve is substan- gives a conservative stability limit and is preferable be-
tially the same in magnitude whether the round-rotor cause the calculations are much simpler.
method or the two-reaction method is used.
Consider a simple transmission system*, such as shown
in the insert of Fig. 26. Power-angle diagrams for this sys-
tem have been calculated by the round-rotor and the two- 16. Effect of Saturation on Transient Stability
reaction methods using the same values for zd’ in the ma- Machine saturation affects transient stability by reduc-
chine and for the renctances of the remainder of the sys- ing the magnitude of transient reactances. As brought out
tem. These power-angle diagrams for initial machine- in Chap. 6, the unsaturated transient reactance is rarely
conditions corresponding to a steady transmitted load of useful. The two commonly available and useful values of
0.833 per unit are shown in Fig. 26. In this case there is a transient reactance are (1) the “rated-current value” ob-
difference of one percent in the power limit, the larger be- tained by short-circuiting a machine at the appropriate
ing obtained by the two-reaction method. The areas in the reduced excitation, and (2) the “rated-voltage value” ob-
power-angle diagram for the initial output of 0.833 per unit tained by short circuiting the machine from no load but
are somewhat greater for the two-reaction method than for with excitation corresponding to rated voltage. The dif-
the round-rotor method. Furthermore, with the two-reac- ference in these reactances results from saturation arising
tion method an appreciably greater percentage of this area from the difference in excitabion, the higher value being for
occurs at a greater angle than with the round-rotor meth- the lower excitation. The rated-voltage value is the one
od. The power-angle curves show that the round-rotor commonly used for short-circuit calculations and, there- i
method gives a conservative stability limit for the usual fore, is generally available. Actually the variation in the j
transient conditions. This is illustrated by Fig. 27 which value of transient reactance caused by saturation is not ;
is based on the system of Fig. 26 subjected to a double line- large and it is preferable in stability studies to use a con- i
to-ground fault at the sending end. In this figure two servative, that is, the higher value. It is possible to include d
curves are given for the stability limit plotted as a function the effect of saturation in the estimate of the transient re-
*This is identical with the system used in the single-machine actance corresponding to the particular excitation and of +
problem, Sec. 24. armature current as discussed in Chap. 6. Practically,
Chapter I3 Power-System Stability Basic Elements of Theory and Application 455

however, there is little difference for the ra:ge of currents


commonly encountered. For this reason it is usually suffi-
ciently accurate to use the “rated-current value.”
17. Dynamic St ab i 1i t y with Automatic Devices
When synchronous machines are operated with voltage
reglilators, the stability limits of the system are impor- t REGULATOR t
tantly changed from the values which obtain for hand
control. This phenomenon has been designated “dynamic zj100t-++q--~
stal~ility with automatic devices.” Dynamic stability on DYNAMIC STABILITY LIMIT WITH
oo\ver systems is made possible by the action of voltage ATIC VOLTAGE REGULATOR
rcgtilators that are capable of increasing or decreasing flux
within a machine at a faster rate than that caused by the
&em in falling out of step. When the inherent stability
limit is exceeded, both the mechanical system and the elec-
trical system are maintained in a continuous state of oscil-
l:ltion through the development of restoring forces equal to
,)r greater than the disturbing forces. 0
This conception of dynamic stability was first recognized
1)~ E. B. Shand, but at the time it was not thought to lie LINE REACTANCE
\\ithin the range encountered with commercial equipment. PERCENT OF GENERATOR OR MOTOR RATING
Subsequently, Evans and Wagner* demonstrated by ana- Fig. 28-Comparison of stability limit with automatic voltage
lytical methods and by miniature-system tests that sub- regulator and limit with fixed excitation or hand control.
stantial improvement in stability limits could be obtained Shows gain due to “Dynamic Stability.”
hy making use of this phenomenon. Their tests, reported
in 1926, showed that the stability limits of a transmission bility,s reference should also be made to the second part
system with a 200-mile transmission line could be increased of Sec. 47 under Excitation Systems.
25 percent by this method. Later Doherty’ and Nickle
made tests for the special and rather academic condition 18. Hunting of Synchronous Machines
of two machines directly connected, which showed that The hunting of synchronous machines can arise from
the limits could be increased about 300 percent by the phenomena closely related to system stability. In the
same means. These two tests are actually quite compara- early stages of power-system development it was difficult
hle when the effects of line reactances are considered. to differentiate between hunting and instability. The
Dynamic stability with automatic devices can be con- term “hunting” is now commonly restricted to two phe-
sidered as a problem in transient stability, making use of nomena, which may be designated as
the machine air-gap flux and a reactance intermediate
hrtween the familiar synchronous and transient react- (1) Hunting from spontaneousaction, and
(2) Hunting from pulsating torques.
:mces. With ideal excitation systems, that is, with volt-
age regulators without time lag, with high frequency The first of these phenomena was observed in connection
of operation, and with unlimited exciter range and re- with the operat,ion of synchronous converters when sup-
sponse, the stability limit would be determined by the plied over “shoe-string lines.” It was found that the
transient reactance. From a practical standpoint the ex- hunting could be overcome (1) by limiting the resistance
citer response is not sufficiently fast to approach closely drop of these lines to a certain percent of the total react-
the ideal condition. More important, however, is the in- ance drop, or (2) by the use of suitable damper windings.
ability of the regulator to approximate the ideal charac- Spontaneous hunting is still encountered occasionally,
tcristics because of the time delay and the finite steps of principally in connection with high-resistance lines or in
regulator action, and delay in the anti-hunting feature, connection with series capacitors as a result of which the
‘lhis provides a definite limit to the increase in the stabil- resistance sometimes becomes relatively large through the
ity limit resulting from regulator action. Nevertheless, for neutralization of inductive reactance. The phenomenon
the system consisting of two machines, as described in of spontaneous hunting is now well understood, and the
Icx. 1 of Sec. 13, operating at equal excitation and con- conditions under which it can occur can now be expressed
stant terminal voltage under the control of a voltage regu- in mathematical form.lg
l:itor, the stability limit was raised with automatic devices The hunting that results from pulsating torques is a
from 52 to 183 kilowatts. The importance of the increase phenomenon which today is of much less importance than
in stability limits due to the operation of automatic de- it was when reciprocating types of prime movers were
vices is, of course, greatly reduced when appreciable react- used. These pulsations have been minimized by the use
Linceis introduced between the sending and receiving sys- of greater inertia and the use of damper windings. The
tems. For esample, Fig. 28 shows the effect of introducing development of the continuous-torque prime movers of
line reactance between the two machines just described. the turbine type for both steam and hydro-electric instal-
For a discussion of operation in the zone of dynamic sta- lations substantially eliminated the problem in
-1 ._ connection
‘Keference5; test results reported in closing discussion. with these prime movers. At present the problem is occa-
456 Power-System Stability Basic Elements of Theory and Application Chapter 13

sionally encountered in connection with Diesel-engine sired block. A governor under such a setting is, of course
prime movers or with certain types of pulsating loads. operative to limit overspeed, the control becoming effecJ
The phenomenon may be analyzed by methods outlined tive at a frequency slightly above the normal frequency,
in this chapter for a study of transient”stability by using Governors are rclativcly slow in action with respect to
the known pulsating-torque characteristic of the prime the time elements which are important from the stand-
mover or of the load, and the electro-mechanical equations point of power-system oscillations. For this reason gov-
or the electric-circuit equivalents. ernors are usually not important from the Standpoint of
transient stability. In the case of hydra-electric plants
Natural Frequency of Synchronous Machines*-- because of the large amount of energy stored in the lvate;
The natural frequency of undamped electro-mechanical column it is impracticable for the governor to limit rap-
oscillation for a synchronous machine connected to an idly the prime-mover input, although by-passing action
infinite bus and shaft-connected to reciprocating machin- can be effected more rapidly. Proposals for faster action
ery is given by have been made, but by-passing arrangements as built
are too slow to be beneficial from the standpoint of sta-
(34) bility. In the case of steam turbines, there is somelvhat
greater possibility of control. However, in many plants
lvherc
the amount of energy stored in the steam in the piping
fn = Sntural frequency in cycles per minute. and various high- and low-pressure units, limits the bene-
n=Speed of machine in revolutions per minute. fits that might be obtained.
PI = Synchronizing power as defined below. Governors, however, have an important effect on
f = Frequency of circuit in cycles per second. steady-state stability as a result of their control of the
WR2=Moment of inertia of synchronous machine and division of increments of load among the various gener-
shaft-connected prime mover or load, in lbs-ft2. ating units. It is necessary, therefore, to give consider-
The synchronizing power is the power at synchronous ation to the actual distribution of the incremental load
speed corresponding to the torque developed at the air gap when the stability limit is being approached. Further-
between the armature and field. The synchronizing co- more, where loads and generating equipment are distrib-
efficient P, is determined by dividing the shaft power in uted throughout a network, a large difference of phase is
kw by the corresponding angular displacement of the rotor sometimes introduced between the principal generating
in electrical radians. Pr, therefore, is expressed in kw per stations on the system. Under such conditions a system
electrical radian. The displacement angle of the rotor for fault can sometimes produce a severe oscillation and re-
a given current and power factor is sult in instability. Such a condition can be avoided by
controlJ8 of the phase angle between the machines so as
Ix, cos c#I
6 = tan-’ to limit the initial angle between principal generating
Et+?xc, sin 4 stations to a safe value for the initial condition, that is,
n-here prior to the fault.
6 = Rotor displacement angle in electrical radians. Governors may introduce a disturbing factor and tend
f= Per-unit armature current. to produce hunting and even loss of synchronism. This
E, = Per-unit armature terminal voltage. condition produced by governor action is identical with
4 = Power-factor angle. the other forms of pulsating disturbances applied to a
x, = Per-unit quadrature-axis synchronous reactance. system and discussed in Sec. 18, Hunting of Synchronous
The value of P, determined by this method is quite gen- Machines. The adjustment of the governor is an impor-
erally applicable for predicting operation at full load, tant factor in preventing any tendency toward hunting
particularly where the amplitude and frequency of the action. The time lag of the governor and its natural pe-
power pulsations are low. The value of P, at no load with riod of movement, if closely related to that natural period
the field excitation corresponding to normal open-circuit of the system, can contribute to hunting action.
voltage may be taken as normal rated kva divided by zq. If a machine pulls out of step with the remainder of
The variation of P, from no load to full load is approx- the system, the governor is called into action by the over-
imately linear when the terminal voltage and power factor speeding of the machine. The slipping of poles produces
are held constant. a pulsating disturbance of low frcquency15, which the
governor can or cannot follow, depending upon its adjust-
19. Governors ment. For this reason radically different results can be
At present, prime movers for waterwheel and turbine obtained when two generally similar generators pull out
generators are under the control of governors that rc- of step. There is, therefore, some advantage in adjust-
spond to variation in speed or frequency. Some prime ing governors so as to minimize the resulting disturbance
movers are operated on a mechanically-limited valve to the system in the event of the machine losing sYn-
opening or LLblock” and an adjustment of the governor for chronism.
that particular unit to regulate for a frequency somewhat
above the system so that the unit operates to give the 20. Calculation of System Oscillations
maximum prime-mover input corresponding to the de- The electro-mechanical oscillations produced by a tra*-
*American Standard for Rotating Electrical Machinery, ASA, sient disturbance on a two-machine system are very corn- <
C-50, 1943, page 28. plicated. The formal mathematical solution of these OS-,
Chapter 13 Power-System Stability Basic Elements of Theory and Application 457

cillations is not possible as even the simplest cases involve 21. Use of Angle-Time or Swing Curves
elliptical integrals. The solution, however, can be ob- Angle-time or swing curves may be calculated by means
tained to any desired degree of accuracy by step-by-step of the step-by-step procedure discussed in Sec. 23. These
approximate methods discllssed subsequently in Sec. 23. curves show the angular position of the rotor(s) plotted
The relations of the principal variables can readily be against time measured from the inception of a fault. Fig-
visualized by curves that give the acceleration, velocity, ure 36 is an example of an angle-time curve.
and displacement as a function of time. For this purpose If a two-machine system is subjected to a switching
it is convenient to think of an oscillation for \\hich the transient as shown in Fig. 6, it is possible to deter-
change in power and angle are Iinearaas shown in Fig. mine by the “equal-area method” previously discussed.
29 (a). The time v:arintion of acceleration, velocity, and \&ether the system is stable. This answer, it will be
noted, would be obtained without a knowledge of the
time variation of the various elcctro-mechanical quan-
tities. Similarly, if a two-machine system is subjected to
a transient disturbance involving a fault with subsequent
clearing, as illustrated in Fig. 7, it is also possible to
determine whether the system is stable. In this case
Vi I \
. ANGLE
the duration of the various fault conditions must be es-
pressed in terms of the angular swing. From a practical
standpoint such information is not generally available be-
cause faults are cleared as a function of time measured
from the application of the fault. Determination of this
time requires solution of the electro-mechanical oscilla-
tion. Examination of the angle-time curves for a par-
ticular system subjected to a specified disturbance not
only establishes whether the system is stable, but if
stable it provides some basis for estimating the margin
of stability as well. The angle-time or “swing curves” also
provide a basis for estimating the magnitude of the
voltage, current, power, and other quantities throughout
the disturbance, which information is frequent,ly of great
value in circuit-breaker and relay applications.
The determination of angle-time curves is carried out
by approximating methods either analytically or with the
+,-INITIAL ANGLE aid of the a-c network calculator. The essential parts
of these methods are the same, since calculations in both
TIME cases are carried out by step-by-step methods. In this
Fig. 29-Graphical sofution of system oscillation
method small intervals are taken so that the accelerating
forces can be assumed constant within the interval. On
displacement are given in Fig. 29 (b) to (d). For the this basis it is a simple problem in mechanics to deter-
case chosen the quantities plotted are simple sine and mine for each step the change in position of the rotor of
cosine curves. Simple relations exist between these curves each machine as a result of the accelerating or decelerat-
that can be derived from the basic laws of motion. Thus ing forces, the inertia of the machine, and the duration
the change in velocity is proportional to the square root of the interval.
of the integral of the acceleration-angle curve, and the
(lisplscement is a function of the integral of the velocity 22. Inertia Constants and Acceleration
Curve.* By means of the methods previously described, it is
For the practical cases the simple trigonometric rela- possible to reduce the electrical input or output of each
tions do not hold because the power-angle relation is not machine to a simple power-angle curve or a simple trigo-
linear. However, curves similar to those of Fig. 29 (b), nometric expression with the angle between internal emf’s
(c), and (d) can still be plotted, and they will help to give as the variable. The accelerating power depencls upon the
2 Picture of the variations in these quantities. initial operating condition and upon the difference between
input and output, including the effect of losses. Thus, for
*These relations provide the basis for a graphical method proposed a generator the accelerating power, which is the variable
‘1~’Skilling and YamakawaJ8 for obtaining velocity-angle and time- AP, is
W$e curves. This method has certain advantagesin comparison AP=Pi-(Po+L) (35)
\Gth a step-by-step method from the standpoint of formal mathe-
where Pi is the mechanical input, PO is the electrical out-
lllatical presentation. It can readily be used to provide a check on
the suitability of interval used in step-by-step analysis, since velocity
put, and L is the total loss. In the case of a synchronous
is Ilroportional to ttw squaw root of t,heintegral of the acceleration- motorthe equation is similarin meaning, but the numerical
Wle curve. The method is not applicable to a system with more sign of the accelerating forces is negative ivhen the input
than two machines and for this mason has not been presented in is less than the output plus the losses. Losses are, however,
detail. often neglected.
458 Power-System Stability Basic Elements of Theory and Application Chapter 13

The inertia of synchronous machines varies through a - 1st.-z-f’d--y


wide range depending principally upon the capacity and fG----. aI a*
speed and upon whether additional inertia has been in- P a+
tentionally added. Fortunately, however, the constants E I
vary through a relatively narrow range if they are es- 2
w
pressed in terms of the stored energy per kva of capacity. ii I
II
The relation between the stored energy constant*, IT, and s II II
WZZ*is given by the following equation: a,-‘0
H = kw-sec = 0.23 1 (WR2) (rpm)‘X lO+ 0 I At 2At 3A1
(36)
kva kva
where WR2 is the moment of inertia in pounds-feet
squared, and rpm is the speed in revolutions per minute.
The inertia constants vary through a range of from less .)b’2
than one to about ten kilowatt-seconds per kva, depending
upon the type of apparatus and the speed. Since control
of the inertia is one of the possible methods of improving
the stability of the system, the subject of inertia constants
is discussed at some length under the first part of Sec. 47
dealing with measures for improving system stability. TIME
Reference should also be made to Chap. 6, Part XIII, for
?I I I I
further information on inertia constants which can be used
in preliminary work or in the absence of specific information
applying to the machine under consideration.
Frequently it is convenient when neglecting loss to re-
place a system of two machines, each with finite inertia, by
another system consisting of one machine with an equiva-
lent inertia and a second machine with infinite inertia. I
0 At 2A1
1
3At
By this means the problem is reduced to that of a single-
machine system.5 If the stored energies of the machines tco 120 TIME
- -
are (H,kva,) and (N,,kva,J, then the equivalent inertia Fig.30--Step-by-step solution-detailsof method for approx-
constant for one of them, Hest3.)is given by imating acceleration, velocity, and angle changes.
HZ NOTE: For computing velocity at the end of an interval, it is
H es(n)= necessary to add a correction term to include change it1
H,kva, (37)
I+----- velocity from the middle to the end of the interval as shown
H,,kvnb by V, for the third interval.
In this method the acceleration, velocity, and phase rela-
tion of the selected machine are obtained in relation to the many ways, depending upon the particular set of assump-
other machine as reference. When losses, intermediate tions used to minimize the error resulting from the appros- j
loads, or more than two machines are involved, it is neces- imation. The following procedure is the one we have found
sary to use the more general method whereby the absolute to be the most suitable for transient-stability studies using
acceleration, velocity, and phase relation for each machine the a-c network calculator. In studying the step-by-step
are separately determined as discussed in the following method, it is suggested that consideration be given first
section. to its application to a single-machine system, that is, a
With the inertia constant, H, and the accelerating or two-machine system for which one machine is of infinite
decelerating power, AP, it is possible to compute the ac- inertia. Reference should be made to Fig. 30, which shows
celeration by means of the following important formula: for a particular machine the variation of acceleration, ve-
locity, and angle of rotor with respect to the other machine
(38) which is assumed to be of infinite inertia. The method
upon which this figure is based can readily be modified to
where cr is the acceleration or deceleration in electrical apply to the general case of two machines of finite inertia
degrees per second per second, f is the system frequency by making allowance for the changes in the positions of the
in cycles per second, AP is the kilowatts available for ac- rotor of the other machine. The calculations are arranged ‘,.?
celeration (or deceleration), H is the inertia constant in in tabular form as shown in Table 2. Two similar tabula: A
kilowatt-seconds per kva as obtained from Eq. (36). tions are required for a two-machine system, one for each
machine. The calculation for a particular machine is tied
23. Step-by-Step Procedure in with that for the other machine by means of Column 11
The step-by-step procedure2,5**2,36
can be carried out in of the tabulation, which is obtained from Column 10 of the
*The formulas for acceleration and inertia constants are based on tabulation for the other machine. If one of the machines
the forms presented in the “First Report of Power System Stabil- is assumed to be of infinite inertia, the problem reduces
ity,” Reference 33. that of a single-machine system, and only one tabulation
Chapter 13 Power-System Stability Basic Elements of Theory and Application 459

TABLE~-SUGGESTEDFORMFORSTEP-BY-STEP ANGLE-TIME
CALCULATIONS
Machine Nos. Total Kva
Machine, WR* = lbs -it2
H= stored energy, kilowatt-seconds per kva.
lWf)(AP)
Acceleration, a= = kAP, degrees per second per second
(If) (ha)
l8Oj
-=
k=(H)(kva)
P MWh.= kilowatts, mechanical input

(5) ( (6) / (7) / (8) (9) (10) (11) w


Angular Angular
Vel. Change for Change
Accel., LY Accel. Velocity Angle Final
change, Machine for
Degrees per Time @, Time ilngle
Aa, Under Con- Other
Set per Incre- Degrees Incre- 4
Degrees sideration, Machinr
Set ment per Set ment Degrees
per Set AO, As’,
Degrees Degrees

(51X (6)) (7) +(8),-I (8) x (9) ** (2)+(10)+(11)

0.0 00 PO Pnreell.--PO /iaPo =an+ Al/2 w,Al= A& Ae,' eo+~eI+~e~‘=ol


0.1 01 Pl PMMech.-PI kAP, =a~ AI w,Al = A82 Ae,' e, + As2+ Ao?’ = o2
0.2 02 p2 PM& -P1 LAP? =crp AL waAt = A& A03 oz+ae3+ho31 =e3
0.3- 03 PJ- PMieCh. -P:,- izAP,- = cc- At/2
--- _
0.3+ 03 p3+ P.Mech.- P 3+ kAPa+ = a~+ Al/2 call= AOr Aea‘
0.4 04 PC PMeeh. - p4 kAP, =a, At asAl= Ae5 Aef,’
0.5 Or.
SW Fig. 30 for meaning of a!, W, Aw, 0 and A0 terms.
‘Losses are of.ten neglected where they are small compared to the machine output during the fault.
**These values obtained from similar tabulation for other machine.

required, as AfY, the angular change for the other machine, the acceleration (~1through the interval At. This velocity
can be taken as zero. is then used to compute the change in angle taking place
In Fig. 30 three intervals in the step-by-step method are through the second interval, which is equal to the velocity
shown, and a circuit change is assumed to take place at the w2 times the increment of time At.
end of the third interval. The velocities ~1, WZ,and wg are This process is repeated for each step throughout any
assumed to remain constant through the corresponding period for which the circuit is not changed or for which the
three intervals. The acceleration on the other hand is same time interval is used. If there is a change of either
assumed to remain constant from the middle of one inter- condition, it is necessary to compute a velocity correction
val to the middle of the subsequent interval. By this means term since, as pointed out previously, velocities are com-
acceleration is chosen to be alternately greater and less puted for the middle of the interval while acceleration and
than the actual value as shown by the plotted curve. Such angular displacement are computed for the end of the
an arrangement is used to minimize the cumulative error. interval. For the case illustrated in Fig. 30 the circuit is
The initial acceleration CV~+
is computed from the power assumed to be changed at the end of the third interval.
flow corresponding to the phase position at the beginning Consequently, it is necessary to add a correction term K
of the transient disturbance which takes place at t =O. to the velocity WQto obtain the velocity at the end of the
This acceleration is then used for half of the first time third interval as shown in the figure.
interval At to determine the velocity wl which is assumed The fourth and subsequent intervals can be computed
throughout the interval. The angular change A& for the as for the first and subsequent intervals. To distinguish
Particular machine is then computed from the average between the acceleration rates corresponding to the be-
velocity during the interval. Similar calculations are then ginning of an interval or the end of the preceding interval,
made for the other machine to determine its angular change the practice has been followed of using plus and minus
4’ during the same interval. The final angle, the angle signs respectively. This procedure has been applied to the
01, at the end of the first interval, is the sum of the initial case under consideration using the terms ao- and CYWat
angle B. and the angular displacements A& and Aor for zero time. In this case the acceleration cyo- is zero since
the two machines. it is assumed that the system is in equilibrium prior to the
The calculations for the second interval are made in a application of the transient at the time t =O, and the ac-
similar manner. The acceleration 0~1is computed with the celeration CQ+applies upon the application of the transient.
aid of the angle 8r obtained at the end of the first interval. The term cu3- gives acceleration at the end of the third
Next the increment in velocity is obtained by assuming interval prior to the circuit change, and the term OJ~+
gives
460 Power-System Stability Basic Elements of Theory and Application Chapter 13

the acceleration subsequent to the circuit change. Ordi- can he illustrated with the least possibility of confusion.
narily the plus and minus signs should be omitted, and in The single-machine problem is also useful when there are
that case the turm is understood to give the acceleration no intermediate loads, and losses can be neglected, since a
at the end of the interval indicated by the subscript. two-machine problem can then be reduced to a single-
The time interval to be used in the step-by-step analysis machine problem, (Sec. 22). In the single-machine prob-
is a matter of judgment and convenience. In the ordinary lem all resistances and line capacitances are neglected to
stability problem the interval should not be longer than simplify the calculations.
0.1 second, which is a convenient interval since it gives the The two-machine example has been selected so that the
time in an even number of cycles. For some applications sending end is the same for both problems. Both sending
it is desirable to shorten the interval to 0.05 second, which and receiving systems have finite inertia, and rcsist:mces
corresponds to three cycles. The time interval can be are considered. This problem is important because it is
changed from point to point throughout the transient clis- the type most frequently calculated manually. 111~0,in
turbance. For example, during one part of a disturbance using the general two-machine problem, all fundamental
involving some circuit changes there can be little relative considerations affecting system stability in multi-machine
change in angular position, and relatively large intervals systems can be illustrated.
can be permitted. Conversely, other transient conditions
can introduce large changes in angle during an interval.
As a practical matter, the length of the interval should
always be decreased if the change result’s in an angular
swing of 20 degrees to 30 degrees in a single interval. The
velocity-angle curve for two-machine systems can be
plotted and compared with the results of calculation by
the method of Skilling and Yamakawa.3” SENDING END RECEIVING END
The labor of making a step-by-step calculation lvill
Fig. 31---Single-machine system assumed for study.
be reduced greatly by arranging the work in tabular form.
For this reason Table 2 has been introduced. This table
is based on the procedure found desirable in a-c network 24. Description of Single-Machine System
calculator studies and can be supplemented by additional The single-machine system selected for study, shown
columns if this is desirable to facilitate the calculation of schematically in Fig. 31, has the following characteristics:
the output power which in the table is assumed to have
been obtained from the a-c network calculator readings or Transmission Lines:
from calculated power-angle curves. The calculations have Two circuits in parallel, 50 miles long, 10 foot flat spacing=
been arranged so that velocity and acceleration curves 12.6 foot equivalent-delta spacing. Conductors are 250 000
can be plotted readily; this has been found desirable in circular mils, copper. Distance between line centers is 40
a sufficient number of cases as to justify the additional feet and the conductors are transposed. There are no
columns required. ground wires. 50 000 kw at 100 percent power factor is de-
livered to the infinite receiver system. Normal voltage 66kv.
Further det,ails of the step-by-step procedure can be
obtained from a study of the numerical examples. Sending end :
Two 30 OOO-kva,three-phase, 60-cycle, waterwheel gener-
ators.
V. EXAMPLES OF TRANSIENT-STABILITY Unsaturated synchronous reactance zd= 63.8 percent
PROBLEMS Rated-current transient reactance zd’ = 25.4 percent
(Chap. 6, Part XIII)
In the previous sections, the concepts of calculating Negative-sequencere:tctance x2= 28.9 percent
power-system stability are discussed in some detail. TO Inertia constant (kw-sec/kva) H=3
illustrate t.he various salient features of stability calcula- Normal regulators and excitation system.
tions, and to make clear the exact procedure in a specific Transformers:
problem, two examples will be calculated in detail. All of One 60 OOO-kva,three-phase, 60-cycle bank connected as
the individual steps in the calculation are given, so that shown in Fig. 31 at each end of the transmission lines.
one inexperienced in this work can follow the problem Reactance=8 percent. Exciting current is neglected.
readily. To facilitate understanding of the various factors
involved in transient-stability calculations, references are Receiving end:
given to the sections where the theory involved is dis- Low-voltage side of receiver transformers connected to an
cussed, and a considerable portion of the theory is re- infinite inertia system. Receiver low-voltage bus fixed at
viewed. In addition to a thorough knowledge of the fore- 95 percent of normal voltage.
going sections of this chapter, an understanding of machine
characteristics, Chap. 6, is necessary in solving the 25. Circuit Constants
problems. This problem is calculated using the per-unit system.
The first example is a single-machine problem. This was The values given in the illustrations are all in per unit. The
chosen because it is the simplest case met in practice, and base selected is the kva of the sending end, or GO000 kva.
because in its solution the elements of a stability problem Using the formulas in Chap. 10, Sec. 4 to 7,
Chapter 13 Power-System Stability Basic Elements of Theory and Application 461

f = 6~000 - 26. Transient Stability Calculation


Xormal Current ~ = 325 amperes. The most critical type of transient disturbance that
n d/3(66) 1 receives consideration in stabilit,y studies is t,hat arising
Sormal Voltage E, = 5 = 38.1 kvline-to-neutral. I (39) from the application of a fault and the subsequent swit,ch-
I’ ing necessary to isolate the fault. In this problem a zcro-
3S.I x lo” impedance double line-to-ground fault is assumed to take
Xormal Impedance Z, = m-.-i27 = 72.6 ohms.
place at the sending end of one of the transmission lines
as shown in Fig. 31. Both ends of the faulted line are
These values apply to the 66-kv portion of the system. opened simultaneously to clear the fault. The problem is
If the above normal values are desired at any other point to determine the maximum permissible time between the
in the system, the transformer turns ratio should be used inception of the fault and the opening of the circuit
to determine the normal voltage at that point. breakers for which stability can be maintained. The time
The first step in the calculation is to determine the thus determined is not the breaker operating time that
impedances of the different elcmcnts of the system in per would normally be used but the maximum operating time
unit. These values are then put in the network and it is which could be allowed and still maintain stnbilit,y. The
reduced to its simplest form. ability of a system to withstand a double line-to-grolmd
The percent reactance of the generators on 60 000 kva fault is often, but not invariably, taken as the criterion of
is twice the values given, but since the two machines are system stability.
in parallel, the reactance in the networks is halved so the The first step is to calculate and plot power-angle dia-
above values can be used. grams (See Chap. 10; Chap. 13, Sec. 2) for three circuit
Using the methods of Chap. 3, X1 and -YZ of each line conditions: (1) the initial condition immediately prior to
equal 39.7 ohms. X0 equals 138.2 ohms for one line, and inception of the fault, (2) the condition during the fault),
108.2 ohms for the two lines in parallel. The line reactances and (3) the condition after the fault is isolated. Since in
in per unit on GO000 kva at 66 kv are: this case the receiver has infinite inertia, its angular posi-
tion remains fised and it is necessary only to calclllnte
Single Line: power-angle diagrams for the sending end. The equation
Positive- and negative-sequencereactance XI, Xf = 0.547
Zero-sequencereactance xy,= 1.90 relating sending-end power to the known circuit quantities
Two lines in parallel: (See Chap. 9) reduces to the following in this problem
Positive- and negative-sequencereactance X1, Xy,=0.2i-l because losses have been neglected:
Zero-sequencereactance x0 = 1.49 p = _ E-&-It
9 -cos (90”+8) (43)
il definite voltage is usually maintained at certain car- x
dinal points in a system, and in this case the receiver low- in which 0 is the angle between the internal voltages E&
voltage bus is maintained at 0.95 per-unit voltage. The and E,-,. Since the power-angle diagrams are to be de-
sending-end generator terminal voltage is desired, so it is termined for transient conditions, the voltage behind tmn-
convenient to combine the portion of the network between sient reactance EL must be used, and the value of S
the two buses into a single reactance. It is: must he determined using generator transient reactance
Y, = 0.434 per unit XL. The generator internal voltage, or voltage behind
(JO) transient reactance is the vector sum of the terminal volt-
=31.5 ohms.
age of the machine and the voltage necessary to force the
The load delivered at the receiver low-voltage bus is load current through the transient reactance.
.50000 kw (0.833 per unit) at unity power factor. The EC, = 0.95+j0.381+0.877(j0.254)
current in the network is: = 1.12~J~~,~’
per unit
7=0.833 Recause of the times involved in transient disturbances,
-=0.877 per unit (41)
0.95 the internal voltage of the machine is generally considered
= 460 amperes. constant (Sec. 30, and Chap. 6, Sec. 21), so this value of
With this current flowing, the terminal voltage of the Ebs is used for the entire calculation.
sending-end generator is :
E,=0.95+0.877(j0.434)
=0.95fj0.381 (42)
= 1.023 ej?*Oper unit
=39.8~~**” kv line-to-neutral
With the above quantities determined, all necessary
information is available to compute the sending- and
receiving-end power-circle diagrams. This is often done oE&, E
8-R
=
in practical problems in order to determine the initial =I.123 0.95
operating conditions, but in the problem this information Fig. 32--Single-machine system. Network before the fault
is given, so circle diagrams are not necessary. occurs.
462 Power-System Stability Basic Elements of Theory and Application Chapter 13

Before the Fault-The network to be used in calculating would be considered. As the generator internal voltage or
the sending-end power before the fault is shown in Fig. 32. voltage back of transient reactance is assumed to remain
All necessary constants are known, so that, constant, the same voltages calculated for the condition
before the fault apply, and
p 8= - (l~12)(o~g5)cos (go+@
0.688 p sI= J12)(o*g5)cos (go+@
= -1.55 cos (90+0) per unit (45) 2.58
= -0.370 cos (90+0) per unit.
(46)
During the Double Line-to-Ground Fault-The first
step in determining the power-angle diagram during the After the Fault-When the faulted line section is iso-
fault is to reduce the negative- and zero-sequence networks lated from the system, the network to he used for culcu-
to single equivalent reactances to be applied at the point
of fault, (Sec. 10). The constants to be used in the nega-
tive- and zero-sequence networks are known, so these nct-
works can be drawn readily. They are shown in Fig. 33 (a)

j 0.547
jOJ6l

(a)

1 Network after the fault is


L-----J!--- ------ i Fig. 34-Single-machine system.
isolated.
jo.00 jO.0762

(2 LINES) ‘9 m F lating Ps” is that shown in Fig. 34. Using the constants
I N given, the sending-end power equation becomes:
I b)
I
p 8N= _ (1J2)(o.g5)cos (go+@
L--pN_----- ----: 0.957
j 0.547 = -1.11 cos (90fe) per unit. (47)
(cl Power-Angle Diagrams and Limiting Angles-
Equations (45), (46), and (47) are plotted in Fig. 35 as a
function of 0, giving the power-angle diagrams of the
single-machine system for the condition assumed. In-
spection of the diagram or solving Eq. (45) for 0 with
Ps=O.833 per unit shows that before the fault occurs the
system is operating at an angle of 32.3 degrees. The maxi-
mum angle (critical angle of Sec. 4 and 6) to which the
machine can swing, after the fault is isolated, without 10~s
of stability is 131.6 degrees. This angle can be read from
Fig. 35 or calculated by determining the value of 0 between
Fig. 33--Single-machine system. Networks for use during the I.00
double line-to-ground fault.
(a)-Negative-sequence network. 1.60
Ps-BEFORE
(b)-Zero-sequence network. //-k:THE, FAlJ;T
140.
(c)-Network during the fault. /
I I I I/l I I I \I I I I
(d)--Network (c) reduced. L
‘5 1.20 / I I I I\I I I
3
and (b), and to the right of each is the single equivalent “w 1.00 1’
/ I I
reactance to which each network reduces. Since the fault 4-
is double line-to-ground, these two equivalent reactances 8 0.633
0.00
ZE
must be paralleled (Chap. 2, Fig. 21) and connected at the a 0.60
point of fault. This is illustrated in Fig. 33 (c) which finally
reduces to the network of Fig. 33 (d) by a simple star-delta
conversion. With all losses neglected, the sending-end
power is determined by Eq. (43). The shunt branches of
Fig. 33 (d) need not be considered, as they only affect 0
reactive power transfer. If maintained internal voltage 0 30 60 90 120 150
had not been assumed and it was required to consider the &DEGREES
demagnetizing effect of shunt loads, the shunt branches Fig. 35--Power-angle diagrams for single-machine system. ‘-:
Chapter 13 Power-System Stability Basic Elements of Theory and Application 463

90” and 180’ that will satisfy Eq. (47) with P,“=O.833 The second part of the tabulation assumes that the fault
per unit. This is the maximum value that ~9can reach is isolated in 0.15 seconds, since in this time 0 has increased
without the system becoming unstable. If the angle 0 ex- to 57.2 degrees which matches closely the 57 degrees chosen
cccds 131.6’, then the mechanical input to the sending-end as the maximum switching angle to maintain stability in
generator exceeds its electrical output (see Fig. 35), and Fig. 35. The terms -0.15 and +0.15 seconds in column 1
the generator pulls out of synchronism. By the equal-area indicate the increments of time before and after the brenk-
lnethod described in Sec. 6, an angle of approximately 57 ers open. Note the changes in columns 6, 7, and 9 for the
degrees is selected as the maximum angle at which the -0.15 second time. The calculation indicates that sta-
fault can be isolated if stability is to be maintained. bility is maintained, since 0 reaches a maximum value less
Angle-Time or Swing Curves-To determine the than the critical angle of 131.6 degrees. The calculation
time of fault isolation corresponding to 57 degrees, B is is carried far enough to show that 0 begins to return to the
determined as a function of time by a step-by-step method. new operating point.
The method is described in detail in Sec. 23, and a con- The angle-time or swing curves resulting from the step-
venient means of calculating is to use the tabular form by-step calculation are plotted in Fig. 36. Curves A and B
illustrated by Table 2. Such a calculation is carried out in are the graphic plot of the calculations carried out in Table
Table 3, using this form. The first part of Table 3 assumes 3. They show more clearly that stability will be lost
that the fault is not isolated, and the rapid increase in 8 quickly if the fault is not isolated and that stability is
indicates how fast the system becomes unstable under just maintained if the total fault clearing time is not
these conditions. Note that the low inertia constant greater than 0.15 seconds. Curves C and D have also been
(fi=3 kw-sec/kva) of the generators permits them to calculated by the step-by-step method, and show that
change angular position rapidly, so that relatively small stability is lost for fault clearing times slightly longer
time intervals, 0.05 seconds, are chosen for the calculation. than 0.15 seconds.
As previously explained, the velocity is assumed con-
stant over each period, but the acceleration is assumed 27. Assumptions Made in Solving Two-Machine
constant from the middle of one period to the middle of Problems
the next. This is done to minimize cumulative errors. The two-machine problem given below is an example
Column 6 shows how this is done. of the manner in which this problem can be solved by

TABLE ~--STEP-BY-STEP CALCULATION OF ANGLE-TIME CURVES FOR SINGLE-MACHINE SYSTEM


H=3 &8ox6o,36OO
3x1
- -
(1) (2) (3) (4) (5) (6) (7) (8) (9) (10) (11)
AP, Me- Accelern- I
Electrical Accelera- Velocity
Time in Set Angle B at chanical tion, Velocity, Angular 6 Final
Power tion Time Change, A.ngle-Time
:xt.Reginning Beginning Input Minus Degrees Degrees Change, Angle,
of Interval of Interval output, Increment ‘, Degrees 1Increment
Electrical per Set per Second Degrees Degrees
Per LJnit Seconds 1per Second
output per Set
- --
- - - 0.833 - (3) (4) Xk - (5) X (6) - (7) + (8L1 -- - (8) X (9) (10)+w
-_
0.0 32.3 0.199 0.634 2285 0.025 57.0 57.0 0.05 2.85 35.2
0.05 35.2 0.213 0.620 2230 0.05 111.5 168.5 0.05 8.43 43.6
0.10 43.6 0.255 0.578 2080 0.05 104.0 272.5 0.05 13.6 57.2
0.15 57.2 0.312 0.521 1880 0.05 94.0 366.5 0.05 18.3 75.5
0.20 75.5 0.358 0.475 1710 0.05 85.5 452.0 0.05 22.6 98.1
0.25 98.1 0.367 0.466 1680 0.05 84.0 536.0 0.05 26.8 124.9
0.30 124.9 0.303 0.530 1910 0.05 95.5 631.5 0.05 31.6 166.5
0.35 166.5 .,...,.... ... . . . . . . . . .
- - -
Fault Isolated in 0.15 Seconds
-
-0.15 57.2 0.312 0.521 1880 0.025 47.0 320 ... . ...
$0.15 57.2 0.936 -0.103 -372 0.025 -9.3 311 0.05 15.5 72.7
0.20 72.7 1.063 -0.230 -829 0.05 -41.5 269 0.05 13.5 86.2
0.25 86.2 1.112 -0.279 - 1000 0.05 -50.0 219 0.05 11.0 97.2
0.30 97.2 1.105 -0.272 -977 0.05 -48.9 170 0.05 8.5 105.7
0.35 105.7 1.071 -0.238 -858 0.05 -42.8 127 0.05 6.4 112.1
0.40 112.1 1.032 -0.199 -714 0.05 -35.7 91 0.05 4.6 116.7
0.45 116.7 0.996 -0.163 -588 0.05 -29.4 62 0.05 3.1 119.8
0.50 119.8 0.963 -0.130 -460 0.05 -23.4 38 0.05 2.0 120.8
0.55 120.8 0.958 -0.125 -450 0.05 -22.5 16 0.05 0.8 121.6
0.60 -0.117 -420 0.05 -21.0 -5 0.05 -0.2 121.1
0.65 -0.117 - 420 0.05 -21.0 -26 0.05 -1.3 120.1
-
464 Power-System StaDiltty Basic Elements of Theory and Application Chapter 13

100 machine problem. Transformer resistance is included, but


A, generator resistances are not. Including resistance, the
160
transformer impedance becomes I+j8 percent. The line
140. data in ohms using the methods of Chap. 3 arc:
CRITICAL
-,---,- ANGLE -
Single line:
Positive- and negative-sequence
impedance ZI, ZZ= 12.9+j39.7
Zero-sequence impedanc= Z0=27.2+j13S.2
Two lines in parallel:
a, 60 Positive- and negative-sequence
impedance Zi, Z2=6.43+j19.9
Zero-sequence impedance Z0=20.7+j108.2
20 I I I I I I I 1 1
The receiving-end data are:
0’ Generators:
0 0.1 0.2 0.3 0.4 0.5 0.6
Two 62 500-kva, three-phase, GO-cycle turbine generators
TIME-SECONDS Unsaturated synchronous reactance Z,I = 125 percent
Fig. 36-Angle-time curves for single-machine system. Rated-current transient reactance ~,i’= 15.6 percent
A-Fault not cleared. Negative-sequence reactance x2= 9.8 percent
Inertia constant (kw-sec/kva) H=5
B-Fault isolated in 0.15 sec.
C--Fault isolated in 0.16 sec. Shunt load :
D--Fault isolated in 0.17 sec. 115 000 kw at 55 percent power factor located at receiving-
end low-tension bus. Load is represented by a constant
calculation. A number of simplifying assumptions are impedance.
made, most of which are conservative.
The common assumptions are listed, together with refer-
ences from which their effect can be determined.
1. Impedance of the load is constant (Sec. 9). gj-gG&g
2. Effect of saliency is generally neglected (Sec. 15).
3. Negative-sequence loss varies as 7; for all machines (Chap. T v LOAD
6, Part XIII). This assumption is inherent in the method
of symmetrical components (Sec. 10). SENDING END RECEIVING END
4. Rated-current transient reactance is normally used (Chap.
Fig. 37-Two-machine system assumed for study.
6, Part XIII).
5. The losses in generators are sometimes neglected. This is
permissible when the output of the machine during the 29. Circuit Constants
fault is large compared with its losses. Typical generator
resistances are given in Chap. 6. The loss due to the uni- The two-machine problem is also calculated using the
directional component of short-circuit current is discussed per-unit system. The kva base is optional, so for simplicity
in Chap. 6. 60 OOO-kva base is again used.
6. The internal voltage or voltage behind transient reactance
The circuit constants in per unit on 60 000 kva are.
is assumed to remain constant during a transient disturb-
ance (Chap. 6, Sec. 22). Transmission lines :
7. The effect of negative-sequence torque is generally neg- Single line :
lected (Sec. 10). Positive- and negntive-
sequence impedance Z,, Zy=0.177 +jO.543
Almost all of the above assumptions are conservative, zo=o.373 +j1.90
Zero-sequence impedance
and the net effect is conservative. More accurate calcula- Two lines in parallel:
tions can be made by referring to the references given, but Positive- and negative-
this is not usually done because more margin than is ob- sequence impedance Zl, Z2 = O.OSSS+jO.274
tained by these assumptions is necessary for safe operation Zero-sequence impedance Zo=0.28-1 +j1.49
of a system from the standpoint of transient stability.
Generally, the first step in the calculation of a two- Receiving End:
machine problem is to draw the sending-end and receiving- Each Generator:
end circle diagrams, which would be used to determine the Conventional synchronous
operating conditions of a system at the time of a fault reactance 5d=1.20 i
Rated-current transient reactance Q’ =0.15
(Chap. 10, Sec. 21). In this problem this information is x* = 0.094
Negative-sequence reactance ,)
given. H=5
Inertia constant (kw-sec/kva)
28. Description of Two-Machine System Shunt load:
The two-machine system assumed for study is illustrated The shunt load is 1.92 per unit at 0.85 lagging power
in Fig. 37. The sending end is the same as in the single- factor, or 1.92fj1.19 per unit.
Chapter 13 Power-System Stability Basic Elements of Theory and Application 465

Since the machines are in parallel, the above values must The current flowing t’o the load from the receiving-end
be divided by two before insertion in the sequence networks. machines, when they are delivering 1.08+jI.l9 per unit
The capacitance of the two 50-mile transmission lines is power (1.605 per unit power at, 67.4 percent power fnct,or) is
neglected in this problem. This is justified on the basis of
7 po5
calculations that show the line capacitive reactance to be -= 1.69 per unit at Gi.4 percent power factor.
nearly equal in magnitude to the transformer magnetizing R 0.95
reactance, and the latter has also been neglected. Con- I,= 1.14--j1.25 per unit (50)
sideration of line capacitive reactance and transformer =599 -j658 amperes.
magnetizing reactance would add in no way to the prob-
lem’s effectiveness in illustrating a typical stability calcula- 30. Transient-Stability Calculation
tion, nor would it add to the generality of the networks in- In the single-machine problem the most severe type of
volved, since the load introduces a shunt branch. If it is transient disturbance was considered, namely, the applica-
necessary to include these effects, Chap. 3 gives line con- tion of a fault and its subsequent isolation. The same dis-
stants, which may be converted to general circuit (ABCD) turbance is consiclcred in the present problem, and the
constants by Table 9, Chap. 10 or by Chap. 9, Sec. 6. The same zero-impedance double line-t,o-ground fault located
ecluivalent r form is given in Chap. 9, Sec. 6. The appendix at the sending end of one transmission line is used. This is
gives equivalent circuits for transformers, which can be shown in Fig. 37. The circuit breakers are assumed to
introduced into the circuit. open simultaneously to isolate the faulted line, and again
As in the single-machine problem, voltage is considered maximum permissible time between fault inception and
to be maintained at the receiving low-tension bus. The breaker clearing to maintain stability is to be determined.
receiving-end maintained bus voltage is 36.2 kv line-to- Here again it becomes apparent that prompt switching is
neutral (9.5 percent of normal). With voltage maintained imperative if the assumed load is to be carried.
at this point, it is again convenient to combine the net- Before plotting power-angle diagrams for the ‘sending
work between the low-voltage buses into a single set of cir- and receiving ends for the three circuit conditions, (1) be-
cuit constants. These quantities are tabulated in the first fore, (2) during, and (3) after the fault, it is necessary to
four columns of Table 4 in terms of the familiar ABCD calculate the generator internal voltages using the known
constants (See Chap. lo), which are used in this problem terminal voltages, ES and E, and the generator rated-
to facilitate the handling of the network involving shunt current transient reactances (Q’). The sending-end inter-
branches. The ABCD constants for one line plus the trans- nal voltage is:
formers, and for two lines in parallel plus the transformers,
EL,= 1.045+jO.381+0.877 (j0.254)
can be written immediately without further calculation by
f 1.045+jO.G04 per unit
using the quantities given above and Network Number 1
= 1.21ei300per unit 61)
of the tabulated formulas for ABCD constants given in
= 46.2~‘~~’ kv line-to-neutral.
Chap. 10. These two sets of constants are listed in Table 4,
Cols. (1) and (2). Since the load also forms part of the net- The receiving-end voltage behind transient reactance,
work between the points of maintained voltage, it will be remembering that E, is 0.95 per unit volts, is
combined with the constants of Cols. (1) and (2) to give
Ek,=0.95+(1.14--j1.25)(j0.075)
those listed in Cols. (3) and (4), respectively. This is ac-
= 1.044+jO.O855 per unit (52)
complished by using Network Number 10, Table 9,
= 1.048~‘“,~’ per unit
Chap. 10.
= 40+” kv line-to-neutral.
The load at the receiver low-tension bus is 1.92 per unit
at 85 percent power factor, or 1.92+j1.19 per unit. Part Before the Fault-The network for use in calculating
of the total kva is supplied by the sending-end generators the sending- and receiving-end power is shown in Fig. 38.
and part by the receiving-end units. For this problem, it is Since the equivalent circuits of the generators consist of a
assumed that the sending-end station is delivering 50 000 series impedance, their ABCD constants can be written
kw (0.833 per unit) at unity power factor to the load. This down without calculation. These are listed in Col. (5) and
dictates that the receiving-end station is delivering 1.08+ (6) of Table 4. Now using Network Number 16 from the
jl.19 per unit to the load, or 1.08 per unit real power at tabulation of ABCD-constants formulas of Chap. 10, the
67.4 percent power factor. With 0.833 per unit real power ABCD constants for the entire system can be determined.
coming to the load through the network, the current drawn The results are given in Table 4, Col. (7). To illustrate the
through the network is
1 =0.833
- = 0.877 per unit at 100 percent power factor ABC0
s 0.95
(48) TABLE 4 COL.4
xote that this expression is identical to Eq. (41). With the
above current flowing, the sending-end low tension bus
voltage is
&=0.95+0.877 (0.108+jO.434)
= 1.045fj0.381 per unit
=l.ll e jzooper unit (4% Fig. 38-Two-machine system. Network before the fault
~42.5 e izookv line-to-neutral. occurs.
466 Power-System Stability Basic Elements of Theory and Application Chapter 13

method, the B constant is calculated below. Subscript 1


denotes the receiving-end generator; 2 denotes two parallel
lines with transformers and load; and 3 the sending-end
generators.
B=As(B1A*+D1BZ)+B(3(B1C2+D1DZ)
=(l+j0)[(0+j0.075)(1.799+j0.774)+(1+jO)(0.109
+jO.434)]+(O+jO.254)[(O+jO.O75)(2.11-j1.31)
+u+jo)(l+jo>l
=O.Oll +jO.847 = 0.847d~9.20.
The real parts of equations 85 and 86, Chap. 9 can be
espressed in the form:
- --
GJG
i%=z; cos (P-S) -B cos (p+e)
- --

and P,= -Eg $ cos (p-,)+g@ cos (p-8). (54)

Where Ps and_ PR are the sending- and receiving-end


power, Es and ER are their respective internal voltages
from equations (51) and (52), and LY,p, and 6 are the vector
angles of the A, B, and D constants, respectively. Positive
direction of power flow is out of the sending-end generators A=l+jO
and into the receiving-end generators.
PS and PR for the condition before the fault can now
be calculated.
P*= (1.21)$g cos (89.2”-8.2”)
0.00996
A=l.672+jO.617
_ W1)U.@@) cos (89 20+81 E =0.099+)0.354
0.847 C= IZ25-i30.2
D= 7.65-jO.961
=0.300-1.50 cos (89.2”+8) per unit. (55)
(e)
PR= -(1.048)$$ cos (89.2”-31.5)

+(1’21)(1’048) cos (89 20-o)


0.847
= -1.73+1.50 cos (89.2”-(Y) per unit. (56)
During the Fault-As in the single-machine system, Fig. 39-Two-machine system. Networks for use during the
the negative- and zero-sequence networks must be deter- double line-to-ground fault.
mined, reduced to single impedances, and applied at the (a)-Segative-sequence network.
point of fault. Both of these networks can be readily (b)-Zero-sequence network.
constructed as all of the circuit constants are given in (c)-Complete network during the fault.
Sec. 29. The negative- and zero-sequence networks are (d)--First reduction of complete network.
shown in Fig. 39 (a) and (b), and at the right of each the (c)Second reduction of complete network.
(f)-Final reduced network during the fault.
single equivalent impedance that represents the network
is shown. Because the assumed fault is double line-to-
ground, the two single impedances representing the nega- branches consist of the impedances representing the load
tive- and zero-sequence networks must be paralleled before and the fault, both of which are taken directly from Fig.
they are applied to the point of fault (Chap. 2, Fig. 21). 39 (c). The center unit is found by paralleling the two
The complete network for use during the fault is shown in transmission lines and adding the receiving-end trans-
Fig. 39 (c), which includes this resulting shunt impedance. former impedance. The latter renders one series imped-
It is now necessary to reduce the network of Fig. 39 (c) ance for which the ABCD constants can be written without
to one set of circuit constants before the power equations calculation. The network of Fig. 39 (d) is thus complete,
can be solved. To do this involves a rather general usage and the next step is to simplify this network to that shown
of ABCD constants and the necessary steps will be in- in Fig. 39 (e). This step combines the two shunt branches
dividually traced. The first step is to obtain the network of into the general circuit constants and can be performed
Fig. 39 (d), which is readily accomplished. The sum of the by using Network Number 12 of the table of formulas for
sending-end generator and transformer impedances form ABCD constants given in Chap. 10. Before using Network
the left-hand branch, the receiving-end generator imped- Number 12, the two shunt branches must be converted+;
ance alone forms the right-hand branch, and the shunt to admittances by taking the reciprocal of the know*
Chapter 13 Power-System Stability Basic Elements of Theory and Application 467

TABLE &-CIRCUIT CONSTANTS FOR TWO-MACHINE SYSTEM

(1) (2) (3) (4) (5) (6) (7) (8) (0)


One Line Two Lines Sending- Heceiving-
One Line TWO Lines System System System
with with End End
with with Before During Aft,er
Transformers Transformers Gener- Gencr-
Transformers Transformers The Fault The Fault The Fault
and T,ond and Load ators ntors

1 +jO 1 +jO 2.34+j1.24 1.7nn+jo.774 1 +io 1 +jO 2.13+j1.307 11.8O+j6.06 2.tii+j1.771


<JO ,io 2.66cjz7-’ 1.955cj23J ,jO ,iO 2.5Oe’3’,5 13.34s’?7.0 3.21c1a3.b
_
0.197+jO.708 O.lO!I+jO.434 0.19i+jO.i08 O.lOS+jO.434 O+jO.254 0 +jO.OT5 0.011 +jO.847 0.0413fj3.78 O.ON-bjl.l6l
0.735P’ 0.448sj75.9 O.i35ej”.’ 0.448~i’~.~ 0.254dgo 0.075ei9o 0.847~1*~.~ 3,7<)ei89-3 l.lF2C’*“.8

2.11 -j1.31 2.11-j1.31 0 0 2.11 -j1.31 17.25 -j30.2 2.11 -j1.31


0 0 2,#c-j31.R 34,iC-iRO’?
2.48~-~~‘,” 2.48c-~~‘,” 2,~8e-i31-8

1 +jO 1 +jO 1 +jo 1 +jo 1 +.io 1 +jO 1.098+jO.1583 9.91+jO.331 l.OOS+jO.1583


,io El0 ,io ,jO ,io .io l.llOei8.2 O.Dlei’~g l.llOciS.’

impedances. The fault and load branches expressed as


ABCD
admittances are, respectively: TABLE 4 GOL.3
1
Ys= =2.3G-j18.14 per unit (57)
0.00706+jO.O542

1
Ya= = 2.11 -j1.31 per unit. (58)
0.34O+jO.211
Kow the network of Fig. 39 (e) is complete, and it re- Fig. IO-Two-machine system. Network after the fault is
isolated.
mains only to combine the two series impedances with the
central set of circuit constants, and Fig. 39 (f), the final
reduction, is determined. This simplification is performed PSI’= (l.21)‘s2 cos (86.8”-8.2”)
by using Network Number 16 from the table in Chap. 10
referred to above. The sample calculation of the B con- -0.W1.048) cos ~86,80+o~
stant, for the network used before the fault, will illustrate 1.162
the method. Col. (8) of Table 4 gives the final circuit =0.276- 1.09 cos (86.8”+8) per unit. (61)
constants for use during the fault. Using these circuit
constants and the previously calculated internal voltages, Pa”= -(1.048)?s2 cos (86.8”-33.5”)
which we assume to remain constant, all quantities are
available for calculation of Ps’ and PR’, the sending- and + (1.21) (1.048) cos (86 8o_ e)
receiving-end power during the fault. Substituting in 1.162
Eqs. (53) and (54), = -1.726+1.092 cos (86.8’-0) per unit. (62)
2.00
Ps’= (1.21)2;+ cos (89.3”-1.9”)
I .00
- (1.21)(1.048) cos (89.3”+0)
3.79 I .60
=O.1753-0.335 cos (89.3”+0) per unit. (59) 1.40
PR’= -(1.048)2E cos (89.3”- 27.0’)

+ (1.21) (1.048) cos (89 3owe)


3.79
= - 1.797+0.335 cos (89.3”--8) per unit.(60)
After the Fault-The network for use in calculating
sending- and receiving-end power after the double line-
to-ground fault has been isolated, is shown in Fig. 40.
Except for the fact that one transmission line only is in
service, the network is identical to that which applied
before the fault occurred. Exactly the same procedure
is followed in arriving at the final set of circuit constants, G-DEGREES
and these constants are listed in Col. (9) of Table 4. Fig. Il-Sending-end power-angle diagrams for two-machine
The power equations after the fault become; problem.
468 Power-System StabilitzJ Basic Elements of Theory and Application Chapter 13

F; 1pJnJad -FmoboomuY
“mm~oo-ca
‘+ndlng .taxod pxqaaI3 c??c?-?‘?Yrf”
II I 00000000
Chapter 13 Power-System Stability Basic Elements of Theory and Application 469

Power-Angle Diagrams-Eqs. (55)) (50)) and (61) are as a quick check on the c:alcul:Ltion of the pan-er-angle
plotted in Fig. 41 as a function of 0, giving the sending- diagrams for the condition before the fault.
erld power-angle diagrams for the conditions assumed. The In the single-machine problem it ins possible to estimate
receiving-end diagrams are plotted in a similar manner the masimum angle of fault clearing by simply balancing
from Eqs. (56), (60)) and (62). These are shown in Fig. 42. positive and negative areas on the pan-er-angle diagram
The solution of the receiving-end polver equations to obtain (See Sec. 2G). This was possible because the moremcnt, of
fig. 62 renders negative values, because positive direction only one machine rotor had to be folio\\-etl. In the prc>s(lnt
of po\ver flow lvas chosen as being into the receiving-end case, this equal-area method can not be applied because
generators. In Fig. 42 the per-unit polver scale is plotted stability or instability is determined by the relative nnglilar
as positive, because this is believed to be less confusing position of tlvo mnchincs. The maximum rotor-displnce-
than negative values. This is permissible if the change in ment angle before fault isolation is not detcrminecl from
sign is recognized tvhen performing the step-by-step solu- the power-angle diagrams, hut will be found as a part of
t,ion for angle-time curves. the calculation of angle-time curves.
Sote that in Fig. 41 the sending-end input is indicated Angle-TimeorSwingCurves-Theangle-timccurves,
by the horizontal line as 0.917 per-unit. This figure is the lyhich relate time to angular displacement, are most
sllrn of the 0.833 per-unit pan-er delivered to the load plus conveniently determined by the step-by-step integration
(11cline and transformer losses. Since line capacitance is method described in Sec. 23. The calculation is similar
ncglccted (Sec. 29) the total volt-ampere consumption in to that carried out for the single-machine system except
tfic system is, that the angular swing of both sending anal receiving
I?Z= (o.s77)yo.loo+jo.434) machines must be traced during each time interval.
=0.0838+jO.334 per unit The best description of the actual procedure is had by
= 5OOO+j20 200 kva. referring to Table 5 in which the angle-time or string
curves are calculated. The form used is identical, for each
The in-phase portion, or loss, is 0.0838 per unit, so that the machine, to that of Table 3, so that altogether it is similar
total sending-end po\\-er is 0.S33f0.0838 =0.917 per unit. to tivo single-machine system calculations. The calcula-
The receiving-end polver-angle diagrams of Fig. 42 show tions for one time interval must be made for both machines
the receiving-end input to be 1.083 per unit, which is the before proceeding to the nest interval. This is true because
same figure as the polver delivered to the load from the the one quantity relating the angular position of the tn-o
receiving bus, since there are no losses present in that end machines, 0, is found by taking the difference in angle of
of the network. the txvo machines at the end of each interval, and in order
The initial operating angle is 0=25.3 degrees as indi- to find the electrical output for each machine in the suc-
cated in Figs. 41 and 42. This is the angular difference in ceeding interval, this value of 0 is applied to each set of
polver-angle diagrams or calculated from the corresponding
sending- and receiving-end polver equations. To make this
clear, refer to the first time interval in Table 5. The initial
position of each rotor, ivith respect to the receiving-end
loIv-tension bus voltage, is given in Cols. (2) and (12). The
initial value of 0 is the difference betxveen the rotor angles,
Col. (2) minus Col. (12), or 25.3 degrees as previously
determined. Using this value of 0, the electrical output
from each machine is determined, and the calculation pro-
ceeds to find the angle of each rotor at the end of the first
interval. These figures are tabulated in Cols. (11) and (21),
and subtracting (21) from (11) gives the nelv 0, Col. (23),
to be used in the next time interval. This ne\v 8 is t.hen
used in the power-angle diagrams, or the corresponding
sending- and receiving-end power equations, to obtain the
electrical output from each machine in the second interval.
The computation is now carried on to find 0 at the end of
the second interval, etc.
The first part of Table 5 assumes that the fault is not
B-DEGREES
isolated, and illustrates by the continued increase of 0 that
the system becomes unstable under this condition. Time
Fig. 42-Receiving-end power-angle diagrams for two-ma- intervals of 0.05 second are used because of the relatively
chine problem. rapid swing of the sending-end machines. A comparison of
Cols. (11) and (21) points out that the receiver machines
elect,ricnl degrees between the rotors, or internal voltages, slving much slower than the sending-end machines. This
of the sending- and receiving-end machines before the is caused by the relatively larger inertia constant and kva
fault occurs. This figure of 25.3 degrees can be readily rating of the receiver generators, resulting in a much
checked by taking the difference in angle of the internal smaller acceleration [Col. (15) compared to (5)]. The
voltSges expressed in Eqs. (51) and (52). This serves second part of Table 5 assumes that the fault is isolated in
470 Power-System Stability Basic Elements of Theory and Application

A and D of Fig. 43 represent a plot of the figures in Cols. ’


(11) and (21) of Table 5. Curves B and C of Fig. 43
160
represent similar step-by-step calculations for longer times :
of fault, isolation. By following the trend of the sending, :;
and receiving-end angle-time curves for a given fault-clear- ’
ing time, the loss or maintenance of stability can be seen j
If the phase angle difference of the two machines continues i
to increase after fault isolation, instability results, but if ’
the two machines tend to move back together during this
time, the system is stable. It is possible for instability to
occur on the second overswing, which is an exception to
the above statement. This phenomenon is relatively rare
but should be remembered in multi-machine problems,
particularly where one or two machines are swinging very
fast with respect to the other sources involved. Figure 43
indicates that for fault clearing times of 0.15 and 0.17
seconds stability is maintained, and for 0.20 seconds
instability results.
In the two-machine system a more convenient way of
plotting swing curves is that shown in Fig. 44, in which the
-601 ’ ’ ’ ’ ’ ’ ’
0 0.1 0.2 0.3 0.4 i.5 0.6 0.7 difference in angular displacement, 6, is used rather than
TIME-SECONDS the individual position of each machine. Referring to Fig,
Fig. 43-Angle-time curves for each machine. Two-machine 44, it is plain that the system is stable for fault isolation
system. times of 0.15 and 0.17 seconds, and that stability is quickly
A-Fault not cleared.
lost if the fault duration is 0.20 seconds. Curves A and D
B-Fault isolated in 0.20 sec. of Fig. 44 are plotted from Col. (23) in Table 5.
C-Fault isolated in 0.17 sec.
D--Fault isolated in 0.15 sec. VI. SHORT-CUT METHODS OF CALCULATION
-TWO-MACHINE SYSTEM
0.15 seconds. Col. (23) shows that 0 reaches a maximum
of 98.7 degrees and then starts to return toward a new Perhaps the most usual reason for making a stability cal-
stable operating point. Figures 41 and 42 indicate that culation on this type of system is to determine how fast
the new operating point is at an angle 8=39 degrees. relays and circuit breakers must be made to operate if sta-
The results of the calculations performed in Table 5 are bility is to be maintained after a fault occurs. R. D. Evans
given in Figs. 43 and 44. The swing of each rotor with and W. A. Lewis presented a group of curves,16 calcu-
respect to the fixed reference is shown in Fig. 43. Curves lated for a two-machine system having the usual circuit
elements, which permit the quick estimation of permis-
sible fault durations for various types of faults.
31. Assumed System
For a complete and accurate calculation on a particular
system it is necessary to consider all the various factors
discussed in Part V. For determining approximate relay
and circuit-breaker time, results of sufficient accuracy can
be obtained, except under extreme or unusual conditions.
The assumed system upon which the calculation of the
general curves is based, is shown in Fig. 45, and the *
.1’
.~
I
0.!I
2IOR MORE)
’ PARALLEL LINES

0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 T 7


FAULT :‘i
TIME-SECONDS
Fig. 45-System conditions assumed for study:
Fig. 44-Angle-time curves for two-machine system showing
difference in rotor angle between sending and receiving ma- Symmetrical system, high tension bus at each end; line capacitance
chines.
and 12R losses neglected; transformer neutrals solidly grounded;
A-Fault not cleared. quick responseexcitation (constant internal voltage); no damper
B-Fault isolated in 0.20 sec. windings; frcquency=60 cycles; load= 100 percent at, instant Of
C-Fault isolated in 0.17 sec. fault inception; faults located at most severepoint on high-tension
D-Fault isolated in 0.15 sec. lines; average short-circuit losses.
chapter 13 Power-System Stability Basic Elements of Theory and Application 471

simplifying assumptions made for the study are included


at the bottom of the figure.
The results of the stability calculations are given in the 36
four groups of curves, Figs. 46-49. These curves give
dircct,ly the results for a system with the smallest inertia 32
Jvhich may be expected, corresponding to water-wheel
gcncrators at both ends of the system. In the more usual
cast, the receiver machine will have a larger inertia con-
stant, and correction terms to be applied to the results
obtained from the curves, to adjust for this departure
from assumed conditions, mill be given.
w
32. Application of Data I
r 16
The procedure for using the curves is as follows:
(1) First, it is necessary to determine the reactance be- 12
tween the internal voltages of the sending- and receiving-
end machines. This reactance should be expressed in per- 6
cent, based upon the total capacity of the generating units
in operation at the time the fault occurs. If the exact 4

01 I I I I II I I I
0 0.1 0.2 0.3 0.4 0.5 0.6 0. 7 0.6 0.9 1.0
SINE OF INITIAL ANGLE

Fig. 47-Maximum permissible duration of fault to maintain


stability:
LINE-TO-LINE FAULT

be read from the curve (Figs. 46-49) for the type of fault
being studied.
(5) The inertia constants for the sending- and receiving-
end machines should be determined. If the total mechan-
ical inertia of the machines at one end is known, the inertia
constant for that end of the system can be determined by
using Eq. (37) appearing in Sec. 22. In case the inertia is
not definitely known, an average value can be obbained by

SINE OF INITIAL ANGLE

Fig. 46-Maximum permissible duration of fault to maintain


stability:
SINGLE LINE-TO-GROUND FAULT

machine constants are not known, an average value can


be assumed from the synchronous-machine constants given
in Table 4 of Chap. 6. If other than full load is assumed,
the reactance thus determined must be multiplied by the
ratio of assumed load to full load.
(2) Using the value of reactance just determined, the
initial angle can be found from Fig. 50.
(3) By reference to Fig. 45, the section of line that must
be removed from service to clear the fault is known, so
that the ratio II of reactance after the fault is isolated to SINE OF INITIAL ANGLE
the initial reactance can be determined. Fig. 48-Maximum permissible duration of fault to maintain
(4) Using the sine of the initial angle determined in (2) stability:
and the ratio Z,,determined in (3), the time in cycles should DOUBLE LINE-TO-GROUND FAULT
472 Power-System Stability Basic Elements of Theory and Application Chapter 13

Each transmission line was calculated to have a positive,


sequence reactance of 39.7 ohms, which can be COnVe&d
to percent on this same base by conventional methods.
Each line represents 54.7 percent, on 60 000 kva, and the
two lines in parallcl equal 27.4 percent.
The receiver has no reactance since it was assumed to ,$
be an infinite inertia system of large capacity.
The total reactance between generator internal voltage
and the infinite receiver is then:
Generators 25.4 pcrccnt
Transformer 8 0 percent
Two lines in parallel 27.4 percent
Transformer 8.0 percent

Total 68.8 percent on


60 000 kva.
The assumed load is 50 000 kw, SO the ratio of actual
load to generator rated kva is 50 000 divided by GO000,
or 0.833. Hence, at the present load, the reactance is,
68.8 X0.833 = 57.4 percent.
From Fig. 50, the initial operating angle is approxi-
SINE OF INITIAL ANGLE mately 32 degrees, the sine of which is 0.53. Note that
Fig. 49-Maximum permissible duration of fault to maintain
stability: 90
THREE-PHASE FAULT
c 00

reference to Table 8. When the inertia constants, H, in kw- ii


; 70
seconds per kva, for both ends of the system are known, 0
the inertia correction factor by which the values of time A 60
should be multiplied can he found by reference to Table 6, d
z 50
or to the following equations from which Table 6 has a

been prepared. z 40

H,+-= Il.3, 5
e 30
, 1 H,+Hr (63)
%
II, r II, w *O

ICI= Inertia correction factor = HS,


15 2d 10
(64)
d-T v)
0
In these equations I/, and H, arc the inertia constants of 0 20 40 60 00 100 120 140 160 I00
t,he sending- and receiving-end machines, in kw-seconds REACTANCE-PERCENT
per kva, respectively. Fig. JO-Initial operating angle as a function of reactance.
(fi) If the frequency is other than 60 cycles, the result
should he multiplied by the square root of the ratio of the the figure of 32 degrees checks closely the initial operating
ne\Y frequency to GOcycles. angle determined in the detailed calculation.
(7) If the load at the time the fault occurs is not equal When one line is switched out to isolate the fault, which
to the kva rating of the generators, the result should be was assumed to be double line-to-ground, the reactance
divided by the square root of the ratio of the actual km increases to,
load to the generator rating in kva. (68.8+27.4)0.833 =80.1 percent.
Example: In order to illustrate the use of the short-
cut method just described, the single-machine problem Hence,
calculated in Part V of this chapter n-ill be solved and the
resulting maximum circuit-breaker clearing time will be From Fig. 48, which applies for a double line-to-ground
compared to that obtained by the complete calculation. fault, corresponding to sine of initial angle=O.53 and 11~
The assumed system is defined in Sec. 24, and the 50 OOO- 1.4, it is seen that t =5.8 cycles, approximately.
kw load assumed there will still apply. From Table 6, corresponding to H,= 3 and H,= *,
The total generator capacity is 60 000 kva and the kl= 1.41.
transient reactance on this base, of the two machines in Since the initial load is 0.833 times the generator kva
parallel, is 25.4 percent. rating, the corrected maximum time to fault isolation is,
The assumed transformers each have eight percent re-
t = 5.8 X L= 8.94 or approximately 9 cycles. *
actance on a 60 OOO-kva base. 40.833
chapter 13 Power-System Stability Basic Elements of Theory and Application 473

TABLE B-INERTIA CORRECTION FACTOR, kl. cent longer than the figure obtained from the curves. The
(Computed from Eqs. (63) and (64)) corresponding time for each breaker mill thus increase t,o
about two-thirds of the curve values. Consideration of t)hc
H,or II, reactances involved will indicate a reasonable correction to
- - be used in an individual case.
2 3 4 8 10 11 12 50 m
-~ ___--
0 81( D.S94 0. !bK 1.03 1.05 l.OB 1.07 1.13 1.15
VII. METHODS OF STABILITY CALCULA-
0. w- 1.00 1.07 1.21 1.24 1.25 1.26 1.37 1.41 TION-MULTI-MACHINE SYSTEMS
0.94: I .Oi 1.15 1.33 1.38 1.40 1.41 1.X 1.63
33. Simplification of Networks with Multi-
0.9X 1.12 1.22 1.43 1 ‘4!) 1.51 1.53 1.i4 1.83
Machine Systems
1.00 1.15 1.2G 1.51 1.58 l.Gl 1.63 1.89 2.00
1.03 1.21 1.33 1.63 1.72 1.76 l.iS The method of solving multi-machine stability prob-
2.14 2.31
I 05 1.24 1.38 1.72 1.83 1.87 1.91 -1ems follows closely the procedure just described for the
2.36 2.58
LOG 1.25 1.40 1.78 1.91
1.87 2.71
1.96 general cast for two-machine systems, and the same
2.45
1.071.26 1.41 1.79 1.91 1.96 2.00
2.83 2.54
steady-St&c and step-by-step transient procedures should
1.131.37 1.57 2.14 2.30 2.45 2.54 5.77 4.08
be used. The first step in the solution of multi-machine
1.151.41 1.03 2.31 2.58 2.71 2.83 m 5.77
problems is to set up the equivalent network for lines,
loads, and other shunt branches and for machines as pre-
‘l’llis figure matches the one obtained by detailed calcula- viously described for the general two-machine system.
t.,ion to within the limits of accuracy of reading the curves. Such networks involve a series impedance bet\veen each
:Irltl show that the quick-estimating curves when carefully internal emf and the remainder of the system. Such a
:&ied give rcslllts that are dependable, as long as the network does not lend itself to analytical calculations
:I(:tllal system being considered is similar in circuit elements and should be replaced by mesh-connected systems with
I,() the assumed system of Fig. 45. a single-impedance branch connecting each pair of inter-
Limitations in Using Curves-The greater the num- nal emf’s. For example, Fig. 51 shows a typical netlvork
t)c:rof arbitrary assumptions and the larger the departures for a three-machine system, characterized (1) by a hydro-
1’romthe assumed conditions, the greater the resulting er- electric source with voltage &, and (2) by two receiver
ror. However, for systems of average characteristics the machines which have voltages E, and E3, which are con-
rcsdts are sntisfactorv. For examnle. if the actual svstem nected together and to the hydro-electric machine b\
has no voltage regulaiors, the perkissible fault duraiion is transmission lines represented by equivalent ir method.
rnatcrially reduced. This is particularly true for cases
where low fault duration is Dermitted. Also. if there is no
hi+ten&n bus in the act& case, more synchronizing
p<Evercan be transmitted while the fault is on the system,
l)ut a greater incrcasc in reactance occurs when the faulted
lint and transformers are removed as a unit from the sys-
Icm, so that the two effects are in the direction to com-
Pensate.
Where large steam generators are closely connected to \ /-
the receiving end of the system, the effective initial angle is
M, tletcrmined solely by the transfer reactance from the
wndincr-end aencrstors. but is usuallv reduced consider-
:lbty biTthe receiving-en’d generators. This can be taken in-
1.0account approximately by reducing the reactance of the
rw%rer machines. Where the power supplied by the re-
(‘(‘iving-end generators is greater than about three times 6E3
Illat of the sending-end machines, it is safe to neglect the
(a) TYPICAL NETWORK WITH THREE MACHINES
rwcivcr reactance, and measure the total reactance to the
reviver low-tension bus.
ln the foregoing all breakers necessary to isolate the fault
\‘cre awlmet to open simultaneously. In practice, when
tllc fault is near one breaker, a basis of discrimination for
tripping the breaker does not exist until the first breaker
11~ opened; hence the two breakers operate sequentially.
ln such cases the fault duration is increased to twice the
timc of a circuit-breaker opening. Where the distance from
tllc fault location to each bus is short, this mill require a
breaker-opening time of half the permissible fault duration.
If, however, the line reactance between busing points is
xE3
7i
(b) EOUIVALENT MESH-CONNECTED NETWORK
hiah, tt le severity of the fault is greatly reduced and a Fig. 51-Method of reducing networks _.to the form conven-
longer total duration is permissible, up to probably 50 per- ient for stability studies.
.1!
5
474 Power-System Stability Basic Elements of Theory and Application Chapter 13 ’

Such a network should be transformed by the methods complexity.10~36 This results from the many condition8
previously discussed in Chap. 2 to the form shown in to be considered and tht: laboriousness of the calcula,
Fig. 5 1 (b). This network involves only (1) shunt branches tions. Additional complication is introduced if, ag b
connected directly across the internal voltage ordinarily usually the case, automatic Voltage regulators are used,
assumed constant and (2) mesh-connected branches con- Fortunately, however, the problem when considered fro,
nected directly between pairs of internal emf’s. The the practical viewpoint is greatly simplified because it
power equations for such a system are readily written for becomes one of determining whether a pa&ular syster,
each line in terms of the source emf’s, in magnitude and is stable for an assumed load below the actual stability
phase position, and t,he se&s impedance of that line. limit. Under these conditions, many of the complicating
‘l’hus, it is readily possible to determine the electrical factors are eliminated. It is often necessary to provide B
olitput or input for each machine if the phase posit~ion and considerable margin between the steady-state power limit
magnitude of the various internal emf’s are available. with fixed excitation and the assumed operating con&
Analytical methocls of calculation can be applied to tions. A further factor is the action of automatic voltage
systems involving more than three machines by using the regulators in increasing limits due to phenomenon of
same procedure just described in connection with the dynamic stability. For these reasons little effort is di-
three-machine system of converting the network to the rected toward the determination of the actual stability
simplest mesh-connectetl system. Such a procedure has limits of multi-machine systems. Instead, the problem
been used for the solution of four-machine systems.lO takes the form of showing that the system is stable for a
However, the complication increases rapidly with the particular set of assumed conditions. Usually the impor-
number of mnchincs, and it is not practical to carry out tant limit is the transient stability limit.
calculations for systems with more than three or at the The practical method of solving stability problems of
most more than follr machines. central-station systems is by means of the a-c network
calculator.18 Analytical methods become exceedingly la-
34. Steady-State Solution for Multi-Machine borious for cases involving more than three or four ma-
Systems chines. The average central-station utility problem usually
The determination of the steady-state stability limit involves more than this number of machines and solution
for a multi-machine system is a problem of considerable is more easily done by a-c network calclllntor.

.DJUSTABLE CALCI J .ATOR ELEMENTS

--. -. ---, ^-
Generator and iesistor * Reactor 2nd Lrsisror * Reactor and Resistor - Reactor and Resistor - Reactor and Rcsirror * Reactoi and
esistor l Reacror Uni ,uto.Transformcr Unit Capcitor Units Auto-Transformer Units Capacitor Units Load Adjuster Units

JNECTIONS AS PER’SINGLE-LINE DIAGR.

4r T ELECTRICAL
T t
CtiARACTERISTICS
STEP.UP STEP.DOWN SUB-STATION LOADS
POWER STATION ‘RANSMISSION LINE
TRANSFORMER TRANSFORMER

Voltage . Current Resistance R&talKe Rerirrance Voltage - Current V&age


Power Factor ReXtXlCe ReaCtalICe Reactance Resistance . Reactance Current
Resistance - Reactam Turn Ratio Capacitance Turn Ratio Synchronous Condenser Power Facror

Fig. 52-Various system elements and the calculating-board elements used to represent them.
Chapter 13 Power-System Stability Basic Elements of Theory and Application 475

into the power system valrws. Various pow+system clc-


ments and the corresponding calculator circuits are illus-
trated in Fig. 52, and a general vielv of the calculator is
shown in Fig. 5B.
The number and types of circuits provided in the Wcst-
inghouse a-c n&work calculator at East Pittsburgh are
listed in Table 7.
The power supply for the calculator consists of a UO-
cycle, 220-volt motor-generator set, which has its voltage
controlled by an electIronic voltage regulator and an elcc-
tronic exciter to provide quick response and accurate
regulation. The generator of this set supplies three-phase
power to the calculator generator units, which are actualiy
regulators especially designed to convert the three-phase
power input to a single-phase power output having adjust-
able magnitude and phase angle.
Two independent sets of master instruments, circuit
selector and metering controls are provided, each set be-
Fig. 53-The a-c network calculator at East Pittsburgh. ing mounted on a separate metering and control desk.
Direct readings of either scalar or vector vnlues of cur-
35. The A-C Network Calculator rents and voltages, and magnitudes of watts, vars, and
l’he general design of the a-c network calculator is phase angles can be obtained. The two metering desks
SUC:~ that all of the essential elements of a modern power provide for conducting two simultaneous studies of sepa-
systcrn can be reproduced in a miniature replica. The rate systems with independent control of each system.
wrious parts are reproduced accurately in suitable propor- Any calculator unit can be instantly connected to the
t,ion to the system values, and observations and measure- metering equipment by a remote-control circuit selector
rnrnts on the replica network correspond to what would which enables metering of system quantities at any point
ol)t,t~inunder like conditions on the power system. Suit- in the system.
:tl)lc multipliers or conversion factors readily translate the The determination of the electrical conditions on the
wlculator readings of voltage, current, watts, and vars a-c network calculator gives practical solutions for the

TABLE ~-NETWORK CALCULATORCIRCUIT ELEMENTS

Nurnl1c:r Range
of Type oECircuit Prefix Used to Represent of Steps
Circuits Adjustment
22 Generatorunit,swith voltmeter, G Generator, phase-shifting transform- Voltage: o- 4005’0 Smooth
ammckr, wattmeter, and var- er, etc. Angle: 0- 360” Smooth
meter
IS Low-loss reactors X Generator reactance React: o- 49076 0.2

1% Line-impedance units Lines, transformers, etc. Resis: o- 3sn70 0.2


React: o- 301’10 Smooth

Transmission-line Pi units - Long, high-voltage transmission lines Resis: o- 309% 0.2


React: o- 301’;7 Smooth
Suscept:* o- 4170 0.1
I.oad-impedance units wit,h load L Shunt loads Rcsis: o-3!X)Oc/ 2.0
adjustors and voltmeters React: O-2400C:” Smooth
Load Adj : F lo’;l, 1%

Condenser units c T,ine-charging capacity, synchronous Mfd: o- 4.1 01


condensers, negative reactance
36 Autotransformer units T Transformer taps, regulators
36 I to 1 ratio transformers M Mutual induction, or used as 2 to 1
autotransformers for extended range
studies
Metering jumper circuits J Zero-impedance metering jumper cir-
cuits
*SWeptance at each end of Pi unit.
1
476 Power-System Stability Basic Elements of Theory and Application Chapter 13 ?

many design and operating problems of electrical systems. ods, esceedingly complicated systems can be set up on the
The niost common problems may be classified as: calculator and a practical solution obtained.
a. voltage-regulation studies for determining bus voltages, 37. Two-Reaction Method Using A-C Network
load-control studies and current-distribution studies, either Calculator
as a system-designor an operating problem 2nd for normal
or emergency conditions, The a-c network calculator also provides a means for
b. short-circuit studies for circuit-breaker and protective-relay carrying out in a practical manner calculations of corn-
npplicntion, and plicated systems using the two-reaction method*. For
c. stenrly-state nn(l tmnsicnt-stability studies for determining this purpose each machine should be laid out so as to
the power limit of transmission systems. have two sources of voltage electrically at right angles to
each other. The vector diagram for a salient-pole gen-
36. Transient-Stability Solutions on the A-C erator under transient conditions is shown in Fig. 25. One
Network Calculator of these sources would represent the voltage Ed’, the mag-
For stability purposes t,he problems need be considered nitude and phase position of which are associated with
merely as the solution of a set of simultaneous equations the excitation and with the rotor position. .It right angles
under successive steady-state conditions. The transient- to this vector is the voltage E,‘, which represents the react-
stability solution, by the step-by-step procedure, is ob- ance drop due to flux in the quadrature asis. The value
tainetl by a succession of appropriately-adjusted stcady- of this voltage is assumed to vary instantlyt so as to
state conditions. provide the proper quadrature-reactance drop. For each
The system is reduced to a common base and is nor- point in the stability analysis the voltage in the quadrature
mally set up on t,he calculator on the basis of the positive- axis is adjusted until the vector diagram is satisfied for
sequence network, using transient reactance in series with the particular terminal condition.
the generator voltage. Where large synchronous con- An alternative method requiring only one source of
densers are involved and the inertia of these condensers voltage for each machine is outlined in Chap. 6. This
must be considered, they are represented by a voltage method uses the quadrature-axis reactance to relate rotor
behind the condenser transient reactance. position, direct- and quadrature-asis voltages, and the
The system is set up for the conditions prior to the dis- terminal quantities. The method is, therefore, based on
turbance, and the generator internal voltage, power, and the adjustment of the network-calculator settings to al-
angle are read at the point behind the generator reactance. low for the variation in the direct- and quadrature-axis
The power so obtained is assumed to be the mechanical voltages whose transient values are separately calculated.
input to the generator and is maintained constant through- Both methods involve a cut-and-try proposition and
out the study, assuming that during the short time being are somewhat tedious. The principal merit of such a
considered, the governor cannot change. The internal method is that it provides a basis for estimating the dif-
voltage is also maintained constant throughout the study. ference in results with the two-reaction method and the
The internal angle initially read is the normal angle, and conventional round-rotor method which is generally
the departure from this angle is calculated from the found adequate.
generator power output and machine dynamic charac-
teristics. VIII. SHORT-CUT METHODS OF
The fault is then applied at the desired point in the sys- CALCULATION-METROPOLITAN SYSTEM
tern by connecting that point to the neutral bus in accord-
ance with the type of fault as described in Sec. 10. The The discussion in Part VI describes a useful short cut in
internal angles and voltages of the generators are adjusted calculating transient stability on transmission systems.
to the values measured before the fault was applied, and Similarly, a general study has been made and general
the power distribution read. The difference between the curves presented for the quick estimation of transient-
power before the fault and the power after the fault is the stability limits on metropolitan-type systems.23 In this
accelerating or decelerating power available for changing discussion a metropolitan-type system is considered to be
the angular position of the machine rotor. From the rela- one in which the principal power sources are steam gener-
t,ions between the machine inertia, the change in power, and ating stations, located relatively close to their load centers,
the time interval, the change in angular position of each with distribution provided by a multiplicity of moderate-
machine rotor is calculated, and the generator internal voltage circuits. The power supply to most metropolitan
angles shifted to these new values. The procedure is re- districts is of this character; there are, of course, notable
peated for the next time interval, and so on throughout exceptions.
successive intervals until the system is proven either stable Although most systems of this type are inherently sta-
or unstable for the conditions being studied. ble as compared to systems coupled with long transmission
The a-c network calculator provides a means not only lines, nevertheless transient stability analyses are fre- j
for solving stability problems but also for obtaining the quently desirable. For example, other aspects of system 4
time variation of all the related electrical and mechanical *This method was first used for analytical calculations by C. F* $
quantities useful for circuit-breaker and relay application Wagner and R. D. Eva&; it was adapted for USCwith the a-c network
and for other similar purposes. The network calculator is calculator by Dr. W. A. Lewis.
also a device for simplifying networks and reducing them tThe basis for the rapid variation of quadrature-axis flux w@
4
to a simpler form for more detailed study. By these meth- shown experimentally in Reference 5.
(-Jmpte13 Power-System Stability Basic Elements of Theory and Application

,pcration, such as placin, 0‘ of new generation, reduction of


sllort-circuit kva, and flexibility of operation may suggest
13YoLltsdiffering from those at present in use, and it is de-
sirable to be able to evaluate whether the desired changes
,vill increase or decrease the transient limits, and whether
tl,c rcsulting value is satisfactory.
38. General Stability Curves
>lctropolitan systems, as defined above, are similar in
,n:ljor characteristics making gencrnlized studies practical.
~l,~;y are usually similar in the follon-ing features:
1. With equal percent loadings the internal voltages of
all gcncrators are essentially in phase.
2. With a multiplicity of circuits, the reactance of the
connecting lines holding a generator or group of generators
in step with the system does not change appreciably when
LLf:llllt is cleared.
3. With turbo-generators and short lines involved, the
gcllcrator characteristics are no longer affected by the
I iI iI iI iI /I iI iI iI iI iI iI Ii iI iI iI iI iI iI -120 , -
ypccd of prime mover, line charging-current requirements,
(‘tc., and they tend to become fairly uniform in their es- tiiiiiiiiiii
scatial points, such as rcactances, inertia, and short-cir&it 0 “““Ls”‘tJ’uLL
0 0.2 0.4 0.6 0.0 I.0 1.2 1.4 1.6 I.0 2.0 2.2
lXti0. TIME IN SECONDS
‘Thesesimilarities make it possible to calculate transient (a)
st.:lbility solutions for a number of hypothetical systems
:lr~clgive the results in curve form, using the remaining
v:~ri:tldes as indices. The curves are then applied to specific
1:tyouts by determining these quantities for the specific
cue.
Space is not justified to include the derivation of the
general curves, but the complete procedure is described in
t.hcpaper in which these curves were originally presented,
“Generalized Stability Solution for Metropolitan-Type Sys-
tams” by Griscom, Lewis, and Ellis.23 In developing the
cwvcs some minor influences had to be eliminated from
consideration with some sacrifice in accuracy of results.
Such influences include resistance in the lines and the fault,
variations in generator loading, and the effect of voltage
rcgulntors. The errors introduced by neglecting these in-
fluences, and possible means for compensating for them,
will be discussed in a later section.
The general stability curves for metropolitan-type sys-
tcms are shown in Fig. 54. These curves assume that the
Rcnerators have a short-circuit ratio of 1.0. In the paper
originally presenting these curves, a similar set was in- 0 0.2 0.4 0.6 0.0 I.0 1.2 1.4 1.6 I.0 2.0 2.2
cluded using a generator short-circuit ratio of 0.8, but the TIME IN SECONDS
rpsulting differences are so small that both groups of curves (b)
arc not included here. Part (a) of Fig. 54 consists of a fam- I .o
ily of curves covering the range of overall reactance X, 6 0.0
Plotted in terms of short-circuit current, IFG, from the z
faulted generator and the permissible fault duration, t. Part 2 0.6
(1))is similar except that the power dropped by the faulted
generator is used instead of IFo. Part (c), as will be ex-
plained later, provides a means of correction for resistance
in the fault, and for other than rated initial load. Part (a)
applies directly to faults at the generator terminals. For 0
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.0 0.9 1.0 I.1
faults occurring at other locations, a close approximation is rco
Securedby dividing IFG by a factor read from Part (c) be- (cl
fore entering Part (a). This location factor, designated as
Flg. H-General stability curves for metropolitan-type sys-
rF~, is a function of the ratio of I*o to IF, the total fault tems.
‘Went.
478 Power-System Stability Basic Ek !ments of Theory and Application
,i!
Chapter 181

rating of generator A. The fault current supplied by the


farilted generator is:

IBC.= i$x 10.4 = 3.7 times rated current.

The ratio of ZFC/IF gives TFG = 0.357, so that now the


indices necessary to use the curves of Fig. 54 are:
Overall reactance X = $2 percent
Current from faulted generator =3.7 X rating
Ratio ZFo/Zr=r~o = 0.397.
Using this value of TFG and interpolating for a reactance
of 42 percent, Fig. 54 (c) gives a location factor of 0.7. The
adjusted value of ZFo is then 3.7 divided by 0.7 = 5.3, and
the permissible fault duration can now be read from Fig,
54 (a) (by extrapolation) and is found to be 0.39 seconds,
If the fault occurs at point N of Fig. 55, outside of the
feeder reactor, the circuit reduces to that shown in Fig. 57,
The overall reactance does not change, but a high-react,
ante shunt branch is introduced to represent the reactor.
It will be found for this case that TFG remains the same
Fig. 55--Typical metropolitan-type system selected to dem- because it depends only on the reactance branches adj+
onstrate application of curves. cent to the generators. The total fault current is greatly
reduced owing to the presence of the 30-percent reactance
39. Application of Curves
An example is chosen to illustrate the application of this
short-cut method for metropolitan systems. The typical
system is shown schematically in Fig. 55, with reactances
as indicated. A three-phase fault at point M will be con-
sidered. This fault isolates generator A from the remainder
of the system during the fault, and this unit is then the one
most likely to pull out of step first. Generator A therefore
becomes the “faulted generator,” and all other machines Fig. 57-Network of Fig. 55 reduced toequivalent for faultath!
including those in the same group become the “remaining
generators.” With a fault at M, the network of Fig. 55 in series with the fault point, and becomes 2.52 times rated
reduces to that of Fig. 56. The actual reduction can be current of machine 8. In this case ZFC,calculates to be 0.9
accomplished analytically or, more easily, by using a d-c times rated current, and when adjusted for location be
network calculator (since resistances are not included). comes 0.9/0.7= 1.29. When these indices are referred to
If the network calculator is used, the actual reduction to Fig. 54 (a), it is evident that the point is beyond the range.
the form shown in Fig. 56 need not be completed, as the of the curves, and the permissible fault duration exceeds
two seconds.
15% If the fault were at point 0 of Fig. 55, it would affect-d1
R four of the generators in station A more equally. Hence,
1-
0% there is a possibility that this entire group may lose syn-
chronism with the remainder of the system. In this C&BB
1 the group should be considered as the faulted generator,
and all indices should be expressed in terms of the rating Of
the group as a base. This solution can be compared with
Fig. 56-Network of Fig. 55 reduced toequivalent for fault at M. that for generator A considered as the faulted unit, and
the shorter of the two figures for permissible fault duration
necessary indices can be obtained from the current read- should be taken as the result. i.
ings taken to perform the reduction. From Fig. 56, the NOW, suppose that the three-phase fault occurs on the
total reactance X between the faulted generator and the leads of generator 8, as designated by I-’ in Fig. 55. In tb!$,
remaining generators is 27+15=42 percent (always on case generator A must be disconnected from the system t$
the rated-kva base of the faulted generator). To deter- isolate the fault, and this must be accomplished before,
mine the total fault current IF, the branches on each side machines B, C, and D lose synchronism with the rema
of the fault are paralleled: of the system. Generator A is isolated from the syste
(27 X 15) the fault while the fault persists, and is isolated by
= 9.65 percent, breaker when the fault is cleared, hence B, C, and D 0
42
are considered as the faulted generators, and generator
and the total fault current is l/O.0965 = 10.4 times the is eliminated from the calculation. By reduction of
chapter13 Power-System Stability Bwsic Elements of Theory and Application 479

percent power would have to be dropped by the machine


if the fault were at its terminals. The curves show t,his
power dropped as percent of the generator kilowatt, rating,
which is assumed 85 percent of the kva rating. If machine
A and its transformer have a resistance of 1.5 percent, then
with 3.7 times rated current flowing, the I?Tzloss in the ma-
chine and transformer is (3.7)?X 1.5= 20.5 percent of the
Fig, 5g-Networkof Fig. 55 reduced to equivalent for fault atP. generator kva rating, or 20.5 divided by O.S.5= 24 percent
of its kilowatt rating. So, instead of 100 percent load
sct,,.ork of Fig. 55 for a fault at P, the simplified equiva- dropped, the equivalent load dropped is 100 minus 24, or 7G
lent shown in Fig. 58 is obtained, the reactnnces now being percent. The permissible fault duration, considering the
cxprcssetl in percent on the combined kva rating of ma- effect of resistance, is then determined from Fig. 54 (b) for
rhincs B, c, and D. From this point the calculations are X = 42 and power = 76 to be 0.6 seconds.
iclcntical to the previous examples, and the masimum fault If resistance in the fault itself is to be considered, the
,l,ir:rtion is determined to be 0.53 seconds. power loss in the fault must be divided between the faulted
Unbalanced Faults-In the foregoing paragraphs generator and the remaining generators. An approximate
tl,rcc-phase faults have been assumed to demonstrate the method of doing this is to multiply the total loss in the
,,pplic3tion of the general curves. If unbalanced faults are fault by rro, and add this figure to the loss in the generator
to l)c considered, the method of symmetrical components branch of the circuit. For example, for the fault at M as-
citn l)c used by adding a series impedance at the point of sume 0.25 percent resistance in addition to that of the
f:rult,, which impedance is a function of the negative- and generator and transformer. With 10.4 times normal cur-
zcre-sequence networks. This procedure is illustrated in rent, ( 1O.4)2XO.25 or 27 percent of generator kva is created
SW. 26 and 30 of this chapter and discussed in Sec. 10. in the fault. This is equal to 27 divided by 0.85 or 31.8
percent of generator kilowatt rating. Then multiplying by
10. Correction Factors rro, 31.8X0.357= 11.3 percent power in the fault taken by
.ls stated above, certain factors influencing stability the faulted generator. As determined above, the power
\vcrc not considered in the preparation of the general dropped is 100 percent when X= 42 percent and t = 0.39
(:Irrvcs. These simplifying assumptions all tend to make seconds (from Fig. 54 (b)). When 24 percent resulting
ttic permissible fault duration shorter, or to make the tran- from generator and transformer resistance and 11.3 per-
+nt-stability solution more critical. The curves of Fig. 54 cent resulting from fault resistance are subtracted, 64.7
r:m thus be used directly for most work without applying percent remains as the equivalent power dropped. From
correction factors since the error will consistently be on the Fig. 5-1 (b) this amount of power dropped is seen to give a
n:tfc side. It is appreciated, however, that the effect of permissible fault duration of 2.0 seconds.
someof these neglected considerations may be of interest Initial Generator Load-The general curves assume
it1specific cases, so approximate corrections are presented, that all generators are loaded to 100 percent of their kilo-
\vhich while they are not rigorously correct, should be watt rating. For other than rated load, first find the per-
accurate enough for most practical work. centage of kilowatts dropped, corresponding to X and t for
Eflect of Resistance-The usual resistances present in rated initial load, then multiply this by the ratio of initial
power circuits have a minor effect on stability, except for load to full load, and read the corrected permissible fault
l.lrcresistance in the fault circuit. Because of the very large duration from Fig. 54 (b), for the curve corresponding to
(Nrrents in the fault circuit, a small resistance will result in X. For example, with X = 42 percent, t = 0.39 seconds, 100
11large power loss, which in a measure compensates for the percent kilowatts is dropped, and if the initial load had
drop in load on the faulted generator and lessens the tend- been 75 percent instead of 100 percent, the fault duration
cncy to pull out of step. Parts (a) and (b) of Fig. 54 arc can be read as 1=0.61 seconds for kilowatts dropped=
Plotted for faults at the generator terminals. Applying the 100 X0.75 = 75 percent and X = 42 percent.
lOWion factor from Fig. 54 (c) converts a fault at any Voltage Regulators-Regulators with a moderate
Otherlocation to its equivalent fault at the generator ter- rate of response give a certain amount of improvement in
rnirl:rls. For each point in Part (a) there is a corresponding stability over the amount shown by the curves of Fig. 54.
I)cirrt in Part (b), from which may be found the amount of The exact magnitude of this increase is difficult to deter-
P()\verwhich would have to be dropped by the faulted gen- mine, but a reasonable idea of the improvement can be
erator for the equivalent fault at its terminals. If the easily obtained by multiplying the value of Ire by 0.85
llmount of power dropped is reduced by resistance in the before entering the curves of Fig. 54 (a). This gives a rela-
lines or fault the effect would be substantially the same tively good estimate over most of the range of the curves.
regardlessof iault location. Hence the result may be found
t1y reducing the equivalent amount of power dropped by IX. ESTIMATING PERMISSIBLE
the amount of resistance losses taken by the faulted gener- TRANSMISSION LINE LOADING
ator, and reading the corrected fault duration from Fig.
‘q (b). For example, with the fault at point M of Fig. 55, a 41. Surge-Impedance Loading
clearing time of 0.39 seconds was indicated by Fig. 54 (a). When a resistance equal to the surge impedance of a
‘he same clearing time must be indicated by Fig. 54 (b) resistanceless transmission line is connected across the re-
heace,for X = 42 percent and t=0.39, it is found that 106 ceiving end of the line, a surge introduced into the sending
480 Power-Syste’wl Stability Basic Elements of Theory ad Application

end is absorbed completely without reflection. Thus a system. This criterion is that the operating load, af
sinusoidal voltage introduced into the sending end travels switching of the faulty line, be 80 percent of the crest, d
along. the line and is completely absorbed. The voltage at the transient power-angle relation.
the receiving end varies sinusoidally with time, has the X justification for this particular value of 80 percent k
same magnitude as the voltage at the sending end, and is given in Fig. 59. Curve 1 is a hypothetical power-angle
displaced by an angle equivalent to the time required for diagram, based on generator transient reactance, having B
the wave to move from one end of t.he line to the other. crest of 100 percent after switching of the faulty line 8ec- 8,:
The load delivered over the line to the resistance is tion. The horizontal line PO represents the prime-rnov,,,, fG
“.

called “surge-impedance loading.” Based on an average input, presumed constant at 80 percent of the crest value
value of surge impedance of 400 ohms, and equal to the generator rat’ing.
SIL = 2.5(kv)? First, assume a three-phase short circuit at the genera& ?,,
(65) high-voltage bus. The generator output will decrease from,?,
where
80 percent to zero and remain there until the fault is m ‘:
SIL = surge-impedance loading in kw lieved, after which it follows Curve 1. If the angle of swing :‘.
kv = line-to-line kilovolts of transmission line is adjusted so that the area bounded by &cd is equal to the
2.5= a constant derived from the average surge im- area bounded by aejjg, the system will have transient st&
pedance as shown in Chap. 9. bility for a three-phase fault on the high-tension bus, for
Thus, surge-impedance loading is a constant for lines of a the time required to increase the angle from c to b, with no
particular operating voltage and can be used as a basis for margin. The time to increase the angle from c to b can b
comparison of lines operating at different voltages. The obtained if the inertia constants of the generators are
follow-ing analysis derives a simple method of determining knolvn. If these are waterwheel generators, Ei may by
the permissible loading of a straight-away transmission about three. The acceleration for dropping full-power
line based on a transient-stability criterion and expressed output is
in terms of surge-impedance loading and the line length in 18Of (lSO)(c,O)
miles. = 3600 elec. deg.jsec.2
a=H= 3
42. Criterion of Stability The angle traversed in time t is
A rigorous determination of the power limit of a system
is dependent upon many detailed considerations such as
circuit-breaker clearing time, type and location of faults,
type and speed of the excitation system, bussing arrange- The angular difference, b-c, in Fig. 59 is about 10 degrees,
ments, line-sectionalizing, station spacing, generator short- hence the required fault-clearing time
circuit ratio, generator inertia constant, etc. Even when
extensive work is done along these lines, it is still necessary t=$$=.&$$=O.O;j second.
to apply judgment factors to calculated results. In esti-
mating the permissible loading of long, high-voltage, Various details have been omitted for clarity in the fore-
straight-away transmission lines, a single overall criterion going. The power does not drop to zero because of ma-
can be used rather than attempting a detailed design of the chine losses. Curve 1 is not traced because of some decre
ment. Point d is not the correct starting point, but rather
the intersection with POof the unswitched transient power
angle diagram, Curve 0. Also, other values of inertia
constant give different required fault-clearing times.
The approximate conclusions are that a three-phase
fault on the generator high-voltage bus would result in
instability for 8-cycle and 5-cycle circuit breakers. Fo$,ll i
S-cycle circuit breakers, the clearing time under ideal con-+$
ditions would be 0.067 second. However, a fault as severe ’
as a three-phase fault is too rigorous a criterion.
A similar analysis is approximated for a single phase-t&
ground fault on the generator high-voltage bus. On th!,>
basis of XO=X~= ~2, the power-angle diagram during the$
fault mill have a crest value of about 2/3 of Curve 1. WC;
is shown as Curve 2. Equating area dughi to area gjj givy 1~
an angular change of about 32 degrees, and an appro*.,%
ANGLE-DEGREES mate required clearing time of 0.275 second. This time
Fig. 59-Hypothetical power-angle diagrams showing switch- be obtained readily with g-cycle breakers and carrier-
ing times for maintaining stability with no margin during rent relaying and allows considerable margin.
three-phase and single line-to-ground faults. From the preceding demonstration, it is consi
Curve l-Power-angle diagram, faulty line switched. logical to operate a system at a loading equal to
Curve a-power-angle diagram,during singleline-to-groundfault. of the crest of the transient power-angle diagram.
Curve O-Power-angle diagram, system normal. interest to note that if the loading were to be incr
chapter13 Power-System Stability Basic Elements of Theory and Application 481

85 percent of the maximum power, the area above the new system may vary considerably. For systems in which the
p,, line 1smarkedly reduced; while dropping below 80 pcr- transmission system supplies most of the energy used, the
ceIlt increases the area rapidly. While SOpercent may not receiving-system impedance may represent a large per-
,)c tl1e best operating point, it is a very reasonable value. centage of the total. Where the transmission system mere-
l,, deriving the curves in Fig. 59, the generator power ly augments the generating capacity already existing, and
o,,tput was csprcssed by in particular where multiple terminals arc used, each fced-
ing into existing large systems, the rccciver-system imped-
P= 100 sin 0
ance may not be much greater than the reactance of the
,,.herc B is the angle between sending and receiving volt- step-down transformer. In this analysis, the receivirlg-
:,Rrs. For an actual system, the cspression for generator system impedance is taken as the receiver trnnsformel
pw is reactance only for two reasons: first, it results in greater
P=Zi1E,2+ZiJ?,E, sin (0-S). line loadings, reflecting possible future improvements in
technique, and second, the stability criterion being used is
lf I’“, the maximum operating load, is taken as 80 percent probably on the conservative side.
Of t tic crest of the transient power-angle diagram, the area
,l,~~C~~~ of Fig. 59, available to withstand transient dis- 44. Permissible-Loading Curve
t,,rtJancesis reasonably constant over a wide range of sys- With the foregoing values of reactances set, namely 25-
t,!m lnyouts. Essentially, the above analysis was based on percent generator transient reactance, and S-percent trnns-
l\‘,fl,’ being small compared with K2E,E,. In terms of former reactance, permissible line loadings as a function of
;l[jcD constants, ZC1is the real component of D/B while distance may be obtained. The procedure is to assign a
1~~is the scalar value of l/B. Unless the resistances of the line loading, such that, when terminal equipment imped-
circrlits are quite high, or the lines quite long (beyond one- ance is added, POis 80 percent of the crest of the power-
clll:lrtcr wavelength or approximately 775 miles), ZC1ES2angle diagram. The line impedances depend upon the
rcrnnins small compared to KzE,E,, and close comparisons operating voltages, whereas the equipment impedances
tl(:t,\vcensystems can be made with the criterion. depend upon the kva ratings.
‘l’hc proposed criterion is based on holding the gener- The first step is to obtain the power-circle diagrams of a
:rt,ing station in step with the receiving system during transmission line of a given length and voltage including
t.r:msicnt disturbances, and presumes that the receiving transformers of appropriate size. The expected loading is
nystem inertia is infinite compared with the generating approximated or assumed, P, and Q. are available
Hystcm. This is substantially true for most systems in from the circle diagrams, and E,, the internal voltage be-
operation today. In particular, in order for the criterion to hind generator transient reactance, can be calculated.
:~pply at all, it is necessary that pull out, should it occur, The generator reactance can then be added to the trans-
t)c due primarily to overspeed of the generating station former and line constants, and the equations of the pow-
rather than underspeed of the receiving system. er-angle diagram determined, and hence the crest value
of the generator output. If 80 percent of this crest does
43. Terminal Equipment Impedance not equal the loading originally assumed, the work must
The transient reactance of the generators and the leak- be repeated, revising the generator and transformer kva
:tge reactance of the step-up and step-down transformers ratings in accordance with the deviation noted.
InlIst be added to the line impedance to obtain the tmn- When the analyses are carried through, a power-angle
sicnt power-angle characteristic of the system. The react- diagram will have been obtained for each line 1engt.hstudied
:mce of the terminal equipment can vary through rather and for each voltage rating studied, such that P,, is 80 per-
\vitlc limits. The generator transient reactance may be as cent of the crest of the diagram. If the loadings of the lines
1~ as 15 percent for turbine generators and as high as 40 are expressed in per unit of the “natural” or surge-imped-
Wrcent for slow-speed waterwheel generators. The ma- ance loading, there is little variation in characteristics of
jority of straight-away transmission systems are in con- lines over a wide range of operating voltages. A curve of
jrmction with waterwheel generators, and generators of delivered power expressed in terms of per-unit surge-im-
lo\ver than normal reactance are used to be able to operate pedance loading and plotted as a function of transmission-
tllc lines at higher power levels. On this basis, 25 percent line length in miles is shown in Fig. 60. The curve is closely
Wrcsents a fair approximation of the generator transient applicable in determining transmission-line loadings based
WUtance. on transient stability for operating voltages between 69
11similar condition applies to the transformers in that and 500 kv.
the normal transformer reactance varies with voltage rat- As an example, the curve indicates that a -250-mile trans-
ing. At 138 kv, and to a lesser extent at 230 kv, the react- mission line can deliver an amount of power equal to 0.69
lLncesof normally designed transformers are about ideal times the surge-impedance loading. If the operating volt-
considering the opposing requirements to limit short- age were 345 kv, the line could deliver (0.69) (2.5) (3-l5)“=
circuit currents and to obtain maximum stability. At 205 000 kw. At 230 kv, the capability of the line would be
higher voltages, however, it is advantageous to use trans- 91 000 kw. In each case, the delivered power is the value
formers of reactance lower than normal. A fair average of PO obtained in the analyses above less the line loss, and
value of transformer leakage reactance is eight percent for is the deliverable power for rating purposes.
transformers at both ends of the line. Before it can be considered operable, a system must be
The amount of reactance used to represent the receiving stable under steady-state as well as transient conditions.
2. transfer reactance or “through reactance” between sm.>
chronous machines, as this directly increases the sync&
nixing power that can be interchanged between there
The reactance of a transmission line can be decreased l,i &
reducing the conductor spacing. Usually, however, the ;%t
spacing is controlled by other features, such as lightning .t:
protection, and minimum clearance to prevent an 8rc ;‘
from one phase involving another phase. .\nother me& ,_,
od of reducing line reactance is to increase the conductor ‘:
diameter by using mat,erial of low contluctivity or by
hollow cores. Usually, however, the characteristics ot
the conductors are fised by economic conditions quite :;.
apart from stability. The use of bundle conductora .j
(Chap. 3, Sec. 10) is an effective means of reducing se
ries reactance.
The transformer reactance should be kept as low 81)
practical. While some reduction from normal reactance
as shown in Chap. 5, is permissible, economic consider:
tions usually prevent much departure from the lolvest
Fig. 60-Permissible loading of straight-away transmission value obtainable without increasing the cost.
lines as a function of line length in miles for voltages from The series capacitor provides another means for dc-
69 kv to 500 kv.
creasing the “series” reactance of transmission systems.
However, at times of system faults the current through
The curve of Fig. 60 is based on a criterion of transient the capacitor raises the voltage across it to several time8
stability, and it shows the permissible loading when the normal. To protect against such overvoltages, two pro-
criterion is met. These results were examined for steady- cedures are available: (1) relatively espensive capacitors
state stability and found to be within steady-state limits capable of withstanding the abnormal voltage can be
with satisfactory margin. Therefore, the loadings for vari- used, (2) the capacitors can be designed for the maximum
ous line lengths may be considered acceptable under voltages produced under normal circuit conditions and
steady-state and transient criteria. provided with a device for short-circuiting it during the
excess-current condition. When series capacitors are
X. METHODS OF IMPROVING SYSTEM used with short-circuiting means, they are ineffective
during the fault condition. However, when high-speed
STABILITY 1
circuit breakers are used, the fault condition is promptly
The effect of various specific factors in the stability relieved and the advantage of low series reactance is ob-
problem will be considered from the standpoint of im- tained for the subsequent part of the oscillation. The ap-
proving system stability. For convenience these factors plication of series capacitors is discussed in Chap. 8.
will be considered under the principal headings of “Power- Transmission-circuit reactance drops are commonly
System Layout,” (‘Power-System Operation,” and “Char- reduced by adding parallel lines or increasing the circuit
acteristics of Apparatus.” These sections are followed by voltage. Comparisons at times are made between several
a discussion of “Other Methods of Increasing the Practical low-voltage circuits and a few high-voltage circuits. Ob-
Operating Power Limits.” viously, the fewer the number of circuits the greater irr
the reduction in the power limit of the layout when one
45. Power-System Layout circuit is switched out.
Power-system layouts should usually be analyzed from Bussing Arrangements-The method of paralleling
the stability point of view for the three circuit conditions lines or apparatus, or the bussing arrangements, can have
associated with the transient, viz., before, during, and an important bearing on system stability. High-voltage
after the transient. Some features of layout are beneficial busses at the ends of transmission lines or at intermediate
to stability for all three circuit conditions while other fen- points result in smaller change in the transfer reactance
tures are beneficial for one condition and detrimental for at the time of the isolation of a faulted transmission-line :;:
another; hence, the many features of power-system lay- section than for the case with low-voltage busses, since %$
out must be weighed individually in connection with each the latter involves the loss not only of the line but also of i<
circuit condition. the associated transformers. During the faulted condition :i”
Series Reactance-The most obvious method of in- the shock to the system is greater with the high-Volta@! k
creasing the stability limit of a system is to reduce the bus than with t.he low-voltage bus. It is impossible to
fPart X is based largely upon the “First Report of Power System
generalize on the relative merits of high- and low-voltage
Stability,” A.I.E.E. Subcommittee on Interconnection and Stability bus arrangements because the result in any particular case
Factors, R. D. Evans, Chairman, A.I.E.E. Transaclions, pp.261-282, is dependent upon the relative reactance proportions Of
Feb. 1937. It includes some changes and additions due to progress the system, the type and duration of the fault, and the
in the art. For the practices summarized in this report see App., character of system grounding. The results of calculations
Table 3. on a particular system with alternative bus arrangements
chapterl3 Power-System Stability Basic Elements of Theory and Application 453

of longer duration, the shock to the system is more im-


portant and the converse is true regarding !ayout. By
usingreactorsbetween the high-voltage busses, it IS possible
to obtain characteristics intermediate between those for
high- and low-voltage bussing, approaching either to any
16
degree desired. The results of the study in a particular
%--
case of the effect of varying the number of intermediate
switching stations on a long transmission line is shown
in Fig. 62.
Another method of bussing is incorporated in the scheme
known as “synchronizing at the load”” as applied to
metropolitan-type power systems. By metropolitan sys-
tem is meant the type of system that exists in large cities
and is characterized by large turbine-generating units
located close together with short transmission distances.
.6 With this scheme there are no direct ties between syn-
chronous-machine busses but only indirect ties through a
multiplicity of connections at secondary or utilization
voltages. With this layout secondary faults do not have
C a severe effect upon the system and can be “burned clear.”
Faults on a particular generator bus require disconnection
of that unit, but the remaining units accelerate or decel-
erate together. Of course, the shock to the connected load
0.2 is decreased as the speed of circuit breakers and relays
0 0.2 0.4 0.6 0.8 1.0
DURATION OF FAULT-SECONDS is increased.
While “synchronizing at the load” was developed for
rig. 61-Effect of bussing arrangement on stability limits: supplying power to metropolitan areas, the underlying
double line-to-ground fault at sending end.
general principle has been applied in connection with
Al-T,ow voltage bussing. certain long-distance transmission projects, notably for
B-High voltage bussing. the Conowingo-Philadelphia24 and Hoover-Chino lines.
Systc\rnreactance shown in percent; inertia constant H=kilowatt- The modification of the scheme for this application is
s;(:c:onds/kilovolt-ampere. characterized by the bussing of the system only on the
lower-voltage side at the receiving end. On such a system
:trc illustrntedin Fig. 61. For faults of short duration the transmission-line faults result in disconnection of an
c*ll:qc reactance of the system after the
in the transfer entire unit consisting of a generator, sending transformer,
T:bultis cleared is more important than the shock to the transmission line and receiving transformers. Since the
system during the fault, and, therefore, the high-volt,age plan of operation contemplates the disconnection of a unit
INS arrangement gives higher stability limits; for faults for every fault on the transmission line or its associated
apparatus, each circuit can be operated relatively close
Four 75,000~kva generators,Xd’= to its steady-state power limit. Faults on the lolver-
20 per cent) trdnsformer Xg - 12 voltage bus at the receiving end or on the connecting
per centj 2 lines 280 miles long; lines will probably be controlling in determining the
fault dt load end transient power limits. These connections are similar to
those employed on early systems where transmission lines
from separate hydroelectric plants were paralleled only
at the receiver.
The same general principles of system connection have
also been employed in circuits with two-winding gener-
ators and four-winding transformers.13,17 These schemes
improve stability by limiting the severity of short circuit
and by distributing the st,ress among the remaining units.
An important advantage of the double-winding gen-
erator arises from the fact that in the event of a fault
DURATION OF FAULT - SECONDS on one winding the remaining winding can carry load
Fk. 62-Effect of number of switching stations on stability and thus minimize the disturbance to the system that
limit. would result from the disconnection of the faulted ma-
A-Single line-to-ground fault.
chine and the readjustment of load on the remaining units.
L3-Double line-to-ground fault. Another method of bussing is the “loose-linked” sys-
- - --One intermediate station. tern,‘4 which consists of several power areas normally op-
-Two intermediate stations. erated in parallel, being loosely connected for purposes of
- - -Bus fault cleared with no loss of line. synchronizing and interchange of power. The plan of
484 pozrler-System Stability Basic Elements of Theory and Application Chapter 1

operation is such that in any power area t,he largest and the generator output increases and its acceleration
generator or the interlinking ties can be lost without is correspondingly retarded. The effects of these factors
leaving in any area a load greater than the ability to are illrlstratcd in Fig. 63, which shows the st,ability limit
carry it. In the event of a serious disturbance within a as a function of the duration of the fault and the connec, .X;:
power arca, that area including its load and sources of tion of the neutral impedance for single and double line. z’
power is isolated from other power areas by opening of to-ground fnlllts on the high-voltage line at both the 4:;;
the ties at appropriate points. sending and receiving ends of a typical system. The,,, ;T
Grounding-In America it is common practice on curves show that neutral impedances, prefcrnbly resistance ::.
high-voltage systems to ground the neutral solidly and at the sending end and reactance at the receiving end I ‘,
on moderate-voltage systems to ground the neutral sol- help maintain stability. The importance of the methA 1,
idly or through a resistance. For some types of high- of grounding in relation to power-system stability has
voltage systems there has been recently an increased been minimized by the development of high-speed breaken
tendency to provide transformers with sufficient insu- and relays and the trend in the direction of basing system
lation in the neutral to permit grounding through a mod- design upon the more severe types of faults. In general
erate impedance. The ground-fault neutralizer scheme however, factors such as lightning protection and relayi
in which the syst,em is grounded through reactors tuned ing, and cost affected by insulation and interconnectinn
with the system capacitance to ground at fundamental with other systems, rather than stability, determin&iiI
frequency, has not been generally accepted, although it is titular methods of grounding to be employed. For further
being used successfully in an increasing number of loca- discussion, refer to Chap. 19.
tions. These schemes also have arc-suppression charac-
teristics as discussed in Sec. 49. The introduction of 46. Power-System Operation
neutral impedances, by limiting the severity of the fault, Power-system operation is often as great a factor to
increases the stability limits. Two effects may be pres- insure system stability as proper system design. The al.
fbnt: if the impedance is a pure reactance, the current is location of generator capacity in relation to the system-
limited and the synchronizing power is increased thereby; load and circuit conditions is of considerable importance,
if the imp&tnce is a resistance, power is absorbed in it particularly under abnormal circuit conditions. The st&
bility problem can be accentuated by interconnection and
is complicated by the related problems that arise when
frequency control is applied or when the location of gen-
crating capacity is determined by maximum-economy con-
siderations rather than system-load requirements.
Most power systems are designed for adequate sta-
bility under steady-state conditions. There are, however,
many systems where a stability problem is encountered
as a result of a fault, and for economic reasons it is not
always possible to eliminate this condition. Observance
of certain basic operating principles will prevent exceed-
ing the steady-state limits and insure prompt recovery
following a fault.
Adequate spinning-reserve capacity either in the form
of spare generators or reliable interconnections, must be’
available in each load area to insure a steady-state limit
in excess of the power and reactive kva requirements in
event of loss of a generating unit or loss of excitation.
The method of supplying excitation to a system haa
f, 0.6
an important effect on stability. The choice of the bug ‘1
z
P 0.4
voltages to be maintained or compensated for load and 1
circuit changes, can be of great importance. Voltage regu-
lators tend to improve stability conditions by automatic- ’
f I I / I I I I I ) I I I / II (1 11 11 ’
ally changing the excitation in accordance with loads. ‘*
0
0
11111’11111111111111111
IO 20 30 40 50 60 They are capable of sustaining system voltages within
DURATION OF FAULT IN CYCLES ON A 60-CYCLE SYSTEM safe limits even in the event of the loss of excitation on
one of the units. They also tend to keep the field strength
Fig. 63-Effect of grounding method upon system stability.
of individual units within reasonable limits thereby Pre
Curve 2, Percent Z, Percent venting the cascading of trouble following the initial dis;
line-to-ground.. . . . . .
d-Single 13 +i10 tnrbance. Other characteristics of excitation systems and
B-Double line-to-ground.. . 13 +.a their control in relation to stability are discussed in Sec. 47.
C-Double line-to-ground. . 13 0 The increasing use of automatic devices, such as
D-Double line-to-ground. . 0 0 frigerators, water heaters, water pumps, etc., which
Upper set of curves for fault on high-voltage bus at sending end. *This part,icular arrangement is used on the IS-Mile Falls De
Lower set of curves for fault on high-voltage bus at receiving end. opment.20,21
Chapter13 Power-System Stability Basic Elements of Theory and Application 485

not locked out following an outage, results in extremely


higl1 power &ma& when service is restored. A recent
O,ttngc resulted in a peak following restoration of service
,vllich was approximately 4.5 percent more than t.he load
illtcrrupted. Provision must bc made for escess gen-
crntor capacity for a short period n-hen service is resumed,
“r the service must be restored slowly to limit the tem-
porary load until its d’lversity becomes normal. The spin-
,,irlg-reserve capacity for best results should be distrib-
r,tctl In the several load areas so that its availability is
,,ot rcstrictcd by tic-line limitations.
‘l’lle USCof automatic load control on interconnecting
tic lines has increased the practical load limits of these
lirlc:s by preventing the usual drift in the tie-line load,
tt,crcl~y holding the scheduled load well below the tie-line DURATION OF FAULT - SECONDS
limits. These devices are of no value for transient con- Fig. 64-Effect of generator reactance upon stability.
&tionS.
A-Single line-to-ground fault.
Coortlination of stability studies
. and operating in- B-Double line-to-ground fault.
strll(atwns for abnormal condltlons is a matter of con- Solid curves for generator transient reactance .rd’=30 percent;
~itl~;ral)leimportance for inwlring the maintenance of sta- broken curves for z,i’=21 percent.
ljilit,y or avoidance of service interruption. Fault at land end; 2 lines, 280 miles, 3 sections; transformer
When synchronism is lost on a system having syn- zt= 10 percent; 4-70 OOO-kvn generators.
c:jlronous condensers, a state of equilibrium is sometimes
rc>:&:d under which t.hc system will neither accelerate For most present-day systems, steady-state stability
ll()r retard unt,il conditions are changed by switching limits are unimportant. With increased application of faster
,jl)cbr:ttions, or by removal of synchronous condensers. breakers and relays and the logical attempt to increase
‘1’1~:removal of synchronous condensers, either manually the load carried on these circuits, the steady-state stability
()r by underspeed relays, relieves the system of super- limitations will become increasingly important. X useful
~~~sc:cl low-frequency currents caused by condenser esci- criterion of machine performance with reference to steady-
I,:ll,ion, and permits a more rapid restoration of service. state stability is the machine short-circuit ratio. The
short-circuit ratio is a direct measure of the relative pull-
47. Characteristics of Apparatus out torques for generators with the same per-unit escita-
Synchronous Machines-The characteristics of syn- tion. However, for the same current and power factor on
c:twonous machines that are important from the stand- machines of different short-circuit ratios, the relative short-
point of stability are substantially the same in the syn- circuit ratios do not give a direct measure of the relative
c4ronous generator, motor, or condenser. In general, the pull-out torques, because the excitations are not equal.
characteristics of generators are of much more impor- In general, the higher the short-circuit ratio, the higher is
tance because they constitute the largest percentage of the pull-out torque. It is the one constant of the generator
t,hc total connected synchronous capacity and because that comes closest to being a direct index of pull-out
lhey have such an important bearing on the overall sys- torque.
tcm angles. The following discussion will be given in Short-circuit ratio is also of value as an approximate
terms of synchronous generators with the understanding measure of the size of machine. Its use for this purpose
that for synchronous condensers and motors the general depends upon the fact that to a considerable extent any
features are the same but generally of relatively less im- reduction of reactance in a machine below its normal
portancc. value is obtained by derating a larger machine and modi-
The best criterion of generator performance under con-
(litions in which system stability is determined chiefly 3.0
1)~the transient characteristics is its transient reactance
‘Jr more definitely, the direct-axis component commonly
Ggnated as sd’, as discussed in Sets. 15 and 16. The
rffects of decreasing the transient reactance of generators
Won increasing the stability limits for a particular study
~(1 shown in the curve of Fig. 64. The normal value of
the constants of various types of synchronous machines
are shown in Table 4 of Chap. 6. The effect of decreasing
tlle transient reactance upon the cost of a machine is
indicated in a general way by the curves of Fig. 6S. In a I.01 I I I I I I I I I I I I I I I I w
0 20 40 60 80 I00
considerable number of installations, beginning with Cono-
RATIO i$&$$ TRANSIENT REACTANCE-PER CENT
“%o” and including Hoover Darn,sl it has been found
d~sirsble to employ generators of less than normal tran- Fig. LJ-Approximate cost of decreasing the transient react-
sient reactance. ance of salient-pole synchronous generators.
486 Power-System Stability Basic Elements of Theory and Application Chapter 13

Fault at load end, 2 lines, 980 The severity of U~S~m~~trkd system faults is affected
miles, 3 sectionsj transformer)(l = by the negative-sequence impedance of the connected
12 per cent) 4 x,000-kva machines. Amortisseurs or damper windings affect both
generators, Xd’ =I 90 per cent the real and reactive components of this impedance
Machines without damper windings possess the highesi
negative-sequence reactance, but. machines with high-
resistance damper windings POSSCSS the highest negative,
sequence resistance. The curves of Fig. 67 show the coTn
bincd effect of the damper material upon the stabilit;
linlit of a typical system for line-to-line and double line-t+
ground faults on the high-voltage bus at the generator
end. The improvement with high-resistance dampers is
quite appreciable for long fault duration, but for the dura-
0 0.2 0.4 4.v I.6
tion that can be obtained at present with high-speed
DURATION OF FAv;:T - S&DS breakers, the improvement is very much less. In the event
Fig. 66-Effect of generator inertia upon system stability. of system oscillations low-resistance copper damper jvind.
:I-Single line-to-ground fault. ings produce the greattest damping of the mechanical
J3-Double line-t,o-ground fault. movement. However, this effect is unimportant during
-Minimum WA? (31 X lo6 lbs-ftz). and following a system fault except in the rather rare case
---_ 50 percent ntltlitionul TVR?. in which the system is so constituted that pullout &kc8
-- -100 percent additional lVR*. place as a result of compound oscillations following a tliy-
fying the current-carryin g parts to meet the reduced turbance. To obtain t,he partial advantage of the high
vnl11es. loss associated with high-resistance dampers at times of
The inertia of a synchronous generator or motor is also
a factor in the stability problem since it affects the nat-
ural period of system owillation, or the time required to
reach a point beyond which recovery would be impossible.
5 0.0
Figure GAshows the results of calculst,ions for various val- 3
ues of generator inertia upon the stability limits for a par- 2 0.6
ticular system. The range of inertia constants for various
types of synchronous machines is shown in Table 8, and
more specific data based on speed and kve are given in
Chap. 6, Part XIII. The cost of adding inertia to large
vertical waterwheel generators increases about one-fifth g 0.8
as fast as the inertia. In a few cases, including Hoover
Dam, where calculations have indicated that a particular a5 0.6
system lvould operate relatively close to the stability 0.4
limits, generators of higher than normal inertia have been 0 IO 20 30 50 60
DURATION OF FAULT IN CYCLES ON A%-CYCLE SYSTEM
installed.
Fig. 67-Effect of damper-winding material upon stability
TABLE S-TYPICAL INERTIA CONSTANTS OF limits.
SYNCHRONOUS MACHINES*
System Same as Fig. 63-C.
A-High resistance. B-No dampers. C-Copper.
Inertia Constant II
Type of hlachine Upper curves for line-to-line fault.
Stored Energy in Kw-set per Kva**
Lower curves for double line-to-ground fault.
Turbine Generator
Condensing 1800 rpm 9-6 unbalanced faults and the damping of oscillations ass+
3600 rpm 7-4 ciated with low-resistance dampers, the generators of one
Non-condensing 3600 rpm 4-3 installation, i.e., Is-Mile Falls,l”.20 were supplied with a
Waterwheel Generator
Slow-speed (<200 rpm) 2-3
special type of damper winding which consists of a double
High-speed ( > 200 rpm) 2-4 cage arrangement in which the outer row of bars is made of
Synchronous Condenser*** high-resistance material and the inner row of bars is made
Large 1.25 of a low-resistance material imbedtled in the iron. For the
Small 1.00 double frequency associated with negative-sequence, the
SynchronousMotor with Load 2.00 copper bars possess a high reactance and, therefore, force
varies from 1.0 to 5.0 and most of the current through the high-resistance bars. For
higher for heavy flywheels / the low frequency associated with the system oscillations,
*For more specific figures, see Fig. 75 of Chap. 6. the current varies inversely with the’ resistance of the
*‘Where range is given, the first figure applies to the smaller kva damper bars and allows most of the current to flow through
sizes. the copper winding. The benefit from high-resistance
***Hydrogen-cooled, 25 percent less. damper windings is decreased as the fault duration is de
chapter 13 Power-System Stability Basic Elements of Theory and Application 457

creasedby t,hc use of faster breakers and relays. Damper


,,,indings also have characteristics which tend to suppress
,pont:~ncolIs huntin, r and to rcclllcc system overvoltages
Lm,l recovery rates arising from short circuits; in these
r,spe(ats, low-resistance copper dnmpers are somewhat
m,,rcL&e&w than high-rcsistancc dampers.
\viLh the incrcnse in size of D. wncrator units, the grcatcr
,,,,,,(A,~ntrationof power on a single bus has increased the
,l,,fy on circuit, brcakcrs and the arca affected by a fault
,),, ,)I‘ near the bus. Thcsc effects can be minimized by the
,,sc of the two-winding generator’3,‘7 in which the two
,,,m:Ltllre windings arc connect,otl only through their
n,,lt,l~:~lcorlpling which can be controlled by suitable de-
sigrl. Gcncrators of this charact,tr lend themselves to in-
,.,,rporat,ion as units in the system layout known as
~~,~ncllronizing at the load ” or its variations as described
,~~~:viorlsly.
Excitation SZwtems-Control of the excitation system
,III synchronous machines provicles a means for improving
st,:ll,ility limits for transient condit,ions and also for steady-
St:lt(: conditions. Excitation systems that are effective
fl.0111the: standpoint of . stability are commonly termed
,l~~~~~k-resp,~nse esclt:rt,lon systems, the principal features
,)j which are:
I. Escitcr of quick response,i.e., of high rate of build-up
:urtl of high “ceiling” voltage.
2. A reli:Ae s,~~,x of power to the exciter.
3. (2uick-resp,)ntliIlg regulntor.
Is:sciter response is the rate of build-up or build-down
I)[ I hc main-exciter voltage when a change in this voltage
is cl~mantlec~by the action of the voltage regulator. The
twponse of the exciter was formerly expressed in “volts
pw second” corresponding to the average value effective
I hro~~ghan interval of one-half second beginning at rat,ed-
load field voltage. This rate is standardized as the nu-
wt+al value obtained, called the response ratio, by di-
vitlillg thtl average vahle of volts per second in the same
I inw int ctrvtd by the rated-load field voltage. The method
ol cl,~tc~rminingesciter response is illustrated and formal
tl&itions are given in Chap. 7. Exciter response ratio
()I’0.5 on the per unit basis just described is now standard;
r:~,,r rwponse up to 2.0 is regularly available at a small
:t,ltlit,ionnl cost, and still faster response can be provided.
‘I’hc characteristics which an excitation system must
Iuv,> t,o ,A!tain the benefits of qlick response include a
Iligil-wiling voltage as well as a high rate of build-up.
‘1’1~1wiling voltage of an exciter varies through quite a
\vi(I,> range depending upon the particular design. The
:l(xl~~alvalue in a particular case is adjusted so as to give
t,h(: d&red response through t.hc half-second interval.
I.~nlly the ceiling voltage will be considerably more than
50 percent above the normal exciter voltage for the
t~~:~simllrnratccl load.

Fig. 68--Typical voltage regulator for control of the quick-


“sPonse excitation system for a large waterwheel generator.
TYPe BJ indirect-acting exciter-rheostatic voltage regulator.
(a) Alain control clement in projection-type case with glass cover.
(1)) Cubicle-type assembly of regulator-contactor panel and
plate-type motor-operated main-exciter field rheostat. (b)
Power-System Stabil~it~ Basic Elewerlts of Theory and Application Chapter 13

R,=SHUNT FIELD FIXED R


R,,=FIELD FORCING-UP R
R,,=FIELD FORCING-DOWN R
RA,=MOTOR-OPER SHUNT FIELD
RHEO CONTROLLED BY
CROSS-CURRENT PE. REGULATOR NORMAL-RESP
COMPENSATOR SERIES CONTACTS
FIELD R,,=DIFF FIELD FIXED R
QR = REGULATOR OUICK-RAISE
FORCING CONTACTOR
OL= REGULATOR QUICK-LOWER
i FORCING CONTACTOR

Fig. 63-Elementary schematic diagram of Type BJ regulator illustrated in Fig. 68.

The exciters, regulators, and other voltage-control eqrlip- internal voltages of a lvaterwheel generator connected to
mcnt required for quick-response excitation are built in a typical system subjected to faults is illustrated in Fig. 70.
various forms, which are discussed in detail in Chap. ‘7. The internal voltages are calclllnted by the method out-
The most common system in recent years has been that lined in Chap. 6 for two conditions, which give per-unit
rlsing a separately-escited main esciter and an esciter- demagnetizing currents of about 1.,5 ant1 1.0 for line-to-
rhcostatic regulat,or such as the BJ type illustrated in line and line-to-ground faults, rcspectivcly. These curves
Fig. 68 and shown schematically in Fig. 69. The main are based on constant phase displacement between the
csciter is of liberal design having specially designed field machine ancl the receiver. The correction for this factor
circuits to reduce the time constants to a minimum. n-ould slightly reduce the voltages and alter the shapes for
I<scitation for the separately-excited field is under control all curves without changin g the relative effects. Quick-
of the voltage regulator and is supplied by a flat-com- response exciters do not make very important gains in
pounded, self-excited d-c generator, called the pilot exciter. main-machine flux for line faults o’f the short durations
The exciter-rheostatic regulator has two sets of con- possible with high-speed circuit breakers and relays. How-
tacts: ever, the flux conditions within the machine will continue
1. Kormal-response contacts that operate for normal below normal throughout the “first swing,” even though
load changes causing small voltage changes, and which the fault has been removed, particularly if a line section
control the motor n/1 driving rheostat RRH to increase or has been removed from the circuit for isolating the fault.
decrease the exciter field current. This circumstance increases the scope of beneficial action
2. Quick-response contacts which control the high- possible by a quick-response excitation system. If the
speed contactors &R and QL, and which operate for sud- line faults are not cleared in the normal high-speed man-
den, large changes in system voltage and excitation re- ner, a very substantial improvement in the stability limits
quirement,s. The normal-response contacts are sensitive is accomplished. With exciter-response ratios greater than
to a change in a-c voltage of s of one percent,. These 0.5 per unit, it is possible not only to overcome the demag-
contacts control the main-exciter motor-operated field netizing action of the fault currents, but actually to in-
rheostat. Modern regulating equipment is designed to crease the main-machine flux in the time normally required
initiate excitation corrective action within a period of 3 for the system to reach the critical point in its oscillation.
cycles on a 60-cycle basis. This action is controlled by the Quick-response excitation provided one of the earliest
quick-response contacts, which in combination with the methods used for improving t.he transient-stability limits
high-speed contactor start to change the exciter-field cur- of systems. Its importance in this respect has, however,
rent within 3 cycles after the generator voltage has de- been minimized by the developments of high-speed circuit
parted from normal by an amount equal to npprosimately breakers and relays which limit the duration of fault
three times the sensibivity setting of the quick-response currentIs and their demagnetizing effect H.
contacts. Llnother feature of quick-response excitation systems
Quick-response escitation systems tend to improve sta- is the ability to increase the escitation to meet t.he re-
bility limits of power systems in three ways: q\lirements of a system arising from the loss of other
1. 1Iairit:Lining or increasing machine flux against tlemng- sources of excitation, as from the disconnection of a gen-
netizing action of fault currents. erator or condenser. This feature cannot, of course, be
3. Supplying deficiency in system excitation due to loss of supplied by high-speed circuit breakers. In order to be
other sourcesof excitation. effective in this respect, a quick-response escitation SYS- ,+,,
3. Increasing steady-state stability limits by facilitating w- tern must have a relatively high ratio of ceiling to normal- 5
tion in the region of dynamic stability. operating voltage and the regulating equipment must be
The effect of quick-response on the magnitude of the such as to permit operation under these conditions for
Chapter 13 Power-System Stability Basic Elements of Theory and Application 489

tion of a station at its rated load being dependent upon the


functioning of a regulator. Consequently, the choice of
regulator has been determined from its performance under
transient conditions and its maintenance under ordinary
operation.
High-Speed Circuit Breakers and Relays-The
duration of a fault condition has a very important effect
106
LINE-TO-LINE
-. -
) I”R~NI~ / 1 1 on the stability of a system. The fault condition reduces
I04 -
FAULT /RESPONSE=2.q synchronizing power, (1) directly by altering the equiva-
lent-circuit constants and (2) indirectly by reducing the
102 - /’
HI.0 effective machine voltages through the demagnetizing
100 \ /
I Y
action of fault currents. The stability limits 3s affected
I
by the speed of breaker and relay operation vary through
a wide range from (1) the limits corresponding to sus-
I-
tained faults to (2) a mere switching operation assuming
; 96
02
extremely fast fault isolation. High-speed circuit break-
2 94 ers and relays are capable of covering most of this range
and thus constitute a very important measure for in-
-: 92 creasing the stability limits, particularly for transmission
w
’ I I systems.16
sgo’ ’ ’
0.2 ’ ’
0.4 ’ ’
0.6 ’ 0.8 1.0 1.2 The relation between the speed of fault isolation and the
2 TIME IN SECONDS
2
transient-stability limits for a typical trjnsmission system
> is indicated in Fig. 71, which also gives the impedance
2 106
constants of the various system elements. The system is
2 assumed to be subjected to a fault on one line near the
&j 104 RESPONSE=Z.
I-
z high-voltage bus at the sending end and to be cleared by
102 the opening of the two breakers simultaneously. The
9
2 100 curves assume waterwheel-type generators, and receiving-
A
end machines of relatively high inertia. The calculations
a 98 mere made for the four different types of faults shown on
the curves, which are plotted in terms of the time required
96
for the isolation of the fault and the ratio of the power that
can be transmitted to the power limit corresponding to the
92

90
0.2 0.4 0.6 0.6 1.0 1.2
TIME IN SECONDS
Fig. ‘IO-The effect of different speeds of exciter response on
the internal voltage of a waterwheel generator with damper too
windings. System shown in the insert is subjected to line-to-
line and line-to-ground faults at sending end. The ratios of
ceiling to normal exciter voltage are 2.2, 1.6 and 1.6 for per-
unit exciter responses of 2.0, 1.0 and 0.5, respectively.

t,hclength of time necessary for some readjustment of the t 70


system. Ordinarily the speed of exciter response is of Ii
sccondnry importance in comparison with the exciter 5 60
I’:mvc
h ‘. However, quick-response excitation systems nor- 3
ln:llly possess the essential exciter range and whatever g 50
:Ldvanta.gethat resides in the quicker response.
Quick-response excitation systems also provide means 40
for increasing the steady-state stability limits by facili-
Mng operation in the zone of dynamic stability as dis-
cllssed in Sec. 17. In a few cases it appears probable that 20
some beneficial action from regulators in the region of 0 4 8 12 I6 20 24 28 32 36 40 44
dynamic stability is required to explain the absence of DURATION OF FAULT IN CYCLES OF 60-CYCLE SYSTEM
Pollouts. In general, however, since the steady-state limits Fig. 71-Effect of duration of fault on power limits for differ-
are higher than the transient limits, the favorable charac- ent kinds of faults.
teristics of a voltage regulator to increase the steady- A-Single line-to-ground fault. C--Double line-to-ground fault.
state limits has been without real significance. There is B-Line-to-line fault. D-Three-phase fault.
also the question as to the desirability of having the opera- System reactance shown in percent.
490 Power-System Stability Basic Elements of Theory and Application Chapter I3

switching out of one section of the transmission line. The percent more than the standard five-cycle breakers for the
dotted lines show the loads which can be carried with sus- same rating. The standard operating time for 69 kv and
tained short circuits of the various types assuming quick- below is 8 cycles. It is interesting to note that at the time
response excitation systems capable of preventing demag- this book was originally published (1942) g-cycle breakers
netization of the machines. were standard up to 230 kv.
The curves in Fig. 71 apply to a system subjected to a For composite systems with long-transmission lines from
fault at the sending end. The relative stability conditions a source of power and for interconnecting lines between I’I:
for the fault at sending and receiving ends of a somewhat various parts of the receiver, system studies will frequently ;$:
different system were given in Fig. 63 which has been dis- show the desirability of using high-speed circuit breakers ‘T
cussed previously in connection with the use of neutral and relays in order to increase the stability limits. In a lip
impedances. A moderate value of neutral resistance at the number of such cases it will be important to extend the :$.
sending end can make a fault at that end on a grounded- application of the high-speed breakers to interconnecting *
neutral system relatively less severe than a fault at t.he re- lines of the receiver system. Otherwise, the stability limits ,_
ceiver. However, the gains in stability due to the use of are determined not by faults on the main transmission line
high-speed circuit breakers are of the same order for faults but by faults on the receiving system, even though it is
at the sending or receiving ends of the transmission system. operating at lower voltage with transformers between it
On metropolitan-type systems the permissible time for and the transmission line.
isolating the fault will be relatively longer than for trans- This development. in the speed of circuit breakers has
mission systems since the latter are usually operated brought about important changes in the relaying of tran+
closer to the stability limits. Thus in the metropolitan mission lines. With fast circuit breakers it is no longer
systems it is possible to introduce reactance in the system feasible to contemplate relay-operating times of one-
in such a way as to limit the duty on circuit breakers. quarter second to three seconds or the use of time intervals
This problem can convenient,ly be studied by the short- as the basis of discrimination. This has led to the use of
cut method23 discussed in detail in Part VIII. distance or current-balance types of relays which are
The curves used in this method indicate that by taking capable of simultaneous action for the middle section of a
advantage of the faster speeds made possible by the recent t,ransmission line with high-speed sequential tripping for
developments of circuit breakers, increased amounts of re- the end sections.
actance can be introduced in the system either to reduce In cases where the transmission system is operated rela-
the duty on circuit breakers or to increase the continuity of tively close to the stability limits there is considerable
power supply or reliability of the service to the customer. advantage in providing simultaneous breaker operation,
The speed of circuit breakers and relays in relation to In general, such relay operation can be obtained by funda-
power-system stability can conveniently be analyzed under mental-frequency relays operating in conjunction with a
three headings as follows: signal transmitted by pilot wires or carrier current between
1. Conventional or slow-speedbreakers and relays for fault the ends of the line section. This has brought about an
isolation. important development in the application of high-speed
2. High-speed breakers and relays capable of isolating fault relaying with superposed carrier-frequency. The relaying
in time to improve stability limit. quantity to be transmitted by carrier frequency was se-
3. High-speed breakers and relays with reclosure in time to lected initially as some electrical indication, such as direc-
improve stability limit. tion of the power flow, but more recently as the position of
The curves of Fig. 71 show that conventional slow-speed various fundamental-frequency relays which indicate the
circuit breakers and relays of the type commonly in use existence of a fault on the system within predetermined
prior to 1929 were so slow from the stability point of view zones. The carrier-current and pilot-wire relay systems
t.hat the limits corresponded to sustained faults. The power also provide opportunity for including relay measures for ’
limit for the three-phase fault is almost negligible with the the prevention of undesired breaker operation in the event
conventional slow-speed breakers formerly in use. The that the system does pull out of step. Reference should $I
benefits which arise from the use of high-speed circuit be made to Chap. 11 for further, information on circuit- 1,
breakers and relays in maintaining stability depend upon breaker and relay applications. .
isolating the fault in an interval of time which is short in Reclosing Circuit Breaker-Reclosing circuit break- i’
respect to the period of system oscillation. The preceding ers provide a means for carrying one step further the $-
discussion has been based on the isolation of the fault in a advantages possible from high-speed fault clearing. For $$
single step. For sequential operation the time permissible lower-voltage systems and feeder circuits, automatic rB- “<
for each breaker will be less than that shown but need not closing breakers make it possible to maintain the stability @?
be reduced to half value. This is, of course, due to the fact of a system with induction-motor load. Disconnection of g
that the stability conditions are generally much improved the source is required for the suppression of the arc in the
upon the operation of the first circuit breaker. fault, but the total time required for disconnection and for
The need for high-speed circuit breakers has brought reclosure should be made sufficiently short as to prev
about the development and general use of circuit breakers pullout of induction motors. Where synchronous machi
with shorter operating times. At present, standard breakers can maintain the arc, it is necessary to isolate the affec
115 kv and above have an operating time of 5 cycles, ex- line and to reconnect it in a period of time that is relat
cept 230-kv standard breakers, which have an operating short with respect to the period of system oscillati
time of 3 cycles. Three-cycle breakers cost about five stability is to be maintained.26B34Hence, if automatic
chapter 13 Power-System Stability Basic Elements of Theory and Application, 491

closing breakers are considered for maintaining the sta-


\,ility &on a transmission system, it becomes a practical
IlecessltY to use carrier-current or pilot-wire relaying.
The esistence of multiple or repetitive lightning discharges
mav constitute an important factor in limiting the appli-
,ation of reclosing breakers for maintaining stability.
The selection of the operating speed required of high-
speed reclosmg breakers is dependent upon a compromise
t,ctwcen two conflicting factors. One of these is the maxi-
nlum permissible time between the inception of the fault
and t.he final reclosure as determined by the power-system
loat1and synchronizing-power conditions. The other is the
&onization time, the minimum time that must be allowed
in order to be reasonably sure that the arc will not reignite
lIntI thus create a second fault condition. In many cases
lvhcre high-speed reclosing is desired, there is sufficient
Ljlnc to permit successful application.
The de-ionization time depends upon the circuit volt-
TIME IN SECONDS
agc, the conductor spacing, t,he fault current, and weather
Fig. 72-Permissible time for breaker tripping and reclosure
c:ontlitions. Furthermore, the reestablishment of the arc without causing loss of synchronism with gang operated
:Jt,cr an interval is a matter of probability and perhaps breakers.
twenty tests may be required to establish a single point
on a 9.5percent probability curve for a single combination over the tie line is then expressed as a percentage of the
of circuit voltage, fault current, conductor spacing, and maximum synchronizing power over the tie line and used
\vckather conditions. For these conditions the available as the ordinate of the curve of Fig. 72. If the capacity
t(bstdata on de-ionization time, although covering several and inertia constants of the two systems are kva,, kvab,
hlmclrcd individual tests, is not considered to cover the and H,, Hb, then the equivalent inertia constant H,,,,
ficltl adequately for the purpose of establishing limits. can be determined from Eq. (37), Sec. 22. The inertia
From the available information26 the estimated de-ioni- factor to be used in the curves of Fig. 72 is obtained from
zation time for successful reclosure is given in Table 9.
H,sc,,kva,
Inertia Factor= TL (‘361
TABLE B-MINIMUM DE-IONIZATION TIME FOR RECL~SING kw
BREAKERS
where TLk, is the tie-line load in kw. Reclosing breakers
System Voltage Cycles on 60-Cycle Basis have been used to improve the stability conditions on a
Line-to-Line Kv number of 132-kv systems, notably of the American Gas
95% Probnbility 7557, Probability and Electric Company34 and of the West Penn Power
23 4 Company. The important advantage of reclosing break-
46 5 3.5 ers arises from the fact that their use can frequently con-
69 6 4 vert an unstable tie line to one which can be considered
115 8.5 6 as a firm-power source and thus justify a reduction in the
138 10 7.5 connected generating capacity.
161 13 10 Single- Pole Reclosing Breakers-During World War
230 II it became necessary due to increasing demand for power
to use single-circuit tie lines between systems to transfer
From the standpoint of maintaining stability, the max- firm blocks of power. Single-pole reclosing breakers have
imum permissible total time from the inception of the been used successfully in this application. Ground-fault
fault to the final reclosure varies over a wide range, de- neutralizers are useful in this application, but provide
Pc!ndingupon the system, location and severity of the fault, improvement only in t,he case of single line-to-ground
Imd the type of circuit breaker, that is, whether three-phase faults, whereas single-pole reclosing breakers improve the
1~sdiscussed in this paragraph or single-phase as discussed stability limits of a single tie line for all types of faults, ex-
in the next. The permissible reclosure time can be cal- cept three-phase. In this case the operation is that of a
culated with satisfactory accuracy by methods previously gang-operated reclosing breaker.
cliscussedin this chapter, or by reference to the curve9 The advantage of single-pole operation lies in the fact
of Fig. 72. These curves apply to two systems of rela- that power can be transferred over the unfaulted phase(s)
tively high inertia connected through a tie line of rela- during the period when the breakers are open to clear the
tively high reactance. In order to use these curves it is fault. Since most line interruptions do not permanently
necessary to determine, first, the synchronizing-power ground a phase conductor, successful reclosure is obtained
limit as determined by the quantity 3: where E is the in the majority of cases and thus restores the system to its
original condition without at any time reducing the power
nominal system voltage line-to-neut,ral and X is the limits to as low a value as would be the case if all three
transfer reactance per phase. The load to be transferred conductors were disconnected.
492 power-system Stability Basic Elements of Theory and Application Chapter 13

If single-pole reclosing is to be used, the transformer 48. Double Line-to-Ground Fault on Single Tie
banks at both ends of the tie line should be grounded sol- Line
i(lly or through low values of impedance in order that The transient-stability performance of a single tie line
power may be transferred during the breaker operating between two systems can be calculated using the step-by- :
period. step procedure discussed previously. The only difference
A comparison of three-pole and single-pole reclosure between this calculation and the previous examples lies in
has been made for the system shown in the insert of Fig. the fact that the sequence networks must be set up so that
73. The result of stability calculations for the two types the power transferred during the period the breakers are
of reclosure are plotted in Fig. 73 in terms of the per- open can be determined.
In calculating a transient-stability problem involving ,
single-pole reclosing, it is convenient to divide the sequence
of operations into four steps as follows: ‘3
_’ :
1. Condition before the fault.
2. Condition during the fault.
3. Condition with faulted phase(s) open.
4. Condition after fault (line re-energized).
In setting up the sequence networks for condition 3 it is
generally sufficiently accurate to use connections 71to r
inclusive of Fig. 21, Chap. 2, which assumes equal shunt ,,
capacitance on all phases. A more accurate calculation can
be made using the method presented in Fig. 22, Chap. 2.
Reference 41 gives the sequence-network connections.
Figure 74 presents the results of investigations of over
100 practical solutions. 42These curves apply only to double
line-to-ground faults and can be used to estimate breaker
requirements under proposed operating conditions and
also to estimate the transient performance of existing lines.
In the study upon which these curves are based, the
sending and receiving systems were assumed to be made up ”
0 4 0 I2 I6 20 24 26 32 36 40 44 48 of 1800-rpm, 80-percent power-factor machines operating
PERMISSISLE RECLOSING TIME-CYCLES at full load with necessary excitation. Typical system
constants were used. The shunt loads were assumed to be
Fig. 73-Comparison of three-pole and single-pole reclosing
breakers from standpoint of permissible transmitted power
85-percent power factor. In each case the line regulation
and reclosing time for clearing one line-to-ground fault and was adjusted to ten percent. In certain cases this required
maintaining stability for the system shown in the insert. synchronous condensers at the receiving end to furnish
the necessary reactive kva in excess of the capacity of the
A--Three-pole reclosing breaker, 4-cycle opening time.
B-Single-pole reclosing breaker, 4 to lo-cycle opening time.
receiver generators. The inertia of the condensers is not
C--Stability limit for system, one phase switched open-system included in the swing calculations because it is usually
same as insert except for theoretical condition of zero-sequence found to be negligible.
impedance equal zero-IO-cycle opening time. Conventional a-c network calculator studies were carried
D-Stability limit for system, one phase switched open-system through for each principle system chosen until the maxi-
same as insert but grounded at fault end only. mum length of line was determined for which transient
stability would be maintained keeping all system elements
missible transmitted loads and reclosure times. The curves constant except the line length. These curves give only the ,: j
show the advantages of single-pole reclosure which can be minimum reclosing equipment that can be safely applied.
used (1) to transmit greater power, (2) to provide greater Allowance should be made for system growth.
deionizing time, (3) to permit the use of slower-speed These curves give transient-stability solutions using
breakers for fault clearing or reclosure, or a combination different types of reclosing equipment. Double line-to- :
.%.S
of these three. The power-transferring ability of a system ground faults were used in each case.
for a sustained one-phase open condition varies with the To determine the maximum power which
zero-sequence impedance of the circuit between the limits transferred over a tie line, plot the ratio, PS/PR, on the
of (1) infinite impedance which obtains with the un- proper “(miles/kv*)PR” curve for the reclo
grounded system, and (2) zero impedance, a theoretical uncler consideration. The ordinate of the pl
condition which is rarely approached even for solidly- the maximum power which could be safely
grounded systems. The practical case for grounded systems per unit, based on receiving-end generation.
lies between these two extremes. are not intended as a solution of all problems cancer
The single-pole reclosing breaker is somewhat more high-speed reclosing, but are presented merely as a
expensive than the three-pole breaker because of the three These general curves are calculated to apply specifical
separate mechanisms and the more complicated relay to tie lines between systems on which steam turbin
system required. predominate. Detailed calculations should be made whe
chapter 13 Power-System Stability Basic Elements of Theory and Applicataon

0.6

IA I.0 I I,, I I
I I III
I-
5
I POLE 30CYCLES
2
5
CL 0.8
(cl
II/i 1 (d)
0.8

0.6 0.6

0.4

/7 I I
0.2 A ,/5.0
/-

PS/PR PS/PR
h!. 74-T ransient-stability limits for a double line-to-ground fault on a single tie-line between two systems on which a*,~-
turbines predominate.
PS and PR=sending and receiving-end generation, in mw, respectively; KV=Line-to-line kilovolts.
494 Power-System Stability Basic Elements of Theory and Application Chapter 1;

marginal or unstable conditions are indicated by these system. In America, however, little use is made of this type
curves. of arc-suppression device as dependence is placed on circuit
breakers and relays for automatically isolating a faulty
49. Other Methods of Increasing the Practical section of line. Circuit-breaker schemes have the merit of
Operating Power Limits suppressing all types of faults that occur on systems r+
Flashover-PreventionandArc-Suppression-Adif- gardless of whether they are of the single line-to-ground ,,r
ferent approach to the problem of improving the practical more severe types. In addition they permit grounding the
operating power limit of a system is obtained by the use system so that the tendency for a single-phase fault t,,
of flashover-prevention and arc-suppression measures. It develop into a multi-phase fault is minimized. See als,,
is obvious, of course, that a system rarely subjected to Chap. 19.
faults can be operated relatively close to the stability High-Voltage D-C, and Low-Frequency A-C
limits. Consequently, under some conditions it is more Transmission--Low-frequency a-c systems have been pr+
advantageous to spend money for minimizing the likcli- posed frequently for increasing the practical operating
hood of faults than for increasing the capacity of the SYS- stability limits of long-distance transmission systems,
tern to withstand the system disturbances resulting from More recently d-c transmission has been proposed w
faults. a means for avoiding the stability limits since such a sys.
The principal cause of flashover on high-voltage lines tern inherently provides a non-synchronous tie. In Amer.
is lightning. Much has been accomplished during the past ica, 6O-cycle a-c is very generally established for utilizb
fifteen years to minimize flashovers resulting not only tion. Consequently, the proposals to use low-frequency
from induced strokes but particularly from direct strokes.* a-c and high-voltage d-c transmission schemes have in.
Increased transmission-line spacing and increased insu- eluded conversion means at the receiving end. In general
lation in the form of insulator strings and wood have t,he use of the low-frequency a-c system involves no ney
generally been adopted. On the higher-voltage lines the problem in apparatus or application so t,hat its use is noi
use of ground wires is of great value when suitably located hindered on this account, although static apparatus migh{
with respect to the conductors to be protected. Special find application in the field of frequency conversion. In t,hc
efforts have been made to reduce the tower-footing resist- case of d-c transmission, however, the conversion from a-(
ance to a relatively low value in order to prevent a flash- generation to the d-c high voltage required for the trane
over of the insulator string as a result of the building up of mission line involves rectifiers for which there is no corn,
high potent,ial due to the flow of lightning current through parable operating experience; in the case of the inverten
the tower to ground. at the receiving end still less work has been done. Con,
The use of the ground wires reduces the zero-sequence siderable interest has been displayed in d-c transmission
impedance of the system and thus increases the severity but it is still generally considered impractical especially in_
of the shock resulting from a single or double line-to-ground this country. During the recent war the Germans consid-
fault. With the development of high-speed circuit breakers ered d-c transmission particularly as a means of gettirig
and relays these faults can be cleared promptly; conse- power from Scandinavian peninsula to Germany. D-o
quently, the use of ground wires results in a gain from the transmission can show economic gains over high-voltage
stability point of view by reducing the number of flash- a-c transmission only where large blocks of power are to
overs which overbalances any disadvantage from the be transferred40 for extremely long distances. Even thin,?
standpoint of the shock to the system in case the fault d-c transmission may not be economical if it is desired tO$$
occurs. tap off intermediate loads because of the high cost of the$
The fault-suppression measures have as their object the terminal equipment. Much work remains to be done before ;:
interruption of the power-arc following a flashover without d-c transmission can seriously compete with a-c trau+:...:;
the necessity for isolating the affected circuit. The use of mission.
fused arcing rings or special tube-type protectors in parallel At the present time the limitations in 60-cycle syste
with the insulators permits flashover to take place through from the standpoint of system stability, are not of SU
a path that insures the subsequent interruption of the cient importance as to justify the adoption of either 1
power arc. Lightning arresters distributed along the line frequency a-c or high-voltage d-c transmissionzgv”. The :
will accomplish this same general objective. See also possible field for d-c transmission depends largely on
Chap. 17. practical necessity for transmitting power to consider
Arc-suppression devices of the ground-fault neutral- greater distances than those used heretofore, on the
izer or Petersen-coil type have received consideration for fulness of its operating characteristics aside from stabil
minimizing circuit outages in connection with multiple- and on the future development of conversion appar
circuit systems of the type in common use and have been In t.his connection it should be noted that the serie
used in the single-circuit Hoover-Chino transmission line pacitor offers tremendous improvement in a-c transmi
*Referenceshould be made to Chaps. 16 and, particularly, 17. at normal frequencies.
p

chapter 13 Power-System Stability Basic Elements of Theory and Application 495

STABILITY REFERENCES IN THE ENGLISH LANGUAGE


~1,~: “First Report of Power System Stnbility,” item 33, includes 21. Stability Precautions on P 220-Kv System, by H. II. Spencer,
a list of 180 nrticles, which are arranged in chronological order and Eleckical World, Aug. 15, 1931, pp. 276-280.
bear symbols indicating their character. 22. Proposed Definitions of Terms Used in Power System Studics-
1. Experimental Analysis of Stability and Power Limitations, by Report of Subject Committee on Definitions, by II. 1~. Sels,
11. D. Evans and R. C. Bergvall, A.I.E.E. Transactions, 1924, h.1.E.E. paper 32&I-2, Abstract Electrical Engijtccring, 1932,
I)!). 39-58. Disc., pp. 71-103. p. 106.
2, l’ower System Transients, by V. Bush and R. D. Booth, 23. Generalized Stability Solution for RIctropolit:ln-Tyl,t! Systems,
..L.I.E.R. Transaclions, Feb. 1925, pp. 80-97. Disc., pp. 97-103. by S. B. Griscom, W. A. Lewis, and W. R. Ellis, A.I.E.E. Tm~s-
3. ‘rransmission Stability, Analytical Discussion of Some Factors aclions, June 1932, pp. 363-372. Disc., pp. 3i3-374.
p:ntering into the Problem, by C. L. Fortescue, A.I.E.E. Trans- 24. Stability Experiences with Conowingo Hytlro-Electric Plant,
aclions, Sept. 1925, pp. 984-994. Disc., pp. 994-1003. by R. A. Hentz and J. W. *Jones, A.I.E.E. Transaclions, .Junc
.I, Practical Aspects of System Stability, by Roy Wilkins, A.I.E.E. 1932, pp. 3i5-384. Disc., p. 384.
~rcmsnckms, 1926, pp. 41-50. Disc., pp, 80-94. 25. Adjusted Synchronous Reactance and Its Relation to Stability,
5, Further Studies of Transmission System Stability, by R. D. by H. B. Dwight, General Electric Review, Dec. 1932, pp. 609-61-l.
p:vans and C. F. Wagner, A.I.E.E. Transaclions, 1926, pp. 26. Keeping the Line in Service by Rapid Reclosure, by S. B. Gris-
5 l-80. Disc., pp. 80-94. corn and S. J. Torok, The Electric Journal, I\Iay 1933, p. 201.
6. h llechanical Analogy of the Problem of Transmission Stabil- 27. Symmelrical Components, by C. F. Wagner and R. D. Evans (a
ity, by S. B. Griscom, The Electric Journal, May 1926, pp. book), McGraw-Hill Book Company, New York, 1933.
230-235. 28. Quick-Response Excitation, by W. A. Lewis, The Electric Jour-
7. I’;scitation Systems: Their Influence on Short Circuits and nal, Aug. 1934, pp. 308-312.
blaximum Power, by R. E. Doherty, A.I.E.E. Transactions, 29. Constant Current D-C Transmission, by C. II. Willis, B. D.
July 1928, pp. 944-956. Disc., pp. 969-979. Bedford, and F. R. Elder, A.I.E.E. Transaclions, Jan. 1935, pp.
8. System Stability with Quick-Response Excitation and Voltage 102-108. Disc., Mar. 1935, pp. 327-329, and Apr. 1935, pp.
Rqulators, by J. H. Ashbaugh and II. C. Nycum, The Electric 447-449. Aug. 1935, pp. 882-883.
.Iourxul, Oct. 1928, pp. 504-509. 30. Steady-State Solution of Saturated Circuits, by Sterling Beck-
9. Transients Due to Short Circuits-A Study of Tests Made on with, A.I.E.E. Trasactions, July 1935, pp. 728-734.
the Southern California Edison 220-Kv System, by R. J. C. 31. Engineering Features of the Boulder Dam-Los Angeles Line, hy
\Vootl, L. F. Hunt, and S. B. Griscom, A.Z.E.E. Transactions, E. F. Scattergood, A.I.E.E. Transacliorhs, ;\Iay 1935, pp. 494-
.J:rn. 1!128, pp. 68-86. Disc., pp. 86-89. 512. Disc., 1936, pp. 200-204 and 208.
10. Static Stability Limits and t,he Intermediate Condenser Station, 32. The Scientific Basis of Illuminaling Engineering, by Parry hloon
by C. F. Wagner and It. I). Evans, A.Z.E.E. Transactions, 1928, (a hook), McGraw-Hill Book Company, New York, 1936.
pp. !I+121. Disc., pp. 121.-123. 33. First Report of Power System Stability: Report of Subcom-
II. Synchronized at the Load-A Symposium on New York City mittee on Interconnection and Stability Factors, by R. D.
6O-Cycle Power System Connection, hy A. H. Kehoe, S. B. Evans, Chairman, A.I.E.E. Transactions, 1937, pp. 261-282.
(iriscorn, Ii. It. Searing, anti G. R. Milne, A.I.E.E. Tralzsaclions, Disc., &lay, pp. 632-634 and Sept., p. 1204.
Oct. 1929, pp. lOi+1 100. Disc., pp. 1100-1107. 34. Ultra High-Speed Reclosing of High-Voltage Transmission
IL’. l’rogress in the Studv of System Stability, by I. H. Summers and Lines, by Philip Sporn and D. C. Prince, A.Z.E.E. TransacliorLs,
.I. 13..\IcClure, A.I.E.E. Transaclions, 1930, pp. 132-158. Disc., 1937, pp. 81-90 and 100. Disc., p. 1036.
pp. I!)!)-161. 35. Unsymmetrical Short Circuits on Waterwheel Generators Under
1% I)ouble Windings for Turbine Alternators, by P. L. Alger, Capacitive Loading, by C. F. Wagner, A.I.E.E. Transactions,
li. H. Freiburghouse, and D. D. Chase, R.I.E.E. Transactions, 1937, pp. 1385-1395. Disc., 1938, p. 406.
Jan. 1930, pp. 226-238. Disc., pp. 238-244. 36. E’leclric Power Circuils-Theory and Operation-System Stabil-
11. l”untl:rmental Plan of Power Supply of the Detroit Edison ity, by 0. G. C. Dahl (a book), vol. 2, McGraw-Hill Book Com-
(‘ompany, by S. M. Dean, A.Z.E.E. Transaclions, 1930, pp. pany, Sew York, 1938.
~~!)i-60-l. Disc., pp. 612-620. 37. D-C Transmission Evolving Slowly, by D. ,\I. Jones, C. II.
1:. Opcrnting Characteristics of Turbine Governors, by T. E. Pur- Willis, &I. M. Morrack, and B. D. Bedford, Eleclrical World,
c(-iI and A. P. Hayward, A.I.E.E. Transacli~ns, April 1930, pp. Feb. 25, 1939, pp. 41-42.
715-i19. Disc., pp. 719-722. 38. Phase-Angle Control of System Interconnection, by R. E.
Iti. S(>lr,ct.ingBreaker Speeds for Stable Operation, by R. D. Evans Pierce and G. W. Hamilton, A.I.E.E. Transaclions, 1939, pp.
:w~ W. A. Lewis, Eleclrical World, Feb. 15, 1930, pp. 336-340. 83-91. Disc., p. 92.
‘;. I)ouble-Winding Generators, by R. E. Powers and L. A. Kil- 39. A Graphical Solution of Transient Stability, by H. H. Skilling
gore, The Eleclric Journal, Feb. 1930, pp. 107-111. and M. H. Yamakawa, Electrical Engineering, Nov. 1940, pp.
‘% An Alternating-Current Calculating Board, by H. A. Travers 462-465.
:ind W. W. Parker, The Electric Journal, May 1930, pp. 266-270. 40. Brown Boveri Review, Issueon D.C. Transmission, Vol. XxX11,
‘!I. l$gect of Armature Resistance Upon Hunting of Synchronous x0. 9.
~lachines, by C. F. Wagner, A.I.E.E. Transaclions, July 1930. 41. Reclosing of Single Tie Lines Between Systems, by W. W.
PP. 101 l-1024. Disc., pp. 1024-1026. Parker and H. A. Trovers, A.Z.E.E. Transactions, 1944, pp.
?fl, cI()nerator Stability Features-Fifteen Mile Falls Development, 1 I!)-122. Disc., p. 472.
I?’ li. Coe and H. R. Stewart, The El&vie Journal. blsrch 1931, 42. Ilecloaing Single-Circuit Tie Lines, by H. N. Mullor, Jr. and
PP. 139-143. W. W. Parker, WE'E~TINGHOUSE ENGINEER, March 1945, pp. 60-63.
CHAPTER 14

POWER SYSTEM VOLTAGES AND CURRENTS DURING


ABNORMAL CONDITIONS
Original Auth.or: Rcuiscd hg:
R. L. Witzke R. L. Witzke

F
OR many years it was common practice to base the c
requirements of system apparatus on normal load
conditions and on three-phase short circuits. More
or less empirical multiplying factors were sometimes used
to predict the probable ground-fault currents from the
three-phase fault currents. HoIvever, this procedure is
unsatisfactory because the reMions between three-phase
and ground-fault currents vary greatly between systems.
In some systems the current for a single line-to-ground
fault is less than normal load current, whereas, in other $ c
systems, or at other locations in the same systems, the 3 PHASE FAULT SINGLE LINE-TO-GROUND
current for a single line-to-ground fault is larger than the (L-L-L OR 3L-Gl FAULT (L-G)
three-phase fault current. The analysis of power systems
by symmetrical components’ (see Chap. 2) has made pos-
sible the accurate calculation of fault currents and voltages
for unsymmetrical faults directly from system constants.
Under many conditions the voltages present on a power
system may be higher than those calculated for steady-
state conditions. These higher voltages are usually of a
transient nature and exist during the transition from one
steady-state condition to another. Transient voltages can
be produced by simple circuit changes such as the opening
of a circuit breaker or the grounding of a conductor,’ or
t,hey can be produced by an intermittent arc in a circuit
breaker or in a fault. Usually the higher voltages are
associated with intermittent arcs rather than with simple ---*-
+
circuit changes without arcing. Most transient voltages
DOUBLE LINE-TO-GROUND LINE-TO-LINE FAULT
are not of large magnitude but may still be important FAULT (2L-G) (L-L)
because of their effect on the performance of circuit-
interrupting equipment and protective devices. An apprc- Fig. l-Types of faults on three-phase systems.
ciable number of these transient voltages are of sufficient
magnitude to cause insulation breakdown. the positive-, negative-, and xcro-sequence networks, ro’
The various factors that determine the magnitudes of spectively. In the present analysis the fault resistnnco ie
cluwnts and voltages in power systems during abnormal represented by R and is not included in &. ZOincludes all
conditions will be discussed in this chapter. zero-sequence resistance to the point of fault but does not
include the fault resistance. It is further assumed that all
I. STEADY-STATE VOLTAGES AND CURRENTS the generated emfs can be reduced to a single positive
DURING FAULT CONDITIONS sequence emf, E,.
1. Assumptions 2. Formulas
Voltages and currents produced under fault conditions In Tables 1 and 2 are given the formulas* for calculfiting _
are a function of the type of fault and the ratios of the the line currents and line-to-ground voltages for the faultr,
sequence impedances. The effect of these factors on the illustrated in Fig. 1. These formulas are co
voltages and currents produced can be shcnvn by sets of such an extent that it is difficult to visualize
curves as will be done here. The four types of faults il- currents and voltages that can be produced
lustrated in Fig. 1 will be considered. It is assumed that conditions for ranges of system constants. For
the network is symmetrical to the point of fault, F, and the currents and voltages have been calculated
can be reduced to series impedances, 21, 22, and 20 for *Formulas takers from pages 22 L and 226 of reference 1.
4Yti
chapter 14 Power &stem Voltages and Currents During Abnormal Conditions 497

ratios of system constants and the rewdts are presented as 4. Fault Current and Voltage Curves
:1sprigs of curves. Curves prepared in accordance with the preceding dis-
cussion are plotted in Figs. 2 to Ginclusive. In these figures
3. Range of Sequence Impedances Considered the fault current is plotted as a ratio of the three-phase
‘rhc principal impedances t,hst usually apply to tran- short-circuit, and the line-to-ground and line-to-line volt-
Siclnt conditions are the positive-sequence impedance Z,, ages are plotted as a ratio to their respective normal values.
tl,(: rlegative-sequence impedance Za, and the zero-sequence In Figs. 2, 3, and 4 all resistances are equal to zero.
;,np&tnce 20, each consisting of a resistance and a react- Figs. 2 and 3 show the ranges of line currents and line-to-
:,ncc component. In general, the positive-sequence rcsist-
:L,l(~(:lil and the negative-sequence resistance R, are small 2.0

i,, comparison to the positive- and negative-sequence re- 18


:L,aI:mces.Consequently, the effect of these two resistances
,,,, t hr: magnitude of the voltages and currents during fault
,~~,ricIitionsis small. For this reason and because of compli- 14

rx:ltions introduced by considering positive- and negative-


s(L(Itwn(‘eresistances, these factors will be neglected. Zero-
s(b(Iiwnceresistance & and zero-sequence reactance X0 can
\:lry through wide ranges depending on the type of system
grolmtling used, hence the curves are arranged to cover a
~itlc range of zero-sequence resistance and zero-sequence
p:tct,ance.
The positive-sequence reactance that applies to tran-
sicbntconditions may be either the sub-transient or the
(,r:msit:nt reactance depending on whether or not the initial Ratio XQ/X,
high decrement component of the current is to be consid-
cwtl or neglected. The ratio of X2 to X1 for commercial Fig. 2-Curves of fault currents vs. system reactances for
single and double line-to-ground faults. Each curve is labeled
nwhines usually lies between 0.5 and 1.5, although with to indicate the type of fault and the ratio of X2/X1. All cur-
s~~c~cial machines it is possible to exceed this range. The rents are expressed as a ratio to the three-phase short-circuit
Ili$er ratios of X2 to Xl are in machines without dampers current. For these curves, all resistances are assumed equul
whcreas the lower ratios are in machines with dampers to zero’.
or their equivalent. In general calculations it is usually
~~crmissibleto assume a ratio of X2/X1 of unity especially ground voltages respectively for single and double line-to-
if :m appreciable percentage of the negative-sequence re- ground faults for ratios of X,/X, from zero to six. The
xtance to the point of fault is in static apparatus or trans- ranges of fault current and fault voltages for ratios of
Inksion lines. The general curves are limited to ratios X2/X1 between 0.5 and 1.5 are shown in Fig. 4.
of SL’ to X1 within the range of 0.5 to 1.5; the formulas
The ranges of fault current for ratios of 2 between zero
in Tables 1 and 2 can be used for ratios outside of this 1
range. and six are given in Fig. 5. In this figure the ratio Z?,‘S1

TABLE ~-FAULT CURRENTS

Vector espression, eHectof fault resistanceincluded Jlagnitude of currents when


R,,=R,=R,=R=R,=O

I;,=E, I,=I,,=I,=$
z,+-Iz L

I, = 3& I,= 3*,


zu+z,+2,+312 .Y,+x, f.YYy

II, = - 4E,
-[\/:~(Z~+RLJ+~(~ZO+Z~+~RL+~R,)~ ~.kv:+x”x,+x;
2Au

hhle line-to-ground

-
~‘=_PoJitive-~erlllerlce impedance to the point of fault
“emLIve-xequenre impedance to the point of fault
z?=
0 Zero-xw~uence impedance to the point of fault and does not include any fault resistance
See Fig. I for detinitiom+ of II, RL and R.
498 Power System Voltages and Currents During Abnormal Conditions

covers the range of 0.5 to 1.5 and the ratio X,/X, covers X,/X, cover the same ranges as in Fig. 5. In the prepara- ’
the range of zero to five. As pointed out previously, fault tion of these curves fault resistance has been neglected.
All voltages are measured to true ground at the point
of fault.
In special cases, for example in the application of light-
ning arresters, it is necessary to consider the effect of fault
resistance on the voltages produced during single line-t+
1.4

1.2
z
2 1.0
d, 0.6
I-
z 0.6
Es
2 0.4
0 I 2 4 5 6’=
fh+io3 x,/x, I I I_
0.2 ’ ’ ’ ’ ’ ’ ’ ’ ’ ’ ’ ’ ’ ’
Fig. 3-Curves of fault voltages vs. system reactances for
single and double line-to-ground faults. Each curve is labeled I _
to indicate the type of fault and the ratio of X2/X,. The volt-
8.5’ ’ ‘017’ ’ ’ 0.9
’ ’ ’ ’ I.1
’ ’ ’ 1.3 I.5
ages are from line-to-ground and are expressed as a ratio to RATIO X,/X,
the normal line-to-neutral voltages. For these curves, all re-
Fig. 4-Curves of fault voltages and currents vs. system react-
sistances are assumed equal to zero’.
antes for line-to-line faults. Line-to-ground and line-to-ltne
voltages are expressed as ratios to their respective normal
resistance has been neglected in these curves; Ko is the values. Current is expressed as a ratio to the three-phase
zero-sequence resistance to the point of fault F and does short-circuit current. All resistances are assumed equal
not include R, R,, or R, (see Fig. 1). It is, however, pos- to zero.
sible to include the effect of R and R, in Fig. 1 by including
them in RO. ground faults. The curves in Figs. 7 and S include this
The ranges of fault voltages for ratios of R,/X1 between factor. The curves in Fig. 7 give the highest voltages from
zero and six are shown in Fig. 6. The ratios X,/Xi and line to true ground for a fault through a fault resistance Rt.
TABLE 2-FAULT VOLTAGES
-
vector Effect of Fault Resistmce Included 1Iagnitude of Volbges When
Type of Fault Expression,
R,=R,=R,=O
R E,,=O
Three-phase. En = ExpR

22,+1x?
En=EgZ,+Z,+R
R .d:jR
2 f”y- +z1 X,
Eb=Ee=&------
Line-to-line. . Eb= -*, Z,+Z?+R
x,+x2

~-jI+.!Z+Z?
Eeb = Em = GX, +Ay2
Ec= -Eg~,+Z2+R
3R
Ea=EuZ,+Z,+Z,+3R
Single line-to-ground. b
1
E = - ~~E,T~5(Z,,+R)+j(Zo+22*+3R)
---FL
E = -,,GE,
Zo+Z,+Z2+3R
&2,1$-R) -j(Z,,+2Z,+3R)
-
c
1 -2 [ Zo+ZI+Z2+3R

~.=~~(z,+ll~!(zo+R~+ZRr)
F,=~[~~(z,+R~.)(~L+~R.)+~R,(~~~+Z,+~RL+~R,)] h’b=&=o
Double line-to-ground
&b = E, = E.
AM =x,x,+&(x,+xz)
-
ZI=positive-sequence impedance to the point of fault
Sz=nt!rcntive-sequence impedance to the point of fault
Zo=zero-sequence impedance to the point of fault and does not include auy fault revivtarlce
See Yig. 1 for definitioos of R, I(L and R.
Chapter 14 Power @stem Voltages and Currents During Abnormal Conditions 499

2.4

2.2

2.0

1.6
‘2
i2.0 a 1.4
5
’ 1.6 v 1.2

0 I 2 3 4 5 6-- a~
RATIO R,/ X, RATIO R. / X, RATIO R, /X,

3.2, , I

2.4 2L-G SHORT-CIRCUIT-j

+ 2.0
3
2 I.6

u 0.6 3 I.2
0.4

0 ::I
“0 I 2 3 4 5 6-- a~ 0 I 2 3 4 5 6-- (0 ‘0 I 2 3 4 5 6-- a~
RATIO R. IX, RATIO R, / X, RATIO R, /X,

3.2

1.4

1.2 2.4

I- 1.0 + 2.0
z iTI
‘2
: 0.8 g 1.6 Y 1.2
Q
’ 0.6 I I I s I.2 = I.0

0.4 0.8-

0
012345 6-- aD “0 I 2 3 4 5 6-- (D O.4Om
RATIO R. / X, RATIO R, /X, RATIO R,/X,

(a) LINE CURRENT (b) GROUND CURRENT (c) LINE CURRENT


SINGLE LINE-TO-GROUND FAULT OOU8LE LINE-TO-GROUND FAULT DOUBLE LINE-TO-GROUND FAULT

Fi& J-Curves of fault currents vs. system impedances. The legend with each group of curves indicates the type of fault, the
current plotted, and the ratio X2/X1. The individual curves in each group are for various values of the ratio of X0/X1. All
CUrrents are expressed as a ratio to the three-phase short-circuit current. RO is the zero-sequence resistance to the point of
fault and does not include any fault resistance; the fault resistance is assumed equal to zero’.
Power System Voltages and Currents Dm-ing Abnormal Conditions Chapter 14
1.8 Q 1.8

1.6

1.4

1.2
W

U.3’
L-G SHORT-CIRCUIT
0.4 Ebc

0.3 -x2 =0.5


Xl

3 4 5 6 Q o*20 I 2 3I 4I 5 6 Q
RATIO R, /X, RATIO R, /x, RATIO R, IX,

l.6l
ml I I I I I I

w I.0 w 1.0
:: ::
3 0.8 3 0.8
9 0.6 z 0.6

0.2

I
O*?o1 Q 0
0123456a 0123456~
RATIO R, /X, RATIO Ro /XI RATIO R, / X,

I.8

1.6

sf I.0
“. z
\- g 0.8
XI >
,.-.I .w I I I I I
I.L 0.6 ‘” ’
1 2L-,G SHORT-CIRCUIT
L-G SHORT-CIRCUIT
1.0 EC
0.4111 Eo -i--‘--j
x2
0.8 yl.5

0.6l ’ I I I I 1
0123456Q 4 5 6 Q OOM 2 3 4
RATIO R, / X, RATIO Ro/ X, RATIO R, /X,

(0) LINE-TO-GROUND VOLTAGE (b) LINE-TO-LINE-VOLTAGE (C 1 LINE-TO-GROUND VOLTAGE


$1 NGLE LINE-TO-GROUND FAULT SINGLE LINE-TO-GROUND FAULT DOUBLE LINE-TO-GROUND FAULT
Fig. B-Curves of fault voltages vs. system impedances. The legend with each group of curves indicates the type of fault,
.the voltage plotted, and the ratio of X2/X1. The individual curves iq each group are for the various values of the ratio of %
/XI. Line-to-ground and line-to-line voltages are expressed as ratios to their respective normal values. R. is the zero-se-
quence resistance to the point of fault and does not include any fault resistance; the fault resistance is assumed equal
to zero’.
Chapter 14 Poroer System Voltages and Currents During Abnol -ma1 Conditio*ns 501

I I I I I I ! I I
Ii I I I I I I I I i I

I I

Z’ 1.0
I i I
I I
o.90
2 3 4 5
x,/x,
(b) RJX,.I.O (cl R./X, - I.5

Fig. 7-Curves of line-to-ground voltages vs. system impedances for a single-line-to-ground fault through a fault resistance Rf
RO is the zero-sequence resistance to the point of fault and does not include R, or Rt. X/X, is assumed equal to 1.0.

These curves cover a range of R~/XI of zero to 6 and a


range of R,/X, of from 0.5 to 1.5. RO is the zero-sequence
resistance to the point of fault and does not include Rf.
The curves in Fig. 8 show the voltages across an arrester
for a fault to the arrester neutral. As in Fig. 7, ROis the
zero-sequence resistance to the point of fault and does not
include R,.
Reference should also be made to Figs. 28 and 29 of
Chap. 18, particularly in lightning arrester application

Fig. 9-A-c network calculator.

II. TRANSIENT VOLTAGES


A transient voltage of some magnitude is present on a
power system each time a circuit change is made. This
circuit change may be a normal switching operation such
as the opening of a circuit breaker, or it may be a fault
condition such as the grounding of a line conductor. The
existence of transient voltages on power systems as a result
of circuit changes caused by switching operations or faults
was recognized at an early date2. The phenomena, how-
ever, were not thoroughly investigated at the time because
Fig. S-Curves of the maximum voltages across a lightning suitable measuring and recording devices were not avail-
arrester for a fault to the lightning arrester neutral point. able and because the immediate difficulties were largely
RO is the zero-sequence resistance to the point of fault and overcome by the adoption of the practice of grounding
does not include R,, the resistance of the arrester ground.
The fault resistance is assumed equal to zero and X1/X2 is power systems. The invention by J. F. Peters3 of the
assumed equal to 1.0. “klydonograph” made possible the collection of a mass of
field data on transient voltages. However, the time and
problems. These figures give the maximum line-to-ground expense involved in making extensive field studies limited
voltages during single- or double-line-to-ground faults on the scope of these investigations. Furthermore many in-
ungrounded and grounded-neutral systems. vestigators were concentrating their efforts on lightning, a
502 Power System Voltages and Cwrents During Abnormal Conditions Chapter 14

much more important problem at that, time. The intro- depends upon several factors, such as line length, supply
duction of the protector tube for the: protection of trans- impedance, etc.
mission lines, however, showcd the ncctl for a better under- After the miniature system has been set up as shown in
standing of power system transients because it,s perform- Fig. 10, the eqllipment shown diagrammatically in Fig. 11
ance is greatly affected by them. The first attempts to is used for performing switching operations or for applying
calculate transient voltages acre matlc by convcntionnl faults. Each of the synchronous switches shown at the
methods using differential equations. The limitations of
conventional mathemat,ical methods were soon apparent,
however, because of the tremendous amount of time re-
11
quired. The introduction of the A-C NetTvork Calculator
II&hod of Stlldying Power System Transients4 gave a II
A-C ;TWRK CALCULATOR 11
practical tool for studying the behavior of power systems
under transient conditions and made possible general in-
vestigations of power-system transients. The later de-
velopment of the Anacom, or analog computer,5 further
increased the possible scope of power system investiga-
tions. It is the pllrpose of the following sections to describe
these computing devices, and to present the results of
general studies made with them.
5. The A-C Network Calculator Method of Study-
ing Transient Voltages
To stlldy transients on power systems by the X-C Set-
work Calculator II&hod, the system in qllestion is set up
in miniature on the A-C Network Calculator. In Fig. 10 is
shown the equivalent circuit for a relatively simple system
consisting of a generator, a transformer, and a transmission v-
line. The generator is represented by a low-impedance
three-phase supply with additional impedance in series to
give the miniature system the same impedance as the im-
pedance of the actual system. The zero-sequence imped-
ance of the source is represented by a grounding trans-
Fig. 11--Schematic diagram showing equipment used in a-c
former of low impedance grounded through reactance or
network calculator method of studying transients.
.\I--Synchronous mot,or
(;-Gear
FItD-Fault rcprrscntation dovice
C--Synchronous switches
AR-Arc resistance rcprescntal,ion
GR-Ground rasistancc reprcscnt,ation
VlID-Voltage measuring dcvicc
CRO-Cathode-ray osrilloscope
L-Lens system
PFH-Polar film holder

bottom of Fig. 11 consists essentially of a conducting and


an insulating segment on a drum and two movable brushes,
one for controlling the closing and the other the opening of
the switch. Each brush is located on a gear that can be
rotated by a worm, making the brush adjustable through
3fjO degrees.
Fig. IO-Schematic diagram illustrating method of system
representation used on the a-c network calculator. For representing faults on power systems the switches
are connected between line and ground or between lines
FRD--Fault, reprcserltationdevice depending upon the type of fault being studied. Where
VMD-Voltage measuring device circuit breaker operations are to be simulated the switches
are inserted in series with the line. The switching opera-
resistance depending upon the type of grounding used. In tions are repeated once per revolution of the drum and, 8s
the equivalent circuit in Fig. 10 the transmission line is the drums are rotated by a synchronous motor, the switch-
represented by an equivalent 7r section. This type of line ing operations always take place in synchronism with the
representation is used in some studies but often it is neces- system voltage. The transient voltage produced by the
sary to employ more complicated networks. The choice switching operation is therefore repeated once per revolu-
of the network to use for representing a section of line tion of the drum. All transient voltages are measured by &
,~~~lhode-rayhscilloscope connected to tl:e miniature net-
,,-c~rk. Ry repeating the transient, a number of tim-s per
5(xc+ontl,
the equivalwt of a ste:ttl\--state voltage is produced
,,n the scrwn of the cathode ray oscillc scope. This makes
it possible t,o study a transient that, lasts for a fraction of
:Lbale \vithorlt taking oscillograms. The effect of initiating

Fig. 14--Close-up view of the hnacom control desk and


Fig. 12--Switching and recording equipment used with a-c synchronous switch.
network calculator.
the a-c network calculator. An analog is formed by con-
I IN: transient at different points on the normal dynamic necting circuit elements, R, L, and C, into a circuit that has
\,oltage wave can be studied by simply changing the posi- the same differential equation as the system under con-
I ions of the brushes on the synchronous switch. The time sideration. Synchronous switches are usually used to re-
intc,rval between successive transients is so chosen as to peat the desired transient solution a number of times per
t)ring the system back to normal between switching second, which permits visual and photographic mensure-
cqwrations. ments on a cathode-ray oscilloscope. In power system
studies the switches normally represent circuit, breaker
6. The Analog Computer operation or faults.
The analog for many systems (electrical, mechanical,
thermal, etc.) requires low-loss inductance coils, amplifiers,
multipliers, and other special circuit elements. The analog
c:omputcr,5 or r\nacom, was developed primarily for the
solution of these systems. Its characteristics, however,
make it ideally suited to the solution of all power-system
transient problems formerly studied on the a-c network
wlculator. The Westinghouse Electric Corporation now
makrs all electric transient studies on the Anncorn, reserv-
ing the a-c network calculator for power system problems
wch as voltage regulation, load flow, stability, etc.
In most cases the procedure for setting up a problem and
obtaining a solution is the same with the --Inacorn as with

Fig. 15-Details of an Anacom inductance-resistance drawer.

The computer elements include inductance coils having


a Q of 100 or higher over the frequency range from 100 to
1000 cycles; precision capacitors and resistors; special
transformers having minimum exciting current, leakage
impedance, and distributed capacitance; amplifiers, and
Fig. 13--General view of the large-scale, general-purpose multipliers. Special analogs have been developt~d to repre-
electric analog computer. sent lightning arresters, corona, and other non-linear char-
504 Power &stem Voltages and Currents During Abnormal Conditions Chapter 14

acteristics. The use of the synchronous switches in com- tions. No voltage can appear across the condenser until it
bination with R, L, and C circuit elements, amplifiers and is charged up and the charging rate is fixed by the source
muhipliers permit the formation of special forcing func- inductance and the capacitance. When the short-circuit is
tions such as lightning surges, air-gap torques in turbine removed, the condenser voltage will be accelerated toward
generators during short circuits, etc. The measuring equip- normal but will overshoot because of the circuit inductance.
ment includes cathode ray oscilloscopes with suitable If no losses were present in the circuit t,he transient voltage
photographic means, harmonic analyzers, wire and tape across the condenser would reach a crest equal to twice
recorders, and all types of conventional ammeters, volt- normal crest voltage. In a practical circuit with some loss,
meters and wattmeters. the oscillation will not quite reach twice normal; it will
The Anacom is arranged with d-c, 440-cycle, and 60- eventually be damped out, leaving only the normal-
cycle power supplies to solve problems normally assigned frequency voltage across the condenser.
to the a-c and d-c network calculators; however it is nor- This transient voltage across the condenser, following
mally used in the transient field. It is suited to the solution the removal of the fault, is commonly referred to as the
of many problems of concern to power company engineers, system recovery voltage as it defines the manner in which
including recovery voltage, switching-surge and arcing- the system voltage “recovers” following the removal of the
ground investigations, surge-protection applications, tur- fault. Changing the source reactance in the circuit in Fig.
bine generator short-circuit torques, analysis of generator 16 is equivalent to changing the amount of generation con-
voltage regulating systems and motor-starting problems. nected in a power system, and changing the value of capaci-
It can be used in solving many equipment design problems tance is equivalent to varying the length of line connected.
such as surge-voltage distribution in transformers and ro- The natural frequency of the oscillation in the circuit in
tating machines, dielectric field mapping, and heat-flow. Fig. 16 depends upon both the inductance and the capaci-
Its possible application in the fields of applied mechanics, tance and varies inversely as the square root of the product
hydraulics, thermodynamics and servomechanisms is of these two quantities. The recovery voltage of a power
almost unlimited. system therefore depends upon the connected generator
capacity and the length of line.
7. Recovery Voltage The De-ion Protector Tube-As previously stated,
Theory-One transient phenomenon studied by the recovery voltage is important because of its effect on the
A-C Network Calculator Method is system recovery volt- performance of circuit interrupting and protective devices.
age, which is important because of its effect upon the oper- This can be shown by a detailed study of the operation of a
ation of circuit interrupting and protective devices, such De-ion protector tube. A typical installation of protector
as circuit-breakers, protector tubes, etc. The simple circuit tubes is shown in Fig. 17. In this case the protector tube is
in Fig. 1G can be used for defining system recovery volt- mounted vertically just below the line conductors. The
lower electrode of the tube is connected to ground and the
upper electrode is connected to an arcing horn used to
maintain a constant external gap between the upper elec-

Fig. l&Simple system for illustrating recovery voltage for a


fault (F).
ef-Voltage across fault
+-Fault current

ages. In this circuit a condenser C is used to represent a


transmission line, and a voltage and an impedance, the
source. Applying a short-circuit across the condenser in
this circuit is equivalent to applying a line-to-ground fault Fig. 17-Typical installation of De-ion protector tubes.
on a single-phase power system. During the time the con-
denser is short-circuited, a fault current it will flow. If the trod; and the line conductor. The cross-section of a pro-
resistance in the source is small in comparison to the react- tector tube in Fig. 18 shows the two electrodes and the
ance, this fault current will lag the generated voltage epby internal gap. In operation, lightning striking the line
approximately 90 degrees. If the short-circuit is removed breaks down the series gap instead of flashing over the
at the instant the fault current passes through zero, the insulator string because the tube has the lower breakdotvn’.
voltage across the condenser will not immediately return to voltage. After breakdown of the gap, power-follow current
normal but will reach normal only after a series of oscilla- volatilizes a small layer of the fiber wall and the gas given”
Chapter 14 Power System Voltages and Currents During Abnormal Conditions 505

off mixes in the arc to help de-ionize the space between the
electrodes. A pressure is built up in the tube and the hot
gasesare discharged through the lower electrode, which is
hollow. If the de-ionizing action is sufficiently strong and
if the voltage does not build up too rapidly across the
tube, the arc will go out at a current zero and will not be
reestablished. w
While the tube is discharging, it is a good conductor and 2
5
sfter the arc has been extinguished it is a good insulator. 0
>

AR‘CING
HORN

UPPER TIME
ELECTRODE
Fig. 19-Comparison of system recovery voltage and insula-
tion recovery curves.
A-Insulation Recovery Curve for Tube A
/ FIBER B-Insulation Recovery Curve for Tube B

lie above the system recovery voltage curve, otherwise the


arc will be re-established in the tube. Protector tube B
would not operate satisfactorily on a system having re-
covery voltage characteristics similar to the recovery volt-
age in Fig. 19. A tube similar to tube A would have t,o
be used.
The recovery voltage for the simple circuit in Fig. 16 is
made up of a single-frequency oscillation. In a practical
power system, the recovery voltage does not usually consist
of a single-frequency oscillation but is usually made up of
tlvo or more high-frequency components. In Fig. 20 is
.VENT
shown the recovery voltage following a single line-to-
ground fault on a 138-kv, three-phase system having a
symmetrical three-phase short-circuit current of 1000 am-
peres and 90 miles of overhead transmission line. The
recovery voltage in this case consists of two high-frequency
components and is typical of the shape of the recovery
voltage on many three-phase power systems.

Fig. 18-Cross-section of a typical De-ion protector tube.

This change from a good conductor to a good insulator does


not take place instantaneously because time is required to
discharge the hot gases from the tube. It is therefore im-
portant that the voltage across the tube does not build
UP more rapidly than the change in the protector tube
dielectric strength. This is where recovery voltage enters
the picture because recovery voltage determines the rate
cf build-up of the voltage across the tube.
In Fig. 19 the recovery voltage for the circuit in Fig. 16
is replotted to a larger scale. Curves A and B in this figure
are typical of the shape of insulation recovery curves for
MICROSECONDS
11 different protector tubes. It is of utmost importance
two
Lnat the protector tube insulation recovery curves always Fig. 20;Recovery voltage curve for a typical power system.
506 Power System Voltages and Currents During Abnormal Conditions Chapter 14

General Recovery Voltage Study-A broad per- cause the problems are similar and also the recovery
spective of the recovery-voltage problem can be obtained voltrages are less severe when ground wires are used.
from the study of a representative set of systems. For this In making the general analysis the factors varied were;
purpose three-phase, GO-cycle systems with transmission method of grounding, load, type of fault, fault resistance
lines of t,hree voltage classes, namely, 34.5, 69, and 138-kv arc resistance, and location of fault. The studies can coni
were selected. Since the recovery voltage of a system is veniently be divided into two groups with respect to the
materially affected by the length of connected line, the method of grounding, namely: group I with system solidly
lengths were selected to represent the shortest that would grounded both at sending- and receiving-end transformers,
be encountered at that particular voltage for the large and group II with the system grounded through a react-
majority of systems. These selections were as follows: 22.5 ance at the sending end only. The solidly grounded sys-
miles for 34.5 kv, 45 miles for 69 kv, and 90 miles for 138 terns, of group I, were studied for both single line-t&
kv. Although it was recognized that more than one circuit ground and double line-to-ground faults and for fault or
would be required to transmit the maximum amount of tower-footing resistance of 0, 25, and 100 ohms, and with
power a single-circuit line was used because this gives the and without resistance for arc representation. The effect
more severe recovery-voltage conditions. of load was investigated by comparing the results of the
The general features of these systems are shown sche- above tests with results of a few tests made without load
matically in Fig. 21. For each voltage class three different and without fault or arc resistance. The second set of tests
for the reactance-grounded system, group II, was made
with the addition of a neutral reactor of such magnitude
as to make the zero-sequence reactance at the sending end
equal to 8.5 or 3-l times the zero-sequence reactance of the
supply transformer.
Results of General Study-In an investigation of
this type it is not practical to consider the application of
the fault at several points of the system. A preliminary
study was, therefore, made to determine the effect of mov-
Fig. 21-Schematic diagram of system selected for study.
ing the fault along the line. Considering the shape of
Group I. Solidly grounded at both ends. Used for curves of Fig. insulation-recovery voltage curves for specific pieces of
22. apparatus, it was concluded that the recovery-voltage con- -
Group II. Reactance grounded at sending end; ungrounded at re- ditions were about as severe for faults at the sending end
wiving end. Used for curves of Fig. 23. as at any location along the line. Therefore, the fault at
the sending end was considered to be representative and
conditions were assumed, each having different amounts of was used in the general studies.
generating capacity and load. Table 3 gives the symmet- Based on the selected systems, a series of studies ~a.3
rical three-phase short-circuit current that would be en- made on the a-c network calculator to determine the effect
countered for a “bolted fault” at the sending end. Systems of the different factors entering into the recovery-voltage
capable of supplying the higher short-circuit currents have problem. These studies may be divided into t.wo groups;
in general larger connected loads. Table 3 gives the ratio group I for systems with solidly-grounded neutral, and
of short circuit kilovolt-amperes to load kilovolt-amperes group II for the reactance-grounded systems, described in
connection with Fig. 21. The results of these studies are
TABLE 3-CHARACTERISTICS OF SYSTEMS SELECTED FOR STUDY
presented in Figs. 22 and 23 respectively. The manner in
which these data are plotted can more readily be understood
Voltage 31.5 Kv 69 Kv 138 Kv
by referring to Fig. 20. The recovery voltage curve in this
Short-Circuit Ampcrcs illustration has two predominate crests. If the insulation .’
(a) 500 500 500 recovery curve for a protector tube lies above these crests, ‘V
(b) 2 000 2 000 1000 the tube will perform satisfactorily. In the general applica- *
(cl 6 000 6 000 4 000 tion of protector tubes it is not necessary to have the :
Short-Circuit KVA complete recovery-voltage curve if the data corresponding
Load KVA to these predominate crests are available. Therefore, in f
Line Length (miles) summarizing the results of the general study only the data “9
pertaining to these predominate crests were plotted ln ‘:$
that was used in this study. Both no-load and loaded Figs. 22 and 23. li
conditions were considered. An 80 percent power factor Referring to Fig. 22, it, will be seen that for each
load was divided equally between the generator bus and class studied the time to the first crest and to them
t,he receiver bus as shown in Fig. 21. overshoot, as well as the magnitude of the first cr
The generating and transformer capacities were propor- the maximum overshoot are presented for the single
tioned to the load for the particular system and short- to-ground and double line-to-ground fault cases. For
circuit current, and typical constants were assumed for all curves the abscissa is the current magnitude for a
of the system elements. Transmission lines without ground metrical three-phase short-circuit at the sending end.
wires were chosen. The additional complication to take results for a system under load are plotted for each c
care of the cases with ground wires is not warranted be- condition, with and without the arc representation
Chapter 14 Power S@em Voltages and Currents During Abnormal Conditions
508 Power System Voltages and Currents During Abnormal Conditions

for O-‘, 25-, and lOO-ohms tower-footing resistance. For having characteristics similar to curve Tz should be uSed
comparison, one study with no load and with zero arc and for this system.
tower-footing resistance is plotted. The arc representation Using the data in Figs. 22 and 23 it is possible to predict
device makes use of Rectox resistors to simulate the arc the performance of any protector tube on any of the typical
characteristics of a protector tube. The Rectox resistor systems studied in this general investigation. A more de-
was adjusted to give approximately 20 percent of line-to- tailed discussion of the application of these data is in-
neutral voltage at the peak of the symmetrical short-circuit cluded in Chap. 17.
current wave.
Fig. 23 presents the results of similar studies made on 8. Distribution-System Recovery Voltage Char.
the same systems except with reactance grounding. The acteristics
system arrangement with respect to grounding is shown The data in Sec. 7 are not generally applicable to the
in Fig. 21. lower-voltage circuits because of the differences in source
Application of Data-Although the recovery-voltage reactances, circuit arrangements, line lengths, conductor
data presented are useful in a number of applications, the spacings, etc. For this reason, a study’ was made on the
particular application of the protector tube will be taken analog computer to obtain fundamental data on the re.
as an illustration. The case of a 34.5 kv solidly-grounded
system with 22.5 miles of transmission line with a sym-
metrical three-phase short-circuit current of 4,000 amperes INFINITE
BUS
at the sending end has been selected. No-load and zero-arc HE FOUR WIRE
and tower-footing resistance give the highest recovery volt- MULTIGROUNDED SYSTEM
age for both single-line-to-ground and double-line-to- AC&-

ground faults as shown in Fig. 22. The data for these two
Fig. 25-Distribution system selected for study on Anacom,
cases have been plotted in Fig. 24. The insulation recovery
curves for two protector tubes are also included in this
figure. Curve TX extends below the system recovery volt- covery voltage characteristics of circuits in the 2400-m
age curve for the case of a single-line-to-ground fault but 13 800-volt range. The general study was limited to the
is always above the corresponding curve for the case of a case of a four-wire, multi-grounded system supplied from a
double-line-to-ground fault. As both types of faults must delta-star power transformer, connected to an infinite bus
be considered in the application of protector tubes, a tube on the primary side and solidly grounded on the secondary
side.
160 Geometric-mean distances of 2.66 feet between phase
conductors, and 4.1 feet between the phase and the neutral
conductors were assumed. These spacings give reactance6
that are an average of the values obtained over the range
of spacings normally used between 2400 and 13 800 volts.
The small variations introduced by changes in spacing are
not considered significant in the general problem. A con-
ductor height of 30 feet and a ground resistivity of 100
meter ohms were used in all studies. The phase- and.
neutral-conductor sizes were assumed to be the same, and
were varied between 4/O and No. 6 copper. The line
constants for these two extreme conductor sizes are
included in Table 4.
TABLE ~-CONSTANTSOFTYPICALDISTRIBIJTI~NCIRCUITS

Copper co
System
Size Zl 1 ZO Cl
-- --
4-wire 4/o 0.278+jO.615 0.564fjl.89 0.0187 0.0078
No. 6 2.18 +jO.756 2.03 +j2.77 0.0149 0.0069
3-wire 4/o 0.278+jO.615 0.564fj3.15 0.0187 o.oo@
No. 6 2.18 +jO.756 2.47 fj3.29 0.0149 0.0059
Single-phase1 4/O 1 2 =0.373+j1.04 4
Note: All impedancesin ohms per mile at 60-cycles. All capacitancesin miorp
farads per mile.
I I I I I I I
OO 200 400 600 BOO 1000 1200 Fault location was found to have a significant effect so.*
TIME IN MICROSECONDS faults were applied on the sending-end bus and at the
Fig. 24-Comparison of system recovery voltage and dielec- s, and 1.0 points, the latter being the open end of the
tric recovery curves for De-ion protector tubes. ’ Recovery The studies were made by applying single- and dou
voltage data re-plotted from Fig. 22. line-to-ground faults at four locations, and recording
Chapter 14 Power System Voltages and Currents During Abnormal Conditions 509

times to go-percent voltage, and the times and magnitudes were t,hen reduced to a one-milt basis by dividing bv the
associated with the maximum recovery-voltage transient. line length in miles; then plotted as a function of the
These data are illustrated in Fig. 2Gfor the case of a single- S/M ratio (ratio of source ohms to line lcngt,h in milts).
line-to-ground fault on an eight-mile syst,cm. Time is cx- These data are summarized in Fig. 27 for single- and
llrcssed in microseconds and voltage in percent of normal double-line-to-ground faults, and 4/O and Ko. G copper
line-to-ground crest voltage. It is evident that, fault loca- conductors. The times, for a given S/J1 ratio, do not
tion has considerable influence on the pertinent data. With vary greatly with the type of fault or the conductor size,
even though consideration was given to vnriorrs fault
locations. For this reason, it was decided that prncticnl
answers could be obtained by drawing a single curve under
each set of data. The differences between the actual times
and those defined by the lower-limit curves were not
considered important in view of the complexity of the over-
all problem, and the complicated circuits encountered in
practice. The actual times for any given lint length can be
obtained by multiplying the values in Fig. 27 by the line
length in miles.
The maximum voltages measured are plotted in Fig. 25
as a function of the X/M ratio. Values are included for
/ four conductor sizes, which allows an evaluation of this
FAULT
2
w - LOCATION --x=2 X=8
SENDING END l A
;
0 40 - 2 MILES o 0
w
(I 4 1’ Y 0
8 1’ + *
-DEFINING CURVES
0 I I I I I I
0 40 80 120 160 200
TIME IN MICROSECONDS

Fig. 26-.Method of recording and interpreting data illus-


trated for one line-to-ground fault on eight-mile, four-wire
system.

a two-ohm source, the time to go-percent voltage is a


minimum for a sending-end fault, whereas a receiving-end
fault dictates this time with an eight-ohm source. Maxi-
mum voltages are obtained for faults away from the send-
ing-end bus. However, many cases were noted where the
maximum voltage did occur for sending-end faults, es- I.OIIV~l 1 111 II/l I III
pecially where small line conductors were represented. This .0?5 .07 0.1 0.2 0.3 0.5 0.7 I 23 579
illustrates the complexity of the problem, and the need X/M
for considerable data before formulating conclusions. Fig. 27-Times to 90 percent and maximum recovery voltage
11sit would be impractical to summarize, in the form of referred to a one-mile line basis. To.g/M, T,/M-times to 90
useful curves, all of the data obtained, a simple uniform percent and maximum voltage divided by line length in miles.
method of interpretation was adopted. As a protective X-60-cycle sourcereactancein ohms
(lcvice must function at any location on a circuit, it is I--T,/,M neglectingline inductance
necessary to know only the most severe circuit conditions, II--To.~/M neglectingline inductance
regardless of fault location. With this in mind, a straight III--?‘o.Q/M neglecting line reflections
he was drawn to connect the points giving the minimum
times to go-percent and maximum recovery voltage. This variable on the voltages obtained. Conductor size has the
line then defines the voltage-recovery characteristics of the most influence on the maximum voltages when the X/i11
Particular system. In certain cases, such as the eight-ohm ratio is small. With 4/O conductors the voltages do not
System in Fig. 26, the defining straight line was extended vary appreciably with the X/N ratio, and can be repre-
through one maximum voltage point to a horizontal line sented by a straight horizontal line equal to 175 percent
that intercepts the highest voltage recorded. This results for single-line-to-ground faults and 205 percent for double-
in a simple method of plotting data without being ultra- line-to-ground faults. If protective devices are to be
conservative. In the case illustrated, the maximum re- applied independent of conductor size, these maximum
covery voltage would be recorded as 170 percent at 140 values should be considered as a basis for standardization.
microseconds. The voltages are expressed in percent of normal line-to-
The times to 90 percent and to maximum recovery volt- ground crest voltage and apply to systems in the 2400- to
age were obtained by plots similar to Fig. 26. These times 13 800-volt range.
Power System Voltages and Currents During Abnormal Conditions Chapter 14

Because of conclusion 2, calculations were made for


the case of an infinite number of lines in parallel, by
neglecting all line inductance and representing the lines
by lumped capacitances. These data, for a single-line-t%
ground fault on a two-ohm, 16-mile system are given in
Table 5. The maximum voltages vary between 168 and
TABLE&CALCULATEDRECOVERY-VOLTAGEDATAFOR A SOLIDLY.
GROUNDEDSYSTEM CONSISTINGOF A TWO-OHM SOURCEAND
16-MILES OF LINE
.3:,
"y
Conductor
System
Size

No. 6 a-wire 43.5 00 175 i&


4/O a-wire 47.3 95 168 ,:’
3 456 810 .‘No. 6 ‘4-wire 45.3 94 183 5:;
;3j
X/M 4/O 4-wire 49.6 103 180 :i.”
(a) IL-G FAULTS +-
Note: The shove data were calculated for B sinule-lint-to-ground fault. ne&ctfng ,i
loss and line inductance. ..

183 percent, and compare favorably with the 175 percent -’


,” 200 obtained in the general study for single-line-to-ground <,’
aw faults. The times to maximum voltage range between 90 ‘I
z-
160
and 103 microseconds, the shorter time being obtained ‘4
ii with the smaller conductor on a three-wire system. The ‘:.’
5 time to go-percent voltage is also a minimum for this same I.
‘“.
9 120 system.
G Whenever line inductance can be neglected, the signifii >i
y8 00
cant recovery voltage times vary as JXM, where X is the !
60-cycle source reactance and- M is the’ total miles of 5.
E connected line, assumed to be equal on $he three-phases. ,;s
5 40 . 2/o cu * Curve I, Fig. 27, is the calculated curve for times to 1
I A*2 GU ’
; rY6 CU ‘* maximum voltage for a single-line-to-ground fault on a ‘.
2 n
No. 6-conductor, three-wire system. This straight-line ;
0704 .06 08 .Ol 0.2 0.3 0.4 06 0.8 I 2 3 456 810 curve approaches the analog comnut,er data for X/M
X/M ratios at&e 1.0, even thoughthe computer data were’ob- :;
(b) 2L-G FAULTS tained for a single line, and the calculated curve applies for i,
,,:’
%
Fig. 28-Maximum recovery voltages as a function of X/M an infinite number of lines in parallel. This shows that l,,
ratio. line inductance has little effect on the times to maximum
S-Source reactance in ohms voltage for large X/IV ratios. The significant time to
M-Line length in miles maximum voltage for the case of a d-mile line and a 12-
mile line in parallel is plotted in Fig. 27. This point falls
General Circuit Arrangements-The data in Figs. closer to Curve I than to the single-line curve. AS most
27 and 28 are obtained for a source and a single line, which systems have a multiplicity of circuits, it is suggested that
would be an exceptional condition in practice. It is there- curve I be used for estimating times to maximum voltage,
fore necessary to have available a definite procedure for regardless of circuit arrangement. Curve II, Fig. 27,
estimating the voltage-recovery characteristics of the more represents the times to go-percent voltage for the case of
practical systems, consisting of a multiplicity of trunk an infinite number of parallel circuits. The times to 9@
feeders and laterals. Guided by the results of analog percent and maximum voltage, for the limiting case of an
computer studies of a few special cases, theoretical equa- infinite number of feeders in parallel, can be estimated +
tions have been derived for estimating the voltage-recovery follows :
characteristics of practical systems, and are included in (1) To.9= 7.7 ~XIM microseconds.
this section. (2) T, = 15.9 4X&I microseconds.
Studies’ were made of a system with 16 miles of line Note: X is the 60-cycle source reactance in ohm%
connected as (1) one 16 mile line, (2) two eight-mile lines and M is the connected overhead line in miles
in parallel, and (3) one four-mile line in parallel with one per phase, including trunk feeders and laterals.
12-mile line. The following conclusions were drawn from The constants in the equations were derived
the data obtained: from the calculated times in Table 5 for a No,
1. The time to go-percent voltage is a minimum with a 6 conductor, three-wire system.
single line.
2. The time to maximum recovery voltage is a minimum The computer data in Fig. 27 fall close to Curve II f0:
with more than one line in parallel. X/M ratios larger than approximately $$. BeloW th$

...
.,
F
Chapter 14 Power System Voltages and Currents During Abnormul Conditions 511

/ARC
ratio, the times for a single line are not a function of line 200%/J RESTRIKES
lengt,h, but only of source reactance. The minimum times
!,,erc obtained for single-line-to-ground faults on the send-
ing-end bus, and the recovery voltage reached the 90-
Percent values before reflections returned from the open
end of the line. These times therefore vary directly with
tlic GO-cyclesource reactance, and follow Curve III.
With several long feeders in parallel, and a low source
rcLtctance,the times to go-percent voltage are independent 1/ARC
of line length, and vary directly with source reactance and EXTINGUl3HED
,vith the number of feeders connected to the source bus.
These cases can be represented in Fig. 27 by additional
curves in parallel with Curve III, and with the times for a
given X/M ratio increased directly with the number of
Parallel feeders. The times to 90-percent voltage for these
long-line cases, where line reflections can be neglected, can (d)
l)c estimated from the following relation:
Fig. 29-Arcing fault at the terminals of a three-phase gen-
(3) To.g= 13.8 NX, where X is the 60-cycle source re- erator grounded through a neutral reactor.
actance in ohms and N is the number of long feed-
ers in parallel. The constant in the equation X,-Reactance of generatorwinding
C-Capacitance of generator winding to ground
is the calculated time to go-percent voltage for X,--Neutral reactor
a system consisting of a one-ohm source and a I--Fault current
single No. 6 copper overhead circuit. +--Fault voltage
e,--Internal voltage of generator
In any particular case being studied, the time to 90-
percent voltage should be calculated by Eqs. (1) and (3),
ant1 the minimum time thus obtained should be used. neglected, the circuit in Fig. 29 (a) can be reduced to the
‘This procedure will give conservative results for systems simple circuit in Fig. 29 (b).
normally encountered in practice. In the assumed circuit the fault current will lag the
generated voltage by 90 electrical degrees as loss has
9. Switching Surges and Arcing Grounds been neglected. If the arc in the fault is extinguished at
The transient voltages discussed in the previous sec- the instant the fault current passes through zero, as
tion were based on the opening of a circuit without re- shown in Fig. 29 (c), the voltage across the fault will not
striking. Under some conditions restriking of the arc can immediately return to normal but will oscillate around
occur, resulting in transient voltages of higher magnitude normal. It will reach a crest of twice normal voltage, $5
than produced with no restriking. Circuit changes that cycle of the high frequency oscillation after the arc is
produce the highest transient voltages involve arc paths. extinguished. This oscillation is the same as the simple
The arc path may be in the fault or it may be in a circuit- oscillation discussed in connection wit,h Fig. 16. During
interrupting device such as a circuit breaker. If the in- the fault, approximately full generated voltage appears
termittent arcing takes place in a fault to ground, the across the neutral reactor as it has been assumed that the
P~rn~%?Z?ZZZ~~&-~%~e reactance of the neutral reactor is large in comparison to
~Xr%-ii%?ir~~t~~itlng~evice the voltages the machine reactance. Therefore at the instant the arc
Prom3Xiqvm is extinguished in the fault, the voltage across the reactor
“TlKmec--f-- lanism -b$- - w ic m ermlttent arcs produce is approximately equal to the crest value of the gener-
high transient voltages can best be explained by using ated voltage. After the arc is extinguished the steady-
simple circuits that are basically equivalent to actual power state voltage across the neutral reactor is zero. The re-
systems. Also it is convenient to represent the intermit- actor voltage will therefore oscillate from a plus 100 per-
tent arc by a switch, the opening and closing of which is cent voltage to a negative 100 percent voltage following
equivalent to the extinction and restriking of the arc, arc extinction.
respectively. Using simple circuits, the mechanism of Xow, if the voltage across the arc rises faster than the
Producing transient voltages will be explained for both dielectric strength of the arc space recovers, the arc will
arcing grounds and swit.ching surges. restrike. This restriking of the arc can occur at any
Arcing Grounds-Theory-The circuit in Fig. 29 point on the wave of high frequency voltage across the
illustrates the phenomenon during an arcing ground on arc. Suppose the arc restrikes when the voltage across
a system. The windings of a three-phase generator are the dielectric reaches its maximum value of twice normal.
‘epresented by simple T networks. The generator is as- After the restrike occurs the fault voltage will drop to
sumed to be grounded through a neutral reactor, the re- zero as shown in Fig. 29 (c). After the arc restrikes the
actance of which is large in comparison with the gen- steady-state voltage across the neutral reactor will be
erator winding reactance. It is further assumed that an approximately equal to the crest value of the generated
arcing fault occurs at the terminals of the generator. If, voltage. The reactor voltage will therefore start at a
for the purpose of discussion, the unfaulted phases are negative 100 percent voltage at the instant the arc is
512 Power System Voltages and Currents During Abnormal Conditions Chapter 14

reestablished and will oscillate around normal voltage, opening, the capacitor voltage mill tend to reach a value
reaching a crest of three times normal. of fl but will overshoot to +5. Thus the voltage builds
In the above analysis it was shown that the voltage up according to the series, 1, 3, 5, 7, . . and will have no
across the neutral reactor can reach three times normal limit if damping is neglected. In this analysis it has been
line-to-ground voltage even when the arc is reestablished assumed that the inductance is small and that the nat-
only once. This process can be repeated several times re- ural frequency of the circuit is high in comparison to the
suiting in still higher voltages. In this analysis it was as- fundamental frequency.
sumed that arcs were extinguished at zero points of the
high-frequency current wave (except for the first estinc-
tion) and arcs were established at the crest of voltage
naves. Other tl~eories2*Rof arcing are based upon fun- A
1 0
damental frequency arc extinction and restriking. \ SOLID
e
Switching Surges-Theory--The transient voltages LL
B,
‘( FAULT
produced during the de-energizing of an unfaulted line u
section are shown in Fig. 30 for a single-phase system in
which the line is represented by a condenser. The suc-
cessive steps of building up the capacitor voltage are (a)
shown in Fig. 30 (b). Kormal capacitor voltage has been
added as a dotted curve. The capacitor voltage is nor-
mal and at point A the switch is opened and a charge is
left on the capacitor. The switch voltage is now the
algebraic sum of the generated voltage and the voltage
resulting from the charge on the capacitor. It will reach
a maximum of twice normal generated voltage at one--
half cycle of fundamental frequency after the switch is (b)
opened. At point B the capacitor voltage has a value of Fig. 31-De-energizing a line section subjected to a single
fl in per unit values, whereas the normal capacitor line-to-ground fault.
voltage, with the switch closed, is -1. If the switch is
A third important case is de-energizing a line section
subjected to a single line-to-ground fault. Consider a
solid single line-to-ground fault on phase’C of the threc-
phase system in Fig. 31. Assume the fault is cleared by
the opening of the circuit breaker with arcing in pole A.
First, if XN is large in comparison to the reactance of the
generator, full line-to-line voltage will appear between
phase A and ground, independent of whether pole A of
the breaker is closed or open. For simplicity the three-
VOLTAGE ACROSS
phase system can be reduced to the circuit in Fig. 31 (b)
CAPACITOR “C.’ in which the breaker is represented by a switch. Normal
line-to-line voltage has been inserted back of Xx. The
only difference between this circuit and the one in Fig.’
30 is in the voltage back of the circuit reactance; the
voltage in Fig. 30 (a) is normal line-to-neutral voltage
and the voltage in 31 (b) is normal line-to-line voltage.-
The transient voltages produced in the circuit in Fig. 31
(b) will therefore be equal to 4, times the voltages pro-
duced in Fig. 30 (b). The voltage across t)he capacitor will
then increase according to the series & (1, 3, 5, 7---).
Characteristics of Arc Path-In Fig. 32 is shown
the voltage across the switch for the transient conditions
(b) in Fig. 30. The switch voltage is found by subtracting
Fig. 30-De-energizing an unfaulted line section.
the condenser voltage from normal generated voltage.
Sate: Switch opened at A, C, E The first arc reestablishment occurs at A at twice normal
Switch closed at B, D voltage. This requires that the dielectric strength of the
arc .path recovers along some curve such as I, that is, ,
closed at this time the capacitor voltage will tend to along a curve above the curve of recovery voltage until .s.
reach a value of - 1 but because of the circuit inductance at point A where they intersect. While the arc path is <I,,
or inertia the voltage will overshoot and, without damp- conducting, the dielectric strength of the switch is prac-
ing, will reach -3. If now the switch is opened, the tically zero. When the arc is again extinguished, the.
capacitor wili’ have a charge corresponding to a voltage dielectric strength curve again starts from zero but re-
of -3. If the switch is again reclosed one-half cycle after covers much more rapidly and intersects the curve Qf
Chapter 14 Power System Voltages and Currents During Abnormal Conditions 513

ceding theories, More specifically, the maximum volt-


ages are obtained for simple circuits with the arcs recw-
ring at, either the high-frequency voltage crest or at the
fundamental-frequency voltage crest. With complicated
circuits higher voltages may be obtained if the arc is es-
tablished before or after these points. This is because the
oscillating circuits have several natural frequencies. The
determination of the exact manner of restriking is diffi-
cult to define analytically. Because of this fact and be-
cause of t,he importance of damping it is imprnct,ical to
350,000 KVA LOAD
GENERATORS AT SO % R F.
156,000 KVA
40 X REACTANCE
ter
RECEIVING SOURCE
3
25% REACTANCE

Fig. 33--Schematic diagram of system selected for study.


P
study arcing grounds and switching transients by the
Fig. 32-Dielectric recovery characteristics assumed in Fig. 30. usual mathematical methods. It is more convenient to
represent actual systems in miniature on the a-c network
wcovery voltage at the point B causing a second re- calculator and perform the switching operations with the
strike. If the dielectric strength of the arc path recovered special switches described previously.
along some curve III the arc would not reestablish at B. To study the magnitude and other characteristics of
These curves show the requirement for the dielectric transient voltages produced by switching operations and
strength of the arc path to obtain high overvoltages. If faults with intermittent arcing, a typical transmission
curve I were not as high as shown, the restrike would system (Fig. 33) was selected for a study* on the a-c
have occurred at a lower voltage, and the capacitor volt- network calculator. Since these transient voltages are
age would not have been as large as shown in Fig. 30 greatly influenced by the method of grounding, the neu-
(b). If the dielectric strength had built up at a more tral impedances of the system were varied through a wide
rapid rate, no restrike would have taken place. Thus, the range of resistances and reactances, between the limits
dielectric strength must build up at a higher rate after of the solidly grounded system and the ungrounded sys-
any extinction than it did after the preceding extinction tem.
to develop cumulatively higher voltages. This phenom- The system consists of a hydroelectric generating sta-
enon is unlikely to take place in open air between sta- tion, the output of which is transmitted 100 miles over
tConary contacts because such an arc path is unlikely to 230-kv lines to a load, which is also supplied by local
develop the required dielectric recovery strength. In steam generators. The sending and receiving-end tmns-
confined arcs, where the pressure may increase after each formers are star-connected on the 230-kv side to permit
condrlction period, this phenomenon may take place. grounding, as discussed subsequently. The reactance
Separation of breaker contacts has a tendency to cause characteristics of the different parts of the system are
higher dielectric strength recovery rates after each con- shown in Fig. 33 and the wire sizes and configuration of
ducting period because of the increasingly larger contact
Separation. These requirements of the arc path probably
provide an explanation for the difficulties experienced in
att,empts to produce high voltages by arcing in air over
insulator strings. The conditions for producing high
voltages by intermittent arcing are somewhat more fav-
orable for apparatus failure under oil than for flashover
of an insulator string. Perhaps apparatus failure under
oil causes line flashover instead of a line flashover causing
apparatus failure.
General Study-The foregoing discussion has been Fig. 34-Configuration of transmission line.
based on simple circuits for the purpose of illustrating
the essential elements of the theories of intermittent arc- the transmission lines are shown in Fig. 34. The trans-
ing. All actual systems are relatively quite complicated mission lines are separated so there is no mutual effect
and cannot be reduced to the simple circuits used. Be- between them. Also, the generators at both ends of the
cause of this complexity, the maximum voltages with line are assumed to be in phase and to have the same in-
intermittent, arcing are not quite in accord with the pre- ternal voltage.
514 Power System Voltages and Currents During Abnormal Conditions

The general method of setting up the network calcu- 1. Arcing-ground conditions on one phase to ground.
lator makes use of equivalent three-phase networks for 2. De-energizing an unfaulted line, one pole unit open-
each circuit element such as machines, transformers, and ing and two remaining closed.
transmission lines. The character of these equivalent cir- 3. De-energizing an unfaulted phase with a ground
cuits is obvious and requires no comment except for the fault, on one of the other phases, one pole opening and
transmission lines, and these are represented by the cir- the other two remaining closed.
cuit shown schematically in Fig. 35. 4. De-energizing an unfaulted phase with a ground
fault on the two other phases, one pole opening and the
other two remaining closed.
In general, arcing-ground conditions are for a fault on
one phase. De-energizing a line section is considered
more important than energizing because for the latter
the intermittent arcing is limited in duration by the ~10%
TTT TTT TTT ing of the switch. In the case of opening the faulted
Fig. 35-Equivalent network used for representing each 230
lines it is assumed that the unfaulted phase opens before
kv transmission line of Fig. 33. the pole units of the faulted phase or phases. Such an
assumption is based on the ability of the switch to re-
The highest voltages for a particular condition are cover dielectric strength at a high rate. This assumption
sought throughout the investigation. In the arcing tends to give higher magnitudes of transient voltage. If
ground the fault is applied at the crest of the normal line- the pole unit in the sound phase tends to open after the
to-ground voltage and is then removed at the first current fault is cleared, then the voltages will be similar to those
zero. The point of restriking is adjusted to give the max- produced when an unfaulted line is de-en&gized. The
imum voltage for the number of restrikes considered. The voltages will range between these limits as the time of
fault is always removed at the first current zero following relative opening is varied. The conditions selected for
each arc recurrence. In the case of switching operations study illustrate possible circuit-breaker operations on an
the circuit is initially opened at a fundamental current actual system.
zero. The point of restriking is adjusted so as to give In this study the transient voltages are obtained for
the maximum voltage for a given number of restrikes. the conditions corresponding to both one and two re-
The subsequent circuit openings are always assumed to strikes. This number of restrikes may be taken as the
take place at the first current zero following the arc equivalent of a larger number with the earlier restrikes
reestablishment. taking place so quickly that they do not contribute much
The highest voltages at the point of circuit change are to the voltage magnitude.
always recorded. For esample, for arcing-grounds the One of the variable factors considered is the method of
voltages are measured at the receiver end. On the other system grounding that includes both resistances and re-
hand, in the case of de-energizing an unfaulted or faulted actances between the limits of a solidly grounded system
line, the voltages are measured at the sending end where and an ungrounded system. When the system is solidly
the switching is done. When arcing grounds are con- grounded, the transformer at the sending end is solidly
sidered on the system, several phase voltages as well as grounded when one line is in operation, and the trans-
the neutral voltage are recorded. In the case of switching formers are solidly grounded at both ends when two lines
operations the voltages are recorded on the phase being are in operation. In the case of impedance grounding a
switched, both on the line and supply sides as well as reactor or resistor of varying ohmic value is considered
across the switch that is opening the circuit. in the neutral-to-ground circuit at the sending end when
The voltages recorded are those occurring Icithin 1% one line is in operation, and a reactor or resistor of equal
cycles of the first interruption considered. In some cases, magnitude is considered in the circuit in the sending and
either because of system loss or because of the relation receiving ends when two lines are in operation. The
of the natural frequency to the fundamental frequency, ohmic values plotted on the figures to be discussed later
higher voltages may be experienced with one or no re- are the actual ohms considered in the ground connection
strikes than with two or one restrikes, respectively. In at one point. For example, 50 ohms on a system lvith one
some cases, particularly in the ground-fault neutralizer ground point is the resistance or reactance considered in
case, the voltages after the lx-cycle period may con- the sending end ground. When two lines are considered
tinue to increase to a much higher steady-state voltage. in operation, 50 ohms corresponds to the ohms in the
With a ground-fault neutralizer quite high voltages are sending-end neutral connection and a like value in the
obtained if the circuit is in tune at fundamental fre- receiving-end neutral connection.
quency and a residual voltage is produced as by some un- Results of General Study-The results of the a-c
balance. l?or example, the opening of one phase of ct sys- network calculator study are presented in graphical form
tem subjected to a three-phase or a line-to-line fault on the in Figs. 36 to 39 inclusive. They give the transient volt-
phase being opened will produce a steady-state voltage ages expressed in percent of the normal line-to-ground
of many times normal. voltage crest and are plotted as a function of the react-
In this investigation of transient overvoltages pro- ance or resistance in the neutral connection. The sohd-
duced by switching operations and faults, four principal line curves are for reactance grounding and the dotted-
cases have been selected for study as follows: line curves arc for resistance grounding. The neutral
Chapter 14 Power System Voltages and Currents During Abnormal Conditions 515

reactance correspondin g to a ground-fault neutralizer is for a free-neutral system the voltages are appreciably
indicated. In cnch of these figures the data is plotted for lower for the larger lengths of connected lint.
,~ncand two lines and one and two restrikes. The transient voltages for the condition of de-energiz-
>-isshown in Fig. 36 transient voltages can be avoided ing a line section with a fault on a phase other than that
t,y the use of the solidly-grounded system or the system which is being switched are shown in Fig. 38. The volt-
Irr,junded through a ground-fault neutralizer, both of
13 ages in all cases of reactance grounding increase as the
neutral reactance increases. The voltages between neu-
ONE LINE TWO LINES tral point and ground also increase for resistance grouncl-
ing as the magnitude of the resistance is increased. The
voltages with a ground-fault neutralizer are definitely
higher than for any of the lower values of reactance
grounding. This is to be contrasted with the dip in the
voltage curves of Figs. 36 and 37. In Fig. 38 the volt-
ages with two restrikes increase as compared to the case
with one restrike. As would be espected, the longer the
connected line, the lower the magnitude of the transient,
voltages.
, Figure 39 shows the results of a study similar to that
NEUTRAL REACTANCE -OHMS NEUTRAL REACTANCE - 0tih4.s of Fig. 38 except that a double instead of a single linc-
0 20 40
NEUTRAL
60 60 100
RESISTANCE -OHM:
0 20 40 60 60 100
RESlSTANCE - OHM:
to-ground fault is applied to the line sect,ion being de-
NEUTRAL
energized. In general, the comments are the same as for

ONE LINE TWO LINES


w7w ,700
s 1 RESTRIKE 0 I RESTRIKE I

NEUTRAL REACTANCE-OHM;
0 20 40 60 60 100 m 0 20 40 60 60 100
NEUTRAL RESISTANCE -OHMS NEUTRAL RESISTANCE-OHM; -lu”W~ ~~ -0 200 A00 600 600 1000
plct
.__I 17-n
..AL REACTANCE-&MS NEUTRAL REACTANCE-OHM:
Fig. 36-Effect of grounding impedance on transient voltages 0 20
-- 40 60 80 100 - 0 20 40 60 80 100
NEUTR. AL RESISTANCE- OHMS NEUTRAL RESISTANCE-OHM:
caused by arcing grounds.
w 700
Solid curve: Rcttctsnce grounding
I)ottcd curve: R&stance grounding ya,,
2
eT=l,
RESTRIKES
1
Sate: Letters on curves refer to lettered points on inset circuit.
Ground-fault neutralizer reactance: 875 ohms

which have been employed for many years to avoid the


:Lbnormal voltages encountered on ungrounded systems.
The voltages corresponding to resistance grounding are
fairly uniform and relatively low for the range of resist-
ance studied. However, for neutral resistances approach-
ing infinity, the transient voltages will approach those _“” -WV w -0 200 A00 600 800 1000 -
IUEUTRAL
-...,. REACTANCE-OHMS NEUTRAL REACTANCE- OHMS
of the ungrounded system. The study shows that there 0 20. 40 60 80 100 00 0 20 40 60 80 100 -
is a value of reactance intermediate between the solidly NEUTR, 4L RESISTANCE-OHMS NEUTRAL RESISTANCE-OHMS

grounded system and the system grounded through a Fig. 37-Effect of grounding impedance on transient voltages
ground-fault neutralizer almost as high as for the un- caused by de-energizing an unfaulted line
grounded system. See subcaption of Fig. 36.
‘The transient voltages resulting from the de-energizing
of an unfaulted line are shown in Fig. 37. The lowest the case of Fig. 38. For reactance grounding the tran-
transient voltages, with the exception of those across the sient voltages increase rapidly for a relatively small addi-
neutral impedances, are obtained for a system grounded tion of neutral reactance, so that for low neutral react-
through a ground-fault neutralizer. In all cases the neu- antes the transient voltages closely approach those of the
tral-point voltage increases as the neutral impedance in- free-neutral system.
Creases. For the range of practical neutral impedances, The results obtained in the a-c network calculator stu-
there is no appreciable difference between the voltages dies are based on a definite number of restrikes which
obtained for the case of one and of two lines. However, are spaced at such intervals as to give the maximum volt-
516 Power System Voltages and Cbrents During Abnormal Conditions Chapter 14

age for this number of restrikes. Thus, in the average 10001


ONE LINE
case, since the restrikes may not occur at the optimum
point, the voltages will be of lower magnitude giving a
probability curve for the voltage. Of course, only a mi-
nority of the cases of system faults and switching produce
abnormal voltages.
The a-c network calculator studies have also been
based on the assumption that transient voltages of in-
creasing magnitude can be impressed on the system with-
out altering the characteristics of the system. Actually,
the transient voltages will be limited by other factors
that become of increasing importance as the transient
voltage increases. On some systems corona will limit the
magnitude of transient voltage by introducing losses in
the oscillating circuits. Under some conditions excess
0 200 400 600 800 1000 - 0 zoo 400 600 8ca Ioc
NEUTRAL REACTANCE-OHMS NEUTRAL REACTANCE -OHMS
ONE LINE TWO LINES 0 20 40 60 80 100 00 0 20 40 60 80 100
NEUTRAL RESl.SrANCE-OHMS NEUTRAL REStSTANCE-0”~;

‘; 600 I
k! _...-.
. ,: ,! .

NEUTRAL REACTANCE-OHMS NEUTRAL REACTANCE -OHMS


0 20 40 60 80 100 - 0 20 40 60 80 100 - 0 200 400 600 800 1000 0 0 200400800600Ica -
NEUTRAL RESISTANCE -OHMS NEUTRAL RESISTANCE -OHMS NEUTRAL REACTANCE -OHMS NEUTRAL REACTANCE-OHMS
0 20 40 60 80 100 0 20 40 60 80 100 -
mu NEUTRAL RESISTANCE -OHM: NEUTRAL RESISTANCE-OHMS

Fig. 39-Effect of grounding impedance on transient voltages


caused by de-energizing line with double line-to-ground fault
: 800 See subcaption of Fig. 36
2
2 700
>
tude of transient voltages on a particular system. Fi-
5 800
E
nally, the transient voltage is limited by the flashover
u 500 characteristics of line and apparatus insulation. Oper-
a1 400 ating experience confirms the results of this study in that
cc
0 some switching operations do result in flashover of line or
2 300
neutral-point insulation.
& 200
Many klydonograph investigations have been reported
s
100
in the literature, and frequently overvoltages resulting
oy J-r&-$--t++-j from switching operations are segregated from those due
0
0 200 400 600 800 1000 - 0 200 400 600 800 loo0 - to lightning. Extensive investigations were reported by ,
NEUTRAL REACTANCE-OHMS NEUTRAL REACTANCE -OHMS
0 20 40 60 80 100 0 20 40 60 80 100
Cox, McAuley, and Huggins,g Gross and Cox,iO Lewis and
NEUTRAL RESISTANCE-OHM6 NEUTRAL RESISTANCE-OHM? Foust,ll and by some European investigators. The Joint
Fig. 38-Effect of grounding impedance on transient voltages Subcommittee on Development and Research of the Edi-
caused by de-energizing line with single line-to-ground fault son Electric Institute and Bell Telephone System, has
See subcaption of Fig. 36. also-carried on investigations and has made an excellent ,.’
,:A
summary’” of the more important published data. ,,s
voltages will produce increases in exciting current par- The principal results of the switching-surge studies us- *’
ticularly at the lower frequencies, but usually this factor ing the klydonograph have been summarized in Fig. 40.
is unimportant. Transient voltages can also be limited Curves A and B, obtained from the original investiga-
by the operation of lightning arresters or prot,ective gaps tion by Cox, Mchuley, and Huggins, give the voltages
adjusted to operate below the flashover level of line or ap- caused by energizing or de-energizing operations and the
paratus insulation. These devices may limit the magni- voltages resulting from faults with subsequent switching,
chapter 14 Power System Voltages and Currents During Abnormal Conditions 517

,cspcctively. Curve C gives a summary derived from the and the amount of energy in these oscillations increases.
,vork of Lewis and Foust. In order to give a more suit- Thus, these factors tend to increase the importance of
%blescale for plotting the results of the surge studies all switching surges.
the surges of a magnitude less than twice normal have The maximum voltages of Figs. 36 to 39 correspond
heen disregarded. The Lewis and Foust paper, however, closely with the limiting voltage of six times normal indi-
cated in Fig. 40. The shape of the curves of Fig. 40
should probably not be accepted too freely as these are
no doubt influenced by the flashover of lines or apparatus,
or the operation of lightning arresters.
10. Effect of Generator Grounding on Transient
Voltages
The results of the general study of transient overvolt-
ages produced by switching and faults in the preceding
section were based on the assumption that there was no
Fig. 40- -Distribution of surge voltages caused by switching appreciable arc drop and that the arc was always extin-
and faults.
guished at a current zero, either fundamental or high-
.4-Switching surges-Cox, McAuley, and Huggins frequency. In some cases, especially in low-voltage cir-
Ij-Surges from faults-Cox, McAuley, and Huggins cuits, additional characteristics of an arc must be con-
C-Switching surges-Lewis and Foust sidered because of their influence on transient voltages.
ii and B-Eighteen systems-1925 to 1926
C-Fourteen systems-1926 to 1930 AX Characteristics-Prior to the actual interruption
of the arc in a circuit breaker there is a voltage drop be-
tlveen the breaker terminals. The magnitude of this drop
HIKNXthat of all the reported surges above normal volt- varies for different types of breakers, being lower for the
:LIJC,45 percent were above twice normal. Fig. 40 shows
higher voltage circuit breakers when expressed in percent
that the limiting value of the surges is about six times
of system voltage. This drop is of two parts, first an arc
normal crest voltage, 5 percent exceed five times normal,
drop that is fairly uniform in magnitude and lasts during
:mtl 20 percent exceed four times normal. These results the entire arcing period, and second, a drop that is a
show that there is an upper limit to the voltage recorded, function of the efficiency of arc interruption and the cur-
indicating the possibility of some limiting factor. Fig. 41
rent being handled. Fig. 43 shows a fairly uniform break-
shon-s the ratio of flashover voltage to the normal crest
er voltage until the arc is ruptured at which time the
voltage, for transmission lines of different voltages. The
voltage increases quite rapidly to a negative crest of ap-
shapeof the curve of Fig. 40 compared with the data given
proximately normal line-to-ground crest voltage. This
in Fig. 41 indicates that the magnitude of switching
negative crest voltage is commonly referred to as the
breaker “extinction voltage.” An analysis made of os-
cillograms of inany breaker operations indicates that for
a circuit breaker opening 12 000 and 13 200-volt circuits
this “extinction voltage” may be as large as 125 percent
of the normal line-to-ground crest voltage but is usually
much lower. This extinction voltage is produced by ex-
tinction of the arc before a normal current zero, that is,
before the current in the arc would normally pass
through zero.
In general, the same characteristics as mentioned
above are found in all arcs under oil or in confined spaces,
such as arcs caused by flashover of apparatus under oil,
in cables, etc. Arcs between stationary contacts in air
will usually have entirely different characteristics because
‘ no large de-ionizing agent is present.
t i i i i i
Effect of Extinction Voltage on Transient Volt-
3O 4 6 12 16 20 ages-The system in Fig. 42 will be used in presenting the
NUMBER OF INSULATORS
theory involved in the production of transient voltages
FilL 41--60-cycle flashover voltage ratios for lo-inch suspen- by switching or arcing grounds. In this circuit the gen-
sion insulators. erator windings are represented by simple T networks and
additional capacitance is added at the machine terminals
surges recorded could be limited by line flashover. While to represent the capacitance of connected feeders. The
it is undoubtedly true that a considerable portion of positive, negative, and zero-sequence reactances of the
these switching operations occur with relatively little generator and feeders are assumed to be equal. The
energy in the oscillation and at relatively high frequency, generator is grounded through a neutral reactor, and a
it is also true that as systems expand the natural fre- single line-to-ground fault is assumed on a feeder outside
quency of systems for switching operations decreases of a breaker. The effect of the unfaulted phases on the
518 Power System Voltages and Currents During Abnormal Conditions

t,rnnsient voltages can be neglected, reducing the circuit zero; and without damping it would reach a negative
to the one shown in Fig. 42 (b). crest of twice normal. With damping it reaches a nega-
Consider the case of a single line-to-ground fault oc- tive crest somewhat less as shown in Fig. 43.
curring on a feeder and the fault removed by operation With the breaker open and with the fault on the sys.
of the breaker. The fault is assumed to last long enough tern, the normal steady-state voltage across the breaker
to allow damping out of all initiating transients and the is approximately equal to the generated voltage. When
the arc is ruptured at A the breaker voltage will start at
a ncgativc crest of 100 percent and oscillate around the
generated voltage. It will reach a positive crest of three
times normal with no damping or some less with damping,
The maximum reactor voltage is equal to the breaker
extinction voltage plus the generated voltage at the time
OCB this extinction voltage appears across the breaker ter-
A
minals. In the case of a reactance grounded generator
:<F the arc is ruptured at near crest generated voltage so
cg cg cb -cb _cb
the reactor voltage is equal to the extinction voltage plus
normal crest generated voltage. The breaker voltage ap-

xg/2 xg/2OCB proaches a crest equal to twice the generated voltage plus
the extinction voltage.
c

xNf-JT-p~F BREAKER ‘1
iJ
Ii
AB
VOLTAGE -1
11
(b)
Fig. 42-Generator grounded through neutral reactor.
(a) Simple three-phase system
(b) Simplified single-phase system
X,-Generator subtransient rcactancc
(‘,-Generator winding capacitance to ground
Cb-Capacitance of bus, cables, etc.
OCB-Oil circuit breaker (a) A
F-Fault
X,--Neutral reactor

arc in the breaker is ruptured far enough ahead of a nor-


mal current zero to give an extinction voltage equal to
normal line-to-ground crest voltage. The generated volt-
age and fault current are shown in Fig. 43 for this con-
dition. A small arc drop in phase with the current ap-
pears across the breaker terminals during the entire arc-
ing period.
If the neutral reactance is large in comparison to the
machine reactance, practically all of the generated volt-
age will appear as a drop across the neutral reactor while
the fault is present. The reactor voltage will then be ap-
(b)
proximately equal to the generated voltage until the
breaker terminal voltage starts to increase as a result of Fig. 43-Transient voltages with no restriking.
the de-ionizing action of the breaker. As the neutral re- (a) Breaker voltage.
actor was assumed to be large in comparison to the ma- (b) Reactor voltage
chine reactance, the reactor voltage is approximately e,--Normal line-to-ground voltage
equal to the difference between the generated voltage and E,,t-Extinction voltage
the breaker voltage. It therefore reaches a crest of twice i--Fault current
normal at A’. If the arc is ruptured* at A, normal gener-
ated voltage is removed from the reactor as with no AS shown in Fig. 43, the breaker voltage may build up”
fault on the system no voltage appears across the neutral fairly high. If at any time this voltage exceeds the dl-
reactor. The reactor voltage therefore oscillates around electric strength of the arc space between the breaker
*In this analysis the arc is assumed to be ruptured at the instant contacts, the arc will restrike. In Fig. 44 the restriking
of crest negative voltage between breaker terminals. It is realized is assumed to occur at the instant the breaker voltage
that the arc may be ruptured before this time. reaches its maximum value at C. Assuming that 100
Chapter 14 Power System Voltages and Currents During Abnormal Conditions 519

Percent extinction voltage appeared across the breaker axis. As the resulting breaker voltage oscillation after
terminals at the instant of arc rupture and further as- the arc is ruptured at A depends upon the generated
suming no damping, this maximum breaker voltage will voltage, the oscillations will be quite small. No voltage
he three times normal. When the breaker voltage is at appears across the resistor at the time the arc is ruptured
C the reactor voltage will be at a negative 200 percent because no current is flowing at that time. The oscilla-
voltage. When the arc is reestablished the breaker volt- tion in the resistor voltage will be small and will be
age will decrease to a very small arc drop as shown in Fig.
~4. After the restrike occurs the steady state voltage -----BREAKER VOLTAGE
across the reactor is approximately equal to the normal %
generated voltage. The reactor voltage will therefore
start at C’ and oscillate around normal generated voltage.
lt will overshoot to a crest voltage of four times normal .a
if losses are neglected.
With one restrike and without damping the reactor
voltage will reach three times normal crest generated A
v&age plus the breaker extinction voltage. With addi- (0)
tional restrikes the voltage can increase further if the
restrikes occur at the right time. It is of course rather
c
/I300 %
II
BREAKER ”
VOLTAGE ; 1

(b)
,~ Fig. 45-Transient voltages produced with resistance ground-
ing.
(a) Breaker voltage
(b) Voltage across neutral resistor
A

damped out rapidly because of the high loss present in


the system.
REACTOR
VOLTAGE
’ Parallel Resistance and Reactance-Since fairly
high voltages can be produced when a neutral reactor
is used and since these voltages are greatly reduced when
a neutral resistor is used, the question naturally arises
as to whether it would be possible to compromise and use
a combination of both. With resistance and reactance in
parallel the phenomenon will follow closely one of the
cases above depending upon which predominates. Re-
sistance in parallel with a reactor will usually prevent
cumulative building up of the reactor voltage on succes-
sive restrikes but a low parallel resistance is necessary in
order to prevent the breaker extinction voltage from ap-
pearing across the neutral reactor. As shown in Fig. 43
the reactor voltage is the sum of the generated voltage
and the extinction voltage. Because the resistance re-
Fig. 44-Transient voltages produced with restriking. quired to keep most of the extinction voltage from ap-
pearing across the neutral reactor is small, it is usually
improbable that more than one or two restrikes will occur preferable to omit the reactor entirely and use resistance
at just the right time to give these high overvoltages. grounding.
Resistance Grounding-If the neutral reactor is re- Analog Computer Studies-In the theoretical dis-
Placed with a resistor having the same impedance, the cussion given above the neutral reactance was assumed to
Power factor of the fault circuit will be approximately be much larger than the machine reactance. To show
unity. The breaker and resistor voltages for this condi- the effect of variations in transient voltages with neutral
tion are shown in Fig. 45. Normal current zero will co- reactance, studies were made on the analog computer.
incide with normal voltage zero. As the arc drop is still The circuit employed was similar to the one in Fig. 42(a)
in Phase with the current, the breaker extinction voltage excepting that the oil circuit breaker was omitted, and
and normal generated voltage are on the same side of the an arcing fault was applied between phase A and ground
520 Power System Voltages and Currents During Abnormal Conditions Chapter I4 ?‘F

TABLE ~-SURGE VOLTAGES PRODUCED WITH REACTANCE this case the maximum voltage was recorded as 430 per-
- GROUNDING cent. These results show that it would be desirable to
limit the X,/Xi ratio to some value less than ten, in order
I Surge Voltages* to rule out the possibility of obtaining the excessive tran-
sient voltages associated with the larger X,&X, ratios.
Across Seutral More fundamentally an Xo/Xi ratio should be selected
X0/X1 Faulted Phase I Jnfaulted Phases
Ratio
Reactor that does not produce a high-frequency current zero fol-
-. - lowing a restrike. If this condition is met, the voltages is
One Tao One Two not appreciably higher with two restrikes than with one,
lestrikc I i I !Ii lestrikc: j 1Rcstrikc .t R cstrikcs and no cumulative build-up of voltages is possible with
--
170 170 160 100 0 0
successive restrikes.
165 168 l-l0 142 45 45 The results in Table 6 were obtained by removing the
165 16.5 180 103 100 100 fault at a current zero, that is, without forcing current zero.
165 165 190 215 115 130 If the fault is in a confined space, such as under oil or in
apparatus or cable insulation, the deionizing agents present
6 l&5 185 200 230 150 155 may produce a rapid increase in arc drop, with the result
8 190 100 260 260 180 180 that the fault is interrupted prior to a normal current zero.
10 280 430 285 400 175 270 This forcing of a current zero increases the transient volt-
12 . 460 450 300 ages as was discussed in connection with Figs. 43 and 44.
It also increases the magnitude of the high-frequency cur-
14 400 440 390 490 250 350
rent following a restrike, which decreases the So/Xi ratio
20 390 400 410 450 250 270
30 370 400 390 500 250 300 required to produce a high-frequency current zero follow-
50 330 370 400 430 230 300 ing a restrike. This makes it difficult to select a suitable
100 280 260 400 410 230 280 maximum X0/X1 ratio for application purposes because
- - - - the ratio is influenced by the magnitude of the arc-extinc-
*Expressed in percent of normal line-to-ground crest voltage. tion voltage assumed. As discussed above under arc
characteristics, circuit breakers opening 12 000 and 13 200
at the generator terminals. The following constants were volt circuits may infrequently have extinction voltages
used : somewhat larger than normal line-to-ground crest voltage.
X,= 1.28 ohms at 60 cycles. Similar data are not available for fault arcs because this
information is extremely difficult to obtain primarily be-
C, = 0.35 microfarad.
cause of the probability nature of the phenomenon.
Cb = 0.20 microfarad.
To obtain some idea of the influence of arc-extinction
The fault was applied at the instant the 60-cycle voltage voltage on the transient voltages produced by an arcing
between phase A and ground was equal to its crest value, ground on a reactance grounded system, a special study
and removed at the first current zero, either 60-cycle or was made on the computer using the same circuit and con-
high frequency. The fault was reapplied at crest recovery stants as above. A line-to-ground fault was applied at the
voltage across the fault and then removed at the first
current zero following the restrike, or fault re-application. 250,
II II I I I I 1
In the case of two restrikes the latter procedure was re-
peated. Table 6 is a summary of the results obtained with
one and two restrikes for X,/X, ratios between one and
100. In this table X1 is equal to X, in Fig. 42, and X0 is
equal to X, plus 3X,, the positive- and zero-sequence
machine reactances being equal in the equivalent circuit
employed. The faulted phase, maximum unfaulted phase 150
and neutral reactor voltages are included in the summary.
In making these studies it was noted that the magnitude
of the transient voltages was influenced to a large extent
by the presence or absence of high-frequency current zeros 100
following the fault application or a restrike. With an
X,/X, ratio of eight, there was no high-frequency current
zero, even following a restrike, and the circuit-opening
operation was delayed until t,he 60-cycle current went 50
through zero. As considerable time was available for dis-
sipation of transient energy between circuit-closing and
circuit-opening operations, the transient voltages did not
0
exceed 260 percent with two restrikes. Increasing the
X,/X, ratio to ten gave a high-frequency current zero 2 RATIO
following the first restrike, permitting a circuit-opening
operation without waiting for a 60-cycle current zero. In Fig. 46-Transient voltages with resistance grounding.
Chapter 14 Power System Voltages and Currents During Abnormal Conditions 521

instant, the 60-cycle voltage between phase A and ground Computer studies were also made with the same system
was equal to its crest value, and removed approximately grounded through the primary winding of a distribution
one-half cycle later. The circuit was opened slightly ahead transformer, having a resistor across the secondary wind-
of a normal GO-cycle current zero to give loo-percent es- ing as shown in Fig. 29 of Chap. 19. The transient voltages
tin&ion voltage. The fault was re-applied at crest re- for this case are summarized in Fig. 47. The results are
covery voltage across the fault. It was noted that no high- plotted as a function of the kilowatts loss in the resistor
frequency current zero occurred following the restrike,
I
\vlth an X0/X1 ratio of four, but that such a zero was
present with a ratio of six. The transient voltages did not “o F320
exceed 260 percent with the ratio of four. JJ
This analysis shows that the masimum transient volt- $9
ages with reactance grounding are influenced by the X,/X, E+
ratio and by arc-extinction voltage. If the transient volt- (L $240
:a
ages are to be limited to 250 or 260 percent of normal line- 0
z
to-ground crest voltage, the X0/X1 ratio should be limited -s
to eight or four depending upon whether zero or lOO- ii= P- = NEUTRAL TO GROUND 1,
a g 160”
percent extinction voltage is assumed. In generator cir- a ,-
cry
cuits, where fault,s can occur in confined spaces, it is sug- -10 Sk----- XX 1
gcsted that the X0/X, ratio be limited to three. This limit $7 FAULTiD PHASE
permits the application of 80-percent lightning arresters, =g 80
and allows for arc-extinction voltages somewhat larger WJ
z-i
than normal line-to-ground crest voltage.
5s
Studies were made for the case of a generator grounded
through a resistor of 98 percent power factor. The circuit OO .4 .8 1.2 1.6 2.0
and constants were the same as used in the studies of re-
actance grounding. The results for two restrikes are sum- xo RATIO
Ro
marized in Fig. 46. for R,/X, ratios between 3 and 90.
.\lthough the data are based on two restrikes, there is no Fig. 48--Influence of reactance on transient voltages obtained
with high-resistance grounding.
appreciable difference between the results with one and

400 during a single-line-to-ground fault and the three-phase


I I I 1 charging kva of the system during normal operation.
360 Ratios of resistor loss to charging kva of one and larger will
limit the transient voltages to approximately 260 percent
320 of normal line-to-ground crest voltage.
The data in Fig. 47 are based on a resistor having unity
power factor and a transformer having zero reactance.
Practical resistors and transformers introduce reactance
240 in the zero-sequence circuit. To show the effect of this
reactance, studies were made for XO/Ro ratios of zero to
two. The resistor loss-to-charging kva ratio was made
equal to unity in this study. The results in Fig. 48 she\\
160
that practical values of reactance have little influence on
120 I I I the transient voltages obtained.
I
I
80
REFERENCES
40
1. Symmetrical Components by C. F. Wagner and R. D. Evans (a
book), blcGraw-Hill Book Company, Inc., New York, 1933.
0
0 .2 .4 .6 .8 1.0 1.2 1.4 1.6 I.8 2.0 2. Voltages Induced by Arcing Grounds, by J. F. Peters and J.
Slepian, A.I.E.E. Transactions, Vol. 42, April 1923, pages 478-
RATIO _ RESISTOR KW
493.
CHARGING KVA 3. The Klydonograph, by J. F. Peters, Electrical World, April 19,
Fig. 47-Transient voltages with high-resistance grounding. 1924, pages 769-773.
4. System Recovery Voltage Determination by Analytical and
A-C Calculating Board Methods, by R. D. Evans and A. C.
two restrikes. The fault to ground was always removed as
Monteith, A.I.E.E. Transactions, Vol. 56, June 1937, pages
the 60-cycle current went through zero because there were 695-703.
no high-frequency current zeros over the entire range of -
3. A Large-Scale General-Purpose Electric Analog Computer,
lie/X, ratios considered. The transient voltages do not E. L. Harder and G. D. McCann, A.I.E.E. Tmr~.snc~ior~s,Vol.
exceed
” 235 percent of normal line-to-ground crest voltage 67, 1948, pages 664-673.
ior any ratio considered. 6. Recovery Voltage Characteristics of Typical Transmission Sys-
522 Po*wer System Voltages and Currents During Abnormal Conditions Chapter 14

terns and Relation to Protector-Tube Applications, by R. D. Company’s Transmission System, by I. W. Gross and J. H. Cox,
Evans and A. C. 1Ionteil,h, I<leclrical Engineering, Voi. 57, A.I.E.E. Transactions, Vol. 50, September 1931, page 1113.
August 1938, pages 432-443. 11. T,ightning Investigation on Transmission Lines-II, W. w
7. Voltage-Recovery Characterist.ics of Distribution Systems, R. Lewis and C. M. Foust, A.I.E.E. Z’ransuclior~s, Vol. 50, Septem.
L. Witzke, A.I.E.E. Technical Pnpcr 49-53, 1949. : \ her 1931, pages 1139-1146.
8. Power System Transients Caused by Switching and Faults, by 12.,’ Ovcrvoltagcs on Transmission Lines Due to Ground Faults as
R. D. Evans, A. C. .\lontcith and R. I,. Witzke, Electrid Affected by Neutral Impedances. Engineering Report Xo. 30,
Engineering, Vol. 55, August, 1939, pages 350-394. Joint Subcommittee on Development and Research, Edison
9. Klydonograph Surge Investigations, by J. H. Cos, P. H. Elect,ric Institute and Bell Telephone System, November 15,
>TcAuley and L. G. Huggins, A.I.E.E. ‘I‘ransaclions, Vol. 46, 1934.
February 1927, pages 3 15-329. 13. Reactance or Resistance Grounding? R. L. Witzkc, E&tic
10. Lightning Investigation on the Appalachian Electric Power Light and Power, August 1939, pages 42-45.
CHAPTER 15

WAVE PROPAGATION ON TRANSMISSION LINES


Original Authors: Revised by:
C. F. Wagner and G. D. McCann C. F. Wagne--

I. SIMPLE WAVES
TRANSMISSION line can be regarded as made up

A of elements. If resistance is neglected, each element


consists of a shunt capacitance and a series induct-
:tnce as shown in Fig. 1. If a voltage is applied to one end
of such a line, the first capacitor becomes charged imme-
diately to the instantaneous applied voltage. However,

Fig. l-Transmission line broken up into small elements.

hecause of the first series inductor, the second capacitor


does not respond immediately but is delayed. Similarly,
the third capacitor is delayed-still more by the presence of
the second inductor. Thus the farther removed from the
end of the line the greater the delay. If the applied voltage
is in the form of a surge, starting from zero and returning
again to zero, it can be seen that the voltages on the inter-
mediate condensers rise to some maximum value and
return again to zero. The disturbance of the applied surge
is thus propagated along the line in the form of a wave.
1. Mechanical Analogy
It can be shown with mathematical rigor that for a
system of the kind just postulated (without series or shunt
resistances and zero ground resistivity) the wave will be
propagated along the line with undistorted or undimin-

Fig. 3-Illustrating wave form of the traveling wave in a


Fig. 2-Photograph of mechanical wave analogy. mechanical analogue for successive intervals of time.
523
524 Wace Propagation on Tranxmissio~nLinws Chapter 15

ished amplitude. The snmc phenomenon can be deman- Tn Fig. 4 is depicted the general properties of traveling
strntcd by nieans of a number of analogies. One which is waves just enunciated. Note that the positive sense of
particularly adapted to the present problem has been potential is taken with respect to ground as zero and that
developed by Wagner’ and is illustrated in Fig. 2. It con- the positive sense of current flow in the conductor is the
sists of a number of aluminum arms mounted side by side. same as the direction of propagation of the wave.
These arms are balanced about their center of rotation and
their axes of rotation are in the same straight line. The 3. Line Constants
onlv connection between adjacent arms is a flat spring, The inductance of a single conductor parallel to the
which offers a restraining torque when one arm is displaced earth, assuming an earth of zero resistivity, is
\vith respect to the next. The mass of the arm corresponds
to the inductance of the line and the spring to the capac- L = (2) (10-9) log, F in henries per cm. (3)
itance. Fig. 3 illustrates what happens in this device
\vhcn a disturbance is applied at one end. The wave moves =(7.410)(10-J) log10$ in henries per mile (4)
along the line with essentially undiminished amplitude and
and its capacitance
unchanged wave form.
c= lo-”
2. Current Wave, Surge Impedance and Surge Ad- in farads per cm. (5)
mittance 18 log, p
Knowing that the voltage surge moves along the line = (3.882) (10-E) .
and imparts charge to the capacitors at any particular m farads per mile. 6)
point o”ly for the duration of the wave at that location, one log,, F
can see that currents must flow in the connecting induct-
ances, but only for the interval during which the surge where h= height of conductor above ground
exists at that point. That is, a wave of current should r = radius of conductor in same units.
accompany the wave of voltage. It can be shown mathe- The foregoing expression for inductance assumes that
matically that the current wave will have exactly the same there is no flus within the conductor. This is the case for
wave form as the voltage and at any instant will be pro- surges of short duration, because the current flows in a
portional to the voltage. The constant of proportionality thin layer next to the surface-the phenomenon of “skin
is known as the surge impedance and is usually designated effect.” For this reason ferrous conductors can be treated
L as non-ferrous conductors in considering traveling waves.
by the symbol 2. It is equal to c where L is the in-
J Making the same assumptions for cables (that all the
ductance in henries per unit length of line and C is the current flows next to the return conductor) the inductance is
capacity in farads per unit length of line. The dimensions
of 2 are those of a resistance and its value is expressible in L= (7.410)(10e4) log102 in henries per mile. (7)
r1
ohms. Thus there exists the relation and the capacitance is

(1) C = (3’882)(10-8)k in farads per mile. (8)


where e = instantaneous voltage logm ;
i = instantaneous current. where rl= radius of conductor
The reciprocal of surge impedance is called the surge rq=inner radius of sheath
admittance and is usually designated by the symbol Y. Ic= permittivity
Thus 4. Evaluation of Surge Impedance
i= Ye (2) The surge impedance of a single aerial wire with ground
i _
return is
t (7.410) (10-9 log,, ;
e z I
z= J c=y
,,,,,,,,,,,,,,,,,, ,,, ,, , , ,,,,,,,,,, , (3.882) (IO-*)

r
= 138 log,, ‘+ ohms
The curve of Fig. -5 will assist in the ready evaluation of
this expression. In the absence of more definite informa-
tion a surge impedance of 500 ohms is usually assumed.
For cables
DIRECTION OF PROPAGATION 138
2 = 71E log,, z ohms (10)
Fig. a--Depicting a voltage wave and its associated current
wave together with the positive sense assumed. A good average value for this quantity is 50 ohms. .;:
Chapter 15 Wave Propagation on Transmission Lines 525

650 6. Mathematical Expression of Voltage and Cur-


rent Wave
625
Mathematically a traveling wave can be designated as
follows:
600
e =f(x - ut) (13)
m 575 where z is the distance measured along the line and c is
I
the velocity of propagation, With t fixed, plotting c as a
5
z 550
function of 2 gives the voltage distribution along the line
w at that instant. With x fised e gives the variation of the
g2 525
voltage with time at that point.
Similarly, the current wave is
ii!
I 500 . e j(x--vt)
w z=z=T
2 475
7. Waves in Reverse Direction
450 The same relations as mentioned above apply to a wave
traveling in the opposite direction when the positive sense
425 ’ of current is taken the same as the direction of propugn-
tion. This means that the positive sense of current would
400, 2 3 45 IO 20 30 40 50 be t.he reverse of the wave moving in the opposite direction.
zh For analytical work it is convenient that the positive sense
7 IN THOUSANDS OF UNITS
of both currents be the same. By arbitrarily reversing the
Fig. 5-Surge impedance of an aerial conductor. sign of one of the currents and making the corresponding

5. Velocity of Propagation DIRECTION OF DIRECTION OF


PROPAGATION PROPAGATION
The velocity of propagation of any electromagnetic
disturbance in air is the same as that of light, namely ‘OTAL AT A
‘ARTICULAR INSTANT
2.998 X lOLo cm. per sec. The only difference for trans-
mission lines is that the conductor provides a guide. In
terms of the constants of the line, this velocity is equal to
1
___ To verify the velocity relation, substitute (3) and
vm’
(5) into this expression giving
velocity = __ = ef er
dLz JGygq (11)

= 3 X lOlo cm per sec.


r --I+--
A convenient though approximate figure of 1000 ft per ef=zif e, 8-z i,
microsecond (a more exact value being 984 ft per micro-
second) is generally used in connection with line calcu- Fig. 6-Forward and backward voltage waves with their asso-
lations. ciated current waves and also the sum of the two.
Applying relation (11) to cables there results that
changes in the equations, this difficulty may be avoided.
velocity=&= (3) uw
- fi cm per sec. 02) Fig. 6 gives the conventions adopted for both types of
waves together with the equations relating the voltages
This likewise is a special case of a more general phenom- and currents. The waves moving from left to right are
enon, that the velocity of propagation of any disturbance designated by the subscript f suggestive of forward moving
in a medium of permittivity Ic varies inversely as the and the wave from right to left by the subscript r sug-
square root of the permittivity. Since the permittivity of gestive of a wave moving in the reverse direction or a
materials used in cables varies from absr,2.5 to 4.0, the reflected wave.
velocity of propagation of surges in cables) is about one-
third to one-half that of light. SimilarFa disturbance in 8. Principle of Superposition
a counterpoise buried in earth having a permittivity of When two waves of this character meet, they do not
1000 influence each other but seem to pass through each other.
say 6 propagates within the earth at a velocity of ---= or
r4 An illustration of this phenomenon is shown in Fig. 7 in
JO8 ft. per microsecond. i,L- -/?I sir, .u which two oppositely moving waves meet in the me-
*,,I. , ;*. -i J
Wave Propagation on Transmission Lines

II. POINTS OF DISCONTINUITY ,.p


Cl
When a simple voltage and current wave (er and if)
moves along a line and meets a point of discontinuity
reflections take place. If a resistor is connected across the
end of a line, the reflections from this point are relatively
simple to calculate but if the resistor is replaced by an
inductor or capacitor the solution becomes more compli-
cated. Some of the more usual cases will be analyzed in
detail.
9. Relations for Simple Reflections from the End
of the Line
In Fig. 8 let er and if be the instantaneous voltage and
current of the forward wave at the point of discontinuity.
These are usually the known quantities. Further, let e,
and i, be the instantaneous voltage and current of the re-
flected wave at the point of discontinuity, and e and i the
instantaneous voltage and current at the point of dis-
continuity. Thus
e=ef+e, (15)
i=if+i, (16)

From (17)
Zi=ef-e, (18)
Adding (15) and (18)
e+Zi=2ef (19)
This equation supplies a relation connecting e and i with
the instantaneous value of the oncoming wave. The
shunting network must supply another equation to pro-
vide the solution.

VOLTAGE AND CURRENT


AFOR-C’PWIRCUITED~ _ __ _

Fig. 7--Illustrating superposition of two waves upon each


other.
(a) Two positive waves. (b) One positive and one negative wave.

chanical analogy described previously. Upon meeting,


the instantaneous amplitudes of the two waves add to-
gether but, after passing through each other, remain un-
disturbed in magnitude and wave shape. Thus traveling
waves may be said to follow the laws of superposition. CURRENT AND VOLTAGE .::
Each component can be analyzed separately. The right FOR SHORT-CIRCUITED LINE ‘.“:‘.
.I 5
hand column of Fig. 6 shows how the two voltage and Fig. S-Reflection of waves from open-circuited and from
current waves add at a particular instant. short-circuited end of line.
Chapter 15 Wave Propagation on Transmission Lines 527

After e and i have been determined, e, can be obtained 11. Junction of Dissimilar Lines
by subtracting (18) from (15) giving Fig. 9 (a) illustrates the case in which the section to
er=i(e-Zi) cw the left of a represents a line whose surge impedance is 2
and the section to the right one whose surge impedance
An alternate form is obtained by inserting e from (19)
is 2’. Since the volt-ampere characteristics of a line are
into (20), giving the same as those of a resistance, the reflections resulting
e,=ef--2% (204 when a wave approaches the junction point from the left
10. Line Terminated by a Resistance - Open and are the same as though the line to the right of a were re-
Short-Circuited Line placed by a resistance equal to Z’, as shown in Fig. 9 (b).
When the line is terminated by a resistance R, then
e=Ri (21)
Combining this with (19)
7////////N////////////////////////////
2
(22) (a)
z=n+ge’

And from (20)


2R
e=n+p (23)
rk; ,,,,,,,,,,,,
rr
R-Z
(2‘4) (b)
er=Ezei
Fig. 9-Equivalent circuit of line terminating at (a) and con-
(a) Open-Circuited Line. If R= m, the condition tinued by a line of different surge impedance.
which corresponds to an open-circuited line, then
e,=ef (25) The instantaneous voltage, e, and the reflected wave at
Thus, the reflected wave is equal to the oncoming voltage the junction point can be computed by Eqs. (23) and
wave. Also (24), respectively. The voltage, e, thus gives the wave
e=2ef shape of the wave propagated out along the line to the
(26) right of a.
a relation which proves the well-known doubling up of a
voltage wave as it strikes the end of an open-circuited 12. Junction of Several Lines
line. Equating e, and et to their Zi equivalents from Fig. When a surge travels along line A of Fig. 10 and strikes
6 there is obtained the junction point of two or more other lines that are
i,= -if (27) separated a sufficient distance that mutual coupling be-
a relation that must be maintained since the currents at tween them is negligible, the reflections and transmitted
the end of an open line must be zero, that is, i=i,+if=O. voltages can be calculated by replacing the lines to the
The variations of the principle quantities at different in- right of the junction points by a shunt resistance as in
stants are illustrated in Fig. 8. Fig. 9 in which the resistance is equal to the parallel surge
(b) Short-Circuited Line. For the short-circuited con- impedance of all the lines to the right of a. Equal voltage
dition R of Eq. (24) is zero, for which waves are then propagated along lines B, C and D.
er= -ef (28) B

The reflected wave is the negative of the oncoming wave


at any instant and the sum of the waves, e, is equal to /
a
zero. On the other hand, inserting the Zi equivalents of e, A \ c
and er in (28), there results that
i,=if (29)
\ D
which shows that the total current doubles at the end of
the line. As shown in Fig. 8, the relations are the same Fig. lo-Junction of several lines.
as for the open-circuited line except that the voltages and
currents are interchanged. 13. Single Line Terminated by an Inductance
(c) R=Z. For th’IS case as can be seen from (24), e, is The schematic diagram for this case is shown in Fig. 11.
equal to zero and there is no reflected wave. Since the line From the terminating network there results that
has the same characteristic as that of a resistance it is
evident that electrically there is no discontinuity. The ,&c (39)
wave merely disappears as the end of the line is reached. dt
(d) Other Cases. For other cases the reflected wave Combining this with Eq. (19)
will be positive or negative depending upon the extent
2ef=Zi+L@ (31)
to which R is greater or less than 2. dt
528 Wave Propagation on Transmission Lines Chapter 15

It n-ill be observed that the solution of this equation is the From (19)
same as the case for which the voltage 2er is applied to a e=2ef-Zi (35)
resistance and inductance circuit in which the resistance which permits the determination of e since both ef and
i are now known. The reflected voltage wave can be de-

f i
Fig. ll-Line terminated by an inductance.

is Z and the inductance is L. The current depends upon


the character of the applied voltage.
If ef is a square-topped wave of magnitude E, i ap-
proachcs a magnitude of ‘+ along an esponential curve
L
whose time contant is -. The expression for this curve is
Z
Zt
i=-[1-e-”
2E

From (30)
1
Z
(32)

e 4-3 (33)
From (20), the reflected nave is

1 (34)
Fig. 13-Reflected wave and total voltage waves at successive
instants upon a line terminated by an inductance in response
to a square topped wave having a maximum value of E.

Fig. 12-Voltages and currents at the end of the line shown


in Fig. 11 in response to a square-top wave having a maximum
value of E.
1
Fig. 12 shows graphs of these curves and Fig. 13 successive
positions of the oncoming and reflected wave. It will be (a)
observed that the circuit acts like an open-circuited line
i-l +-
2et
initially but finally takes on the characteristics of a short- e
circuited line. The voltage starts at a value twice that of
the oncoming wave and finally reaches zero. The reflected I?\
wave starts at +E and gradually approaches -E.
If instead of a square-topped wave the oncoming wave
ef of Eq. (31) is of a generalized form, such as shown in
Fig. 14, the current response can be determined by the
follow-up method described in Part VI, Sec. 20 of
Chap. 6. Equation (31) characterizes the phenomenon
as one in which the instantaneous value of i tends to ap-
proach, along an exponential curve whose time constant
L
is 2, a value determined by the voltage at that instant (b)
divided by the surge impedance. Fig. 14 illustrates the Fig. 14-Graphical method of analyzing fine terminated b
graphical construction. an inductance.
Chapter 15 Wave Propagation on Transmission Lines 529

termined through the use of Eq. (20a). All of these quan-


tities are shown in Fig. 14. Fig. 15 illustrates the relative e=Jc iat
/
positions along the line of these waves at different instants. Substituting this expression for e into (19) there results
14. Single Line Terminated by a Capacitor that
Fig. 16 shows the schematic diagram for this case from 2ef=Zi+A i dt
which it may be seen that I
This is the well known equation representing the charging
of a capacitor through a resistance upon the application
of a voltage 2 et.
If er is a square-topped wave of magnitude E, i is equal
t0
2E -&
i=--e
z
From (19)
(37)
From (20a)
e,=ef--Zi=E[ 1-2e-‘] (3%
These quantities are plotted as a function of time in

Fig. 15-Relative positions of waves of Fig. 14 along line at


different instants.

Fig. 16-Line terminated by a capacitor.

Fig. ll-Reflected and total voltage waves upon a line termi-


e nated by a capacitor in response to a square-topped wave
having a maximum value (Eh

Fig. 17. Fig. 18 shows the position of the reflected wave


and the total voltage at different instants of time.
15. Special Case
A special case will be considered for which the voltage
across the terminal equipment is a non-linear function of
Fig. 17-Voltages and currents at the end of the line shown the current through it, such as for a lightning arrester.
in Fig. 16 in response to a square-top wave having a maximum In Fig. 19 let the heavy full line represent the volt-ampere
value of E. characteristic of the arrester and the dotted straight line
530 Wave Propagation on Transmission Lines Chapter I5

Zi, the surge impedance of the line times the current Adding (40) and (41)
through the arrester. From (19) 2ef=Zi+2e (42)
ef= +(e+Zi)
(39) The shunting network will provide another equation con-
netting e and i which in combination with Eq. (42) per-
This quant,ity is plotted also in Fig. 19. Since er is the
mits of the determination of e and i. Subtracting (40)
magnitude of the oncoming wave at any instant, then i
and (41)
er= --i
z
2 (43)
Note that the line to the right can be replaced by a re-
sistor 2 in shunt across the network at the junction point
as shown by the dotted line.
e As an illustration of this case let the network be a
resistor R. Then
e=Ri
and substituting in (42)
i
2er=Zi+2Ri
Fig. 19-Special case where voltage across terminal equip-
2
or (44)
ment is a known function of current through it. z = zfef
2R
and, consequently, e is known for any value of er and can e=Z+Ref

be plotted as a function of time. Similarly, from (20), e,


The transmitted wave is also equal to (45) and the re-
can also be plotted against i and is known in terms of
e and er. flected wave is from (43)

16. Network Connected in Shunt Across a Con- (46)


tinuous Line
The schematic diagram for this case is shown in Fig. III. LATTICE NETWORKS
20. Let a wave travel from the left and approach the
When the circuit consists of a number of shunt im-
network. As the network is reached a reflection will occur
pedances distributed along the line as in Fig. 21 (a), the
solution is expedited and simplified by means of the lattice
network by Bewley. While the system can be applied
generally, it will be discussed principally with regard to
shunt resistors.
e =ef+e,
17. Voltage Lattice Network
ef-zif
e,-- zi, If in Fig. 21(a) a traveling wave ef moves from the left
to right toward a then upon reaching a, a transmitted
I/ I wave and a reflected wave is produced. These waves
/////////////////////////////////////////////// can be expressed as follows
2ef =zi +2e
et = transmitted wave = aaef (47)
ers-hl Z.
e, = reflected wave = Aef (48)
Fig. 20-Network connected in shunt across a continuous line.
where LY*is the transmission coefficient which from (45)
is equal to
and a voltage e is built up across the network. A wave, 2R,
et is transmitted along the line to the right equal at any (49)
instant at the junction point to the voltage e. From the Z-l-‘.%
voltage conditions at the junction point and P3.is the reflection coefficient which from (46) is equal
to
ef+e,=e (40) Z
-- (50)
and from the current relations Z+2R,
if+i,=i+i, SO long as the line surge impedances are equal on both
sides of the resistor then the transmitted and reflected
or z-;=i+;
waves are independent of the direction from which the
wave propagates. If on the other hand the line is un-
=i+f. symmetrical with respect to the resistor this statement is
z untrue. Thus, if the line surge impedance to the left of
or ef-e,=Zi+e (41) the resistor is Z and to the right Z’, then for a wave mov-
Chapter 15 Wave Propagation on Transmission Lines 531

ing from the left hand side at the point a the transmission and the reflection coefficient, 6,, is
coefficient is 6 =RZ-RZ’-Z’Z
2RZ’ (514
(514 3 RZ’+RZ+Z’Z
ffa= RZf RZ’+ ZZ’
When the transmitted wxve from a reaches 0, another
and the reflection coefficient is reflection and partial transmission occurs. The reflected
RZ’- RZ - ZZ’ wave from b is partially transmitted and reflected from 0.
(51b) This continues indefinitely throughout the network until
On= IZZ+RZ’+ZZ’ the components have been reduced to zero. By means of
For a wave moving from the right to the left the trans- the system’ shown in Fig. 21 (b) account can be kept of
mission coefficient, Ye, is each component not only in magnitude but in time. The
2RZ horizontal distance represents length along the line and
(51c) the vertical distance time. The inclined lines arc so sloped
‘“=RZ’+RZ+ZZ’ that the vertical distance represents the time required for
the original wave or a reflected component to reach the
point designated. Let zero time be the instant at which
the traveling wave ef leaves 0. >-it, time t1 this wave has
reached a. The reflected wave from this point is B,,efwhich
is sloped the opposite direction and is thus indicative of
motion in the reverse direction. The transmitted wave
from a, cy, ef reaches b at time t2 when a reflection Ph a;, ef
occurs and the wave 0!ybN, ef is transmitted beyond this
point. This latter wave reaches c at the time t3. Each
wave whether it be transmitted or reflected has its own
transmitted and reflected components. Where two naves
coincide as at b for time t5 where xaves from a and c arrive
at the same time, the reflected and transmitted waves
from this point are added, as has been done for the nave
between b and a between tg and t6.
To determine the actual voltage at any point such as
X it is necessary to add the different components with
their proper time relations as is shown in Fig. 21 (c). The
method is much simpler than this description might con-
vey as numerical values simplify very greatly the appear-
ance of the steps. In most cases the resistors are equal and
equally spaced. If the voltage at any of the resistors is
desired, the components of voltage on either one side or the
other should be added not the components on both sides.
18. Current Lattice Network
So far consideration has been given only to the voltage
waves in lattice networks. The currents can be obtained
from the voltage components by merely dividing those
(b) that move from left to right by the proper line surge im-
pedance Z and those that move from right to left by the
corresponding--Z. The sign is determined simply by the
direction of downward slope of the lines in Fig. 21(b).
However, instead of using the voltage waves as a basis for
the lattice network, the current waves can be used with
equal facility. A similar set of equations employing trans-
mission and reflection coefficients relates the transmitted
and reflected waves to the oncoming wave approaching the
discontinuity.
COMPONENTS
For waves, If, moving from left to right
(C) it = transmitted current wave = asir (52)
Fig. 21-Lattice network. i, = reflected current wave = - @.z’t (53)
(a) Equivalent circuit of line with several shunt impedances at dis- For waves, If, moving from right to left
tributed points. (b) Lattice network for voltages on above circuit.
it = y.ir (54)
(c) Addition of components from lattice network to give actual volt-
age at a given point. i, = - &jr (55)
532 Wave Propagation on Transmission fines Chapter 15

For these equations the transmission and reflection co- These relations for a pair of forward moving waves is
efficients are identical to those used for the voltages in given by Eqs. (57) and (58) of Fig. 22. The voltages are
the voltage lattice network for either the simple condition measured with respect to ground as zero potential and
of uniform line surge impedance 2 (see equations 49 and the positive sense of current flow is taken as from left to
50) or for the more general case of different surge impe- right. The corresponding relations for a reverse moving
dances on each side of the point of discontinuity (see equa- pair is given by Eqs. (59) and (60). The coefficients in
tions 51 (a) to 5 1 (d)). The negative signs in equations (53) these equations are called self and mutual surge imped-
and (55) for the reflected waves are due to difference in ances.
polarity relations between the current waves and their cor- The converse relations for currents in terms of voltages
responding voltage waves for surges propagating in the are given by equations (61) to (64) in which the coefficients
two directions. are called the self and mutual surge admittances. Equa-
In accordance with Kirchoff’s law, the current flowing tions (65) to (67) give the admittances in terms of the
in any of the shunt resistors is equal to the algebraic sum surge impedances.
of the current waves moving into and out of the point. For cases in which these components only are involved
Where the line surge impedance Z is the same on both the total voltages and currents in the two conductors are
sides of the resistor, the resistor current can be given in given by Eqs. (68) to (80).
terms only of the summation of the incoming waves from Where more than two conductors are involved these
both left and right by the following equation equations may be generalized quite readily by the addition
r)D - .&Lb
of other terms. Thus, for three conductors Eqs. (57) and
resistor) = Z?? z ’ if 56(a) (58) would be extended by the addition of a third term
?
involving the current in the third conductor with a co-
In summing the different components they must be added efficient equal to the mutual surge impedance. In addition
with the proper time displacement between them. a third equation would be introduced for ef3. Similar addi-
tions would be incorporated throughout the system of
IV. MUTUALLY COUPLED CIRCUITS equations.
19. Voltages and Currents for Two Parallel Con- 20. Self and Mutual Surge Impedances
ductors For most traveling waves the current flows near the
Just as the steady-state voltage and current relations surface of the conductor which permits neglecting the
between two coupled electromagnetically or two electro- flux inside. In addition the earth can in nearly all cases
statically coupled circuits can be expressed in terms of be regarded as having perfect conductivity. For these
two simple linear equations so also can the relations be- assumptions the self and mutual impedances in terms of
tween voltages and currents associated with traveling the nomenclature illustrated in Fig. 23 are
Ivaves in two parallel conductors be similarly expressed.
ZU = 138 log10 ‘+ ohms
FORWARD COMPONENTS REVERSE COMPONENTS

-c DIRECTION OF cf DIRECTION OF 213= Zzl = 138 log,, i ohms


PROPOGATION PROPOGATION

IO >

20

er1 =Zliifl+Zl& (57) (59)


CfZ=Z,2ir,fZ& (58) (60)
Alternate Form
ifI = Y,,efl+ YO~B (61) irl = - Yllerl - Y12er2 (63)
if2 = Y,,ert + Y2sf2 (62) irz = - Ydh - Yz2efl (64)
in which
Y,, = -7 Z?2 (65)
z,,z,?-&g
Zll
Y*? =
ZL1.G -z,:
(66)

(67)
for total quantities
(68)
(69)
(70)
(80)
Fig. 22-Analytic representation of voltage and current waves
on mutually-coupled circuits. Fig. 23--Two parallel conductors with their images. ’
Chapter 15 Wave Propagation on Transmission Lines 533

21. Several Conductors in Parallel It can be seen that the only effect of the presence of the
There are certain practical cases where surges are in- grounded conductor is to reduce the effective surge im-
troduced simultaneously on several conductors in parallel pedance of the ungrounded conductor.
and sufficient symmetry esists that it can be assumed that
t,he voltage and currents are equal on each of them. For 23. Reflected and Transmitted Waves When One
these assumptions an equivalent surge impedance can be Conductor Is of Finite Length and Open Cir-
(letermined which enables the treatment of the conductors cuited
as a single equivalent conductor. This case is illustrated in Fig. 25. Let it be assumed that
For two conductors if the voltage, e, of the single the forward moving waves erl and efz are known and it is
equivalent conductor is taken as the mean of el and ez and desired to determine their associated currents, the voltages
by assumption il and iz are equal to 5 where i is the total
I
current, then from equations (57) and (58) I
irl=+fe ~rl*OJ
elfed I,
e=--=~(Zll+2Z12+Z22)i
n
L q
Therefore, the equivalent surge impedance is I
z,, = +&+2;512+222) CONDUCTOR-l
’ (83)
Upon substituting (81) and (82) this becomes

from which it can be seen that the two conductors can be


replaced by a single conductor whose radius is i/rlrza2
and height above ground is WY-. For most cases
the height can be taken as the arithmetic mean of the
two conductors and when they have equal radii
(hl+hz) Fig. 25-Reflected and transmitted waves when one conductor
Z,, = 138 log,, p
dar is of finite length and open circuited.

22. Wave on One Conductor with the Other


and currents that will be reflected backward n-hen the
Grounded
point corresponding to the end of the one line is reached,
In order to clarify some of the physical concepts in- and the voltage and current transmitted beyond this point
volved several specific cases will be considered. The first on conductor number 1. These quantities constitute the
of these is sholvn in Fig. 24, in which a voltage wave is eight unknowns ifl, if?, e,l, ers, irl, irz, et1 and itl. The
eight equations required for their solutions are Eqs. (57)
to (60) of Fig. 22 and the four following which apply at the
point of discontinuity:
efl+erl=etl (88)
et1 = Z& (89)
ifl+i,l= it1 (90)
irz+i,z = 0 (91)

irl and if2 can be determined from Eqs. (57) and (58) and
then from Eq. (91) ir2 is known. By the combination of
Fig. 24-Voltage and current relations for voltage applied to Eqs. (88), (89), and (90)
one conductor with other conductor grounded.
eflfed =.G(if~+i,J
applied to conductor number 1 and conductor number 2
is grounded. Substituting the condition into Eq. (58) Substituting in this equation the values of en and erl
as given by Eqs. (57) and (59) there results
that ef2 is always zero, then
212 Zl2if2 - 2Zllir1 - Z12ir2= 0
if?, = - -2f1 (86)
222 which gives the equation for irl when the value of i,z
Substituting this value into (57) given by Eq. (91) is substituted
z:, Zt*Z22 -2%
efl = Zllifl - --tfI
222
=
222 -zfl
(87) (92)
534 Wave Propagation on Transmission Lines Chapter 15

Substituting the values of i,l and i,~ given by Eqs. for the currents can be determined from the voltages by
(91) and (92) into Eq. (59) the equations given in Fig. 22.
212
e,l=

erl=O
-2~

(93)
( ) -
Zll
zf2--&2(-if2)
25. Conditions at the Beginning of a Parallel
This case is illustrated in Fig. 27, and the point of dis
continuity A will be discussed first. As in all the cases
Thus there is no reflected voltage wave on conductor just considered, the original waves are regarded as ap
number 1 and the voltage en is transmitted undistorted
past the point of discontinuity. i+,=o
Making similar substitutions in Eq. (60)
212. I------Y ett=z++,
er2 = -Z12
( > -212
%I1
-Z22( -if21 I
I
ICONDUCTOR-
I
I I
(94) I I
ef, et,
From Eqs. (62), (66), and (67) ifl=z -it,=%
212 Z,, CONDUCTOR-I
If2 = - Z,J,, - z,: en+ z,,z,2 -Z1:ef3

and substituting this value of if2 into Eq. (94)


z12
er2 = -zTlefl+ef2 (95)
A 0
The total voltage at the end of conductor number 2 is Fig. 27-Conditions at the beginning of a parallel.
ZP
e2=ef2+er2= ---efl+2ef2
Zl,
proaching the point of discontinuity from the left-hand
side. The reverse or backward moving waves of current
24. Reflected and Transmitted Waves When Con- and voltage to the right of A must therefore be equal to
ductor of Finite Length Is Grounded zero. Since no current can flow to the left of A, then the
transmitted current wave in conductor number 2 must at
For this case, which is illustrated in Fig. 26, the four all times be equal to zero. The only current present to
additional equations to be used with Eqs. (57) to (60) the right of A is the transmitted current wave in conduc-
are the following: tor number 1. The presence of conductor number 2 can-
efl+e,l= et1 (97) not affect either the current or voltage in conductor
etl=&itl (98) number 1. Similarly, when considering the discontinuity
ifl+i,l =it1 (99) at B, it follows that since the approaching current wave in
Ot er2= -ef2
ef2+e,2 (100) = conductor number 2 is zero then following the same
reasoning as for A, the current in the conductor to the
These eight equations can be solved for the eight un- right of B must be zero and conductor number 2 can have
knowns with the results given in Fig. 26. The relations no effect upon conductor number 1.
The transmitted and reflected waves in conductor
number 1 can be calculated by neglecting the presence-of
conductor number 2.
26. Coupling Factor
In any case such as Fig. 27 in which the current in one
conductor, such as number 2, is zero, the voltages are
from Eqs. (57) and (58)
et1=.&&I
%2 I h=-ef, et2 = Z2it,

; &2

-=I
and
et2=Zllet1
,I
CONDUCTOR-2 Thus for this condition the voltage induced on con-4
ductbr number 2 is related to that on conductor number 14
by the term g. This is commonly called the couplingi
factor and will te denoted by the symbol ‘iI
7//////17////////////////////////(///////~///~/~~
Fig. 26-Reflected and transmitted waves when conductor of K12 zz$ (102
finite length is grounded. 11
Chapter 15 Wave Propagation on Transmission Lines

The coupling factor can be written in terms of the phys- GROUND


ical constants of the conductors shown in Fig. 23, by the
use of Eqs. (81) and (82)
logi
K,*=- (103)
log 2
As will be shown subsequently, the coupling factor is
of importance in calculating the voltages induced in con-
ductors parallel to those struck directly by lightning.
Values of the coupling factor between phase wire and
ground wire for lines with one ground wire are given in
the curves of Fig. 28 for a practical range of transmission
line construction. For estimating purposes a value of
0.25 can be used. In Fig. 28 the coupling factor is plotted
as a function of the spacing (a) between the ground wire
and conductor for various ground wire heights (h). As
shown by Eq. (103) it is also a function of the dimension
(b) of Fig. 23 which is defined not only by (h) and (a)
but by the angular position of the conductor relative
to the ground wire and the vertical. However this angu-
lar position has little effect and the curves of Fig. 28 give
the coupling factor to within about three percent for
practical conductor positions. In addition the curves ap-
ply to a fixed ground wire diameter of 4 inch. The prac-
tical range of ground wire sizes is from $ to 2 inches and
for this range the use of $ inch gives a maximum error of I /
only five percent. X-d

Coupling Factor Between Conductor and Two Fig. 29-Configuration for two ground wires and a conductor.
Ground Wires. If lightning strikes one conductor of
a double ground wire system at midspan without flash- both ground wires are immediately involved. For cases
over, coupling factors between the ground wire system in which both ground wires are involved the voltages
and phase conductors can be computed on the basis of and currents because of the usual symmetrical arrange-
involvement of one ground wire only as no current will ment will be equal on the two ground wires. In Fig. 29
flow in the other ground wire. This condition applies let the quantities referring to the ground wires be desig-
until the disturbance on the ground wire propagates to nated by the subscripts 1 and 2 and those on the con-
B point in the system such as a tower at which metallic ductor by the subscript a. The voltage induced on the
connection is made between the two ground wires. If conductor is given bv
on t,he other hand the lightning strikes a tower top, then cz1*+z2,> .
e, = Z~~il+Z2~i2=
2
GROUND WIRE = l/2” DIA. where
0.50
4 il = if = z
t \ 2
0
h therefore, the equivalent mutual impedance is
zh+z2&
74neq= ___I
2
which from Eqs. (81) and (82) is
v’b,bz
z meq= 138 log,,
= (104)
-\/ala2
The two ground wires can be replaced by a single equiv-
alent ground wire whose spacings are shown in Fig. 29.
The coupling factor can then be written, by combining
Eqs.
- (85) and (104), as -
log+!? logb”9
DISTANCE (0) IN FEET K= d/ala2
=- aep (105)
Fi% 28-Couplink factors between conductor and one ground
wire l/z inch in diameter.
536 Wave Propagation on Transmission Lines

ductor with respect to the ground wires. Ground wire


diameter has little effect upon coupling factor for values
betn-een 2 and 2 inches.
0.6
V. ATTENUATION AND DISTORTION
Aside from the effects of reflections at transition points,
traveling waves are both attcnuatcd and distorted as they
propagate along a line. This is caused primarily by losses
in the energy of the wave due to rcsistancc, leakage, di-
electric and corona loss. For sufficiently high voltages
corona is the most important factor and due to it waves
are attenuated within a few miles to a safe voltage.
The nature of the distortion produced is shown in the
oscillograms of Fig. 31 which are typical of the results
obtained by several studies made with artificial surges on
0 .2 transmission lines 3-1o. Examination of these oscillograms
shows that both the front and tail of the wave are sloped
I I I I I I 4=75-.
off by propagation.
Any of the possible types of losses will produce this ef-
0.1
fect. rlbove corona voltage, however, effects become much
more pronounced.
27. Effect of Series Resistance
OO IO 20 30 40 50
DISTANCE m IN FEET For the special case of the so-called “distortionless line”
(a) R
---= (: (106)
LCO
““I where R is the series resistance and C; the shunt conduc-
tance per unit length of line. For such a line, surges are
attenuated without distortion. The attenuation in a dis-
-$z
tance 2 is equal to E , which expresses the fraction to
0 .s
which the wave is reduced. The unit of x is dependent
solely upon the unit used in expressing R.
In actual transmission lines the shunt conductance is
so low as to be negligible and the condition expressed
.4 by Eq. (106) is not satisfied. Thus in actual lines a surge
is not only attenuated but also distorted. If, however,
the distortion is neglected and the attenuation is derived
.3 on the basis of energy loss alone 12, a factor equal to
-E,
B *’ is obtained. Assuming a 0000 copper conductor of
surge impedance 500 ohms and d-c resistance of 0.302
.2 ohms per mile, the surge must travel 2300 miles to attenu-
ate to one-half value. Of course, the resistance of the
conductor under surge conditions, due to crowding of the
0 .I current toward the surface, is much greater than that of
the d-c value. To form some idea as to the order of mag- c
nitude of this effect, the resistance of the conductor at a
0 frequency of 1 000 000 cycles can be calculated. At this
IO 20 30 40 50
frequency the resistance is 18 times the d-c value and
DISTANCE me IN FEET
assuming a resistance to surges of this magnitude it is
(b) found that the surge must travel 130 miles to attenuate
Fig. 30-Coupling factors for two ground wires of ?&inch to one-half value. In general it may be concluded that the
diameter. attenuation due to resistance is negligible as compared to
other factors, such as corona.
Fig. 30 gives values of this factor for practical ranges of A more accurate indication of the resistance of a con-
ground wire and conductor configurations for ground ductor under surge conditions is provided by Miller.13 If a
wires of $ inch diameter. Calculations indicate that for square-front wave is applied to a conductor, all of the cur’
practical configurations these curves are accurate to within rent initially crowds toward the periphery. The current
about five percent regardless of the position of the con- density then “soaks” into the interior with a diffusion
Chapter 15 Wave Propagation on Transmission Lines 537

,zri I I I
I- %I-/-il
v) 1I I
30w- I I I
s i-5
53
b-a
2 a4
23
5 p3
a
k $2
gL
l-a
2s’
“0
1.0 0.0 0.6 0.4 0.2 0 0.2 0.4 0.6 0.0 1.0
RADIAL DISTANCE
Fig. 32-Transient current distribution in solid rod.

“velocity,” h, given by

MICROSECONDS -t in cm. per sec.%


h= (!OTj
d 47V
INITIAL WAVE, 1 where p = Specific resistivity.
P = Magnetic permeability.
600 For copper h is 11.6 cm per sec.%; for aluminum 14.5; and
for steel, if P is assumed to be 1000, h is 1.9 cm per sec.%.
For a solid round conductor, it is convenient to espress
the results in terms of a numeric given by the relation

where t is time in seconds and b is the radius of the con-


ductor in cm.
The current distribution within the conductor is shown
in Fig. 32. With increasing time the current first crowds
MICROSECONDS
toward the periphery at zero time and then penetrates the
(a)
DOTTED CURVES OSCILLOGRAMS BY BRUNE 8. EATON(~
SOLID CURVES CALCULATED BY SKILLING EL DYKES’*‘l

MldROSECONDS
(b)
DOTTED CURVE OSCILLOGRAM BY CONWELL 8 FORTESCUE’e)
SOLID CURVE CALCULATED BY SKILLING 8 DYKES (“I I
Fi% 31-Oscillograms of artificial surges showing attenuation Fig. 33-Ratios of effective resistance to d-c resistance for a
and distortion. solid round conductor.
538 Wave Propagation on Transmission Lines Chapter 15

interior until at long times it is uniformly distributed over Foust and Menger formula in the high voltage range. For-
the cross section. mulae of this type do not take into account the various
Let K define the ratio of the instantaneous resistance to important fact,ors controlling attenuation and serve only 1
the d-c resistance, and K,, the average of K up to the time to indicate its ardor of magnitude. Since the effect of dis
t. Values of these quantities are given in Fig. 33. As a tortion is not considered, the curves of Fig. 34 can be used
numerical example of the use of Fig. 33, suppose a constant for estimating purposes to determine the attenuation of
current suddenly is applied to a solid copper rod 3 inch the crest in a given distance for a surge of a given initial
2.54 crest voltage by using the point on the curve corresponding
in diameter, for which b is then -= 2x2 0.635 cm. The
to the initial voltage as a reference point. For example
values of t, K and K,, for various times is given by Table 1. examination of the mean curve of Fig. 34 indicates that a
2 000 kv surge will be attenuated to 750 kv in 6 miles and
TABLE ~-VALUES OF < K, AND K,, FOR DIFFERENT TIMES a 1000 kv surge to 750 kv in 2.5 miles.
Since at the higher voltages corona is the most important
t IO-’ 10-e 10-b 10-4 factor, the effects of wave shape, polarity, and line con-
I 3.35x10-6 3.35x10-4 3.35s10-3 3.35x10-* struction on attenuation can be explained on the basis of
K 36 12 3.6 1.4
22 T.0
their effect upon corona. Thus surges on large conductors
K,” 70 2.5
should be attenuated more slowly than on small conduc-
These values give upper limits. For other than abrupt waves the tors. Likewise positive surges should be attenuated more
effective resistance is smaller. rapidly than negative ones since corona loss is greater for
positive waves.
28. Empirical Data on Attenuation The effect of some of the more important factors are
Studies made by several investigators with klydono- shown by the curves of Fig. 35 obtained from studies with
graphs have yielded data on the attenuation of the crest artificial surges. The curves give the effect of polarity
magnitude of voltage waves due to lightning’4-1*. An and wave shape showing that short surges are attenuated
empirical formula has been developed by Foust and more rapidly than long ones. Surges of the same voltage
IIenge+’ to fit such data. This formula, which assumes propagating on more than one conductor are shown to be
that the loss in the wave is proportional to the third attenuated less than a surge on only one conductor.
power of the voltage, is shown in Fig. 34. Its absolute Ground wires appear to have slight effect on attenua-
value depends upon the arbitrary constant K. In Fig. 34 tion. Brune and Eaton9 found that at high voltages
are plotted curves from this formula which represent the ground wires increased the attenuation slightly but at
envelope of all available field data and a curve which rep- lower voltages decreased it. This appeared to be true for
resents a common mean. Other empirical formulae have both polarities. McEachron, Hemstreet, and Rudgeq
also been developed2,20which correspond (with the proper however, found that positive surges were not affected by
choice of the arbitrary constants) fairly closely to the the presence of a ground wire while negative surges were
attenuated less.
In using the data of Fig. 34, the evidence indicates that
the information from sharp chopped waves lay closer to
the dotted curves and that information from slower waves
lay closer to the dashed curve.
29. Corona
e,- INITIAL VOLTAGE IN KILOVOLTS.
Attempts have been made to obtain analytical expres-
S- OlSTANCE OF TRAVEL IN MILES. sions for the effect of corona on distortion20,22. The best
picture of the mechanism of corona power loss at the
present time seems to be the following as given by Skilling
and DykesP : “There is a critical electric gradient for air
that cannot be exceeded. Any attempt to increase it
results in profuse ionization of the air, and the charges c
liberated by ionization take up such positions in space
that the gradient does not exceed this value.
“Shortly after its formation space charge becomes rela-
tively immobile, probably due to the formation of rela-
tively heavy ions whose mobility is ‘almost negligible
compared to electrons.
“The supply of space charge to the region about a con-
---_ --- ductor increases as long as the voltage increases and
-- - ---- ___ mm- -_- ___ _-- energy must be supplied for their formation from the ‘’
00 4 6 I2 $-:.*
h
16 20 24 conductor.
DISTANCE IN MILES “After the crest of a voltage wave is reached and begins
Fig. 34-Foust and Menger formula for determination of to decrease, the space charge remains practically constant
attenuation of crest magnitudes of voltage waves. in magnitude and position. During this time there is little
Chapter 15 Wave Propagation on Transmission Lines

ON ONE CONDUCT&
800

sa 400 3 MICROSECOND
I I
FRONT

SURGE ON THREE CONDUCTORS


\ - NEGATIVE SURGE t-l
/POSITIVE, e =574 Kb z400 ,\ --- POSITIVE SURGE
I I I \
3 MICROSECOND FRONT
1 1 , , , , SURGE ON BOTTOM 8.
4 a 12 16 20 4oo
MIDDLE CONDUCTORS
-- I / I /
MILES OF TRAVEL
-, I I
r ,

PPED SURGE ON ONE CONDUCT


-NEGATIVE SURGE

SURGE ON ALL
HREE CONDUCTORS

z
200 2400

1 FRONT r---j
-----kiREE CONDUCTORS/ 1 1
400 600 a00 1000 “0 I OO
I I ” 1 I I,

ORIGINAL CREST KV I 2 3 4 5 6 4 a 12 16 20
MILES MILES
(0) FROM CONWELL Et FORTESCUE”’ (bl FROM MCEACHRON, HEMSTREET 8 RUDGE”’ (~1 FROM BRUNE R EATON”’

Fig. 35-Effect of the more important factors on attenuation.


(a) Effect of polarity and wave length. (b) Effect of propagation on more than one conductor. (c) Effect of polarity and propagation
on more than one conductor.

loss in energy from the conductor, what there is being due With analytical expressions for the initial surge voltage
to diffusion of ions in the electric field at a slow rate.” as given by the following
Skilling and Dykes. 22 have developed an analytical e =f0(0 (111)
method of determining the distortion which is produced or t = K(e) (112)
hy conversion of a portion of the energy of the wave into
corona loss as the voltage rises to crest value. This de- The equations which they developed for the correspond-
creases the net stored energy of the wave. Line loss is ing quantities after the wave has propagated a distance
neglected after the voltage crest is reached. Distortion x are
of the tail is not considered, and it is assumed that the K(e-eo)+nCe
crest of the wave is moved along the original tail. Exam-
X (113)
n&e
ination of oscillograms showing corona distortion such as
x
those of Fig. 31 indicate that this is a good assumption. x+; (114)
‘The equation which they use for the energy per unit length
ot’ the wave is the following where
t= time in seconds
Energy = $9 e=voltage in volts
(109) e. = corona starting voltage in volts (crest)
v=velocity of propagation of the wave in feet per
\‘hich neglects distortion and the formation of space second.
charge. The quadratic formula for corona loss per unit =9.84x lo*
length is used in the form C = capacitance of line in farads per foot
2 = distance of travel in feet
Loss=X(e-e# (110) K=the constant of Eq. (110) which relates crest
voltage in volts to energy loss. in joules per foot
where e. is the critical corona voltage and K and 72are per half cycle, and which may be found from
empirical constants which will be discussed later. This Peek’s quadratic law or otherwise. It is equal to
type of expression for power frequency corona 10~33 was Peek’s constant (which is expressed in kilowatts
developed by Peek. per kilovolt per mile) multiplied by
540 Wave Propagation on Transmission Lines

t MICROSECOND 6 MICROSECOND IO MICROSECOND


I
FRONT
I
FRONT
I
FRONT x. In this manner the front of the i!
distorted wave-can be plotted. The crest of the wave is ;
determined by plotting the distorted wave on the same i:
figure with the initial wave, starting both at the same
point. The crest is the point of intersection of the distorted
front with the tail of the initial wave.
A comparison of calculations of distortion using this
formula with oscillograms of actual cases is shown in Fig.
31 where the solid curve expresses waves calculated by
Skilling and Dykes. As seen by these curves the calcu-
lated results conform closely to the oscillogrnms above
the critical voltage except at the crest of the wave.
In order to obtain a better idea of the effect of corona
in sloping off the front of voltages high enough to be of
importance from an insulation standpoint calculations
were made of the distortion of waves of different fronts
and magnitudes after traveling different distances. These
are shown in Fig. 36.

VI. 60-CYCLE STEADY-STATE PERFORMANCE


Misunderstanding sometimes occurs in the application
of wave theory to the steady-state 60-cycle operation of
transmission lines. This occurs particularly with regard to
the no-load condition. The question is frequently asked,
5 IO IS 6 IO I6 0 5 IO I5 20 “Since it is known that the waves travel with the speed of
TIME IN MICROSECONDS
light, should there not be a phase-angle displacement be
Fig. 36-Effect of corona in sloping the front of negative- tween the two ends of the line equivalent to the time
voltage waves of different fronts and magnitudes. required for the wave to travel the length of the line?”
Actually, of course, at no load the phase displacement is
103 very low and if the resistance is equal to zero the phase
= 1.895X 10-7 . For high voltage
5280 x 106 angle is also zero. This difficulty is resolved when the re
transmission lines K is 0; the order of 4X 10-12. flections are taken into consideration. To clarify this
Skilling and Dykes describe the constant R as follows: situation, consideration will be given to some simple 60-
“The factor n is a more or less constant factor which is cycle conditions as applied to a resistanceless line.
needed to account for three differences between the corona As was shown in Section 10 of this chapter, if a resist- :
of traveling waves and corona at power frequency. These ante, equal to the surge impedance, is connected in shunt
are (1) the effect of mobility of charge (2) the fact that across the receiving end of a resistanceless line and a surge
when voltage is alternating there is a space charge left is impressed upon the line, no reflections occur at the re-
over from one-half cycle to the next, and (3) the difference ceiving end. Under these same line conditions, if a 60-cycle ”
between positive and negative corona.” voltage is impressed across the sending end, waves of volt-
They found that good results could be obtained if age propagate along the line and no reflections occur. Since
n= 23 for positive waves and n=4 for negative waves. waves travel with the speed of light, 186 000 miles Per
Eq. (114) is more convenient for an actual calculation. second, then a full wave or 360 degrees phase displacement
This equation shows that at a distance z for every value 186 000 c
occurs on a ~ or 31OO-mile line. The phase dis-
of e on the front of the original wave there is a new value 60
of t. If there were no distortion this would be the original
placement for a 300-mile line is $+$ 360 or 34.8 degrees
value PO(e) from Eq. (112) plus 4 the term which repre-
V and the voltages at the two ends are equal in magnitudes
sents the time for the wave to travel the distance 2. The
The amount of power absorbed in the re
x describes the distortion of the wave
three-phase basis, where E is the line-to-li
produced by corona. It is not necessary to know the ana- be transmitted an indefinitely long distant
lytical expression for the initial wave. The wave can be voltage all along the line. At this load
plotted graphically and successive values of voltage se- charging kva just equals the inductive reactiv
lected on the front of the wave with their corresponding inductance. This particular load is called the “sur
times. To obtain the time it takes the voltage to rise from pedance load.” If the resistance, which m
zero to this same value after the wave has traveled the acterized as a “dead” load is replaced by
distance x it is merely necessary to add to the initial time equipment, other factors enter which lim
Chapter 15 Wave Propagation on Transmission fines 541

E,a ESI 300 MILES REFERENCES


OPEN
1. Nechanical Demonstrator of Traveling Waves, by C. F. m-&g-
ner, Electrical Erkgineerirkg, October, 1939, page 413.
r-O Traveling Waves on Transmission Systems, by L. V. Bewlcy
(a book), John Wiley and Sons.
Theoretical and Field Investigations of Lightning, by C. L.
Fortescue, A. 1,. Atherton, and J. H. Cos, A.I.E.E. Tramtrc-
tions, Volume 48, 1929, page 449 (395).
4. Cathode Ray Oscillograph Study of Artificial Surges on the
Turner Falls Transmission Line, by IX. B. McEachron and V. E.
Goodwin, A.I.E.E. Transactions, 1929, Volume 48, page 475
(475).
5. Study of the Effect of Short Lengths of Cable on Traveling
Waves. bv K. B. NcEachron, .J. G. Hemstrcct, and H. P. Seelye,
Volume 49, 1930, pagc 1432 (527).
A.I.E.E.-Transactions,
6. Traveling Waves on Transmission Lines with Artificial Light-
ning, by K. B. ALcEachron, J. G. Hemstrcet, and W. J. nudge,
G. E. Review, April, 1930, page 254 (722).
7. Symposium on Lightning, by J. II. Cox and Edward Beck.
A.Z.E.E. Transaclions, Volume 49, 1930, page 857 (T32).
8. Lightning Laboratory at Stillwater, New Jersey, by R. S. Con-
well and C. L. Fortescue, A.I.E.E. Transacfions, Volume 49,
1930, page 872 (746).
9. Experimental Studies in the Propagation of Lightning Surges
on Transmission Lines, by 0. Brunt and J. R. Eaton, A.I.E.E.
Transactions, Volume 50, 1931, page 1132 (813).
10. Attenuation and Successive Reflections of Traveling Waves, b>
E, (TOTAL)
J. C. Dowell, A.Z.E.E. Transaclions, Volume 50, 1931, page 551
(cl VOLTAGE AT SENDING END (855).
Electric Circuit Theory arkd Operational Calculus (a book), John
R. Carson, McGraw-Hill Book Company.
Elektrische Schaltvorgange, by R. Rudenberg (a book), Julius
E, (TOTAL) Springer, Berlin.
13. Diffusion of Electric Current Into Rods, Tubes and Flat Pur-
(d) VOLTAGE AT RECEIVING END
faces, by K. W. Miller, A.Z.E.E. Transacliorks, Volume 66, 11147,
Fig. 37--Steady-state analysis by means of wave theory of an page’1496.
open-circuited resistanceless line 300 miles in length. 14. Lightning Investigation on the Ohio Power Co.‘s 132-kv Systrm
-1930, by Philip Sporn and W. L. Lloyd, Jr., A.I.E.E. TTWLS-
power that can be transmitted. For detailed consideration actions, Volume 50, 1931, page 1111 (659).
of these factors see the chapter on System Stability. 15. Lightning Investigation on the 220-kv System of the Penn.
Now ret,urning to the open circuit, let the voltage whose Power&Light Co. 1930, by Edgar Bell and A. L. Price, A.I.E.E.
vector (or phasor) value is indicated by E,l of Fig. 37 be 16. Transactions, Volume 50, 1931, page 1101 (691).
Lightning Investigation on 220-kv System of the Penn. Powrt
impressed across the sending end of a 300-mile line. At a
and Light Co. 1928-1929, by N. X. Smcloff and A. L. Pricct,
I,irne later represented by the time required for the wave A.I.E.E. Transactions, Volume 49, 1930, page 895 (712).
1.0traverse the line (34.8 deg.) the wave, Erl, reaches the 17 Lightning Investigation on the Appalachian Electric Power Co’s
md of the line and is reflected with equal magnitude and ’ Transmission System, by I. W. Gross and J. H. Cox, A.I.E.E.
l)ll:lse position, Erz. This wave reaches the sending end Transactions, Volume 50, 1931, page 1118 (818).
wit11 a magnitude and phase position given by Es?. This 18. Surge Voltage Investigations on Transmission Lines, by W. IV.
voltage is reflected with opposite polarity as given by E.+ Lewis, A.Z.E.E. Transactions, Volume 47, 1928, page 1111 (281).
sow impress upon the line an additional voltage given by 1% Corona and Line Surges, by H. H. Skilling, Elec&ical Engineer-
801 which is equal to E,,. The purpose of this additional ing, Oct. 1931.
\‘cltage is to annul the effect of Es3in so far as the line is 20. The Hysterisic Character of Corona Formation, by II. J. Ryan
and H. H. Hemline, A.I.E.E. Transaclio?ks, Volilme 50, 1931,
concerned. Both Ea3and ES4propagate along the line but
page 798.
Yince they are equal and opposite they cancel each other. 21 Discussion, by E. W. Boehne, A.Z.E.E. Transactions, Volume
(‘11 reflections are now provided for adequately. At the ’ 50, 1931, page 558.
@riding end are the voltages ES1,Es*, Ea3 and E84which 22. Distortion of Traveling Waves by Corona, by H. H. Skilling
add up to E+atn~, in (c). At the receiving end are the and P. deK. Dykes, A.I.E.E. Transactions, Volume 56, 1937,
‘Oltages
^. 1 . ErI and Er2. Thus the voltage at the receiving page 850.
‘“U 1s in phase with that at the sending end and is greater NOTE: Number in parentheses indicates page number in Lightning
by the reciprocal of the cosine of 34.8 degrees or 1.218. Reference Book.
CHAPTER 16

LIGHTNING PHENOMENA*
Original Authors: Revised by :
C. F. Wagner and G. D. McCann C. F. Wagner and J. M. Clayton

centimeters becomes elongated until at a critical field d+


I. GENERAL CHARACTERISTICS termined by the relation F1/?, = 3875 it becomes unstable,

T
HE physical manifestations of lightning have been A luminous glow is formed at each end and the energy
with us from the remotest times, but only compara- absorbed thereby results in evaporation of a portion of the
t<ively recently have the phenomena become even water forming the droplet. This sets a limit to the size of
part,ly understood. Franklin in his electrical experiments drops in a thunderstorm. Thus, no drops greater than 0.15
between 1740 and 1750 succeeded in identifying lightning centimeter in radius can persist in fields of 10 000 volts per
as the static electricity of his time. Beyond this fact little centimeter. Air pressure has no influence upon the field at
was learned until within the past 35 years. The real in- which this occurs. Macky suggests that in general the
centive to obtain additional knowledge lay in the necessity fields within thunderstorms will rise to a value of the order
of the electrical industry to protect against its effects. As of 10 000 volts per centimeter before discharge occurs,
longer transmission lines were built the need for reduction Wilson’s theory premises the existence of the normal
in outages due to lightning became more acute. This placed field which occurs during fair weather. This is generally
more stringent requirements upon lightning arresters and directed downward, the direction which convention has
other protective devices. Largely through the co-operation adopted as positive. In magnitude it is of the order of
of the utilities and manufacturers and through the use of one volt per centimeter at the surface of the earth and
special instruments such as the klydonograph, cathode-ray gradually decreases with altitude until at 30 000 feet it is
oscillograph, surge-crest ammeter, Boys camera, and ful- only about 0.02 volt per centimeter. A relatively large
chronograph, information of a very valuable character has drop of water (of say one millimeter radius) in such a field
been obtained regarding stroke mechanism and the voltages will become polarized by induction, the upper side acquir-
and currents associated with lightning. ing a negative charge and the lower side a positive charge
(see Fig. 1). The velocity of fall under the influence of
1. Charge Formation gravity of such a charge will be 590 centimeters per second,
In spite of the great interest in the manner in which which is large with respect to the velocity of the slowly
charges arise in thunderclouds, the question is still contro- moving ions even under the maximum field strength of
versial. Some half-dozen theories have been advanced, 10 000 volts per centimeter. At the under surface of the
but those of C. T. R. Wilson and of G. C. Simpson or drop a selective action with regard to the slowly moving
modifications of them have received most consideration. ions occurs. The negative ions tend to be attracted and
Both theories postulate ascending currents of air and the positive ions repelled. No such selection occurs at thi
relative motion of rain drops of different sizes.
Wilson’s theory’ depends for its explanations upon the ELE;;;;RX.l;ES
presence of large numbers of ions in the atmosphere. Many
of these ions, both positive and negative, attach themselves
to minute particles of dust and extremely small drops of
water, called Aitken nuclei, to form large ions as contrasted
with unattached or small ions. Over land the number of
small ions of each sign ranges from about 300 to 1000 per
cubic centimeter, and the large ions from 1000 to 80 000
per cubic centimeter. The small ions do not play an im-
portant part in Wilson’s theory. The mobility of an ion is
the steady velocity that can be attained under a voltage NEGATIVE
gradient of one volt per centimeter. The large ions have ION

very low mobility ranging from 0.0003 to 0.0005 centimeter


per second. Under a gradient of 10 000 volts per centimeter
this would correspond to a velocity of only 3 centimeters
per second.
Macky*, in a study of the behavior of water drops when
exposed to electric fields, found that a droplet of radius p Fig. l-capture of negative ions by large falling drop’

*The material in sections I and 11 of this chapter is essentially the fame 88 that presented in e. series of articles by the original authors that appeared in Au&*
tember. and October, 1941 issues of Electrical Enyineering. The material in section III is revised to include the reaulta of field studies through 1949.

542
chapter16 Lightning Phenomena 543

upPer surface. As a result of this action, the drop accu-


mulates negative charge. With the loss of the negatively
charged ions the remaining large ions are predominantly
positive. The smaller drops descend with a lower velocity
__-__--_-
_-^ -- -----
--- _----__- -
--_--_
,“(l thus their velocity becomes more nearly equal to that 4 A-\- - /
,,f the velocity of the large ions under the influence of the
,+ctric field. It becomes possible then for the small drops
of water to pick up positive charge by impact with the
@tive ions.
Thus, the original charges which were distributed at
random and produce an essentially neutral space charge, NEGATIVE RAIN’ ~POSITIVE RAIN
become separated. The large drops carry the negative
&q-gcS to the lower portions of the cloud and the small Fig. 3-Electrical conditions within thunderclouds’.
drops retain the positive charge in the upper portion.
hccording to Wilson’s theory the lower portion of the oval 8. The drops that do fall within this volume will be
&r~tl is negatively charged and the upper portion, posi- broken and the parts blown upward. The small drops that
tivclv. This mechanism of discharge has been verified have been blown upward will recombine and fall back
,!&imentally in the laboratory by Gott? who actually again, and so the process will be continued.
oi~t,ninedcharge separation by this process. The distribution of electrical charge that will result from
The theory of G. C. Simpson4 also has been substan- the conditions represented in Fig. 2 is shown diagrammatic-
tiated in part by laboratory experiments. It has been ally in Fig. 3. The mechanism by which charge separation
&own that a water drop of radius greater than 2.5 milli- occurs is explained clearly by Simpson as follows:
metersbecomes flattened or unstable when it falls through “In the region where the vertical velocity exceedseight meters
still or ascending air. A large number of smaller drops are a secondthere can be no accumulation of electricity. Above this
formed. The terminal or steady-state velocity of drops 0.25 region where the breaking and recombining of water drops take
centimeter in diameter is eight meters per second, which place (the region marked B in Fig. 3) here, every time a drop
thus constitutes the limiting relative velocity of rain drops. breaks, the water of which the drop is composed receives a
No drops will fall to earth in an ascending current of air positive charge. The corresponding negative charge is given to
cxccedingeight meters per second. It has also been shown the air and is absorbed immediately by the cloud particles, which
Ihut I\-hen water drops break up, the resulting droplets are carried away with the full velocity of the air current (neglect-
I)c!c:omepositively charged and the air negatively. ing the effect of the electrical field in resisting separation). The
The meteorological conditions within a cloud according positively charged water, however, does not so easily pass out of
the region B, for the small drops rapidly recombine and fall back
to Simpson are shown in Fig. 2. The unbroken lines rep- again, only to be broken once more and to receive an additional
positive charge. In this way the accumulated water in B be-
7 comes highly charged with positive electricity, and this is in-
6
dicated by the plus signs in the diagram. The air with its nega-
tive charge passesout of B into the main cloud, so that the latter
5 receivesa negative charge. In what follows, the region B will be
4: described as the region of separation, for here the negative
i
electricity is separated from the positive electricity. The density
3 of the negative charge obviously will be greatest just outside the
2
region of separation, and this is indicated in Fig. 3 by the more
numerous negative signs entered in the region around 8.”
I
ii.0 In contrasting the two theories, it may be observed that
Wilson’s theory leads to the conclusion that the lower
Fi& 2-Meteorological conditions within thunderclouds, portion of a cloud is negatively charged and the upper
according to Simpson. portion positively. Simpson’s theory as given above, on
the other hand, leads to the converse-that an intense
resentlines of flow of the air, their distance apart being positive charge resides in the head of the cloud and that
inversely proportional to the wind velocity. The air enters negative charge is distributed throughout the rest of the
thestorm from the right and passes under the forward end cloud. Wilson’s experimental observations of field changes
of the cloud where it takes an upward direction. Within next to the ground indicated that a charge of positive
the cross-hatched oval marked 8 the vertical component electric moment, that is, a charge distribution equivalent
of the wind is more than eight meters per second; and to a positive charge above a negative charge, is destroyed
Olltsideless. For the reason just stated no water can fall in the process of most lightning discharges. In addition
through this area. The dotted lines show the general path the results of magnetic-link investigations on electrical
Ofthe larger drops as they fall to earth. The balloon-like systems, as discussed hereinafter, indicate that approx-
Surfaceof which the oval 8 forms the bottom represents imately 90 percent of all strokes lower negative charge
a boundary within which the upward velocity is still very to the transmission system.
high. Only the larger drops are able to descend within The direct contradiction between these two theories led
the volume so formed and none are able to penetrate the Simpson and Scrase5 to investigate the charge distribution
,544 Lightning Phenomena

in a more direct manner. Free balloons equipped with “Our observations have shown quite conclusively that the
clock-operated apparatus to measure electric gradient, boundary between the positive electricity in the upper part of
atmospheric pressure, and relative humidity were released the cloud and the negative electricity in the lower is in every
during storms. It was found that in general the main body casein a region of the cloud where the tempernture is well below
the freezing point and generally below-10 degrees centigrade.
of a thundercloud is negatively charged and the upper part In this part of the cloud raindrops cannot esist. The cloud pa,.-
positively charged. A concentration of positive charge titles may be supercooled water, but on coalescing they would
appears to esist frequently in the base of the cloud. hc- immetliately freeze. The precipitation in the upper part of a
cording to Simpson and Scrase t,he cloud structure of the clout[ is in the form of crystals, either needles or p&es, which
t,ype shown in Fig. 4 offers a satisfactory explanation of tend to lie horizontally and to fall slowly in :t series of nearly
horizontal motions, first in one direction and then in an&her,
These crystals cannot play the role of the raindrops in Wilsoa~a
theory, for in the first place they are nearly perfect nonconductor8
and so do not become electrically polarized, and, even if they do
conduct, their shape and orientation is not favorable to the
formation of induced charges, and finally their rate of fall
relatively to the air is very slow. It is clear, therefore, that
Wilson’s influence theory cannot explain the separation of the
charges found in the upper part of the thunder-clouds.
“It is well known that during blizzards in polar regions which
are accompanied by large masses of blown snow, very strong
electrical fields are set up near the earth’s surface. These fielda,
with very few exceptions, are positive in direction; that is to say,
in the same direction as the field in the upper part of a thunder.
cloud. Simpson, in his discussion of the observations made in ttio
+ POTENTIAL GRADIENT
Antarctic (Simpson 1919), suggested that the impact of ice
AT GROUND crystals results in the ice becoming negatively charged and the
\
air positively charged. The genera1 settling of the negatively
charged ice crystals relatively to the positively charged air wouh]
Fig. 4-Hypothetical case of a cloud with a positive charge in then result in a separation of electricity with the positive chargo
the upper part, a negative charge in the lower part and a above the negative. This explanation, however, has not yet been
small region of strong positive charge near the basej. confirmed by satisfactory laboratory experiments. Whatever tho
physical explanation may be, there seems little doubt that the
practically all the soundings obtained in their investiga- upper separation of charge in a thunderstorm is in some way
tions. The positive charge at the top of the cloud gives connected with the presence of ice crystals.
rise to the positive field encountered at the ground as the “There appear therefore to be two different physical processeN
taking place in a thunderstorm to protluce the electrical effects:
storm approaches and as it recedes. The negative charge
One is confined to the upper parts of the cloud where the tem-
contained in the lower half produces a negative field every- perature is below the freezing point, and the second occurs in the
where under the cloud except where the local concentra- lo\ver part of the cloud where the temperature is above the
tions of positive electricity produce positive fields. Further freezing point. There is reason to believe that the former ia
verification of this fact is offered by data obtained by associated with the presence of ice crystals and the latter with
Simpson and Scrase by recording ground gradients during raindrops, probably in the way described by Simpson in his
the passage of storm clouds. From the records of 20 storms breaking-drop theory.”
it was found that the average length of time for which
the potential gradient was appreciably disturbed from its Fig. 5 represents Simpson’s revised diagram to illustrate
fine-weather value was i3 minutes. Ry centering each the meteorological and electrical conditions in a thunder-
record about the midpoint of the total period and dividing cloud. This differs from his early conception illustrated in
the record into five-minute intervals, the curve in Fig. 8 Fig. 3, in that a positive charge resides in the upper portion
shows the percentage of frequency of positive potential of the cloud above a region of separation from the negative
gradient. The parts of the curve above the line corres- charge, in which the temperat,ure is between - 10 and -20
ponding to 50 percent represent a preponderance of posi-
tive gradient and those below a preponderance of negative
gradient. It shows that the approach and recession of a
storm usually are accompanied by positive gradients while
the center of the cloud produces a negative gradient. This
is what would occur if the lower portion of the cloud carried
negative charge and the upper portion positive charge.
As between the Simpson and Wilson theories, the induc-
t’ion theory of Wilson seems to offer an adequate explan-
ation of negative charge in the lower regions of the cloud
and the concentration of positive electricity higher up in
the cloud. It does not explain the positive charge found NEGATIVE RAIN’ POSITIVE RAIN’

at t,hc base of the clouds. However, quoting from Simpson Fig. 5-Meteorological and electrical conditions within ’
7-t
and Scrase : thundercloud, according to Simpson’s revised theory. ”
;
I ,_
chapter 16 Lightning Phenomena 545

degreescentigrade. More recent investigations of Simpson respectively, of thunder arising from the stroke at A.
Znd Robinson6 further corroborate these concepts of the From this record Wilson calculated that this particular
three distinct regions of charge distribution. They also stroke was 7.1 kilomctcrs distant from the obscrvntion
more firmly establish that the separation of the positive station. Points B, b, and 0 are similarly associated. Tm-
,,llLLrgein the upper region from the negative charge in the mediately after the occurrence of a stroke the regenerative
ln;lin body of the cloud takes place at, temperatures below processes within the cloud begin to re-establish the field at
f,.cezing, while the positive-charge center found at the base the rate indicated by the rate of change of the gradient.
of the cloud is separated at a temperature above freezing.
11~..J. I-Iumphreys’ offers a modification of Simpson’s
breaking-drop theory. Hc ret,ains the esperiment,ally veri-
ectl fact that when a neutral drop is broken up by a jet
,)f :lir, the spray particles are negatively charged and the
lnrgcr remaining particles positively charged. It has been
,lIjscrved, principally by aviators, that the mean level at
,vllic:h t,he maximum vertical velocity of air occurs is well Fig. 6-Measurement by Wilson of ground gradient during a
LL/,ovcthe halfway point between the base and top of the thunderstorm.
tl,,lntlercloud. This velocity is commonly so great that
r:lirltlrops cannot fall through the air at its level. There- It can be seen that in general the curve is exponential in
f,)rc, the greatest concentration of raindrops occurs at this character and requires many seconds before the charging
Ijoint and the seat of the most active electric separation process attains a substantially constant value. The prom-
mllst be at a still higher level-the level at which drops inence at 14 hours 12 minutes 30 seconds was produced by
c:ln just maintain their position against the ascending air. the measuring device to establish the zero line and is not
‘The negative electricity presumably is first carried to or a record of change in gradient caused by a stroke.
tl(:ar to, the top of the cloud and from there pulled down
:&mg, or near to, the cloud wall by the descending air 3. Cloud Heights
III:L~,commonly flows down the sides, incident to cooling A search of the literature reveals very little definite data
ct:ulsedby evaporation. According to this explanation, a regarding the height at which the stroke can be said to
net, positive charge will occur above the midlevel of the originate. Simpson and Scrasej from a limited number of
18lo11d and the negative charge will be distributed more observations in England estimate charge centers as occur-
~oncrally throughout the cloud body. This theory does ring as low as 1500 feet and as high as 30 000 feet. Of
not accept the subzero temperature region of separation course, the origin of the stroke may not coincide with the
hct,wcenthe negative and positive charges as put forward charge center but may lie between the charge center and
t)Y Simpson. the base. E. J. Minser, chief meteorologist of Transcon-
E. J. Minser,8 however, largely from observations of tinental and Western Air, Inc., has observed that the alti-
:lviators, retains the conception of a region of subzero tude of the base of low-level thunderclouds frequently lies
trmperature as an essential factor in the explanation of between 500 and 1000 feet. He further states that hisstudies
Ihe charge generation within a cloud. He has found that show that the majority of lightning discharges have oc-
doud masses of high electric charge exist not only in the curred in the cumulus clouds of the shower type and that
cxllmulo-nimbus cloud but also in the cumulus cloud of the strokes to ground occur most frequently from clouds hav-
shower type. His explanation is based on a combination ing the lower altitudes. Data in possession of the United
of the Wilson and Simpson theories plus the ice-crystal States Weather Bureau indicate cumulo-nimbus clouds as
theory of precipitation suggested by Bergeron. having a mean ceiling of 5500 feet with some of them as
The processes occurring within cloud formations are so low as GO0to 700 feet. Thunderstorms for which the ceiling
complicated that it is quite possible that all the foregoing is practically zero are also reported at times. Instances in
t)hcnomena-the electrification resulting from breaking which the storm clouds actually envelop mountains rising
(lr()ps, the selective attraction by polarized drops, and from a plain are quite common.
interactions between wind and ice crystals at subzero
temperatures-are involved. 4. Charge and Field Distribution
Fig. 7, taken from Simpson and Scrase’s paper, shows
2. Rate of Charge Accumulation also that the fields and consequently the charge densities
The rate at which the charge accumulates is relatively are quite variable. The thickness of the vertical columns
slo\vas evidenced by the measurements of ground gradients is a measure of the potential gradient, the shaded portion
hY l%lsong and others. lo Fig. G is a typical record obtained indicating a positive field and the unshaded portion a
hY Wilson which shows both the magnitude and manner negative field. The maximum gradient that could be re-
Of variation of this quantity. The division between the corded in the balloon experiments of Simpson and Scmse5
solid black and shaded areas indicates the magnitude of and Simpson and Robinson6 was about 100 volts per cen-
the gradient according to the scale at the left-hand side. timeter. It was found that a gradient in excess of this
Sudden discontinuitics such as that at /l represent the amount very rarely was recorded in any of the balloon
destruction of a portion of the gradient as the result of a ascents, and it was concluded that the field in the thunder-
‘jghtning stroke. The single dark line at a and the double cloud is of the order of 100 volts per centimeter esccpt
‘lark line at (x indicate the time of the beginning and end, in relatively small regions of very great electrical activity
Lightning Phenomena

the lower pressure at the higher altitudes, even if there


be no water droplets, decreases the breakdown gradient,
On the other hand, tests indicate that discharges from
positive terminals appear to require lower gradients than
discharges from negative terminals, and since most dib
charges are from negative cloud sources, this property
would tend to encourage the initiation of discharges from
the ground.
What are the facts? The results of a large number of
G,MJ50 ,300 IO 20 30 40 50 ,400 IO 20 30 40 50 ,p
- .-^ CHARGE ON RAIN NOT KNOWN FLASHES ALONG BASE OF CLCUO
photographic records by Schonland’8 indicate that all of
the discharges he has observed were initiated from the
cloud end rather than from the ground. McEachronl’ hu
shown that for the discharge of lightning to a very tall
building the initial streamer usually proceeds upward from
Fig. 7-Electric gradient by Simpson and Scrasej with free the building. In a later discussionI he states: “Thus far
balloons.
1 have no evidence that upward leader strokes occur ti
transmission lines of the usual height.” The evidence,
where the lightning discharges originate. They found no therefore, suggests that for the type of discharge with
evidence of large horizontal sheets of positive and negative which these articles are largely concerned, namely, those
charge with electric fields approaching the breakdown to low structures, the initial discharge can be assumed to
strength of the air. start from the cloud.
As shown in Fig. 7, Simpson and Scrase found that the Present knowledge of the mechanism of stroke propaga-
field between cloud and ground was more or less inde- tion is largely the result of the work of Schonland and his
pendent of height and of the order of 50 to 100 volts per
centimeter. Thus the gradient in the region between cloud
and ground is about 1 000 000 volts per thousand feet so
that for a 10 000 foot cloud the potential at the cloud base
would be of the order of 10 000 000 volts. Taking into
consideration the more intense fields near regions of high
charge distribution, it is likely that cloud potentials are of
the order of 20 000 000 volts.
5. Mechanism of Stroke
The electrical charge concentrations within a cloud, of
course, must be limited to the bounds of the cloud proper
and in most cases are much smaller. In relation to these
dimensions the earth can be regarded as infinite in extent.
It follows then, from consideration of a flux plot, such as
that of Fig. 4, that before the discharge the electrical gra-
dient within the cloud must be very much greater than at
the earth where the gradient never exceeds about 100 volts
per centimeter. Thus, the discharge tends to be initiated
100 CEbJTER
CLOUD CLOUD
5 5 APPROACHING OVERHEAD
i5 w
$5:
F&S

$j
Y&S
a E
2 B 0.’
-30 -20 -10 0 IO 20 30
TIME-MINUTES

Fig. S-Average frequency of occurrence of positive potential


gradient at the ground during passage of a thunderclouds.

at the cloud rather than at the ground. As mentioned


previously, the tests of Macky show that in a region occu-
pied by water droplets of the size expected in clouds the
critical breakdown voltage is 10 000 volts per centimeter,
I, :i
a magnitude contrasted with 30 000 volts per centimeter (b) ,:;
in air without water droplets. This phenomenon likewise Fig. 9-Boys-camera photograph of lightning taken by;;
tends to initiate the discharge from the cloud. In addition, Schonland’3-17
2
.,I
‘ai
chapter 16 Lightning Phenomena

tisociates in South :\frica. *s-l7 Most of their data were


,+tained photographically by means of a Boys camera.
The essential feature of the Boys camera is that it contains
t,vo lenses mounted diametrically to the axis about which
the lens system rotates with respect to the film. The com-
bination of the motion of the lenses and the propagation
af the stroke produces two distorted pictures of the stroke
from which, by superposing, one can deduce the direction
llnd velocity of propagation of the stroke from the displace-
ment between corresponding points on the two images.
The speed of revolution of Schonland’s Boys camera was
3000 rpm which permitted a resolution of the photograph
of 0.3 microsecond. Fig. 9(a) shows a pair of these pictures
morlnted together.
11lightning discharge which usually appears to the eye
:,s:Lsingle flash is in reality generally made up of a number
,)f scparnte strokes that travel down the same path. The
i,,t,(:rval between these components varies between 0.0005
braid0.5 second. Each separate stroke starts as a downward
leader from the cloud. When the downward leader strikes
~11~ ground it is followed by an intense return streamer
which consists in a point of intense luminescence traveling
from the ground to the cloud. The rather interesting
Properties of these phases of the flash are to be discussed
subsequently in some detail. Fig. 9(b) is typical of the
pictures obtained by Schonland. It shows a number of
repetitive strokes. A slower camera of this general type Fig. lo-Boys-camera photograph by Schonland*3-17 showing
permits the determination of the order in which the the “stepped leader.”
tlischnrges occurred.
Initial Leaders-The leader of the first component Schonland by means of the Boys camera. The nrrolvs
stroke of a flash is preceded by a “pilot streamer” which indicate the direction of time, and the stepped leaders
rcprcsents propagation of the discharge into virgin air hav- are shown to the right of the subsequent brilliant return
ing very low ionization. Current@ associated with the stroke. As the leader seeks its way to earth, branches
pilot streamer are small, the majority being of the order radiate from the main stem forming tentacle-like fingers
of only a few amperes. The luminosity is likewise very spreading earthward. This stage of the process is shown
h-so low that it does not register on the photographic in Fig. 11(a). A portion of the charge in the center from
Plat)eof a Boys camera. Its existence is deduced by infer- which the stroke originated is lowered and distributed over
cnccand by an analysis of the mechanism of the discharge. this entire system of temporary conductors. This process
In the following discussion velocities are given in terms of continues until one of the leaders strikes the earth. Short
that of light (approximately 1000 feet per microsecond) streamers have been observed to reach upward from the
:U it is the same as that of waves on transmission lines, earth to meet the downward-moving leader just before it
:Ind, therefore, provides a very convenient bench mark reaches the earth, but, in general, if such exist they must
when the phenomenon is applied to considerations of the be short. Regarding this point, Schonland in a letter to
rlrect upon systems. The most frequent velocity of prop- the authors says:
Qation of the pilot streamer is about l/20 of one percent “It must be remembered that the country in which we work
of that of light. consists of rolling hills and valleys, so that the base of the dis-
21s the pilot streamer proceeds, it is accompanied by charge is often obscured; there must, however, be a large num-
Points of luminescence which travel in jumps giving rise ber of casesin which the full length of the discharge was recorded
10the term “stepped leader.” The velocity of these steps by the cameras and we have seen no evidence of any extensive
exceedsone-sixth of that of light and the distance traveled leader discharge from ground. Such leaders as do occur are com-
in one step is about 50 meters. The path of each step is paratively short, for otherwise we should have detected them.”
essentially straight but each fresh step, in general, takes a Return Stroke-As the leader strikes the ground an
different direction. The change in direction at each junc- extremely bright return streamer propagates upward from
tion thus gives rise to the tortuous path characteristic of the earth to the cloud following the same path as the main
lightning. The electrostatic lines of force from the stroke channel of the downward leader. The charge distributed
to ground should form essentially smooth curves-another along the leaders thus is discharged progressively to ground
fact which suggests that the zigzag path must be attribut- giving rise to the very large currents usually associated
able to some variable condition at the head of the dis- with lightning discharges-currents varying between 1000
charge, this condition being either variations in the head and 200 000 amperes. The rate of propagation, about 10
itself or variations in space ionization. Fig. 10 shows a per cent of that of light, is determined by the rate at which
Photograph of several such stepped leaders obtained by the head of the lightning channel can become sufficiently
548 LightnCng Phenmmenn

(a) Charge centers in cloud; pilot (b) Process of (a) almost com-
st,reamcrandsteppedleaderprop- pleted; pilot streamer about t,o
agate carthwurd; outward strike earth
branching of strwmers to earth.
T,owcring of charge into space
twnrath cloud Fig. 12--Mechanism of discharge of component stroke,
according to Schonland’*.

Fig. 12 represents the story of a complete discharge of a


component stroke according to Schonland,‘8 in which the
upper figure shows the progress of the stepped leaders and
the lower figure the return streamer. Xote that the time
scale has different units.
From the instant of initiation of the leader streamer to
ground similar leaders progress into the cloud, tapping
more and more charge. After the completion of the initial
. . . . . . . . . . . I . . . . I* high-current discharge, a smaller current continues to flow
(c) Heavy return streamer; dis- (d) First charge center com- for some time, the magnitude and duration being dependent
charge to earth of negatively plctely discharged; development upon the propagation of the streamers within the cloud
charged space beneath cloud of streamers between charge cen- body. This point is illustrated very well by the current
ters within cloud record’” shown in Fig. 13 obtained at the Cathedral of

INITIAL HIGH CURRENT


SHORT DURATION
LOW-CURRENT-
LONG-DURATION TAIL

f . + * ..‘I , . . t .

(c) Discharge between two (f) Heavy return streamer dis-


charge centers; dart leader prop- charge to earth of negatively
agates to ground along original charged space beneath cloud
TIME -MICROSECONDS
channel; dart leader about to
strike earth; negative charge Fig. 13-Current record of direct stroke to Cathedral of
lowered and distributed along Learning of the University of Pittsburgh, June 10, 1939;
stroke channel negative polarity; four coulombs.
Fig. ll-Diagram showing charge distribution at various
stages of lightning discharge. Learning of the University of Pittsburgh. A high-current
component, which rises very quickly to 20 000 ampere%
conducting to accommodate these large currents. The decreases to 1000 amperes in 200 microseconds. From lO@J
charge that had been lowered from the cloud to the amperes the decay is much slower, the current dropping
antenna-like system of streamers by this means is further to less than 100 amperes in 10 000 microseconds.
lowered to ground. The former of these processes is rela- Multiple Strokes-With the development of a high-
tively slow, requiring a time of the order of 10 000 micro- conducting arc path between the charge center and groun dJ
seconds, whereas the latter is relatively fast, requiring only the potential of the charge center is lowered considerablJ’*:~!
about 50 to 100 microseconds. Since the same charge is This process may develop higher potential differences be-p:
involved in both stages, the difference in time esplains the tween this charge center and another charge center vGt@.i
large difference in currents involved in the two stages. the cloud, resulting in the continued progress of streamer?@
d
Chapter 16 Lighhing Phenomena 549

into the cloud and the formation and attraction of stream- the slowest, being about l/20 of one percent of that of
ers from the other charge center. Upon the meeting of two light. The stepped leaders that follomcd in the path blazed
s,~ch approaching strenmcrs, a relatively low-conducting by the pilot streamer have a velocity of the order of 3
p:Ltll to ground for the new charge center is formed. The percent of that of light. The return streamer is also quite
,.&ting discharge traverses the same path blazed by the rapid as it follows the intense ionization of the initial
first stroke. The leader streamer of this stroke differs from streamer and has a velocity about 10 percent of that of
that of the first stroke in that the stepped phenomenon is light. Because of the interval elapsing between component
,,sually not discernible in Boys camera photographs, there strokes and the resultant deionization, the velocity of
is no branching, and the velocity of propagation is much propagation of the dart leaders is about one per cent of
larger, being of the order of three percent of that of light. that of light. The velocity of propagation of the pilot
ljecause of these characteristics this leader is known as a streamer into virgin air appears to be associated16with the
ct&rt” leader. Upon reaching the earth, a return streamer critical drift velocity of an electron under the influence of
travels back to the cloud just as for the first stroke. This the breakdown voltage gradient of air.
me&nism is illustrated in Fig. 11. The stroke current Hot and Cold Lightning-It has been known for a
Llt, the ground is also similar in character to that of the long time that the explosive and incendiary effects of dif-
first stroke, rising rapidly from zero to a maximum, filling ferent strokes vary widely. One stroke might blow a tree
sl~\~ly for several hundred microseconds and then more apart and still have little burning tendency while another
,sl~\vlyfor a much longer time. Schonland’s results indicate might have little bursting effect and still result in a fire.
tllnt in the majority of cases the crest magnitude of the This difference was recognized as early as 23 A.D. by Pliny
first stroke is the greatest, probably because the branching the Elder who wrote in his “Satural History”:
of the antennae system of streamers permits of a lowering
“Of thunderbolts themselves several variations are reportecl.
of a larger charge before it is released to earth. This is not Those that come with a dry flash do not cause fire but an es-
:~lways the case, as the second or subsequent strokes are plosion. The smoky ones do not burn but blacken. There is a
sometimes the greatest. third sort called ‘bright thunderbolts’ of an extremely remnrk-
11sthe charge in the second charge center is dissipated able nature; this kind draws casks dry without damaging theil
by being carried to ground, the streamer in the cloud might lids and without leaving any other trace and melts gold and
tap a third center and the same process be repeated. In copper and silver in their bags without singeing the seal. Marcia,
general, approximately half the flashes are of this multiple a lady of high station in Rome, was struck by lightning while
character. Flashes having as many as 40 component strokes pregnant and though the child was killed, she, herself, survived
have been observed by Larsen.20 A conception of the without being otherwise injured. Among the portents in connec-
rclstive time involved in these processes is given by tion with Catiline, a town councillor of Pompei named Marcus
Herrenius was struck by lightning on a fine day.”
Fig. 11.
In general, the rates of propagation of the discharges Returning from antiquity, fire-tower lookouts have ob-
discussedvary in inverse manner to the amount of previous served similar distinguishing characteristics in strokes that
ionization of the path. Thus, the initial pilot streamer do and do not cause fires. Along more scientific lines the
progressing into virgin air with very little ionization was persistence of the luminosity of the main channel of a

OART LEADER

RETURN STREAMER

IO PER CENT
GROUND

TIME-

Fig. 14-Diagram showing lightning mechanism and ground current.


A1l velocities expressed in percent of the speed of light, which is 984 feet per microsecond or approximately 1000 feet per microsecond.
550 Lightning Phenomena Chapter 16

lightning stroke was recognized by Schonlsnd and CoIlens’”


in 1934.
Walter?’ in 193.5discussed a photograph taken by Doctor
H. H. Hoffert in 1889 which was obtained by turning the
camera to and fro by hand about a vertical asis, the period
of rotation being about three-quarters of a second. Streaks
of light appeared between component strokes on the
negative and in explaining their presence he says:
“Now, as I demonstrated some years ago, they are by no -
meansdue to an afterglow of the lightning channel produced by RECORD NO. I 2 21 22
thermal or phosphorescent causes, but they are always asso- CREST CURRENT
16.000
IN AMPERES. 21,000 7,000
ciated with a real after-discharge in the channel, that is, with
an electric current following the main discharge along the same CHARGE IN
4
COULOMBS 60 MORE THAN 2D
track.”
SIZE OF COPPER
According to his explanation, the duration of these points WIRE FUSED NO. 20 NO. 22 NO. I8 NO. 16
of luminescence must have been at least 0.1 second.
Stekolnikov and ValceP m 1936 measured voltages in- Fig. 15-Fusion data on strokes to the Cathedral of Learning,
University of Pittsburgh.
duced on a horizontal antenna by indirect lightning strokes.
Results they obtained with a rotating klydonograph indi-
cated that the duration of the current was between the inch, which were placed by the authors in the path of
limits of 2600 and 10 000 microseconds. actual lightning currents. A fulchronogrnph record for one
McEachron and McMorris zu also in 1936, refer to an of these is shown in Fig. 13.
unpublished photograph by o’ne of them which shows a
duration of luminescence of 0.23 second. This stroke how- 6. Ground Gradients
ever is described as being to a tall steel-frame building and As stated previously, the fine-weather electrostatic gra-
such a stroke has different characteristics from strokes to dient at the surface of the earth is positive and averages
open ground and transmission lines. about one volt per centimeter. As a charged cloud passes
Continuing the work of Schonland and his associates, over a particular spot this gradient at first rises because
Malan and Coilens report data on the luminescence in the positive charge in the upper portion of the cloud be-
the following statement: comes effective first. As the cloud continues to approach,
“The most frequent value of the duration as measured on the the gradient then decreases and finally becomes negative
photographs appears to be of the order of 1000 microseconds, as the negative charge in the lower portion becomes effec-
ranging in extreme casesfrom a few hundred microseconds to tive. The magnitudes of field gradients directly beneath
half a second.” thunder clouds are from about 50 to 100 volts per centi-
Bellaschi,“” by comparing laboratory discharges of differ- meter before a discharge occurs.
ent magnitudes and durations, showed that long-duration As discharges occur, the nature of the electric field be-
currents were essential to ignite excelsior, form fulgurites, comes more complicated. Appleton and ChapmarP have
or produce significant melting of metal. Further evidence obtained cathode-ray oscillograms of the change in gradient
of the existence of lightning currents of long duration was due to strokes at various distances and correlated them
observed by Bergvall and Beckz5 in the form of markings with the characteristic portions of the stroke mechanism
left by discharges upon lightning rods and arrester gaps. Schonland, Hodges, and Collens” have co-ordinated Boys
These markings were correlated in the laboratory with camera photographs with similar cathode-ray oscillograms
markings produced by impulses of known wave shape, from of the change in gradient due to strokes at distances of
which the existence of long-duration waves was demon- several miles. These records were found to be of the two
strated. Fig. 15 shows the degree of melting of several principal types illustrated in Fig. 16, 65 percent being of
one-half-inch copper rods tapered for a distance of one the type shown on the left and 35 percent of the type shown

TIME -

Fig. 16-Relation between stroke mechanism and ground gradients for the two types of discharges observed by Schonland.
Chapter 16 Lightning Phenomena 551

on the right. In this figure the upper portions show the as to draw strokes from clouds at a smaller voltage than
gradientIs and the lower portions the photographic records. lower objects.
.ks may be seen from this figure, the electric field can be
resolved into three characteristic portions labeled a, b, and II. INSTRUMENTS FOR THE MEASUREMENT
C. As shown by the photographic record, the “a” portion OF LIGHTNING SURGES
is associated with the downward leaders, the “b” portion is
associated with the return streamer in the period it prop- Of primary importance in the lightning protection of
Ligates from ground to cloud, and the “c” portion with the transmission lines is a knowledge of the magnitude, dura-
lower-magnitude current flowing down the channel after tion, and wave shape of the voltage and current surges
the return streamer reaches the cloud. appearing on utility systems. The characteristics of the
For the more predominant type of discharge illustrated stroke itself determine the resulting surges which occur on
on the left in Fig. 16, the pilot streamer moves from cloud the electrical systems. Thus it becomes desirable to have
to ground at a more or less uniform speed and the field instruments capable of measuring not only the system volt-
increases as the pilot streamer propagates, having super- ages and currents, but also the properties of the stroke.
imposed oscillations produced by the stepped leaders. The One difficulty encountered in the development of such
increase in gradient is produced by the lowering of charge instruments is the wide recording range both in magnitude
from the charge center in the cloud to the region between and time that must be covered. Currents vary from a felt
cloud and ground. In the second type illustrated at the amperes to 200 000 amperes. Portions of the wave change
right, the pilot streamer moves at a uniform velocity of so rapidly that time intervals of the order of a microsecond
the same order of magnitude as for the first case over the need to be measured, while at the same time the duration
first part of its path. However, at a certain point in the of the complete stroke may be longer than one second, or
path its velocity decreases, and the step length and bright- 1000 000 microseconds.
ness of the stepped leaders becomes much smaller. Owing The element of chance is also introduced in that the
to the time constant of the amplifier used for measuring point at which lightning may strike is unpredictable. The
the field, the recording spot falls to zero during this phase probability of a given point being struck is enhanced by
of the leader process because of the slow change of field height so that in some cases instruments are installed on
strength. tall objects. However, the available evidence indicates
The “b” portion represents a much more rapid rate of that discharges to such objects differ in important aspects
change of field because of the rapid lowering of the charge from those to low objects. In order to obtain data that
from the antenna-like system between cloud and ground are truly characteristic of strokes to transmission lines and
to the ground by the return streamer. Since rapid changes other electrical equipment, the observer is faced with the
of current also are present, they produce part of the electric prospect of placing a large number of instruments in the
field. As the nature of the field is a function of the distance field with the hope that some will obtain for him the desired
from the stroke, these records should not be taken as information. Economic considerations thus place a very
typical of the gradients very close to strokes. serious limitation upon the instruments, since to be prac-
ticable for use in large numbers their unit cost must be small.
7. Strokes to Tall Buildings Since voltage rather than current is the immediate cause
McEachronll has made investigations of lightning to the of system outages it is natural that field measurements
Empire State Building in New York City. Equipment were first made of voltages produced on lines by lightning.
installed in the tower can measure the current of strokes Thus voltage-measuring instruments were developed first.
to the mooring mast, and cameras located in near-by
buildings can photograph the stroke simultaneously, thus 8. Spark Gaps
permitting co-ordination of the records. Because of the The first attempts were made with a relatively crude
high altitude of this building, it acti much as a large needle device consisting of parallel gaps with different spacings.
extending up from a plane. The gradients developed at the To prevent the first gap to break down from short-circuit-
tower become so large that most of the discharges develop ing the others and to prevent a system outage, a relatively
from the tower mast and propagate upward. These dis- high resistance was placed in series with each gap. The
charges usually begin with small currents and may or may maximum gap broken down, which was indicated by mark-
not develop into distinct discharges of high current value. ings on a thin piece of paper, was a measure of the voltage.
of 47 strokes photographed, 34 indicated continuous cur- Peekz7 used sphere gaps and needle gaps in parallel to
rent flow until the end of the stroke and 4 consisted of two obtain a measure of the wave shape. A comparison of the
succeeding continuous discharges in the same path, while length of gap sparked over for the two types of electrodes
7 others began as continuing strokes followed by distinct gave some indication of wave shape.
discharges. Development of extensive leaders from the
ground end appears to be characteristic of strokes to tall 9. The Klydonograph
buildings exclusively. Caution must be exercised in apply- The first successful field instrument developed for surge-
ing data obtained from tall structures to lower structures voltage measurements was the klydonograph, invented by
such as transmission lines, for certainly the pilot leader J. F. Peters28 in 1924. In 1777, Doctor G. C. Lichtenberg
and stepped leader of the first component differ from those discovered that figures can be produced in sulphur dust by
for strokes to essentially flat ground. In addition, the the electrostatic field of a charged electrode placed near by.
mechanism of discharge from tall objects may be such Others found that Lichtenberg figures could also be pro-
Lightning Phenomenu Chapter 113
NEGATIVE POSITIVE
FIGURES FIGURES

._ 1

Fig. 17-Klydonograph.

duced on photographic plate. These figures are functions


of the magnitude, polarity, and wave shape of the im-
pressed voltage. The klydonograph (Fig. 17) employs these
characteristics for the measurement of surge voltages.
The klydonograph consists of a rounded electrode bear-
S-MICROSECOND FRONTS
ing upon the emulsion side of a photographic film or plate
resting on the smooth surface of an insulating plate backed
by a plate electrode. In Fig. 18 are shown typical klydono-
grams obtained for different types of voltages. The mini-
mum critical voltage necessary to produce a figure is about
2.0 kv and the maximum voltage that can be recorded is
about 18 kv, since at higher voltages spark-over occurs
and fogs the film.
For unipolarity there are characteristic differences be-
tween the figures for positive and negative voltages. HOW-
ever, for either polarity the radius of the figure, if it is
symmetrical, or the greatest distance from the center of the -~~ ZOO-MICROSECOND FRONTS
figure to its outside edge, if it is unsymmetrical, is a function
only of the applied voltage. Oscillatory waves produce
superimposed figures for each part of the wave, enabling
a distinction to be made between unidirectional and
oscillatory voltages.
The klydonograph has been built with multiple elements
for simultaneously recording several voltages on a trans-
mission line. It has been developed also with a slowly
moving roll film co-ordinated with a recording clock to
enable more than one surge to be recorded together with
its time of occurrence. In addition rapidly moving film
has been used for measuring power-frequency voltages and BEYOND THE CALIBRATION RANGE
lightning surges. A better interpretation of the character
of the surge can be obtained from positive figures since for
the same voltage they are more than twice the size of the
negative figure, and the nature of the figure varies more
with wave shape. Thus negative surges of less than twice
normal line volt,nge cannot be recorded as they are obliter-
ated by the positive part of the power-frequency record.
To overcome this disadvantage, Foust3” developed an in-
strument having two elements in parallel, one connected
in the opposite polarity to the other so that a positive
figure is always obtained. In applying the klydonograph
to the measurement of voltages on transmission lines a OSCILLATORY SURGE DUE TO AN ARCING GROUND
capacitance potential divider is generally used. Fig. 18-Typical klydonograms.
Chapter 16 Lzghtning Phenomena 553

The klydonograph has been employed in conjunction The Radio Corporation of America has developed 3
,vith a resistance shunt for the measurement of surge cur- sealed-off cathode-ray oscillograph tube that permits suf-
rents and has also been used to measure the maximum rate ficient recording speed by means of esternal photography
of rise of current in transmission-line conductorszg and of the fluorescent screen. Sufficient writing speeds by this
tower legs3’ by connecting it across a resistance in series method were made possible by its great beam intensity
)vitll a loop of wire inductively coupled with the main and the development of more sensitive photographic films
current circuit. and faster lenses. A laboratory oscillograph utilizing this
The klydonograph is a relatively simple and inexpensive tube has been described by Kuehni and Ramo.37 Being
device, which permits its use in large numbers. It has been scaled off, this tube lends itself readily to field work, for
valuable in providing statistical data on the magnitude, automatic operation. Wagner and McCann38 with the co-
polarity, and frequency of voltage surges on transmission operation of Ackermann developed a circuit and auxiliary
lines. However, its accuracy in measuring magnitude is device for use with this tube that permits its placement in
only of the order of 25 or 50 percent and certain inter- the field without the constant attendance of an operator.
ljretntions regarding wave shape that have been made with It is portable and operates from a IlO-volt a-c circuit. The
it are questionable. tube is of the hot-cathode type and requires a potential of
15 000 volts to accelerate the electron beam which im-
10. The Cathode-Ray Oscillograph pinges upon a Willamite screen. The image thus produced
A cathode beam consisting of a stream of electrons is photographed. An auxiliary grid within the tube pre-
emitted from a “cold” cathode and accelerated in an electric vents the formation of an electron beam under normal
field in an evacuated tube was first produced by F. Braun conditions; hence fogging of the film is prevented. On the
in 1897. Wiechect developed the concentrating coil for occurrence of a surge the beam is automatically initiated
l)cam focusing and the principle of magnetic and electro- by the control grid and records the phenomenon.
static deflection. In 1913 Zenneck employed the principle To measure the voltages on transmission lines a ca-
of the cathode-ray beam to record electrical phenomena. pacitance divider is generally used, and for surge currents
110photographed traces of the beam impinging on a fluo- a resistance shunt, the voltage across the resistance being
rescent screen and deflected by a surge of a few milliseconds applied to the oscillograph plates. To cover a wider cur-
tluration. This method of recording, however, was not rent range a nonlinear shunt can be used.
suitable for surges as fast as those produced by lightning.
Dufou? developed the first cathode-ray oscillograph cap- 11. Paper Gaps
:thle of recording such transients. He increased the record- A thin piece of paper between two electrodes connected
ing speed by permitting the beam to impinge directly upon in the lead carrying the surge current has been used to
photographic film placed inside the evacuated tube. An obtain an indication of the magnitude of surge cur-
oscillograph of this type was first used to study the be- rents.3g*40.t1 Tests with surge-generator discharges and
havior of artificial lightning surges on a transmission line 60-cycle currents indicate that the area of the hole pro-
in the United States by the Westinghouse Electric Corpor- duced in the paper is proportional to crest magnitude of
&on in 1926, on a five-mile line furnished by the Duquesne current and is independent of wave shape. The effect of a
Light Company. multiple stroke, however, is questionable.
1:nlessthe beam is prevented from striking the film until
the occurrence of the phenomenon which it is desired to 12. Fusible Wires
record, fogging of the film results. Norinder 33overcame By calibrating different-sized wires connected in series
this difficulty by means of a special relay, which normally and noting the largest one that fuses,42it is possible to ob-
tIrevented the beam from striking the film but which upon tain an approximate indication of the time integral of the
tllc occurrence of a surge bent the beam around the block- square of the current. One of the first to employ this
ing target. The Westinghouse company34 employing this principle was Professor E. C. Starr of Oregon State Uni-
relay developed an oscillograph suitable for both field and versity, who used it to measure strokes to masts at light-
laboratory work. ning stations which he established on mountain peaks.
Two other schemes have been used to initiate a Dufour
type of oscillograph and make it suitable for lightning 13. Magnetic Surge-Crest Ammeter
studies. The General Electric Company35 developed an The magnetic surge-crest ammeter developed by Foust
oscillograph in which the voltage supply to the cathode and Kuehn?” provided a simple and inexpensive instru-
1~s an impulse, from a small surge generator, initiated ment capable of measuring the crest magnitude and po-
through a triple gap by the surge to be recorded. Georges6 larity of surge currents. This instrument consists of a
developeda hot-cathode grid-controlled high-vacuum tube. small bundle of laminated permanent-magnet steel pieces.
Oscillographs of the foregoing type employ cathode volt- It is placed in an unmagnetized condition in the vicinity of
%es of about 30 to 40 kv. Having power supplies of such a conductor whose current it is desired to measure. The
hi& voltage and being of the pumped type to enable remanent magnetism produced in the steel is a function of
‘emoval of film, they are relatively expensive and delicate the magnitude of the current producing it for unidirec-
in operation and require the constant attendance of an tional surges. A special instrument measures the remanent
Operator. These considerations greatly limit their use in magnetism and is calibrated directly in terms of the orig-
the field, especially in numbers sufficient to obtain data of inal magnetizing current. The polarity of the surge is
a statistical nature. indicated by the direction of magnetization. This instru-
\
554 Lightning Phenomena Chapter 16

a light source consisting of a neon treater lamp, which can


be initiated by the transient in about 20 microseconds.
15. Fulchronograph
The cathode-ray oscillograph is the best instrument
available from the standpoint of determining \vave shape
of transients, such as lightning surges. Tts cost and corn-
plexity, however, limit its use in the field. Because of the
variable character of lightning, it is important to obtain
sufficient data to determine the statistical nature of its
properties. The klydonograph and surge-crest ammeter
have provided data of this type on the magnitude and
polarity of surge voltages and currents. The number of
components, wave shape, and duration of surges are of
even more importance, however, and it was with t,he view
of gathering data on these properties of surges that the
Westinghouse Electric Corporstion”8 developed a number
of new recording instruments. The most important of
these is the fulchronograph,* a device capable of measuring
the wave shape and duration of the tail of current surges,
but cheap enough, and simple enough in its operation to be
used in large quantities in the field.
The essential part of the fulchronograph is a slotted
aluminum rotating wheel. In a “high-speed” fulchrono.
graph, Fig. 20(a), the wheel turns at 3130 rpm, and in the
“sloly-speed,” at approximately GO rpm. In the rim of
each are 408 laminations of permanent-magnet steel nine
mils thick, projecting from each side. The laminations
pass between narrow coils, Fig. 20(b), through which flows
(a) (b) the current to be measured. As a particular set of laminn-
Fig. 19-Surge-crest ammeter links. tions spans the gap between the coils, they are subjected
(a) Link. to a radial magnetizing force proportional to the current at
(b) Link in position on transmission-line tower. that instant. By measuring the retentivity or residual flus
in the laminations it is possible to reconstruct a graph of
ment has been used extensively both in the United States the current as a function of time. The device functions in
and abroad to measure currents in direct strokes; in trans- a manner similar to the surge-crest ammeter except that
mission-line tower legs, ground wires, and phase con- time has been introduced by the rotation of the wheel.
ductors, in counterpoise conductors and in ground leads of By placing a high-speed and a low-speed fulchronograph
arrest,ers. together in series and running them continuously, greater
The magnetic links are usually placed in brackets as wave detail and a longer period of time can be covered
shown in Fig. 19 (h), fastened to the conductor so that than by the use of either one separately. The high-speed
their axes coincide with the normal direction of the mag- unit in one revolution divides 17 000 microseconds into
netic lines of force. Several links placed at different dis- 43-microsecond intervals, the low-speed unit in one revolu-
tances from the conductor commonly are used to cover tion divides one second into l/400 second intervals. Mul-
a wider range of currents and also to distinguish between tiple-stroke discharges rarely last longer than one second,
unipolarity and oscillatory surges. These instruments or have time intervals between strokes of more than 0.5
being cheap and simple, thousands of them have been used second. These facts make it possible with the data Pro-
throughout the United States and have provided valuable vided by the two wheels to resolve a surge into its multiple
information relating to lightning currents. components and to obtain the wave shape and magnitude
of each.
14. Crater-Lamp Oscillograph
A magnetic oscillograph cannot record faithfully fre- 16. Magnetic Surge-Front Recorder
quencies much above 10 000 cycles per second and cannot The principal disadvantage of the fulchronograph is ita
record the wave shape or crest magnitude of the initial inability to measure the high rates of rise of the front Of
high-current components of lightning surges. However, it the waves. Devices for measuring the maximum rate Of
should be able to record the relatively long low-current rise have been available for some time. As mentioned
component and give some information on the total dura- previously, the klydonograph can be used to indicate the
tion and number of components of strokes. Ordinary maximum rate of rise on the front of lightning-curret
methods of a,utomatic operation by mechanical relays surges. Probably of greater importance than the mti-
require about one-half cycle to initiate. However, the *This name was obtained ns a combination of the Latin word /ulme*. rod$
lightning. and the Greek word chronos. meaning time, and graphein. mesnieO
crater-lamp oscillographM overcomes this difficultly. It uses write.
Chapter 16 Lightning Phenomend

Fig. 2l--Magnetic surge-front recorder.

/,,-- inductors of these three circuits serve to record their


maximum currents i,,,. The introduction of an nppre-
t’ ciable time constant T, into these circuits prevents the
currents in them from responding to instantaneous changes
MAGNETIC :
LINE OF FORCE; in the main current, thus substantially eliminating the
effect of high-frequency oscillations in the front of the
I
\
\
wave. If the resistors mere not present, the current in
MAGNETS MOUNTED the auxiliary coils at all times would be proportional to the
\ ON PERIPHERY OF WHEEL
rate of change of the main surge current and the masi-
mum current in them would be proportional to the masi-
MOTl6N OF MAGNETS mum rate of rise of current on the front of the main
W surge.
When inductance is added to the auxiliary circuits, the
Fig. 20-Fulchronograph.
maximum current in any one of them is proportional to
(A) High-speed fulchronograph showing wheel. the average rate of rise of the main surge current over a
Cb)Diagram of fulchronogrnph showing relation between one definite range. Three of these circuits are adequate to
set,of lamimitions ltnd the coils on one side of the wheel.
cover the desired range of time to reach crest.
The other side of the wheel is the same, except that t,he mag-
netic circuit is partially completed through iron. 17. Magnetic Surge Integrator
The magnetic surge integrator is a relatively simple and
mm rate of rise is the average rate of rise, such as can inexpensive device for recording the total charge or the
1)~defined by a straight line drawn through the two points integral of the current in a lightning surge. It consists
\vlrich are 10 percent and 90 percent of crest value. essentially, as shown by the schematic diagram of Fig.
The magnetic surge-front recorder which, with a sche- 22 (a), of a noninductive shunt that carries the main surge
nlatic d&ram, is shown in Fig. 21 is a device for record- current, and across which an inductor is connected.
ing this p;operty of lightning currents. It consists of three Neglecting the resistance of the inductor, its current at
rircuits containing resistance and inductance having dif- any instant is equal to the time integral of the main surge
fWnt time constants. They are connected across an in- current, and, if the surge is nonoscillatory, the final max-
‘lrU:mce carrying the main surge current or a loop in- imum value of this current is the total integral of the main
‘1Uively coupled with the circuit carrying the main surge surge current. To cover a wide range, three magnetic links
Crn’rent. Magnctio links placed within the field of the are placed at different points within the magnetic field
556 Lightning Phenomena \ Chapter 16

18. Photographic Surge-Current Recorder


The photographic surge-current recorders5 is an inst,m-
ment which has been developed to record the multiple
character of strokes and the continuing currents of very
low magnitude (below the 50-ampere sensitivity limit of
the fulchronograph). The instrument is shown in Fig. 23
with a typical record. It employs the principle of photo.
graphing the luminosity produced by flow of the surge cur-
rent, across a short gap. The film image is produced through
0 4000 so00 12,000 16,CCO
(a) TIME -MICROSECONDS a special aperture and set of barriers so constructed that
(b) the light from the gap spreads in a non-uniform manner
Fig. 22-Magnetic surge integrator. over the film perpendicular to its direction of motion. The
(a) Schematicdiagram. barriers confine the image to a narrow wedge in the
(b) Response curve. direction of film motion to enable high resolving power with
time. The width and density of the image provide a mea.+
produced by the coil. The magnetic field that magnetizes ure of current, magnitude. As current is increased, the film
the links is a function of the coil current. Thus from a density is saturated at increasing distances from the ten.
measurement of the remsnent magnetism in the links a ter axis (See Fig. 23). However, at a point just beyond this
record of the total charge in the surge is obtained. The region, the film density can be measured, which together
effect of the resistance of the coil is to limit the time for with distance from the axis determines the current, mag
which the response is an accurate measure of the integral nitude. Current can be measured to an accuracy of about
of surge current. If two coils having different time con- two to one, but over the very greal range of 0.1 to 150 m
stants are used it is possible, in addition to measuring the amperes. The resolving power with time for the inst,ru-
charge, to form some idea of the wave shape. The two ment is 600 microseconds. The film rotates one revolution
time constants are adjusted so that one coil can measure per second; thus, time intervals between separate com-
accurately up to 10 000 microseconds (Fig. 22 (b)) and the ponents can be measured for strokes having total dura-
other up to 300 microseconds. This type of integrator tions up to one second.
forms with the magnetic surge-front recorder and surge-
crest ammeter, a good, inexpensive combination, espe- III. FIELD STUDIES
cially where power is not available.
From the standpoint of the lightning performance of
electrical systems the frequency of occurrence, as well c~9
the magnitude and wave shape of the voltages and cur
rents produced on systems, is important.
19. Frequency of Thunderstorms
Isokeraunic charts have been published showing the
frequency of occurrence of thunderstorms thdbughout the
United States. The total number of storm days (days on
which thunder could be heard) to be expecipd each year-
m different parts of the country is shown in Fig. 24. The
average number of storm days recorded each month over a
40-year period is given in Fig. 25. The data for these
charts for storms in the United States were obtained for a .’
period from 1904 to 1943 by the United States Weather
Bureau.g2 The storm days in Canada (Fig. 24) are based
on isokeraunic charts published by W. H. Alexander.” %”

-‘oo’ooo;
IPI
c% ~0.000
1000
100 - 6600 5000 10.500
Examination of the yearly chart shows an average
number of about 40 storm days per year for all of the
United States east of the Rocky Mountains. There am,%
two pronounced centers of activity, the greatest in Floritaj’$.
t 10 0”RATl0N LESS with more than 90 storm days, the other in New Mexico ? j
.0025 SEC.
L- L with a maximum of about 60. The number of storms !?!?+’
0.1 II 1 I I
7 the Pacific Coast area is considerably low
0 01 .02 .03 .04 .05
TlME IN SECONDS
from 3 to 10.
The month of least storms in the United
Ib) cember, with the center of thunderstorm
Louisiana and with some activity in the Gu
Fig. 23-Photographic surge-current recorder.
Atlantic states. For each succeeding month
(a) Surge-current recorder with cover removed. activity increases throughout the country, spreadi
(b) Typical record. idly in the southeastern states and reaching a pe
Chapter 16 Lightnkng Phenomena 557

Fig. 24-Annual isokeraunic map showing the number of thunderstorm days per year.

most of the country in July, when the number of storms transformers, and the like, of course, should depend to a
per month for all but the Pacific Coast area has reached great extent upon their density of installation and on the
an average of about 9 storm days with a maximum of degree of shielding of the lines.
about 20 in South Florida and 18 in Kew Mexico. By There are also other important reasons. Both local topo-
.4ugust the number of storm days has started to decrease graphical and meteorological conditions appear to cause
and in September it is rapidly decreasing. In the Pacific large localized variations in storm densities. In mountnin-
Coast region the activity is more nearly constant, but has ous regions thunderstorms are generally of the heat or
a slight peak in July. mountain type. Their formation depends on local meteor-
Although these charts do not give an indication of the ological and topographical conditions. Thunderstorms of
intensity, duration, extent, or number of storms occurring, the cold-front and warm-front types depend for their for-
they constitute the best data available. Also, a comparison mation on the interaction of adjacent cold and warm air
of the data obtained by several investigations on the sea- masses, which frequently cover hundreds of square miles.
sonal variation of the number of lightning disturbances Their formation thus does not depend wholly on local
produced on power systems in a given region with the topographical conditions. However, storms of this type,
number of storm days indicates fairly close agreement. which are common to the East and Middle West, appear
That is, the relative number of system disturbances re- to follow more or less defined paths that do depend upon
corded per month varies with the months in practically topographical conditions. Storms of this type sometimes
the same manner as the number of storm days per month. follow rivers and valleys.
An example of this is shown in Fig. 26 for data on distri- For such reasons the number of lightning disturbances
bution-arrester discharge currents.46 However, the number on any one system depends upon its location relative to
of such disturbances varies widely from year to year and local topographical conditions and prevailing storm paths.
for systems in different regions, even though the isokeraunic Thus, it is rather difficult to establish from data obtained
levels of the regions are nearly the same. There are several on a limited number of systems mean figures for the num
reasons for this. The number of surges reaching arresters, ber of electrical disturbances to be expected. The best
available method seems to be to base such data on the
isokeraunic levels and to give as many data as possible
on the range of variance that these localized conditions
might introduce. The isokeraunic level of 30 storms per
year is commonly used for this basis. When considering
data regarding the number of strokes to transmission lines
or the number of surges produced on transmission lines,
one is interested in the number per unit length per unit
time. The common basis used here is the number per
hundred miles of transmission line per year. However, for
*i& 26-Comparison between variance of disturbances considering the lightning performance of such equipment
on systems (solid curve) and monthly isokeraunic levels; as arresters and transformers, the number of disturbances
McEachron and McMorrW. should be based upon the number occurring per unit 01
Chapter 16 Lightning Phenomena 559

tlpparatus per unit time. Tn this discussion, surges in


arresters or transformers are based on the number per
single-phase unit per year.
20. Surge-Voltage Measurements on Transmission
Lines with the Klydonograph
The first important field studies of surge voltages on
transmission lines were begun in 192547 with 26 three-
terminal klydonographs installed on 27 systems varying CREST VOLTAGE LINE TO GROUND IN KILOVOLTS
In voltage from fj.6 to 220 kv. Subsequently, other studies (4) (b) LINE WITHOUT (c) LINE WITH GROUND
GROUND WIRE 1925 WIRE 1926
were begun in the United States.48-52 Investigations also
ll:Lve been made in South Africa and Japan.% At the time Fig. ZS-Klydonograph records of voltages produced by Iight-
thesestudies were started it was thought that induced volt- ning on a particular 120-kv 14%mile line” before and after
:lg:csresulting from strokes in the vicinity of a transmission installation of a ground wire. Ordinates in (b) and (c) give
numbers at a three-phase station. Curves A, B, and C are
line were the primary cause of system flashover. defined in Fig. 27.
In Figs. 27 to 30 are shown percentage distribution
(:tIrvcs of the magnitude of lightning surges obtained from
thrscl studies. These curves give data on voltages that characteristics of the surges probably affect the conclusions.
might he expected at a given point on a line caused by Most of the available data on polarity were obtained with
surges originating at different points along the line. The the normal-type klydonograph having but one element for
voltage is, of course, a function of the insulation level and each voltage measurement. For positive polarity the lower
the wave shape of the surge. The maximum voltage that range of sensitivity is slightly above the normal crest line-
has been recorded was 5 000 000 volts and was obtained by to-ground operating voltage. But for negative polarity
the lower range of sensitivity is two or three times this
magnitude. Thus negative surges of lotv magnitude were
not recorded. Most direct strokes to lines without ground
wires produce flashover resulting in chopped and some-
times oscillatory waves. Short-tail waves are attenuated
much more rapidly than long-tail waves. Available data
indicate that negative waves of this type are attenuated
to voltages below the recording range of the klydonograph
in 4 or 5 miles. Positive surges of longer duration, however,
CREST VOLTAGE LINE TO GROUNO IN KILOVOLTS may propagate 15 or 20 miles before decreasing below the
(a) (b) 100-140 KV (c) 66 KV (d)22-33 KY recording range of the klydonograph. Therefore the dis-
7 LINES 9 LINES 6 LINES tance from which positive surges can originate and still
Fig. 27-Klydonograph records of voltages produced by light- be recorded IS three or four times as great as for negative
ningi7-52 on transmission lines of various voltage ratings, both surges. Consequently the number of positive surges re-
with and without ground wires. corded should be proportional.
~‘IKVW A apply to total lightningsurgeson lines without ground wires.
(‘U~WS I3 apply to surges not producing outages on lines without
ground wires.
(:UI.VPSC apply to to&l lightning surges on lines with ground wires. 160

Pittman and TorokM with a cathode-ray oscillograph from


a direct stroke to a conductor of a IlO-kv wood-pole line
lvithout ground wires. Examination of Figs. 27(a)-(d)
shows that the voltage decreases with the voltage rating
of the line. This probably results primarily from the re-
duction of insulation strength with reduction of operating
voltage. The klydonograph studies indicated that most
surges on lines were unidirectional and of positive polarity
The data in Sec. 27 relating to the currents in lightning
strokes indicate that about 90 percent of all strokes to 40 CREST VOLTAGE IN I(”
Ground lower negative charge to earth. Such negative
strokes produce negative voltages on a transmission line 20
if they strike the line directly but induce positive surges
if they strike in the vicinity of the line. Tn spite of the 0
Predominance of the recorded positive voltages, it does 0 i : : : x
nlr
8
z
not follow that the surges produced on the line at the CREST YOLTAGE IN K;
Point of origin are predominantly positive. The recording Fig. 29-Amplitude and frequency of surge voltages measured
characteristics of the klydonograph and the attenuation by Rokkaku on the Inawashiro lines in Japa@.
560 Lightning Phenomena ,Chapter 16

500 -0 20 40
,c,,.O”OLTS-PRIMIRI W&SE WIRE TO GROUND I,,J,“OLTS-PRIMARY PWASE WlRE TO GROUND

Bib. X0-Lightning
--D- --
surge voltages recorded by Halperin and McEachrofP on 4-kv overhead
circuits of the Commonwealth Edison Company.

Another factor that may color the results drawn from the instruments and the variance of this with polarity,
data of this type is that sometimes switching surges resulting it is likely that the data below the first peaks for both
from the lightning disturbance were recorded instead of the polarities are questionable.
actual lightning surge voltage. However, all switching sur- Fig. 30 shows curves of voltages obtained on both rural
ges that were known to be such are excluded from the data. and urban 4-kv circuits of the Commonwealth Edison
Company.s? These curves indicate that voltages over about
21. Frequency of Occurrence of Lightning Surge 200 kv seldom occur on urban circuits which are much
Voltages
The number of lightning surges recorded at any one
three-phase klydonograph station per year in the studies
conducted in the eastern part of the United States varied
from 15 to about 100 for lines rated from 33 to 220 kv.
These lines were situated in regions having annual iso-
keraunic levels from 25 to 40. The instrument stations
were located at the ends of lines, and since surges originat-
ing at distances in excess of 20 miles are attenuated below
the recording range of the klydonograph the foregoing data
result in estimates of from 75 to 500 surges per 100 miles of
line per year. As shown in Sec. 28 by studies with magnetic
links.55 the number of direct strokes to be expected to
lines’in this class in regions of this isokeraunic level is from z 600
i
50 to 250 per 100 miles of line per year, with an average -
of about 100. Thus the klydonograph data indicate that
Time
approximately half of the significant surges are produced -
Rate of
by direct strokes. Since those strokes that induce voltages
are about equal to those that strike the line, and since Surge Po-
Rise, ro 2
Kv Crest Kv Max
the line attracts strokes only from within a narrow band SO. larity Per To Crest,
Volt-
adjacent to it, then those indirect strokes that produce psec psec
age
surges must strike the ground close to the line. This has P=C
been verified” by a stroke observed to have struck ground _- _-
200 feet from a transmission line of the Public Service a Neg. 143 Unknown; 7 psec to
Company of New Jersey and 1600 feet from a lightning- 1000 1000 kv
recorded
recording station on the line. No surge voltage was recorded 5 \, 33
Neg. 183 750
in this case, although klydonographs and a cathode-ray Neg. 270 550 6 \ 26
oscillograph were in operation at the time to record voltages Pos. 137 325 3 4
on the phase wires. PO% 30 180 5 15
In general, induced voltages, since they seldom exceed Pos. 45 30
500 kv, rarely produce outages on 66-kv or higher-voltage Neg. 167 160 2.5 8
lines. As the operating voltage of the line decreases the 1 Pos. 500 - 1000 2 43
insulation also decreases and induced voltages may produce
‘Trafford Laboratory Test.
outages. 1. - I^
In Fig. 29 are shown data obtamed m Japan” on a Fig. 31-Typical lightning surges recorded with
154-kv line. Because of the lower limit of sensitivity of oacillograph.@.
Chapter 16 Lightning jPhenomena 561

better shielded than the rural circuits where the upper


limit of voltages appears to be about 500 kv. Curves also
arc plotted in this figure showing the probability of surge
voltages of different magnitudes reaching transformers.
22. Surge-Voltage Measurements on Transmission
Lines with the Cathode-Ray Oscillograph
Studres with the cathode-ray oscillograph of voltages
produced on transmission lines were begun in 1928. The

-6OO-

Y) -6OO-
5
2 -4oo-
-'
x -eoo-
10 I5 20 25 30 35 40
MltROSECONDS
+200-

,400 _
(b)

Fig. 32-Cathode-ray oscillogram of highest voltage recorded


on a transmission line;” IlO-kv wood-pole line of Arkansas
Power and Light Company; no ground wire.

relatively few oscillograph stations that could be estab-


lished did not permit of obtaining many records. In addi-
tion, interpretation of the records was difficult because
of the influence of such unknown factors as propagation,
distortion, and reflection. However, some valuable quali-
tative and quantitative information has been obtained
from these studies. Some of the more important oscillo-
grams are shown in Figs. 31 to 37.
In Fig. 31 are seven oscillograms obtained in the West- W
inghouse studies.58 All were obtained on steel-pole lines,
Fig. 34-Group of cathode-ray oscillograms of line voItage
most of which had ground wires, and the surges originated taken on the Wallenpaupack lineon.
at appreciable distances from the recording equipment.
(a) First cathode-ray oscillogram of a lightning surge on a trans-
They indicate fronts of from two to seven microseconds mission line. The oscillations were caused by flashover on an
and rates of voltage rise as high as 270 kv per microsecond. adjacent phase.
For comparison, an approximate standard lxx40 test (b) Dead-end protective gaps flashed over on all three phases,
wave’is also plotted. The surges of larger magnitude have causing a sharp change in voltage from 1260 kv negative to 310
tails conforming closely to that of the standard wave. kv positive in one microsecond. Flashover took place on front
The surge of highest voltage recorded on a transmission of wave.
line is shown in Fig. 32. It occurred on a IIO-kv wood-pole (c) Record obtained while line was not energized. Voltage was
line without ground wires of the Arkansas Power and Light still rising at the end of 36 microseconds and was then sud-
denly reduced to zero. Subsequent examination of the line
indicated a flashover 23 miles away, which appeared to cor-
relate with this oscillogram.
(d) The slightly oscillatory nature of this oscillogram is typical of
a large group of waves. A cloud-to-ground stroke, at least ten
miles distant from the Yaboratory and some distance from the
line, was seen at the instant this record was obtained.

Company.54 The oscillograph was located about four miles


from the point where the line was struck, and flashover
-2000
occurred. This voltage wave has a maximum rate of rise
-2500 of 4000 kv per microsecond.
In Fig. 33 is shown the only oscillogram obtained from
-3000
a direct stroke close enough to the recording equipment
Fig. 33-oscillogram of lightning surge voltage measured at that the wave shape before flashover occurred is not dis-
point of origin”. torted by propagation. This oscillogram was obtained by
562 Lightning Phenomena

Bell and Prices” on a section of a 220-kv steel-tower line


without ground wires of the Pennsylvania Power and Tdght
Company. Flashover occurred 125 feet from the oscillo-
graph on the phase to which it was connected, an outer
conductor of a horizontal single-circuit configuration. The
insulation level of the line is about 1300 kv and the voltage
reached 2800 kv before flashover took place. The interval
between the time when the voltage was high enough to
operate the oscillograph and flashover occurred was about
six microseconds.
The front of this surge is interesting. The voltage rose
relatively gradually for more than three microseconds to
about 500 kv. It then increased much more rapidly to
the flashover voltage in about two microseconds, with an
average rate of rise in this interval of about 1300 kv per Fig. 36-Cathode-ray oscillogram of voltage due to natural
microsecond. The relatively slow portion of the front is lightning showing effect of propagation and reflection.@*.
probably voltage produced before contact of the stroke
to the phase wire by the advancing stroke leader. Upon age and of surges originating quite a distance from the
contact of the stroke the voltage rose rapidly until flash- oscillograph station.
over took place. The nature of the front of the voltage An interesting oscillogram which shows the effect of
wave produced on phase wires is probably influenced by reflections is given in Fig. 36. This record5* is of the
ground wires. For lines with ground wires the initial slow voltage on a phase wire induced by a stroke to another
component of the front will not be so marked. phase wire and three miles from the oscillograph station.
In Fig. 34 is shown a group of oscillograms obtained by The wave front increased at a rate of 143 kv per micro-
the General Electric Company.Gu Fig. 34(a) is of interest second to a magnitude considerably beyond the oscillo-
because it is the first cathode-ray oscillogram obtained of graph range. At approximately 12 microseconds flashover
occurred to the adjacent conductor reducing the voltage
on the conductor to which the oscillograph was connected.
MICROSECONDS
The recorded voltage rose to 1000 kv after which it decayed
to 600 kv in 55 microseconds. At this time the negative
+3oor
v) 200.
2000 2400
MICROSECONDS

fz$Iv
MICROSECONDS -3oo-

Fig. 37-Cathode-ray oscillogram of voltage due to natural


-2.v
lightning which shows the prolongation of the disturbance as
a result of successive reflection@. ’

4812 20 32 40
MICROSECONDS
reflected wave arrived from the far end of the line, a die
tance of eight miles from the oscillograph, where it had
flashed over a noninductive resistance, thereby modifying
the original tail of the wave as shown. This illustrates the
typical effect of reflection on the tail of the wave.
These cathode-ray oscillograph studies led to the conclu-
sion that the original voltage produced by the lightning
Fig. 35-Group of cathode-ray oscillograms of lightning volt- stroke does not persist longer than 200 microseconds, but
age on transmission lines obtained by George and Eatone2.
that successive reflections from different parts of the sy*
tern may spread the disturbance out to as much as several
a natural-lightning transient. Figs. 34(b)-(d) are typical thousand microseconds. Fig. 37 shows oscillograms illus-
of the three groups into which the 16 oscillograms exceed- trating this effect obtained by Bell and Price.ss The long-
ing 300 kv recorded by Smeloff and Price”’ may be classified. duration low-current components of lightning surges, later
Figure 34(b) is typical of records in which flashover occurs found to be present, were not recorded. However, they a*
close to the recording equipment; Fig. 34(d) of voltages not important from the standpoint of voltage insulation. $
too low to cause flashover, but which are distorted by both ,&$3
propagation and negative reflections. The reversal of volt- 23. Current Measurements
age is caused by such reflections, and the sloping off of the While the voltage on a transmission line is fundam
front results from propagation and reflections. in determining whether an insulator string, gap, or arr
Fig. 35 shows a group of oscillograms published by flashes over, it is difficult to determine what the voltag
George and Eaton. 62 They all are of relatively low volt- would be on the line if the insulation did not fail. Howevflj
Chapter 16 Lightning Phenomena 563

currents are not influenced to as great an extent by flash- 17. Collins? who used paper-gap recorders to measure dis-
avers. In addition, currents are important in their bearing charge currents in arresters on a 24kv system.
,,n the mechanical stresses and thermal effects set up in 18. Wagner, McCann, Bowen, and Beck65.a6*Mwho measured
nrotective devices and other equipment. For this reason the discharge currents in arresters by means of the fulchrono-
graph, magnetic surge-front recorder, magnetic-surge integrator,
most of the investigations during the past 17 years have
and surge-crest ammeter.
b(:en devoted to the determination of the current char- 19. Gross, McCann, and BeckR3who measured discharge cur-
actcristics of lightnjng strokes. These investigations can rents in arresters by means of the cathode-ray oscillograph.
\)c given three classifications: fulchronograph, magnetic surge-front recorder, and surge-crest
(a) Strokes to Open Ground and Tall Buildings. ammeter.
These comprised the following investigations:
1. Schonlnnd, hlalan, Hodges, and Collensr3+ in South
24. Multiple Character of Strokes
,lfrica who studied the mechanism of lightning with the Boys In Figs. 35 to 40 are plotted curves giving statistical data
camera and by measurement with the cathode-ray oscillograph on the number of components, the time intervals between
of the electric field produced by strokes. them and the total duration of strokes. These curves
2, Stekolnikov and ValeeP in Russia who measured, with
the cathode-ray oscillogrnph and high-speed rotating klydono- w;:
graph, currents in strokes to captive balloons flown to altitudes :g
between 500 and 800 meters and voltages induced in a short t-m
g 9 100
horizontal antenna by strokes to ground. w>
3. McEachrorP~ who measured currents in strokes to the -‘m 90 MCCANN 8 BECK”
$2 w ARRESTER DISCHARGES
Empire State Building in New York, N. Y., with the cathode- 60
31 PHOTO-RECORDER RECORDS
-2
ray and crater-lamp oscillogrnphs and the surge-crest ammeter. 3a 70 228 FULCHRONOGRAPH RECORDS
4. NorindeP in Sweden who measured with the cathode-ray TV)
a+
xt 60
oscillograph the magnetic fields produced by lightning-strokes. fnw
5. Wagner, McCann and Beck8S*85who measured with the yg 50 OF STROKES TO
(65 STROKES)
fulchronograph, magnetic surge-front recorder, surge-crest am- 8% 40
meter, and magnetic surge integrator, the currents in tall objects ti*g 3.
of different heights. :% 20
(b) Strokes to Transmission Lines. These include the fol- 5K
s; IO
lowing investigations made with the surge-crest ammeter: k-55 0
8.2
6. Lewis and Faust? who measured surge currents in trans- NUMBER OF COMPONENTS IN STROKE
mission-line towers, ground wires, counterpoises, and tower (a)
masts.
7. Waldorf and Hansson55,8r who measured surge currents in uz
tower legs. c-5
g p too
8. Be11c7*68who measured currents in tower legs and cross aa
braces and in counterpoises. 5; 90 STEKOLNIKOV a VALEEV*’
25 INOUCED SURGES
9. Grnnewaldti~ in Germany who measured current in towers. !Iis 80
10. Itokkaku and Katohj”*‘o in Japan who measured currents -9 70
MC CANNe5 DIRECT STROKES
zz
in tower legs and ground wires. 46 DIRECT STROKES
& 60
11. Antlrews and McCannS* who measured surge currents on 138 PHOTOGRAPHS
\vood-pole lines. 695 50
uz
go 40
In addition to the foregoing are the following investigations (La
kg 30 PROTECTOR TUBE SURGE?
made with other instruments:
g: 20
12 McEachronrl who measured with the crater-lamp oscillo- co IO
graph currents discharged by protector tubes on transmission $5
Bi 0
lines. 0 2 4 6 8 IO I2 14 I6 I6 20 22 24 26 26 30 32 34
13. BergeP m . Switzerland who, besides measuring trans- ow1 NUMBER OF COMPONENTS IN STROKE
mission-line tower-leg currents with the surge-crest ammeter, --@I
recorded their maximum rate of rise with klydonographs induc- Fig. 38-Percentage distribution curves of the number of
tively coupled with the tower legs. components in lightning strokes.

(c) Arrester Discharge Currents. The following investi-


gations were made with surge-crest ammeters: represent data on strokes of three general types: (1) strokes
to power systems as given by the protector-tube and ar-
14. -McEachron and McMorris48 who measured discharge cur- rester data; (2) strokes to open country as given by the
rents in distribution arresters on 120- to 20 OOO-volt systems. photographic records and the data on induced voltages;
15. Gross and McMorrisr3 who measured discharge currents (3) strokes to tall objects. With regard to number of com-
ia station-type arresters on 1l- to 132-kv systems. ponents and total duration, there is a fair check between
16. Grunewald?’ in Germany who measured arrester currents
the curves of each type, but there are important differences
on systems frotn 6 to 100 kv.
between the types. More components and longer durations
In addition to the foregoing are the following investigations are recorded for strokes to tall objects. This is probably
made with other instruments: because tall projections from the earth affect stroke mech-
:g
564 Lightning Phenomena ,Chapter 16 ,$
G,
recorded is 10. From one-half to two-thirds of the strokes
to open country are multiple and as many as 40 components
have been photographed.20
Fig. 39 indicates time intervals as high as 0.5 Second
between components. In Fig. 39(b) the basis of 100 percent
was taken at a time interval of 0.01 second as the resolving
power of some of the measuring instruments did not extend
below this time. Only about a sixth of the intervals are
less than one-half cycle of 60-cycle frequency.
25. Crest Magnitude of Currents
Extensive studies have been made both in the United
States and abroad with surge-crest ammeter links on trans-
mission lines and in ground leads of lightning arresters.
Fig. 39-Percentage distribution curves of time intervals be- Most of the measurements on transmission lines have been
tween the beginnings of successive components of multiple
lightning strokes. of currents in the legs of towers, although they have also
been made of currents in ground wires, phase wires,
anism and cause strokes t,o them to differ in character counterpoise wires, and masts mounted on top of towers,
from those to ground or to lower objects. Tall objects Transmission-Line-Tower Currents-The curves of
should influence a greater region of the thundercloud and Fig. 41, showing the magnitude of currents in transmission-
thus tap more charge centers, causing strokes to have more 100
components and longer durations. Of practical importance
is the indication that the records to power systems have 90 IIL /GRUNEWALD6’(1689 RECORDS)
fewer components and shorter durations. This results
probably from the diminution of the surge current by the
following causes: (1) All of the direct-stroke current is not
likely to pass through a protective device because more LEWIS 8 FOUST” (2721 RECORDS)
than one may operate, thus dividing the current, or flash- iz
overs may occur on the lines thereby limiting the discharge : 2 60
current; (2) the protective device may be operated by !z ANDREWS 8 M&ANN”* (147 RECORDS)
attenuated surges from strokes to the system at remote
points; (3) the protective device may be discharged by
HANSSON B WALDORF”(1987 RECORDS)
induced surges. Thus some of the smaller components of
current may have been reduced to such an extent that they ROKKAKU 6 KATOH” (60 RECORDS)
are below the recording range of the instruments, or have
voltages associated with them below the operating voltage
of the protective device. Arresters and other terminal
equipment are therefore exposed to less severe duty than
is indicated by the results from direct strokes or strokes to
open country. Only about a third of power-system surges
are multiple and the maximum number of components
CREST CURRENT IN KILOAMPERES
Fig. Il-Percentage distribution curves of tower currents for
strokes to transmission lines.

line towers, were compiled only from the currents in the


tower thought to be close to the terminating point of the
stroke or the tower carrying the most current. The char-
acter of the curves is influenced by the minimum current
that could be measured due to the sensitivity limit of the
links and the minimum different investigators thought it
advisable to include in their data. These minimum values
affect both the point regarded as 100 percent on the
ordinate and also the shape of the curve. The minimum
tower currents included in the data of Hansson and Wal-
dorfs7 were about 2400 amperes for Bells* and Grunewald” ,i,.
about 5000 amperes, and for Andrews and McCannss about G
600 amperes. The curves of Lewis and Faust? comprise
TOTAL DURATION IN SECONDS some of the data of Waldorf and Bell plus data obtained on
Fig. IO-Percentage distribution of total duration of lightning other lines in the United States. However, 5000 amper
strokes. was the minimum considered by them.
Chapter 16 Lightning Phenomena 565

Before drawing any conclusions from these curves it is Roklraku’O and Schahfer and Knutz75 made studies in
!vell to consider their probable accuracy. The majority of which they measured the main leg rlrrrents and the differ-
the magnetic-link measurements of steel-tower currents ence between the ground-wire currents on each side of
lvere made on only one leg of the tower, the total current the tower. Assuming this difference to be the total tower
being assumed to be this measurement multiplied by the current gives an indication of the discrepancy between
number of tower legs. Records obtained with links on all the total tower current and the sum of the leg currents.
taxer legs indicate that frequently currents are not equally Their results are summarized in Fig. 43, which indicates
distributed. Data obtained by Waldorf, shown in Fig. 42 that this correction factor should increase with the mngni-
tude of the tower current. The curves of Fig. Al, so far
“T-l as the authors are aware, do not take this correction factor
into consideration and are plotted simply as the sum of
the four tower-leg currents.
Direct-Stroke Currents-Fig. 44 gives percent dis-
tribution curves for direct strokes as a function of the

‘ooli-r STROKES TO TRANSMISSION LINES


I LEWIS AND FOUST” 2721 RECORDS
2 GRUNEWALD” 654 ”
SUM OF TOWER CURRENTS IN KILOAMPERES 3 WALDORF55 500 -
4 ROKKAKU’O’ 30 y
Fig. 42-Deviation from equal division of lightning current in 5 ANDREWS R McCANNB8147 11
tower legs, as obtained by Waldorf% from 209 records.
STROKES TO ALL OBJECTS
30 RECORDS
indicate the mean deviation of an individual tower leg from 46 RECORDS
the mean of the four supporting legs. This deviation ap-
CALCULATIONS FROM MAGNETIC
pears to decrease as the sum of the four tower-leg currents
FIELD MEASUREMENTS
increases, being about ten percent above 40 000 amperes. 204 RECORDS
Factors that might cause such discrepancies are dissym-
metry in the counterpoise or other type of grounding or
in the tower itself. These factors might even result in
differences in wave shape of the component currents. In
addition, there are the possible errors of the recording
equipment, particularly at low currents. It is probable,
however, that some of these effects are minimized by the
quantity of data making up the statistical averaging of
CREST CURRENT IN KILOAMPERES
several hundred records.
Data obtained by Belle7 who also measured the currents Fig. 44-Percentage distribution curves of lightning-stroke
in the tower cross braces show that appreciable current currents.
flows in them. His results indicate that a correction factor
varying from 1.64 to 2.75, with a mean of about 2, should crest magnitude. Curves 1 to 3, which are for strokes to
be applied to t,he tower-leg current readings for his records. transmission lines, were obtained by adding the tower-leg
Lewis and FousP say that from 30 to 100 percent of the currents in all the towers thought to,be involved in the
main leg currents flowed in the cross braces. stroke. Errors introduced by this procedure are the follow-
ing: First, the sum of the tower-leg currents may be less
than the total tower current; second, the effects of more
28 O SCHAHFER” (24 RECORDS)
than one stroke might be involved in summing the currents
132 K” LINES OF NORTHERN of different towers; and, third, because of distortion .as the
26 INDIANA PUBLIC SERVICE CMIR
result of reflection from other towers, the sum of the crest
24
XROKKAKU70f30 RECORDS) currents at the towers will not equal the stroke current.
2.2 154 KV LINE OF TOKYO
ELECTRIC LIGHT CO. IN JAPA
The first item tends to indicate a low value of stroke
20 current, and the second and third a high value. Rokkaku
1.6
in comparing the results of stroke measurements obtained
by summing the ground-wire currents on both sides of the
terminating point of the stroke with the results obtained
by summing the tower currents found that the two agree
where the correction factor of Fig. 43 is included. Their
Curve 4 of Fig. 44 takes this factor into consideration.
CREST CURRENT IN KILOAMPERES However, Lewis and Foust in data presented in Fig. 45
Fig. 43-Relation between total tower lightning current and showed substantial agreement between stroke currents and
sum of main tower-leg currents in transmission-line steel sum of tower currents without including the correction
towers. factor of Fig. 43. The effect of this factor may be reflected
,I

566 Lightning Phenomena Chapter 16 ”


I

The direct-stroke curve of Fig. 46 gives the percent


distribution of the crest magnitude of the individual corn.
ponents of direct strokes to objects varying in height from
300 to 585 feet. A comparison of t.his curve with Curve 7
of Fig. 44 shows a larger proportion of small currents for
the former. This is because only the maximum components
of the multiple strokes were included in Curve 7 of Fig. 44.
The curves of Fig. 46 are probably more representative of
conditions for judging arrester performance.
Crest currents as high as 220 000 amperes are indicated
for strokes to lines. However, since these were obtained by
w I I 0Ya.1
I2 0 I
Y 0 20 40 60 SO loa 120 140 160 160200 220
STROKE CREST CURRENT IN KILOAMPERES
%
CR”NEWALD6%RRESTERS IN GERMANY
Fig. 45-Lewis and Foustfie stroke-current curve compared (222 RECORDS)
with currents from lightning-rod measurements (circles) and
overhead ground-wire measurements (triangles). CEACHRON AND MWORRIS46
DISTRIBUTION ARRESTERS
(1608 RECORDS)
in the comparison between Curves 1 and 4 of Fig. 44, in
that Rokkaku’s is greater than Lewis and Foust’s. S?ARRESTERS ON 24 KV.
POLE LINE (499 RECORDS)
Fig. 44 also contains data relating to strokes to tall
objects, that of McEachron being to the 1250-foot Empire
AND DISTRIBUTION
State Building in New York, N. Y. The curve of McCann ESTERS (76 RECORDS)
represents data to objects of varying heights all of which
are considerably lower. Neither of these curves involves
the errors discussed previously as the total stroke current
passed through a single conductor. A comparison of Mc-
Eachron’s curve data with those of strokes to transmission
lines indicates a much greater proportion of currents of
low magnitude. This may be caused partly by the higher
sensitivity of McEachron’s instruments but more likely by
I8 20 22 24
the difference in mechanism of strokes to tall objects and 2 4 6 B IO I2 14 16
CREST CURRENT IN KILOAMPERES
the influence of tall projections from the earth in producing (a)
premature initiation of discharges.
Curve 8 of Fig. 44 was calculated by Norinder from a .“”

knowledge of the magnetic field disturbance produced by 80 STATION ARRESTEdS I


a stroke to open ground. An evaluation of the accuracy 60
BOWEN 8 BECK” (90jRECORDS)
of this curve is difficult because it involves an assumption
as to the stroke mechanism, distance to stroke, and direc- MCCANN R BECK” (226’RECORDS)
\
tion and length of stroke path.
LEWIS Et FOUST6’ (124 RiCORDS)
2 GROSS, MCCANN a BECK”
9 IO (49 RECORDS)
~100 I I I11111 I Ill1 8
2 MCCANN 8 BECKa 6
L 90 III

a 40
I
2 30 IRECT STROKES
(135 COMPONENTS1
8 McMORRIS4’
I u I I
(1608 RECORDS)
.2 I I I
0 2 4 6 8 IO 12 14 I6 I8 20 22 24
CREST CURRENT IN KILOAMPERES
CREST CURRENT IN AMPERES (b)
Fig. 46-Percentage distribution curves of crest magnitude of Fig. 47-Percentage distribution curves of discharge CUfle
individual components of surge current%. in lightning arresters.
Chapter 16 Lightning Phenomena 567

&ing currents in several towers they may be high. The of strokes to transmission lines were of positive polarity,
highest current definitely known to have occurred some- while Waldorfs5 found 18 percent and Grunewsld,6g 14 per-
,&at exceeds 160 000 amperes, recorded at the Westing- cent. Waldorf’s figure may be higher t,han the others be-
house recording station on t,he 585-foot smokestack of the cause his data comprised lower currents. If this is true, a
Xnaconda Copper Mining Company in Anaconda, Mont. higher percentage of the lower-magnitude currents should
Arrester Currents-Crest magnitudes of arrester dis- be positive. This is borne out in the curves of Fig. 49
charge currents, summarized in Fig. 47, are considerably
sm:Jler than those occurring on transmission lines. Those PERCENT OF
in station arresters, in general, are smaller than those STROKE TO
TRANiYISSION LINES
POSlTl”E 10
TOTAL SURGES
“ccurring in distribution arresters. The maximum crest LEWIS AN0 FOUST66 7
16
current measured in station arresters is 15 000 amperes and A:,
WALDORF”
GRUNEWAL069 I,
in distribution arresters approximately 30 000 to 40 000 ARRESTER SURGES
0lSTRlS”TlON ARRESTERS l6 37
amperes. The latter figure has been estimated since the STATION ARRESTERS” 12
maximum range of the recording instruments was 25 000
amperes. Other data pertinent to the magnitude of arrester
discharge currents are discussed later.
26. Charge
Wilson9 has estimated that the average charge lowered
t)y a discharge to open ground is from 10 to 50 coulombs.
Fig. 48 gives data on charge for strokes to the Empire SURGE CREST CVRRENT IN KILOAMPERES

Fig. 49-Percentage distribution curves of positive surges as a


function of current magnitude.
EMPIRE STATE BUILDING-NEW YORK CITY
1937, 1936, 1939. 1940
plotted from Waldorf’s and Grunewald’s data showing the
percentage of total positive currents as a function of mag-
nitude. At the minimum of 1000 amperes Waldorf’s data
show that about 35 percent of the records are positive, and
Grunewald’s, with a minimum of 5000 amperes, show
about 24 percent.
Possibly currents as great as 5000 or 10 000 amperes can
be produced in towers by induced strokes, and they may
be the cause of the higher percentage of positive records
0
20 40 60 60 100 120 140 160 160 in the lower current range.
CHARGE IN COULOMBS
The studies of McEachron and McMorris show that 63
Fig. 48-Frequency of occurrence of stroke charge as meas- percent of all their records of currents in distribution ar-
ured by McEachron,W based largely on low-speed oscillo- resters are negative and 37 percent positive, while Gross
graphic data. and McMorris found that for the station arresters 88 per-
cent were negative and 12 percent positive. The curves
State Building by McEachron, which indicate values in of Fig. 49 plotted from these data show that for station
csccss of 160 coulombs. In the investigations of Wagner, arresters, the polarity is independent of current magnitude
McCann, and Beckfi5charges in direct strokes to tall objects while for distribution arresters the number of positive
of lower height ranged from 4 to 60 coulombs. Probably discharges decreases with increase in current magni-
on the average the charge lowered increases with the height tude.
of the object. Charges exceeding one coulomb were found It is interesting to compare these results with the voltage
to be rare for arrester service. measurements made on 4-kv distribution circuits by Hal-
perin and McEachron, the results of which are shown in
27. Polarity Fig. 30. If these voltages had appeared across 4-kv arresters
Direct strokes of a given polarity produce surges of the with an impulse breakdown voltage of about 40 kv, the
same polarity, but induced surges are of opposite polarity. voltage curves for urban circuits indicate that 22 percent
Schonlnnd, Hodges, and CollinsJ7 state that all their electric of the arrester discharge currents would have been positive,
field measurements indicated negative-polarity strokes; and the curves for rural circuits indicate a figure of about
that is, they lowered negative charge to ground. All 58 35 percent. If these voltages had appeared on a 20-kv
strokes recorded to the Empire State Building were initially circuit with arresters having an impulse breakdown voltage
negative; only 3 of the 27 recorded with the crater-lamp of about 75 kv, no positive discharge currents would have
oscillograph reversed their polarity. Of the 12 direct strokes been produced by the urban circuits and 27 percent would
recorded by Wagner, McCann, and Beck65all were initiated have been produced by the rural circuits. The increase in
hi negative discharges. Only two had subsequent positive positive discharge currents recorded in distribution arrest-
components. ers probably is due to induced surges. Quite likely they are
Lewis and Faust@ state that 7 percent of their records greater on the lower-voltage circuits,66 and greater the
568 Lightning Phenomena Chapter 16

TABLE 1 -DATA ON STROKES TO LINES OF THE PENNSYLVANIA TABLE ~-OUTAGES DUE TO LIGHTNING FOR LIN&S WITHOUT
WATER AND POWER COMPANY~,~~
- GROUND WIRES
,,is
ength
-T- Recorded
Strokes
-I- Strokes
‘er 100 hIiles* ! iears rOt:il
jutages
Per l@J
.F;c
;<
F8
Line in Year - Length
Kv ZOV- Out- Miles a
\Iiles In rcLver. In Aver- Line If Line
em1 ages Per ;
> ‘ear age rear age Line.
--
1935 115 125 Year
1936 LO8 118 Interstate Power Co.,
Safe Harbor-Westport- 1937 87 95 Clinton-Dubuque’*. 66 6 277 87
Takomn, 220 kv. . 1938 54 59 Pa. Water & Power Co.‘9
1939 118 129 Holtwood-York’g. 66 23 11 213 84
‘ik 05 (95) Various lines in Unite1 ;
Safe Harbor-lliverside, 1938 46 ‘ii States and Canada*
220 kv.. . l!XN 45 89 16-A, wood. 110 79.4 6
‘&j‘ 90
24
20-A, steel. 140 148.0 10 5.6
31.5 27 86 23-BB, wood.. 132 39.8 8 37.2
31.5 1938 69 219 31-B, steel.. 132 111 .o 1 0
Safe Harbor-Perrys- 31.5 1937 44 140 34-K, steel. 110 38.3 10 Gl
ville, 132 kv.. 33.8 1938 56 166 34-0, steel. 110 104.5 10 22.8
33.8 1939 53 157 Steel**. Abov 673 1929 21
50 L54 (135) 100
1936
1937
31
41
I’
136
180
Wooda*.
Steela2.
cio-101
fio-10’
560
394
481
1930
1929
1929
14
26.6
23.5
IToltwood-York, 66 kv 22.8 1938 15 66 738 1930 25.9
1939/ 22 97 Wood** :IO- 6 3 475 1929 34.G
27 120 (119) 420 1930 30.4
1936, ‘36 102 Steels2 :10- 6 I65 1929 17.6
Ifoltwood-Coatesville, 1937 25 85 128 1930 14.2
GGkv. .. 1938 68 232 Pa. Power & Light Co .1

IIoltwood-Baltimore, 40
1939I 45
‘ii’ I.
153
143 (123)
steeF’. I 220 41
6’For numbered references see list at end of article.
*See Table 1 of the Appendix.
8I: z 25

66 kv (2 lines) ant (of


Philadelphia Road right ‘193CI 66 66 165 165
Gunpowder, 110 kv. of- 113 to the conventional standard isokersunic level of 30
nay) -I results in 97, or about 100 strokes per 100 miles per year.
U’eichted ~wwpe for all lines throuph 1939 is 120 strokes per 100 mile-years Additional information is provided by available light-
having mnvnitudev Riving tower currents in excess of 2400 amperes.
*Fiuuws in parentheses DR awrnges extending through 19428’ and represent 1364 ning outage records of lines without ground/wires. Data
rrde-years of experience. of this nature are summarized in Table 2. The lines listed
System areraze strokes per 100 miles of line per year is 113 for five obserred
lines totaling 1617 mile-years of experience. in this table are in regions with annual isok t raunic levels
ranging from about 30 to 55, and the data ‘give outages
more exposed the lines, thus permitting higher magnitudes varying from 15 to 87 per 100 line-miles per year, with an
of induced surges. average weighted according to length of from 30 to 35.
All strokes to lines do not produce flashover, and all
28. Number of Strokes to Transmission Lines flashovers do not produce outages. Data published by
Of particular importance in evaluating lightning per- BelP’ indicate a ratio of 1.5 between the number of strokes
formance of a transmission line is knowledge of the prob- producing flashover and those producing outage on the
able number of strokes to it. Hansson and Waldorf55.87 portion of the 220-kv Wallenpaupack-Siegfried line of the
present valuable data on this subject from surge-crest am- Pennsylvania Power and Light Company that does not
meter studies on lines of the Pennsylvania Water and have ground wires. Information supplied by I. W. Gross
Power Company with voltage ratings ranging from 66 to on the 132-kv lines of the American Gas and Electric
220 kv, as magnetic links were placed on every tower. Company (which have ground mires) indicates
These data for the first five years are summarized in Table 1 1.27. This ratio probably varies with the syst
and show a maximum variance in the number of strokes higher the longer the flashover path and the lower
per 100 miles of line per year of from 59 to 232. The max- current. An estimate of the number of strokes p
imum variance for any line over the eight-year period flashover on a given line without ground wires ca.n
studieds7 was from 48 to 232 and the variance of the aver- obtained from, say, Curve 3 of Fig, 44, together wit
age for each line over the eight-year period was from 95 to knowledge of the surge impedance of the iine and its
135 strokes per 100 miles per year. The weighted average sulation level. The voltage produced by a stroke to a
.of the data according to length of line and years considered conductor should be eclual to the product of on
,is 113. These lines are located in a region with annual iso- stroke current and the surge impedance of the CO
keraunic levels from 35 to 40. Converting the figure of Estimates of the probable mean ratio between out
Chapter 16 Lightning Phenomena 569

other factors such as line locations cause a greater variance.


120
Thus the average value of 100 should apply to all practical
values of tower height.
It is then possible to plot Waldorf’s percentage distri-
bution curve in Fig. 44 as a probability curve giving the
number of strokes of a given magnitude to be expected.
This is shown in Fig. 51 with the corresponding curve of
Lewis and Foust which is Curve 1 of Fig. 4-l. The prob-
ability curve used by Harder and Claytong for estimating
line performance is also given in Fig. 51. This curve is
essentially based on the data published by Waldorfs5 except
that it has been modified slightly in the high-current re-
gion. The data of this figure are on a line basis and not a
circuit basis; the number of strokes to a line is independent
of the number of circuits comprising it.
a
0 40 60 120 160 200 29. Number of Surges Discharged by Lightning Ar-
TOWER HEIGHT IN FEET resters
Fig. 50-Probable variation of strokes to line as a function of Fig. 52 shows curves compiled from the data of Gross
height.7e and McMorris73 and McEachron and McMorris46 on the

strokes to lines without ground wires for the lines listed in


Table 2 indicate a mean value for strokes to lines of about
GOper 100 line-miles per year. This is, of course, only an
estimate, and probably t,he figure of 100 based on Waldorf’s
data should be used in a region of isokeraunic level of 30.
Lightning-performance studies of lines made in the lab- AVERAGE OF ALL DISTRIBUTION ARRESTERS46
oratory with models by Wagner, McCann, and NIacLane76
+ ARRESTERS IN46
indicate that the number of strokes to the line is a function .OS
of tower height as shown in Fig. 50. However, no such
t,rend is shown in Waldorf’s data. This is probably because .04

I”” .02 L
80 \
60 \\
.Ol I

CREST CURRENT IN KILOAMPERES


aa 8
kc” Fig. 52-Curves showing number of surges of given magni-
,^ . 6
tudes that arresters discharge per year.

0 40 80 120 160 200 I


CREST CURRENT IN KILOAMPERES N”wER OF SURGES PER SlNG‘E
PHASE ARRESTER PER YEAR
F’*g. 51-Probability curves of crest currents in lightning Fig. 53-Distribution of duty on station arresters: data from
strokes to transmission lines. Gross and McMorrisr3 on 85 three-phase banks for four-year
*aged on 100 strokes to line per 100 miles of line per year. period.
570 Lightning Phenomena Chapter 16

curve of Fig. 54 indicates more discharges. This may not


be typical of duty on an average group of arresters, as the
90 MCCANN a BECK”
locations were chosen because experience indicated that
ARRESTERS IN STATIONS they were subject to severe lightning conditions.
80
(13 3.5 ARRESTER YEiRS) The effect of line insulation on arrester duty is shown in
I I I Fig. 55. Wood-pole lines with no ground wires, as would
DISTRIBUTION ARRESTERS be expected, produce more severe duty.
60 (160 ARRESTER YEARS)
I I I I I 30. Wave Shape of Lightning Currents
An inherent difficulty in measuring the total current in
direct strokes is the necessity of obtaining a point at which
the current is totalized. This has led to collecting the
current in a single mast. If, however, these masts are on
low objects such as transmission towers, the chance of a
particular point being struck is small. On the other hand,
if tall objects such as buildings and smoke stacks are uti-
lized, more records for a single installation can be obtained
but it is always uncertain how much such strokes differ
I I I I I I I 1 I 1 I
‘0 I 2 3 4 5 6 7 8 9 IO from those to lower objects, as dealt with in the power-
NUMBER OF SURGES PER INDIVIDUAL ARRESTER PER YEAR
transmission problem. It is known, for example, that the
initial streamers, the direction of propagation, and other
Fig. 54-Duty on individual arresters from data obtained by vital characteristics differ in the measured discharges at
McCann and Beck.8B the Empire State Building from those elsewhere. In spite
of these uncertainties, most direct-stroke data have been
expected number of surges of a given magnitude to be obtained on tall objects.
discharged per single-phase arrester per year. The curves Stekolnikov and Valeev22 in Russia in 1936 obtained the
indicate an average of 0.8 surge exceeding 300 amperes for first oscillograms of the current in direct strokes. These
station arresters, but only 0.4 for all distribution arresters. studies were made with a balloon attached to a metal cable
Rural distribution arresters experience more than urban and flown at altitudes between 500 and 800 meters during a
arresters, because of the greater density and better shielding thunderstorm. Resistance shunts were connected directly
of urban arresters. Rural distribution arresters, although in the cable circuit for a cathode-ray oscillograph and a
having fewer surges than station arresters, are required to high-speed rotating klydonograph. In addition, a short
discharge higher currents. horizontal antenna about 20 meters above the ground was
Figs. 53 and 54 show the distribution of duty among used with a cathode-ray oscillograph and a rotating kly-
individual arresters. Fig. 53, drawn from the data reported donograph. During the lightning season only two storms
by Gross and McMorris, shows that for a group of station occurred near the lightning station, but six strokes to the
arresters 32 percent discharged no surges in four years, vertical antenna were recorded, five in one’storm. The
only 25 percent discharged two, and the maximum number cathode-ray oscillogram of one of these is shown in Fig. 56,
discharged was 3.84 per single-phase arrester per year. The

pl[ (
0 5 IO I5 20 25 50
MICROSECONOS

Fig. 56-Cathode-ray oscillogram of current in lightnlnll


stroke to captive balloon.2*

and data on the five strokes that could be analyzed arei


given in Table 3. These records indicate fronts of from 1% :
to 10 microseconds and rates of rise of from 1.8 to 9 kilo- .j
amperes per microsecond. The maximum duration @I
recorded by the oscillograph was not over 50 microseconds,‘i
but the instrument was not very sensitive. Some of th
rotating klydonograph records of the individual comPc
nents of the induced surges on the horizontal antenna
Fig. 55-Effect of line construction on number and magnitude however, indicate durations from 2600 to 10 000 micra
of station-arrester discharge currents; Gross and McMorris.T3 seconds.
Chapter 16 Lightning Phenomena 571

Several cathode-ray oscillograms obtained by McEach- it may be only a few amperes. An example of a crater-lamp
ran” show the wave shape of the initial high-current por- oscillogram showing the presence of such currents between
tion of successive components of multiple strokes. Oscillo- successive peaks is given in Fig. 58. This oscillogram is
grams for two of these strokes are shown in Fig, 57. The also interesting in that it confirms an essential difference
first (a) is of a single stroke having a crest current of about between the types of discharge to high and low objects.
15 000 amperes, a front of about 4 microseconds, and a
MICROSECONDS
time to half value of about 75 microseconds. The second
two oscillograms (b, c) are of two components of a multiple
stroke. Each has crest values of about 20 000 amperes,
fronts of about 10 microseconds, and times to half value
of about 70 microseconds. (a)
McEachron concludes that the current between com-
ponents of a stroke is continuous, although in many cases

STROKE TO CATHEDRAL OF LEARNING,


UNIV. OF PlTTSBURGH
6000 k NO. 21 IO-39
u) I e

MICROSECONOS

Kq==qY

STROKE TO CATHEDRAL OF LEARNING, Fig. 57-Cathode-ray oscillograms of the currents in two


UNIV. OF PITTSBURGH
NO. 27 5-6-40
strokes to the Empire State Building.”
NEGATIVE POLARITY
TIME-SECONDS

TIME IN MICROSECONOS
STROKE TO STACK OF ANACONDA COPPER MINING CO.,
AT ANACONDA, MONTANA.
NO. 29 6-I-40
L , Fig. 58-Crater-lamp oscillogram of stroke to the Empire
State Building by McEachron,” showing successive peaks and
continuing current.

STROKE TO 565 FT. STACK OF ANACONDA COPPER MINING CO.,


AT ANACONDA, MONTANA.
NO. 34 6-21-40 l2,SOO
TIME IN MICROSECONDS ALL COMPONENTS NEGATIVE I

TIME IN MICROSECONDS

Fig. 59-Fulchronograms of currents in direct str0kes.a


572 Lightning Phenomena Chapter 16 ,
TABLE ~-TABULATED DATA ON FIVE STROKE-CURRENTOSCILLO- .NEGATIVE POLARITY
GRAMSOBTAINEDBYSTEKOLNIKOVANDVALEEV~~
Oscillogrnm number.. 1 2 3 4 5
Crest value of current in kilo-
amperes.. 30 18 31 17 30
Front, of wave in microsec-
ends. 8 10 3.5 10 1.5-2.0
Maximum rate of rise of cur-
rent in kilo-amperes per
microsecond, 6.6 7.6 25 4.0 6 lb 2b - 40 6
;i**
Mean rate of rise in kiloam- TIME IN MICROSECONDS “1

Peres per microsecond. 3.8 1.8 9.0 1.7


Pleasurable duration in mi-
croseconds. . 35 45 30 23

Polarity-all negative but last one, which was oscillatory.


s(r
AND MAGNETIC LINKS
MISS. POW. CO. SO. CAR. E. 8 G. CO. 2 6000
:
6000

5000

4000

3000

2000

1000

0 5 - IO
TIME IN MICROSECONOS

TIME IN ME.-SEC. (b)

0 SLOW SPEED

UONON.-WEST PENN PUB. SER. CO.


NO. 46 7-23-40

x x 8 8
“SC0 is P 4 0.
P =
TIME IN MICROSECONDS

PHASES NOS. I e 2 HAD SINGLE COMPONENT NEGATIVE DISC,,ARGES OF A60”7 300


AMPhRES AND NEGLIGIBLE DURATION.

Fig. 60-Fulchronograms of lightning-arrester discharge


currents.ffi

The vast majority of the discharges to the Empire State TIME IN MICRC6ECONDS
Building were initiated by upward streamers from the 63
building, and until this streamer tapped a concentration Fig. 61-Record of arrester discharge currents obtained at ths :: ,
of charge in the cloud the record indicated a low magnitude 33 kv Stone Creek Substation of the Ohio Power CompanY*”
of current as shown in Fig. 58 for the first few tenths (a) Cathode-ray oscillogram of current in the common ground.
of a second. (b) Replot of cathode-ray oscillogram in linear coordinates.
Wagner, McCann, and Becks5 have presented data ob- (c) Fulchronograms of current in the individual arrester ph
tained with the fulchronograph on subjects varying be- legs.
tween 300 and 600 feet in height. Of twelve records ob-
tained only one shows evidence that the discharge was maximum measured lightning current for which th
initiated by an upward streamer. This record was obtained ured current flowed through a single conductor.
at the Cathedral of Learning of the University of NO. 34 has the largest number of components of
Pittsburgh, Pa., and is No. 21 shown in Fig. 59. This figure chronograms obtained in this investigation, and s
also shows fulchronograms of direct strokes of the more furthermore, that the maximum component does not
conventional type. The Anaconda No. 29 represents the ways occur near the beginning of the stroke. A sim
Chapter 16 Lightning Phenomena 573

phenOmenOn was observed with photographic studies.65


Several fulchronograms of current discharged by arresters
are shown in Fig. GO. A cathode-ray oscillogram of the
neutral current and fulchronograms of phase currents for
a lightning discharge of a three-phase arrester bank are
shown in Fig. 61.
31. rulg;Shape of Initial High-Current Portion of

Time to Half VaZue-Fulchronograms85~86 giving the


current wave shape and duration have been obtained of
4~ direct strokes having 118 components, and of station
arrester discharges having 223 components, and of dis-
tribution arrester discharges having 83 components. Ex-
cluding four low-magnitude components of strokes that
MICROSECONDS
lvere initiated by upward streamers, the times to half value
Of the direct-stroke records of the initial high-current por- Fig. 63-Duration of current peaks measured to half-value, as
tions varied from approximately 15 to 90 microseconds, a function of frequency of occurrence;65 based on 11 strokes
with 50 percent of the components having a time to half measured with cathode-ray oscillograph.
v:tlue of 43 microseconds. The times to half value of the
station arrester surges varied from 10 to 120 microseconds,
with 50 percent of the surges having a time to half value
cf 27 microseconds. The times to half value of the dis-
tribution arrester surges varied from 10 to 350 micro-
seconds. The character of the tail of the high-current
components is the same in both direct-strokes and dis-
tribution-arrester discharge records. The times to half
value for arresters in stations are shorter than for distri-
bution arresters or direct strokes. These data are sum-
marized in Fig. 62.

MICROSECONDS
MCCANN 8 BECKW
ARRESTERS IN STATION Fig. 64-Time to first crest of current peaks, as a function of
frequency of occurrence;a3 based on cathode-ray oscillograms
of 13 strokes.

BERGER72TRANSMISSION LINE TOWER


CURRENTS (43 RECORDS)

0
RINDER64 FOR TOTAL STROKE CURRENTS
TIME TO HALF VALUE IN MICROSECONDS LCULATED FROM MAGNETIC FIELD
Pig. 62-Percentage distribution curves of duration of in- MEASUREMENTS
dividual components of lightning-surge currents.
McEACHRON” I I STROKES TO
EMPIRE STATE BUILDING WITH
Similar data obtained by McEachrorP by means of the ODE-RAY OSCILLOGRAPH
cathode-ray oscillograph are summarized in Fig. 63. DIRECT STROKES
Wave Fronts-The results of Stekolnikov and Valeev
cn direct strokes as summarized in Table 3 indicate wave
fronts of from 1.5 to 10 microseconds. Fig. 64 summarizes
data obtained on the Empire State Building.63
Table 4 gives the results of measurements made with the
‘“agnetic surge-front recorder on direct-stroke currents RATE OF RISE IN KILOAMPERES PER MICROSECOND
arrester discharge currents, and a transmission-line towe; Fig. 6%Percentage distribution curves of rate of current rise
current.66 These data indicate a lower limit of 0.5 and an on fronts of lightning surges.
574 Lightning Phenomena Chapter 16 ,,

TABLE ~-RECORDS OBTAINED WITH MAGNETIC SURGE-FRONT amperes. Norinder’s values are questionnble,‘as they were
RECORDERS BY WAGNER, MCCANN, AND BECK% estimated from measurements made of the magnetic fields j.;
produced by lightning strokes. McEachron’s data repre, ‘I
Average Rntc
Crest
Surge Front, of Rise, Am-
sent the effective rate of rise of strokes measured with the 1
Record
Sumher
Polarity current,
Microseconds Peres Per cathode-ray oscillograph. McCann measured with the :
Amperes cathode-ray oscillograph and magnetic surge-front recorder .z
Microsecond
the effective rate of rise of direct strokes to tall objects. -1
Currents direct strokes
24 Neg. 19 000 2.5 7 600 32. Characteristics of the Long-Duration Tails
34 Neg. 3 000-12 500 0.5- 9.6* 1 300- 6 OOO*
1 ooo- 3 300 li4- 2 ooo*
The records obtained on the long-duration portion of
59 Keg. 0.5-19.0*
60 Neg. 325- 6 800 0.5- 6.0* 1 140- 2 ooo* direct strokes indicate that their character varies over tide ;
Currents in common grounds of three !-r chase arreste :r txmks limits. Aside from the strokes of continuing character
5 scg. 100 More 10 Less 10 recorded to tall objects, 65*71 the fulchronogramsa6 of direct
5.5 Neg. 1 600 2 800 strokes indicate component durations of between 50 and
30 PO% 500 1 500 300 000 microseconds. The curves of Fig. 66 show the
41 scg. 500 1.1 450 measurable duration of individual components of direct
31 Pos. 600 More 6 Less 100 strokes as measured with the fulchronogrnph and also the
42 Pos. 825 More 20 Less 40 photographic-recorder. The fulchronograph and photo.
38 Pos. 1 100 3.9 280
graphic-recorder have recording sensitivities of 50 amperw
47 Neg. 2 300 6 380
Neg. More 10 Less 20
and 0.2 ampere, respectively. It is of interest that for any
45 200
58 Neg. *5 100 1.6 3 200 percentage occurrence value on this figure, the duration m
48 Neg. 400- 4 300 (0.5-20)* 500- 2 600* recorded by the fulchronograph is only a small fraction of
Trnnsmission-line tower current that shown by the photographic-recorder curve. This
66 ( Neg. 1 50 400 1 1.16 1 43 600 shows that on the average the duration of current above
‘These ml~es indicate t,he limits within which the true values lie due to inaccu- 50 amperes in a component is only a small fraction of ib
racics introduced by multiple strokes. total duration.
It is shown in Fig. 66 that arrester-current records have
upper limit of 20 microseconds. The lower limit, however, considerably less evidence of long-duration tails. Of the
is quite doubtful because the presence of multiple strokes 268 discharge records obtained from arresters in stations,
impaired the indication. The highest average rate of cur- only 8 percent of the surges lasted longer than 300 micre
rent rise measured in a direct stroke in these studies is seconds. Of the 97 discharge records obtained from die-
7600 amperes per microsecond for a stroke with a crest of tribution arresters, 54 percent of the surges had durations
19 000 amperes. However, the transmission line tower exceeding 300 microseconds. The 137 records obtained by
current, which had a crest of 50 400 amperes, indicated an photographic-recorder on arresters in stations show that
average rate of rise of 43 600 amperes per microsecond. 50 percent of the surges lasted longer than 3000 micro-
The highest average rate of rise measured in an arrester seconds. As shown by Bergvall and Beckz5 power trans-
discharge was 3200 amperes per microsecond for a surge formers on grounded-neutral systems shbuld be able to
with a crest current of 5100 amperes. absorb the long-tail portion of the wave to an appreciable
Fig. 65 gives percentage distribution curves on the rate degree, if a sufficiently low impedance path to ground is
of rise occurring on the front of the wave. Berger’s meas- provided. Distribution transformers should perform this
urements are of currents in transmission-line towers. The function to a lesser degree. Thus, under ‘these conditions,
highest rate of rise that he recorded was between 30 000 the arresters and transformers tend to protect each other.
and 40 000 amperes per microsecond. However, the crest The arrester takes the high-current portion of the surge,
currents associated with the records did not exceed 40 000 which is injurious to the transformer; and the transformer
the long-duration portion, which is injurious to the arrester.
This is verified by the facV5 that the 14 long-duration
records were obtained on systems in which the protective
value of the transformer ground connection is absent,
although only about 30 percent of the arrester records
were obtained on this type of circuit.
Further evidence of the influence of the system ground
on surge duration is found in the field experience that ha
been gained in the past with a new type distribution
arrester. 65 Of 27 000 arrester years of operation on four ,.
wire systems in which the neutrals of the source
formers are grounded with the neutral brought out
distribution transformers being protected, no failures
0
‘0 Ioc 1000 10000 l000co occurred. For systems with the source grounded but
0”RATlON IN YtCROSECONoS the neutral not brought out and the primary of th
Fig. 66-Percentage distribution curves of duration of indi- tected transformer not grounded, the record shows
vidual components of lightning-surge currents. ures caused by lightning out of 8500 arrester Ye&m)
Chapter 16 Lightning Phenomena 575

0,082 percent. On delta systems 11 lightning failures have 3. On the Electrical Charge Collected by Water Drops. J. P.
cccurred in 4500 arrester years, giving a performance of Gott. Proceedings Royal Society, Series -4, Vol. 151, 1935,
0.24 percent. This result can be explained only by the page 665.
Presence of long-duration surges. 4. The Mechanism of a Thunderstorm, Sir George Simpson, Pro-
A further significant fact is that 16 of the 18 failures ceedings Royal Society, Series A, Vol. 114, l!I2i, page 376.
-
3. The Distribution of Electricity in Thunderclouds, Sir George
cccurred on four systems having only 1078 arrester years’ Simpson and F. J. Scrase, Proceedings Royal Society, Series A,
cspcrience. These systems, in addition to being either Number 906, Vol. 161, 193i, page 309.
delta- or wye-connected with the protected transformer 6. The Distribution of Electricity in Thunderclouds-II, Sir
,,ngrounded, were in regions of very high soil resistivity. George Simpson and G. D. Robinson, Proceetlin~s Royal So-
,fhis indicates that strokes in regions of high soil resistivity ciety, Series A, Vol. li7, 1941, page 281.
nrny have longer-duration components than those in 7. On the Origin and Distribution of Thunderstorm Electricity,
regions of low soil resistivity. W. J. Humphreys, Monlhly Wealher Revietc, September 1939,
67:321.
33. Conclusion 8. Aircraft Lightning Discharges, E. J. hlinser, Journul of Ihe Aero-
AS a result of the investigations described, certain char- naulical Sciences, Volume 7, Number 2, December 1939.
9. Investigations on Lightning Discharges and on the Electrical
sctcristics of lightning may be said to be quite definitely Field of Thunderstorms, C. T. R. Wilson, Philosophical Trans-
knonn. Among these are: uc1io7ts, Royal Society, Series A, Vol. 221, 1920, page 73.
I, Mechanism of the discharge. 10. Atmosrjheric Eleclricily (book), 13. F. .J. Schonland, 1Iethuen
2. Polarity. and Company, London.
:I. General wave shape. 11. Lightning to the Empire State Building, K. B. &IcEachron,
4. Xumber of components in the discharge. Journal Franklin Institute, Vol. 227, Number 2, February 1939.
$5.Time intervals between components of discharges. 12. Lightning Investigation on Transmission Lines-VII, W. \V.
6. Total stroke durations. Lewis, C. M. Foust, A.Z.E.E. Z’runsacliorrs, Vol. 59, 1940 (April
i. Crest magnitude of stroke current at ground, of tower section), page 232.
(.urrents, and of currents discharged by lightning arresters. 13. Progressive Lightning, B. F. J. Schonland, H. Collens, Proceed-
ings Royal Society, Series A, Vol. 143, 1934, page 654.
On the other hand, many questions are still only par- 14. Progressive Lightning-II, B. F. J. Schonlsnd, D. J. M&n,
tially answered. Thus, H. Collens, Proceedings Royal Society, Series d, Vol. 152, 1935,
1. Thunderstorms appear to follow more or less definite paths page 595.
11sinfluenced by local terrain, which produces great localized 15. Progressive Lightning, III-The Line Structure of Return
v:uiations in storm and lightning-stroke density. The only in- Lightning Strokes, D. J. Mnlan, H. Collens, Proceedings Royal
formation available as to the density of strokes is that distributed Society, Series A, Vol. 162, 1937, page 175.
by the Weather Bureau, which pertains only to the number of 16. Progressive Lightning, IV-The Discharge AIechanism, B. F. J.
storm days, and is based upon aural indications. The Bureau Schonland, Proceedings Royal Society, Series A, Vol. 164, 1938,
data do not take these local conditions and line locations with page 132.
regtlrd to them into consideration. 17. Progressive Lightning, V-A Comparison of Photographic and
2. Of the half-dozen proposed theories of charge formation, Electrical Studies of the Discharge Process, B. F. J. Schonlnnd,
nnne explains completely all the factors involved. D. B. Hodges, H. Collens, Proceedings Royal Society, Series A,
3. The length of the stroke channel, that is, the height of the Vol. 166, 1938, page 56.
(#huge centers above earth, and the distribution of charge and 18. The Lightning Discharge, B. F. J. Schonland, Clarendon Press,
current in the channels are still insufficiently known. Oxford, England, 1938.
4. Earth resistivity and geological structure appear to in- 19. Direct Stroke Proves Length of Lightning Tail, C. F. Wagner
fluence the duration and possibly the crest magnitude of stroke and Edward Beck, Electrical World, July 29, 1939, page 37.
clischarges,but insufficient information is available to determine 20. Photographing Lightning With a Moving Camera, Alex Larsen,
the extent. Annual Report Smithsonian Institute, 1905, page 119.
5. Tall objects unquestionably affect the initial streamers 21. Intermittent Lightning Discharges, B. Walter, Philosophical
ant1it is likely that the subsequent discharge is also affected. Magazine, Section 7, Vol. 20, Number 137, December 1935,
6. The extent to which current at the ground flows between the pages 1144-55 and 115&l.
in(lividua1 components is still somewhat questionable. 22. L’Etude de la Foudre dans un Laboratorie de Campagne, I.
7. The initial rates of rise of stroke currents and voltages Stekolnikov and Ch. Valeev, CIGRE, 1937, Bulletin 330.
(‘il(‘ountered on systems are still worthy subjects of research. 23. The Lightning Stroke; Mechanism of Discharge, K. B. >Ic-
8. More direct evidence is required to determine whether some Eachron and W. A. McMorris, General Electric lieview, October
Of the recorded tower currents are due to induced effects. 1936, page 487.
24. Lightning Strokes in Field and Laboratory, P. L. Bellaschi,
It is apparent, therefore, that although considerable ElectTicuZ Engineering, Vol. 58, November 1939, page 466.
Progresshas been made in lightning research, many ques- 25. Lightning and Lightning Protection of Distribution Systems,
tions still remain for further investigation. R. C. Bergvall and Edward Beck, A.I.E.E. Transaclions, Vol.
59, 1940 (August section), page 442.
26. On the Nature of Atmospherics-IV, E. V. Appleton and F. W.
REFERENCES Chapman, Proceedings Royal Society, Series A, Vol. 158, 1937,
1. Some Thundercloud Problems, C. T. R. Wilson, Journal Frank- page 1.
lin Institute, Vol. 208, 1929, Page 1. 27. Lightning and Other Transients on Transmission Lines, F. W.
2. Some In vestigntions in the Deformation and Breaking of Water Peek, Jr., A.I.E.E. Transactions, Vol. 43, 1924, page 1205.
Drops in Strong Electric Fields, W. A. Macky, Proceedings 28. The Klydonograph, J. F. Peters, Eleclrical lvorld, April 19,
Royal Society, Series A, Vol. 133, 1931, Page 565. 1924, page 3.
576 Lightning Phenomena

29. The Klydonograph and Its Application to Surge Investiga- R. Pittman and J. J. Torok, A. I.E.E. Transactions, Vol. w, j
tions, J. H. Cos and J. W. Legg, A.I.E.E. Transactions, Vol. 44, 1931, page 568.
1925, page 8.57. 55. Experience With Preventive Lightning Protection on Tra&’
30. The Measurement of Surge Voltages on Transmission Lines mission Lines, S. K. Waldorf, A.I.E.E. Transactions, vol. 80 j
Due to Lightning, E. S. Lee and C. M. Foust, A.I.E.E. Trans- 1941 (June Section), page 249. ‘i
actions, Vol. 46, 1927, page 339. 56. Direct Strokes, Not Induced Strokes, Chief Cause of H,b
31. Itcsultats des MCsurcs Effect&es an Cours Orages de 1934- Voltage-Line Flashover, C. L. Fortescue, Electric Journal, ~~~~
1935, K. Berger, Association Suisse des Electriciens Bulletin, ust 1930, page 459.
Vol. 27, Number 6, March 20, 1936, page 145. 57. Lightning Measured on 4-Kv Overhead Circuits, Herman HaI;
32. Cathode-Ray Oscillograph, A. Dufour, Comptes Rendus, Vol. perin and K. B. McEachron, A.Z.E.E. Transactions, Vol. m
I
158, 1!114, page 1139. 1934, page 33.
33. The Cathode-Ray Oscillograph, H. Norinder, A.I.E.E. Trans- 58. Lightning on Transmission Lines, J. H. Cox and E. Bee,
mtions, Vol. 47, 1928, page 446. A.I.E.E. Transactions, Vol. 49, 1930, page 944.
34. A Cathode-Ray Oscillograph with Norinder Relay, 0. Acker- 59. Lightning Investigations of the 220-Kv System of the Penn&
mann, A.I.E.E. Transactions, Vol. 49, 1930, page 285. vania Power and Light Company (1930), E. Bell and A. L. Price;
35. Cathode-Ray Oscillographs and Their Uses, E. S. Lee, General A.I.E.E. Transactions, Vol. 50, 1931, page 1101.
Electric Review, Vol. 31, 1928, page 404. 60 Lightning Surges on Transmission Lines-Natural Lightning’
36. A New Type of Hot-Cathode Oscillograph and Its Application W. W. Lewis and C. M. Foust, General Electric Review, No”&
to the Automatic Recording of Lightning and Switching Surges, ber 1936, page 543. 1
R. H. George, A.I.E.E. Transactions, Vol. 48, 1929, page 884. 61. Lightning Investigation on 220-Kv System of the PennsyIvanIr
37. Sew High-Speed Cathode-Ray Oscillograph, H. P. Kuehni and Power and Light Company (1928 and 1929), N. N. Smeloff and
S. Ramo, A.Z.E.E. Transactions, Vol. 56, 1937 (June Section), A. L. Price, A.I.E.E. Transuctions, Vol. 49, 1930, page 895.
page 721. 62. Lightning Voltages on Transmission Lines, R. H. George and
38. New Instruments for Recording Lightning Currents, C. F. J. R. Eaton, A.I.E.E. Transaclions, Vol. 49, 1930, page 877.
Wagner and G. D. McCann, A.I.E.E. Transactions, Vol. 59, 63. Lightning to the Empire State Building, K. B. McEachron,
1940, page 1061. A.I.E.E. Transactions, Vol. 60, 1941 (September Section),
39. Lightning Currents Measured, H. W. Collins, Electrical World, page 885. 5
May 12, 1934. 64. Lightning Currents and Their Variation, H. Norinder, Jou&
40. Gewittermessungen der Jahr 1932 and 1933 in der Schweiz, H. of the Franklin Institute, Vol. 220, 1933, page 69.
Berger, Association Suisse des Electriciens Bulletin, April 27, 65. Field Investigations on Lightning, C. F. Wagner, G. D. McCann:
1934. and E. Beck, A.I.E.E. Transuclions, Vol. 60, 1941.
41. Die LIessung von Blitzstromstaerken, H. Grunewald, Elektro- 66. Lightning Investigations on Transmission Lines-VII, W. W,.
technische Zeitschrijt, 1934, page 505. Lewis and C. RI. Foust, A.I.E.E. Transactions, Vol. 59, 1040

42. Symposium on Operation of Boulder Dam Transmission Line (April Section), page 227.
-Insulation and Lightning Protection, Bradley Cozzens, A.I. 67. Lightning Investigations on a 220-Kv System, Edgar Bell, A.!,
E.E. Tra7~mtions, Vol. 58, 1939 (April Section), page 140. E.E. Transactions, Vol. 53, 1934 (August Section), page 1184.
43. The Surge-Crest Ammeter, C. M. Foust and H. P. Kuehni, 68. Lightning Investigations on a 220-Kv System-III, Edgar Bell,
General Electric Review, Vol. 35, 1932, page 644. A.I.E.E. Transactions, Vol. 59, 1940, page 822.
44. The Crater-Lamp Oscillograph, W. A. McMorris, M. A. Rush- 69. Recherches sur les Perturbations Provoquees par les Orages et’ i
cr, and J. H. Hagenguth, General Eleclric Review, Vol. 37, 1934, sur la Protection des Lignes Aeriennes Contre les Ora
page 514. Grunewald, CIGRE 1939, Bulletin No. 323.,’
45. The Distribution of Thunderstorms in the United States 1904- 70. Direct-Stroke Currents Investigation on a 154-Kv Line, Ro
33, W. II. Alexander, Monthly Weather Review, Vol. 63, 1935, kaku and Katoh, Electrotechnical Journal (+pan), 1938, Vol. a
_--
page 157. page 1 I 3.
46. Discharge Currents in Distribution Arresters-II, K. B. Mc- 71. Multiple Lightning Strokes-II, K. B. McEachron, A.I.E.$’
Eachron and W. A. McMorris, A.I.E.E. Transactions, Vol. 57, Transactions, Vol. 57, 1938 (September Section), page 510. .
1!138 (June Section), page 307. 72. Resultats des Mesures Effectuees au Cours des Orages de 1934
47. Klydonograph Surge Investigations, J. H. Cox, P. H. McAuley, 1935, Berger, Association Suisse des Electriciens Bulletin, VO
and L. G. Huggins, A.I.E.E. Transactions, Vol. 46, 1927, page 27, March 20, 1936, page 145.
315. 73. Lightning Currents in Arresters at Stations, I. W. Gross ani
48. Surge-Voltage Investigation on Transmission Lines, W. W. W. A. McMorris, A.I.E.E. Transactions, Vol. 59, 1940 (August
Lewis, A.I.E.E. Transaclions, Vol. 47, 1928, page 1111. section), page 417.
49. Surge-Voltage Investigations on the 140-Kv System of the Con- 74. Resultats de Quatre Annees de Recherches Faites sur les
sumers Power Co. During 1927, J. G. Hemstreet and J. R. Aeriennes au Sujet des Emplacements de-Chutes de la Fou
Eaton, A.I.E.E. Transactions, Volume 47, 1928, page 1125. de 1’Intensite des Courants dus a la Foudre, Grunewald, C
50. Surge-Voltage Investigation on the 132-Kv Transmission Lines 1937, Bulletin No. 316.
of the American Gas and Electric Company, Philip Sporn, 75. Discussion of paper listed in reference 66, R. M. Schahfer
A.I.E.E. Transactions, Vol. 47, 1928, page 1132. W. H. Knutz, A.I.E.E. Transactions, Vol. 59, 1940 (AI’
51. Surge-Voltage Investigation on 220-Kv System of Pennsylvania Section), page 233.
Power and Light Company, N. N. Smeloff, A.I.E.E. Transac- 76.. Shielding of Transmission Lines, C. F. Wagner, G. D. McG
lions, Vol. 47, 1928, page 1140. and G. L. MacLane, Jr., A.I.E.E. Transactions, Vol. 60, 1
52. Lightning Investigation on New England Power Company sys- page 313.
tem, E. W. Dillard, A.I.E.E. Transactions, Vol. 47, 1928, 77. Wave Shapes of Successive Lightning Current Peak% K.,
page 1122. McEachron, Electrical World, February 10, 1940.
53. Lightning on Transmission Lines, Vis. H. Rokkaku, CIGRE, 78. Experience With Protector Tubes, E. Wisco and A. C*’
1939, Bulletin No. 321. teith, Electric Journal, Vol. 35, 1938, pages 299-300.
54. Lightning Investigation on a Wood-Pole Transmission Line, R. 79. Design, Construction, and Operation of a Lightning-
Lightning Phenomena 577

Transmission Line, E. Hnnsson, Edison Electric Institute Pub- 87. An Eight-Year Investigation of Lightning Currents and Pre-
iicstion No. F-6. ventive Lightning Protection on a Transmission System, E.
Lightning Performance of 110- to 165-Kv Transmission Lines, Hansson, S. K. Waldorf, A.Z.E.E. Transactions, Vol. 63, 1944,
A.Z.E.E. !f’ransaclions, Vol. 58, 1939 (June Section), pages pages 251-58.
294-304. 88. Lightning Investigations on 33-Kv Wood Pole Lines, F. E.
Great Lakes Division of NELA 1929-30 Report of Overhead Andrews, G. D. ;\ZcCnnn, A.Z.E.E. Transaclions, Vol. 04, 1945.
Systems Committee. pages 768-77.
1930-31 Report of Engineering Section of NELA-Tmnsmis- 89. Lightning Investigation on Transmission Lines-VIII, W. W.
sion Line Operating Records, 1930. Lewis, C. hf. Foust, A.Z.E.E. Transactions, Vol. G4, 1945, pages
Field Investigation of the Characteristics of Lightning Currents 107-15.
Discharged by Arresters, I. W. Gross, G. D. McCann and 90. Lightning Investigation on the 25-Kv System of the West Penn
Edward Beck, A.Z.E.E. Paper 42-17. System, William C. Bowen, Edward Beck, A.Z.E.E. Trarrsac-
Photographic Study of Lightning, J. H. Hagenguth, A.I.E.E. lions, Vol. 66, 1947, pages 831-36.
Transactions, Vol. 66, 1947, pages 577-83. 91. Transmission Line Design and Performance Based on Direct
The Measurement of Lightning Currents in Direct Strokes, G. Lightning Strokes, E. L. Harder, J. bl. Clayton, A.Z.E.E.
D. McCann, A.I.E.E. Transactions, Vol. 63,1944, pages 1157-64. Technical paper 49-l 11, 1949.
Field Research on Lightning Arrester Discharges, G. D. 92. Hydrometeorological Report No. 5-Part IT, Hydrometeorolog-
McCann, Edward Beck, A.Z.E.E. Transaclions, Vol. 66, 1947, ical Section Office of Hydrologic Director, U.S. Weather Bureau,
psges 625-29. August 1945.
CHAPTER 17

LINE DESIGN BASED UPON DIRECT STROKES


Original Author: Revised by : 1
A. C. Monteith E. L. Harder and J. M. Claytot

T
HE insulation requirements of transmission lines are
determined by lightning and switching transients
and not by the normal frequency voltage. For lines
11pto the highest voltages now in use, lightning disturb-
ances resulting from direct strokes are usually a principal
factor. The direct-stroke theory attributes the severe
lightning disturbances on any transmission line to direct
contact of the discharge with the line. Lines built in
accord with this theory are shown in Fig. 1. Prior to the
acceptance of the direct-stroke theory designers did not
attempt to protect lines for direct strokes. They thought
it highly improbable that lines would be struck directly,
and, with the limited knowledge available, believed it
practically impossible to cope with direct strokes. -Lines
were designed on the basis of induced strokes, which as-
sumed that the charged cloud (covering the vicinity of
the line) with its accompanying gradient of voltage to
ground, bound a cha.rge on the line. The discharge of the
cloud to a location other than the line itself released this
bound charge, which was then free to travel along the
line. Tests have shown that actual gradients appearing
on the line during near-by discharges are too low to ac-
count for the damage frequently done.

Fig. a--Proof of the direct stroke theory-in this case thl


lightning struck close to the line and 1600 feet from a record
ing station yet no abnormal voltages were recorded. j

An instance of lightning (Fig. 2) that struck earth with


in 1600 feet of a field measuring station and within 2a
feet of a 220-kv line, without establishing any above
normal voltage on the line itself, did much to start the
investigators actively to consider direct strokes &9 thc
actual menace. c4
Consideration was given to the effect of direct stokd
and methods of combating them as early as 1929.’ The
early exponent of the theory was Dr. C. L. Fortescue
In 1930 Dr. Fortescue was sufficiently satisfied with the
theory to publish an article* “Direct Strokes, Not I?
duced Surges Chief Cause of High-Voltage Line Fle
over,” and in 1931 Fortescue and ConwelP gave 8
Fig. l-These two lines were designed in accordance with the plete discussion on the application of the direct-s
direct stroke theory of protection. theory to actual line design.
678
chapter 17 Line Design Based Upon Direct Slrokes 579

The direct stroke theory is now completely accepted for up to the protective voltage level used for the line
high-voltage lines (See App. Tables 1 and 2). Much evi- design.
dence is being collected on the low-voltage rural lines to (4) Last, but equally as important, tower-footing re-
indicate that even here it is the direct stroke for which sistances as low as are economically justified must
protection must be provided. More evidence must be be secured.
secured for medium- and low-voltage lines to evaluate
Properly the possible effects of induced strokes. However, /.43hp---42.25’-.p 713’1
if the protection is based on the direct-stroke viewpoint,
then induced strokes sink to insignificance on lines of any
vOttnge.
protection against direct strokes requires a shield to
Prevent lightning from striking the electrical conductors,
tcgcther with adequate drainage facilities and adequate
iasulation structures so that the discharge can drain to
ground without affecting the conductors. As an alterna-
tivc the line can be built without shielding but rather
suxilinry discharge paths provided so that any discharge
tending to interfere with the flow of normal-frequency
current will be interrupted. The shielding method does
act allow an arc path to form from the line conductor to
ground, thereby giving inherent protection in the design
itself. Ground wires is one form of this type of protec-
tion. The non-shielding method or protection by auxil-
isry devices does allow an arc to form between the ground .-
structure and conductors but means are provided to
cluench it without line interruption. De-ion protector
tubes are a form of the latter type of protection.
This discussion is confined to the electrical character-
istics of transmission-line design, and does not deal with
the mechanical characteristics! which are adequately
covered elsewhere.4 The discussron of the general factors
to be considered in designing the two types of lightning-
proof lines is intended only to give a general idea of how
these factors affect the line performance. The results
should not be taken as rigorous but rather should be used
for considering preliminary designs on a comparative
basis. The chief value of the general curves lies in the
facility provided for considering alternative designs on a : I I :
comparative basis; however, a check of the curves against
a large amount of actual line experience does indicate Fig. 3-Ground wire arrangements on 230-kv line.
good agreement.
The above points can be better visualized from Fig. 3
I. LINE DESIGN-INHERENT PROTECTION which shows a sketch of the ground wire arrangement for
1. Design Factors a single-circuit. The ground wires are shown placed high
above the line conductors and are well out on the towers.
The design of a transmission line against lightning for With this type of construction the ground wires are not
a desired performance, is practically independent of oper- placed directly over the conductors. This eliminates the
ating voltage. The main consideration is how to obtain possibility of contact in case of dancing conductors with
s Protection level for the desired performance. sleet loading and also reduces the tower-top cost. Expe-
The basic principles underlying the design of a line rience with lines and also tests6 have shown that when
hosed on the direct-stroke theory are: the protective angle (the angle formed by a line through
(1) Ground wires with sufficient mechanical strength the ground wire and the outer phase wire and the vertical)
must be located to shield the line conductors ade- does not exceed 30 degrees, good shielding of the line con-
yuately from direct strokes. ductors is obtained, and the probability of side stroke to
(2) Adequate clearance from the line conductor to the the conductor is slight. Data taken from many lines
tower or to ground must be maintained so that the show that as this angle increases, the probability of flash
full effectiveness of the insulating structure can be to the conductor increases. This factor will be discussed
obtained. (Sleet might influence this selection.6) in greater detail later.
(3) Adequate clearances from ground wires to con- Where the ground wires are directly connected to the
ductors must be maintained, especially at the supporting structures, such as to the tower top in the
midspan, to prevent flashover to the conductors case of steel lines, or to the pole top with ground wires
580 Line Design Based Upon Direct Strokes Chapter 17 :
I ‘,,”

down the poles in case of wood-pole construction, the current region to allow for strokes up to 200 000 amperes
correct location of ground wires placed high above the which are known to occur from other field data. The&
phase wires is a compromise with the effective utility of data have been obtained through field research on a large
the insulating structure. However, unless ground wires number of lines. This estimating method treats the light-
are placed to intercept the strokes their purpose is de- ning stroke as a constant fixed current; that is, the current
feated. Thus the first requisite is to correctly place the magnitude is assumed to be independent of the stroke
ground wires well above the conductors to prevent side terminating impedance.
flashes to the conductors. Structures on which the ground The curves have been calculated on the basis that the
wires are not directly connected to the steel pole have stroke is intercepted by a shield wire. The lightning
been considered. For example, wood has been used to current is then expected to take the path along the shield
insulate the ground wires from the steel supporting struc-
ture, the ground connection to the ground wires being TABLED-SUMMARYOF ANACOMSTUDY
taken entirely free of the supporting structure. Also the -
erection of poles entirely separate from the conductor Tower Tower-Top Mid-Span Time Lag to
supporting structures and elevated high enough to shield Tooting Voltage Voltage Insulate
Span, Rcsist- ‘er Ampere ‘er Ampere (Nicroseconds)
the conductors have also been proposed. Since the design Feet
factors for arrangements of this sort are different they ance, of Stroke of Stroke
Ohms Current Current Tower (lidspun
will be considered later. This discussion is confined en-
tirely to lines having the ground wires directly connected 200 5 11.6 27.5 2.0 2.0
to the supporting structure. 10 12.5 27.5 2.0 2.0
The second and third factors, the maintenance of ade- 20 16.3 28.5 2.0 2.0
quate clearance from conductors to towers and from 50 28.8 30.5 2.0 2.0
100 45.0 40.5 2.0 2.0
ground wires to conductors are naturally of importance
in obtaining a balanced design and are discussed at length 400 5 13.2 45.0 2.0 2.0
later. 10 15.0 45.0 2.0 2.0
The degree to which the fourth requirement-low foot- 20 21.0 46.5 2.0 2.0
ing resistance-can be met depends on local soil condi- 50 36.0 48.8 2.0 2.0
tions. The method used to reduce the equivalent footing 100 57.5 56.3 2.0 2.0
resistance and the degree to which this is carried is surely
a matter of economics as the problem is one of balancing 600 5 14.0 65.0 2.0 2.0
the cost of lowering the resistance against the cost of in- 10 15.4 65.0 2.0 2.0
creased insulation and tower structure to secure the de- 20 21.5 67.5 2.0 2.0
50 38.8 68.0 2.0 2.0
sired performance. Experience indicates that some means
100 64.0 72.0 2.0 2.0
of reducing the footing resistance to an equivalent of ten
ohms, as measured with the ground wires removed, is 800 5 14.0 86.0 2.0 2.0
more economical than adding insulation. The resistivities 10 16.0 86.0 2.0 2.0
of the principle earth materials, listed in Table 1, vary 20 22.0 87.5 2.0 2.0
50 42.0 90.0 I/ 2.0 2.0
TABLE ~-EARTH RESISTIVITY 100 72.0 92.5 2.0 2.0

Meter Centimeter 1000 5 14.0 110.0 ‘5 2.0 2.0


Ohms
Foot Ohms Ohms 10 17.0 110.0 ’ 2.0 2.0
20 24.5 110.0 2.0 2.0
General -4verage. 100 328 10,000 50 45.0 110.0 2.0 2.0
Sea Water., 0.01-1.0 0.0328-3.28 l-100 100 75.0 113.0 2.0 2.0
Swampy Ground. 10-100 32.8-328 1000-10000
Dry Eurt,h 1000 3280 106 1200 5 14.0 125.0 2.0 2.0
Pure Slate.. 10’ 3.28X107 109 2.0 2.0
10 17.0 125.0
Sandstone. lOa 3.28X108 10’0
20 24.5 125.0 2.0 2.0
50 45.0 125.0 2.0 2.0
100 75.0 130.0 2.4 2.0
over a considerable range so that the selection of the
method of securing low tower footing resistance, will de- 2.0
1600 5 14.0 158.0 2.0
pend on local soil conditions. A more complete discussion 10 17.0 158.0 2.0 2.0
of the use of ground rods and counterpoise will be given 20 24.5 158.0 2.0 2.0
later. 50 45.0 158.0 3.2 2.0
Considerable work has been done on establishing meth- 100 75.0 158.0 3.2 2.0 C’,
ods’ for predetermining the design requirements of lines
to provide a desired immunity against lightning tripouts. 2000 5 14.0 167.0 2.0
The curves of Fig. 4 present an estimating methods which 10 17.0 16i.0 2.0
is based on the stroke current probability curve. This 20 24.5 16i.0 2.0
50 45.0 167.0 4.0
curve is essentially based on the data published by Wal-
100 75.0 167.0 4.0
dorfg except that it has been modified slightly in the high
Chapter 17 Line Design Based Upon Direct Strokes 581

Tower Flashovers
200 FT. SPAN
20

18

16 I6

I4

I2

0
0 2 4 6 8 IO 12 I4 I6 I6 20 22 24
INSULATORS
ii. INSULATORS

(a) (b)

600 FT. SPAN 800 FT. SPAN


20, ,\, 20
I I\&.I K/l 1 I I 1 lI\IIAIYYlIIl
I6

16 ” ” /20

14. \\ ,\ I

2 4 6 IO 12 I4 I6 I6 20 22 24 4 6 -8 lo I2 I4 16 I8 20 22 24
P
INSULATORS d
INSULATORS

CC) W

1000 FT. SPAN 1200 FT. SPAN


20 20

18 18

I6 lb

14 I\IA ! 1
I RCPERMISSIBLE I4

I2

IO

0
0 2 4 6 6 IO 12 I4 I6 18 20 22 24
P
INSULATORS 0
INSULATORS

(e) .w

Figure 4-Continued on Next Page


Line Design Based Upon Direct Strokes Chapter 17

Tower Flashovers
1600 FI. SPAN 2000 FT. SPAN

14 16 16 20 22 24
INSULATORS ii INSULATORS

(W

Midspan Flashovers
200.400. 600, 600 a 1000 FT. SPANS
0 TO 100 OHAS TOWER FOOTING RESISTANCE 1000. 1200, 1600 a 2000 FT. SPANS
0 TO 100 OHMS TOWER FOOTING RESISTANCE

‘“I

0
0 4 6 12 I6 20 24 26 32 36 40 44, 46 52
P
0 MINIMUM MIDSPAN CLEARANCE IN FEET E MINIMUM MIDSPAN CLEARANCE IN FEET,’

(0 6)

Fig. 4-Curves for estimating line insulation and performance, based on lo-inch, 53/-inch spaced suspensiorl insulators, or
equivalent, and an isokeraunic level of 30 storm days per year. _
The numerals on curves (a) to (h) indicate tower footing resistance, (i) and (j) length of span.

wire, down the tower or towers, and through the tower- potentials measured. A 2X40 microsecond current wave
footing resistance to ground. As the current follows this was used throughout the study as representative of light-
path to ground, a transient voltage appears across the ning strokes to transmission lines. Tower-top and midspan
line insulation. Neglecting normal-frequency voltage, the potentials were determined for the range of span lengths
magnitude of this voltage depends chiefly on the stroke and footing resistances covered by the curves of Fig. 4.
current magnitude and wave shape, tower-footing resist- Some typical voltage solutions are shown in Fig. 6 and
ance, tower inductance, span length, and coupling factor. the complete results of the study are summarized in
Assuming the voltage across the insulation has been de- Table 2. Using these solutions and taking coupling into
termined for a particular set of parameters, the insulation account the insulation requirement for any particular
requirements can be determined from the characteristic value of stroke current to tower can be determined from
curves of Fig. 5. the following relationship.
The curves of Fig. 4 are based on tower-top and mid-
span potentials, which were determined from a study on Insulation strength = stroke current x tower-top voltage
the Anacom.‘O A typical line was set up on the Anacom per ampere of stroke current X (one-
and using a typical current wave, stroke currents were coupling).
applied at tower-top and midspan and the corresponding For this insulation strength the required num’Jer of iasu-
Chapter 17 Line Design Based Upon Direct Strokes 583

1600

1500

700

600

500

400

‘3 4 5 6 7 6 9 IO II 12 13 14 15 I6 I7 18 19 20 )- STANDARD INSULATOR UNITS


GAP SPACING-INCHES --t IO I5 20 25 30 35 40 45 50 55 60 65 70m 75 60 ti5 90 95 100

Fig. 5-Characteristics of insulators and gaps, all values are based on 1$$~40 positive waves and corrected to standard
atmospheric conditions,

lators was determined from the characteristic curves of combination of the permissible stroke current curves of
Fig. -5. Xote that the time lag curve to use is determined Fig. 4 and the probability curve of Fig. 7 results in the
from the Anacom solutions. For example, the 3.2-micro- general probability curves of Fig. 4.
second time-lag curve is used in determining the tower The probability curves give line performance on the
insulation requirements for a line with 1600-foot spans basis that all strokes are to tower, or all to midspan, re-
and 100 ohms tower-footing resistance, Fig. 6(d). This is spectively. Thus, line performance is determined by aver-
the time at which the tower-top potential is reduced ap- aging the two outage probabilities obtained from the
preciably by reflected waves from adjacent towers. tower and midspan curves, respectively. For a co-ordi-
Midspan insulation requirements for strokes to midspan nated line, having equal outage probabilities at tower and
were determined from the results of the Anacom study in at midspan, either curve gives the total outages per 100
a similar manner. The Anacom study and basis of the miles of line per year,
parameters used in the study are described in detail in The result of reducing the tower-footing resistance is
reference 8. shown in Fig. 4. For example, a line designed for 10 insu-
Thus, using the method outlined above, the tower and lators with 400-foot span and loo-ohm footing resistance,
midspan insulation requirements were determined for would have a protection level of 28 000 amperes stroke-
various span lengths and tower-footing resistances and current maximum. Further, the same line with 20-ohm
plotted as the permissible stroke current curves of Fig. 4. footing resistance would have a protection level of 80 000
The probability of flashover can be determined by com- amperes and with 5 ohms, a level of 126 000 amperes
bining these curves with the stroke current probability maximum. Thus, lowering the footing resistance increases
curve. The magnitude of the stroke current is recognized the utility of a given string of insulators. The protection
as a matter of probability. Thus, the probability of flash- level can further be increased by the addition of insulators
over for a given case is simply the probability of stroke with corresponding increase in clearances. A line designed
current in excess of that required to cause flashover. The with two insulators and a footing resistance of 10 ohms
stroke current probability curve is given in Fig. 7. The would have a protection level of approximately 28 000
584 Line Design Based Vpon Direct Strokes Chapter 17

2 X 40 CURRENT WAVE of the conductor by the wind will then dbtermine the
clearance from the conductor to the tower for the con-
ductor in the normal position. The spacing between
conductors can be determined by the method given above
the proper allowance being made for the supporting str&
tures. The only insulation requirement from an operating
point of view is that the 60-cycle flashover of the insula-
tion or clearances must be of the order of four times the
a operating voltage to neutral. If this requirement is sat-
(0) I L , 1 I
isfied the probability of outage from switching surges
40 0 4 8 12
TO&R-T% POTENTIAL M IOSPAN POTENTIAL Tvill be negligible and then the lightning consideration Tvill
prevail. Table 3 shows the number of insulators neces-
sary to satisfy this requirement for various operating
voltages.

TABLE ~-MINIMUM SUSPENSION INSULATORS TO PREVENT


OUTAGES FROM SWITCHING SURGES

Maximum Expected /
Voltage Switching Surge - Kv S umhcr
ChSS _.
of
Kv. Voltage Class X@ Insulators
4X
4%
69 225 4
115 375 5
138 415 6
161 520 7
a 230 745 10
287 930 13
: 80
a
2 40 The third requirement, midspan clearance, requires
more consideration. On modern lines midspan clearances
normally required for icing and shielding considerations
(d); ,I,, ,’ Y,

#
.,.

and for mechanical reasons provide a high level of protec-


I I I
0 4 8 12 0 4 8 12 tion. For example, the midspan clearances required to
provide the relatively high protection level of 100 000
TIME IN MICROSECONDS amperes for 400-, 600-, 800- and lOOO-foot )$pans are 9.7,
13.8, 19.8, and 26 feet, respectively, according to Fig. 4(i).
Fig. 6-Typical current wave and tower-top and midspan
potentials from Anacom study. These clearances closely approximate the ‘average values
usually encountered on modern lines.
(a) 2 X40 microsecond current wave; In general, midspan protection levels are higher than
(b) 400-foot span, 50 ohm tower footing resistance; tower protection levels, and in some cases midspan pro-
(c) lOOO-foot span, 10 ohm tower footing resistance; tection levels are extremely high with the results that
(d) 1600-foot span, 100 ohm tower footing resistance
midspan flashovers become negligible. In the previous
example of a line designed with 400-foot span, 10 insu-
amperes while 7 and 11 insulators would have protection lators, and with loo-, 20-, and 5-ohm footing resistances,
levels of 80 000 and 122 000 amperes masimum, respec- the minimum midspan clearances should be at least 2.3,
tively, according to Fig. 4(b). These curves for different 7.0 and 12.5 feet, respectively, to be insulated for the
span lengths provide a method of making estimates for same stroke current at midspan as at tower. However, a
different numbers of insulators and different footing re- line with 400-foot spans normally has a midspan clear-
sistances, facilitating the selection of the most economical ance of approximately 10 feet irrespective of footing re-
design of a transmission line to meet the service require- sistance. This clearance provides a protection level of
ments. 102 000 amperes; a comparable protection level at tower
The second factor-adequate clearance from conductor requires 1Bohm footing resistance. For higher values of
to the tower can readily be obtained by providing an air- footing resistance, it is desirable to maintain the high
gap distance equivalent to the number of insulators. Al- midspan protection level since this results in better line
though flashover curves of gaps and insulators have been performance. In some cases it may be desirable to raise
published they are given in Fig. 5 for convenience in arriv- the midspan protection level. This can be accomplished
ing at equivalents between insulators and gaps in air. by increasing the midspan clearance by allowing the :~*.
This air distance plus the distance allowed for the swing .-\,...
ground wires to sag less than the conductors.
Chapter 17 Line Design Based Upon Direct Strokes 585

line designed for a protection level of 20 000 amperes


stroke current masimum has a probability of 30 outages
per 100 miles per year for an isokeraunic level of 30. In
other words, the probability of having outages on a line
decreases as the protection level increases, because the
probability of experiencing strokes in excess of the higher
level is not so great.
Adding insulators or reducing tower-footing resistances
result in an increased protection level. There is an eco-
nomic limit to which this increase in protection level can
be carried. Little is gained in performance of the line by
raising the protection level beyond a certain limit. For
example, on a line designed with 8 insulators and 50, 20,
or 5 ohms footing resistance the expected probabilit’y of
outage is 15.6, 4.1, and 0.8 outages per 100 miles per year,
respectively. With 12 insulators the expected performance
is 7.8 1.0, and 0.2 outages per 100 miles per year. These
values assume equal protection levels at tower and mid-
span. Therefore, for the higher footing resistances con-
siderably better performance can be expected from in-
creased insulation, up to a certain limit. However, for
the lower footing resistance not much is gained from in-
Fig. T-Lightning stroke current probability curve. Strokes
per 100 miles of line per year based on isokeraunic level of 30. creased insulation. If 5 ohms can be obtained, little re-
turn can be expected from any increase over 11 insulators,
but for 20 ohms the desirable number of insulators is in-
2. Design for Given Performance creased to 17 to obtain the same outage probability.
This discussion has been based entirely on securing The probability curves of Figs. 4 and 7 are based on an
estimates for a given protection level. The question arises isokeraunic level of 30 storm days per year. An isokeraunic
:rs to the level that should be secured for a given standard map”, l2 for the United States is shown in Fig. 8. The
of service. The probability of flashover for a given pro- probability of outage is assumed to vary directly with
tection level can be determined from the stroke current the number of storm days so that if an area has 45 storm
prohability curve of Fig. 7, which is based on an isoker- days per year from the map, the outage probability
uunic level of 30 storm days per year. should be multiplied by 1.5.
For example, a transmission line with a protection The curves of Fig. 4 for estimating outages due to
level for 100 000 amperes stroke current maximum has strokes to tower are based on coupling factors correspond-
:Lnexpected probability factor of 0.7 outage per 100 miles ing to a ground wire 100 feet above the ground plane
per year for an isokeraunic level of 30, and twice that, or and a 30-foot separation between ground wire and con-
1.4 for an isokeraunic level of 60. Also a transmission ductor. For other values of ground wire height and sepa-
ration, the number of insulators
should be corrected to allow for the
corresponding change in coupling
factor; the correction factors are
given in Fig. 9. The equivalent
number of insulators to use with the
curves of Fig. 4 is obtained by
multiplying the actual number of
insulators by the correction factor
corresponding to the actual ground
wire height and spacing. The spac-
ing between ground wire and con-
ductor refers to the distance to the
conductor with the greatest tran-
sient voltage across its insulator
string. This is the conductor most
distant from the ground wire, since
the coupling between this conductor
and ground wire is less than the
coupling for the closer conductors.
On some lines the midspan pro-
Fig. B--Annual isokeraunic map of the United States showing number of thunder- tection level may be more than
storm davs ner vear. twice the tower protection level with
586 L&e Design Based Upon Direct Strokes

strength of wood in series with the insulator\string can be


determined from Fig. 11. I3 For estimating purposes the
flashover voltages of the different insulating media can
be added and the equivalent number of insulators for the
total flashover voltage can be determined from Fig. 5. In
making these calculations all flashover voltages should be
based on the two microsecond time lag curves.
The general curves are based on all &hovers causing
power follow and consequently outages; ho\vever, all

1800
I I I I I I II 11 I
I I I I I I

1600 POSITIVE POLARITY


I% x 40 MICROSECOND WAVE
! I I I
I I I

SPACING AT TOWER FROM GROUND WIRE TO CONDUCTOR-FEET 1400-


i--WOOD GAP--l
Fig. 9-Correction factors for ground wire height and ground
wire-to-conductor spacing at tower.

the result that strokes to midspan may cause flashover at


tower rather than at midspan. If the permissible stroke
current to midspan is more than twice the permissible
stroke current to tower, the outage probability is the aver-
age of that corresponding to the permissible stroke current
to tower and that corresponding to twice this stroke cur-
rent. If the permissible stroke current curves of Fig. 4 in-
dicate the midspan protection level is more than twice the
tower protection level, the outage probability should be
determined from the curve of Fig. 10.
600
On wood-pole lines where the insulating medium may
be a combination of porcelain, wood, and air, the insula-
tion strength of the flashover path must be determined
and converted to an equivalent number of standard insu-
lators. The insulation strengths of standard insulators
and air can he determined from Fig. 5, and the insulation

FEET OF WOOD
Fig. ll-Impulse insulation added to suspension-insulator
strings by wood crossarms.

flashovers do not resuIt in outages depending on the line


insulation characteristics and other factors. The ratio of
outage to flashover is discussed in section III.
3. Application of Curves
The use of the curves of Fig. 4 in estimating line Per
formance is illustrated by a few examples.
‘Exanple 1. A proposed 13%kv line is to have not more
than 2 outages per 100 miles per year based on an iscr
So’ ’ ’ ’ ’ ’ ’ keraunic level of 30. Shielding the line is recognized a
0 0 20 40 60 80 100
E PERMISSIBLE STROKE CURRENT desirable. Soil conditions are such that the footing re-
TO TOWER IN AMPERES X IO3 sistance is 100 ohms. Tests show that four 30-foot ground .
Fig. IO-Curve for determining the outage probability if the rods reduce the resistance to 50 ohms; that a Partid.
midspan protection level is more than twice the tower pro- counterpoise reduces this to 20 ohms equivalent, and *
tection level. an adequate counterpoise reduces it to 10 ohms equ id
Chapter 17 Line Design Based Upon Direct Strokes 587

The first question is span length. The topography of The equivalent insulation of the wood and porcelain
the country, condrlctor size, etc., must be considered. based on the two microsecond time-lag curves can be
Ho\vever, assume that all factors have been considered determined from Figs. 5 and 11. The flnshover volt,ages
and IOOO-foot spans have been selected and that ground for six insulators and six feet of mood are 800 kv and 700
wires and conductors will bc sagged to permit a midspan kv, respectively. From Fig. 5 the sum of these values,
separation of 2-l feet. The outage probability for this 1500 kv, is equivalent to 12 standard insulators.
midspan separation is 1.0, Fig. G(i). Therefore, the outage The increased coupling due to spacing and ground wire
height can be taken into account by the correction factors
TABLE ~-MINIMUM CLEARANCE FROM CONDUCTOR TO TOWER of Fig. 9; a correction factor of 1.1 corresponds to a 12-
foot separation and ground wire height of 50 feet. Correct-
Number of ClearsIKe ing for coupling the equivalent insulation becomes
Tnsultltors IrIches 1.1 X 12 = 13.2 insulators.
27 15.5 From Figs. 4(c) and 4(i) the outage probabilities corre-
18 105 sponding to 13.2 insulators, 50 ohms pole-grounding re-
10 xl sistance, and 14 foot midspan separation are 5.0 and 0.7
7 43 per 100 miles per year for strokes to tower and midspan,
respectively. The average of these, (5.OfO.T) 2=2.85,
,““t)ability for strokes to tower must be 3.0 so that the is the outage probability for the line assuming all flash-
:lvcrsge of the tower and midspan outages will be 2.0. overs result in sustained power follow and trip-out. Since
I”or three outages per 100 miles per year and loo-ohms part of the insulating medium is wood, approximately
footing resistance, 27 insulators are required, Fig. 4(e). 50 percent of the flashovers will result in outages. Thus
The number of insulators becomes 18 for 50 ohms, 10 for the o&age probability is 0.50x2.85 = 1.42 per 100 miles
21) ohms, and 7 for 10 ohms footing resistance. The mini- per year.
mum conductor-to-tower clearance, balanced against the
insulator flashover, is given in Table 4. These dimensions II. PERFORMANCE OF TYPICAL LINES
allow a layout of the towers; and the added cost of towers,
insulators, etc., can be balanced against the cost of re- The general curves of Fig. 4 express line performance in
ducing the footing resistance. terms of four main parameters; namely, footing resistance,
Example 2. Determine the outage probability of a 69-kv line insulation, midspan clearance, and span length. Tower
steel-tower line, shielded by overhead ground wire, lo- footing resistance and line insulation requirements are
cated in an area where the isokeraunic level is 50, which usually determined by the standard of service that is
has eight 53A-inch spaced suspension insulators per string. required of the line. Midspan clearance and span length
The average span is 600 feet with a midspan separation affect line performance but are determined largely by
of 16 feet. The average tower-footing resistance is 50 other factors. Midspan clearances normally required for
ohms. mechanical reasons provide adequate protection against
From the probability curves, Fig. 4(c), the outage midspan flashovers. The length of span is determined
Probability for strokes to tower corresponding to eight primarily by the conductor size and tower construction.
insulators and 50 ohms tower-footing resistance is 13.7 The selection of towers and conductors depends primarily
per 100 miles per year and the permissible stroke current on the voltage class of the line; thus, average values of
is 35 000 amperes. From Fig. 4(i) the outage probability midspan clearance and span length are representative of a
for strokes to midspan corresponding to the given span large percentage of the lines in a particular voltage class.
length and separation is 0.5 per 100 miles per year, and Using average values for these parameters, line perform-
the permissible stroke current is 110 000 amperes. Since ance of a typical line in a particular voltage class can be
the permissible stroke current to midspan is more than expressed in terms of two parameters-footing resistance
twice the permissible stroke current to tower, strokes to and line insulation. On this basis the curves of Figs. 12
midspan can cause flashovers and consequently outages and 13 present a method for estimating the performance
at the tower. For this case the outage probability is de- of typical lines of voltage classes ranging from 34.5 to
termined from Fig. 10. The outage probability for a 287.5 kv. Three curves are given for each voltage class
Permissible stroke current to tower of 35 000 amperes is which cover the range of insulators normally encountered,
8.5 per 100 miles per year for an isokeraunic level of 30. the center curve being based on the number of insulators
‘l’he corresponding outage probability for an isokeraunic most common for the voltage class.
level of 50 is 50/30x8.5 = 14.2 per 100 miles per year. The curves are calculated on the basis that probability
E+WrnpZe3. Determine the outage probability based on of flashover is independent of the normal frequency volt-
an isokeraunic level of 30 of a 69-kv wood-pole line having age. Therefore, the application of the curves is not re-
Six standard insulators and an average pole-grounding stricted to the indicated voltage class. For example, a
resistance of 50 ohms. The average span is 600 feet with 69-kv line may be under consideration with span length
a 14-foot midspan separation. The line insulation con- and midspan separation which are approximately equal
sists of six feet of wood in the electrical circuit in addition to the values on which the 11%kv estimating curves are
to the six insulators. The spacing between ground wire based. In this case the 115-kv curves are used in esti-
and conductors is 12 feet at the poles and the ground wire mating performance of a 69-kv line, provided the desired
is 50 feet above the ground plane. line insulation level is also covered by t,he curves.
588 Line Design Based Upon Direct Strokes

II5 K”.
5 I , I I
L MlOSPAN SEPARATION-14 FT.
/
9
>
/ J /
84
0.
. / / /

I III I I I I I I
20 40 60 80 100
POLE GROUNDING RESISTANCE IN OnYS AVERAGE SPAN-300 FT. POLE GROUNDING RESISTANCE IN OHMS AVERAGE SPAN-600 FT.

69 KV.
IO / , / , ,
cc MIDSPANSEPARATION-14 FT
/ I I I I 1
s /?

POLE GROUNDING RESISTANCE IN OHMS : SPAN-500 FT. POLE GROUNDING RESISTANCE IN OHMS A”ERA6E WAN-600 FT.

(b)

WLE GROUNDING RESISTANCE IN OHMS AVERAGE SPAN-600 FT.

Fig. 12-Typical configurations of wood-pole lines and curves for estimating line performance based on standard
and an isokeraunic level of 30 storm days per year.
Chapter 17 Line Design Based Upon Direct Strokes
589

63 KV,

5 ‘“I-SEPARATliN- l/u
n
YI I I/I
2 16 FT.
’ I

5
P ‘6 I
/
2 I /’
i
s .^ /i ‘1’ ‘7’ ’
I/

01 1 I I I I I II I ]
0 20 40 60 60 100
AVERAGE SPAN-600 FT.
TOWER FOOTING RESISTANCE IN OHMS
AVERAGE SPAN-600 FT.

115 KV.
P 2o MIOSPAN,;E$IRATION-
I I
P /I /’ I

I I I , , , ,
0 20 40 60 60 too
AVERAGE SPAN-700FT.
TOWER FOOTING RESISTANCE IN OHMS
AVERAGE SPAN-700FT.
(b)

“I
138 KV.

f$ ‘” 1 MI&AN +EPAI~AT,O(J-~O;T

I I , ] , ( ,
0 20 . 40 60 60 100
TOWER FOOTING RESISTANCE IN OHMS
AVERAGE SPAN-600 FT.

Fig. 13-Continued on Next Page.


Line Design Based Upon Direct Strokes Chapter 17
\
I61 KV.
_. LV

0
0 20 40 60 00 I00
AVERAGE SPAN-1000 FT. TOWER FOOTING RESISTANCE IN OHMS AVERAGE SPAN-900 FT.

Cd)

230 KV.

0 20 40 60 60 I00
AVERAGE SPAN- 1000 FT. TOWER FOOTING RESISTANCE IN OHMS AVERAGE SPAN-900’

(e)

.-. I I ” i,, / I
I I I I A I/ I I /I

II I
I /’
c I0 22 INSULATORS

g 1
2
z
ILO
0 20 40 60 00 too
AVERAGE SPAN - 1000 FT. TOWER FOOTING RESISTANCE IN OHMS AVERAGE
SPAN-BX)
FT.
(0

Fig. 13-Typical configurations of steel-tower lines and curves for estimating line performance based on standard insulators
and an isokeraunic level of 30 storm days per year.
Chapter 1’7 Line Design Based Upon Direct Strokes 591

The average values of span lengths and midspan sepa- minimum impulse insulation is assumed to be the porce-
rations used in calculating the curves are shown in Figs. lain plus the wood in the electrical circuit. The length
12 and 13. In general, small variations in these factors of wood in the electrical circuit is assumed to be half the
do not affect the number of flnshovers appreciably. For distance between phase conductors, the distance between
esample, a 1 I&kv line with eight insulators, SOO-foot conductors being shown in Fig. 12. The ground wire
spans, l&foot midspan separation, and 10 ohms tower- down-lead is assumed to be fastened directly to the pole.
footing resistance has a flashover probability of 1.2 per In some cases the line insulation is increased by mounting
100 miles per year. As the span length is increased to the down-lead away from the pole so that an air gap is
1000 feet or decreased to 600 feet, the corresponding Aash- included in the flashover path in addition to the porcelain
over probability becomes 1.35 or 1.1 per 100 miles per and wood. General data on wood-pole lines are summar-
year. Assuming the midspan separation is increased to ized in Table 5.
22 feet or decreased to 14 feet the corresponding flash-
over probability becomes 1.0 or 1.65 per 100 miles per 5. Performance of Steel-Tower Lines
year. Thus, small variations in the midspan clearance Curves for estimating the performance of typical steel-
and span length do not affect the outage probability appre- tower lines are presented in Fig. 13; typical conductor and
ciably. If the span length and midspan separation of a ground wire configurations for single-circuit and double-
part,icular line under consideration are appreciably dif- circuit lines are included in this figure. General data on
fcrcnt from the values on which the curves are based, the steel-tower lines are summarized in Table 6. Spans for
line performance should be determined from the curves
of Fig. 4. TABLE ~-GENERAL DATA ON STEEL,-TOWERLINES
The curves of Figs. 12 and 13 give the number of light- - - -
ning flashovers rather than the number of line outages; 1[mpulse Insu- Times
Nominal
No. of lation Level
fiO-Cycle Dry Normal
a11flashovers do not result in line outages. The ratio of Voltage Flashover
outage to flashover which is discussed in section III de- nsulators’ k (:I% X40 Posi- 1,ine-Ground
WV) (KV-RMS)
pends on the line and line insulation characteristics of the tive Waves) Voltage
-- _- --
particular line being considered. 4 430 2i0 6.8
69 6 600 380 9.5
4. Performance of Wood-Pole Lines 8 760 500 12.5
The curves of Fig. 12 for estimating the performance
of Irood-pole lines are based on the typical conductor and 6 600 380 5.7
ground wire configurations shown in the same figure; 115 8 760 500 7.5
these configurations are averages of several lines. In 10 930 600 9.0
calculating the number of flashovers at poles, the path of 8 760 500 6.3
138 10 930 600 7.5
TABLE ~-GENERAL DATA ON WOOD-POLELINES 12 1100 710 8.9
-

Sominsl Number I .mpulse Insu- tiO-Cycle Dry Times 9 850 550 5.9
1ation Level** Normal 161 11 1020 660 7.1
Voltage of Flashover’
I ( 1%X40 Posi- I ,ine-Ground 14 1270 820 8.8
(KV) I nsulators’ (KV-RMS)
tive Waves) Voltage
- - .-
14 1270 820 6.2
500 120 6.0
230 16 1440 930 7.0
3-l.5 Pintype 600 180 9.0
20 1780 1140 8.6
700 .. ...
16 1440 930 5.6
4 970 270 6.8
287.5 18 1610 1030 6.2
69 5 1020 330 8.3
6
22 1950 1250 7.5
1070 380 9.5
18 1610 1030 5.2
6 1130 380 5.7
345** 20 1780 1140 5.7
115 8 1220 500 7.5
24 2110 1350 6.8
10 1330 600 9.0 - - -
*Middle value shows the most common number; upper and lower values show
the range for modern lines of this voltage class.
8 1330 500 6.3 **No existing lines of this voltage class today.
138 9 1380 550 6.9
11 1490 660 8.3 single-circuit lines are generally about 100 feet longer than
double-circuit lines in the same voltage class. Other fac-
9 1450 550 5.9
10 1490 600 6.5
tors remaining equal, the outage probability is slightly
12 1600 710 7.6 greater for the line with longer spans. However, coupling
- - - factors are usually less on double-circuit lines due to the
*~liddle value shows the most common number; upper and low values show
the r:mgc for modern lines of this voltage &as. greater separation between ground wires and conductors,
*“Based on r.omber of insulators shown io previous column plus the length of and this increases the outage probability slightly, other
wood m electrical circuit shown in Fig. 12.
’ Based on porcelain imutation ody. factors remaining equal. Thus, the performance of single-
592 Line Design Based Upon Direct Strokes Chapter 17

circuit and double-circuit lines can be espressed without slope of the hill. A study of actual linesI shows this to
sppreciahlc error in a single set of estimating curves. be the case.
The curves for estimating flashovers on 287.5-kv lines Tests and experience show that 30 degrees is‘ a good
are not based on the actual number of insulators used on average; however, the shielding angle can be worked out
the only existing lint of this voltage class. The curves are in detail with the curves of Fig. 14. These curves show
based on a range of insulator values so that line perform-
ance can he determined for various insulation levels. Also, X IN FEET
the curves covering the upper insulation levels can be
used for estimating lint performance of higher voltage
lines that may be constructecl in the future.

III. DETAILED DISCUSSION OF FACTORS


6. Ground Wires
The selection of the size, arrangement, and mechanical
strength of ground wires is of paramount importance in
the design of a line. Some of the earlier troubles with
ground wires (sometimes called ‘(static” wires) have been
traced to mechanical difficulties or incorrect selection of
the material. Sleet sometimes causes ground wires to
come in contact with the conductors, producing line out-
age. This is minimized as ground wires with characteris-
tics practically the same as the conductors are used. The
proper location and tension is discussed at length in a
published paper.5
When a ground wire is selected with the above thoughts d* 100 50 25
in mind the size is more or less fixed. A small increase of
diameter affects the protection slightly but the increased Fig. 14-Ground wire and conductor configurations for 0.1
cost does not warrant carrying this very far. Usually percent exposure of conductors.
more improvement is obtained by spending this same
money to improve other factors. The material should be ground wire and conductor configurations that permit
non-corrosive. Practically all wire manufacturers now O.l-percent exposure of the conductors. The general
have available a suitable high-strength, non-corrosive wire. curves of Fig. 4 assume that all strokes are intercepted
Calculations indicate a small improvement in coupling by by the shield wire. If the phase conductors are not com-
increasing the ground wire size. A reduction of tower- pletely shielded, the outage probability is determined by
footing resistance gives the same effect in the final design adding directly the estimated number of strokes termi-
and is much cheaper. It is therefore seen that the selec- nating on the conductors to the outage probability given
tion of the ground wires should be based on mechanical by the curves. /
rather than electrical considerations. /
The experience with properly selected and arranged 8. Coupling
ground wires has been satisfactory, some lines now being The entire ground wire or tower-top voItage does not
practically lightning-proof. appear across the line insulation since a Goltage of the
same polarity as the ground wire voltage is induced on
7. Protective Angle the conductors. The ratio of this induced voltage on the
The necessary protective angle between a line through conductor to the ground wire voltage is the coupling fac-
the vertical of the tower and a line through the ground tor. Thus, the voltage across the line insulation is the
wire and outermost line conductor has been a much dis- ground wire voltages times (one- coupling factor), neglect-
cussed subject. Experience with various lines indicated ing normal frequency voltage.
that 20 degrees was giving entire satisfaction but how The electromagnetic and electrostatic coupling factors
much higher this angle could be made was open to ques- are equal unless the effective radius of the ground wire is
tion. Some lines with 45 degrees were giving poor re- increased by corona, then the electrostatic coupling in-
suits. creases and the electromagnetic coupling is believed to be
Laboratory tests,6 coordinated with field results on unaffected. The coupling factor with corona considered
esisting lines indicate that a good average for this angle is calculated by the equation, coupling
is 30 degrees. In arriving at this conclusion models were
erected in the laboratory and by using different scales ‘-d/electrostatic couplingxelectromagnetic COUPl~g*

with different locations of ground wire and electrode sim- Coupling is calculated by the equation,
ulating the cloud it was concluded that 45 degrees for this
angle should be satisfactory when the line was on the level. c = log b/a
However, it is found that when the tower is erected on a log $
hillside the angle should be decreased by the angle of the
Chapter 17 Line Design Based Upon Direct Strokes 593

where sistance depends on the characteristics of the driven


C = coupling factor. grounds, Lvhieh are determined largely by soil resistivity
a = distance from conductor to ground tvire. and the critical gradient at rvhich the soil hre:ks down. A
b = distance from conductor to image* of ground wire. number of laboratory tests 18,lo have been m:ltle on driven
h = height of ground wire above ground. grounds to detorminc t,he impulse characteristics under
r = radius of ground Tvire. various conditions. The impulse resistances of v:lrious
grounds for impulse currents ranging 11p to 12 000 am-
The electromagnetic coupling factor is calculated using peres are sholvn in Fig. 15. For grormtling rcsidnncm in
the actual radius of the ground mire, and the electrostatic
(.oupling factor is calculated by the same equation using 120
60 CYCLE RESISTANCE
the effective radius I5 of the ground Gre due to corona. I I I I I
hi i i i i i i i i 1 i I
9. Lightning Flashover and Power Follow
All lightning flashovers do not result in sustained poTver
follow. The percentage of flashovers that result in po\ver
follom depends principally upon the type and length of the
insulation path, the magnitude of the power follow cur-
rclnt, and the magnitude and duration of the lightning
flashover current. Performance records on various types
of lines have yielded some data I6 on the ratio of sustained
power follow to flashover.
For the higher voltage, steel-tower lines where the prin-
(*ipal flashover path is in air or over porcelain, about S5
percent of all lightning &shovers result in sustained
power follow if the line length is less than 100 miles. The
ratio is reduced to about 0.50 for such lines over 200 miles
in length. For Ivood-pole lines where part of the flashover
path is over good, the ratio of polver follow t’o flnshover
ranges from 0.33 to 0.50. For 13- and 33-kv lvood-pole
lines Ekvall” shows the sustained polver follow to be a
function of the length of flashover path over wood divided IMPULSE CURRENT (CREST)-AMPERES
by the normal frequency voltage. Fig. 15-Variation of impulse resistance with impulse cur-
If the characteristics of the line and line insulation re- rent for various values of 60-cycle resistance.
sult in a considerable reduction of the ratio of power fol-
lo\v to flashover, this should be considered in estimating the order of 10 ohms or less, the impulse resistance is only
the outage probability. To determine the outage proba- slightly less than the 60-cycle value; however, for high
bility taking this factor into account, multiply the ratio ground resistances the impulse resistance is considerably
of power follow to flashover by the outage probability less than the 60-cycle value. Thus, in estimating line
from the general curves. If the ratio is near unity, it can performance footing resistances of ten ohms or less can
be neglected and the general curves Ivill indicate a slightly be taken as the impulse value; however, if the footing
pessimistic outage probability. resistance is high, the impulse resistance should be de-
termined and used in the general curves of Fig. 4. Values
10. Tower-Footing Resistance of impulse resistance can be worked out in detail with
Tomer-footing resistance is usually expressed as the references 18 and 19.
measured 60-cycle value; however, line performance de-
ponds on the impulse value of the footing resisbance. The 11. Lowering Tower-Footing Impedance (Rods and
value of the impulse resistance depends on a number of Counterpoise)
factors such as soil resistivity, critical breakdolvn gradient The discussion on the design factors indicates the de-
of the soil, magnitude of the surge current, and length sirability of reducing the tower-footing impedance as
and type of driven grounds or counterpoises. If long or much as economically possible. The steel tower naturally
continuous counterpoises are used because the soil re- has a large surface in contact with the soil, particularly
sistivity is high, the initial impulse resistance is the surge that type of tower with the grillage type footing or earth
impedance of the counterpoise, which is usually greater anchor. The methods of calculating the tower-footing
than the 60-cycle resistance. Counterpoises are discussed resistance and the effect of surface have been worked out.“)
in the following section. This Jvork shoTvs the effectiveness of contact of the tower
In soils of low or medium resistivity, adequate ground- and counterpoise mith the soil. If the tolver inherent
ing can usually be obtained by driven ground rods. For construction does not naturally give a resistance to ground
these grounds the impulse resistance is usually less than low enough for an economical design the grounds can be
the go-cycle value. The ratio of impulse to 60-cycle re- improved by driving rods in and around the tolver footing
*The imageof a wire is the samedistancebelowthe groundsurface either during or following erection of the line. A practical
that the wire is abovethe ground surface. example of this is shoIvn in Table 7.
594 Line Design Based Upon Direct Strokes Chapter 17

TABLE ~-TOWER GROUND RESISTANCES, OHMS 1.6~ , , , , , , , , , ,

30 ft. Driven Ground Rod Test of Tower


\
Res. of Rod Ground at Ground Res. 1.6
30 ft. Rod
15 ft. 20 ft. 25 ft. 30 ft. Connected
--- .-
48 35 25 20 9.83
84 37.5 2.5 21 9.8
108 67 38 31.8 11.33
60 39 27 27 11.1 1.2
80 45 32 31 11.5

Chemical treatment of ground has been considered, but ’ ’


this has not been a satisfactory method for actual line 20 40 60 60 100
SPACING- FEET
design, it being used more for substation grounds. The
curves of Fig. 16 show that the size of ground rod does not Fig. 17-Ratio of resistance of ground rods in parallel to that
influence the resistance materially whereas the length is of isolated rods.
most influential. For this reason it is better either to use A-two rods, B-three rods, C-four rods.
small but long rods or many small rods. The curves of Ground rods are % inch diameter, 10 feet deep; 3 rods on equi-
Fig. 16 provide a method of estimating the number of lateral triangle, 4 rods on square.
rods necessary to reduce the tower-footing resistance to a Taken from H. B. Dwight paper “Calculation of Resistance to
Ground.”

counterpoise should be used and advantage taken of it.


This should not, however, be allowed to dictate, as leak-
age resistance and initial surge impedance are more im-
portant factors in selecting a successful counterpoise.
A wire or counterpoise buried has an initial surge im-
pedance depending somewhat on soil conditions but this

” ”
6 6 ID 12 14 16 IS, 20 22 24 26 26 30 32
DRIVEN DEPTH-FEET

Fig. 16-Resistance to earth of driven rods for three different


diameters and a specific resistance p = 1000 foot ohms.
Curves taken from H. B. Dwight “Calculation of Resistances to
Ground,” A.I.E.E. Transacfions. December, 1936.
where L = length in cm. and a = radius of rod

specific magnitude provided the resistivity of the soil is


known. These are based on resistivity of 1000 foot ohms.
For other resistivities the curve can be varied directly in
proportion to the changed resistivity. The curves of Fig. 17
show the effect of increased number of rods for different
spacings.
The counterpoise is a practical means of reducing the 40
resistance by increased area of earth in contact with the 30
grounding system. This is nothing more than a conduc-
tor buried in the ground, it being run parallel to or at 20
some angle to the line conductors themselves. The paral-
lel counterpoise as compared to one at right angles gives IO

a little more coupling with the line conductor. This in- I I II I


I
I LEAKAGE RESISTANCE+
I I 2.
0’ ’
crease in itself is so small that it need not be considered 0 I 2 3 4 5 6 .,: y.
in the calculation but rather taken as an additional factor MICROSECONDS
of safety. At the most this could be ten percent but usu- Fig. 18-Effect of number of wires on the counterpoise
ally it is less than five percent. If possible a parallel impedance.
Line Design Based Upon Direct Strokes 595

is about 150 to 200 ohms. As the surge current travels 60


along the counterpoise this initial surge impedance is re-
duced to the leakage resistlance in a time depending upon
t,he length of the counterpoise and the speed of propaga- 50
tion of the surge. In general, t,he surge travels at approxi-
mately one-third the speed of light so that a lOOO-foot
counterpoise has an initial surge impedance of approsi- !G
g 40
mately 150 ohms and at the end of six microseconds an I
effective resistance equal to the leakage resistance. Like- E
wise, a 250-foot counterpoise has an initial surge im- %
perlance of 150 ohms but reduces to the leakage resistance Id
c 30

in 1.5 microseconds. This indicates the desirability of


ki
using many short counterpoises instead of one long coun- f
terpoise as the leakage resistance is dependent largely 2 20
upon surface area so that this is the same whether one Fl
ii
lOOO-foot counterpoise or four 250-foot counterpoises are
used. On the other hand, the counterpoise of four 250- IO
foot sections has an initial surge impedance of 37.5 ohms
and reaches the final leakage resistance in 1.5 microseconds
as compared to 150 ohms and 6 microseconds for the
0
1600-foot counterpoise. The one important point in 0 100 200 300 400 500 )O
applying this rule is to be sure that the leakage resistance LENGTH-FEET
of the counterpoise is lower than the initial surge imped- Fig. ZO-Resistance to earth of +&-inch single counterpoise for
ance, otherwise positive reflections result and the tower two depths Cp= 1000 foot ohms).
footing is raised rather than lowered. The curves of Calculated from H. B. Dwight paper “Calculation of Resistance
Fig. 1P illustrate the above discussion. Some of the to Ground.”
R=&(log.F+log,$-2+$-&)where
2L =length in centimeters, S =distance wire to image in centi-
meters, and
a =radius of wire in centimeters.

25 ohms. Driving four 32.0 foot long x-inch diameter


rods on the corners of a 30-foot square would give a re-
sistance of 25 ohms (Figs. 16 and 17). The resultant re-
sistance of this combination is 12.5 ohms. Or with 200
feet of wire buried 3 feet deep the resistance is also 12%
ohms (Fig. 20). Omitting the time factor for going from
the initial to the final or steady-state impedance of the
Fig. 19-Arrangements of counterpoises. counterpoise is not serious where the counterpoise is short

arrangements of counterpoises that have been used in


actual tower construction are shown in Fig. 19.
The steps necessary to apply counterpoises properly are
given in the E.E.I. report F6 by Merril DeMerit.20 This
takes into account all surface factors. A close estimate
can be obtained by driving say an eight-foot rod and from
the proper resistance curves arrive at an average specific
resistance for the soil. Reference to counterpoise curves
for this specific resistance shows the leakage resistance of
counterpoise of different lengths or reference to the resist-
ance curves for driven rods gives the effectiveness of rods
in reducing the ground resistance. Mr. DeMerit’s curves
indicate 10 ohms tower-footing resistance for a specific re-
sistance of 1000 ohms and proportionately higher for
higher earth resistances. Thus knowing the resistance of LENGTH-FEET
the elements of the circuit a prediction of the results can Fig. 21-Resistance to earth of two parallel s/8-inch counter-
be made. poises plotted for two separations at a depth of 2 feet (p = 1000
For example, assume by driving an eight-foot ground foot ohms).
rod the specific resistance at a tower location is calculated Calculated from H. B. Dwight “Calculation of Resistance to
to be 2500 ohms. The expected resistance of the tower is Ground.”
596 Line Design Based Upon Direct Strokes Chapter 17

as the average rate of rise of potential in t,he stroke is some belief that the impulse characteristics of the insulator
such that the effect of this time element is negligible. string were improved. The use of high-speed clearing of
The question arises as to the proper depth to bury the faults and improved porcelain have practically eliminated
\vire. .1s shown in Fig. 20 the depth does not materially the first reason. It is nom found that any device that tends
affect the resistance of the counterpoise. It is necessary to prevent cascading of the arc over the insulator reduces
to bury only deep enough to prevent theft. the impulse strength of the insulator.
Where it is necessary to bury more than one counter-
poise in each direction from a tower and when the lvidth 14. Size and Spacing of Insulators
of right-of-way dictates parallel counterpoise there is the The standard porcelain insulator is one having a shell
qllcstion of the proper distance between t,he wires. The 10 inches in diameter and a spacing of 5% inches from
c~~rvesof Fig. 21 indicate that the 150-foot spacing lowers center to center. It is not difficult to increase this spacing
the resistance a small amount below that of the lo-foot between discs, and consideration has been given to
spacing. Therefore the spacing should be as large as pos- changing the diameter of the porcelain. The impulse char-
sible. Usually it is possible to space the counterpoise acteristics of three different diameters with three different
lvircs at least as far apart as the two outside conductors. spacings are presented in Fig. 23.2ZThey show, for instance,
In gcncral it is possible to space them 40 feet apart, which that 16 insulators, 4x-inch spacing have a somewhat lower
gives approximately the results of the 150-foot curve. impulse strength than 16 insulators with GM-inch spscing.
The fact that, tl~pt,h is not, a great, factor in securing low The cost of a power line is, however, determined more by
the steel than by the number of insulators in the string.
The 16, 6%-inch spaced units require more steel and great-
er spacings to maintain proper clearances than the shorter
spaced units. Or, in other words, for a given length of
insulator string fixed by tower construction the closer
spaced units will give a higher overall impulse strength.
Likewise, as the diameter of the insulator is increased the
impulse strength is slightly increased. Increasing the
diameter and shortening the spacing naturally increases
the cost of a given string length. The correct selection
therefore is a compromise between cost and performance.
The lo-inch 5x-spaced units is a satisfactory compromise.
LENGTH OF ARM-FEET The flashover characteristic curvesof Fig. 23 for standard
insulators do not agree with the standard insulator curves
Fig. 22-Resistance toearth of 3/-inch four-point star counter- of Fig. 5. The curves of Fig. 5 are the accepted curves for
poise plotted for two depths Cp= 1000 foot ohms). determining flashover characteristics of standard insulators
Calculated from H. B. Dwight “Calculation of Resistance to since they are based on more recent laboratory tests made
Ground.” since the standardization of laboratory techniques. The
curves of Fig. 23 should be used only for comparing the
impulse flashover characteristics of insulators of various
Where L = length of arm in centimeters. diameters and spacings.
S = dist,ance wire to image in centimeters.
n = radius of wire in centimeters. 15. Wood Construction
Many forms of wood construction are available. One
leakage resistance for the counterpoise is again illustrated consists of a steel tower, wood crossarms and’ttsuspension
in the curves of Fig. 22, calculated for a four-point star insulators. The wood insulation plus the ins&lators in-
counterpoise. creases the overall impulse strength. The design factors
are the same as above except the advantage of wood insu-
12. Clearances lation can be utilized up to the point of the next weakest
Air clearances must be large enough to have as great path, which is probably from the conductor to the steel
an impulse breakdown as that over the insulation itself. tower with conductor swing. In order to arrive at the
That is, in calculating the protection or probability of design constants it is necessary only to determine the
outage of a line it is essential to use the lowest figure of weakest point in the design, convert this into equivalent
impulse-breakdown strength whether it be over the insu- insulators and apply the curves directly.
lator string or whether it be from the conductor to ground The data are equally applicable to all wood construction.
point. An easy method of checking this for air clearances For example assume a 115-kv H-frame line with the
as compared to that of the standard insulator unit is shown dimensions shown in Fig. 24. As in the case of the steel
in Fig. 5. design the ground wires must be placed to form an angle
of 30 degrees or less on the level. If the line is to be on a
13. Arcing Rings hillside the slope of the hill must be subtracted from the
Arcing rings or arcing horns were once quite popular. 30 degrees. The use of a second crossarm to support the
It was reasoned that if properly designed the 60-cycle arc ground wires as shown in Fig. 24 (a) may save in cost, as it
would be kept clear from the porcelain., and also there was allows the use of shorter poles in securing the protective
5001 I , , I ,
6 8 IO I8 20 22 6 8 IO 12 14 16 18 20 22 6 8 IO 12 14 16 18 20 22
NUMBER OF UNITS NUMBER OF UNITS NUMBER OF UNITS

2100

1900

1700

: 1500
i
2 300
:’

I I 00

900

I I I
/
I
12 14 I6 18 20 22 6 8 IO 12 14 16 18 20 22 6 8 IO I2 14 16 18 20 22 *
NUMBER OF UNITS NUMBER OF UNITS NUMBER OF UNITS

a,OO 12” DIAM. 4-3/4” SPACING (/(


I A’ I/

1900

1700

F 1500

700

5007 1
6 8 IO I2 I4 I6 I8 20 22 6 8 IO 12 14 I6 18 20 22 6 8 IO 12 14 I6 18 20 22
NUMBER OF UNITS NUMBER OF UNITS -NUtiiER -OF UNITS
Fi& 23-Time-lag flashover characteristics of suspension insulators of various sizes and spacings. All values are based on
11/,X40 positive waves and humidity corrected to 6.5 grain.
598 Line Design Based Upon Direct Strokes Chapter I7
,
angle. This will act also as a brace and may reduce the GROUND WIRE
necessity for elaborate X-braces below the conductors.
Alany combinations are given in the article by Mr. \
Saney.?3 This fixes the height of ground wire. Seven
insulators f7 feet of wood is equivalent to 695+700 kv
or a total of 1395 kv where a good average value of wood
is taken as 100 kv per foot for the long times to flashover.
For detailed and close designs reference should be made to WOOD BRACES,
IF STEEL BRACES
the published data4,13’2J. The value B is 7 feet minus MAKE ALLOWANCES
2 feet or 5 feet in air, which has a minimum impulse level FOR LOSS OF CLEARANCE
of 9.50 kv when the insulator string is at an angle of 30
degrees. The total impulse strength for 7 feet of air is 1310
kv for the insulator in the vertical position. The line
strength is therefore 950 kv with high wind or 1310 kv
with no wind and not the strength developed by the wood-
arm plus the insulators shown above to be 1395 kv. The
figures, 950 kv and 1310 kv, are the equivalent of 10 in-
sulators or 14% insulators respectively. All the design
features can now be determined. For example, assume the ,!?-GROUND WIRE
line is designed for the full swing of the insulator or an
equivalent of ten insulators. The clearance from the con-
ductor to ground wire must exceed five feet. Satisfying the
protective angle assures this clearance. In the example
discussed above the midspan clearance is 14 feet, under
normal conditions. Referring to Figs. 4(c and i) and
assuming that 10 ohm tower-footing resistance is possible,
lib
w
0

\i
3-10” DISC
/INSULATORS
5-314” SPACING

POSSIBLE
CROSS CONNECTION

GROUND WIRES

t
A 7’-
t

B-
Fig. 25-Design of single pole structures based on direct
stroke theory.
rfif 2’
17-10” DISC the line should he good for 110 000 and 100,000 amperes
INSULATORS
5-3/4” SPACING SPAN LENGTH stroke current to tower and midspan, respectively with a

00
-8 : 600’ probability of outage of 0.6 per 100 miles per year for a
30-storm level. If the construction of Fig. 24 (a) is used
it might be necessary to use differential sagging, i.e., allow

K GROUND WIRES
.

the ground wire to sag less than the phase wires to obtain
adequate clearance at the midspan. Where sleet is a prob-
lem, this construction might not be permissible. In this
manner a design of wood-pole line can be developed from
the same curves. The procedure in arriving at dimensions
for other wood-pole constructions is the same as outlined
for the H-frame line.
In considering wood design the splitting of the wood is
quite serious. The ground wire and down lead protect the
pole but quite often the crossarms are shattered by the
stroke. The double crossarm, one on either side of the
pole, eliminates possible dropping of the line but does not
remove the shattering problem. Well-seasoned wood *P-
Fig. 24-Design of H-frame type of wood pole line based on parently is not as susceptible to shattering as green wood*
direct stroke theory.
This is true for poles as well as crossarms.
(a) Alternate plan using two crossarms permitting use of shorter The manner of grounding a wood-pole line depends on! j$
poles to secure 30 degree angle. soil conditions and may range from a butt wrap on the !f
Chapter 17 Line Design Based Upon Direct Strokes 599

pole, to the driving of ground rods, or to some form of In this type of construction, sometimes called the diverter
counterpoise as for a steel line. Wood poles must be guyed scheme, because up to the point of insulation flashover no
at corners or angle points. Care must be exercised in the current flows through the tower, the only stress on the
location of these as on improperly designed lines an undue insulators is the induced potential up to the point of flash-
proportion of outages will be concentrated at these points. over of the wood pole. Although the construction is very
If it is not possible to locate the guy to give adequate effective it does not lend itself to economical line design.
clearance, then wood strain insulation in the guy should be Another scheme used in connection with substations and
considered with horns used around this wood to eliminate suggested for lines, is to erect separate steel masts tall
splintering. enough to shield the phase wires from the stroke. This is
The ground wire is effective for lines with operating volt- practical only for shielding existing substations or very
ages above 31.5 kv where low ground resistances are se- special line cases. It is effective where high ground resist-
cured. The clearances commensurate with the construc- ance is encountered. Usually low ground resistance can be
tion for voltages lower than 34.5 kv are such that the use of obtained, which allows the direct connection of the ground
ground wires are questionable. Here reclosing breakers, wires to the steel supporting structures. In this scheme
&ion protector tubes and other forms of protection are no surge current passes through the tower and therefore
more practical. there is no tendency to flash over an insulator string.
16. Other Forms of Construction
IV. PROTECTION BY AUXILIARY DEVICES
.I short section of line was built with wood senaratinr
the steel structure from the ground wire. Here the ground- The second method of protection, making use of nusil-
ing was accomplished by separate guy wires as in Fig. 26. iary devices or non-shielding has been extensively used in
improving the performance of lines against lightning. Here
“-“- I
the path of the discharge is controlled and some device
used to extinguish the power follow arc.
Several devices have been used, such as lightning ar-
resters, fuse arcing links, and protector tubes. The light-
ning arrester is too expensive for general application and

Fig. 26-Wallenpaupack-Siegfried 220-kv line with ground Fig. 27-Protector tubes on steel tower, 66-kv line of the Inter-
wires designing based on diverter principle. state Power Company and cross section of a typical tube.
600 Line Design Based Upon Direct Strokes Chapter 17

follow; so for satisfactory operation, the protector tube


must recover its insulation strength after generated-cm-
rent zero faster than the system voltage rises\ This can
best be explained by considering the recovery voltage on a 1
simple circuit. .&.+.
The circuit shown in Fig. 28 possessesthe basic elements :$
required to illustrate the transient recovery voltage, fol- ,/’
lowing interruption of fault current. This circuit contains :,,
lumped constants of L, R, and C in such proportion that it ‘“:
will have a natural frequency of oscillation. When a fault .’
is placed at F and later removed at a normal-current zero, ‘,
an oscillating voltage appears across the condenser. It is ::
composed of the normal-frequency voltage and a voltage .
whose frequency corresponds to the circuit’s natural fre-
quency. The simplest method of developing the oscillating
(b) voltage is to consider the generated voltage and oscillating
voltage separately. At the instant the fault is removed, the
voltage across the fault must be zero. This condition of
zero voltage is satisfied if it is assumed that there is a nat-
ural frequency voltage that appears instantly equal and
opposite in magnitude to that of the generated voltage.
The sum of these two voltages En is therefore the recovery
voltage of the circuit. The time to -crest of the oscillation is
approximately proportional to dLC. Therefore if either
Fig. 28-Elements of recovery voltage. L or C is increased, the time to the recovery voltage crest
E,-generated voltage, I,-generated current. of the natural-frequency oscillation increases. This con-
ER--protector tube voltage. ception is important as the L of the source and C of the
EN-nnturtll frequencyvolt:Lge. line differ for different line conditions. Theoretically, the
natural-frequency voltage starts equal to the generated
has not been extensively used. The maintenance of the voltage at the instant the fault is removed assuming no
fuses on the arcing rings made their application limited. losses, and oscillates about this voltage as an axis. How-
The most popular device at present is the protector tube. ever, losses produce damping and this natural-frequency
This device is simple both in construction and in opera- component decays at a rate depending upon the losses in
tion. Basically it consists of a fiber tube with an electrode the circuit.
in each end and is applied so that the impulse breakdown When a protector tube discharges lightning and power
through it is lower than that of the insulation to be pro- current follows through the tube, it must have the prop-
tected. On a transmission tower one tube is often mounted
below each conductor so that the upper electrode is con-
nected to an arc-shaped horn located the proper distance
below the conductor, thus forming a series gap with the
conductor. The lower electrode is solidly grounded. When
a surge appears on the conductor, the series gap is spanned
and an arc is formed in the tube between the electrodes.
The heat of the arc vaporizes some of the fiber of the tube
walls, the resulting neutral gas being expelled violently into
the arc stream sufficiently deionizing it to prevent the arc
restriking after the first zero point of the 60-cycle power
current. Since the protector tube is the most practical ?
auxiliary device available at present, to improve the per- P
formance of lines against lightning, this discussion is con-
fined to it.
I 17. Theory of Tube Operation25
Since the protector tubes are to prevent flashover of line
insulation their discharge voltage must be lower than the
flashover voltage of that insulation. They must also be
capable of interrupting the generated follow current. Op-
eration of protector tubes can be more readily understood
by first considering the phenomena involved in current Fig. 29-Elements of protector tube operation.
interruption. After the surge currents are discharged to A-recovery voltage of complexsystem.
ground, the normal frequency or generated current may B, C, D-protector tube insulation recovery curves.
Chapter 17 Line Design Based Upon Direct Strokes 601

erties of changing from a good conductor to a good insu- For this reason the rate of erosion must be considered in
lator for satisfactory operation. In any interrupting device protector-tube design. Likewise, the same tube will have
it takes time to establish the insulating ohsractcristics, different insulation recovery curves for different, current.
which are commonly called the insulation recovery char- magnitudes. Curve d, Fig. 31, may he inslllnt,ion recovery
acteristics of the device. The interruption therefore starts
a race between the insulation recovery strength of the w
200
&vice and the voltage recovery on the system. Curve A of s
3 160
Fig. 29 is the recovery voltage for a more complicated sys-
tem. Instead of having simple oscillations as in Fig. 28 the ii 160
recovery voltage is now a more complicated function of
time as the result of a succession of traveling waves on the 2 140
zi
line. b I20
Curves B, C, and D of Fig. 29 are hypothetical insula- 7
tion-recovery curves for a protective device. If the pro- g 100
tective device has the characteristics shown in Curve B ?
< 60
3nd the system recovery characteristics are as shown in f
Curve A, then the interruption will be satisfactory, as the b$ 60
insulation recovery of the device is faster than the voltage IL
recovery on the system. On the other hand, if the pro- 0 40
tective-device insulation recovery strength is as shown in 5
y 20.
Curve C or Curve D, then the system recovery voltage over-
takes the insulation recovery strength at second or first E
O I 2 3 4 5 6 7 6 9 IO
crest, respectively, restriking will take place, and if this
HUNOREOS OF MICROSECONOS
occurs at more than two consecutive current zeros, the
operation is in general not considered satisfactory. It is Fig. 31-Effect of current on recovery voltage of protector tube.
therefore possible to predetermine the operation of tubes on A-characteristic curve for maximum current-1500 amperes.
a system by comparing the insulation recovery strength of B--characteristic curve for minimum current-500 amperes.
the tube and the system recovery voltage. C-characteristic curve for 1000 amperes,
The protector-tube insulation recovery curves and the
voltage recovery curves will differ for each current. For strength for maximum current, and the insulation recovery
a given short-circuit current the protector-tube insulation strength for minimum current might be of the order of
recovery curves also are lower with increased bore. Thus, Curve B, of this figure.
if the protector tube, when new, starts with a character- It is important that the system recovery voltage curves
istic such as shown in Curve B, Fig. 30, as it erodes the bore be compared with the insulation recovery strengths of the
will increase and the curve will drop until at Curve C it protective device to see that operation will be correct. The
will fail to give satisfactory interrupting characteristics. following discussion will therefore deal with system char-
acteristics and protector-tube characteristics showing how
this has been done to arrive at a standard line of protector
tubes.
18. Protector-Tube Characteristics
The requirement that the breakdown voltage of a tube
must be lower than that of the line insulation naturally
limits the length of air between the inner electrodes as
well as limits the length of gap external to the tube, as the
sum of these two gaps determines the breakdown voltage
of the device. The external series gap is provided for the
purpose of withstanding normal impressed voltage to avoid
possible corona or leakage currents across the protector
tube itself under normal operating conditions. The im-
pulse breakdown voltage level of protector tubes is best
shown in the form of volt-time curves. The characteristics
of a large number of different voltage ratings for the posi-
tive 155X40 wave are given in Fig. 32. The volt-time
characteristic of the protector tube is flatter than practic-
ally all forms of insulators. Thus it can be applied by
simply comparing the critical voltage of the tube with the
critical voltage of the insulators to be protected.
Fig. 3QEffect of erosion on protector tube operation. To simplify the application of protector tube, Table 8
A-recovery voltage of complex system. not only shows the discharge level of protector tubes, but
B, C-protector tube insulation recovery. also includes the minimum string metal-to-metal arcing
602 Line Design Based Upon Direct Strokes Chapter 17 ‘j

that lightning flashover will be confined within the pro-


tector tube itself.
The ability of a protector tube to operate’properly is a
function of the insulation recovery characteristics of the
protector tube for a fixed short-circuit current. This in-
sulation recovery characteristic varies with the magnitude
600 of short-circuit current through the protector tube. These
properties are illustrated in Fig. 31. Likewise, the insula-
tion recovery for a given current is dependent upon the
bore. As the bore of the tube increases in diameter the
clearing characteristics of the tube undergo a change, the
effect being to lower the insulation recovery characteristics
of the tube with increased diameter. Likewise, the opera-
tion of the protector tube volatilizes fiber from the tube
wall with the result, that the bore increases with each
operation. This characteristic necessitates the selection of
a bore such that after a given number of operations the
46 KV
insulation recovery strength of the tube is still high enough
to permit satisfactory performance. These characteristics
200 34.5 KV
are illustrated in Fig. 33.
Actual measurements of the bores of protector tubes
23 KV after years of service show plainly that erosion of the bore
by repeated operation does not, seriously affect tube life.
On one line of one thousand tubes with ratings of 600 to
2000 amperes none were foundz6 after five years of service
to have reached the end of their useful life. A similar
I 1 I 1 1
’ 2466 IO 12 14 16 studyZ7 on tubes rated at 1000 to 4000 amperes on a 132-kv
MICROSECONDS system showed a total of 63 operations in four years but
Fig. 32-Volt-time curves of De-ion protector tubes (Positive
measurements of the erosion of the tubes indicated that the
11/2X40 microsecond wave). bore was still within the manufacturing tolerance used at
the time of assembly of the device. The rate of erosion
distance that the tube is expected to protect. These figures might. be considerably increased if used for the protection
include a factor of ten percent between the actual discharge of disconnecting switches or the like where the tube pro-
voltage of the protector tube and the impulse flashover vides the only path for a long length of line.
voltage corresponding to the dry arcing distance. Suffi-
cient clearance should be provided between the protector
tube and the structure to which it is attached to be sure
v) 900
ii
TABLE 8 g 600
a
Protector Tube Impulse Discharge ; 700
Tube Discharge(l) Voltage Characteristics zl
Critical Voltage - oz 600
Representative Number ?I
Circuit v 500
Value Dry IMin. Dry Standard
Voltage g
1%X40 Wave Series(*) Arc Dis- Ins. Discs 5 400
Rating
Gap t anceTube Tube Will
‘II
Inches Will Protect 0 300
Protect 5%X10” I
Pos. Keg.
Spacing 1 200
___- -- z
13.8 100 110 M 6” 1 s 100
23 150 155 1% 9” 2 III III1 II III
34.5 200 220 2 12%” 2 01 ’ 1 1 1 1 1 1 1 1 1 1
100 120 140
46 260 285 3% 17” 3
DIAMETER OF BORE IN PERCENT OF ORIGINAL
60 375 420 5% 28” 5
92 475 540 SW . . 6 Fig. 33-Effect of erosion on minimum current required for
115 575 1 635 I1 A 7 interruption.
“‘Actual Values will vary somewhat, depending on the design and Time to recovery voltage crest 160 percent normal line to n&J&*
mounting of the tube. A-200 microseconds.
(*‘These arc recommended minimum series gaps. Under no con- B-500 microseconds.
ditions of operation should the series gap be less than 80% of the C-1000 microseconds.
recommended minimum. D--2ooO microseconds.
Chapter 17 Line Design Based Upon Direct Strokes 603

In general, the protector tube can withstand lightning device. Likewise, since current is an important factor in
stroke currents of 50 000 to 100 000 amperes on the basis the correct operation of this device, the maximum and
of a current wave that rises to crest in 10 microseconds and minimum current must be calculated for the range of
decays to half value in 20 microseconds. Experience to system operating conditions. Such calculations should be
date with a large number of tubes shows that the probabil- made for the single, double, and three line-to-ground fault
ity of failure from lightning is small, allowing the conclu- currents and naturally the corresponding recovery volt-
sion that the impulse discharge capabilities of protector ages must be evaluated. h number of factors will deter-
tubes are sufficient to withstand all but the most severe mine the magnitude of the currents and the associated
&reCt strokes. recovery voltages. For example, the method of grounding
Experience with modern finishes indicates that the tube the neutrals (solid grounding, resistance or reactance
11:~s good weathering characteristics. The exact perform- grounding, or any combination of these), maximum and
ance will depend on local atmospheric conditions. Period- minimum connected capacity (variation in operating con-
ically applying a good paint to the protector tubes in- ditions), length of connected circuit or lines in miles, rela-
creases their weather resistance as well as improves the tive location of short-circuit current sources, line configura-
electrical characteristics of the exterior. tion and presence of overhead ground wires, tower-footing
The operation of the protector tube results in the ex- resistance, and protector-tube location. The method of
pelling of ionized gases that must be properly directed to making short-circuit calculations will be found in reference
avoid flashover from live conductors to ground. Experi- 28. The method of determining recovery-voltage char-
ence with the application of a large number of protector acteristics of systems has also been defined in the printed
tubes indicate that this is not a serious requirement, and matter2g~30*31.For this reason these methods will not be
can readily be satisfied with the available mechanical set- reviewed at this time.
tings, and arrangements of tubes. When arranging the
mounting of the protector tube, care must be taken to 19. Selection of Tube Rating
direct the discharged ionized gases so as to avoid flashover In order to facilitate the selection of tubes, Table 9 has
to another phase or to ground. The length of visible flame been prepared. This table shows that if all factors are
path as a function of the power current and voltage is checked for a given application, the selection of the proper
shown in Fig. 34. Obviously, the circuit voltage and the protector tube is not complicated. The table is prepared
on the basis of a solidly-grounded neutral system which has
all sources of short-circuit current solidly grounded. This
is representative of the type of system found particularly
at the higher operating voltages. The effect of tower-
footing resistance is to reduce the current and to reduce the
magnitude of recovery voltages across the tube. This
resistance reduces the recovery voltage because of the
improvement of the power-factor in the circuit, which
means that at current zero or time of interruption, the
instantaneous fundamental frequency voltage is of lower
magnitude than for a pure reactive circuit. However, there
is a lower limit to which the current can be reduced and
still have successful operation.
For practical purposes the effect of system neutral re-
sistance is similar to the effect of tower-footing resistance
discussed above. In cases where both neutral grounding
resistance and tower footing resistance are encountered,
LENGTH OF FLAME PATH -FEET they should be considered as being in series. Thus the
same limits apply as pointed out for solidly grounded sys-
Fig. 34-Visible flame path as a function of power current and
voltage.
tems with tower-footing resistance alone. If the sum of
those resistances is such that a single protector tube does
A-1500 amperes. not have the current range to interrupt both the phase
R-2000 amperes. currents not limited by resistance and the single line-to-
C-5000-6000 amperes. ground currents limited by resistance, then the use of four
protector tubes can be considered where three protector
Protector-tube dimensions should be considered when tubes of a high current rating are connected in star, and
establishing the safe strike distance from the gas envelope the star point connected to ground through a protector
to the object of different potential. Recoil forces must be tube of lower current rating.
considered when designing the mounting hardware. It is of When the system neutral (or neutrals) is grounded
importance that the mounting hardware be designed to through reactance, standard protector tubes for solidly
facilitate ease of installation. grounded service can be applied under conditions such
The normal rating of the protector tube is based on a that the zero-sequence reactance XO viewed from the
solidly grounded neutral system and any deviation from protector tube locations is not more than three times as
this should be taken into account in the application of the great as the positive-sequence reactance X1. When the
604 Line Design Based Upon Direct Strokes Chapter 17

TABLE ~-RECOVERY VOLTAGE CHARACTERISTICSFOR WHICH ratio of X0 to X1 is greater than this, special consideration
TUBES ARE DESIGNED must be eiven to the mote&or tube. However. in ma.nv 8
- J 7i
cases the protector tube for the next higher voltage Patina. :
hIinimum will be applicable. When the protector tubes are used on .:
m %
Maximum Current
Current
Tube - a systemusing a tuned reactance or using a ground-fault ‘i
Current Mns. Sig- IUris. Sig- neutralizer, the line-to-ground currents should not have pi
RatingcJ’ nificant 1st Crest nificant to be cleared by the tube. Thus protector tubes built for
Crest
-
Crest line-to-ground voltage can be applied on the basis of the
- -
line-to-line fault, currents only.
Per- ‘er- ‘er-
Protector tubes applied on an isolated-neutral system
cent ‘ime ent ent ‘ime
51Yin.(4 ‘imc must be given special consideration, as the single line-t,+
v’o1t- [icro- ‘OlL dolt/
sec. w w
ground current (charging current,) will usually be below
we -
-- the minimum current rating for the suggested standard
13.8 300 1500 160 230 90 55 165 130 tube. In connection with the application of protector
400 3000 160 230 90 35 160 120 tubes to isolated-neutral systems consideration should be
600 6000 160 200 90 25 160 120
given to the four-tube scheme as such a scheme should ewe
300 1500 165 400 73 65 165 250 the problem of interrupting charging current.
400 3000 165 400 86 45 160 190 To facilitate the selection from a recovery-voltage view-
600 6000 165 400 94 30 158 190 point the reactance of the various ratings, in combination
.5 3oa 1500 170 600 65 80 165 390 with a given length of line was set down. Column 2, Table
400 3000 170 600 85 60 159 270 9, gives the lower limit, of line that should be considered
600 6000 li0 600 100 50 156 270 without making a detailed calculation. Actually however
the recovery-voltage characteristics given in the last six
46 3oc 1500 165 800 i0 115 165 530
columns should be taken as the limits for the standard
4oc 3000 165 800 90 80 159 370
750 105 70 153 330 protector tube and the recovery voltage for a given applica-
9oc 6000 165
tion should be less severe than herewith listed. The four
69 4oc 1500 165 1100 85 180 165 800
6OC 3000 165 1100 105 140 158 590
9OC 5000 165 900 115 100 149 490
92 I 4oc 1500 160 1300 88 240 165 1070
60( 3000 160 1300 104 220 157 930
lOO( 5000 160 1100 115 180 145 760
115 1 5oc 1500 160 1450 90 300 165 1350
60( 3000 160 1450 98 300 156 1270
lOO( 5000 160 1350 105 300 140 1100
138 ) 50( 1500 160 1600 90 350 165 1440
60( 3000 160 1600 90 350 155 1320
- -lOO( 5000 160 1500 - 90 -390 -136 1250
(1) Miles listed are the minimum circuit milts of overhead line con-
nected or equivalent where the line has a single source of short
circuit current at one end. Cable should be reduced to the equiva-
lent miles of overhead line as indicated in Fig. 35.
(2) When two sources of short circuit current are available, the
miles of line in Column 2 should be increased by a factor K, deter-
Fig. 35-Overhead line equivalent of cable.
mined from Fig. 36. If less miles of line between sources are available
than required by the use of Fig. 36 but more than shown in Column 2, - - - Single conductor
then a detailed calculation is necessary for the application. __ Three conductor
(3) Guide for application when minimum current is limited by For paper insulated cable assumed dielectric constant 3.8 (For
resistance. varnished cambric or rubber insulation multiply by 1.35).
The minimum current rating which is assigned to standard pro- Overhead line equivalent based on positive sequence capacity,
tector tubes is based on the short circuit current through the tube susceptance of 6.0 micromhos per mile.
being limited predominantly by inductive reactance. The protector
tubes will actually interrupt currents as low as 85 per cent of their
minimum nameplate rating for circuits 69 kv and above or 70 per having the next higher voltage rating, this higher voltage Protector .*
cent of their minimum current rating for circuits 46 kv and below, tube will interrupt lower than the listed
where circuit resistance (tube grounding resistance) is included, To determine the minimum current which
provided the calculated minimum current neglecting all resistance interrupt when used on a circuit below its v
is equal to or greater than the tube’s minimum nameplate rating. the normal minimum current rating of the
(4) Standard Tubes Operating at Reduced Voltage. ratio of the lower operating voltage on whi
Where the minimum line-to-ground current of the circuit is below used to the normal voltage rating of the prot
the minimum current rating assigned to standard tubes, and the value of current can be considered as
insulation of the circuit is high enough to permit the use of a tube only and applied in the same way stand
Chapter 17 Line Design Based Upon Direct Strokes 605

RIGHT ANGI

A
I i i i i i’-i,i i i i i I 3k
‘ROTECTOR
TUBES

DESIGN USING :SIGN USING


TWO PROTECTOR THREE PROTEC-
TUBES ON WISH- TOR TUBES ON
BONE CONSTRUC- WISHBONE CON-
TION WITH 3 DISC (a) STRUCTION WITH (b)
CURRENT FROM LARGEST SOURCE IN PERCENT INSULATORS. 3 DISC INSULATORS.
OF TOTAL THREE-PHASE FAULT CURRENT

Fig. 36-“K” factor for line with two sources. GROUND WIRE

PRO ECTOR TUBE /I-GROUND WIRE

6
I
I
\

OESIGN USING
PIN INSULATORS, DESIGN USING
ONE PROTECTOR ONE GROUND
TUBE 8 GROUND WIRE ON WISH-
WIRE, TWO CROSS BONE CONSTRUC.
ARM CONSTRUC- TION EL 3 DISC
DESIGN USING (cl
TION. INSULATORS.
DISC INSULATORS
d ONE GROUND Y

Fig. 38-Types of protection for wishbone constructed lines.


OR
for tubes rated at 3000 amperes, and three operations for
tubes rated at 1500 amperes, at maximum rated current
with fully offset current wave after which the protector
tube will be required to clear two operations at minimum
rated current and with the associated recovery voltage.
The tube performance is based on interruption of the cur-
rent actually obtained during the one test at maximum
rated current in less than l/60 second and the minimum
rated current in less than l/40 second.
The maximum symmetrical nameplate rating in Table 9
is based on the maximum crest current that the tube will
stand divided by a factor of not less than 2.5 to take into
account the effect of asymmetry. The minimum sym-
metrical rms current rating is based on the minimum crest
current divided by 1.41 to convert to rms amperes.
Service experience shows that systems using protector
tubes should not have relay settings less than two cycles.
Fig. 37-Protection methods for some typical lines. Where relays have a shorter operating time, it will be
necessary to introduce a delay to prevent unnecessary
noteson the bottom of Table 9 give some rules for apphca- circuit outages. The best possible protection is secured
nons for other than standard condition. when all insulation structures on the line are protected.
When some are not protected, the degree of lightning pro-
20. Correct Operation tection will be decreased, the degree of protection depend-
Protector tubes are designed to withstand one operation ing on span length, insulation strength, ground resistance
fer tubes rated at 5000 and 6000 amperes, two operations and tube breakdown.
606 Line Design Based Upon Direct Strokes Chapter 17 $
2’

MICROSECONDS

100
0 I 2 3 4 5 6
I
7
MICROSECONDS

Fig. 39-Design of single- and double-circuit pole tops.

In applying tubes it is necessary simply to observe the the upper conductor instead of the ground wire. The sim-
limits as far as 60-cycle currents are concerned and see plest method of correcting this difficulty, if a ground wire
that the breakdown of the tube is lower than the insulator is present, is to install a protector tube on the insulator on
to be protected. Clearances, of course, should be adequate the upper crossarm, Fig. 37 (a). The lower arm is now
to assume that the surge will flow through the tube rather shielded and fair, performance will be obtained depending
than over the insulator structure. A large number of on the length of crossarm and value of ground resistance*
arrangements have been used. If no ground wire is present the cheapest and most ef-
fective method of reconstruction would be to remove the
21. The Conductor-A Ground Wire
upper crossarm, install an insulator on the top of the Pole
On many miles of line now in operation improved per- with a protector tube as shown in Fig. 37 (b). Again, 80
formance would be desirable. The construction of Fig. 37 extension to the pole can be considered as in Fig. 37 (0)
(d) has been used extensively and the outages will be high. but usually this is difficult and expensive. Suggestions f”‘;
In some cases a ground wire is used on the spare space on reconstructing a line built of the wishbone type of co*:
the upper crossarm, Fig. 37 (a), but even with low ground struction are given in Fig. 38. /.
resistance there is an even chance that lightning will strike In building a new low-voltage line where low ground 4~”
;gu
chapter 17 Line Design Based Upon Direct Strokes 60'i

upper wire is a ground wire. Fig. 41 illustrates a number


of methods of mounting protector tubes.

REFERENCES
1. Theoretical and Field Investigations of Lightning, by C. L.
Fortescue, A. L. Atherton, and J. H. Cos, A.I.E.E. Transac-
PROTECTED POLE FOR ALL tions, V. 48, April 1929, pp. 449-468. (Also A.Z.E.E. Lightning
Reference Book, pp. 395-414.)
2. Direct Strokes -Not Induced Surges-Chief Cause of High-
Voltage Line Flashover, by C. L. Fortescue, The Electric JOUT-
nal, V. 27, August 1930, pp. 459-462. (Also A.I.E.E. Lightning
Reference Book, pp. 546-549).
3. Lightning Discharges and Line Protective Measures, by C. L.
Fortescue and R. N. Conwell, A.I.E.E. Transaclions, V. 50,
September 1931, pp. 1090-1100. (Also A.Z.E.E. Lightning
Reference Book, pp. 801-81 I).
DISTANCE BETWEEN TUBES -FEET 4. Mechanical Characteristics of Transmission Lines, by L. E.
MAXIMUM Imlay (a book). East Pittsburgh: Westinghouse Technical
Night School Press (1928).
5. Ice-Coated Electrical Conductors, by A. E. Davison. ‘Paper
presented at the Conference Internationale des Grands Reseaux
Electriques a Haute Tension at Paris, France, on July 1, 1939.
6 Shielding of Transmission Lines, by C. F. Wagner, G. D. hlc-
Cann, and G. L. MacLane, Jr., A.Z.E.E. Transactions, V. 60,
1941, pp. 313-328.
7. Transmission and Protective Equipment, by J. J. Torok, W. It.
Ellis, A. C. Monteith, and Edward Beck, The Electric Journal,
V. 30, June 1933, pp. 253-257, July 1933, pp. 290-293, August
1933, pp. 347-352, September 1933, pp. 381-387, November
1933, pp. 467-71, December 1933, pp. 515-517, V. 31, February
1934, pp. 72-75, April 1933, pp. 151-155.
8. Transmission Line Design and Performance Based on Direct
Lightning Strokes, E. L. Harder, J. M. Clayton, A.I.E.E.
Technical Paper 49-111, 1949.
9. Experience with Preventive Lightning Protection on Transmis-
sion Lines, S. IS. Waldorf (Discussion C. F. Wagner, G. D.
McCann). A.Z.E.E. Transactions, V. 60, 1941, page 702.
10. A Large-Scale General-Purpose Electric Analog Computer, E.
DISTANCE BETWEEN TUBES-FEET
MAXIMUM L. Harder, G. D. McCann. A.Z.E.E. Transactions, V. 67, 1948,
pages 664-73.
Fig. 40-Curves showing required location of protector tubes. 11. Hydrometeorological Report No. 5-Part II, Hydrometeorolog-
ical Section Office of Hydrologic Director, U. S. Weather Bureau,
A-single-circuit pole line. B-double-circuit pole line.
Aug. 1945. (for storms in U.S.)
12. The Distribution of Thunderstorms in the United States 1904-
sistsnces are expected the construction of Fig. 37 (b) will 33, W. H. Alexander, Monthly Weather Review, V. 63, 1935,
no doubt be the most economical. If high resistances are page 157. (for storms in Canada)
present it will be necessary to use three tubes per pole. 13. What Wood May Add to Primary Insulation for Withstanding
Lightning, J. T. Lusignan, Jr., C. J. Miller, Jr., A.Z.E.E. Tram-
‘Thespacing of the tubes will be dependent on span length
a&ions, V. 59, September 1940, pp. 534-40.
aad ground resistance. A large amount of line has been 14. Lightning Performance of 110- to 165-Kv Transmission Lines
built in accordance with the construction of Fig. 37 (b). by Philip Sporn (Committee Report), A.I.E.E. Transactions,
The details of construction and the factors used by Public V. 58, June 1939, pp. 294-304.
Service of New Jersey were covered in a paper “Lightning 15. The Effect of Corona on Coupling Factors Between Ground
Protection of Wood Pole Lines 40-22” by Sels and Goth- Wires and Phase Conductors, G. D. McCann. A.Z.E.E. Trans-
berg presented at the A.I.E.E. Midwinter Convention actions, V. 62, 1943, pages 818-26.
1940. Figs. 39 and 40 show the data presented and ar; 16. Lightning Surge Effects on Transmission Lines, G. D. McCann.
Givenhere as they represent practice with which there has Electric Light and Power, (Chicago, Ill.) May 1945, pages 76-84.
been experience. Although the curves are applicable for 17. Minimum Insulation Level for Lightning Protection of Medium-
Voltage Lines, H. N. Ekvall, A.I.E.E. Transactions V. 60, 1941,
the 26kv circuits they can be used to approximate the de-
pages 128-32.
%n proportions for lines up to 66-kv as the only difference 18. Impulse and 60-Cycle Characteristics of Driven Grounds, P. L.
‘vould be in the pin-type insulation used. As the curves Bellaschi. A.I.E.E. Transactions, V. 60, 1941, pages 123-28.
shcw, the lower the ground resistance, the more effective 19. Impulse and 60-Cycle Characteristics of Driven Grounds-II,
the scheme. The curves in Fig. 4 can also be used for esti- P. L. Bellaschi, R. E. Armington, A. E. Snowden. A.Z.E.E.
mating the possible performance on the basis that the Transactions, V. 61, 1942, pages 349-63.
Chapter 17 Line Design Based Upon Direct Strokes 609

?,J. Determination of Tower Ground Resistance and of the Count- 26. Experience with Protector Tubes, by E. Wisco and A. C.
erpoise Necessary to Reduce It to a Predetermined Value, by llonteith, The Electric Journal, Aug. 1938, pp. 299-300.
slcrrill DeMerit, E.E.I. Publication No. F6. 27. 132-Kv Line Modernized Economically with Prot,ector Tubes,
21, The Counterpoise, by L. V. Bewlcy, E.E.I. Publication No. PG. by E. WV.Hatz, Electric Light and Pozuo-, December 1939, p. 43.
22, Suspension Insulator Assemblies, J. J. Torok, C. G. Archibald, 28. S~mmelrical Components (a book), by C. F. Wagner and R. D.
:l.I.E.E. Transaclions, V. 51, September 1932, pages 682-89. Evans, McGraw-Hill Book Company, 1933.
23, Comparison of Protector Tubes and Ground Wires for 66 Kv., 29. System Recovery Voltage Determination by Analytical and
by E. P. Nancy, The Electric Journal, V. 35, August 1938, pp. A-C Calculating Board Methods, by R. D. Evans and A. C.
301-305. Monteith, A.Z.E.E. Transactions, V. 56, June 1937, pp. 695-705.
24, Lightning Strength of Wood in Power Transmission Structures 30. Recovery-Voltage Characteristics of Typical Transmission
by Philip Sporn and J. T. Lusignan, Jr., A.Z.E.E. Z’ransac~ions Systems and Relation to Protector-Tube Applications, by
V. 57, February 1938, pp. 91-101. R. D. Evans and A. C. Monteith, A.I.E.E. Transactions, V. 57.
25. Protector Tubes for Power Systems, by H. A. Peterson, W. J. August 1938, pp. 432-440.
nudge, Jr., A. C. Monteith, and L. R. Ludwig, A.I.E.E. Trans- 31. Voltage-Recovery Characteristics of Distribution Systems, R.
uclions, V. 59, May 1940, pp. 282-288. L. Witzke, A.Z.E.E. Technical Paper 49-53, 1949.
CHAPTER 18

INSULATION COORDINATION
Original Authors: Revised by:
A. C. Monteith and H. R. Vaughan A. A. Johnson

been made during the past 20 years in improving the d4

,I
NSULATION coordination is the correlation of the in-
sulation of electrical equipment and circuits with the sign of power systems and equipment with the result that
characteristics of protective devices such that the in- failure of major electrical equipment insulation is rare.
sulation is protected from excessive overvoltages. Thus in The problem of providing insulation properly coo&.
a substation the insulation of transformers, circuit break- nated with protective devices involves not only guarding
ers, bus supports, etc. should have insulation strength in the equipment insulation, but also the protection of the
excess of the voltage levels that can be provided by pro- devices themselves. To prevent damage to an arrester or a
tective equipment such as lightning arresters and gaps. protector tube, each should be applied on a system in such
The determination of the economic relationship between a way that it will discharge t.he excessive voltage safely to
the impulse strength of equipment insulation and pro- ground after which it will cease to carry current to ground,
tective voltage level provided by protective devices has Thus the arrester or tube must protect the equipment
received and continues to receive a great amount of study. insulation and be capable of restoring itself as an insulator
The basic concept of insulation coordination is illustrated against whatever system voltages might exist across it to
in Fig. 1. Curve A is the demonstrated impulse strength ground. The voltage to ground is determined for a system
of the insulation on a piece of electrical equipment which of given voltage largely by the method used for system
in operation is exposed to the hazards of lightning surges. grounding, the maximum voltage to ground usually being
Curve B is a protective level afforded by a valve type during the existence of a phase-to-ground fault. Rod gap8
lightning arrester. Thus any insulation having a withstand do not seal off after being flashed over and therefore the
voltage strength in excess of the insulation strength of circuit must be disconnected from the system to clear gap
breakdowns.
I. HISTORY
Coordination of insulation was not given serious con-
sideration until after the first World War, mainly because
of lack of information on the nature of lightning surges and
the surge strength of apparatus insulation. Since concrete
data were lacking on the actual surge strength of insulation
or the discharge characteristics of protective equipment,
early attempts at coordination were rul ‘-of-thumb methods
based on experience and individual ide s. The result wf18
that some parts of the station were o1 er-insulated while
0 I 2 3 4 5 6 7 8 9 IO others were under-insulated. Also, the gradual increasing
MICROSECONDS of line insulation in an attempt to prevent line flashover
Fig. l-Protection of insulation with characteristic of “A” by subjected the station equipment to more severe surg‘%
protective device with characteristic of “B.” and in many cases line flashovers were eliminated at thee*-
pense of apparatus failures. Growth of power system& de
Curve A is protected by the protective device of Curve B. mands for improved power service, and more economical
To protect insulation from excessive voltages the pro- system operation focused more and more attention on the
tective device must have a lower breakdown voltage. problems of surge voltages, adequate insulation, and $8
The insulation of electrical equipment in a station or ,I
protection.
substation is subject from time to time to momentary over- Thus during the period from about 1918 to 1939 co:-
voltages that may be caused by system faults, switching siderable work was done by individual investigator8 and 3L
surges or lightning surges. Except for special cases, over- laboratories in collecting data on natural lightning ana ‘!!.
voltages caused by system faults or switching do not cause developing insulation testing methods and
damage to equipment insulation although they may be Although progress was seemingly slow, it resul
detrimental to protective devices. Overvoltages caused by knowledge of the nature of lightning surges an
lightning are of sufficient magnitude to flashover or break- lishment of universal surge producing and mea
down equipment insulation and are therefore the most vices. Very little correlation between laboratories
troublesome and of greatest concern to the manufacturers attempted during that period.
and operators of electrical equipment. Great strides have In 1930, the NEMA-NELA Joint Committee o?
610
Chapter 18 Insulation Coordination 611

lation Coordination was formed to consider laboratory TABLE 1 -BASIC IMPULSE INSULATION LEVELS
testing technique and data, to determine the insulation -
levels in common use, to establish the insulation strength Column
_-
Column 2 Column 3
of all classes of equipment, and to establish insulation Reference Standard Basic Reduced
levels for various voltage classifications. After ten years Class Impulse Level Insulation Levels
Pf study and collection of data this schedule was fairly well Kv KV In Use-Kv
completed. Numerous articles in trade magazines show .-
1.2 30* 45t
the results. In a report dated January 1941’, the com-
2.5 45* W
mittee, now known as the Joint AIEE-EEI-NEMR Com-
5.0 - 60* w
mittee on Insulation Coordination, rounded out the pro- 8.7 75* SW ...
gram by specifying basic impulse insulation levels for the
different voltage classifications. 15 95* 11ot
Test specifications for apparatus are prepared on the 23 150
basis of demonstrating that the insulation strength of the 34.5 200
equipment will be equal to or greater than the selected 46 250
basic level and the protective equipment for the station 69 350
should be chosen to give the insulation meeting these
92 450
levels as good protection as economically justified.
115 550 450
II. BASIC INSULATION LEVELS 138 650 550 ,.
161 750 650
Several methods of providing coordination between in-
sulation levels in the station and on the line leading into 196 900
the station 2,3have been offered. The best method is to 230 - 1050 900
establish a definite common level for all the insulation in 287 1300
the station and bring all insulation to or above this level. 345 - 1550
This limits the problem to three fundamental requirements, *For distribution class equipment.
Gamely, the selection of a suitable insulation level, the tFor power class equipment.
Gsurance that-the breakdown or flashover strength of all
insulation~~ini~‘thestation will equal or exceed the selected demonstration of acceptability of equipment. Finally,
level, and-the application of protective devices that will in January, 19411, the Joint AIEE-EEI-NEMA Com-
give the apparatus as good protection as can be justified mittee adopted basic insulation levels (Table 1) in terms
economically. of iithstand voltages according to the following definition:
Data collected from utility systems during the early
work on insulation coordination provided existing insula- “Basic impulse insulation levels are reference levels expressed
tion levels. The data collected (60-cycle wet flashover in impulse crest voltage with a standard wave not longer than
1%X40 microsecond wave. Apparatus insulation as demon-
characteristics measured in terms of equivalent gap spac-
strated by suitable tests shall be equal to or greater than the
ing) fell within well defined limits. The upper limit cor- basic insulation level.”
responded to about ten times E, at the upper end of the
curve and to about six times E, at the lower end of the This requires that apparatus conforming to these levels
curve, E, being the system voltage-to-neutral. The lower shall have a withstand test value not less than the kv
limit lay on a curve about four times E, for systems 46 kv magnitude given in the second column of Table 1. It was
and below and about three times E, for systems 69 kv and also understood that apparatus conforming to these re-
above. These data together with impulse. characteristics quirements should be capable of withstanding the specified
of insulation obtained in the field and laboratory provided a voltage whether the impulse is positive or negative in
basis for establishing insulation levels. Impulse test lev- polarity. Atmospheric conditions at time of test should
els, in terms of inches of gap, were therefore, selected that be taken into consideration.
represented a medium between the upper and lower limits The values in Table 1, column 2 were selected initially
defined above and that fell within the scope of available as the standard basic impulse insulation levels (BILs) to
Protective devices. As laboratory technique improved so be applied regardless of how the system was grounded.
that different laboratories were in close agreement on test Systems ungrounded or grounded so as to allow full dis-
results, the test levels were expressed in kilovolts corre- placement of the neutral during line-to-ground faults re-
sponding to the test gaps, based on a 1%X40 microsecond quire lightning arresters based on the full line-to-line volt-
Positive wave, which is illustrated in Fig. 5(a). The basic age of the system. If the system is grounded solidly or so
levels were expressed on a 50-50 flashover basis, that is, as to _limit
..-_.. . .. the _lineTt~;~ge.during ground faults
values in kv crest corresponding to gap spacings giving (X,/X,s3)-the so called 80-percent arrester can and has
59 percent flashover and 50 percent full wave when sub- been used. Thus in some of the---.voltage - _-_. classes
.“” of 115 kv
lected to 1%X40 positive impulse. Recognizing that it and”zbze a number
I .___-,of%y?tems
.. ..- have used, with solid
l&s not practical to subject most types of apparatus to groundi<~,%$pment having’msulation with BILs one
a series of flashover tests to demonstrate their insulation class Idtier~$&&yn in~Table&column 3.
levels, a minus tolerance of five percent was allowed in ‘-&yofn solidly-grounded systems where the ratio X0/X1
the definition of basic levels to permit a practical test is equal to about one or less, the one class lower BIL has

,’
612 Insulation Coordination ’ Chapter 18.

been used with 75 percent arresters with satisfactory expe-


rience. As a result of this experience, better overall under-
standing of the problem, and the economy of reducing
BIT, in the higher voltage classes, particularly on trans-
formers, the *Joint AIEE-EET-KEhId Committee on In-
sulation Coordination is studying the possibility of re-
ducing the BIL figures (for X,/X, 5 1.0) to loner values
than those shown in Table 1, column 3. Another reason
for giving serious considcrntion to reducing the BIL for
solidly-grounded systems is that there are many old trnns-
formers in service with insulation levels below that given
in Table 1, column 3 which have given twenty or more
years of service without failure. Thus, since the first group ‘0 I 2 3 4 5 6 7 6 9 IO
of BILs was adopted in 1941, the manner in which the TIME-MICROSECONDS
system is grounded has been brought into the picture with
the result that lower BIL equipment can be protected, Fig. 2-Coordination of transformer insulation with arrester
characteristic.
t,hereby enabling systems to be built to do the same job
at less cost. Curve A-10%kv station-type SV arrester-maximum voltaKo
for 5000-ampere 10 x 20 current wave.
1. Selection of Basic Impulse Insulation Level Curve B-Transformer insulation withstand characteristic.
The basic impulse insulation level should be selected
which can be protected with a suitable lightning protective lation gives 495 kv. Since this value is under the standard
device. The best protection is provided by modern type of 550 kv, this value can be applied as shown on Curve 13
lightning arresters.. The spread or margin between the of Fig. 2. Based on the recommended application voluo~
RIL and the protective device, allowing for manufacturing for voltage drop across the 109-kv arrester for a 5000.
tolerances, is an economic consideration that must balance ampere surge 388 kv instead of 400 kv can be used, which
the chances of insulation failure against the cost of greater gives additional margin of protection in 95 percent of
insulation strength. When using lightning arresters the the cases.
economic factor may be one of greater risk to the arrester Direct lightning strokes in general have a high rata of
than to the equipment insulation. The arrester can be voltage rise (1000 to 10 000 kv per microsecond) and high
applied so that it will protect the insulation but may under current values (5000 to 200 000 amperes). Such strokes
certain extreme conditions, usually unlikely, be subjected may occur at any point on exposed structures whether
to sustained rms overvoltages against which it cannot re- they are lines or stations. The severity of the surges on
cover. Practice has been to apply arresters so that they station insulation and protective devices largely depend3
have an rms voltage rating of at least five percent above on whether or not adequate shield wires are placed abovo
the maximum possible rms line-to-neutral voltage under the structures to intercept the lightning and conduct it to
any normal or expected fault condition. The BIL of the ground. Without overhead ground wires at stations, direct
equipment insulation must therefore be higher than the strokes may damage protective devices, thus leaving equip-
maximum expected surge voltage across the selected ment insulation without adequate protection.. Surges that
arrester. originate as direct strokes on the line and propagate into
To illustrate one method for selecting the BIL of a trans- a station are by far the most common! but are generally
former to be operated on a 13%kv system, assume the easily by-passed to ground by the lightning-protective de
transformer is of large capacity and wye connected on the vice. Overhead ground wires above open-wire circuits rc-
13%kv side. The transformer is solidly grounded and the duce the number of strokes that reach the phase conduc-
impedance ratios at the transformer terminals are such tors as discussed in Chapter 17.
that X0/X1 = 2.0; Ro/Xl = 1.0, RI/XI = 0.1, R, = Rz and The nature of lightning strokes and the propagation of
Xl =X2. For these conditions the maximum voltage to surges are explained in detail in Chaps. 15 and 16. The
ground at the transformer terminals during any type of characteristics of traveling surges at the station depend
system fault for any fault resistance is 74 percent of nor- upon the nature of the direct stroke as it originates on
mal phase-to-phase voltage as obtained from Fig. 29 (b). the phase conductors, the distance between origin and
Allowing five percent for system overvoltage, the arrester station, the insulation and electrical characteristics of the
rms voltage rating should be (1.05)(74) or 77.7 percent line, and the capacitance of the equipment in the stations
which is (77.7)(138) or 107.2 kv. Thus an arrester of The surge is attenuated as it travels by corona loss fnd
109 kv, which is the closest standard rating, would be re- skin effect, and is distorted by reflection at the statIon*
quired. Curve A in Fig. 2 is the characteristic of a 109-kv The capacitance of the station equipment charged through
station valve-type arrester for an assumed 10x20 micro- the inductance of the line from the point where the sur@
second wave of 5000 amperes and a plus tolerance of 15 originates to the station has the effect of sloping off the
percent on the average impulse sparkover and a plus tol- front of the surge wave.
erance of 10 percent above the average drop across the The magnitude of the surge voltage that can be im-
arrester. Assuming a 15 percent margin plus 35 kv between pressed on electrical equipment is not determined by the
the 400 kv and the required BIL nf the transformer insu- system operating voltage so there is some argument agaiId :, ;
:.1.‘r
chapter 18 Insulation Coordination 613

associating impulse levels directly with operating voltages. the Norinder device, the wave shape is recorded on the
However, low-voltage lines are not as highly insulated as film in its entirety.
higher voltage lines so t>hat lightning surges coming into A typical diagram of impulse-testing equipment is shown
t,hc st,at,ion would normally be much less than in a higher in Fig. 3. The capacitors, usually rated 100 kv each,
voltnge station because the high-voltage surges will flash making up the surge generator are charged in parallel
over the line insulation and not reach the station. Also, through resistors. When the charge on each condenser
the lower operating voltage permits the use of protective reaches the predetermined breakdown voltage of the sphere
Clcviceswith lower discharge characteristics. The insula- gaps separating the condensers, the sphere gaps flash over
tion necessary for high operating voltages inherently thereby connecting all the condensers in series. One ter-
provides high impulse strength. The-impulse levels shown minal of the capacitor bank is normally grounded. The
in Table 1, therefore, can be obt@ned-with ihe cdrrespond- other terminal must be insulated from ground to with-
$g oe&&ing voltage class without ex&e&$ reasonable stand the full magnitude of the discharge voltage. A volt-
design proportions.
_ __- _- -- age impulse of either positive or negative polarity can be
obtained by connecting the charging circuit to give the
III. SURGE TESTING desired polarity. The potential divider shown supplies a
The determination of t,he impulse strength of the various reduced voltage to the oscillograph proportional to the
insulations is generally done by an adaptation of the surge test voltage.
generator devised by Dr. Emil Marx in Germany. It con- The shape of the impulse wave applied to the test speci-
sists essentially of a group of condensers, spark gaps, and men is determined by the constants (resistance, induct-
resistors SO connected that the condensers are charged in ance, and capacitance) of the discharge circuit, some of
parallel from a relatively low-voltage source and dis- which are inherent in the capacitors and leads and some
charged in series to give a high voltage across the test of which are added externally. A typical laboratory in-
piece. stallation of impulse-testing equipment is shown in Fig. 4.
The only oscillograph available until quite recently for
measuring waves of as short duration as lightning surges 2. Wave Shape
was the cathode-ray oscillograph devised by Dufour. This It became evident in the early stages of surge testing
oscillograph was improved by Norinder through the addi- that it would be necessary to standardize on test wave
tion of a simple cathode-ray beam control, and today this forms in order to establish insulation levels on a common
oscillograph is widely used in this country and others. In basis. The accepted designation of defining the impulse

Surge Generalor ) To Test


\ r nnmninn / Specimen
&Yectrosfatic Potential
Divider

I9

60Kv. Rectifier,
II
Emission AiL_bq III
1
I

Surqe Zero line jfi,m


Push B&tons
Main Control CalhodeRay
Paneland Oscilloqraph
/nduction
Regula/on
Fig. 3-Typical diagram of impulse testing equipment.
-L
614 Insulation Coordination \ Chapter 18 i

However, the lix40 microsecond wave, either positive


or negative, has now been accepted as standard because
it simulates the more severe full wave lightning surges and
because it can be obtained readily with the surge genera,
tor. The effect of lightning surges of shorter duration can
be simulated with this wave by chopping at short times.
3. Volt-Time Curve
The breakdown voltage of insulation or the flashover
voltage of a gap, particularly the latter, will vary with
the length of time voltage is applied. The so-called volb
time curve is a graph of crest flashover voltages plotted
against time to flashover for a series of impulse applies
tions of a given wave shape. The construction of the
volt-time curve and the terminology associated with im.
pulse testing are shown in Fig. 5 (b)4. The critical or
minimum flashover voltage is the crest voltage of the wave
that will just cause flashover on the tail of the wave, that
is, it will cause flashover for 50 percent of the applications,
and for the other 50 percent of the applications there will
be a full wave (no flashover).
The figure also shows the relation of the critical with-
stand voltage. To obtain the magnitude of the voltage,
the applied voltage is reduced to just below the disruptive
Fig. I-Typical impulse laboratory. Sharon Works of West- discharge of the test specimen. The rated withstand volt-
inghouse Electric Corporation.
age is the crest value of the impulse wave that the appa-
wave shape is to give the time in microseconds for the ratus will stand without disruptive discharge.
impulse to reach crest followed by the time in microseconds
for the wave to reach half magnitude. Fig. 5 (a)“. 4. Effect of Atmospheric Conditions
For practical reasons a virtual zero time point is estab- The flashover characteristics of insulation in air varies
lished at Or and. determined by a line drawn through the with atmospheric conditions. In general, flashover volt-
0.3E and 0.9E points in -t&wave front. For example, ages vary inversely with temperature, directly with baro-
a 1$X40 microsecond wave would have an Oltl value-of metric pressure, and directly with absolute humidity. Test
1; microseconds and an Or24value of 40 microseconds. In data obtained under various actual weather conditions arc
transformer. testing where the time to crest is not easily usually corrected to the American standard conditions
determined, it is taken as two times the interval between which are:
the 0.3E and 0.9E points on the wave front, that is 2x223. Temperature, 77°F.
The 1 X 5 and 1 x 10 microsecond waves, and other wave Barometric pressure, 29.92 inches of mercury
shapes, have been used occasionally in testing insulation. Humidity, 0.6085 inches of mercury

CRITICAL WITHSTANC

RATED WITHSTAND

. SI..L ..“..“L , ,,.,& ..-.---


/i IX3Ix,-
I”-
:X,
.
- 4WAVE FRONT/--TIME
FLASHOVER
RANGE WAVE TAIL FLASHOVER --+--NO IMPULSE-
FLASHOVER ”
01
TIME IN MICROSECONDS

(0) (b)
Fig. 5-Wave shape. 4’.

(a) An impulse testing wave illustrating methods of designating significant characteristics of the wave. (b) Series of impulse wavea
illustrating the terminology and definitions associated with impulse voltage testing.
chapter 18 Insulation Coordination 615

,a

,,I
NWYIP” ‘M&RED ‘K,Lo&LTS
BY THE CORRECTION P&CTOR
OR boo PERCENT CORRECTION
TO NEAS”RE0 YILO”OL*S.
(0)
ING-INCHES
tbl
0

BELOW 1.1 I(“, CREST oEcRE,%$E Fig. 7-Impulse flashover characteristics of standard rod gaps.
PERCENT CORRECTION IN MREcT
24 PR0P0RTloN TO vcu*GE. BELOW Long spacings for 11/s x 40 wave at 77”F., 30-inch barometric
TO FLASHOVER FOR “oLTlGE.3 AB and 0.6085-inch vapor pressure.
,J2 THE GRITICAL FLASHOVER GRADE
PERCENT CORRECTlON OlREtTLY WIT”
(a) Positive waves.
(b) Negative waves.

The AIEE-EEI-NEMA Subcommittee on Correlation


of Laboratory Data have published a paper giving a sum-
Fig. &Humidity correction factors for flashover voltages of mary of recommended standard definitions and methods
gaps, insulators and bushings, based on data from several applying to high-voltage testing4. These recommendations
laboratories. are now generally followed by the industry.
Temperature and barometric pressure are usually com- 5. Flashover Characteristics of Rod Gaps and In-
bined into a single factor known as relative air density sulators
according to the following relation which is unity for
Because of laboratory differences in test results on ap-
standard atmospheric conditions:
paratus insulation in the early days of impulse testing, the
17.95 X Bar. Pressure (inches) rod gap was selected as a yard stick of insulation strength.
Relative Air Density =
4GO+Temp. “F. Because different types of gaps gave different results, a
The chart shown in Fig. G4 has been accepted, based
on an accumulation of test data, as giving correction fac-
tors for humidity conditions. The measured test voltage
is then corrected by dividing by the relative air density
tlcfined above and multiplying by the humidity factor
obtained from these curves.
TABLE Z-TENTATIVE AIEE STANDARD0N INSULATION TESTS
FoRINDOORAIR SWITCHES,INSULATORUNITS AND Bus SUPPORTS
Withstand Voltage - Kv
-
Low Freq. Impulse
Vol tagc
1 Min. 1.5X40 Full Wave
Rating
Dry U’os. or Neg. Dry)
- _-
2.5 15 45
50 19 60
7.5 26 75
15 L’ 36 95 SPACING-INCHES SPACING-INCHES
Id lb1
15 H 50 110 Fig. S-Impulse flashover characteristics of standard rod gaps.
23 60 150 Short spacings for 11/z x 40 wave at 77”F., 30-inch barometric
34 5 80 200 and 0.6085-inch vapor pressure.
*The 15 L rating is intended to match other apparatue
on which the 36-95 test (a) Positive waves,
‘ewl is specified. (b) Negative waves.
616 Insulation Coordination Chapter 18 ’

TABLES-TENTATIVEAIEESTANDARDONINSULATIONTESTSFOR 2000
OUTDOOR AIR SWITCHES, INSULATOR UNITS AND Bus SUPPORTS 1600
Withstand Voltage-Kv 1600
-
; 1400
Voltage Low Freq. Low Freq. Impulse
Rating 1 Min. 10 Sec. .,5X40 Full Wave
Kv (Dry) (Wet) (Pas. or Neg.)
.-
7 .5 36 30 95
15 50 45 110
23 70 60 150
34 5 95 80 200
46 120 100 250
69 175 145 350 SPACING-INCHES
92 225 190 450 Fig. IO-Sixty-cycle and critical impulse flashover voltages of
115 280 230 550 standard rod gaps, averaged by the AIEE, EEI, NEMA Sub.
138 335 275 650 committee from results of tests from several laboratories.
161 385 315 750
196 465 385 900
230 545 445 1050
287 680 555 1300
345 810 665 1550
-

standard gap was established. The following defines the


standard rod gap5.
“The rod gap shall consist of two, 0.5 inch square-cornered
square-cut rods spaced co-axially and overhanging their sup-
ports at least one-half the gap spacing. The rods shall be
mounted on standard apparatus insulators giving a height of
gap above the ground plane of 1.3 times the gap spacing plus
four inches, with a tolerance of + 10 percent.”
Laboratory technique is now developed to the point that
apparatus insulation levels can be expressed in terms of
voltage. However, the rod gap is still sometimes used
j / j j j j i ]
I I III l II I I
3o02 6 IO 14 16 25 6 IO 14 I8
UNITS UNITS
(0) (b)
Fig. 11-Impulse flashover characteristics of suspension inau-
lators for 11/2 x 40 waves at 77°F.. 30-inch barometric and
0.6085-inch vapor pressure. Relative air density= 1.0.
(a) Positive waves.
(b) Negative waves.

I I I I I I I

0 4 8 I2 16
MICROSECONDS
(0) (b)

Fig. 9-Impulse flashover characteristics of 40-inch standard


and vertical rod gaps, wet and dry, for 11/z x 40 waves, water
0.2 in. per min., 1350 ohms per cubic inch.
(a) Positive waves.
(b) Negative waves. UNITS
A-Average curve for standard rod gaps. Fig. 12-Sixty-cycle flashover of suspension insulators show’
B-Test curve for 40-inch standard gap. in Fig. 11.
C--Standard gap, wet test. Dry: relative air density= 1.0. humidity =0.6085.
D-Vertical gap. Wet: precipitation=0.2 in. per min.
E-Vertical gap, wet test. resistanceof water = 7000 ohms ner cubic inch.
Chapter 18 Insulation Coordination 617

‘& NiGAtlVq
,020o
s \\
. POSITIVE .-

loo0 I 234567%4567% 0 I 2 3 4 5 6 7 8 9 IO II2


MICROSECONDS TO FLASHOVER MICROSECONDS TO FLASHOVER MICROSECONDS TO FLASHOVER
(a) (bl
600,11. 1100, , ( , , , / , --

0 NFGATIVF

-- -1 POSITIVE 1
1
345670 2345670 TO FLASHOVER
MdOSECONDS 2 3 4 5 6 7 8 9I IO III 12
MICROSECONDS TO FLASHOVER MICROSECONDS TO FLASHOVER
Cdl (e) If)
Fig. 13-Impulse flashover character -istics of particular types of apparatus insulators on positive and negative II/z x 40 wav ‘es
at standard air conditions.
(3) 7.5 kv class. (c) 23 kv class. (e) 46 kv class.
(b) 15 kv class. (d) 34.5 kv class. (f) 69 kv class.

so that information on its flashover characteristics is pension insulators of various lengths is given in Fig. 18.
useful. The data for 10 to 18 insulators were obtained by labora-
Suspension and apparatus insulators play an important tory tests by Sorensenz5v26.
part in the coordination of station equipment, not only in Table 2 gives data from a Tentative AIEE standard
establishing the insulation level but also in determining on the BO-cycle and impulse withstand characteristic for
the magnitude of surges entering the station. Suspension indoor air switches, insulator units and bus supports.
insulators are generally made up of at least three ten- Table 3 gives similar data for corresponding outdoor in-
inch units in a string, spaced 5: inches apart. Apparatus sulation.
insulators can be either the pedestal type or the so-called
post type.
11 complete resume of impulse and GO-cycle flashover
characteristics of rod gaps and insulators was published
hy P. IT. McAuleys. For convenience some of these data
:W reproduced in Figs. 7 to 17. Figure 9 is of particular
interest in that it shows the effect of mounting and at-
mospheric conditions on the flashover characteristics of
rod gaps.
The voltage distribution across strings of standard sus-

& 800
2
"700
I
E 600
i
5 500
Y UNITS UNITS
(0) (b)
400
0 2 4 6 8 IO I2 14 16 IS 20 22 Fig. 15-Impulse flashover characteristics of two to seven
MICROSECONDS TO FLASHOVER units, apparatus insulators, for 1r/2 x’ 40 waves at standard
b. 14--Impulse flashover characteristics for 88 kv class air conditions.
3-unit column for positive and negative 1*/z x 40 waves a; (a) Positive waves.
standard air conditions. (b) Negative waves.
Insulation Coordination Chapter 18
\
900-i - ,

160; ’ ’ ’ ’ ’ ’ ’ ’ ’ ’
2 4 6 0 IO
MICROSECONDS TO ‘FLASHOVER MICROSECONDS TO FLASHOVER MICROSECONDS TO FLASHOVER
(a) (b)

‘2
=zzu j ‘i 1 7
Y

!II
\,\
z=: PO.SITI,VE --

l6O(j 2 4 6 0 IO
MICROSECONDS TO FLASHOVER MICROSECONDS TO FLASiiOVER - MICROSECONDS TO FLASHOVI ER
(d) (a)
320
\

b
i 400
I I
k NEGATIVF , ,
1 POSITIVE
200- / I
0 2 4 6 0 IO 12 14 I6 I6 3oo0 2 4 6 0 IO 12 14
MICROSECONDS TO FLASHOVER MltROSECbNDS Tt FLAS;OVER ‘” MICROSECONDS TO FLASHOVE
(cl) (h) (i)

Fig. 16-Impulse flashover characteristics of particular sizes of pin type insulators for positive and negative 11/2x 40 waves at
standard air conditions.

Since the voltage-time curves for various types of insu- of the insulators shown do not meet the required irnpd~6
lators are not available from the standards, the curves in withstand voltage.
Figs. 13, 14, 15, 16, and 17 are given even though some
6. Impulse Characteristics of Transformer Insu-
lation
+ 000 Because a power transformer is usually the most expen-
El
az sive equipment in a station and because its failure may
* mean a lengthy and costly outage, it is investigated most
’ 600
;2 critically from an insulation standpoint.
2 The impulse level of a transformer can be determined
g2 400 by t.he breakdown voltage of the major internal insulation
Y (insulation to ground), the breakdown voltage of the minor
insulation (insulation between turns and windings), ad
2oo0 2 4 6 0 IO I2 14 16 the flashover voltage of the bushings, or a combination
MICROSECONDSTO FLASHOVER of these. The impulse characteristic of the internal i
Fig. 17-Impulse flashover characteristics of line-post insula- lation in a transformer differs from flashover in air in
tors for positive and negative 11/z x 40 waves at standard air main respects. First of all, the impulse ratio (the r
conditions. of minimum breakdown on impulse to breakdown on
Chapter 18 Insulation Coordination 619

PERCENT WINDING

Fig. 20-Effect of wave front on initial voltage distribution in


some types of transformer windings.
Fig. 18-Power-frequency voltage across each unit in an insu-
lator string starting with insulator No. 1 on the grounded end
of the string. Insulator No. 5 in a string of 10 has 7 percent that the minor insulation meets all the requirements of
of the total string voltage. (Without grading rings except applied impulse tests. To demonstrate this, modern trans-
where noted.)
formers usually must be capable of passing a chopped wave
test of a higher voltage crest than the full wave test. This
cycle peak) is higher, being from 2.1 to 2.2 for trans- chopped wave is produced by flashover of a gap or bushing
former insulation, whereas, it is 1.5 or less for rod gaps, in parallel with the transformer insulation. The standard
insulators, bushings, etc. Secondly, the impulse break- impulse tests for transformers, regulators, and reactors for
down of transformer insulation does not vary as much the different voltage classifications as standardized by the
with time as seen from a typical volt-time curve, shown American Standards Association C 57 are as follows:
in Fig. 19’. After three microseconds the breakdown volt- Standard impulse tests consist of two applications
age is substantially constant. of a chopped wave followed by one application of a
The insulation stress between turns or between coils full wave. Either positive or negative waves may be
in a transformer is dependent largely upon the steepness used.
of the surge wave front. It may be further aggravated by (a) Chopped-Wave Test
oscillations within the transformer or by a “piling up” of (1) For this test, the applied voltage wave shall
the surge voltage in a small portion of the winding. (See have a crest voltage and time to flashover in
Fig. 207.) Modern transformers are designed, however, so accordance with Table 4.
(2) The chopped wave shall be obtained by flash-
over of a suitable air gap.

160

90 0 I I I I i MICROSECONDS
I 2 3 4 5 t
Fig. 21-Typical volt-time curve of transformer winding and
bushing (heavy solid line represents the overall volt-time
F’lg. 19-Volt-time curve of typical major insulation in trans- curve of transformer, to be used when protecting against
formers. lightning surges).
DLV 1 nsauataon ~ooraana~aon cnapter 18

TABLE ~-STANDARD IMPULSE TESTS FOR TRANSFORMERS, REGU-


LATORS, AND REACTORS
TABLE ~-STANDARD WITHSTAND TEST VOLT)
BUSHINGS t”’SS?JORAPPARATUS
-

Cbil-Type Transformers
Impulse

500
Tests

cN-Type Transformers over


r Low Frequency Test
RMS Kv (2)
Impulse Test
1 5X40 Micro-
S;ccond Full Wave
Crest Kv (2, 4)
Kva or Less-Oil-Type In- 500 Kva - Oil-Type Reg- - -
strument Transformers- ulating Transformers -
Outdoor Bushings
Oil-Type Constant-Cur- Oil-Type Current Limit- Insula- -
rent Transformers-Step ing Reactors-Step and tion In- Outdoor
and Induction Voltage Induction Voltage Regu- Classifi- Large Small loor Bushings
Regulators 250 Kva or lators Over 250 Kva Sin- cation Apparatus Apparatus In-
Insula (7)
Less Single-Phase and 750 glc-Phase and Over 750 (1) (5) (6) loor
tion 3ush.
Class- - Kva or Less Three-Phase Kva Three-Phase KV ings - (7)
- -7-
bh-
Kv Mir ‘L arge ‘mall
Full Full ‘(3)
In68
Chopped Wave Chopped Wave Mir OSec 1Mir OSec
(5) (6)
Wave Wave Dry
- - Dry Wet Dry Wet AP- AP-
Ejara- Jara-
Min Min tus tus
Time Time
Kv ;o Flash- Kv Kv 1to Flash- Kv 1.2 10 6 30
Crest over in Crest Crest over in Crest 2.5 21 Zb 15 13 zi 60 45 45
Micro- Micro- .5 0 27 24 21 20 24 75 60 60
seconds seconds 8.7 35 30 27 24 30 95 75 75
-- 15 50 45 35 30 50(8 ) 110 95 10(B)
1.2 36 10 30 54 15 45
25 54 1.25 45 69 1.5 60 23 70 60 70 60 60 150 150 150
50 69 15 60 88 1.6 75 34 5 95 80 95 80 80 200 200 200
8.6( s 88 1.6 75 110 1.8 95 46 120 100 120 100 250 250
15 110 1.8 95 130 2.0 110 69 175 145 175 145 350 350

25.0 175 3.0 150 175 3.0 150 92 225 190 225 190 450 450
34.5 230 3.0 200 230 30 200 115 280 230 280 230 550 550 .
46.0 290 3.0 250 290 3.0 250 138 335 275 335 275 650 650 ...
69.0 400 30 350 400 3.0 350 161 385 315 385 315 750 750 .

92 520 3.0 450 520 3.0 450 196 465 385 465 385 900 900 .
115 630 3.0 550 630 3.0 550 230 545 445 545 445 11050 1050 ...
138 750 30 650 750 3.0 650

-I
287.5 680 555 680 555 I1300 1300
161 865 3.0 750 865 3.0 750 345 810 665 810 665 1550 1550
.
- -
196 1035 30 900 1035 3.0 900 (1) Bushings of B given insulation classificationare in general recommendedfor np-
230 1210 30 1050 1210 3.0 1050 paratus having 8 rating up to and including the insolation classificationof tho
bushing and maybe used for apparatus of a higher voltage rating when nd6-
287 1500 30 1300 1500 3.0 1300 quate for the particular application.
(2) All values are withstand test values without negative tolerance.
345 1785 30 1550 1785 3.0 1550 (3) Wet teat values are not assignedto indoor bushings.
- A (4)
(5)
Either positive or negativewives may be used--whichever givesthe lower vnll10.
Bushings for use in large appuatus are those intended for use in trnnsformura
rated above 500 kva, outdoor circuit breakers, and other apparatus of CO~TO-
spending importance.
(6) Bushings for use in small apparatus are those intended for usein transformor
rated 500 kva and less and other apparntus of correspondingimportance.
(b) Full-Wave Test (7) Bushings for use in indoor apparatus BR those intended for use in indoor tYp”
circuit breakers, instrument transformers. and other indoor apparatus excol’t
For this test, the applied voltage wave shall dry-type instrument transformers. sir-cooled transformers. air-cooled ro~ok~.
have a crest value in accordance with Table 4. tom, and bushings used primarily for mechanicnl protection of insulated cablo
(c) Excitation During Impulse (8) %%ngs for small indoor apparatus msy be supplied to withstand D low fr*
quency test of 38 kv and an impulse test of 05 kv.
During the impulse test if the transformer is
excited at normal voltage and frequency, the
impulse shall be timed within 30 electrical de- The volt-time characteristics of the bushings on a trans-
grees of the crest of the normal frequency volt- former differ from the volt-time characteristics of the
age of opposite polarity. transformer internal insulation. In general, the bushing
The test values for the different voltage classifications are will have a higher flashover at short time lags than the
shown in Table 4. transformer internal insulation. At long time lags its flash-
Since the bushing represents a vital portion of the trans- over may be slightly more or slightly less than the winding
former insulation, its impulse flashover must be carefully breakdown. The impulse strength of the winding is esse*-
considered in establishing the transformer insulation lev- tially the same for positive or negative waves; whereas
els. The standard withstand voltage tests for apparatus the bushing critical flashover may be higher for one ~010
bushings as given in ASA C 76 Standard 1943 are listed ity than for the other. The manufacturer takes the overall
in Table 5. impulse characteristics of a transformer into account when
Chnpter 1s Insulation Coordinatzon 621

rod gap, the protector tube, and the conventional valve-


type lightning arrester.
Rod Gap-Although the rod gap has the advantage of
being extremely simple and rugged, it has two important
disadvantages from a protective standpoint. First, it does
not fulfill one of the requirements of a trlle protective
device in that it will not valve off power voltage after it.
has once been flashed over by a surge. The circuit must
be deenergized to clear the flashover arc each time the
gap operates. Second, its breakdown voltage rises more
at short time lags than most insulation, which means that
a relatively short gap is required to provide protection
against surges having steep wave fronts. It would thus
have a low flashover at long time lags that would result
in numerous flashovers with consequent outages resulting
from minor lightning surges or severe switching surges.
The rod gap is, therefore, generally used only for back-up
protection or on circuits where the outages with short
gaps can be tolerated or compensated for by high-speed
reclosing of the circuit energizing breaker.
Modifications of the rod gap, such as the fused gap and
control gap, have been used occasionally. The fuse gap
is simply a rod gap with a fuse in series with it to inter-
rupt the power follow current caused by the flashover.
Fig. 22-Power transformer undergoing impulse test. Surge
generator is in building in background.
It: therefore, has the same surge protective characteristic

9001 \, , /
+ing its withstand voltage characteristic. A transformer
0
I i I I I I
widergoing an impulse test is illustrated in Fig. 22.
7. Impulse Characteristics of Other Station Appa-
ratus
In addition to power transformers, the outdoor station RATED
generally has instrument transformers, circuit breakers, VOLTAGE
700 \ - 138 KV
tlisconnect switches, and bus insulators exposed to light- I
ning surges. Some stations will also include reactors and
\ \ i I /
regulating equipment. All of this equipment nom meets
the basic impulse insulation levels listed in Table 1.
The standard withstand impulse tests for instrument
transformers, regulators, and reactors are shown in Table
-1, referred to above for transformers. The withstand
impulse tests for outdoor circuit breakers, disconnect
switches, and bus insulst,ors are the same as those listed
in Table 5 for outdoor bushings. a 69 iV

IV. CHARACTERISTICS OF PROTECTIVE ) 1


DEVICES 300. \, /
46 KV
The purpose of a protective device is to limit the surge
voltage that may be applied to the apparatus it protects \I j
wl by-pass the surge to ground. It must withstand con- 200+++ I 34.5 KV-

tinuously the rated power voltage for which it is designed. I \I i I I -_.!..


Z3 KV
The ratio of the maximum surge voltage it will permit on I I I I I I I I 1

discharge to the maximum crest power voltage it will


withstand following discharge, called the protective ratio,
is, therefore, a measure of its protective ability. Of great,
IiWortance also is its ability to discharge severe surge
currents, either of high magnitude or long duration, with-
‘O:: 0 2 4 6 9 IO
MICROSECONDS
12 14 16 16

Out injury.
J There are three general types of lightning-protective Fig. 23-Impulse characteristics
_ _
of transmission
_ . _. .
type pro-
ueVl~cs, each having its field of application; namely, the tector tubes for grounded-neutral circuits.
622 Insulation Coordination

TABLE ~--INDUSTRY PERFORMANCE CHARACTERISTICS OF


DISTRIBUTION EXPULSION-TYPE LIGHTNING ARRESTERS
-
Front of Wave
Impulse Sparkover Average Critical
Rated
mpulse Sparkovcr
Voltage 01
1 5X40 Microsec.
Arrester Rate of Rise* Kv**
-- 7Vave
KV Kv per
hlicrosrc. NV**
i\Iin Avg ibras

23 33 45 29
32 50 70 41
48 71 97 53
63 8-I 94 61
77 / 101 I 114 ml

as the plain rod gap and, although it prevents a circuit


outage upon flashover, it requires the replacement and
maintenance of fuses. Also, to be effective it requires
proper coordination between the fuse blowing time and
adjacent relay timing.
The control gap”, consisting of a double gap arrange-
ment to approach a sphere gap characteristic, has a some-
what better volt-time characteristic than the rod gap. It
can be used with or jvithout fuses, and although it is ap-
plicable for back-up or secondary protection, it is usually
considered in the same class as the rod gaps, as far as
major protection is concerned.
Protector Tube-The transmission type protectortube
has a volt-time characteristic, Fig. 23, somewhat better
than the rod gap and has the ability to interrupt power
voltage after flashover. It is, therefore, used extensively
to prevent flashover of transmission line insulators, dis-
CONNECTOR FOR
(bl
/LINE CONDUCTOR

WATER-TIGHT JOINT,
.COVER

-SERIES GAPS
WET PROCESS+ 1 MAKING UP
PORCELAIN HOUSING GAP ELEMENl

SOLDER-SEALED-----~
(METAL TO PORCELAIN) ’
WET PROCESS PORCE-
LAIN TUBE

Fig. 25 -Typical oscillograms of current discharge


POROUS BLOCKS-‘---
MAKING UP
lightning arresters.
c
VALVE ELEMENT
(4 Standard 10X20 microsecond current surge aPPl
kv station type arrester.
/’ /FOUNDATION BASE (b) Arrester voltage during discharge of current snr
GROUND TERMINAL in (a).
CONNECTION (IN BACK
NOT VISBLE) I
(cl Current and voltage of 3 kv station type arrester
ing a 5X10 microsecond current surge hating i
Fig. 24--Sectional view of station-type lightning arrester. excess of 100 000 amperes.
Chapter 18 Insulation Coordination 623

TABLE ~-PERFORMANCE CHARACTERISTICS OF VALVE-TYPE LIGHTNING ARRESTERS

Arrester
Front of Wave Impulse Sparkover
T-
Discharge Voltage-Kv
- on 10 x 20 Microsecond
- Current Wave**

Type and
Rated
\‘dtage--Kv
Rate of Rise*
Kv per p sec.
- -
Kv** 5,000 Amperes
- I
_-
10,000 Amperes
4 I 20,000 Amperes
-__
Avg. Max. t Avg. Max. t Avg. Max. t Avg. bras. t
.- .- -- .- __-

J!hlribulion
3 25 18 23 23 14 17 17 16 20 20 18 23 23
6 50 34 45 45 26 34 34 30 38 38 34 44 44
9 75 48 62 62 30 51 51 44 57 57 51 66 66
12 100 61 77 77 49 62 62 55 69 69 62 78 78
15 125 73 91 91 61 77 77 69 87 87 79 99 99

Line
20 167 75 90 85 83 96 91 02 106 102 101 116 111
25 208 '33 111 105 101 116 111 111 128 122 121 139 133
30 250 110 132 125 121 139 133 135 155 149 149 172 164
37 308 136 163 154 149 172 164 164 189 181 181 208 199
40 333 147 176 167 161 185 177 177 204 195 196 225 216

50 417 183 220 208 202 232 225 222 255 245 243 280 268
GO 500 220 264 250 242 278 267 271 312 300 298 344 328
73 608 267 320 302 297 342 328 328 378 361 360 41-i 396

Slation
3 25 13 15 15 10 11 11 11 13 12 12 14 13
6 50 23 26 26 20 22 22 22 25 23 24 27 26
9 75 35 3Q 39 30 33 32 33 37 35 35 30 38
12 100 43 50 48 40 44 43 44 48 47 47 52 51
15 125 53 61 59 50 55 54 54 60 58 59 65 63

20 167 72 83 80 67 74 72 72 80 77 78 86 8-4
25 208 89 102 98 83 92 89 90 99 96 100 110 107
30 250 106 122 117 100 110 107 108 119 115 118 130 126
37 308 131 151 144 124 137 133 132 146 141 145 160 155
40 333 136 157 150 134 148 143 144 159 154 153 169 164

50 417 178 205 196 167 184 179 179 197 191 191 211 205
60 500 214 246 236 200 220 214 217 239 231 234 258 250
73 608 261 300 288 245 270 262 262 288 279 283 313 303
'37 808 345 3Q7 380 323 356 345 349 384' 372 377 415 403
109 908 388 446 427 363 400 388 394 434 420 424 4G7 453

121 1008 430 495 474 403 444 430 438 482 467 470 517 502
145 1208 515 592 566 487 536 520 523 575 558 564 622 602
169 1408 602 693 663 566 624 605 610 672 650 658 725 702
196 1633 691 796 760 647 713 691 698 768 744 755 832 803
242 2017 860 988 945 806 887 860 872 960 931 940 1035 100‘4
- - --
“100 kv per micro8ocond per 12 kv of arrester rating. t%% of the arresters manufactured will have characteristics not excewling the
“In~ulse of polarity giving higher sparkover voltage. value in this column. For distribution arresters use the maximum values.

connect switches, and bus insulators. It is also used on 15 kv and below. Industry performance characteristics
transmission-line towers adjacent to a station to reduce of distribution expulsion-type lightning arresters are given
the magnitude of surges coming in on the line and thus in Table 6.
hlieve the duty on the station arresters. The tube is not Valve-Type Arresters-The conventional valve-
at the present time considered adequate protection for type lightning arrester, a typical example of which is shown
h’ansformer insulation, except for distribution type ratings in Fig. 24, provides the highest degree of protection of all
1j kv and below. Its application on circuits above 15 kv protective devices. Its essentially flat,_,.
___, ___ volt-time
.” .. ..-.. d.charac-
‘squires certain limitations in system short-circuit currents teristic makes it ideally suited for the protection of trans-
and recovery voltage rates. fz insulation in the higher voltage classes where the
The protector-tube principle is used extensively for ex- margin between operating voltage and surge strength is
pulsion type arresters in the distribution classifications relatively low. If properly applied, its discharge voltage
.

624 Insulation Coordination

TABLE ~-INSULATION TESTS FOR LIGHTNING ARRESTERS second test wave. In addition, they are given an insula,
(Withstand Test Voltages) tion test in accordance with Table 8, which is from ASA
c 62 Standard dtlteaApril 1944.
kation-type Arresters I- The valve-type lightning arrester is usually made up
All ratings ILine and Distribution- of two elements, a gap element capable of withstanding
Ar- Line and Distrihutio n- type .4rresters rated
power voltage and a valve element capable of suppressing
Tnsu- type Arresters rate<1 below 20 Kv
‘01t- 20 Kv and above
the current following the discharge of the surge. The
lation
Classi- sgo -- breakdown of the gap, which is affected somewhat by
fiCtl- tat- GO-Cycle Impulz ;e fO-CjTlC Impulse the rate of voltage rise, determines the initial discharge
tion ing ‘est Voltage Test T‘est Voltage Test voltage of the arrester. The voltage drop across the valve
Kv Kv 2ms Kv (2) .,5x40 PS 1Xms Kv (2) .3x40 ps element, which depends upon the rate of rise and magni-
(1) - rull We.ve - rull Wave tude of surge current discharged determines the arrester
1 Min 1 Crest Fiv 1 Min I.OSet Crest Kv voltage during discharge.
Dry (2, 3) Dry Wet (2, 3) Typical oscillograms of arrester current discharge tests
60 1.5 13 45 are shown in Fig. 25.
3 21 20
6 27 24 75 21 20 60 The protective ratio of a modern lightning arrester is
9 35 30 95 27 24 75 substantially constant through its range of voltage ratings
15 50 45 110 35 30 95 which means that the gap break-down voltage and the
maximum surge discharge voltage for a given surge con.
23 25 70 60 150 .. dition are approximately proportional to the voltage rating
3-l 5 37 95 80 200 .. of the arrester. The curves of Fig. 26 show how the gap
46 50 120 100 250 .. breakdown varies with rate of voltage rise, and the curves
69 73 175 145 350 .. of Fig. 27 show how the discharge voltage varies with the
92 97 225 190 450 .. magnitude and rate of rise of surge current for typical
230 550 ..
line type and station type arresters. From these curvea,
115 121 280
138 145 335 275 650 .. expressing the gap breakdown and discharge voltage, ench
161 169 385 315 750 in terms of kv per kv of arrester rating, it is possible to
196 196 465 385 900 determine readily the protective characteristics of any
230 242 545 445 1050 rating arrester for an expected surge condition.
- -
(1) Whereapplicationis to he madeof an arresterhavingB lower voltagerating
thnn the ratedvoltageof thecircuitonwhichit is to heusedsuch88ongrounded
neutral circuits. the insulationtest shall be that swcified for the insulation
classonesteplowerthan the rated circuit voltage.
(2) All valuesarewithstandtest voltageswithout negstivetolerance.
(3) Either positiveor negativepolarity WBV~S
lowervalue.
may he used--whichevergivesthe
‘O1-1111111
9

6
remains below the breakdown strength of the transformer P
insulation, even at short time lags. Experience with actual
lightning discharges and laboratory tests have demon- STANDARD A I E E TEST WAVE
strated the ability of the modern lightning arrester to
discharge surges commensurate with direct strokes of
lightning.
Lightning arresters for a-c power circuits are rated ac-
cording to the maximum line-to-ground circuit voltage
they will withstand. There are three classes available;
namely, the station type with voltage ratings ranging from
3 to 242 kv, the line type, for 20 to 73 kv, and distribu- =a
tion type, 3 to 15 kv. The characteristics of these arresters ma
are given in Table 7.
Station-type arresters, as distinguished by their heavier
construction, better protective characteristics, and higher
discharge-current capacity are used for the protection of
substation and power transformers. Line-type arresters
are used for the protection of distribution transformers,
small power transformers, and sometimes small substa- Fig. 26-Average impulse gap breakdown of station- and llfic
tions. Distribution type arresters are intended primarily type arresters. :k
for pole mounting in distribution circuits for the protec-
(a) Represents rate of rise of 5 kv per microsecond per k” f
tion of distribution transformers up to and including the arrester rating.
15.0-kv classification. (b) Represents rate of rise of 10 kv per microsecond
Modern station-type arresters are designed to discharge arrester rating.
not less than 100 000 amperes; line and distribution types (cl Represents rate of rise of 20 kv per microsecond
not less than 65 000 amperes, each with a 5X 10 micro- arrester rating.
Chapter 18 Insulation Coordination 625

1.30

Iw
2:
gd 120
*
w
%
I Y I 2” 1.10
STANDARD AIEEt $4
a Ok
1 1c-1X 70 US TEST WAVE I- ’

ii‘Y 1 1.00
10
=z
2;
x iz 0.90
s?i Y VALUE GIVING MAXIMUM VOLTAGE

I
oJqoo -80 -60 -40 -20 3
x04
Fig. 28-Maximum line-to-ground voltage at fault location
for isolated-neutral systems during fault.
Values shown are maximum values for single line-to-ground fault.
For double line-to-ground fault the voltages are less for ratios of
X,/X, between -m and -2.
Xo=zero-sequence capacitive reactance and
I Xl = positive-sequence subtransient reactance.
::
6 out injury any lightning surge except the most severe
direct strokes originating close to the arrester, it is not
lb00 2000 3000 5000 10000 20000 40000
practical or economical to design them to discharge power
SURGE CURRENT IN AMPERES
current for any appreciable time. A lightning discharge’
(b)
may reach thousands of amperes, but the time is short,
Fig. 27-Average discharge voltage characteristics of typical being measured in microseconds, so that the energy that
lightning arresters. (Numbers on curves represent rate of is absorbed by the arrester is small compared to the energy
rise of current in amperes per microsecond.) that would have to be absorbed with a few amperes power
(a) Line type. (b) Station type. flow for even a few cycles. The first consideration in
applying an arrester should, therefore, be the maximum
line-to-ground dynamic voltage to which the arrester may
For example, suppose it is desired to determine the gap be subjected for any condition of system operation or
breakdown voltage and maximum discharge voltage of a fault.
73 kv, station-type arrester for a surge wave front rising High operating voltage may exist on the far end of long,
st a rate of 500 kv per microsecond, and a discharge cur- high voltage, unloaded transmission lines because of charg-
rent of 2000 amperes with a maximum rate of rise of 2500 ing current flowing through the line reactance. It can
amperes per microsecond. A voltage rise of 500 kv per also be caused by the sudden loss of load on water-wheel
microsecond with a 73 kv arrester, represents a voltage rise generators. It is sometimes possible to rearrange the
500 switching scheme to eliminate or at least minimize t.he
of E = 6.85 kv per microsecond per kv of arrester rating.
possibility of overvoltages from these sources. These fac-
From Fig. 26, the gap breakdown voltage would be tors, however, must be taken into account in the appli-
3.6X73 = 263 kv, at 0.5 microseconds. The maximum dis- cation of lightning arresters.
cllarge voltage from Fig. 27 (b) would be 3.2 X 73 = 234 kv. The maximum rms line-to-ground voltage during a sys-
tem fault can be calculated by the methods of Chap 14,
v. APPLICATION OF PROTECTIVE DEVICES taking into account the constants of the system, the type
of fault, and the fault resistance. The selection of the
8. Selection of Arrester Rating arrester rating should, where possible, be based on such
A valve type lightning arrester begins to dischargetat calculation. Where the fault voltages are not determined
a definite value of overvoltage in accordance with the more accurately by calculation, Fig. 2812 and Fig. 29’*,
curve of Fig. 26, and valves off at a lower voltage, corre- can be used as guides in selecting the arrester rating.
sponding to the maximum permissible voltage rating of The curves of Fig. 28 show the maximum line-to-ground
the arrester. If the power voltage is above the valve-off voltage during fault for isolated-neutral systems as a func-
voltage, t e arrester may continue to discharge power tion of the ratio of zero-sequence capacitive reactance,
current un‘eil it is destroyed. X0, to positive-sequence inductive reactance, X1. In Fig.
Although modern lightning arresters will discharge with- 29, applying to grounded neutral systems, the ratio of
626 Insulation Coordhzation

II I IAl I I IylI1-7

0
0 I 2 3 4 5 6

(a) Voltage conditions neglecting positive- and ncgative- (c) Voltage conditions for Rl=R2=0.2 X1.
sequence resistance--R, = Rz = 0. *,A. *
Fig. 29-Maximum line-td-gtound vo&ge at fault location
for grounded-neutral system under any fault condition.
Note: Numbers on curves indicate maximum line-to-ground fault
voltage of any phase for any type of fault in percent of unfaulhd
line-to-line voltage for area bounded by curve and axes. When using
the curves all impedance values must be on the same kva base or in
ohms on same voltage base. For all curves
100 R, = zero-sequence resistance,
6 /
/ X0 = zero-sequence inductive reactance,
XI =positive-sequence subtransient reactance,
X2 = negative-sequence reactance,
x, =x,.
The effect of fault resistance was taken into account. The fault rO-
sistance which gives the maximum voltage to ground on any phm
was the value used. The discontinuity of the curves is caused mainly
by the effect of fault resistance.

zero-sequence resistance, R. to X1, is plotted against


1X0/X1, for several different values of maximum linote
ground fault voltages, ranging from 65 to 100 percent of
line voltage and for three values of RI/X,, namely 0, 0.1
and 0.2. The area below each curve represents the region
-- in ‘which the maximum fault voltage is below the value
I iTY4i i i iA indicated on the curve. The curves represent the mMi-
mum voltage at the fault location. k fault at the arrest@
mill generally subject the arrester to a higher voltage thy
a fault at some other point in the system. However, thM
condition does not always exist and should be checked
For example a fault near the Lource of a ra
circuit grounded at the source only through a neu

(b) Voltage conditions for R, = R, =O.l Xl. resistor or reactor might have a larger value of
Chapter 18 Insulation Coordination 627

,nd therefore produce a higher voltage on an arrester The 84-percent arrester can be applied safely on systems
located at the end of the feeder than a fault at the ar- whose constants are within the range indicated by the
&er location. 80-percent curve of Fig. 29 provided the impulse insulation
ln applying arresters, it is cust,omary to make an allom- level of the equipment is protected. As a general guide
:I,lre for operation at a voltage in escess of that usually to arrester application, with full insulation on the pro-
c,J~lsitl(~red3s normal. This is usually five percent. For tected equipment, the 84 percent arrester rating is satis-
cs:implc, an arrester rated at 105 percent of normal line- factory if the following conditions exist.
to-line voltage is used where the line-to-ground voltage 1. The ratio of the zero-sequence resistance, Ro, to
is expected to reach normal line-to-line voltage during the positive-sequence subtransient reactance, X1, as
fault. Likewise, on a solidly grounded neutral system viewed from the point of arrester location is one or
where the maximum line-to-ground voltage during fault less.
is expected not to exceed 80 percent of line voltage, an 2. The ratio of zero-sequence reactance, X0, to positive-
nrrester rated at about 84 percent of normal line-to-line sequence reactance, X1, as viewed from the point
voltsge has been used generally. The line-to-ground volt- of arrester location does not exceed three under any
:Lgcfor fault conditions where X0/X, ratio is near 1.0 or condition of oporstion.
lessmay allow the use of arresters with less than 84 percent 3. The arrester cannot remain energized from un-
(If line-to-line voltage. grounded sources of power after the grounded neu-
‘I’hcrc are a number of isolated-neutral systems on which tral sources of power have been disconnected to
:Ilresters rated at 105 percent of nominal line-to-line volt- clear a fault.
:Lg(:have proven satisfactory over a period of years. How- 4. The system neutral is grounded at every source of
(;vcr, there are also systems of this type where it has been supply of short-circuit current.
ncccssary to use arresters of a higher rating to prevent If the fault is to the arrester ground, then the resistance
,:sccssive failures. This is indicated in Fig. 28, which of the arrester ground should be included as part of the
s\lo\\-sthat if fault resistance is included, the fault voltage zero-sequence resistance of the system. When this is
may exceed 105 percent of normal line-to-line voltage. done, the curves of Fig. 29 also apply to the arrester at
C:Jculntion should be made to determine the maximum that fault location.
fault voltages. In addition to high arrester voltages resulting from
The overvoltages encountered on systems grounded system faults, high momentary or peak voltages may also
throllgh ground-fault neutralizers are less than on isolated be caused by any of the following:
neutral systems, provided the ground-fault neutralizer is 1. Switching surges may reach several times normal
properly tuned. Arresters rated to withstand maximum line-to-ground voltage with certain combinations of
line voltage, usually 105 percent of normal circuit voltage, system constants.
MC, therefore, considered safe for application on these 2. High harmonic voltages to ground may exist during
systems. There is some risk of damage to the arrester if fault conditions on lightly loaded lines energized
t Ilc ground-fault neutralizer is not properly tuned. Switch- from generators with damper windings for which
ing operations on thrsc systems may also produce high X,“/X,” is too great. See Chap. 6.
voltngcs to ground. However, it is gcnernlly not feasible 3. Arcing grounds or the accumulation of static charges
to select arresters of sufficiently high rating to eliminate from dust particles in the air on ungrounded sys-
:Jl risk of arrester damage from these causes. tems may cause repetitive discharges through the
It has been common practice to apply arresters rated at arrester that exceed its thermal capacity.
105percent of circuit voltage to systems grounded through It is not considered feasible to apply arresters rated
impedance, and arresters rated at 84 percent of circuit sufficiently high to withstand the overvoltages that might
voltage (80 percent of 105 percent rating) to systems con- be produced by any of the above. However, the possi-
sidered solidly grounded. Experience has shown that such bility of damage to the arrester from these causes should
:Vplications are generally safe against over-voltage at time be considered in making the application. It is sometimes
of fault. However, as indicated by Fig. 28, the possible possible to make minor modifications to the system equip-
line-to-ground voltages during faults on systems vary ment or operation that will greatly alleviate these sources
blirough a wide range, depending upon the ratio of system of trouble.
constants. Arresters rated at some voltage between 75 Where there is doubt as to the arrester rating, the
and 105 percent of circuit voltage may, therefore, be better maximum line-to-ground voltages should be calculated by
suited from an overall standpoint. the methods of Chap. 14.
As indicated by Fig. 29 (a, b, c), the maximum voltage
to ground varies with the ratios of &/Xl, X,/X, and 9. Coordination of Protective Devices with Appa-
111/X1. Thus the voltage to ground can be determined ratus Insulation
for a given system if the impedance constants are accu- The margin that should exist between the BIL of the
rately known. In some cases, particularly for the higher insulation to be protected and the maximum voltage that
“oltage systems, where the X0/X1 and R,/X, ratios are can appear across a lightning arrester is a much-discussed
1.0 or less, arresters less than 84 percent of line-to-line question. The answer is difficult because it depends on
“oltage can be used, thus allowing the application of trans- many factors. The breakdown voltage of the arrester is
former insulation with a minimum acceptable impulse affected by the rate of voltage rise and the discharge voltage
insulation level. by the rate of rise of the surge current and the magnitude
628 Insulation Coordinatzon Chapter 18 ,:

of the surge current. The distance between the arrester Suppose it is desired to protect the 138-kv substation
location and the protected insulation affects the voltage shown schematically in Fig. 30 against traveling waves.
imposed on insulation due to reflections. The severity of The system at this point is grounded SO as to allow a basic
the surge depends upon how well the station is shielded, impulse insulation level of 550 kv. The major equipment
the insulat,ion level of the station structure, and the in- consists of a power transformer, circuit breakers, discon,
coming line insulation. A typical problem is reviewed nect switches mounted on four apparatus insulator units
later to give one way of applying a suitable margin. and bus insulation consisting of 12 suspension insulators)
Direct strokes to an arrester should be eliminated, where The line insldation consists of nine suspension insulators, -
possible, by proper shielding because the current in a direct The arrester is located close to the transformer. Adequate
stroke may be in excess of that for which the arrester is shielding is provided over the substation and the incoming
designed. Where shielding is impractical, the arrester transmission lines.
should protect the insulation within the range of direct- The line insulation of nine insulators permits a trav
stroke surge currents within the capability of the arrester. wave of 860-kv crest (13X40) and rate of rise of 10
Currents in excess of the arrester rating may damage or per microsecond to enter the station. This rate of rise
ruin the arrester. represents 8.25 kv per microsecond per kv of arrester
For a traveling wave coming into a dead-end station, rating for the required 121-kv arrester. From Fig. 26 the
the discharge current in the arrester is determined by the average arrester-gap breakdown is 3.6 X 121 or 435 kv at
maximum voltage that the line insulation can pass, by 0.5 microsecond, which, with a 15 percent plus tolerance,
the surge impedance of the line, and the voltage character- becomes 500 kv. Assuming a line surge impedance of 466
istic of the arrester, according to the following relation: ohms, the magnitude of the arrester current is about 3200
amperes determined as follows:
2E-E,
I,=7 I =2 (860 000) -435 000
a = 3200 amperes.
where I, -arrester current 400
E -magnitude of incoming surge voltage The rate of rise of current would be approximately
En-arrester terminal voltage
2 -surge impedance of the line 2 (1 000 000)
= 5000 amps/microsecond.
400
From Fig. 27(b) the discharge voltage for a current
of 3200 amperes and a rate of rise of 5000 amperes is
3.45X 121 or 418 kv. Adding the manufacturing tolerance
of plus 10 percent gives 460 kv as the discharge voltagc
provided by the 121-kv arrester for the assumed condi-
tions. Since the rate of rise has been taken into consid-
1600 eration in establishing this protective level of 460 kv, no
additional margin need be added. There is, however, a
difference of 550 minus 460 or 90 kv between the pro-
tective level and the BIL of 550 kv of the transformer
insulation.
Suppose a direct stroke at the station discharges through
the arrester a current of 50 000 amperes, rising to crest in
three microseconds, with a nominal rate of rise of 20 000
amperes per microsecond. The discharge voltage from
Fig. 27 (b) is 4.55X121 = 550 kv for a 121-kv arrester
which with plus 10 percent is 605 kv or 55 kv in exc@Y
of the insulation BIL.
10. Location and Connection of Protective Device8
200 The protective device should be placed as close as Pas-
sible to the apparatus it is to protect, particularly ;if$@
0 overhead line dead ends, in a station or terminate+ a$#
MICROSECONDS
transformer. A traveling wave coming into the statlon’l@
limited in magnitude at the arrester location to the’di@
Fig. 30-Coordination of insulation in a 13%kv substation for charge voltage of the arrester. However, a wave with the
11/* x 40 microsecond positive wave.
same rate of voltage rise as the original wave and with
(1) Transformer with 550 kv BIL. a magnitude equal to the arrester discharge voltage travel8
(2) Line insulation of 9 suspension units.
on to the station terminus where it reflects to twice lte
(3) Disconnect switches on 4 apparatus insulators.
(4) Bus insulation of 10 suspension units.
value if the line dead ends or to almost twice its value
(5) Maximum 1% x 40 wave permitted by line insulation. if the line terminates in a transformer. The voltage at
(6) Discharge of 121-kv arrester for maximum 1% x 40 full the transformer builds up at a rate iwice that of the
wave. original wave until it reaches a maximum value of tw?: ; ::
Chapter 18 Insulation Coordination 629

the mngnit~tdc of the arrester voltage or to whatever volt-


age magnitude can build up during the time the reflected
lvave travels back to the lightning arrester and a negative
reflected wave travels from the lightning arrester back to P
the transformer. I
Likewise, apparatus, such as a disconnect switch, lo- ARRE=iTER
-- -
cat,ed ahead of the arrester is subject to the incoming
snrgc until the arrester discharges and its negative re-
flected wave i-&urns to the switch.
To illustrate the effect of arrester location consider the
13%kv station shown schematically in Fig. 31 with the
arrester located 100 circuit feet beyond the disconnect
switch and 100 circuit feet ahead of the transformer. Con-
sider a traveling wave having a rate of voltage rise of
1000 kv per microsecond entering the station and an ar-
rester which limits the voltage to 400 kv. In 0.1 micro-
second after the wave reaches the switch it reaches the
lightning arrester and 0.1 microsecond later, or at the end
of 0.2 microsecond, it reaches the transformer where it re-
flects and builds up at a rate of 2000 kv per microsecond.
At the end of 0.4 microsecond after the wave first reached
the switch, the incoming wave and the reflected wave
from the transformer would total to 400 kv at the arrester.
I-Is shown in Fig. 31, the voltages at the switch and at
the transformer would also be 400 kv. The reflected wave
from the transformer has just reached the switch. The
voltage at the arrester remains at 400 kv until the crest
of the incoming wave is reached but the voltages at the I
I
I I
I
I
1
I
I
switch and transformer continue to rise at 2000 kv per ARRESTER VOLTAGE
microsecond until the reflected negative waves from the I
arrester reaches the switch and transformer at the end of,
0.5 microsecond. Successive reflections occur until the
wave spends itself by discharging through the arrester.
0 100 200 300 400 5 0
As shown in. Fig. 31, the voltages at the switch and trans- L IN CIRCUIT FEET
tormer resulting from the first reflection reaches 600 kv, Fig. 32-Maximum voltage due to first reflection of traveling
or 50 percent more than t,he arrester discharge voltage. wave as function of distance from arrester and steepness of
The maximum voltage at the terminus of a $ or at a wave front.
transformer at the end of a line beyond an arrester as a *Voltage at P may reach crest of incoming surge as maximum.
Voltage at T may reach twice arrester voltage as maximum.

result of the first reflection of a traveling wave, may be


100 FT 100 FT expressed mathematically, as follow@:
DISCONNECT I
SWITCH TRANSFOR/MER
4
up to a maximum of 2 e,,
where en= arrester discharge voltage
de
- = rate of rise of wave front in kv per ms.
dt
L = distance between arrester and line terminus in
feet.
The same expression can also be used to determine the
MICROSECONDS
(0) lb) (cl
voltage at a point on a line ahead of an arrester due to a
traveling wave. In this case, the voltage can reach as a
Fig. 31-Voltages at 138 kv substation resulting from first re- maximum the crest of the traveling wave if the distance
flection of traveling surge having 1000 kv per microsecond to the arrester is great enough or if the rate of rise of the
wave front.
wave front is sufficiently high.
(a) At disconnectswitch located 100 feet ahead of arrester. The curves of Fig. 32 show the voltage in excess of the
(b) At arrester. arrester voltage as a function of distance from the arrester
(c) At transformer located 100feet beyond arrester. for rates of rise of wave front of 100, 500, and 1000 kv per
630 Insulation Coordination Chapter 18

microsecond. The curves can be used to determine the tive device is mounted direct,ly on the transformer. This
actual voltage at a point ahead of an arrester or at a line is illustrated in the installation view, Fig. 33, of a CSP
terminus beyond an arrester by adding to the curve value transformer which has the protective devices, secondary
the discharge voltage of the particular arrester involved. circuit breaker, and metering equipment built integral
For example, the maximum voltages obtained at the with the transformer14. With the line side of the arresters
switch and transformer in Fig. 31, by plotting the volt- connected directly to the transformer terminals and the
time curves, could be taken from the 1000 kv per micro- arrester ground connected directly to the transformer tank,
second curve of Fig. 32. For a distance of 100 feet, and a the voltage between the winding and core is definitely lim-
wave front that rises at the rate of 1000 kv per micro- ited to the discharge voltage of the arrester. To provide
second, the voltage in excess of the arrester voltage is 200 protection to an extended station an arrester should be
kv. This added to the arrester discharge voltage, assumed located directly ahead of the disconnect switch where the
to be 400 kv, gives 600 kv as the maximum voltage after line enters the station and another arrester located directly
the first reflection. adjacent to or on the transformer. A modification of this
In addition to the reflected wave phenomena, it is quite scheme, which is sometimes used, is to locate protector
possible that still higher peak voltages would exist at the tubes at the entrance to the station and convent,ional sta-
apparatus as a result of oscillations caused by the induct- tion type arresters at the transformer terminals. The pro-
tector tubes will generally protect the switch and will limit
the magnitude of surges entering the station.
11. Direct Stroke Protection
Wherever it is possible for direct strokes of lightning to
strike the line at or near the station, there is a possibility
of exceedingly high rates of surge-voltage rise and large
magnitude of surge-current discharge. If the stroke is
severe enough, the margin of protection provided by the
protective device may be inadequate. The installation
may, therefore, justify shielding the station and the incom-
ing lines far enough out to limit the severity of surges that
can come into the station, particularly in the higher volt-
age classifications, 69 kv and above. This can be done by
properly placed masts or overhead ground wires.
The number of direct strokes per year to an unshielded
substation, based on accumulated records of direct strokes
to tall objects, can be approximated by the expressionI
(w+700)(L+700)g 5
(5280)* ’
/ Et
o.c.0. I
ARRESTER
T

(a)
Fig. 33-Installation view of CSP power transformer with
protective devices, secondary circuit breaker, and metering
equipment built integral with transformer. ,~,

ante of the line between the arrester and the apparatus,


and the capacitance of the apparatus. Furthermore, the
voltage drops in the lead from the line to the arrester and
in the lead from the arrester to ground, which are affected
(b)
by rate of rise of surge current, add t.o the drop across the
arrester. Any difference in ground potential between the APPROX. l/2 MILE
rl
apparatus ground and the arrester ground also adds to the u
PROTECTOR O.C.0.
voltage impressed across the apparatus insulation. In I
ARRESTER
view of the above factors, it is important, particularly in
stations where direct strokes may originate close to the
station, that the protective devices be located close to the
apparatus they are to protect, that the leads to the devices Fig. 34-Typical schemes of station protection.
be kept as short and direct as possible, and that the ar- (a) Arrester at station with no direct stroke shielding.
rester and apparatus grounds be interconnected and as low (b) Arrester at station with shielding against direct strokes-
in resistance as possible, preferably one ohm or less. (c) Arrester at station with protector tubes extending out g
The ultimate in this respect is reached when the protec- mile.
Chapter 18 Insulation Coordination 631

where IT; and I; are the width and length, respectively, in


feet, of the substation. From this estimate of strokes to
an exposed substation, which is about one stroke every
four and one-half years to a 100 feet square substation, it
can be reasoned that reducing the exposure to 0.1 percent
would practically eliminate the possibility of a stroke to a
station. The curves of Fig. 3515 were, therefore, con-
structed from extensive laboratory test data to show the
configurations of masts or overhead ground wires necessary
to reduce the exposure of an object to 0.1 percent. The
curves are plotted to show the height (L) of the shielding
X IN FEET
0

(cl (4
Fig. 36-Areas protected by multiple masts for point expo-
sures of 0.1 percent.
(a) Two masts with values of 2 and s taken from Fig. 35 (a)
and (c).
(b) Two masts separated by half the distance of those in (a).
(c) Three masts with (b) points obtained from Fig. 35 (c) for
mid-point between two masts.
(d) Four masts with (b) points obtained from Fig. 35 (c) for
mid-point between two masts.
100 50 25
d=lOO 50 25
(0)
masts or ground wires above the protected object as a func-
tion of the horizontal separation (X) and the height (d) of
X IN FEET
0 the protected object.
The dotted-line curves, Fig. 35 (a), showing the neces-
sary configuration of a single mast protecting a single ob-
ject, apply to an exposed structure having a single prom-
inent projection or several projections in a limited region,
such as a set of disconnects. The full-line curves, applying
to a ring of objects, should be used if the live parts to be
shielded are generally distributed at a given height. The
configuration of the mast should be based on the most
remote object.
The required configurations of a single horizontal ground
wire are given in Fig. 35 (b). The dotted-line and the
full-line curves of Fig. 35 (c) apply, respect,ively, to two
(b) masts and to two horizontal ground wires.
S IN FEET The diagrams of Fig. 3615illustrate the area that can be
protected by two or more shielding masts. The cross-
hatched area of Fig. 36 (a) is the area protected by two
masts for given values of d and y, where the radii z of the
semi-circles are taken directly from Fig. 35 (a), and the
separation distance S from Fig. 35 (c). If the distance
between masts is decreased, the protected area is at least
equal to the area obtained by superposing the areas of
Fig. 36 (a). For example, if the distance between masts is
halved, the resultant protected area is somewhat as shown
in Fig. 36 (b).
(Cl On this basis, to form an approximate idea of the width
Fig. 35-Configuration of shielding object with respect to of the overlap between masts, first obtain a value of y from
protected object for 0.1 percent exposure. Fig. 35 (c), corresponding to twice the actual distance be-
(a) One shielding mast. Dotted lines for one exposed object of tween the masts. The width-of overlap is then equal to the
height (d). Full lines for ring of exposed objects of height value of Z, obtained from Fig. 35 (a), that correspond to
Cd). this y. This undoubtedly gives a conservative width of
(b) One horizontal ground wire. substation that can be protected by two masts.
(c) Two masts or two ground wires. Dotted lines for masts. For three masts located at the points of an equilateral
Full lines for horizont,al wires. triangle or for four masts located at the points of a square,
632 Insulation Coordination Chapter 18

the protected areas are as shown in Figs. 36 (c) and (d). 3. Modern type lightning arresters applied properly
The height of the shielding mast should be so chosen that protect station apparatus conforming to basic insu-
the b points provide 0.1 percent exposure as obtained from lation levels against traveling surges. On Systems
Fig. 35 (c) for the midpoint between two masts. The 2 having a solidly grounded ncutrnl reduced rating ar-
radii are obtained from the data for a single mast. resters can be applied. Full-rated arresters are re-
The curves of Fig. 35 apply to stations located in regions quired generally on ungrounded neutral systems or
of relatively flat terrain and low resistivity, where the systems grounded through impedance. The possibil-
effective ground plane is essentially at the earth’s surface. ities of system overvoltages should be investigated
High values of earth resistivity lowers the ground plane, carefully in determining the minimum rating arrester
which results in less effective shielding for a given config- that can be applied economically.
uration. However, most stations are, or if not, should be, 4. For effectively grounded systems insulation levels
provided with low-resistance grounding systems for light- one class below the standard have given satisfactory
ning-arrester grounds, which can also serve as shielding service using reduced rated arresters particularly at
grounds. Where the soil resistivity is high the effective voltages 115 kv and above.
ground plane can be raised to the earth’s, surface by laying 5. Consideration should be given to shielding stations
counterpoise wires from the shielding masts to distances of against direct lightning strokes. Where shielding is
two or three times their height. However, in most cases, not practical, additional protection can be provided
it is probably more economical to increase the height of by installing protector tubes at the entrance to the
the masts. station and at each transmission-line tower for a dis-
For application of the curves to hillside locations, the tance of f mile from the station.
dimensions (h) (the shielding mast height) and (cl) (the
height of the protected object) should be measured per- VI. PROTECTION OF DISTRIBUTION
pendicular to the earth’s surface. The distance (r) be-
TRANSFORMERS
tween the object and shielding mast should be measured
along the earth’s surface. The distribution transformer with its protective devices
The lines coming into the station can be effectively is in effect a miniature substation constituting the final
shielded against direct strokes by overhead ground wires voltage transformation between the generating station and
as outlined in Chap. 17. A direct stroke on a line more the individual customer’s premises. Because the distribu-
than 3 mile out from the station is limited in severity at tion transformer is small in size and comparative cost, and
the station by the surge impedance and insulation of the because it is usually pole mounted, often in out-of-the-way
line and to some extent by the shunt capacity of the station locations, its protective devices must be inexpensive, small
equipment. Shielding of the station and the lines approx- in size and weight, simple, and reliable. The failures of
imately 4 mile out from the station, as illustrated in Fig. early type distribution arresters and the large amount of
34 (b), is, therefore, a desirable supplement to the lightning lightning data obtained on distribution circuits furnish
arrester located at the station. proof that the protective devices must also have the ability
Where overhead ground wires on the incoming lines are to withstand severe lightning discharges.
not practical due to existing construction, additional pro-
tection of the station equipment against direct strokes on 13. General Considerations
the lines near the station can be obtained by equipping Distribution circuits are generally overhead construction
each line with protector tubes at the entrance structure of and are, therefore, subject to lightning disturbances, the
the station and at each tower for a distance of approxi- nature of which are discussed in detail in Chap. 16. Data
mately 3 mile out from the station, see Fig. 34 (c). How- collected over a period of years with surge-crest devices
ever, shielding the station is the only way to eliminate indicate that the majority of surge-current discharges on
direct strokes to the station itself. distribution circuits are relatively low in magnitude, less
than 5000 amperes, but occasionally a discharge may ex-
12. Summary of Considerations Applying to Pro- ceed 100 000 amperes. More recent data collected with the
tection of High-Voltage Equipment fulchronograph show that some of the surge-current dis-
The following points can be generally concluded in the charges that are moderate in magnitude may be long in
application of protective devices to high-voltage systems, duration, of the order of several thousand microseconds.
22 kv and above. See Chap. 16.
1. Rod-gaps do not protect apparatus insulation against Experience has shown that lightning disturbances are
surges of steep wave front unless the spacing is so more severe on rural circuits than on urban circuits, prob-
low that the gap is subject to numerous flashovers ably for two reasons. First, rural circuits are generally
from minor surges. more exposed to lightning and, therefore, receive many
2. Protector tubes are not considered suitable for the more direct strokes. Second, because distribution trans-
protection of apparatus insulation although they are formers are less frequent on rural circuits-the drainage of
effective in preventing transmission-line flashovers long-duration surges through grounded transformer wind-
and in decreasing the severity of surges from direct ings is less16.
strokes near the station. The application of protector These general conclusions have been borne out by oPer-
tubes involves certain limitations in system short- ating experience with distribution lightning arresters. The
circuit and recovery voltage characteristics. failure rate of early arresters, attributed to lightning, that
Chapter 18 Insulation Coordination 633

were designed before high surge-current testing facilities The distribution transformer (2400 to 13 200 volts) has
nere available was comparatively high. Later arresters, a much higher ratio of surge strength to operating voltage?
designed and tested to withstand high surge currents of as Table 1 shows. As an example, the ratio of the basic
about 100 microseconds duration have a good operating insulation level to the peak of the GO-cycle voltage classi-
record on urban circuits. However, when these arresters . . 45
were applied more extensively to rural circuits with sparse- ficatlon 1s 2,5x
~- d2 - 12.75, for 2500 volt equipment, as
ly located transformers, the failure rate increased. Modern 650
arresters, designed with more emphasis on ability to dis- against I38 x l/2-=3.33, for 138-kv equipment. For this
charge surges of long duration, have acquitted themselves reason, it is permissible for the protective device in the
\vell on rural circuits. low-voltage ratings to have a higher protective ratio than
Most distribution transformers are pole mounted, one at that required at higher voltages.
a location, and are used to step the voltage down from a The effect of the location and connection of the protec-
single-phase primary circuit (2300 to 13 200 volts) to a tive devices is more pronounced with distribrrtion trans-
single-phase, three-wire, secondary circuit at utilization formers. Because lightning discharges on distribution cir-
voltage, usually 120/240 volts. Occasionally they are used cuits and on high-voltage transmission circuits are about
in three-phase banks to supply three-phase, low-voltage equal in magnitude, the actual surge-voltage drops in the
power. The primary circuits, whether single or three- leads to the protective devices and through the ground
phase, may be from a source having either a grounded or connections of the two circuits are about equal. While
ungrounded neutral. If the neutral is ungrounded the these voltage drops may be only a portion of the discharge
single-phase primary consists of two of the ungrounded voltage of the protective device in the higher voltages, they
phase conductors, which means that the two primary ter- may be several times the discharge voltage of the low-
minals of the distribution transformer must be equally voltage protective device. It is extremely important,
protected. If the neutral is grounded, the single-phase pri- therefore, that protective devices on distribution circuits
mary circuit will usually consist of one phase wire and the be located and connected properly with respect to the
neutral conductor. The neutral conductor is usually apparatus they are to protect.
grounded, so that only one high voltage terminal of the
distribution transformer need be provided with protective 14. Methods of Connecting Protective Devices
equipment. The secondary will usually be three-wire, with Three schemes of connecting protective devices to pro-
the mid-point grounded. tect distribution transformers against lightning surges are
~1three-phase bank of distribution transformers may be commonly known :
connected delta delta, star delta, or delta star. With the
delta delta connection, the secondary can have no common 1. Separate connection method.
neutral. Sometimes, either one phase or the mid-point of 2. Interconnection method.
one of the phases of the secondary is grounded. The star 3. Three-point protection method.
delta and delta delta connection are alike as far as the Separate Connection Method-This method of pro-
secondary delta connection is concerned. The primary tection, universally used until about 1932, is illustrated in
neutral might or might not be grounded. The delta star Fig. 37. Protective devices are connected between the pri-
connection usually has the common neutral of the star
connected secondary grounded. H.V. ~ L.V.
In addition to surge protection, the distribution trans-
former usually includes protection against internal short-
circuit and secondary short-circuit or overloads consisting
either of high-voltage fuses mounted external to the trans-
former, or high-voltage fuse links and a secondary circuit
breaker mounted inside of and included as a part of the
transformer. .
The distribution transformer, like larger power trans- LA ‘LA
formers contains three groups of insulation subject to volt-
L-r’
age stress, which should be considered in the protective T
scheme, namely : Fig. 37-Separate connection method of protecting single-
1. The insulation between the high-voltage winding and phase transformers.
the core or tank.
2. The insulation between the low-voltage winding and mary conductors near the transformer and a driven ground
the core or tank. at the pole. The secondary neutral is usually grounded
3. The insulation between the high- and low-voltage separately. With this connection, the protective devices
windings. are connected in series with a relatively long ground lead
There are, however, two conditions that make the pro- which has considerable inductance and is usually connect-
tection of distribution transformers and high-voltage power ed to a driven ground, the resistance of which may be high.
transformers differ. These are the difference in the ratios The voltage, therefore, between the primary winding and
Of surge strength to operating voltage and the relative ground is not only the discharge voltage of the arrester but
@ects of locating and connecting the protective devices. also the impedance drop of the ground lead and ground
634 Insulation Coordination Chapter 18
.j

4
(a) (bl (cl
Fig. 3CInterconnection method of protecting single-phase transformers.
(a) Straight interconnection. (c) Interconnection with protective ground at transformer and
(h) Interconnection with protcctivc ground at transformer. insulating gap in interconnection.

connection, which may be several times the discharge volt- ground, or, if not, upon the magnitude of voltage drop
age of the arrester. Failure or flashover of the transformer in the arrester ground lead and connection. The arrester
insulation may occur even though the actual surge voltage ground is in parallel with the secondary ground so that
across the arrester is only a fraction of the transformer the complete surge is not directed to the secondary. The
breakdown voltage. When this happens, the surge gener- direct tie between the arrester ground and secondary is
ally passes through to the secondary ground connection. undesirable unless the secondary is effectively grounded,
The surge is usually followed by a flow of dynamic current again making the connection generally unapplicable to
until the primary fuse blows. rural circuits.
Interconnection Method-The straight interconnec- Another modification that eliminates the permanent
tion consists of connecting the protective devices from the tie between the arrester ground and secondary neutral ia
primary lines directly to the secondary neutral as illus- shown in Fig. 38 (c). An isolating gap, having low flash-
trated in Fig. 38 (a). The surge voltage that can exist over, breaks the direct tie. A rise in potential between
between the primary winding and the secondary is de& windings during a surge discharge breaks down the gap
nitely limited to the discharge voltage of the protective and limits the voltage between windings to the arrester
devices. The potential of the core and tank, because of discharge voltage. The protection of the transformer
their electrostatic coupling to the secondary winding, nor- insulation to the core or tank still depends upon the tank
mally rises along with the primary and secondary windings being insulated from ground, or, if not, upon the voltage
during a surge discharge and thus limits the voltage be- drop in the arrester ground lead and connection being
tween the windings and core. This connection is an im- low.
provement over the conventional connection because it Three-Point Protection Method-This scheme, il-
eliminates the factor of voltage drop in the arrester ground lustrated in Fig. 39 (a), definitely limits the voltage across
lead. Operating experience supports this conclusion17. the three groups of insulation in the transformer inde-
Two decided disadvantages prevent universal applica- pendently of ground connections or resistances. The pro-
tion of this scheme of connection. First, the protection tective devices connected between the high-voltage linea
between windings and core or tank depends upon the tank and tank definitely limit the voltage between those part8
rising in potential with the windings. Actually, practical to the discharge voltage of the protective device. Like-
conditions might keep this from happening. The resistance wise, the protective device between the secondary and
to ground of the wood pole on which the transformer is tank (usually a gap for 480 volts and below) limits the
mounted may be low enough to supply the small charging voltage between those parts to the breakdown voltage of
current required to keep the tank at ground potential. the device. With the voltage between the high-voltago
Also, as it rises in potential, the tank may flashover to a winding and core or tank and the voltage between the low-
nearby guy wire or other grounded object. Either condi- voltage winding and core or tank definitely limited, the
tion results in the application of the full potential of the voltage between the two windings is also limited.
surge between the windings and tank until the insulation Referring to Fig. 39 (a), a surge coming in over a Pri-
breaks down or the secondary flashes over to the tank. mary lead raises the potential of the primary winding to
The second disadvantage of this connection is that it the breakdown of the protective device that discharges
directs the entire primary surge voltage into the second- to ground. If the arrester-ground impedance is high or fi
aries, which is undesirable, particularly if the resistance of there is no ground at that point, the potential of the hi@
the secondary grounds is not low. This restriction makes voltage winding rises above that of the core and tank untl’
the straight interconnection in general unapplicable to the gap TG breaks down and limits the voltage between
rural circuits or other circuits that might not have the the winding and tank to the discharge voltage of the
secondaries effectively grounded. arrester plus the gap. If the voltage between the tank ad
A modification of the straight interconnection is shown secondary exceeds the breakdown of the gap TN, the gap
in Fig. 38 (b). Here, a ground is made at the arrester lo- operates and discharges to the secondary ground. The
cation also. The protection provided the transformer in- gaps, TG and TN, while they definitely isolate the
sulation depends upon the tank being insulated from from the primary and secondary ground connection
Chapter 18 Insulation Coordination 635

protection to the three groups of insulation in the trans-


former independently of the arrester or secondary ground-
ing conditions, whether the tank is insulated or not, or
whether the surge originates on the primary or secondary.
Variations in the methods of connecting the protective
devices to obtain three-point protection are shown in (b),
(c), (d), and (e) of Fig. 39.
15. Protection of Three-Phase Transformer Ranks
The shortcomings of the separate connection method of
protection apply equally well to the protection of three-
DOUkiLE
phase transformers or three-phase transformer banks on
PROTECTIVE GAP
distribution circuits. The interconnection method is gen-
erally not applicable bccausc there is no secondary neutral
---- unless the secondary is connected in star. Sometimes one
phase of the secondary or the midpoint of one of the phases
(b) ---
is grounded as shown by the broken lines of Fig. 40.
--- The three-point scheme of protection, illustrat,ed in
Fig. 40, is applicable to any winding connection. A pro-

%
T

4
(d)
N

Fig. IO-Three-point protection applied to three-phase dis-


tribution transformers.

tective device is connected between each primary phase


winding and tank either directly or through an isolating
b-3) gap. Likewise, a protective device (air gap or coordinated
secondary bushing for 480 volts and below) is connected
between each secondary phase lead and the tank. The
tanks of all transformers in the bank are tied t,oget,her.
With this connection, the windings of all transformers are
protected irrespective of grounding conditions or whether
Fig. 39-Three-point protection method.
the surge originates on the primary or secondary circuit.
(a) Three-point protection with insulating gaps.
(b) Three-point protection simplified circuit, 16. Surge Voltages in Secondary Circuits
Cc) Three-point protection with single insulating gap. Overhead secondary circuits are, to some extent, sub-
(d) Three-point protection of single-phase transformer on four- ject to lightning surges originating on the secondary.
wire, grounded-neutral circuit. They can also experience surges passing from the primary
(e) Three-point protection with insulated tank.
into the secondary. The separate connection, Fig. 37,
isolates the primary from the secondary. However, when
ing normal operation, do not greatly add to the surge the transformer fails or flashes over as a result of a pri-
volt,age impressed across the winding insulation. The mary surge, the surge passes directly on to a phase wire
three-point scheme of protection thus provides definite or neutral of the secondary circuit. The primary-system
636 Insulation Coordination Chapter 13

voltage is also impressed on the secondary until the pri- are often located in remote locations, it is important to
mary fuse blows. The straight interconnection directs all avoid as many fuse replacements as possible. For that
the primary surge on to the secondary neutral. With the reason and because of the somewhat questionable pro-
modified interconnection shown in Fig. 38 (b) or with the tection obtained for surges of steep wave front, plain air
three-point scheme of protection, some of the surge may gaps or fused gaps are not extensively used to protect
pass on to the secondary neutral, depending upon how distribution transformers.
effectively the primary protective devices are grounded. Protector Tubes-The distribution-type protector
Experience has shown that damage caused by surges on tube, introduced about 1931, consists essentially of a small
secondary house circuits is negligible. Where long expo- air gap, a diffuser tube, and sometimes a resistor, all con-
sures and relatively high secondary insulation may result nected in series. The series gap is just enough to insulate
in damage, protection should be provided by low-voltage the tube from normal power voltage, thus eliminating a
protective devices located at the house entrance, and con- continuous voltage stress across the diffuser tube. The
nected between the phase wires and neutral, which is purpose of the series resistor when used is to limit to
usually grounded. All grounds on the customer’s premises approximately 500 amperes the one-half cycle of power
should be connected together. In case the secondary is
not grounded in the customer’s premises, such as may be
the case with :L three-phase, four-wire delta circuit, the
danger of damage is greater than with the usual house
circuit. Where the hazard is considered serious, it can be
eliminated by connecting a protector between each phase 80
wire and ground at the house entrance, or preferably right
at the apparatus to be protected.
Three-phase, 440-volt circuits sometimes extend a con-
siderable distance overhead to motor circuits, thus con-
stituting a hazard to the motors and associated starting
equipment. They can be protected by connecting a low-
voltage protective device between each phase wire and
the frame of the apparatus, which should be grounded.
Protectors connected to the secondary at the transformer
will generally not provide adequate protection to the load 01234567 01234567
apparatus. MlCROSECONDS
17. Protective Devices for Distribution Trans- Fig. 41-Volt-time breakdown characteristics of one type of
formers distribution type protector tubes.
Three general classes of devices are used for the protec-
t ion of distribution transformers just as for the protection current that may follow the surge discharge, thus making
of high-voltage substations, namely, the plain air gap, the the application of the tube independent of the system
protector tube, and the conventional valve-type lightning short-circuit current.
arrester. However, the lower operating voltages, the The gap breakdown characteristics of the different volt-
higher ratio between insulation breakdown voltage and age ratings of a typical type of protector tube are shown
operating voltage, and the requirement that the device be in Fig. 41. After the gap breaks down, the discharge
small in size and cost, make the design and application of voltage is equal to the arc drop in the tube plus the drop
protective devices somcwhnt different for distribution across the series resistor, if one is used. The series resistor
transformers than for higher voltage equipment. is generally provided with a shunt gap that limits the
Plain Air Gap-Plain air gaps or fused gaps are some- voltage across the resistor to about 30 kv. If the lightning
times used to protect distribution transformers. The surge is of sufficient current magnitude to build up &
relatively high insulation strength of the transformer resistance drop of 30 kv across the resistor the shunt gap
makes it possible to provide a fair degree of protection to flashes over and takes the resistor out of the discharge cir-
the transformer against lightning surges without having cuit in which case the discharge voltage is the arc drop
to decrease the gap spacing to a value where numerous through the tube. Surge currents high enough to cause
flashovers occur as a result of minor surges. However, the shunt gap to flash over, produce sufficient deionizing
the device will not restore power voltage (above 480 volts) action in the diffuser tube to cut off after the discharge
after a discharge without momentarily deenergizing the without the one-half cycle of power-follow current.
circuit, which usually results in the blowing of a fuse, Although the gap breakdown voltage of the protector
either at the transformer, or at a sectionalizing point on tube is higher than that of a correspdnding valve-type
the line. The gap spacings associated with low operating lightning arrester, particularly at short time lags, the tube
voltages are necessarily low so that unless the gap is adequately protects modern distribution transformers
enclosed ‘or protected, numerous flashovers can occur as rated 13 800 volts and below if connected properly.
a result of birds or foreign objects bridging the gap. Laboratory tests and operating experience have demo*-
Double gaps of various constructions are sometimes used strated the ability of a tube to discharge severe strokes of
to minimize this trouble. Since distribution transformers lightning. This characteristic together with its ability to
i “.
L’
‘.$&
.z-,
;..,
: y&p&
Chapter 18 Insulation Coordination 637

high crest magnitude. More recent data obtained with


the fulchronograph have shown that the distribution-type
arrester should also be capable of discharging surge cur-
rents of long duration.
Valve-type lightning arresters are now available that
mill handle either surges of high crest magnitude or long
duration.
Surge-Proof and CSP Transformers--The merge-
proof distribution transformer, containing, as a part of
the transformer, devices for complete surge protection,
was introduced in 1932. An expulsion tube arrester, known
as the De-ion arrester was connected between each pri-
mary terminal and tank. These arresters and the coordi-
nated low-voltage bushings of these transformers together
provided the three-point method of surge protection which
for the first time gave the means for completely protecting
IO all three major insulations.
These surge-proof transformers still required external
0 fuse cutouts to disconnect the transformer from the line in
0.2 0.4 0.6 0.0 1.0 1.2 1.4 1.6 I.0 2.0
case of secondary overload or short circuit or internal
MICROSECONDS TO BREAKDOWN
failure. Blowing of these fuses and somet,imes failure of
Fig. 42-Gap breakdown characteristics of typical distribu-
tion type arresters for 11/2 x 40 microsecond voltage wave. I DEION GAPS I

withstand high momentary system voltage makes it


especially well suited for application on rural circuits.
Conventional Valve-Type Lightning Arresters-
The valve-type lightning arrester is the device most gen-
erally used for the protection of conventional distribution
transformers, that is, transformers requiring separately
mounted protective devices. The curves of Fig. 42 and
Fig. 43, show respectively the gap breakdown charac-
teristics and the discharge characteristics of typical mod-
ern distribution-type arresters.
Operating experience of several years has demonstrated
the ability of conventional valve-type arresters to provide
a high degree of protection to distribution transformers.
BREAKER
Modern construction has eliminated the mechanical diffi-
culties experienced with early designs, which resulted in a
relatively high failure rate and occasional radio-inter-
ference complaints. Field measurements of surge-crest COORDINATED
magnitudes together with laboratory tests led to later BUSHING GAP
designs having the ability to discharge surge currents of Fig. 44-Circuit diagram of CSP transformer.

100 If practice is to ground tanks, remove tank discharge gap and con-
nect tank directly to ground.

60
the cutout constituted a large share of the trouble expe-
c-
8 50
rienced with distribution transformers caused by lightning
LY surges. Fuses cannot always be depended on to give ade-
‘: 40
._ quate overload and short-circuit protection. Also, the
mounting of cutouts necessarily adds to the cost and com-
plication of installation of the transformer.
The completely self-protecting (CSP) distribution trans-
former, introduced in 1933, overcame these difficulties.
Like its predecessor, it contained complete lightning pro-
tection, provided by high-voltage De-ion arresters and low-
voltage coordinated bushings arranged to give three-point
‘Yooo 2000 3000 5000 10000 20000 protection, as shown in the circuit diagram of Fig. 44.
AMPERES In addition, an internal circuit breaker connected be-
Fig. 43-Discharge voltage characteristics of typical distribu- tween the low-voltage windings and low-voltage terminals
tion type arresters for 10 x 20 microsecond current wave. protected the transformer against overload or secondary
638 Insulation Coordination Chapter 18

breakers instead of one. These are intercon-


nected within the transformer so as to section-
alize the low-voltage circuits in case of faults
or overloads.
The CSP transformer is completely assem-
bled in the factory thus making it possible to
surge test the combined transformer and pro-
tectivc equipment. Proof of coordination of the
insulation of each CSP transformer is now
given by applying to each assembled unit 8
surge test equivalent to a direct stroke of
lightning?“.

PR VII. SURGE PROTECTION FOR


ROTATING MACHINES
The insulation on the windings of rotating
.EYEL machines, such as large or small motors, a-c
generators, and synchronous condensers, is held
to a minimum because of limited space. Also,
since the insulation is not immersed in oil, its
surge strength is not much greater than the
peak of the 60-cycle voltage breakdown. Special
measures are, therefore, necessary to protect
such equipment when it is connected to a sys-
Fig. 45-Sectional view of CSP transformer for operation on tem subject to the hazards of lightning-surge
grounded-neutral circuit. - voltages. Likewise, the method of grounding
effects the overvoltages, during fault con-
short circuits. Finally, protection to the high-voltage ditions and switching, which may be impressed on rotat-
feeders from internal transformer failures was given by ing machines; these phenomena are discussed in Chapters
internal protective links connected between the high- 14 and 19.
voltage winding and bushing. The internal breaker and The stress on the major insulation of any machine, that
protective links perform all of the functions of the fuse, so is, the insulation between the winding and frame, is de-
that with these transformers no external protective de- termined mainly by the magnitude of the surge voltage
vices are required. Those transformers have now almost to ground, whereas the stress on the turn insulation is
entirely superseded the surge-proof design. more a function of the rate of rise of surge voltage as the
The bimetallic tripping element of the breaker, which surge penetrates the winding21’22. Protection of a rotat-
is actuated by both load current and oil temperature, is ing machine, therefore, requires limiting the surge voltage
calibrated to follow closely the permissible thermal load- magnitude at the machine terminals and sloping the wave
time charact,cristics of the transformer windings and pro- front of the incoming surge.
vides loading on the basis of copper temperature. The effect of sloping the wave front is illustrated in
A sectional view of a CSP transformer with two cover Fig. 46. The curves of Fig. 46 (a) show the relative volt-
bushings and De-ion arresters is illustrated in Fig. 45. Of
special interest is the emergency control now supplied on
these transformers. This device takes care of the occa-
sional situation where the breaker cannot be kept closed 3 6 GROUND
after having been tripped by overload, because the over- ‘2
HALF-MICROSECOND WAVE ‘.‘. TWELVE-MICROSECOND WAVE
load persists or motor starting currents are high. If it is 0 120
imperative that service be restored, even at the risk of s= 100
some loss of transformer life, the breaker setting may be
w so
elevated by means of the external emergency control
handle to permit additional overloads. The necessity for E 60
w
the use of this device usually indicates that the load growth z 40
has exceeded the capacity of the transformer so that the
2 20
unit should be replaced as soon as possible by a larger one.
Recent developments include the extension of the CSP 4 8 12 16
principle to include three-phase dishribution transformers (a) MICROSECONDS (b)
and both single- and three-phase completely self-protect-
ing transformers for banked secondary operation (CSPB’s). Fig. 46-Distribution of surge voltage in generator winding-
The latter contain all of the protective features of the CSP (a) Without rotating machine protection.
transformers, and, in addition, they are supplied with two (b) With rotating machine protection.
Chapter 18 Insulation Coordination 639

ages to ground of the line terminal and two intermediate frame. Where more than one machine is connected to a
points in a phase xvinding of a machine without protec- common bus, one arrester connected between each phase
tion for an incoming surge rising to crest in one-half micro- of the bus and ground generally is adequate if the machine
second. The diffcrcnces in voltages at the various points frames are connected to a low-resistance ground common
in the lvinding result in high stresses betlveen turns. lvith the arrester ground.
The curves of Fig. 46 (b) show horn the stresses betlveen Sloping of the surge leave front is accomplished by let-
turns are decreased by sloping the lvave front so that the ting the surge, after passing through a series impedance,
singe at the machine terminals reaches crest in ttvelve charge a shunt capacitor connected to the machine ter-
microseconds. minals.
Limiting the surge voltage to ground sufficiently to
protect the major insulation usually requires a special 18. Line Surge Impedance and Capacitor Method
lightning arrester, having a low protective ratio, con- In this scheme of protection, a special arrester is in-
nected between each machine terminal and grounded stalled at the machine terminal to limit the magnitude
of the voltage impressed on its windings. The sloping of
the surge is accomplished by a capacitor charged through
the surge impedance and reactance of the line. See Fig.
47. To limit the voltage that determines the charging
ROTATING
rate of the capacitor, a lightning arrester or protector tube
MACHINE
1 T is placed on each overhead line far enough ahead of the
1 STANDARD
LINE TYPE
I SPECIAL 1 CAPA-
machine SO that the arrester will discharge before the
1 ARRESTER T CITOR voltage impressed on it is modified by reflections from the
ARRESTER
1
I capacitor. This distance Ivill depend upon the slope of
17 INSTALLED
--L AT MACHINE F
the incoming surge. The farther out the arrester is located,
TERMINALS OR BUS the less lvill be the stress on the machine jvinding for
(a) surges originating beyond the arrester, but the greater will
t---oVERHEAoGROUNDWIRES(IFUSED)---l be the possibility of a surge originating betn-een the line
I IEUS ! arrester and the station. A distance of 1500 to ZOO0 feet
is a good compromise between the possibilities of a stroke
lvithin this area and the effect of distance on the charging
CAPACITOR -’
rate of the capacitor.
MACHINES
1 *STANDARD The rate of rise of the surge reaching the machine is
SPECIAL #I -8
LINE TYPE
ARRESTER ) ;;
also a function of the amount of capacitance used. The
I
maximum permissible rate of rise depends upon the ve-
I J locity of propagation of the surge in the machine winding,
h-1500 FT -----4 the number of turns per coil, the turn length and the turn
? (b) insulation. A study of many cases has indicated that the
maximum rate of rise should be limited to a value such
-------------_----- that, if the terminal voltage continues to rise, it lvill not
T OVERHEAD GROUND WIRE (IF USED)
ROTATING;
I equal the test voltage of the machine in less than 10 micro-
seconds. Considering a minimum practical line surge
impedance and a practical machine surge impedance, this
requires at least a microfarad of capacitance. It is inde-
pendent of rated circuit voltage because the machine test
voltage and the voltage limited by the line arrester are
+ 1500 FT--/ I proportional to rated circuit voltage. Horvever, in the
construction of capacitors there is a limit to the minimum
Fig. 47-Line surge impedance and capacitor method of pro- capacitance that can be obtained economically on a
tecting rotating machines. standard unit. For example, the standard G900-volt unit
contains 4 microfarad, whereas the 13 SOO-volt unit con-
(a) Single machine connect&l to overhead line.
tains only 4 microfarad.
(b) Two or more machines connected to common bus.
(c) Machine connected through short cable to overhead lines. In an ungrounded machine, because of the possibility of
For simplicity, protective devices are shown on one phase only. reflections from the neutral point, the voltage may double
Each phase however must have the same protective apparatus in- at the neutral. To limit the voltage at the neutral as
stalled. recommended, it is necessary to hold the rate of rise of the
*For circuits below 2300 volts. surge entering the machines to 4 the recommended value,
**For circuits 2300 volts and above. by using at least 3, instead of 4 microfarad. In Table 9
***Cable lengths up to 1000 feet are considered short cables in this are given the recommended capacitances for various volt-
type of application. If the cable is over 2500 feet long and the ma- age classes from 650 to 13 800 volts. For 11 500 and
chine is connected directly to it, it is satisfactory to omit the capaci- 13 SOO-volt classes, two standard a-microfarad units are
tor at machine terminals. In this case the capacity effect of the cable recommended for ungrounded machines, whereas 4 micro-
is approximately equivalent to the capacitor. farad is sufficient for a grounded machine. Below 11 500
640 Insulation Coordination

TABLE ~-RECOMMENDED CAPACITANCE VALUES FOR LINE 19. Choke Coil and Capacitor Method
SURGE IMPEDANCE METHOD OF PROTECTING ROTATING MACHINES
The most complete protection of rotating machines
connected directly to overhead lines is obtained when
ILIachine* Number of Microfarnds
Circuit lightning arresters are used to limit the magnitude of the
Neutral Standard Units in Each
Voltage incoming surge, and lumped inductance and capacitance
Connection per Phase Standard knit
are used to limit the slope of the incoming surge. With
660 any 2 this scheme of protection, the machine is given full pro-
2400 any 0.5 tection for all surges, even for direct strokes to the over-
4160 any 0.5 head line close to the station.
4800 any 0.5 Special lightning arresters are paralleled with the re-
6900 any 05
quired amount of capacitance and tied to the generator
11 500 Grounded 0 25
terminals or station bus. See Fig. 48. A standard arrester
11 500 Ungrounded 0 25 is applied on the line side of the choke coil to limit the
13 800 Grounded 0 25
13 800 Ungrounded 0.25

*Machine neutral considered grounded if grounded through a. resistor of 50 ohms


or less. Reactnnce grounded lnechines should be considered ungrounded.
I
CHOKE COIL
MACHINE
i
I
volts, the standard unit contains $ microfarad so no in-
crease is rcquircd for ungrounded machines. In some I
applications it may be expedient to use an arrester from
J
the neutral point of the machine to ground.
For all machines larger than 1000 kva, special station Fig. &b--Choke coil and capacitor method of protecting rotat-
type arresters should be used at the generator terminals. ing machines.
For machines of less than 1000 kva station type arresters
may not be justified economically. Special line-type ar- voltage that determines the charging rate of the capacitor.
resters can be used. The rate of rise of the terminal voltage depends upon both
In all cases, standard line-type arresters or protettor the amount of inductance and amount of capacitance
tubes are placed out on every overhead line entering the used. The values that should be used to limit the rate of
station at generator voltage. For 2300-volt circuits and rise to the maximum permissible value are given in Table
above, these arresters should be located approximately 10. A study has shown that the minimum capacitance
1500 feet from the station. For voltages below 600 volts, to use in conjunction with a 175-microhenry choke is 4
these arresters can be located within 500 feet of the station.
The possibility of a lightning stroke to the line near the TABLE lo-RECOMMENDED CAPACITANCE VALUES FOR CHOKE
station can be minimized by overhead ground wires placed COIL AND CAPACITOR METHOD OF PROTECTING ROTATING
MACHINES
over this part of the line as indicated in Fig. 47 (b). Their -
spacing and location, with respect to the phase wires, is
<umber of Standard Capacitors
important and the application requires special study. Circuit
Machine*
per Phase
There is a limit, however, to what can be done with ground Voltage
Neutral - -
wires. It should be stressed that the lightning strokes Connection
175 ph Choke 350uh Choke
terminating on low-voltage circuits are just as severe as -
those terminating on high-voltage circuits. Therefore, to 650 any 1 ..
get good protection with overhead ground wires, the
equivalent of a high-voltage line, with large spacing and 2400 Grounded 1 ..
2400 Ungrounded 2 1
increased surge insulation from line wires to ground con-
ductors should be used for the first 1500 or 2000 feet from 4160 Grounded 1 ..
the station. Properly applied ground wires then are ex- 4160 Ungrounded 2 1
pensive on low-voltage circuits, especially if considerable
money has to be spent to decrease the ground resistance. 4800 Grounded 1 ..
In many cases, it is more economical to use the choke-coil 4800 Ungrounded 2 2
scheme of surge protection.
If the machine is connected to the overhead line through 6900 Grounded 1 . .
1
a short cable, Fig. 47 (c), the protection at the machine 6900 Ungrounded 2 1

should be the same as discussed above. In addition there


11 500 Grounded 2 1
should be a set of line-type arresters on the line 1500 to 11 500 Ungrounded 4 2
2000 feet from the cable pothead and another set at the
cable potheLd. If several cables are connected to the bus 13 800 Grounded 2
or machine and their total length exceeds 2500 feet the 13 800 Ungrounded 4
cable capacity acts to slope the wave front, and the capac- -
*Machine neutral considered wounded if grounded through a resistor of 50 ohm
itor can be omitted at the machine. or less. Reactance grounded machines should be considered ungrounded.
Chapter 18 Insulation Coordination 641

microfarad for grounded machines. If the inductance is minnl of the machine. A standard light,ning arrester is,
increased to 350 microhenries, t microfarad would be of course, required on the line side of the transformer to
sufficient. protect the transformer. See Fig. 49.
For all machines above 1000 kva, special station-type When the machine is connected to an overhead line
arresters should be used at the generator terminals- both direct and through transformers, the special arrest-
lvhereas below 1000 kva special line type arresters can be ers and capacitors should be applied at each machine
used. In all cases, standard line or station-type arresters terminal the same as when the machine is connected to
are located on the line side of the choke coil. Station-type the overhead line only. Standard line-type arresters
arresters are recommended, but, where it is not felt that should be located from 1500 to 2000 feet out on the direct-
they can be justified, line-type arresters can be used; the connected line. Standard station type arresters should
degree of protection expected will dictate the arrester be installed on the high side of the transformer. See Fig.
to use. 50.
This scheme is more expensive, but, gives decidedly
more reliable protection because the area close to the sta- 21. Machines Connected to Overhead Lines
tion is fully protected. Through Feeder Regulators or Current Limit-
ing Reactors
20. Machines Connected to Overhead Lines If the machine is connected to the overhead line through
Through Transformers a feeder regulator or current limiting reactor, the protec-
Esperience with machines connected to overhead lines tion should be the same as for a machine directly con-
through transformers has indicated that damage to the nected to the overhead line. In addition, a standard line-
machines from lightning surges on the overhead lines is T-------------RoTA.NJ
rare if adequate arrester protection is provided on the OVERHEAD GROUND WIRE (IF USED)
high-voltage side of the transformer. However, surges I
MACHINE 1
REACTOR OR REGULATOR
coming in over an overhead line may produce high volt- I
ages on the low-voltage side of the transformer, even if I
STANDARD I
; A LINE TYPE
ARRESTER -- CITOR
L ARRESTERS .; -1
1500 F 4 7
I-
F
Fig. Jl-Protection of rotating machines connected through
current limiting reactor or feeder voltage regulator to over-
head lines.
(A reactor, when present, is equivalent approximately to the effect
of using a choke coil. Arrester A may be omitted if the current
Fig. 49-Protection of rotating machines connected through
power transformers to overhead lines. limiting reactor has an inductance of over 350 microhenries.)

the high side is adequately protected with arresters. The type arrester should be added on the line side of the regu-
surge is transmitted through the transformer by both lator or reactor. See Fig. 51.
electrostatic and electromagnetic coupling. The electro- If the inductance of the current limiting reactor is
static coupling depends upon the transformer capacitances greater than 350 microhenries, the arrester on the line
between windings and to ground, and is independent of can be omitted.
reactance and turns ratio. The electromagnetic coupling
depends upon the turns ratio, reactance and size of the 22. Characteristics of Special Lightning Arresters
transformer, as well as the bank connection, that is, Special low-breakdown lightning arresters for connec-
whether star-delta, star-star, etc. tion in parallel with capacitors at the machine terminals
Where additional protection to the rotating equipment (or at the bus if two or more machines are connected to a
is desired, it can be obtained by connecting a special ar- common bus) are available in either the station type or
rester and one standard capacitor unit to each phase ter- line type. The characteristics of typical arresters of both
T ----- ---- ----- - ---‘, types are shown in Table 11. The station type arresters
OVERHEAD GROUND WIRE (IF USED)
have a somewhat lower breakdown voltage, a lower dis-
POWER TRANSFORMER I
! 2c ROTATING i charge voltage at high surge currents, and a higher surge-
current discharge capacity.
For the best protection, station-type arresters should
be applied to machines of all ratings. However, it is
recognized that applications involving small sized ma-
chines may not economically justify the most expensive
protection. For that reason, line-type arresters are gen-
;$ix%
- -I
SP/ECIAL
ARRESTER erally applied on machines 1000 kva and below, and
-ARRESTER a station-type arresters on machines larger than 1000 kva.
Fig. JO-Protection of rotating machines connected direct to Either arrester must be applied on the basis that the
and through transformers to overhead lines. power voltage from line to ground across the arrester
642 Insulation Coordination Chapter 18

TABLE 11 -PERFORMANCE CHARACTERISTICS OF SPECIAL LIGHT- 5. Flashovcr Voltages of Insulators and Gaps, A.I.E.E. Subcorn-
NING ARRESTERS FOR SURGE PROTECTION OF ROTATING mittee Report, A.I.E.E. Transactions, Vol. 53, page 882.
MACHINES 6. Flashover Characteristics of Insulation, P. H. McAulcy, El,,,-
tric Journal, July 1938.
Gap Breakdown 7. Protection of Power Transformers Against I,ightning Surges,
A.I.E.E. Committee on Electrical hfachinery, Transformer Sub-
Front of committee, Technical Paper 41-79.
Discharge
Wave Wave 8. Report on Apparatus Bushings, A.T.E.E. Joint Committee on
Voltage Voltages
3rcakdown Front of Bushings, Technical Paper 41-76.
Type Rating on 10X20
60 Cycle of Stand- 10 Micro- 9. The Control Gap for Lightning Protcrtion, Ralph Higgins and
Kv Itms ps wave
ICv Rms ard AIDE seconds to H. L. Rorden, A.I.E.E. Transactions, 1936, page 1029.
1500 Amp
Rntc of 3reakdown 10. Line Type Lightning Arrester Performance Characteristics,
Rise, Iiv Crest* A.I.E.E. Lightning Arrester Subcommittee, Technical Paper
Kv crest 41-138.
11. Station-Type Lightning-Arrester Performance Characteristics,
12 9 9 A.I.E.E. Lightning Arrester Subcommittee, Electrical Engineer-
Special 22 17 18 ing, June 1940.
St ation 30 26 27 12. Selection of Lightning Arrester Ratings, R. D. Evans and Ed-
Typo 40 34 36 ward Beck, Westinghouse Engineer, February 1942.
50 42 45 13. A Traveling Wave Primer, Edward Beck, Electric Journal,
March 11132to October 1932 inclusive.
25 21 2.5
14. Transmission Tapped for Distribution by New Unit, George S,
34 30 34
Van Antwerp and H. S. Warford, Electrical World, 1938.
Special 14 9 9
15. Shielding of Substations, C. F. Wagner, G. D. 11cCann and
Line 25 18 18
C. M. Lear. A.Z.E.E. Transactions, Vol. 6 1.
Type 33 27 27
16. Lightning and Lightning Protection in Distribution Systems,
44 36 36
R. C. Bergvall and Edward Beck, A.I.E.E. Transactions, Vol. 59.
55 45 45
17. Distribution Transformer Lightning-Protection Practice, L. G.
Smith, A.Z.E.E. Transactions, Vol. 57.
18. Surge Proof Distribution Transformers, J. K. Hodnctte, E’lec-
tric Journal, February 1932.
under any normal or fault condition does not exceed the
19. Surge Protection for Distribution Transformers, J. K. Hodnettc,
arrester phase-leg rating. Electric Journal, March 1936.
20. Direct-Stroke Protection of Distribution Transformers, H. V.
VIII. SUMMARY Putman, Electric Journal, February 1937.
21. Protection of Rotating A. C. Machines Against Traveling Wave
The problem of coordinating the insulation of electrical Voltages Due to Lightning, W. J. Rudge, Jr., R. M. Wieseman
equipment has progressed through years of research from and W. W. Lewis, A.I.E.E. Transactions, Vol. 52.
a subject only vaguely underst.ood to a sound engineering 22. Surge Protection for Rotating Machines, J. F. Calvert, A. C.
practice based on well defined principles and known facts. blonteith, and E. Beck, Electric Journal, March 1933.
23. Application of Arresters and the Selection of Insulation Leiels,
Basic insulation levels have now been established that fix
.J. H. Foote and J. R. North, Electrical Engineering, June 1937.
the loiver limits of insulation surge strength to definite
24. Application of Station-Type Lightning Arresters, A. C. Mon-
values that can be demonstrated by standardized test teith and W. G. Roman, Electric Journal, March 1938.
methods. Protective devices are available that will pro- 25. The Insulator String, R. W. Sorensen, A.Z.E.E. Transactions,
vide a high degree of protection to insulation meeting the 1934, Vol. 53.
basic levels. Effective schemes have been devised for pro- 26. Failure of Disk Insulators on High Tension Transmission Sys-
tecting insulation that requires special consideration. tems, H. D. Panton, A.Z.E.E. Transactions, 1922, Vol. 41.
This progress was made possible only by cooperation 27. Transmission of Electric Power at Extra High Voltages, Philip
between the manufacturers and users of electrical equip- Sporn, A. C. Monteith, il.I.E.E. Transactions, Vol. 66, 1947.
ment in obtaining invaluable information on the nature 28. Corona Considerations on High-Voltage Lines and Design Fea-
of lightning and its effects on equipment in service. Con- tures of Tidd 500-kv Test Lines, C. F. Wagner, Anthony Wag-
ner, E. L. Peterson, I. W. Gross, A.Z.E.E. Transactions, vol. 66,
tinued cooperation will undoubtedly produce additional
1947.
information that will make possible further improve- 29. Transformers and Lightning Arresters-Tidd 500-kv Test Lines,
ments to the methods of coordinating insulation. F. A. Lane, J. K. Hodnctte, P. I,. Bellaschi, Edward Beck,
A.Z.E.E. Transactions, Vol. 66, 1947.
REFERENCES 30. Flashover Characteristics of Rod Gaps and Insulators, A.I.E.E.
1. Standard Basic Impulse Insulation Levels, A Report of the Committee. Electrical Engineering (A.I.E.E. Transactions),
Joint Committee on Coordination of Insulation A.I.E.E., E.E.I. Vol. 56, June 1937, pages 7 12- 14.
and x.E.hI.A. E.E.I. Publication So. H-8, N.E.M..4. Publica- 31. Lightning Performance of 200-kv Transmission Lines-II,
tion So. 109, A.I.E.E. Transaclions, 1941. A.I.E.E. Committee. A.I.E.E. Transactions, Vol. 65, 19‘%
2. A.I.E.E. Lightning Reference Book 1915-19.35. pages 70-5.
3. Coordination Session Toronto Convention 1930. Seven Papers 32. The Characteristics and Performance in Service of High-Voltage
A.I.E.E. Transactions 1930. Porcelain Insulators, J. S. Forrest, journal, Institution of Elec-
4. Recommendations for High-Voltage Testing, E.E.I.-N.E.M.A. trical Engineers (London, England), Vol. 89, part II, No. 7~ ,.
.,.i :
Subcommittee Report, A.I.E.E. Transactions, Vol. 59, page 598. February 1942, pages 60-80. :3:
CHAPTER 19

GROUNDING OF POWER SYSTEM NEUTRALS


Original Aulhor: Revised OIJ:
S. B. Griscom S. B. Griscom

T
HE m&hod of power-system grounding is perhaps that, while ungrounded operation is more hazardous to
more difficult to select than any other feature of equipment than, grounded, the degree of difference was
its design. The large number of factors that must somewhat masked by improvement in the apparatus itself
be considered is partly responsible, but primarily it is while changeovers to grounded operation were taking place.
because most of these factors cannot individually be set The first tendency in grounding was to limit the mnsi-
up in terms of dollars and cents, and thus weighed, one mum amount of fault current by means of neutral rc-
against the other, to get the best compromise between sistances. A number of empirical formulas were advnncetl
conflicting influences. , /‘.,,,.I.7 in an attempt to rationalize the procedure of determining
Historically, there has been a gradual tgend in Ameri- the maximum value of resistance that could be ~wcl.
can practice from ungrounded, to resistance grounded, to These formulas were variously expressed in terms of line
solid or effective grounded. The main reasons for these or cable lengths, charging current to ground, and some
trends can readily be traced. Most systems were initially involved the connected generating kva of the system.
operated with their neutrals free, that is, not connected to More recent investigations seem to confirm that the musi-
ground. This was the natural thing to do as the ground mum permissible neutral-grounding resistance is inversely
connection was not useful for the actual transfer of power. proportioned to the total line-to-ground charging kvn.
The method had a strong argument in its favor, since an However, it appears that other practical considerations,
insulator failure on one of the phases could be tolerated such as relaying, will dictate a lower maximum limit to
for some little time until the fault could be located and grounding resistance than the arcing phenomena woulcl
repairecl. Also most lines then were single circuit, and the require.
free-neutral feature permitted loads to be carried with On systems whose voltage is higher than generated volt-
fewer interruptions than had the neutral been grounded age, particularly 113 kv and above, a saving in system
and considerable fault current flowed. Another important cost became available by the use of transformers having
consideration was that relaying had not come into general the insulation graded from the line terminal to t,he neutral,
use, so that many prolonged outages were avoided by the if the neutral was solidly grounded. The cost of the ground-
ungrounded operation. ing resistor and the space required by it were also saved.
Limitations to ungrounded operation began to develop Consequently, the next major trend, particularly in the
with the growth of systems, both as to mileage and volt- transmission field, was toward solid or effective grounding.
age. This increased the currents when a ground occurred, For the higher voltages, this is now the most prevalent
so that an increasing proportion of transient grounds grounding procedure in the United States.
(from lightning, or momentary contacts) were no longer In individual locations on some systems, particularly
self-clearing. Furthermore, the phenomena of ‘(arcing in the vicinity of 69-kv nominal system voltage, instances
grounds” became prominent in the eyes of utility engi- have occurred where high concentrations of power have
neers. By arcing grounds was meant a process by which led to ground-fault currents so high as to be deemed ob;
alternate clearing and restriking of the arc caused recur- jectionable from the standpoint of conductor burningXnd i
ring high surge voltages. This phenomena proved quite inductive influence on communication circuits. In several
elusive and long defied conclusive confirmation, but the of these instances, neutral-grounding reactors of moderate
theory gained many adherents, so that by 1920 the ma- ohmic size have been used in the grounding of certain
jority of systems were grounded either solidly or through transformer banks.
resistance. Subsequently progress has been made in ana- In Europe, the last thirty years have seen considerable
lyzing this phenomena, and recently an accumulation has use of ground-fault neutralizers (Petersen coils). In many
been made of operating records of isolated-neutral systems. instances they have materially reduced outages caused
More recent transient-overvoltage comparisons between by ground faults. There are about 50 installations in this
isolated and grounded systems have shown the former to country, most of which were made in the last 15 years,
give higher overvoltages, both during faults and switching indicating an increasing interest.
operations, although not as high in magnitude as formerly
suspected. Furthermore the operating records of un- I. FUNDAMENTAL PRINCIPLES OF
grounded systems in recent years with proper surge pro- SYSTEM GROUNDING
tection and coordination of insulation do not show pro- 1. Ungrounded Systems
nouncedly greater equipment failure rates than on the A simple ungrounded-neutral system is shown in Fig.
grounded systems. It therefore appears logical to conclude 1 (a). The line conductors have capacitances between one
643
644 Grounding of Power System Neutrals Chapter 19

. c tral of the transformer bank is also at ground potential,


being held there by the balanced electrostatic capacitance
to ground. In a sense, the system is therefore capacitance
Ia grounded.
=’ b If one conductor, phase a for example, becomes faulted
to ground, there will no longer be any current flowing in
the capacity branch between that phase and ground, be-
cause the difference of potential no longer esists. How-
ever, the voltage across the other two capacity branches
will increase because the voltage across them rises to
phase-to-phase voltage. Moreover, as shown by Fig. 2 (b),
the voltages to ground are no longer 120 degrees out of
phase, but 60 degrees. Hence the sum of the currents is
no longer zero, but is three times the original current to
neutral. In phase position the current If flowing from the
a faulted conductor to ground, which is the usual conven-
tion, leads the original phase-to-neutral voltage by ap-
proximately 90 degrees.
The actual solution for voltages and currents is most
(bl conveniently carried out by means of the method of sym-
Fig. l--Simple ungrounded-neutral system. metrical components as given in Chap. 2. The current in
the faulted phase is then
another and to ground, as represented by the delta- and 3E,
star-connected sets of capacitances. The delta set of ca-
z1+z*+zll
pacitances has little influence on the grounding charac-
teristic of the system and will therefore thenceforth be dis- In this connection, two points are of interest. Z,, the
regarded. : i . zero-sequence impedance at the point of fault will, for an
In a perfectly transposed line, each phase conductor will ungrounded neutral system, be predominantly capacitive,
have the same capacitance to ground. With balanced whereas Z1 and Z2 are predominantly inductive. Conse-
three-phase voltage applied to the line, the current in each quently, the two tend somewhat to neutralize one another.
of the equivalent capacitances will be equal and displaced On long lines, this is particularly so, as Z1 and Z? increase
120 degrees from one nnothcr. The voltages across each with length, whereas ZO decreases. A further effect noted
branch are therefore equal and also displaced 120 degrees on long lines is that the zero-sequence charging currents
from one another. Consequently, there will be no potential for remote sections must be drawn through the series
difference between the neutral points of the supply trans- reactance of intervening sections, causing a zero-sequence
former bank and that of the capacitances. These vector voltage rise toward the far end. This can result in the
relations are shown by Fig. 1 (b). Since the neutral of the ground or “neutral” point lying outside of the triangle of
capacitances is at earth potential, it follows that the neu- line voltages as shown by Fig. 3. This situation is rarely

Fig. 3-Neutral displacement outside triangle of voltage on


long lines.

of importance unless the line lengths exceed about 200


miles. If the generating capacity is small, the additional
charging current caused by a ground fault may materially
increase the phase-to-phase voltages.
The electrostatic capacitances of each line to ground
were.assumed in the discussion above to be the same. This
will be substantially the case for a transposed line. With
untransposed lines this will not be true :,gartictlarly if the
configuration of the conductors is flat- or vertical. The
exact amount of unbalance can be calculated by determin-
b ing the capacity coefficients of the conductors.* In ex-
(b)
treme cases, the unbalance with either configuratioq may
Fig. 2-Ground fault on simple ungrounded-neutral system. “SeeChapter 3.
Chapter 19 Grounding of Power SzJsternNeutrals 645

give as much as five percent zero-sequence voltage. There- For this esample, &=3R+j8; Z,=O+j24; &=O+j2~.
fore, in practice, the system neutral on an ungrounded- The per unit fault current is given by the expression
neutral system may be displaced from ground as much as ~~=300/(3~+j~~).Thevoltagedevelopedacrosstheground-
five percent of the normal line-to-neutral voltage under ing resistor is I&. The power loss in the grounding resistor
unf:tulted conditions. This may not be objectionable, al- is IrER or Ir2R. If and ER are both in terms of normal
though sometimes interference may be caused with com- values per phase. The power loss obtained by their prod-
munication circuits. uct is therefore in terms of normal value per phase. Con-
seqcntly, if the power loss in the resistor is to be espressed
2. Resistance-Grounded Systems in terms of total three-phase system kva rating, it must
‘4 typical resistance-grounded neutral system is shown be divided by three. Thus resistor power loss in percent
in Fig. 1. As commonly installed, the resistance has a is Ir21Z/3, when If is in per unit and R in percent.
The maximum power loss for this case is 89.3 percent
of the system rated capacity if three times the resistance
in the neutral has the same ohmic magnitude as the resct-

A antes determining the ground-fault current. If the gen-


erator reactances are lower, still higher power mill occur
during grounds and may cause violent swinging of gen-
erator phase position or instability. Resistances in this
* region are to be avoided, and since there is always some
Fig. h-simple resistance-grounded system. additional resistance in the fault, it is preferable that the
grounding resistors alone be sufficient to carry well beyond
considerably higher ohmic magnitude than the system the peak.
reactance at the resistor location. Consecluently, the line-
to-ground fault current is primarily limited by the resistor 1000
itself. Other than in exceptional cases, such as long lines 800
at high voltage, or extensive cable systems, the capacitive
600
current is small compared to the resistive current, and
can be neglected.
An important consideration in resistance-grounded sys-
tems is the power loss in the resistor during line-to-ground
faults. The power loss is shown in Fig. 5 as a percentage

8
6

4
40 SO 120 160 200 240
NEUTRAL RESISTANCE-PERCENTON SYSTEM KVA
I I I
Fig. 5-Power loss in neutral resistor during line-to-ground 2 I --
faults. -

of the kva rating of the entire connected generating ca-


Pacity on the system, and as a function of the value of the ‘0 200.000 400,000 600,000 800,000 I~OO.000 l,200,000
neutral resistance. The latter is expressed in percent on KVA. RATING OF SYSTEM
the system kva. A generator reactance of 16 percent and Fig. 6-Effect of system size and operating voltage on size of
a transformer reactance of 8 percent were used in the neutral resistor to limit ground fault current to one-quarter
Preparation of the curve. full-load system current.
646 Orounding of Power System Neutrals

The actual ohmic value of the grounding resistor re- only, the positive- and negative-sequence reactances for
quired will vary widely depending upon the circuit volt- faults at station A are each 25+7 =32 percent, this being
age and system capacity. This effect is shown in Fig. 6, the sum of the generator and transformer reactances. The
which assumes arbitrarily that the ground-fault current
three-phase fault current is therefore %=3.12 times full-
is to be limited to M of full-load system current. By “full-
load system current” is meant the summation of the rated load current. The fault current for a single line-to-ground
currents of all generating capacity, converted to the volt- 300
age base of the line. In terms of the rated line currents, fault is = 4.23 times full-load current. The ratio
32+32+7
the fault currents may still be several times full load, de-
pending upon the number of lines. Fig. 6 is principally X0/X1 is &=0.219.
for illustrative purposes, and quite wide variations from
For a fault at station B, 80 miles away, the positive
the resistor ohms shown are satisfactory in practice. It
and negative-sequence reactances are increased by 34 per-
should be understood that the resistance value indicated
cent and the zero-sequence reactance by 120 percent, by
by Fig. 6 is the paralleled value of all resistors, if multiple
the transmission lines. The three-phase fault current is
grounding is used.
g= 1.51 times full load. The single-phase fault current
3. Effectively Grounded Systems
The term “effectively grounded” has replaced the older 300
is = 1.16 times full load. The ratio X,/X, ia
term “solidly grounded,” for reasons of definition. A 66+66+127
transformer neutral may be “solidly grounded” in that gc1.92.
there may be no impedance between the neutral and earth. I
However, the transformer capacity thus “solidly ground- The voltage of the sound or unfaulted phases can he
ed” may be too small in comparison with the size of the conveniently read from Chap. 14, Fig. 6. For a fault
system to be effective in stabilizing the voltages from at station A, where the ratio X,/X, is 0.219, Fig. 6
phases to ground, when ground faults occur. This is par- shows that the line-to-ground voltage is approximately
ticularly the case when small grounding transformers are 0.9 of normal line-to-neutral voltage (&/Xl is about
used to provide a source of ground current for relaying. 0.1 if there is no fault resistance). For a fault at station
The effect of different degrees of grounding is illustrated B, the corresponding ratio X0/X1 is 1.92 and the line-to-
in considerable detail in Chap. 14. From Fig. 5, Chap. 14, ground voltage on an unfaulted phase is about 1.15
the range of ground-fault currents is from 0 to 3.0 times times normal.
the three-phase short-circuit current. As shown in Fig. 6,
the line-to-ground voltage on an unfaulted phase ranges 4. Reactance-Grounded Systems
from about 0.6 to 2.0 times the normal line-to-neutral AIEE Standard No. 32-1.08 states:
voltage during a line-to-ground fault. These figures are “Reactance Grounded-Reactance grounded means
the rms dynamic quantities, as distinguished from transi- grounded through impedance, the principal element of
ent voltages or currents. which is reactance. (Modified from 35.15.215.) ,
These curves make it apparent that the term “solidly NOTE: The reactance may be inserted either directly, in the
grounded” is too indefinite to describe a grounding pro- connection to ground, or indirectly by increasing the reactance
cedure that varies over such a wide range. A designation of the ground return circuit. The latter may be done by in-
in terms of the ratio of zero sequence to positive sequence tentionally increasing the zero-sequencereactance of apparatus
reactance X,/X,, is much more logical and definite. connectedto ground, or by omitting some of the possible connec-
Section 32-1.05 of AIEE Standard No. 32, May 1947, tions from apparatus neutrals to ground.”
defines effective grounding as follows: As thus defined, “reactance grounded” implies the in-’
“A system or portion of a system can be said to be effectively sertion of a reactance in the ground connection. Within _j’
grounded when for all points on the system or specified portion this meaning a reactance-grounded system is not solidly
thereof the ratio of zero-sequencereactance to positive-sequence grounded; it may or may not be effectively grounded, and
reactanceis not greater than three and the ratio of zero-sequence it may or may not be resonant grounded. For the discus-
resistanceto positive-sequencereactance is not greater than one sions in this chapter, “reactance grounded” is defined in
for any condition of operation and for any amount of generator terms of X,/X, ratio, a system being reactance groundec!
capacity.” if X,/X, exceeds 3.0, but is less than the value necessa0’
An example of an effectively grounded system is shown for resonant grounding. Thus defined, ‘putting a low r~-
by Fig. 7. On the basis of generating capacity at station A actance between a generator or transformer neutral and
ground such that X,/X, remains less than 3.0 does not
X,=25% n & 80 MILES 69 KV
constitute reactance grounding. Similarly, if a grounding
X2=25% - A X,=34% 6 transformer has its neutral solidly grounded, but X0/X1
X,=120% exceeds 3.0, the system is presumed t’o be reactancqa,,pi c
WE-f= -4 grounded.
X,=7% The system of Fig. 7 can be converted to a Yeact
X2=7% grounded system if a reactor of sufficiently high reactan
X,=7% is connected between the transformer neutral and g
Fie. 7-Typical solidly grounded system. at station A. If a reactor having a 60-cycle reactance-
Chapter 19 Grounding of Power System Neutrals 647

16 ohms is used, this will be the equivalent of 8.4 percent


on 2.5000 kva. When multiplied by 3 (See Chap. 2) and
,dded to the transformer reactance of seven percent tho
sero-sequence reactance becomes equal to the positive-
and negative-sequence reactances. The current for a line-
to-ground fault at station A then becomes equal to that
for a three-phase fault. If therefore, the high ground-fault
current with transformers, solidly grounded had necessi-
tated circuit breakers with greater interrupting ability
than required for three-phase faults, the addition of the
(0) SYSTEM WITH NEUTRAL REACTOR
reactor would make the larger breakers unnecessary. AND NO CAPACITANCE TO GROUND
300
At station B, the ground fault current is 66+66+152
= 1.06 times full load. The ratio X0/X1 is ‘g=2.30.

From Chap. 14, Fig. 6, the maximum line-to-ground volt-


age on an unfaulted phase is about 1.18 times normal.
l’hus, the addition of a neutral reactor at a generating
station may equalize the three-phase and single-phase
short-circuit currents without greatly changing the mini-
mum line-to-ground fault current, or the voltage from
(b) SYSl ‘EM WITH FREE NEUTRAL
4
= 3.0

maximum phase to ground.


AND CAPACITANCE TO GROUND
The installation of such a nominal amount of reactance
is not sufficient to change the classification of the system
from effectively grounded to reactance grounded, inasmuch
3s excessive neutral displacements do not occur with
ground faults. This applies particularly in the vicinity of
station A, but to a lesser extent in the vicinity of station B.
If a 50-ohm neutral reactor is installed at station A, the
effective zero-sequence reactance at that point becomes
8GOj,. The ratio X,/X, at station A is then g= 2.7. At
(c) COMBINATION OF(a) AND(b)
station B the ratio X0/X1 is %!=3.1. Therefore on the
66 IF

basis of the AIEE definition cited above, the system would


he regarded as effectively grounded at station A but not
at station B. On the basis of the treatment in this chapter
the system of Fig. 7, with the 50-ohm grounding reactor
is considered reactance grounded.

5. Resonant-Grounded Systems
IF Ir
A resonant-grounded system is one in which the capaci- SYSTEM (a) SYSTEM (b) COMBINATION OF(a)B(b)
tance current is tuned or neutralized by a neutral reactor (d) VECTOR RELATIONS
or similar device. The principle of operation of the ground-
fault neutralizer is quite simple. As commonly used, the Fig. S-Illustration of operation of ground fault neutralizer
neutralizer is simply a tapped reactor connected between by principle of superposition.
a transformer neutral and ground. When one phase of the
system is grounded, a lagging reactive current flows from tain itself, and the fault is extinguished or “quenched.”
the
,* neutralizer through the transformer to the fault and This condition is shown in Fig. 8.
‘thence to ground. At the same time the capacitance cur- When extinguishing a ground fault, the combination of
rent will be flowing from line to ground (See Sec. 1). The neutralizer reactance and line capacitance constitutes a
lagging current from the reactor and the leading current parallel resonant circuit. This is brought out clearly by
from line capacitance are practically 180 degrees out of the zero-sequence diagram as shown by Fig. 9. In this
Phase and therefore the actual current to ground at the diagram XL is the neutralizer inductive reactance and XC
fault is equal to the difference between them. By properly the line capacitive reactance. “G” is an equivalent gen-
tuning the reactor (selecting the right tap) the two currents erator of zero-sequence voltage numerically equal to the
can be made almost exactly equal, so that their difference system line-to-neutral voltage and X the fault. With X
is substantially zero. Under this condition the current in closed, there will be a current circulating between Xo and
the fault is so small that in general the arc will not main- XL but no current through the fault X. If X be assumed
648 Grounding of Power System Neutrals Chapter 19

voltage, and X’o is the zero-sequence capacitive reactance


per phase.
The ground-fault neutralizer current rating is ma&
equal to or greater than the total system charging current
in a ground fault. A standard reference on methods of
calculating these currents is the Joint EEI Bell Telephone
Fig. 9--Zero-sequence reactance diagram of system with systems report Vol. IV, Reports 26-38 dated January
ground fault neutralizer showing parallel resonant circuit 1937. However, it has been found that all the method;
where zero-sequence voltage is created by fault to ground. available for calculating this current, invariably give lower
than the corresponding measured ones. For results that
to open, as by the extinguishment of the arc, the resonant are estimates, the data of Table 1 can be used:
combination of XL and Xo will continue to produce an
alternating voltage of about the same frequency and mag- TABLE 1 -GROUND FAULT NEUTRALIZER CURRENT PER
nitude as the original applied voltage from G. Conse- MILE OF SINGLE CIRCUIT OVERHEAD LINE
quently, the actual voltage across the arc is small when it Voltage-Kv Amperes
first extinguishes. This is a condition favorable to pre-
23 0.145
venting restriking. In other words, the successful extin-
34.5 0.20
guishing of ground faults by neutralizers results in part
46 0.26
from the low current and in part from the low voltage 69 0.39
appearing across the arc when it goes through a “current
zero.”
It is of interest to note that the ground-fault neutralizer For double-circuit lines on the same tower or poles, re-
also constitutes a series resonant circuit in case there are duce the particular line sections to equivalent single-circuit
any zero-sequence voltages on the system. In Sec. 1 on miles of overhead line by increasing the mileage by 1.3 for
Ungrounded Systems, reference was made to the fact that 34.5 kv and 1.6 for 69 kv lines.
with unsymmetrical line configurations a difference of For overhead ground wires, convert the particular lint
several percent may exist in the charging current to ground sections to equivalent single-circuit miles of overhead line
of the three phases, resulting in a residual voltage. A zero- by increasing the line mileage by 1.08 for one ground wire
sequence voltage created by line or transformer unbalances and 1.15 for two ground wires.
is the equivalent of an actual source of voltage between For cables, reduce sections to equivalent sections of
the system neutral and ground, as shown in Fig. 10. Here overhead lines by the following factors:
1 mile of three-conductor cable=25 miles of overhead
line.
1 mile of single-conductor cable = 50 miles of overhead
line.
The neutralizer selected should have a current rating
at least 20 percent in excess of the maximum total current *
obtained by using the above figures.
On lines shorter than 200 miles calculations made in the
Fig. IO-Zero-sequence reactance diagram of system with above manner will be well within the engineering accuracy
ground fault neutralizer showing series resonant circuit
where a zero-sequence voltage is created by unbalanced required. For longer lines, the zero-sequence inductive
capacitances to ground. reactance of the line should be considered, as it may have
some influence on the size of reactor required.
XC and XL are the same as in Fig. 9, but the generator G
equivalent to the zero-sequence voltage is now in series II. PRACTICAL CONSIDERATIONS IN
with the combination. The result of this connection is SYSTEM GROUNDING
that a relatively small zero-sequence voltage is capable of
producing a fairly high voltage across the reactor and ca- The broad objective in selecting a type of system ground-
pacitor. This, of course, causes the neutral to be con- ing is to secure the best compromise of the conflicting ad-
siderably displaced, perhaps 10 or 15 times the amount of vantages and disadvantages of the various methods. The.
the original zero-sequence voltage. This situation must be first column of Table 2 lists items affected by the method
watched in the application of ground-fault neutralizers, of grounding. The subsequent columns give in abbreviated
and if the fundamental frequency zero sequence voltage is form the attributes of the particular type of grounding,
in excess of about lyz percent, transposition of this line The following sections discuss the features of the different
will probably be necessary. methods of grounding in more detail.
Except for extremely long lines, the zero-sequence ca-
“pacitive reactance alone can be used to calculate the cur- 6. Ungrounded Systems
rent rating of the ground-fault neutralizer from the rela- The principal virtue of an ungrounded-neutral system
tion I,=$, where Ir is t,he fault-to-ground current when is its ability, in some cases, to clear ground faults without
0 interruption. The self-clearing feature disappears when
operated with neutral isolated, E, is the phase to neutral the length becomes appreciable. This effect is one d
iii*,
Chapter 19 Grounding of Power System Neutrals 649

TABLE 2
- -
A B G D E
Ungrounded 1Sffectively Grounded Reactance Grounded Resistance Grounded Resonant Grounded
.- .-
(1) Apparatus Irully Insulated 1Lowest Partially Graded Partially Graded Partially Graded
Insulation
(2) Fault to 1lTsually Low SIaximum value Zannot satisfactorily Low Negligil)le except when
Ground rarely higher than be reduced below Petcrscn coil is short
Current three-phase short one-half or one- circuited for relay pur-
circuit current third of values for poses when it may
solid grounding compare with solidly-
grounded systems

(3) Safety from 1Gsua!~ good, but not IZives greatest gradi- Slightly better than Better than effective Least gradient normally,
voltage fully dependable be- ents, but not usual- effective grounding. or reactance but may approach
gradient cause of possibility of ly a problem where grounded. effective grounding
considera- simultanrous fault on continuous ground valurs when necessary
tions another phase wires are used. to shunt ground fault
neutralizer to isolate
faulty circuit by re-
laying.

(4) Stability Usually unimportant Lower than with Improved over solid Improved over ef- Is eliminated from con-
other methods but grounding particu- fective grounding sideration during sin-
can be made satis- larly if used at re- particularly if used gle line-to-ground
factory by use of ceiving end of sys- at sending end of faults unless neu-
high speed relays tem system tralizer is short cir-
and circuit breaker! cuited to isolate fault
by relays

(5) Relaying Difficult ,Satisfactory Satisfactory Satisfactory Requires special provi-


sions but can be nrnde
satisfactory

(6) Arcing 1Likely Unlikely Possible if reactance Unlikely Unlikely


Grounds is excessive

(7) Localizing 1Effect of fault trans- Effect of faults local- Effect of faults local- Effect of faults trans- Effect of faults trans-
Faults mitted as excess volt- ized to system or ized to system or mitted as excess mitted as excess volt-
age on sound phases part of system part of system voltage on sound age on sound phases
to all parts of conduc- where they occur where they occur phases to all parts to all parts of conduc-
tively connected net- unless reactance is of conductively con tively connected net-
work quite high netted network work

(8) Double 1Likely Unlikely Unlikely unless re- Unlikely unless re- Seem to be more likely
Faults actance is quite sistance is quite but conclusive infor-
high and insulation high and insulation mation not available
wenk weak
(!J) Lightning IUngrounded neutral Highest efficiency an d If reactance is very Arresters for un- Ungrounded neutral
Protection service arresters must lowest cost high arresters for grounded, neutral service arresters must
be applied at sacrifice ungrounded neutral service usually mus be applied at sacrifice
in cost and efficiency service must be ap- be applied at sacri- in cost and efficiency
plied at sacrifice in fice in cost and
cost and efficiency efficiency

(10) Inductive IWill usually be low ex- 1Will be greatest in Will be reduced from Will be reduced from Will be low in magni-
Coordina- cept in cases of double magnitude due to solidly grounded solidly grounded tude except in cases of
tion faults or electrostatic higher fault cur- values values double faults or series
induction with neutral I rents but can be resonance at harmonic
displaced but duration quickly cleared par- frequencies, but dura-
may be great ticularly with high tion may be great
speed breakers

(11) Radio In- :May be quite high dur- IMinimum IGreater than for Greater than for May be high during
fluence ing faults or when solidly grounded, solidly grounded, faults
when faults occur when faults occur
- neutral is disulaced -
TABLE 2--Continued on Next Page
rt
650 Orounding of Power System Neutrals Chapter 19

TABLE 2-CONTINUED
- -
B c D I?
Ungrounded Xectively Grounded Reactance Grounded csistance Grounded Resonant Grounded
--
(12) Line Avail- Nil1 inherently clear SIust be isolated for Crust be isolated for Iust be isolated foi >iced not be isolatecd
ability themselves if total each fault each fault eachfault but will inherently
length of intercon- clear itself in about
nected lint is low and 60 to 80 percent of
require isolation from faults
system in increasing
percentages as length
becomes greater

(13) Adapta- >annot be intercon- jatisfactory indefi- Satisfactory indefi- atisfactory with ( :annot be intercon-
bility to nected unless inter- nitely with react- nitely with solidly- solidly- or reactance ,_ nected unless intcr-
Intercon- connecting system is ance-grounded sys- grounded systems grounded systems connected system is
nection ungrounded or isolat- tems with proper atten- resonant grounded or
ing transformers are tion to relaying isolating transformers
used arc used. Requires
coordination between
interconnected sys-
tems in neutraliscr
settings

(14) Circuit Ynterrupting capacity Same interrupting fnterrupting capacity ntcrrupting capacity i 1nterrupting capacity
Brcakcrs determined by three- capacity as required determined by three determined by three :- determined by thrcc-
phase fault conditions for three-phase shor phase fault condi- phase fault condi- phase fault conditions
circuit will prac- tions tions
tically always be
satisfactory

3rdinarily simple but Simple r


(15) Operating Simple imple Paps on neutralizers
Procedure possibility of double must be changed when
faults introduces corn. major system switch-
plication in times of ing is performed and
trouble difficulty may arise in
interconnected SYS-
terns. Difficult t,o tell
where faults are
located

(16) Total Cost Iigh, unless conditions Lowest Intermediate ntermediate 1Highest unless the arc
are such that arc tend .s suppressing character-
to extinguish itself, istic is relied on to
when duplicate cir- eliminate duplicate
cuits may be elimi- circuits when it may
nated, reducing total be lowest for the par-
cost ticular type of service
-

probability, but completely satisfactory results probably give sufficient fault current for relaying, then the self-
cannot be secured above 100 miles of 11-kv circuits or 25 clearing advantage is lost and the system might as well be
miles of 69-kv circuits. On total circuit lengths of this grounded in some manner.
order or lower the ungrounded-neutral systems will prob- The ungrounded-neutral system is not likely to cause
ably have fewer tripouts than any form of grounded sys- high voltages to be induced in neighboring communication
tem, and, where feeds are essentially single-circuit radial, circuits because the ground-fault currents are ordinarily
better service to customers can be rendered. 10~. However, on early designs or lines in a poor state of
Lightning arresters must be applied on the basis of full maintenance, this is not necessarily so, as the full displace
line-to-line voltage, which increases the expense of protec- ment of neutral accompanying a ground fault on one phase
tion and somewhat reduces their effectiveness. Selective is conducive to producing a fault on one of the other
relaying on ground faults is practically impossible for these phases, thus producing a double fault with earth currents
short line lengths so that the detection and isolation of comparable with systems of solidly grounded neutral.
faulty lines is likely to be quite long. In some instances, Furthermore, the influence on communication systems ia
for example with a line down, this circumstance may not alone a matter of current magnitude; it also involves
present a hazard to life. If the circuits are long enough to duration and wave form of the earth current. Because &,i.‘
-.%-*;
,,’,,
a$
Chapter 19 Grounding of Power System Neutrals 651

the absence of or ineffectiveness of ground relaying on un-


grounded systems, such faults will persist for some time.
,ilso, the arcing condition with the capacitance current is
productive of badly distorted wave forms, throwing a good
part of the energy into the higher frequencies where the
irrfhrence is greater. In several instances it has actually
l)ccn found true in practice that inductive influence has
l,ccn decreased following adoption of some form of ground-
ing, As a general statement therefore, ungrounded opera-
tion cannot be considered superior to grounded operation
from the inductive influence point of view. 0
\Vhile it is likely that the destructive effects of “arcing -
grounds” has been esaggcrnted in the past, all of the ac- Fig. 11-Low- or medium-voltage looped transmission system
cumulated opinion in this regard cannot be discarded. with single grounding point presents difficulties in relaying
&lore recent studies (See Chap. 14) also bear out the ground faults unless a neutral grounding resistor is employed.
higher “switching surges” existent on ungrounded-neutral
systems. It therefore seems necessary to assume that an neutral voltage. If a ground fault having a resistance of
lmgrounded-neutral system will result in more equipment 10 ohms occurs, the fault current will be reduced to 1320
damages and “unaccounted for” interruptions than some amperes, and the zero-sequence voltage to about 6.5 per-
form of grounded system. Transformers must be designed cent of the normal phase-to-neutral value. This voltage is
on the basis of full neutral displacement and in the higher insufficient for dependable directional ground relaying if
voltage classes this will result in a somewhat higher cost. fault resistances of 10 ohms and upward are encountered,
as they ordinarily will be unless the lines are on steel
7. Resistance-Grounded Systems towers, and connecting ground wires are used. In cases
Grounding through resistance immediately disposes of like this, impedance, preferably resistance, in the neutral
t\vo defects of the ungrounded system: it permits ready is necessary for satisfactory relaying. On a smaller system,
relaying of ground faults and it minimizes the hazard of where the maximum short-circuit current is much less than
arcing grounds. the esample given, there may always be sufficient residual
In general the grounding resistances used have limited voltage without the necessity of a neutral-impedance de-
the ground-fault current to a magnitude much less than vice. Furthermore, on simple radial systems where zero-
the three-phase short-circuit current. This is almost im- sequence voltage is not required for polarizing of direc-
perative in order to limit the power loss in the grounding tional relays, this factor need not be considered.
resistor to a reasonable figure as discussed in Sec. 2. How- A typical stainless steel grounding resistor is shown in
ever, the result is that the system neutral will almost in- Fig. 12.
variably be fully displaced in case of a ground fault, there-
by necessitating the use of full-rated lightning arresters at
an increase in cost and sacrifice in protective performance.
The latter is not particularly a handicap with modern ar-
resters and modern transformers, but it may be important
with older transformers having materially lower impulse
strength.
In certain instances, the use of grounding resistances
may improve the stability of a power system during ground
faults by replacing the power dropped, as a result of low
voltage, with an approximately equal power loss in the
resistor, thus reducing the advance in phase of the gen-
erators. This scheme was used on the lEGMile Falls de-
velopment of the New England Power Company.
In general, a resistance-grounded system will have ma-
terially lower ground-fault current than a solidly grounded
system and hence will have less inductive influence on
paralleling communication circuits. In some instances this
may be of considerable practical importance.
On systems of lower voltage, say up to and including 46
kv, ground relaying may play an important part in the
selection of a grounding procedure. Consider, for example,
the 22-kv system of Fig. 11 where the three-phase short-
circuit current at station A is 12 500 amperes and the line-
to-ground fault current with zero-fault resistance is 9700
amperes. The zero-sequence voltage at station A, if cal-
culated will be found to be about 48% of normal phase to Fig. 12-30-ohm stainless steel grounding resistor.
5,

652 Grounding of Power System Neutrals Chapter 19

8. Effectively Grounded Systems cepted standard, the criterion will here be taken in tew
In all voltage classes, effectively grounded systems are of the ratio, -. XII
A ratio of more than three requires the use
less expensive than any other type of grounding. This is X1
because “arresters for solidly grolmded neutral service” of full-rat,ed arresters, so the range between this point and
can he applied, and because no auxiliary grounding devices the reactance for ground-fault neutralizers should logically
in the form of resistors, reactors, neutralizers, etc., are be considered as reactance grounded.
ordinarily required. This statement implies either a new At points on the system where &/XL =3 or less, the
system, or an addition to a system. It may also apply to an ground-fault currents will be of the same order as those on
existingsystemifsufficientstar-connectedapparatusisavail- effectively grounded systems, and the same comments 88
able. On a system where only delta-connected transformers for effective grounding will apply except that the trans-
are available, any form of grounding of the existing system former insulation may need to be graded at the neutral
will involve extra expense. On systems 115 kv and above, end, if a neutral reactor is used.
additional savings are available because transformers for For neutral reuctances, the ground-fault currents de
solidly grounded neutral service can be purchased, with crease and the neutral displacements increase. The tran-
the insulation graded toward the neutral end, at less cost. sient overvoltages resulting from arcing increase as the
On an effectively grounded system all faults including reactance is increased, up to a reactance of about J$ that
grounds must be cleared by opening the line. (This is also required for ground-fault neutralizing, beyond which point
true of resistance- and reactance-grounded systems, and they again decrease, reaching another minimum at the
partly on ungrounded- and neutralized-grounded systems.) tuned reactance. Further increases in reactance again re-
Close to the grounding points, the ground-fault currents sult in higher voltages. During switching operations the
are high, in some cases exceeding the three-phase short- indications are that the higher the reactance, the higher
circuit currents. In a few instances higher interrupting the surge voltage to be expected. See Fig. 36 in Chap. 14.
capacity breakers may be required over that necessary for The general indication is that there is no merit in pur-
three-phase short-circuit interruption. The higher cur- posely increasing the grounding reactance of a system
rents also produce more conductor burning. The greater beyond that required to keep currents within nondestruc-
currents result in lower positive-sequence voltages with a tive range, except of course, for the special case of ground-
tendency toward a lower stability limit for line-to-ground fault neutralizers. Systems grounded through high-react-
faults. The higher earth currents may in some cases inter- ance are uncommon except where delta-connected un-
fere with communication circuits. grounded systems have been grounded by means of ground-
Most unfavorable influences from the above high-cur-
rent phenomena have largely been removed, so far as sys-
tem extensions are concerned, by the availability of the
newer high-speed relays and circuit breakers. These com-
ments apply particularly t,o such items as stability, con-
ductor burning and communication circuit influence. The
interrupting requirements of circuit breakers can be
brought to equality with that for the three-phase fault con-
dition by the addition of a moderate-sized grounding reac-
tor where necessary. When the reduction in current is no
more than this, the system will still retain the classification
of “effectively grounded,” although the transformers
grounded through reactance will require greater neutral
insulation, abut will not necessarily be fully insulated.
On grounded neutral systems, it is usual for the trans-
formers in generating stations to be connected delta on the
generator side and groudded star on the high voltage side.
Practice varies with regard to step-down transformers,
some being connected star and others delta on the high
voltage side. The latter is perhaps the more usual, par-
ticularly if the secondary transmission or distribution cir-
cuits are also grounded neutral. Systems laid out in this
manner are in some instances subject to abnormally high
voltages in the event of single conductor breaks in the line.
The same comment may be made with regard to fusing
and single pole switching. The circumstances required to
produce these abnormal voltages rarely occur, but the
phenomena warrants consideration. See reference 10.
9. Reactance-Grounded Systems
Reactance-grounding falls somewhere between effective
grounding and resonant grounding. In the lack of an ac- Fig. 13-Typical grounding transformer.
Chapter 19 Grounding of Power System Neutrals 653

ing transformers. Here, the element of expense has fre- reactance device. 11 typical connection diagram is shown
qucntly caused small grounding transformers to be used, in Fig. 15.
t,he principal object usually being to secure enough-~~~~ind The value of ground fault neutralizers to a system de-
ciirrent for relaying. pends upon its type and construction. If the system is
Grounding transformers are usually wound “zig-zag” predominantly of multi-circuit or loop-feed construction,
for economy. For temporary jobs, or where idle trans- the principal advantages are those resulting from small
formers are available, conventional star-delta transformers
TO NEUTRAL OF GROUNDING TRANSFORMER
are sometimes used. When this is done, care must be ex-
DISCONNECTING
crcised that the transformers are not burned out by exces- SWITCH D. C, CONTROL BUS
+
sive fault duration, as the current through the transformers / I I
during ground faults will usually be nearly the full short- f 1’ I
circuit value. A typical grounding transformer is shown
in Fig. 13. I r-1 TO GONG
I

10. Resonant-Grounded Systems


When a system is equipped with ground-fault neutral-
izers, the neutral is displaced over all parts conductively
tied together when a ground fault occurs. This means that
two phases are at full line-to-line voltage above ground.
Full-rated lightning arresters are therefore required. All
line switching must be coordinated centrally in order to
determine the proper neutralizer taps. Interconnected
systems must be included in this coordination, or else iso-
lated by two-winding transformer banks. An alternative \ I P ,
RES.

r
TO A.C. SUPPLY
zero-sequence isolating device is shown in Fig. 14. The RECORDING OF SAME RATING
principle of operation is that for three-phase currents AMMETER
AS RELAY
whose sum total is zero, the device presents only the leak- T
AUXILIARY SWITCH a =CLOSED WHEN BREAKER IS CLOSED.
age reactance of the windings whereas for zero-sequence Y ,I b-OPEN WHEN BREAKER IS CLOSED.
currents flowing in the same direction in each winding,
only the high magnetizing impedance is effective. +CONTACTS OPEN WHEN IN DE-ENERGIZED POSITION.
In general, the use of ground-fault neutralizers will de-
CONTACTS CLOSED WHEN IN DE-ENERGIZED POSITION.
crease the number of line interruptions from ground faults +
to 20 or 30 percent of those obtainable with some form of Fig. S-Method of short-circuiting ground fault neutralizer
after predetermined duration of ground-fault current.

ground currents-less likelihood of communication-circuit


interference, conductor burning and light flicker. In in-
dividual cases these favorable influences may be of value.
If the lines are predominantly of wood-pole construction
with high insulation to ground, a greater proportion of the
faults will be line-to-line and the neutralizer will therefore
not be so effective.
On systems having a large proportion of single-circuit
radial lines the value of neutralizers may be considerable.
In addition to the items mentioned above is the fact that
a large proportion of ground faults will be cleared without
Fig. lk-Zero-sequence isolator. The positive- and negative- line interruption. With radial feeds this is important, as
sequence reactance between a, b, c and a’, b’, and c’ are low, it may avoid construction of paralleling lines for service
but the zero-sequence reactance is high. continuity alone, and thus be productive of considerable
capital savings.
grounded operation. Complete effectiveness cannot be at- Ground-fault neutralizers cannot be used on systems
tained, because some faults will be caused by physical line where fully graded insulation transformers are in service,
damage and a proportion will fail to clear as a result of as these neutrals are not sufficiently well insulated. If line
other causes, such as improper tuning. Interruptions sectionalizing switches are used, they should be gang op-
caused by initial involvement of more than one phase are erated. Fuses should not be used in series with any ap-
Practically unchanged but the tendency of a single-phase preciable length of line. Ground-fault neutralizers should
ground fault developing into a two- or three-phase fault not be used on systems employing auto-transformers hav-
will be decreased. Ground relays must be retained to clear ing a greater ratio than 0.95 to 1.00.
those ground faults not extinguished by neutralizer action. Ten-minute time-rated ground-fault neutralizers are
They are brought into play after a predetermined duration used on systems on which permanent ground faults can
of ground-fault current by short-circuiting the neutral- be located and removed promptly either by ground relays
654 Grounding of Power System Neutrals

or other suitable means. Continuous time-rated ground- erally, this is quite eSpCnSiVe. .in altCrnatiVe procedure
fault neutralizers are used on all other systems. is to induce an equal and opposite voltage in the neutralized
It’o general rule on the number of neutralizers to use in system by means of reactors fed from current transformera ’ “. j,
a given application can be stated. A neutralizer in each in the delta windings. This entails. much engineering $1
section of the system that may become sectionalized during study and adjustments when placing in operation. Gen. *Ij
disturbances will give the utmost in protection and sim- erally, the best procedure is to avoid the condition bY not / v/
plicity of operation. The increased flexibility of operat>ion grollnding the other neutral point, and seeking other 10~~ ‘”
must be weighed against t,he increased cost for the larger tions for grounding the system.
number of neutralizers in making the final decision on
11. General Summary on Transmission System
what is to be undertaken.
Occasionally a situation arises wherein it is desired to Grounding
11cea ground-fault neutralizer in conjunction with a three- The preceding discussion brings out that the varioub
winding star-delta-star transformer bank. If the neutral- methods of grounding have their peculiar advantages and
izer is connected between one neutral point and ground, disadvantages so that individual circumstances can bc Bx-
and the other neutral point is solidly grounded, serious petted to decide the issue. Kcvertheless, a few combin*
overvoltages on the neutralizer grounded system may en- tions of conditions cover the great majority of systems,
sue, when a ground fault occurs on the solidly-grounded and some generalization is possible for these combinationa, : 1
sitlc of the transformer bank. In the vicinity of our larger cities and in industrialis@
Figure 16 illustrates in (a) the system connection, and areas, continuity of service is regarded as of such impal
in (lo) the equivalent zero-sequence impedance diagram. tance that multiple circuit lines and two direction feed

zA
are the rule. On such systems a momentary line trip01
does not interrupt service, because additional circuits ~1
available for the worse eventuality of physical damage t

c a line. These lines are usually relayed to clear a fault j


GROUND FAULT
NEUTRALIZER
LA from 0.15 to 0.5 seconds. They are usually tied in CQI
ductively with lines of the same voltage operated by ~01
tiguous companies. There is a large amount of equipmcl
tied to these lines, and lightning protection and confin
ment of trouble to a small area is desirable. For systen
13* KV I36 KV
of this character, effective grounding appears to bo tl
best practice. At some locations, ground fault currel
I3i KV limitation may be necessary from the standpoint of circrtlt
(0) breaker interrupting duty or inductive effects, but this can
probably be accomplished without exceeding a zero BP
GROUND FAULT quence ratio of three, thus permitting application of “Ii&G
NEUTRALIZER ning arresters for grounded neutral service.”
In less densely populated regions, the relation betwoon
loads and transmission distances is frequently such that
ZERO
ZERO SEQUENCE SEQUENCE
only single-circuit lines are justified. Systems of this @‘Pa
VOLTAGEPRODUCED -CAPACITANCE are good fields for the application of ground-fault nCUtr&
BY GROUND FAULT OF 33 KV izers. The number of interruptions can be greatly r&cod
ON 138 KV SYSTEMS SYSTEM at moderate cost by such means. While full-ra
ning arresters and transformers are required, t
of substations will usually be large enough that
not unduly increase the cost. Where only a fe
Fig. 16-(a) Hypothetical system using ground fault neutral- single-circuit radial, improvement of these lines b
izer with three-winding transformer. ning proofing” or the application of lightning Pro
(b) Zero sequence impedance diagram applying to (a). tubes may bc the most economical solution.
In some instances of long-distance poiver trans
Tn the latter, it will be noted that branch n of the t’rans- the overall cost can be decreased by using one trans
former equivalent circuit is common to both star connected circuit at a high voltage rather than two or more
circuits. A ground fault on the grounded neutral side at a lower voltage. Where other power sources ar
therefore causes a zero-sequence voltage to be applied to able when the line is out for maintenance or repair)
the neutralized system, The neutralizer inductive react- of the single-circuit line with ground-fault neu
ance and system zero sequence capacitance are in series becomes a feasible way of limiting the total inv
relationship to this voltage. Series resonance therefore oc- This method should be compared in cost and other
curs, and due to the high X/R ratio of neutralizers, the with the use of high-speed reclosing breakers.
applied voltage may be amplified ten or more times. The question of the number of grounding P&GM !8
When it is known that such usage is contemplated at the quently asked, On systems in the effectively gr
time of purchase of the transformer bank, it may be possi- class there is no reason why all available neutrals
ble to design it so that branch 72has zero impedance. Gen- not Lie grounded, so long as the ground-fault current
chapter 19 Grounding of Power System Neutrals 655

not require the application of breakers having larger inter- 71 KV AND UP SYSTEMS
rupting capacity. On resistance- or reactance-grounded
+tcms, or with . ground-fault neutralizers, each additional
groundmg pomt, mcrenses the total cost. In these cases,
tl,cbnumber of grounding points will largely be dictated
lly the ability to secure satisfactory ground relaying. On
otll(~r than radial systems, at least tn-o and preferably z
“,()rc grounding points are desirable to get most satisfac- ?
to,‘y tlirectionnl ground relaying. ?
ul
(‘irounding practice should be considered in the light of g
;,,provcmcnt in other branches of central-station work. +
l&ys and breakers have been improved so that they will E
clcar both phase and ground faults with a reliability and 8
nl,c(:~lgrcntly exceeding those obtainable a few years ago. k
C,)mpl:Lints from flicker, and unnecessary operation of
8-
l,J\v-voltage releases are correspondingly fewer. Automatic
l,;Kll-speed reclosin,(r is available for transmission service
llrltl :Jfords a means of avoiding outages from momentary
c:Lwcs from both phase and ground faults. Lightning
1925 1935 1945
proofin,(+ of transmission lines is markedly effective in re-
(1) UNGROUNDED
tlllc:ing the total number of f&hovers. In most instances
(2) GROUND-FAULT NEUTRALIZER
(IH:SCfactors will indicate a preference for the effectively (3) RESISTANCE
g~0w&xl system. A chart showing a comparison between (4) REACTANCE
t,Ilc various ground procccdurcs is given in Table 2.
Fig. ll-Relative United States use of grounding methods on
12.Trends and Practices in Transmission System transmission systems from 71 kv up.
Grounding
l’igures 17 and 18 are plotted from data obtained from use of grounding t,ransformers. In the majority of cases,
1,11cThird :1IEE Report on System Grounding.‘* The data “solid” grounding means that the systems are effectively
used in that report was collected by questionnaires, and grounded (X,/X, is three or less). Likewise, many of the
wwding to the definitions used, “solid” means that no “reactance” grounded systems are effectively grounded.
cst I’:L impedance is inserted between apparatus neutral For purpose of classification, a system is still considered
points and ground. “Reactance” grounded means that in “ungrounded”, if the only ground is through potential
sornc instance, neut)ral reactors are used on an otherwise transformers.
Holitlly-glounclcd system; in other instances, it means the Figure 17 shows the relative use of grounding methods
22 TO 70 KV SYSTEMS
on transmission and distribution systems in the voltage
range of 22 to 70 kv. There has been a steady decrease in
the ungrounded category, and an approximately like in-
crease in solid grounding. Ground-fault neutralizers are
being used to an increasing extent, although still a small
portion of the total. Their use in the United States is still
largely confined to single-circuit lines serving large areas.
Figure 18 is for systems 71 kv and up. These curves
show the dominant use of effective or solid grounding
in the United States. The majority of “reactance ground-
ed” systems are effectively grounded.

III. FUNDAMENTAL PRINCIPLES OF


GENERATOR GROUNDING
There are even more ramifications of generator ground-
ing than for transmission-system grounding. The many
possible combinations of connections between generators
and outgoing lines is responsible for this. The more com-
mon connections in use in generating stations are shown
in Figs. 19 to 23.
The so-called unit system, Fig. 19 is one in which each
“GROUND-FAULT NEUTRALIZER generator is directly connected to its individual trsns-
F’g* 17-Relative United States use of grounding methods on former bank, the low-voltage side being delta, and the
,trPnSmission and distribution systems in the voltage range of high-voltage side, star. So far as ground currents are
22 to 70 kv. concerned the machines are isolated from one another
656 Grounding of Power System Neutrals Chapter 19

and the high-voltage system. .A variation of this arrnnge-


ment is sometimes used where two generators supply a
common transformer bank. An arrangement using both
high- and low-voltage buses is given in Fig. 20. The in-
dividual machines are therefore tied, insofar as the flow
of ground current is concerned. Fig. 21 is for power

Fig. 19-Unit system-power transmitted at high voltage.

(b) IdI

7
Fig. 22-Power transmitted at generator voltage-four-wire
system.

Fig. 20-High- and low-voltage bus system-power trans-


mitted at high voltage.

12 KV
GENERATORS SYNCHRONIZING BUS
(0)

Fig. 21-Power transmitted at generator voltage-three-wire


system.

Q
T
distribution over a three-wire system at generator volt-
age. Fig. 22 is the same as Fig. 21 except the distribution
system is four-wire. A system where the generator voltage
is doubled or increased by & by auto-transformers for
distribution is shown in Fig. 23.
In generai the unit scheme of Pig. 19 gives the greatest
6 L I e
(d) (e)
freedom in the selection of a grounding procedure, while Fig. 23-Power transmitted at doub k generator voltage by
the other schemes place various restrictions on the choice. auto-transform e!rs.

c
Chapter 19 Grounding of Power System Neutrals 657

13. Ground Currents The three-phase fault current of an individual generatol


The ground-fault current for one phase of a three-phase
is s= 100 = 11.4 times full load. Consequently, in the
system is given by the expression x1 8.8
case illuskated, grounding only one generator will cause
I,= (zo+~l+zz) =z ,“z”g+,-.
0 1 ?
that generator to carry z or twice the current it would
If a generator is operating as i, is$ated machine, the
current so calculated will be the current through the have on a three-phase fault. Since mechanical stresses
faulted phase. If Zo is less than 21 or X, as is commonly are proportional to the square of the current, they would
the case, the ground-fault current mill be greater than be equal to four times the three-phase short-circuit
the three-phase fault current 2. If several machines stresses. ‘_‘,‘I’
1 The effect of different numbers of machines operating
are operated in parallel, and only one machine grounded, in parallel, with all neutrals fiunded, and with only one
this effect is accentuated in the grounded machine. machine grounded is illustrated in Fig. 25. These curves
For example, consider four generators operating in wcrc computed on the basis of X,=X? =8.8 percent and
parallel as shown in Fig. 24 (a). The reactances shown X0=2.2 percent, and for the machines paralleled directly
are in percent based on the individual machine ratings. at their terminals. It will be observed that the line-to-
ground fault current is always greater than the three-
phase fault current, and that the situation becomes pw-

L-2.2-l L-2.2-r L-2.2-4


POS. NEG. ZERO
(b)
Fig. 24-Single line-to-ground fault on four generators op-
erating in parallel with only one machine grounded.

The phase-sequence-reactance diagram is shown by Fig.


24 (b) from which ZO= 2.2; Zl= 2.2 and 2, = 2.2.
The sequence components for a line-to-ground fault
are
100
Io=Z,=I*= = 15.2 NUMBER OF MACHINES
2.2+2.2+2.2
Fig. 25-Total fault and machine currents for single line-to-
times full-load current of one generator. The total fault ground and three-phase faults.
current = lo+ll+Zz = 45.6 times full load of one generator. A-Current in any machine-three-phase fault.
The components of fault current through the grounded B-Current in one machine-single line-to-ground fault with all
machines grounded.
generator are :
C-Total current-three-phase fault.
I,,=10 = 15.2 times full load. D-Total current-single line-to-ground fault with all machines
I,, = $1, = 3.8 times full load. grounded.
I,, = $1, = 3.8 times full load. E-Current in grounded machine-sbgle line-to-ground fault with
only one machine grounded.
The fault current through the faulted phase of the F-Total current-single line-to-ground fault with only one ma-
grounded generator = I,O+lHl+l,B = 22.8 times full load. chine grounded.
658 Grounding of Power System Neutrals Chapter 19

titularly serious as the number of paralleled machines


increases. In an installation of this kind, some form of
neutral impedance device is a necessity.
In order to determine the size of neutral reactor to
limit the generator winding current for a single line-to-
ground fault to the generator winding current on a three-
phase fault the constants of the generator and the con-
stants of the system must be known. The system con-
stants must include all circuits and sources of supply to
the fault except t,he machine under consideration. Five
groups of formulas are listed below for single line-to-
ground faults depending upon the reactance values. Crroup Fig. 26-Two generators operating in parallel at generated
1 is perfectly general and the other groups are simplified. voltage.
e =percent generated voltage
Xa=percent rcactnnce of neutral reactor on generator culating harmonic currents. This is true whether the
kva base neutrals are interconnected or not. The two conditions
IR = percent reactor current based on normal generator necessary for the: flow of harmonic current are: the prcs-
current ence of a resultant harmonic voltage, and a path for the
flow of current. It is important to note the term “result-
Generator System
ant.” If the two machines are duplicates and are being
Pos. seq. reactance on gen. kva x’l 9
Al operated under identical conditions, they will probably
Seg. seq. reactance on gcn. kva X2 ss generate the same harmonics of about the same magni-
Zero seq. reactance on gen. kva Y
10 SO tude and phase position. If the harmonics are thus equal
Group 1. ,411reactance values finite and different. Xa= and opposite, there will be no resultant voltage available
s,(x,x~+2,Y~S~- Yys-J fXn(X,Sz - x32 - xzso - SOS?) to circulate harmonic current. If, ho\vever, the machines
3(xpso+x~S, - x&+&s?) are dissimilar, one may generate harmonic voltages that
the other does not. There will then be a circulating har-
300eXo monic current between them whose magnitude is equal
to the resultant harmonic voltage divided by the imped-
ance at the harmonic frequency. For line-to-line har-
monics the latter is approximately equal to the negative-
Group 2. &=infinite; others finite and different. Xa= sequence reactance in ohms at rated frequency times the
Y,-x,+s(x,-x)* 300e order of the harmonic. For two machines as illustrated,
IR=
3 3(X,+&) ’ the resultant reactance would be the sum gf the harmonic
g&+~+xo+3x,
reactances of the two machines, as they are in series for
harmonic-current flow. If more than two machines are in
Group 3. X1= Xt; others finite and different. XR=
parallel, but only one generating a high-harmonic volt-
age, the harmonic reactance of the one machine is added
in series with the paralleled reactance of the remaining
generators. If all machines are generating considerable
harmonic voltage, an analysis is almost impossible be-
Group /,. X1=X2; So= infinite; others finite and different, cause slight shifts in fundamental frequency phase posi-
x =x1-x0
1 tion with load will greatly alter the resultant harmonic
R -; IR+!? s
3 --EC+1 voltages.
* ( x,;s,+x,+s, 1 The situation with respect to neutral harmonics is
much similar to that for line harmonics except that on1Y
Group 5. X1 = Xs; S1= &; X0 = finite; So= infinite, triple series harmonics, 3rd, 9th, 15th, 21st, etc., can
x =x1-x0 300e ____
XI+SI flow in the neutral. This is because the 120 degrees rc-
R -; In=--
3 x1 ( x1+3& ) lationship of phases causes all other harmonics to be bal-
anced and thus total to zero in the three phases. Also
14. Neutral Displacement the zero sequence impedances apply rather than the
When a ground fault occurs, there is a tendency for a ,negative sequence. Referring again to Fig. 26, it is aP-
neutral shift with consequent change in voltage on the parent that neutral circulating harmonic currents cannot
unfaulted phases. The phenomenon is the same as dis- flow unless both neutral circuit breakers are closed.
cussed in Part I; and Fig. 6, Chap. 14, can be used to de- Then, if there is a resultant zero-sequence harmonic volt-
termine the voltage to which apparatus on the unfaulted age, a current will flow equal to the voltage divided by the
phases will be subjected. zero-sequence reactance at the harmonic frequency.
The harmonic currents circulating id the neutral are
15. Circulating Harmonic Currents likely to be somewhat higher in magnitu ii e than the line-
When two generators are operated in parallel at gener- to-line harmonic currents. -This is because the third bar-
ated voltage as in Fig. 26, there is the possibility of cir- manic voltage is usually higher than any other and .be
Chapter 19 Grounding of Power System Neutrals 659

cause the zero-sequence reactance is usually lower than grounding of the generators, removing the ground from a
the negative-sequence reactance. In the case of two- particular generator may correct the situation, but may
thirds pitch mnc’hines, the triple series (neutral) harmonics reqllire additional equipment to establish a ground to
\vill be practically zero, so that it will not create harmonic permit proper relaying. Ncrltral filters are sometimes
c!urrents. On the other hand, the zero-sequence renctnncc applicable.
of a two-thirds pitch machine is quite low so that it is a A detailed study of each situation is necessary to deter-
likely p:lth for the flow of triple harmonics generated by mine the best overall engineering solution. A further dis-
ot,her mnchincs. cussion of this question is given in Chap. 23.
Circulating harmonic currents between apparatus in a
st:tl.ion arc not particlllarly objectionable unless unusually 19. Mechanical Stress in Generator Winding
large. .I circrllnting neutral harmonic current of 3070 Paragraph 3.130 of ASA Standard C-SO Rotating Elec-
~o~&l offhand appear to bc of an order to be injurious trical Machinery, 1943 Edition, reads as follows:
to a machine. However, this means only 10 percent “A machine shall be cnpable of withstan(lin~ without injury
harmonic current per phase. The rms value in combina- the stressesof a lo-second, X-phaseshort circuit :it its terminals
tion with full-load current would be JlOO’f lo? = 100.5 when operated at rated kva, power fnctor and &percent overvolt-
percent. The heating effect will be somcwhnt greater age or any other lo-second short circuit provided the mnchine
than t.his, but probably not more than another x percent phase currents under the fault condition are limited by means of
suitable reactance or resistance to a value which does not exceetl
so that the loss of load-carrying capacit,y is inappreciable.
the maximum phase current obtained from t S-phase fault.”
16. Communication-Circuit Influence Reference to Sec. 12 shows that when XY,is less than SI,
Where generator neutrals are grounded and distribu- which is usually the case, some form of impedance is re-
tion is done at generated voltage, whatever residual har- quired in the generator neutral to permit grounded opera-
monics are present in the generator wave form are im- tion.
pressed on the lines. Residual harmonics are more likely
to cause inductive effect,s in nearby communication cir- 20. Transient Overvoltages
cuits than line-to-line harmonics because the return cir- This subject is treated in detail in Chap. 14. In any dis-
cuit is through the earth at a considerable depth. When cussion of this subject, it should he recognized that
the distribution circuits are in underground cables the numerous field tests have been made in an at,tempt to set
likelihood of inductive effects is small. On overhead lines, up and measure high transient voltages resulting from
however, consideration should be given to this question. phase-to-ground arcing faults in air. Generally speaking,
the overvoltages thus measured have been lower than those
17. Surge Protection indicated by pure theory, or by transient-analyzer studies,
This question is covered in detail in Chap. IS. It is and rarely exceeded three times the normal line-to-neutral
related to grounding methods in that ‘(grounded neutral crest. However, because of the random nature of arcs,
service” arresters can be applied if the system is effectively it is difficult to capture the maximum overvoltages, unless
grounded, whereas arresters rated at maximum line-to- numerous tests are made and high grade equipment such
line voltage are necessary if the system is not effectively as a cathode-ray oscillograph is used. Studies on the
grounded. transient analyzer are usually made by controlling the
Because of space limitations and costs, it is not prac- restriking of the arc to produce the maximum overvolt,age.
tical to insulate generators to the same impulse levels as Therefore, the results of transient-analyzer studies are of
oil-insulated apparatus of the same voltage class. There- more value in comparisons of methods of grounding, rather
fore, the protection margin is decreased for ungrounded, than in accurately predetermining magnitudes.
resistance-grounded and high-reactance-grounded genera- Switching operations may cause relatively high transient
tors. This situation has been helped to a degree by the overvoltages, if restriking occurs in the breaker. Accord-
use of “rotating machine” arresters. The experience so far ingly, in evaluating any method of grounding from the
indicates that full-rated arresters afford sufficient protec- viewpoint of transient voltages, it is well to consider
tion. Therefore, if other circumstances warrant the use of whether there will be switching at generator voltage either
a non-effectively grounded system, the matter of surge initially or some time in the future.
protection need not prohibit such use. Transient overvoltages due to switching have caused
electrical failure of equipment, circuit insulation, and
18. Inductive Coordination lightning arresters. Generally, lightning arresters are not
It is practically impossible to predetermine inductive considered as being applied for protection against such
coordination situations, because they arise from the inter- transient overvoltages, but evidence is available that
relation of three factors; inductive influence of the supply shows arresters have operated on transient overvoltages,
system, inductive susceptiveness of the communication thus protecting equipment. It is good practice to design
circuits, and the coupling between the two types of cir- the system and to ground it in such a manner, whenever
cuits. Therefore, remedial measures may involve reduc- possible, that transient voltages are below arrester break-
tion in the supply circuit influence, or in the susceptiveness down voltage.
of the communication circuits, or in the coupling between For generator grounding, it is commonly accepted that
the two; or in a combination of two or more of the above. transient overvoltages will be within acceptable limits if
When the remedial measures can best be applied to the the following conditions are met:
660 Grounding of Power System Neutrals Chapter 19

1. For application of generator neutral reactors, X,/Xi 23. Damage at Point of Fault
as determined at the machine terminals should be three or When a fault occurs within a generator, the affected
less. For purposes of this determination, X0 and Xi are coils must be replaced. While this is a large job, it is not
the resultant of the generator and system reactances, paral- nearly as serious as the problem of replacing damaged
leled. stator iron and restacking the laminations, should that be
2. For afiplication of generator-neutral resistances (or found necessary. Fortunately, such cases have been rare,
the equivalent through a grounding transformer), the cur- but they are nevertheless important. Laboratory studies
rent passed through the resistor during ground faults and field investigations of generator coil failures have been
should equal or exceed the capacitive current that would made with the view of determining the relation between
flow during a line-to-ground fault with the resistor dis- fault current, fault duration, and iron burning. So far,
connected. See Section 18 for a fuller discussion of this these investigations have been non-conclusive, although
point. The upper limit of current passed through a gen- service experience indicates that if the fault is cleared with
erator neutral resistor is fixed by the desire to avoid exces- standard differential relays and circuit breakers, the dam-
sive power loss, and is customarily held to 1M times full age will be limited to minor burning of the iron, which can
load generator current, or less. The ratio of Xo/Ro should be cleaned up without restacking. There is every indica-
preferably not exceed 1.0, including the reactance of the tion that low fault currents plus fast clearing, however,
resistor. Cast-iron grid resistors may have power factors minimizes fault damage.
of 0.98 and sometimes less, which means that their react- At present, the industry attitude seems to be tolerant of
ance may be about 20 percent of their resistance, at system moderate to high ground fault currents, where other condi-
frequency. tions require it, but to work toward low ground-fault cur-
rents, where conditions permit-this occurring mainly
21. Generator Relaying with the “unit system” of connection. The more con-
It is necessary to consider the effect of the generator servative attitude in the latter cases is to trip immediately,
grounding device on the operation of protective relays. even though the fault current be but a few amperes.
Most large generators arc provided with differential re-
lays. These are fully effective against phase-to-phase 24. Generator Neutral Breakers
faults within the machine. When the generator is effec- When a fault occurs within a generator, it is customary
tively grounded, the differential relays also give fairly ef- to trip the generator armature and field circuit breakers
fective protection against faults to ground. and shut off the input to the prime mover. These opera-
When the generator neutral is grounded through high tions do not necessarily stop the current through the fault,
impedance, the differential relays lose a considerable because a certain time is required for the generator field
amount of their effectiveness against ground faults. This flux to decay. If a generator neutral breaker is employed,
is particularly the case for ground faults near the neutral and it also is tripped on the incidence of a ground fault,
of the machine. It will usually be necessary to provide a the fault current immediately drops to a very low value
supplementary relay actuated by neutral or zero-sequence as determined by capacitance effects.
current when the machine is grounded through high im- In general, the smaller the ground-fault current (limited
pedance. by a neutral device), the less justification there is for an
automatic neutral circuit breaker.
22. Relaying of Feeders at Generator Voltage In some cases non-automatic neutral breakers or dis-
When power is distributed at generator voltage, it is connect switches are used. These are not operated during
necessary that the grounding method be selected giving faults, but are used to disconnect the neutral for safety or
consideration to that fact. The generator grounding de- operational reasons. Where several generators are con-
vice determines to a large extent the magnitude of the nected to a common neutral bus, which in turn connects
feeder line-to-ground fault current and thus the type and to a single neutral grounding device, these breakers or dis-
effectiveness of the feeder ground relays. There has been connect switches can be used to ground the desired gen-
some European use of grounding schemes that limit the erators to the neutral bus.
ground fault current to around 50 amperes. With feeders
having full-load currents of 600 amperes or more, fairly 25. Time Rating of Neutral Devices
sensitive ground relays are required. Such relays are avail- The following is Section 32-2.05 of AIEE Standard No.
able, but require more than usual care in selection of cur- 32 for Neutral Grounding Devices, dated May, 1947:
rent transformers, determination of settings, and main- “Rated Time-Standard rated time shall be 10 seconds,1 min-
tenance. While their use is, or probably can be made ute, 10 minutes and extended time.
practical, the more usual practice in the United States is “It shall be assumed, unless otherwise specified, that a one-
to select a grounding scheme that causes the ground fault minute rating is intended for neutral grounding devicesexcept for
current to equal or exceed full-load current on the feeders. ground-fault neutralizers and grounding transformers for use
With reactor or conventional reactor grounding, ade- with ground-fault neutralizers, for which a ten-minute rating is
quate current for relaying is readily obtained. Ungrounded assumed.”
operation, or the use of the transformer-resistor combina- When grounding reactors are used on th d unit-system*
tion are not suited for systems having’ feeders at gen- a lo-second rating is usually employed as this is consistent
erator voltage, as there is not sufficient current to permit with the thermal ability of the generator, and the opera-
ready selection of the faulted circuit. tion is non-repetitive.
Chapter 19 Grounding of Power System Neutrals 661

When grounding resistors, reactors, or grounding trans-


formers are used with systems having feeders at gcnerat,or
voltage, a one-minute rating is usually employed, thus al-
T-
T4 T
I
I
I 1
1
I

lowing for repetitive feeder faults and also for the fact that
the neutral device mlrst carry current whenever a ground
fault occurs on any of the three phases.
When the distribution-transformer-resistor scheme is
used, it has generally been the practice to apply extended
time ratings to the resistor. This is done primarily be-
cause of the small cost of the resistor, and partly because
of the possibility that time-delay tripping might be con-
UJ 6 f
iQ
R
templated in the future.
I
IV. PRACTICAL CONSIDERATIONS IN (a) (b)
GENERATOR GROUNDING
Fig. 27-Alternative methods of ground fault detection on
The broad objective in grounding a generator system is isolated neutral generators.
to gain additional protection to the generators and other
equipment without introducing disproportionate hazards. it can be set more sensitively. In addition for 27 (b) the
In the sections which follow, t,he various generator con- alarm will be given in case of an open circuit in the primary
nections are analyzed with the view of selecting the meth- of a potential transformer. In 27 (a), if there is sufficient
od of grounding most suitable. bus and transformer capacitance the triangle of line volt-
age will tend to be stabilized with reference to ground and
26. Unit System-Fig. 19 the residual harmonics will appear between neutral and
From the discussion under Sec. 12, it is evident that ground. The relay must be set above any such harmonic
solid grounding of the generator neutrals, whether one voltage, which therefore decreases its sensitivity. Usually
machine or all of them, will usually result in ground fault this will not be a serious handicap although in extreme
currents exceeding the three-phase fault current. From cases harmonic voltages as much as 1.5percent of normal
the standpoint of mechanical strength of the generator phase-to-neutral voltage might exist between neutral and
winding, this situation requires that any grounding of the ground. The scheme of Fig. 27 (b) avoids this situation.
generator neutrals be through an impedance sufficient to In the scheme of both Figs. 27 (a) and (b), the sensitivity
limit the ground-fault current to the three-phase value. of protection decreases as the ground-fault approaches the
If the neutrals are to be grounded, and no further limita- neutral point. This is not often a serious handicap as most
tion of ground current is required, other than to secure faults are near the line end. For complete protection any-
protection against winding distortion, a neutral reactor is where within the windings, the scheme of 27 (c) suggested
suitable. As to transient overvoltages it is safe, and in the by R. Pohl can be used. As shown, this involves displacing
larger sizes has the advantage of lower cost and smaller the neutral continuously by means of an auxiliary wind-
space as compared with a resistor. A neutral breaker ing on one potential transformer. Therefore, when a
should usually be provided to limit burning in case of in- ground occurs anywhere-even on the neutral lead itself-
ternal generator faults because of slow decay of field cur- a voltage will appear across the relay. This scheme is
rent and residual voltage even when the field breaker is limited to stations where the generator leads and buses are
opened. However in small stations the saving in cost may isolated from the system by transformers. Otherwise, ca-
bc worth weighing against the possibility of increased pacity effects or neutral grounds on other equipment would
damage to the machine. cause a continuous indication. These ground fault detec-
An advanmge sometimes attributed to grounding gener- tors are in addition to the customary differential protec-
ators with the unit system of operation is that most arma- tion.
ture-winding faults start as grounds. Ry grounding the In all of the schemes of Figs. 27 (a), (b) and (c), there
neutral, positive current flow is obtained in case of a fault is some risk of false indication caused by ground faults on
SO that quick and positive relaying is obtained. It is the high-tension system. This can arise as a result of zero-
doubtful if there is any pronounced advantage insofar as sequence capacitive coupling between high-voltage and
relaying is concerned over that obtainable with unground- low-voltage windings of the step-up power transformers.
ed operation and ground-fault detectors. Three forms of The zero-sequence diagram of part of the system is illus-
ground-fault detection are illustrated in Fig. 27. A single trated in Fig. 28. As there shown, the capacity effect of
potential transformer from neutral to ground is utilized in the power-transformer windings can be represented by an
Pig. 27 (a). A ground fault on any part of the circuit com- equivalent star. Part of the zero-sequence voltage on the
prising the low-voltage winding of the transformer, con- high-voltage side created by a ground fault is transferred
necting leads, or generator winding will produce a voltage to the low-voltage side by capacity potentiometer effect,
on the relay that can be used for tripping or alarm pur- and will give some voltage across the fault-detector relay.
poses. In Fig. 27 (b) three potential transformers are con- The magnitude of this voltage is determined by the ratio
nected in star, and function in a similar manner. This of transformation, type of high voltage grounding, proxi-
scheme has an advantage over that of Fig. 27 (a) in that mity of fault, amount of capacitances in the transformer
662 Grounding of Power System Neutrals Chapter Ig

(a) (b)
CAPACITORS
Fig. ZS-How zero-sequence capacitive coupling may cause
false indications. I .25$,;;; .06
(a.) Internal capacitances of two-winding transformer.
(b) Zero-sequence diagram showing how zero-sequence volt.ngcs
may be transferred from the high-voltage to the low-voltage
side of a transformer where the low-voltage sick is ungrounded
and of low electrostatic capacity to ground.

VOLTAGE dELAY OR CURRENT RELAY


branches and the generator, and the burden of the relay.
In general, the larger the transformer bank and the higher Fig. 30-Capacitance values for grounding through distribu-
the voltage, the greater the risk of false operation. The tion transformer fix kw loss value of secondary resistor.
difficulty can be eliminated by paralleling the relay with a
dummy load or by using a low-impedance current relay, The zero-sequence capacitance per phase of each circuit
without interfering with the sensitivity of the protection. component are listed below and totalled.
While the conditions necessary to such false indication are
not likely, one such case has actually been observed. Be- Generator 0.320 mfd
cause of this electrostatic coupling, it is probably unde- Generator surge capacitor 0.250 mfd
sirable to operate the generators without some form of Generator leads 0.060 mfd
Power transformer 0.001 mfd
drainage to ground.
A scheme which avoids the principal objections to un- Total 0.63~ mfd
grounded neutral is shown in Fig. 29. This consists of
1
At GOcycIes, this is a capacitive reactance of - or
2xfC ’
106
or 4180 ohms. The zero-sequence current is
377(O.G34) I
equal to the normal phase to neutral voltage divided by
this reactance or 6620/4180= 1.58 amneres. The total
capacitive fault current is three times the zerolsequence
curren~~z:7-i--~&5~zi2-~ --- ..~_
_---~ .-_-. ____-
Transient-analyzer studies have been made to determine
the influence of the size of the resistor upon the transient
overvoltage produced during an arcing fault. This subject
is treated in more detail in Chap. 14. In general, it was
found that as the kilowatts dissipation in the resistor is
increased, the transient voltages steadily decrease until
the resistor kilowatt loss equals the capacitive kvn. In-
creasing the resistor energy loss further gave but little
additional reduction in transient overvoltage.
Fig. 29-Grounding scheme for unit system. The total current at the point of the fault to ground is
the vector sum of the capacitive component of current,
connecting the primary of a distribution type transformer and the resistive component. If the resistive component
between the generator neutral and ground. The secondary is made equal to the capacitive component, the sum is I.41
of this transformer is shunted by a resistor and by a po- times as much as the capacitive component. Increasing
tential relay for tripping or alarm, as desired. The size of the resistive current beyond equality with the capacitive
the transformer and resistor depend upon the charging current produces little further reduction in transient over-
current in case of a line-to-ground fault. This charging voltage, but increases the energy in the arc and the dam-
current can be obtained by summing up the various com- age therefrom. It has become more or less standard prac-
ponents of circuit capacitance, and determining the cur- tice to apply the resistor to develop an energy loss equal
rent that flows if one phase is grounded. The system of to or slightly exceeding the capacitive kva duringground-
Fig. 30 is used for an example. This covers an 11.5-kv, fault conditions. I
75 OOO-kva, 1800-rpm, 60-cycle turbine generator having The kva of the transformer is determined by the product
surge-protective capacitors at its terminals. of the primary current and the rated primary voltage!
Chapter 19 ’ Grounding of Power System Neutrals 663

divided by an overload factor from the following table: tices as to neutral grounding have been employed, perhaps
Time Factor the commonest of which is to provide a neutral bus to
which one or more machine neutrals are tied, with a resistor
1 Minute 4.7 from this bus to ground. The resistance is usually such as
5 Minutes 2.8 to limit the ground-fault current to 0.5 to 1.5 times full-
30 Minutes 1.8 load current of the smallest machine, however no hard and
1 Hour 1.G fast rule can be given. With the sensitive differential pro-
2 Hours 1.4 tection now used, this permits satisfactory tripping for
The rated primary voltage of the transformer should be grounds in any machine. Grounding transformers on the
approsimntely 1yz times the generator line-to-neutral volt- low-voltage bus have also been used to insure a source of
:Lge,in order to avoid excessive magnetizing inrush, when ground current for relaying. However, it is difficult to
a ground occurs. It is preferable to disconnect a generator hold X,/X, to 3.0 and transient overvoltages may be ex-
from the system, and remove excitation immediately upon cessive.
the occurrence of a fault, in order to confine the damage
as much as possible. On small systems, some operators 28. Power Transmitted at Generator Voltage,
prefer to have a ground relay sound an alarm, giving the Three-Wire System Fig. 21
system operator a chance to make provision for the loss of The problem of selectively isolating ground faults will
the generator. In any case, automatic tripping should usually require that a system of this kind be grounded in
follow after a reasonable time delay. some manner. Likewise if cables are used for the distribu-
For the system of Fig. 30, the capacitive kva developed tion circuits, the matter of neutral stabilization and sup-
is (11.5/1.732) (4.74) =31.5 kva. The resistor should dissi- pression of arcing grounds will require that the grounding
pate 31.5 kw. If a transformer of 11 500 volts primary, impedance be moderately low. One machine alone can be
-IO0 volts secondary were selected, the open-circuit sec- grounded and satisfy these requirements, but a neutral-
ondary voltage would be 4GOj1.732 or 265 volts. The cur- impedance device will be necessary to limit the maximum
rent rating of the resistor would be 31 500 watts/265 volts current through the machine. Because of the various
or 119 amperes, and its resistance 265/119 or 2.23 ohms. combinations of machines that may be in service at dif-
The kva duty on the transformer is (11.5)(4.74) or 54.5 ferent times there is some operating complication in insur-
kvn. Sote that this exceeds the actual loading, due to the ing that a system ground is always available, and for this
use of a transformer rated on the basis of line-to-line volt- reason it is probably desirable that all neutrals be ground-
age. For a l-hour duty cycle a transformer rated 54.5,‘l.G ed. If a neutral bus is employed, each neutral can be con-
or 34 kva can be used. A standard 37.5-kva transformer nected to this and a single grounding resistor or reactor
can be selected on this basis. For a 5-minute duty cycle a used. An alternative and probably more desirable ar-
rating of 54.6/2.8 or 19.5 kva would suffice, and a standard rangement is to ground each neutral through sufficient
2%kva transformer can be selected. In general, it is prefer- impedance that the ground-fault current through each
able to be conservative on the transformer rating in order individual machine will never exceed its safe value.
that its reactance not be an appreciable factor. It is prefer- The influence on communication circuits is almost im-
able to apply the resistors on the basis of continuous duty, possible to forecast, because most cases arise out of reso-
as their size and cost are usually not significant factors. nance between the ground reactance and the capacitance
Oil-immersed, askerel-immersed, and air-cooled trans- to ground of the circuits. With these constantly changing
formers can be used, based on user preference. Either with the growth of the system, about the only course that
current- or voltage-actuated relays can be used, as indi- can be pursued is to consider each case as it arises. Usually
cated by Fig. 30. a parallel tuned filter in the neutral connection of one
The scheme is, in effect, a generator-neutral grounding generator will cure a specific case of trouble.
device of very high resistance in which a fragile and bulky
high-voltage resistor is replaced by a step-down trans- 29. Power Transmitted at Generator Voltage,
former and low-resistance resistor. With the proportion- Four-Wire System Fig. 22
ing suggested, the possibility of ferro-resonance with an The general situation with this system connection is the
unshunted transformer is avoided, transient overvoltages same as on the three-wire system. However since loads
from switching or arcing are reduced, and there is a re- are connected from phase wires to the neutral wire, the
duction in harmonic voltage in the potential indication, question of neutral displacement during faults becomes
making it possible to use lower settings for the ground much more important. Otherwise, during a ground fault
relay. on one phase, the voltage on the other phases will rise,
and lamps, radios and other utilization devices will be
27. Power Transmitted at High Voltage, Low-Volt- flashed. It is therefore essential on a four-wire system that
age Bus System Fig. 20 no more impedance be inserted in the neutral connection
A good many of the arguments with reference to Fig. 19 than necessary to protect the generators against excessively
also apply to Fig. 20, particularly to limitation of ground- high currents during ground faults. The proper impedance
fault current. If the neutrals are all ungrounded, however, can be calculated by the method of symmetrical com-
it is not possible to secure individual selection of the ma- ponents. If all generators are grounded, making $= 1.0
chine developing a ground fault, as the low-voltage tie
puts the residual voltage on all machines. Various pmc- for each generator will satisfy the generator require;ents.
Grounding of Power System Neutrals
‘!
Y
664 Chapter 19 z$

exists some possibility of communication circuit interfer-


Tf $= 1 for the entire system, this will hold the line-to- ence. In fact, the case is exactly analogous to that dis-
11
neutral voltage down to normal value (as shown by Fig. 6, cussed in Section 28.
Chap. 1-I) and thus satisfy the load requirements. It is Figure 23 (c) is similar to 23 (b) except that a delta
probable that a moderate increase in line-to-neutral volt- tertiary has been added. The effect of the tertiary is to
age during ground faults is permissible because the condi- decrease the magnitude of the triple series harmonic volt-
ages applied t,o the outgoing lines and to cause a circulat-
tion is temporary, so that ratios of g= 1.5 or even 2.0 for ing current to flow in the neutral interconnection. In most
1
the system may be feasible. These figures are approxi- cases it is doubtful whether either of these influences exists
mate, as resistance has not been considered, and in some in sufficient magnitude to be of any practical importance.
cases, it will be important. Assume for example that the delta winding is rated at one-
Three possible ways in which neutral impedances can half the kva parts of a one to two ratio auto-transformer.
be employed are presented in Figs. 22 (b), (c) and (d). It will then be one-fourth’the generator kva rating. The
The first is shown merely for the sake of completeness; it reactance from generator winding to tertiary winding may
.serves no necessary function in limitation of current and be 8 percent on the tertiary kva or 32 percent on the gen-
would prove a liability in excessive neutral displacement erator kva. If the generator zero-sequence reactance is 8
and regulation with unbalanced loads. percent, the triple harmonic voltages at the generator
In both Figs. 22 (c) and (d), the neutral impedance is terminals will be reduced to about 302) or four-fifths
between generator neutral and ground where it is effective 3(8+X9
in reducing ground-fault currents. In 22 (c) the regula- the value without a tertiary. This reduction would ordi-
tion to unbalanced loads is slightly better than in 22 (d), narily not be sufficient to correct interference to a satis-
but the impedances necessary for neutral stabilization will factory level. The harmonic circulating current is similar-
be usually low compared to the line impedances where ly of small importance from the standpoint of heating.
there are a number of individual feeders and this point will For example, assume 10 percent third harmonic voltage
ordinarily not be important. On many systems the fourth in the generator phase to neutral wave form (a very high
wire will be grounded at each transformer installation, figure for modern generators). This would be acting on an
and 22 (d) is necessary in this event. In general 22 cd) impedance of 3X(8+32) or 120 percent. The circulating
represents a more satisfactory connection. 10
current would then be w. X 100 or 8 percent per phase
In most power stations, there is considerable shifting of
generators in and out of service. With the four-wire sys- increasing the 12R by only g percent. See Sec. 15 of this
tem, the dual requirements of prevention of high individual chapter. (NOTE: In both of the above calculations, it
generator currents during ground faults, and restriction of was assumed that the generator reactance would increase
neutral displacement are necessary. The most satisfactory as the order of the harmonic.) The foregoing discussion
method of maintaining these requirements is to use in- shows that where both the generator and auto-transformer
dividual grounding devices with each generator. The gen- are to be grounded and are in the same station, there is
erator-neutral breaker may be left closed whether the gen- little point to adding a delta tertiary winding to the auto-
erator is in or out of service, and only opened in case of a transformer. Should there be an appreciable distance be-
generator fault. tween the generator and the transformer, and particularly
For this type of service reactors are preferable as ground- if there are paralleling communication circuits this ques-
ing devices. For a given limitation of current, the distor- tion should be carefully considered, as the flow of trans-
tion of phase voltages to ground will be less than for a former magnetizing current or generator triple harmonic
resistor because the voltage drop is in phase with the circulating current may cause inductive influence.
phase-to-neutral voltage of the faulted phase. The cost In Fig. 23 (d) the generator neutral is ungrounded, and
and space requirements will usually be less. The likeli- the auto-transformer neutral grounded, with a delta terti-
hood of excessively high transient voltages during arcing ary provided. This minimizes all communication- circuit
influence and generally gives satisfactory stabilization of
grounds is small because the 2 ratio must be kept low
1 voltages in the event of ground faults. Generator differen-
on the four-wire system. tial protection is less sensitive for faults in the vicinity of
the generator neutral point.
30. Power Transmitted at Double Generator Volt- Figure 23 (e) shows the generator neuk.al grounded and
age by Auto-Transformers, Fig. 23 the auto-transformer neutral ungrounded. This connec-
Figure 23 (b) is being used to a considerable extent on tion puts the generator triple series harmonics on the out-
large systems employing 24 kv or 27.6 kv underground going circuits, but facilitates generator differential Pro-
cable distribution systems. Interconnecting and ground- tection. The line voltages are properly stabilized in the
ing the neutrals of the generators and auto-transformers event of ground faults.
stabilizes the neutral and prevents excessive voltage stres- If both generator and auto-transformer grounds “fe
ses in the event of ground faults. Any triple series har- omitted, the generator insulation will be qverstressed ln
monics present in the generator wave form are passed to the event of a ground fault on the high v ltage side of the “3
the outside lines. On cable systems there is little likeli- auto-transformer and this connection shou $ d therefore not uI
hood of this causing interference with communication cir- be used. If the high voltage side of a grounded neutral ’
cuits. Where the distribution is by overhead lines there auto-transformer is connected to an effectivply grounded,
Chapter 19 Grounding of Power System Neutrals 665

WITHOUT FEEDERS AT GENERATED VOLTAGE

UNGROUh

RiSlSTANCi
I
I .

- REACTANCE

*DISTRIBUTION TRANSFORMER WITH SECONDARY


Fig. 31--Relative United States use of grounding methods on RESISTOR
generators without feeders at generated voltage.
Fig. 32-Relative United States use of grounding methods on
generators with feeders at generated voltage.
system (preferably with grounded star-delta transformers
at the same station) the tertiary may be omitted whether
2. General Considerations in Grounding the Neutral of Power Sys-
the generator neutral is grounded or not. The generator
tems, by H. H. Dewey, A.Z.E.E. Transaclions, April 1923, pages
neutral will be shifted from ground potential in the event 405-416.
of a ground fault on the system, but not sufficient to over- 3. Voltages Induced by Arcing Grounds, by J. F. Peters and
stress the generator insulation. J. Slepian, A.I.E.E. Transaclions, April 1923, pages 478-489.
Generally, a fault to ground on the high-voltage side of 4. Experimental Studies of Arcing Faults on a 75-Kv Transmission
the auto-transformer will not result in generator currents System, by Eaton, Peck, and Dunham, A.I.E.E. Transactions,
exceeding those permissible. For ground faults on the low- December 1931, pages 1469-1478.
voltage side, the generator currents may exceed permissible 5. Present-Day Practice in Grounding of Transmission Systems
v&es unless a reactor is placed between the generator (Committee Report), A.I.E.E. Transactions, September 1931,
neutral and ground. pages 892-900.
6. Petersen Coil Tests on 140-Kv System, by J. R. North and
31. Trends and Practices in Generator Grounding J. R. Eaton, A.I.E.E. Transaclions, January 1934, pages 63-74.
7. Some Engineering Features of Petersen Coils and Their Appli-
Figures 31 and 32 are plotted from data obtained from cation, by E. M. Hunter, A.I.E.E. Trunsac~ions, January 1938,
the Third AIEE Report on System GroundingI*. In most pages 11-18.
of the cases of “reactance grounding,” the grounding 8. System Analysis for Petersen-Coil Application, by W. C.
reactors are of low ohms, resulting in “effective ground- Champe and F. Von Voigtlander, A.I.E.E. Transactions, De-
ing.” “Solid” and “reactance” grounded may therefore cember 1938, pages 663-672.
be combined as “effective” grounding, and as such, about 9. Power System Faults to Ground, by C. L. Gilkeson, P. A.
half of the systems are so grounded. The percentage of Jeanne, J. C. Davenport, Jr., and E. F. Vaage, A.Z.E.E. Truns-
affectively grounded systems is decreasing slightly. The actions, April 1937, pages 421-433.
10. Abnormal Voltage Conditions in Three-Phase Systems Pro-
“ungrounded” classification includes potential transformer
duced by Single-Phase Switching, by Edith Clarke, H. A.
grollnding. Peterson, and P. H. Light, A.I.E.E. Technical Paper 40-105.
11. American Standards Association Standards for Neutral Ground-
REFERENCES ing Devices, January 30, 1941.
1. Present-Day Practices in Grounding of Transmission Systems, 12. Present-Day Grounding Practices on Power Systems-Third
by Woodruff and Stone (Committee Report), A.Z.E.E. Trans- A.I.E.E. Report on System Grounding (Committee Report),
uclions, April 1923, pages 446-464. A.I.E.E. Technical Paper 47-237.
CHAPTER 20

DISTRIBUTION SYSTEMS ’
Original Authors: Revised by:
John S. Parsons and H. G. Barnett John S. Parsons and H.G. Barnett

I. GENERAL -BULK POWER SOURCE

A
N electric distribution system, or distribution plant
SUBTRANSMISSION
as it is sometimes called, is all of that part of an
electric power system between the bulk power
source or sources and the consumers’ service switches. DISTRIBUTION
The bulk power sources are located in or near the load area

c
SUBSTATION
to be served by the distribution system and may be either
PRIMARY FEEDER
generating stations or power substations supplied over
transmission lines. Distribution systems can, in general,
be divided into six parts, namely, subtransmission cir-
cuits, distribution substations, distribution or primary
feeders, distribution transformers, secondary circuits or
secondaries, and consumers’ service connections and
meters or consumers’ services. Figure 1 is a schematic dia-
gram of a typical distribution system showing these parts.
The subtransmission circuits extend from the bulk
power source or sources to the various distribution sub-
7-b ‘CONSUMERS’ SERVICES’
stations located in the load area. They may be radial cir-
cuits connected to a bulk power source at only one end or Fig. i-Typical distribution system showing component parts,
loop and ring circuits connected to one or more bulk
power sources at both ends. The subtransmission circuits The distribution plant occupies an important place in
consist of underground cable, aerial cable, or overhead any electric power system. Briefly, its function is to take
open-wire conductors carried on poles, or some combina- electric power from the bulk power source or sources and
tion of them. The subtransmission voltage is usually be- distribute or deliver it to the consumers. . The effec-
tween 11 and 33 kv, inclusive. tiveness with which a distribution system fulfills this
Each distribution substation normally serves its own function is measured in terms of voltage regulation, service
load area, which is a subdivision of the area served by the continuity, flexibility, efficiency, and cost. The cost of
distribution system. At the distribution substation the distribution is an important factor in the delivered cost
subtransmission voltage is reduced for general distribu- of electric power. Approximately 50 per cent of the capital
tion throughout the area. The substation consists of one investment in electric power systems in the United State8
or more power-transformer banks together with the neces- is in the distribution plant.
sary voltage regulating equipment, buses, and switchgear. Briefly, the problem of distribution is to design, con-
The area served by the distribution substation is also struct, operate, and maintain a distribution system that
subdivided and each subdivision is supplied by a distri- will supply agequate electric service to the load area under
but’ion or primary feeder. The three-phase primary feeder consideration, both now and in the future, at the lowest
is usually run out from. the low voltage bus of the sub- possible cost. Unfortunately, no one type of distribution
station to its load center where it branches into three- system can be applied economically in all load areas, be-
phase subfeeders and single-phase laterals. The primary cause of differences in load densities, existing distribution
feeders and laterals may be either cable or openwire cir- plant, topography, and other local conditions.
cuits, operated in most cases at 2400 or 4160 volts. In studying any load area, the entire distribution Or
Distribution transformers are ordinarily connected to delivery system from the bulk power source-which may
each primary feeder and its subfeeders and laterals. These be one or more generating stations or power substations,
transformers serve to step down from the distribution to the consumers should be considered as a unit. This
voltage to the utilization voltage. Each transformer or includes subtransmission-distribution substations, Pri-
bank of transformers supplies a consumer or group of con- mary feeders, distribution transformers,
sumers over its secondary circuit. Each consumer is con- services. All of these parts are interrel
nected to the secondary circuit through his service leads be considered as a whole so that money
and meter. The secondaries and service connections may of the distribution system will not be more’ than offset
be either cable or open-wire circuits. a resulting increase elsewhere in the system.
,
666
Chapter 20 ‘Distribution Systems 667

For different load areas, or even different parts of the


Sameload area, the most effective distribution system will
often take different forms. Certain principles and features,
ho\vevcr, are common to almost all of these systems. The
distribution system should provide service with a mini-
mum voltage variation and a minimum of interruption.
Service interruptions should be of short duration and
al’fect a small number of consumers. The overall system
cost-including construction, operation, and maintenance
of the system-should be as low as possible consistent
wit,11the quality of service required in the load area. The
syst,cm should be flexible, to allow its being expanded in
small increments, so as to meet changing load conditions
with a minimum amount of modification and expense.
This flexibility permits keeping the system capacity
close to actual load requirements and thus permits the
most effective use of system investment. It also largely
eliminates the need for predicting the location and magni-
tudes of future loads. Therefore, long-range distribution
Planning, which is at best based on scientific guesses, can
be greatly reduced.

II. TYPES OF DISTRIBUTION SYSTEMS


Electric power was originally distributed by radial d-c Fig. 2--Simple form of radial-type distribution system.
systems which later developed into the well known d-c net-
work system. For many years this was the standard form secondary circuits to which the consumers’ services a?e
of distribution system for the heavy-density load areas connected.
where the distribution circuits are usually underground, Oil circuit breakers arranged for overcurrent tripping
such as in the business sections of the larger cities. Be- are used to connect the radial-primary feeders to the low-
cause power could be transmitted only at the utilization voltage bus of their associated substation. When a short-
voltage, the d-c system was not suitable for serving eco- circuit occurs on a feeder its station breaker opens and
nomically the more extensive lighter-load areas. After interrupts the service to all consumers supplied by the
the introduction of alternating current into this country by feeder. Manually-operated sectionalizing switches are
George Westinghouse, these areas were served by over- often installed at the junction of the subfeeders and
head a-c systems of the radial type. The heavy-density the main feeder. When trouble on a subfeeder has been
load areas in many of the smaller cities, where it was felt located the faulty section can be isolated by opening the
that the necessity for service reliability did not warrant proper switch, and service can be restored to the remain-
the expense of a d-c network system, were also fed from der of the feeder before repairs are made. The purpose of
a-c radial systems. For that matter they still are. Most the fuses in the primary leads of the distribution trans-
electric power today is distributed by a-c systems. The formers is to open the circuit in case of trouble in a trans-
rrlutively few d-c distribution systems still in service are former or on its associated secondary lines and prevent a
gradually being replaced by a-c systems. The following possible shutdown of a considerable portion of the feeder
descriptions and discussions of distribution systems are or the entire feeder on such faults. The subfeeders and
confined to alternating current systems. laterals are sometimes fused to prevent tripping the feeder
breaker at the substation and thus reduce the extent of
1. The Radial System the outage when a fault occurs on one of them. Obviously,
The radial type of distribution system, a simple form the transformer fuses, branch fuses, and feeder breaker
of which is shown in Figure 2, is the most common. It is should be properly coordinated so that the circuit mill
used extensively to serve the light- and medium-density be opened at t,he proper point to keep the outage to a
load areas where the primary and secondary circuits are minimum.
usually carried overhead on poles. The distribution sub- When a fault that is not self clearing develops on any
station or substations can be supplied from the bulk- section of the feeder, in one of its associated distribution
Power source over radial or loop subtransmission circuits transformers, or on one of its secondary circuits, a number
or over a subtransmission grid or network. The radial of the consumers will be without service for a considerable
system gets its name from the fact that the primary period. All consumers connected to the feeder will, of
feeders radiate from the distribution substations and course, be affected if the fault is located so as to cause the
branch into subfeeders and laterals which extend into all feeder breaker at the substation to open. Experience with
Parts of the area served. The distribution transformers are faults on open-wire circuits has shown that deenergizing
connected to the primary feeders, subfeeders, and laterals, these circuits causes the faults to clear themselves in most
usually through fused cutouts, and supply the radial cases. For this reason the feeder breakers are often made
668 Distribution Systems Chapter 20 ?

to reclose automatically. The reclosing equipment pro- cause of the poor service reliability it provides. A fault
vides one, two, or three reclosures before the breaker is on a radial subtransmission circuit results in a service in-
locked open. terruption to all loads fed over it. The economical use of
Fundamentally the advantages of the radial distribu- subtransmission circuits and associated circuit breakers
tion system are simplicity and low first cost. These result dictates that each subtransmission circuit carry a rels
from a straightforward circuit arrangement, where a sin- tively large block of load. Thus a fault on a radial sub-
gle or radial path is provided from the distribution sub- transmission circuit results in the 10s~ of considerable
station, and sometimes from the bulk power source, to the load, which usually means that a large area and many
consumer. With such a circuit arrangement the amount consumers are without service.
of switching equipment is small and the protective relay- An improved form of radial subtransmission is shown in
ing is simple. Although simplicity and low first cost Fig. 4. Each radial subtransmission circuit serves as a
account for the widespread use of the radial system they
are not present in all forms of the system. /BULK POWER SOURCE BUS,
The lack of continuity of service is the principal defect
of the radial system of distribution. Attempts to over-
come this defect have resulted in many forms and arrange-
ments of the radial system. Frequently the system is
radial only from the distribution substations to the dis- QUBTRANSMISSiON
CIRCUIT -
tribution transformers. Because of the many system
arrangements encountered it is sometimes difficult to de-
termine in what major type a system should be classified.
To aid in such classification and to follow more readily the
discussion of radial systems, it should be remembered
that a radial system is a system having a single path over
which current may flow for a part or all of the way from
the distribut)ion substation or substations to the primary
of any distribution transformer. DISTRIBUTION
Subtransmission.-Power is transmitted from the SUBSTATION
bulk power source or sources to the distribution substa-
tions over the subtransmission circuits. These circuits
may be simple radial circuits, parallel or loop circuits, or a
number of interconnected circuits forming a subtrans-
mission grid or network. Several factors influence the
selection of the subtransmission arrangement for supplying
distribution substations in a radial system. Two of the
most important are cost and reliability of power supply
to distribution substations.
A radial arrangement of subtransmission circuits such
as that shown in Fig. 3 results in the lowest first cost.
+ -BREAKER
* -THESE TWO
NORMALLY

BREAKERS
OPEN

ARE INTERLOCKED TO PROVIDE


AuToMATic THROWOVER
This form of subtransmission is not usually employed be-
Fig. &-Improved form of ra)dial type subtransmission circuits.

A x -BULK POWER SOURCE BUS/ & 6


normal feed to certain distribution substation transform-
Y SUBTRANSMISSION-.,
--I -
ers and as an emergency feed to others. This arrangement
permits quick restoration of service when a radial sub-
CIRCUIT
t- transmission circuit is faulted. The substation trans-
formers normally fed from the faulty circuit are each pre
vided with an emergency circuit to which they can be
switched either manually or automatically. This arrange
ment does not prevent an extensive servic+ int.erruption
for a short time and requires spare capacity to be built .i.
into the radial subtransmission circuits. i’
DISTRIBUTION Because extensive service interruptions cannot oft@
SUBSTATION be- tolerated, the subtransmission for a radial system‘
usually takes the form of parallel or loop circuits or of a.p;i
’ subtransmission grid. Whether a loop or a grid a
ment of subtransmission circuits is preferable will
largely on conditions in the particular load\area:’
the load distribution, the topography, and the num
location of the bulk power sources.
Fig. 3--Simple form of radial type subtransmission circuits. A parallel- or loop-circuit subtransmission layout
Chapter 20 Distribution Systems 669

shown in Fig. 5, on which no single fault on any circuit substation. This paralleling of bulk power sources through
,b,ill interrupt service to a distribution substation. All cir- the subtransmission circuits also has the advantage of
cuits must be designed so that they will not be overloaded tending to equalize the load on the bulk power sources.
,&en any one circuit is out of service. Two parallel cir- In a large distribution system any two or even all of
cnits are considered to be a sectionalized loop supplying the above forms of subtransmission may be employed be-
“ne distribution substation. However, two parallel cir-
crlits running over the same right-of-way are not nearly
ns reliable as two circuits following different routes. A
f:iult on one circuit may involve the other if the two cir-
cuits are closely adjacent. This is not as likely to result,
h~WVCr, with cable circuits as with open-wire circuits.
The term “loop” as used here should not be confused
pith the term “ring”. By loop is meant a circuit which
atarts from a power-supply point or bus and after running
tllrough an area returns to the same point or bus; where-
:Lsa ring is a circuit or circuits which start from a pomer-
s11pp1ypoint or bus, tie together a number of power-sup- 3 6- P
ply points or buses, and return to the starting point or
\)ns. In other words, a ring is a loop from which substa-
tions can be supplied and into which power is fed at more
\
/
I\ :
than one point. The ring arrangement is quite often used
for subtransmission. It is a simple form of subtransmission DlSTRlEilTlON
network, and as the system grows it very often develops SUBSTATION
into a grid.
The network form of subtransmission is flesible in that
it, c:m readily be estcnded to supply additional distribu-
1
t,ion substations in the area it covers with a relatively
--L-c-L -w-
small amount of new circuit construction. It requires a
I:lrge number of circuit breakers, however, and is difficult i 0 0
:tnd costly to relay. The network or grid form of sub-

Fig. 6-Network or grid form of subtransmission.

tween the bulk power sources and the various distribution


substations, depending upon the service requirement of
the different substations and economic considerations.
The form of subtransmission employed is also influenced
by the design of the distribution substations used.
Distribution Substations.-Twenty years ago it was
common practice to use large distribution substations.
The transformer capacity in many of them lay between
I 1
15 000 and 30 000 kva. This, of course, meant that every
\
DISTRIBUTION
reasonable precaution was taken to insure continuous
SUBSTATION power supply to these stations. It also meant that sys-
tems employing these large stations contained a rela-
tively small mileage of subtransmission circuits compared
to the mileage of primary distribution circuits. Except
in the areas of heavy load density this meant that the

-Y--Y
“r “r
load was being carried too far at the lower distribution
voltage and not far enough at the higher subtransmission
voltage to give an economical distribution system. The
use of these large stations also resulted in a system not
Fig. 5-A parallel- or loop-circuit subtransmission layout. readily adapted to changing load conditions. The sub-
station capacity could not be increased in small incre-
transmission shown in Fig. 6 provides greater service re- ments economically to take care of load growth. Also as
liability to the distribution substations than the radial the load grew, it often grew away from the locations where
Qd loop forms of subtransmission. This is true particu- it was assumed it would grow when the large substation
larlY when the distribution system is supplied from two locations were selected. This further increased the dis-
Ormore bulk power sources, because it is possible for pow- tance over which the load had to be carried at distribu-
er to flow from any bulk power source to any distribution tion voltage. Thus as time passed these systems became
670 Distribution Systems Chapter 20

even less economical than when first designed and in- can easily and quickly be taken to any of the distribution
stalled. In order to increase the economy and flexibility substation sites and connected temporarily to serve the
of distribution systems the trend during recent years has load in such an emergency.
been toward the use of more and smaller distribution The substations of Fig. 7 may or may not require volt-
substations, with a resulting increase in the mileage of age regulating equipment. This equipment may take the
subtransmission circuits and a decrease in the mileage of form of automatic tap-changing-under-load, built into the
primary distribution circuits. transformer, or one or more separate voltage regulators
Along with the change in the size of distribution sub- Tap-changing-under-load equipment on a three-ph&
stations has gone a change in the subtransmission nrrange- transformer provides voltage regulation in the least space
ments used. This change has been a simplification of the and usually at the lowest cost. For small substatio,-,B
subtransmission layout and as large a reduction in the with one primary feeder or relatively few low capacity
number of high-voltage circuit breakers as is consistent primary feeders a single set of regulating equipment is
with sci-vice requirements. These changes have led to an usually sufficient to maintain SatiSfaCtOi-y VOhge on the
increased use of the radial form of subtransmission along load side of the substation transformer bank. Large sul,.
with the simpler loop and network forms. There is also stations having many primary feeders of larger capacity,
a growing tendency to treat a subtransmission circuit and
its associated substation transformer or transformers as a
unit, thus eliminating high-voltage circuit breakers and
doing the ncccssnry automatic switching on the low-volt-
ngc side of the substation transformer. When this is done
t,ho high-voltage bus in the substation is omitted. In the
larger substations however, it will at times prove eco-
nomical to employ a high-voltage bus and omit the low-
voltage bus.
The economical sizes of distribution substations to em-
ploy on a particular radial system depend on load density,
L--$ 1 c A1
subtransmission arrangement, unit cost of subtransmis-
sion circuits, unit cost of primary distribution feeders,
(0) (b)
Fig. Y-Simplest forms of distribution substations.
cost of land, and other factors. Because many factors in-
fluence the economical design of a distribution system and however, ordinarily require voltage regulators on UII
because existing distribution plant and local conditions feeders. In t,hese large substations it is sometimes satis-
and requirements must be taken into account, many dis- factory to employ bus regulation, as in the small sub&
tribution substation designs are required. Some of the more tions, supplemented by regulators on only a few of tho
basic designs are illustrated and will be discussed briefly. primary feeders. Where this can be done it is usually moro
Perhaps the simplest form of distribution substation is economical than using feeder rewlators thro!lghout.
that shown in Fig. 7 (a). It consists of a high voltage dis- The single primary-feeder breaker of Fig. 7(a) is usually
., connecting switch, a transformer bank, and a primary- provided with overcurrent relays and automatic reclosing
feeder breaker in the low-voltage leads of the transformer equipment. Its interrupting capacity need be equal only
bank. The transformer bank can consist of three single- to the maximum fault current through the transformer.
phase transformers or one three-phase transformer. Now It should be remembered, however, that the interrupting
t,hat more small substations are being used the trend is rating of the breaker is affected by the reclosing cyc10.
definitely to the use of three-phase transformers. A three- In order to permit safe inspection and maintenance of the
phase transformer makes a neater and more compact breaker, disconnecting switches are shown on both sides
substation, reduces the number of bushings, valves, and of it. If there is no possibility of the primary feeder being
fittings to be inspected and maintained, and saves in- energized from another source at some point on the system,
stallation time and expense. The use of single-phase trans- the disconnecting switch on the load side of the breaker
formers has the advantage of permitting open-delta opera- can be omitted. However, switches on both sides of tllo
tion of the substation at reduced capacity, which is not breaker are preferable. If the load on the primary feeder
possible when using a three-phase transformer. Modern cannot be carried by some other feeder or feeders, when the
transformers fail so rarely, however, that this disadvan- feeder breaker is tripped and its associate9 disconnects are
tage of the three-phase transformer is more than out- opened, it must be dropped while the breaker is being in-
weighed by its advantages. When it is remembered spected or maintained. Sometimes this is not permissible
that we are talking primarily about transformer banks of and then a by-pass disconnecting switch, connected as in-
from 600 to 3000 kva it is often possible to keep a spare dicated by the dotted lines, should be used. By closipg
transformer at some central point. This transformer can this by-pass switch and then opening the breaker and I@
be taken to any substation whose transformer fails. Such two disconnecting switches, the breaker can be isolated for
a procedure may, however, take considerable time par- maintenance without interrupting service to the loads Oen
ticularly if the transformer to be transported is large. A its associated feeder. Should a feeder fault occumunder th@
better solution to the problem of quickly restoring service condition it must be cleared by the breaker in the sub’
from a small distribution substation whose three-phase transmission circuit supplying the substation or bY a
transformer has failed is to have a portable substation, that breaker or fuses in the primary feeder. AlthOugh the Prok’
chapter 20 Distribution Systems 671

$bility of a fault occurring while the primary feeder break- locked with the primary feeder breaker or breakers so
er is out of service is small, provision should be made for that it cannot be opened unless this breaker or brenkers
clearing the fault from the system without serious damage. are open. No breaker is used on the high-voltage side of
For safety, ease of inspection and maintenance, and the transformer bank because the possibility of trouble in
c0mpactness, lift-up or draw-out type breakers are now a transformer or in the connections between the trans-
rl,litc commonly used as the primary-feeder breakers in former and the feeder breaker or breakers is remote. Con-
distribution substations. These breakers provide the dis- necting the substation directly to the subtransmission
conncctmg-switch features on each side of the breaker, circuit without a high-voltage breaker is no more likely
:,s shown in Fig. 7(a), interlocked in such a way that the to produce an outage of the circuit than is extending the
$sconnects cannot be opened until the breaker is tripped. subtransmission circuit a few hundred feet. Should a
ljy having a spare breaker that can be inserted in place of fault occur in the transformer bank or its low-voltage
tllc: one removed, it is necessary to interrupt service to connections to the primary-feeder breaker or breakers,
the breaker in the subtransmission or supply circuit trips
to clear the fault. Sometimes the rating of the transformer
bank is so small in comparison with the rating of its asso-
ciated supply circuit that the current flowing to a fault
in the transformer winding or between the transformer
and the primary feeder breaker or breakers is insufficient
to trip the breaker in the supply circuit. To prevent dam-
age to the transformer under such a condition and to
disconnect the substation from the supply system, fuses
or protective links can be inserted in the high voltage
leads of the transformer either inside the transformer tank
or external to it. These protective links must be properly
coordinated with the feeder-breaker relaying so that their
blowing time is longer than the tripping time of a feeder
breaker for all currents that can result from faults on the
low-voltage side of the transformer.
Instead of fuses or protective links on the high side of
the transformer, where the substation capacity is small
compared with that of its associated subtransmission cir-
cuit, a circuit breaker can be used. Because of the high
voltage of the supply circuit and the fact that the inter-
Fig. g-1500 kva CSP power transformer in service in Pennsyl-
rupting duty on the high-voltage breaker is determined
vania. High voltage-13.2 kv delta; low voltage-2500/4340 Y.
by the characteristics of the supply system, the cost of
the load only for a very short time when work is to be such a breaker is likely to be out of proportion to the cost
(lone in a feeder breaker. If even a momentary interrup- of the remainder of the small substation and excessive for
tion is serious, a spare cell or compartment can be provided the amount of load controlled. For a single-circuit sub-
into which the spare breaker can be placed and closed station such as shown in Fig. 7(a) it is sometimes possible
in parallel with the breaker to be worked on before it is to justify a breaker on the high-voltage side of the trans-
tripped and removed. Either of these arrangements has former by omitting the primary-feeder breaker on the
the advantage of leaving the primary feeder with normal load side of the transformer. If the feeder breaker is
protection against a fault that might occur while the omitted a disconnecting switch can be used in its place to
normal feeder breaker is being serviced. A spare breaker insure complete isolation of the transformer where neces-
in almost all cases provides satisfactory inspection and sary. When using only a high-voltage breaker its over-
maintenance facilities, and the expense of a spare cell or current relays must be set to trip on both transformer and
compartment to prevent a very short time interruption to primary feeder faults. Except in the case of a cable feeder,
service can rarely be justified. it is desirable to have the breaker automatically reclose
The substation shown in Fig. 7(b) is similar to that of on feeder faults but it is undesirable to have it reclose on
Fig. 7(a) escept that it has a low-voltage bus and several a fault in the transformer. Relaying to accomplish this
Primary feeders instead of one. It is preferred to the becomes unduly complicated and questionable in opera-
single-feeder station where the magnitude or nature of tion. Thus it is usually desirable to retain the primary-
the load is such that it is necessary or desirable to split feeder breaker when a high-voltage breaker is used. In
the load between several primary feeders. Both of the the multiple-feeder station of Fig. 7(b) the primary-
stations of Fig. 7 are usually supplied over a single radial- feeder breakers are used either with or without a high-
subtransmission circuit. In each case the transformer is voltage breaker on the supply side of the transformer.
connected directly to the supply circuit through a discon- A distribution substation with a single subtransmission
necting switch. The disconnecting switch should never supply circuit will often be subjected to too many outages
he opened under load but should be capable of opening of considerable duration to be satisfactory, because of
the transformer exciting current. To prevent accidental faults on the supply circuit that must be located and re-
opening under load the switch should preferably be inter- paired before service can be restored. In order to restore
672 Distribution Systems Chapter 20

service quickly when a fault occurs on the substation’s The decision between the use of a disconnecting switch or
normal supply circuit, an ahernate supply circuit can be breakers is primarily an economic one and the cost will
brought to the substation and a double-throw disconnect- usually favor the disconnecting switch.
ing switch or two interlocked disconnecting switches used The station layouts discussed in connection with Fig. Q
on the high-voltage side of the transformer as shown in (a) and (b) permit reasonably quick restoration of serv-
Fig. 9. When the normal supply circuit is deenergized be- ice when a fault occurs on the subtransmission circuit
cause of a fault on it, the substation transformer can be supplying the station. This ability to restore service is
manually connected to its alternate supply circuit by the dependent on arranging the two circuits to each station
double-throw disconnecting switch and service thus so that a fault on one does not involve the other. A trans.
quickly restored to the loads fed through the substation. former failure, however, causes a relatively long inter.
After the normal supply circuit is repaired and reenergized ruption of service to the loads fed by the substation,
it is usually desirable to reconnect the substation to it.
To do this the disconnecting switch must be capable of
interrupting the transformer exciting current, or the alter-
nate supply circuit must be deenergized when the transfer
is made. Deenergizing the alternate circuit involves un-
due complication and is usually impractical because the
alternate feed to this substation also supplies some other
substation or substations. Because most disconnecting
switches are incapable of interrupting load current, the
double-throw switch should be interlocked so that the
primary-feeder breaker or breakers must be open before
the switch can be moved from one position to another. In
a multiple-feeder substation such as that shown in Fig.
9(b) it may be desirable to use a transformer breaker in the
secondary leads of the transformer as shown in order to (a) (b)
simplify the switching procedure and the interlock cir-
cuits. Fig. lo--Distribution substations with duplicate transformer8
The double-throw disconnecting switch of Fig. 9(a) and subtransmission circuits to reduce duration of service
interruptions due to transformer failures.

Such interruptions are infrequent but sometimes are


serious. TO guard against relatively long service inter-
ruptions resulting from transformer trouble, substations
as shown in Fig. 10 can be used. Because two subtrans-
mission circuits are brought to each substation to allow
quick restoration of service when a fault occurs on one of
them, as discussed in connection with Fig. 9, the substa-
tion transformer capacity can be divided into two banka
and one bank normally connected td each supply circuit.
With one transformer out of service the remaining bank
(0) should be able to carry the entire substation load. Using
self-cooled transformers this requires 100 per cent spare
transformer capacity in the station. By equipping each
of the transformers with automatic air-blast, however,
(RI the rating of each of the two banks can be reduced to 75
per cent of the substation rating, or in other words the
Fig. 9-Distribution substations with alternate subtransmis- amount of spare self-cooled transformer capacity can ha
sion supply to reduce duration of service interruptions.
reduced to 50 per cent. The use of three supply circuits
and three transformer banks further reduces the spare
and (b) can be replaced by two manually-operated high- transformer capacity.
voltage breakers, one in each supply circuit, interlocked The distribution substation show: in Fig. 10(a) b
so that only one can be closed at a time. If this is done, similar to that of Fig. 7(b) except that two supply qir
no interlocks with the primary-feeder breaker or breakers cuits are run to the station and the transformer caPacltY
are necessary to prevent opening load current. Where is divided into two banks. Each of the two banks hM
high-voltage breakers are used the transformer breaker is a self-cooled rating approximately equal to 75 per cent 0’
in practically all cases omitted. To do this switching with the substation rating and is equipped with automatlC
breakers, particularly oil breakers, they should be capa- air-blast. The station is normally oper ‘ted with the IoY
ble of interrupting any fault current that might flow voltage bus split into two sections sf that-each trm
through them, because of the remote possibility that a former supplies half of the substation load. This metI@
fault may occur while performing the manual transfer. of operation has the advantage of reducing the sho%:? .I&:
, ‘i?&
Chapter 20 Distribution Systems 673

circuit duty on the primary-feeder breakers. Supplying by using automatic throw-over substations such as those
the load from two separate bus sections instead of con- in Fig. 11. The substation shown in Fig. 11(a) is similar
setting all primary feeders to a single bus means less to that of Fig. 9(b) except that two high-voltage breakers
sdvantage is normally taken of the diversity between have been used to obtain the automatic throw-over fea-
primary feeders. This has no effect on the amount of ture. Only the breaker associated with the normal supply
,&station transformer capacity required, however, be- circuit is ordinarily closed. When a fault occurs on that
cause this capacity is determined by the condition of one circuit the breaker trips because voltage is absent. Its
transformer out of service, at which time the bus is opening causes the other high-voltage breaker in the
cnerated closed and full diversity among all primary alternate supply circuit to close. The return to the normal
feeders is obtained. To prevent the two transformers supply circuit after repairs have been made can be either
operating in parallel the load-break disconnecting switch manual or automatic. If the two supply circuits cannot
cr breaker between the two bus sections is interlocked so be momentarily paralleled the advantage of using manual
that it cannot be closed unless one of the two discon- reconnection is that the substation can be switched to its
necting switches in the secondary leads of the trans- normal circuit when a short service interruption is least
formers is open. When a fault occurs in one of the supply objectionable. An automatic reconnection functions to
circuits or its associated transformer the supply-circuit switch the transformer to its normal supply circuit when
hrenker trips and deenergizes the supply circuit and trans- the circuit is reenergized at about normal voltage. The
former thus dropping half of the substation load. This substation shown in Fig. 11(b) is similar to the station of
load can be picked up in a relatively short time, however,
hy opening the low-voltage disconnecting switch asso-
ciated with the deenergized transformer and then closing
the switch between the two bus sections. The entire load
of the substation, after this switching operation, is carried
through the one remaining transformer. If the fault is in
the deenergized transformer and not in its associated
supply circuit, the supply circuit can be reenergixed to
feed other stations connected to it after the disconneoting
switch on the high-voltage side of the defective transformer
has been opened. When the defective supply circuit or
transformer is repaired or replaced the transformer dis-
connecting switch should be closed before the bus sectional-
izing switch or breaker is opened to prevent dropping
load. To insure against operating the transformers in
parallel, except momentarily, it is best to use a bus-sec-
tionalizing breaker which automatically trips when both
low-voltage transformer disconnecting switches are closed. (a) (bl (cl
The substation illustrated in Fig. 10(b) is similar to
Fig. 11-Throw-over type distribution substations to auto-
that of Fig. 9(b) except that the transformer capacity is matically restore service and minimize the duration of service
divided between two banks and the low-voltage bus is interruptions resulting from subtransmission or transformer
normally operated in two sections just as described for faults.
the station of Fig. 10(a). This substation differs from that
of Fig. 10(a) in that the only time both transformers cannot Fig. 10(a) except for the use of breakers in the low-voltage
be used to supply the substation load is when one trans- leads of the transformers and between the two bus sec-
former fails. If a fault develops on a subtransmission cir- tions to obtain the automatic throw-over feature. The
cuit the associated transformer can be switched to the re- bus sectionalizing breaker is open under normal operating
maining supply circuit, after its low-voltage breaker has conditions. It is arranged to close automatically when
heen opened, thus making both transformers available for either of the transformer breakers open, and to reopen
carrying the substation load. In both of the substations when both transformer breakers are closed. This opening
of Fig. 10 the switching is so arranged that the two trans- of the sectionalizing breaker after both transformer break-
formers cannot be operated in parallel except momentarily. ers are closed has the advantage of not dropping load when
This reduces the short-circuit duty on the primary-feeder returning to normal operating conditions. Sometimes it
breakers when compared with the stations of Figs. 7(b) is objectionable to parallel the two supply circuits even
and 9(b) having the same load ratings. momentarily. Then the sectionalizing breaker is arranged
All substations discussed thus far have involved an to trip when there is about normal voltage on the low-
outage to all or a part of their load when a fault occurred voltage side of both transformers. The tripping of the
in a transformer or on the associated subtransmission cir- sectionalizing breaker in this case is arranged to close
cuit. The stations differ in the extent of the outage and whichever transformer breaker is open. When a supply
in the length of time required to restore service to the circuit or transformer fault occurs the associated supply
affected loads, and in each case the restoration of service circuit breaker trips. Because of loss of voltage the trans-
requires some manual switching. By additional expense a former breaker associated with the deenergized trans-
marked decrease in service restoration time can be secured former opens. The opening of this breaker causes the bus-
674 Distribution Systems Chapter 20

sectionalizing breaker to close and quickly reenergize the high- and low-voltage breakers are closed the low-voltage
deenergized bus section through the good transformer. bus sectionalizing breaker opens. This sectionalizing
Thus the half of the substation load that was dropped as breaker is arranged to close when either of the low-voltage
a result of the fault is automatically picked up within a transformer breakers are opened, and to open when both
second or two by connecting it to the good transformer of these breakers are closed if the voltage on the trans.
and subtransmission circuit. After the faulted supply cir- former side of both is about normal. This voltage check
cuit or transformer is repaired and about normal voltage prevents the accidental dropping of half the substation
is restored on the low-voltage terminals of the transformer, load should an attempt be made to return the transformer
the associated transformer breaker automatically re- to service by closing its low-voltage breaker without first
closes-either just before or just after the sectionalizing closing its high-voltage breaker. Should the resulting
breaker trips, depending upon the control scheme used- momentary paralleling of the two supply circuits through
thus restoring the station to its normal operating condition. the substation transformers be objectionable, the section-
In the station just discussed either a supply circuit or
a transformer fault results in the loss of half the trans-
former capacity until repairs can be made. By employing
both high-side and low-side throw-over in a two trans-
former substation as shown in Fig. 11(c) all transformer
t t
capacity can be utilized at all times except when a trans-
former fault occurs, just as in the case of the manual
throw-over station of Fig. 10(b). The low-side throw-
over functions similar to that of the station shown in Fig.
4 4
L _ 1

11(b). The high-side throw-over requires the use of three

I I-II- 1
high-voltage breakers connected as shown in Fig. II(c).
Normally the substation operates with both bus-sectional-
izing breakers open and with half of the station load sup-
1 1-r 1
plied over each subtransmission circuit and through each
transformer. The high-voltage sectionalizing breaker is
interlocked with the two high-voltage transformer break-
ers so that it closes when either of these breakers opens,
~~~‘l M
because of loss of voltage on its supply side, and opens (a) (b)
when both of these breakers close. If the momentary Fig. 12-Distribution substations with duplicate supply clr-
parallel of the two supply circuits resulting from this cuits to eliminate serviceinterruptionsdue tosubtransmisslon
method of control is objectionable, the sectionalizing break- faults.
er can be made to open when about normal voltage exists
on the supply side of both high-voltage transformer break- alizing breaker can be arranged to open when the voltage
ers. The opening of the sectionalizing breaker, in this on the supply side of both high-voltage transformer break-
case, causes the open transformer breaker to close. The ers is about normal. The opening of the low-voltage sec-
sectionalizing breaker is also equipped with overcurrent or tionalizing breaker causes the open low-voltage trans-
differential relaying inasmuch as it also functions as a former breaker to close.
transformer breaker when either supply circuit is de- Automatic-throwover distribution substations can rare
energized. When a supply-circuit fault occurs the circuit ly be justified except where the two subtransmission cir-
is disconnected from the system by the circuit breaker at cuits supplying the station cannot be paralleled and quick
its source end. The removal of voltage from the supply restoration of service is necessary after a supply circuit or
circuit causes the associated high-voltage transformer transformer fault occurs. To obtain the automatic-throw-
breaker to open. As a result the high-voltage sectionalizing over feature several more circuit breakers are usually rB-
breaker closes and reenergizes the deenergized transformer quired than in the substations previously discussed and
and low-voltage bus section over the good subtransmission the control of these breakers is relatively complicated.
circuit. Restoration of voltage to the faulty supply circuit Subst,ations can be built, using no more circuit breakers
after repairs are made causes the associated high-voltage and simpler relaying, that prevent even a momentary
transformer breaker to reclose and the high-voltage sec- service interruption when a subtransmission-circuit Or
tionalizing breaker opens and restores the station to its transformer fault occurs.
normal operating condition. TWO types of distribution substations ‘that continue to
When a transformer fails its associated high- and low- supply all of their load when a supply circuit fault OCCUR
voltage breakers are tripped by the overcurrent relays of are shown in Fig. 12. The two supply circuits for the
the high-voltage transformer breaker or by differential substation of Fig. 12(a) are connected to a high-volta@
relaying. They remain open until manually reclosed. The bus through circuit breakers. These breakers are norm&’
opening of the low voltage transformer breaker causes the controlled by directional-overcurrent relays that trip when
low-voltage bus-sectionalizing breaker to close and connect fault current flows from the substation high-vo!tage buS
half of the substation load, which was temporarily dropped, toward the power source. When a fault occurs on a suPPly,
to the good transformer. After the defective transformer circuit the associated high-voltage breaker at the su!-?
is repaired or replaced and its associated high-voltage or station and the breaker at bhe source end of the circuit trlP 1
Chapter 20 Distribution Systems 675

and disconnect the faulty circuit from the system. The modified by the addition of a high-voltage transformer
.&station continues to be supplied over the good sub- breaker as shown in Fig. 12(b) so that the supply-circuit
transmission circuit, with a voltage dip as the only disturb- breakers do not open when a transformer fault occurs.
%nceto its loads. The two high-voltage breakers at the Supply-circuit faults in this station are cleared just as they
sul&ttion are also equipped n-ith over-current relays, are in the station of Fig. 12(a), however, transformer faults
,vhich htlw a longer time setting than the directional- are cleared by the high-voltage transformer breaker. -1
transformer fault in either of the substations of Fig. 12
causes an interruption to the station load until the defec-
tive transformer can be repaired or replaced.
The loads supplied by substations shown in Fig. 13 are
not interrupted when a transformer or supply-circuit fault
occurs. In these stations the transformer capacity is di-
vided between two units so that if one transformer fails
the other carries the entire load. Each transformer prefer-
ably has a self-cooled rating equal to about 75 per cent of
the substation rating and should be equipped with auto-
matic air-blast as discussed in connection with the sub-
stations of Fig. 10.
A high quality of service with minimum equipment is
provided by the substation shown in Fig. 13(a). Each
transformer is operated as a unit with its associated sub-
transmission circuit and has only a disconnecting switch
on its high-voltage side. The breaker in the low-voltage
leads of the transformer is controlled by directional-over-
current relays arranged to trip when current flows from the
(a) (b) (cl substation bus toward the transformer. These relays are
given a short time setting and operate when a transformer
Fig. t3-Distribution substations with duplicate suppiy cir-
cuits and transformers to eliminate service interruptions due or supply-circuit fault occurs. The breaker is also equipped
to subtransmission or transformer faults. with overcurrent relays, with a longer time setting, to pro-
tect against low-voltage bus faults. When a supply-circuit
overcurrent relays previously mentioned, to trip both or transformer fault, occurs the associated low-voltage
breakers if the transformer fails. The opening of t,hese two transformer breaker opens. The breaker at the source end
breakers when the transformer fails may be objectionable of the supply circuit also opens and completely disconnects
hrcause the two supply circuits may be parts of a loop or the circuit and associated transformer from the system.
ring that should be continuous. The substation can be The substation of Fig. 13(b) provides the same qualit,y

Fig. 14-A 1500 kva open structure substation and a 3000 kva unit substation on a power system in the midwest. High voltage
-13.2 kv; low voltage-4160 volts.
676 Distribution Systems Chapter 20

of service as the station just described, however, both such faults in a modern unit substation is remote, and if
transformers remain in service when a supply-circuit fault small substations of 3000 kva or less are used the consem
occurs. To accomplish this a high-volt,age bus and three quences of thcsc bus falilts are minimized. They can be
high-voltage breakers, all of which are normally closed, further minimized by the design of the distribution sys-
are required, In addiCon to maintaining both trunsform- terns primary feeder layout, as discussed later. By the
ers in service when a supply circuit fault occurs, this sub- term modern unit substation is meant a complete substam
station differs from the station of Fig. 13(a) in that the tion factory built and tested. Such a substation usually
two supply circuits are tied together through the high- consists of one or more three-phase transformers equipped
voltage sectionalizing breaker with negligible impedance with automatic tap-changing-under-load, the necessary
between them instead of being connected through the im- high-voltage disconnecting switches or breakers, and the
pedance of the two substation transformers in series. low-voltage breakers and bus work. The switchgear se+
Such a tie with low impedance is necessary where the two tion or sections, containing all necessary disconnecting
supply circuits are parts of a subtransmission loop, ring, switches, buses, circuit breaker, relays, and auxiliaries, are
or grid. The two high-voltage transformer breakers are completely metal enclosed and mount on or bolt directly
equipped with directional-overcurrent relays to trip in the to the associated transformer or transformers. This gives
event of a supply circuit fault. Overcurrent relays, with a a completely metal-enclosed weatherproof substation con-
longer time setting, or differential relays are used to trip sisting of one or more sections that can be readily handled
these breakers on a transformer or high-voltage bus fault. as a unit or in sections and bolted together on the site.
The high-voltage bus-sectionalizing breaker is also con- Provision is usually made for bringing the subtransmission
trolled by overcurrent or differential relays to trip only and primary-feeder circuits into the unit or units under-
when a transformer or high-voltage bus fault occurs. The ground so as to avoid all overhead structures and conges-
low-voltage transformer breakers are relayed either sim- tion of overhead circuits near the station. If desired the
ilar to those of the station of Fig. 13(a) or with overcurrent smaller unit stations, instead of being installed outdoors,
and differential relays. The relay coordination in this sub- can be constructed for subway service and installed in
station, however, is such that each of these breakers trips vaults or manholes underground. Such construction is
only on low-voltage bus faults and on faults in its asso- usually very expensive but at times can be justified be-
ciated transformer and high-voltage bus section. Upon cause of the difficulty of obtaining a site for the substation
the occurrence of a supply-circuit fault the circuit is dis- in the neighborhood where it should be located. In certain
connected from the substation by the opening of the asso- locations it is necessary to enclose the unit substation
ciated high-voltage transformer breaker. The station load within an ornamental wall or building, which may have
is then carried over the good supply circuit and through the appearance of a private residence. In such installa-
both transformers. A transformer fault is cleared by the tions a standard outdoor unit substation can be used, or
high-voltage bus-sectionalizing breaker and its associated if it is located in a building the switchgear can be of unit
high- and low-voltage transformer breakers. This leaves indoor cubicle construction with the transformer or trans-
the substation load supplied through the good transformer formers bolted directly to it.
and over its associated supply circuit only. In building service reliability into a substation, and par-
It may be objectionable to have a subtransmission loop, ticularly into a relatively small station where the magni-
ring, or grid open on a substation transformer fault as tude of the outage is not too great, it should be remem-
\\ould occur with the station of Fig. 13(b). This can be bered that regardless of how much reliability is built; into
prevented by using four high-voltage breakers as shown in the substation a fault on a primary feeder energized from
Fig. 13(c). The two subtransmission breakers at the sub- the station bus will interrupt an appreciable amount of
station are relayed to trip by means of directional-over- load. Another thing to remember when selecting the type
current and overcurrent or differential relays to protect of distribution substation for a particilar job is that the
against supply circuit and high-voltage bus faults, respec- probability of a fault in a subtransmission circuit is much
tively. Each transformer may have its associated breakers greater than in a substation transformer. Also if the sub-
controlled by differential relays to protect against trans- station is small the amount of load thht may be affected
former failures. The low-voltage transformer breakers are by the subtransmission-circuit fault is much greater. Be-
equipped with overcurrent relays to protect against low- cause of these facts a few of the types of distribution sub-
voltage bus faults. A supply circuit fault is cleared from stations already discussed will take care of the majority of
t,he station by the associated subtransmission breaker at distribution requirements where relatitily small substa-
the substation. When a transformer fault occurs its high- tions are economical. In general small distribution sub-
and low-voltage breakers open and disconnect the trans- stations promote system flexibility. System studies indi-
former from the system. The substation load is then fed cate that such substations usually offer economic advan-
over both supply circuits and through the good trans- tages when considering the distribution system as a whole*
former. Sometimes, however, in congested areas with high load
In all of the distribution substations discussed a low- densities relatively large substations.of about 10 000 kva
voltage bus fault interrupts service to all or a part of the or larger are economical. Because of&e magnitide anp
substation load for a relatively long time until repairs can the importance of the load involved a high degree of rel*-
be made or the primary feeders can be temporarily con- ability is often built into these stations. These large sub-
nected to a portable substation. This is also true of a stations may be similar to some of the typ,es previoyslY
high-voltage bus fault in most stations. The likelihood of discussed, particularly those of Figs. 12 and 13. In vie’”
Chapter 20 Distribution Systems 6’7’7

of the seriousness of a bus fault in such a large substation changing-under-load on the substation transformer OI
it is sometimes desirable to use some type of double-bus transformers is often satisfactory for small substations,
s,lbstjation. One such station is shown in Fig. 15. This individual feeder regulators are usually required on some
st;Lt,ion is similar in layout and operation to the subst,ation or all of the primary feeders in the larger substnt,ions as
of Fig. 13(c), except for t,he double-bus feature. shown in Fig. 15. These regulators may replace automatic
Sormnlly the station is operated with all double-throw tap-changing-under-load on the substation transformers.
disconnecting switches or selector switches in the positions At times, however, it is economical to use the individual
feeder regulators only on the feeders whcrc needed to sup-
plement bus regulation.
In a large distribution substation similar to that of Fig.
15, or a less elaborate large substation laid out similar to
one of the stations of Fig. 13, the short-circuit current
MAIN SUS which the primary feeder breakers must interrupt becomes
very large. Also as the capacity of such a station increases,
AUX BUS
the short circuit duty on the primary feeder breakers in-
creases. As the station grows this duty may exceed the
interrupting rating of the original feeder breakers. This
high short-circuit duty on the primary-feeder breakers
MAIN BUS means relatively expensive feeder breakers.
A substation which provides substantially the same
AUX BUS quality of service and Tvith much lower short-circuit duty
on the primary-feeder breakers is shown in Fig. 16. Also
the station capacity can be increased indefinitely without
increasing the maximum short-circuit current the primary-
feeder breakers must interrupt. The marked reduction in
short-circuit duty on the primary-feeder breakers follows
because each transformer and primary feeder is opcruted
as a unit with all selector switches normally in the posi-
t t t t * t tions shown. Since the transformers are not paralleled on
Fig. 15-Distribution substation with high- and low-voltage their low-voltage sides the short-circuit current which each
double bus to permit isolating bus faults. primary-feeder breaker can be called upon to interrupt is
limited by the impedance of its associated transformer.
shown, so that all circuits and transformers are connected
to the two main buses. Differential relays associated with
the breakers in the subtransmission circuits at the substa-
tion and the high-voltage transformer breakers trip all of
these breakers when a high-voltage main-bus fault occurs
thus dropping the entire station load. Service can be re-
stored quickly to all loads, however, by closing all high-
voltage selector switches to their auxiliary-bus positions
and then reclosing the high-voltage transformer and sup-
ply-circuit breakers. This leaves the station with all
breakers in service and complete protection while the de-
fective bus is being repaired. Similarly a fault on the low-
voltage main bus is cleared by its differential relays trip-
ping all low-voltage transformer breakers and primary-
feeder breakers. The primary-feeder breakers need not be
opened if there is no possibility of a back feed over any
primary feeder. However, they are usually tripped as a
Fig. 16-Distribution substation with high-voltage double bus
matter of safety. Such a bus fault completely interrupts and low-voltage auxiliary bus and individual transformation
service to the substation load, but this load can be picked in each primary feeder resulting in relatively low interrupting
UP in a short time by closing all low-voltage selector duty on feeder breakers.
switches to their auxiliary-bus positions and reclosing the
low-voltage transformer breakers and the primary-feeder Each transformer is relatively small because its capacity
breakers. A normally closed bus-tie breaker can be used is equal to that of it,s associated feeder, which will usually
between the two low-voltage buses with half the primary be from 1000 to 2000 kva. To prevent a transformer fault
feeders ordinarily connected to each bus. This reduces the interrupting service to its associated feeder for a relatively
amount of load dropped when a low-voltage bus fault long time pending repairs or replacement an auxiliary low-
occurs by about one half, but it complicates the low- voltage bus is provided and arrangements are made so that
voltage bus relaying. any one primary feeder can be switched from its associated
While bus regulation in the form of automatic tap- transformer to the auxiliary bus. The auxiliary low-volt-
678 Distribution @sterns Chapter 33

age bus is energized through a spare transformer shown on station having only a single high-voltags bus such as the
the right in Fig. 16. This transformer is ordinarily of the station of Fig. 13(c) as well as to a double high-voltage bus
same capacity as each of the feeder transformers, because station. Such a substation, unlike most large stations, is
such a station is usually designed on the basis that only one very flexible in that its capacity can be increased econom-
primary feeder is connected to the auxiliary low-voltage ically in relatively small steps and thus kept close at all
bus at any one time. The saving in low-voltage breaker times to that required to serve its load.
cost may or may not be offset by the increased transformer Primary Feeders-As has already been explained a
cost. The transformer cost is increased primarily because radial type of distribution system usually is not radial
the transformer capacity is made up of a relatively large from the bulk power source or sources to the low-voltage
number of small units. Also since the transformers are not buses of the distribution substations. The primary feeders
paralleled on their load sides advantage cannot be taken of from the substation low-voltage buses to the primaries of
the diversity between primary feeders to reduce the station the distribution transformers, however, are in all cases
transformer capacity as is done in a substation such as that radial circuits, and the system is usually radial from the
of Fig. 1.5. This tendency to require more transformer substat,ion low voltage buses to the consumers’ services.
capacity is usually more than offset, however, by the much The radial primary feeders are principally responsible for
smaller spare transformer capacity required. The rel- the lack of service continuity provided by most radial dis-
at,ively large number of transformers required in such a tribution systems. A fault on any one of the radial pri-
station often would result in excessive high-voltage trans- mary-feeder circuits results in an outage to many consum-
former breaker cost. For this reason high-voltage fuses or ers. With the radial type of distribution system these
protective links as shown in Fig. 16 are ordinarily used service interruptions cannot be prevented. The amount of
with each small transformer. Except for this substitution load dropped when certain primary-feeder faults occur can
of fuses for breakers the high-voltage side of this station be decreased, however, and service often can be restored
is similar to that of the station in Fig. 15. Individual feed- promptly to all or a part of the consumers affected.
er regulation can be and usually is provided in a station of A simple form of primary feeder is shown in Fig. 17(a).
this type by means of automatic tap-changing-under-load The main primary feeder branches into several subfeeders
on each transformer. which in turn divide into a number of primary laterals so
The feature of unit operation of each primary feeder as to reach all of the distribution transformers in the arca
with its own relatively small transformer and one similar served by the primary feeder. The main feeder and sub-
spare transformer for all feeders can be applied to a sub- feeders are ordinarily three-phase three- or four-wire cir-

(b)
Fig. 17--Simple form of radial primary feeder.
(a) Without subfceder fuses. (21) With subfeeder fuses to reduce the number of
consumers affected by subfeeder faults.
Chapter 20 Distribution Systems 679

cuit:: and the primary laterals can be either three-phase or the primary-feeder breaker, the distribution transformer
single-phase circuits. Most primary laterals are usually fuses, and with each other so that the first fuse on the
single-phase circuit’s. The distribution transformers are supply side of the fault and only that fuse will blow. This
connected to the various parts of the primary feeder means that on any current flowing to a fault the fuse
through primary fuses or fused cutouts. These transform- adjacent to the fault must blow before any other fuse that
ers arc both three-phase banks and single-phase; however, carries the fault current will be damngcd. For any possible
the great majority of them are ordinarily single-phase. value of fault current all fuses must have a blowing time
When a fault occurs anywhere on the primary feeder less than the tripping time of the primary-feeder breaker.
of Fig. 17 (a) the primary-feeder breaker at the substation Where the percentage of permanent faults is large, as in
trips and dcenergizes all loads connected to the feeder. the case of cable feeders, sectionalizing the feeder with
Where the feeder is of overhead open-wire construction fuses will improve the quality of service rendered. On
the fault may be temporary, such as an insulator flashover feeders where most faults are temporary and where nuto-
or an arc between conductors which clears itself when the matic-reclosing breakers are used, such as overhead open-
primary-feeder breaker trips. In such cases when the wire feeders, the use of feeder-sectionalizing fuses is ques-
[ceder breaker is reclosed it remains closed. To restore tionable. This is because many fuse blowings will occur
service quickly when primary-feeder breakers trip on on temporary faults and cause an outage to a portion of
temporary faults these breakers, on overhead open-wire the feeder load until a complaint is received and the fuse
feeders, are usually equipped with automatic reclosing can be replaced. If sectionalizing fuses are not used the
relays. The reclosing relaying ordinarily provides for two entire feeder load will be dropped on these temporary
or three reclosures at intervals of several seconds. If the faults, but service will be restored to all loads in a fe\r
fault has not cleared itself after the second or third re- seconds by the reclosing of the feeder breaker.
closure it is in nearly all cases of a permanent nature and The objection to fusing these overhead feeders can be
the breaker trips a third or fourth time and is locked open. overcome, at least to a considerable estent, by using two-
>Iost temporary faults will clear themselves upon the first or three-shot repeater fuses. When repeater fllses are used
opening of the primary-feeder breaker, and to restore they must be closely supervised, otherwise they may be
service as quickly as possible in these cases the first re- left in operation with only one fuse unblon-n. Then when
&sure is often made without, any time delay. Experience another temporary fault occurs in the section an outage
indicates that in many cases 80 per cent or more of the to the load fed from that section will occur until the fuse
faults on open-wire primary feeders are temporary. This is replaced just as when using single fuses.
means in the majority of cases service can be quickly Perhaps a better method of overcoming the difficulty
restored when faults occur on such feeders by making the of having sectionalizing fuses blow on temportiry faults is
primary-feeder breakers automatic reclosing. If the fault to use single fuses and relay the primary-feeder breaker
on the primary feeder of Fig. 17 (a) is permanent, all of so that it trips substantially instantly on all feeder faults.
the feeder load is without service until the fault can be Thus when a fault occurs anywhere on the feeder the
located and repairs made. On an overhead open-wire cir- feeder breaker trips before any sectionalizing fuse has time
cuit that does not cover too large an area and contain too to blow. This first tripping of the breaker modifies its
many miles of circuit the fault can usually be located and relay control so that its second and subsequent trippings
repaired in a few hours. take place in the usual way only after some time delay.
If the conductors of the primary feeder of Fig. 17 (a) When the breaker recloses the first time it remains closed
are cables most faults on the feeder will be permanent. if the fault has cleared itself, and if not, fault current flows
Because of this an automatic-reclosing feeder breaker is long enough to blow the fuse adjacent to the fault on the
rarely used on a cable feeder. The likelihood of faults on supply side, Thus no fuse blowings occur on most tem-
such a feeder are much less than on an overhead open- porary faults because they clear themselves on the first
wire feeder; however, the time required to locate and deenergization of the feeder.
repair a cable-feeder fault will be much greater. This Permanent faults and the few temporary faults that do
mcans there will be fewer outages on such a feeder than not clear themselves when the feeder is deenergized the
on an open-wire feeder but all customers will be without first time are cleared by the sectionalizing fuses, and serv-
service for a much longer time when a fault occurs. It ice can be restored to the affected section or sections of
will often require a half day or more to locate and repair the feeder only after repairs, if any, are made and the fuses
~~11a fault. To reduce the number of consumers affected are replaced. This entire discussion of primary feeder
hy many of these long service interruptions the primary sectionalizing has been on the basis of using sectionalizing
feeder and its branches or subfeeders are often fused as fuses. Fuses are the most generally used sectionalizing
shown in Fig. 17 (b). When a fault occurs on a primary devices because of their relatively low cost. At times;
lateral or subfecder the associated subfeeder fuse blows however, circuit breakers, usually reclosing breakers, are
ml disconnects the faulty section from the remainder of used for this purpose.
the primary feeder. This confines the outage to only a The effectiveness of sectionalizing fuses in reducing the
portion of the feeder load and may decrease the duration extent of the outage when a primary-feeder fault of a
of the outage somewhat because less time may be required permanent nature occurs depends upon the location of
to locate the fault. the fault. The fault may be so located that two or more
In applying feeder and branch or subfeeder fuses care sections of the feeder or the entire feeder will be de-
must be taken that they are properly coordinated with energized until the fault is located and repairs are made.
680 Distributio,n Systems Chapter 20

To restore scrvicc quickly to unfaulted sections of a feeder, This procedure for switching loads between feeders has
which are deenergized along with the faulty section, pro- the advantage of not interrupting service to the loads on
visions arc sometimes made to permit temporarily sn-itch- the good feeder sections when they are reconnected to
ing such sections over to an adjacent primary feeder or their normal feeder. At the time of reconnection, the
feeders. One met,hod of doing this is shown in Fig. 18. feeders between which the loads are being switched are
Scctionn.lizing switches are used in conjunction n-ith the paralleled for a short time. This is usually not objection-
sectionalizing fuses shown in Fig. 17 (b), or the fuses can able, however, should a fault occur on either feeder at the
be omitted as in Fig. 17 (a) and only the switches used at time they are paralleled both feeders will be deenergized
the feeder sectionalizing points. By the use of these sec- if sectionalizing fuses are not used, and a section of the
tionalizing s\vit,chcs and the four tie switches shown all of unfaulted feeder will probably be dcencrgized even if fuses
the good sections of the central primary feed can be sup- are used. If it is felt that this short-time paralleling of
plied over the two adjacent feeders, and the faulty section feeders is objectionable the tie switches must be capable
of the central feeder can be completely isolated for repairs. of breaking load current.
The sectionalizing and tie switches can be of the clis- To avoid paralleling the feeders when reconnecting good
connecting type. If they are care should be taken not to feeder sections to their normal circuit their associated tie
interrupt load current with them. When the feeder, or a switches must be opened and their loads deenergized bc-
port,ion of it, is deenergized as the result of a fault the fore their sectionalizing switches are closed. Regardless
faulty sect.ion is first determined. The deenergized sec- of which switching procedure is used, it is safer to employ
tions are then disconnected from each other by opening load-break switches for both sectionalizing and tie switches
their associated sectionalizing switches. The good sections to eliminate the danger of opening a switch by mistake
arc reenergizctl from the adjacent feeders by closing the when load current is flowing through it. If primary feeders
tie switches. After the fault is repaired the faulty section are arranged so that their loads can be switched from one
is rcenergized by closing the feeder breaker or replacing feeder to another under emergency conditions, sufficient
the blown fuse and closing its associated sectionalizing spare capacity must be built into each feeder SO that it
switch, depending upon the location of the fault. Then can carry any load which can be connected to it. When
all open sectionalizing slvitches should be closed and the a feeder is carrying all or a part of the load of a defective
tie switches opened after this is done. By following this feeder it is usually advisable for economic reason to allow
procedure no switches are required to open load current. somewhat greater voltage drop over it than is satisfactory
However, the tie switches are required to open parallel under normal operating conditions.
paths over which current flows. Many interrelated factors affect the choice of rating for

: ? 0 1

\
‘SECTIONALIZING SWITCH’ 1SECTIONALIZING SWITCH ’

W 18-Simple form of radial primary feeder with tie and sectionalizing switches to provide for quick restoration of servffl
to consumers on unfaulted feeder sections.
Chapter 20 Distribution Systems 681

8 primary feeder. Some of the more important factors are factory voltage. Also at times of maximum load the volt-
the nature, density, and rate of growth of the load; the age drop from this point on the primary feeder to thr
necessity for providing spare capacity for emergency oper- consumers meter where the lowest voltage occurs must be
stion; t,he type and cost of the circuit construction which such that this lowest voltage is not too low to be satis-
must be used; the design and capacity of the associated factory. This total voltage drop should be divided among
substation; the type of regulating equipment necessary; the primary feeder, the distribution transformer, the sec-
:Lntl the quality of service required. Some kinds of loads, ondary circuit, and service so as to obtain the lowest over-
alch as wlders and arc furnaces, may have to be segre- all cost for these portions of the distribution system. The
g:lt,ed to a separata fecclcr or feeders to prevent their permissible voltage drop on the primary feeder between
&crsely affecting other loads. The amount of such load the first and last distribution transformers is usually about
in the area and the voltage requirements at the load in- 2 per cent or less at the time of peak load. This figure will
fluence the rating of the feeder or feeders. The rate of load of course be affected somewhat by the type of primary
growth and t,he provision for emergency operation affect and secondary construction used and by the permissible
the amount of spare capacity a feeder should have. In load voltage variation. If the voltage at the first trans-
:~cas of heavy load density it will usually be economical former on the primary feeder can be boosted by means of
to use larger capacity feeders than in the lighter load over-compensation as the load on the feeder increases the
density areas. The feeders are shorter, the circuits are permissible voltage drop is increased somewhat. The
,~sually of expensive underground cable construction with amount of overcompensation or boost in voltage permis-
low reactance per unit length, and the size and design of sible during maximum load without overvoltage at some
the substations are often such that higher interrupting consumers during light loads depends upon the uniformity
c:Lpacity and consequently more expensive feeder breakers of the loading of the distribution transformers. The more
:Lrerequired. The nature and density of the load together uniform the load on these transformers the more the over-
with the substation size also influence the type of regulat- compensation that can safely be used. When a primary
ing equipment selected. If individual feeder regulators are feeder is loaded to the point where the permissible volt-
necessary larger feeders are usually chosen, for economic age drop has been reached further load can be added, if
wasons, than when bus regulation is satisfactory. Rela- the current carrying capacity of the feeder has not been
tively small substations, usually found in medium and light reached, by installing a voltage booster or another feeder
load density areas, are ordinarily accompanied by smaller regulator in the feeder just on the supply side of the point
Feedersbecause of the lower cost of feeder breakers, the where the voltage drop becomes excessive when the addi-
:Lbsenceof individual feeder regulators, and the lower cost tional load is being carried. The consideration of feeder
:md higher reactance per unit length of circuit. The quality voltage drop when the feeder is supplied from a bus regu-
of service, in addition to some of the other factors men- lated substation is similar to that just described, except
tioned, will help determine the permissible feecler voltage that all primary feeders connected to the station bus must
Uference between the first and last transformers on the be considered as a unit. The allowable voltage drop on
feeder, or between the first and last transformers on the any feeder of the group is determined by the voltage differ-
group of feeders from a substation if bus regulation is used. ence between the high- and low-voltage points on the
The! amount of load that should be dependent on any one group of feeders, where distribution transformers are con-
primary feeder and interrupted when a feeder fault occurs nected, which will just give satisfactory voltage at all
is influenced primarily by the necessary quality of service. consumers at the time of peak load.
The various interrelated factors mentioned and others that The trend in the power-factor of loads in residential
:lffcct the proper rating for a primary feeder, can in general areas has been downward for some years. This is largely
be boiled down to two major factors, namely cost and because of the increasing use of motored appliances. The
qwlity of service. Cost considerations most often dictate lower power-factor loads on the parts of distribution sys-
the use of a relatively large feeder, and a high quality of tems serving these areas has aggravated the voltage regu-
service calls for a small feeder. After all factors have been lation problem. Shunt capacitors are used frequently to
carefully weighed to determine the economics and service improve voltage conditions on distribution systems. This
requirements the feeder capacity should be made as small improves the power-factor and thus reduces the voltage
2~ can be economically justified. Primary feeders ordi- drops and currents in the parts of a distribution system
narily vary in rating from about 500 to 2500 kva with between the capacitors and the bulk-power sources. To
most ranging between 750 and 1500 kva. get the maximum advantage from shunt capacitors they
The permissible voltage drop in a primary feeder is an should be connected to the system as near the loads as
important factor in its design. When a voltage regulator possible. For economic reasons they are usually connected
is used on the feeder the voltage at the primary of the to the primary feeders through primary fuses or fused
tlistribution transformer nearest the substation low-voltage cutouts. Whether the capacitors are connected to the
bus is maintained constant within about plus or minus one feeder proper or to its subfeeders or laterals depends upon
Per cent, or if overcompensation is used this voltage is the load and voltage conditions on the feeder. When ap-
increased somewhat as the flow of load current over the plying capacitors their ratings should be such that objec-
feeder increases. In order to provide satisfactory voltage tionable overvoltages do not occur, at light load periods,
conditions at all consumers the voltage maintained at the because of the voltage rise produced by the capacitor
above mentioned point must be such that at times of currents. To get the desired results from capacitors in
binimum load no consumer receives a higher than satis- certain installations it is necessary to connect them to the
682 Distribution Systems Chapter 20

system through breakers and arrange to automatically usually solidly connected to radial secondary circuits from
disconnect all or part of them at times of light load. which the consumers services are tapped as shown in Fig,
Series capacitors are also used on distribution feeders to 19. This means that no protection is provided the trans-
improve voltage conditions. However, they do not reduce former against overloads and high-impedance faults on its
the currents in the system and thus permit a saving in secondary circuits. Relatively few distribution trans-
system capacity as do shunt capacitors. The usual appli- formers are burned out by overloads. This is largely be-
cation of series capacitors is in relatively high reactance cause distribution transformers are applied so that full
circuits, supplying fluctuating loads, to reduce abrupt volt- advantage is rarely taken of their overload capacity.
ago changes. The capacitors are selected so their cnpaci- Another factor contributing to the small number of dis-
tive reactance about cancels the inductive reactance of the tribution transformer failures by overloads is the frequent
line. They are installed on the supply side of the location load checks often made and the corrective measures taken
where the improvement in voltage is desired. before dangerous overloads occur. Probably high imped-
Distribution Transformers, Secondaries, and ance faults on their secondary circuits cause more distribu-
Service.-The distribution transformers step down from tion transformer failures than do overloads. This is cer-
the distribution or primary feeder voltage to the utilization tainly true in localities where bad tree conditions exist.
Fuses in the secondary leads of distribution transformers
,PRIMARY FEEDER are little if any more effective in preventing transformer
burnouts than are primary fuses and for the same reasons.
The proper way to obtain satisfactory protection for a
distribution transformer against overloads and high-im-
pedance faults is by means of a breaker in the secondary
leads of the transformer. The tripping curve of this
breaker must be properly coordinated with safe current-
CONSUMER’S SERVICE SECONDARY CIRCUIT time curve of the transformer. The primary fuse must be
Fig. I9-Typical method of connecting distribution trans-
coordinated with the secondary breaker so that the breaker
formers between primary feeders and radial secondary circuits. trips on any current that can pass throllgh it before the
fuse is damaged. Faults on a consumer’s service connection
voltage. They are connected to the primary feeder, sub- from the secondary circuit to the service switch are so rare
feeders, and laterals through primary fuses or fused cut- that the use of a secondary fuse, where the service con-
outs as shown in Fig. 19. The primary fuse disconnects nection taps onto the secondary circuit, cannot be eco-
its associated distribution transformer from the primary nomically justified except in unusual cases such as large
feeder when a transformer fault or low-impedance sec- services from underground secondaries.
ondary-circuit fault occurs. The blowing of the primary As has been previously pointed out the allowable voltage
fuse prevents an interruption of service to other loads drop from the point where the first distribution trans-
supplied over the feeder, but interrupts service to all con- former connects to the primary feeder to the service switch
sumers supplied through its transformer. Fused cutouts of the last consumer supplied over the feeder should be
shown in Fig. 19, which are normally closed, provide a economically divided among the primary feeder, the dis-
convenient means for disconnecting small distribution tribution transformer, the secondary circuit, and the con-
transformers for inspection and maintenance. sumer’s service connection. Assuming a maximum voltage
Satisfactory overload protection of a distribution trans- variation of about 10 per cent at any consumer’s service
former cannot be obtained with a primary fuse, because switch the division of this drop among the various parts
of the difference in the shape of its current-time curve and of the system, at times of full load, may be about 2 per
the shape of the safe current-time curve of a distribution cent in the primary feeder between the first and last trans-
transformer. The shapes of the two curves are such that formers, 2.5 per cent in 6he distribution transformer, 3 per
if a small enough fuse is used to provide complete overload cent in the secondary circuit, and 0.5 per cent in the con-
protection for the transformer much valuable transformer sumer’s service connection. The fact that the voltage at
overload capacity is lost, because the fuse blows and pre- the primary of the first distribution transformer cannot
vents its being used. Such a small fuse also frequently ordinarily be maintained exactly accounts for the other
blows unnecessarily on surge currents. Because of this a 2 per cent. While these figures are typical for overhead
primary fuse should be selected on the basis of providing systems supplying residential loads, they can be expected
short-circuit protection only and its minimum blowing to differ considerably on underground systems where cable
current should usually exceed 200 per cent of the full load circuits and large distribution transfo .mers are used or
current of its associated transformer. where industrial and commercial loads 1 re supplied. The
Distribution transformers connected to overhead open- economic size of distribution transformer and secondary-
wire feeders are often subjected to severe lightning dis- circuit combination for any uniform load density and type
turbances. To minimize insulation breakdown and trans- of construction at any particular market prices can readily
former failures from lightning, lightning arresters are or- be determined once the total allowable voltage drop in
dinarily used with these transformers. The protection of these two parts of the system is determined. If the trans-
distribution transformers from lightning is discussed in former is too large the secondary circuit cost and total
Chapter 14. cost is excessive, and if the transformer is too small the
The secondary leads of a distribution transformer are transformer cost a,nd total cost is too larbe.
Chapter 20 Distribution Systems 683

With the distribution transformers and secondary cir-


cuits arranged as shown in Fig. 19 any one load is supplied
through only one transformer and in only one direction
over the secondary circuit. Because of this a suddenly
applied load, such as the starting of a motor, on a con-
sumer’s service can cause objectionable light flicker on
other consumers’ services fed from the same transfurmcr.
The increasing use in residential areas of motor-driven
appliances, such as washers, refrigerators, forced-air hent-
ing systems, and air-conditioning equipment, is resulting
in a considerable number of light-flicker complaints. In
some areas light flicker and not voltage regulation may
be the determining factor in the size and arrangement of
transformers and secondary circuits. The banking of dis-
tribution transformers is usually the best and most eco-
nomical means of improving or eliminating light flicker.
The term banking transformers means paralleling on the
secondary side a number of transformers all of which are
connected to the same primary circuit as shown in Fig. 21.
The secondary circuit arrangement in a banked trans-
former layout can take the form shown in Fig. 21, or it,
may be a loop or grid similar to that used in a secondary
network system. Because of this similarity in secondary-
circuit arrangements a banked-transformer layout is some-
times incorrectly referred to as a secondary net\vork sys-
tem. Banked transformers, because they are connected
to and supplied over a single radial-primary feeder, are a
form of radial distribution system; whereas a secondary
network loop or grid is supplied over two or more primary
&. .1 feeders which results in much greater service reliability.
Ranking of distribution transformers is not new and has
Fig. 20-Pole mounted, 5 kva, single phase, 60 cycle distribu-
tion transformer with single cover mounted high-voltage been used on a number of systems for many years. The
bushing-High voltage-7200 volts; low voltage-120/240 volts.
PRIMARY FEEDER

As in any other part of the distribution system, load FUSED CUTOUT


change or load growth must be considered and provided OR PRIMARY FUSE
-0ISTRl8UTION
for in the distribution transformers and secondary circuits. TRANSFORMER
~11~0,as wit,h other parts of the distribution system the ECONDARY FUSE
distribution transformers and secondary circuits are not
installed to serve only the loads existing at the time of
their installation but some future loads as well. It is not I i J 1 i i i I i I i J ’
CONSUMER’S SERVICE SECONDARY CIRCUIT
economical to make too much allowance for growth, how- (al
ever. When a distribution transformer becomes danger-
ously overloaded it can be replaced by one of the next
larger size if the current-carrying capacity of the secondary
circuit and the overall voltage regulation permit. If not,
another transformer of about the same size can be installed
between the overloaded transformer and the one adjacent
to it. When this is done load is removed from the over-
LSECONDARY FUSE --I
loaded transformer by connecting a part of its secondary
circuit and associated load to the new transformer. This (b)
also reduces the load on the secondary circuit of the over- Fig. 2l-Typical methods of banking transformers supplied
loaded transformer and improves the overall voltage regu- by the same radial primary feeder.
lation. If the load in the area is reasonably uniform trans-
formers may have to be installed on both sides of the conversion from the usual radial secondary circuit arrange-
overloaded transformer in a relatively short time to main- ment of Fig. 19 to the banked-transformer arrangement
tain satisfactory voltage conditions and prevent over- of Fig. 21 can usually be made simply and cheaply by
loading a part of the secondary circuit. The same result closing the gaps between the radial secondaries of a number
can be obtained, however, by installing one new trans- of the transformers associated with the same primary
former and moving the overloaded transformer so that feeder and installing the proper primary and secondary
it feeds into the center of its shortened secondary circuit. fuses.
684 Distribution Systems Chapter 20

Two major forms of protection have been used when primary fuse and the adjacent secondary fuses on each
banking distribution transformers. The arrangement side of it. Thus, unlike the previous arrangement, a trans.
shown in Fig. 21 (a) is probably the oldest and most former fault results in a service interruption to those con-
common. The distribution transformers are connected to sumers associated with the faulted transformer. A sec-
their primary feeder through primary fuses or fused cut- ondary-circuit fault is usually burned clear; however, if the
outs. These fuses should blow only on a fault in their fault persists for an unusually long time it is cleared by
associated transformer. All transformers are connected to the secondary fuses next to the faulty section and the
the common secondary circuit through secondary fuses. primary fuse associated with the transformer connected
The purpose of these fuses is to disconnect a faulty trans- to the faulty section. The secondary fuses are usually
former from the secondary circuit. The size of the second- selected SO that they operate even on a high-impedance
ary fuse must be such that it will blow on a primary fault fault, but the primary fuses are not for the reason previ-
between its transformer and the associated primary fuse. ously discussed in connection with the radial-secondary
Faults on the secondary circuit are normally expected to circuits. Thus even when a high-impedance fault occurs
burn themselves clear. To prevent frequent blowing of and hangs on, the secondary fuses adjacent to the faulty
secondary fuses on secondary-circuit faults these fuses section blow and prevent interrupting service on the good
should have relatively long blowing times on all fault cur- secondary sections. The transformer associated with the
rents. Their blowing times should not be so long, however, faulty section in this case, however, will be burned out.
as not to provide some degree of protection to their trans- In order to prevent this a secondary breaker whose current-
formers against secondary faults that do not burn clear time curve is coordinated with the safe current-time curve of
or require an unusually long time to do so. As previously the transformer can be used in the secondary leads of the
stated secondary fuses cannot be expected to protect trans- transformer. When such a breaker is used the secondary
formers satisfactorily against overloads and high-imped- fuses must be selected so that their blowing times for all
ance secondary faults. The use of a secondary breaker fault currentsare less than the tripping times of the breakers.
having the proper current-time characteristics is preferable Normally the two banking arrangements function alike.
to secondary fuses when banking transformers as shown They reduce or eliminate light flicker and improve voltage
in Fig. 21 (a) because greater protection is afforded the regulation or permit reduction in the amount of trans-
transformer against overloads and high-inpedance faults. former capacity necessary as compared with radial-second-
The secondary fuses or breakers should open in less time ary circuits. This improvement in voltage regulation or
than the primary fuses on any possible current so as to reduction in transformer capacity is the result of tying
prevent the blowing of primary fuses on a secondary fault. several radial-secondary circuits together and thus taking
A transformer fault is cleared by the transformer’s advantage of the diversity among a number of groups of
primary and secondary fuses without any interruption consumers. A considerable increase in the use of banked
to service. Most secondary faults will clear themselves transformers can be expected in the future because these
quickly. However, when a secondary fault hangs on for advantages often can be obtained at no increase in cost
a long time or fails to clear altogether several or all of the or a saving over the usual radial secondary-circuit
secondary fuses blow and some of the transformers may arrangement.
be burned out. Experience indicates that, where a careful
study of the fault currents to be expected is made and 2. The Loop System
the primary and secondary fuses are properly selected, The loop type of distribution system is used most
this method of banking operates with very lit.tle trouble. frequently to supply bulk loads, such as small industrial
Occasionally a secondary-circuit fault causes the blowing plants and medium or large commercial buildings, where
of all secondary fuses or the blowing of some secondary continuity of service is of considerable importance. The
fuses and the burning out of a few transformers. When subtransmission circuits of the loop ,system should be
this happens the extent of the service interruption is much parallel or loop circuits or a subtransmission grid as shown
greater than when radial secondary circuits are used. in Figs. 5 and 6. These subtransmission circuits should
The banking arrangement shown in Fig. 21 (b) is prefer- supply a distribution substation or substations similar to
able to that just described because there is no danger of those of Figs. 13, 15, or 16. The reason for this is that as
a complete service interruption to the banked area by a much or more reliability should be built into the system
secondary fault. It should be remembered, however, in from the low-voltage bus of the distribution substation
considering either of these arrangements that the possi- hick to the bulk power source or sources as is provided
bility of a secondary fault is considerably less than that of by the loop-primary feeders shown in Fig. 22. The use
a primary fault and that secondary faults are ordinarily in a loop system of a radial-subtransmission circuit or
infrequent. In this second arrangement the distribution circuits and a distribution substation or substations, which
transformers are connected to the primary feeder through may not provide good service continuity! does not give a
primary fuses just as in the first arrangement and for the well coordinated system. This is because a fault on *
same reason. The transformers are connected solidly to subtransmission circuit or in a distribution substation
the secondary circuit and the secondary circuit is section- transformer results in an interruption of service to the
alized between transformers by secondary fuses. These loads supplied over the more reliable loop-primary feeders
fuses are selected so that for any secondary-circuit fault The subtransmission circuits and distribution substations
they will blow quicker than any primary fuse. When a are often common to both radial- and loop-type distrib”-
transformer fails it is cleared from the system by its tion systems.
Chapter 20 Distribution Systems 655

One of the most common forms of loop-primary feeder any section of the loop is cleared by the circuit breakers
for supplying bulk industrial and commercial loads is at, the two ends of the faulty section and service is not,
sllo\\-n in Fig. 22 (a). Each end of the loop-primary fee&r interrupted to any secondary substation. As a feeder fault,
is connected to the dist,ribution subst,ation low-voltage bus can occur in one of the sections adjacent to the distribution
through a primary-feeder breaker. The feeder is run or substation bus the entire feeder load may have to be fed
looped through its load area and small industrial or second- in one direction over either end section of the feeder until
ary substations are connected to the loop feeder us~~ally repairs are made. Sufficient spare capacity must be bllilt
into the loop feeder to permit operating with either cnrl
DlSTRlBUTlON SUBSTATION
LOW VOLTAGE BUS
section out of service without excessive voltago drop or
overheating of the feeder. A fault in a secondary slob-
station transformer is cleared by the circuit breaker or fuse
1 FLOOP PRIMARY FEEDER4 1
in its primary leads and the loop feeder remains intact. If
f” no transformer primary breaker or fuse is used such a
transformer fault must be cleared by tripping the two
sectionalizing breakers adjacent to the faulty transformer.
Tn this case the loop is opened and must remain open until

+If DISTRIBUTION “r
the defective transformer is disconnected from the loop.
Obviously a transformer fault in a single-transformer
secondary substation results in an interruption of service
to all loads fed from the station. Such a fault is much
TRANSFORMER
less likely than a primary-feeder fault. In some cases the
resulting service interruption may be serious enough, how-

I ever, to justify a more elaborate form of secondary sub-


station, such as those shown in Figs. 13 (b) and (c). -4
fault on one of the radial secondary feeders from a second-
ary substation is cleared by the tripping of the air circuit
T breaker associated with the faulty feeder. This interrupts
“y” service to those loads connected to that feeder until the
Ti (b) fault can be located and repaired.
The investment in sectionalizing breakers and relaying
Fig. 22-Two frequently used formsof the loop primary feeder.
may make a loop system employing primary feeders similar
(a) Two sectionalizing breakers per secondary sub- to that of Fig. 22 (a) more expensive than the necessary
station to isolatcx a faulted loop section without
quality of service justifies. If an outage to a secondary
interrupting service to any load.
(6) One sectionalizing breaker per secondary substa-
substation can be tolerated when a primary-feccler fault
tion for use where interrupting one load when LYL occurs a loop-feeder arrangement can be used as shown
loop section fault occurs can be tolerated. in Fig. 22 (b). Here only one sectionalizing-breaker is used
with each secondary substation thus reducing the number
through circuit breakers or fuses in the primary leads of of these breakers to half of the number used in Fig. 22 (a).
the substation transformers as shown. These transformers, The sectionalizing breakers are relayed as discussed in
\\-hich step down from the distribution to the utilization connection with Fig. 22 (a). When a primary feeder fault
voltage, are ordinarily relatively large distribution trans- occurs the two breakers at the ends of the faulty section
formers. Because these secondary substations are usually open as in the previous arrangement. In this case, how-
considerably smaller than a distribution substation only ever, the secondary substation associated with the faulty
one three-phase or one bank of single-phase transformers section is deenergized because its transformer is tied di-
is used ordinarily as shown in Figs. 12 (a) and (b). In rectly to the feeder section through a disconnecting switch,
these secondary substations the low-voltage feeders are a primary transformer breaker, or a fuse. Service to the
operated at a utilization voltage of 600 volts or below and deenergized substation cannot be restored until the fault
they are commonly controlled by air circuit breakers. has been located and repairs have been made.
These secondary feeders are usually radial dircuits that There is one exception to the above. A fault in the left
run directly to large motors, to power panels, and to feeder section just beyond the distribution substation bus
lighting panels or small lighting transformers. does not interrupt service to any of the secondary sub-
The loop-primary feeder is sectionalized by a circuit stations. The sectionalizing breaker associated with this
breaker on each side of the points where secondary sub- line section and the adjacent secondary substation can be
stations are connected to it. The two primary-feeder omitted, and then this substation is deenergized at the
breakers and the sectionalizing breakers associated with time of a fault in this section. Whether omitting this
the loop feeder are ordinarily controlled by directional- breaker appreciably reduces the continuity of service to
overcurrent relays or by pilot-wire relays. Pilot-wire relay- this first substation connected to the loop, when going
ing is used where the number of secondary substations from left to right, depends on whether its associated loop
connected to the loop is such that selective timing cannot section becomes much longer than the other loop sections.
be obtained with directional-overcurrent relays. Except for primary-feeder faults this system functions
With this loop primary feeder arrangement a fault on similar to the loop system previously described.
686 Distribution Systems Chapter 20

Sometimes a consumer connected to the loop requires A third way of improving service is to supply the con-
more reliable service than the arrangement of Fig. 22 (b) sumer through a single-transformer substation arranged
provides. Service to this consumer can be improved in so that it can be connected to either side of its associated ,
several ways. Two sectionalizing breakers can be used, sectionalizing breaker by a double-throw switch or two
one on each side of the point where the secondary sub- interlocked disconnecting switches. Service will then be
station that serves him is connected to the loop, as shown interrupted to the secondary substation when a fault
in Fig. 22 (a). Another way is to divide the transformer occurs in the loop section to which the station is normally
capacity of the secondary substation serving this consumer connected. The station loads can be quickly recnergized,
into two units, and connect one of these units or trans- however, without waiting for repairs, by connecting the
formers to the loop feeder on each side of the single sec- substation to the good section of the loop on the other
tionalizing breaker. Each of these transformers should side of the open sectionalizing breaker.
have sufficient capacity to supply the entire station load The above discussion of the loop system has been on
and is usually connected to the loop feeder through a cir- the basis of supplying relatively small bulk loads from
cuit breaker or fuse. The two transformers are ordinarily distribution substations over loop primary feeders. In
bused on the secondary side through transformer-second- many cases, however, where the bulk loads are relatively
ary breakers. When this arrangement is used a feeder large the loop is a subtransmission loop supplied directly
fault in either of the two loop sections immediately adja- from a bulk power source. In such systems the distribution
cent to the sectionalizing breaker results in the deenergiza- substations and primary feeders are omitted and only one
tion of one of the two transformers at the sub-station. voltage transformation is employed in going from sub-
This is because the sectionalizing breaker at the station, transmission to utilization voltage. This transformation
the sectionalizing breaker at the far end of the faulty is made at the secondary substations, which are usually
section, and the breaker in the secondary leads of the considerably larger and somewhat more elaborate than
transformer connected to the faulty section are tripped. those employed on 2400 to 4800 volt loop-primary feeders.
When this happens the secondary substation load is fed The arrangement of the subtransmission loop and its con-
over the good loop section which is adjacent to the open trol and protection is in general similar to that discussed
sectionalizing breaker at the station, and its associated in connection with the loop-primary feeders of Fig. 22.
transformer. Any form of loop system normally provides a two-way

TRANSFORMER 7

\SECTIONALIZING BREAKER

Fig. 23-Common arrangement of loop primary feeder for supplying distributed loads.
Chapter 20 Distribution Systems 687

feed to the distribution transformers or secondary sub- by opening the sectionalizing switch or switches asso-
shtions. In general, the service continuity and voltage ciated with the faulty section and then reclosing one of
regulation provided is better than when using a radial both of the tripped breakers depending upon the location
system. The amount by which the quality of service of of the fault. Faults on the subfeeders and laterals arc
the loop system exceeds that provided by the radial system cleared by their associated primary fuses. These fuse
depends upon the particular forms of the two systems operations do not interrupt service to any of the feeder
being compared. Ordinarily the loop system will be more loads except those beyond the blown fuse on the sub-
cspensive than the radial system. Also it is usually less feeder and laterals. .1s in the case of the loop feeders or
flexible than the radial system particularly in the forms Fig. 22 this loop-primary feeder should be designed to
used in supplying bulk loads discussed above. This is permit its carrying all loads that can be connected to it
principally because two circuits must be run to each new when any section of the loop is out of service.
secondary substation location in order to connect the
station onto the loop. The addition of new substations on
a loop feeder also often results in relaying complications. REFERENCES
While the loop system has been discussed from the
1. OverheadS@emsRefererlceBook, National Electric Light Asso-
standpoint of supplying bulk industrial and commercial ciation, New York, 1927.
loads it is also used to supply distributed loads such as 2. Underground Systems Reference Book, National Electric Light
residential loads. The chief reasons for supplying such Association, Sew York, 1931.
loads from a loop system rather than a radial system are 3. Electrical Distribution Engineering (a book), by Howard P.
to improve voltage conditions, to equalize the load on and Seelye, &lcGraw-Hill Book Company, Inc., New York, 1930.
take advantage of the diversity between what would other- 4. Electric Distribution Fundamentals (a book), by Frank Sanford,
wise be two radial primary feeders, and to assist in the McGraw-Hill Book Company, Inc., New York, 1940.
restoration of service to the unfaulted portions of a 5. Variable Elements in the Cost of Distribution of Electrical
faulted feeder. Energy, by Norman H. Gibson, E.E.I. Bulletin, June 1933.
6. Fundamentals of Design and Electric Energy Delivery Systems,
A common arrangement of a loop-primary feeder for
by J. Allen Johnson and R. T. Henry, A.T.E.E. Transactions,
supplying distributed loads is shown in Fig. 23. The Vol. 53, 1934, pp. 1704-1711.
similarity between this loop-feeder arrangement and the 7. The Effects of Service Standards on System Design, by N. E.
radial-primary feeders of Fig. 18, where emergency ties Funk, E.E.Z. Bulletin, July 1935.
are provided between adjacent feeders, is apparent. 8. Firm Ratings as a Guide to System Loading and Design, by
Each end of the loop-primary feeder is connected to the S. hI. Dean, E.E.I. Bullelin, June 1936.
low-voltage bus of its distribution substation through 9. Trouble Analysis and Power System Economics, by W. B.
primary-feeder breakers. The main feeder is automati- Elmer, E.E.I. Bulletin, October 1937.
cally sectionalized near its midpoint by a sectionalizing 10. Considerations Involved in Making System Investments for
breaker controlled by overcurrent relays. Manual sec- Improved Service Reliability, S. M. Dean, E.E.I. Bulletin,
November 1938.
tionalizing switches are provided at other points in the
11. System Service and Economy, Electrical World, November 10,
main feeder as shown in order to reduce the area that 1934.
must remain without service, until repairs are made, 12. Trends in Power Distribution, Electrical World, May 23, 1936.
when a fault occurs on the main feeder. Fuses are not 13. Urban Distribution Symposium, Electrical West, i\Iay, 1939.
used in the main-feeder loop. The sectionalizing breaker 14. Progressive Distribution, by Merril Dc Merit, Electrical World,
could be replaced with fuses at some sacrifice in the speed April 27, 1935.
of restoring service, but not more than one set of fuses 15. System Planning to Save Millions in Fiscd Charges, Electric
should be used in the loop because they will not operate Light and Power, November 1933.
selectively for feeder faults in various locations. More 16. Pertinent Facts in Primary Distribution Economics, by D. K.
than one automatic sectionalizing breaker could be used Blake, Electrical World, April 22, 1933.
in the main loop with directional-overcurrent or pilot- 17. Save Money on Secondary Distribution, by D. K. Blake, Elec-
frical World, September 23, 1933.
\vire relaying, as was done in Fig. 22, to reduce the extent
18. Can Distribution Cost Be Cut 40 Per Cent?, by AIerril De
of the outage when a main feeder fault occurs. The im- llerit, Electric Light and Power, April, 1935.
provement in the quality of service obtained, however, 19. Distribution Service and Costs, by M. M. Koch, Electrical
is not ordinarily sufficient to justify the additional break- World, March 16, 1935.
ers and the more complicated relaying. The subfeeders 20. Cutting Distribution Costs, by John S. Parsons, Electric Jour-
are provided with primary fuses or fused cutouts as in nal, March 1935.
the case of the radial-primary feeders previously dis- 21. Facts on Distribution Costs, by Howard P. Seelye, Electrical
cussed. When a fault occurs on the main feeder loop the World, June 20, 1936.
sectionalizing breaker opens quickly and splits the loop 22. Practical Distribution Economics, by H. S. St. John, Electrical
feeder into two radial feeders, The primary-feeder break- World, September 7, 1940.
23. Secondary System Economy, by Howard P. Seelye, Electrical
er associated with the faulty half of the loop feeder then
World, October 12, 1935.
opens and disconnects the fault from the system. This 24. 1Iodernization of Power Distribution Systems, by Howard P.
results in an interruption of service to about half the Yeelye, -4.I.E.E. I’ransactions, 1936, pp. 75-84.
10th normally supplied over the loop-primary feeder. 25. Cost Reduction and Reliability Keynotes Two Decades of
Service can be quickly restored to all deenergized loads Distribution Progress, by A. C. Montcith, Electrical South,
except those connected to the faulty section of the feeder February 1941.
688 Distribution Systems

26. Distribution Planning, by C. E. Arvidson. 41. A Graphical Method of Calculating Voltage Drop, by V. w.
Part I-Calculating Overhead Primaries, Electrical World, Palen, Elecfric Light and Power, January, 1938.
October 7, 1933. 42. Primary Limits; Application of Fcedcr Voltage Regulators, hy
Part II-Rcsitlcntial Loads, Diversities, Electrical IVorZd, Octo- R. 0. Loomis, Electrical TVorZd, November 2, 1940.
her 21 1939. 43. Regulation Beyond the Distribution Substation, by P. E
Part IIIlDcsign of Radial Primaries, Electrical IliorZd, Sovem- Benner, A.I.E.E. TTMWX~~O~S,1935, pp. 832-37.
ber 4, 1339. 44. Automatic Boosters on Distribution Circuits, by Leonard ~1.
Part IV-Fixing Regulator Settings, EZK~T~CUZ World, Novem- Olmsted, A.I.E.E. Transactions, 1936, pp. 1083-96.
her 18, 1933. 4,5. Applying Shunt Capacitors to Distribution Systems, by Shcr-
Part V-Transformer-Secondary Design for Service, Electrical win Wright, Electric Journal, ;1Iay 1937.
FVorZd, December 2, 1939. 46. Capacitors Increase Distribution Capacity, by Sam H. Pollock,
Part VI-Checking Transformer and Secondary Conditions, Electrical WorZd, September 24, 1938.
EZeclricaZ World, Dcccmber 16, 1939. 4i. Basis for a Program of Capacitor Additions on a Growing
27. T,ight, Portable Substation Affords Continuous Service, by 31. Distribution System, by V. G. Rettig, E.E.Z. Bulletin, August,
.J. Wohlgemuth and W. W. Richardson, EZeclricuZ World, 1940.
November 4, 1939. 48. Capacitors-Design, Application, Performance, by hl. C.
28. Tmmcdiate Automatic Reclosing of Circuit Breakers, by W. J\2. Miller, Electric Light and Power, October, 1938.
Emmons, Eleclric Journal, hIarch 1935. 49. Current Control Broadens Capacitor Application, by A. D.
29. Economic Design of Overhead Primaries, by Paul II. Jeynes, Caskey, Electric Light and Power, February, 1940.
E.E.I. Bulletin, May, 1938. 50. Application Data on Series Capacitors, by V. W. Palen, Electric
30. The Gathering and Evaluation of Data for Improving 4-Kv Light and Power, March, 1940.
Dist,ribution System Operation, by Harold E. Deardorff, 51. Series Capacitors Perform as Voltage Regulators, by V. W.
E.E.Z. Bulletin, July, 1938. Palen, Electric Light and Power, April, 1940.
31. A Review of Overhead Secondary Distribution, by W. P. 52. Reclosing Breakers or Reclosing Fuses-Which?, by H. A. p,
Holben, A.I.E.E. Transactions, 1937, pp. 114-122 and 189. Langstaff, Electrical World, March 22, 1941.
32. Banking Transformers Improves Service, by M. T. Crawford, 53. Recent Developments in Cable Fault Locating, b$ James A.
E’ZecfricaZ World, November 23, 1935. Vahey, E.E.I. Bulletin, March, 1939.
33. Light Flicker Reduced at Low Cost, by B. E. Ellsworth, 54. Economic Benefits of Scientific Line Clearing, by T. H. Hainca
Electrical World, November 23, 1935. and E. F. Robinson, EZectricaZ World, January 14, 1933.
34. Secondary Voltage Dips, by Paul H. Jeynes, Electric Journal, 55. Tree Clearance for Overhead Electric Lines-Preliminary Sug-
June, 1936. gestions, by G. D. Blair, E.E.Z. BuZZelin, August 1941.
35. Banking Secondaries, by P. E. Benner, Electric Light and Power, 56. Realigning Transformers with Distribution, by W. A. Sumner
April 1939. and J. B. Hodtum, Electrical World, June 22, 1935.
36. Trends in Distribution Overcurrent Protection, by G. F. Lincks 57. Choosing Transformer Sizes for Distribution Circuits, by R.
and P. E. Benner, A.I.E.E. l’ransaclions, 1937, pp. 138-52. Rader, Electrical World, January 16, 1937.
37. Systematic Voltage Survey-Procedure and Application to Dis- 58. Maximum Allowable Loading on Distribution Transformers, by
tribution Design, by R. W. Burrell and W. E. Appleton, Howard P. Seelye and N. A. Pope, E.E.I. Bulletin, 1939.
A.I.E.E. Z’ransactions, 1938, Vol. 57. 59. Loading Limits for Distribution Transformers, Erik N. Nelson
38. Voltage Drops in Radial Overhead Distribution Circuits, by and J. Edwin Davies, Electrical World, October 19, 1940.
W. R. Bullard, E.E.I. Bulletin, November, 1940. 60. Distribution Transformer Load Testing Methods Used by the
39. Voltage Drop in Distribution, by E. hl. Adkins, Electrical Detroit Edison Company, by W. E. Groves, E.E.I. Bulletin,
TYorZcZ,September 12, 1936. February, 1939.
40. Is Good Voltage Regulation Necessary and Practical?, by L. A. 61. Field Testing of Distribution Tracsformers, by J. A. Tenbrook
Buese and Frank A. Ayres, Electrical West, December, 1934. and L. R. Gaty, E.E.I. Bulletin, February, 1939.
CHAPTER 21

PRIMARY AND SECONDARY NETWORK DISTRIBUTION SYSTEMS


()riqitml Authors: Recised by:
John S. Parsons and H. G. Barnett John S. Parsons and H. G. Barnett

the a-c low-voltage network the recognized ideal distribu-


I. DEVELOPMENT OF THE A-C NETWORK tion system for highest quality of service’“,?“. In henvy-
SYSTEMS load areas the network usually was cheaper than any other
XRLY in the history of electric power distribution

E
system that attempted to give a high degree of reliability.
systems the d-c network system became the best In 1926 seven cities used the network and by 1949 the
m&hod of serving loads in heavy load density number had grown to 196.
areas of cities where a high degree of reliability was re-
cluired. In the d-c network system power was carried at 2. The Primary Network
~ltilization voltage from several substations to points in The attractive characteristics of the automatic low-
the load area where the power was introduced into an inter- voltage a-c network suggested the application of the net-
connected grid of mains in underground ducts. Individual work principle to the primary-feeders of a distribution
loads were supplied by services tapped off the mains. The system. As early as 1926 consideration was given to a
several paths of supply to the grid and the fact that there primary network in which the distribution-system pri-
were normally two or more paths in the grid to any service mary feeders would form interconnecting ties between
prevented service interruptions except for complete failure distribution substations, network relaying would be used
of power supply. As the load density and total load in- at the distribution-substation transformer breaker, and
creased in d-c network areas the large amount of copper re- selective operation of feeder breakers would provide correct
quired, the cost of substation sites, and large, rotating con- isolation of primary-feeder faults.
version equipment made the cost of the d-c network practi- The development of an overcurrent relay with satis-
cally prohibitive. The noise of the conversion equipment factory inverse-time characteristics and the choice of
made it difficult to find satisfactory locations for substations. relatively small substations facilitated the first economic
application of the primary network in the Pittsburgh area
1. The Secondary Network in 19317Jo.11J2.For areas of medium load density the pri-
mary network frequently was the most economical system,
The characteristics of the network system, particularly particularly where overhead construction was used. After
reliability and the fact that the network took full advan- the first installation in 1931 there was a gradual increase in
tage of diversity among loads, made that system prefer- the number of primary network installations; in 1942 twelve
able if it could be installed economically. The relative utilities were operating primary networks and thirteen
compactness and the quietness of transformers suggested others had installed unit substations with primary-net-
the use of an a-c network system in which several high- work relaying so that primary-network operation could be
voltage feeders would be carried into the load area to sup- initiated simply by completing tie circuits between sub-
nly transformers feeding into an interconnected grid of stations.
low-voltage conductors. By 1920 there was considerable
thought being given to such a system. Some experimental II. THE PRIMARY NETWORK SYSTEM
installations using fuses for protecting a low-voltage a-c
network proved to be unsatisfactory because of the operat- 3. General Description
ing limitations of fuses and possibly because of the lack A typical arrangement of a primary network system is
of estremely careful design. This experience showed that shown in Fig. 16,g. Basically a primary network is a system
directional control of power flow was required to prevent a of interconnected primary feeders supplied by two or more
fault in a transformer or primary feeder from interrupting subtransmission circuits through several distribution sub-
service from the system. stations or network units located at the intersection points
In 1922 the first automatic low-voltage a-c networkI of the interconnected feeders. Usually there are radial
lvas installed using equipment which was subsequently primary-feeder taps from the tie circuits between the
improved by Westinghouse developments1g~20. With low- primary-network unit substations, and in many cases ra-
voltage a-c network transformers and network protectors dial primary feeders originate at the substation buses. Dis-
perfected, the a-c network system equalled the d-c network tribution transformers are connected to the tie circuits, to
system in reliabilityls. This high degree of reliability plus the radial taps off the tie circuits, and to the radial primary
good voltage regulation, the convenience and comparative- feeders out of the substations just as in a radial system.
lY low cost of alternating-current equipment, and the Two or more subtransmission circuits are taken into the
flexibility of the network system for load growth made primary-network area to supply the several primary-net-
689
690 Primary and Secondary Network Distribution Systems Chapter 21

\ /PRIMARY NETWORK UNIT


-.-_ .--1
-I- Ei-
AL
\
w
PRIMARY SUB-FEEDER
+
I
-. e
t-
f i CRADIAL PRIMARY
P
FEEDER
-,

TIE FEED ‘ER I

DISTRIBUTION
TRANSFORMER

------I SUBTRANSMISSION CIRCUIT I /’


SECONDARY MAINS
I
i
Fig. 1-Typical primary-network arrangement using breakers at each end of each tie feeder.
.
work substations. Because the distribution feeders are cuits between major bulk power substations or between
interconnected, power is supplied to all distribution trans- generating plants and bulk stations. Primary-network
formers on the primary feeders even though part of the units also can be tapped from radial circuits supplying
subtransmission circuits feeding the network units is out other loads such as bulk substations, industrial loads, or
of service. Usually it can be assumed that not more than small radial substations. In practice, the circuits supply-
one out of any five or six s&transmission circuits supply- ing primary-network units range from 11 to 33 kv de-
ing a primary network will be out of operation at any pending on the subtransmission voltage in the power
time. Therefore, the primary network must be able to system where the network is installed.
carry the total load in the network area, when any one The primary-network units or unit substations located
subtransmission circuit is out of operation, without seri- at the intersections of the tie circuits generally have lea
ously overloading any network-unit transformer or any capacity than the substations used in a radial system; the
tie circuit. This can be accomplished with the least total network unit usually has a rated capacity between 1000
transformer capacity when the subtransmission circuits and 3000 kva. Frequently the transformers are provided
are interlaced so that every transformer connected to a with air-blast equipment to increase their capacity for
supply circuit is surrounded by transformers connected emergency operation when part of the network units are
to other subtransmission circuits. out of operation or during infrequent short intervals of
Subtransmission circuits supplying a primary network abnormally high peak load. Each small unit is located as
can be simple radial circuits without impairing the relia- near as practicable to the load center of an area comprising
bility or operation of the network., This permits simple a total load demand corresponding to the capcity of the
relaying for protecting the subtransmission circuits. Under substation. This keeps to a reasonable minimum th?
certain conditions the supply for primary-network units average length of primary feeder between the distributlO?
can be tapped from subtransmission loops or from tie cir- substation and the distribution transformers. Thus, the
‘,,,
I
Chapter 21 Primary and Secondary Network Distribution Systems 691

oo\\-er is carried as close as is reasonably possible to the transformer and the transformer breaker are fundamen-
loads at subtransmission voltage with consequent mini- tally the same. In both forms the primary-feeder breakers
nlum loss and voltage drop in the primary feeders. are controlled by ovcrcurrent and reclosing relays. In the
The primary-network unit consists of the transformer to arrangement shown in Fig. 1 a fault on a primary tie
reduce subtransmission voltage to primary-feeder voltage feeder is isolated by the breakers at the ends of the faulted
and the necessary switchgear to protect service from the circuit. In the other form of the system, Fig. 2, a similar
network and to control the distribution feeders. The fault is isolated by the transformer breaker at the end of
transformer breaker is provided with network and over- the faulted section of the tie circuit and the breakers in all
current relaying so that it not only opens on reversed cur- the tie feeders connected to the transformer whose breaker
rents to faults in the associated transformer or in the sub- opens. The chief advantage of the original form of the
transmission circuit supplying that transformer but also primary network is that less load is interrupted by a tie
serves as back up protection for the feeder breakers and feeder fault than in the later form using mid-tic breakers.
iSolL$teS intersection faults. Furthermore, the network In a case where four tie circuits are connected to each unit
relaying functions to close the main breaker when the a tie-circuit fault in the original form interrupts only half
transformer voltage is such that power flows into the pri- as much load as does a similar fault in the other form.
mary feeders when the breaker is closed. However, the system using mid-tie breakers uses only half
There are two general forms of the primary network de- as many tie breakers as does the original form.
pending on the location and number of breakers in the tic
circuits. The original form uses two breakers in each tie 4. Operation of Network with Two Breakers Per Tie
circuit, one at each end as shown in Fig. 1. The other form The operation of the primary network with two break-
IWS one breaker, normally near the middle of each tie crs in each tie circuit is described best by reference to Fig.
circriit, as shown in Fig. 215. In the two forms the network 1. Under normal conditions all network units are in serv-

,PRIMARY NETWORK UNIT

=-RADIAL PRIMARY
FEEDER
TRANSFORMER
BREAKER

DISTRIBUTION
1

r’--‘--‘--‘1

y SUBTRANSMISSION CIRCUIT SECONDARY MAINS

Fig. a--Typical primary-network arrangement using one breaker at the middle of each tie feeder.
692 Primary and Secondary Network Distribution Systems Chapter 21

ice and the load is divided among the various units. Under are isolated from the system by the overcurrent tripping
fault conditions the faulted element of the system is iso- of all tic-feeder breakers connected to the faulted bus
lated without interrupting service from the rest of the breakers c, e, f, and g for fault C. The overcurrent relaYA
network. for breaker g not only trip and lock out that breaker but
Supply-Line Faults are isolated by the breaker at the also trip and lock out all the feeder breakers COnneCted to
supply end of the subtransmission circuit and the trans- the same bus. This prevents the tie-feeder breakers re-
former breakers in the network units connected to the closing and reenergizing a bus fault and causing unnece&
faulted circuit. For example, the subtransmission-line snry damage to the switchgear unit. The transformer
fault at 8, Fig. 1, is isolated automatically by opening the breaker operates just as it does for a bus fault when 8
circuit breaker at the supply end of the faulted circuit and primary-feeder breaker fails to open and clear a feeder
transformer breaker a. In an extensive network system fault. The time setting for the transformer breaker ia
a subtransmission circuit may supply several network units longer than that for the feeder-breaker relays so that the
and the transformer breakers in all these units open to transformer breaker can provide back up protection for
isolate a fault on the supply circuit. The transformer the feeder breakers and still give the feeder breakers ample
breaker a, Fig. 1, opens on reversed current through the time to operate correctly. For example, if breaker d
transformer from the network to the supply circuit. If a should fail to open for a fault on its associated feeder the
subsequent reclosure of the supply-circuit breaker re- overcurrcnt relays at breaker g would trip and lock out
energizes the s&transmission line, transformer breaker a brcnkcrs c, d, e, f, and g. Since the transformer has a long-
~c1oscs bccuust: of the overvoltage-reclosing function of time setting the breakers at either or both ends of the tie
the network relays, provided the voltage on the reenergized circuits connected to a faulted bus may open before the
subtransmission line is correct with respect to the network feeder breakers at the faulted bus are tripped and locked
voltage. A network-transformer fault is isolated in the out by the transformer breaker overcurrent relays. In the
same way as a subtransmission-line fault. The faulted example shown in Fig. 1, fault C might cause breakers
transformer can be disconnected from the subtransmission b, h, and k to open before breakers c, e, and f are locked
circuit by means of the switch on the high-voltage side of open; the result would be that service from arry or all tie
the transformer, and the subtransmission line can be re- feeders 6-c, h-e, and k-f would be interrupted momentarilY.
energized to supply other loads connected to it. However, breakers b, h, and k would reclose and reestablish
Tie-Feeder Faults-The operation of the network service to all the interrupted loads after a time delay of 15
system on tie-circuit faults is illustrated by fault B, Fig. 1, or 30 seconds. Before these breakers reclose, the breakers
which is isolated by breakers b and c opening on over- at the faulted bus are locked out and the fault is isolated
current. These breakers open before breakers in other from the system.
tie circuits, because of the broad-range, inverse-time
characteristics of the relays, even though the fault cur- 5. Operation of Network with One Breaker Per Tie
rents through other adjacent tie-circuit breakers exceed Supply-Line Faults-The operation of the primary
the minimum currents required to close the respective network in Fig. 2 is the same as that of the network in l?ig.
relay contacts. As long as there are at least two tie circuits 1 for subtransmission and transformer faults.
or a tie circuit and a transformer circuit in addition to the Tie-Feeder Faults-The operation for a feeder fault
faulted circuit connected to the same bus, selective opera- is different. For example, a tie-feeder fault at D, Fig. 2,
tion of the breakers is assured because the breaker in the causes feeder breakers, m, n, and p and transformer break-
faulted circuit carries the sum of the currents through the er q to open on overcurrent and isolate the faulted circuit.
other breakers. The mid-tie breakers remain open but after a predeter-
As soon as fault B, Fig. 1, is isolated, automatic re- mined time delay transformer breaker q goes through &
closing of breakers 6 and c is initiated so that each breaker prearranged succession of reclosures until the breaker
recloses after its respective time delay. Assume that the locks out on a permanent fault, or until the fault clears and
time delay before reclosing is 15 seconds for breaker b and reclosing the breaker reestablishes voltage on the primary
30 seconds for breaker c. Then 15 seconds after breaker b feeders in the faulted area. If reclosing the transformor
opens it recloses. If the fault has cleared, service is restored breaker establishes normal voltage on the feeders and the
to loads on the tie feeder but if the fault has not cleared, voltage is sustained for the time delay for which the mid-
breaker b opens and locks out. Thirty seconds after break- tie breakers are set, tie breakers VZ, n, and p reclose and
er c opens (approximately 15 seconds after breaker b re- the network continues to operate normally. A fault on *
closes), breaker c recloses and either reestablishes service radial primary feeder supplied from one of the network
from the tie circuit or locks out.. ,If the fault clears before units in Fig. 2 can be treated the same as a tie-feeder fault,
the first breaker recloses, the second breaker reclosing re- or some sectionalizing device such as a breaker or a fused
establishes normal operation of the network system. How- cutout can be used to isolate a faulted rydial feeder from
ever, if the fault clears between the first and second re- the network so that a permanent fault on the radial cir
closures, service to all loads is reestablished but the tie cuit does not interrupt service from the tie feeders.
circuit is open at one end and it is not capable of transfer-
ring load from one unit to the other. Normal operation of 6. Comparative Characteristics
the tie circuit is reestablished by manually reclosing the The primary network has several charactccistics which!
breaker which closed first and locked out. in comparison with other general types of distribution
Intersection-Bus Faults, for example al C, Fig. 1, systems, give the primary network definite advantages in
Chapter 21 Primary and Secondary Network Distribution Systems 693

o- 0
0 2 4 6 8 IO 12 14 16 18 20 22 24 26
YEARS

Fig. 3-Comparison of the costs of radial and primary-network systems over a period of 25 years in a uniformly loaded sixteen-
square-mile area where the load growth is ten percent per year and all subtransmission circuits, primary feeders, and secon-
daries are overhead. A: Total load in the area. B: Total accumulated installed cost of a radial distribution system with 4-kv
primary feeders supplied from large distribution substations. C: Total accumulated cost of a 4-kv primary network.

many cases. In general the primary network provides are those on any one primary feeder. Even if many small
better service and can be adapted more flexibly to chang- unit substations are used in a distributed radial system
ing loads than other systems in common use except the several feeders are served by each unit. If one of these
low-voltage secondary network described later in this units is deenergized all the consumers served by the feeders
chapter. out of that unit suffer an outage. Deenergizing a primary-
Better Service results from better voltage regulation network unit does not cause an outage for any consumer.
and fewer consumer outages. In many radial systems the To accomplish the same minimum consumer outage in
primary feeders originate at relatively large substations the distributed radial system duplicate transformers and
and the average length of the feeders is greater than that subtransmission supply circuits must be provided at each
in the primary network where small unit substations are radial unit substation; this requires more transformer
distributed throughout the load area in accordance with capacity, more miles of subtransmission lines, and usually
the load distribution. This results in less voltage drop in more complicated relaying than does the primary network.
the primary-network distribution feeders than occurs in Losses in the primary network system generally are
radial feeders supplied by a large distribution substation. lower than those in radial systems for the same reasons
Essentially the same result is accomplished in a radial that the inherent voltage regulation of the system is good.
system by locating small unit substations at the load cen- One of the two major reasons is that power is carried as
ters where primary-network units are installed. The tie near to the loads as practicable by high-voltage low-cur-
circuits in the primary network, which generally are the rent subtransmission circuits instead of by long lower-
main distribution feeders, are supplied from both ends. voltage higher-current primary feeders. The other reason
This usually will provide better voltage regulation in the is that the load along each tie feeder automatically divides
primary feeders under normal conditions than is provided between the two ends of the feeder so that minimum losses
in the distributed radial system. are maintained.
Consumer Outages are lower in the primary network Flexibility-One important feature of the primary-net-
system than in a radial system because the most services work system is that it utilizes small unit substations each
that will be interrupted by any fault in a primary network located at or near the center of the load it serves. This and
694 Primary and Secondary Network Distribution Systems Chapter 21

the interconnected system of primary feeders makes it If the primary network with well interlaced subtrang,
possible to remove or add small increments of transformer mission circuits is compared with a radial system using
capacity at various places in the network area without small unit substations distributed throughout the load
having to make extensive reconnections of the primary area each of which is supplied by only one subtransmission
feeders or to reroute large sections of circuits. In other circuit the network requires more subtransmission line.
words the network system is flexible in that it can readily The additional line is primarily due to the interlacing.
accommodate load growth or load shifting with minimum Interlacing accomplishes no useful purpose in the radial
disturbance to the system. system. However, if duplicate supply circuits to each
The flexibility of the primary network is a decided ad- radial unit substation are used to reduce the number of
vantage in the long-time over-all economy of a distribution consumer outages the radial system may reqllire more sub
system, particularly where the total load changes with transmission circuit than a primary network.
time or where load shifts from one section to another. Primary Feeders About Equal-The primary net-
T,oad gro\vth or shifts can bc accommodated by the pri- work uses about the same amount of primary feeder cir-
mary network with a minimum of rerouting and reconnect- cuit,s as does a distributed radial system. The main trunk
ing primary feeders and with relatively small increments feeders usually are about the same in a given area for
of substation capacity. l?or this reason the system invcst- either system. Hut in the primary network additional
ment can be kept more nearly proportional to the load short sections of primary circuit may be required to make
served than in the case of other systems where substation the tie circuits continuous between substations. Also in
capacity has t,o be changed in large increments or major the network the tie circuits must have the same size cop-
rerouting and reconnecting must be done to avoid over- per throughout their length while radial primary feeders
loading or underloading radial substations. The effect sometimes are graded down to smaller size copper as the
of this on the system investment is shown in Fig. 3. The load decreases along the circuit. However, the primary-
primary network is churactcrized by regular small incre- feeder circuit required by the network may be no greater
ments of investment while the radial system occasionally than that required by the radial system if it is necessary
requires large additions to the system. in the radial system to extend feeders from one substation
Large Number of Substations-The primary net- area into another area to equalize the loading on the radial
work requires many relatively small substations in com- substation units or if normally open ties are provided so
parison with a radial system supplied by a large substation that the load in one radial-substation area can be picked
at the load ccntcr of a large load area. A large number of up by other substations when that unit is out of service.
substation sites and structures must be provided for the See Chapter 20, Fig. 18.
primary network. However, each of these sites usually is
cheaper than that for a large radial station. Smaller sites 7. Economic Field
are required by the relatively small primary network units. It is impossible to say that the primary network is
Furthermore, in most cases several small substation sites economically applicable in any specific range of load den.
can be found scattered throughout a load area more readily sity because many factors affect the relative overall costs
than can a single large one near the load center of the whole of the various systems that may be considered adequate
area because the load center usually is in the most highly in specific cases. The voltage class, type of construction
developed section of the area. On the basis of real-estate used for the subtransmission and primary-feeder circuits,
requirements the primary network is comparable with the the load density, the anticipated rate of load growth, the
radial system using small unit substations distributed required quality of service, real-estate co& type of sub-
throughout the load area. station required, and local labor and material costs affect
Large Amount of Subtransmission Required- the economic comparison of systems in any particular
The primary network requires more subtransmission line case. The choice of the type of distribution system to
to supply the small substations distributed throughout the supply any load area should be based on the overall cost
load area than a radial system using large substations. The of distributing power in the area; the cost should include
amount of subtransmission circuit required depends on installed cost of equipment and circuits, cost of the losses,
the amount of interlacing of the supply circuits in the and the cost of accommodating load changes over a reason-
network area. The minimum of subtransmission line is able number of years.
required by parallel subtransmission, that is when each While no conclusive generalizations can be made re-
supply circuit is taken straight through the network area garding the economic field of application of the primary
and connected to all the substations along that line. &ore network some specific comparisons13 show where the Pri-
uniform load distribution when a subtransmission circuit mary-network system is likely to be the economical one.
is out of operation can be accomplished by interlacing the The comparisons shown in Fig. 4 show the/relative cost of
supply circuits so that each deenergixed unit is surrounded five types of system for four types of circuit construction
as completely as possible by units in operation. This in ‘a sixteen-square-mile area where the uniformly dis-
requires more subtransmission line than does the arrange- tributed load is assumed to grow at the rate of ten percent
ment using supply lines going straight through the net- per year. The four sets of curves, Fig. 4 (a, b, c, and d)~
work area. However, the saving in spare transformer show that for medium load densities in the range from 50°
capacity to provide for emergency operation usually more to 5000 kva per square mile the primary-network is likely
than pays for the additional subtransmission circuit. See to be economical, particularly if the system is to be Pre- ’
section 13. dominantly of overhead construction. If all the subtr@S- b,
360

340

320

300

280

260

240

220

200

180

160

140
0
; 120

8 100
2 80 (0) (b)
0 1000 2000 3000 4000 5000
“w 360
a
z 340
4
; 320
0
D 300

280

260

240

220

200

180

160

140

120

100 I
(cl
80
0 1000 2000 3000 4000 5000
LOAD DENSITY-KVA PER SQUARE MILE
Fig. 4-Relative cost of several types of distribution systems for various load densities in a sixteen-square mile area where the uni-
formly distributed load grows ten percent per year. (a) Subtransmission circuits underground; all other circuits overhead open-
wire. (b) Main subtransmission circuits underground; branch subtransmission aerial cable; 4 kv primary feeders and secondaries
overhead open-wire. (c) Subtransmission circuits aerial cable; all other circuits overhead open-wire. (d) All circuits overhead open-
wire. Al : Radial system with 4-kv radial primary feeders with individual voltage regulators supplied by a 12 OOO-kva distribution sub-
station. A2: Same as Al except for 24 OOO-kva substation. B: Radial system with bus-regulated distribution substation and 4-kv
primary feeders. C: Radial system with 13.2-kv subtransmission circuits supplying distribution transformers. D: Primary network
with 4-kv primary feeders. Offset in curve at 1500 kva, per square mile is due to increasing interrupting capacity of primary-feeder
breakers. E: Overhead secondary network.
696 Primary and Secondary Network Distrihtion Sysh~as Chapter 21

mission circuits are underground the relatively higher cost


of that part of the system penalizes the primary network
because more subtransmission circuit is required as com-
pared to the radial systems.
The cost of the network is consistently low throughout
the range of load density considered. Even in those nar-
row ranges of load density where the cost curve of some
other type of syst,em drops below the primary-network
curve the primary network is only slightly more espensive
than the other system, except for very low load densities
when underground subtransmission is used. This is im-
portant in load arcas where the load density is not uniform
throughout the area. The floxibility of the primary-net-
work system for accommodating load growth makes it
better for nonuniform load density and irregular load
growth than any radial system, particularly one using
large centrally located substations. The use of large sub-
stations depends on accurate long-range load forecasting. HIGH-VOLTAGE
Many large substat,ions located on the basis of long-time OISCONNECT
load predictions arc never fully loaded because the load
does not grow as rapidly or as much as anticipated. Be-
cause the network system can be expanded in small incre-
ments long-time forecasting is not necessary and irregular
load gro\vth can be accommodated more economically by
the network system. Therefore, in many cases where the
primary-network system appears to be slightly more ex-
BREAKER PRIMARY FEEDERS
pensive than some other systems on the basis of uniform
load density and regular load growth the additional cost (b)
of the network is more than compensated by the flexibility Fig. 5-Typical primary network unit. (a) Unit substation
of the network system. consisting of transformer with air-blast fans and tap-chang-
ing-under-load and throat-connected metal-enclosed switch-
The curves of Fig. 4 are not conclusive evidence that the gear. (b) Schematic diagram of a unit substation for operation
primary network is the most economical system for me- in a primary network.
dium load densities. However, the curves do indicate that
the primary network is likely to be economical in areas with a manually-operated primary disconnecting switch
\vhere the overall load density is between 500 and 5000 kva built into an oil-filled compartment on the transformer.
per square mile. The switch generally is capable of interrupting esciting
current so that the transformer can be disconnected from
8. The Primary-Network Unit the subtransmission supply circuit without deenergizing
I3asically the primary-network unit consists of a trans- the supply circuit. Either a two-position or a three-posi-
former to step down the voltage from the subtransmission tion switch can be used depending on whether it is desirable
voltage to the primary-feeder voltage and circuit break- to have a ground position in addition to closed and open
ers to control the feeder circuits and protect the system positions. The ground position is for grounding the in-
from faults that may occur in the various circuits. These coming supply circuit. The three-position switch generally
basic elements and their associated auxiliary equipment is preferred.
usually are assembled into a self-contained unit substation A completely-self-protected transformer frequently is
such as shown in Fig. 5. However when the primary net- used in a primary-network unit. Such a transformer in-
work uses only one breaker near the middle of each tie cludes high-voltage fusible protective links, integral light-
circuit the network unit is usually an assembly of the ning protection, and a thermal relay for tripping an as-
transformer, the transformer breaker, and auxiliary equip- sociated transformer breaker. When these elements are
ment. The mid-tie feeder breakers are located along the properly coordinated with the thermal characteristics and
tie circuits usually in the form of switchhouses. insulation of the transformer it is completely protected
The Transformer-A three-phase oil-immersed self- from damage from external causes. The completely-seff-
cooled transformer generally is used in a primary-network protected power transformer is described in detail In
unit. Frequently air-blast equipment is provided so that Chapter 16.
occasional high overloads can be carried without exceeding Voltage Regulation-Tap-changi 1,g-under-load
safe operating temperatures in the transformer. The ad- equipment is generally built into the transformer part of
ditional load capacity with air blast often is used as the the network unit so that the primary-feeder voltage of
spare capacity in the unit to take care of emergency loads the network system can be maintained at the proper level.
when a subtransmission circuit is out of operation. The The operation of this equipment is described in Chapter
trend is toward air-blast cooling on all network units. 5. A range of plus or minus ten percent usually is used
The primary-network transformer usually is provided although in some cases a smaller range is adequate. The
Chapter 21 Primary und Secondary Network Distribution Systems 697

choice of regulation range should be based on the maxi- ing current flowing through the network unit toward the
mum probable variation of subtransmission voltage at the network causes the regulator to reduce the voltage at that
net\vork units and the voltage buck or boost to keep the point because of the effect of the reactive current acting
primary-feeder voltage within the required limits. Since through the reversed-reactance element of the line-drop
each primary-network unit normally serves a relatively compensator. Conversely a reactive current from the
small arca the feeders out of any one substation are about network through t)he network unit causes the regulator
the same length and have the same type of load. Under to raise the voltage. As a result the voltage difference be-
such conditions bus-voltage regulation is adequate. Fur- tween the units that causes the circulating current is cor-
thermore, feeder-voltage regulation in a network system rected and stable operation of the regulators is maintained.
~vould be complicated and expensive. The rcsistancc element of the compensator can be used
The operation of voltage-regulating equipment in a pri- to give a rising voltage characteristic at the primary nct-
mary network involves a problem that does not occur in work unit for increasing load currents. This generally re-
the regulat,ion of radial circuits. In the network system quires somewhat higher settings for the r&stance com-
t,he voltage-regulating equipments in the various network pcnsation than is necessary with normal reactance com-
units are operating essentially in parallel. When one regu- pensation. The most practical method of adjusting the
lator raises the voltage above the general level of the nct- compensator elements is to start with a fairly high react-
work system undesirahlc circulating currents flow through ance setting and a relatively low resistance setting and
the network units and the tie feeders. If the control of the then by trial arrive at the best combination of settings.
regulators is compensated* in the normal way so that the The reactance compensation can be reduced gradually
regulators hold higher voltage for peak load than for until the minimum setting is found where stable opera-
minimum load the circulating current may be increased as tion is positive. This can be determined by manually
-3oonas it is cstablishecl. The reason for this is that the moving the regulator away from the position correspond-
circulating current appears to be a load current at the ing to the desired system voltage. The regulator should
rrgulator that establishes the higher voltage and appears return to the desired position automatically instead of
to he a reduction of load at regulators holding lower continuing, in the direction of the manual displacement,
voltage. The result may be that once the unstable opera- to the end of its range. The resistance can then bc in-
tion of the regulating devices is initiated the regulator creased to give the necessary compounding. Small read-
holding the higher voltage tries to raise the voltage unt,il justments in the reactance element may be necessary after
the regulator reaches the upper limit of its range and the the resistance element is adjusted. These adjustments
regulators holding low voltage try to lower the voltage should be made during light load because unstable opera-
until those regulators reach the lower limit of their range. tion is more likely at times of light load than at heavy
The resulting circulating current may open several break- load.
ers and may completely interrupt the operation of the If it is sufficient to maintain constant voltage at the in-
system. tersection buses in the primary network, the line-drop
The path of the circulating current is a closed loop ex- compensator does not function. In other words it is ad-
tending from the power source through a subtransmission justed for zero resistance and reactance compensation. In
line to the transformers supplied by that line, thence such a case the regulators operate stably regardless of the
through the primary network tie circuits, and back through connection of the reactance element. In fact if the voltage
network units to another subtransmission circuit by which at some point on every tie circuit decreases as load in-
it, returns to the power source. The impedance of the loop creases on the adjacent network units the regulators
is predominantly reactance. Therefore the circulating cur- operate stably with the reactance element not reversed.
rent lags the system voltage by a much larger angle than The most economical rating of transformer usually n-ill
do load currents. This provides a simple means for pre- be between 1000 and 3000 kva depending on circuit con-
venting unstable operation of the regulating equipment in struction, load density, location of units (outdoors or
the primary network. Interconnecting the regulator con- underground), and existing primary conductors. In order
trols in widely separated network units is not practicable. to use large units it is necessary to have correspondingly
However, by the simple expedient of reversing the react- large primary-feeder circuits or to have a large number of
ance elements” of the line-drop compensators in the control feeders out of each substation. The latter means that the
systems of the network-unit voltage regulators stable circuits are relatively long and that some of these circuits
operation of the regulators can be enforced. This can be may have to be carried some distance from the station
explained briefly by stating that a highly reactive circulat- before any load is served. The additional cost of primary
*This compensation is acronrplishrd by means of a Line-drop eompensntor. The feeders may more than offset the savings in the cost of
Compenantor coruists of a variable rcsivtance element and a variable
ment. These elements are connected in series with the secondary
reactance ele-
winding of a cur- network unit and subtransmission circuit. The long-
rent trnnsformer in the circuit through the voltage regulator.
drops in the two elements are proportional
The resulting
to the line current of the regulated
voltage
circuit.
term total annual cost of large units is likely to be higher
The two vnltqe drops are introduced into the voltage-measuring circuit of the regu- than that of smaller units because large units make it
lator control in series with B voltage proportional to the system voltage at the regu-
lator. The resistance element produces a voltage component 180 degrees from the necessary to add capacity to the system in large incre-
rqwlator current. and the reactance element. as normally connected, produces a volt-
?ue lauainu the current by ‘JO degrees. These elements are variable and can be ad- ments. This is particularly important where the load is
lusted so that the regulator holds not n constant voltage at the regulator but 11.voltage
high enough to compensate for the resistance and reactance drops in a radial circuit not uniformly distributed in the load area or where load
;Ind thus to maintain
rhis explanation
constant voltage at some predetermined
of the line drop compensator
point along the line.
is rigidly correct only for&feeder regu-
growth is irregular. Both these conditions are more preva-
lator in a single line with loud only at the end of the line. However. the line-drop com- lent than uniform load density and a regular rate of
Pensator is used aenernlly in all feeder nrrangements to compound the voltage regu-
lation so that 3 higher voltage is maintained at high-load than at light-load periods. growth. Past experience indicates that a 1500 or 2000 kva
698 Primary and Secondary Network Distribution Systems Chapter 21

unit (1875 or 2.500 kva with air blast) is usually most delay the tripping of the breaker on reverse currents up to
economical. Large units may appear economical in areas about 150 percent of normal full load on the associated
of heavy load density. However, in such areas the low- transformer. Thus momentary reversals of power that
voltage secondary network should be carefully considered disappear before the time-delay interval is completed do
because it is probable that the secondary network is less not open the transformer breaker, but if the reversal per-
expensive and it provides better service than the primary sists the breaker opens at the end of the time delay. A
network. delay of one to five minutes usually is long enough to take
Switchgear and Relaying-The two general arrange- care of momentary reversals. With this arrangement re-
ments of switchgear in a primary network are shown by versed fault currents, which generally exceed two or three
Figs. 1 and 2. In the type shown in Fig. 1 there are two times normal rated current of the transformer, trip the
breakers in each tie feeder, one at each end. The arrange- breaker and isolate the faulted element without intentional
ment in Fig. 2 uses one breaker in each tie feeder and this time delay.
breaker is usually located near the middle of the tie; how- The feeder breakers are controlled by overcurrent r+
ever, it may be located at any point in the feeder. From lays and time-delay reclosing relays. The overcurrent re-
the standpoint of interrupting duty and of load affected lays should have broad-range, very-inverse-time character,
by a feeder fault the midpoint location is best. istics to insure selective operation of the breakers in the
The one-breaker primary network costs less because it various tie circuits so that a primary-feeder fault causes
uses fewer breakers of lower interrupting capacity. Re- only the faulted circuit to bc isolated. Current discrimina-
closures to reestablish service on faulted feeders do not tion alone is inadequate for selective operation of tie-cir-
disturb loncls on the remainder of the net,work. In the cuit breakers. If current-discriminating relays in all the
t,wo-breaker primary network feeder, faults drop less load tie feeders are set low enough to trip their respective break-
and there are fewer locations where equipment must be ers correctly on the minimum faults, the breakers in sev-
maintained. era1 tie feeders probably trip incorrectly on severe faults.
The switchgear for the two-breaker primary network is The minimum fault current in a faulted tie feeder generally
shown schematically in Fig. 5(b). The transformer break- is lower than the maximum current in that feeder for a
er is provided with reversed-power and overvoltage-re- fault in an adjacent feecler. Definite-time settings for the
closing (network) relaying. The network relay disconnects overcurrent relays can be used to obtain satisfactory opera-
the transformer from the network in the case of a trans- tion of the tie breakers if the settings are carefully selected
former or subtransmission supply line fault and reconnects for the various breakers. This methods reqllires carefully
the transformer to the network when such a fault has planning the relay settings and depends, for correct opera-
been repaired and the relationship between the transformer tion, on accurate settings and the proper geographical
and the network voltages is correct. The transformer sequence of the time delays in the tie feeders of the net-
breaker is also equipped with very-inverse-time overcur- work. The broad-range, very-inverse-time relay scheme is
rent relays to isolate the transformer from bus faults and the most practical method of providing selective operation
to provide back-up protection for the feeder breakers. of the feeder breakers because it permits uniformly low
This overcurrent relaying on the transformer breakers also minimum current settings throughout the network and
trips and locks out the tic-circuit breakers connected to generally allows all the tie-feeder relays to be given the
the same bus. same settings.
The network relay is inherently sensitive enough on The feeder-breaker overcurrent relays are set faster than
reverse current to trip the transformer breaker on trans- the transformer-breaker relays so that any feeder fault is
former exciting current when t,he transformer is energized cleared by the feeder breakers before the transformer
from the low-voltage side. This makes it possible for the breaker can trip unless the feeder breaker that should iso-
network relay to isolate single-line-to-ground faults on late the faulted feeder fails to operate. If the feeder
subtransmission circuits supplying the network, when breaker fails to open, the transformer breaker operates
using network transformers with their primaries connected and, in conjunction with the other feeder breakers con-
in delta. It also facilitates testing and maintaining the nected to the same bus, isolates the faulted circuit.
supply circuit because it is not necessary to go to the pri- Reclosing of the primary-feeder breakers is used in the
mary-net,work units in order to deenergize the associated primary-network system, as in radial systems, to rees-
subtransmission line. This is particularly convenient tablished service from a faulted circuit if the fault clears
when no radial loads are supplied by the same circuit that when the feeder is deenergized. Most temporary faults are
supplies network units because then the subtransmission cleared before the first or second reclosures. In the pri-
circuit can be opened without interrupting any load. The mary network two reclosures for any tie feeder can be pro-
use of sensitive-reversed-current tripping is complicated vided conveniently by one reclosure at each end of the
by the possibility of momentary reversals of power flow circuit. To prevent both reclosures occurring simultan-
through the network transformers when radial loads are eously or near enough together that thd fault is not de-
supplied by the same circuits that feed the network units. energized between reclosures it is necessary to use different
This is particularly true if the radial load is characterized time delays before reclosure at opposite ends of the line.
by large abrupt fluctuations, as, for example, when large The shorter time delay is made long enough that both
industrial motors or furnaces are started. To prevent such breakers have ample time to open. The longer time delay
momentary reversals of power from opening the network- is made long enough that the two reclosures do not occur
transformer breakers a desensitizing relay68 can be used to simultaneously as a result of a large difference in the
Chapter 21 Primary and Secondary Network Distribution Systems 699

opening times of the two breakers in the faulted feeder. TABLE ~-RANGE OF INTERRUPTING CAPACITY USUALLY
Time delays of 15 and 30 seconds are generally adequate REQUIRED FOR BREAKERS IN PRIMARY NETWORKS
for the two reclosures. Using only one reclosure for each
Type of Primary Network
breaker minimizes the operating duty on the breakers.
The transformer breaker in the primary network with Breaker
Two Breakers Per One Breaker at ;\Iiddle
one breaker per tie feeder, Fig. 2, is controlled by network Tie Feeder of Each Tie
relaying and overcurrent relaying in essentially the same
Transformer 100 000 to 250 000 kva 100 000 to 250 000 kva
way that the transformer breaker in Fig. 1 is controlled.
Tie-Feeder 100 000 to 250 000 kva 25 000 to 100 000 kva
IIowever, in addition to network and overcurrent relaying
the transformer breakers in Fig. 2 are provided with rc-
closing relays so that the transformer breaker recloses on in Fig. 2 depends largely on their location in the tie circuits.
primary-feeder faults. Two or three successive reclosures If these breakers are located electrically at the middle of
are made before lock out. In the form of the network the tie feeder the masimum duty on them may be as low
shown in Fig. 2 the transformer breaker usually is included as a third of the maximum duty on the transformer break-
in the transformer structure to form a completely-self- ers because the impedance in the tie circuit limits the fault
protected single-circuit unit substation. currents. Table 1 shows the ranges of interrupting ratings
The mid-tie breakers in Fig. 2 differ physically and generally required for the various breakers in the two
functionally from the tie breakers in Fig. 1. These brenk- forms of the primary network.
crs are usually locat,ed along the tie feeders remote from
the substation in widely separated locations and cannot be 9. Designing the Primary Network
assembled together to form a switchgear unit. However, The design of the primary network, like that of any dis-
the breakers can be located anywhere along the tie feeders. tribution system, must be based on complete and accurate
If they are located at the intersections, those at a particu- load and geographical data, such as, (1) location, size, and
lar intersection can be grouped together to form a switch- character of large loads; (2) the amount, location, distribu-
gear assembly. Mid-tie breakers can be mounted on a tion, and character of the small loads; (3) anticipated load
pole, on a platform, or on the ground. The control for a growth in the area being studied; (4) location of bulk
pole-mounted breaker is in a separate pole-mounted hous- power substations; (5) location and capacity of exist)ing
ing. A breaker mounted on a platform or on the ground distribution circuits, transformers, and substat,ions; (0)
can be either an outdoor breaker or a breaker in a switch- available sites for substations and other distribution equip-
house. Outdoor breakers require a separate weatherproof ment; and (7) available routes for distribution circuits.
cabinet for the control and operating mechanism while Preliminary analysis should reduce the load data to quan-
the switchhouse type of mounting provides a weather- tity of load and load centers corresponding to relatively
proof structure for the control, operating mechanism, and small areas such as mile or half-mile squares.
the breaker. Network Unit Locations-On the basis of the loads
Mid-tie breakers are controlled by very-inverse-time and location of load centers in the small areas network
overcurrent relays and voltage reclosing relays. The mid- units are located at the load centers of larger areas each
tie breaker opens on overcurrent in either direction through comprising a load corresponding approximately to the
the breaker and recloses only after substantially normal proportionate share of the total load in the network area
voltage is maintained on both sides of the breaker for a that each unit will normally carry. The proportionate
predetermined length of time. Power for closing the share of load for each unit is determined by the total
breaker can be taken from the tie feeder on either side of number of units that must be installed in the network area.
the breaker or from an adjacent secondary main supplied There must be enough units in normal operation so that
by the tie feeder. under emergency conditions when one subtransmission
The interrupting duty on breakers in any primary-net- circuit and the network units connected to it are out of
work system depends not only on the short-circuit current operation the maximum capacity of the remaining units
of the adjacent network transformer but also on the char- will be adequate for the total load in the area. A rough
acteristics of the network system because currents can cost comparison can be made on the basis of a preliminary
flow to any fault over two or more paths. Unless the location of units to indicate the sizes of units that are
average tie-feeder impedance is more than about three likely to be most economical. Detail design and final com-
times the network-transformer impedance, the network parisons then need be carried through for only a few com-
transformer will supply less current to a fault at its termi- binations.
nals than will the remainder of the network. Therefore, The actual location of network-unit substations depends
tie-circuit construction, load density, and the extent of the not only on the location of the corresponding load centers
network are important factors in the interrupting duty on but also on the location of available sites, available rights-
circuit breakers in a primary network system. In the type of-way for subtransmission and primary-feeder circuits,
of system shown in Fig. 1 the duty on all the breakers at and the location of existing distribution facilities that
any substation is about the same and usually the variation can be utilized. The choice of substation locations usually
of interrupting duty from one substation to another is not takes into consideration the cost of real estate and the need
enough to justify using different breaker ratings in dif- for landscaping or special construction to match the sub-
ferent substations. The interrupting duty on the tie station with the surrounding buildings and area.
breakers in the form of the primary-network system shown Tie Feeders-The carrying capacity of the tie cir-
700 Primary and Secondary Network Distribution Systems Chapter 21

cuits between network units is related to the capacity of a feeder faults and subsequent time-delay tripping of the
network as well as to the load supplied from the circuit. feeder breakers to permit subfeeder sectionalizing fuses to
Generally there are from three to five tie feeders connected clear permanent subfeeder faults cannot be used in the
to each intersection bus and for practical purposes the network system. Instantaneous tripping or delayed trip-
average can be taken as four. The carrying capacity of the ping of the tie-feeder breakers does not permit selective
four tie circuits should be enough to carry the maximum operation of the tie-feeder breakers in the various tie cir-
load on the corresponding network unit. Also each tie cuits of the network. However, the subfeeders can be
circuit must be able to carry all of its load from one end. fused SO that faults on these circuits do not take the main
The reason for this is illustrated by considering that the tie feeder out of service. It is important that these fuses
transformer of network unit E, Fig. I, is out of service; be carefully coordinated with the tie-feeder breakers so
then feeders c-b, e-h and f-k are supplied only at the b, h that subfeeder faults are correctly isolated from the main
and k ends respectively. Under normal operating condi- tie feeder. A radial primary feeder can be served directly
tions, when all units in a network are operating, about half from the primary-network units through its own breaker
the load on the tie circuits connected to a network unit which usually is controlled by the same type of relaying
represent the normal load on that unit. Therefore, the used for the network tie circuits. However, any form of
combined carrying capacity of the tie feeders connected to relaying can be used for a radial feeder breaker in a pri-
a network unit must be at least twice the normal load on mary-network unit, if it coordinates properly with the
that unit. Actually each tie feeder should have a carrying network tie-feeder breakers.
capacity equal to about half the rated capacity, instead of Subtransmission Supply Circuits-At least two
the normal load, of the network transformer. On the basis subtransmission circuits are required to supply a primary
of an average of four tie feeders connected to each primary- network; a larger number of supply circuits reduces the
network unit, this carrying capacity usually gives enough spare capacity required in the network units to provide for
margin to take care of unequal division of load among the an emergency condition when one supply circuit is out of
tie feeders. The same size of tie-feeder conductors and operation. It generally can be assumed that ou) of any
network units generally is used throughout the network number of supply circuits, up to about five or six, only one
because of interchangeability and simplification of design will be out of service at any one time. Theoretically two
and construction. supply circuits require loo-percent spare transformer ca-
The tie feeders between primary-network units should pacity so that when one of the two subtransmission cir-
follow reasonably direct routes. This keeps the impedance cuits is out of service the transformers associated with the
of the tie circuit to a minimum. Low tie-circuit impedance operating feeder can carry the total load; actually the
facilitates uniform load distribution among the network maximum load capacity of all the network units has to be
units and keeps voltage drop in the tie circuit to a mini- somewhat more than twice the normal peak load because
mum. These factors are particularly important under the transformer ratings cannot be exactly fitted to the
emergency operating conditions when a subtransmission actual loads and because under emergency conditions the
circuit and its associated network transformers are out of load probably does not divide uniformly among the trans-
service and some of the tie circuits are being supplied from formers remaining in service. The corresponding theoret-
only one end. Short tie feeders minimize the probability ical reserve capacity for three supply circuits is 50 percent;
of faults on these circuits. Each tie feeder should follow a for four circuits 33% percent; and for five circuits 25 per-
separate route as far as possible so that tree limbs, derrick cent. Practically, very little reduction of necessary reserve
booms, or similar hazards do not involve more than one capacity results from using more than five or six supply
tie feeder. Usually the installation of a primary network circuits. When a larger number of circuits is used, some of
involves the adaptation of existing primary feeders to the the transformers in the network area will be remote from
tie circuits of the network system and the routes of the transformers that are out of qperation and will pick UP
existing main primary feeders are major factors in routing relatively little of the load normally supplied by the trans-
the tie lines. formers associated with a supply circtiit that is out of
Either overhead or underground construction can be service. In other words, the reserve capacity in a network
used for the tie feeders. The choice of the type of con- supplied by more than five or six subtransmission lines
struction depends almost entirely on the class of neighbor- cannot be effectively utilized and the necessary percent
hood through which the feeders run and on the economic reserve capacity in the network becomes practically con-
balance between the cost of underground construction and stant as the number of supply circuits increases beyond
freedom from lightning, sleet, and tree troubles. When an five or six.
existing system is adapted to primary-network operation For more than five or six circuits the probability of two
the type of construction already being used usually de- circuits being out of operation simulta ‘eously may be
termines the construction of the primary-network tie feed- great enough that such an emergency mu.7t be considered,
ers. In areas of medium load density, where the primary More reserve capacity may be required in a network sup
network is generally applicable, overhead open-wire con- plied by a larger number of supply circuits than in one
struction predominates. supplied by five or six circuits. The number of subtrans-
Radial subfeeders and primary laterals can be supplied mission circuits that can be expected to be operating at any
from the tie feeders in the same way that they are served time must have enough capacity to carry the total Pri-
by radial primary feeders. However, instantaneous de- mary-network load.
energizing of the main tie feeder to clear temporary sub- Interlacing of the subtransmission circuits, to avoid
Chapter 21 Primary and Secondary Network Distribution Systems 701

adjacent transformers being connected to the same sup- the reclosing to reenergize the primary feeders after a tcm-
ply circllit, should be used to keep the spare capacity in porary fault is done by the transformer breaker. Tn the
the network to a minimum. The additional length of system using two brenkcrs per tie feeder, substituting
supply circuit usually is more than out-weighed by the fuses for these breakers is not practical because the fuses
saving in network unit capacity. See section 13. do not provide means for reestablishing scrvicc on the tie
The construction used for the subtransmission circuits feeders in the case of temporary faults. Reclosing fuses
depends on available rights of way, subtransmission volt- might be used for this purpose if suitable, accurate, long
age, and the value of the protection from lightning, time delays could be incorporated in the fuse to insure
storm, and tree hazards afforded by underground con- properly coordinated operation of the fuses at, opposite
st,rrwt,ion. Prevailing subtransmission circuits usually ends of the line. If fuses are used in place of mid-tic
establish the type of construction to be followed by pri- breakers they must be coordinated carefully so that the
mary-nct\vork supply circuits. Closely built up areas may fuses in the various tie circuits opernto selectively. One
require underground or aerial cable lines while open areas important disaclvantage of these fuses is that the tie feeders
may permit, lising overhcnd open-wire construction. must be patrolled frequently so that fuses adjacent to a
One important advantage of the network system IS that substation near jvhich a tic-feeder fault has occurred do not
the subtransmission circuits can be straight radial circuits remain open for long periods of time and result in dropping
protected by simple overcurrent relaying systems because load around that s~lbstation when it is taken out of service
service to all the loads in the network area is independent at some later time because of a transformer or subtrans-
of the continuity of operation of any subtransmission mission-line fault or for maintenance or testing.
circuit,. The: complicated relaying and duplicnt,ion of sup- Primary networks are usually applied in areas n-here
ply circrlits required by the subtransmission grid (See there is an existing distribution system. For this reason
Chapter 20) are not necessary for the operation of a pri- it is often desirable to adapt existing substations to net-
mary netxvork. However, it is important that the supply work operation. When the existing substations are equal
circuits originate at bulk power stations that are closely or nearly equal to the network units that are to be used,
interconnected so that the voltages on the various sub- it is necessary only to provide existing stations with net-
transmission circuits are maintained practically eqllal and work relaying and properly coordinated over-current relay
in phase. This is necessary to insure uniform load distribu- ing and to make sure that esisting breakers are of adequate
tion among the supply circuits. interrupting capacity. In larger stations it may be neces-
Automatic reclosing of the breaker at the supply end sary to divide the station into sections nearly equal in
of an open-wire subtransmission circuit supplying primary- capacity to the new network units to be installed. In some
network units is not as important as it is for primary cases it may be feasible to segregate a small section of the
feeders or subtransmission lines in a simple radial system. bus in a large substation for operation in the network sys-
In the primary-network system a fault on a subtransmis- tem and supply this section of bus from the main station
sion circuit does not interrupt any load. Furthermore, it bus through a bus-sectionalizing breaker and current-
is not necessary to restore the faulted circuit to operation limiting reactor so that the normal load and the available
t>omaintain service to any loads served from the net,work. short-circuit kva on the small bus section arc comparable
Rcenergizing a subtransmission line connected to a faulted to that of the network units. In this latter case the section-
network transformer almost invariably would reestablish alizing breaker is relayed in the same way as the trans-
the fault and cause unnecessary damage to the transformer, former breaker in a network unit, and the feeder breakers
If considerable radial load in addition to network load is on the small bus section are provided with the same type
served by an overhead subtransmission circuit, automatic of control as other tie-feeder breakers in the network.
reclosing of the subtransmission-line breaker may be justi- Other modifications may suggest themselves in particu-
fied by the reduction of the duration of outages for the lar cases. Any modification should be made only after it
radial load when temporary subt,rsnsmission-line faults has been determined that tie-feeder scctionnlizing devices
occur. Reclosing is not used on subtransmission cables and network-unit transformer breakers arc properly co-
because a fault in a high-voltage cable usually does not ordinated and correct operation of the network is assured.
(‘leer when the cable is deenergized. Reclosing on faulted
cable circuits usually causes unnecessary damage to the III. THE AUTOMATIC A-C SECONDARY
(sable. NETWORK SYSTEM
10. Modification of the Primary Network All the secondary networks now operating in 196 cities,
The foregoing discussion has been confined to the two with one exception,33e65work on the same basic principle.
basic forms of the primary network both of which oper- Loads throughout a load area are supplied by taps from an
ate on the same fundamental network principle. Modi- interconnected system of low-voltage circuits. The utiliza-
fications that have been used or suggested are variations tion voltage,26 at which the secondary mains are operated,
of arrangement and generally do not affect the funda- varies among installations from 115/119 to 125/216 volts.
mental operation. The two most important modifications The most prevalent voltage is 120/208 volts which pro-
are the use of fuses in place of mid-tie breakers and the vides a standard lamp voltage from line-to-neutral and a
adaptation of the network system to existing substations three-phase line-to-line voltage that is generally satisfac-
and distribution facilities. Fuses can be used In place of tory for 220-volt motors. 17 Power is supplied to this sys-
themid-tie breakers in the system shown in Fig. 2 because tem of low-voltage circuits through several transformers
702 Primary and Secondary Network Distribution Systems Chapter 21

which in turn are energized by two or more primary-feeder SUBSTATION


circuits. Automatic network protectors56.57and the natural
tendency of low-voltage faults to clear themselvesY1eEare
utilized to protect service from the secondary network from NETWORK PROTECTOR

all faults in the system, escept complete failure of the NETWORK


power supply. TRANSFORMER
I /
11. The Underground Secondary Network
The basic electrical arrangement of the secondary net-
work is shown in Fig. G. The grid of secondary mains is
the interconnected system of low-voltage circuits from
which loads are served at utilization voltage. The network
transformers introduce power into the secondary mains at
the intersection of the mains through network protectors,
which are automatic air circuit breakers controlled by net-
work relaying. Two or more primary feeders are used so
that even when a primary feeder is out of service all of the
load can still be supplied over the remaining feeder or
feeders. The feeders to the network can come either from
a distribution substation, from a bulk power substation, or
a generating station. In network systems the feeders fre-
quently operate at subtransmission voltage and are, in
fact, subtransmission circuits carried directly to the dis-
tribution or network transformers.
Secondary Mains-The load circuits or secondary
mains from which consumer services are tapped generally
follow the geographical pattern of the load area because
the mains are located under the streets or alleys in the
area so that the services to the consumers can be as short
as possible. This arrangement facilitates access to the
mains for repairs, maintenance, and service connections.
In underground systems the secondary mains as well as
other circuits are generally carried in duct systems and
the service connections are made in manholes, vaults, or
shallow junction boxes. At the intersections of the sec-
ondary mains the corresponding phase conductors of the
intersecting mains are connected together so that, in most ’
city areas where the low-voltage secondary network is -SECONDARY MAINS/
applicable, the system of secondary mains takes the form Fig. 6-Schematic diagram showing the basic arrangement of
of a grid. In an idea1 case the grid forms a regular pattern primary feeders, network transformers, and skcondary mains
such as that shown in Fig. 6. in a low-voltage secondary ne$work.
In underground systems the secondary mains generally
are made up of single-conductor cables because the many percent. The carrying capacity of a secondary-network
mterconnections and service taps required in a secondary main should be one-half to two-thirds of the rated capacity
network can be made more easily and less expensively on of the predominant size of network-transformer unit. This
single-conductor cables than on multi-conductor cables. In is true because a part of the maximum load on a trans-
the early stages of the network system lead-covered cables former is usually supplied from the junction where the
were used almost exclusively. Within the last decade im- transformer is connected, and the remainder of the output
proved insulating materials have resulted in extensive use of the transformer usually is divided unequally among the
of non-metallic sheathed cabless because splices can be mains connected to the same junction as the transformer.
made more easily. Although three-conductor cables gen- Also, when the normal power supply from a network trans-
erally are not used it is common practice to twist all the former at one end of a secondary main is out, all the load
conductors of a three-phase circuit together to keep to a along the main and part of the load at the end where the
minimum the reactance of the circuit and thus improve transformer is out is supplied from the other end of the
voltage regulation. main. .‘\
The size of the conductors* in the secondary main The conductor sizes most frequently used in under-
depends primarily on the required carrying capacity. ground low-voltage networks are 4/O and X0-, 350-, and
However, the voltage drop from a transformer to any load 500-MCM. However, because of relatively high voltage
along the mains under normal operating conditions (all drop, difficulty of handling, and the difficulty of burning
transformers in operation) should not exceed about two clear faults on 500-MCM cable, two 4/O or 250-MCM
*See Chapter 6. cables in parallel are frequently used in p&e of one 5@
Chapter 21 Primuq and Secondary Network Distribution Systems 703

J’IC~CI conductor. The improvement in voltage regula- TABLE ~-MINIMUM CURRENT IN AMPERES REQUIRED IN EACH
tion’s is shown by Fig. 7. Two 250-MCM conductors in CONDUCTOR ON BOTH SIDES OF A SOLID FAULT ON SINGLE-
CONDUCTOR CABLES TO BURN OFF THE FAULT
pnrnllcl have the same copper cross-section and essentially
the same resistance as one 500-lMCM. The paralleled Conductor Six Ovcrhcitd Circuit, Underground Circuit
2SMC31 cables provide better regulation because the
reactance of that circuit is about half that of the 500-MCbI 1 1000 1000
rircuit. The smaller cables are easier to handle in the l/O 1200 1800
limited space in manholes and vaults. Where transformers 2/o l-100 2100
3/O 1700 2500
larger than 500-kva are used in a network multiple-
4/O 2100 2900
conductor circuits always should be used. 250 MCM 2300 3200
The operation of the secondary network depends on 350 MCM 3000 4000
faults on the secondary mains being burned off and clear- ,500 Mc!hI 4000 5000
ing without deenergizing the system. This is feasible on
low-voltage circuits such as 120/20%volt secondary-nct-
work mains because arcs are not sustained at that voltage. ductor more quickly than a large conduct,or. Also with
For circuits operating at higher voltages such as 460 volts the parallel arrangement of the secondary-main conduc-
this method of clearing faults is not dependable. Test9 tors a fault opens only one of the branches of the main and
leaves the other branch of the main in operat,ion to help
maintain the masimum possible fault current available at
the fault point. Furthermore, the paralleled circuits of the
main can be tied together at short intervals so that only a
z I.6 small section of the main is affected by a fault. Tying the
parallel circuits together increases the fault, current at the
4
:
fault point in most cases.
za 1.4 The effects of paralleled mains and tie points are illus-
trated by Fig. 8. A fault near a junction is more difficult
w
?
to clear than a similar fault at any other location on the
i- main because the current to one side of the fault is limited
; 1.2 by the impedance of t.he entire main. Such a fault in a
c
well-designed network grid is quickly burned clear between
the fault and the nearest junction point as shown in Fig.
1.0 8(a). Occasionally the fault current over a long secondary
100 90 90 70 60 50 40 31J
main is not enough to burn off a solid fault on a main con-
PERCENT POWER FACTOR
sisting of a single-conductor per phase. The currents shown
Fig. 7-Relative regulation per unit length of three-phase cir- in Fig. 8 are calculated for the conditions shown. The
cuit for a balanced three-phase current at various power fac- current to a fault at the end of a 500-foot, 500-hICILI
tors. A: For a circuit consisting of three 500-MCM single-con-
ductor cables in a duct. B: For a circuit consisting of two
secondary main, Fig. 8(a), will be 4250 amperes or only 85
parallel three-phase branches each made up of three 250- percent of the 5000 amperes necessary to clear a solid fault
IMCM single-conductor cables in a separate duct.
300 KVA 300 KVA
and calculations have shown that the minimum currents 5% 2 5% 2
shown in Table 2 are required to burn clear the most 0.0072 OHM 500 MCM-0.021 OHM 0.6072 OHM 1
severe type of fault. Such a fault is one where the current If - 4250 AMP. (85 X)
FAULT
and thermal capacity of the fault is greater than those of I (a)
the conductor itself making it necessary to fuse the con- 500 FT.
ductor on each side of the fault. In an actual installation 300 KVA 300 KVA
such a fault might occur when a power shovel digs into a v\Nv5% 2 5% 2 \ilN
0.0072 OHM TWO 4/O;-0.0359 OHM EACH 0.0072 OHM
duct line. The probability of such a fault is rather small.
If - 2970 AMP. (98.2%) %
Most faults on network secondaries clear with much FAULT----+
smaller currents than those shown in the tabulation. The
values for underground circuits are for either lead-covered (b)
or non-leaded cables. A 500-MCM conductor is about the
largest conductor that can be expected to burn clear con- 300 KVA 300 KVA
sistently because larger conductors require high minimum
fault currents, which are difficult to obtain in network Mw0.0072
5% 2 OHM TWO 4/04 -0.0359 OHM EACH 0.0072
5%f OHM ”
mains except where the transformer capacity is highly con- 4330 AMP. If -
(149.2%) FAULT>
centrated, and also because of the large amount of metallic
vapor generated when a large conductor fuses. (c)
The ability of any network to clear secondary faults is Fig. S-Effect of paralleled conductors and tie points in
improved by the use of paralleled-conductor circuits. paralleled conductors on the ability of a low-voltage network
Available short-circuit currents will burn off a small con- to clear secondary faults.
Primary and Seconclarg Network Distribution Systems Chapter 21

on t,hst. size conductor. If, as in (b), two paralleled 4/O necting sn-itch provides means for disconnecting a trans-
cables without tie points arc sltbstituted for the 500-MC31 former from the primary feeder and it mav also incorporate
conductor t,hc fa77lt clearing ability is improved. There is means for short circuiting and grounciing the primary
still only 95.2 percent of the 2000 amperes required for the feeder for the safet,y of workmen \I-hen t,he fccclcr is being
xorst fault; ho\\-ever, the probabi1it.y of the fault not clear- repaired or estendctl. The nctxork protc:ct~or5”is an clec-
ing is very remote. But if, as in (c), the tn-o paralleled 4/O trically-operated air circuit brwker controlled by net\vork
condllctors are tied tog&her at the midpoint of the main, relay9 so that, it automatically tliaconnect,s the trans-
the available fn77lt current from the main to the fault is former from the secondary grid when power flow from the
incrensetl to 140.2 percent of the 2900 amperes required. grid to the transformer and reconnects the trnnsformcr t,()
This provides a wide margin of safety. There are t\vo the grid when the transformer can supply power to the
rwsons for this result. Both transformers can supply (rrid. =In installation of three network units in a vault is
current II, the fault aven after it burns off on one side; Eholvn in Fig. 9.
and the ecfectivc impetlancc to the fa77lt is less than that Transformer-Three-phase transformers generally arc
in cGthcr case (a) or (1)). Tn the case of tn-o 4/O conductors usccl because the space required and weight of the trans-
per ph:~sc~and 300-kva transformers, lOO- to 150- foot former is less for three-phase 77nits t)hnn for an equivalent
int,c:rvaIs bct,\veen tic: points arc short cno77ghto burn clear bank of single-phase units anal the cost, is less for the three-
a fault s7wh as shown in Fig. S(c), even on mains as long as phase unit. Single-phase transformers off’er no advantage
13.N feet. AIains of such lcngt,h seldom occur in secondary from the standpoint of serviw cont,inuity because the
networks. The effectiveness of this method depends on interconnected secondary grid maintains the service at a
there being two hranchcs of t,hc main each in a separate transformer point even though that transformer is o77t of
tl7ict to prevent, a fa77lt in one hranch from communicating operation. However, when existing single-phase trans-
to the other. l~s71ally these tie points are provided auto- formers have impedances and voltage such that, they can
matic:ally by service taps along the mains; on a parallel- be paralleled with network units, t,hey can be usecl in a
contluc:t,or main t,he branches should be tied t,ogether at network system. This often occurs \vhen an esisting dis-
service points lxea77se of the improved voltage rcg77lntion tribution system is converted to a low-voltage secondary-
and tlccreasecl losses in the main. network system. Single-phase transformers sometimes arc
Limiters-Frequently there arc a few mains in a sec- necessary beca77seof space and weight limitations of eleva-
ondary-network grid where fault current is insufficient to tors, hall~rays, doorlvays, manholes, and other means by
insure clearing a solid fault. Also some severe fnnlts result \vhich the transformers must be moved into position in
in a considerable amount of damaged cable before the vaults. This is particularly true for building vaults.
fault is cleared. To minimize the amount of cable damage Oil predominates as the cooling and insulating medium
result>ing from secondary faults and to avoid the infreqent for netirork transformers primarily becaase of its relatively
cases where a secondary fault fails to clear in a reasonable low cost and because other suitable mediums were not
time the limiter was developed and applied first in New
York in 103~.5s~6~The limiter also provides means for
isolating secondary faults on secondary mains in fringe
areas of a network where there is insufficient fault current
available to fuse the secondary mains in the case of a solid
fault. The limiter is a restricted copper section installed in
the secondary main at each junct,ion point; the f77sing
chnractcristics of the limiter are designed to clear a faulted
section of main before the cable insulation is damaged by
the heat generated by the fault current. The exutent to
which limiters arc applied in a network depends on eco-
nomic considerations as well as on the necessity for provid-
ing means of clearing faults. In some networks, limiters
are installed in all secondary mains on the basis that the
saving in damaged secondary cable justifies the applica-
tion. It is cheaper t;o apply limiters on non-leaded cables
than on lead-covered ones, especially if the lead sheath
must be continued over the limiters by means of miped-
solder joints. Local costs and local secondary-fault espe-
riencc must be considered in each case.
Network Units-A secondary-network unit consists
of the network transformer and its associated primary
disconnect switch and network protector. The network
transformer is the distribution transformer in the network
system. It combines the functions of both the distribution-
Fig. 9-Three submersible secondary-network units installed
substation transformer and the distribution transformer in a vault. Each unit consists of a 500-kva transformer with a
when subtransmission supply circuits are connected di- 1600-ampere network protector on the left end and a primary
rectly to the network transformers. The primary discon- switch and terminal chamber on the right end.
Chapter 21 Primary and Secondary Network Distribution Systems 705

connected and are properly insulated a high-voltage d-c


test potential can be used on the feeder cables. Star-
connected primary windings make it impractical to use
this type of switch because it is then practically impossible
to test the feeder cables without disconnecting the trans-
former from the feeder cables. The two-position discon-
necting switch facilitates &tin, v the feeder cables but has
the disadvantage that the feeder cable must be grolmded
separately to provide safe working conditions for repairing
the cable. The three-position disconnecting and grounding
switch provides both the safety of grounding the feeder
cable and the convenience of disconnecting the transformer
from the cable t,o facilitate testing the feecler cable. The
three positions of this switch are “Transformer,” “Open,”
and “Ground.” In the “Transformer” position the feeder
is connected to the t,ransformer. In the “Open” position
the transformer is disconnected from the fecdcr circuit.
In the “Ground” position the primary feeder is discon-
nected from the transformer and grounded.
The primary switch is a manually operated device and
generally is not capable of opening transformer exciting
current. For that reason the switch usually is interlocked
so that it cannot be operated unless the transformer is
deenergized. Therefore, the feeder circuit must be deener-
Fig. 10-A network protector in a subway housing. This is the
gized at its supply end to deenergize the transformers be-
type of protector that is mounted on the left end of the trans- fore the disconnect switches can be opened. The sequence
formers in Fig. 9. of operations of the three-position primary switch is ar-
ranged so that to ground the primary feeder the witch can
available in early stages of the development of the network be moved to the “Ground” position only from the “Trans-
system. The chief disadvantages of oil-filled transformers former” position. This sequence of operations prevents
are the e?;plosion and fire hazards. A non-inflammable grounding an energized feeder circuit because if the feeder
liquid, such as Inerteen, eliminates the fire hazard and it is is energized with the switch in the “Open” position, the
used in many cases \vhcre a fire would be difficult to con- interlock locks the switch when the switch is moved to the
trol or would be likely to cause extensive damage. Both “Transformer” position where it must be before being
oil-insulated and non-inflammable-liquid-insulated trans- moved to the “Ground” position. In some cases, such as
formers can be used wl~erc a submersible unit is required. \vhcn radial loads are served from the same primary feeders
Air-inslllated transformers that use no liquid and eliminate that serve network transformers, it is desirable to be able
both the fire and explosion hazards are particularly suit- to disconnect a network transformer from an energized
able for installations in buildings. feeder. For that purpose the primary disconnecting sn-itch
In addition to providing for a primary switch and means must be capable of opening exciting current and must be so
for mounting a low-voltage protector, a network trnns- inter-locked that it cannot be opened unless the associated
former is carefully constructed to reduce the probability protector on the low-voltage side of the transformer is opened
of internal faults. Submersible-transformer tanks are to remove load from the transformer. A three-position
constructed to resist corrosion resulting from submersion. switch for interrupting exciting current must have an addi-
Resistance to corrosion is obtained by heavier tank bot- tional interlock to prevent grounding an energized feeder
toms and cooling tubes, alloy hardware, and special paint. circuit. A three-position primary switch is sholvn on the
The size of a network transformer is made as small as right end of each network unit in Fig. 9. The high-voltage
possible, consistent with proper electrical construction, to switch compartment usually is combined Jvith a terminal
save transformer-vault space. chamber or potheads for terminating the primary-feeder
The High-Voltage Switch, with which a network cables.
transformer is generally provided, may be a two-position The Network Protector56 is an electrically-operated
grounding switch, a two-position disconnecting switch, or air circuit breaker controlled by directional-tripping and
a three-position disconnecting and grounding switch. The voltage-reclosing relays. The breaker, the operating mech-
t\vo-position grounding switch does not disconnect the anism, and the relays are assembled together to form a self-
transformer from its primary feeder; it short circuits and contained unit that in many cases is bolted to a throat,
grounds the primary-feeder circuit at the transformer pri- enclosing the secondary terminals, on the network trans-
mary terminals. From the standpoint of safety this type former. Such a protector is shown in Fig. 10 and on the
of switch is udcquute but it has the disadvantage that left end of the network unit in Fig. 9.
dielectric tests on the primary-feeder cables must be made The basic directional-tripping function and the over-
with the primary windings of the network transformers voltage-reclosing function of the network relaying are
connected to the cable circuits. If these windings are delta- combined in one three-phase relays7 called the master
706 Primary and Secondary Network Distribution Systems Chapter 21

netn-ork relay. The master relay is mounted in the lower network grid and angular voltage differences between
left corner of the protector, Fig. 10. This relay is a watt- primary feeders result in improper load division or cause a
type induction relay. The master relay closes its closing large number of protectors to open. Furthermore, if the
contacts when the protector breaker is open and the volt- feeders are supplied from more than one sllbstation, it may
age of its associated transformer is slightly greater than be necessary to plan the network on the basis of one of a
and essentially in phase with the corresponding network few substations instead of one of several feeders being out
voltage. The tripping contacts close when the protector is of service. For example, a network system supplied over
closed and a current in escess of the minimum setting of four feeders from two single-t,ransformer distribution sub-
the relay flows through the protect,or from the network stations (two feeders per substation) has to be designed to
secondary mains to the transformer. carry the total nctmork load on half of the network trans-
The overvoltage-closing function of the master relay is formers because of the probability of an outage of one
usually modified by a phasing relay”’ so that the protector substation. If all four feeders are supplied by one sub-
does not close if the voltage of the transformer being station SO arranged that power is always available at its
connccterl to the secondary grid appreciably lags the net- low-voltage bus, it is reasonable to assume that the worst
work voltage. This insures that, the network protector emergency condition is the loss of one of the four primary
closes only if the relationship between the transformer feeders. In this case three-fourths of the network trans-
voltage and network voltages is such that power flow formers are always available to carry the total load. Much
toward the network when the protector closes and does not more reserve network transformer capacity is required in
immediutcly reopen because of the resulting current flow the former case than in the latter. If the feeders supplying
being in effect a reversed current. The phasing relay is network transformers originate at a distribution substation
mounted directly above the master relay in the protector, the subtransmission supply to that substation should be a
Fig. 10. subtransmission loop or grid and the substation should
It is desirable to have the network relays sensitive have duplicate transformers (See Chapter 20). The ar-
enough that the network protectors open on the exciting rangement of the secondary network provides continuous
current, of their associated transformers when the corre- service regardless of faults in network transformers cr pri-
sponding primary-feeder breaker is opened. This not only mary feeders. In practical operation the reliability of
provides a simple means of periodically checking the opera- service from the secondary network is limited only by the
tion of the network protectors but also makes it unneces- reliability of power supply to the primary feeders supply-
sary to go to all the protectors associated with a particular ing the network transformers.
feeder in order to deenergize the feeder for repairs. An- In many areas xhere the secondary network is appli-
other advantage of sensitive tripping is that the protectors cable the total load frequently is sufficient for two or more
can isolate single-line-to-ground faults on a circuit supply- subtransmission circuits. Network transformers usually
ing the network, when the primaries of the network trans- are three phase and range from 150 to 600 kva. The addi-
formers are connected in delta. However, in infrequent tional cost of using transformers rated for subtransmission
cases, such as when regenerative loads are supplied from voltages instead of for the lower voltages generally used
the network, sensitive tripping will result in too frequent for radial primary feeders is fairly small. These two factors
opcrntion of protectors. In these cases the sensitivity is make it economical to supply a secondary-network system
decreased for normal conditions by means of a desensitiz- over radial subtransmission circuits and thus eliminate
ing relay.68 This relay permits the protector to trip on the distribution substation. In this case there is only one
small reversed currents only after a predetermined time- voltage transformation bctneen subtransmission voltage
delay and on large reversed currents without intentional and utilization voltage. In many cases these subtrans-
time-delay. mission circuits originate at a generator’bus. This makes
Primary Feeders-The primary feeders supplying a a simple distribution system with a direct path from gen-
low-voltage network generally are radial circuits because erators to consumer services.
the interconnection of the secondary mains and the opera- Automatic reclosing generally is not used on under-
t,ion of the network protectors provide means of maintain- ground supply circuits in a network system for two rea-
ing service to all loads on the network independent of the sons. The first is that faults in cable circuits operating at
loss of any one feeder. In underground systems the feeder more than 600 volts seldom clear when they are deener-
circuits are usually lead-sheathed cables. Both three-con- gized. The second reason is that in the network system
ductor and single-conductor cables are used. Three-con- it is not necessary to reenergize a supply circuit as quickly
ductor cables frequently arc used for the main feeders be- as possible to minimize service interruption because a
cause of the lower cost. Single-conductor cables frequently supply circuit fault does not drop any network load.
arc used for sub-feeders and laterals because single-conduc- Furthermore, the network system allolvs a faulted SUPPLY
tor cables facilitate making the large number of splices and circuit to be repaired deliberately, using’!is much time and
joints required on these sections of feeders. taking whatever precautions are necessary to insure a good
The primary feeders to a secondary network may origi- repair job, without interrupting load.
nate at a distribution substation, at a bulk power sub- The secondary-network system is well adapted to bus-
station, or at a generating plant. The primary feeders voltage regulation because the network load is divided
should originate at the same substation or at substations almost equally among the feeders or subtransmission cir-
that are closely tied together62 because the feeders are cuits supplying the network and consequently the same
paralleled through the low-voltage secondary mains of the relationship bet\vccn bus voltage and load voltage is satis-
Chapter 21 Primary and Secondaq Network Distribution Systems 707

factory for all the network supply circuit,s. Feeder-voltage secondary mains. hIost of these faults either are arcs or
wgulat,ion seldom is used because of voltage differences” have less thermal capacity than the secondary-main con-
that may be introclrlced between feeders by the individllnl ductor; this type of fault is cleared quickly without inter-
regu!ntors. This is purt,icl&rly true of three-phase induc- rupting loads. ;\ fe\v faults have high thermal capacity
tion regulators because they may introdllcc an angular and must be cleared by fusing the conductor between the
displacement as well as an in-phase voltage difference. fault and adjacent junction points in the grid. Such faults
Fllrthermore, bus-voltage regulnt.ion is generally more eco- may result in dropping all the load on one section of sec-
nomic~nl. When network feeders are supplied from a gen- ondary main. However, such faults occur infrequently.
cxr:ttor I)rls, grlnolator-voltage regulation can be used if the Primary-Feeder Faults are cleared by opening the
voltage variations required by the netn-ork loads are satis- breaker at the s~lpply end of the faulted feeder and opening
factory fur ot,her loatls served from the same generator bus.all the network protectors in network units associated with
the faulted feeder. None of the load is dropped and the
12. The Overhead Network total load divides among the remaining feeders. When the
The overhcnd secondary network39 follows the same faulted supply circuit is repaired it is returned to operation
general p&tern as the undergrolmd network and differs by closing its breaker. When the feeder is reenergized with
from the underground network primarily by having the the correct voltage, the protectors that opened because of
sccomlnry mains, n&work units, and in many cases the the fault reclose and the feeder again carries its share of the
primary feeders ovcrhentl on poles. &tensions of the load. A transformer fault is isolated in the same manner as
fringe of an underground network frequently are carried a primary-feeder fault. If the transformer is equipped with
overhead in arcas whew underground construction is not a high-voltage disconnecting switch the faulted trans-
Ilscd. The secondary mains are supported by racks or former can be switched off the deenergized feeder and that
messenger cables. The network transformers and net- feeder can be returned to service. However, t,his is not
work protectors are mormted on poles or on platforms necessary, if the transformer can be replaced in a reason-
depending on t,he size of the network unit. In areas where ably short time, because the network system must be
overhead construction is used load densities are generally capable of carrying the total network load with any one
lower than in underground areas and the network trans- feeder out of service.
formers are correspondingly smaller. Transformer ratings I-nder emergency conditions with one feeder open the
most frequently used in overhead networks range from 50 load is distributed among the network units supplied by
to 150 kva. The network protectors41 used in overhead the feeders remaining in operation. Under these conditions
network systems are generally smaller than protectors for the voltage regulation at some points in the network, par-
Imderglound systems but operate in the same way. Over- ticularly those where a network unit is disconnected from
head secondary-network main conductors are smaller than the grid, will not be as good as under normal conditions.
underground-network main conductors and faults are The amount by which the voltage drop under emergency
burned clear as they are in the underground network. When conditions exceeds that for normal operation depends to a
the secondary-main conductors are mounted in the open considerable extent on the uniformity of the load distribu-
on racks in the overhead network, a definite spacing is tion among the netlvork units during an emergency.
maintained between the conductors and faults are more Load Division- The uniformity of load division
easily cleared than in underground mains. The fault cur- among the network units for either emergency or normal
rents required to clear faults’on overhead secondary mains operation depends on the ratio of the impedance of a
are shown in Table 2. section of secondary main to the impedance of a network
transformer. The load division between transformer banks
13. Operation of the Secondary Network on a network generally is satisfactory if the ratio of main-
Normally all primary feeders of the network system are to-transformer impedance is three or less and if the trans-
in operation and carry a proportionate share of the total formers are correctly selected as to size and properly
network load according to the transformer capacity served located with respect to the major loads on the network. In
by each feeder. Each load on the network is supplied by general, load division under normal operating conditions
not less than two paths and the load inherently divides so has not proved to be a serious problem on network systems
that the best possible voltage is maintained at all points because, when enough transformer capacity is provided to
in the network grid. As loads change, the division of load prevent overloading with a primary circuit, out of service,
changes so that equal voltage drop is maintained from there is sufficient capacity to take care of the normal differ-
adjacent transformers to every point on any interconnect- ence in loading of the banks. If in isolated cases a bank
ing main. Thus, for any given load conditions the least of transformers is carrying much more than its share of the
possible voltage drop to services is obtained. Since there load, this can be corrected by installing a larger bank, a
are at least two paths of supply to any load tap in the duplicate unit, or external reactor9 in series with the
secondary grid, abrupt changes of load-such as starting existing bank on the secondary side.
large motors 36*48-cause less voltage disturbance in a net- The choice of transformer impedance for the network
work system than in a system having radial secondary unit depends on its effect not only on load division but
mains, even if the radial system were designed for the same also on fault currents, circulating currents, and voltage
steady-lost1 voltage drop as the network system. regulation. Other things being equal, the lower the im-
Faults in Secondary Mains are burned clear as ex- pedance of the transformers the better the voltage regula-
plained previously in the description of the network tion, the higher the fault currents, the higher the circulat-
708 Primary and Secondary Network Distribution Systems Chapter 21

ing currents between primary feeders, and the poorer the TABLE ~-RELATIONSHIP BETWEEN TRANSFORMER CAPACITY
load division between transformer banks. Improved volt- AND PEAK LOAD IN A SECONDARY-NETWORK SYSTEM
age regulation and, in most cases, higher fault currents to
Ratio of PC& Land To Trnnsformcr CtLpacity
insure burning secondary faults clear favor the use of low- Sumbcr of Feeders
impedance transformers. High transformer impedances, I&xl Usunlly .4ttctinablc
such as seven to ten percent, have been used, particularly
2 0.50 0.40
in early installations of the secondary n&work, to improve
3 O.GT 0.54
load division and to reduce circulating currents betiveen 4 O.Td 0.58
banks at times of light load and the resultant undesirable 5 0.80 0.60
network-protector operations. Circulating currents are 6 0.53 0.61
caused by voltage differences between primary feeders,
resulting from such factors as supplying the feeders from
different buses, differences in feeder-voltage regulators, or impedance of about five percent provides satisfactory oper-
tapping large radial loads off one or more of the network ating conditions. The majority of network transformers
primary feeders. Rclativcly high impedance in the sec- in operation have impedances ranging from four to six
ondary mains between lo\v-impedance transformers re- percenLF3 If an impedance outside this range appears de-
ducts the circlllating currant, but results in poorer distribu- sirable, the et’fect on voltage regulation and lamp flicker
tion of load between transformer banks, both under nor- should be carefully considered.
mal conditions and when one primary feeder is out of Interlacing sl~ppiy Circuits-The maximum load on
service, than wo11ld be the case if lower-impedance sec- transformers in a network system lvhen one feeder is out
ondary mains ncre used. Generally a netn-ork-transformer depends not only on the ratio of secondary-main imped-
ance to transformer impedance but also on the pattern of
A B c D E A B c D E the primary-feeder connections to the transformers in the
network. This latter effect is illustrated in Fig. 11 for a
uniformly loaded, regularly spaced network. Tivo ex-
E A B c D
tremes of primary feeder routing are shown in Figs. 11(a)
and 11(b). One extreme is the parallel primary-feeder
II E A B c arrangement in which all transformers along one line of
secondary mains are connectecl to one primary feeder as
C D E A B
shown in Fig. 11(a). The other estreme is the interlaced
primary-feeder arrangement in lrhich each transformer
connected to one feeder is surrounded by transformers, at
B C D E A adjacent junction points, that arc connected to other feed-
ers. The curves in Fig. 11(c) show that the maximum
(b) transformer load when one feeder is out of service is con-
siderably less, for all practical impedance ratios, with inter-
laced feeders than with parallel feeders.
Ratio of Load to Transformer Capacity-In order
to avoid overloading the transformers in a network it is
necessary to provide enough capacity in the network units
so that the maximum loading on any unit-when one feeder
is out of service does not exceed the capacity of the unit.
The necessary installed capacity depends on how well the
load divides among the units as determined by impedance
ratio and feeder interlacing and on the number of feeders
supplying the network. Under ideal conditions it is neces-
sary to have twice as much transformer capacity as total
load in a network served by two primary feeders, SO that
the network units served by one feeder can carry the total
12oL
0
’ ’
I
’ ’
2 3 4
load when the other feeder is out of service. For networks
RATIO OF MAIN IMPEDANCE
supplied by six feeders or less it is reasonable to assume
TO TRANSFORMER IMPEDANCE that not more than one feeder will be open at any time
(c) during peak load. Table 3 gives the ideal ratio of peak
Fig. 11-Effect of interlacing primary feeders on load division load to total transformer capacity in a etwork for two to
among the network units remaining in service in a regularly six interlaced feeders. Increasing the ?l umber of feeders
spaced uniformly loaded network when one feeder is out of from two to three and from three to four improves the
service. (a) Five feeders, A, B, C, D, and E, running parallel ideal ratio rapidly; but, as the number of feeders is in-
through the network area. (b) F ive feeders, A, B, C, D, and E, creased further, the saving in transformer capacity de-
interlaced in the network area. (c) Maximum load on any
network unit with any one feeder, out of a total of five supply- creases so that there is little gain in using six feeders in-
ing the network, out of service: Curve A for parallel feeders stead of five. This is especially true for the ratio that usu-
and Curve B for interlaced feeders. ally can be attained. The ideal ratio can be realized only
Chapter 21 Primary and Secondary Network &?ribution Systems 709

if the transformers can be loaded exactly to their capacities two paths of supply to each service tap, the load currents
and if the load divides uniformly among the units in divide among the secondary mains in such a way that min-
service at any time. These conditions do not occur in imum losses are obtained for any given load condition.
practice and the ratio that actually is obtained is usually Maintenance and repair work on the system can be done
abollt that shonn in the right hand column of Table 3. The under the most favorable conditions because any element
ratio of total peak load to total transformer capacity of 121 in the system, except secondary mains, can be isolated from
netsvorks in 1937 was 0.44.‘j3 This value is based on esist- the system without interrupting any load. One operat.ing
ing load and transformer capacity; the transformer capa- disadvantage is the large number of network protectors
cit,y in the a&la1 networks probably provides for some that must, be maintained.
load growth beyond the existing loads. The factors in The interconnected secondary grid places the duplicn-
Table 3 are based on loads for which a network is designed tion of supply paths as close as possible to the loads being
and n-hich include provision for load growth. If allowance served. For this reason the secondary-network provides
is made for this discrepancy, the ratio of 0.44 is compara- better continuity of service than any other distribution
ble to the average of the attainable ratios in Table 3. system esccpt the d-c network system. The high cost of
the d-c network system eliminates it from consideration in
14. Economic Field of Application the selection of a distribution system especially since it
The simplicity of the secondary-network system is an affords no greater reliability than the a-c seconclary net-
economic advantage in many cases. In many distribution work. The grid arrangement of the secondary mains also
systems subtransmission circuits can be carried directly provides the best possible voltage conditions at the loads
from bulk power stations to the distribution or network consistent with economical system design. The voltage
transformers. This means that a considerable saving can regulation at the service taps on a secondary network sys-
be made by eliminating the distribution substation nor- tem generally is better than that provided by other sys-
mally required by other systems. Another source of sav- terns. This IS particularly true from the standpoint of
ings results from eliminating the duplication of primary lamp flicker because abrupt load changes can divide be-
feeders or subtransmission circuits and the accompanying tween at least two paths of supply.
high-voltage switchgear required in radial systems to pro- Generally if high quality of service is required in any
vide a high degree of reliability. Secondary copper can be load area the secondary-network system is the most
saved in many cases because the interconnected grid elim- economical means of supplying power. Under certain con-
inates the need for separate secondaries frequently required ditions the secondary-network system is the most eco-
in radial systems for light and power loads. Capacity can nomical system even when a high degree of reliability is
be added in the secondary-network system in even smaller not necessary. This is generally true where the entire
increments than in the primary network. The economic distribution system is underground because a radial sys-
advantage of adding small increments, as explained in the tem requires many switching and sectionalizing devices
discussion of the primary network system, is more pro- and duplication of subtransmission circuits and primary
nounced for the low-voltage network than for the primary feeders to avoid long interruptions of service while cable
network. circuits are being repaired. Faulted overhead circuits
The relatively large amount of secondary switchgear, usually can be returned to service in a reasonably short
in the form of network protectors, tends to make the in- time, but a much longer time is required to locate and re-
stalled cost of the network system higher than that of a pair a fault in a cable circuit. The economic comparison13
radial systeA and counteracts part of the gain from the of typical distribution systems shown in Fig. 4 shows that
simplicity of the subtransmission and primary-feeder part if all distribution circuits are open-wire the overhead net-
of the secondary-network system. Interlaced primary work is likely to be the least expensive system for uniform
feeders in the secondary-network system require more load densities above about 3000 kva per square mile. A
feeder circuit than do parallel feeders. They may require similar comparison40 of systems in a uniformly loaded area
more feeder circuit than a radial system using duplicate where all subtransmission and primary circuits are under-
feeders or primary switching to provide for isolating a ground, as shown in Fig. 12, indicates that in such load
faulted primary feeder or section of feeder. The additional areas the overhead network (Curve E), may be economical
feeder circuit required by interlacing usually is compen- for load densities above about 3600 kva per square-mile.
sated for by the saving in network-transformer capacity. The comparisons shown jn Figs. 4 and 12 are based on an
The use of primary switches in the network units counter- area of sixteen square miles in which the load is assumed to
acts some of the savings resulting from the elimination of be uniformly distributed and to grow uniformly at a con-
many automatic breakers in the subtransmission circuits stant rate of ten percent per year. Although such uniform
or primary feeders. conditions do not occur in actual cases the comparisons
The low-voltage network generally has an economic ad- show trends that are likely to occur in actual cases. In
vantage from the standpoint of operating costs. System actual cases the load generally is not uniformly distributed
losses are generally lower in the secondary network than in and the load growth usually varies from year to year and
other systems of comparable load capacity chiefly because from section to section. The fact that the secondary net-
of two factors. One of these is the simplicity of the sub- work can be expanded in small increments is of greater
transmission circuits and primary feeders and, in many advantage under such conditions than under uniform load
cases, the elimination of the distribution-substation trans- conditions, as explained in connection with the primary-
formers. The other factor is that, since there are at least network system (See sections 6 and 7). This factor is
Primary and Secondary Network Distribution Systems

the various transformers and primary circuits in such a


way that calculations of the characteristics of the system
by ordinary methods become tedious. There are two
general methods of planning a network system. One is to
use a network calculator or a miniature system67 to de-
termine the characteristics of an estimated system arrange.
ment and then make such revisions as are required. The
other method is to estimate a plan and then by inspection
estimate the division of load for various conditions; the
plan is then revised until the estimated load division gives
satisfactory conditions. The first method is more sati&
factory because it shows accurately the operating charac-
teristics of the plan being considered while the accuracy of
the estimation-by-inspection method can be determined
only after the system has been installed. The network-
calculator method is described briefly in the following
paragraphs.
The first step is to concentrate the loads, in the proper
units, at various points throughout the network so that a
reasonable number of circuit elements can be considered,
In order to do this the secondary-main arrangement that
appears best should be drawn. This step is illustrated by
the mesh of solid lines in Fig. 13 for a section of a typical
network area. The numbers distributed inside tlie dotted
building areas in Fig. 13 are present loads at service points
and are in terms of diversified kilowatt demand at the
distribution transformers. After the secondary grid is
drawn the distributed loads along each section of main are
LOAD DENSITY-KVA PER SQUARE MILE concentrated at the junction points. A good approxima-
Fig. 12-Relative cost of several types of distribution systems, tion is to divide each load between the adjacent junctions
for various load densities in a sixteen-square-mile area where in inverse proportion to the distances between the load and
the uniformly distributed load grows ten percent per year, on the junctions. After these loads are concentrated at junc-
the basis of all subtransmission and 4-kv primary feeders
underground and secondaries overhead. See Fig. 4 for the
tion points they are converted to ultimate kva of diversified
type of system represented by each curve. demand, at the transformers, for which the network is to
be designed. In the typical example the present loads are
increased by a factor of 1.4, providing for 25-percent load
even more important in the secondary network than it is growth (or approximately seven percent annually for three
in the case of the primary network because the secondary- years) and converting from kilowatts to kva at go-percent
network units are smaller than those in t,he primary net- power factor. The loads are then of such size and 90
work and system capacity can be changed in correspond- located that they can be represented OTPa network calcu-
ingly smaller increments. lator conveniently, and they accuratgy represent load
conditions in the network area for which the network must
15. Planning the Secondary Network be designed. Where a large individual load is served from
The planning of a network system is not as straight- a point along a section of main it is preferable to consider
forward as that of a radial system but the procedure is that load at that point and possibly locate a transformer
relatively simple.‘l The ideal method is to use a calcu- adjacent to the load, even if there is no junction with other
lating board because it is,practically impossible to calcu- secondaries. This condition is illustrated at point e in
late the characteristics of a network by other means. As Fig. 13. The load near some points, such as i, may be so
in any planning problem, it is necessary to have adequate light that a concentrated load need not be considered but
information (loads, available supply, existing facilities, secondary mains should be provided to insure good load
and available circuit locations) on which to base the division among the various parts of the network for
design of a network. With this information available the emergency conditions.
procedure then is to lay out by estimation an apparently The layout of the secondary grid isimade on the basis
feasible plan. This plan is then studied on a network of the locations of the loads that must be served and the
calculator or by inspection and revised until a good design routes of existing secondary mains. In most cases existing
is obtained. secondaries almost completely cover the area and it is
Preliminary Estimates-In a radial system primary only necessary to connect these secondaries into a contin-
and secondary circuits can be laid out and regulation, uous grid. In some places it may be desirable to add
transformer capacity, and circuit capacity can be calcu- sections of main to provide multiple paths to certain loads
lated directly by arithmetical means. This is not true in for emergencies when adjacent transformers are out of
the case of the network because the loads divide among service.
Chapter 21 Primary and Secondary Network Distribution Systems

\(85) ----
b \(112)
---
C \rw d
G-L5 3 2 I7 G-2: I I 23 ?I--3--?3---6T4--T6--1
,

I I
I’ I
I
19 /
’ 12 1.8 0.6 -4 0.5 9 5 6 j

\ne)
--- -----_-___----
I.5 1 1
I I
I I
Fig. 1LPresent distributed loads along the secondary main, in terms of kw of diversified demand at the distribution trans-
former, and the corresponding concentrated loads at the intersections of the mains, in terms of diversified kva demand includ-
ing estimated load growth, form the basis for designing a secondary network in a typical load area.

When the loads and secondary plan have been deter- sizes. In addition, multiple unit installations improve load
mined the approximate sizes and locations of transformers distribution and voltage regulation at the large loads for
can be selectecl. The transformer size will depend on the emergency conditions.
t,ype of system, size of concentrated loads, number of After tentatively selecting sizes and locations of trans-
feeders available, the feeder interlacing obtainable, and formers a size of secondary main is selected. This size de-
spacing of the transformers. In general, the larger the pends on the required carrying capacity, estimated regu-
transformer the lower the cost per kva and the wider the lation, and size of existing secondary copper. The carrying
spacing between transformers in the network. But as this capacity should be adequate to carry one-half to two-
spacing is increased the secondaries must be larger to keep thirds of the rated capacity of the predominating size of
secondary voltage drop within reasonable limits and to transformer. The voltage regulation for normal operation
provide adequate carrying capacity. As the number of can be estimated by calculating the voltage drop to the
transformers is reduced less primary cable is required. distributed loads along some sections of main where in-
The ideal size of transformer then is that which not only spection indicates the worst regulation is likely to prevail.
handles the loads but also gives a minimum total cost The primary-feeder connections to the various trans-
including costs of primary feeders, transformers, and formers must be carefully selected to avoid, if possible,
secondary mains. In the initial trial plan for the network adjacent transformers being out of service when any one
the transformers should be located at the major loads and feeder is open. This is accomplished by int,erlacing the
at the various junctions where the concentrated loads are primary feeders. In a network plan where the trans-
large enough so that the distance between transformers is formers are spaced regularly and uniformly throughout
not greater than about two blocks or 600 to 800 feet. the area the interlacing of feeders, such as A,B,C,D, and
Usually the spacing is less than this because of the locations E, can be shown in Fig. 11(b). In actual interlacing
of loads. It is generally desirable to select not more t,han problems the network units are seldom regularly spaced.
two sizes of network transformers. This permits stocking However, the interlacing is simplified by using some basic
fewer spare transformers and protectors. Also, inter- system, such as that illustm,ted in Fig. 11 (b) and modify-
changeability of units and parts is increased by using only ing the order of the feeder connections where necessary
one or two sizes. At points where large concentrated loads because of the absence of a transformer or the use of
are served it is desirable to use multiple installations con- multiple units. When the interlacing has been selected,
sisting of two or more transformers rather than one trans- a map of primary feeder routings is made. It may be pos-
former much larger than the rest of the units. This avoids sible to change some of the feeder connections to save
a large number of sizes and the use of a few units of a size feeder cable and still retain good interlacing.
that is not interchangeable with any of the predominating By means of the preliminary estimates the location and
712 Primary and Secondary Network Distribution Systems Chapter 21

ratings of transformers, feeder interlacing, secondary-grid


arrangement, and secondary-copper size are selected so
37
that a reasonable network plan is established. This plan
can then be simulated on the network calculator on the
basis of the impedances of the various circuit elements. 37
The impedance of the primary feeders is usually low enough
that its effect on the characteristics of the network is
negligible. The impedance of a primary feeder is usually
not larger than about 0.5 percent on the basis of the rating
7-l 7-l
of the largest network transformer or about one-tenth of
the impedance of the transformer. Every case should be
checked and if the primary-feeder impedance exceeds this 77 37 77
value it may be necessary to consider the impedance.
Whether or not the primary-feeder impedance is considered /’
FAULT
also depends on the primary-voltage regulation. If the
drop in the primary can be compensated for so that ap- 7-l h 37 37 77
proximately constant primary voltage is maintained at a a

R
the primary terminals of the network transformers the
primary-feeder impedance should not be considered in
load studies.
37 37 i7

Checking the Preliminary Plan--With the estimat-


ed plan set on the network-calculator, check studies can
be made to determine the accuracy of the preliminary 77
estimates. It may be necessary to change transformer
capacities or locations, interlacing, or secondary copper to (0)
avoid overloading or inadequate use of some elements of
the network. Then with a final plan determined, the
characteristics of the network can be completely and ac-
curately determined by means of the network calculator.
All reasonable operating conditions should be investi-
gated. For example, the load division among the network
units should be determined with each primary feeder out
of service. Typical load division results obtained from
the network calculator are shown in Fig. 14 for the typical
area for the case when feeder “A” is open. By means of the
network calculator the maximum load on any element of
the network, the voltage regulation under various condi-
tions, and the available fault currents can be determined.
These data show whether any of the elements of the net-
work are overloaded and whether secondary faults can be
cleared. Necessary revisions of the plan can then be made

MAIN IMPEDANCE
2 RATIO=
TRANS. IMPEDANCE
(c)

Fig. f5-Short-circuit currents in regularly spaced network


234 301 3’o 270 176 for various ratios of the impedance of a section of secondary
main to the impedance of a network transformer. (a) An ex-
206 206 t
30 336 I4 tensive network having 45 network transformers all with the
ft
cq same rating. (b) A small network having nine transformers
-62 0\ 0 all with the same rating. (c) Ratio of total fault current from
the network to the short-circuit current f one of the network
126 216
transformers for a solid three-phase fa 1 lt at the secondary
246 i 72 terminals of the transformer at the center of the network.
1 Curve A is for the network shown in (a) and Curve B is for the
network shown in (b).
16- i 12- ‘I\ 40 -

“r

115Y
,a..

200 i? and a workable design developed. The sum of the loads


on the transformers connected to any primary feeder
TRANSFORMERS- +I50 KVA, -100 KVA, LOADS - -
indicates the required capacity in that feeder.
Fig. 14-Loads in amperes in variouselements of a typical sec- The network calculator provides the best means of de
tion of a secondary network in an emergency when feeder A is termining the fault currents in a network. However, if
out of operation. approximations are necessary, the curves in Fig. 15(c) shorn
Chapter 21 Primary and Secondary Network Distribution Systems 713

the current to a fault at the center of large and small net- units. The network units in the building are interconnect-
\vorks having regularly-spaced equal-capacity network ed by secondary ties that usually are connected to the
llnits. The CIII’VESgive the ratio of the total current from secondary-network grid in the streets adjacent to the
the netn-ork to the short-circuit current of a network tmns- building. In some cases the secondary ties between the
former. As indicated by the curves the ratio increases as network units in the building do not serve any loads and
the ratio of secondary-main impedance to transformer the loads on the various floors between network units are
impedance decreases. Total current from the network supplied by short radial services from the network units.
tl~es not include the current from the transformer at the In other cases the tie circuits are tapped to serve the
f:Lult, point. The total fault current from the network loads on the floors between network-unit locations. The
tlivities equally among the four secondary mains terminnt- tapped secondaries may have to be somewhat larger than
ing at the faulted junction point. One or the other of the untapped ones because the tapped ties have to supply
:Lrrnngcments shown in Fig. 15(a) or 15(b) usually approxi- loads as well as equalize the loads on the various network
mates the actual n&work arrangement where fault CUT- units. However, tapping the secondary mains between the
rcnt,s arc to be estimated. To use the curves it is first network units eliminates the radial service circuits required
necessary to determine the average impedance of the when the ties are not tapped.
network-main sections surrounding the fault point. The The secondary network uses considerably less copper
ratio of this impedance to the impedance of a transformer than does a radial system because power is carried to the
in the actual network is the entry point to the curve for various levels in the building over subtransmission or
tlctcrmining the C ratio of the network, Fig. 15 (a) or (b), primary-feeder circuits instead of over large low-voltage
1hat approximates the actual network. Multiplying the services from secondary mains outside the building. Fur-
short-circuit current of the transformer, whose impedance thermore, the network generally provides better voltage
is the basis of the main-transformer impedance ratio, by
C ratio gives the total fault current supplied by the net-
work. In a network having only one size of transformer
the impedance and short-circuit current of that size trans- NETWORK UNITS
former is used for calculating fault currents. If there is
more than one size of transformer in the actual network
the predominating size is used. The fault currents de-
* I
tctrmined in this way are correct only for a network ar- 1 -
TIE TO STREET SERVICES
rangement like that in Fig. IS(a) or 15(b) for which the C NETWORK (0)
ratio is determined. The effect of minor deviations from
the regularity of the arrangement will depend on how
close the deviation is to the fault point. The effect of
deviations remote from the fault point is indicated by the
fact, that each main a, Fig. 15(a), carries 3.5 percent of the
total fault current from the network when the impedance
ratio is 0.3 and a smaller percentage when impedance ratios
we higher. Each transformer T supplies less than three
percent of the fault current from the network for any
impedance ratio.
16. Special Applications TIE TO STREET
NETWORK (b)
The high degree of reliability, the simplicity of opera-
tion, and the economy of the secondary-network system
are desirable in several special cases such as in large or
multi-story buildings, bulk loads where continuity of
service is important, in generating plants for supplying
auxiliary motors, and in industrial plants. The application
of the secondary network in some of these cases involves
modifications of the network system but the basic prin-
ciples of operation remain unchanged. SPOT NETWORK BUS L
Building or Vertical Networks-Fire pumps, eleva- TIE TO STREET t ) SERVICES
tors, and similar services in tall buildings require a high NETWORK
degree of reliability that can be provided most economical- (Cl

1~ by a secondary-network system.““J4s38Such buildings Fig. 16-Typical spot networks. (a) Two network units sup-
we almost invariably located in an underground-network plying a spot network bus from which services are tapped. (b)
area. Network units are located at several levels accord- Two network units connected to spot-network bus through
ing to the location and size of the major loads in the build- reactors. Services are supplied directly from terminals of net-
work units. (c) Two network units supplying a spot-network
ing. The primary feeders or subtransmission circuits that bus through balancing transformers. Any of these forms of
supply the street network surrounding the building are the spot network may or may not be connected to the sec-
extended up through the building to the various network ondary mains of a street network.
714 Primary and Secondary Network Distribution Z&terns Chapter 21

conditions, particularly in the upper floors of the building, of circulating current through the network units. The
and less loss because of the reduction in the length of low- secondary winding of a balancing transformer must he
voltage, high-current circuits. The secondary network short circuited, when its associated network protector
utilizes all the diversity among the loads in the building to opens, to prevent high voltage drops in other balancing
reduce the circuit and transformer capacity required to transformers interconnected with the balancing tran+
supply the building load. former whose primary circuit is open.
The Spot Network is frequently used to supply a The use of balancing transformers permits taking serv-
concentrated load such as a theater, a hospital, or a small ices from a common bus. It is not necessary to have equal
industrial plant where a high degree of reliability of scrv- loads on the services. The service loads can be totalized hY
ice is necessary. (2 In its simplest form a spot network is a current transformers and simple metering.cquipment using
hus to which power is supplied by two or more network the common bus potential. Motor starting currents and
units, each of which is supplied by a separate primary similar abrupt loads divide bctwecn the network units thus
feeder or subtransmission circuit, Fig. 16(a). The opera- reducing the likelihood of lamp flicker. Balancing trane
tion of the spot network is the same as that of the ordi- formers are generally used only when circulating currents
nary network. Instead of an interconnected grid of and consequent protector operations are likely to occur
secondary mains the spot network uses a concentrated frequently because of voltage diffcrenccs between the cir-
bus from which the loads are served. cuits supplying the network units. Inequalities of load
Since a spot-network is a relatively low impedance path division among the network units usually do not justify
between the associated supply circuits large circulating balancing transformers because sufficient network-unit
currents through the spot-network units, frequent pro- capacity must be installed so that the total load can hc
tector operations, or extremely unequal load division carried with one unit out of service.
among the spot-network units may result from large When a spot network is located in a secondary-network
voltage differences between the supply circuits because of area the spot network bus is frequently tied to the street
other loads on those circuits. The most common methods mains of the surrounding secondary network as shown in
of reducing circulating currents and equalizing load di- Fig. 16. This may improve the reliability of the spot
vision are shown in Figs. 16(b) and 16(c). ReactorsT3 are network. It takes advantage of diversity between the
relatively inexpensive but their use depends on the prac- spot-network load and the loads on the surrounding nct-
ticability of dividing the load into parts approximately work to reduce the capacity required in the spot network.
proportional to the transformer capacities. Because the Power-Plant Networks--The continuous operation
network units usually are of equal rating the loads on the of a steam generating plant depends not only on tho
services must be nearly equal. In the scheme shown in reliability of the generators and boilers but also on the
Fig. lti(b) the voltages at the services are not necessarily reliability of the auxiliaries such as draft fans, fuel hnn-
eqllal and each service must be metered separately. Total- dling equipment, boiler-feed pumps, and cooling-wntor
izing the loads, where that, is necessary, requires complicat- pumps. Therefore it is extremely important that the
ed equipment. Starting large motors on one of the services power supply for the motors driving the auxiliaries bo ab
is more likely to cause lamp flicker in the scheme in Fig. reliable as possible. Many schemes are devised to improve
16(b) than in a scheme where the services are supplied the reliability of the power supply to the auxiliaries. Thcso
from a common bus. schemes use duplicate buses, duplicate transformers,
To avoid the difficulties involved in the use of reactors, throw-over switching, and various other devices. In many
balancing transformers 37frequently are used as shown in cases a secondary network is idcal not only from the
Fig. 16(c) although they are more expensive than reactors. w

The balancing transformers operate like differentially GENERATOR BUS


t 1
connected current transformers in the secondary leads of ‘/ ‘/ ‘/ /
the network units. Equal load currents in the leads of the
network units induce voltages in the differentially con-
nected secondary windings of the balancing transformers.
These voltages add and cause a circulating current in the
balancing-transformer secondaries. This circulating cur-
rent is in such a direction in each transformer that it
essentially neutralizes the magnetomotive force due to the
load current flowing through the primary winding of each
balancing transformer, and there is practically no voltage
drop in the balancing-transformer primary windings to
oppose the flow of load current. If only a circulating cur-
rent flows in the secondary leads of the network units, 1 _ L/SECO_NDARY 1/ NETWORK L/ MAINS
that is, toward the spot-network bus from one unit and / /
from the bus to the other network unit, the voltages in
the balancing-transformer secondary windings oppose each
other. Therefore, there is no current in the balancing-
transformer secondaries, and there is a large voltage drop ark for
Fig. 17-Typical shematic diagram of a secondary netw
in the balancing-transformer primaries opposing the flow supplying power-plant auxiliaries.
Chapter 21 Primary and Secondary Network Distribution Systems 715

Otherwise the protectors may close and attempt to


parallel a generator with other generators through the
network system.
The utilization voltage for power-plant nusiliaries
usually is nominally 440 volts. Since faults on circuits
operating at that voltage frequent)ly do not clear with-
out being deencrgized, limiters are connected in the
secondary mains of a secondary network operating at
that voltage. The auxiliary load in a generating plant
is highly concentrated and consequently the possible
short-circuit currents in a power-plant secondary-net-
work system are usually much higher than in the
ordinary street network.
Small Towns--In the commercial areas of small
residential towns it is sometimes necessary to put the
distribution circuits underground. Under these con-
ditions the secondary-network system has been ap-
plied in many places where the load involved is only a
few hundred kva.55 These installations generally use
light-duty network protectors and network trans-
formers ranging in capacity from 50 to 150 kva.
These small networks are usually supplied by only
two primary feeders; in fact the supply circuits for
the network units usually are subfeeders from over-
head primary feeders that supply adjacent residential
areas. In some cases the voltage level on one of the
feeders is maintained enough higher than the other
that the protectors associated with the other feeder
are open under normal-load conditions and close only
when the feeder with the higher voltage goes out of
service or when an unusually high load peak occurs
on the network.
Fig. 18-A low-voltage network unit consisting of an air-
cooled transformer, a high-voltage three-position selector Industrial Plant Networks-The secondary-network
switch, and a network protector for use in industrial plants, system, Fig. 19, has been used to distribute power in in-
generating plants, and buildings. dustrial plants60~7°J2where a high degree of reliability and
flexibility for load changes frequently are required. The
standpoint of service reliability but also from the stand- utilization voltage most frequently used in industrial
point of economy.60*70A typical arrangement of the net- plants is a nominal voltage of 440 but it may be 220 or 550.
work system for supplying power-plant auxiliaries is shown For the voltages above 220 some means of isolating faulted
in Fig. 17. The network mains are carried through the secondary tie circuits is necessary because faults at those
plant according to load locations and the loads are sup- PRIMARY FEEDER POWER SUPPLY
plied from these mains. The network units are distributed SECONDARY LOOP

along these mains in accordance with the distribution of


load. Two or more primary feeders are used to energize
the network transformers.
It is necessary to have two or more circuits supplying
the network. To avoid using a breaker to connect each
of the primary feeders of the network to the plant bus
\vhere the interrupting duty and the corresponding breaker
cost are high, the primary feeders frequently are connected
to the generator terminals as shown in Fig. 17. The hazard
of a fault in a short primary feeder and the associated
RANSFORUER
network unit or units usually is small enough that it does NETWORK PROTECTOR
not jeopardize the operation of the generator. However,
there must be at least one network supply circuit con-
nected to the station bus or an outside source of power so
that the plant auxiliaries can be energized when all the
generators are idle. The network protectors associated
lvith a feeder supplied from the terminals of a generator
must be interlocked with the generator breaker SO that Fig. 19-Typical schematicdiagram of a secondary network for
when the breaker is open the protector is locked open. distributing power in an industrial plant.
‘716 Primary and Secondary Network Distribution Systems Chapter 21

DOWNTOWN
COMMERICAL

SERVED BY
SECONDARY
NETWORK

Fig. 20-A complete power system is a combination of generation, transmission, and several types of distiibution systems.
The particular combination of distribution systems used in any power system depends on economics and the types of loads,
load densities, and quality of service required in local areas. In this diagram A is a generating plant, B is a bulk power sub-
station; C is a plant where an industrial-plant network is applicable; D is an industrial plant served by a subtransmission
loop; E is a plant served by a single subtransmission circuit; F is a plant served by duplicate subtransmission circuits; C is
a distribution substation supplying radial primary feeders: H is a primary-network unit substation: J is a single-circuit
distribution substation supplying a primary feeder in a rural area.

voltages frequently do not burn clear. Furthermore, the REFERENCES


arcing and noise accompanying a secondary fault that General
burns clear are likely to disturb the personnel in a plant 1. Overhead Syslems Z?e/erenceBook, Sational Electric Light Asso-
where the secondary ties usually are overhead in conduit ciation, Xew York, 1927.
2. Electrical Distribution Engineering, Howard P. Seelye, LIcGraw-
or similar enclosures. Therefore, limiters or similar pro-
Hill Book Company, Inc., Xew York, 1!)30.
tcctive devices should be used in the secondary ties of an 3. Underground Syslems Rejerence Book, Xational Electric Light
industrial-plant network as shown in Fig. 19. Association, Kern York, 1931.
One modification of the secondary-net.work system for 4. Electric Distribulion Fundamentals, Frank Sanford, McGraw-
industrial-plant applications is the use of a secondary loop Hill Book Company, Inc., Xcw York, 1940.
instead of a grid. The load density in an industrial plant Primary Networks
is high compared to that in urban areas where networks r
0. 4-KV Network Saves 20 Per Cent, A. Il. Sweetnam, Electrical
are applied. For that reason the transformer capacity and World, Vol. 97, Starch 14, 1!)31, pages 500-503.
the corresponding fault current available is much higher 6. Fundamentals of the Medium-Voltage Network, D. K. Blake,
in an industrial-plant network system than that in street General Electric Review, Vol. 34, April, 1!)31, pages 210-216.
networks. Omitting cross ties in a plant network and 7. The Primary Network, R. LI. Stanley and C. I,. Sinclair,
using a simple loop for the secondary ties reduce the A.I.E.E. l’ransaclions, Vol. 50, X:0. 3, September, 1931, pages
available fault current. The use of parallel circuits in the 871-879, (discussion 879-884).
loop sections facilitates selective operation of the limiters 8. Protecting A Medium-Voltage Network, *John%. Parsons, Elec-
for isolating secondary faults. lric Journal, Vol. 28, September, 1931, pages 520-525.
Another modification of the network system generally 9. The Primary Network System, 1-I. Itichter, Electric Journal,
Vol. 28, December, 1931, pages 661-664.
used in the industrial-plant applications is a primary
10. Primary Ketwork Stations-Vault, Building, Outdoors, R. J.
selector switch by means of which each network unit can Salsbury and H. S. Moore, Elecfrical IVo~ld, Vol. 100, September
be connected to either of two feeders. Frequently the total 3, 1932, pages 304-307.
load on a plant network is not enough to justify more than 11. Year of Experience Solves Primary Network Problems, R. J.
two feeders. On the basis of street-network design this Salsbury and H. S. Moore, Electrical World, Vol. 100, November
requires about two units of transformer capacity for each 5, 1932, pages 624-626. I
unit of load. By using the selector switch the transformer 12. Short Circuit Tests Prove Primary Network, R.iJ. Salsbury and
normally supplied by a faulted feeder can be switched to a H. S. Moore, Electrical World, Vol. 100, December 24, 1932.
good feeder, thus keeping all the transformer capacity in pages 849-851.
operation. It is necessary to have only enough reserve 13. Primary Network Economical For hfedium-Load Densities,
John S. Parsons and Leonard M. Olmsted, Electrical Wo#
transformer capacity to permit any one transformer to be
Vol. 101, June 24, 1933, pages 835-838.
out of service because of a fault or for maintenance. In an 14. Primary Network Proves Advantageous in Boston, St. George
industrial plant where the transformers are all in a small T. Arnold, Electrical World, Vol. 112, August 26, 1939, pages
area the switching can be done quickly enough that the 590-592 and 648.
thermal capacity of the transformers permit them to carry 15. Simplified Primary Network Saves ~$110,160 on Investment, Fe
the overload that occurs while the deenergized transform- W. Floyd, Electric Light and Potuer, Vol. 18, Xovember, 19401
ers are being switched back into service. pages 47-49.
i
1 Chapter 21 Primary and Secondary Network Distribution Systems 717
I
1. Secondary Networks
R. Bullard, Electrical World, Vol. 99. April 23, 1932, pages 745
746.
IF. Underground Alternating Current Network Distribution for 40. Overhead Secondary Network Offers Real Economy, J S
Central Station Systems, A. H. Kehoe, A.I.E.E. Transactions, Parsons and L. hI. Olmsted, Electrical World, Vol. 99, May 7,
Vol. 43, June 1924, pages 844-853, (discussion pages 869-874). 1932, pages 808-813.
17. Motor Performance on Combined Secondary Networks, A. P. 41. Protectors For Overhead Networks, J. A. Butts, Electrical Jour-
Fugill, Electric Journal, Vol. XXII, July, 1925, pages 316-320. nal, Vol. 29, May, 1932, pages 245-247.
18. Evolution of the A.C. Network System, H. Richter, Elecfric 42. Spot Networks Installed In Chicago Region, C. E. Van Den-
Jou~al, Vol. XXII, July, 1925, pages 320-336, burgh, Electrical W&d, Vol. 100, September 3, 1932, pages 381-
19. Recent Development in Automatic Network Units, G. G. 382.
Grissinger, Electric JournaZ, Vol. XXII, July, 1925, pages 336- 43. Spot Networks Reduce Cost of Duplicate Service, John S.
338. Parsons and S. B. Griscom, Electric Journal, Vol. 29, November,
20. The Automatic Network Relay, J. S. Parsons, Electric Journal, 1932, pages 503-505 and 530.
Vol. XXII, July, 1925, pages 339-344. 44. New Reactors Limit Voltage Rise on Network Cables, C A
21. Regulators For Network Distribution Systems, E. E. Lehr, Woodrow, Electrical World, Vol. 100, December 17, 1932, pages
Electric Journal, Vol. XXII, July, 1925, pages 344-345. 822-825
22. Regulators on Setwork Feeders, C. C. Hudspeth, Electric Jour- 45. Voltage Regulation of Cables Used For Low-Voltage AC Dis-
ml, Vol. XXII, July, 1925, pages 346-347. tribution, II. R. Searing and E. R. Thomas, A.Z.E.E. Trans-
23. No-Winding Reactors For Paralleling Transformers and For uctiorLs, Vol. 52, No. 1, March, 1933, pages 114-120.
Secondary Networks, J. S. Hebrew, Electric Journal, Vol. 46. Application of Phase Sequence Principles To Relaying of Low
/ XXIII, June, 1926, pages 329-332. Voltage Secondary Networks, H. R. Searing and R. E. Powers,
24. Evolution of the Automatic Network Relay, John S. Parsons, A.I.E.E. Transactions, Vol. 52, No. 2, June, 1933, pages 614-
A.I.E.E. Transactions, Vol. 45, November, 1926, pages 1195- 620, (discussion pages 626-629).
1202, (discussion pages 1220-1227). 47. Voltage Regulation and Load Control, H. C. Forbes, and H. R.
25, Operating Requirements of the Automatic Network Relay, W. Searing, A.I.E.E. Transactions, Vol. 53, 1934, pages 903-909,
It. Bullard, A.T.E.E. Transactions, Vol. 45, November, 1926, (discussion pages 1525-1528).
pages 1203-1211, (discussion pages 1220-1227). 48. Motor-Starting-Current Steps Based on Connected Load,
26. Combined Light and Power Systems for A.C. Secondary Net- Thomas .J. Brosnan, Electrical World, Vol. 103, April 28, 1934,
works, H. Richter, A.Z.E.E. 7’ran.~aclions, Vol. 46, February, pages 608-609.
1927, pages 216-234, (discussion pages 234-239). 49. Distribution System Within Rockefeller Center, Electric Jour-
27. Low-Voltage AC Networks, D. K. Blake, General Electric Re- nal, Vol. 31, &lay, 1934, pages 180-183.
view, Vol. 31, February, &larch, April, hlay, August, September, 50. Load Division in Networks, L. M. Olmsted, Etectric Journal,
and November, 1928, pages 82-84, 140-143, 186-190, 215-248, Vol. 31, June, 1934, pages 226-227 and 232.
440-443,480-482, and 600-604, and Vol. 32, March 1!)29, pages 51. Improving the Division of Load In Networks, L. M. Olmsted,
/ 170-173. Electric Journal, Vol. 31, July, 1934, pages 268-271.
/ 28. Developments in Network Systems and Equipment, T. J. 52. Limiting Voltage Rise on Cable Fed Networks, R. E. Powers,
( Brosnan and Ralph Kelly, A.I.E.E. Transactions, Vol. 48, No. 3, Electric Journal, Vol. 32, July, 1935, pages 290-293.
, July, 1929, pages 967-975, (discussion pages 975-976). 53. Secondary Network Goes Overhead, R. 0. Sutherland, Elec-
29. Low-Voltage AC Networks of the Standard Gas and Electric trical World, Vol. 106, April 25, 1936, pages lliO-1172 and 1249.
1 Company’s Properties, R. hI. Stanley and C. T. Sinclair, 54. A New Thermal Fuse For Network Protectors, L. A. Settleton,
A.I.E.E. Transacfiom, Vol. 49, INO. 1, January, 1930, pages 265- A.I.E.E. Transactions, Vol. 55, October, 1936, pages 1096-1099,
279, (discussion pages 280-284). (discussion Vol. 56, pages 1031-1032).
30. Vertical Distribution In World’s Tallest Structure, J. A. 55. Small Underground Networks, J. A. Pulsford, Electric Journal,
I Walsh, Electrical World, Vol. 97, February 14, 1931, pages 328- Vol. 34, March, 1937, pages 111-114.
334. 56. Heavy Duty Network Protector, G. G. Grissinger, Electric
I 31. Burn-Off Characteristics of AC T,ow Voltage Network Cables, Journal, Vol. 34, June, 1937, pages 254-256.
G. Sutherland and D. S. hIacCorkle, A.I.E.E. Transactions, 57. New Network Relays, John S. Parsons and M. A. Bostwick,
Vol. 50, No. 3, September, 1931, pages 831-844, (discussion Electric Journal, Vol. 34, July, 1937, pages 288-293.
pages 845 -846). 58. Short-Circuit Protection of Distribution Networks By the Use
32. Arcs in Low-Voltage AC Networks, J. Slepian and A. P. Strom, of Limiters, C. P. Xenis, A.I.E.E. Transactions, Vol. 56,
A.I.E.E. Tmnsuclions, Vol. 50, September, 1931, pages 847-852, September, 1937, pages 1191-1196.
(discussion pages 852-853). 59. Performance Tests on Non-Metallic Sheathed Cable For Under-
33. The Philadelphia AC Network System, H. S. Davis and W. R. ground Setwork Mains, C. W. Pickells, E.E.I. Bulletin, Vol. 5,
Ross, A.I.E.E. !Z’ransaclions, Vol. 50, No. 3, September, 1931, September, 1937, pages 391-396.
pages 885-891, (discussion page 891). 60. Distribution Systems For Power-House Auxiliaries, F. S. Doug-
34. Vertical Networks in Metropolitan Office Buildings, A. H. las and A. C. Monteith, Electric Journal, Vol. 34, October, 1937,
Kehoe and Bassett Jones, A.Z.E.E. Transactions, Vol. 50, No. 3, pages 399-404.
September, 1931, pages 1159-1164. 61. Planning A Distribution System, J. F. Fairman, Electric Jour-
35. Starting Currents on Networks, L. C. Bell, Electric Journal, Vol. nal, Vol. 35, June, 1938, pages 236-239.
28, 1931, pages 615-617. 62. Operation of AC Low Voltage Network From Two Voltage
36. Reducing Network Protector Operation, J. S. Parsons, Elec- Sources, W. B. Kenyon, E.E.I. Bulletin, Vol. 7, March, 1939,
tticul World, Vol. 98, December 5, 1931, pages 1010-1013. pages 115-l 18.
37. Network Balancing Transformers, R. E. Powers, Electric Jour- 63. AC Network Operation, 1936-1937, E.E.I. Publication No. Cl,
nal, Vol. 29, February, 1932, pages 89-92. August, 1938, 48 pages.
38. Radio City Starts With 13,000 KVA Capacity, E. Clute, Elec- 64. Operating Record Proves Value of Limiters, C. P. Xenis and E.
trical World, Vol. 99, April 9, 1932, pages 656-659. Williams, Electrical lVorld, Vol. 112, October 21, 1939, pages
39. Overhead Secondary Network Next Move In Distribution, W. 1165-1166 and 1225.
718 Primary and Secondary Network Distribution Systems Chapter 21

65. Philadelphia AC Network Operating Results, Paul W. Crosby, 69. Secondary Setworks to Serve Industrial Plants, C. A. Powel
Electricnl Engineering, Vol. 58, December, 1939, pages 517-521. and H. G. Barnett, A.I.E.E. Tmnsnclions, Vol. 60, 1941, pages
66. Vaults For AC Secondary Networks, John S. Parsons, Electrical 154-156, (discussion pages 698-700).
World, March 23, April 20, and bIay 18, 1940, pages 886-888, 70. New Applications for Secondary Networks, John S. Parsons,
955, 1201-1203, 1277-1278, 1512-1513, and 157221573. Westinghouse Engineer, Vol. 1, May 1941, pages 24-27.
67. Simulated Network Cheeks Actual System, C. T. Xcholson, 71. Secondary Setwork Planning, H. G. Barnett, Eleclrical World,
Electrical World, Vol. 114, September 7, 1940, pages 670-671. Vol. 116, August 9, August 23, and September 6, 1941, pages
68. Network Protector Operations Reduced, W. W. Edson and M. 422-423, 425, 575-576, 579 and 718-719.
A. Bostwick, Elecbical 1Yorld, Vol. 113, February 22, 1941, 72. Secondary Setwork For Industrial Plants, John S. Parsons,
page 56. Weshghouse Engineer, Vol. 1, November 1941, pages 85-88.
CHAPTER 22

LAMP FLICKER ON POWER SYSTEMS


Original Author: Revised by:
S. B. Griscom S. B. Griscom

OLTAGE regulation has been one of the most im- change, duration of change, and frequency of occurrence of

V portant problems of the electric industry since its


inception. The sizes of many parts of a power
system are determined largely by this one consideration
the flicker. These and other factors greatly complicate the
problem of assigning limits to permissible flicker voltages.
Numerous investigators have studied the flicker prob-
alone. -1 large proportion of the selling price of electrical lem. The most complete analysis is found in the report
power is the interest and other fixed charges on production “The Visual Perception and Tolerance of Flicker,” pre-
and distribution facilities, so that any improvement in regu- pared by Utilities Coordinated Research, Inc. and printed
lation is ultimately reflected in higher rates. Similarly, in 1937, from which Figs. 1 to 4 of this chapter are re-
types of load imposing exceptionally severe regulation re- produced.
quirements will also increase the cost of supplying energy. Figure 1 shows the cyclic pulsation of voltage at which
In the early days of the industry, a relatively wide range flicker of 115 volt tungsten-filament lamp is just percep-
of voltage variation was permissible, because the public
was at that time unaccustomed to uniform lighting in-
tensity. Today, there is a greater consciousness as to
whether the voltage level is about right, as indicated by
the “whiteness” of the light and by lamp life. While, how-
ever, a narrower voltage band is required than formerly,
this is not always the limiting factor in voltage regulation.
Sumerous new devices have been added to power lines
in the last few years, which impose rapid and frequent
changes of load, with correspondingly rapid voltage
changes. Repeated observations have shown that rapid
changes of voltage are much more annoying than slow
ones, so that “flicker” effects may limit the useful load-
carrying ability of individual circuits long before maximum
01 I I I I J
steady-state regulation or heating is reached. 0 2 4 6 6 IO 12 14 16 IS 20
Consequently, the voltage regulation problem must now FREQUENCY OF VOLTAGE PULSATION (CYCLES PER SEC.)
he considered from two angles: the normal drop in voltage
from light load to full load, and the superimposed flickers Fig. l-Cyclic pulsation of voltage at which flicker of 115~volt
tungsten filament lamp is just perceptible-derived from 1104
due to motor-starting and to various pulsating and ir- observations by 95 persons in field tests of 25-watt, IO-watt,
regular loads. The differences in voltage between light and 60-watt lamps conducted by Commonwealth Edison
and full load affect the performance, efficiency, and life of Company. Figures on curves denote percentages of observers
electrical equipment, and are treated in Chap. 10. The expected to perceive flicker when cyclic voltage pulsations of
indicated values and frequencies are impressed on lighting
present chapter considers only the flicker component of circuits. Plotted points denote medians of observation- at
voltage regulation, and deals primarily with the reaction various frequencies, number of observations in each case
of the human eye to variations in electric light intensity. being indicated by adjacent figures.

I. PERMISSIBLE FLICKER tible. Flickers as low as g volt were perceptible in 10


percent of the observations, when the rate of variation
The permissible amount of flicker voltage cannot be was 8 cycles per second. In order for the variations to be
stated concisely for several reasons. There is first the perceptible in 90 percent of the observations, however,
human element; one individual may think objectionable the voltage change had to be over one volt at the same
a flicker not perceptible to another. The lighting fixture frequency. The range between 6 and 12 cycles per second
used is of considerable importance. Smaller wattage in- was the most critical.
candescent lamps change illumination more quickly upon Figure 2 shows the minimum abrupt voltage dip to cause
a change of voltage than lamps with heavier filaments. perceptible flicker in a 60-watt, 120-volt tungsten-filament
The character of the voltage change is also important. lamp, as a function of intensity of illumination. Curves
Cyclic or rapidly recurring voltage changes are generally are shown for 5 and 15 cycles (GOcycles per second basis)
more objectionable than non-cyclic. On non-cyclic changes durations of voltage dip. It should be noted that abrupt
the annoyance due to the flicker is affected by the rate of voltage dips of 1.5 to 2.0 volts were perceptible.
719
Power Systems Chapter 22

---- FARADY HOUSE TESTING LABORATORY

------- BAIT. ELEC. AND ALLIED h4FRS.I ASSN.

(NO PULSATIONS BETWEEN 3 AND 12 CYCLES

‘L
+ O 1.0
$2
aO X 5 CYCLE DURATION OF VOLTAGE DROP
cub- 015 ” II 1, II ,I
aa
w 0.5 I

3”d ( 1 j 1
.I I.o IO 100 1000

ILLUMINATION ON READING MATTER (FOOT-CANDLES) zol LL1I-l I


0 5 IO 15
Fig. 2-Minimum abrupt voltage drop for perception of
FREOUENCY OF VOLTAGE PULSATION (CYCLES PER SEC.)
flicker of 60-watt, 120-volt coiled-coil tungsten-filament
lamps operated on 60-cycle alternating current. Each point Fig. 4-Recommended maximum allowable cyclic variation of
represents the means of the observation of 44 persons. voltage.

Figure 3 shows the effect of “duration of transition” of TABLE ~-MAXIMUM ALLOWABLE VOLTAGE FLUCTUITIONS
voltage on the average t,hreshold of perceptibility of flicker
for tungsten-filament lamps. This curve shows quite
cIe:wly that whereas an abrupt change of about 14; volts
Class of Service 1v‘ery
I nfre- Jir(.-
Frt,-
cluent cpIcut Frc-
cl,ucnt
lucnt
-
A. *On ;Lsubstationbus feeding only
po\ver lines.. tj 3 3
B. *On a po\rer line primary Tvhose
entire output is not t,aken by the
one customer and rend at the

‘4;
X KEHOE,25 AND IOO-WATT, IIJ-VOLT, LAMPS customer’s premises. 8 ‘4
A BROOKLYN EDISON CO., 50-W, 115-V, LAMP C. On n po\ver line whose entire out-
0 WERDENBERG 40-WATT 220-VOLT LAMP put is taken by one customer and
. LINOBERG, 25 a so-WATT, II5-VOLT, LAMPS
read at the customer’s premises S’0 ( te Lim it
v ETL 25 TO IOO-WATT 120-VOLT, LAMPS
D. On a substation bus feeding dis-
tribution circuit and on distribu-
Ea
awO tion circuit primaries. 6 2
ax 0 I 2 3 4 5 E. On a distribution circuit sccond-
wo
OURATION OF TRANSITION OF VOLTAGE (SEC) ary:
si
(a) At the secondary customer
Fig. J-Effect of duration of transition of voltage on average causing the fluctuation. 6 4
threshold of perceptibility of flicker of tungsten-filament (b) At the secondary customer
lamps. not causing the fluctuation. 3**
6
- - - -

*Loon Power Lines or their eouivalent automatic throwover lines shall be con-
is perceptible, a change of 5 volts or more is necessary sidered’ns Distribution Circuits. -
before voltage variations requiring several seconds for **On Farm Lines this limit has been increased to six volts because motor stnrtiw
is so lnrxely confined to daylight hows. This limit permits us to reasonably col”‘
completion can he perceived. with the long distances encountered

Figures 1 to 3 are of inter& in showing the perceptibil- DEFINITIONS:


1. Infrequent Flicker shall include cases occurring six times or less in twenty:f?lr
itics for various classes of flicker voltages. These are not hours but not more than once between 6:OO p.m. and 12:Ml midnight. This provY’o
is intended to cover apparatus such as motor generators. fans. pumps. etc.. \vhlch
working limits, because a perceptible flicker is not neces- normslly run continuously throughout the working day.
saril~ an objectionable one. Fig. 4 shows the recommended 2. Frequent Flicker shall include cases occurring
hour. except that between 6:OO p.m. and 12:00 midnight
not oftrner than three times per
they shall not 0CCur In?re
maximum :~llowable cyclic variation of voltages as set up than once per hour. This provision is intended to cover spparatlls such as mwhlne
tools, electric furnaces. etc., which are periodically stnrtcd and stopped throuKhor”
by various nllthorities for their own use. The variations in the working day.
these recommendations is an indication of the extent to 3. Very Frequent shall include cases orcurring
on the svera~e and shrrll include all exceptrapidly
not oftener than once 8 ?in””
and regularly recurrinK flicker?
which individual judgment enters the problem. The curves This provision is intended to cover such apparatus as elevator motors. nUtonlSt’e
pumps. ice machines. etc.. which ure started fairly frequently but, in 6~eoernl. Or0
are nevertheless an exceedingly valuable guide. not regularly started several times a minute.
Cyclic flicker, when perceptible, is likely to be objec- 4. Extremely Frequent
above. This provision is intended
shall include all cases occurring
to cover such apparatus
more frequently than t”e
as flashing signs, we’dem.
tionable, at least to some individuals. Isolated voltage gra\-el pit hoists. and certain electric furnaces, which are frequently
stopped and started or rnpidly louded and unloaded during normal use.
and rePeated’

dips, however, even if plainly perceptible, are not ob-


jcctionable to the majority of individuals unless rather ations are permissible for non-cyclic than for cyclic VU;-
frequent. It can, therefore, be expected that larger vnri- ations, but that the amount of tolerable dip depends uPon
Chapter 22 Lamp Flicker on Power Systems $21

the frequency of occurrence and the class of service. Here quency doubled to get it out of the object,ionable range,
again, judgment is an important factor as well as technical by synchronizing the generators so that the power strokes
facts. The maximum allowable fluctuations practiced by of the two engines alternate rather than occur simultanc-
one operating company are shown in Table 1. ously. This can be done because there arc usually more
This is a very comprehensive set of standards and has poles on the generators than cylinders on the engine, pnr-
proved satisfactory in practice. titularly in those engines where the flicker is in the ob-
jectionable range. A stroboscope or similar device 11sed
II. ORIGIN OF FLICKER VOLTAGES with the regular synchroscope permits such synchronizing.
It has sometimes been thought that it should be possible
Flicker voltages may originate in the power system, but to correct flicker of this type by the use of special voltage
most frequently in the equipment connected to it. regulators of unusually fast response. In practically every
case this is completely out of the question because the
1. Generating Equipment frequency of the flicker is too high for the time constant
Prime Movers---Engine driven generators are prob- of the generator field. For example, the field time constant
ably responsible for most of the rare cases of flicker origi- of a typical moderate-sized engine-type generator is be-
nating due to the power system itself. Curve (a) of Fig. 5 tween 0.5 and 1.5 seconds, whereas the range of most
shows the variation in tangential force of a four cylinder objectionable flicker is between % and & second per cycle.
Even electronic escitation systems are unable to regulate
voltage at such a high rate.
Generators-A symmetrical generator with constant
load, excitation and angular velocity produces a constant
terminal voltage. If any of these quantities varies, holy-
ever, the terminal voltage also varies.
It is possible to have a sufficient degree of non-uniform-
ity in the generator air gap to cause pulsating terminal
ANGULAR POSITIzbN OF FLYWHEEL voltage. Ho\\-ever, the commercial manufacturing toler-
ances are sufficiently close that no case of flicker due to
this cause is known to have occurred. To produce flicker
in this manner, both the rotor and stator must be eccentric.
Stator bores of all but the smallest size machines will in-
-0. I
FW -0.2
herently have a certain degree of eccentricity, because they
50 -0.3 must be built up with segmental laminations. In spite of
g 5 -0.4
0 30 60 90 120 150 160 210 240 270 300 330
this built-up construction, quite close tolerances are held
apz ANGULAR POSIT;;; OF FLYWHEEL by the use of accurate dies and assembly keys and dowels.
Further attempts at improvement would be very difficult
Fig. 5-Curves from a four-cylinder 300 rpm Diesel engine at as it would require boring or grinding the inner bore of
full load driving a generator. The variation in velocity caused the stator punchings. This is quite undesirable from the
a corresponding variation in the generated voltage. standpoint of accumulation of iron chippings and filings
between laminations and into the slots, which might result
300 rpm Diesel engine at full load, and Curve (b) shows in a condition of insulation breakdown and localized heat-
the corresponding percent change in angular velocity of ing of the stator The rotor eccentricity is, because of the
the rotating parts. With all other factors constant, this necessity of dynamic balancing, held normally to quite
non-uniform rate of rotation produces a fluctuation in close tolerances. Since no voltage fluctuations can be pro-
amplitude of the generator voltage The total variation duced if the rotor is concent’ric with the shaft, no modifi-
in voltage is the same as the total variation in speed; in cation of standard manufacturing procedures has ever been
this example 0.7 percent. The frequency of the variation necessary from the standpoint of flicker voltages.
is equal to the rpm times the number of power strokes Abrupt changes of load on generators produce corre-
per revolution; in this case 300X2 = 600 per minute or sponding changes in the terminal voltages. This voltage
10 per second. fluctuation is the result of two factors: the change in speed,
Referring to Fig. 1, it is seen that 0.7 percent change in and the regulation of the machine. In central station
voltage is readily perceived by most individuals. Fig. 4 practice it is very unusual for change in speed to be a
indicates that most operators regard this as too much significant factor. Sudden load increments are usually too
flicker to be tolerable. About the only practicable remedies small as compared with the total generating capacity to
are increasing the flywheel effect, or changing the speed change the speed materially. Even if the speed changes,
to get within a less objectionable frequency range. In this however, the rate at which the voltage drops is ordinarily
actual case, the flicker of the original installation caused so slow, that the effect is imperceptible to the eye (see
many complaints and it was satisfactorily corrected by Fig. 3).
increasing the flywheel effect. A typical voltage-time regulation curve of a large tur-
When two or more engine-driven generators are in con- bine generator, following sudden application of load is
tinuous operation at the same station, the amplitude of shown in Fig. 6. Speed-d excitation voltage are assumed
the fluctuation can frequently be lowered, and the fre- constant. Three points on this curve are of especial in-
Lamp Flicker on Pozoer Systems Chapter 22

Similarly, point (b) is calculated from synchronous re-


nctance using the relation:
O-6= E, - Ix,,
The transition from (a) to (2) and from (2) to (b) may
be calculated by using the appropriate machine time con-
stants. This procedure is more fully described in Chap. 6.
From the standpoint of flicker voltage, the following points
are of interest.
For single load applications more than 10 cycles in du-
ration (on a 60-cycle system), the voltage regulation point
Fig. 6-Voltage-time regulation of a large turbo-generator (c) of Fig. 6, calculated from the transient reactance, is
following sudden application of load. the determining quantity. Fig. 2 shows that there is little
difference in perception lasting from 5 to 15 cycles of volt,-
terest. Point (a) is the voltage immediately following the age drop. In average machines, the subtransient drop is
application of load; point (b) is the voltage after the usually about two-thirds of the transient drop. However,
voltage has sct,tled; point (c) is an extrapolation of the after about the first 5 cycles, the voltage drops to the value
curve from (b) back to zero time. Each of these points determined by transient reactance. ,4 further drop in
may be determined closely by the use of the appropriate voltage takes place due to the decrement of the field,
generator reactance. In fact, the standard definition of reaching point (b) on Fig. 6. Usually, this synchronous
the various reactances has been made for this particular reactance drop is not more than two or three times the
use. For a fuller discussion of machine characteristics transient reactance drop. Automatic voltage regulators
see Chap. 6. may limit the drop to less than l$$ times the transient
Point (a) is determined by the use of the machine sub- drop. Reference to Fig. 3 shows that for a transitiqn time
transient reactance Q”. In the case of an initially un- of the order required (3 to 10 seconds), the additional
loaded machine, the voltage (O-a) is the vector difference voltage drop due to field decrement is not perceptible
between the no-load voltage and the product of the load For load durations less than 5 cycles, it is likely that the
current times the suhtransicnt reactance. That is, regulation as calculated from the subtransient reactance
determines the permissible flicker. While the voltage drop
O-a = E, - Ixd” at the end of 5 cycles is greater than initially, the transition
The voltage rapidly falls further to a point (2) and at is gradual and it is doubtful if the eye can discern so
a much lower rate to point (b). small a difference.
The reason may be described approximately as follows. For load durations between 5 and 10 cycles, it is prob-
At the instant of load application, the magnetic flux in able that an average between subtransient and transient
the air gap remains substantially constant, and the initial reactances should be used to calculate flicker voltages for
drop in voltage is principally that due to reactance of the comparison with perception data similar to those given in
armature winding. However, the armature currents set Figs. 1 to 3.
up a demagnetizing effect to buck the field flux. The The proper reactance to be used to calculate the effect
decreasing field flux generates voltages and currents in the of cyclic variations depends upon the frequency of their
field structure, which resist or delay the ultimate change. occurrence. The following range is suggested for gener-
The induced currents in some parts of the field structure, ators 5000 kva and above. w
such as the eddy currents in the pole face, damper wind-
ings, or rivets, subside rapidly because of the high resist- PulsLttion Frequency
ance of the path, and allow part of the flux to change Reactance
Cycles per Second I
quickly. In the average machine, about 0.1 second is
1-4 Xd’
required for this change. Most of the change of voltage 5d’fXd”
between points (a) and (z) is due to this cause. The 5-12
2
majority of the field flux is encircled by the field winding
which is of very low resistance, and, therefore, constitutes
an effective damper to rapid changes of voltage. The In smaller machines the field time constant may be so
change in voltage from (2) to (b), therefore, constitutes short that pulsation frequencies below 2 cycles per second
an effective damper to rapid changes of voltage. The may require the use of synchronous reactance.
change in voltage from (2) to (b) is, therefore, compara- Excitation Systems-Excitation systems are rarely
tively slow, from 3 to 10 seconds being required for 90 the cause of flicker voltages in central station practice. In 1
percent of the change to take place in large machines. larger generators, field time constants above 3 seconds i
Point (2) is not directly calculable by using standard cause variation in armature v ltage to be very gradual
machine reactances alone. Point (c), however, can be no matter how fast the excitat Pon may change. Occasion-
calculated in the same manner as point (a), except that ally, hunting of generator voltage regulators causes wide
transient reactance is used. That is voltage fluctuations, but this is not a true flicker. On small
generators, continuously vibrating regulators occasionallY
o-c = E, - IXd’ cause a small pulsation of the armature voltage.
Chapter 22 Lamp Flicker on Power Systems 723

Since the alternator field constant is usually too high to to design a distribution system to supply 20 amperes at
permit exciter fluctuations to show up in the alternator 110 volts without objectionable lamp flicker. Where single
terminal voltage, correction of flicker by means of excitn- phase 110/220 systems arc used, do-ampere starting cur-
tion control is not practical. In other words, the amount rents are permissible on the 220-volt connection, allowing
of generator flicker depends upon its inherent reactance larger motors to be used.
characteristics and cannot he substantially improved by (2) Integral-horsepower motors on secondary circuits
excitation cont,rol. are potential sources of flicker. In most cases, such motors
Short Circuits and Switching Surges-Short circuitare used in areas of high load concentration and the power
currents, because of their magnitude, produce large voltage circuits are correspondingly large. This usually permits
drops and attendant flicker. Reduction in the amount of ordinary 3-phase squirrel cage motors to be started di-
voltage drop is not feasible without major changes in rectly across the lines. In some cases, however, the size
system layout and large expenditures. The duration of of a motor is out of proportion with its supply line. The
the voltage drop can, however, be markedly reduced in practical solution is to use a starter that limits the initial
a number of cases by the use of high-speed relays and inrush of current and thereafter changes the current in
breakers. Flicker due to short circuits occurs so seldom increments sufficiently small to prevent objectionable
that no special consideration for this purpose alone is lamp flicker.
necessary. The tendency is toward a gradual reduction (3) Supplying large motors from primary power lines
in flicker, as system improvements arc made for other is usually not troublesome because such motors are usually
purposes such as protection of lines against lightning, located in an “industrial district” where power supply lines
installation of high speed relays and breakers, etc. These are inherently heavy and where wider limits of voltage>
comments apply to networked systems; in radial lines, drop are permissible (See Table 1). There are nevertheless
short circuits produce outages, a distinctly different a number of cases particularly in rural communities, where
problem. motor ratings are too high for the power facilities. A suit-
Line switching rarely produces flicker unless load is able motor starter may correct such cases, although in
picked up or dropped, or lines with large charging currents some installations other measures may be required.
are switched. Here again, special provisions to reduce Starting currents for both induction and synchronous
flicker are rarely necessary. motors at full voltage vary from 5 to 10 times full load,
depending upon the size, number of poles, and other ap-
2. Utilization Equipment plication requirements, such as required starting, pull-in,
Most of the flicker on central station systems is due to and pull-out torques. The power factor under locked-
the customer’s utilization equipment. The following are rotor conditions varies between 25 and 50 percent. For
some of the more common types of equipment known to approximate calculations, a starting current of 6 times
cause flicker. normal at 35 percent power factor may be used. Wide
Motor Starting-Probably most of the flicker prob- variations from this should be expected, and specific data
lems are caused by the starting of motors. For reasons should always be used when obtainable.
of cost, efficiency, and reliability, commercial general pur- Motor-Driven Reciprocating Loads-This type of
pose motors require a momentary starting current several load usually consists of air compressors, pumps and re-
times their full load running current, in order to produce frigerators. The motor load varies cyclically with each
sufficient starting torque. power stroke and produces a corresponding variation in
Three general classes of motor installations are of im- the line current. Thus, comparatively small variations of
portance in the flicker problem. voltage may be objectionable if the pulsation occurs 6 to
(1) Single phase fractional horsepower motors com- 12 times per second. (See Fig. 1.) Difficulty from this
monly used in homes and small stores. source has been caused in the past by domestic refriger-
(2) Integral-horsepower polyphase motors operated ators, but in modern designs both the frequency of pulsa-
from secondary distribution circuits, such as in tion and the amount of fluctuation have been improved,
small shops, large stores and buildings, and re- so that complaints from this cause are now rare.
cently in a small number of homes for air condi- Figure 7 is an oscillogram showing the armature voltage,
tioning. current and three-phase power of an air compressor driven
(3) Large integral-horsepower three-phase motors op- by a 100-horsepower wound rotor induction motor. There
erated from primary lines, mostly by industrial are several points of interest on this oscillogmm. First,
concerns. although the voltage variation can scarcely be detected
(1) Single phase fractional horsepower motors are man- on the oscillogram, it actually was very objectionable to
ufactured in large quantities, and to maintain this extent lighting customers. This shows that oscillographs used in
of usage, they must continue to be low in cost, economical, the conventional manner may not always be suitable
rugged and reliable. These requirements have led to sev- for flicker-voltage measurements. Second, the three-phase
eral classes of motors depending upon the service, with power and current fluctuations occur simultaneously and
one class designed specifically for frequent starting with the peak is about 2?4 times the minimum. This is interest-
low starting current. This motor is used in great quantities ing because it shows that the slip of induction type motors
in domestic refrigerators and oil burners, and the x horse- cannot prevent load fluctuations from showing up in the
power IlO-volt class usually has a locked-rotor starting supply lines, unless the inertia of the load is high or the
current of 20 amperes or less. It is not unduly expensive rate of power pulsation is high.
724 Lamp Flicker on. Power Systems Chapter 22
I
Publication C 50-1943 “9mericsn Standard Rotating of load fluctuation, and the steady-state performance of
Electrical Machine& of the American Stnndards Com- moderately-sized induction motors as det&mined by test
mittee establishes the amount of pulsations for synchro- or circle diagram may be used in calculating flicker due to
nous motors. Section 3-160 reads: cyclic load variation of power factor with load, but specific i
“Pulsating Arm:lture Current: When the driven load such as data should be used where obtainable. 4
that of reciprocating type pumps, compressors,etc., requires a
variable torque during cnch revolution, the corn&net1 install:Ltion
shall have sufficient inertia in its rotating parts to limit the Load, Percent Power Factor, Percent
~ -~--.
variations in motor armature current to a value not exceeding 25 72
66 percent of full lontl current. 50 78
“NOTE I-The basis of determining this variation shall be 7.5 85
by oscillogmph mensurernent and not by ammeter readings. A 100 87
line shall be drawn on the oscillogrnm through the consecutive 125 90
peaks of the current wave. This line is the envelope of the cur-
rent wave. The vwintion is the difference betlveen the maximum
and minimum ordinates of this envelope. This variation shall The variation of power factor of a synchronous motor
not exceed 86 per cent of the maximum value of the rated full during cyclic load fluctuations is a more complicated phe-
lontl current of the motor. (The maximum value of the motor nomenon. The average power factor is, of course, greatly
zrmature current to be nssumedas 1.41 times the rated full load influenced by the supply voltage and by the field excita-
current.) Adopted Stnnd:wd G-13-1923.” tion. The variations from this average power factor due
The above excerpt provides a basis for standardization to load fluctuation is largely dependent upon the rate of
and gives a criterion for a design unlikely to cause flicker. the fluctuations as compared with the time constant of the
However, there are still possibilities that this amount of field. For example, if the field time constant is 1 second
pulsation may at times result in flicker, particularly if the and the load fluctuates once every 2 seconds the synchro-
rate is between 6 and 12 cycles per second, and the supply nous reactance of the machine determines the extent, of the
line impedance is high. change in power factor. If, holyever, the power flwtua-
An analysis of Fig. 7 shows that with an induction motor tions are, say, 8 cycles per second, the transient reactance
both the current and power factor pulsate when the motor largely determines the change in power factor because the
load varies, the power factor being highest when the load load swings are too rapid to demagnetize the field.
is highest as shown in the tabulation below. Usually, the Since in flicker problems, the change in load is of greater
armature time constant is high compared with the rate concern than the magnitude of the load, the average power
factor is of no particular interest. The preferable proce-

Fig. 7-Oscillogram of current I, voltage E, and three phase Fig. S-Vector diagrams illustrating method of obtaining
power W of a IOO-hp wound-rotor induction motor driving an magnitude and phase position of synchronous motor current
air compressor. The voltage change which cannot be meas- and magnitude of bus voltage with change of load. % is
ured from the oscillogram caused objectionable flicker. system reactance and X, is motor reactance.
Chapter 22 Lamp Flicker on Power Systems 725

dure, if complete motor data are available, is to calculate The position of the voltage drops will then determine the
the changes in the bus supply voltage to the motor due to position of the current vector as well as t,hc bus voltage
chnngrs in the load on the motor. The method is illus- vector El,,,. Using the current, voltage (E,,,J and the
trated in the vector diagrams on Fig. 8. Vector diagram angle between them t,he power can be found. With the
((2) sholvs the vector relations for a synchronous motor curve of bus voltage against motor load change the voltage
opcruting at full load and SO percent power factor lead. for any desired change in motor load can be obtninrd.
E:,, El,,, and E’,,, are respectively the system voltage, bus The variation in reactive kvu wit,h real powr is shown
supply voltage to t,he motor and the internal voltage of the in Fig. 9 for a typical synchronous motor. These data are
mot,or. IR, and IX, are the voltage drops through the
system impedance. I-Y, is the drop through the motor 200- &oo
where S,,, may he the synchronous, transient or sub- 5
transient reactance depending upon the rate of load fluctu- .I&
ation compared to the time constant of the machine. s
5 160 _ 3 00
Using diagram (a) as the starting point where the motor
E x
power factor angle 01 is known along with the average cc
load, E bus and all of the reactances, the change in bus 2 5
voltage can be obtained as shown in vector diagram (0). 2
120- g 60
For all sudden changes in load the system voltage, E,, and 3 k!
the internal voltage of the motor, E,,, remain substantially 5
I
a
constant. To determine the sudden dip in bus voltage it fj 60-z40
is necessary to calculat,e a curve of bus voltage against c w
motor load or motor load change. This requires for each z 2
point on the curve that a magnitude of current be assumed z
w
t;
40 - a 20
and the voltage drop through the system and motor de- a.
E
termined. This will locate the internal voltage E, with I I
5
respect to the system voltage E, (In Fig. 8 E, and also
0-g 0
E, in the diagrams (a) and (b) have the same magnitude). 0 40 00 120 160 200
z
PERCENT OUTPUT
!Tjso,0 Fig. lo-Characteristics of a typical induction motor.
200 &lOOl ! ! ! I I I I I IB-VI
t PbWEi FAtTOR /- for a power factor of 80 percent at full load, but for ordi-
: 100 I
/ nary purposes the variations in reactive factor may be
E
2 160 superimposed on the initial reactive factor. Curve A is
REACTIVE KVA/ / for a rapid rate of fluctuation starting from full load 80
: 140- percent power factor; Curves R are for a rate slow com-
2 pared to the field time constant with fixed terminal voltage.
I” 120-
Q
Motor Driven Intermittent Loads-In this cate-
a IOO- gory fall motor drives where the nature of the work calls
2 for heavy overloads, and for cyclic loads of long and ir-
2 00- regular period. Saw mills and coal cutters are typical
= 60-
examples of applications where heavy overloads, some-
2 times to the stalling point, are common and difficult to
I- 40- prevent. The motor currents in such installations vary
5 rapidly from light load, through pull-out at heavy current
z 20- and high power factor, to the high locked-rotor current at
w
Il. low power factor. Punch presses and shears are examples of
o-
applications where the load goes through wide variations,
but where flywheels and other design features limit both
the rate of application and magnitude of the load swings.
Motors used to drive intermittent loads are likely to
have been designed with special characteristics. If possible,
80% POWER FACTOR MOTOR the fluctuation in current and power factor should be ob-
1 tained by test or from the manufacturer. In the absence
of such specific data, Curve B of Fig. 9 may be used for
slow cycling intermittent loads, and the curve of Fig. 10
60 may be used for applications where pull-out and stalling
occur.
701 ’ ’ 1 1 1 1 1 1 1 1 u Electric Furnaces-There are three general types of
Fig. 9-Characteristics of a typical synchronous motor at electric furnaces-resistance, induction, and arc. The re-
normal rated voltage. Curve A is for rapid changes in load sistance furnace usually causes no more flicker than any
from initial value and curve B is for slow changes. other resistance load of comparable size. Most induction
726 Lamp Flicker on Power Systems Chapter 22

ing the regulator settings or by a combination of several


of these procedures. Forcing the furnace in this manner
increases both the magnitude and the violence of the load
swings. The type of the scrap being melted also affects
the estent of the load swings, heavy scrap causing wider
fluctuations than light scrap.
The oscillogram of Fig. 12 represents a short part of a
melting-down period of a 10 OOO-kvaarc furnace. At times,

Fig. 11-Three-phase melting arc furnace of the Heroult type.

furnaces operate at high frequency, and therefore, are Fig. 12-Oscillogram at start of heat in a 10 000 kva Heroult
connected to the power line through a frequency changer type three-phase arc furnace. A single-phase arc struck and
and consequently represent a fairly steady load. restruck 10 times in the space of 15 seconds before all three
phases struck. After this initial period, all three phases struck
Three-phase steel melting arc furnaces of the Heroult and restruck 10 times with currents in all three phases fairly
type, illustrated in Fig. 11, are being used to a considerable well balanced before the arcs became generally stable. A por-
extent to make high grade alloy steel, and frequently cause tion of this performance is shown on this figurelO.
voltage flicker.
While the average load factor and power factor of elec- the current variations occur at a periodicity approximating
tric arc furnaces are as good or better than many other the rate of the most objectionable flicker. A graphic chart
industrial devices, the problem of supplying them with illustrating the variation of load over a longer period of
power is usually much more difficult. During the melting operation is shown in Fig. 13. These two figures are
down period, pieces of steel scrap will at times, more or reprints of figures from reference 10. w
less, completely bridge the electrodes, approximating a Calculated curves in Fig. 14 show th+! electrical char-
short circuit on the secondary side of the furnace trnns- acteristics of a 10 OOO-kva, three-phase arc furnace. These
former. Consequently, the melting down period is char- curves were prepared on the assumption that the maximum
acterized by violent fluctuations of current at low power attainable current would be approximately twice normal
factors, single-phase. When the refining period is reached, at 50 percent power factor. The effective impedance of
the steel has been melted down to a pool and arc lengths the arc (based on 11 500 volts in the primary) is plotted
can be maintained uniform by automatic electrode regu- as the abscissa. For convenience, zero ohms, as plotted,
lators, so that stable arcs can be held on all three elec- represents the minimum arc resistance as determined by
trodes. The refining period is, therefore, characterized by the so-called short circuit condition. Actually, at this
a steady three-phase load of high power factor. point there is appreciable voltage drop at the electrode
The size of load fluctuations during the melting down tips, and considerable arc energy; the curves are plotted
period is influenced by a number of factors, of which the in this manner only to show the working range. It is of
rate of melting is perhaps the most important. The fur- interest that the point of maximum power is not that of
nace-supply transformers have winding taps for control of maximum kva. The usual melt-down range is probably
the arc voltage and in the smaller sizes (about 6000 kva between the points corresponding to 0 and 10 ohms, the
and below) have separate built-in reactors to limit the arcs fluctuating during this period so that the heating
current and stabilize the arc. The rate of melting is subject effect is some sort of an average between these limits. The
to further control by means of electrode regulators. Some- refining range is probably above 10 ohms.
times the production of the furnaces is stepped up by It is difficult to obtain definite figures on the values of
raising the arc voltage, reducing the series reactance, rais- instantaneous swings in current and power factor for use
Chapter 22 Lamp Flicker on Power Systems 727

I i i i i i i i i i I
OO 5 IO I5 20 25
ARC RESISTANCE-OHMS

Fig. 14-Electrical characteristics of a 10 000 kva, three-phase


arc furnace.

These values will give approximately the same flicker as


the single-phase swings given in references 14 and 15. The
curve values are not the maximum possible swings for a
given furnace size but are good values to use in estimating
flicker. The frequency of occurrence of these swings cor-
responds to the Extremely Frequent classification as given

FURNACE TRANSFORMER RATING -WA

Fig. 15 Equivalent kva swings in an electric arc furnace.

in Table 1. Load swings can occur more rapidly, but their


magnitudes are less than those in Fig. 15. These curves
can be used in conjunction with the method suggested in
Sec. 5, to estimate the amount of flicker. The information
shown in Fig. 15, together with suitable system constants
should give a fair approximation of the flicker voltage to
Fig. 13-Graphic charts at time of same heat shown on oscil- be expected.
logram of Fig. 12. Furnace swings occur approximately once Electric Welders-This is a class of equipment of
a second’Q. great importance in power system flicker. Most, welders
have a smaller “on” time than “off” time, and conse-
in flicker determinations, because an oscillograph must be quently, the total energy consumed is small compared with
used and the maximum swings cannot always be caught. the instantaneous demand. Fortunately, most welders are
On small furnaces, the current may reach a maximum of located in factories, where other processes require a large
3% times that at full load, but the process of reaching this amount of power, and where the supply facilities are sufi-
value is usually through a series of small increments, and ciently heavy, so that no flicker trouble is experienced.
as noted previously the annoyance to lighting customers In isolated cases, but nonetheless important, the welder
is largely a matter of the rate of change rather than the may be the major load in the area, and serious flicker
total change. may be imposed on distribution systems adequate for
The kvn swings given in Figure 15 are equivalent swings. ordinary loads.
728 Lamp Flicker on Power Systems Chapter 22

The more common types of electric welders are:


i I) Flash welders
(2) Pressure butt welders
(3) Projection welders
(-I) Resistance welders
(a) Spot
(b) Seam
In welders the source voltage, usually 230, 460 or 2300
volts is stepped down to a few volts to send high current
t,hrough the parts to be welded. Practically all welders
in service are single-phase, although experimental three-
phase welders show promise.
With flash welders, one piece is held rigidly, and the
other is held in quasi-contact with it, with voltage applied.
An arc is formed, heating the metal to incandescence, and
the movable piece is made t,o follow to maintain the arc.
The hcnting of the metal is partly by the passage of current
and partly by burning with the arc. -After a sufficient
tcmperaturc and heat penetration has been obtained, the
pieces are forced together under great pressure. In some
casts, the power is cut off before this”upset”; in others,
the power is left on. The current, drawn during the flash-
ing period, is irregular because of the instability of the arc,
so that the flicker effect is obnoxious more than if the
cllrr‘ent were steady at its maximum value. The average
power factor during flashing may be as high as 60 percent.
At upset, it is about 40 percent. The flashing may last up
to 20 or 30 seconds, but 10 seconds is more common. The
duration of power during upset is usually short; of the
order of M second. This type of welder may draw up
to 1000 kva during flashing and about twice this loading
ut ups&.
Pressure butt welders are similar to flash welders, except
for the important difference that the parts being welded
are kept continuously in contact by a following pressure.
The heating is produced primarily by contact resistance.
From a power supply standpoint the butt welder is more
desirable than the flash welder because the welding current
once applied, is practically steady and the only flicker
produced is at the time power is applied and removed.
The range of currents and power factors is about that
for Rash welders.
Projection welders are similar to pressure butt welders
except that the latter usually join pieces of about equal
size, and projection welders usually join small pieces to
large ones. The current demand is usually smaller, but
the operations are likely to be more frequent.
In resistance welders current is applied through elec-
trodes to the parts to be welded, usually thin sheets of
steel or aluminum. The weld is accurately timed to bring
the metal just to the welding temperature. The pieces are
fused together in a small spot. In the spot welder, one or
a few such spots completes the weld. In a seam welder,
a long succession of spots produces the equivalent of a
single continuous weld or seam. Resistance welders are . *
characterized by large short-time currents. In spot weld- (b)
Fig. 16-Ignitron timer for resistance welder.
ers, the current may be applied for only a few cycles (on
a GO-cycle basis), with welds following one another in a age dips occurring at objectionably frequent intervals.
fraction of a second up to about a minute. Thus, from a Seam welders have an “on” duration of a few cyclesfol-
flicker standpoint there are a succession of individual volt- lowed by an “off” duration also of only a few rycles, ‘rhe
Chapter 22 Lamp Flickrr on Power Systems 729

Resistance welders drawing energy from all three phases


greatly minimize flicker. Electronic devices are used to
convert from the GO-cycle, 3-phase source to a single-phase
output of lower frequency, say 10 cycles per second. On
small welders, the stored energy of capacitors or inductors
can often be used to minimize the peak demand from the
source.
Miscellaneous--Under this category come special
equipment as electric shovels, heavy rolling mills, and
similar installations. Most of these must be considered
individually as to special features and power supply.
Strip mining shovels frequently cause severe voltage
dips in power systems, principally because of their large
size and wide variation of their loads. The fast rate of
load application is usually injurious to the power system
principally by creating a wide band of voltage fluctuation,
rather than flicker as it is commonly encountered. The
site of mining operstion is often at out-of-the-way locations
where the power requirements for general purposes are
small and hence, the normal power facilities are of low
capacity, and very susceptible to flicker due to load
changes.
Fig. 17-Typical resistance welders-(a) spot welder, (b) seam The large continuous rolling mills now used extensively
welder. in producing wide metal strip have imposed a new problem
on the power industry. Like the electric shovel, these loads
process is a continuous one while a given piece is in the do not necessarily produce flicker in the customary sense
machine, and since the perioclicity of the welds is uniform, of the word. The power supply is usually through motor-
the flicker can be annoying even for relatively small voltage generator sets without added flywheel effect. The loath
dips. The essence of good spot and seam welding is ac- comes on and drops off in steps as the metal enters w
curate control of the heat, consequently accurate magni- leaves the rolls. The individual increments are not in
tude and duration of current are necessary. Vacuum tubes themselves abrupt, a fraction of a second to over a second
are being used to a large extent for welder control functions being required for the metal to enter a roll completely.
because there are no wearing parts, and close and con- A large hot strip mill and a typical load chart are shown
sistent regulation of the heat is possible. Fig. 16 shows a in Figs. 18 and 19.
photograph of an ignitron electric timer and Fig. 17 shows The power drawn by a large continuous mill may build
a typical resistance welder. up to 30 000 kw in a period of 8 seconds,‘stay nearly con-

Fig. M-Tandem cold mill for producing tinplate.


Lamp Flicker on Power Systems Chapter 22

A heavy cycling load of this kind may produce wide


\ ROLLING 36”~ 4-1/2”x 75” frequency variations on an isolated power supply system
20000
SLABS TO 0.104”X 36-l/8” and lvide load swings on an interconnected system. ,I
power plant recording chart in Fig. 20 shows the power
flow between the steel mill power plant, and a large power
pool. Fig. 21 (a) sho\vs the hot strip mill load cycle a*,,1

0
TIME-SECONDS

/ I , o/, I I I I I
90 80 70 60 50 40 30 20 IO
SECONDS
25000 KW

\ ROLLING 5O”X 4-l/2” X 75”


SLABS TO 0.060” X 50-l/8”
\ 20000
TIME-SECONDS
I ; \ \ \ i Cb)
I
I \, \l5000
1 Fig. 21-(a) Hot strip mill load. (b) Effect on frequency of
FINISHING ROUGHING TRAIN large interconnected system.
TRAIN
10000 n

7 J L/svn,R Fig. 21 (b) the results of calculations on how power surges


of this kind cause frequency rlisturbanccs \vhich+avel as
I5000 waves between the local power company to which the strcl
/ I I
/ / plant is connected and a larger po\ver pool.
I I 0 I I I I I
80 70 60 50 40 30 20 IO 0 III. LOCATION OF FLICKER VOLTAGES
SECONDS

Fig. 19-Load chart for a hot strip rolling mill. Load equipment may create flicker conditions in one
or more of the following locations:
stnnt for a minute, and then drop to almost zero in another (1) Secondary distribution
8-second period. There may then be an off period of a (2) Primary lines
minute followed by a repetition of the load cycle. The (3) Substation busses
power source is usually ample so that no flicker is percep- (4) Generating stations
tible to the eye, but there is nevertheless a tendency for
Any flicker in bus voltage of the generating station can
the voltage to ‘Lweave” up and down. This is undesirable
be expected to show up at practically all points served by
because it widens the band of voltage regulation and may
that station. Similarly if a substation bus flickers, all of
cause excessive operation of feeder voltage regulators.
the radial loads from that substation are affected. Primary
Automatic control of the excitation to the motor-generator
line flicker affects all customers remote frbm the source
sets to conform to the load variations is effective in
of flicker, and to a lesser extent, some of tfi,ose nearer the
minimizing these voltage swings.
source of supply. Secondary circuit flicker is usually con-
. -. .“_-^ .~--. . --r-- -’ ,, ~ . fined to an area immediately adjacent to the source of
the disturbances.
The location of flicker voltage, or the extent of the af-
flicted area, has a considerable influence on possible rem-
! \ \ \ ..’ \ : \ -.-- .\ \. t edies. If the generating station busses are affected, there
are usually no commerciahy practical means of remedying
the situation on the power system, and the correction must
usually be made at the utilization point. If a substation
is affected, but the generation stations are not, then more
tie lines or transmission at higher voltage can be employed,
or a separate line run from the generating station to the
affected area. Sometimes the utilization e uipment itself
can be corrected. If a primary line is affec \ ed, improve-
ments can be made in either the power system or the
utilization equipment. If the distribution system alone is
-- .,I -I_ “- I ,.., ,..... _ .-...e-.A.~,- ^ ..,.- x ,--- I”_ ,_-_ - affected the correction may be made either on the system
Fig. 20-Power flow between a steel mill and a large intercon- or the utilization device. If the utilization device is stand-
nected power system. ard equipment, it is usually best to correct the distribution
Chapter 22 Lamp Flicker on Power Systems 731

svstem, and thuds improvc other loads as ~rell. If the suitable for the supply of cithcr single-phase or polyphasc
utilization device is spccinl, it is probably more efficient to loads.
correct the device. When a synchronous motor drams additional power from
t,he lint it drops back in phase position. This causes a
IV. REMEDIAL MEASURES temporary drop in speed, but t,he flywheel effect of the
rotor tends to oppose this change and to give up tem-
.1 large variety of corrcct,ive equipment and procedures porarily part of its rotational energy. This results in a
can be used to minimize flicker. Those most commonly “cushioning” of the rate of application of load to the pan-el
considered are : system, and a material reduction in peak demand can be
1. hIotor gcncrntor sets effected for loads of short dlwations as compared I\-ith one-
2. Phase converters half of the natural period of electro-mechanical oscillation
3. Synchronous condensers (see Chapter 13). The natural period usually ranges be-
4. Series capacitors tn-een M and 1 second, so that for loads lasting about >fi
5. Shunt capacitors second and less, substantial reductions in peak demand
6. Voltage regulators can be expected. Thus, synchronous-motor-driven m-g
7. Uooster transformers sets are quite suitable for spot and seam \\cltlers having
S. Motor starters an “on” time of 1 to 10 cycles (60-cycle basis). Similarly,
0. Escitation control sudden increases or decreases of load are shielclctl from the
10. T,oatl cont,rol power system if the load factor is high, bllt the load is
11. Flynfieels subject to short violent irregularities. This is true of elec-
12. System changes tric furnaces, for example, ivhere the overall load factor is
good, but there is considerable “choppiness,” sudden power
3. Motor Generator Sets factor changes and short-circuiting of individual phases.
A corrective scheme using m-g sets is illust,rated in Fig. For this type of load, synchronous motor drives are nearly
22. In general, it is probably true that a motor-generator as effective from the flicker standpoint as squirrel-cage
induction, and preferable for other reasons.
When an induction motor draws added po\ver from the
line, it drops in speed. Its output, in the normal lvorking
range, is closely proportional to the slip, that is, to the
difference between synchronous and actual speed. If load
is suddenly applied to a generator driven by a squirrel-cage
induction-motor, the system does not feel the full effect
until the motor-generator set has sloned down from nearly
synchronous speed to full-load speed. In the meanwhile,
the inertia of the rotating parts supplies the energy, and
thus the rate at which power is drawn from t,he system is
1,-..- ., ,..__
“. .. materially reduced. Furthermore, as in the case of syn-
Fig. 22--Motor-generator set. chronous driving motors, if the generator load consists of
a series of short pulses, the load is off before its full effect
set between the utilization device and the power system is transmitted to the power system, and the peak load on
gives the maximum possible reduction in flicker, because the system is thereby decreased. Because an induction
it is effective in minimizing three of the most undesirable motor must actually slow down, whereas a synchronous
load characteristics: single phase, low power factor, and motor merely shifts in phase, the rate of load application
sudden application. Since the only tie between the motor to the power system is less for the induction than for the
and the generator is the shaft, the disturbances due to synchronous motor. On an average, it takes an induction
single-phase load or to low power factor are not transferred motor-generator set about one second to transfer full load
to the power system. The reactance of the driving motor, to the source. In Fig. 3, it is shown that this delay alone
in conjunction with the flywheel effect of the motor and results in doubling the threshold of flicker perception, as
generator delay the transfer of a change in load to the compared with the perception due to sudden voltage dip
: power system. The rate at which the voltage drops is of equal magnitude.
t)hcrcfore lessened and the eye is less likely to perceive If the load pulses last several seconds, the power drawn
this flicker. from the system levels off to the amount of generator load
The motor-generator set is probably the costliest ar- plus losses for either a synchronous or squirrel-cage motor
rangement, heaviest, least efficient, and occupies more drive. The voltage drop in the power system during this
floor space than any of the various corrective devices that steady load period is usually about the same for either
can be used. But the m-g set has the advantage of con- the induction or synchronous motor drive, assuming that
sisting entirely of standard equipment, and is, therefore, the excitation of the synchronous motor is constant. By
’ reliable and well understood apparatus. The motor end increasing the synchronous-motor excitation w&h the load
I may be synchronous, squirrel-cage induction, or wound the final regulation of the system can be made very small.
I rotor induction, the latter usually being provided with a However, from the standpoint of flicker such excitation
1 flywheel and slip regulator. The generator end may be changes are usually imperceptible because of the time
732 Lamp Flicker on Power Systems Chapter 22

required for correction. Thus, from the flicker standpoint,


the principal superiority of the induction motor to the
synchronous motor is the doubling of the threshold of
perception, because of slower load application. This is
particularly so for short pulses of power, say s second
and less, where the induction set draws considerably lower
peaks than the synchronous set.
A further material reduction in flicker can be effected by
the use of motor generator sets equipped with flywheels.
In such cases a wound-rotor-induction motor is used, and
additional rotor or secondary resistance is connected ex-
ternally. By this means, the full-load slip of the motor can
be increased from 1 or 2 percent to 10 percent or more.
In order to transfer full load to the system, the set must
then slow down considerably and the fullest advantage is
thus taken of the inertia of the set and the additional fly-
wheel. The extent to which improvement by this means
may be carried is limited by cost and each case must be
TIME-SECONDS
considered on its own merits. Limitation of peak demand
is probably not feasible for loads in excess of about 3 Fig. 24-Curves showing the relation between the power sup.
seconds, but the reduction of rate of load application plied by the generator and the power taken from the system
may nevertheless be of benefit. for motor-generator sets using three types of motors. ten-
erator load on for 0.1 second.
Figures 23 and 24 bring out in graphic form the points
.
discussed above. These curves were calculated using typi-
cal machine constants, and to facilitate computation, losses cycle. It can be seen that the system load builds up at
were neglected except when used to calculate speed changes about half the rate as for the synchronous motor, and that
on the induction sets. it does not become equal to the applied load until the end
The curves of Fig. 23 are for a load on 1% seconds and of the load application. The system load never exceeds
off 4% seconds. Curve (a) represents the load drawn by the applied load disregarding, of course, m-g set losses,
the synchronous set, and shows that it takes approximately and the difference between input and output during the
0.2 seconds for the system load to equal the generator load, early part of the load cycle is compensated by a similar
and also that an “overswing” of about 35 percent makes exponential continuance of load on the system for some
up for the deficiency between input and output during the time after the applied load has ceased. Curve (c) is for a
first 0.2 second. A similar swing occurs when the load is wound rotor motor with a constant secondary resistance
dropped. Curve (b) shows the load drawn by a standard and a flywheel. The relation between slip, flywheel effect
squirrel cage induction motor subject to the same load and load cycle is such that although the generator load
goes on and off, the system load never drops to zero. The
rate of load application is very low, and the system peak
is only about a third of the load peak.
The curves of Fig. 24 are for a load cycle of 0.1 second on
and 5.9 seconds off. Curve (a) is for a synkhronous motor
and shows that the peak system load is qbout two-thirds
of the generator load. Curve (b) is for the squirrel cage set
and shows a system peak of less than ?,$ of the generator
peak. Curve (c) is for the flywheel set and shows a system
peak of about 3 percent of the load peak.
Figures 23 and 24 are of interest in illustrating the manner
in which motor-generator sets transfer power from load
to line, and suggest the conditions under which the various
motors are most suitable. As pointed out previously, the
phase balancing and power factor improvement qua11 .ths
are usually the most valuable factors in the correction
of flicker.
.There are so many variables in load, power factor, duty
cycle, etc., that general figures on the iyrovement that
0
can be expected may be open to criticism.’ For very a~
TIME-SECONDS
proximate purposes, however, it can be expected that If the
load changes last one second or more, either synchronous
Fig. 23-Curves showing the relation between the power sup-
plied by the generator and the power taken from the system
or squirrel cage induction sets without flywheels reduce
for motor-generator sets using three types of motors. Gener- the voltage drop to g for single-phase loads and to @ for
ator load on for 1.5 seconds. polyphase loads. The perceptibility of the flicker 1s ye-
Chapter 22 Lamp Flicker on Power Systems 733

duced still further by the slower rate at which the voltage vices such as inductances and capacitors, or in rotating
dips, particularly with the induction set. For loads of very equipment with mechanical inertia. Except for small sizes,
short duration such as M second and less the voltage drop the static equipment has not yet been found commercially
may be reduced to l/10 or even l/20. practical.
Motor generator sets may be had with either single- or A lack of appreciation of this fundamental energy re-
three-phase generators. Even when the generator is single quirement has led to frequent proposals of schemes at-
phase, it is customary to use a three-phase star stator tempting single-phase to polyphase conversion by trans-
winding using only two legs in series. The third phase is former connection. Fig. 25 is typical of these schemes. It
wound for possible future use, or to increase synchronizing
power if paralleled with other units, or dummy coils may
be placed in the slots. If single-phase loads are to be I
I
carried, the field must be built with low resistance damper
windings to minimize rotor heating. In the larger sizes,
single-phase machines are mounted on springs to minimize tI
vibration due to the pulsating torque caused by single-
phase operation.
When more than one utilization device causing flicker is
involved, the question of a single m-g set versus an m-g set
for each such load must be answered. In these cases it is
very important to consider the regulation of the generator
of the set and how constant a voltage is required by the
utilization devices. For example, it frequently happens
that a factory is using several electric welders which pro-
duce 5 percent voltage dips of very objectionable fre-
quency. This 5 percent drop usually does not affect the
performance of the welders, and they could be operated
at, random on the power system. If a motor-generator set I I
is to be used, however, the transient reactance of the gen-
SINGLE PHASE LOAD
crater is apt to be as high as 35 percent based on its rated
current, and, assuming that the welder reactive current Fig. 25-Unsound attempt to supply balanced three-phase
equals the generator rating, a 35 percent drop in voltage power to a single-phase load.
would occur. Tf only one welder is operated at a time, this
is quite satisfactory, as the welder tap can be set on the is not only completely ineffective for its intended purpose,
basis of “closed circuit” voltage, that is, the regulation of but is also wasteful of transformer capacity. Although the
the generator can be taken into account. If, however, transformers are all loaded equally, the currents drawn
another welder is operated simultaneously, even though from the source as shown by the current arrows, are still
on another phase, the additional voltage drop, uncom- single-phase, and a single-phase transformer is, therefore,
pensated by the welder tap, is enough to spoil the weld. preferable.
In order to operate several “choppy” loads simultaneously The most familiar type of phase converter is that shown
from the same m-g set, it is therefore necessary to use an in Fig. 26. It has been extensively used in railway elcctri-
oversize generator (from a thermal standpoint) to keep fications to convert single-phase power from the contact
the regulation within required limits. Alternate solutions system to three-phase power for the locomotive motors;
are to interlock utilization devices so that they cannot this is merely the converse of the phase-balance. As shown,
operate simultaneously or to provide separate m-g sets for a rotating two-phase machine is connected to the three-
each device. Another alternative is to use one common
driving motor and several separate generators on the same
shaft. The separate m-g set plan has the advantage of
permitting operation at partial capacity in case of damage
to one set, but is costlier.
4. Phase Balancers
In industrial plants a large percentage of the potential
causes of flicker are single-phase devices. A discussion of
phase balancers is, therefore, of interest, although there
have been few commercially installed.
In a single-phase circuit the flow of power pulsates at
a frequency twice that of the alternating supply, whereas Fig. 26-Schematic diagram for phase converter used ex-
in a balanced polyphase circuit the flow of power is uni- tensively on railway electrifications to convert single-phase
power from the trolley to three-phase power for the locomo-
form. Therefore, in order to effect a conversion between tive motors. A rotating two-phase machine is connected
a single-phase and a polyphase system, some energy stor- through the equivalent of a Scott-connected transformer to
age is necessary. This storage may be made in static de- the three-chase- IDower svstem.
734 Lamp Flicker on Pou;er Systems Chapter 22

phase power system through the equivalent of a Scott- When a single-phase load is suddenly applied, a magneti&
connected transformer, which also serves as the primary ing transient results, so that part of the negative-sequence
for the single-phase load winding. The two-phase machine component of load current is passed on the source. ~1~
may be of the induction type and act as a phase converter though this transient subsides in about 0.1 second, it
only, or it may be synchronous and used for power factor detracts considerably from the value of the scheme for
correction as well. Because of the regulation of the ma- use with “choppy” loads.
chine, the source currents are not balanced during variable- The series impedance balancer shown in Fig. 28 consists
load conditions, unless the taps on the transformer winding of an ausiliary induction-type machine in series with the
are varied. From this point of view, it is not very suitable polyphase supply and with the main shunt machine.
for “choppy” loads. Where there are several separate The single-phase load is drawn from between the two
single-phase loads to be served, the capacity of a converter The series machine rotates oppositely to normal directioi
of this type must be equal to the sum of the individual for positive-sequence applied voltage, and therefore, offers
loads. high impedance to negative-sequence currents and low
The series type of phase converter is shown in Fig. 27. impedance to positive-sequence currents. The shunt ma-
This is probably most efficient for conversion from three- chine therefore takes the negative-sequence component of
load current. The positive-sequence component of load
current is taken by the system if the shunt is an induction
type unit. If a synchronous type unit is used for the shunt
machine, it can also take the wnttless component of load
THREE PHASE current with suitable control of e