Professional Documents
Culture Documents
Hong 2017
Hong 2017
fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRD.2017.2707922, IEEE
Transactions on Power Delivery
> REPLACE THIS LINE WITH YOUR PAPER IDENTIFICATION NUMBER (DOUBLE-CLICK HERE TO EDIT) < 1
0885-8977 (c) 2016 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRD.2017.2707922, IEEE
Transactions on Power Delivery
> REPLACE THIS LINE WITH YOUR PAPER IDENTIFICATION NUMBER (DOUBLE-CLICK HERE TO EDIT) < 2
v(t)
RM LM ZL [kV] 0
a2
a1 a3
Δt
t
-50
2
(a) 5
R1 Ls R2 di/dt 0 0
v1(t) v2(t) [kA/ms]
-2 -5 i(t) [kA]
i1(t) i2(t)
Fig. 2. 3-D Lissajous curve for a 300 MVA transformer.
RM1 LM1 RM2 LM2 ZL
To illustrate the data-driven online diagnostics process, we
start with the discussion of the discretized data acquisition
system. The sampling frequency is fs and the corresponding
(b) sampling time is Δt. The kth data set obtained from the acquisi-
Fig. 1. Two equivalent circuits for a transformer: (a) T equivalent circuit; (b) π tion system is denoted as {v12[k], i12[k]}, where v12[k], i12[k] are
equivalent circuit.
0885-8977 (c) 2016 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRD.2017.2707922, IEEE
Transactions on Power Delivery
> REPLACE THIS LINE WITH YOUR PAPER IDENTIFICATION NUMBER (DOUBLE-CLICK HERE TO EDIT) < 3
discretized v12(t) and i12(t) of the kth sample. Each data set sat- accurately. When the measurements are not accurate (have
isfies (3). After N data sets are collected, we have: noise), the inaccuracies will be magnified by taking derivatives.
𝑑 According to (5), the standard deviation of the error introduced
𝑖12 [1] 𝑖 (𝑡)| 𝑅𝑇
𝑣12 [1] 𝑑𝑡 12 𝑡=∆𝑡+𝑡0 by white noise will be amplified by √2/Δt times. Hence, merely
[ ⋮ ]= ⋮ ⋮ [2] (4) increasing the sampling rate fs (using a faster data acquisition
𝐿𝑇
𝑣12 [𝑁] 𝑑 system) will reduce the numerical measurement error, but
𝑖12 [𝑁] 𝑖 (𝑡)| 2
[ 𝑑𝑡 12 𝑡=𝑁∆𝑡+𝑡0 ] magnify the error introduced by noise.
where N is the observation window length; t0 is the initial time Using a high order differentiation method is a sensible choice
and assumed to be zero in this paper. When the measurements to solve the problem. An 8-point stencil central differences
are sufficiently accurate, the current derivative can be ap- (SCD) method is applied in this paper to reduce the effect of
proximated by a first-order difference to save computational noise. The mathematical expression of the 8-point SCD method
power. Yielding: at the kth sample is [15]:
𝑑 𝑖12 [𝑘 + 1] − 𝑖12 [𝑘] 𝑑 4(𝑖𝑘+1 − 𝑖𝑘−1 ) (𝑖𝑘+2 − 𝑖𝑘−2 )
𝑖12 (𝑡)| = (5) 𝑖| ≈ −
𝑑𝑡 𝑡=𝑘∆𝑡 ∆𝑡 𝑑𝑡 𝑡=𝑘∆𝑡 5∆𝑡 5∆𝑡 (9)
4(𝑖𝑘+3 − 𝑖𝑘−3 ) (𝑖𝑘+4 − 𝑖𝑘−4 )
+ −
For simplicity, we convert (4) into a matrix as follows: 105∆𝑡 280∆𝑡
1 𝑅 where i is the target current function; the subscript is the sample
𝑽12 = 𝑰12 [ 𝑇 ] (6)
index. To calculate the initial derivative of the current, the
2 𝐿𝑇
where 𝑽12 is a N × 1 column vector containing the information current measurement from previous observation window can be
of instantaneous voltage measurements; 𝑰12 is a N × 2 matrix used.
containing the information of instantaneous current measure- C. De-Noising Implementation
ments and its derivative. By minimizing the 2-norm of the
difference between the left and right sides of (6), we obtain: Measurement noise is a nuisance for all online diagnostics
1 methods. As mentioned before, the noise is amplified when
𝑅 𝑅
[ 𝑇 ] = arg min ‖𝑽12 − 𝑰12 [ 𝑇 ]‖ (7) taking the derivatives during the numerical computation pro-
𝐿𝑇 𝑅𝑇 ,𝐿𝑇 2 𝐿𝑇 2
cess. To minimize the impact from measurement noise, it is
Solving problem (7) as a standard ridge regression, the fol-
better to select a larger observation window length N at the cost
lowing analytical solution is obtained [13]:
of a slower response time to the system dynamics.
𝑅
[ 𝑇 ] = 2(𝑰12
𝑇
𝑰12 + 𝜆𝑬)−1 𝑰12
𝑇
𝑽12 (8) The winding deformation monitor is a system for protecting
𝐿𝑇
𝑇 transformers in steady state. Hence, the dynamic performance
where 𝜆 is a regulation factor used in cases when 𝑰12 𝑰12 is
can be sacrificed a little to improve accuracy and robustness to
ill-conditioned; E is the identity matrix of the same dimension
𝑇 𝑇 measurement noise. The relationship between sampling fre-
as 𝑰12 𝑰12 . Based on our experience, 𝑰12 𝑰12 normally has an
quency fs and the observation window length N is:
acceptable condition number. Hence, 𝜆 is set to zero for most
𝑓𝑠
cases. Under the extreme situation when the condition number 𝑁 = 𝛼 ∙ 𝑁𝑐 = 𝛼 ∙ (10)
𝑇
of 𝑰12 𝑰12 is larger than 105, 𝜆 is set to 0.01. Based on our ex- 𝑓1
perience this solves all problems with ill-conditioned matrices. where Nc is the number of the samples per cycle and f1 is the
Note that (8) is a very simple equation which can be calcu- fundamental frequency of the target power system; α is a posi-
lated directly based only on online measurements regardless the tive integer. According to (10), the diagnostics system performs
shapes of voltage and current waveforms. Different from most leakage impedance identification every 𝛼 cycles.
of the previous studies, the proposed online diagnostics method Instead of selecting a large observation window length N, a
has no strict requirements on the quality of the input voltage low-pass filter has been attached after the identification process.
and the load connected to the transformer. The transfer function of a digital Butterworth low-pass filter of
m-order can be expressed as:
B. Application to Transformer Diagnostics Y(𝑧) 𝑏(1) + 𝑏(2)𝑧 −1 + ⋯ + 𝑏(𝑚 + 1)𝑧 −𝑚
According to the IEEE Std. 62 [14], changes in total winding 𝐻(𝑧) = = (11)
𝑋(𝑧) 𝑎(1) + 𝑎(2)𝑧 −1 + ⋯ + 𝑎(𝑚 + 1)𝑧 −𝑚
resistance within 5% are considered satisfactory. This means where a(k) and b(k) are the transfer function coefficients which
that the maximum allowable deviation of the winding re- can be obtained from the cutoff frequency of the low-pass filter
sistance is 5%. Meanwhile, the maximum allowable deviation [16]. According to (11), the output of the low-pass filter at the
of the leakage inductance is 3% [14]. As a result, the error of (k+1)th sample is:
the online diagnosis process should be much smaller than 𝑦[𝑘 + 1] = 𝑏(1)𝑥[𝑘 + 1] + 𝑟1 [𝑘] (12)
3% for leakage inductance and 5% for winding resistance. where
Hence, numerical errors are critical especially when the de- 𝑟𝑖 [𝑘] = 𝑏(𝑖 + 1)𝑥[𝑘] + 𝑟𝑖+1 [𝑘 − 1] − 𝑎(𝑖 + 1)𝑦[𝑘],
formation has just occured (minor change in the short-circuit 𝑟𝑚 [𝑘] = 𝑏(𝑚 + 1)𝑥[𝑘] − 𝑎(𝑚 + 1),
impedance). x[k+1], y[k+1] are the input and output of the low-pass filter at
The leakage impedance (inductance) of large power trans- the (k+1)th time step; ri[k] has the information of the past, which
formers is usually much larger than the winding resistance. can be used to set the output initial value of the low-pass filter.
Therefore, it is crucial to compute the derivatives of the current
0885-8977 (c) 2016 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRD.2017.2707922, IEEE
Transactions on Power Delivery
> REPLACE THIS LINE WITH YOUR PAPER IDENTIFICATION NUMBER (DOUBLE-CLICK HERE TO EDIT) < 4
In this paper, the input and output of the low-pass filter are following section, the winding resistance and leakage induct-
the total winding resistance or total leakage inductance ob- ance are distributed in a realistic fashion, meaning R1 ≠ R2 and
tained from (8). The initial values of the low-pass filter are set L1 ≠ L2. A hysteretic inductor represents the core (nonlinear
to be the leakage impedance obtained from the factory im- magnetizing current and losses) in the simulation studies. The
pedance test. The initial value of the winding resistance needs simulations are made as realistic as possible.
to be constantly adjusted because it changes with temperature.
The IEEE Std. 62 [14] gives the following expression: III. NUMERICAL EXAMPLE WITH TRANSFORMER EQUIVALENT
𝑇𝑡 + 𝑇𝑐𝑜𝑝𝑝𝑒𝑟 MODEL
𝑅𝑇 [0] = 𝑅𝑇,𝑡0 (13)
𝑇𝑡0 + 𝑇𝑐𝑜𝑝𝑝𝑒𝑟 Sinusoidal voltage excitation and supplying linear loads are
where 𝑅𝑇 [0] is the initial value of the winding resistance to be the expected working conditions of a transformer. However,
entered to the low-pass filter, Tt is the temperature at which the loads are increasingly becoming more nonlinear because of the
resistance was measured in ˚C, Tt0 is the reference temperature widespread use of power electronics supplies. To validate the
in ˚C, 𝑅𝑇,𝑡0 is the winding resistance measured at Tt0; Tcopper is a accuracy and robustness of the proposed online diagnostics
constant equals to 234.5˚C for copper windings. If temperature method, several numerical examples are provided in this sec-
measurements are not available, the winding resistance cannot tion.
be used as an indicator for winding deformation and one must A. Evaluation of the Identification Error using Simulated
rely only on the changes in inductance. In the following dis- Terminal Data from Different Transformer Models
cussion, we assume that temperature measurements are avail-
Based on the simulated measurement data, the proposed di-
able and the initial value of the winding resistance has been
agnostics method is applied to identify the short-circuit im-
adjusted accordingly. The flow chart of the proposed online
pedances when the transformer is loaded at rated condition.
diagnostics method is shown in Fig. 3.
The equivalent circuits of T and π models shown in Fig. 1 are
built in EMTP-RV [18]. The corresponding circuit parameters
Initialize
k, i
Start detection of the T and π models are listed in Table I. All the parameters
are obtained from a real 300 MVA transformer from [19] and
Prepare matrices
No V12, I12 based on Calculate RT[i] and referred to the primary side. The medium voltage winding is not
If k < N
(4) and (5)/(9); LT[i] based on (8) used in this study. The magnetizing inductances are modeled
Yes i = i + 1;
using hysteresis curves.
Store data set TABLE I
{v12[k], i12[k]} Pass RT[i] and
k = k + 1; Output RT[i], LT[i] to CIRCUIT PARAMETERS FOR T AND π CIRCUITS
LT[i] to low-pass
monitor R1 R2 Ls1 Ls2 Rm Ls Rm1, Rm2
filter (12)
[Ω] [Ω] [mH] [mH] [kΩ] [mH] [kΩ]
Set k = 0
0.26 0.2605 15.1 20 53 35.1 106
Calculate
If ΔL > 3% ΔL=|LT[i]–LTref|/LTref If ΔR > 5% The voltage sources for the two circuits are cosine functions:
Yes No ΔR=|RT[i]–RTref|/RTref Yes
No 𝑣(𝑡) = 𝑉𝑚 cos(𝜔1 𝑡) (14)
where Vm equals to 281.7 kV and ω1 equals to 120π. The sim-
Inductive Heath condition Resistive ulation time step is 20 s. The sampling frequency of the data
abnormality alarm abnormality alarm
acquisition system is 2.5 kHz which means 50 data points per
Fig. 3. Flowchart of the transformer winding diagnostics process. cycle. Several commercial transformer monitors or digital
differential relays claim that they can provide faster sampling
D. Discussion of Assumptions frequencies [20]-[21]. Hence, additional investment in data
Most of the existing online SCI methods assume that the acquisition systems is not needed for the proposed method. The
input voltage is sinusoidal and the load connected to the rated load with unity power factor is connected to the two
transformer is linear. In comparison, the proposed method has transformer models, namely ZL = 131.92 [Ω].
no requirements on the input voltage or load behavior. How- The maximum identification error in percent between the
ever, several assumptions were made during the derivation of identified RT and its reference is calculated as:
𝑓
the proposed online diagnostics method. We assumed that a max|𝑅𝑇 (𝑡) − 𝑅𝑇 |
∆𝑅𝑇 = 𝑓
× 100% (15)
transformer could be modeled by a T equivalent circuit with 𝑅𝑇
identical equivalent winding resistance and leakage inductance where ∆𝑅𝑇 is the maximum identification error in percent; 𝑅𝑇
𝑓
of the primary and secondary windings. The T equivalent cir-
is the reference winding resistance obtained from the imped-
cuit is not the best choice for modeling single phase trans-
ance test (and considering variations with temperature). The
formers in the presence of saturation [17]. Additionally,
winding resistances of primary and secondary depend on the maximum identification error of leakage inductance ∆𝐿 𝑇 is
calculated in a similar manner.
wire gauge, the number of turns, winding dimensions, manu-
facturing process, etc. The time sequence identification errors are shown in Fig. 4.
The assumptions mentioned above are not strict require- The maximum identification errors on the winding resistance
and leakage inductance are summarized in Table II. According
ments for the implementation of the proposed method. In the
0885-8977 (c) 2016 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRD.2017.2707922, IEEE
Transactions on Power Delivery
> REPLACE THIS LINE WITH YOUR PAPER IDENTIFICATION NUMBER (DOUBLE-CLICK HERE TO EDIT) < 5
to the results shown in Table II, the maximum error in total tion (power factor = 0.707) are considered.
winding resistance RT is 0.196% and the maximum error in When the transformer is loaded at rated current, the accuracy
leakage inductance LT is only 0.074%. The error in the identi- of the identification results is affected by the changes in power
fication process comes from the computation process of deriv- factor; see Fig. 5. The maximum identification errors from
atives and nonlinear currents from the nonlinear magnetizing cases 1 to 8 are summarized in Table IV. Accordingly, the
branches. identification error of the winding resistance is larger when a
capacitive load is connected to the transformer. In contrast, the
Error in RT [%] Error in LT [%]
0 0.08 maximum inductive identification error occurs when the
-0.05 0.06 transformer is loaded by a lightly inductive load. Although ∆𝑅𝑇
π
-0.1 () T is almost 5 times larger than ∆𝐿 𝑇 (see Table IV), the simulation
T 0.04
-0.15 π results show that the proposed method still can be used for
-0.2 0.02 () identifying transformer winding deformations.
-0.25 0
0 0.2 0.4 0.6 TABLE III
0 0.2 0.4 0.6
Time [s] Time [s] LINEAR LOADING CONDITIONS (RLC IN SERIES)
(a) (b) |ZL| [Ω] RL [Ω] LL [mH] CL [μF] Power Factor
Fig. 4. Identification errors when using simulated terminal measurements: Case 1 131.92 0 0 1
(a) Identification error in total winding resistance RT (0.5206 Ω); (b) Identifi- Case 2 129.92 60.76 0 0.985 (lagging)
131.92
cation error in total leakage inductance LT (35.1 mH). Case 3 93.28 247.4 0 0.707 (lagging)
(rated)
Case 4 93.28 0 28.4 0.707 (leading)
TABLE II Case 5 129.92 0 115.8 0.985 (leading)
MAXIMUM ERROR IN PERCENT UNDER RATED LOADING Case 6 263.84 0 0 1
∆𝑅𝑇 [%] ∆𝐿 𝑇 [%] 263.84
Case 7 186.56 494.87 0 0.707 (lagging)
T model 0.196 0.074 (half)
Case 8 186.56 0 14.2 0.707 (leading)
π model 0.020 0.059
Comparing ∆𝑅𝑇 and ∆𝐿 𝑇 , one can appreciate that the iden- Error in RT [%] Error in LT [%]
0.6 0.08
tification error is not equally distributed between RT and LT
since ω1LT is much larger than RT; see Table I. This phenom- 0.4 0.07
enon brings significant problems to the identification of the 0.2 0.06
winding resistance when measurement noise is considered. For Cases 1 and 5 overlapped
now, the identification results of the leakage impedance with 0 0.05
the two models are small and acceptable. According to Fig. 4, -0.2 0.04
the identification results of T and π models are close to each
-0.4 0.03
other. The maximum deviation of the identification results 0 0.2 0.4 0.6 0 0.2 0.4 0.6
between T and π models is 0.18%. Although the derivation of Times [s] Times [s]
(8) is obtained using the T equivalent circuit, the identification
Case 1 Case 2 Case 1 Case 2
accuracy is higher when the π equivalent circuit is used to Case 3 Case 4 Case 3 Case 4
simulate transformer terminal measurements. According to Case 5 Case 5
(a) (b)
[17] and [22], the π model is more accurate than the T model for
Fig. 5. Identification errors for a fully loaded transformer. (a) Identification
the representation of transformers. Hence, the π model is used errors in RT (0.5206 Ω) from cases 1 to 5; (b) Identification errors in LT (35.1
to simulate the transformer terminal measurements in the next mH) from cases 1 to 5.
four numerical studies.
Error in RT [%] Error in LT [%]
0.6 0.07
B. Evaluation of the Identification Error when Changing
0.4
Loading Cases 1 and 6 overlapped 0.06
0.2
The load is modeled as constant impedance during at least Cases 1 and 6 overlapped
0 0.05
one fundamental period in this example. Changes in the loading
-0.2
conditions are defined as changes in the amplitude of the cur- 0.04
-0.4
rent and power factor. Without magnetizing branch, the iden-
-0.6 0.03
tification process is independent of the changes in the loading 0 0.2 0.4 0.6 0 0.2 0.4 0.6
conditions. However, the magnetizing branch current cannot be Time [s] Time [s]
neglected in practice. In this subsection, the impacts coming Case 1 Case 6 Case 1 Case 6
from the loading condition are discussed in detail. Case 7 Case 8 Case 7 Case 8
(a) (b)
In the following examples, several loading scenarios are
Fig. 6. Identification errors for a half loaded transformer. (a) Identification
simulated with the π equivalent circuit. The loading conditions errors in RT (0.5206 Ω) from cases 1 and 6 to 8; (b) Identification errors in LT
are summarized in Table III. For a normal power system, the (35.1 mH) from cases 1 and 6 to 8.
power factor is commonly larger than 0.8. Hence, both the
normal operation (power factor = 0.985) and the worst condi-
0885-8977 (c) 2016 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRD.2017.2707922, IEEE
Transactions on Power Delivery
> REPLACE THIS LINE WITH YOUR PAPER IDENTIFICATION NUMBER (DOUBLE-CLICK HERE TO EDIT) < 6
0885-8977 (c) 2016 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRD.2017.2707922, IEEE
Transactions on Power Delivery
> REPLACE THIS LINE WITH YOUR PAPER IDENTIFICATION NUMBER (DOUBLE-CLICK HERE TO EDIT) < 7
resistance and inductance are reduced by 5% and 3% in case C. tics methods, the proposed method in this paper has no re-
In the third simulation (case D), we first simulate the case using quirements of voltage quality or linear load behavior. Two
a five-order low-pass filter with 5 Hz cutoff frequency. The numerical examples are provided next to validate this state-
three simulation results are shown in Fig. 8. ment.
Deviation in RT [%] Deviation in LT [%] Deviation in RT [%] Deviation in LT [%]
10 4 10 0
Case B 3 Case F -1
8
5 2
Case B -2
Case D 1 Case D 6
0 0 -3
4 Case F
Case A -1 Case C -4 Case E
Case A
-5 -2 2 Case E -5
-3
Case C 0 -6
-10 -4
0 50 100 0 50 100
0 50 100 0 50 100 Time [s] Time [s]
Time [s] Time [s]
(a) (b) (a) (b)
Fig. 8. Winding deformation diagnostics with linear load: (a) deviation of the Fig. 10. Winding deformation diagnostics with non-sinusoidal excitation and
winding resistance RT; (b) deviation of leakage inductance LT. nonlinear load: (a) deviation of the winding resistance RT; (b) deviation of
leakage inductance LT.
In all three simulations, the initial values of the low-pass
filter are equal to the leakage impedance obtained from The input voltage of the transformer is a combination of
short-circuit test. Hence, explicit dynamic responses can be fundamental frequency and 3rd harmonic. The mathematical
found in Figs. 8(a) and (b). It takes 20 s for the stabilization of description of the voltage source is:
𝜋
the low-pass filter when winding deformations occur (the 𝑣(𝑡) = 𝑉𝑚 cos(𝜔𝑡) + 0.1𝑉𝑚 cos (3𝜔𝑡 + ) (17)
oscillations in Figs. 8(a) and (b) are created by the measurement 6
rd
The amplitude of the 3 harmonic is set to be 10% of the fun-
noise). As mentioned before, if the order of the low-pass filter is
damental frequency to produce an extremely bad input voltage.
increased and the cutoff frequency is reduced, the identification
Two cases are simulated in this section. In the first case (case E),
results become more robust to noise, but the stabilization time
the transformer carries half load with a 0.707 leading power
increases; see the dotted lines in Figs. 8(a) and (b).
factor. The second case (case F) has the transformer connected
After the output of the low-pass filter is stable, the defor-
to a nonlinear resistor and nonlinear inductor. The normalized
mations on both resistance and inductance can be found in Fig.
primary terminal voltage and secondary current for case E are
8. Although the identification results on the winding resistance
shown in Fig. 9(a). The normalized nonlinear behavior of the
are heavily polluted by measurement noise, one still can find
resistor and inductor are shown in Fig. 9(b). Similar to the
resistive deformation looking at Fig. 8(a). In comparison, the
previous studies, a 1% noise is added to the measurements in
proposed method is very accurate for inductive deformation
both simulation studies. The winding resistance is increased by
detection. Since inductive deformation is the major defor-
5% and the leakage inductance is reduced by 5% to create a
mation that occurs in practice, the proposed method can
different example. The results can be found in Fig. 10. One can
effectively detect incipient winding deformations.
observe that both resistive and inductive deformations can be
1 detected under very severe circumstances (including input
1
v1(t) LL(i) voltage harmonics, nonlinear loads, and noise). Although errors
Voltage(Flux) p.u.
0.5 0.5 can be found in the identification results, the diagnosis results
0 0 RL(i) are still trustable.
0885-8977 (c) 2016 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRD.2017.2707922, IEEE
Transactions on Power Delivery
> REPLACE THIS LINE WITH YOUR PAPER IDENTIFICATION NUMBER (DOUBLE-CLICK HERE TO EDIT) < 8
rounding domain is padded to about 3 times in all the directions 1.3% which will not create a resistive deformation alarm. In
to ensure that all the flux remains inside the solution domain. contrast, a large difference (9.4%) on the leakage inductance
We verified that a negligible error is introduced by the termi- can be found in Fig. 12(b). As a result, the inductive defor-
nation of the domain. A Neumann boundary condition is used mation alarm is created to inform the operator.
as the external boundary. A magnetostatic analysis was carried
B. Experimental Validation
out to determine the sensitivity of magnetizing and leakage
inductance (calculated using the magnetic energy meth- The proposed method has been validated with a lab experi-
od) changing mesh size. Based on this analysis, appropriate ment. The secondary of a small transformer (see Fig. 13) has
mesh setting (70,831 elements) was chosen and used for the been moved down to almost touch the yoke to create a winding
time-domain simulations. The online measurements are deformation. The primary voltage and current recorded with a
obtained from the voltmeter and ammeter available in the cir- LabVIEW data acquisition module are shown in Fig. 14(a). The
cuit interface of Ansys Maxwell. A cosine excitation is used in sampling frequency is 2.5 kHz. One can see from Fig. 14(a) that
the circuit interface to avoid transformer inrush transients. The the primary voltage and current are not perfect sinusoidal
simulation time is 0.1 s and the time step is 1/3000 s. waveforms. Fig. 14(b) presents the detection results without the
use of a low-pass filter. As shown in Fig. 14(b), the proposed
method can identify the transformer winding deformation when
the transformer is loaded. The leakage inductance of the
transformer has increased 18% when the secondary winding
falls down. One can see that the differences between the cal-
culated inductances (Lissajous method) and the standard
short-circuit test results are negligible. With the help of a
low-pass filter, the impact of the measurement noise can be
eliminated; see Fig. 15.
(a) (b)
Fig. 11. FEM of a 167 kVA transformer; (a) transformer model with no de- Primary
formation; (b) transformer model with deformation (the winding has moved winding Primary
down 4 in). winding
Secondary
winding Secondary
RT [Ω] LT [mH] Support winding
19.1 71
No
Deformed 69 Support
19 Deformed
67
18.9 (a) (b)
Normal 65 Normal
Fig. 13. Experimental setup for winding deformation diagnostics system test;
18.8 63 (a) normal transformer; (b) deformed transformer.
10 30 50 70 90 10 30 50 70 90
Time [ms] Time [ms] 30 1.6
Deformed
NoFull DeFull NoShort NoFull 20 v1(t) [V] 1.5
LT [mH]
0885-8977 (c) 2016 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRD.2017.2707922, IEEE
Transactions on Power Delivery
> REPLACE THIS LINE WITH YOUR PAPER IDENTIFICATION NUMBER (DOUBLE-CLICK HERE TO EDIT) < 9
V. CONCLUSION [14] IEEE Guide for Diagnostic Field Testing of Electric Power Appa-
ratus-Part 1: Oil Filled Power Transformer, Regulators, and Reactors,
In this paper, a data-driven online diagnostics method for the IEEE Standard 62-1995 (R2005), Mar. 2005.
detection of transformer winding deformation has been pro- [15] F. Bengt, “Generation of finite difference formulas on arbitrarily spaced
grids,” Mathematics of Computation, vol. 51, no. 184, pp. 699-706, Oct.
posed. The method is robust even under extremely severe 1988.
working conditions such as: noisy measurements, load changes, [16] A. V. Oppenheim and R. W. Schafer, Digital Signal Processing. Eng-
input harmonics, and system nonlinearities. lewood Cliffs, NJ: Prentice-Hall, 1975.
[17] F. de Leόn, A. Farazmand, and P. Joseph, “Comparing the T and π
Several numerical examples illustrate the virtues of the
equivalent circuits for the calculation of transformer inrush currents,”
proposed method. FEM simulations and a lab experiment con- IEEE Trans. Power Del., vol. 27, no. 4, pp. 2390-2398, Oct. 2012.
firm that the method can successfully detect the change of [18] DCG-EMTP (Development coordination group of EMTP) Version
short-circuit impedance created by winding deformations. The EMTP-RV, Electromagnetic Transients Program. [Online]. Available:
http://www.emtp.com.
results provided in this paper demonstrate that the novel [19] X. Chen, “Negative inductance and numerical instability of the saturable
method is implementable in practice for detecting transformer transformer component in EMTP,” IEEE Trans. Power Del., vol. 15, no.
winding abnormality. Only information already available to the 4, pp. 1199-1204, Oct. 2000.
[20] Data Sheet of SEL-2414 Transformer Monitor, “SEL-2414 Transformer
differential protection relay is needed. According to the case Monitor,” Sept. 2016. [Online]. Available:
studies from cases D to E, the proposed method is more noise http://selinc.com/products/2414.
resistive for identifying the change in the leakage inductance [21] Manuals of T60 Transformer Management Relay, “T60 Instruction
Manual for 7.3x product version (Rev. AB2),” Sept. 2015 [Online].
which is usually caused by winding deformation. Hence, the Available: http://www.gegridsolutions.com/multilin/catalog/t60.htm.
proposed method is a promising candidate for detecting wind- [22] M. Lambert, M. Martinez-Duro, Jean Mahseredjian, F. de Leόn, F. Sirois,
ing deformations. “Transformer leakage flux models for electromagnetic transients: critical
review and validation of a new model,” IEEE Trans. Power Del., vol. 29,
no. 5, pp. 2180-2188, Oct. 2014.
REFERENCE
[1] N. Hashemnia, A. A-Siada, and S. Islam, “Improved power transformer
winding fault detection using FRA diagnostics – part 2: radial defor- Tianqi Hong (S'13) was born in Nanjing, China, in
mation simulation,” IEEE Trans. Dielectr. Electr. Insul., vol. 22, no. 1, pp. 1989. He received the B.Sc. degree in electrical
564-570, May. 2014. engineering from Hohai University, China, in 2011,
[2] M. Bagheri, M. S. Naderi, T. Blackburn, and B. T. Phung, “Frequency and the M.Sc. degree in the electrical engineering
response analysis and short circuit impedance measurement in detection from the Southeast University, China and the Engi-
of winding deformation within power transformers,” IEEE Electr. Insul neering school of NYU in 2013. He received the Ph.D.
Mag., vol. 29, no. 3, pp. 33-40, 2013. degree from New York University in 2016.
[3] L. M. Burrage, E. F. Veverka, and B. W. McConnell, “Steep front short He is currently a Postdoc Fellow in the Engineer-
duration low voltage impulse performance of distribution transformer,” ing School of NYU. His main interests are power
IEEE Trans. Power Delivery, vol. 2, no. 4, pp. 1152-1156, Oct. 1987. system analysis, micro-grids, and electromagnetic
[4] M. Bagheri, M. S. Naderi, and T. Blackburn, “Advanced transformer field design.
winding deformation diagnosis: moving from off-line to on-line,” IEEE
Trans. Dielectr. Electr. Insul., vol. 19, no. 6, pp. 1860-1870, Dec. 2012
[5] S. A. Ryder, “Diagnosing transformer faults using frequency responding
analysis,” IEEE Electrical Insulation Magazine, 2003, vol. 2, no. 19, pp. Digvijay Deswal (S’16) completed his B. Tech. and
16-22. M. Tech. degrees in Electrical Engineering at the
[6] J. C. Gonzales and E. E. Mombello, “Fault interpretation algorithm using Indian Institute of Technology (IIT) Kharagpur, West
frequency-response analysis of power transformers,” IEEE Trans. Power Bengal, India in 2014. He is currently a PhD candidate
Delivery, vol. 31, no. 3, pp. 1034-1042, Jun. 2016. at New York University School of Engineering. His
[7] M. Bagheri, M. S. Naderi, T. Blackburn, and T. Phung, “FRA vs. short research interests include machine design, power
circuit impedance measurement in detection of mechanical defects within electronics, and analysis of electrical machines.
large power transformer,” 2012 IEEE International Symposium on Elec-
trical Insulation, San Juan, PR., pp. 301-305. Jul. 2012.
[8] V. Behjat, A. Vahedi, A. Setayeshmehr, H. Borsi, and E. Gockenbach,
“Diagnosing shorted turns on the windings of power transformers based
upon online FRA using capacitive and inductive couplings,” IEEE Trans.
Power Del., vol. 26, no. 4, Oct. 2011. Francisco de León (S’86–M’92–SM’02–F’15) re-
[9] T. D. Rybel, A. Singh, J. A. Vandermaar, M. Wang, J. R. Marti, and K. D. ceived the B.Sc. and the M.Sc. (Hons.) degrees in
Srivastava, “Apparatus for online power transformer winding monitoring electrical engineering from the National Polytechnic
using bushing tap injection,” IEEE Trans. Power Del., vol. 24, no. 3, pp. Institute, Mexico City, Mexico, in 1983 and 1986,
996-1003, Jul. 2009. respectively, and the Ph.D. degree in electrical engi-
[10] A. Abu-Siada and S. Islam, “A novel online technique to detect power neering from the University of Toronto, Toronto, ON,
transformer winding faults,” IEEE Trans. Power Del., vol. 27, no. 2, pp. Canada, in 1992.
849-857, Apr. 2013. He has held several academic positions in Mexico
[11] A. Masoum, N. Hashemnia, A. A. Siada, M. Masoum, and S. Islam, and has worked for the Canadian electric industry.
“Online transformer internal fault detection based on instantaneous Currently, he is an Associate Professor with the De-
voltage and current measurements considering impact of harmonics,” partment of Electrical and Computer Engineering at New York University. His
Accept for publishing by IEEE Trans. Power Del., available online. research interests include the analysis of power phenomena under
[12] T. Hong and F. de Leόn, “Lissajous curve methods for the identification non-sinusoidal conditions, the transient and steady state analyses of power
of nonlinear circuits: calculation of a physical consistent reactive power,” systems, the thermal rating of cables and transformers, and the calculation of
IEEE Trans. Circuits and Syst. I: Regular Papers, vol. 62, no. 12, pp. electromagnetic fields applied to machine design and modeling.
2874-2885, Dec. 2015 Prof. de León is an Editor of the IEEE Transactions on Power Delivery and
[13] C. R. Vogel, Computational Methods for Inverse Problems, 2002, SIAM. the IEEE Power Engineering Letters.
0885-8977 (c) 2016 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.