Airfinity™

Packaged Rooftops

Models
IH – Reversible
IC – Cooling-only
40-135 kW

RT-PRC082A-GB
Table of Contents
Technical Data
Introduction........................................................................................................ 4

Unit model number short description.............................................................. 5


FWD 08 12 20 30 45
Power supply (V/Ph/Hz) 230/1/50
Capacities
Features and benefits.........................................................................................
Cooling capacity on water (1)
(kW) 5,2 8,3 15 18,8 6
30,1
Heating capacity on water (2) (kW) 6,3 11,9 18,9 20,9 38,2
Fan motor (type) 2 x direct drive centrifugal
Fan power input (3) (kW) 0,23 0,46 0,65 1,04 1,51
Options and accessories....................................................................................
Current amps (3) 1,1 (A) 2,2 9
5,5 3,1 4,7
Start-up amps (A) 3,2 5,5 9,3 14,1 16,5
Air flow
minimum (m3/h) 490 980 1400 1800 2700
Heat recovery solutions...................................................................................
nominal (m /h) 820 3
1650 2300 3000 13
4500
maximum (m3/h) 980 1970 2600 3600 5400
Main coil
Water entering/leaving connections (type) ISO R7 rotating female
Airfinity Solar....................................................................................................
(Dia) 3/4" 3/4" 1 1/2" 1 1/2" 115
1/2"
Electric heater (accessory for blower only)
Electric power supply (V/Ph/Hz) 230/1/50 230/1/50 or 400/3/50 400/3/50 400/3/50 400/3/50
Heating capacity (kW) 2/4 8 10 12 12
Product configuration...................................................................................... 17
Hot water coil (accessory for blower only)
Heating capacity (4) (kW) 6,3 12 17,4 22,4 34,5
G2 filter (filter box accessory)
Quantity 2 2 2 2 2
Operating map..................................................................................................
Dimensions ( LxWxth) (mm) 386x221x8 486x271x8 586x321x8 586*421*8 21
586*621*8
G4 filter (filter box accessory)
Quantity - 2 2 2 2
Dimensions ( LxWxth) (mm) - 486x264x48 586x314x48 586*414*48 586*614*48
General data...................................................................................................... 22
Condensate pump (accessory) (type) Centrifugal
Water flow - lift height (l/h - mm) 24 - 500
Not available for FWD30 and FWD45
Sound level (L/M/H speed)
Dimensions and weights.................................................................................
Sound pressure level (5)
(dB(A)) 36/40/43 38/41/44 46/50/53 47/52/57 24
47/52/58
Sound power level (5) (dB(A)) 46/50/53 48/51/54 56/60/63 57/62/67 57/62/68
Unit dimensions
Width x Depth (mm) 890 x 600 1090 x 710 1290 x 820 1290 x 970 1290 x 1090
Acoustic data....................................................................................................
Height (mm) 250 300 350 450 26
650
Shipped unit dimensions
Width x Depth (mm) 933 x 644 1133 x 754 1333 x 864 1333 x 1008 1333*1133
Height (mm) 260 310 360 460 660
Weight (kg) 32 46 61 76 118
Colour galvanised steel
Recommended fuse size
Unit alone (aM/gI) (A) 8/16 8/16 8/16 8/25 8/25
Unit with electric heater (gI) (A) 16 (2kW),25 (4kW) 40 (230V),3*16 (400V) 3*20 3*25 3*25

(1) Conditions: Water entering/leaving temperature: 7/12 °C, Air inlet temperature 27/19°C DB/WB - Nominal air flow
(2) Conditions: Water entering/leaving temperature: 50/45 °C, Air inlet temperature 20°C DB - Nominal air flow
(3) At high speed with nominal air flow.
(4) Water entering/leaving temperature 90/70 °C, air inlet temperature 20 °C DB, Nominal air flow.
(5) A rectangular glass wool duct 1m50 long is placed on the blower.The measurement is taken in the room containing the blower unit.

Heat exchanger operating limits:


FWD:
*water temperature: max 100° C
*absolute service pressure: min 1 bar/max 11 bars

Accessories - Hot water coil:


*water temperature: min. +2° C/max. 100° C
*absolute service pressure: min 1 bar/max 11 bars

4
2 © 2017 Trane UNT-PRC002-GB
RT-PRC082A-GB
Sound power levels
Discharge

Measurement conditions:
Measurements taken in a room adjacent to the room containing the FWD, at the outlet of the rectangular duct (1.5 m
long) fixed to its discharge opening.

Fan Power level in dB(A), per Hz frequency band Overall power


Unit speed 125 250 500 1000 2000 4000 8000 dB(A)
1 55 50 42 37 37 31 30 46
FWD 08 2 57 54 47 40 30 38 40 50
3 58 57 50 42 32 40 43 53
1 57 51 45 42 34 33 28 48
FWD 10 2 58 54 48 45 38 39 35 51
3 60 58 50 48 40 42 39 54
1 57 51 45 42 34 33 28 48
FWD 12 2 58 54 48 45 38 39 35 51
3 60 58 50 48 40 42 39 54
1 56 62 50 48 39 38 36 56
FWD 14 2 61 66 55 53 47 46 45 60
3 63 69 58 56 50 50 49 63
1 57 63 51 49 40 39 37 57
FWD 20 2 61 66 55 53 47 46 45 60
3 63 69 58 56 50 50 49 63

Intake

Measurement conditions:
Measurements taken at the horizontal air intake.

Fan Power level in dB(A), per Hz frequency band Overall power


Unit speed 125 250 500 1000 2000 4000 8000 dB(A)
1 56 55 55 53 46 45 42 57
FWD 08 2 63 62 60 60 53 53 53 64
3 66 65 63 62 56 55 57 67
1 62 58 55 58 51 48 44 61
FWD 10 2 66 63 60 62 56 55 52 66
3 70 67 63 65 59 59 57 69
1 62 58 55 58 51 48 44 61
FWD 12 2 66 63 60 62 56 55 52 66
3 70 67 63 65 59 59 57 69
1 66 65 65 65 57 50 46 68
FWD 14 2 73 72 69 71 64 59 57 74
3 78 76 73 75 69 64 63 78
1 68 72 64 64 56 52 50 69
FWD 20 2 76 76 68 71 65 61 61 75
3 78 79 71 74 69 66 66 78

UNT-PRC002-GB
RT-PRC082A-GB 131
Introduction
Technical Data
The new Trane Airfinity Rooftop is the result of several years of customer research and Engineering development,
in order to conceive a product which is both ready to face the tough environment of today, and embrace the
challenging future which lies ahead.

Value
FWD throughout the total lifecycle 08 12 20 30 45
Power supply
Trane Airfinity™ Rooftops have been (V/Ph/Hz)
designed having in mind the complete lifecycle of230/1/50 the unit. Our high efficiency
Capacities
units will help you to reduce
Cooling capacity on water (1) your operating
(kW) costs and improve
5,2 your carbon8,3 footprint. The easy plug-and-play
15 18,8 30,1
installation and
Heating capacity onset-up
water (2)will bring down (kW)
your initial investments,
6,3 while the 11,9
smooth operation 18,9 and proven reliability38,2
20,9
will help to minimize your downtime costs.
Fan motor (type) 2 x direct drive centrifugal
Fan power input (3) (kW) 0,23 0,46 0,65 1,04 1,51
Current amps (3) (A) 1,1 2,2 3,1 4,7 5,5
Reduced installation costs
Start-up amps (A) 3,2 5,5 9,3 14,1 16,5
•AirPlug
minimum
flow
and play packaged solution (m3/h) 490 980 1400 1800 2700
•nominal
Lightweight design (m3/h) 820 1650 2300 3000 4500
•maximum
Customizable return and supply air configuration (m3/h) 980 1970 2600 3600 5400
•Main Designed coil for quick replacement: compatible with a wide variety of roofcurbs
Water entering/leaving connections (type) ISO R7 rotating female
• Optimum compact packaging to reduce (Dia)waste on-site 3/4" 3/4" 1 1/2" 1 1/2" 1 1/2"
Electric heater (accessory for blower only)
Reduced operating costs
Electric power supply (V/Ph/Hz) 230/1/50 230/1/50 or 400/3/50 400/3/50 400/3/50 400/3/50
Heating capacity (kW) 2/4 8 10 12 12
•Hot High efficiency R410A scroll compressors
water coil (accessory for blower only) in advanced refrigeration system
•Heating Intelligent capacity fresh
(4) air management and(kW) free cooling 6,3 12 17,4 22,4 34,5
•G2Rfilter eliable operation
(filter with the CH536 Trane controller
box accessory)
•Quantity Electronically Commutated (EC) plug fan with modulating 2
airflow 2 2 2 2
Dimensions ( LxWxth) (mm) 386x221x8 486x271x8 586x321x8 586*421*8 586*621*8
•G4Efilter lectronic expansion
(filter box accessory)valves
•Quantity Heat recovery module for maximum energy savings - 2 2 2 2
Dimensions ( LxWxth) (mm) - 486x264x48 586x314x48 586*414*48 586*614*48
Reduced maintenance costs
Condensate pump (accessory)
Water flow - lift height
(type)
(l/h - mm)
Centrifugal
24 - 500
•Not Doubleavailable refrigeration
for FWD30 andcircuit
FWD45 for enhanced reliability
•Sound EC plug level (L/M/H
fan withspeed)
zero maintenance
Sound pressure level (5) (dB(A)) 36/40/43 38/41/44 46/50/53 47/52/57 47/52/58
•Sound Dynamic defrost cycles and anti-freeze
power level (5)
protection 46/50/53
(dB(A)) 48/51/54 56/60/63 57/62/67 57/62/68
•Unit Easy access to filtration and key components
dimensions
•Width Remote
x Depth unit management with alarm(mm) notifications
890 x 600 1090 x 710 1290 x 820 1290 x 970 1290 x 1090
Height (mm) 250 300 350 450 650
Shipped unit dimensions
Width x Depth (mm) 933 x 644 1133 x 754 1333 x 864 1333 x 1008 1333*1133
Height (mm) 260 310 360 460 660
Weight (kg) 32 46 61 76 118
Colour galvanised steel
Recommended fuse size
Unit alone (aM/gI) (A) 8/16 8/16 8/16 8/25 8/25
Unit with electric heater (gI) (A) 16 (2kW),25 (4kW) 40 (230V),3*16 (400V) 3*20 3*25 3*25

(1) Conditions: Water entering/leaving temperature: 7/12 °C, Air inlet temperature 27/19°C DB/WB - Nominal air flow
(2) Conditions: Water entering/leaving temperature: 50/45 °C, Air inlet temperature 20°C DB - Nominal air flow
(3) At high speed with nominal air flow.
(4) Water entering/leaving temperature 90/70 °C, air inlet temperature 20 °C DB, Nominal air flow.
(5) A rectangular glass wool duct 1m50 long is placed on the blower.The measurement is taken in the room containing the blower unit.

Heat exchanger operating limits:


FWD:
*water temperature: max 100° C
*absolute service pressure: min 1 bar/max 11 bars

Accessories - Hot water coil:


*water temperature: min. +2° C/max. 100° C
*absolute service pressure: min 1 bar/max 11 bars

4 UNT-PRC002-GB
RT-PRC082A-GB
Unit model number short description
E I H 085 S A E A A X D 1
1 2 3 4-6 7 8 9 10 11 12 13 14

Sound
Digit 1power levels location
– Manufacturing
E = France
Discharge
Digit 2 – Range
Measurement
I = Airfinity™conditions:
Measurements taken in a room adjacent to the room containing the FWD, at the outlet of the rectangular duct (1.5 m
long) fixed
Digit 3 –to its discharge
Unit applicationopening.
H = Heat pump (reversible)
Fan Power level in dB(A), per Hz frequency band Overall power
UnitC = Cooling-only speed 125 250 500 1000 2000 4000 8000 dB(A)
1 55 50 42 37 37 31 30 46
FWD 08 2 57 54 47 40 30 38 40 50
Digit 4,5,6 – Unit size
3 58 57 50 42 32 40 43 53
Net heating capacity 1 in kW 57 51 45 42 34 33 28 48
FWD 10 2 58 54 48 45 38 39 35 51
3 60 58 50 48 40 42 39 54
Digit 7 – Efficiency 1 57 51 45 42 34 33 28 48
FWDS12= Standard efficiency
2 58 54 48 45 38 39 35 51
3 60 58 50 48 40 42 39 54
1 56 62 50 48 39 38 36 56
Digit 8 – Refrigerant
FWD 14 2 61 66 55 53 47 46 45 60
A = R410A 3 63 69 58 56 50 50 49 63
1 57 63 51 49 40 39 37 57
FWDDigit
20 2
9 – Unit voltage 61 66 55 53 47 46 45 60
3 63 69 58 56 50 50 49 63
E = 400 V / 3 Ph / 50 Hz
Intake
Digit 10, 11 – Series
Measurement conditions:
Digit 12 – Auxiliary heat
Measurements taken
G = Staged gas at the horizontal air intake.
burner
M = Modulating gas
Fanburner Power level in dB(A), per Hz frequency band Overall power
UnitH = Hot water coilspeed 125 250 500 1000 2000 4000 8000 dB(A)
1 56 55 55 53 46 45 42 57
FWDE08
= Electric heater 2 63 62 60 60 53 53 53 64
3 66 65 63 62 56 55 57 67
X = Without 1 62 58 55 58 51 48 44 61
FWD 10 2 66 63 60 62 56 55 52 66
Digit 13 – Gas type3 70 67 63 65 59 59 57 69
G = Propane gas 21
FWD 12
62
66
58
63
55
60
58
62
51
56
48
55
44
52
61
66
M = Natural gas 3 70 67 63 65 59 59 57 69
1 66 65 65 65 57 50 46 68
FWDX14= Without 2 73 72 69 71 64 59 57 74
3 78 76 73 75 69 64 63 78
1 68
Digit 14 – Airflow configuration 72 64 64 56 52 50 69
FWD 20 2 76 76 68 71 65 61 61 75
D = Downflow 3 78 79 71 74 69 66 66 78
H = Horizontal flow

See the Options & Accessories section for a more exhaustive list of options and accessories available.

UNT-PRC002-GB
RT-PRC082A-GB 151
Features and benefits
Technical Data
AIRFINITY is a packaged plug and play solution, and Quality and reliability
an ideal all-in-one solution for retail applications. These
All of Airfinity’s designs were rigorously rain tested at
units have been designed to be installed on the roof,
the factory to ensure water integrity.
but thanks to its versatility and flexibility, can also be
installed on the ground. We perform a 100% coil leak test at the factory.
FWD 08 12 20 30 45
Power supply
The evaporator and condenser coils are leak and
Because Trane cares about delivering (V/Ph/Hz)
value, Airfinity 230/1/50
Capacities pressure tested at 5.0 MPa.
units are equipped with many standard(kW)
Cooling capacity on water (1)
features that 5,2
bring Every unit and8,3its options receive 15
a unit run18,8
test before30,1
Heatingenergy
capacitysavings and improve comfort
on water (2) (kW) through tight 6,3 11,9 18,9 20,9 38,2
temperature
Fan motor regulation and high indoor air quality.
(type) leaving the production line to make sure
2 x direct drive centrifugal it lives up to
Fan power input (3) (kW) 0,23 Trane requirements.
0,46 0,65 1,04 1,51
Current amps (3) (A) 1,1 2,2 3,1 4,7 5,5
Casing
Start-up amps (A) 3,2 5,5 9,3 14,1 16,5
Air flow
The indoor section is provided with double skin panels
Indoor Air Quality
minimum (m3/h) 490 The indoor air980 section is fully1400 insulated with 1800a double2700
as standard, with 25 mm thick glass wool
nominal (m3/h)insulation. The
820 1650 2300 3000 4500
unit casing is constructed of zinc coated,
maximum heavy-gauge,
(m3/h) 980 wall panel and 1970glasswool insulation
2600 with 253600 mm 5400
Main coil
galvanized steel, painted with a polyester white RAL thickness and density according to norm DIN EN 1602.
Water entering/leaving connections
9002 powder paint. All seams have been (type)
tightly sealed The insulation is completely self-maintaining.
ISO R7 rotating female Panels in
(Dia) 3/4" 3/4" 1 1/2" 1 1/2" 1 1/2"
to prevent
Electric heater water leakages
(accessory dueonly)
for blower to rain and snow. The the indoor section are fire-resistant.
modular cabinet
Electric power supplyconstruction allows easy
(V/Ph/Hz)access for230/1/50 Each unit is equipped
230/1/50 or 400/3/50with 400/3/50
two filter rails400/3/50
upstream 400/3/50
of
Heating capacityon both sides of the unit. (kW)
maintenance 2/4 the indoor coil,8 with G4 filters10with M1 fire 12 classification 12
Hot water coil (accessory for blower only)
Airfinity units (4)
Heating capacity are provided from the factory(kW) with 6,3 provided as standard.
12 Additional
17,4 F5 (100mm), 22,4 F7 34,5
G2 filter (filter
horizontal orbox accessory) configuration. To maximize
downflow (100 mm) and F9 (100mm) filters can be provided as
Quantity 2 2
optional. All filters are certified 2 by Eurovent. 2 2
flexibility
Dimensionson-site,
( LxWxth)it is possible to convert (mm) from 386x221x8 486x271x8 586x321x8 586*421*8 586*621*8
downflow tobox
G4 filter (filter horizontal
accessory) flow on-site by ordering a simple Airfinity rooftops are fitted with EC plugs fans as
conversion
Quantity kit. - standard to ensure 2 that no rubber 2 dust particles
2 2
Dimensions ( LxWxth) (mm) - 486x264x48 586x314x48 586*414*48 586*614*48
For different supply/return configurations, (typically associated to belt fans) will be carried into the
Condensate pump (accessory) (type)a multi- Centrifugal
directional
Water flow - liftroofcurb
height is available (see (l/h
Options).
- mm) air stream. 24 - 500
Not available for FWD30 and FWD45 Our drain pans are made of galvanized steel and powder-
Sound level (L/M/H speed)
Advanced refrigeration circuits
Sound pressure level (5) (dB(A)) 36/40/43 painted to prevent
38/41/44 corrosion. Moreover, 47/52/57
46/50/53 they are sloped 47/52/58
Sound powerfeatures
AIRFINITY level (5) high efficiency Scroll
(dB(A))
compressors 46/50/53 to prevent water
48/51/54stagnation56/60/63
that could lead to corrosion
57/62/67 57/62/68
Unit dimensions
units. and microorganism life such as mold and fungi.
Width The
x Depthdual compressor models are(mm) outstanding890 x 600 1090 x 710 1290 x 820 1290 x 970 1290 x 1090
for humidity control, light load cooling(mm)
Height and heating 250 300 350 450 650
conditions, and system back-up applications. The Trane
Shipped unit dimensions Ventilation
Width x Depth (mm) 933 x 644 1133 x 754 1333 x 864 1333 x 1008 1333*1133
Airfinity
Height
rooftop has among the best EER (mm)
and COP in 260
For a typical retail
310
application, 360
your rooftop 460
unit will 660
its class. All performances are Eurovent(kg)
Weight certified which32 run in part load 46 more than 95% 61 of the time.76 That’s why118
provides
Colour the assurance of accurate performance and Trane chose the EC pluggalvanisedfan, provided
steel as a standard
Recommended
common fuse size criteria
comparison on all AIRFINITY units. Thanks to the variable speed
Unit alone (aM/gI) (A) 8/16 8/16 8/16 8/25 8/25
The
Unit design hasheater
with electric been(gI)
optimized to minimize(A) pipe16 (2kW),25 (4kW)technology, the rooftop
40 (230V),3*16 (400V) is quieter,
3*20 more efficient3*25 and 3*25
length and improve serviceability. The heat exchanger more reliable compared to other solutions.
(1) Conditions: Water entering/leaving temperature: 7/12 °C, Air inlet temperature 27/19°C DB/WB - Nominal air flow
is(2)manufactured using aluminized
Conditions: Water entering/leaving temperature:steel with
50/45 °C, copper
Air inlet With
temperature 20°C DB the air
- Nominal ECflow
plug fan, you can also maximize comfort in
(3) At high speed with nominal air flow.
tubes for maximum durability. your building
(4) Water entering/leaving temperature 90/70 °C, air inlet temperature 20 °C DB, Nominal air flow.
and improve the indoor air quality:
Prevent
(5) A rectangular glass wool duct 1m50 long is placed on the blower.The measurement is•taken cold
in the room shower
containing the effect
blower unit.
Figure 1 – IH085 model
Heat exchanger operating limits: •  revent air stratification when using auxiliary heating
P
FWD: • Avoid rubber dust typically due to belt wearing
*water temperature: max 100° C
*absolute service pressure: min 1 bar/max 11 bars • L imited vibrations
• Reduced starting amps (suitable for textile ducts)
Accessories - Hot water coil:
*water temperature: min. +2° C/max. 100° C • Lower weight and lower installation cost
*absolute service pressure: min 1 bar/max 11 bars

4
6 UNT-PRC002-GB
RT-PRC082A-GB
Features and benefits

CH536 Trane controller Advanced heating management


The Trane CH536 controller software has been In the case of heat pump and dual fuel units, heating
completely designed by Trane engineers, leverage many priority is given by default to the most energy efficient
years of expertise in comfort cooling applications. It mode (thermodynamic). Auxiliary heat modes (electric
Sound
providespower levels
unit control for heating, cooling and ventilating heater, hot water coil, gas burner) are activated when an
utilizing input from sensors that measure outdoor and additional need for heating is required.
indoor temperature.
Discharge Thanks to the CH536 controller, the user can customize
The CH536 controller improves quality and reliability the priority between different heating mode based on
through theconditions:
Measurement use of time-tested controls and logic: local atmospheric conditions and building needs.
Measurements taken in a room adjacent to the
• Prevents the unit from short cycling, considerably room containing the FWD, at the outlet of the rectangular duct (1.5 m
long) improving
fixed to itscompressor
discharge opening.
life. Electronic Expansion Valves
• Ensures that the compressor will run for a specific Airfinity™ utilizes electronic expansion valves (EEV) as
amount of time Fanwhich allows oil to return Power
forlevel in dB(A), per Hz frequency band
better standard on all2000
models. Working together Overall power
with the CH536
Unit speed 125 250 500 1000 4000 8000 dB(A)
lubrication, enhancing
1 the reliability
55 of the
50 compressor.
42 controller,
37 the EEV
37 allow to31optimize the 30 performances
46
FWD• 08Reduces the number 2 of components
57 required
54 to 47 in both
40 cooling30 and heating 38mode while 40 providing 50
operate the unit, 3thereby reducing
58 57
possibilities for 50 42 and accurate
reliable 32 40
operation 43
in all conditions, 53
no
1 57 51 45 42 34 33 28 48
FWD 10
component failure. 2 58 54 48 matter45 what time 38 of the year.
39 Furthermore,
35 unlike51
• Features expanded 3 diagnostic 60 capabilities
58 when 50 conventional
48 expansion
40 valves,
42 EEV ensures
39 smooth
54 and
utilized with Trane’s
1 Tracer™57 Systems. 51 45 42 control 34
precise 33
at low capacities, 28
improving 48
part load
FWD• 12Softens electrical2‘’spikes’’ by 58staging on 54fans, 48 45 38 39 35 51
3 60 58 50
performances.
48 40 42 39 54
compressors and1 heaters. 56 62 50 48 39 38 36 56
FWD• 14Includes internal 2log memory 61 to record66 unit operating55 Fresh 53 air management
47 46 and free 45 cooling 60
3
trends (e.g. temperatures 63
before alarm 69 occurrence). 58 56 50 50 49 63
1 57 63 51 Every 49 Airfinity™ 40unit is provided
39 with 37
an economizer 57
FWDThe
20 Intelligent Fallback2 or Adaptive
61 Control66 is a benefit 55 as standard.
53 The 47economizer 46 increases45energy 60
to the building occupant.
3 If a component
63 goes astray,58
69 56
savings 50
by enabling 50 cooling mode
the free 49 every 63
time
the unit will continue to operate at predetermined outdoor conditions are favorable. This way, seasonal
Intake
temperature set points. efficiency can be maximized by reducing the need for
Figure 2 – Trane CH536 controller thermodynamic cooling in mid-season.
Measurement conditions:
Measurements taken at the horizontal air intake. The economizer consists of:
• A motorized damper with separate fresh air and return
Fan Power level in dB(A), per Hzair sections.
frequency band Overall power
Unit speed 125 250 500 • A1000 2000 with a protection
fresh air hood 4000 8000
grille. dB(A)
1 56 55 55 53 46 45 42 57
FWD 08 2 63 62 60 • T
 emperature
60 sensors
53 for free
53 cooling 53 operation 64
3 66 65 63 (humidity
62 sensors
56 provided
55 with enthalpy
57 free cooling
67
1 62 58 55 option).
58 51 48 44 61
FWD 10 2 66 63 60 62 56 55 52 66
3 70 67 63 65 59 59 57 69
1 62 58 55 58 51 48 44 61
FWD 12 2 66 63 60 62 56 55 52 66
3 70 67 63 65 59 59 57 69
1 66 65 65 65 57 50 46 68
FWD 14 2 73 72 69 71 64 59 57 74
3 78 76 73 75 69 64 63 78
1 68 72 64 64 56 52 50 69
Alternate defrost
FWD 20 2
3
76
78
76
79
68
71
71
74
65
69
61
66
61
66
75
78
Alternate defrost is provided as a standard feature on all
Airfinity rooftop heat pump models. The intelligence is
embedded into the unit controller and limits the number
and the duration of the defrost cycles in cold conditions
in order to improve reliability and maximize COP.

UNT-PRC002-GB
RT-PRC082A-GB 171
Features and benefits
Technical Data
Fresh air percentage can vary from 0 to 100% of nominal Transport and handling
airflow. The mechanical opening of the damper is
To facilitate handling of the unit and minimize waste on-
managed by the actuator which is adjusted by the Trane
site, Airfinity units are provided with lifting lugs located
CH536 controller. When the unit is in free cooling mode,
in the base frame of the unit and compact wooden
the
FWDdamper will be automatically activated. 08 blocks suitable12for forklifting. 20 30 45
Power supply (V/Ph/Hz) 230/1/50
Figure 3 – Economizer section in the Airfinity unit,
Capacities For handling instructions, please consult the Operation
shown with barometric
Cooling capacity on water (1) relief damper (kW) 5,2 and Maintenance
8,3 Manual. 15 18,8 30,1
Heating capacity on water (2) (kW) 6,3 11,9 18,9 20,9 38,2
Fan motor (type) 2 x direct drive centrifugal
Fan power input (3) (kW) 0,23 0,46 0,65 1,04 1,51
Current amps (3) (A) 1,1 2,2 3,1 4,7 5,5
Start-up amps (A) 3,2 5,5 9,3 14,1 16,5
Air flow
minimum (m3/h) 490 980 1400 1800 2700
nominal (m3/h) 820 1650 2300 3000 4500
maximum (m3/h) 980 1970 2600 3600 5400
Main coil
Water entering/leaving connections (type) ISO R7 rotating female
(Dia) 3/4" 3/4" 1 1/2" 1 1/2" 1 1/2"
Electric heater (accessory for blower only)
Electric power supply (V/Ph/Hz) 230/1/50 230/1/50 or 400/3/50 400/3/50 400/3/50 400/3/50
Heating capacity (kW) 2/4 8 10 12 12
Hot water coil (accessory for blower only)
Heating capacity (4) (kW) 6,3 12 17,4 22,4 34,5
G2 filter (filter box accessory)
Quantity 2 2 2 2 2
Dimensions ( LxWxth) (mm) 386x221x8 486x271x8 586x321x8 586*421*8 586*621*8
G4 filter (filter box accessory)
Quantity - 2 2 2 2
Dimensions ( LxWxth) (mm) - 486x264x48 586x314x48 586*414*48 586*614*48
Condensate pump (accessory) (type) Centrifugal
Water flow - lift height (l/h - mm) 24 - 500
Not available for FWD30 and FWD45
Sound level (L/M/H speed)
Sound pressure level (5) (dB(A)) 36/40/43 38/41/44 46/50/53 47/52/57 47/52/58
Sound power level (5) (dB(A)) 46/50/53 48/51/54 56/60/63 57/62/67 57/62/68
Unit dimensions
Width x Depth (mm) 890 x 600 1090 x 710 1290 x 820 1290 x 970 1290 x 1090
Height (mm) 250 300 350 450 650
Serviceability
Shipped unit dimensions
Width x Depth (mm) 933 x 644 1133 x 754 1333 x 864 1333 x 1008 1333*1133
The Airfinity design uses up to 40% fewer
Height (mm)parts than 260 310 360 460 660
legacy
Weight units. Since it is simpler in design, (kg)it is easier 32 46 61 76 118
to diagnose. Moreover, thanks to its consistent and
Colour galvanised steel
Recommended fuse size
modular design, no matter which Airfinity
Unit alone (aM/gI) (A)
model you 8/16 8/16 8/16 8/25 8/25
choose, the components
Unit with electric heater (gI) are placed in the(A) same16 location.
(2kW),25 (4kW) 40 (230V),3*16 (400V) 3*20 3*25 3*25
Rail systems have been implemented inside the cabinet
(1) Conditions: Water entering/leaving temperature: 7/12 °C, Air inlet temperature 27/19°C DB/WB - Nominal air flow
in
(2) order to Water
Conditions: facilitate accesstemperature:
entering/leaving to key components
50/45 °C, Air inlet such as 20°C DB - Nominal air flow
temperature
(3) At high speed with nominal air flow.
the supply fan, auxiliary heater and filters.
(4) Water entering/leaving temperature 90/70 °C, air inlet temperature 20 °C DB, Nominal air flow.
(5) A rectangular glass wool duct 1m50 long is placed on the blower.The measurement is taken in the room containing the blower unit.
Figure 4 – Easy access via rail system to key components
on
Heatan Airfinity
exchanger unitlimits:
operating
FWD:
*water temperature: max 100° C
*absolute service pressure: min 1 bar/max 11 bars

Accessories - Hot water coil:


*water temperature: min. +2° C/max. 100° C
*absolute service pressure: min 1 bar/max 11 bars

4
8 UNT-PRC002-GB
RT-PRC082A-GB
Options and accessories
The Airfinity product line comes with a wide range of Electric heaters
options and accessories to ensure all the flexibility and
Electric heaters are fitted in the heating section, under
versatility you need.
the supply fan discharge. The two-stage heaters are
provided with two types of overheat thermostats:
Auxiliary
Sound powerheat
levelsoptions • A utomatic reset thermostats which stop the electric
heater when the air temperature rises to 65°C.
Hot water coil
Discharge Automatic reset at 32°C.
The hot water coil can be fitted when additional heat • Manual reset thermostat which stops the unit when the
Measurement
is required conditions:
and hot water is available from an external air temperature rises to 128°C.
Measurements taken in a room adjacent to the room containing
device (e.g. boiler). An additional factory-mounted coil is FigureFWD,
the at the outlet
6 – Electric heateroffitted
the rectangular duct (1.5 m
onto the unit
long) fixed after
located to itsthe
discharge opening.
indoor coil and offers fully modulating
heating control by the use of a 3-way valve. The control
Fan
is managed by measuring Power level
the zone temperature andin dB(A), per Hz frequency band Overall power
Unit speed 125 250 500 1000 2000 4000 8000 dB(A)
adapting the supply1 air temperature.
55 50 42 37 37 31 30 46
FWDTo
08 ensure 2
proper operation, 57 pump circulating
the 54 hot47 40 30 38 40 50
3 58 57 50 42 32 40 43 53
water should be permanently
1
working
57
to avoid
51
water45 42 34 33 28 48
FWDfreezing
10 in the coil.2Otherwise,58it is recommended
54 to 48
use 45 38 39 35 51
ethylene glycol. Refer
3 to Installation
60 and Operation
58 for
50 48 40 42 39 54
more details. 1 57 51 45 42 34 33 28 48
FWD 12 2 58 54 48 45 38 39 35 51
For reversible units3 (IH models),
60 priority is
58given by 50 48 40 42 39 54
default to heat pump1 mode. Priority
56 can be62 altered on-
50 48 39 38 36 56
FWD 14 2 61 66 55 53 47 46 45 60
site. 3 63 69 58 56 50 50 49 63
1 57 63 51 49 40 39 37 57
Figure 5 – Hot water
FWD 20 2
coil located
61
inside the
66
unit 55 53 47 46 45 60
3 63 69 58 56 50 50 49 63

Intake

Measurement conditions: Gas burner


Measurements taken at the horizontal air intake. Both IH and IC models can be equipped with a gas
burner.
Fan Power level in dB(A), per Hz frequency band Overall power
Unit speed 125 250 500
The1000
standard gas
2000
burner module
4000
offers
8000
2 stages of
dB(A)
1 56 55 55 control
53 in order46to improve45zone comfort 42 by avoiding
57
FWD 08 2 63 62 60 large60 deviations53in supply air
53 temperature.
53 64
3 66 65 63 62 56 55 57 67
1 62 58 55 For 58
applications51that require
48 a larger modulating
44 range,
61
FWD 10 2 66 63 60 modulating
62 gas56burners are
55 available.52 66
3 70 67 63 65 59 59 57 69
1 62 58 55 58 51 48 44 61
FWD 12 2 66 63 60 62 56 55 52 66
3 70 67 63 65 59 59 57 69
1 66 65 65 65 57 50 46 68
FWD 14 2 73 72 69 71 64 59 57 74
3 78 76 73 75 69 64 63 78
1 68 72 64 64 56 52 50 69
FWD 20 2 76 76 68 71 65 61 61 75
3 78 79 71 74 69 66 66 78

UNT-PRC002-GB
RT-PRC082A-GB 191
Options and accessories
Technical Data
Indoor Air Quality options Control options
Filtration levels User interface (THS04)
Each
FWD
unit is equipped with two filter rails upstream of 08 The THS04 is a12remote wall-mounted
20
user interface
30 45
the indoor
Power supplycoil, with G4 filters provided as standard.
(V/Ph/Hz) intended for the end-user. It230/1/50
includes an incorporated
Additional
Capacities F5 (100mm), F7 (100 mm) and F9 (100mm) temperature sensor which can be used as a room
Coolingcan
filters capacity on water (1)as optional. All filters
be provided (kW) are certified
5,2 8,3
temperature sensor. 15 18,8 30,1
Heating capacity on water (2) (kW) 6,3 11,9 18,9 20,9 38,2
by Eurovent.
Fan motor (type) The intuitive graphical display
2 x direct driveprovides
centrifugalinformation
Fanfilters
All power input (3)
are provided with galvanized (kW) 0,23
metallic frames. 0,46 mode, ventilation
such as operating 0,65 status,1,04 1,51
temperature
Current amps (3) (A) 1,1 2,2 3,1 4,7 5,5
Start-up7amps (A) 3,2 set points and5,5
indoor temperature.
9,3 A user can
14,1 set the16,5
Figure – Air filters
Air flow temperature set point, switch the unit on or off and
minimum (m3/h) 490 adjust the clock.
980 1400 1800 2700
nominal (m3/h) 820 1650 2300 3000 4500
maximum (m3/h) 980 An admin user1970can access advanced
2600 settings
3600 of the 5400
Main coil THS04 via a password. The privileged access to
Water entering/leaving connections (type) adjust more parametersISO R7
androtating
viewfemale
alarms. For more
(Dia) 3/4" 3/4" 1 1/2" 1 1/2" 1 1/2"
Electric heater (accessory for blower only) information, refer to the THS04 User Guide.
Electric power supply (V/Ph/Hz) 230/1/50 230/1/50 or 400/3/50 400/3/50 400/3/50 400/3/50
Heating capacity (kW) 2/4 8 10 12 12
Hot water coil (accessory for blower only)
Heating capacity (4) (kW) 6,3 12 17,4 22,4 34,5
G2 filter (filter box accessory)
Quantity 2 2 2 2 2
Dimensions ( LxWxth) (mm) 386x221x8 486x271x8 586x321x8 586*421*8 586*621*8
G4 filter (filter box accessory)
Quantity - 2 2 2 2
Dimensions ( LxWxth) (mm) - 486x264x48 586x314x48 586*414*48 586*614*48
Condensate pump (accessory) (type) Centrifugal
Water flow - lift height (l/h - mm) 24 - 500
Not available for FWD30 and FWD45
Sound level (L/M/H speed)
Table
Sound 1pressure
– Filtration
level (5)levels (dB(A)) 36/40/43 38/41/44 46/50/53 47/52/57 47/52/58
Sound power level (5) (dB(A)) 46/50/53 48/51/54 56/60/63 57/62/67 57/62/68
Filter
Unit class
dimensions Thickness Efficiency (1)
Width x Depth (mm) 890 x 600 1090 x 710 1290 x 820 1290 x 970 1290 x 1090
G4
Height 50 mm 90% gravimetric 250
(mm) 300 350 450 650
Shipped
G4+F7 unit dimensions50 mm + 100 mm 58% opacimetric
Width x Depth (mm) 933 x 644 1133 x 754 1333 x 864 1333 x 1008 1333*1133
F5+F7
Height 50 mm + 100 mm 58% opacimetric 260
(mm) 310 360 460 660
Weight
G4+F9 50 mm + 100 mm (kg) opacimetric 32
90% 46 61 76 118
Colour galvanised steel
Recommended
(1) fuse
Initial efficiency size according to EN779:2012
levels
Unit alone (aM/gI) (A) 8/16 8/16 8/16 8/25 8/25
Unit with electric heater (gI) (A) 16 (2kW),25 (4kW) 40 (230V),3*16 (400V) 3*20 3*25 3*25
Dehumidification function
(1) Conditions: Water entering/leaving temperature: 7/12 °C, Air inlet temperature 27/19°C DB/WB - Nominal air flow
When the room
(2) Conditions: temperature
Water entering/leaving reaches
temperature: the
50/45 °C,desired set
Air inlet temperature 20°C DB - Nominal air flow
point butspeed
(3) At high thewith
humidity
nominal airlevel
flow. is above the requirement,
(4) Water entering/leaving temperature 90/70 °C, air inlet temperature 20 °C DB, Nominal air flow.
the
(5) ATrane controller
rectangular glass wool will automatically
duct 1m50 long is placed onsignal the unit
the blower.The to
measurement is taken in the room containing the blower unit.
begin dehumidication of the supply air using an electric
Heat exchanger operating limits:
heater
FWD: fitted into the unit.
*water temperature: max 100° C
This feature
*absolute service is particularly
pressure: interesting
min 1 bar/max 11 bars for retail spaces
which used closed cabinets, in order to prevent
Accessories - Hot water coil:
condensation
*water temperature:onmin.the windows.
+2° C/max. 100° C
*absolute service pressure: min 1 bar/max 11 bars

4
10 UNT-PRC002-GB
RT-PRC082A-GB
Options and accessories

Service interface (PGD) Barometric relief damper


The optional service interface can easily be plugged Typically, the maximum overpressure recommended
to the unit controller using a RJ25 phone cable. The inside a building is 12 to 25 Pa. Excessive overpressure
interface is composed of six different buttons and a can lead to unwanted effects, such as tight doors, air
Sound power
graphical levels
display. This view of plug-and-play service and whistling through windows and doors, etc.
the controller allows building owners and maintenance The barometric relief damper uses gravity to relief
personnel to read and modify all unit parameters such as pressure whenever fresh air is introduced into the
Discharge
unit settings, operating time and number of compressor building. It is recommended when the application
starts, low and
Measurement high pressure reading, and airflow rate of
conditions: demands fixed fresh air rates around 25%.
supply fan. The
Measurements PGD
taken in also allows
a room to read
adjacent to the
the history of the
room containing thereturn
FWD, airat the outletdrop
of the
The pressure is rectangular duct (1.5 m
above the building
last
long) 99 alarms.
fixed to its discharge opening. overpressure allowed by the customer (e.g. 25 Pa),
The service terminal can be provided as loose or wall- the barometric relief dampers will open.
mounted version and Fan is available in multiple
Powerlanguages.
level in dB(A), per Hz frequency band Overall power
Unit speed 125 250 500 The1000
barometric relief damper
2000 4000 is installed
8000 under the
dB(A)
Figure 8 – PGD Service 1 Terminal
55 50 42 fresh37 air section37and provided
31 as standard
30 with the46
FWD 08 2 57 54 47 40
economizer for30 38
downflow configuration. 40 One or two50
3 58 57 50 42 32 40 43 53
1 57 51 45 dampers
42 are provided,
34 dependent
33 on 28
the size of the
48 unit.
FWD 10 2 58 54 48 45 38 39 35 51
3 60 58 50
Figure
48
9 – Barometric
40
relief42damper 39 54
1 57 51 45 42 34 33 28 48
FWD 12 2 58 54 48 45 38 39 35 51
3 60 58 50 48 40 42 39 54
1 56 62 50 48 39 38 36 56
FWD 14 2 61 66 55 53 47 46 45 60
3 63 69 58 56 50 50 49 63
1 57 63 51 49 40 39 37 57
FWD 20 2 61 66 55 53 47 46 45 60
3 63 69 58 56 50 50 49 63

Intake
Building pressurization control
Measurement conditions:
The externaltaken
Measurements staticat
pressure (ESP) ofaira intake.
the horizontal rooftop unit is
defined as the static pressure between inlet and outlet Exhaust fans
of the unit, includingFan all options and accessories and
Power level in dB(A), perMulti-speed exhaust axial fans work togetherOverall
Hz frequency band with power
the
Unitexcluding ductwork. This external
speed 125 static pressure
250 will500
be 1000 2000 4000 8000 dB(A)
barometric relief dampers to provide air pressure relief
used to push the air1 through the 56 supply and 55 the return 55
when
53 46 45 42 57
FWD 08 2 63 62 60 60 high fresh53rates are being
53 used.53
This option64is
ductwork installed 3on site. It can 66 be computed65 summing 63 recommended
62 when there55
56 is a maximum57 of 150 Pa 67
the supply duct pressure
1 drop62with the return
58 pressure 55 58
pressure drop in51 the return48duct. 44 61
FWDdrop.
10 2 66 63 60 62 56 55 52 66
3 70 67 63 The65 exhaust fans59 are fitted59
in the fresh57air section,69before
It is recommended,1 for a basic62unit, that the 58 return 55 the 58
economizer.51They are only48 activated 44 when the61 fresh
FWDductwork
12 pressure 2drop be lower66 than 150 63Pa in order 60 62 56 55 52 66
3 70
air rate exceeds a preset value, and the overpressure
to accommodate operating modes which 67 demand high 63 65
can 65no longer be
59 59 57 69
1 66 65 65 57 compensated
50 by the46barometric68
fresh
FWD 14 air rates, such2 as free cooling.
73 72 69 relief
71 damper. Up64 to 50% of 59the nominal57 airflow can
74 be
In the case that the3return ductwork78 76
pressure drop is73 75
exhausted, 69
depending 64 pressure63drop in the
on the 78return
1 68 72 64 64 56 52 50 69
FWDhigher
20 than 150 Pa,2several exhaust
76 options76 exist in 68 ductwork.
71 65 61 61 75
order to control building
3 pressurization.
78 79 71 74 69 66 66 78

UNT-PRC002-GB
RT-PRC082A-GB 11
Options and accessories
Technical Data
Return roofcurb Roofcurbs
The return roofcurb is recommended when there is
a significant pressure drop in the return duct (up to Adjustable roofcurb
250 Pa). This options allows a tighter control of the return
A roofcurb serves as a connection between30a flat
airflow
FWD and balances it with the supply airflow, especially
08 12 20 45
Power supply (V/Ph/Hz) or sloped roof and the rooftop unit. In addition to
230/1/50
when the supply fan is not enough to overcome both
Capacities supporting the rooftop, it ensures water tightness
supply and return
Cooling capacity static
on water (1) pressure (ESP).(kW) 5,2 8,3 connection of 15the ductwork. 18,8Trane 30,1
and allows easy
Heating
The capacity
return on wateris(2)
roofcurb (kW)unit and has6,3
installed below the 11,9 18,9 20,9 38,2
Fan motor (type) can provide high quality roofcurbs with
2 x direct drive centrifugalup to 6% of
an EC plug fan
Fan power input (3) integrated into the module.
(kW) One or two 0,23 inclination, adjustable
0,46 on-site.0,65 1,04 1,51
plugs
Currentfans
ampsare
(3) included, depending on the (A) unit size. 1,1 2,2 3,1 4,7 5,5
Start-up
The amps is fully powered by the rooftop
module (A) itself. The 3,2 5,5 9,3 14,1 16,5
Air flow Multi-directional roofcurb
roofcurb
minimum
is also equipped with an additional
(m /h)
damper for
490 This option is980
a required when1400an installation
1800 demands2700
3

the exhaust air.


nominal (m /h) 3
820 1650 2300 3000 4500
maximum (m /h) 3
980
horizontal return
1970
and horizontal
2600
supply on3600
the same side.
5400
This roofcurb can be used in either horizontal or It is also necessary when the customer requires a heat
Main coil
downflow applications.
Water entering/leaving connections (type) recovery module withISO horizontal
R7 rotatingflow configuration.
female
(Dia) 3/4" 3/4" 1 1/2" 1 1/2" 1 1/2"
Figure 10 – Airfinity
Electric heater (accessoryunit with only)
for blower return roofcurb Figure 11 – Multi-directional roofcurb
Electric power supply (V/Ph/Hz) 230/1/50 230/1/50 or 400/3/50 400/3/50 400/3/50 400/3/50
Heating capacity (kW) 2/4 8 10 12 12
Hot water coil (accessory for blower only)
Heating capacity (4) (kW) 6,3 12 17,4 22,4 34,5
G2 filter (filter box accessory)
Quantity 2 2 2 2 2
Dimensions ( LxWxth) (mm) 386x221x8 486x271x8 586x321x8 586*421*8 586*621*8
G4 filter (filter box accessory)
Quantity - 2 2 2 2
Dimensions ( LxWxth) (mm) - 486x264x48 586x314x48 586*414*48 586*614*48
Condensate pump (accessory) (type) Centrifugal
Water flow - lift height (l/h - mm) 24 - 500
Not available for FWD30 and FWD45
Sound level (L/M/H speed)
Table
Sound 2pressure
– Building pressurization options
level (5) comparison
(dB(A)) 36/40/43 38/41/44 46/50/53 47/52/57 47/52/58
Sound power level (5) (dB(A)) 46/50/53 48/51/54 56/60/63 57/62/67 57/62/68
Unit dimensions Barometric
Width x Depth Exhaust(mm) Return
890 x 600 1090 x 710 1290 x 820 1290 x 970 1290 x 1090
relief
Height fans(mm) roofcurb 250 300 350 450 650
damper
Shipped unit dimensions
Building
Width air
x Depth (mm) 933 x 644 1133 x 754 1333 x 864 1333 x 1008 1333*1133
Medium Medium High
tightness
Height (mm) 260 310 360 460 660
Weight
Pressure drop (kg) 32 46 61 76 118
Colour
in the return Below 50 Pa Up to 150 Pa Up to 250 Pa galvanised steel
Recommended
ductwork fuse size
Unit alone (aM/gI) (A) 8/16 8/16 8/16 8/25 8/25
Building
Unit with electric heater (gI) (A) 16 (2kW),25 (4kW) 40 (230V),3*16 (400V) 3*20 3*25 3*25
Low Low Medium
pressure control
(1) Conditions: Water entering/leaving temperature: 7/12 °C, Air inlet temperature 27/19°C DB/WB - Nominal air flow
Low totemperature: 50/45 °C, Air inlet temperature 20°C DB - Nominal air flow
(2) Conditions: Water entering/leaving
Fresh air rate High High
(3) At high speed with nominalmedium
air flow.
(4) Water entering/leaving temperature 90/70 °C, air inlet temperature 20 °C DB, Nominal air flow.
Volume
(5) of glass wool duct 1m50 long is placed on the blower.The measurement is taken in the room containing the blower unit.
A rectangular
Low Medium Medium
exhaust air
Heat exchanger operating limits:
FWD: Warehouses, Cinemas,
Typical Small retail,
*water temperature: max 100°large
C retail new air-tight
applications
*absolute service pressure: minspaces gas stations
1 bar/max 11 bars buildings
Accessories - Hot water coil:
*water temperature: min. +2° C/max. 100° C
*absolute service pressure: min 1 bar/max 11 bars

4
12 UNT-PRC002-GB
RT-PRC082A-GB
Heat recovery solutions
To enhance energy savings and reduce operating costs, Thanks to the enthalpy rotary wheel, both sensible and
Airfinity rooftops can be equipped with a packaged and latent heat is transferred from the exhaust air stream to
easy-to-install heat recovery system. All heat recovery the outdoor air stream, which makes this system more
systems for rooftops provided by Trane are designed to energy efficient compared to conventional plate heat
maximize efficiency with little to no impact on footprint exchangers. The module has been fully designed by
Sound power levels
and installation time. Trane and optimized to minimize the overall pressure
Heat recovery systems are ideal for climates in which drop in the system. The rotary wheel is certified by
Discharge Eurovent.
there is a significant difference between outdoor and
indoor air temperature (e.g. winter). Airfinity rooftops fitted with the ERM can still benefit
Measurement conditions:
Trane provides two heat recovery solutions to address from free cooling mode, and high fresh air rates up to
Measurements taken in a room adjacent to the room containing the FWD, at the outlet of the rectangular duct (1.5 m
a wide variety of needs: energy recovery module and 100%.
long) fixed to its discharge opening.
thermodynamic heat recovery. The heat recovery system is recommended for
Fan Power level in dB(A), perapplications with 20% to 40% of fresh air intake.
Hz frequency band When
Overall power
UnitEnergy Recovery speed Module 125 (ERM) 250 500 fresh
1000air requirements
2000 exceed
4000 the airflow
8000 which dB(A)
can
1 55 50 42 37
be managed by37the wheel,31
the bypass30damper will 46
FWDThe
08 Energy Recovery 2 Module 57 is a packaged
54 system that 47 40 30 38 40 50
transfers the energy 3 contained 58in the exhaust
57 air to fresh
50 automatically
42 open
32 to compensate
40 the43excess air 53
intake.
1
air. It is an add-on module that57includes a51heat exchanger
45 42 ERM is equipped
Every 34 33 the necessary
with 28 sensors48 and a
FWD 10 2 58 54 48 45 38 39 35 51
(rotary wheel), exhaust3 fan, G4
60filter and dampers.
58 50
micro-inverter
48
to
40
reduce the
42
rotation speed
39
of the54wheel
The module is fully1powered by 57 the rooftops
51 itself and
45 when
42 the outdoor
34 temperatures
33 is below
28 -2°C, in 48
order to
FWDmanaged
12 2
via the Trane CH536 58 54
unit controller. 48 protect
45 the module
38 against39freezing. 35 51
3 60 58 50 48 40 42 39 54
Figure 12 – Trane Airfinity
1 unit56
fitted with 62
an Energy 50 48 39 38 36 56
FWD 14
Recovery Module 32 61
63
66
69
55
58
53
56
47
50
46
50
45
49
60
63
1 57 63 51 49 40 39 37 57
FWD 20 2 61 66 55 53 47 46 45 60
3 63 69 58 56 50 50 49 63

Intake

Measurement conditions:
Measurements taken at the horizontal air intake.

Fan Power level in dB(A), per Hz frequency band Overall power


Unit speed 125 250 500 1000 2000 4000 8000 dB(A)
1 56 55 55 53 46 45 42 57
FWD 08 2 63 62 60 60 53 53 53 64
3 66 65 63 62 56 55 57 67
1 62 58 55 58 51 48 44 61
FWD 10 2 66 63 60 62 56 55 52 66
Figure 13 – Trane Airfinity
3 Energy
70 Recovery
67 Module 63 65 59 59 57 69
1 62 58 55 58 51 48 44 61
FWD 12 2 66 63 60 62 56 55 52 66
3 70 67 63 65 59 59 57 69
1 66 65 65 65 57 50 46 68
FWD 14 2 73 72 69 71 64 59 57 74
3 78 76 73 75 69 64 63 78
1 68 72 64 64 56 52 50 69
FWD 20 2 76 76 68 71 65 61 61 75
3 78 79 71 74 69 66 66 78

For more information regarding the installation and operation of the ERM, please consult the Installation & Operation
Manual.

UNT-PRC002-GB
RT-PRC082A-GB 11
13
Heat recovery solutions
Technical Data
Thermodynamic Energy Recovery Circuit (ERC)
The Thermodynamic Energy Recovery integrated system is characterized by a dedicated high efficiency refrigeration
circuit which uses the exhaust air to pre-heat or pre-cool the fresh air introduced into the building. By recovering
the heat in the exhaust air, the overall capacity of the machine can be increased by up to 25% in typical working
conditions
FWD without significantly impacting power consumption.
08 Therefore, 12
the overall efficiency
20 of the rooftop
30 unit45
isPower supply
increased.
Capacities
(V/Ph/Hz) 230/1/50

To maximize
Cooling capacitythe efficiency
on water (1) of the unit, especially
(kW) in part
5,2 load conditions, priority
8,3 is always15given to the18,8
energy 30,1
Heating capacity
recovery circuitonover
water the
(2) main unit refrigeration
(kW) circuit6,3
when meeting capacity11,9 requirements.
18,9 20,9 38,2
Fan motor (type) 2 x direct drive centrifugal
Thanks
Fan powertoinput
the (3)
additional refrigeration circuit
(kW) and tighter
0,23control of the exhaust
0,46 air, Trane’s0,65
ERC system 1,04
guarantees 1,51
Current amps
higher (3)
performances (A)
compared to alternative systems1,1which utilize the outdoor
2,2 coil. 3,1 4,7 5,5
Start-up amps (A) 3,2 5,5 9,3 14,1 16,5
Air flow
minimum (m3/h) 490 980 1400 1800 2700
nominal (m3/h) 820 1650 2300 3000 4500
maximum
Table 3 – Energy Recovery Comparison(m /h)
3
980 1970 2600 3600 5400
Main coil
Water entering/leaving connections (type) ERC ISO R7 rotating female
ERM
(Dia) 3/4" 3/4" 1 1/2" 1 1/2" 1 1/2"
Name heater (accessory for blower only)
Electric Energy Recovery Circuit Energy Recovery Module
Electric power supply (V/Ph/Hz) 230/1/50 230/1/50 or 400/3/50 400/3/50 400/3/50 400/3/50
Technology Thermodynamic circuit Enthalpy Rotary Wheel
Heating capacity (kW) 2/4 8 10 12 12
Type
Hot of heat
water recoveryfor blower only)
coil (accessory Active recovery Static recovery
Heating capacity (4) (kW) 6,3 12 17,4 22,4 34,5
Installation
G2 type
filter (filter box accessory) Integrated inside the main unit Add-on module
Quantity
Footprint impact 2 None 2 2 Minimum 2 2
Dimensions ( LxWxth) (mm) 386x221x8 486x271x8 586x321x8 586*421*8 586*621*8
Recommended
G4 filter (filter box fresh air rate*
accessory) Up to 60% 30%
Quantity
Maximum fresh air rate - 100% 2 2 100% 2 2
Dimensions ( LxWxth) (mm) - 486x264x48 586x314x48 586*414*48 586*614*48
Maximum pump
Condensate pressure drop
(accessory) (type) 50 Pa Centrifugal 150 Pa
Water flow - lift height (l/h - mm) 24 - 500
Installation cost Low Low to medium
Not available for FWD30 and FWD45
Sound level (L/M/H
Return on investment speed) Low to medium High
Sound pressure level (5) (dB(A)) 36/40/43 38/41/44 46/50/53 47/52/57 47/52/58
Sound power level (5) (dB(A)) 46/50/53 48/51/54 56/60/63 57/62/67 57/62/68
Unit dimensions
Width x Depth (mm) 890 x 600 1090 x 710 1290 x 820 1290 x 970 1290 x 1090
Height (mm) 250 300 350 450 650
Shipped unit dimensions
Width x Depth (mm) 933 x 644 1133 x 754 1333 x 864 1333 x 1008 1333*1133
Height (mm) 260 310 360 460 660
Weight (kg) 32 46 61 76 118
Colour galvanised steel
Recommended fuse size
Unit alone (aM/gI) (A) 8/16 8/16 8/16 8/25 8/25
Unit with electric heater (gI) (A) 16 (2kW),25 (4kW) 40 (230V),3*16 (400V) 3*20 3*25 3*25

(1) Conditions: Water entering/leaving temperature: 7/12 °C, Air inlet temperature 27/19°C DB/WB - Nominal air flow
(2) Conditions: Water entering/leaving temperature: 50/45 °C, Air inlet temperature 20°C DB - Nominal air flow
(3) At high speed with nominal air flow.
(4) Water entering/leaving temperature 90/70 °C, air inlet temperature 20 °C DB, Nominal air flow.
(5) A rectangular glass wool duct 1m50 long is placed on the blower.The measurement is taken in the room containing the blower unit.

Heat exchanger operating limits:


FWD:
*water temperature: max 100° C
*absolute service pressure: min 1 bar/max 11 bars

Accessories - Hot water coil:


*water temperature: min. +2° C/max. 100° C
*absolute service pressure: min 1 bar/max 11 bars

4
14 UNT-PRC002-GB
RT-PRC082A-GB
Airfinity Solar
Air-conditioning and ventilation can represent up to 80% of your commercial building’s energy consumption.
Ironically, these systems consume valuable peak power at the same time that solar energy is most available.
By installing solar panels to power your HVAC equipment, you can reduce your carbon emissions and peak time
electricity consumption. At the same time you can put unexploited rooftop space to good use while protecting your
operation
Sound powerfrom future
levelselectricity price fluctuations.
Trane has committed to developing a solution that can reduce your operating costs while using sustainable and
clean energy: Airfinity™ Solar. Trane Airfinity™ Rooftops have been specially designed to be solar-ready. That means
Discharge
you can now use clean solar energy to partially or totally power your air-conditioning system while continuing to
benefit from
Measurement the quick and easy installation of a direct expansion system. Our integrated solar rooftop solution offers
conditions:
you an innovative
Measurements and
taken in reliable
a room way of to
adjacent reducing operating
the room costs
containing without
the compromising
FWD, at the outlet of comfort, while drastically
the rectangular duct (1.5 m
reducing the carbon footprint of
long) fixed to its discharge opening. your building.
Airfinity Solar consists of a pre-packaged solution comprising all the elements required to set up your own self-
consumption off-grid
Fan solution. Power level in dB(A), per Hz frequency band Overall power
Unit speed 125 250 500 1000 2000 4000 8000 dB(A)
1 55 50 42 37 37 31 30 46
FWD 08 2 57 54 47 40 30 38 40 50
3 58 57 50 42 32 40 43 53
1 57 51 45 42 34 33 28 48
FWD 10 2 58 54 48 45 38 39 35 51
3 60 58 50 48 40 42 39 54
1 57 51 45 42 34 33 28 48
FWD 12 2 58 54 48 45 38 39 35 51
3 60 58 50 48 40 42 39 Solar ready
Solar ready
54
1 56 62 44 50 48 39 11 38 36 56
FWD 14 2 2 DC 61 66 55 53
PV generation 47 46 45 60
3 55 63 69 58 56 50 50 49 63
1 57 63 51 49 40 39 37 57
FWD 20 2 61 66 55 53 47 46 45 60
3 63 69 58 56 50 50 49 63
Production 22 3 11
Intake 3 Consumption

Measurement conditions: Electrical


cabinet
Measurements taken at the horizontal air intake.
Even when the energy production exceeds the HVAC
consumption required, the surplus of energy can be used to
power the rest of your building (lights, computers, refrigeration
Fan Power level in dB(A), per Hz frequency band
cabinets, etc.) Overall power
Unit speed 125 250 500 1000 2000 4000 8000 dB(A)
1 56 55 55 53 46 45 42 57
FWD 08 2 63 62 60
Exported power 60 Electrical 53 53 53 64
3 66 65 63
Imported power
62 meter
56 55 57 67
1 62 58 55 58 51 48 44 61
FWD 10 2 66 63 60 62 56 55 52 66
1) Airfinity™ rooftop
3 units. 70 67 63 65 59 59 57 69
1 62 58 55 58 51 48 44 61
2)
FWD 12
Silicon photovoltaic
2
panels:
66
The most63widely-used 60
technology
62
to convert 56
solar energy
55
into DC52electrical power.
66
3) Mounting structure:
3 Used70to support67 the PV panels 63 without 65 puncturing59 the building’s
59 roof. The57membranes 69 are
1 66 65 65 65 57 50 46 68
FWD 14
durable but lightweight
2
and
73
serve as72
a wind deflector.
69 71 64 59 57 74
4) High efficiency3 inverter: Converts
78 DC76power supply 73 provided 75 by the PV69 panels into64AC power needed
63 to operate
78
1
the rooftop HVAC unit and68to feed into
72 the utility64grid. 64 56 52 50 69
FWD 20 2 76 76 68 71 65 61 61 75
5) Cables and connectors:
3 Double-insulated
78 79 and UV 71resistant cables
74 suitable 69 for rooftop
66 applications
66 with water
78
resistant IP65 crimped connectors.

UNT-PRC002-GB
RT-PRC082A-GB 11
15
Airfinity Solar
Technical Data
There are two types of pre-packaged kits available:
• P V-S: Solar PV kits with south mounting configuration
• PV-EW: Solar PV kits with east-west mounting configuration
Table 4 – Airfinity solar kit data
FWD 08 12 20 30 45
Airfinity
Power Solar PV-S kits
supply PV05S
(V/Ph/Hz) PV08S PV12S PV15S PV20S PV25S PV35S
230/1/50 PV40S PV50S
Capacities
Nominal PV power (kWp) 6 9 13 16 21 26 37 42 52
Cooling capacity on water (1) (kW) 5,2 8,3 15 18,8 30,1
Heating
Numbercapacity on water (2)
of panels (kW)22 34 6,3 50 62 11,9 82 100 18,9 144 20,9
160 38,2
200
Fan motor (type) 2 x direct drive centrifugal
Power
Fan DC input
power output(3)per panel (Wc) 260
(kW) 260 0,23 260 260 0,46260 260 0,65 260 260
1,04 260
1,51
Current amps (3)
Roof space required (without (A) 1,1 2,2 3,1 4,7 5,5
Start-up (m2) (A)58 90 3,2 132 164 5,5216 264 9,3 380 422 528
shadowsamps and obstructions) 14,1 16,5
Air flow
Number of inverters
minimum (m3/h)1 1 490 1 1 980 1 1 1400 2 2
1800 22700
nominal (m3/h) 820 1650 2300 3000 4500
Expected yearly production based on local 3irradiance factor (1)
maximum (m /h) 980 1970 2600 3600 5400
900coil
Main kWh/m² (Benelux) (kWh) 4800 7400 10900 13500 17850 21750 31350 34800 43500
Water entering/leaving connections (type) ISO R7 rotating female
1400 kWh/m² (Lyon) (kWh) (Dia)7450 115003/4" 16950 21000 27750
3/4" 338501 1/2" 48750
154150
1/2" 67700
1 1/2"
Electric
1600heater
kWh/m² (accessory
(Rome)for blower only)
(kWh) 8500 13150 19350 24000 31700 38700 55700 61900 77400
Electric power supply (V/Ph/Hz) 230/1/50 230/1/50 or 400/3/50 400/3/50 400/3/50 400/3/50
1750 capacity
Heating kWh/m² (Madrid) (kWh) (kW) 9300 144002/4 21150 26250 834700 42300 10 60950 67700
12 84650 12
Hot water coil (accessory for blower only)
Heating capacity (4) (kW) 6,3 12 17,4 22,4 34,5
Airfinity
G2 Solar
filter (filter boxPV-EW kits
accessory) PV05EW PV08EW PV12EW PV16EW PV20EW PV24EW PV30EW PV40EW PV50EW
Quantity 2 2 2 2 2
Nominal PV( power
Dimensions LxWxth) (kWp) (mm) 6 9
386x221x8 13 17 486x271x821 26
586x321x8 31 42
586*421*8 52
586*621*8
G4 filter (filter
Number box accessory)
of panels 22 34 50 64 82 100 120 160 200
Quantity - 2 2 2 2
Power DC output
Dimensions ( LxWxth) per panel (Wc) (mm) 260 260 - 260 260 260
486x264x48 260
586x314x48 260 260 260
586*414*48 586*614*48
Condensate
Roof space pump required (accessory)
(without (type) Centrifugal
Water flowand- liftobstructions)
height (m 2) (l/h - mm)
44 67 99 127 162 19824 - 500 238 317 396
shadows
Not available for FWD30 and FWD45
Inverter
Sound model
level (L/M/H (DC/AC)
speed) 1 1 2 2 2 2 2 2 2
Sound pressure level (5) (dB(A)) 36/40/43 38/41/44 46/50/53 47/52/57 47/52/58
Estimated yearly production based on local irradiance factor (1)
Sound power level (5) (dB(A)) 46/50/53 48/51/54 56/60/63 57/62/67 57/62/68
Unit
900dimensions
kWh/m² (Benelux) (kWh) 4650 7150 10550 13500 17250 21050 25250 33700 42100
Width x Depth (mm) 890 x 600 1090 x 710 1290 x 820 1290 x 970 1290 x 1090
1400 kWh/m² (Lyon)
Height (kWh) (mm) 7200 11150250 16400 20950 300 26850 32750350 39300 52400
450 65500650
Shipped unit dimensions
1600 kWh/m² (Rome) (kWh) 8250 12750 18700 23950 30700 37450 44950 59900 74900
Width x Depth (mm) 933 x 644 1133 x 754 1333 x 864 1333 x 1008 1333*1133
1750 kWh/m² (Madrid)
Height (kWh) (mm) 9000 13900260 20500 26200 310 33600 40950360 49150 65500
460 81900660
Weight (kg) 32 46 61 76 118
Colour galvanised steel
(1) Subject to local
Recommended weather
fuse size conditions and dependent on good design and maintenance practice.
Unit alone (aM/gI) (A) 8/16 8/16 8/16 8/25 8/25
Unit with electric heater (gI) (A) 16 (2kW),25 (4kW) 40 (230V),3*16 (400V) 3*20 3*25 3*25

(1) Conditions: Water entering/leaving temperature: 7/12 °C, Air inlet temperature 27/19°C DB/WB - Nominal air flow
(2) Conditions: Water entering/leaving temperature: 50/45 °C, Air inlet temperature 20°C DB - Nominal air flow
(3) At high speed with nominal air flow.
(4) Water entering/leaving temperature 90/70 °C, air inlet temperature 20 °C DB, Nominal air flow.
(5) A rectangular glass wool duct 1m50 long is placed on the blower.The measurement is taken in the room containing the blower unit.

Heat exchanger operating limits:


FWD:
*water temperature: max 100° C
*absolute service pressure: min 1 bar/max 11 bars

Accessories - Hot water coil:


*water temperature: min. +2° C/max. 100° C
*absolute service pressure: min 1 bar/max 11 bars

4
16 UNT-PRC002-GB
RT-PRC082A-GB
Product configuration
Basic airflow configurations
Downflow (Digit 14=D): Horizontal flow (Digit 14=H):

Sound power levels


Discharge

Measurement conditions:
Measurements taken in a room adjacent to the room containing the FWD, at the outlet of the rectangular duct (1.5 m
long) fixed to its discharge opening.

Fan Power level in dB(A), per Hz frequency band Overall power


Unit speed 125 250 500 1000 2000 4000 8000 dB(A)
1 55 50 42 37 37 31 30 46
FWD 08 2 57 54 47 40 30 38 40 50
3 58 57 50 42 32 40 43 53
1 57 51 45 42 34 33 28 48
FWD 10 2 58 54 48 45 38 39 35 51
3 60 58 50 48 40 42 39 54
1 57 51 45 42 34 33 28 48
FWDCustomizable
12 2 / supply
return 58
flow: 54 48 45 38 39 35 51
3 60 58 50 48 40 42 39 54
1 56 62 50 48 39 38 36 56
FWD 14 2 61 66 55 53 47 46 45 60
3 63 69 58 56 50 50 49 63
1 57 63 51 49 40 39 37 57
FWD 20 2 61 66 55 53 47 46 45 60
3 63 69 58 56 50 50 49 63

Intake

Measurement conditions:
Measurements taken at the horizontal air intake.

Fan Power level in dB(A), per Hz frequency band Overall power


Unit speed 125 250 500 1000 2000 4000 8000 dB(A)
1 56 55 55 53 46 45 42 57
FWD 08 2 63 62 60 60 53 53 53 64
3 66 65 63 62 56 55 57 67
1 62 58 55 58 51 48 44 61
FWD 10 2 66 63 60 62 56 55 52 66
Key digit descriptions
3
1
70
62
67
58
63
55
65
58
59
51
59
48
57
44
69
61
FWD 12 2 66 63 60 62 56 55 52 66
Digit 14 - Airflow configuration
3 70 67 63 65 59 59 57 69
D = Down Flow 1 66 65 65 65 57 50 46 68
FWD 14
H = Horizontal Flow32 73
78
72
76
69
73
71
75
64
69
59
64
57
63
74
78
1 68 72 64 64 56 52 50 69
FWDDigit
20 18 - Heat Recovery
2 Module76 76 68 71 65 61 61 75
X = Without 3 78 79 71 74 69 66 66 78
R = Configured for Rotary Wheel
T = Thermodynamic circuit

Digit 31 - Building Pressurization Control


X = Without
1 = Barometric relief damper
2 = Exhaust Fan (ESP=70 pa)
3 = Exhaust Fan - High speed (ESP=150 Pa)
4 = Configured for Return roofcurb (ESP=250 Pa)

Digit 32 – Multidirectional roofcurb


X = Without
1 = Configured for multidirectional roofcurb

UNT-PRC002-GB
RT-PRC082A-GB 11
17
Product configuration
Technical Data
Table 5 – Product matrix
Custom return/supply Building pressurization
Unit configuration Energy recovery
configuration control Compatibility
Digit 14 Digit 32 Digit 31 Digit 18
FWD 08 12 ERM 20 30(1) 45
Power supply (V/Ph/Hz) Barometric relief ERC 230/1/50 (1)
Capacities
Without x
Cooling capacity on water (1) (kW) 5,2 8,3 15 18,8 30,1
Heating capacity on water (2) (kW) 6,3 11,9 ERM 18,9 (2)
20,9 38,2
Fan motor (type) Exhaust fan 2ERC
x direct drive centrifugal (2)
Fan power input (3) (kW) 0,23 0,46 0,65 1,04 1,51
Without multi-directional Without x
Current amps (3) (A) 1,1 2,2 3,1 4,7 5,5
Start-up amps roofcurb (A) 3,2 5,5 ERM 9,3 14,1x 16,5
Air flow Return roofcurb ERC x
minimum (m3/h) 490 980 Without 1400 1800x 2700
nominal (m3/h) 820 1650 2300 3000 4500
maximum (m3/h) 980 1970 ERM 2600 3600x 5400
Main Horizontal
coil flow
Without ERC x
Water entering/leaving connections (type) ISO R7 rotating female
Without √
(Dia) 3/4" 3/4" 1 1/2" 1 1/2" 1 1/2"
Electric heater (accessory for blower only) ERM x
Electric power supply (V/Ph/Hz) Barometric relief
230/1/50 ERC
230/1/50 or 400/3/50 400/3/50 x
400/3/50 400/3/50
Heating capacity (kW) 2/4 8 Without 10 12 √ 12
Hot water coil (accessory for blower only)
Heating capacity (4) (kW) 6,3 12 ERM 17,4 22,4x 34,5
G2 filter (filter box accessory) Exhaust fan ERC x
Quantity With multi-directional 2 2 Without 2 2 √ 2
Dimensions ( LxWxth) roofcurb(mm) 386x221x8 486x271x8 586x321x8 586*421*8 586*621*8
ERM √
G4 filter (filter box accessory)
Quantity Return
- roofcurb 2 ERC 2 2 √ 2
Dimensions ( LxWxth) (mm) - 486x264x48
Without 586x314x48 586*414*48
√ 586*614*48
Condensate pump (accessory) (type) Centrifugal
ERM √
Water flow - lift height (l/h - mm) 24 - 500
Not available for FWD30 and FWD45 Without ERC √
Sound level (L/M/H speed) Without √
Sound pressure level (5) (dB(A)) 36/40/43 38/41/44 46/50/53 47/52/57 47/52/58
Sound power level (5) (dB(A)) 46/50/53 48/51/54 56/60/63 57/62/67 57/62/68
Unit dimensions ERM (1)
Width x Depth (mm) Barometric
890 x 600 relief 1090 x 710 ERC 1290 x 820 1290 x(1)
970 1290 x 1090
Height (mm) 250 300 Without 350 450√ 650
Shipped unit dimensions
Width x Depth (mm) 933 x 644 1133 x 754 ERM 1333 x 864 1333 x (2)
1008 1333*1133
Height (mm) Exhaust fan
260 310 ERC 360 460(2) 660
Weight (kg) 32 46 Without 61 76 √ 118
Without multi-directional
Colour galvanised steel
roofcurb ERM √
Recommended fuse size
Unit alone (aM/gI) (A) Return
8/16 roofcurb 8/16 ERC 8/16 8/25√ 8/25
Unit with electric heater (gI) (A) 16 (2kW),25 (4kW) 40 (230V),3*16 (400V)
Without 3*20 3*25√ 3*25
Down flow
(1) Conditions: Water entering/leaving temperature: 7/12 °C, Air inlet temperature 27/19°C DB/WB - Nominal air flow ERM √
(2) Conditions: Water entering/leaving temperature: 50/45 °C, Air inlet temperatureWithout
20°C DB - Nominal air flow ERC √
(3) At high speed with nominal air flow.
(4) Water entering/leaving temperature 90/70 °C, air inlet temperature 20 °C DB, Nominal air flow. Without √
(5) A rectangular glass wool duct 1m50 long is placed on the blower.The measurement is taken in the room containingERMthe blower unit. (1)
Heat exchanger operating limits: Barometric relief ERC (1)
FWD: Without √
*water temperature: max 100° C
*absolute service pressure: min 1 bar/max 11 bars ERM x
Exhaust fan ERC x
Accessories - Hot water coil:
With
*water temperature: min. +2° C/max. 100° C multi-directional Without √
*absolute service pressure: min 1 bar/max 11 bars
roofcurb ERM x
Return roofcurb ERC x
Without x
ERM √
Without ERC √
Without √
The above matrix is intended merely for guidance. For a proper selection, please contact your local Trane sales office.

(1) Barometric relief already included in ERM / ERC


(2) Exhaust fan already included in ERM / ERC

4
18 UNT-PRC002-GB
RT-PRC082A-GB
Product configuration

Options and Accessories


Legend: (S) Standard feature (O) Factory-fitted option (A) Field-mounted accessory

SoundName
power levels Application / benefit Type IH IC
G4 filters Filter the air – 50mm S √ √

Discharge
G4+F7 filters Filter the air – 50mm + 100mm O √ √
VENTILATION & IAQ

G4+F9 filters Filter the air – 50mm + 100mm O √ √


Measurement conditions: Filter the air – 50mm + 100mm
F5+F7 filters O √ √
Measurements taken in a room adjacent to the room containing the FWD, at the outlet of the rectangular duct (1.5 m
Clogged filter To facilitate maintenance of the filters by sending an alarm whenever the pressure
long) fixed to its discharge drop
detector
opening.
of the filter reaches or exceeds an user-defined value
O √ √

Fan Modulating airflow on supply


Power fanintodB(A),
level deliver
peroptimum comfort
Hz frequency bandwith higher energy Overall power
EC plug fan S √ √
Unit speed savings.
125 Includes progressive
250 start-up
500 for textile duct applications
1000 2000 4000 8000 dB(A)
1 Suitable55for retail spaces
50 which use42closed refrigeration
37 37 Unit is fitted
cabinets. 31 with 30 46
FWD 08 Dehumidification2 40O √ 50 √
electric57
heater which 54 47
manages dehumidification 40
of the air 30 38
3 58 57 50 42 32 40 43 53
1 A motorized
57 fresh air51
damper introduces
45 a permanent
42 amount34 of fresh air into
33 the 28 48
Fresh air damper
FWD 10 and hood 2 unit, up58to 100% of the54 nominal airflow.
48 The damper
45 position 38
is adjusted by39an 35S √ 51 √
3 actuator60managed by58the Trane controller.
50 48 40 42 39 54
FRESH AIR MANAGEMENT

1 57 51 45 42 34 33 28 48
The economizer comprises the fresh air hood, damper and sensors to enable free
FWD 12 Economizer 2 58 54 48 45 38 39 35 51
cooling when outdoor conditions are favorable. Dry bulb control (temperature-based) S √ √
(free cooling) 3 60 58 50 48 40 42 39 54
provided as standard.
1 56 62 50 48 39 38 36 56
FWD 14 2 Economizer
61 is equipped 66 with an additional
55 humidity
53 sensor in 47 order to measure
46 45 60
Enthalpy control3 indoor and
63 outdoor enthalpy
69 (energy58 content), for
56 more accurate50 control and 50 higher 49O √ 63 √
1 energy 57
savings 63 51 49 40 39 37 57
FWD 20 2 61 66 55 53 47 46 45 60
Allows to
63 recovery heat69 from the exhaust air and56transfer it to50
the fresh air,50
thus
Heat Recovery 3 58 49 63
reducing the need for mechanical work. Module is installed on the fresh air side of the A √ √
Module
unit with no impact on the footprint
Intake
Sensor installed in the room or ductwork measures the concentration of carbon
CO2 sensor dioxide (e.g. level of occupancy) in order to increase or decrease the fresh air O √ √
Measurement conditions: amount in the buildings
Measurements taken at theReliefs
Barometric relief
horizontal air intake.
pressure when fresh air is being introduced into the building. Adequate for
PRESSURIZATION

S √ √
damper buildings with good air tightness. Available as standard on downflow units only.
Fan Power level in dB(A), per Hz frequency band Overall power
Unit speed Minimizes
125 overpressure250 in the building
500 caused by introduction
1000 of fresh air, 4000
2000 used in 8000 dB(A)
Exhaust fans 1 combination
56 with barometric
55 relief 55
damper (included).
53 Pressure
46 drop in the 45return 42O √ 57 √
FWD 08 2 ductwork63 up to 150 Pa
62 60 60 53 53 53 64
3 66
For applications with 65
high fresh air63 62 system balancing
rates and where 56 55 Roof
is critical. 57 67
Return roof curb1 62 additional damper
curb with 58 and EC 55plug fan extracts
58 51 Pa at nominal
up to 300 48 airflow 44A √ 61 √
FWD 10 2 rate. 66 63 60 62 56 55 52 66
3 70 67 63 65 59 59 57 69
Trips off62in case of presence of smoke55 in the supply
58 side of the51unit. Automatically
Smoke detector1 58 48 44A √ 61 √
FWD 12 2 closes the
66 return air 63and stops the60 unit. 62 56 55 52 66
3 70 67 63 65 59 59 57 69
Fire thermostat Stops the unit when temperature of the air stream rises abnormally A √ √
1 66 65 65 65 57 50 46 68
SAFETY

FWD 14 Epoxy fin coating


2 Provides73additional coil
72 corrosion resistance
69 to protect
71 indoor and
64 outdoor aluminum
59 fins 57O √ 74 √
3 78 76 73 75 69 64 63 78
Network 1 Detects68 phase loss, reversal
72 and imbalance
64 from64main power supply/
56 In case52 of fault, 50O √ 69 √
FWD 20 protection relay2 unit stops.
76 Phase reversal
76 protection 68 provided as71standard 65 61 61 75
Compressor soft3 78 starting current
Limits the 79 71
of the compressor for74 69
a smooth re-start 66 a power 66
(e.g. after 78
O √ √
starter failure)
Provides auxiliary heating using hot water (requires hot water external device such as
Hot water coil O √ √
heat pump or boiler, etc.)
AUX.

Electric heater Provides auxiliary heating using electric heater fitted to the unit O √ √
Provides auxiliary heating using staged or modulating gas burner module fitted to the
Gas burner O √ √
unit

UNT-PRC002-GB
RT-PRC082A-GB 11
19
Product configuration
Technical Data
Name Application / benefit Type IH IC
Airflow Allows to measure airflow based on air differential pressure sensor. PGD Display
A √ √
measurement included.
Remote service Service terminal intended for use by building owners and maintenance personnel.
A √ √
FWDterminal (PGD) Allows to access and adjust advanced 08unit parameters. 12 20 30 45
Power supply (V/Ph/Hz) 230/1/50
THS04 Room User Simple user interface to access and adjust basic unit parameters. Includes room
Capacities A √ √
CONTROLS

interface temperature thermostat. Intended for end-users.


Cooling capacity on water (1) (kW) 5,2 8,3 15 18,8 30,1
Heating capacity
ModBus on water (2) To communicate on
interface (kW)
a ModBus network 6,3 at the unit level. 11,9 18,9 S 20,9 √ 38,2

Fan motor (type) 2 x direct drive centrifugal
Fan power input (3) To communicate on a
(kW) BACnet® MS/TP
0,23 network at the unit level.
0,46 Suitable for 0,65
BacNet interface O 1,04 √ 1,51

Current amps (3) integration with Building
(A) Management 1,1Systems. 2,2 3,1 4,7 5,5
Start-up amps To communicate on(A) a BACnet® MS/TP 3,2 network at the unit level.
5,5 Suitable for 9,3 14,1 16,5
LonTalk interface
Air flow O √ √
integration with Building Management Systems.
minimum (m3/h) 490 980 1400 1800 2700
Customer I/O
nominal Module required for(m3user-defined
/h) external
820 input/output signals
1650(i.e. conventional
2300 3000 4500
O √ √
option module
maximum thermostat). PGD(m service
3
/h) terminal recommended.
980 1970 2600 3600 5400
Main coil
Energy recovery Recover energy contained in the exhaust air using an enthalpy rotary wheel. Mixed
ENERGY RECOVERY

Water entering/leaving connections (type) ISO R7 rotating female O √ √


module (ERM) air streams increase efficiency of the machine.
(Dia) 3/4" 3/4" 1 1/2" 1 1/2" 1 1/2"
Electric heaterrecovery
Energy (accessory for blower
Recover only)
energy contained in the exhaust air using an additional refrigeration circuit
Electric power supply O400/3/50√ √
circuit (ERC) contained in the(V/Ph/Hz)
main unit. 230/1/50 230/1/50 or 400/3/50 400/3/50 400/3/50
Heating capacity (kW) 2/4 8 10 12 12
Recommended
Hot water coil (accessory for blower only) when units are expected to work below +10°C outdoor air in cooling
Heating capacity (4) mode. EC axial fans are fitted to the6,3
(kW) condensing section to reduce
12 the airflow 17,4
when
Low ambient O 22,4 √ 34,5

G2 filter (filter box accessory) required.
Quantity 2 2 2 2 2
Dimensions ( LxWxth) (mm) 386x221x8 486x271x8 586x321x8 586*421*8 586*621*8
G4 filter (filter box accessory)
Quantity - 2 2 2 2
Dimensions ( LxWxth) (mm) - 486x264x48 586x314x48 586*414*48 586*614*48
Condensate pump (accessory) (type) Centrifugal
Water flow - lift height (l/h - mm) 24 - 500
Not available for FWD30 and FWD45
Sound level (L/M/H speed)
Sound pressure level (5) (dB(A)) 36/40/43 38/41/44 46/50/53 47/52/57 47/52/58
Sound power level (5) (dB(A)) 46/50/53 48/51/54 56/60/63 57/62/67 57/62/68
Unit dimensions
Width x Depth (mm) 890 x 600 1090 x 710 1290 x 820 1290 x 970 1290 x 1090
Height (mm) 250 300 350 450 650
Shipped unit dimensions
Width x Depth (mm) 933 x 644 1133 x 754 1333 x 864 1333 x 1008 1333*1133
Height (mm) 260 310 360 460 660
Weight (kg) 32 46 61 76 118
Colour galvanised steel
Recommended fuse size
Unit alone (aM/gI) (A) 8/16 8/16 8/16 8/25 8/25
Unit with electric heater (gI) (A) 16 (2kW),25 (4kW) 40 (230V),3*16 (400V) 3*20 3*25 3*25

(1) Conditions: Water entering/leaving temperature: 7/12 °C, Air inlet temperature 27/19°C DB/WB - Nominal air flow
(2) Conditions: Water entering/leaving temperature: 50/45 °C, Air inlet temperature 20°C DB - Nominal air flow
(3) At high speed with nominal air flow.
(4) Water entering/leaving temperature 90/70 °C, air inlet temperature 20 °C DB, Nominal air flow.
(5) A rectangular glass wool duct 1m50 long is placed on the blower.The measurement is taken in the room containing the blower unit.

Heat exchanger operating limits:


FWD:
*water temperature: max 100° C
*absolute service pressure: min 1 bar/max 11 bars

Accessories - Hot water coil:


*water temperature: min. +2° C/max. 100° C
*absolute service pressure: min 1 bar/max 11 bars

4
20 UNT-PRC002-GB
RT-PRC082A-GB
Operating map
Cooling mode

Operating map at cooling mode


Sound power levels Operating map of cooling mode Low ambient

Discharge
50
45
Ambient temperature (°C)

40
Measurement35 conditions:
Measurements
30 taken in a room adjacent to the room containing the FWD, at the outlet of the rectangular duct (1.5 m
long) fixed25
to its discharge opening. Standard ambient
20
15 Fan Power level in dB(A), per Hz frequency band Overall power
Unit 10 speed 125 250 500 1000 2000 4000 8000 dB(A)
1 55 50 42 37 37 31 30 46
FWD 08
5 2 57 54 47 40 30 38 40 50
0 3 58 57 50 42 32 40 43 53
-5 1 57 51 Low 45ambient 42 34 33 28 48
FWD 10 -10 2 58 54 48 45 38 39 35 51
-15 3 60 58 50 48 40 42 39 54
-20 1 57 51 45 42 34 33 28 48
FWD 12 2 58 54 48 45 38 39 35 51
10 3 15 60 20 58 2550 30
48 40 35 42 40 39 54
1 56 62 50 48 39 38 36 56
FWD 14 2 61 Return
66 air mix temperature
55 (°C)
53 47 46 45 60
3 63 69 58 56 50 50 49 63
1 57 63 51 49 40 39 37 57
FWDMaximum
20 Outdoor2 Temperature
61 (@ Eurovent)
66 = 46°C
55 53 47 46 45 60
Minimum Outdoor 3Temperature
63 = -5°C 69 58 56 50 50 49 63
Maximum Indoor Coil Entering Temperature = 35°C
Intake
Minimum indoor Coil Entering Temperature = 18°C

Measurement conditions:
Heating mode
Measurements taken at the horizontal air intake.

Fan OperatingPower
maplevel
atinheating mode
dB(A), per Hz frequency band Overall power
Unit speed 125 250 500 1000 2000 4000 8000 dB(A)
1 56 55 55 53 46 45 42 57
FWD 08 2 63 Operating
62 map of60
heating mode
60 53 53 53 64
3 66 65 63 62 56 55 57 67
25 1 62 58 55 58 51 48 44 61
Ambient temperature (°C)

FWD 10 2 66 63 60 62 56 55 52 66
20 3 70 67 63 65 59 59 57 69
1 62 58 55 58 51 48 44 61
FWD 12 15 2 66 63 60 62 56 55 52 66
3 70 67 63 65 59 59 57 69
10 1 66 65 65 65 57 50 46 68
FWD 14 2 73 72 69 71 64 59 57 74
5 3 78 76 73 75 69 64 63 78
1 68 72 64 64 56 52 50 69
FWD 20 0 2 76 76 68 71 65 61 61 75
3 78 79 71 74 69 66 66 78
-5
-10
-15
-20
0 5 10 15 20 25 30
Return air mix temperature (°C)

Maximum Outdoor Temperature (@ Eurovent) = 20°C


Minimum Outdoor Temperature = -15°C
Maximum Indoor Coil Entering Temperature = 27°C
Minimum indoor Coil Entering Temperature = 5°C

Note: For units expected to operate in cooling mode with an outdoor air temperature below +10°C, the Low Ambient
option is recommended.

UNT-PRC002-GB
RT-PRC082A-GB 11
21
General data
Technical Data
Table 6 – Single compressor per circuit models
Models IH 039 049 059 064 074 084
Number of circuits / compressors 2/2 2/2 2/2 2/2 2/2 2/2
Nominal airflow (m3/h) 8200 10000 11100 12400 15500 16700
Available static pressure at nominal flow rate (Pa) 250 250 250 250 250 250
FWD 08 12 20 30 45
Available static pressure at nominal flow rate (oversized drive) (Pa) 500 500 500 500 500 500
Power supply (V/Ph/Hz) 230/1/50
Performance data (cooling mode) (1)
Capacities
Net cooling capacity (1)
Cooling capacity on water (1) (kW) 5,2 (kW) 43
8,352 58
15 65 80
18,8 87
30,1
Totalcapacity
Heating power inputon water (2) (kW) 6,3 (kW) 13 11,917 20 18,9 25 27
20,9 31 38,2
Net EER
Fan motor (type) kW / kW 3.4 3.1 2 x direct
2.8 drive centrifugal
2.6 3.0 2.8
Eurovent
Fan power Energy
input (3) class (kW) 0,23 A 0,46A B 0,65 C A
1,04 B 1,51
Current ampsspace
Seasonal (3) efficiency (A) 1,1 % 166 2,2152 138 3,1 128 4,7
145 135 5,5
Start-up ampsoutdoor air temperature range (min./max.)
Operating (A) 3,2 (°C) 10 / 46 5,5
10 / 46 10 / 46 9,3 10 / 46 1014,1
/ 46 16,5
10 / 46
Air flow
Operating outdoor air temperature range (min./max.) - Low ambient (°C) -15 / 46 -15 / 46 -15 / 46 -15 / 46 -15 / 46 -15 / 46
minimum
Performance data (heating mode) (m3/h) 490 980 1400 1800 2700
nominal
Net heating capacity (m 3
/h) 820 (kW) 38 1650
47 54 2300 63 3000
71 78 4500
maximum (m3/h) 980 1970 2600 3600 5400
Total power input (kW) 11 14 17 20 21 24
Main coil
Net COP kW / kW 3.4 3.3 3.1 3.1 3.4 3.3
Water entering/leaving connections (type) ISO R7 rotating female
Eurovent Energy class A
(Dia) 3/4" 3/4"B C
1 1/2" C 1 A1/2" B
1 1/2"
Seasonal space efficiency
Electric heater (accessory for blower only) % 111 109 104 106 103 102
Operating outdoor
Electric power supply air temperature range (min./max.)
(V/Ph/Hz) 230/1/50 (°C) -15230/1/50
/ 20 -15 / 20
or 400/3/50-15 / 20 -15 / 20
400/3/50 -15 / 20
400/3/50 -15 400/3/50
/ 20
General capacity
Heating data (kW) 2/4 8 10 12 12
A-weighted
Hot water Outdoor sound
coil (accessory power level
for blower (2)
only) (dB(A)) 85 85 85 85 86 86
Heating capacity
A-weighted (4) power level in duct (2)
sound (kW) 6,3 (dB(A)) 83 1288 93 17,4 97 22,4
84 87 34,5
G2 filter (filter box accessory) 12,5 / 12,5 /
Auxiliary electric heating capacity - Stage 1 / 2 (kW) 12,5 / 25 12,5 / 25 12.5 / 25 12.5 / 25
Quantity 2 12,5 212,5 2 2 2
Dimensions
Auxiliary (gasLxWxth)
burner heating capacity (mm) 386x221x8(kW) 486x271x8 586x321x8
Available Spring 2017 586*421*8 586*621*8
G4 filter (filter
Weights box accessory)
and dimensions (Operating)
Quantity
Length - (mm) 3010 23010 3010 2 3010 2
3890 3890 2
Dimensions
Width ( LxWxth) (mm) - (mm) 2250 486x264x48
2250 586x314x48
2250 2250 586*414*48
2250 586*614*48
2250
Condensate
Height
pump (accessory) (type) (mm) 1565 1565
Centrifugal
1565 1565 1585 1585
Water flow - lift height (l/h - mm) 24 - 500
Weight (downflow - without options) (kg) 988 1005 1016 1016 1333 1347
Not available for FWD30 and FWD45
Electrical Data
Sound level (L/M/H speed)
SoundPower supply level (5)
pressure (dB(A)) 36/40/43 38/41/44 400 V 46/50/53
/ 3 Ph / 50 Hz 47/52/57 47/52/58
SoundMaximum
power running
level (5)amps (dB(A)) 46/50/53 (A) 41 46
48/51/54 56 56/60/6365 68
57/62/67 84
57/62/68
Unit Start-up
dimensions amps (A) 127 157 175 186 201 209
WidthStart-up
x Depth amps (with soft starter) (mm) 890 x 600 (A) 92 1090 x113
710 126 135
1290 x 820 145
1290 x 970 155 x 1090
1290
Height
Additional amps per option (mm) 250 300 350 450 650
Shipped unit
Electric dimensions
Heater (A) 36 36 54 54 54 54
Width x Depth
Exhaust Fan (70pa) (mm) 933 x 644 (A) 1 1133 x 1754 1 1333 x 8641 1333 1x 1008 1333*1133
1
Height
Exhaust Fan (150pa) (mm) 260 (A) 1 3101 1 360 1 460
2 2 660
Weight
Return Roofcurb (kg) 32 (A) 5 46 5 5 61 9 76
11 11 118
Colour galvanised steel
Energy Recovery Module (ERM) (A) 8 8 8 8 8 8
Recommended fuse size
Supply fan data
Unit alone (aM/gI) (A) 8/16 8/16 8/16 8/25 8/25
Unit Fan
withtype
electric heater (gI) (A) 16 (2kW),25 (4kW) Plug Fan Plug Fan
40 (230V),3*16 Plug Fan
(400V) 3*20Plug Fan Plug Fan
3*25 Plug Fan
3*25
Drive Type EC Motors EC Motors EC Motors EC Motors EC Motors EC Motors
Minimum Water
(1) Conditions: Airflow (m3/h)
entering/leaving temperature: 7/12 °C, Air inlet temperature 27/19°C DB/WB -6560
Nominal air 8000
flow 8880 10300 12400 13360
(2) Conditions: Water entering/leaving temperature: 50/45 °C, Air inlet temperature 20°C
Nominal Airflow (mDB
3
/h)- Nominal
8200air flow 10000 11100 12400 15500 16700
(3) At high speed with nominal air flow.
Maximal Airflow (m3/h) 10660 13000 14430 16120 20150 21710
(4) Water entering/leaving temperature 90/70 °C, air inlet temperature 20 °C DB, Nominal air flow.
Number of fans
(5) A rectangular glass wool duct 1m50 long is placed on the blower.The measurement is # taken in the
1 room containing
1 1
the blower unit. 1 2 2
Motor Max Amps per fan (A) 5 5 9 9 5 5
Heat Motor
exchanger operating limits:
Power - Standard drive (1) (kW) 0.9 1.4 2.0 2.6 2.1 2.6
FWD:
*waterMotor Power - max
temperature: Oversized
100° C drive (1) (kW) 0.9 1.4 2.0 2.6 2.2 2.7
Motorservice
*absolute RPM at nominalmin
pressure: flow1 rate - Standard
bar/max 11 bars drive (1) RPM 1247 1502 1676 1851 1321 1426
Motor RPM at nominal flow rate - Oversized drive (1) RPM 1247 1502 1676 1851 1321 1423
Accessories - Hot
Available water
Static coil:
Pressure at nominal flow rate - Standard drive (Pa) 250 250 250 250 250 250
*water temperature: min. +2° C/max. 100° C
Available
*absolute Static
service Pressure
pressure: min at nominal11
1 bar/max flow rate - Oversized drive
bars (Pa) 500 500 500 500 500 500
Condenser fan data
Fan type Axial Axial Axial Axial Axial Axial
Drive type - Standard ambient AC motor AC motor AC motor AC motor AC motor AC motor
Drive type - Low ambient EC motor EC motor EC motor EC motor EC motor EC motor
Number of fans per circuit # 1 1 1 1 1 1
Motor Power (kW) 0.5 0.5 0.5 0.5 0.7 0.7
Motor Max Amps per fan (A) 1 1 1 1 2 2
Motor RPM RPM 910 910 910 910 686 686

(1) At standard Eurovent rating conditions.


(2) Sound power levels were measured following the ISO 9614 as recommended by Eurovent requirement. All data are given according to standard
EN 12102:2013.

4
22 UNT-PRC002-GB
RT-PRC082A-GB
General data

Table 7 – Dual compressor per circuit models


Models IH 040 050 060 065 075 085 100 110 130
Number of circuits / compressors 2/4 2/4 2/4 2/4 2/4 2/4 2/4 2/4 2/4
Nominal airflow (m3/h) 8700 10600 12100 13700 15700 16700 19800 21600 25500
Available static pressure at nominal flow rate (Pa) 250 250 250 250 250 250 250 250 250
Sound power
Available levels
static pressure at nominal flow rate
(Pa) 500 500 500 500 500 500 500 500 500
(oversized drive)
Performance data (cooling mode) (1)
Discharge
Net cooling capacity (1) (kW) 45 56 64 72 82 88 104 113 133
Total power input (kW) 13 17 19 24 27 30 34 40 51
Measurement
Net EER conditions: kW / kW 3.5 3.4 3.3 3.0 3.0 2.9 3.0 2.8 2.6
Eurovent Energy
Measurements takenclass A
in a room adjacent to the room A
containing theA FWD, at
A the outlet
A of theB rectangular
A B (1.5 m C
duct
Seasonal space efficiency % 176 172 146 151 144 143 146 137 125
long) fixed to its discharge opening.
Operating outdoor air temperature range
(°C) 10 / 46 10 / 46 10 / 46 10 / 46 10 / 46 10 / 46 10 / 46 10 / 46 10 / 46
(min./max.)
Fan
Operating outdoor air temperature range Power level in dB(A), per Hz frequency band Overall power
(°C) -15 / 46 -15 / 46 -15 / 46 -15 / 46 -15 / 46 -15 / 46 -15 / 46 -15 / 46 -15 / 46
Unit (min./max.) - Lowspeed
ambient 125 250 500 1000 2000 4000 8000 dB(A)
1
Performance data (heating mode) 55 50 42 37 37 31 30 46
FWD 08 Net heating capacity 2 57 (kW) 54 39 47 49 40
55 64 30 72 38 77 9240 104 50 125
Total power input 3 58 (kW) 57 11 50 15 42
17 19 32 21 40 23 2743 31 53 39
Net COP 1 57 51
kW / kW 3.4 45 3.4 42
3.2 3.3 34 3.4 33 3.3 28
3.4 3.3 48 3.2
FWD 10 Eurovent Energy class 2 58 54 A
48 B 45
B B
38 A
39 B A
35 B
51 B
3 60 58 50 48 40 42 39 54
Seasonal space efficiency % 113 119 114 118 126 123 128 128 118
1 57 51 45 42 34 33 28 48
Operating outdoor air temperature range
FWD 12 2 58 (°C)54 -15 / 20 48 -15 / 20 -1545
/ 20 -15 / 2038 -15 / 20 39
-15 / 20 -15 35
/ 20 -15 / 2051 -15 / 20
(min./max.)
3 60 58 50 48 40 42 39 54
General data
1 56 62 50 48 39 38 36 56
A-weighted Outdoor sound power level (2) (dB(A)) 84
FWD 14 2 61 66 55 84 85
53 85
47 85
46 85 85
45 85
60 91
A-weighted sound power3 level in duct
63(2) (dB(A))
69 75 58 78 82
56 80 50 84 50 87 9249 96 63 99
Auxiliary electric heating
1 capacity - Stage
57 63 12,5 / 5112,5 /
(kW) 12,549 40 12,5 / 25 12,5
/ 25 12,5 / 25 39 / 25 25 / 37
37,5 25 / 37,557 25 / 37,5
FWD 20 1 / 2 2 61 66 12,5
55 12,5 53 47 46 45 60
Auxiliary gas burner heating
3 capacity
63 (kW) 69 58 56 50 50 49 63
Weights and dimensions (Operating)
Length (mm) 3010 3010 3010 3010 3890 3890 3890 3890 3890
Intake Width (mm) 2250 2250 2250 2250 2250 2250 2250 2250 2250
Height (mm) 1565 1565 1565 1565 1585 1585 1890 1890 1890
Measurement conditions:
Weight (downflow - without options) (kg) 1100 1112 1116 1153 1342 1348 1566 1570 1570
Measurements
Electrical Data taken at the horizontal air intake.
Power supply
Maximum running amps
Fan (A)Power level
44 in dB(A),
50 per Hz frequency
55 66
band 75 80 93 114
Overall 132
power
Unit Start-up amps speed 125 (A)250 80 500 93 113
1000 1292000 161 4000168 204
8000 233dB(A) 253
Start-up amps (with 1
soft starter) 56 (A)55 65 55 75 89
53 102 46 126 45132 159
42 184 57 202
FWD 08 Additional amps per 2 option 63 62 60 60 53 53 53 64
Electric Heater 3 66 (A)65 36 63 36 62
54 54 56 54 55 54 57
90 90 67 90
Exhaust Fan (70pa) 1 62 (A)58 1 55 1 58
1 1 51 1 48 1 44
1 1 61 1
FWD 10 Exhaust Fan (150pa)2 66 (A)63 1 60 1 62
1 1 56 2 55 2 52
2 2 66 2
Return Roofcurb 3 70 (A)67 5 63 5 65
5 9 59 11 59 11 57
11 11 69 18
1 (ERM)
Energy Recovery Module 62 (A)58 8 55 8 58
8 8 51 8 48 8 44
8 8 61 8
FWD 12 2 66 63 60 62 56 55 52 66
Supply fan data
3 70 67 63 65 59 59 57 69
Fan type Plug Fan Plug Fan Plug Fan Plug Fan Plug Fan Plug Fan Plug Fan Plug Fan Plug Fan
1 66 65 65 65 57 50 46 68
FWD 14 Drive Type 2 73 72 EC Motors EC Motors EC Motors EC Motors
69 71 64 EC Motors EC Motors EC Motors EC Motors EC Motors
59 57 74
Minimum Airflow 3 78 (m /h)
3
76 6960 738480 9680
75 1096069 12560 13360
64 15840
63 17280 78 20400
Nominal Airflow 1 68 (m3/h)
72 8700 6410600 12100
64 1370056 15700 16700
52 19800
50 21600 69 25500
FWD 20 Maximal Airflow 2 76 (m3/h)
76 11310 6813780 15730
71 1781065 20410 21710
61 25740
61 28080 75 33150
Number of fans 3 78 # 79 2 71 2 2
74 2 69 2 66 2 2
66 2 78 2
Motor Max Amps per fan (A) 5 5 5 5 5 5 9 9 9
Motor Power - Standard drive (1) (kW) 1.1 1.2 1.4 2.2 2.3 2.6 3.3 3.9 5.7
Motor Power - Oversized drive (1) (kW) 1.1 1.2 1.4 2.1 2.3 2.7 3.3 3.2 4.5
Motor RPM at nominal flow rate - Standard
RPM 1092 1242 1332 1573 1358 1426 1587 1682 1941
drive (1)
Motor RPM at nominal flow rate - Oversized
RPM 1092 1242 1332 1281 1358 1423 1587 1295 1471
drive (1)
Available Static Pressure at nominal flow
(Pa) 250 250 250 250 250 250 250 250 250
rate - Standard drive
Available Static Pressure at nominal flow
(Pa) 500 500 500 500 500 500 500 500 500
rate - Oversized drive
Condenser fan data
Fan type Axial Axial Axial Axial Axial Axial Axial Axial Axial
Drive type - Standard ambient AC motor AC motor AC motor AC motor AC motor AC motor AC motor AC motor AC motor
Drive type - Low ambient EC motor EC motor EC motor EC motor EC motor EC motor EC motor EC motor EC motor
Number of fans per circuit # 1 1 1 1 1 1 1 1 1
Motor Power (kW) 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 1.3
Motor Max Amps per fan (A) 2 2 2 2 2 2 2 2 3
Motor RPM RPM 686 686 686 686 686 686 686 686 900

(1) At standard Eurovent rating conditions.


(2) Sound power levels were measured following the ISO 9614 as recommended by Eurovent requirement. All data are given according to standard
EN 12102:2013.
UNT-PRC002-GB
RT-PRC082A-GB 11
23
Dimensions and Weights
12101973 Sheet 1 of 4 Technical Data
UnitDate: Revision: B
Dimensions (in mm)
21-SEP-2016
Frame 1 – Sizes 039 to 065 (Downflow)
FWD 2773 08 12 20 30 45
Power supply (V/Ph/Hz) 230/1/50
Capacities 2256 (518) 2962
Cooling capacity on water (1) (kW) 5,2 8,3 15 18,8 30,1
Heating capacity on water (2) (kW) 6,3 11,9 18,9 20,9 38,2
Fan motor (type) 2 x direct drive centrifugal
A Fan power input (3) (kW) 0,23 0,46 0,65 1,04153 1,51
Current amps (3) (A) 1,1 2,2 3,1 4,7 5,5
Start-up amps (A) 3,2 5,5 3 9,3 3 14,1 16,5
Air flow 12
1565
minimum 5 4 (m3/h) 490 980 1400 1800 2700
nominal 12 (m3/h) 820 1650 2300 3000 4500
maximum (m3/h) 980 1970 2600 3600 5400
Main coil
14
11 490
Water entering/leaving connections (type) ISO R7 rotating female 263
(Dia) 3/4" 3/4" 1 1/2" 1 1/2" 1 1/2"
Electric heater (accessory for blower only)
Electric power supply (V/Ph/Hz) 230/1/50 230/1/50 or 400/3/50 400/3/50 400/3/50 400/3/50
294 15 3010
12101974
Heating capacity Sheet 1 of 4
Hot water coil (accessory for blower only)
(kW) 2/4 8 10 12 12
11
Date: capacity
Heating Revision:
(4) B 2250 (kW) 6,3 12 17,4 22,4 34,5
G2 filter (filter box accessory)
21-SEP-2016
Quantity 2 2 2 2 2
Frame 2 – Sizes 074 to 085 (Downflow)
Dimensions ( LxWxth) (mm) 386x221x8 486x271x8 586x321x8 586*421*8 586*621*8
G4 filter (filter box accessory)
Quantity - 2 2 2 2
Dimensions ( LxWxth)
(2773) (mm)1300 - 486x264x48 586x314x48 586*414*48 586*614*48
Condensate pump (accessory) 2256 (type)
(518) 3842 Centrifugal
Water flow - lift height (l/h - mm) 24 - 500
Not available for FWD30 and FWD45
Sound level (L/M/H speed)
A Sound pressure level (5) (dB(A)) 36/40/43 38/41/44 46/50/53 153
47/52/57 47/52/58
Sound power level (5) (dB(A)) 46/50/53 48/51/54 56/60/63
3 57/62/67 57/62/68
3
Unit dimensions
12
1585
Width x Depth
12 5 4 (mm)
7 890 x 600 1090 x 710 1290 x 820 1290 x 970 1290 x 1090
Height (mm) 250 300 350 450 650
Shipped unit dimensions
Width x11 Depth
14
(mm) 933 x 644 1133 x 754 1333 x 864 1333 x 1008 1333*1133
Height (mm) 260 310 360 460
510 660
283
Weight (kg) 32 46 61 76 118
Colour galvanised steel
Recommended fuse size 294 15 3890
Unit alone (aM/gI) (A) 8/16 8/16 8/16 8/25 8/25
Unit with electric heater (gI) 2250
11
12101975 Sheet 1 of 4 (A) 16 (2kW),25 (4kW) 40 (230V),3*16 (400V) 3*20 3*25 3*25

Date:
(1) Revision:
Conditions: Water B
entering/leaving temperature: 7/12 °C, Air inlet temperature 27/19°C DB/WB - Nominal air flow
(2) Conditions: Water entering/leaving temperature: 50/45 °C, Air inlet temperature 20°C DB - Nominal air flow
Frame 3 – Sizes 100 to 130 (Downflow)
21-SEP-2016
(3) At high speed with nominal air flow. 1300
(4) Water entering/leaving temperature 90/70 °C, air inlet temperature 20 °C DB, Nominal air flow.
(5) A rectangular glass wool duct 1m50 long is placed on the blower.The measurement is taken in the room containing the blower unit.
2773
Heat exchanger operating limits:
FWD: 1000 1600
*water temperature: max 100° C2256 (518) 3842
*absolute service pressure: min 1 bar/max 11 bars

Accessories - Hot water coil: 1600


A *water temperature: min. +2° C/max. 100° C 153
*absolute service pressure: min 1 bar/max 11 bars
5 3 3
12
1890 4
12 14
5
7
11 510
283

294 15 3890
2250 11

1600

4
24 1000 2100RT-PRC082A-GB
UNT-PRC002-GB
Dimensions and Weights

Energy Recovery Module dimensions (in mm)

Sound power levels


Discharge

Measurement conditions:
Measurements taken in a room adjacent to the room containing the FWD, at the outlet of the rectangular duct (1.5 m
long) fixed to its discharge opening.

Fan Power level in dB(A), per Hz frequency band Overall power


Unit speed 125 250 500 1000 2000 4000 8000 dB(A)
1 55 50 42 37 37 31 30 46
FWD 08 2 57 54 47 40 30 38 40 50
3 58 57 50 42 32 40 43 53
1 57 51 45 42 34 33 28 48
FWD 10 2 58 54 48 45 38 39 35 51
3 60 58 50 48 40 42 39 54
1 57 51 45 42 34 33 28 48
FWD 12 2 58 54 48 45 38 39 35 51
3 60 58 50 48 40 42 39 54
1 56 62 50 48 39 38 36 56
FWD 14 2 61 66 55 53 47 46 45 60
3 63 69 58 56 50 50 49 63
1 57 63 51 49 40 39 37 57
FWD 20 2 61 66 55 53 47 46 45 60
3 63 69 58 56 50 50 49 63

Intake Frame Models L W H


ERM-01 039 to 065 1750 1180 1510
Measurement conditions:
ERM-02 074 to 085 2250 1180 1530
Measurements taken at the horizontal air intake.
ERM-03 100 to 130 2250 1180 1835
Fan Power level in dB(A), per Hz frequency band Overall power
Unit speed 125 250 500 1000 2000 4000 8000 dB(A)
Weights
FWD 08
1
2
56
63
55
62
55
60
53
60
46
53
45
53
42
53
57
64
3 66 65 63 62 56 55 57 67
Basic unit Additional weight per option or accessory
1 62 58 55 58 51 48 44 61
FWD 10 Operating Shipping
2 66 63 60 62 56 55 52 66
Hot Return Return Downflow Energy
Weight 3Weight 70 Electric
67 Exhaust
63 65 59 59 Multidirectional
57 69
Water Roofcurb Roofcurb Adjustable recovery
(Down- 1(Down- 62 Heater
58 Fan
55 58 51 48 Roofcurb
44 61
Coil Down Horizontal Roofcurb module
FWD 12 flow) 2 flow) 66 63 60 62 56 55 52 66
3 70 67 63 65 59 59 57 69
kg 1 kg 66 kg 65 kg kg
65 kg65 kg57 kg 50 kg
46 68kg
FWD 14
IH039 983 2 1015 73 48 72 22 69
24 38071 28064 15059 57
190 74375
3 78 76 73 75 69 64 63 78
IH049 999 1 1031 68 48 72 22 24
64 38064 28056 15052 190
50 69375
FWD 20
IH059 1010 2 1042 76 48 76 22 68
24 38071 28065 15061 61
190 75375
3 78 79 71 74 69 66 66 78
IH064 1010 1042 48 22 24 390 290 150 190 375
IH040 1095 1127 48 22 24 380 280 150 190 375
IH050 1107 1139 48 22 24 380 280 150 190 375
IH060 1111 1143 48 22 24 380 280 150 190 375
IH064 1010 1042 48 22 24 380 280 150 190 375
IH065 1147 1179 48 22 24 390 290 150 190 375
IH075 1335 1367 59 26 39 470 350 170 220 455
IH085 1341 1373 59 26 39 470 350 170 220 455
IH100 1557 1589 65 29 43 470 350 170 220 535
IH110 1561 1593 65 29 43 470 350 170 220 535
IH130 1561 1593 65 29 43 490 370 170 220 535

UNT-PRC002-GB
RT-PRC082A-GB 11
25
Acoustic data
Technical Data
Sound
Overall outdoor sound power level (dB(A) pressure
Spectrum per octave band at full load at 10 m
dB (A)
ESP Global
Model 63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz Lp
FWD (Pa) 08 12 20 dBA
30 45
Power
IH039 supply 100 53 63 (V/Ph/Hz)
73 79 82 78 73 230/1/50
64 85 54
Capacities
IH040
Cooling capacity on water (1)60
100 70 (kW) 74 79
5,2 81 748,3 69 15 64 84
18,8 5330,1
IH049capacity100
Heating on water (2)53 63 (kW) 73 79
6,3 81 7811,9 73 18,9 65 85
20,9 5438,2
Fan motor
IH050 100 60 70 (type)74 79 81 74 2 x69
direct drive 66
centrifugal 84 53
Fan power input (3) (kW) 0,23 0,46 0,65 1,04 1,51
IH059 100 53 63 73 79 81 78 73 64 85 54
Current amps (3) (A) 1,1 2,2 3,1 4,7 5,5
IH060amps 100
Start-up 60 70 (A) 74 79
3,2 82 755,5 70 9,3 66 85
14,1 5416,5
Air flow
IH064 100 53 63 73 79 82 78 75 66 85 54
minimum (m3/h) 490 980 1400 1800 2700
IH065 100 60 70 74 79 81 75 73 69 85 54
nominal (m3/h) 820 1650 2300 3000 4500
IH074
maximum 100 60 70 (m3/h)75 79
980 83 78
1970 69 260058 86
3600 545400
IH075
Main coil 100 60 70 74 79 82 76 73 64 85 53
Water
IH084 entering/leaving
100 connections
60 70 (type)75 80 82 80 ISO
73 R7 rotating
86 52female
54
(Dia) 3/4" 3/4" 1 1/2"
1 1/2" 1 1/2"
IH085
Electric 100
heater (accessory for 60
blower only)70 74 79 82 76 72 85 63 53
IH100
Electric 100
power supply 60 70 (V/Ph/Hz)74 79
230/1/50 81 75or 400/3/50
230/1/50 73 66
400/3/50 85
400/3/50 53
400/3/50
Heating
IH110capacity100 60 70 (kW) 74 792/4 81 76 8 74 10 66 8512 53 12
Hot water coil (accessory for blower only)
IH130capacity100
Heating (4) 59 69 (kW) 78 836,3 88 8312 78 17,4 70 91
22,4 5934,5
G2 filter (filter box accessory)
Unit with standard drive (250 Pa)
Quantity 2 2 2 2 2
Dimensions ( LxWxth) (mm) 386x221x8 486x271x8 586x321x8 586*421*8 586*621*8
G4 filter (filter box accessory) Supply indoor sound power level dB(A)
Quantity Spectrum
- per octave band 2 at full load 2 2 2
Dimensions ( LxWxth) (mm) - 486x264x48 586x314x48 586*414*48 Global
586*614*48
Model pump
Condensate ESP(accessory)
(Pa) 63 Hz 125 Hz
(type) 250 Hz 500 Hz 1000 Hz 2000 Hz Centrifugal
4000 Hz 8000 Hz
dBA
Water flow - lift height (l/h - mm) 24 - 500
IH039 85
Not available for FWD30 and FWD45 71 71 72 76 73 80 72 58 83
IH040
Sound level (L/M/H85 speed) 62 65 65 67 68 66 65 62 75
Sound
IH049 pressure level
110 (5) 70 77(dB(A)) 77 36/40/4379 77 38/41/44 80 46/50/53
85 47/52/57
63 47/52/58
88
Sound power level (5) (dB(A)) 46/50/53 48/51/54 56/60/63 57/62/67 57/62/68
IH050
Unit dimensions 110 65 68 69 70 72 70 69 66 78
IH059
Width x Depth 110 71 82 (mm) 79 890 x 600 82 86 1090 x 71080 1290 90
x 820 71 x 970
1290 93 x 1090
1290
Height
IH060 110 68 72 (mm) 73 250 74 76 300 73 350
72 72450 82 650
Shipped unit dimensions
IH064 110 74 84 81 84 89 83 95 77 97
Width x Depth (mm) 933 x 644 1133 x 754 1333 x 864 1333 x 1008 1333*1133
IH065
Height 110 74 70 (mm) 70 260 76 73 310 76 69
360 60460 80 660
Weight
IH074 110 73 74 (kg) 73 32 77 75 46 79 61
75 62 76 84 118
Colour galvanised steel
IH075 110 73 74 73 77 75 79 75 62 84
Recommended fuse size
IH084
Unit alone (aM/gI)135 70 78 (A) 76 8/16 79 77 8/16 80 82
8/16 658/25 87 8/25
Unit with electric heater
IH085 135 (gI) 70 78 (A) 16 (2kW),25 (4kW)
76 79 4077
(230V),3*16 (400V)
80 3*20
82 653*25 873*25
(1) IH100
Conditions: Water135
entering/leaving72 80 °C, Air inlet temperature
temperature: 7/12 80 82 DB/WB - Nominal
27/19°C 83 air flow 82 88 69 92
(2) IH110
Conditions: Water150
entering/leaving74 84 °C, Air inlet 82
temperature: 50/45 85DB - Nominal90
temperature 20°C air flow 83 93 73 96
(3) At high speed with nominal air flow.
IH130 150 77 87 84 87
(4) Water entering/leaving temperature 90/70 °C, air inlet temperature 20 °C DB, Nominal air flow. 92 86 97 80 99
(5) A rectangular glass wool duct 1m50 long is placed on the blower.The measurement is taken in the room containing the blower unit.

Heat exchanger operating limits:


FWD:
Return indoor sound power level dB(A)
*water temperature: max 100° C Spectrum per octave band at full load
*absolute service pressure: min 1 bar/max 11 bars Global
Model ESP (Pa) 63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz
dBA
Accessories - Hot water coil:
IH039
*water 85 +2° C/max. 67
temperature: min. 100° C 69 72 68 67 80 69 56 81
*absolute service pressure: min 1 bar/max 11 bars
IH040 85 50 63 65 62 60 59 61 62 71
IH049 110 67 72 75 71 71 79 84 62 86
IH050 110 53 67 69 65 64 63 64 66 74
IH059 110 68 79 80 75 76 77 89 69 91
IH060 110 57 70 73 70 67 67 68 72 78
IH064 110 69 79 84 78 79 79 94 76 95
IH065 110 71 69 69 66 67 75 65 57 77
IH074 110 69 71 72 68 69 78 71 59 81
IH075 110 69 71 72 68 69 78 71 59 81
IH084 135 67 75 74 70 71 78 79 63 84
IH085 135 67 75 74 70 71 78 79 63 84
IH100 135 69 76 79 75 75 79 86 67 89
IH110 150 70 80 83 78 79 79 92 72 93
IH130 150 73 81 86 81 82 82 97 78 98

4
26 UNT-PRC002-GB
RT-PRC082A-GB
Acoustic data

Unit with oversized drive (500 Pa)


Supply indoor sound power level dB(A)
Spectrum per octave band at full load
Global
Model ESP (Pa) 63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz
dBA
Sound power levels
IH039 500 75 75 76 80 77 84 76 62 87
IH040 500 68 71 71 73 74 72 71 68 81
Discharge
IH049 500 73 80 80 82 80 83 88 66 91
IH050 500 70 73 74 75 77 75 74 71 83
Measurement conditions:
IH059 500 74 85 82 85 89 83 93 74 96
Measurements taken in a room adjacent to the room containing the FWD, at the outlet of the rectangular duct (1.5 m
IH060 500 72 76 77 78 80 77 76 76 86
long) fixed to its discharge opening.
IH064 500 76 86 83 86 91 85 97 79 99
IH065 500 Fan 78 74 74 in dB(A), per
Power level 80 Hz frequency
77 band 80 73 64 84
Overall power
Unit IH074 500speed 77 125 78 250 77 500 81 1000 79 2000 83 4000 79 800066 dB(A)88
IH075 500 1 77 55 78 50 77 42 81 37 79 37 83 31 79 30 66 4688
FWD 08 2 57 54 47 40 30 38 40 50
IH084 500 74 82 80 83 81 84 86 69 91
3 58 57 50 42 32 40 43 53
IH085 500 1 74 57 82 51 80 45 83 42 81 34 84 33 86 28 69 4891
FWD 10IH100 500 2 75 58 83 54 83 48 85 45 86 38 85 39 91 35 72 5195
3 60 58 50 48 40 42 39 54
IH110 500 77 87 85 88 93 86 96 76 99
1 57 51 45 42 34 33 28 48
FWD 12IH130 500 2 79 58 89 54 86 48 89 45 94 38 88 39 99 35 82 51101
3 60 58 50 48 40 42 39 54
1 56 62 50 48 39 38 36 56
FWD 14 2 61 66 55
Return indoor53sound power47 level dB(A)46 45 60
3 63 69 58
Spectrum per56octave band
50at full load50 49 63
1 57 63 51 49 40 39 37 57
Global
FWD 20Model ESP (Pa)
2 63 Hz 61 125 Hz 66 250 Hz 55 500 Hz 531000 Hz 472000 Hz 4000 Hz
46 8000
45 Hz 60
dBA
3 63 69 58 56 50 50 49 63
IH039 500 71 73 76 72 71 84 73 60 85

IntakeIH040 500 56 69 71 68 66 65 67 68 77
IH049 500 70 75 78 74 74 82 87 65 89
IH050
Measurement 500
conditions: 58 72 74 70 69 68 69 71 79
IH059 500 71 82 intake.
Measurements taken at the horizontal air 83 78 79 80 92 72 94
IH060 500 61 74 77 74 71 71 72 76 82
IH064 500 Fan 71 81 Power 86 in dB(A), per
level 80 Hz frequency
81 band 81 96 78 97
Overall power
Unit IH065 500speed 75 125 73 250 73 500 70 1000 71 2000 79 4000 69 800061 dB(A)81
1 56 55 55 53 46 45 42 57
IH074 500 73 75 76 72 73 82 75 63 85
FWD 08 2 63 62 60 60 53 53 53 64
IH075 500 3 73 66 75 65 76 63 72 62 73 56 82 55 75 57 63 6785
IH084 500 1 71 62 79 58 78 55 74 58 75 51 82 48 83 44 67 6188
FWD 10IH085 500 2 71 66 79 63 78 60 74 62 75 56 82 55 83 52 67 6688
3 70 67 63 65 59 59 57 69
IH100 500 1 72 62 79 58 82 55 78 58 78 51 82 48 89 44 70 6192
FWD 12IH110 500 2 73 66 83 63 86 60 81 62 82 56 82 55 95 52 75 6696
IH130 500 3 75 70 83 67 88 63 83 65 84 59 84 59 99 57 80 69100
1 66 65 65 65 57 50 46 68
FWD 14 2 73 72 69 71 64 59 57 74
3 78 76 73 75 69 64 63 78
1 68 72 64 64 56 52 50 69
FWD 20 2 76 76 68 71 65 61 61 75
3 78 79 71 74 69 66 66 78

UNT-PRC002-GB
RT-PRC082A-GB 11
27
Trane optimizes the performance of homes and buildings around the world. A business of Ingersoll Rand, the leader
in creating and sustaining safe, comfortable and energy efficient environments, Trane offers a broad portfolio
of advanced controls and HVAC systems, comprehensive building services and parts. For more information visit
www.Trane.com