Single-Phase

Transformers COOPER POWER


SERIES
Effective April 2017
CA201002EN Supersedes August 2015

Single-phase pad-mounted
distribution transformers

General
Eaton manufactures a complete line of single- The MaxiShrub transformer is an ANSI® and
phase pad-mounted distribution transformers in IEEE® Type-1 single-phase dead-front pad-mounted
its Cooper Power™ series product line. They are transformer. The ANSI® and IEEE® Type-1
available in standard ratings and configurations or frontplate arrangement allows vertical feed to the
can be customized to meet specific needs. primary and secondary bushings. It is ideal for
Single-phase transformers are available as single-phase industrial and residential applications
Shrubline™, MaxiShrub™, and Ranch Runner™ where a wide range of kVAs or heavy cabling is
transformers (shown above in order). All of these required.
distribution transformers are oil-insulated, self- The Ranch Runner transformer is manufactured
cooled, available in loop or radial feed, and are with ratings from 10-50 kVA. It is Rural Utilities
dead-front. Services (RUS) approved, and meets all ANSI®
Both the Shrubline and MaxiShrub transformer and IEEE® requirements except frontplate
versions are manufactured with ratings from10-167 arrangements. The Ranch Runner transformer
kVA. All of these transformers meet or exceed is a very compact pad-mounted transformer.
ANSI®, IEEE® and NEMA® standards. Its compact design makes it ideal for irrigation,
oil field and residential applications. It offers
The Shrubline transformer is a Type-2 single-phase an economical design which provides standard
dead-front pad-mounted transformer. The low transformer capabilities in a very compact space.
profile design blends visually with surroundings- This unit is shipped complete with its own poly-
shrubs, low hedges, and home air conditioners— pad suitable for shipping and installation.
making it ideal for residential applications.
Eaton offers Cooper Power™ series poly-pads that
are usable with most transformers conforming to
ANSI® C57.12.25-1990 standard (Type-1 or Type-2).
This polymer pad serves as a shipping pallet as
well as an installation pad.
Catalog Data CA201002EN Single-phase pad-mounted distribution transformers
Effective April 2017

STRIPS FOR TAMPER


RESISTANCE

DOOR

LIFTING PROVISION

AUTOMATIC PRESSURE RE-


LIEF DEVICE

BAY-O-NET FUSE
NAMEPLATE

PARKING STAND LOW-VOLTAGE BUSHING

HIGH-VOLTAGE BUSHING

GROUNDING STRAP
DUAL VOLTAGE
SWITCH

GROUNDING PROVISIONS

REMOVABLE
SILL
GROUNDING PROVISIONS

FLOATING LOCK POCKET

Figure 1. Shrubline single-phase pad-mounted transformer.

Standard features • Ground strap from X2 to tank ground


• Meet or exceeds ANSI®, IEEE® and NEMA® standards
• Tamper strips of noncorrosive material
• Meets DOE Energy Efficiency Standard 10 CFR Part 431 for
• Decal bushing designations
distribution transformers • Quality System ISO 9001 certified
• Tank coating exceeds IEEE Std C57.12.28™-2005 and IEEE Std
C57.12.29™-2005 standards (stainless steel units only) Optional features
• Full compliance with IEEE Std C57.12.28™-2005 standard • Various multiple voltages or taps
enclosure integrity requirements • Externally-operable multiple voltage or tap changer switches for
• Laser engraved nameplate safe operation
• Recessed stainless steel lifting provisions • Stainless steel tank, tank bottom, sill, door, and/or hardware
• Tank grounding provisions • Service entrance in sill
• Automatic pressure relief device • Various spades and terminals available for secondary bushings
• Electrical grade mineral oil • High efficiency transformers at 0.05% above DOE efficiency or
• Hinged door with stainless steel hinge pins and barrels higher
• Floating lock pocket for easy alignment
• Stencilled bushing designations
• Captive stainless steel pentahead door locking bolt
• Various other designations available, e.g., kVA, voltages, fuse
number
• Oil fill and drain provisions
• High-voltage bushing inserts
• Removable sill
• Ground connectors
• Welded domed tank cover
• Captive stainless steel hexhead door locking bolt
• High-voltage bushing wells - 200 A
• RUS design

2 www.eaton.com/cooperpowerseries
Single-phase pad-mounted distribution transformers Catalog Data CA201002EN
Effective April 2017

• One piece high-voltage bushings • Liquid level gauge1


• High-voltage bushing wells with removable studs • Temperature gauge1
• Envirotemp™ FR3™ fluid where less-flammable fluid is required • Combination shipping and installation poly-pad3
and where superior enviromental characteristics are desired 1 Not available with the Ranch Runner.

• Canadian Standards Association (CSA) and Consumer Electronics 2 Only available with ANSI®and/or IEEE® Type -2 front plate configurations.
Association (CEA) designs 3 Standard with the Ranch Runner transformer.

• Special designs to meet international specifications are also


available
• Loadbreak switches1
• Drain/sampling valve
• Pressure vacuum gauge1

Single-phase pad-mounted Single-phase pad-mounted


Single-phase pad-mounted ranch runner transformer
shrubline transformer maxishrub transformer
Product Scope:
Product Scope: Product Scope:
kVA: 10-50
kVA: 10-167 kVA: 10-167
Primary Voltage: 2400-14,400 V
Primary Voltage: 2400-19,920 V Primary Voltage: 2400-19,920 V
Secondary Voltage: 120-600 V
Secondary Voltage: 120-600 V Secondary Voltage: 120-600 V

(19" for 150 kV BIL) (19" for 150 kV BIL) 16"


16" 16"
NP

H1B X3
X1
X1 X3
H1A H1B A
A H1A
X2 30" X2

B B B C
C C

Figure 2. Single-phase pad-mounted Figure 3. Single-phase pad-mounted Figure 4. Single-phase pad-mounted


Shrubline. MaxiShrub. Ranch Runner.

Table 1. Typical Dimensions and Table 2. Typical Dimensions and Typical Dimensions and Weights1
Weights3 Weights3 Dimensions (in.) Approx.
Dimensions (in.) Dimensions (in.) Weight
Approx. Approx. kVA “A” “B” “C” (lbs.)
Weight kVA “B” “C” Weight (lbs.)
kVA “A” “B” “C” (lbs.) 10 24 28.5 21 400
10 281 33-36 700
10 24 291 33 600 15 24 28.5 21 500
15 381 33-36 700
15 24 291 33 625 25 24 32.5 21 600
25 24 291 33 650 25 281 33-36 700
37.5 24 35.5 21 650
37.5 24 301 33 700 37.5 281 33-36 750
50 24 35.5 21 720
50 24 321 33 750 50 301 33-36 800
1 Weights, gallons of fluid and dimensions are for reference only,
75 24 341 33 1000 75 321 33-36 1000 and not for construction. Please contact your Eaton
representative for exact dimensions.
100 30 371 36 1150 100 341 36 1150
167 30 471, 2 36 1650 167 461, 2 36 1650
1 Add 3” for 150 kV BiL 1 Add 3” for 150 kV BiL
2 Includes corrugate 2 Includes corrugate
3 Weights, gallons of fluid and dimensions are for reference only, 3 Weights, gallons of fluid and dimensions are for reference only,
and not for construction. Please contact your Eaton and not for construction. Please contact your Eaton
representative for exact dimensions. representative for exact dimensions.

www.eaton.com/cooperpowerseries 3
Catalog Data CA201002EN Single-phase pad-mounted distribution transformers
Effective April 2017

Protection options Quality control


• Bay-O-Net expulsion fuse with Flapper™ valve Eaton provides outstanding performance in its Cooper Power series
• Bay-O-Net and partial range current-limiting fuses1 single-phase pad-mounted distribution transformers.
• Weak link fuse All transformers pass routine tests as prescribed per ANSI® and
IEEE® prior to shipment.
• Weak link and partial range current-limiting fuses
MaxiShrub ANSI® and IEEE® Type-1, Shrubline ANSI® and IEEE®
• Secondary breaker with weak link1 Type-2 and Ranch Runner designs are in full compliance with IEEE
• MagneX® interrupter with isolation link1 Std C57.12.28™-2005 standard security requirements.
• MagneX interrupter with partial range current-limiting fuse1 Corrosion resistance is optimized with the utilization of a superior
coating system, combined with the strategic use of stainless steel
• Under-oil high-voltage MOV arrester1 material, and a tank designed to reduce the retention of water. Our
• Low-voltage distribution-class MOV arrester, internally or coating systems exceed IEEE Std C57.12.28™-2005 and IEEE Std
externally mounted C57.12.29™-2005 standards. Stainless steel components include
door hinge pins and barrels, parking stands, mounting studs, and
• Vacuum Fault Interrupter (VFI) for electronic breaker trip control2
recessed lifting provisions.
1 Not available with the Ranch Runner.
Door and tank covers are permanently domed to eliminate retention
2 Only available with ANSI® and/or IEEE® Type -2 front plate configurations.
of water. All external parts are full-welded to eliminate corrosion
caused by moisture entrapment. Bumper pads on doors reduce
Single-phase VFI transformer shipping damage. Lifting provisions are recessed to reduce damage
Eaton combines both Cooper Power series conventional distribution during handling.
transformer with its proven vacuum fault interrupter (VFI) in its The Quality System at Eaton’s Cooper Power Systems Division
Cooper Power series VFI transformer. This combination provides Transformer Products is ISO 9001 certified.
both voltage transformation and overcurrent protection in one space-
saving, money-saving package. Fluid options
The single-phase pad-mounted VFI transformer with loop protection
is designed to protect the loop or downstream section of a feeder, Transformers can be filled with standard electrical grade mineral
and provide proper coordination with upstream and downstream insulating oil, Envirotemp™ FR3™ fluid, or other dielectric coolants.
protective devices. In this configuration, when a fault occurs For fire-sensitive locations, Envirotemp™ FR3™ fluid, a fire resistant
downstream, the VFI trips and isolates the fault, leaving the natural ester-based fluid is recommended. Envirotemp™ FR3™ fluid
transformer load uninterrupted. also offers the benefits of a soy oil-based dielectric coolant that is
The VFI breaker has an interrupting rating that far exceeds standard sustainable and has unique environmental and material properties in
riser pole fuses, enabling better fault clearing coordination and addition to increased fire safety over conventional mineral oil.
thereby minimizing outage area. Because it is resettable, fault Check with your Eaton representative for the availability of other
locating is simplified and outage time is reduced. dielectric coolants in single-phase, pad-mounted transformers.

Poly-pad
Eaton offers its Cooper Power series poly-pad that is usable with
most transformers conforming to ANSI® C57.12.25-1990 standard
(Type-1 or Type-2). This polymer pad enables transformers to be
shipped and installed on the same pad. Use of the poly-pad can
eliminate the purchasing, inventory, and administrative costs
associated with conventional concrete, polymer or fiberglass
pads. Installation costs can also be significantly reduced since the
transformer is pre-mounted to its pad. These forkliftable units can be
transported damage free during shipping and handling.

Eaton
1000 Eaton Boulevard
Cleveland, OH 44122
United States
Eaton.com

Eaton’s Power Systems Division


2300 Badger Drive
Waukesha, WI 53188
United States
Eaton.com/cooperpowerseries

© 2017 Eaton Eaton is a registered trademark. For Eaton’s Cooper Power series single-phase
All Rights Reserved pad-mounted transformer product information
Printed in USA All other trademarks are property call 1-877-277-4636 or visit:
Publication No. CA201002EN of their respective owners. www.eaton.com/cooperpowerseries.