You are on page 1of 6

High temperature and humidity

transmitter manual
High temperature and humidity transmitter
Model:HT403

1.Brief

This temperature and humidity transmitter is specialized in strict industrial


application with HENGKO RHT series humidity measuring element. It
has the advantage of accurately measuring, adapts to a wide temperature
range, excellent chemical pollution resistance, steady working and long
service time, etc. 2-pin temperature and humidity 4-20mA current signal
output.
Max temperature resistance: 200℃

The chip of HT403 has excellent temperature resistance and can works
under the 200 ℃ for a long time. The special handling of the sensor
surface can make sensor keeping working in the chemical contamination.
HT401 is the best choice in the high temperature harsh environmen t.

2.Specification

Humidity range 0~100%RH

Temperature range -40~200℃

Humidity accuracy ±2%RH

Temperature accuracy ±0.3℃

Response time ≤15s

Output 4-20mA current signal with RS485 interface

Supply voltage 24V DC

3.Feature

1
 0~100%RH full range measuring
 It can be calibrated in the field
 Temperature, humidity, dew point, mixture ratio, absolute humidity
and other 4-20mA output for choice
 Precision measuring - with High precision measuring chip, has
excellent accuracy of measuring.
 Widely measuring range - the measuring range of temperature is
-40~200℃
 Chemical contamination resistance - excellent chemical contamination
ability and can be worked steady in various complex chemical
contamination for a long time.
 Digital interface - with RS485 digital interface with real-time
communication, accuracy calibration, multi monitor, etc.

4.On-site correction

HT403 has be multi-point corrected at the factory. It also can be


corrected via 485 interface or software entering the on-site correction
menu doing multi--point correction. Sending us transmitter for calibration
also available.

5. Application

Industrial on-site measuring, Petrochemical gas emission measuring,


Thermoelectric gas emission measuring, tobacco industry, drying bak
er, environmental test chamber.

6. Technical index

2
Humidity measuring HT403

Humidity range 0-100%RH

Humidity acuracy@25℃ ±2%RH(20% RH…80% RH)

Repeatability(Humidity) ±0.1%RH

Humidity
<0.5%RH
(long-term steady)

Response time-humidity
15s
(tau 63%)

Temperature measuring HT403

Temperature range -40℃~200℃

Accuracy(temperature) ±0.2℃ @25℃

Repeatability(temperature) ±0.1℃

Long-term steady (temperature) <0.04℃

Response time-temperature
30s
(tau 63%)

Power supply/connect HT403

3
Supply voltage 24V DC±10%

Current consumption Max 80mA

Electrical connection Terminal

Output/Parameter HT403

Temperature, humidity, dew point, mixture ratio and absolute


Parameter calculation
humidity for choose

Housing material ABS/ Aluminium alloy

Digital interface RS485 MODBUS RTU

Displayer working temperature -40~70℃

Display method Nixie tube

Cable length Standard length is 1M,can be customized(Max 6M)

7. Terminal definition

8.Product sizes

4
Temperature size

Probe size

9.Note
1. Supply voltage: 12-24VDC
2. Please do not pull the probe forcefully
3. Please pay attention to ventilation and prevent the condensation of
probe if you the measure environment is >90%RH
4. Don’t open the transmitter enclosure without manufacturer's permission