Professional Documents
Culture Documents
Type : i-Temp ci 90 t
i-Temp ci 140 t
i-Temp ci 160 t
Version: V1
Please keep the manual near the product!
© ics
Index
Index
2 General .......................................................................................................................... 3
8 Description ....................................................................................................................11
11.2 Filling......................................................................................................................19
11.3 Adjusting the set-point temperature ........................................................................20
11.4 Installation ..............................................................................................................21
11.5 Commissioning the i-Temp .....................................................................................21
11.6 Bleeding the i-Temp ci 140/160 ..............................................................................23
12 Operation ...................................................................................................................24
35 Maintenance ............................................................................................................110
41.1 Rating...................................................................................................................134
42 Technical data i-Temp ci 140t .................................................................................135
42.1 Rating...................................................................................................................135
43 Technical data i-Temp ci 160t .................................................................................136
43.1 Rating...................................................................................................................136
44 Product overview drawing ........................................................................................137
1 Declaration of Conformity
We declare,
Totton 2014
2 General
2.1 Introduction
These operating instructions are valid for the i-Temp specified in chapter “Technical Data”
and on the name plate.
- The technician or electrician on site who installs and starts up the i-Temp.
- The technician or electrician on site, who is responsible for service and repair work.
- The service engineer who carries out service and repair work.
The operating manual has to always be available for the operating and maintenance
personnel.
Before starting up the i-Temp please read and understand the manual for trouble free
operation.
ICS Cool Energy have no liability whatsoever for damage caused by not understanding these
operating instructions
When passing on this equipment to third parties or other companies, these operating
instructions must be passed on as well.
ICS Cool Energy recommend that you obtain a signature to this effect.
3 Operator’s duties 4
3 Operator’s duties
3.1 Safety Precautions Prior to use
Only use this i-Temp in an undamaged condition and in a safe manner in accordance with
this manual.
Any work carried out on the i-Temp must be by a suitably qualified engineer.
4 Safety Information
4.1 General
When handling or maintaining the i-Temp, personnel must
operate with care observing all instructions concerning health
and safety on site.
Local safety and accident prevention regulations are to be applied for operation.
Unauthorized modifications or alterations that may affect the safety, are not allowed.
For normal operation adhere to the measures that are prescribed by the manufacturer in the
operation manual.
Any unauthorized repair, modification or adjustment of the i-Temp may invalidate the
Warranty. Before proceeding with any work on the i-Temp obtain authorization to proceed
from ICS Cool Energy Limited.
5 Safety Information 6
5 Safety Information
5.1 Use of hoses
To connect the process circuit (PFO and PFI) and cooling water circuit (CWI and CWO and
N) of the i-Temp only use hoses suitable for the fluid, pressure and temperature.
6 Warning Information
Warning information is always marked with a warning label and a hazard-specific symbol.
SIGNAL WORD!
Imminent hazard!
DANGER!
Consequences if not observed are death or
most severe injuries.
7 Used Symbols
Danger of slipping
Danger of explosion
Do not touch
Recycling
Fire extinguisher
7 Used Symbols 9
Electric cabling
CEE plug
Transport
Centre of gravity
Lifting point
Rescue measures
Wear gloves
Magnetic field
Pacemakers prohibited!
Explosion protection
Note
8 Description 11
8 Description
8.1 Proper Use
The operating instructions are directed at the operator of the
system; they contain important information about the safe
operation and maintenance of the system.
The heat transfer fluid is heated up to the set-point temperature selected on the controller
(37) and is pumped through the process.
Depending on the process, heat is supplied to the process or removed from it so the set-
point temperature remains constant.
If the heat transfer fluid in the process cools down below the selected set-point temperature,
the electrical heating (7) is controlled by the i-Temp controller (37) to heat the fluid back up to
set-point temperature .
If the heat transfer fluid in the process is higher than the set-point temperature, then the i-
Temp controller (37) opens the solenoid valve (22.1) in the cooling water supply (CWI)
allowing the cooling water to flow through the heat exchanger (10) where the heat is
absorbed from the heat transfer medium.
If the heat transfer fluid temperature exceeds the set-point and reaches the overtemp stat
(18) set value the i-Temp is switched off. After cooling down and when the reason for the
overheating has been rectified the unit can be reset manually.
8 Description 12
Depending on the temperature set-point, the process is either heated with the heater
elements or cooled with the heat exchanger. The process fluid is circulated by means of a
pump. The cooling water circuit is separated from the process circuit by a heat exchanger.
Temperature control of the process circuit is automatic. A temperature sensor installed in the
process circuit measures the actual temperature. The controller compares the measured
value with the set-point value and controls the heating or cooling. The safety devices ensure
a safe operation of the i-Temp.
9 Transport and Installation 13
Make sure that the i-Temp does not slide, slip, tip or fall over
during transport. Take suitable measures!
Minimum ambient temperature for transport and storage is 5 °C otherwise measures against
frost needs to be taken.
Check the i-Temp for transport damages at receipt. Later claims are excluded!
Inform ICS Cool Energy, before returning the i-Temp Tel.: 02380 527300
Compare the serial number on the shipping documents with the serial number on the name
plate on the rear of the i-Temp .
9.2 Transport
Transport and store i-temp only in an upright position.
Lifting point
Position the i-Temp in such a way that it is not damaged by factory traffic such as fork lifts
etc.
9.4 Installation
National & local standards, regulations and guidelines must be adhered to.
Please allow adequate operation & maintenance space around the i-Temp as per the general
arrangement drawing.
The i-Temp is suitable for internal use only. Adapted units for external installations are
available on request.
9 Transport and Installation 15
Pumps and the heat exchanger are filled with a 100% solution of Corrosion and Frost
protection solution.
Pipe systems, vessels etc. are coated inside with an 100% solution of Corrosion and Frost
protection solution.
After application of the corrosion and frost protection all pipe connections and tank openings
are closed with caps
If the unit has not been run for a long time the free and smooth rotation of the shaft must be
checked.
9.6 Storage
Protect the i-Temp from direct sunlight, frost and humidity. When
storing, a maximum ambient temperature of 55 °C must not be
exceeded. In operation the ambient must not exceed 45 °C.
10 Connecting the system 16
Hot fluid or steam may discharge from the safety valve when the
maximum allowable pressures in the system has been exceeded.
The operator of the i-Temp must ensure that the hot fluid or steam can
discharge without risk of injury. The outlet on the safety valve must
only be connected to piping of the same or larger dimensions having
no back pressure.
CAUTION!
Process fluid
Cooling water
Safety thermostat
Only use suitable hoses for the process fluid lines (PFO & PFI) as
well as the cooling water lines (CWI & CWO) with the correct
pressure, temperature and fluid type ratings!
10 Connecting the system 18
WARNING!
Dangerous voltage!
Dangerous voltage!
Operate the Unit only with the voltage specified on the name
plate that is attached to the back.
Do not open any of the electrical equipment guard panels while the circuit is powered.
Electrical intervention must be performed by qualified personnel using the appropriate
equipment to protect against electrical hazards.
11 Filling and venting the i-Temp 19
Please ensure the process equipment is leak tight, clean and free
of debris. All connecting pipework must be flushed, clean and
suitable for the required temperature, pressure and process fluid.
11.2 Filling
90t
After switching on the unit the fill solenoid valve opens and fills the tank.
140t / 160t
After switching the unit on the fill solenoid valve opens and fills the tank. If installed the fill
pump also starts. The air release solenoid valve is also opened during the first filling process
when the process fluid temperature is below 60C°. After 5 min of operation the valve closes.
If the correct tank level is reached and the level switch activates then the fill solenoid valve
closes. The process pump will start and pump the heat transfer fluid through the process
circuit.
When the level falls the level switch will open the fill solenoid valve to refill the circuit
automatically. The pump continues to run during this time. If the required tank level is not
reached within a set time (standard at 2 minutes), the fill solenoid valve is closed and the
process pump is switched off. A Fill level error is displayed on the Touch-Screen to prevent
the pump from running dry.
11 Filling and venting the i-Temp 20
With this key you can change to the position after the decimal point.
With this key you can change to the position after the decimal point.
11.4 Installation
Required cooling water differential pressure should be no smaller than 2 bar but ideally 4 bar.
If this is not possible, consult our service, see Chapter „Service“.
The safety guidelines as per chapter “Safety” must always be adhered to.
WARNING!
Dangerous voltage!
Remove the right side (viewed from the front by the key pad)
panel. To do this, hold the side panel at the front and at the back
and pull the panel off.
Switch on the unit for a short instant and check the direction of the
motor fan blade. An arrow on the the pump motor marks the
correct rotating direction.
Standard pressure control block cover plate position for venting into the cooling return
line
12 Operation 24
12 Operation
The i-Temp either heats or cools the heat transfer fluid to bring it to the set-point temperature
set on the controller. If the temperature of the heat transfer fluid falls below the set-point
temperature, then the electrical heating is switched on by the controller which heats up the
heat transfer fluid flowing to the process. If the temperature of the heat transfer fluid rises
above the set-point temperature, the controller will open the cooling valve allowing cooling
water to flow through the heat exchanger absorbed the excess heat from the heat transfer
fluid. At the same time, the bypass valve between cooling water inlet CWI and cooling water
outlet CWO opens and the cooling water is mixed in to reduce the cooling water return line
temperature and to avoid steam hammers.
If the temperature of the process fluid temperature rises above a safe working limit, the
overtemp stat will switch the unit off. It must be manually reset after the unit has cooled down
sufficiently and after the cause for overheating has been corrected.
If the pressure in the vessel rises above the normal operating pressure set on the pressure
switch (4 bar), the pressure relief solenoid valve will relief the excess pressure to the cooling
water outlet line.
Timer 1 starts running when the pump starts and stops (only break, no reset) when the pump
stops. After timer 1 expires, the pressure relief solenoid valve opens for the maximum time
set in timer 2. If filling level monitoring triggers before timer 2 expires (message “Filling level”
is suppressed), the pressure relief solenoid valve closes and the fill valve opens until the
filling level is reached. Then the pressure relief valve opens again, etc. until timer 2 has
expired. After that, timer 1 starts automatically.
When timer 1 expires, a message is shown on the display, e.g. “Water exchange required”.
The operator can confirm this with a button “YES”; then the procedure is as described above
starts. When the button “NO” is pressed, water replacement is not made and timer 1 starts
again.
If the buttons “YES” or “NO” are not activated within 30 minutes, timer 1 starts again without
replacing the water.
577
14 Button and Symbol Descriptions 28
Draining.
14 Button and Symbol Descriptions 30
i-Temp draining.
Pump error.
14 Button and Symbol Descriptions 31
In case the function is locked with a lock, you must log in as Engineer! Refer to
User type selection menu. For further details.
You get into the same menu, by tapping on the temperature Set-Point value on
Touch Screen home display.
15 Target value menus 33
Here a 2nd temperature Set-Point value can be entered. This value can be used
as an alternative to the main Set-Point value.
To get to the limit entry, to make changes to the limit value, please press the
button briefly.
In the event of this Set-Point value being selected a ‹2.› appears on the main
display above the temperature Set-Point value. Enable or disable by pressing
the button (1 s).
A upper Set-Point band alarm value can be set here in addition to the set value.
When this limit value is exceeded a limit fault is displayed.
To get to the Set-Point screen to make changes to the limit value, please press
the button briefly. Enable or disable by pressing the button (1 s).
A lower Set-Point band alarm value can be set here in addition to the set value.
When this limit value is exceeded a limit fault is displayed.
To get to the Set-Point screen to make changes to the limit value, please press
the button briefly. Enable or disable by pressing the button (1 s).
An absolute limit can be set here. When this limit value is exceeded a limit
value fault is displayed.
To get to the limit entry, to make changes to the limit value, please press the
button briefly. Enable or disable by pressing the button (1 s).
An absolute limit can be set here. When this limit value is under-run a limit value
fault is displayed.
To get to the limit entry, to make changes to the limit value, please press the
button briefly. Enable or disable by pressing the button (1 s).
In case the ramp is active, an icon with an arrow is displayed on the main
display above the temperature Set-Point value.
In case this arrow blinks, the gradient chosen is too great and the actual value
cannot follow the required ramp up value.
The ramp set value is suspended until the actual value has reached the set
value.
To make changes, tap the button briefly to get to the entry menu.
In case the ramp is active, an icon with an arrow is displayed on the main
display above the temperature Set-Point value.
In case this arrow blinks, the gradient chosen too great and the actual value
cannot follow the required ramp up value.
The ramp set value is suspended until the actual value has reached the set
value.
To make changes, tap the button briefly to get to the entry menu.
If this function is locked with a padlock please log on as ‘Engineer’ in the user
menu!
Note:
This view is only available for the option vtc. Depending on the configuration,
four or eight circuits are displayed.
15 Target value menus 37
The limit values for flow and the difference temperature are set here.
An absolute limit value can be set here. If the value is outside this limit, error of
limit value is displayed.
To change the limit value, tap the button briefly to access input for limit values.
To activate or deactivate, hold down the button briefly (1s).
An absolute limit value can be set here. If the value is outside this limit, error of
limit value is displayed.
To change the limit value, tap the button briefly to access input for limit values.
To activate or deactivate, hold down the button briefly (1s).
The difference between flow line and return line temperature is monitored. An
absolute limit value can be set here. If the value is outside this limit, error of
limit value is displayed.
To change the limit value, tap the button briefly to access input for limit values.
To activate or deactivate, press the button (1s).
16 Trend display menu 38
By pressing on the button you get into the selection menu for the graphs. You
can change the graphs at any time.
In the lower icon line all actual temperature values and the nominal value are
displayed. The orange and the green lines above the temperatures correspond
to the legends of the graphs. The black displayed values show the nominal and
the actual values of the control sensor.
Here you can choose which two graphs to display between the set temperatures
and the three temperature sensors.
16.3 Exception
Is an external actual value used for control purposes via an interface, it will
appear.
17 User selection menu 40
The Operator only has limited rights. He cannot make rule-specific or unit-
specific changes.
The Administrator has full rights to make changes. This level is protected by a
code.
18 Info service info menu 41
Please press one of the three Reset buttons after successful maintenance has
been carried out to acknowledge the Maintenance due alarm.
In case these buttons do not appear, you must log on in the user menu as
Engineer!
Hours, minutes and seconds are changed after pressing the upper keys. Hours
are to be specified in the 24 hour format. By pressing the «OK» button, the
settings are stored in the clock module and also remain after a restart.
Within the dialog you can select the desired time zone.
By default, the «GMT»-time zone is set, this means no time shift. The set time
zone remains, even after a restart.
Note:
The year can not be set less than the current year.
This program is used for the touch calibration and the touch activation / deactivation.
The following display appears on the screen after starting the calibration with «Recalibrate».
The calibration requires a touch pen. Please follow the instructions on the screen.
Press and hold the pen for a short time in the centre of the target (cross) and repeat this
action on the moving target.
If the calibration was performed successfully, the following screen will appear. The calibration
is completed as soon as the calibration is confirmed with a short touch. The calibration data
is stored permenatly in the unit, i.e. the data will be preserved even after a restart.
Note:
The touch pen for calibration is included in the delivery and will be locacted
inside the i-Temp’s control panel.
Please do not use any other sharp objects- they could damage the Touch
screen!
19 Selection info menu 45
19.7.1 IP address
In principle it is possible that the unit receives an IP (network) address from a DHCP server
upon start up «Obtain an IP address via DHCP». To be able to identify the unit explicitly
choose this method «Specifies an IP address».
To do this, ensure that you set an address «IP address », that is still available on your
network. Choose the subnet mask according to your network configuration, select «Subnet
mask» (see the TCP/IP settings on the network properties on your Workstations).
19.7.2 Gateway
The setting (address) for the «gateway» is only needed if you want to access the internet
with the unit via a router. To do this, please ask your network administrator or enter the
address that is entered into your work computer. Enter 0.0.0.0 if no gateway is required or it
is unknown.
The program only allows valid subnet masks. A valid subnet mask contains a continuous
sequence of 1 bits, followed by of 0 bits. At least the MSB (most significant bit - highest) (Bit)
must be 1 and the LSB (least significant bit - lowest) (Bit) must be 0 for the mask to be valid.
See also above chapter about IP classes.
19 Selection info menu 46
19.7.3 DNS
Ask your network administrator about DNS or set for «Primary DNS» and «Secondary DNS»
the address 0.0.0.0.
19.7.4 WINS
Ask your network administrator about WINS or set for «Primary WINS» and «Secondary
WINS» the address 0.0.0.0.
19.7.5 Info
The MAC address of the HMI unit is displayed on the Info page. Is this a proprietary,
worldwide unique ID for the Ethernet port of the unit.
Note:
Changes to the network settings only become active, after the Touch screen
has been restarted.
19 Selection info menu 47
Note:
If the following error message appears after starting the network settings, there
is a problem with the network adapter. The set network location is possibly
already in use by other network user.
20 Sensor selection menu 48
In case this function is locked with a lock, you must log on as an Engineer!
With a brief press of the button you will get into the drop-down menu for
selection of sensor type. PT100, PT1000, Type ‘K’ or Type ‘J’ Thermocouple.
21 Parameter menu 49
21 Parameter menu
• Profibus
• Varanbus
• Euromap 66
• Device Net
• Canbus
• Simplified protocol
- -100°C...+400°C
The control parameters for heating and cooling can be configured here.
Note:
Here you can export the last 3600 actual values (12 minutes) as a CSV file to
the SD card.
The self optimisation for heating can be started here Enable or disable by
shortly pressing the button (1 s).
21 Parameter menu 54
The self optimisation for cooling can be started here Enable or disable by
shortly pressing the button (1s).
The self optimisation for heating and cooling can be started here. Enable or
disable by shortly pressing the button (1s).
The fine optimization for heating and cooling can be started here. Activate or
deactivate by shortly pressing the button (1s).
The set of control parameters for heating can be exchanged here between P 1
and P 2.
The set of control parameters for cooling can be exchanged here between P 1
and P 2.
All control parameters P 1 for heating and cooling are set back here to factory
default.
Note:
Proportional (Pb)
Proportional band (Pb) too small Proportional band (Pb) too large
If Proportional band (Pb) is too small, the control will a adjust control deviation
insufficiently and too slowly and reacts generally too slowley.
On the other hand, if Proporational band is too large, the system will tend to oscillate
Integral time (I) too small Integral time (I) too large
- If Integral time is too large, the integral ratio in the control variable cannot build up fast
enough. Therefore the integral ratio must correct adjustment to the setpoint value slowly
through the remaining control deviation.
21 Parameter menu 57
Derivative time (D) too small Derivative time (D) too large
If Derivative time (D) is set too small, too much energy is fed into a control line in case of
a jump in setpoint values due to the proportionate and integral ratio because the
differential ratio cannot sufficiently counter-regulate. This will therefore cause
overshooting. However, unlike when ‘I’ is too small, errors are balanced in a better way.
If ‘D’ is selected too large, a counter-reaction that is too strong will be triggered in case a
control deviation occurs. Therefore the control value will show a tendency to oscillate
when adjusting control. As the control adjustment in case of ’P’ too large shows, the
behaviour can be hardly distinguished. However, it is apparent that control deviations
are balanced faster when merging into the setpoint value.
Optimal settings
Optimal settings
21 Parameter menu 58
In addition to the measured value of the sensor, a static offset can be set here.
In addition to the measured value of the sensor, a static offset can be set here.
In addition to the measured value of the sensor, a static offset can be set here.
In addition to the measured value of the flow meter, a static offset can be set
here.
Here you can set a static offset for the measured value of the sensor.
21 Parameter menu 59
Here you can set whether the i-Temp shall start automatically after a power
outage. The unit has to be switched on before the power outage occurred.
Enable or disable by pressing the button (1s).
One start and stop time can be programmed here for each weekday. Enable or
disable by pressing the button (1s). Not programmed times are displayed as ‹-:-
› and skipped in the reporting.
Info timer
One start and stop time can be programmed here for each weekday. Not
programmed times are displayed as ‹-:-› and skipped in the reporting.
It is possible to program a start time for Monday at 6:00 a.m. and a stop time for
Friday 6:00 p.m. The unit would then automatically turn on Monday at 6:00 a.m.
and turn not off until Friday at 6:00 p.m.
After turn off the next start time will be displayed on the main display. The unit
may be switched on / off at any time via the start/stop button. This however
disables the timer!
To create or change a switching time first a day of the week must be selected.
Then select whether it is a start or stop time.
Afterward select the desired switching times via the arrows set. To disable a
switching time enter the minutes or hours smaller than ‹00› and ‹-:-› appears on
the display.
21 Parameter menu 60
A profile can be created here, which will be executed at every restart of the
program. Enable or disable by shortly pressing the button (1s).
The program remains in step 0 until the actual value has reached the soft start value
The program remains in step 1until the timer T1 is expired. In case this step should be
skipped please set the timer T1 to 0 sec.
The program remains in step 2 until the actual value has reaches the standard target value.
The program remains in step 3 until the timer T2 is expired. In case this step should be
skipped please set the timer T2 to 0 sec.
As step 4 you may set what the unit shall do after the program ends.
Range of settings:
Here you can create new recipes and load existing recipes, save, delete, export
or import.
The original recipe data has been changed. E.g. changing the set point.
21 Parameter menu 62
To do so, select the pick list the appropriate recipe and press the 'delete' button.
To do so, select the pick list the appropriate recipe and press the 'save ' button.
To do so , select the pick list the appropriate recipe and press the 'load' button.
Select a recipe
Select a recipe
You can select between manual water exchange and automatic water
exchange.
Note:
21.9 Parameters P 01 to P 50
Note:
21.9.1 Parameter P 01 to P 10
Setting range:
- On: After 60 seconds without input the backlight is slightly dimmed. This
increases the lifespan of the display.
21.10 Parameters P 11 to P 20
• P [17]: Limit value error affecting collect of fault message Setting range:
- Yes: Limit value errors effect collect of fault massage.
- No: Limit value errors do not affect collect of fault message.
21.11 Parameters P 21 to P 30
A fixed switching value is always used for switching between control elements.
- dynamically:
An adjustable value, corresponding to the setpoint value is always used for
switching between control elements.
21.12 Parameters P 31 to P 40
21.13 Parameters P 41 to P 50
22 Language menu
You can switch to a different language here. You will get into the same menu by
clicking on the flag above.
Note:
By clicking on the ICS Cool Energy symbol in the right upper corner you create
a Screenshot.
In case of a long help text you can scroll with the aid of the plastic touch screen
pen which is supplied with Touch Screen.
The Scroll bar can be found on the right side of the monitor display.
Note:
To switch to the overview of the vtc distributor, click on the highlighted temperature display
on the home screen.
Return line temperature, flow quantity and the calculated and dissipated power per circuit are
shown in a table.
If one of the limit values set in the menu “Setpoint values” is violated this is indicated in the
table.
To return to the main screen, click the temperature display in the top right.
25 Error messages 74
25 Error messages
The touch panel has stored other parameters than the unit control! Please enter the correct
device parameters!
Maintenance required
System error
Please check the power supply of unit control and the connection cable between the touch
system and the unit control.
Pump control
Please check the rated current of the motor and the settings of the appropriate monitoring
unit.
Temperature control
Please cool off the unit to the safe temperature level and Reset the safety thermostat.
Flow disturbance
Interface error!
Please check the connectors and the wiring between the master and unit control.
25 Error messages 76
Overflow alarm
Please check the nominal current of the motor and the setting of the corresponding
monitoring device.
Phase error
vtc Line: #1
• 1 start bit
• 8 data bit
• 1 parity bit
• 1 stop bit
The bytes of the test sum present the last two digits of the binary sum, formed of 1st byte up
to nth byte.
Only the contents of messages (6th – nth byte of the message) are listed below.
4 bytes Nominal value in degree Celsius, 3 digits before the comma, 1 digit after the comma
every byte is coded in ASCII (30H, 39H). Negative temperatures have 2DH at first digit.
Adjustments are only possible up to –99,9 °C.
6BH (k): Cool to stop set-point and switch pump off, respond with either „k“ or „p“
bit 3: spare = 0
bit 5, 6, 7: 1, 1, 0 set
1 byte Status word for alarms 1 (announce alarms additionally as total alarm in bit 4
of the preceding byte)
bit 6, 7: 1, 0 set
28 Connection of the serial interface 87
Bit 3, 4, 5: spare = 0
Bit 6, 7: 1, 0 set
Bit 3: spare = 0
Bit 5, 6, 7: 1, 1, 0 set
28 Connection of the serial interface 88
Bit 6, 7: 1, 0 set
Bit 3, 4, 5: spare = 0
Bit 6, 7: 1, 0 set
60H spare
20 H spare
40H alarm 1
40H alarm 2
60H spare
20 H spare
40H alarm 1
40H alarm 2
30H, 31H, 32H, 35H actual value flow rate 12,5 l/min
Control commands
Hex Dec Control code Description
41 65 A Controlling internal sensor
42 66 B Controlling external sensor
43 67 C Standby
44 68 D Stop (Pump off)
45 69 E Cool down to cool-down temperature / hold
46 70 F Cool down to cool-down temperature / stop
47 71 G Cool down to safety temperature / stop
48 72 H Pump down at cooling temperature
49 73 I Pump down at safety temperature
4A 74 J Leakage stop enterprise
4B 75 K Normal operation
Statusbyte 1
Hex Dec Marking Description
65 101 o Actual value of external sensor
(Option)
69 105 i Actual value of internal sensor
Statusbyte 2
Hex Dec Marking Description
61 97 a Controlling activated (normal
operation)
62 98 b Stand by
63 99 c Stop
64 100 d Cooling down
65 101 e Holding at 2nd set value
66 102 f Pump down
6C 108 l Leakage stop actively
-----------------------------------------------------------------------------------------------------------------
-----------------------------------------------------------------------------------------------------------------
Bit 4 = 1 Leakage stop enterprise switch on; Pump left handed rotation
-----------------------------------------------------------------------------------------------------------------
Bit 11 = 0 reserve
-----------------------------------------------------------------------------------------------------------------
Bit 14 = 0 reserve
Bit 15 = 0 reserve
-----------------------------------------------------------------------------------------------------------------
-----------------------------------------------------------------------------------------------------------------
Bit 6 = 1 passing of limit value (-) act. > set –II (P)
----------------------------------------------------------------------------------------------------------------
-----------------------------------------------------------------------------------------------------------------
-----------------------------------------------------------------------------------------------------------------
= 0 Hand operation
-----------------------------------------------------------------------------------------------------------------
Bit 7 = 0 reserve
-----------------------------------------------------------------------------------------------------------------
Bit 10 = 0 reserve
Bit 11 = 0 reserve
-----------------------------------------------------------------------------------------------------------------
Bit 12 = 0 reserve
Bit 13 = 0 reserve
Bit 14 = 0 reserve
Bit 15 = 0 reserve
-----------------------------------------------------------------------------------------------------------------
interface:
Serial: RS 422
Baud: 4800
Data: 8 BIT
Stop: 1 BIT
Parity: no
Checks.: no, answer with wrong data. Monitoring by Timeout.
MASTER -> controller ( account Version no controller board )
high-
4 0-255 SOLL - TEMP. Byte 4 0 Not used
5 0 Not used binary 5 0 Not used
6 0-255 STATUS binary 6 0 Not used
7 FF hex STOP binary 7 0 Not used
controller -> MASTER
BYTE VALUE IMPACT Different Versions
0 FE hex START binary e.g. 0700 = CI 160
1 0-128 ADDRESS binary 0800 = CI 140
2 "V" IDENTIFIER ASC 1000 = CI 90
3 0 Not used binary 1100 = CW 25
4 0-255 Version no low-Byte
high-
5 0-255 Version no Byte
6 0-200 Offset inlet
7 0-200 Offset outlet
8 0-200 Offset Extern
Offset rate of
9 0-200 flow
10 0 Not used binary
11 FF hex STOP binary
Offset : 000 = -10.0
100 = 0
200 = +10.0
controller -> MASTER
STATUS 1
BYTE VALUE IMPACT BYTE VALUE IMPACT
0 FE hex START binary 0 0/1 Circuit on
1 0-128 ADDRESS binary 1 0 Not used
2 "A" IDENTIFIER ASC 2 0 Not used
3 0-255 STATUS 1 binary 3 0/1 draining
4 0-255 STATUS 2 binary 4 0/1 Fault sensor inlet
5 0-255 IST VL low-Byte 5 0/1 Fault sensor outlet
high-
6 0-255 IST VL Byte 6 0/1 Fault sensor Extern
7 0-255 IST RL low-Byte 7 0/1 Fault Flow
high-
8 0-255 IST RL Byte
9 0-255 IST EXT low-Byte
high-
10 0-255 IST EXT Byte STATUS 2
11 0-255 IST FLOW binary BYTE VALUE IMPACT
12 0-255 IST LEISTUNG binary 0 0/1 Level fault
13 0 Not used binary 1 0/1 Overtemperature heating
14 FF hex STOP binary 2 0/1 Pump fault
3 0 Not used
Unit output % : 000 = -100 % 4 0 Not used
100 = 0 % 5 0/1 System fault
Switch temperature to
200 = +100% 6 0/1 high
7 0 Not used
32 Connection the VARAN Bus interface 102
Read/
Offset Description Write Size Units
Read/
Offset Description Write Size Units
Bit 4 : Suction mode error Setting alarm
Bit 5 : Manual mode active
Bit 6 : reserved
Bit 7 : reserved
Read/
Offset Description Write Size Units
Bit 3 : reserved
Bit 4 : Flow sensor failure Machine alarm
Bit 5 : reserved
Bit 6 : reserved
32 Connection the VARAN Bus interface 104
Bit 7 : reserved
Read/
Offset Description Write Size Units
Bit 7 : reserved
Pin 2 CAN L
= 1 Unit switch on
Possible Baud rates: 125, 250, 500 kBaud; Default: 125 kBaud
34 Fault Finding 108
34 Fault Finding
Motor does not run, motor Motor winding short. Replace the pump motor.
winding has an
excessively high or low/no
resistance.
Water leaks at the tank. Level switch faulty. Check level switch, replace
if necessary
i-Temp is not filling Controller fault, y-strainer is Replace controller, clean y-
blocked, no water available strainer, ensure water is
available
Fill level probe in the i-Temp wi Clean fill level probe (wi),
faulty or dirty, pressure switch in the check wiring and replace
i-Temp wd faulty or dirty. pressure switch (wd).
i-Temp is over-filled
Wiring fault. Check all wiring and
cabling.
34 Fault Finding 109
i-Temp controller is Heater contactor or solid state relay Replace heater contactor,
showing that it is heating faulty safety contactor and/or
although there is no output solid state relay.
voltage.
Pump is not pumping or Size of the hoses/piping too small, i- Use hoses with a bigger
not enough water Temp not suitable for application, bore, obtain correct i-
process pipework or pump clogged Temp, clean process
or blocked, valves not fully open, pipework and pump, open
all valves
i-Temp does not heat or Heater contactor faulty, heater Check and replace heater
heats insufficiently element faulty, overtemp stat contactor, replace heater
activated, cooling is on element, wait for over temp
permanently, heating load too big stat to cool and reset or
replace, check function,
clean or replace of cooling
motor/solenoid valve,
obtain i-Temp with correct
heating capacity
i-Temp does not cool or Insufficient cooling water pressure, Increase the differential
cools insufficiently dirty y-strainer, cooling pressure between CWI
motor/solenoid valve dirty or faulty, and CWO to a minimum of
cooling water pipework clogged or 2 bar but ideally 3bar,
blocked, cooling heat exchanger clean the y-strainer, clean
calcified. or replace the cooling
motor/solenoid valve, clean
or unblock cooling water
pipework, de-calcify or
replace cooling heat
exchanger
i-Temp does not start; No power, fuse blown Check fuse, check power
supply
35 Maintenance 110
35 Maintenance
35.1 General
Regular visual inspections prevent unexpected shutdowns and downtime.
These inspections, together with maintenance and the replacement of worn parts, should be
done at regular intervals.
Spare parts must conform to the technical specifications made by the manufacture.
Inadequate or incorrect maintenance can cause long downtimes and also high repair costs.
Due to the large variety of possible operating conditions, it is not possible to determine in
advance what maintenance intervals should be followed.
Our service division would be glad to recommend suitable maintenance intervals based on
your operating conditions.
Please contact the service division if you have any questions concerning maintenance work.
36 Service Intervals 111
36 Service Intervals
All listed service intervals are guidelines. Depending on application type, operating
circumstances and ambient conditions, shorter intervals may be necessary.
We recommend draining and rinsing the machine at intervals depending on the local water
quality and the degree of contamination.
Filling Shunt Check function, ensure water supply; check for leaks, 1000
pump operating period max. 10 min
This special software version makes it possible that the specified time can be shifted up and
down from the specification.
Making individual adjustment may result in premature failure of components and malfunction
of the system.
Adjusting the warning recommendation will release us from any warranty obligation that is
caused by insufficient service.
Moving the service intervals up from those specified by ICS is registered in the controller and
is retroactively traceable by us.
36 Service Intervals 113
WARNING!
Dangerous voltage!
Before carrying out of any maintenance or repair work: pull out the mains
plug!
CAUTION!
Danger of burning!
Danger of burning!
High temperatures may arise on any part of the i-Temp that is in contact with the heat
transfer fluid.
Connection pipes & hoses and machine panels can heat up due to the hot circulating
process fluid.
36 Service Intervals 114
The operator has to ensure that the electrical motor, components etc. do not come into
contact with liquids.
36.4 Storage
Undo pipes from connection block and unscrew connection block mountings
Disconnect plugs (pump & heater element) from the back off control box and undo back
panel
Unbolt tank lid with hydraulic assembly and remove from the casing
Pump / cooling coil / / heater element and level switch can now be removed and replaced as
required.
Dirty
Clean
Flow meter
Dirty
Clean
Loosen screw.
36 Service Intervals 121
Turn counter-clockwise.
Lift off.
37 Disposal
Dismantling and Disposal of the i-Temp
37.1 Dismantling
All work on the i-Temp may be undertaken by trained staff only, e.g.
electricians, metal workers or specialists of similar disciplines.
37.2 Disposal
When disposing of heat transfer fluid and electrical components and
devices, observe all local and national regulations.
When water is used as the heat transfer fluid on the i-Temp, no special
regulation needs to be observed.
Disposal must be carried out according to the relevant waste regulations. For the disposal of
hazardous waste a relevant waste disposal company must be consulted. Waste Transfer
notes must be filed.
38 Required Water Quality 125
To protect the i-Temp from corrosion and deposits, the quality of the cooling water must be
monitored.
The suitable procedure for preparation and/or treatment of cooling water depends on:
a. In systems with galvanised pipe materials, the pH-value of 8.5 must not be exceeded.
The treatment procedure must be adjusted to this.
c. Addition of biocides should only happen in sufficiently large intervals before or after
discharge or draining.
Added water
These guideline values by ICS provide recommendation for the water-chemical operation of
cooling and temperature control circuits.
If the above guideline values for the quality of added water and circulation water are
monitored, the basic conditions for fault-free operation of the products are met.
Stephenson Road
Totton, Southampton
SO40 3SU
If deviation of water quality causes breakdown or damage to the i-Temp, ICS cannot assume
liability.
39 Spare Parts and Consumables 127
E Spare part
V Consumable part
Consumables are spare parts that are subject to constant wear. Therefore, they have a
shorter service life and cannot be replaced in the course of warranty.
To order spare parts and/or consumables, please contact out sales office spare parts, see
also chapter "Customer service".
39 Spare Parts and Consumables 128
E = Spare part
V = Consumable
When ordering, please always state the serial number of the i-Temp.
40 After Sales Service 133
The voltage for which your equipment is suitable is on the name plate at the back of the
equipment.
42 Technical data i-Temp ci 140t 135
140t 9 140t 18
Line voltage 400-415V, 50 Hz, 3 Ph PE
Control voltage 24V DC, 50Hz
Protection IP 54
Max. temperature °C 140
Process circuit Pressurised water
Heat transfer medium Water
Heating capacity kW 0/6/9 12 / 18
Nom. cooling capacity at
kW
Cooling water temperature
15°C 40 / 120
Circulating water
130°C
temperature
Process pump WP 60
Design Peripheral pump with axial face seal / Magnetic
coupled pump / Stainless steel pump
Flow rate, max. l/min 60 / 60
Pump pressure, max. bar 5,5 / 6,0
Pump Capacity kW 0,75 / 1,0
Mould drain volume l
Dimensions LxWxH 680x250x595 955x400x740
Weight kg 50 95
Noise emission <70dB(A) Lpa1m DIN 45635T1
Other available mains voltages (optional)
The voltage for which your equipment is suitable is on the name plate at the back of the
equipment.
43 Technical data i-Temp ci 160t 136
160t 9
Line voltage 400-415V, 50 Hz, 3 Ph PE
Control voltage 24V DC, 50Hz
Protection IP 54
Max. temperature °C 160
Process circuit Pressurised water
Heat transfer medium Water
Heating capacity kW 0/9
Nom. cooling capacity at
kW
Cooling water temperature
15°C 40
Circulating water
130°C
temperature
Process pump WP 80
Design Peripheral pump
Flow rate, max. l/min 60
Pump pressure, max. bar 5,5
Pump capacity kW 1,0
Mould drain volume l
Dimensions LxWxH 680x250x595
Weight kg 50
Sound Pressure <70dB(A) Lpa1m DIN 45635T1
Other available mains voltage (optional)
The voltage for which your equipment is suitable is on the name plate at the back of the
equipment .
44 Product overview drawing 137
The electrical diagram will be in the control box or with the unit.
∅
0 1 2 3 4 5 6 7 8 9
18.09.2014
CWI/F CWI/F
-F1
y-strainer
-H1
solenoid valve
-1Y1
10W | 24V DC
ics-standard-Normblatt-MCAD-A3-Quer-V1
-H2
solenoid valve
-1Y2
8W | 24V DC
CWO CWO
PFO PFO
TI FQI
200 200
F F -1M1
0,5kW | 1,6A | 380-420V -1B1 -H3
Flow meter with temperature sensor solenoid valve
-1Y3
8W | 24V DC PFI PFI
-P1
0,5kW
process pump
-A1
LZ- 0,153m²
500
-2S1
Level switch
TIC TZ+
-B1
501 tank 502
-2B2 -2B1
temperature sensor overtemp stat
-1E1
3 x 3kW | 400-415V | 14,2A el
heating
drain
TIC
100
-1B2
temperature sensor
PFO PFO
-1Y1
36VA (Anzug)
16VA/8W | 24VDC
ics-standard-Normblatt-MCAD-A3-Quer-V1
CWI CWI
-H2 -F1
solenoid valve y-strainer
CWO CWO
-W1
1,60m²
heat exchanger
-H1
solenoid valve
-1Y2
8W | 24V DC
TI FQI
-1B1
flow meter with temperature sensor
LZ-
500
-2S1
level switch
TZ+
-B1
tank 502
-1E1 -2B1
temperature limitation
3 x 3kW | 400-415V | 14,2A el
-1E2
3 x 3kW | 400-415V | 14,2A el
drain
TIC
100
-1B2
temperature sensor
PFO PFO
-1Y1
36VA
16VA/8W | 24VDC
ics-standard-Normblatt-MCAD-A3-Quer-V1
CWI CWI
-H2 -F1
solenoid valve y-strainer
CWO CWO
-W1
1,60m²
heat exchanger
-H1
solenoid valve
-1Y2
8W | 24V DC
TI FQI
-1B1
Flow meter with temperature sensor
LZ-
500
-2S1
Level switch -1E1
3 x 3kW | 400-415V | 14,2A el
-1E2 TZ+
-B1
3 x 3kW | 400-415V | 14,2A el tank 502
-1E3 -2B1
temperature limitation
3 x 3kW | 400-415V | 14,2A el
-1E4
3 x 3kW | 400-415V | 14,2A el
drain
1 3 5
0Q1
2 4 6
1 2 3 4 5 1 7 8 3 9 2
x1 x2
PE 1 2 3 4 5 1 7 8 3 9 2
M
3
CEE 16A
1L+
(1.11)
5
x1
5
6
x1
6
12 1 2 8 9 10 11 13 14 15 8 9 10 11 13 14 15
X1b 12 1 2 8 9 10 11 13 14 15
X1a 8 9 10 11 13 14 15
12 1 2 3 4 5 6 7 7 3 4 5 6
X1a X1b
12 1 2 3 4 5 6 7 7 3 4 5 6
PE1
(1.13) 1
0H1
2
1L-
(1.12)
1 2 1 2 1 2
1.6 1.5 1.4
3 4 3 4 3 4
1.6 1.5 1.4
5 6 5 6 5 6
1.6 1.5 1.4
13 14 13 14 13 14
.10 .3 .2
1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 10
X2 X3
1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 10
X9 X10 X8
X6
X7
X4 X4
RJ45
X2
M12
1 2 1 2 1 2
1 2 1 2 1 2
1 2 1 2 1 2 1 2
1 2 1 2 1 2 1 2
RJ45
RJ45
1 3 2 4
M12 TD+ TD- RD+ RD-
L1
L2
L3
1 3 5
1F2
32A
2 4 6
1 3 5
0Q1
2 4 6 0G1
PE PE PE PE
PE 1 2 3 4 5 1 7 8 3 9 2 5 1 7 8 3 9 2
x1 x2 x3
1 2 3 4 5 1 7 8 3 9 2 5 1 7 8 3 9 2
M
3
1L+
(1.10)
12 1 2 8 9 10 11 13 14 15 8 9 10 11 13 14 15
X1b 12 1 2 8 9 10 11 13 14 15
X1a 8 9 10 11 13 14 15
12 1 2 3 4 5 6 7 7 3 4 5 6
X1a X1b
12 1 2 3 4 5 6 7 7 3 4 5 6
PE
(1.13)
1
0H1
2
1L-
(1.12)
1 2 1 2 1 2
1.7 1.5 1.4
3 4 3 4 3 4
1.7 1.5 1.4
5 6 5 6 5 6
1.7 1.5 1.4
13 14 13 14 13 14
.9 .3 .2
1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 10
X2 X3
1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 10
L1
L2
(2.1)
L3
1 3 5
1F2 1 3 5
32A
1F3
2 4 6 32A
2 4 6
1 3 5
0Q1
2 4 6
PE PE PE PE PE PE
PE 1 2 3 4 5 1 7 8 3 9 2 5 1 7 8 3 9 2 5 1 7 8 3 9 2 5 1 7 8 3 9 2
x1 x2 x3 x4 x5
1 2 3 4 5 1 7 8 3 9 2 5 1 7 8 3 9 2 5 1 7 8 3 9 2 5 1 7 8 3 9 2
M
3
L1
L2
(1.14)
L3
0G1
1L+
(2.10)
12 1 2 8 9 10 11 13 14 15 8 9 10 11 13 14 15
X1b 12 1 2 8 9 10 11 13 14 15
X1a 8 9 10 11 13 14 15
12 1 2 3 4 5 6 7 7 3 4 5 6
X1a X1b
12 1 2 3 4 5 6 7 7 3 4 5 6
PE
(2.13) 1
0H1
2
1L-
(2.11)
1 2 1 2 1 2 1 2
1.7 1.11 1.5 1.4
3 4 3 4 3 4 3 4
1.7 1.11 1.5 1.4
5 6 5 6 5 6 5 6
1.7 1.11 1.5 1.4
13 14 13 14 13 14 13 14
.3 .10 .4 .2
1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 10
X2 X3
1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 10
X9 X10 X8
X6
X7
X4 X4
RJ45
X2
M12
1 2 1 2 1 2
1 2 1 2 1 2
1 2 1 2 1 2 1 2
1 2 1 2 1 2 1 2
RJ45
RJ45
1 3 2 4
M12 TD+ TD- RD+ RD-
0G1
1 3 5
0Q1
2 4 6
1 2 3 4 5 1 7 8 3 9 2
x1 x2
PE 1 2 3 4 5 1 7 8 3 9 2
M
3
CEE 16A
1L+
(1.10) 5 4 3
5
2 2
x1 5 4 3
5
1 1
6
6 6
x1
6
12 1 2 8 9 10 11 13 14 15 8 9 10 11 13 14 15
X1b 12 1 2 8 9 10 11 13 14 15
X1a 8 9 10 11 13 14 15
12 1 2 3 4 5 6 7 7 3 4 5 6
X1a X1b
12 1 2 3 4 5 6 7 7 3 4 5 6
1
PE1 0H1
(1.13) 2
1L-
(1.12)
1 2 1 2 1 2
1.6 1.5 1.4
3 4 3 4 3 4
1.6 1.5 1.4
5 6 5 6 5 6
1.6 1.5 1.4
13 14 13 14 13 14
.9 .3 .2
1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 10
X2 X3
1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 10
X9 X10 X8
X6
X7
X4 X4
RJ45
X2
M12
1 2 1 2 1 2
1 2 1 2 1 2
1 2 1 2 1 2 1 2
1 2 1 2 1 2 1 2
RJ45
RJ45
1 3 2 4
M12 TD+ TD- RD+ RD-
0 1 2 3 4 5 6 7 8 9
09.10.2014
TI FQI
101 100
-1B1 -1B3
temperature sensor
Flow meter
CWI/F CWI/F
-1Y1
10W | 24V DC
ics-standard-Normblatt-MCAD-A3-Quer-V1
CWO CWO
-H1 -F1
solenoid valve y-strainer
PFO PFO
-W1 -R1
heat exchanger non-return valve -R2
non-return valve
-H2
3 way switchable block
-P2
TZ+ PZ+ refeeding pump
-2B1
overtemp stat 502 501
-2B2
pressure switch
-1M2
48W | 5,5A | 24V
-P1 el -1E1
process-pump 3 x 3kW | 415V | 7,23A
1 3 5
0Q1
2 4 6
1 2 3 4 5 1 7 8 3 9 2
x1 x2
PE 1 2 3 4 5 1 7 8 3 9 2
M
3
CEE 16A
1L+
(1.10) 5 4 3
5
2 2
x1 5 4 3
5
1 1
6
6 6
x1
6
12 1 2 8 9 10 11 13 14 15 8 9 10 11 13 14 15
X1b 12 1 2 8 9 10 11 13 14 15
X1a 8 9 10 11 13 14 15
1 2 3 12 4 5 6 7 7 3 4 5 6
X1a X1b
1 2 3 12 4 5 6 7 7 3 4 5 6
1
0H1
2
PE1
(1.13)
1L-
(1.12)
1 2 11 14 1 2 1 2
1.6 1.9 1.5 1.4
3 4 12 3 4 3 4
1.6 1.5 1.4
5 6 21 24 5 6 5 6
1.6 1.5 1.4
13 14 22 13 14 13 14
.9 .3 .2
1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 10
X2 X3
1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 10
X9 X10 X8
X6
X7
X4 X4
RJ45
X2
M12
1 2 1 2 1 2
1 2 1 2 1 2
1 2 1 2 1 2 1 2
1 2 1 2 1 2 1 2
RJ45
RJ45
1 3 2 4
M12 TD+ TD- RD+ RD-