Professional Documents
Culture Documents
Hospital Fire Safety
Hospital Fire Safety
Requirements for
Protection and Compliance
March 10, 2020
Electrical Systems. All electrical installations must comply with NFPA 70:
National Electrical Code (NEC)® and the specific requirements of
Chapter 6 of NFPA 99. When generator sets are utilized where an
alternate power source is required, they must be installed and
maintained following NFPA 110: Standard for Emergency and Standby
Power Systems.
To
promote hospital fire safety and prevent surgical fires, “the U.S. Food and
Drug Administration has launched an education program for medical
professionals using safeguards found in NFPA codes and standards.”
Source: NFPA Journal
Fire safety guidelines for hospitals
Individual fire protection and life safety measures are part of a system.
No single fire protection feature can be effective without other
supporting elements. For example, a fire sprinkler system without an
alarm or compartmentation may not be able to do its job adequately.
Without an alarm, there would be no notification that a fire is occurring
and that action should be taken. Without compartmentation, the fire
could grow unimpeded, and it might quickly overcome the capabilities of
a fire sprinkler system.
These surfaces must remain intact to ensure that their required fire-
resistance rating is in place. Any openings in a fire-resistance-rated
wall must be adequately sealed or protected. This requires
appropriately rated fire doors, windows, and transfer grilles.
8.3.3.1 General. Every opening in a fire barrier shall be protected to limit the
spread of fire from one side of the fire barrier to the other.
8.3.4.2.1 Penetrations for cables, cable trays, conduits, pipes, tubes, combustion
vents and exhaust vents, wires, and similar items to accommodate electrical,
mechanical, plumbing, and communications systems that pass through a wall, floor,
or floor/ceiling assembly constructed as a fire barrier shall be protected by a
firestop system or device.
S
ource: DTNEXT
Fire extinguishers and specialized fire suppression
systems
Fire extinguishers are required throughout the building. These must be
selected, placed, inspected, tested, and maintained following the rules
in NFPA 10: Standard for Portable Fire Extinguishers.
Quarterly evacuation drills are required for each shift, and records of
these drills must be maintained. Additionally, hospital staff should be
aware of and sustain general housekeeping standards. These activities
include maintaining clear access to exits, enforcing “no smoking”
policies, making sure decorations in halls and patient rooms are fire
resistant and do not exceed allowed limits, and ensuring soiled linens
and trash are regularly emptied and not permitted to accumulate
beyond allowed maximums (0.5 gallons per room, 32 gallons total in a
protected area).