Professional Documents
Culture Documents
TRACKSIDE LV SWITCH Room 3 (EAL) - (L5-P19) - Cylinder Ak
TRACKSIDE LV SWITCH Room 3 (EAL) - (L5-P19) - Cylinder Ak
00 (FM-200)
UL: EX4674 / Component of FM Approved System
Consolidated Report
Customer Information
Company Name: Intergral E&M Engineering Limited
Address:
Phone:
Contact:
Title:
Project Data
Project Name: MTR-ADM-1124
Designer: IEM
Number: [L5-P19]
Account: 1124_B_ADM_BKJ_F96_533_Rev.C
Location: Hong Kong
Description: TRACKSIDE LV SWITCH Room 3 (EAL) (Cylinder A)
Enclosure Report
Page: 1 of 7
Consolidated Report
Adjusted: 7.20 % Non-permeable: 24.65 m ³
Minimum: 7.00 % Total Volume: 88.43 m ³
Min. Agent Required: 51.44 kg
Adjusted Agent Required: 53.00 kg
Agent: FM-200
(FM-200 is a Trademark of Chemours)
Cylinder Name: 81 L Cylinder w/LLI
Cylinder Part Number: 90-100201-101
Agent Per Cylinder: 53.00 kg
Fill Density: 0.655 kg / l
Number of Main Cylinders: 1
Number of Reserve Cylinders: 0
Page: 2 of 7
Consolidated Report
Parts Report
Pipe &
Fittings Type Diameter Length Elbows (90) Elbows (45) Tees Unions
40T 20 mm 0.90 m 1 0 0 0
40T 25 mm 2.25 m 1 0 0 0
40T 32 mm 32.64 m 10 0 1 0
Other
Objects Name Quantity Part Number
50 mm Valve Outlet Adapter 1 283905
Enclosure Number: 1
Enclosure Name: Main Room
Minimum Design Concentration: 7.00%
Adjusted Design Concentration: 7.20%
Predicted Concentration: 7.20%
Maximum Expected Agent Concentration: 8.04% (At 38.0 C)
Page: 3 of 7
Consolidated Report
Maximum Allowed Enclosure Pressure: 100000.00 Pa
Installed Vent Area: 0.00 m²
Estimated Free Vent Area Required (Negative): -1.00 m²
Estimated Free Vent Area Required (Positive): -1.00 m²
Predicted Enclosure Pressure (Negative): N/A
Predicted Enclosure Pressure (Positive): N/A
Page: 4 of 7
Consolidated Report