You are on page 1of 1

N

IMPORTANT:

This drawing is the copyright © of ChapmanBDSP and shall


not be copied or reproduced without permission.

This drawing shall not be scaled.

Unless stated otherwise, all dimensions are in millimetres.


600(W)x600(H)x350(D)mm Electrical
Manhole/Drawpit 300(W)x300(H)x300(D)mm Electrical Where applicable, all dimensions shall be checked by the
Manhole/Drawpit contractor onsite, prior to commencement of any works.
First Floor

This drawing shall be read in conjunction with all other


drawings and the services specification document(s).
22 WAY TP&N All materials and workmanship shall conform with the
Distribution Board for Prospect
Park Lighting and Small Power 50mm relevant British & European Standards, Specifications and
100mm
XLPE/SWA/LSF Cables
200x50mm Cable Tray 50mm
50mm Codes of Practice.
50mm
Ground
Light Fittings 100mm
50mm 100mm
500mm
50mm
100mm Ø Cable Duct for NOTES:
600(W)x600(H)x300(D)mm
Draw Pit External Lighting and
Power 1. PLEASE REFER TO DRAWING NUMBER E-2000 E-XX-000-XX-01
& E-2001FORFORELECTRICAL
ELECTRICALSYMBOLS.
XLPE/SWA/LSF Cables 2. SYMBOLS.
THE CONTRACTOR SHALL ENSURE THAT FINAL LOCATIONS OF ALL POWER
XLPE/SWA/LSF Cables 2. BOLLARDS,
THE CONTRACTOR
MANHOLES SHALL ANDENSURE
DRAWTHATPITS FINAL
ARE CONFIRMED
LOCATIONSBY OFTHE
ALL ARCHITECT.
POWER
3. POINTS,
THIS DRAWING
MANHOLES INDICATES
AND DRAWPRIMARY
PITSCONTAINMENT
ARE CONFIRMED ONLY.
BY THE
THEARCHITECT.
CONTRACTOR IS
3. TO SUPPLY
THIS DRAWING ANDINDICATES
INSTALL SECONDARY
PRIMARY CONTAINMENT
CABLE CONTAINMENT ONLY. THESYSTEMS,
CONTRACTOR
WHICH
SHALL
ARE NOTSUPPLY
SHOWN ANDON INSTALL
THIS DRAWING,
SECONDARY TO CABLE
COMPLETE
CONTAINMENT
THE INSTALLATION.
SYSTEMS, WHICH
4. ARE
THE NOT
CONTRACTOR
SHOWN ON SHALL
THISCOORDINATE
DRAWING, TO ALLCOMPLETE
ELECTRICALTHECONTAINMENT/DUCTS
INSTALLATION.
4. WITH
THE CONTRACTOR
OTHER SERVICES SHALL WITHIN
COORDINATE
THE AVAILABLE
ALL ELECTRICAL
FLOOR BUILD-UP.
CONTAINMENT/DUCTS
5. WITH
ALL ELECTRICAL
OTHER SERVICES
ACCESSORIES
WITHININSTALLED
THE AVAILABLE
SHALLFLOOR
BE WEATHER
BUILD-UP.
PROOF TO IP
5. 66/68.
ALL ELECTRICAL ACCESSORIES INSTALLED SHALL BE WEATHER PROOF TO IP
DETAIL A: (P) POP UP POWER - PUPS 02 DETAIL B: TYPICAL ELECTRICAL DETAIL SECTION FOR DETAIL C: TYPICAL ELECTRICAL MANHOLE/DRAWPIT (DP-1). FINISH DETAIL D: TYPICAL ELECTRICAL MANHOLE/DRAWPIT (DP-2). FINISH 6. IT
66/68.
IS THE RESPONSIBILITY OF THE CONTRACTOR TO ENSURE ALL POWER AND
4040 FLOOR BOX - FOR COVER DETAILS GROUND FLOOR EXTERNAL LIGHTING AND POWER TO MANHOLE COVER BY LANDSCAPING CONSULTANT. TO MANHOLE COVER BY LANDSCAPING CONSULTANT. 6. IT
ASSOCIATED
IS THE RESPONSIBILITY
SECONDARYOF CONTAINMENT
THE CONTRACTOR REQUIREMENTS
TO ENSUREHAVE ALL POWER
BEEN AND
COORDINATED
ASSOCIATED SECONDARY
AND INSTALLEDCONTAINMENT
FOR ALL ITREQUIREMENTS
DATA POINT WITHIN HAVERETAIL
BEEN FLOOR
AND INSTALLATION PIT DISTRIBUTION BOX
COORDINATED.
AND POWER BOLLARDS.
REFER TO LANDSCAPING ENGINEERS 7. THE CONTRACTOR IS TO ALLOW FOR ALL CABLE ROUTES AND FINAL CIRCUIT
LOCATIONS TO MOVE UP TO 3 METERS PRIOR TO FINAL INSTALLATION OR
DRAWINGS & INFORMATION. SIGN-OFF FROM THE CLIENT'S REPRESENTATIVE.
8. THE CONTRACTOR SHALL PROVIDE ADEQUATE MANHOLES/ DRAWPITS FOR ALL
EXTERNAL LIGHTING, SMALL POWER AND DATA.
3X 9. THE CONTRACTOR SHALL NOTE THAT THE FINAL LOCATION OF ALL MANHOLES
D1/07 AND DRAWPITS ARE TO BE COORDINATED AND AGREED ON SITE WITH THE
DP-2 LANDSCAPE ARCHITECTS/ ENGINEER.
DB/2H/00/04/3L1 10. THE CONTRACTOR IS SHALL
TO ALLOW
CONSTRUCT
FOR ALLA 150MM
EXTERNAL CONCRETE
ELECTRICAL
PLINTH
CIRCUITS
FOR THE
TO BE
MOUNTING
FED FROM AN OFRCBO
ALL EXTERNAL
(MCB TYPEPOWERB) 30MABOLLARDS.
FOR LIGHTING AND SMALL POWER.
4X 11. WP
THEINDICATES
CONTRACTOR ITEM ISTO
TOBEALLOW
PROTECTED
FOR ALLTO EXTERNAL
IP66/68 DEGREE
ELECTRICAL
OF INGRESS
CIRCUITS TO BE
D1/07 DB/2H/00/04/3L2 FED FROM AN RCBO (MCB TYPE B) 30MA FOR LIGHTING AND SMALL POWER.
PROTECTION.
12. WP
THEINDICATES
CONTRACTOR ITEM SHALL
TO BEALLOW
PROTECTED
FOR LIAISON
TO IP66/68
AND DEGREE
COORDINATION
OF INGRESS
WITH ICT
L1/04
PROTECTION.
CONSULTANT.
13. ANY
THE CONTRACTOR
DISCREPANCIES SHALL
ARE TOALLOW
BE REPORTED
FOR LIAISON TO THE
ANDENGINEERS.
COORDINATION WITH ICT
14. CONSULTANT.
ALL ELECTRICAL INSTALLATIONS SHALL COMPLY WITH THE CURRENT BS 7671 -
os DB/2H/00/04/2L1 14. IET
ANYWIRING
DISCREPANCIES
REGULATIONS.ARE TO BE REPORTED TO THE ENGINEERS.
a DB/2H/00/04/2L3 600x600mm LV TRENCH FOR LV 15. WHERE
ALL ELECTRICAL
DUCTS TO INSTALLATIONS
BE CAST-IN, LIAISE
SHALLWITH
COMPLYTHE MAIN
WITH THE
CONTRACTOR
CURRENT BS AT 7671
VERY -
IEE WIRING
EARLY STAGESREGULATIONS.
OF CONSTRUCTION TO LAY THE DUCTS OR CONDUITS AS
CONNECTION TO PLOT 2 BY 16. REQUIRED.
WHERE DUCTS TO BE CAST-IN, LIAISE WITH THE MAIN CONTRACTOR AT VERY
WESTERN POWER DISTRIBUTION. D2/07 16. EARLY
WHERESTAGES
SHOWN OFONCONSTRUCTION
SOFT LANDSCAPING,TO LAYDUCTS
THE DUCTS
SHALLORBECONDUITS
LAID ON AAS BED OF
D1/07 CONTRACTOR TO COORDINATE REQUIRED.
SOFT SAND AND MUST BE ABOVE ATTENUATION TANK. AT MIDPOINT BETWEEN
AND REFER TO WESTERN POWER 17. WHERE
TOP OF DUCT
SHOWN & GROUND
ON SOFT LANDSCAPING,
SURFACE PROVIDE DUCTS WARNING
SHALL BETAPE.
LAID ON A BED OF
SPECIFICATION AND 17. CONTRACTOR
SOFT SAND AND SHALL
MUST ENSURE
BE ABOVE
THATATTENUATION
ALL CABLES TOTANK.BE TERMINATE
AT MIDPOINT WITH BETWEEN
WATER
PROOF
TOP OFIP66/IP68
DUCT & GROUND
GLANDS SURFACE
FOR EXTERNAL
PROVIDELIGHTING
WARNINGANDTAPE.
POWER AND THE CABLE
2NO. 100mm Ø BURIED IN U1/02 REQUIREMENTS.
18. DUCTS
CONTRACTOR
ARE SEALED.
TO ENSURE ALL CABLES TO BE TERMINATE WITH WATER PROOF
GROUND RIDGI-DUCTS 18. IP66/IP68
CONTRACTOR GLANDS
SHALL TORUN
EXTERNAL
ALL CONTAINMENT
LIGHTING AND ABOVE
POWER STRUCTURE
AND THE CABLE
SLABS/DUCTS
BEAMS
(FLEXIBLE) FOR LIGHTING 600x600mm LV TRENCH FOR LV ARE SEALED.
AND COORDINATE WITH STRUCTURE ENGINEERS WHERE THIS IS NOT POSSIBLE.
CONNECTION TO PLOT 2 BY 19. DUCT
CONTRACTOR
ACCESS BOXES
SHALL RUNCOVER ALLSHALL
CONTAINMENT
BE TO THE ABOVE
ARCHITECTS
STRUCTURE
SPECIFICATION
SLABS/ BEAMS
AND
2X WESTERN POWER DISTRIBUTION. AND COORDINATE
ACCEPT THE FLOORWITH TILES/STONES.
STRUCTURE ENGINEERS WHERE THIS IS NOT POSSIBLE.
D1/07 20.DUCT
20. ALL EXTERNAL
ACCESS BOXES
LIGHTING,
COVERFLOOR
SHALLBOX,
BE TO
MANHOLE
THE ARCHITECTS
AND DREW SPECIFICATION
PITS TO BE LINKED
AND
CONTRACTOR TO COORDINATE ACCEPT
TO EXTERNAL
THE FLOOR
DRAINAGE
TILES/STONES.
SYSTEM.
AND REFER TO WESTERN POWER 21. CONTRACTOR SHALLIS TO REFER
REFERTO TOARCHITECTS
THE LANDSCAPING
FOR FINAL
ARCHITECTS
NUMBER LDA ANDDRAWINGS
POSITION
SPECIFICATION AND FOR
OF ALL
ALLPOWER
FINAL SETTING
BOLLARDS. OUT DETAILS AND SECTIONS.
REQUIREMENTS. 22. CONTRACTOR
ALL EXTERNAL SHALL
LIGHTING,
REFERFLOOR
TO STRUCTURE
BOX, MANHOLE ENGINEER
AND DRAWINGS
DREW PITS TO AND BE LINKED
D1/07 SECTIONS.
TO EXTERNAL DRAINAGE SYSTEM.
U1/02
23. CONTRACTOR SHALL REFER TO SPECIALIST THE LANDSCAPING
LIGHTING ARCHITECTS
CONSULTANTS LDA DRAWINGS
LIGHTING
FOR ALL FINAL
LAYOUTS, SECTIONS
SETTINGANDOUTENSURE
DETAILS
THATANDTHESECTIONS.
FINAL CONTAINMENT ROUTE AND
24. LOCATION
CONTRACTOR IS COORDINATED.
SHALL REFER TO STRUCTURE ENGINEER RBG DRAWINGS AND
24. CONTRACTOR
SECTIONS. TO REFER TO CBDSP LIGHTING LAYOUT FOR LIGHTING CIRCUITS.
25. CONTRACTOR
THIS DRAWINGSHALL SHALLREFER
BE READ
TO SPEIRS
IN CONJUNCTION
AND MAJORWITH LIGHTING
ALL CBDSP
LAYOUTS,
DOCUMENTATION
SECTIONS AND ENSURE AND FINAL
SPECIFICATION.
CONTAINMENT ROUTE AND LOCATION BE
26. COORDINATED.
THE CONTRACTOR SHALL ALLOW FOR SEPARATE ELECTRICAL METER FOR EACH
2X 26. CONTRACTOR
THREE PHASE POWER
TO REFER POINT.
TO CBDSP LIGHTING LAYOUT FOR LIGHTING CIRCUITS.
D1/07 27. THE
THISCONTRACTOR
DRAWING SHALL SHALLBE READ
ALLOW INFOR
CONJUNCTION
ELECTRICALWITHMETERSALLTOCBDSP
POWER POINTS.
28. DOCUMENTATION
THE CONTRACTOR AND SHALLSPECIFICATION.
ALLOW FOR DIN/RAIL SINGLE PHASE AND THREE PHASE
METERS TO BE INSTALLED FOR EACH EXTERNAL POWER POINT CIRCUIT WITHIN
EACH DISTRIBUTION BOARD.
U1/02
D1/07

300x300x300mm DRAW PIT FOR


STREET HIGHWAY LIGHTING BY
GLOUCESTER COUNCIL

C1/01
REFER TO DETAIL C 4X
D1/07
DP-2 Legend

DP-1 MANHOLE/DRAWPIT (FINISH TO FLOOR BOX COVER BY


DB/2H/00/04/1L3 DP-1
LANDSCAPING CONSULTANT)
DIMENSIONS: 600mm L x 600mm W x 350mm D
STREET HIGHWAY LIGHTING BY
MANHOLE/DRAWPIT (FINISH TO FLOOR BOX COVER BY
GLOUCESTER COUNCIL DP-2
LANDSCAPING CONSULTANT)
4X DIMENSIONS: 300MM L X 300MM W X 330MM D
D1/07 DB/2H/00/04/2L2
P POP UP POWER SUPPLY. FLOOR BOX (FINISH TO FLOOR
DP-2
REFER TO DETAIL D BOX COVER BY LANDSCAPING CONSULTANT)
1 x 32A TP&N COMMANDO SOCKET (IP67)
1 x 16A SP&N COMMANDO SOCKET (IP67)
1 RJ45 CONNECTOR (WEATHERPROOF)

RIDGI-DUCT (100mm Ø CABLE DUCT INSTALLED


WITHIN BUILDUP AREA).

4X
3NO. 100mm Ø BURIED IN D1/07
GROUND RIDGI-DUCTS
(FLEXIBLE) FOR LIGHTING

REFER TO DETAIL A

DB/2H/00/04/15
REFER TO DETAIL C

REFER TO DETAIL C
U1/02 DP-1
22 WAY TP&N EXTERNAL
3NO. 50mm Ø BURIED IN GROUND 2X LIGHTING & POWER
RIDGI-DUCTS (FLEXIBLE) FOR D1/07 DISTRIBUTION BOARD
LIGHTING 14 WAY TP&N FOR
LIGHTING
8 WAY TP&N FOR POWER
U1/02
DB/2H/00/04

6NO. 150mmØ STEEL CABLE


DUCTS FOR HOTEL LV SUPPLY
DB/2H/00/04/1L2 DP-1
REFER TO DETAIL D
C1/01 4No. 100mm Ø BURIED IN GROUND 2X 4NO. 150mmØ INCOMING CABLE
RIDGI-DUCTS (FLEXIBLE) FOR D1/07
DUCTS FOR HOTEL COMMS.
LIGHTING.
THE COVER OF THE MANHOLE TO
FLEXIBLE DUCT TO RUN
DP-2 LANDSCAPING CONSULTANT.
UNDERNEATH THE TRENCH

600x600x600mm MANHOLE.
D1/07 FOR HOTEL COMMS

UP

2NO. 100mm Ø BURIED IN


GROUND RIDGI-DUCTS
(FLEXIBLE) FOR LIGHTING

6NO. 150mmØ STEEL CABLE


DUCTS FOR CAR PARK LV
SUPPLY

300x300x300mm DRAW PIT FOR


STREET HIGHWAY LIGHTING BY
GLOUCESTER COUNCIL
P01 MAY 21 TENDER ISSUE HH
Rev Date Description Appr
DP-2
Status

C1/01 STAGE 4
Client
STREET HIGHWAY LIGHTING BY REEF GROUP
GLOUCESTER COUNCIL 600x600mm LV TRENCH FOR LV
CONNECTION TO PLOT 2 BY
WESTERN POWER DISTRIBUTION. Project
CONTRACTOR TO COORDINATE
AND REFER TO WESTERN POWER KINGS QUARTER THE FORUM
SPECIFICATION AND
REQUIREMENTS.

Drawing Title
PLOT 2 & 4
ELECTRICAL SERVICES
3NO. 50mm Ø BURIED IN GROUND EXTERNAL CONTAINMENT,
RIDGI-DUCTS (FLEXIBLE) FOR
LIGHTING SMALL POWER & LIGHTING
U1/02 SHEET 3 0F 5

www.chapmanbdsp.com info@chapmanbdsp.com
U1/02 Drawn Engineer Checked Date origin

REFER TO DRAWING NUMBER - 55415-CBD-XX-00-DR-E-2040-5 2NO. 100mm Ø BURIED IN


GROUND RIDGI-DUCTS
CAD

Scale @A0
NT

File/BIM ref
HH MAY 21

(FLEXIBLE) FOR LIGHTING NTS 55415-CBD-XX-00-DR-E-2040

Sheet number Revision

55415-CBD-XX-00-DR-E-2040-3 P01