Professional Documents
Culture Documents
Aerospace Engineering Lab 1 Document
Aerospace Engineering Lab 1 Document
2. Basic theory
Combustion occurs in the presence of fuel and air under the right conditions
(including ignition). Consider the equation of the chemical reaction for the
combustion of methane 𝐶𝐻 in the gaseous form as follows:
𝐶𝐻 + 2𝑂 → 𝐶𝑂 + 2𝐻 𝑂
The chemical reaction is complete when the volume ratio of 𝐶𝐻 /𝑂 is 1:2. If this
ratio is more than 1:2, the combustion is rich in fuel; conversely, if this ratio is less
than 1:2, the combustion process is fuel-poor. In addition, the combustion of the fuel
and air mixture depends on the heat load (Burner loading - heat released per unit
area) at the place where the flame occurs. Heat load BL (MW/m2) is calculated as
follows:
𝑀𝐽
𝑇ℎ𝑒 𝑐𝑎𝑙𝑜𝑟𝑖𝑓𝑖𝑐 𝑣𝑎𝑙𝑢𝑒 𝑜𝑓 𝑓𝑢𝑒𝑙 × 𝑇ℎ𝑒 𝑓𝑙𝑜𝑤 𝑜𝑓 𝑓𝑢𝑒𝑙(𝑚 /𝑠)
𝐵𝐿 = 𝑚
𝑃𝑙𝑎𝑖𝑛 𝐴𝑟𝑒𝑎 𝑜𝑓 𝐶𝑜𝑚𝑏𝑢𝑠𝑡𝑖𝑜𝑛 (𝑚 )
The combustion process can be qualitatively assessed by the shape and color of the
flame. The stability limit of the combustion process includes the following stages:
- The rich-fuel combustion process shows in the form of a yellow flame. When
maintaining the flow rate of the fuel and increasing that of air, the flame turns
from yellow to blue, from root to tip. The limit state of the transition is when
only the tip of the flame remains yellow (Yellow tipping - YT). Thus, this is
the limit state to maintain combustion with a sufficient mixing ratio for
complete combustion.
- Further increase in the airflow rate will result in complete blue flame. At an
appropriate ratio, the blue flame will rise from the surface of the fusion tube
(Lift off - LO). This phenomenon occurs when the velocity of the combustion
mixture is close to the flame propagation velocity. If the airflow rate is
continued to increase, the velocity of the mixture will be greater than the
flame propagation velocity, the flame will rise from the surface and be
extinguished. This is the limit state of the fuel-poor combustion process and
the transition state to end the combustion process.
- Light back (LB) occurs when the mixing ratio exceeds the value of the LO
phenomenon. When the heat load is low, if the fuel flow rate is kept
unchanged and the airflow rate is increased, the flame propagation velocity
will be greater than the velocity of the combustion mixture. The flame
burning in the fuel-poor state tends to move back towards the source of the
combustion mixture to maintain combustion if the place which consists of the
combustion is large enough.
To determine the stability limit of the flame, it is necessary to burn a mixture of fuel
and air with different volume ratios. Then express this ratio according to the heat
load with different flame states (Fuidge diagram – example Figure 1).
Figure 1. Fuidge diagram of the stability limit of the fuel and air mixture combustion
3. Experiment equipment
C551 combustion test equipment is described in Figure 2, including a flow control
panel, a fuel source (gas tank 50% Propane + 50% Butane, calorific value 46 MJ/m 3),
a set of 4 mixing tubes with different diameters, plastic tubes for observing and
measuring the flame propagation velocity, and ignition system.
Equipment operation:
- Connect the power source, turn on the switch and let the exhaust fan run.
Open the gas tank valve, and press the gas pump button if necessary.
- On the control panel, first open the air valve, and the gas valve later. Ignites
the mixture.
- Air and fuel flow are measured on a centimeter scale, marked from the top of
the cone. This value is converted to 𝑚 /𝑠 by using the diagram in Figure 3.
However, in Figure 3, there are only two types of fuel: Propane or Coal Gas
and Methane. For a mixture of propane and butane fuel, the actual flow rate
will be the actual flow rate in the case of propane multiplied by the factor K
(referred to in Figure 4). For example, if the fuel used is a mixture of 50%
propane and 50% Butane, the K factor will be about 1.06. If the flow column
is only 8 cm, using the propane curve in Figure 3 to find 0.04 × 10 𝑚 /𝑠 ,
the actual flow rate for this case will be 1.06 × 0.04 × 10 𝑚 /𝑠.
- Lock all the valves, switch off, and turn off the power source after finishing
the experiment.
Safety Note:
- Always check for gas leaks at the beginning of the experiment.
- Set up a fire extinguisher near the test site.
- Always open the air valve before the gas valve.
- Do not leave the gas valve open without combustion. Once the gas
valve is opened, it must be ignited immediately to avoid the “fireball”
phenomenon.
- Mixing tubes can be extremely after the test. Protective tools are
required.
- Switch off, lock the valves on the control panel, unplug the power, and
close the gas valve at the end of the experiment.
Figure 3. The relation between the flow rate on the scale (cm) and the actual flow rate (m 3/s) of fuel
and air
Figure 4. Correction factor K for the mixture of Propane and Butane
Figure 5. Flame propagation velocity under the ambient air temperature and pressure condition for 3
types of fuel: Propane, Methane, and coal gas
YT
3 d = … mm 0.5 LO
LB
0.5
6.2. Lesson 2
During data recording and processing:
Fuel
Fuel Air/
flow Airflow Airflow
flow Length Time Velocity Fuel
rate rate rate (10-
rate (m) (s) (m/s) mixing
(10-3 (cm) 3
m3/s)
(cm) ratio
m3/s)
THE SURVEY OF THE CENTRIFUGAL FAN
CHARACTERISTICS 1
This experiment includes 4 sub-tests:
- Lesson 1: The survey of the centrifugal fan characteristic curve
- Lesson 2: The survey of the centrifugal fan dynamical similarity
- Lesson 3: Determine the system characteristic curve
- Lesson 4: Change the impeller
In this course, students are given Lessons 1 and 2. The remaining two lessons will
be done in the Aeronautical Experiment 1 course.
1. Hydraulic machine
A hydraulic machine is a device that works by exchanging energy with the fluid
flowing through the machine, for example, pumps, turbines, fans, compressors... In
this lesson we focus on a fan – a hydraulic machine with fluid interaction is air.
Hydraulic machines can be classified in many different ways:
According to how they exchange energy with the fluid
Receive the energy of the fluid, and convert it into mechanical energy
(water turbine, wind turbine ...)
Supply power for fluids (pumps, fans, compressors, etc.)
According to the principle of interaction with fluids in the energy-exchange
process
The turbomachinery/ van machine uses the rotation of an impeller
(including the blades) to exchange kinetic and potential energy with
the fluid. The fluid velocity, outlet, and inlet pressure are
characteristic parameters for determining the operating state. Divided
into 2 subclasses: centrifuges and axial machines.
The volumetric machine exchanges energy with the fluid on the
principle of compressing the liquid in a closed volume under the
effect of hydrostatic pressure, with the form of energy exchange
being pressure. The volumetric machine is capable of working with
high pressure but with a small flow. Machine speed is a parameter
that determines machine operation.
Depending on the purpose (head height, flow rate), the appropriate type of hydraulic
machine is chosen. Figure 6 shows the distribution of head by the flow rate of 3
popular types of hydraulic machines (volumetric machine, centrifugal vane machine,
axial guide vane machine) used in water pumps.
For centrifugal vane machines (Figure 7), the fluid enters the center of the rotors
with rotating blades and pushes the centrifuge outside which then is collected by a
collection chamber, and led to the exit. At high rotational speed, the fluid receives
large kinetic energy. The pressure difference between the outlet and inlet is produced
by the conversion of the kinetic energy into pressure. Centrifugal vane machines are
used in many different fields. However, there are some limitations in terms of low
static pressure, noise, etc.
2. Experiment equipment
The experimental set includes a centrifugal fan model as shown in Figure 8, an IDF7
data processor, and 2 impellers with different blades which are set in various
directions. The device is connected to the computer via the USB port.
FM40 operates with one of two available impellers (backward-curved blades and
forward-curved blades) with rotational speed controlled by an interactive program.
The impeller is placed in the manifold and connected to two ducts (one is a suction
pipe, and one is a discharge pipe) placed at right angles to each other. On these two
pipes are sensors and other devices as follows (Figure 9):
Suction pipe: sensor measures inlet pressure and pressure before the fan,
temperature sensor, honeycomb grid stabilizes the flow before it enters the
fan.
Discharge pipe: sensor measures the fan outlet pressure, and a flow control
device.
There is also a torque sensor on the motor shaft.
Figure 9. Sensors and their function on the suction and discharge pipe
Note:
The flow control device does not keep a steady flow in case of being
nearly closed and small flow but will be more stable as the opening
gradually increases.
FM40's two impellers are numbered: (1) backward-curved blades and (2) forward-
curved blades as shown in Figure 10.
Set constants
Sensor values
Note:
Set the value of the sensor to 0 before recording data.
2.3. Noteworthy quantities
Constants:
Impeller’s diameter D = 180 mm
Flow rate coefficient Cd = 0.596
Atmospheric pressure Pa = 101 kPa
Gravity acceleration g = 9.81 m/s2
The diameter of the suction pipe d1 = 95 mm
The diameter of the discharge pipe d2 = 75 mm
Quantities Symbol
Measured values
Head coefficient: 𝐶 =
(8)
Dynamic similarity helps us to easily control the factors affecting the results with
high accuracy. The accuracy is higher when more and more influencing factors are
considered in the similarity model such as friction, roughness, etc. Two fans are
considered to be dynamically similar with the following conditions:
- Have the same number of blades
- Have the same angular dimensions
- The linear dimensions are proportional to each other
Note:
Students prove the formulas from (6) to (8). Set up the formula for the
quantities of pressure, power, and flow rate of the 1st fan type from the
2nd fan type (supposing that we know its conditions).
4.3. Experiment operation
Do the same as Section 3.3 but with 2 other engine speeds.
Note:
Students manually change the engine speed from rpm to FS according
to a linear ratio.
Results can be rounded properly during operation.
HYDRAULIC SYSTEM 1
This experiment includes three lessons:
- Lesson 1: Investigate the characteristic curve of the pump
- Lesson 2: Safety valve
- Lesson 3: Adjustable Throttle valve
- Lesson 4: Two-way hydraulic cylinder
- Lesson 5: Flow control valve
This course will cover the first and second lessons.
1. Theory of Hydraulics
Students revive their knowledge of hydraulics through the document Summary of
hydraulic theory.
2. Experiment equipment
The experiment equipment system includes the source station (oil pump and tank -
Figure 16), volumetric cylinder, pipes, valves, pressure gauges/ pressure indicators,
etc. as shown in Figure 15.
Average
Volume V Pumping Pressure P Flow rate
Valve level flow rate Q
(l) time t (s) (bar) Q (l/s)
(l/s)
Lesson 2:
- Safety valve at 25 bar
Volume V (l) Pressure P (bar) Pumping time t (s) Flow rate Q (l/s)
15
20
25
Volume V (l) Pressure P (bar) Pumping time t (s) Flow rate Q (l/s)
15
20
25
30
Volume V (l) Pressure P (bar) Pumping time t (s) Flow rate Q (l/s)
15
20
25
30
35
EXPERIMENT OF FLOW-MEASURING
APPARATUS
1. Experiment objectives
2. Basic theory
2.1. The steady-flow energy equation
For steady, adiabatic flow of an incompressible fluid along a stream tube, as shown
in Figure 3, Bernoulli's equation can be written in the form:
+ +𝑧 = + + 𝑧 + ∆𝐻 (1)
Where
: is termed the hydrostatic head
(Rotameter)
(Wide-angle
diffuser) (Orifice meter)
(Head tubes)
(Flow inlet)
From continuity: 𝜌𝑉 𝐴 = 𝜌𝑉 𝐴
/
The discharge: 𝑄 = 𝑉 𝐴 = 𝐴 ( )
−
/ 𝜌𝑔 𝜌𝑔
With the apparatus provided, the bores of the meter at (A) and (B) are 26mm and 16mm
respectively. Thus:
𝐴𝐵
= 0.38 and 𝐴𝐵 = 2.01 × 10 (𝑚 )
𝐴𝐴
1
Since g = 9.81 m/s2 and , are the respective heights of the manometric tubes A and B
𝜌𝑔 𝜌𝑔
in meters, we have from Equation (2):
𝑄 = 9.62 × 10 (ℎ − ℎ ) 𝑚3 ⁄𝑠
1/2
0.962 hA hB
The mass flow: m kg/s
h hB
1/2
e.g. if hA 375 mm and hB 110 mm , therefore A
0.51 and
0.962 0.51 0.49 kg/s
m
(The corresponding weigh tank assessment was 0.48 kg/s)
b) Orifice Meter
Between tapping’s (E) and (F) ∆H12 in Equation (1) is by no means negligible. Re-
writing the equation with the appropriate symbols:
VF2 VE2 pE pF
2g 2g g g
The effect of the head loss is to make the difference in manometric height,
hE hF less than it would otherwise be. An alternative expression is
VF2 VE2 p p
K2 E E
g g g g
Since with the apparatus provided, the bore at (E) is 51.9 mm and at (F) is 20 mm,
Since:
Q 8.46104 hE hF
1/2
m3/s
2
1/2
0.846 hE hF
And m kg/s
c) Rotameter
Observation of the recordings for the pressure drop across the rotameter (H)-(I) shows that this
difference is large and virtually independent of discharge. Though there is a term which arises
because of wall shear stresses and which is therefore velocity dependent, since the rotameter is of
large bore this term is small. Most of the observed pressure difference is required to maintain the
float in equilibrium and as the float is of constant weight, this pressure difference is independent
of discharge.
The cause of this pressure difference is the head loss associated with the high velocity of water
around the float periphery. Since this head loss is constant then the peripheral velocity is constant.
To maintain a constant velocity with varying discharge rate, the cross-sectional area through which
this high velocity occurs must vary. This variation of cross-sectional area will arise as the float
move up and down the tapered rotameter tube.
3
From Figure 5.1, if the float radius is Rf , and the local bore of the rotameter tube
is Rt , then
R2t R2f 2R2f Cross-sectional area=
Discharge
Constant peripheral velocity
Now , where l is the distance from datum to the cross-section at which the local bore
is R, is the semi-angle of tube taper. Hence, l is proportional to discharge. An
approximately linear calibration characteristic would be anticipated for the rotameter.
4
V A2
This can be made dimensionless by dividing it by the inlet kinetic head
2g
2g p A pB
Now: VB2
1 A B / A A g
2
g
And: VA VB A B / A A
2 2 2
Thus:
AB pA pB
2
1
V
2
2
A A 1 A B / A A g g
A
With the apparatus provided A B / A A 0.38 therefore the inlet kinetic head is::
VA2 p p
0.1441.16 A B 0.167 hA hB
2g g g
For example if::
hA 375mm
hB 110mm
hC 350mm
Then:
H AC hA hC 25mm
VA2
0,167 265 44.26mm
2g
25
Therefore: Head loss 0.565 inlet kinetic heads.
44.26
b) Orifice Meter
Applying Equation (1) between (E) and (F) by substituting kinetic and hydrostatic
heads would give an elevated value to the head loss for the meter. This is because at
an obstruction such as an orifice plate, there is a small increase in pressure on the
pipe wall due to part of the impact pressure on the plate being conveyed to the pipe
5
wall. BS 1042 (Section 1.1 1981) gives an approximate expression for finding the
head loss and generally this can be taken as 0.83 times the measured head difference.
Therefore:
HEF 0.83 hE hF mm
0.83 372 40 mm 275mm
The orifice plate diameter (51.9 mm) is approximately twice the venturi inlet
diameter (26 mm), therefore the orifice inlet kinetic head is approximately 1/16 that
44.26
of the venturi, thus: 2.76
16
Therefore:
275
Head loss 99.62 inlet kinetic heads
2.76
c) Rotameter
6
Then as illustrated in Figure 5.3:
Inspection of the table of experimental results shows that this head loss is virtually
independent of discharge and has a constant value of approximately 100 rom of
water. As has already been shown, this is a characteristic property of the rotameter.
For comparative purposes it could be expressed in terms of the inlet kinetic head.
However, when the velocity is very low the head loss remains the same and so
becomes many, many times the kinetic head.
It is instructive to compare the head losses associated with the three meters with
those associated with the rapidly diverging section, or wide-angled diffuser, and with
the right-angled bend or elbow. The same procedure is adopted to evaluate these
losses.
d) Wide-Angled Diffuser
The inlet to the diffuser may be considered to be at (C) and the outlet at (D).
Applying Equation (1):
Then
7
Inlet kinetic head = 44.26 mm
(See venturi meter head loss calculations). The corresponding outlet kinetic head is:
Outlet kinetic head = 44.6/16=2.8 mm
The outlet kinetic head is now 2.8 times the inlet kinetic head. For example if:
And
Inlet kinetic head = 2.76 mrn
Outlet kinetic head = 7.73 mrn
Then
8
3. DESCRIPTION OF THE APPARATUS
3.1. Device construction
The apparatusis shown in Figure 6.
9
Following a further settling length and a right-angled bend, the flow enters the rotameter.
This consists of a transparent tube in which a float takes up an equilibrium position. The
position of this float is a measure of the flow rate.
After the rotameter the water returns via a control valve to the Hydraulic Bench, where the
flow rate can be evaluated. The equipment has nine pressure tappings (A to I) as detailed
in Figure 2.2, each of which is connected to its own manometer for immediate read out.
3.3. Operation steps
(Air purge-valve)
(Main valve)
10
Step 1: Connect the supply hose from the hydraulic bench to the inlet of the venturi meter
and secure with a hose clip. Connect a hose to the control valve outlet and direct its free
end into the bench measuring device.
Before continuing, refer to the hydraulic bench manual to find the method of flow
evaluation.
Step 2: Turn on pump.
Step 3: Open the bench valve fully. Then open main valve fully to allow rotameter
indicating the ceiling level. Waiting for water fill full the Manometer Tubes.
Step 4: Close the main valve completely. Then close the bench valve completely. Open
1/3 of the main valve. Then push and hold air purge-valve to let the air flow with the
Manometer Tubes. Continue to push and hold air purge-valve in combination with slightly
opening the main valve to decrease the water level in the Manometer Tubes. When the
water level in the Manometer Tubes drops steadily to 110 mm, immediately close the main
valve. Stop pushing the air purge-valve. Then the water level in the Manometer Tubes will
be equal at 110 mm.
Step 5: Open the bench valve fully.
Step 6: Adjust the flow rate in the system by turning the main valve while observing the
float position in the rotameter at 0, 10, 20, 30, 40, 50, 60, 70, 80, 90, 100, 110, 120, 130,
11
140, 150, 160, 170. At each position, record the head of water columns in Manometer
Tubes.
Step 7: Repeat step 6 10 times. Record the data of each measurement according to the
table.
Step 8: Turn off the pump, wait for the water to completely drain from the system. Lock
bench valve and main valve.
Form of results
Test number 1 2 3 4 5 6 7 8 9 10
A
B
Manometric C
levels
D
E
F
G
H
I
Rotameter (cm)
Water, W (kg)
Time, (sec)
Rotameter
Weigh tank
Rotameter
Diffuser (16)
12
Elbow (17)
4. Experiment report
- Calculating the discharge by each equipment.
- Evaluating head loss at local locations when flow rate in the system changes.
Explain.
13
A BRIEF SUMMARY OF THE THEORY OF
HYDRAULICS
1. The theory of hydraulics
1.1. Fluids
Fluids are divided into two types: gases (highly compressible) and liquids (less
compressible). During the movement of the fluid, the binding force between the fluid
molecules creates a force that resists this movement. This property of a fluid is its viscosity:
An ideal fluid is one in which the molecules of the fluid move without resistance
between one molecule and another.
A real fluid is a fluid in which the molecules of the fluid slide these molecules over
other molecules with a definite resistance.
All the fluids we use are real fluids, so it's important to take account of their viscous
properties as soon as they're in motion.
1.2. Hydrostatic
Hydrostatics studies the properties of a fluid when it is at rest, especially the problem of
pressure transfer. In hydrostatics, the laws established for ideal fluids are still applicable to
real fluids.
Pressure: force per unit area (1 Pa = 1 N/m2; 1 Bar = 105 Pa)
1.3. The pressure difference
Atmospheric pressure (Pa): used in storage tanks, allowing power to the pumps.
Atmospheric pressure fluctuates around 1.033 Bar.
Pressure in a fluid at rest: caused by the weight of the liquid column. 𝑃 = 𝜌𝑔ℎ (h is the
height of the liquid column). This results in an increase of 1 bar in pressure for every 10 m
of water column.
Pressure exerted by an external force on a fluid in a closed volume.
Pascal's Law: The pressure exerted on a fluid at rest is transmitted to all of the elements
of the fluid. Usually it will act on interactive surfaces. This property is used for the
transmission of forces (pressures) in hydraulics.
Energy transfer: the work generated during the force (pressure) transmission in hydraulics
is conserved ⇒ tensile strain = resistance strain.
14
1.4. Hydrodynamics (Hydrodynamique)
Hydrodynamics studies the properties of fluids in motion. A fluid in motion is
characterized by its pressure and flow. Due to the influence of viscosity, internal resistance
will appear when there is a difference in velocities between the molecular layers in the
fluid. Dynamic pressure is the pressure produced by the kinetic energy of the fluid:
𝑃 = 𝜌𝑉 /2
Flow rate is the volume of fluid that moves across an area perpendicular to the direction of
motion in a unit of time (The unit of flow is m3/s).
Average volume flow rate: 𝑄 = 𝑆. 𝑉 (𝑚 /𝑠)
Average mass flow rate: 𝑄 = 𝜌. 𝑄 = 𝜌𝑆. 𝑉 (𝑘𝑔/𝑠)
Flow conservation: The flow rate Q is constant at every point in the same motion circuit,
the velocity of the fluid will change depending on the change of the cross-sectional area at
each survey point.
𝑄 = 𝑆 𝑉 = 𝑆 𝑉 = 𝑆 𝑉 = 𝑐𝑜𝑛𝑠𝑡𝑎𝑛𝑡
1.5. Different types of energy
In a moving fluid medium, energy manifests itself in the following three states:
Potential energy: depends on the weight of the liquid column relative to the survey point
𝑊 = 𝑚𝑔ℎ (𝐽)
Kinetic energy: is the form of energy stored during motion
𝑊 = (1/2)𝑚𝑣 (𝐽)
Pressure: is the form of energy transferred by pressure on a moving fluid
𝑊 = 𝑃. 𝑆. 𝐼 = 𝑃. 𝑉 = 𝑃. 𝑚/𝜌 (𝐽)
In hydraulic transmission, all three forms of energy exist.
1.6. Bernoulli relation
Bernoulli equation: “in a steady state of motion, in an ideal incompressible fluid, the sum
of the changes in kinetic energy, potential energy, and pressure energy is zero”
1 𝑚
𝑚 (𝑣 − 𝑣 ) + 𝑚𝑔(ℎ − ℎ ) + (𝑃 − 𝑃 ) = 0
2 𝜌
15
1.7. Notes on different levels of pressures
Static pressure: is the form of pressure transmitted by the pump or generator. Depending
on the circuit design, the static pressure can range from 50-80 bars and 300-400 bars.
Pressure caused by the weight of the column of fluid: expressed in form of 𝜌𝑔ℎ. Usually
this form of pressure has a very small value compared to the static pressure generated by
the pump or generator.
Dynamic pressure: represents the kinetic energy of the fluid, (𝜌𝑉 /2), which is even
smaller than the pressure due to the weight of the fluid column in many cases
2. Flow
2.1. Schiller – Reynolds experiment
16
Turbulent Flow: When the velocity of the fluid in the tube increases, the mutual sliding
between the layers of the laminar flow will no longer be the same, instead the vortices will
appear, represent the mutual mixing of the flow. In steady-state turbulence, the average
velocity of the fluid in the tube will be within 0.84 times the value of the maximum
velocity.
2.3. Reynolds number
In Reynolds' experiment, the survey flow moves in a circular tube with constant diameter,
and haves unchanged properties. After studying the transition from laminar to turbulent
flows, the physicist Reynolds determined there is a factor influencing this change of flow
dynamics, which he called the Reynolds number.
𝑣𝑑
𝑅𝑒 =
𝜈
(with v: velocity – m/s; d: the pipe diameter – m; 𝜈 - kinematic viscosity - 𝑚 /𝑠)
Reynolds number is a dimensionless number.
For flow in a circular tube, in general, the flow will be laminar if Re < 2000, turbulent if
Re > 3000. The flow regime region with Re number between 2000 and 3000 is an unstable
flow.
2.4. The flow velocity
Because the energy loss in the turbulent flow mode is usually much larger compared to that
of the laminar flow, so for the flow in the pipe, in order to keep the laminar flow regime,
practically, we often apply the following fluid velocity levels:
- In the suction part, from 0.6 to 1.2 m/s
- At the push part, from 3 to 6 m/s
- In return lines, from 2 to 3 m/s
- In channels, ducts, from 1 to 1.5 m/s
The above values are average values applied to hydraulic oils with a viscosity between 2.8
and 4.5oE, and with a density between 0.85 and 0.9.
2.5. Types of energy loss
The relation of Bernoulli's equation with the ideal fluid: is the case when the system
supplies energy to the external environment, then the energy supplied is the difference
among all of the energy forms when the system transits from State 1 to State 2:
17
1 1
𝑊 = 𝑉 −𝑉 + 𝑔(ℎ − ℎ ) + (𝑃 − 𝑃 ) (𝐽/𝑘𝑔)
2 𝜌
The relation of Bernoulli's equation with viscous fluids: a real fluid is a fluid in which
viscosity is not neglected. This property gives extra internal drag when the fluid is in
motion. The energy absorbed by viscous drag is the loss of energy. This form of energy
loss is usually denoted J, then the Bernoulli equation for the real fluid will take the form
as:
1 1
𝑊 −𝐽 = 𝑉 −𝑉 + 𝑔(ℎ − ℎ ) + (𝑃 − 𝑃 ) (𝐽/𝑘𝑔)
2 𝜌
The general equation of linear energy loss of flow in pipe: It has been shown
experimentally that for a smooth straight pipe, the energy loss along the path of the flow in
this case can be expressed by the following equation:
𝐿𝑉
𝐽=𝜆 (𝐽/𝑘𝑔)
𝐷 2
where L is the pipe length (m); D is the pipe diameter (m); v is the flow velocity (m/s); 𝜆
is the energy loss coefficient along the pipe. This is a dimensionless coefficient that
depends on the Reynolds number and the internal surface roughness of the tube.
18
𝜇
𝜈=
𝜌
The unit of kinematic viscosity in the SI system is m 2/s
Stockes (St): 1 St = 10-4 m2/s; 1 cSt = 1/100 St = 10-6 m2/s
The kinematic viscosity of water at 20oC is 1 cSt.
3.3. Relative viscosity (La viscosité relative)
In practice, to determine kinematic viscosity, it is common to compare the drain time of a
definite volume of that fluid at a reference temperature (usually 50°C) with the drain time
of the same volume of water at 20°C.
There are many types of viscometers designed based on the above principle. The common
use in Europe are Engler viscometers; and the US and UK use the Saybolt viscometer...
𝑡𝑒𝑚𝑝𝑠 𝑒𝑐𝑜𝑢𝑙𝑒𝑚𝑒𝑛𝑡 200 𝑐𝑚 𝑑 ℎ𝑢𝑖𝑙𝑒 𝐹𝑙𝑜𝑤 𝑡𝑖𝑚𝑒 𝑜𝑓 200 𝑐𝑚 𝑜𝑖𝑙
𝑉𝑖𝑠𝑐𝑜𝑠𝑖𝑡𝑒 𝐸 = =
𝑡𝑒𝑚𝑝𝑠 𝑒𝑐𝑜𝑢𝑙𝑒𝑚𝑒𝑛𝑡 200 𝑐𝑚 𝑒𝑎𝑢 𝐹𝑙𝑜𝑤 𝑡𝑖𝑚𝑒 𝑜𝑓 200 𝑐𝑚 𝑤𝑎𝑡𝑒𝑟
19
3.4. The viscosity change
At a constant temperature, the viscosity increases with pressure; whereas at a constant
pressure, the viscosity will decrease very sharply with the increase of temperature.
3.5. Fluids used in the hydraulic systems
Fluids used in hydraulic systems are divided into two main groups: petroleum and non-
combustible fluids.
The petroleum group (Huiles minérales) is divided into 4 types according to its
characteristic properties:
HH group: are refined, processed petroleum oils. It has poor lubricity.
HL group: are petroleum oils with anti-oxidation and anti-corrosion properties.
HM group: are HL group oils with enhanced anti-usure ability. The petroleum oils
in this group are divided into 7 viscosity grades/ degrees (at a reference temperature
of 40℃): 15 – 22 – 32 – 46 – 68 – 100 – 150.
HV group: are HM group oils with enhanced ability to minimize the effect of
viscosity with temperature. The petroleum oils of this group are divided into 6
viscosity grades/degrees (at a reference temperature of 40℃): 22 – 32 – 46 – 68 –
100 – 150
20