Instruction Manual
Request ! !
Please apply appropriate means to ensure that Instruction
Manual is delivered to the persons assigned with final
Responsibilities for maintenance of this equipment.
2.0 Acceptance 11
3.1 Storage 11
3.2 Transportation 11
3.3 Weight 12
4.1 Unpacking 14
5.0 Installation 15
5.2 Preparation 16
6.1 Schematic diagram for secondary circuit terminals of BT2-1600 circuit breaker 17
6.3 Grounding 17
7.0 Operation 24
Breaker socket 33
9.0 Checking 57
11.1 Maintenance 58
13.0 Accessories 65
·1·
1. 0 GENERAL DESCRIPTION
There are two kinds of circuit breakers: fixed and draw-out. The latter is formed by putting the
the main body into the exclusive draw-out socket. The main body is composed of contact system,
arc-over system, operating mechanism system, current transformer, intelligent controller, auxiliary
switch, secondary connector, under-voltage release, shunt release etc; The draw-out socket is
composed of two-side plates of cradle, base, crossbeam,etc….
Fig1-1. Fixed
·2·
1. 0 GENERAL DESCRIPTION
Illustrations:
1 Name Plate
2 Indication window of energy-storage and energy-release
3 Switching-on Button
4 Manual energy-storage handle
5 Brand
6 Wiring terminals of secondary circuit
7 "Switching-off "lock mechanism
8 Release indication and resetting button
9 Intelligent controller
10 Switching button
11 Indication of switching-on( "I" )andswitching-off( "O" )
12 Indication of ready-for-switching-on(" OK" )
13 Unlock button of the three positions( "separated ",
"test" and "connected" ) for draw-out circuit breakers
14 Rocker operating hole of the draw-out circuit breaker
15 Rocker storage hole of the draw-out circuit breaker
16 Indication of the three positions( "separated" , "test"
17 and "connected") of the draw-out circuit breaker
Fig.1-2 Draw-out
Note:
1 “ Separated” : indicates that main circuit
and secondary circuit are both in isolation.
“ test” : indicates that main circuit is in
iso lation and s econdary cir cuit is in
connection.
“ connected” : indicates that main circuit
and secondary circuit are both in connection.
2 The circuit breaker can be automatically
locked (rocker can not be turned at this point)
when its main body is at the position of
“ separated” , “ test” or “ connected”
by turning the rocker, and can be unlocked by
pushing “unlock button” to the left side.
Illustrations:
20 18 Installation hole
21
19 Satety back plate
19 20 Wiring terminals of secondary circuit
22
21 Side plate
23 22 Copper bar of the main circuit
23 Draw-out socket
24 Earthing point at draw-out socket
18
24
·3·
1. 0 GENERAL DESCRIPTION
Characteristic Curve
2
Time/Current Curve of Type L25 intelligent controller (I t)
10000
Factory's setting value
t1 Instantaneous range
Ir3=(3~15)Ir1+OFF
100
long-time delay curve
I2T ON Ir2
t(s)
10
1
t2
Short-time delay curve
0.4
0.3
0.2 I2 T OFF
0.1
Instantaneous range
0.02
Instantaneous curve
0.01
0.4 1 1.5 3 10 15
Ir1
·4·
1. 0 GENERAL DESCRIPTION
2
Time/Current Curve of Type M25, M26 , H26, P25, P26 intelligent controller (I t)
10000
Factory's setting value
2
I T ON Ir2
t(s)
10
t2
Short-time delay curve
1
0.4
0.3 I2 T OFF
0.2
0.1
Instantaneous range
0.02
Instantaneous curve
0.01
0.4 1 1.6 10 15 80
Ir1 kA
·5·
1. 0 GENERAL DESCRIPTION
Time/Current Curve of Type P25 and P26 intelligent controller (inverse time delay special It)
10000
Factory's setting value
2
I T ON Ir2
t(s)
10
0.4
0.3 2
I T OFF
0.2
0.1
Instantaneous range
0.02
Instantaneous curve
0.01
0.4 1 1.6 10 15 80
Ir1 kA
·6·
1. 0 GENERAL DESCRIPTION
Time/Current Curve of Type P25 and P26 intelligent controller (high-voltage fuse I4t)
100000
Factory's setting value
100
long-time delay curve
I2 T ON Ir2
t(s)
10
0.4
0.3
0.2
2
I T OFF
0.1
0.01
Instantaneous range
Instantaneous curve
0.001
0.4 1 1.6 10 15 80
Ir1 kA
·7·
1. 0 GENERAL DESCRIPTION
Time/Current Curve of Type M26 , H26 and P26 intelligent controller (for ground-fault protection)
1000
Grounding current
Ir4=(0.4~0.8)In(BT2-1600)
Ir4=(0.2~0.8)In(BT2-2000、
BT2-2500)
Ir4=(0.2~0.6)In(BT2-4000)
Ir4=(0.2~0.5)In(BT2-6300)
t4=0.1s~0.4s 4级 four steps
Ir4 Maximum 1000A(For BT2-1600)
Maximum 1200A(For BT2-2000、BT2-2500)
Maximum
10
t(s)
0.4
0.3
0.2
0.1
0.01
0.2 0.8 1 10 100
In
·8·
1. 0 GENERAL DESCRIPTION
Time/Current Curve of Type M25, M26 , H26 , P25 and P26 intelligent controller
(for load-monitoring pattern one)
10000
ILC1=(0.2~1)In
tC1 =t 1/2(t1=15,30,60,120,240,480s)
I LC2=(0.2~1)In
t C2=t1/4(t1=15,30,60,120,240,480s)
ILC2
I LC2 ≤ ILC1
1000
I LC1
200
t C1
tC2
100
t(s)
10
0.1
0.2 0.8 1 10 100
In
·9·
1. 0 GENERAL DESCRIPTION
Time/Current Curve of Type M25 , M26 , H26 , P25 and H26 intelligent controller
for Load-monitoring pattern one
10000
ILC1=(0.2~1)In
tC1 =t1/2(t1=15,30,60,120,240,480s)
ILC2=(0.2~1)In
I LC2 tC2=60s
1000
ILC1
tC2
100
60 tC1
t(s)
10
0.1
0.2 0.4 0.8 1 10 100
In
·10·
2.0 ACCEPTANCE
Check the type and specification of the breakers upon receiving. Remove the external package
carefully in order not to destroy the breakers.
3.1 STORAGE
The breaker is packed with wooden case and fixed on wooden crate by screws. If the breaker is
stored for a short period, please put it in the dry place with ventilation and cover it with waterproof
oilcloth.
Notice: ① Please put the breaker in the dry place without dust (the ambient temperature is
from -25℃ to +55℃ , the relative humidity is not more than 95% at 25℃ ) and corrosion of
chemical gas.
② The breaker should be open and put into the wooden case, the charging indicator (see
Fig.1-1, Fig.1-2 Preface) is at the position of DISCHARGED.
③Put the breaker or base on horizontal wooden stand (provided by the factory).
④Don't pile up breakers.
3.2 TRANSPORTATION
Put the breaker on the wooden stand horizontally and move it with fork lift. See Fig. 3-1.
B T2
Fig. 3-1
·11·
3.0 STORAGE, TRANSPORTATION AND WEIGHT
3.3 WEIGHT
Rated Pole
Type Fixed Draw-out
Current Number
3 28.8 45
200
4 36.5 58
3 28.8 45
400
4 36.5 58
3 28.8 45
630
4 36.5 58
BT2-1600 3 28.8 45
800
4 36.5 58
3 28.8 45
1000
4 36.5 58
3 28.8 45
1250
4 36.5 58
3 28.8 45
1600
4 36.5 58
3 54.5 84.9
630
4 59.5 96
3 54.5 84.9
800
4 59.5 96
3 54.5 84.9
1000
4 59.5 96
BT2-2000
3 54.5 84.9
1250
4 59.5 96
3 54.5 84.9
1600
4 59.5 96
3 56 88
2000
4 62 100
·12·
3.0 STORAGE, TRANSPORTATION AND WEIGHT
Unit: kg
Rated Pole
Type Fixed Draw-out
Current Number
3 65 95
1250
4 78 110
3 65 95
1600
4 78 110
BT2-2500
3 65 95
2000
4 78 110
3 65 95
2500
4 78 110
3 66 113.5
2000
4 84.5 141.5
3 66 113.5
2500
4 84.5 141.5
3 66 113.5
2900
4 84.5 141.5
BT2-4000
3 66 113.5
3200
4 84.5 141.5
3 66 113.5
3600
4 84.5 141.5
3 66 113.5
4000
4 84.5 141.5
3 135 227
4000
4 166 280
3 135 227
BT2-6300 5000
4 166 280
3 135 227
6300
4 166 280
·13·
4.0 UNPACKING AND NOTICE
4.1 UNPACKING
①
③
Fig. 4-1
Fig. 4-2
·14·
4.0 UNPACKING AND NOTICE
Unscrew the cross screws ① (16 or 20 pieces) around the under part of the wooden case, lift
the wooden case and remove it ( See Fig. 4-1);
As for fixed breaker, just remove four STC4.8-C Screws together with washers for fixing the
breaker in the wooden stand ③, then move it away from the stand;
As for draw-out breaker (See Fig. 4-2), turn the handle to pull out the main body till it is
obstructed (See7-3 for details). Lift up the main body from the draw-out socket and move it away.
Then remove four nuts of M10 and washers④ for fixing the socket with the wooden stand③ at the
bottom of draw-out socket in order to separate the socket from the wooden base. (Please make sure
the nuts and washers are already removed from the draw-out socket) Put the main body back into
the draw-out socket and finish the operations. (See7.3 for details)
Check the following settings on the data plate, make sure they will satisfy your requirements
while making order.
Voltage of Shunt Release; 2. Voltage of Power-driven Operating Mechanism; 3. Voltage of
Closing electro-magnet; 4. Voltage of Intelligent Controller; 5. Voltage and Delayed Time of Under-
voltage Release; 6. Type of Auxiliary Switch
Check the items in package according to the packing list.
Do read the operation manual before the installation, operation and maintenance.
5.0 INSTALLATION
Put the breaker in the dry place where there is no dust, corrosive gas and explosive medium
and prevent it from striking. If the environment condition can’t be satisfied, protection grade of the
switchgear should be upgraded. Requirements of temperature, humidity and elevation see the
following table:
Item Norm
Ambient Temperature -5℃~+40℃ and the average is no more than +35℃ within 24 hours
The relative humidity of the gas is no more than 50% at the maximum temperature of
40℃. It may be higher at the lower temperature, for example, 90% at +20℃. Special
Relative Humidity
measures should be taken to prevent the breaker from dew caused by temperature
change.
Elevation ≤2000m
·15·
5.0 INSTALLATION
5.2 PREPARATION
Check insulation resistance of the breaker with megohm meter of 1000VDC, the value should
be no less than 20MΩ when the ambient temperature is 25℃ ±5℃ and the relative humidity is
50%~70%.
Place to be tested: test the resistance between each phase and between phase and framework
when the breaker is closed; test the resistance between the incoming wire and outgoing wire for each
phase when the breaker is open.
Take the main body out of the draw-out socket, then install the socket into the switchboard, fix
the socket with four screws of M10 (with washers) (See Fig. 5-1). The applied torque is from 17.7 N.
m to 22.6N. m. At last put the main body into the socket.
Fig. 5-1
Put the breaker into switchboard, fix it with four screws of M10 (with washers). The applied
torque is from 17.7N. m to 22.6N. m (See Fig. 5-2)
Fig. 5-2
·16·
6.0 ELECTRICAL WIRING
Insert the slotted point screw driver (Φ 3) into the square hole of the connector insert the
conductor wire into the round hole and at last remove the screw driver
Diameter of Screw Applied torque N.m with spring spacer Applied torque N.m with flat spacer
M10 17.7~22.6 35.4~45.2
M12 31.4~39.2 62.8~78.4
M16 78.5~98.1 157.0~196.2
6.3 GROUNDING
Clean and dry the grounding point with cloth before the grounding of fixed and draw-out
breakers.
① Grounding of fixed breaker
Fix the PE cable on the grounding busbar of switchboard with M10 screw directly, cross
section of the cable see IEC 60439-1.
·17·
6.0 ELECTRICAL WIRING
Ambient environmental
temperature +40℃ +45℃ +50℃ +55℃ +60℃
·18·
6.0 ELECTRICAL WIRING
6.5 SPECIFICATION OF THE COPPER BUSBAR WIRED IN THE PRIMARY CIRCUIT OF DRAW-OUT BREAKER
Busbar specification
Rated Frame Current Inm(A) Rated Current In(A)
Amount Size(mm×mm)
200 1 20×5
400 1 50×5
630 2 40×5
1600 800 2 50×5
1000 3 40×5
1250 4 40×5
1600 2 50 ×10
630 2 50×5
800 2 60×5
1000 2 60×5
2000
1250 3 60×5
1600 2 60 ×10
2000 3 60 ×10
1250 3 60×5
1600 2 60 ×10
2500
2000 3 60 ×10
2500 4 60 ×10
2000 3 100×5
2500 4 100×5
2900 3 100×10
4000
3200 4 100×10
3600 4 100×10
4000 5 100×10
4000 5 100×10
6300 5000 6 100×10
6300 8 100×10
The specifications of copper bars in the above table are introduced under which the circuit breakers by open
installation are at maximum ambient temperature of 40℃ and satisfy the conventional heating condition in IEC60947-2
·19·
6.0 ELECTRICAL WIRING
·20·
6.0 ELECTRICAL WIRING
·21·
6.0 ELECTRICAL WIRING
·22·
6.0 ELECTRICAL WIRING
·23·
7.0 OPERATION
BT2-1600 Circuit Breaker BT2 with frame current of 2000A and above
Fig. 7-1
·24·
7.0 OPERATION
BT2-1600 Circuit Breaker BT2 with frame current of 2000A and above
Fig. 7-2
② Switching-off
As the circuit breaker is switched on, push the red “Ο ” button (See Fig. 7-3), it will be
switched off at once. At this time, “On/off” indicator should be at the position of red “Ο”.
BT2-1600 Circuit Breaker BT2 with frame current of 2000A and above
Fig. 7-3
7.2.2 Power-driven switching on and off
① Switching-on
As the circuit breaker is charged and switched off, it can be switched on by providing the
closing electro-magnet with rated voltage.
② Switching-off
As the circuit breaker is switched on, it can be switched off by providing the shunt release with
rated voltage.
·25·
7.0 OPERATION
Fig. 7-4
② Put the main body on the slideway, See Fig. 7-5, and push it inside the socket till it can't be
pushed any more, See Fig. 7-6.
·26·
7.0 OPERATION
Fig. 7-7
④ Pull out of the rocker from its storage hole and fully plug it into the hole at the bottom of draw-out
socket, move “unlock button” to the left side, See Fig. 7-8
Fig. 7-8
·27·
7.0 OPERATION
⑤ Turn the rocker in clockwise. When the indicator is at the position of “ test” , the circuit
breaker will be locked automatically and the rocker can not be turned.
The unlock button has to be moved to the left, and the rocker continues to be turned in
clockwise. When the indicator is at the position of “ connected”, the circuit breaker will be locked
automatically ,pull out the rocker and put it back to the original place, See Fig. 7-9
Fig. 7-9
Fig. 7-10
·28·
7.0 OPERATION
Fig. 7-11
③ Pull the main body out of the draw-out socket, See Fig. 7-12, and take out the main body,
See Fig. 7-13
④ Push the slideway back into the socket, See Fig. 7-14
Fig. 7-14
·29·
7.0 OPERATION
7.3.2 Operation of draw-out BT2-2000 circuit breaker with frame current 2000 and
above
7.3.2.1 Push the main body into the socket
① Press the lock catch with thumb, pull out the slideway till it can't be moved
② Put the main body on the slideway as shown in Fig. 7-15, note that the main body should
be stuck right on the slideway.
Lock catch
Fig. 7-15
③ Push the main body inside the socket till it can't pushed any more and “ click” occurs,
See Fig. 7-16
Fig. 7-16
·30·
7.0 OPERATION
④ Pull out of the rocker from its storage hole 16 and fully plug it into the operation hole 15 at
the bottom of draw-out socket, push “unlock button” 13 to the left side, See Fig. 7-17
13
15
16
Fig. 7-17
⑤ Turn the rocker in clockwise. When the indicator 17 is at the position of “ test” , the
circuit breaker will be locked automatically and the rocker can not be turned.
The unlock button 13 has to be pushed to the left, and the rocker continues to be turned in
clockwise till it can't be moved. When the indicator is at the position of “connected”, the rocker
can be pulled out to the original place.
17
13
Fig. 7-18
7.3.2.2 Pull out the main body
① Move the “ unlock button” in order to unlock the mechanism at the position of
“ connected” at first, then turn the rocker to move the main body from “ connected” to
“ separated” (turn the rocker in counter clockwise, notice in this process: the button is locked
automatically at the position of “test”, the “unlock button” has to be moved in order to pull out
the main body)
·31·
7.0 OPERATION
Fig. 7-19
② After the rocker is pulled out, press the lock catch to pull out the main body as shown in Fig.
7-20, note that when the main body is pulled out, prevent it from pouring out and falling due to
forward move of centre-of-gravity.
Lock catch
Fig. 7-20
③ Take the main body out of the draw-out socket as shown in Fig. 7-21, then push the
slideway back into the socket.
Fig. 7-21
·32·
7.0 OPERATION
7.4 LOCK AT THE POSITION OF “SEPARATED” BY SAFETY PADLOCK MECHANISM FOR THE DRAW-OUT SOCKET
“Separated” position
Safety padlock mechanism Unlock button
Three-position indication
“Separated” position
Unlock button Three-position indication
Safety padlock mechanism
Fig. 7-22
Note: the padlock should be provided by users themselves.
·33·
8.0 SETTING AND USE OF INTELLIGENT CONTROLLER
2
15
3
4
5
6
14
7
13 8
12 9
11 10
1. Light columnar indication of loading rate (%Ir1 ) 9. Adjustment of imitative test current
2. Indication of controller power supply 10. Test terminal (for the Factory ’s testing and checking)
3. Indication of long-time delayed fault 11. Test button
4. Indication of short-time delayed fault 12. Adjustment of short-time delayed time
5. Indication of instantaneous fault 13. Adjustment of long-time delayed time
6. Adjustment of instantaneous operating current 14. Adjustment of long-time delayed current
7. Adjustment of short-time delayed current 15. Indication of alarm and trip
8. “Clear ” button
·34·
8.0 SETTING AND USE OF INTELLIGENT CONTROLLER
Parameters of the intelligent controller can be set in the network while the auxiliary electric
source is provided by controller’s power supply ( Wiring pattern see Chapter 6.6)
For example: Rated current In is equal to 2500A; the parameters such as Ir1=0.8In, t 1=480s;
Ir2=8Ir1, t2=0.2s; Ir3=10Ir1 orginally set can be changed as follows: Ir1=1750A, t1=60s; Ir2=14kA,
2
t2=0.2s (the function of inverse time protection I t should be cancelled); Ir3=17.5kA
Operate as follows:
Convert the above current settings into the multiple of In (or Ir1) so that it will be easy to be
adjusted.
Ir1=0.7In, t1=60s
2
Ir2=8Ir 1, t2=0.2s (I t OFF)
Ir3=10Ir1
Turn the knob to the target point with screw driver, See Fig. Below
clear
Note: New settings will be valid after 5 seconds. In case that fault happens within this period,
Please operate the circuit breaker in terms of the original settings.
8.1.3 Test
Push “test” button to check the setting of test current
If only checking current-time feature of the controller: make the circuit breaker be switched
off before test with auxiliary power supply.
If checking current-time feature of the controller and the operation of operating mechanism at
the same time: make the circuit breaker be switched on before test.
·35·
8.0 SETTING AND USE OF INTELLIGENT CONTROLLER
For example: ① Set the test current on 1.5In as shown in Fig. Above, push the test button once
again, the delayed operating time should be within the range of t1’(stipulated time)±15%.
Note: t1’ (stipulated time) must be converted. In this case, if the value of Ir1 (equal to 0.7In)
and the value of t1 (equal to 60s) is adjusted, put the value of Ir1 and the value of t 1 into the formula:
2 2
(1.5Ir1) t1=(1.5Ir1) t1’, the value of t1’ can be worked out.
② Set the test current on 10In, then I will be 10 multiple with 2500, equal to 25kA which
keeps within the range of instantaneous prection Ir3. Press test button and the circuit breaker will
operate at once.
③ Push the button of “clear” and “RESET” after test in order to operate the circuit
breaker regularly.
Note: In order to avoid mistakes, turn the knob for setting the test current to the right value
prior to each test, and the setting is only effective within 2 minutes. If over 2 minutes, turn the knob
once again even though test current is the same.
I1 I2 I3 IN
90%
A
90
%I r 1
105 P owe r ind ic ato r
Trip ped/a larm
Ir 2 Ir 2 Ir 3
·36·
8.0 SETTING AND USE OF INTELLIGENT CONTROLLER
clear
8.2 SETTING AND USE OF TYPE M25, M26 AND H26 INTELLIGENT CONTROLLER
test
test
U I % U I clear
Fig. 8-1
·38·
8.0 SETTING AND USE OF INTELLIGENT CONTROLLER
8.2.2.1 Current meter The maximum current value in three phases will display in operation
[the current value as shown in the Fig. 8-1 indicated in the current meter is the maximum current I2
in three phases(light of I2 and MAX on), equal to 1600A. Press the button of “I” to display I N (four
poles), I G (Type M26 and H26) and the real-time value of I1,I2,I3 in circulation, the maximum real-
time value will display again after 5 minutes without operation.
8.2.2.2 Voltage meter The minimum voltage value of three phases will display in operation [the
voltage value as shown in the Fig. 8-1 indicated in the voltage meter is the minimum voltage U31 in
three phases (Light of U31 and MIN on), equal to 380V]. Press the button of “U” to display U12, U23
and U31 in circulation, the minimum real-time value will display again after 5 minutes without
operation.
·39·
8.0 SETTING AND USE OF INTELLIGENT CONTROLLER
1. The seting value of Ir1 is equal to 1380A (t1 is still 30s), operate as follows:
test test
MEM MEM
U I inspect inspect
fault clear U I fault clear
te st test
MEM MEM
U I inspect U I inspect
fault clear fault clear
BT2-1600
·40·
8.0 SETTING AND USE OF INTELLIGENT CONTROLLER
te st test
MEM MEM
U I % clear U I % clear
In=1600A In=1600A
te st test
MEM MEM
U I % clear U I % clear
In=1600A In=1600A
·41·
8.0 SETTING AND USE OF INTELLIGENT CONTROLLER
2. The re-setting value of t2 is equal to 0.3s and the function of I2t is shut off, operate as follows:
test test
MEM MEM
test
fault
trip
c) Press "mem" button
and the new setting
will take effect.
MEM
set mem
inspect
U I fault clear
trip non-trip
BT2-1600
·42·
8.0 SETTING AND USE OF INTELLIGENT CONTROLLER
test te st
MEM MEM
U I % clear U I % clear
In=1600A In=1600A
test
fault
trip
c) Press "mem" button
and the new setting
will take effect.
MEM
s et mem
U I % clear
In=1600A
·43·
8.0 SETTING AND USE OF INTELLIGENT CONTROLLER
3. The earthing fault protection feature (Only for Type M26 and H26) is shut off, operate as follows:
test te st
MEM MEM
U I inspect inspect
fault clear U I fault clear
test
fault
trip
c) Press "mem" button
and the new setting
will take effect.
MEM
Note: All protection parameters can be
adjusted by following the above steps.
s et mem
Check: After the setting operation is over,
U I
inspect
clear
press “clear” button and “set” button in
fault
succession to check the displayed new value of
trip non-trip protection parameters, which should be the
same as the desired values. (Note: The
controller will recover its displaying of current
if no buttons are pressed within 10 seconds.)
BT2-1600
·44·
8.0 SETTING AND USE OF INTELLIGENT CONTROLLER
test test
MEM MEM
U I % clear U I % clear
In=1600A In=1600A
test
fault
trip
MEM
·45·
8.0 SETTING AND USE OF INTELLIGENT CONTROLLER
8.2.4 Test
The protection characteristics including long-time delay, short-time delay, instantaneous and
earthing fault can be tested. There are two kinds of testing ways: “trip” test and “non-trip” test.
As for the “trip” test, set the current value at which the circuit breaker will trip, press “trip”
button and the circuit breaker should be switched off (In general, this test is carried without load);
As for the “ non-trip” test, set the current value at which the circuit breaker will trip, press
“non-trip” button and the circuit breaker shouldn’t be switched off.
[Example] Test of long-time delayed operating features (1.5Ir1)
1. As first, check the original setting value of Ir1 and t1, operate as follows:
test te st
MEM MEM
s et mem s et mem
BT2-1600
test te st
MEM MEM
U I % clear U I % clear
In=1600A In=1600A
·46·
8.0 SETTING AND USE OF INTELLIGENT CONTROLLER
test test
MEM MEM
inspect U I inspect
U I fault clear fault clear
BT2-1600
test test
MEM MEM
mem set
U I % clear U I % clear
In=1600A In=1600A
·47·
8.0 SETTING AND USE OF INTELLIGENT CONTROLLER
3. Test operation
test test
a) Press “ non-trip”
button and the b) The screen will display
fault corresponding light of fault
“ 0” and the corresponding
trip light flashs. With the setting
“test” will be on. trip
time of 30s elapsed, the
c o r re sp o n d i n g l i g h t o f
“ trip” , “ Ir1” and fault
will be on, which means the
MEM
completion of test operation.
MEM
set mem
set mem
U I inspect inspect
fault U I fault clear
BT2-1600
test test
a) Press “ non-trip”
button and the b) The screen will display
fault corresponding light of fault
“ 0” and the corresponding
trip “test” will be on. trip light flashs. With the setting
time of 30s elapsed, the
c o r re sp o n d i n g l i g h t o f
“ trip” , “ Ir1” and fault
will be on, which means the
completion of test operation.
MEM MEM
U I % I clear
U %
inspect trip non-trip inspect
fault fault trip non-trip
In=1600 A In=1600A
·48·
8.0 SETTING AND USE OF INTELLIGENT CONTROLLER
te st test
fault fault
trip trip
MEM MEM
mem mem
BT2-1600
te st test
fault fault
trip trip
MEM MEM
mem mem
U I % clear U I % clear
In=1600A In=1600A
a) With the completion of test operation, press “inspect fault” button and “I” button till
the light of “I1” (“I2”, “I3”) is on (interval between two steps should be within 5s), at the time
which the screen displays the imitative breaking current value of 2060A.
b) Press “I” button again, the light of “A” will be off and the light of “s” will be on, at
the time which the screen displays the imitative operating time value of 30.60s within the range of
the setting value: t1(30s)±15%, which keeps in accordance with the setting operating features.
·49·
8.0 SETTING AND USE OF INTELLIGENT CONTROLLER
fault
trip When the operating current
is wit hin the rang e of
1.05Ir 1 to 1.20Ir 1, the light
of “Ir1 ” will flash.
MEM
MEM MEM
inspect U I % clear
U I fault clear
In=1600A
test test
fault fault
trip trip
MEM MEM
In=1600A
test test
fault fault
trip trip
MEM MEM
mem mem
In=1600A
·51·
8.0 SETTING AND USE OF INTELLIGENT CONTROLLER
test
fault
trip
MEM
8.2.9 Other
① Contact wearing indication
test te st
fault fault
trip trip
set set
In=1600A
·52·
8.0 SETTING AND USE OF INTELLIGENT CONTROLLER
② Self-diagonosis
test test
MEM MEM
set
U I % clear
·53·
8.0 SETTING AND USE OF INTELLIGENT CONTROLLER
Moniter computer
RS232
RS232/RS485
Converter
RS485
DA TA +
Note: As an option, this accessory is necessory when remote reading of main body postions of draw-out
breakers is required.
Note: ① Please protect the controller against dust, humidity and mechanical damage while setting.
② Make sure Ir1<Ir2<Ir3 while setting parameters again
③ The following items should be checked by technicians before operating the circuit breaker: whether the
setting of parameters is correct, whther the intelligent controller is cleared and resetted, whether the circuit breaker
is in normal condition and should be tested. Inspect the circuit breaker while its operation. Get rid of any faults or
abnormalities in time.
④ If the circuit breaker trips due to fault, remove the troubles in terms of the indications on the panel before
the circuit breaker is in operation again.
·55·
8.0 SETTING AND USE OF INTELLIGENT CONTROLLER
Busbar
Zone1 21
22
Circuit Breaker at up-stream level 23
Release delay t 2
24
Control line
Control line
Busbar
21
22
Zone2 23
Release delay t 2
24
Fault
Control line
Control line
Busbar
Circuit breaker at
down-stream level
21 21
22 22
Zone3 23 23
24 24
Note: 21, 22, 23 and 24 serve as the wiring terminals of secondary circuit.
When several of circuit breakers are linked together up and down, zone selective interlock can
ensure fully-selective protection of circuit breakers at up-stream or down-stream so as to reduce
the range of operation by fault and the breaking time of circuit breakers. This function serves for
2
short-circuit short-time delay (I t OFF) and earthing fault protection of circuit breakers.
As the sketch shown above, control lines can interlock with other units of circuit breakers
equipped with intelligent controllers of Type M25, M26 and H26.
After detecting the fault, the intelligent controller (zone 2) will send out a signal to circuit
breakers (zone 1) at higher level and check whether the signal of circuit breakers (zone 3) at lower
level arrives. If circuit breakers at lower level send out a signal, the circuit breaker will be switched
on at the time duration of release delay; if circuit breaker at lower level don’t send out a signal, the
circuit breaker will break at once no matter whether the release has the protection of delay.
·56·
9.0 CHECKING
Provide the charging motor with power Check whether the charging
Motor-driven operating supply, switch the breaker on and off for motor works normally without
2 noise; whether the breaker is
mechanism several times
switched off
7 Auxiliary Switch Provide the corresponding contact with Check whether the signal is
signal normal
·57·
10.0 TRIAL OPERATION
controller.
④ Ambient environment is ventilated.
Caution:
Before any maintenance and inspection, the following procedures should be carried out:
① Switch off the main circuit and the secondary circuit of the circuit breaker
② Switch off the breaker and check the spring of the operating mechanism is discharged
③ Pull the main body out of the draw-out socket for the draw-out circuit breaker
11.1 MAINTENANCE
● Check whether the ambient environment can meet the general requirements
● Check whether all rubbing and movable parts are lubricated periodically
● Check whether the screw bolt for fixing the breaker with busbar is fixed firmly and whether
the contact is fine
● Check the state of dust piling up on the main body and insulation parts of the draw-out
socket, and cleaning on schedule
● Check whether the wiring terminals of secondary circuit are connected reliably
● Check whether the intelligent controller displays correctly
● Check whether protection features of the intelligent controller are set correctly
● Check whether ON/OFF indication is correct and reliable
·58·
11.0 MAINTENANCE, EXAMINATION AND REPAIR
When the right maintenance is carried out, the circuit breaker can have the following operating
performances in the table:
Mechanical durability* (times) Electrical durability* (times)
Rated Current
Frame current Without With
(A) AC440V AC690V
maintenance maintenance
200 15000 30000 6500 3000
400 15000 30000 6500 3000
630 15000 30000 6500 3000
1600 800 15000 30000 6500 3000
1000 15000 30000 6500 3000
1250 15000 30000 6500 3000
1600 15000 30000 6500 3000
630 15000 30000 6500 3000
800 15000 30000 6500 3000
1000 15000 30000 6500 3000
2000
1250 15000 30000 6500 3000
1600 15000 30000 6500 3000
2000 15000 30000 6500 3000
1250 15000 30000 5000 2500
1600 15000 30000 5000 2500
2500
2000 15000 30000 5000 2500
2500 15000 30000 5000 2500
2500 10000 20000 1500 1000
2900 10000 20000 1500 1000
4000 3200 10000 20000 1500 1000
3600 10000 20000 1500 1000
4000 10000 20000 1500 1000
4000 5000 10000 1000 800
6300 5000 5000 10000 1000 800
6300 5000 10000 1000 800
*Note: For IEC60947-2,the term" durability"expresses the expectancy of number of operating cycles which can be
performed by the equipment before repair or replacement of parts.The consequent test is not intended to be
acceptance test for application by the user.
● Check whether all parts of the circuit breaker, such as the insulation parts of the framework,
footing, are integral and clean;
·59·
11.0 MAINTENANCE, EXAMINATION AND REPAIR
● Check whether the base of the breaker is fixed firmly. Should be no vibration in operation;
● Manual operating mechanism for the switching on/off of breaker should be moved flexibly
without being stuck. The switching of auxiliary contact of secondary circuit should operate reliably;
● Pull the slideway out or in by turning the rocker manually. The position of “ test” ,
“separated” and “connected” should be clear and interlocking should be operated reliably
● When the secondary circuit is electrified, shunt, closing electro-magnet, under-voltage
release should operate in compliance with stipulations in technical manual of the breaker, power-
driven operating mechanism should operate normally;
● The contact system of the arc-chute chamber including contact tips should be complete,
silver coating layer should be in good condition, the arc-chute chamber should be cleaned up inside;
(Note: Don’t operate the mechanism when the arc-chute chamber is opened)
● The connection between the circuit breaker and busbar should be reliable and screw bolt
should be fastened;
● Check whether the surface of connector between the main body and the draw-out socket
should be clean and neat to ensure the reliable connection;
● Check the insulated resistance of the breaker with megohm meter of 1000VDC at the
ambient temperature of 20℃± 5℃, and the resistance should not be less than 20MΩ under the
relative humidity of 50~70%;
● Check the setting values of protection features of the intelligent controller;
If the controller is electrified with DC 24V, check as follows:
○ For Type L25 Intelligent Controller
Connect with the exclusive tester for Type L25 Controller, press the button “ select” to
choose the setting values to check. If the setting values want to be adjusted, please turn the knob.
○ For Type M25, M26 and H26 Intelligent Controller
Press the button “Set” and the corresponding setting values will display on LED screen. To
△
modify the setting values, press the button “△”/“ ”, then press the button “mem” to save
the modifications.
○ For Type P25 and P26 controller
Press F3 ( protection setting ) to see the setting values of protection characteristics press
“enter”, press “ ”/“ ”to adjust the values and then press “enter”.
Before the breaker is in operation again, check the setting parameters of the controller. At the
position of “test”, the secondary circuit is electrified or simulate tripping test with DC24V, make
sure that all simulated operations are correct before its regular operation. Check as follows:
○Type L25 Controller
1: Turn the knob “test” to choose the suitable test current (NхIr 1);
2: Wait two seconds after step 1, press the button “trip” , and then the controller will be
tested and the breaker will be switched off according to the protective curve.
○Type M25, M26 and H26 Controller
1: Press the button “set” to choose the phase current to test;
△
2: Press the button “△”/“ ” to choose the suitable test current;
·60·
11.0 MAINTENANCE, EXAMINATION AND REPAIR
3: Press the button “trip” to do tripping test or press the button “non-trip” to do non-
tripping test;
4: When the test light is on, the controller is being tested. In terms of the test current value
within the operating range of LSI protection, the circuit breaker will be switched off (“trip”) or
(“non-trip”) only indicates on the panel according to the protective curve.
○ P25、P26 Controller
1. Press F4 → test parameters, choose “I1”、“IN”or“IG”;
2. Set simulation current in the “Current value”;
3. Choose “non-trip”or “trip” in the “Type” to test
4. Press“ESC” and “Yes”to test.
11.3.1 Replacement of shunt release (f), closing electromagnet (x) and under-voltage release (q)
1. Remove
① Remove the cable connector connecting with shunt release, closing electromagnet and
under-voltage release from the wiring terminals of the secondary circuit
② Remove the connector connecting with closing electromagnet, and remove the cover of the
control panel of under-voltage release and then the panel.
③ Loosen the mounting screw on the plank of shunt release, closing electromagnet and under-
voltage release, and then remove the plank.
④ Remove the shunt release, closing electromagnet and under-voltage release
2. Installation
① Put back the shunt release, closing electromagnet and under-voltage release right onto the
appointed place.
② Place the plank and tighten the mounting screw.
③ Link up the closing electromagnet and ready-for-switching-on contact with the connector
put the control panel of the under-voltage inside its shell and cover it.
④ Connect the lead wires of shunt release, closing electromagnet and under-voltage release
with the corresponding wiring terminals of the secondary circuit, under which the lines and the
terminals have the same No.
·61·
12.0 COMMON FAULT AND SOLUTION
Below list the common fault of the circuit breaker in its installing, checking and operating, and
then list the possible reasons and solutions:
No. Technical problems Possible reasons Inspection and solution
Trip (the light of fault ● Over-load trip 1. Check the breaking current value and
indication is on) (indication light for operating time on the intelligent controller;
2. Analyze the operation of load and electric grid;
long-time delay is on)
3. In case of overload, find out and eliminate the
fault at once;
4. If the actual operating current doesn't match
with long-time delayed operating current, please
modify the setting value of long-time delayed
operating current in terms of the actual operating
current to make the suitable protection;
5. Press the reset button and switch the breaker
on again.
·62·
12.0 COMMON FAULT AND SOLUTION
● Reset button Press the reset button and switch the breaker on
doesn't work again
● Error for the closing 1. Check whether the power supply for the closing
electromagnet electro-magnet is equal to 85% Us at least;
2. Check whether there is something wrong
with the closing electromagnet, replace it.
·63·
12.0 COMMON FAULT AND SOLUTION
Unable to be switched ● The breaker can't be 1. Check whether the connection of shunt release
operated be remote controll circuit is reliable. In case of errors for the release,
on
● Unable to switch off the replace it;
breaker with the 2. Check whether the operating mechanism is out
4
“ switching-off” button of mechanical failure.
The draw-out breaker ● The turning mechanism Check whether there are objects falling into the
can't be pushed into is stuck or the gear of the mechanism and check the conditions of rack and
the position of mechanism is damaged due gear
7
“ connected” to the falling objects
The screen on the ● The intelligent controller 1. Check whether the intelligent controller is well
intelligent controller is not electrified; electrified;
can't display ● Input voltage of auxiliary 2. Cut off power supply for the intelligent
power supply is abnormal; controller, then to be electrified. Should the errors
● Secondary output voltage still appear, replace the intelligent controller.
of the socket transformer is
8
abnormal;
● The connection between
the secondary output
terminal of the socket
transformer and the
controller is not reliable.
·64·
12.0 COMMON FAULT AND SOLUTION
The screen on the ● Extra high temperature To reduce the ambient temperature
intelligent around the controller
10
controller displays
“ERR9”
13.0 ACCESSORIES
For BT2-1600 Circuit Breaker For BT2 with frame current of 2000A and above
▲ Switch the breaker off by remote control
▲ Features
·65·
13.0 ACCESSORIES
○ Closing electromagnet
For BT2-1600 Circuit Breaker For BT2 with frame current of 2000A and above
▲ After the circuit breaker is charged, the closing electromagnet will make the energy-charging
spring discharge instantly, and then switch the breaker on quickly.
▲ Features
For BT2-1600 Circuit Breaker For BT2 with frame current of 2000A and above
▲ The circuit breaker has the functions of motor-driven energy-charging and automatic energy-
discharging.
▲ Energy charging can also be done manually.
▲ Features
·66·
13.0 ACCESSORIES
○ Auxiliary Switch
Rated Current
230
AC 300VA
400 6
DC 220 60W
Note: For the standard type of auxiliary switch, there are four pairs of changeover contacts; for the special type,
there are four pieces of normally-opened contacts (NO) and four pieces of normally-closed contacts (NC),
or 6 pieces of NO and 2 pieces of NC, or 2 pieces of NO and 6 pieces of NC.
▲ When the draw-out circuit breaker is at the position of “separated”, the locking stick
can be locked with padlock after being pulled out so that the rocker of the circuit breaker can not be
turned to the position of “test” or “connected”.
▲ Padlock should be provided by users themselves.
·67·
13.0 ACCESSORIES
○ DC Power Module
When power supply of the secondary circuit is DC220V, it should be transformed into DC24V
by this module to provide power supply for the intelligent controller.
·68·
13.0 ACCESSORIES
INPUT input
0.5s 1s 2s 3s
out put
Fuju Electric FA
·69·
13.0 ACCESSORIES
·70·
13.0 ACCESSORIES
when there's data transmission. Fault lamp will light on when the detected address is not complied
with the module address or no breaker is connected with the module. After powering up for the
module or modification of communication address, check mode or baud rate by upper devices, the
module will scan the addresses for several minutes during which the communication between the
module & upper device and between breaker & upper devices will be interrupted.
○ Ready-for-switching-on signal: Ready-for-switching-on information could be got by
upper devices.
○Under-voltage signal: Informations of trip caused by under-voltage could be got by upper
devices.
○Fault-trip signal:Informations of trip caused by overload, short-circuit or ground, etc. could
be got by upper devices.
○ Electrical module for indication of ready-for-switching-on
▲This electrical module indicates that the circuit breaker is ready for switching-on.
▲ Features
·71·
13.0 ACCESSORIES
2m Max.
1QF 2QF
1QF 2QF 0 0
0 1
1 0
○ Linking rod interlock between three pieces of stacked circuit breakers(without BT2-1600)
0 0 0
1QF 2QF 3QF
Circuit 1 0 0
Breaker 1 0 1 0
0 0 1
600~700 0 0 0
1QF 2QF 3QF 1 0 0
Circuit
Breaker 2 0 1 0
1 0 1
0 0 1
180
Pattern three: two sets of power supply plus one
piece of coupling busbar
1QF 2QF 3QF
0 0 0
600~700
Circuit 1QF 2QF 3QF
1 0 0
Base point Breaker 3
0 1 0
0 0 1
1 1 0
Breaker base 0 1 1
1 0 1
·72·
13.0 ACCESSORIES
0 0 0
1QF 2QF 3QF 1 0 0
0 1 0
0 0 1
1 1 0
0 1 1
1 0 1
·73·
13.0 ACCESSORIES
○ Counter
Counting mechanical operation times accumulatively, clear at a glance.
·74·
14.0 OUTLINE DIMENSIONS AND INSTALLATION DIMENSIONS
● BT2-1600 Intelligent Air Circuit Breaker with three poles (Draw-out type)
Current
specifications L( mm )
Direction A
800A,1000A,
15
1250A,1600A 70 70
12-Φ11
200A,400A,
10
630A 25 50
Outside of the
cabinet door
A
51
Base point
72.5 1 02.5 86
D 38 150 60
77.5
46 297
“ Separated” po sition
Horizontal (rear connected)
C
Direction D
Outside of the
cabinet door
2-Φ6.5
51
15
12-Φ11
2-6.5×8.5
Base point
72.5 102.5
77.5
46 297
“Separated” posi tion
Ve rtical ( rear connected )
Direction C
70 70
·75·
14.0 OUTLINE DIMENSIONS AND INSTALLATION DIMENSIONS
● BT2-1600 Intelligent Air Circuit Breaker with four poles (Draw-out type)
Current
specifications L( mm )
800A,1000A,
15 Direction A
1200A,1600A
70 70 70
16-Φ11
200A,400A,
10
630A
25 50
N pole
Ou tside of the
cab inet door
A
51
Base point
“Separated” position
Hor izontal ( rear connected )
C
Outside of the
cabinet door
Direction D 51
15
2-Φ6.5 16-Φ11
Base point
2- 6.5×8.5
72.5 102.5
77.5
46 297
“Separated” posi tion
Ve rtical ( rear connected )
Direction C
70 70 70
L
N pole
·76·
14.0 OUTLINE DIMENSIONS AND INSTALLATION DIMENSIONS
● BT2-1600 Intelligent Air Circuit Breaker with three poles (fixed type)
Current
specifications L( mm ) Direction A
50
800A,1000A, 25
15 12-Φ11
1200A,1600A
200A,400A, 70 70
10
630A
Outside of the
cabinet door
A
32
4-Φ6.5
10 234 10
100 38.5 50.6
19 2
197
32
4-Φ6.5
15
214
100 38.5 50.6
Breaker base 234
192
1 97
Aperture dim ensions of the back plate
at the time of hanging type i nstallation Vertical (rear connected)
Direction C
L
70 70
·77·
14.0 OUTLINE DIMENSIONS AND INSTALLATION DIMENSIONS
● BT2-1600 Intelligent Air Circuit Breaker with four poles (fixed type)
Direction A
Current 50
specifications L( mm )
25
16-Φ11
800A,1000A,
15
1200A,1600A
70 70 70
200A,400A, N pol e
10
630A
Outside of the
cabinet door
A
32
4-Φ6.5
10 304 10
100 38.5 50.6
192
197
314
Outside of the
cabinet door C
32
4-Φ6.5
15
284
100 38.5 50.6
Breaker base 304
192
197
Aperture dime nsions of the b ack plate
at the time of hanging type installation Vertical (rear connected)
Direction C
L
70 70 70
N p ole
·78·
14.0 OUTLINE DIMENSIONS AND INSTALLATION DIMENSIONS
● BT2-2000 Intelligent Air Circuit Breaker with three poles (Draw-out type)
Current
specifications L(mm ) H(mm) A(mm )
Direction A
2000A 20 20 30
95 95
630A,800A 24-Φ11
1000A,1250A 15 15 25
1600A
30 70
Outside of the
cabinet door
A
61
Base point
10
97 175 41 265 41
102 D
47 390
“Separ ated” positio n
Horizo ntal ( rear connected )
C
Outsi de of the
Direction D cabinet door 60
30 15
2-Φ14
24-Φ11
Base point
11×17
Φ11
10
97 175
102
47 390 66
“Separated” position
Vertical ( rear connected )
Direction C
95 95
10
60
30
·79·
14.0 OUTLINE DIMENSIONS AND INSTALLATION DIMENSIONS
● BT2-2000 Intelligent Air Circuit Breaker with four poles (Draw-out type)
Current Direction A
specifications L(mm ) H(mm) A(mm )
95 95 95 32-Φ11
2000A 20 20 30
630A,800A
1000A,1250A 15 15 25
1600A N pole 30 70
Outside of the
cabinet door
A
61
Base point
10
97 175
D 41 360 41
102
47 390
“Separated” position
Horizontal ( rear connect ed )
C
Outside of the
Direction D cabinet door
60
2-Φ14 30 15
32-Φ11
11×17 Base point
Φ11
10
97 175
102
47 39 0 66
“Separated” position
Vertical ( rear connecte d)
Direction C
95 95 95
N极 10
60
30
·80·
14.0 OUTLINE DIMENSIONS AND INSTALLATION DIMENSIONS
● BT2-2000 Intelligent Air Circuit Breaker with three poles (Fixed type)
Current L A W B
specifications (mm) (mm) (mm) (mm) Direction A
2000A 20 269 20 13 95 95
24-Φ11
630A,800A
1000A,1250A 15 264 15 3
1600A 30 60
Outside of the
cabinet door
A
61
Base point
Outside of the
cabinet door
C
60
Direction C
95 95
24-Φ11
10 Base point
60
30
15 30
150 6 9.5
285 94
·81·
14.0 OUTLINE DIMENSIONS AND INSTALLATION DIMENSIONS
● BT2-2000 Intelligent Air Circuit Breaker with four poles (Fixed type)
Current L A W B
specifications (mm) (mm) (mm) (mm)
Direction A
2000A 20 269 20 13
95 95 95 32-Φ11
630A,800A
1000A,1250A 15 264 15 3
1600A
N pole 30 60
Outside of the
cabinet door
A
61
Base point
Outside of the
cabinet door C
Direction C
95 95 95 60
10
N pole 60
30
32-Φ11
Base point
15 30
150 69.5
285 94
·82·
14.0 OUTLINE DIMENSIONS AND INSTALLATION DIMENSIONS
● BT2-2500 Intelligent Air Circuit Breaker with three poles (Draw-out type)
Current
specifications L( mm )
Direction A
2000A, 2500A 20 95 95
24-Φ11
1250A,1600A 15
30 70
Outside of the
cabinet door
A
62
Base point
10
97 175 41 265 41
D
102
47 390
Outside of the
Direction D cabinet door
62
2-Φ14
24 -Φ11
10
97 175
102
47 39 0
“Separated” position
Vertica l ( rear connec ted )
Direction C
95 95
·83·
14.0 OUTLINE DIMENSIONS AND INSTALLATION DIMENSIONS
● BT2-2500 Intelligent Air Circuit Breaker with four poles (Draw-out type)
Current
specifications L(mm)
Direction A
2000A ,2500A 20 95 95 95
32 -Φ11
1250A ,1600A 15
30 70
N po le
Outside of the
cabinet door
A
62
Base point
10
97 175
D 41 360 41
102
47 390
“Sep arated” posi tion
Horizontal ( rear connect ed)
Outside of the
cabinet door
62
Direction D
32-Φ1 1
2-Φ14
Base point
11×1 7 10
Φ11 97 175
102
47 390
Direction C
95 95 95
L
N极
·84·
14.0 OUTLINE DIMENSIONS AND INSTALLATION DIMENSIONS
● BT2-2500 Intelligent Air Circuit Breaker with three poles (Fixed type)
Direction A
Current L C 95 95
24-Φ11
specifications (mm ) ( mm )
2000A,2500A 20 132
30 60
1250A,1600A 15 134.5
Outside of the
cabinet door
A
61
Base point
● BT2-2500 Intelligent Air Circuit Breaker with four poles (Fixed type)
Direction A
Current L C
specifications (mm ) ( mm ) 95 95 95 32-Φ11
2000A,2500A 20 132
1250A,1600A 15 134.5
N pole 30 60
Outside of the
cabinet door
A
61
Base point
·85·
14.0 OUTLINE DIMENSIONS AND INSTALLATION DIMENSIONS
● BT2-4000 Intelligent Air Circuit Breaker with three poles (Draw-out type)
Direction A
1 30 130 24-Φ17
50 100
Outside of the
cabinet door A
104
Base point
10
97 175 37 327 37
B
102
47 395
“Separated” position
Horizontal ( r ear connected )
C
Direction B
Outside of the
Φ11 cabinet door
104
50 25
Base point
Base point 10
97 175
102
47 395
“Separated” position
Vertical ( re ar connected)
Direction C
11 3 113
10
30
·86·
14.0 OUTLINE DIMENSIONS AND INSTALLATION DIMENSIONS
● BT2-4000 Intelligent Air Circuit Breaker with four poles (Draw-out type)
Direction A
N pole 50 100
Outside of the
cabinet door A
104
Base point
10
97 175
B 37 440 37
102
47 395
“Separated” position
Horizontal ( rear connected )
C
Direction B
Outside of the
Φ11 cabinet door
104
50 25
Base point
Base point 10
97 175
102
47 395
“Separat ed”position
Vertical ( rear connect ed )
Direction C
113 113 113
10
N pole
30
·87·
14.0 OUTLINE DIMENSIONS AND INSTALLATION DIMENSIONS
●BT2-4000 Intelligent Air Circuit Breaker with three poles (Fixed type)
Direction A
113 11 3 24-Φ13
40 80
Outside of the
cabinet door
A
82
Base point
● BT2-4000 Intelligent Air Circuit Breaker with four poles (Fixed type)
Direction A
113 113 113 32-Φ13
N pole 40 80
Outside of the
cabinet door
A
82
Base point
·88·
14.0 OUTLINE DIMENSIONS AND INSTALLATION DIMENSIONS
● BT2-6300 Intelligent Air Circuit Breaker with three poles (Draw-out type)
Direction A
113 126.5 130 126.5 113 4 8-Φ17
50 100
A
183
Outside of the
cabinet door
104
Base point
6-Φ11 Base point
10
77 258
82 693
47 395
767
“Separated” position
Horizontal ( rear connected)
Current specifications:In=4000A、5000A C
Outside of the
cabinet door
10 4
50 25
Direction C
Base point
6-Φ11
10
10
30
77 258
82
47 39 5
“Separated” position
Vertical ( rear connected )
Current specifications:In=4000A、5000A、6300A
·89·
14.0 OUTLINE DIMENSIONS AND INSTALLATION DIMENSIONS
● BT2-6300 Intelligent Air Circuit Breaker with four poles (Draw-out type)
Direction A
N pole 50 100
A 239.5
Outside of
the cabinet
door
104
10
77 258
82 95
47 395
919
993
“Separated” position
Horizontal ( r ear connected )
Current specifications:In=4000A、5000A
C
Outside of
the cabinet
door
104
50 25
Direction C
113 113 113 140 113 113 113
64-Φ17
10
30 Base point
8-Φ11
10
77 258
82
47 395
“Separated” position
Vertical ( re ar connected )
Current specifications:In=4000A、5000A、6300A
·90·
14.0 OUTLINE DIMENSIONS AND INSTALLATION DIMENSIONS
● BT2-6300 Intelligent Air Circuit Breaker with three poles (Fixed type)
Direction A
205
50 55 50
23 9. 5 239.5
Outside of
the cabinet
door
A
134
Base point
1 50 69.5 11 7 60
Base point 11
2 85
290
● BT2-6300 Intelligent Air Circuit Breaker with four poles (Fixed type)
Direction A
205
50 55 50
Outside of
the cabinet
door
A
134
Base point
·91·
14.0 OUTLINE DIMENSIONS AND INSTALLATION DIMENSIONS
BT2-1600 Intelligent Air Circuit Breaker with BT2-1600 Intelligent Air Circuit Breaker with
three poles (Draw-out type) four poles (Draw-out type)
The drawing of aperture dimensions for The drawing of aperture dimensions for
installing cover of door frame installing front cover of door frame
Distance from the panel center of the circuit Distance from the panel center of the circuit
breaker to the right hinge of cabinet door should be at breaker to the right hinge of cabinet door should be at
least 227mm least 262mm
BT2-1600 Intelligent Air Circuit Breakers BT2-1600 Intelligent Air Circuit Breakers
with three poles ( fixed type) with four poles (fixed type)
The drawing of aperture dimensions for The drawing of aperture dimensions for
mounting cover of door frame mounting front cover of door frame
Distance from the panel center of the circuit Distance from the panel center of the Circuit
breaker to the right hinge of cabinet door should be at Breaker to the right hinge of cabinet door should be at
least 227mm least 262mm
·92·
14.0 OUTLINE DIMENSIONS AND INSTALLATION DIMENSIONS
BT2-2000 Intelligent Air Circuit Breaker with BT2-2000 Intelligent Air Circuit Breaker with
three poles (Draw-out type) four poles (Draw-out type)
The drawing of aperture dimensions for The drawing of aperture dimensions for
installing front cover of door frame installing front cover of door frame
Distance from the panel center of the circuit Distance from the panel center of the circuit
breaker to the right hinge of cabinet door should be at breaker to the right hinge of cabinet door should be at
least 256mm least 303.5mm
BT2-2000 Intelligent Air Circuit Breaker with BT2-2000 Intelligent Air Circuit Breaker with
three poles (Fixed type) four poles (Fixed type)
The drawing of aperture dimensions for The drawing of aperture dimensions for
installing front cover of door frame installing front cover of door frame
Distance from the panel center of the circuit Distance from the panel center of the circuit
breaker to the right hinge of cabinet door should be at breaker to the right hinge of cabinet door should be at
least 256mm least 303.5mm
·93·
14.0 OUTLINE DIMENSIONS AND INSTALLATION DIMENSIONS
BT2-2500 Intelligent Air Circuit Breaker with BT2-2500 Intelligent Air Circuit Breaker with
three poles (Fixed type) four poles (Fixed type)
The drawing of aperture dimensions for The drawing of aperture dimensions for
installing front cover of door frame installing front cover of door frame
Distance from the panel center of the circuit Distance from the panel center of the circuit
breaker to the right hinge of cabinet door should be at breaker to the right hinge of cabinet door should be at
least 256mm least 303.5mm
·94·
14.0 OUTLINE DIMENSIONS AND INSTALLATION DIMENSIONS
BT2-4000 Intelligent Air Circuit Breaker with BT2-4000 Intelligent Air Circuit Breaker with
three poles (Draw-out type) four poles (Draw-out type)
The drawing of aperture dimensions for The drawing of aperture dimensions for
installing front cover of door frame installing front cover of door frame
Distance from the panel center of the circuit Distance from the panel center of the circuit
breaker to the right hinge of cabinet door should be at breaker to the right hinge of cabinet door should be at
least 264mm least 320.5mm
BT2-4000 Intelligent Air Circuit Breaker with BT2-4000 Intelligent Air Circuit Breaker with
three poles (Fixed type) four poles (Fixed type)
The drawing of aperture dimensions for The drawing of aperture dimensions for
installing front cover of door frame installing front cover of door frame
Distance from the panel center of the circuit Distance from the panel center of the circuit
breaker to the right hinge of cabinet door should be at breaker to the right hinge of cabinet door should be at
least 264mm least 320.5mm
Breaker base
Breaker base
8- 6
328 10- 6 100
366 441
479
·95·
14.0 OUTLINE DIMENSIONS AND INSTALLATION DIMENSIONS
BT2-6300 Intelligent Air Circuit Breaker with BT2-6300 Intelligent Air Circuit Breaker with
three poles (Draw-out type) four poles (Draw-out type)
The drawing of aperture dimensions for The drawing of aperture dimensions for
installing front cover of door frame installing front cover of door frame
Distance from the panel center of the circuit Distance from the panel center of the circuit
breaker to the right hinge of cabinet door should be breaker to the right hinge of cabinet door should be at
at least 264mm least 320.5mm
BT2-6300 Intelligent Air Circuit Breaker with BT2-6300 Intelligent Air Circuit Breaker with
three poles (Fixed type) four poles (Fixed type)
The drawing of aperture dimensions for The drawing of aperture dimensions for
installing front cover of door frame installing front cover of door frame
Distance from the panel center of the circuit Distance from the panel center of the circuit
breaker to the right hinge of cabinet door should be breaker to the right hinge of cabinet door should be
at least 264mm at least 320.5mm
·96·