You are on page 1of 1

STRESSING REPORT

Pier No. : P19


Segment No.: pier table K0

Tendon No & Size: T00-1 12T15


Strand coil No: 4B4177
Designed or Assumed
Design Jacking Force (F0): 2310 KN Elongation(Design): L 81 mm
Elongation(Design): R mm
Design strand Area: 140 mm2 Design Modulus of Elasticity: 197000 N/mm2
Actual strand Area: 141.8 mm2 Actual Modulus of Elasticity: 198000 N/mm2

Corrected Elongation E x A (Design) L R


= Design elongation x =79.6 mm
(mm) E x A (Actual) 79.6
95% 75.6
105% 83.5
F0
Corrected Pressure (Mpa) = =35.24 Mpa
(S) x (1-K1-K2)

Lj: Length from Anchor head to pulling head 400mm


K1: Friction loss of Anchorage components 2%
K2: Friction factor of the jack 1.40%
READINGS END 1 END 2
Jack # : 230724 Gauge # : 2021.3.2775 Jack area (S)= 678.6 cm2 Jack # : Gauge # : D Jack area= cm2
Equivalent Gauge Pressure = 35.2 Mpa Equivalent Gauge Pressure = Mpa
95% 33.5 Mpa 95% Mpa
105% 37.0 Mpa 105% Mpa
Grade of Pressure Readings Increment Elongation Pressure Readings Increment Elongation
force Mpa mm mm mm Mpa mm mm mm
0.10Pk 3.83 200 11.0 11.0
0.20Pk 7.04 205 5.0 16.0
0.40Pk 13.77 220 15.0 31.0
0.60Pk 20.70 240 20.0 51.0
0.80Pk 27.64 255 15.0 66.0
1.00Pk 34.78 285 30.0 96.0
1.05Pk 36.54
276 (A)= 96.0 (A')=
( B ) = Dead end Slip = 3.1 mm ( B' ) = Dead end Slip =
( C ) = Active End Slip = 9.0 mm ( C' ) = Active End Slip =
( D ) = Jack inside Elongation = 2.74 mm ( D' ) = Jack inside Elongation =
Actual Elongation = (A)-(B+C+D) = 81.18 mm Actual Elongation = (A')-(B'+C'+D') =
% Elongation = 102% OK % Elongation =
% Pressure = 99% OK % Pressure =
Remarks:

Acceptance (Sự chấp thuận): o Accepted (Chấp thuận) o Not Accepted (Không chấp thuận)
CONTRACTOR ( Nhà thầu )
CONSULTANT ( Tư vấn )
Sub-Contractor Contractor (Kumho E&C)
Project Manager Site Engineer Constructi on Si te Engi neer

You might also like