S E R I A L C O M M U N I C A T I O N I N T E R F A C E F O R I N D U S T R I A L A U T O M A T I O N

ADAM-4510/4510S ADAM-4520/4522
RS-422/485 Repeater RS-232 to RS-422/485 Converter

Introduction Tough industrial design


You can power the ADAM-4510/4510S and ADAM-
Most industrial computer systems come with RS- 4520/4522 with any unregulated power source
232 serial ports as standard. Though widely between +10 and +30 VDC.
accepted, RS-232 has limited transmission speed,
range and networking capabilities. The RS-422 Their industrial-grade plastic shells can be
and RS-485 standards overcome these limitations mounted on a DIN-rail, panel or in a piggybacked
by using differential voltage lines for data and stack. You make signal connections through plug-
control signals. The ADAM-4520/4522 converter in screw terminal blocks, guaranteeing easy
lets you take advantage of RS-422 and RS-485 installation, maintenance and modification
on systems originally equipped with RS-232. It
transparently converts RS-232 signals into
isolated RS-422 or RS-485 signals. You don't need Features
to change your PC's hardware or your software. • Automatic internal RS-485 bus supervision
The ADAM-4520/4522 lets you easily build an
industrial grade, long distance communication • No external flow control signals required for
system with standard PC hardware. RS-485
www.DataSheet4U.com
The ADAM-4510/4510S repeater simply amplifies, • Minimum 3000 VDC isolation protection
or boosts, existing RS-485 signals to enable them (ADAM-4510S/4520 only)
to cover longer distances. It extends the • Transient suppression on RS-485 data lines
communication distance by 4000 ft (1200 m) or
extends the number of connected nodes by 32. • Baudrate up to 115.2 Kbps
• Networking up to 4000 feet
Intelligent RS-485 control
• Reserved space for termination resistors
The RS-485 standard supports half-duplex
communication. This means that just two wires are • Power and data flow indicator for troubleshoot-
needed to both transmit and receive data. Handshak- ing
ing signals (such as RTS, Request To Send) are • Power requirement: +10 to +30 VDC
normally used to control the direction of the data flow.
A special I/O circuit in the ADAM-4510/4510S and • Mounts easily on DIN-rail or panel
ADAM-4520/4522 automatically senses the
direction of the data flow and switches the
Specifications
transmission direction. No handshaking signals
are necessary—you can build an RS-485 network Common
with just two wires. This RS-485 control is
completely transparent to the user. Software • Power requirement:
written for half-duplex RS-232 works without Unregulated +10 to +30 VDC with protection
modification. from power reversals
• Case: ABS with captive mounting hardware
Isolation (ADAM-4510S/4520 only) • Accessories (Supplied):
The ADAM-4510S/4520's Opto-isolators provide NYLON DIN-rail Mounting Adapter
3000 VDC of isolation to protect the host computer SECC Panel Mounting Bracket
from ground loops and destructive voltage spikes
on the RS-422/485 data lines. • Plug-in screw terminal wiring:
Accepts AWG 1-#12 to #22 (0.5 to 2.5 mm)
wires
Surge protection (RS-485 only)
ADAM-4510/4510S and ADAM-4520/4522 offer ADAM-4510/4510S specifications
internal surge-protection on their data lines.
• Baudrate (bps): 1200, 2400, 4800, 9600, 19.2 K,
Internal high speed transient suppressors on
38.4 K, 57.6 K, 115.2 K, RS-422 (switchable)
each data line protect the modules from
dangerous voltages levels or spikes. • Isolation Voltage: 3000 VDC (4510S only)

ADAM and the ADAM logo are trademarks of Advantech. Part no. 2000000290 4th Edition Printed in Taiwan Oct 1998
Data Format
• RS-422/RS-485 interface connector: plug-in Baud Rate Setting (SW1)
Setting (SW2)
screw terminal ON 1.8432 MHz
OSC

• Power consumption: 1 W maximum GND

TxD
RS-232 RS-422/ DATA1 +
RxD
Receiver/ CommunicationDATA RS-485 RS-485

ADAM-4520/4522 specifications RTS


GND Driver
DATA
Controller Receiver/
DATA1 -

Tx1 +
Driver
Tx1 -
• Baudrate (bps): 1200, 2400, 4800, 9600, 19.2 Opto-Coupled
Isolation GND Rx1 +
RS-422

K, 38.4 K, 57.6 K, 115.2 K, RTS control and Direction


Rx1 -

Control
RS-422 mode (switchable) Logic

• Isolation voltage: 3000 VDC (4520 only) +5 V GND

• RS-232 interface connector: Female DB-9 P.S.

• RS-422/RS-485 interface connector: plug-in +5 V Rect & Power Power Input


Filter Converter +10 ~ +30 V
screw terminal Power
Isolation

• Power consumption: 1.2 W maximum


ADAM-4520 Converter Function Diagram
Operating environment
Data Format
• Operating temperature: Baud Rate
Setting (J2)
Setting (J1)

-10 ~ 70o C (14 ~ 158o F) 1.8432 MHz


OSC
• Storage temperature: GND

-25 ~ 85o C (-13 ~ 185oF) TxD


RS-232
RS-422/ DATA1 +
CommunicationDATA RS-485 RS-485
Receiver/DATA
RxD
DATA1 -
RTS Controller Receiver/
• Humidity: 5 ~ 95%, non-condensing GND Driver Driver
Tx1 +
Tx1 -
RS-422
GND Rx1 +

www.DataSheet4U.com Direction
Rx1 -

Function diagrams Control


Logic

Data Format
Baud Rate Setting (SW1) +5 V Rect & Power Power Input
ON
Setting (SW2)
1.8432 MHz Filter Converter +10 ~ +30 V
OSC

GND GND

RS-422/ RS-422/
RS-485
DATA0 +
RS-485 D A T A CommunicationDATA
RS-485
DATA1 +
DATA1 -
RS-485 ADAM-4522 Converter Function Diagram
Receiver/ Controller Receiver/
DATA0 -
Tx1 +
Rx0 +
Driver Driver Tx1 -
Rx0 -
RS-422
RS-422 Rx1 +
Tx0 + GND

Installation
GND
Tx0 - Rx1 -
Direction
Control
Logic

Initial inspection
+5 V Rect & Power Power Input
Filter Converter +10 ~ +30 V We carefully inspected the ADAM-4510/4510S
and 4520/4522 Modules both mechanically and
ADAM-4510 Repeater Function Diagram electrically before we shipped them. They should
be free of marks and scratches and in perfect
order on receipt.
Data Format
Baud Rate
Setting (SW2)
Setting (SW1)
As you unpack the modules, check them for
1.8432 MHz
ON
OSC signs of shipping damage (damaged box,
GND GND
scratches, dents, etc.). If it is damaged or fails to
DATA0 +
RS-422/ RS-422/ meet our specifications, notify our service
RS-485 RS-485 DATA Communication RS-485
DATA1 +
RS-485
DATA0 -
Receiver/ Controller DATA DATA
Receiver/
DATA1 -
department or your local sales representative
Rx0 +
Driver Driver
Tx1 +

RS-422
Rx0 -
Tx0 + GND Opto-Coupled
Tx1 -
RS-422 immediately. Also, call the carrier immediately and
GND Rx1 +
Tx0 -
Direction
Isolation
Rx1 - retain the shipping carton and packing material for
Control
Logic inspection by the carrier. We will then make
+5 V GND
arrangements to repair or replace the unit.
P.S.

+5 V Rect &
Filter
Power
Converter
Power Input
+10 ~ +30 V
Switch and jumper settings
Power
Isolation

Switch settings
ADAM-4510S Repeater Function Diagram DIP switches or jumpers (4522 only) in the ADAM

ADAM-4510/4510S/4520/4522 User's Manual


converter and repeater modules set the data
ADAM-4510/4510S Baud rate settings (SW2)
format (number of bits) and baudrate for the ADAM
network. You can configure the other modules in Baud Rate 1 2 3 4 5 6 7 8 9
the network via software commands. Your program
and the PC's serial port should match the settings 1200 bps l ¡ ¡ ¡ ¡ ¡ ¡ ¡ ¡
of the converter and repeater modules.
2400 bps ¡ l ¡ ¡ ¡ ¡ ¡ ¡ ¡
SW1 4800 bps ¡ ¡ l ¡ ¡ ¡ ¡ ¡ ¡
Switch 1 controls the data format. Data can be 9, * 9600 bps ¡ ¡ ¡ l ¡ ¡ ¡ ¡ ¡
10, 11 or 12 bits. The factory default is 10 bits:
one start bit, eight data bits, no parity bit and one 19.2 Kbps ¡ ¡ ¡ ¡ l ¡ ¡ ¡ ¡
stop bit. 38.4 Kbps ¡ ¡ ¡ ¡ ¡ l ¡ ¡ ¡
When using the converter in combination with 57.6 Kbps ¡ ¡ ¡ ¡ ¡ ¡ l ¡ ¡
other ADAM modules, do not change the default
setting as ADAM modules have a fixed data format 115.2 Kbps ¡ ¡ ¡ ¡ ¡ ¡ ¡ l ¡
of ten data bits. The option of changing to 9, 11 or RS-422 ¡ ¡ ¡ ¡ ¡ ¡ ¡ ¡ l
12 bits is for use with other modules (other than
ADAM modules) that have different data formats. ¡ = Open l = Closed * = Default
Should you change the data format, be aware that
you will have to change the data format settings ADAM-4520/4522 RS-232/RS-485
on all the other modules in the network.
Converter Module
The following tables illustrate the switch
SW2 settings for the Converter Module.
Switch 2 sets the baudrate. The options range
www.DataSheet4U.com
from 1200 bps to 115.2 Kbps. The factory default
is 9600 bps. Be aware that when you change the ADAM-4520/4522 Data format settings
baudrate, you have to change the baudrate for all (SW1)
the connected modules accordingly. If the RS-422 Data Format 1 2
mode is ON, the baudrate doesn't need to be set. 9 bits ¡ ¡

Default settings
* 10 bits l ¡

Since neither module is addressable by the host 11 bits ¡ l


computer, the baud rate and data format must be
12 bits l l
set using SW1 and SW2 located inside the
module. The default settings are: ¡ = Open l = Closed * = Default

* Default settings for both modules ADAM-4520/4522 Baud rate settings (SW2)
Function Setting Baud Rate 1 2 3 4 5 6 7 8 9 10
Baud rate 9600 bps RTS control l ¡ ¡ ¡ ¡ ¡ ¡ ¡ ¡ ¡
Data format 10 bits
1200 bps ¡ l ¡ ¡ ¡ ¡ ¡ ¡ ¡ ¡
ADAM-4510/4510S RS-422/RS-485 2400 bps ¡ ¡ l ¡ ¡ ¡ ¡ ¡ ¡ ¡
Repeater Module
4800 bps ¡ ¡ ¡ l ¡ ¡ ¡ ¡ ¡ ¡
The following tables illustrate the switch settings
for the Repeater Module. * 9600 bps ¡ ¡ ¡ ¡ l ¡ ¡ ¡ ¡ ¡
19.2 Kbps ¡ ¡ ¡ ¡ ¡ l ¡ ¡ ¡ ¡
ADAM-4510/4510S Data format settings
38.4 Kbps ¡ ¡ ¡ ¡ ¡ ¡ l ¡ ¡ ¡
(SW1)
Data Format 1 2 57.6 Kbps ¡ ¡ ¡ ¡ ¡ ¡ ¡ l ¡ ¡
9 bits ¡ ¡ 115.2 Kbps ¡ ¡ ¡ ¡ ¡ ¡ ¡ ¡ l ¡
* 10 bits l ¡ RS-422 ¡ ¡ ¡ ¡ ¡ ¡ ¡ ¡ ¡ l
11 bits ¡ l ¡ = Open l = Closed * = Default
12 bits l l
¡ = Open l = Closed * = Default
ADAM-4510/4510S/4520/4522 User's Manual
Power supply Communication wiring
We recommend that shielded-twisted-pair cables
For the ease of use in industrial environments the that comply with the EIA RS-485 standard be
ADAM modules are designed to accept industry used with the ADAM network to reduce
standard +24 VDC unregulated power. Operation is interference. Only one set of twisted-pair cables
guaranteed when using any power supply between is required to transmit both Data and RTS signals.
+10 and +30 VDC. Power ripples must be limited to We advise that the following standard colors (as
200 mV peak to peak while the voltage in all indicated on the modules) be used for the
cases must be maintained between +10 and +30 communication lines:
VDC. All power supply specifications are
referenced at module connector. DATA + (Y) è Yellow
DATA - (G) è Green
The power cables should be selected according to
the number of modules connected and the length
of the power lines. When using a network with Basic configuration hook-up
long cables, we advise the use of thicker wire to Before placing a module in an existing network,
limit the line voltage drop. In addition to serious the module should be properly configured. The two
voltage drops, long voltage lines can also cause following diagrams show typical layouts for both
interference with communication wires. modules.
(B) GND 10
(G) DATA-

(R) +Vs

DATA + DATA +
www.DataSheet4U.com DATA - DATA -

RS-232
RS-485 Device TxD (2) RxD (2)
RxD (3) TxD (3)
RTS (7) RTS (7)
Rx + GND (5) GND (5)
- Rx -
Tx +
Tx +
Tx -
- Power Supply Tx -
Rx +
Rx -
DB-9 female
connector
Host

+ +10~30 V
+ RS-422 Device

We advise that the following standard colors (as


indicated on the modules) be used for power
ADAM-4520/4522 Converter Connection Diagram
lines:

+Vs è (R) Red


GND è (B) Black

DATA + DATA0 + DATA1 + DATA +


DATA - DATA0 - DATA1 - DATA -

RS-485 Device RS-485 Device

Tx + Rx0 + Rx +
Tx1 +
Tx - Rx0 - Rx -
Tx1 -
Rx + Tx0 + Tx +
Rx1 +
Rx - Tx0 - Tx -
Rx1 -

RS-422 Host RS-422 Slave

ADAM-4510/4510S Repeater Connection Diagram

ADAM-4510/4510S/4520/4522 User's Manual