You are on page 1of 8

PALU-3 COAL FIRED STEAM

POWER PLANT (2 x 50 MW) CONSORTIUM


PT. PLN (Persero) WIKA-DHI-KOEN

Document No. Rev. : 00


COMPREHENSIVE STUDY OF
18JE05-DOC-ZEN-57-0001
UPVC DRAIN, SEWAGE AND SOIL PIPE Page No. : 1 of 8

CLIENT : PT. PLN (PERSERO)

CONSULTANT : PT. PLN ENJINIRING


CONSULTANT
: A5.I2.D1.19.01-DOC-ZEN-57-C-0001
DOCUMENT NO.
CONTRACTOR : CONSORTIUM WIKA-DHI-KOEN

PROJECT NAME : PALU-3 COAL FIRED STEAM POWER PLANT (2 x 50 MW)

PROJECT NO. : 18JE05

LOCATION : DONGGALA, SULAWESI TENGAH , INDONESIA

00 5-Mar-21 Issued For Approval ADB SAL AF

REV DATE DESCRIPTION PREPARED CHECKED APPROVED

This document and the information contained in it is issuer property. It cannot be used, reproduced, transmitted, and/or
disclosed without prior written permission.
PALU-3 COAL FIRED STEAM
POWER PLANT (2 x 50 MW) CONSORTIUM
PT. PLN (Persero) WIKA-DHI-KOEN

Document No. Rev. : 00


COMPREHENSIVE STUDY OF
18JE05-DOC-ZEN-57-0001 DRAIN, SEWAGE, & SOIL PIPE Page No. : 2 of 8

REVISION NOTES

Rev Section / Page Change Description

HOLDS

Page No. Hold Description


PALU-3 COAL FIRED STEAM
POWER PLANT (2 x 50 MW) CONSORTIUM
PT. PLN (Persero) WIKA-DHI-KOEN

Document No. Rev. : 00


COMPREHENSIVE STUDY OF
18JE05-DOC-ZEN-57-0001 DRAIN, SEWAGE, & SOIL PIPE Page No. : 3 of 8

TABLE OF CONTENTS

1 GENERAL .................................................................................................................................. 4
1.1 Introduction ....................................................................................................................... 4
1.2 Introduction ....................................................................................................................... 4
2 DEFINITION AND ABBREVIATIONS ........................................................................................ 4
2.1 Definitions ......................................................................................................................... 4
2.2 Abbreviations..................................................................................................................... 4
3 REFERENCES ........................................................................................................................... 4
3.1 Code and Standards.......................................................................................................... 4
3.2 Project Specifications ........................................................................................................ 5
4 MATERIAL SPECIFICATION BASED ON STANDARD ............................................................ 5
4.1 Material specification based on JIS K6741 ........................................................................ 5
4.2 Material Specification based on ISO 3633 and ISO 4435 ................................................. 6
4.3 Material Specification based on SNI 06-0162-1987 .......................................................... 6
4.4 Material Specification based on Market ............................................................................ 7
5 COMPARISON ........................................................................................................................... 7
5.1 Dimensioning and wall Thickness Comparison .................................................................. 7
6 CONCLUSION ........................................................................................................................... 8
PALU-3 COAL FIRED STEAM
POWER PLANT (2 x 50 MW) CONSORTIUM
PT. PLN (Persero) WIKA-DHI-KOEN

Document No. Rev. : 00


COMPREHENSIVE STUDY OF
18JE05-DOC-ZEN-57-0001
UPVC DRAIN, SEWAGE AND SOIL PIPE Page No. : 4 of 8

1 GENERAL
1.1 Introduction
In order for fulfilling the electricity demand in Central Sulawesi, PT. Perusahaan Listrik Negara
(Persero) has planned to build a Coal Fired Steam Power Plant Palu-3 for supplying the
electric power for public use. The power plant will consist of two (2) units, having a minimum
Net Output 2x50 MW. The plant is located on Lero Tatari Village, Donggala Regency,
Sulawesi Tengah Province, Indonesia.

1.2 Introduction
This document cover technical justification of usage of the UPVC Drain, Sewage And Soil
Pipe applied for Coal Fired Steam Power Plant Palu-3.
The reason of why this document is made because the material availability on Local Market,
and considering the design.
Based on design, plumbing pipe for drain, sewage and soil designed non pressure deisgn use
since the design is use gravity for the conveyance of fluid. The material specified in Contract
as per JIS K6741 is not available on local market on site, and need long time delivery to
purchase.
The above technical explaination as the basis for Contractor’s proposal to use equals UPVC
Drain, Sewage And Soil Pipe material availability on local market.

2 DEFINITION AND ABBREVIATIONS


2.1 Definitions
Company PT. PLN (Persero)
Contractor Consortium WIKA-DHI-KOEN
Supplier Supplier of the equipment, including sub-suppliers appointed by the
Supplier to carry out part or all of the work
2.2 Abbreviations
ISO International Standard Organization
JIS Japanese Industrial Standard
SNI Standar Nasional Indonesia

3 REFERENCES
3.1 Code and Standards
JIS K6741 Uplasticised Poly ( Vinly Chloride) (PVC-U) Pipes
ISO 4435 Plastics piping systems for non-pressure underground drainage and
sewerage - Unplasticized poly(vinyl chloride) (PVC-U)
ISO 3633 Plastics piping systems for soil and waste discharge (low and high
temperature) inside buildings — Unplasticized poly(vinyl chloride)
(PVC-U)
SNI 06-0162-1987 Pipa PVC untuk saluran buangan didalam dan dan diluar bangunan
PALU-3 COAL FIRED STEAM
POWER PLANT (2 x 50 MW) CONSORTIUM
PT. PLN (Persero) WIKA-DHI-KOEN

Document No. Rev. : 00


COMPREHENSIVE STUDY OF
18JE05-DOC-ZEN-57-0001 DRAIN, SEWAGE, & SOIL PIPE Page No. : 5 of 8

3.2 Project Specifications


18JE05-SPC-ZEN-50-0006 Specification for Architectural Work

4 MATERIAL SPECIFICATION BASED ON STANDARD


4.1 Material specification based on JIS K6741
The JIS K6741 is prepared in accordance of the ISO 4422-1and ISO 4422-2 for the
pressurized design and ISO 3622 & ISO 4435 for the non pressurized design. Following JIS
K6741 standard, pipe is is classified pipe into 5 category as listed on table below

Based on the Standard JIS K6741, material used for drain, sewerage, and conveyance is use
ID-VP, IS-VP and IW-VP.

The specification for the ID-VP,IS-VP and IW-VP (on this table dimension is limited to ND200)
on table 4 of JIS K6741 as below:
PALU-3 COAL FIRED STEAM
POWER PLANT (2 x 50 MW) CONSORTIUM
PT. PLN (Persero) WIKA-DHI-KOEN

Document No. Rev. : 00


COMPREHENSIVE STUDY OF
18JE05-DOC-ZEN-57-0001 DRAIN, SEWAGE, & SOIL PIPE Page No. : 6 of 8

4.2 Material Specification based on ISO 3633 and ISO 4435


Pipe dimension and Wall thickness as per ISO 3633 (Table 1 and 3) and ISO 4435 (Table 3
and 4).

Pipe dimensioning and wall thickness listed in the ISO 4435 table 4 is equal with ISO 3633,
therefore not listed

4.3 Material Specification based on SNI 06-0162-1987


SNI 06-0162-1987 specification for pipe dimensioning and wall thickness can be seen as table
below:
PALU-3 COAL FIRED STEAM
POWER PLANT (2 x 50 MW) CONSORTIUM
PT. PLN (Persero) WIKA-DHI-KOEN

Document No. Rev. : 00


COMPREHENSIVE STUDY OF
18JE05-DOC-ZEN-57-0001 DRAIN, SEWAGE, & SOIL PIPE Page No. : 7 of 8

4.4 Material Specification based on Market


Material that commonly available on local market is speficied as Below

5 COMPARISON
5.1 Dimensioning and wall Thickness Comparison
Comparison of material dimension and wall thickness
PALU-3 COAL FIRED STEAM
POWER PLANT (2 x 50 MW) CONSORTIUM
PT. PLN (Persero) WIKA-DHI-KOEN

Document No. Rev. : 00


COMPREHENSIVE STUDY OF
18JE05-DOC-ZEN-57-0001 DRAIN, SEWAGE, & SOIL PIPE Page No. : 8 of 8

6 CONCLUSION
There are several item can be concluded as follow :
 The JIS K6741 describe the UPVC pipe usage for the material use in drain, sewage and soil
Pipe is equivalent with ISO 3633 and 4435 and listed as ID-VP,IS-VP and IW-VP.
 Drain, sewage and Soil pipe is designed as non pressure design and use, the use thicker
wall thickness only affect on design for pressurized pipe.
 Pipe which is available on local market is have different range dimension and thickness, but
have equal specification as ISO 3633 . Pipe that follow JIS K6741 wall thickness is not
available on local market and need long time waiting for order.
 Project will use the AW and D class as per available on market. Which D class will use as
downpipe.

You might also like