You are on page 1of 582

© Siemens 2022

Edition
Catalog August
D 21.3 2022

MOTION CONTROL DRIVES

SINAMICS S120
Chassis Format Converter Units
Chassis-2 Format Converter Units
Cabinet Modules, Cabinet Modules-2
SINAMICS S150
Converter Cabinet Units
siemens.com/d21-3
© Siemens 2022

Related catalogs
SINAMICS G130 D 11 Industrial Communication IK PI
Drive Converter Chassis Units SIMATIC NET
SINAMICS G150
Drive Converter Cabinet Units

E86060-K5511-A101-A6-7600 E86060-K6710-A101-B8-7600

Motion Control Drives D 31.1 Low-Voltage Power Distribution and LV 10


SINAMICS Inverters for Single-Axis Drives Electrical Installation Technology
Built-In Units SENTRON • SIVACON • ALPHA
Protection, Switching, Measuring and Monitoring
Devices, Switchboards and Distribution Systems
PDF (E86060-K5531-A111-A2-7600) PDF (E86060-K8280-A101-B5-7600)

Motion Control Drives D 31.2 SIMATIC ST 70


SINAMICS Converters for Single-Axis Drives Products for
Distributed Converters Totally Integrated Automation

PDF (E86060-K5531-A121-A2-7600) PDF (E86060-K4670-A101-B9-7600)

SINAMICS Drives D 35 Industry Mall


SINAMICS G120P and Information and Ordering Platform
SINAMICS G120P Cabinet on the Internet:
pump, fan, compressor converters

PDF (E86060-K5535-A101-A5-7600) www.siemens.com/industrymall

Motion Control Drives D 21.4


SINAMICS S120 and SIMOTICS
The Engineering Manual
SINAMICS Low Voltage Engineering Manual

E86060-K5521-A141-A1-7600 Engineering Manual for


• SINAMICS G130 Converter Built-In Units,
SIMOTICS GP, SD, XP, DP D 81.1 • SINAMICS G150 Converter Cabinet Units,
Low-Voltage Motors • SINAMICS S120 Chassis Format Converter Units,
Type series 1FP1, 1LE1, 1LE5, 1MB1, 1MB5, 1PC1 • SINAMICS S120 Cabinet Modules,
Frame sizes 63 to 450 • SINAMICS S150 Converter Cabinet Units
Power range 0.09 to 1000 kW
PDF (E86060-K5581-A111-B5-7600) This manual offers users comprehensive support with the
configuring of drives and associated system components.

SIMOTICS FD D 81.8 The first three chapters are devoted primarily to the fundamental
physical principles of variable-speed electric drives and include
Low-Voltage Motors
EMC Installation Guidelines as well as general system descriptions
Frame sizes 315 to 450 and planning information which relate to all products in the
Power range 200 to 1800 kW SINAMICS range.

PDF (E86060-K5581-A181-A5-7600) The other chapters then discuss in detail questions relating to the
dimensioning of drives with converters of specific types as well as
the selection of suitable motors.
LOHER Low-Voltage Motors D 83.1
Note:
Type series 1MD5, 1PS0, 1PS1, 1PS4 and 1PS5
Frame sizes 71 to 500 The manual is not available in hard copy form, but only as an
Power range 0.12 to 1400 kW electronic file in PDF format.

E86060-K5583-A111-A3-7600

Industrial Controls IC 10
SIRIUS

PDF (E86060-K1010-A101-B3-7600)
© Siemens 2022

Edition
Catalog August
D 21.3 2022

MOTION CONTROL DRIVES

SINAMICS S120
Chassis and Chassis-2 Format Converter Units
Cabinet Modules, Cabinet Modules-2
SINAMICS S150
Converter Cabinet Units
siemens.com/d21-3

Dear Customer,
We are pleased to present you with the new Catalog D 21.3 · August 2022. The catalog provides a comprehensive overview of the
SINAMICS S120 Chassis and Chassis-2 Format Converter Units, the Cabinet Modules and Cabinet Modules-2 as well as the
SINAMICS S150 Converter Cabinet Units.
In addition to updates and technical modifications, the new edition of the catalog has also been supplemented with the OEM kits for
SINAMICS S120 Chassis-2 for control cabinet installation, Active Line Connection Modules compact and Motor Modules compact for
SINAMICS S120 Cabinet Modules in a liquid-cooled version.
Up-to-date information about SINAMICS S120 is available on the internet at: www.siemens.com/sinamics-s120
Up-to-date information about SINAMICS S150 is available on the internet at: www.siemens.com/sinamics-s150
You can access our Industry Mall on the internet at: www.siemens.com/industrymall
Your personal contact will be happy to receive your suggestions and recommendations for improvement.
You can find your representative in our Personal Contact database at: www.siemens.com/automation-contact
We hope that you will often enjoy using Catalog D 21.3 · August 2022 as a selection and ordering reference document and wish you
every success with our products and solutions.
With kind regards

Frank Golüke
Vice President
General Motion Control
Siemens AG, Digital Industries, Motion Control
© Siemens 2022
© Siemens 2022

SINAMICS S120 Chassis Format Converter Units


SINAMICS S120 Cabinet Modules
SINAMICS S150 Converter Cabinet Units
Motion Control Drives
System Overview
1

Highlights
2

SINAMICS S120 Chassis Format Converter Units


75 kW to 5700 kW
3

SINAMICS S120 Chassis-2 Format Converter Units


315 kW to 3590 kW
4
Catalog D 21.3 · 2022

Supersedes: System Components


for SINAMICS S120 converter built-in units
5
Catalog D 21.3 · 2019

Refer to the Industry Mall for current updates of


this catalog:
www.siemens.com/industrymall SINAMICS S120 Cabinet Modules
4.8 kW to 5700 kW
6
Please contact your local Siemens branch.

© Siemens 2022

SINAMICS S120 Cabinet Modules-2


315 kW to 3590 kW
7

SINAMICS S150 Converter Cabinet Units


75 kW to 1200 kW
8

Tools and Engineering


9

Services and Documentation


10

Appendix
11

The products and systems described in


this catalog are manufactured/distributed
under application of a certified quality
management system in accordance with
EN ISO 9001. The certificate is recognized
by all IQNet countries.
© Siemens 2022

Digitalization in drive technology


From the digital world to the real world
siemens.com/digital-drives

Increase your transparency and productivity by digitalizing your drive technology


Many drives are used in the manufacturing and process industries. They produce lots of data anyway – why not use them
to increase the availability and productivity of machines and plants?
Drive technology offers the ideal entry point into the world of digitalization – for plant and machine builders as well as
for users.
The digitalization portfolio for the drive train spans over the complete life cycle – from the design phase to realization
and optimization – in the digital and the real world.
Our portfolio contains drive simulation solutions and efficient engineering tools, comprehensive connectivity that allows
drives to be easily linked to the relevant platforms as well as smart analytics (e.g. cloud and edge apps) and drive system
services.
These solutions enable you to gain a better understanding of processes, states and utilization. The health status of the
drive train can be monitored and analyzing drive data enables an early detection of anomalies and reduces downtimes.
This way, availability and productivity of machines and plants can be increased and the actual maintenance demand can
be identified. Furthermore, data-based business models and service offerings are facilitated.

Our digitalization portfolio covers all phases of the life cycle:


from the design phase to realization and optimization. It covers the digital and the real drive train.
Design: By creating a digital twin of the drives, machine
builders can shorten their time-to-market since they can
design, simulate and optimize their machine before
ordering any material or products. Together with other
tools from the engineering box, simulation can also speed
up the engineering phase of drives and entire machines,
for example by virtual commissioning of the PLC.
Realize: Once the machine is in operation, the drives can
be connected to other platforms, for example to the cloud
and Industrial Edge. This creates transparency in terms of
what is going on inside the drive train, e.g. with regard to
the actual current, torque and speed.
Optimize: To understand the collected data, our drive
train analytics portfolio provides algorithms and analysis
tools to unlock the potential of the data and turn the
gained transparency into insights and valuable
knowledge. These insights can then again be used in the
design phase of the next life cycle, thus closing the loop.

2 Siemens D 21.3 · 2022


© Siemens 2022

Benefits of drive train digitalization

Machine Availability Speed Business models


builders

Increase the availability Shorten Develop new service and


of your machines time-to-market business models

Machine Productivity Flexibility Efficiency


operators

Increase the productivity of Increase the flexibility of Identify potential for


your production your production optimization

Benefits for machine and plant builders Benefits for machine and plant operators
• Increased availability of machines and plants – thanks to • Increased availability and productivity of production, fewer
digital options for checking and implementing design unscheduled downtimes – through the early detection of
improvements and comprehensive monitoring of drive deviations and emerging risks thanks to digital drive
systems monitoring
• Shorter time-to-market and faster development times – • More flexible production down to batch size 1 – through
thanks to practical software tools and a continuous more effective use of knowledge from existing production
database for concurrent development processes as well as lines thanks to transparent utilization, states, locations, and
virtual simulations, tests, and commissioning of machines capacities down to the drive level
and plants • Identification of potential for optimization to make
• New options for future service and business models – production faster, better, and more efficient thanks to
ranging from customized application solutions and digital data-based transparency – for example, for faster
services to contractually guaranteed availabilities of modifications, simpler quality control, and the early
machines and plants prediction of maintenance demand as well as demand-
oriented maintenance

siemens.com/digital-drives

Siemens D 21.3 · 2022 3


© Siemens 2022

TIA Selection Tool –


quick, easy, smart configuration
For you to get the most out of our portfolio quickly and easily.

Do you always need the optimum configuration for


planning your project?
For your application we offer the TIA Selection Tool to
support all project planners, beginners and experts alike.
No detailed portfolio knowledge is necessary.
TIA Selection Tool is available for download as a free
desktop version or a cloud variant.

Your Advantages

Quick Easy Smart

• Configure a complete project with • Tool download either as desktop • Smart selection wizard for error-free
just a few entries – version or web-based cloud version configuration and ordering
without a manual, without special • Technically always up-to-date • Configuration options can be tested
knowledge about product portfolio and innova- and simulated in advance
• Import and export of hardware tive approaches • Library for archiving sample configu-
configuration to TIA Portal or other • Highly flexible, secure, cross-team rations
systems work in the cloud
• Ideal visualization of the projects to • Direct ordering in the Siemens
be configured Industry Mall

The TIA Selection Tool is a


completely paperless solution.
For more
Download it now: information,
www.siemens.com/tst scan the
QR code

4 Siemens D 21.3 · 2022


1
© Siemens 2022

System Overview

1/2 The SINAMICS converter family


1/2 Integration in automation
1/2 Applications
1/3 SINAMICS as part of the Siemens modular
automation system
1/3 Energy efficiency
1/4 Variants
1/4 Platform concept
1/4 Quality management according
to EN ISO 9001
1/4 Industry Online Support app
1/5 DRIVE-CLiQ – the digital interface between
all components
1/5 Swift and automatic:
The electronic rating plate
1/5 IDS – integration at its very best

1/6 Drive selection


1/6 SINAMICS selection guide –
typical applications

1/7 SIMOTICS motors

1/8 SINAMICS S120


The flexible, modular drive system
for demanding drive tasks

1/12 SINAMICS S150


The drive solution for demanding
single-motor drives

Siemens D 21.3 · 2022


© Siemens 2022

System overview

The SINAMICS converter family

1 ■ Overview
Integration in automation

Management level Office environment: SIMATIC IT / COMOS...

Process control level Control center / control system:


SIMATIC PCS 7 / WINCC

Control level Automation systems / HMI:


SIMATIC / SIMOTION / SINUMERIK

Fieldbus

SINAMICS V SINAMICS V
SINAMICS V SINAMICS G SINAMICS G
SINAMICS G SINAMICS S SINAMICS S SINAMICS S

G_D011_EN_00337d
pumping
ventilating
compressing moving processing machining

Totally Integrated Automation and communication Applications


SINAMICS is an integral component of Siemens Totally SINAMICS is the comprehensive converter family from Siemens
Integrated Automation. The integrated and seamless SINAMICS designed for machine and plant engineering applications.
system covering configuration, data management, and SINAMICS offers solutions for all drive tasks:
communication at the automation level ensures solutions with • Simple pump and fan applications in the process industry
minimal associated effort in conjunction with the SIMATIC,
SIMOTION, and SINUMERIK control systems. • Demanding single drives in centrifuges, presses, extruders,
elevators, as well as conveyor and transport systems
Depending on the application, the appropriate converter can be • Drive line-ups in textile, plastic film, and paper machines as
selected and incorporated in the automation concept. With this well as in rolling mill plants
in mind, the converters are clearly subdivided into their different
applications. A wide range of communication options • Highly dynamic servo drives for machine tools, as well as
(depending on the drive type) are available for establishing packaging and printing machines
a communication link to the automation system:
• PROFINET
• PROFIBUS
• EtherNet/IP
• Modbus TCP
• Modbus RTU
• AS-Interface
• BACnet MS/TP

1/2 Siemens D 21.3 · 2022


© Siemens 2022

System overview

The SINAMICS converter family

■ Overview 1
SINAMICS as part of the Siemens modular automation system

SIMOTION SINUMERIK SIMATIC

SINAMICS

SIMOGEAR SIMOTICS

G_D011_XX_00515b
Innovative, energy-efficient and reliable drive systems and Almost two thirds of the industrial power requirement is from
applications as well as services for the entire drive train electric motors. This makes it all the more important to use drive
technology permitting energy consumption to be reduced
The solutions for drive technology place great emphasis on the effectively even in the configuration phase, and consequently to
highest productivity, energy efficiency and reliability for all optimize plant availability and process stability. With SINAMICS,
torque ranges, performance and voltage classes. Siemens offers powerful energy-efficient solutions which,
Siemens offers not only the right innovative variable frequency depending on the application, enable a significant reduction
drive for every drive application, but also a wide range of in electricity costs.
energy-efficient low voltage motors, geared motors, explosion- Up to 70 % potential for savings using variable speed operation
protected motors and high-voltage motors for combination with
SINAMICS. SINAMICS enables great potential for savings to be realized by
controlling the motor speed. In particular, huge potential savings
Furthermore, Siemens supports its customers with global pre- can be recovered from pumps, fans and compressors which are
sales and after-sales services, with over 295 service points in operated with mechanical throttles and valves. Here, changing
130 countries – and with special services e.g. application to variable-speed drives brings enormous economic
consulting or motion control solutions. advantages. In contrast to mechanical control systems, the
Energy efficiency power consumption at partial load operation is always
immediately adjusted to the demand at that time. Thus, energy
Energy management process is no longer wasted, permitting savings of up to 60 % –
Efficient energy management consultancy identifies the energy in exceptional cases even up to 70 %. Variable-speed drives
flows, determines the potential for making savings and also offer clear advantages over mechanical control systems
implements them with focused activities. when it comes to maintenance and repair. Current spikes when
powering up the motor and strong torque surges become things
of the past – and the same goes for pressure waves in pipelines,
cavitation or vibrations which cause sustainable damage to the
plant. Smooth starting and ramp-down relieve the load on the
mechanical system, ensuring a significantly longer service life of
the entire drive train.

Siemens D 21.3 · 2022 1/3


© Siemens 2022

System overview

The SINAMICS converter family

1 ■ Overview
Regenerative feedback of braking energy Energy transparency in all configuration phases
In conventional drive systems, the energy produced during Early on, in the configuration phase, the SIZER for Siemens
braking is converted to heat using braking resistors. Energy Drives (integrated in the TIA Selection Tool) engineering tool
produced during braking is efficiently recovered to the supply provides information on the specific energy requirement. The
system by versions of SINAMICS G and SINAMICS S converters energy consumption across the entire drive train is visualized
with regenerative feedback capability and these devices do not and compared with different plant concepts.
therefore need a braking resistor. This permits up to 60 % of the
energy requirement to be saved, e.g. in lifting applications. SINAMICS in combination with energy-saving motors
Energy which can be reused at other locations on a machine. Engineering integration stretches beyond the SINAMICS
Furthermore, this reduced power loss simplifies the cooling of converter family to higher-level automation systems, and to
the system, enabling a more compact design. a broad spectrum of energy-efficient motors with a wide range
of performance classes, which, compared to previous motors,
are able to demonstrate up to 10 % greater efficiency.
Variants
Depending on the application, the SINAMICS range offers the
ideal variant for any drive task.

Performance

SINAMICS V SINAMICS G SINAMICS S Price

SINAMICS V drives focus on SINAMICS G drives function perfectly for low SINAMICS S drives are predestined
the essentials both in terms of hardware and medium demands on the dynamic for demanding single - and multi-axis
and functionality. response of the control system. applications in machine and plant engineering

G_D011_EN_00449b
This results in a high degree of ruggedness as well as for numerous motion control tasks.
combined with lower investment costs.

Platform concept Main functions at a glance:


All SINAMICS variants are based on a platform concept. Joint • Scanning of product codes and EAN codes to directly display
hardware and software components, as well as standardized all of the technical and graphical data (e.g. CAx data) of the
tools for dimensioning, configuration, and commissioning tasks product
ensure high-level integration across all components. SINAMICS • Sending of product information or entries via e-mail to further
handles a wide variety of drive tasks with no system gaps. The process the information at the workstation
different SINAMICS variants can be easily combined with each • Conveniently send inquiries to Technical Support. Detailed
other. information can be conveniently completed using the scan or
Quality management according to EN ISO 9001 photo function
SINAMICS conforms to the most exacting quality requirements. • Save the favorites on the device using the offline cache
Comprehensive quality assurance measures in all development function. These articles, products and conferences can then
and production processes ensure a consistently high level of be called even without network access.
quality. • Transfer of PDF documents to an external library
Of course, our quality management system is certified by an • The contents and interfaces are available in six languages
independent authority in accordance with EN ISO 9001. (German, English, French, Italian, Spanish and Chinese) -
including a temporary switchover to English.
Industry Online Support app
You can find additional information on the internet at:
With the Industry Online Support app, you can access more than www.siemens.com/sinamics-assistant
300000 documents for Siemens Industry products – any time
and from anywhere.

1/4 Siemens D 21.3 · 2022


© Siemens 2022

System overview

The SINAMICS converter family

■ Overview 1
DRIVE-CLiQ – the digital interface between all components equivalent circuit diagram and the characteristic data of the
built-in motor encoder in addition to information such as order
All SINAMICS S120 components, including the motors and and identification numbers.
encoders, are interconnected by a shared serial interface called
DRIVE-CLiQ. The standardized cables and connectors reduce IDS – integration at its very best
the variety of different parts and cut storage costs. Converter
boards (Sensor Modules) for converting standard encoder The Siemens Integrated Drive Systems (IDS) solution offers per-
signals to DRIVE-CLiQ are available for third-party motors or fectly matched drive components with which you can meet your
retrofit applications. requirements. The drive components reveal their true strengths
as an Integrated Drive System over the full range from engineer-
Swift and automatic: The electronic rating plate ing and commissioning through to operation: Integrated system
configuration is performed using the Siemens Product
An important digital linkage element of the SINAMICS S120 Configurator. Just select a motor and a converter and design
drive system are the electronic rating plates integrated in every them with the SIZER engineering tool for Siemens Drives
component. They allow all drive components to be detected (integrated in the TIA Portal). The STARTER and SINAMICS
automatically via a DRIVE-CLiQ link. As a result, data do not Startdrive commissioning tools integrate the motor data and, at
need to be entered manually during commissioning or the same time, simplify efficient commissioning. Integrated Drive
component replacement – helping to ensure that drives are Systems are incorporated in the TIA Portal – this simplifies
commissioned successfully! The electronic rating plates of the engineering, commissioning and diagnostics.
motors contain, for example, the parameters of the electrical

Direct Medium
Low voltage
voltage voltage

Standard performance Distributed Industry-specific Servo drives High performance DC Converters for
frequency converters frequency frequency converters frequency converters converters applications
converters with high
outputs

SINAMICS SINAMICS SINAMICS SINAMICS SINAMICS SINAMICS SINAMICS SINAMICS SINAMICS SINAMICS SINAMICS SINAMICS
V20 G130 G115D G120X G180 V90 S110 S210 S120 S150 DCM GH150
G120C G150 G120D S120M DCP 1) GH180
G120 SIMATIC GM150
ET 200pro FC-2 SM150
GL150
SL150
SH150

0.12 kW to 75 kW to 0.37 kW to 0.75 kW to 2.2 kW to 0.05 kW to 0.55 kW to 0.05 kW to 0.55 kW to 75 kW to 6 kW to 0.15 MW to


250 kW 2700 kW 7.5 kW 630 kW 6600 kW 7 kW 132 kW 7 kW 5700 kW 1200 kW 30 MW 85 MW
Pumps, Pumps, Conveyor Pumps, Pumps, Handling Single-axis Packaging Production Test bays, Rolling mill Pumps,
fans, fans, technology, fans, fans, machines, positioning machines, machines cross cutters, drives, fans,
compressors, compressors, single-axis compressors, compressors, packaging applications in handling (packaging, centrifuges wire-drawing compressors,
conveyor conveyor positioning building conveyor machines, machine and equipment, textile and machines, mixers,
belts, belts, applications management belts, automatic plant feed and printing extruders and extruders,
mixers, mixers, (G120D) systems, extruders, assembly engineering withdrawal machines, kneaders, mills,
mills, mills, process mixers, machines, devices, paper cableways crushers,
spinning extruders industry, mills, metal forming stacking units, machines, and lifts, rolling mills,
machines, HVAC, kneaders, machines, automatic plastic test bay drives conveyor
textile water/waste centrifuges, printing assembly processing technology,
machines, water separators machines, machines, machines), excavators,
refrigerated industries winding and laboratory machine test bays,
display unwinding automation, tools, marine drives,
counters, units wood, glass plants, blast furnace
fitness and ceramics process lines fans,
equipment, industry, and rolling retrofit
ventilation digital printing mills, marine
systems, machines drives,
single-axis test bays
positioning
applications in
machine and
plant
engineering
Catalog Catalog Catalog Catalog Catalog Catalog Catalog Catalog Catalogs Catalog Catalog Internet 2)
D 31.1 D 11 D 31.2 D 31.5 D 18.1 D 33 D 31.1 D 32 D 21.3, D 21.4 D 21.3 D 23.1,
NC 62 Industry Mall

Engineering tools (e.g. Siemens Product Configurator, SIZER for Siemens Drives, STARTER and SINAMICS Startdrive)

G_D011_EN_00450s
1)
DC/DC controllers, see Industry Mall.
2)
www.siemens.com/medium-voltage-converter

Siemens D 21.3 · 2022 1/5


© Siemens 2022

System overview

Drive selection

1 ■ Overview
SINAMICS selection guide – typical applications
Use Requirements for torque accuracy/speed accuracy/position accuracy/coordination of axes/functionality
Continuous motion Non-continuous motion
Basic Medium High Basic Medium High

Pumping, Centrifugal pumps Centrifugal pumps Eccentric screw Hydraulic pumps Hydraulic pumps Descaling pumps
ventilating, Radial/axial fans Radial/axial fans pumps Metering pumps Metering pumps Hydraulic pumps
compressing Compressors Compressors
V20 G120X S120 G120 S110 S120
G120C G130/G150
G120X G180 1)
DCM

Moving Conveyor belts Conveyor belts Elevators Acceleration Acceleration Storage and retrieval
Roller conveyors Roller conveyors Container cranes conveyors conveyors machines
Chain conveyors Chain conveyors Mining hoists Storage and retrieval Storage and retrieval Robotics
Lifting/lowering Excavators for open- machines machines Pick & place
devices cast mining Cross-cutters Rotary indexing tables
Elevators Test bays Reel changers Cross-cutters
Escalators/moving Roll feeds
walkways Engagers/
Indoor cranes disengagers
Marine drives
Cable railways
V20 G120 S120 V90 S110 S120
G115D G120D S150 G120 S210 S210
G120C G130/G150 DCM G120D DCM DCM
ET 200pro FC-2 2) G180 1)
Processing Mills Mills Extruders Tubular bagging Tubular bagging Servo presses
Mixers Mixers Winders/unwinders machines machines Rolling mill drives
Kneaders Kneaders Lead/follower drives Single-axis motion Single-axis motion Multi-axis motion
Crushers Crushers Calenders control control control such as
Agitators Agitators Main press drives such as such as • Multi-axis positioning
Centrifuges Centrifuges Printing machines • Position profiles • Position profiles • Cyclic cams
• Path profiles • Path profiles • Interpolations
V20 G120 S120 V90 S110 S120
G120C G130/G150 S150 G120 S210 S210
G180 1) DCM DCM
Machining Main drives for Main drives for Main drives for Axis drives for Axis drives for Axis drives for
• Turning • Drilling • Turning • Turning • Drilling • Turning
• Milling • Sawing • Milling • Milling • Sawing • Milling
• Drilling • Drilling • Drilling • Drilling
• Gear cutting • Lasering
• Grinding • Gear cutting
• Grinding
• Nibbling and
punching
S110 S110 S120 S110 S110 S120
S120 S120

Using the SINAMICS selection guide • The application type is selected from the vertical column
- Pumping, ventilating, compressing
The varying range of demands placed on modern variable - Moving
frequency converters requires a large number of different types. - Processing
Selecting the optimum converter is becoming a significantly - Machining
more complex process. The application matrix shown simplifies
this selection process considerably, by suggesting the ideal • The quality of the motion type is selected from the horizontal
SINAMICS converter for examples of typical applications and row
requirements. - Basic
- Medium
- High

■ More information
More information about SINAMICS is available on the internet at Practical application examples and descriptions are available
www.siemens.com/sinamics on the internet at
www.siemens.com/sinamics-applications

1) 2)
Industry-specific converters. Information on the SIMATIC ET 200pro FC-2 frequency converter is
available in Catalog D 31.2 and at www.siemens.com/et200pro-fc

1/6 Siemens D 21.3 · 2022


© Siemens 2022

System overview

SIMOTICS motors

■ Overview 1
SIMOTICS
Low-voltage motors for line and converter operation
General Purpose Severe Duty Explosion-protected Definite Purpose Transnorm High Torque
SIMOTICS GP SIMOTICS SD SIMOTICS XP SIMOTICS DP SIMOTICS TN SIMOTICS HT

DC motors High-voltage motors


Direct Current SIMOTICS DC High Voltage SIMOTICS HV

Motors for motion control


SIMOTICS S servomotors SIMOTICS M main motors SIMOTICS L linear motors SIMOTICS T torque motors

G_D011_EN_00491a
Servomotors Servo geared motors

SIMOTICS stands for An outstanding performance for any job


• 150 years of experience in building electric motors A key characteristic of all SIMOTICS motors is their quality.
• The most comprehensive range of motors worldwide They are robust, reliable, dynamic and precise to assure the
• Optimum solutions in all industries, regions and requisite performance level for any process and deliver exactly
power/performance classes the capabilities demanded by the application in hand. Thanks to
their compact design, they can be integrated as space-saving
• Innovative motor technologies of the highest quality and units into installations. Furthermore, their impressive energy
reliability efficiency makes them effective as a means of reducing
• Highest dynamic performance, precision and efficiency operating costs and protecting the environment.
together with the optimum degree of compactness
A dense network of skill sets and servicing expertise around
• Our motors can be integrated into the drive train as part of the the world
overall system
SIMOTICS offers not only a wealth of sound experience gleaned
• A global network of skill sets and worldwide service around from a development history which stretches back over around
the clock 150 years, but also the know-how of hundreds of engineers. This
A clearly structured portfolio knowledge and our worldwide presence form the basis for
a unique proximity to industries which feeds through in tangible
The entire SIMOTICS product portfolio is transparently terms to the specific motor configuration which is tailored to suit
organized according to application-specific criteria in order to your application.
help users select the optimum motor for their application.
Our specialists are available to answer all your queries
The product range extends from standard motors for pumps, regarding any aspect of motor technology. At any time –
fans and compressors to highly dynamic, precise motion control wherever you are in the world. When you choose SIMOTICS,
motors for positioning tasks and motion control in handling therefore, you reap the benefits of a global service network
applications, as well as production machinery and machine which is continuously accessible, thereby helping to optimize
tools, to DC motors and powerful high-voltage motors. Whatever response times and minimize downtimes.
it is that you want to move – we can supply the right motor for
the task. Perfection of the complete drive train
www.siemens.com/simotics SIMOTICS is perfectly coordinated with other Siemens product
families. In combination with the SINAMICS integrated converter
family and the SIRIUS complete portfolio of industrial controls,
SIMOTICS fits seamlessly as part of the complete drive train into
automation solutions which are based on the SIMATIC,
SIMOTION and SINUMERIK control systems.

Siemens D 21.3 · 2022 1/7


© Siemens 2022

System overview

SINAMICS S120

1 ■ Overview ■ Application
The flexible, modular drive system for demanding drive SINAMICS S120 vector control is recommended for drive
tasks solutions with continuous material webs, for example, wire-
drawing machines, film and paper machines, as well as for
SINAMICS S120 is the modular drive system with vector and hoisting gear, centrifuges and marine drives with harmonic,
servo control that is ideal for sophisticated drive tasks in plant circular motion.
and machine construction.
SINAMICS S120 with servo control and servo motors is
Multi-axis drive solutions with higher-level motion control can be employed for cyclic processes with both precise and highly
implemented with the modular SINAMICS S120 system just the dynamic closed-loop position control.
same as solutions for single-axis drives.
With SINAMICS S120, more performance is integrated into
Covering a power range from 0.12 kW to 5700 kW and various machines that are used in many industries, for instance in:
control modules with a graduated range of functions, the
modular SINAMICS S120 system can be used to simply and • Packaging machines
quickly create a precisely tailored drive configuration – • Plastics processing machines
for almost any sophisticated drive application. • Textile machines
On the SINAMICS S120, the drive intelligence is combined with • Presses and punches
closed-loop control functions into Control Units. • Printing and paper machines
These units are capable of controlling drives in the vector, servo • Machines used in the woodworking, glass and ceramics
and V/f modes. They also perform the speed and torque control industries
functions plus other intelligent drive functions for all axes on the
drive. • Hoisting gear
• Handling and assembly systems
Using the available closed-loop control techniques, both
synchronous as well as induction motors can be operated, • Machine tools
and therefore the complete range of low-voltage motors from • Rolling mill drives
Siemens. • Vehicle and gearbox test stands
Integrated PROFINET or PROFIBUS DP interfaces ensure easy • Test stand applications
integration into complete automation solutions. SINAMICS S120 • Marine applications
also supports many other fieldbus interfaces.
SINAMICS S120 Cabinet Modules are available as a cabinet
system specifically for use in plant construction. These can be
combined to form drive cabinet line-ups with a total power rating
of up to 5700 kW. Standardized interfaces enable the modules
to be linked quickly to create a ready-to-connect drive solution
for multi-motor applications.

■ Benefits
SINAMICS S120 is characterized by the following properties:
• Can be universally used in high-performance single and
multi-axis applications
• Can be freely combined to create customized solutions
• Wide range of power ratings
• Wide range of functions
• SINAMICS Safety Integrated functions
• Supports various cooling types (air/liquid-cooled)
• Supports various infeed concepts
• Can be simply integrated into higher-level automation and
IT environments
• User-friendly engineering
• Ease of handling
• Simple installation
• Practical connection system
• Auto-configuration with electronic rating plates

1/8 Siemens D 21.3 · 2022


© Siemens 2022

System overview

SINAMICS S120

■ Design 1
SINAMICS S120 built-in units are available as Power Modules, Types of construction
Line Modules and Motor Modules with the appropriate line-side
and motor-side components. Power Modules are available in blocksize and chassis formats.
Motor Modules and Line Modules are available in booksize,
Cooling types booksize compact, chassis and chassis-2 formats.
There are various cooling options available depending on the Precise details and ordering data on the booksize, booksize
type of construction: compact and blocksize formats are found in Catalog D 21.4.
Booksize format
Booksize format units are optimized for multi-axis applications
and are mounted adjacent to one another. The connection for the
common DC link is an integral feature.
G_D211_EN_00341
The units are cooled by an internal air cooling circuit.

Internal
air cooling

Liquid
cooling

Internal air cooling


In this standard solution, the power loss from the electronics and
power units of the drive components is removed by natural
cooling or by a forced-ventilation system and routed to the
interior of the control cabinet.
Liquid cooling
Booksize compact format
Onto liquid-cooled units, the power semiconductors are
Derived from the booksize format we developed the booksize
mounted on a heat sink through which the cooling medium flows.
compact format for machines with particularly high requirements
Most of the heat produced by the unit is absorbed by the cooling
for the compactness of their drives.
medium and can be dissipated outside the control cabinet.
The booksize compact format combines all benefits of the
Water cooling for shared circuits
booksize format and provides the same performance with an
With water cooling for shared circuits, the water that is available even smaller overall height and an extended overload capability.
at the plant can be used. This results in a shared cooling circuit
The booksize compact format is thus particularly suitable for
for the plant, motor, and converter. The requirements for the
integration into machines requiring a high dynamic performance
water quality are low in this case. Additives are not needed in the
and where installation space is restricted.
water circuit which simplifies environmentally friendly
commissioning and maintenance. Furthermore, the converter is The units are cooled by an internal air cooling circuit.
resistant to the addition of oxygen to the cooling water.
The advantages of liquid cooling, such as high energy savings
and efficient heat recovery, are also available with water cooling.
G_D211_EN_00358

Water cooling for shared circuits

Siemens D 21.3 · 2022 1/9


© Siemens 2022

System overview

SINAMICS S120

1 ■ Design
Blocksize format Chassis and chassis-2 formats
Blocksize format units are optimized for single-axis applications Higher-output units (approximately 100 kW and above) are
and are supplied only as Power Modules. constructed in chassis or chassis-2 format. The main
components for the formats are:
The CU310-2 can be directly snap-mounted. The units are
cooled by an internal air cooling circuit. Chassis format Chassis-2 format
Power Modules –
Basic Line Modules –
Smart Line Modules (air-cooled only) –
Active Line Modules Active Infeeds (Active Line Module
and Active Interface Module)
Active Interface Modules
Motor Modules Motor Modules

Cooling occurs by an internal air cooling unit, liquid cooling or


water cooling for shared circuits. The CU310-2 Control Unit can
be integrated in the Power Modules.
Liquid-cooled units and water-cooled units for shared circuits
are used primarily for applications where installation space is
restricted (up to a 60% smaller footprint when compared to air
cooling) or where low noise emissions are important. They are
also suitable for applications in tough ambient conditions.

Power units in chassis format, air-cooled and liquid-cooled

Motor Modules in chassis-2 format, air-cooled

1/10 Siemens D 21.3 · 2022


© Siemens 2022

System overview

SINAMICS S120

■ Design 1
Cabinet Modules and Cabinet Modules-2
SINAMICS S120 Cabinet Modules and SINAMICS S120 Cabinet
Modules-2 are a modular cabinet system for multi-motor drives
with a central supply infeed and a common DC busbar, for
example, as used in paper machines, rolling mills, test bays, and
hoisting gear.
Cabinet Modules are available with a total power rating of up to
4500 kW in the air-cooled version and up to 5700 kW in the
liquid-cooled version.
Cabinet Modules-2 are available with a total power rating of up
to 3590 kW in the air-cooled version. The main components of
the system are as follows:
Cabinet Modules Cabinet Modules-2
Line Connection Modules Active Line Connection Modules
(Line Connection Module + Active
Line Module + Active Interface
Module) SINAMICS S120 Cabinet Modules, air-cooled and liquid-cooled
Basic Line Modules –
Smart Line Modules –
Active Line Modules including –
Active Interface Modules
Central Braking Modules –
Motor Modules Motor Modules
Auxiliary Power Supply Modules – (combinable with Auxiliary Power
Supply Module)

SINAMICS S120 Cabinet Modules-2, air-cooled

Siemens D 21.3 · 2022 1/11


© Siemens 2022

System overview

SINAMICS S150

1 ■ Overview ■ Design
The drive solution for demanding single-motor drives SINAMICS S150 systems are ready-to-connect converters
accommodated in a standard control cabinet.
They can be optimally adapted to specific requirements as
a result of a wide range of options.
Different variants allow the line and the motor connection to be
made at the top or bottom. This ensures a high degree of
flexibility regarding how the drive is installed.
The drive units are available with cabinet widths starting from
1400 mm in grid dimension increments of 200 mm. As standard,
the cabinets have degree of protection IP20, and can be
optionally increased up to IP54. The AOP30 Advanced Operator
Panel is fitted as standard in the cabinet door.

Commissioning SIMATIC HMI SIMATIC S7


tool

STARTER

PROFIBUS

SINAMICS S150 cabinet units are designed for variable-speed


drives in plant and machinery construction. PROFINET
SINAMICS S150
They are especially suitable where high demands are placed on
dynamic performance and speed precision, as well as for
frequent braking cycles with high braking energies and four-
quadrant operation. The drive converter cabinet units provide 3 AC
high performance speed control with a high precision and Induction motor
dynamic performance, and are available for a power range
extending from 75 kW up to 1200 kW. G_D213_EN_00075a

1/12 Siemens D 21.3 · 2022


2
© Siemens 2022

Highlights

2/2 Safety Integrated


2/2 Overview
2/3 Function

2/14 Safety Integrated for


SINAMICS S120 Chassis and Chassis-2
Format Converter Units,
SINAMICS S120 Cabinet Modules and
Cabinet Modules-2
SINAMICS S150 Drive Converter
Cabinet Units
2/14 Overview
2/15 Function

2/16 Communication
2/16 Overview
2/17 PROFINET
2/22 PROFIdrive
2/23 PROFIBUS
2/24 Industrial Ethernet
2/25 EtherNet/IP
2/25 Modbus TCP
2/25 USS

2/26 Technology functions


2/26 Basic positioner EPos
2/28 SINAMICS Technology Extensions
(SINAMICS TEC)

D 21.3 · 2022
© Siemens 2022

Highlights

Safety Integrated

■ Overview
Safety-related standards
Functional safety is specified in various standards. For example,
EN ISO 12100 specifies standards pertaining to machine safety
(risk assessment and risk reduction). IEC 61508 specifies basic
2 requirements for electronic and programmable safety-related
systems. EN 62061 (only applicable for electrical and electronic
control systems) and EN ISO 13849-1 define the functional and
safety-related requirements of safety-oriented control systems.
The above-mentioned standards define different safety
requirements that the machine has to satisfy in accordance with
the risk, frequency of a dangerous situation, probability of
occurrence and the opportunities for recognizing impending
danger.
• EN ISO 13849-1: Performance Level PL a ... e;
Category B, 1 ... 4
• EN 62061: Safety Integrity Level SIL 1 ... 3
Trend toward integrated safety systems
The trend toward greater complexity and higher modularity of
Legal framework machines has seen a shift in safety functions away from the
classical central safety functions (for example, shutdown of the
Machine manufacturers and plant construction companies must complete machine using a main disconnecting means) and into
ensure that their machines or plants cannot cause danger due the machine control system and the drives. This is often
to malfunctions in addition to the general risks of electric shock, accompanied by a significant increase in productivity because
heat or radiation. the setup times are shortened. Depending on the type
of machine, it may even be possible to continue manufacturing
In Europe, for example, compliance with the Machinery Directive other parts while the setup is in progress.
2006/42/EC is legally stipulated by the EU framework directive
for occupational safety. In order to ensure compliance with this Safety Integrated Functions act much faster than those of
directive, it is recommended that the corresponding harmonized a conventional design. The safety of a machine is increased
European standards are applied. This triggers the "assumption further with Safety Integrated. Furthermore, thanks to the faster
of conformity" and gives manufacturers and operators the legal method of operation, safety measures controlled by integrated
security in terms of compliance with both national regulations safety systems are perceived as less of a hindrance by the
and EU directives. The machine manufacturer uses the CE machine operator, therefore significantly reducing the motivation
marking to document compliance with all relevant directives and to consciously bypass safety functions.
regulations in the free movement of goods.

2/2 Siemens D 21.3 · 2022


© Siemens 2022

Highlights

Safety Integrated

■ Function
The safety functions integrated in SINAMICS drives are listed below.
Safety Integrated S120 S150
S120M
CU310-2 CU320-2 CU320-2
Functions 2
STO   
SS1   
SS2  1)  1)  1)
SOS  1)  1)  1)
SBC   
SBT  1)  1)  1)
SLS  1)  1)  1)
SSM  1)  1)  1)
SDI  1)  1)  1)
SLA  1)  1)  1)
SLP  2)  2) 3)  4)
SP  2)  2) 3)  4)
SCA  2)  2) 3)  4)
Control
PROFIsafe   
F-DI   

Safety functions integrated in SINAMICS drives The safety functions integrated into the SINAMICS drive system
can be roughly divided into four categories:
SINAMICS drives are characterized by a large number of Safety
Integrated Functions. In combination with the sensors and safety • Functions for safely stopping a drive
control required for the safety functionality, they ensure that - Safe Torque Off (STO)
highly-effective protection for persons and machines is - Safe Stop 1 (SS1)
implemented in a practice-oriented manner. - Safe Stop 2 (SS2)
- Safe Operating Stop (SOS)
They comply with the requirements of the following safety
categories: • Functions for safe brake management
- Safe Brake Control (SBC)
• PL d and Category 3 according to EN ISO 13849-1 - Safe Brake Test (SBT) (this diagnostic function exceeds the
• SIL 2 according to IEC 61508 and IEC 61800-5-2 scope of IEC 61800-5-2)
Note: • Functions for safely monitoring the motion of a drive
- Safely-Limited Speed (SLS)
The Safe Brake Test (SBT) diagnostic function meets the - Safe Speed Monitor (SSM)
requirements for Category 2 according to EN ISO 13849-1. - Safe Direction (SDI)
The PM240-2 Power Modules, frame sizes FSD to FSG - Safely-Limited Acceleration (SLA)
additionally offer STO acc. to IEC 61508 SIL 3 and • Functions for safely monitoring the position of a drive
EN ISO 13489-1 PL e and Category 3. - Safely-Limited Position (SLP)
- Safe Position (SP) (this function exceeds the scope of
The Safety Integrated functions are generally certified by IEC 61800-5-2)
independent institutes. You can obtain the corresponding test - Safe Cam (SCA)
certificates and manufacturer's declarations from your Siemens
contacts.
The Safety Integrated Functions that are currently available are
described below. Their functional safety satisfies the
requirements defined in the international standard
IEC 61800-5-2 for variable-speed drive systems.

1) With Safety Extended license. 3) Safety Advanced license for cabinet modules on request.
2) With Safety Advanced license. 4) Safety Advanced license on request.

Siemens D 21.3 · 2022 2/3


© Siemens 2022

Highlights

Safety Integrated

■ Function
Safe Torque Off (STO) Safe Stop 1 (SS1)
The STO function is the most common and basic drive- The SS1 function causes a motor to stop rapidly and safely and
integrated safety function. It ensures that no torque-generating switches the motor to torque-free mode after coming
energy can continue to affect a motor and prevents unintentional to a standstill by activating STO.
2 start-ups.
Effect Effect
This function is a mechanism that prevents the drive from The SS1 function can safely stop the drive in accordance with
restarting unexpectedly, in accordance with EN 60204-1, EN 60204-1, Stop Category 1. When the SS1 function is
Section 5.4. The STO function suppresses the drive pulses selected, the drive brakes autonomously along a quick-stop
(corresponds to Stop Category 0 according to EN 60204-1). ramp and automatically activates the Safe Torque Off and Safe
The drive is reliably torque-free. This state is monitored internally Brake Control functions (if configured) when the parameterized
in the drive. safety delay time expires.
If the variant "SS1 with external stop (SS1E)" is parameterized,
the drive does not brake autonomously when the function is
selected. In this case, the higher-level control must bring the
drive to a standstill within a parameterized STO transition time.
The SBR (Safe Brake Ramp) and SAM (Safe Acceleration
Monitor) functions are not active. SS1E is a useful function for
drives that need to be stopped as a group by the Motion Control
system in order to prevent potential damage to the machine or
product.

Application Application

STO has the immediate effect that the drive cannot supply any The SS1 function is used when, in the event of a safety-relevant
torque-generating energy. STO can be used wherever the drive incident, the drive must stop as quickly as possible with
will naturally reach a standstill due to load torque or friction in a subsequent transition into the STO state (e.g. EMERGENCY
a sufficiently short time or when "coasting down" of the drive will STOP). It is thus used to bring large centrifugal masses to a stop
not have any relevance for safety. as quickly as possible for the safety of the operating personnel,
or to brake motors at high speeds as quickly as possible.
STO makes it possible for persons to work safely when the Examples of typical applications are saws, grinding machine
protective door is open (restart interlock) and is used on spindles, centrifuges, winders and storage and retrieval
machines/installations with moving axes, e.g. on handling or machines.
conveyor systems.
Customer benefits Customer benefits
Some of the advantages of the Safety Integrated Function STO The targeted stopping of a drive by means of SS1 reduces the
over conventional safety technology with electromechanical risk of danger, increases the productivity of a machine, and
switchgear include the elimination of separate components as allows the safety clearances in a machine to be reduced. The
well as of the work that would be required to wire and service principle is to bring the drive actively to a standstill, compared
them, i.e. no wearing parts as a result of the electronic shutdown. with just using the STO function. Complex mechanical brakes
Because of the fast electronic switching times, the function that are susceptible to wear are normally not required to brake
provides a shorter reaction time than the conventional solution the motor.
comprising electromechanical components. When STO is
triggered, the converter remains connected to the network and
can be fully diagnosed.

v STO v STO
G_D211_XX_00304

G_D211_XX_00305

t t

2/4 Siemens D 21.3 · 2022


© Siemens 2022

Highlights

Safety Integrated

■ Function
Safe Stop 2 (SS2) Safe Operating Stop (SOS)
The SS2 function brings the motor to a standstill quickly and With the SOS function, the stopped motor is held in position by
safely and then activates the SOS function once the motor has the drive control system and its position is monitored.
stopped.
Effect Effect 2
The Safe Stop 2 function can safely stop the drive in accordance The SOS function constitutes safe standstill monitoring. The
with EN 60204-1, Stop Category 2. When the SS2 function is drive control remains in operation. The motor can therefore
selected, the drive brakes autonomously along a quick stop deliver the full torque to hold the current position. The actual
ramp. In contrast to SS1, the drive control remains operational position is reliably monitored. In contrast to safety functions SS1
afterwards, i.e. the motor can supply the full torque required to and SS2, the speed setpoint is not influenced autonomously.
maintain zero speed. Standstill is safely monitored After SOS has been activated, the higher-level control must
(Safe Operating Stop function). bring the drive to a standstill within a parameterized time and
then hold the position setpoint.
If the variant "SS2 with external stop (SS2E)" is parameterized,
the drive does not brake autonomously when the function is
selected. In this case, the higher-level control must bring the
drive to a standstill within a parameterized Safe Operating Stop
transition time. The SBR (Safe Brake Ramp) and SAM
(Safe Acceleration Monitor) functions are not active. SS2E is a
useful function for drives that need to be stopped as a group by
the Motion Control system in order to prevent potential damage
to the machine or product.
Application Application
As with SS1, the SS2 function ensures the quickest possible SOS is an ideal solution for all those applications for which the
deceleration of the motor. However, the motor power is not machine or parts of the machine must be at a safe standstill for
switched off. Instead, a control system prevents it from leaving certain steps, but the drive must also supply a holding torque. It
the standstill position – even if it is affected by external forces. is ensured that despite counter torque the drive remains in its
Typical applications for SS2 include machine tools, for example. current position. In contrast to SS1 and SS2, the drive does not
brake autonomously in this case. It expects the higher-level
controller to ramp down the relevant axes as a coordinated
group within an adjustable delay time. This can be used to
prevent any damage to the machine or product. Typical
applications for SOS include winders, converting and
packaging machines and machine tools.
Customer benefits Customer benefits
The SS2 function ensures a rapid axis stop. Because the control No mechanical components are necessary to keep the axis in
remains active, after the safety function is deselected, position despite any counterforce that may occur. Due to the
productive operation can continue without referencing. This short switching times and the fact that the drive control always
ensures short setup and standstill times and high productivity. remains active, setup and downtimes are reduced.
Recalibration of the axis after exiting the SOS function is not
necessary. The axis can immediately be moved again after
deactivation of the SOS function.

v
SOS s SOS
G_D211_XX_00306

G_D211_XX_00207

t ∆t t

Siemens D 21.3 · 2022 2/5


© Siemens 2022

Highlights

Safety Integrated

■ Function
Safe Brake Control (SBC) Safe Brake Test (SBT)
The SBC function permits the safe control of a holding brake. The SBT diagnostic function carries out a brake function test at
SBC is always activated in parallel with STO. regular intervals or before personnel enter the danger zone.
Effect Effect
2 A holding brake which is active in a de-energized state is A good way to check the proper functioning of brakes that have
controlled and monitored using safe two-channel technology. become worn is to apply a torque to the closed brake. Drive
Due to the two-channel control, the brake may still be activated systems that have two brakes, e.g. motor brake and external
in the event of an insulation fault in the control cable. Errors of brake, can be tested with different torque values.
this kind are detected early by means of test pulses.
Note:
Safe Brake Control does not detect mechanical faults in the
brake itself, such as worn brake linings. For Motor Modules in
booksize format, the terminals for the motor brake are
integrated. An additional Safe Brake Relay is required for Power
Modules in blocksize format. An additional Safe Brake Adapter
is necessary for Power Modules in chassis format.
Application Application
The SBC function is used in conjunction with the functions STO The SBT diagnostic function is suitable for implementing a safe
or SS1 to prevent the movement of an axis in the torque-free brake in combination with the SBC function.
state, e.g. because of gravity.
Customer benefits Customer benefits
Again, the function saves the use of external hardware and the The function detects faults or wear in the brake mechanics.
associated wiring. Automatically testing the effectiveness of brakes reduces
maintenance costs and increases the safety and availability of
the machine or plant.

SBT
v
STO

G_D211_XX_00311
M,s
G_D211_XX_00276

SBC
t
t

2/6 Siemens D 21.3 · 2022


© Siemens 2022

Highlights

Safety Integrated

■ Function
Safely-Limited Speed (SLS) Safe Speed Monitor (SSM)
The SLS function monitors the drive to ensure that it does not The SSM function warns when a drive is working below an
exceed a preset speed or velocity limit. adjustable speed limit. As long as it remains below the threshold,
the function issues a safety-related signal.
Effect Effect 2
The SLS function monitors the drive against a parameterized If a speed value drops below a parameterized limit, a safety-
speed limit. Four different limit values can be selected. As in the related signal is generated. This can, for example, be processed
case of SOS, the speed setpoint is not influenced independently. in a safety control unit to respond to the event by programming,
After SLS has been selected, the higher-level control must bring depending on the situation.
the drive down below the selected speed limit within
a parameterizable time. If the speed limit is exceeded,
a customizable drive-integrated fault reaction occurs.
The SLS limit stage 1 can be multiplied by a factor that is
transferred in 16-bit resolution via PROFIsafe. This allows
an almost unlimited number of limits to be specified.
Application Application
The SLS function is used if people are in the danger zone of With the SSM function, in the simplest case, a safety door can be
a machine and their safety can only be guaranteed by reduced unlocked if the speed drops below a non-critical level. Another
speed. Typical application cases include those in which an typical example is that of a centrifuge that may be filled only
operator must enter the danger zone of the machine for the when it is operating below a configured speed limit.
purposes of maintenance or setting up, such as a winder in
which the material is manually threaded by the operator.
To prevent injury to the operator, the roller may only spin at
a safely reduced speed. SLS is often also used as part of
a two-stage safety concept. While a person is in a less critical
zone, the SLS function is activated, and the drives are only
stopped safely in a smaller area with higher potential risk. SLS
can be used not only for operator protection, but also for
machinery protection, e.g. if a maximum speed must not be
exceeded.
Customer benefits Customer benefits
The SLS function can contribute to a significant reduction in Unlike SLS, there is no drive-integrated fault reaction when the
downtime, or greatly simplify or even accelerate setup. speed limit is exceeded. The safe feedback can be evaluated in
The overall effect achieved is a higher availability of the a safety control unit, allowing the user to respond appropriately
machine. Moreover, external components such as speed to the situation.
monitors can be omitted.

v
v SLS
G_D211_XX_00209
G_D211_XX_00307

t 0
t

Siemens D 21.3 · 2022 2/7


© Siemens 2022

Highlights

Safety Integrated

■ Function
Safe Direction (SDI) Safely-Limited Acceleration (SLA)
The SDI function ensures that the drive can only move in the The SLA function monitors that the drive does not exceed
selected direction. a preset acceleration limit value.
Effect Effect
2 Deviation from the direction of motion currently being monitored The SLA function monitors that the motor does not violate the
is detected reliably and the configured drive-integrated fault defined acceleration limit (e.g. in setup mode). SLA detects
reaction is initiated. It is possible to select which direction of early on whether the speed is increasing at an inadmissible rate
rotation is to be monitored. (the drive accelerates uncontrollably) and initiates the stop
response.
Application Application
The SDI function is used when the drive may only move in one The SLA function is used, e.g., for SIMATIC Safe Kinematics.
direction. A typical application is to permit the operator access SLA can only be used in safety systems with an encoder.
to a danger zone, as long as the machine is rotating in the safe
direction, i.e. away from the operator. In this state, the operator
can feed material into the work zone or remove material from the
work zone without danger.
Customer benefits Customer benefits
The function saves the use of external components such as The function monitors for maximum permissible acceleration in
speed monitors and the associated wiring. The release of setup mode and safe monitoring of the tool center point with
a danger zone while the machine is moving away from the different kinematics.
operator increases productivity. Without the SDI function, the
machine must be safely stopped during material loading and
removal.

a
G_D211_XX_00308a

S SLA

G_D211_XX_00363

2/8 Siemens D 21.3 · 2022


© Siemens 2022

Highlights

Safety Integrated

■ Function
Safely-Limited Position (SLP) Safe Position (SP)
The SLP function monitors the axis to ensure that it remains The SP function transfers the actual position values determined
within the permissible traversing range. safely in the drive over safe PROFIsafe communication to
a safety control.
Effect
When SLP is activated, the traversing range limited by the
Effect 2
configured software limit switches is safely monitored. If the In contrast to the SLP function that monitors the current actual
permitted traversing range is exited, a configurable fault position value against a limit and, in the case of an overshoot,
reaction occurs. It is possible to toggle between two traversing activates a drive-integrated fault reaction, SP transfers the
ranges, even when the machine is in operation. current actual position values to the safety control. Position
monitoring is implemented in the safety program of the control.
Extended PROFIsafe telegrams are available for transferring the
position values. The position values can be transferred in 16-bit
or 32-bit resolution, as required. A time stamp is also transferred
with the position values.
Application Application
SLP is used for applications in which machine operators have to Tailor-made safety concepts can be created using the SP
enter a protection area, e.g. for feeding in and removing function. It is ideal for use on machines that require flexible
material. Safe monitoring of the axis position ensures that the safety functions. It is extremely versatile and can be used, for
axis cannot move into the protection area released for operators example, to implement safe, axis-specific range detection by
and so place them in danger, for example, on storage and means of safe cams. The SP function can also be used to
retrieval machines, gantry cranes or machining centers. implement multi-axis safety concepts, multi-dimensional
protection areas and zone concepts.
Customer benefits Customer benefits
SLP can be used for highly-effective protection area monitoring. Position monitoring or speed monitoring is implemented in the
The function does away with the use of external components safety program of the control, so the user has the flexibility for
such as hardware limit switches and the associated wiring implementing tailor-made safety functions. The reaction to a limit
expense. Due to the short reaction time following a limit over- overshoot must also be specified in the safety program. This
shoot, safety clearances can be reduced. means a higher initial programming outlay, but it does offer the
opportunity for initiating different fault reactions depending on
the situation.

s
SLP
G_D211_XX_00310

t
G_D211_XX_00309a

Siemens D 21.3 · 2022 2/9


© Siemens 2022

Highlights

Safety Integrated

■ Function
Safe Cam (SCA)
The SCA function enables safety-related monitoring of the
position.
Effect
2 The SCA function outputs a safe signal if the drive is within
a specified position range. It facilitates the realization of safe
axis-specific range detection. Up to 30 safe cams can be
parameterized per axis.
Application
It is only permissible that a protective door is opened if a drive is
in a certain position range. The drive may only be traversed with
reduced speed when it is located in a certain position range.
Customer benefits
The function enables safety-related switchover of safety
functions. With SCA, safe electronic cam controllers can
be implemented without additional hardware. With SCA,
work and protection zone delimitations are reliably detected.

s
SCA 3
G_D211_XX_00360

SCA 2

SCA 1 t

0
t

2/10 Siemens D 21.3 · 2022


© Siemens 2022

Highlights

Safety Integrated

■ Function
Basic Functions, Extended Functions, and Advanced PROFIsafe
Functions
SINAMICS drives support the PROFIsafe profile based
With SINAMICS G converters, the safety functions are basically on PROFINET as well as on PROFIBUS.
implemented without encoders.
PROFIsafe is an open communications standard that supports
With SINAMICS S drives, the safety functions are implemented
with encoders – individual safety functions can also be operated
standard and safety-related communication over the same
communication path (wired or wireless). A second, separate bus
2
without encoders. system is therefore not necessary. The telegrams that are sent
are continually monitored to ensure safety-relevant
The Safety Integrated Functions are grouped into Basic communication.
Functions, Extended Functions, and Advanced Functions.
Possible errors such as telegrams that have been lost, repeated
The Basic Functions are included in the standard scope of or received in the incorrect sequence are avoided. This is done
supply. by consecutively numbering the telegrams in a safety-relevant
The Extended Functions must be activated by a license. fashion, monitoring their reception within a defined time and
The Advanced Functions for SINAMICS S120 must also be transferring an ID for transmitter and receiver of a telegram.
activated via a license. A CRC (cyclic redundancy check) data security mechanism is
The electronic Certificate of License is the paperless delivery also used.
form for runtime options for SINAMICS and contains information
about the type of rights of use purchased for the software. The operating principle of Safety Integrated
• Basic Functions Two independent switch-off signal paths
- Safe Torque Off (STO) Two independent switch-off signal paths are available.
- Safe Brake Control (SBC) All switch-off signal paths are low active. This ensures that the
- Safe Stop 1 (SS1) system is always switched to a safe state if a component fails or
• Extended Functions in the event of cable breakage. If a fault is discovered in the
- Safe Stop 1 with external stop (SS1E) switch-off signal paths, the STO or SS1 function (depending on
- Safe Stop 1 (SS1) with SBR or SAM parameter settings) is activated and a system restart inhibited.
- Safe Stop 2 with external stop (SS2E)
- Safe Stop 2 (SS2) with SBR or SAM Two-channel monitoring structure
- Safe Operating Stop (SOS) All the main hardware and software functions for Safety
- Safely-Limited Speed (SLS) Integrated are implemented in two independent monitoring
- Safe Speed Monitor (SSM) channels (e.g. switch-off signal paths, data management, data
- Safe Direction (SDI) comparison). A cyclic crosswise comparison of the safety-
- Safely-Limited Acceleration (SLA) relevant data in the two monitoring channels is carried out.
- Safe Brake Test (SBT) diagnostic function
The monitoring functions in each monitoring channel work on the
• Advanced Functions principle that a defined state must prevail before each action is
- Safely-Limited Position (SLP) carried out and a specific acknowledgement must be made after
- Safe Position (SP) each action. If these expectations of a monitoring channel are
- Safe Cam (SCA) not fulfilled, the drive coasts to a standstill (two channel) and an
The license for Safety Integrated Advanced Functions also appropriate message is output.
includes the license for Safety Integrated Extended Functions. Forced dormant error detection using test stop
For the Extended Functions SS1 and SS2 with SAM, Safe The functions and switch-off signal paths must be tested at least
Acceleration Monitor (SAM) is performed during braking to once within a defined time in order to meet requirements as per
identify any faults already during the braking phase. EN ISO 13849-1 and IEC 61508 in terms of timely fault
With SS1 and SS2, a Safe Brake Ramp (SBR) can be configured detection. This must be implemented either in cyclic manual
as an alternative. mode or the test stop must be automatically initiated as part
of the process. The test stop cycle is monitored, and after
The Basic Functions – activated via on-board terminals on the a specific time has been exceeded, an alarm is output. A test
device, TM54F Terminal Module (only for SINAMICS S) or via stop does not require a POWER ON. The acknowledgment is set
PROFIsafe – do not require an encoder. by canceling the test stop request.
Activation of the Safety Integrated Functions Examples of when forced dormant error detection must be
The safety functions for SINAMICS drives can be activated via performed:
terminals, e.g. for use of a conventional safety circuit. • When the drives are at a standstill after the system has been
switched on
For standalone safety solutions for small to medium-sized
applications, it is frequently sufficient that the various sensing • Before the protective door is opened
components are directly hardwired to the drive. • At defined intervals (e.g. every 8 hours)
For integrated safety solutions, the safety-relevant sequences • In automatic mode, time and event-driven
are generally processed and coordinated in the fail-safe
SIMATIC controller. Here, the system components communicate
via the PROFINET or PROFIBUS fieldbus. The safety functions
are controlled via the safe PROFIsafe communication protocol.
SINAMICS drives can be easily integrated into the plant
or system topology.

Siemens D 21.3 · 2022 2/11


© Siemens 2022

Highlights

Safety Integrated

■ Function
Safe speed/position sensing without/with encoder The encoder must be mechanically attached in such a manner
that the encoder shaft is unable to unplug or slide off. For notes
Safe actual value sensing without encoder on this, see IEC 61800-5-2: 2016, Table D.16.
A drive monitor with encoder is necessary for operation A list of Siemens motors that fulfill the electrical and mechanical
of a series of safety functions.
2 For applications with encoderless mode or with encoders that
requirements is available at:
https://support.industry.siemens.com/cs/document/33512621
have no safety capability, the safety functions can also be The following can be used for safe speed/position sensing:
implemented without encoder. It is not possible to use all safety
functions in this case. • Single-encoder systems or
For chassis format devices, encoderless safety functions can be • Dual-encoder systems
implemented on request (see SINAMICS S120 Safety Integrated Single-encoder system
and SINAMICS G130, G150, S120 Chassis, S120 Cabinet
Modules, S150; Safety Integrated Function Manuals).
DRIVE-CLiQ
In operation without encoder, the actual speed values are
calculated from the measured electrical actual values. This E = Encoder
means that speed monitoring is also possible during operation M = Motor
without an encoder.
Safety Integrated Extended Functions "without encoder" must
not be used if the motor, after it has been switched off, can still

G_D211_EN_00216b
be accelerated by the mechanical elements of the connected Machine table
machine component.
Sensor Module E M
Safe actual value sensing with encoder (not applicable for motor with
DRIVE-CLiQ interface) Backlash
Incremental encoders or absolute encoders can be used for
safe sensing of the position values on a drive.
Example: Single-encoder system
Safe actual value sensing relies on redundant evaluation of the
incremental tracks A/B that supply sin/cos signals of 1 Vpp. Only In a single-encoder system, the motor encoder is used
encoders of the type whose A/B track signals are created and exclusively for safe actual value sensing.
processed using purely analog techniques can be used. The Dual-encoder system
encoder signals are input via the SMC20 Sensor Module
Cabinet-Mounted (Option K48 for cabinets).
DRIVE-CLiQ
HTL/TTL incremental encoders may also be used. In this case,
safe actual value sensing is achieved by using two independent
encoders. The minimum possible speed resolution must also be
taken into account.The encoder signals are input via the SMC20
Sensor Module Cabinet-Mounted (Option K50, K52 for
cabinets).
E = Encoder
As an alternative, motors with an integrated DRIVE-CLiQ M = Motor
interface can be used. The speed or position actual values

G_D211_EN_00217b
are generated directly in the motor as safe values and are Sensor Module E M
transferred to the Control Unit over safe communication via (not applicable for motor with
DRIVE-CLiQ. DRIVE-CLiQ interface) E
Certified built-on rotary encoders with DRIVE-CLiQ interface
may also be used (see
https://support.industry.siemens.com/cs/document/65402168). Example: Dual-encoder system
In the case of the dual-encoder system, the safe actual values
for a drive are provided by two separate encoders. The actual
values are transferred to the Control Unit over DRIVE-CLiQ.
When motors without a DRIVE-CLiQ connection are used,
a Sensor Module must be provided.
HTL/TTL incremental encoders can be used as an alternative
with a dual-encoder system. Either two HTL/TTL encoders, one
dual-HTL/TTL encoder or one HTL/TTL encoder and one sin/cos
encoder can be used.

2/12 Siemens D 21.3 · 2022


© Siemens 2022

Highlights

Safety Integrated

■ Function
The safety functions are listed below with criteria for actual value sensing:
Functions Abbreviation With encoder Without encoder Description
Basic Functions Safe Torque Off STO Yes Yes Safe Torque Off
Yes 1)
Safe Stop 1 SS1 Yes Safe stopping process in
accordance with stop category 1 2
Safe Brake Control SBC Yes Yes Safe Brake Control
Extended Functions Safe Torque Off STO Yes Yes Safe Torque Off
Safe Stop 1 SS1 Yes Yes 1) Safe stopping process in
accordance with stop category 1
Safe Brake Control SBC Yes Yes Safe Brake Control
Safe Operating Stop SOS Yes No Safe monitoring of the standstill
position
Safe Stop 2 SS2 Yes No Safe stopping process in
accordance with stop category 2
Safely-Limited Speed SLS Yes Yes 1) Safe monitoring of the maximum
speed
Safe Speed Monitor SSM Yes Yes 1) Safe monitoring of the minimum
speed
Safe Direction SDI Yes Yes 1) Safe monitoring of the direction of
motion
Safely-Limited Accelera- SLA Yes No Safely-Limited Acceleration
tion
Safe Brake Test SBT Yes No Diagnostic function for safe testing
of the required holding torque of
a brake
Advanced Functions Safely-Limited Position SLP Yes No Safely-Limited Position
Safe Position SP Yes Yes 2) Safe transfer of position values
Safe Cam SCA Yes No Safe cams

■ More information
The Safety Integrated Function Manual contains detailed
information about the safety functions
https://support.industry.siemens.com/cs/document/109781722
Further manuals pertaining to Safety Integrated in drive systems
can be found on the internet at
https://support.industry.siemens.com/cs/ww/en/ps/13206/man
More information about Safety Integrated in SINAMICS can be
found on the internet at
www.siemens.com/safety-drives

1) The use of this safety function without encoder is permitted with 2) Only for the transmission of relative position values. An encoder is required
asynchronous (induction) motors, synchronous motors from the to transmit absolute position values.
SIEMOSYN series, or with SIMOTICS reluctance motors.

Siemens D 21.3 · 2022 2/13


© Siemens 2022

Highlights

Safety Integrated for SINAMICS S120 Chassis/Cabinet Modules/S150

■ Overview
The safety functions integrated into the drive can greatly reduce The Extended and Advanced Functions require a license for
the effort required to implement safety concepts. each axis with safety functions. It is of no consequence here
which safety functions are used and how many.
The Safety Integrated functions are implemented electronically
and therefore offer short response times in comparison to The license can be ordered as an option with the memory card.
2 solutions with externally implemented monitoring functions.
As an alternative to controlling via terminals and/or PROFIsafe,
Alternatively, a single-user license can also be purchased.
The electronic Certificate of License is the paperless delivery
there is also the option to parameterize several Safety Integrated form for runtime options for SINAMICS and contains information
functions without selection. In this mode, after parameterization about the type of rights of use purchased for the software.
and a POWER ON, these functions are permanently selected. The electronic Certificate of License is supplied as a PDF file via
the Online Software Delivery Portal (OSD).
Example This enables quick notification with a download link to the email
"SLS without selection" can be used, for example, to monitor the address to be stated in the order.
maximum velocity to prevent the drive from exceeding The Web License Manager can also be called from the OSD to
a mechanical speed limit. For this purpose, use of the "SLS assign the runtime license to a memory card.
without selection" function means that an F-DI is not needed. In this case, the data of the electronic Certificate of License are
automatically transferred to the Web License Manager and do
Licensing not have to be entered manually.
No license is required for the Basic Functions. This ensures quick availability of the license key and simple and
secure handling and management of the license certificates.
You will find information on the OSD at:
https://support.industry.siemens.com/cs/ww/en/view/109759444

Online Web
Siemens Direct link
Software License
Mall
Delivery Manager
OSD Automatic

G_D011_EN_00601
Log In
Log In

Within a few hours

„CoL“ „Key“
PDF

The licenses for SINAMICS S120 Chassis and Chassis-2 format Safe Brake Adapter
units can be ordered as option F01 to F06 (Extended Functions)
or A01 to A06 (Advanced Functions) for specific axes at the The Safe Brake Control (SBC) function requires a Safe Brake
same time as the memory card. Adapter (option K88 for SINAMICS S120 Cabinet Modules and
SINAMICS S150). The Safe Brake Control is integrated in Motor
The Certificates of License are stored in directory "KEYS". Modules in booksize format.
For SINAMICS S120 Cabinet Modules and Cabinet Modules-2, The Safe Brake Adapter and the brake control that is integrated
the licenses for Safety Extended Functions can be ordered for in the booksize format allows safe control of electro-mechanical
specific axes with the options K01 to K05 for Motor Modules. motor brakes.
Safety Advanced Functions are available on request.
The Safe Brake Adapter controls 230 V AC brakes. The SBC
The license for Safety Extended Functions for SINAMICS S150 function monitors the control of the brake, however, not its
can be ordered as option K01. Safety Advanced Functions are mechanical functioning.
available on request.
The converter controls the connected brake using the motor
holding brake function.
External surge suppressors are not required. The cable
harnesses for connection to the Power Module are included in
the scope of supply.
The brake is controlled in accordance with IEC 61508 SIL 2
and EN ISO 13849-1 PL d and Category 3.
Safe Brake Adapter

230 V AC Motor holding


brake

Brake M
G_D213_EN_00090a

diagnostics

Safe Brake Control (SBC)

2/14 Siemens D 21.3 · 2022


© Siemens 2022

Highlights

Safety Integrated for SINAMICS S120 Chassis/Cabinet Modules/S150

■ Function
Overview of Safety Integrated functions
Function Control Underlying function Reaction to limit External setpoint Encoder License
overshoot input effective required 1) required
Basic Functions
STO • EP terminals on the power unit and SBC – No No No 2
a DI on the Control Unit (if activated)
• Terminal module (option K82 2))
• F-DI on TM54F
• F-DI on CU310-2/D4xx/CX32
• PROFIsafe
SBC • With STO (immediately or following – – – No No
expiry of the delay time with SS1)
• Via Safe Brake Adapter 2)
SS1 • EP terminals on the power unit and STO, following expiry of the STO Can be No No
a DI on the Control Unit parameterized delay time, SBC parameterized
• Terminal module (option K82 2)) (if activated)
• F-DI on TM54F
• F-DI on CU310-2/D4xx/CX32
• PROFIsafe
Extended Functions
STO • F-DI on TM54F SBC – No Yes Yes
• F-DI on CU310-2/D4xx/CX32 (if activated)
• PROFIsafe
SS1 with • F-DI on TM54F Safe Acceleration Monitor (SAM) or Safe STO Can be No Yes
SBR/SAM • F-DI on CU310-2/D4xx/CX32 Brake Ramp (SBR) during braking. STO parameterized
• PROFIsafe and SBC (if activated) following expiry of
the parameterized delay time or if the
speed falls below the minimum speed
limit
SS2 • F-DI on TM54F Safe Acceleration Monitor (SAM) during SS1  STO No Yes Yes
• F-DI on CU310-2/D4xx/CX32 braking. Following expiry of the parame-
• PROFIsafe terized delay time SOS
SLS • F-DI on TM54F – STO, SS1 (can be Yes No Yes
encoder- • F-DI on CU310-2/D4xx/CX32 parameterized)
less • PROFIsafe
• Continuously activated
SLS • F-DI on TM54F – STO, SS1, SS2 or Yes Yes Yes
• F-DI on CU310-2/D4xx/CX32 SOS (can be
• PROFIsafe parameterized)
• Continuously activated
SOS • F-DI on TM54F – SS1  STO Yes Yes Yes
• F-DI on CU310-2/D4xx/CX32
• PROFIsafe
SSM • Always active, if configured – Signals that the Yes No Yes
speed has fallen
below a specified
value
SDI • F-DI on TM54F – STO, SS1, SS2 or Yes No Yes
• F-DI on CU310-2/D4xx/CX32 SOS (can be
• PROFIsafe parameterized)
• Continuously activated
SLA • F-DI on TM54F – STO, SS1, SS2 (can Yes Yes Yes
• PROFIsafe be parameterized)
SBT • Safety Control Channel – Signals test result. Yes Yes Yes
• BICO signals Warning if test fails
• for test stop selection
Advanced Functions
SLP 3) • F-DI on TM54F – STO, SS1, SS2 or Yes Yes Yes
• F-DI on CU310-2/D4xx/CX32 SOS (can be
• PROFIsafe parameterized)
SP 3) • Always active, if configured – – Yes Yes Yes
SCA 3) • PROFIsafe – can be Yes Yes Yes
parameterized

1)
The encoderless Safety Extended Functions can be implemented only on
request for SINAMICS S120 chassis format units and cabinet units.
2)
In addition for SINAMICS S120 Cabinet Modules and SINAMICS S150
converter cabinet units (option K88).
3)
SINAMICS S120 Cabinet Modules and SINAMICS S150 Converter
Cabinet Units available on request

Siemens D 21.3 · 2022 2/15


© Siemens 2022

Highlights

Communication

■ Overview
Communication overview
Digital bus systems are commonly used in industrial automation
today. These handle communication between the control level,
the machine control, the sensors and actuators. The SINAMICS
2 product family offers integrated communication interfaces in all
product groups – which can be used to connect the most
important fieldbus systems in the simplest possible way.
The properties and special application areas of the different bus
systems are described briefly below. The following table
provides an overview of the available reports for the CU310-2
and CU320-2 Control Units.

Protocol S120 S150


S120M
CU310-2 CU320-2 CU320-2
PROFINET   
• PROFINET RT   
• PROFINET IRT isochronous   
• PROFINET IRT non-isochronous   
• PROFINET Shared Device   
• PROFINET media redundancy MRP   
(surge prone)
• PROFINET media redundancy MRPD   
(surge free)
• System redundancy S2   
• PROFIsafe   
• PROFIenergy   
• PROFIdrive application class 1   
• PROFIdrive application class 3   
• PROFIdrive application class 4   
PROFIBUS DP   
• PROFIBUS DP equidistance and   
isochronous mode
• PROFIBUS DP peer-to-peer   
communication
EtherNet/IP –  
Modbus TCP   
Modbus RTU – – –
AS-Interface – – –
BACnet MS/TP – – –
USS   
FLN P1 – – –
Web server   

2/16 Siemens D 21.3 · 2022


© Siemens 2022

Highlights

Communication > PROFINET

■ Overview
PROFINET – the Ethernet standard for automation
PROFINET is the world's leading Industrial Ethernet standard for
automation with more than 40 million nodes installed worldwide.
PROFINET makes companies more successful, because it
speeds up processes and raises both productivity and plant
availability.
2

G_D211_XX_00050

Your advantages at a glance

Flexibility Efficiency Performance

Tailor-made plant concepts Optimal use of resources Increased productivity

Industrial Wireless LAN One cable for everything Speed

Safety Device/network diagnostics High precision

Flexible topologies Energy efficiency Large quantity structures

Open standard Simple wiring High transmission rate

(@*,@99@
Web tools Fast device replacement Redundancy

Expandability Ruggedness/stability Fast start-up

Siemens D 21.3 · 2022 2/17


© Siemens 2022

Highlights

Communication > PROFINET

■ Overview
Flexibility Open standard
Short response times and optimized processes are the basic PROFINET, the open multi-vendor standard
requirements for competitiveness in global markets because the (IEC 61158/IEC 61784), is supported by PROFIBUS and
product lifecycles are becoming shorter and shorter. PROFINET International (PI). It stands for maximum
2 PROFINET ensures maximum flexibility in plant structures and
production processes, and it enables you to implement
transparency, open IT communication, network security and
simultaneous real-time communication.
innovative machine and plant concepts. For example, mobile Thanks to its openness, PROFINET provides the basis for
devices can also be integrated at locations that are difficult a standardized automation network in the plant, to which all
to access. other machines and devices can be connected. Even the
integration of existing plant components, for example using
Flexible topologies PROFIBUS, presents no problems due to the use of network
In addition to the linear structure characterized by the transitions.
established fieldbuses, PROFINET also enables the use of star, Use of web tools
tree and ring structures. This is made possible by switching
technology via active network components, such as Industrial Thanks to the unrestricted support of TCP/IP, PROFINET permits
Ethernet switches and media converters, or by integrating the use of standard web services such as web servers.
switch functionality into the field devices. This results in Irrespective of the tool used, information from the automation
increased flexibility in the planning of machines and plants, level can be accessed from virtually any location using
as well as savings in cabling. a commercially available internet browser. This considerably
simplifies commissioning and diagnostics. Users can then
The PROFINET network can be installed without any specialist decide for themselves how much openness to the IT world they
knowledge at all and meets all requirements that are relevant to want to allow for their machine or plant. This means that
the industrial environment. The "PROFINET Installations PROFINET can be used simply as an isolated plant network or
Guidelines" assist manufacturers and users with network connected via appropriate Security Modules, such as the
planning, installation and commissioning. Symmetrical copper SCALANCE S modules, to the office network or the internet.
cables or RFI-resistant fiber-optic cables are used, depending In this way, new remote maintenance concepts or the high-
on the application. Devices from different manufacturers are speed exchange of production data become possible.
easily connected via standardized and rugged plug-in
connectors (up to IP65/IP67 degree of protection). Expandability
By integrating switch functionality into the devices, linear On the one hand, PROFINET facilitates the integration of existing
topologies can be created that are directly oriented toward systems and networks without any great effort. In this way,
an existing machine or plant structure. This reduces cabling PROFINET safeguards investments in existing plant
overhead and cuts down on components such as external components that communicate via PROFIBUS and other
switches. fieldbuses such as AS-Interface. On the other hand, additional
PROFINET nodes can be added at any time. By using additional
IWLAN network components, network infrastructures can be expanded
PROFINET also supports wireless communication with Industrial using cabling or wireless methods – even while the plant is
Wireless LAN, thus opening up new fields of application. For operating.
example, technologies subject to wear, such as trailing cables,
can be replaced and automated guided vehicle systems and
mobile operator panels can be used.
Safety
The PROFIsafe safety profile, which has been tried and tested
with PROFIBUS and which permits the transmission of standard
and safety-related data on a single bus cable, can also be used
with PROFINET. No special network components are necessary
for fail-safe communication, which means that standard
switches and standard network transitions can continue to be
used without any restrictions. In addition, fail-safe
communication is equally possible via Industrial Wireless LAN
(IWLAN).

2/18 Siemens D 21.3 · 2022


© Siemens 2022

Highlights

Communication > PROFINET

■ Overview
Efficiency Energy efficiency
Greater global competition means that companies must use Moving toward the green factory: PROFIenergy is a profile that
their resources economically and efficiently. This applies in provides functions and mechanisms for PROFINET field devices
particular to production. This is where PROFINET ensures that support energy-efficient production.
greater efficiency. Simple engineering guarantees fast
commissioning, while reliable devices ensure a high level of The profile, which is defined by the PNO and is independent of
any manufacturers or devices, enables energy demand and
2
plant availability. Comprehensive diagnostic and maintenance
concepts help to reduce plant downtimes and keep costs to be significantly reduced: Using PROFIenergy, any
maintenance costs to a minimum. specific loads that are not currently being used can be switched
off. This achieves a noticeable reduction in energy costs during
One cable for everything breaks in production. PROFIenergy permits the simple,
automated activation and deactivation of technologically related
PROFINET permits simultaneous fieldbus communication with plant components. It is coordinated centrally by means of
isochronous mode and standard IT communication (TCP/IP) on a higher-level controller and is networked via PROFINET. This
one cable. This real-time communication for the transmission of ensures that as much energy as possible is saved during long
user/process data and diagnostic data takes place on a single breaks. Temporarily switching off plant components contributes
cable. Specific profile communication (PROFIsafe, PROFIdrive to the even distribution and most efficient use of energy.
and PROFIenergy) can be integrated without any additional
cabling. This solution offers a wide scope of functions at a low The use of PROFIenergy is made easy for the machine builder
level of complexity. by its integration into familiar series of products. In addition,
PROFIenergy is defined in such a way that the necessary
Device and network diagnostics function blocks can easily be integrated into existing automation
By retaining the tried and tested PROFIBUS device model, the systems at a later stage.
same diagnostics information is available with PROFINET. Simple wiring
In addition, module-specific and channel-specific data can also
be read out from the devices during device diagnostics, Particularly stringent demands are made on the installation
enabling faults to be located quickly and easily. Apart from the of cables in the industrial environment. In addition, there is
availability of device information, the reliability of network a requirement to set up industry-standard networks in the
operation has top priority in the network management. shortest possible time without any special knowledge.
In existing networks the Simple Network Management Protocol With FastConnect, Siemens offers a high-speed installation
(SNMP) has established itself as the de facto standard for the system that meets all of these requirements. FastConnect is the
maintenance and monitoring of the network components and standard-compliant, industry-standard cabling system
their functions. PROFINET uses this standard and gives users consisting of cables, connectors and assembly tools for
the opportunity to maintain their networks with tools that are PROFINET networks. The time required for connecting terminals
familiar to them, such as the SINEMA Server network is minimized by the simple installation method using just a single
management software. tool, while installation errors are prevented by the practical color-
coding. Both copper cables and glass fiber optic cables can be
For easier maintenance of PROFINET devices, both on-site and easily assembled on site in this way.
remotely via a secure VPN connection, application-specific
websites can be set up on the web server of the field devices Fast device replacement
using the familiar HTML standard.
PROFINET devices are identified by means of a name assigned
during configuration. When replacing a defective device, a new
device can be recognized from its topology information by the
IO controller and a new name can be assigned to it
automatically. This means that no engineering tool is necessary
for the replacement of equipment.
This mechanism can even be used for the initial commissioning
of a complete system. This speeds up commissioning,
particularly in the case of series machines.
Ruggedness
An automation network must be able to withstand most external
sources of interference. The use of Switched Ethernet prevents
faults in one section of the network from affecting the entire plant
network. For areas that are particularly prone to radio frequency
interference (RFI), PROFINET allows the use of fiber optic
cables.

Siemens D 21.3 · 2022 2/19


© Siemens 2022

Highlights

Communication > PROFINET

■ Overview
Performance Media redundancy
Productivity and product quality determine the level of success A higher plant availability can be achieved with a redundant
in the market. Precise motion control, dynamic drives, installation (ring topology). The media redundancy can be
high-speed controllers and the deterministic synchronization of implemented not only with the aid of external switches, but also
2 devices are therefore key factors in achieving superior
production. They facilitate high production rates and optimum
by means of integrated PROFINET interfaces. Using the media
redundancy protocol (MRP), reconfiguration times of 200 ms
product quality at the same time. can be achieved. If the communication is interrupted in just one
part of the ring installation this means that a plant standstill is
Speed and precision prevented and any necessary maintenance or repair work can
Fast motion control applications demand precise and be performed without any time pressure.
deterministic exchange of data. This is implemented by means For motion control applications, PROFINET with IRT in ring
of drive controllers using isochronous real time (IRT). topologies offers extended media redundancy for planned
With IRT and isochronous mode, PROFINET permits fast and duplication (MRPD) which operates in a bumpless mode without
deterministic communication. This synchronizes the various any reconfiguration time. If communication is interrupted
cycles of a system (input, network, CPU processing and output), (e.g. a cable break) the process can continue operating without
even in the case of parallel TCP/IP traffic. The short cycle times interruption.
of PROFINET make it possible to raise the productivity of
machines and plants and to guarantee the product quality and SIMOTION
high level of precision. D4x5-2
The standardized PROFIdrive profile permits vendor-
independent communication between CPUs and drives.
SIMOTION
Large quantity structures
C240 PN
The use of PROFINET makes it possible to overcome the existing
restrictions regarding the scope of machines and systems that
SINAMICS
can be implemented. In one network, several different S120
controllers can interact with their assigned field devices. SIMOTION
The number of field devices per PROFINET network is virtually D4x5-2
unlimited – the entire range of IP addresses is available.
High data rate
PROFINET
By using 100 Mbit/s in full duplex mode, PROFINET achieves
a significantly higher data rate than previous fieldbuses.
This means that other plant data can be transmitted over TCP/IP
without any problems, in addition to the process data.
PROFINET therefore meets the combined industrial demands
for simultaneously transmitting high-speed IO data and large Switch SINAMICS
volumes of data for additional sections of the application.

G_D211_XX_00294a
SCALANCE S120
Even the transmission of large volumes of data, such as that X200IRT
from cameras, has no adverse effect on the speed and precision
of the IO data transmission, thanks to PROFINET mechanisms.

Bumpless media redundancy illustrated by example of SINAMICS S120


with SIMOTION and SCALANCE X200IRT

2/20 Siemens D 21.3 · 2022


© Siemens 2022

Highlights

Communication > PROFINET

■ Benefits
• PROFINET is the open Industrial Ethernet standard
for automation
• PROFINET is based on Industrial Ethernet
• PROFINET uses TCP/IP and IT standards
• PROFINET is real-time Ethernet
• PROFINET enables seamless integration of fieldbus systems
2
• PROFINET supports fail-safe communication via PROFIsafe
and also via IWLAN

■ Integration
PROFINET – Functions of the SINAMICS S120/
SINAMICS S150 Control Units
SINAMICS S120/ CU320-2 PN CU320-2 DP CU310-2 PN
SINAMICS S150 (CBE20)
PROFINET with IRT   
(isochronous mode)
Number of ports 2 4 2
Min. send clock in ms 0.25 0.5 0.25
Shared Device   
Bumpless media   
redundancy (MRPD)
Step-change media   
redundancy (MRP)
System redundancy S2  – 
PROFIsafe   
PROFIenergy   
PROFIdrive   

System redundancy
SINAMICS S120 supports the PROFINET function
"system redundancy":
SINAMICS S120 can now be connected to high-availability
systems such as SIMATIC S7-400H with two controllers.
No additional hardware is required to make the connection.
Complex automation tasks in the process industry, in particular,
where plant availability and redundancy of the control system
are essential, require reliable communication with a high-
availability system. Both controllers of the high-availability
system always have access to the SINAMICS S120.
In the event of a cable break or failure of a CPU, the other
controller takes over, thus ensuring uninterrupted
communication.

■ More information
More information is available on the internet at:
www.siemens.com/profinet

Siemens D 21.3 · 2022 2/21


© Siemens 2022

Highlights

Communication > PROFIdrive

■ Overview One drive profile – different application classes


The integration of drives into automation solutions depends very
strongly on the particular drive application. In order to be able to
address the complete, huge bandwidth of drive applications –
from basic frequency converters up to synchronized multi-axis
systems with a high dynamic performance – using just one
profile, PROFIdrive defines six application classes, to which
2 most drive applications can be assigned:
• Class 1 – standard drives (pumps, fans, agitators, etc.)
• Class 2 – standard drives with technological functions
PROFIdrive – the standardized drive interface for PROFINET • Class 3 – positioning drives
and PROFIBUS • Class 4 – motion control drives with central, higher-level
PROFIdrive defines the device behavior and technique to motion control intelligence and the patented "Dynamic Servo
access internal device data for electric drives connected to Control" positioning concept
PROFINET and PROFIBUS – from basic frequency converters • Class 5 – motion control drives with central, higher-level
up to high-performance servo controllers. motion control intelligence and position setpoint interface
It describes in detail the practical use of communication • Class 6 – motion control drives with distributed motion control
functions – device-to-device communication, equidistance and intelligence integrated in the drives
clock cycle synchronization (isochronous mode) in drive
applications. In addition, it specifies all device characteristics ■ Design
which influence interfaces connected to a controller over
PROFINET or PROFIBUS. This also includes the state machine The device model of PROFIdrive
(sequence control), the encoder interface, scaling of values, PROFIdrive defines a device model comprising function
definition of standard telegrams, access to drive parameters, modules, which interoperate inside the device and which reflect
etc. the intelligence of the drive system. These modules have objects
The PROFIdrive profile supports both central as well as assigned to them which are described in the profile and are
distributed motion control concepts. defined with respect to their functions. The overall functionality
of a drive is therefore described through the sum of its
What are profiles? parameters.
For devices and systems used in automation technology, profiles In contrast to other drive profiles, PROFIdrive defines only the
define properties and modes of behavior. This allows access mechanisms to the parameters as well as a subset of
manufacturers and users to define common standards. Devices profile parameters (approx. 30) such as the fault buffer, drive
and systems that comply with such a cross-manufacturer profile, control and device identification.
are interoperable on a fieldbus and, to a certain degree, can be
interchanged. All other parameters are vendor-specific which gives drive
manufacturers great flexibility with respect to implementing
Are there different types of profiles? control functions. The elements of a parameter are accessed
acyclically over data records.
A distinction is made between what are known as application
profiles (general or specific) and system profiles: As a communication protocol, PROFIdrive uses DP-V0, DP-V1,
• Application profiles (also device profiles) predominantly refer and the DP-V2 expansions for PROFIBUS including the functions
to devices (e.g. drives) and include an agreed selection "Device-to-Device Communication" and "Isochronous
regarding bus communication as well as specific device Operation", or PROFINET IO with real-time classes RT and IRT.
applications.
• System profiles describe classes of systems, including master Application Class 4
functionality, program interfaces and integration resources. Automation
Is PROFIdrive fit for the future? Technology

PROFIdrive has been specified by the PROFIBUS and Interpolation


Pos. Control
PROFINET International (PI) user organization, and is specified
as a standard that is fit for the future through standard Clock
G_PM10_DE_00133
IEC 61800-7. Control Word + Speed Setpoint + ... Status Word + Actual Position ...

The basic philosophy: Keep it simple Clock synchronism

The PROFIdrive profile tries to keep the drive interface as simple Drive Drive Drive
as possible and free from technology functions. As a result, Closed Loop Speed Ctrl. Closed Loop Speed Ctrl. Closed Loop Speed Ctrl.

referencing models as well as the functionality and performance


of the PROFINET/PROFIBUS master have either no or only little
influence on the drive interface.

M M M
Encoder Encoder Encoder

■ More information
More information on PROFINET and PROFIBUS is available at:
www.profibus.com

2/22 Siemens D 21.3 · 2022


© Siemens 2022

Highlights

Communication > PROFIBUS

■ Overview DP master class 2


Devices of this type (programming, configuring or operator
control devices) are used during commissioning, for configuring
the DP system, for diagnostics or for operating the active plant
or system. A DP master class 2 can, for example, read input,
output, diagnostic and configuration data of the devices.
DP device 2
A DP device is an I/O device which receives output information
or setpoints from the DP master, and as response, returns input
information, measured values and actual values to the
DP master. A DP device never sends data automatically, but only
when requested by the DP master.
G_PM10_XX_00144

The quantity of input and output information depends on the


PROFIBUS – the proven, rugged bus system for automation device, and for each DP device in each send direction can be
engineering applications a maximum of 244 bytes.

The requirements of users for an open, non-proprietary


communication system have resulted in the specification and
■ Function
standardization of the PROFIBUS protocol. Functional scope in DP masters and DP devices
PROFIBUS defines the technical and functional features of The functional scope can differ between DP masters and
a serial fieldbus system, with which the distributed field DP devices. The different functional scopes are classified as
automation devices in the lower area (sensor/actuator level) DP-V0, DP-V1 and DP-V2.
can be networked up to the mid performance range (cell level).
DP-V0 communication functions
Standardization according to IEC 61158/EN 50170 secures your
investments for the future. The DP-V0 master functions consist of "Configuration",
"Parameter Assignment" and "Reading Diagnostics Data",
Using the conformity and interoperability test performed by as well as cyclic reading of input data/actual values and writing
the test laboratories authorized by PROFIBUS & PROFINET output data/setpoints.
International (PI) and the certification of the devices by PI, users
have the security of knowing that the quality and functionality DP-V1 communication functions
is guaranteed, even in multi-vendor installations. The DP-V1 function expansions make it possible to perform
PROFIBUS versions acyclic read and write functions as well as processing cyclic
data communication. This type of device must be supplied with
Two different PROFIBUS versions have been defined in order extensive parameterization data during start-up and during
to comply with the widely varying requirements at field level: normal operation. These acyclically transferred
• PROFIBUS PA (Process Automation) – the version for parameterization data are only rarely changed in comparison to
applications in process automation. PROFIBUS PA uses the the cyclic setpoints, actual values, and measured values, and
intrinsically safe transmission technology specified in are transferred at lower priority in parallel with the cyclic
IEC 61158-2. high-speed user data transfer. Detailed diagnostic information
can be transferred in the same way.
• PROFIBUS DP (Distributed Periphery) – this version, which
is optimized for speed, is specifically tailored to the DP-V2 communication functions
communication of automation systems with distributed I/O
stations and drives. PROFIBUS DP sets itself apart as a result The extended DP-V2 master functions mainly comprise
of very short response times and high noise immunity, and functions for isochronous operation and device-to-device
replaces cost-intensive, parallel signal transfer with 24 V and communication between DP devices.
measured value transfer utilizing 0/4 … 20 mA technology. • Isochronous mode:
Isochronous mode is implemented by means of an equidistant
■ Design signal in the bus system. This cyclic, equidistant cycle is sent
by the DP master to all bus nodes in the form of a Global
Bus participants on PROFIBUS DP Control Telegram. Master and devices can then synchronize
their applications with this signal. The signal jitter between
PROFIBUS DP makes a distinction between two different master cycles is less than 1 s.
classes and one device class:
• Device-to-device communication:
DP master class 1 The "publisher/subscriber" model is used to implement
device-to-device communication. Devices declared as
For PROFIBUS DP, DP master class 1 is the central component. publishers make their input data/actual values and measured
In a defined and continually repeating message cycle the values available to other devices, the subscribers, for reading.
central master station exchanges information with distributed This is performed by sending the response frame to the
stations (DP devices). master as a broadcast. Device-to-device communication is
therefore a cyclic process.

■ Integration
PROFIBUS with SINAMICS
SINAMICS uses the PROFIBUS DP protocol.
SINAMICS drives can only be used as DP devices.

Siemens D 21.3 · 2022 2/23


© Siemens 2022

Highlights

Communication > Industrial Ethernet

■ Overview ■ Integration
Industrial Ethernet with SINAMICS
SINAMICS provides Control Units and Communication Boards
with PROFINET interface based on 100 Mbit/s Ethernet. This

Ethernet
means that process communication in real-time, as well as
2 engineering and HMI via standard TCP/IP are simultaneously
possible.
Industrial
It is also possible to access the web server in SINAMICS at the
same time that process communication is in progress.
Ethernet is the basic internet technology for worldwide
networking. The many possibilities of intranet and internet, which The CU310-2 and CU320-2 Control Units have an additional
have been available for office applications for a long time, Ethernet interface at the front so that service and engineering
are now utilized for production automation with Industrial tasks can be performed very easily.
Ethernet.
Communication with SINAMICS over Industrial Ethernet
Apart from the use of information technology, the deployment
of distributed automation systems is also on the increase. PG/PC/HMI communication
This entails breaking up complex control tasks into smaller, PG/PC/HMI communication is performed using protocols which
manageable and drive-based control systems. This increases are based on the basic TCP/IP protocol.
the demand for communication and consequently • Engineering and diagnostics with STARTER
a comprehensive and powerful communication system.
IT communication
Industrial Ethernet provides a powerful area and cell network for
the industrial field, compliant with the IEEE 802.3 (ETHERNET) IT communication is performed using protocols which are based
standard. on the basic TCP/IP protocol. The most important IT protocols
are:
■ Benefits • HTTP/HTTPS: Hypertext Transfer Protocol (Secure)
Using a standard internet browser, it is possible to retrieve
Ethernet enables a very fast data transfer (10/100 Mbit/s, predefined web pages containing diagnostic information from
1/10 Gbit/s) and at the same time has full-duplex capability. the device. Furthermore, user-defined web pages containing
It therefore provides an ideal basis for communication tasks information defined by the user can be stored in the device.
in the industrial field. With a share of over 90 %, Ethernet is the
number one network worldwide and offers important features • SNMP: Simple Network Management Protocol
which have essential advantages:
• Fast commissioning thanks to the simplest connection method
• High availability since existing networks can be extended
without any adverse effects
• Almost unlimited communication performance because
scalable performance is available through switching
technology and high data rates when required
• Networking of different application areas such as office and
production areas
• Company-wide communication based on WAN (Wide Area
Network) technology or the internet
• Investment protection due to continuous compatibility with
further developments
• Wireless communication using Industrial Wireless LAN
In order to make Ethernet suitable for industrial applications,
considerable expansions with respect to functionality and
design are required:
• Network components for use in harsh industrial environments
• Fast assembly of the RJ45 connectors
• Fail-safety through redundancy
• Expanded diagnostics and message concept
• Use of future-oriented network components (e.g. switches)
SIMATIC NET offers corresponding network components and
products.

2/24 Siemens D 21.3 · 2022


© Siemens 2022

Highlights

Communication > EtherNet/IP

■ Overview
Ethernet Industrial Protocol (EtherNet/IP) is an open standard for
industrial networks. EtherNet/IP is used to transmit cyclic I/O
data and acyclic parameter data. EtherNet/IP was developed by
the ODVA (Open DeviceNet Vendor Association) and belongs
to the international standard series IEC 61158.
2

Communication > Modbus TCP

■ Overview
The Ethernet protocol Modbus TCP is an open standard for
industrial networks. Modbus TCP is used to transmit acyclic
register data. Modbus TCP has been standardized in the
international series of standards IEC 61158 since 2007.

Communication > USS

■ Overview
As a simple fieldbus protocol, USS (Universal Serial Interface
protocol of Siemens AG, 1992) can be used both cyclically and
acyclically. Based on RS485 physical bus characteristics, up to
32 nodes can be networked to one bus segment and connected
to a higher-level controller. This protocol is generally used when
there are limited demands on data throughput.

Siemens D 21.3 · 2022 2/25


© Siemens 2022

Highlights
Technology functions
Basic positioner EPos

■ Overview
Function module basic positioner EPos The EPos basic positioner in the SINAMICS drive system
provides powerful and precise positioning functions. Due to its
The basic positioner EPos is available as a standard technology flexibility and adaptability, the basic positioner can be used for
function for the following SINAMICS Control Units and can be a wide range of positioning tasks.
called as a function module that can be activated additionally.
2 • SINAMICS S120 CU310-2 and CU320-2 Control Units The functions are easy to handle both during commissioning
and during operation, and the comprehensive monitoring
• SINAMICS S110 CU305 Control Units functions are outstanding.
• SINAMICS G120 CU250S-2 Control Units
Many applications can be carried out without external position
• SINAMICS G120D CU250D-2 Control Units controllers.
The basic positioner can be used to resolve basic motion control The EPos basic positioner is used to position linear and rotary
tasks without additional external technological outlay from the axes (modulo) in absolute/relative terms with rotary as well as
drive itself. linear motor encoder or machine encoder (indirect or direct
Integrated functionality for absolute and relative positioning measuring system).
of linear and rotary axes with motor encoders or machine EPos is a function module that can be activated additionally in
encoders. Servo Control and in Vector Control.
User-friendly configuring and commissioning, including control
panel (operation using PC) and diagnostics, are possible with
the STARTER and SINAMICS Startdrive commissioning tools.
In addition to extremely flexible positioning functions, EPos
offers a high degree of user-friendliness and reliability thanks to
integral monitoring and compensation functions.
Different operating modes and their functionality increase
flexibility and plant productivity, for example, by means of
"on-the-fly" and bumpless correction of the motion control.
Preconfigured PROFIdrive positioning frames are available
which, when selected, automatically establish the internal
"connection" to the basic positioner.

2/26 Siemens D 21.3 · 2022


© Siemens 2022

Highlights
Technology functions
Basic positioner EPos

■ Overview
Functionality of the EPos basic positioner Traversing block mode
Lower-level closed-loop position control with the following • 64 traversing blocks for
essential components - SINAMICS S120 CU310-2 and CU320-2 Control Units
• Position actual value sensing (including the lower-level • 16 traversing blocks for
measuring probe evaluation and reference mark search)
• Position controller (including limits, adaptation and pre-control
- SINAMICS S110 CU305 Control Units
- SINAMICS G120 CU250S-2 Control Units 2
- SINAMICS G120D CU250D-2 Control Units
calculation)
• Positioning using traversing blocks that can be stored in the
• Monitoring functions (standstill, positioning and dynamic drive unit including continuation conditions and specific jobs
following error monitoring, cam signals) for a previously homed axis
Mechanical system • Configuring traversing blocks using the traversing block
• Backlash compensation editor in the relevant commissioning tool of the SINAMICS
• Modulo offset converter family
• A traversing block contains the following information:
Limitations - Job number and job (e.g. positioning, waiting, GOTO block
• Speed/acceleration/delay/jerk limitation jump, setting of binary outputs, travel to fixed stop)
• Software limit switches (traversing range limitation by means - Motion parameters (target position, velocity, override
of position setpoint evaluation) for acceleration and deceleration)
- Mode (e.g.: hide block, continuation conditions such as
• Stop cams (traversing range limitation using hardware limit "Continue_with_stop", "Continue_flying" and
switch evaluation) "Continue_externally using high-speed measuring inputs")
Referencing or adjustment - Job parameters (e.g. wait time, block step conditions)
• Set reference point (for an axis at standstill) Direct setpoint specification (MDI) mode
• Search for reference (separate mode including reversing cam • Positioning (absolute, relative) and setting-up (endless
functionality, automatic reversal of direction, homing to "output closed-loop position control) using direct setpoint inputs
cam and encoder zero mark" or only "encoder zero mark" (e.g. via the PLC using process data)
or "external zero mark (BERO)") • It is always possible to influence the motion parameters during
• Flying referencing (seamless referencing possible during traversing (on-the-fly setpoint acceptance) as well as for
"normal" traversing with the aid of the measuring input on-the-fly changes between the setup and positioning modes.
evaluation; generally evaluation, e.g. of a BERO. Subordinate • The direct setpoint specification mode (MDI) can also be used
function for the modes "jog", "direct setpoint input/MDI" and in the relative positioning or setup mode if the axis is not
"traversing blocks") referenced. This means that on-the-fly synchronization and
• Absolute encoder alignment re-referencing can be carried out using "flying referencing".
Jog mode
• Closed-loop position controlled traversing of the axis with
"endless position controlled" or "jog incremental" modes
(traverse through a "step width"), which can be toggled
between

Siemens D 21.3 · 2022 2/27


© Siemens 2022

Highlights
Technology functions
SINAMICS Technology Extensions (SINAMICS TEC)

■ Overview
The SINAMICS Technology Extensions are configurable SERVCOUP is generally released for the following SIMOTICS
functions or Siemens technologies that can be added onto motors:
firmware functions. The extensions are designed to allow • 1FE2 (built-in spindle motor) as a built-in spindle drive for
implementation of highly complex, targeted application-specific machine tools
tasks for various sectors such as test bays, storage and retrieval
2 machines, transportation systems based on linear motors or
multi-winding motors in machine manufacture.
• 1FN3 (linear motor) as milling centers with large rotary tables
for machine tools or portal applications with linear motors
• 1FW4 (torque motor) for servo presses and test stands for high
The SINAMICS Technology Extensions are part of the Advanced performances with superior dynamics
Technology Function and are added to the existing firmware as
self-contained software packages. They are easy to install using • 1FW6 (torque motor) for servo presses
the SINAMICS Startdrive and STARTER commissioning tools • 1FW68 (segment motor) in milling centers with large rotary
and expand the existing device functionality by the application- tables for machine tools
specific functions contained in the software. The software is
parameterized and diagnosed using SINAMICS Startdrive and Fundamentally, operation is possible with the following motors:
STARTER. • Segment motors (axial and radial)
Installing these extended functions customizes the functionality • Direct drives (linear and rotary)
of the SINAMICS S120 converter so that it meets the specific • Double and multi-winding motors (induction and
requirements of the user. synchronous)
SINAMICS Technology Extensions can be used for the following Peak load management of the spindle for overload
drive systems (the way in which they are used depends on the protection of the infeed of machine tools
individual Technology Extension): with SINAMICS Technology Extension DYNEGMA
• SINAMICS G130 The SINAMICS Technology Extension DYNEGMA (Dynamic
• SINAMICS G150 Energy Management) from the Advanced Technology Functions
• SINAMICS S120 is an extension for the infeed and SERVO drive objects of
SINAMICS. The SINAMICS Technology Extensions are also
• SINAMICS S150 known by the name SINAMICS Open Architecture.
• SINAMICS DCM The Technology Extension DYNEGMA is a peak load
• SINAMICS DCP management and overload protection function for machine tool
infeeds. The task of DYNEGMA is to protect the infeed unit
• SINAMICS GM150 during power peaks; these can occur when several drives/
• SINAMICS SM150 spindles simultaneously accelerate or brake, e.g. during tool
• SINAMICS SM120CM change. DYNEGMA only intervenes when actually required in
order to guarantee not only safe and reliable operation, but also
• SINAMICS GL150 maximum dynamic performance. To protect the infeed unit
• SINAMICS SL150 against overload, and in turn resulting machine downtimes or
• SINAMICS GH150 tool, material, or machine damage, when required DYNEGMA
also limits the torque of individual spindles/drives.
• SIMOTION D (SINAMICS Integrated)
• SIMATIC Drive Controller (SINAMICS Integrated) For example, the following applications can be used with
DYNEGMA:
• SINUMERIK 840D sl (SINAMICS Integrated)
• Overload protection of the infeed and peak load management
• SINUMERIK 828D (SINAMICS Integrated) of spindles for milling and turning machines, even during
• SINUMERIK ONE (SINAMICS Integrated) a forced EMERGENCY STOP
The following SINAMICS Technology Extensions are available to • Dynamic tool change for optimal utilization of the maximum
download from the Siemens Industry Online Support website infeed power of machine tools
https://support.industry.siemens.com Vibration extinction for storage and retrieval machines
Simply enter your Article No. in “Search for product information”. with SINAMICS Technology Extension VIBX
Coupling of SERVO Motor Modules The Technology Extension VIBX (Vibration Extinction) is an
with SINAMICS Technology Extension SERVCOUP extension of the SINAMICS drive objects SERVO and VECTOR.
A setpoint filter is implemented in VIBX. The objective of
The Technology Extension SERVCOUP (Servo Coupling) is an the setpoint filter is to change the setpoint of an axis so that there
extension for the SERVO drive object of SINAMICS. is as little vibration as possible caused in the natural frequency
In the SERVO control mode, SERVCOUP allows motors to be range of the moving mechanical components. This function is
operated, which as a result of their size and/or design format, primarily deployed on storage and retrieval machines to
cannot be operated from a single SINAMICS S120 power unit. significantly reduce mast vibrations caused by acceleration and
These motors are subdivided into several drive objects, each of braking. It has been demonstrated that reducing the mast
which can be operated on a Motor Module, and can be coupled vibrations will allow the mast to come to a standstill more quickly
with one another. As a consequence, the individual drive objects and so enable it to handle goods faster.
can be considered as partial motors with their own winding and
terminals. The SINAMICS Technology Extension Vibration Extinction
implemented as setpoint filter can be used both in basic
Irrespective of the number of coupled drive objects, only one positioners (EPos) and Dynamic Servo Controls (DSC) together
encoder is required for the operation of the motor because with a controller in the drive. For this purpose, two modes of
Technology Extension SERVCOUP implements a digital encoder application are supported by the Technology Extension:
splitter in the Control Unit. In this way, the actual encoder values
together with the setpoint specifications are passed on to all • EPos and LR application mode
encoderless drive objects. • DSC application mode

2/28 Siemens D 21.3 · 2022


© Siemens 2022

Highlights
Technology functions
SINAMICS Technology Extensions (SINAMICS TEC)

■ Overview
The filter characteristics can be set using frequency and Signal generator for test bays
damping (attenuation). The filter frequency can be linearly with SINAMICS Technology Extension POLYGON
changed between two limit values via an input during operation.
This means that the filter frequency can be tracked to follow the The Technology Extension POLYGON (Polygonal Line) is an
changing natural frequency of a mechanical system extension of the SINAMICS drive objects SERVO, VECTOR and
(e.g. as a result of different load states) (online frequency
change).
HLA.
The polygonal line application makes it possible to create 2
a master-value-dependent output signal based on a
The following applications can be implemented with VIBX: parameterized characteristic in the current controller sampling
• Sway control for storage and retrieval unit time (or an integer multiple of the current controller sampling
time). The characteristic is defined by up to 10000 equidistantly
• Vibration extinction of positioning applications with distributed interpolation points between which linear
mechanical natural oscillations interpolation is performed. The y values of the interpolation
Engineered DC-DC Converters with Standard Motor Modules points can be taken from an Excel sheet using a script.
with SINAMICS Technology Extension DCDCCONV By interconnecting the output signals to different connector
inputs, it is possible to create various relationships via the
The SINAMICS Technology Extension DCDCCONV (DC-DC characteristic functionality, e.g.:
Converter) is an extension for the booksize and chassis formats • Position-position reference
of SINAMICS S120.
Using Technology Extension DCDCCONV, you can use • Position-speed reference
the booksize or chassis design formats of the Motor Module - • Position-torque reference
which normally control a 3-phase motor - as an engineered
DC/DC converter. Additional components (e.g. energy storage Point-to-point connection between two CUs
reactor or smoothing capacitor) must be connected downstream with SINAMICS Technology Extension OALINK
from the Motor Module. The Technology Extension OALINK (Open Application Link) is
The following applications can be implemented with a SINAMICS extension for the CU320-2 Control Unit.
DCDCCONV: The OALINK enables bidirectional communication between two
Control Units based on DRIVE-CLiQ to facilitate the simple
• Integration of capacitors (Ultracapacitor Modules or exchange of data. In this way, an additional Control Unit can be
electrolytic capacitors) as energy storage for the following integrated as a technology extension for extensive drive-based
applications: technology with SINAMICS Drive Control Chart (DCC).
- Reduction of electrical connected power
- Mains buffering The following applications can be implemented with OALINK:
- Storage for generated energy • Technology extension for the SINAMICS S120 (CU320-2
• Integration of battery modules as energy storage for as replacement for the SIMATIC T400 technology module)
the following applications: • Technology extension for the SINAMICS DCM (CU320-2
- Reduction of electrical connected power as replacement for the SIMATIC T400 technology module)
- Mains buffering
- Storage for generated energy • Load distribution of physically coupled drives
- Provision of a stand-alone network (master/device drive)
- Load on the connected battery modules with defined test • General couplings between SINAMICS DCM and
cycles SINAMICS S120
- Supply of inverters: • General couplings between SINAMICS DCP and
-Supply of a connected inverter with defined voltage level SINAMICS S120
-Test bay for the entire vehicle drive system
• General couplings between SINAMICS DCM and
In addition to the Function Manual, there is also the Application SINAMICS MV
Description for the respectively approved applications in the
SINAMICS Technology Extension DCDCCONV. The Application Fast fault reaction of coupled axes with SINAMICS
Descriptions contain information on the configuration of Technology Extension FASTBRK
SINAMICS S120 Motor Modules together with DCDCCONV in The SINAMICS Technology Extension FASTBRK (Fast Brake
the respective applications. This application description should Reaction for Coupled Axes) is a SINAMICS extension for SERVO
be observed in order to be able to reliably and safely configure drive objects.
the application.
Technology Extension FASTBRK is used on machines with
Application description for DCDCCONV coupled axes, such as gantry axes.
• and the Ultracapacitor Modules is available at: Previously, in cases of a drive-autonomous fault, braking was
https://support.industry.siemens.com/cs/ only applied to the affected axis. The coupled axes were only
document/109748701 braked after the set gantry switch-off limit of the synchronism
• and the battery modules is available at: difference was exceeded, for example.
https://support.industry.siemens.com/cs/ The FASTBRK Technology Extension on the other hand
document/109751796 propagates the original fault reaction to the coupled axes.
This means that in the event of a fault such as an encoder failure
• and supply of inverters is available at: on a drive axis, the same fault reaction (e.g. encoderless
https://support.industry.siemens.com/cs/ braking) is initiated as quickly as possible on all mechanically
document/109771893 coupled axes.
In this way, the Technology Extension FASTBRK enables
coupled drive objects to simultaneously and evenly brake to
a standstill, thus minimizing the risk of damage to the machine.

Siemens D 21.3 · 2022 2/29


© Siemens 2022

Highlights
Technology functions
SINAMICS Technology Extensions (SINAMICS TEC)

■ Overview ■ More information


The following applications can be implemented with FASTBRK: Further SINAMICS Technology Extensions are available for the
• Fast fault reaction in the drive for SINUMERIK axis couplings, following applications:
such as gantry and master/device axes. • Signal generator or operating profiles for test bays with
• Propagation of the axis fault possible with a minimum reaction Technology Extension SETPGEN (Setpoint Generator)

2 time from the current controller cycle (e.g. 125 µs)


• Grouping of up to three groups per Control Unit / NCU / NX
• Fast signal evaluation and processing with Technology
Extension SIVALU (Signal Evaluation)
• Specification of current setpoint and transformation angle with
■ Selection and ordering data Technology Extension EXLOOP (External Loop Controller)
• Rotation detection to determine the speed with Technology
Description Article No. Extension ROTDTEC (Rotation Detection)
SINAMICS Technology Extensions • Detection of chattering during the machining process with
Runtime license per performance unit (of a Control Unit) Technology Extension CHATDTEC (Chatter Detection)
All software products can be downloaded free of charge from • Coupling of linear motors for transportation systems with
Siemens Industry Online Support Technology Extension RAILCTRL (Rail Control)
SINAMICS Technology Extension
SERVCOUP
More information about SINAMICS Technology Extensions is
available on the internet at
Usable with SINAMICS firmware as of
V4.5 HF21
www.siemens.com/sinamics-firmware
• CoL in electronic form 6SL3077-0AA00-8AH0
(Section: Advanced Technology Functions)
SINAMICS Technology Extension
DYNEGMA
Usable with SINAMICS firmware as of
V4.7
• CoL in electronic form 6SL3077-0AA03-0AH0
SINAMICS Technology Extension
VIBX
Usable with SINAMICS firmware as of
V4.4
• CoL in electronic form 6SL3077-0AA00-5AH0
SINAMICS Technology Extension
HEM
Usable with SINAMICS firmware as of
V5.1

In the SINAMICS S120 Cabinet


Modules, Heat Exchanger Modules
are included.
• CoL in electronic form 6SL3077-0AA05-2AH0
SINAMICS Technology Extension
POLYGON
Usable with SINAMICS firmware as of
V4.5
• CoL in electronic form 6SL3077-0AA00-7AH0
SINAMICS Technology Extension
OALINK
Usable with SINAMICS firmware as of
V4.6 HF5
• CoL in electronic form 6SL3077-0AA01-0AH0
SINAMICS Technology Extension
FASTBRK
Usable with SINAMICS firmware as of
V4.5
• CoL in electronic form 6SL3077-0AA01-7AH0
SINAMICS Technology Extension
DCDCCONV
Usable with SINAMICS firmware as of
V5.2 SP3 with DCDCCONV V2.1 or
with SINAMICS firmware as of V4.8
HF4 with DCDCCONV V1.3 SP1
• CoL in electronic form 6SL3077-0AA02-0AH0

2/30 Siemens D 21.3 · 2022


3
© Siemens 2022

SINAMICS S120 Chassis Format Converter Units

3/2 System overview


3/2 Overview
3/4 Function
3/6 Technical specifications

3/7 Air-cooled units


3/7 Technical specifications
3/9 Characteristic curves
3/12 Power Modules
3/16 Basic Line Modules
3/22 Smart Line Modules
3/27 Active Line Modules
3/33 Active Interface Modules
3/39 Motor Modules
3/56 Mounting device for power blocks

3/57 Liquid-cooled units


3/57 Overview
3/58 Technical specifications
3/62 Characteristic curves
3/67 Power Modules
3/71 Basic Line Modules
3/75 Active Line Modules
3/79 Active Interface Modules
3/84 Motor Modules
3/94 Mounting device for liquid-cooled
power units

3/95 Water-cooled units


3/95 Overview
3/96 Technical specifications
3/100 Characteristic curves
3/104 Power Modules
3/108 Active Line Modules
3/112 Active Interface Modules
3/118 Motor Modules
3/131 Mounting device for water-cooled
power units

Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Chassis Format Units

System overview

■ Overview
The Control Unit is plugged onto the Power Module; in addition
to the complete control intelligence, the Control Unit also has all
the drive interfaces for communication with higher-level systems
and interfacing of add-on components.
Line Modules
Line Modules contain the central line infeed for the DC link.
Various Line Modules can be selected to address the various
application profiles:
• Basic Line Modules
• Smart Line Modules
3 • Active Line Modules
Basic Line Modules
Basic Line Modules are designed only for infeed operation,
i.e. they are not capable of recovering energy to the line supply.
If regenerative energy is produced, e.g. when drives brake,
it must be converted into heat using a Braking Module and
With its separate power unit and Control Unit, the SINAMICS a braking resistor.
S120 drive system can be perfectly adapted to a wide variety of A line filter can be optionally installed in order to ensure
different drive tasks. compliance with the limits stipulated for Category C2 in
EN 61800-3.
The Control Unit is selected according to the number of drives to
be controlled and the required performance level, while the
power unit must be rated to meet requirements regarding Switch disconnector Line filter Line Basic Line
regenerative feedback capability or energy exchange. The and fuses or reactor Module
circuit-breaker
connection between the Control Unit and power unit is made
very simply using the DRIVE-CLiQ digital system interface.
...
The following units are available in chassis format:
• Power Modules
Main
• Basic Line Modules contactor
Motor
• Smart Line Modules (only available in the air-cooled version) Module

G_D211_EN_00032a
• Active Line Modules
• Active Interface Modules M
• Motor Modules 3

Power Modules
Smart Line Modules
The simplest version of a SINAMICS S120 drive system
comprises a CU310-2 Control Unit and a Power Module. Smart Line Modules can supply energy and return regenerative
energy to the supply system. A Braking Module and braking
In Power Modules specifically designed for single drives without resistor are required only if the drives need to be decelerated in
regenerative feedback into the line supply, the line-side infeed a controlled manner after a power failure (i.e. when energy
and the motor-side power unit are combined in one unit. cannot be recovered to the supply). For an infeed using a
Smart Line Module, the appropriate line reactor is required.
A line filter can be optionally installed in order to ensure
compliance with the limits stipulated for Category C2 in
EN 61800-3.
DRIVE-CLiQ ~
Control Power
Unit Module Switch Line filter Line Smart Line
~
disconnector and reactor Module
G_D211_XX_00042

fuses

M ...
3~

Generated energy produced during braking is converted to heat Bypass contactor Motor =
G_D213_EN_00033a

in braking resistors. Module

M
3

3/2 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Chassis Format Units

System overview

■ Overview
Active Line Modules Since the Motor Modules share the same DC link, they can
exchange energy with one another, i.e. if one Motor Module
Active Line Modules can supply energy and return regenerative operating in generator mode produces energy, the energy can
energy to the supply system. A Braking Module and braking be used by another Motor Module operating in motor mode. The
resistor are required only if the drives need to be decelerated in DC link is supplied with line supply voltage by a Line Module.
a controlled manner after a power failure (i.e. when energy
cannot be recovered to the supply). Control Units
In contrast to Basic Line Modules and Smart Line Modules, The control intelligence for all the drive axes integrated in the
Active Line Modules generate a controlled DC voltage that is multi-axis group is combined in the Control Units. They also
kept constant despite fluctuations in the line supply voltage if the feature drive-related inputs/outputs and interfaces for
line supply voltage fluctuates within the permitted tolerance communicating with higher-level controllers. Control Units are
range. Active Line Modules in combination with an Active
Interface Module draw a virtually sinusoidal current from the
available with different ranges of functions and with different
performance levels.
3
supply system. Almost no harmonics occur.
System components
The total harmonic distortion factors of the current THD(I) and
voltage THD(U) are typically in the range of approx. 3 % for rated The structure of the drive system is defined by selecting the
current. THD(I) is calculated according to IEEE 519 (2014) and Control Unit and Power Module or Line Module and Motor
THD(U) according to IEC 61000-2-4 (2002). The stringent limit Modules. The additional components provided allow optimum
values of IEEE 519 (2014) are typically complied with. adaptation of the drive system to the application.
All of the components necessary to operate an Active Line These components are subdivided into:
Module are integrated in the Active Interface Module. • Line-side components, e.g. line reactors and line filters
A line filter can be optionally installed in order to ensure • DC link components e.g. Braking Modules and braking
compliance with the limits stipulated for Category C2 in resistors
EN 61800-3.
• Motor-side components, e.g. motor reactors and dv/dt filters
plus VPL, sine-wave filters
Switch disconnector Line filter Active Active Line
and fuses or Interface Module • Supplementary system components, e.g. Terminal
circuit-breaker Module Modules, Operator Panels, and Communication Boards
• Encoder system interface for connecting various encoder
... types to SINAMICS S120
DRIVE-CLiQ – the digital interface between the components
Line  SINAMICS S120 components, including motors and encoders,
contactor Motor are equipped with the high-performance DRIVE-CLiQ system
Module interface.
G_D211_EN_00035c

Line and Motor Modules for example are connected to the


Control Unit – and Terminal Modules and Sensor Modules to the
. drive system via DRIVE-CLiQ – simply and efficiently. Motors that
 also have this interface can be directly connected to the drive
system.
Motor Modules Converter boards (Sensor Modules) for converting standard
A voltage DC link and an inverter for supplying a motor are encoder signals to DRIVE-CLiQ are available for third-party
integrated in the Motor Module. motors or retrofit applications.
The electronic rating plate

Control DRIVE-CLiQ An important digital linkage element of the SINAMICS S120


Unit drive system are the electronic rating plates integrated in every
component. They allow all drive components to be automatically
identified via the DRIVE-CLiQ link.
The electronic rating plate contains all the relevant technical
data about that particular component. In addition to the
~ technical data, the rating plate includes logistical data
(manufacturer ID, article number and ID). Since this data can be
= called up electronically on site or remotely, all the components
used in a machine can always be individually identified, which
Line = Motor = helps simplify servicing.
Module Module
~ ~
G_D211_XX_00043

M M
3~ 3~

Motor Modules are designed for multi-axis drive systems and are
controlled by either a CU320-2 or a SIMOTION D Control Unit.
Motor Modules are interconnected through the DC link.
One or several Motor Modules are supplied with energy for the
motors via the DC link. Both synchronous and induction motors
can be operated.

Siemens D 21.3 · 2022 3/3


© Siemens 2022

SINAMICS S120 Chassis Format Units

System overview

■ Overview ■ Function
Coated modules Communication with higher-level controller and customer
terminal strip
The following devices are equipped as standard with coated
modules: As customer interface to a higher-level control, as standard there
• Blocksize format units is a PROFIBUS or PROFINET communication interface on the
Control Unit CU320-2; there are also expansions such as the
• Booksize format units Terminal Module TM31, the Terminal Board TB30 and modules
• Chassis format units to communicate via CANopen or EtherNet/IP.
• Control Units These interfaces can be used to connect the system to the
• Sensor Modules higher-level controller using analog and digital signals, or to
• Terminal Modules connect additional units.
3 • Advanced Operator Panel (AOP30) For additional information, please refer to the SINAMICS Low
Voltage Engineering Manual.
The coating on the modules protects the sensitive
SMD components against corrosive gases, chemically active Open-loop and closed-loop control functions
dust and moisture. SINAMICS S120 can use a dynamic, high-precision closed-loop
Nickel-plated busbars vector control (drive object type VECTOR), or a highly dynamic
closed-loop servo control (drive object type SERVO).
All of the copper busbars used are nickel-plated in order to
achieve the best possible immunity to environmental effects. Software and protective functions
Furthermore, there is no need to clean the contacts on the The software functions available as standard are described
customer terminals as otherwise required for bare copper below:
connections.
Note:
For some components, parts of the copper busbars cannot be
nickel-plated for technical reasons.
Software and protective Description
functions
Setpoint input The setpoint can be specified both internally and externally; internally as a fixed setpoint, motorized potentiometer setpoint or
jog setpoint, externally via the communications interface or an analog input. The internal fixed setpoint and the motorized
potentiometer setpoint can be switched or adjusted via control commands from any interface.
Motor identification The automatic motor identification function makes commissioning faster and easier and optimizes closed-loop control of the
drive.
Ramp-function generator A user-friendly ramp-function generator with separately adjustable ramp-up and ramp-down times, together with adjustable
rounding times in the lower and upper speed ranges, allows the drive to be smoothly accelerated and braked. This results in
a good speed control response and contributes to the reduction of stress on the mechanical system. The down ramp can be
parameterized separately for a quick stop.
Vdc max controller The Vdc max controller automatically prevents overvoltages in the DC link, if the set down ramp is too short, for example.
This may also extend the set ramp-down time.
Note: This function only makes sense for single-axis applications.
Kinetic buffering (KIP) For brief line supply failures, the kinetic energy of the rotating drive is used to buffer the DC link and therefore prevents fault
trips. The converter remains operational as long as the drive can provide regenerative energy as a result of its motion and
the DC link voltage does not drop below the shutdown threshold. When the line supply recovers within this time, the drive is
again bumplessly accelerated up to its setpoint speed.
Automatic restart The automatic restart switches the drive on again when the power is restored after a power failure, and ramps up to the current
speed setpoint.
Flying restart The flying restart function allows the converter to be switched to a motor that is still turning. With the voltage sensing capability
provided by the optional VSM10, the flying restart time for large induction motors can be significantly reduced because the
motor does not need to be de-magnetized.
Technology controller (PID) Using the technology controller (PID controller) function module, level or flow controls and complex tension controls can be
implemented, for example. The existing D component can act both on the system deviation as well as on the actual value
(factory setting). The P, I, and D components are set separately.
Free function blocks (FFB) Using the freely programmable function blocks, it is easy to implement logic and arithmetic functions for controlling the
SINAMICS drive. The blocks can be programmed at the operator panel or the STARTER commissioning tool.
Drive Control Chart (DCC) Drive Control Chart (DCC) is an additional tool for the easy configuration of technological functions for SINAMICS. The block
library contains a large selection of control, arithmetic and logic blocks as well as extensive open-loop and closed-loop control
functions. The user-friendly DCC editor enables easy graphics-based configuration, allows control loop structures to be clearly
represented and provides a high degree of reusability of charts that have already been created. DCC is an add-on for the
STARTER commissioning tool (see Tools and engineering).
SINAMICS Technology The SINAMICS TEC are configurable functions or Siemens technologies that can be added to extend firmware functions.
Extensions (SINAMICS TEC) These extensions are designed to allow implementation of highly complex, application-specific tasks for various sectors -
such as storage and retrieval machines.
Additional information about Technology Extensions (TEC) is provided in the "Technology functions" section.
I2t sensing for motor A motor model stored in the converter software calculates the motor temperature based on the current speed and load.
protection More exact measurement of the temperature, which also takes into account the influence of the ambient temperature,
is possible by means of direct temperature measurement using Pt100/KTY84 sensors in the motor winding.
Motor temperature evaluation Motor protection by evaluating a KTY84, PTC, Pt100 or Pt1000 temperature sensor. When a KTY84 temperature sensor is
connected, the limit values can be set for alarm or shutdown. When a PTC thermistor is connected, the system reaction to
triggering of the thermistor (alarm or trip) can be defined.
Motor blocking protection A blocked motor is detected and protected against thermal overloading by a fault trip.

3/4 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Chassis Format Units

System overview

■ Overview
Software and protective Description
functions
Brake control "Simple brake control" for control of holding brakes:
The holding brake is used to secure drives against unwanted motion when deactivated.
"Extended brake control" function module for complex brake control, e.g. for motor holding brakes and operational brakes:
When braking with a feedback signal, the brake control reacts to the feedback signal contacts of the brake.
Write protection Write protection to prevent unintentional changing of the setting parameters (without password function).
Know-how protection Know-how protection for encrypting stored data, e.g. to protect configuration know-how, and to protect against changes and
duplication (with password function).
Web server The web server provides information about the drive unit via its web pages. The web server is accessed using a web browser
via unsecured (http) or secured transfer protocol (https).
3
Power unit protection
Power unit protection Description
Ground fault monitoring A ground fault at the output is detected by a total current monitor and results in shutdown in grounded systems.
at the output
Electronic short-circuit A short-circuit at the output (e.g. at the converter output terminals, in the motor cable or in the motor terminal box) is detected
protection at the output and the converter shuts down with a "fault".
Thermal overload protection An alarm is issued first when the overtemperature threshold responds. If the temperature continues to rise, the unit either shuts
down or independently adjusts the pulse frequency or output current so that thermal load is reduced. Once the cause of the
fault has been eliminated (e.g. cooling has been improved), the original operating values are automatically resumed.

Siemens D 21.3 · 2022 3/5


© Siemens 2022

SINAMICS S120 Chassis Format Units

System overview

■ Technical specifications
The most important directives and standards are listed below. These are used as the basis for the SINAMICS S120 built-in units in
chassis format and they must be carefully observed to achieve an EMC-compliant configuration that is safe both functionally and in
operation.
European directives
2014/35/EU Low-voltage Directive:
Directive of the European Parliament and Council of February 26, 2014 for the harmonization of the laws of the member states
relating to the provision of electrical equipment designed for use within certain voltage limits on the market (recast)
2014/30/EU EMC Directive:
Directive of the European Parliament and Council of February 26, 2014 for the harmonization of the laws of the member states
relating to electromagnetic compatibility (recast)

3 2006/42/EC Machinery Directive:


Directive of the European Parliament and Council of May 17, 2006, on machinery and amending Directive 95/16/EC (recast).
2011/65/EU RoHS II Directive:
Directive of the European Parliament and of the Council of 8 June 2011 on the restriction of the use of certain hazardous
substances in electrical and electronic equipment (recast)
European standards
EN ISO 3744 Acoustics – Determination of the sound power level and sound energy level for noise sources that result from sound pressure
measurements – envelope surface procedure of the accuracy class 2 for a largely free sound field over a reflecting plane
EN ISO 13849-1 Safety of machinery – Safety-related parts of control systems;
Part 1: General principles for design (EN ISO 13849-1: 2006) (replaces EN 954-1)
EN 60146-1-1 Semiconductor converters – General requirements and line-commutated converters
Part 1-1: Specification of basic requirements
EN 60204-1 Safety of machinery – Electrical equipment of machines;
Part 1: General requirements
EN 60529 Degrees of protection provided by enclosures (IP code)
IEC 61508-1 Functional safety of electrical/electronic/programmable electronic safety-related systems
Part 1: General requirements
IEC 61508-2 Functional safety of electrical/electronic/programmable electronic safety-related systems
Part 2: Requirements for electrical/electronic/programmable electronic safety-related systems
IEC 61508-3 Functional safety of electrical/electronic/programmable electronic safety-related systems
Part 3: Software requirements
EN 61800-2 Adjustable speed electrical power drive systems
Part 2: General requirements – Rating specifications for low voltage adjustable frequency AC power drive systems
EN 61800-3 Adjustable speed electrical power drive systems
Part 3: EMC requirements and specific test methods
EN 61800-5-1 Adjustable speed electrical power drive systems
Part 5: Safety requirements
Main section 1: Electrical and thermal requirements
EN 61800-5-2 Adjustable speed electrical power drive systems
Part 5-2: Safety requirements – Functional safety (IEC 61800-5-2: 2007)
North American standards
UL 508A Industrial Control Panels
UL 508C Power Conversion Equipment
UL 61800-5-1 Adjustable Speed Electrical Power Drive Systems - Part 5-1: Safety requirements – Electrical, thermal and energy
CSA C22.2 No. 14 Industrial Control Equipment
Certificates of suitability
cULus, cURus Testing by UL (Underwriters Laboratories, www.ul.com) according to UL and CSA standards

3/6 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Chassis Format Units


Air-cooled units

■ Technical specifications
General technical specifications
Unless clearly specified otherwise, the following technical data are valid for all the following components of the air-cooled
SINAMICS S120 drive system in chassis format.
Electrical specifications
Line voltages 380 ... 480 V 3 AC ±10 % (-15 % <1 min)
500 ... 690 V 3 AC ±10 % (-15 % <1 min)
Line supply types Grounded TN/TT systems and non-grounded IT systems
Line frequency 47 ... 63 Hz
Overvoltage category
Electronics power supply
III acc. to EN 61800-5-1
24 V DC, -15 % +20 %
3
implemented as PELV circuit in accordance with EN 61800-5-1
Ground = negative pole grounded via the electronics
Rated short-circuit current
per IEC, in conjunction with the speci-
fied fuses or circuit breakers
• 1.1 ... 447 kW 65 kA
• 448 ... 671 kW 84 kA
• 672 ... 1193 kW 170 kA
• > 1194 kW 200 kA
Rated short-circuit current SCCR
(Short Circuit Current Rating)
according to UL508C (up to 600 V), in
conjunction with the specified fuses or
circuit breakers
• 1.1 ... 447 kW 65 kA
• 448 ... 671 kW 84 kA
• 672 ... 1193 kW 170 kA
• > 1194 kW 200 kA
Control method Vector/Servo control with and without encoder or V/f control
Fixed speeds 15 fixed speeds plus 1 minimum speed, parameterizable
(in the default setting, 3 fixed setpoints plus 1 minimum speed are selectable using terminal strip/PROFIBUS/
PROFINET)
Skippable speed ranges 4, parameterizable
Setpoint resolution 0.001 rpm digital (14 bits + sign)
12 bits analog
Braking operation With Active Line Modules and Smart Line Modules, four-quadrant operation as standard (energy recovery).
With Basic Line Modules, two-quadrant operation as standard, braking by means of an optional braking chopper,
or alternatively by a Motor Module.
Mechanical specifications
Degree of protection IP00 or IP20 depending on type
Protection class I acc. to EN 61800-5-1
Touch protection EN 50274/DGUV regulation 3 when used as intended
Cooling method Forced air cooling AF according to EN 60146

Siemens D 21.3 · 2022 3/7


© Siemens 2022

SINAMICS S120 Chassis Format Units


Air-cooled units

■ Technical specifications
Ambient conditions Storage 1) Transport 1) Operation
Ambient temperature -25 ... +55 °C (-13 ... 131 °F) -25 ... +70 °C (-13 ... +158 °F) Line-side components,
Class 1K4 Class 2K4 Power Modules, Line Modules and
acc. to EN 60721-3-1 (1997) acc. to EN 60721-3-2 (1997) Motor Modules:
0 … 40 °C (32 ... 104 °F) without
derating
Up to 55 °C (131 °F),
see derating data
Control Units, supplementary system
components, and Sensor Modules:
0 ... 55 °C (32 ... 131 °F)
(for operation in a control cabinet)
3 DC link components and motor-side
components:
0 ... 55 °C (32 ... 131 °F)
Relative humidity 5 ... 95 % 5 ... 95 % at 40 °C (104 °F) 5 ... 95 %
Condensation, splashwater, and ice for- Class 1K4 Class 2K3 Class 3K3
mation not permitted (EN 60204, Part 1) acc. to EN 60721-3-1 (1997) acc. to EN 60721-3-2 (1997) acc. to EN 60721-3-3 (2002)
Environmental class/harmful chemi- Class 1C2 Class 2C2 Class 3C2
cal substances acc. to EN 60721-3-1 (1997) acc. to EN 60721-3-2 (1997) acc. to EN 60721-3-3 (2002)
Organic/biological influences Class 1B1 Class 2B1 Class 3B1
acc. to EN 60721-3-1 (1997) acc. to EN 60721-3-2 (1997) acc. to EN 60721-3-3 (2002)
Mechanically active substances Class 1S1 Class 2S1 Class 3S1
acc. to EN 60721-3-1 (1997) acc. to EN 60721-3-2 (1997) acc. to EN 60721-3-3 (2002)
Degree of pollution 2 acc. to EN 61800-5-1
Installation altitude Up to 2000 m (6562 ft) above sea level without derating
> 2000 m (6562 ft) above sea level, see derating data
Mechanical stability Storage 1) Transport 1) Operation
Vibratory load – Class 2M2 Test values
acc. to EN 60721-3-2 (1997) acc. to EN 60068-2-6 test Fc:
• 10 ... 58 Hz with constant deflection
0.075 mm
• 58 ... 150 Hz with constant
acceleration 9.81 m/s2 (1 × g)
Shock load – Class 2M2 Test values
acc. to EN 60721-3-2 (1997) according to EN 60068-2-27 test Ea:
98 m/s2 (10 × g)/20 ms
Compliance with standards
Conformances/certificates of suitabil- CE (EMC Directive No. 2014/30/EU, Low Voltage Directive No. 2014/35/EU, and Machinery Directive 2006/42/EC
ity, according to for functional safety)
RCM, RoHS II, UKCA
cULus (only for devices connected to line supply voltages 380 ... 480 V 3 AC and 500 ... 600 V 3 AC)
Radio interference suppression SINAMICS S120 chassis format units are not designed for connection to the public grid (first environment). Radio
interference suppression is compliant with the EMC product standard for variable-speed drives EN 61800-3, "second
environment" (industrial line supplies). EMC disturbances can occur when connected to the public grid. However, if
additional measures are taken (e.g.  line filter), it can also be operated in the "first environment".

Deviations from the specified class are underlined.

1) In transport packaging.

3/8 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Chassis Format Units


Air-cooled units

■ Characteristic curves
Derating data, chassis format current, whereby ambient temperatures lower than 40 °C may
be offset to compensate.
Air-cooled SINAMICS G120 chassis format units and the
associated system components are rated for an ambient The following table lists the permissible output currents
temperature of 40 °C and installation altitudes up to 2000 m depending on the installation altitude and ambient temperature.
above sea level. The specified values already include a permitted compensation
in respect of installation altitude and ambient temperatures
At ambient temperatures > 40 °C, the output current must be < 40 °C (temperature at the air intake of the built-in unit).
reduced. Ambient temperatures above 55 °C are not
permissible. The values apply under the precondition that a cooling air flow
through the devices is guaranteed as specified in the technical
At installation altitudes > 2000 m above sea level, it must be specifications.
taken into account that the air pressure, and therefore air density,
decreases as the height increases. As a consequence, the As additional measure for installation altitudes from 2000 m up 3
cooling efficiency and the insulation capacity of the air also to 5000 m, an isolating transformer is required in order to reduce
decrease. transient overvoltages according to EN 60664-1.
For additional information, please refer to the SINAMICS Low
Due to the reduced cooling efficiency, it is necessary, on the one Voltage Engineering Manual.
hand, to reduce the ambient temperature and on the other hand,
to reduce the heat loss in the built-in unit by reducing the output
Current-derating factors for SINAMICS S120 chassis units as a function of the ambient/air intake temperature and the installation altitude
Installation altitude Current derating factor (as a percentage of the rated current)
above sea level for an ambient/air intake temperature of
m (ft) 20 °C (68 °F) 25 °C (77 °F) 30 °C (86 °F) 35 °C (95 °F) 40 °C (104 °F) 45 °C (113 °F) 50 °C (122 °F) 55 °C (131 °F)
0 ... 2000 93,3 % 86,7 % 80 %
(0 ... 6562)
2001 ... 2500 96,3 %
(6565 ... 8202)
2501 ... 3000 100 % 98,7 %
(8205 ... 9843)
3001 ... 3500
(9846 ... 11483)
3501 ... 4000 96,3 %
(11486 ... 13123)
4001 ... 4500 97,5 %
(13127 ... 14764)
4501 ... 5000 98,2 %
(14767 ... 16404)

Current derating for Power Modules and Motor Modules in For additional information, please refer to the SINAMICS Low
chassis format as a function of the pulse frequency Voltage Engineering Manual.
To reduce motor noise or to increase output frequency, the pulse The following table lists the rated output currents of the
frequency can be increased relative to the factory setting SINAMICS S120 Power Modules and Motor Modules with pulse
(1.25 kHz or 2 kHz). When the pulse frequency is increased, the frequency set in the factory as well as the current derating
derating factor of the output current must be taken into account. factors (permissible output currents referred to the rated output
This derating factor must be applied to the currents specified in current) for higher pulse frequencies.
the technical specifications.
Derating factor of the output current as a function of the pulse frequency for units with a rated pulse frequency of 2 kHz
Power Module Type rating Output current Derating factor
Motor Module at 400 V at 2 kHz at pulse frequency
6SL3310-... kW A 2.5 kHz 4 kHz 5 kHz 7.5 kHz 8 kHz
6SL3320-...
380 ... 480 V 3 AC
1TE32-1AA3 110 210 95 % 82 % 74 % 54 % 50 %
1TE32-6AA3 132 260 95 % 83 % 74 % 54 % 50 %
1TE33-1AA3 160 310 97 % 88 % 78 % 54 % 50 %
1TE33-8AA3 200 380 96 % 87 % 77 % 54 % 50 %
1TE35-0AA3 250 490 94 % 78 % 71 % 53 % 50 %
1TE41-4AS3 800 1330 88 % 55 % - - -

Siemens D 21.3 · 2022 3/9


© Siemens 2022

SINAMICS S120 Chassis Format Units


Air-cooled units

■ Characteristic curves
Derating factor of the output current as a function of the pulse frequency for units with a rated pulse frequency of 1.25 kHz
Motor Module Type rating Output current Derating factor
at 400 V or 690 V at 1.25 kHz at pulse frequency
6SL3320-... kW A 2 kHz 2.5 kHz 4 kHz 5 kHz 7.5 kHz 8 kHz
380 ... 480 V 3 AC
1TE36-1AA3 315 605 83 % 72 % 64 % 60 % 40 % 36%
1TE37-5AA3 400 745 83 % 72 % 64 % 60 % 40 % 36%
1TE38-4AA3 450 840 87 % 79 % 64 % 55 % 40 % 37 %
1TE41-0AA3 560 985 92 % 87 % 70 % 60 % 50 % 47 %
3 1TE41-2AA3 710 1260 92 % 87 % 70 % 60 % 50 % 47 %
1TE41-4AA3 800 1405 97 % 95 % 74 % 60 % 50 % 47 %
500 ... 690 V 3 AC
1TG28-5AA3 75 85 93 % 89 % 71 % 60 % 40 % -
1TG31-0AA3 90 100 92 % 88 % 71 % 60 % 40 % -
1TG31-2AA3 110 120 92 % 88 % 71 % 60 % 40 % -
1TG31-5AA3 132 150 90 % 84 % 66 % 55 % 35 % -
1TG31-8AA3 160 175 92 % 87 % 70 % 60 % 40 % -
1TG32-2AA3 200 215 92 % 87 % 70 % 60 % 40 % -
1TG32-6AA3 250 260 92 % 88 % 71 % 60 % 40 % -
1TG33-3AA3 315 330 89 % 82 % 65 % 55 % 40 % -
1TG34-1AA3 400 410 89 % 82 % 65 % 55 % 35 % -
1TG34-7AA3 450 465 92 % 87 % 67 % 55 % 35 % -
1TG35-8AA3 560 575 91 % 85 % 64 % 50 % 35 % -
1TG37-4AA3 710 735 87 % 79 % 64 % 55 % 35 % -
1TG38-1AA3 800 810 97 % 95 % 71 % 55 % 35 % -
1TG38-8AA3 900 910 92 % 87 % 67 % 55 % 33 % -
1TG41-0AA3 1000 1025 91 % 86 % 64 % 50 % 30 % -
1TG41-3AA3 1200 1270 87 % 79 % 55 % 40 % 25 % -

Maximum output frequencies achieved by increasing the pulse frequency


The adjustable pulse frequencies – and therefore the output
frequencies that can be achieved with the factory-set current
controller clock cycles – are listed below.
Current controller clock cycle Adjustable pulse frequency Max. achievable output frequency fA
TI fp
V/f mode Vector mode Servo mode
250 µs 1) 2 kHz 166 Hz 166 Hz 333 Hz
4 kHz 333 Hz 333 Hz 550 Hz 3)
8 kHz 550 Hz 3) 480 Hz 550 Hz 3)
2)
400 µs 1.25 kHz 104 Hz 104 Hz –
2.5 kHz 208 Hz 208 Hz –
5.0 kHz 416 Hz 300 Hz –
7.5 kHz 550 Hz 3) 300 Hz –

1) As factory setting, the following devices have a current controller clock 3) With the "High output frequencies" license, which can be ordered as option
cycle of 250 µs - and a pulse frequency of 2 kHz: J01 on the CompactFlash card for SINAMICS S120, the maximum output
- 3 AC 380 ... 480 V: 250 kW / 490 A, 6SL3320-1TE41-4AS3 frequency is increased up to 650 Hz.
2) As factory setting, the following devices have a current controller clock For more information, see
cycle of 400 µs and a pulse frequency of 1.25 kHz: https://support.industry.siemens.com/cs/document/104020669
- 380 ... 480 V 3 AC: 315 kW / 605 A, except 6SL3320-1TE41-4AS3,
- 500 ... 690 V 3 AC: All power ratings

3/10 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Chassis Format Units


Air-cooled units

■ Characteristic curves
Overload capability Line Modules
SINAMICS S120 built-in units have an overload reserve, e.g. to The base-load current for a high overload IH DC is the basis for
handle breakaway torques. If larger surge loads occur, this must a duty cycle of 150 % for 60 s or Imax DC for 5 s.
be taken into account in the configuration. For drives with
overload requirements, the appropriate base load current must,
Converter current
therefore, be used as a basis for the required load.
5s
The permissible overload levels are valid under the prerequisite
Imax DC Short-time current Imax
that the drive units are operated with their base-load current
before and after the overload condition based on a duty cycle 1.5 x IH DC Short-time current 150 %
duration of 300 s.
Another precondition is that the Power Modules or the Motor
Modules are operated at their factory-set pulse frequency at
Rated current (continuous) 3
Base-load current IH DC
output frequencies > 10 Hz. for high overload
For temporary, periodic duty cycles with high variations of load IN DC
within the duty cycle, the relevant sections of the SINAMICS Low
IH DC

G_D213_EN_00079
Voltage Engineering Manual must be observed.
60 s
Power Modules and Motor Modules 300 s
The base load current for a low overload IL is based on a duty
cycle of 110 % for 60 s or 150 % for 10 s.
t

Converter current
High overload
10 s
1.5 x IL

Short-time current 150 %

Short-time current 110 %


Rated current (continuous)
Base-load current IL
1.1 x IL
for low overload
IN
IL
G_D213_EN_00035

60 s
300 s

Low overload
The base load current for a high overload IH is based on a duty
cycle of 150 % for 60 s or 160 % for 10 s.

Converter current
10 s
1.6 x IH Short-time current 160 %
1.5 x IH Short-time current 150 %

Rated current (continuous)

Base-load current IH for high overload


IN

IH
G_D213_EN_00036

60 s
300 s

High overload

Siemens D 21.3 · 2022 3/11


© Siemens 2022

SINAMICS S120 Chassis Format Units


Air-cooled units
Power Modules

■ Overview Application in multi-axis systems


Power Modules in chassis format can also be connected directly
via DRIVE-CLiQ to a separate CU320-2 or SIMOTION D4x5-2
Control Unit or Controller Extension CX32-2. The appropriate
DRIVE-CLiQ cable for the required distance must be ordered
(see section MOTION-CONNECT connection systems).

■ Selection and ordering data


Type rating Rated output current Power Module
at 400 V
kW A Article No.

3 Line voltage 380 ... 480 V 3 AC


110 210 6SL3310-1TE32-1AA3
132 260 6SL3310-1TE32-6AA3
160 310 6SL3310-1TE33-1AA3
200 380 6SL3310-1TE33-8AA3
250 490 6SL3310-1TE35-0AA3
The Power Module comprises a line rectifier, a DC link and an Extended liability for defects
inverter to supply the motor.
Siemens offers for SINAMICS S120 chassis units an extended
Power Modules are designed for drives that are not capable of liability for defects/Service Protect up to 6½ years.
regenerating energy to the mains supply. Regenerative energy
produced while braking is converted to heat using braking Details can be found in chapter
resistors. Services and Documentation
Power Modules in the chassis format can be connected to Accessories for re-ordering
grounded TN/TT systems and non-grounded IT systems.
Description Article No.

■ Design Dust protection blanking plugs


(50 units)
6SL3066-4CA00-0AA0

The Power Modules have the following interfaces as standard: For DRIVE-CLiQ port

• 1 line supply connection For line and motor-side components, Braking Modules as well as
• 1 motor connection recommended line-side system components, see System
components.
• 1 connection for the 24 V DC electronics power supply
• 1 DC link connection (DCPA, DCNA) for connecting a Braking
Module
• 1 DC link connection (DCPS, DCNS) for connecting
a dv/dt filter
• 3 DRIVE-CLiQ sockets
• 1 temperature sensor input for KTY84-130, Pt1000,
PTC or Pt100 (Pt1000 can be used from firmware V4.7 HF17
and higher)
• 1 connection for Safe Brake Adapter
• 1 connection for Safety Integrated
• 2 PE/protective conductor connections
The Power Modules are controlled by the CU310-2 Control Unit
that can be integrated into the Power Module.
The status of the Power Modules is indicated via three LEDs.
The scope of supply of the Power Modules includes:
• 1 DRIVE-CLiQ cable for connection to the CU310-2
Control Unit
• 1 connecting cable 24 V DC for power supply to the CU310-2
Control Unit
• 1 mounting plate for attaching the CU310-2 Control Unit
• 1 set of warning labels in 30 languages
(BG, CN, CZ, DE, DK, EE, ES, FI, FR, GB, GR, HU, IE, IS, IT,
JP, KR, LT, LV, MT, NL, NO, PL, PT, RO, RU, SE, SI, SK, TR)

3/12 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Chassis Format Units


Air-cooled units
Power Modules

■ Integration
The Power Modules communicate with the higher-level control module via DRIVE-CLiQ. The Control Unit in this case could be
a CU310-2, CU320-2 or a SIMOTION D Control Unit.

380 to 480 V 3 AC
L1L2L3 PE
230 V 1 AC

Line reactor
3

W1
PE
U1
V1
Power Module M
1~
chassis
format Option
Braking
module
-X9
1 P24_1 = R1
24 V 2 M_1 Braking
= DCPA R2
DC 3 resistor
4 Contactor
DCNA
5 control
6
EP +24 V 7
EP M1 8
+ 1) -X42 1 DCPS
READY
LEDs

+
M 4 DC LINK DCNS
M
POWER OK

Control Unit X400


DRIVE-CLiQ socket 0

X401 DRIVE-CLiQ socket 1

X402
DRIVE-CLiQ socket 2

-X46
1 BR output+
2 BR output-
3 FB input+
4 FB input- IPD card
Microprocessor
-X41
4 +Temp
3 -Temp
2
1
W2
PE
U2

G_D211_EN_00254b
V2

DRIVE-CLiQ
1) 24 V supply cable to power a CU310-2 or D410-2 M
E
Control Unit built into the Power Module 3 ~

Connection example of a Power Module


Note:
The integrated 24 V power supply at connector X42 can have
a maximum load of 2 A. When the Control Unit is supplied from
the integrated power supply, the total load of the digital outputs
must be carefully observed to ensure that the 2 A is not
exceeded.

Siemens D 21.3 · 2022 3/13


© Siemens 2022

SINAMICS S120 Chassis Format Units


Air-cooled units
Power Modules

■ Technical specifications
General technical specifications
Electrical specifications
Line connection voltage 380 ... 480 V 3 AC ±10 % (-15 % <1 min)
Up to 2000 m (6562 ft) above sea level
Line power factor
for a 3 AC line supply voltage and out-
put power
• Basic fundamental (cos 1) >0.96
• Total () 0.75 ... 0.93
DC link voltage, approx. 1) 1.35 × line voltage
3 Output voltage, approx. 0.97 x Uline
Output frequency 2)
• Control mode Servo 0 ... 550 Hz
• Control mode Vector 0 ... 550 Hz
• Control mode V/f 0 ... 550 Hz
Main contactor control
• Terminal strip -X9/5-6 240 V AC, max. 8 A
30 V DC, max. 1 A
Safety Integrated Safety Integrity Level 2 (SIL2) acc. to IEC 61508, Performance Level d (PLd) acc. to EN ISO 13849-1 and Control
Category 3 acc. to EN ISO 13849-1.

1) The DC link voltage is unregulated and load-dependent.


For additional information, please refer to the SINAMICS Low Voltage
Engineering Manual.
2) Please note:
• Note the correlation between max. output frequency, pulse frequency and
current derating. Higher output frequencies on request For more
information, see
https://support.industry.siemens.com/cs/document/104020669
• The correlation between the minimum output frequency and permissible
output current (current derating).
For additional information, please refer to the SINAMICS Low Voltage
Engineering Manual.

3/14 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Chassis Format Units


Air-cooled units
Power Modules

■ Technical specifications
Line voltage 380 ... 480 V 3 AC Power Modules
6SL3310- 6SL3310- 6SL3310- 6SL3310- 6SL3310-
1TE32-1AA3 1TE32-6AA3 1TE33-1AA3 1TE33-8AA3 1TE35-0AA3
Type rating
• At IL (50 Hz 400 V) 1) kW 110 132 160 200 250
• At IH (50 Hz 400 V) 1) kW 90 110 132 160 200
• At IL (60 Hz 460 V) 2) hp 150 200 250 300 400
• At IH (60 Hz 460 V) 2) hp 150 200 200 250 350
Output current
• Rated current IN O A 210 260 310 380 490
• Base-load current IL3)
• Base-load current IH4)
A
A
205
178
250
233
302
277
370
340
477
438
3
• Maximum current Imax O A 307 375 453 555 715
Input current
• Rated current IN I A 229 284 338 395 509
• Maximum current Imax I A 335 410 495 606 781
Current demand
• 24 V DC auxiliary power supply A 0.8 0.8 0.9 0.9 0.9
Pulse frequency 5)
• Rated frequency kHz 2 2 2 2 2
• Pulse frequency, max.
- Without current derating kHz 2 2 2 2 2
- With current derating kHz 8 8 8 8 8
Power loss, max. 6)
• At 50 Hz 400 V kW 2.46 3.27 4 4.54 5.78
• At 60 Hz 460 V kW 2.54 3.36 4.07 4.67 5.96
Cooling air requirement m3/s (ft3/s) 0.17 (6.00) 0.23 (8.12) 0.36 (12.7) 0.36 (12.7) 0.36 (12.7)
Sound pressure level LpA dB 64/67 71/71 69/73 69/73 69/73
(1 m) at 50/60 Hz
Line connection M10 screw M10 screw M10 screw M10 screw M10 screw
U1, V1, W1
• Conductor cross-section, max. (IEC) mm2 2 × 185 2 × 185 2 × 240 2 × 240 2 × 240
Motor connection M10 screw M10 screw M10 screw M10 screw M10 screw
U2/T1, V2/T2, W2/T3
• Conductor cross-section, max. (IEC) mm2 2 × 185 2 × 185 2 × 240 2 × 240 2 × 240
Cable length, max. 7)
• Shielded m (ft) 300 (984) 300 (984) 300 (984) 300 (984) 300 (984)
• Unshielded m (ft) 450 (1476) 450 (1476) 450 (1476) 450 (1476) 450 (1476)
PE1/GND connection M10 screw M10 screw M10 screw M10 screw M10 screw
• Conductor cross-section, max. (IEC) mm2 2 × 185 2 × 185 2 × 240 2 × 240 2 × 240
PE2/GND connection M10 screw M10 screw M10 screw M10 screw M10 screw
• Conductor cross-section, max. (IEC) mm2 2 × 185 2 × 185 2 × 240 2 × 240 2 × 240
Degree of protection IP20 IP20 IP20 IP20 IP20
Dimensions
• Width mm (in) 326 (12.8) 326 (12.8) 326 (12.8) 326 (12.8) 326 (12.8)
• Height mm (in) 1400 (55.1) 1400 (55.1) 1533 (60.4) 1533 (60.4) 1533 (60.4)
• Depth mm (in) 356 (14.0) 8) 356 (14.0) 8) 549 (21.6) 549 (21.6) 549 (21.6)
Weight, approx. kg (lb) 104 (229) 104 (229) 162 (357) 162 (357) 162 (357)
Frame size FX FX GX GX GX
Minimum short-circuit current 9) kA 3 3.6 4.4 4.4 8

1) 6)
Rated power of a typical 6-pole standard induction motor based on IL or IH The specified power loss represents the maximum value at 100 %
for 400 V 3 AC 50 Hz. utilization. The value is lower under normal operating conditions.
2) 7)
Rated power of a typical 6-pole standard induction motor based on IL or IH Longer cable lengths for specific configurations are available on request.
for 460 V 3 AC 60 Hz. For additional information, please refer to the SINAMICS Low Voltage
3)
The base-load current IL is based on a load cycle of 110 % for 60 s or Engineering Manual.
8)
150 % for 10 s with a load cycle duration of 300 s. Depth = 421 mm (16.6 in) including front cover when CU310-2 Control Unit
4)
The base-load current IH is based on a duty cycle of 150 % for 60 s or is installed.
9)
160 % for 10 s with a duty cycle duration of 300 s. Current required for reliably triggering protective devices.
5)
Information regarding the correlation between the pulse frequency and
maximum output current/output frequency is provided in the SINAMICS
Low Voltage Engineering Manual

Siemens D 21.3 · 2022 3/15


© Siemens 2022

SINAMICS S120 Chassis Format Units


Air-cooled units
Basic Line Modules

■ Overview The scope of supply of the Basic Line Modules includes:


• DRIVE-CLiQ cable to connect to a Control Unit
• DRIVE-CLiQ cable to connect the Control Unit to the first Motor
Module
• 1 set of warning labels in 30 languages
(BG, CN, CZ, DE, DK, EE, ES, FI, FR, GB, GR, HU, IE, IS, IT,
JP, KR, LT, LV, MT, NL, NO, PL, PT, RO, RU, SE, SI, SK, TR)
Pre-charging circuit for the Basic Line Modules, frame size GD
Unlike Basic Line Modules in frame sizes FB and GB, a Basic
Line Module in frame size GD requires a separate precharging
circuit. The pre-charging circuit components must be ordered
3 separately.
During startup, the pre-charging circuit ensures that the DC link
capacitors of the Basic Line Module and the connected
Motor Modules are pre-charged with current limiting. After pre-
charging has been completed, the circuit breaker is closed and
the pre-charging circuit bypassed; the Basic Line Module is then
directly connected to the line supply.

Basic Line Modules are available for applications in which no The pre-charging circuit comprises a pre-charging contactor
energy is returned to the supply or where the energy exchange and pre-charging resistors; the circuit must be protected against
between motor and generator axes takes place in the DC link. overcurrent using suitable protection measures. To increase the
Basic Line Modules are designed for connection to grounded permissible DC link capacitance, the pre-charging resistors can
TN/TT and non-grounded IT supply systems. also be connected in parallel in each phase.

The Basic Line Modules are available in different frame sizes. More information on the pre-charging circuit is to be found in the
With frame sizes FB and GB, a fully controlled thyristor bridge is SINAMICS Low Voltage Engineering Manual.
used to pre-charge the Basic Line Modules and connected For components for the pre-charging circuit and for
Motor Modules. The thyristors normally operate with a trigger recommended line-side system components, see System
delay angle of 0°. components.
Basic Line Modules, frame size GD for 900 kW (400 V) or
1500 kW (690 V) include a diode bridge, and the DC link is ■ Selection and ordering data
pre-charged via a separate line-side pre-charging circuit.
Rated power Rated infeed current Basic Line Module
A Braking Module of the appropriate frame size can be at 400 V or 690 V
integrated into a Basic Line Module in order to permit, in con-
kW A Article No.
junction with an external braking resistor, regenerative operation
of the drive system (see section System components  Line voltage 380 ... 480 V 3 AC
DC link components). 200 365 6SL3330-1TE34-2AA3

■ Design 250
400
460
710
6SL3330-1TE35-3AA3
6SL3330-1TE38-2AA3
The Basic Line Modules have the following interfaces as stan- 560 1010 6SL3330-1TE41-2AA3
dard:
710 1265 6SL3330-1TE41-5AA3
• 1 line supply connection
900 1630 6SL3330-1TE41-8AA3
• 1 connection for the 24 V DC electronics power supply
Line voltage 500 ... 690 V 3 AC
• 1 DC link connection (DCP, DCN) for supplying the connected
Motor Modules 250 260 6SL3330-1TG33-0AA3
• 1 DC link connection (DCPA, DCNA) for connecting a Braking 355 375 6SL3330-1TG34-3AA3
Module 560 575 6SL3330-1TG36-8AA3
• 3 DRIVE-CLiQ sockets 900 925 6SL3330-1TG41-1AA3
• 1 temperature sensor input for KTY84-130, Pt1000 or PTC 1100 1180 6SL3330-1TG41-4AA3
(Pt1000 can be used from firmware V4.7 HF17 and higher)
1500 1580 6SL3330-1TG41-8AA3
• 1 PE/protective conductor connection
Extended liability for defects
The status of the Basic Line Modules is indicated via three LEDs.
Siemens offers for SINAMICS S120 chassis units an extended
liability for defects/Service Protect up to 6½ years.
Details can be found in chapter
Services and Documentation
Accessories for re-ordering

Description Article No.


Dust protection blanking plugs 6SL3066-4CA00-0AA0
(50 units)
For DRIVE-CLiQ port

For line-side components and recommended line-side system


components, see System components.

3/16 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Chassis Format Units


Air-cooled units
Basic Line Modules

■ Integration
The Basic Line Modules communicate with the higher-level control module via DRIVE-CLiQ. The control module in this case can be
a CU320-2 or a SIMOTION D Control Unit. An external 24 V DC power supply is required to operate Basic Line Modules.

X400 X401 X402

2
0
L1
L2

DRIVE-CLiQ socket

DRIVE-CLiQ socket

DRIVE-CLiQ socket
L3
Basic Line
Module
chassis 3
Main switch format
-X9
1 P24 V =
External
24 V DC 2 M
=
3
4 Internal
power supply
5
Main contactor
6 control

-X41 ~ DCP
Main contactor 4 DC link
+Temp = DCN
3 -Temp DCPA Connection for
Line filter 2
EP +24 V -F10 DCNA Braking Module
1
EP M1

-X42 -F11 Fan


1 internal
P24L
2
Line reactor P24L
3 M READY
LEDs

4
M
DC LINK
POWER OK

IPD card

-X1
W1

G_D213_EN_00082b
PE
U1
V1

Connection example for Basic Line Module, frame sizes FB, GB

Siemens D 21.3 · 2022 3/17


© Siemens 2022

SINAMICS S120 Chassis Format Units


Air-cooled units
Basic Line Modules

■ Integration
X400 X401 X402

2
0
L1
L2

DRIVE-CLiQ socket

DRIVE-CLiQ socket

DRIVE-CLiQ socket
L3
Basic Line
Module
chassis
Fuses
format
3 -X9
Internal
power supply
1 P24 V
External
24 V DC 2 M
3
230 V 1 AC Main contactor
4 control =
Circuit breaker
5
Control of =
6 pre-charging contactor DC link
N
~ DCP
Pre-charging = DCN
contactor DCPA
N -F10 DCNA
Connection for
Pre-charging Braking Module
resistors -F11 Fan
Internal

LEDs READY
-X41
4 DC LINK
+Temp
Line filter 3 -Temp
2 POWER OK
EP +24 V
1
EP M1
IPD card
-X42
1 P24L
Line reactor 2
P24L
3 M
4
M
-X1
W1

G_D213_EN_00096a
PE
U1
V1

Connection example, Basic Line Module, frame size GD

3/18 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Chassis Format Units


Air-cooled units
Basic Line Modules

■ Technical specifications
General technical specifications
Electrical specifications
Line power factor
at rated power
• Basic fundamental (cos 1) >0.96
• Total () 0.75 ... 0.93
Efficiency >99 %
DC link voltage, approx. 1) 1.35 × line voltage under partial load
1.32 × line voltage under full load
Main contactor control
• Terminal strip -X9/5-6 240 V AC, max. 8 A 3
30 V DC, max. 1 A

1)
The DC link voltage is unregulated and load-dependent.
For additional information, please refer to the SINAMICS Low Voltage
Engineering Manual.

Siemens D 21.3 · 2022 3/19


© Siemens 2022

SINAMICS S120 Chassis Format Units


Air-cooled units
Basic Line Modules

■ Technical specifications
Line voltage 380 ... 480 V 3 AC Basic Line Modules
6SL3330- 6SL3330- 6SL3330- 6SL3330- 6SL3330- 6SL3330-
1TE34-2AA3 1TE35-3AA3 1TE38-2AA3 1TE41-2AA3 1TE41-5AA3 1TE41-8AA3
Rated power
• At IN DC (50 Hz 400 V) kW 200 250 400 560 710 900
• At IH DC (50 Hz 400 V) kW 160 200 315 450 560 705
• At IN DC (60 Hz 460 V) hp 305 385 615 860 1090 1390
• At IH DC (60 Hz 460 V) hp 245 305 485 690 860 1090
DC link current
• Rated current IN DC A 420 530 820 1200 1500 1880
3 • Base-load current IH DC 1)
• Maximum current Imax DC
A
A
328
630
413
795
640
1230
936
1800
1170
2250
1467
2820
Input current
• Rated current IN I A 365 460 710 1010 1265 1630
• Maximum current Imax I A 547 690 1065 1515 1897 2380
• Max. pre-charging current (max. 3 s) A Internal Internal Internal Internal Internal 308
Current demand
• 24 V DC auxiliary power supply A 1.1 1.1 1.1 1.1 1.1 1.1
DC link capacitance
• Basic Line Module F 7200 9600 14600 23200 29000 34800
• Drive line-up, max. F 57600 76800 116800 185600 232000 139200/2784002)
Power loss, max. 3)
• At 50 Hz 400 V kW 1.9 2.1 3.2 4.6 5.5 6.9
• At 60 Hz 460 V kW 1.9 2.1 3.2 4.6 5.5 6.9
Cooling air requirement m3/s (ft3/s) 0.17 (6.00) 0.17 (6.00) 0.17 (6.00) 0.36 (12.7) 0.36 (12.7) 0.36 (12.7)
Sound pressure level LpA dB 66/68 66/68 66/68 71/73 71/73 71/73
(1 m) at 50/60 Hz
Line connection Flat connector Flat connector Flat connector Flat connector Flat connector Flat connector
U1, V1, W1 for M10 screw for M10 screw for M10 screw for M12 screw for M12 screw for M12 screw
• Conductor cross-section, max. (IEC) mm2 2 × 240 2 × 240 2 × 240 6 × 185 6 × 185 6 × 185
DC link connection M10 screw M10 screw M10 screw 3 × hole for M12 3 × hole for M12 3 × hole for M12
DCP, DCN
• Conductor cross-section, max. (IEC) mm2 2 × 240 2 × 240 2 × 240 6 × 185 6 × 185 6 × 185
PE/GND connection 2 × hole for M10 2 × hole for M10 2 × hole for M10 2 × hole for M12 2 × hole for M12 2 × hole for M12
• Conductor cross-section, max. (IEC) mm2 2 × 240 2 × 240 2 × 240 4 × 240 4 × 240 4 × 240
Cable length, max. 4)
• Shielded m (ft) 2600 (8530) 2600 (8530) 2600 (8530) 4000 (13123) 4000 (13123) 4800 (15748)
• Unshielded m (ft) 3900 (12795) 3900 (12795) 3900 (12795) 6000 (19685) 6000 (19685) 7200 (23622)
Degree of protection IP00 IP00 IP00 IP00 IP00 IP00
Dimensions
• Width mm (in) 310 (12.2) 310 (12.2) 310 (12.2) 310 (12.2) 310 (12.2) 310 (12.2)
• Height mm (in) 1164 (45.8) 1164 (45.8) 1164 (45.8) 1653 (65.1) 1653 (65.1) 1653 (65.1)
• Depth mm (in) 352 (13.9) 352 (13.9) 352 (13.9) 550 (21.7) 550 (21.7) 550 (21.7)
Weight, approx. kg (lb) 96 (212) 96 (212) 96 (212) 214 (472) 214 (472) 214 (472)
Frame size FB FB FB GB GB GD
Minimum short-circuit current 5) kA 4.4 5.2 10 12.4 18.4 18.6

1) 4)
The base-load current IH DC is the basis for a duty cycle of 150 % for 60 s or Total of all motor cables and DC link. Longer cable lengths for specific
Imax DC for 5 s with a duty cycle duration of 300 s. configurations are available on request.
2)
The first value applies for one precharging resistor for each phase, For additional information, please refer to the SINAMICS Low Voltage
the second value for two precharging resistors connected in parallel for Engineering Manual.
5)
each phase. Current required for reliably triggering protective devices.
3)
The specified power loss represents the maximum value at 100 %
utilization. The value is lower under normal operating conditions.

3/20 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Chassis Format Units


Air-cooled units
Basic Line Modules

■ Technical specifications
Line voltage 500 ... 690 V 3 AC Basic Line Modules
6SL3330- 6SL3330- 6SL3330- 6SL3330- 6SL3330- 6SL3330-
1TG33-0AA3 1TG34-3AA3 1TG36-8AA3 1TG41-1AA3 1TG41-4AA3 1TG41-8AA3
Rated power
• At IN DC (50 Hz 690 V) kW 250 355 560 900 1100 1500
• At IH DC (50 Hz 690 V) kW 195 280 440 710 910 1220
• At IN DC (50 Hz 500 V) kW 175 250 390 635 810 1085
• At IH DC (50 Hz 500 V) kW 165 235 365 595 755 1015
• At IN DC (60 Hz 575 V) hp 250 350 600 900 1250 1500
• At IH DC (60 Hz 575 V) hp 200 300 450 800 1000 1250
DC link current
• Rated current IN DC A 300 430 680 1100 1400 1880
3
• Base-load current IH DC 1) A 234 335 530 858 1092 1467
• Maximum current Imax DC A 450 645 1020 1650 2100 2820
Input current
• Rated current IN I A 260 375 575 925 1180 1580
• Maximum current Imax I A 390 563 863 1388 1770 2370
• Max. pre-charging current (max. 3 s) A Internal Internal Internal Internal Internal 234
Current demand
• 24 V DC auxiliary power supply A 1.1 1.1 1.1 1.1 1.1 1.1
DC link capacitance
• Basic Line Module F 3200 4800 7300 11600 15470 19500
• Drive line-up, max. F 25600 38400 58400 92800 123760 78000/156000 2)
Power loss, max. 3)
• At 50 Hz 690 V kW 1.5 2.1 3.0 5.4 5.8 7.3
• At 60 Hz 575 V kW 1.5 2.1 3.0 5.4 5.8 7.3
Cooling air requirement m3/s (ft3/s) 0.17 (6.00) 0.17 (6.00) 0.17 (6.00) 0.36 (12.7) 0.36 (12.7) 0.36 (12.7)
Sound pressure level LpA dB 66/68 66/68 66/68 71/73 71/73 71/73
(1 m) at 50/60 Hz
Line connection Flat connector Flat connector Flat connector Flat connector Flat connector Flat connector
U1, V1, W1 for M10 screw for M10 screw for M10 screw for M12 screw for M12 screw for M12 screw
• Conductor cross-section, max. (IEC) mm2 2 × 240 2 × 240 2 × 240 6 × 185 6 × 185 6 × 185
DC link connection M10 screw M10 screw M10 screw 3 × hole for M12 3 × hole for M12 3 × hole for M12
DCP, DCN
• Conductor cross-section, max. (IEC) mm2 2 × 240 2 × 240 2 × 240 6 ×185 6 × 185 6 × 185
PE/GND connection 2 × hole for M10 2 × hole for M10 2 × hole for M10 2 × hole for M12 2 × hole for M12 2 × hole for M12
• Conductor cross-section, max. (IEC) mm2 2 × 240 2 × 240 2 × 240 4 × 240 4 × 240 4 × 240
Cable length, max. 4)
• Shielded m (ft) 1500 (4921) 1500 (4921) 1500 (4921) 2250 (7382) 2250 (7382) 2750 (9022)
• Unshielded m (ft) 2250 (7382) 2250 (7382) 2250 (7382) 3375 (11073) 3375 (11073) 4125 (13533)
Degree of protection IP00 IP00 IP00 IP00 IP00 IP00
Dimensions
• Width mm (in) 310 (12.2) 310 (12.2) 310 (12.2) 310 (12.2) 310 (12.2) 310 (12.2)
• Height mm (in) 1164 (45.8) 1164 (45.8) 1164 (45.8) 1653 (65.1) 1653 (65.1) 1653 (65.1)
• Depth mm (in) 352 (13.9) 352 (13.9) 352 (13.9) 550 (21.7) 550 (21.7) 550 (21.7)
Weight, approx. kg (lb) 96 (212) 96 (212) 96 (212) 214 (472) 214 (472) 214 (472)
Frame size FB FB FB GB GB GD
Minimum short-circuit current 5) kA 3 4.4 8 10.4 16 18.6

1) 4)
The base-load current IH DC is the basis for a duty cycle of 150 % for 60 s or Total of all motor cables and DC link. Longer cable lengths for specific
Imax DC for 5 s with a duty cycle duration of 300 s. configurations are available on request.
2)
The first value applies for one precharging resistor for each phase, For additional information, please refer to the SINAMICS Low Voltage
the second value for two precharging resistors connected in parallel for Engineering Manual.
5)
each phase. Current required for reliably triggering protective devices.
3)
The specified power loss represents the maximum value at 100 %
utilization. The value is lower under normal operating conditions.

Siemens D 21.3 · 2022 3/21


© Siemens 2022

SINAMICS S120 Chassis Format Units


Air-cooled units
Smart Line Modules

■ Overview ■ Selection and ordering data


Rated power Infeed/regenerative Smart Line Module
at 400 V or 690 V feedback current
kW A Article No.
Line voltage 380 ... 480 V 3 AC
250 463 6SL3330-6TE35-5AA3
355 614 6SL3330-6TE37-3AA3
500 883 6SL3330-6TE41-1AA3
630 1093 6SL3330-6TE41-3AA3
800 1430 6SL3330-6TE41-7AA3
3 Line voltage 500 ... 690 V 3 AC
450 463 6SL3330-6TG35-5AA3
710 757 6SL3330-6TG38-8AA3
1000 1009 6SL3330-6TG41-2AA3
1400 1430 6SL3330-6TG41-7AA3

Extended liability for defects


Smart Line Modules are infeed/regenerative feedback units that
supply power to connected Motor Modules. Furthermore, they Siemens offers for SINAMICS S120 chassis units an extended
are capable of feeding regenerative energy back into the grid. liability for defects/Service Protect up to 6½ years.
The infeed occurs over a diode jumper, while stable,
line-commutated regenerative feedback takes place via IGBTs Details can be found in chapter
with 100 % continuous energy regeneration. The regenerative Services and Documentation
capability of the modules can be deactivated by means of Accessories for re-ordering
parameterization. An integrated Voltage Sensing Module VSM10
is used for sensing the line voltage for regenerative feedback. Description Article No.
Smart Line Modules are designed for connection to grounded Dust protection blanking plugs 6SL3066-4CA00-0AA0
TN/TT and non-grounded IT supply systems. (50 units)
For DRIVE-CLiQ port
The DC link is pre-charged by means of integrated pre-charging
resistors. For line-side components, Braking Modules, and recommended
system components, see System components.
To operate the Smart Line Module, the associated line reactor or
a suitable transformer is required.

■ Design
The Smart Line Modules have the following interfaces as
standard:
• 1 line supply connection
• 1 connection for the 24 V DC electronics power supply
• 1 DC link connection (DCP, DCN) for supplying the connected
Motor Modules
• 1 DC link connection (DCPA, DCNA) for connecting a Braking
Module
• 3 DRIVE-CLiQ sockets
• 1 temperature sensor input for KTY84-130, Pt1000, PTC
or Pt100 (Pt1000 can be used from firmware V4.7 HF17
and higher)
• 1 PE/protective conductor connection (2 connections for sizes
HX and 3 connections for size JX)
The status of the Smart Line Modules is indicated via three LEDs.
The scope of supply of the Smart Line Modules includes:
• DRIVE-CLiQ cable to connect to a Control Unit
• DRIVE-CLiQ cable for connection between the Control Unit
and first Motor Module (type dependent)
• 1 set of warning labels in 30 languages
(BG, CN, CZ, DE, DK, EE, ES, FI, FR, GB, GR, HU, IE, IS, IT,
JP, KR, LT, LV, MT, NL, NO, PL, PT, RO, RU, SE, SI, SK, TR)

3/22 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Chassis Format Units


Air-cooled units
Smart Line Modules

■ Integration
The Smart Line Modules communicate with the higher-level control module via DRIVE-CLiQ. The control module in this case can be
a CU320-2 or a SIMOTION D Control Unit. An external 24 V DC power supply is required to operate the Smart Line Modules.

L1
L2
L3 X400 X401 X402 X500

Smart Line

DRIVE-CLiQ socket
DRIVE-CLiQ socket 0

DRIVE-CLiQ socket 1

DRIVE-CLiQ socket 2
Module LED
chassis format READY
3
-X41
VSM10
4
Voltage
+Temp Sensing
3 -Temp Module
2 EP +24 V
1 EP M1 READY

LEDs
-X42 DC LINK
IPD Card
1 P24L POWER OK
2
P24L
3 M
4
M
External
Main switch 24 V DC -X9
1 P24 V =
2 M
=
230 V AC 3 control of
4 bypass Internal
5 contactor power supply
Bypass
contactor 6
7 Checkback signal
8 pre-charging
L1
Line L2
infeed L3
-F10

1)
-F11 Fan
Line reactor
-F20

-F21

Fan DCPA Connection for


Internal
DCNA Braking Module
U1 -X1
V1 ~
~ DCP
DC link
W1 = DCN
PE

G_D211_EN_00256d

1)The number of fans depends on the frame size.

Connection example of a Smart Line Module

Siemens D 21.3 · 2022 3/23


© Siemens 2022

SINAMICS S120 Chassis Format Units


Air-cooled units
Smart Line Modules

■ Technical specifications
General technical specifications
Electrical specifications
Line power factor
at rated power
• Basic fundamental (cos 1) >0.96
• Total () 0.75 ... 0.93
Efficiency >98.5 %
DC link voltage, approx. 1) 1.32 × line voltage under partial load
1.30 × line voltage under full load

3 Main contactor control


• Terminal strip -X9/5-6 240 V AC, max. 8 A
30 V DC, max. 1 A

1)
The DC link voltage is unregulated and load-dependent.
For additional information, please refer to the SINAMICS Low Voltage
Engineering Manual.

3/24 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Chassis Format Units


Air-cooled units
Smart Line Modules

■ Technical specifications
Line voltage 380 ... 480 V 3 AC Smart Line Modules
6SL3330- 6SL3330- 6SL3330- 6SL3330- 6SL3330-
6TE35-5AA3 6TE37-3AA3 6TE41-1AA3 6TE41-3AA3 6TE41-7AA3
Rated power
• At IN DC (50 Hz 400 V) kW 250 355 500 630 800
• At IH DC (50 Hz 400 V) kW 235 315 450 555 730
• At IN DC (60 Hz 460 V) hp 385 545 770 970 1230
• At IH DC (60 Hz 460 V) hp 360 485 695 855 1125
DC link current
• Rated current IN DC A 550 730 1050 1300 1700
• Base-load current IH DC 1)
• Maximum current Imax DC
A
A
490
825
650
1095
934
1575
1157
1950
1513
2550
3
Infeed/regenerative feedback current
• Rated current IN I A 463 614 883 1093 1430
• Maximum current Imax I A 694 921 1324 1639 2145
Current demand
• 24 V DC auxiliary power supply A 1.35 1.35 1.4 1.5 1.7
• 400 V AC A 1.8 1.8 3.6 5.4 5.4
DC link capacitance
• Smart Line Module F 8400 12000 16800 18900 28800
• Drive line-up, max. F 42000 60000 67200 75600 115200
Power loss, max. 2)
• At 50 Hz 400 V kW 3.7 4.7 7.1 11.0 11.5
• At 60 Hz 460 V kW 3.7 4.7 7.1 11.0 11.5
Cooling air requirement m3/s 0.36 (12.7) 0.36 (12.7) 0.78 (27.5) 1.08 (38.1) 1.08 (38.1)
(ft3/s)
Sound pressure level LpA dB 69/73 69/73 70/73 70/73 70/73
(1 m) at 50/60 Hz
Line connection Flat connector for Flat connector for Flat connector for Flat connector for Flat connector for
U1, V1, W1 M10 screw M10 screw M12 screw M12 screw M12 screw
2
• Conductor cross-section, max. (IEC) mm 2 × 240 2 × 240 4 × 240 6 × 240 6 × 240
DC link connection M10 screw M10 screw 4 × hole for M12 4 × hole for M12 4 × hole for M12
DCP, DCN
• Conductor cross-section, max. (IEC) mm2 2 × 240 2 × 240 Busbar Busbar Busbar
PE/GND connection Hole for M10 Hole for M10 – – –
• Conductor cross-section, max. (IEC) mm2 2 × 240 2 × 240 – – –
PE1/GND connection – – M12 screw M12 screw M12 screw
• Conductor cross-section, max. (IEC) mm2 – – 240 240 240
PE2/GND connection – – 2 × M12 screw 3 × M12 screw 3 × M12 screw
• Conductor cross-section, max. (IEC) mm2 – – 2 × 240 3 × 240 3 × 240
Cable length, max. 3)
• Shielded m (ft) 4000 (13123) 4000 (13123) 4800 (15748) 4800 (15748) 4800 (15748)
• Unshielded m (ft) 6000 (19685) 6000 (19685) 7200 (23622) 7200 (23622) 7200 (23622)
Degree of protection IP00 IP00 IP00 IP00 IP00
Dimensions
• Width mm (in) 310 (12.2) 310 (12.2) 503 (19.8) 704 (27.7) 704 (27.7)
• Height mm (in) 1413 (55.6) 1413 (55.6) 1475 (58.1) 1480 (58.3) 1480 (58.3)
• Depth mm (in) 550 (21.7) 550 (21.7) 548 (21.6) 550 (21.7) 550 (21.7)
Weight, approx. kg (lb) 150 (331) 150 (331) 294 (648) 458 (1010) 458 (1010)
Frame size GX GX HX JX JX
Minimum short-circuit current 4) kA 6.2 9.2 10.4 16 21

1) 3)
The base-load current IH DC is the basis for a duty cycle of 150 % for 60 s Total of all motor cables and DC link. Longer cable lengths for specific
or Imax DC for 5 s with a duty cycle duration of 300 s. configurations are available on request.
2)
The specified power loss represents the maximum value at 100 % For additional information, please refer to the SINAMICS Low Voltage
utilization. The value is lower under normal operating conditions. Engineering Manual.
4)
Current required for reliably triggering protective devices.

Siemens D 21.3 · 2022 3/25


© Siemens 2022

SINAMICS S120 Chassis Format Units


Air-cooled units
Smart Line Modules

■ Technical specifications
Line voltage 500 ... 690 V 3 AC Smart Line Modules
6SL3330-6TG35-5AA3 6SL3330-6TG38-8AA3 6SL3330-6TG41-2AA3 6SL3330-6TG41-7AA3
Rated power
• At IN DC (50 Hz 690 V) kW 450 710 1000 1400
• At IH DC (50 Hz 690 V) kW 405 665 885 1255
• At IN DC (50 Hz 500 V) kW 320 525 705 995
• At IH DC (50 Hz 500 V) kW 295 480 640 910
• At IN DC (60 Hz 575 V) hp 500 790 1115 1465
• At IH DC (60 Hz 575 V) hp 450 740 990 1400
DC link current
3 • Rated current IN DC
• Base-load current IH DC 1)
A
A
550
490
900
800
1200
1068
1700
1513
• Maximum current Imax DC A 825 1350 1800 2550
Infeed/regenerative feedback
current
• Rated current IN I A 463 757 1009 1430
• Maximum current Imax I A 694 1135 1513 2145
Current demand
• 24 V DC auxiliary power supply A 1.35 1.4 1.5 1.7
• 500 V AC A 1.3 2.9 4.3 4.3
• 690 V AC A 0.94 2.1 3.1 3.1
DC link capacitance
• Smart Line Module F 5600 7400 11100 14400
• Drive line-up, max. F 28000 29600 44400 57600
Power loss, max. 2)
• At 50 Hz 690 V kW 4.3 6.5 12.0 13.8
• At 60 Hz 575 V kW 4.3 6.5 12.0 13.8
Cooling air requirement m3/s (ft3/s) 0.36 (12.7) 0.78 (27.5) 1.08 (38.1) 1.08 (38.1)
Sound pressure level LpA dB 69/73 70/73 70/73 70/73
(1 m) at 50/60 Hz
Line connection Flat connector for M10 Flat connector for M12 Flat connector for M12 Flat connector for M12
U1, V1, W1 screw screw screw screw
• Conductor cross-section, max. mm2 2 × 240 4 × 240 6 × 240 6 × 240
(IEC)
DC link connection M10 screw 4 × hole for M12 4 × hole for M12 4 × hole for M12
DCP, DCN
• Conductor cross-section, max. mm2 2 × 240 Busbar Busbar Busbar
(IEC)
PE connection Hole for M10 – – –
• Conductor cross-section, max. mm2 2 × 240 – – –
(IEC)
PE1/GND connection – M12 screw M12 screw M12 screw
• Conductor cross-section, max. mm2 – 240 240 240
(IEC)
PE2/GND connection – 2 × M12 screw 3 × M12 screw 3 × M12 screw
• Conductor cross-section, max. mm2 – 2 × 240 3 × 240 3 × 240
(IEC)
Cable length, max. 3)
• Shielded m (ft) 2250 (7382) 2750 (9022) 2750 (9022) 2750 (9022)
• Unshielded m (ft) 3375 (11073) 4125 (13533) 4125 (13533) 4125 (13533)
Degree of protection IP00 IP00 IP00 IP00
Dimensions
• Width mm (in) 310 (12.2) 503 (19.8) 704 (27.7) 704 (27.7)
• Height mm (in) 1413 (55.6) 1475 (58.1) 1480 (58.3) 1480 (58.3)
• Depth mm (in) 550 (21.7) 548 (21.6) 550 (21.7) 550 (21.7)
Weight, approx. kg (lb) 150 (331) 294 (648) 458 (1010) 458 (1010)
Frame size GX HX JX JX
Minimum short-circuit current 4) kA 6.2 10.5 12.4 21

1) The base-load current IH DC is the basis for a duty cycle of 150 % for 60 s 3) Total of all motor cables and DC link. Longer cable lengths for specific
or Imax DC for 5 s with a duty cycle duration of 300 s. configurations are available on request.
2) The specified power loss represents the maximum value at 100 % For additional information, please refer to the SINAMICS Low Voltage
utilization. The value is lower under normal operating conditions. Engineering Manual.
4) Current required for reliably triggering protective devices.

3/26 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Chassis Format Units


Air-cooled units
Active Line Modules

■ Overview ■ Selection and ordering data


Rated power Rated infeed/ Active Line Module
at 400 V or 690 V regenerative
feedback current
kW A Article No.
Line voltage 380 ... 480 V 3 AC
132 210 6SL3330-7TE32-1AA3
160 260 6SL3330-7TE32-6AA3
235 380 6SL3330-7TE33-8AA3
300 490 6SL3330-7TE35-0AA3
380 605 6SL3330-7TE36-1AA3 3
450 745 6SL3330-7TE37-5AA3
500 840 6SL3330-7TE38-4AA3
630 985 6SL3330-7TE41-0AA3
800 1260 6SL3330-7TE41-2AA3
900 1405 6SL3330-7TE41-4AA3
The self-commutated infeed/regenerative feedback units with Line voltage 500 ... 690 V 3 AC
IGBTs generate a regulated DC link voltage. This means that the
630 575 6SL3330-7TG35-8AA3
connected Motor Modules are decoupled from the line voltage.
Line voltage fluctuations within the permissible supply 800 735 6SL3330-7TG37-4AA3
tolerances have no effect on the motor voltage. 1100 1025 6SL3330-7TG41-0AA3
If required, the Active Line Modules can also provide reactive 1400 1270 6SL3330-7TG41-3AA3
power compensation.
Extended liability for defects
Active Line Modules are designed for connection to grounded
TN/TT and non-grounded IT supply systems. Siemens offers for SINAMICS S120 chassis units an extended
liability for defects/Service Protect up to 6½ years.
Active Line Modules are always operated together with the
associated Active Interface Modules. These include the Details can be found in chapter
necessary pre-charging circuit as well as a Clean Power Filter. Services and Documentation

■ Design
Accessories for re-ordering

Description Article No.


The Active Line Modules have the following interfaces as
Dust protection blanking plugs 6SL3066-4CA00-0AA0
standard: (50 units)
• 1 line supply connection For DRIVE-CLiQ port
• 1 connection for the 24 V DC electronics power supply For line-side components, Braking Modules, and recommended
• 1 DC link connection (DCP, DCN) for supplying the connected system components, see System components.
Motor Modules
• 1 DC link connection (DCPA, DCNA) for connecting a Braking
Module
• 3 DRIVE-CLiQ sockets
• 1 temperature sensor input for KTY84-130, Pt1000, PTC or
Pt100 (Pt1000 can be used from firmware V4.7 HF17 and
higher)
• 2 PE/protective conductor connections
The status of the Active Line Modules is indicated via three
LEDs.
The scope of supply of the Active Line Modules includes:
• DRIVE-CLiQ cable to connect to a Control Unit
• DRIVE-CLiQ cable to connect the Control Unit to the first Motor
Module
• 1 set of warning labels in 30 languages
(BG, CN, CZ, DE, DK, EE, ES, FI, FR, GB, GR, HU, IE, IS, IT,
JP, KR, LT, LV, MT, NL, NO, PL, PT, RO, RU, SE, SI, SK, TR)

Siemens D 21.3 · 2022 3/27


© Siemens 2022

SINAMICS S120 Chassis Format Units


Air-cooled units
Active Line Modules

■ Integration
The Active Line Modules communicate with the higher-level control module via DRIVE-CLiQ. This control module can be:
• A CU320-2 Control Unit
• A SIMOTION D Control Unit
• A SINUMERIK 840D sl
• A SINUMERIK ONE
An external 24 V DC power supply is required to operate the Active Line Modules.

X400 X401 X402

2
3 -X41

DRIVE-CLiQ socket

DRIVE-CLiQ socket

DRIVE-CLiQ socket
4 +Temp
3 -Temp
Active Line
2 EP +24 V Module
1 EP M1
chassis
-X42 format
1 P24L
2 READY

LEDs
P24L
3 M
4 DC LINK
M IPD Card
POWER OK

-X9
1 P24 V =
ext.
24 V DC 2 M
=
3 Control of bypass
4 contactor Internal power
to Active Interface Module supply
5
Control of
6 pre-charging contactor
-F10
Fan supply terminal for sizes HX L1
and JX. L2
The number of the fans depends on -F11 Fan
the frame size.
-F20

-F21 Fan
internal
DCPA Connection for
Fan supply terminal for sizes FX -F10 DCPN Braking Module
and GX directly on the fuse carrier.
-F11 Fan
internal

U1 -X1
~ DCP
V1 DCN DC link connection
from Active
Interface Module W1 =
PE

G_D211_EN_00258b

Connection example of an Active Line Module

3/28 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Chassis Format Units


Air-cooled units
Active Line Modules

■ Technical specifications
General technical specifications
Electrical specifications
Line power factor
• Basic fundamental (cos 1) 1 (factory setting),
can be altered by inputting a reactive current setpoint
• Total () 1 (factory setting)
Efficiency >97.5 % (including Active Interface Module)
DC link voltage The DC link voltage is regulated and can be adjusted as a voltage decoupled from the line voltage.
Factory setting of the DC link voltage: 1.5 × line voltage
Radio interference suppression
• Standard (Active Line Module with Ac- Category C3 acc. to EN 61800-3 3
tive Interface Module)
• With line filter Category C2 acc. to EN 61800-3

Siemens D 21.3 · 2022 3/29


© Siemens 2022

SINAMICS S120 Chassis Format Units


Air-cooled units
Active Line Modules

■ Technical specifications
Line voltage 380 ... 480 V 3 AC Active Line Modules
6SL3330- 6SL3330- 6SL3330- 6SL3330- 6SL3330-
7TE32-1AA3 7TE32-6AA3 7TE33-8AA3 7TE35-0AA3 7TE36-1AA3
Rated power
• At IN DC (50 Hz 400 V) kW 132 160 235 300 380
• At IH DC (50 Hz 400 V) kW 115 145 210 270 335
• At IN DC (60 Hz 460 V) hp 200 250 400 500 600
• At IH DC (60 Hz 460 V) hp 150 200 300 400 500
DC link current
• Rated current IN DC A 235 291 425 549 678
3 • Base-load current IH DC 1)
• Maximum current Imax DC
A
A
209
352
259
436
378
637
489
823
603
1017
Infeed/regenerative feedback current
• Rated current IN I A 210 260 380 490 605
• Maximum current Imax I A 315 390 570 735 907
Current demand
• 24 V DC auxiliary power supply A 1.1 1.1 1.35 1.35 1.4
• 400 V AC A 0.63 1.13 1.8 1.8 3.6
DC link capacitance
• Active Line Module F 4200 5200 7800 9600 12600
• Drive line-up, max. F 41600 41600 76800 76800 134400
Power loss, max. 2)
• At 50 Hz 400 V kW 2.2 2.7 3.9 4.8 6.2
• At 60 Hz 460 V kW 2.3 2.9 4.2 5.1 6.6
Cooling air requirement m3/s 0.17 (6.00) 0.23 (8.12) 0.36 (12.7) 0.36 (12.7) 0.78 (27.5)
(ft3/s)
Sound pressure level LpA 3) dB 64/67 71/71 69/73 69/73 70/73
(1 m) at 50/60 Hz
Line supply connection Flat connector for Flat connector for Flat connector for Flat connector for Flat connector for
U1, V1, W1 M10 screw M10 screw M10 screw M10 screw M12 screw
2
• Conductor cross-section, max. (IEC) mm 2 × 185 2 × 185 2 × 240 2 × 240 4 × 240
DC link connection M10 screw M10 screw M10 screw M10 screw 4 × hole for M12
DCP, DCN
• Conductor cross-section, max. (IEC) mm2 2 × 185 2 × 185 2 × 240 2 × 240 Busbar
PE1/GND connection M10 screw M10 screw M10 screw M10 screw M12 screw
• Conductor cross-section, max. (IEC) mm2 2 × 185 2 × 185 2 × 240 2 × 240 240
PE2/GND connection M10 screw M10 screw M10 screw M10 screw 2 × M12 screw
• Conductor cross-section, max. (IEC) mm2 2 × 185 2 × 185 2 × 240 2 × 240 2 × 240
Cable length, max. 4)
• Shielded m (ft) 2700 (8858) 2700 (8858) 2700 (8858) 2700 (8858) 3900 (12795)
• Unshielded m (ft) 4050 (13287) 4050 (13287) 4050 (13287) 4050 (13287) 5850 (19193)
Degree of protection IP20 IP20 IP20 IP20 IP00
Dimensions
• Width mm (in) 326 (12.8) 326 (12.8) 326 (12.8) 326 (12.8) 503 (19.8)
• Height mm (in) 1400 (55.1) 1400 (55.1) 1533 (60.4) 1533 (60.4) 1475 (58.1)
• Depth mm (in) 356 (14.0) 356 (14.0) 545 (21.5) 545 (21.5) 540 (21.3)
Weight, approx. kg (lb) 95 (209) 95 (209) 136 (300) 136 (300) 290 (639)
Frame size FX FX GX GX HX
Minimum short-circuit current 5) kA 6.2 10.5 10.5 8 9.2

1) The base-load current IH DC is the basis for a duty cycle of 150 % for 60 s or 4) Total of all motor cables and DC link. Longer cable lengths for specific
Imax DC for 5 s with a duty cycle duration of 300 s. configurations are available on request.
2) The specified power loss represents the maximum value at 100 % For additional information, please refer to the SINAMICS Low Voltage
utilization. The value is lower under normal operating conditions. Engineering Manual.
5) Current required for reliably triggering protective devices.
3) Total sound pressure level of Active Interface Module and Active Line
Module.

3/30 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Chassis Format Units


Air-cooled units
Active Line Modules

■ Technical specifications
Line voltage 380 ... 480 V 3 AC Active Line Modules
6SL3330- 6SL3330- 6SL3330- 6SL3330- 6SL3330-
7TE37-5AA3 7TE38-4AA3 7TE41-0AA3 7TE41-2AA3 7TE41-4AA3
Rated power
• At IN DC (50 Hz 400 V) kW 450 500 630 800 900
• At IH DC (50 Hz 400 V) kW 400 465 545 690 780
• At IN DC (60 Hz 460 V) hp 600 700 900 1000 1250
• At IH DC (60 Hz 460 V) hp 600 700 800 900 1000
DC link current
• Rated current IN DC A 835 940 1103 1412 1574
• Base-load current IH DC 1)
• Maximum current Imax DC
A
A
700
1252
837
1410
982
1654
1255
2120
1401
2361
3
Infeed/regenerative feedback current
• Rated current IN I A 745 840 985 1260 1405
• Maximum current Imax I A 1117 1260 1477 1890 2107
Current demand
• 24 V DC auxiliary power supply A 1.4 1.4 1.5 1.7 1.7
• 400 V AC A 3.6 3.6 5.4 5.4 5.4
DC link capacitance
• Active Line Module F 15600 16800 18900 26100 28800
• Drive line-up, max. F 134400 134400 230400 230400 230400
Power loss, max. 2)
• At 50 Hz 400 V kW 7.3 7.7 10.1 12.1 13.3
• At 60 Hz 460 V kW 7.7 8.2 10.8 13.0 14.2
Cooling air requirement m3/s 0.78 (27.5) 0.78 (27.5) 1.08 (38.1) 1.08 (38.1) 1.08 (38.1)
(ft3/s)
Sound pressure level LpA 3) dB 70/73 70/73 71/73 71/73 71/73
(1 m) at 50/60 Hz
Line supply connection Flat connector for Flat connector for Flat connector for Flat connector for Flat connector for
U1, V1, W1 M12 screw M12 screw M12 screw M12 screw M12 screw
2
• Conductor cross-section, max. (IEC) mm 4 × 240 4 × 240 6 × 240 6 × 240 6 × 240
DC link connection 4 × hole for M12 4 × hole for M12 4 × hole for M12 4 × hole for M12 4 × hole for M12
DCP, DCN
• Conductor cross-section, max. (IEC) mm2 Busbar Busbar Busbar Busbar Busbar
PE1/GND connection M12 screw M12 screw M12 screw M12 screw M12 screw
• Conductor cross-section, max. (IEC) mm2 240 240 240 240 240
PE2/GND connection 2 × M12 screw 2 × M12 screw 3 × M12 screw 3 × M12 screw 3 × M12 screw
• Conductor cross-section, max. (IEC) mm2 2 × 240 2 × 240 3 × 240 3 × 240 3 × 240
Cable length, max. 4)
• Shielded m (ft) 3900 (12795) 3900 (12795) 3900 (12795) 3900 (12795) 3900 (12795)
• Unshielded m (ft) 5850 (19193) 5850 (19193) 5850 (19193) 5850 (19193) 5850 (19193)
Degree of protection IP00 IP00 IP00 IP00 IP00
Dimensions
• Width mm (in) 503 (19.8) 503 (19.8) 704 (27.7) 704 (27.7) 704 (27.7)
• Height mm (in) 1475 (58.1) 1475 (58.1) 1480 (58.3) 1480 (58.3) 1480 (58.3)
• Depth mm (in) 540 (21.3) 540 (21.3) 550 (21.7) 550 (21.7) 550 (21.7)
Weight, approx. kg (lb) 290 (639) 290 (639) 450 (992) 450 (992) 450 (992)
Frame size HX HX JX JX JX
Minimum short-circuit current 5) kA 8.8 10.4 16 21 21

1) 4)
The base-load current IH DC is the basis for a duty cycle of 150 % for 60 s or Total of all motor cables and DC link. Longer cable lengths for specific
Imax DC for 5 s with a duty cycle duration of 300 s. configurations are available on request.
2)
The specified power loss represents the maximum value at 100 % For additional information, please refer to the SINAMICS Low Voltage
utilization. The value is lower under normal operating conditions. Engineering Manual.
5)
3)
Total sound pressure level of Active Interface Module and Active Line Current required for reliably triggering protective devices.
Module.

Siemens D 21.3 · 2022 3/31


© Siemens 2022

SINAMICS S120 Chassis Format Units


Air-cooled units
Active Line Modules

■ Technical specifications
Line voltage 500 ... 690 V 3 AC Active Line Modules
6SL3330-7TG35-8AA3 6SL3330-7TG37-4AA3 6SL3330-7TG41-0AA3 6SL3330-7TG41-3AA3
Rated power
• At IN DC (50 Hz 690 V) kW 630 800 1100 1400
• At IH DC (50 Hz 690 V) kW 620 705 980 1215
• At IN DC (50 Hz 500 V) kW 447 560 780 965
• At IH DC (50 Hz 500 V) kW 450 510 710 880
• At IN DC (60 Hz 575 V) hp 675 900 1250 1500
• At IH DC (60 Hz 575 V) hp 506 600 1000 1250
DC link current
3 • Rated current IN DC
• Base-load current IH DC 1)
A
A
644
573
823
732
1148
1022
1422
1266
• Maximum current Imax DC A 966 1234 1722 2133
Infeed/regenerative feedback current
• Rated current IN I A 575 735 1025 1270
• Maximum current Imax I A 862 1102 1537 1905
Current demand
• 24 V DC auxiliary power supply A 1.4 1.5 1.7 1.7
• 500 V AC A 3.0 4.4 4.4 4.4
• 690 V AC A 2.1 3.1 3.1 3.1
DC link capacitance
• Active Line Module F 7400 11100 14400 19200
• Drive line-up, max. F 59200 153600 153600 153600
Power loss, max. 2)
• At 50 Hz 690 V kW 6.8 10.2 13.6 16.5
• At 60 Hz 575 V kW 6.2 9.6 12.9 15.3
Cooling air requirement m3/s 0.78 (27.5) 1.08 (38.1) 1.08 (38.1) 1.08 (38.1)
(ft3/s)
Sound pressure level LpA 3) dB 70/73 71/73 71/73 71/73
(1 m) at 50/60 Hz
Line supply connection Flat connector for M12 Flat connector for M12 Flat connector for M12 Flat connector for M12
U1, V1, W1 screw screw screw screw
• Conductor cross-section, max. (IEC) mm2 4 × 240 6 × 240 6 × 240 6 × 240
DC link connection 4 × hole for M12 4 × hole for M12 4 × hole for M12 4 × hole for M12
DCP, DCN
• Conductor cross-section, max. (IEC) mm2 Busbar Busbar Busbar Busbar
PE1/GND connection M12 screw M12 screw M12 screw M12 screw
• Conductor cross-section, max. (IEC) mm2 240 240 240 240
PE2/GND connection 2 × M12 screw 3 × M12 screw 3 × M12 screw 3 × M12 screw
• Conductor cross-section, max. (IEC) mm2 2 x 240 3 x 240 3 x 240 3 x 240
Cable length, max. 4)
• Shielded m (ft) 2250 (7382) 2250 (7382) 2250 (7382) 2250 (7382)
• Unshielded m (ft) 3375 (11073) 3375 (11073) 3375 (11073) 3375 (11073)
Degree of protection IP00 IP00 IP00 IP00
Dimensions
• Width mm (in) 503 (19.8) 704 (27.7) 704 (27.7) 704 (27.7)
• Height mm (in) 1475 (58.1) 1480 (58.3) 1480 (58.3) 1480 (58.3)
• Depth mm (in) 540 (21.3) 550 (21.7) 550 (21.7) 550 (21.7)
Weight, approx. kg (lb) 290 (639) 450 (992) 450 (992) 450 (992)
Frame size HX JX JX JX
Minimum short-circuit current 5) kA 8.4 10.5 16 20

1) The base-load current IH DC is the basis for a duty cycle of 150 % for 60 s or 4) Total of all motor cables and DC link. Longer cable lengths for specific
Imax DC for 5 s with a duty cycle duration of 300 s. configurations are available on request.
2) The specified power loss represents the maximum value at 100 % For additional information, please refer to the SINAMICS Low Voltage
utilization. The value is lower under normal operating conditions. Engineering Manual.
5) Current required for reliably triggering protective devices.
3) Total sound pressure level of Active Interface Module and Active Line
Module.

3/32 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Chassis Format Units


Air-cooled units
Active Interface Modules

■ Overview ■ Selection and ordering data


Suitable for Active Line Rated power of Active Interface Module
Module in chassis format, the Active Line
air-cooled Modules at
400 V or 690 V
kW Article No.
Line voltage 380 ... 480 V 3 AC
6SL3330-7TE32-1AA3 132 6SL3300-7TE32-6AA1
6SL3330-7TE32-6AA3 160 6SL3300-7TE32-6AA1
6SL3330-7TE33-8AA3 235 6SL3300-7TE33-8AA1
6SL3330-7TE35-0AA3
6SL3330-7TE36-1AA3
300
380
6SL3300-7TE35-0AA1
6SL3300-7TE38-4AA1
3
6SL3330-7TE37-5AA3 450 6SL3300-7TE38-4AA1
6SL3330-7TE38-4AA3 500 6SL3300-7TE38-4AA1
6SL3330-7TE41-0AA3 630 6SL3300-7TE41-4AA1
6SL3330-7TE41-2AA3 800 6SL3300-7TE41-4AA1
6SL3330-7TE41-4AA3 900 6SL3300-7TE41-4AA1
Line voltage 500 ... 690 V 3 AC
6SL3330-7TG35-8AA3 630 6SL3300-7TG35-8AA1
6SL3330-7TG37-4AA3 800 6SL3300-7TG37-4AA1
Active Interface Modules are used in conjunction with Active
6SL3330-7TG41-0AA3 1100 6SL3300-7TG41-3AA1
Line Modules. Active Interface Modules contain a Clean Power
Filter with basic RI suppression, the pre-charging circuit for the 6SL3330-7TG41-3AA3 1400 6SL3300-7TG41-3AA1
Active Line Module, the line voltage sensing circuit and
monitoring sensors. The bypass contactor is an integral Extended liability for defects
component in frame sizes FI and GI, This ensures a highly Siemens offers for SINAMICS S120 chassis units an extended
compact design. The bypass contactor must be provided liability for defects/Service Protect up to 6½ years.
separately for frame sizes HI and JI.
Details can be found in chapter
Line harmonics are largely suppressed by the Clean Power Filter. Services and Documentation

■ Design
Active Interface Modules have the following interfaces as
standard:
• 1 line supply connection
• 1 load connection
• 1 connection for the 24 V DC electronics power supply
• 1 connection for the external 230 V AC supply (fan power
supply)
• 1 DRIVE-CLiQ socket (on VSM10 Voltage Sensing Module)
• 1 connection for pre-charging circuit, frame sizes HI and JI
• 1 PE/protective conductor connection
The scope of supply of the Active Interface Modules includes:
• DRIVE-CLiQ cable for the connection between Active
Interface Module and Active Line Module
• 1 set of warning labels in 30 languages
(BG, CN, CZ, DE, DK, EE, ES, FI, FR, GB, GR, HU, IE, IS, IT,
JP, KR, LT, LV, MT, NL, NO, PL, PT, RO, RU, SE, SI, SK, TR)

Siemens D 21.3 · 2022 3/33


© Siemens 2022

SINAMICS S120 Chassis Format Units


Air-cooled units
Active Interface Modules

■ Integration
X500

DRIVE-CLiQ-socket
LED
-X609 Active Interface READY
PE
1
Module
P24
ext. 2
P24
chassis format Voltage
24 V DC 3 Sensing Module
M
3 L
4
5
M
-Q101
VSM10

ext. 6
230 V AC 7 I>
N 8 Fan
Control of
1) 9
pre-charging Pre-charging
contactor 10 contactor
Control of
1) 11 Bypass
bypass contactor 12 contactor
13
Contactors open 14

Main switch

L1 U1 -X1 -X2 U2 to
V1 V2 Active
L2
W1 W2 Line
L3
PE PE Module

1) G_D211_EN_00007e
Control by Active Line Module

Connection example of an Active Interface Module with integrated bypass contactor (frame sizes FI and GI)

3/34 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Chassis Format Units


Air-cooled units
Active Interface Modules

■ Integration
X500

DRIVE-CLiQ-socket
-X609
PE
Active Interface LED
1 P24
Module READY
ext. 2 P24 chassis format
DC 24 V 3 M
4 M Voltage
L -Q101

Control of ext.
5
6
Sensing Module
VSM10 3
pre-charging AC 230 V 7 I>
contactor N Fan
8
Control of 1) 9
pre-charging Pre-charging
10 contactor
contactor
1) 11
Control of
bypass contactor/fan 12
13
Contactors open 14

Bypass
contactor
-K4
2/T1
4/T2
Main switch 6/T3
L1 L1 -X1 -X2 U2
to
L2 V2 Active
L2
L3 W2 Line
L3
PE PE Module

1) G_D211_EN_00008i
Control by Active Line Module

Connection example of an Active Interface Module with externally mounted bypass contactor (frame sizes HI and JI)

Siemens D 21.3 · 2022 3/35


© Siemens 2022

SINAMICS S120 Chassis Format Units


Air-cooled units
Active Interface Modules

■ Technical specifications
Line voltage 380 ... 480 V 3 AC Active Interface Modules
6SL3300-7TE32-6AA1 6SL3300-7TE33-8AA1 6SL3300-7TE35-0AA1
Suitable for Active Line Module
• Rated power at 400 V kW 132 160 235 300
- Air-cooled 6SL3330-7TE32-1AA3 6SL3330-7TE32-6AA3 6SL3330-7TE33-8AA3 6SL3330-7TE35-0AA3
- Liquid-cooled – – – 6SL3335-7TE35-0AA3
Rated current A 210 260 380 490
Bypass contactor Included Included Included Included
Current demand

3 • 24 V DC auxiliary power supply


• 230 V 2 AC
A 0.17 0.17 0.17 0.17

- Inrush current A 1.25 1.25 2.5 2.5


- Holding current A 0.6 0.6 1.2 1.2
DC link capacitance
• Drive line-up, max. 1) F 41600 41600 76800 76800
Power loss, max. 2)
• At 50 Hz 400 V kW 2.1 2.2 3.0 3.9
• At 60 Hz 460 V kW 2.1 2.2 3.0 3.9
Cooling air requirement m3/s (ft3/s) 0.24 (8.48) 0.24 (8.48) 0.47 (16.6) 0.47 (16.6)
Line/load connection Flat connector for M10 Flat connector for M10 Flat connector for M10 Flat connector for M10
L1, L2, L3 / U2, V2, W2 screw screw screw screw
• Conductor cross-section, max. (IEC) mm2 2 × 185 2 × 185 2 × 185 2 × 185
PE/GND connection 2 × M10 nut 2 × M10 nut 2 × M10 nut 2 × M10 nut
• Conductor cross-section, max. (IEC) mm2 2 × 185 2 × 185 2 × 185 2 × 185
Degree of protection IP20 IP20 IP20 IP20
Dimensions
• Width mm (in) 325 (12.8) 325 (12.8) 325 (12.8) 325 (12.8)
• Height mm (in) 1400 (55.1) 1400 (55.1) 1533 (60.4) 1533 (60.4)
• Depth mm (in) 355 (14.0) 355 (14.0) 544 (21.4) 544 (21.4)
Weight, approx. kg (lb) 135 (298) 135 (298) 190 (419) 190 (419)
Frame size FI FI GI GI
Minimum short-circuit current 3) kA 6.2 10.5 10.5 8

1)
Information on higher capacities is included in the SINAMICS Low Voltage
Engineering Manual.
2)
The specified power loss represents the maximum value at 100 %
utilization. The value is lower under normal operating conditions.
3)
Current required for reliable triggering of the protective devices.

3/36 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Chassis Format Units


Air-cooled units
Active Interface Modules

■ Technical specifications
Line voltage 380 ... 480 V 3 AC Active Interface Modules
6SL3300-7TE38-4AA1 6SL3300-7TE41-4AA1
Suitable for Active Line Module
• Rated power at 400 V kW 380 450/500 630 800/900
- Air-cooled 6SL3330-7TE36-1AA3 6SL3330-7TE37-5AA3 6SL3330-7TE41-0AA3 6SL3330-7TE41-2AA3
6SL3330-7TE38-4AA3 6SL3330-7TE41-4AA3
Rated current A 605 745/840 985 1260/1405
Bypass contactor 3RT1476-6AP36 3WA1110-4AE03-4EQ0 3WA1112-4AE03-4EQ0) 3WA1116-4AE03-4EQ0
Current demand
• 24 V DC auxiliary power supply
• 230 V 2 AC
A 0.17 0.17 0.17 0.17
3
- Inrush current A 9.9 9.9 10.5 10.5
- Holding current A 4.6 4.6 4.9 4.9
DC link capacitance
• Drive line-up, max. 1) F 134400 134400 230400 230400
Power loss, max. 2)
• At 50 Hz 400 V kW 5.5 6.1 7.5 8.5
• At 60 Hz 460 V kW 5.5 6.1 7.5 8.5
Cooling air requirement m3/s (ft3/s) 0.4 (14.1) 0.4 (14.1) 0.4 (14.1) 0.4 (14.1)
Line/load connection 4 × hole for M12 4 × hole for M12 3 × hole for M12 3 × hole for M12
L1, L2, L3 / U2, V2, W2
• Conductor cross-section, max. (IEC) mm2 4 × 240 4 × 240 6 × 240 6 × 240
PE/GND connection 2 × M12 nut 2 × M12 nut 4 × M12 nut 4 × M12 nut
• Conductor cross-section, max. (IEC) mm2 2 × 240 2 × 240 4 × 240 4 × 240
Degree of protection IP00 IP00 IP00 IP00
Dimensions
• Width mm (in) 305 (12.0) 305 (12.0) 505 (19.9) 505 (19.9)
• Height mm (in) 1750 (68.9) 1750 (68.9) 1750 (68.9) 1750 (68.9)
• Depth mm (in) 544 (21.4) 544 (21.4) 544 (21.4) 544 (21.4)
Weight, approx. kg (lb) 390 (860) 390 (860) 480 (1058) 480 (1058)
Frame size HI HI JI JI
Minimum short-circuit current 3) kA 9.2 8.8/10.4 16 21

1)
Information on higher capacities is included in the SINAMICS Low Voltage
Engineering Manual.
2)
The specified power loss represents the maximum value at 100 %
utilization. The value is lower under normal operating conditions.
3)
Current required for reliable triggering of the protective devices.

Siemens D 21.3 · 2022 3/37


© Siemens 2022

SINAMICS S120 Chassis Format Units


Air-cooled units
Active Interface Modules

■ Technical specifications
Line voltage 500 ... 690 V 3 AC Active Interface Modules
6SL3300-7TG35-8AA1 6SL3300-7TG37-4AA1 6SL3300-7TG41-3AA1
Suitable for Active Line Module
• Rated power at 690 V kW 630 800 1100 1400
- Air-cooled 6SL3330-7TG35-8AA3 6SL3330-7TG37-4AA3 6SL3330-7TG41-0AA3 6SL3330-7TG41-3AA3
- Liquid-cooled 6SL3335-7TG35-8AA3 – – –
Rated current A 575 735 1025 1270
Bypass contactor 3RT1476-6AP36 3RT1476-6AP36 (3 units) 3WA1220-4AE03-4EQ0-Z 3WA1220-4AE03-4EQ0-Z
B12 B16

3 Current demand
• 24 V DC auxiliary power supply A 0.17 0.17 0.17 0.17
• 230 V 2 AC
- Inrush current A 9.9 10.5 10.5 10.5
- Holding current A 4.6 4.9 4.9 4.9
DC link capacitance
• Drive line-up, max. 1) F 59200 153600 153600 153600
Power loss, max. 2)
• At 50 Hz 690 V kW 6.8 9.0 9.2 9.6
• At 60 Hz 575 V kW 6.8 9.0 9.2 9.6
Cooling air requirement m3/s (ft3/s) 0.4 (14.1) 0.4 (14.1) 0.4 (14.1) 0.4 (14.1)
Line/load connection 4 × hole for M12 3 × hole for M12 3 × hole for M12 3 × hole for M12
L1, L2, L3 / U2, V2, W2
• Conductor cross-section, max. (IEC) mm2 4 × 240 6 × 240 6 × 240 6 × 240
PE/GND connection 2 × M12 nut 4 × M12 nut 4 × M12 nut 4 × M12 nut
• Conductor cross-section, max. (IEC) mm2 2 × 240 4 × 240 4 × 240 4 × 240
Degree of protection IP00 IP00 IP00 IP00
Dimensions
• Width mm (in) 305 (12.0) 505 (19.9) 505 (19.9) 505 (19.9)
• Height mm (in) 1750 (68.9) 1750 (68.9) 1750 (68.9) 1750 (68.9)
• Depth mm (in) 544 (21.4) 544 (21.4) 544 (21.4) 544 (21.4)
Weight, approx. kg (lb) 390 (860) 430 (948) 530 (1168) 530 (1168)
Frame size HI JI JI JI
Minimum short-circuit current 3) kA 8.4 10.5 16 20

1) Information on higher capacities is included in the SINAMICS Low Voltage


Engineering Manual.
2) The specified power loss represents the maximum value at 100 %
utilization. The value is lower under normal operating conditions.
3) Current required for reliable triggering of the protective devices.

3/38 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Chassis Format Units


Air-cooled units
Motor Modules

■ Overview ■ Selection and ordering data


Type rating Rated output current Motor Module
at 400 V or 690 V
kW A Article No.
Line voltage 380 ... 480 V 3 AC
(DC link voltage 510 ... 720 V DC)
110 210 6SL3320-1TE32-1AA3
132 260 6SL3320-1TE32-6AA3
160 310 6SL3320-1TE33-1AA3
200 380 6SL3320-1TE33-8AA3
250 490 6SL3320-1TE35-0AA3 3
315 605 6SL3320-1TE36-1AA3
400 745 6SL3320-1TE37-5AA3
450 840 6SL3320-1TE38-4AA3
560 985 6SL3320-1TE41-0AA3
710 1260 6SL3320-1TE41-2AA3
A Motor Module comprises a self-commutated inverter with 800 1405 6SL3320-1TE41-4AA3
IGBTs. It generates a variable voltage with variable frequency
from the DC link voltage that feeds the connected motor. Line voltage 500 ... 690 V 3 AC
(DC link voltage 675 ... 1035 V DC)
Multiple Motor Modules can be operated on a single DC link. 75 85 6SL3320-1TG28-5AA3
This permits energy to be transferred between the Motor
Modules. This means that if one Motor Module operating in 90 100 6SL3320-1TG31-0AA3
generator mode produces energy, the energy can be used by 110 120 6SL3320-1TG31-2AA3
another Motor Module operating in motor mode. 132 150 6SL3320-1TG31-5AA3
Motor Modules are controlled by a Control Unit. 160 175 6SL3320-1TG31-8AA3

■ Design
200 215 6SL3320-1TG32-2AA3
250 260 6SL3320-1TG32-6AA3
The Motor Modules in the chassis format have the following 315 330 6SL3320-1TG33-3AA3
interfaces as standard:
400 410 6SL3320-1TG34-1AA3
• 1 motor connection
450 465 6SL3320-1TG34-7AA3
• 1 connection for the 24 V DC electronics power supply
560 575 6SL3320-1TG35-8AA3
• 1 DC link connection (DCP, DCN) for connecting to the supply
DC link 710 735 6SL3320-1TG37-4AA3

• 1 DC link connection (DCPA, DCNA) for connecting a Braking 800 810 6SL3320-1TG38-1AA3
Module 900 910 6SL3320-1TG38-8AA3
• 1 DC link connection (DCPS, DCNS) for connecting 1000 1025 6SL3320-1TG41-0AA3
a dv/dt filter 1200 1270 6SL3320-1TG41-3AA3
• 3 DRIVE-CLiQ sockets
Extended liability for defects
• 1 temperature sensor input for KTY84-130, Pt1000, PTC or
Pt100 (Pt1000 can be used from firmware V4.7 HF17 and Siemens offers for SINAMICS S120 chassis units an extended
higher) liability for defects/Service Protect up to 6½ years.
• 1 connection for Safe Brake Adapter Details can be found in chapter
• 1 connection for Safety Integrated Services and Documentation
• 2 PE/protective conductor connections Accessories for re-ordering
The status of the Motor Modules is indicated via three LEDs.
Description Article No.
The scope of supply of the Motor Modules includes: Dust protection blanking plugs 6SL3066-4CA00-0AA0
• DRIVE-CLiQ cable for connection to the Control Unit (50 units)

• DRIVE-CLiQ cable for connection to the next Motor Module For DRIVE-CLiQ port

• 1 set of warning labels in 30 languages For motor-side components and Braking Modules, see System
(BG, CN, CZ, DE, DK, EE, ES, FI, FR, GB, GR, HU, IE, IS, IT, components.
JP, KR, LT, LV, MT, NL, NO, PL, PT, RO, RU, SE, SI, SK, TR)

Siemens D 21.3 · 2022 3/39


© Siemens 2022

SINAMICS S120 Chassis Format Units


Air-cooled units
Motor Modules

■ Integration
The Motor Modules communicate with the higher-level control module via DRIVE-CLiQ. This Control Unit can either be a CU320-2 or
a SIMOTION D Control Unit.

X400 X401 X402

2
DRIVE-CLiQ socket

DRIVE-CLiQ socket

DRIVE-CLiQ socket
Motor Module
chassis format
DCP
DC link connection
DCN
3 Connection for DCPA
Braking Module DCNA =

Connection for DCPS =


dv/dt filter DCNS

-X9
1 P24 V -X2 PE
External
24 V DC 2 M
U2
3 =
Internal V2 M
4 ~ W2 3~
power
5 supply
6
Fan power supply terminal -F10
for sizes HX and JX. L1
The number of fans depends on the L2
frame size. -F11 Fan
-F20

-F21 Fan
Internal

-F10
Fan power supply terminal
for sizes FX and GX directly on the fuse
carrier -F11 Fan
-X41 Internal
4 +Temp
3 -Temp READY
LEDs

2 EP +24 V
1 EP M1 DC LINK
M
POWER OK
-X42
1 P24L
2 P24L
3 M
4 M IPD Card

-X46
1 BR output+
2 BR output-
3 FB input+
4 FB input-

G_D213_EN_00085d

Connection example of a Motor Module

3/40 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Chassis Format Units


Air-cooled units
Motor Modules

■ Technical specifications
General technical specifications
Electrical specifications
Efficiency >98.5 %
DC link voltage 510 ... 720 V DC (line voltage 380 ... 480 V 3 AC) or
(up to 2000 m (6562 ft) above sea level) 675 ... 1035 V DC (line voltage 500 ... 690 V 3 AC)
Output frequency 1)
• Control mode Servo 0 ... 550 Hz
• Control mode Vector 0 ... 550 Hz
• Control mode V/f 0 ... 550 Hz
Safety Integrated Safety Integrity Level 2 (SIL2) acc. to IEC 61508, Performance Level d (PLd) acc. to EN ISO 13849-1 and Control
Category 3 acc. to EN ISO 13849-1 3

1) Please note:
• The correlation between the maximum output frequency, pulse frequency
and current derating. Higher output frequencies on request. For further
information, see
https://support.industry.siemens.com/cs/document/104020669
• The correlation between the minimum output frequency and permissible
output current (current derating).
For additional information, please refer to the SINAMICS Low Voltage
Engineering Manual.

Siemens D 21.3 · 2022 3/41


© Siemens 2022

SINAMICS S120 Chassis Format Units


Air-cooled units
Motor Modules

■ Technical specifications
Line voltage 380 ... 480 V 3 AC Motor Modules
DC link voltage 510 ... 720 V DC
6SL3320- 6SL3320- 6SL3320- 6SL3320- 6SL3320-
1TE32-1AA3 1TE32-6AA3 1TE33-1AA3 1TE33-8AA3 1TE35-0AA3
Type rating
• At IL (50 Hz 400 V) 1) kW 110 132 160 200 250
• At IH (50 Hz 400 V) 1) kW 90 110 132 160 200
• At IL (60 Hz 460 V) 2) hp 150 200 250 300 400
• At IH (60 Hz 460 V) 2) hp 150 200 200 250 350
Output current

3 • Rated current IN O
• Base-load current IL 3)
A
A
210
205
260
250
310
302
380
370
490
477
• Base-load current IH 4) A 178 233 277 340 438
• Maximum current Imax O A 307 375 453 555 715
DC link current
• Rated current IN DC
when supplied via
- Basic/Smart Line Module A 252 312 372 456 588
- Active Line Module A 227 281 335 411 529
• Base-load current IL DC 3)
when supplied via
- Basic/Smart Line Module A 245 304 362 444 573
- Active Line Module A 221 273 326 400 515
• Base-load current IH DC 4)
when supplied via
- Basic/Smart Line Module A 224 277 331 405 523
- Active Line Module A 202 250 298 365 470
Current demand
• 24 V DC auxiliary power supply A 0.8 0.8 0.9 0.9 0.9
• 400 V AC A 0.63 1.13 1.8 1.8 1.8
DC link capacitance F 4200 5200 6300 7800 9600
Pulse frequency 5)
• Rated frequency kHz 2 2 2 2 2
• Pulse frequency, max.
- Without current derating kHz 2 2 2 2 2
- With current derating kHz 8 8 8 8 8
Power loss, max. 6)
• At 50 Hz 400 V kW 1.86 2.5 2.96 3.67 4.28
• At 60 Hz 460 V kW 1.94 2.6 3.1 3.8 4.5
Cooling air requirement m3/s 0.17 (6.00) 0.23 (8.12) 0.36 (12.7) 0.36 (12.7) 0.36 (12.7)
(ft3/s)
Sound pressure level LpA dB 64/67 71/71 69/73 69/73 69/73
(1 m) at 50/60 Hz
DC link connection M10 screw M10 screw M10 screw M10 screw M10 screw
DCP, DCN
• Conductor cross-section, max. (IEC) mm2 2 × 185 2 × 185 2 × 240 2 × 240 2 × 240
Connection for Braking Module M6 threaded bolt M6 threaded bolt M6 threaded bolt M6 threaded bolt M6 threaded bolt
DCPA, DCNA 7)
Connection for dv/dt filter M8 screw M8 screw M8 screw M8 screw M8 screw
DCPS, DCNS
• Conductor cross-section, max. (IEC) mm2 1 × 35 1 × 35 1 × 70 1 × 70 1 × 70
Motor connection M10 screw M10 screw M10 screw M10 screw M10 screw
U2, V2, W2
• Conductor cross-section, max. (IEC) mm2 2 × 185 2 × 185 2 × 240 2 × 240 2 × 240
Cable length, max. 8)
• Shielded m (ft) 300 (984) 300 (984) 300 (984) 300 (984) 300 (984)
• Unshielded m (ft) 450 (1476) 450 (1476) 450 (1476) 450 (1476) 450 (1476)

3/42 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Chassis Format Units


Air-cooled units
Motor Modules

■ Technical specifications
Line voltage 380 ... 480 V 3 AC Motor Modules
DC link voltage 510 ... 720 V DC
6SL3320- 6SL3320- 6SL3320- 6SL3320- 6SL3320-
1TE32-1AA3 1TE32-6AA3 1TE33-1AA3 1TE33-8AA3 1TE35-0AA3
PE1/GND connection M10 screw M10 screw M10 screw M10 screw M10 screw
• Conductor cross-section, max. (IEC) mm2 2 × 185 2 × 185 2 × 240 2 × 240 2 × 240
PE2/GND connection M10 screw M10 screw M10 screw M10 screw M10 screw
• Conductor cross-section, max. (IEC) mm2 2 × 185 2 × 185 2 × 240 2 × 240 2 × 240
Degree of protection IP20 IP20 IP20 IP20 IP20
Dimensions
• Width mm (in) 326 (12.8) 326 (12.8) 326 (12.8) 326 (12.8) 326 (12.8) 3
• Height mm (in) 1400 (55.1) 1400 (55.1) 1533 (60.4) 1533 (60.4) 1533 (60.4)
• Depth mm (in) 356 (14.0) 356 (14.0) 545 (21.5) 545 (21.5) 545 (21.5)
Weight, approx. kg (lb) 95 (209) 95 (209) 136 (300) 136 (300) 136 (300)
Frame size FX FX GX GX GX

1) 6)
Rated power of a typical 6-pole standard induction motor based on IL or IH The specified power loss represents the maximum value at 100 %
for 400 V 3 AC 50 Hz. utilization. The value is lower under normal operating conditions.
2) 7)
Rated power of a typical 6-pole standard induction motor based on IL or IH The connecting cables are included in the scope of supply of the Braking
for 460 V 3 AC 60 Hz. Module.
3) 8)
The base-load current IL is based on a duty cycle of 110 % for 60 s or Total of all motor cables and DC link. Longer cable lengths for specific
150 % for 10 s with a duty cycle duration of 300 s. configurations are available on request.
4)
The base-load current IH is based on a duty cycle of 150 % for 60 s or For additional information, please refer to the SINAMICS Low Voltage
160 % for 10 s with a duty cycle duration of 300 s. Engineering Manual.
5)
Information regarding the correlation between the pulse frequency and
maximum output current/output frequency is provided in the SINAMICS
Low Voltage Engineering Manual.

Siemens D 21.3 · 2022 3/43


© Siemens 2022

SINAMICS S120 Chassis Format Units


Air-cooled units
Motor Modules

■ Technical specifications
Line voltage 380 ... 480 V 3 AC Motor Modules
DC link voltage 510 ... 720 V DC
6SL3320-1TE36-1AA3 6SL3320-1TE37-5AA3 6SL3320-1TE38-4AA3
Type rating
• At IL (50 Hz 400 V) 1) kW 315 400 450
• At IH (50 Hz 400 V) 1) kW 250 315 400
• At IL (60 Hz 460 V) 2) hp 500 600 700
• At IH (60 Hz 460 V) 2) hp 350 450 600
Output current
• Rated current IN O A 605 745 840
3 • Base-load current IL 3)
• Base-load current IH 4)
A
A
590
460
725
570
820
700
• Maximum current Imax O A 885 1087 1230
DC link current
• Rated current IN DC
when supplied via
- Basic/Smart Line Module A 726 894 1008
- Active Line Module A 653 805 907
• Base-load current IL DC 3)
when supplied via
- Basic/Smart Line Module A 707 871 982
- Active Line Module A 636 784 884
• Base-load current IH DC 4)
when supplied via
- Basic/Smart Line Module A 646 795 897
- Active Line Module A 581 716 807
Current demand
• 24 V DC auxiliary power supply A 1.0 1.0 1.0
• 400 V AC A 3.6 3.6 3.6
DC link capacitance F 12600 15600 16800
Pulse frequency 5)
• Rated frequency kHz 1.25 1.25 1.25
• Pulse frequency, max.
- Without current derating kHz 1.25 1.25 1.25
- With current derating kHz 8 8 8
Power loss, max. 6)
• At 50 Hz 400 V kW 5.84 6.68 7.15
• At 60 Hz 460 V kW 6.3 7.3 7.8
Cooling air requirement m3/s 0.78 (27.5) 0.78 (27.5) 0.78 (27.5)
(ft3/s)
Sound pressure level LpA dB 70/73 70/73 70/73
(1 m) at 50/60 Hz
DC link connection 4 × hole for M10 4 × hole for M10 4 × hole for M10
DCP, DCN Busbar Busbar Busbar
Connection for Braking Module Connection for connection clip Connection for connection clip Connection for connection clip
DCPA, DCNA 7)
Connection for dv/dt filter M10 screw M10 screw M10 screw
DCPS, DCNS
• Conductor cross-section, max. (IEC) mm2 1 × 185 1 × 185 1 × 185
Motor connection 2 × M12 screw 2 × M12 screw 2 × M12 screw
U2, V2, W2
2
• Conductor cross-section, max. (IEC) mm 4 × 240 4 × 240 4 × 240
Cable length, max. 8)
• Shielded m (ft) 300 (984) 300 (984) 300 (984)
• Unshielded m (ft) 450 (1476) 450 (1476) 450 (1476)

3/44 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Chassis Format Units


Air-cooled units
Motor Modules

■ Technical specifications
Line voltage 380 ... 480 V 3 AC Motor Modules
DC link voltage 510 ... 720 V DC
6SL3320-1TE36-1AA3 6SL3320-1TE37-5AA3 6SL3320-1TE38-4AA3
PE1/GND connection M12 screw M12 screw M12 screw
• Conductor cross-section, max. (IEC) mm2 240 240 240
PE2/GND connection 2 × M12 screw 2 × M12 screw 2 × M12 screw
• Conductor cross-section, max. (IEC) mm2 2 × 240 2 × 240 2 × 240
Degree of protection IP00 IP00 IP00
Dimensions
• Width
• Height
mm (in) 503 (19.8)
mm (in) 1475 (58.1)
503 (19.8)
1475 (58.1)
503 (19.8)
1475 (58.1) 3
• Depth mm (in) 547 (21.5) 547 (21.5) 547 (21.5)
Weight, approx. kg (lb) 290 (639) 290 (639) 290 (639)
Frame size HX HX HX

1) 6)
Rated power of a typical 6-pole standard induction motor based on IL or IH The specified power loss represents the maximum value at 100 %
for 400 V 3 AC 50 Hz. utilization. The value is lower under normal operating conditions.
2) 7)
Rated power of a typical 6-pole standard induction motor based on IL or IH The connection clips are included in the scope of supply of the Braking
for 460 V 3 AC 60 Hz. Module.
3) 8)
The base-load current IL is based on a duty cycle of 110 % for 60 s or Total of all motor cables and DC link. Longer cable lengths for specific
150 % for 10 s with a duty cycle duration of 300 s. configurations are available on request.
4)
The base-load current IH is based on a duty cycle of 150 % for 60 s or For additional information, please refer to the SINAMICS Low Voltage
160 % for 10 s with a duty cycle duration of 300 s. Engineering Manual.
5)
Information regarding the correlation between the pulse frequency and
maximum output current/output frequency is provided in the SINAMICS
Low Voltage Engineering Manual.

Siemens D 21.3 · 2022 3/45


© Siemens 2022

SINAMICS S120 Chassis Format Units


Air-cooled units
Motor Modules

■ Technical specifications
Line voltage 380 ... 480 V 3 AC Motor Modules
DC link voltage 510 ... 720 V DC
6SL3320-1TE41-0AA3 6SL3320-1TE41-2AA3 6SL3320-1TE41-4AA3
Type rating
• At IL (50 Hz 400 V) 1) kW 560 710 800
• At IH (50 Hz 400 V) 1) kW 450 560 710
• At IL (60 Hz 460 V) 2) hp 800 1000 1150
• At IH (60 Hz 460 V) 2) hp 700 900 1000
Output current
• Rated current IN O A 985 1260 1405
3 • Base-load current IL 3)
• Base-load current IH 4)
A
A
960
860
1230
1127
1370
1257
• Maximum current Imax O A 1440 1845 2055
DC link current
• Rated current IN DC
when supplied via
- Basic/Smart Line Module A 1182 1512 1686
- Active Line Module A 1064 1361 1517
• Base-load current IL DC 3)
when supplied via
- Basic/Smart Line Module A 1152 1474 1643
- Active Line Module A 1037 1326 1479
• Base-load current IH DC 4)
when supplied via
- Basic/Smart Line Module A 1051 1345 1500
- Active Line Module A 946 1211 1350
Current demand
• 24 V DC auxiliary power supply A 1.25 1.4 1.4
• 400 V AC A 5.4 5.4 5.4
DC link capacitance F 18900 26100 28800
Pulse frequency 5)
• Rated frequency kHz 1.25 1.25 1.25
• Pulse frequency, max.
- Without current derating kHz 1.25 1.25 1.25
- With current derating kHz 8 8 8
Power loss, max. 6)
• At 50 Hz 400 V kW 9.5 11.1 12.0
• At 60 Hz 460 V kW 10.2 12.0 13.0
Cooling air requirement m3/s 1.08 (38.1) 1.08 (38.1) 1.08 (38.1)
(ft3/s)
Sound pressure level LpA dB 71/73 71/73 71/73
(1 m) at 50/60 Hz
DC link connection 4 × hole for M10 4 × hole for M10 4 × hole for M10
DCP, DCN Busbar Busbar Busbar
Connection for Braking Module Connection for connection clip Connection for connection clip Connection for connection clip
DCPA, DCNA 7)
Connection for dv/dt filter 2 x M10 screw 2 x M10 screw 2 x M10 screw
DCPS, DCNS
• Conductor cross-section, max. (IEC) mm2 2 × 185 2 × 185 2 × 185
Motor connection 3 × M12 screw 3 × M12 screw 3 × M12 screw
U2, V2, W2
2
• Conductor cross-section, max. (IEC) mm 6 × 240 6 × 240 6 × 240
Cable length, max. 8)
• Shielded m (ft) 300 (984) 300 (984) 300 (984)
• Unshielded m (ft) 450 (1476) 450 (1476) 450 (1476)

3/46 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Chassis Format Units


Air-cooled units
Motor Modules

■ Technical specifications
Line voltage 380 ... 480 V 3 AC Motor Modules
DC link voltage 510 ... 720 V DC
6SL3320-1TE41-0AA3 6SL3320-1TE41-2AA3 6SL3320-1TE41-4AA3
PE1/GND connection M12 screw M12 screw M12 screw
• Conductor cross-section, max. (IEC) mm2 240 240 240
PE2/GND connection 3 × M12 screw 3 × M12 screw 3 × M12 screw
• Conductor cross-section, max. (IEC) mm2 3 × 240 3 × 240 3 × 240
Degree of protection IP00 IP00 IP00
Dimensions
• Width
• Height
mm (in) 704 (27.7)
mm (in) 1475 (58.1)
704 (27.7)
1475 (58.1)
704 (27.7)
1475 (58.1) 3
• Depth mm (in) 549 (21.6) 549 (21.6) 549 (21.6)
Weight, approx. kg (lb) 450 (992) 450 (992) 450 (992)
Frame size JX JX JX

1) 6)
Rated power of a typical 6-pole standard induction motor based on IL or IH The specified power loss represents the maximum value at 100 %
for 400 V 3 AC 50 Hz. utilization. The value is lower under normal operating conditions.
2) 7)
Rated power of a typical 6-pole standard induction motor based on IL or IH The connection clips are included in the scope of supply of the Braking
for 460 V 3 AC 60 Hz. Module.
3) 8)
The base-load current IL is based on a duty cycle of 110 % for 60 s or Total of all motor cables and DC link. Longer cable lengths for specific
150 % for 10 s with a duty cycle duration of 300 s. configurations are available on request.
4)
The base-load current IH is based on a duty cycle of 150 % for 60 s or For additional information, please refer to the SINAMICS Low Voltage
160 % for 10 s with a duty cycle duration of 300 s. Engineering Manual.
5)
Information regarding the correlation between the pulse frequency and
maximum output current/output frequency is provided in the SINAMICS
Low Voltage Engineering Manual.

Siemens D 21.3 · 2022 3/47


© Siemens 2022

SINAMICS S120 Chassis Format Units


Air-cooled units
Motor Modules

■ Technical specifications
Line voltage 500 ... 690 V 3 AC Motor Modules
DC link voltage 675 ... 1035 V DC
6SL3320-1TG28-5AA3 6SL3320-1TG31-0AA3 6SL3320-1TG31-2AA3 6SL3320-1TG31-5AA3
Type rating
• At IL (50 Hz 690 V) 1) kW 75 90 110 132
• At IH (50 Hz 690 V) 1) kW 55 75 90 110
• At IL (50 Hz 500 V) 1) kW 55 55 75 90
• At IH (50 Hz 500 V) 1) kW 45 55 75 90
• At IL (60 Hz 575 V) 2) hp 75 75 100 150
• At IH (60 Hz 575 V) 2) hp 75 75 100 125

3 Output current
• Rated current IN O A 85 100 120 150
• Base-load current IL 3) A 80 95 115 142
• Base-load current IH 4) A 76 89 107 134
• Maximum current Imax O A 120 142 172 213
DC link current
• Rated current IN DC
when supplied via
- Basic/Smart Line Module A 102 120 144 180
- Active Line Module A 92 108 130 162
• Base-load current IL DC 3)
when supplied via
- Basic/Smart Line Module A 99 117 140 175
- Active Line Module A 89 105 126 157
• Base-load current IH DC 4)
when supplied via
- Basic/Smart Line Module A 90 106 128 160
- Active Line Module A 81 96 115 144
Current demand
• 24 V DC auxiliary power supply A 0.8 0.8 0.8 0.8
• 500 V AC A 0.7 0.7 0.7 0.7
• 690 V AC A 0.4 0.4 0.4 0.4
DC link capacitance F 1200 1200 1600 2800
Pulse frequency 5)
• Rated frequency kHz 1.25 1.25 1.25 1.25
• Pulse frequency, max.
- Without current derating kHz 1.25 1.25 1.25 1.25
- With current derating kHz 7.5 7.5 7.5 7.5
Power loss, max. 6)
• At 50 Hz 690 V kW 1.17 1.43 1.89 1.8
• At 60 Hz 575 V kW 1.1 1.3 1.77 1.62
Cooling air requirement m3/s 0.17 (6.00) 0.17 (6.00) 0.17 (6.00) 0.17 (6.00)
(ft3/s)
Sound pressure level LpA dB 64/67 64/67 64/67 64/67
(1 m) at 50/60 Hz
DC link connection M10 screw M10 screw M10 screw M10 screw
DCP, DCN
• Conductor cross-section, max. (IEC) mm2 2 × 185 2 × 185 2 × 185 2 × 185
Connection for Braking Module M6 stud M6 stud M6 stud M6 stud
DCPA, DCNA 7)
Connection for dv/dt filter M8 screw M8 screw M8 screw M8 screw
DCPS, DCNS
• Conductor cross-section, max. (IEC) mm2 1 × 70 1 × 70 1 × 70 1 × 70
Motor connection M10 screw M10 screw M10 screw M10 screw
U2, V2, W2
• Conductor cross-section, max. (IEC) mm2 2 × 185 2 × 185 2 × 185 2 × 185
Cable length, max. 8)
• Shielded m (ft) 300 (984) 300 (984) 300 (984) 300 (984)
• Unshielded m (ft) 450 (1476) 450 (1476) 450 (1476) 450 (1476)

3/48 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Chassis Format Units


Air-cooled units
Motor Modules

■ Technical specifications
Line voltage 500 ... 690 V 3 AC Motor Modules
DC link voltage 675 ... 1035 V DC
6SL3320-1TG28-5AA3 6SL3320-1TG31-0AA3 6SL3320-1TG31-2AA3 6SL3320-1TG31-5AA3
PE1/GND connection M10 screw M10 screw M10 screw M10 screw
• Conductor cross-section, max. (IEC) mm2 2 × 185 2 × 185 2 × 185 2 × 185
PE2/GND connection M10 screw M10 screw M10 screw M10 screw
• Conductor cross-section, max. (IEC) mm2 2 × 185 2 × 185 2 × 185 2 × 185
Degree of protection IP20 IP20 IP20 IP20
Dimensions
• Width
• Height
mm (in) 326 (12.8)
mm (in) 1400 (55.1)
326 (12.8)
1400 (55.1)
326 (12.8)
1400 (55.1)
326 (12.8)
1400 (55.1) 3
• Depth mm (in) 356 (14.0) 356 (14.0) 356 (14.0) 356 (14.0)
Weight, approx. kg (lb) 95 (209) 95 (209) 95 (209) 95 (209)
Frame size FX FX FX FX

1) 6)
Rated power of a typical 6-pole standard induction motor based on IL or IH The specified power loss represents the maximum value at 100 %
for 500 V or 690 V 3 AC 50 Hz. utilization. The value is lower under normal operating conditions.
2) 7)
Rated power of a typical 6-pole standard induction motor based on IL or IH The connecting cables are included in the scope of supply of the Braking
for 575 V 3 AC 60 Hz. Module.
3) 8)
The base-load current IL is based on a duty cycle of 110 % for 60 s or Total of all motor cables and DC link. Longer cable lengths for specific
150 % for 10 s with a duty cycle duration of 300 s. configurations are available on request.
4)
The base-load current IH is based on a duty cycle of 150 % for 60 s or For additional information, please refer to the SINAMICS Low Voltage
160 % for 10 s with a duty cycle duration of 300 s. Engineering Manual.
5)
Information regarding the correlation between the pulse frequency and
maximum output current/output frequency is provided in the SINAMICS
Low Voltage Engineering Manual.

Siemens D 21.3 · 2022 3/49


© Siemens 2022

SINAMICS S120 Chassis Format Units


Air-cooled units
Motor Modules

■ Technical specifications
Line voltage 500 ... 690 V 3 AC Motor Modules
DC link voltage 675 ... 1035 V DC
6SL3320-1TG31-8AA3 6SL3320-1TG32-2AA3 6SL3320-1TG32-6AA3 6SL3320-1TG33-3AA3
Type rating
• At IL (50 Hz 690 V) 1) kW 160 200 250 315
• At IH (50 Hz 690 V) 1) kW 132 160 200 250
• At IL (50 Hz 500 V) 1) kW 110 132 160 200
• At IH (50 Hz 500 V) 1) kW 90 110 132 160
• At IL (60 Hz 575 V) 2) hp 150 200 250 300
• At IH (60 Hz 575 V) 2) hp 150 200 200 250

3 Output current
• Rated current IN O A 175 215 260 330
• Base-load current IL 3) A 171 208 250 320
• Base-load current IH 4) A 157 192 233 280
• Maximum current Imax O A 255 312 375 480
DC link current
• Rated current IN DC
when supplied via
- Basic/Smart Line Module A 210 258 312 396
- Active Line Module A 189 232 281 356
• Base-load current IL DC 3)
when supplied via
- Basic/Smart Line Module A 204 251 304 386
- Active Line Module A 184 226 273 347
• Base-load current IH DC 4)
when supplied via
- Basic/Smart Line Module A 186 229 277 352
- Active Line Module A 168 206 250 316
Current demand
• 24 V DC auxiliary power supply A 0.9 0.9 0.9 0.9
• 500 V AC A 1.5 1.5 1.5 1.5
• 690 V AC A 1.0 1.0 1.0 1.0
DC link capacitance F 2800 2800 3900 4200
Pulse frequency 5)
• Rated frequency kHz 1.25 1.25 1.25 1.25
• Pulse frequency, max.
- Without current derating kHz 1.25 1.25 1.25 1.25
- With current derating kHz 7.5 7.5 7.5 7.5
Power loss, max. 6)
• At 50 Hz 690 V kW 2.67 3.09 3.62 4.34
• At 60 Hz 575 V kW 2.5 2.91 3.38 3.98
Cooling air requirement m3/s 0.36 (12.7) 0.36 (12.7) 0.36 (12.7) 0.36 (12.7)
(ft3/s)
Sound pressure level LpA dB 69/73 69/73 69/73 69/73
(1 m) at 50/60 Hz
DC link connection M10 screw M10 screw M10 screw M10 screw
DCP, DCN
• Conductor cross-section, max. (IEC) mm2 2 × 240 2 × 240 2 × 240 2 × 240
Connection for Braking Module M6 stud M6 stud M6 stud M6 stud
DCPA, DCNA 7)
Connection for dv/dt filter M8 screw M8 screw M8 screw M8 screw
DCPS, DCNS
• Conductor cross-section, max. (IEC) mm2 1 × 70 1 × 70 1 × 70 1 × 70
Motor connection M10 screw M10 screw M10 screw M10 screw
U2, V2, W2
• Conductor cross-section, max. (IEC) mm2 2 × 240 2 × 240 2 × 240 2 × 240
Cable length, max. 8)
• Shielded m (ft) 300 (984) 300 (984) 300 (984) 300 (984)
• Unshielded m (ft) 450 (1476) 450 (1476) 450 (1476) 450 (1476)

3/50 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Chassis Format Units


Air-cooled units
Motor Modules

■ Technical specifications
Line voltage 500 ... 690 V 3 AC Motor Modules
DC link voltage 675 ... 1035 V DC
6SL3320-1TG31-8AA3 6SL3320-1TG32-2AA3 6SL3320-1TG32-6AA3 6SL3320-1TG33-3AA3
PE1/GND connection M10 screw M10 screw M10 screw M10 screw
• Conductor cross-section, max. (IEC) mm2 2 × 240 2 × 240 2 × 240 2 × 240
PE2/GND connection M10 screw M10 screw M10 screw M10 screw
• Conductor cross-section, max. (IEC) mm2 2 × 240 2 × 240 2 × 240 2 × 240
Degree of protection IP20 IP20 IP20 IP20
Dimensions
• Width
• Height
mm (in) 326 (12.8)
mm (in) 1533 (60.4)
326 (12.8)
1533 (60.4)
326 (12.8)
1533 (60.4)
326 (12.8)
1533 (60.4) 3
• Depth mm (in) 545 (21.5) 545 (21.5) 545 (21.5) 545 (21.5)
Weight, approx. kg (lb) 136 (300) 136 (300) 136 (300) 136 (300)
Frame size GX GX GX GX

1) 6)
Rated power of a typical 6-pole standard induction motor based on IL or IH The specified power loss represents the maximum value at 100 %
for 500 V or 690 V 3 AC 50 Hz. utilization. The value is lower under normal operating conditions.
2) 7)
Rated power of a typical 6-pole standard induction motor based on IL or IH The connecting cables are included in the scope of supply of the Braking
for 575 V 3 AC 60 Hz. Module.
3) 8)
The base-load current IL is based on a duty cycle of 110 % for 60 s or Total of all motor cables and DC link. Longer cable lengths for specific
150 % for 10 s with a duty cycle duration of 300 s. configurations are available on request.
4)
The base-load current IH is based on a duty cycle of 150 % for 60 s or For additional information, please refer to the SINAMICS Low Voltage
160 % for 10 s with a duty cycle duration of 300 s. Engineering Manual.
5)
Information regarding the correlation between the pulse frequency and
maximum output current/output frequency is provided in the SINAMICS
Low Voltage Engineering Manual.

Siemens D 21.3 · 2022 3/51


© Siemens 2022

SINAMICS S120 Chassis Format Units


Air-cooled units
Motor Modules

■ Technical specifications
Line voltage 500 ... 690 V 3 AC Motor Modules
DC link voltage 675 ... 1035 V DC
6SL3320-1TG34-1AA3 6SL3320-1TG34-7AA3 6SL3320-1TG35-8AA3 6SL3320-1TG37-4AA3
Type rating
• At IL (50 Hz 690 V) 1) kW 400 450 560 710
• At IH (50 Hz 690 V) 1) kW 315 400 450 630
• At IL (50 Hz 500 V) 1) kW 250 315 400 500
• At IH (50 Hz 500 V) 1) kW 200 250 315 450
• At IL (60 Hz 575 V) 2) hp 400 450 600 700
• At IH (60 Hz 575 V) 2) hp 350 450 500 700

3 Output current
• Rated current IN O A 410 465 575 735
• Base-load current IL 3) A 400 452 560 710
• Base-load current IH 4) A 367 416 514 657
• Maximum current Imax O A 600 678 840 1065
DC link current
• Rated current IN DC
when supplied via
- Basic/Smart Line Module A 492 558 690 882
- Active Line Module A 443 502 621 794
• Base-load current IL DC 3)
when supplied via
- Basic/Smart Line Module A 479 544 672 859
- Active Line Module A 431 489 605 774
• Base-load current IH DC 4)
when supplied via
- Basic/Smart Line Module A 437 496 614 784
- Active Line Module A 394 446 552 706
Current demand
• 24 V DC auxiliary power supply A 1.0 1.0 1.0 1.25
• 500 V AC A 3.0 3.0 3.0 4.4
• 690 V AC A 2.1 2.1 2.1 3.1
DC link capacitance F 7400 7400 7400 11100
Pulse frequency 5)
• Rated frequency kHz 1.25 1.25 1.25 1.25
• Pulse frequency, max.
- Without current derating kHz 1.25 1.25 1.25 1.25
- With current derating kHz 7.5 7.5 7.5 7.5
Power loss, max. 6)
• At 50 Hz 690 V kW 6.13 6.80 10.3 10.9
• At 60 Hz 575 V kW 5.71 6.32 9.7 10
Cooling air requirement m3/s 0.78 (27.5) 0.78 (27.5) 0.78 (27.5) 1.08 (38.1)
(ft3/s)
Sound pressure level LpA dB 70/73 70/73 70/73 71/73
(1 m) at 50/60 Hz
DC link connection 4 × hole for M10 4 × hole for M10 4 × hole for M10 4 × hole for M10
DCP, DCN Busbar Busbar Busbar Busbar
Connection for Braking Module M8 stud M8 stud M8 stud M8 stud
DCPA, DCNA 7)
Connection for dv/dt filter M10 screw M10 screw M10 screw 2 x M10 screw
DCPS, DCNS
• Conductor cross-section, max. (IEC) mm2 1 × 185 1 × 185 1 × 185 2 × 185
Motor connection 2 × M12 screw 2 × M12 screw 2 × M12 screw 3 × M12 screw
U2, V2, W2
2
• Conductor cross-section, max. (IEC) mm 4 × 240 4 × 240 4 × 240 6 × 240
Cable length, max. 8)
• Shielded m (ft) 300 (984) 300 (984) 300 (984) 300 (984)
• Unshielded m (ft) 450 (1476) 450 (1476) 450 (1476) 450 (1476)

3/52 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Chassis Format Units


Air-cooled units
Motor Modules

■ Technical specifications
Line voltage 500 ... 690 V 3 AC Motor Modules
DC link voltage 675 ... 1035 V DC
6SL3320-1TG34-1AA3 6SL3320-1TG34-7AA3 6SL3320-1TG35-8AA3 6SL3320-1TG37-4AA3
PE1/GND connection M12 screw M12 screw M12 screw M12 screw
• Conductor cross-section, max. (IEC) mm2 240 240 240 240
PE2/GND connection 2 × M12 screw 2 × M12 screw 2 × M12 screw 3 × M12 screw
• Conductor cross-section, max. (IEC) mm2 2 × 240 2 × 240 2 × 240 3 × 240
Degree of protection IP00 IP00 IP00 IP00
Dimensions
• Width
• Height
mm (in) 503 (19.8)
mm (in) 1475 (58.1)
503 (19.8)
1475 (58.1)
503 (19.8)
1475 (58.1)
704 (27.7)
1475 (58.1) 3
• Depth mm (in) 547 (21.5) 547 (21.5) 547 (21.5) 550 (21.7)
Weight, approx. kg (lb) 290 (639) 290 (639) 290 (639) 450 (992)
Frame size HX HX HX JX

1) 6)
Rated power of a typical 6-pole standard induction motor based on IL or IH The specified power loss represents the maximum value at 100 %
for 500 V or 690 V 3 AC 50 Hz. utilization. The value is lower under normal operating conditions.
2) 7)
Rated power of a typical 6-pole standard induction motor based on IL or IH The connection clips are included in the scope of supply of the Braking
for 575 V 3 AC 60 Hz. Module.
3) 8)
The base-load current IL is based on a duty cycle of 110 % for 60 s or Total of all motor cables and DC link. Longer cable lengths for specific
150 % for 10 s with a duty cycle duration of 300 s. configurations are available on request.
4)
The base-load current IH is based on a duty cycle of 150 % for 60 s or For additional information, please refer to the SINAMICS Low Voltage
160 % for 10 s with a duty cycle duration of 300 s. Engineering Manual.
5)
Information regarding the correlation between the pulse frequency and
maximum output current/output frequency is provided in the SINAMICS
Low Voltage Engineering Manual.

Siemens D 21.3 · 2022 3/53


© Siemens 2022

SINAMICS S120 Chassis Format Units


Air-cooled units
Motor Modules

■ Technical specifications
Line voltage 500 ... 690 V 3 AC Motor Modules
DC link voltage 675 ... 1035 V DC
6SL3320-1TG38-1AA3 6SL3320-1TG38-8AA3 6SL3320-1TG41-0AA3 6SL3320-1TG41-3AA3
Type rating
• At IL (50 Hz 690 V) 1) kW 800 900 1000 1200
• At IH (50 Hz 690 V) 1) kW 710 800 900 1000
• At IL (50 Hz 500 V) 1) kW 560 630 710 900
• At IH (50 Hz 500 V) 1) kW 500 560 630 800
• At IL (60 Hz 575 V) 2) hp 800 900 1000 1250
• At IH (60 Hz 575 V) 2) hp 700 800 900 1000

3 Output current
• Rated current IN O A 810 910 1025 1270
• Base-load current IL 3) A 790 880 1000 1230
• Base-load current IH 4) A 724 814 917 1136
• Maximum current Imax O A 1185 1320 1500 1845
DC link current
• Rated current IN DC
when supplied via
- Basic/Smart Line Module A 972 1092 1230 1524
- Active Line Module A 875 983 1107 1372
• Base-load current IL DC 3)
when supplied via
- Basic/Smart Line Module A 947 1064 1199 1485
- Active Line Module A 853 958 1079 1337
• Base-load current IH DC 4)
when supplied via
- Basic/Smart Line Module A 865 971 1094 1356
- Active Line Module A 778 874 985 1221
Current demand
• 24 V DC auxiliary power supply A 1.25 1.4 1.4 1.4
• 500 V AC A 4.4 4.4 4.4 4.4
• 690 V AC A 3.1 3.1 3.1 3.1
DC link capacitance F 11100 14400 14400 19200
Pulse frequency 5)
• Rated frequency kHz 1.25 1.25 1.25 1.25
• Pulse frequency, max.
- Without current derating kHz 1.25 1.25 1.25 1.25
- With current derating kHz 7.5 7.5 7.5 7.5
Power loss, max. 6)
• At 50 Hz 690 V kW 11.5 11.7 13.2 16.0
• At 60 Hz 575 V kW 10.5 10.6 12.0 14.2
Cooling air requirement m3/s 1.08 (38.1) 1.08 (38.1) 1.08 (38.1) 1.08 (38.1)
(ft3/s)
Sound pressure level LpA dB 71/73 71/73 71/73 71/73
(1 m) at 50/60 Hz
DC link connection 4 × hole for M10 4 × hole for M10 4 × hole for M10 4 × hole for M10
DCP, DCN Busbar Busbar Busbar Busbar
Connection for Braking Module M8 stud M8 stud M8 stud M8 stud
DCPA, DCNA 7)
Connection for dv/dt filter 2 x M10 screw 2 x M10 screw 2 x M10 screw 2 x M10 screw
DCPS, DCNS
• Conductor cross-section, max. (IEC) mm2 2 × 185 2 × 185 2 × 185 2 × 185
Motor connection 3 × M12 screw 3 × M12 screw 3 × M12 screw 3 × M12 screw
U2, V2, W2
2
• Conductor cross-section, max. (IEC) mm 6 × 240 6 × 240 6 × 240 6 × 240
Cable length, max. 8)
• Shielded m (ft) 300 (984) 300 (984) 300 (984) 300 (984)
• Unshielded m (ft) 450 (1476) 450 (1476) 450 (1476) 450 (1476)

3/54 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Chassis Format Units


Air-cooled units
Motor Modules

■ Technical specifications
Line voltage 500 ... 690 V 3 AC Motor Modules
DC link voltage 675 ... 1035 V DC
6SL3320-1TG38-1AA3 6SL3320-1TG38-8AA3 6SL3320-1TG41-0AA3 6SL3320-1TG41-3AA3
PE1/GND connection M12 screw M12 screw M12 screw M12 screw
• Conductor cross-section, max. (IEC) mm2 240 240 240 240
PE2/GND connection 3 × M12 screw 3 × M12 screw 3 × M12 screw 3 × M12 screw
• Conductor cross-section, max. (IEC) mm2 3 × 240 3 × 240 3 × 240 3 × 240
Degree of protection IP00 IP00 IP00 IP00
Dimensions
• Width
• Height
mm (in) 704 (27.7)
mm (in) 1475 (58.1)
704 (27.7)
1475 (58.1)
704 (27.7)
1475 (58.1)
704 (27.7)
1475 (58.1) 3
• Depth mm (in) 550 (21.7) 550 (21.7) 550 (21.7) 550 (21.7)
Weight, approx. kg (lb) 450 (992) 450 (992) 450 (992) 450 (992)
Frame size JX JX JX JX

1) 6)
Rated power of a typical 6-pole standard induction motor based on IL or IH The specified power loss represents the maximum value at 100 %
for 500 V or 690 V 3 AC 50 Hz. utilization. The value is lower under normal operating conditions.
2) 7)
Rated power of a typical 6-pole standard induction motor based on IL or IH The connection clips are included in the scope of supply of the Braking
for 575 V 3 AC 60 Hz. Module.
3) 8)
The base-load current IL is based on a duty cycle of 110 % for 60 s or Total of all motor cables and DC link. Longer cable lengths for specific
150 % for 10 s with a duty cycle duration of 300 s. configurations are available on request.
4)
The base-load current IH is based on a duty cycle of 150 % for 60 s or For additional information, please refer to the SINAMICS Low Voltage
160 % for 10 s with a duty cycle duration of 300 s. Engineering Manual.
5)
Information regarding the correlation between the pulse frequency and
maximum output current/output frequency is provided in the SINAMICS
Low Voltage Engineering Manual.

Siemens D 21.3 · 2022 3/55


© Siemens 2022

SINAMICS S120 Chassis Format Units


Air-cooled units
Mounting device for power blocks

■ Overview ■ Selection and ordering data


Description Article No.
Mounting device 6SL3766-1FA00-0AA0
for installing and removing power blocks

Power block mounting device for installing and removing the


power blocks for the Basic Line Modules, Smart Line Modules,
Active Line Modules, Power Modules, and Motor Modules in
chassis format.
The mounting device is a mounting aid. It is placed in front of the
module and attached to the module. The telescopic rails allow
the device to be adjusted to the installation height of the power
blocks.
Once the mechanical and electrical connections have been
released, the Power block can be removed from the module.
The power block is guided and supported by the guide rails on
the handling device.

3/56 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Chassis Format Units


Liquid-cooled units

■ Overview
The product portfolio includes the following liquid-cooled
SINAMICS S120 chassis units:
• Power Modules
• Basic Line Modules
• Active Line Modules
• Active Interface Modules
• Motor Modules
The associated system components such as line filters, line
reactors, motor reactors, dv/dt filters plus VPL and sine-wave
filters are air-cooled. Active Interface Modules are available in
air-cooled and liquid-cooled versions.
3
Highlights of the liquid-cooled units
• Up to a 60 % smaller footprint than air-cooled drive converters
• All main components such as power semiconductors, DC link
capacitors and balancing resistors are cooled by the cooling
circuit
• Only a low flow rate is required
• Uniform pressure drop of 0.7 bar
• Automatic protective functions
• Nickel-plated busbars
• Low noise
The SINAMICS S120 liquid-cooled units are specifically
designed to address the requirements relating to liquid cooling; • Compatible with all components and functions and tools of the
they are characterized by their high power density and SINAMICS system family
optimized footprint. Liquid cooling dissipates heat much more • The power rating can be extended by connecting units in
efficiently than air cooling systems. As a result, liquid-cooled parallel
units are much more compact than air-cooled units with the • No equipment fans
same power rating. Since the heat losses generated by the
electronic components are almost completely dissipated by Cabinet units in liquid-cooled version
the liquid coolant, only very small cooling fans are required. This
means that the devices are quiet in operation. Due to their Liquid-cooled SINAMICS S120 units are also available as
compact dimensions and almost negligible cooling air cabinet units, including cooling system (Heat Exchanger
requirement, liquid-cooled units are the preferred solution Module). See section SINAMICS S120 Cabinet Modules 
wherever installation space is restricted and/or the ambient Liquid-cooled units.
operating conditions are rough.
Control cabinets with liquid cooling are easy to implement
as sealed units with degrees of protection of IP55.

Siemens D 21.3 · 2022 3/57


© Siemens 2022

SINAMICS S120 Chassis Format Units


Liquid-cooled units

■ Overview
Line Module Motor Module Motor Module Motor Module
Pressure-relief valve max.
system pressure 600 kPa
Air/
water cooler
or
Water/
water cooler

3 3-way
Controller valve
TI
Temp

TI Pressure
Ambient air Filter PI
Ambient Expan-
humidity sion
tank
Pumps

Flow Temp
TI

FA
G_D213_EN_00034a

Example of a drive line-up with SINAMICS S120 liquid-cooled units

■ Technical specifications
General technical specifications
Unless clearly specified otherwise, the following technical data are valid for all the following components of the liquid-cooled
SINAMICS S120 drive system in chassis format.
Electrical specifications
Line voltages 380 ... 480 V 3 AC ±10 % (-15 % <1 min)
500 ... 690 V 3 AC ±10 % (-15 % <1 min)
Line supply types Grounded TN/TT systems and non-grounded IT systems
Line frequency 47 ... 63 Hz
Overvoltage category III acc. to EN 61800-5-1
Electronics power supply 24 V DC, -15 % +20 %
implemented as PELV circuit in accordance with EN 61800-5-1
Ground = negative pole grounded via the electronics
Rated short-circuit current
per IEC, in conjunction with the specified
fuses or circuit breakers
• 1.1 ... 447 kW 65 kA
• 448 ... 671 kW 84 kA
• 672 ... 1193 kW 170 kA
• > 1194 kW 200 kA
Rated short-circuit current SCCR
(Short Circuit Current Rating)
according to UL508C (up to 600 V), in con-
junction with the specified fuses or circuit
breakers
• 1.1 ... 447 kW 65 kA
• 448 ... 671 kW 84 kA
• 672 ... 1193 kW 170 kA
• > 1194 kW 200 kA

3/58 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Chassis Format Units


Liquid-cooled units

■ Technical specifications
Electrical specifications
Control method Vector/Servo control with and without encoder or V/f control
Fixed speeds 15 fixed speeds plus 1 minimum speed, parameterizable (in the default setting, 3 fixed setpoints plus 1 minimum
speed are selectable using terminal strip/PROFIBUS/PROFINET)
Skippable speed ranges 4, parameterizable
Setpoint resolution 0.001 rpm digital (14 bits + sign)
12 bits analog
Braking operation With Active Line Modules, four-quadrant operation as standard (energy recovery).
With Basic Line Modules, two-quadrant operation as standard, braking by means of a Motor Module.
Mechanical specifications
Degree of protection IP00 (IP20, without taking into account the connecting busbars)
3
Protection class I acc. to EN 61800-5-1
Touch protection EN 50274/DGUV regulation 3 when used as intended
Cooling method Liquid cooling with integrated heat exchanger in aluminum or stainless steel version
Ambient conditions Storage 1) Transport 1) Operation
Ambient temperature (air) -25 ... +55 °C (-13 ... 131 °F) -25 ... +70 °C (-13 ... +158 °F) Line-side components, Power Mod-
Class 1K4 Class 2K4 ules, Line Modules and Motor Mod-
acc. to EN 60721-3-1 (1997) acc. to EN 60721-3-2 (1997) ules:
0 ... 45 °C (32 ... 113 °F) without
derating
>45 ... 50 °C (113 ... 122 °F) see
derating characteristics
Control Units, supplementary system
components, and Sensor Modules:
0 ... 55 °C (32 ... 131 °F)
(for operation in a control cabinet)
DC link components and motor-side
components:
0 ... 55 °C (32 ... 131 °F)
Relative humidity 5 ... 95 % Max. 95 % at 40 °C (104 °F) 5 ... 95 %
Condensation, splashwater, and ice forma- Class 1K4 Class 2K4 Class 3K3
tion not permitted (EN 60204, Part 1) acc. to EN 60721-3-1 (1997) acc. to EN 60721-3-2 (1997) acc. to EN 60721-3-3 (2002)
Environmental class/harmful chemical Class 1C2 Class 2C2 Class 3C2
substances acc. to EN 60721-3-1 (1997) acc. to EN 60721-3-2 (1997) acc. to EN 60721-3-3 (2002)
Organic/biological influences Class 1B1 Class 2B1 Class 3B1
acc. to EN 60721-3-1 (1997) acc. to EN 60721-3-2 (1997) acc. to EN 60721-3-3 (2002)
Mechanically active substances Class 1S1 Class 2S1 Class 3S1
acc. to EN 60721-3-1 (1997) acc. to EN 60721-3-2 (1997) acc. to EN 60721-3-3 (2002)
Degree of pollution 2 acc. to IEC/EN 61800-5-1
Installation altitude Up to 2000 m (6562 ft) above sea level without derating,
> 2000 m (6562 ft) above sea level, refer to the derating data
Mechanical stability Storage 1) Transport 1) Operation
Vibratory load Class 2M2 Test values
acc. to EN 60721-3-2 (1997) acc. to EN 60068-2-6 test Fc:
• 10 ... 58 Hz with constant
deflection 0.075 mm
• 58 ... 150 Hz with constant
acceleration 9.81 m/s2 (1 × g)
Shock load Class 2M2 Test values
acc. to EN 60721-3-2 (1997) acc. to EN 60068-2-27 test Ea:
98 m/s2 (10 × g)/20 ms
Compliance with standards
Conformances/certificates of suitability, CE (EMC Directive 2014/30/EU, Low Voltage Directive 2014/35/EU, and Machinery Directive 2006/42/EC for
according to functional safety)
RCM, RoHS II,
marine certification DNV (Type approval)
Green passport: The article number 6SL3095-5AA00-0BG0 creates a form for the material declaration according
to Green Passport.
The subject matter of the declaration described is in line with the guidelines for the establishment of the inventory
of hazardous materials - Resolution MEPC.269(68).
cULus (only for devices connected to line voltages 380 ... 480 V 3 AC and 500 ... 600 V 3 AC)
Radio interference suppression SINAMICS S120 chassis format units are not designed for connection to the public grid (first environment). Radio
interference suppression is compliant with the EMC product standard for variable-speed drives EN 61800-3,
"second environment" (industrial line supplies). EMC disturbances can occur when connected to the public grid.
For further information, see section Engineering information.

Deviations from the specified class are underlined.

1) In transport packaging.

Siemens D 21.3 · 2022 3/59


© Siemens 2022

SINAMICS S120 Chassis Format Units


Liquid-cooled units

■ Technical specifications
Cooling circuit and coolant quality
The following tables and sections describe the quality The coolant consists of a coolant basis and an additional
requirements of the coolant used in the liquid-cooled antifreeze agent or inhibitor.
SINAMICS S120 drive system in chassis format. See "Antifreeze and inhibitors".
Cooling circuit
• System pressure with reference to atmospheric 600 kPa
pressure, max.
• Pressure drop at rated volumetric flow 70 kPa
• Recommended pressure range 80 ... 150 kPa (is applicable for water as coolant)
• Inlet temperature of liquid coolant Dependent on ambient temperature, no condensation permitted
3 0 ... 45 °C (32 ...113 °F) without derating
>45 … 50 °C (113 ... 122 °F), see derating data
Antifreeze essential for temperature range between 0 °C (32 °F) and 5 °C (41 °F)
Coolant quality
Coolant basis for aluminum heat exchangers Distilled, demineralized, completely desalinated water or
deionized water with reduced electrical conductivity in accordance with ISO 3696, quality 3 or based on
IEC 60993
• Electrical conductivity when filling <30 S/cm (3 mS/m)
• pH value 5 ... 8
• Components that can be oxidized as oxygen <30 mg/l
content
• Residue after vaporization and drying at 110 °C <10 mg/kg
(230 °F)
Coolant basis for stainless steel heat exchangers Filtered drinking, process, and cooling water
• Electrical conductivity <2500 S/cm (250 mS/m)
• pH value 6.5 ... 9
• Total salt content TDS <1550 mg/l
• Chloride (Cl-) <250 mg/l
• Sodium (Na+) <200 mg/l
• Sulfate (SO42-) <240 mg/l
• Sulfide (S2-) <1 mg/l
• Nitrate (NO3-) <50 mg/l
• Iron <1 mg/l
• Silicate <10 mg/l
• Ammonia (NH3), ammonium (NH4+) <1 mg/l
• Total hardness with a maximum of <1.78 mmol/l (10 °dH)
- Calcium hardness <1.25 mmol/l (7 °dH), <57 mg/l calcium
- Magnesium hardness < 1.43 mmol/l (8 °dH), <35 mg/l magnesium
- Carbonate hardness <0.45 mmol/l (2.5 °dH)
• Suspended solids/suspended substances
- Solids <340 mg/l
- Size of entrained particles <100 m
The coolant definition specified here should only be considered as recommendation. For units that have
been shipped, the information and data provided in the equipment manual supplied should be observed!

Recommendation: Fill initially with demineralized water (via ion exchanger)

3/60 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Chassis Format Units


Liquid-cooled units

■ Technical specifications
Antifreeze and inhibitors
Antifreeze Antifrogen N Antifrogen L DOWCAL 100
Manufacturer Clariant Clariant DOW
Chemical base Ethylene glycol Propylene glycol Ethylene glycol
Minimum concentration 25 % 25 % 25 %
Antifreeze agent with minimum concentration -10 °C (14 °F) -10 °C (14 °F) -10 °C (14 °F)
Maximum concentration 45 % 48 % 45 %
Antifreeze agent with maximum -30 °C (-22 °F) -30 °C (-22 °F) -30 °C (-22 °F)
concentration
Inhibitor content Contains inhibitors with nitrites Contains inhibitors that are free of
nitrites, amines, borates and
Contains inhibitors that are free of
nitrites, amines and phosphates 3
phosphates
Biocide action with a concentration of >25 % >25 % >25 %

Biocides prevent corrosion that is caused by slime-forming, corrosive or iron-depositing bacteria. These can occur in closed cooling
circuits with low water hardness and in open cooling circuits. Biocides must always be selected according to the relevant bacterial
risks. Compatibility with inhibitors or antifreeze used with them must be checked on a case-by-case basis.

Inhibitors Antifrogen N ANTICORIT S 2000 A


Manufacturer Clariant Fuchs
Chemical base Ethylene glycol –
Minimum concentration 25 % 4%
Maximum concentration 45 % 5%

Recommended service
The manufacturer of the inhibitor/antifreeze should analyze the coolant at least every two years. The concentration and boundary
conditions of the inhibitor/antifreeze should be checked. It may be necessary to correct the concentration on the plant side.
Protection against condensation
With liquid-cooled units, warm air can condense on the cold The temperature at which water vapor contained in the air
surfaces of heat sinks, pipes and hoses. This condensation condenses into water is known as the dew point. In order to
depends on the air humidity and the temperature difference reliably prevent condensation, the coolant temperature must
between the ambient air and the coolant. always be higher than the dew point.
The water which is produced as a result of condensation can The table below specifies the dew point as a function of room
cause corrosion as well as electrical damage such as creepage temperature T and relative air humidity  for an atmospheric
shorts and flashovers. As the SINAMICS units cannot prevent pressure of 100 kPa (1 bar). This corresponds to an installation
condensation if it is caused by the prevailing climatic conditions, altitude of 0 up to approximately 500 m above sea level. Since
any potential risk of condensation must be prevented by appro- the dew point drops as the air pressure decreases, the dew point
priate engineering or by precautionary measures implemented values at higher installation altitudes are lower than the specified
by the customer. These measures include the following: table values. It is therefore the safest approach to engineer the
• a fixed coolant temperature that has been adjusted to the coolant temperature according to the values in the table for an
expected air humidity or ambient temperature ensures that installation altitude of zero.
critical differences between the coolant and ambient air A detailed description of the cooling circuits and the
temperatures do not develop or recommended coolant is given in the SINAMICS Low Voltage
• temperature regulation of the coolant as a function of the Engineering Manual.
ambient air temperature
Specification of the dew point / coolant temperature

Room temperature Relative air humidity 


T 20 % 30 % 40 % 50 % 60 % 70 % 80 % 85 % 90 % 95 % 100 %
10 °C (50 °F) <0 °C <0 °C <0 °C 0.2 °C 2.7 °C 4.8 °C 6.7 °C 7.6 °C 8.4 °C 9.2 °C 10 °C
(<32 °F) (<32 °F) (<32 °F) (32.4 °F) (36.9 °F) (40.6 °F) (44.1 °F) (45.7 °F) (47.1 °F) (48.6 °F) (50 °F)
20 °C (68 °F) <0 °C 2 °C 6 °C 9.3 °C 12 °C 14.3 °C 16.4 °C 17.4 °C 18.3 °C 19.1 °C 20 °C
(<32 °F) (35.6 °F) (42.8 °F) (48.7 °F) (53.6 °F) (57.7 °F) (61.5 °F) (63.3 °F) (64.9 °F) (66.4 °F) (68 °F)
25 °C (77 °F) 0.6 °C 6.3 °C 10.5 °C 13.8 °C 16.7 °C 19.1 °C 21.2 °C 22.2 °C 23.2 °C 24.1 °C 24.9 °C
(33.1 °F) (43.3 °F) (50.9 °F) (56.8 °F) (62.1 °F) (66.4 °F) (70.2 °F) (72.0 °F) (73.8 °F) (75.4 °F) (76.8 °F)
30 °C (86 °F) 4.7 °C 10.5 °C 14.9 °C 18.4 °C 21.3 °C 23.8 °C 26.1 °C 27.1 °C 28.1 °C 29 °C 29.9 °C
(40.5 °F) (50.9 °F) (58.8 °F) (65.1 °F) (70.3 °F) (74.8 °F) (79.0 °F) (80.8 °F) (82.6 °F) (84.2 °F) (85.8 °F)
35 °C (95 °F) 8.7 °C 14.8 °C 19.3 °C 22.9 °C 26 °C 28.6 °C 30.9 °C 32 °C 33 °C 34 °C 34.9 °C
(47.7 °F) (58.6 °F) (66.7 °F) (73.2 °F) (78.8 °F) (83.5 °F) (87.6 °F) (89.6 °F) (91.4 °F) (93.2 °F) (94.8 °F)
40 °C (104 °F) 12.8 °C 19.1 °C 23.7 °C 27.5 °C 30.6 °C 33.4 °C 35.8 °C 36.9 °C 37.9 °C 38.9 °C 39.9 °C
(55.0 °F) (66.4 °F) (74.7 °F) (81.5 °F) (87.1 °F) (92.1 °F) (96.4 °F) (98.4 °F) (100 °F) (102 °F) (104 °F)
45 °C (113 °F) 16.8 °C 23.3 °C 28.2 °C 32 °C 35.3 °C 38.1 °C 40.6 °C 41.8 °C 42.9 °C 43.9 °C 44.9 °C
(62.2 °F) (73.9 °F) (82.8 °F) (89.6 °F) (95.5 °F) (101 °F) (105 °F) (107 °F) (109 °F) (111 °F) (113 °F)
50 °C (122 °F) 20.8 °C 27.5 °C 32.6 °C 36.6 °C 40 °C 42.9 °C 45.5 °C 46.6 °C 47.8 °C 48.9 °C 49.9 °C
(69.4 °F) (81.5 °F) (90.7 °F) (97.9 °F) (104 °F) (109 °F) (114 °F) (116 °F) (118 °F) (120 °F) (122 °F)

Siemens D 21.3 · 2022 3/61


© Siemens 2022

SINAMICS S120 Chassis Format Units


Liquid-cooled units

■ Characteristic curves
Pressure drop

400
Pressure drop [kPa]

300

200
3 150 maximum differential
pressure

G_D211_EN_00316a
100
70 nominal differential
pressure

0
0 10 20 30 40 50 60 70 80
Volumetric flow dv/dt [liters/min]

Power Module Power Module Active Interface Module Active Line Module, Active Line Module,
frame size FL frame size GL frame size JIL (10 l/min) Motor Module Motor Module
Basic Line Module Basic Line Module frame size HXL frame size JXL
frame size FBL frame size GBL Active Interface Module
Motor Module Active Line Module frame size JIL (16 l/min)
frame size FXL frame size GXL
Motor Module
frame size GXL

Pressure drop for liquid-cooled built-in units in chassis format


The pressure drop characteristics are valid for water. If anti- For further information, please refer to the SINAMICS Low
freeze is used, the characteristics typically shift to the left. Voltage Engineering Manual.

3/62 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Chassis Format Units


Liquid-cooled units

■ Characteristic curves
Derating
Liquid-cooled SINAMICS S120 chassis format units are rated for
an ambient temperature of 45 °C and installation altitudes up to 110
2000 m above sea level. At ambient temperatures > 45 °C, the 100
output current must be reduced. Ambient temperatures above

Rated current %
90
50 °C are not permissible. At installation altitudes > 2000 m
80
above sea level, it must be taken into account that the air
pressure, and therefore air density, decreases as the height 70
increases. As a consequence, the cooling efficiency and the 60
insulation capacity of the air also decrease.
50
At installation altitudes above 2000 m, the line voltage must not
exceed certain limits in order to be able to isolate the surge
40
3

G_D213_EN_00038
30
voltages according to IEC 61800-5-1 for overvoltage
category III. If the line voltage is above this limit at installation 20
altitudes > 2000 m, measures must be taken to reduce the 10
transient overvoltages of Category III to values of Category II, 0
e. g. supply of the devices via an isolating transformer. -5 0 10 20 30 40 50 60
(23) (32) (50) (68) (86) (104) (122) (140)
For additional information, please refer to the SINAMICS Low Ambient temperature °C (°F)
Voltage Engineering Manual.
In order to prevent condensation, the inlet temperature of the
Current derating as a function of ambient temperature 1)
liquid coolant should be kept above the ambient temperature
depending on the relative air humidity.
50
Permissible ambient temperature (air) °C (°F)

(122)
100
Output current %

40
90 (104)
80
70 30
(86)
60
20
50 (68)

G_D213_EN_00072
40
10
G_D213_EN_00037b

30 (50)
20
10 0
(32) 0 1000 2000 3000 4000
0 (3281) (6562) (9843) (13124)
-5 0 10 20 30 40 45 50 60 Installation altitude above sea level m (ft)
(23) (32) (50) (68) (86) (104)(113)(122) (140) Ambient temperature Tmax at I = 100 %
Coolant temperature °C Ambient temperature Tmax at I = 90 %
without antifreeze (°F)
with antifreeze
Permissible ambient temperature as a function of installation altitude
Current derating as a function of the temperature of the cooling liquid 1)
The inlet temperature of the liquid coolant depends on the
ambient temperature, no condensation permitted.

1)
The factors of the two curves must not be multiplied. The highest value in
each case must be assumed for the purposes of calculation, so that the
derating factor in the worst-case scenario is 0.9.

Siemens D 21.3 · 2022 3/63


© Siemens 2022

SINAMICS S120 Chassis Format Units


Liquid-cooled units

■ Characteristic curves
Current derating as a function of the pulse frequency For additional information, please refer to the SINAMICS Low
Voltage Engineering Manual.
To reduce motor noise or to increase output frequency, the pulse
frequency can be increased relative to the factory setting The following tables list the rated output currents of the Power
(1.25 kHz or 2 kHz). When the pulse frequency is increased, the Modules and Motor Modules with pulse frequency set in the
derating factor of the output current must be taken into account. factory as well as the current derating factors (permissible
This derating factor must be applied to the currents specified in output currents referred to the rated output current) for higher
the technical specifications. pulse frequencies.
Derating factor of the output current as a function of the pulse frequency for units with a rated pulse frequency of 2 kHz
Power Module Type rating Output current at 2 kHz Derating factor at pulse frequency
Motor Module at 400 V
3 6SL3315-... kW A 2.5 kHz 4 kHz 5 kHz 7.5 kHz 8 kHz
6SL3325-...
380 ... 480 V 3 AC
1TE32-1AA3 110 210 95 % 82 % 74 % 54 % 50 %
1TE32-6AA3 132 260 95 % 83 % 74 % 54 % 50 %
1TE33-1AA3 160 310 97 % 88 % 78 % 54 % 50 %
1TE35-0AA3 250 490 94 % 78 % 71 % 53 % 50 %
1TE41-4AS3 1) 800 1330 88 % 55 % – – –

Derating factor of the output current as a function of the pulse frequency for Motor Modules with a rated pulse frequency of 1.25 kHz
Motor Module Type rating at Output current at Derating factor at pulse frequency
400 V or 690 V 1.25 kHz
6SL3325-... kW A 2 kHz 2.5 kHz 4 kHz 5 kHz 7.5 kHz 8 kHz
380 ... 480 V 3 AC
1TE36-1AA3 315 605 83 % 72 % 64 % 60 % 40 % 36 %
1TE37-5AA3 400 745 87 % 79 % 64 % 55 % 40 % 37 %
1TE38-4AA3 450 840 87 % 79 % 64 % 55 % 40 % 37 %
1TE41-0AA3 560 985 92 % 87 % 70 % 60 % 50 % 47 %
1TE41-2AA3 710 1260 97 % 95 % 74 % 60 % 50 % 47 %
1TE41-4AA3 800 1405 97 % 95 % 74 % 60 % 50 % 47 %
500 ... 690 V 3 AC
1TG31-0AA3 90 100 92 % 88 % 71 % 60 % 40 % –
1TG31-5AA3 132 150 90 % 84 % 66 % 55 % 35 % –
1TG32-2AA3 200 215 92 % 87 % 70 % 60 % 40 % –
1TG33-3AA3 315 330 89 % 82 % 65 % 55 % 40 % –
1TG34-7AA3 450 465 92 % 87 % 67 % 55 % 35 % –
1TG35-8AA3 560 575 91 % 85 % 64 % 50 % 35 % –
1TG37-4AA3 710 735 84 % 74 % 53 % 40 % 25 % –
1TG38-0AA3 2) 800 810 82 % 71 % 52 % 40 % 25 % –
1TG38-1AA3 800 810 97 % 95 % 71 % 55 % 35 % –
1TG41-0AA3 1000 1025 91 % 86 % 64 % 50 % 30 % –
1TG41-3AA3 1200 1270 87 % 79 % 55 % 40 % 25 % –
1TG41-6AP3 1500 1560 87 % 79 % 55 % 40 % 25 % –

1) This Motor Module has been specifically designed for loads demanding 2) The Motor Module 6SL3325-1TG38-0AA3 is optimized for low overload;
a high dynamic performance. The derating factor kIGBT and the derating with an increased pulse frequency, the derating factor is higher than for the
characteristics can be ignored (see section “Duty cycles” in the SINAMICS Motor Module 6SL3325-1TG38-1AA3.
Low Voltage Engineering Manual).

3/64 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Chassis Format Units


Liquid-cooled units

■ Characteristic curves
Maximum output frequencies achieved by increasing the pulse
frequency
The adjustable pulse frequencies – and therefore the output
frequencies that can be achieved with the factory-set current
controller clock cycles – are listed below.
Current controller clock Adjustable pulse frequency Max. achievable output frequency fA
cycle fp
TI V/f mode Vector mode Servo mode
1)
250 µs 2 kHz 166 Hz 166 Hz 333 Hz
4 kHz 333 Hz 333 Hz 550 Hz 3)
8 kHz 550 Hz 3)
480 Hz 550 Hz 3) 3
400 µs 2) 1.25 kHz 104 Hz 104 Hz –
2.5 kHz 208 Hz 208 Hz –
5.0 kHz 416 Hz 300 Hz –
7.5 kHz 550 Hz 3) 300 Hz –

1) 3)
As factory setting, the following devices have a current controller clock With the "High output frequencies" license, which can be ordered as option
cycle of 250 µs and a pulse frequency of 2 kHz: J01 on the CompactFlash card for SINAMICS S120, the maximum output
- 380 ... 480 V 3 AC:  250 kW / 490 A, 6SL3325-1TE41-4AS3 frequency is increased up to 650 Hz. For more information, see
2)
As factory setting, the following devices have a current controller clock https://support.industry.siemens.com/cs/document/104020669
cycle of 400 µs and a pulse frequency of 1.25 kHz:
- 380 ... 480 V 3 AC: 315 kW / 605 A, except 6SL3325-1TE41-4AS3
- 500 ... 690 V 3 AC: All power ratings

Siemens D 21.3 · 2022 3/65


© Siemens 2022

SINAMICS S120 Chassis Format Units


Liquid-cooled units

■ Characteristic curves
Overload capability The following applies to the Motor Module 6SL3325-1TG41-6AP3:
Liquid-cooled SINAMICS S120 units have an overload reserve, This Motor Module is particularly suited to high breakaway
e.g. to handle breakaway torques. If larger surge loads occur, torques with applications such as drilling, mixers, centrifuges,
this must be taken into account in the configuration. For drives and test bays. An additional duty cycle is required at output
with overload requirements, the appropriate base load current frequencies of 5 Hz to 10 Hz.
must, therefore, be used as a basis for the required load. At output frequencies of 1 Hz to 5 Hz, the short-time current is
1900 A for 5 s.
The permissible overload levels are valid under the prerequisite
that the drive units are operated with their base-load current
before and after the overload condition based on a duty cycle Converter current
duration of 300 s. 5s
A
3 Another precondition is that the Power Modules or the Motor
Modules are operated at their factory-set pulse frequency at
2340 Short-time current

output frequencies > 10 Hz.


For temporary, periodic duty cycles with high variations of load Rated current (continuous)
within the duty cycle, the relevant sections of the SINAMICS Low
Voltage Engineering Manual must be observed.
Base-load current
Power Modules and Motor Modules
IN
The base-load current for a low overload IL is the basis for a duty

G_D213_EN_00116
cycle of 110 % for 60 s or 150 % for 10 s. 1460

600 s
Converter current
10 s
1.5 x IL t

Short-time current 150 %


High overload for Motor Module 6SL3325-1TG41-6AP3
Short-time current 110 % Line Modules
Rated current (continuous) The base-load current for a high overload IH DC is the basis for
Base-load current IL a duty cycle of 150 % for 60 s or Imax DC for 5 s.
1.1 x IL
for low overload
IN Converter current
IL
G_D213_EN_00035

5s
60 s
300 s Imax DC Short-time current Imax

1.5 x IH DC Short-time current 150 %

t
Rated current (continuous)
Low overload Base-load current IH DC
for high overload
The base-load current IH for a high overload is based on a load
IN DC
cycle of 150 % for 60 s or 160 % for 10 s.
IH DC G_D213_EN_00079
Converter current 60 s
10 s 300 s

1.6 x IH Short-time current 160 %


1.5 x IH Short-time current 150 % t

Rated current (continuous) High overload

Base-load current IH for high overload


IN

IH
G_D213_EN_00036

60 s
300 s

High overload

3/66 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Chassis Format Units


Liquid-cooled units
Power Modules

■ Overview Use in multi-axis systems


Power Modules in chassis format can also be connected directly
via DRIVE-CLiQ to a separate CU320-2 or SIMOTION D4x5-2
Control Unit or Controller Extension CX32-2. The appropriate
DRIVE-CLiQ cable for the required distance must be ordered
(see section Connection system).

■ Selection and ordering data


Type rating Rated output current Power Module
at 400 V
kW A Article No.
Line voltage 380 ... 480 V 3 AC
110 210 6SL3315-1TE32-1AA3
3
132 260 6SL3315-1TE32-6AA3
160 310 6SL3315-1TE33-1AA3
250 490 6SL3315-1TE35-0AA3

Extended liability for defects


The Power Module comprises a line rectifier, a DC link and an
Siemens offers for SINAMICS S120 chassis units an extended
inverter to supply the motor.
liability for defects/Service Protect up to 6½ years.
Power Modules are designed for drives that are not capable of
Details can be found in chapter
regenerating energy to the mains supply. If the motor produces
Services and Documentation
energy during braking, a Braking Module with braking resistors
will be required. Accessories
Liquid-cooled Power Modules are especially suitable for Description Article No.
applications where installation space is restricted and
environmental conditions are harsh. Liquid cooling ensures 3-way valve 1) VXF41...
efficient heat dissipation. VXG41...

Power Modules in the chassis format can be connected to Actuator for 3-way valve 1)
grounded TN/TT systems and non-grounded IT systems. • 230 V 1 AC SAX31...
• 24 V AC/DC SAX61...

■ Design SAX81...
Accessories for re-ordering
The liquid-cooled Power Modules have the following interfaces
Dust protection blanking plugs 6SL3066-4CA00-0AA0
as standard: (50 units)
• 1 line supply connection For DRIVE-CLiQ port
• 1 motor connection
For additional information, refer to the manual.
• 1 connection for the 24 V DC electronics power supply
For line-side and motor-side components, see System
• 1 DC link connection components.
• 3 DRIVE-CLiQ sockets
• 1 temperature sensor input for KTY84-130, Pt1000, PTC or
Pt100 (Pt1000 can be used from firmware V4.7 HF17 and
higher)
• 1 connection for Safe Brake Adapter
• 1 connection for Safety Integrated
• 2 PE/protective conductor connections
• 2 coolant connections
The CU310-2 Control Unit can be integrated into the
liquid-cooled Power Modules.
The status of the Power Modules is indicated via three LEDs.
The scope of supply of the Power Modules includes:
• 1 DRIVE-CLiQ cable for connection to the CU310-2 Control
Unit
• 1 mounting plate for attaching the CU310-2 Control Unit
• 2 seals for coolant connections
• 1 set of warning labels in 30 languages
(BG, CN, CZ, DE, DK, EE, ES, FI, FR, GB, GR, HU, IE, IS, IT,
JP, KR, LT, LV, MT, NL, NO, PL, PT, RO, RU, SE, SI, SK, TR)

1) Recommended components for installing a flow control as condensation


protection; manufactured by Siemens Building Technologies.

Siemens D 21.3 · 2022 3/67


© Siemens 2022

SINAMICS S120 Chassis Format Units


Liquid-cooled units
Power Modules

■ Integration
The Power Modules communicate with the higher-level control module via DRIVE-CLiQ. The Control Unit in this case could be
a CU310-2, CU320-2 or a SIMOTION D Control Unit. An external 24 V DC power supply is required to operate liquid-cooled
Power Modules.
Main switch Main contactor Line reactor

L1
L2
L3

W1
PE
U1
V1
-X1
Power Module
chassis format
~
=
-X9
1 P24 V =
ext. Cooling circuit
24 V DC 2 M
=
3
4 Internal power
supply
5
Main contactor
6 control
EP P24 V 7
EP M1 8

-X41
4 DCP
+Temp
3 - Temp
2 DCN
1

-X42 =
1
+ 2
P24L ~
+ 1)
P24L
M 3 M
M 4 M
IPD Card
-X46
1 BR Output+
2 BR Output-
3 FB Input+
4 FB Input-
READY
LEDs

X400 DC LINK
Control Unit DRIVE-CLiQ-socket 0
POWER OK
X401
DRIVE-CLiQ-socket 1
G_D211_EN_00255c

X402
DRIVE-CLiQ-socket 2
-X2
W2
PE
U2
V2

1)
24 V connecting cable for supply of a CU310-2
Control Unit or SIMOTION D410-2 integrated in a
Power Module.

M
3~

Connection example, liquid-cooled Power Module in the chassis format


Note:
The integrated 24 V power supply at connector X42 can have the integrated power supply, the total load of the digital outputs
a maximum load of 2 A. When the Control Unit is supplied from must be carefully observed to ensure that the 2 A is not
exceeded.

3/68 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Chassis Format Units


Liquid-cooled units
Power Modules

■ Technical specifications
General technical specifications
Electrical specifications
Line connection voltage 380 … 480 V 3 AC ±10 % (-15 % < 1 min)
Up to 2000 m (6562 ft) above sea level
Line power factor
for a 3 AC line supply voltage and rated
output
• Basic fundamental (cos 1) >0.96
• Total () 0.75 ... 0.93
Efficiency > 98 %
DC link voltage, approx. 1.35 × line voltage 3
Output voltage, approx. 0 ... 0.97 × Uline
Output frequency 1)
• Control mode Servo 0 ... 550 Hz
• Control mode Vector 0 ... 550 Hz
• Control mode V/f 0 ... 550 Hz
Electronics power supply 24 V DC -15 %/+20 %
Main contactor control
• Terminal strip -X9/5-6 240 V AC, max. 8 A
30 V DC, max. 1 A
Safety Integrated Safety Integrity Level 2 (SIL2) acc. to IEC 61508, Performance Level d (PLd) acc. to EN ISO 13849-1 and
Control Category 3 acc. to EN ISO 13849-1.

1) Please note:
• The correlation between the maximum output frequency, pulse
frequency and current derating. Higher output frequencies on request.
For further information, see
https://support.industry.siemens.com/cs/document/104020669
• The correlation between the minimum output frequency and
permissible output current (current derating).
For additional information, please refer to the SINAMICS Low Voltage
Engineering Manual.

Siemens D 21.3 · 2022 3/69


© Siemens 2022

SINAMICS S120 Chassis Format Units


Liquid-cooled units
Power Modules

■ Technical specifications
Line voltage 380 V ... 480 V 3 AC Power Modules
6SL3315-1TE32-1AA3 6SL3315-1TE32-6AA3 6SL3315-1TE33-1AA3 6SL3315-1TE35-0AA3
Type rating
• At IL (50 Hz 400 V) 1) kW 110 132 160 250
• At IH (50 Hz 400 V) 1) kW 90 110 132 200
• At IL (60 Hz 460 V) 2) hp 150 200 250 400
• At IH (60 Hz 460 V) 2) hp 150 200 200 350
Output current
• Rated current IN O A 210 260 310 490
• Base-load current IL 3) A 205 250 302 477
• Base-load current IH 4) A 178 233 277 438

3 • Max. output current Imax O


Input current
A 307 375 453 715

• Rated current IN I A 230 285 340 540


• Maximum current Imax I A 336 411 496 788
Current demand
• 24 V DC auxiliary power supply A 1.4 1.4 1.5 1.5
Pulse frequency 5)
• Rated frequency kHz 2 2 2 2
• Pulse frequency, max.
- Without current derating kHz 2 2 2 2
- With current derating kHz 8 8 8 8
Power loss, at 50 Hz 400 V 6)
• Dissipated to coolant kW 2.34 2.95 3.28 5.25
• Dissipated to ambient air kW 0.08 0.09 0.12 0.18
• Total kW 2.42 3.04 3.4 5.43
Coolant volume flow 7) l/min (US 9 (2.38) 9 (2.38) 12 (3.17) 12 (3.17)
gal./min)
Liquid volume dm3 0.52 0.52 0.88 0.88
of the integrated heat exchanger
Pressure drop, typ. 8) Pa 70000 70000 70000 70000
for volume flow
Heat exchanger material Stainless steel Stainless steel Stainless steel Stainless steel
Coolant connections Pipe thread ISO 228 G 3/4 B
Intake/return (external thread 3/4", flat-sealing)
Sound pressure level LpA dB 52 52 52 52
(1 m) at 50/60 Hz
Line supply connection Hole for M12 Hole for M12 Hole for M12 Hole for M12
U1, V1, W1
2
• Conductor cross-section, max. (IEC) mm 2 × 95 2 × 95 2 × 240 2 × 240
DC link connection Hole for M12 Hole for M12 Hole for M12 Hole for M12
DCP, DCN
• Conductor cross-section, max. (IEC) mm2 2 × 95 2 × 95 2 × 240 2 × 240
Motor connection Hole for M12 Hole for M12 2 × hole for M12 2 × hole for M12
U2/T1, V2/T2, W2/T3
• Conductor cross-section, max. (IEC) mm2 2 × 95 2 × 95 2 × 240 2 × 240
Cable length, max. 9)
• Shielded m (ft) 300 (984) 300 (984) 300 (984) 300 (984)
• Unshielded m (ft) 450 (1476) 450 (1476) 450 (1476) 450 (1476)
PE/GND connection 2 × hole for M12 2 × hole for M12 2 × hole for M12 2 × hole for M12
• Conductor cross-section, max. (IEC) mm2 2 × 95 2 × 95 2 × 240 2 × 240
Dimensions
• Width mm (in) 265 (10.4) 265 (10.4) 265 (10.4) 265 (10.4)
• Height mm (in) 836 (32.9) 836 (32.9) 983 (38.7) 983 (38.7)
• Depth mm (in) 549 (21.6) 549 (21.6) 549 (21.6) 549 (21.6)
Weight, approx. kg (lb) 77 (170) 77 (170) 108 (238) 108 (238)
Frame size FL FL GL GL
Minimum short-circuit current 10) kA 3 3.6 4.4 8

1) 6)
Rated power of a typical 6-pole standard induction motor based on IL or IH The specified power loss represents the maximum value at 100 %
for 400 V 3 AC 50 Hz. utilization. The value is lower under normal operating conditions. To ensure
2)
Rated power of a typical 6-pole standard induction motor based on IL or IH safe dissipation of the minor power loss released to the ambient air, it is
for 460 V 3 AC 60 Hz. important to follow the instructions pertaining to control cabinet installation
3)
in the SINAMICS Low Voltage Engineering Manual.
The base-load current IL is based on a duty cycle of 110 % for 60 s or 7)
150 % for 10 s with a duty cycle duration of 300 s. The value applies to coolants comprising water and a mixture of
4)
water and antifreeze agent.
The base-load current IH is based on a duty cycle of 150 % for 60 s or 8)
160 % for 10 s with a duty cycle duration of 300 s. The value is valid for water as coolant.
5)
Additional information and notes on other coolants are provided in the
Information regarding the correlation between the pulse frequency and SINAMICS Low Voltage Engineering Manual.
maximum output current/output frequency is provided in the SINAMICS 9)
Low Voltage Engineering Manual. Longer cable lengths for specific configurations are available on request.
For additional information, please refer to the SINAMICS
Low Voltage Engineering Manual.
10) Current required for reliably triggering protective devices.

3/70 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Chassis Format Units


Liquid-cooled units
Basic Line Modules

■ Overview ■ Selection and ordering data


Rated power Rated DC link current Basic Line Module
at 400 V or 690 V
kW A Article No.
Line voltage 380 ... 480 V 3 AC
360 740 6SL3335-1TE37-4AA3
600 1220 6SL3335-1TE41-2AA3
830 1730 6SL3335-1TE41-7AA3
Line voltage 500 ... 690 V 3 AC
355 420 6SL3335-1TG34-2AA3
630 730 6SL3335-1TG37-3AA3 3
1100 1300 6SL3335-1TG41-3AA3
1370 1650 6SL3335-1TG41-7AA3

Extended liability for defects

Siemens offers for SINAMICS S120 chassis units an extended


Basic Line Modules are used for applications where energy is liability for defects/Service Protect up to 6½ years.
not fed back into the line supply or where energy is exchanged Details can be found in chapter
in the DC link between axes operating in the motor and Services and Documentation
generator modes. The connected Motor Modules are pre-
charged via the thyristor gate control. Basic Line Modules are Accessories
designed for connection to grounded TN/TT and non-grounded
Description Article No.
IT supply systems.
3-way valve 1) VXF41...
Liquid-cooled Basic Line Modules are especially suitable
VXG41...
for applications where installation space is restricted and
environmental conditions are harsh. Liquid cooling ensures Actuator for 3-way valve 1)
efficient heat dissipation. • 230 V 1 AC SAX31...
• 24 V AC/DC SAX61...
■ Design SAX81...
Accessories for re-ordering
The liquid-cooled Basic Line Modules have the following
interfaces as standard: Dust protection blanking plugs 6SL3066-4CA00-0AA0
(50 units)
• 1 line supply connection For DRIVE-CLiQ port
• 1 connection for the 24 V DC electronics power supply
For line-side components, see System components.
• 1 DC link connection (DCP, DCN) for supplying the connected
Motor Modules
• 3 DRIVE-CLiQ sockets
• 1 temperature sensor input for KTY84-130, Pt1000, PTC or
Pt100 (Pt1000 can be used from firmware V4.7 HF17 and
higher)
• 1 PE/protective conductor connection
• 2 coolant connections
The status of the Basic Line Modules is indicated via three LEDs.
The scope of supply of the Power Modules includes:
• 1 DRIVE-CLiQ cable for connection to the Control Unit
• 2 seals for coolant connections
• 1 set of warning labels in 30 languages
(BG, CN, CZ, DE, DK, EE, ES, FI, FR, GB, GR, HU, IE, IS, IT,
JP, KR, LT, LV, MT, NL, NO, PL, PT, RO, RU, SE, SI, SK, TR)

1)
Recommended components for installing a flow control as condensation
protection; manufactured by Siemens Building Technologies.

Siemens D 21.3 · 2022 3/71


© Siemens 2022

SINAMICS S120 Chassis Format Units


Liquid-cooled units
Basic Line Modules

■ Integration
The liquid-cooled Basic Line Modules communicate with the higher-level control module via DRIVE-CLiQ. The control module in this
case can be a CU320-2 or a SIMOTION D Control Unit. An external 24 V DC power supply is required to operate liquid-cooled Basic
Line Modules.

X400 X401 X402

DRIVE-CLiQ socket 1

DRIVE-CLiQ socket 2
L1
L2

DRIVE-CLiQ socket
L3
Basic Line
Module
3 chassis format
Main switch
-X9 Cooling circuit
1 P24 V
ext. =
24 V DC 1
2 M =
2
3 Internal
power supply
4
Main contactor 5
Main contactor
6 control
7 EP +24 V
~ DCP
DCN DC link
8 EP M1 =

-X41 READY
LEDs

4 DC LINK
+Temp
3 -Temp
Line reactor 2 POWER OK
EP +24 V
1
EP M1

-X42
IPD Card
1 P24L
2 P24L
3 G_D213_EN_00039c
M
4 M

-X1
W1
PE
U1
V1

Connection example of a Basic Line Module

■ Technical specifications
General technical specifications
Electrical specifications
Line power factor at rated power
• Basic fundamental (cos 1) >0.96
• Total () 0.75 ... 0.93
Efficiency >99 %
DC link voltage, approx. 1) 1.35 × line voltage
Main contactor control
• Terminal strip -X9/5-6 240 V AC, max. 8 A
30 V DC, max. 1 A

1)
The DC link voltage is unregulated and load-dependent.
For additional information, please refer to the SINAMICS Low Voltage
Engineering Manual.

3/72 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Chassis Format Units


Liquid-cooled units
Basic Line Modules

■ Technical specifications
Line voltage 380 ... 480 V 3 AC Basic Line Modules
6SL3335-1TE37-4AA3 6SL3335-1TE41-2AA3 6SL3335-1TE41-7AA3
Rated power
• At IN DC (50 Hz 400 V) kW 360 600 830
• At IH DC (50 Hz 400 V) kW 280 450 650
• At IN DC (60 Hz 460 V) hp 555 925 1280
• At IH DC (60 Hz 460 V) hp 430 690 1000
DC link current
• Rated current IN DC A 740 1220 1730
• Base-load current IH DC 1) A 578 936 1350
• Maximum current Imax DC A 1110 1830 2595 3
Input current
• Rated current IN I A 610 1000 1420
• Maximum current Imax I A 915 1500 2130
Current demand
• 24 V DC auxiliary power supply A 0.7 0.7 0.7
DC link capacitance
• Basic Line Module F 12000 20300 26100
• Drive line-up, max. F 96000 162400 208800
Power loss, at
50 Hz 400 V 2)
• Dissipated to coolant kW 2.7 4.36 5.82
• Dissipated to ambient air kW 0.25 0.41 0.57
• Total kW 2.95 4.77 6.39
Coolant volume flow 3) l/min (US 9 (2.38) 9 (2.38) 12 (3.17)
gal./min)
Liquid volume dm3 0.45 0.45 0.79
of the integrated heat exchanger
Pressure drop, typ. 4) Pa 70000 70000 70000
for volume flow
Heat exchanger material Aluminum Aluminum Aluminum
Coolant connections Pipe thread ISO 228 G 3/4 B
Intake/return (external thread 3/4", flat-sealing)
Sound pressure level LpA dB 54 56 56
(1 m) at 50/60 Hz
Line supply connection 2 × M12 nut 2 × M12 nut 2 × M12 nut
U1, V1, W1
• Conductor cross-section, max. (IEC) mm2 4 × 240 4 × 240 4 × 240
DC link connection 2 × M12 nut 2 × M12 nut 2 × M12 nut
DCP, DCN Busbar Busbar Busbar
PE/GND connection 2 × M12 nut 2 × M12 nut 2 × M12 nut
• Conductor cross-section, max. (IEC) mm2 4 × 240 4 × 240 4 × 240
Cable length, max. 5)
• Shielded m (ft) 2600 (8530) 4000 (13123) 4800 (15748)
• Unshielded m (ft) 3900 (12795) 6000 (19685) 7200 (23622)
Dimensions
• Width mm (in) 160 (6.30) 160 (6.30) 160 (6.30)
• Height mm (in) 1137 (44.8) 1137 (44.8) 1562 (61.5)
• Depth mm (in) 545 (21.5) 545 (21.5) 545 (21.5)
Weight, approx. kg (lb) 108 (238) 108 (238) 185 (408)
Frame size FBL FBL GBL
Minimum short-circuit current 6) kA 8.8 12.4 20

1) 4)
The base-load current IH DC is the basis for a duty cycle of 150 % for 60 s The value is valid for water as coolant.
or Imax DC for 5 s with a duty cycle duration of 300 s. Additional information and notes on other coolants are provided in the
2)
The specified power loss represents the maximum value at 100 % SINAMICS Low Voltage Engineering Manual.
5)
utilization. The value is lower under normal operating conditions. To ensure Total of all motor cables and DC link. Longer cable lengths for specific con-
safe dissipation of the minor power loss released to the ambient air, it is figurations are available on request.
important to follow the instructions pertaining to control cabinet installation For additional information, please refer to the SINAMICS Low Voltage
in the SINAMICS Low Voltage Engineering Manual. Engineering Manual.
3) 6)
The value applies to coolants comprising water and a mixture of water Current required for reliably triggering protective devices.
and antifreeze agent.

Siemens D 21.3 · 2022 3/73


© Siemens 2022

SINAMICS S120 Chassis Format Units


Liquid-cooled units
Basic Line Modules

■ Technical specifications
Line voltage 500 ... 690 V 3 AC Basic Line Modules
6SL3335-1TG34-2AA3 6SL3335-1TG37-3AA3 6SL3335-1TG41-3AA3 6SL3335-1TG41-7AA3
Rated power
• At IN DC (50 Hz 690 V) kW10 355 630 1100 1370
• At IH DC (50 Hz 690 V) kW 275 475 840 1070
• At IN DC (50 Hz 500 V) kW 245 420 750 950
• At IH DC (50 Hz 500 V) kW 200 345 610 775
• At IN DC (60 Hz 575 V) hp 395 705 1230 1530
• At IH DC (60 Hz 575 V) hp 305 530 940 1195
DC link current
3 • Rated current IN DC
• Base-load current IH DC 1)
A
A
420
328
730
570
1300
1014
1650
1287
• Maximum current Imax DC A 630 1095 1950 2475
Input current
• Rated current IN I A 340 600 1070 1350
• Maximum current Imax I A 510 900 1605 2025
Current demand
• 24 V DC auxiliary power supply A 0.7 0.7 0.7 0.7
DC link capacitance
• Basic Line Module F 4800 7700 15500 19300
• Drive line-up, max. F 38400 61600 124000 154400
Power loss, at 50 Hz 690 V 2)
• Dissipated to coolant kW 1.55 2.71 4.66 5.7
• Dissipated to ambient air kW 0.21 0.38 0.43 0.55
• Total kW 1.76 3.09 5.09 6.25
Coolant volume flow 3) l/min (US 9 (2.38) 9 (2.38) 12 (3.17) 12 (3.17)
gal./min)
Liquid volume dm3 0.45 0.45 0.79 0.79
of the integrated heat exchanger
Pressure drop, typ. 4) Pa 70000 70000 70000 70000
for volume flow
Heat exchanger material Aluminum Aluminum Aluminum Aluminum
Coolant connections Pipe thread ISO 228 G 3/4 B
Intake/return (external thread 3/4", flat-sealing)
Sound pressure level LpA dB 54 54 56 56
(1 m) at 50/60 Hz
Line supply connection 2 × M12 nut 2 × M12 nut 2 × M12 nut 2 × M12 nut
U1, V1, W1
• Conductor cross-section, max. (IEC) mm2 4 × 240 4 × 240 4 × 240 4 × 240
DC link connection 2 × M12 nut 2 × M12 nut 2 × M12 nut 2 × M12 nut
DCP, DCN Busbar Busbar Busbar Busbar
PE/GND connection 2 × M12 nut 2 × M12 nut 2 × M12 nut 2 × M12 nut
• Conductor cross-section, max. (IEC) mm2 4 × 240 4 × 240 4 × 240 4 × 240
Cable length, max. 5)
• Shielded m (ft) 1500 (4921) 1500 (4921) 2250 (7382) 2250 (7382)
• Unshielded m (ft) 2250 (7382) 2250 (7382) 3375 (11073) 3375 (11073)
Dimensions
• Width mm (in) 160 (6.30) 160 (6.30) 160 (6.30) 160 (6.30)
• Height mm (in) 1137 (44.8) 1137 (44.8) 1562 (61.5) 1562 (61.5)
• Depth mm (in) 545 (21.5) 545 (21.5) 545 (21.5) 545 (21.5)
Weight, approx. kg (lb) 108 (238) 108 (238) 185 (408) 185 (408)
Frame size FBL FBL GBL GBL
Minimum short-circuit current 6) kA 4.4 7.2 16.8 18.9

1) The base-load current IH DC is the basis for a duty cycle of 150 % for 4) The value is valid for water as coolant.
60 s or Imax DC for 5 s with a duty cycle duration of 300 s. Additional information and notes on other coolants are provided in the
2) The specified power loss represents the maximum value at 100 % SINAMICS Low Voltage Engineering Manual.
utilization. The value is lower under normal operating conditions. To ensure 5) Total of all motor cables and DC link. Longer cable lengths for specific con-
safe dissipation of the minor power loss released to the ambient air, it is figurations are available on request.
important to follow the instructions pertaining to control cabinet installation For additional information, please refer to the SINAMICS Low Voltage
in the SINAMICS Low Voltage Engineering Manual. Engineering Manual.
3) 6)
The value applies to coolants comprising water and a mixture of water Current required for reliably triggering protective devices.
and antifreeze agent.

3/74 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Chassis Format Units


Liquid-cooled units
Active Line Modules

■ Overview ■ Selection and ordering data


Rated power Rated infeed/ Active Line Module
at 400 V or 690 V regenerative
feedback current
kW A Article No.
Line voltage 380 ... 480 V 3 AC
300 490 6SL3335-7TE35-0AA3
380 605 6SL3335-7TE36-1AA3
500 840 6SL3335-7TE38-4AA3
630 985 6SL3335-7TE41-0AA3
900 1405 6SL3335-7TE41-4AA3 3
Line voltage 500 ... 690 V 3 AC
630 575 6SL3335-7TG35-8AA3
800 735 6SL3335-7TG37-4AA3
900 810 6SL3335-7TG38-1AA3
1100 1020 6SL3335-7TG41-0AA3
The self-commutated infeed/regenerative feedback units (with 1400 1270 6SL3335-7TG41-3AA3
IGBTs in infeed and regenerative feedback directions) generate
1700 1560 6SL3335-7TG41-6AA3
a regulated DC link voltage. This means that the connected
Motor Modules are decoupled from the line voltage. Line voltage Extended liability for defects
fluctuations within the permissible supply tolerances have no
effect on the motor voltage. Siemens offers for SINAMICS S120 chassis units an extended
liability for defects/Service Protect up to 6½ years.
If required, the Active Line Modules can also provide reactive
power compensation. Details can be found in chapter
Services and Documentation
Active Line Modules are designed for connection to grounded
TN/TT and non-grounded IT supply systems. Accessories

Liquid-cooled Active Line Modules are especially suitable for Description Article No.
applications where installation space is restricted and environ-
3-way valve 1) VXF41...
mental conditions are harsh. Liquid cooling ensures efficient
heat dissipation. VXG41...
Actuator for 3-way valve 1)
Active Line Modules are always operated together with the
• 230 V 1 AC SAX31...
associated Active Interface Modules. These include the
• 24 V AC/DC SAX61...
necessary pre-charging circuit as well as a Clean Power Filter.
SAX81...

■ Design Accessories for re-ordering


Dust protection blanking plugs 6SL3066-4CA00-0AA0
The liquid-cooled Active Line Modules have the following (50 units)
interfaces as standard: For DRIVE-CLiQ port
• 1 line supply connection
For additional information, refer to the manual.
• 1 connection for the 24 V DC electronics power supply
• 1 DC link connection (DCP, DCN) for supplying the connected For line-side components and recommended system
Motor Modules components, see System components.
• 3 DRIVE-CLiQ sockets
• 1 temperature sensor input for KTY84-130, Pt1000, PTC or
Pt100 (Pt1000 can be used from firmware V4.7 HF17 and
higher)
• 1 PE/protective conductor connection
• 2 coolant connections
The status of the Active Line Modules is indicated via three
LEDs.
The following are included in the scope of supply of the Active
Line Modules:
• 1 DRIVE-CLiQ cable for connection to the Control Unit
• 2 seals for coolant connections
• 1 set of warning labels in 30 languages
(BG, CN, CZ, DE, DK, EE, ES, FI, FR, GB, GR, HU, IE, IS, IT,
JP, KR, LT, LV, MT, NL, NO, PL, PT, RO, RU, SE, SI, SK, TR)

1)
Recommended components for installing a flow control as condensation
protection; manufactured by Siemens Building Technologies.

Siemens D 21.3 · 2022 3/75


© Siemens 2022

SINAMICS S120 Chassis Format Units


Liquid-cooled units
Active Line Modules

■ Integration
Active Line Modules are always operated together with the The liquid-cooled Active Line Modules communicate with the
associated Active Interface Modules. Active Interface Modules higher-level control module via DRIVE-CLiQ. The control module
contain a Clean Power Filter with basic RI suppression, the pre- in this case can be a CU320-2 or a SIMOTION D Control Unit.
charging circuit for the Active Line Module, line supply voltage An external 24 V DC power supply is required to operate
sensing circuit and monitoring sensors. the liquid-cooled Active Line Modules.

X400 X401 X402

2
DRIVE-CLiQ socket

DRIVE-CLiQ socket

DRIVE-CLiQ socket
Active Line
3 Module
chassis format

-X9 Cooling circuit


1 P24 V =
ext.
24 V DC 2 M
Control of =
3
to Active 4 bypass contactor Internal
Interface Module 5 Control of power supply
pre-charging
6 contactor
7
EP +24 V
8
EP M1
~ DCP
DC link
DCN
=

-X41
4 READY
+Temp
LEDs

3 -Temp DC LINK
2 EP +24 V
1 POWER OK
EP M1

-X42
1 P24L
2 IPD Card
P24L
3 M
4
G_D213_EN_00040c

-X1
W1
PE
U1
V1

from Active
Interface Module

Connection example of an Active Line Module

■ Technical specifications
General technical specifications
Electrical specifications
Line power factor
• Basic fundamental (cos 1) 1 (factory setting), can be altered by inputting a reactive current setpoint
• Total () 1 (factory setting)
Efficiency >98.5 % (Active Line Modules)
>99 % (Active Interface Module)
DC link voltage, approx. The DC link voltage is regulated and can be adjusted as a voltage decoupled from the line voltage.
Factory setting of the DC link voltage: 1.5 × line voltage

3/76 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Chassis Format Units


Liquid-cooled units
Active Line Modules

■ Technical specifications
Line voltage 380 V ... 480 V 3 AC Active Line Modules
6SL3335- 6SL3335- 6SL3335- 6SL3335- 6SL3335-
7TE35-0AA3 7TE36-1AA3 7TE38-4AA3 7TE41-0AA3 7TE41-4AA3
Rated power
• At IN DC (50 Hz 400 V) kW 300 380 500 630 900
• At IH DC (50 Hz 400 V) kW 270 335 465 545 780
• At IN DC (60 Hz 460 V) hp 500 600 700 900 1250
• At IH DC (60 Hz 460 V) hp 400 500 700 800 1000
DC link current
• Rated current IN DC A 549 677 941 1100 1573
• Base-load current IH DC 1)
• Maximum current Imax DC
A
A
489
823
603
1017
837
1410
982
1654
1401
2361
3
Infeed/regenerative feedback current
• Rated current IN I A 490 605 840 985 1405
• Maximum current Imax I A 735 907 1260 1477 2055
Current demand
• 24 V DC auxiliary power supply A 1.5 1.6 1.6 1.6 1.6
DC link capacitance
• Active Line Module F 9600 12600 17400 18900 28800
• Drive line-up, max. F 76800 134400 134400 230400 230400
Pulse frequency kHz 4 2.5 2.5 2.5 2.5
Power loss, at 50 Hz 400 V 2)
• Dissipated to coolant kW 3.42 4.65 5.52 7.46 9.58
• Dissipated to ambient air kW 0.14 0.17 0.23 0.44 0.62
• Total kW 3.56 4.82 5.75 7.9 10.2
Coolant volume flow 3) l/min (US 12 (3.17) 16 (4.23) 16 (4.23) 27 (7.13) 27 (7.13)
gal./min)
Liquid volume dm3 0.91 0.74 0.74 1.56 1.56
of the integrated heat exchanger
Pressure drop, typ. 4) Pa 70000 70000 70000 70000 70000
for volume flow
Heat exchanger material Stainless steel Aluminum Aluminum Aluminum Aluminum
Coolant connections Pipe thread ISO 228 G 3/4 B
Intake/return (external thread 3/4", flat-sealing)
Sound pressure level LpA 5) dB 69/73 70/73 70/73 71/73 71/73
(1 m) at 50/60 Hz
Line supply connection Hole for M12 2 x hole for M12 2 x hole for M12 2 x hole for M12 2 x hole for M12
U1, V1, W1
2
• Conductor cross-section, max. (IEC) mm 2 × 240 4 × 185 4 × 185 Busbar Busbar
DC link connection 2 × hole for M12 2 × hole for M12 2 × hole for M12 2 × hole for M12 2 × hole for M12
DCP, DCN Busbar Busbar Busbar Busbar Busbar
PE/GND connection 2 × hole for M12 2 × hole for M12 2 × hole for M12 2 × hole for M12 2 × hole for M12
• Conductor cross-section, max. (IEC) mm2 2 × 240 4 × 185 4 × 185 4 × 240 4 × 240
Cable length, max. 6)
• Shielded m (ft) 2700 (8858) 3900 (12795) 3900 (12795) 3900 (12795) 3900 (12795)
• Unshielded m (ft) 4050 (13287) 5850 (19193) 5850 (19193) 5850 (19193) 5850 (19193)
Dimensions
• Width mm (in) 150 (5.91) 265 (10.4) 265 (10.4) 295 (11.6) 295 (11.6)
• Height mm (in) 1172 (46.1) 1002 (39.4) 1002 (39.4) 1516 (59.7) 1516 (59.7)
• Depth mm (in) 545 (21.5) 545 (21.5) 545 (21.5) 545 (21.5) 545 (21.5)
Weight, approx. kg (lb) 80 (176) 110 (243) 110 (243) 220 (485) 220 (485)
Frame size GXL HXL HXL JXL JXL
Minimum short-circuit current 7) kA 8 9.2 12.6 16 21

1) 4)
The base-load current IH DC is the basis for a duty cycle of 150 % for The value is valid for water as coolant.
60 s or Imax DC for 5 s with a duty cycle duration of 300 s. Additional information and notes on other coolants are provided in the
2)
The specified power loss represents the maximum value at 100 % SINAMICS Low Voltage Engineering Manual.
5)
utilization. The value is lower under normal operating conditions. To ensure Total sound pressure level of Active Interface Module and Active Line
safe dissipation of the minor power loss released to the ambient air, it is Module.
important to follow the instructions pertaining to control cabinet installation 6)
Total of all motor cables and DC link. Longer cable lengths for specific
in the SINAMICS Low Voltage Engineering Manual. configurations are available on request. For additional information, please
3)
The value applies to coolants comprising water and a mixture of water and refer to the SINAMICS Low Voltage Engineering Manual.
antifreeze agent. 7)
Current required for reliably triggering protective devices.

Siemens D 21.3 · 2022 3/77


© Siemens 2022

SINAMICS S120 Chassis Format Units


Liquid-cooled units
Active Line Modules

■ Technical specifications
Line voltage 500 ... 690 V 3 AC Active Line Modules
6SL3335- 6SL3335- 6SL3335- 6SL3335- 6SL3335- 6SL3335-
7TG35-8AA3 7TG37-4AA3 7TG38-1AA3 7TG41-0AA3 7TG41-3AA3 7TG41-6AA3
Rated power
• At IN DC (50 Hz 690 V) kW 630 800 900 1100 1400 1700
• At IH DC (50 Hz 690 V) kW 620 705 670 1000 1215 1490
• At IN DC (50 Hz 500 V) kW 447 560 620 780 965 1180
• At IH DC (50 Hz 500 V) kW 450 510 485 710 880 1080
• At IN DC (60 Hz 575 V) hp 675 900 975 1250 1500 1880
• At IH DC (60 Hz 575 V) hp 506 600 765 1000 1250 1530

3 DC link current
• Rated current IN DC A 644 823 907 1147 1422 1740
• Base-load current IH DC 1) A 573 732 808 936 1266 1550
• Maximum current Imax DC A 966 1235 1360 1722 2133 2620
Infeed/regenerative feedback current
• Rated current IN I A 575 735 810 1025 1270 1560
• Maximum current Imax I A 862 1100 1214 1537 1905 2055
Current demand
• 24 V DC auxiliary power supply A 1.6 1.6 1.6 1.6 1.46 1.5
DC link capacitance
• Active Line Module F 9670 10500 10500 16000 19330 21000
• Drive line-up, max. F 59200 153600 153600 153600 153600 210000
Pulse frequency kHz 2.5 2.5 2.5 2.5 2.5 2.5
Power loss, at 50 Hz 690 V 2)
• Dissipated to coolant kW 5.45 7.45 8.28 10.37 12.98 17.17
• Dissipated to ambient air kW 0.16 0.2 0.22 0.53 0.57 0.79
• Total kW 5.61 7.65 8.5 10.9 13.55 17.96
Coolant volume flow 3) l/min (US 16 (4.23) 16 (4.23) 16 (4.23) 27 (7.13) 27 (7.13) 27 (7.13)
gal./min)
Liquid volume dm3 0.74 0.74 0.74 1.56 1.56 1.56
of the integrated heat exchanger
Pressure drop, typ. 4) Pa 70000 70000 70000 70000 70000 70000
for volume flow
Heat exchanger material Aluminum Aluminum Aluminum Aluminum Aluminum Aluminum
Coolant connections Pipe thread ISO 228 G 3/4 B
Intake/return (external thread 3/4", flat-sealing)
Sound pressure level LpA 5) dB 70/73 71/73 71/73 71/73 71/73 71/73
(1 m) at 50/60 Hz
Line supply connection 2 × hole for M12 2 × hole for M12 2 × hole for M12 2 × hole for M12 2 × hole for M12 2 × hole for M12
U1, V1, W1
• Conductor cross-section, max. (IEC) mm2 4 × 185 4 × 185 4 × 185 Busbar Busbar Busbar
DC link connection 2 × hole for M12 2 × hole for M12 2 × hole for M12 2 × hole for M12 2 × hole for M12 2 × hole for M12
DCP, DCN Busbar Busbar Busbar Busbar Busbar Busbar
PE/GND connection 2 × hole for M12 2 × hole for M12 2 × hole for M12 2 × hole for M12 2 × hole for M12 2 × hole for M12
• Conductor cross-section, max. (IEC) mm2 4 × 185 4 × 185 4 × 185 Busbar Busbar Busbar
Cable length, max. 6)
• Shielded m (ft) 2250 (7382) 2250 (7382) 2250 (7382) 2250 (7382) 2250 (7382) 2250 (7382)
• Unshielded m (ft) 3375 (11073) 3375 (11073) 3375 (11073) 3375 (11073) 3375 (11073) 3375 (11073)
Dimensions
• Width mm (in) 265 (10.4) 265 (10.4) 265 (10.4) 265 (10.4) 265 (10.4) 265 (10.4)
• Height mm (in) 1002 (39.4) 1002 (39.4) 1002 (39.4) 1516 (59.7) 1516 (59.7) 1516 (59.7)
• Depth mm (in) 545 (21.5) 545 (21.5) 545 (21.5) 545 (21.5) 545 (21.5) 545 (21.5)
Weight, approx. kg (lb) 110 (243) 110 (243) 110 (243) 220 (485) 220 (485) 230 (507)
Frame size HXL HXL HXL JXL JXL JXL
Minimum short-circuit current 7) kA 8.4 10.5 12.6 16 20 24

1) 4)
The base-load current IH DC is the basis for a duty cycle of 150 % for The value is valid for water as coolant.
60 s or Imax DC for 5 s with a duty cycle duration of 300 s. Additional information and notes on other coolants are provided in the
2)
The specified power loss represents the maximum value at 100 % SINAMICS Low Voltage Engineering Manual.
5)
utilization. The value is lower under normal operating conditions. To ensure Total sound pressure level of Active Interface Module and Active Line
safe dissipation of the minor power loss released to the ambient air, it is Module.
important to follow the instructions pertaining to control cabinet installation 6)
Total of all motor cables and DC link. Longer cable lengths for specific
in the SINAMICS Low Voltage Engineering Manual. configurations are available on request. For additional information, please
3)
The value applies to coolants comprising water and a mixture of water and refer to the SINAMICS Low Voltage Engineering Manual.
antifreeze agent. 7)
Current required for reliably triggering protective devices.

3/78 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Chassis Format Units


Liquid-cooled units
Active Interface Modules

■ Overview ■ Design
Active Interface Modules have the following interfaces
as standard:
• 1 line supply connection
• 1 load connection
• 1 connection for the 24 V DC electronics power supply
• 1 connection for the external 230 V AC supply
• 1 DRIVE-CLiQ socket (on VSM10 Voltage Sensing Module)
• 1 connection for pre-charging circuit
• 1 PE/protective conductor connection
• 2 coolant connections 3
The scope of supply of the Active Interface Modules includes:
• Liquid-cooled filter reactor
• Liquid-cooled filter module
• Connection kit (cables and hoses)
• DRIVE-CLiQ cable for the connection between Active
Interface Module and Active Line Module
• 2 seals for coolant connections
• 1 set of warning labels in 30 languages
(BG, CN, CZ, DE, DK, EE, ES, FI, FR, GB, GR, HU, IE, IS, IT,
The Active Interface Module essentially comprises a liquid- JP, KR, LT, LV, MT, NL, NO, PL, PT, RO, RU, SE, SI, SK, TR)
cooled filter reactor and a liquid-cooled filter module. The filter
module contains a Clean Power Filter with basic RI suppression, Extended liability for defects
the pre-charging circuit for the Active Line Module, the line Siemens offers for SINAMICS S120 chassis units an extended
voltage sensing circuit and monitoring sensors. liability for defects/Service Protect up to 6½ years.
A bypass contactor is provided separately. Active Interface Details can be found in chapter
Modules are used in conjunction with Active Line Modules. Services and Documentation
Liquid-cooled Active Interface Modules cannot be supplied for
all liquid-cooled Active Line Modules. Where they are not
available, air-cooled Active Interface Modules can be ordered
instead.

■ Selection and ordering data


Suitable for Active Line Module Rated power of the Active Line Active Interface Module, Active Interface Module,
chassis format, liquid-cooled Modules at 400 V or 690 V liquid-cooled air-cooled
kW Article No. Article No.
Line voltage 380 ... 480 V 3 AC
6SL3335-7TE35-0AA3 300 – 1) 6SL3300-7TE35-0AA1
6SL3335-7TE36-1AA3 380 6SL3305-7TE38-4AA5 –
6SL3335-7TE38-4AA3 500 6SL3305-7TE38-4AA5 –
6SL3335-7TE41-0AA3 630 6SL3305-7TE41-4AA5 –
6SL3335-7TE41-4AA3 900 6SL3305-7TE41-4AA5 –
Line voltage 500 ... 690 V 3 AC
6SL3335-7TG35-8AA3 630 – 1) 6SL3300-7TG35-8AA1
6SL3335-7TG37-4AA3 800 6SL3305-7TG37-4AA5 –
6SL3335-7TG38-1AA3 900 6SL3305-7TG41-0AA5 –
6SL3335-7TG41-0AA3 1100 6SL3305-7TG41-0AA5 –
6SL3335-7TG41-3AA3 1400 6SL3305-7TG41-3AA5 –
6SL3335-7TG41-6AA3 1700 6SL3305-7TG41-6AA5 –

1)
For these power ratings, no liquid-cooled Active Interface Modules are
available. Air-cooled devices can be alternatively used. See the right-hand
column and additional information in section Air-cooled Active Interface
Modules.

Siemens D 21.3 · 2022 3/79


© Siemens 2022

SINAMICS S120 Chassis Format Units


Liquid-cooled units
Active Interface Modules

■ Integration
X500

DRIVE-CLiQ socket
-X609 Filter module
PE LED
1 READY
P24
External 2 X520
P24 5
24 V DC 3 M Active 6
4 M Interface Voltage
Sensing
L
3 5 Module Module
External 6
230 V AC 7
P7
N 8 Cooling circuit
1) 9
Control
pre-charging contactor 10
Pre-charging contactor
Control 1) 11
bypass contactor / fan 12
13
Contactors open 14
P5

Cooling circuit

Bypass contactor
P6
-K4
2/T1
4/T2
6/T3
-X1

3NE1 021-0
(100 A) G_D211_EN_00315b
U1 V1 W1 PE

P1 P3
2)
P4
Cooling circuit
Main switch

U1 U2
L1
V1 V2 to the
L2 Active
W1 W2 Line
L3
Module
PE PE PE

1) X1
Control via Active Line Module 1 2
2)
With line SCCR > 40 kA: SITOR 3NE3 231 (350 A)
Filter reactor

Connection example of liquid-cooled Active Interface Module with external bypass contactor, valid for article numbers 6SL3305-7TE41-4AA5 and
6SL3305-7TG41-6AA5

3/80 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Chassis Format Units


Liquid-cooled units
Active Interface Modules

■ Integration
X500

DRIVE-CLiQ socket
-X609 Filter module
PE LED
1 READY
P24
External 2 X520
P24 5
24 V DC 3 M Active 6
4 M Interface Voltage
L 5 Module Sensing Module
3
External 6
230 V AC 7
P7
N 8
1) 9
Control Cooling circuit
pre-charging contactor 10
Pre-charging contactor
Control 1) 11
bypass contactor / fan 12
13
Contactors open 14

Resistor and series


resonant circuit
components
Bypass contactor
P6
-K4
2/T1
4/T2
6/T3
-X1

3NE1 021-0
(100 A) G_D211_EN_00362a
U1 V1 W1 PE

2)
P1 P4
Cooling circuit
Main switch

U1 U2
L1
V1 V2 to the
L2 Active
W1 W2 Line
L3
Module
PE PE PE

1)
Control via Active Line Module X1
2) 1 2
With line SCCR > 40 kA: SITOR 3NE3 231 (350 A)
Filter reactor

Connection example of liquid-cooled Active Interface Module with external bypass contactor, valid for article numbers 6SL3305-7TE38-4AA5,
6SL3305-7TG37-4AA5, 6SL3305-7TG41-0AA5, and 6SL3305-7TG41-3AA5

Siemens D 21.3 · 2022 3/81


© Siemens 2022

SINAMICS S120 Chassis Format Units


Liquid-cooled units
Active Interface Modules

■ Technical specifications
Line voltage 380 ... 480 V 3 AC Active Interface Module
6SL3305-7TE38-4AA5 6SL3305-7TE41-4AA5
Suitable for Active Line Module
• Rated power at 400 V kW 380 500 630 900
- Liquid-cooled 6SL3335-7TE36-1AA3 6SL3335-7TE38-4AA3 6SL3335-7TE41-0AA3 6SL3335-7TE41-4AA3
Rated current A 605 840 985 1405
Bypass contactor 1) 3RT1476-6AP36 3WA1110-4AE03-4EQ0 3WA1112-4AE03-4EQ0 3WA1116-4AE03-4EQ0
Current demand
• 24 V DC auxiliary power supply A 0.17 0.17 0.17 0.17
• 230 V 2 AC
- Inrush current A 1.0 1.0 1.0 1.0
3 - Holding current A 0.1 0.1 0.1 0.1
DC link capacitance
• Drive line-up, max. 2) F 134400 134400 230400 230400
Coolant volume flow l/min (US 10 (2.64) 10 (2.64) 16 (4.23) 16 (4.23)
gal./min)
Pressure drop, typ. for volume flow Pa 70000 70000 70000 70000
Sound pressure level LpA dB 71/71 71/71 71/71 71/71
(1 m) at 50/60 Hz
Frame size JIL JIL JIL JIL
Filter reactor
Power loss 3)
• At 50 Hz 400 V kW 3.5 3.5 8.6 8.6
• At 60 Hz 460 V kW 3.5 3.5 8.6 8.6
• Dissipated to ambient air kW 1.2 1.2 0.9 0.9
Liquid volume
• Of integrated reactor cooler dm3 0.6 0.6 0.6 0.6
• Of hoses supplied dm3/m 0.285 0.285 0.285 0.285
Coolant volume flow l/min (US 10 (2.64) 10 (2.64) 8 (2.11) 8 (2.11)
gal./min)
Heat exchanger material Aluminum Aluminum Aluminum Aluminum
Coolant connections Pipe thread ISO 228 G 3/4 B
Return and connection to filter module (external thread 3/4", flat-sealing)
Line/load connection Flat connector for M12 Flat connector for M12 Flat connector for M12 Flat connector for M12
L1, L2, L3 / U2, V2, W2 screws screws screws screws
PE/GND connection M10 stud M10 stud M10 stud M10 stud
• Conductor cross-section, max. (IEC) mm2 1 × 240 1 × 240 1 × 240 1 × 240
Degree of protection IP00 IP00 IP00 IP00
Dimensions
• Width mm (in) 349 (13.7) 349 (13.7) 382 (15.0) 382 (15.0)
• Height mm (in) 700 (27.6) 700 (27.6) 698 (27.5) 698 (27.5)
• Depth mm (in) 575 (22.6) 575 (22.6) 575 (22.6) 575 (22.6)
Weight, approx. kg (lb) 230 (507) 230 (507) 299 (659) 299 (659)
Filter module
Power loss 3)
• At 50 Hz 400 V kW 2.7 2.7 3.6 3.6
• At 60 Hz 460 V kW 2.7 2.7 3.6 3.6
• Dissipated to ambient air kW 0.15 0.15 0.15 0.15
Liquid volume dm3 1 1 1 1
Heat exchanger material Aluminum Aluminum Aluminum Aluminum
Coolant connections Pipe thread ISO 228 G 3/4 B
Intake and connection to filter reactor (external thread 3/4", flat-sealing)
PE/GND connection Flat connector for M8 Flat connector for M8 Flat connector for M8 Flat connector for M8
screw screw screw screw
2
• Conductor cross-section, max. (IEC) mm 2 × 120 2 × 120 2 × 120 2 × 120
Degree of protection IP00 IP00 IP00 IP00
Dimensions
• Width mm (in) 506 (19.9) 506 (19.9) 506 (19.9) 506 (19.9)
• Height mm (in) 840 (33.1) 840 (33.1) 840 (33.1) 840 (33.1)
• Depth mm (in) 574 (22.6) 574 (22.6) 574 (22.6) 574 (22.6)
Weight, approx. kg (lb) 110 (243) 110 (243) 110 (243) 110 (243)

1) 3)
The bypass contactor is not included in the scope of supply. The specified power loss represents the maximum value at 100 %
2)
Information on higher capacitances is included in the SINAMICS Low utilization. The value is lower under normal operating conditions. To ensure
Voltage Engineering Manual. safe dissipation of the minor power loss released to the ambient air, it is
important to follow the instructions pertaining to control cabinet installation
in the SINAMICS Low Voltage Engineering Manual.

3/82 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Chassis Format Units


Liquid-cooled units
Active Interface Modules

■ Technical specifications
Line voltage 500 ... 690 V 3 AC Active Interface Modules
6SL3305-7TG37-4AA5 6SL3305-7TG41-0AA5 6SL3305-7TG41-3AA5 6SL3305-7TG41-6AA5
Suitable for Active Line Module
• Rated power at 690 V kW 800 900/1100 1400 1700
- Liquid-cooled 6SL3335-7TG37-4AA3 6SL3335-7TG38-1AA3 6SL3335-7TG41-3AA3 6SL3335-7TG41-6AA3
6SL3335-7TG41-0AA3
Rated current A 735 1025 1270 1560
Bypass contactor 1) 3RT1476-6AP36 3WA1220-4AE03-4EQ0-Z 3WA1220-4AE03-4EQ0-Z 3WA1220-4AE03-4EQ0-Z
(3 units) B12 B16 B16
Current demand
• 24 V DC auxiliary power supply A 0.17 0.17 0.17 0.17
• 230 V 2 AC
- Inrush current A 1.0 1.0 1.0 1.0
3
- Holding current A 0.1 0.1 0.1 0.1
DC link capacitance
• Drive line-up, max. 2) F 153600 153600 153600 210000
Coolant volume flow l/min (US 10 (2.64) 10 (2.64) 10 (2.64) 16 (4.23)
gal./min)
Pressure drop, typ. for volume flow Pa 70000 70000 70000 70000
Sound pressure level LpA dB 71/71 71/71 71/71 71/71
(1 m) at 50/60 Hz
Frame size JIL JIL JIL JIL
Filter reactor
Power loss 3)
• At 50 Hz 690 V kW 5.5 6.2 9.3 11.0
• At 60 Hz 575 V kW 5.5 6.2 9.3 11.0
• Dissipated to ambient air kW 0.5 0.6 0.95 1.15
Liquid volume
• Of integrated reactor cooler dm3 0.6 0.6 0.6 0.6
• Of hoses supplied dm3/m 0.285 0.285 0.285 0.285
Coolant volume flow l/min (US 10 (2.64) 10 (2.64) 10 (2.64) 8 (2.11)
gal./min)
Heat exchanger material Aluminum Aluminum Aluminum Aluminum
Coolant connections Pipe thread ISO 228 G 3/4 B
Return and connection to filter module (external thread 3/4", flat-sealing)
Line/load connection Flat connector for M12 Flat connector for M12 Flat connector for M12 Flat connector for M12
L1, L2, L3 / U2, V2, W2 screws screws screws screws
PE/GND connection M10 stud M10 stud M10 stud M10 stud
• Conductor cross-section, max. (IEC) mm2 1 × 240 1 × 240 1 × 240 1 × 240
Degree of protection IP00 IP00 IP00 IP00
Dimensions
• Width mm (in) 358 (14.1) 440 (17.3) 440 (17.3) 440 (17.3)
• Height mm (in) 675 (26.6) 705 (27.8) 705 (27.8) 705 (27.8)
• Depth mm (in) 575 (22.6) 575 (22.6) 575 (22.6) 580 (22.8)
Weight, approx. kg (lb) 234 (516) 365 (805) 365 (805) 365 (805)
Filter module
Power loss 3)
• At 50 Hz 690 V kW 4.0 5.0 5.0 7.5
• At 60 Hz 575 V kW 4.0 5.0 5.0 7.5
• Dissipated to ambient air kW 0.15 0.15 0.15 0.15
Liquid volume dm3 1 1 1 1
Heat exchanger material Aluminum Aluminum Aluminum Aluminum
Coolant connections Pipe thread ISO 228 G 3/4 B
Intake and connection to filter reactor (external thread 3/4", flat-sealing)
PE/GND connection Flat connector for M8 Flat connector for M8 Flat connector for M8 Flat connector for M8
screw screw screw screw
• Conductor cross-section, max. (IEC) mm2 2 × 120 2 × 120 2 × 120 2 × 120
Degree of protection IP00 IP00 IP00 IP00
Dimensions
• Width mm (in) 506 (19.9) 506 (19.9) 506 (19.9) 506 (19.9)
• Height mm (in) 840 (33.1) 840 (33.1) 840 (33.1) 840 (33.1)
• Depth mm (in) 574 (22.6) 574 (22.6) 574 (22.6) 574 (22.6)
Weight, approx. kg (lb) 110 (243) 110 (243) 110 (243) 110 (243)

1) 3)
The bypass contactor is not included in the scope of supply. The specified power loss represents the maximum value at 100 %
2)
Information on higher capacitances is included in the SINAMICS Low utilization. The value is lower under normal operating conditions. To ensure
Voltage Engineering Manual. safe dissipation of the minor power loss released to the ambient air, it is
important to follow the instructions pertaining to control cabinet installation
in the SINAMICS Low Voltage Engineering Manual.

Siemens D 21.3 · 2022 3/83


© Siemens 2022

SINAMICS S120 Chassis Format Units


Liquid-cooled units
Motor Modules

■ Overview ■ Selection and ordering data


Type rating Rated output current Motor Module
at 400 V or 690 V
kW A Article No.
Line voltage 380 ... 480 V 3 AC
(DC link voltage 510 ... 720 V DC)
110 210 6SL3325-1TE32-1AA3
132 260 6SL3325-1TE32-6AA3
160 310 6SL3325-1TE33-1AA3
250 490 6SL3325-1TE35-0AA3
3 315 605 6SL3325-1TE36-1AA3
400 745 6SL3325-1TE37-5AA3
450 840 6SL3325-1TE38-4AA3
560 985 6SL3325-1TE41-0AA3
710 1260 6SL3325-1TE41-2AA3
800 1405 6SL3325-1TE41-4AA3
800 1) 1330 6SL3325-1TE41-4AS3
Line voltage 500 ... 690 V 3 AC
(DC link voltage 675 ... 1035 V DC)
90 100 6SL3325-1TG31-0AA3
132 150 6SL3325-1TG31-5AA3
A Motor Module comprises a self-commutated inverter with 200 215 6SL3325-1TG32-2AA3
IGBTs. It generates a variable voltage with variable frequency
from the DC link voltage that feeds the connected motor. 315 330 6SL3325-1TG33-3AA3
450 465 6SL3325-1TG34-7AA3
Multiple Motor Modules can be operated on a single DC link.
This permits energy to be transferred between the Motor 560 575 6SL3325-1TG35-8AA3
Modules. This means that if one Motor Module operating in 710 735 6SL3325-1TG37-4AA3
generator mode produces energy, the energy can be used by
800 810 6SL3325-1TG38-0AA3
another Motor Module operating in motor mode.
800 810 6SL3325-1TG38-1AA3
Motor Modules are controlled by a Control Unit.
1000 1025 6SL3325-1TG41-0AA3
Liquid-cooled Motor Modules are especially suitable for
1200 1270 6SL3325-1TG41-3AA3
applications where installation space is restricted and
environmental conditions are harsh. Liquid cooling ensures 1500 1560 6SL3325-1TG41-6AP3
efficient heat dissipation.
Extended liability for defects

■ Design Siemens offers for SINAMICS S120 chassis units an extended


liability for defects/Service Protect up to 6½ years.
The liquid-cooled Motor Modules have the following interfaces
as standard: Details can be found in chapter
Services and Documentation
• 1 motor connection
• 1 connection for the 24 V DC electronics power supply Accessories

• 1 DC link connection (DCP, DCN) for connecting to the supply Description Article No.
DC link
3-way valve 1) VXF41...
• 3 DRIVE-CLiQ sockets VXG41...
• 1 temperature sensor input for KTY84-130, Pt1000, PTC or Actuator for 3-way valve 2)
Pt100 (Pt1000 can be used from firmware V4.7 HF17 and • 230 V 1 AC SAX31...
higher) • 24 V AC/DC SAX61...
• 1 connection for Safe Brake Adapter SAX81...
• 1 connection for Safety Integrated Accessories for re-ordering
• 2 PE/protective conductor connections Dust protection blanking plugs 6SL3066-4CA00-0AA0
• 2 coolant connections (50 units)
For DRIVE-CLiQ port
The status of the Motor Modules is indicated via three LEDs.
For motor-side components, see System components.
The scope of supply of the Motor Modules includes:
• 1 DRIVE-CLiQ cable for connection to the Control Unit
• 2 seals for coolant connections
• 1 set of warning labels in 30 languages
(BG, CN, CZ, DE, DK, EE, ES, FI, FR, GB, GR, HU, IE, IS, IT,
JP, KR, LT, LV, MT, NL, NO, PL, PT, RO, RU, SE, SI, SK, TR) 1)
This Motor Module has been specifically designed for loads demanding a
high dynamic performance.
2)
Recommended components for installing a flow control as condensation
protection; manufactured by Siemens Building Technologies.

3/84 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Chassis Format Units


Liquid-cooled units
Motor Modules

■ Integration
The liquid-cooled Motor Modules communicate with the higher-level control module via DRIVE-CLiQ. The control module in this case
can be a CU320-2 or a SIMOTION D Control Unit.

X400 X401 X402

DRIVE-CLiQ socket 0

DRIVE-CLiQ socket 1

DRIVE-CLiQ socket 2
DCP
DC link DCN

Motor
Module
chassis =

-X9
format = 3
1 P24 V
ext.
24 V DC 1
2 M
2 Internal
power supply -X2 PE
3
VL1
4 U2
VL2 =
5 V2 M
HS1
6 ~ W2 3~
HS2
7
EP +24 V
8
EP M1

-X41
4 READY
LEDs

+Temp
3 -Temp DC LINK
2
EP +24 V
1 POWER OK
EP M1 Cooling circuit

-X42
1 P24L
2 P24L
3 M
4 M

-X46 IPD Card


1 BR Output+
2
G_D213_EN_00041d

BR Output-
3 FB Input+
4 FB Input-

Connection example of a liquid-cooled Motor Module

■ Technical specifications
General technical specifications
Electrical specifications
Efficiency 98.5 %
DC link voltage 510 ... 720 V DC (line voltage 380 ... 480 V 3 AC) or
(up to 2000 m (6562 ft) above sea level) 675 ... 1035 V DC (line voltage 500 ... 690 V 3 AC)
Output frequency 1)
• Control mode Servo 0 ... 550 Hz
• Control mode Vector 0 ... 550 Hz
• Control mode V/f 0 ... 550 Hz
Safety Integrated Safety Integrity Level 2 (SIL2) acc. to IEC 61508, Performance Level d (PLd) acc. to EN ISO 13849-1 and Control
Category 3 acc. to EN ISO 13849-1.

1)
Please note:
• The correlation between the maximum output frequency, pulse frequency
and current derating. Higher output frequencies on request. For more
information, see
https://support.industry.siemens.com/cs/document/104020669
• The correlation between the minimum output frequency and permissible
output current (current derating).
For additional information, please refer to the SINAMICS Low Voltage
Engineering Manual.

Siemens D 21.3 · 2022 3/85


© Siemens 2022

SINAMICS S120 Chassis Format Units


Liquid-cooled units
Motor Modules

■ Technical specifications
Line voltage 380 ... 480 V 3 AC Motor Modules
DC link voltage 510 ... 720 V DC
6SL3325- 6SL3325- 6SL3325- 6SL3325- 6SL3325-
1TE32-1AA3 1TE32-6AA3 1TE33-1AA3 1TE35-0AA3 1TE36-1AA3
Type rating
• At IL (50 Hz 400 V) 1) kW 110 132 160 250 315
• At IH (50 Hz 400 V) 1) kW 90 110 132 200 250
• At IL (60 Hz 460 V) 2) hp 150 200 250 400 500
• At IH (60 Hz 460 V) 2) hp 150 200 200 350 350
Output current

3 • Rated current IN O
• Base-load current IL 3)
A
A
210
205
260
250
310
302
490
477
605
590
• Base-load current IH 4) A 178 233 277 438 460
• Maximum current Imax O A 307 375 453 715 885
DC link current
• Rated current IN DC
when supplied via
- Basic Line Module A 256 317 380 600 738
- Active Line Module A 230 287 340 538 664
• Base-load current IL DC 3)
when supplied via
- Basic Line Module A 250 305 368 581 719
- Active Line Module A 225 274 331 522 646
• Base-load current IH DC 4)
when supplied via
- Basic Line Module A 227 284 338 534 561
- Active Line Module A 195 255 303 480 504
Current demand
• 24 V DC auxiliary power supply A 1.4 1.4 1.5 1.5 1.6
DC link capacitance F 4800 5800 8400 9600 12600
Pulse frequency 5)
• Rated frequency kHz 2 2 2 2 1.25
• Pulse frequency, max.
- Without current derating kHz 2 2 2 2 1.25
- With current derating kHz 8 8 8 8 8
Power loss, max. 6)
• At 50 Hz 400 V kW 1.61 1.95 2.29 3.56 4.81
• At 60 Hz 460 V kW 1.68 2.06 2.38 3.74 5.25
• Dissipated to ambient air kW 0.06 0.07 0.09 0.14 0.16
Coolant volume flow 7) l/min (US 9 (2.38) 9 (2.38) 12 (3.17) 12 (3.17) 16 (4.23)
gal./min)
Liquid volume dm3 0.31 0.31 0.91 0.91 0.74
of the integrated heat exchanger
Pressure drop, typ. 8) Pa 70000 70000 70000 70000 70000
for volume flow
Heat exchanger material Stainless steel Stainless steel Stainless steel Stainless steel Aluminum
Coolant connections Pipe thread ISO 228 G 3/4 B
Intake/return (external thread 3/4", flat-sealing)
Sound pressure level LpA dB 52 52 52 52 54
(1 m) at 50/60 Hz
DC link connection 2 × hole for M12 2 × hole for M12 2 × hole for M12 2 × hole for M12 2 × hole for M12
DCP, DCN Busbar Busbar Busbar Busbar Busbar
Motor connection Hole for M12 Hole for M12 Hole for M12 Hole for M12 2 × hole for M12
U2, V2, W2
2
• Conductor cross-section, max. (IEC) mm 2 × 95 2 × 95 2 × 240 2 × 240 4 × 185
PE/GND connection 2 × hole for M12 2 × hole for M12 2 × hole for M12 2 × hole for M12 2 × hole for M12
• Conductor cross-section, max. (IEC) mm2 2 × 95 2 × 95 2 × 240 2 × 240 4 × 185

3/86 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Chassis Format Units


Liquid-cooled units
Motor Modules

■ Technical specifications
Line voltage 380 ... 480 V 3 AC Motor Modules
DC link voltage 510 ... 720 V DC
6SL3325- 6SL3325- 6SL3325- 6SL3325- 6SL3325-
1TE32-1AA3 1TE32-6AA3 1TE33-1AA3 1TE35-0AA3 1TE36-1AA3
Cable length, max. 9)
• Shielded m (ft) 300 (984) 300 (984) 300 (984) 300 (984) 300 (984)
• Unshielded m (ft) 450 (1476) 450 (1476) 450 (1476) 450 (1476) 450 (1476)
Dimensions
• Width mm (in) 150 (5.91) 150 (5.91) 150 (5.91) 150 (5.91) 265 (10.4)
• Height mm (in) 746 (29.4) 746 (29.4) 1172 (46.1) 1172 (46.1) 1002 (39.4)
• Depth
Weight, approx.
mm (in)
kg (lb)
545 (21.5)
41 (90.4)
545 (21.5)
41 (90.4)
545 (21.5)
80 (176)
545 (21.5)
80 (176)
545 (21.5)
110 (243)
3
Frame size FXL FXL GXL GXL HXL

1) 6)
Rated power of a typical 6-pole standard induction motor based on IL or IH The specified power loss represents the maximum value at 100 %
for 400 V 3 AC 50 Hz. utilization. The value is lower under normal operating conditions. To ensure
2)
Rated power of a typical 6-pole standard induction motor based on IL or IH safe dissipation of the minor power loss released to the ambient air, it is
for 460 V 3 AC 60 Hz. important to follow the instructions pertaining to control cabinet installation
3)
in the SINAMICS Low Voltage Engineering Manual.
The base-load current IL is based on a duty cycle of 110 % for 60 s or 7)
150 % for 10 s with a duty cycle duration of 300 s. The value applies to coolants comprising water and a mixture of water and
4)
antifreeze agent.
The base-load current IH is based on a duty cycle of 150 % for 60 s or 8)
160 % for 10 s with a duty cycle duration of 300 s. The value is valid for water as coolant.
5)
Additional information and notes on other coolants are provided in the
Additional notes regarding the correlation between the pulse frequency SINAMICS Low Voltage Engineering Manual.
and maximum output current/output frequency is provided in the 9)
SINAMICS Low Voltage Engineering Manual. Total of all motor cables. Longer cable lengths for specific configurations
are available on request.
For additional information, please refer to the SINAMICS Low Voltage
Engineering Manual.

Siemens D 21.3 · 2022 3/87


© Siemens 2022

SINAMICS S120 Chassis Format Units


Liquid-cooled units
Motor Modules

■ Technical specifications
Line voltage 380 ... 480 V 3 AC Motor Modules
DC link voltage 510 ... 720 V DC
6SL3325- 6SL3325- 6SL3325- 6SL3325- 6SL3325- 6SL3325-
1TE37-5AA3 1TE38-4AA3 1TE41-0AA3 1TE41-2AA3 1TE41-4AA3 1TE41-4AS3 1)
Type rating
• At IL (50 Hz 400 V) 2) kW 400 450 560 710 800 800
• At IH (50 Hz 400 V) 2) kW 315 400 450 630 710 630
• At IL (60 Hz 460 V) 3) hp 600 700 800 1000 1150 1000
• At IH (60 Hz 460 V) 3) hp 450 600 700 900 1000 900
Output current

3 • Rated current IN O
• Base-load current IL 4)
A
A
745
725
840
820
985
960
1260
1230
1405
1370
1330
1310
• Base-load current IH 5) A 570 700 860 1127 1257 1150
• Maximum current Imax O A 1087 1230 1440 1845 2055 2055
DC link current
• Rated current IN DC
when supplied via
- Basic Line Module A 894 1025 1202 1512 1714 1550
- Active Line Module A 805 922 1080 1361 1544 1403
• Base-load current IL DC 4)
when supplied via
- Basic Line Module A 871 1000 1170 1474 1670 1525
- Active Line Module A 784 898 1051 1326 1500 1405
• Base-load current IH DC 5)
when supplied via
- Basic Line Module A 795 853 1048 1345 1532 1676
- Active Line Module A 716 767 942 1211 1377 1403
Current demand
• 24 V DC auxiliary power supply A 1.6 1.6 1.46 1.46 1.46 1.46
DC link capacitance F 17400 17400 21000 29000 29000 21000
Pulse frequency 6)
• Rated frequency kHz 1.25 1.25 1.25 1.25 1.25 2
• Pulse frequency, max.
- Without current derating kHz 1.25 1.25 1.25 1.25 1.25 2
- With current derating kHz 8 8 8 8 8 4
Power loss, max. 6)
• At 50 Hz 400 V kW 5.1 5.75 7.9 9.15 10.2 10.9
• At 60 Hz 460 V kW 5.61 6.33 8.55 10.05 11.2 12.3
• Dissipated to ambient air kW 0.2 0.23 0.44 0.56 0.62 0.65
Coolant volume flow 8) l/min (US 16 (4.23) 16 (4.23) 27 (7.13) 27 (7.13) 27 (7.13) 27 (7.13)
gal./min)
Liquid volume dm3 0.74 0.74 1.56 1.56 1.56 1.56
of the integrated heat exchanger
Pressure drop, typ. 9) Pa 70000 70000 70000 70000 70000 70000
for volume flow
Heat exchanger material Aluminum Aluminum Aluminum Aluminum Aluminum Aluminum
Coolant connections Pipe thread ISO 228 G 3/4 B
Intake/return (external thread 3/4", flat-sealing)
Sound pressure level LpA dB 54 54 56 56 56 56
(1 m) at 50/60 Hz
DC link connection 2 × hole for M12 2 × hole for M12 2 × hole for M12 2 × hole for M12 2 × hole for M12 2 × hole for M12
DCP, DCN Busbar Busbar Busbar Busbar Busbar Busbar
Motor connection 2 × hole for M12 2 × hole for M12 2 × hole for M12 2 × hole for M12 2 × hole for M12 2 × hole for M12
U2, V2, W2
2
• Conductor cross-section, max. (IEC) mm 4 × 185 4 × 185 4 × 240 4 × 240 4 × 240 4 × 240
PE/GND connection 2 × hole for M12 2 × hole for M12 2 × hole for M12 2 × hole for M12 2 × hole for M12 2 × hole for M12
• Conductor cross-section, max. (IEC) mm2 4 × 185 4 × 185 Busbar Busbar Busbar Busbar

3/88 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Chassis Format Units


Liquid-cooled units
Motor Modules

■ Technical specifications
Line voltage 380 ... 480 V 3 AC Motor Modules
DC link voltage 510 ... 720 V DC
6SL3325- 6SL3325- 6SL3325- 6SL3325- 6SL3325- 6SL3325-
1TE37-5AA3 1TE38-4AA3 1TE41-0AA3 1TE41-2AA3 1TE41-4AA3 1TE41-4AS3 1)
Cable length, max. 10)
• Shielded m (ft) 300 (984) 300 (984) 300 (984) 300 (984) 300 (984) 300 (984)
• Unshielded m (ft) 450 (1476) 450 (1476) 450 (1476) 450 (1476) 450 (1476) 450 (1476)
Dimensions
• Width mm (in) 265 (10.4) 265 (10.4) 295 (11.6) 295 (11.6) 295 (11.6) 295 (11.6)
• Height mm (in) 1002 (39.4) 1002 (39.4) 1516 (59.7) 1516 (59.7) 1516 (59.7) 1516 (59.7)
• Depth
Weight, approx.
mm (in)
kg (lb)
545 (21.5)
110 (243)
545 (21.5)
110 (243)
545 (21.5)
220 (485)
545 (21.5)
220 (485)
545 (21.5)
220 (485)
545 (21.5)
230 (507)
3
Frame size HXL HXL JXL JXL JXL JXL

1) 7)
This Motor Module has been specifically designed for loads demanding a The specified power loss represents the maximum value at 100 %
high dynamic performance. The derating factor kIGBT and the derating utilization. The value is lower under normal operating conditions. To ensure
characteristics can be ignored (see section “Duty cycles” in the SINAMICS safe dissipation of the minor power loss released to the ambient air, it is
Low Voltage Engineering Manual). important to follow the instructions pertaining to control cabinet installation
2)
Rated power of a typical 6-pole standard induction motor based on IL or IH in the SINAMICS Low Voltage Engineering Manual.
8)
for 400 V 3 AC 50 Hz. The value applies to coolants comprising water and a mixture of water and
3)
Rated power of a typical 6-pole standard induction motor based on IL or IH antifreeze agent.
9)
for 460 V 3 AC 60 Hz. The value is valid for water as coolant.
4)
The base-load current IL is based on a duty cycle of 110 % for 60 s or Additional information and notes on other coolants are provided in the
150 % for 10 s with a duty cycle duration of 300 s. SINAMICS Low Voltage Engineering Manual.
10)
5)
The base-load current IH is based on a duty cycle of 150 % for 60 s or Total of all motor cables. Longer cable lengths for specific configurations
160 % for 10 s with a duty cycle duration of 300 s. are available on request.
6)
For additional information, please refer to the SINAMICS Low Voltage
Additional notes regarding the correlation between the pulse frequency Engineering Manual.
and maximum output current/output frequency is provided in the
SINAMICS Low Voltage Engineering Manual.

Siemens D 21.3 · 2022 3/89


© Siemens 2022

SINAMICS S120 Chassis Format Units


Liquid-cooled units
Motor Modules

■ Technical specifications
Line voltage 500 ... 690 V 3 AC Motor Modules
DC link voltage 675 ... 1035 V DC
6SL3325- 6SL3325- 6SL3325- 6SL3325- 6SL3325- 6SL3325-
1TG31-0AA3 1TG31-5AA3 1TG32-2AA3 1TG33-3AA3 1TG34-7AA3 1TG35-8AA3
Type rating
• At IL (50 Hz 690 V) 1) kW 90 132 200 315 450 560
• At IH (50 Hz 690 V) 1) kW 75 110 160 250 400 450
• At IL (50 Hz 500 V) 1) kW 55 90 132 200 315 400
• At IH (50 Hz 500 V) 1) kW 55 90 132 200 250 315
• At IL (60 Hz 575 V) 2) hp 75 150 200 300 450 600
• At IH (60 Hz 575 V) 2) hp 75 125 200 250 450 500
3 Output current
• Rated current IN O A 100 150 215 330 465 575
• Base-load current IL 3) A 95 142 208 320 452 560
• Base-load current IH 4) A 89 134 192 280 416 514
• Maximum current Imax O A 142 213 312 480 678 840
DC link current
• Rated current IN DC
when supplied via
- Basic Line Module A 122 183 263 403 558 702
- Active Line Module A 110 165 237 363 502 632
• Base-load current IL DC 3)
when supplied via
- Basic Line Module A 116 173 253 390 544 683
- Active Line Module A 105 156 229 352 489 616
• Base-load current IH DC 4)
when supplied via
- Basic Line Module A 108 163 234 341 496 627
- Active Line Module A 98 147 211 308 446 565
Current demand
• 24 V DC auxiliary power supply A 1.0 1.0 1.5 1.5 1.6 1.6
DC link capacitance F 2800 2800 4200 5800 9670 9670
Pulse frequency 5)
• Rated frequency kHz 1.25 1.25 1.25 1.25 1.25 1.25
• Pulse frequency, max.
- Without current derating kHz 1.25 1.25 1.25 1.25 1.25 1.25
- With current derating kHz 7.5 7.5 7.5 7.5 7.5 7.5
Power loss, max. 6)
• At 50 Hz 690 V kW 1.15 1.64 2.34 3.38 5.44 5.61
• At 60 Hz 575 V kW 1.02 1.45 2.05 2.96 5.1 5.45
• Dissipated to ambient air kW 0.06 0.07 0.09 0.12 0.14 0.16
Coolant volume flow 7) l/min (US 9 (2.38) 9 (2.38) 12 (3.17) 12 (3.17) 16 (4.23) 16 (4.23)
gal./min)
Liquid volume dm3 0.31 0.31 0.91 0.91 0.74 0.74
of the integrated heat exchanger
Pressure drop, typ. 8) Pa 70000 70000 70000 70000 70000 70000
for volume flow
Heat exchanger material Stainless steel Stainless steel Stainless steel Stainless steel Aluminum Aluminum
Coolant connections Pipe thread ISO 228 G 3/4 B
Intake/return (external thread 3/4", flat-sealing)
Sound pressure level LpA dB 52 52 52 52 54 54
(1 m) at 50/60 Hz
DC link connection 2 × hole for M12 2 × hole for M12 2 × hole for M12 2 × hole for M12 2 × hole for M12 2 × hole for M12
DCP, DCN Busbar Busbar Busbar Busbar Busbar Busbar
Motor connection Hole for M12 Hole for M12 Hole for M12 Hole for M12 2 × hole for M12 2 × hole for M12
U2, V2, W2
2
• Conductor cross-section, max. (IEC) mm 2 × 95 2 × 95 4 × 240 4 × 240 4 × 185 4 × 185
PE/GND connection 2 × hole for M12 2 × hole for M12 2 × hole for M12 2 × hole for M12 2 × hole for M12 2 × hole for M12
• Conductor cross-section, max. (IEC) mm2 2 × 95 2 × 95 2 × 240 2 × 240 4 × 185 4 × 185

3/90 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Chassis Format Units


Liquid-cooled units
Motor Modules

■ Technical specifications
Line voltage 500 ... 690 V 3 AC Motor Modules
DC link voltage 675 ... 1035 V DC
6SL3325- 6SL3325- 6SL3325- 6SL3325- 6SL3325- 6SL3325-
1TG31-0AA3 1TG31-5AA3 1TG32-2AA3 1TG33-3AA3 1TG34-7AA3 1TG35-8AA3
Cable length, max. 9)
• Shielded m (ft) 300 (984) 300 (984) 300 (984) 300 (984) 300 (984) 300 (984)
• Unshielded m (ft) 450 (1476) 450 (1476) 450 (1476) 450 (1476) 450 (1476) 450 (1476)
Dimensions
• Width mm (in) 150 (5.91) 150 (5.91) 150 (5.91) 150 (5.91) 265 (10.4) 265 (10.4)
• Height mm (in) 728 (28.7) 728 (28.7) 1172 (46.1) 1172 (46.1) 1002 (39.4) 1002 (39.4)
• Depth
Weight, approx.
mm (in)
kg (lb)
545 (21.5)
41 (90.4)
545 (21.5)
41 (90.4)
545 (21.5)
80 (176)
545 (21.5)
80 (176)
545 (21.5)
110 (243)
545 (21.5)
110 (243)
3
Frame size FXL FXL GXL GXL HXL HXL

1) 6)
Rated power of a typical 6-pole standard induction motor based on IL or IH The specified power loss represents the maximum value at 100 %
for 500 V or 690 V 3 AC 50 Hz. utilization. The value is lower under normal operating conditions. To ensure
2)
Rated power of a typical 6-pole standard induction motor based on IL or IH safe dissipation of the minor power loss released to the ambient air, it is
for 575 V 3 AC 60 Hz. important to follow the instructions pertaining to control cabinet installation
3)
in the SINAMICS Low Voltage Engineering Manual.
The base-load current IL is based on a duty cycle of 110 % for 60 s or 7)
150 % for 10 s with a duty cycle duration of 300 s. The value applies to coolants comprising water and a mixture of water and
4)
antifreeze agent.
The base-load current IH is based on a duty cycle of 150 % for 60 s or 8)
160 % for 10 s with a duty cycle duration of 300 s. The value is valid for water as coolant.
5)
Additional information and notes on other coolants are provided in the
Additional notes regarding the correlation between the pulse frequency SINAMICS Low Voltage Engineering Manual.
and maximum output current/output frequency is provided in the 9)
SINAMICS Low Voltage Engineering Manual. Total of all motor cables. Longer cable lengths for specific configurations
are available on request.
For additional information, please refer to the SINAMICS Low Voltage
Engineering Manual.

Siemens D 21.3 · 2022 3/91


© Siemens 2022

SINAMICS S120 Chassis Format Units


Liquid-cooled units
Motor Modules

■ Technical specifications
Line voltage 500 ... 690 V 3 AC Motor Modules
DC link voltage 675 ... 1035 V DC
6SL3325- 6SL3325- 6SL3325- 6SL3325- 6SL3325- 6SL3325-
1TG37-4AA3 1TG38-0AA3 1) 1TG38-1AA3 1TG41-0AA3 1TG41-3AA3 1TG41-6AP3 11)
Type rating
• At IL (50 Hz 690 V) 2) kW 710 800 800 1000 1200 1500
• At IH (50 Hz 690 V) 2) kW 630 710 710 900 1000 1260
• At IL (50 Hz 500 V) 2) kW 500 560 560 710 900 1000
• At IH (50 Hz 500 V) 2) kW 450 500 560 630 800 900
• At IL (60 Hz 575 V) 3) hp 700 800 800 1000 1250 1500
• At IH (60 Hz 575 V) 3) hp 700 700 700 900 1000 1250
3 Output current
• Rated current IN O A 735 810 810 1025 1270 1560
• Base-load current IL 4) A 710 790 790 1000 1230 1500
• Base-load current IH 5) A 657 724 724 917 1136 1370
• Maximum current Imax O A 1065 1185 1185 1500 1845 2250
DC link current
• Rated current IN DC
when supplied via
- Basic Line Module A 903 990 990 1250 1550 1903
- Active Line Module A 808 891 891 1125 1395 1714
• Base-load current IL DC 4)
when supplied via
- Basic Line Module A 870 948 963 1219 1500 1800
- Active Line Module A 781 870 869 1100 1353 1650
• Base-load current IH DC 5)
when supplied via
- Basic Line Module A 795 885 883 1118 1384 1680
- Active Line Module A 732 808 796 1009 1250 1550
Current demand
• 24 V DC auxiliary power supply A 1.6 1.6 1.46 1.46 1.46 1.46
DC link capacitance F 10500 10500 14000 16000 19330 21000
Pulse frequency 6)
• Rated frequency kHz 1.25 1.25 1.25 1.25 1.25 1.25
• Pulse frequency, max.
- Without current derating kHz 1.25 1.25 1.25 1.25 1.25 1.25
- With current derating kHz 7.5 7.5 7.5 7.5 7.5 7.5
Power loss, max. 6)
• At 50 Hz 690 V kW 7.65 8.47 9.56 10.87 13.49 17.9
• At 60 Hz 575 V kW 6.67 7.39 8.34 9.55 11.84 15.7
• Dissipated to ambient air kW 0.2 0.22 0.43 0.53 0.57 0.78
Coolant volume flow 8) l/min (US 16 (4.23) 16 (4.23) 27 (7.13) 27 (7.13) 27 (7.13) 27 (7.13)
gal./min)
Liquid volume dm3 0.74 0.74 1.56 1.56 1.56 1.56
of the integrated heat exchanger
Pressure drop, typ. 9) Pa 70000 70000 70000 70000 70000 70000
for volume flow
Heat exchanger material Aluminum Aluminum Aluminum Aluminum Aluminum Aluminum
Coolant connections Pipe thread ISO 228 G 3/4 B
Intake/return (external thread 3/4", flat-sealing)
Sound pressure level LpA dB 54 54 56 56 56 56
(1 m) at 50/60 Hz
DC link connection 2 × hole for M12 2 × hole for M12 2 × hole for M12 2 × hole for M12 2 × hole for M12 2 × hole for M12
DCP, DCN Busbar Busbar Busbar Busbar Busbar Busbar
Motor connection 2 × hole for M12 2 × hole for M12 2 × hole for M12 2 × hole for M12 2 × hole for M12 2 × hole for M12
U2, V2, W2
2
• Conductor cross-section, max. (IEC) mm 4 × 185 4 x 185 Busbar Busbar Busbar Busbar
PE/GND connection 2 × hole for M12 2 × hole for M12 2 × hole for M12 2 × hole for M12 2 × hole for M12 2 × hole for M12
• Conductor cross-section, max. (IEC) mm2 4 × 185 4 × 185 Busbar Busbar Busbar Busbar

3/92 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Chassis Format Units


Liquid-cooled units
Motor Modules

■ Technical specifications
Line voltage 500 ... 690 V 3 AC Motor Modules
DC link voltage 675 ... 1035 V DC
6SL3325- 6SL3325- 6SL3325- 6SL3325- 6SL3325- 6SL3325-
1TG37-4AA3 1TG38-0AA3 1) 1TG38-1AA3 1TG41-0AA3 1TG41-3AA3 1TG41-6AP3 11)
Cable length, max. 10)
• Shielded m (ft) 300 (984) 300 (984) 300 (984) 300 (984) 300 (984) 300 (984)
• Unshielded m (ft) 450 (1476) 450 (1476) 450 (1476) 450 (1476) 450 (1476) 450 (1476)
Dimensions
• Width mm (in) 265 (10.4) 265 (10.4) 295 (11.6) 295 (11.6) 295 (11.6) 295 (11.6)
• Height mm (in) 1002 (39.4) 1002 (39.4) 1516 (59.7) 1516 (59.7) 1516 (59.7) 1516 (59.7)
• Depth
Weight, approx.
mm (in)
kg (lb)
545 (21.5)
110 (243)
545 (21.5)
110 (243)
545 (21.5)
220 (485)
545 (21.5)
220 (485)
545 (21.5)
220 (485)
545 (21.5)
230 (507)
3
Frame size HXL HXL JXL JXL JXL JXL

1) The device is optimized for a base pulse frequency of 1.25 kHz, for an 7) The specified power loss represents the maximum value at 100 %
increased pulse frequency or for certain overloads the derating factor is utilization. The value is lower under normal operating conditions. To ensure
higher than that for the device with article number 6SL3325-1TG38-1AAx. safe dissipation of the minor power loss released to the ambient air, it is
2) Rated power of a typical 6-pole standard induction motor based on IL or IH important to follow the instructions pertaining to control cabinet installation
for 500 V or 690 V 3 AC 50 Hz. in the SINAMICS Low Voltage Engineering Manual.
8) The value applies to coolants comprising water and a mixture of water and
3) Rated power of a typical 6-pole standard induction motor based on IL or IH
for 575 V 3 AC 60 Hz. antifreeze agent.
9) The value is valid for water as coolant.
4) The base-load current IL is based on a duty cycle of 110 % for 60 s or
150 % for 10 s with a duty cycle duration of 300 s. Additional information and notes on other coolants are provided in the
5)
SINAMICS Low Voltage Engineering Manual.
The base-load current IH is based on a duty cycle of 150 % for 60 s or 10) Total
160 % for 10 s with a duty cycle duration of 300 s. of all motor cables. Longer cable lengths for specific configurations
6)
are available on request.
Additional notes regarding the correlation between the pulse frequency For additional information, please refer to the SINAMICS Low Voltage
and maximum output current/output frequency are provided in the Engineering Manual.
SINAMICS Low Voltage Engineering Manual. 11) Additional duty cycle for output frequencies from 5 Hz to 10 Hz: Base-load
current = 1460 A, short-time current = 2340 A for 5 s with a duty cycle
duration of 600 s. For output frequencies from 1 Hz to 5 Hz, the short-time
current is 1900 A for 5 s.

Siemens D 21.3 · 2022 3/93


© Siemens 2022

SINAMICS S120 Chassis Format Units


Liquid-cooled units
Mounting device for liquid-cooled power units

■ Overview ■ Selection and ordering data


Description Article No.
Mounting device 6SL3766-1CA00-0AA0
for installing and removing power units

The mounting device is used to install or remove liquid-cooled


power units (Power Modules, Line Modules, Motor Modules) into
or out of a control cabinet. The mounting device can be used if
the power units are mounted on mounting rails, which at the front
have two M6 threads at a vertical distance of 20 mm to attach the
mounting device.
The mounting device is a mounting aid. It is placed in front of the
power unit and attached to the mounting rails below the power
unit. The telescopic rails allow the mounting device to be
adjusted to the installation height and width of the power unit.
The power unit can be removed from the control cabinet after
releasing the mechanical and electrical connections and the
coolant connections. The power unit is guided and supported by
the guide rails on the mounting device. To prevent it toppling
over, the power unit must be secured to a crane, tripod, or similar
assembly using the lifting lugs or the lifting equipment. The unit
can then be lowered down from the mounting device.

3/94 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Chassis Format Units


Water-cooled units

■ Overview
The main difference to the current liquid-cooled SINAMICS S120
chassis units is the operation with a significantly reduced water
quality. The components are resistant to a proportion of oxygen
in the cooling water. Generally, the water usually used in industry
can also be used for cooling the drive system. Additives such as
antifreeze and inhibitors are not required.
The new cooling concept saves space and costs. Water cooling
for motor and converter ensures that less space is needed, as
the converter cooling unit can be dispensed with due to the
shared cooling circuit. This results in low acquisition and
operating costs.
The devices with copper-nickel heat sinks are fitted with rail 3
profiles at the bottom and can be stored on the floor in a way that
is easy to assemble.
The product portfolio includes the following water-cooled
SINAMICS S120 built-in units:
• Power Modules
The water-cooled SINAMICS S120 chassis units are specifically • Active Line Modules
designed for the operation of shared cooling circuits for the • Active Interface Modules
plant, motor, and converter.
• Motor Modules
They are especially suitable for applications where installation
space is restricted and environmental conditions are harsh. The associated system components such as motor reactors and
They ensure efficient heat dissipation. dv/dt filters plus VPL are air-cooled.

Line Module Motor Module

Air/water
cooler or
water/water
cooler

3-way
Air-to-water heat Motor Controller Temp valve
exchanger TCI
PT
Pressure

Pressure-relief
TIAH
valve
Ambient air max. system
pressure Expan-
600 kPa sion
Filter tank
Pumps

Pressure Option
PT

G_D213_EN_00113

Example of a drive line-up with SINAMICS S120 water-cooled units

Siemens D 21.3 · 2022 3/95


© Siemens 2022

SINAMICS S120 Chassis Format Units


Water-cooled units

■ Technical specifications
General technical specifications
Unless clearly specified otherwise, the following technical specifications are valid for all the following components of the
water-cooled SINAMICS S120 drive system in chassis format.
Electrical specifications
Line voltages 380 ... 480 V 3 AC ±10 % (-15 % <1 min)
500 ... 690 V 3 AC ±10 % (-15 % <1 min)
Line supply types Grounded TN/TT systems and non-grounded IT systems
Line frequency 47 ... 63 Hz
Overvoltage category III acc. to EN 61800-5-1
3 Electronics power supply 24 V DC, -15 % +20 %
implemented as PELV circuit in accordance with EN 61800-5-1
Ground = negative pole grounded via the electronics
Rated short-circuit current
per IEC, in conjunction with the speci-
fied fuses or circuit breakers
• 1.1 ... 447 kW 65 kA
• 448 ... 671 kW 84 kA
• 672 ... 1193 kW 170 kA
• > 1194 kW 200 kA
Rated short-circuit current SCCR
(Short Circuit Current Rating)
according to UL508C (up to 600 V), in
conjunction with the specified fuses or
circuit breakers
• 1.1 ... 447 kW 65 kA
• 448 ... 671 kW 84 kA
• 672 ... 1193 kW 170 kA
• > 1194 kW 200 kA
Control method Vector/Servo control with and without encoder or V/f control
Fixed speeds 15 fixed speeds plus 1 minimum speed, parameterizable (in the default setting, 3 fixed setpoints plus
1 minimum speed are selectable using terminal strip/PROFIBUS/PROFINET)
Skippable speed ranges 4, parameterizable
Setpoint resolution 0.001 rpm digital (14 bits + sign)
12 bits analog
Braking operation With Active Line Modules, four-quadrant operation as standard (energy recovery).
Braking with a Motor Module.
Mechanical specifications
Degree of protection IP00 (IP20, without taking into account the connecting busbars)
Protection class I acc. to EN 61800-5-1
Touch protection EN 50274/DGUV regulation 3 when used as intended
Cooling method Water cooling with integrated heat exchanger in copper-nickel version
Ambient conditions Storage 1) Transport 1) Operation
Ambient temperature (air) -25 ... +55 °C (-13 ... 131 °F) -25 ... +70 °C (-13 ... +158 °F) Line-side components, Line Modules,
Class 1K4 Class 2K4 and Motor Modules:
acc. to EN 60721-3-1 (1997) acc. to EN 60721-3-2 (1997) 0 ... 45 °C (32 ... 113 °F) without
derating
>45 ... 50 °C (113 ... 122 °F)
see derating characteristics
Control Units, supplementary system
components, and Sensor Modules:
0 ... 55 °C (32 ... 131 °F) (for operation
in a control cabinet)
DC link components and motor-side
components:
0 ... 55 °C (32 ... 131 °F)
Relative humidity 5 ... 95 % Max. 95 % at 40 °C (104 °F) 5 ... 95 %
Condensation, splashwater, and ice for- Class 1K4 Class 2K4 Class 3K3
mation not permitted (EN 60204, Part 1) acc. to EN 60721-3-1 (1997) acc. to EN 60721-3-2 (1997) acc. to EN 60721-3-3 (2002)
Environmental class/harmful chemi- Class 1C2 Class 2C2 Class 3C2
cal substances acc. to EN 60721-3-1 (1997) acc. to EN 60721-3-2 (1997) acc. to EN 60721-3-3 (2002)
Organic/biological influences Class 1B1 Class 2B1 Class 3B1
acc. to EN 60721-3-1 (1997) acc. to EN 60721-3-2 (1997) acc. to EN 60721-3-3 (2002)
Mechanically active substances Class 1S1 Class 2S1 Class 3S1
acc. to EN 60721-3-1 (1997) acc. to EN 60721-3-2 (1997) acc. to EN 60721-3-3 (2002)

3/96 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Chassis Format Units


Water-cooled units

■ Technical specifications
Electrical specifications
Degree of pollution 2 acc. to IEC/EN 61800-5-1
Installation altitude Up to 2000 m (6562 ft) above sea level without derating,
> 2000 m (6562 ft) above sea level, refer to the derating data
Mechanical stability Storage 1) Transport 1) Operation
Vibratory load Class 2M2 Test values
acc. to EN 60721-3-2 (1997) acc. to EN 60068-2-6 test Fc:
• 10 ... 58 Hz with constant deflection
0.075 mm
• 58 ... 150 Hz with constant
acceleration 9.81 m/s2 (1 × g)
Shock load Class 2M2 Test values 3
acc. to EN 60721-3-2 (1997) acc. to EN 60068-2-27 test Ea:
98 m/s2 (10 × g)/20 ms
Compliance with standards
Conformances/certificates of suitabil- CE (EMC Directive 2014/30/EU, Low Voltage Directive 2014/35/EU, and Machinery Directive 2006/42/EC for
ity, according to functional safety)
RCM, RoHS II,
marine certification DNV (Type approval)
cULus (only for devices connected to line voltages 380 ... 480 V 3 AC and 500 ... 600 V 3 AC)
Radio interference suppression SINAMICS S120 chassis format units are not designed for connection to the public grid (first environment).
Radio interference suppression is compliant with the EMC product standard for variable-speed drives EN 61800-3,
"Second environment" (industrial line supplies). EMC disturbances can occur when connected to the public grid.
For further information, see section Engineering information.

Deviations from the specified class are underlined.

1)
In transport packaging.

Siemens D 21.3 · 2022 3/97


© Siemens 2022

SINAMICS S120 Chassis Format Units


Water-cooled units

■ Technical specifications
Cooling circuit and coolant quality
The following tables and sections describe the quality requirements of the coolant used in the water-cooled SINAMICS S120 drive
system in chassis format.
Cooling circuit
• System pressure with reference to 600 kPa
atmospheric pressure, max.
• Pressure drop at rated volumetric flow 70 kPa
• Recommended pressure range 80 ... 150 kPa (is applicable for water as coolant)
• Inlet temperature of cooling liquid Dependent on ambient temperature, no condensation permitted
(all of the devices with copper-nickel heat 0 ... 38 °C (32 ...100 °F) without derating,
3 exchangers described in this section)
>38 … 43°C (100 ... 109 °F) see derating data
Antifreeze essential for temperature range between 0 °C (32 °F) and 5 °C (41 °F)
Note:
Compared to the liquid-cooled chassis format units, the inlet temperatures are 7 K lower, as a heat exchanger is
not required.
• Inlet temperature of cooling liquid Dependent on ambient temperature, no condensation permitted
(all of the devices with stainless steel heat 0 … 45 °C (32 … 113 °F) without derating,
exchangers described in this section)
> 45 … 50 °C (113 ... 122 °F), see derating data
Antifreeze essential for temperature range between 0 °C (32 °F) and 5 °C (41 °F)
Coolant quality
Coolant basis for copper-nickel heat exchangers: Coolant basis for stainless steel heat exchangers:
filtered drinking, process and cooling water filtered drinking, process and cooling water
• Electrical conductivity <2900 S/cm (>290 mS/m) <2500 S/cm (>250 mS/m)
• pH value 6.5 ... 9 6.5 ... 9
• Total salt content TDS <1800 mg/l <1550 mg/l
• Chloride (Cl-) <500 mg/l <250 mg/l
• Sodium (Na+) <200 mg/l <200 mg/l
• Sulfate (SO42-) <300 mg/l <240 mg/l
• Sulfide (S2-) <1 mg/l <1 mg/l
• Nitrate (NO3-) <50 mg/l <50 mg/l
• Iron <1 mg/l <1 mg/l
• Silicate <10 mg/l <10 mg/l
• Ammonia (NH3), ammonium (NH4+) <1 mg/l <1 mg/l
• Total hardness with a maximum of <1.78 mmol/l (10 °dH) <1.78 mmol/l (10 °dH)
- Calcium hardness <1.25 mmol/l (7 °dH), <57 mg/l calcium <1.25 mmol/l (7 °dH), <57 mg/l calcium
- Magnesium hardness < 1.43 mmol/l (8 °dH), <35 mg/l magnesium < 1.43 mmol/l (8 °dH), <35 mg/l magnesium
- Carbonate hardness <0.45 mmol/l (2.5 °dH) <0.45 mmol/l (2.5 °dH)
• Suspended solids/suspended substances
- Solids <340 mg/l <340 mg/l
- Size of entrained particles <100 m <100 m
The coolant definition specified here should only be considered as recommendation. For units that have been
shipped, the information and data provided in the equipment manual supplied should be observed!
Recommendation:
With an open pressure equalization tank, initial filling should be conducted using desalinated water (via ion
exchanger).

3/98 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Chassis Format Units


Water-cooled units

■ Technical specifications
Antifreeze and biocide
The water-cooled built-in units can be operated within
a temperature range above 5 °C without antifreeze. At operating
temperatures of <5 °C, one of the following antifreeze agents
must be used.
Antifreeze Antifrogen N Antifrogen L DOWCAL 100
Manufacturer Clariant Clariant DOW
Chemical base Ethylene glycol Propylene glycol Ethylene glycol
Minimum concentration 25 % 25 % 25 %
Antifreeze agent with minimum
concentration
-10 °C (14 °F) -10 °C (14 °F) -10 °C (14 °F) 3
Maximum concentration 45 % 48 % 45 %
Antifreeze agent with maximum -30 °C (-22 °F) -30 °C (-22 °F) -30 °C (-22 °F)
concentration
Inhibitor content Contains inhibitors with nitrites Contains inhibitors that are free of Contains inhibitors that are free of
nitrites, amines, borates and nitrites, amines and phosphates
phosphates
Biocide action with a concentration of >25 % >25 % >25 %

Biocides prevent corrosion that is caused by slime-forming, Recommended service


corrosive or iron-depositing bacteria. These can occur in closed
cooling circuits with low water hardness and in shared cooling The cooling water must be checked 3 months after the cooling
circuits with open pressure equalization vessel. Biocides must circuit is initially filled and once every year thereafter.
always be selected according to the relevant bacterial risks. We recommend contacting a coolant manufacturer for the
Compatibility with inhibitors or antifreeze used with them must coolant inspection. If the cooling water becomes cloudy,
be checked on a case-by-case basis. is colored, or becomes contaminated by mold spores,
the cooling circuit must be cleaned and refilled.
Protection against condensation
With water-cooled units, warm air can condense on the cold The temperature at which water vapor contained in the air
surfaces of heat sinks, pipes, and hoses. This condensation condenses into water is known as the dew point. To prevent
depends on the air humidity and the temperature difference condensation reliably, the coolant temperature must always be
between the ambient air and the coolant. higher than the dew point.
The water which is produced as a result of condensation can The table below specifies the dew point as a function of room
cause corrosion as well as electrical damage such as creepage temperature T and relative air humidity  for an atmospheric
shorts and flashovers. As the SINAMICS units cannot prevent pressure of 100 kPa (1 bar). This corresponds to an installation
condensation if it is caused by the prevailing climatic conditions, altitude of 0 up to approximately 500 m above sea level. Since
any potential risk of condensation must be prevented by the dew point drops as the air pressure decreases, the dew point
appropriate engineering or by precautionary measures values at higher installation altitudes are lower than the specified
implemented by the customer. table values. It is therefore the safest approach to engineer the
These measures include the following: coolant temperature according to the values in the table for an
• A fixed coolant temperature that has been adjusted to the installation altitude of zero.
expected air humidity or ambient temperature ensures that
critical differences between the coolant and ambient air
temperatures do not develop or
• Temperature regulation of the coolant as a function of the
ambient air temperature
Room temperature Relative air humidity 
T 20 % 30 % 40 % 50 % 60 % 70 % 80 % 85 % 90 % 95 % 100 %
10 °C (50 °F) <0 °C <0 °C <0 °C 0.2 °C 2.7 °C 4.8 °C 6.7 °C 7.6 °C 8.4 °C 9.2 °C 10 °C
(<32 °F) (<32 °F) (<32 °F) (32.4 °F) (36.9 °F) (40.6 °F) (44.1 °F) (45.7 °F) (47.1 °F) (48.6 °F) (50 °F)
20 °C (68 °F) <0 °C 2 °C 6 °C 9.3 °C 12 °C 14.3 °C 16.4 °C 17.4 °C 18.3 °C 19.1 °C 20 °C
(<32 °F) (35.6 °F) (42.8 °F) (48.7 °F) (53.6 °F) (57.7 °F) (61.5 °F) (63.3 °F) (64.9 °F) (66.4 °F) (68 °F)
25 °C (77 °F) 0.6 °C 6.3 °C 10.5 °C 13.8 °C 16.7 °C 19.1 °C 21.2 °C 22.2 °C 23.2 °C 24.1 °C 24.9 °C
(33.1 °F) (43.3 °F) (50.9 °F) (56.8 °F) (62.1 °F) (66.4 °F) (70.2 °F) (72.0 °F) (73.8 °F) (75.4 °F) (76.8 °F)
30 °C (86 °F) 4.7 °C 10.5 °C 14.9 °C 18.4 °C 21.3 °C 23.8 °C 26.1 °C 27.1 °C 28.1 °C 29 °C 29.9 °C
(40.5 °F) (50.9 °F) (58.8 °F) (65.1 °F) (70.3 °F) (74.8 °F) (79.0 °F) (80.8 °F) (82.6 °F) (84.2 °F) (85.8 °F)
35 °C (95 °F) 8.7 °C 14.8 °C 19.3 °C 22.9 °C 26 °C 28.6 °C 30.9 °C 32 °C 33 °C 34 °C 34.9 °C
(47.7 °F) (58.6 °F) (66.7 °F) (73.2 °F) (78.8 °F) (83.5 °F) (87.6 °F) (89.6 °F) (91.4 °F) (93.2 °F) (94.8 °F)
40 °C (104 °F) 12.8 °C 19.1 °C 23.7 °C 27.5 °C 30.6 °C 33.4 °C 35.8 °C 36.9 °C 37.9 °C 38.9 °C 39.9 °C
(55.0 °F) (66.4 °F) (74.7 °F) (81.5 °F) (87.1 °F) (92.1 °F) (96.4 °F) (98.4 °F) (100 °F) (102 °F) (104 °F)
45 °C (113 °F) 16.8 °C 23.3 °C 28.2 °C 32 °C 35.3 °C 38.1 °C 40.6 °C 41.8 °C 42.9 °C 43.9 °C 44.9 °C
(62.2 °F) (73.9 °F) (82.8 °F) (89.6 °F) (95.5 °F) (101 °F) (105 °F) (107 °F) (109 °F) (111 °F) (113 °F)
50 °C (122 °F) 20.8 °C 27.5 °C 32.6 °C 36.6 °C 40 °C 42.9 °C 45.5 °C 46.6 °C 47.8 °C 48.9 °C 49.9 °C
(69.4 °F) (81.5 °F) (90.7 °F) (97.9 °F) (104 °F) (109 °F) (114 °F) (116 °F) (118 °F) (120 °F) (122 °F)

A detailed description of the cooling circuits and the


recommended coolant is given in the SINAMICS Low Voltage
Engineering Manual.

Siemens D 21.3 · 2022 3/99


© Siemens 2022

SINAMICS S120 Chassis Format Units


Water-cooled units

■ Characteristic curves
Pressure drop

400
Pressure drop [kPa]

300

200
3 150 maximum differential
pressure

G_D211_EN_00361a
100
70 nominal differential
pressure

0
0 10 20 30 40 50 60 70 80
Volumetric flow dv/dt [liters/min]

Power Module Power Module Active Interface Module Active Line Module, Active Line Module,
frame size FL frame size GL frame size JIL (10 l/min) Motor Module Motor Module
Motor Module Motor Module frame size HXL frame size JXL
frame size FXL frame size GXL

Pressure drop for water-cooled chassis format units


The pressure drop characteristics are valid for water. If anti- For further information, please refer to the SINAMICS Low
freeze is used, the characteristics typically shift to the left. Voltage Engineering Manual.

3/100 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Chassis Format Units


Water-cooled units

■ Characteristic curves
Derating
Water-cooled SINAMICS S120 in chassis format with stainless 100
steel heat exchanger are rated for an ambient temperature of

Output current %
90
45 °C and installation altitudes up to 2000 m above sea level.
At ambient temperatures > 45 °C, the output current must be 80
reduced. Ambient temperatures above 50 °C are not 70
permissible. 60
Water-cooled SINAMICS S120 in chassis format with heat 50
exchanger made of copper-nickel alloy are rated for an ambient 40
temperature of 38 °C and installation altitudes up to 2000 m

G_D213_EN_00037b
30
above sea level. At ambient temperatures > 38 °C, the output
current must be reduced. Ambient temperatures above 43 °C 20 3
are not permissible. 10

At installation altitudes > 2000 m above sea level, it must be 0


-5 0 10 20 30 40 45 50 60
taken into account that the air pressure, and therefore air density, (23) (32) (50) (68) (86) (104)(113)(122) (140)
decreases as the height increases. As a consequence, the Coolant temperature °C
without antifreeze (°F)
cooling efficiency and the insulation capacity of the air also
decrease. with antifreeze

At installation altitudes above 2000 m, the line voltage must not


Current derating as a function of the temperature of the cooling liquid 1)
exceed certain limits in order to be able to isolate the surge (stainless steel heat exchanger)
voltages according to IEC 61800-5-1 for overvoltage category
III. If the line voltage is above this limit at installation
altitudes > 2000 m, measures must be taken to reduce the 110
transient overvoltages of Category III to values of Category II, 100
e. g. supply of the devices via an isolating transformer.
Rated current %

90
For additional information, please refer to the SINAMICS Low
80
Voltage Engineering Manual.
70
Note:
60
Compared to the liquid-cooled chassis format units, the inlet 50
temperatures are 7 K lower, as a heat exchanger is not required.
40
In order to prevent condensation, the inlet temperature of the

G_D213_EN_00038
30
liquid coolant should be kept above the ambient temperature
20
depending on the relative air humidity.
10
0
-5 0 10 20 30 40 50 60
100 (23) (32) (50) (68) (86) (104) (122) (140)
%

Ambient temperature °C (°F)


90
Output current

80
70 Current derating as a function of ambient temperature 1)
60
50
50
Permissible ambient temperature (air) °C (°F)

40 (122)
G_D213_EN_00111

30
40
20 (104)
10
30
0 (86)
-5 0 10 20 30 38 40 43 50 60
20
Coolant temperature °C (68)
without antifreeze
G_D213_EN_00072

with antifreeze
10
(50)
Current derating as a function of the temperature of the cooling liquid 1)
(copper-nickel heat exchanger) 0
(32) 0 1000 2000 3000 4000
(3281) (6562) (9843) (13124)
Installation altitude above sea level m (ft)
Ambient temperature Tmax at I = 100 %
Ambient temperature Tmax at I = 90 %

Permissible ambient temperature as a function of installation altitude

1)
The factors of the curves of the respective cooling liquid temperature and
of the ambient temperature must not be multiplied. The highest value in
each case must be assumed for the purposes of calculation, so that the
derating factor in the worst-case scenario is 0.9.

Siemens D 21.3 · 2022 3/101


© Siemens 2022

SINAMICS S120 Chassis Format Units


Water-cooled units

■ Characteristic curves
Current derating as a function of the pulse frequency For additional information, please refer to the SINAMICS Low
Voltage Engineering Manual.
To reduce motor noise or to increase output frequency, the pulse
frequency can be increased relative to the factory setting The following tables list the rated output currents of the Power
(1.25 kHz or 2 kHz). When the pulse frequency is increased, the Modules and Motor Modules with pulse frequency set in the
derating factor of the output current must be taken into account. factory as well as the current derating factors (permissible
This derating factor must be applied to the currents specified in output currents referred to the rated output current) for higher
the technical specifications. pulse frequencies.
Derating factor of the output current as a function of the pulse frequency for units with a rated pulse frequency of 2 kHz
Power Module Type rating Output current at 2 kHz Derating factor
Motor Module at 400 V at pulse frequency
3 6SL3315-... kW A 2.5 kHz 4 kHz 5 kHz 7.5 kHz 8 kHz
6SL3325-...
380 ... 480 V 3 AC
1TE32-1AA3 110 210 95 % 82 % 74 % 54 % 50 %
1TE32-6AA3 132 260 95 % 83 % 74 % 54 % 50 %
1TE33-1AA3 160 310 97 % 88 % 78 % 54 % 50 %
1TE35-0AA3 250 490 94 % 78 % 71 % 53 % 50 %

Derating factor of the output current as a function of the pulse frequency for Motor Modules with a rated pulse frequency of 1.25 kHz
Motor Module Type rating Output current at 1.25 Derating factor
at 400 V or 690 V kHz at pulse frequency
6SL3325-... kW A 2 kHz 2.5 kHz 4 kHz 5 kHz 7.5 kHz 8 kHz
380 ... 480 V 3 AC
1TE37-5AA7 400 745 87 % 79 % 64 % 55 % 40 % 37 %
1TE41-0AA7 560 985 92 % 87 % 70 % 60 % 50 % 47 %
1TE41-2AA7 710 1260 97 % 95 % 74 % 60 % 50 % 47 %
1TE41-4AA7 800 1405 97 % 95 % 74 % 60 % 50 % 47 %
500 ... 690 V 3 AC
1TG31-0AA3 90 100 92 % 88 % 71 % 60 % 40 % -
1TG31-5AA3 132 150 90 % 84 % 66 % 55 % 35 % -
1TG32-2AA3 200 215 92 % 87 % 70 % 60 % 40 % -
1TG33-3AA3 315 330 89 % 82 % 65 % 55 % 40 % -
1TG34-7AA7 450 465 92 % 87 % 67 % 55 % 35 % -
1TG35-8AA7 560 575 91 % 85 % 64 % 50 % 35 % -
1TG38-1AA7 800 810 97 % 95 % 71 % 55 % 35 % -
1TG41-0AA7 1000 1025 91 % 86 % 64 % 50 % 30 % -
1TG41-3AA7 1200 1270 87 % 79 % 55 % 40 % 25 % -
1TG41-6AA7 1500 1560 87 % 79 % 55 % 40 % 25 % -

Maximum output frequencies achieved by increasing the pulse frequency


The adjustable pulse frequencies – and therefore the output
frequencies that can be achieved with the factory-set current
controller clock cycles – are listed below.
Current controller clock cycle Adjustable pulse frequency Max. achievable output frequency fA
TI fp
V/f mode Vector mode Servo mode
250 µs 1) 2 kHz 166 Hz 166 Hz 333 Hz
4 kHz 333 Hz 333 Hz 550 Hz 3)
8 kHz 550 Hz 3) 480 Hz 550 Hz 3)
2)
400 µs 1.25 kHz 104 Hz 104 Hz –
2.5 kHz 208 Hz 208 Hz –
5.0 kHz 416 Hz 300 Hz –
7.5 kHz 550 Hz 3) 300 Hz –

1) As factory setting, the following devices have a current controller 3) With the "High output frequencies" license, which can be ordered as option
clock cycle of 250 µs and a pulse frequency of 2 kHz: J01 on the CompactFlash card for SINAMICS S120, the maximum output
- 380 ... 480 V 3 AC:  250 kW / 490 A frequency is increased up to 650 Hz. For more information, see
2) As factory setting, the following devices have a current controller https://support.industry.siemens.com/cs/document/104020669
clock cycle of 400 µs and a pulse frequency of 1.25 kHz:
- 380 ... 480 V 3 AC: 315 kW / 605 A
- 500 ... 690 V 3 AC: All power ratings

3/102 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Chassis Format Units


Water-cooled units

■ Characteristic curves
Overload capability The following applies to the 6SL3325-1TG41-3AA7 and
6SL3325-1TG41-6AA7 Motor Modules:
Water-cooled SINAMICS S120 units have an overload reserve,
e.g. to handle breakaway torques. If larger surge loads occur, The short-time current for low overload must be reduced from
this must be taken into account in the configuration. For drives 150 % to 130 % for 10 s. At 10 s and 60 s, the short-time current
with overload requirements, the appropriate base load current for high overload must be reduced to 130 %. The duty cycle
must, therefore, be used as a basis for the required load. remains unchanged.
The permissible overload levels are valid under the prerequisite Converter current
that the drive units are operated with their base-load current 10 s
before and after the overload condition based on a duty cycle Short-time current 130 %
duration of 300 s.
Another precondition is that the Power Modules or the Motor
Modules are operated at their factory-set pulse frequency at
1.3 x IL Short-time current 110 %
3
output frequencies > 10 Hz. Rated current (continuous)

For temporary, periodic duty cycles with high variations of load Base-load current IL
1.1 x IL
for low overload
within the duty cycle, the relevant sections of the SINAMICS Low
Voltage Engineering Manual must be observed. IN

G_D213_EN_00114
IL
Power Modules and Motor Modules 60 s
300 s
The base-load current for a low overload IL is the basis for a duty
cycle of 110 % for 60 s or 150 % for 10 s.
t
Converter current
10 s Low overload for 6SL3325-1TG41-3AA7 and 6SL3325-1TG41-6AA7
Motor Modules
1.5 x IL
Converter current
Short-time current 150 % 10 s
Short-time current 110 % Short-time current 130 %
Rated current (continuous)
Base-load current IL 1.3 x IH Rated current (continuous)
1.1 x IL
for low overload Base-load current IH for high overload
IN
IL IN
G_D213_EN_00035

60 s
300 s IH

G_D213_EN_00115
60 s
300 s
t

t
Low overload
High overload for 6SL3325-1TG41-3AA7 and 6SL3325-1TG41-6AA7
The base-load current IH for a high overload is based on a load Motor Modules
cycle of 150 % for 60 s or 160 % for 10 s.
Line Modules
Converter current The base-load current for a high overload IH DC is the basis for a
10 s duty cycle of 150 % for 60 s or Imax DC for 5 s.
1.6 x IH Short-time current 160 % Converter current
1.5 x IH 5s
Short-time current 150 %
Imax DC Short-time current Imax
Rated current (continuous) 1.5 x IH DC Short-time current 150 %

Base-load current IH for high overload Rated current (continuous)

IN Base-load current IH DC
for high overload
IH IN DC
G_D213_EN_00036

60 s
IH DC
G_D213_EN_00079

300 s
60 s
300 s

t
t
High overload
High overload

Siemens D 21.3 · 2022 3/103


© Siemens 2022

SINAMICS S120 Chassis Format Units


Water-cooled units
Power Modules

■ Overview The scope of supply of the Power Modules includes:


• 1 DRIVE-CLiQ cable for connection to the CU310-2 Control
Unit
• 1 mounting plate for attaching the CU310-2 Control Unit
• 2 seals for cooling water connections
• 1 set of warning labels in 30 languages
(BG, CN, CZ, DE, DK, EE, ES, FI, FR, GB, GR, HU, IE, IS, IT,
JP, KR, LT, LV, MT, NL, NO, PL, PT, RO, RU, SE, SI, SK, TR)
Use in multi-axis systems
Power Modules in chassis format can also be connected directly
via DRIVE-CLiQ to a separate CU320-2 or SIMOTION D4x5-2
3 Control Unit or Controller Extension CX32-2. The appropriate
DRIVE-CLiQ cable for the required distance must be ordered
(see System components  section Connection system).

■ Selection and ordering data


The Power Module comprises a line rectifier, a DC link, and
Type rating Rated output current Power Module
an inverter to supply the motor. at 400 V
Power Modules are designed for drives that are not capable of kW A Article No.
regenerating energy to the line supply system. If the motor
produces energy during braking, a Braking Module with braking Line voltage 380 ... 480 V 3 AC
resistors will be required. 110 210 6SL3315-1TE32-1AA3

The water-cooled Power Modules are specifically designed for 132 260 6SL3315-1TE32-6AA3
the operation of shared cooling circuits for the plant, motor and 160 310 6SL3315-1TE33-1AA3
converter.
250 490 6SL3315-1TE35-0AA3
Power Modules in chassis format can be connected to grounded
TN/TT systems and non-grounded IT systems. Extended liability for defects

Siemens offers for SINAMICS S120 chassis units an extended


■ Design liability for defects/Service Protect up to 6½ years.
The water-cooled Power Modules have the following interfaces Details can be found in chapter
as standard: Services and Documentation
• 1 line supply connection Accessories
• 1 motor connection
Description Article No.
• 1 connection for the 24 V DC electronics power supply
3-way valve 1) VXF41...
• 1 DC link connection VXG41...
• 3 DRIVE-CLiQ sockets Actuator for 3-way valve 1)
• 1 temperature sensor input for KTY84-130, Pt1000, PTC, • 230 V 1 AC SAX31...
or Pt100 (Pt1000 can be used from firmware V4.7 HF17 and • 24 V AC/DC SAX61...
higher) SAX81...
• 1 connection for Safe Brake Adapter Accessories for re-ordering
• 1 connection for Safety Integrated Dust protection blanking plugs 6SL3066-4CA00-0AA0
• 2 PE/protective conductor connections (50 units)
• 2 cooling water connections For DRIVE-CLiQ port

The CU310-2 Control Unit can be integrated into the water- For additional information, refer to the manual.
cooled Power Modules. For line-side and motor-side components, see System
The status of the Power Modules is indicated via three LEDs. components.

1) Recommended components for installing a flow control as condensation


protection; manufactured by Siemens Building Technologies.

3/104 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Chassis Format Units


Water-cooled units
Power Modules

■ Integration
The Power Modules communicate with the higher-level control module via DRIVE-CLiQ. The control module in this case could be
a CU310-2, CU320-2, or a SIMOTION D Control Unit. An external 24 V DC power supply is required to operate water-cooled
Power Modules.

Main switch Main contactor Line reactor

L1
L2
L3

W1
PE
U1
V1
-X1
Power Module
chassis format
~
=
-X9
1 P24 V =
ext. Cooling circuit
24 V DC 2 M
=
3
4 Internal power
supply
5
Main contactor
6 control
EP P24 V 7
EP M1 8

-X41
4 DCP
+Temp
3 - Temp
2 DCN
1

-X42 =
1
+ 2
P24L ~
+ 1)
P24L
M 3 M
M 4 M
IPD Card
-X46
1 BR Output+
2 BR Output-
3 FB Input+
4 FB Input-
READY
LEDs

X400 DC LINK
Control Unit DRIVE-CLiQ-socket 0
POWER OK
X401
DRIVE-CLiQ-socket 1
G_D211_EN_00255c

X402
DRIVE-CLiQ-socket 2
-X2
W2
PE
U2
V2

1)
24 V connecting cable for supply of a CU310-2
Control Unit or SIMOTION D410-2 integrated in a
Power Module.

M
3~

Connection example of a water-cooled Power Module in chassis format


Note: the integrated power supply, the total load of the digital outputs
The integrated 24 V power supply at connector X42 can have must be carefully observed to ensure that the 2 A is
a maximum load of 2 A. When the Control Unit is supplied from not exceeded.

Siemens D 21.3 · 2022 3/105


© Siemens 2022

SINAMICS S120 Chassis Format Units


Water-cooled units
Power Modules

■ Technical specifications
General technical specifications
Electrical specifications
Line connection voltage 380 … 480 V 3 AC ±10 % (-15 % <1 min)
Up to 2000 m (6562 ft) above sea level
Line power factor
for a 3 AC line supply voltage and rated
output
• Basic fundamental (cos 1) >0.96
• Total () 0.75 ... 0.93
Efficiency >98 %
3 DC link voltage, approx. 1.35 × line voltage
Output voltage, approx. 0 ... 0.97 × Uline
Output frequency 1)
• Control mode Servo 0 ... 550 Hz
• Control mode Vector 0 ... 550 Hz
• Control mode V/f 0 ... 550 Hz
Electronics power supply 24 V DC -15 %/+20 %
Main contactor control
• Terminal strip -X9/5-6 240 V AC, max. 8 A
30 V DC, max. 1 A
Safety Integrated Safety Integrity Level 2 (SIL2) acc. to IEC 61508, Performance Level d (PLd) acc. to EN ISO 13849-1 and
Control Category 3 acc. to EN ISO 13849-1.

1)
Please note:
• The correlation between the maximum output frequency, pulse frequency
and current derating. Higher output frequencies on request. For further
information, see
https://support.industry.siemens.com/cs/document/104020669
• The correlation between the minimum output frequency and permissible
output current (current derating).
For additional information, please refer to the SINAMICS Low Voltage
Engineering Manual.

3/106 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Chassis Format Units


Water-cooled units
Power Modules

■ Technical specifications
Line voltage 380 V ... 480 V 3 AC Power Modules
6SL3315-1TE32-1AA3 6SL3315-1TE32-6AA3 6SL3315-1TE33-1AA3 6SL3315-1TE35-0AA3
Type rating
• At IL (50 Hz 400 V) 1) kW 110 132 160 250
• At IH (50 Hz 400 V) 1) kW 90 110 132 200
• At IL (60 Hz 460 V) 2) hp 150 200 250 400
• At IH (60 Hz 460 V) 2) hp 150 200 200 350
Output current
• Rated current IN O A 210 260 310 490
• Base-load current IL 3) A 205 250 302 477
• Base-load current IH 4) A 178 233 277 438
• Max. output current Imax O
Input current
A 307 375 453 715
3
• Rated current IN I A 230 285 340 540
• Maximum current Imax I A 336 411 496 788
Current demand
• 24 V DC auxiliary power supply A 1.4 1.4 1.5 1.5
Pulse frequency 5)
• Rated frequency kHz 2 2 2 2
• Pulse frequency, max.
- Without current derating kHz 2 2 2 2
- With current derating kHz 8 8 8 8
Power loss, at 50 Hz 400 V 6)
• Dissipated to coolant kW 2.34 2.95 3.29 5.25
• Dissipated to ambient air kW 0.08 0.09 0.12 0.18
• Total kW 2.42 3.04 3.4 5.43
Coolant volume flow 7) l/min (US 9 (2.38) 9 (2.38) 12 (3.17) 12 (3.17)
gal./min)
Liquid volume dm3 0.52 0.52 0.88 0.88
of the integrated heat exchanger
Pressure drop, typ. 8) Pa 70000 70000 70000 70000
for volume flow
Heat exchanger material Stainless steel Stainless steel Stainless steel Stainless steel
Coolant connections Pipe thread ISO 228 G 3/4 B
Intake/return (external thread 3/4", flat-sealing)
Sound pressure level LpA dB 52 52 52 52
(1 m) at 50/60 Hz
Line supply connection Hole for M12 Hole for M12 Hole for M12 Hole for M12
U1, V1, W1
• Conductor cross-section, max. (IEC) mm2 2 × 95 2 × 95 2 × 240 2 × 240
DC link connection Hole for M12 Hole for M12 Hole for M12 Hole for M12
DCP, DCN
• Conductor cross-section, max. (IEC) mm2 2 × 95 2 × 95 2 × 240 2 × 240
Motor connection Hole for M12 Hole for M12 2 × hole for M12 2 × hole for M12
U2/T1, V2/T2, W2/T3
2
• Conductor cross-section, max. (IEC) mm 2 × 95 2 × 95 2 × 240 2 × 240
Cable length, max. 9)
• Shielded m (ft) 300 (984) 300 (984) 300 (984) 300 (984)
• Unshielded m (ft) 450 (1476) 450 (1476) 450 (1476) 450 (1476)
PE/GND connection 2 × hole for M12 2 × hole for M12 2 × hole for M12 2 × hole for M12
• Conductor cross-section, max. (IEC) mm2 2 × 95 2 × 95 2 × 240 2 × 240
Dimensions
• Width mm (in) 265 (10.4) 265 (10.4) 265 (10.4) 265 (10.4)
• Height mm (in) 836 (32.9) 836 (32.9) 983 (38.7) 983 (38.7)
• Depth mm (in) 549 (21.6) 549 (21.6) 549 (21.6) 549 (21.6)
Weight, approx. kg (lb) 77 (170) 77 (170) 108 (238) 108 (238)
Frame size FL FL GL GL
Minimum short-circuit current 10) kA 3 3.6 4.4 8

1) 6)
Rated power of a typical 6-pole standard induction motor based on IL The specified power loss represents the maximum value at 100 %
or IH for 400 V 3 AC 50 Hz. utilization. The value is lower under normal operating conditions. To ensure
2)
Rated power of a typical 6-pole standard induction motor based on IL safe dissipation of the minor power loss released to the ambient air, it is
or IH for 460 V 3 AC 60 Hz. important to follow the instructions pertaining to control cabinet installation
3)
in the SINAMICS Low Voltage Engineering Manual.
The base-load current IL is based on a duty cycle of 110 % for 60 s or 7)
150 % for 10 s with a duty cycle duration of 300 s. The value applies to coolants comprising water and a mixture of water and
4)
antifreeze agent.
The base-load current IH is based on a duty cycle of 150 % for 60 s or 8)
160 % for 10 s with a duty cycle duration of 300 s. The value is valid for water as coolant.
5)
Additional information and notes on other coolants are provided in the
Information regarding the correlation between the pulse frequency and SINAMICS Low Voltage Engineering Manual.
maximum output current/output frequency is provided in the SINAMICS 9)
Low Voltage Engineering Manual. Longer cable lengths for specific configurations are available on request.
For additional information, please refer to the SINAMICS Low Voltage
Engineering Manual.
10) Current required for reliably triggering protective devices.

Siemens D 21.3 · 2022 3/107


© Siemens 2022

SINAMICS S120 Chassis Format Units


Water-cooled units
Active Line Modules

■ Overview ■ Design
The water-cooled Active Line Modules have the following
interfaces as standard:
• 1 line supply connection
• 1 connection for the 24 V DC electronics power supply
• 1 DC link connection (DCP, DCN) for supplying the connected
Motor Modules
• 3 DRIVE-CLiQ sockets
• 1 temperature sensor input for KTY84-130, Pt1000, PTC,
or Pt100 (Pt1000 can be used from firmware V4.7 HF17 and
higher)
3 • 1 PE/protective conductor connection
• 2 cooling water connections
The status of the Active Line Modules is indicated via three
LEDs.
The following are included in the scope of supply of the Active
Line Modules:
The self-commutated infeed/regenerative feedback units (with • 1 DRIVE-CLiQ cable for connection to the Control Unit
IGBTs in infeed and regenerative feedback directions) generate
a regulated DC link voltage. This means that the connected • 2 seals for cooling water connections
Motor Modules are decoupled from the line voltage. Line voltage • 1 set of warning labels in 30 languages
fluctuations within the permissible supply tolerances have (BG, CN, CZ, DE, DK, EE, ES, FI, FR, GB, GR, HU, IE, IS, IT,
no effect on the motor voltage. JP, KR, LT, LV, MT, NL, NO, PL, PT, RO, RU, SE, SI, SK, TR)
If required, the Active Line Modules can also provide reactive
power compensation. ■ Selection and ordering data
Active Line Modules are designed for connection to grounded Rated power Rated infeed/ Active Line Module
TN/TT and non-grounded IT supply systems. at 400 V or 690 V regenerative
feedback current
The water-cooled Active Line Modules are specifically designed
for the operation of shared cooling circuits for the plant, motor kW A Article No.
and converter. Line voltage 380 ... 480 V 3 AC
Active Line Modules are always operated together with the 630 985 6SL3335-7TE41-0AA7
associated Active Interface Modules. These include the 900 1405 6SL3335-7TE41-4AA7
necessary pre-charging circuit as well as a Clean Power Filter.
Line voltage 500 ... 690 V 3 AC
900 810 6SL3335-7TG38-1AA7
1100 1020 6SL3335-7TG41-0AA7
1400 1270 6SL3335-7TG41-3AA7
1700 1560 6SL3335-7TG41-6AA7

Extended liability for defects

Siemens offers for SINAMICS S120 chassis units an extended


liability for defects/Service Protect up to 6½ years.
Details can be found in chapter
Services and Documentation
Accessories

Description Article No.


3-way valve 1) VXF41...
VXG41...
Actuator for 3-way valve 1)
• 230 V 1 AC SAX31...
• 24 V AC/DC SAX61...
SAX81...
Accessories for re-ordering
Dust protection blanking plugs 6SL3066-4CA00-0AA0
(50 units)
For DRIVE-CLiQ port

For additional information, refer to the manual.


For line-side components and recommended system compo-
nents, see System components.

1) Recommended components for installing a flow control as condensation


protection; manufactured by Siemens Building Technologies.

3/108 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Chassis Format Units


Water-cooled units
Active Line Modules

■ Integration
Active Line Modules are always operated together with the The water-cooled Active Line Modules communicate with the
associated Active Interface Modules. Active Interface Modules higher-level control module via DRIVE-CLiQ. The control module
contain a Clean Power Filter with basic RI suppression, the pre- in this case can be a CU320-2 or a SIMOTION D Control Unit.
charging circuit for the Active Line Module, line voltage sensing An external 24 V DC power supply is required to operate water-
circuit, and monitoring sensors. cooled Active Line Modules.

X400 X401 X402

2
DRIVE-CLiQ socket

DRIVE-CLiQ socket

DRIVE-CLiQ socket
Active Line
Module 3
chassis format

-X9 Cooling circuit


1 P24 V =
ext.
24 V DC 2 M
Control of =
3
to Active 4 bypass contactor Internal
Interface Module 5 Control of power supply
pre-charging
6 contactor
7
EP +24 V
8
EP M1
~ DCP
DC link
DCN
=

-X41
4 READY
+Temp
LEDs

3 -Temp DC LINK
2 EP +24 V
1 POWER OK
EP M1

-X42
1 P24L
2 IPD Card
P24L
3 M
4
G_D213_EN_00040c

-X1
W1
PE
U1
V1

from Active
Interface Module

Connection example of an Active Line Module

■ Technical specifications
General technical specifications
Electrical specifications
Line power factor
• Basic fundamental (cos 1) 1 (factory setting), can be altered by inputting a reactive current setpoint
• Total () 1 (factory setting)
Efficiency >98.5 % (Active Line Module)
>99 % (Active Interface Module)
DC link voltage, approx. The DC link voltage is regulated and can be adjusted as a voltage decoupled from the line voltage.
Factory setting of the DC link voltage: 1.5 × line voltage

Siemens D 21.3 · 2022 3/109


© Siemens 2022

SINAMICS S120 Chassis Format Units


Water-cooled units
Active Line Modules

■ Technical specifications
Line voltage 380 V ... 480 V 3 AC Active Line Modules
6SL3335-7TE41-0AA7 6SL3335-7TE41-4AA7
Rated power
• At IN DC (50 Hz 400 V) kW 630 900
• At IH DC (50 Hz 400 V) kW 545 780
• At IN DC (60 Hz 460 V) hp 900 1250
• At IH DC (60 Hz 460 V) hp 800 1000
DC link current
• Rated current IN DC A 1100 1573
• Base-load current IH DC 1) A 982 1401
3 • Maximum current Imax DC A 1654 2361
Infeed/regenerative feedback current
• Rated current Irated I A 985 1405
• Maximum current Imax I A 1477 2055
Current demand
• 24 V DC auxiliary power supply A 1.6 1.6
DC link capacitance
• Active Line Module F 18900 28800
• Drive line-up, max. F 230400 230400
Pulse frequency kHz 2.5 2.5
Power loss, at 50 Hz 400 V 2)
• Dissipated to coolant kW 7.46 9.58
• Dissipated to ambient air kW 0.44 0.62
• Total kW 7.9 10.2
Coolant volume flow 3) l/min (US 27 (7.13) 27 (7.13)
gal./min)
Liquid volume dm3 1.56 1.56
of the integrated heat exchanger
Pressure drop, typ. 4) Pa 70000 70000
for volume flow
Heat exchanger material Copper-nickel alloy Copper-nickel alloy
Coolant connections Pipe thread ISO 228 G 3/4 B
Intake/return (external thread 3/4", flat-sealing)
Sound pressure level LpA 5) dB 71/73 71/73
(1 m) at 50/60 Hz
Line supply connection 2 x hole for M12 2 x hole for M12
U1, V1, W1
• Conductor cross-section, max. (IEC) mm2 Busbar Busbar
DC link connection 2 × hole for M12 2 × hole for M12
DCP, DCN Busbar Busbar
PE/GND connection 2 × hole for M12 2 × hole for M12
• Conductor cross-section, max. (IEC) mm2 4 × 240 4 × 240
Cable length, max. 6)
• Shielded m (ft) 3900 (12795) 3900 (12795)
• Unshielded m (ft) 5850 (19193) 5850 (19193)
Dimensions
• Width mm (in) 295 (11.6) 295 (11.6)
• Height mm (in) 1510 (59.4) 1510 (59.4)
• Depth mm (in) 545 (21.5) 545 (21.5)
Weight, approx. kg (lb) 230 (507) 230 (507)
Frame size JXL JXL
Minimum short-circuit current 7) kA 16 21

1) 4)
The base-load current IH DC is the basis for a duty cycle of 150 % for 60 s or The value is valid for water as coolant.
Imax DC for 5 s with a duty cycle duration of 300 s. Additional information and notes on other coolants are provided in the
2)
The specified power loss represents the maximum value at 100 % SINAMICS Low Voltage Engineering Manual.
5)
utilization. The value is lower under normal operating conditions. To ensure Total sound pressure level of Active Interface Module and Active Line
safe dissipation of the minor power loss released to the ambient air, it is Module.
important to follow the instructions pertaining to control cabinet installation 6)
Total of all motor cables and DC link. Longer cable lengths for specific
in the SINAMICS Low Voltage Engineering Manual. configurations are available on request.
3)
The value applies to coolants comprising water and a mixture of water and For additional information, please refer to the SINAMICS Low Voltage
antifreeze agent. Engineering Manual.
7)
Current required for reliably triggering protective devices.

3/110 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Chassis Format Units


Water-cooled units
Active Line Modules

■ Technical specifications
Line voltage 500 ... 690 V 3 AC Active Line Modules
6SL3335-7TG38-1AA7 6SL3335-7TG41-0AA7 6SL3335-7TG41-3AA7 6SL3335-7TG41-6AA7
Rated power
• At IN DC (50 Hz 690 V) kW 900 1100 1400 1700
• At IH DC (50 Hz 690 V) kW 670 1000 1215 1490
• At IN DC (50 Hz 500 V) kW 620 780 965 1180
• At IH DC (50 Hz 500 V) kW 485 710 880 1080
• At IN DC (60 Hz 575 V) hp 975 1250 1500 1880
• At IH DC (60 Hz 575 V) hp 765 1000 1250 1530
DC link current
• Rated current IN DC
• Base-load current IH DC 1)
A
A
907
808
1147
936
1422
1266
1740
1550
3
• Maximum current Imax DC A 1360 1722 2133 2620
Infeed/regenerative feedback current
• Rated current IN I A 810 1025 1270 1560
• Maximum current Imax I A 1214 1537 1905 2055
Current demand
• 24 V DC auxiliary power supply A 1.6 1.6 1.46 1.5
DC link capacitance
• Active Line Module F 10500 16000 19330 21000
• Drive line-up, max. F 153600 153600 153600 210000
Pulse frequency kHz 2.5 2.5 2.5 2.5
Power loss, at 50 Hz 690 V 2)
• Dissipated to coolant kW 8.28 10.37 12.98 17.17
• Dissipated to ambient air kW 0.22 0.53 0.57 0.79
• Total kW 8.5 10.9 13.55 17.96
Coolant volume flow 3) l/min (US 16 (4.23) 27 (7.13) 27 (7.13) 27 (7.13)
gal./min)
Liquid volume dm3 0.74 1.56 1.56 1.56
of the integrated heat exchanger
Pressure drop, typ. 4) Pa 70000 70000 70000 70000
for volume flow
Heat exchanger material Copper-nickel alloy Copper-nickel alloy Copper-nickel alloy Copper-nickel alloy
Coolant connections Pipe thread ISO 228 G 3/4 B
Intake/return (external thread 3/4", flat-sealing)
Sound pressure level LpA 5) dB 71/73 71/73 71/73 71/73
(1 m) at 50/60 Hz
Line supply connection 2 × hole for M12 2 × hole for M12 2 × hole for M12 2 × hole for M12
U1, V1, W1
• Conductor cross-section, max. (IEC) mm2 4 × 185 Busbar Busbar Busbar
DC link connection 2 × hole for M12 2 × hole for M12 2 × hole for M12 2 × hole for M12
DCP, DCN Busbar Busbar Busbar Busbar
PE/GND connection 2 × hole for M12 2 × hole for M12 2 × hole for M12 2 × hole for M12
• Conductor cross-section, max. (IEC) mm2 4 × 185 Busbar Busbar Busbar
Cable length, max. 6)
• Shielded m (ft) 2250 (7382) 2250 (7382) 2250 (7382) 2250 (7382)
• Unshielded m (ft) 3375 (11073) 3375 (11073) 3375 (11073) 3375 (11073)
Dimensions
• Width mm (in) 265 (10.4) 295 (11.6) 295 (11.6) 295 (11.6)
• Height mm (in) 987 (38.9) 1510 (59.4) 1510 (59.4) 1510 (59.4)
• Depth mm (in) 545 (21.5) 545 (21.5) 545 (21.5) 545 (21.5)
Weight, approx. kg (lb) 125 (276) 230 (507) 230 (507) 230 (507)
Frame size HXL JXL JXL JXL
Minimum short-circuit current 7) kA 12.6 16 20 24

1) 4)
The base-load current IH DC is the basis for a duty cycle of 150 % for 60 s or The value is valid for water as coolant.
Imax DC for 5 s with a duty cycle duration of 300 s. Additional information and notes on other coolants are provided in the
2)
The specified power loss represents the maximum value at 100 % SINAMICS Low Voltage Engineering Manual.
5)
utilization. The value is lower under normal operating conditions. To ensure Total sound pressure level of Active Interface Module and Active Line
safe dissipation of the minor power loss released to the ambient air, it is Module.
important to follow the instructions pertaining to control cabinet installation 6)
Total of all motor cables and DC link. Longer cable lengths for specific
in the SINAMICS Low Voltage Engineering Manual. configurations are available on request.
3)
The value applies to coolants comprising water and a mixture of water and For additional information, please refer to the SINAMICS Low Voltage
antifreeze agent. Engineering Manual.
7)
Current required for reliably triggering protective devices.

Siemens D 21.3 · 2022 3/111


© Siemens 2022

SINAMICS S120 Chassis Format Units


Water-cooled units
Active Interface Modules

■ Overview ■ Accessories
Installation kit for Active Interface Modules
The installation kit contains support plates, holding plates,
partition plates, insulating mats and mounting hardware for
installing an Active Interface Module in a 600 mm wide control
cabinet.
Note:
When using the installation kit, the mounting device can also be
used for installing and removing the filter module.

3 ■ Selection and ordering data


Suitable for Rated power of Active Interface Module,
Active Line Module the Active Line water-cooled
in chassis format, Modules at
water-cooled 400 V or 690 V
kW Article No.
Line voltage 380 ... 480 V 3 AC
The Active Interface Module essentially comprises a water- 6SL3335-7TE41-0AA7 630 6SL3305-7TE41-4AA7
cooled filter reactor and a water-cooled filter module. The filter
6SL3335-7TE41-4AA7 900 6SL3305-7TE41-4AA7
module contains a Clean Power Filter with basic RI suppression,
the pre-charging circuit for the Active Line Module, the line Line voltage 500 ... 690 V 3 AC
voltage sensing circuit and monitoring sensors. 6SL3335-7TG38-1AA7 900 6SL3305-7TG41-0AA7
A bypass contactor is provided separately. Active Interface 6SL3335-7TG41-0AA7 1100 6SL3305-7TG41-0AA7
Modules are used in conjunction with Active Line Modules. 6SL3335-7TG41-3AA7 1400 6SL3305-7TG41-3AA7
The water-cooled Active Interface Modules are specifically 6SL3335-7TG41-6AA7 1700 6SL3305-7TG41-6AA7
designed for the operation of shared cooling circuits for the
plant, motor, and converter. Extended liability for defects

Siemens offers for SINAMICS S120 chassis units an extended


■ Design liability for defects/Service Protect up to 6½ years.
Active Interface Modules have the following interfaces as Details can be found in chapter
standard: Services and Documentation
• 1 line supply connection Accessories
• 1 load connection
Description Article No.
• 1 connection for the 24 V DC electronics power supply
Installation kit for Active Interface 6SL3065-1FJ00-0AA0
• 1 connection for the external 230 V AC supply Modules
• 1 DRIVE-CLiQ socket (on VSM10 Voltage Sensing Module) for installation in a Rittal TS8 control cabinet
• 1 connection for pre-charging circuit
• 1 PE/protective conductor connection
• 2 cooling water connections
The scope of supply of the Active Interface Modules includes:
• Water-cooled filter reactor
• Water-cooled filter module
• Connection kit (cables and hoses)
• DRIVE-CLiQ cable for the connection between Active
Interface Module and Active Line Module
• 2 seals for cooling water connections
• 1 set of warning labels in 30 languages
(BG, CN, CZ, DE, DK, EE, ES, FI, FR, GB, GR, HU, IE, IS, IT,
JP, KR, LT, LV, MT, NL, NO, PL, PT, RO, RU, SE, SI, SK, TR)

3/112 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Chassis Format Units


Water-cooled units
Active Interface Modules

■ Integration
X500

DRIVE-CLiQ socket
-X609 Filter module
PE LED
1 READY
P24
External 2 X520
P24 5
24 V DC 3 M Active 6
4 M Interface Voltage
L 5 Module Sensing Module
3
External 6
230 V AC 7
P7
N 8
1) 9
Control Cooling circuit
pre-charging contactor 10
Pre-charging contactor
Control 1) 11
bypass contactor / fan 12
13
Contactors open 14

Resistor and series


resonant circuit
components
Bypass contactor
P6
-K4
2/T1
4/T2
6/T3
-X1

3NE1 021-0
(100 A) G_D211_EN_00362a
U1 V1 W1 PE

2)
P1 P4
Cooling circuit
Main switch

U1 U2
L1
V1 V2 to the
L2 Active
W1 W2 Line
L3
Module
PE PE PE

1)
Control via Active Line Module X1
2) 1 2
With line SCCR > 40 kA: SITOR 3NE3 231 (350 A)
Filter reactor

Connection example of water-cooled Active Interface Module with external bypass contactor

Siemens D 21.3 · 2022 3/113


© Siemens 2022

SINAMICS S120 Chassis Format Units


Water-cooled units
Active Interface Modules

■ Technical specifications
Line voltage 380 ... 480 V 3 AC Active Interface Module
6SL3305-7TE41-4AA7
Suitable for Active Line Module
• Rated power at 400 V kW 630 900
- Water-cooled 6SL3335-7TE41-0AA7 6SL3335-7TE41-4AA7
Rated current A 985 1405
Bypass contactor 1) 3WA1112-4AE03-4EQ0 3WA1116-4AE03-4EQ0
Current demand
• 24 V DC auxiliary power supply A 0.17 0.17

3 • 230 V 2 AC
- Inrush current A 1.0 1.0
- Holding current A 0.1 0.1
DC link capacitance
• Drive line-up, max. 2) F 230400 230400
Coolant volume flow l/min (US 10 (2.64) 10 (2.64)
gal./min)
Pressure drop, typ. Pa 70000 70000
for volume flow
Sound pressure level LpA dB 71/71 71/71
(1 m) at 50/60 Hz
Frame size JIL JIL
Filter reactor
Power loss 3)
• At 50 Hz 400 V kW 6.0 8.6
• At 60 Hz 460 V kW 6.0 8.6
• Dissipated to ambient air kW 0.9 0.9
Liquid volume
• Of integrated reactor cooler dm3 0.6 0.6
• Of hoses supplied dm3/m 0.285 0.285
Coolant volume flow l/min (US 10 (2.64) 10 (2.64)
gal./min)
Heat exchanger material Copper-nickel alloy Copper-nickel alloy
Coolant connections Pipe thread ISO 228 G 3/4 B
Return and connection to filter module (external thread 3/4", flat-sealing)
Line/load connection Flat connector for M12 screws Flat connector for M12 screws
L1, L2, L3 / U2, V2, W2
PE/GND connection M10 stud M10 stud
• Conductor cross-section, max. (IEC) mm2 1 × 240 1 × 240
Degree of protection IP00 IP00
Dimensions
• Width mm (in) 382 (15.0) 382 (15.0)
• Height mm (in) 698 (27.5) 698 (27.5)
• Depth mm (in) 575 (22.6) 575 (22.6)
Weight, approx. kg (lb) 299 (659) 299 (659)
Filter module
Power loss 3)
• At 50 Hz 400 V kW 3.6 3.6
• At 60 Hz 460 V kW 3.6 3.6
• Dissipated to ambient air kW 0.15 0.15
Liquid volume dm3 1 1
Heat exchanger material Copper-nickel alloy Copper-nickel alloy
Coolant connections Pipe thread ISO 228 G 3/4 B
Intake and connection to filter reactor (external thread 3/4", flat-sealing)
PE/GND connection Flat connector for M8 screw Flat connector for M8 screw
• Conductor cross-section, max. (IEC) mm2 2 × 120 2 × 120

3/114 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Chassis Format Units


Water-cooled units
Active Interface Modules

■ Technical specifications
Line voltage 380 ... 480 V 3 AC Active Interface Module
6SL3305-7TE41-4AA7
Degree of protection IP00 IP00
Dimensions
• Width mm (in) 300 (11.8) 300 (11.8)
• Height mm (in) 864 (34.0) 864 (34.0)
• Depth mm (in) 540 (21.3) 540 (21.3)
Weight, approx. kg (lb) 160 (353) 160 (353)

1) The bypass contactor is not included in the scope of supply. 3) The specified power loss represents the maximum value at 100 %
2) Information on higher capacitances is included in the SINAMICS Low utilization. The value is lower under normal operating conditions. To ensure
Voltage Engineering Manual. safe dissipation of the minor power loss released to the ambient air, it is
important to follow the instructions pertaining to control cabinet installation
in the SINAMICS Low Voltage Engineering Manual.

Siemens D 21.3 · 2022 3/115


© Siemens 2022

SINAMICS S120 Chassis Format Units


Water-cooled units
Active Interface Modules

■ Technical specifications
Line voltage 500 ... 690 V 3 AC Active Interface Modules
6SL3305-7TG41-0AA7 6SL3305-7TG41-3AA7 6SL3305-7TG41-6AA7
Suitable for Active Line Module
• Rated power at 690 V kW 900/1100 1400 1700
- Water-cooled 6SL3335-7TG38-1AA7 6SL3335-7TG41-3AA7 6SL3335-7TG41-6AA7
6SL3335-7TG41-0AA7
Rated current A 1025 1270 1560
Bypass contactor 1) 3WA1220-4AE03-4EQ0-Z 3WA1220-4AE03-4EQ0-Z 3WA1220-4AE03-4EQ0-Z
B12 B16 B16
Current demand
3 • 24 V DC auxiliary power supply A 0.17 0.17 0.17
• 230 V 2 AC
- Inrush current A 1.0 1.0 1.0
- Holding current A 0.1 0.1 0.1
DC link capacitance
• Drive line-up, max. 2) F 153600 153600 210000
Coolant volume flow l/min 10 (2.64) 10 (2.64) 10 (2.64)
(US
gal./mi
n)
Pressure drop, typ. Pa 70000 70000 70000
for volume flow
Sound pressure level LpA dB 71/71 71/71 71/71
(1 m) at 50/60 Hz
Frame size JIL JIL JIL
Filter reactor
Power loss 3)
• At 50 Hz 690 V kW 6.2 9.3 11.0
• At 60 Hz 575 V kW 6.2 9.3 11.0
• Dissipated to ambient air kW 0.6 0.95 1.15
Liquid volume
• Of integrated reactor cooler dm3 0.6 0.6 0.6
• Of hoses supplied dm3/m 0.285 0.285 0.285
Coolant volume flow l/min 10 (2.64) 10 (2.64) 10 (2.64)
(US
gal./mi
n)
Heat exchanger material Copper-nickel alloy Copper-nickel alloy Copper-nickel alloy
Coolant connections Pipe thread ISO 228 G 3/4 B
Return and connection to filter module (external thread 3/4", flat-sealing)
Line/load connection Flat connector for M12 screws Flat connector for M12 screws Flat connector for M12 screws
L1, L2, L3 / U2, V2, W2
PE/GND connection M10 stud M10 stud M10 stud
• Conductor cross-section, max. (IEC) mm2 1 × 240 1 × 240 1 × 240
Degree of protection IP00 IP00 IP00
Dimensions
• Width mm (in) 440 (17.3) 440 (17.3) 440 (17.3)
• Height mm (in) 705 (27.8) 705 (27.8) 705 (27.8)
• Depth mm (in) 575 (22.6) 575 (22.6) 580 (22.8)
Weight, approx. kg (lb) 365 (805) 365 (805) 365 (805)
Filter module
Power loss 3)
• At 50 Hz 690 V kW 5.0 5.0 7.5
• At 60 Hz 575 V kW 5.0 5.0 7.5
• Dissipated to ambient air kW 0.15 0.15 0.15
Liquid volume dm3 1 1 1
Heat exchanger material Copper-nickel alloy Copper-nickel alloy Copper-nickel alloy
Coolant connections Pipe thread ISO 228 G 3/4 B
Intake and connection to filter reactor (external thread 3/4", flat-sealing)
PE/GND connection Flat connector for M8 screw Flat connector for M8 screw Flat connector for M8 screw
• Conductor cross-section, max. (IEC) mm2 2 × 120 2 × 120 2 × 120

3/116 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Chassis Format Units


Water-cooled units
Active Interface Modules

■ Technical specifications
Line voltage 500 ... 690 V 3 AC Active Interface Modules
6SL3305-7TG41-0AA7 6SL3305-7TG41-3AA7 6SL3305-7TG41-6AA7
Degree of protection IP00 IP00 IP00
Dimensions
• Width mm (in) 300 (11.8) 300 (11.8) 300 (11.8)
• Height mm (in) 864 (34.0) 864 (34.0) 864 (34.0)
• Depth mm (in) 540 (21.3) 540 (21.3) 540 (21.3)
Weight, approx. kg (lb) 160 (353) 160 (353) 160 (353)

1) 3)
The bypass contactor is not included in the scope of supply. The specified power loss represents the maximum value at 100 %
2)
Information on higher capacitances is included in the SINAMICS Low utilization. The value is lower under normal operating conditions. To ensure
Voltage Engineering Manual. safe dissipation of the minor power loss released to the ambient air, it is
important to follow the instructions pertaining to control cabinet installation
in the SINAMICS Low Voltage Engineering Manual.

Siemens D 21.3 · 2022 3/117


© Siemens 2022

SINAMICS S120 Chassis Format Units


Water-cooled units
Motor Modules

■ Overview ■ Selection and ordering data


Type rating Rated output current Motor Module
at 400 V or 690 V
kW A Article No.
Line voltage 380 ... 480 V 3 AC
(DC link voltage 510 ... 720 V DC)
110 210 6SL3325-1TE32-1AA3
132 260 6SL3325-1TE32-6AA3
160 310 6SL3325-1TE33-1AA3
250 490 6SL3325-1TE35-0AA3
3 400 745 6SL3325-1TE37-5AA7
560 985 6SL3325-1TE41-0AA7
710 1260 6SL3325-1TE41-2AA7
800 1405 6SL3325-1TE41-4AA7
Line voltage 500 ... 690 V 3 AC
(DC link voltage 675 ... 1035 V DC)
A Motor Module comprises a self-commutated inverter with 90 100 6SL3325-1TG31-0AA3
IGBTs. It generates a variable voltage with variable frequency 132 150 6SL3325-1TG31-5AA3
from the DC link voltage that feeds the connected motor.
200 215 6SL3325-1TG32-2AA3
Multiple Motor Modules can be operated on a single DC link. 315 330 6SL3325-1TG33-3AA3
This permits energy to be transferred between the Motor
Modules. This means that if one Motor Module operating in 450 465 6SL3325-1TG34-7AA7
generator mode produces energy, the energy can be used by 560 575 6SL3325-1TG35-8AA7
another Motor Module operating in motor mode. 800 810 6SL3325-1TG38-1AA7
Motor Modules are controlled by a Control Unit. 1000 1025 6SL3325-1TG41-0AA7
The water-cooled Motor Modules are specifically designed for 1200 1270 6SL3325-1TG41-3AA7
the operation of shared cooling circuits for the plant, motor, and 1500 1560 6SL3325-1TG41-6AA7
converter.
Extended liability for defects
■ Design Siemens offers for SINAMICS S120 chassis units an extended
The water-cooled Motor Modules have the following interfaces liability for defects/Service Protect up to 6½ years.
as standard: Details can be found in chapter
• 1 motor connection Services and Documentation
• 1 connection for the 24 V DC electronics power supply Accessories
• 1 DC link connection (DCP, DCN) for connecting to the supply
DC link Description Article No.

• 3 DRIVE-CLiQ sockets 3-way valve 1) VXF41...


VXG41...
• 1 temperature sensor input for KTY84-130, Pt1000, PTC,
or Pt100 (Pt1000 can be used from firmware V4.7 HF17 and Actuator for 3-way valve 1)
higher) • 230 V 1 AC SAX31...
• 24 V AC/DC SAX61...
• 1 connection for Safe Brake Adapter
SAX81...
• 1 connection for Safety Integrated
Accessories for re-ordering
• 2 PE/protective conductor connections
Dust protection blanking plugs 6SL3066-4CA00-0AA0
• 2 cooling water connections (50 units)
The status of the Motor Modules is indicated via three LEDs. For DRIVE-CLiQ port

The scope of supply of the Motor Modules includes: For motor-side components, see System components.
• 1 DRIVE-CLiQ cable for connection to the Control Unit
• 2 seals for cooling water connections
• 1 set of warning labels in 30 languages
(BG, CN, CZ, DE, DK, EE, ES, FI, FR, GB, GR, HU, IE, IS, IT,
JP, KR, LT, LV, MT, NL, NO, PL, PT, RO, RU, SE, SI, SK, TR)

1)
Recommended components for installing a flow control as condensation
protection; manufactured by Siemens Building Technologies.

3/118 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Chassis Format Units


Water-cooled units
Motor Modules

■ Integration
The water-cooled Motor Modules communicate with the higher-
level control module via DRIVE-CLiQ. The control module in this
case can be a CU320-2 or a SIMOTION D Control Unit.

X400 X401 X402

DRIVE-CLiQ socket 0

DRIVE-CLiQ socket 1

DRIVE-CLiQ socket 2
DCP
DC link DCN

Motor
Module
chassis = 3
format =
-X9
1 P24 V
ext.
24 V DC 1
2 M
2 Internal
power supply -X2 PE
3
VL1
4 U2
VL2 =
5 V2 M
HS1
6 ~ W2 3~
HS2
7
EP +24 V
8
EP M1

-X41
4 READY
LEDs

+Temp
3 -Temp DC LINK
2
EP +24 V
1 POWER OK
EP M1 Cooling circuit

-X42
1 P24L
2 P24L
3 M
4 M

-X46 IPD Card


1 BR Output+
2
G_D213_EN_00041d

BR Output-
3 FB Input+
4 FB Input-

Connection example of a water-cooled Motor Module

Siemens D 21.3 · 2022 3/119


© Siemens 2022

SINAMICS S120 Chassis Format Units


Water-cooled units
Motor Modules

■ Technical specifications
General technical specifications
Electrical specifications
Efficiency 98.5 %
DC link voltage 510 ... 720 V DC (line voltage 380 ... 480 V 3 AC) or
(up to 2000 m (6562 ft) above sea level) 675 ... 1035 V DC (line voltage 500 ... 690 V 3 AC)
Output frequency 1)
• Control mode Servo 0 ... 550 Hz
• Control mode Vector 0 ... 550 Hz
• Control mode V/f 0 ... 550 Hz

3 Safety Integrated Safety Integrity Level 2 (SIL2) acc. to IEC 61508, Performance Level d (PLd) acc. to EN ISO 13849-1 and Control
Category 3 acc. to EN ISO 13849-1.

1)
Please note:
• The correlation between the maximum output frequency, pulse frequency
and current derating. Higher output frequencies on request. For further
information, see
https://support.industry.siemens.com/cs/document/104020669
• The correlation between the minimum output frequency and permissible
output current (current derating).
For additional information, please refer to the SINAMICS Low Voltage
Engineering Manual.

3/120 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Chassis Format Units


Water-cooled units
Motor Modules

■ Technical specifications
Line voltage 380 ... 480 V 3 AC Motor Modules
DC link voltage 510 ... 720 V DC
6SL3325-1TE32-1AA3 6SL3325-1TE32-6AA3 6SL3325-1TE33-1AA3 6SL3325-1TE35-0AA3
Type rating
• At IL (50 Hz 400 V) 1) kW 110 132 160 250
• At IH (50 Hz 400 V) 1) kW 90 110 132 200
• At IL (60 Hz 460 V) 2) hp 150 200 250 400
• At IH (60 Hz 460 V) 2) hp 150 200 200 350
Output current
• Rated current IN O A 210 260 310 490
• Base-load current IL 3)
• Base-load current IH 4)
A
A
205
178
250
233
302
277
477
438
3
• Maximum current Imax O A 307 375 453 715
DC link current
• Rated current IN DC
when supplied via
- Basic Line Module A 256 317 380 600
- Active Line Module A 230 287 340 538
• Base-load current IL DC 3)
when supplied via
- Basic Line Module A 250 305 368 581
- Active Line Module A 225 274 331 522
• Base-load current IH DC 4)
when supplied via
- Basic Line Module A 227 284 338 534
- Active Line Module A 195 255 303 480
Current demand
• 24 V DC auxiliary power supply A 1.4 1.4 1.5 1.5
DC link capacitance F 4800 5800 8400 9600
5)
Pulse frequency
• Rated frequency kHz 2 2 2 2
• Pulse frequency, max.
- Without current derating kHz 2 2 2 2
- With current derating kHz 8 8 8 8
Power loss, max. 6)
• At 50 Hz 400 V kW 1.61 1.95 2.29 3.56
• At 60 Hz 460 V kW 1.68 2.06 2.38 3.74
• Dissipated to ambient air kW 0.06 0.07 0.09 0.14
Coolant volume flow 7) l/min (US 9 (2.38) 9 (2.38) 12 (3.17) 12 (3.17)
gal./min)
Liquid volume dm3 0.31 0.31 0.91 0.91
of the integrated heat exchanger
Pressure drop, typ. 8) Pa 70000 70000 70000 70000
for volume flow
Heat exchanger material Stainless steel Stainless steel Stainless steel Stainless steel
Coolant connections Pipe thread ISO 228 G 3/4 B
Intake/return (external thread 3/4", flat-sealing)
Sound pressure level LpA dB 52 52 52 52
(1 m) at 50/60 Hz
DC link connection 2 × hole for M12 2 × hole for M12 2 × hole for M12 2 × hole for M12
DCP, DCN Busbar Busbar Busbar Busbar
Motor connection Hole for M12 Hole for M12 Hole for M12 Hole for M12
U2, V2, W2
• Conductor cross-section, max. (IEC) mm2 2 × 95 2 × 95 2 × 240 2 × 240

Siemens D 21.3 · 2022 3/121


© Siemens 2022

SINAMICS S120 Chassis Format Units


Water-cooled units
Motor Modules

■ Technical specifications
Line voltage 380 ... 480 V 3 AC Motor Modules
DC link voltage 510 ... 720 V DC
6SL3325-1TE32-1AA3 6SL3325-1TE32-6AA3 6SL3325-1TE33-1AA3 6SL3325-1TE35-0AA3
PE/GND connection 2 × hole for M12 2 × hole for M12 2 × hole for M12 2 × hole for M12
• Conductor cross-section, max. (IEC) mm2 2 × 95 2 × 95 2 × 240 2 × 240
Cable length, max. 9)
• Shielded m (ft) 300 (984) 300 (984) 300 (984) 300 (984)
• Unshielded m (ft) 450 (1476) 450 (1476) 450 (1476) 450 (1476)
Dimensions
• Width mm (in) 150 (5.91) 150 (5.91) 150 (5.91) 150 (5.91)
3 • Height
• Depth
mm (in)
mm (in)
746 (29.4)
545 (21.5)
746 (29.4)
545 (21.5)
1172 (46.1)
545 (21.5)
1172 (46.1)
545 (21.5)
Weight, approx. kg (lb) 41 (90.4) 41 (90.4) 80 (176) 80 (176)
Frame size FXL FXL GXL GXL

1) 6)
Rated power of a typical 6-pole standard induction motor based on IL or IH The specified power loss represents the maximum value at 100 %
for 400 V 3 AC 50 Hz. utilization. The value is lower under normal operating conditions. To ensure
2)
Rated power of a typical 6-pole standard induction motor based on IL or IH safe dissipation of the minor power loss released to the ambient air, it is
for 460 V 3 AC 60 Hz. important to follow the instructions pertaining to control cabinet installation
3)
in the SINAMICS Low Voltage Engineering Manual.
The base-load current IL is based on a duty cycle of 110 % for 60 s or 7)
150 % for 10 s with a duty cycle duration of 300 s. The value applies to coolants comprising water and a mixture of water and
4)
antifreeze agent.
The base-load current IH is based on a duty cycle of 150 % for 60 s or 8)
160 % for 10 s with a duty cycle duration of 300 s. The value is valid for water as coolant.
5)
Additional information and notes on other coolants are provided in the
Additional notes regarding the correlation between the pulse frequency SINAMICS Low Voltage Engineering Manual.
and maximum output current/output frequency is provided in the 9)
SINAMICS Low Voltage Engineering Manual. Total of all motor cables. Longer cable lengths for specific configurations
are available on request.
For additional information, please refer to the SINAMICS Low Voltage
Engineering Manual.

3/122 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Chassis Format Units


Water-cooled units
Motor Modules

■ Technical specifications
Line voltage 380 ... 480 V 3 AC Motor Modules
DC link voltage 510 ... 720 V DC
6SL3325-1TE37-5AA7 6SL3325-1TE41-0AA7 6SL3325-1TE41-2AA7 6SL3325-1TE41-4AA7
Type rating
• At IL (50 Hz 400 V) 1) kW 400 560 710 800
• At IH (50 Hz 400 V) 1) kW 315 450 630 710
• At IL (60 Hz 460 V) 2) hp 600 800 1000 1150
• At IH (60 Hz 460 V) 2) hp 450 700 900 1000
Output current
• Rated current IN O A 745 985 1260 1405
• Base-load current IL 3)
• Base-load current IH 4)
A
A
725
570
960
860
1230
1127
1370
1257
3
• Maximum current Imax O A 1087 1440 1845 2055
DC link current
• Rated current IN DC
when supplied via
- Basic Line Module A 894 1202 1512 1714
- Active Line Module A 805 1080 1361 1544
• Base-load current IL DC 3)
when supplied via
- Basic Line Module A 871 1170 1474 1670
- Active Line Module A 784 1051 1326 1500
• Base-load current IH DC 4)
when supplied via
- Basic Line Module A 795 1048 1345 1532
- Active Line Module A 716 942 1211 1377
Current demand
• 24 V DC auxiliary power supply A 1.6 1.46 1.46 1.46
DC link capacitance F 17400 21000 29000 29000
5)
Pulse frequency
• Rated frequency kHz 1.25 1.25 1.25 1.25
• Pulse frequency, max.
- Without current derating kHz 1.25 1.25 1.25 1.25
- With current derating kHz 8 8 8 8
Power loss, max. 6)
• At 50 Hz 400 V kW 5.1 7.9 9.15 10.2
• At 60 Hz 460 V kW 5.61 8.55 10.05 11.2
• Dissipated to ambient air kW 0.2 0.44 0.56 0.62
Coolant volume flow 7) l/min (US 16 (4.23) 27 (7.13) 27 (7.13) 27 (7.13)
gal./min)
Liquid volume dm3 0.74 1.56 1.56 1.56
of the integrated heat exchanger
Pressure drop, typ. 8) Pa 70000 70000 70000 70000
for volume flow
Heat exchanger material Copper-nickel alloy Copper-nickel alloy Copper-nickel alloy Copper-nickel alloy
Coolant connections Pipe thread ISO 228 G 3/4 B
Intake/return (external thread 3/4", flat-sealing)
Sound pressure level LpA dB 54 56 56 56
(1 m) at 50/60 Hz
DC link connection 2 × hole for M12 2 × hole for M12 2 × hole for M12 2 × hole for M12
DCP, DCN Busbar Busbar Busbar Busbar
Motor connection 2 × hole for M12 2 × hole for M12 2 × hole for M12 2 × hole for M12
U2, V2, W2
• Conductor cross-section, max. (IEC) mm2 4 × 185 4 × 240 4 × 240 4 × 240

Siemens D 21.3 · 2022 3/123


© Siemens 2022

SINAMICS S120 Chassis Format Units


Water-cooled units
Motor Modules

■ Technical specifications
Line voltage 380 ... 480 V 3 AC Motor Modules
DC link voltage 510 ... 720 V DC
6SL3325-1TE37-5AA7 6SL3325-1TE41-0AA7 6SL3325-1TE41-2AA7 6SL3325-1TE41-4AA7
PE/GND connection 2 × hole for M12 2 × hole for M12 2 × hole for M12 2 × hole for M12
• Conductor cross-section, max. (IEC) mm2 4 × 185 Busbar Busbar Busbar
Cable length, max. 9)
• Shielded m (ft) 300 (984) 300 (984) 300 (984) 300 (984)
• Unshielded m (ft) 450 (1476) 450 (1476) 450 (1476) 450 (1476)
Dimensions
• Width mm (in) 265 (10.4) 295 (11.6) 295 (11.6) 295 (11.6)
3 • Height
• Depth
mm (in)
mm (in)
987 (38.9)
545 (21.5)
1510 (59.4)
545 (21.5)
1510 (59.4)
545 (21.5)
1510 (59.4)
545 (21.5)
Weight, approx. kg (lb) 125 (276) 230 (507) 230 (507) 230 (507)
Frame size HXL JXL JXL JXL

1) Rated power of a typical 6-pole standard induction motor based on IL or IH 6) The specified power loss represents the maximum value at 100 %
for 400 V 3 AC 50 Hz. utilization. The value is lower under normal operating conditions. To ensure
2) Rated power of a typical 6-pole standard induction motor based on IL or IH safe dissipation of the minor power loss released to the ambient air, it is
for 460 V 3 AC 60 Hz. important to follow the instructions pertaining to control cabinet installation
3)
in the SINAMICS Low Voltage Engineering Manual.
The base-load current IL is based on a duty cycle of 110 % for 60 s or 7)
150 % for 10 s with a duty cycle duration of 300 s. The value applies to coolants comprising water and a mixture of water and
4)
antifreeze agent.
The base-load current IH is based on a duty cycle of 150 % for 60 s or 8)
160 % for 10 s with a duty cycle duration of 300 s. The value is valid for water as coolant.
5)
Additional information and notes on other coolants are provided in the
Additional notes regarding the correlation between the pulse frequency SINAMICS Low Voltage Engineering Manual.
and maximum output current/output frequency is provided in the 9)
SINAMICS Low Voltage Engineering Manual. Total of all motor cables. Longer cable lengths for specific configurations
are available on request.
For additional information, please refer to the SINAMICS Low Voltage
Engineering Manual.

3/124 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Chassis Format Units


Water-cooled units
Motor Modules

■ Technical specifications
Line voltage 500 ... 690 V 3 AC Motor Modules
DC link voltage 675 ... 1035 V DC
6SL3325-1TG31-0AA3 6SL3325-1TG31-5AA3 6SL3325-1TG32-2AA3 6SL3325-1TG33-3AA3
Type rating
• At IL (50 Hz 690 V) 1) kW 90 132 200 315
• At IH (50 Hz 690 V) 1) kW 75 110 160 250
• At IL (50 Hz 500 V) 1) kW 55 90 132 200
• At IH (50 Hz 500 V) 1) kW 55 90 132 200
• At IL (60 Hz 575 V) 2) hp 75 150 200 300
• At IH (60 Hz 575 V) 2) hp 75 125 200 250
Output current
• Rated current IN O A 100 150 215 330
3
• Base-load current IL 3) A 95 142 208 320
• Base-load current IH 4) A 89 134 192 280
• Maximum current Imax O A 142 213 312 480
DC link current
• Rated current IN DC
when supplied via
- Basic Line Module A 122 183 263 403
- Active Line Module A 110 165 237 363
• Base-load current IL DC 3)
when supplied via
- Basic Line Module A 116 173 253 390
- Active Line Module A 105 156 229 352
• Base-load current IH DC 4)
when supplied via
- Basic Line Module A 108 163 234 341
- Active Line Module A 98 147 211 308
Current demand
• 24 V DC auxiliary power supply A 1.0 1.0 1.5 1.5
DC link capacitance F 2800 2800 4200 5800
Pulse frequency 5)
• Rated frequency kHz 1.25 1.25 1.25 1.25
• Pulse frequency, max.
- Without current derating kHz 1.25 1.25 1.25 1.25
- With current derating kHz 7.5 7.5 7.5 7.5
Power loss, max. 6)
• At 50 Hz 690 V kW 1.15 1.64 2.34 3.38
• At 60 Hz 575 V kW 1.02 1.45 2.05 2.96
• Dissipated to ambient air kW 0.06 0.07 0.09 0.12
Coolant volume flow 7) l/min (US 9 (2.38) 9 (2.38) 12 (3.17) 12 (3.17)
gal./min)
Liquid volume dm3 0.31 0.31 0.91 0.91
of the integrated heat exchanger
Pressure drop, typ. 8) Pa 70000 70000 70000 70000
for volume flow
Heat exchanger material Stainless steel Stainless steel Stainless steel Stainless steel
Coolant connections Pipe thread ISO 228 G 3/4 B
Intake/return (external thread 3/4", flat-sealing)
Sound pressure level LpA dB 52 52 52 52
(1 m) at 50/60 Hz
DC link connection 2 × hole for M12 2 × hole for M12 2 × hole for M12 2 × hole for M12
DCP, DCN Busbar Busbar Busbar Busbar
Motor connection Hole for M12 Hole for M12 Hole for M12 Hole for M12
U2, V2, W2
2
• Conductor cross-section, max. (IEC) mm 2 × 95 2 × 95 4 × 240 4 × 240

Siemens D 21.3 · 2022 3/125


© Siemens 2022

SINAMICS S120 Chassis Format Units


Water-cooled units
Motor Modules

■ Technical specifications
Line voltage 500 ... 690 V 3 AC Motor Modules
DC link voltage 675 ... 1035 V DC
6SL3325-1TG31-0AA3 6SL3325-1TG31-5AA3 6SL3325-1TG32-2AA3 6SL3325-1TG33-3AA3
PE/GND connection 2 × hole for M12 2 × hole for M12 2 × hole for M12 2 × hole for M12
• Conductor cross-section, max. (IEC) mm2 2 × 95 2 × 95 2 × 240 2 × 240
Cable length, max. 9)
• Shielded m (ft) 300 (984) 300 (984) 300 (984) 300 (984)
• Unshielded m (ft) 450 (1476) 450 (1476) 450 (1476) 450 (1476)
Dimensions
• Width mm (in) 150 (5.91) 150 (5.91) 150 (5.91) 150 (5.91)
3 • Height
• Depth
mm (in)
mm (in)
728 (28.7)
545 (21.5)
728 (28.7)
545 (21.5)
1172 (46.1)
545 (21.5)
1172 (46.1)
545 (21.5)
Weight, approx. kg (lb) 41 (90.4) 41 (90.4) 80 (176) 80 (176)
Frame size FXL FXL GXL GXL

1) 6)
Rated power of a typical 6-pole standard induction motor based on IL or IH The specified power loss represents the maximum value at 100 %
for 500 V or 690 V 3 AC 50 Hz. utilization. The value is lower under normal operating conditions. To ensure
2)
Rated power of a typical 6-pole standard induction motor based on IL or IH safe dissipation of the minor power loss released to the ambient air, it is
for 575 V 3 AC 60 Hz. important to follow the instructions pertaining to control cabinet installation
3)
in the SINAMICS Low Voltage Engineering Manual.
The base-load current IL is based on a duty cycle of 110 % for 60 s or 7)
150 % for 10 s with a duty cycle duration of 300 s. The value applies to coolants comprising water and a mixture of water and
4)
antifreeze agent.
The base-load current IH is based on a duty cycle of 150 % for 60 s or 8)
160 % for 10 s with a duty cycle duration of 300 s. The value is valid for water as coolant.
5)
Additional information and notes on other coolants are provided in the
Additional notes regarding the correlation between the pulse frequency SINAMICS Low Voltage Engineering Manual.
and maximum output current/output frequency is provided in the SINAMICS 9)
Low Voltage Engineering Manual. Total of all motor cables. Longer cable lengths for specific configurations
are available on request.
For additional information, please refer to the SINAMICS Low Voltage
Engineering Manual.

3/126 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Chassis Format Units


Water-cooled units
Motor Modules

■ Technical specifications
Line voltage 500 ... 690 V 3 AC Motor Modules
DC link voltage 675 ... 1035 V DC
6SL3325-1TG34-7AA7 6SL3325-1TG35-8AA7
Type rating
• At IL (50 Hz 690 V) 1) kW 450 560
• At IH (50 Hz 690 V) 1) kW 400 450
• At IL (50 Hz 500 V) 1) kW 315 400
• At IH (50 Hz 500 V) 1) kW 250 315
• At IL (60 Hz 575 V) 2) hp 450 600
• At IH (60 Hz 575 V) 2) hp 450 500
Output current
• Rated current IN O A 465 575
3
• Base-load current IL 3) A 452 560
• Base-load current IH 4) A 416 514
• Maximum current Imax O A 678 840
DC link current
• Rated current IN DC
when supplied via
- Basic Line Module A 558 702
- Active Line Module A 502 632
• Base-load current IL DC 3)
when supplied via
- Basic Line Module A 544 683
- Active Line Module A 489 616
• Base-load current IH DC 4)
when supplied via
- Basic Line Module A 496 627
- Active Line Module A 446 565
Current demand
• 24 V DC auxiliary power supply A 1.6 1.6
DC link capacitance F 9670 9670
Pulse frequency 5)
• Rated frequency kHz 1.25 1.25
• Pulse frequency, max.
- Without current derating kHz 1.25 1.25
- With current derating kHz 7.5 7.5
Power loss, max. 6)
• At 50 Hz 690 V kW 5.44 5.61
• At 60 Hz 575 V kW 5.1 5.45
• Dissipated to ambient air kW 0.14 0.16
Coolant volume flow 7) l/min (US 16 (4.23) 16 (4.23)
gal./min)
Liquid volume dm3 0.74 0.74
of the integrated heat exchanger
Pressure drop, typ. 8) Pa 70000 70000
for volume flow
Heat exchanger material Copper-nickel alloy Copper-nickel alloy
Coolant connections Pipe thread ISO 228 G 3/4 B
Intake/return (external thread 3/4", flat-sealing)
Sound pressure level LpA dB 54 54
(1 m) at 50/60 Hz
DC link connection 2 × hole for M12 2 × hole for M12
DCP, DCN Busbar Busbar
Motor connection 2 × hole for M12 2 × hole for M12
U2, V2, W2
2
• Conductor cross-section, max. (IEC) mm 4 × 185 4 × 185
PE/GND connection 2 × hole for M12 2 × hole for M12
• Conductor cross-section, max. (IEC) mm2 4 × 185 4 × 185

Siemens D 21.3 · 2022 3/127


© Siemens 2022

SINAMICS S120 Chassis Format Units


Water-cooled units
Motor Modules

■ Technical specifications
Line voltage 500 ... 690 V 3 AC Motor Modules
DC link voltage 675 ... 1035 V DC
6SL3325-1TG34-7AA7 6SL3325-1TG35-8AA7
9)
Cable length, max.
• Shielded m (ft) 300 (984) 300 (984)
• Unshielded m (ft) 450 (1476) 450 (1476)
Dimensions
• Width mm (in) 265 (10.4) 265 (10.4)
• Height mm (in) 987 (38.9) 987 (38.9)
• Depth mm (in) 545 (21.5) 545 (21.5)
3 Weight, approx. kg (lb) 125 (276) 125 (276)
Frame size HXL HXL

1) Rated power of a typical 6-pole standard induction motor based on IL or IH 6) The specified power loss represents the maximum value at 100 %
for 500 V or 690 V 3 AC 50 Hz. utilization. The value is lower under normal operating conditions. To ensure
2) Rated power of a typical 6-pole standard induction motor based on IL or IH safe dissipation of the minor power loss released to the ambient air, it is
for 575 V 3 AC 60 Hz. important to follow the instructions pertaining to control cabinet installation
3)
in the SINAMICS Low Voltage Engineering Manual.
The base-load current IL is based on a duty cycle of 110 % for 60 s or 7)
150 % for 10 s with a duty cycle duration of 300 s. The value applies to coolants comprising water and a mixture of water and
4)
antifreeze agent.
The base-load current IH is based on a duty cycle of 150 % for 60 s or 8)
160 % for 10 s with a duty cycle duration of 300 s. The value is valid for water as coolant.
5)
Additional information and notes on other coolants are provided in the
Additional notes regarding the correlation between the pulse frequency SINAMICS Low Voltage Engineering Manual.
and maximum output current/output frequency is provided in the 9)
SINAMICS Low Voltage Engineering Manual. Total of all motor cables. Longer cable lengths for specific configurations
are available on request.
For additional information, please refer to the SINAMICS Low Voltage
Engineering Manual.

3/128 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Chassis Format Units


Water-cooled units
Motor Modules

■ Technical specifications
Line voltage 500 ... 690 V 3 AC Motor Modules
DC link voltage 675 ... 1035 V DC
6SL3325-1TG38-1AA7 6SL3325-1TG41-0AA7 6SL3325-1TG41-3AA7 1) 6SL3325-1TG41-6AA7 1)
Type rating
• At IL (50 Hz 690 V) 2) kW 800 1000 1200 1500
• At IH (50 Hz 690 V) 2) kW 710 900 1000 1260
• At IL (50 Hz 500 V) 2) kW 560 710 900 1000
• At IH (50 Hz 500 V) 2) kW 560 630 800 900
• At IL (60 Hz 575 V) 3) hp 800 1000 1250 1500
• At IH (60 Hz 575 V) 3) hp 700 900 1000 1250
Output current
• Rated current IN O A 810 1025 1270 1560
3
• Base-load current IL 4) A 790 1000 1230 1500
• Base-load current IH 5) A 724 917 1136 1284
• Maximum current Imax O A 1185 1500 1600 1950
DC link current
• Rated current IN DC
when supplied via
- Basic Line Module A 990 1250 1550 1903
- Active Line Module A 891 1125 1395 1714
• Base-load current IL DC 4)
when supplied via
- Basic Line Module A 963 1219 1500 1800
- Active Line Module A 869 1100 1353 1650
• Base-load current IH DC 5)
when supplied via
- Basic Line Module A 883 1118 1384 1680
- Active Line Module A 796 1009 1250 1550
Current demand
• 24 V DC auxiliary power supply A 1.46 1.46 1.46 1.46
DC link capacitance F 14000 16000 19330 21000
Pulse frequency 6)
• Rated frequency kHz 1.25 1.25 1.25 1.25
• Pulse frequency, max.
- Without current derating kHz 1.25 1.25 1.25 1.25
- With current derating kHz 7.5 7.5 7.5 7.5
Power loss, max. 7)
• At 50 Hz 690 V kW 9.56 10.87 13.49 17.9
• At 60 Hz 575 V kW 8.34 9.55 11.84 15.7
• Dissipated to ambient air kW 0.43 0.53 0.57 0.78
Coolant volume flow 8) l/min (US 27 (7.13) 27 (7.13) 27 (7.13) 27 (7.13)
gal./min)
Liquid volume dm3 1.56 1.56 1.56 1.56
of the integrated heat exchanger
Pressure drop, typ. 9) Pa 70000 70000 70000 70000
for volume flow
Heat exchanger material Copper-nickel alloy Copper-nickel alloy Copper-nickel alloy Copper-nickel alloy
Coolant connections Pipe thread ISO 228 G 3/4 B
Intake/return (external thread 3/4", flat-sealing)
Sound pressure level LpA dB 56 56 56 56
(1 m) at 50/60 Hz
DC link connection 2 × hole for M12 2 × hole for M12 2 × hole for M12 2 × hole for M12
DCP, DCN Busbar Busbar Busbar Busbar
Motor connection 2 × hole for M12 2 × hole for M12 2 × hole for M12 2 × hole for M12
U2, V2, W2
2
• Conductor cross-section, max. (IEC) mm Busbar Busbar Busbar Busbar

Siemens D 21.3 · 2022 3/129


© Siemens 2022

SINAMICS S120 Chassis Format Units


Water-cooled units
Motor Modules

■ Technical specifications
Line voltage 500 ... 690 V 3 AC Motor Modules
DC link voltage 675 ... 1035 V DC
6SL3325-1TG38-1AA7 6SL3325-1TG41-0AA7 6SL3325-1TG41-3AA7 1) 6SL3325-1TG41-6AA7 1)
PE/GND connection 2 × hole for M12 2 × hole for M12 2 × hole for M12 2 × hole for M12
• Conductor cross-section, max. (IEC) mm2 Busbar Busbar Busbar Busbar
Cable length, max. 10)
• Shielded m (ft) 300 (984) 300 (984) 300 (984) 300 (984)
• Unshielded m (ft) 450 (1476) 450 (1476) 450 (1476) 450 (1476)
Dimensions
• Width mm (in) 295 (11.6) 295 (11.6) 295 (11.6) 295 (11.6)
3 • Height
• Depth
mm (in)
mm (in)
1510 (59.4)
545 (21.5)
1510 (59.4)
545 (21.5)
1510 (59.4)
545 (21.5)
1510 (59.4)
545 (21.5)
Weight, approx. kg (lb) 230 (507) 230 (507) 230 (507) 240 (529)
Frame size JXL JXL JXL JXL

1) 7)
The short-time current for 10 s for low overload must be reduced from The specified power loss represents the maximum value at 100 %
150 % to 130 % for this Motor Module. At 10 s and 60 s, the short-time utilization. The value is lower under normal operating conditions. To ensure
current for high overload must be reduced to 130 % for this Motor Module. safe dissipation of the minor power loss released to the ambient air, it is
The duty cycle remains unchanged. important to follow the instructions pertaining to control cabinet installation
2)
Rated power of a typical 6-pole standard induction motor based on IL or IH in the SINAMICS Low Voltage Engineering Manual.
8)
for 500 V or 690 V 3 AC 50 Hz. The value applies to coolants comprising water and a mixture of water and
3)
Rated power of a typical 6-pole standard induction motor based on IL or IH antifreeze agent.
9)
for 575 V 3 AC 60 Hz. The value is valid for water as coolant.
4)
The base-load current IL is based on a duty cycle of 110 % for 60 s or Additional information and notes on other coolants are provided in the
150 % for 10 s with a duty cycle duration of 300 s. SINAMICS Low Voltage Engineering Manual.
10)
5)
The base-load current IH is based on a duty cycle of 150 % for 60 s or Total of all motor cables. Longer cable lengths for specific configurations
160 % for 10 s with a duty cycle duration of 300 s. are available on request.
6)
For additional information, please refer to the SINAMICS Low Voltage
Additional notes regarding the correlation between the pulse frequency Engineering Manual.
and maximum output current/output frequency are provided in the
SINAMICS Low Voltage Engineering Manual.

3/130 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Chassis Format Units


Water-cooled units
Mounting device for water-cooled power units

■ Overview ■ Selection and ordering data


Description Article No.
Mounting device 6SL3766-1CA00-0AA0
for installing and removing power units

The mounting device is used to install or remove water-cooled


power units (Power Modules, Line Modules, Motor Modules, filter
module on the Active Interface Module) in or out of a control
cabinet. The mounting device can be used if the power units are
mounted on mounting rails, which at the front have two M6
threads at a vertical distance of 20 mm to attach the mounting
device.
The mounting device is a mounting aid. It is placed in front of the
power unit and attached to the mounting rails below the power
unit. The telescopic rails allow the mounting device to be
adjusted to the installation height and width of the power unit.
The power unit can be removed from the control cabinet after
releasing the mechanical and electrical connections and the
coolant connections. The power unit is guided and supported by
the guide rails on the mounting device. To prevent it toppling
over, the power unit must be secured to a crane, tripod, or similar
assembly using the lifting lugs or the lifting equipment. The unit
can then be lowered down from the mounting device.

Siemens D 21.3 · 2022 3/131


© Siemens 2022

SINAMICS S120 Chassis Format Units

Notes

3/132 Siemens D 21.3 · 2022


4
© Siemens 2022

SINAMICS S120 Chassis-2 Format Converter Units

4/2 System overview


4/2 Overview
4/4 Function
4/5 Technical specifications

4/6 Air-cooled units


4/6 Technical specifications
4/8 Characteristic curves
4/11 Active Infeeds
4/17 Active Line Modules
4/18 Active Interface Modules
4/21 Motor Modules
4/26 Mounting aid for Motor Modules/
Active Line Modules in chassis-2 format
4/27 OEM kits for control cabinet installation
4/28 Mechanical Installation Kits
4/29 DC-Busbar Kits Basic
4/30 DC-Busbar Kits Fuse
4/31 Busbar Connection Kits
4/32 Line Connection Kit for Active Interface
Modules
4/33 Motor Connection Kits
4/34 Protection Kits
4/36 Installation Ramp Kit

Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Chassis-2 Converter Units

System overview

■ Overview
Switch disconnector Active Active Line
and fuses or Interface Module
circuit-breaker Module

...

Line =
contactor Motor
Module

G_D211_EN_00446
M
3

Motor Modules
4 A voltage DC link and an inverter for supplying a motor are
integrated in the Motor Module.
With its separate power unit and Control Unit, the SINAMICS
S120 drive system can be perfectly adapted to a wide variety of
different drive tasks.
Control DRIVE-CLiQ
The Control Unit is selected according to the number of drives to Unit
be controlled and the required performance level, while the
power unit must be rated to meet requirements regarding
regenerative feedback capability or energy exchange.
The connection between the Control Unit and power unit is made
very simply using the DRIVE-CLiQ digital system interface.
~
The following devices are available in chassis-2 format:
• Active Infeeds (Active Line Module and Active Interface =
Module) = =
Line Motor
• Motor Modules Module Module
~ ~

G_D211_XX_00043
Highlights of the built-in units in chassis-2 format
• Compact, innovative mechanical design with reduced
footprint M M
3~ 3~
• Rated pulse frequency of the Motor Modules 2.5 kHz
• Optimized derating
Motor Modules are designed for multi-axis drive systems and are
• Innovative cooling concept controlled by either a CU320-2 Control Unit or a SIMOTION D
• Condition monitoring Control Unit. Motor Modules are interconnected through the
DC link.
• Very easy replacement of the device fans
One or several Motor Modules are supplied with energy for the
Active Infeed motors via the DC link. Both synchronous and asynchronous
Active Infeeds comprise an Active Line Module and an motors can be operated.
Active Interface Module. Active Line Modules contain the central Since the Motor Modules share the same DC link, they can
line infeed for the intermediate DC circuit. They can supply exchange energy with one another, i.e. if one Motor Module
energy and return regenerative energy to the supply system. operating in the generator mode produces energy, the energy
Active Line Modules produce a stabilized DC voltage that can be used by another Motor Module operating in the motor
remains constant regardless of fluctuations in the line voltage if mode. The DC link is supplied with line supply voltage by
the line voltage remains within the permissible tolerances. Active a Line Module.
Line Modules in combination with an Active Interface Module
draw a virtually sinusoidal current from the supply system.
Almost no harmonics occur.
The total harmonic distortion factors of the current THD(I) and
voltage THD(U) are typically in the range of approx. 3 % for rated
current. THD(I) is calculated according to IEEE 519 (2014) and
THD(U) according to IEC 61000-2-4 (2002). The stringent limit
values of IEEE 519 (2014) are typically complied with.

4/2 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Chassis-2 Converter Units

System overview

■ Overview
Control Units Coated modules
The control intelligence for all the drive axes integrated in the The following devices are equipped as standard with coated
multi-axis group is combined in the Control Units. They also modules:
feature drive-related inputs/outputs and interfaces for • Devices in chassis-2 format
communicating with higher-level controllers. Control Units are
available with different ranges of functions and with different • Control Units
performance levels. • Sensor Modules
System components • Terminal Modules
• Advanced Operator Panel (AOP30)
The structure of the drive system is defined by selecting the
Control Unit, Line Modules and Motor Modules. The additional The coating on the modules protects the sensitive
components provided allow optimum adaptation of the drive SMD components against corrosive gases, chemically active
system to the application. dust and moisture.
These components are subdivided into: Nickel-plated busbars
• Line-side components, All of the copper busbars used are nickel-plated in order to
e.g. components for pre-charging achieve the best possible immunity to environmental effects.
• DC link components,
e.g. DC link fuses
Furthermore, there is no need to clean the contacts on the
customer terminals as otherwise required for bare copper
4
• Motor-side components, e.g. motor reactors and dv/dt filters connections.
plus VPL Note:
• Supplementary system components, e.g. Terminal For some components, parts of the copper busbars cannot be
Modules, Operator Panels, and Communication Boards nickel-plated for technical reasons.
• Encoder system interface for connecting various encoder
types to SINAMICS S120
DRIVE-CLiQ – the digital interface between the components
The SINAMICS S120 components, including the motors and
encoders, are equipped with the high-performance DRIVE-CLiQ
system interface. DRIVE-CLiQ interfaces are used, for example,
to connect Line Modules and Motor Modules to the Control Unit,
as well as Terminal Modules and Sensor Modules to the drive
system – simply and efficiently. Motors that also have this
interface can be directly connected to the drive system.
Converter boards (Sensor Modules) for converting standard
encoder signals to DRIVE-CLiQ are available for third-party
motors or retrofit applications.
The electronic rating plate
An important digital linkage element of the SINAMICS S120
drive system are the electronic rating plates integrated in every
component. They allow all drive components to be automatically
identified via the DRIVE-CLiQ link.
The electronic rating plate contains all the relevant technical
data about that particular component. In addition to the
technical data, the rating plate includes logistical data
(manufacturer ID, article number and ID). Since this data can be
called up electronically on site or remotely, all the components
used in a machine can always be individually identified, which
helps simplify servicing.

Siemens D 21.3 · 2022 4/3


© Siemens 2022

SINAMICS S120 Chassis-2 Converter Units

System overview

■ Function
Communication with higher-level controller Open-loop and closed-loop control functions
As customer interface to a higher-level control, as standard there SINAMICS S120 can use a dynamic, high-precision closed-loop
is a PROFIBUS or PROFINET communication interface on the vector control (drive object type VECTOR), or a highly dynamic
Control Unit CU320-2; there are also expansions such as the closed-loop servo control (drive object type SERVO).
Terminal Module TM31, the Terminal Board TB30 and modules
to communicate via CANopen or EtherNet/IP. Software and protective functions

These interfaces can be used to connect the system to the The software functions available as standard are described
higher-level controller using analog and digital signals, or to below:
connect additional units.
For additional information, please refer to the SINAMICS Low
Voltage Engineering Manual.
Software and protective Description
functions
Setpoint input The setpoint can be specified both internally and externally; internally as a fixed setpoint, motorized potentiometer setpoint or
jog setpoint, externally via the communications interface or an analog input. The internal fixed setpoint and the motorized

4 Motor identification
potentiometer setpoint can be switched or adjusted via control commands from any interface.
The automatic motor identification function makes commissioning faster and easier and optimizes closed-loop control of the
drive.
Ramp-function generator A user-friendly ramp-function generator with separately adjustable ramp-up and ramp-down times, together with adjustable
rounding times in the lower and upper speed ranges, allows the drive to be smoothly accelerated and braked. This results in
a good speed control response and contributes to the reduction of stress on the mechanical system. The down ramp can be
parameterized separately for a quick stop.
Vdc max controller The Vdc max controller automatically prevents overvoltage in the DC link, if the set down ramp is too short, for example.
This may also extend the set ramp-down time.
Note: This function only makes sense for single-axis applications.
Kinetic buffering (KIP) For brief line supply failures, the kinetic energy of the rotating drive is used to buffer the DC link and therefore prevents fault
trips. The converter remains operational as long as the drive can provide regenerative energy as a result of its motion and the
DC link voltage does not drop below the shutdown threshold. When the line supply recovers within this time, the drive is
smoothly accelerated up to its setpoint speed again.
Automatic restart The automatic restart switches the drive on again when the power is restored after a power failure, and ramps up to the current
speed setpoint.
Flying restart The flying restart function allows the converter to be switched to a motor that is still turning. With the voltage sensing capability
provided by the optional VSM10, the flying restart time for large asynchronous motors can be significantly reduced because
the motor does not need to be de-magnetized.
Technology controller (PID) Using the technology controller (PID controller) function module, level or flow controls and complex tension controls can be
implemented, for example. The existing D component can act both on the system deviation as well as on the actual value
(factory setting). The P, I, and D components are set separately.
Free function blocks (FFB) Using the freely programmable function blocks, it is easy to implement logic and arithmetic functions for controlling the
SINAMICS drive. The blocks can be programmed at the operator panel or the STARTER commissioning tool.
Drive Control Chart (DCC) SINAMICS DCC comprises the block library, so-called DCB Drive Control Blocks and the DCC Editor for graphical
interconnection of blocks. SINAMICS DCC is primarily employed to solve arithmetic and control-related tasks or logic functions
associated with complex applications.
In addition to the DCB Standard library, the DCB Extension library can also be used to create applications.
The DCB Extension library is comprised of freely programmable blocks which are created for specific applications using DCB
Studio and are then graphically interconnected with the DCC Editor in a similar fashion to standard blocks.
SINAMICS Technology SINAMICS Technology Extensions are configurable firmware expansions of Siemens that are specifically created for use in
Extensions (SINAMICS TEC) a customized application with special requirements.
This functionality can therefore be subsequently installed as an add-on to the standard scope of firmware functions.
I2t sensing for motor A motor model stored in the converter software calculates the motor temperature based on the current speed and load. More
protection exact sensing of the temperature, which also takes into account the influence of the ambient temperature, is possible by means
of direct temperature sensing using Pt1000/KTY84 sensors in the motor winding.
Motor temperature evaluation Motor protection by evaluating a KTY84, PTC, Pt100 or Pt1000 temperature sensor. When a KTY84 temperature sensor is
connected, the limit values can be set for alarm or shutdown. When a PTC thermistor is connected, the system reaction to
triggering of the thermistor (alarm or trip) can be defined.
Motor blocking protection A blocked motor is detected and protected against thermal overloading by a fault trip.
Brake control "Simple brake control" for control of holding brakes:
The holding brake is used to secure drives against unwanted motion when deactivated.
"Extended brake control" function module for complex brake control, e.g. for motor holding brakes and operational brakes:
When braking with a feedback signal, the brake control reacts to the feedback signal contacts of the brake.
Write protection Write protection to prevent unintentional changing of the setting parameters (without password function).
Know-how protection Know-how protection for encrypting stored data, e.g. to protect configuration know-how, and to protect against changes and
duplication (with password function)
Web server The web server provides information about the drive unit via its web pages. The web server is accessed using an internet
browser via unsecured (http) or secured transfer protocol (https).

4/4 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Chassis-2 Converter Units

System overview

■ Function
Power unit protection
Power unit protection Description
Ground fault monitoring at A ground fault at the output is detected by a total current monitor and results in shutdown in grounded systems.
the output
Electronic short-circuit A short-circuit at the output (e.g. at the converter output terminals, in the motor cable or in the motor terminal box) is detected
protection at the output and the converter shuts down with "fault".
Thermal overload protection An alarm is issued first when the overtemperature threshold responds. If the temperature continues to rise, the unit either shuts
down or independently adjusts the pulse frequency or output current so that thermal load is reduced. Once the cause of the
fault has been eliminated (e.g. cooling has been improved), the original operating values are automatically resumed.

■ Technical specifications
The most important directives and standards are listed below. These are used as the basis for the SINAMICS S120 built-in units in
chassis format and they must be carefully observed to achieve an EMC-compliant configuration that is safe both functionally and in
operation.
European directives
2014/35/EU Low-voltage Directive:
4
Directive of the European Parliament and Council of February 26, 2014 for the harmonization of the laws of the member states
relating to the provision of electrical equipment designed for use within certain voltage limits on the market (recast)
2014/30/EU EMC Directive:
Directive of the European Parliament and Council of February 26, 2014 for the harmonization of the laws of the member states
relating to electromagnetic compatibility (recast)
2006/42/EC Machinery Directive:
Directive of the European Parliament and Council of May 17, 2006, on machinery and amending Directive 95/16/EC (recast)
2011/65/EU RoHS II Directive:
Directive of the European Parliament and of the Council of 8 June 2011 on the restriction of the use of certain hazardous
substances in electrical and electronic equipment (recast)
European standards
EN ISO 3744 Acoustics – Determination of sound power levels and sound energy levels of noise sources using sound pressure –
Engineering methods for an essentially free field over a reflecting plane
EN ISO 13849-1 Safety of machinery – Safety-related parts of control systems
Part 1: General principles for design (EN ISO 13849-1: 2006) (replaces EN 954-1)
EN 60146-1-1 Semiconductor converters – General requirements and line-commutated converters
Part 1-1: Specification of basic requirements
EN 60204-1 Safety of machinery – Electrical equipment of machines
Part 1: General requirements
EN 60529 Degrees of protection provided by enclosures (IP code)
IEC 61508-1 Functional safety of electrical/electronic/programmable electronic safety-related systems
Part 1: General requirements
IEC 61508-2 Functional safety of electrical/electronic/programmable electronic safety-related systems
Part 2: Requirements for electrical/electronic/programmable electronic safety-related systems
IEC 61508-3 Functional safety of electrical/electronic/programmable electronic safety-related systems
Part 3: Software requirements
EN 61800-2 Adjustable speed electrical power drive systems
Part 2: General requirements – Rating specifications for low voltage adjustable frequency AC power drive systems
EN 61800-3 Adjustable speed electrical power drive systems
Part 3: EMC requirements and specific test methods
EN 61800-5-1 Adjustable speed electrical power drive systems
Part 5: Safety requirements
Main section 1: Electrical and thermal requirements
EN 61800-5-2 Adjustable speed electrical power drive systems
Part 5-2: Safety requirements – Functional safety (IEC 61800-5-2: 2007)
North American standards
UL 508A Industrial Control Panels
UL 508C Power Conversion Equipment
UL 61800-5-1 Adjustable Speed Electrical Power Drive Systems - Part 5-1: Safety requirements – Electrical, thermal and energy
CSA C22.2 No. 14 Industrial Control Equipment
Certificates of suitability
cULus, cURus Testing by UL (Underwriters Laboratories, www.ul.com) according to UL and CSA standards

Test codes and UL files:


( Appendix, approvals)

Siemens D 21.3 · 2022 4/5


© Siemens 2022

SINAMICS S120 Chassis-2 Converter Units


Air-cooled units

■ Technical specifications
General technical specifications
Unless clearly specified otherwise, the following technical data are valid for all the following components of the air-cooled
SINAMICS S120 drive system in chassis-2 format.
Electrical specifications
Line voltages 380 ... 480 V 3 AC ±10 % (-15 % < 1 min)
Line system configurations Grounded TN/TT systems or non-grounded IT systems
Line frequency 47 ... 63 Hz
Overvoltage category III acc. to EN 61800-5-1
Electronics power supply 24 V DC, -15 % +20 %
implemented as PELV circuit acc. to EN 61800-5-1
Ground = negative pole grounded via the electronics
Rated short-circuit current 100 kA
Acc. to IEC, in conjunction with the specified
fuses or circuit breakers
Rated short-circuit current SCCR 100 kA
4 (Short Circuit Current Rating)
Acc. to UL61800-5-1, in conjunction with the
specified fuses or circuit breakers
Control method Vector/Servo control with and without encoder or V/f control
Fixed speeds 15 fixed speeds plus 1 minimum speed, parameterizable
(in the default setting, 3 fixed setpoints plus 1 minimum speed are selectable using terminal
strip/PROFIBUS/PROFINET)
Skippable speed ranges 4, parameterizable
Setpoint resolution 0.001 rpm digital (14 bits + sign)
12 bits analog
Braking operation With Active Line Modules (energy recovery). Braking by means of a Motor Module.
Mechanical specifications
Degree of protection IP00
Protection class I acc. to EN 61800-5-1
Touch protection EN 50274/DGUV regulation 3 when used as intended
Cooling method Forced air cooling AF according to EN 60146

4/6 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Chassis-2 Converter Units


Air-cooled units

■ Technical specifications
Ambient conditions Storage 1) Transport 1) Operation
Ambient temperature -25 ... +55 °C (-13 ... 131 °F) -25 ... +70 °C (-13 ... +158 °F) • -10 ... +45 °C (14 ... 113 °F) at
Class 1K4 Class 2K4 installation altitude  1000 m
acc. to EN 60721-3-1 (1997) acc. to EN 60721-3-2 (1997) (3281 ft) above sea level without
derating
• -10 ... +40 °C (14 ... 104 °F) at
installation altitude  2000 m
(6562 ft) above sea level without
derating
• > 45 ... +60 °C (113 ... 140 °F) at
installation altitude  2000 m
(6562 ft) above sea level,
see derating data
Control Units, supplementary system
components, and Sensor Modules:
0 ... 55 °C (32 ... 131 °F)
(for operation in a control cabinet)
DC link components and motor-side
components:

Relative humidity 5 ... 95 % 5 ... 95 % at 40 °C (104 °F)


0 ... 55 °C (32 ... 131 °F)
5 ... 95 %
4
Condensation, splashwater, and ice Class 1K4 Class 2K3 Class 3K3
formation not permitted (EN 60204, Part 1) acc. to EN 60721-3-1 (1997) acc. to EN 60721-3-2 (1997) acc. to EN 60721-3-3 (2002)
Environmental class/harmful chemical Class 1C2 Class 2C2 Class 3C2
substances acc. to EN 60721-3-1 (1997) acc. to EN 60721-3-2 (1997) acc. to EN 60721-3-3 (2002)
Organic/biological influences Class 1B1 Class 2B1 Class 3B1
acc. to EN 60721-3-1 (1997) acc. to EN 60721-3-2 (1997) acc. to EN 60721-3-3 (2002)
Mechanically active substances Class 1S1 Class 2S1 Class 3S1
acc. to EN 60721-3-1 (1997) acc. to EN 60721-3-2 (1997) acc. to EN 60721-3-3 (2002)
Degree of pollution 2 acc. to EN 61800-5-1
Installation altitude Up to 2000 m (6562 ft) above sea level without derating
> 2000 m (6562 ft) above sea level, see derating data
Mechanical strength Storage 1) Transport 1) Operation
Vibratory load – Class 2M2 Test values
acc. to EN 60721-3-2 (1997) acc. to EN 60068-2-6 test Fc:
• 10 ... 58 Hz with constant
deflection 0.075 mm
• 58 ... 150 Hz with constant
acceleration 9.81 m/s2 (1 × g)
Shock load – Class 2M2 Test values
acc. to EN 60721-3-2 (1997) according to EN 60068-2-27 test
Ea: 98 m/s2 (10 × g)/20 ms
Compliance with standards
Conformances/ CE (EMC Directive 2014/30/EU, Low Voltage Directive 2014/35/EU, and Machinery Directive 2006/42/EC
certificates of suitability, acc. to for functional safety)
RCM, RoHS II,
cULus (only for devices connected to line voltages 380 ... 480 V 3 AC and 500 ... 600 V 3 AC)
Radio interference suppression SINAMICS S120 chassis-2 format units are not designed for connection to the public grid (first environment).
Radio interference suppression is compliant with the EMC product standard for variable-speed drives
EN 61800-3, "second environment" (industrial line supplies). EMC disturbances can occur when connected to the
public grid. However, if additional measures are taken (e.g.  line filter), it can also be operated in the
"first environment".
For additional information, see the SINAMICS Low Voltage Engineering Manual.

Deviations from the specified class are underlined.

1) In transport packaging.

Siemens D 21.3 · 2022 4/7


© Siemens 2022

SINAMICS S120 Chassis-2 Converter Units


Air-cooled units

■ Characteristic curves
Derating data in chassis-2 format The following table lists the permissible output currents
depending on the installation altitude and ambient temperature.
Air-cooled SINAMICS S120 units in chassis-2 format and the The specified values already include a permitted compensation
associated system components are rated for an ambient in respect of installation altitude and ambient temperatures
temperature of 45 °C and installation altitudes up to 1000 m < 40 °C – temperature at the air intake of the built-in unit.
above sea level.
The values apply under the precondition that a cooling air flow
At ambient temperatures > 45 °C, the output current must be through the devices is guaranteed as specified in the technical
reduced. Ambient temperatures above 60 °C are not specifications.
permissible.
As an additional measure for installation altitudes from 2000 m
At installation altitudes > 2000 m above sea level, it must be up to 5000 m, an isolating transformer is required in order to
taken into account that the air pressure, and therefore air density, reduce transient overvoltages according to EN 60664-1.
decreases as the height increases. As a consequence, the For additional information, please refer to the SINAMICS Low
cooling efficiency and the insulation capacity of the air also Voltage Engineering Manual.
decrease.
Due to the reduced cooling efficiency, it is necessary, on the one
hand, to reduce the ambient temperature and on the other hand,
to reduce the heat loss in the built-in unit by reducing the output
4 current, whereby ambient temperatures lower than 45 °C may
be offset to compensate.
Current-derating factors for SINAMICS S120 chassis-2 units as a function of the ambient/air intake temperature and the installation
altitude
Installation Current derating factor (as a percentage of the rated current)
altitude above for an ambient/air intake temperature of
sea level
m (ft) 20 °C (68 °F) 25 °C (77 °F) 30 °C (86 °F) 35 °C (95 °F) 40 °C (104 °F) 45 °C (113 °F) 50 °C (122 °F) 55 °C (131 °F) 60 °C (140 °F)
0 ... 1000 83 % 69 % 54 %
(0 ... 3281)
1001 ... 1500 98 % 81 % 67 % 52 %
(3284 ... 4921)
1501 ... 2000 93 % 78 % 65 % 50 %
(4925 ... 6562)
2001 ... 2500 100 % 96 %
(6565 ... 8202)
2501 ... 3000 99 %
(8205 ... 9843)
3001 ... 3500
(9846 ... 11483)
3501 ... 4000 96 %
(11486 ... 13123)
4001 ... 4500 97 %
(13127 ... 14764)
4501 ... 5000 98 %
(14767 ... 16404)

4/8 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Chassis-2 Converter Units


Air-cooled units

■ Characteristic curves
Current derating for Motor Modules in chassis-2 format as For additional information, please refer to the SINAMICS Low
a function of the pulse frequency Voltage Engineering Manual.
To reduce motor noise or to increase output frequency, the pulse The following table lists the rated output currents of the Motor
frequency can be increased relative to the factory setting Modules in chassis-2 format with pulse frequency set at the
(2.5 kHz). When the pulse frequency is increased, the derating factory as well as the current derating factors (permissible
factor of the output current must be taken into account. This output currents referred to the rated output current) for higher
derating factor must be applied to the currents specified in the pulse frequencies.
technical specifications.
Derating factor of the output current as a function of the pulse frequency for units with a rated pulse frequency of 2.5 kHz
Motor Module Type rating Output current Derating factor at pulse frequency
at 400 V at 2.5 kHz
6SL3321-... kW A 4 kHz 5 kHz 7.5 kHz 8 kHz
380 ... 480 V 3 AC
1TE36-6AA0 315 655 78 % 67 % 48 % 45 %
1TE37-4AA0 355 740 78 % 67 % 48 % 45 %
1TE38-1AA0 400 840 78 % 67 % 48 % 45 % 4
1TE38-8AA0 450 910 78 % 67 % 48 % 45 %
1TE41-0AA0 500 975 78 % 67 % 48 % 45 %
1TE41-1AA0 560 1075 78 % 67 % 48 % 45 %
1TE41-2AA0 630 1200 78 % 67 % 48 % 45 %
1TE41-3AA0 710 1325 78 % 67 % 48 % 45 %
1TE41-5AA0 800 1495 75 % 62 % 39% 36 %

The following tables list the maximum achievable output frequency as a function of the pulse frequency.
Maximum output frequencies achieved by increasing the pulse frequency
The adjustable pulse frequencies – and therefore the output
frequencies that can be achieved with the factory-set current
controller clock cycles – are listed below.
Current controller clock cycle Adjustable pulse frequency Max. achievable output frequency fA
TI fp
V/f mode Vector mode Servo mode
400 s 2.5 kHz 208 Hz 208 Hz –
5.0 kHz 416 Hz 300 Hz –
7.5 kHz 550 Hz 1) 300 Hz –

1)
With the "High output frequencies" license, which can be ordered as option J01 on the CompactFlash card for SINAMICS S120, the maximum output
frequency is increased up to 650 Hz. For more information, see https://support.industry.siemens.com/cs/document/104020669

Siemens D 21.3 · 2022 4/9


© Siemens 2022

SINAMICS S120 Chassis-2 Converter Units


Air-cooled units

■ Characteristic curves
Overload capability The base-load current for duty cycle IS6 is based on a duty cycle
of 200 % for 6 s.
SINAMICS S120 built-in units have an overload reserve, e.g. to
handle breakaway torques. If larger surge loads occur, this must
be taken into account in the configuration. For drives with Converter current
overload requirements, the appropriate base-load current must 6s
therefore be used as a basis for the required load. Short-time current 200 %
2 × IS6

G_D213_EN_00120
The permissible overload levels are valid under the prerequisite
that the drive units are operated with their base-load current
before and after the overload condition based on a duty cycle
duration of 300 s.
Another precondition is that the Motor Modules are operated at
their factory-set pulse frequency at output frequencies >10 Hz. Rated current Irated O (continuous)
For temporary, periodic duty cycles with high variations of load Irated O
within the duty cycle, the relevant sections of the SINAMICS Low
Voltage Engineering Manual must be observed. 0.7 × Irated O
60 s
4 Motor Modules in chassis-2 format Base-load current IS6 for duty cycle S6
The base-load current for a low overload IL is based on a duty
cycle of 110 % for 60 s.
t

Converter current
Duty cycle S6 with initial load with a duty cycle duration of 60 s
Active Line Modules in chassis-2 format
Short-time current 110 %
The base-load current for low overload IL_DC is based on a duty
Rated current Irated O (continuous) cycle of 115 % for 60 s with a duty cycle duration of 300 s, the
maximum current Imax_DC can flow for 5 s.
1.1 × IL Base-load current IL
for low overload
Irated O
IDC
IL
G_D213_EN_00118

Short-time current 115 %


60 s
300 s Rated current (continuous)
1.15 × IL_DC Base-load current IL_DC
for low overload
t In_DC

Low overload IL_DC

G_D213_EN_00126
60 s
The base-load current for a high overload IH is based on a duty
cycle of 150 % for 60 s. 300 s

Converter current t

Short-time current 150 %


Low overload
The duty cycle with maximum current Imax_DC is based on a duty
1.5 × IH Rated current Irated O (continuous) cycle of 150 % for 5 s with a duty cycle duration of 300 s.
Base-load current IH
for high overload IDC
Irated O
5s
IH I max_DC
G_D213_EN_00119

Maximum current
60 s = 1.5 × I L_DC
300 s

t
Rated current (continuous)
I n_DC
High overload
Base-load current I L_DC for low overload
I L_DC
G_D213_EN_00127

300 s

Duty cycle with maximum current

4/10 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Chassis-2 Converter Units


Air-cooled units
Active Infeeds

■ Overview ■ Selection and ordering data


Rated power at 400 V Rated infeed/ Active Infeed
regenerative
feedback current
kW A Article No.
Line voltage 380 ... 480 V 3 AC
355 560 6SL3341-7TE35-6AA0
400 635 6SL3341-7TE36-4AA0
450 745 6SL3341-7TE37-5AA0
500 840 6SL3341-7TE38-4AA0
560 900 6SL3341-7TE38-8AA0
630 985 6SL3341-7TE41-0AA0
710 1110 6SL3341-7TE41-2AA0
800 1260 6SL3341-7TE41-3AA0
900 1405 6SL3341-7TE41-4AA0
4
An Active Line Module in chassis-2 format is offered and
supplied with the associated Active Interface Module in
chassis-2 format as a package with the designation
"Active Infeed".
The article numbers of the individual components (Active
Interface Module in chassis-2 format and Active Line Module
in chassis-2 format) are listed in the table below:
Active Infeed in Rated power Active Interface Active Line
chassis-2 format at 400 V Module in Module in
chassis-2 format chassis-2 format
6SL3341-... kW 6SL3301-... 6SL3331-...
7TE35-6AA0 355 7TE36-4AA0 7TE35-6AA0
7TE36-4AA0 400 7TE36-4AA0 7TE36-4AA0
7TE37-5AA0 450 7TE41-0AA0 7TE37-5AA0
7TE38-4AA0 500 7TE41-0AA0 7TE38-4AA0
7TE38-8AA0 560 7TE41-0AA0 7TE38-8AA0
7TE41-0AA0 630 7TE41-0AA0 7TE41-0AA0
7TE41-2AA0 710 7TE41-4AA0 7TE41-2AA0
7TE41-3AA0 800 7TE41-4AA0 7TE41-3AA0
7TE41-4AA0 900 7TE41-4AA0 7TE41-4AA0

Note:
The pre-charging input circuit that is necessary for operation,
comprised of resistors, a pre-charge contactor and a main
contactor, must be provided separately. The pre-charge
contactor is activated from the Active Line Module.

Siemens D 21.3 · 2022 4/11


© Siemens 2022

SINAMICS S120 Chassis-2 Converter Units


Air-cooled units
Active Infeeds > Active Line Modules

■ Overview Parallel connection for power increase


To increase the power, a parallel connection of up to six Active
Line Modules in chassis-2 format with the same power is
possible. You must observe the following rules:
• Up to 6 identical Active Line Modules in chassis-2 format can
be connected in parallel.
• Each Active Line Module in chassis-2 format requires its own
Active Interface Module in chassis-2 format.
• A common Control Unit is required whenever the modules are
connected in parallel. For more than 4 power units, these must
be distributed as symmetrically as possible between at least
two DRIVE-CLiQ ports (e.g. 3 x 2 Active Line Modules in
series or at least 2 x 3 Active Line Modules in series).
• For multiple infeed units, power must be supplied to the
systems from a common infeed point, i.e. different supply
systems are not permitted.
• The Active Line Modules in chassis-2 format must supply
a shared DC link.
4 • A derating factor of 5 % must be taken into consideration,
The self-commutated infeed/regenerative feedback units act as regardless of the number of modules connected in parallel.
step-up converters and generate a stabilized DC link voltage Note:
that is 1.5x greater (factory setting) than the nominal voltage of
the distribution system. In this way, the connected Motor No mixed operation possible!
Modules are decoupled from the line voltage. This improves the It is only possible to connect identical power units in parallel if all
dynamic response and control quality because line tolerances power units have the same hardware version. Mixed operation of
and fluctuations do not affect the motor voltage. an Active Line Module in chassis format (Article No. 6SL3330-
xxxxx–xAAx) and an Active Line Module in chassis-2 format
If required, the Active Line Modules can also provide reactive (Article No. 6SL3331-xxxxx–xAA0) is not possible.
power compensation.
Active Line Modules are designed for connection to grounded ■ Selection and ordering data
TN/TT and non-grounded IT systems.
Rated power Rated Active Line Module
Active Line Modules in chassis-2 format are always operated at 400 V infeed/regenerative
together with the associated Active Interface Modules in feedback current
chassis-2 format. The pre-charging input circuit, comprising
kW A Article No.
resistors and pre-charge contactor, that is necessary for
operation must be provided separately. The pre-charge Line voltage 380 ... 480 V 3 AC
contactor is activated from the Active Line Module. 355 560 6SL3331-7TE35-6AA0

■ Design
400 635 6SL3331-7TE36-4AA0
450 745 6SL3331-7TE37-5AA0
The Active Line Modules in chassis-2 format feature the 500 840 6SL3331-7TE38-4AA0
following interfaces as standard:
560 900 6SL3331-7TE38-8AA0
• 1 line supply connection
630 985 6SL3331-7TE41-0AA0
• 1 connection for the 24 V DC electronics power supply
710 1110 6SL3331-7TE41-2AA0
• 1 DC link connection (DCP, DCN) for supplying the connected
Motor Modules 800 1260 6SL3331-7TE41-3AA0

• 3 DRIVE-CLiQ sockets 900 1405 6SL3331-7TE41-4AA0

• 1 temperature sensor input for KTY84-130, Pt1000, PTC or Description Article No.
Pt100
Accessories for re-ordering
• 1 connection for the fan supply
Dust protection blanking plugs 6SL3066-4CA00-0AA0
• 1 PE/protective conductor connection (50 units)
For DRIVE-CLiQ port
The status of the Active Line Modules is indicated via three
LEDs.
The scope of supply of the Active Line Modules includes:
• DRIVE-CLiQ cable to connect to a Control Unit
• DRIVE-CLiQ cable to connect the Control Unit to the first Motor
Module
• 1 set of warning labels in 30 languages
(BG, CN, CZ, DE, DK, EE, ES, FI, FR, GB, GR, HU, IE, IS, IT,
JP, KR, LT, LV, MT, NL, NO, PL, PT, RO, RU, SE, SI, SK, TR)

4/12 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Chassis-2 Converter Units


Air-cooled units
Active Infeeds > Active Line Modules

■ Integration
The Active Line Modules in chassis-2 format communicate with the higher-level control module via DRIVE-CLiQ. This control module
can be:
• A CU320-2 Control Unit
• A SIMOTION D Control Unit
An external 24 V DC power supply is required to operate the Active Line Modules.

X400 X401 X402

2
Active Line

DRIVE-CLiQ socket

DRIVE-CLiQ socket

DRIVE-CLiQ socket
-X41
Module Chassis-2
1 EP +24 V
2 EP M1
M
3 +Temp (motor)
4 -Temp (motor)
5
NC
6

-X42
NC
4
READY

LEDs
1 P24L
2 P24L DC LINK
3 M
4 PWR ON
M

-X46
IPD Card
1
BR output+
2
BR output-
3
FB input+
4
FB input-
5
NC
6
NC
-X47 -X49
Pre-charging contactor 1 VL_R LAMPPWR 1
feedback signal 2 M M 2
Main contactor feedback 3 HS_R 3
NC
signal 4 M NC 4
5 NC 5
NC
6 NC 6
NC

-X51 Fans
Connection for fan supply L1
L2
L3
PE

-X9

Pre-charging contactor VL1


control VL2
NC
Main contactor control HS1
HS2
P24 V =
External
24 V DC M
=
Internal
power supply
1
U1 -X1
~ DCP
V1 DCN DC link connection
From the Active
Interface Module W1 =
PE

G_D213_EN_00123a

1 The DC link fuses must be provided on the plant/system side.

Connection example of Active Line Module in chassis-2 format

Siemens D 21.3 · 2022 4/13


© Siemens 2022

SINAMICS S120 Chassis-2 Converter Units


Air-cooled units
Active Infeeds > Active Line Modules

■ Technical specifications
General technical specifications
Electrical specifications
Line power factor
• Basic fundamental (cos 1) 1 (factory setting),
can be altered by inputting a reactive current setpoint
• Total () 1 (factory setting)
Efficiency > 97.5 % (including Active Interface Module)
DC link voltage The DC link voltage is regulated and can be adjusted as a voltage decoupled from the line voltage.
Factory setting of the DC link voltage: 1.5 × line voltage
Radio interference suppression
• Standard (Active Line Module with Active Category C3 acc. to EN 61800-3
Interface Module)

4/14 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Chassis-2 Converter Units


Air-cooled units
Active Infeeds > Active Line Modules

■ Technical specifications
Line voltage 380 ... 480 V 3 AC Active Line Modules
6SL3331-7TE35-6AA0 6SL3331-7TE36-4AA0 6SL3331-7TE37-5AA0 6SL3331-7TE38-4AA0
Rated power
• At IN DC (50 Hz 400 V) kW 355 400 450 500
• At IL DC (50 Hz 400 V) kW 300 350 400 450
• At IN DC (60 Hz 460 V) hp 500 550 650 700
• At IL DC (60 Hz 460 V) hp 400 500 550 650
DC link current
• Rated current IN DC A 630 710 835 940
• Base-load current IL DC A 571 649 760 954
• Maximum current Imax DC A 857 974 1140 1281
Infeed/regenerative feedback
current
• Rated current IN I A 560 635 745 840
• Maximum current Imax I A 773 878 1028 1155
Pulse frequency kHz 4 4 4 4
Current demand 4
• 24 V DC auxiliary power supply A 1.3 1.3 1.3 1.3
• 400 V AC (fan current supply) A 1.8 1.8 1.8 1.8
DC link capacitance
• Active Line Module F 16450 16450 18800 18800
• Drive line-up, max.
- At 400 V / 50 Hz 1) F 130000/400000/ 130000/400000/ 130000/400000/ 130000/400000/
not permissible not permissible not permissible not permissible
- At 480 V / 60 Hz 1)
F 95000/250000/ 95000/250000/ 95000/250000/ 95000/250000/
not permissible not permissible not permissible not permissible
Power loss, max. 2)
• At 50 Hz 400 V kW 4.47 4.47 5.89 6.79
• At 60 Hz 460 V kW 4.48 4.48 5.90 6.80
Cooling air requirement m3/s (ft3/s) 0.64 (22.6) 0.64 (22.6) 0.64 (22.6) 0.64 (22.6)
Sound pressure level LpA dB 72.5 72.5 72.5 72.5
(1 m) at 50/60 Hz
Line supply connection 4 x M12 4 x M12 4 x M12 4 x M12
U1, V1, W1
• Conductor cross-section, max. (IEC) mm2 4 × 240 4 × 240 4 × 240 4 × 240
DC link connection 2 x M12 2 x M12 2 x M12 2 x M12
DCP, DCN
• Conductor cross-section, max. (IEC) mm2 Busbar 70 x 4 Busbar 70 x 6 Busbar 70 x 4 Busbar 70 x 4
PE connection 4 x M12 4 x M12 4 x M12 4 x M12
• Conductor cross-section, max. (IEC) mm2 4 × 240 4 × 240 4 × 240 4 × 240
Cable length, max. 3) 4) 5)
• Shielded m (ft) 3900 (12795) 3900 (12795) 3900 (12795) 3900 (12795)
• Unshielded m (ft) 5850 (19193) 5850 (19193) 5850 (19193) 5850 (19193)
Degree of protection IP00 IP00 IP00 IP00
Dimensions
• Width mm (in) 280 (11.0) 280 (11.0) 280 (11.0) 280 (11.0)
• Height mm (in) 1248 (49.1) 1248 (49.1) 1248 (49.1) 1248 (49.1)
• Depth mm (in) 542 (21.3) 542 (21.3) 542 (21.3) 542 (21.3)
Weight, approx. kg (lb) 119 (262) 119 (262) 122 (269) 122 (269)
Frame size FS2 FS2 FS2+ FS2+
Minimum short-circuit current 6) kA 18 18 14 16

1) The maximum DC link capacitances of the drive line-up depend on the 4) The cable lengths are valid for use in IT systems. When used in TN
number of pre-charging resistors (2.2 ) connected in parallel per phase: systems, the cable lengths are shortened to 30 % of the specified value.
1 pre-charging resistor/2 pre-charging resistors/3 pre-charging resistors. 5) When used in TN systems and during operation of the Active Line Module
2) The specified power loss represents the maximum value at 100 % in chassis-2 format or the connected Motor Modules with increased pulse
utilization. The value is lower under normal operating conditions. frequency, you can obtain the permitted cable lengths on request.
3) Total of all motor cables and DC link. Longer cable lengths for specific 6) Minimum current required for reliably triggering the protective devices.
configurations are available on request.
For additional information, please refer to the SINAMICS Low Voltage
Engineering Manual.

Siemens D 21.3 · 2022 4/15


© Siemens 2022

SINAMICS S120 Chassis-2 Converter Units


Air-cooled units
Active Infeeds > Active Line Modules

■ Technical specifications
Line voltage 380 ... 480 V 3 AC Active Line Modules
6SL3331- 6SL3331- 6SL3331- 6SL3331- 6SL3331-
7TE38-8AA0 7TE41-0AA0 7TE41-2AA0 7TE41-3AA0 7TE41-4AA0
Rated power
• At IN DC (50 Hz 400 V) kW 560 630 710 800 900
• At IL DC (50 Hz 400 V) kW 500 560 630 700 800
• At IN DC (60 Hz 460 V) hp 800 900 1050 1150 1300
• At IL DC (60 Hz 460 V) hp 700 800 900 1000 1150
DC link current
• Rated current IN DC A 1010 1100 1245 1415 1575
• Base-load current IL DC A 915 1004 1131 1287 1432
• Maximum current Imax DC A 1373 1506 1697 1931 2147
Infeed/regenerative feedback
current
• Rated current IN I A 900 985 1110 1260 1405
• Maximum current Imax I A 1238 1358 1530 1740 1935

4 Pulse frequency
Current demand
kHz 4 4 4 4 4

• 24 V DC auxiliary power supply A 1.3 1.3 1.3 1.3 1.3


• 400 V AC (fan current supply) A 1.8 1.8 1.8 1.8 1.8
DC link capacitance
• Active Line Module F 25900 25900 25900 40800 40800
• Drive line-up, max.
- At 400 V / 50 Hz 1) F 130000/400000/ 130000/400000/ 130000/400000/ 130000/400000/ 130000/400000/
630000 630000 630000 630000 630000
- At 480 V / 60 Hz 1)
F 95000/250000/ 95000/250000/ 95000/250000/ 95000/250000/ 95000/250000/
450000 450000 450000 450000 450000
Power loss, max. 2)
• At 50 Hz 400 V kW 7.13 7.86 9.43 10.5 11.6
• At 60 Hz 460 V kW 7.14 7.87 9.44 11.4 12.5
Cooling air requirement m3/s (ft3/s) 0.64 (22.6) 0.64 (22.6) 0.64 (22.6) 0.64 (22.6) 0.64 (22.6)
Sound pressure level LpA dB 72.5 72.5 72.5 72.5 72.5
(1 m) at 50/60 Hz
Line supply connection 6 x M12 6 x M12 6 x M12 6 x M12 6 x M12
U1, V1, W1
• Conductor cross-section, max. (IEC) mm2 6 × 240 6 × 240 6 × 240 6 × 240 6 × 240
DC link connection 4 × M12 4 × M12 4 × M12 4 × M12 4 × M12
DCP, DCN
• Conductor cross-section, max. (IEC) mm2 Busbar 80 x 8 Busbar 80 x 8 Busbar 80 x 8 Busbar 80 x 8 Busbar 80 x 8
PE connection 6 x M12 6 x M12 6 x M12 6 x M12 6 x M12
• Conductor cross-section, max. (IEC) mm2 6 x 240 6 x 240 6 x 240 6 x 240 6 x 240
Cable length, max. 3) 4) 5)
• Shielded m (ft) 3900 (12795) 3900 (12795) 3900 (12795) 3900 (12795) 3900 (12795)
• Unshielded m (ft) 5850 (19193) 5850 (19193) 5850 (19193) 5850 (19193) 5850 (19193)
Degree of protection IP00 IP00 IP00 IP00 IP00
Dimensions
• Width mm (in) 280 (11.0) 280 (11.0) 280 (11.0) 280 (11.0) 280 (11.0)
• Height mm (in) 1491 (58.7) 1491 (58.7) 1491 (58.7) 1491 (58.7) 1491 (58.7)
• Depth mm (in) 542 (21.3) 542 (21.3) 542 (21.3) 542 (21.3) 542 (21.3)
Weight, approx. kg (lb) 162 (357) 162 (357) 162 (357) 173 (381) 173 (381)
Frame size FS4 FS4 FS4 FS4+ FS4+
Minimum short-circuit current 6) kA 18 20 30 30 30

1) 4)
The maximum DC link capacitances of the drive line-up depend on the The cable lengths are valid for use in IT systems. When used in TN
number of pre-charging resistors (2.2 ) connected in parallel per phase: systems, the cable lengths are shortened to 30 % of the specified value.
1 pre-charging resistor/2 pre-charging resistors/3 pre-charging resistors. 5)
When used in TN systems and during operation of the Active Line Module
2)
The specified power loss represents the maximum value at 100 % in chassis-2 format or the connected Motor Modules with increased pulse
utilization. The value is lower under normal operating conditions. frequency, you can obtain the permitted cable lengths on request.
3) 6)
Total of all motor cables and DC link. Longer cable lengths for specific Minimum current required for reliably triggering the protective devices.
configurations are available on request.
For additional information, please refer to the SINAMICS Low Voltage
Engineering Manual.

4/16 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Chassis-2 Converter Units


Air-cooled units
Active Infeeds > Active Line Modules

■ More information
Use of the Active Line Modules in chassis-2 format in
networks according to the standard IEC 61000-2-4 (2002),
Class 2
When using the Active Line Modules in chassis-2 format in
networks according to the standard IEC 61000-2-4 (2002),
Class 2, the following conditions must be observed:
• Class 2 of IEC 61000-2-4 (2002) is complied with for the
step-up factor set in the factory (= 1.5) and an RSC > 20
and a pulse frequency of 4 kHz.
• With a step-up factor  1.5, the pulse frequency of the
Active Line Module in chassis-2 format must be set to 8 kHz.
When used in TN systems and during operation of the
Active Line Module in chassis-2 format or the connected
Motor Modules with increased pulse frequency, you can
obtain the permitted cable lengths on request.
Use of the Active Line Modules in chassis-2 format in weak
grids 4
When the Active Line Modules in chassis-2 format are used in
weak grids (RSC < 20), the band-stop filter must be activated
(parameter p5200.0 = 1) to suppress increased line harmonic
distortions.
When using Active Line Modules in chassis-2 format in strong
grids (RSC > 20), the band-stop filter should not be activated
(parameter p5200.0 = 0) to avoid unfavorable overshoots.

Siemens D 21.3 · 2022 4/17


© Siemens 2022

SINAMICS S120 Chassis-2 Converter Units


Air-cooled units
Active Infeeds > Active Interface Modules

■ Overview ■ Design
The Active Interface Modules in chassis-2 format feature the
following interfaces as standard:
• 1 line supply connection
• 1 load connection
• 1 connection for the 24 V DC electronics power supply
• 1 connection for the external 230 V AC supply
(fan power supply)
• 1 DRIVE-CLiQ socket (on VSM10 Voltage Sensing Module)
• 1 connection for pre-charging input circuit
• 1 PE/protective conductor connection
The scope of supply of the Active Interface Modules in chassis-2
format includes:
• DRIVE-CLiQ cable for the connection between
Active Interface Module and Active Line Module

4 • DRIVE-CLiQ cable to connect the Control Unit to the first


Motor Module
Active Interface Modules in chassis-2 format are used in • 1 set of warning labels in 30 languages
combination with Active Line Modules in chassis-2 format. (BG, CN, CZ, DE, DK, EE, ES, FI, FR, GB, GR, HU, IE, IS, IT,
The Active Interface Modules in chassis-2 format contain JP, KR, LT, LV, MT, NL, NO, PL, PT, RO, RU, SE, SI, SK, TR)
a Clean Power Filter with basic interference suppression, line
voltage detection, and monitoring sensors.
The pre-charging input circuit that is necessary for operation
must be provided separately. The pre-charge contactor is
activated from the Active Line Module in chassis-2 format.
Line harmonics are largely suppressed by the Clean Power
Filter. Active Line Modules are designed for connection to
grounded TN/TT and non-grounded IT systems.
Pre-charging input circuit
A separate pre-charging input circuit is essential for operating
the Active Line Modules in chassis-2 format. The pre-charging
input circuit components must be ordered separately.
The pre-charging input circuit ensures that there is a current-
limited pre-charging of the DC link capacitors of the Active Line
Module in chassis-2 format and the connected Motor Modules
during the switch-on procedure. After pre-charging has been
completed, the circuit breaker is closed and the pre-charging
input circuit is bridged; the Active Interface Module in chassis-2
format is then directly connected to the supply system.
The pre-charging input circuit comprises a pre-charge
contactor, pre-charging resistors, and a main contactor.
The circuit must be protected against overcurrent using suitable
protection measures. The pre-charging is monitored via
feedback from the contactors to the Active Line Module
in chassis-2 format.
To achieve or to increase the permissible DC link capacitance,
the pre-charging resistors must or can be connected in parallel
in each phase.
The specifications regarding connecting pre-charging resistors
in parallel and the DC link capacitance can be found in the
technical specifications of the Active Line Module in chassis-2
format.

4/18 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Chassis-2 Converter Units


Air-cooled units
Active Infeeds > Active Interface Modules

■ Integration
X500

Active Interface LED

DRIVE-CLiQ socket
-X609 READY
PE
Module Chassis-2
Voltage
1 P24 Sensing
External 2 P24 Module
24 V DC 3 M -G10
4 M
L 5 TxXW
L1
External 6 M
pe 1~ 1 2 X530
230 V AC 7
N
N 8
12 3 5 PE
1) 9
Control
Fan contactor 10

Reserved, do not use


11
12
4
13
Reserved, do not use 14
PE

Main contactor Pre-charging contactor


1) 1) Pre-charging
Fuses resistors

Line
contactor
U1 -X1 -X2 U2
to the
L1
V1 V2
L2 Active Line
W1 W2 Modules
L3
PE PE Chassis-2
PE

1)
Controlled by the Active Line Module Chassis-2
G_D213_EN_00122a

Connection example for Active Interface Module in chassis-2 format

N 230 V 1 AC
Main contactor Pre-charging contactor
-X9
VL1
VL2
NC
Fuses Pre-charging resistors HS1
HS2

Active Line
Line contactor 21 22 Module
Chassis-2
L1
24 V DC
L2

L3
PE
13 14 -X47
Circuit breaker feedback 1 VL_R
2
M
3
G_D213_EN_00128a

HS_R
4 M
5 NC
6 NC

Pre-charging input circuit for Active Line Module in chassis-2 format

Siemens D 21.3 · 2022 4/19


© Siemens 2022

SINAMICS S120 Chassis-2 Converter Units


Air-cooled units
Active Infeeds > Active Interface Modules

■ Technical specifications
Line voltage 380 ... 480 V 3 AC Active Interface Module
6SL3301-7T36-4AA0 6SL3301-7TE41-0AA0 6SL3301-7TE41-4AA0
Suitable for Active Line Module
• Rated power at 400 V kW 355/400 450/500/560/630 710/800/900
- Air-cooled 6SL3331-7TE35-6AA0/ 6SL3331-7TE37-5AA0/ 6SL3331-7TE41-2AA0/
6SL3331-7TE36-4AA0 6SL3331-7TE38-4AA0/ 6SL3331-7TE41-3AA0/
6SL3331-7TE38-8AA0/ 6SL3331-7TE41-4AA0
6SL3331-7TE41-0AA0
Rated current A 560/635 745/840/900/985 710/800/900
Max. pre-charging current (max. 3 s)
• One resistor/phase A 91 91 91
• Two resistors/phase A 182 182 182
• Three resistors/phase A 274 274 274
Current demand
• 24 V DC auxiliary power supply A 0.2 0.2 0.2
• 230 V 2 AC

4 - Inrush current
- Holding current
A
A
0.2
3.1
0.2
3.1
0.2
3.1
Power loss, max. 1)
• At 50 Hz 400 V kW 6.9 9.9 14.5
• At 60 Hz 460 V kW 6.9 9.9 14.5
Cooling air requirement m3/s (ft3/s) 0.61 (21.5) 0.61 (21.5) 0.61 (21.5)
Sound pressure level LpA dB 73.5 73.5 73.5
(1 m) at 50/60 Hz
Line/load connection Busbar 2 x M12 Busbar 2 x M12 Busbar 2 x M12
L1, L2, L3 / U2, V2, W2
• Conductor cross-section, max. (IEC) mm2 Busbar 60 x 8 Busbar 80 x 8 Busbar 80 x 8
PE/GND connection M10 screw M10 screw M10 screw
• Conductor cross-section, max. (IEC) mm2 4 × 240 4 × 240 4 × 240
Degree of protection IP00 IP00 IP00
Dimensions
• Width mm (in) 501 (19.7) 501 (19.7) 501 (19.7)
• Height mm (in) 1676.5 (66.0) 1676.5 (66.0) 1676.5 (66.0)
• Depth mm (in) 533 (21.0) 533 (21.0) 533 (21.0)
Weight, approx. kg (lb) 358 (789) 456 (1005) 548 (1208)
Frame size FS2 FS4 FS4+
Minimum short-circuit current 2) kA 18/18 18/18/18/20 30/30/30

1) The specified power loss represents the maximum value at 100 %


utilization. The value is lower under normal operating conditions.
2) Current required for reliably triggering protective devices.

4/20 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Chassis-2 Converter Units


Air-cooled units
Motor Modules

■ Overview Parallel connection for power increase


The power rating can be increased by connecting Motor
Modules in chassis-2 format in parallel. You must observe the
following rules:
• Up to six identical Motor Modules can be connected in
parallel.
• A common Control Unit is required whenever the modules are
connected in parallel. For more than 4 power units, these must
be distributed as symmetrically as possible between at least
two DRIVE-CLiQ ports (e.g. 3 x 2 Motor Modules in series or
at least 2 x 3 Motor Modules in series).
• The motor supply cables must have the same length
(symmetrical design).
• Power must be supplied to the Motor Modules from a common
DC link.
• A derating factor of 5 % must be taken into consideration,
regardless of the number of modules connected in parallel.
• For motors with multi-winding systems, please observe the
notes in the Low Voltage Engineering Manual. 4
• For motors with a single-winding system, the length of the
A Motor Module comprises a self-commutated inverter with supply lines must be kept to a minimum or motor reactors must
IGBTs. It generates a variable voltage with variable frequency be used. The respective cable lengths are listed in the table
from the DC link voltage that feeds the connected motor. below.
Multiple Motor Modules can be operated on a single DC link.
Motor Module in PN INeff Minimum cable
This permits energy to be transferred between the Motor chassis-2 format length
Modules. This means that if one Motor Module operating in
generator mode produces energy, the energy can be used by 6SL3321-... kW A m
another Motor Module operating in motor mode. 1TE36-6AA0 315 655 13
1TE37-4AA0 355 740 12
Motor Modules are controlled by a Control Unit that is not 1TE38-1AA0 400 810 10
included in the scope of supply.
1TE38-8AA0 450 910 9
DRIVE-CLiQ cables are required to operate a Motor Module. 1TE41-0AA0 500 975 8
1TE41-1AA0 560 1075 8
■ Design 1TE41-2AA0 630 1200 8
1TE41-3AA0 710 1325 8
The Motor Modules in chassis-2 format have the following 1TE41-5AA0 800 1495 8
interfaces as standard:
• 1 motor connection Note:
• 1 connection for the 24 V DC electronics power supply No mixed operation possible!
• 1 DC link connection (DCP, DCN) for connecting to the supply It is only possible to connect identical power units in parallel if all
DC link power units have the same hardware version. Mixed operation
between Motor Modules in chassis format (Article No. 6SL3320-
• 3 DRIVE-CLiQ sockets xxxxx–xAA3) and Motor Modules in chassis-2 format
• 1 temperature sensor input for KTY84-130, Pt1000, PTC or (Article No. 6SL3321-xxxxx–xAA0) is not possible.
Pt100
• 1 connection for Safe Brake Adapter ■ Selection and ordering data
• 1 connection for Safety Integrated
Type rating Rated output current Motor Module
• 2 PE/protective conductor connections at 400 V
The status of the Motor Modules is indicated via three LEDs. kW A Article No.
Line voltage 380 ... 480 V 3 AC
The scope of supply of the Motor Modules includes: (DC link voltage 510 ... 720 V DC)
• PE connection bars 315 655 6SL3321-1TE36-6AA0
• Mounting brackets for mechanical fastening of the chassis 355 740 6SL3321-1TE37-4AA0
400 810 6SL3321-1TE38-1AA0
• Screws for the motor cable connection and PE connection
bars 450 910 6SL3321-1TE38-8AA0
500 975 6SL3321-1TE41-0AA0
• Connector set for customer connection (control cables)
560 1075 6SL3321-1TE41-1AA0
• Shield connection kit (control cables) 630 1200 6SL3321-1TE41-2AA0
• 1 set of warning labels in 30 languages 710 1325 6SL3321-1TE41-3AA0
(BG, CN, CZ, DE, DK, EE, ES, FI, FR, GB, GR, HU, IE, IS, IT, 800 1495 6SL3321-1TE41-5AA0
JP, KR, LT, LV, MT, NL, NO, PL, PT, RO, RU, SE, SI, SK, TR)
Description Article No.
Accessories for re-ordering
Dust protection blanking plugs 6SL3066-4CA00-0AA0
(50 units)
For DRIVE-CLiQ port

For motor-side components, see System components.

Siemens D 21.3 · 2022 4/21


© Siemens 2022

SINAMICS S120 Chassis-2 Converter Units


Air-cooled units
Motor Modules

■ Integration
The Motor Modules communicate with the higher-level control module via DRIVE-CLiQ.
This control module can be:
• A CU320-2 Control Unit
• A SIMOTION D Control Unit

X400 X401 X402

2
DRIVE-CLiQ socket 0

DRIVE-CLiQ socket 1

DRIVE-CLiQ socket
1

DCP
DC link connection
DCN
-X9
1 VL1 =
2 VL2
3 =
NC
4 4
5
HS1
HS2
-X2 PE
U2
1 P24 V =
External V2 M
24 V DC 2 M
~ W2 3~
Internal power
supply
-X51 Fan
Fan power supply terminal L1
L2
L3
PE

-X41
1 EP +24 V
2 EP M1
M
3 +Temp (Motor)
4 -Temp (Motor)
5 NC
6 NC
Motor Module
-X49
1
Chassis-2
LAMPPWR
2 M
3 NC
4 NC
5 NC
6 NC
-X42 READY
LEDs

1 P24L
2 DC LINK
P24L
3 M PWR ON
4 M
-X46
1
BR Output+
2 BR Output-
3 IPD Card
FB Input+
4 FB Input-
5
NC
6 NC
-X47
1 VL_R
2 M
3 HS_R
4 M
5 NC
6 NC

G_D213_EN_00117a

1 The DC link fuses must be provided on the plant/system side.

Connection example for Motor Module in chassis-2 format

4/22 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Chassis-2 Converter Units


Air-cooled units
Motor Modules

■ Technical specifications
General technical specifications
Electrical specifications
Efficiency > 98.5 %
DC link voltage 510 ... 720 V DC (line connection voltage 380 ... 480 V 3 AC)
(up to 2000 m (6562 ft) above sea level)
Output frequency 1)
• Control mode Servo 0 ... 550 Hz
• Control mode Vector 0 ... 550 Hz
• Control mode V/f 0 ... 550 Hz
Safety Integrated Safety Integrity Level 2 (SIL2) acc. to IEC 61508, Performance Level d (PLd) acc. to EN ISO 13849-1 and Control
Category 3 acc. to EN ISO 13849-1

1)
Please note:
• The correlation between the maximum output frequency, pulse frequency
and current derating. Higher output frequencies on request. For more
information, see
https://support.industry.siemens.com/cs/document/104020669
• The correlation between the minimum output frequency and permissible
output current (current derating).
For additional information, please refer to the SINAMICS Low Voltage
Engineering Manual.

Siemens D 21.3 · 2022 4/23


© Siemens 2022

SINAMICS S120 Chassis-2 Converter Units


Air-cooled units
Motor Modules

■ Technical specifications
Line voltage 380 ... 480 V 3 AC Motor Modules
DC link voltage 510 … 720 V DC 6SL3321-1TE36-6AA0 6SL3321-1TE37-4AA0 6SL3321-1TE38-1AA0 6SL3321-1TE38-8AA0
Type rating
• At IL (50 Hz 400 V) 1) kW 315 355 400 450
• At IH (50 Hz 400 V) 1) kW 280 315 355 400
• At IL (60 Hz 460 V) 2) hp 500 600 650 700
• At IH (60 Hz 460 V) 2) hp 450 500 550 650
Output current
• Rated current IN O A 655 740 810 910
• Base-load current IL 3) A 620 700 770 865
• Base-load current IH 4) A 555 620 675 760
• Maximum current Imax O A 917 1036 1134 1274
DC link current
• Rated current IN DC A 785 890 975 1090
Current demand
• 24 V DC auxiliary power supply A 1.3 1.3 1.3 1.3
4 • 400 V AC A 1.8 1.8 1.8 1.8
DC link capacitance F 16450 16450 18800 18800
Pulse frequency 5)
• Rated frequency kHz 2.5 2.5 2.5 2.5
• Pulse frequency, max.
- Without derating kHz 2.5 2.5 2.5 2.5
- With derating kHz 8 8 8 8
Power loss, max. 6)
• At 50 Hz 400 V kW 6.4 6.7 7.4 8.4
• At 60 Hz 460 V kW 6.6 7.0 7.7 8.7
Cooling air requirement m3/s (ft3/s) 0.64 (22.6) 0.64 (22.6) 0.64 (22.6) 0.64 (22.6)
Sound pressure level LpA dB 72.5 72.5 72.5 72.5
(1 m) at 50/60 Hz
DC link connection 2 × hole for M12 2 × hole for M12 2 × hole for M12 2 × hole for M12
DCP, DCN
• Conductor cross-sections, max. mm² Busbar Busbar Busbar Busbar
(IEC)
Motor connection 4 × M12 screw 4 × M12 screw 4 × M12 screw 4 × M12 screw
U2, V2, W2
• Conductor cross-sections, max. mm² 4 × 240 4 × 240 4 × 240 4 × 240
(IEC)
Cable length, max. 7)
• Shielded m (ft) 300 (984) 300 (984) 100 (328) 8) 100 (328) 8)
• Unshielded m (ft) 450 (1476) 450 (1476) 100 (328) 8) 100 (328) 8)
PE/GND connection 4 × M12 screw 4 × M12 screw 4 × M12 screw 4 × M12 screw
• Conductor cross-sections, max. mm² 4 × 240 4 × 240 4 × 240 4 × 240
(IEC)
Degree of protection IP00 IP00 IP00 IP00
Dimensions
• Width mm (in) 280 (11.0) 280 (11.0) 280 (11.0) 280 (11.0)
• Height mm (in) 1248 (49.1) 1248 (49.1) 1248 (49.1) 1248 (49.1)
• Depth mm (in) 542 (21.3) 542 (21.3) 542 (21.3) 542 (21.3)
Weight, approx. kg (lb) 119 (262) 119 (262) 122 (269) 122 (269)
Frame size FS2 FS2 FS2+ FS2+

1) Rated power of a typical 6-pole standard asynchronous motor based on IL 5) Information regarding the correlation between the pulse frequency and
or IH for 400 V 3 AC 50 Hz. maximum output current/output frequency is provided in the SINAMICS
2) Rated power of a typical 6-pole standard asynchronous motor based on IL Low Voltage Engineering Manual.
or IH for 460 V 3 AC 60 Hz. 6) The specified power loss represents the maximum value at 100 %
3) The base-load current for a low overload IL is based on a duty cycle of utilization. The value is lower under normal operating conditions.
110 % for 60 s. 7) When used in the TN system and with infeed via Active Line Module and
4) The base-load current IH for a high overload is based on a duty cycle of when operating the Motor Modules in chassis-2 format with an increased
150 % for 60 s. The value is valid for a pulse frequency of 2 kHz. It is also pulse frequency, you will obtain the permitted motor cable lengths upon
valid for a pulse frequency of 2.5 kHz if p0290 is set = 12. request.
8) Longer cables are available on request.

4/24 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Chassis-2 Converter Units


Air-cooled units
Motor Modules

■ Technical specifications
Line voltage 380 ... 480 V 3 AC Motor Modules
DC link voltage 510 … 720 V DC 6SL3321- 6SL3321- 6SL3321- 6SL3321- 6SL3321-
1TE41-0AA0 1TE41-1AA0 1TE41-2AA0 1TE41-3AA0 1TE41-5AA0
Type rating
• At IL (50 Hz 400 V) 1) kW 500 560 630 710 800
• At IH (50 Hz 400 V) 1) kW 450 500 560 630 710
• At IL (60 Hz 460 V) 2) hp 750 850 950 1050 1200
• At IH (60 Hz 460 V) 2) hp 650 750 850 900 1050
Output current
• Rated current IN O A 975 1075 1200 1325 1495
• Base-load current IL 3) A 910 1000 1145 1260 1420
• Base-load current IH 4) A 800 890 1000 1100 1240
• Maximum current Imax O A 1365 1505 1680 1855 2093
DC link current
• Rated current IN DC A 1170 1290 1440 1590 1795
Current demand
• 24 V DC auxiliary power supply
• 400 V AC
A
A
1.3
1.8
1.3
1.8
1.3
1.8
1.3
1.8
1.3
1.8
4
DC link capacitance F 25900 25900 25900 40800 40800
Pulse frequency 5)
• Rated frequency kHz 2.5 2.5 2.5 2.5 2.5
• Pulse frequency, max.
- Without derating kHz 2.5 2.5 2.5 2.5 2.5
- With derating kHz 8 8 8 8 8
Power loss, max. 6)
• At 50 Hz 400 V kW 8.7 9.5 10.4 12.1 13.7
• At 60 Hz 460 V kW 9.0 9.8 10.8 13.2 14.8
Cooling air requirement m3/s (ft3/s) 0.64 (22.6) 0.64 (22.6) 0.64 (22.6) 0.64 (22.6) 0.64 (22.6)
Sound pressure level LpA dB 72.5 72.5 72.5 72.5 72.5
(1 m) at 50/60 Hz
DC link connection 4 × hole for M12 4 × hole for M12 4 × hole for M12 4 × hole for M12 4 × hole for M12
DCP, DCN
• Conductor cross-sections, max. mm² Busbar Busbar Busbar Busbar Busbar
(IEC)
Motor connection 6 × M12 screw 6 × M12 screw 6 × M12 screw 6 × M12 screw 6 × M12 screw
U2, V2, W2
• Conductor cross-sections, max. mm² 6 × 240 6 × 240 6 × 240 6 × 240 6 × 240
(IEC)
Cable length, max. 7)
• Shielded m (ft) 300 (984) 300 (984) 300 (984) 100 (328) 8) 100 (328) 8)
• Unshielded m (ft) 450 (1476) 450 (1476) 450 (1476) 100 (328) 8) 100 (328) 8)
PE/GND connection 6 × M12 screw 6 × M12 screw 6 × M12 screw 6 × M12 screw 6 × M12 screw
• Conductor cross-sections, max. mm² 6 × 240 6 × 240 6 × 240 6 × 240 6 × 240
(IEC)
Degree of protection IP00 IP00 IP00 IP00 IP00
Dimensions
• Width mm (in) 280 (11.0) 280 (11.0) 280 (11.0) 280 (11.0) 280 (11.0)
• Height mm (in) 1491 (58.7) 1491 (58.7) 1491 (58.7) 1491 (58.7) 1491 (58.7)
• Depth mm (in) 542 (21.3) 542 (21.3) 542 (21.3) 542 (21.3) 542 (21.3)
Weight, approx. kg (lb) 162 (357) 162 (357) 162 (357) 173 (381) 173 (381)
Frame size FS4 FS4 FS4 FS4+ FS4+

1) 5)
Rated power of a typical 6-pole standard asynchronous motor based on IL Information regarding the correlation between the pulse frequency and
or IH for 400 V 3 AC 50 Hz. maximum output current/output frequency is provided in the SINAMICS
2)
Rated power of a typical 6-pole standard asynchronous motor based on IL Low Voltage Engineering Manual.
6)
or IH for 460 V 3 AC 60 Hz. The specified power loss represents the maximum value at 100 %
3)
The base-load current for a low overload IL is based on a duty cycle of utilization. The value is lower under normal operating conditions.
7)
110 % for 60 s. When used in the TN system and with infeed via Active Line Module and
4)
The base-load current IH for a high overload is based on a duty cycle of when operating the Motor Modules in chassis-2 format with an increased
150 % for 60 s. The value is valid for a pulse frequency of 2 kHz. It is also pulse frequency, you will obtain the permitted motor cable lengths upon
valid for a pulse frequency of 2.5 kHz if p0290 is set = 12. request.
8)
Longer cables are available on request.

Siemens D 21.3 · 2022 4/25


© Siemens 2022

SINAMICS S120 Chassis-2 Format Converter Units


Air-cooled units
Mounting aid for Motor Modules/Active Line Modules in chassis-2 format

■ Overview ■ Selection and ordering data


Description Article No.
Mounting aid 6SL3766-1CH02-0AA0
for Motor Module/Active Line Module
in chassis-2 format
G_D213_XX_00151

4
The mounting device is used to install and remove power units
(Active Line Modules, Motor Modules) of the chassis-2 format in
or from a Rittal TS8 or Rittal VX25 control cabinet.
The mounting height resulting from the use of cabinet bases
or cable marshalling space from Rittal is supported.
The mounting device is placed in front of the power unit and
secured to the upper control cabinet profile.
The adjusting tube and guide rails can be used to adjust the
mounting device to the respective control cabinet and
installation height.
After loosening the mechanical and electrical connections, the
power unit is attached to the crossbar and rolled out of the
control cabinet on the guide rails.
The power unit is then lifted with the rope winch and lowered
to the floor after removing the guide rails.

4/26 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Chassis-2 Converter Units


Air-cooled units
OEM kits for control cabinet installation

■ Overview
OEM kits are suitable for easy installation of SINAMICS S120
chassis-2 format built-in units in Rittal VX25 control cabinets
(cabinet height 2000 mm, cabinet depth 600 mm). They also
serve to establish an electrical connection between the built-in
units and to increase the degree of protection of the control
cabinets.
OEM kits are divided into the following main groups:
• Mechanical installation of the power units, including air routing
to avoid air short-circuits inside the control cabinets
• Electrical power connection of the power units to the DC link,
of the individual control cabinets to each other, and
connection of the power cables and motor cables
• Increase the degree of protection of the control cabinets
• Installation ramp
Using OEM kits assists the control cabinet builder in creating
a complete, finished and ready-to-connect drive system with
SINAMICS S120 chassis-2 and Rittal VX25. 4
More information about the OEM kits can be found via the
following link in SIOS. The article numbers of the Rittal VX25
control cabinets for SINAMICS S120 chassis-2 are also listed
there.
https://support.industry.siemens.com/cs/de/en/view/109799904

Siemens D 21.3 · 2022 4/27


© Siemens 2022

SINAMICS S120 Chassis-2 Converter Units


Air-cooled units
OEM kits for control cabinet installation > Mechanical installation kits

■ Overview ■ Integration
The mechanical installation kits make it possible to install
chassis-2 format power units (Active Line Module / Active
Interface Module / Motor Module) in a control cabinet.
They include a base plate for mounting the unit at the bottom of
the control cabinet, a mounting plate for the rear panel, an
exhaust air duct for removing heat from the control cabinet,
as well as the mounting accessories required.
Mechanical installation kits for Motor Modules also include
a PE plate for mounting and earthing shielded motor cables.
The following mechanical installation kits are available:
Power unit in chassis-2 format Cabinet Article No. OEM kit
width in mm
Active Line Module frame sizes 400 6SL3760-4AV22-0CA0
FS2/FS2+
Active Line Module frame sizes 600 6SL3760-6AV42-0CA0
4 FS4/FS4+
Motor Module frame sizes 600 6SL3760-6AV22-0CA0
FS2/FS2+
Motor Module frame sizes 600 6SL3760-6AV42-0CA0
FS4/FS4+
Active Interface Module with 600 6SL3760-6AV22-0AA0
line supply via busbars

G_D213_XX_00132
Active Interface Module with 800 6SL3760-8AV22-0AA0
line supply via cable 1)

The cutouts in the top plate required to connect the exhaust air
duct can be made by the customer. Ready-prepared cabinets
can also be obtained from Rittal.

■ Selection and ordering data Mechanical installation kit for Active Line Modules and Motor Modules in
chassis-2 format
Designation of OEM kit Article No.
Mechanical installation kit for Active Line 6SL3760-4AV22-0CA0
Modules FS2/FS2+, cabinet width of 400 mm
Mechanical installation kit for Motor Modules 6SL3760-6AV22-0CA0
FS2/FS2+, cabinet width of 600 mm
Mechanical installation kit for Motor Modules 6SL3760-6AV42-0CA0
and Active Line Modules FS4/FS4+, cabinet
width of 600 mm
Mechanical installation kit for Active Interface 6SL3760-6AV22-0AA0
Modules FS2-FS4+, cabinet width of 600 mm
Mechanical installation kit for Active Interface 6SL3760-8AV22-0AA0
Modules FS2-FS4+ for line connection kit,
cabinet width of 800 mm
G_D213_XX_00144

Mechanical installation kit for Active Interface Modules in chassis-2


format

1)
The line connection kit for Active Interface Modules
(6SL3760-6BV00-0EC0) is also recommended.

4/28 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Chassis-2 Converter Units


Air-cooled units
OEM kits for control cabinet installation > DC busbar basic kits

■ Overview ■ Integration
DC busbar basic kits are used to set up a cross-cabinet DC
power supply in the upper area of the control cabinet.
DC busbar basic kits are available for various current ratings
and cabinet widths. The kits build on each other and must be
ordered separately.
• DC busbar basic kit for a current rating of 1840 A

G_D213_XX_00142
- It includes, among other things, a mounting plate, a busbar
bracket and one DC busbar each for DCP and DCN.
• DC busbar basic kit for increasing to a current rating of 3320 A
- It contains, among other things, a second DC busbar each
for DCP and DCN.
- The DC busbar basic kit, 1840 A must be ordered DC busbar basic kit for current rating of 1840 A
separately.
• DC busbar basic kit for increasing to a current rating of 4480 A
- It contains, among other things, a third DC busbar each for
DCP and DCN.
- The DC busbar basic kits, 1840 A and 3320 A must be
ordered separately. 4

G_D213_XX_00141
Each DC busbar basic kit also includes two connecting bridges
for connecting the DC busbars from two control cabinets as well
as the necessary mounting accessories.
The following DC busbar basic kits are available:
Cabinet width in mm Current rating in A Article No. OEM kit DC busbar basic kit for current rating of 4480 A
400 1840 6SL3760-4BV00-1DB0
400 3320 6SL3760-4BV00-3DB0
400 4480 6SL3760-4BV00-7DB0
600 1840 6SL3760-6BV00-1DB0
600 3320 6SL3760-6BV00-3DB0
600 4480 6SL3760-6BV00-7DB0
800 1840 6SL3760-8BV00-1DB0
800 3320 6SL3760-8BV00-3DB0
800 4480 6SL3760-8BV00-7DB0

■ Selection and ordering data


Designation of OEM kit Article No.
DC busbar basic kit - 1840 A for cabinet 6SL3760-4BV00-1DB0
width of 400 mm
DC busbar basic kit - 3320 A for cabinet 6SL3760-4BV00-3DB0
width of 400 mm
DC busbar basic kit - 4480 A for cabinet 6SL3760-4BV00-7DB0
width of 400 mm
DC busbar basic kit - 1840 A for cabinet 6SL3760-6BV00-1DB0
width of 600 mm
DC busbar basic kit - 3320 A for cabinet 6SL3760-6BV00-3DB0
width of 600 mm
DC busbar basic kit - 4480 A for cabinet 6SL3760-6BV00-7DB0
width of 600 mm
DC busbar basic kit - 1840 A for cabinet 6SL3760-8BV00-1DB0
width of 800 mm
DC busbar basic kit - 3320 A for cabinet 6SL3760-8BV00-3DB0
width of 800 mm
DC busbar basic kit - 4480 A for cabinet 6SL3760-8BV00-7DB0
width of 800 mm

Siemens D 21.3 · 2022 4/29


© Siemens 2022

SINAMICS S120 Chassis-2 Converter Units


Air-cooled units
OEM kits for control cabinet installation > DC busbar fuse kits

■ Overview ■ Integration
DC busbar fuse kits are used to connect between a DC power
supply in the upper part of the control cabinet and an Active Line
Module or Motor Module. The busbar set includes a mounting
space for installing the DC fuses provided as well as the
necessary mounting accessories.
The DC fuses required for fuse protection are not included in the
scope of delivery.
The following DC busbar fuse kits are available:
Power unit in chassis-2 format Article No. OEM kit
Active Line Module/Motor Module frame 6SL3760-6BV20-0DF0
sizes FS2/FS2+
Active Line Module/Motor Module frame 6SL3760-6BV40-0DF0
sizes FS4/FS4+

Prerequisite for DC busbar fuse kit:


• Mechanical installation kit for Active Line Module or Motor
4 Module
• DC busbar kit (depending on current rating and cabinet width)

G_D213_XX_00130
■ Selection and ordering data
Designation of OEM kit Article No.
DC busbar fuse kit FS2/FS2+ 6SL3760-6BV20-0DF0
DC busbar fuse kit FS4/FS4+ 6SL3760-6BV40-0DF0

DC busbar fuse kit with DC fuses

4/30 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Chassis-2 Converter Units


Air-cooled units
OEM kits for control cabinet installation > Busbar connection kits

■ Overview ■ Integration
The busbar connection kits make it possible to connect
an Active Interface Module and an Active Line Module in
chassis-2 format in the control cabinet using prefabricated
busbar sets.
The busbar connection kits include a busbar set arranged
centrally and a set of connecting bars to the Active Interface
Module and to the Active Line Module as well as mounting
accessories required. Busbar connection kits are available for
various arrangements of Active Line Modules and
Active Interface Modules.
The following busbar connection kits are available:
Arrangement Frame size Article No. OEM kit
for Active
Line Module
in chassis-2
format
Active Interface Module to the FS2/FS2+
right of the Active Line Module
6SL3760-6BV22-0AE0
4
Active Interface Module to the FS2/FS2+ 6SL3760-6BV22-0EA0
left of the Active Line Module
Active Interface Module to the FS4/FS4+ 6SL3760-6BV42-0AE0
right of the Active Line Module
Active Interface Module to the FS4/FS4+ 6SL3760-6BV42-0EA0

G_D213_XX_00138
left of the Active Line Module

Prerequisites for installing a busbar connection kit:


• Mechanical installation kit for Active Line Module
• Mechanical installation kit for Active Interface Module

■ Selection and ordering data


Busbar connection kit for arranging Active Interface Module to the left of
Designation of OEM kit Article No. the Active Line Module
Busbar connection kit for 6SL3760-6BV22-0AE0
Active Line Modules FS2/FS2+,
AIM to the right, cabinet width of 600 mm
Busbar connection kit for 6SL3760-6BV22-0EA0
Active Line Modules FS2/FS2+,
AIM to the left, cabinet width of 600 mm
Busbar connection kit for 6SL3760-6BV42-0AE0
Active Line Modules FS4/FS4+,
AIM to the right, cabinet width of 600 mm
Busbar connection kit for 6SL3760-6BV42-0EA0
Active Line Modules FS4/FS4+,
AIM to the left, cabinet width of 600 mm
G_D213_XX_00135

Busbar connection kit for arranging Active Interface Module to the right
of the Active Line Module

Siemens D 21.3 · 2022 4/31


© Siemens 2022

SINAMICS S120 Chassis-2 Converter Units


Air-cooled units
OEM kits for control cabinet installation > Line connection kit for Active Interface Modules

■ Overview ■ Integration
The line connection on the Active Interface Module is designed
for busbars as standard. The line connection kits for Active
Interface Modules make it possible to connect an Active
Interface Module using power cables. The power cables can be
fed either vertically from below through the control cabinet or
from an adjacent cabinet and to the Active Interface Module
from the right or left side.
The line connection kits for Active Interface Modules include
a set of connection bars, fastening plates, a PE plate for
mounting and earthing shielded power cables, as well as the
necessary mounting accessories.
Note:
When using power cables to connect the Active Interface
Module, it is recommended to install it in a control cabinet with
a width of 800 mm.
The following line connection kit for Active Interface Modules is
4 available:
Power unit in chassis-2 format Article No. OEM kit
Active Interface Module 6SL3760-6BV00-0EC0

Prerequisite for line connection kit for Active Interface Modules:


• Mechanical installation kit for Active Interface Module

G_D213_XX_00136
■ Selection and ordering data
Designation of OEM kit Article No.
Line connection kit for Active Interface 6SL3760-6BV00-0EC0
Modules

Line connection kit for Active Interface Modules

4/32 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Chassis-2 Converter Units


Air-cooled units
OEM kits for control cabinet installation > Motor connection kits

■ Overview ■ Integration
The Motor Modules are designed for connecting the motor
cables directly. The motor connection kits make it possible to
easily connect the motor cables to a separate connection panel.
This makes it simple to remove the Motor Module, facilitating
rapid maintenance.
The motor connection kits include a connection panel for
supporting the motor cables, a set of connecting bars to the
Motor Module as well as the necessary mounting accessories.
The following motor connection kits are available:
Power unit in chassis-2 format Article No. OEM kit
Motor Module frame sizes FS2/FS2+ 6SL3760-6BV20-0MC0
Motor Module frame sizes FS4/FS4+ 6SL3760-6BV40-0MC0

Prerequisite for motor connection kit:


• Mechanical installation kit for Motor Module

■ Selection and ordering data


4
Designation of OEM kit Article No.
Motor connection kit for Motor Module 6SL3760-6BV20-0MC0
FS2/FS2+
Motor connection kit for Motor Module 6SL3760-6BV40-0MC0

G_D213_XX_00133
FS4/FS4+

Motor connection kit

Siemens D 21.3 · 2022 4/33


© Siemens 2022

SINAMICS S120 Chassis-2 Converter Units


Air-cooled units
OEM kits for control cabinet installation > Protection kits

■ Overview The following Rittal filter inserts must be ordered separately:


Cabinet Achievable degree of Quantity Rit- Rittal Article No.
The protection kits make it possible to set up a control cabinet width in protection tal filter
with one of the following degrees of protection: mm inserts
• The protection kit - Standard enables installation in the 400 Standard (IP20), Medium 5 SK 3240.200
IP20 degree of protection. (IP21)
It includes a ventilation grille for the top plate. 400 High (IP43/IP54) 7 SK 3240.200
• The protection kit - Medium enables installation in the 600 Standard (IP20), Medium 4 SK 3243.200
IP21 degree of protection. (IP21)
It includes a ventilation grille for the top plate, a drip shield with
600 High (IP43/IP54) 4 SK 3240.200
spacers and an air baffle.
4 SK 3243.200
• The protection kit - High enables installation in the
IP43/IP54 degree of protection. 800 Standard (IP20), Medium 8 SK 3240.200
It includes a top hood with an integrated air baffle. (IP21)
800 High (IP43/IP54) 12 SK 3240.200
The Rittal filter inserts required for the air inlet and air outlet are
not included in the scope of delivery. The cut-outs in the top plate required to use the ventilation grilles
The following protection kits are available: can be made by the customer; ready-prepared cabinets can
also be obtained from Rittal.
4 Power unit in chassis-2 format Cabinet
width in
Achievable
degree of
Article No. OEM
kit
The cut-outs in the cabinet doors required to use the filter inserts
mm protection can be made by the customer; ready-prepared cabinet doors
can also be obtained from Rittal.
Active Line Module 400 Standard 6SL3760-
frame sizes FS2/FS2+ (IP20) 4CV00-0DA0
Active Line Module 400 Medium 6SL3760- ■ Selection and ordering data
frame sizes FS2/FS2+ (IP21) 4CV00-0FA0
Designation of OEM kit Article No.
Active Line Module 400 High 6SL3760-
frame sizes FS2/FS2+ (IP43/IP54) 4CV00-0JA0 Protection kit - Standard for cabinet 6SL3760-4CV00-0DA0
width of 400 mm
Active Line Module 600 Standard 6SL3760-
frame sizes FS4/FS4+ (IP20) 4CV00-0DA0 Protection kit - Medium for cabinet 6SL3760-4CV00-0FA0
width of 400 mm
Motor Module
frame sizes Protection kit - High for cabinet 6SL3760-4CV00-0JA0
FS2/FS2+/FS4/FS4+ width of 400 mm
Active Line Module 600 Medium 6SL3760- Protection kit - Standard for cabinet 6SL3760-4CV00-0DA0
frame sizes FS4/FS4+ (IP21) 6CV00-0FA0 width of 600 mm
Motor Module Protection kit - Medium for cabinet 6SL3760-6CV00-0FA0
frame sizes width of 600 mm
FS2/FS2+/FS4/FS4+
Protection kit - High for cabinet 6SL3760-6CV00-0JA0
Active Line Module 600 High 6SL3760- width of 600 mm
frame sizes FS4/FS4+ (IP43/IP54) 6CV00-0JA0
Protection kit Active Interface Modules 6SL3760-8CV00-0DA0
Motor Module
FS2/FS4/FS4+ - Standard for cabinet
frame sizes
widths of 600 mm/800 mm
FS2/FS2+/FS4/FS4+
Active Interface Module Protection kit - Medium for cabinet 6SL3760-8CV00-0FA0
frame sizes FS2/FS4/FS4+ width of 800 mm

Active Interface Module 600/800 Standard 6SL3760- Protection kit - High for cabinet 6SL3760-8CV00-0JA0
frame sizes FS2/FS4/FS4+ 1)
(IP20) 8CV00-0DA0 width of 800 mm

Active Interface Module 800 1) Medium 6SL3760-


frame sizes FS2/FS4/FS4+ (IP21) 8CV00-0FA0
Active Interface Module 800 1) High 6SL3760-
frame sizes FS2/FS4/FS4+ (IP43/IP54) 8CV00-0JA0

1)
A cabinet width of 800 mm is only required for an Active Interface Module
if the line connection kit for Active Interface Modules
(6SL3760-6BV00-0EC0) is also to be used.

4/34 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Chassis-2 Converter Units


Air-cooled units
OEM kits for control cabinet installation > Protection kits

■ Integration

4
G_D213_XX_00143

G_D213_XX_00140
Protection kit - Standard and Rittal filter inserts for control cabinet Protection kit - Medium and Rittal filter inserts for control cabinet
with cabinet width of 600 mm with cabinet width of 600 mm

G_D213_XX_00139

Protection kit - High and Rittal filter inserts for control cabinet with cabinet
width of 600 mm

Siemens D 21.3 · 2022 4/35


© Siemens 2022

SINAMICS S120 Chassis-2 Converter Units


Air-cooled units
OEM kits for control cabinet installation > Installation ramp kit

■ Overview ■ Integration
The installation ramp kit is used to install or remove an Active
Line Module or Motor Module in chassis-2 format from the
control cabinet.

G_D213_XX_00134
The installation ramp kit includes a ramp that attaches to the
base plate of mechanical installation kit.
Prerequisite for installation ramp kit:
• Mechanical installation kit for Active Line Modules or
• Mechanical installation kit for Motor Modules

■ Selection and ordering data


Designation of OEM kit Article No.
Installation ramp kit for Active Line Modules 6SL3760-6CR22-0CA0
and Motor Modules in chassis-2 format
Control cabinet with installation ramp
4

4/36 Siemens D 21.3 · 2022


5
© Siemens 2022

System Components for SINAMICS S120


Converter Built-in Chassis and Chassis-2 Format Units

5/2 System components


5/3 Line-side power components
5/3 Line filters
5/7 Line reactors
5/12 Recommended line-side
system components
5/21 DC link components
5/21 Braking Modules
5/24 Braking resistors
5/26 DC link fuses
5/29 Motor-side power components
5/29 Motor reactors
5/34 dv/dt filter plus VPL
5/40 dv/dt filter compact plus VPL
5/46 Sine-wave filter
5/48 Control Units
5/51 CU320-2 Control Unit
5/55 CompactFlash card for CU320-2
5/57 CU310-2 Control Unit
5/61 CompactFlash card for CU310-2
5/62 Supplementary system components
5/62 BOP20 Basic Operator Panel
5/63 AOP30 Advanced Operator Panel
5/65 CBE20 Communication Board
5/66 DMC20 DRIVE-CLiQ Hub Module
5/68 DME20 DRIVE-CLiQ Hub Module
5/70 TB30 Terminal Board
5/72 TM15 Terminal Module
5/74 TM31 Terminal Module
5/77 TM41 Terminal Module
5/80 TM54F Terminal Module
5/83 TM120 Terminal Module
5/85 TM150 Terminal Module
5/87 VSM10 Voltage Sensing Module
5/89 SBA Safe Brake Adapter
5/91 Encoder system connection
5/92 SMC10 Sensor Module Cabinet-Mounted
5/93 SMC20 Sensor Module Cabinet-Mounted
5/94 SMC30 Sensor Module Cabinet-Mounted
5/95 Connection system
5/95 Signal cables

Siemens D 21.3 · 2022


© Siemens 2022

System components for SINAMICS S120 Chassis and Chassis-2 Units


System components

■ Technical specifications
General technical specifications
Unless clearly specified otherwise, the following technical data are valid for all the following system components of the air-cooled
and liquid-cooled SINAMICS S120 drive system in chassis and chassis-2 format.
Electrical specifications
Line voltages 380 ... 480 V 3 AC ±10 % (-15 % <1 min)
500 ... 690 V 3 AC ±10 % (-15 % <1 min)
Line supply types Grounded TN/TT systems and non-grounded IT systems
Line frequency 47 ... 63 Hz
Overvoltage category III acc. to EN 61800-5-1
Electronics power supply 24 V DC, -15 % +20 %
implemented as PELV circuit in accordance with EN 61800-5-1
Ground = negative pole grounded via the electronics
Mechanical specifications
Degree of protection IP00 or IP20 depending on type
Protection class I acc. to EN 61800-5-1
Touch protection EN 50274/DGUV regulation 3 when used as intended
Ambient conditions Storage 1) Transport 1) Operation
Ambient temperature -25 ... +55 °C (-13 ... 131 °F) -25 ... +70 °C (-13 ... +158 °F) Line-side components:
Class 1K4 Class 2K4 0 … 40 °C (32 ... 104 °F) without

5 acc. to EN 60721-3-1 (1997) acc. to EN 60721-3-2 (1997) derating


Up to 55 °C (131 °F), see derating
data
Control Units, supplementary system
components, and Sensor Modules:
0 ... 55 °C (32 ... 131 °F)
(for operation in a control cabinet)
DC link components and motor-side
components:
0 ... 55 °C (32 ... 131 °F)
Relative humidity 5 ... 95 % 5 ... 95 % at 40 °C (104 °F) 5 ... 95 %
Condensation, splashwater, and ice Class 1K4 Class 2K4 Class 3K3
formation not permitted (EN 60204, acc. to EN 60721-3-1 (1997) acc. to EN 60721-3-2 (1997) acc. to EN 60721-3-3 (2002)
Part 1)
Environmental class/harmful chemi- Class 1C2 Class 2C2 Class 3C2
cal substances acc. to EN 60721-3-1 (1997) acc. to EN 60721-3-2 (1997) acc. to EN 60721-3-3 (2002)
Organic/biological influences Class 1B1 Class 2B1 Class 3B1
acc. to EN 60721-3-1 (1997) acc. to EN 60721-3-2 (1997) acc. to EN 60721-3-3 (2002)
Degree of pollution 2 acc. to IEC/EN 61800-5-1 2 acc. to IEC/EN 61800-5-1 2 acc. to IEC/EN 61800-5-1
Installation altitude Up to 2000 m (6562 ft) above sea level without derating
>2000 m (6562 ft) above sea level, see derating data
Mechanical stability Storage 1) Transport 1) Operation
Vibratory load – Class 2M2 Test values
acc. to EN 60721-3-2 (1997) acc. to EN 60068-2-6 test Fc:
• 10 ... 58 Hz with constant deflection
0.075 mm
• 58 ... 150 Hz with constant
acceleration 9.81 m/s2 (1 × g)
Shock load – Class 2M2 Test values
acc. to EN 60721-3-2 (1997) according to EN 60068-2-27 test
Ea: 98 m/s2 (10 × g)/20 ms
Compliance with standards
Conformances/certificates of suit- CE (EMC Directive 2014/30/EU, Low Voltage Directive 2014/35/EU, Machinery Directive 2006/42/EC for
ability, according to functional safety)
cURus or cULus (only for devices connected to line supply voltages 380 ... 480 V 3 AC and 500 ... 600 V 3 AC)
Radio interference suppression SINAMICS S120 chassis format units are not designed for connection to the public grid (first environment). Radio
interference suppression is compliant with the EMC product standard for variable-speed drives EN 61800-3,
"second environment" (industrial line supplies). EMC disturbances can occur when connected to the public grid.
However, if additional measures are taken (e.g.  line filter), it can also be operated in the "first environment".
For further information, see section Engineering information.

Deviations from the specified class are underlined.

1)
In transport packaging.

5/2 Siemens D 21.3 · 2022


© Siemens 2022

System components for SINAMICS S120 Chassis and Chassis-2 Units


System components
Line-side power components > Line filters

■ Overview
In conjunction with line reactors and a logically consistent
configuration of the plant or system, line filters limit the
interference conducted by the Line Modules and Power
Modules to the limit values of Category C2 acc. to EN 61800-3.
The line filters are suitable for TN and TT supply systems
grounded at the neutral point.

■ Selection and ordering data


Line filters for Power Modules
Suitable for Power Module in chassis
format,
air-cooled
Type rating of the Power Modules
at 400 V
Rated input current of the Power Module Line filter
5
6SL3310-... kW A Article No.
Line voltage 380 ... 480 V 3 AC
1TE32-1AA3 110 229 6SL3000-0BE32-5AA0
1TE32-6AA3 132 284 6SL3000-0BE34-4AA0
1TE33-1AA3 160 338
1TE33-8AA3 200 395
1TE35-0AA3 250 509 6SL3000-0BE36-0AA0

Line filters for Basic Line Modules


Suitable for Basic Line Module in chassis Rated power of the Basic Line Module Rated input current of the Basic Line Line filter
format, air-cooled at 400 V or 690 V Module
6SL3330-... kW A Article No.
Line voltage 380 ... 480 V 3 AC
1TE34-2AA3 200 365 6SL3000-0BE34-4AA0
1TE35-3AA3 250 460 6SL3000-0BE36-0AA0
1TE38-2AA3 400 710 6SL3000-0BE41-2AA0
1TE41-2AA3 560 1010
1TE41-5AA3 710 1265 6SL3000-0BE41-6AA0
1TE41-8AA3 900 1581
Line voltage 500 ... 690 V 3 AC
1TG33-0AA3 250 260 6SL3000-0BG34-4AA0
1TG34-3AA3 355 375
1TG36-8AA3 560 575 6SL3000-0BG36-0AA0
1TG41-1AA3 900 925 6SL3000-0BG41-2AA0
1TG41-4AA3 1100 1180
7TG41-8AA3 1500 1580 6SL3000-0BG41-6AA0

Siemens D 21.3 · 2022 5/3


© Siemens 2022

System components for SINAMICS S120 Chassis and Chassis-2 Units


System components
Line-side power components > Line filters

■ Selection and ordering data


Line filters for Smart Line Modules
Suitable for Smart Line Module Rated power of Rated input current of Line filter
in chassis format, air-cooled the Smart Line Module at 400 V or 690 V the Smart Line Module
6SL3330-... kW A Article No.
Line voltage 380 ... 480 V 3 AC
6TE35-5AA3 250 463 6SL3000-0BE35-0AA0
6TE37-3AA3 355 614 6SL3760-0MB00-0AA0
6TE41-1AA3 500 883 6SL3760-0MC00-0AA0
6TE41-3AA3 630 1093
6TE41-7AA3 800 1430
Line voltage 500 ... 690 V 3 AC
6TG35-5AA3 450 463 6SL3760-0ME00-0AA0
6TG38-8AA3 710 757 6SL3760-0MN00-0AA0
6TG41-2AA3 1000 1009
6TG41-7AA3 1400 1430 6SL3760-0MG00-0AA0

Line filters for Active Line Modules


Suitable for Active Line Module Rated power of Rated input current of Line filter
in chassis format, air-cooled the Active Line Module at 400 V or 690 V the Active Line Module
5 6SL3330-... kW A Article No.
Line voltage 380 ... 480 V 3 AC
7TE32-1AA3 132 210 6SL3000-0BE33-1AA0
7TE32-6AA3 160 260
7TE33-8AA3 235 380 6SL3000-0BE35-0AA0
7TE35-0AA3 300 490
7TE36-1AA3 380 605 6SL3760-0MB00-0AA0
7TE37-5AA3 450 745
7TE38-4AA3 500 840 6SL3760-0MC00-0AA0
7TE41-0AA3 630 985
7TE41-2AA3 800 1260
7TE41-4AA3 900 1405
Line voltage 500 ... 690 V 3 AC
7TG35-8AA3 630 575 6SL3760-0ME00-0AA0
7TG37-4AA3 800 735 6SL3760-0MN00-0AA0
7TG41-0AA3 1100 1025
7TG41-3AA3 1400 1270 6SL3760-0MG00-0AA0

Note:
Line filters are not available for liquid-cooled Line Modules.

5/4 Siemens D 21.3 · 2022


© Siemens 2022

System components for SINAMICS S120 Chassis and Chassis-2 Units


System components
Line-side power components > Line filters

■ Technical specifications
Line voltage 380 ... 480 V 3 AC Line filter
6SL3000- 6SL3000- 6SL3000- 6SL3000- 6SL3000-
0BE32-5AA0 0BE34-4AA0 0BE36-0AA0 0BE41-2AA0 0BE41-6AA0
Rated current A 250 440 600 1200 1600
1)
Power loss kW 0.015 0.047 0.053 0.119 0.153
At 50 Hz
Load/line supply connection 1 × hole for M10 1 × hole for M10 1 × hole for M10 1 × hole for M12 1 × hole for M12
Provided for busbar Provided for busbar Provided for busbar Provided for busbar Provided for busbar
connection connection connection connection connection
PE connection Hole for M8 Hole for M8 Hole for M10 Hole for M10 Hole for M10
Degree of protection IP00 IP00 IP00 IP00 IP00
Dimensions
• Width mm (in) 360 (14.2) 360 (14.2) 400 (15.7) 425 (16.7) 505 (19.9)
• Height mm (in) 240 (9.45) 240 (9.45) 265 (10.4) 265 (10.4) 265 (10.4)
• Depth mm (in) 116 (4.57) 116 (4.57) 140 (5.51) 145 (5.71) 145 (5.71)
Weight, approx. kg (lb) 12.3 (27.1) 12.3 (27.1) 19 (41.9) 25.8 (56.9) 28.8 (63.5)
Suitable for Power Module in chassis format
• Air-cooled 6SL3310- 1TE32-1AA3 1TE32-6AA3 1TE35-0AA3 – –
1TE33-1AA3
1TE33-8AA3
Suitable for Basic Line Module in chassis format
• Air-cooled 6SL3330- – 1TE34-2AA3 1TE35-3AA3 1TE38-2AA3 1TE41-5AA3
5
1TE41-2AA3 1TE41-8AA3

Line voltage 500 ... 690 V 3 AC Line filter


6SL3000-0BG34-4AA0 6SL3000-0BG36-0AA0 6SL3000-0BG41-2AA0 6SL3000-0BG41-6AA0
Rated current A 440 600 1200 1600
Power loss 1) kW 0.047 0.053 0.119 0.153
At 50 Hz
Load/line supply connection 1 × hole for M10 1 × hole for M10 2 × hole for M12 2 × hole for M12
Provided for busbar Provided for busbar con- Provided for busbar Provided for busbar
connection nection connection connection
PE connection Hole for M8 Hole for M10 Hole for M10 Hole for M10
Degree of protection IP00 IP00 IP00 IP00
Dimensions
• Width mm (in) 360 (14.2) 400 (15.7) 425 (16.7) 505 (19.9)
• Height mm (in) 240 (9.45) 265 (10.4) 265 (10.4) 265 (10.4)
• Depth mm (in) 116 (4.57) 140 (5.51) 145 (5.71) 145 (5.71)
Weight, approx. kg (lb) 12.3 (27.1) 19 (41.9) 25.2 (55.6) 28.8 (63.5)
Suitable for Basic Line Module in chassis format
• Air-cooled 6SL3330- 1TG33-0AA3 1TG36-8AA3 1TG41-1AA3 1TG41-8AA3
1TG34-3AA3 1TG41-4AA3

1)
The specified power loss represents the maximum value at 100 %
utilization. The value is lower under normal operating conditions.

Siemens D 21.3 · 2022 5/5


© Siemens 2022

System components for SINAMICS S120 Chassis and Chassis-2 Units


System components
Line-side power components > Line filters

■ Technical specifications
Line voltage 380 ... 480 V 3 AC Line filter
6SL3000-0BE33-1AA0 6SL3000-0BE35-0AA0 6SL3760-0MB00-0AA0 6SL3760-0MC00-0AA0
Rated current A 400 600 840 1405
Power loss 1) kW 0.042 0.06 0.058 0.111
At 50 Hz
Load/line supply connection M10 connecting lugs M10 connecting lugs M10 connecting lugs M10 connecting lugs
PE connection Hole for M8 Hole for M10 Hole for M10 Hole for M10
Degree of protection IP00 IP00 IP00 IP00
Dimensions
• Width mm (in) 360 (14.2) 390 (15.4) 425 (16.7) 505 (19.9)
• Height mm (in) 240 (9.45) 265 (10.4) 265 (10.4) 265 (10.4)
• Depth mm (in) 116 (4.57) 140 (5.51) 145 (5.71) 145 (5.71)
Weight, approx. kg (lb) 12.7 (28.0) 19.9 (43.9) 25.9 (57.1) 28.9 (63.7)
Suitable for Smart Line Module in chassis format
• Air-cooled 6SL3330- – 6TE35-5AA3 6TE37-3AA3 6TE41-1AA3
6TE41-3AA3
6TE41-7AA3
Suitable for Active Line Module in chassis format
• Air-cooled 6SL3330- 7TE32-1AA3 7TE33-8AA3 7TE36-1AA3 7TE38-4AA3

5 7TE32-6AA3 7TE35-0AA3 7TE37-5AA3 7TE41-0AA3


7TE41-2AA3
7TE41-4AA3

Line voltage 500 ... 690 V 3 AC Line filter


6SL3760-0ME00-0AA0 6SL3760-0MN00-0AA0 6SL3760-0MG00-0AA0
Rated current A 600 1025 1270
Power loss 1) kW 0.063 0.063 0.097
At 50 Hz
Load/line supply connection M10 connecting lugs M12 connecting lugs M12 connecting lugs
PE connection Hole for M10 Hole for M10 Hole for M10
Degree of protection IP00 IP00 IP00
Dimensions
• Width mm (in) 400 (15.7) 425 (16.7) 505 (19.9)
• Height mm (in) 365 (14.4) 365 (14.4) 365 (14.4)
• Depth mm (in) 140 (5.51) 145 (5.71) 145 (5.71)
Weight, approx. kg (lb) 27 (59.5) 36.7 (80.9) 36.7 (80.9)
Suitable for Smart Line Module in chassis format
• Air-cooled 6SL3330- 6TG35-5AA3 6TG38-8AA3 6TG41-7AA3
6TG41-2AA3
Suitable for Active Line Module in chassis format
• Air-cooled 6SL3330- 7TG35-8AA3 7TG37-4AA3 7TG41-3AA3
7TG41-0AA3

1) The specified power loss represents the maximum value at 100 %


utilization. The value is lower under normal operating conditions.

5/6 Siemens D 21.3 · 2022


© Siemens 2022

System components for SINAMICS S120 Chassis and Chassis-2 Units


System components
Line-side power components > Line reactors

■ Overview
With a high line short-circuit power (i.e. low line supply cable
inductance) a line reactor is required in order to
• protect the converter itself from excessively high harmonic
currents and therefore overload
• limit the harmonics to permissible values. The harmonic
currents are limited by the complete inductance comprising
the line reactor and line supply cable inductance.
For additional information, please refer to the SINAMICS Low
Voltage Engineering Manual.

■ Selection and ordering data


Line reactors for Power Modules
Suitable for Power Module
in chassis format,
air-cooled
Suitable for Power Module
in chassis format,
liquid/water-cooled
Type rating of the Power
Modules
at 400 V
Rated input current of the
Power Module
Line reactor
5
6SL3310-... 6SL3315-... kW A Article No.
Line voltage 380 ... 480 V 3 AC
1TE32-1AA3 1TE32-1AA3 110 229/230 6SL3000-0CE32-3AA0
1TE32-6AA3 1TE32-6AA3 132 284/285 6SL3000-0CE32-8AA0
1TE33-1AA3 1TE33-1AA3 160 338/340 6SL3000-0CE33-3AA0
1TE33-8AA3 – 200 395 6SL3000-0CE35-1AA0
1TE35-0AA3 1TE35-0AA3 250 509/540

Siemens D 21.3 · 2022 5/7


© Siemens 2022

System components for SINAMICS S120 Chassis and Chassis-2 Units


System components
Line-side power components > Line reactors

■ Selection and ordering data


Line reactors for Basic Line Modules
Suitable for Suitable for Rated power of the Rated input current of the Line reactor
Basic Line Module in chassis Basic Line Module Basic Line Module Basic Line Module
format, in chassis format, at 400 V or 690 V
air-cooled liquid-cooled
6SL3330-... 6SL3335-... kW A Article No.
Line voltage 380 ... 480 V 3 AC
1TE34-2AA3 – 200 365 6SL3000-0CE35-1AA0
1TE35-3AA3 – 250 460
– 1TE37-4AA3 360 610 6SL3000-0CE36-3AA0
1TE38-2AA3 – 400 710 6SL3000-0CE37-7AA0
1TE41-2AA3 – 560 1010 6SL3000-0CE41-0AA0
– 1TE41-2AA3 600 1000
1TE41-5AA3 – 710 1265 6SL3000-0CE41-5AA0
– 1TE41-7AA3 830 1420
1TE41-8AA3 – 900 1581 6SL3000-0CE41-6AA0
Line voltage 500 … 690 V 3 AC
1TG33-0AA3 – 250 260 6SL3000-0CH32-7AA0
– 1TG34-2AA3 355 340 6SL3000-0CH33-4AA0
5 1TG34-3AA3 – 355 375 6SL3000-0CH34-8AA0
1TG36-8AA3 – 560 575 6SL3000-0CH36-0AA0
– 1TG37-3AA3 630 600
1TG41-1AA3 – 900 925 6SL3000-0CH41-2AA0
– 1TG41-3AA3 1100 1070
1TG41-4AA3 – 1100 1180
– 1TG41-7AA3 1370 1350 6SL3000-0CH41-6AA0
1TG41-8AA3 – 1500 1580

Line reactors for Smart Line Modules


Suitable for Rated power of the Rated input current of the Line reactor
Smart Line Module Smart Line Module Smart Line Module
in chassis format, at 400 V or 690 V
air-cooled
6SL3330-... kW A Article No.
Line voltage 380 ... 480 V 3 AC
6TE35-5AA3 250 463 6SL3000-0EE36-2AA0
6TE37-3AA3 355 614
6TE41-1AA3 500 883 6SL3000-0EE38-8AA0
6TE41-3AA3 630 1093 6SL3000-0EE41-4AA0
6TE41-7AA3 800 1430
Line voltage 500 ... 690 V 3 AC
6TG35-5AA3 450 463 6SL3000-0EH34-7AA0
6TG38-8AA3 710 757 6SL3000-0EH37-6AA0
6TG41-2AA3 1000 1009 6SL3000-0EH41-4AA0
6TG41-7AA3 1400 1430

5/8 Siemens D 21.3 · 2022


© Siemens 2022

System components for SINAMICS S120 Chassis and Chassis-2 Units


System components
Line-side power components > Line reactors

■ Technical specifications
Line voltage 380 ... 480 V 3 AC Line reactor
6SL3000- 6SL3000- 6SL3000- 6SL3000- 6SL3000- 6SL3000-
0CE32-3AA0 0CE32-8AA0 0CE33-3AA0 0CE35-1AA0 0CE36-3AA0 0CE37-7AA0
Rated current A 224 278 331 508 628 773
Nominal inductance LN H 76 62 52 42 27 22
Power loss 1) kW 0.274 0.247 0.267 0.365 0.368 0.351
At 50 Hz
Line/load connection 1 × hole for M10 1 × hole for M10 1 × hole for M10 1 × hole for M12 1 × hole for M12 1 × hole for M12
Provided for Provided for Provided for Provided for Provided for Provided for
busbar busbar busbar busbar busbar busbar
connection connection connection connection connection connection
PE connection M6 screw M6 screw M6 screw M6 screw M6 screw M6 screw
Degree of protection IP00 IP00 IP00 IP00 IP00 IP00
Dimensions
• Width mm (in) 270 (10.6) 270 (10.6) 270 (10.6) 300 (11.8) 300 (11.8) 300 (11.8)
• Height mm (in) 248 (9.76) 248 (9.76) 248 (9.76) 269 (10.6) 269 (10.6) 269 (10.6)
• Depth mm (in) 200 (7.87) 200 (7.87) 200 (7.87) 212.5 (8.37) 212.5 (8.37) 212.2 (8.35)
Weight, approx. kg (lb) 24.5 (54.0) 26 (57.3) 27.8 (61.3) 38 (83.8) 41.4 (91.3) 51.3 (113)
Suitable for Power Module in chassis format
• Air-cooled 6SL3310- 1TE32-1AA3 1TE32-6AA3 1TE33-1AA3 1TE33-8AA3 – –

• Liquid-cooled/water-cooled 6SL3315- 1TE32-1AA3 1TE32-6AA3 1TE33-1AA3


1TE35-0AA3
1TE35-0AA3 – –
5
Suitable for Basic Line Module in chassis format
• Air-cooled 6SL3330- – – – 1TE34-2AA3 – 1TE38-2AA3
1TE35-3AA3
• Liquid-cooled 6SL3335- – – – – 1TE37-4AA3 –

Line voltage 380 ... 480 V 3 AC Line reactor


6SL3000-0CE41-0AA0 6SL3000-0CE41-5AA0 6SL3000-0CE41-6AA0
Rated current A 1060 1485 1600
Nominal inductance LN H 16 13 13
Power loss 1) kW 0.498 0.776 0.606
At 50 Hz
Line/load connection 1 × hole for M12 1 × hole for M12 1 × hole for M12
Provided for busbar connection Provided for busbar connection Provided for busbar connection
PE connection M6 screw M6 screw M6 screw
Degree of protection IP00 IP00 IP00
Dimensions
• Width mm (in) 350 (13.8) 460 (18.1) 416 (16.4)
• Height mm (in) 321 (12.6) 435 (17.1) 435 (17.1)
• Depth mm (in) 211.5 (8.33) 235 (9.25) 235 (9.25)
Weight, approx. kg (lb) 69.6 (153) 118 (260) 123 (271)
Suitable for Basic Line Module in chassis format
• Air-cooled 6SL3330- 1TE41-2AA3 1TE41-5AA3 1TE41-8AA3
• Liquid-cooled 6SL3335- 1TE41-2AA3 1TE41-7AA3 –

1)
The specified power loss represents the maximum value at 100 %
utilization. The value is lower under normal operating conditions.

Siemens D 21.3 · 2022 5/9


© Siemens 2022

System components for SINAMICS S120 Chassis and Chassis-2 Units


System components
Line-side power components > Line reactors

■ Technical specifications
Line voltage 380 ... 480 V 3 AC Line reactor
6SL3000-0EE36-2AA0 6SL3000-0EE38-8AA0 6SL3000-0EE41-4AA0
Rated current A 615 885 1430
Nominal inductance LN H 55 35 25
Power loss 1) kW 0.56 0.81 1.08
At 50 Hz
Line/load connection 1 × hole for M10 2 × hole for M10 2 × hole for M10
Provided for busbar connection Provided for busbar connection Provided for busbar connection
PE connection M6 thread M6 thread M6 thread
Degree of protection IP00 IP00 IP00
Dimensions
• Width mm (in) 300 (11.8) 442 (17.4) 544 (21.4)
• Height mm (in) 264 (10.4) 376 (14.8) 386 (15.2)
• Depth mm (in) 203 (7.99) 263 (10.4) 232 (9.13)
Weight, approx. kg (lb) 57 (126) 85.5 (188) 220 (485)
Suitable for Smart Line Module in chassis format
• Air-cooled 6SL3330- 6TE35-5AA3 6TE41-1AA3 6TE41-3AA3
6TE37-3AA3 6TE41-7AA3

Line voltage 500 ... 690 V 3 AC Line reactor


5 6SL3000-
0CH32-7AA0
6SL3000-
0CH33-4AA0
6SL3000-
0CH34-8AA0
6SL3000-
0CH36-0AA0
6SL3000-
0CH41-2AA0
6SL3000-
0CH41-6AA0
Rated current A 270 342 482 597 1167 1600
Nominal inductance LN H 100 81 65 46 30 17
Power loss 1) kW 0.277 0.27 0.48 0.485 0.783 0.977
At 50 Hz
Line/load connection 1 × hole for M10 1 × hole for M10 1 × hole for M12 1 × hole for M12 2 × hole for M12 2 × hole for M12
Provided for Provided for Provided for Provided for Provided for Provided for
busbar connec- busbar connec- busbar connec- busbar connec- busbar connec- busbar connec-
tion tion tion tion tion tion
PE connection M6 screw M6 screw M6 screw M6 screw M6 screw M6 screw
Degree of protection IP00 IP00 IP00 IP00 IP00 IP00
Dimensions
• Width mm (in) 270 (10.6) 270 (10.6) 350 (13.8) 350 (13.8) 460 (18.1) 416 (16.4)
• Height mm (in) 248 (9.76) 248 (9.76) 321 (12.6) 321 (12.6) 435 (17.1) 435 (17.1)
• Depth mm (in) 200 (7.87) 200 (7.87) 232 (9.13) 232.5 (9.15) 235 (9.25) 250 (9.84)
Weight, approx. kg (lb) 27.9 (61.5) 38.9 (85.8) 55.6 (123) 63.8 (141) 147 (324) 134 (295)
Suitable for Basic Line Module in chassis format
• Air-cooled 6SL3330- 1TG33-0AA3 – 1TG34-3AA3 1TG36-8AA3 1TG41-1AA3 1TG41-8AA3
1TG41-4AA3
• Liquid-cooled 6SL3335- – 1TG34-2AA3 – 1TG37-3AA3 1TG41-3AA3 1TG41-7AA3

1) The specified power loss represents the maximum value at 100 %


utilization. The value is lower under normal operating conditions.

5/10 Siemens D 21.3 · 2022


© Siemens 2022

System components for SINAMICS S120 Chassis and Chassis-2 Units


System components
Line-side power components > Line reactors

■ Technical specifications
Line voltage 500 ... 690 V 3 AC Line reactor
6SL3000-0EH34-7AA0 6SL3000-0EH37-6AA0 6SL3000-0EH41-4AA0
Rated current A 465 760 1430
Nominal inductance LN H 115 70 40
Power loss 1) kW 0.82 0.95 1.85
At 50 Hz
Line/load connection 1 × hole for M10 2 × hole for M10 2 × hole for M10
Provided for busbar connection Provided for busbar connection Provided for busbar connection
PE connection M6 nut M6 nut M6 nut
Degree of protection IP00 IP00 IP00
Dimensions
• Width mm (in) 360 (14.2) 442 (17.4) 655 (25.8)
• Height mm (in) 325 (12.8) 370 (14.6) 383 (15.1)
• Depth mm (in) 229 (9.02) 303 (11.9) 288 (11.3)
Weight, approx. kg (lb) 58 (128) 145 (320) 239 (527)
Suitable for Smart Line Module in chassis format
• Air-cooled 6SL3330- 6TG35-5AA3 6TG38-8AA3 6TG41-2AA3
6TG41-7AA3

1)
The specified power loss represents the maximum value at 100 %
utilization. The value is lower under normal operating conditions.

Siemens D 21.3 · 2022 5/11


© Siemens 2022

System components for SINAMICS S120 Chassis and Chassis-2 Units


System components
Line-side power components > Recommended line-side system components

■ Selection and ordering data


Appropriate line-side power components are assigned More information about the main contactors, switch
depending on the power rating of the Power Modules, Basic disconnectors, fuses and circuit breakers is provided
Line Modules, Smart Line Modules or Active Line Modules. in the Catalogs IC 10 and LV 10.
Assignment of line-side power components to air-cooled and liquid/water-cooled Power Modules in chassis format
Type rating Rated input current Suitable for Power Main contactor Switch disconnector Handle and shaft
at 400 V Module in chassis for recommended switch
format disconnector
Air-cooled Liquid/
water-
cooled
6SL3310-... 1)
kW A A 6SL3315-... 2) Article No. Article No. Article No.
Line voltage 380 ... 480 V 3 AC
110 229 230 1TE32-1AA3 3RT1064-6AP36 3KF3325-0LF11 8UD1141-3AF21
132 284 285 1TE32-6AA3 3RT1065-6AP36 3KF4340-0LF11 8UD1151-3AF21
160 338 340 1TE33-1AA3 3RT1066-6AP36 –
200 395 – 1TE33-8AA3 3RT1075-6AP36 –
250 509 540 1TE35-0AA3 3RT1076-6AP36 3KF5363-0LF11 8UD1161-4AF21

Type rating Rated input current Suitable for Power Cable protection fuse 3) Cable protection fuse
at 400 V Module in chassis incl. Semiconductor protection 4)
5 Air-cooled Liquid/
format
Rated current Rated current
water-
cooled
6SL3310-... 1)
kW A A 6SL3315-... 2) A Article No. A Article No.
Line voltage 380 ... 480 V 3 AC
110 229 230 1TE32-1AA3 250 3NA3144 315 3NE1230-2
132 284 285 1TE32-6AA3 300 3NA3250 350 3NE1331-2
160 338 340 1TE33-1AA3 355 3NA3254 450 3NE1333-2
200 395 – 1TE33-8AA3 400 3NA3260
250 509 540 1TE35-0AA3 630 3NA3372 2 × 315/630 3NE1230-2
or
3NE1436-2

1) 4)
6SL3310-… is the air-cooled version. For device protection, only fuses of type 3NE1… can be used.
2)
6SL3315-... is the liquid/water-cooled version. These must be placed as close as possible to the converter.
3)
For additional conductor protection, the specified fuses of type
3NA3... can be used.

5/12 Siemens D 21.3 · 2022


© Siemens 2022

System components for SINAMICS S120 Chassis and Chassis-2 Units


System components
Line-side power components > Recommended line-side system components

■ Selection and ordering data


Assignment of line-side power components to air-cooled and liquid-cooled Basic Line Modules in chassis format
Rated power Rated input Suitable for Main contactor Fixed-mounted circuit Switch Handle and shaft
at 400 V or current Basic Line Module breaker disconnector for recommended
690 V switch disconnector
kW A Type Article No. Article No. Article No.
Line voltage 380 ... 480 V 3 AC
200 365 6SL3330-1TE34-2AA3 1) 3RT1075-... – 3KF5363-0LF11 8UD1161-4AF21
250 460 6SL3330-1TE35-3AA3 1) 3RT1076-... – 3KF5363-0LF11 8UD1161-4AF21
360 610 6SL3335-1TE37-4AA3 2) 3RT1076-... – 3KF5363-0LF11 8UD1161-4AF21
400 710 6SL3330-1TE38-2AA3 1) 3RT1066-... – 3KF5380-0LF11 8UD1161-4AF21
(3 units)
560 1010 6SL3330-1TE41-2AA3 1) – 3WA1112-4AE03-4EQ0 – –
600 1000 6SL3335-1TE41-2AA3 2) – 3WA1112-4AE03-4EQ0 – –
710 1265 6SL3330-1TE41-5AA3 1) – 3WA1116-4AE03-4EQ0 – –
830 1420 6SL3335-1TE41-7AA3 2) – 3WA1116-4AE03-4EQ0 – –
900 1630 6SL3330-1TE41-8AA3 1) – 3WA1120-4AE03-4EQ0 – –
Line voltage 500 ... 690 V 3 AC
250 260 6SL3330-1TG33-0AA3 1) 3RT1066-... – 3KF4340-0LF11 8UD1151-4AF21
355 375 6SL3330-1TG34-3AA3 1) 3RT1075-... – 3KF5363-0LF11 8UD1161-4AF21
340 6SL3335-1TG34-2AA3 2) 5
560 575 6SL3330-1TG36-8AA3 1) 3RT1076-... – 3KF5363-0LF11 8UD1161-4AF21
630 600 6SL3335-1TG37-3AA3 2) 3RT1076-... – 3KF5363-0LF11 8UD1161-4AF21
900 925 6SL3330-1TG41-1AA3 1) – 3WA1220-4AE03-4EQ0-Z – –
B10
1100 1180 6SL3330-1TG41-4AA3 1) – 3WA1220-4AE03-4EQ0-Z – –
1070 6SL3335-1TG41-3AA3 2) B12
1370 1350 6SL3335-1TG41-7AA3 2) – 3WA1220-4AE03-4EQ0-Z – –
B16
1500 1580 6SL3330-1TG41-8AA3 1) – 3WA1220-4AE03-4EQ0 – –

1)
6SL3330-… is the air-cooled version.
2)
6SL3335-… is the liquid-cooled version.

Siemens D 21.3 · 2022 5/13


© Siemens 2022

System components for SINAMICS S120 Chassis and Chassis-2 Units


System components
Line-side power components > Recommended line-side system components

■ Selection and ordering data


Rated power Rated input Suitable for Basic Line Module Cable protection fuse3) Cable protection fuse
at 400 V or current incl. Semiconductor protection4)
690 V
Rated current Rated current
kW A A Article No. A Article No.
Line voltage 380 ... 480 V 3 AC
200 365 6SL3330-1TE34-2AA3 1) 500 3NA3365 450 3NE1333-2
250 460 6SL3330-1TE35-3AA3 1) 630 3NA3372 500 3NE1334-2
360 610 6SL3335-1TE37-4AA3 2) 2 × 315 3NA3352 2 × 450 3NE1333-2
(2 units) (2 units)
400 710 6SL3330-1TE38-2AA3 1) 800 3NA3475 800 3NE1438-2
1)
560 1010 6SL3330-1TE41-2AA3 1250 3NA3482 2 × 560 3NE1435-2
(2 units)
600 1000 6SL3335-1TE41-2AA3 2) 2 × 500 3NA3365 2 × 560 3NE1435-2
(2 units) (2 units)
710 1265 6SL3330-1TE41-5AA3 1) 2 × 800 3NA3475 2 × 710 3NE1437-2
(2 units) (2 units)
830 1420 6SL3335-1TE41-7AA3 2) 3 × 500 3NA3365 2 × 800 3NE1438-2
(3 units) (2 units)
900 1630 6SL3330-1TE41-8AA3 1) 3 × 630 3NA3372 3 × 630 3NE1436-2
(3 units) (3 units)
5 Line voltage 500 ... 690 V 3 AC
250 260 6SL3330-1TG33-0AA3 1) 315 3NA3252-6 315 3NE1230-2
355 375 6SL3330-1TG34-3AA3 1) 500 3NA3365-6 450 3NE1333-2
340 6SL3335-1TG34-2AA3 2) 355 3NA3354-6
560 575 6SL3330-1TG36-8AA3 1) 2 × 315 3NA3252-6 630 3NE1436-2
(2 units)
630 600 6SL3335-1TG37-3AA3 2) 2 × 300 3NA3250-6 2 × 350 3NE1331-2
(2 units) (2 units)
900 925 6SL3330-1TG41-1AA3 1) 2 × 500 3NA3365-6 2 × 500 3NE1334-2
(2 units) (2 units)
1100 1180 6SL3330-1TG41-4AA3 1) 3 × 500 3NA3365-6 2 × 630 3NE1436-2
(3 units) (2 units)
1070 6SL3335-1TG41-3AA3 2) 3 × 400 3NA3360-6 2 × 670 3NE1447-2
(3 units) (2 units)
1370 1350 6SL3335-1TG41-7AA3 2) 3 × 500 3NA3365-6 3 × 560 3NE1435-2
(3 units) (3 units)
1500 1580 6SL3330-1TG41-8AA3 1) 4 × 500 3NA3365-6 3 × 630 3NE1436-2
(4 units) (3 units)

Power components for the pre-charging circuit of the Basic Line Modules in chassis format, frame size GD
Rated power at Rated input Suitable for Basic Pre-charging resistors Pre-charging Cable protection fuse
400 V or current Line Module contactor for pre-charging arm
690 V
Pre-charging Rated current
current 5)
kW A 6SL3330-... A Article No. Type A Article No.
Line voltage 380 ... 480 V 3 AC
900 1630 1TE41-8AA3 91 6) 6SL3000-0KE12- 3RT1034-... 6) 50 3NE1817-0 6)
182 7) 2AA0 3RT1044-... 7) 100 3NE1021-0 7)
Line voltage 500 ... 690 V 3 AC
1500 1580 1TG41-8AA3 86 6) 6SL3000-0KH14- 3RT1034-... 6) 50 3NE1817-0 6)
172 7) 0AA0 3RT1044-... 7) 100 3NE1021-0 7)

Note:
The dimension drawings of the pre-charging resistors are to be
found in the dimension drawing collection for Catalog D 21.3
in the Siemens Industry Online Support (SIOS).
1) 5)
6SL3330-… is the air-cooled version. Line current present at the start of the pre-charging process
2)
6SL3335-… is the liquid-cooled version. (initial rms value).
6)
3)
For additional conductor protection, the specified fuses of type With one pre-charging resistor per phase.
7)
3NA3... can be used. With two pre-charging resistors connected in parallel per phase.
4)
For device protection, only fuses of type 3NE1… can be used.
These must be placed as close as possible to the converter.

5/14 Siemens D 21.3 · 2022


© Siemens 2022

System components for SINAMICS S120 Chassis and Chassis-2 Units


System components
Line-side power components > Recommended line-side system components

■ Selection and ordering data


Assignment of line-side power components to Smart Line Modules in chassis format
Rated power Rated input Suitable for Main contactor Bypass contactor Switch Handle and shaft for
at 400 V or current Smart Line Module disconnector recommended
690 V switch disconnector
kW A 6SL3330-... Article No. Article No. Article No. Article No.
Line voltage 380 ... 480 V 3 AC
250 463 6TE35-5AA3 3RT1476-6AP36 – 3KF5363-0LF11 8UD1161-4AF21
355 614 6TE37-3AA3 3RT1476-6AP36 – 3KF5380-0LF11 8UD1161-4AF21
500 883 6TE41-1AA3 – 3WA1110-4AE03-4EQ0 – –
630 1093 6TE41-3AA3 – 3WA1112-4AE03-4EQ0 – –
800 1430 6TE41-7AA3 – 3WA1116-4AE03-4EQ0 – –
Line voltage 500 ... 690 V 3 AC
450 463 6TG35-5AA3 3RT1466-6AP36 – 3KF5363-0LF11 8UD1161-4AF21
710 757 6TG38-8AA3 3RT1466-6AP36 – 3KF5380-0LF11 8UD1161-4AF21
(3 units)
1000 1009 6TG41-2AA3 – 3WA1220-4AE03-4EQ0-Z – –
B12
1400 1430 6TG41-7AA3 – 3WA1220-4AE03-4EQ0-Z – –
B16

Rated power
at 400 V or
Rated input
current
Suitable for
Smart Line Module
Cable protection fuse 1) Cable protection fuse incl.
semiconductor protection 2)
5
690 V
Rated current Rated current
kW A 6SL3330-... A Article No. A Article No.
Line voltage 380 ... 480 V 3 AC
250 463 6TE35-5AA3 500 3NA3365 560 3NE1435-2
355 614 6TE37-3AA3 630 3NA3372 710 3NE1437-2
500 883 6TE41-1AA3 1000 3NA3480 2 × 500 3NE1334-2
(2 units)
630 1093 6TE41-3AA3 1250 3NA3482 2 × 630 3NE1436-2
(2 units)
800 1430 6TE41-7AA3 2 × 800 3NA3475 2 × 850 3NE1448-2
(2 units) (2 units)
Line voltage 500 ... 690 V 3 AC
450 463 6TG35-5AA3 500 3NA3365-6 560 3NE1435-2
710 757 6TG38-8AA3 2 × 400 3NA3360-6 850 3NE1448-2
(2 units)
1000 1009 6TG41-2AA3 3 × 355 3NA3354-6 2 × 560 3NE1435-2
(3 units) (2 units)
1400 1430 6TG41-7AA3 3 × 500 3NA3365-6 2 × 850 3NE1448-2
(3 units) (2 units)

1) For additional conductor protection, the specified fuses of type


3NA3... can be used.
2) For device protection, only fuses of type 3NE1… can be used.
These must be placed as close as possible to the converter.

Siemens D 21.3 · 2022 5/15


© Siemens 2022

System components for SINAMICS S120 Chassis and Chassis-2 Units


System components
Line-side power components > Recommended line-side system components

■ Selection and ordering data


Assignment of line-side power components to air-cooled and liquid-cooled Active Line Modules or Active Interface Modules
in chassis format
Rated power Rated input Suitable for Suitable for Active Line Module Bypass contactor
at 400 V or 690 V current Active Interface Module
kW A Article No.
Line voltage 380 ... 480 V 3 AC
132 210 6SL3300-7TE32-6AA1 6SL3330-7TE32-1AA3 Included in Active Interface
Module
160 260 6SL3300-7TE32-6AA1 6SL3330-7TE32-6AA3 Included in Active Interface
Module
235 380 6SL3300-7TE33-8AA1 6SL3330-7TE33-8AA3 Included in Active Interface
Module
300 490 6SL3300-7TE35-0AA1 6SL3330-7TE35-0AA3 Included in Active Interface
6SL3335-7TE35-0AA3 Module
380 605 6SL3300-7TE38-4AA1 6SL3330-7TE36-1AA3 3RT1476-6AP36
6SL3305-7TE38-4AA5 6SL3335-7TE36-1AA3
450 745 6SL3300-7TE38-4AA1 6SL3330-7TE37-5AA3 3WA1110-4AE03-4EQ0
500 840 6SL3300-7TE38-4AA1 6SL3330-7TE38-4AA3 3WA1110-4AE03-4EQ0
6SL3305-7TE38-4AA5 6SL3335-7TE38-4AA3
630 985 6SL3300-7TE41-4AA1 6SL3330-7TE41-0AA3 3WA1112-4AE03-4EQ0
6SL3305-7TE41-4AA5 6SL3335-7TE41-0AA3

5 800 1260
6SL3305-7TE41-4AA7
6SL3300-7TE41-4AA1
6SL3335-7TE41-0AA7
6SL3330-7TE41-2AA3 3WA1116-4AE03-4EQ0
900 1405 6SL3300-7TE41-4AA1 6SL3330-7TE41-4AA3 3WA1116-4AE03-4EQ0
6SL3305-7TE41-4AA5 6SL3335-7TE41-4AA3
6SL3305-7TE41-4AA7 6SL3335-7TE41-4AA7
Line voltage 500 ... 690 V 3 AC
630 575 6SL3300-7TG35-8AA1 6SL3330-7TG35-8AA3 3RT1476-6AP36
6SL3335-7TG35-8AA3
800 735 6SL3300-7TG37-4AA1 6SL3330-7TG37-4AA3 3RT1476-6AP36
6SL3305-7TG37-4AA5 6SL3335-7TG37-4AA3 (3 units)
900 810 6SL3305-7TG41-0AA5 6SL3335-7TG38-1AA3 3WA1220-4AE03-4EQ0-Z
6SL3305-7TG41-0AA7 6SL3335-7TG38-1AA7 B12
1100 1025 6SL3300-7TG41-3AA1 6SL3330-7TG41-0AA3 3WA1220-4AE03-4EQ0-Z
6SL3305-7TG41-0AA5 6SL3335-7TG41-0AA3 B12
6SL3305-7TG41-0AA7 6SL3335-7TG41-0AA7
1400 1270 6SL3300-7TG41-3AA1 6SL3330-7TG41-3AA3 3WA1220-4AE03-4EQ0-Z
6SL3305-7TG41-3AA5 6SL3335-7TG41-3AA3 B16
6SL3305-7TG41-3AA7 6SL3335-7TG41-3AA7
1700 1560 6SL3305-7TG41-6AA5 6SL3335-7TG41-6AA3 3WA1220-4AE03-4EQ0-Z
6SL3305-7TG41-6AA7 6SL3335-7TG41-6AA7 B16

5/16 Siemens D 21.3 · 2022


© Siemens 2022

System components for SINAMICS S120 Chassis and Chassis-2 Units


System components
Line-side power components > Recommended line-side system components

■ Selection and ordering data


Rated power Rated input Suitable for Suitable for Switch Handle and shaft Cable protection fuse 2) Cable protection fuse
at 400 V or current Active Active Line disconnector for recommended incl. semiconductor
690 V Interface Module switch protection 3)
Module disconnector
Rated Rated
current current
kW A 6SL3300-... 6SL3330-... Article No. Article No. A Article No. A Article No.
6SL3305-... 6SL3335-...
Line voltage 380 ... 480 V 3 AC
132 210 7TE32-6AA1 7TE32-1AA3 3KF3325-0LF11 8UD1141-3AF21 315 3NA3252 315 3NE1230-2
160 260 7TE32-6AA1 7TE32-6AA3 3KF4340-0LF11 8UD1151-3AF21 355 3NA3254 350 3NE1331-2
235 380 7TE33-8AA1 7TE33-8AA3 3KF4340-0LF11 8UD1151-3AF21 500 3NA3365 500 3NE1334-2
300 490 7TE35-0AA1 7TE35-0AA3 3KF5363-0LF11 8UD1161-4AF21 630 3NA3372 630 3NE1436-2
7TE35-0AA3 1)
380 605 7TE38-4AA1 7TE36-1AA3 3KF5380-0LF11 8UD1161-4AF21 800 3NA3475 800 3NE1438-2
7TE38-4AA5 1) 7TE36-1AA3 1)
450 745 7TE38-4AA1 7TE37-5AA3 – – 2 x 400 3NA3260 2 x 450 3NE1333-2
500 840 7TE38-4AA1 7TE38-4AA3 – – 2 × 425 3NA3362 2 × 500 3NE1334-2
7TE38-4AA5 1) 7TE38-4AA3 1) (2 units) (2 units)
630 985 7TE41-4AA1 7TE41-0AA3 – – 2 × 500 3NA3365 2 × 630 3NE1436-2
7TE41-4AA5 1) 7TE41-0AA3 1) (2 units) (2 units)
7TE41-4AA7 1) 7TE41-0AA7 1)
800 1260 7TE41-4AA1 7TE41-2AA3 – – 3 × 425 3NA3362
(2 units)
2 × 850 3NE1448-2
(2 units)
5
900 1405 7TE41-4AA1 7TE41-4AA3 – – 3 × 500 3NA3365 2 × 850 3NE1448-2
7TE41-4AA5 1) 7TE41-4AA3 1) (3 units) (2 units)
7TE41-4AA7 1) 7TE41-4AA7 1)
Line voltage 500 ... 690 V 3 AC
560/630 575 7TG35-8AA1 7TG35-8AA3 3KF5363-0LF11 8UD1161-4AF21 2 × 315 3NA3352-6 670 3NE1447-2
7TG35- (2 units)
8AA3 1)
800 735 7TG37-4AA1 7TG37-4AA3 3KF5380-0LF11 8UD1161-4AF21 2 × 400 3NA3360-6 850 3NE1448-2
7TG37- 7TG37- (2 units)
4AA5 1) 4AA3 1)
900 810 7TG41- 7TG38- – – 2 × 500 3NA3365-6 2 x 560 3NE1435-2
0AA5 1) 1AA3 1) (2 units) (2 units)
7TG41- 7TG38-
0AA7 1) 1AA7 1)
1100 1025 7TG41-3AA1 7TG41-0AA3 – – 3 × 355 3NA3354-6 2 × 630 3NE1436-2
7TG41- 7TG41- (3 units) (2 units)
0AA5 1) 0AA3 1)
7TG41- 7TG41-
0AA7 1) 0AA7 1)
1400 1270 7TG41-3AA1 7TG41-3AA3 – – 3 × 500 3NA3365-6 2 × 800 3NE1438-2
7TG41- 7TG41- (3 units) (2 units)
3AA5 1) 3AA3 1)
7TG41- 7TG41-
3AA7 1) 3AA7 1)
1700 1560 7TG41- 7TG41- – – 4 x 500 3NA3365-6 3 x 630 3NE1436-2
6AA5 1) 6AA3 1) (4 units) (3 units)
7TG41- 7TG41-
6AA7 1) 6AA7 1)

1)
Liquid-cooled version, 6SL3305-... or 6SL3335-...
2)
For additional conductor protection, the specified fuses of type
3NA3... can be used.
3)
For device protection, only fuses of type 3NE1… can be used.
These must be placed as close as possible to the converter.

Siemens D 21.3 · 2022 5/17


© Siemens 2022

System components for SINAMICS S120 Chassis and Chassis-2 Units


System components
Line-side power components > Recommended line-side system components

■ Selection and ordering data


Assignment of line-side power components to Active Line Modules or Active Interface Modules in chassis-2 format
Rated power Rated input current Suitable for Active Suitable for Active Switch disconnector Handle and shaft for
at 400 V Interface Module Line Module recommended switch
disconnector
kW A 6SL3301-... 6SL3331-... Article No. Article No.
Line voltage 380 ... 480 V 3 AC
355 560 7TE36-4AA0 7TE35-6AA0 3KF5380-0LF11 8UD1161-4AF21
400 635 7TE36-4AA0 7TE36-4AA0 3KF5380-0LF11 8UD1161-4AF21
450 745 7TE41-0AA0 7TE37-5AA0 – –
500 840 7TE41-0AA0 7TE38-4AA0 – –
560 900 7TE41-0AA0 1TE38-8AA0 – –
630 985 7TE41-0AA0 1TE41-0AA0 – –
710 1110 7TE41-4AA0 1TE41-2AA0 – –
800 1260 7TE41-4AA0 1TE41-3AA0 – –
900 1405 7TE41-4AA0 1TE41-4AA0 – –

Rated power Rated Suitable for Suitable for Line protection fuse Line protection fuse incl. Line protection fuse acc. to
at 400 V input Active Interface Active Line semiconductor protection UL 3)
current Module Module
Rated current Rated current Rated current
5 kW A 6SL3301-... 6SL3331-... A Article No. A Article No. A Article No.
Line voltage 380 ... 480 V 3 AC
355 560 7TE36-4AA0 7TE35-6AA0 800 3NA3475 800 3NE1438-2 800 3NE1438-2
400 635 7TE36-4AA0 7TE36-4AA0 800 3NA3475 800 3NE1438-2 800 3NE1438-2
450 745 7TE41-0AA0 7TE37-5AA0 2 x 400 3NA3260 2 x 450 3NE1333-2 1000 3NB3350-1KK26
(2 units) (2 units 4))
500 840 7TE41-0AA0 7TE38-4AA0 2 x 425 3NA3362 2 x 500 3NE1334-2 1000 3NB3350-1KK26
(2 units) (2 units 4))
560 900 7TE41-0AA0 1TE38-8AA0 2 x 500 3NA3365 2 x 500 3NE1435-2 1100 3NB3351-1KK26
(2 units) (2 units 4))
630 985 7TE41-0AA0 1TE41-0AA0 2 x 500 3NA3365 2 x 630 3NE1436-2 1250 3NB3352-1KK26
(2 units) (2 units 4))
710 1110 7TE41-4AA0 1TE41-2AA0 3 x 425 3NA3362 2 x 850 3NE1448-2 1700 3NB3358-1KK26
(3 units) (2 units 4))
800 1260 7TE41-4AA0 1TE41-3AA0 3 x 425 3NA3362 2 x 850 3NE1448-2 1700 3NB3358-1KK26
(3 units) (2 units 4))
900 1405 7TE41-4AA0 1TE41-4AA0 3 x 500 3NA3365 2 x 850 3NE1448-2 1700 3NB3358-1KK26
(3 units) (2 units 4))

1)
For additional conductor protection, the specified fuses of type
3NA3... can be used.
2)
For device protection, only fuses of type 3NE1… can be used.
These must be placed as close as possible to the converter.
3)
To achieve a UL-approved system, it is absolutely essential to use
the fuse types specified in the table.
4)
When using fuses connected in parallel in each phase, if one fuse ruptures,
then all of the fuses must be replaced.

5/18 Siemens D 21.3 · 2022


© Siemens 2022

System components for SINAMICS S120 Chassis and Chassis-2 Units


System components
Line-side power components > Recommended line-side system components

■ Selection and ordering data


Power components for the pre-charging circuit of the Active Line Modules or Active Interface Modules in chassis-2 format
Rated power at Rated input Suitable for Active Pre-charging resistors Pre-charging Cable protection fuse Main contactor/
400 V or current Line Module contactor for pre-charging arm Circuit breaker
690 V
Pre-charging Rated current
current 1)
kW A 6SL3331-... A Article No. Type A Article No. Article No.
Line voltage 380 ... 480 V 3 AC
355 560 7TE35-6AA0 91 2) 6SL3000- 3RT2027-... 2) 50 3NE1817-0 2) 3RT1466-6AP36
182 3) 0KE12-2AA0 3RT2037-... 3) 4) 100 (3 units)
400 635 7TE36-4AA0 274 4) 3NE1021-0 3) 4) 3RT1466-6AP36
(3 units)
450 745 7TE37-5AA0 3WA1220-4AE03-
4EQ0-Z
B10
500 840 7TE38-4AA0 3WA1220-4AE03-
4EQ0-Z
B10
560 900 1TE38-8AA0 3WA1220-4AE03-
4EQ0-Z
B10
630 985 1TE41-0AA0 3WA1220-4AE03-
4EQ0-Z
5
B12
710 1110 1TE41-2AA0 3WA1220-4AE03-
4EQ0-Z
B12
800 1260 1TE41-3AA0 3WA1220-4AE03-
4EQ0-Z
B16
900 1405 1TE41-4AA0 3WA1220-4AE03-
4EQ0-Z
B16

Note:
The dimension drawings of the pre-charging resistors are to be found in the dimension drawing collection for Catalog D 21.3
in the Siemens Industry Online Support (SIOS).

1) 3)
Line current present at the start of the pre-charging process With two pre-charging resistors per phase.
(initial rms value). 4)
With three pre-charging resistors per phase.
2)
With one pre-charging resistor per phase.

Siemens D 21.3 · 2022 5/19


© Siemens 2022

System components for SINAMICS S120 Chassis and Chassis-2 Units


System components
DC link components > Braking Modules

■ Overview ■ Selection and ordering data


Rated power Peak power Frame size Braking Module
PDB P15
kW kW Article No.
Line voltage 380 ... 480 V 3 AC
DC link voltage 510 ... 720 V DC
25 125 FX/FB 6SL3300-1AE31-3AA0
50 250 GX/GB/GD 6SL3300-1AE32-5AA0
50 250 HX/JX 6SL3300-1AE32-5BA0
Line voltage 500 ... 600 V 3 AC
DC link voltage 675 ... 900 V DC
25 125 FX/FB 6SL3300-1AF31-3AA0
50 250 GX/GB/GD 6SL3300-1AF32-5AA0
50 250 HX/JX 6SL3300-1AF32-5BA0

A Braking Module and the matching external braking resistor are Line voltage 660 ... 690 V 3 AC
DC link voltage 890 ... 1035 V DC
required to bring drives to a controlled standstill in the event of
a power failure (e.g. with an EMERGENCY STOP) or to limit the 25 125 FX/FB 6SL3300-1AH31-3AA0
DC link voltage for brief periods of regenerative operation, 50 250 GX/GB/GD 6SL3300-1AH32-5AA0
e.g. if the Line Module is not capable of energy recovery.
50 250 HX/JX 6SL3300-1AH32-5BA0
The Braking Module includes the power electronics and the
associated control circuit. During operation, the DC link energy Description Article No.

5 is converted to heat loss in an external braking resistor. Accessories


The Braking Module works independently of the converter Cable harness set 6SL3366-2NG00-0AA0
control. for mounting a Braking Module of frame size
GX into a Basic Line Module of frame size
Several Braking Modules can be operated in parallel, GB or GD
but a separate braking resistor must be connected to each
Braking Module.
Braking Modules are designed to be integrated into air-cooled
Motor Modules, Line Modules or Power Modules and are cooled
by the fans on these modules. The supply voltage for the
electronics is taken from the DC link. The Braking Modules are
connected to the DC link by means of the busbar sets included
in the scope of supply or flexible cables and, in the case of Basic
Line Modules of frame size GB or GD, using a separate cable
harness set.
The activation threshold of the Braking Module can be adjusted
by means of a DIP switch. The braking power values specified
in the technical specifications apply to the upper activation
threshold.
Note:
The Braking Modules are not intended for installation in a Line
Module or Motor Module in chassis-2 format.

■ Design
The Braking Modules have the following interfaces as standard:
• 1 DC link connection
• 1 braking resistor connection
• 1 digital input (inhibit Braking Module / acknowledge error)
• 1 digital output (Braking Module inhibited)
• 1 DIP switch for adjusting the activation threshold
Information about Braking Module activation thresholds and
other notes are included in the SINAMICS Low Voltage
Engineering Manual.

5/20 Siemens D 21.3 · 2022


© Siemens 2022

System components for SINAMICS S120 Chassis and Chassis-2 Units


System components
DC link components > Braking Modules

■ Integration

Braking Module
X21

+24 V
21.6

Fault output
21.5 Fault
0V
21.4

Inhibit input
21.3
Inhibit
0V
21.2
Shield
21.1

Braking resistor

R1 T1

DCPA
5
R2
DC link T2
connection terminals
DCNA
G_D211_EN_00012a

Connection example of a Braking Module

■ Characteristic curves
P/P20 G_D011_EN_00328

1.50

1.25 P15

1.00 P20

0.75

0.50 P40
PDB
0.25

0
10 15 20 30 40 50 60 70 80 90 100 s t

PDB = Rated power


P15 = 5 x PDB = Power which is permissible every 90 s for 15 s
P20 = 4 x PDB = Power which is permissible every 90 s for 20 s
P40 = 2 x PDB = Power which is permissible every 90 s for 40 s

Load diagram for Braking Modules and braking resistor

Siemens D 21.3 · 2022 5/21


© Siemens 2022

System components for SINAMICS S120 Chassis and Chassis-2 Units


System components
DC link components > Braking Modules

■ Technical specifications
Line voltage 380 ... 480 V 3 AC Braking Module
DC link voltage 510 ... 720 V DC
6SL3300-1AE31-3AA0 6SL3300-1AE32-5AA0 6SL3300-1AE32-5BA0
Power
• Rated power PDB kW 25 50 50
• Peak power P15 kW 125 250 250
• Power P20 kW 100 200 200
• Power P40 kW 50 100 100
Activation thresholds V 774 (factory setting) 774 (factory setting) 774 (factory setting)
(adjustable via DIP switch) or 673 or 673 or 673
Digital inputs
in accordance with IEC 61131-2
Type 1
• Voltage V 24 DC 24 DC 24 DC
• Low level (an open digital input is V -3 ... +5 -3 ... +5 -3 ... +5
interpreted as "low")
• High level V 15 ... 30 15 ... 30 15 ... 30
• Current consumption at 24 V DC, mA 10 10 10
typ.
• Conductor cross-section, max. mm2 1.5 1.5 1.5
Digital outputs
(continuously short-circuit proof)
• Voltage V 24 DC 24 DC 24 DC

5 • Load current per digital output, max. mA


• Conductor cross-section, max. mm2
500
1.5
500
1.5
500
1.5
R1/R2 connection M8 nut M8 nut M8 nut
• Conductor cross-section, max. mm2 35 50 50
Weight, approx. kg (lb) 3.6 (7.94) 7.3 (16.1) 7.5 (16.5)
Suitable for installation in air-cooled Power Modules, Line Modules or Motor Modules
• Air-cooled Frame FX/FB GX/GB/GD 1) HX/JX
size

Line voltage 500 ... 600 V 3 AC Braking Module


DC link voltage 675 ... 900 V DC
6SL3300-1AF31-3AA0 6SL3300-1AF32-5AA0 6SL3300-1AF32-5BA0
Power
• Rated power PDB kW 25 50 50
• Peak power P15 kW 125 250 250
• Power P20 kW 100 200 200
• Power P40 kW 50 100 100
Activation thresholds V 967 (factory setting) 967 (factory setting) 967 (factory setting)
(adjustable via DIP switch) or 841 or 841 or 841
Digital inputs
in accordance with IEC 61131-2
Type 1
• Voltage V 24 DC 24 DC 24 DC
• Low level (an open digital input is V -3 ... +5 -3 ... +5 -3 ... +5
interpreted as "low")
• High level V 15 ... 30 15 ... 30 15 ... 30
• Current consumption at 24 V DC, mA 10 10 10
typ.
• Conductor cross-section, max. mm2 1.5 1.5 1.5
Digital outputs
(continuously short-circuit proof)
• Voltage V 24 DC 24 DC 24 DC
• Load current per digital output, max. mA 500 500 500
• Conductor cross-section, max. mm2 1.5 1.5 1.5
R1/R2 connection M8 nut M8 nut M8 nut
• Conductor cross-section, max. mm2 35 50 50
Weight, approx. kg (lb) 3.6 (7.94) 7.3 (16.1) 7.5 (16.5)
Suitable for installation in air-cooled Power Modules, Line Modules or Motor Modules
• Air-cooled Frame FX/FB GX/GB/GD 1) HX/JX
size

1) Cable harness set 6SL3366-2NG00-0AA0 is required to connect the


Braking Module to a Basic Line Module of frame size GB or GD.

5/22 Siemens D 21.3 · 2022


© Siemens 2022

System components for SINAMICS S120 Chassis and Chassis-2 Units


System components
DC link components > Braking Modules

■ Technical specifications
Line voltage 660 ... 690 V 3 AC Braking Module
DC link voltage 890 ... 1035 V DC
6SL3300-1AH31-3AA0 6SL3300-1AH32-5AA0 6SL3300-1AH32-5BA0
Power
• Rated power PDB kW 25 50 50
• Peak power P15 kW 125 250 250
• Power P20 kW 100 200 200
• Power P40 kW 50 100 100
Activation thresholds V 967 (factory setting) 1158 (factory setting) 1158 (factory setting)
(adjustable via DIP switch) or 841 or 1070 or 1070
Digital inputs
in accordance with IEC 61131-2
Type 1
• Voltage V 24 DC 24 DC 24 DC
• Low level (an open digital input is V -3 ... +5 -3 ... +5 -3 ... +5
interpreted as "low")
• High level V 15 ... 30 15 ... 30 15 ... 30
• Current consumption at 24 V DC, mA 10 10 10
typ.
• Conductor cross-section, max. mm2 1.5 1.5 1.5
Digital outputs
(continuously short-circuit proof)
• Voltage V 24 DC 24 DC 24 DC
• Load current per digital output, max. mA
• Conductor cross-section, max. mm2
500
1.5
500
1.5
500
1.5
5
R1/R2 connection M8 nut M8 nut M8 nut
• Conductor cross-section, max. mm2 35 50 50
Weight, approx. kg (lb) 3.6 (7.94) 7.3 (16.1) 7.5 (16.5)
Suitable for installation in air-cooled Power Modules, Line Modules or Motor Modules
• Air-cooled Frame FX/FB GX/GB/GD 1) HX/JX
size

1) Cable harness set 6SL3366-2NG00-0AA0 is required to connect the


Braking Module to a Basic Line Module of frame size GB or GD.

Siemens D 21.3 · 2022 5/23


© Siemens 2022

System components for SINAMICS S120 Chassis and Chassis-2 Units


System components
DC link components > Braking resistors

■ Overview ■ Selection and ordering data


Rated power PDB Suitable for Braking Braking resistor
Module
kW 6SL3300-... Article No.
Line voltage 380 ... 480 V 3 AC
DC link voltage 510 ... 720 V DC
25 1AE31-3AA0 6SL3000-1BE31-3AA0
50 1AE32-5 . A0 6SL3000-1BE32-5AA0
Line voltage 500 ... 600 V 3 AC
DC link voltage 675 ... 900 V DC
25 1AF31-3AA0 6SL3000-1BF31-3AA0
50 1AF32-5 . A0 6SL3000-1BF32-5AA0
Line voltage 660 ... 690 V 3 AC
DC link voltage 890 ... 1035 V DC
25 1AH31-3AA0 6SL3000-1BH31-3AA0
50 1AH32-5 . A0 6SL3000-1BH32-5AA0
Excess energy in the DC link is dissipated via the braking
resistor. ■ Characteristic curves
The braking resistor is connected to a Braking Module.
By positioning the braking resistor outside the cabinet or P/P20 G_D011_EN_00328

switchgear room, it is possible to extract the heat losses away


5 from the Line Modules / Motor Modules. This reduces the level of
air conditioning required.
1.50
The maximum permissible cable length between the Braking
Module and braking resistor is 100 m. 1.25 P15

Two braking resistors with different rated and peak power values 1.00 P20
are available for the devices.
0.75
The braking resistor is monitored on the basis of the duty cycle.
A temperature switch (NC contact) is also fitted. This responds 0.50 P40
when the maximum permissible temperature is exceeded and PDB
can be evaluated by a controller. 0.25

Information about possible load cycles of the braking resistors 0


and other notes are included in the SINAMICS Low Voltage 10 15 20 30 40 50 60 70 80 90 100 s t
Engineering Manual.

PDB = Rated power


P15 = 5 x PDB = Power which is permissible every 90 s for 15 s
P20 = 4 x PDB = Power which is permissible every 90 s for 20 s
P40 = 2 x PDB = Power which is permissible every 90 s for 40 s

Load diagram for Braking Modules and braking resistors

5/24 Siemens D 21.3 · 2022


© Siemens 2022

System components for SINAMICS S120 Chassis and Chassis-2 Units


System components
DC link components > Braking resistors

■ Technical specifications
Line voltage 380 ... 480 V 3 AC Braking resistor
DC link voltage 510 ... 720 V DC
6SL3000-1BE31-3AA0 6SL3000-1BE32-5AA0
Resistance  4.4 (±7.5 %) 2.2 (±7.5 %)
Rated power PDB kW 25 50
(continuous braking power)
Power P15 kW 125 250
Power P20 kW 100 200
Power P40 kW 50 100
Current, max. A 189 378
Power connection M10 stud M10 stud
• Conductor cross-section, max. (IEC) mm2 50 70
Degree of protection IP20 IP20
Dimensions
• Width mm (in) 740 (29.1) 810 (31.9)
• Height mm (in) 605 (23.8) 1325 (52.2)
• Depth mm (in) 486 (19.1) 486 (19.1)
Weight, approx. kg (lb) 50 (110) 120 (265)
Suitable for Braking Module Type 6SL3300-1AE31-3AA0 6SL3300-1AE32-5 . A0

Line voltage 500 ... 600 V 3 AC


DC link voltage 675 ... 900 V DC
Braking resistor
5
6SL3000-1BF31-3AA0 6SL3000-1BF32-5AA0
Resistance  6.8 (±7.5 %) 3.4 (±7.5 %)
Rated power PDB kW 25 50
(continuous braking power)
Power P15 kW 125 250
Power P20 kW 100 200
Power P40 kW 50 100
Current, max. A 189 378
Power connection M10 stud M10 stud
• Conductor cross-section, max. (IEC) mm2 50 70
Degree of protection IP20 IP20
Dimensions
• Width mm (in) 740 (29.1) 810 (31.9)
• Height mm (in) 605 (23.8) 1325 (52.2)
• Depth mm (in) 486 (19.1) 486 (19.1)
Weight, approx. kg (lb) 50 (110) 120 (265)
Suitable for Braking Module Type 6SL3300-1AF31-3AA0 6SL3300-1AF32-5 . A0

Line voltage 660 ... 690 V 3 AC Braking resistor


DC link voltage 890 ... 1035 V DC
6SL3000-1BH31-3AA0 6SL3000-1BH32-5AA0
Resistance  9.8 (±7.5 %) 4.9 (±7.5 %)
Rated power PDB kW 25 50
(continuous braking power)
Power P15 kW 125 250
Power P20 kW 100 200
Power P40 kW 50 100
Current, max. A 125 255
Power connection M10 stud M10 stud
• Conductor cross-section, max. (IEC) mm2 50 70
Degree of protection IP20 IP20
Dimensions
• Width mm (in) 740 (29.1) 810 (31.9)
• Height mm (in) 605 (23.8) 1325 (52.2)
• Depth mm (in) 486 (19.1) 486 (19.1)
Weight, approx. kg (lb) 50 (110) 120 (265)
Suitable for Braking Module Type 6SL3300-1AH31-3AA0 6SL3300-1AH32-5 . A0

Siemens D 21.3 · 2022 5/25


© Siemens 2022

System components for SINAMICS S120 Chassis and Chassis-2 Units


System components
DC link components > DC link fuses

■ Selection and ordering data


Suitable DC link fuses are assigned depending on the power Further information about the fuses listed is provided in the
rating of the Motor Modules. Catalogs IC 10 and LV 10.
Assignment of the DC link fuses to the Motor Modules in chassis format, liquid-cooled and water-cooled
Type Rated DC link Suitable for DC link fuse according to IEC DC link fuse according to UL 1)
rating current for power Motor Module in
at 400 V supplied via chassis format
Basic Line Module /
Active Line Module
Rated Quantity Frame Rated Quantity Frame
current / Phase size current / Phase size
kW A 6SL3325-... A Article No. A Article No.
Line voltage 380 ... 480 V 3 AC
110 256/230 1TE32-1AA3 315 1 1 3NE3230-0B 315 1 1 3NE3230-0B
315 1 2L 3NB1231-4KK11
132 317/287 1TE32-6AA3 400 1 1 3NE3232-0B 400 1 1 3NE3232-0B
400 1 2L 3NB1234-4KK11
160 380/340 1TE33-1AA3 450 1 1 3NE3233 450 1 1 3NE3233
500 1 3L 3NB1337-4KK11
250 600/538 1TE35-0AA3 630 1 2 3NE3236 630 1 2 3NE3236
800 1 3L 3NB1345-4KK11
5 315 738/664 1TE36-1AA3 800 1 2 3NE3338-8 800 1 2 3NE3338-8
800 1 3L 3NB2345-4KK16
400 894/805 1TE37-5AA3 500 2 2 3NE3334-0B 1000 1 3L 3NB2350-4KK16
1TE37-5AA7
450 1025/922 1TE38-4AA3 560 2 2 3NE3335 560 2 2 3NE3335
1000 1 3L 3NB2350-4KK16
560 1202/1080 1TE41-0AA3 630 2 2 3NE3336 630 2 2 3NE3336
1TE41-0AA7
1400 1 3L 3NB2355-4KK16
710 1512/1361 1TE41-2AA3 900 2 2 3NE3340-8 2100 1 3L 3NB2364-4KK17
1TE41-2AA
800 1714/1544 1TE41-4AA3 900 2 2 3NE3340-8 900 2 2 3NE3340-8
1TE41-4AA7
2100 1 3L 3NB2364-4KK17
800 1550/1403 1TE41-4AS3 2) 900 2 2 3NE3340-8 2100 1 3L 3NB2364-4KK17

1) To achieve a UL-approved system, it is absolutely essential to use


the fuse types specified in the table.
2) This Motor Module has been specifically designed for loads demanding
a high dynamic performance.

5/26 Siemens D 21.3 · 2022


© Siemens 2022

System components for SINAMICS S120 Chassis and Chassis-2 Units


System components
DC link components > DC link fuses

■ Selection and ordering data


Type Rated DC link Suitable for DC link fuse according to IEC DC link fuse according to UL 1)
rating current for power Motor Module in
at 690 V supplied via chassis format
Basic Line Module /
Active Line Module
Rated Quantity Frame Rated Quantity Frame
current / Phase size current / Phase size
kW A 6SL3325-... A Article No. A Article No.
Line voltage 500 ... 690 V 3 AC
90 122/110 1TG31-0AA3 160 1 1 3NE3224 160 1 1 3NE3224
200 1 1L 3NB1126-4KK11
132 183/165 1TG31-5AA3 200 1 1 3NE3225 200 1 1 3NE3225
250 1 1L 3NB1128-4KK11
200 263/237 1TG32-2AA3 315 1 1 3NE3230-0B 315 1 1 3NE3230-0B
315 1 2L 3NB1231-4KK11
315 403/363 1TG33-3AA3 450 1 2 3NE3233 450 1 2 3NE3233
500 1 3L 3NB1337-4KK11
450 558/502 1TG34-7AA3 630 1 2 3NE3336 800 1 3L 3NB1345-4KK11
1TG34-7AA7
560 702/632 1TG35-8AA3 400 2 1 3NE3232-0B 400 2 1 3NE3232-0B
1TG35-8AA7

710 903/759 1TG37-4AA3 560 2 2 3NE3335


800
1000
1
1
3L
3L
3NB2345-4KK16
3NB2350-4KK16
5
800 990/891 1TG38-0AA3 2) 560 2 2 3NE3335 1000 1 3L 3NB2350-4KK16
800 990/891 1TG38-1AA3 560 2 2 3NE3335 560 2 2 3NE3335
1TG38-1AA7
1000 1 3L 3NB2350-4KK16
1000 1250/1125 1TG41-0AA3 710 2 2 3NE3337-8 710 2 2 3NE3337-8
1TG41-0AA7
1600 1 3L 3NB2357-4KK16
1200 1550/1395 1TG41-3AA3 900 2 2 3NE3340-8 900 2 2 3NE3340-8
1TG41-3AA7
2100 1 3L 3NB2364-4KK17
1500 1903/1605 1TG41-6AA3 710 3 2 3NE3337-8 2400 1 3L 3NB2366-4KK17
1TG41-6AA7

Assignment of the DC link fuses to the Motor Modules in chassis-2 format, air-cooled
Type Rated DC link Suitable for DC link fuse according to IEC DC link fuse according to UL 1)
rating current Motor Module in
at 400 V chassis-2 format
Rated Quantity Frame Rated Quantity Frame
current / phase size current / phase size
kW A 6SL3321-... A Article No. A Article No.
Line voltage 380 ... 480 V 3 AC
315 785 1TE36–6AA0 500 23) 2 3NE3334-0B 1000 1 3L 3NB2350-4KK16
355 890 1TE37–4AA0 560 23) 2 3NE3335 1000 1 3L 3NB2350-4KK16
400 975 1TE38-1AA0 560 23) 2 3NE3335 1400 1 3L 3NB2355-4KK16
450 1090 1TE38-8AA0 630 23) 2 3NE3336 1400 1 3L 3NB2355-4KK16
3)
500 1170 1TEA41-0AA0 630 2 2 3NE3336 1400 1 3L 3NB2355-4KK16
560 1290 1TEA41-1AA0 710 23) 2 3NE3337-8 1400 1 3L 3NB2355-4KK16
630 1440 1TEA41-2AA0 800 23) 2 3NE3338-8 1600 1 3L 3NB2357-4KK16
710 1590 1TEA41-3AA0 1000 23) 3 3NC3341-1U 2100 1 3L 3NB2364-4KK17
800 1795 1TEA41-5AA0 1100 23) 3 3NC3342-1U 2100 1 3L 3NB2364-4KK17

1) 3)
To achieve a UL-approved system, it is absolutely essential to use the fuse When using fuses connected in parallel in each phase, if one fuse ruptures,
types specified in the table. then all of the fuses must be replaced.
2)
Device 6SL3325-1TG38-0AA3 is optimized for a base pulse frequency of
1.25 kHz, for an increased pulse frequency or with certain overloads, the
derating factor is higher than for the device 6SL3325-1TG38-1AA3.

Siemens D 21.3 · 2022 5/27


© Siemens 2022

System components for SINAMICS S120 Chassis and Chassis-2 Units


System components
DC link components > DC link fuses

■ Selection and ordering data


Assignment of the DC link fuses to the Active Line Modules in chassis-2 format, air-cooled
Rated Rated DC link Suitable for DC link fuse according to IEC DC link fuse according to UL 1)
power current Active Line
at 400 V Modules in
chassis-2 format
Rated Quantity Frame Rated Quantity Frame
current / phase size current / phase size
kW A 6SL3331-... A Article No. A Article No.
Line voltage 380 ... 480 V 3 AC
355 630 7TE35-6AA0 450 22) 2 3NE3333 1000 1 3L 3NB2350-4KK16
400 710 7TE36-4AA0 500 22) 2 3NE3334-0B 1000 1 3L 3NB2350-4KK16
450 835 7TE37-5AA0 560 22) 2 3NE3335 1400 1 3L 3NB2355-4KK16
500 940 7TE38-4AA0 630 22) 2 3NE3336 1400 1 3L 3NB2355-4KK16
530 1010 7TE38-8AA0 710 22) 2 3NE3337-8 1400 1 3L 3NB2355-4KK16
630 1110 7TE41-0AA0 800 22) 2 3NE3338-8 1400 1 3L 3NB2355-4KK16
710 1245 7TE41-2AA0 800 22) 2 3NE3338-8 1600 1 3L 3NB2357-4KK16
800 1415 7TE41-3AA0 800 22) 2 3NE3338-8 1600 1 3L 3NB2357-4KK16
900 1575 7TE41-4AA0 1000 22) 3 3N3341-1U 1600 1 3L 3NB2357-4KK16

1)
To achieve a UL-approved system, it is absolutely essential to use the fuse
types specified in the table.
2)
When using fuses connected in parallel in each phase, if one fuse ruptures,
then all of the fuses must be replaced.

5/28 Siemens D 21.3 · 2022


© Siemens 2022

System components for SINAMICS S120 Chassis and Chassis-2 Units


System components
Motor-side power components > Motor reactors

■ Overview
Motor reactors reduce the voltage load on the motor windings by
reducing the voltage gradients at the motor terminals that occur
during converter operation. At the same time, the capacitive
charge/discharge currents that place an additional load on the
converter output when using long motor cables, are reduced.
For group drives, output reactors should always be used.
The maximum permissible output frequency when a motor
reactor is used is 150 Hz.
The motor reactor must be installed as close as possible to the
Motor Module or Power Module. Up to two motor reactors can be
connected in series.
Motor reactors are approved for use only in conjunction with
Vector and V/f control modes.
For additional notes on the use of motor reactors, please refer to
the SINAMICS Low Voltage Engineering Manual.

■ Selection and ordering data


Motor reactors for Power Modules and Motor Modules in chassis format
Suitable for Power Module Suitable for Motor Module Type
rating
at 400 V
Rated
output
current
Motor reactor
5
Air-cooled Liquid-cooled/ Air-cooled Liquid-cooled/ kW A Article No.
water-cooled water-cooled
Line voltage 380 ... 480 V 3 AC
6SL3310-1TE32-1AA3 6SL3315-1TE32-1AA3 6SL3320-1TE32-1AA3 6SL3325-1TE32-1AA3 110 210 6SL3000-2BE32-1AA0
6SL3310-1TE32-6AA3 6SL3315-1TE32-6AA3 6SL3320-1TE32-6AA3 6SL3325-1TE32-6AA3 132 260 6SL3000-2BE32-6AA0
6SL3310-1TE33-1AA3 6SL3315-1TE33-1AA3 6SL3320-1TE33-1AA3 6SL3325-1TE33-1AA3 160 310 6SL3000-2BE33-2AA0
6SL3310-1TE33-8AA3 – 6SL3320-1TE33-8AA3 – 200 380 6SL3000-2BE33-8AA0
6SL3310-1TE35-0AA3 6SL3315-1TE35-0AA3 6SL3320-1TE35-0AA3 6SL3325-1TE35-0AA3 250 490 6SL3000-2BE35-0AA0
– – 6SL3320-1TE36-1AA3 6SL3325-1TE36-1AA3 315 605 6SL3000-2AE36-1AA0
– – 6SL3320-1TE37-5AA3 6SL3325-1TE37-5AA3 400 745 6SL3000-2AE38-4AA0
6SL3325-1TE37-5AA7
– – 6SL3320-1TE38-4AA3 6SL3325-1TE38-4AA3 450 840
– – 6SL3320-1TE41-0AA3 6SL3325-1TE41-0AA3 560 985 6SL3000-2AE41-0AA0
6SL3325-1TE41-0AA7
– – 6SL3320-1TE41-2AA3 6SL3325-1TE41-2AA3 710 1260 6SL3000-2AE41-4AA0
6SL3325-1TE41-2AA7
– – 6SL3320-1TE41-4AA3 6SL3325-1TE41-4AA3 800 1405
6SL3325-1TE41-4AA7
6SL3325-1TE41-4AS3 1) 800 1330

1)
This Motor Module has been specifically designed for loads demanding
a high dynamic performance.

Siemens D 21.3 · 2022 5/29


© Siemens 2022

System components for SINAMICS S120 Chassis and Chassis-2 Units


System components
Motor-side power components > Motor reactors

■ Selection and ordering data


Suitable for Power Module Suitable for Motor Module Type Rated Motor reactor
rating output
at 690 V current
Air-cooled Liquid-cooled/ Air-cooled Liquid-cooled/ kW A Article No.
water-cooled water-cooled
Line voltage 500 ... 690 V 3 AC
– – 6SL3320-1TG28-5AA3 – 75 85 6SL3000-2AH31-0AA0
– – 6SL3320-1TG31-0AA3 6SL3325-1TG31-0AA3 90 100
– – 6SL3320-1TG31-2AA3 – 110 120 6SL3000-2AH31-5AA0
– – 6SL3320-1TG31-5AA3 6SL3325-1TG31-5AA3 132 150
– – 6SL3320-1TG31-8AA3 – 160 175 6SL3000-2AH31-8AA0
– – 6SL3320-1TG32-2AA3 6SL3325-1TG32-2AA3 200 215 6SL3000-2AH32-4AA0
– – 6SL3320-1TG32-6AA3 – 250 260 6SL3000-2AH32-6AA0
– – 6SL3320-1TG33-3AA3 6SL3325-1TG33-3AA3 315 330 6SL3000-2AH33-6AA0
– – 6SL3320-1TG34-1AA3 – 400 410 6SL3000-2AH34-5AA0
– – 6SL3320-1TG34-7AA3 6SL3325-1TG34-7AA3 450 465 6SL3000-2AH34-7AA0
6SL3325-1TG34-7AA7
– – 6SL3320-1TG35-8AA3 6SL3325-1TG35-8AA3 560 575 6SL3000-2AH35-8AA0
6SL3325-1TG35-8AA7
– – 6SL3320-1TG37-4AA3 6SL3325-1TG37-4AA3 710 735 6SL3000-2AH38-1AA0
5 – – 6SL3320-1TG38-1AA3 6SL3325-1TG38-0AA3 800 810
6SL3325-1TG38-1AA3
6SL3325-1TG38-1AA7
– – 6SL3320-1TG38-8AA3 – 900 910 6SL3000-2AH41-0AA0
– – 6SL3320-1TG41-0AA3 6SL3325-1TG41-0AA3 1000 1025 6SL3000-2AH41-1AA0
6SL3325-1TG41-0AA7
– – 6SL3320-1TG41-3AA3 6SL3325-1TG41-3AA3 1200 1270 6SL3000-2AH41-3AA0
6SL3325-1TG41-3AA7

Motor reactors for Motor Modules in chassis-2 format


Suitable for Motor Module in chassis-2 Type rating Rated output current Motor reactor
format at 400 V
Air-cooled kW A Article No.
Line voltage 380 ... 480 V 3 AC
6SL3321-1TE36-6AA0 315 655 6SL3000-2AE38-4AA0
6SL3321-1TE37-4AA0 355 740 6SL3000-2AE38-4AA0
6SL3321-1TE38-1AA0 400 810 6SL3000-2AE38-4AA0
6SL3321-1TE38-8AA0 450 910 6SL3000-2AE41-4AA0
6SL3321-1TE41-0AA0 500 975 6SL3000-2DE41-4DA0
6SL3321-1TE41-1AA0 560 1075 6SL3000-2DE41-4DA0
6SL3321-1TE41-2AA0 630 1200 6SL3000-2DE41-4DA0
6SL3321-1TE41-3AA0 710 1325 6SL3000-2DE41-4DA0
6SL3321-1TE41-5AA0 800 1495 6SL3000-2DE41-4DA0

5/30 Siemens D 21.3 · 2022


© Siemens 2022

System components for SINAMICS S120 Chassis and Chassis-2 Units


System components
Motor-side power components > Motor reactors

■ Technical specifications
Line voltage 380 ... 480 V 3 AC Motor reactor (for pulse frequencies of 2 kHz to 4 kHz)
6SL3000- 6SL3000- 6SL3000- 6SL3000- 6SL3000-
2BE32-1AA0 2BE32-6AA0 2BE33-2AA0 2BE33-8AA0 2BE35-0AA0
Rated current A 210 260 310 380 490
1)
Power loss, max. kW 0.486 0.5 0.47 0.5 0.5
Load connection 1 × hole for M10 1 × hole for M10 1 × hole for M10 1 × hole for M10 1 × hole for M12
PE connection M8 screw M8 screw M8 screw M8 screw M8 screw
Cable length, max.
between motor reactor and motor
(number of reactors in series) (1) (2) (1) (2) (1) (2) (1) (2) (1) (2)
• Shielded m (ft) 300 (984) 525 300 (984) 525 300 (984) 525 300 (984) 525 300 (984) 525
(1722) (1722) (1722) (1722) (1722)
• Unshielded m (ft) 450 787 450 787 450 787 450 787 450 787
(1476) (2582) (1476) (2582) (1476) (2582) (1476) (2582) (1476) (2582)
Degree of protection IP00 IP00 IP00 IP00 IP00
Dimensions
• Width mm (in) 300 (11.8) 300 (11.8) 300 (11.8) 300 (11.8) 300 (11.8)
• Height mm (in) 285 (11.2) 315 (12.4) 285 (11.2) 285 (11.2) 365 (14.4)
• Depth mm (in) 257 (10.1) 277 (10.9) 257 (10.1) 277 (10.9) 277 (10.9)
Weight, approx. kg (lb) 66 (146) 66 (146) 66 (146) 73 (161) 100 (220)
Suitable for Power Module 6SL3310- 6SL3310- 6SL3310- 6SL3310- 6SL3310-
1TE32-1AA3
6SL3315-
1TE32-6AA3
6SL3315-
1TE33-1AA3
6SL3315-
1TE33-8AA3 1TE35-0AA3
6SL3315-
5
1TE32-1AA3 1TE32-6AA3 1TE33-1AA3 1TE35-0AA3
Suitable for Motor Module 6SL3320- 6SL3320- 6SL3320- 6SL3320- 6SL3320-
1TE32-1AA3 1TE32-6AA3 1TE33-1AA3 1TE33-8AA3 1TE35-0AA3
6SL3325- 6SL3325- 6SL3325- 6SL3325-
1TE32-1AA3 1TE32-6AA3 1TE33-1AA3 1TE35-0AA3
• Rated output current of A 210 260 310 380 490
Motor Module

Line voltage 380 ... 480 V 3 AC Motor reactor (for pulse frequencies of 1.25 kHz to 2.5 kHz)
6SL3000- 6SL3000-2AE38-4AA0 6SL3000- 6SL3000-2AE41-4AA0
2AE36-1AA0 2AE41-0AA0
Rated current A 605 745 840 985 1260 1405
Power loss, max. 1) kW 0.9 0.84 0.943 1.062 0.9 1.054
Load connection 1 × hole for M12 1 × hole for M12 1 × hole for M12 1 × hole for M12 2 × hole for M12 2 × hole for M12
PE connection M10 screw M10 screw M10 screw M10 screw M10 screw M10 screw
Cable length, max.
between motor reactor and motor
(number of reactors in series) (1) (2) (1) (2) (1) (2) (1) (2) (1) (2) (1) (2)
• Shielded m (ft) 300 525 300 525 300 525 300 525 300 525 300 525
(984) (1722) (984) (1722) (984) (1722) (984) (1722) (984) (1722) (984) (1722)
• Unshielded m (ft) 450 787 450 787 450 787 450 787 450 787 450 787
(1476) (2582) (1476) (2582) (1476) (2582) (1476) (2582) (1476) (2582) (1476) (2582)
Degree of protection IP00 IP00 IP00 IP00 IP00 IP00
Dimensions
• Width mm (in) 410 (16.1) 410 (16.1) 410 (16.1) 410 (16.1) 460 (18.1) 460 (18.1)
• Height mm (in) 392 (15.4) 392 (15.4) 392 (15.4) 392 (15.4) 392 (15.4) 392 (15.4)
• Depth mm (in) 292 (11.5) 292 (11.5) 292 (11.5) 302 (11.9) 326 (12.8) 326 (12.8)
Weight, approx. kg (lb) 130 (287) 140 (309) 140 (309) 146 (322) 179 (395) 179 (395)
Suitable for Power Module 6SL3315- 6SL3315- – – – –
1TE36-1AA7 1TE37-5AA7
Suitable for Motor Module 6SL3320- 6SL3320- 6SL3320- 6SL3320- 6SL3320- 6SL3320-
1TE36-1AA3 1TE37-5AA3 1TE38-4AA3 1TE41-0AA3 1TE41-2AA3 1TE41-4AA3
6SL3325- 6SL3325- 6SL3325- 6SL3325- 6SL3325- 6SL3325-
1TE36-1AA3 1TE37-5AA3 1TE38-4AA3 1TE41-0AA3 1TE41-2AA3 1TE41-4AA3
6SL3325- 6SL3325- 6SL3325- 6SL3325-
1TE37-5AA7 1TE41-0AA7 1TE41-2AA7 1TE41-4AA7
6SL3325-
1TE41-4AS3 2)
• Rated output current of the A 605 745 840 985 1260 1405
Motor Module

1) The specified power loss represents the maximum value at 100 % 2) This Motor Module has been specifically designed for loads demanding
utilization. The value is lower under normal operating conditions. a high dynamic performance.

Siemens D 21.3 · 2022 5/31


© Siemens 2022

System components for SINAMICS S120 Chassis and Chassis-2 Units


System components
Motor-side power components > Motor reactors

■ Technical specifications
Line voltage 380 ... 480 V 3 AC Motor reactor (for pulse frequencies 2.5 kHz)
6SL3000-2AE38-4AA0 6SL3000- 6SL3000-2DE41-4DA0
2AE41-4AA0
Rated current A 840 1405 1405
Power loss, max. 1)
• At 50 Hz kW 0.75 0.946 1.111
• At 150 Hz kW 0.84 1.054 1.23
Load connection M12 2 x M12 2 × M12
PE connection M10 M6 M6
Cable length, max.
between motor reactor and motor
(number of reactors in series) (1) (2) (1) (2) (1) (2)
• Shielded m (ft) 300 (984) 450 (1476) 300 (984) 450 300 (984) 450 (1476)
(1476)
• Unshielded m (ft) 450 675 (2215) 450 675 450 675 (2215)
(1476) (1476) (2215) (1476)
Degree of protection IP00 IP00 IP00
Dimensions
• Width mm (in) 410 (16.1) 460 (18.1) 445 (17.5)
• Height mm (in) 392 (15.4) 392 (15.4) 385 (15.2)
• Depth mm (in) 292 (11.5) 326 (12.8) 312 (12.3)

5 Weight, approx.
Suitable for Motor Module in
kg (lb) 140 (309)
6SL3321- 6SL3321-
179 (395)
6SL3321- 6SL3321-
158 (348)
6SL3321- 6SL3321- 6SL3321- 6SL3321- 6SL3321-
chassis-2 format 1TE36- 1TE37- 1TE38- 1TE38-8AA0 1TE41- 1TE41- 1TE41- 1TE41- 1TE41-
6AA0 4AA0 1AA0 0AA0 1AA0 2AA0 3AA0 5AA0
• Rated output current of the A 655 740 810 910 975 1075 1200 1325 1495
Motor Module

Line voltage 500 ... 690 V 3 AC Motor reactor (for pulse frequencies of 1.25 kHz to 2.5 kHz)
6SL3000-2AH31-0AA0 6SL3000-2AH31-5AA0 6SL3000- 6SL3000-
2AH31-8AA0 2AH32-4AA0
Rated current A 85 100 120 150 175 215
Power loss, max. 1) kW 0.257 0.3 0.318 0.335 0.4 0.425
Load connection Flat connector Flat connector Flat connector Flat connector Flat connector Flat connector
for M10 screw for M10 screw for M10 screw for M10 screw for M10 screw for M10 screw
PE connection M6 screw M6 screw M6 screw M6 screw M6 screw M6 screw
Cable length, max.
between motor reactor and motor
(number of reactors in series) (1) (2) (1) (2) (1) (2) (1) (2) (1) (2) (1) (2)
• Shielded m (ft) 300 525 300 525 300 525 300 525 300 525 300 525
(984) (1722) (984) (1722) (984) (1722) (984) (1722) (984) (1722) (984) (1722)
• Unshielded m (ft) 450 787 450 787 450 787 450 787 450 787 450 787
(1476) (2582) (1476) (2582) (1476) (2582) (1476) (2582) (1476) (2582) (1476) (2582)
Degree of protection IP00 IP00 IP00 IP00 IP00 IP00
Dimensions
• Width mm (in) 270 (10.6) 270 (10.6) 270 (10.6) 270 (10.6) 300 (11.8) 300 (11.8)
• Height mm (in) 248 (9.76) 248 (9.76) 248 (9.76) 248 (9.76) 285 (11.2) 285 (11.2)
• Depth mm (in) 200 (7.87) 200 (7.87) 200 (7.87) 200 (7.87) 212 (8.35) 212 (8.35)
Weight, approx. kg (lb) 25 (55.1) 25 (55.1) 25.8 (56.9) 25.8 (56.9) 34 (75.0) 34 (75.0)
Suitable for Motor Module 6SL3320- 6SL3320- 6SL3320- 6SL3320- 6SL3320- 6SL3320-
1TG28-5AA3 1TG31-0AA3 1TG31-2AA3 1TG31-5AA3 1TG31-8AA3 1TG32-2AA3
6SL3325- 6SL3325- 6SL3325-
1TG31-0AA3 1TG31-5AA3 1TG32-2AA3
• Rated output current of the A 85 100 120 150 175 215
Motor Module

1)
The specified power loss represents the maximum value at 100 %
utilization. The value is lower under normal operating conditions.

5/32 Siemens D 21.3 · 2022


© Siemens 2022

System components for SINAMICS S120 Chassis and Chassis-2 Units


System components
Motor-side power components > Motor reactors

■ Technical specifications
Line voltage 500 ... 690 V 3 AC Motor reactor (for pulse frequencies of 1.25 kHz to 2.5 kHz)
6SL3000- 6SL3000- 6SL3000- 6SL3000- 6SL3000- 6SL3000-
2AH32-6AA0 2AH33-6AA0 2AH34-5AA0 2AH34-7AA0 2AH35-8AA0 2AH38-1AA0
Rated current A 260 330 410 465 575 735
Power loss, max. 1) kW 0.44 0.45 0.545 0.72 0.8 0.96
Load connection Flat connector Flat connector Flat connector Flat connector Flat connector Flat connector
for M10 screw for M10 screw for M12 screw for M12 screw for M12 screw for M12 screw
PE connection M6 screw M6 screw M8 screw M8 screw M8 screw M8 screw
Cable length, max.
between motor reactor and motor
(number of reactors in series) (1) (2) (1) (2) (1) (2) (1) (2) (1) (2) (1) (2)
• Shielded m (ft) 300 525 300 525 300 525 300 525 300 525 300 525
(984) (1722) (984) (1722) (984) (1722) (984) (1722) (984) (1722) (984) (1722)
• Unshielded m (ft) 450 787 450 787 450 787 450 787 450 787 450 787
(1476) (2582) (1476) (2582) (1476) (2582) (1476) (2582) (1476) (2582) (1476) (2582)
Degree of protection IP00 IP00 IP00 IP00 IP00 IP00
Dimensions
• Width mm (in) 300 (11.8) 300 (11.8) 350 (13.8) 410 (16.1) 410 (16.1) 410 (16.1)
• Height mm (in) 285 (11.2) 285 (11.2) 330 (13.0) 392 (15.4) 392 (15.4) 392 (15.4)
• Depth mm (in) 212 (8.35) 212 (8.35) 215 (8.46) 292 (11.5) 292 (11.5) 279 (11.0)
Weight, approx. kg (lb) 40 (88.2) 46 (101) 68 (150) 80 (176) 80 (176) 146 (322)
Suitable for Power Module – – 6SL3315-1TG34- 6SL3315-1TG34- 6SL3315-1TG35- –
1AA7 7AA7 8AA7
5
Suitable for Motor Module 6SL3320- 6SL3320- 6SL3320- 6SL3320- 6SL3320- 6SL3320-
1TG32-6AA3 1TG33-3AA3 1TG34-1AA3 1TG34-7AA3 1TG35-8AA3 1TG37-4AA3
6SL3325- 6SL3325- 6SL3325- 6SL3325-
1TG33-3AA3 1TG34-7AA3 1TG35-8AA3 1TG37-4AA3
6SL3325- 6SL3325-
1TG34-7AA7 1TG35-8AA7
• Rated output current of the A 260 330 410 465 575 735
Motor Module

Line voltage 500 ... 690 V 3 AC Motor reactor (for pulse frequencies of 1.25 kHz to 2.5 kHz)
6SL3000-2AH38-1AA0 6SL3000-2AH41-0AA0 6SL3000-2AH41-1AA0 6SL3000-2AH41-3AA0
Rated current A 810 910 1025 1270
Power loss, max. 1) kW 1.0 0.97 1.05 0.95
Load connection Flat connector for M12 Flat connector for M12 Flat connector for M12 Flat connector for M12
screw screw screw screw
PE connection M8 screw M8 screw M8 screw M8 screw
Cable length, max.
between motor reactor and motor
(number of reactors in series) (1) (2) (1) (2) (1) (2) (1) (2)
• Shielded m (ft) 300 (984) 525 (1722) 300 (984) 525 (1722) 300 (984) 525 (1722) 300 (984) 525 (1722)
• Unshielded m (ft) 450 (1476) 787 (2582) 450 (1476) 787 (2582) 450 (1476) 787 (2582) 450 (1476) 787 (2582)
Degree of protection IP00 IP00 IP00 IP00
Dimensions
• Width mm (in) 410 (16.1) 410 (16.1) 410 (16.1) 460 (18.1)
• Height mm (in) 392 (15.4) 392 (15.4) 392 (15.4) 392 (15.4)
• Depth mm (in) 279 (11.0) 279 (11.0) 317 (12.5) 296 (11.7)
Weight, approx. kg (lb) 146 (322) 150 (331) 163 (359) 153 (337)
Suitable for Motor Module 6SL3320-1TG38-1AA3 6SL3320-1TG38-8AA3 6SL3320-1TG41-0AA3 6SL3320-1TG41-3AA3
6SL3325-1TG38-0AA3 6SL3325-1TG41-0AA3 6SL3325-1TG41-3AA3
6SL3325-1TG38-1AA3 6SL3325-1TG41-0AA7 6SL3325-1TG41-3AA7
6SL3325-1TG38-1AA7
• Rated output current of the A 810 910 1025 1270
Motor Module

1)
The specified power loss represents the maximum value at 100 %
utilization. The value is lower under normal operating conditions.

Siemens D 21.3 · 2022 5/33


© Siemens 2022

System components for SINAMICS S120 Chassis and Chassis-2 Units


System components
Motor-side power components > dv/dt filter plus VPL

■ Overview ■ Design
The dv/dt filter plus VPL consists of two components, which are
also supplied as separate mechanical units:
• dv/dt reactor
• Voltage limiting network, which cuts off the voltage peaks and
feeds the energy back to the DC link.

dv/dt filter plus VPL (Voltage Peak Limiter) limit the voltage rate
of rise dv/dt to values < 500 V/s and the typical peak voltage to
the following values in accordance with the limit value curve
according to IEC/TS 60034-17: 2006:

5 < 1000 V at Uline < 575 V


< 1250 V at 660 V < Uline < 690 V
Standard motors with standard insulation and without insulated
bearings with a supply voltage of up to 690 V can be used for
converter operation if a dv/dt filter plus VPL is used.
dv/dt filters plus VPL are designed for the following maximum
motor cable lengths:
• Shielded cables: 300 m (e.g. Protodur NYCWY)
• Unshielded cables: 450 m (e.g. Protodur NYY)
For shorter cable lengths (100 m shielded, 150 m unshielded),
see also dv/dt filter compact plus VPL.
Notice:
The maximum permissible cable length between the dv/dt filter
plus VPL and the Power Module/Motor Module is 5 m.

5/34 Siemens D 21.3 · 2022


© Siemens 2022

System components for SINAMICS S120 Chassis and Chassis-2 Units


System components
Motor-side power components > dv/dt filter plus VPL

■ Selection and ordering data


dv/dt filter plus VPL for Motor Modules in chassis format
Suitable for Power Module Suitable for Motor Module Type Rated dv/dt filter plus VPL
rating output
at 400 V/ current
690 V
Air-cooled Liquid-cooled/ Air-cooled Liquid-cooled/ kW A Article No.
water-cooled water-cooled
Line voltage 380 ... 480 V 3 AC
6SL3310-1TE32-1AA3 6SL3315-1TE32-1AA3 6SL3320-1TE32-1AA3 6SL3325-1TE32-1AA3 110 210 6SL3000-2DE32-6AA0
6SL3310-1TE32-6AA3 6SL3315-1TE32-6AA3 6SL3320-1TE32-6AA3 6SL3325-1TE32-6AA3 132 260
6SL3310-1TE33-1AA3 6SL3315-1TE33-1AA3 6SL3320-1TE33-1AA3 6SL3325-1TE33-1AA3 160 310 6SL3000-2DE35-0AA0
6SL3310-1TE33-8AA3 – 6SL3320-1TE33-8AA3 – 200 380
6SL3310-1TE35-0AA3 6SL3315-1TE35-0AA3 6SL3320-1TE35-0AA3 6SL3325-1TE35-0AA3 250 490
– – 6SL3320-1TE36-1AA3 6SL3325-1TE36-1AA3 315 605 6SL3000-2DE38-4AA0
– – 6SL3320-1TE37-5AA3 6SL3325-1TE37-5AA3 400 745
6SL3325-1TE37-5AA7
– – 6SL3320-1TE38-4AA3 6SL3325-1TE38-4AA3 450 840
– – 6SL3320-1TE41-0AA3 6SL3325-1TE41-0AA3 560 985 6SL3000-2DE41-4AA0
6SL3325-1TE41-0AA7
– – 6SL3320-1TE41-2AA3 6SL3325-1TE41-2AA3 710 1260

– – 6SL3320-1TE41-4AA3
6SL3325-1TE41-2AA7
6SL3325-1TE41-4AA3 800 1405
5
6SL3325-1TE41-4AA7
6SL3325-1TE41-4AS3 1) 800 1330
Line voltage 500 ... 690 V 3 AC
– – 6SL3320-1TG28-5AA3 – 75 85 6SL3000-2DH31-0AA0
– – 6SL3320-1TG31-0AA3 6SL3325-1TG31-0AA3 90 100
– – 6SL3320-1TG31-2AA3 – 110 120 6SL3000-2DH31-5AA0
– – 6SL3325-1TG31-5AA3 6SL3320-1TG31-5AA3 132 150
– – 6SL3320-1TG31-8AA3 – 160 175 6SL3000-2DH32-2AA0
– – 6SL3320-1TG32-2AA3 6SL3325-1TG32-2AA3 200 215
– – 6SL3320-1TG32-6AA3 – 250 260 6SL3000-2DH33-3AA0
– – 6SL3320-1TG33-3AA3 6SL3325-1TG33-3AA3 315 330
– – 6SL3320-1TG34-1AA3 – 400 410 6SL3000-2DH34-1AA0
– – 6SL3320-1TG34-7AA3 6SL3325-1TG34-7AA3 450 465 6SL3000-2DH35-8AA0
6SL3325-1TG34-7AA7
– – 6SL3320-1TG35-8AA3 6SL3325-1TG35-8AA3 560 575
6SL3325-1TG35-8AA7
– – 6SL3320-1TG37-4AA3 6SL3325-1TG37-4AA3 710 735 6SL3000-2DH38-1AA0
– – 6SL3320-1TG38-1AA3 6SL3325-1TG38-0AA3 800 810
6SL3325-1TG38-1AA3
6SL3325-1TG38-1AA7
– – 6SL3320-1TG38-8AA3 – 900 910 6SL3000-2DH41-3AA0
– – 6SL3320-1TG41-0AA3 6SL3325-1TG41-0AA3 1000 1025
6SL3325-1TG41-0AA7
– – 6SL3320-1TG41-3AA3 6SL3325-1TG41-3AA3 1200 1270
6SL3325-1TG41-3AA7

1)
This Motor Module has been specifically designed for loads demanding
a high dynamic performance.

Siemens D 21.3 · 2022 5/35


© Siemens 2022

System components for SINAMICS S120 Chassis and Chassis-2 Units


System components
Motor-side power components > dv/dt filter plus VPL

■ Selection and ordering data


dv/dt filter plus VPL for Motor Modules in chassis-2 format
Suitable for Motor Module Type rating Rated output current dv/dt filter plus VPL
in chassis-2 format at 400 V
Air-cooled kW A Article No.
Line voltage 380 ... 480 V 3 AC
6SL3321-1TE36-6AA0 315 655 6SL3000-2DE38-4AA0
6SL3321-1TE37-4AA0 355 740 6SL3000-2DE41-4AA0
6SL3321-1TE38-1AA0 400 810 6SL3000-2DE41-4AA0
6SL3321-1TE38-8AA0 450 910 6SL3000-2DE41-4AA0
6SL3321-1TE41-0AA0 500 975 6SL3000-2DE41-4AA0
6SL3321-1TE41-1AA0 560 1075 6SL3000-2DE41-4AA0
6SL3321-1TE41-2AA0 630 1200 6SL3000-2DE41-4AA0

5/36 Siemens D 21.3 · 2022


© Siemens 2022

System components for SINAMICS S120 Chassis and Chassis-2 Units


System components
Motor-side power components > dv/dt filter plus VPL

■ Technical specifications
Line voltage 380 ... 480 V 3 AC dv/dt filter plus VPL
6SL3000-2DE32-6AA0 6SL3000-2DE35-0AA0 6SL3000-2DE38-4AA0 6SL3000-2DE41-4AA0 1)
Ith max A 260 490 840 1405
Degree of protection IP00 IP00 IP00 IP00
Cable length, max.
between dv/dt filter and motor 2)
• Shielded m (ft) 300 (984) 300 (984) 300 (984) 300 (984)
• Unshielded m (ft) 450 (1476) 450 (1476) 450 (1476) 450 (1476)
Conformity CE CE CE CE
Certificate of suitability cURus cURus cURus cURus
dv/dt reactor
Power loss, max. 3)
• At 50 Hz 400 V kW 0.701 0.874 1.106 1.111
• At 60 Hz 460 V kW 0.729 0.904 1.115 1.154
• At 150 Hz 400 V kW 0.78 0.963 1.226 1.23
Connections
• To the Power Module/Motor Module 1 × hole for M10 1 × hole for M12 1 × hole for M12 2 × hole for M12
• To load 1 × hole for M10 1 × hole for M12 1 × hole for M12 2 × hole for M12
• PE M6 screw M6 screw M6 screw M6 screw
Dimensions
• Width
• Height
mm (in)
mm (in)
410 (16.1)
370 (14.6)
460 (18.1)
370 (14.6)
460 (18.1)
385 (15.2)
445 (17.5)
385 (15.2) 5
• Depth mm (in) 229 (9.02) 275 (10.8) 312 (12.3) 312 (12.3)
Weight, approx. kg (lb) 66 (146) 122 (269) 149 (328) 158 (348)
Voltage Peak Limiter (VPL)
Power loss, max.
• At 50 Hz 400 V kW 0.029 0.042 0.077 0.134
• At 60 Hz 460 V kW 0.027 0.039 0.072 0.125
• At 150 Hz 400 V kW 0.025 0.036 0.066 0.114
Connections
• To dv/dt reactor M8 nut 70 mm2 terminals 1 × hole for M8 1 × hole for M10
• To DC link M8 nut 70 mm2 terminals 1 × hole for M8 1 × hole for M10
• PE M8 stud 35 mm2 terminals M8 stud M8 stud
Dimensions
• Width mm (in) 265 (10.4) 392 (15.4) 309 (12.2) 309 (12.2)
• Height mm (in) 263 (10.4) 285 (11.2) 1313 (51.7) 1313 (51.7)
• Depth mm (in) 190 (7.48) 210 (8.27) 400 (15.7) 400 (15.7)
Weight, approx. kg (lb) 6 (13.2) 16 (35.3) 48 (106) 72 (159)
Suitable for Power Module 6SL3310-1TE32-1AA3 6SL3310-1TE33-1AA3 6SL3315-1TE36-1AA7 –
6SL3315-1TE32-1AA3 6SL3315-1TE33-1AA3 6SL3315-1TE37-5AA7
6SL3310-1TE32-6AA3 6SL3310-1TE33-8AA3
6SL3315-1TE32-6AA3 6SL3310-1TE35-0AA3
6SL3315-1TE35-0AA3
Suitable for Motor Module 6SL3320-1TE32-1AA3 6SL3320-1TE33-1AA3 6SL3320-1TE36-1AA3 6SL3320-1TE41-0AA3
6SL3325-1TE32-1AA3 6SL3325-1TE33-1AA3 6SL3325-1TE36-1AA3 6SL3325-1TE41-0AA3
6SL3320-1TE32-6AA3 6SL3320-1TE33-8AA3 6SL3320-1TE37-5AA3 6SL3325-1TE41-0AA7
6SL3325-1TE32-6AA3 6SL3320-1TE35-0AA3 6SL3325-1TE37-5AA3 6SL3320-1TE41-2AA3
6SL3325-1TE35-0AA3 6SL3325-1TE37-5AA7 6SL3325-1TE41-2AA3
6SL3320-1TE38-4AA3 6SL3325-1TE41-2AA7
6SL3325-1TE38-4AA3 6SL3320-1TE41-4AA3
6SL3321-1TE36-6AA0 6SL3325-1TE41-4AA3
6SL3325-1TE41-4AA7
6SL3325-1TE41-4AS3 2)
6SL3321-1TE37-4AA0
6SL3321-1TE38-1AA0
6SL3321-1TE38-8AA0
6SL3321-1TE41-0AA0
6SL3321-1TE41-1AA0
6SL3321-1TE41-2AA0

1) 2)
These dv/dt filters include two dv/dt reactors. The technical specifications Longer cable lengths for specific configurations are available on request.
listed refer to a dv/dt reactor. 3)
This Motor Module has been specifically designed for loads demanding
For additional information on dv/dt filters, please refer to the SINAMICS Low a high dynamic performance.
Voltage Engineering Manual.

Siemens D 21.3 · 2022 5/37


© Siemens 2022

System components for SINAMICS S120 Chassis and Chassis-2 Units


System components
Motor-side power components > dv/dt filter plus VPL

■ Technical specifications
Line voltage 500 ... 690 V 3 AC dv/dt filter plus VPL
6SL3000-2DH31-0AA0 6SL3000-2DH31-5AA0 6SL3000-2DH32-2AA0 6SL3000-2DH33-3AA0
Ith max A 100 150 215 330
Degree of protection IP00 IP00 IP00 IP00
Cable length, max.
between dv/dt filter and motor 1)
• Shielded m (ft) 300 (984) 300 (984) 300 (984) 300 (984)
• Unshielded m (ft) 450 (1476) 450 (1476) 450 (1476) 450 (1476)
Conformity CE CE CE CE
Certificate of suitability 2) cURus cURus cURus cURus
dv/dt reactor
Power loss, max.
• At 50 Hz 500/690 V kW 0.49 0.389 0.578 0.595
• At 60 Hz 575 V kW 0.508 0.408 0.604 0.62
• At 150 Hz 500/690 V kW 0.541 0.436 0.645 0.661
Connections
• To the Power Module/Motor Module 1 × hole for M10 1 × hole for M10 1 × hole for M10 1 × hole for M10
• To load 1 × hole for M10 1 × hole for M10 1 × hole for M10 1 × hole for M10
• PE M6 screw M6 screw M6 screw M6 screw
Dimensions

5 • Width
• Height
mm (in)
mm (in)
350 (13.8)
320 (12.6)
350 (13.8)
320 (12.6)
460 (18.1)
360 (14.2)
460 (18.1)
360 (14.2)
• Depth mm (in) 227 (8.94) 227 (8.94) 275 (10.8) 275 (10.8)
Weight, approx. kg (lb) 48 (106) 50 (110) 83 (183) 135 (298)
Voltage Peak Limiter (VPL)
Power loss, max.
• At 50 Hz 500/690 V kW 0.016 0.02 0.032 0.042
• At 60 Hz 575 V kW 0.015 0.019 0.03 0.039
• At 150 Hz 500/690 V kW 0.013 0.018 0.027 0.036
Connections
• To dv/dt reactor M8 nut M8 nut 70 mm2 terminals 70 mm2 terminals
• To DC link M8 nut M8 nut 70 mm2 terminals 70 mm2 terminals
• PE M8 stud M8 stud 35 mm2 terminals 35 mm2 terminals
Dimensions
• Width mm (in) 263 (10.4) 263 (10.4) 392 (15.4) 392 (15.4)
• Height mm (in) 265 (10.4) 265 (10.4) 285 (11.2) 285 (11.2)
• Depth mm (in) 188 (7.40) 188 (7.40) 210 (8.27) 210 (8.27)
Weight, approx. kg (lb) 6 (13.2) 6 (13.2) 16 (35.3) 16 (35.3)
Suitable for Motor Module 6SL3320-1TG28-5AA3 6SL3320-1TG31-2AA3 6SL3320-1TG31-8AA3 6SL3320-1TG32-6AA3
6SL3320-1TG31-0AA3 6SL3320-1TG31-5AA3 6SL3320-1TG32-2AA3 6SL3320-1TG33-3AA3
6SL3325-1TG31-0AA3 6SL3325-1TG31-5AA3 6SL3325-1TG32-2AA3 6SL3325-1TG33-3AA3

1) Longer cable lengths for specific configurations are available on request.


2) Only for line voltages 500 ... 600 V 3 AC.

5/38 Siemens D 21.3 · 2022


© Siemens 2022

System components for SINAMICS S120 Chassis and Chassis-2 Units


System components
Motor-side power components > dv/dt filter plus VPL

■ Technical specifications
Line voltage 500 ... 690 V 3 AC dv/dt filter plus VPL
6SL3000-2DH34-1AA0 6SL3000-2DH35-8AA0 6SL3000-2DH38-1AA0 1) 6SL3000-2DH41-3AA0 1)
Ith max A 410 575 810 1270
Degree of protection IP00 IP00 IP00 IP00
Cable length, max.
between dv/dt filter and motor 2)
• Shielded m (ft) 300 (984) 300 (984) 300 (984) 300 (984)
• Unshielded m (ft) 450 (1476) 450 (1476) 450 (1476) 450 (1476)
Conformity CE CE CE CE
Certificate of suitability 3) cURus cURus cURus cURus
dv/dt reactor
Power loss, max.
• At 50 Hz 500/690 V kW 0.786 0.862 0.828 0.865
• At 60 Hz 575 V kW 0.826 0.902 0.867 0.904
• At 150 Hz 500/690 V kW 0.884 0.964 0.927 0.966
Connections
• To the Power Module/Motor Module 1 × hole for M12 1 × hole for M12 2 × hole for M12 2 × hole for M12
• To load 1 × hole for M12 1 × hole for M12 2 × hole for M12 2 × hole for M12
• PE M6 screw M6 screw M6 screw M6 screw
Dimensions
• Width
• Height
mm (in)
mm (in)
460 (18.1)
385 (15.2)
460 (18.1)
385 (15.2)
445 (17.5)
385 (15.2)
445 (17.5)
385 (15.2) 5
• Depth mm (in) 312 (12.3) 312 (12.3) 312 (12.3) 312 (12.3)
Weight, approx. kg (lb) 147 (324) 172 (379) 160 (353) 164 (362)
Voltage Peak Limiter (VPL)
Power loss, max.
• At 50 Hz 500/690 V kW 0.051 0.063 0.106 0.15
• At 60 Hz 575 V kW 0.048 0.059 0.1 0.14
• At 150 Hz 500/690 V kW 0.043 0.054 0.091 0.128
Connections
• To dv/dt reactor 1 × hole for M8 1 × hole for M8 1 × hole for M10 1 × hole for M10
• To DC link 1 × hole for M8 1 × hole for M8 1 × hole for M10 1 × hole for M10
• PE M8 stud M8 stud M8 stud M8 stud
Dimensions
• Width mm (in) 309 (12.2) 309 (12.2) 309 (12.2) 309 (12.2)
• Height mm (in) 1313 (51.7) 1313 (51.7) 1313 (51.7) 1313 (51.7)
• Depth mm (in) 400 (15.7) 400 (15.7) 400 (15.7) 400 (15.7)
Weight, approx. kg (lb) 48 (106) 48 (106) 72 (159) 73 (161)
Suitable for Power Module 6SL3315-1TG34-1AA7 6SL3315-1TG34-7AA7 – –
6SL3315-1TG35-8AA7
Suitable for Motor Module 6SL3320-1TG34-1AA3 6SL3320-1TG34-7AA3 6SL3320-1TG37-4AA3 6SL3320-1TG38-8AA3
6SL3325-1TG34-7AA3 6SL3325-1TG37-4AA3 6SL3320-1TG41-0AA3
6SL3325-1TG34-7AA7 6SL3320-1TG38-1AA3 6SL3325-1TG41-0AA3
6SL3320-1TG35-8AA3 6SL3325-1TG38-0AA3 6SL3325-1TG41-0AA7
6SL3325-1TG35-8AA3 6SL3325-1TG38-1AA3 6SL3320-1TG41-3AA3
6SL3325-1TG35-8AA7 6SL3325-1TG38-1AA7 6SL3325-1TG41-3AA3
6SL3325-1TG41-3AA7

1) 2)
These dv/dt filters include two dv/dt reactors. The technical specifications Longer cable lengths for specific configurations are available on request.
listed refer to a dv/dt reactor. 3)
Only for line voltages 500 ... 600 V 3 AC.
For additional information on dv/dt filters, please refer to the SINAMICS Low
Voltage Engineering Manual.

Siemens D 21.3 · 2022 5/39


© Siemens 2022

System components for SINAMICS S120 Chassis and Chassis-2 Units


System components
Motor-side power components > dv/dt filter compact plus VPL

■ Overview ■ Design
The dv/dt filter compact plus VPL consists of two components,
which are supplied together as a compact mechanical unit:
• dv/dt reactor
• Voltage limiting network, which cuts off the voltage peaks and
feeds the energy back to the DC link.

dv/dt filters compact plus VPL (Voltage Peak Limiter) limit the
voltage rate of rise dv/dt to values of < 1600 V/s and the typical
peak voltage to the following values in accordance with the limit
value curve A according to IEC 60034-25: 2007:

5 < 1150 V at Uline < 575 V


< 1400 V at 660 V < Uline < 690 V
Standard motors with standard insulation and without insulated
bearings with a supply voltage of up to 690 V can be used for
converter operation if a dv/dt filter compact plus VPL is used.
dv/dt filters compact plus VPL are designed for the following
maximum motor cable lengths:
• Shielded cables: 100 m (e.g. Protodur NYCWY)
• Unshielded cables: 150 m (e.g. Protodur NYY)
For longer cable lengths (> 100 m shielded, > 150 m
unshielded) refer to dv/dt filter plus VPL.
Notice:
• The max. permissible cable length between the dv/dt filter and
Motor Module is 5 m
• Operation with output frequencies < 10 Hz is permissible for
max. 5 min.

5/40 Siemens D 21.3 · 2022


© Siemens 2022

System components for SINAMICS S120 Chassis and Chassis-2 Units


System components
Motor-side power components > dv/dt filter compact plus VPL

■ Selection and ordering data


dv/dt filter plus VPL for Motor Modules in chassis format
Suitable for Power Module Suitable for Motor Module Type rating dv/dt filter
at 400 V/ 690 V compact plus VPL
Air-cooled Liquid-cooled Air-cooled Liquid-cooled/ kW Article No.
water-cooled
Line voltage 380 ... 480 V 3 AC
6SL3310-1TE32-1AA3 6SL3315-1TE32-1AA3 6SL3320-1TE32-1AA3 6SL3325-1TE32-1AA3 110 6SL3000-2DE32-6EA0
6SL3310-1TE32-6AA3 6SL3315-1TE32-6AA3 6SL3320-1TE32-6AA3 6SL3325-1TE32-6AA3 132
6SL3310-1TE33-1AA3 6SL3315-1TE33-1AA3 6SL3320-1TE33-1AA3 6SL3325-1TE33-1AA3 160 6SL3000-2DE35-0EA0
6SL3310-1TE33-8AA3 – 6SL3320-1TE33-8AA3 – 200
6SL3310-1TE35-0AA3 6SL3315-1TE35-0AA3 6SL3320-1TE35-0AA3 6SL3325-1TE35-0AA3 250
– – 6SL3320-1TE36-1AA3 6SL3325-1TE36-1AA3 315 6SL3000-2DE38-4EA0
– – 6SL3320-1TE37-5AA3 6SL3325-1TE37-5AA3 400
6SL3325-1TE37-5AA7
– – 6SL3320-1TE38-4AA3 6SL3325-1TE38-4AA3 450
– – 6SL3320-1TE41-0AA3 6SL3325-1TE41-0AA3 560 6SL3000-2DE41-4EA0
6SL3325-1TE41-0AA7
– – 6SL3320-1TE41-2AA3 6SL3325-1TE41-2AA3 710
6SL3325-1TE41-2AA7
– – 6SL3320-1TE41-4AA3 6SL3325-1TE41-4AA3 800
6SL3325-1TE41-4AA7 5
6SL3325-1TE41-4AS3 800
1)

Line voltage 500 ... 690 V 3 AC


– – 6SL3320-1TG28-5AA3 – 75 6SL3000-2DG31-0EA0
– – 6SL3320-1TG31-0AA3 6SL3325-1TG31-0AA3 90
– – 6SL3320-1TG31-2AA3 – 110 6SL3000-2DG31-5EA0
– – 6SL3320-1TG31-5AA3 6SL3325-1TG31-5AA3 132
– – 6SL3320-1TG31-8AA3 – 160 6SL3000-2DG32-2EA0
– – 6SL3320-1TG32-2AA3 6SL3325-1TG32-2AA3 200
– – 6SL3320-1TG32-6AA3 – 250 6SL3000-2DG33-3EA0
– – 6SL3320-1TG33-3AA3 6SL3325-1TG33-3AA3 315
– – 6SL3320-1TG34-1AA3 – 400 6SL3000-2DG34-1EA0
– – 6SL3320-1TG34-7AA3 6SL3325-1TG34-7AA3 450 6SL3000-2DG35-8EA0
6SL3325-1TG34-7AA7
– – 6SL3320-1TG35-8AA3 6SL3325-1TG35-8AA3 560
6SL3325-1TG35-8AA7
– – 6SL3320-1TG37-4AA3 6SL3325-1TG37-4AA3 710 6SL3000-2DG38-1EA0
– – 6SL3320-1TG38-1AA3 6SL3325-1TG38-0AA3 800
– – 6SL3325-1TG38-1AA3 800
6SL3325-1TG38-1AA7
– – 6SL3320-1TG38-8AA3 – 900 6SL3000-2DG41-3EA0
– – 6SL3320-1TG41-0AA3 6SL3325-1TG41-0AA3 1000
6SL3325-1TG41-0AA7
– – 6SL3320-1TG41-3AA3 6SL3325-1TG41-3AA3 1200
6SL3325-1TG41-3AA7

1)
This Motor Module has been specifically designed for loads demanding
a high dynamic performance.

Siemens D 21.3 · 2022 5/41


© Siemens 2022

System components for SINAMICS S120 Chassis and Chassis-2 Units


System components
Motor-side power components > dv/dt filter compact plus VPL

■ Selection and ordering data


dv/dt filter compact plus VPL for Motor Modules in chassis-2 format
Suitable for Motor Module Type rating Rated output current dv/dt filter
in chassis-2 format at 400 V compact plus VPL
Air-cooled kW A Article No.
Line voltage 380 ... 480 V 3 AC
6SL3321-1TE36-6AA0 315 655 6SL3000-2DE38-4EA0
6SL3321-1TE37-4AA0 355 740 6SL3000-2DE41-4EA0
6SL3321-1TE38-1AA0 400 810 6SL3000-2DE41-4EA0
6SL3321-1TE38-8AA0 450 910 6SL3000-2DE41-4EA0
6SL3321-1TE41-0AA0 500 975 6SL3000-2DE41-4EA0
6SL3321-1TE41-1AA0 560 1075 6SL3000-2DE41-4EA0
6SL3321-1TE41-2AA0 630 1200 6SL3000-2DE41-4EA0

For additional information on dv/dt filters, please refer to the SINAMICS Low Voltage Engineering Manual.

5/42 Siemens D 21.3 · 2022


© Siemens 2022

System components for SINAMICS S120 Chassis and Chassis-2 Units


System components
Motor-side power components > dv/dt filter compact plus VPL

■ Technical specifications
Line voltage 380 ... 480 V 3 AC dv/dt filter compact plus VPL
6SL3000-2DE32-6EA0 6SL3000-2DE35-0EA0 6SL3000-2DE38-4EA0 6SL3000-2DE41-4EA0
Rated current A 260 490 840 1405
Ith max A 260 490 840 1405
Power loss, max.
• At 50 Hz 400 V kW 0.21 0.29 0.518 Reactor: 1.027
VPL: 0.127
Total: 1.154
• At 60 Hz 460 V kW 0.215 0.296 0.529 Reactor: 1.077
VPL: 0.12
Total: 1.197
• At 150 Hz 400 V kW 0.255 0.344 0.609 Reactor: 1.354
VPL: 0.09
Total: 1.444
Power connection Hole for M10 Hole for M10 Hole for M12 2 × elongated hole,
input and output side 14 × 18 mm
• Conductor cross-section, max. (IEC) Provided for busbar Provided for busbar Provided for busbar Provided for busbar
connection connection connection connection
DC link connection Threaded socket M8 Threaded socket M8 Hole for M8 Hole for M8
DCPS, DCNS
• Conductor cross-section, max. (IEC) mm2 16 25 50 95
PE/GND connection Threaded socket M6 Threaded socket M6 Threaded socket M6 Threaded socket M6
(reactor and VPL)
Motor cable length, max.
• Shielded m (ft) 100 (328) 100 (328) 100 (328) 100 (328)
5
• Unshielded m (ft) 150 (492) 150 (492) 150 (492) 150 (492)
Degree of protection IP00 IP00 IP00 IP00
Dimensions
• Width mm (in) 310 (12.2) 350 (13.8) 440 (17.3) Reactor: 430
VPL: 277
• Height mm (in) 283 (11.1) 317 (12.5) 369 (14.5) Reactor: 385
VPL: 360
• Depth mm (in) 238 (9.37) 260 (10.2) 311 (12.2) Reactor: 323
VPL: 291
Weight, approx. kg (lb) 41 (90.4) 61 (134) 103 (227) Reactor: 168.8
VPL: 19.2
Total: 188
Conformity CE CE CE CE
Certificates of suitability cURus cURus cURus cURus
Suitable for Power Module 6SL3310-1TE32-1AA3 6SL3310-1TE33-1AA3
6SL3315-1TE32-1AA3 6SL3315-1TE33-1AA3
6SL3310-1TE32-6AA3 6SL3310-1TE33-8AA3
6SL3315-1TE32-6AA3 6SL3310-1TE35-0AA3
6SL3315-1TE35-0AA3
Suitable for Motor Module 6SL3320-1TE32-1AA3 6SL3320-1TE33-1AA3 6SL3320-1TE36-1AA3 6SL3320-1TE41-0AA3
6SL3325-1TE32-1AA3 6SL3325-1TE33-1AA3 6SL3325-1TE36-1AA3 6SL3325-1TE41-0AA3
6SL3320-1TE32-6AA3 6SL3320-1TE33-8AA3 6SL3320-1TE37-5AA3 6SL3325-1TE41-0AA7
6SL3325-1TE32-6AA3 6SL3320-1TE35-0AA3 6SL3325-1TE37-5AA3 6SL3320-1TE41-2AA3
6SL3325-1TE35-0AA3 6SL3325-1TE37-5AA7 6SL3325-1TE41-2AA3
6SL3320-1TE38-4AA3 6SL3325-1TE41-2AA7
6SL3325-1TE38-4AA3 6SL3320-1TE41-4AA3
6SL3321-1TE36-6AA0 6SL3325-1TE41-4AA3
6SL3325-1TE41-4AA7
6SL3325-1TE41-4AS3 1)
6SL3321-1TE37-4AA0
6SL3321-1TE38-1AA0
6SL3321-1TE38-8AA0
6SL3321-1TE41-0AA0
6SL3321-1TE41-1AA0
6SL3321-1TE41-2AA0

1) This Motor Module has been specifically designed for loads demanding
a high dynamic performance.

Siemens D 21.3 · 2022 5/43


© Siemens 2022

System components for SINAMICS S120 Chassis and Chassis-2 Units


System components
Motor-side power components > dv/dt filter compact plus VPL

■ Technical specifications
Line voltage 500 ... 690 V 3 AC dv/dt filter compact plus VPL
6SL3000-2DG31-0EA0 6SL3000-2DG31-5EA0 6SL3000-2DG32-2EA0 6SL3000-2DG33-3EA0
Rated current A 100 150 215 330
Ith max A 100 150 215 330
Power loss, max.
• At 50 Hz 500/690 V kW 0.227 0.27 0.305 0.385
• At 60 Hz 575 V kW 0.236 0.279 0.316 0.399
• At 150 Hz 500/690 V kW 0.287 0.335 0.372 0.48
Power connection Hole for M10 Hole for M10 Hole for M10 Hole for M10
input and output side
• Conductor cross-section, max. (IEC) Provided for busbar Provided for busbar Provided for busbar Provided for busbar
connection connection connection connection
DC link connection Threaded socket M8 Threaded socket M8 Hole for M8 Hole for M8
DCPS, DCNS
• Conductor cross-section, max. (IEC) mm2 16 16 25 25
PE/GND connection Threaded socket M6 Threaded socket M6 Threaded socket M6 Threaded socket M6
Motor cable length, max.
• Shielded m (ft) 100 (328) 100 (328) 100 (328) 100 (328)
• Unshielded m (ft) 150 (492) 150 (492) 150 (492) 150 (492)
Degree of protection IP00 IP00 IP00 IP00
Dimensions
5 • Width
• Height
mm (in)
mm (in)
310 (12.2)
283 (11.1)
310 (12.2)
283 (11.1)
350 (13.8)
317 (12.5)
350 (13.8)
317 (12.5)
• Depth mm (in) 238 (9.37) 238 (9.37) 260 (10.2) 260 (10.2)
Weight, approx. kg (lb) 34 (75.0) 36 (79.4) 51 (112) 60 (132)
Conformity CE CE CE CE
Certificate of suitability 1) cURus cURus cURus cURus
Suitable for Motor Module 6SL3320-1TG28-5AA3 6SL3320-1TG31-2AA3 6SL3320-1TG31-8AA3 6SL3320-1TG32-6AA3
6SL3320-1TG31-0AA3 6SL3320-1TG31-5AA3 6SL3320-1TG32-2AA3 6SL3320-1TG33-3AA3
6SL3325-1TG31-0AA3 6SL3325-1TG31-5AA3 6SL3325-1TG32-2AA3 6SL3325-1TG33-3AA3

1) Only for line voltages 500 ... 600 V 3 AC.

5/44 Siemens D 21.3 · 2022


© Siemens 2022

System components for SINAMICS S120 Chassis and Chassis-2 Units


System components
Motor-side power components > dv/dt filter compact plus VPL

■ Technical specifications
Line voltage 500 ... 690 V 3 AC dv/dt filter compact plus VPL
6SL3000-2DG34-1EA0 6SL3000-2DG35-8EA0 6SL3000-2DG38-1EA0 6SL3000-2DG41-3EA0
Rated current A 410 575 810 1270
Ith max A 410 575 810 1270
Power loss, max.
• At 50 Hz 500/690 V kW 0.55 0.571 Reactor: 0.88 Reactor: 0.926
VPL: 0.084 VPL: 0.124
Total: 0.964 Total: 1.05
• At 60 Hz 575 V kW 0.568 0.586 Reactor: 0.918 Reactor: 0.993
VPL: 0.08 VPL: 0.111
Total: 0.998 Total: 1.104
• At 150 Hz 500/690 V kW 0.678 0.689 Reactor: 1.137 Reactor: 1.23
VPL: 0.059 VPL: 0.089
Total: 1.196 Total: 1.319
Power connection Hole for M12 Hole for M12 2 × elongated hole, 2 × elongated hole,
input and output side 14 × 18 mm 14 × 18 mm
• Conductor cross-section, max. (IEC) Provided for busbar Provided for busbar Provided for busbar Provided for busbar
connection connection connection connection
DC link connection Hole for M8 Hole for M8 Hole for M8 Hole for M8
DCPS, DCNS
• Conductor cross-section, max. (IEC) mm2 50 50 95 95
PE/GND connection Threaded socket M6 Threaded socket M6 Threaded socket M6 Threaded socket M6
(reactor and VPL) (reactor and VPL)
Motor cable length, max.
• Shielded m (ft) 100 (328) 100 (328) 100 (328) 100 (328)
5
• Unshielded m (ft) 150 (492) 150 (492) 150 (492) 150 (492)
Degree of protection IP00 IP00 IP00 IP00
Dimensions
• Width mm (in) 440 (17.3) 440 (17.3) Reactor: 430 (16.9) Reactor: 430 (16.9)
VPL: 277 (10.9) VPL: 277 (10.9)
• Height mm (in) 369 (14.5) 369 (14.5) Reactor: 385 (15.2) Reactor: 385 (15.2)
VPL: 360 (14.2) VPL: 360 (14.2)
• Depth mm (in) 311 (12.2) 311 (12.2) Reactor: 323 (12.7) Reactor: 323 (12.7)
VPL: 291 (11.5) VPL: 291 (11.5)
Weight, approx. kg (lb) 87 (192) 100 (220) Reactor: 171.2 (377) Reactor: 175.8 (388)
VPL: 18.8 (41.4) VPL: 19.2 (42.3)
Total: 190 (419) Total: 195 (430)
Conformity CE CE CE CE
Certificate of suitability 1) cURus cURus cURus cURus
Suitable for Motor Module 6SL3320-1TG34-1AA3 6SL3320-1TG34-7AA3 6SL3320-1TG37-4AA3 6SL3320-1TG38-8AA3
6SL3325-1TG34-7AA3 6SL3325-1TG37-4AA3 6SL3320-1TG41-0AA3
6SL3325-1TG34-7AA7 6SL3320-1TG38-1AA3 6SL3325-1TG41-0AA3
6SL3320-1TG35-8AA3 6SL3325-1TG38-0AA3 6SL3325-1TG41-0AA7
6SL3325-1TG35-8AA3 6SL3325-1TG38-1AA3 6SL3320-1TG41-3AA3
6SL3325-1TG35-8AA7 6SL3325-1TG38-1AA7 6SL3325-1TG41-3AA3
6SL3325-1TG41-3AA7

1)
Only for line voltages 500 ... 600 V 3 AC.

Siemens D 21.3 · 2022 5/45


© Siemens 2022

System components for SINAMICS S120 Chassis and Chassis-2 Units


System components
Motor-side power components > Sine-wave filter

■ Overview
If a sine-wave filter is connected to the output of the Power
Module or Motor Module, the voltage between the motor
terminals is virtually sinusoidal. This reduces the voltage load on
the motor windings and prevents motor noise induced by the
pulse frequency.
The pulse frequency of the modules must be set to 4 kHz for the
sine-wave filters. The max. output frequency with sine-wave filter
is limited to 150 Hz.
As a result, the max. possible output current and the max.
achievable output voltage of the units are reduced. The voltage
drops across the sine-wave filter, a factor which must also be
taken into account in the drive design.
A sine-wave filter must be installed as close as possible to the
Motor Module or Power Module.
It is only permissible to operate the sine-wave filter when the
motor is connected (sine-wave filters are not no-load proof)!
For additional information on sine-wave filters, please refer to the
SINAMICS Low Voltage Engineering Manual.

■ Selection and ordering data


5 Suitable for Power Module Suitable for Motor Module Type
rating
Rated
output
Sine-wave filter

at 400 V current
Air-cooled Liquid-cooled Air-cooled Liquid-cooled kW A Article No.
Line voltage 380 ... 480 V 3 AC
6SL3310-1TE32-1AA3 6SL3315-1TE32-1AA3 6SL3320-1TE32-1AA3 6SL3325-1TE32-1AA3 110 210 6SL3000-2CE32-3AA0
6SL3310-1TE32-6AA3 6SL3315-1TE32-6AA3 6SL3320-1TE32-6AA3 6SL3325-1TE32-6AA3 132 260
6SL3310-1TE33-1AA3 6SL3315-1TE33-1AA3 6SL3320-1TE33-1AA3 6SL3325-1TE33-1AA3 160 310 6SL3000-2CE32-8AA0
6SL3310-1TE33-8AA3 – 6SL3320-1TE33-8AA3 – 200 380 6SL3000-2CE33-3AA0
6SL3310-1TE35-0AA3 6SL3315-1TE35-0AA3 6SL3320-1TE35-0AA3 6SL3325-1TE35-0AA3 250 490 6SL3000-2CE34-1AA0

5/46 Siemens D 21.3 · 2022


© Siemens 2022

System components for SINAMICS S120 Chassis and Chassis-2 Units


System components
Motor-side power components > Sine-wave filter

■ Technical specifications
Line voltage 380 ... 480 V 3 AC Sine-wave filter
6SL3000-2CE32-3AA0 6SL3000- 6SL3000- 6SL3000-
2CE32-8AA0 2CE33-3AA0 2CE34-1AA0
Rated current A 225 276 333 408
Power loss, max.
• At 50 Hz 400 V kW 0.221 0.235 0.245 0.34
• At 60 Hz 460 V kW 0.265 0.282 0.294 0.408
• At 150 Hz 400 V kW 0.48 0.5 0.53 0.75
Load connection Flat connector for M10 screw Flat connector for Flat connector for Flat connector for
M10 screw M10 screw M10 screw
PE connection 1 × hole for M10 1 × hole for M10 1 × hole for M10 1 × hole for M10
Cable length, max.
between sine-wave filter and motor
• Shielded m (ft) 300 (984) 300 (984) 300 (984) 300 (984)
• Unshielded m (ft) 450 (1476) 450 (1476) 450 (1476) 450 (1476)
Degree of protection IP00 IP00 IP00 IP00
Dimensions
• Width mm (in) 620 (24.4) 620 (24.4) 620 (24.4) 620 (24.4)
• Height mm (in) 300 (11.8) 300 (11.8) 370 (14.6) 370 (14.6)
• Depth mm (in) 320 (12.6) 320 (12.6) 360 (14.2) 360 (14.2)
Weight, approx. kg (lb) 124 (273) 127 (280) 136 (300) 198 (437)
Conformity CE CE CE CE 5
Certificate of suitability cURus cURus cURus cURus
Suitable for Power Module 6SL3310- 6SL3310- 6SL3310- 6SL3310- 6SL3310-
1TE32-1AA3 1TE32-6AA3 1TE33-1AA3 1TE33-8AA3 1TE35-0AA3
6SL3315- 6SL3315- 6SL3315- 6SL3315-
1TE32-1AA3 1TE32-6AA3 1TE33-1AA3 1TE35-0AA3
Suitable for Motor Module 6SL3320- 6SL3320- 6SL3320- 6SL3320- 6SL3320-
1TE32-1AA3 1TE32-6AA3 1TE33-1AA3 1TE33-8AA3 1TE35-0AA3
6SL3325- 6SL3325- 6SL3325- 6SL3325-
1TE32-1AA3 1TE32-6AA3 1TE33-1AA3 1TE35-0AA3
• Rated output current of the Motor A 170 215 270 330 380
Module or Power Module at a pulse
frequency of 4 kHz

Siemens D 21.3 · 2022 5/47


© Siemens 2022

System components for SINAMICS S120 Chassis and Chassis-2 Units


System components
Control Units

■ Overview
You can obtain further information about SIMOTION in the
Industry Mall and Catalog PM 21.
Each of these Control Units is based on an object-oriented
SINAMICS standard firmware, which contains all common
control modes and can be scaled to meet even the most
advanced performance requirements.
The drive controls are supplied as ready-to-configure
drive objects:
• Infeed Control for mains infeed
• Vector control
- Speed-controlled drives with high speed and torque stability
in general machine and plant construction
- Particularly suitable for induction motors
- Optimized pulse patterns for efficient motor/converter
systems
• Servo control
- Drives with highly dynamic motion control
CU310-2 PN Control Unit - Angular-locked synchronism with isochronous
PROFIBUS/PROFINET
- For use in machine tools and clocked production machines
The most commonly used v/f control modes are stored in the
"Vector control" drive object and are ideal for implementing
5 even simple applications such as group drives with
SIEMOSYN motors.
CompactFlash card
The functions of the drives are stored on a CompactFlash card.
This card contains the firmware and parameter settings for all
drives in the form of a project. The CompactFlash card can also
hold additional projects, which means that the correct project
can be accessed immediately when series machines of different
types are commissioned. When the Control Unit has booted, the
data on the CompactFlash card is read and loaded to the RAM.
The firmware is organized in objects. Drive objects are used to
implement open-loop and closed-loop control functions for Line
Modules, Motor Modules, Power Modules and other system
components connected by DRIVE-CLiQ.
CU320-2 PN Control Unit
System architecture with a central Control Unit
Electronically coordinated individual drives work together to
perform your drive tasks. In multi-axis drives, the individual
drives are controlled from the higher-level control systems in
such a way as to achieve the desired coordinated movement.
This requires cyclic data exchange between the controller and
the drives. A central Control Unit controls the drives for all
connected axes and also establishes the technological links
between the drives and/or axes. Since all the required data
is stored in the central Control Unit, it does not need to be
transferred. Inter-axis connections can be established within
a Control Unit and easily configured in the STARTER
commissioning tool using a mouse.
• The SINAMICS Control Unit can handle simple technological
tasks by itself
• The CU310-2 DP or CU310-2 PN Control Units are used in
conjunction with Power Modules and single-motor drives.
• The CU320-2 DP or CU320-2 PN Control Units are used in
conjunction with all Motor Modules or Line Modules for single
or multi-motor drives.
• Sophisticated motion control tasks can be implemented with
the support of the more powerful D410-2, D425-2, D435-2,
and D445-2 Control Units of SIMOTION D (graded according
to performance).

5/48 Siemens D 21.3 · 2022


© Siemens 2022

System components for SINAMICS S120 Chassis and Chassis-2 Units


System components
Control Units

■ Overview
Drive objects
A drive object is a self-contained software function with its own
parameters and, where appropriate, its own fault messages and
alarms.

Control Unit Drive objects

On-board Option Terminal Terminal


I/O
Infeed Drive ... Drive
Board Module ... Module
control control control
evaluation evaluation evaluation evaluation

Option
Board
Line Motor Motor Terminal Terminal

G_D211_EN_00057a
Module Module Module Module Module

Comprehensive package of open-loop and closed-loop control functions


A wide variety of standard functions such as setpoint input, data set changeover, controller optimization, kinetic buffering, etc. ensure
a high degree of functional reliability and excellent flexibility when addressing the application.
Overview of key open-loop and closed-loop control functions
Closed-loop control types S120 Open-loop control types Main functions S120 for Comment, note
S120 booksize/chassis
Infeed • Chassis • Booksize/chassis • Mains identification The VSM10 is the Voltage Sensing
Control - Current control - Basic Mode • Controller optimization Module;
with VSM10 Rectification only "current" is the line current;
• Harmonics filter 3-phase with line frequency
- VDC control - Smart Mode • Automatic restart
with VSM10 Rectification and
- Network functionalities (island grids) regenerative feedback

Vector • Induction motor • Linear V/f characteristic • Data set changeover Mixed operation with V/f control
control - Torque control with/without encoder • Constant-frequency V/f • Extended setpoint input modes is possible; it is for this
- Speed control with/without encoder characteristic (textile) • Motor identification reason that the V/f control modes
• Torque motor • Independent voltage • Current/speed controller are stored only once in the "Vector
- Torque control with encoder setpoint input optimization control" drive object
- Speed control with/without encoder • Technology controller Position control can be selected
• Induction motor, torque motor • Basic positioner as a function module from both
- Position control with encoder • Automatic restart Servo and Vector mode
• Reluctance motor • Flying restart with/without
- Torque control with/without encoder encoder Permanent-magnet 1FW4
- Speed control with/without encoder • Kinetic buffering synchronous motors can be
• Synchronization operated over the complete
• Droop operating range in Vector control.
• Brake control
Servo • Induction motor • Linear V/f characteristic • Data set changeover Mixed operation with V/f control
control - Torque control with/without encoder • Constant-frequency V/f • Setpoint input modes is possible; it is for this
- Speed control with/without encoder characteristic (textile) • Motor identification reason that the V/f control modes
• Synchronous motor, linear motor and • Independent voltage • Damping application are stored only once in the "Vector
torque motor setpoint input • Technology controller control" drive object
- Torque control with encoder • Basic positioner Position control can be selected
- Speed control with encoder • Brake control as a function module from both
• All motor types Servo and Vector mode.
- Position control with encoder

Siemens D 21.3 · 2022 5/49


© Siemens 2022

System components for SINAMICS S120 Chassis and Chassis-2 Units


System components
Control Units

■ Overview
Extended technology with SIMOTION Integral safety functions (Safety Integrated)
SIMOTION D Control Units support the coordinated motion The Control Units support comprehensive safety functions.
control of multiple drives. Technology objects are implemented
in addition to drive objects on these Control Units. These are The integrated safety functions are the Safety Integrated Basic
grouped to form technology packages and make available Functions
extended Motion Control functions (e.g. synchronous operation, • STO = Safe Torque Off
cam disk, path interpolation and others) or technological • SBC = Safe Brake Control
functions (e.g. a cam controller, a temperature or pressure
control). The IEC 61131-3-compliant PLC integrated in • SS1 = Safe Stop 1 (Time controlled)
SIMOTION D Control Units means that they are not just capable and the Safety Integrated Extended Functions that require
of controlling sequences of motions, but the entire machine a license
including HMI and I/Os. • STO = Safe Torque Off
You can obtain further information about SIMOTION in the • SS1 with SBR/SAM = Safe Stop 1 with Safe Brake Ramp/Safe
Industry Mall and Catalog PM 21. Acceleration Monitor
BICO technology • SS2 = Safe Stop 2
Every drive object contains a large number of input and output • SBC = Safe Brake Control
variables which can be freely and independently interconnected • SOS = Safe Operating Stop
using Binector Connector Technology (BICO). A binector is • SLS = Safely-Limited Speed
a logic signal which can assume the value 0 or 1. A connector is
a numerical value, e.g. the actual speed or current setpoint. • SSM = Safe Speed Monitor
• SDI = Safe Direction
SINAMICS Drive Control Chart (SINAMICS DCC)
• SLA = Safely-Limited Acceleration
5 SINAMICS DCC expands the scope of device functions by
means of freely available closed-loop control, arithmetic and
• SBT = Safe Brake Test
logic blocks and offers a means by which proprietary and Safety Integrated Advanced Functions
technological functions can be graphically configured in the • SLP = Safely-Limited Position
SINAMICS drive system. In addition, local data processing in the
drive supports the implementation of modular machine • SP = Safe Position transmission
concepts and results in an increase in the overall machine • SCA = Safe Cam
performance.
(Abbreviations in accordance with IEC 61800-5-2)
Additional information about the Drive Control Chart (DCC) is
provided in section Engineering tools. If the integrated safety functions are used, licenses,
supplementary system components such as TM54F Terminal
SINAMICS Technology Extensions (SINAMICS TEC) Modules, or suitable safety controls will be necessary.
The SINAMICS TEC are configurable functions or Siemens Additional information about the integrated safety functions is
technologies that can be added to extend firmware functions. provided in section Safety Integrated.
The extensions implement high-performance and targeted
application-specific tasks for different areas, e.g. storage Diagnostics optimally supported by trace function
and retrieval machines. The time characteristics of input and output variables associated
Further information about Technology Extensions (TEC) is with drive objects can be measured by the integrated trace
provided in section Technology functions. function and displayed using the STARTER commissioning tool.
Several signals can be simultaneously traced. A recording can
be triggered dependent on freely selectable boundary
conditions, e.g. the value of an input or output variable.

5/50 Siemens D 21.3 · 2022


© Siemens 2022

System components for SINAMICS S120 Chassis and Chassis-2 Units


System components
Control Units > CU320-2 Control Unit

■ Overview ■ Design
CU320-2 Control Units feature the following interfaces
as standard:
• Fieldbus interface:
- CU320-2 PN: 1 PROFINET interface with 2 ports
(RJ45 sockets) with PROFIdrive V4 profile
- CU320-2 DP: 1 PROFIBUS interface with PROFIdrive V4
profile
• 4 x DRIVE-CLiQ sockets for communication with other
DRIVE-CLiQ nodes, e.g. Motor Modules, Active Line Modules,
Sensor Modules, Terminal Modules
• 12 parameterizable digital inputs (isolated)
• 8 parameterizable bidirectional digital inputs/digital output
(not isolated)
• 1 serial RS 232 interface (e.g. to connect the AOP30 Advanced
Operator Panel)
• 1 interface for the BOP20 Basic Operator Panel
• 1 slot for the CompactFlash card on which firmware and
parameters are stored
• 1 slot for mounting an option module (e.g. TB30 Terminal
Board)
• CU320-2 DP: 2 rotary coding switches for manually setting the 5
PROFIBUS address
• 1 Ethernet interface for commissioning and diagnostics
• 3 measuring sockets and one reference ground for
commissioning support
• 1 connection for the electronics power supply via the 24 V DC
supply connector
• 1 PE/protective conductor connector
• 1 ground connection
A shield connection for the signal cable shield of the option
module is located on the CU320-2 Control Unit.
CU320-2 PN and CU320-2 DP Control Units
The available option slot is used to expand the interfaces,
The communication, open-loop and closed-loop control for example, to include additional terminals or for
functions for one or more Line Modules and/or Motor Modules communication purposes.
are executed in a CU320-2 Control Unit. The CU320-2 Control
Unit is essentially designed for multi-axis operation. The status of the CU320-2 Control Unit is indicated via
Communication with the higher-level control system is multi-color LEDs.
performed via PROFIBUS DP or PROFINET. As the firmware and parameter settings are stored on a plug-in
CompactFlash card, the Control Unit can be changed without
the need for software tools.
The CU320-2 Control Unit can be mounted on the side of the
Line Module via brackets integrated in a Line Module.
The CU320-2 Control Unit can also be fixed to the wall of the
control cabinet using the integrated fixing lugs.

Siemens D 21.3 · 2022 5/51


© Siemens 2022

System components for SINAMICS S120 Chassis and Chassis-2 Units


System components
Control Units > CU320-2 Control Unit

■ Selection and ordering data ■ Integration


Description Article No. DRIVE-CLiQ components, for example, Motor Modules and
Active Line Modules, can be connected to a CU320-2 Control
CU320-2 PN Control Unit 6SL3040-1MA01-0AA0
Unit. The number of modules depends on the performance
Without CompactFlash card required, including duty type and additional functions.
CU320-2 DP Control Unit 6SL3040-1MA00-0AA0
The BOP20 Basic Operator Panel can also be snapped onto the
Without CompactFlash card CU320-2 Control Unit during operation for diagnostic purposes.
Accessories
The CU320-2 Control Unit and other connected components are
For CU320-2 PN: commissioned and diagnosed with the STARTER
Industrial Ethernet FC commissioning tool and the installed SINAMICS Support
• RJ45 Plug 145 (1 units) 6GK1901-1BB30-0AA0 Package or the AOP30 Advanced Operator Panel.
• RJ45 Plug 145 (10 units) 6GK1901-1BB30-0AB0
• Stripping tool 6GK1901-1GA00 To operate the CU320-2 PN Control Unit, a CompactFlash card
• Standard cable GP 2x2 6XV1840-2AH10 with firmware V4.4 or higher is required.
• Flexible cable GP 2x2 6XV1870-2B To operate the CU320-2 DP Control Unit, a CompactFlash card
• Trailing cable GP 2x2 6XV1870-2D with firmware V4.3 or higher is required.
• Trailing cable 2x2 6XV1840-3AH10
• Marine cable 2x2 6XV1840-4AH10
For CU320-2 DP:
PROFIBUS connector
• Without PG/PC connection 6ES7972-0BA42-0XA0
• With PG/PC connection 6ES7972-0BB42-0XA0
Spacers 6SL3064-1BB00-0AA0
(2 units)
5 Increases the depth of the CU320-2 DP Con-
trol Unit to 270 mm (if the integrated brackets
are not to be used, but the depth still has to
be 270 mm)
STARTER commissioning tool 1) 6SL3072-0AA00-0AG0
On DVD-ROM
Accessories for re-ordering
Dust protection blanking plugs 6SL3066-4CA00-0AA0
(50 units)
For DRIVE-CLiQ port

For more information on connectors and cables, please refer to


Catalog IK PI and the Siemens Industry Mall:
www.siemens.com/industrymall

1) For further information, see


https://support.industry.siemens.com/cs/document/104020669

5/52 Siemens D 21.3 · 2022


© Siemens 2022

System components for SINAMICS S120 Chassis and Chassis-2 Units


System components
Control Units > CU320-2 Control Unit

■ Integration
+

ext. M
24 V
X100 X101 X102 X103
X124
+ M +

DRIVE-CLiQ socket 0

DRIVE-CLiQ socket 1

DRIVE-CLiQ socket 2

DRIVE-CLiQ socket 3
+ 24 V
+

M
M
M
M

X122
1 DI 0
2 M1
DI 1
M1
3 DI 2
X126
4 M1
DI 3
PROFIBUS
5 M1
DI 16

6 M1
DI 17 X150 P2
7
M1
M1
PROFINET 5
2) 8
M PROFINET
9 X150 P1
DI/DO 8 1)

Option board
10
DI/DO 9 1) X127
11 Control Unit
M LAN
12 CU320-2
DI/DO 10 1)
13
DI/DO 11 1)
14
M
3)
X132
1 DI 4
2 M2
DI 5
M2
3 DI 6
4 M2
DI 7
5 M2
DI 20

6 M2
DI 21
7 M2
M2
2) 8
M
9
DI/DO 12 1)
10
DI/DO 13 1)
11
M
12
DI/DO 14 1)
G_D211_EN_00285

13
DI/DO 15 1)
14 T1 M
RxD

TxD

M
M

3) T0 T2

1) High-speed inputs (must be shielded). X140


2

2) Jumper open, galvanic isolation for digital inputs (DI).


3) Can be parameterized individually as input/output. Serial interface Test sockets

Connection example of a CU320-2 Control Unit

Siemens D 21.3 · 2022 5/53


© Siemens 2022

System components for SINAMICS S120 Chassis and Chassis-2 Units


System components
Control Units > CU320-2 Control Unit

■ Technical specifications
CU320-2 Control Unit
PROFINET 6SL3040-1MA01-0AA0
PROFIBUS 6SL3040-1MA00-0AA0
Power requirement, max. 1.0 A
At 24 V DC,
without taking account of digital outputs, expansion option slot and
DRIVE-CLiQ supply
Conductor cross-section, max. 2.5 mm2
Fuse protection, max. 20 A
Digital inputs In accordance with IEC 61131-2 Type 1
12 isolated digital inputs
8 bidirectional non-isolated digital inputs/digital outputs
• Voltage -3 ... +30 V
• Low level (an open digital input is interpreted as "low") -3 ... +5 V
• High level 15 ... 30 V
• Current consumption at 24 V DC, typ. 3.5 mA
• Delay time of digital inputs 1), approx.
- LH 50 s
- HL 100 s
• Delay time of high-speed digital inputs 1), approx.
- LH 5 s
- HL 50 s
• Conductor cross-section, max. 1.5 mm2
5 Digital outputs 8 bidirectional non-isolated digital outputs/inputs
(continuously short-circuit proof)
• Voltage 24 V DC
• Load current per digital output, max. 500 mA
• Delay time 1), typ./max.
- LH 150 s/400 s
- HL 75 s/100 s
• Conductor cross-section, max. 1.5 mm2
Power loss 24 W
PE connection M5 screw
Ground connection M5 screw
Dimensions
• Width 50 mm (1.97 in)
• Height 300 mm (11.8 in)
• Depth 226 mm (8.90 in)
Weight, approx. 2.3 kg (5.07 lb)

1) The specified delay times refer to the hardware. The actual reaction time
depends on the time slice in which the digital input or output is processed.

5/54 Siemens D 21.3 · 2022


© Siemens 2022

System components for SINAMICS S120 Chassis and Chassis-2 Units


System components
Control Units > CompactFlash card for CU320-2

■ Overview ■ Selection and ordering data


Description Article No.
CompactFlash card for CU320-2 Control
Unit without safety license
• Without performance expansion 6SL3054-00-1BA0
• With performance expansion firmware 6SL3054-01-1BA0
option
CompactFlash card for CU320-2 Control
Unit with safety license for Extended
Functions
• For 1 axis 6SL3054-0-1BA0-Z
F01
• For 2 axes 6SL3054-0-1BA0-Z
The CompactFlash card contains the firmware and set
parameters. The CompactFlash card is inserted into the F02
appropriate slot of the CU320-2 Control Unit. • For 3 axes 6SL3054-0-1BA0-Z
F03
■ Design • For 4 axes 6SL3054-01-1BA0-Z
F04
A CU320-2 Control Unit can perform the communication, open- • For 5 axes 6SL3054-01-1BA0-Z
loop and closed-loop control functions for several power units. F05
The computing capacity requirement increases in proportion • For 6 axes 6SL3054-01-1BA0-Z
to the number of power units and system components and in F06
relation to the dynamic response required. The computing
capacity requirement and utilization of the CU320-2 Control CompactFlash card for CU320-2 Control
Unit with/without safety license
Unit can be calculated with the SIZER for Siemens Drives
engineering tool (integrated in the TIA Selection Tool). • With high output frequency 1) 6SL3054-0-1BA0-Z 5
The full computing capacity of the CU320-2 Control Unit is only J01
available on systems with performance expansion. For the • With DCB Extension license 6SL3054-0-1BA0-Z
CU320-2 Control Unit, the performance expansion is necessary (firmware V4.6 and higher) U01
(more information about DCB Extension
from the 4th axis. and license upgrades can be found under
Drive Control Chart (DCC) in section Tools
In addition to the firmware, the CompactFlash card also contains and Engineering)
licensing codes which are required to enable firmware options.
Firmware version 
In addition to the Article No., the following firmware options can
V4.8 EJ
currently be ordered with or without performance expansion:
V5.1 FB
• Safety Integrated Extended Functions, order code per axis
F01 to F06 V5.2 FC
• Safety Integrated Advanced Functions, order code per axis 
A01 to A06 Service Pack SP1 2) 1
• High output frequency, order code J01 Service Pack SP3 3) 3
• DCB Extension, order code U01 
Converter cabinets with a Control Unit already contain the Without performance expansion 0
CompactFlash card with the current firmware. The firmware
With performance expansion firmware option 1
options can be added as cabinet options.
The firmware options can also be enabled subsequently. You
require the serial number of the CompactFlash card and the
article number of the firmware option to be enabled. With this
information, you can purchase the associated license code from
a license database and enable the firmware option. The license
code is only valid for the CompactFlash card declared and
cannot be transferred to other CompactFlash cards.
Subsequent licensing is possible in the internet via the web
license manager by generating a license key:
www.siemens.com/automation/license

1) 2)
For more information, see Applies only to firmware version V5.1
https://support.industry.siemens.com/cs/document/104020669 3)
Applies only to firmware version V5.2

Siemens D 21.3 · 2022 5/55


© Siemens 2022

System components for SINAMICS S120 Chassis and Chassis-2 Units


System components
Control Units > CompactFlash card for CU320-2

■ Selection and ordering data ■ More information


Description Article No. A firmware version of  4.3 is required for the CU320-2 Control
Unit.
License upgrades
Electronic Certificate of License (eCoL) The current firmware version at the time of publication of this
• Safety Integrated Extended Function 6SL3074-0AA10-0AH0 catalog is version 5.2.
License upgrade for one axis on
a CompactFlash card. The electronic Certificate of License is the paperless delivery
This option must be ordered once for each form for runtime options for SINAMICS and contains information
axis, e.g. a maximum of 6 for one about the type of rights of use purchased for the software.
CompactFlash card (F01 - F06) The electronic Certificate of License is supplied as a PDF file
• Safety Integrated Advanced Function 6SL3074-0AA20-0AH0 via the Online Software Delivery Portal (OSD).
License upgrade for one axis on This enables quick notification with a download link to the email
a CompactFlash card.
This option must be ordered once for each address to be stated in the order.
axis, e.g. a maximum of 6 for one The Web License Manager can also be called from the OSD to
CompactFlash card (A01 - A06) assign the runtime license to a memory card.
• High output frequency1) 6SL3074-0AA02-0AH0 In this case, the data of the electronic Certificate of License are
Upgrading license to enable high output automatically transferred to the Web License Manager and do
frequencies above 550 Hz for all axes on not have to be entered manually.
a CompactFlash card (J01)
This ensures quick availability of the license key and simple and
• SINAMICS DCB extension 6SL3077-0AA00-0AH0
Runtime license as of firmware V 4.6 for secure handling and management of the license certificates.
upgrading the license on a CompactFlash You will find information on the OSD at:
card (U01) (see Section Tools and https://support.industry.siemens.com/cs/ww/en/view/
Engineering, SINAMICS Drive Control Chart 109759444
engineering software)
• SINAMICS Technology Extension HEM 6SL3077-0AA05-2AH0
Online
In the SINAMICS S120 Cabinet Modules, Web

5
Siemens Direct link
Software License
Mall
Heat Exchanger Modules are included. OSD
Delivery
Automatic
Manager

G_D011_EN_00601
Log In
• Dynamic Grid Support Log In
According to ALM frame size 2)
- Chassis 6SL3074-0AA07-0AH0 Within a few hours
With hardware version for grid converter
„CoL“ „Key“
application PDF

• Grid control for Island Grid


According to ALM power rating 2) The Certificates of License are stored in directory "KEYS".
- 201 ... 350 kW 6SL3074-0AA08-5AH0
Active Line Modules:
6SL3330-7TE35-0AA4
- 351 ... 650 kW 6SL3074-0AA08-4AH0
Active Line Modules:
6SL3330-7TE41-0AA4,
6SL3335-7TG35-8AA4,
6SL3335-7TG35-8AA8
- 651 ... 950 kW 6SL3074-0AA08-3AH0
Active Line Module:
6SL3330-7TE41-4AA4
- 951 ... 1250 kW 6SL3074-0AA08-2AH0
Active Line Module:
6SL3330-7TG41-0AA4
- 1251 ... 1600 kW 6SL3074-0AA08-1AH0
Active Line Modules:
6SL3330-7TG41-3AA4,
6SL3335-7TG41-3AA4,
6SL3335-7TG41-3AA8
- 1601 ... 2000 kW 6SL3074-0AA08-0AH0
Active Line Modules:
6SL3335-7TG41-6AA4,
6SL3335-7TG41-6AA8

1) For more information, see


https://support.industry.siemens.com/cs/document/104020669
2) For more information, see
https://support.industry.siemens.com/cs/document/109781647

5/56 Siemens D 21.3 · 2022


© Siemens 2022

System components for SINAMICS S120 Chassis and Chassis-2 Units


System components
Control Units > CU310-2 Control Unit

■ Overview ■ Design
CU310-2 Control Units feature the following interfaces
as standard:
• Fieldbus interface
- CU310-2 PN:
1 PROFINET interface with 2 ports (RJ45 sockets) with
PROFIdrive V4 profile
- CU310-2 DP:
1 PROFIBUS interface with PROFIdrive V4 profile
• 1 DRIVE-CLiQ socket to allow communication with other
DRIVE-CLiQ nodes
• 1 encoder evaluation for evaluating the following encoder
signals
- Incremental encoder TTL/HTL
- SSI encoders without incremental signals
• 6 parameterizable digital inputs (isolated) or alternatively
3 parameterizable, fail-safe digital inputs (isolated, can be
used with firmware V4.5 and higher).
The fail-safe digital inputs can be routed, i.e. they can be
CU310-2 PN and CU310-2 DP Control Units routed via PROFIsafe to a higher-level controller.
The CU310-2 Control Unit for the communication and open- • 5 parameterizable digital inputs (isolated)
loop/closed-loop control functions of a Power Module is • 1 digital output (isolated) or alternatively
combined with the Power Module to create a powerful single 1 parameterizable, fail-safe digital output (isolated, can be
drive. A PROFINET (PN) variant and a PROFIBUS (DP) variant
are available for fieldbus communication.
used with firmware V4.5 or higher)
• 8 parameterizable bidirectional digital inputs/digital outputs
5
(not isolated)
• 1 analog input, either ± 10 V (resolution 12 bits + sign)
or ± 20 mA (11 bits + sign)
• 1 Ethernet interface (RJ45 socket) for commissioning and
diagnostics
• 1 serial RS232 interface
• 1 connection for the electronics power supply via the 24 V DC
supply connector
• 1 temperature sensor input for KTY84-130, Pt1000 or PTC
(Pt1000 can be used from firmware V4.7 HF17 and higher)
• 3 measuring sockets and one reference ground for
commissioning support
• 1 slot for the CompactFlash card on which firmware and
parameters are stored
• 1 PM-IF interface for communication with Power Modules in
blocksize format
• 1 interface to the BOP20 Basic Operator Panel
• 1 PE/protective conductor connection
The status of the CU310-2 Control Unit is indicated via multi-
color LEDs.
A BOP20 Basic Operator Panel can also be snapped directly
onto the CU310-2 Control Unit for diagnostic procedures.
As the firmware and parameter settings are stored on a plug-in
CompactFlash card, the Control Unit can be changed without
the need for software tools.

Siemens D 21.3 · 2022 5/57


© Siemens 2022

System components for SINAMICS S120 Chassis and Chassis-2 Units


System components
Control Units > CU310-2 Control Unit

■ Selection and ordering data ■ Integration


Description Article No. Power Modules in chassis format are controlled from the
CU310-2 Control Unit via the DRIVE-CLiQ interface. Sensor
CU310-2 PN Control Unit 6SL3040-1LA01-0AA0
Modules and Terminal Modules must be connected to the free
Without CompactFlash card DRIVE-CLiQ sockets of the Power Module.
CU310-2 DP Control Unit 6SL3040-1LA00-0AA0
With the BOP20 Basic Operator Panel, parameters can be
Without CompactFlash card changed directly on the device. The BOP20 Basic Operator
Accessories Panel can also be snapped onto the CU310-2 Control Unit
For CU310-2 PN:
during operation to perform diagnostics.
Industrial Ethernet FC The CU310-2 Control Unit and other connected components are
• RJ45 plug 180 (1 unit) 6GK1901-1BB10-2AA0 commissioned and diagnosed with the commissioning tools
• RJ45 plug 180 (10 units) 6GK1901-1BB10-2AB0 SINAMICS Startdrive or STARTER.
• Stripping tool 6GK1901-1GA00
A CU310-2 DP Control Unit communicates with the higher-level
• Standard cable GP 2x2 6XV1840-2AH10
control system using PROFIBUS and the PROFIdrive V4 profile.
• Flexible cable GP 2x2 6XV1870-2B
• Trailing cable GP 2x2 6XV1870-2D A CU310-2 PN Control Unit communicates with the higher-level
• Trailing cable 2x2 6XV1840-3AH10 control system using PROFINET IO and the PROFIdrive V4
• Marine cable 2x2 6XV1840-4AH10 profile.
For CU310-2 DP: The SINAMICS S120 drive system with the CU310-2 PN Control
PROFIBUS connector Unit then assumes the function of a PROFINET IO device and
• Without PG/PC connection 6ES7972-0BA42-0XA0 can perform the following functions:
• With PG/PC connection 6ES7972-0BB42-0XA0 • PROFINET IO device
Accessories for re-ordering • 100 Mbps full duplex
5 Dust protection blanking plugs
(50 units)
6SL3066-4CA00-0AA0 • Supports real-time classes of PROFINET IO:
- RT (Real-Time)
For DRIVE-CLiQ port - IRT (isochronous real-time), minimum send clock 250 s
For more information on connectors and cables, please refer to • Connects to controls as PROFINET IO devices using
Catalog IK PI and the Siemens Industry Mall: PROFIdrive compliant with Specification V4
www.siemens.com/industrymall • Standard TCP/IP communication for engineering processes
using the commissioning tools SINAMICS Startdrive or
STARTER
• Integrated 2-port switch with two RJ45 sockets based on
the ERTEC ASIC. The optimum topology (line, star, tree) can
therefore be configured without additional external switches.
A 24 V power supply must be connected to terminal X124 in
order to use the digital outputs. To operate the CU310-2 Control
Unit, a CompactFlash card with firmware V4.4 or higher
is required.

1)
For further information, see
https://support.industry.siemens.com/cs/document/104020669

5/58 Siemens D 21.3 · 2022


© Siemens 2022

System components for SINAMICS S120 Chassis and Chassis-2 Units


System components
Control Units > CU310-2 Control Unit

■ Integration
+

8) ext. M ext.
24 V X22
24 V
X21 PROFIBUS
2 3 5 X100 X23
24 V M 24 V2 M2
X150 P1 X150 P2

RxD
TxD

DRIVE-CLiQ socket 0
PROFINET
X124

Encoder interface
+ Serial interface
24 V
+
M X127
M
M LAN
M

X120 X121
1 DI 0 1
DI 0
+Temp 1)
2 DI 1 2
DI 1
-Temp 1)
24 V1 DI 2 DI 2 3
3 DI 16
DI 3 4
Curr. sourcing 24 V1 4 DI 17+ F-DI 0 DI 3
6) 3)
Curr. sinking M2 5
5 DI 17-
2)
M1
24 V1
6 DI 18
4)
M

DI/DO 8
6
7
24 V 5
7 DI 19+ F-DI 1
4) DI/DO 9 8
7) Curr. sourcing M1 8 DI 19-
Curr. sourcing 2) M 9
9 DI 20
4) DI/DO 10 10
M1 10 DI 21+ F-DI 2
4) DI/DO 11 11
11 DI 21- 6)
2)
M1 12 M1 M 12
ext.
24 V

24 V1 M1 X130 X131
24 V
1 DI 22+ 4) DI/DO 12 1
DI 22 4) DI/DO 13 2
2 DI 22-

M2 M 3
3
4) DI/DO 14 4
4 M
M1 5 M1 4) DI/DO 15 5
6)
6 24 V1 M 6
24 V1 F-DO 0
7 AI 0+ 7
DO 16+
AI 0- 8 ± 10 V
8 DO 16-

Control Unit 5)
G_D211_EN_00278a

CU310-2
Memory card

1) Motor temperature sensor input must be shielded.


2) Inversion can be parameterized.
3) Jumper open, galvanic isolation for digital inputs (DI).
4) High-speed inputs must be shielded.
5) Analog input must be shielded.
6) Safety-related control with current sourcing and current sinking outputs.
7) Safety-related control with two current sourcing outputs.
8) In order to use the digital outputs, an external 24 V power supply must be connected to terminal X124.

Connection example of CU310-2 Control Unit

Siemens D 21.3 · 2022 5/59


© Siemens 2022

System components for SINAMICS S120 Chassis and Chassis-2 Units


System components
Control Units > CU310-2 Control Unit

■ Technical specifications
CU310-2 Control Unit
PROFINET 6SL3040-1LA01-0AA0
PROFIBUS 6SL3040-1LA00-0AA0
Power requirement, max. 0.35 A for CU310-2 Control Unit + 0.5 A for Power Module
At 24 V DC,
without taking into account the digital outputs and DRIVE-CLiQ supply
Conductor cross-section, max. 2.5 mm2
Fuse protection, max. 20 A
Digital inputs in accordance with IEC 61131-2 Type 1
5 isolated digital inputs
8 bidirectional non-isolated digital inputs/digital outputs
3 parameterizable, fail-safe digital inputs (isolated) or alternatively
6 parameterizable digital inputs (isolated)
• Voltage -3 ... +30 V
• Low level (an open digital input is interpreted as "low") -3 ... +5 V
• High level 15 ... 30 V
• Current consumption at 24 V DC, typ. 10 mA
• Delay time of digital inputs 1), approx.
- LH 50 s
- HL 100 s
• Delay time of high-speed digital inputs 1), approx.
(high-speed digital inputs can be used for position detection)
- LH 5 s
5 - HL
• Conductor cross-section, max.
50 s
1.5 mm2
Digital outputs 8 bidirectional non-isolated digital inputs/digital outputs
(continuously short-circuit proof)
• Voltage 24 V DC
• Load current per digital output 2), max. 500 mA
• Delay time 1), typ./max.
- LH 150 s/400 s
- HL 75 s/100 s
• Conductor cross-section, max. 1.5 mm2
Analog input 1 analog input for current or voltage input, switchable
• Common mode range ±12 V
• As voltage input -10 ... +10 V; Ri > 100 
Resolution: 12 bits + sign (referred to the maximum range that
can be resolved -11 ... +11 V)
• As current input -20 ... +20 mA; Ri > 250 
Resolution: 11 bits + sign (referred to -22 ... + 22 mA)
Max. range that can be resolved: -44 ... +44 mA
Encoder evaluation • Incremental encoder TTL/HTL
• SSI encoders without incremental signals
• Input current range TTL/HTL 2 ... 10 mA (typ. 5 mA)
• Encoder supply 24 V DC / 0.35 A or
5 V DC / 0.35 A
• Encoder frequency, max. 300 kHz
• SSI baud rate 100 ... 250 kBaud
• Resolution absolute position SSI 30 bits
• Cable length, max.
- TTL encoder 100 m (328 ft) (only bipolar signals permitted) 3)
- HTL encoder 100 m (328 ft) for unipolar signals
300 m (984 ft) for bipolar signals 3)
- SSI encoder 100 m (328 ft)
Power loss <20 W
PE connection M4 screw
Dimensions
• Width 73 mm (2.87 in)
• Height
- CU310-2 PN 191 mm (7.52 in)
- CU310-2 DP 187 mm (7.36 in)
• Depth 75 mm (2.95 in)
Weight, approx. 0.95 kg (2.09 lb)

1) The specified delay times refer to the hardware. The actual reaction time 2) In order to use the digital outputs, an external 24 V power supply must be
depends on the time slice in which the digital input or output is processed. connected to terminal X124.
3) Signal cables twisted in pairs and shielded.

5/60 Siemens D 21.3 · 2022


© Siemens 2022

System components for SINAMICS S120 Chassis and Chassis-2 Units


System components
Control Units > CompactFlash card for CU310-2

■ Overview Siemens
Mall
Online
Software Direct link
Web
License
Delivery Manager
OSD Automatic

G_D011_EN_00601
Log In
Log In

Within a few hours

„CoL“ „Key“
PDF

The Certificates of License are stored in directory "KEYS".

■ Selection and ordering data


Description Article No.

The CompactFlash card contains the firmware and set CompactFlash card for CU310-2 Control 6SL3054-000-1BA0
Units without safety license
parameters. The CompactFlash card is plugged into the
appropriate slot on the CU310-2 Control Unit. CompactFlash card for CU310-2 Control 6SL3054-000-1BA0-Z
Units with safety license F01
■ Design
• including Certificate of License
CompactFlash card for CU310-2 Control
A CU310-2 Control Unit can perform the communication, open- Units with/without safety license
loop and closed-loop control functions for one Power Module. • With high output frequency 1) 6SL3054-00-1BA0-Z
The performance expansion is not required in this case. J01
• With DCB Extension license 6SL3054-00-1BA0-Z
In addition to the firmware, the CompactFlash card also contains (firmware V4.6 and higher) U01
licensing codes which are required to enable firmware options. (further information about DCB Extension
and license upgrades can be found under
In addition to the Article No., the following firmware options can
currently be ordered:
Drive Control Chart (DCC) in section Tools
and Engineering)
5
• Safety Integrated Extended Functions, order code F01 Firmware version 
• Safety Integrated Advanced Functions, order code A01 V4.8 EJ
• High output frequency, order code J01 V5.1 FB
• DCB Extension, order code U01 V5.2 FC
The firmware options can also be enabled subsequently. You will 
need the serial number of the CompactFlash card and the Article Service Pack SP1 2) 1
No. of the firmware option to be enabled. With this information,
Service Pack SP3 3) 3
you can purchase the associated license code from a license
database and enable the firmware option. The license code is License upgrades
only valid for the CompactFlash card declared and cannot be Electronic Certificate of License (eCoL)
transferred to other CompactFlash cards. • Safety Integrated Extended Functions 6SL3074-0AA10-0AH0
including Certificate of License
Subsequent licensing is possible in the internet via the web Upgrading license for one axis on
license manager by generating a license key: a CompactFlash card
www.siemens.com/automation/license • Safety Integrated Advanced Functions 6SL3074-0AA20-0AH0
including Certificate of License
The electronic Certificate of License is the paperless delivery Upgrading license for one axis on
form for runtime options for SINAMICS and contains information a CompactFlash card
about the type of rights of use purchased for the software. • High output frequency1) 6SL3074-0AA02-0AH0
The electronic Certificate of License is supplied as a PDF file via Upgrading license to enable high output
the Online Software Delivery Portal (OSD). frequencies above 550 Hz for all axes on
a CompactFlash card
This enables quick notification with a download link to the email
• SINAMICS Technology Extension HEM 6SL3077-0AA05-2AH0
address to be stated in the order. In the SINAMICS S120 Cabinet Modules,
The Web License Manager can also be called from the OSD to Heat Exchanger Modules are included.
assign the runtime license to a memory card.
In this case, the data of the electronic Certificate of License are
automatically transferred to the Web License Manager and do
not have to be entered manually.
This ensures quick availability of the license key and simple and
secure handling and management of the license certificates.
You will find information on the OSD at:
https://support.industry.siemens.com/cs/ww/en/view/
109759444

1) 2)
For more information, see Applies only for firmware version V5.1
https://support.industry.siemens.com/cs/document/104020669 3)
Applies only for firmware version V5.2

Siemens D 21.3 · 2022 5/61


© Siemens 2022

System components for SINAMICS S120 Chassis and Chassis-2 Units


Supplementary system components
BOP20 Basic Operator Panel

■ Overview ■ Integration
The BOP20 Basic Operator Panel can be inserted on the follow-
ing Control Units:
• SINAMICS S120
- CU310-2
- CU320-2

BOP20 Basic Operator Panel


Parameters can be set, diagnostics information (e.g. alarm and
fault messages) read out and faults acknowledged using the
BOP20 Basic Operator Panel.
5 ■ Design CU310-2 PN Control Unit with inserted BOP20 Basic Operator Panel

The BOP20 Basic Operator Panel has a backlit two-line display


area with six keys.
The integrated plug connector on the rear of the BOP20 Basic
Operator Panel provides its power and establishes
communication with the Control Unit.

■ Selection and ordering data


Description Article No.
BOP20 Basic Operator Panel 6SL3055-0AA00-4BA0

CU320-2 PN Control Unit with inserted BOP20 Basic Operator Panel

5/62 Siemens D 21.3 · 2022


© Siemens 2022

System components for SINAMICS S120 Chassis and Chassis-2 Units


Supplementary system components
AOP30 Advanced Operator Panel

■ Overview AOP30 CU320-2


X540 X140
9-pole SUB-D 9-pole SUB-D
2 2 RxD
RxD
3 3
TxD TxD
5 5
M 0V M 0V

G_D011_EN_00068

Assignment of the serial plug-in cable

■ Design
The AOP30 is an operator panel with graphical display and
membrane keyboard. The device can be installed in a cabinet
door which is between 2 mm and 4 mm thick.
Features:
• Display with green backlighting, resolution 240 × 64 pixels
• Membrane keyboard with 26 keys
• Connection for a 24 V power supply
• RS232 interface
• Time and date memory with internal battery backup
5
• 4 LEDs to indicate the operating state of the drive:
The AOP30 Advanced Operator Panel is an input/output device - RUN green
for converters of the SINAMICS series, preferably for cabinet - ALARM yellow
installation. - FAULT red
It has the following characteristics: - Local/Remote green
• Graphical backlit LCD display for plain text display and a bar
display of process variables ■ Selection and ordering data
• LEDs for display of the operating states Description Article No.
• Help function describing causes of and remedies for faults AOP30 Advanced Operator Panel 6SL3055-0AA00-4CA5
and alarms
Accessories
• Keypad for operational control of a drive
RS232 plug-in cable
• Local/remote switchover for selecting the operating location for connecting the AOP30 to the CU320-2
(control priority assigned to operator panel or customer
1 m (3.28 ft) long 6FX8002-1AA01-1AB0
terminal strip/communication channel)
2 m (6.56 ft) long 6FX8002-1AA01-1AC0
• Numeric keypad for input of setpoint or parameter values
3 m (9.84 ft) long 6FX8002-1AA01-1AD0
• Function keys for guided navigation in the menu
4 m (13.1 ft) long 6FX8002-1AA01-1AE0
• Two-stage safety concept to protect against accidental or
unauthorized changes to settings. 5 m (16.41 ft) long 6FX8002-1AA01-1AF0
- Operation of the drive from the operator panel can be 6 m (19.7 ft) long 6FX8002-1AA01-1AG0
disabled by the keyboard lock so that only parameter values
and process variables can be displayed on the operator 7 m (23.0 ft) long 6FX8002-1AA01-1AH0
panel. 8 m (26.2 ft) long 6FX8002-1AA01-1AJ0
- A password can be used to prevent the unauthorized 9 m (29.5 ft) long 6FX8002-1AA01-1AK0
modification of converter parameters.
10 m (32.8 ft) long 6FX8002-1AA01-1BA0
• Front panel with degree of protection IP55
For the SINAMICS S120 Cabinet Modules, the AOP30 can be
The AOP30 and SINAMICS drive communicate via the RS232
ordered as an option by specifying order code K08.
serial interface with PPI protocol.
For SINAMICS G150 and SINAMICS S150, the AOP30
The AOP30 may be omitted if the drive is only operated via
Advanced Operator Panel is installed in the cabinet door as
PROFIBUS, for example, and no local display is required on the
standard.
cabinet. The AOP30 can then be used simply for commissioning
purposes and to obtain diagnostic information, in which case,
it is plugged into the RS232 interface on the CU320-2 Control
Unit. In this case, an external 24 V power supply (max. current
requirement 200 mA) is required.

Siemens D 21.3 · 2022 5/63


© Siemens 2022

System components for SINAMICS S120 Chassis and Chassis-2 Units


Supplementary system components
AOP30 Advanced Operator Panel

■ Function ■ Technical specifications


The current operating states, setpoints and actual values, AOP30 Advanced Operator Panel
parameters, indices, faults and alarms are displayed on the 6SL3055-0AA00-4CA5
display panel. Power supply 24 V DC (20.4 ... 28.8 V DC)
German, English, French, Italian, Spanish and Chinese are Current requirement
stored on the CU320-2 Control Unit CompactFlash card as • Without backlighting <100 mA
operator panel languages. The desired language must be • For max. backlighting < 200 mA
downloaded to the AOP30 prior to commissioning.
Data interface RS232 interface,
In addition to these preinstalled languages, Russian and PPI protocol
Portuguese (Brazil) are also available for subsequent Backup battery 3 V lithium CR2032
installation.
Operating temperature 0 ... 55 °C (32...131 °F)
Further languages are available on request.
Storage and transport temperature -25 ... +70 °C (-13 ... +158 °F)
■ Integration Degree of protection IP20 for the inside of the cabinet
IP55 for the outside of the cabinet
If one CU320-2 Control Unit controls several power units (multi- Dimensions
motor drives) in the SINAMICS S120 drive system, the • Width 212 mm (8.35 in)
parameters, alarms and faults of all the connected devices can • Height 156 mm (6.14 in)
be simultaneously displayed and processed on the AOP30 • Depth 31 mm (1.22 in)
Advanced Operator Panel.
Weight, approx. 0.55 kg (1.21 lb)
Certificate of suitability cULus

5/64 Siemens D 21.3 · 2022


© Siemens 2022

System components for SINAMICS S120 Chassis and Chassis-2 Units


Supplementary system components
CBE20 PROFINET Communication Board

■ Overview ■ Selection and ordering data


Description Article No.
CBE20 Communication Board 6SL3055-0AA00-2EB0
Accessories
Industrial Ethernet FC
• RJ45 Plug 180 (1 unit) 6GK1901-1BB10-2AA0
• RJ45 Plug 180 (10 units) 6GK1901-1BB10-2AB0
• Stripping tool 6GK1901-1GA00
• Standard cable GP 2x2 6XV1840-2AH10
• Flexible cable GP 2x2 6XV1870-2B
• Trailing cable GP 2x2 6XV1870-2D
• Trailing cable 2x2 6XV1840-3AH10
• Marine cable 2x2 6XV1840-4AH10

For the SINAMICS G150, SINAMICS S150 and SINAMICS S120


Cabinet Modules, the CBE20 Communication Board can be
ordered as an option by specifying order code G33.
Additional information on connectors and cables is provided in
• Section MOTION-CONNECT connection system
The CBE20 Communication Board can be used to connect to
a PROFINET IO network via a CU320-2 Control Unit. • Catalog IK PI
The SINAMICS S120 or SINAMICS S150 drive system then • Siemens Industry Mall:
assumes the function of a PROFINET IO device and can perform www.siemens.com/industrymall
the following functions:
• PROFINET IO device ■ Integration 5
• 100 Mbps full duplex The CBE20 Communication Board plugs into the option slot on
• Supports real-time classes of PROFINET IO: the CU320-2 Control Unit.
- RT (Real-Time) SINAMICS Link
- IRT (Isochronous Real-Time), minimum send cycle 500 s
• Connection to control systems as PROFINET IO devices in SINAMICS Link can be used to directly exchange data between
accordance with PROFIdrive, Specification V4 several CU320-2 DP (PROFIBUS) or CU320-2 PN (PROFINET)
Control Units without using a higher-level control system. In this
• Standard TCP/IP communication for engineering processes case, the CBE20 Communication Board is required. Possible
using the Startdrive or STARTER commissioning tools applications for the SINAMICS Link include:
• Integrated 4-port switch with four RJ45 sockets based on the • Torque distribution for several drives
PROFINET ASIC ERTEC400. The optimum topology (line, star,
tree) can therefore be configured without additional external • Setpoint cascading for several drives
switches • Load distribution for drives coupled through a material web
• Supports the functions "media redundancy" and • Couplings between SINAMICS G or SINAMICS S with the
"shared device" CU320-2 Control Unit and SINAMICS DC Master with CUD
Control Units.
The CBE20 Communication Board is required if:
• a SINAMICS S120 or SINAMICS S150 converter with Participants other than CU320-2 Control Units and/or CUD
a CU320-2 DP Control Unit (PROFIBUS) should be connected Control Units of the SINAMICS DC Master cannot be integrated
to a PROFINET-IO network into this communication.
• SINAMICS Link is to be used to directly exchange data SINAMICS Link is activated by appropriately parameterizing the
between several CU320-2 DP (PROFIBUS) or CU320-2 PN Control Units of the participants.
(PROFINET) Control Units without using a higher-level control
system ■ Technical specifications
• EtherNet/IP in a CU320-2 DP should be used
CBE20 Communication Board
• Modbus TCP in a CU320-2 DP should be supported 6SL3055-0AA00-2EB0
Current requirement 0.16 A
at 24 V DC
Power loss 2.4 W
Weight, approx. 0.1 kg (0.22 lb)
Certificate of suitability cULus

Siemens D 21.3 · 2022 5/65


© Siemens 2022

System components for SINAMICS S120 Chassis and Chassis-2 Units


Supplementary system components
DMC20 DRIVE-CLiQ Hub Module

■ Overview ■ Selection and ordering data


Description Article No.
DMC20 DRIVE-CLiQ Hub Module 6SL3055-0AA00-6AA1
Without DRIVE-CLiQ cable
Accessories for re-ordering
Dust protection blanking plugs 6SL3066-4CA00-0AA0
(50 units)
For DRIVE-CLiQ port

■ Technical specifications
DMC20 DRIVE-CLiQ Hub Module
6SL3055-0AA00-6AA1
Power requirement, max. 0.15 A
at 24 V DC without DRIVE-CLiQ
supply
• Conductor cross-section, max. 2.5 mm2
Degree of protection IP20
The DMC20 DRIVE-CLiQ Hub Module is used to implement Dimensions
a star-shaped topology of a DRIVE-CLiQ line. Two DMC20 • Width 30 mm (1.18 in)
DRIVE-CLiQ Hub Modules can be connected in series • Height 151 mm (5.94 in)
(cascaded). • Depth 110 mm (4.33 in)

5 ■ Design
Weight, approx.
Certificate of suitability
0.36 kg (0.79 lb)
cULus
The DMC20 DRIVE-CLiQ Hub Module in degree of protection
IP20 is designed for mounting in control cabinets.
The following are located on the DMC20 DRIVE-CLiQ Hub
Module:
• 6 DRIVE-CLiQ sockets for connecting 5 DRIVE-CLiQ devices
• 1 connection for the electronics power supply via the 24 V DC
supply connector
The status of the DMC20 DRIVE-CLiQ Hub Module is indicated
via a multi-color LED.
The DMC20 DRIVE-CLiQ Hub Module can be snapped onto
a TH 35 standard mounting rail according to EN 60715
(IEC 60715).

5/66 Siemens D 21.3 · 2022


© Siemens 2022

System components for SINAMICS S120 Chassis and Chassis-2 Units


Supplementary system components
DMC20 DRIVE-CLiQ Hub Module

■ Integration
Signals from more than one encoder can be collected with one DRIVE-CLiQ Hub Module and forwarded to the Control Unit through
a single DRIVE-CLiQ cable.

Sensor
X100 X500
Module
X101
DRIVE-CLiQ
X102
X500 X501
X103 Sensor
X502 X500
Module
X503
Control DMC20
Units or X504
DME20
X505
DRIVE-CLiQ Sensor
Hub Module X500
Module
G_D211_EN_00067c

With a DRIVE-CLiQ Hub Module, individual DRIVE-CLiQ nodes can be removed without interrupting the data exchange with the
remaining devices in the DRIVE-CLiQ line.

Drive 1 Drive 2 Drive 5

X100

X101
X200
X201
X200
X201
X200
X201
5
X500 X501
X102
X502 Single Single Single
X103 Motor Motor ... Motor
X503
Module Module Module
X504
CU320-2 DMC20
D4x5-2 or X505 X202 X202 X202
CX32-2 DME20
Control DRIVE-CLiQ
Units Hub Module
...
G_D211_EN_00068b DRIVE-CLiQ

Siemens D 21.3 · 2022 5/67


© Siemens 2022

System components for SINAMICS S120 Chassis and Chassis-2 Units


Supplementary system components
DME20 DRIVE-CLiQ Hub Module

■ Overview ■ Selection and ordering data


Description Article No.
DME20 DRIVE-CLiQ Hub Module 6SL3055-0AA00-6AB0
Without DRIVE-CLiQ cable; without
electronics power supply cable and
circular connector for 24 V DC
Accessories
24 V DC power supply cable Ordering and delivery
Phoenix Contact
www.phoenixcontact.de
• Shielded connector, 5-pole, can be 1508365
assembled by the user
• Unshielded connector, 4-pole, can 1521601
be assembled by the user, Speedcon
rapid interlock
Accessories for re-ordering
SINAMICS dust-proof blanking plugs IP67 6SL3066-4CA01-0AA0
(6 units)
For DRIVE-CLiQ port
The DME20 DRIVE-CLiQ Hub Module is used to implement
a star-shaped topology of a DRIVE-CLiQ line. Two DME20
DRIVE-CLiQ Hub Modules can be connected in series ■ Technical specifications
(cascaded).
DME20 DRIVE-CLiQ Hub Module
5 ■ Design Power requirement, max.
6SL3055-0AA00-6AB0
0.15 A
The following are located on the DME20 DRIVE-CLiQ at 24 V DC without DRIVE-CLiQ
Hub Module: supply
• Conductor cross-section, max. 4 × 0.75 mm2
• 6 DRIVE-CLiQ sockets for connecting 5 DRIVE-CLiQ devices
Degree of protection IP67
• 1 connection for the electronics power supply via the 24 V DC
circular supply connector with conductor cross-section Dimensions
4 × 0.75 mm2 (pins 1+2 internally bridged; pins 3+4 internally • Width 99 mm (3.90 in)
bridged) • Height 149 mm (5.87 in)
• Depth 55.7 mm (2.19 in) (without connector)
The scope of supply of the DME20 DRIVE-CLiQ Hub Modules
Weight, approx. 0.8 kg (1.76 lb)
includes:
Certificate of suitability cULus
• 6 blanking plugs for sealing unused DRIVE-CLiQ sockets

5/68 Siemens D 21.3 · 2022


© Siemens 2022

System components for SINAMICS S120 Chassis and Chassis-2 Units


Supplementary system components
DME20 DRIVE-CLiQ Hub Module

■ Integration
Signals from more than one encoder can be collected with one DRIVE-CLiQ Hub Module and forwarded to the Control Unit through
a single DRIVE-CLiQ cable.

Sensor
X100 X500
Module
X101
DRIVE-CLiQ
X102
X500 X501
X103 Sensor
X502 X500
Module
X503
Control DMC20
Units or X504
DME20
X505
DRIVE-CLiQ Sensor
Hub Module X500
Module
G_D211_EN_00067c

With a DRIVE-CLiQ Hub Module, individual DRIVE-CLiQ nodes can be removed without interrupting the data exchange with the
remaining devices in the DRIVE-CLiQ line.

Drive 1 Drive 2 Drive 5

X100

X101
X200
X201
X200
X201
X200
X201
5
X500 X501
X102
X502 Single Single Single
X103 Motor Motor ... Motor
X503
Module Module Module
X504
CU320-2 DMC20
D4x5-2 or X505 X202 X202 X202
CX32-2 DME20
Control DRIVE-CLiQ
Units Hub Module
...
G_D211_EN_00068b DRIVE-CLiQ

The DME20 DRIVE-CLiQ Hub Module in degree of protection IP67 is suitable for installation outside control cabinets.

Siemens D 21.3 · 2022 5/69


© Siemens 2022

System components for SINAMICS S120 Chassis and Chassis-2 Units


Supplementary system components
TB30 Terminal Board

■ Overview ■ Technical specifications


TB30 Terminal Board
6SL3055-0AA00-2TA0
Power requirement, max. 0.05 A
at 24 V DC via Control Unit CU320-2
without taking account of digital out-
puts
• Conductor cross-section, max. 2.5 mm2
• Fuse protection, max. 20 A
Digital inputs
In accordance with IEC 61131-2
Type 1
• Voltage -3 ... +30 V
• Low level -3 ... +5 V
(an open digital input is interpreted
as "low")
• High level 15 ... 30 V
• Current consumption at 24 V DC, 6 mA
typ.
• Delay time of digital inputs 1), ap-
prox.
The TB30 Terminal Board supports the addition of digital - LH 50 s
inputs/digital outputs and analog inputs/analog outputs to - HL 100 s
a Control Unit. • Conductor cross-section, max. 0.5 mm2
Digital outputs

5 ■ Design (continuously short-circuit proof)


• Voltage 24 V DC
The following are located on the TB30 Terminal Board: • Load current per digital output, max. 500 mA
• Power supply for digital inputs/digital outputs • Delay time of digital outputs 1), ap- 150 s
prox.
• 4 digital inputs • Conductor cross-section, max. 0.5 mm2
• 4 digital outputs Analog inputs
• 2 analog inputs (difference)
• Voltage range -10 ... +10 V
• 2 analog outputs (an open analog input is interpreted
A shield connection for the signal cable shield is located on the as 0 V)
Control Unit. • Internal resistance Ri 65 k
• Resolution 2) 13s bits + sign
0.5 mm2
■ Selection and ordering data • Conductor cross-section, max.
Analog outputs
(continuously short-circuit proof)
Description Article No.
• Voltage range -10 ... +10 V
TB30 Terminal Board 6SL3055-0AA00-2TA0 • Max. load current -3 ... +3 mA
• Resolution 11 bits + sign
For the SINAMICS G150, SINAMICS S150 and SINAMICS S120
• Settling time, approx. 200 s
Cabinet Modules, the TB30 Terminal Board can be ordered as
• Conductor cross-section, max. 0.5 mm2
an option by specifying order code G62.
Power loss, max. 3W
Weight, approx. 0.1 kg (0.22 lb)
Certificate of suitability cULus

1) The specified delay times refer to the hardware. The actual reaction time 2) If the analog input is to be operated in the signal processing sense with
depends on the time slice in which the digital input/output is processed. continuously variable input voltage, the sampling frequency fa = 1/ttime slice
must be at least twice the value of the highest signal frequency fmax.

5/70 Siemens D 21.3 · 2022


© Siemens 2022

System components for SINAMICS S120 Chassis and Chassis-2 Units


Supplementary system components
TB30 Terminal Board

■ Integration
The TB30 Terminal Board is inserted in the slot to optionally expand the CU320-2 Control Unit.

ext. M
24 V

+ M

X424
+ + 24 V
Terminal Board
+
TB30
M
M
M
M

X481
1 1 DI 0
2 DI 1
M

M
5
3 DI 2

Internal interface to Control Unit


M
4 DI 3
M
5 DO 0
6 DO 1
7 DO 2
8 8 DO 3

X482
1 1
AI 0+ +
±10 V
2 AI 0- -
3 AI 1+ +
4 AI 1- -
5 -
AO 0+
V
6 +
AO 0-
7 -
AO 1+
V
G_D212_EN_00028c

8 8 +
AO 1-

Connection example of a TB30 Terminal Board

Siemens D 21.3 · 2022 5/71


© Siemens 2022

System components for SINAMICS S120 Chassis and Chassis-2 Units


Supplementary system components
TM15 Terminal Module

■ Overview ■ Technical specifications


TM15 Terminal Module
6SL3055-0AA00-3FA0
Power requirement, max. 0.15 A
at 24 V DC without load
• Conductor cross-section, max. 2.5 mm2
• Fuse protection, max. 20 A
Number of DRIVE-CLiQ sockets 2
I/O
• Digital inputs/outputs Parameterizable channel-by-channel
as DI or DO
• Number of digital inputs/outputs 24
• Galvanic solation Yes, in groups of 8
• Cables and connections Plug-in screw-type terminals
• Conductor cross-section, max. 1.5 mm2
Digital inputs
• Voltage -30 ... +30 V
• Low level -30 ... +5 V
(an open digital input is interpreted
as "low")
The number of available digital inputs and outputs within a drive
• High level 15 ... 30 V
system can be expanded with the TM15 Terminal Module.
• Current consumption at 24 V DC 9 mA
• Delay times of digital inputs, typ.1)
■ Design - LH 50 s

5 The TM15 Terminal Module is equipped with the following:


- HL
Digital outputs
100 s

• 24 bidirectional digital inputs/outputs (galvanic isolation in (continuously short-circuit proof)


3 groups with 8 channels per group) • Voltage 24 V DC
• 24 green status LEDs for indicating the logical signal state of • Load current per digital output, max. 0.5 A
the corresponding terminal • Delay times (resistive load) 1)
• 2 DRIVE-CLiQ sockets - L  H, typ. 50 s
- L  H, max. 100 s
• 1 connection for the electronics power supply via the 24 V DC - H  L, typ. 150 s
supply connector - H  L, max. 225 s
• 1 PE/protective conductor connection • Total current of outputs
(per group), max.
The status of the TM15 Terminal Module is indicated via a multi- - To 60 °C (140 °F) 2A
color LED. - To 50 °C (122 °F) 3A
The TM15 Terminal Module can be snapped onto a TH 35 - To 40 °C (104 °F) 4A
standard mounting rail in accordance with EN 60715 Power loss, max. 3W
(IEC 60715).
PE connection M4 screw
The signal cable shield can be connected to the TM15 Terminal Dimensions
Module by means of a shield connection terminal, e.g. Phoenix • Width 50 mm (1.97 in)
Contact type SK8 or Weidmüller type KLBÜ CO 1. The shield • Height 150 mm (5.91 in)
connection terminal must not be used as a strain relief • Depth 111 mm (4.37 in)
mechanism.
Weight, approx. 1 kg (2.20 lb)

■ Selection and ordering data Certificate of suitability cULus

Description Article No.


TM15 Terminal Module 6SL3055-0AA00-3FA0
Without DRIVE-CLiQ cable
Accessories for re-ordering
Dust protection blanking plugs 6SL3066-4CA00-0AA0
(50 units)
For DRIVE-CLiQ port

1) The specified delay times refer to the hardware. The actual reaction time
depends on the time slice in which the digital input/output is processed.

5/72 Siemens D 21.3 · 2022


© Siemens 2022

System components for SINAMICS S120 Chassis and Chassis-2 Units


Supplementary system components
TM15 Terminal Module

■ Integration
The TM15 Terminal Module can communicate with the following Control Units via DRIVE-CLiQ:
• CU310-2 Control Unit
• CU320-2 Control Unit

+ +
ext.
24 V M M

X500 X501
X524 X520

1
1
+ L1+ L1+

DRIVE-CLiQ socket

DRIVE-CLiQ socket
+ 24 V
2
+ DI/DO 0 M1
3
M DI/DO 1
M
4
M DI/DO 2
M
5
DI/DO 3
M 6
DI/DO 4 1)
7
DI/DO 5
8
DI/DO 6

DI/DO 7
9

10
5
M1

Terminal Module
X521
TM15 1
L2+ L2+
2
DI/DO 8 M2
3
DI/DO 9
4
DI/DO 10
5
DI/DO 11
M 6
DI/DO 12 1)
7
DI/DO 13
8
DI/DO 14
9
DI/DO 15
10
M2

X522
1
L3+ L3+
2
DI/DO 16 M3
3
DI/DO 17
4
DI/DO 18
5
DI/DO 19
M 6
DI/DO 20 1)
7
DI/DO 21
8
DI/DO 22
9
DI/DO 23
10
M3

G_D211_EN_00040

1) Can be parameterized individually as input or output.

Connection example of TM15 Terminal Module

Siemens D 21.3 · 2022 5/73


© Siemens 2022

System components for SINAMICS S120 Chassis and Chassis-2 Units


Supplementary system components
TM31 Terminal Module

■ Overview ■ Selection and ordering data


Description Article No.
TM31 Terminal Module 6SL3055-0AA00-3AA1
Without DRIVE-CLiQ cable
Accessories for re-ordering
Dust protection blanking plugs 6SL3066-4CA00-0AA0
(50 units)
For DRIVE-CLiQ port

For the SINAMICS S150 and SINAMICS S120 Cabinet Modules,


the TM31 Terminal Module can be ordered as an option by
specifying order code G60 or G61.

TM31 Terminal Module


With the TM31 Terminal Module, the number of available digital
inputs and outputs and the number of analog input and outputs
within a drive can be expanded.
5 The TM31 Terminal Module also features relay outputs with
changeover contact and a temperature sensor input.

■ Design
The following are located on the TM31 Terminal Module:
• 8 digital inputs
• 4 bidirectional digital inputs/outputs
• 2 relay outputs with changeover contact
• 2 analog inputs
• 2 analog outputs
• 1 temperature sensor input for KTY84-130, Pt1000 or PTC
(Pt1000 can be used from firmware V4.7 HF17 and higher)
• 2 DRIVE-CLiQ sockets
• 1 connection for the electronics power supply via the 24 V DC
supply connector
• 1 PE/protective conductor connection
The status of the TM31 Terminal Module is indicated via a multi-
color LED.
The TM31 Terminal Module can be snapped onto a TH 35
standard mounting rail in accordance with EN 60715
(IEC 60715).
The signal cable shield can be attached to the TM31 Terminal
Module via a shield connection terminal, e.g. type SK8 supplied
by Phoenix Contact or type KLBÜ CO 1 supplied by Weidmüller.
The shield connection terminal must not be used as a strain relief
mechanism.

5/74 Siemens D 21.3 · 2022


© Siemens 2022

System components for SINAMICS S120 Chassis and Chassis-2 Units


Supplementary system components
TM31 Terminal Module

■ Technical specifications
TM31 Terminal Module TM31 Terminal Module
6SL3055-0AA00-3AA1 6SL3055-0AA00-3AA1
Power requirement, max. 0.5 A Analog outputs
At 24 V DC without taking account of (continuously short-circuit proof)
the digital outputs and DRIVE-CLiQ • Voltage range -10 ... +10 V
supply • Max. load current -3 ... +3 mA
• Conductor cross-section, max. 2.5 mm2 • Current ranges 4 ... 20 mA, -20 ... +20 mA,
• Fuse protection, max. 20 A 0 ... 20 mA
Digital inputs • Load resistance, max. 500  in the range -20 ... +20 mA
In accordance with IEC 61131-2 • Resolution 11 bits + sign
Type 1 • Conductor cross-section, max. 1.5 mm2
• Voltage -3 ... +30 V
Relay outputs
• Low level -3 ... +5 V CO contacts
(an open digital input is interpreted
as "low") • Max. load current 8A
• High level 15 ... 30 V • Operational voltage, max. 250 V AC, 30 V DC
• Current consumption at 24 V DC, 9 mA • Switching capacity, max.
typ. - At 250 V AC 2000 VA (cos  = 1)
• Delay times of digital inputs 1), ap- 750 VA (cos  = 0.4)
prox. - At 30 V DC 240 W (resistive load)
- LH 50 s • Required minimum current 100 mA
- HL 100 s • Conductor cross-section, max. 2.5 mm2
• Conductor cross-section, max. 1.5 mm2 Power loss, max. 10 W
Digital outputs PE connection M4 screw
(continuously short-circuit proof)
• Voltage 24 V DC Dimensions
• Width 50 mm (1.97 in)
5
• Load current per digital output, max. 100 mA
• Total current of digital outputs, max. 400 mA • Height 150 mm (5.91 in)
• Delay times of digital outputs 1) • Depth 111 mm (4.37 in)
- Typ. 150 s with 0.5 A resistive load Weight, approx. 0.49 kg (1.08 lb)
- Max. 500 s
Certificate of suitability cULus
• Conductor cross-section, max. 1.5 mm2
Analog inputs
a switch is used to toggle between
voltage and current input
• As voltage input
- Voltage range -10 ... +10 V
- Internal resistance Ri 100 k
- Resolution 2) 11 bits + sign
• As current input
- Current ranges 4 ... 20 mA, -20 ... +20 mA,
0 ... 20 mA
- Internal resistance Ri 250 
- Resolution 2) 10 bits + sign
• Conductor cross-section, max. 1.5 mm2

1) The specified delay times refer to the hardware. The actual reaction time
depends on the time slice in which the digital input/output is processed.
2) If the analog input is to be operated in the signal processing sense with
continuously variable input voltage, the sampling frequency fa = 1/ttime slice
must be at least twice the value of the highest signal frequency fmax.

Siemens D 21.3 · 2022 5/75


© Siemens 2022

System components for SINAMICS S120 Chassis and Chassis-2 Units


Supplementary system components
TM31 Terminal Module

■ Integration
The TM31 Terminal Module can communicate via DRIVE-CLiQ with the following Control Units.
• CU310-2 Control Unit
• CU320-2 Control Unit

+ +
ext.
24 V M M

X500 X501
X524 X521

DRIVE-CLiQ socket 0

DRIVE-CLiQ socket 1
+
+ 24 V + AI 0+ 1
+
- AI 0- 2
M AI 1+ 3
M +
M AI 1- 4
M -
P10 5

6
M
Terminal Module N10
7

TM31 M
8

5 X520
1 DI 0 X522
M -
2 DI 1 AO 0V+ 1
V
+
3 DI 2 AO 0- 2
M
4 + AO 0C+ 3
DI 3 A
M - 2)
-
5 AO 1V+ 4
V
M1 +
1) 6 M 5
AO 1-
M
+
AO 1C+ 6
A
-
7
+Temp
X540 + 24 V
8
1 - Temp

2
IC for 4)
0.15 A current
3 limitation X541
+ 1
4 3)
DI/DO 8 2
5
DI/DO 9 3
6
DI/DO 10 4
7
DI/DO 11 5
8
6
M

X530 X542
1 DI 4 1

2 DI 5 M 2
DO 0
3 DI 6 M 3

4 DI 7 4
M
5 DO 1 5
M2
1) M
6 6
M

1) The jumpers must be inserted


in this circuit example.
2) Can be parameterized individually
G_D212_EN_00029e
as current source.
3) Can be parameterized individually as output.
4) Current limitation can be parameterized (0.1 A or 1 A)

Connection example of TM31 Terminal Module

5/76 Siemens D 21.3 · 2022


© Siemens 2022

System components for SINAMICS S120 Chassis and Chassis-2 Units


Supplementary system components
TM41 Terminal Module

■ Overview ■ Design
The following are located on the TM41 Terminal Module:
• 4 bidirectional digital inputs/outputs
• 4 digital inputs (with galvanic isolation)
• 1 analog input
• 1 interface for emulation of TTL incremental encoder (RS422)
• 1 LED for signaling zero mark detection for encoder interface
• 2 DRIVE-CLiQ sockets
• 1 connection for the electronics power supply and to supply
the digital outputs via the 24 V DC supply connector
• 1 PE/protective conductor connection
The status of the TM41 Terminal Module is indicated via a multi-
color LED.
An LED next to the interface for TTL pulse encoder emulation is
illuminated as soon as a zero mark is detected.
The TM41 Terminal Module can be snapped onto a TH 35
standard mounting rail in accordance with EN 60715
The TM41 Terminal Module supplies TTL signals which emulate (IEC 60715).
an incremental encoder, e.g. to a higher-level control.
The encoder interface (incremental encoder emulation) can be The signal cable shield can be attached to the TM41 Terminal
linked to an encoder signal from the Control Unit, Module via a shield connection terminal, e.g. type SK8 supplied
e.g. incremental encoder sin/cos, by parameter assignment. by Phoenix Contact or type KLBÜ CO 1 supplied by Weidmüller.
The TM41 Terminal Module increases the number of digital
The shield connection terminal must not be used as a strain relief
mechanism.
5
inputs/outputs and analog inputs that are available in the drive
system.
■ Selection and ordering data
Description Article No.
TM41 Terminal Module 6SL3055-0AA00-3PA1
Without DRIVE-CLiQ cable
Accessories for re-ordering
Dust protection blanking plugs 6SL3066-4CA00-0AA0
(50 units)
For DRIVE-CLiQ port

Siemens D 21.3 · 2022 5/77


© Siemens 2022

System components for SINAMICS S120 Chassis and Chassis-2 Units


Supplementary system components
TM41 Terminal Module

■ Technical specifications
TM41 Terminal Module TM41 Terminal Module
6SL3055-0AA00-3PA1 6SL3055-0AA00-3PA1
Current requirement 0.5 A Pulse encoder emulation
(X524 at 24 V DC) without DRIVE- • Level TTL (RS422), A+, A-, B+, B-, zero
CLiQ supply or digital outputs (X514) track N+, N-
• Conductor cross-section, max. 2.5 mm2 • Limit frequency fmax. 512 kHz
• Fuse protection, max. 20 A • Ratio Any number of ratio/reduction ratio of
I/O Encoder pulses: Encoder emulation pulses
• Digital inputs/outputs Individually parameterizable as DI or Power loss, max. 12 W
DO
PE connection M4 screw
• Number of digital inputs/outputs 4
• Number of digital input/outputs 4 Dimensions
(with galvanic isolation) • Width 30 mm (1.18 in)
• Cables and connections Plug-in screw-type terminals • Height 151 mm (5.94 in)
• Conductor cross-section, max. 1.5 mm2 • Depth 110 mm (4.33 in)
Digital inputs Weight, approx. 0.32 kg (0.71 lb)
• Voltage Certificate of suitability cULus
- Without galvanic isolation -3 ... +30 V
- With galvanic isolation -30 ... +30 V
• Low level
(an open digital input is interpreted
as "low")
- Without galvanic isolation -3 ... +5 V
- With galvanic isolation -30 ... +5 V
5 • High level
• Current consumption at 24 V DC,
15 ... 30 V
<9 mA
typ.
• Delay times of digital inputs, max. 1)
- LH 3 ms
- HL 3 ms
Digital outputs
(continuously short-circuit proof)
• Voltage 24 V DC
• Load current per digital output, max. 0.5 A
• Delay times (resistive load) 1)
- L  H, typ. 50 s
- L  H, max. 100 s
- H  L, typ. 75 s
- H  L, max. 150 s
Analog input
(difference)
• Voltage range -10 ... +10 V
• Internal resistance 100 k
• Resolution 2) 12 bits + sign

1) The specified delay times refer to the hardware. The actual reaction time
depends on the time slice in which the digital input/output is processed.
2) If the analog input is to be operated in the signal processing sense with
continuously variable input voltage, the sampling frequency fa = 1/ttime slice
must be at least twice the value of the highest signal frequency fmax.

5/78 Siemens D 21.3 · 2022


© Siemens 2022

System components for SINAMICS S120 Chassis and Chassis-2 Units


Supplementary system components
TM41 Terminal Module

■ Integration
The TM41 Terminal Module can communicate via DRIVE-CLiQ with the following Control Units.
• CU310-2 Control Unit
• CU320-2 Control Unit

+
+
M
M
X500 X501

DRIVE-CLiQ socket 0

DRIVE-CLiQ socket 1
LED
X524 RDY
+ + 24 V

+
+ 24 V
M
M
M
M

Terminal Module
TM41

X521 3)
X520
1
5
1 A
DI/DO 0
2) 2
R
2
DI/DO 1 3
B
3
DI/DO 2
4
4
DI/DO 3
5
5 + 24 V_1
6
6 A*
+ 24 V_1
7
7 R*
+ 24 V_1
8
8 + 24 V_1 B*
9
M

X522
1 DI 0

2 DI 1 M

3 DI 2 M
4 DI 3
M
5
M1
1) M
6
M

X523
±10 V 1
AI 0– –
G_D211_EN_00072b

2
AI 0+ +
3
1) For this circuit example, the jumpers NC
must be inserted.
2) Can be individually parameterized as output.
3) 9-pin sub-D socket connector

Connection example of TM41 Terminal Module

Siemens D 21.3 · 2022 5/79


© Siemens 2022

System components for SINAMICS S120 Chassis and Chassis-2 Units


Supplementary system components
TM54F Terminal Module

■ Overview ■ Design
The following are located on the TM54F Terminal Module:
• 4 fail-safe digital outputs
• 10 fail-safe digital inputs
• 4 LEDs, single color for indicating the status of the read back
channel of the fail-safe digital outputs
• 4 LEDs, dual-color for indicating the status of the fail-safe
digital outputs
• 20 LEDs, dual-color for indicating the status of the fail-safe
digital inputs
• 3 LEDs, single color for indicating the status of the 24 V sensor
supplies
• 2 DRIVE-CLiQ sockets
• 2 connections for 24 V sensor supply, switchable
• 1 connection for 24 V sensor supply, not switchable
• 1 connection for the electronics power supply via the 24 V DC
supply connector
The TM54F Terminal Module is a dual-processor I/O interface • 1 connection for the 24 V power supply to digital outputs
with four fail-safe digital outputs and ten fail-safe digital inputs and sensors
for utilization of the Safety Integrated functions of the SINAMICS
drive system via external actuators and sensors. • 1 PE/protective conductor connection
The status of the TM54F Terminal Module is indicated via a multi-
5 Every available safety function integrated in the drive can be
controlled via the fail-safe digital inputs on the TM54F Terminal color LED.
Module. In the event that the parameterized safety functions of The TM54F Terminal Module can be snapped onto a TH 35
several drives operated together on a Control Unit are to be standard mounting rail in accordance with EN 60715
executed together, then these drives can be grouped in the (IEC 60715).
TM54F Terminal Module. The advantage of this approach is
that only one fail-safe digital input needs to be connected for The signal cable shield can be attached to the TM54F Terminal
these drives. Module via a shield connection terminal, e.g. type SK8 supplied
by Phoenix Contact or type KLBÜ CO 1 supplied by Weidmüller.
The fail-safe digital inputs and outputs have two channels and The shield connection terminal must not be used as a strain relief
are redundantly configured with an internal data cross-check mechanism.
using the two processors. A fail-safe digital output consists of
one P-switching and one M-switching output as well as one Pins for connector coding are included in the TM54F Terminal
digital input to read back the switching state. A fail-safe digital Module scope of supply.
input consists of two digital inputs.
Safety sensors can be connected over two switchable 24 V
■ Selection and ordering data
sensor supplies and can be evaluated over the fail-safe digital Description Article No.
inputs. The switchable 24 V sensor supply ensures that the fail-
safe digital inputs can be dynamized to detect dormant errors TM54F Terminal Module 6SL3055-0AA00-3BA0
(this dynamization is used to check the shutdown paths). Without DRIVE-CLiQ cable
An unswitchable 24 V sensor supply is additionally provided Accessories for re-ordering
by the TM54F Terminal Module for connecting undynamizable
Dust protection blanking plugs 6SL3066-4CA00-0AA0
safety sensors. (50 units)
The TM54F Terminal Module must be directly connected to For DRIVE-CLiQ port
a Control Unit via a DRIVE-CLiQ cable. Only one TM54F Terminal
Module can be assigned to each Control Unit. It is not For the SINAMICS G150, SINAMICS S150 and SINAMICS S120
permissible to make the TM54F connection via another Cabinet Modules, the TM54F Terminal Module can be ordered
DRIVE-CLiQ device, e.g. a Power Module, a Motor Module or as an option by specifying order code K87.
a Line Module.

5/80 Siemens D 21.3 · 2022


© Siemens 2022

System components for SINAMICS S120 Chassis and Chassis-2 Units


Supplementary system components
TM54F Terminal Module

■ Technical specifications
TM54F Terminal Module TM54F Terminal Module
6SL3055-0AA00-3BA0 6SL3055-0AA00-3BA0
Current requirement 0.2 A Scanning cycle tSI 4 ... 25 ms (adjustable)
(X524 at 24 V DC) without for fail-safe digital inputs or fail-safe
DRIVE-CLiQ supply digital outputs
• Conductor cross-section, max. 2.5 mm2 Power loss, max. 4.5 W
• Fuse protection, max. 20 A At 24 V
Max. current requirement ext. 24 V 4 A PE connection M4 screw
for supplying the digital outputs and
24 V sensor supply (X514 at 24 V DC) Dimensions
• Conductor cross-section, max. 2.5 mm2 • Width 50 mm (1.97 in)
• Fuse protection, max. 20 A • Height 151 mm (5.94 in)
• Depth 110 mm (4.33 in)
I/O
• Number of fail-safe digital inputs 10 Weight, approx. 0.9 kg (1.98 lb)
• Number of fail-safe digital outputs 4 Certificate of suitability cULus
• 24 V sensor supply 3, of which 2 can be temporarily shut
down using an internal test routine for Safety Integrated Acc. to IEC 61508 SIL 2
dynamizing fail-safe digital inputs, and EN ISO 13849-1 PL d and
current carrying capacity 0.5 A each Category 3
• Cables and connections Plug-in screw-type terminals
• Conductor cross-section, max. 1.5 mm2
Digital inputs
in accordance with IEC 61131-2
Type 1, with galvanic isolation
• Voltage
• Low level
-3 ... +30 V
-3 ... +5 V
5
(an open digital input is interpreted
as "low")
• High level 15 ... 30 V
• Current consumption at 24 V DC, >3.2 mA
typ.
• Delay time of digital inputs, approx.
1)

- L  H, typ. 30 s
- H  L, typ. 60 s
• Safe state Low level (for inputs that can be
inverted: without inversion)
Digital outputs
(continuously short-circuit proof)
• Voltage 24 V DC
• Load current per fail-safe digital 0.5 A
output, max. 2)
• Delay times (resistive load) 1)
- L  H, typ. 300 s
- H  L, typ. 350 s
• Safe state Output switched off

1) The specified delay times refer to the hardware. The actual reaction time
depends on the time slice in which the digital input/output is processed.
2) The total current of all fail-safe digital outputs must not exceed 5.33 A.

Siemens D 21.3 · 2022 5/81


© Siemens 2022

System components for SINAMICS S120 Chassis and Chassis-2 Units


Supplementary system components
TM54F Terminal Module

■ Integration
The TM54F Terminal Module can communicate via DRIVE-CLiQ with the following Control Units.
• CU310-2 Control Unit
• CU320-2 Control Unit

+ +
M M
X500 X501
X524 +

DRIVE-CLiQ socket 1
DRIVE-CLiQ socket 0
+ 24 V

+
Terminal Module
M M
TM54F
M M

X514 + + 24 V ext

+
IC for
current
M M1 limitation

M M1

X520 1 L3+

2 M1

5 X521
1 L1 L2
1 X531 M +
5)
2) Sensor DI 10 2
2 DI 0 DO1
DI 11+ 3
3 DI 1+ M1 M1 DO2
1)
& F-DI 0 F-DI 5 & 1)
4 DI 2 DI 12 4

1) Safety switch
3) Sensor 5 DI 3+ 1) DI 13+ 5 device XY
M1 F-DI 1 F-DI 6
6 DI 1- 1)
& & 1)
M1
DI 11- 6

7 DI 3- DI 13- 7

8 M1 M1 8
+ M

4) X522 X532
1 DI 4 DI 14 1
DO+
M1 & & M1
2 DI 5+ 1) F-DI 2 F-DI 7 DI 15+ 2
1)
DO-
3 DI 6 DI 16 3
1) 1)
Safety switch 4 DI 7+ DI 17+ 4
device XY
M1
1)
& F-DI 3 F-DI 8 & M1
1)
5 DI 8 DI 18 5

6 DI 9+ 1) 1) DI 19+ 6
F-DI 4 F-DI 9
M1 & & M1
7 DI 5- 1) 1) DI 15- 7

8 DI 7- DI 17- 8

9 DI 9- DI 19- 9
+ 24 V ext. 6)
10 M1 M1 10
Load circuit
X523 DI 20 DI 22 X533
1 1
M1 M1
F-DO 0 F-DO 2 7)
2 DO 0+ DO 2+ 2
+ 24 V + 24 V
3 DO 0- M1 DO 2- 3
M1

X525 DI 21 DI 23 1
1
M1 M1
2 DO 1+ F-DO 1 F-DO 3 DO 3+ 2
+ 24 V + 24 V
3 DO 1-
M1 M1 DO 3- 3
X535
G_D211_EN_00201

1) Inversion can be parameterized 5) Sensor consists of 2 standard digital outputs of a safety relay/F control
2) Sensor with NC/NO contacts (inversion for digital input 1 can be parameterized) 6) Control of an actuator via fail-safe digital output
3) Sensor with NC/NC contacts 7) Positively-driven auxiliary contacts
4) Sensor is a fail-safe digital output of a safety relay/F control

Connection example of TM54F Terminal Module

5/82 Siemens D 21.3 · 2022


© Siemens 2022

System components for SINAMICS S120 Chassis and Chassis-2 Units


Supplementary system components
TM120 Terminal Module

■ Overview ■ Selection and ordering data


Description Article No.
TM120 Terminal Module 6SL3055-0AA00-3KA0
Without DRIVE-CLiQ cable
Accessories for re-ordering
Dust protection blanking plugs 6SL3066-4CA00-0AA0
(50 units)
For DRIVE-CLiQ port

■ Technical specifications
TM120 Terminal Module
6SL3055-0AA00-3KA0
Power requirement, max. 0.5 A
at 24 V DC
• Conductor cross-section, max. 2.5 mm2
• Fuse protection, max. 20 A
Temperature sensor inputs
The inputs can be individually param-
eterized to evaluate sensors of type
KTY84-130, Pt1000, PTC or tempera-
ture switches
• Conductor cross-section 0.2 ... 6 mm2
• Constant current per sensor, approx. 2 mA
• Safe electrical separation up to line 480 V AC
5
Four temperature sensors can be evaluated via the TM120
Terminal Module. The temperature sensor inputs are safely voltage, max.
electrically isolated from the evaluation electronics in the TM120 Power loss, typically 2.4 W
Terminal Module and are suitable for evaluating the temperature PE connection M4 screw
of special motors, e.g. SIMOTICS L-1FN linear motors and
SIMOTICS T-1FW6 built-in torque motors. Dimensions
• Width 30 mm (1.18 in)

■ Design • Height
• Depth
150 mm (5.91 in)
111 mm (4.37 in)
The following are located on the TM120 Terminal Module: Weight, approx. 0.41 kg (0.90 lb)
• 4 temperature sensor inputs for KTY84-130, Pt1000 or PTC
(Pt1000 can be used from firmware V4.7 HF17 and higher)
• 2 DRIVE-CLiQ sockets
• 1 connection for the electronics power supply via the 24 V DC
supply connector
• 1 PE/protective conductor connection
The status of the TM120 Terminal Module is indicated using
a multi-color LED.
The TM120 Terminal Module can be snapped onto a TH 35
standard mounting rail in accordance with EN 60715
(IEC 60715).

Siemens D 21.3 · 2022 5/83


© Siemens 2022

System components for SINAMICS S120 Chassis and Chassis-2 Units


Supplementary system components
TM120 Terminal Module

■ Integration
The TM120 Terminal Module can communicate via DRIVE-CLiQ with the following Control Units with SINAMICS firmware version V4.3
and higher:
• CU310-2 Control Unit
• CU320-2 Control Unit

+ +
ext.
24 V M M

to Motor Module from Sensor Module

X500 X501
X524

DRIVE-CLiQ socket 0

DRIVE-CLiQ socket 1
+ +24 V
+
M M

M M

5 Terminal Module TM120

X521

-Temp
+Temp
-Temp
+Temp
-Temp
+Temp
-Temp
+Temp

G_D211_EN_00261

Example connection of a TM120 Terminal Module

5/84 Siemens D 21.3 · 2022


© Siemens 2022

System components for SINAMICS S120 Chassis and Chassis-2 Units


Supplementary system components
TM150 Terminal Module

■ Overview ■ Selection and ordering data


Description Article No.
TM150 Terminal Module 6SL3055-0AA00-3LA0
Without DRIVE-CLiQ cable
Accessories for re-ordering
Dust protection blanking plugs 6SL3066-4CA00-0AA0
(50 units)
For DRIVE-CLiQ port

For the SINAMICS S120 Cabinet Modules, the TM150 Terminal


Module can be ordered as an option by specifying order code
G51 or G51 to G54.

■ Technical specifications
TM150 Terminal Module
6SL3055-0AA00-3LA0
Power requirement, max. 0.5 A
at 24 V DC
• Conductor cross section, max. 2.5 mm2
• Fuse protection, max. 20 A
Temperature sensor inputs
The inputs can be parameterized
individually for the evaluation of
sensors
• Conductor cross section, max. 1.5 mm2
5
The TM150 Terminal Module is a DRIVE-CLiQ component for
• Measuring current per sensor, 0.8 mA
temperature evaluation. The temperature is measured in approx.
a temperature range from -99 °C to +250 °C for the following
temperature sensors: Power loss 1.6 W

• Pt100 (with monitoring for wire breaks and short-circuits) PE connection M4 screw
• Pt1000 (with monitoring for wire breaks and short-circuits) Dimensions
• Width 30 mm (1.18 in)
• KTY84 (with monitoring for wire breaks and short-circuits)
• Height 150 mm (5.91 in)
• PTC (with monitoring for short-circuit ) • Depth 111 mm (4.37 in)
• Bimetallic NC contact (without monitoring) Weight, approx. 0.41 kg (0.90 lb)
For the temperature sensor inputs, for each terminal block the
evaluation can be parameterized for 1×2-wire, 2×2-wire, 3-wire
or 4-wire. There is no galvanic isolation in the TM150 Terminal
Module.
The temperature channels of a TM150 can be subdivided into
3 groups and evaluated together.

■ Design
The following are located on the TM150 Terminal Module:
• 6 ... 12 temperature sensor inputs
• 2 DRIVE-CLiQ sockets
• 1 connection for the electronics power supply via the 24 V DC
supply connector
• 1 PE/protective conductor connection
The status of the TM150 Terminal Module is indicated via a multi-
color LED.
The TM150 Terminal Module can be snapped onto a TH 35
standard mounting rail in accordance with EN 60715
(IEC 60715).

Siemens D 21.3 · 2022 5/85


© Siemens 2022

System components for SINAMICS S120 Chassis and Chassis-2 Units


Supplementary system components
TM150 Terminal Module

■ Integration
The TM150 Terminal Module can communicate via DRIVE-CLiQ with the following Control Units.
• CU310-2 Control Unit
• CU320-2 Control Unit

ext. + +
24 V M M

X500 X501
X524
+ +24 V

DRIVE-CLiQ socket 0

DRIVE-CLiQ socket 1
+
X531
M M
+Temp 1
M M Channel 0
-Temp 2
3 2×2-wire
+Temp
4 Channel 6
-Temp

5 +Temp
1
X532

2 Channel 1
-Temp
3 2×2-wire
+Temp
Channel 7
Terminal Module -Temp 4

TM150 X533
1
+Temp
Channel 2
2
-Temp
2×2-wire
3
+Temp
Channel 8
-Temp 4

X534
1
+
2
-
3 Channel 3
+ lc 3-wire
4
- lc
X535
1
+
2
-
3 Channel 4
+ lc
4-wire
- lc 4

X536
1
+
2
-
3 Channel 5
+ lc
4-wire
- lc 4

G_D211_EN_00295

Connection example of a TM150 Terminal Module

5/86 Siemens D 21.3 · 2022


© Siemens 2022

System components for SINAMICS S120 Chassis and Chassis-2 Units


Supplementary system components
VSM10 Voltage Sensing Module

■ Overview ■ Selection and ordering data


Description Article No.
VSM10 Voltage Sensing Module 6SL3053-0AA00-3AA1
Without DRIVE-CLiQ cable
Accessories for re-ordering
Dust protection blanking plugs 6SL3066-4CA00-0AA0
(50 units)
For DRIVE-CLiQ port

For the SINAMICS S150 and SINAMICS S120 Cabinet Modules,


the VSM10 Voltage Sensing Module can be ordered as an option
by specifying order code K51 in order to implement the flying
restart function.

■ Technical specifications
VSM10 Voltage Sensing Module
6SL3053-0AA00-3AA1
Power requirement, max. 0.2 A
The VSM10 Voltage Sensing Module enables the line or motor at 24 V DC
voltage characteristic to be measured precisely. The phase • Conductor cross-section, max. 2.5 mm2
differential voltage can be measured, either grounded (in the Power loss, max. 10 W
delivery state with jumper plugged in) or isolated.
Line voltage detection
In addition, the VSM10 is used to connect to rotating
synchronous motors – or for a "quick flying restart" of rotating
• Insulation resistance neutral point – >10 M
ground when jumper is not inserted 5
induction motors. • Input resistance
- Terminal X521 >362 k/phase
■ Design - Terminal X522 >2.5 M/phase
Analog inputs
The VSM10 Voltage Sensing Module has the following (reserved for monitoring an Active
connections and interfaces: Interface Module in chassis format)
• 1 connection for direct voltage sensing up to 690 V • Internal resistance, approx. 100 k
(between differential inputs)
• 1 connection for voltage sensing using voltage transformers; • Resolution 12 bits + sign
maximum voltage 100 V
PE connection M4 screw
• 2 analog inputs (reserved for monitoring of resonance in the
Dimensions
Active Interface Module in chassis format)
• Width 50 mm (1.97 in)
• 1 temperature sensor input for KTY84-130, Pt1000 or PTC • Height 150 mm (5.91 in)
(Pt1000 can be used from firmware V4.7 HF17 and higher) • Depth 111 mm (4.37 in)
• 1 DRIVE-CLiQ socket Weight, approx. 1 kg (2.20 lb)
• 1 connection for the electronics power supply via the 24 V DC Certificate of suitability cULus
supply connector
• 1 plug-in jumper for either grounded (delivery state)
or isolated measurement
• 1 PE/protective conductor connection
The status of the VSM10 Voltage Sensing Module is indicated
via a dual-color LED.
The VSM10 Voltage Sensing Module can be snapped onto
a TH 35 standard mounting rail in accordance with
EN 60715 (IEC 60715).

Siemens D 21.3 · 2022 5/87


© Siemens 2022

System components for SINAMICS S120 Chassis and Chassis-2 Units


Supplementary system components
VSM10 Voltage Sensing Module

■ Integration
The VSM10 Voltage Sensing Module can communicate with the following Control Units via DRIVE-CLiQ:
• CU310-2 Control Unit
• CU320-2 Control Unit
On the SINAMICS S120 chassis format, the VSM10 Voltage Sensing Module is integrated in the Active Interface Modules and
Smart Line Modules.

X500

DRIVE-CLiQ socket
X524
+ + +24 V
ext. +
24 V
M M
M
M
M

Voltage Sensing
Module VSM10
X521
1 U
Line voltage detection
2 V via transformers
LED

5 READY 3 W max. 100 V

X520 +
or
1 –
+ X522
2 –
1 U
3 Line voltage detection
+ 2 V via direct line connection
4 –
3 W max. 690 V
5 +Temp
6 -Temp

G_D211_EN_00069a
X530 1)
1) Point grounding (delivery state with jumper plugged in) 1 2

Connection example of a VSM10 Voltage Sensing Module

5/88 Siemens D 21.3 · 2022


© Siemens 2022

System components for SINAMICS S120 Chassis and Chassis-2 Units


Supplementary system components
Safe Brake Adapter SBA

■ Overview ■ Selection and ordering data


Description Article No.
Safe Brake Adapter
• 230 V AC/2 A 6SL3355-2DX00-1AA0
Accessories
Pre-assembled interface cable to connect 6SL3060-4DX04-0AA0
the SBA to the electronics module (4 m)

■ Technical specifications
Safe Brake Adapter
6SL3355-2DX00-1AA0
Electronics power supply
Supply voltage 24 V DC
(via the Control Interface Module) (20.4 … 28.8 V DC)
Supply voltage of the motor holding 230 V AC
brake
Max. permissible current
The Safe Brake Adapter SBA is needed for the implementation consumption 1)
of a safe brake control (Safety Integrated function SBC) in • Motor holding brake 2A
accordance with IEC 61800-5-2. • Fast de-energization 2A
The Safe Brake Adapter is available for a 230 V AC brake control Max. permissible cable lengths
voltage.
Note:
• to the Control Interface Module
• to the brake
10 m (32.8 ft)
300 m (984 ft)
5
The SBA is approved for the IEC area. Safe Brake Adapter with Max. conductor cross section 2.5 mm2
UL approval are available on request. The UL approval is valid Dimensions
for a maximum permissible current consumption of 1.5 A • Width 75 mm (2.95 in)
(inductive). • Height 111 mm (4.37 in)
• Depth 89 mm (3.50 in)
■ Design Weight, approx. 0.25 kg (0.55 lb)
The Safe Brake Adapter SBA has the following connections and Safety Integrated According to IEC 61508 SIL2 and
interfaces: EN ISO 13849-1 PLd and Category 3
• 1 connection for the connecting cable to the Power
Module/Motor Module
• 1 connection for the external 230 V AC supply
• 1 connection for motor holding brake
• 1 connection for fast de-excitation

1) The UL approval is valid for a maximum permissible current consumption


of 1.5 A (inductive).

Siemens D 21.3 · 2022 5/89


© Siemens 2022

System components for SINAMICS S120 Chassis and Chassis-2 Units


Supplementary system components
Safe Brake Adapter SBA

■ Integration
The control and feedback signal regarding the switching state of It is available as option (K88) for SINAMICS S150 and S120
the SBA relay is realized via terminals of the Control Interface Cabinet Modules.
Module (CIM). The excitation coil of the holding brake is
connected directly at the SBA. For the SINAMICS S120 units, chassis format, the brake supply
voltage must be connected externally at the SBA.
The SBA can be ordered as an additional component for
SINAMICS S120 built-in units in chassis format.

Safe Brake Adapter Motor Module /


SBA Power Module
230 V AC Control Interface
-X11 Module (CIM)
-X46
BR+ 1
1 BR Output+
BR- 2
Connecting cable 2 BR Output-
FB+ 3 3 FB Input+
6SL3060-4DX04-0AA0
LEDs FB- 4 4 FB Input-
230 V OK P24 -X42
5
K1 ON M 6 2 P24
K2 ON 3 M
-X15
AUX1 1
5 External
Fast
de-excitation AUX2 2

voltage supply -X12 -X14


1 L SBA_BR_L 1 G_D213_EN_00091b

W2
U2

PE
V2
230 V AC 2 N SBA_BR_N 2

M
3~

Connection example of a Safe Brake Adapter

5/90 Siemens D 21.3 · 2022


© Siemens 2022

System components for SINAMICS S120 Chassis and Chassis-2 Units


Encoder system connection
Encoder system connection

■ Overview ■ More information


Motors with DRIVE-CLiQ interface Motor encoder and temperature signals should preferably be
connected to the corresponding Motor Module or Power Module
DRIVE-CLiQ is the preferred method for connecting the encoder and external encoders to the Control Unit. However, the
systems to SINAMICS S120. Motors with DRIVE-CLiQ interface DRIVE-CLiQ connections can also be bundled via DRIVE-CLiQ
are available for this purpose. Hub Modules.
Motors with a DRIVE-CLiQ interface can be directly connected Safety Integrated
to the associated Motor Module using MOTION-CONNECT
DRIVE-CLiQ cables. The MOTION-CONNECT DRIVE-CLiQ The Safety Integrated Extended Functions of the SINAMICS
cable connection at the motor has degree of protection IP67. drive system require suitable encoders.
The DRIVE-CLiQ interface supplies the motor encoder via the Belt-driven motor
integrated 24 V DC supply and transfers the motor encoder and
temperature signals and the electronic rating plate data, Unfavorable material combinations generate static electricity
e.g. a unique identification number and rated data (voltage, between the belt pulley and the belt. Electrostatic charging must
current, torque) to the Control Unit. This means that for the be prevented, since this can discharge via the motor shaft and
various encoder types – e.g. resolver or absolute encoder – the encoder, thereby causing disturbances in the encoder
different encoder cables with varying permissible lengths are no signals. One remedy is to use an anti-static belt.
longer required; just one cable type, MOTION-CONNECT
DRIVE-CLiQ with varying permissible lengths, can be used for
all encoders.
These motors simplify commissioning and diagnostics, as the
motor and encoder type are identified automatically.
Motors without DRIVE-CLiQ interface
The encoder and temperature signals of motors without
DRIVE-CLiQ interfaces, as well as those of external encoders,
5
must be connected via Sensor Modules. Sensor Modules
Cabinet-Mounted are available in degree of protection IP20 for
control cabinet installation, as well as Sensor Modules External-
Mounted in degree of protection IP67.
Only one encoder system can be connected to each
Sensor Module.

Siemens D 21.3 · 2022 5/91


© Siemens 2022

System components for SINAMICS S120 Chassis and Chassis-2 Units


Encoder system connection
SMC10 Sensor Module Cabinet-Mounted

■ Overview ■ Selection and ordering data


Description Article No.
SMC10 Sensor Module Cabinet-Mounted 6SL3055-0AA00-5AA3
Without DRIVE-CLiQ cable
Accessories for re-ordering
Dust protection blanking plugs 6SL3066-4CA00-0AA0
(50 units)
For DRIVE-CLiQ port

For the SINAMICS S150 and SINAMICS S120 Cabinet Modules,


the SMC10 Sensor Module Cabinet-Mounted can be ordered as
an option by specifying order code K46.

■ Integration
SMC10 Sensor Modules Cabinet-Mounted communicate with
a Control Unit via DRIVE-CLiQ.

■ Technical specifications
The SMC10 Sensor Module Cabinet-Mounted is required to
evaluate the encoder signals of motors without a DRIVE-CLiQ SMC10 Sensor Module
interface. External encoders can also be connected via the Cabinet-Mounted
SMC10. 6SL3055-0AA00-5AA3
Current requirement, max. 0.2 A
5 The following encoder signals can be evaluated:
• 2-pole resolver
at 24 V DC,
without taking encoder into account
• Conductor cross-section, max. 2.5 mm2
• Multi-pole resolver
• Fuse protection, max. 20 A

■ Design Power loss, max. 10 W


Encoders which can be evaluated • 2-pole resolver
The SMC10 Sensor Module Cabinet-Mounted features the • Multi-pole resolver
following connections and interfaces as standard: • Excitation voltage, rms 4.1 V
• 1 encoder connection including motor temperature sensing • Excitation frequency 5 ... 16 kHz depending on the current
controller clock cycle of the Motor
(KTY84-130, Pt1000 or PTC) via SUB-D connector Module or Power Module
• 1 DRIVE-CLiQ interface • Transformation ratio 0.5
• 1 connection for the electronics power supply via the 24 V DC • Encoder frequency, max. 2 kHz (120000 rpm) depending on
the number of resolver pole pairs and
supply connector current controller clock cycle of the
• 1 PE/protective conductor connection Motor Module or Power Module
• Signal subdivision (interpolation), 16384 times (14 bits)
The status of the SMC10 Sensor Module Cabinet-Mounted is max.
indicated via a multi-color LED. • Cable length to encoder, max. 130 m (427 ft)
The SMC10 Sensor Module Cabinet-Mounted can be snapped PE connection M4 screw
onto a TH 35 standard mounting rail according to Dimensions
EN 60715 (IEC 60715). • Width 30 mm (1.18 in)
The signal cable shield is connected via the encoder system • Height 150 mm (5.91 in)
connector and can also be connected to the SMC10 Sensor • Depth 111 mm (4.37 in)
Module Cabinet-Mounted via a shield connection terminal, Weight, approx. 0.45 kg (0.99 lb)
e.g. Phoenix Contact type SK8 or Weidmüller type KLBÜ CO 1.
Certificate of suitability cULus
The shield connection terminal must not be used as a strain relief
mechanism.

5/92 Siemens D 21.3 · 2022


© Siemens 2022

System components for SINAMICS S120 Chassis and Chassis-2 Units


Encoder system connection
SMC20 Sensor Module Cabinet-Mounted

■ Overview ■ Selection and ordering data


Description Article No.
SMC20 Sensor Module Cabinet-Mounted 6SL3055-0AA00-5BA3
Without DRIVE-CLiQ cable
Accessories for re-ordering
Dust protection blanking plugs 6SL3066-4CA00-0AA0
(50 units)
For DRIVE-CLiQ port

For the SINAMICS S150 and SINAMICS S120 Cabinet Modules,


the SMC20 Sensor Module Cabinet-Mounted can be ordered as
an option by specifying order code K48.

■ Integration
SMC20 Sensor Modules Cabinet-Mounted communicate with
a Control Unit via DRIVE-CLiQ.

■ Technical specifications
The SMC20 Sensor Module Cabinet-Mounted is required to
evaluate the encoder signals of motors without a DRIVE-CLiQ SMC20 Sensor Module
interface. External encoders can also be connected via the Cabinet-Mounted
SMC20. 6SL3055-0AA00-5BA3
Power requirement, max. 0.2 A
The following encoder signals can be evaluated:
• Incremental encoder sin/cos 1 Vpp
at 24 V DC,
without taking encoder into account
5
2
• Conductor cross-section, max. 2.5 mm
• Absolute encoder EnDat 2.1
• Fuse protection, max. 20 A
• SSI encoder with incremental signals sin/cos 1 Vpp
Power loss, max. 10 W
(firmware version 2.4 and later)
Encoders which can be evaluated • Incremental encoder sin/cos 1 Vpp
The motor temperature can also be sensed using a PTC • Absolute encoder EnDat 2.1
thermistor KTY84-130, Pt1000 or PTC. • SSI encoder with incremental
signals sin/cos 1 Vpp

■ Design • Encoder supply


(firmware version 2.4 and later)
5 V DC/0.35 A
The SMC20 Sensor Module Cabinet-Mounted features the • Encoder frequency incremental 500 kHz
signals, max.
following connections and interfaces as standard:
• Signal subdivision (interpolation), 16384 times (14 bits)
• 1 encoder connection including motor temperature sensing max.
(KTY84-130, Pt1000 or PTC) via SUB-D connector • SSI baud rate 100 ... 1000 kBaud
• 1 DRIVE-CLiQ interface • Cable length to encoder, max. 100 m (328 ft)

• 1 connection for the electronics power supply via the 24 V DC PE connection M4 screw
supply connector Dimensions
• 1 PE/protective conductor connection • Width 30 mm (1.18 in)
• Height 150 mm (5.91 in)
The status of the SMC20 Sensor Module Cabinet-Mounted is • Depth 111 mm (4.37 in)
indicated via a multi-color LED.
Weight, approx. 0.45 kg (0.99 lb)
The SMC20 Sensor Module Cabinet-Mounted can be snapped Certificate of suitability cULus
onto a TH 35 standard mounting rail according to
EN 60715 (IEC 60715).
The signal cable shield is connected via the encoder system
connector and can also be connected to the SMC20 Sensor
Module Cabinet-Mounted via a shield connection terminal,
e.g. Phoenix Contact type SK8 or Weidmüller type KLBÜ CO 1.
The shield connection terminal must not be used as a strain relief
mechanism.

Siemens D 21.3 · 2022 5/93


© Siemens 2022

System components for SINAMICS S120 Chassis and Chassis-2 Units


Encoder system connection
SMC30 Sensor Module Cabinet-Mounted

■ Overview ■ Selection and ordering data


Description Article No.
SMC30 Sensor Module Cabinet-Mounted 6SL3055-0AA00-5CA2
Without DRIVE-CLiQ cable
Accessories for re-ordering
Dust protection blanking plugs 6SL3066-4CA00-0AA0
(50 units)
For DRIVE-CLiQ port

For the SINAMICS S150 and SINAMICS S120 Cabinet Modules,


the SMC30 Sensor Module Cabinet-Mounted can be ordered as
an option by specifying order code K50.
A second SMC30 can be ordered as an option with the order
code K52 for reliable actual value acquisition when using the
Safety Integrated Extended Functions.

■ Integration
SMC30 Sensor Modules Cabinet-Mounted communicate with
The SMC30 Sensor Module Cabinet-Mounted is required to a Control Unit via DRIVE-CLiQ.
evaluate the encoder signals of motors without a DRIVE-CLiQ
interface. External encoders can also be connected via the
SMC30. ■ Technical specifications
5 The following encoder signals can be evaluated:
• Incremental encoders TTL/HTL with/without open-circuit
SMC30 Sensor Module Cabinet-
Mounted
6SL3055-0AA00-5CA2
detection (open-circuit detection is only available with bipolar
signals) Current requirement, max. 0.2 A
at 24 V DC,
• SSI encoder with TTL/HTL incremental signals without taking encoder into account
• SSI encoder without incremental signals • Conductor cross-section, max. 2.5 mm2
• Fuse protection, max. 20 A
The motor temperature can also be sensed using a PTC
Power loss, max. 10 W
thermistor KTY84-130, Pt1000 or PTC.
Encoders which can be evaluated • Incremental encoder TTL/HTL
■ Design • SSI encoder with TTL/HTL
incremental signals
• SSI encoder without incremental
The SMC30 Sensor Module Cabinet-Mounted features the signals
following connections and interfaces as standard: • Input current range TTL/HTL 4 ... 20 mA (typ. 10 mA)
• 1 encoder connection including motor temperature sensing • Encoder supply 24 V DC/0.35 A or 5 V DC/0.35 A
(KTY84-130, Pt1000 1) or PTC) either via SUB-D connector or • Encoder frequency, max. 500 kHz
via terminals • SSI baud rate 100 ... 1000 kBaud
• Limiting frequency 500 kHz
• 1 DRIVE-CLiQ interface
• Resolution absolute position SSI 30 bits
• 1 connection for the electronics power supply via the 24 V DC • Cable length, max.
supply connector - TTL encoder 100 m (328 ft) (only bipolar signals
• 1 PE/protective conductor connection permitted)1)
- HTL encoder 100 m (328 ft) for unipolar signals
The status of the SMC30 Sensor Module Cabinet-Mounted is 300 m (984 ft) for bipolar signals1)
indicated via a multi-color LED. - SSI encoder 100 m (328 ft)
The SMC30 Sensor Module Cabinet-Mounted can be snapped PE connection M4 screw
onto a TH 35 standard mounting rail in according to Dimensions
EN 60715 (IEC 60715). • Width 30 mm (1.18 in)
The maximum encoder cable length between SMC30 modules • Height 150 mm (5.91 in)
and encoders is 100 m. For HTL encoders, this length can be • Depth 111 mm (4.37 in)
increased to 300 m if the A+/A- and B+/B- signals are evaluated Weight, approx. 0.45 kg (0.99 lb)
and the power supply cable has a minimum cross-section Certificate of suitability cULus
of 0.5 mm2.
The signal cable shield can be connected to the SMC30 Sensor
Module Cabinet-Mounted via a shield connection terminal,
e.g., Phoenix Contact type SK8 or Weidmüller type KLBÜ CO 1.
The shield connection terminal must not be used as a strain relief
mechanism.

1) Signal cables twisted in pairs and shielded.

5/94 Siemens D 21.3 · 2022


© Siemens 2022

System components for SINAMICS S120 Chassis and Chassis-2 Units


Connection system
Signal cables

■ Overview
Signal cables are required for the DRIVE-CLiQ connection
between different components. Signal cables are pre-
assembled and are sold by the meter. The following signal
cables are available:
• DRIVE-CLiQ signal cables
• MOTION-CONNECT DRIVE-CLiQ signal cables
• MOTION-CONNECT pre-assembled signal cables

MOTION-CONNECT DRIVE-CLiQ signal cable with IP20/IP67 connector


Type of delivery for pre-assembled signal cables
Application Connection 24 V cores MOTION- MOTION- MOTION- Length stages
on the module side/on CONNECT CONNECT CONNECT
the motor side 500
6FX2...
500
6FX5...
800PLUS
6FX8...
5
DRIVE-CLiQ signal line
Components with DRIVE-CLiQ interface, RJ45 IP20/RJ45 IP20 without 70 m (230 ft) – – To the decimeter
with internal or external 24 V DC power
supply in the control cabinet
Components with DRIVE-CLiQ interface RJ45 IP20/RJ45 IP20 with – 100 m (328 ft) 75 m (246 ft) To the decimeter
in the control cabinet
For built-in or built-on encoder systems RJ45 IP20/RJ45 IP67 with
with DRIVE-CLiQ interface.
RJ45 IP67/RJ45 IP67
Basic cable RJ45 IP20/M17 with
Extension M17/M17
Adapter cable RJ45 IP67/M17
M17/RJ45 IP67
Basic cable RJ45 IP20/M12 with – 100 m (328 ft) 75 m (246 ft) To the meter up
to 20 m (65.6 ft),
Extension M12/M12 beyond that in
Adapter cable RJ45 IP67/M12 30 m (98.4 ft) 30 m (98.4 ft) steps of 5 m
(16.4 ft)
M12/RJ45 IP67
M17/M12

Above 30 kg (66.1 lb) or 100 m (328 ft), the cables are supplied on drums, otherwise as coils.

Siemens D 21.3 · 2022 5/95


© Siemens 2022

System components for SINAMICS S120 Chassis and Chassis-2 Units


Connection system
Signal cables

■ Application ■ Design
DRIVE-CLiQ signal cables without 24 V DC cores If pre-assembled signal cables are to be installed in a cable
carrier in such a way that the connector would inhibit assembly,
are used to connect components with DRIVE-CLiQ connections pre-assembled cables without assembled connector can also
which have a separate or external 24 V DC power supply. be supplied. In this case, the contacts of the cables are crimped
MOTION-CONNECT DRIVE-CLiQ signal cables with 24 V DC and the connector housing is supplied separately.
cores After installing the cables, the customer assembles the
connector housing.
are used whenever components with DRIVE-CLiQ connections
must meet high requirements such as mechanical stress and oil The 6FX.002-2....-.... signal cables are available with crimped
resistance, e.g. where a connection is made outside the control contacts and with the connector housing supplied separately
cabinet between (not in the case of DRIVE-CLiQ signal cables and signal cables
with exposed core ends).
• Motor Modules and Sensor Modules
• Power Modules/Motor Modules and motors with DRIVE-CLiQ Signal cables with module-side connector housing supplied as
interface a separate accessory: In this case, the 6th position of the Article
No. must be changed from 0 to 1:
• Motor Modules and direct measuring systems with 6FX.012-2C...-.... (not for signal cables for connecting via
DRIVE-CLiQ interface (incl. non-Siemens measuring systems) terminals or 6FX.002-2AH00-...., 6FX.002-2CA12-....).
MOTION-CONNECT pre-assembled signal cables Signal cables with motor-side connector housing supplied as
are used whenever motor encoders on motors without a separate accessory. In this case, the 6th position of the Article
DRIVE-CLiQ interface are connected to Sensor Modules. No. must be changed from 0 to 4:
6FX.042-2C...-.... (not for signal cables for connecting via
terminals or 6FX8002-2BA20-…., 6FX8002-2BA21-….).
Note:
5 Once the contacts have latched into the insulator, they can no
longer be removed.

5/96 Siemens D 21.3 · 2022


© Siemens 2022

System components for SINAMICS S120 Chassis and Chassis-2 Units


Connection system
Signal cables

■ Selection and ordering data


Signal cable Length Connector/degree Connector/degree Basic cable
of protection of protection
module-side motor-side
Article No.
Pre-assembled DRIVE-CLiQ signal cables (without 24 V DC cores)
Fixed lengths 0.11 m (0.36 ft) RJ45/IP20 RJ45/IP20 6SL3060-4AB00-0AA0
0.16 m (0.52 ft) 6SL3060-4AD00-0AA0
0.21 m (0.69 ft) 6SL3060-4AF00-0AA0
0.26 m (0.85 ft) 6SL3060-4AH00-0AA0
0.31 m (1.02 ft) 6SL3060-4AK00-0AA0
0.36 m (1.18 ft) 6SL3060-4AM00-0AA0
0.41 m (1.35 ft) 6SL3060-4AP00-0AA0
0.60 m (1.97 ft) 6SL3060-4AU00-0AA0
0.95 m (3.12 ft) 6SL3060-4AA10-0AA0
1.20 m (3.94 ft) 6SL3060-4AW00-0AA0
1.45 m (4.76 ft) 6SL3060-4AF10-0AA0
1.60 m (5.25 ft) 6SL3060-4AG10-0AA0
2.10 m (6.89 ft) 6SL3060-4AB20-0AA0
2.40 m (7.87 ft) 6SL3060-4AE20-0AA0
2.80 m (9.19 ft) 6SL3060-4AJ20-0AA0 5
5.00 m (16.4 ft) 6SL3060-4AA50-0AA0
To the decimeter Max. 70 m (230 ft) RJ45/IP20 RJ45/IP20 6FX2002-1DC00-….
DRIVE-CLiQ MOTION-CONNECT 500 signal cables (with 24 V DC cores)
To the decimeter Max. 100 m (328 ft) RJ45/IP20 RJ45/IP20 6FX5002-2DC00-....
Max. 100 m (328 ft) RJ45/IP20 RJ45/IP67 6FX5002-2DC10-….
Max. 100 m (328 ft) RJ45/IP67 RJ45/IP67 6FX5002-2DC20-….
DRIVE-CLiQ MOTION-CONNECT 800PLUS signal cables (with 24 V DC cores)
To the decimeter Max. 75 m (246 ft) RJ45/IP20 RJ45/IP20 6FX8002-2DC00-….
Max. 75 m (246 ft) RJ45/IP20 RJ45/IP67 6FX8002-2DC10-.…
Max. 75 m (246 ft) RJ45/IP67 RJ45/IP67 6FX8002-2DC20-….

Siemens D 21.3 · 2022 5/97


© Siemens 2022

System components for SINAMICS S120 Chassis and Chassis-2 Units


Connection system
Signal cables

■ Selection and ordering data ■ More information


Length codes Further information is available:
• Catalog D 21.4 (SINAMICS S120 and SIMOTICS)
Description Article No. supplement
• Internet
Length codes for pre-assembled cables
- www.siemens.com/motion-connect
6FX.0.2-.....-     - www.siemens.com/industrymall
0 m (0 ft) 1
100 m (328 ft) 2
200 m (656 ft) 3
0 m (0 ft) A
10 m (32.8 ft) B
20 m (65.6 ft) C
30 m (98.4 ft) D
40 m (131 ft) E
50 m (164 ft) F
60 m (197 ft) G
70 m (230 ft) H
80 m (262 ft) J
90 m (295 ft) K
0 m (0 ft) A
1 m (3.28 ft) B

5 2 m (6.56 ft)
3 m (9.84 ft)
C
D
4 m (13.1 ft) E
5 m (16.4 ft) F
6 m (19.7 ft) G
7 m (23 ft) H
8 m (26.2 ft) J
9 m (29.5 ft) K
0 m (0 ft) 0
0.1 m (0.33 ft) 1
0.2 m (0.66 ft) 2
0.3 m (0.98 ft) 3
0.4 m (1.31 ft) 4
0.5 m (1.64 ft) 5
0.6 m (1.97 ft) 6
0.7 m (2.30 ft) 7
0.8 m (2.62 ft) 8
Examples: 1.0 m 1 A B 0
(3.28 ft) 1 A C 2
2.2 m 1 A J 0
(7.22 ft)
3 K K 0
8.0 m
(26.2 ft)
299.0 m
(981 ft)

Note:
Prefabricated cables with a length of 0 m (...-1AA0)
cannot be ordered!
Description Article No. supplement
Length code for cables sold by the meter1)
6FX.008-.....-   A 0
50 m (164 ft) 1 F
100 m (328 ft) 2 A
200 m (656 ft) 3 A
500 m (1640 ft) 6 A

1)
Note type of delivery. Power cables with core cross-section 4 x 4 m2
or 4 x 4 m2 with brake cores can be delivered in units of 1 m.

5/98 Siemens D 21.3 · 2022


© Siemens 2022

System components for SINAMICS S120 Chassis and Chassis-2 Units


Connection system
Signal cables

■ Integration
Connection overview for the CU320-2 Control Unit

SINAMICS S120 Article No.


Control Unit Pre-assembled cable
CU320-2

X400- Basic Line


X402 Module
6SL3060-4A..0-0AA0
X100- ≤ 5 m (16 ft) X400- Smart Line
X103 6FX2002-1DC00-.... X402 Module
≤ 70 m (230 ft) 6SL3060-4A..0-0AA0
X400- Active Line ≤ 5 m (16 ft) Active Interface
X500
X402 Module 6FX2002-1DC00-.... Module
≤ 70 m (230 ft)
6SL3060-4A..0-0AA0
X100- ≤ 5 m (16 ft) X400- Motor
X103 6FX2002-1DC00-.... X402 Module
≤ 70 m (230 ft)
6SL3060-4A..0-0AA0
X100- ≤ 5 m (16 ft) X500- Terminal
X103 6FX2002-1DC00-.... X501 Module
≤ 70 m (230 ft)

PROFIBUS connection
5
X126 6ES7972-0BA42-0XA0 (without PG socket)
6ES7972-0BB42-0XA0 (with PG socket)

6FX8002-1AA01-1AF0
X140 PC/PG
(5 m) (16 ft)
G_NC01_EN_00421g

Connection overview for the SIMOTION D4x5-2 Control Unit

Control Unit Article No.


SIMOTION Pre-assembled cable
D4x5-2

X400- Basic Line


X402 Module
6SL3060-4A..0-0AA0
X100- ≤ 5 m (16 ft) X400- Smart Line
X1051) 6FX2002-1DC00-.... X402 Module
≤ 70 m (230 ft) 6SL3060-4A..0-0AA0
X400- Active Line ≤ 5 m (16 ft) Active Interface
X500
X402 Module 6FX2002-1DC00-.... Module
≤ 70 m (230 ft)
6SL3060-4A..0-0AA0
X100- ≤ 5 m (16 ft) X400- Motor
X1051) 6FX2002-1DC00-.... X402 Module
≤ 70 m (230 ft)

6SL3060-4A..0-0AA0
X100- ≤ 5 m (16 ft) X500- Terminal
X1051) 6FX2002-1DC00-.... X501 Module
≤ 70 m (230 ft)

X126 PROFIBUS cable


X136 PC/PG
e. g. 6ES7901-4BD00-0XA0
(3 m) (9.8 ft)

X1202)
X127 Ethernet cable
PC/PG
X130 e. g. 6XV1870-3RH60
G_D211_EN_00266b
(6 m) (19 ft)
1) 2) X120 for D4x5-2 DP only.
For SIMOTION D425-2: X100-X103.
For SIMOTION D435-2/D445-2/D455-2: X100-X105.

Siemens D 21.3 · 2022 5/99


© Siemens 2022

System components for SINAMICS S120 Chassis and Chassis-2 Units


Connection system
Signal cables

■ Integration
Connection overview for Line Modules and Motor Modules
The DRIVE-CLiQ type 6SL3060-4A..0-0AA0 cables for the standard configuration are part of the scope of supply of the Line Modules
and Motor Modules. In this case, the modules must be mounted directly adjacent in a line.

SINAMICS S120 Article No.


Motor Module Pre-assembled cable
Chassis X400- Basic Line
format X402 Module

X400- Smart Line


X402 Module
6SL3060-4A..0-0AA0
X400- Active Line ≤ 5 m (16 ft) Active Interface
X500
X402 Module 6FX2002-1DC00-.... Module
6SL3060-4A..0-0AA0
X400- ≤ 5 m (16 ft) Control Unit ≤ 70 m (230 ft)
X100-
X402 X103 CU320-2
6FX2002-1DC00-....
≤ 70 m (230 ft) Control Unit
X100- SIMOTION
X103 CX32-2
Control Unit
X100-
SIMOTION
X1051)
D4x5-2
Motor encoder 6SL3060-4A..0-0AA0
interface ≤ 5 m (16 ft) X400-
5 via SMC
(Sensor Module
X400-
X402
Motor Module
6FX2002-1DC00-.... X402
Motor Module

≤ 70 m (230 ft)
Cabinet-Mounted)
for motors without
DRIVE-CLiQ X500 SMC102)
6SL3060-4A..0-0AA0
interface
X400- ≤ 5 m (16 ft)
X500 SMC202)
X402 6FX2002-1DC00-....
≤ 70 m (230 ft)
Motor encoder X500 SMC302)
interface
for motors with
DRIVE-CLiQ
Absolute encoder with
interface
DRIVE-CLiQ interface with
M12 connection
6FX5002-2DC30-.... 6FX2001-5.D..-1AA0
X400- ≤ 100 m (328 ft)3)
X402
6FX8002-2DC30-.... Non-Siemens direct
≤ 75 m (246 ft) 3)
measuring systems with
DRIVE-CLiQ interface with
M12 connection

6FX5002- 2DC10-.... Motor encoder in SIMOTICS


X400- ≤ 100 m (328 ft) motors with DRIVE-CLiQ
X402 6FX8002- 2DC10-.... interface with RJ45
≤ 75 m (246 ft) connection

U2
Motor Pre-assembled power cables, see power cables for motors
V2 Motors
connection (max. cable length, see Technical specifications of Motor Modules)
W2 G_D211_EN_00037m

1)
For SIMOTION D425-2: X100-X103.
For SIMOTION D435-2/D445-2/D455-2: X100-X105.
2)
See connection overviews of SMC10/SMC20/SMC30.
3)
See connection overview "SIMOTICS motors with RJ45 or M17 connection and external measuring systems with M12 connections"
for further connection possibilities.

5/100 Siemens D 21.3 · 2022


© Siemens 2022

System components for SINAMICS S120 Chassis and Chassis-2 Units


Connection system
Signal cables

■ Integration
Connection overview for Power Modules
A DRIVE-CLiQ cable of type 6SL3060-4A..0-0AA0 for connection to the chassis-mounted CU310-2 Control Unit is already included
in the scope of supply.

SINAMICS S120 Article No.


Power Module Pre-assembled cable
SINAMICS S120
Chassis X100
Control Unit CU310-2
format
X100- SINAMICS S120
U1/L1 X103 Control Unit CU320-2
Line Power supply cables, see power cables for motors (by the meter)
V1/L2
connection Control Unit
W1/L3 X100
SIMOTION D410-2
6SL3060-4A..0-0AA0
X400- ≤ 5 m (16 ft) X100- Control Unit
X402 6FX2002-1DC00-.... X105 1) SIMOTION
D4x5-2
≤ 70 m (230 ft)
Control Unit
X100-
SIMOTION
X103
CX32-2
X500-
Terminal Module
X501
Motor encoder
interface
via SMC
X400-
X402
Power Module 5
(Sensor Module
Cabinet-
Mounted) for X500 SMC102)
motors without 6SL3060-4A..0-0AA0
DRIVE-CLiQ ≤ 5 m (16 ft)
interface X402 X500 SMC202)
6FX2002-1DC00-....
≤ 70 m (230 ft)
X500 SMC302)
Motor encoder
interface for Absolute encoder with
motors with DRIVE-CLiQ interface with
DRIVE-CLiQ M12 connection
interface 6FX5002-2DC30-.... 6FX2001-5.D..-1AA0
≤ 100 m (328 ft) 3)
X402
6FX8002-2DC30-.... Non-Siemens direct
≤ 75 m (246 ft) 3)
measuring systems with
DRIVE-CLiQ interface with
M12 connection

6FX5002-2DC10-.... Motor encoder in


≤ 100 m (328 ft) SIMOTICS motors with
X402 DRIVE-CLiQ interface with
6FX8002-2DC10-....
≤ 75 m (246 ft) RJ45 connection

U2 Pre-assembled power cables, see power cables for motors


Motor V2 Motors
connection (max. cable length, see Technical specifications of Motor Modules)
W2 G_D211_EN_00139k

1) For SIMOTION D425-2: X100-X103.


For SIMOTION D435-2/D445-2/D455-2: X100-X105.
2)
See connection overviews SMC10/SMC20/SMC30.
3) See connection overview "SIMOTICS motors with RJ45 or M17 connection and external measuring systems with M12 connections"
for further connection possibilities.

Siemens D 21.3 · 2022 5/101


© Siemens 2022

System components for SINAMICS S120 Chassis and Chassis-2 Units


Connection system
Signal cables

■ Integration
Connection of a machine encoder (direct measuring system)

SINAMICS S120 Article No. Incremental encoder


Control Unit Pre-assembled cable 6FX8002-2CA88-....
sin/cos 1 Vpp without
CU310-2/CU320-2 ≤ 3 m (9.8 ft) C and D tracks
or X500 SME20 X520
6FX.002-2CB54-.... Incremental encoder
6FX5002-2DC10-....
X100- ≤ 100 m (328 ft) ≤ 3 m (9.8 ft) 2) sin/cos 1 Vpp (5 V)
X1051) 6FX8002-2DC10-....
≤ 75 m (246 ft) Absolute encoder
EnDat 2.1 (5 V)
6FX8002-2AD04-....
SIMOTION D410-2 X500 SME25 X520
≤ 3 m (9.8 ft) 2) Absolute encoder SSI
SIMOTION D4x5-2
SIMOTION CX32-2 with incremental signals
sin/cos 1 Vpp (5 V)

6SL3060-4A..0-0AA0
X100- ≤ 5 m (16.4 ft) 6FX.002-2CC11-.... Absolute encoder with SSI
X500 SMC30 X520
X1051) 6FX2002-1DC00-.... ≤ 100 m (328 ft) 6FX2001-5.S..
≤ 70 m (230 ft)

6FX5002-2DC30-... 4)
≤ 100 m (328 ft) possible Absolute encoder with

5 6FX8002-2DC30-...
≤ 75 m (246 ft) possible
4)
DRIVE-CLiQ interface with
M12 connection
6FX5002-2DC30-.... 3) 6FX2001-5.D..-1AA0
X100- ≤ 100 m (328 ft)4) 6FX.002-2DC34-....
X1051)
6FX8002-2DC30-... ≤ 30 m (98.4 ft) Non-Siemens direct
≤ 75 m (246 ft)4) measuring systems with
6FX5002-2DC30-.... DRIVE-CLiQ interface with
≤ 100 m (328 ft)4) 3)
6FX.002-2DC34-.... M12 connection
6FX8002-2DC30-.... ≤ 30 m (98.4 ft)
≤ 75 m (246 ft)4) 6FX2003-0DT67-....
G_D211_EN_00293h

(cabinet bushing)

1) For Control Unit CU310-2/SIMOTION D410-2: X100.


For Control Unit CU320-2/SIMOTION D425-2/SIMOTION CX32-2: X100-X103.
For SIMOTION D435-2/D445-2/D455-2: X100-X105.
2) Up to 10 m (32.8 ft) possible, dependent on encoder current consumption.
3) The total cable length (basic cable and extension cable) must not exceed 30 m (98 ft).
4) See connection overview "SIMOTICS motors with RJ45 or M17 connection and external measuring systems with M12 connections"

for further connection possibilities.

Connection overview of SINAMICS S120 Sensor Module


Cabinet-Mounted SMC10

Sensor Module Article No.


SINAMICS S120 Pre-assembled cable
Cabinet-Mounted
SMC10
6FX.002-2FN20-.... Resolver for the
≤ 130 m (427 ft) 1FK701 motor

6FX.002-2CF02-.... Resolver for


X520 SIMOTICS motor
≤ 130 m (427 ft)

Resolver
6FX.002-2CF06-....
1XP8013-10/-11
≤ 130 m (427 ft) 1XP8023-10/-11
G_NC01_EN_01033

5/102 Siemens D 21.3 · 2022


© Siemens 2022

System components for SINAMICS S120 Chassis and Chassis-2 Units


Connection system
Signal cables

■ Integration
Connection overview of SINAMICS S120 Sensor Module Connection overview of SINAMICS S120 Sensor Module
Cabinet-Mounted SMC20 Cabinet-Mounted SMC30

Sensor Module Article No. Sensor Module Article No.


SINAMICS S120 Pre-assembled cable SINAMICS S120 Pre-assembled cable
Cabinet-Mounted Cabinet-Mounted
SMC20 6FX.002-2CN20-.... Incremental encoder SMC30
sin/cos 1 Vpp 6FX.002-2CC11-.... Absolute encoder
≤ 50 m (164 ft) in 1FK701 motor with SSI (24 V DC)
≤ 100 m (328 ft) 6FX2001-5.S.
Incremental encoder Absolute encoder
6FX.002-2CQ31-.... sin/cos 1 Vpp with 6FX.002-2CC06-.... with SSI (24 V DC)
≤ 100 m (328 ft) C/D tracks in 1XP8014-20
1FT7 motor ≤ 100 m (328 ft)
1XP8024-20/-211)
Incremental encoder X520 Incremental encoder
sin/cos 1 Vpp
6FX.002-2CA31-.... with C/D tracks in TTL RS 422
≤ 100 m (328 ft) 1FT7/1FK7/1PH8/ (5 V DC)
1FW3 motors1) 6FX2001-2...
6FX.002-2CR00-....
Incremental encoder ≤ 100 m (328 ft) Incremental encoder
6FX8002-2CQ80-.... sin/cos 1 Vpp TTL RS 422
≤ 50 m (164 ft) without C/D tracks (5 V DC)
in 1PH8 motor2) 1XP8012-20/-21/-22
1XP8032-20/-21/-22

6FX8002-2CA80-....
Incremental encoder
sin/cos 1 Vpp
without C/D tracks 6FX.002-2CD24-....
Incremental encoder
TTL RS 422
5
≤ 50 m (164 ft) in 1PH8 motor3) ≤ 100 m (328 ft) (24 V DC)
6FX2001-2
X520 6FX.002-2CG00-.... Incremental encoder
Incremental encoder
≤ 50 m (164 ft) sin/cos 1 Vpp
6FX2001-3... HTL (24 V DC)
6FX2001-4...
Direct linear 6FX5002-2CA12-....
increm. encoder ≤ 100 m (328 ft) Incremental encoder
sin/cos 1 Vpp HTL (24 V DC)
LS 187(C)/LF 183(C) X521 1XP8012-10/-11
Adapter LB 382(C) X531 1XP8032-10/-11/-12
cable4) LS 487(C)/LF 481(C)
6FX.002-2AH00-.... Incremental encoder
Absolute encoder HTL in 1PH8 motor
6FX.002-2EN20-.... ≤ 300 m (984 ft)2)
with EnDat 2.1 G_D211_EN_00269d
≤ 50 m (164 ft) in 1FK701 motor

Absolute encoder
6FX.002-2EQ31-.... with EnDat 2.1 in 1) For
1FT7/1PH85) position control only.
≤ 100 m (328 ft) 2)
Applies to HTL encoders with bipolar signal evaluation or for
motors
evaluation of difference signals A*, A and B*, B; for HTL encoders
Absolute encoder with unipolar signal evaluation the permissible cable length is
6FX.002-2EQ10-.... with EnDat 2.1 in reduced to 100 m (328 ft).
≤ 100 m (328 ft) 1FK7/1PH8/1FW3
motors1)
Direct linear
Adapter absolute encoder
cable 4) EnDat 2.1
LC 183/LC 483
Absolute encoder
with EnDat 2.1
6FX2001-5.E.
Absolute encoder
with EnDat 2.1
1XP8014-10
6FX.002-2CH00-.... 1XP8024-10
≤ 100 m (328 ft) G_NC01_EN_01034
1) 1FW3 motor not suitable for machine tools.
2) Possible for 1PH808/1PH810/1PH813/1PH816 motors for encoders
with 512 S/R and 256 S/R.
3) Possible for 1PH8 motors for encoders with 512 S/R and 256 S/R.
4) Adapter cable available from measuring system manufacturer.
5) Possible for 1PH808/1PH810/1PH813/1PH816 motors.

Siemens D 21.3 · 2022 5/103


© Siemens 2022

System components for SINAMICS S120 Chassis and Chassis-2 Units


Connection system
Signal cables

■ Technical specifications
Signal cables MOTION-CONNECT 500 MOTION-CONNECT 800PLUS
6FX50..-.....-.... 6FX80..-.....-....
Certificates of suitability,
according to
• cURus or UR/CSA UL758-CSA-C22.2-N.210.2-M90 UL758-CSA-C22.2-N.210.2-M90
• UR-CSA File No. 1) Yes Yes
• RoHS conformity Yes Yes
Rated voltage according to 30 V 30 V
EN 50395
Test voltage, rms 500 V 500 V
Operating temperature on the surface
• Permanently installed -20 ... +80 °C (-4.0 ... +176 °F) -50 ... +80 °C (-58 ... +176 °F)
• Flexible installation 0 ... +60 °C (32 ... 140 °F) -20 … +60 °C (-4.0 ... 140 °F)
Tensile stress, max.
• Permanently installed 50 N/mm2 50 N/mm2
• Flexible installation 20 N/mm2 20 N/mm2
Smallest bending radius
• Permanently installed 60 mm (2.36 in) 4 × Dmax
• Flexible installation 100 mm (3.94 in) 70 mm (2.76 in) 2)
Torsional stress Absolute 30°/m Absolute 30°/m
Bending operations 2 million 10 million
5 Traversing speed 180 m/min (591 ft/min) Up to 300 m/min (984 ft/min)
Acceleration 5 m/s2 (16.4 ft/s2) Up to 50 m/s2 (164 ft/s2)
Insulation material, incl. jacket CFC/silicone-free CFC/halogen/silicone-free
IEC 60754-1/DIN VDE 0472-815
Oil resistance EN 60811-2-1 (mineral oil only) EN 60811-2-1
Jacket PVC PUR, HD22.10 S2 (VDE 0282, Part 10)
DESINA color green RAL 6018 DESINA color green RAL 6018
Flame-retardant EN 60332-1-1 to 1-3 EN 60332-1-1 to 1-3

Degree of protection of the pre-assembled signal cables and


their extensions when closed and inserted: IP67.

1) The File No. is printed on the cable jacket.


2) Exception: 6FX8002-2SL..-....; smallest bending radius (flexible): 85 mm (3.35 in).

5/104 Siemens D 21.3 · 2022


© Siemens 2022

System components for SINAMICS S120 Chassis and Chassis-2 Units


Connection system
Signal cables

■ Technical specifications
DRIVE-CLiQ signal cables DRIVE-CLiQ DRIVE-CLiQ DRIVE-CLiQ
MOTION-CONNECT 500 MOTION-CONNECT 800PLUS
6FX2...-1DC..-.... 6FX5...-.DC..-.... 6FX8...-.DC..-....
Certificates of suitability,
according to
• cURus or UR/CSA UL STYLE 2502/CSA-N.210.2-M90 UL STYLE 2502/CSA-N.210.2-M90 UL STYLE 2502/CSA-N.210.2-M90
• UR-CSA File No. 1) Yes Yes Yes
• RoHS conformity Yes Yes Yes
Rated voltage according to 30 V 30 V 30 V
EN 50395
Test voltage, rms 500 V 500 V 500 V
Operating temperature on the surface
• Permanently installed -20 ... +80 °C (-4.0 ... 176 °F) -20 ... +80 °C (-4.0 ... 176 °F) -20 ... +80 °C (-4.0 ... 176 °F)
• Flexible installation – 0 ... +60 °C (32 ... 140 °F) -20 ... +60 °C (-4.0 ... 140 °F)
Tensile stress, max.
• Permanently installed 45 N/mm2 80 N/mm2 50 N/mm2
• Flexible installation – 30 N/mm2 20 N/mm2
Smallest bending radius
• Permanently installed 50 mm (1.97 in) 35 mm (1.38 in) 35 mm (1.38 in)
• Flexible installation – 125 mm (4.92 in) 75 mm (2.95 in)
Torsional stress – Absolute 30°/m Absolute 30°/m
Bending operations
Traversing speed


100000
30 m/min (98.4 ft/min)
10 million
300 m/min (984 ft/min)
5
Acceleration – 2 m/s2 (6.56 ft/s2) Up to 50 m/s2 (164 ft/s2)
Insulation material, incl. jacket CFC/silicone-free CFC/silicone-free CFC/halogen/silicone-free
IEC 60754-1/DIN VDE 0472-815
Oil resistance EN 60811-2-1 EN 60811-2-1 (mineral oil only) EN 60811-2-1
Jacket PVC PVC PUR, HD22.10 S2
(VDE 0282, Part 10)
Gray RAL 7032 DESINA color green RAL 6018 DESINA color green RAL 6018
Flame-retardant EN 60332-1-1 to 1-3 EN 60332-1-1 to 1-3 EN 60332-1-1 to 1-3

Degree of protection of the pre-assembled signal cables and


their extensions when closed and inserted: IP67.

1) The File No. is printed on the cable jacket.

Siemens D 21.3 · 2022 5/105


© Siemens 2022

System components for SINAMICS S120 Chassis and Chassis-2 Units

Notes

5/106 Siemens D 21.3 · 2022


6
© Siemens 2022

SINAMICS S120 Cabinet Modules

6/2 System overview


6/2 Overview
6/3 Benefits
6/4 Application
6/4 Design
6/5 Function
6/7 Technical specifications

6/8 Air-cooled units


6/17 Line Connection Modules
6/24 Basic Line Modules
6/30 Smart Line Modules
6/34 Active Line Modules incl.
Active Interface Modules
6/40 Motor Modules in booksize format
6/44 Motor Modules in chassis format
6/51 Central Braking Modules
6/55 Auxiliary Power Supply Modules
6/58 Customer terminal strip -X55

6/61 Liquid-cooled units


6/73 Basic Line Connection Modules
6/77 Active Line Connection Modules
6/82 Active Line Connection Modules compact
6/88 Motor Modules
6/96 Motor Modules compact
6/100 Auxiliary Power Supply Modules
6/103 Heat Exchanger Modules

6/108 Options
6/108 Overview
6/114 Option selection matrix
6/117 Description of the options

6/134 Supplementary system components


6/134 Mounting device for air-cooled
power blocks
6/134 Mounting device for liquid-cooled
power units

6/135 Order-specific integration engineering


6/136 Option selection matrix of the order-specific
integration engineering

6/137 Customized solutions

Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Cabinet Modules

System overview

■ Overview
All drive components, from the supply infeed to the motor-side
inverters, are configured in a clear, compact layout in the
individual Cabinet Modules. They can be flexibly combined and
optimally adapted to customer-specific requirements thanks to
a comprehensive array of options.
The main components of the air-cooled system are as follows:
• Line Connection Modules with line-side components such as
contactors, fuses and circuit breakers, as well as line reactors
for Basic Line Modules
• The following types of infeed Line Modules:
- Basic Line Modules for two-quadrant operation
- Smart Line Modules for four-quadrant operation
- Active Line Modules for four-quadrant operation with
negligible line harmonics
• Central Braking Modules for braking operation
• The following types of Motor Modules:
- Booksize Cabinet Kit
SINAMICS S120 Cabinet Modules, air-cooled and liquid-cooled - Chassis
SINAMICS S120 Cabinet Modules are the components of • Control Units
a modular cabinet system for multi-motor drives with a central • Auxiliary Power Supply Modules to supply the auxiliary power
supply infeed and a common DC link busbar, as used, for supply system
example, in the process industry, automotive industry, metal
processing industry as well as in the crane and mining domains. The main components of the liquid-cooled system are as follows:
They are available in air-cooled or liquid-cooled versions. • Active Line Connection Modules as a combination of Line
As standard, they are installed side by side in a row. Other Connection Module and Active Line Module with an Active
installation types (e.g. back to back) are possible on request. Interface Module
SINAMICS S120 Cabinet Modules include the chassis units from
the SINAMICS S120 series in booksize format (Motor Modules) • Basic Line Connection Modules as a combination of a Line
and chassis format, thus making the range an ideal supplement Connection Module and a Basic Line Module
6 to the SINAMICS G150 and SINAMICS S150 cabinet converter • Motor Modules
series for single-motor drives. • Control Units
• Auxiliary Power Supply Modules to supply the auxiliary power
supply system
• Heat Exchanger Modules with pumps, closed-loop control
and a heat exchanger between the deionized water and raw
water circuits
Standardized interfaces for both the power and the control
connections facilitate configuration and installation.
Communication between the power modules and the central
Control Unit takes place via DRIVE-CLiQ, the internal drive serial
interface.

=
~
= = = = = = = = = =
~ ~ ~ ~ ~ ~ ~ ~ ~ ~
G_D211_XX_00203

M M M M M M M M M M M M
3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~

Example of a drive line-up with SINAMICS S120 Cabinet Modules for a multi-motor drive

6/2 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Cabinet Modules

System overview

■ Overview
The following tables provide an overview of the voltage ranges
and power ratings of the available SINAMICS S120 Cabinet
Modules.
Voltage ranges and powers for air-cooled SINAMICS S120 Cabinet Modules
Line voltage Input current DC link voltage DC link current Output current Power range of
single modules
Line Connection Modules 1) 380 ... 480 V 3 AC 250 ... 3200 A – – – –
500 ... 690 V 3 AC 280 ... 3200 A – – – –
Basic Line Modules 1) 380 ... 480 V 3 AC 365 ... 1630 A 510 ... 650 V 420 ... 1880 A – 200 ... 900 kW
500 ... 690 V 3 AC 260 ... 1580 A 675 ... 930 V 300 ... 1880 A – 250 ... 1500 kW
Smart Line Modules 1) 380 ... 480 V 3 AC 463 ... 1430 A 510 ... 650 V 550 ... 1700 A – 250 ... 800 kW
500 ... 690 V 3 AC 463 ... 1430 A 675 ... 930 V 550 ... 1700 A – 450 ... 1400 kW
Active Line Modules 1) 380 ... 480 V 3 AC 210 ... 1405 A 570 ... 720 V 235 … 1574 A – 132 ... 900 kW
500 ... 690 V 3 AC 575 ... 1270 A 750 ... 1035 V 644 ... 1422 A – 630 ... 1400 kW
Motor Modules booksize 380 ... 480 V 3 AC – 510 ... 720 V – 9 ... 132 A 4.8 ... 71 kW
Motor Modules chassis 1) 380 ... 480 V 3 AC – 510 ... 720 V – 210 ... 1405 A 110 ... 800 kW
500 ... 690 V 3 AC – 675 ... 1035 V – 85 ... 1270 A 75 ... 1200 kW
Central Braking Modules 1) 380 ... 480 V 3 AC – 510 ... 720 V – – 500 ... 1000 kW
500 … 600 V 3 AC – 675 ... 900 V – – 550 ... 1100 kW
660 … 690 V 3 AC – 890 ... 1035 V – – 630 ... 1200 kW
Auxiliary Power Supply 380 ... 690 V 3 AC 125 ... 250 A – – – –
Modules

Voltage ranges and power ratings for liquid-cooled SINAMICS S120 Cabinet Modules
Line voltage Input current DC link voltage DC link current Output current Power range of
single modules
6
Basic Line Connection 380 ... 480 V 3 AC 610 ... 1420 A 510 ... 650 V 740 ... 1730 A – 360 ... 830 kW
Modules 1)
500 ... 690 V 3 AC 340 ... 1350 A 675 ... 930 V 420 ... 1650 A – 355 ... 1370 kW
Active Line Connection 380 ... 480 V 3 AC 605 ... 1405 A 570 ... 720 V 677 ... 1573 A – 380 ... 900 kW
Modules 1)
500 ... 690 V 3 AC 735 ... 1560 A 750 ... 1035 V 823 ... 1740 A – 800 ... 1700 kW
Motor Modules 1) 380 ... 480 V 3 AC – 510 ... 720 V – 210 ... 1405 A 110 ... 800 kW
500 ... 690 V 3 AC – 675 ... 1035 V – 100 ... 1560 A 90 ... 1500 kW
Auxiliary Power Supply 380 ... 690 V 3 AC 25 A – – – –
Modules

■ Benefits
The outstanding system features of the SINAMICS S120 Cabinet - Generally the line infeed is only dimensioned for the
Modules provide the following advantages: maximum energy required when motoring or the maximum
• Process optimization with minimum outlay current required when motoring – and not for the sum of the
- A standard PROFIBUS or PROFINET interface and various energy requirements of the Motor Modules connected to the
analog and digital interfaces enable easy integration into DC link. As a consequence, for example, for conveyor belts
automation solutions or motor test stands with Motor Modules that are
- Vector and servo control ensures that they fulfill the most simultaneously operated in motoring and generating modes,
exacting requirements regarding the accuracy and dynamic a significantly smaller line infeed unit can be selected.
response of drives. • Minimal operative, maintenance, and servicing costs
• High level of reliability and availability - Simple commissioning thanks to the menu-driven
- Individual modules and power components can be replaced commissioning tools SINAMICS Startdrive or STARTER.
quickly and easily, which ensures a higher level of plant - Optional, menu-navigated AOP30 advanced operator panel
availability with plain text display and bar-type display of process
variables.
• Energy saving during operation - All modules are easily accessible, making them extremely
- The motor-side inverters are coupled via the common DC service-friendly
link and allow energy to be exchanged between motors that
are motoring and generating. This means that energy is • Space-saving design
saved, there is less load on the supply infeed and line • Environmentally-friendly operation
harmonics are reduced - The converters are exceptionally quiet and compact thanks
to state-of-the-art IGBT power semiconductors and an
innovative cooling concept

1)
The power can be increased by connecting up to four identical modules
in parallel.

Siemens D 21.3 · 2022 6/3


© Siemens 2022

SINAMICS S120 Cabinet Modules

System overview

■ Application
SINAMICS S120 Cabinet Modules have been specially • Hoists and cranes
developed to allow simple configuration of multi-motor systems. • Printing and paper machines
They are used for applications where several motors must be
coordinated to realize a drive task as multi-motor drives in • Vehicle and gearbox test bays
a drive line-up. Examples of such applications include: • Test bay applications
• Packaging machines • Machines used in the woodworking, glass and ceramics
• Plastics processing machines industries
• Textile machines • Handling and assembly systems
• Presses and punches • Machine tools
• Rolling mill drives High-power single-motor drives (parallel connection) can also
be implemented with Cabinet Modules.

■ Design
The devices have been designed according to the zone concept The auxiliary power supply system comprises one Auxiliary
principle and therefore offer the highest possible level of Power Supply Module with two terminal blocks (air cooling) and
operational reliability. EMC measures have been rigorously one connecting terminal with two terminal blocks (liquid cooling)
implemented. With the help of simulated conditions, partitions and a 24 V DC fuse as well as the required connecting cables.
have been designed to act as air guides and heat dissipation It is supplied completely assembled and ready to operate.
units. Only the cable connections to the adjacent Cabinet Module
must be established on-site.
Special measures used in the construction of the cabinets
ensure that they remain mechanically durable over their entire DRIVE-CLiQ communication
life cycle.
Communication between the Control Unit, power units and other
Attention has been paid to providing a wide range of cable active SINAMICS components is realized via DRIVE-CLiQ
routing options and special design concepts are applied connections.
consistently to broaden the scope of application and simplify
service. The units have all the necessary connections and DRIVE-CLiQ is an internal serial interface of the drive that
connecting elements. Thanks to their carefully considered enables fast and easy configuration of the complete drive
6 configuration concept, cabinets are shipped in a ready-to-
connect state or, in the case of multiple transport units, have
line-up with prefabricated cables in varying lengths.
Transport units
been prepared for quick assembly. An extensive spectrum of
options designed to adapt the units to a variety of different The Cabinet Modules can be optionally supplied in pre-
applications facilitates the selection process. configured transport units up to a total length of 2400 mm.
This option is particularly recommended in air-cooled Cabinet
All components, from individual parts to the ready-to-connect Modules for Line Modules together with Line Connection
cabinet, undergo rigorous testing throughout the entire Modules since, in this case, the Line Connection Module
production process. This guarantees a high level of functional must be equipped with a pre-charging DC link or line reactors
reliability during installation and commissioning, as well as (depending on the type of Line Module), in addition to the
in operation. electrical interface (busbar). For liquid-cooled Cabinet Modules,
Replaceable components have been designed so that they can delivery in transport units has the advantage that the tube
be quickly and easily replaced. In addition, the "Spares On Web" system of the cooling system can be implemented completely
internet tool makes it easy to view the spare parts that are without couplings. Transport units thus enable the various
available for the particular order at all times 1). devices to be quickly and easily assembled on-site.

System design Coated modules

Line Modules are coupled with the various Motor Modules by The following devices are equipped as standard with coated
means of prefabricated busbar sets with different current modules:
carrying capacities. • Booksize format units
All standard busbars, as well as electronics components, are • Chassis format units
protected against environmental influences. This is achieved • Control Units
through the use of nickel-plated copper bars and painted • Sensor Modules
modules throughout.
• Terminal Modules
Auxiliary power supply system • Advanced Operator Panel (AOP30)
A special, standard auxiliary power supply system supplies the The coating on the modules protects the sensitive SMD
individual Cabinet Modules with the required auxiliary voltages components against corrosive gases, chemically active dust
for the power components, fans and 24 V loads. and moisture.
These voltages are preferably generated using an Auxiliary
Power Supply Module. Additional supply possibilities are Nickel-plated busbars
available using the K76 option (auxiliary power supply All of the copper busbars used in the converter cabinets
generation in the Line Connection Module) or using an external are nickel-plated to achieve the best possible immunity to
supply in the auxiliary power supply system. environmental effects. Furthermore, there is no need to clean the
contacts on the customer terminals as otherwise required for
bare copper connections.
Note:
1) The properties of the SINAMICS S120 Cabinet Modules described in this With some options, parts of the copper busbars cannot be
catalog are not transferable to cabinet units constructed to meet the nickel-plated for technical reasons.
requirements of specific applications.

6/4 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Cabinet Modules

System overview

■ Design ■ Function
PE bars Communication with higher-level controller and customer
terminal strip
The Cabinet Modules are delivered with a PE bar as standard.
It is used to connect and fasten PE conductors. As the customer interface to the control system, a PROFIBUS
interface is available on the CU320-2 DP Control Unit or
Degrees of protection of Cabinet Modules a PROFINET interface on the CU320-2 PN Control Unit as
The EN 60529 standard covers the protection of electrical standard.
equipment by means of housings, covers or equivalent, In the case of the air-cooled Cabinet Modules, the inputs and
and includes: outputs available as standard on the customer terminal strip -
• Protection of persons against accidental contact with live X55, which are easy to access and easy to connect up,
or moving parts within the housing and protection of the can be provided.
equipment against the ingress of solid foreign bodies In the case of the liquid-cooled Cabinet Modules,
(touch protection and protection against ingress of solid the components are directly connected.
foreign bodies)
For further information, please refer to the SINAMICS Low
• Protection of the equipment against the ingress of water Voltage Engineering Manual.
(water protection)
• Abbreviations for the internationally agreed degrees of Open-loop and closed-loop control functions
protection SINAMICS S120 can use a dynamic, high-precision closed-loop
The degrees of protection are specified by abbreviations vector control (drive object type VECTOR), or a highly dynamic
comprising the code letters IP and two digits. closed-loop servo control (drive object type SERVO).

Degree of First code number Second code number


protection (touch protection and (protection of the
protection against solid equipment against
foreign bodies) the ingress of water)
IP20 Protected against solid No water protection
(Standard for foreign bodies
air-cooled version) Diameter  12.5 mm
IP21 Protected against solid Protected against drip
(Standard for foreign bodies water
liquid-cooled
version, option M21
Diameter  12.5 mm Vertically falling water
drops shall not have
6
for air-cooled a harmful effect.
version)
IP23 Protected against solid Protected against spray
(Option M23) foreign bodies water
Diameter  12.5 mm Water sprayed on both
sides of the vertical at an
angle of up to 60° shall
not have a harmful effect.
IP43 Protected against solid Protected against spray
(Option M43) foreign bodies water
Diameter  1 mm Water sprayed on both
sides of the vertical at an
angle of up to 60° shall
not have a harmful effect.
IP54 Dust protected Protected against splash
(Option M54) Ingress of dust is not totally water
prevented, but dust must Water splashing onto the
not be allowed to enter in enclosure from any
such quantities that the direction shall not have
functioning or safety of the a harmful effect.
equipment is impaired.
Complete touch protection
IP55 Dust protected Protected against water
(Liquid-cooled Ingress of dust is not totally jet (nozzle)
version only) prevented, but dust must Water projected by
(Option M55) not be allowed to enter in a nozzle against the
such quantities that the enclosure from any
functioning or safety of the direction shall not have
equipment is impaired. a harmful effect.
Complete touch protection

Air-cooled Cabinet Modules meet degree of protection IP20,


liquid-cooled Cabinet Modules degree of protection IP21,
as standard. Heat Exchanger Modules have degree of
protection IP55 as standard.

Siemens D 21.3 · 2022 6/5


© Siemens 2022

SINAMICS S120 Cabinet Modules

System overview

■ Function
Software and protective functions
The software functions available as standard are described
below:
Software and Description
protective functions
Setpoint input The setpoint can be specified both internally and externally; internally as a fixed setpoint, motorized potentiometer setpoint or jog
setpoint, externally via the communications interface or an analog input. The internal fixed setpoint and the motorized potentiometer
setpoint can be switched or adjusted via control commands from any interface.
Motor identification The automatic motor identification function makes commissioning faster and easier and optimizes closed-loop control of the drive.
Ramp-function A user-friendly ramp-function generator with separately adjustable ramp-up and ramp-down times, together with adjustable rounding
generator times in the lower and upper speed ranges, allows the drive to be smoothly accelerated and braked. This results in a good speed
control response and plays its role in reducing the stress on the mechanical system. The down ramp can be parameterized separately
for a quick stop.
Vdc max controller The Vdc max controller automatically prevents overvoltages in the DC link, if the set down ramp is too short, for example. This may also
extend the set ramp-down time.
Note: This function only makes sense for single-axis applications.
Kinetic buffering For brief line supply failures, the kinetic energy of the rotating drive is used to buffer the DC link and therefore prevents fault trips.
(KIP) The converter remains operational as long as the drive can provide regenerative energy as a result of its motion and the DC link voltage
does not drop below the shutdown threshold. When the line supply recovers within this time, the drive is again bumplessly accelerated
up to its setpoint speed.
Automatic restart The automatic restart switches the drive on again when the power is restored after a power failure, and ramps up to the current speed
setpoint.
Flying restart The flying restart function allows the converter to be switched to a motor that is still turning. With the voltage sensing capability provided
by the optional VSM10, the flying restart time for large induction motors can be significantly reduced because the motor does not need
to be de-magnetized.
Technology Using the technology controller (PID controller) function module, level or flow controls and complex tension controls can be
controller implemented, for example. The existing D component can act both on the system deviation as well as on the actual value
(factory setting). The P, I, and D components are set separately.

6 Free function blocks Using the freely programmable function blocks, it is easy to implement logic and arithmetic functions for controlling the SINAMICS drive.
(FFB) The blocks can be programmed at the operator panel or the commissioning tools SINAMICS Startdrive or STARTER.
Drive Control Chart Drive Control Chart (DCC) is an additional tool for the easy configuration of technological functions for SINAMICS. The block library
(DCC) contains a large selection of control, arithmetic and logic blocks as well as extensive open-loop and closed-loop control functions.
The user-friendly DCC editor enables easy graphics-based configuration, allows control loop structures to be clearly represented and
provides a high degree of reusability of charts that have already been created. DCC is an add-on for the commissioning tools SINAMICS
Startdrive or STARTER ( Tools and Engineering).
SINAMICS The SINAMICS TEC are configurable functions or Siemens technologies that can be added to extend firmware functions.
Technology These extensions are designed to allow implementation of highly complex, application-specific tasks for various sectors -
Extensions such as storage and retrieval machines.
(SINAMICS TEC) Additional information about Technology Extensions (TEC) is provided in the "Technology functions" section.
I2 t recording for A motor model stored in the converter software calculates the motor temperature based on the current speed and load. More exact
motor protection sensing of the temperature, which also takes into account the influence of the ambient temperature, is possible by means of direct
temperature sensing using Pt1000/KTY84 sensors in the motor winding.
Motor temperature Motor protection by evaluating a KTY84, PTC, Pt100 or Pt1000 temperature sensor. When a KTY84 temperature sensor is connected,
evaluation the limit values can be set for alarm or shutdown. When a PTC thermistor is connected, the system reaction to triggering of
the thermistor (alarm or trip) can be defined.
Motor blocking A blocked motor is detected and protected against thermal overloading by a fault trip.
protection
Brake control “Simple brake control” for controlling holding brakes:
The holding brake is used to secure drives against unwanted motion when deactivated.
The "extended braking control" function module allows complex braking control, for example, for motor holding brakes and operational
brakes.
In the case of brakes with feedback signal, the brake control reacts to the feedback contacts of the brake.
Write protection Write protection to prevent unintentional changing of the setting parameters (without password function).
Know-how Know-how protection for encrypting stored data, e.g. to protect expert configuring knowledge, and to protect against modification and
protection duplication (with password function).
Web server The web server provides information about the drive unit via its web pages. The web server is accessed using a web browser via
unsecured (http) or secured transfer protocol (https).

Power unit protection


Power unit protection Description
Ground fault A ground fault at the output is detected by a total current monitor and results in shutdown in grounded systems.
monitoring at the
output
Electronic short- A short-circuit at the output (e.g. at the converter output terminals, in the motor cable or in the motor terminal box) is detected and the
circuit protection at converter shuts down with a "fault".
the output
Thermal overload An alarm is issued first when the overtemperature threshold responds. If the temperature continues to rise, the unit either shuts down
protection or independently adjusts the pulse frequency or output current so that thermal load is reduced. Once the cause of the fault has been
eliminated (e.g. cooling has been improved), the original operating values are automatically resumed.

6/6 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Cabinet Modules

System overview

■ Technical specifications
The most important directives and standards are listed below.
These are used as basis for the SINAMICS S120 Cabinet
Modules and they must be carefully observed to achieve an
EMC-compliant configuration that is safe both in terms of
functionality and in operation.

European directives
2014/35/EU Low-voltage Directive:
Directive of the European Parliament and Council of February 26, 2014 on the harmonization of the laws of the member states relating
to the making available on the market of electrical equipment designed for use within certain voltage limits (recast)
2014/30/EU EMC Directive:
Directive of the European Parliament and Council of February 26, 2014 on the harmonization of the laws of the member states relating
to electromagnetic compatibility (recast)
2006/42/EC Machinery Directive:
Directive of the European Parliament and Council of May 17, 2006, on machinery and amending Directive 95/16/EC (recast).
2011/65/EU RoHS II Directive:
Directive of the European Parliament and of the Council of 8 June 2011 on the restriction of the use of certain hazardous substances
in electrical and electronic equipment (recast)
European standards
EN ISO 3744 Acoustics – Determination of sound power levels and sound energy levels of noise sources using sound pressure –
Engineering methods for an essentially free field over a reflecting plane
EN ISO 13849-1 Safety of machinery – Safety-related parts of control systems;
Part 1: General principles for design (EN ISO 13849-1: 2006)
EN 60146-1-1 Semiconductor converters – General requirements and line-commutated converters
Part 1-1: Specification of basic requirements
EN 60204-1 Safety of machinery – Electrical equipment of machines;
Part 1: General requirements
EN 60529 Degrees of protection provided by enclosures (IP code)
IEC 61508-1 Functional safety of electrical/electronic/programmable electronic safety-related systems
Part 1: General requirements 6
IEC 61508-2 Functional safety of electrical/electronic/programmable electronic safety-related systems
Part 2: Requirements for electrical/electronic/programmable electronic safety-related systems
IEC 61508-3 Functional safety of electrical/electronic/programmable electronic safety-related systems
Part 3: Software requirements
EN 61800-2 Adjustable speed electrical power drive systems
Part 2: General requirements – Rating specifications for low voltage adjustable frequency AC power drive systems
EN 61800-3 Adjustable speed electrical power drive systems
Part 3: EMC requirements and specific test methods
EN 61800-5-1 Adjustable speed electrical power drive systems
Part 5: Safety requirements
Main section 1: Electrical and thermal requirements
EN 61800-5-2 Adjustable speed electrical power drive systems
Part 5-2: Safety requirements – Functional safety (IEC 61800-5-2: 2007)

Siemens D 21.3 · 2022 6/7


© Siemens 2022

SINAMICS S120 Cabinet Modules


Air-cooled units

■ Overview
Line Modules
Line Connection Module
Power is fed to the drive line-up via Line Modules, which
generate a DC voltage from the line voltage and, therefore, Circuit breaker Basic Line
Module
supply energy to the Motor Modules connected to the DC link.
They are suitable for connection to grounded TN/TT and
non-grounded IT systems.
=
The Line Modules are connected to the line supply system Motor
via Line Connection Modules and are equipped as standard G_D213_EN_00043b Module
according to Category C3. Category C3 is part of the "second
environment" (in accordance with EN 61800-3). The “second
environment” constitutes locations outside residential areas or M
industrial sites which are supplied from the medium-voltage 3
network via a separate transformer.
The range of Line Modules has power ratings from 132 kW to Line Connection Module with Basic Line Module >800 A
900 kW (380 V to 480 V) and from 250 kW to 1500 kW (500 V to If, for example, a converter transformer is used to connect to the
690 V). Furthermore, up to four identical Line Modules can be line supply (12-pulse operation), it may be possible to omit line
connected in parallel in order to increase the power rating. reactors (depending on the supply conditions on site) and they
For a compact configuration, Line Connection Modules up to can be optionally deselected (option L22 for a Line Connection
input currents of 3200 A are available. Two Line Modules can be Module combined with a Basic Line Module).
operated in parallel on these Line Connection Modules. For a compact configuration, Line Connection Modules with
The following types of Line Modules are available: input currents of up to 3200 A are available. Two Basic Line
Modules can be operated in parallel on these Line Connection
• Basic Line Modules Modules. Versions with line-side fuses are available for parallel
• Smart Line Modules connections in order to provide selective protection of the
• Active Line Modules individual Basic Line Modules.

Basic Line Modules


Line Connection Module
Basic Line Modules are designed only for infeed operation, Basic Line
6 i.e. they are not capable of recovering energy to the line supply.
Circuit breaker
Module

If regenerative energy is produced, e.g. when the drives brake,


then it must be converted to heat by means of a Braking Module
and a braking resistor.
When a Basic Line Module is used as the infeed, a line reactor = Motor
appropriate to the supply conditions must be installed. Line Module
reactors are generally required if two or more Basic Line
Modules are operated in parallel on a common supply
G_D213_EN_00044b
system in order to increase power.
M
For this reason, line reactors are installed in the appropriate Line 3
Connection Module as standard.
Line Connection Module with Basic Line Modules connected in parallel
Line Connection Module
Switch disconnector Main Basic Line
with fuses contactor Module

= Motor
G_D213_EN_00042b Module

M
3

Line Connection Module with Basic Line Module 800 A

6/8 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Cabinet Modules


Air-cooled units

■ Overview
Smart Line Modules Active Line Modules
Smart Line Modules can supply energy to the DC link and return Active Line Modules can supply energy to the DC link and return
regenerative energy to the supply system. A Braking Module regenerative energy to the supply system. A Braking Module
and braking resistor are required only if the drives need to be and braking resistor are required only if the drives need to
decelerated in a controlled manner after a power failure be decelerated in a controlled manner after a power failure
(i.e. when energy cannot be recovered to the supply). When (i.e. when energy cannot be recovered to the supply).
a Smart Line Module is used as the infeed, the necessary line
reactor is included in the device as standard and can be In contrast to Basic Line Modules and Smart Line Modules,
optionally deselected (option L22). however, Active Line Modules generate a regulated DC voltage
which remains constant despite fluctuations in the line voltage.
However, in this case, the line voltage must remain within the
Line Connection Module permissible tolerance range. Active Line Modules in
Switch disconnector Main Line Smart Line combination with an Active Interface Module draw a virtually
with fuses contactor reactor Module sinusoidal current from the supply system. Almost no harmonics
occur. The total harmonic distortion factors of the current THD(I)
and voltage THD(U) are typically in the range of approx. 3 % for
rated current. THD(I) is calculated according to IEEE 519 (2014)
and THD(U) according to IEC 61000-2-4 (2002). The stringent
= limit values of IEEE 519 (2014) are typically complied with.
Motor
G_D213_EN_00045a Module
Active Line Modules must always be used in conjunction with an
Active Interface Module. Active Interface Modules include the
required pre-charging circuit for the Active Line Module in
M
3 addition to a Clean Power Filter. For SINAMICS S120 Cabinet
Modules, these two components are always regarded as
a single unit.
Line Connection Module with Smart Line Module 800 A

Line Connection Module


Line Connection Module
Switch Bypass Active Active Line
Line Smart Line disconnector contactor Interface Module
Circuit breaker reactor Module with fuses Module
6
=
= Motor
Motor G_D213_EN_00046a Module
G_D213_EN_00094 Module

M
M 3
3

Line Connection Module with Active Interface Module and Active Line
Line Connection Module with Smart Line Module >800 A Module  800 A (example frame size HX + HI)

Line Connection Module Line Connection Module


Line Smart Line Active Active Line
Circuit breaker Circuit breaker Interface Module
reactor Module
Module

=
Motor
= Motor G_D213_EN_00047a Module
Module

M
G_D213_EN_00095
3
M
3
Line Connection Module with Active Interface Module and Active Line
Module >800 A
Line Connection Module with Smart Line Modules connected in parallel

Siemens D 21.3 · 2022 6/9


© Siemens 2022

SINAMICS S120 Cabinet Modules


Air-cooled units

■ Overview
In the example, two units comprising an Active Interface Module Motor Modules
and Active Line Module are connected in parallel to jointly
supply the DC link. There are two different types of Motor Modules available with the
SINAMICS S120 Cabinet Modules drive system.

Line Connection Module


Booksize Base Cabinets with Booksize Cabinet Kits
Active Active Motor Modules at the low end of the power range from 4.8 kW to
Circuit breaker Interface Line 71 kW (380 V to 480 V) can be implemented as Booksize
Module Module
Cabinet Kits installed in Booksize Base Cabinets.
Chassis Cabinets
= Each Chassis Cabinet is fitted with one SINAMICS S120 Motor
Module in chassis format and covers the power range from
= Motor 75 kW to 1200 kW (380 V to 480 V or 500 V to 690 V). The power
Module rating can be extended up to approx. 4500 kW by connecting up
to four Motor Modules in chassis format in parallel.
G_D213_EN_00048b SINAMICS S120 Motor Modules in chassis format can also be
M used as Braking Modules (braking choppers) if a 3-phase
3
braking resistor is connected instead of a motor.
For more information on this topic, please refer to the SINAMICS
Line Connection Module with Active Interface Modules and Active Line Low Voltage Engineering Manual.
Modules connected in parallel
Auxiliary Power Supply Modules
DC link components
Auxiliary Power Supply Modules supply power to the auxiliary
Braking Modules enable braking resistors to absorb the power supply system of the SINAMICS S120 Cabinet Modules.
regenerative energy produced during drive deceleration,
which is then converted into heat. Using a Braking Module Units connected to this auxiliary power supply system include
and a braking resistor, it is possible to brake motors even when the fans of the SINAMICS S120 devices installed in the Cabinet
the power fails. Modules. In addition, the auxiliary power supply system supplies
the electronic modules with an external 24 V DC voltage. This is
Braking Modules as a Line Module or Motor Module option required when the DC link is not charged, for instance, in order
6 For lower braking powers, Braking Modules are available with
to maintain PROFIBUS or PROFINET communication.
continuous braking powers up to 50 kW. These Braking Modules
are ordered as an option for the Line Modules and Motor
Modules (order codes L61/L64 (25 kW) or L62/L65 (50 kW),
refer to the option description).
Central Braking Modules
For higher continuous braking powers, separate Central Braking
Modules are available. These modules are used centrally in the
drive line-up. To increase the braking power, up to four Central
Braking Modules can be connected in parallel in the drive
line-up.

6/10 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Cabinet Modules


Air-cooled units

■ Technical specifications
General technical specifications
Electrical specifications
Line voltages 380 ... 480 V 3 AC, ±10 % (-15 % <1 min)
500 … 690 V 3 AC, ±10 % (-15 % <1 min)
Line supply types Grounded TN/TT systems and non-grounded IT systems
Line frequency 47 ... 63 Hz
Output frequency 1)
• Control mode Servo 0 ... 550 Hz
• Control mode Vector 0 ... 550 Hz
• Control mode V/f 0 ... 550 Hz
Line power factor
Fundamental
• Basic Line Module >0.96
• Smart Line Module >0.96
• Active Line Module Adjustable (factory-set to cos  = 1)
Efficiency
• Basic Line Module >99 %
• Smart Line Module >98.5 %
• Active Line Module >97.5 % (including Active Interface Module)
• Motor Module >98.5 %
Overvoltage category III acc. to EN 61800-5-1
Control method Vector/Servo control with and without encoder or V/f control
Fixed speeds 15 fixed speeds plus 1 minimum speed, parameterizable (in the default setting, 3 fixed setpoints plus 1 minimum speed
are selectable using terminal strip/PROFIBUS/PROFINET)
Skippable speed ranges 4, parameterizable
Setpoint resolution 0.001 rpm digital (14 bits + sign)

Braking operation
12 bits analog
With Active Line Modules and Smart Line Modules, four-quadrant operation as standard (energy recovery).
6
With Basic Line Modules, two-quadrant operation as standard,
braking by means of an optional braking chopper, or alternatively by a Motor Module.
Cabinet system
Cabinet system Rittal TS 8, doors with double-bit key, three-section base plates for cable entry
Paint finish RAL 7035 (indoor requirements)
Mechanical specifications
Degree of protection IP20 (higher degrees of protection up to IP54 optional)
Protection class I acc. to EN 61800-5-1
Touch protection EN 50274/DGUV regulation 3 when used as intended
Cooling method Forced air cooling AF according to EN 60146
Ambient conditions Storage 2) Transport 2) Operation
Ambient temperature -25 ... +55 °C (-13 ... 131 °F) -25 ... +70 °C (-13 ... +158 °F) 0 ... +40 °C (32 ... 104 °F)
from -40 °C (-40 °F) for 24 hours to +50 °C (122 °F) see derating data
Relative humidity 5 ... 95 % 5 ... 95 % at 40 °C (104 °F) 5 ... 95 %
(condensation not permissible) Class 1K4 acc. to IEC 60721-3-1 Class 2K3 acc. to IEC 60721-3-2 Class 3K3 acc. to IEC 60721-3-3
(1997) (1997) (2002)
Environmental class/harmful Class 1C2 Class 2C2 Class 3C2
chemical substances acc. to EN 60721-3-1 (1997) acc. to EN 60721-3-2 (1997) acc. to EN 60721-3-3 (2002)
Organic/biological influences Class 1B1 Class 2B1 Class 3B1
acc. to EN 60721-3-1 (1997) acc. to EN 60721-3-2 (1997) acc. to EN 60721-3-3 (2002)
Mechanically active substances Class 1S1 Class 2S1 Class 3S1
acc. to EN 60721-3-1 (1997) acc. to EN 60721-3-2 (1997) acc. to EN 60721-3-3 (2002)
Degree of pollution 2 acc. to IEC/EN 61800-5-1
Installation altitude Cabinet Modules chassis format:
2000 m (6562 ft) above sea level without derating, >2000 m (6562 ft), see characteristic curves/derating data
For Booksize Cabinet Kit format Motor Modules as well as Central Braking Modules:
 1000 m (3281 ft) above sea level without derating, > 1000 m (3281 ft), see characteristic curves/derating data
Deviations from the specified class are underlined.

1) Higher output frequencies available on request. 2) In transport packaging.

Siemens D 21.3 · 2022 6/11


© Siemens 2022

SINAMICS S120 Cabinet Modules


Air-cooled units

■ Technical specifications
Mechanical stability Storage 1) Transport 1) Operation
Vibratory load Class 1M2 Class 2M2 –
acc. to EN 60721-3-1 (1997) acc. to EN 60721-3-2 (1997)
• Deflection 1.5 mm (0.06 in) at 5 ... 9 Hz 3.1 mm (0.12 in) at 5 ... 9 Hz 0.075 mm (0.003 in) at 10 ... 58 Hz
• Acceleration 5 m/s² (16.4 ft/s²) at >9 ... 200 Hz 10 m/s² (32.8 ft/s²) at >9 ... 200 Hz 9.8 m/s² (32.2 ft/s²) at >58 ... 200 Hz
Shock load Class 1M2 Class 2M2 Class 3M1
acc. to EN 60721-3-1 (1997) acc. to EN 60721-3-2 (1997) acc. to EN 60721-3-3 (2002)
• Acceleration 40 m/s² (131 ft/s²) at 22 ms 100 m/s² (328 ft/s²) at 11 ms Test values acc. to EN 60068-2-27
test Ea: 5 g, 30 ms, 3 shocks
Compliance with standards
Conformances/certificates of CE (EMC Directive 2014/30/EU, Low Voltage Directive 2014/35/EU, and Machinery Directive 2006/42/EC for functional
suitability, according to safety)
RCM, RoHS II, UKCA, marine certification DNV (Type approval), CCS (only in combination with the Option M66)
Green Passport: Option B50 creates a form for the material declaration according to Green Passport.
Radio interference suppression SINAMICS converter systems are not designed for connection to the public grid (first environment). Radio interference
suppression is compliant with the EMC product standard for variable-speed drives EN 61800-3, "Second environment"
(industrial networks). EMC disturbances can occur when connected to the public grid. However, if additional measures
are taken (e.g.  line filter), it can also be operated in the "first environment".

Deviations from the specified class are underlined.

1)
In transport packaging.

6/12 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Cabinet Modules


Air-cooled units

■ Characteristic curves
Derating data for the chassis format The following table specifies the permissible output currents as
a function of the installation altitude and ambient temperature for
SINAMICS S120 Cabinet Modules and the associated system the various degrees of protection. (The permissible
components are rated for an ambient temperature of 40 °C and compensation between installation altitude and the ambient
installation altitudes up to 2000 m above sea level. temperatures < 40 °C – air intake temperature at the entry to the
At ambient temperatures > 40 °C, the output current must be Cabinet Module – has been taken into account in the specified
reduced. Ambient temperatures above 50 °C are not values.)
permissible. The values apply under the precondition that it is guaranteed
At installation altitudes > 2000 m above sea level, it must be that the cooling air, as specified in the technical data, flows
taken into account that the air pressure, and therefore air density, through the units as a result of the cabinet arrangement.
decreases as the height increases. As a consequence, the As an additional measure for installation altitudes from 2000 m
cooling efficiency and the insulation capacity of the air also up to 5000 m, an isolating transformer is required in order to
decrease. reduce transient overvoltages according to EN 60664-1.
Due to the reduced cooling efficiency, it is necessary to both For additional information, please refer to the SINAMICS Low
reduce the ambient temperature and lower heat loss in the Voltage Engineering Manual.
Cabinet Module by reducing the output current, whereby
ambient temperatures lower than 40 °C may be offset
to compensate.
Current-derating factors for Cabinet Modules as a function of the ambient/air intake temperature,
the installation altitude and the degree of protection
Degree of Installation altitude Current derating factor (as a percentage of the rated current)
protection above sea level for an ambient/air intake temperature of
m (ft) 20 °C (68 °F) 25 °C (77 °F) 30 °C (86 °F) 35 °C (95 °F) 40 °C (104 °F) 45 °C (113 °F) 50 °C (122 °F)
IP20, IP21, 0 ... 2000 93.3 % 86.7 %
IP23, IP43 (0 ... 6562)
2001 ... 2500 96.3 %
(6565 ... 8202)
2501 ... 3000
(8205 ... 9843)
100 % 98.7 %
6
3001 ... 3500
(9846 ... 11483)
3501 ... 4000 96.3 %
(11486 ... 13123)
4001 ... 4500 97.5 %
(13127 ... 14764)
4501 ... 5000 98.2 %
(14767 ... 16404)
IP54 0 ... 2000 93.3 % 86.7 % 80 %
(0 ... 6562)
2001 ... 2500 96.3 % 89.8 %
(6565 ... 8202)
2501 ... 3000 100 % 98.7 % 92.5 %
(8205 ... 9843)
3001 ... 3500 94.7 %
(9846 ... 11483)
3501 ... 4000 96.3 % 90.7 %
(11486 ... 13123)
4001 ... 4500 97.5 % 92.1 %
(13127 ... 14764)
4501 ... 5000 93 %
(14767 ... 16404)

Siemens D 21.3 · 2022 6/13


© Siemens 2022

SINAMICS S120 Cabinet Modules


Air-cooled units

■ Characteristic curves
Current derating for SINAMICS S120 Motor Modules, chassis the derating factor of the output current must be taken into
format as a function of the pulse frequency account. This derating factor must be applied to the currents
specified in the technical specifications.
To reduce motor noise or to increase output frequency, the pulse For additional information, please refer to the SINAMICS Low
frequency can be increased relative to the factory setting Voltage Engineering Manual.
(1.25 kHz or 2 kHz). When the pulse frequency is increased,
Derating factor of the output current as a function of the pulse frequency for units with a rated pulse frequency of 2 kHz
Motor Module in Type rating Output current Derating factor
chassis format at 400 V at 2 kHz at pulse frequency
6SL3720-... kW A 2.5 kHz 4 kHz 5 kHz 7.5 kHz 8 kHz
380 ... 480 V 3 AC
1TE32-1AA3 110 210 95 % 82 % 74 % 54 % 50 %
1TE32-6AA3 132 260 95 % 83 % 74 % 54 % 50 %
1TE33-1AA3 160 310 97 % 88 % 78 % 54 % 50 %
1TE33-8AA3 200 380 96 % 87 % 77 % 54 % 50 %
1TE35-0AA3 250 490 94 % 78 % 71 % 53 % 50 %

Derating factor of the output current as a function of the pulse frequency for units with a rated pulse frequency of 1.25 kHz
Motor Module in Type rating Output current Derating factor
chassis format at 400 V or 690 V at 1.25 kHz at pulse frequency
6SL3720-... kW A 2 kHz 2.5 kHz 4 kHz 5 kHz 7.5 kHz 8 kHz
380 ... 480 V 3 AC
1TE36-1AA3 315 605 83 % 72 % 64 % 60 % 40 % 36%
1TE37-5AA3 400 745 83 % 72 % 64 % 60 % 40 % 36%

6 1TE38-4AA3 450 840 87 % 79 % 64 % 55 % 40 % 37 %


1TE41-0AA3 560 985 92 % 87 % 70 % 60 % 50 % 47 %
1TE41-2AA3 710 1260 92 % 87 % 70 % 60 % 50 % 47 %
1TE41-4AA3 800 1405 97 % 95 % 74 % 60 % 50 % 47 %
500 ... 690 V 3 AC
1TG28-5AA3 75 85 93 % 89 % 71 % 60 % 40 % -
1TG31-0AA3 90 100 92 % 88 % 71 % 60 % 40 % -
1TG31-2AA3 110 120 92 % 88 % 71 % 60 % 40 % -
1TG31-5AA3 132 150 90 % 84 % 66 % 55 % 35 % -
1TG31-8AA3 160 175 92 % 87 % 70 % 60 % 40 % -
1TG32-2AA3 200 215 92 % 87 % 70 % 60 % 40 % -
1TG32-6AA3 250 260 92 % 88 % 71 % 60 % 40 % -
1TG33-3AA3 315 330 89 % 82 % 65 % 55 % 40 % -
1TG34-1AA3 400 410 89 % 82 % 65 % 55 % 35 % -
1TG34-7AA3 450 465 92 % 87 % 67 % 55 % 35 % -
1TG35-8AA3 560 575 91 % 85 % 64 % 50 % 35 % -
1TG37-4AA3 710 735 87 % 79 % 64 % 55 % 35 % -
1TG38-1AA3 800 810 97 % 95 % 71 % 55 % 35 % -
1TG38-8AA3 900 910 92 % 87 % 67 % 55 % 33 % -
1TG41-0AA3 1000 1025 91 % 86 % 64 % 50 % 30 % -
1TG41-3AA3 1200 1270 87 % 79 % 55 % 40 % 25 % -

6/14 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Cabinet Modules


Air-cooled units

■ Characteristic curves
Maximum output frequencies achieved by increasing the pulse frequency
The adjustable pulse frequencies – and therefore the output
frequencies that can be achieved with the factory-set current
controller clock cycles – are listed below.
Current controller clock cycle Adjustable pulse frequency Max. achievable output frequency fA
TI fp
V/f mode Vector mode Servo mode
250 µs 1) 2 kHz 166 Hz 166 Hz 333 Hz
4 kHz 333 Hz 333 Hz 550 Hz 3)
8 kHz 550 Hz 3) 480 Hz 550 Hz 3)
400 µs 2) 1.25 kHz 104 Hz 104 Hz –
2.5 kHz 208 Hz 208 Hz –
5.0 kHz 416 Hz 300 Hz –
7.5 kHz 550 Hz 3) 300 Hz –

1) 3)
As factory setting, the following Motor Modules in chassis format have With the "High output frequencies" license, which can be ordered as option
a current controller clock cycle of 250 µs and a pulse frequency of 2 kHz: J01 on the CompactFlash card for SINAMICS S120, the maximum output
- 510 ... 720 V DC:  250 kW / 490 A frequency is increased up to 650 Hz. For more information, see
2)
As factory setting, the following Motor Modules in chassis format have a https://support.industry.siemens.com/cs/document/104020669
current controller clock cycle of 400 µs and a pulse frequency of 1.25 kHz:
- 510 ... 720 V DC:  315 kW / 605 A
- 675 ... 1035 V DC: All power ratings

Siemens D 21.3 · 2022 6/15


© Siemens 2022

SINAMICS S120 Cabinet Modules


Air-cooled units

■ Characteristic curves
Derating data for devices in booksize format The base-load current IH for a high overload is based on a load
cycle of 150 % for 60 s or 160 % for 10 s.
SINAMICS S120 Cabinet Modules with power units in booksize
format and the associated system components are rated for an
ambient temperature of 40 °C and installation altitudes up to Converter current
1000 m above sea level. If SINAMICS S120 Cabinet Modules 10 s
with power units in booksize format are operated at ambient
1.6 x IH Short-time current 160 %
temperatures higher than 40 °C and/or installation altitudes
higher than 1000 m above sea level, then the corresponding 1.5 x IH Short-time current 150 %
derating factors must be taken into account as a function of the
ambient temperature and/or the installation altitude.
Rated current (continuous)
These derating factors are different from the derating factors for
the chassis format power units and are listed in Catalog D 21.4.
Base-load current IH for high overload
Overload capability IN
SINAMICS S120 Cabinet Modules have an overload reserve,
IH

G_D213_EN_00036
e.g. to handle breakaway torques. If larger surge loads occur,
this must be taken into account in the configuration. For drives 60 s
300 s
with overload requirements, the appropriate base load current
must, therefore, be used as a basis for the required load.
Permissible overload assumes that the converter is operated at t
its base-load current before and after the overload occurs,
based on a duty cycle duration of 300 s.
High overload
Another precondition is that the Motor Modules are operated at
Motor Modules in booksize format
their factory-set pulse frequency at output frequencies >10 Hz.
Motor Modules with power units in the booksize format have the
For temporary, periodic duty cycles with high variations of load
following overload capabilities:
within the duty cycle, the relevant sections of the SINAMICS Low
Voltage Engineering Manual must be observed.
Motor Modules in chassis format Converter current
6 Motor Modules with power units in chassis format can be 1.76 IH
Short-time current

configured on the basis of different base load currents.


1 .5 IH Rated current (continuous)
The base-load current for a low overload IL is the basis for a duty
Base-load current IH
cycle of 110 % for 60 s or 150 % for 10 s. for high overload

G_D213_EN_00049
Converter current
IH
30 s
10 s 60 s
300 s
1.5 x IL

Short-time current 150 %


t
Short-time current 110 %
Rated current (continuous) High overload
Base-load current IL Line Modules in chassis format
1.1 x IL
for low overload
The base-load current for a high overload IH DC is the basis for
IN
IL
a duty cycle of 150 % for 60 s or Imax DC for 5 s.
G_D213_EN_00035

60 s
300 s Converter current
5s
Imax DC Short-time current Imax
t
1.5 x IH DC Short-time current 150 %
Low overload
Rated current (continuous)
Base-load current IH DC
for high overload
IN DC

IH DC
G_D213_EN_00079

60 s
300 s

6/16 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Cabinet Modules


Air-cooled units
Line Connection Modules

■ Overview ■ Design
Different versions exist depending on the input current:
• Units  800 A are equipped with a main circuit breaker with
a fuse switch disconnector
• Units > 800 A are equipped with a fixed-mounted circuit
breaker (draw-out circuit breaker is available as option)
When Line Connection Modules are ordered, the type of Line
Module used must be specified:
• For Basic Line Modules: Option L43
• For Smart Line Modules: Option L44
• For Active Line Modules: Option L42
When using a Basic Line Module, a reactor is included in the
scope of supply of the Line Connection Module, and when
required, can be deselected (option L22).
For additional information, please refer to the SINAMICS Low
Voltage Engineering Manual.

Line Connection Modules (LCM) contain the line-side infeed with Option
L13
main circuit breaker and fuse switch disconnector or circuit -X1 -Q1 -Q2 -R1 -X2
breaker and provide the connection between the plant power U1/L1 U1/L1
V1/L2 V1/L2
system and the Line Modules. W1/L3 W1/L3

Line Connection Modules are available for the following voltages


and currents:
G_D213_EN_00050a
Line voltage Rated infeed/regenerative
feedback current
380 ... 480 V 3 AC 250 ... 3200 A Connection example of a Line Connection Module for units  800 A to
connect to Basic Line Modules, option L43, option main contactor,
500 ... 690 V 3 AC 280 ... 3200 A
order code L13 6
3WL1

-X 1 - Q1 -R1 -X 2
U1/L1 U1/L1
V1/L2 V1/L2
W1/L3 W1/L3

G_D213_XX_00051a

Connection example of a Line Connection Module for units > 800 A,


< 2000 A to connect to Basic Line Modules, option L43
For input currents  2000 A, additional options are available:
• Grounding switch upstream of main circuit breaker:
Option L46
• Current transformer upstream of main circuit breaker:
Option L41
• Grounding switch downstream of main circuit breaker:
Option L47

Option Option Option


L46 L41 3WL1 L47
-X1 -Q1 -R1 -X2
U1/L1 U1_1
V1/L2 V1_1
W1/L3 W1_1

-R1.1 -X3
U1_2
V1_2
W1_2

G_D213_EN_00052a

Connection example of a Line Connection Module  2000 A

Siemens D 21.3 · 2022 6/17


© Siemens 2022

SINAMICS S120 Cabinet Modules


Air-cooled units
Line Connection Modules

■ Design ■ Selection and ordering data


When Basic Line Modules that are fed via a common Line Rated infeed/regenerative Line Connection Module
Connection Module are connected in parallel, line reactors are feedback current 1)
generally required. These are installed in the Line Connection A Article No.
Module.
Line voltage 380 ... 480 V 3 AC
250 6SL3700-0LE32-5AA3
3WL1
380 6SL3700-0LE34-0AA3
-X1 -Q1 -R1 -X2
U1/L1 U1_1 600 6SL3700-0LE36-3AA3
V1/L2 V1_1
W1/L3 W1_1 770 6SL3700-0LE38-0AA3
-R1.1 -X3 1000 6SL3700-0LE41-0AA3
U1_2
V1_2 1250 6SL3700-0LE41-3AA3
W1_2
1600 6SL3700-0LE41-6AA3
G_D213_XX_00053a
2000 6SL3700-0LE42-0AA3

Connection example of a Line Connection Module  2000 A for 2000 6SL3700-0LE42-0BA3


connection to Basic Line Modules, option L43 2500 6SL3700-0LE42-5BA3
3200 6SL3700-0LE43-2BA3
-Q10 Line voltage 500 ... 690 V 3 AC
K4_2_1
K4_4_1 280 6SL3700-0LG32-8AA3
K4_6_1
K4_2_2 380 6SL3700-0LG34-0AA3
K4_4_2
3WL1 K4_6_2 600 6SL3700-0LG36-3AA3
-X1 -Q1 -X2
U1/L1 U1_1 770 6SL3700-0LG38-0AA3
V1/L2 V1_1
W1/L3 W1_1 1000 6SL3700-0LG41-0AA3
-X3
U1_2 1250 6SL3700-0LG41-3AA3
V1_2
W1_2 1600 6SL3700-0LG41-6AA3

6 G_D213_XX_00054a 2000 6SL3700-0LG42-0BA3


2500 6SL3700-0LG42-5BA3
Connection example of a Line Connection Module  2000 A for
connection to Active Line Modules in parallel connection, option L42 3200 6SL3700-0LG43-2BA3

Note:
When ordering Line Connection Modules, the option order code
must be appended to the article number to indicate whether the
Line Connection Module is to be connected to a Basic Line
Module (option L43), to a Smart Line Module (option L44) or to
an Active Line Module (option L42).
This information is required to ensure that the Line Connection
Module is correctly equipped at the factory. This particularly
applies to the busbar connection at the 3-phase end (3 AC),
to any pre-charging circuits required and to the specified line
reactors for Basic Line Modules.
When Cabinet Modules are selected and combined, the
specified equipping and preparation of the Line Connection
Modules is performed at the factory in accordance with the
assignment table in the Integration section. For all other
combinations deviating from this, this is not the case. In such
cases, the 3-AC busbar connections will have to be configured
and installed on site.

1) The current values stated are based on an ambient temperature


(air intake temperature) of 40 °C (104 °F).

6/18 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Cabinet Modules


Air-cooled units
Line Connection Modules

■ Integration
Line Connection Module Basic Line Module Smart Line Module Active Line Module
Rated Rated input Rated Rated
infeed/ current infeed/ infeed/
regenera- regenera- regenera-
tive feed- tive feed- tive feed-
back back back
current 1) current current
A A A A
Line voltage 380 ... 480 V 3 AC
250 6SL3700-0LE32-5AA3 – – – – 210 6SL3730-7TE32-1BA3
380 6SL3700-0LE34-0AA3 – – – – 260 6SL3730-7TE32-6BA3
600 6SL3700-0LE36-3AA3 365 6SL3730-1TE34-2AA3 463 6SL3730-6TE35-5AA3 380 6SL3730-7TE33-8BA3
460 6SL3730-1TE35-3AA3 490 6SL3730-7TE35-0BA3
770 6SL3700-0LE38-0AA3 710 6SL3730-1TE38-2AA3 614 6SL3730-6TE37-3AA3 605 6SL3730-7TE36-1BA3
1000 6SL3700-0LE41-0AA3 – – 883 6SL3730-6TE41-1AA3 840 6SL3730-7TE38-4BA3
1250 6SL3700-0LE41-3AA3 1010 6SL3730-1TE41-2AA3 1093 6SL3730-6TE41-3AA3 985 6SL3730-7TE41-0BA3
1600 6SL3700-0LE41-6AA3 1265 6SL3730-1TE41-5AA3 1430 6SL3730-6TE41-7AA3 1405 6SL3730-7TE41-4BA3
2000 6SL3700-0LE42-0AA3 1630 6SL3730-1TE41-8AA3 – – – –
2000 6SL3700-0LE42-0BA3 2 × 935 6SL3730-1TE41-2BA3 2 × 817 6SL3730-6TE41-1BA3 2 × 936 6SL3730-7TE41-0BA3
6SL3730-1TE41-2BC3 6SL3730-6TE41-1BC3 6SL3730-7TE41-0BC3
2500 6SL3700-0LE42-5BA3 2 × 1170 6SL3730-1TE41-5BA3 2 × 1011 6SL3730-6TE41-3BA3 – –
6SL3730-1TE41-5BC3 6SL3730-6TE41-3BC3
3200 6SL3700-0LE43-2BA3 2 × 1508 6SL3730-1TE41-8BA3 2 × 1323 6SL3730-6TE41-7BA3 2 × 1335 6SL3730-7TE41-4BA3
6SL3730-1TE41-8BC3 6SL3730-6TE41-7BC3 6SL3730-7TE41-4BC3
Line voltage 500 ... 690 V 3 AC
280 6SL3700-0LG32-8AA3 260 6SL3730-1TG33-0AA3 – – – – 6
380 6SL3700-0LG34-0AA3 375 6SL3730-1TG34-3AA3 – – – –
600 6SL3700-0LG36-3AA3 575 6SL3730-1TG36-8AA3 463 6SL3730-6TG35-5AA3 575 6SL3730-7TG35-8BA3
770 6SL3700-0LG38-0AA3 – – 757 6SL3730-6TG38-8AA3 735 6SL3730-7TG37-4BA3
1000 6SL3700-0LG41-0AA3 925 6SL3730-1TG41-1AA3 – – – –
1250 6SL3700-0LG41-3AA3 1180 6SL3730-1TG41-4AA3 1009 6SL3730-6TG41-2AA3 1025 6SL3730-7TG41-0BA3
1600 6SL3700-0LG41-6AA3 1580 6SL3730-1TG41-8AA3 1430 6SL3730-6TG41-7AA3 1270 6SL3730-7TG41-3BA3
2000 6SL3700-0LG42-0BA3 2 × 855 6SL3730-1TG41-1BA3 2 × 700 6SL3730-6TG38-8BA3 2 × 698 6SL3730-7TG37-4BA3
6SL3730-1TG41-1BC3 6SL3730-6TG38-8BC3 6SL3730-7TG37-4BC3
– – 2 × 934 6SL3730-6TG41-2BA3 2 × 974 6SL3730-7TG41-0BA3
6SL3730-6TG41-2BC3 6SL3730-7TG41-0BC3
2500 6SL3700-0LG42-5BA3 2 × 1092 6SL3730-1TG41-4BA3 – – 2 × 1206 6SL3730-7TG41-3BA3
6SL3730-1TG41-4BC3 6SL3730-7TG41-3BC3
3200 6SL3700-0LG43-2BA3 2 × 1462 6SL3730-1TG41-8BA3 2 × 1323 6SL3730-6TG41-7BA3 – –
6SL3730-1TG41-8BC3 6SL3730-6TG41-7BC3
Entries in Parallel circuit of two Line Modules connected to a Line Connection Module.
italics: The required derating factors listed below are already included in the current values given above:
• 7.5 % for Basic Line Modules
• 7.5 % for Smart Line Modules
• 5 % for Active Line Modules

1)
The current values stated are based on an ambient temperature
(air intake temperature) of 40 °C (104 °F).

Siemens D 21.3 · 2022 6/19


© Siemens 2022

SINAMICS S120 Cabinet Modules


Air-cooled units
Line Connection Modules

■ Technical specifications
Line voltage 380 ... 480 V 3 AC Line Connection Modules
6SL3700- 6SL3700- 6SL3700- 6SL3700- 6SL3700- 6SL3700-
0LE32-5AA3 0LE34-0AA3 0LE36-3AA3 0LE38-0AA3 0LE41-0AA3 0LE41-3AA3
Infeed/regenerative feedback
current
• Rated current IN I A 250 380 600 770 1000 1250
Current demand
• Fan power supply A – – – – 1.07 1.07
230 V AC
• 230 V AC 1)
- Inrush current A 3.6 3.6 3.6 10.8 0.5 0.5
- Holding current A 0.04 0.04 0.04 0.12 0.06 0.06
Power loss, max. 2)
• At 50 Hz 400 V
- Option L42/L44 kW 0.115 0.19 0.31 0.39 0.18 0.29
- Option L43 kW – – 0.675 0.74 – 0.787
• At 60 Hz 460 V
- Option L42/L44 kW 0.115 0.19 0.31 0.39 0.18 0.29
- Option L43 kW – – 0.675 0.74 – 0.787
Cooling air requirement 3) m3/s (ft3/s) – – – – 0.36 (12.7) 0.36 (12.7)
Sound pressure level LpA dB – – – – 68/70 68/70
(1 m) at 50/60 Hz
Line supply connection 2 x M12 2 x M12 2 x M12 4 x M12 10 x M12 10 x M12
L1, L2, L3
• Conductor cross-section, max. (IEC) mm2 2 × 150 2 × 150 4 × 240 8 × 240 8 × 240 8 × 240
PE/GND connection PE bar PE bar PE bar PE bar PE bar PE bar
• Busbar cross-section mm2 600 600 600 600 600 600
• Conductor cross-section, max. (IEC) mm2 240 240 240 240 240 240

6 Degree of protection IP20 IP20 IP20 IP20 IP20 IP20


Dimensions
• Width mm (in) 400 (15.7) 400 (15.7) 600 (23.6) 600 (23.6) 600 (23.6) 600 (23.6)
• Height 4) mm (in) 2200 (86.6) 2200 (86.6) 2200 (86.6) 2200 (86.6) 2200 (86.6) 2200 (86.6)
• Depth mm (in) 600 (23.6) 600 (23.6) 600 (23.6) 600 (23.6) 600 (23.6) 600 (23.6)
Weight, approx.
• Option L42/L44 kg (lb) 210 (463) 230 (507) 310 (683) 340 (750) 450 (992) 470 (1036)
• Option L43 kg (lb) – – 360 (794) 420 (926) – 570 (1257)
Frame size FL FL GL HL JL JL
Rated short-circuit current kA 50 50 50 50 50 50
according to IEC
Minimum short-circuit current 5) kA 3 3 8 12 2 2.5

1) 4)
Current demand of contactors/circuit breakers and fans with degree of The cabinet height increases by 250 mm (9.84 in) with degree of protection
protection IP23, IP43, IP54 (in combination with Basic Line Modules). IP21, and by 400 mm (15.7 in) with degrees of protection IP23, IP43 and
2)
The specified power loss represents the maximum value at 100 % IP54.
5)
utilization. The value is lower under normal operating conditions. Current required to ensure reliable tripping of installed protective devices.
3)
For IP23, IP43 or IP54 degree of protection only (in combination with Basic
Line Modules).

6/20 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Cabinet Modules


Air-cooled units
Line Connection Modules

■ Technical specifications
Line voltage 380 ... 480 V 3 AC Line Connection Modules
6SL3700- 6SL3700- 6SL3700- 6SL3700- 6SL3700-
0LE41-6AA3 0LE42-0AA3 0LE42-0BA3 0LE42-5BA3 0LE43-2BA3
Prepared for connection to Line Modules connected
in parallel
Infeed/regenerative feedback
current
• Rated current IN I A 1600 2000 2000 2500 3200
Current demand
• Fan power supply A 1.07 2.14 2.14 2.14 2.14
230 V AC
• 230 V AC 1)
- Inrush current A 0.5 0.5 0.5 0.5 0.5
- Holding current A 0.06 0.06 0.06 0.06 0.04
Power loss, max. 2)
• At 50 Hz 400 V
- Option L42/L44 kW 0.41 0.6 0.6 0.95 0.95
- Option L43 kW 1.186 1.366 1.594 2.502 2.482
• At 60 Hz 460 V
- Option L42/L44 kW 0.41 0.6 0.6 0.95 0.95
- Option L43 kW 1.186 1.366 1.594 2.502 2.482
Cooling air requirement 3) m3/s (ft3/s) 0.36 (12.7) 0.72 (25.4) 0.72 (25.4) 0.72 (25.4) 0.72 (25.4)
Sound pressure level LpA dB 68/70 70/72 70/72 70/72 70/72
(1 m) at 50/60 Hz
Line supply connection 10 x M12 10 x M12 + 4 x M16 10 x M12 + 4 x M16 10 x M12 + 4 x M16 10 x M12 + 4 x M16
L1, L2, L3
• Conductor cross-section, max. (IEC) mm2 8 × 240 10 × 240 10 × 240 10 × 240 10 × 300
PE/GND connection PE bar PE bar PE bar PE bar PE bar
• Busbar cross-section mm2
• Conductor cross-section, max. (IEC) mm2
600
240
600
240
600
240
600
240
600
240
6
Degree of protection IP20 IP20 IP20 IP20 IP20
Dimensions
• Width mm (in) 600 (23.6) 1000 (39.4) 1000 (39.4) 1000 (39.4) 1000 (39.4)
• Height 4) mm (in) 2200 (86.6) 2200 (86.6) 2200 (86.6) 2200 (86.6) 2200 (86.6)
• Depth mm (in) 600 (23.6) 600 (23.6) 600 (23.6) 600 (23.6) 600 (23.6)
Weight, approx.
• Option L42/L44 kg (lb) 490 (1080) 600 (1323) 620 (1367) 620 (1367) 720 (1587)
• Option L43 Kg (lb) 650 (1433) 760 (1676) 820 (1808) 900 (1984) 1000 (2205)
Frame size JL KL KL KL LL
Rated short-circuit current kA 100 100 100 100 100
according to IEC
Minimum short-circuit current 5) kA 3.2 4 4 5 6.4

1) 4)
Current demand of contactors/circuit breakers and fans with degree of The cabinet height increases by 250 mm (9.84 in) with degree of
protection IP23, IP43, IP54 (in combination with Basic Line Modules). protection IP21, and by 400 mm (15.7 in) with degrees of protection IP23,
2)
The specified power loss represents the maximum value at 100 % IP43 and IP54.
5)
utilization. The value is lower under normal operating conditions. Current required to ensure reliable tripping of installed protective devices.
3)
For IP23, IP43 or IP54 degree of protection only (in combination with
Basic Line Modules).

Siemens D 21.3 · 2022 6/21


© Siemens 2022

SINAMICS S120 Cabinet Modules


Air-cooled units
Line Connection Modules

■ Technical specifications
Line voltage 500 ... 690 V 3 AC Line Connection Modules
6SL3700- 6SL3700- 6SL3700- 6SL3700- 6SL3700-
0LG32-8AA3 0LG34-0AA3 0LG36-3AA3 0LG38-0AA3 0LG41-0AA3
Infeed/regenerative feedback
current
• Rated current IN I A 280 380 600 770 1000
Current demand
• Fan power supply A – – – – 1.07
230 V AC
• 230 V AC 1)
- Inrush current A 3.6 3.6 3.6 10.8 0.5
- Holding current A 0.04 0.04 0.04 0.12 0.06
Power loss, max. 2)
• At 50 Hz 500/690 V
- Option L42/L44 kW 0.125 0.19 0.31 0.39 0.18
- Option L43 kW 0.402 0.668 0.794 – 0.963
• At 60 Hz 575 V
- Option L42/L44 kW 0.125 0.19 0.31 0.39 0.18
- Option L43 kW 0.402 0.668 0.794 – 0.963
Cooling air requirement 3) m3/s (ft3/s) – – – – 0.36 (12.7)
Sound pressure level LpA dB – – – – 68/70
(1 m) at 50/60 Hz
Line supply connection 2 x M12 2 x M12 2 x M12 2 x M12 10 x M12
L1, L2, L3
• Conductor cross-section, max. (IEC) mm2 2 × 150 2 × 150 4 × 240 8 × 240 8 × 240
PE/GND connection PE bar PE bar PE bar PE bar PE bar
• Busbar cross-section mm2 600 600 600 600 600
• Conductor cross-section, max. (IEC) mm2 240 240 240 240 240

6 Degree of protection IP20 IP20 IP20 IP20 IP20


Dimensions
• Width mm (in) 400 (15.7) 600 (23.6) 600 (23.6) 600 (23.6) 600 (23.6)
• Height 4) mm (in) 2200 (86.6) 2200 (86.6) 2200 (86.6) 2200 (86.6) 2200 (86.6)
• Depth mm (in) 600 (23.6) 600 (23.6) 600 (23.6) 600 (23.6) 600 (23.6)
Weight, approx.
• Option L42/L44 kg (lb) 220 (485) 230 (507) 310 (683) 340 (750) 450 (992)
• Option L43 kg (lb) 260 (573) 310 (683) 400 (882) – 650 (1433)
Frame size FL FL GL HL JL
Rated short-circuit current kA 50 50 50 50 85
according to IEC
Minimum short-circuit current 5) kA 3.2 3.5 9 15 2

1) 4)
Current demand of contactors/circuit breakers and fans with degree of The cabinet height increases by 250 mm (9.84 in) with degree of
protection IP23, IP43, IP54 (in combination with Basic Line Modules). protection IP21, and by 400 mm (15.7 in) with degrees of protection IP23,
2)
The specified power loss represents the maximum value at 100 % IP43 and IP54.
5)
utilization. The value is lower under normal operating conditions. Current required to ensure reliable tripping of installed protective devices.
3)
For IP23, IP43 or IP54 degree of protection only (in combination with
Basic Line Modules).

6/22 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Cabinet Modules


Air-cooled units
Line Connection Modules

■ Technical specifications
Line voltage 500 ... 690 V 3 AC Line Connection Modules
6SL3700- 6SL3700- 6SL3700- 6SL3700- 6SL3700-
0LG41-3AA3 0LG41-6AA3 0LG42-0BA3 0LG42-5BA3 0LG43-2BA3
Prepared for connection to Line Modules connected
in parallel
Infeed/regenerative feedback
current
• Rated current IN I A 1250 1600 2000 2500 3200
Current demand
• Fan power supply A 1.07 1.07 2.14 2.14 2.14
230 V AC
• 230 V AC 1)
- Inrush current A 0.5 0.5 0.5 0.5 0.5
- Holding current A 0.06 0.06 0.06 0.06 0.06
Power loss, max. 2)
• At 50 Hz 500/690 V
- Option L42/L44 kW 0.29 0.41 0.6 0.6 0.95
- Option L43 kW 1.073 1.387 2.166 2.166 2.894
• At 60 Hz 575 V
- Option L42/L44 kW 0.29 0.41 0.6 0.6 0.95
- Option L43 kW 1.073 1.387 2.166 2.166 2.894
Cooling air requirement 3) m3/s (ft3/s) 0.36 (12.7) 0.36 (12.7) 0.72 (25.4) 0.72 (25.4) 0.72 (25.4)
Sound pressure level LpA dB 68/70 68/70 70/72 70/72 70/72
(1 m) at 50/60 Hz
Line supply connection 10 x M12 10 x M12 10 x M12 + 4 x M16 10 x M12 + 4 x M16 10 x M12 + 4 x M16
L1, L2, L3
• Conductor cross-section, max. (IEC) mm2 8 × 240 8 × 240 10 × 240 10 × 240 10 × 300
PE/GND connection PE bar PE bar PE bar PE bar PE bar
• Busbar cross-section mm2
• Conductor cross-section, max. (IEC) mm2
600
240
600
240
600
240
600
240
600
240
6
Degree of protection IP20 IP20 IP20 IP20 IP20
Dimensions
• Width mm (in) 600 (23.6) 600 (23.6) 1000 (39.4) 1000 (39.4) 1000 (39.4)
• Height 4) mm (in) 2200 (86.6) 2200 (86.6) 2200 (86.6) 2200 (86.6) 2200 (86.6)
• Depth mm (in) 600 (23.6) 600 (23.6) 600 (23.6) 600 (23.6) 600 (23.6)
Weight, approx.
• Option L42/L44 kg (lb) 470 (1036) 490 (1080) 600 (1323) 620 (1367) 720 (1587)
• Option L43 kg (lb) 670 (1477) 680 (1499) 980 (2161) 1000 (2205) 1080 (2381)
Frame size JL JL KL KL LL
Rated short-circuit current kA 85 85 85 85 85
according to IEC
Minimum short-circuit current 5) kA 2.5 3.2 4 5 6.4

1) 4)
Current demand of contactors/circuit breakers and fans with degree of The cabinet height increases by 250 mm (9.84 in) with degree of
protection IP23, IP43, IP54 (in combination with Basic Line Modules). protection IP21, and by 400 mm (15.7 in) with degrees of protection IP23,
2)
The specified power loss represents the maximum value at 100 % IP43 and IP54.
5)
utilization. The value is lower under normal operating conditions. Current required to ensure reliable tripping of installed protective devices.
3)
For IP23, IP43 or IP54 degree of protection only (in combination with
Basic Line Modules).

Siemens D 21.3 · 2022 6/23


© Siemens 2022

SINAMICS S120 Cabinet Modules


Air-cooled units
Basic Line Modules

■ Overview
Basic Line Modules are suitable for connection to grounded
TN/TT and non-grounded IT systems. The following voltages and
power ratings are available:
Line voltage Rated power
380 ... 480 V 3 AC 200 ... 900 kW
500 ... 690 V 3 AC 250 ... 1500 kW

The power ratings can be increased by connecting up to four


identical Basic Line Modules in parallel.
For an infeed with the Basic Line Modules, depending on the line
short-circuit power, a line reactor should be provided at the
connection point. This reactor is available as standard in the Line
Connection Module. However, it can be omitted if it is not
required (option L22).
Further information can be found in the SINAMICS Low Voltage
Engineering Manual.

Basic Line Modules (BLM) are compact line infeeds for two-
quadrant operation, i.e. no regenerative feedback.
They are used when energy need not be fed back into the
network.
If regenerative conditions occur in the drive line-up, Braking
Modules must be used because they convert the excess energy
into heat in braking resistors.

■ Design
6 The Basic Line Modules are available in different frame sizes. Parallel connection of Basic Line Modules to increase power
rating
With frame sizes FB and GB, a fully controlled thyristor bridge is
used to pre-charge the Basic Line Modules and connected Line Modules can be connected in parallel (relative to the line
Motor Modules. The thyristors normally operate with a trigger supply) in two ways for the purpose of creating drive line-ups
delay angle of 0°. with a higher power rating.
Basic Line Modules, frame size GD for 900 kW (400 V) or Two Basic Line Modules supplied with power via two separate
1500 kW (690 V) include a diode bridge, and the DC link is pre- Line Connection Modules
charged via a separate line-side pre-charging device that is
located in the Line Connection Module (option L43, Line With this arrangement, each Basic Line Module is supplied
Connection Module for Basic Line Module). via a Line Connection Module and the Basic Line Modules are
protected by fuses or circuit breakers (at I > 800 A) in the Line
Connection Module. A Basic Line Module is assigned to a Line
Connection Module and is mechanically coupled. It is not
necessary to mechanically directly couple both "groups"
comprising Line Connection Module and Basic Line Module.
Other modules can also be inserted in between.

DC busbar

Motor Motor Motor Line Basic Line Basic Motor Motor Motor
G_D213_EN_00055a

Module Module Module Connection Line Connection Line Module Module Module
Module Module Module Module

6SL3730- 6SL3730-
1T...-.AA3 1T...-.AA3

Motor feeder Infeed Infeed Motor feeder

6/24 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Cabinet Modules


Air-cooled units
Basic Line Modules

■ Design
Two Basic Line Modules supplied with power via a single Line For additional information, please refer to the SINAMICS Low
Connection Module Voltage Engineering Manual.
Basic Line Modules are available that can be operated on These module versions feature integrated line-side fuses which
a single Line Connection Module. These can be connected are required because the circuit breaker in the Line Connection
to the left and right of the Line Connection Module. The power Module is not capable of providing selective protection for the
connections on the Basic Line Module on the left of the Line Basic Line Modules. They are therefore 200 mm wider in each
Connection Module are a mirror image (article no. with "C" in the case than version 6SL3730-1T...-.AA3.
next to last position, example: 6SL3730-1T.41-.BC3), which
results in a very compact design for the line infeed.

Expansion Basic

DC busbar

Motor Motor Basic Line Basic Motor Motor Motor

G_D213_EN_00056a
Module Module Line Connection Line Module Module Module
Module Module Module
6SL3730- 6SL3730-
1T...-.BC3 1T...-.BA3

Motor feeder Infeed Motor feeder

Note:
If the Basic Line Modules are supplied with power via the same of 7.5 % applies and this must be taken into account when the
circuit breaker, line-side fuses are provided to ensure selective modules are dimensioned.
individual protection of the modules. This arrangement
increases the cabinet width by 200 mm (dimension data
in selection tables includes extra width).
A connection of the Basic Line Modules connected in parallel
using DRIVE-CLiQ must be taken into consideration. 6
Please note that only Basic Line Modules with exactly the same For additional information, please refer to the SINAMICS Low
output rating may be connected in parallel. The potential for Voltage Engineering Manual.
imbalances in current distribution means that current derating

■ Selection and ordering data


Rated power Rated DC link Note for Basic Line Module Rated power Rated DC link Note for Basic Line Module
at 400 V current a parallel at 690 V current a parallel
connection connection
kW A Mounting Article No. kW A Mounting Article No.
onto a Line onto a Line
Connection Connection
Module Module
Line voltage 380 ... 480 V 3 AC Line voltage 500 ... 690 V 3 AC
(DC link voltage 510 ... 650 V DC) (DC link voltage 675 ... 930 V DC)
200 420 – 6SL3730-1TE34-2AA3 250 300 – 6SL3730-1TG33-0AA3
250 530 – 6SL3730-1TE35-3AA3 355 430 – 6SL3730-1TG34-3AA3
400 820 – 6SL3730-1TE38-2AA3 560 680 – 6SL3730-1TG36-8AA3
560 1200 – 6SL3730-1TE41-2AA3 900 1100 – 6SL3730-1TG41-1AA3
Right 6SL3730-1TE41-2BA3 Right 6SL3730-1TG41-1BA3
Left 6SL3730-1TE41-2BC3 Left 6SL3730-1TG41-1BC3
710 1500 – 6SL3730-1TE41-5AA3 1100 1400 – 6SL3730-1TG41-4AA3
Right 6SL3730-1TE41-5BA3 Right 6SL3730-1TG41-4BA3
Left 6SL3730-1TE41-5BC3 Left 6SL3730-1TG41-4BC3
900 1880 – 6SL3730-1TE41-8AA3 1500 1880 – 6SL3730-1TG41-8AA3
Right 6SL3730-1TE41-8BA3 Right 6SL3730-1TG41-8BA3
Left 6SL3730-1TE41-8BC3 Left 6SL3730-1TG41-8BC3

Siemens D 21.3 · 2022 6/25


© Siemens 2022

SINAMICS S120 Cabinet Modules


Air-cooled units
Basic Line Modules

■ Integration
Cabinet Module

DC busbar

X400 X401 X402

DRIVE-CLiQ socket 1
DRIVE-CLiQ socket 0

DRIVE-CLiQ socket 2
Basic Line
Module
Cabinet Module

-X9
1 P24 V =
Line Connection 2 M
Module 3 =
(Option L43) 4 Internal
power supply
5
Activation of main
6
contactor

-X41
4
~ DCPA
+Temp
= DCNA
3 -Temp
2 DCP
EP +24 V
1 EP M 1 DCN

6 Line reactor
-F10
DC fuses
Option N52
Supply L1 U1 -X1
-F11 Fan
infeed L2 V1
internal
L3 W1
PE
READY
LEDs

DC LINK
-X42 POWER OK
1 P24L
2 P24L
3 M
4 M IPD Card

G_D213_EN_00057d

Connection to next
auxiliary power supply

Connection example of a Basic Line Module (frame size FB and GB)

6/26 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Cabinet Modules


Air-cooled units
Basic Line Modules

■ Integration
Cabinet Module

DC busbar

X400 X401 X402

DRIVE-CLiQ socket 1
DRIVE-CLiQ socket 0

DRIVE-CLiQ socket 2
Basic Line
Module
Cabinet Module
Internal
power supply
Line Connection -X9
Module 1 P24 V =
L1 (Option L43) 2 M
L2 3 =
Supply infeed Activation of
L3 4
PE main contactor
5
Activation of
6
pre-charging contactor
1 AC 230 V

-X41
Fuses
4
~ DCPA
+Temp
= DCNA
3 -Temp
2 DCP
EP +24 V
Circuit breaker 1 DCN
EP M 1

N
-X42
-F10
DC fuses
(Option N52)
6
1 P24L -F11 Fan
Pre-charging 2 P24L internal
contactor 3 M
4 M READY
N
LEDs

Pre-charging DC LINK
resistors POWER OK

Line reactor
U1 -X1 IPD Card
V1
W1
PE PE

Connection to next
auxiliary power supply

G_D213_EN_00152

Connection example: Basic Line Module (Frame size GD)

Siemens D 21.3 · 2022 6/27


© Siemens 2022

SINAMICS S120 Cabinet Modules


Air-cooled units
Basic Line Modules

■ Technical specifications
Line voltage 380 ... 480 V 3 AC Basic Line Modules
6SL3730- 6SL3730- 6SL3730- 6SL3730- 6SL3730- 6SL3730-
1TE34-2AA3 1TE35-3AA3 1TE38-2AA3 1TE41-2AA3 1TE41-5AA3 1TE41-8AA3
For a parallel circuit configuration, 6SL3730- 6SL3730- 6SL3730-
mounted to the right of the Line Connection 1TE41-2BA3 1TE41-5BA3 1TE41-8BA3
Module
For a parallel circuit configuration, 6SL3730- 6SL3730- 6SL3730-
mounted to the left of the Line Connection Module 1TE41-2BC3 1TE41-5BC3 1TE41-8BC3
Rated power
• At IN DC (50 Hz 400 V) kW 200 250 400 560 710 900
• At IH DC (50 Hz 400 V) kW 160 200 315 450 560 705
• At IN DC (60 Hz 460 V) hp 305 385 615 860 1090 1390
• At IH DC (60 Hz 460 V) hp 245 305 485 690 860 1090
DC link current
• Rated current IN DC A 420 530 820 1200 1500 1880
• Base-load current IH DC1) A 328 413 640 936 1170 1467
• Maximum current Imax DC A 630 795 1230 1800 2250 2820
Input current
• Rated current IN I A 365 460 710 1010 1265 1630
• Maximum current Imax I A 547 690 1065 1515 1897 2380
Current demand
• 24 V DC auxiliary power supply A 1.1 1.1 1.1 1.1 1.1 1.1
• 400 V AC 2) A Internal Internal Internal Internal Internal Internal
DC link capacitance
• Basic Line Module F 7200 9600 14600 23200 29000 34800
• Drive line-up, max. F 57600 76800 116800 185600 232000 139200
Power loss, max. 3)
• At 50 Hz 400 V kW 1.9 2.1 3.2 4.6 5.5 6.9
6 • At 60 Hz 460 V kW 1.9 2.1 3.2 4.6 5.5 6.9
Cooling air requirement m3/s (ft3/s) 0.17 (6.00) 0.17 (6.00) 0.17 (6.00) 0.36 (12.7) 0.36 (12.7) 0.36 (12.7)
Sound pressure level LpA dB 66/68 66/68 66/68 71/73 71/73 71/73
(1 m) at 50/60 Hz
PE/GND connection PE bar PE bar PE bar PE bar PE bar PE bar
• Busbar cross-section mm2 600 600 600 600 600 600
• Conductor cross-section, max. (IEC) mm2 240 240 240 240 240 240
Cable length, max. 4)
• Shielded m (ft) 2600 (8530) 2600 (8530) 2600 (8530) 4000 (13123) 4000 (13123) 4800 (15748)
• Unshielded m (ft) 3900 (12795) 3900 (12795) 3900 (12795) 6000 (19685) 6000 (19685) 7200 (23622)
Degree of protection IP20 IP20 IP20 IP20 IP20 IP20
Dimensions
• Width mm (in) 400 (15.7) 400 (15.7) 400 (15.7) 400/600/600 400/600/600 400/600/600
(15.7/23.6/23.6) (15.7/23.6/23.6) (15.7/23.6/23.6)
• Height 5) mm (in) 2200 (86.6) 2200 (86.6) 2200 (86.6) 2200 (86.6) 2200 (86.6) 2200 (86.6)
• Depth mm (in) 600 (23.6) 600 (23.6) 600 (23.6) 600 (23.6) 600 (23.6) 600 (23.6)
Weight, approx. kg (lb) 166 (366) 166 (366) 166 (366) 320/440/480 320/440/480 320/440/480
(705/970/1058) (705/970/1058) (705/970/1058)
Frame size FB FB FB GB GB GD
Rated short-circuit current kA 65 65 65 84 100 100
according to IEC
Minimum short-circuit current 6) kA 4.4 5.2 10 2.5 3.2 4
• For connection in parallel kA – – – 4 5 6.4

1) 4)
The base-load current IH DC is the basis for a duty cycle of 150 % for 60 s Total of all motor cables and DC link. Longer cable lengths for specific
or Imax DC for 5 s with a duty cycle duration of 300 s. configurations are available on request.
2) 5)
The current demand for the 400 V AC auxiliary power supply is drawn from The cabinet height increases by 250 mm (9.84 in) with degree of protection
the line input voltage. IP21, and by 400 mm (15.7 in) with degrees of protection IP23, IP43 or
3)
The specified power loss represents the maximum value at 100 % IP54.
6)
utilization. The value is lower under normal operating conditions. Current required to ensure reliable tripping of installed protective devices.

6/28 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Cabinet Modules


Air-cooled units
Basic Line Modules

■ Technical specifications
Line voltage 500 ... 690 V 3 AC Basic Line Modules
6SL3730- 6SL3730- 6SL3730- 6SL3730- 6SL3730- 6SL3730-
1TG33-0AA3 1TG34-3AA3 1TG36-8AA3 1TG41-1AA3 1TG41-4AA3 1TG41-8AA3
For a parallel circuit configuration, 6SL3730- 6SL3730- 6SL3730-
mounted to the right of the Line Connection 1TG41-1BA3 1TG41-4BA3 1TG41-8BA3
Module
For a parallel circuit configuration, 6SL3730- 6SL3730- 6SL3730-
mounted to the left of the Line Connection Module 1TG41-1BC3 1TG41-4BC3 1TG41-8BC3
Rated power
• At IN DC (50 Hz 690 V) kW 250 355 560 900 1100 1500
• At IH DC (50 Hz 690 V) kW 195 280 440 710 910 1220
• At IN DC (50 Hz 500 V) kW 175 250 390 635 810 1085
• At IH DC (50 Hz 500 V) kW 165 235 365 595 755 1015
• At IN DC (60 Hz 575 V) hp 250 350 600 900 1250 1500
• At IH DC (60 Hz 575 V) hp 200 300 450 800 1000 1250
DC link current
• Rated current IN DC A 300 430 680 1100 1400 1880
• Base-load current IH DC1) A 234 335 530 858 1092 1467
• Maximum current Imax DC A 450 645 1020 1650 2100 2820
Input current
• Rated current IN I A 260 375 575 925 1180 1580
• Maximum current Imax I A 390 563 863 1388 1770 2370
Current demand
• 24 V DC auxiliary power supply A 1.1 1.1 1.1 1.1 1.1 1.1
• 500 V/690 V AC 2) A Internal Internal Internal Internal Internal Internal
DC link capacitance
• Basic Line Module F 3200 4800 7300 11600 15470 19500
• Drive line-up, max. F 25600 38400 58400 92800 123760 78000
Power loss, max. 3)
• At 50 Hz 690 V kW 1.5 2.1 3 5.4 5.8 7.3
6
• At 60 Hz 575 V kW 1.5 2.1 3 5.4 5.8 7.3
Cooling air requirement m3/s (ft3/s) 0.17 (6.00) 0.17 (6.00) 0.17 (6.00) 0.36 (12.7) 0.36 (12.7) 0.36 (12.7)
Sound pressure level LpA dB 66/68 66/68 66/68 71/73 71/73 71/73
(1 m) at 50/60 Hz
PE/GND connection PE bar PE bar PE bar PE bar PE bar PE bar
• Busbar cross-section mm2 600 600 600 600 600 600
• Conductor cross-section, max. (IEC) mm2 240 240 240 240 240 240
Cable length, max. 4)
• Shielded m (ft) 1500 (4921) 1500 (4921) 1500 (4921) 2250 (7382) 2250 (7382) 2750 (9022)
• Unshielded m (ft) 2250 (7382) 2250 (7382) 2250 (7382) 3375 (11073) 3375 (11073) 4125 (13533)
Degree of protection IP20 IP20 IP20 IP20 IP20 IP20
Dimensions
• Width mm (in) 400 (15.7) 400 (15.7) 400 (15.7) 400/600/600 400/600/600 400/600/600
(15.7/23.6/23.6) (15.7/23.6/23.6) (15.7/23.6/23.6)
5)
• Height mm (in) 2200 (86.6) 2200 (86.6) 2200 (86.6) 2200 (86.6) 2200 (86.6) 2200 (86.6)
• Depth mm (in) 600 (23.6) 600 (23.6) 600 (23.6) 600 (23.6) 600 (23.6) 600 (23.6)
Weight, approx. kg (lb) 166 (366) 166 (366) 166 (366) 320/440/480 320/440/480 320/440/480
(705/970/1058) (705/970/1058) (705/970/1058)
Frame size FB FB FB GB GB GD
Rated short-circuit current kA 65 65 65 84 100 100
according to IEC
Minimum short-circuit current 6) kA 3 4.4 8 2 2.5 3.2
• For connection in parallel kA – – – 4 5 6.4

1) The base-load current IH DC is the basis for a duty cycle of 150 % for 60 s 4) Total of all motor cables and DC link. Longer cable lengths for specific
or Imax DC for 5 s with a duty cycle duration of 300 s. configurations are available on request.
2) The current demand for the 500 V/690 V AC auxiliary power supply is 5) The cabinet height increases by 250 mm (9.84 in) with degree of protection
drawn from the line input voltage. IP21, and by 400 mm (15.7 in) with degrees of protection IP23, IP43 or
3) The specified power loss represents the maximum value at 100 % IP54.
utilization. The value is lower under normal operating conditions. 6) Current required to ensure reliable tripping of installed protective devices.

Siemens D 21.3 · 2022 6/29


© Siemens 2022

SINAMICS S120 Cabinet Modules


Air-cooled units
Smart Line Modules

■ Overview
Smart Line Modules are non-regulated infeed/regenerative units.
The infeed occurs over a diode jumper, while stable, line-
commutated regenerative feedback takes place via IGBTs with
100 % continuous energy regeneration. An autotransformer is
not required for regenerative feedback.
The regenerative capability can be deactivated.
Smart Line Modules are suitable for connection to grounded
TN/TT and non-grounded IT systems. The following voltages and
power ratings are available:
Line voltage Rated power
380 ... 480 V 3 AC 250 ... 800 kW
500 ... 690 V 3 AC 450 ... 1400 kW

The power ratings can be increased by connecting up to four


identical Smart Line Modules in parallel.
For additional information, please refer to the SINAMICS Low
Voltage Engineering Manual.

■ Design
IGBTs (fundamental frequency-switched) serve as Smart Line Parallel connection of Smart Line Modules to increase
Module power semiconductors. Because this reduces switching power rating
losses, a high percentage of the power unit current can
be utilized. Up to four Smart Line Modules with the same power rating can
be connected in parallel in order to increase power. Current
The current flows in the direction of the infeed via the derating of 7.5 % with respect to the rated current of each Smart
freewheeling diodes of the IGBTs. This means that the Smart Line Module must be taken into account when the system
Line Module behaves in a similar way to the Basic Line Module. is dimensioned.
If the DC link voltage increases due to regenerative operation of
6 the drives, the IGBTs conduct the current, thus feeding the
energy back into the supply system.
A connection of the Smart Line Modules connected in parallel
using DRIVE-CLiQ must be taken into consideration during the
engineering phase.
In contrast to Active Line Modules, Smart Line Modules do not
require a line-side filter; all they require is a line reactor (4 % uk). For additional information, please refer to the SINAMICS Low
The unit has a built-in pre-charging circuit for the DC link Voltage Engineering Manual.
capacitors. For this reason, a main contactor or a motor-driven A 4 % reactor is always required upstream of each Smart Line
circuit breaker is absolutely essential. By specifying the option Module for the purpose of current symmetrization. This is
with order code L44 for the Line Connection Modules, these integrated as standard. Just as with the Basic Line Modules,
components are appropriately accommodated in the Line "mirror-image" power connections are available for Smart Line
Connection Module. Modules, which enable parallel circuits to be realized in
a compact design. Units that are arranged to the left of the Line
Connection Module have the letter "C" at the penultimate position
of the article number.
Example: 6SL3730-6TE41-1BC3 (see also the corresponding
diagram for the Basic Line Modules).

■ Selection and ordering data


Rated power Rated infeed/ Note for Smart Line Module Rated power Rated infeed/ Note for Smart Line Module
at 400 V or regenerative a parallel at 400 V or regenerative a parallel
690 V feedback connection 690 V feedback connection
current current
kW A Mounting Article No. kW A Mounting Article No.
onto a Line onto a Line
Connection Connection
Module Module
Line voltage 380 ... 480 V 3 AC Line voltage 500 ... 690 V 3 AC
(DC link voltage 510 ... 650 V DC) (DC link voltage 675 ... 930 V DC)
250 463 – 6SL3730-6TE35-5AA3 450 463 – 6SL3730-6TG35-5AA3
355 614 – 6SL3730-6TE37-3AA3 710 757 – 6SL3730-6TG38-8AA3
500 883 – 6SL3730-6TE41-1AA3 Right 6SL3730-6TG38-8BA3
Right 6SL3730-6TE41-1BA3 Left 6SL3730-6TG38-8BC3
Left 6SL3730-6TE41-1BC3 1000 1009 – 6SL3730-6TG41-2AA3
630 1093 – 6SL3730-6TE41-3AA3 Right 6SL3730-6TG41-2BA3
Right 6SL3730-6TE41-3BA3 Left 6SL3730-6TG41-2BC3
Left 6SL3730-6TE41-3BC3 1400 1430 – 6SL3730-6TG41-7AA3
800 1430 – 6SL3730-6TE41-7AA3 Right 6SL3730-6TG41-7BA3
Right 6SL3730-6TE41-7BA3 Left 6SL3730-6TG41-7BC3
Left 6SL3730-6TE41-7BC3

6/30 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Cabinet Modules


Air-cooled units
Smart Line Modules

■ Integration
Cabinet Module

DC busbar

X400 X401 X402 X500

DRIVE-CLiQ socket 1
DRIVE-CLiQ socket 0

DRIVE-CLiQ socket 2

DRIVE-CLiQ socket
-X41 Smart LED
4 +Temp READY
3 -Temp
Line
2 EP +24 V Module
Cabinet Module 1 EP M1
Voltage
Sensing Module
Line Connection -X9 VSM10
Module 1 P24 V =
(Option L44) 2 M
=
3 Activation of
230 V AC
4 bypass contactor Internal
5 power supply
6
7
Feedback READY

LEDs
8 pre-charging
DC LINK
L1
POWER OK
L2
L3
-F10
6
-F11 Fan Connection
-X42
1 -F20 for Braking
P24L
2 Module
P24L
3 M DCPA
4 -F21 DCNA
M
Line
reactor
L1 U1 Fan1)
Supply ~ DCP
infeed L2 V1
DCN
L3 W1
=
PE

IPD Card
1 2 3 4 5 6
-X100

Auxiliary power supply:


-F24

380 - 480 V 2 AC
or 500 - 690 V 2 AC

230 V AC
G_D213_EN_00058c

24 V DC

1) The number of fans depends on the frame size.

Connection example of a Smart Line Module

Siemens D 21.3 · 2022 6/31


© Siemens 2022

SINAMICS S120 Cabinet Modules


Air-cooled units
Smart Line Modules

■ Technical specifications
Line voltage 380 ... 480 V 3 AC Smart Line Modules
6SL3730- 6SL3730- 6SL3730- 6SL3730- 6SL3730-
6TE35-5AA3 6TE37-3AA3 6TE41-1AA3 6TE41-3AA3 6TE41-7AA3
For a parallel circuit configuration, 6SL3730- 6SL3730- 6SL3730-
mounted to the right of the Line Connection 6TE41-1BA3 6TE41-3BA3 6TE41-7BA3
Module
For a parallel circuit configuration, 6SL3730- 6SL3730- 6SL3730-
mounted to the left of the Line Connection Module 6TE41-1BC3 6TE41-3BC3 6TE41-7BC3
Rated power
• At IN DC (50 Hz 400 V) kW 250 355 500 630 800
• At IH DC (50 Hz 400 V) kW 235 315 450 555 730
• At IN DC (60 Hz 460 V) hp 395 545 770 970 1230
• At IH DC (60 Hz 460 V) hp 360 485 695 855 1125
DC link current
• Rated current IN DC A 550 730 1050 1300 1700
• Base-load current IH DC 1) A 490 650 934 1157 1513
• Maximum current Imax DC A 825 1095 1575 1950 2550
Infeed/regenerative feedback
current
• Rated current IN I A 463 614 883 1093 1430
• Maximum current Imax I A 694 921 1324 1639 2145
Current demand
• 24 V DC auxiliary power supply A 1.35 1.35 1.4 1.5 1.7
• 400 V AC 2) A 1.8 1.8 3.6 5.4 5.4
DC link capacitance
• Smart Line Module F 8400 12000 16800 18900 28800
• Drive line-up, max. F 42000 60000 67200 75600 115200
Power loss, max. 3)
6 • At 50 Hz 400 V
• At 60 Hz 460 V
kW
kW
3.7
3.7
4.7
4.7
7.1
7.1
11.0
11.0
11.5
11.5
Cooling air requirement m3/s (ft3/s) 0.36 (12.71) 0.36 (12.71) 0.78 (27.55) 1.08 (38.14) 1.08 (38.14)
Sound pressure level LpA dB 69/73 69/73 70/73 70/73 70/73
(1 m) at 50/60 Hz
PE/GND connection PE bar PE bar PE bar PE bar PE bar
• Busbar cross-section mm2 600 600 600 600 600
• Conductor cross-section, max. (IEC) mm2 240 240 240 240 240
Cable length, max. 4)
• Shielded m (ft) 4000 (13124) 4000 (13124) 4800 (15749) 4800 (15749) 4800 (15749)
• Unshielded m (ft) 6000 (19686) 6000 (19686) 7200 (23623) 7200 (23623) 7200 (23623)
Degree of protection IP20 IP20 IP20 IP20 IP20
Dimensions
• Width mm (in) 400 (15.75) 400 (15.75) 600 (23.62) 800 (31.50) 800 (31.50)
• Height 5) mm (in) 2200 (86.61) 2200 (86.61) 2200 (86.61) 2200 (86.61) 2200 (86.61)
• Depth mm (in) 600 (23.62) 600 (23.62) 600 (23.62) 600 (23.62) 600 (23.62)
Weight, approx. kg (lb) 270 (595) 270 (595) 490 (1080) 775 (1709) 775 (1709)
Frame size GX GX HX JX JX
Rated short-circuit current kA 65 65 84 84 100
according to IEC
Minimum short-circuit current 6) kA 6.2 9.2 2 2.5 3.2

1) 4)
The base-load current IH DC is the basis for a duty cycle of 150 % for Total of all motor cables and DC link. Longer cable lengths for specific
60 s or Imax DC for 5 s with a duty cycle duration of 300 s. configurations are available on request.
2) 5)
The current demand for the 400 V AC auxiliary power supply The cabinet height increases by 250 mm (9.84 in) with degree of protection
is drawn from the line input voltage. IP21, and by 400 mm (15.7 in) with degrees of protection IP23,
3)
The specified power loss represents the maximum value at 100 % IP43 or IP54.
6)
utilization. The value is lower under normal operating conditions. Current required to ensure reliable tripping of installed protective devices.

6/32 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Cabinet Modules


Air-cooled units
Smart Line Modules

■ Technical specifications
Line voltage 500 ... 690 V 3 AC Smart Line Modules
6SL3730-6TG35-5AA3 6SL3730-6TG38-8AA3 6SL3730-6TG41-2AA3 6SL3730-6TG41-7AA3
For a parallel circuit configuration, 6SL3730-6TG38-8BA3 6SL3730-6TG41-2BA3 6SL3730-6TG41-7BA3
mounted to the right of the Line Connection
Module
For a parallel circuit configuration, 6SL3730-6TG38-8BC3 6SL3730-6TG41-2BC3 6SL3730-6TG41-7BC3
mounted to the left of the Line Connection Module
Rated power
• At IN DC (50 Hz 690 V) kW 450 710 1000 1400
• At IH DC (50 Hz 690 V) kW 405 665 885 1255
• At IN DC (50 Hz 500 V) kW 320 525 705 995
• At IH DC (50 Hz 500 V) kW 295 480 640 910
• At IN DC (60 Hz 575 V) hp 500 790 1115 1465
• At IH DC (60 Hz 575 V) hp 450 740 990 1400
DC link current
• Rated current IN DC A 550 900 1200 1700
• Base-load current IH DC 1) A 490 800 1068 1513
• Maximum current Imax DC A 825 1350 1800 2550
Infeed/regenerative feedback
current
• Rated current IN I A 463 757 1009 1430
• Maximum current Imax I A 694 1135 1513 2145
Current demand
• 24 V DC auxiliary power supply A 1.35 1.4 1.5 1.7
• 500 V AC 2) A 1.3 2.9 4.3 4.3
• 690 V AC A 1 2.1 3.1 3.1
DC link capacitance
• Smart Line Module F 5600 7400 11100 14400
• Drive line-up, max.
Power loss, max. 3)
F 28000 29600 44400 57600
6
• At 50 Hz 690 V kW 4.3 6.5 12.0 13.8
• At 60 Hz 575 V kW 4.3 6.5 12.0 13.8
Cooling air requirement m3/s (ft3/s) 0.36 (12.71) 0.78 (27.55) 1.08 (38.14) 1.08 (38.14)
Sound pressure level LpA dB 69/73 70/73 70/73 70/73
(1 m) at 50/60 Hz
PE/GND connection PE bar PE bar PE bar PE bar
• Busbar cross-section mm2 600 600 600 600
• Conductor cross-section, max. (IEC) mm2 240 240 240 240
Cable length, max. 4)
• Shielded m (ft) 2250 (7382) 2750 (9023) 2750 (9023) 2750 (9023)
• Unshielded m (ft) 3375 (11073) 4125 (13534) 4125 (13534) 4125 (13534)
Degree of protection IP20 IP20 IP20 IP20
Dimensions
• Width mm (in) 400 (15.75) 600 (23.62) 800 (31.50) 800 (31.50)
• Height 5) mm (in) 2200 (86.61) 2200 (86.61) 2200 (86.61) 2200 (86.61)
• Depth mm (in) 600 (23.62) 600 (23.62) 600 (23.62) 600 (23.62)
Weight, approx. kg (lb) 270 (595) 550 (1213) 795 (1753) 795 (1753)
Frame size GX HX JX JX
Rated short-circuit current kA 65 84 100 100
according to IEC
Minimum short-circuit current 6) kA 6.2 10.5 2.5 3.2

1) 4)
The base-load current IH DC is the basis for a duty cycle of 150 % Total of all motor cables and DC link. Longer cable lengths for specific
for 60 s or Imax DC for 5 s with a duty cycle duration of 300 s. configurations are available on request.
2) 5)
The current demand for the 500 V / 690 V AC auxiliary power supply The cabinet height increases by 250 mm (9.84 in) with degree of protection
is drawn from the line input voltage. IP21, and by 400 mm (15.7 in) with degrees of protection IP23,
3)
The specified power loss represents the maximum value at 100 % IP43 or IP54.
6)
utilization. The value is lower under normal operating conditions. Current required to ensure reliable tripping of installed protective devices.

Siemens D 21.3 · 2022 6/33


© Siemens 2022

SINAMICS S120 Cabinet Modules


Air-cooled units
Active Line Modules incl. Active Interface Modules

■ Overview
Active Line Modules are regulated infeed/regenerative units.
They can supply energy to the DC link and return regenerative
energy to the supply system.
In contrast to Basic Line Modules and Smart Line Modules,
Active Line Modules generate a stabilized DC voltage that is
kept constant despite fluctuations in the line voltage (the line
voltage must remain within the permissible tolerance range).
Active Line Modules in combination with an Active Interface
Module draw a virtually sinusoidal current from the supply
system. Almost no harmonics occur.
A Braking Module and braking resistor are required only if the
drives need to be decelerated in a controlled manner after
a power failure (i.e. when energy cannot be recovered to
the supply).
Active Line Modules are suitable for connection to grounded
TN/TT and non-grounded IT systems. The following voltages and
power ratings are available:
Line voltage Rated power
380 ... 480 V 3 AC 132 ... 900 kW
500 ... 690 V 3 AC 630 ... 1400 kW

■ Design
Active Line Modules are always operated together with an Active The power connections on the Active Line Module on the left of
Interface Module that contains the associated Clean Power Filter the Line Connection Module are a mirror image (article no. with
and pre-charging circuit. The integrated line filter ensures "C" in the next to last position, example: 6SL3730-7T.41.-.BC3),
compliance with the EMC requirements for the "second which results in a very compact design for the line infeed.
6 environment".
Please note that only Active Line Modules with exactly the same
The Active Line Module and Active Interface Module are power rating may be connected in parallel. The potential for
supplied as a complete, fully wired unit, i.e. the customer does imbalances in current distribution means that a current derating
not need to supply any further cables or carry out any other of 5 % applies; this must be taken into account when the
wiring tasks. modules are dimensioned.
Parallel connection of Active Line Modules to increase A connection of the Active Line Modules connected in parallel
power rating using DRIVE-CLiQ must be taken into consideration during the
engineering phase.
Active Line Modules are available for creating drive line-ups with
more power. These modules can be operated in parallel on For additional information, please refer to the SINAMICS Low
a common Line Connection Module and are arranged to the Voltage Engineering Manual.
right and left of the Line Connection Module.

Expansion Basic

DC busbar

Motor Motor Active Active Line Active Active Motor Motor Motor
G_D213_EN_00059a

Module Module Line Interface Connection Interface Line Module Module Module
Module Module Module Module Module

6SL3730-7T...-.BC3 6SL3730-7T...-.BA3

Motor feeder Infeed Motor feeder

6/34 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Cabinet Modules


Air-cooled units
Active Line Modules incl. Active Interface Modules

■ Selection and ordering data


Rated power Rated infeed/ Note for Active Line Module Rated power Rated infeed/ Note for Active Line Module
at 400 V regenerative a parallel (incl. Active Interface at 690 V regenerative a parallel (incl. Active Interface
feedback connection Module) feedback connection Module)
current current
kW A Mounting Article No. kW A Mounting Article No.
onto a Line onto a Line
Connection Connection
Module Module
Line voltage 380 ... 480 V 3 AC Line voltage 500 ... 690 V 3 AC
(DC link voltage 570 ... 720 V DC) (DC link voltage 750 ... 1035 V DC)
132 210 – 6SL3730-7TE32-1BA3 630 575 – 6SL3730-7TG35-8BA3
160 260 – 6SL3730-7TE32-6BA3 800 735 – 6SL3730-7TG37-4BA3
235 380 – 6SL3730-7TE33-8BA3 Left 6SL3730-7TG37-4BC3
300 490 – 6SL3730-7TE35-0BA3 1100 1025 – 6SL3730-7TG41-0BA3
380 605 – 6SL3730-7TE36-1BA3 Left 6SL3730-7TG41-0BC3
500 840 – 6SL3730-7TE38-4BA3 1400 1270 – 6SL3730-7TG41-3BA3
630 985 – 6SL3730-7TE41-0BA3 Left 6SL3730-7TG41-3BC3
Left 6SL3730-7TE41-0BC3
900 1405 – 6SL3730-7TE41-4BA3
Left 6SL3730-7TE41-4BC3

Siemens D 21.3 · 2022 6/35


© Siemens 2022

SINAMICS S120 Cabinet Modules


Air-cooled units
Active Line Modules incl. Active Interface Modules

■ Integration
The Active Line Module is controlled by the CU320-2 Control
Unit. Communication between the Control Unit and module is
established via DRIVE-CLiQ connections. The Active Interface
Module is included in the scope of supply for the Active Line
Module.

Cabinet Module Cabinet Module

DC busbar

X500 3 X400 X401 X402 3

DRIVE-CLiQ socket 1

DRIVE-CLiQ socket 2
DRIVE-CLiQ socket 0
Active Active

DRIVE-CLiQ socket
Interface LED Line
READY
Module Module
-X609
Voltage
PE
Sensing -X41
1 P24 Module VSM10
4 2 4 +Temp
P24 READY
3

LEDs
Cabinet Module 3 -Temp
M 2 DC LINK
4 EP + 24 V
M -Q101 POWER OK
1 EP M1
L 5
6 Internal
230 V AC I>
N7 -X9 power supply
8 1 P24 V
Fan 4 =
1 9 2 M
6 Line
Connection
2
10
11
Pre-charging contactor
2
3
4
Activation of
=

Module bypass contactor


12 Bypass 5
(Option L42) contactor 1 Activation of
13 6 Connection
pre-charging
14 Contactors for Braking
contactor
Supply open Module
infeed DCPA
DCNA
-X1 -X2 -X1
L1 U1 U2 U1 DCP
~
L2 V1 V2 V1
DCN
L3 W1 ≈ W2 W1
=
PE PE PE

-F10

1 -F11 Fan
2 Connection between Active Interface Module and -X42
3 Active Line Module pre-assembled at the factory 1 P24L
4 2 P24L
3 IPD Card
M
4 M
1 2 3 4 5 6
-X100

Auxiliary power supply:


-F24

380 - 480 V 2 AC
or 500 - 690 V 2 AC

230 V AC

24 V DC

G_D213_EN_00060d

Connection example of an Active Line Module (frame size FI/FX and GI/GX)

6/36 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Cabinet Modules


Air-cooled units
Active Line Modules incl. Active Interface Modules

■ Integration
Cabinet Module Cabinet Module

DC busbar

X500 3 X400 X401 X402 3

DRIVE-CLiQ socket 1

DRIVE-CLiQ socket 2
DRIVE-CLiQ socket 0
Active Active

DRIVE-CLiQ socket
Interface LED Line
READY
Module Module
-X609 -X41
PE 4 +Temp
1 Voltage
P24 3 -Temp
4 2 Sensing
P24 2 EP +24 V
Module VSM10 READY
Cabinet Module 3 M 1 EP M1

LEDs
4 M DC LINK
-Q101
L 5 Internal POWER OK
6 -X9 power supply
230 V AC
N7 I> 1 P24 V
8 4 =
Fan 2 M =
1 9 3
2 Activation of
10 4
Pre-charging bypass contactor
2 11 5
contactor 1 Activation of
Bypass 12 6
contactor 13 pre-charging
14 Contactors contactor Connection for
Braking Module
open
T1 DCPA
Supply
infeed T2 DCNA

L1
T3
L1 -X1
-X2
U2 U1 -X1 DCP
6
~
L2 L2 V2 V1
DCN
L3 L3 ≈ W2 W1
=
PE PE PE
-X9
L1 -F10
Line Connection L2
Module
(Option L42) -F11 Fan
-F20

-F21 Fan 1)
internal
1 -X42
2 Connection between Active Interface Module and Active 1 P24L
3 Line Module pre-assembled at the factory 2 P24L
3 M IPD Card
4
1 2 3 4 5 6 4 M
-X100

Auxiliary power supply:


-F24

380 - 480 V 2 AC
or 500 - 690 V 2 AC

230 V AC

24 V DC

G_D213_EN_00061e

1) The number of fans depends on the frame size.

Connection example of an Active Line Module (frame size HI/HX and JI/JX)

Siemens D 21.3 · 2022 6/37


© Siemens 2022

SINAMICS S120 Cabinet Modules


Air-cooled units
Active Line Modules incl. Active Interface Modules

■ Technical specifications
Line voltage 380 ... 480 V 3 AC Active Line Modules
6SL3730- 6SL3730- 6SL3730- 6SL3730- 6SL3730- 6SL3730- 6SL3730- 6SL3730-
7TE32-1BA3 7TE32-6BA3 7TE33-8BA3 7TE35-0BA3 7TE36-1BA3 7TE38-4BA3 7TE41-0BA3 7TE41-4BA3
For a parallel circuit configuration, 6SL3730- 6SL3730-
mounted to the left of the Line Connection 7TE41-0BC3 7TE41-4BC3
Module
Rated power
• At IN DC (50 Hz 400 V) kW 132 160 235 300 380 500 630 900
• At IH DC (50 Hz 400 V) kW 115 145 210 270 335 465 545 780
• At IN DC (60 Hz 460 V) hp 200 250 400 500 600 700 900 1250
• At IH DC (60 Hz 460 V) hp 150 200 300 400 500 700 800 1000
DC link current
• Rated current IN DC A 235 291 425 549 678 940 1103 1574
• Base-load current IH DC1) A 209 259 378 489 603 837 982 1404
• Maximum current Imax DC A 352 436 637 823 1017 1410 1654 2361
Infeed/regenerative feedback
current
• Rated current IN I A 210 260 380 490 605 840 985 1405
• Maximum current Imax I A 315 390 570 735 907 1260 1477 2107
Current demand
• 24 V DC auxiliary power supply A 1.27 1.27 1.52 1.52 1.57 1.57 1.67 1.67
• 230 V AC auxiliary power supply A 0.6 0.6 1.2 1.2 4.6 4.6 4.9 4.9
• 400 V AC 2) A 0.63 1.13 1.8 1.8 3.6 3.6 5.4 5.4
DC link capacitance
• Active Line Module F 4200 5200 7800 9600 12600 16800 18900 28800
• Drive line-up, max. F 41600 41600 76800 76800 134400 134400 230400 230400
Power loss, max. 3)
• At 50 Hz 400 V kW 4.3 4.9 6.9 8.7 11.7 13.8 17.6 21.8
6 • At 60 Hz 460 V
Cooling air requirement
kW
m3/s
4.4
0.47 (16.6)
5.1
0.47 (16.6)
7.2 9.0 12.1 14.3 18.3
0.83 (29.31) 0.83 (29.31) 1.18 (41.67) 1.18 (41.67) 1.48 (52.27) 1.48 (52.27)
22.7

(ft3/s)
Sound pressure level LpA 4) dB 71/73 71/73 72/74 72/74 77/79 77/79 78/80 78/80
(1 m) at 50/60 Hz
PE/GND connection PE bar PE bar PE bar PE bar PE bar PE bar PE bar PE bar
• Busbar cross-section mm2 600 600 600 600 600 600 600 600
• Conductor cross-section, max. mm2 240 240 240 240 240 240 240 240
(IEC)
Cable length, max. 5)
• Shielded m (ft) 2700 (8859) 2700 (8859) 2700 (8859) 2700 (8859) 3900 3900 3900 3900
(12796) (12796) (12796) (12796)
• Unshielded m (ft) 4050 4050 4050 4050 5850 5850 5850 5850
(13288) (13288) (13288) (13288) (19194) (19194) (19194) (19194)
Degree of protection IP20 IP20 IP20 IP20 IP20 IP20 IP20 IP20
Dimensions
• Width mm (in) 800 (31.50) 800 (31.50) 800 (31.50) 800 (31.50) 1000 (39.37) 1000 (39.37) 1400 (55.12) 1400 (55.12)
• Height 6) mm (in) 2200 (86.61) 2200 (86.61) 2200 (86.61) 2200 (86.61) 2200 (86.61) 2200 (86.61) 2200 (86.61) 2200 (86.61)
• Depth mm (in) 600 (23.62) 600 (23.62) 600 (23.62) 600 (23.62) 600 (23.62) 600 (23.62) 600 (23.62) 600 (23.62)
Weight, approx. kg (lb) 380 (838) 380 (838) 530 (1169) 530 (1169) 930 (2051) 930 (2051) 1360 (2999) 1360 (2999)
Frame size FX + FI FX + FI GX + GI GX + GI HX + HI HX + HI JX + JI JX + JI
Rated short-circuit current kA 65 65 65 65 65 84 84 100
according to IEC
Minimum short-circuit current 7) kA 6.2 10.5 10.5 10.5 12 2 4 6.4

1) 5)
The base-load current IH DC is the basis for a duty cycle of 150 % for Total of all motor cables and DC link. Longer cable lengths for specific
60 s or Imax DC for 5 s with a duty cycle duration of 300 s. configurations are available on request.
2) 6)
The current demand for the 400 V AC auxiliary power supply is drawn from The cabinet height increases by 250 mm (9.84 in) with degree of protection
the line input voltage. IP21, and by 400 mm (15.7 in) with degrees of protection IP23,
3)
The specified power loss represents the maximum value at 100 % IP43 or IP54.
7)
utilization. The value is lower under normal operating conditions. Current required to ensure reliable tripping of installed protective devices.
4)
Total sound pressure level of Active Interface Module and Active Line
Module.

6/38 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Cabinet Modules


Air-cooled units
Active Line Modules incl. Active Interface Modules

■ Technical specifications
Line voltage 500 ... 690 V 3 AC Active Line Modules
6SL3730-7TG35-8BA3 6SL3730-7TG37-4BA3 6SL3730-7TG41-0BA3 6SL3730-7TG41-3BA3
For a parallel circuit configuration, 6SL3730-7TG37-4BC3 6SL3730-7TG41-0BC3 6SL3730-7TG41-3BC3
mounted to the left of the Line Connection
Module
Rated power
• At IN DC (50 Hz 690 V) kW 630 800 1100 1400
• At IH DC (50 Hz 690 V) kW 620 705 980 1215
• At IN DC (50 Hz 500 V) kW 447 560 780 965
• At IH DC (50 Hz 500 V) kW 450 510 710 880
• At IN DC (60 Hz 575 V) hp 675 900 1250 1500
• At IH DC (60 Hz 575 V) hp 506 600 1000 1250
DC link current
• Rated current IN DC A 644 823 1148 1422
• Base-load current IH DC1) A 573 732 1022 1266
• Maximum current Imax DC A 966 1234 1722 2133
Infeed/regenerative feedback
current
• Rated current IN I A 575 735 1025 1270
• Maximum current Imax I A 862 1102 1537 1905
Current demand 2)
• 24 V DC auxiliary power supply A 1.57 1.67 1.87 1.87
• 230 V AC auxiliary power supply A 4.6 4.9 4.9 4.9
• 500 V AC A 3.0 4.4 4.4 4.4
• 690 V AC A 2.1 3.1 3.1 3.1
DC link capacitance
• Active Line Module F 7400 11100 14400 19200
• Drive line-up, max. F 59200 153600 153600 153600
Power loss, max. 3)
• At 50 Hz 500/690 V kW 13.6 19.2 22.8 26.1
6
• At 60 Hz 575 V kW 13.0 18.6 22.1 24.9
Cooling air requirement m3/s 1.18 (41.67) 1.48 (52.27) 1.48 (52.27) 1.48 (52.27)
(ft3/s)
Sound pressure level LpA 4) dB 77/79 77/79 77/79 77/79
(1 m) at 50/60 Hz
PE/GND connection PE bar PE bar PE bar PE bar
• Busbar cross-section mm2 600 600 600 600
• Conductor cross-section, max. mm2 240 240 240 240
(IEC)
Cable length, max. 5)
• Shielded m (ft) 2250 (7382) 2250 (7382) 2250 (7382) 2250 (7382)
• Unshielded m (ft) 3375 (11073) 3375 (11073) 3375 (11073) 3375 (11073)
Degree of protection IP20 IP20 IP20 IP20
Dimensions
• Width mm (in) 1000 (39.37) 1400 (55.12) 1400 (55.12) 1400 (55.12)
• Height 6) mm (in) 2200 (86.61) 2200 (86.61) 2200 (86.61) 2200 (86.61)
• Depth mm (in) 600 (23.62) 600 (23.62) 600 (23.62) 600 (23.62)
Weight, approx. kg (lb) 930 (2051) 1360 (2999) 1360 (2999) 1360 (2999)
Frame size HX + HI JX + JI JX + JI JX + JI
Rated short-circuit current kA 65 84 100 100
according to IEC
Minimum short-circuit current 7) kA 9 10.5 2.5 3.2
• For connection in parallel kA – 4 4 5

1) 5)
The base-load current IH DC is the basis for a duty cycle of 150 % for Total of all motor cables and DC link. Longer cable lengths for specific
60 s or Imax DC for 5 s with a duty cycle duration of 300 s. configurations are available on request.
2) 6)
The current demand for the 500 V/690 V AC auxiliary power supply is The cabinet height increases by 250 mm (9.84 in) with degree of protection
drawn from the line input voltage. IP21, and by 400 mm (15.7 in) with degrees of protection IP23,
3)
The specified power loss represents the maximum value at 100 % IP43 or IP54.
7)
utilization. The value is lower under normal operating conditions. Current required to ensure reliable tripping of installed protective devices.
4)
Total sound pressure level of Active Interface Module and Active Line
Module.

Siemens D 21.3 · 2022 6/39


© Siemens 2022

SINAMICS S120 Cabinet Modules


Air-cooled units
Motor Modules in booksize format

■ Overview ■ Selection and ordering data


Type rating Rated output Width Single Motor Module
at 400 V current IN Booksize Cabinet Kit
kW A mm (in) Article No.
Line voltage 380 ... 480 V 3 AC
(DC link voltage 510 ... 720 V DC)
4.8 9 100 (3.94) 6SL3720-1TE21-0AB4
9.7 18 100 (3.94) 6SL3720-1TE21-8AB4
16 30 100 (3.94) 6SL3720-1TE23-0AB4
24 45 200 (7.87) 6SL3720-1TE24-5AB4
32 60 200 (7.87) 6SL3720-1TE26-0AB4
46 85 200 (7.87) 6SL3720-1TE28-5AB3
71 132 300 (11.8) 6SL3720-1TE31-3AB3

Booksize Cabinet Kits must always be ordered in combination


with at least one Booksize Base Cabinet (cannot be supplied as
a single unit).
Motor Modules Booksize format are also available as Booksize The required number of Booksize Cabinet Kits installed in
Cabinet Kits in voltage class 380 V to 480 V (DC link voltage a Booksize Base Cabinet must be stated in plain text in the order.
510 V to 720 V). The number of possible kits is limited only by the usable
installation width of the Booksize Base Cabinet.
Motor Modules are also available as Single Motor Modules for
power ratings of 4.8 kW to 71 kW for connection of a motor. Booksize Base Cabinets ready to be installed in the Booksize
Cabinet Kits:
■ Design Usable Weight, Dimensions Booksize Base Cabinet
installation approx. with degree of
Motor Modules Booksize format are installed in the factory as width protection IP20 1)
Booksize Cabinet Kits in Booksize Base Cabinets. This complete (W × D × H)
unit contains all of the components necessary for operation.
6 Several Booksize Cabinet Kits can be installed in one Booksize
mm (in)
600 (23.6)
kg (lb) mm (in)
170 (375) 800 × 600 × 2200
Article No.
6SL3720-1TX38-0AA3
Base Cabinet, depending on the installation width requirements, (31.5 × 23.6 × 86.6)
which in turn depend on the power rating. The number of 1000 (39.4) 240 (529) 1200 × 600 × 2200 6SL3720-1TX41-2AA3
Booksize Cabinet Kits that can be installed in a Booksize Base (47.2 × 23.6 × 86.6)
Cabinet is determined solely on the basis of the available
cabinet width. By changing the way in which the cabinet width is
used (i.e. the equipment that is installed), it can be adapted to
suit system requirements.
Each Motor Module is connected separately to the DC busbar of
the SINAMICS S120 Cabinet Module via a separate fuse switch
disconnector with integrated fuses. The DC connecting busbar
integrated in the units is not used.
The basic version of the Booksize Cabinet Kit comprises the
following components:
• Motor Module in booksize format
• Fuse switch disconnector for each Motor Module installed
• Customer interface -X55.1 located in the connection area of
the Booksize Base Cabinet
• Shield connection plate
• Complete electrical connection to the Booksize Base Cabinet
interfaces
The Booksize Base Cabinets can be operated up to and
including IP54 degree of protection without additional
temperature derating. However, some values need to be taken
into account that differ from those of the chassis format.
For derating data, see Air-cooled units > Characteristic curves.

1) The cabinet height increases by 250 mm (9.84 in) with degree of protection
IP21, and by 400 mm (15.7 in) with degrees of protection IP23, IP43 and
IP54.

6/40 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Cabinet Modules


Air-cooled units
Motor Modules in booksize format

■ Integration
Cabinet Module (Booksize Base Cabinet)

DC busbar

X200 X201 X202

DCP

DRIVE-CLiQ socket 1
DRIVE-CLiQ socket 0

DRIVE-CLiQ socket 2
DCN

+
~
M 24 V DC
=

Customer
Internal
terminal
power supply

LEDs
strip READY
DC LINK
-X55.1 -X21
1 1 +Temp
1) 2 2 -X1
-Temp U2
3 3 EP +24 V = V2 M
2) 4 4 EP M1 ~ W2 3~
PE
Booksize Cabinet Kit
-X12
Single Motor Module
Fan
1
2 3)
6
1 2 3 4 5 6
-X100

Auxiliary power
supply:
-F24

380 to 480 V 2 AC
and 500 to 690 V 2 AC
230 V AC
G_D213_EN_00097a

24 V DC

1) Connection of a temperature sensor for motors without a DRIVE-CLiQ interface.


2) Required for Safety Integrated.
3) Fan insert with 132 A rated output current.

Connection example of a Booksize Cabinet Kit (Single Motor Module in booksize format) in Booksize Base Cabinet

Siemens D 21.3 · 2022 6/41


© Siemens 2022

SINAMICS S120 Cabinet Modules


Air-cooled units
Motor Modules in booksize format

■ Technical specifications
Line voltage 380 ... 480 V 3 AC Single Motor Modules Booksize Cabinet Kit
DC link voltage 510 ... 720 V DC
6SL3720-1TE21-0AB4 6SL3720-1TE21-8AB4 6SL3720-1TE23-0AB4 6SL3720-1TE24-5AB4
Type rating
• At IL (50 Hz 400 V) 1) kW 4.8 9.7 16 24
• At IH (50 Hz 400 V) 1) kW 4.1 8.2 13.7 21
• At IL (60 Hz 460 V) 2) hp 5 10 20 30
• At IH (60 Hz 460 V) 2) hp 5 10 15 25
Output current
• Rated current IN O A 9 18 30 45
• Base-load current IH 3) A 7.7 15.3 25.5 38
• Maximum current Imax O A 27 54 90 90
DC link current Id4) A 11 22 36 54
Current demand
• 24 V DC, max. A 0.75 0.75 0.8 0.9
DC link capacitance F 110 220 705 1230
Pulse frequency 5)
• Rated frequency kHz 4 4 4 4
• Pulse frequency, max.
- With current derating kHz 16 16 16 16
Power loss, max. 6)
• At 50 Hz 400 V kW 0.08 0.165 0.29 0.36
• At 60 Hz 460 V kW 0.08 0.165 0.29 0.36
Cooling air requirement m3/s (ft3/s) 0.009 (0.32) 0.009 (0.32) 0.016 (0.57) 0.023 (0.81)
Sound pressure level LpA dB <60 <60 <60 <65
(1 m) at 50/60 Hz

6 Motor connection
U2, V2, W2
Terminal Terminal Terminal Terminal

• Conductor cross-section, max. (IEC) mm2 6 6 6 16


Cable length, max. 7)
• Shielded m (ft) 50 (164) 70 (230) 100 (328) 100 (328)
• Unshielded m (ft) 75 (246) 100 (328) 150 (492) 150 (492)
PE/GND connection PE bar PE bar PE bar PE bar
• Busbar cross-section mm2 600 600 600 600
• Conductor cross-section, max. (IEC) mm2 240 240 240 240
Degree of protection IP20 IP20 IP20 IP20
Weight, approx. kg (lb) 20 (44.1) 20 (44.1) 21.9 (48.3) 27 (59.5)
Width mm (in) 100 (3.94) 100 (3.94) 100 (3.94) 200 (7.87)
Rated short-circuit current kA 65 65 65 65
according to IEC

1) Rated power of a typical 6-pole standard induction motor based on IL 5) Information regarding the correlation between the pulse frequency and
or IH for 400 V 3 AC 50 Hz. max. output current/output frequency is provided in the SINAMICS Low
2) Rated power of a typical 6-pole standard induction motor based on IL Voltage Engineering Manual.
or IH for 460 V 3 AC 60 Hz. 6) The specified power loss represents the maximum value at 100 %
3)
The base-load current IL is based on a load cycle of 110 % for 60 s or utilization. The value is lower under normal operating conditions.
7)
150 % for 10 s with a load cycle duration of 300 s. Total of all motor cables. Longer cable lengths for specific configurations
4)
For a DC link voltage of 600 V DC. are available on request.

6/42 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Cabinet Modules


Air-cooled units
Motor Modules in booksize format

■ Technical specifications
Line voltage 380 ... 480 V 3 AC Single Motor Modules Booksize Cabinet Kit
DC link voltage 510 ... 720 V DC
6SL3720-1TE26-0AB4 6SL3720-1TE28-5AB3 6SL3720-1TE31-3AB3
Type rating
• At IL (50 Hz 400 V) 1) kW 32 46 71
• At IH (50 Hz 400 V) 1) kW 28 37 57
• At IL (60 Hz 460 V) 2) hp 40 60 100
• At IH (60 Hz 460 V) 2) hp 40 50 75
Output current
• Rated current IN O A 60 85 132
• Base-load current IH 3) A 51 68 105
• Maximum current Imax O A 120 141 210
DC link current Id4) A 72 102 158
Current demand
• 24 V DC, max. A 0.9 1.5 1.5
DC link capacitance F 1410 1880 2820
Pulse frequency 5)
• Rated frequency kHz 4 4 4
• Pulse frequency, max.
- With current derating kHz 16 16 16
Power loss, max. 6)
• At 50 Hz 400 V kW 0.48 0.75 1.25
• At 60 Hz 460 V kW 0.48 0.75 1.25
Cooling air requirement m3/s (ft3/s) 0.023 (0.81) 0.044 (1.55) 0.144 (5.09)
Sound pressure level LpA dB <65 <60 <73
(1 m) at 50/60 Hz
Motor connection
U2, V2, W2
Terminal Terminal Terminal
6
• Conductor cross-section, max. (IEC) mm2 16 35 70
Cable length, max. 7)
• Shielded m (ft) 100 (328) 100 (328) 100 (328)
• Unshielded m (ft) 150 (492) 150 (492) 150 (492)
PE/GND connection PE bar PE bar PE bar
• Busbar cross-section mm2 600 600 600
• Conductor cross-section, max. (IEC) mm2 240 240 240
Degree of protection IP20 IP20 IP20
Weight, approx. kg (lb) 27 (59.5) 33 (72.8) 41 (90.4)
Width mm (in) 200 (7.87) 200 (7.87) 300 (11.8)
Rated short-circuit current kA 65 65 65
according to IEC

1) Rated power of a typical 6-pole standard induction motor based on IL 5) Information regarding the correlation between the pulse frequency and
or IH for 400 V 3 AC 50 Hz. max. output current/output frequency is provided in the SINAMICS Low
2) Rated power of a typical 6-pole standard induction motor based on IL Voltage Engineering Manual.
or IH for 460 V 3 AC 60 Hz. 6) The specified power loss represents the maximum value at 100 %
3)
The base-load current IL is based on a load cycle of 110 % for 60 s or utilization. The value is lower under normal operating conditions.
7)
150 % for 10 s with a load cycle duration of 300 s. Total of all motor cables. Longer cable lengths for specific configurations
4)
For a DC link voltage of 600 V DC. are available on request.

Siemens D 21.3 · 2022 6/43


© Siemens 2022

SINAMICS S120 Cabinet Modules


Air-cooled units
Motor Modules in chassis format

■ Overview ■ Selection and ordering data


Type rating Rated output current Motor Module
at 400 V or 690 V IN in chassis format
kW A Article No.
Line voltage 380 ... 480 V 3 AC
(DC link voltage 510 ... 720 V DC)
110 210 6SL3720-1TE32-1AA3
132 260 6SL3720-1TE32-6AA3
160 310 6SL3720-1TE33-1AA3
200 380 6SL3720-1TE33-8AA3
250 490 6SL3720-1TE35-0AA3
315 605 6SL3720-1TE36-1AA3
400 745 6SL3720-1TE37-5AA3
450 840 6SL3720-1TE38-4AA3
560 985 6SL3720-1TE41-0AA3
710 1260 6SL3720-1TE41-2AA3
Motor Modules in chassis format are available in the power 800 1405 6SL3720-1TE41-4AA3
range from 75 kW to 1200 kW. Line voltage 500 ... 690 V 3 AC
(DC link voltage 675 ... 1035 V DC)
Line voltage DC link voltage Type rating
75 85 6SL3720-1TG28-5AA3
380 ... 480 V 3 AC 510 ... 720 V DC 110 ... 800 kW
90 100 6SL3720-1TG31-0AA3
500 ... 690 V 3 AC 675 ... 1035 V DC 75 ... 1200 kW
110 120 6SL3720-1TG31-2AA3
By connecting in parallel up to four Motor Modules operated on 132 150 6SL3720-1TG31-5AA3
one Control Unit and which supply one motor, it is possible to
increase the available shaft power to a maximum of approx. 160 175 6SL3720-1TG31-8AA3
4500 kW (taking into account the derating factors according 200 215 6SL3720-1TG32-2AA3
6 to the SINAMICS Low Voltage Engineering Manual). 250 260 6SL3720-1TG32-6AA3
SINAMICS S120 Motor Modules in chassis format can also be 315 330 6SL3720-1TG33-3AA3
used as Braking Modules (braking choppers) if, instead of
400 410 6SL3720-1TG34-1AA3
a motor, a 3-phase braking resistor is connected.
For additional information, please refer to the SINAMICS Low 450 465 6SL3720-1TG34-7AA3
Voltage Engineering Manual. 560 575 6SL3720-1TG35-8AA3

■ Design 710
800
735
810
6SL3720-1TG37-4AA3
6SL3720-1TG38-1AA3
Motor Modules in chassis format contain the following 900 910 6SL3720-1TG38-8AA3
components as standard:
1000 1025 6SL3720-1TG41-0AA3
• Retaining device for the DC busbar, including the connection
to the DC connections of the Motor Module 1200 1270 6SL3720-1TG41-3AA3

• Nickel-plated connection busbars for motor cables for Motor


Modules, frame sizes FX and GX; for Motor Modules, frame
sizes HX and JX, the connection is made directly on the unit
• Cable retaining bar for the power cables
• DRIVE-CLiQ interface (3 DRIVE-CLiQ sockets), without
Control Unit
• Customer interface -X55
• Auxiliary power supply system (6-pole) for the auxiliary power
supply, including cable connections for looping through to the
next Cabinet Module
• Nickel-plated PE busbar (60 x 10 mm), including jumper for
looping through to the next Cabinet Module
• EMC-compliant design thanks to additional shielding
measures and appropriately routed cables

6/44 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Cabinet Modules


Air-cooled units
Motor Modules in chassis format

■ Integration
Motor Modules are controlled by the CU320-2 DP or externally, the DRIVE-CLiQ cable will not be included in the
CU320-2 PN Control Unit. Communication between the Control scope of supply and must be configured on site.
Unit and Modules is established via a DRIVE-CLiQ connection.
For additional information, please refer to the SINAMICS Low
If the Control Unit is integrated in the same cabinet as an option Voltage Engineering Manual.
with order code K90 or K95, these communication cables will
already be installed. If the Control Unit is to be mounted For a description of the customer terminal strip, see section
Customer terminal strip -X55.
Cabinet Module
DC busbar

X400 X401 X402

DRIVE-CLiQ socket 0

DRIVE-CLiQ socket 2
DRIVE-CLiQ socket 1
Motor Module
DCP
DCN
DCPA
DCNA =

DCPS =
Customer
DCNS
terminal READY

LEDs
strip
DC LINK
-X55
-X9 POWER OK
1 P24 V
2 M -X2
U2
3 =
4
5
Internal
power supply ~
V2
W2
M
3~ 6
6 PE
-F10
L1
L2
-F11 Fan
-F20

-F21 Fan1)
-X41
4 +Temp internal
2) 3 -Temp
2 EP +24 V
3) 1 EP M1 M
-X46
1 BR Output+
2 BR Output-
3 FB Input+
4 FB Input- IPD Card
-X42
1 P24L
1 2 3 4 5 6 2 P24L
3 M
-X100

4 M

Auxiliary power supply:


-F24

380 - 480 V 2 AC
or 500 - 690 V 2 AC
G_D213_EN_00064d

230 V AC

24 V DC

1) The number and the terminals of the fans depend on the frame size.
2) Connection of temperature sensor for motors without DRIVE-CliQ interface.
3) Required for Safety Integrated.

Connection example of a Motor Module in chassis format

Siemens D 21.3 · 2022 6/45


© Siemens 2022

SINAMICS S120 Cabinet Modules


Air-cooled units
Motor Modules in chassis format

■ Technical specifications
Line voltage 380 ... 480 V 3 AC Motor Modules in chassis format
DC link voltage 510 ... 720 V DC
6SL3720- 6SL3720- 6SL3720- 6SL3720- 6SL3720- 6SL3720-
1TE32-1AA3 1TE32-6AA3 1TE33-1AA3 1TE33-8AA3 1TE35-0AA3 1TE36-1AA3
Type rating
• At IL (50 Hz 400 V) 1) kW 110 132 160 200 250 315
• At IH (50 Hz 400 V) 1) kW 90 110 132 160 200 250
• At IL (60 Hz 460 V) 2) hp 150 200 250 300 400 500
• At IH (60 Hz 460 V) 2) hp 150 200 200 250 350 350
Output current
• Rated current IN O A 210 260 310 380 490 605
• Base-load current IL3) A 205 250 302 370 477 590
• Base-load current IH4) A 178 233 277 340 438 460
• Maximum current Imax O A 307 375 453 555 715 885
DC link current
• Rated current IN DC
when supplied via
- Basic/Smart Line Module A 252 312 372 456 588 726
- Active Line Module A 227 281 335 411 529 653
• Base-load current IL DC 3)
when supplied via
- Basic/Smart Line Module A 245 304 362 444 573 707
- Active Line Module A 221 273 326 400 515 636
• Base-load current IH DC 4)
when supplied via
- Basic/Smart Line Module A 224 277 331 405 523 646
- Active Line Module A 202 250 298 365 470 581
Current demand
• 24 V DC auxiliary power supply A 0.8 0.8 0.9 0.9 0.9 1.0
• 400 V AC A 0.63 1.13 1.8 1.8 1.8 3.6
DC link capacitance F 4200 5200 6300 7800 9600 12600
Pulse frequency 5)
6 • Rated frequency
• Pulse frequency, max.
kHz 2 2 2 2 2 1.25

- Without current derating kHz 2 2 2 2 2 1.25


- With current derating kHz 8 8 8 8 8 8
Power loss, max. 6)
• At 50 Hz 400 V kW 1.86 2.5 2.96 3.67 4.28 5.84
• At 60 Hz 460 V kW 1.94 2.6 3.1 3.8 4.5 6.3
Cooling air requirement m3/s (ft3/s) 0.17 (6.00) 0.23 (8.12) 0.36 (12.7) 0.36 (12.7) 0.36 (12.7) 0.78 (27.5)
Sound pressure level LpA dB 67 69 69 69 69 72
(1 m) at 50/60 Hz
Motor connection M12 screws M12 screws M12 screws M12 screws M12 screws M12 screws
U2, V2, W2
• Conductor cross-section, max. (IEC) mm2 2 × 185 2 × 185 2 × 240 2 × 240 2 × 240 4 × 240
Cable length, max. 7)
• Shielded m (ft) 300 (984) 300 (984) 300 (984) 300 (984) 300 (984) 300 (984)
• Unshielded m (ft) 450 (1476) 450 (1476) 450 (1476) 450 (1476) 450 (1476) 450 (1476)
PE/GND connection PE bar PE bar PE bar PE bar PE bar PE bar
• Busbar cross-section mm2 600 600 600 600 600 600
• Conductor cross-section, max. (IEC) mm2 240 240 240 240 240 240
Degree of protection IP20 IP20 IP20 IP20 IP20 IP20
Dimensions
• Width 8) mm (in) 400 (15.75) 400 (15.75) 400 (15.75) 400 (15.75) 400 (15.75) 600 (23.62)
• Height 9) mm (in) 2200 (86.61) 2200 (86.61) 2200 (86.61) 2200 (86.61) 2200 (86.61) 2200 (86.61)
• Depth mm (in) 600 (23.62) 600 (23.62) 600 (23.62) 600 (23.62) 600 (23.62) 600 (23.62)
Weight, approx. kg (lb) 145 (320) 145 (320) 286 (631) 286 (631) 286 (631) 490 (1080)
Frame size FX FX GX GX GX HX
Rated short-circuit current kA 65 65 65 65 65 65
according to IEC

1) Rated power of a typical 6-pole standard induction motor based on IL or IH 6) The specified power loss represents the maximum value at 100 %
for 400 V 3 AC 50 Hz. utilization. The value is lower under normal operating conditions.
2) Rated power of a typical 6-pole standard induction motor based on IL or IH 7) Total of all motor cables. Longer cable lengths for specific configurations
for 460 V 3 AC 60 Hz. are available on request. For additional information, please refer to the
3) The base-load current IL is based on a duty cycle of 110 % for 60 s or SINAMICS Low Voltage Engineering Manual.
8)
150 % for 10 s with a duty cycle duration of 300 s. With option L10 (dv/dt filter plus VPL):
4)
The base-load current IH is based on a duty cycle of 150 % for 60 s or - Frame sizes FX/GX/HX/JX: Additional cabinet 600 mm (23.62 in) wide.
160 % for 10 s with a duty cycle duration of 300 s. With option L34 (circuit breaker on the output side):
5)
- Frame size FX/GX: Additional cabinet 400 mm (15.7 in) wide
Information regarding the correlation between the pulse frequency and - Frame size HX/JX: Additional cabinet 600 mm (23.62 in) wide.
max. output current/output frequency is provided in the SINAMICS Low 9)
Voltage Engineering Manual. The cabinet height increases by 250 mm (9.84 in) with degree of protection
IP21, and by 400 mm (15.7 in) with degrees of protection IP23, IP43 and IP54.

6/46 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Cabinet Modules


Air-cooled units
Motor Modules in chassis format

■ Technical specifications
Line voltage 380 ... 480 V 3 AC Motor Modules in chassis format
DC link voltage 510 ... 720 V DC
6SL3720- 6SL3720- 6SL3720- 6SL3720- 6SL3720-
1TE37-5AA3 1TE38-4AA3 1TE41-0AA3 1TE41-2AA3 1TE41-4AA3
Type rating
• At IL (50 Hz 400 V) 1) kW 400 450 560 710 800
• At IH (50 Hz 400 V) 1) kW 315 400 450 560 710
• At IL (60 Hz 460 V) 2) hp 600 700 800 1000 1150
• At IH (60 Hz 460 V) 2) hp 450 600 700 900 1000
Output current
• Rated current IN O A 745 840 985 1260 1405
• Base-load current IL3) A 725 820 960 1230 1370
• Base-load current IH4) A 570 700 860 1127 1257
• Maximum current Imax O A 1087 1230 1440 1845 2055
DC link current
• Rated current IN DC
when supplied via
- Basic/Smart Line Module A 894 1008 1182 1512 1686
- Active Line Module A 805 907 1064 1361 1517
• Base-load current IL DC 3)
when supplied via
- Basic/Smart Line Module A 871 982 1152 1474 1643
- Active Line Module A 784 884 1037 1326 1479
• Base-load current IH DC 4)
when supplied via
- Basic/Smart Line Module A 795 897 1051 1345 1500
- Active Line Module A 716 807 946 1211 1350
Current demand
• 24 V DC auxiliary power supply A 1.0 1.0 1.25 1.4 1.4
• 400 V AC A 3.6 3.6 5.4 5.4 5.4
DC link capacitance F 15600 16800 18900 26100 28800
Pulse frequency 5)
• Rated frequency
• Pulse frequency, max.
kHz 1.25 1.25 1.25 1.25 1.25 6
- Without current derating kHz 1.25 1.25 1.25 1.25 1.25
- With current derating kHz 8 8 8 8 8
Power loss, max. 6)
• At 50 Hz 400 V kW 6.68 7.15 9.5 11.1 12.0
• At 60 Hz 460 V kW 7.3 7.8 10.2 12.0 13.0
Cooling air requirement m3/s (ft3/s) 0.78 (27.5) 0.78 (27.5) 1.08 (38.1) 1.08 (38.1) 1.08 (38.1)
Sound pressure level LpA dB 72 72 72 72 72
(1 m) at 50/60 Hz
Motor connection M12 screws M12 screws M12 screws M12 screws M12 screws
U2, V2, W2
• Conductor cross-section, max. (IEC) mm2 4 × 240 4 × 240 6 × 240 6 × 240 6 × 240
Cable length, max. 7)
• Shielded m (ft) 300 (984) 300 (984) 300 (984) 300 (984) 300 (984)
• Unshielded m (ft) 450 (1476) 450 (1476) 450 (1476) 450 (1476) 450 (1476)
PE/GND connection PE bar PE bar PE bar PE bar PE bar
• Busbar cross-section mm2 600 600 600 600 600
• Conductor cross-section, max. (IEC) mm2 240 240 240 240 240
Degree of protection IP20 IP20 IP20 IP20 IP20
Dimensions
• Width 8) mm (in) 600 (23.62) 600 (23.62) 800 (31.50) 800 (31.50) 800 (31.50)
• Height 9) mm (in) 2200 (86.61) 2200 (86.61) 2200 (86.61) 2200 (86.61) 2200 (86.61)
• Depth mm (in) 600 (23.62) 600 (23.62) 600 (23.62) 600 (23.62) 600 (23.62)
Weight, approx. kg (lb) 490 (1080) 490 (1080) 700 (1544) 700 (1544) 700 (1544)
Frame size HX HX JX JX JX
Rated short-circuit current kA 65 84 84 100 100
according to IEC

1) 6)
Rated power of a typical 6-pole standard induction motor based on IL or IH The specified power loss represents the maximum value at 100 %
for 400 V 3 AC 50 Hz. utlization. The value is lower under normal operating conditions.
2) 7)
Rated power of a typical 6-pole standard induction motor based on IL or IH Total of all motor cables. Longer cable lengths for specific configurations
for 460 V 3 AC 60 Hz. are available on request. For additional information, please refer to the
3)
The base-load current IL is based on a duty cycle of 110 % for 60 s or SINAMICS Low Voltage Engineering Manual.
8)
150 % for 10 s with a duty cycle duration of 300 s. With option L10 (dv/dt filter plus VPL):
4)
The base-load current IH is based on a duty cycle of 150 % for 60 s or - Frame sizes FX/GX/HX/JX: Additional cabinet 600 mm (23.62 in) wide.
160 % for 10 s with a duty cycle duration of 300 s. With option L34 (circuit breaker on the output side):
5)
- Frame size FX/GX: Additional cabinet 400 mm (15.7 in) wide
Information regarding the correlation between the pulse frequency and - Frame size HX/JX: Additional cabinet 600 mm (23.62 in) wide.
max. output current/output frequency is provided in the SINAMICS Low 9)
Voltage Engineering Manual. The cabinet height increases by 250 mm (9.84 in) with degree of protection
IP21, and by 400 mm (15.7 in) with degrees of protection IP23, IP43 and IP54.

Siemens D 21.3 · 2022 6/47


© Siemens 2022

SINAMICS S120 Cabinet Modules


Air-cooled units
Motor Modules in chassis format

■ Technical specifications
Line voltage 500 ... 690 V 3 AC Motor Modules in chassis format
DC link voltage 675 … 1035 V DC
6SL3720- 6SL3720- 6SL3720- 6SL3720- 6SL3720- 6SL3720-
1TG28-5AA3 1TG31-0AA3 1TG31-2AA3 1TG31-5AA3 1TG31-8AA3 1TG32-2AA3
Type rating
• At IL (50 Hz 690 V) 1) kW 75 90 110 132 160 200
• At IH (50 Hz 690 V) 1) kW 55 75 90 110 132 160
• At IL (50 Hz 500 V) 1) kW 55 55 75 90 110 132
• At IH (50 Hz 500 V) 1) kW 45 55 75 90 90 110
• At IL (60 Hz 575 V) 2) hp 75 75 100 150 150 200
• At IH (60 Hz 575 V) 2) hp 75 75 100 125 150 200
Output current
• Rated current IN O A 85 100 120 150 175 215
• Base-load current IL3) A 80 95 115 142 170 208
• Base-load current IH4) A 76 89 107 134 157 192
• Maximum current Imax O A 120 142 172 213 255 312
DC link current
• Rated current IN DC
when supplied via
- Basic/Smart Line Module A 102 120 144 180 210 258
- Active Line Module A 92 108 130 162 189 232
• Base-load current IL DC 3)
when supplied via
- Basic/Smart Line Module A 99 117 140 175 204 251
- Active Line Module A 89 105 126 157 184 226
• Base-load current IH DC 4)
when supplied via
- Basic/Smart Line Module A 90 106 128 160 186 229
- Active Line Module A 81 96 115 144 168 206
Current demand
• 24 V DC auxiliary power supply A 0.8 0.8 0.8 0.8 0.9 0.9
• 690 V AC A 0.4 0.4 0.4 0.4 1.0 1.0
F
6 DC link capacitance
Pulse frequency 5)
1200 1200 1600 2800 2800 2800

• Rated frequency kHz 1.25 1.25 1.25 1.25 1.25 1.25


• Pulse frequency, max.
- Without current derating kHz 1.25 1.25 1.25 1.25 1.25 1.25
- With current derating kHz 7.5 7.5 7.5 7.5 7.5 7.5
Power loss, max. 6)
• At 50 Hz 690 V kW 1.17 1.43 1.89 1.8 2.67 3.09
• At 60 Hz 575 V kW 1.1 1.3 1.77 1.62 2.5 2.91
Cooling air requirement m3/s (ft3/s) 0.17 (6.00) 0.17 (6.00) 0.17 (6.00) 0.17 (6.00) 0.36 (12.7) 0.36 (12.7)
Sound pressure level LpA dB 67 67 67 67 69 69
(1 m) at 50/60 Hz
Motor connection M12 screws M12 screws M12 screws M12 screws M12 screws M12 screws
U2, V2, W2
• Conductor cross-section, max. (IEC) mm2 2 × 185 2 × 185 2 × 185 2 × 185 2 × 240 2 × 240
Cable length, max. 7)
• Shielded m (ft) 300 (984) 300 (984) 300 (984) 300 (984) 300 (984) 300 (984)
• Unshielded m (ft) 450 (1476) 450 (1476) 450 (1476) 450 (1476) 450 (1476) 450 (1476)
PE/GND connection PE bar PE bar PE bar PE bar PE bar PE bar
• Busbar cross-section mm2 600 600 600 600 600 600
• Conductor cross-section, max. (IEC) mm2 240 240 240 240 240 240
Degree of protection IP20 IP20 IP20 IP20 IP20 IP20
Dimensions
• Width 8) mm (in) 400 (15.75) 400 (15.75) 400 (15.75) 400 (15.75) 400 (15.75) 400 (15.75)
• Height 9) mm (in) 2200 (86.61) 2200 (86.61) 2200 (86.61) 2200 (86.61) 2200 (86.61) 2200 (86.61)
• Depth mm (in) 600 (23.62) 600 (23.62) 600 (23.62) 600 (23.62) 600 (23.62) 600 (23.62)
Weight, approx. kg (lb) 145 (320) 145 (320) 145 (320) 145 (320) 286 (631) 286 (631)
Frame size FX FX FX FX GX GX
Rated short-circuit current kA 65 65 65 65 65 65
according to IEC

1) Rated power of a typical 6-pole standard induction motor based on IL or IH 6) The specified power loss represents the maximum value at 100 %
for 500 V or 690 V 3 AC 50 Hz. utilization. The value is lower under normal operating conditions.
2) Rated power of a typical 6-pole standard induction motor based on IL or IH 7) Total of all motor cables. Longer cable lengths for specific configurations
for 575 V 3 AC 60 Hz. are available on request. For additional information, please refer to the
3) The base-load current IL is based on a duty cycle of 110 % for 60 s or SINAMICS Low Voltage Engineering Manual.
150 % for 10 s with a duty cycle duration of 300 s. 8) With option L10 (dv/dt filter plus VPL):
4) The base-load current IH is based on a duty cycle of 150 % for 60 s or - Frame sizes FX/GX/HX/JX: Additional cabinet 600 mm (23.62 in) wide.
160 % for 10 s with a duty cycle duration of 300 s. With option L34 (circuit breaker on the output side):
5)
- Frame size FX/GX: Additional cabinet 400 mm (15.7 in) wide
Information regarding the correlation between the pulse frequency and - Frame size HX/JX: Additional cabinet 600 mm (23.62 in) wide.
max. output current/output frequency is provided in the SINAMICS Low 9)
Voltage Engineering Manual. The cabinet height increases by 250 mm (9.84 in) with degree of protection
IP21, and by 400 mm (15.7 in) with degrees of protection IP23, IP43 and IP54.

6/48 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Cabinet Modules


Air-cooled units
Motor Modules in chassis format

■ Technical specifications
Line voltage 500 ... 690 V 3 AC Motor Modules in chassis format
DC link voltage 675 … 1035 V DC
6SL3720- 6SL3720- 6SL3720- 6SL3720- 6SL3720- 6SL3720-
1TG32-6AA3 1TG33-3AA3 1TG34-1AA3 1TG34-7AA3 1TG35-8AA3 1TG37-4AA3
Type rating
• At IL (50 Hz 690 V) 1) kW 250 315 400 450 560 710
• At IH (50 Hz 690 V) 1) kW 200 250 315 400 450 630
• At IL (50 Hz 500 V) 1) kW 160 200 250 315 400 500
• At IH (50 Hz 500 V) 1) kW 132 160 200 250 315 450
• At IL (60 Hz 575 V) 2) hp 250 300 400 450 600 700
• At IH (60 Hz 575 V) 2) hp 200 250 350 450 500 700
Output current
• Rated current IN O A 260 330 410 465 575 735
• Base-load current IL3) A 250 320 400 452 560 710
• Base-load current IH4) A 233 280 367 416 514 657
• Maximum current Imax O A 375 480 600 678 840 1065
DC link current
• Rated current IN DC
when supplied via
- Basic/Smart Line Module A 312 396 492 558 690 882
- Active Line Module A 281 356 443 502 621 794
• Base-load current IL DC 3)
when supplied via
- Basic/Smart Line Module A 304 386 479 544 672 859
- Active Line Module A 273 347 431 489 605 774
• Base-load current IH DC 4)
when supplied via
- Basic/Smart Line Module A 277 352 437 496 614 784
- Active Line Module A 250 316 394 446 552 706
Current demand
• 24 V DC auxiliary power supply A 0.9 0.9 1.0 1.0 1.0 1.25
• 690 V AC A 1.0 1.0 2.1 2.1 2.1 3.1
F
DC link capacitance
Pulse frequency 5)
3900 4200 7400 7400 7400 11100
6
• Rated frequency kHz 1.25 1.25 1.25 1.25 1.25 1.25
• Pulse frequency, max.
- Without current derating kHz 1.25 1.25 1.25 1.25 1.25 1.25
- With current derating kHz 7.5 7.5 7.5 7.5 7.5 7.5
Power loss, max. 6)
• At 50 Hz 690 V kW 3.62 4.34 6.13 6.8 10.3 10.9
• At 60 Hz 575 V kW 3.38 3.98 5.71 6.32 9.7 10.0
Cooling air requirement m3/s (ft3/s) 0.36 (12.7) 0.36 (12.7) 0.78 (27.5) 0.78 (27.5) 0.78 (27.5) 1.08 (38.1)
Sound pressure level LpA dB 69 69 72 72 72 72
(1 m) at 50/60 Hz
Motor connection M12 screws M12 screws M12 screws M12 screws M12 screws M12 screws
U2, V2, W2
• Conductor cross-section, max. (IEC) mm2 2 × 240 2 × 240 4 × 240 4 × 240 4 × 240 6 × 240
Cable length, max. 7)
• Shielded m (ft) 300 (984) 300 (984) 300 (984) 300 (984) 300 (984) 300 (984)
• Unshielded m (ft) 450 (1476) 450 (1476) 450 (1476) 450 (1476) 450 (1476) 450 (1476)
PE/GND connection PE bar PE bar PE bar PE bar PE bar PE bar
• Busbar cross-section mm2 600 600 600 600 600 600
• Conductor cross-section, max. (IEC) mm2 240 240 240 240 240 240
Degree of protection IP20 IP20 IP20 IP20 IP20 IP20
Dimensions
• Width 8) mm (in) 400 (15.75) 400 (15.75) 600 (23.62) 600 (23.62) 600 (23.62) 800 (31.50)
• Height 9) mm (in) 2200 (86.61) 2200 (86.61) 2200 (86.61) 2200 (86.61) 2200 (86.61) 2200 (86.61)
• Depth mm (in) 600 (23.62) 600 (23.62) 600 (23.62) 600 (23.62) 600 (23.62) 600 (23.62)
Weight, approx. kg (lb) 286 (631) 286 (631) 490 (1080) 490 (1080) 490 (1080) 700 (1544)
Frame size GX GX HX HX HX JX
Rated short-circuit current kA 65 65 65 84 84 100
according to IEC

1) 6)
Rated power of a typical 6-pole standard induction motor based on IL or IH The specified power loss represents the maximum value at 100 %
for 500 V or 690 V 3 AC 50 Hz. utilization. The value is lower under normal operating conditions.
2) 7)
Rated power of a typical 6-pole standard induction motor based on IL or IH Total of all motor cables. Longer cable lengths for specific configurations
for 575 V 3 AC 60 Hz. are available on request. For additional information, please refer to the
3)
The base-load current IL is based on a duty cycle of 110 % for 60 s or SINAMICS Low Voltage Engineering Manual.
8)
150 % for 10 s with a duty cycle duration of 300 s. With option L10 (dv/dt filter plus VPL):
4)
The base-load current IH is based on a duty cycle of 150 % for 60 s or - Frame sizes FX/GX/HX/JX: Additional cabinet 600 mm (23.62 in) wide.
160 % for 10 s with a duty cycle duration of 300 s. With option L34 (circuit breaker on the output side):
5)
- Frame size FX/GX: Additional cabinet 400 mm (15.7 in) wide
Information regarding the correlation between the pulse frequency and - Frame size HX/JX: Additional cabinet 600 mm (23.62 in) wide.
max. output current/output frequency is provided in the SINAMICS Low 9)
Voltage Engineering Manual. The cabinet height increases by 250 mm (9.84 in) with degree of protection
IP21, and by 400 mm (15.7 in) with degrees of protection IP23, IP43 and IP54.

Siemens D 21.3 · 2022 6/49


© Siemens 2022

SINAMICS S120 Cabinet Modules


Air-cooled units
Motor Modules in chassis format

■ Technical specifications
Line voltage 500 ... 690 V 3 AC Motor Modules in chassis format
DC link voltage 675 … 1035 V DC
6SL3720-1TG38-1AA3 6SL3720-1TG38-8AA3 6SL3720-1TG41-0AA3 6SL3720-1TG41-3AA3
Type rating
• At IL (50 Hz 690 V) 1) kW 800 900 1000 1200
• At IH (50 Hz 690 V) 1) kW 710 800 900 1000
• At IL (50 Hz 500 V) 1) kW 560 630 710 900
• At IH (50 Hz 500 V) 1) kW 500 560 630 800
• At IL (60 Hz 575 V) 2) hp 800 900 1000 1250
• At IH (60 Hz 575 V) 2) hp 700 800 900 1000
Output current
• Rated current IN O A 810 910 1025 1270
• Base-load current IL3) A 790 880 1000 1230
• Base-load current IH4) A 724 814 917 1136
• Maximum current Imax O A 1185 1320 1500 1845
DC link current
• Rated current IN DC
when supplied via
- Basic/Smart Line Module A 972 1092 1230 1524
- Active Line Module A 875 983 1107 1372
• Base-load current IL DC 3)
when supplied via
- Basic/Smart Line Module A 947 1064 1199 1485
- Active Line Module A 853 958 1079 1337
• Base-load current IH DC 4)
when supplied via
- Basic/Smart Line Module A 865 971 1094 1356
- Active Line Module A 778 874 985 1221
Current demand
• 24 V DC auxiliary power supply A 1.25 1.4 1.4 1.4
• 690 V AC A 3.1 3.1 3.1 3.1
DC link capacitance F 11100 14400 14400 19200

6 Pulse frequency 5)
• Rated frequency kHz 1.25 1.25 1.25 1.25
• Pulse frequency, max.
- Without current derating kHz 1.25 1.25 1.25 1.25
- With current derating kHz 7.5 7.5 7.5 7.5
Power loss, max. 6)
• At 50 Hz 690 V kW 11.5 11.7 13.2 16.0
• At 60 Hz 575 V kW 10.5 10.6 12.0 14.2
Cooling air requirement m3/s (ft3/s) 1.08 (38.1) 1.08 (38.1) 1.08 (38.1) 1.08 (38.1)
Sound pressure level LpA dB 72 72 72 72
(1 m) at 50/60 Hz
Motor connection M12 screws M12 screws M12 screws M12 screws
U2, V2, W2
2
• Conductor cross-section, max. (IEC) mm 6 x 240 6 x 240 6 x 240 6 x 240
Cable length, max. 7)
• Shielded m (ft) 300 (984) 300 (984) 300 (984) 300 (984)
• Unshielded m (ft) 450 (1476) 450 (1476) 450 (1476) 450 (1476)
PE/GND connection PE bar PE bar PE bar PE bar
• Busbar cross-section mm2 600 600 600 600
• Conductor cross-section, max. (IEC) mm2 240 240 240 240
Degree of protection IP20 IP20 IP20 IP20
Dimensions
• Width 8) mm (in) 800 (31.50) 800 (31.50) 800 (31.50) 800 (31.50)
• Height 9) mm (in) 2200 (86.61) 2200 (86.61) 2200 (86.61) 2200 (86.61)
• Depth mm (in) 600 (23.62) 600 (23.62) 600 (23.62) 600 (23.62)
Weight, approx. kg (lb) 700 (1544) 700 (1544) 700 (1544) 700 (1544)
Frame size JX JX JX JX
Rated short-circuit current kA 100 100 100 100
according to IEC

1) 6)
Rated power of a typical 6-pole standard induction motor based on IL or IH The specified power loss represents the maximum value at 100 %
for 500 V or 690 V 3 AC 50 Hz. utilization. The value is lower under normal operating conditions.
2) 7)
Rated power of a typical 6-pole standard induction motor based on IL or IH Total of all motor cables. Longer cable lengths for specific configurations
for 575 V 3 AC 60 Hz. are available on request. For additional information, please refer to the
3)
The base-load current IL is based on a duty cycle of 110 % for 60 s or SINAMICS Low Voltage Engineering Manual.
8)
150 % for 10 s with a duty cycle duration of 300 s. With option L10 (dv/dt filter plus VPL):
4)
The base-load current IH is based on a duty cycle of 150 % for 60 s or - Frame sizes FX/GX/HX/JX: Additional cabinet 600 mm (23.62 in) wide.
160 % for 10 s with a duty cycle duration of 300 s. With option L34 (circuit breaker on the output side):
5)
- Frame size FX/GX: Additional cabinet 400 mm (15.7 in) wide
Information regarding the correlation between the pulse frequency and - Frame size HX/JX: Additional cabinet 600 mm (23.62 in) wide.
max. output current/output frequency is provided in the SINAMICS Low 9)
Voltage Engineering Manual. The cabinet height increases by 250 mm (9.84 in) with degree of protection
IP21, and by 400 mm (15.7 in) with degrees of protection IP23, IP43 and IP54.

6/50 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Cabinet Modules


Air-cooled units
Central Braking Modules

■ Overview ■ Selection and ordering data


Braking powers Central Braking Module
P15 P150 P270 PDB
kW kW kW kW Article No.
DC link voltage 510 ... 720 V DC
730 500 300 200 6SL3700-1AE35-0AA3
1380 1000 580 370 6SL3700-1AE41-0AA3
DC link voltage 675 ... 900 V DC
830 550 340 220 6SL3700-1AF35-5AA3
1580 1100 650 420 6SL3700-1AF41-1AA3
DC link voltage 890 ... 1035 V DC
920 630 380 240 6SL3700-1AH36-3AA3
1700 1200 720 460 6SL3700-1AH41-2AA3

Note:
In contrast to the optional Braking Modules (options L61, L62 or
Central Braking Modules limit the DC link voltage at a central L64, L65), the braking resistors for the Central Braking Modules
location in the drive line-up when the motors are operating in must be ordered separately.
generator mode and energy recovery to the supply system is not
possible. If, in regenerative mode, the voltage of the DC busbar Braking power Dimensions (W × D × H) Braking resistor in degree
P150 of protection IP21
exceeds a limit value, an externally installed braking resistor is
switched in, thus restricting the voltage from increasing further. kW mm (in) Article No.
The regenerative energy is converted into heat. The braking DC link voltage 510 ... 720 V DC
resistor is switched in by the Braking Unit integrated in the
500 960 × 620 × 790 6SL3000-1BE35-0AA0
Cabinet Module, which is equipped with state-of-the-art (37.80 × 24.41 × 31.10)
MOSFET/IGBT semiconductors.
1000 960 × 620 × 1430 6SL3000-1BE41-0AA0
Central Braking Modules are an alternative to the optional (37.80 × 24.41 × 56.30)
Braking Modules (options L61/L62 or L64/L65) and are
particularly suitable when high braking powers are required in
DC link voltage 675 ... 900 V DC 6
a drive line-up. The required braking power can also be 550 960 × 620 × 1110 6SL3000-1BF35-5AA0
(37.80 × 24.41 × 43.70)
increased by connecting units in parallel.
1100 960 × 620 × 1430 6SL3000-1BF41-1AA0
Line voltage DC link voltage Braking power P150 (37.80 × 24.41 × 56.30)
380 ... 480 V 3 AC 510 ... 720 V DC 500 kW/1000 kW DC link voltage 890 ... 1035 V DC
500 ... 600 V 3 AC 675 ... 900 V DC 550 kW/1100 kW 630 960 × 620 × 1110 6SL3000-1BH36-3AA0
(37.80 × 24.41 × 43.70)
660 … 690 V 3 AC 890 ... 1035 V DC 630 kW/1200 kW
1200 960 × 620 × 1430 6SL3000-1BH41-2AA0
The built-in fan means that Central Braking Modules are also (37.80 × 24.41 × 56.30)
suitable for high continuous power levels.

■ Design
The Central Braking Module is a cabinet unit with integrated
braking chopper. Using state-of-the-art MOSFET/IGBT
semiconductors, the power unit controls when the braking
resistor is switched-in.
Central Braking Modules are designed as a 400 mm wide
cabinet module. Its connection to the DC link is protected
by fuses.
Central Braking Modules require braking resistors that must
be externally mounted and which can be ordered separately.
The cables to the resistors can be connected to lugs which are
specially prepared for plant application and which are located in
the connection area of the cabinet.
The power units have diagnostics LEDs for the display of faults
and also a control output for the communication of faults.
The Central Braking Module can be disabled externally via
a control input.
The arrangement in the DC link system is subject to specific
configuring rules.
For additional information, please refer to the SINAMICS Low
Voltage Engineering Manual.

Siemens D 21.3 · 2022 6/51


© Siemens 2022

SINAMICS S120 Cabinet Modules


Air-cooled units
Central Braking Modules

■ Integration
Cabinet Module

DC busbar

C -X1 -X1 G -X5 1


D H 2

Central
Braking
Module

Overcurrent
-X2

LEDs
Overload
1 Lock/
2 Overtemp
Reset
3 Ready
M
4
Relay
5 Ready
6 Fault

Fan

6
1 2 3 4 5 6
-X100

Auxiliary power supply:


-F24

380 - 480 V 2 AC
or 500 - 690 V 2 AC

230 V AC
G_D213_EN_00065b

24 V DC

To drive control

Braking resistor

Connection example of a Central Braking Module

6/52 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Cabinet Modules


Air-cooled units
Central Braking Modules

■ Technical specifications
Central Braking Modules
6SL3700- 6SL3700- 6SL3700- 6SL3700- 6SL3700- 6SL3700-
1AE35-0AA3 1AE41-0AA3 1AF35-5AA3 1AF41-1AA3 1AH36-3AA3 1AH41-2AA3
Line voltage 380 ... 480 V 500 ... 600 V 660 ... 690 V
Braking power P150 kW 500 1000 550 1100 630 1200
Continuous braking power PDB kW 200 370 220 420 240 460
Braking current for P150 A 650 1200 580 1100 520 1000
Current demand 1)
• 230 V 2 AC A 0.4 0.4 0.4 0.4 0.4 0.4
Power loss, max. 2) kW 0.8 1.5 0.8 1.5 0.8 1.5
At 50 Hz 400/500/690 V
DC link capacitance F 8160 9720 7640 8680 7640 8680
Cooling air requirement m3/s (ft3/s) 0.14 (4.94) 0.14 (4.94) 0.14 (4.94) 0.14 (4.94) 0.14 (4.94) 0.14 (4.94)
Sound pressure level LpA dB 55 55 55 55 55 55
(1 m) at 50/60 Hz
Braking resistor connection M12 screws M12 screws M12 screws M12 screws M12 screws M12 screws
• Conductor cross-section, max. (IEC) mm2 2 × 240 2 × 240 2 × 240 2 × 240 2 × 240 2 × 240
PE/GND connection PE bar PE bar PE bar PE bar PE bar PE bar
• Busbar cross-section mm2 600 600 600 600 600 600
• Conductor cross-section, max. (IEC) mm2 240 240 240 240 240 240
Degree of protection IP20 IP20 IP20 IP20 IP20 IP20
Dimensions
• Width mm (in) 400 (15.75) 400 (15.75) 400 (15.75) 400 (15.75) 400 (15.75) 400 (15.75)
• Height 3) mm (in) 2200 (86.61) 2200 (86.61) 2200 (86.61) 2200 (86.61) 2200 (86.61) 2200 (86.61)
• Depth mm (in) 600 (23.62) 600 (23.62) 600 (23.62) 600 (23.62) 600 (23.62) 600 (23.62)
Weight, approx. kg (lb) 230 (507) 230 (507) 230 (507) 230 (507) 230 (507) 230 (507)
Frame size mm (in) 400 (15.75) 400 (15.75) 400 (15.75) 400 (15.75) 400 (15.75) 400 (15.75) 6
Braking resistors
6SL3000- 6SL3000- 6SL3000- 6SL3000- 6SL3000- 6SL3000-
1BE35-0AA0 1BE41-0AA0 1BF35-5AA0 1BF41-1AA0 1BH36-3AA0 1BH41-2AA0
Line voltage 380 ... 480 V 500 ... 600 V 660 ... 690 V
Braking power PBR kW 500 1000 550 1100 630 1200
Continuous braking power PDB kW 23 58 34 62 42 75
Resistance value  0.95 0.49 1.35 0.69 1.8 0.95
Degree of protection IP21 IP21 IP21 IP21 IP21 IP21
Dimensions
• Width mm (in) 960 (37.80) 960 (37.80) 960 (37.80) 960 (37.80) 960 (37.80) 960 (37.80)
• Height mm (in) 620 (24.41) 620 (24.41) 620 (24.41) 620 (24.41) 620 (24.41) 620 (24.41)
• Depth mm (in) 790 (31.10) 1430 (56.30) 1110 (43.70) 1430 (56.30) 1110 (43.70) 1430 (56.30)
Weight, approx. kg (lb) 82 (181) 170 (375) 110 (243) 180 (397) 124 (273) 196 (432)

1)
Current demand of the fans.
2)
The specified power loss represents the maximum value at 100 %
utilization. The value is lower under normal operating conditions.
3)
The cabinet height increases by 250 mm (9.84 in) with degree of protection
IP21, and by 400 mm (15.7 in) with degrees of protection IP23,
IP43 and IP54.

Siemens D 21.3 · 2022 6/53


© Siemens 2022

SINAMICS S120 Cabinet Modules


Air-cooled units
Central Braking Modules

■ Characteristic curves
Central Braking Modules are dimensioned for braking powers In most applications, Central Braking Modules are only used for
with the following duty cycles: occasional braking operations, e.g. stopping a drive in an
emergency. Low-cost braking resistors in degree of protection
IP21 are specifically offered for these types of applications;
P
these braking resistors are dimensioned for braking powers PBR
with the following duty cycle:

G_D213_EN_00073
P P
15 15

P P
150 150

P
BR
P270 P270
PDB

G_D213_EN_00066a
15 150 270 600 s t

PDB = Continuous braking power


P15 = Power which is permissible every 600 s for 15 s
15 s 40 s 20 min t
P150 = Power which is permissible every 600 s for 150 s
P270 = Power which is permissible every 600 s for 270 s
PBR = Power which is permissible every 20 min for 15 s

Braking powers of the Central Braking Modules


Duty cycle for braking resistors
The braking powers are subject to a cycle time of 600 s. P150 is
Braking resistors with a higher braking power and shorter cycle
assumed to be the rated braking power. The braking resistors
times are available on request.
can be assigned according to these power ratings.
6

6/54 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Cabinet Modules


Air-cooled units
Auxiliary Power Supply Modules

■ Overview ■ Selection and ordering data


System-side power supply Auxiliary Power Supply
(380 ... 690 V 3 AC) Module
A Article No.
125 6SL3700-0MX14-0AA3
160 6SL3700-0MX16-3AA3
200 6SL3700-0MX21-0AA3
250 6SL3700-0MX21-4AA3

Note:
In smaller systems, there is often no need for an additional
Cabinet Module for the auxiliary power supply. In such cases,
the infeed for the auxiliary power supply system can also be
supplied by the Line Connection Module. This must then be
ordered separately (option K76).

Auxiliary Power Supply Modules supply the auxiliary power


supply system for the SINAMICS S120 Cabinet Modules. Units
connected to this auxiliary power supply system include the fans
of the SINAMICS S120 devices installed in the Cabinet Modules.
In addition, the auxiliary power supply system supplies the
electronic modules with an external voltage of 24 V DC. This is
required when the DC link is not charged, for instance, in order
to maintain PROFIBUS/PROFINET communication.

■ Design
The Auxiliary Power Supply Module is connected in the
customer's plant to a voltage corresponding to the respective 6
rated unit voltage.
The standard version contains the following components:
• Fuse switch disconnector with fuse monitoring for external
evaluation
• Supply of the auxiliary power supply system with 3 fused
auxiliary voltages:
- 24 V DC for the electronics power supply
- 230 V 2 AC to supply 230 V loads
- 380 V to 690 V 2 AC to supply the equipment fans
• Transformer with 230 V output voltage
• SITOP 24 V DC power supply
• 6-pole auxiliary power supply system (ready-wired), including
connections for looping through to the next Cabinet Module
• Nickel-plated PE busbar (60 mm × 10 mm), including jumper
for looping through to the next Cabinet Module

Siemens D 21.3 · 2022 6/55


© Siemens 2022

SINAMICS S120 Cabinet Modules


Air-cooled units
Auxiliary Power Supply Modules

■ Integration
Cabinet Module

Auxiliary
Power Supply
Module -X45
-Q1 -Q4
L1 1
2
L2 3
4
L3

-Q3 -Q2 -T2

-X47
1
2
3
4
11
12
13
Fuse
14 monitoring
15
16

6 17
18

1 2 3 4 5 6
-X100

Auxiliary power supply:


-F24

380 - 480 V 2 AC
or 500 - 690 V 2 AC
G_D213_EN_00067b

230 V AC

24 V DC

Connection example of an Auxiliary Power Supply Module

6/56 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Cabinet Modules


Air-cooled units
Auxiliary Power Supply Modules

■ Technical specifications
Auxiliary Power Supply Modules
6SL3700-0MX14-0AA3 6SL3700-0MX16-3AA3 6SL3700-0MX21-0AA3 6SL3700-0MX21-4AA3
Plant-side power supply A 125 160 200 250
380 ... 690 V 3 AC
Line supply connection
• Conductor cross-section, max. (IEC) mm2 150 150 150 150
Max. current carrying capacity
• Load connection
380 V ... 690 V 2 AC
- To auxiliary power supply A 63 80 100 100
- To customer terminal -X45 A 50 63 80 80
• Load connection
230 V 2 AC
- To auxiliary power supply A 6 10 10 20
- To customer terminal -X47 A 8 10 10 20
• Load connection
24 V DC
- To auxiliary power supply A 20 40 80 80
Cable cross-section, max.
• Connection -X45 mm2 16 16 16 16
• Connection -X47 mm2 2.5 2.5 2.5 2.5
Cooling air requirement m3/s (ft3/s) Natural convection Natural convection Natural convection Natural convection
PE/GND connection PE bar PE bar PE bar PE bar
• Busbar cross-section mm2 600 600 600 600
• Conductor cross-section, max. (IEC) mm2 240 240 240 240
Degree of protection IP20 IP20 IP20 IP20
Dimensions
• Width mm (in) 600 (23.62) 600 (23.62) 600 (23.62) 600 (23.62)
• Height 1)
• Depth
mm (in)
mm (in)
2200 (86.61)
600 (23.62)
2200 (86.61)
600 (23.62)
2200 (86.61)
600 (23.62)
2200 (86.61)
600 (23.62)
6
Weight, approx. kg (lb) 170 (375) 180 (397) 210 (463) 240 (529)
Minimum short-circuit current 2) A 3200 4000 5000 7000

1) The cabinet height increases by 250 mm (9.84 in) with degree of protection
IP21, and by 400 mm (15.7 in) with degrees of protection IP23, IP43 and
IP54.
2) Current required to ensure reliable tripping of installed protective devices.

Siemens D 21.3 · 2022 6/57


© Siemens 2022

SINAMICS S120 Cabinet Modules


Air-cooled units
Customer terminal strip -X55

■ Overview ■ Design
To connect signal cables on the customer side, terminal
strip -X55 includes terminals -X122, -X132, -X41 and -X46
(terminals -X1 to -X4 are used inside the cabinet and are not
available). As a consequence, depending on the version
(with/without option K90) the following digital inputs/outputs
and/or signals are available:
The customer Motor Modules Line Modules
terminal strip -X55 in chassis format
includes:
Without With Without With
CU320-2 (K90/K95) CU320-2 (K90/K95)
-X122, -X132
G_D213_XX_00078a 12 digital inputs DI –  – 
8 bidirectional –  – 
inputs/outputs
(DI/DO)
-X41
Connection safety   – 1) – 1)
function Safe Torque
Off / Safe Stop 1

Customer terminal strip -X55 is the interface with the I/O devices Connection   – 1) – 1)
temperature sensor
and marshals a range of cabinet-internal signals to a central KTY84/PTC/Pt100
terminal strip module mounted in the lower part of the cabinet.
-X46
It can be used for Motor Modules in the chassis format as well
Connection Safe   – –
as together with options K90 (Control Unit CU320-2 DP) or K95 Brake Adapter
(Control Unit CU320-2 PN) for Basic Line Modules, Smart Line
Modules, Active Line Modules and Booksize Cabinet Kits.
6

1) For Booksize Cabinet Kits, a connection is provided at the separate


customer terminal strip -X55.1.

6/58 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Cabinet Modules


Air-cooled units
Customer terminal strip -X55

■ Design
Pin assignment Terminal strip -X55-X122 digital inputs/outputs
Terminal Designation 1) Technical data
Customer terminal strip -X55 1 DI 0 Voltage -30 V to +30 V DC
Current consumption, typical: 9 mA at
-X122 2 DI 1 24 V DC
1 DI0 3 DI 2 Galvanic isolation: The reference potential
2 DI1 is terminal M1
3 DI2 4 DI 3
4 DI3
Level (incl. ripple):
5 DI 16 High level: 15 V ... 30 V
5 DI16
6 DI17 6 DI 17 Low level: -30 V ... +5 V
7 M1 Input delay (typ.):
8 M at 0  1: 50 s
9 DI/DO8 at 1  0: 150 s
10 DI/DO9
7 M1 Reference potential for terminals 1 to 6
11 M
12 DI/DO10 8 M Ground
13 DI/DO11
14 M 9 DI/DO 8 As input:
10 DI/DO 9 Voltage -30 V ... +30 V DC
-X132 Current consumption, typical: 9 mA at
1 DI4 11 M 24 V DC
+24 V DC 2 DI5 Level (incl. ripple):
12 DI/DO 10
3 DI6 High level: 15 V ... 30 V
4 DI7 13 DI/DO 11 Low level: -30 V ... +5 V
5 DI20
6 DI21
14 M Fast inputs: 2)
7 M2 DI/DO 8, 9, 10 and 11
8 M Input delay (typ.):
9 DI/DO12 at 0  1: 5 s
10 DI/DO13 at 1  0: 50 s
11 M
As output:
12 DI/DO14
13 DI/DO15 Voltage 24 V DC
Max. load current per output: 500 mA

-X41
14 M
Continuously short-circuit proof
Output delay (typ./max.): 3)
6
Function 1 EP M1 at 0  1: 150 s/400 s
STO/SS1 2 EP +24V at 1  0: 75 s/100 s
3 - Temp Switching frequency:
4 + Temp For resistive load: max. 100 Hz
For inductive load: max. 0.5 Hz
-X46
For lamp load: max. 10 Hz
Interface 1 BR Output + Max. lamp load: 5 W
2 BR Output -
Safe Brake
Adapter
3 FB Input + Max. connectable cross-section: 2.5 mm2
4 FB Input -

G_D213_EN_00071b

Interface to
Control Unit CU320-2
Interface to
Chassis Power Unit

Terminal assignment of customer terminal strip -X55

1)
DI: Digital input
DI/DO: Bidirectional digital input/output
M: Electronics ground
M1: Reference ground.
2)
Can be used as measuring probe input or input for the external zero mark.
3)
Data for: Ucc = 24 V; load 48 ; High (1) = 90 % Uout;
Low (0) = 10 % Uout.

Siemens D 21.3 · 2022 6/59


© Siemens 2022

SINAMICS S120 Cabinet Modules


Air-cooled units
Customer terminal strip -X55

■ Design
Terminal strip -X55-X132 digital inputs/outputs Terminal strip -X55-X41 temperature sensor connection
Terminal Designation 1) Technical data Terminal Function Technical data
1 DI 4 Voltage -30 V to +30 V DC 1 EP M1 Supply voltage 24 V DC (20.4 ... 28.8 V DC)
Current consumption, typical: 9 mA at (enable pulses) Current consumption: 10 mA
2 DI 5 24 V DC
2 EP +24 V Signal propagation times:
3 DI 6 Galvanic isolation: The reference potential (enable pulses) L  H: 100 s
4 DI 7 is terminal M2 H  L: 1000 s
Level (incl. ripple): The pulse inhibit function is only available
5 DI 20 High level: 15 V ... 30 V when Safety Integrated Basic Functions
6 DI 21 Low level: -30 V ... +5 V are enabled
Input delay (typ.): 3 -Temp Temperature sensor connection for motor
at 0  1: 50 s temperature sensing:
at 1  0: 150 s 4 +Temp KTY84-1C130, PTC, Pt100
7 M2 Reference potential for terminals 1 to 6
Max. connectable cross-section: 2.5 mm2
8 M Ground
Terminal strip -X55-X46 brake control and monitoring
9 DI/DO 12 As input:
Voltage -30 V ... +30 V DC Terminal Function Technical data
10 DI/DO 13
Current consumption, typical: 9 mA at 1 BR output + The interface is used to connect the
11 M 24 V DC Safe Brake Adapter
Level (incl. ripple): 2 BR output -
12 DI/DO 14
High level: 15 V ... 30 V 3 FB input +
13 DI/DO 15 Low level: -30 V ... +5 V
2) 4 FB input -
14 M Fast inputs:
DI/DO 12, 13, 14 and 15 Max. connectable cross-section: 2.5 mm2
Input delay (typ.):
at 0  1: 5 s
at 1  0: 50 s
As output:
Voltage 24 V DC
Max. load current per output: 500 mA
6 Continuously short-circuit proof
Output delay (typ./max.): 3)
at 0  1: 150 s/400 s
at 1  0: 75 s/100 s
Switching frequency:
For resistive load: max. 100 Hz
For inductive load: max. 0.5 Hz
For lamp load: max. 10 Hz
Max. lamp load: 5 W

Max. connectable cross-section: 2.5 mm2

1)
DI: Digital input
DI/DO: Bidirectional digital input/output
M: Electronics ground
M2: Reference ground.
2)
Can be used as measuring probe input or input for the external zero mark.
3)
Data for: Ucc = 24 V; load 48 ; High (1) = 90 % Uout; Low (0) = 10 % Uout.

6/60 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Cabinet Modules


Liquid-cooled units

■ Overview
To comply with high requirements regarding installation and
ambient conditions, SINAMICS S120 Cabinet Modules are also Basic Line Connection Module
available in a liquid-cooled version. Line Connection Module
The power loss of the units is transferred to the cooling liquid and Switch disconnector Main Basic Line
with fuses contactor Module
dissipated, without noticeably increasing the temperature of the
surrounding environment. As a consequence it is possible to
save the expense of controlling the climate of the electrical room.
The system consists of liquid-cooled Basic Line Connection = Motor
Modules, Active Line Connection Modules, Motor Modules, an Module
Auxiliary Power Supply Module, and a suitably selected cooling G_D213_EN_00105

unit (Heat Exchanger Module).


M
Basic Line Connection Modules 3
Basic Line Connection Modules comprise a Line Connection
Module and a liquid-cooled Basic Line Module. Basic Line Basic Line Connection Module  800 A
Connection Modules are only suitable for infeed operation,
i.e. they are not capable of feeding regenerative energy back
into the supply system. Basic Line Connection Module
Line Connection Module
If regenerative energy is produced, e.g. when the drives brake,
it must be converted into heat in external braking resistors using Circuit breaker Basic Line
Module
a supplementary Motor Module, which is used as Braking
Module.
When a Basic Line Connection Module is used as the infeed,
a line reactor appropriate for the supply conditions must be = Motor
installed. If the infeed is realized via a transformer with an Module
G_D213_EN_00106
appropriate rating in 6-pulse operation with a Basic Line
Connection Module or in 12-pulse operation with two Basic Line
Connection Modules, the line reactor is optional and can be M
omitted.
If two or more Basic Line Connection Modules are operated in
3
6
parallel on a common supply system in order to increase power, Basic Line Connection Module > 800 A
then line reactors must also be used.

Siemens D 21.3 · 2022 6/61


© Siemens 2022

SINAMICS S120 Cabinet Modules


Liquid-cooled units

■ Overview
Active Line Connection Modules
Active Line Connection Module
Active Line Connection Modules comprise a Line Connection
Module, a liquid-cooled Active Interface Module and a liquid- Line Connection Module
cooled Active Line Module. Active Line Connection Modules can Switch Bypass Active Active Line
supply energy to the DC link and return regenerative energy to disconnector contactor Interface Module
with fuses Module
the line supply (energy recovery). The use of an additional Motor
Module as a Braking Module is only required if the drives need
to be decelerated in a controlled manner after a power failure
(i.e. when energy cannot be fed back into the line supply).
=
Motor
In contrast to Basic Line Connection Modules, Active Line Module
Connection Modules generate a regulated DC voltage which G_D213_EN_00107
remains constant irrespective of fluctuations in the line voltage.
However, in this case, the line voltage must remain within the M
permissible tolerance range. Active Line Connection Modules 3
draw a virtually sinusoidal current from the supply system.
Almost no harmonics occur. The total harmonic distortion factors
Active Line Connection Module with Active Interface Module and Active
of the current THD(I) and voltage THD(U) are typically in the Line Module 800 A
range of approx. 3 % for rated current. THD(I) is calculated
according to IEEE 519 (2014) and THD(U) according to
IEC 61000-2-4 (2002). The stringent limit values of Active Line Connection Module
IEEE 519 (2014) are typically complied with. Line Connection Module
Active Line Connection Modules always contain an Active Active Active Line
Interface Module, which in addition to a Clean Power Filter, also Circuit breaker Interface Module
Module
includes the necessary pre-charging circuit for the Active Line
Module.
Active Line Connection Modules compact
=
Active Line Connection Modules compact comprise a liquid- Motor
cooled Active Interface Module and a liquid-cooled Active Line Module
6 Module. They can supply motoring energy to the DC link and
return regenerative energy to the line supply. The line-side
G_D213_EN_00108

M
infeed via main switch with fuse switch disconnector or circuit 3
breaker must be done on the plant side.
In contrast to Basic Line Connection Modules, Active Line Active Line Connection Module with Active Interface Module and Active
Connection Modules compact generate a regulated DC voltage Line Module >800 A
which remains constant irrespective of fluctuations in the line
voltage. However, in this case, the line voltage must remain
Active Line Connection Module compact
within the permissible tolerance range. Active Line Connection
Modules compact draw a virtually sinusoidal current from the Active Active Line
supply system. Almost no harmonics occur. The total harmonic Interface Module
Module
distortion factors of the current THD(I) and voltage THD(U) are
typically in the range of approx. 3 % for rated current. THD(I) is
calculated according to IEEE 519 (2014) and THD(U) according
to IEC 61000-2-4 (2002). The stringent limit values of
=
IEEE 519 (2014) are typically complied with. Motor
The line-side infeed via main circuit breaker with fuse switch Module
disconnector or circuit breaker must be carried out on the
plant side.
M
G_D213_XX_00148 3

Active Line Connection Module compact with Active Interface Module


and Active Line Module

6/62 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Cabinet Modules


Liquid-cooled units

■ Overview
Motor Modules Heat Exchanger Modules
Each Cabinet Module is fitted with one SINAMICS S120 Motor Heat Exchanger Modules are used to dissipate the power loss
Module in chassis format and covers the power range from from the converter. They comprise a deionized water circuit on
90 kW to 1500 kW (380 V to 480 V or 500 V to 690 V). The power the converter side and a raw water circuit on the plant side.
rating can be extended up to approx. 5700 kW by connection in
parallel. The hot deionized water in the circuit on the converter side
passes through a low-maintenance circulating pump(s) into the
The Motor Modules can also be used as Braking Modules water/water plate-type heat exchanger. This is made of stainless
(braking chopper) if a 3-phase braking resistor is connected steel and connected to the raw water circuit on the plant side.
instead of a motor. The deionized water is cooled there by the raw water of the outer
Further information can be found in the SINAMICS Low Voltage circuit and flows back into the drive.
Engineering Manual.
Auxiliary Power Supply Modules
Auxiliary Power Supply Modules supply power to the auxiliary
power supply system of the SINAMICS S120 Cabinet Modules.
The heat exchangers, which are installed in the SINAMICS S120
Cabinet Modules with degree of protection IP55, are one of the
connections to the auxiliary power supply system. In addition,
the auxiliary power supply system supplies the electronic
modules with an external 24 V DC voltage. This is required when
the DC link is not charged, for instance, in order to maintain
PROFIBUS or PROFINET communication.
The installation is analogous to the air-cooled Auxiliary Power
Supply Modules with an additional water pipe system.
The Auxiliary Power Supply Modules provide an expansion to
the option K76 (auxiliary voltage generating unit) if higher power
ratings are required.

Siemens D 21.3 · 2022 6/63


© Siemens 2022

SINAMICS S120 Cabinet Modules


Liquid-cooled units

■ Technical specifications
General technical specifications
Electrical specifications
Line voltages 380 ... 480 V 3 AC, ±10 % (-15 % <1 min)
500 … 690 V 3 AC, ±10 % (-15 % <1 min)
Line supply types Grounded TN/TT systems and non-grounded IT systems
Line frequency 47 ... 63 Hz
Output frequency 1)
• Control mode Servo 0 ... 550 Hz
• Control mode Vector 0 ... 550 Hz
• Control mode V/f 0 ... 550 Hz
Line power factor
Fundamental
• Basic Line Module >0.96
• Active Line Module Adjustable (factory-set to cos  = 1)
Efficiency
• Basic Line Module >99 %
• Active Line Module >97.5 % (including Active Interface Module)
• Motor Module >98.5 %
Overvoltage category III acc. to EN 61800-5-1
Control method Vector/Servo control with and without encoder or V/f control
Fixed speeds 15 fixed speeds plus 1 minimum speed, parameterizable (in the default setting, 3 fixed setpoints plus 1 minimum speed
are selectable using terminal strip/PROFIBUS/PROFINET)
Skippable speed ranges 4, parameterizable
Setpoint resolution 0.001 rpm digital (14 bits + sign)
12 bits analog
Braking operation With Active Line Modules, four-quadrant operation as standard (energy recovery).
6 With Basic Line Modules, two-quadrant operation as standard,
braking by means of a Motor Module.
Cabinet system
Cabinet system Rittal TS 8, doors with double-barb lock, base plate with cable entry options
Paint finish RAL 7035 (indoor requirements)
Mechanical specifications
Degree of protection IP21 (higher degrees of protection up to IP55 optional)
Protection class I acc. to EN 61800-5-1
Touch protection EN 50274/DGUV regulation 3 when used as intended
Cooling method Cooling in compliance with EN 60146:
Basic Line Connection Modules, Active Line Connection Modules, Motor Modules: WE
- W: Liquid cooling
- E: Forced air cooling, drive device outside the equipment
Line reactors, motor reactors, dv/dt filters with Voltage Peak Limiter: AN
- A: Air cooling
- N: Natural cooling (convection)

1)
Higher output frequencies available on request.

6/64 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Cabinet Modules


Liquid-cooled units

■ Technical specifications
Ambient conditions Storage 1) Transport 1) Operation
Ambient temperature -25 ... +55 °C (-13 ... 131 °F) -25 ... +70 °C (-13 ... +158 °F) 0 ... +45 °C (32 ... 113°F)
from -40 °C (-40 °F) for 24 hours to +50 °C (122 °F) see derating data
Relative humidity 5 ... 95 % 5 ... 95 % at 40 °C (104 °F) 5 ... 95 %
(condensation not permissible) Class 1K4 acc. to IEC 60721-3-1 (1997) Class 2K3 acc. to IEC 60721-3-2 (1997) Class 3K3 acc. to IEC 60721-3-3 (2002)
Environmental class/harmful Class 1C2 Class 2C2 Class 3C2
chemical substances acc. to EN 60721-3-1 (1997) acc. to EN 60721-3-2 (1997) acc. to EN 60721-3-3 (2002)
Organic/biological influences Class 1B1 Class 2B1 Class 3B1
acc. to EN 60721-3-1 (1997) acc. to EN 60721-3-2 (1997) acc. to EN 60721-3-3 (2002)
Mechanically active substances Class 1S1 Class 2S1 Class 3S1
acc. to EN 60721-3-1 (1997) acc. to EN 60721-3-2 (1997) acc. to EN 60721-3-3 (2002)
Degree of pollution 2 acc. to IEC/EN 61800-5-1
Installation altitude  2000 m (6562 ft) above sea level without derating; > 2000 m (6562 ft) see derating data
Mechanical stability Storage 1) Transport 1) Operation
Vibratory load Class 1M2 Class 2M2 –
acc. to EN 60721-3-1 (1997) acc. to EN 60721-3-2 (1997)
• Deflection 1.5 mm (0.06 in) at 5 ... 9 Hz 3.1 mm (0.12 in) at 5 ... 9 Hz 0.075 mm (0.003 in) at 10 ... 58 Hz
• Acceleration 5 m/s² (16.4 ft/s²) at >9 ... 200 Hz 10 m/s² (32.8 ft/s²) at >9 ... 200 Hz 9.8 m/s² (32.2 ft/s²) at >58 ... 200 Hz
Shock load Class 1M2 Class 2M2 Class 3M1
acc. to EN 60721-3-1 (1997) acc. to EN 60721-3-2 (1997) acc. to EN 60721-3-3 (2002)
• Acceleration 40 m/s² (131 ft/s²) at 22 ms 100 m/s² (328 ft/s²) at 11 ms Test values acc. to EN 60068-2-27
test Ea: 5 g, 30 ms, 3 shocks
Compliance with standards
Conformances/certificates of CE (EMC Directive 2014/30/EU, Low Voltage Directive 2014/35/EU, and Machinery Directive 2006/42/EC for functional
suitability, according to safety)
RCM, RoHS II, UKCA, marine certification DNV, CCS (Type approval, only in combination with the Option M66)
Green Passport: Option B50 creates a form for the material declaration according to Green Passport.
Radio interference suppression SINAMICS converter systems are not designed for connection to the public grid (first environment). Radio interference
suppression is compliant with the EMC product standard for variable-speed drives EN 61800-3, "Second environment"
6
(industrial networks). EMC disturbances can occur when connected to the public grid.

Deviations from the specified class are underlined.

1)
In transport packaging.

Siemens D 21.3 · 2022 6/65


© Siemens 2022

SINAMICS S120 Cabinet Modules


Liquid-cooled units

■ Technical specifications
Cooling circuit and coolant quality
The following tables and sections describe the coolant quality Converter-side deionized water circuit
requirements for the raw water circuit on the plant side and the
• System pressure with 600 kPa
deionized water circuit of the liquid-cooled SINAMICS S120 reference to atmospheric
Cabinet Modules on the converter side. pressure, max.
The coolant consists of a coolant basis and an additional • Pressure drop at rated 70 kPa
volumetric flow
antifreeze agent or inhibitor.
• Recommended pressure 80 ... 150 kPa (is applicable for water as
See "Antifreeze and inhibitors". range coolant)
Plant-side raw water circuit (based on VDI 3803) • Inlet temperature of liquid Depending on ambient temperature;
coolant no condensation permitted
• System pressure with 600 kPa Antifreeze essential for temperature range
reference to atmospheric between 0 °C (32 °F) and 5 °C (41 °F)
pressure, max.
- Degree of protection <IP55 0 ... 45 °C (32 ... 113 °F) without derating
• Inlet temperature of liquid Antifreeze essential for temperature range >45 ... 50 °C (113 ... 122 °F),
coolant between 0 °C (32 °F) and 5 °C (41 °F) see derating characteristics
- Degree of protection <IP55 0 ... 38 °C (32 ... 104 °F) without derating
>38 ... 43 °C (104 ... 131 °F), - Degree of protection IP55 0 ... 40 °C (32 ... 104 °F) without derating
see derating characteristics >40 ... 45 °C (104 ... 113 °F),
- Degree of protection IP55 0 ... 33 °C (32 ... 104 °F) without derating see derating characteristics
>33 ... 38 °C (104 ... 131 °F),
see derating characteristics Coolant quality
• Coolant basis Distilled, demineralized, completely
Coolant quality desalinated water or deionized water with
• Electrical conductivity < 2200 S/cm reduced electrical conductivity ISO 3696,
• pH value 7.5 ... 9 quality 3 or based on IEC 60993
• Chloride (Cl-) < 180 mg/l • Electrical conductivity <30 S/cm (3 mS/m)
• Sulfate (SO42-) <200 mg/l when filling
• Orthophosphate <50 mg/l • pH value 5 ... 8
• Dissolved iron < 3 mg/l • Components that can <30 mg/l
be oxidized as oxygen
• Dissolved copper < 0.2 mg/l content
• Biological load < 50 CFU/ml • Residue after vaporization <10 mg/kg
6 • SiO2 as silicic acid
• Aluminum
< 47 mg/l
< 2.65 mg/l
and drying at 110 °C (230 °F)

• Fluoride < 4 mg/l The coolant definition specified here should only be considered
• Total hardness < 20 (< 40 °C (104 °F)) °dH as recommendation. For units that have been shipped, the
• Size of entrained particles  0.5 mm (0.02 in) information and data provided in the equipment manual
• SK 4.3 (upper limit value of < 10 mmol/l supplied should be observed!
polymer phosphates for
untreated additional water)
• Permissible limit values for No deposits of solid particles at  0.5 m/s
suspended particles in the
coolant

6/66 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Cabinet Modules


Liquid-cooled units

■ Technical specifications
Antifreeze and inhibitors Recommended service
Antifreeze Antifrogen N Antifrogen L DOWCAL 100 The manufacturer of the antifreeze/inhibitor should analyze
the coolant at least once per annum. The concentration and
Manufacturer Clariant Clariant DOW
boundary conditions of the antifreeze/inhibitor should be
Chemical base Ethylene glycol Propylene Ethylene checked. It may be necessary to correct the concentration
glycol glycol on the plant side.
Minimum concentration 25 % 25 % 25 %
Antifreeze agent with -10 °C (14 °F) -10 °C (14 °F) -10 °C (14 °F)
minimum concentration
Maximum concentration 45 % 48 % 45 %
Antifreeze agent with -30 °C (-22 °F) -30 °C (-22 °F) -30 °C (-22 °F)
maximum concentration
Inhibitor content Contains inhibi- Contains Contains
tors with nitrites inhibitors that inhibitors that
are free of are free of
nitrites, amines, nitrites, amines,
borates, and and phosphate
phosphate
Biocide action with >25 % >25 % >25 %
a concentration of

Biocides prevent corrosion that is caused by slime-forming,


corrosive or iron-depositing bacteria. These can occur in closed
cooling circuits with low water hardness and in open cooling
circuits. Biocides must always be selected according to the
relevant bacterial risks. Compatibility with inhibitors or antifreeze
used with them must be checked on a case-by-case basis.
Inhibitors Antifrogen N ANTICORIT S 200 A
Manufacturer Clariant Fuchs
Chemical base Ethylene glycol - 6
Minimum concentration 25 % 4%
Maximum concentration 45 % 5%

Siemens D 21.3 · 2022 6/67


© Siemens 2022

SINAMICS S120 Cabinet Modules


Liquid-cooled units

■ Technical specifications
Protection against condensation The temperature at which water vapor contained in the air
condenses into water is known as the dew point. In order to
With liquid-cooled units, warm air can condense on the cold reliably prevent condensation, the coolant temperature must
surfaces of heat sinks, pipes and hoses. This condensation always be higher than the dew point.
depends on the air humidity and the temperature difference
between the ambient air and the coolant. The table below specifies the dew point as a function of room
temperature T and relative air humidity  for an atmospheric
The water which is produced as a result of condensation can pressure of 100 kPa (1 bar). This corresponds to an installation
cause corrosion as well as electrical damage such as creepage altitude of 0 to approximately 500 m above sea level. Since the
shorts and flashovers. As the SINAMICS units cannot prevent dew point drops as the air pressure decreases, the dew point
condensation if it is caused by the prevailing climatic conditions, values at higher installation altitudes are lower than the specified
any potential risk of condensation must be prevented by table values. It is therefore the safest approach to engineer the
appropriate engineering or by precautionary measures coolant temperature according to the table values for an
implemented by the customer. These measures include installation altitude of zero.
the following:
• a fixed coolant temperature that has been adjusted to the
expected air humidity or ambient temperature ensures that
critical differences between the coolant and ambient air
temperatures do not develop or
• temperature regulation of the coolant as a function of the
ambient air temperature
Indication of dew point temperature / coolant temperature
Room Relative air humidity 
temperature
T 20 % 30 % 40 % 50 % 60 % 70 % 80 % 85 % 90 % 95 % 100 %
10 °C <0 °C <0 °C <0 °C 0.2 °C 2.7 °C 4.8 °C 6.7 °C 7.6 °C 8.4 °C 9.2 °C 10 °C
(50 °F) (<32 °F) (<32 °F) (<32 °F) (32.4 °F) (36.9 °F) (40.6 °F) (44.1 °F) (45.7 °F) (47.1 °F) (48.6 °F) (50 °F)
20 °C <0 °C 2 °C 6 °C 9.3 °C 12 °C 14.3 °C 16.4 °C 17.4 °C 18.3 °C 19.1 °C 20 °C
(68 °F) (<32 °F) (35.6 °F) (42.8 °F) (48.7 °F) (53.6 °F) (57.7 °F) (61.5 °F) (63.3 °F) (64.9 °F) (66.4 °F) (68 °F)
6 25 °C
(77 °F)
0.6 °C
(33.1 °F)
6.3 °C
(43.3 °F)
10.5 °C
(50.9 °F)
13.8 °C
(56.8 °F)
16.7 °C
(62.1 °F)
19.1 °C
(66.4 °F)
21.2 °C
(70.2 °F)
22.2 °C
(72.0 °F)
23.2 °C
(73.8 °F)
24.1 °C
(75.4 °F)
24.9 °C
(76.8 °F)
30 °C 4.7 °C 10.5 °C 14.9 °C 18.4 °C 21.3 °C 23.8 °C 26.1 °C 27.1 °C 28.1 °C 29 °C 29.9 °C
(86 °F) (40.5 °F) (50.9 °F) (58.8 °F) (65.1 °F) (70.3 °F) (74.8 °F) (79.0 °F) (80.8 °F) (82.6 °F) (84.2 °F) (85.8 °F)
35 °C 8.7 °C 14.8 °C 19.3 °C 22.9 °C 26 °C 28.6 °C 30.9 °C 32 °C 33 °C 34 °C 34.9 °C
(95 °F) (47.7 °F) (58.6 °F) (66.7 °F) (73.2 °F) (78.8 °F) (83.5 °F) (87.6 °F) (89.6 °F) (91.4 °F) (93.2 °F) (94.8 °F)
40 °C 12.8 °C 19.1 °C 23.7 °C 27.5 °C 30.6 °C 33.4 °C 35.8 °C 36.9 °C 37.9 °C 38.9 °C 39.9 °C
(104 °F) (55.0 °F) (66.4 °F) (74.7 °F) (81.5 °F) (87.1 °F) (92.1 °F) (96.4 °F) (98.4 °F) (100 °F) (102 °F) (104 °F)
45 °C 16.8 °C 23.3 °C 28.2 °C 32 °C 35.3 °C 38.1 °C 40.6 °C 41.8 °C 42.9 °C 43.9 °C 44.9 °C
(113 °F) (62.2 °F) (73.9 °F) (82.8 °F) (89.6 °F) (95.5 °F) (101 °F) (105 °F) (107 °F) (109 °F) (111 °F) (113 °F)
50 °C 20.8 °C 27.5 °C 32.6 °C 36.6 °C 40 °C 42.9 °C 45.5 °C 46.6 °C 47.8 °C 48.9 °C 49.9 °C
(122 °F) (69.4 °F) (81.5 °F) (90.7 °F) (97.9 °F) (104 °F) (109 °F) (114 °F) (116 °F) (118 °F) (120 °F) (122 °F)

A detailed description of the cooling circuits and the


recommended coolant is given in the SINAMICS Low Voltage
Engineering Manual.

6/68 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Cabinet Modules


Liquid-cooled units

■ Characteristic curves
Derating
110
Liquid-cooled SINAMICS S120 Cabinet Modules are rated for an
100
ambient temperature of 45 °C and installation altitudes up to

Rated current %
2000 m above sea level and a plant-side raw water temperature 90
of 38 °C (<IP55) or 33 °C (IP55). At ambient temperatures 80
> 45 °C and a plant-side raw water temperature > 38 °C (<IP55) 70
or 33 °C (IP55), the output current must be reduced. Ambient
60
temperatures above 50 °C are not permissible. At installation
altitudes > 2000 m above sea level, it must be taken into account 50
that the air pressure, and therefore air density, decreases as the 40
height increases. As a consequence, the cooling efficiency and

G_D213_EN_00038
30
the insulation capacity of the air also decrease.
20
At installation altitudes above 2000 m, the line voltage must not 10
exceed certain limits in order to be able to isolate the surge
0
voltages according to IEC 61800-5-1 for overvoltage -5 0 10 20 30 40 50 60
category III. If the line voltage is above this limit at installation (23) (32) (50) (68) (86) (104) (122) (140)
altitudes > 2000 m, measures must be taken to reduce the Ambient temperature °C (°F)
transient overvoltages of Category III to values of Category II,
e. g. supply of the devices via an isolating transformer.
Current derating as a function of ambient temperature 1)
For additional information, please refer to the SINAMICS Low
Voltage Engineering Manual.
The intake temperatures in the plant/system side raw water 50
circuit must always be at least 7 K below the intake temperatures Permissible ambient temperature (air) °C (°F) (122)
in the converter-side deionized water circuit. This ensures that
the cooling power of the Heat Exchanger Module of the 40
(104)
deionized water circuit, specified in the technical data, can be
dissipated to the raw water circuit. 30
(86)
In order to prevent condensation, the inlet temperature of the
liquid coolant should be kept above the ambient temperature
depending on the relative air humidity.
20
(68) 6

G_D213_EN_00072
For additional information, please refer to the SINAMICS Low 10
Voltage Engineering Manual. (50)

0
(32) 0 1000 2000 3000 4000
(3281) (6562) (9843) (13124)
100 Installation altitude above sea level m (ft)
Output current %

90 Ambient temperature Tmax at I = 100 %


80 Ambient temperature Tmax at I = 90 %

70
60 Permissible ambient temperature as a function of installation altitude
IP55 < IP55
50
40
G_D213_EN_00109

30
20
10
0
-5 0 10 20 30 40 45 50 60
(23) (32) (50) (68) (86) (104) (113)(122) (140)
Coolant temperature °C (°F)
Without antifreeze
With antifreeze

Current derating as a function of the temperature of the cooling liquid in


the converter-side deionized water circuit 1),
The inlet temperature of the liquid coolant depends on the ambient
temperature, no condensation permitted.

1) The factors of the two derating curves must not be multiplied. The highest
value in each case must be assumed for the purposes of calculation, so
that the derating factor in the worst-case scenario is 0.9.

Siemens D 21.3 · 2022 6/69


© Siemens 2022

SINAMICS S120 Cabinet Modules


Liquid-cooled units

■ Characteristic curves
Current derating as a function of the pulse frequency For additional information, please refer to the SINAMICS Low
Voltage Engineering Manual.
To reduce motor noise or to increase output frequency, the pulse
frequency can be increased relative to the factory setting The following table lists the rated output currents of the Motor
(1.25 kHz or 2 kHz). When the pulse frequency is increased, the Modules with pulse frequency set at the factory as well as the
derating factor of the output current must be taken into account. current derating factors (permissible output currents referred to
This derating factor must be applied to the currents specified in the rated output current) for higher pulse frequencies.
the technical data.
Derating factor of the output current as a function of the pulse frequency for units with a rated pulse frequency of 2 kHz
Motor Module Type rating Output current Derating factor
at 400 V at 2 kHz at pulse frequency
6SL3725-... kW A 2.5 kHz 4 kHz 5 kHz 7.5 kHz 8 kHz
380 ... 480 V 3 AC / 510 ... 720 V DC
1TE32-1AA3 110 210 95 % 82 % 74 % 54 % 50 %
1TE32-6AA3 132 260 95 % 83 % 74 % 54 % 50 %
1TE33-1AA3 160 310 97 % 88 % 78 % 54 % 50 %
1TE35-0AA3 250 490 94 % 78 % 71 % 53 % 50 %
1TE41-4AS3 1) 800 1330 88 % 55 % – – –

Derating factor of the output current as a function of the pulse frequency for units with a rated pulse frequency of 1.25 kHz
Motor Module Type rating at Output current Derating factor
400 V or 690 V at 1.25 kHz at pulse frequency
6SL3725-... kW A 2 kHz 2.5 kHz 4 kHz 5 kHz 7.5 kHz 8 kHz
380 ... 480 V 3 AC / 510 ... 720 V DC
1TE36-1AA3 315 605 83 % 72 % 64 % 60 % 40 % 36 %
1TE37-5AA3 400 745 87 % 79 % 64 % 55 % 40 % 37 %
6 1TE38-4AA3 450 840 87 % 79 % 64 % 55 % 40 % 37 %
1TE41-0AA3 560 985 92 % 87 % 70 % 60 % 50 % 47 %
1TE41-2AA3 710 1260 97 % 95 % 74 % 60 % 50 % 47 %
1TE41-4AA3 800 1405 97 % 95 % 74 % 60 % 50 % 47 %
500 ... 690 V 3 AC / 675 ... 1035 V DC
1TG31-0AA3 90 100 92 % 88 % 71 % 60 % 40 % -
1TG31-5AA3 132 150 90 % 84 % 66 % 55 % 35 % -
1TG32-2AA3 200 215 92 % 87 % 70 % 60 % 40 % -
1TG33-3AA3 315 330 89 % 82 % 65 % 55 % 40 % -
1TG34-7AA3 450 465 92 % 87 % 67 % 55 % 35 % -
1TG35-8AA3 560 575 91 % 85 % 64 % 50 % 35 % -
1TG37-4AA3 710 735 84 % 74 % 53 % 40 % 25 % -
1TG38-0AA3 800 2) 810 82 % 71 % 52 % 40 % 25 % -
1TG38-1AA3 800 810 97 % 95 % 71 % 55 % 35 % -
1TG41-0AA3 1000 1025 91 % 86 % 64 % 50 % 30 % -
1TG41-3AA3 1200 1270 87 % 79 % 55 % 40 % 25 % -
1TG41-6AA3 1500 1560 87 % 79 % 55 % 40 % 25 % -

1) This Motor Module has been specifically designed for loads demanding 2) The Motor Module 6SL3725-1TG38-0AA3 is optimized for low overload;
a high dynamic performance. The derating factor kIGBT and the derating with an increased pulse frequency, the derating factor is higher than for the
characteristics can be ignored Motor Module 6SL3725-1TG38-1AA3
(see section “Duty cycles” in the SINAMICS Low Voltage Engineering
Manual)..

6/70 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Cabinet Modules


Liquid-cooled units

■ Characteristic curves
Maximum output frequencies achieved by increasing the pulse frequency
The adjustable pulse frequencies – and therefore the output
frequencies that can be achieved with the factory-set current
controller clock cycles – are listed below.
Current controller clock cycle Adjustable pulse frequency Max. achievable output frequency fA
TI fp
V/f mode Vector mode Servo mode
250 µs 1) 2 kHz 166 Hz 166 Hz 333 Hz
4 kHz 333 Hz 333 Hz 550 Hz 3)
8 kHz 550 Hz 3) 480 Hz 550 Hz 3)
400 µs 2) 1.25 kHz 104 Hz 104 Hz –
2.5 kHz 208 Hz 208 Hz –
5.0 kHz 416 Hz 300 Hz –
7.5 kHz 550 Hz 3) 300 Hz –

1) 3)
As factory setting, the following devices have a current controller clock With the "High output frequencies" license, which can be ordered as option
cycle of 250 µs and a pulse frequency of 2 kHz: J01 on the CompactFlash card for SINAMICS S120, the maximum output
- 510 ... 720 V DC:  250 kW / 490 A, 6SL3725-1TE41-4AS3 frequency is increased up to 650 Hz. For more information, see
2)
As factory setting, the following devices have a current controller clock https://support.industry.siemens.com/cs/document/104020669
cycle of 400 µs and a pulse frequency of 1.25 kHz:
- 510 ... 720 V DC:  315 kW / 605 A, except 6SL3725-1TE41-4AS3,
- 675 ... 1035 V DC: All power ratings

Siemens D 21.3 · 2022 6/71


© Siemens 2022

SINAMICS S120 Cabinet Modules


Liquid-cooled units

■ Characteristic curves
Overload capability The following applies to the Motor Module 6SL3725-1TG41-6AP3:
This Motor Module is particularly suited to high breakaway torques
SINAMICS S120 Cabinet Modules have an overload reserve, with applications such as drilling, mixers, centrifuges, and test
e.g. to handle breakaway torques. If larger surge loads occur, bays. An additional duty cycle is required at output frequencies
this must be taken into account in the configuration. For drives of 5 Hz to 10 Hz.
with overload requirements, the appropriate base load current At output frequencies of 1 Hz to 5 Hz, the short-time current is
must, therefore, be used as a basis for the required load. 1900 A for 5 s.
Permissible overload assumes that the converter is operated at
its base-load current before and after the overload occurs, Converter current
based on a duty cycle duration of 300 s.
5s
A
Another precondition is that the Motor Modules are operated at
2340 Short-time current
their factory-set pulse frequency at output frequencies >10 Hz.
For temporary, periodic duty cycles with high variations of load
within the duty cycle, the relevant sections of the SINAMICS Low
Voltage Engineering Manual must be observed. Rated current (continuous)

Motor Modules
Base-load current
Motor Modules can be configured on the basis of different base
load currents. IN

G_D213_EN_00116
The base-load current for a low overload IL is the basis for a duty 1460
cycle of 110 % for 60 s or 150 % for 10 s.
600 s

Converter current
10 s t
1.5 x IL
High overload for Motor Module 6SL3725-1TG41-6AP3
Short-time current 150 %
Basic Line Connection Modules and Active Line Connection
6 Short-time current 110 %
Rated current (continuous)
Modules
The base-load current for a high overload IH DC is the basis for
Base-load current IL a duty cycle of 150 % for 60 s or Imax DC for 5 s.
1.1 x IL
for low overload
IN Converter current
IL
G_D213_EN_00035

5s
60 s
300 s Imax DC Short-time current Imax

1.5 x IH DC Short-time current 150 %

t
Rated current (continuous)

Low overload Base-load current IH DC


for high overload
The base-load current IH for a high overload is based on a load IN DC
cycle of 150 % for 60 s or 160 % for 10 s.
IH DC G_D213_EN_00079

Converter current 60 s
300 s
10 s
1.6 x IH Short-time current 160 %
1.5 x IH Short-time current 150 % t

Rated current (continuous)


High overload

Base-load current IH for high overload


IN

IH
G_D213_EN_00036

60 s
300 s

High overload

6/72 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Cabinet Modules


Liquid-cooled units
Basic Line Connection Modules

■ Overview ■ Design
Depending on the input current, the following versions are
available:
•  800 A: Main circuit breaker with fuse switch disconnector
• > 800 A: Circuit breaker, type 3WL, with option L25 as
withdrawable circuit breaker
A fully controlled thyristor bridge is used to pre-charge the Basic
Line Connection Module and the connected DC link.
The thyristors normally operate with a trigger delay angle of 0°.
The power rating can be increased by connecting Basic Line
Connection Modules in parallel. You must observe the following
rules:
• Up to four identical Active Line Connection Modules can be
connected in parallel.
• A common Control Unit is required whenever the modules are
connected in parallel.
• The parallel connection must be supplied from a common
infeed point (i.e. the modules cannot be operated on different
line supplies). For information on using line reactors,
see section Basic Line Connection Modules  Overview.
• A derating factor of 7.5 % must be taken into consideration,
regardless of the number of modules connected in parallel.
• The main contactors or circuit breakers of the respective Line
Basic Line Connection Modules are compact line infeeds for Connection Modules must close together and simultaneously.
two-quadrant operation, i.e. no regenerative feedback. They are Monitoring is performed via the -X50 terminals of the
used when energy need not be fed back into the network. respective Line Connection Module.
• Option M88 must be ordered.
Basic Line Connection Modules comprise a Line Connection
Module and a liquid-cooled Basic Line Module.
As standard, the Basic Line Connection Module is positioned in
For additional information, please refer to the SINAMICS Low
Voltage Engineering Manual. 6
the drive line-up so that the Motor Modules are arranged to the
right. If Motor Modules are to be arranged to the left of the Basic ■ Selection and ordering data
Line Connection Module, option M88 (DC bus system for line-
side Cabinet Modules) must be ordered. Rated power Rated DC link current Basic Line Connection
at 400 V or 690 V Module
Line Connection Modules contain the line-side infeed via main kW A Article No.
breaker with fuse switch disconnector or circuit breaker and
establish the connection between the plant power system and Line voltage 380 ... 480 V 3 AC
(DC link voltage 510 ... 650 V DC)
the Basic Line Modules. They are equipped as standard with
a radio interference suppression filter according to 360 740 6SL3735-1TE37-4LA3
EN 61800-3 Category C3. 600 1220 6SL3735-1TE41-2LA3
Under full load, the DC link voltage is higher than the rms value 830 1730 6SL3735-1TE41-7LA3
of the rated line voltage by a factor of 1.32, and under partial Line voltage 500 ... 690 V 3 AC
load by a factor of 1.35. (DC link voltage 675 ... 930 V DC)
If regenerative conditions occur in the drive line-up, a Motor 355 420 6SL3735-1TG34-2LA3
Module can be used as braking chopper, which then converts 630 730 6SL3735-1TG37-3LA3
excess energy to heat in a braking resistor.
1100 1300 6SL3735-1TG41-3LA3
Basic Line Connection Modules are suitable for connection to
1370 1650 6SL3735-1TG41-7LA3
grounded TN/TT and non-grounded IT systems. The following
voltages and power ratings are available:
Line voltage Rated input current Rated power
380 ... 480 V 3 AC 610 ... 1420 A 360 ... 830 kW
500 ... 690 V 3 AC 340 ... 1350 A 355 ... 1370 kW

For a Basic Line Connection Module a line reactor should be


provided at the connection point depending on the line short-
circuit power. This reactor is available as standard.
However, it can be omitted if it is not required (option L22).
Further information can be found in the SINAMICS Low Voltage
Engineering Manual.

Siemens D 21.3 · 2022 6/73


© Siemens 2022

SINAMICS S120 Cabinet Modules


Liquid-cooled units
Basic Line Connection Modules

■ Integration
Cabinet Module

DC busbar

230 V AC
24 V DC
Auxiliary power
-F160

-F150
supply
X400 X401 X402

Basic Line

DRIVE-CLiQ socket 1
DRIVE-CLiQ socket 0

DRIVE-CLiQ socket 2
Line Connection
Module
Module
-X9
1 P24 V
=
1
2 M =
1 1 2
Internal READY
3

LEDs
power supply DC LINK
4
5 POWER OK
Bypass
6 contactor
7 control
8 IPD card

6 -X41
4 ~ DCP
+Temp DCN
3 -Temp =
2 EP +24 V DC fuses
1 EP M1 N52

-X42
1 P24L
2 P24L
3
M
4
M Cooling circuit
Line reactor
L1 U1 -X1
Line infeed L2 V1
L3 W1
PE

Cooling circuit

G_D213_EN_00104b

1 Door fan -G160 (IP21, IP23, IP43, IP54) or heat exchanger -E160 (IP55)

Connection example of the Basic Line Connection Module, liquid-cooled

6/74 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Cabinet Modules


Liquid-cooled units
Basic Line Connection Modules

■ Technical specifications
Line voltage 380 ... 480 V 3 AC Basic Line Connection Modules
6SL3735-1TE37-4LA3 6SL3735-1TE41-2LA3 6SL3735-1TE41-7LA3
Rated power
• At IN DC (50 Hz 400 V) kW 360 600 830
• At IH DC (50 Hz 400 V) kW 280 450 650
• At IN DC (60 Hz 460 V) hp 555 925 1280
• At IH DC (60 Hz 460 V) hp 430 690 1000
DC link current
• Rated current IN DC A 740 1220 1730
• Base-load current IH DC 1) A 578 936 1350
• Maximum current Imax DC A 1110 1830 2595
Input current
• Rated current IN I A 610 1000 1420
• Maximum current Imax I A 915 1500 2130
Current demand
• 24 V DC auxiliary power supply A 0.8 0.8 0.8
• 230 V 1 AC A 1.2 1.2 1.2
DC link capacitance
• Basic Line Module F 12000 20300 26100
• Drive line-up, max. F 96000 162400 208800
Power loss, max. 2)
at 50 Hz 400 V
• Degree of protection <IP55
- Dissipated to coolant kW 2.7 4.4 5.8
- Dissipated to ambient air kW 2.7 3.5 4.2
• Degree of protection IP55
- Dissipated to coolant kW 4.9 7.4 9.5
- Dissipated to ambient air kW 0.5 0.5 0.5
Coolant volume flow 3) l/min (US 9/36 (2.38/9.51) 9/36 (2.38/9.51) 12/39 (3.17/10.3)
Degree of protection <IP55/IP55 gal./min)
Liquid volume dm3 6.6/10.2 6.6/10.2 6.9/10.5
Degree of protection <IP55/IP55
Pressure drop, max. 4) Pa 150000 150000 150000
6
for volume flow
Heat exchanger material Aluminum Aluminum Aluminum
Sound pressure level LpA dB 54 56 56
(1 m) at 50/60 Hz
Line supply connection 4 x M12 10 x M12 10 x M12
L1, L2, L3
• Conductor cross-section, max. (IEC) mm2 4 × 240 8 × 240 10 × 240
PE/GND connection PE bar PE bar PE bar
• Busbar cross-section mm2 600 600 600
• Conductor cross-section, max. (IEC) mm2 240 240 240
Cable length, max. 5)
Shielded/unshielded m (ft) 2600/3900 (8531/12796) 4000/6000 (13124/19686) 4800/7200 (15749/23623)
Degree of protection IP21 IP21 IP21
(standard version)
Dimensions
• Width mm (in) 1000 (39.4) 1000 (39.4) 1000 (39.4)
• Height mm (in) 2200 (86.6) 2200 (86.6) 2200 (86.6)
• Depth mm (in) 600 (23.6) 600 (23.6) 600 (23.6)
Weight, approx. kg (lb) 688 (1517) 838 (1847) 995 (2194)
(standard version)
Frame size
• Line Connection Module HL JL JL
• Basic Line Module FBL FBL GBL
Rated short-circuit current kA 65 84 100
according to IEC
Minimum short-circuit current 6) kA 8.8 2 3.2

1) 4)
The base-load current IH DC is the basis for a duty cycle of 150 % for The value is valid for water as coolant.
60 s or Imax DC for 5 s with a duty cycle duration of 300 s. Additional information and notes on other coolants are provided in the
2)
The specified power loss represents the maximum value at 100 % SINAMICS Low Voltage Engineering Manual.
5)
utilization. The value is lower under normal operating conditions. Total of all motor cables and DC link. Longer cable lengths for specific
3)
The value applies to coolants comprising water and a mixture of water configurations are available on request.
6)
and antifreeze agent. Current required for reliably triggering protective devices.

Siemens D 21.3 · 2022 6/75


© Siemens 2022

SINAMICS S120 Cabinet Modules


Liquid-cooled units
Basic Line Connection Modules

■ Technical specifications
Line voltage 500 ... 690 V 3 AC Basic Line Connection Modules
6SL3735-1TG34-2LA3 6SL3735-1TG37-3LA3 6SL3735-1TG41-3LA3 6SL3735-1TG41-7LA3
Rated power
• At IN DC (50 Hz 690 V) kW 355 630 1100 1370
• At IH DC (50 Hz 690 V) kW 275 475 840 1070
• At IN DC (50 Hz 500 V) kW 245 420 750 950
• At IH DC (50 Hz 500 V) kW 200 345 610 775
• At IN DC (60 Hz 575 V) hp 395 705 1230 1530
• At IH DC (60 Hz 575 V) hp 305 530 940 1195
DC link current
• Rated current IN DC A 420 730 1300 1650
• Base-load current IH DC 1) A 328 570 1014 1287
• Maximum current Imax DC A 630 1095 1950 2475
Input current
• Rated current IN I A 340 600 1070 1350
• Maximum current Imax I A 510 900 1605 2025
Current demand
• 24 V DC auxiliary power supply A 0.8 0.8 0.8 0.8
• 230 V 1 AC A 1.2 1.2 1.2 1.2
DC link capacitance
• Basic Line Module F 4800 7700 15500 19300
• Drive line-up, max. F 38400 61600 124000 154400
Power loss, max. 2)
at 50 Hz 690 V
• Degree of protection <IP55
- Dissipated to coolant kW 1.8 2.7 4.7 5.7
- Dissipated to ambient air kW 2.3 2.7 3.3 5.1
• Degree of protection IP55
- Dissipated to coolant kW 3.3 4.9 7.5 10.3
- Dissipated to ambient air kW 0.5 0.5 0.5 0.5
Coolant volume flow 3) l/min (US 9/36 (2.38/9.51) 9/36 (2.38/9.51) 12/39 (3.17/10.3) 12/39 (3.17/10.3)

6 Degree of protection <IP55/IP55


Liquid volume
gal./min)
dm3 6.6/10.2 6.6/10.2 6.9/10.5 6.9/10.5
Degree of protection <IP55/IP55
Pressure drop, max. 4) Pa 150000 150000 150000 150000
for volume flow
Heat exchanger material Aluminum Aluminum Aluminum Aluminum
Sound pressure level LpA dB 54 54 56 56
(1 m) at 50/60 Hz
Line supply connection 2 x M12 4 x M12 10 x M12 10 x M12
L1, L2, L3
• Conductor cross-section, max. (IEC) mm2 2 × 150 4 × 240 8 × 240 8 × 240
PE/GND connection PE bar PE bar PE bar PE bar
• Busbar cross-section mm2 600 600 600 600
• Conductor cross-section, max. (IEC) mm2 240 240 240 240
Cable length, max. 5)
Shielded/unshielded m (ft) 1500/2250 (4921/7382) 1500/2250 (4921/7382) 2250/3375 (7382/11073) 2250/3375 (7382/11073)
Degree of protection IP21 IP21 IP21 IP21
(standard version)
Dimensions
• Width mm (in) 1000 (39.4) 1000 (39.4) 1000 (39.4) 1000 (39.4)
• Height mm (in) 2200 (86.6) 2200 (86.6) 2200 (86.6) 2200 (86.6)
• Depth mm (in) 600 (23.6) 600 (23.6) 600 (23.6) 600 (23.6)
Weight, approx. kg (lb) 578 (1274) 668 (1473) 995 (2194) 1025 (2260)
(standard version)
Frame size
• Line Connection Module GL HL JL JL
• Basic Line Module FBL FBL GBL GBL
Rated short-circuit current kA 65 84 100 100
according to IEC
Minimum short-circuit current 6) kA 4.4 7.2 2.5 3.2

1) The base-load current IH DC is the basis for a duty cycle of 150 % for 4) The value is valid for water as coolant.
60 s or Imax DC for 5 s with a duty cycle duration of 300 s. Additional information and notes on other coolants are provided in the
2) The specified power loss represents the maximum value at 100 % SINAMICS Low Voltage Engineering Manual.
utilization. The value is lower under normal operating conditions. 5) Total of all motor cables and DC link. Longer cable lengths for specific
3) The value applies to coolants comprising water and a mixture of water configurations are available on request.
and antifreeze agent. 6) Current required for reliably triggering protective devices.

6/76 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Cabinet Modules


Liquid-cooled units
Active Line Connection Modules

■ Overview ■ Design
Active Line Connection Modules always include an Active
Interface Module, which contains the associated Clean Power
Filter and pre-charging circuit. The line filter that is included
ensures compliance with the EMC requirements for the “second
environment”.
Depending on the input current, the following versions are
available:
•  800 A: Main circuit breaker with fuse switch disconnector
• > 800 A: Circuit breaker, type 3WL, with option L25 as
withdrawable circuit breaker
The power rating can be increased by connecting Active Line
Connection Modules in parallel. You must observe the following
rules:
• Up to four identical Active Line Connection Modules can be
connected in parallel.
• A common Control Unit is required whenever the modules are
connected in parallel.
• The parallel connection must be supplied from a common
infeed point (i.e. the modules cannot be operated on different
line supplies).
• A derating factor of 5% must be taken into consideration,
Active Line Connection Modules comprise a Line Connection
regardless of the number of modules connected in parallel.
Module, a liquid-cooled Active Interface Module and a liquid-
cooled Active Line Module. They can supply motoring energy to • The main contactors or circuit breakers of the respective Line
the DC link and return regenerative energy to the line supply. Connection Modules must close together and simultaneously.
Monitoring is performed via the -X50 terminals of the
As standard, the Active Line Connection Module is positioned in respective Line Connection Module.
the drive line-up so that the Motor Modules are arranged to the
right. If Motor Modules are to be arranged to the left of the Active For additional information, please refer to the SINAMICS Low
Line Connection Module, option M88 (DC bus system for line- Voltage Engineering Manual. 6
side Cabinet Modules) must be ordered.
Line Connection Modules contain the line-side infeed via main ■ Selection and ordering data
breaker with fuse switch disconnector or circuit breaker and
Rated power Rated DC link current Active Line Connection
establish the connection between the plant power system and at 400 V or 690 V Module
the Active Line Modules. They are equipped as standard
with a radio interference suppression filter according to kW A Article No.
EN 61800-3 Category C3. Line voltage 380 ... 480 V 3 AC
(DC link voltage 570 ... 720 V DC)
Active Line Connection Modules produce a stabilized DC
voltage that remains constant regardless of fluctuations in the 380 677 6SL3735-7TE36-1LA3
line voltage (the line voltage must remain within the permissible 500 941 6SL3735-7TE38-4LA3
tolerances). 630 1100 6SL3735-7TE41-0LA3
In the factory setting, the DC voltage is regulated to 1.5 times the 900 1573 6SL3735-7TE41-4LA3
rms value of the rated line voltage.
Line voltage 500 ... 690 V 3 AC
Active Line Connection Modules draw a virtually sinusoidal (DC link voltage 750 ... 1035 V DC)
current from the supply system and cause virtually no line 800 823 6SL3735-7TG37-4LA3
harmonics.
900 907 6SL3735-7TG38-1LA3
Active Line Connection Modules are suitable for connection 1100 1147 6SL3735-7TG41-0LA3
to supply systems grounded at the neutral point (TN, TT) and
non-grounded (IT) supply systems. The following voltages and 1400 1422 6SL3735-7TG41-3LA3
currents are available: 1700 1740 6SL3735-7TG41-6LA3

Line voltage Rated infeed/ Rated power


regenerative
feedback current
380 ... 480 V 3 AC 605 ... 1405 A 380 ... 900 kW
500 ... 690 V 3 AC 735 ... 1560 A 800 ... 1700 kW

Siemens D 21.3 · 2022 6/77


© Siemens 2022

SINAMICS S120 Cabinet Modules


Liquid-cooled units
Active Line Connection Modules

■ Integration
Cabinet Module
DC busbar

230 V AC

24 V DC

Auxiliary power
-F160

supply 3 4
Active Interface Module

-F150
X500 X400 X401 X402

Line 5 5
Filter module Active Line

DRIVE-CLiQ socket
Connection

DRIVE-CLiQ socket 1

DRIVE-CLiQ socket 2
DRIVE-CLiQ socket 0
Module
Module 6 6
LED
RDY
X520
-X609 5
-G160- PE 6 -G160- Internal power
E160 Voltage E160 supply
1 P24 Sensing
2 P24 -X9
4 Module VSM
3 M 1 P24 V
X522 = READY

LEDs
4 M 1
P7 = DC LINK
L 5 2 M
6 230 V AC 2 POWER OK
3
N7 3
Control of
8 2 4 bypass contactor
1 9 5
Cooling circuit

Pre-charging Control of
10 1 6
contactor pre-charging contactor
2 11 P5 7
Bypass 12 8
contactor 13
14 Contactors open IPD card
6 2/T1 -K4
-X41
4 +Temp
4/T2 3 -Temp
6/T3 2 EP +24 V
P6
1 EP M1

-X42
1 P24L
2 P24L
3 M
DCP
P1 P3 4 M
DCN
Cooling P4
circuit
Line
infeed

-X1
Cooling
U1 U2 U1
L1 ~ circuit
V1 V2 V1
L2
W1 W2 W1
L3 =
PE PE PE
PE
X1
1 2

Filter reactor
Cooling circuit

G_D213_EN_00103a
1
2
3
Connection made in the factory
4
5
6

Connection example of an Active Line Connection Module, liquid-cooled - parallel cooling circuit in the Active Interface Module

6/78 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Cabinet Modules


Liquid-cooled units
Active Line Connection Modules

■ Integration
Cabinet Module
DC busbar

230 V AC

24 V DC

Auxiliary power
-F160

supply 3 4
Active Interface Module

-F150
X500 X400 X401 X402

Line 5 5
Filter module Active Line

DRIVE-CLiQ socket
Connection

DRIVE-CLiQ socket 1

DRIVE-CLiQ socket 2
DRIVE-CLiQ socket 0
Module
Module 6 6
LED
RDY
X520
-X609 5
-G160- PE 6 -G160- Internal power
E160 Voltage E160 supply
1 P24 Sensing
2 P24 -X9
4 Module VSM
3 M 1 P24 V
X522 = READY
4 M 1

LEDs
P7 = DC LINK
L 5 2 M
6 230 V AC 2 POWER OK
3
N7 3
8 Control of
2 4
9 bypass contactor
Cooling circuit

1 5
10 Pre-charging Control of
1 6
11 contactor pre-charging contactor
2 7
Bypass 12 8
contactor 13
14 Contactors open IPD card

2/T1 -K4
-X41
4 +Temp
6
4/T2 3 -Temp
6/T3 P6 2 EP +24 V
1 EP M1

-X42
1 P24L
2 P24L
3 M
DCP
4 M
DCN
P1 Cooling P4
circuit
Line
infeed
Cooling
U1 -X1 circuit
U1 U2
L1 ~
V1 V2 V1
L2
W1 W2 W1
L3 =
PE PE PE
PE
X1
1 2
Filter reactor
Cooling circuit

G_D213_EN_00147
1
2
3
Connection made in the factory
4
5
6

Connection example of an Active Line Connection Module, liquid-cooled - serial cooling circuit in the Active Interface Module

Siemens D 21.3 · 2022 6/79


© Siemens 2022

SINAMICS S120 Cabinet Modules


Liquid-cooled units
Active Line Connection Modules

■ Technical specifications
Line voltage 380 ... 480 V 3 AC Active Line Connection Modules
6SL3735-7TE36-1LA3 6SL3735-7TE38-4LA3 6SL3735-7TE41-0LA3 6SL3735-7TE41-4LA3
Rated power
• At IN DC (50 Hz 400 V) kW 380 500 630 900
• At IH DC (50 Hz 400 V) kW 335 465 545 780
• At IN DC (60 Hz 460 V) hp 600 700 900 1250
• At IH DC (60 Hz 460 V) hp 500 700 800 1000
DC link current
• Rated current IN DC A 677 941 1100 1573
• Base-load current IH DC 1) A 603 837 982 1401
• Maximum current Imax DC A 1017 1410 1654 2361
Infeed/regenerative feedback
current
• Rated current IN I A 605 840 985 1405
• Maximum current Imax I A 907 1260 1477 2055
Current demand
• 24 V DC auxiliary power supply A 1.77 1.77 1.7 1.7
• 230 V 1 AC A 1.2 1.2 1.2 1.2
DC link capacitance
• Active Line Module F 12600 17400 18900 28800
• Drive line-up, max. F 134400 134400 230400 230400
2)
Power loss, max.
at 50 Hz 400 V
• Degree of protection <IP55
- Dissipated to coolant kW 10.9 11.7 19.6 21.8
- Dissipated to ambient air kW 2.4 2.3 3.1 3.8
• Degree of protection IP55
- Dissipated to coolant kW 12.2 13.1 21.8 24.7
- Dissipated to ambient air kW 0.9 0.9 0.9 0.9
Coolant volume flow 3) l/min (US 26/53 (6.87/14.0) 26/53 (6.87/14.0) 43/70 (11.4/18.5) 43/70 (11.4/18.5)
Degree of protection <IP55/IP55 gal./min)
Liquid volume dm3 13/16.6 13/16.6 14/17.6 14/17.6

6 Degree of protection <IP55/IP55


Pressure drop, max. 4) Pa 150000 150000 150000 150000
for volume flow
Heat exchanger material
• Active Line Module Aluminum Aluminum Aluminum Aluminum
• Active Interface Module Aluminum Aluminum Aluminum Aluminum
Sound pressure level LpA 5) dB 65/65 65/65 65/65 65/65
(1 m) at 50/60 Hz
Line supply connection 4 x M12 10 x M12 10 x M12 10 x M12
L1, L2, L3
• Conductor cross-section, max. (IEC) mm2 4 × 240 4 × 240 8 × 240 10 × 240
PE/GND connection PE bar PE bar PE bar PE bar
• Busbar cross-section mm2 600 600 600 600
• Conductor cross-section, max. (IEC) mm2 240 240 240 240
Cable length, max. 6) m (ft) 3900/5850 (12795/19193) 3900/5850 (12795/19193) 3900/5850 (12795/19193) 3900/5850 (12795/19193)
Shielded/unshielded
Degree of protection IP21 IP21 IP21 IP21
(standard version)
Dimensions
• Width mm (in) 1600 (63.0) 1600 (63.0) 1600 (63.0) 1600 (63.0)
• Height mm (in) 2200 (86.6) 2200 (86.6) 2200 (86.6) 2200 (86.6)
• Depth mm (in) 600 (23.6) 600 (23.6) 600 (23.6) 600 (23.6)
Weight, approx. kg (lb) 1134 (2500) 1244 (2743) 1430 (3153) 1470 (3241)
(standard version)
Frame size
• Line Connection Module HL JL JL JL
• Active Interface Module JIL JIL JIL JIL
• Active Line Module HXL HXL JXL JXL
Rated short-circuit current kA 65 84 84 100
according to IEC
Minimum short-circuit current 7) kA 9.2 2 2 3.2

1) 4)
The base-load current IH DC is the basis for a duty cycle of 150 % The value is valid for water as coolant.
for 60 s or Imax DC for 5 s with a duty cycle duration of 300 s. Additional information and notes on other coolants are provided in the
2)
The specified power loss represents the maximum value at 100 % SINAMICS Low Voltage Engineering Manual.
5)
utlization. The value is lower under normal operating conditions. Total sound pressure level of Active Interface Module and Active Line
3)
The value applies to coolants comprising water and a mixture of water Module.
6)
and antifreeze agent. Total of all motor cables and DC link. Longer cable lengths for specific
configurations are available on request.
7)
Current required to ensure reliable tripping of installed protective devices.

6/80 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Cabinet Modules


Liquid-cooled units
Active Line Connection Modules

■ Technical specifications
Line voltage 500 ... 690 V 3 AC Active Line Connection Modules
6SL3735- 6SL3735- 6SL3735- 6SL3735- 6SL3735-
7TG37-4LA3 7TG38-1LA3 7TG41-0LA3 7TG41-3LA3 7TG41-6LA3
Rated power
• At IN DC (50 Hz 690 V) kW 800 900 1100 1400 1700
• At IH DC (50 Hz 690 V) kW 705 670 1000 1215 1490
• At IN DC (50 Hz 500 V) kW 560 620 780 965 1180
• At IH DC (50 Hz 500 V) kW 510 485 710 880 1080
• At IN DC (60 Hz 575 V) hp 900 975 1250 1500 1855
• At IH DC (60 Hz 575 V) hp 600 765 1000 1250 1530
DC link current
• Rated current IN DC A 823 907 1147 1422 1740
• Base-load current IH DC 1) A 732 808 936 1266 1550
• Maximum current Imax DC A 1235 1360 1722 2133 2620
Infeed/regenerative feedback
current
• Rated current IN I A 735 810 1025 1270 1560
• Maximum current Imax I A 1100 1214 1537 1905 2055
Current demand
• 24 V DC auxiliary power supply A 1.7 1.7 1.7 1.7 1.67
• 230 V 1 AC A 1.2 1.2 1.2 1.2 1.2
DC link capacitance
• Active Line Module F 10500 10500 16000 19330 21000
• Drive line-up, max. F 153600 153600 153600 153600 210000
Power loss, max. 2)
at 50 Hz 400 V
• Degree of protection <IP55
- Dissipated to coolant kW 17.0 19.5 21.6 27.3 37.7
- Dissipated to ambient air kW 2.4 2.4 3.1 3.7 4.4
• Degree of protection IP55
- Dissipated to coolant kW 18.4 20.9 23.7 30.1 39.2
- Dissipated to ambient air kW 0.9 0.9 0.9 0.9 0.9
Coolant volume flow 3) l/min (US 26/53 (6.87/14.0) 26/53 (6.87/14.0) 37/64 (9.78/16.9) 37/64 (9.78/16.9) 43/70 (11.4/18.5)
Degree of protection <IP55/IP55
Liquid volume
gal./min)
dm 3
13/16.6 14/17.6 14/17.6 14/17.6 14/17.6
6
Degree of protection <IP55/IP55
Pressure drop, max. 4) Pa 150000 150000 150000 150000 150000
for volume flow
Heat exchanger material
• Active Line Module Aluminum Aluminum Aluminum Aluminum Aluminum
• Active Interface Module Aluminum Aluminum Aluminum Aluminum Aluminum
Sound pressure level LpA 5) dB 65/65 65/65 65/65 65/65 65/65
(1 m) at 50/60 Hz
Line supply connection 4 x M12 10 x M12 10 x M12 10 x M12 10 x M12
L1, L2, L3
• Conductor cross-section, max. (IEC) mm2 8 × 240 8 × 240 8 × 240 8 × 240 8 × 240
PE/GND connection PE bar PE bar PE bar PE bar PE bar
• Busbar cross-section mm2 600 600 600 600 600
• Conductor cross-section, max. (IEC) mm2 240 240 240 240 240
Cable length, max. 6) m (ft) 2250/3375 2250/3375 2250/3375 2250/3375 2250/3375
Shielded/unshielded (7382/11073) (7382/11073) (7382/11073) (7382/11073) (7382/11073)
Degree of protection IP21 IP21 IP21 IP21 IP21
(standard version)
Dimensions
• Width mm (in) 1600 (63.0) 1600 (63.0) 1600 (63.0) 1600 (63.0) 1600 (63.0)
• Height mm (in) 2200 (86.6) 2200 (86.6) 2200 (86.6) 2200 (86.6) 2200 (86.6)
• Depth mm (in) 600 (23.6) 600 (23.6) 600 (23.6) 600 (23.6) 600 (23.6)
Weight, approx. kg (lb) 1150 (2535) 1365 (3009) 1520 (3351) 1540 (3395) 1640 (3616)
(standard version)
Frame size
• Line Connection Module HL JL JL JL JL
• Active Interface Module JIL JIL JIL JIL JIL
• Active Line Module HXL HXL JXL JXL JXL
Rated short-circuit current kA 84 100 100 100 100
according to IEC
Minimum short-circuit current 7) kA 10.5 2 2 3.2 3.2

1) The base-load current IH DC is the basis for a duty cycle of 150 % 4) The value is valid for water as coolant.
for 60 s or Imax DC for 5 s with a duty cycle duration of 300 s. Additional information and notes on other coolants are provided in the
2) The specified power loss represents the maximum value at 100 % SINAMICS Low Voltage Engineering Manual.
utlization. The value is lower under normal operating conditions. 5) Total sound pressure level of Active Interface Module and Active Line
3) The value applies to coolants comprising water and a mixture of water Module.
and antifreeze agent. 6) Total of all motor cables and DC link. Longer cable lengths for specific
configurations are available on request.
7) Current required to ensure reliable tripping of installed protective devices.

Siemens D 21.3 · 2022 6/81


© Siemens 2022

SINAMICS S120 Cabinet Modules


Liquid-cooled units
Active Line Connection Modules compact

■ Overview ■ Design
Active Line Connection Module compact always includes an
Active Interface Module, which contains the associated Clean
Power Filter and pre-charging circuit. The line filter that is
included ensures compliance with the EMC requirements for the
"second environment".
The power rating can be increased by connecting Active Line
Connection Modules compact in parallel. You must observe the
following rules:
• Up to four identical Active Line Connection Modules compact
can be connected in parallel
• A common Control Unit is required whenever the modules are
connected in parallel.
• The parallel connection must be supplied from a common
infeed point (i.e. the modules cannot be operated on different
line supplies).
• A derating factor of 5% must be taken into consideration,
regardless of the number of modules connected in parallel.
Active Line Connection Modules compact comprise a liquid- • The main contactors or circuit breakers of the respective Line
cooled Active Interface Module and a liquid-cooled Active Line Connection Modules must close together and simultaneously.
Module. They can supply motoring energy to the DC link and Monitoring is performed via the -X50 terminals of the
return regenerative energy to the line supply. respective Line Connection Module
As standard, the Active Line Connection Module compact is For additional information, please refer to the SINAMICS Low
positioned in the drive line-up so that the Motor Modules are ar- Voltage Engineering Manual.
ranged to the right. If Motor Modules are to be arranged to the
left of the Active Line Connection Module compact, option M88 ■ Selection and ordering data
(DC bus system for line-side Cabinet Modules) must be ordered.
The line-side infeed via the main switch with fuse switch Rated power Rated DC link current Active Line Connection
disconnector or circuit breaker must be implemented on the at 400 V or 690 V Module compact
6 plant/system side. kW A Article No.
The Active Interface Module is equipped as standard with Line voltage 380 ... 480 V 3 AC
a radio interference suppression filter according to (DC link voltage 570 ... 720 V DC)
EN 61800-3 Category C3. 380 677 6SL3735-7TE36-1MA3
Active Line Connection Modules compact generate a controlled 500 941 6SL3735-7TE38-4MA3
DC voltage that is kept constant regardless of line voltage 630 1100 6SL3735-7TE41-0MA3
fluctuations (the line voltage must remain within the permissible
tolerances). 900 1573 6SL3735-7TE41-4MA3
Line voltage 500 ... 690 V 3 AC
In the factory setting, the DC voltage is regulated to 1.5 times the (DC link voltage 750 ... 1035 V DC)
rms value of the rated line voltage.
800 823 6SL3735-7TG37-4MA3
Active Line Connection Modules draw an almost sinusoidal
900 907 6SL3735-7TG38-1MA3
current from the line supply and cause virtually
no line harmonics. 1100 1147 6SL3735-7TG41-0MA3

Active Line Connection Modules compact are suitable for con- 1400 1422 6SL3735-7TG41-3MA3
nection to supply systems grounded at the neutral point (TN, TT) 1400 1422 6SL3735-7TG41-3MA4
and non-grounded (IT) supply systems. The following voltages 1700 1740 6SL3735-7TG41-6MA3
and currents are available:
1700 1710 6SL3735-7TG41-6MA4
Line voltage Rated infeed/ Rated power
regenerative
feedback current
380 ... 480 V 3 AC 605 ... 1405 A 380 ... 900 kW
500 ... 690 V 3 AC 735 ... 1560 A 800 ... 1700 kW

6/82 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Cabinet Modules


Liquid-cooled units
Active Line Connection Modules compact

■ Integration
Cabinet Module

DC busbar

L 1 230 V AC
2
24 V DC
230 V 1 AC 3
N 4 -F150 1
-F160

PE
6

-F160
24 V DC 7
2 Active Interface Module X500 X400 X401 X402
2
Auxiliary power Filter module Active Line

DRIVE-CLiQ socket 1
supply -X100

DRIVE-CLiQ socket 2
DRIVE-CLiQ socket 0
DRIVE-CLiQ socket
LED
Module
RDY
-G160 -G160
-E160 X520 -E160
-X112 -X609 5
3 6
1 A1 PE Internal power
2 Voltage supply
External A2 1 P24 Sensing
bypass N 2 P24 -X9
Module VSM
contactor 1 3 M 1 P24 V
X522 = READY

LEDs
4 M 1
5
P7 = DC LINK
230 V AC 2 M
6 2 POWER OK
7 3
8 Control of
N 4
9 3 bypass contactor
5
Cooling circuit

10 Pre-charging 4 Control of
4 6
11 contactor P5 pre-charging contactor
7
12 8
13

-X110
14 Contactors open
-X41
IPD card
6
1 2/T1 4 +Temp
Pre-charging 2 4/T2 3 -Temp
3 6/T3 2 EP +24 V
P6 1
-K4 EP M1
3NE1 021-0
(100 A)
-X42
1 P24L
2 P24L
3 M DCP
4 M
P1 P3 DCN
Cooling
circuit
P4

Main switch
Cooling
U1 U1 U2 U1 -X1 circuit
L1 ~
V1 V1 V2 V1
L2
W1 W1 W2 W1
L3 =
PE PE PE PE
PE
X1
Line infeed 1 2

Filter reactor
Cooling circuit

G_D213_EN_00150

1
2
Connection made in the factory
3
4

Connection example, Active Line Connection Module compact liquid-cooled, parallel cooling circuit in the Active Interface Module

Siemens D 21.3 · 2022 6/83


© Siemens 2022

SINAMICS S120 Cabinet Modules


Liquid-cooled units
Active Line Connection Modules compact

■ Integration
Cabinet Module

DC busbar

L 1 230 V AC
2
24 V DC
230 V 1 AC 3
N 4 -F150 1
-F160

PE
6

-F160
24 V DC 7
2 Active Interface Module X500 X400 X401 X402
2
Auxiliary power Filter module Active Line
supply -X100

DRIVE-CLiQ socket 1

DRIVE-CLiQ socket 2
DRIVE-CLiQ socket 0
DRIVE-CLiQ socket
LED
Module
RDY
-G160 -G160
-E160 X520 -E160
-X112 -X609 5
3 6
1 A1 PE Internal power
2 Voltage supply
External A2 1 P24 Sensing
bypass N 2 P24 -X9
Module VSM
contactor 1 3 M 1 P24 V
X522 = READY

LEDs
4 M 1
5
P7 = DC LINK
2 M
230 V AC
6 2 POWER OK
7 3
8 Control of
N 4 bypass contactor
9 3
Cooling circuit

5
10 Pre-charging 4 Control of
4 6
11 contactor pre-charging contactor
7
12 8
13 IPD card
6 -X110
14 Contactors open
-X41
IPD Card

1 2/T1 4 +Temp
Pre-charging 2 4/T2 3 -Temp
3 6/T3 P6 2 EP +24 V
-K4 1 EP M1
3NE1 021-0
(100 A)
-X42
1 P24L
2 P24L
3 M DCP
4 M
DCN
P1 Cooling P4
circuit

Main switch
Cooling
circuit
U1 U1 U2 U1 -X1
L1 ~
V1 V1 V2 V1
L2
W1 W1 W2 W1
L3 =
PE PE PE PE
PE
X1
Line infeed 1 2

Filter reactor
Cooling circuit

G_D213_EN_00149

1
2
Connection made in the factory
3
4

Connection example, Active Line Connection Module compact liquid-cooled, serial cooling circuit in the Active Interface Module

6/84 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Cabinet Modules


Liquid-cooled units
Active Line Connection Modules compact

■ Technical specifications
Line voltage 380 ... 480 V 3 AC Active Line Connection Modules compact
6SL3735-7TE36-1MA3 6SL3735-7TE38-4MA3 6SL3735-7TE41-0MA3 6SL3735-7TE41-4MA3
Rated power
• At IN DC (50 Hz 400 V) kW 380 500 630 900
• At IH DC (50 Hz 400 V) kW 335 465 545 780
• At IN DC (60 Hz 460 V) hp 600 700 900 1250
• At IH DC (60 Hz 460 V) hp 500 700 800 1000
DC link current
• Rated current IN DC A 677 941 1100 1573
• Base-load current IH DC 1) A 603 837 982 1401
• Maximum current Imax DC A 1017 1410 1654 2361
Infeed/regenerative feedback
current
• Rated current IN I A 605 840 985 1405
• Maximum current Imax I A 907 1260 1477 2055
Current demand
• 24 V DC auxiliary power supply A 1.77 1.77 1.7 1.7
• 230 V 1 AC A 1.2 1.2 1.2 1.2
DC link capacitance
• Active Line Module F 12600 17400 18900 28800
• Drive line-up, max. F 134400 134400 230400 230400
Power loss, max. 2)
at 50 Hz 400 V
• Degree of protection <IP55
- Dissipated to coolant kW 10.9 11.7 19.6 21.8
- Dissipated to ambient air kW 2.0 2.1 2.8 3.4
• Degree of protection IP55
- Dissipated to coolant kW 11.8 12.9 21.5 24.3
- Dissipated to ambient air kW 0.9 0.9 0.9 0.9
Coolant volume flow 3) l/min (US 26/53 (6.87/14.0) 26/53 (6.87/14.0) 43/70 (11.4/18.5) 43/70 (11.4/18.5)
Degree of protection <IP55/IP55 gal./min)

Liquid volume
Degree of protection <IP55/IP55
dm3 13/16.6 13/16.6 14/17.6 14/17.6 6
Pressure drop, max. 4) Pa 150000 150000 150000 150000
for volume flow

Heat exchanger material


• Active Line Module Aluminum Aluminum Aluminum Aluminum
• Active Interface Module Aluminum Aluminum Aluminum Aluminum
Sound pressure level LpA 5) dB 65/65 65/65 65/65 65/65
(1 m) at 50/60 Hz
Line supply connection 5/M12 5/M12 5/M12 5/M12
L1, L2, L3
• Conductor cross-section, max. (IEC) mm2 4 × 185 4 × 185 10 × 185 10 × 185
PE/GND connection PE bar PE bar PE bar PE bar
• Busbar cross-section mm2 600 600 600 600
• Conductor cross-section, max. (IEC) mm2 240 240 240 240
Cable length, max. 6) m (ft) 3900/5850 (12795/19193) 3900/5850 (12795/19193) 3900/5850 (12795/19193) 3900/5850 (12795/19193)
Shielded/unshielded
Degree of protection IP21 IP21 IP21 IP21
(standard version)
Dimensions
• Width mm (in) 1200 (47.2) 1200 (47.2) 1200 (47.2) 1200 (47.2)
• Height mm (in) 2200 (86.6) 2200 (86.6) 2200 (86.6) 2200 (86.6)
• Depth mm (in) 600 (23.6) 600 (23.6) 600 (23.6) 600 (23.6)
Weight, approx. kg (lb) 841 (1854) 841 (1854) 1027 (2265) 1027 (2265)
(standard version)
Frame size
• Active Interface Module JIL JIL JIL JIL
• Active Line Module HXL HXL JXL JXL
Rated short-circuit current kA 65 84 84 100
according to IEC
Minimum short-circuit current 7) kA 9.2 10.4 16 21

1) 5)
The base-load current IH DC is the basis for a duty cycle of 150 % Total sound pressure level of Active Interface Module and Active Line
for 60 s or Imax DC for 5 s with a duty cycle duration of 300 s. Module.
2) 6)
The specified power loss represents the maximum value at 100 % Total of all motor cables and DC link. Longer cable lengths for specific
utilization. The value is lower under normal operating conditions. configurations are available on request.
3) 7)
The value applies to coolants comprising water and a mixture of water Current required for reliably triggering protective devices
and antifreeze agent. (additional information see Equipment manual SINAMICS S120 Cabinet
4)
The value is valid for water as coolant. Modules liquid cooled).
Additional information and notes on other coolants are provided in the
SINAMICS Low Voltage Engineering Manual.

Siemens D 21.3 · 2022 6/85


© Siemens 2022

SINAMICS S120 Cabinet Modules


Liquid-cooled units
Active Line Connection Modules compact

■ Technical specifications
Line voltage 500 ... 690 V 3 AC Active Line Connection Modules compact
6SL3735-7TG37-4MA3 6SL3735-7TG38-1MA3 6SL3735-7TG41-0MA3 6SL3735-7TG41-3MA3
Rated power
• At IN DC (50 Hz 690 V) kW 800 900 1100 1400
• At IH DC (50 Hz 690 V) kW 705 670 1000 1215
• At IN DC (50 Hz 500 V) kW 560 620 780 965
• At IH DC (50 Hz 500 V) kW 510 485 710 880
• At IN DC (60 Hz 575 V) hp 900 975 1250 1500
• At IH DC (60 Hz 575 V) hp 600 765 1000 1250
DC link current
• Rated current IN DC A 823 907 1147 1422
• Base-load current IH DC1) A 732 808 936 1266
• Maximum current Imax DC A 1235 1360 1722 2133
Infeed/regenerative feedback
current
• Rated current IN I A 735 810 1025 1270
• Maximum current Imax I A 1100 1214 1537 1905
Current demand
• 24 V DC auxiliary power supply A 1.7 1.7 1.7 1.7
• 230 V 1 AC A 1.2 1.2 1.2 1.2
DC link capacitance
• Active Line Module F 10500 10500 16000 19330
• Drive line-up, max. F 153600 153600 153600 153600
Power loss, max. 2)
at 50 Hz 400 V
• Degree of protection <IP55
- Dissipated to coolant kW 17.0 19.5 21.6 27.3
- Dissipated to ambient air kW 2.0 2.2 2.8 3.3
• Degree of protection IP55
- Dissipated to coolant kW 18.0 20.7 23.4 29.7
- Dissipated to ambient air kW 0.9 0.9 0.9 0.9
Coolant volume flow 3)
6 Degree of protection <IP55/IP55
l/min (US
gal./min)
26/53 (6.87/14.0) 26/53 (6.87/14.0) 37/64 (9.78/16.9) 37/64 (9.78/16.9)

Liquid volume dm3 13/16.6 14/17.6 14/17.6 14/17.6


Degree of protection <IP55/IP55
Pressure drop, max. 4) Pa 150000 150000 150000 150000
for volume flow
Heat exchanger material
• Active Line Module Aluminum Aluminum Aluminum Aluminum
• Active Interface Module Aluminum Aluminum Aluminum Aluminum
Sound pressure level LpA 5) dB 65/65 65/65 65/65 65/65
(1 m) at 50/60 Hz
Line supply connection 5/M12 5/M12 5/M12 5/M12
L1, L2, L3
• Conductor cross-section, max. (IEC) mm2 10 × 185 10 × 185 10 × 185 10 × 185
PE/GND connection PE bar PE bar PE bar PE bar
• Busbar cross-section mm2 600 600 600 600
• Conductor cross-section, max. (IEC) mm2 240 240 240 240
Cable length, max. 6) m (ft) 2250/3375 (7382/11073) 2250/3375 (7382/11073) 2250/3375 (7382/11073) 2250/3375 (7382/11073)
Shielded/unshielded
Degree of protection IP21 IP21 IP21 IP21
(standard version)
Dimensions
• Width mm (in) 1200 (47.2) 1200 (47.2) 1200 (47.2) 1200 (47.2)
• Height mm (in) 2200 (86.6) 2200 (86.6) 2200 (86.6) 2200 (86.6)
• Depth mm (in) 600 (23.6) 600 (23.6) 600 (23.6) 600 (23.6)
Weight, approx. kg (lb) 937 (2066) 942 (2077) 1077 (2375) 1077 (2375)
(standard version)
Frame size
• Active Interface Module JIL JIL JIL JIL
• Active Line Module HXL HXL JXL JXL
Rated short-circuit current kA 84 100 100 100
according to IEC
Minimum short-circuit current 7) kA 8.4 10.5 12.6 20

1) The base-load current IH DC is the basis for a duty cycle of 150 % 5) Total sound pressure level of Active Interface Module and Active Line
for 60 s or Imax DC for 5 s with a duty cycle duration of 300 s. Module.
2) The specified power loss represents the maximum value at 100 % 6) Total of all motor cables and DC link. Longer cable lengths for specific
utilization. The value is lower under normal operating conditions. configurations are available on request.
3) The value applies to coolants comprising water and a mixture of water 7) Current required for reliably triggering protective devices
and antifreeze agent. (additional information see Equipment manual SINAMICS S120 Cabinet
4) The value is valid for water as coolant. Modules liquid cooled).
Additional information and notes on other coolants are provided in the
SINAMICS Low Voltage Engineering Manual.

6/86 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Cabinet Modules


Liquid-cooled units
Active Line Connection Modules compact

■ Technical specifications
Line voltage 500 ... 690 V 3 AC Active Line Connection Modules compact
6SL3735-7TG41-3MA4 8) 6SL3735-7TG41-6MA3 6SL3735-7TG41-6MA4 8)
Rated power
• At IN DC (50 Hz 690 V) kW 1400 1700 1700
• At IH DC (50 Hz 690 V) kW 1215 1490 1490
• At IN DC (50 Hz 500 V) kW 965 1180 1180
• At IH DC (50 Hz 500 V) kW 880 1080 1080
• At IN DC (60 Hz 575 V) hp 1500 1855 1855
• At IH DC (60 Hz 575 V) hp 1250 1530 1530
DC link current
• Rated current IN DC A 1422 1740 1740
• Base-load current IH DC 1) A 1266 1550 1550
• Maximum current Imax DC A 2133 2620 2620
Infeed/regenerative feedback
current
• Rated current IN I A 1270 1560 1560
• Maximum current Imax I A 1905 2055 2055
Current demand
• 24 V DC auxiliary power supply A 1.7 1.7 1.7
• 230 V 1 AC A 1.2 1.2 1.2
DC link capacitance
• Active Line Module F 19330 21000 21000
• Drive line-up, max. F 153600 210000 210000
Power loss, max. 2)
at 50 Hz 400 V
• Degree of protection <IP55
- Dissipated to coolant kW 29.5 36.7 40.2
- Dissipated to ambient air kW 4.0 4.0 4.0
• Degree of protection IP55
- Dissipated to coolant kW 31.9 39.8 43.3
- Dissipated to ambient air kW 0.9 0.9 0.9
Coolant volume flow 3)
Degree of protection <IP55/IP55
l/min (US
gal./min)
52/79 (13.74/20.87) 43/70 (11.4/18.5) 52/79 (13.74/20.87)
6
Liquid volume dm3 14/17.6 14/17.6 14/17.6
Degree of protection <IP55/IP55
Pressure drop, max. 4) Pa 150000 150000 150000
for volume flow
Heat exchanger material
• Active Line Module Aluminum Aluminum Aluminum
• Active Interface Module Aluminum Aluminum Aluminum
Sound pressure level LpA 5) dB 65/65 65/65 65/65
(1 m) at 50/60 Hz
Line supply connection 5/M12 5/M12 5/M12
L1, L2, L3
• Conductor cross-section, max. (IEC) mm2 10 × 185 10 × 185 10 × 185
PE/GND connection PE bar PE bar PE bar
• Busbar cross-section mm2 600 600 600
• Conductor cross-section, max. (IEC) mm2 240 240 240
Cable length, max. 6) m (ft) 2250/3375 (7382/11073) 2250/3375 (7382/11073) 2250/3375 (7382/11073)
Shielded/unshielded
Degree of protection IP21 IP21 IP21
(standard version)
Dimensions
• Width mm (in) 1200 (47.2) 1200 (47.2) 1200 (47.2)
• Height mm (in) 2200 (86.6) 2200 (86.6) 2200 (86.6)
• Depth mm (in) 600 (23.6) 600 (23.6) 600 (23.6)
Weight, approx. kg (lb) 1077 (2375) 1177 (2595) 1177 (2595)
(standard version)
Frame size
• Active Interface Module JIL JIL JIL
• Active Line Module JXL JXL JXL
Rated short-circuit current kA 100 100 100
according to IEC
Minimum short-circuit current 7) kA 20 24 24
1) The base-load current IH DC is the basis for a duty cycle of 150 % 5) Total sound pressure level of Active Interface Module and Active Line
for 60 s or Imax DC for 5 s with a duty cycle duration of 300 s. Module.
2) The specified power loss represents the maximum value at 100 % 6) Total of all motor cables and DC link. Longer cable lengths for specific
utilization. The value is lower under normal operating conditions. configurations are available on request.
3) The value applies to coolants comprising water and a mixture of water 7) Current required for reliably triggering protective devices
and antifreeze agent. (additional information see Equipment manual SINAMICS S120 Cabinet
4) The value is valid for water as coolant. Modules liquid cooled).
Additional information and notes on other coolants are provided in the 8) These devices have the shaft generator drive function (Shaft Generator
SINAMICS Low Voltage Engineering Manual. Drive, SGD). Further information on this can be found in the line infeed
system manual.

Siemens D 21.3 · 2022 6/87


© Siemens 2022

SINAMICS S120 Cabinet Modules


Liquid-cooled units
Motor Modules

■ Overview ■ Design
Motor Modules contain the following components as standard:
• Retaining device for the DC busbar, including the connection
to the DC connections of the Motor Module
• Connection busbars, nickel-plated
- on Motor Modules, frame size JXL, the connection for the
motor cables is routed to the right of the device
- on Motor Modules, frame size HXL, the connection is
underneath the device
• Cable retaining bar for the power cables
• DRIVE-CLiQ interface (three DRIVE-CLiQ sockets), without
Control Unit
• Auxiliary power supply system (4-pole) for the auxiliary power
supply, including cable connections for looping through to the
next Cabinet Module
• Nickel-plated PE busbar (60 x 10 mm), including jumper for
looping through to the next Cabinet Module
• EMC-compliant design thanks to additional shielding
Motor Modules are available in the power range from 90 kW to measures and appropriately routed cables
1500 kW.
Line voltage DC link voltage Type rating
■ Selection and ordering data
380 ... 480 V 3 AC 510 ... 720 V DC 110 ... 800 kW Type rating Rated output current Motor Module
at 400 V or 690 V IN
500 ... 690 V 3 AC 675 ... 1035 V DC 90 ... 1500 kW
kW A Article No.
By connecting in parallel up to four Motor Modules, which are
Line voltage 380 ... 480 V 3 AC
operated on one Control Unit and supply one motor, it is possible (DC link voltage 510 ... 720 V DC)
to increase the available shaft power to max. approx. 5700 kW
(taking into account the derating factors according to the 110 210 6SL3725-1TE32-1AA3

6 SINAMICS Low Voltage Engineering Manual). 132


160
260
310
6SL3725-1TE32-6AA3
6SL3725-1TE33-1AA3
The Motor Modules can also be used as Braking Modules
(braking chopper) if a 3-phase braking resistor is connected 250 490 6SL3725-1TE35-0AA3
instead of a motor.
315 605 6SL3725-1TE36-1AA3
Further information can be found in the SINAMICS Low Voltage
Engineering Manual. 400 745 6SL3725-1TE37-5AA3
450 840 6SL3725-1TE38-4AA3
560 985 6SL3725-1TE41-0AA3
710 1260 6SL3725-1TE41-2AA3
800 1405 6SL3725-1TE41-4AA3
800 1330 6SL3725-1TE41-4AS3
Line voltage 500 ... 690 V 3 AC
(DC link voltage 675 ... 1035 V DC)
90 100 6SL3725-1TG31-0AA3
132 150 6SL3725-1TG31-5AA3
200 215 6SL3725-1TG32-2AA3
315 330 6SL3725-1TG33-3AA3
450 465 6SL3725-1TG34-7AA3
560 575 6SL3725-1TG35-8AA3
710 735 6SL3725-1TG37-4AA3
800 810 6SL3725-1TG38-0AA3
800 810 6SL3725-1TG38-1AA3
1000 1025 6SL3725-1TG41-0AA3
1200 1270 6SL3725-1TG41-3AA3
1500 1560 6SL3725-1TG41-6AP3

6/88 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Cabinet Modules


Liquid-cooled units
Motor Modules

■ Integration
Motor Modules are controlled by the CU320-2 DP or already be installed. If the Control Unit is to be mounted
CU320-2 PN Control Unit. Communication between the Control externally, the DRIVE-CLiQ cable will not be included in the
Unit and Modules is established via a DRIVE-CLiQ connection. scope of supply and must be configured on site.
If the Control Unit is integrated in the same cabinet as an option For additional information, please refer to the SINAMICS Low
with order code K90 or K95, these communication cables will Voltage Engineering Manual.

Cabinet Module
DC busbar

230 V AC
24 V DC
Auxiliary power supply X400 X401 X402
-F150

-F160

DC fuses

DRIVE-CLiQ socket 0

DRIVE-CLiQ socket 2
DRIVE-CLiQ socket 1
Motor Module
DCP
DCN

Z READY
LEDs
-X9
1 P24 V DC LINK
1 POWER OK
2
2
M
IPD card 6
3
4 Internal
5 power
supply -X2
6 U2
7 =
V2 M
Y 8 ~ W2 3~
PE

-X41
4 +Temp
X 3 -Temp
2 EP +24 V
1 EP M1 M
-X46
1 BR Output+
2 BR Output- Cooling circuit
3 FB Input+
4 FB Input-

-X42
1 P24L
2 P24L
3 M
4 M
G_D213_EN_00102a

Cooling circuit

X Connection of temperature sensor for motors without DRIVE-CliQ interface

Y Required for Safety Integrated

Z Door fan -G160 (IP21, IP23, IP43, IP54) or heat exchanger -E160 (IP55)

Connection example of a Motor Module, liquid-cooled

Siemens D 21.3 · 2022 6/89


© Siemens 2022

SINAMICS S120 Cabinet Modules


Liquid-cooled units
Motor Modules

■ Technical specifications
Line voltage 380 ... 480 V 3 AC Motor Modules
DC link voltage 510 ... 720 V DC 6SL3725-1TE32-1AA3 6SL3725-1TE32-6AA3 6SL3725-1TE33-1AA3 6SL3725-1TE35-0AA3
Type rating
• At IL (50 Hz 400 V) 1) kW 110 132 160 250
• At IH (50 Hz 400 V) 1) kW 90 110 132 200
• At IL (60 Hz 460 V) 2) hp 150 200 250 400
• At IH (60 Hz 460 V) 2) hp 150 200 200 350
Output current
• Rated current IN O A 210 260 310 490
• Base-load current IL3) A 205 250 302 477
• Base-load current IH 4) A 178 233 277 438
• Maximum current Imax O A 307 375 453 715
DC link current
• Rated current IN DC
when supplied via
- Basic Line Module A 256 317 380 600
- Active Line Module A 230 287 340 538
• Base-load current IL DC 3)
when supplied via
- Basic Line Module A 250 305 368 581
- Active Line Module A 225 274 331 522
• Base-load current IH DC 4)
when supplied via
- Basic Line Module A 227 284 338 534
- Active Line Module A 195 255 303 480
Current demand
• 24 V DC auxiliary power supply A 1.3 1.3 1.3 1.3
• 230 V 1 AC A 0.6 0.6 0.6 0.6
DC link capacitance F 4800 5800 8400 9600
Pulse frequency 5)
• Rated frequency kHz 2 2 2 2
• Pulse frequency, max.
- Without current derating kHz 2 2 2 2
- With current derating kHz 8 8 8 8
Power loss, max. 6)
6 at 50 Hz 400 V
• Degree of protection <IP55
- Dissipated to coolant kW 1.6 1.9 2.2 3.4
- Dissipated to ambient air kW 0.2 0.2 0.2 0.3
• Degree of protection IP55
- Dissipated to coolant kW 1.7 2.1 2.4 3.8
- Dissipated to ambient air kW 0.2 0.2 0.2 0.2
Coolant volume flow 7) l/min (US 9 (2.38) 9 (2.38) 12 (3.17) 12 (3.17)
All degrees of protection gal./min)
Liquid volume dm3 2.9/4.7 2.9/4.7 3.5/5.3 3.5/5.3
Degree of protection <IP55/IP55
Pressure drop, max. 8) Pa 150000 150000 150000 150000
for volume flow
Heat exchanger material Stainless steel Stainless steel Stainless steel Stainless steel
Sound pressure level LpA dB 52 52 52 52
(1 m) at 50/60 Hz
Motor connection M12 M12 M12 M12
U2, V2, W2
• Conductor cross-section, max. (IEC) mm2 2 × 95 2 × 95 2 × 240 2 × 240
PE/GND connection PE bar PE bar PE bar PE bar
• Busbar cross-section mm2 600 600 600 600
2
• Conductor cross-section, max. (IEC) mm 240 240 240 240
Cable length, max. 9) m (ft) 300/450 (984/1476) 300/450 (984/1476) 300/450 (984/1476) 300/450 (984/1476)
Shielded/unshielded
Degree of protection IP21 IP21 IP21 IP21
(standard version)
Dimensions
• Width mm (in) 400 (15.75) 400 (15.75) 400 (15.75) 400 (15.75)
• Height mm (in) 2200 (86.61) 2200 (86.61) 2200 (86.61) 2200 (86.61)
• Depth mm (in) 600 (23.62) 600 (23.62) 600 (23.62) 600 (23.62)
Weight, approx. kg (lb) 280 (617) 280 (617) 320 (706) 320 (706)
Frame size FXL FXL GXL GXL
Rated short-circuit current kA 65 65 65 65
according to IEC

1) 6)
Rated power of a typical 6-pole standard induction motor based on IL The specified power loss represents the maximum value at 100 %
or IH for 400 V 3 AC 50 Hz. utilization. The value is lower under normal operating conditions.
2) 7)
Rated power of a typical 6-pole standard induction motor based on IL The value applies to coolants comprising water and a mixture of water
or IH for 460 V 3 AC 60 Hz. and antifreeze agent.
3) 8)
The base-load current IL is based on a duty cycle of 110 % for 60 s The value is valid for water as coolant.
or 150 % for 10 s with a duty cycle duration of 300 s. Additional information and notes on other coolants are provided in the
4)
The base-load current IH is based on a duty cycle of 150 % for 60 s SINAMICS Low Voltage Engineering Manual.
9)
or 160 % for 10 s with a duty cycle duration of 300 s. Total of all motor cables. Longer cable lengths for specific configurations
5)
Information regarding the correlation between the pulse frequency and are available on request.For additional information, please refer to the
max. output current/output frequency is provided in the SINAMICS Low SINAMICS Low Voltage Engineering Manual.
Voltage Engineering Manual.

6/90 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Cabinet Modules


Liquid-cooled units
Motor Modules

■ Technical specifications
Line voltage 380 ... 480 V 3 AC Motor Modules
DC link voltage 510 ... 720 V DC 6SL3725-1TE36-1AA3 6SL3725-1TE37-5AA3 6SL3725-1TE38-4AA3
Type rating
• At IL (50 Hz 400 V) 1) kW 315 400 450
• At IH (50 Hz 400 V) 1) kW 250 315 400
• At IL (60 Hz 460 V) 2) hp 500 600 700
• At IH (60 Hz 460 V) 2) hp 350 450 600
Output current
• Rated current IN O A 605 745 840
• Base-load current IL3) A 590 725 820
• Base-load current IH 4) A 460 570 700
• Maximum current Imax O A 885 1087 1230
DC link current
• Rated current IN DC
when supplied via
- Basic Line Module A 738 894 1025
- Active Line Module A 664 805 922
• Base-load current IL DC 3)
when supplied via
- Basic Line Module A 719 871 1000
- Active Line Module A 646 784 898
• Base-load current IH DC 4)
when supplied via
- Basic Line Module A 561 795 853
- Active Line Module A 504 716 767
Current demand
• 24 V DC auxiliary power supply A 1.5 1.5 1.5
• 230 V 1 AC A 0.6 0.6 0.6
DC link capacitance F 12600 17400 17400
Pulse frequency 5)
• Rated frequency kHz 1.25 1.25 1.25
• Pulse frequency, max.
- Without current derating kHz 1.25 1.25 1.25
- With current derating kHz 8 8 8
Power loss, max. 6)
at 50 Hz 400 V
• Degree of protection <IP55
- Dissipated to coolant kW 4.6 5.2 5.5
6
- Dissipated to ambient air kW 0.6 0.7 0.8
• Degree of protection IP55
- Dissipated to coolant kW 5.0 5.7 6.2
- Dissipated to ambient air kW 0.2 0.2 0.2
Coolant volume flow 7) l/min (US 16 (4.23) 16 (4.23) 16 (4.23)
All degrees of protection gal./min)
Liquid volume dm3 3.3/5.1 3.3/5.1 3.3/5.1
Degree of protection <IP55/IP55
Pressure drop, max. 8) Pa 150000 150000 150000
for volume flow
Heat exchanger material Aluminum Aluminum Aluminum
Sound pressure level LpA dB 54 54 54
(1 m) at 50/60 Hz
Motor connection 2/M12 2/M12 2/M12
U2, V2, W2
• Conductor cross-section, max. (IEC) mm2 4 × 185 4 × 185 4 × 185
PE/GND connection PE bar PE bar PE bar
• Busbar cross-section mm2 600 600 600
• Conductor cross-section, max. (IEC) mm2 240 240 240
Cable length, max. 9) m (ft) 300/450 (984/1476) 300/450 (984/1476) 300/450 (984/1476)
Shielded/unshielded
Degree of protection IP21 IP21 IP21
(standard version)
Dimensions
• Width mm (in) 400 (15.75) 400 (15.75) 400 (15.75)
• Height mm (in) 2200 (86.61) 2200 (86.61) 2200 (86.61)
• Depth mm (in) 600 (23.62) 600 (23.62) 600 (23.62)
Weight, approx. kg (lb) 350 (772) 350 (772) 350 (772)
Frame size HXL HXL HXL
Rated short-circuit current kA 65 65 84
according to IEC

1) Rated power of a typical 6-pole standard induction motor based on IL 6) The specified power loss represents the maximum value at 100 %
or IH for 400 V 3 AC 50 Hz. utilization. The value is lower under normal operating conditions.
2) Rated power of a typical 6-pole standard induction motor based on IL 7) The value applies to coolants comprising water and a mixture of water
or IH for 460 V 3 AC 60 Hz. and antifreeze agent.
3) The base-load current IL is based on a duty cycle of 110 % for 60 s 8) The value is valid for water as coolant.
or 150 % for 10 s with a duty cycle duration of 300 s. Additional information and notes on other coolants are provided in the
4) The base-load current IH is based on a duty cycle of 150 % for 60 s SINAMICS Low Voltage Engineering Manual.
or 160 % for 10 s with a duty cycle duration of 300 s. 9) Total of all motor cables. Longer cable lengths for specific configurations
5) Information regarding the correlation between the pulse frequency and are available on request.For additional information, please refer to the
max. output current/output frequency is provided in the SINAMICS Low SINAMICS Low Voltage Engineering Manual.
Voltage Engineering Manual.

Siemens D 21.3 · 2022 6/91


© Siemens 2022

SINAMICS S120 Cabinet Modules


Liquid-cooled units
Motor Modules

■ Technical specifications
Line voltage 380 ... 480 V 3 AC Motor Modules
DC link voltage 510 ... 720 V DC 6SL3725-1TE41-0AA3 6SL3725-1TE41-2AA3 6SL3725-1TE41-4AA3 6SL3725-1TE41-4AS3 10)
Type rating
• At IL (50 Hz 400 V) 1) kW 560 710 800 800
• At IH (50 Hz 400 V) 1) kW 450 630 710 630
• At IL (60 Hz 460 V) 2) hp 800 1000 1150 1000
• At IH (60 Hz 460 V) 2) hp 700 900 1000 900
Output current
• Rated current IN O A 985 1260 1405 1330
• Base-load current IL3) A 960 1230 1370 1310
• Base-load current IH 4) A 860 1127 1257 1150
• Maximum current Imax O A 1440 1845 2055 2055
DC link current
• Rated current IN DC
when supplied via
- Basic Line Module A 1202 1512 1714 1550
- Active Line Module A 1080 1361 1544 1403
• Base-load current IL DC 3)
when supplied via
- Basic Line Module A 1170 1474 1670 1525
- Active Line Module A 1051 1326 1500 1405
• Base-load current IH DC 4)
when supplied via
- Basic Line Module A 1048 1345 1532 1676
- Active Line Module A 942 1211 1377 1403
Current demand
• 24 V DC auxiliary power supply A 1.5 1.5 1.5 1.5
• 230 V 1 AC A 0.6 0.6 0.6 0.6
DC link capacitance F 21000 29000 29000 21000
Pulse frequency 5)
• Rated frequency kHz 1.25 1.25 1.25 2
• Pulse frequency, max.
- Without current derating kHz 1.25 1.25 1.25 2
- With current derating kHz 8 8 8 4
Power loss, max. 6)
at 50 Hz 400 V
6 • Degree of protection <IP55
- Dissipated to coolant kW 7.5 8.6 9.5 10.2
- Dissipated to ambient air kW 1.0 1.3 1.5 1.4
• Degree of protection IP55
- Dissipated to coolant kW 8.3 9.6 10.7 11.3
- Dissipated to ambient air kW 0.2 0.3 0.3 0.3
Coolant volume flow 7) l/min (US 27 (7.13) 27 (7.13) 27 (7.13) 27 (7.13)
All degrees of protection gal./min)
Liquid volume dm3 5.2/7 5.2/7 5.2/7 5.2/7
Degree of protection <IP55/IP55
Pressure drop, max. 8) Pa 150000 150000 150000 150000
for volume flow
Heat exchanger material Aluminum Aluminum Aluminum Aluminum
Sound pressure level LpA dB 56 56 56 56
(1 m) at 50/60 Hz
Motor connection 2/M12 2/M12 2/M12 2/M12
U2, V2, W2
2
• Conductor cross-section, max. (IEC) mm 4 × 240 4 × 240 4 × 240 4 × 240
PE/GND connection PE bar PE bar PE bar PE bar
• Busbar cross-section mm2 600 600 600 600
• Conductor cross-section, max. (IEC) mm2 240 240 240 240
Cable length, max. 9) m (ft) 300/450 (984/1476) 300/450 (984/1476) 300/450 (984/1476) 300/450 (984/1476)
Shielded/unshielded
Degree of protection IP21 IP21 IP21 IP21
(standard version)
Dimensions
• Width mm (in) 600 (23.62) 600 (23.62) 600 (23.62) 600 (23.62)
• Height mm (in) 2200 (86.61) 2200 (86.61) 2200 (86.61) 2200 (86.61)
• Depth mm (in) 600 (23.62) 600 (23.62) 600 (23.62) 600 (23.62)
Weight, approx. kg (lb) 460 (1014) 460 (1014) 460 (1014) 470 (1036)
Frame size JXL JXL JXL JXL
Rated short-circuit current kA 84 100 100 100
according to IEC
1) 7)
Rated power of a typical 6-pole standard induction motor based on IL The value applies to coolants comprising water and a mixture of water
or IH for 400 V 3 AC 50 Hz. and antifreeze agent.
2) 8)
Rated power of a typical 6-pole standard induction motor based on IL The value is valid for water as coolant.
or IH for 460 V 3 AC 60 Hz. Additional information and notes on other coolants are provided in the
3)
The base-load current IL is based on a duty cycle of 110 % for 60 s SINAMICS Low Voltage Engineering Manual.
9)
or 150 % for 10 s with a duty cycle duration of 300 s. Total of all motor cables. Longer cable lengths for specific configurations
4)
The base-load current IH is based on a duty cycle of 150 % for 60 s are available on request.For additional information, please refer to the
or 160 % for 10 s with a duty cycle duration of 300 s. SINAMICS Low Voltage Engineering Manual.
10)
5)
Information regarding the correlation between the pulse frequency and This Motor Module has been specifically designed for loads demanding
max. output current/output frequency is provided in the SINAMICS Low a high dynamic performance. The derating factor kIGBT and the derating
Voltage Engineering Manual. characteristics can be ignored (see section "Duty cycles” in the SINAMICS
6)
Low Voltage Engineering Manual).
The specified power loss represents the maximum value at 100 %
utilization. The value is lower under normal operating conditions.

6/92 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Cabinet Modules


Liquid-cooled units
Motor Modules

■ Technical specifications
Line voltage 500 ... 690 V 3 AC Motor Modules
DC link voltage 675 … 1035 V DC 6SL3725-1TG31-0AA3 6SL3725-1TG31-5AA3 6SL3725-1TG32-2AA3 6SL3725-1TG33-3AA3
Type rating
• At IL (50 Hz 690 V) 1) kW 90 132 200 315
• At IH (50 Hz 690 V) 1) kW 75 110 160 250
• At IL (50 Hz 500 V) 1) kW 55 90 132 200
• At IH (50 Hz 500 V) 1) kW 55 90 132 200
• At IL (60 Hz 575 V) 2) hp 75 150 200 300
• At IH (60 Hz 575 V) 2) hp 75 125 200 250
Output current
• Rated current IN O A 100 150 215 330
• Base-load current IL3) A 95 142 208 320
• Base-load current IH 4) A 89 134 192 280
• Maximum current Imax O A 142 213 312 480
DC link current
• Rated current IN DC
when supplied via
- Basic Line Module A 122 183 263 403
- Active Line Module A 110 165 237 363
• Base-load current IL DC 3)
when supplied via
- Basic Line Module A 116 173 253 390
- Active Line Module A 105 156 229 352
• Base-load current IH DC 4)
when supplied via
- Basic Line Module A 108 163 234 341
- Active Line Module A 98 147 211 308
Current demand
• 24 V DC auxiliary power supply A 1,3 1,3 1,3 1,3
• 230 V 1 AC A 0.6 0.6 0.6 0.6
DC link capacitance F 2800 2800 4200 5800
Pulse frequency 5)
• Rated frequency kHz 1.25 1.25 1.25 1.25
• Pulse frequency, max.
- Without current derating kHz 1.25 1.25 1.25 1.25
- With current derating kHz 7.5 7.5 7.5 7.5
Power loss, max. 6)
at 50 Hz 690 V
6
• Degree of protection <IP55
- Dissipated to coolant kW 1.1 1.6 2.3 3.3
- Dissipated to ambient air kW 0.1 0.1 0.2 0.3
• Degree of protection IP55
- Dissipated to coolant kW 1.2 1.7 2.4 3.5
- Dissipated to ambient air kW 0.1 0.1 0.2 0.2
Coolant volume flow 7) l/min (US 9 (2.38) 9 (2.38) 12 (3.17) 12 (3.17)
All degrees of protection gal./min)
Liquid volume dm3 2.9/4.7 2.9/4.7 3.5/5.3 3.5/5.3
Degree of protection <IP55/IP55
Pressure drop, max. 8) Pa 150000 150000 150000 150000
for volume flow
Heat exchanger material Stainless steel Stainless steel Stainless steel Stainless steel
Sound pressure level LpA dB 52 52 52 52
(1 m) at 50/60 Hz
Motor connection M12 M12 M12 M12
U2, V2, W2
• Conductor cross-section, max. (IEC) mm2 2 × 95 2 × 95 2 × 240 2 × 240
PE/GND connection PE bar PE bar PE bar PE bar
• Busbar cross-section mm2 600 600 600 600
• Conductor cross-section, max. (IEC) mm2 240 240 240 240
Cable length, max. 9) m (ft) 300/450 (984/1476) 300/450 (984/1476) 300/450 (984/1476) 300/450 (984/1476)
Shielded/unshielded
Degree of protection IP21 IP21 IP21 IP21
(standard version)
Dimensions
• Width mm (in) 400 (15.75) 400 (15.75) 400 (15.75) 400 (15.75)
• Height mm (in) 2200 (86.61) 2200 (86.61) 2200 (86.61) 2200 (86.61)
• Depth mm (in) 600 (23.62) 600 (23.62) 600 (23.62) 600 (23.62)
Weight, approx. kg (lb) 280 (617) 280 (617) 320 (706) 320 (706)
Frame size FXL FXL GXL GXL
Short-circuit current rating kA 65 65 65 65
acc. to IEC
1) 6)
Rated power of a typical 6-pole standard induction motor based on IL The specified power loss represents the maximum value at 100 %
or IH for 500 V or 690 V 3 AC 50 Hz. utilization. The value is lower under normal operating conditions.
2) 7)
Rated power of a typical 6-pole standard induction motor based on IL The value applies to coolants comprising water and a mixture of water
or IH for 575 V 3 AC 60 Hz. and antifreeze agent.
3) 8)
The base-load current IL is based on a duty cycle of 110 % for 60 s The value is valid for water as coolant. Additional information and notes on
or 150 % for 10 s with a duty cycle duration of 300 s. other coolants are provided in the SINAMICS Low Voltage Engineering
4)
The base-load current IH is based on a duty cycle of 150 % for 60 s Manual.
9)
or 160 % for 10 s with a duty cycle duration of 300 s. Total of all motor cables. Longer cable lengths for specific configurations
5)
Information regarding the correlation between the pulse frequency and are available on request.For additional information, please refer to the
max. output current/output frequency is provided in the SINAMICS Low SINAMICS Low Voltage Engineering Manual.
Voltage Engineering Manual.

Siemens D 21.3 · 2022 6/93


© Siemens 2022

SINAMICS S120 Cabinet Modules


Liquid-cooled units
Motor Modules

■ Technical specifications
Line voltage 500 ... 690 V 3 AC Motor Modules
DC link voltage 675 … 1035 V DC 6SL3725-1TG34-7AA3 6SL3725-1TG35-8AA3 6SL3725-1TG37-4AA3 6SL3725-1TG38-0AA3 10)
Type rating
• At IL (50 Hz 690 V) 1) kW 450 560 710 800
• At IH (50 Hz 690 V) 1) kW 400 450 630 710
• At IL (50 Hz 500 V) 1) kW 315 400 500 560
• At IH (50 Hz 500 V) 1) kW 250 315 450 500
• At IL (60 Hz 575 V) 2) hp 450 600 700 800
• At IH (60 Hz 575 V) 2) hp 450 500 700 700
Output current
• Rated current IN O A 465 575 735 810
• Base-load current IL3) A 452 560 710 790
• Base-load current IH 4) A 416 514 657 724
• Maximum current Imax O A 678 840 1065 1185
DC link current
• Rated current IN DC
when supplied via
- Basic Line Module A 558 702 903 990
- Active Line Module A 502 632 808 891
• Base-load current IL DC 3)
when supplied via
- Basic Line Module A 544 683 870 948
- Active Line Module A 489 616 781 870
• Base-load current IH DC 4)
when supplied via
- Basic Line Module A 496 627 795 885
- Active Line Module A 446 565 732 808
Current demand
• 24 V DC auxiliary power supply A 1,5 1,5 1,5 1,5
• 230 V 1 AC A 0.6 0.6 0.6 0.6
DC link capacitance F 9670 9670 10500 10500
Pulse frequency 5)
• Rated frequency kHz 1.25 1.25 1.25 1.25
• Pulse frequency, max.
- Without current derating kHz 1.25 1.25 1.25 1.25
- With current derating kHz 7.5 7.5 7.5 7.5
Power loss, max. 6)
6 at 50 Hz 690 V
• Degree of protection <IP55
- Dissipated to coolant kW 5.3 5.5 7.5 8.3
- Dissipated to ambient air kW 0.4 0.5 0.6 0.7
• Degree of protection IP55
- Dissipated to coolant kW 5.6 5.8 7.9 8.8
- Dissipated to ambient air kW 0.2 0.2 0.2 0.2
Coolant volume flow 7) l/min (US 16 (4.23) 16 (4.23) 16 (4.23) 16 (4.23)
All degrees of protection gal./min)
Liquid volume dm3 3.3/5.1 3.3/5.1 3.3/5.1 3.3/5.1
Degree of protection <IP55/IP55
Pressure drop, max. 8) Pa 150000 150000 150000 150000
for volume flow
Heat exchanger material Aluminum Aluminum Aluminum Aluminum
Sound pressure level LpA dB 54 54 54 54
(1 m) at 50/60 Hz
Motor connection 2/M12 2/M12 2/M12 2/M12
U2, V2, W2
2
• Conductor cross-section, max. (IEC) mm 4 × 185 4 × 185 4 × 185 4 × 185
PE/GND connection PE bar PE bar PE bar PE bar
• Busbar cross-section mm2 600 600 600 600
2
• Conductor cross-section, max. (IEC) mm 240 240 240 240
Cable length, max. 9) m (ft) 300/450 (984/1476) 300/450 (984/1476) 300/450 (984/1476) 300/450 (984/1476)
Shielded/unshielded
Degree of protection IP21 IP21 IP21 IP21
(standard version)
Dimensions
• Width mm (in) 400 (15.75) 400 (15.75) 400 (15.75) 400 (15.75)
• Height mm (in) 2200 (86.61) 2200 (86.61) 2200 (86.61) 2200 (86.61)
• Depth mm (in) 600 (23.62) 600 (23.62) 600 (23.62) 600 (23.62)
Weight, approx. kg (lb) 350 (772) 350 (772) 350 (772) 350 (772)
Frame size HXL HXL HXL HXL
Rated short-circuit current kA 84 84 100 100
according to IEC
1) 7)
Rated power of a typical 6-pole standard induction motor based on IL The value applies to coolants comprising water and a mixture of water
or IH for 500 V or 690 V 3 AC 50 Hz. and antifreeze agent.
2) 8)
Rated power of a typical 6-pole standard induction motor based on IL The value is valid for water as coolant.
or IH for 575 V 3 AC 60 Hz. Additional information and notes on other coolants are provided in the
3)
The base-load current IL is based on a duty cycle of 110 % for 60 s SINAMICS Low Voltage Engineering Manual.
9)
or 150 % for 10 s with a duty cycle duration of 300 s. Total of all motor cables. Longer cable lengths for specific configurations
4)
The base-load current IH is based on a duty cycle of 150 % for 60 s are available on request.For additional information, please refer to the
or 160 % for 10 s with a duty cycle duration of 300 s. SINAMICS Low Voltage Engineering Manual.
10)
5)
Information regarding the correlation between the pulse frequency and The device is optimized for a base pulse frequency of 1.25 kHz. For an
max. output current/output frequency is provided in the SINAMICS Low increased pulse frequency or for certain overloads, the derating factor is
Voltage Engineering Manual. higher than that for the device with article number 6SL3325-1TG38-1AAx.
6)
The specified power loss represents the maximum value at 100 %
utilization. The value is lower under normal operating conditions.

6/94 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Cabinet Modules


Liquid-cooled units
Motor Modules

■ Technical specifications
Line voltage 500 ... 690 V 3 AC Motor Modules
DC link voltage 675 … 1035 V DC 6SL3725-1TG38-1AA3 6SL3725-1TG41-0AA3 6SL3725-1TG41-3AA3 6SL3725-1TG41-6AP3 10)
Type rating
• At IL (50 Hz 690 V) 1) kW 800 1000 1200 1500
• At IH (50 Hz 690 V) 1) kW 710 900 1000 1260
• At IL (50 Hz 500 V) 1) kW 560 710 900 1000
• At IH (50 Hz 500 V) 1) kW 560 630 800 900
• At IL (60 Hz 575 V) 2) hp 800 1000 1250 1500
• At IH (60 Hz 575 V) 2) hp 700 900 1000 1250
Output current
• Rated current IN O A 810 1025 1270 1560
• Base-load current IL3) A 790 1000 1230 1500
• Base-load current IH 4) A 724 917 1136 1370
• Maximum current Imax O A 1185 1500 1845 2250
DC link current
• Rated current IN DC
when supplied via
- Basic Line Module A 990 1250 1550 1903
- Active Line Module A 891 1125 1395 1714
• Base-load current IL DC 3)
when supplied via
- Basic Line Module A 963 1219 1500 1800
- Active Line Module A 869 1100 1353 1650
• Base-load current IH DC 4)
when supplied via
- Basic Line Module A 883 1118 1384 1680
- Active Line Module A 796 1009 1250 1550
Current demand
• 24 V DC auxiliary power supply A 1,5 1,5 1,5 1,5
• 230 V 1 AC A 0.6 0.6 0.6 0.6
DC link capacitance F 14000 16000 19330 21000
Pulse frequency 5)
• Rated frequency kHz 1.25 1.25 1.25 1.25
• Pulse frequency, max.
- Without current derating kHz 1.25 1.25 1.25 1.25
- With current derating kHz 7.5 7.5 7.5 7.5
Power loss, max. 6)
at 50 Hz 690 V
• Degree of protection <IP55
6
- Dissipated to coolant kW 9.0 10.0 12.9 17.1
- Dissipated to ambient air kW 1.1 1.2 1.4 1.6
• Degree of protection IP55
- Dissipated to coolant kW 9.8 11.2 14.0 18.4
- Dissipated to ambient air kW 0.3 0.3 0.3 0.3
Coolant volume flow 7) l/min (US 27 (7.13) 27 (7.13) 27 (7.13) 27 (7.13)
All degrees of protection gal./min)
Liquid volume dm3 5.2/7 5.2/7 5.2/7 5.2/7
Degree of protection <IP55/IP55
Pressure drop, max. 8) Pa 150000 150000 150000 150000
for volume flow
Heat exchanger material Aluminum Aluminum Aluminum Aluminum
Sound pressure level LpA dB 56 56 56 56
(1 m) at 50/60 Hz
Motor connection 2/M12 2/M12 2/M12 2/M12
U2, V2, W2
2
• Conductor cross-section, max. (IEC) mm 4 × 240 4 × 240 4 × 240 4 × 240
PE/GND connection PE bar PE bar PE bar PE bar
• Busbar cross-section mm2 600 600 600 600
2
• Conductor cross-section, max. (IEC) mm 240 240 240 240
Cable length, max. 9) m (ft) 300/450 (984/1476) 300/450 (984/1476) 300/450 (984/1476) 300/450 (984/1476)
Shielded/unshielded
Degree of protection IP21 IP21 IP21 IP21
(standard version)
Dimensions
• Width mm (in) 600 (23.62) 600 (23.62) 600 (23.62) 600 (23.62)
• Height mm (in) 2200 (86.61) 2200 (86.61) 2200 (86.61) 2200 (86.61)
• Depth mm (in) 600 (23.62) 600 (23.62) 600 (23.62) 600 (23.62)
Weight, approx. kg (lb) 460 (1014) 460 (1014) 460 (1014) 480 (1058)
Frame size JXL JXL JXL JXL
Rated short-circuit current kA 100 100 100 100
according to IEC
1) Rated power of a typical 6-pole standard induction motor based on IL 7) The value applies to coolants comprising water and a mixture of water
or IH for 500 V or 690 V 3 AC 50 Hz. and antifreeze agent.
2) Rated power of a typical 6-pole standard induction motor based on IL 8) The value is valid for water as coolant.
or IH for 575 V 3 AC 60 Hz. Additional information and notes on other coolants are provided in the
3) The base-load current IL is based on a duty cycle of 110 % for 60 s SINAMICS Low Voltage Engineering Manual.
or 150 % for 10 s with a duty cycle duration of 300 s. 9) Total of all motor cables. Longer cable lengths for specific configurations
4) The base-load current IH is based on a duty cycle of 150 % for 60 s are available on request.For additional information, please refer to the
or 160 % for 10 s with a duty cycle duration of 300 s. SINAMICS Low Voltage Engineering Manual.
10) Additional duty cycle for output frequencies from 5 Hz to 10 Hz: Base-load
5) Information regarding the correlation between the pulse frequency and
max. output current/output frequency is provided in the SINAMICS Low current = 1460 A, short-time current = 2340 A for 5 s with a duty cycle
Voltage Engineering Manual. duration of 600 s. For output frequencies from 1 Hz to 5 Hz, the short-time
6)
current is 1900 A for 5 s.
The specified power loss represents the maximum value at 100 %
utilization. The value is lower under normal operating conditions.

Siemens D 21.3 · 2022 6/95


© Siemens 2022

SINAMICS S120 Cabinet Modules


Liquid-cooled units
Motor Modules compact

■ Overview ■ Design
Motor Modules contain the following components as standard:
• Retaining device for the DC busbar, including the connection
to the DC connections of the Motor Module
• Connection busbars, nickel-plated
- on Motor Modules, frame size JXL, the connection for the
motor cables is routed below the device
• Cable retaining bar for the power cables
• DRIVE-CLiQ interface (three DRIVE-CLiQ sockets), without
Control Unit
• Auxiliary power supply system (4-pole) for the auxiliary power
supply, including cable connections for looping through to the
next Cabinet Module
• Nickel-plated PE busbar (60 x 10 mm), including jumper for
looping through to the next Cabinet Module
• EMC-compliant design thanks to additional shielding
measures and appropriately routed cables

Motor Modules are available in the power range from 90 kW


to 1500 kW.
■ Selection and ordering data
Type rating Rated output current Motor Module compact
Line voltage DC link voltage Type rating at 400 V or 690 V IN
380 ... 480 V 3 AC 510 ... 720 V DC 560 ... 800 kW kW A Article No.
500 ... 690 V 3 AC 675 ... 1035 V DC 800 ... 1500 kW Line voltage 380 ... 480 V 3 AC
(DC link voltage 510 ... 720 V DC)
Motor Modules with the supplementary designation
compact are installed in a compact cabinet 400 mm wide, 560 985 6SL3725-1TE41-0MA3
therefore differing from the Motor Modules with an identical 710 1260 6SL3725-1TE41-2MA3
power rating installed in a 600 mm-wide cabinet. 800 1405 6SL3725-1TE41-4MA3
6 By connecting in parallel up to four Motor Modules compact, Line voltage 500 ... 690 V 3 AC
which are operated on one Control Unit and supply one motor, (DC link voltage 675 ... 1035 V DC)
it is possible to increase the available shaft power to 800 810 6SL3725-1TG38-1MA3
max. approx. 5700 kW (taking into account the derating factors
according to the SINAMICS Low Voltage Engineering Manual). 1000 1025 6SL3725-1TG41-0MA3
1200 1270 6SL3725-1TG41-3MA3
The Motor Modules can also be used as Braking Modules
(braking chopper) if a 3-phase braking resistor is connected 1500 1560 6SL3725-1TG41-6MP3
instead of a motor.
Further information can be found in the SINAMICS Low Voltage
Engineering Manual.

6/96 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Cabinet Modules


Liquid-cooled units
Motor Modules compact

■ Integration
Motor Modules compact are controlled by the CU320-2 DP or The Control Unit must be mounted externally, the DRIVE-CLiQ
CU320-2 PN Control Unit. Communication between the Control cable will not be included in the scope of supply and must be
Unit and Modules is established via a DRIVE-CLiQ connection. configured on site.
For additional information, please refer to the SINAMICS Low
Voltage Engineering Manual.

Cabinet Module
DC busbar

230 V AC
24 V DC
Auxiliary power supply X400 X401 X402
-F150

-F160

DC fuses

DRIVE-CLiQ socket 0

DRIVE-CLiQ socket 2
DRIVE-CLiQ socket 1
Motor Module
DCP
DCN

Z READY
LEDs
-X9
1 P24 V DC LINK
1 POWER OK
2
2
M
IPD card 6
3
4 Internal
5 power
supply -X2
6 U2
7 =
V2 M
Y 8 ~ W2 3~
PE

-X41
4 +Temp
X 3 -Temp
2 EP +24 V
1 EP M1 M
-X46
1 BR Output+
2 BR Output- Cooling circuit
3 FB Input+
4 FB Input-

-X42
1 P24L
2 P24L
3 M
4 M
G_D213_EN_00102a

Cooling circuit

X Connection of temperature sensor for motors without DRIVE-CliQ interface

Y Required for Safety Integrated

Z Door fan -G160 (IP21, IP23, IP43, IP54) or heat exchanger -E160 (IP55)

Connection example of a Motor Module compact, liquid-cooled

Siemens D 21.3 · 2022 6/97


© Siemens 2022

SINAMICS S120 Cabinet Modules


Liquid-cooled units
Motor Modules compact

■ Technical specifications
Line voltage 380 ... 480 V 3 AC Motor Modules compact
DC link voltage 510 ... 720 V DC 6SL3725-1TE41-0MA3 6SL3725-1TE41-2MA3 6SL3725-1TE41-4MA3
Type rating
• At IL (50 Hz 400 V) 1) kW 560 710 800
• At IH (50 Hz 400 V) 1) kW 450 630 710
• At IL (60 Hz 460 V) 2) hp 800 1000 1150
• At IH (60 Hz 460 V) 2) hp 700 900 1000
Output current
• Rated current IN O A 985 1260 1405
• Base-load current IL3) A 960 1230 1370
• Base-load current IH4) A 860 1127 1257
• Maximum current Imax O A 1440 1845 2055
DC link current
• Rated current IN DC
when supplied via
- Basic Line Module A 1202 1512 1714
- Active Line Module A 1080 1361 1544
• Base-load current IL DC 3)
when supplied via
- Basic Line Module A 1170 1474 1670
- Active Line Module A 1051 1326 1500
• Base-load current IH DC 4)
when supplied via
- Basic Line Module A 1048 1345 1532
- Active Line Module A 942 1211 1377
Current demand
• 24 V DC auxiliary power supply A 1.5 1.5 1.5
• 230 V 1 AC A 0.6 0.6 0.6
DC link capacitance F 21000 29000 29000
Pulse frequency 5)
• Rated frequency kHz 1.25 1.25 1.25
• Pulse frequency, max.
- Without current derating kHz 1.25 1.25 1.25
- With current derating kHz 8 8 8
Power loss, max. 6)
at 50 Hz 400 V
6 • Degree of protection <IP55
- Dissipated to coolant
- Dissipated to ambient air
kW
kW
7.5
1.0
8.6
1.3
9.5
1.5
• Degree of protection IP55
- Dissipated to coolant kW 8.3 9.6 10.7
- Dissipated to ambient air kW 0.2 0.3 0.3
Coolant volume flow 7) l/min (US 27 (7.13) 27 (7.13) 27 (7.13)
All degrees of protection gal./min)
Liquid volume dm3 5.2/7 5.2/7 5.2/7
Degree of protection <IP55/IP55
Pressure drop, max. 8) Pa 150000 150000 150000
for volume flow
Heat exchanger material Aluminum Aluminum Aluminum
Sound pressure level LpA dB 56 56 56
(1 m) at 50/60 Hz
Motor connection 10/M12 10/M12 10/M12
U2, V2, W2
• Conductor cross-section, max. (IEC) mm2 10 × 95 10 × 95 10 × 95
PE/GND connection PE bar PE bar PE bar
• Busbar cross-section mm2 600 600 600
• Conductor cross-section, max. (IEC) mm2 240 240 240
Cable length, max. 9) m (ft) 300/450 (984/1476) 300/450 (984/1476) 300/450 (984/1476)
Shielded/unshielded
Degree of protection IP21 IP21 IP21
(standard version)
Dimensions
• Width mm (in) 400 (15.7) 400 (15.7) 400 (15.7)
• Height mm (in) 2200 (86.6) 2200 (86.6) 2200 (86.6)
• Depth mm (in) 600 (23.6) 600 (23.6) 600 (23.6)
Weight, approx. kg (lb) 440 (970) 440 (970) 440 (970)
Frame size JXL JXL JXL
Rated short-circuit current kA 84 100 100
according to IEC

1) 6)
Rated power of a typical 6-pole standard induction motor based on IL The specified power loss represents the maximum value at 100 %
or IH for 400 V 3 AC 50 Hz. utilization. The value is lower under normal operating conditions.
2) 7)
Rated power of a typical 6-pole standard induction motor based on IL The value applies to coolants comprising water and a mixture of water
or IH for 460 V 3 AC 60 Hz. and antifreeze agent.
3) 8)
The base-load current IL is based on a duty cycle of 110 % for 60 s The value is valid for water as coolant.
or 150 % for 10 s with a duty cycle duration of 300 s. Additional information and notes on other coolants are provided in the
4)
The base-load current IH is based on a duty cycle of 150 % for 60 s SINAMICS Low Voltage Engineering Manual.
9)
or 160 % for 10 s with a duty cycle duration of 300 s. Total of all motor cables. Longer cable lengths for specific configurations
5)
Information regarding the correlation between the pulse frequency and are available on request.For additional information, please refer to the
max. output current/output frequency is provided in the SINAMICS Low SINAMICS Low Voltage Engineering Manual.
Voltage Engineering Manual.

6/98 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Cabinet Modules


Liquid-cooled units
Motor Modules compact

■ Technical specifications
Line voltage 500 ... 690 V 3 AC Motor Modules compact
DC link voltage 675 … 1035 V DC 6SL3725-1TG38-1MA3 6SL3725-1TG41-0MA3 6SL3725-1TG41-3MA3 6SL3725-1TG41-6MP3 10)
Type rating
• At IL (50 Hz 690 V) 1) kW 800 1000 1200 1500
• At IH (50 Hz 690 V) 1) kW 710 900 1000 1260
• At IL (50 Hz 500 V) 1) kW 560 710 900 1000
• At IH (50 Hz 500 V) 1) kW 560 630 800 900
• At IL (60 Hz 575 V) 2) hp 800 1000 1250 1500
• At IH (60 Hz 575 V) 2) hp 700 900 1000 1250
Output current
• Rated current IN O A 810 1025 1270 1560
• Base-load current IL3) A 790 1000 1230 1500
• Base-load current IH 4) A 724 917 1136 1370
• Maximum current Imax O A 1185 1500 1845 2250
DC link current
• Rated current IN DC
when supplied via
- Basic Line Module A 990 1250 1550 1903
- Active Line Module A 891 1125 1395 1714
• Base-load current IL DC 3)
when supplied via
- Basic Line Module A 963 1219 1500 1800
- Active Line Module A 869 1100 1353 1650
• Base-load current IH DC 4)
when supplied via
- Basic Line Module A 883 1118 1384 1680
- Active Line Module A 796 1009 1250 1550
Current demand
• 24 V DC auxiliary power supply A 1.5 1.5 1.5 1.5
• 230 V 1 AC A 0.6 0.6 0.6 0.6
DC link capacitance F 14000 16000 19330 21000
Pulse frequency 5)
• Rated frequency kHz 1.25 1.25 1.25 1.25
• Pulse frequency, max.
- Without current derating kHz 1.25 1.25 1.25 1.25
- With current derating kHz 7.5 7.5 7.5 7.5
Power loss, max. 6)
at 50 Hz 690 V
• Degree of protection <IP55
6
- Dissipated to coolant kW 9.0 10.0 12.9 17.1
- Dissipated to ambient air kW 1.1 1.2 1.4 1.6
• Degree of protection IP55
- Dissipated to coolant kW 9.8 11.2 14.0 18.4
- Dissipated to ambient air kW 0.3 0.3 0.3 0.3
Coolant volume flow 7) l/min (US 27 (7.13) 27 (7.13) 27 (7.13) 27 (7.13)
All degrees of protection gal./min)
Liquid volume dm3 5.2/7 5.2/7 5.2/7 5.2/7
Degree of protection <IP55/IP55
Pressure drop, max. 8) Pa 150000 150000 150000 150000
for volume flow
Heat exchanger material Aluminum Aluminum Aluminum Aluminum
Sound pressure level LpA dB 56 56 56 56
(1 m) at 50/60 Hz
Motor connection 10/M12 10/M12 10/M12 10/M12
U2, V2, W2
2
• Conductor cross-section, max. (IEC) mm 10 × 95 10 × 95 10 × 95 10 × 95
PE/GND connection PE bar PE bar PE bar PE bar
• Busbar cross-section mm2 600 600 600 600
2
• Conductor cross-section, max. (IEC) mm 240 240 240 240
Cable length, max. 9) m (ft) 300/450 (984/1476) 300/450 (984/1476) 300/450 (984/1476) 300/450 (984/1476)
Shielded/unshielded
Degree of protection IP21 IP21 IP21 IP21
(standard version)
Dimensions
• Width mm (in) 400 (15.7) 400 (15.7) 400 (15.7) 400 (15.7)
• Height mm (in) 2200 (86.6) 2200 (86.6) 2200 (86.6) 2200 (86.6)
• Depth mm (in) 600 (23.6) 600 (23.6) 600 (23.6) 600 (23.6)
Weight, approx. kg (lb) 440 (970) 440 (970) 440 (970) 460 (1014)
Frame size JXL JXL JXL JXL
Rated short-circuit current kA 100 100 100 100
according to IEC
1) 7)
Rated power of a typical 6-pole standard induction motor based on IL The value applies to coolants comprising water and a mixture of water
or IH for 500 V or 690 V 3 AC 50 Hz. and antifreeze agent.
2) 8)
Rated power of a typical 6-pole standard induction motor based on IL The value is valid for water as coolant.
or IH for 575 V 3 AC 60 Hz. Additional information and notes on other coolants are provided in the
3)
The base-load current IL is based on a duty cycle of 110 % for 60 s SINAMICS Low Voltage Engineering Manual.
9)
or 150 % for 10 s with a duty cycle duration of 300 s. Total of all motor cables. Longer cable lengths for specific configurations
4)
The base-load current IH is based on a duty cycle of 150 % for 60 s are available on request.For additional information, please refer to the
or 160 % for 10 s with a duty cycle duration of 300 s. SINAMICS Low Voltage Engineering Manual.
10)
5)
Information regarding the correlation between the pulse frequency and Additional duty cycle for output frequencies from 5 Hz to 10 Hz: Base-load
max. output current/output frequency is provided in the SINAMICS Low current = 1460 A, short-time current = 2340 A for 5 s with a duty cycle
Voltage Engineering Manual. duration of 600 s. For output frequencies from 1 Hz to 5 Hz, the short-time
6)
current is 1900 A for 5 s.
The specified power loss represents the maximum value at 100 %
utilization. The value is lower under normal operating conditions.

Siemens D 21.3 · 2022 6/99


© Siemens 2022

SINAMICS S120 Cabinet Modules


Liquid-cooled units
Auxiliary Power Supply Modules

■ Overview ■ Design
The Auxiliary Power Supply Module is connected in the
customer's plant to a voltage corresponding to the respective
rated unit voltage.
The standard version contains the following components:
• Fuse switch disconnector with fuse monitoring for external
evaluation
• Supply of auxiliary power supply system with 2 auxiliary
voltages:
- 24 V DC for the electronics power supply
- 230 V 2 AC to supply 230 V loads
• Transformer with 230 V output voltage
• SITOP 24 V DC power supply
• Nickel-plated PE busbar (60 mm × 10 mm), including jumper
for looping through to the next Cabinet Module

■ Selection and ordering data


Auxiliary Power Supply Modules supply the auxiliary power Plant-side power supply Auxiliary Power Supply
supply system for the SINAMICS S120 Cabinet Modules as well (380 ... 690 V 3 AC) Module
as additional external loads. The heat exchangers, which are A Article No.
installed in the Cabinet Modules with degree of protection IP55,
25 6SL3705-0MX22-0AA3
are one of the connections to the auxiliary power supply system.
In addition, the auxiliary power supply system supplies the
electronic modules with an external voltage of 24 V DC. This is
required when the DC link is not charged, for instance, in order
to maintain PROFIBUS/PROFINET communication.
The Auxiliary Power Supply Module provides an expansion to
the option K76 (auxiliary voltage generating unit in the Line
6 Connection Module) if higher power ratings are required.

6/100 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Cabinet Modules


Liquid-cooled units
Auxiliary Power Supply Modules

■ Integration
Cabinet Module
DC busbar

230 V AC
24 V DC
Auxiliary power supply
-X150 -X140

Auxiliary Power
Supply Module

= -F21
-T24
~
-X46 -F24
1
2
3
4

-Q1
L1

L2
-T2
-F20 -F22 -X47 6
1
L3 2
3
4
-Q2 11
12
13
Fuse
14 monitoring
15
16
17
18
G_D213_EN_00112

Cooling circuit

Connection example of an Auxiliary Power Supply Module, liquid-cooled

Siemens D 21.3 · 2022 6/101


© Siemens 2022

SINAMICS S120 Cabinet Modules


Liquid-cooled units
Auxiliary Power Supply Modules

■ Technical specifications
Auxiliary Power Supply Module
6SL3705-0MX22-0AA3
Plant-side power supply A 25
380 ... 690 V 3 AC
Line supply connection
• Conductor cross-section, max. (IEC) mm2 70
• Recommended conductor cross-sec- mm2 6
tion
Max. current carrying capacity
• Load connection
230 V 2 AC
- To auxiliary power supply A 10
- To customer terminal -X47 A 10
• Load connection
24 V DC
- To auxiliary power supply A 20
Cable cross-section, max.
• Connection -X47 mm2 2.5
Cooling air requirement Natural convection
PE/GND connection PE bar
• Busbar cross-section mm2 600
• Conductor cross-section, max. (IEC) mm2 240
Degree of protection IP21
Dimensions
• Width mm (in) 600 (23.62)
• Height mm (in) 2200 (86.61)
• Depth mm (in) 600 (23.62)

6 Weight, approx.
Short-circuit current rating acc. to IEC kA
kg (lb) 160 (353)
80
Minimum short-circuit current 1) kA 0.4

1)
Current required to ensure reliable tripping of installed protective devices.

6/102 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Cabinet Modules


Liquid-cooled units
Heat Exchanger Modules

■ Overview ■ Design
The deionized water is monitored by the converter itself to
ensure intrinsic protection. The operating status is signaled to
the converter.
Heat Exchanger Modules contain the following components
as standard:
• 1 pump
• 1 stainless steel plate-type heat exchanger
• 1 3-way valve
• Filter, expansion chamber, vent, safety valve, pressure
sensors, pressure display, temperature sensor, TM31 and
TM150 Terminal Modules
Scope of supply:
The pipe connections (couplings) for connection to the
deionized water circuit on the converter side are included in the
scope of supply of the Heat Exchanger Modules. The pipe
connections (couplings) for connection to the raw water circuit
Heat Exchanger Modules are used to dissipate the power loss on the plant/system side are not components of the scope of
from the converter. They comprise a deionized water circuit on supply. For this connection, a connecting pipe and a pipe
the converter side and a raw water circuit on the plant side. coupling with the appropriate diameter must be used.
The respective data is given in the Technical specifications.
The hot deionized water in the circuit on the converter side
passes through a low-maintenance circulating pump Note:
(2 redundant pumps with option W01) into the water/water plate- Heat Exchanger Modules can only be located at the beginning
type heat exchanger. This is made of stainless steel and or end of a cabinet row for technical reasons. The cooling water
connected to the raw water circuit on the plant side. on the plant side is fed into the Heat Exchanger Module from
The deionized water is cooled there by the raw water of the outer above as standard.
circuit and flows back into the drive.
The closed converter-side deionized water circuit is filled
with coolant in accordance with the requirements in section
■ Selection and ordering data 6
"Cooling circuit and coolant quality" and deaerated before Cooling power Heat Exchanger Module
commissioning. The pressure is maintained by means of an
expansion chamber. Any residual air that arises in the circuit kW Article No.
during operation is removed via automatic vents. Line voltage 380 ... 415 V 3 AC, 50 Hz; 440 ... 480 V 3 AC, 60 Hz

To avoid condensation at excessively low coolant temperatures, 32 6SL3705-0RE23-2AA5


a 3-way valve for controlling the coolant temperature is installed. 48 6SL3705-0RE24-8AA5
The Heat Exchanger Modules are controlled and monitored in 72 6SL3705-0RE27-2AA5
the external CU320-2 Control Unit or CU310-2 Control Unit 120 6SL3705-0RE31-1AA5
(as of V1.2 on request) as "Technology Extension HEM". This
means that the Heat Exchanger Modules are controlled and Line voltage 500 ... 690 V 3 AC, 50/60 Hz
monitored in a drive-related manner which therefore increases 32 6SL3705-0RG23-2AA5
usability. The system parameters of the Heat Exchanger 48 6SL3705-0RG24-8AA5
Modules can be accessed using the familiar tools (SINAMICS
Startdrive or STARTER). 72 6SL3705-0RG27-2AA5
120 6SL3705-0RG31-1AA5
Functionalities for avoiding condensation are integrated and can
be parameterized together with further settings. Integration into
the drive system means that integration into higher-level control
systems to visualize signals and messages is considerably
easier.
When ordering a Heat Exchanger Module, the SINAMICS
Technology Extension HEM license (CoL) required for operation
is included in electronic form.
Heat Exchanger Modules are available for the following voltages
and cooling power ratings:
Line voltage Cooling power
380 ... 415 V 3 AC, 50 Hz 32 ... 120 kW
500 ... 690 V 3 AC, 50 Hz 32 ... 120 kW

Heat Exchanger Modules for the line voltages 440 V to 480 V,


60 Hz are available as option C95 and 500 V to 690 V, 60 Hz as
option C97.

Siemens D 21.3 · 2022 6/103


© Siemens 2022

SINAMICS S120 Cabinet Modules


Liquid-cooled units
Heat Exchanger Modules

■ Integration
Cabinet Module

Heat Exchanger Module

Infeed 3 AC X1:L1/L2/L3 Manual-Auto Pump on Pump 1/2

Power supply X6:1/3 -S3 -S2 -S1


24 V DC
X500 X501 X500 X501

LED LED

DRIVE-CLiQ socket

DRIVE-CLiQ socket

DRIVE-CLiQ socket

DRIVE-CLiQ socket
RDY RDY

Terminal Module Terminal Module


TM150 1) TM31

6
PT TCI M Plate-type TCI
heat exchanger
C A

P PT
D B

Pump

Converter-side Plant-side raw


deionized water circuit water circuit

G_D213_EN_00110a
1) TM150 only with option W62

Connection example of a Heat Exchanger Module, liquid-cooled

6/104 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Cabinet Modules


Liquid-cooled units
Heat Exchanger Modules

■ Technical specifications
The Heat Exchanger Modules must be selected appropriately The volume flow of coolant stated in the technical data of the
for the required cooling power and the required volume flow of Cabinet Modules must also be added.
coolant in the converter-side deionized water circuit. The values
stated in the technical specifications of the Cabinet Modules for If either of the two total values exceeds the values defined in the
the heat loss dissipated into the coolant must be summated. technical specifications of the Heat Exchanger Module (cooling
The total value is then the required cooling power. power and volume flow of coolant for converter-side deionized
water), the next larger Heat Exchanger Module must be selected.
Line voltage 380 … 415 V 3 AC 50 Hz Heat Exchanger Modules
Line voltage 440 ... 480 V 3 AC 60 Hz 1)
6SL3705-0RE23-2AA5 6SL3705-0RE24-8AA5 6SL3705-0RE27-2AA5 6SL3705-0RE31-1AA5
Cooling power kW 32 48 72 120
Deionized water circuit (on the converter side)
Inlet temperature
• Min. °C (°F) Depending on the ambient temperature and humidity of the air (see table for the dew point in
section Liquid-cooled Cabinet Modules  Protection against condensation)
• Max.
- Drive line-up degree of protection <IP55 °C (°F) 45 (113) 45 (113) 45 (113) 45 (113)
- Drive line-up degree of protection IP55 °C (°F) 40 (104) 40 (104) 40 (104) 40 (104)
Intake pressure
• Min. bar 1.7 1.7 1.7 1.7
• Max. bar 6 6 6 6
2)
Coolant volume flow l/min (US 88 (23.2) 132 (34.9) 197 (52.0) 267 (70.5)
gal./min)
Liquid volume l (US gal.) 20.4 (5.4) 21.4 (5.7) 30.5 (8.1) 32.5 (8.6)
Intake/return connection
• External diameter x wall thickness mm (in) 76.1 x 2 (3.00 × 0.08) 76.1 x 2 (3.00 × 0.08) 76.1 x 2 (3.00 × 0.08) 76.1 x 2 (3.00 × 0.08)
Raw water circuit (on the plant side)
Inlet temperature
• Min. °C (°F) 5 (41.0) 3) 5 (41.0) 3) 5 (41.0) 3) 5 (41.0) 3)
• Max.
- Drive line-up degree of protection <IP55
- Drive line-up degree of protection IP55
°C (°F)
°C (°F)
38 (100)
33 (91.4)
38 (100)
33 (91.4)
38 (100)
33 (91.4)
38 (100)
33 (91.4) 6
Intake pressure, max. bar 6 6 6 6
Coolant volume flow 2) l/min (US 132 (34.9) 198 (52.3) 263 (69.5) 445 (118)
gal./min)
Intake/return connection
• External diameter x wall thickness mm (in) 42 x 1.5 (1.65 × 0.06) 42 x 1.5 (1.65 × 0.06) 76.1 x 2 (3.00 × 0.08) 76.1 x 2 (3.00 × 0.08)
General data
Heat exchanger material Stainless steel Stainless steel Stainless steel Stainless steel
Current consumption
• Operating current, total A 7.5/7.0 7.5/7.0 11.0/12.0 11.0/12.0
at 50/60 Hz 400 V
• Electronics current (24 V DC) A 1.0 1.0 1.0 1.0
Power consumption, max. kW 3.5/4.7 3.5/4.7 5.5/6.4 5.5/6.4
at 50/60 Hz 400 V
Sound pressure level LpA dB 60 60 60 60
(1 m) at 50 Hz
Line supply connection Terminal Terminal Terminal Terminal
L1, L2, L3
• Conductor cross-section, max. (IEC) mm2 4 4 4 4
PE/GND connection Terminal Terminal Terminal Terminal
• Conductor cross-section, max. (IEC) mm2 4 4 4 4
Degree of protection IP55 IP55 IP55 IP55
(standard version)
Dimensions
• Width 4) mm (in) 600 (23.6) 600 (23.6) 600 (23.6) 600 (23.6)
• Height mm (in) 2200 (86.6) 2200 (86.6) 2200 (86.6) 2200 (86.6)
• Depth mm (in) 600 (23.6) 600 (23.6) 600 (23.6) 600 (23.6)
Weight, approx. 5) kg (lb) 310 (683) 310 (683) 320 (705) 320 (705)
(standard version)

1) Heat Exchanger Modules 440 V to 480 V, 60 Hz available with option C95 3) 0 °C (32 °F) with antifreeze (see derating characteristics).
2) The value is valid for water as coolant. 4) With option W01, the cabinet width increases to 1000 mm (39.37 in).
For other coolants, see section Cooling circuit and coolant properties. 5) With option W01, the cabinet weight increases by approximately 110 kg
(243 lb).

Siemens D 21.3 · 2022 6/105


© Siemens 2022

SINAMICS S120 Cabinet Modules


Liquid-cooled units
Heat Exchanger Modules

■ Technical specifications
With Heat Exchanger Modules for line voltages of 500 ... 690 V
3 AC, the voltage is adapted to the 400 V 3 AC/50 Hz or
460 V/60 Hz supply voltage of the pump using a transformer.
Line voltage 500 … 690 V 3 AC 50 Hz Heat Exchanger Modules
Line voltage 500 ... 690 V 3 AC 60 Hz1)
6SL3705-0RG23-2AA5 6SL3705-0RG24-8AA5 6SL3705-0RG27-2AA5 6SL3705-0RG31-1AA5
Cooling power kW 32 48 72 120
Deionized water circuit (on the converter side)
Inlet temperature
• Min. °C (°F) Depending on the ambient temperature and humidity of the air (see table for the dew point in sec-
tion Liquid-cooled Cabinet Modules  Protection against condensation)
• Max.
- Drive line-up degree of protection <IP55 °C (°F) 45 (113) 45 (113) 45 (113) 45 (113)
- Drive line-up degree of protection IP55 °C (°F) 40 (104) 40 (104) 40 (104) 40 (104)
Intake pressure
• Min. bar 1.7 1.7 1.7 1.7
• Max. bar 6 6 6 6
Coolant volume flow 2) l/min (US 88 (23.2) 132 (34.9) 197 (52.0) 267 (70.5)
gal./min)
Liquid volume l (US gal.) 20.4 (5.4) 21.4 (5.7) 30.5 (8.1) 32.5 (8.6)
Intake/return connection
• External diameter x wall thickness mm (in) 76.1 x 2 (3.00 × 0.08) 76.1 x 2 (3.00 × 0.08) 76.1 x 2 (3.00 × 0.08) 76.1 x 2 (3.00 × 0.08)
Raw water circuit (on the plant side)
Inlet temperature
• Min. °C (°F) 5 (41.0) 3) 5 (41.0) 3) 5 (41.0) 3) 5 (41.0) 3)
• Max.

6 - Drive line-up degree of protection <IP55


- Drive line-up degree of protection IP55
°C (°F)
°C (°F)
38 (100)
33 (91.4)
38 (100)
33 (91.4)
38 (100)
33 (91.4)
38 (100)
33 (91.4)
Intake pressure, max. bar 6 6 6 6
Coolant volume flow 2) l/min (US 132 (34.9) 198 (52.3) 263 (69.5) 445 (118)
gal./min)
Intake/return connection
• External diameter x wall thickness mm (in) 42 x 1.5 (1.65 × 0.06) 42 x 1.5 (1.65 × 0.06) 76.1 x 2 (3.00 × 0.08) 76.1 x 2 (3.00 × 0.08)
General data
Heat exchanger material Stainless steel Stainless steel Stainless steel Stainless steel
Current consumption
• Operating current, total A 4.4/4.1 4.4/4.1 6.4/7.0 6.4/7.0
at 50/60 Hz 690 V
• Electronics current (24 V DC) A 1.0 1.0 1.0 1.0
Power consumption, max. kW 3.5/4.7 3.5/4.7 5.5/6.4 5.5/6.4
at 50/60 Hz 690 V
Sound pressure level LpA dB 60 60 60 60
(1 m) at 50/60 Hz
Line supply connection Terminal Terminal Terminal Terminal
L1, L2, L3
2
• Conductor cross-section, max. (IEC) mm 4 4 4 4
PE/GND connection Terminal Terminal Terminal Terminal
• Conductor cross-section, max. (IEC) mm2 4 4 4 4
Degree of protection IP55 IP55 IP55 IP55
(standard version)
Dimensions
• Width 4) mm (in) 600 (23.6) 600 (23.6) 600 (23.6) 600 (23.6)
• Height mm (in) 2200 (86.6) 2200 (86.6) 2200 (86.6) 2200 (86.6)
• Depth mm (in) 600 (23.6) 600 (23.6) 600 (23.6) 600 (23.6)
Weight, approx. 5) kg (lb) 350 (772) 350 (772) 360 (794) 360 (794)
(standard version)

1) 3)
Heat Exchanger Modules 500 V to 690 V, 60 Hz available with option C97 0 °C (32 °F) with antifreeze (see derating characteristics).
2) 4)
The value is valid for water as coolant. With option W01, the cabinet width increases to 1000 mm (39.37 in)
For other coolants, see section Cooling circuit and coolant properties. 5)
With option W01, the cabinet weight increases by approximately 110 kg
(243 lb).

6/106 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Cabinet Modules


Liquid-cooled units
Heat Exchanger Modules

■ Accessories
Components for filling the cooling circuit with liquid-cooled
SINAMICS S120 Cabinet Modules
For commissioning and filling the deionized water circuit on the
converter side with the corresponding cooling medium,
the following components are needed:
• 1 pump
• 1 vessel with capacity of 100 l
• 1 hose (1/2")
• 1 ball valve
The coolant base must be mixed before filling the cooling circuit
with the coolant additive. 100+ liter drums are suitable for this
purpose, for example.
We recommend that a drum pump is used that can produce
a pressure of 3 bar. The following pumps are recommended
for filling:
• Drum and container pumps for emptying the drum, RE-PP,
for corrosive and neutral liquids from Lutz Pumpen GmbH,
www.lutz-pumpen.com or
• Chemical pumps, electrical drum pumps from Sinntec
Schmiersysteme GmbH, www.sinntec.de
Note:
When placing an order, please state that a hose (1/2"), a ball
valve, and a terminal piece are required for a connection with
1/2" on the pump outlet.

Siemens D 21.3 · 2022 6/107


© Siemens 2022

SINAMICS S120 Cabinet Modules

Options

■ Overview
The following table provides an overview of all of the available options – and their assignment to the individual Cabinet Modules.
SINAMICS S120 Cabinet Modules Air-cooled Liquid-cooled
Cabinet Modules Cabinet Modules

Active Line Module with Active Interface Module

Active Line Connection Module compact


Motor Module Booksize (Base Cabinet)
Motor Module Booksize (Cabinet Kit)

Active Line Connection Module


Auxiliary Power Supply Module

Auxiliary Power Supply Module


Basic Line Connection Module
Line Connection Module

Heat Exchanger Module


Central Braking Module

Motor Module compact


Motor Module Chassis
Smart Line Module
Basic Line Module

Motor Module
Order code Options
C95 Supply voltage for the Heat Exchanger Module, – – – – – – – – – – – – – – – 
440 .. 480 V/60 Hz
C97 Supply voltage for the Heat Exchanger Module, – – – – – – – – – – – – – – – 
500 .. 690 V/60 Hz
G33 1) CBE20 Communication Board –     –  – –   –  – – –
G51 1 x TM150 temperature sensor evaluation unit  – – –  –  – –   –  – – –
G52 2 x TM150 temperature sensor evaluation units  – – –  –  – –   –  – – –
G53 3 x TM150 temperature sensor evaluation units  – – – – – – – –   – – – – –
G54 4 x TM150 temperature sensor evaluation units  – – – – – – – –   – – – – –
6 G56 Contactor monitoring –    3) – – – – – – – – – – – –
G60 TM31 Terminal Module – – – –  –  – –   –  – – –
G61 Additional TM31 Terminal Module – – – –  –  – –   –  – – –
G62 1) TB30 Terminal Board –     –  – –   –  – – –
K01 to K05 Safety license Extended Functions for 1 to 5 axes – – – –  –  – – – – –  – – –
K08 1) AOP30 Advanced Operator Panel installed in –     –  – –   –  – – –
the cabinet door
K46 SMC10 Sensor Module Cabinet-Mounted – – – –  –  – – – – –  – – –
K48 SMC20 Sensor Module Cabinet-Mounted – – – –  –  – – – – –  – – –
K50 SMC30 Sensor Module Cabinet-Mounted – – – –  –  – – – – –  – – –
K51 VSM10 Voltage Sensing Module – – – –  –  – – – – –  – – –
K52 Second SMC30 Sensor Module Cabinet-Mounted – – – –  –  – – – – –  – – –
K70 Fan power supply  – – – – – – – – – – – – – – –
K73 SITOP power supply 24 V DC – – – – –  – – – – – – – – – –
K76 Auxiliary power generation  – – – – – – – –   – – – – –
(in the Line Connection Module)
K82 Terminal module for controlling the Safe Torque Off – – – –  –  – – – – –  – – –
and Safe Stop 1 safety functions
K87 TM54F Terminal Module – – – –  –  – – – – –  – – –
K88 Safe Brake Adapter 230 V AC – – – – – –  – – – – –  – – –
K90 2) CU320-2 DP Control Unit –     –  – –   –  – – –
K94 1) Performance expansion for CU320-2 Control Unit –     –  – –   –  – – –
K95 2) CU320-2 PN Control Unit –     –  – –   –  – – –

 Option can be ordered for this Cabinet Module


– Option cannot be ordered for this Cabinet Module

6/108 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Cabinet Modules

Options

■ Overview
SINAMICS S120 Cabinet Modules Air-cooled Liquid-cooled
Cabinet Modules Cabinet Modules

Active Line Module with Active Interface Module

Active Line Connection Module compact


Motor Module Booksize (Base Cabinet)
Motor Module Booksize (Cabinet Kit)

Active Line Connection Module


Auxiliary Power Supply Module

Auxiliary Power Supply Module


Basic Line Connection Module
Line Connection Module

Heat Exchanger Module


Central Braking Module

Motor Module compact


Motor Module Chassis
Smart Line Module
Basic Line Module

Motor Module
Order code Options
L00 4) Use in the “first environment” according to  – – – – – – – – – – – – – – –
EN 61800-3, Category C2 (TN/TT supply systems
with grounded neutral point)
L07 dv/dt filter plus Voltage Peak Limiter – – – – – –  – – – – – – – – –
L08 Motor reactor – – – –  –  – – – – – – – – –
L09 2 motor reactors connected in series – – – –  – – – – – – – – – – –
L10 dv/dt filter plus Voltage Peak Limiter – – – – – –  – – – – – – – – –
L13 Main contactor (for supply currents of  800 A)  5) – – – – – – – –  5) – – – – – –
L20 Use in an IT system – – – – – – – – – – – – – – – –
L21 Surge suppression  – – – – – – – –   – – – – –
L22 Scope of supply without line reactor  6) –  – – – – – –  – – – – – – 6
L25 Withdrawable circuit breaker in place of  7) – – – – – – – –  7)  7) – – – – –
a fixed-mounted circuit breaker
L34 Output-side circuit breaker (motor-driven) – – – – – –  – – – – – – – – –
L37 DC interface incl. pre-charging circuit of the – – – –  –  – – – – – – – – –
associated DC link capacitance
L40 Line filter monitoring – – –  – – – – – –   – – – –
L41 Current transformer upstream of main circuit breaker  – – – – – – – –   – – – – –
L42 Line Connection Module for Active Line Modules  – – – – – – – – – – – – – – –
L43 Line Connection Module for Basic Line Modules  – – – – – – – – – – – – – – –
L44 Line Connection Module for Smart Line Modules  – – – – – – – – – – – – – – –
L45 EMERGENCY OFF pushbutton installed in the  – – – – – – – –    – – – –
cabinet door
L46 Grounding switch upstream of main circuit breaker  8) – – – – – – – – – – – – – – –
L47 Grounding switch downstream of main circuit  8) – – – – – – – – – – – – – – –
breaker
L50 Cabinet lighting with service socket  – – – – – – – –   – – – – –
L55 Cabinet anti-condensation heating     –           
L61 25/125 kW braking module (can be used for frame –  –  – –  – – – – – – – – –
size FB) for line voltages of 380 ... 480 V and
660 ... 690 V
L62 50/250 kW braking unit (can be used for frame size –  9)   – –  – – – – – – – – –
GB/GD) for line voltages of 380 ... 480 V and
660 ... 690 V
L64 25/125 kW braking unit (can be used for frame size –  –  – –  – – – – – – – – –
FB) for line voltages of 500 ... 600 V
L65 50/250 kW braking unit (can be used for frame size –    – –  – – – – – – – – –
GB/GD) for line voltages of 500 ... 600 V
L87 Insulation monitoring  – – – – – – – –   – – – – –

 Option can be ordered for this Cabinet Module


– Option cannot be ordered for this Cabinet Module

Siemens D 21.3 · 2022 6/109


© Siemens 2022

SINAMICS S120 Cabinet Modules

Options

■ Overview
SINAMICS S120 Cabinet Modules Air-cooled Liquid-cooled
Cabinet Modules Cabinet Modules

Active Line Module with Active Interface Module

Active Line Connection Module compact


Motor Module Booksize (Base Cabinet)
Motor Module Booksize (Cabinet Kit)

Active Line Connection Module


Auxiliary Power Supply Module

Auxiliary Power Supply Module


Basic Line Connection Module
Line Connection Module

Heat Exchanger Module


Central Braking Module

Motor Module compact


Motor Module Chassis
Smart Line Module
Basic Line Module

Motor Module
Order code Options
M06 Base 100 mm high, RAL 7022     –           
M07 Cable-marshaling compartment 200 mm high,     –           
RAL 7035
M21 Degree of protection IP21     –     – – – – – – –
M23 Degree of protection IP23 (includes M60)     –           – 10)
M26 Side panel mounted to the right –    –           
M27 Side panel mounted to the left     –           
M43 Degree of protection IP43 (includes M60)     –           – 10)
M51 Motor connection wired to customer terminal – – – –  – – – – – – – – – – –
M54 Degree of protection IP54 (includes M60)     –           – 10)
6 M55 Degree of protection IP55 (includes M60) – – – – – – – – –       – 10)
M56 Reinforced mechanical design     –     – – – – – – –
M59 Closed cabinet door, air intake from below through     –     – – – – – – –
floor opening
M60 11) Additional touch protection (included in M23,M43,     – –  – – – – – – – – –
andM54)
M70 EMC shield bus  – – – –   –        –
M72 Quick-release couplings for water hoses – – – – – – – – –      – –
M77 Version without component support plates and – – – – –  – – – – – – – – – –
without additional control components
M89 Extended motor connection panel – – – – – – – – – – – – – – – –
M90 Crane transport assembly (top-mounted)     –           
M91 Marking of all control cable wire ends     –           
(including customer-specific cables)
N52 DC link fuses –  – – – – – – –    – – – –
P10 Measuring instrument for line supply values;  – – – – – – – –   – – – – –
mounted in cabinet door (includes L41)
P11 Measuring instrument for line supply values like  – – – – – – – –   – – – – –
option P10, with PROFIBUS connection
W01 Heat Exchanger Module, partially redundant with 2 – – – – – – – – – – – – – – – 
pumps
W10 Pipe insulation in the raw water circuit and of the – – – – – – – – – – – – – – – 
heat exchanger
W20 Raw-water connection from the bottom – – – – – – – – – – – – – – – 
W25 Raw water connection from the side – – – – – – – – – – – – – – – 
W34 Heat Exchanger Module for installation on the left – – – – – – – – – – – – – – – 
W36 Heat Exchanger Module for installation on the right – – – – – – – – – – – – – – – 
W43 Release valve in the deionized water circuit – – – – – – – – – – – – – – – 
W48 Leakage sensor in the converter cabinet, at the – – – – – – – – –      – –
bottom in the cabinet floor
W49 Leakage sensor in the Heat Exchanger Module – – – – – – – – – – – – – – – 
W62 Sensors in the raw water circuit on the plant/system – – – – – – – – – – – – – – – 
side
Y09 Special paint finish for cabinet     –           
Y11 Factory-assembled transport units     –           –

 Option can be ordered for this Cabinet Module


– Option cannot be ordered for this Cabinet Module

6/110 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Cabinet Modules

Options

■ Overview
SINAMICS S120 Cabinet Modules Air-cooled Liquid-cooled
Cabinet Modules Cabinet Modules

Active Line Module with Active Interface Module

Active Line Connection Module compact


Motor Module Booksize (Base Cabinet)
Motor Module Booksize (Cabinet Kit)

Active Line Connection Module


Auxiliary Power Supply Module

Auxiliary Power Supply Module


Basic Line Connection Module
Line Connection Module

Heat Exchanger Module


Central Braking Module

Motor Module compact


Motor Module Chassis
Smart Line Module
Basic Line Module

Motor Module
Order code Options
Production flowcharts
B43 Document – Production flowchart: one issue     –           
B44 Document – Production flowchart: updated every     –           
two weeks
B45 Document – Production flowchart: updated every     –           
month
Packaging options
B55 Generation of a preliminary and a final packing list     –           
(shipping)
              
B56
B57
Packed items labeled with a customized label
Photo documentation of the ordered units    

–           
6
Mechanical options for DC busbar system
M80 DC busbar system (Id = 1170 A, 1 × 60 × 10 mm)     –           –
M81 DC busbar system (Id = 1500 A, 1 × 80 × 10 mm)     –           –
M82 DC busbar system (Id = 1840 A, 1 × 100 × 10 mm)     –           –
M83 DC busbar system (Id = 2150 A, 2 × 60 × 10 mm)     –           –
M84 DC busbar system (Id = 2730 A, 2 × 80 × 10 mm)     –           –
M85 DC busbar system (Id = 3320 A, 2 × 100 × 10 mm)     –           –
M86 DC busbar system (Id = 3720 A, 3 × 80 × 10 mm)     –           –
M87 DC busbar system (Id = 4480 A, 3 × 100 × 10 mm)     –           –
M88 DC busbar system for line-side Cabinet Modules – – – – – – – – –    – – – –

 Option can be ordered for this Cabinet Module


– Option cannot be ordered for this Cabinet Module

Siemens D 21.3 · 2022 6/111


© Siemens 2022

SINAMICS S120 Cabinet Modules

Options

■ Overview
SINAMICS S120 Cabinet Modules Air-cooled Liquid-cooled
Cabinet Modules Cabinet Modules

Active Line Module with Active Interface Module

Active Line Connection Module compact


Motor Module Booksize (Base Cabinet)
Motor Module Booksize (Cabinet Kit)

Active Line Connection Module


Auxiliary Power Supply Module

Auxiliary Power Supply Module


Basic Line Connection Module
Line Connection Module

Heat Exchanger Module


Central Braking Module

Motor Module compact


Motor Module Chassis
Smart Line Module
Basic Line Module

Motor Module
Order code Options
Documentation
D00 Documentation in German     –           
D01 Customer documentation (circuit diagram, layout     –           
diagram, dimension drawing, spare parts list)
in EPLAN format.
D02 Customer documentation (circuit diagram, terminal     –           
diagram, layout diagram) in DXF format
D14 Preliminary version of customer documentation     –           
in PDF format
D56 Documentation in Russian     –           
6 D58 Documentation in English/French     –           
D60 Documentation in English/Spanish     –           
D72 Documentation in Italian     –           
D76 Documentation in English     –           
D77 Documentation in French     –           
D78 Documentation in Spanish     –           
D80 Documentation in English/Italian     –           
D84 Documentation in Chinese     –           
D91 Documentation in English/Chinese     –           
D93 Documentation in English/Portuguese (Brazil)     –     – – – – – – –
D94 Documentation in English/Russian     –           
D99 Without operating instructions     –           
Labeling plates
T58 Rating plate data in English/French     –           
T60 Rating plate data in English/Spanish     –           
T80 Rating plate data in English/Italian     –           
T83 Rating plate data in English/Portuguese (Brazil)     –     – – – – – – –
T85 Rating plate data in English/Russian     –           
T91 Rating plate data in English/Chinese     –           
Y31 One-line label for system identification, 40 × 80 mm     –           
Y32 Two-line label for system identification, 40 × 180 mm     –           
Y33 Four-line label for system identification, 40 × 180 mm     –           

 Option can be ordered for this Cabinet Module


– Option cannot be ordered for this Cabinet Module

6/112 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Cabinet Modules

Options

■ Overview
SINAMICS S120 Cabinet Modules Air-cooled Liquid-cooled
Cabinet Modules Cabinet Modules

Active Line Module with Active Interface Module

Active Line Connection Module compact


Motor Module Booksize (Base Cabinet)
Motor Module Booksize (Cabinet Kit)

Active Line Connection Module


Auxiliary Power Supply Module

Auxiliary Power Supply Module


Basic Line Connection Module
Line Connection Module

Heat Exchanger Module


Central Braking Module

Motor Module compact


Motor Module Chassis
Smart Line Module
Basic Line Module

Motor Module
Order code Options
Converter acceptance inspection
F03 Visual acceptance     –           
F71 Function test without motor (witnessed by customer)     –           
F72 Function test without motor (not witnessed by     –           
customer)
F74 Function test with test bay motor in no-load operation     –   – –      – –
(not witnessed by customer) 12)
F75 Function test with test bay motor in no-load operation     –   – –      – –
(witnessed by customer) 12)
              
F76
F77
Insulation test (not witnessed by customer)
Insulation test (witnessed by customer)    

–           
6
F97 Customer-specific acceptance inspections     –           
(on request)
Options specific to the shipbuilding industry
B50 Creation of material declaration Green Passport 13) 13) 13) 13) 13) 13) 13) 13) 13)       
13) 13) 13) 13) 13) 13) 13) 13) 13)
E51 Individual certificate from DNV       
E61 Individual certificate from American Bureau of 13) 13) 13) 13) 13) 13) 13) 13) 13)       
Shipping (ABS)
13) 13) 13) 13) 13) 13) 13) 13) 13)
E71 Individual certificate from China Classification       
Society (CCS)
M16 Dust protection packaging 13) 13) 13) 13) 13) 13) 13) 13) 13)       –
13) 13) 13) 13) 13) 13) 13) 13) 13)
M45 Cable entry via MCT frame       –
M66 Marine version 13) 13) 13) 13) 13) 13) 13) 13) 13)       

 Option can be ordered for this Cabinet Module


– Option cannot be ordered for this Cabinet Module

1) Only in conjunction with option K90 or K95. 8) For rated currents  2000 A.
2) Not for Line Modules mounted on the left of the Line Connection Modules 9) When Basic Line Modules are connected in parallel with a Line Connection
3) Option G56 cannot be selected for Active Line Modules in frame sizes FX Module, there is only space to fit a braking module in the right-hand Basic
and GX. Line Module.
10) Heat Exchanger Modules have degree of protection IP55 as standard.
4) For Basic Line Modules for cable lengths < 100 m (328 ft). Not for a parallel
connection of Line Modules to a common Line Connection Module. 11) Can only be ordered for air-cooled Cabinet Modules. Liquid-cooled Cabinet
5) For rated currents  800 A. Modules incorporate additional touch protection as a standard feature.
12) For a function test with test-bay motor, the motor is connected to Motor
6) Only with option L43 (for Basic Line Modules) and for rated currents
2000 A. Modules in chassis format and/or Motor Modules in booksize format in the
Base Cabinet.
7)
For rated currents  800 A. 13)
On request

Siemens D 21.3 · 2022 6/113


© Siemens 2022

SINAMICS S120 Cabinet Modules

Options

■ Overview
Option selection matrix
Certain options are mutually exclusive.
Options that are not affected are not shown.
 Possible combination
– Combination not possible

Electrical options

G20 G33 G62 K90 K95


G20 – –  
G33 – –  
G62 – –  
K90    –
K95    –

L61/64 L62/65
L61/64 –
L62/65 –

L07 L08 L09 1) L10 L34 L37


L07 – – – – 
L08 – – –  
6 L09 1) – – – – 
L10 – – – – 
L34 –  – – 
L37     

1)
Option for Booksize Cabinet Kit only.

G51 1) G52 1) G53 1) G54 1) G60 1) G61 1) K46 1) K48 1) K50 1) K51 1) K52 1) K87 1) K88 2)
1)
G51            
G52 1)            
G53 1)     –     –  –
G54 1)    – – – – – – – – –
G60 1)    –        
G61 1)   – –        
K46 1)    –      –  
K48 1)    –        
K50 1)    –        
K51 1)    –        
K52 1)   – –        
K87 1)    –        
2)
K88   – –        
1) In total, a maximum of 4 options per Cabinet Module if option K88
is not used.
2) If option K88 is selected, a maximum of 2 additional options are possible
per Cabinet Module.

6/114 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Cabinet Modules

Options

■ Overview
Electrical options (Line Connection Module)

K76 L13 1) L25 2) L41 L46 3) L47 3) P10 P11


K76    –   
L13 1)  –  – –  
L25 2)  –     
L41      – –
L46 3) – –     
L47 3)  –     
P10    –   –
P11    –   –
1)
Option for rated currents of 800 A only.
2)
Option for rated currents of >800 A only.
3)
Option for rated currents of 2000 A only.
Mechanical/electrical options

L00 L22 L42 L43 L44 M06 M07 M21 M23 M26 M27 M43 M54 M55 M60 M66 M70 M90 Y11 Y31 Y32 Y33
1)
L00                    
L22  –  –                 
3)
L42  – – –         –       
L43   – –         –  3)      
3)
L44  – – –         –       
M06      –         –      
M07      –         –       6
M21        –   – – –  –      
M23        –   – – – – 2) –      
M26          –           
M27          –           
M43        – –   – – – 2)       
2)
M54        – –   – – –       
M55   – – –   – –   – – –       
M60         – 2)   – 2) – 2) –       
M66   3) 3) 3) – – – –            
1)
M70                    
M90                  –   
Y11                  –   
Y31                    – –
Y32                    – –
Y33                    – –

1)
Option L00 includes option M70.
2)
Option M60 is already included in M23, M43 and M54 for all Line Modules and Motor Modules in chassis format.
3)
On request
DC busbar system mechanical options (busbars between individual Cabinet Modules)
M80 M81 M82 M83 M84 M85 M86 M87
M80 – –  – – – –
M81 – – –  –  –
M82 – – – –  – 
M83  – – – – – –
M84 –  – – –  –
M85 – –  – – – 
M86 –  – –  – –
M87 – –  – –  –

Siemens D 21.3 · 2022 6/115


© Siemens 2022

SINAMICS S120 Cabinet Modules

Options

■ Overview
Documentation

D00 D01 D02 D14 D56 D58 D60 D72 D76 D77 D78 D80 D84 D91 D93 D94 D99
D00                –
D01   –             –
D02                –
D14  –              –
D56               – –
D58      –  – –  –  – – – –
D60      –  –  – –  – – – –
D72           –     –
D76      – –    –  – – – –
D77      –          –
D78       –         –
D80      – – – –    – – – –
D84             –   –
D91      – –  –   – – – – –
D93      – –  –   –  – – –
D94     – – –  –   –  – – –
D99 – – – – – – – – – – – – – – – –

6/116 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Cabinet Modules

Description of the options

■ Options
B43, B44, B45 C95, C97
Production flowcharts Power supply voltage for the Heat Exchanger Module
with 60 Hz
Production flowcharts are provided with options B43 to B45.
After the order has been clarified, these are emailed as a dual With the option C95, Heat Exchanger Modules are provided for
language (English/German) PDF file. power supply voltages of 440 V to 480 V 3 AC at 60 Hz.
Option Description With the option C97 for line voltages of 500 to 690 V 3 AC/60 Hz,
the voltage is adapted to the 440 V to 480 V 3 AC/60 Hz supply
B43 Documentation – Production flowchart: one issue
voltage of the pump using a transformer.
B44 Documentation – Production flowchart: updated every two
weeks D01
B45 Documentation – Production flowchart: updated every month
Customer documentation (circuit diagram, layout diagram,
dimension drawing, spare parts list) in EPLAN format
B50 When ordering the option D01, the final version of the cabinet
Creation of material declaration Green Passport circuit diagram, layout diagram, dimension drawing and spare
This option creates a form for the material declaration according parts list in EPLAN format will be digitally delivered.
to Green Passport. D02
The subject matter of the declaration described is in line with the Customer documentation (circuit diagram, terminal
guidelines for the establishment of the inventory of hazardous diagram, layout diagram) in DXF format
materials - Resolution MEPC.269(68).
Option D02 can be used to order documents such as circuit
B55 diagrams, terminal diagrams, layout diagrams, and dimension
Generation of a preliminary and a final packing list drawings in DXF format, e.g. for further processing in
(shipping) CAD systems.
This option provides the electronically editable packing list D14
(possibly predefined from the factory) with the following Preliminary version of customer documentation
information in Excel format: in PDF format
• Number of individual packages
If documents such as circuit diagrams, terminal diagrams,
• Type of package (pallet, crate, etc.) layout diagrams and dimension drawings are required in
• Weight (unpacked and packed) advance for the purpose of system engineering (integration of
drive into higher-level systems, interface definition, installation,
6
• Dimensions (unpacked and packed)
building planning, etc.), it is possible to order a draft copy of the
• Delivery location documentation when ordering the Cabinet Modules. These
• Label for package item (when option B56 is ordered) documents are then supplied electronically a few working days
• Description of what is in the package following receipt of the order. If the order includes options that
fall outside the scope of standard supply, these will not be
A first packing list is generated after complete technical covered by the documentation due to the obvious time
clarification with preliminary data. When shipped, a final packing constraints.
list is provided with the actual data.
The client is sent the documentation relating to the order by
B56 email. The recipient's email address must be specified with the
Packed items labeled with a customized label order for this purpose. In the email, the recipient will also receive
a link for downloading order-specific documentation.
With this option, customized labels are attached to the With the option D02, the documents are also delivered in DXF
unpacked and packed packaged units. Internal customers must format.
provide two labels at least 2 weeks before the shipping date
(printout to the factory logistics department, specifying D58, D60, D80, D91, D93, D94
the article number). Documentation as language package
B57 If a documentation option is not selected, the relevant
Photographic documentation of the ordered units documentation is supplied as standard in English/German.
When one of the options specified in the table is selected, the
This option provides digital photographic documentation with standard documentation language will be changed from English
the following content: / German to the language combination provided by the option.
• 1 photo diagonally from the front
Order Language
• 1 photo diagonally from the rear (opposite) code
• 1 photo with the packed item on which the label is legible D58 English/French
The listed photos of the packed items are taken in both an D60 English/Spanish
unpacked and a packed state in each position (a total of 6
D80 English/Italian
photos per packed item).
D91 English/Chinese
D93 English/Portuguese (Brazil)
D94 English/Russian

Siemens D 21.3 · 2022 6/117


© Siemens 2022

SINAMICS S120 Cabinet Modules

Description of the options

■ Options
D00, D56, D72, D76, D77, D78, D84 F03, F71, F72, F74, F75, F76, F77, F97
Documentation in a single language Converter acceptance inspections
The documentation is also available in a single language, for Order code Description
example, to be able to order other language combinations.
F03 Visual acceptance
If a further language is required for standard documentation in The inspection includes the following:
English/German, the option D74 (documentation in English/ • Check of degree of protection
German) must also be ordered in addition to that language.
• Check of equipment (components)
Order code Language • Check of equipment identifiers
D00 German • Check of clearance and creepage distances
• Check of cables
D56 Russian
• Check of customer documentation
D72 Italian
• Submission of the acceptance report
D76 English All the above checks are performed with the equipment in
D77 French a no-voltage condition.
D78 Spanish F71 Function test without motor
(witnessed After the visual acceptance with the converter switched off,
D84 Chinese by the converter is connected to rated voltage. No current at the
customer) converter output end.
D99 F72 (not
Without operating instructions witnessed The inspection includes the following:
by customer) • Visual acceptance as described for option F03
The Cabinet Modules or Booksize Cabinet Kit are shipped • Check of power supply
without a documentation CD. • Check of protective and monitoring devices (simulation)
• Check of fans
E51 to E71 • Pre-charging test
• Function test without connected motor
Individual certification • Submission of the acceptance report
For the Cabinet Modules, type certificates are available for the F74 (not Function test with test bay motor under no-load conditions
marine classification institutes DNV, ABS and CCS. witnessed After the visual acceptance with the converter switched off,
An additional individual certification of the Cabinet Modules by by the converter is connected to rated voltage. A small current
6 the respective certification institute contains the extensions
described under option M66.
customer)
F75
flows at the converter output end in order to operate the test
bay motor under no-load conditions.
(witnessed
With the respective option, the converter and the documentation by The inspection includes the following:
are certified by an acceptor (certified recipient) for the customer) • Visual acceptance as described for option F03
• Check of power supply
respective institute and an individual certificate is created. • Check of protective and monitoring devices (simulation)
• E51 Individual certificate from DNV • Check of fans
• Function test with test bay motor under no-load conditions
• E61 Individual certificate from American Bureau of Shipping • Submission of the acceptance report
(ABS)
F76 (not Insulation test of the equipment
• E71 Individual certificate from China Classification Society witnessed The inspection includes the following:
(CCS) by customer) • High-voltage test
F77 • Measurement of the insulation resistance
Note: (witnessed • Submission of the acceptance report
Several individual certificates can be combined. by customer)
F97 Customer-specific acceptance inspections (on request)
If acceptance inspections that are not covered by the options
F03, F71/F72, F74/F75 or F76/F77 are required, then
customer-specific acceptance inspections/supplementary
tests can be ordered using order code F97 on request and
following technical clarification.

Note:
The options for converter acceptance must be ordered sepa-
rately for each Cabinet Module and each order position.

6/118 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Cabinet Modules

Description of the options

■ Options
G33 G60
CBE20 Communication Board TM31 Terminal Module
The CBE20 Communication Board can be used to connect The TM31 Terminal Module is used to expand the customer
the SINAMICS S120 Cabinet Modules to a PROFINET-IO, terminal.
EtherNet/IP or Modbus TCP network via a CU320-2 Control Unit.
The CBE20 Communication Board plugs into the option slot on The following additional interfaces are available:
the CU320-2 Control Unit. • 8 digital inputs
The CBE20 Communication Board can only be ordered as • 4 bidirectional digital inputs/outputs
option G33 in conjunction with a CU320-2 Control Unit (option • 2 relay outputs with changeover contact
K90 or K95) and is supplied in an accessories pack for possible • 2 analog inputs
configuration.
A combination with option G62 (TB30) is not possible. • 2 analog outputs
• 1 temperature sensor input (KTY84-130/PTC)
Note:
Only one communication interface can be used in isochronous • 2 DRIVE-CLiQ sockets
operation when operating the Communication Board CBE20 in • 1 connection for the electronics power supply via the 24 V DC
a Control Unit CU320-2. supply connector
• CU320-2 DP: Either the DP interface of the Control Unit or the • 1 PE/protective conductor connection
PN interfaces of the CBE20
To simplify configuration and commissioning of the drive,
• CU320-2 PN: Either the internal PN interfaces or the external the optional TM31 Terminal Module is already preset with various
PN interfaces of the CBE20 factory settings, which can then be selected when
Description of the CBE20 Communication Board  Chassis commissioning the system.
format units  System components  Supplementary system Description of the TM31 Terminal Module  SINAMICS S120
components. chassis format units  System components  Supplementary
G51 to G54 system components.
TM150 temperature sensor evaluation unit For additional information, please refer to the SINAMICS Low
Options G51 to G54 can be used to order between one and four Voltage Engineering Manual.
TM150 Terminal Modules for sensing and evaluating several
temperature sensors.
G61
Additional TM31 Terminal Module 6
Order code Option With option G61, the number of digital inputs/outputs, as well as
G51 1 x TM150 temperature sensor evaluation unit the number of analog inputs/outputs in the drive system can be
expanded using a second TM31 Terminal Module (in addition to
G52 2 x TM150 temperature sensor evaluation units
the TM31 Terminal Module that can be selected using
G53 3 x TM150 temperature sensor evaluation units option G60).
G54 4 x TM150 temperature sensor evaluation units Note:
The TM150 Terminal Module is a DRIVE-CLiQ component for Option G61 requires option G60.
temperature evaluation. The temperature is measured in G62
a temperature range from -99 °C to +250 °C for the following TB30 Terminal Board
temperature sensors:
The TB30 Terminal Board provides a way of adding digital
• Pt100 (with monitoring for wire breaks and short-circuits)
inputs/digital outputs and analog inputs/analog outputs to the
• Pt1000 (with monitoring for wire breaks and short-circuits) Control Unit. The TB30 Terminal Board plugs into the option slot
• KTY84 (with monitoring for wire breaks and short-circuits) on the Control Unit.
• PTC (with monitoring for short-circuit ) The following are located on the TB30 Terminal Board:
• Bimetallic NC contact (without monitoring) • Power supply for digital inputs/digital outputs
For the temperature sensor inputs, for each terminal block the • 4 digital inputs
evaluation can be parameterized for 1×2-wire, 2×2-wire, 3-wire • 4 digital outputs
or 4-wire. There is no galvanic isolation in the TM150. • 2 analog inputs
A maximum of 12 temperature sensors can be connected to the • 2 analog outputs
TM150 Terminal Module.
The TB30 Terminal Board can only be ordered in conjunction
Description of the TM150 Terminal Module  SINAMICS S120 with a CU320-2 Control Unit (option K90 or K95). A combination
chassis format units  System components  Supplementary with options G20 and G33 is not possible.
system components.
Description of the TB30 Terminal Board  SINAMICS S120
G56 chassis format units  System components  Supplementary
Contactor monitoring system components.
The option is used for monitoring the pre-charging and bypass
contactors of the Line Modules, mainly for infeeds connected in
parallel.
Note:
Option G56 cannot be selected for Active Line Modules in frame
sizes FX and GX.

Siemens D 21.3 · 2022 6/119


© Siemens 2022

SINAMICS S120 Cabinet Modules

Description of the options

■ Options
K01 to K05 K50
Safety license Extended Functions for 1 to 5 axes SMC30 Sensor Module Cabinet-Mounted
The Safety Integrated Basic Functions do not require a license. The SMC30 Sensor Module Cabinet-Mounted can be used to
However, the Safety Integrated Extended Functions require evaluate the encoders of motors without a DRIVE-CLiQ
a license for each axis equipped with safety functions. It is interface. External encoders can also be connected via the
irrelevant which safety functions are used and how many. SMC30.
Option K01 includes the license for 1 axis, K02 for 2 axes, etc. The following encoder signals can be evaluated:
up to option K05 for 5 axes. • Incremental encoders TTL/HTL with and without open-circuit
The required licenses can be optionally ordered with the detection (open-circuit detection is only available with bipolar
CompactFlash card. signals)
Subsequent licensing is possible online via the WEB License • SSI encoders with TTL/HTL incremental signals
Manager by generating a license key: • SSI encoders without incremental signals
www.siemens.com/automation/license The motor temperature can also be measured using KTY84-130,
Pt1000 or PTC thermistors.
K08
AOP30 Advanced Operator Panel installed in the cabinet Description of the SMC30 Sensor Module  Chassis format
door units  System components  Supplementary system
components.
The AOP30 Advanced Operator Panel is an optional input/output
device for the Cabinet Modules. If, for the Cabinet Module or the K51
Booksize Cabinet Kit, an autonomous closed-control (option VSM10 Voltage Sensing Module
K90 or K95) is selected, this module can be assigned to its own The VSM10 Voltage Sensing Module is used to measure the
operator panel with option K08. voltage characteristic on the motor side, so that the following
The AOP30 Advanced Operator Panel is installed in the cabinet function can be implemented:
door of each Cabinet Module. • Operation of a permanent-magnet synchronous motor without
Description of the AOP30  Chassis format units  System encoder with the requirement to be able to connect to a motor
components  Supplementary system components. that is already running (flying restart function)
• Quick flying restart of large induction motors: The voltage
6 K46
SMC10 Sensor Module Cabinet-Mounted
sensing function eliminates the delay incurred by
demagnetization of the motor.
The SMC10 Sensor Module Cabinet-Mounted can be used to Description of the VSM10 Voltage Sensing Module  Chassis
simultaneously sense the speed and the rotor position angle. format units  System components  Supplementary system
The signals received from the resolver are converted here and components.
made available to the closed-loop controller via the DRIVE-CLiQ
interface for evaluation purposes. K52
Second SMC30 Sensor Module Cabinet-Mounted
The following encoder signals can be evaluated:
• 2-pole resolver With option K50, the cabinet unit contains an SMC30 Sensor
Module Cabinet-Mounted. An additional SMC30 (option K52)
• Multi-pole resolver enables reliable actual-value acquisition when Safety Integrated
The motor temperature can also be measured using KTY84-130, extended functions are used (requires a license: options K01
Pt1000 or PTC thermistors. to K05).
Description of the SMC10 Sensor Module Cabinet-Mounted  Detailed and comprehensive instructions and information for
Chassis format units  System components  Supplementary the Safety Integrated functions can be found in the associated
system components. Function Manual.

K48
SMC20 Sensor Module Cabinet-Mounted
The SMC20 Sensor Module Cabinet-Mounted can be used
to simultaneously sense the speed and position. The signals
received from the incremental encoder are converted here and
made available to the closed-loop controller via the DRIVE-CLiQ
interface for evaluation purposes.
The following encoder signals can be evaluated:
• Incremental encoder sin/cos 1 Vpp
• Absolute encoder EnDat 2.1
• SSI encoder with incremental signals sin/cos 1 Vpp
The motor temperature can also be measured using KTY84-130,
Pt1000 or PTC thermistors.
Description of the SMC20 Sensor Module  Chassis format
units  System components  Supplementary system
components.

6/120 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Cabinet Modules

Description of the options

■ Options
K70 K82
Fan power supply Terminal Module for controlling the Safe Torque Off and Safe
Stop 1 safety functions
With option K70, the line voltage supply for the 400 V 3 AC
auxiliary power supply system is tapped downstream of the The terminal module controls the Safety Integrated Basic
circuit breaker and protected by a motor starter protector. Functions Safe Torque Off (STO) and Safe Stop 1 (SS1) (time-
controlled) for a voltage of 24 V DC/AC (terminology as defined
The voltages 230 V 1 AC and 24 V DC of the auxiliary power in IEC 61800-5-2). The relays used here are permitted up to an
supply system are supplied externally on the plant side. installation altitude of 2000 m. The use of this option for
K73 requirements that go beyond this is possible upon request.
SITOP power supply 24 V DC The integrated safety functions, starting from the Safety
The 24 V DC supply for standard Booksize Cabinet Kits is Integrated (SI) input terminals of the components (Control Unit
tapped from the auxiliary power supply. and Motor Module), satisfy the requirements of EN 61800-5-2,
EN 60204-1, EN ISO 13849-1 Category 3 for Performance Level
With option K73, the 24 V DC supply is provided by a dedicated (PL) d and IEC 61508 SIL 2.
SITOP power supply unit.
With option K82, the requirements specified in EN 61800-5-2,
K76 EN 60204-1, EN ISO 13849-1 Category 3 for Performance Level
Auxiliary voltage generation in the Line Connection Module (PL) d and IEC 61508 SIL 2 are fulfilled.
Cabinet Modules require an auxiliary energy supply to The Safety Integrated functions using option K82 are only
function properly. This current demand must be included in the available in conjunction with certified components and software
configuration and supplied from an external source. If an versions.
external supply is not possible, the required auxiliary voltages
can be supplied by means of an Auxiliary Power Supply Module. The Safety Integrated functions of SINAMICS are generally
certified by independent institutes. An up-to-date list of certified
Alternatively, option K76 can be selected. This provides for components is available on request from your local
generation of auxiliary voltages in the Line Connection Module. Siemens office.
This is particularly advisable for smaller device configurations.
K87
With option K76, the following auxiliary voltages are provided: TM54F Terminal Module
Air-cooled Liquid-cooled The TM54F Terminal Module is a terminal expansion module with
Cabinet Modules Cabinet Modules safe digital inputs and outputs to control the Safety Integrated
functions.
6
380 ... 480 V or Possible tap for the following –
500 ... 690 V 2 AC Line Connection Modules:
The TM54F is directly connected to a Control Unit via
• Line Connection Module DRIVE-CLiQ. Each Control Unit can be assigned precisely to
with rated current up to
800 A: 35 A one TM54F.
• Line Connection Module Note:
with rated current of It is not permissible to connect Motor Modules or Line Modules
1000 to 1600 A: 50 A
to a TM54F.
• Line Connection Module
6SL3700-0LE42-0AA3: 50 A The TM54F provides 4 fail-safe digital outputs and 10 fail-safe
• Line Connection Module digital inputs. A fail-safe digital output consists of one 24 V DC
with rated current of switching output, one output switching to ground and one digital
2000 to 3200 A: 80 A input to check the switching state. A fail-safe digital input con-
230 V 1 AC Possible tap for the Line Possible tap for Basic sists of two digital inputs.
Connection Modules: Line Connection
• <800 A: approx. 4 A Modules / Active Line Description of the TM54F Terminal Module  SINAMICS S120
• > 800 A: approx. 6 A Connection Modules chassis format units  System components  Supplementary
• 4 ... 10 A system components.
24 V DC Possible tap for the Line Con- Possible tap for Basic
nection Modules: Line Connection
• <800 A: approx. 20 A Modules / Active Line
• > 800 A: approx. 40 A Connection Modules
• 5 ... 20 A

The supply for the auxiliary power supply system is connected


at the auxiliary voltage module of the Line Connection Module.

Siemens D 21.3 · 2022 6/121


© Siemens 2022

SINAMICS S120 Cabinet Modules

Description of the options

■ Options
K88 K95
SBA Safe Brake Adapter, 230 V AC CU320-2 PN Control Unit (PROFINET)
The Safe Brake Control (SBC) is a safety function that is used Option K95 assigns a CU320-2 PN Control Unit, incl.
in safety-relevant applications, for example in presses or rolling CompactFlash card, to the Line Modules and Motor Modules.
mills. In the no-current state, the brake acts on the drive motor This unit handles the communication and open-loop/closed-loop
using spring force. The brake is released when current flows in control functions. DRIVE-CLiQ is used to establish a connection
it (low active). to the various modules and where required, to additional I/O
modules. A PROFINET interface is available for the higher-level
The Safe Brake Adapter is already installed in the cabinet unit in communication.
the factory. An infeed is connected to terminal -X12 on the Safe
Brake Adapter for the power supply. For control, a connection is The computational performance required from the CU320-2 PN
established between the Safe Brake Adapter and the Control Control Unit increases with the number of connected Motor
Interface Module in the factory using a cable harness. Modules and system components – as well as the dynamic
performance demanded.
On the plant side, to control the brake, a connection must be
established between terminal -X14 on the Safe Brake Adapter Without performance expansion, it is generally possible to
and the brake. operate two Motor Modules with one Line Module.
Description of the SBA Safe Brake Adapter  SINAMICS S120 The full computational performance of the CU320-2 PN is only
chassis format units  System components  Supplementary available on systems with performance expansion (option K94).
system components.
Description of the CU320-2 DP Control Unit  SINAMICS S120
K90 chassis format units  System components  Control Units.
CU320-2 DP Control Unit (PROFIBUS)
L00
Option K90 assigns a CU320-2 DP Control Unit incl. Use in the first environment according to EN 61800-3, Cate-
CompactFlash card to the Line Modules and Motor Modules. gory C2 (TN/TT supply systems with grounded neutral point)
This unit handles the communication and open-loop/closed-loop
control functions. DRIVE-CLiQ is used to establish a connection With option L00, the Line Modules have a line filter as well as
to the various modules and where required, to additional I/O additional measures installed in the factory; this means that the
modules. A PROFIBUS interface is available as standard for the Cabinet Modules can also comply with the limit values for use in
higher-level communication. the first environment (Category C2) according to EN 61800-3.

6 The computational performance required from the Control Unit


CU320-2 DP increases with the number of connected Motor
Notes on the measures to be implemented by the customer are
provided in the SINAMICS Low Voltage Engineering Manual.
Modules and system components – as well as the dynamic In order to achieve the full filter effect, the optional line filter must
performance demanded. always be used in conjunction with a line reactor.
Without performance expansion, it is generally possible to To allow the shield of the power cables to be connected in
operate two Motor Modules with one Line Module. conformance with EMC requirements, an additional EMC shield
The full computational performance of the CU320-2 DP is only bus (option M70) is installed at the converter input and output.
available on systems with performance expansion (option K94). A separate order is not required in this case.

Description of the CU320-2 DP Control Unit  SINAMICS S120 Note:


chassis format units  System components  Control Units. Option L00 is not available for Line Modules in a parallel
connection.
K94
Performance expansion for CU320-2 Control Unit
With option K94, the CU320-2 Control Unit (option K90 or K95)
is supplied with a CompactFlash card with performance
expansion. This therefore provides the full computational
performance of the CU320-2 Control Unit.
In addition to the firmware, the CompactFlash card also contains
licensing codes that are required to enable firmware options, for
example, the performance expansion and the Safety Integrated
Extended Functions.

6/122 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Cabinet Modules

Description of the options

■ Options
L07 dv/dt filters compact plus VPL are designed for the following
dv/dt filter compact plus Voltage Peak Limiter maximum motor cable lengths:
dv/dt filters compact plus VPL (Voltage Peak Limiter) limit the • Shielded cables 100 m (e.g. Protodur NYCWY)
voltage rate of rise dv/dt to values of < 1600 V/s and the typical • Unshielded cables 150 m (e.g. Protodur NYY)
peak voltage to the following values in accordance with the limit
value curve A according to IEC 60034-25: 2007: For longer cable lengths (> 100 m shielded, >150 m
unshielded), the dv/dt filter plus VPL (option L10) should be
• < 1150 V at Uline < 575 V used.
• <1400 V at 660 V < Uline < 690 V
Notice:
The dv/dt filter compact plus VPL functionally consists of two • Operation with output frequencies <10 Hz is permissible for
components that are supplied as a compact mechanical unit, max. 5 min.
the dv/dt reactor and the voltage limiting network (VPL), which
limits voltage peaks and feeds back the energy to the DC link. • The maximum permissible output frequency is 150 Hz.

It is so compact that it can be completely integrated into the When using dv/dt filters, restrictions regarding permissible pulse
cabinet, even for high power ratings. An additional cabinet is frequencies must be observed.
not required. Please also note the relevant information provided in the
By using a dv/dt filter compact plus VPL, standard motors with SINAMICS Low Voltage Engineering Manual.
standard insulation and without insulated bearings can be used Note:
with supply voltages up to 690 V in converter operation. Option L07 cannot be combined with the following options:
The power losses stated in system component section System • L08 (motor reactor)
components  Motor-side components  dv/dt filters compact • L10 (dv/dt filter plus VPL)
plus VPL can be used to determine the total losses for
engineering purposes.

L08
Motor reactor
Motor reactors reduce the voltage load on the motor windings by The power losses stated in the section System components >
reducing the voltage gradients at the motor terminals that occur
during converter operation. At the same time, the capacitive
Motor-side components > Motor reactors can be used to
determine the total losses for engineering purposes.
6
charge/discharge currents that place an additional load at
the Motor Module output when using long motor cables, Note:
are reduced. The terminal lugs of the reactors are not nickel-plated.

Suitably dimensioned motor reactors or a series connection Option L08 cannot be combined with the following options:
of several motor reactors make it possible to connect larger • L07 (dv/dt filter compact plus VPL)
capacitances and thus allow the use of longer motor cables. • L10 (dv/dt filter plus VPL)
In the case of multi-motor drives, the use of motor reactors is For Motor Modules in chassis format, the maximum cable
recommended as a general principle. lengths when using motor reactors are 300 m (shielded) or
The motor reactor is accommodated in the Cabinet Module. 450 m (unshielded).
An additional 600-mm-wide cabinet located to the right of the For Motor Modules in Booksize Cabinet Kit format, by using
Motor Module is only required for the chassis format in frame motor reactors (option L08) the maximum motor cable lengths,
sizes HX and JX. specified in the following table, can be reached:
Booksize Rated output Maximum motor cable length
Cabinet Kit current of Motor when using motor reactors for Booksize Cabinet Kits
Module
Shielded cable Unshielded cable
Without reactor With one reactor With two reactors Without reactor With one reactor With two reactors
(option L08) in series (option L08) in series
(option L09) (option L09)
6SL3720-... A m (ft) m (ft) m (ft) m (ft) m (ft) m (ft)
1TE21-0AB3 9 50 (164) 135 (443) – 75 (246) 200 (656) –
1TE21-8AB3 18 70 (230) 160 (525) 320 (1050) 100 (328) 240 (787) 480 (1575)
1TE23-0AB3 30 100 (328) 190 (623) 375 (1230) 150 (492) 280 (919) 560 (1837)
1TE24-5AB3 45 100 (328) 200 (656) 400 (1312) 150 (492) 300 (984) 600 (1969)
1TE26-0AB3 60 100 (328) 200 (656) 400 (1312) 150 (492) 300 (984) 600 (1969)
1TE28-5AB3 85 100 (328) 200 (656) 400 (1312) 150 (492) 300 (984) 600 (1969)
1TE31-3AB3 132 100 (328) 200 (656) 400 (1312) 150 (492) 300 (984) 600 (1969)

Siemens D 21.3 · 2022 6/123


© Siemens 2022

SINAMICS S120 Cabinet Modules

Description of the options

■ Options
L09 L13
Two motor reactors in series Main contactor (for supply currents  800 A)
With option L09 for Booksize Cabinet Kits, two motor reactors Line Connection Modules for current ratings up to 800 A feature
are used in series that can be located within the standard width only a manually operated fuse switch disconnector as standard.
of the Cabinet Kit. Option L13 is needed if a switching element is also required for
disconnecting the cabinet from the supply (needed for
The maximum permissible motor cable lengths when using EMERGENCY OFF). The contactor is controlled by the closed-
option L09 are specified in the table under option L08. loop control in this case. Option L13 can be ordered for Line
Note: Connection Modules together with Basic Line Modules
The terminal lugs of the reactors are not nickel-plated. (option L43). With Smart Line Modules and Active Line Modules,
the contactor is included as standard.
L10
dv/dt filter plus Voltage Peak Limiter L20
Use in an IT system
A dv/dt filter plus VPL (Voltage Peak Limiter) limits the voltage
rate of rise dv/dt to values < 500 V/s and the typical peak When used in IT systems, an isolating transformer is connected
voltage to the following values in accordance with the limit value in the fan power supply.
curve according to IEC/TS 60034-17: 2006:
L21
• < 1000 V at Uline < 575 V Surge suppression
• <1250 V at 660 V < Uline < 690 V In ungrounded IT systems, the line voltage is not permanently
The dv/dt filter plus VPL functionally consists of two components, connected to the ground potential because of the missing
the dv/dt reactor and the voltage limiting network (VPL), which ground connection of the supply network. Therefore, when
limits voltage peaks and feeds the energy back to the DC link. a ground fault occurs during operation, a voltage against
ground increased by a factor of 2 can occur. For this reason,
Option L10 is installed in an additional cabinet with a width of it is recommended that a surge suppression against ground
600 mm that is located on the right-hand side of the Motor be installed for operation on IT systems. The surge suppression
Module. option includes the installation of line-side surge arresters and
By using a dv/dt filter plus VPL, standard motors with standard upstream fuses for each system phase. The signaling contacts
insulation and without insulated bearings can be used with for monitoring the surge arresters are connected in series and
supply voltages up to 690 V in converter operation. connected to a customer interface.
6 dv/dt filters plus VPL are designed for the following maximum Note:
motor cable lengths: Option L21 does not include the components required to install
an insulation monitor for the IT system. An insulation monitor
• Shielded cable (e.g. Protodur NYCWY) should always be ordered separately as option L87 when the
- Motor Modules, frame sizes FX to HX: 300 m supplying IT system is not monitored at another position (e.g. at
- Motor Modules, frame size JX: 150 m the transformer outgoing feeder). Only one insulation monitor
• Unshielded cables (e.g. Protodur NYY) can ever be used within the same electrically connected
- Motor Modules, frame sizes FX to HX: 450 m network.
- Motor Modules, frame size JX: 225 m Option L21 also does not include removal in the factory of the
For cable lengths < 100 m shielded or < 150 m unshielded, the metal bracket that makes the connection to ground of the radio
dv/dt filter compact plus VPL (option L07) can be used interference suppression filter installed as standard. The metal
advantageously. bracket should therefore be removed during the installation or
commissioning of the converter if the device is to be operated on
The power losses stated in the section System components > an ungrounded IT system.
Motor-side components > dv/dt filters plus VPL can be used to
determine the total losses for engineering purposes.
Notice:
The maximum permissible output frequency is 150 Hz.
When using dv/dt filters, restrictions regarding permissible pulse
frequencies must be observed.
Please also note the relevant information provided in the
SINAMICS Low Voltage Engineering Manual.
Note:
Parts of option L10 do not have nickel-plated copper busbars.
Option L10 cannot be combined with the following options:
• L07 (dv/dt filter compact plus VPL)
• L08 (motor reactor)

6/124 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Cabinet Modules

Description of the options

■ Options
L22 L37
Delivery scope without line reactor DC interface incl. pre-charging circuit of the relevant DC link
capacitance
The air-cooled Basic Line Modules and Smart Line Modules as
well as the liquid-cooled Basic Line Connection Modules are If, for reasons relating to the process or availability, the Motor
supplied with line reactors as standard; the reason for this is that Module needs to be disconnected from the common DC link
frequently in practice the line configuration at the connection for an entire drive line-up or connected to it during operation,
point of the drive line-up and/or the line supply short-circuit a manually operated isolating distance can be ordered as an
power is not known. option. With chassis format power units, this takes the form of
switch disconnectors, and with Booksize Cabinet Kits,
If the supply is connected through a separate transformer or if a contactor combination.
the line has a suitably low short-circuit power or if the standard
integrated line reactor does not need to be supplied for other Option L37 is installed on the busbar between the Motor Module
reasons, then this can be indicated by selecting option L22. and the main DC busbar. To ensure that the module can be
connected to a pre-charged DC link, the option also includes
In the case of air-cooled Cabinet Modules, option L22 can be a pre-charging circuit for the DC link capacitors of the relevant
selected for Line Connection Modules (rated current < 2000 A) Motor Module.
in conjunction with Basic Line Modules (option L43) and for
Smart Line Modules. In the case of liquid-cooled Cabinet The switching operation is performed externally. The operating
Modules, option L22 can be selected for Basic Line Connection levers can be locked using a padlock (padlock not included in
Modules. scope of supply). The degree of protection of the cabinets is not
influenced.
For Basic Line Modules and Basic Line Connection Modules
connected in parallel, a line reactor should always be used, The air guidance contains option L37 and also option M60
i.e. option L22 cannot be selected. (additional touch protection).
The power losses of each line reactor stated in section System Options L61/L62 and L64/L65 (braking units) cannot be ordered
components  Line-side components  Line reactors can be together with option L37 for space reasons.
deducted from the total power loss for engineering purposes.
L40
For additional information, please refer to the SINAMICS Low Line filter monitoring
Voltage Engineering Manual.
With option L40, the filter in the Active Interface Module is
L25 monitored for effectiveness against harmonic effects on the
Withdrawable circuit breaker system. The capacitance of the filter capacitors of the integrated
filter is continuously calculated and compared with the installed
6
Line Connection Modules (air-cooled), Active Line Connection nominal capacitance by measuring the current and voltage in
Modules and Basic Line Connection Modules (liquid-cooled) the Active Interface Module. If the calculated capacity deviates
with an input current of > 800 A are equipped with fixed- by more than the set tolerance, an alarm is triggered.
mounted circuit breakers as standard. Where the customer
requires a visible isolating distance, a withdrawable circuit L41
breaker can be ordered as an option. Current transformer upstream of main circuit breaker
L34 If additional current transformers are required for measuring or
Output-side circuit breaker monitoring purposes, these can be ordered for (air-cooled) Line
Connection Modules or (liquid-cooled) Active Line Connection
Option L34 can be used to disconnect the motor terminals from Modules and Basic Line Connection Modules with option L41.
the Motor Module Chassis. The current transformers are installed upstream of the main
A rotating permanent-magnet synchronous motor generates circuit breaker in all three infeed phases.
a voltage at its motor terminals proportional to the speed. The transformers have an accuracy class of 1.0. The secondary
The motor terminal voltage is also available at the inverter current is maximum 1 A.
output terminals as well as at the DC link and the components
connected to it. The transformer measuring connections are routed to the
terminal strip in the Line Connection Module.
Option L34 is available for disconnection in the case of a fault or
if maintenance work is to be carried out. Note:
These current transformers are already included in options P10
Option L34 is completely prewired and is accommodated in an and P11 (measuring instrument for the display of line values).
additional cabinet, which is arranged at the right-hand side of
the Motor Module (400 mm wide for frame sizes FX/GX, 600 mm L42
wide for frame sizes HX/JX). It is controlled using a TM31 Line Connection Module for Active Line Modules
Terminal Module, which is included with this option. This means
that the output switch is automatically controlled via the Motor Order code L42 is specified in the order to indicate that the Line
Module. Connection Module will be connected to an Active Line Module.
The Line Connection Module is then adapted accordingly (pre-
Option L34 cannot be combined with the following options: charging circuit, connection busbars, etc.).
• L07 (dv/dt filter compact plus VPL) See also the information for the Line Connection Modules and
the overview of options.
• L10 (dv/dt filter plus VPL)

Siemens D 21.3 · 2022 6/125


© Siemens 2022

SINAMICS S120 Cabinet Modules

Description of the options

■ Options
L43 L50
Line Connection Module for Basic Line Modules Cabinet lighting with service socket
Order code L43 is specified in the order to indicate that the Line With option L50, cabinet lighting is included with an additional
Connection Module will be connected to a Basic Line Module. service socket for a SCHUKO connector (connector type F)
The Line Connection Module is then adapted accordingly according to CEE 7/4. The power supply for the cabinet lighting
(line reactors, pre-charging circuit, connection busbars, etc.). and the service socket is external and must be fuse-protected
See also the information for the Line Connection Modules and for max. 10 A.
the overview of options.
The cabinet lighting consists of an LED hand lamp with On/Off
L44 switch and with magnetic fasteners with an approx. 3 m long
Line Connection Module for Smart Line Modules connecting cable. The lamp is factory-positioned in the cabinet
door at a defined marking, and the connecting cable is wound
Order code L44 is specified in the order to indicate that the Line on the associated mount.
Connection Module will be connected to a Smart Line Module.
The Line Connection Module is then adapted accordingly L55
(pre-charging circuit, connection busbars, etc.). Cabinet anti-condensation heating
See also the assignment table for the Line Connection Modules
and the overview of options. The anti-condensation heating is recommended at low
ambient temperatures and high levels of humidity to prevent
L45 condensation. Depending on the cabinet width, a 100 W cabinet
EMERGENCY OFF pushbutton, installed in the cabinet door heater is installed for each Cabinet Module.
The EMERGENCY OFF pushbutton with protective collar is 1 heating element for cabinet width up to 600 mm, 2 heating
installed in the cabinet door of the Line Connection Module elements for cabinet width over 800 mm.
and its contacts are connected to a terminal strip. The contacts The power supply for the anti-condensation heating (110 V to
are designed as 2 NC contacts wire break-proof. From here, 230 V AC, at terminal strip -X240) must be provided externally
the EMERGENCY OFF pushbutton can be integrated into the and fused with max. 16 A.
plant-side EMERGENCY OFF chain.
L46
Grounding switch upstream of main circuit breaker
The grounding switch is upstream of the circuit breaker in the
6 Line Connection Module and short-circuits the incoming supply
system to ground. The grounding switch is manually engaged
using a rotary operating mechanism to ensure isolation from the
line supply when maintenance is being carried out. Measures
must be taken at the plant to ensure that the grounding switch
cannot be engaged when voltage is applied.
It is also essential to ensure that the supply system cannot be
connected when the grounding switch is engaged.
The signals required for mutual interlocking are available on the
terminal strip.
L47
Grounding switch downstream of main circuit breaker
The grounding switch is installed downstream of the circuit
breaker in the Line Connection Module and short-circuits the
incoming supply system to ground downstream of the main
circuit breaker. The grounding switch is manually engaged using
a rotary operating mechanism to ensure isolation from the line
supply when maintenance work is being carried out on the
converter.
In this case, the grounding switch and the main circuit breaker
for the Line Connection Module are interlocked with each other,
which ensures that the grounding switch cannot be closed when
the main circuit breaker is closed.
If the grounding switch is engaged, it is interconnected to ensure
that the main circuit breaker cannot be closed.

6/126 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Cabinet Modules

Description of the options

■ Options
L61, L62, L64, L65
Braking units P/P20 G_D011_EN_00328

Braking units may be required for drives in which motors might


operate in generator mode, but have no facility for feeding
energy back into the supply system. 1.50
The braking unit comprises two components: 1.25 P15
• A Braking Module that can be installed in the air discharge
of the chassis format power units 1.00 P20

• A braking resistor to be mounted externally (degree of 0.75


protection IP20)
0.50 P40
The braking unit functions as an autonomous unit, and does not PDB
require an external power supply. During the braking process, 0.25
the kinetic energy is converted into heat in the externally
mounted braking resistor. 0
10 15 20 30 40 50 60 70 80 90 100 s t
A max. cable length of 100 m is permissible between the
Braking Module and the braking resistor. This allows the braking
resistor to be mounted externally so that heat losses can be
dissipated outside the converter enclosure. The braking resistor PDB = Rated power
is directly connected to the Braking Module. P15 = 5 x PDB = Power which is permissible every 90 s for 15 s
P20 = 4 x PDB = Power which is permissible every 90 s for 20 s
For SINAMICS S120 Cabinet Modules the following braking
modules are available, depending on the frame size: P40 = 2 x PDB = Power which is permissible every 90 s for 40 s

Option Can be used Braking Module


with frame sizes Load diagram for Braking Modules and braking resistors
Rated Braking Peak Additional notes about possible duty cycles of the braking
power PDB power P20 power P15 resistors and other engineering notes are included in the
kW kW kW SINAMICS Low Voltage Engineering Manual.
380 ... 480 V 3 AC, 660 ... 690 V 3 AC L87 6
L61 FX 25 100 125 Insulation monitoring
L62 GX, HX, JX 50 200 250 An insulation monitor must be used if the converter is connected
500 ... 600 V 3 AC to an ungrounded line supply. The device monitors the entire
galvanically coupled circuit for insulation faults.
L64 FX 25 100 125
L65 GX, HX, JX 50 200 250
An alarm is output in the event of a fault.
Notice:
PDB: Rated power (continuous braking power)
Only one insulation monitor can be used in each galvanically
P20: 20 s power referred to a braking interval of 90 s coupled network.
P15: 15 s power referred to a braking interval of 90 s As there are different response strategies when a ground fault
If the braking units listed here do not provide adequate braking occurs in an ungrounded system, output relays of the insulation
power, up to four braking units on a DC link busbar may be monitor are provided for integration in a plant-side control. It is
connected in parallel. Braking power can be shared among also possible to integrate the outputs into the Cabinet Modules
several Modules. In this case, a Braking Module is assigned to monitoring system on the plant side.
each braking resistor. M06
Note: Base 100 mm high, RAL 7022
It is only possible to use a Braking Module, if a DC interface The additional cabinet base allows larger bending radii for
(option L37) has not been selected for the Motor Module. cables (cable inlet from below) and enables them to be routed
When engineering the system, it should be ensured that the within the cabinet base.
module in which the Braking Module is installed is switched on The cabinet base is supplied in RAL 7022 as standard. A special
during braking so that the Braking Module is properly cooled. paint finish is not available for the base. It is delivered completely
Failure to follow this instruction means that the Braking Module assembled with the cabinet. The height of the operator panel
could overheat and shut down, the drive will no longer be able changes accordingly.
to operate in braking mode. In this case, the Braking Modules
should preferably be located in the Line Modules. Combination with option M66 is not possible.

Siemens D 21.3 · 2022 6/127


© Siemens 2022

SINAMICS S120 Cabinet Modules

Description of the options

■ Options
M07 M27
Cable marshaling space 200 mm high, RAL 7035 Side panel mounted to the left
The cable marshaling space is made of strong sheet steel and For side-by-side installation of Cabinet Modules from right to left,
allows cables to be connected more flexibly (entry from below). cabinets can be ordered ready-prepared at the factory for
It also allows routing of cables within the marshaling space. It is assembly on-site. If option M27 is ordered, the Cabinet Module
delivered completely assembled with the cabinet. The height of is shipped with a side panel fitted on the left.
the operator panel changes accordingly.
This side panel is essential for ensuring compliance with IP20
Notice: and higher degrees of protection.
The cable marshaling space is painted as standard with
RAL 7035. If a special color is requested for the cabinet (option M43
Y09), the cable marshaling space is also painted in this color. Degree of protection IP43

Combination with option M66 is not possible. Cabinet Modules with degree of protection IP43 are supplied
with additional plastic ventilation grilles and a filter medium in
the air inlet and outlet. The filter medium must be maintained
M16 according to the local environmental conditions. The covers
Dust protection packaging provided with option M60 are also included in the scope
of supply.
All Cabinet Modules are taped with a protective film. The
connection fields are omitted so that a connection of the power The air-cooled Cabinet Modules are additionally supplied with
cables is possible. 2-language warning labels are attached to a roof section. This increases the cabinet height by 400 mm.
the protective film. For transport reasons, the roof sections are delivered separately
and must be fitted on site.
Notice:
Notice:
Recommendation for the order of option M16 for shipbuilding The roof sections are painted in RAL 7035 as standard. If
and offshore applications for main and auxiliary drives. In the a special color is requested for the cabinet (option Y09),
event of consequential damage caused by installation work on the roof section is also painted in this color. The molded plastic
site, Siemens assumes no liability/costs in the event parts (e.g. ventilation grilles) are in RAL 7035 and cannot
of contamination. be painted.
M21 M45
6 Degree of protection IP21 (for air cooling only) Cable entry via MCT frame
Cabinet version in IP20, but with additional top cover or canopy. The base plates included as standard for the line and motor
This increases the cabinet height by 250 mm. For transport connection are omitted. Instead, a galvanized MCT-Brattberg
reasons, the top covers or canopies are delivered separately frame type RGSFB 8x1, cut-out 120 x 280 mm, is installed
and must be fitted on site. without inserts.
Notice: Depending on the number of cables, cable cross-section and
The top covers or canopies are painted in RAL 7035 as required seal, the corresponding inserts must be procured on
standard. If a special color is requested for the cabinet (option the system side.
Y09), the top covers or canopies are also painted in this color. Cabinet installation, if necessary in combination with a basic
frame (100 mm), have to be carried out with the order
Degree of protection IP21 is the standard version for liquid- engineering.
cooled Cabinet Modules. The option M45 can only be ordered with option M66, M06
M23 or M07.
Degree of protection IP23 For more information, see: www.mctbrattberg.com/products/
Cabinet Modules with degree of protection IP23 are supplied M51
with additional plastic ventilation grilles and a filter medium in the Motor connection wired to customer terminal
air inlet and outlet. The filter medium must be maintained
according to the local environmental conditions. The covers Option M51 can only be selected in combination with option M77
provided with option M60 are also included in the scope (version without component support plates or additional control
of supply. components).
The air-cooled Cabinet Modules are additionally supplied with With option M51, the connection of the motor cable is wired
a roof section. This increases the cabinet height by 400 mm. For to a customer terminal -X1 and thus makes the process of
transport reasons, the roof sections are delivered separately and connecting motor cables easier.
must be fitted on site. Without option M51, the motor cable is connected directly to the
Notice: Motor Module. In systems with one motor reactor or two series-
The roof sections are painted in RAL 7035 as standard. If connected motor reactors (option L08/L09), the motor cables
a special color is requested for the cabinet (option Y09), the roof are connected directly to the motor reactor.
section is also painted in this color. The molded plastic parts
(e.g. ventilation grilles) are in RAL 7035 and cannot be painted.
M26
Side panel mounted at the right
For side-by-side installation of Cabinet Modules from left to right,
cabinets can be ordered ready-prepared at the factory for
assembly on-site. If option M26 is ordered, the Cabinet Module
is shipped with a side panel fitted on the right.
This side panel is essential for ensuring compliance with IP20
and higher degrees of protection.

6/128 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Cabinet Modules

Description of the options

■ Options
M54 M60
Degree of protection IP54 (for air cooling only) Additional touch protection
Cabinet Modules with degree of protection IP54 are supplied The Cabinet Modules are designed in accordance with DGUV
with additional roof sections, plastic ventilation grilles, and a filter regulation 3 as standard. With option M60, additional covers
medium in the air inlet and outlet, which ensures compliance (out of reach) at accessible operator control and switching
with degree of protection IP54. This increases the cabinet height elements are provided in the area of the AC and DC busbars and
by 400 mm. For transport reasons, the roof sections are in front of the power unit.
delivered separately and must be fitted on site.
Option M60 is already included in M23, M43, and M54 for the
The filters must be maintained according to the local following Cabinet Modules.
environmental conditions. • Line Connection Modules
Notice: • Basic Line Modules
• The roof sections are painted in RAL 7035 as standard. If • Smart Line Modules
a special color is requested for the cabinet (option Y09), the • Active Line Modules with Active Interface Modules
roof section is also painted in this color. The molded plastic
parts (e.g. ventilation grilles) are in RAL 7035 and cannot • Motor Modules chassis
be painted. • Central Braking Modules
• For units with degree of protection IP54, it is important to • Auxiliary Supply Modules
observe the derating factor for output currents in relation
to ambient temperature and installation altitude. Liquid-cooled Cabinet Modules incorporate additional touch
protection as a standard feature – it does not have to be ordered
Degree of protection IP54 (for liquid cooling only) with option M60.
Cabinet Modules with degree of protection IP54 are supplied M66
with additional plastic ventilation grilles and a filter medium in Marine version
the air inlet and outlet. The filter medium must be maintained
according to the local environmental conditions. For compliance with the requirements of the classification
institutes:
M55 • Det Norske Veritas (DNV)
Degree of protection IP55 (for liquid cooling only)
• American Bureau of Shipping (ABS)
Cabinet Modules with degree of protection IP55 are supplied
with closed doors and roof sheets (without additional roof
• China Classification Society (CCS) 6
section). Water jets from any angle are permitted. Because the This option includes a strengthened mechanical version of
cabinets are completely enclosed and there is no exchange of the cabinet, handles (handrail) below the operator panel and
air with the environment, it is not necessary to clean a filter mechanical locking of the cabinet doors. The cabinet has
medium. degree of protection IP23 (option M23) and includes a cabinet
anti-condensation heater (option L55). To secure the converter
The derating data are provided in the derating characteristics to the ship's hull, a basic/welding frame (100 mm high)
for the liquid-cooled Cabinet Modules. is supplied.
Almost all heat losses are dissipated into the cooling liquid. Note:
M56 Combination with options M06, M07, M21, M23 and L55 is not
Reinforced mechanical design possible. Individual certification is additionally required if the
This option includes a strengthened mechanical version of the converter is used for a safety-related drive on the ship
cabinet and mechanical locking of the cabinet doors. To secure (see options E51 to E71).
the converter to the floor, a welding frame (5 mm high) is Other classification institutes on request.
supplied separately. This option is available for all degrees
of protection. M70
EMC shield bus
Note:
Option M56 cannot be combined with option M70 The EMC shield bus is used to connect shielded line and motor
(EMC shield bus). supply cables. The shields can be applied over a large surface
area with the supplied EMC shield clips.
M59
Closed cabinet doors, air inlet from below through floor The EMC shield bus is included as standard with option L00
opening (RFI suppression filter).
If the Cabinet Modules are erected on a false floor or duct which The Active Line Connection Modules compact contain DC link
forms part of a forced ventilation system, the modules can be fuses as standard.
ordered with closed cabinet doors. To ensure an adequate air
inlet cross-section, the units are shipped without the standard
base plates. In this case, the customer must ensure that no
dirt/dust or moisture can enter the Cabinet Module. Cables must
not be routed in such a way that they impede the flow of air
through the cabinet floor opening. If the area beneath the
Cabinet Modules can be accessed, the customer must
provide touch protection.

Siemens D 21.3 · 2022 6/129


© Siemens 2022

SINAMICS S120 Cabinet Modules

Description of the options

■ Options
M72 Order DC busbar system, Number Dimensions Compatible with
Quick-release couplings for water hoses code rated current IN
(for liquid cooling only) A mm (in)
With option M72, the ports for connecting the water hoses to M80 1170 1 60 × 10 (2.36 × M83
the power modules and heat exchangers are fitted with quick- 0.39)
release couplings. The quick-release couplings ensure that M81 1500 1 80 × 10 (3.15 × M84 and M86
no liquid escapes during uncoupling. 0.39)
The use of quick-release couplings makes disassembly of the M82 1840 1 100 × 10 M85 and M87
power units and heat exchangers considerably easier. (3.94 × 0.39)
M83 2150 2 60 × 10 (2.36 × M80
M77 0.39)
Version without component support plates and without
additional control components M84 2730 2 80 × 10 (3.15 x M81 and M86
0.39)
If electronic components (Control Unit, Terminal Modules, M85 3320 2 100 × 10 M82 and M87
Sensor Modules) are not used in the Booksize Cabinet Kit, (3.94 × 0.39)
the mechanical component support plates are omitted with
M86 3720 3 80 × 10 (3.15 x M81 and M84
option M77, including the customer terminal blocks for 0.39)
connecting motor cables.
M87 4480 3 100 × 10 M82 and M85
The motor cables are then connected directly to the Motor (3.94 × 0.39)
Module in booksize format.
The DC busbars are nickel-plated as standard and are available
When option L08/L09 is used (motor reactor / 2 motor reactors in different designs for a variety of current-carrying capacities.
in series), the motor cables are connected directly to the motor The scope of supply also includes the jumpers required to link
reactor. the busbar systems of individual Cabinet Modules.
The table below provides an overview of possible motor cable M88
connection cross-sections for motor cables connected directly DC busbar system for line-side Cabinet Modules
to a Motor Module in booksize format: (only for liquid cooling) and Cabinet Modules-2
Booksize Cabinet Kit Rated output current of Conductor Option M88 is required if Motor Modules are to be installed to the
6 6SL3720-...
Motor Module
A
cross-section
mm2
left or if up to four Basic Line Connection Modules or Active Line
Connection Modules are to be connected for a parallel
connection.
1TE21-0AB3 9 1.5 ... 6
1TE21-8AB3 18 1.5 ... 6 For this purpose, DC busbars are built into the upper part on the
left hand side in the line-side Cabinet Module of each Active Line
1TE23-0AB3 30 1.5 ... 6 Connection Module and Basic Line Connection Module.
1TE24-5AB3 45 6 ... 50
The busbars are nickel plated as standard and are selected for
1TE26-0AB3 60 6 ... 50 different current carrying capacities as for the selected options
1TE28-5AB3 85 16 ... 120 M80 to M87.
1TE31-3AB3 132 25 ... 120 M90
Crane transport assembly (top-mounted)
Note:
A top-mounted crane transport assembly can be ordered as
When combined with option M51, the motor connection is wired an option for Cabinet Modules.
to a customer terminal.
Depending on the width of the module, it consists of either
M80 to M87 transport eyebolts (width 800 mm) or transport rails
DC busbar system (width >800 mm).
The correct DC busbar for the Cabinet Module must be ordered. When Cabinet Modules are ordered as factory-assembled
This is fitted in the upper section of the Cabinet Modules and transport units (option Y11), they are shipped with transport
connects the Line Modules to the Motor Modules. rails, i.e. option M90 is automatically included in the scope of
The busbar is dimensioned according to the load requirements supply of option Y11 and does not need to be ordered
and demand factor associated with operation of the individual separately.
drives, and according to the specific Cabinet Module layout. For M91
this reason, the DC busbar is not supplied as standard, but must Marking of all control cable conductor ends
be ordered as an option. (incl. customer-specific wiring)
When selecting busbars, it is important to ensure that the When this option is selected, all control cables or conductor
systems of adjacent Cabinet Modules are compatible with one ends (including all customer-specific options) are labeled
another (refer to the table below and option selection matrix for throughout the cabinet.
the Cabinet Modules in question).
Where Cabinet Modules are ordered as a factory-assembled
transport unit with option Y11, all busbars in the transport unit
must be identical.

6/130 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Cabinet Modules

Description of the options

■ Options
N52 T58, T60, T80, T83, T85, T91
DC link fuses Rating plate data
The Basic Line Modules (air-cooled), Active Line Connection The rating plate is provided in English/German as standard.
Modules and Basic Line Connection Modules (liquid-cooled) A rating plate in another language combination can be selected
come without DC link fuses as standard. by specifying the following option order codes.
If fuses are required, they can be ordered with option N52. Option Rating plate language
The fuses are mounted on the connecting rail to the DC busbar
T58 English/French
in the cabinet rather than in the power unit.
T60 English/Spanish
The use of DC link fuses is recommended when Basic Line
Modules, Active Line Connection Modules, and Basic Line T80 English/Italian
Connection Modules are connected in parallel. T83 English/Portuguese (Brazil)
The Motor Modules and Motor Modules compact contain DC link T85 English/Russian
fuses as standard. T91 English/Chinese
P10 W01
Measuring instrument for line values, mounted in the Heat Exchanger Module, partially redundant with 2 pumps
cabinet door
The Heat Exchanger Module is equipped with a pump and
A measuring instrument with display, installed in the cabinet a plate-type heat exchanger as standard. With option W01,
door of the Line Connection Module, for acquiring measured two redundant pumps with two dirt traps and non-return valves
values of the power supply. In addition to these measured are fitted. The pumps, which operate alternately, pump the hot
values, additional plant values (such as power and power factor, coolant of the deionized water circuit on the converter side into
etc.) are calculated from the measured values using powerful, the plate-type heat exchanger and there it is cooled by the raw
state-of-the art microprocessors. water of the plant-side circuit.
Current transformers (option L41) are already included in the System reliability is increased as a result of the alternating
scope of supply. operation of the redundant pumps. The time in hours can be
P11 parameterized. In addition, the dirt traps can be cleaned
Measuring instrument for line values with PROFIBUS independently and during operation, as shutoff valves are
connection, mounted in the cabinet door installed before and after the individual pumps.
Note:
6
A measuring instrument with display, installed in the cabinet
door of the Line Connection Module, for acquiring measured Option W01 increases the cabinet width by 400 mm and its
values of the power supply. In addition to these measured weight by 110 kg.
values, additional plant values (such as power and power factor, W10
etc.) are calculated from the measured values using powerful, Pipe insulation in the raw water circuit and of the heat
state-of-the art microprocessors. The measuring instrument has exchanger
a PROFIBUS interface that permits a data transfer rate of up to
12 Mbps. With this option, the pipes in the raw water circuit and of the heat
exchanger are insulated. This means that if the raw water on the
Current transformers (option L41) are already included in the plant side is too cold, condensation does not occur on the pipes
scope of supply. and liquid does not collect in the Heat Exchanger Module.
W20
Raw water connection from the bottom
The raw water from the supply is fed into the Heat Exchanger
Module from above as standard. With option W20, the line-side
raw water connection in the Heat Exchanger Module is at
the bottom.
The piping system is made of W 1.4404 (V4A, AISI 316)
stainless steel.
W25
Raw water connection from the side
The raw water from the supply is fed into the Heat Exchanger
Module from above as standard. With option W25, the raw water
connection in the Heat Exchanger Module is made from the side.
The version of option W25 depends on the ordered option W34
or W36.
The piping system is made of W 1.4404 (V4A, AISI 316)
stainless steel.

Siemens D 21.3 · 2022 6/131


© Siemens 2022

SINAMICS S120 Cabinet Modules

Description of the options

■ Options
W34 Notice:
Heat Exchanger Module for installation on left If options such as cable marshaling space (option M07), top
covers or canopies (option M21) or roof sections (options
With this option, a fixed pipe connection is routed downward on M23/M43/M54) are ordered for the Cabinet Modules, they will
the right-hand side. The option is required to install the Heat also be supplied in the paint finish specified for the cabinet in the
Exchanger Module at the left end of the drive line-up and to be order. The molded plastic parts (e.g. ventilation grilles) are in
able to connect it to the deionized water circuit on the converter RAL 7035 and cannot be painted.
side. The connecting parts are on hand.
Y11
W36 Factory assembly into transport units
Heat Exchanger Module for installation on the right
With this option, Cabinet Modules can be ordered as factory-
With this option, a fixed pipe connection is routed downward assembled transport units with a maximum total width of up to
on the left-hand side. The option is required to install the Heat 2400 mm. In this case, the relevant modules are shipped as
Exchanger Module at the right end of the drive line-up and to be interconnected units (both electrically and mechanically).
able to connect it to the deionized water circuit on the converter
side. The connecting parts are on hand. When DC busbars (options M80 to M87) are selected, it must be
ensured that identical busbars are installed within the transport
W43 unit and are compatible with all adjacent Cabinet Modules.
Release valve in the deionized water circuit
In the case of a transport unit order, all the Cabinet Modules to
A release valve is installed between the intake and return in be included in the unit and their installation sequence from left to
the converter-side deionized water circuit. The valve limits the right must be specified in plain text according to the syntax
discharge pressure of the circulating pumps. As soon as the below:
discharge pressure exceeds the value set at the valve, the valve
opens the bypass. Plain text required to order TU 1 - 1 ... 6

W48 • Transport unit (TU)


Leakage sensor in the converter cabinet, at the bottom in the • Serial number of transport unit
cabinet floor
• Position of Cabinet Module within transport unit from left to right
With this option, a leakage sensor is installed at the cabinet floor
of the respective converter cabinet for which the option is In the case of air-cooled Cabinet Modules, option Y11 is
ordered. A common evaluation module is installed in the Basic recommended when creating units comprising Line Connection
6 Line Connection Module, Active Line Connection Module or Modules with Line Modules because the required pre-charging
circuits and connection busbars, for example, can be
Active Line Connection Module compact. The wiring to the TM31
Terminal Module in the Heat Exchanger Module must be done on incorporated for certain versions. Please refer to the assignment
the plant side. If you order the option W48, please also verify the tables for the Line Connection Modules.
need of option W49 "Leakage sensor in the Heat Exchanger With liquid-cooled Cabinet Modules, option Y11 is especially
Module". recommended to reduce the number of connection elements
Recommendation: used in the cooling circuit on the converter side. It results in
Order of option W48/W49 for shipbuilding and offshore lower resistance to flow and avoids leaks. Option Y11 is not
applications with individual certification DNV, option E51. permitted in connection with Heat Exchanger Modules.
The transport unit is shipped with a crane transport rail,
W49
which means that option M90 is not required.
Leakage sensor in the Heat Exchanger Module, at the bot-
tom in the cabinet floor Y31
With this option, a leakage sensor is installed at the cabinet floor One-line label for system identification, 40 × 80 mm
of the Heat Exchanger Module. The installed evaluation module Resopal labeling plates (white with black lettering) for identifying
is connected to a digital input of the TM31 Terminal Module. Cabinet Modules are available. The labels are stuck to the
When a leak is detected, a corresponding alarm or fault (can be cabinet door.
parameterized) is output.
Dimensions H × W: 40 × 80 mm
Recommendation:
Order of option W48/W49 for shipbuilding and offshore The text must be specified in plain text when ordering.
applications with individual certification DNV, option E51. Field 1: Max. 9 characters, font size 10 mm
W62
Sensors in the raw water circuit on the plant/system side
With this option, a flow monitor and a Pt1000 temperature sensor +D4Z01R04 40
are installed in the intake of the plant-side raw water circuit.
The signals are transferred to the TM31 or TM150 Terminal Field 1

Module. This meansthat the flow and temperature can be 80


monitored.
The temperature alarm limit can be parameterized in the Control
Unit. The flow signal is parameterized at the sensor, and is
evaluated by the TM31 Terminal Module.
Y09
Special cabinet paint finish
The Cabinet Modules are delivered in RAL 7035 as standard.
The special paint finish must be specified in plain text when
ordering. Any RAL colors that are available as powdered
coatings can be selected. Other special colors on request.

6/132 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Cabinet Modules

Description of the options

■ Options
Y32
Two-line label for system identification, 40 × 180 mm
Resopal labeling plates (white with black lettering) for identifying
Cabinet Modules are available. The labels are stuck to the
cabinet door.
Dimensions H × W: 40 × 180 mm
The text must be specified in plain text when ordering.
Field 1: Max. 9 characters, font size 10 mm
Field 2: Max. 9 characters, font size 10 mm
Field 3: Max. 20 characters, font size 10 mm

90

+D4Z01R04 -31FA011
Field 1 Field 2
40

Field 3
infeed roller FS
180

Y33
Four-line label for system identification, 40 × 180 mm
Resopal labeling plates (white with black lettering) for identifying
Cabinet Modules are available. The labels are stuck to the
cabinet door.
Dimensions H × W: 40 × 180 mm
The text must be specified in plain text when ordering.
Field 1: Max. 9 characters, font size 10 mm
6
Field 2: Max. 20 characters, font size 6 mm
Field 3: Max. 20 characters, font size 6 mm
Field 4: Max. 20 characters, font size 6 mm
Field 5: Max. 20 characters, font size 6 mm

80

-31 FA011 Short text 1 Field 2


+D4Z01R04 --31 FA012 Short text 2
31FA013 Short text 3
Field 3

Field 4
40

Field 1 -31FA014 Short text 4 Field 5


180

Siemens D 21.3 · 2022 6/133


© Siemens 2022

SINAMICS S120 Cabinet Modules


Supplementary system components
Mounting device for air-cooled power blocks

■ Overview ■ Selection and ordering data


Description Article No.
Mounting device 6SL3766-1FA00-0AA0
for installing and removing power blocks

Power block mounting device for installing and removing the


power blocks for the Basic Line Modules, Smart Line Modules,
Active Line Modules and Motor Modules in chassis format.
The mounting device is a mounting aid. It is placed in front of the
module and attached to the module. The telescopic rails allow
the device to be adjusted to the installation height of the power
blocks.
Once the mechanical and electrical connections have been
released, the power block can be removed from the module.
The power block is guided and supported by the guide rails on
6 the handling device.

Mounting device for liquid-cooled power units

■ Overview The mounting device is a mounting aid. It is placed in front of the


power unit and attached to the mounting rails below the power
unit. The telescopic rails allow the mounting device to be
adjusted to the installation height and width of the power unit.
The power unit can be removed from the control cabinet after
releasing the mechanical and electrical connections and the
coolant connections. The power unit is guided and supported by
the guide rails on the mounting device. To prevent it toppling
over, the power unit must be secured to a crane, tripod, or similar
assembly using the lifting lugs or the lifting equipment. The unit
can then be lowered down from the mounting device.

■ Selection and ordering data


Description Article No.
Mounting device 6SL3766-1CA00-0AA0
for installing and removing power units

The mounting device is used to install or remove liquid-cooled


power units (Line Modules, Motor Modules) into or out of
a control cabinet. The mounting device can be used if the power
units are mounted on mounting rails, which at the front have two
M6 threads at a vertical distance of 20 mm to attach the
mounting device.

6/134 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Cabinet Modules

Order-specific integration engineering

■ Overview ■ Selection and ordering data


Just like the SINAMICS S120 buit-in units, SINAMICS S120 The following engineering services can be ordered depending
Cabinet Modules and Cabinet Modules-2 form a modular drive on the number of drives/axes included in an order:
system that consists of various intelligent Drive Objects such as
Line Modules, Motor Modules, Control Units, Sensor Modules, Integration engineering Article No.
etc. For 1 drive 6SL3780-0AA00-0AA0
(also parallel connection)
As a consequence, SINAMICS S120 Cabinet Modules and including the associated Line Modules,
Cabinet Modules-2 are supplied with documentation that only Sensor Modules, Terminal Modules, etc.
includes and describes the individual Cabinet Modules (circuit For up to 3 drives 6SL3780-0AC00-0AA0
diagram, layout diagram, terminal diagram and additional (also parallel connection)
Operating Instructions). including the associated Line Modules,
Sensor Modules, Terminal Modules, etc.
By selecting option Y11, individual Cabinet Modules are
assembled at the factory as interconnected units for transport For up to 5 drives 6SL3780-0AE00-0AA0
(also parallel connection)
and are then supplied as such. including the associated Line Modules,
Detailed documentation showing features such as the signal Sensor Modules, Terminal Modules, etc.
connections between the individual Cabinet Modules that make For up to 10 drives 6SL3780-0AJ00-0AA0
up the order, is not included in the normal scope of supply. (also parallel connection)
including the associated Line Modules,
In this case, only a collection of the individual documents are Sensor Modules, Terminal Modules, etc.
shipped with the converter.
Engineering services for larger drive systems are also available
If the documentation is to include a complete representation of on request.
the equipment supplied, the equipment and documentation
must be additionally processed. This can be ordered with the
integration engineering.
Integration engineering includes the following:
• Checking the combinations and options ordered, in relation to
the device configurations
• Defining how the individual drive objects are to be connected
and coordinated, with the customer if required.
• Checking the performance of the ordered CompactFlash card 6
• Installing the required DRIVE-CLiQ cables within the transport
units.
Cables between the transport units are connected at one end
• Higher-level documentation of the scope of supply (layout
diagram, circuit diagram, terminal diagram, dimension
drawing, spare parts list).
• Summary of the individual documents included in a shipment,
in conjunction with a delivery address separate from the
equipment
• Customer-specific system and location designations,
coordinated with the customer
Note:
The order-specific integration engineering is especially
recommended for liquid-cooled Cabinet Modules.

Siemens D 21.3 · 2022 6/135


© Siemens 2022

SINAMICS S120 Cabinet Modules

Order-specific integration engineering

■ Options
The table below lists the options available for order-specific
integration engineering
(for details, see Description of the options):
Available options Order code
Customer documentation (circuit diagram, layout diagram, D01
dimension drawing, spare parts list) in EPLAN format.
Customer documentation (circuit diagram, terminal diagram, D02
layout diagram) in DXF format
Preliminary version of customer documentation in PDF format D14
Documentation in English/French D58
Documentation in English/Spanish D60
Documentation in English/Italian D80
Documentation in English/Chinese D91
Documentation in English/Portuguese (Brazil) D93
Documentation in English/Russian D94

When ordering the order-specific integration engineering, the


required documentation options must always be ordered
together with the order engineering (not with the individual
Cabinet Modules).
Ordering the documentation options for the particular Cabinet
Modules is only required if equipment is ordered without
integration engineering.
Option selection matrix of the order-specific integration
engineering
Certain options are mutually exclusive.
6  Possible combination
– Combination not possible

D01 D02 D14 D58 D60 D80 D91 D93 D94


D01  –      
D02        
D14 –       
D58    – – – – –
D60    – – – – –
D80    – – – – –
D91    – – – – –
D93    – – – – –
D94    – – – – –

6/136 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Cabinet Modules

Customized solutions

■ More information
Customized solutions
In addition to the wide range of possibilities of configuring drives
with the available modules and options to address specific plant
and system requirements, for special applications we also offer
customized applications to fully comply with the actual
requirements.
These are based on the standard SINAMICS S120 Cabinet
Modules and are supplied as completely wired units that are
ready to be connected up.
Examples of applications such as these include:
• SINAMICS S120 liquid-cooled Cabinet Modules
for marine applications
The range of requirements that drive systems have to meet
aboard a ship is enormous – and highly varied. In addition to
maximum efficiency and reliability, compactness is absolutely
essential given the confined spaces. The systems used must
also be low-maintenance, service-friendly, and in every way
suitable for marine applications. Siemens provides the answer Cement mill
to these requirements - with the liquid-cooled SINAMICS S120
Cabinet Modules with compact extension. There are the
variants Active Line Connection Modules compact and Motor
Modules compact as well as additional options for marine
applications.
The innovative liquid-cooled drive system for all marine
applications is based on the SINAMICS platform, which is
a proven success worldwide. Its footprint has been optimized
for use on board and it impresses with its flexibility and
economic efficiency.
• SINAMICS S120 Switch-Over Modules
In order to operate different motors at different times on 6
a common converter, SINAMICS S120 Switch-Over Modules
are the ideal solution.
A Switch-Over Module switches the output of the Motor
Module over to the motor that is required.
If, for example, processes powered by specific motors run
subsequently at different times, or if the individual motor is
only briefly used during the day, then costs and space can be
saved by using just one converter, supplemented with the
corresponding Switch-Over Module.
Such applications include, for instance, pump drives on
tankers when various ship compartments have to be emptied
one after the other, or container cranes, if in addition to the
drive for loading and unloading, the drive for operating the
boom also has to be fed from the converter.
• SINAMICS S120 Motor Multi-Connection Modules
For applications performed in combination with group drives Ship docked in port
that require a different number of multi-motor outputs,
SINAMICS S120 Motor Multi-Connection Modules are
a sensible choice.
Motor Modules are supplemented with a corresponding
control system, as well as switching and protection devices.
This configuration allows the associated motors with small
power ratings (motor groups) to be operated from a common
inverter with a high power rating.
The completely prewired, ready-to-connect cabinet units
facilitate and shorten the commissioning procedure.
The transparent and flexible design allows changes and
additions to be made at any time at low associated costs.
Simply contact us if you are interested or require these or any
other applications.
Notes regarding the addresses of contact persons are provided
in the chapter "Services and Documentation" under "Partners at
Siemens".

Oil rig

Siemens D 21.3 · 2022 6/137


© Siemens 2022

SINAMICS S120 Cabinet Modules

Notes

6/138 Siemens D 21.3 · 2022


7
© Siemens 2022

SINAMICS S120 Cabinet Modules-2

7/2 System overview


7/2 Overview
7/2 Benefits
7/3 Application
7/3 Design
7/4 Function
7/6 Technical specifications

7/7 Air-cooled units


7/12 Active Line Connection Modules-2
7/17 Motor Modules in chassis-2 format

7/21 Options

7/23 Mounting aid for Motor Modules/


Active Line Modules in chassis-2 format

7/24 Order-specific integration engineering


7/25 Option selection

7/26 Customized solutions

Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Cabinet Modules-2

System overview

■ Overview
also with SINAMICS S120 Cabinet Modules – and optimally
adapted to customer-specific requirements thanks
to a comprehensive array of options.
The main components of the air-cooled system are as follows:
• Active Line Connection Modules-2 as a combination of Line
Connection Module and Active Line Module with an Active
Interface Module
• Motor Modules
Standardized interfaces for both the power and the control
connections facilitate configuration and installation.
Communication between the power units and the central Control
Unit takes place via DRIVE-CLiQ, the internal drive
serial interface.
Highlights of the Cabinet Modules-2
SINAMICS S120 Cabinet Modules-2 are the components of • Compact, innovative mechanical design of the Motor Module
a modular cabinet system for multi-motor drives with a central for easier installation and removal, and with reduced footprint
supply infeed and a common DC link busbar, as used, for • Rated pulse frequency 2.5 kHz
example, in the process industry, automotive industry, metal
• Optimized derating
processing industry as well as in the crane and mining sectors.
They are available in air-cooled version. As standard, they are • Innovative cooling concept
installed side by side in a row. • Condition monitoring
SINAMICS S120 Cabinet Modules-2 include the chassis units • Very easy replacement of the device fan without removing
from the SINAMICS S120 series in chassis-2 format. the Motor Module from the control cabinet
All drive components, from the supply infeed to the motor-side The following table provides an overview of the voltage ranges
inverters, are configured in a clear, compact layout in the and power ratings of the air-cooled SINAMICS S120 Cabinet
individual Cabinet Modules-2. They can be flexibly combined – Modules-2 that are available.
Voltage ranges and power ratings for air-cooled SINAMICS S120 Cabinet Modules-2
Line voltage Input current DC link voltage DC link current Output current Power range of
single modules
Active Line Connection 380 ... 480 V 3 AC 560 ... 1405 A 570 ... 720 V 630 ... 1575 A – 355 ... 900 kW
Modules-2 1)
Motor Modules 1)
7 380 ... 480 V 3 AC – 510 ... 720 V 785 ... 1795 A 655 ... 1495 A 315 ... 800 kW

■ Benefits
The outstanding system features of the SINAMICS S120 Cabinet - Generally the line infeed is only dimensioned for the
Modules-2 provide the following advantages: maximum energy required when motoring or the maximum
• Process optimization with minimum outlay current required when motoring – and not for the sum of the
- A standard PROFIBUS or PROFINET interface and various energy requirements of the Motor Modules connected to the
analog and digital interfaces enable easy integration into DC link. As a consequence, for example, for conveyor belts
automation solutions or motor test stands with Motor Modules that are
- Vector and servo control ensures that they fulfill the most simultaneously operated in motoring and generating modes,
exacting requirements regarding the accuracy and dynamic a significantly smaller line infeed unit can be selected.
response of drives. • Minimal operative, maintenance, and servicing costs
• High level of reliability and availability - Simple commissioning thanks to the menu-driven
- Individual modules and power components can be replaced commissioning tools SINAMICS Startdrive or STARTER.
quickly and easily, which ensures a higher level of plant - Optional, menu-navigated AOP30 advanced operator panel
availability with plain text display and bar-type display of process
variables.
• Energy saving during operation - All modules are easily accessible, making them extremely
- The motor-side inverters are coupled via the common DC service-friendly
link and allow energy to be exchanged between motors that
are motoring and generating. This means that energy is • Space-saving design
saved, there is less load on the supply infeed and line • Environmentally-friendly operation
harmonics are reduced - The converters are exceptionally quiet and compact thanks
to state-of-the-art IGBT power semiconductors and
an innovative cooling concept

1) The power can be increased by connecting up to six identical modules in


parallel.

7/2 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Cabinet Modules-2

System overview

■ Application
SINAMICS S120 Cabinet Modules-2 have been specially • Hoists and cranes
developed to allow simple configuration of multi-motor systems. • Printing and paper machines
They are used for applications where several motors must be
coordinated to realize a drive task as multi-motor drives in • Vehicle and gearbox test stands
a drive line-up. Examples of such applications include: • Test stand applications
• Packaging machines • Machines used in the woodworking, glass and ceramics
• Plastics processing machines industries
• Textile machines • Handling and assembly systems
• Presses and punches • Machine tools
• Rolling mill drives High-power single drives (parallel connection) can also be
implemented with Cabinet Modules-2.

■ Design
They have been designed according to the zone concept The auxiliary power supply system comprises an auxiliary power
principle and therefore offer the highest possible level of supply module with two terminal blocks and a 24 V DC fuse as
operational reliability. EMC measures have been rigorously well as the required connecting cables. It is supplied completely
implemented. With the help of simulated conditions, partitions assembled and ready to operate. Only the cable connections to
have been designed to act as air guides and heat dissipation the adjacent Cabinet Module-2 must be established on-site.
units.
DRIVE-CLiQ communication
Special measures used in the construction of the cabinets
ensure that they remain mechanically durable over their entire Communication between the Control Unit, power units and other
life cycle. active SINAMICS components is realized via DRIVE-CLiQ
connections.
Attention has been paid to providing a wide range of cable
routing options and special design concepts are applied DRIVE-CLiQ is an internal serial interface of the drive that
consistently to broaden the scope of application and simplify enables fast and easy configuration of the complete drive
service. The units have all the necessary connections and line-up with prefabricated cables in varying lengths.
connecting elements. Thanks to their carefully considered Transport units
configuration concept, cabinets are shipped in
a ready-to-connect state or, in the case of multiple transport The Cabinet Modules-2 can be optionally supplied in pre-
units, have been prepared for quick assembly. An extensive configured transport units up to a total length of 2400 mm.
spectrum of options designed to adapt the units to a variety of Coated modules
different applications facilitates the selection process.
The following devices are equipped as standard with coated
All components, from individual parts to the ready-to-connect modules:
cabinet, undergo rigorous testing throughout the entire
production process. This guarantees a high level of functional • Devices in chassis-2 format 7
reliability during installation and commissioning, as well as in • Control Units
operation. • Sensor Modules
Replaceable components have been designed so that they can • Terminal Modules
be quickly and easily replaced. In addition, the "Spares On Web" • Advanced Operator Panel (AOP30)
internet tool makes it easy to view the spare parts that are
available for the particular order at all times 1). The coating on the modules protects the sensitive SMD
components against corrosive gases, chemically active dust
System design and moisture.
Active Line Connection Modules are coupled with the Motor Nickel-plated busbars
Modules by means of prefabricated busbar sets with different
current carrying capacities. All of the copper busbars used in the converter cabinets are
nickel-plated to achieve the best possible immunity to
All standard busbars, as well as electronics components, are environmental effects. Furthermore, there is no need to clean the
protected against environmental influences. This is achieved contacts on the customer terminals as otherwise required for
through the use of nickel-plated copper bars and painted bare copper connections.
modules throughout.
Note:
Auxiliary power supply system
With some options, parts of the copper busbars cannot be
A special, standard auxiliary power supply system supplies the nickel-plated for technical reasons.
individual Cabinet Modules-2 with the required auxiliary voltages
for the power components, fans and 24 V loads.
These voltages are preferably generated using an Auxiliary
Power Supply Module. Additional supply possibilities are
available using the K76 option (auxiliary power supply
generation in the Line Connection Module) or using an external
supply in the auxiliary power supply system.

1)
The properties of the SINAMICS S120 Cabinet Modules-2 described in this
catalog are not transferable to cabinet units constructed to meet the
requirements of specific applications.

Siemens D 21.3 · 2022 7/3


© Siemens 2022

SINAMICS S120 Cabinet Modules-2

System overview

■ Design ■ Function
PE bars Communication with higher-level controller and customer
terminal strip
The Cabinet Modules-2 are delivered with a PE bar as standard.
It is used to connect and fasten PE conductors. As the customer interface to the control system, a PROFIBUS
interface is available on the CU320-2 DP Control Unit or
Degrees of protection of Cabinet Modules-2 a PROFINET interface on the CU320-2 PN Control Unit
The EN 60529 standard covers the protection of electrical as standard.
equipment by means of housings, covers or equivalent, For further information, please refer to the SINAMICS Low
and includes: Voltage Engineering Manual.
• Protection of persons against accidental contact with live
or moving parts within the housing and protection of the Open-loop and closed-loop control functions
equipment against the ingress of solid foreign bodies SINAMICS S120 can use a dynamic, high-precision closed-loop
(touch protection and protection against ingress of solid vector control (drive object type VECTOR), or a highly dynamic
foreign bodies) closed-loop servo control (drive object type SERVO).
• Protection of the equipment against the ingress of water
(water protection)
• Abbreviations for the internationally agreed degrees
of protection
The degrees of protection are specified by abbreviations
comprising the code letters IP and two digits.
Degree of First code number Second code number
protection (touch protection and (protection of the
protection against solid equipment against the
foreign bodies) ingress of water)
IP20 Protected against solid No water protection
(Standard for foreign bodies
air-cooled version) diameter  12.5 mm

IP21 Protected against solid Protected against drip


(Option M21) foreign bodies water
diameter  12.5 mm Vertically falling water
drops shall not have
a harmful effect.
IP23 Protected against solid Protected against spray
(Option M23) foreign bodies water
diameter  12.5 mm Water sprayed on both
7 sides of the vertical at an
angle of up to 60° shall
not have a harmful effect.
IP43 Protected against solid Protected against spray
(Option M43) foreign bodies water
diameter  1 mm Water sprayed on both
sides of the vertical at an
angle of up to 60° shall
not have a harmful effect.
IP54 Dust protected Protected against splash
(Option M54) Ingress of dust is not totally water
prevented, but dust must Water splashing onto the
not be allowed to enter in enclosure from any
such quantities that the direction shall not have
functioning or safety of the a harmful effect.
equipment is impaired.
Complete touch protection

7/4 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Cabinet Modules-2

System overview

■ Function
Software and protective functions
The software functions available as standard are described below:
Software and Description
protective functions
Setpoint input The setpoint can be specified both internally and externally; internally as a fixed setpoint, motorized potentiometer setpoint or jog
setpoint, externally via the communications interface or an analog input. The internal fixed setpoint and the motorized potentiometer
setpoint can be switched over or adjusted using control commands from any interface.
Motor identification The automatic motor identification function makes commissioning faster and easier and optimizes closed-loop control of the drive.
Ramp-function A user-friendly ramp-function generator with separately adjustable ramp-up and ramp-down times, together with adjustable rounding
generator times in the lower and upper speed ranges, allows the drive to be smoothly accelerated and braked. This results in a good speed
control response and contributes to the reduction of stress on the mechanical system. The down ramp can be parameterized separately
for a quick stop.
Vdc max controller The Vdc max controller automatically prevents overvoltages in the DC link, if the set down ramp is too short, for example. This may also
extend the set ramp-down time.
Note: This function only makes sense for single-axis applications.
Kinetic buffering For brief line supply failures, the kinetic energy of the rotating drive is used to buffer the DC link and therefore prevents fault trips. The
(KIP) converter remains operational as long as the drive can provide regenerative energy as a result of its motion and the DC link voltage does
not drop below the shutdown threshold. When the line supply recovers within this time, the drive is again bumplessly accelerated up to
its setpoint speed.
Automatic restart The automatic restart switches the drive on again when the power is restored after a power failure, and ramps up to the current speed
setpoint.
Flying restart The flying restart function allows the converter to be switched to a motor that is still turning. With the voltage sensing capability provided
by the optional VSM10, the flying restart time for large induction motors can be significantly reduced because the motor does not need
to be de-magnetized.
Technology Using the technology controller (PID controller) function module, level or flow controls and complex tension controls can be
controller implemented, for example. The existing D component can act both on the system deviation as well as on the actual value
(factory setting). The P, I, and D components are set separately.
Free function blocks Using the freely programmable function blocks, it is easy to implement logic and arithmetic functions for controlling the SINAMICS drive.
(FFB) The blocks can be programmed at the operator panel or the commissioning tools SINAMICS Startdrive or STARTER.
Drive Control Chart Drive Control Chart (DCC) is an additional tool for the easy configuration of technological functions for SINAMICS. The block library con-
(DCC) tains a large selection of control, arithmetic and logic blocks as well as extensive open-loop and closed-loop control functions. The user-
friendly DCC editor enables easy graphics-based configuration, allows control loop structures to be clearly represented and provides
a high degree of reusability of charts that have already been created. DCC is an add-on for the commissioning tools SINAMICS
Startdrive or STARTER ( Tools and Engineering).
SINAMICS The SINAMICS TEC are configurable functions or Siemens technologies that can be added to extend firmware functions. These
Technology
Extensions
extensions are designed to allow implementation of highly complex, application-specific tasks for various sectors - such as storage and
retrieval machines. 7
(SINAMICS TEC) Additional information about Technology Extensions (TEC) is provided in the "Technology functions" section.
I2t recording for A motor model stored in the converter software calculates the motor temperature based on the current speed and load. More exact
motor protection sensing of the temperature, which also takes into account the influence of the ambient temperature, is possible by means of direct
temperature sensing using Pt1000/KTY84 sensors in the motor winding.
Motor temperature Motor protection by evaluating a KTY84, PTC, Pt100 or Pt1000 temperature sensor. When a KTY84 temperature sensor is connected, the
evaluation limit values can be set for alarm or shutdown. When a PTC thermistor is connected, the system reaction to triggering of the thermistor
(alarm or trip) can be defined.
Motor blocking A blocked motor is detected and protected against thermal overloading by a fault trip.
protection
Brake control "Simple brake control" for controlling holding brakes:
The holding brake is used to secure drives against unwanted motion when deactivated.
The "extended braking control" Function module allows complex braking control, for example, for motor holding brakes and operational
brakes.
In the case of brakes with feedback signal, the brake control reacts to the feedback contacts of the brake.
Write protection Write protection to prevent unintentional changing of the setting parameters (without password function).
Know-how Know-how protection for encrypting stored data, e.g. to protect configuration know-how, and to protect against changes and duplication
protection (with password function).
Web server The web server provides information about the drive unit via its web pages. The web server is accessed using a web browser via
unsecured (http) or secured transfer protocol (https).

Power unit protection


Power unit protection Description
Ground fault A ground fault at the output is detected by a summation current monitor and results in shutdown in grounded systems.
monitoring at the
output
Electronic short- A short-circuit at the output (e.g. at the converter output terminals, in the motor cable or in the motor terminal box) is detected and the
circuit protection at converter shuts down with "fault".
the output
Thermal overload An alarm is issued first when the overtemperature threshold responds. If the temperature continues to rise, the unit either shuts down
protection or independently adjusts the pulse frequency or output current so that thermal load is reduced. Once the cause of the fault has been
eliminated (e.g. cooling has been improved), the original operating values are automatically resumed.

Siemens D 21.3 · 2022 7/5


© Siemens 2022

SINAMICS S120 Cabinet Modules-2

System overview

■ Technical specifications
The most important directives and standards are listed below. These are used as basis for the SINAMICS S120 Cabinet Modules-2
and they must be carefully observed to achieve an EMC-compliant configuration that is safe both in terms of functionality and in
operation.
European directives
2014/35/EU Low-voltage Directive:
Directive of the European Parliament and Council of February 26, 2014 for the harmonization of the laws of the member states relating to
the provision of electrical equipment designed for use within certain voltage limits on the market (recast)
2014/30/EU EMC Directive:
Directive of the European Parliament and Council of February 26, 2014 for the harmonization of the laws of the member states relating to
electromagnetic compatibility (recast)
2006/42/EC Machinery Directive:
Directive of the European Parliament and Council of May 17, 2006, on machinery and amending Directive 95/16/EC (recast)
2011/65/EU RoHS II Directive:
Directive of the European Parliament and of the Council of 8 June 2011 on the restriction of the use of certain hazardous substances in
electrical and electronic equipment (recast)
European standards
EN ISO 3744 Acoustics – Determination of sound power levels and sound energy levels of noise sources using sound pressure –
Engineering methods for an essentially free field over a reflecting plane
EN ISO 13849-1 Safety of machinery – Safety-related parts of control systems
Part 1: General principles for design (EN ISO 13849-1: 2006)
EN 60146-1-1 Semiconductor converters – General requirements and line-commutated converters
Part 1-1: Specification of basic requirements
EN 60204-1 Safety of machinery – Electrical equipment of machines
Part 1: General requirements
EN 60529 Degrees of protection provided by enclosures (IP code)
IEC 61508-1 Functional safety of electrical/electronic/programmable electronic safety-related systems
Part 1: General requirements
IEC 61508-2 Functional safety of electrical/electronic/programmable electronic safety-related systems
Part 2: Requirements for electrical/electronic/programmable electronic safety-related systems
IEC 61508-3 Functional safety of electrical/electronic/programmable electronic safety-related systems
Part 3: Software requirements
EN 61800-2 Adjustable speed electrical power drive systems
Part 2: General requirements – Rating specifications for low voltage adjustable frequency AC power drive systems
EN 61800-3 Adjustable speed electrical power drive systems
7 Part 3: EMC requirements and specific test methods
EN 61800-5-1 Adjustable speed electrical power drive systems
Part 5: Safety requirements
Main section 1: Electrical and thermal requirements
EN 61800-5-2 Adjustable speed electrical power drive systems
Part 5-2: Safety requirements – Functional safety (IEC 61800-5-2: 2007)

7/6 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Cabinet Modules-2


Air-cooled units

■ Overview
The SINAMICS S120 Cabinet Modules-2 system comprises Motor Modules
Active Line Connection Modules and Motor Modules in
chassis-2 format. Each SINAMICS S120 Cabinet Module-2 is equipped with
a Motor Module in chassis-2 format and covers the power range
Active Line Connection Modules-2 from 315 kW to 800 kW (380 V to 480 V). The power rating can
be extended up to approx. 4560 kW by connecting up to six
Active Line Connection Modules-2 comprise a Line Connection Motor Modules in parallel.
Module, an Active Interface Module, and an Active Line Module
installed in a cabinet system.
Active Line Connection Modules-2 can supply energy to the
intermediate DC circuit and return regenerative energy to the
line supply (energy recovery).
Active Line Connection Modules-2 generate a regulated DC
voltage which remains constant despite fluctuations in the line
voltage. However, in this case, the line voltage must remain
within the permissible tolerance range. Active Line Connection
Modules-2 draw a virtually sinusoidal current from the supply
system. Almost no harmonics occur. The total harmonic
distortion factors of the current THD(I) and voltage THD(U) are
typically in the range of approx. 3 % for rated current. THD(I) is
calculated according to IEEE 519 (2014) and THD(U) according
to IEC 61000-2-4 (2002). The stringent limit values of
IEEE 519 (2014) are typically complied with.
Active Line Connection Modules-2 always also contain a Clean
Power Filter and the required pre-charging input circuit for the
Active Line Module.

Active Line Connection Module


Line Connection Module
Switch Bypass Active Active Line
disconnector contactor Interface Module
with fuses Module

=
Motor
Module
7
G_D213_EN_00107

M
3

Active Line Connection Module-2 with Active Interface Module and


Active Line Module 800 A

Active Line Connection Module


Line Connection Module
Active Active Line
Circuit breaker Interface Module
Module

=
Motor
Module
G_D213_EN_00108

M
3

Active Line Connection Module-2 with Active Interface Module and


Active Line Module >800 A

Siemens D 21.3 · 2022 7/7


© Siemens 2022

SINAMICS S120 Cabinet Modules-2


Air-cooled units

■ Technical specifications
General technical specifications
Electrical specifications
Line voltages 380 ... 480 V 3 AC, ±10 % (-15 % <1 min)
Line system configurations Grounded TN/TT systems or non-grounded IT systems
Line frequency 47 ... 63 Hz
Output frequency 1)
• Control mode Servo 0 ... 550 Hz
• Control mode Vector 0 ... 550 Hz
• Control mode V/f 0 ... 550 Hz
Efficiency
• Motor Module > 98.5 %
Overvoltage category III acc. to EN 61800-5-1
Control method Vector/Servo control with and without encoder or V/f control
Fixed speeds 15 fixed speeds plus 1 minimum speed, parameterizable (in the default setting, 3 fixed setpoints plus 1 minimum
speed are selectable using terminal strip/PROFIBUS/PROFINET)
Skippable speed ranges 4, parameterizable
Setpoint resolution 0.001 rpm digital (14 bits + sign)
12 bits analog
Braking operation With Active Line Connection Modules, four-quadrant operation as standard (energy recovery).
Braking by means of a Motor Module.
Cabinet system
Cabinet system Rittal TS 8, doors with double-bit key, three-section base plates for cable entry
Paint finish RAL 7035 (indoor requirements)
Mechanical specifications
Degree of protection IP20 (higher degrees of protection up to IP54 optionally available)
Protection class I acc. to EN 61800-5-1
Touch protection EN 50274/DGUV regulation 3 when used as intended
Cooling method Forced air cooling AF according to EN 60146
Ambient conditions Storage 2) Transport 2) Operation

7 Ambient temperature -25 ... +55 °C (-13 ... 131 °F) -25 ... +70 °C (-13 ... +158 °F)
from -40 °C (-40 °F) for 24 hours
0 ... +40 °C (32 ... 104 °F)
to +50 °C (122 °F) see derating data
Relative humidity 5 ... 95 % 5 ... 95 % at 40 °C (104 °F) 5 ... 95 %
(condensation not permissible) Class 1K4 acc. to IEC 60721-3-1 Class 2K3 acc. to IEC 60721-3-2 Class 3K3 acc. to IEC 60721-3-3
(1997) (1997) (2002)
Environmental class/harmful chemical Class 1C2 Class 2C2 Class 3C2
substances acc. to EN 60721-3-1 (1997) acc. to EN 60721-3-2 (1997) acc. to EN 60721-3-3 (2002)
Organic/biological influences Class 1B1 Class 2B1 Class 3B1
acc. to EN 60721-3-1 (1997) acc. to EN 60721-3-2 (1997) acc. to EN 60721-3-3 (2002)
Mechanically active substances Class 1S1 Class 2S1 Class 3S1
acc. to EN 60721-3-1 (1997) acc. to EN 60721-3-2 (1997) acc. to EN 60721-3-3 (2002)
Degree of pollution 2 acc. to IEC/EN 61800-5-1
Installation altitude 2000 m (6562 ft) above sea level without derating, >2000 m (6562 ft) see Characteristic curves/derating data
Mechanical strength Storage 2) Transport 2) Operation
Vibratory load Class 1M2 Class 2M2 –
acc. to EN 60721-3-1 (1997) acc. to EN 60721-3-2 (1997)
• Deflection 1.5 mm (0.06 in) at 5 ... 9 Hz 3.1 (0.12 in) mm at 5 ... 9 Hz 0.075 mm (0.003 in) at 10 ... 58 Hz
• Acceleration 5 m/s² (16.4 ft/s²) at >9 ... 200 Hz 10 m/s² (32.8 ft/s²) at >9 ... 200 Hz 9.8 m/s² (32.2 ft/s²) at >58 ... 200 Hz
Shock load Class 1M2 Class 2M2 Class 3M1
acc. to EN 60721-3-1 (1997) acc. to EN 60721-3-2 (1997) acc. to EN 60721-3-3 (2002)
• Acceleration 40 m/s² (131 ft/s²) at 22 ms 100 m/s² (328 ft/s²) at 11 ms Test values acc. to EN 60068-2-27
test Ea: 5 g, 30 ms, 3 shocks
Compliance with standards
Conformances/certificates of suitability, CE (EMC Directive 2014/30/EU, Low voltage Directive 2014/35/EU, and Machinery Directive 2006/42/EC for
according to Functional safety)
RCM, RoHS II, UKCA
Radio interference suppression SINAMICS converter systems are not designed for connection to the public grid (first environment). Radio
interference suppression is compliant with the EMC product standard for variable-speed drives EN 61800-3,
"second environment" (industrial line supplies). EMC disturbances can occur when connected to the public grid.
However, if additional measures are taken (e.g.  line filter), it can also be operated in the "first environment".

Deviations from the specified class are underlined.


1) 2)
Higher output frequencies available on request. In transport packaging.

7/8 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Cabinet Modules-2


Air-cooled units

■ Characteristic curves
Derating data The following table specifies the permissible output currents as
a function of the installation altitude and ambient temperature for
SINAMICS S120 Cabinet Modules-2 and the associated system the various degrees of protection. (The permissible
components are rated for an ambient temperature of 40 °C and compensation between installation altitude and the ambient
installation altitudes up to 1000 m above sea level. temperatures < 40 °C – air intake temperature at the entry to the
At ambient temperatures > 40 °C, the output current must be Cabinet Module – has been taken into account in the specified
reduced. Ambient temperatures above 50 °C are not values.)
permissible. The values apply under the precondition that it is guaranteed
At installation altitudes > 1000 m above sea level, it must be that the cooling air, as specified in the technical data, flows
taken into account that the air pressure, and therefore air through the units as a result of the cabinet arrangement.
density, decreases as the height increases. As an additional measure for installation altitudes from 2000 m
As a consequence, the cooling efficiency and the insulation up to 5000 m, an isolating transformer is required in order to
capacity of the air also decrease. reduce transient overvoltages according to EN 60664-1.
Due to the reduced cooling efficiency, it is necessary to both For additional information, please refer to the SINAMICS Low
reduce the ambient temperature and lower heat loss in the Voltage Engineering Manual.
Cabinet Module by reducing the output current, whereby
ambient temperatures lower than 40 °C may be offset to
compensate.
Current derating factors for Cabinet Modules-2 as a function of the ambient/air intake temperature, the installation altitude and the
degree of protection
Degree of Installation Current derating factor (as a percentage of the rated current)
protection altitude above for an ambient/air intake temperature of
sea level
m (ft) 15 °C (59 °F) 20 °C (68 °F) 25 °C (77 °F) 30 °C (86 °F) 35 °C (95 °F) 40 °C (104 °F) 45 °C (113 °F) 50 °C (122 °F)
IP20, IP21, 0 ... 1000 83 % 69 %
IP23, IP43 (0 ... 3281)
1001 ... 1500 98 % 81 % 67 %
(3284 ... 4921)
1501 ... 2000 93 % 78 % 65 %
(4925 ... 6562)
2001 ... 2500 100 % 96 %
(6565 ... 8202)
2501 ... 3000 99 %
(8205 ... 9843)
3001 ... 3500
7
(9846 ... 11483)
3501 ... 4000 96 %
(11486 ... 13123)
4001 ... 4500 97 %
(13127 ... 14764)
4501 ... 5000 98 %
(14767 ... 16404)

Degree of Installation Current derating factor (as a percentage of the rated current)
protection altitude above for an ambient/air intake temperature of
sea level
m (ft) 10 °C (50 °F) 15 °C (59 °F) 20 °C (68 °F) 25 °C (77 °F) 30 °C (86 °F) 35 °C (95 °F) 40 °C (104 °F) 45 °C (113 °F) 50 °C (122 °F)
IP54 0 ... 1000 83 % 69 % 54 %
(0 ... 3281)
1001 ... 1500 98 % 81 % 67 % 52 %
(3284 ... 4921)
1501 ... 2000 93 % 78 % 65 % 50 %
(4925 ... 6562)
2001 ... 2500 100 % 96 %
(6565 ... 8202)
2501 ... 3000 99 %
(8205 ... 9843)
3001 ... 3500
(9846 ... 11483)
3501 ... 4000 96 %
(11486 ... 13123)
4001 ... 4500 97 %
(13127 ... 14764)
4501 ... 5000 98 %
(14767 ... 16404)

Siemens D 21.3 · 2022 7/9


© Siemens 2022

SINAMICS S120 Cabinet Modules-2


Air-cooled units

■ Characteristic curves
Current derating for SINAMICS S120 Motor Modules in factor of the output current must be taken into account.
chassis-2 format as a function of the pulse frequency This derating factor must be applied to the currents specified
in the technical specifications.
To reduce motor noise or to increase output frequency, the pulse For additional information, please refer to the SINAMICS Low
frequency can be increased relative to the factory setting Voltage Engineering Manual.
(2.5 kHz). When the pulse frequency is increased, the derating
Derating factor of the output current as a function of the pulse frequency
Motor Modules in Type rating Output current Derating factor
chassis-2 format at 400 V at 2.5 kHz at pulse frequency
6SL3721-... kW A 4 kHz 5 kHz 7.5 kHz 8 kHz
380 ... 480 V 3 AC
1TE36-6BE0 315 655 78 % 67 % 48 % 45 %
1TE37-4BE0 355 740 78 % 67 % 48 % 45 %
1TE38-1BE0 400 810 78 % 67 % 48 % 45 %
1TE38-8BE0 450 910 78 % 67 % 48 % 45 %
1TE41-0BE0 500 975 78 % 67 % 48 % 45 %
1TE41-1BE0 560 1075 78 % 67 % 48 % 45 %
1TE41-2BE0 630 1200 78 % 67 % 48 % 45 %
1TE41-3BE0 710 1325 78 % 67 % 48 % 45 %
1TE41-5BE0 800 1495 78 % 67 % 48 % 45 %

Maximum output frequencies achieved by increasing the pulse


frequency
The adjustable pulse frequencies – and therefore the output
frequencies that can be achieved with the factory-set current
controller clock cycles – are listed below.
Current controller clock cycle Adjustable pulse frequency Max. achievable output frequency fA
TI fp
V/f mode Vector mode Servo mode
400 s 2.5 kHz 208 Hz 208 Hz –
5.0 kHz 416 Hz 300 Hz –

7 7.5 kHz 550 Hz 1) 300 Hz –

1)
Higher frequencies on request. For more information, see
https://support.industry.siemens.com/cs/document/104020669

7/10 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Cabinet Modules-2


Air-cooled units

■ Characteristic curves
Overload capability The base-load current IS6 is based on a duty cycle of 200 %
for 6 s.
SINAMICS S120 Cabinet Modules-2 have an overload reserve,
e.g. to handle breakaway torques. If larger surge loads occur,
this must be taken into account in the configuration. For drives Converter current
with overload requirements, the appropriate base-load current 6s Short-time current 200 %
must therefore be used as a basis for the required load.
2 × IS6

G_D213_EN_00120
Permissible overload assumes that the converter is operated at
its base-load current before and after the overload occurs,
based on a duty cycle duration of 300 s (low overload, high
overload) or 60 s (duty cycle S6).
Another precondition is that the Motor Modules are operated at
their factory-set pulse frequency at output frequencies >10 Hz. Rated current Irated O (continuous)

For temporary, periodic duty cycles with high variations of load Irated O
within the duty cycle, the relevant sections of the SINAMICS Low
Voltage Engineering Manual must be observed. 0.7 × Irated O
60 s
Motor Modules in chassis-2 format Base-load current IS6 for duty cycle S6

Motor Modules with power units in chassis-2 format can be


configured on the basis of different base-load currents. t
The base-load current for low overload IL is based on a duty
cycle of 110 % for 60 s. Duty cycle S6 with initial load with a duty cycle duration of 60 s
Active Line Connection Modules-2
Converter current
The base-load current IL is based on a load cycle of 115 %
for 60 s with a duty cycle duration of 300 s.
Short-time current 110 %

Rated current Irated O (continuous) IDC


1.1 × IL Base-load current IL Short-time current 115 %
for low overload
Irated O Rated current (continuous)
1.15 × IL_DC Base-load current IL_DC
IL
G_D213_EN_00118

for low overload


60 s
300 s
In_DC
7
IL_DC

G_D213_EN_00126
60 s
t
300 s

Low overload
t
The base-load current for a high overload IH is based on a duty
cycle of 150 % for 60 s.
Low overload

Converter current The duty cycle with maximum current Imax_DC is based on a duty
cycle of 150 % for 5 s with a duty cycle duration of 300 s.
Short-time current 150 %

IDC
1.5 × IH Rated current Irated O (continuous) 5s
Base-load current IH I max_DC
for high overload Maximum current
Irated O = 1.5 × I L_DC

IH
G_D213_EN_00119

60 s
300 s Rated current (continuous)
I n_DC
t Base-load current I L_DC for low overload
I L_DC
G_D213_EN_00127

High overload 300 s

Duty cycle with maximum current

Siemens D 21.3 · 2022 7/11


© Siemens 2022

SINAMICS S120 Cabinet Modules-2


Air-cooled units
Active Line Connection Modules-2

■ Overview ■ Design
Active Line Connection Modules-2 always include an Active
Interface Module in chassis-2 format, which contains the
associated Clean Power Filter and pre-charging circuit. The line
filter that is included ensures compliance with the EMC
requirements for the "second environment".
Active Line Connection Modules-2 are available for installing
the Motor Modules to the right (article number "...RE0") and for
installing the Motor Modules to the left (article number "...LE0").
The Line Connection Module with the line connection is installed
directly next to the Active Interface Module.
Depending on the input current, the following versions are
available:
•  800 A: Main circuit breaker with fuse switch disconnector
• > 800 A: Circuit breaker, type 3WL, with option L25 as
draw-out circuit breaker
Parallel connection for power increase

Active Line Connection Modules-2 comprise a Line Connection The power rating can be increased by connecting Active Line
Module, an Active Interface Module in chassis-2 format and an Connection Modules-2 in parallel. You must observe the
Active Line Module in chassis-2 format installed in a cabinet following rules:
system. They can supply motoring energy to the DC link and • Up to 6 identical Active Line Connection Modules-2 can be
return regenerative energy to the line supply. connected in parallel.
The Active Line Connection Module-2 contains the line-side • Option M88 must be ordered so that the infeed can be
infeed via main switch and circuit breaker and pre-charging realized at the common DC link.
circuit. It connects the line-side supply network and the Active • A common Control Unit is required whenever the modules are
Line Module in chassis-2 format. It is equipped as standard with connected in parallel. For more than 4 power units, these must
a radio interference suppression filter according to EN 61800-3 be distributed as symmetrically as possible between at least
Category C3. two DRIVE-CLiQ ports (e.g. 3 x 2 Active Line Connection
Modules-2 in series or at least 2 x 3 Active Line Connection
Active Line Connection Modules-2 generate a controlled DC Modules-2 in series).
voltage that is kept consistent regardless of fluctuations in the
line voltage (the line voltage must lie within the permissible • The parallel connection must be supplied from a common
tolerances). infeed point, i.e. the modules cannot be operated on different
line supplies
In the factory setting, the DC voltage is regulated to 1.5 times the
• A derating factor of 5 % must be taken into consideration,
7 rms value of the nominal voltage of the distribution system.
regardless of the number of modules connected in parallel.
Active Line Connection Modules draw a virtually sinusoidal • The main contactors or circuit breakers of the respective Line
current from the supply system and cause virtually no line Connection Modules must close together and simultaneously.
harmonics. Monitoring is performed via the -X50 terminals of the
Active Line Connection Modules are suitable for connection to respective Line Connection Module
supply systems grounded at the neutral point (TN, TT) and For additional information, please refer to the SINAMICS Low
non-grounded (IT) supply systems. The following voltages and Voltage Engineering Manual.
currents are available:
Line voltage Rated infeed/regenerative Rated power
feedback current
380 ... 480 V 3 AC 560 ... 1405 A 355 ... 900 kW

7/12 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Cabinet Modules-2


Air-cooled units
Active Line Connection Modules-2

■ Selection and ordering data ■ Integration


Rated power Rated DC link current Active Line Connection
at 400 V IN Module-2 Cabinet Module
kW A Article No.
Line voltage 380 ... 480 V 3 AC
(DC link voltage 510 ... 720 V DC)
355 630 6SL3731-7TE35-6RE0
355 630 6SL3731-7TE35-6LE0
Line Connection Module
400 710 6SL3731-7TE36-4RE0
400 710 6SL3731-7TE36-4LE0 Main contactor Pre-charging
450 835 6SL3731-7TE37-5RE0 contactor
450 835 6SL3731-7TE37-5LE0 5
500 940 6SL3731-7TE38-4RE0 Pre-charging
6
resistors
500 940 6SL3731-7TE38-4LE0
Line
560 1010 6SL3731-7TE38-8RE0 contactor
560 1010 6SL3731-7TE38-8LE0
L1 L1
630 1100 6SL3731-7TE41-0RE0 L2 L2
630 1100 6SL3731-7TE41-0LE0 L3 L3

710 1245 6SL3731-7TE41-2RE0


B A
710 1245 6SL3731-7TE41-2LE0
800 1415 6SL3731-7TE41-3RE0
800 1415 6SL3731-7TE41-3LE0
G_D213_EN_00125
900 1575 6SL3731-7TE41-4RE0
900 1575 6SL3731-7TE41-4LE0 5
6
Connection between an Active Line Module
Chassis-2 and Line Connection Module
A
established in the factory
B

Connection example of an Active Line Connection Module-2


(Line Connection Module)

Siemens D 21.3 · 2022 7/13


© Siemens 2022

SINAMICS S120 Cabinet Modules-2


Air-cooled units
Active Line Connection Modules-2

■ Integration
Cabinet Modules Cabinet Modules

DC busbar

X500 X400 X401 X402

2
Active Interface LED
Active Line Module

DRIVE-CLiQ socket

DRIVE-CLiQ socket

DRIVE-CLiQ socket

DRIVE-CLiQ socket
Module Chassis-2 READY
Chassis-2
-X41
Voltage 1 EP +24 V
Sensing 2
EP M1
Module 3 +Temp (motor)
-X609
4 -Temp (motor)
PE
5 NC
1 P24 6
1 NC

LEDs
2 READY
P24
3 -X42 DC LINK
2 M -G10 1 2 X530 1
4 P24L PWR ON
M 2
TxXW 1 P24L -X46
3 5 L1 3
L 6 M 1
M 2 4 M BR Output+
pe 1~ BR Output- 2
N 7
4 N -X47 FB Input+ 3
8 4
12 3 5 PE A 1 VL_R FB Input-
9 2 5
M NC
10 3 NC 6
6 B HS_R
11 4 M
5 -X49
12 NC 1
6 NC LAMPPWR
13 2
M
14 -X9 NC 3
PE NC 4
5 VL1
NC 5
VL2 6
NC NC
HS1 Internal
6 HS2 power supply
U1 -X1 -X2 U2 P24 V =
7 V1
W1
V2
W2
M
=
PE PE
U1 -X1
~ DCP
V1 DCN
W1 =
PE IPD Card
-F50 -X51 Fans
1
2 L1
Connection between an Active Interface Module
L2
3 Chassis-2 and Active Line Module Chassis-2
L3
established in the factory 4
4 PE
3 123 4 5 6 7
6
-X100

5
Connection between an Active Line Module
6
Chassis-2 and Line Connection Module establis-
-F24

A hed in the factory


B
380 - 480 V 3 AC
Auxiliary power supply:
230 V AC
24 V DC

G_D213_EN_00124a

Connection example of an Active Line Connection Module-2 (Active Interface Module in chassis-2 format and Active Line Module in chassis-2 format)

7/14 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Cabinet Modules-2


Air-cooled units
Active Line Connection Modules-2

■ Technical specifications
Line voltage 380 ... 480 V 3 AC Active Line Connection Modules-2
6SL3731-7TE35-6RE01) 6SL3731-7TE36-4RE01) 6SL3731-7TE37-5RE01) 6SL3731-7TE38-4RE01)
1) 1) 1)
6SL3731-7TE35- 6LE0 6SL3731-7TE36-4LE0 6SL3731-7TE37-5LE0 6SL3731-7TE38-4LE01)
Rated power
• At IN DC (50 Hz 400 V) kW 355 400 450 500
• At IL DC (50 Hz 400 V) kW 300 350 400 450
• At IN DC (60 Hz 460 V) hp 500 550 650 700
• At IL DC (60 Hz 460 V) hp 400 500 550 650
DC link current
• Rated current IN DC A 630 710 835 940
• Base-load current IL DC 2) A 571 649 760 854
• Maximum current Imax DC A 857 974 1140 1281
Infeed/regenerative feedback
current
• Rated current IN I A 560 635 745 840
• Maximum current Imax I A 773 878 1028 1155
Pulse frequency kHz 4 4 4 4
Current demand
• 24 V DC auxiliary power supply A 1.5 1.5 1.5 1.5
• 230 V 1 AC A 4.1 4.1 4.1 4.1
DC link capacitance
• Active Line Module F 16450 16450 18800 18800
• Drive line-up, max. F 250000 250000 250000 250000
Power loss, max. 3)
• at 50 Hz 400 V kW 12.14 12.65 16.38 17.32
• at 60 Hz 460 V kW 12.14 12.65 16.38 17.32
Cooling air requirement m3/s (ft3/s) 1.3 (45.9) 1.3 (45.9) 1.3 (45.9) 1.3 (45.9)
4)
Sound pressure level LpA dB 75/75 75/75 75/75 75/75
(1 m) at 50/60 Hz
Line supply connection 4 x M12 4 x M12 10 x M12 10 x M12
L1, L2, L3
• Conductor cross-section, max. (IEC) mm2 8 × 240 8 × 240 8 × 240 8 × 240
PE/GND connection PE bar PE bar PE bar PE bar
• Busbar cross-section mm2 600 600 600 600 7
• Conductor cross-section, max. (IEC) mm2 240 240 240 240
Cable length, max. 5) m (ft) 3900/5850 (12795/19193) 3900/5850 (12795/19193) 3900/5850 (12795/19193) 3900/5850 (12795/19193)
Shielded/unshielded
Degree of protection IP20 IP20 IP20 IP20
(standard version)
Dimensions
(standard version)
• Width mm (in) 1600 (63.0) 1600 (63.0) 1600 (63.0) 1600 (63.0)
• Height mm (in) 2200 (86.6) 2200 (86.6) 2200 (86.6) 2200 (86.6)
• Depth mm (in) 600 (23.6) 600 (23.6) 600 (23.6) 600 (23.6)
Weight, approx. kg (lb) 989 (2180) 994 (2191) 1191 (2626) 1192 (2628)
(standard version)
Frame size
• Line Connection Module HL HL JL JL
• Active Interface Module FS2 FS2 FS4 FS4
• Active Line Module FS2 FS2 FS2+ FS2+
Rated short-circuit current kA 50 50 100 100
according to IEC
Minimum short-circuit current 6) kA 18 18 2 2

1) 5)
Article number "...RE0": Motor Modules installed to the right, "...LE0": Total of all motor cables and DC link. Longer cable lengths for specific
Motor Modules installed to the left. configurations are available on request. For additional information, please
2)
The base-load current IL DC is based on a duty cycle of 115 % for 60 s or refer to the SINAMICS Low Voltage Engineering Manual.
Imax DC for 5 s with a duty cycle duration of 300 s. The cable lengths are valid for use in IT systems. When used in TN
3)
systems, the cable lengths are shortened to 30 % of the specified value.
The specified power loss represents the maximum value at 100 % When used in the TN system and when operating with increased pulse
utilization. The value is lower under normal operating conditions. frequency, you will obtain the permitted cable lengths upon request.
4) 6)
Total sound pressure level of Active Interface Module and Active Line Current required for reliably triggering protective devices.
Module.

Siemens D 21.3 · 2022 7/15


© Siemens 2022

SINAMICS S120 Cabinet Modules-2


Air-cooled units
Active Line Connection Modules-2

■ Technical specifications
Line voltage 380 ... 480 V 3 AC Active Line Connection Modules-2
6SL3731- 6SL3731- 6SL3731- 6SL3731- 6SL3731-
7TE38-8RE01) 7TE41-0RE01) 7TE41-2RE01) 7TE41-3RE01) 7TE41-4RE01)
6SL3731- 6SL3731- 6SL3731- 6SL3731- 6SL3731-
7TE38-8LE01) 7TE41-0LE01) 7TE41-2LE01) 7TE41-3LE01) 7TE41-4LE01)
Rated power
• At IN DC (50 Hz 400 V) kW 560 630 710 800 900
• At IL DC (50 Hz 400 V) kW 500 560 630 710 800
• At IN DC (60 Hz 460 V) hp 800 900 1050 1150 1300
• At IL DC (60 Hz 460 V) hp 700 800 900 1000 1150
DC link current
• Rated current IN DC A 1010 1100 1245 1415 1575
• Base-load current IL DC 2) A 915 1004 1131 1287 1431
• Maximum current Imax DC A 1373 1506 1697 1931 2147
Infeed/regenerative feedback
current
• Rated current IN I A 900 985 1110 1260 1405
• Maximum current Imax I A 1238 1358 1530 1740 1935
Pulse frequency kHz 4 4 4 4 4
Current demand
• 24 V DC auxiliary power supply A 1.5 1.5 1.5 1.5 1.5
• 230 V 1 AC A 4.1 4.1 4.1 4.1 4.1
DC link capacitance
• Active Line Module F 25900 25900 25900 40800 40800
• Drive line-up, max. F 250000 250000 250000 250000 250000
Power loss, max. 3)
• at 50 Hz 400 V kW 17.70 18.55 19.62 23.9 26.5
• at 60 Hz 460 V kW 17.70 18.55 19.62 23.9 26.5
Cooling air requirement m3/s (ft3/s) 1.7 (60.0) 1.7 (60.0) 1.7 (60.0) 1.7 (60.0) 1.7 (60.0)
4)
Sound pressure level LpA dB 75/75 75/75 75/75 75/75 7575
(1 m) at 50/60 Hz
Line supply connection 10 x M12 10 x M12 10 x M12 10 x M12 10 x M12
L1, L2, L3

7 • Conductor cross-section, max. (IEC) mm2


PE/GND connection
8 × 240
PE bar
8 × 240
PE bar
8 × 240
PE bar
8 × 240
PE bar
8 × 240
PE bar
• Busbar cross-section mm2 600 600 600 600 600
• Conductor cross-section, max. (IEC) mm2 240 240 240 240 240
Cable length, max. 5) m (ft) 3900/5850 3900/5850 3900/5850 3900/5850 3900/5850
Shielded/unshielded (12795/19193) (12795/19193) (12795/19193) (12795/19193) (12795/19193)
Degree of protection IP20 IP20 IP20 IP20 IP20
(standard version)
Dimensions
(standard version)
• Width mm (in) 1800 (70.9) 1800 (70.9) 1800 (70.9) 1800 (70.9) 1800 (70.9)
• Height mm (in) 2200 (86.6) 2200 (86.6) 2200 (86.6) 2200 (86.6) 2200 (86.6)
• Depth mm (in) 600 (23.6) 600 (23.6) 600 (23.6) 600 (23.6) 600 (23.6)
Weight, approx. kg (lb) 1264 (2787) 1345 (2965) 1406 (3100) 1509 (3326) 1529 (3371)
(standard version)
Frame size
• Line Connection Module JL JL JL JL JL
• Active Interface Module FS4 FS4 FS4 FS4 FS4
• Active Line Module FS4 FS4 FS4 FS4+ FS4+
Rated short-circuit current kA 100 100 100 100 100
according to IEC
Minimum short-circuit current 6) kA 2 2.5 2.5 3.2 3.2

1) Article number "...RE0": Motor Modules installed to the right, "...LE0": 5) Total of all motor cables and DC link. Longer cable lengths for specific
Motor Modules installed to the left. configurations are available on request. For additional information, please
2) The base-load current IL DC is based on a duty cycle of 115 % for 60 s or refer to the SINAMICS Low Voltage Engineering Manual.
Imax DC for 5 s with a duty cycle duration of 300 s. The cable lengths are valid for use in IT systems. When used in TN
3)
systems, the cable lengths are shortened to 30 % of the specified value.
The specified power loss represents the maximum value at 100 % When used in the TN system and when operating with increased pulse
utilization. The value is lower under normal operating conditions. frequency, you will obtain the permitted cable lengths upon request.
4) Total sound pressure level of Active Interface Module and Active Line 6) Current required for reliably triggering protective devices.
Module.

7/16 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Cabinet Modules-2


Air-cooled units
Motor Modules in chassis-2 format

■ Overview Parallel connection for power increase


The power rating can be increased by connecting Motor
Modules in chassis-2 format in parallel. You must observe the
following rules:
• Up to 6 identical Motor Modules can be connected in parallel.
• A common Control Unit is required whenever the modules are
connected in parallel. For more than 4 power units, these must
be distributed as symmetrically as possible between at least
two DRIVE-CLiQ ports (e.g. 3 x 2 Motor Modules in chassis-2
format in series or at least 2 x 3 Motor Modules in chassis-2
format in series).
• The motor supply cables must have the same length
(symmetrical design).
• Power must be supplied to the Motor Modules from a common
DC busbar.
• A derating factor of 5 % must be taken into consideration,
regardless of the number of modules connected in parallel.
• For motors with multi-winding systems, please observe the
notes in the Low Voltage Engineering Manual.
Motor Modules in chassis-2 format are available in the power • For motors with a single-winding system, the length of the
range from 315 kW to 630 kW. supply lines must be kept to a minimum. The respective cable
lengths are listed in the following tables.
Line voltage DC link voltage Type rating
380 ... 480 V 3 AC 510 ... 720 V DC 315 ... 800 kW Motor Module in PN INeff Minimum cable
chassis-2 format length
By connecting in parallel up to six Motor Modules, which are 6SL3721-... kW A m (ft)
operated on one Control Unit and supply one motor, it is possible
to increase the available shaft power (taking into account the 1TE36-6BE0 315 655 13 (42.7)
derating factors according to the SINAMICS Low Voltage 1TE37-4BE0 355 740 12 (39.4)
Engineering Manual). 1TE38-1BE0 400 810 10 (32.8)

■ Design 1TE38-8BE0
1TE41-0BE0
450
500
910
975
9 (29.5)
8 (26.2)
Motor Modules in chassis-2 format contain the following 1TE41-1BE0 560 1075 8 (26.2)
components as standard:
1TE41-2BE0 630 1200 8 (26.2)
• Retaining device for the DC busbar, including the interface to
the DC connections of the Motor Module (the necessary DC 1TE41-3BE0 710 1325 8 (26.2)
busbar must be provided separately as option M80 to M87.) 1TE41-5BE0 800 1495 8 (26.2) 7
• Lateral connection busbars for the motor cable are nickel- Note:
plated. No mixed operation possible!
• DC fuses It is only possible to connect identical power units in parallel if all
• Cable retaining bar for the power cables power units have the same hardware version. Mixed operation
between Motor Modules in chassis format
• DRIVE-CLiQ interface (3 DRIVE-CLiQ sockets), (Article No. 6SL3720-xxxxx–xAA3) and Motor Modules in
without Control Unit chassis-2 format (Article No. 6SL3721-xxxxx–xBE0)
• Auxiliary power supply, including auxiliary voltage module is not possible.
and cables for looping through to the next Cabinet Module
• Nickel-plated PE busbar (60 x 10 mm), including jumper for ■ Selection and ordering data
looping through to the next Cabinet Module
• EMC-compliant design thanks to additional shielding Type rating at 400 V Rated output current Motor Modules in
IN chassis-2 format
measures and appropriately routed cables
kW A Article No.
Line voltage 380 ... 480 V 3 AC
(DC link voltage 510 ... 720 V DC)
315 655 6SL3721-1TE36-6BE0
355 740 6SL3721-1TE37-4BE0
400 810 6SL3721-1TE38-1BE0
450 910 6SL3721-1TE38-8BE0
500 975 6SL3721-1TE41-0BE0
560 1075 6SL3721-1TE41-1BE0
630 1200 6SL3721-1TE41-2BE0
710 1325 6SL3721-1TE41-3BE0
800 1495 6SL3721-1TE41-5BE0

Siemens D 21.3 · 2022 7/17


© Siemens 2022

SINAMICS S120 Cabinet Modules-2


Air-cooled units
Motor Modules in chassis-2 format

■ Integration
Motor Modules are controlled by the CU320-2 DP or already be installed. If the Control Unit is to be mounted
CU320-2 PN Control Unit. Communication between the Control externally, the DRIVE-CLiQ cable will not be included in the
Unit and Modules is established via a DRIVE-CLiQ connection. scope of supply and must be configured on site.
If the Control Unit is integrated in the same cabinet as an option For additional information, please refer to the SINAMICS Low
with order code K90 or K95, these communication cables will Voltage Engineering Manual.

Cabinet Module-2
DC busbar

X400 X401 X402

Motor Module

DRIVE-CLiQ socket 0

DRIVE-CLiQ socket 2
DRIVE-CLiQ socket 1
-F1
-F2 Chassis-2
DCP
DCN
-X9
VL1 =
VL2
=
NC
-X2
HS1 U2
HS2 =
V2 M
P24 V ~ W2 3~
M
PE
-X51 Internal power supply
Fan
L1
Fan power supply terminal L2
L3
PE
-X41 READY
LEDs

1 EP +24 V
1) DC LINK
2 EP M1
M PWR ON
7 2)
3
4
+Temp (Motor)
-Temp (Motor)
5 NC
-F50 6 NC IPD Card
-X42
1 P24L
to 2 -X47
Line Connection Module P24L 1
3 M VL_R
4 M 2
M 3
HS_R
-X46 M 4
1 NC 5
BR Output+ 6
2 BR Output- NC
3
FB Input+ -X49
4 FB Input- 1
5 LAMPPWR
NC M 2
6 NC NC 3
1 2 3 4 5 6 NC 4
NC 5
-X100

NC 6

Auxiliary power supply:


-F24

380 - 480 V 2 AC
or 500 - 690 V 2 AC
230 V AC

24 V DC

G_D213_EN_00121a

1) Required for Safety Integrated.


2) Connection of temperature sensor for motors without DRIVE-CLiQ interface.

Connection example of a Motor Module in chassis-2 format

7/18 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Cabinet Modules-2


Air-cooled units
Motor Modules in chassis-2 format

■ Technical specifications
Line voltage 380 ... 480 V 3 AC Motor Modules in chassis-2 format
DC link voltage 510 ... 720 V DC
6SL3721-1TE36-6BE0 6SL3721-1TE37-4BE0 6SL3721-1TE38-1BE0 6SL3721-1TE38-8BE0
Type rating
• At IL (50 Hz 400 V) 1) kW 315 355 400 450
• At IH (50 Hz 400 V) 1) kW 280 315 355 400
• At IL (60 Hz 460 V) 2) hp 500 600 650 700
• At IH (60 Hz 460 V) 2) hp 450 500 550 650
Output current
• Rated current IN O A 655 740 810 910
• Base-load current IL 3) A 620 700 770 865
• Base-load current IH4) A 555 620 675 760
• Maximum current Imax O A 917 1036 1134 1274
DC link current
• Rated current IN DC 785 890 975 1090
Current demand
• 24 V DC auxiliary power supply A 1.3 1.3 1.3 1.3
• 400 V AC A 1.8 1.8 1.8 1.8
DC link capacitance F 16450 16450 18800 18800
Pulse frequency 5)
• Rated frequency kHz 2.5 2.5 2.5 2.5
• Pulse frequency, max.
- Without current derating kHz 2.5 2.5 2.5 2.5
- With current derating kHz 8 8 8 8
Power loss, max. 6)
• At 50 Hz 400 V kW 6.7 7.0 7.8 8.8
• At 60 Hz 460 V kW 6.9 7.3 8.1 9.1
Cooling air requirement m3/s (ft3/s) 0.64 (22.6) 0.64 (22.6) 0.64 (22.6) 0.64 (22.6)
Sound pressure level LpA dB 53 ... 72 53 ... 72 53 ... 72 53 ... 72
(1 m) at 50/60 Hz
Motor connection 4 x M12 4 x M12 4 x M12 4 x M12
U2, V2, W2
• Conductor cross-section, max. (IEC) mm2 4 x 240 4 x 240 4 x 240 4 x 240
Cable length, max. 7) 7
• Shielded m (ft) 300 (984) 300 (984) 100 (328) 10) 100 (328) 10)
• Unshielded m (ft) 450 (1476) 450 (1476) 100 (328) 10) 100 (328) 10)
PE/GND connection PE bar PE bar PE bar PE bar
• Busbar cross-section mm2 600 600 600 600
• Conductor cross-section, max. (IEC) mm2 240 240 240 240
Degree of protection IP20 IP20 IP20 IP20
Dimensions
• Width 8) mm (in) 600 (23.6) 600 (23.6) 600 (23.6) 600 (23.6)
• Height 9) mm (in) 2200 (86.6) 2200 (86.6) 2200 (86.6) 2200 (86.6)
• Depth mm (in) 600 (23.6) 600 (23.6) 600 (23.6) 600 (23.6)
Weight, approx. kg (lb) 257 (567) 265 (584) 270 (595) 270 (595)
Frame size FS2 FS2 FS2+ FS2+
Rated short-circuit current ICC kA 100 100 100 100
according to IEC

1) 6)
Rated power of a typical 6-pole standard asynchronous motor based on The specified power loss represents the maximum value at 100 %
IL or IH for 400 V 3 AC 50 Hz. utilization. The value is lower under normal operating conditions.
2) 7)
Rated power of a typical 6-pole standard asynchronous motor based on Total of all motor cables. Longer cable lengths for specific configurations
IL or IH for 460 V 3 AC 60 Hz. are available on request. For additional information, please refer to the
3)
The base-load current for a low overload IL is based on a duty cycle of SINAMICS Low Voltage Engineering Manual.
8)
110 % for 60 s with a duty cycle duration of 300 s. With option L07 (dv/dt filter compact plus VPL), L08 (motor reactor),
4)
The base-load current for a high overload IH is based on a duty cycle of L10 (dv/dt filter plus VPL), L34 (circuit breaker at the output):
150 % for 60 s with a duty cycle duration of 300 s. Additional cabinet 600 mm (23.62 in) wide.
9)
5)
Information regarding the correlation between the pulse frequency and The cabinet height increases by 250 mm (9.84 in) with degree of protection
max. output current/output frequency is provided in the SINAMICS Low IP21, and by 400 mm (15.7 in) with degrees of protection
Voltage Engineering Manual. IP23, IP43 and IP54.
10)
Longer cables available on request.

Siemens D 21.3 · 2022 7/19


© Siemens 2022

SINAMICS S120 Cabinet Modules-2


Air-cooled units
Motor Modules in chassis-2 format

■ Technical specifications
Line voltage 380 ... 480 V 3 AC Motor Modules in chassis-2 format
DC link voltage 510 ... 720 V DC
6SL3721- 6SL3721- 6SL3721- 6SL3721- 6SL3721-
1TE41-0BE0 1TE41-1BE0 1TE41-2BE0 1TE41-3BE0 1TE41-5BE0
Type rating
• At IL (50 Hz 400 V) 1) kW 500 560 630 710 800
• At IH (50 Hz 400 V) 1) kW 450 500 560 630 710
• At IL (60 Hz 460 V) 2) hp 750 850 950 1050 1200
• At IH (60 Hz 460 V) 2) hp 650 750 850 900 1050
Output current
• Rated current IN O A 975 1075 1200 1325 1495
• Base-load current IL 3) A 910 1000 1145 1260 1420
• Base-load current IH4) A 800 890 1000 1100 1240
• Maximum current Imax O A 1365 1505 1710 1855 2093
DC link current
• Rated current IN DC 1170 1290 1440 1590 1795
Current demand
• 24 V DC auxiliary power supply A 1.3 1.3 1.3 1.3 1.3
• 400 V AC A 1.8 1.8 1.8 1.8 1.8
DC link capacitance F 25900 25900 25900 40800 40800
5)
Pulse frequency
• Rated frequency kHz 2.5 2.5 2.5 2.5 2.5
• Pulse frequency, max.
- Without current derating kHz 2.5 2.5 2.5 2.5 2.5
- With current derating kHz 8 8 8 8 8
Power loss, max. 6)
• At 50 Hz 400 V kW 9.2 9.8 11.0 12.1 13.7
• At 60 Hz 460 V kW 9.5 10.1 11.4 13.2 14.8
Cooling air requirement m3/s (ft3/s) 0.64 (22.6) 0.64 (22.6) 0.64 (22.6) 0.64 (22.6) 0.64 (22.6)
Sound pressure level LpA dB 53 ... 72 53 ... 72 53 ... 72 53 ... 72 53 ... 72
(1 m) at 50/60 Hz
Motor connection M12 screws M12 screws M12 screws M12 screws M12 screws
U2, V2, W2
7 • Conductor cross-section, max. (IEC) mm2
Cable length, max. 7)
6 × 240 6 × 240 6 × 240 6 × 240 6 × 240

• Shielded m (ft) 300 (984) 300 (984) 300 (984) 100 (328) 10) 100 (328) 10)
• Unshielded m (ft) 450 (1476) 450 (1476) 450 (1476) 100 (328) 10) 100 (328) 10)
PE/GND connection PE bar PE bar PE bar PE bar PE bar
• Busbar cross-section mm2 600 600 600 600 600
• Conductor cross-section, max. (IEC) mm2 240 240 240 240 240
Degree of protection IP20 IP20 IP20 IP20 IP20
Dimensions
• Width 8) mm (in) 600 (23.6) 600 (23.6) 600 (23.6) 600 (23.6) 600 (23.6)
• Height 9) mm (in) 2200 (86.6) 2200 (86.6) 2200 (86.6) 2200 (86.6) 2200 (86.6)
• Depth mm (in) 600 (23.6) 600 (23.6) 600 (23.6) 600 (23.6) 600 (23.6)
Weight, approx. kg (lb) 305 (672) 305 (672) 305 (672) 316 (697) 316 (697)
Frame size FS4 FS4 FS4 FS4+ FS4+
Rated short-circuit current ICC kA 100 100 100 100 100
according to IEC

1) 6)
Rated power of a typical 6-pole standard asynchronous motor based on The specified power loss represents the maximum value at 100 %
IL or IH for 400 V 3 AC 50 Hz. utilization. The value is lower under normal operating conditions.
2) 7)
Rated power of a typical 6-pole standard asynchronous motor based on Total of all motor cables. Longer cable lengths for specific configurations
IL or IH for 460 V 3 AC 60 Hz. are available on request. For additional information, please refer to the
3)
The base-load current for a low overload IL is based on a duty cycle of SINAMICS Low Voltage Engineering Manual.
8)
110 % for 60 s with a duty cycle duration of 300 s. With option L07 (dv/dt filter compact plus VPL), L08 (motor reactor),
4)
The base-load current for a high overload IH is based on a duty cycle of L10 (dv/dt filter plus VPL), L34 (circuit breaker at the output):
150 % for 60 s with a duty cycle duration of 300 s. Additional cabinet 600 mm (23.62 in) wide.
9)
5)
Information regarding the correlation between the pulse frequency and The cabinet height increases by 250 mm (9.84 in) with degree of protection
max. output current/output frequency is provided in the SINAMICS Low IP21, and by 400 mm (15.7 in) with degrees of protection
Voltage Engineering Manual. IP23, IP43 and IP54.
10)
Longer cables available on request.

7/20 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Cabinet Modules-2

Options

■ Overview
A detailed description of all options is to be found in chapter 6 The following options are available for the Active Line
as well as in the Industry Mall. Connection Modules-2 and Motor Modules in chassis-2 format.
Order code Option designation Active Line Connection Motor Module
Module-2 in chassis-2 format
Electrical options
G33 1) CBE20 Communication Board  
G51 1 x TM150 temperature sensor evaluation unit  
G52 2 x TM150 temperature sensor evaluation units  
G53 3 x TM150 temperature sensor evaluation units  –
G54 4 x TM150 temperature sensor evaluation units  –
G60 TM31 Terminal Module  
G61 Additional TM31 Terminal Module  
1)
G62 TB30 Terminal Board  
K01 ... K05 Safety license Extended Functions for 1 to 5 axes – 
K08 1) AOP30 Advanced Operator Panel installed in the cabinet door  
K46 SMC10 Sensor Module Cabinet-Mounted – 
K48 SMC20 Sensor Module Cabinet-Mounted – 
K50 SMC30 Sensor Module Cabinet-Mounted – 
K51 VSM10 Voltage Sensing Module – 
K52 Second SMC30 Sensor Module Cabinet-Mounted – 
K76 Auxiliary power generation (in the Line Connection Module)  –
K82 Terminal module for activating "Safe Torque Off" and "Safe Stop 1" – 
K87 TM54F Terminal Module – 
K88 Safe Brake Adapter SBA, 230 V AC – 
K90 CU320-2 DP Control Unit  
K94 1) Performance expansion for CU320-2 Control Unit  
K95 CU320-2 PN Control Unit  
L07 dv/dt filter plus Voltage Peak Limiter – 
L08 Motor reactor –  7
L10 dv/dt filter plus Voltage Peak Limiter – 
L20 Use in an IT system  
L21 Surge suppression  –
L25 Withdrawable circuit breaker in place of a fixed-mounted circuit breaker  –
L34 Output-side circuit breaker (motor-driven) – –
L40 Line filter monitoring  –
L41 Current transformer upstream of main circuit breaker  –
L45 EMERGENCY OFF pushbutton installed in the cabinet door  –
L50 Cabinet lighting with service socket  –
L55 Cabinet anti-condensation heating  
L87 Insulation monitoring  –
N52 DC link fuses  –
P10 Measuring instrument for line supply values; mounted in cabinet door (includes  –
L41)
P11 Measuring instrument for line supply values like option P10, with PROFIBUS con-  –
nection
Y09 Special paint finish for cabinet  –
Y11 Factory-assembled transport units  –

 Option can be ordered for this Cabinet Module-2


– Option cannot be ordered for this Cabinet Module-2

1) Only in conjunction with option K90 or K95.

Siemens D 21.3 · 2022 7/21


© Siemens 2022

SINAMICS S120 Cabinet Modules-2

Options

■ Overview
Order code Option designation Active Line Connection Motor Module
Module-2 in chassis-2 format
Mechanical options
M06 Base 100 mm high, RAL 7022  
M07 Cable compartment 200 mm high, RAL 7035  
M21 Degree of protection IP21  
M23, M43 Degree of protection IP23, degree of protection IP43 (each contains M60)  
M26 Side panel mounted to the right  
M27 Side panel mounted to the left  
M54 Degree of protection IP54 (includes M60)  
M60 Additional touch protection – 
M70 EMC shield bus (already included in the Cabinet Module)  
M80 ... M87 DC busbar system  
M88 DC busbar system for line-side Cabinet Modules  –
M89 Extended motor connection panel – 
M90 Crane transport assembly (top-mounted)  
M91 Marking of all control cable wire ends (including customer-specific cables)  

 Option can be ordered for this Cabinet Module-2


– Option cannot be ordered for this Cabinet Module-2

The following options specified in chapter "Cabinet Modules"


and in the Industry Mall also apply for the Active Line Connection
Modules-2 and Motor Modules in chassis-2 format for:
• Production flowcharts (B43 to B45)
• Packaging options (B55 to B57)
• Documentation (D00, D01, D02, D14, D56, D58, D60, D72,
D76, D77, D78, D80, D84, D91, D93, D94, D99)
• Labels (T58, T60, T80, T83, T85, T91, Y31 to Y33)
• Converter acceptance (F03, F71, F72, F74, F75, F76, F77,
7 F97)
The criteria for selecting various options (selection matrix) listed
in Section "Cabinet Modules" in the D 21.3 catalog must also be
observed.

■ Options
The options described below are new for SINAMICS S120
Cabinet Modules-2.
L20
Use in an IT system
When used in IT systems, an isolating transformer is connected
in the fan power supply.
M89
Extended motor connection panel
With the selection of option M89, the motor cables are not
directly connected to the Motor Module in chassis-2 format,
but to prefabricated copper busbars in the Cabinet Module.
The copper busbars make the contact to the Motor Module
and can be easily separated by removing screws.
As a consequence, the Motor Module can be simply
disconnected from the motor cables. This simplifies installation
and cable connection. For example, this means that the Motor
Module can be removed from the cabinet to make it simpler to
connect the motor cables.

7/22 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Cabinet Modules-2


Supplementary system components
Mounting aid for Motor Modules/Active Line Modules in chassis-2 format

■ Overview ■ Selection and ordering data


Description Article No.
Mounting aid 6SL3766-1CH02-0AA0
for Motor Modules/Active Line Modules
in chassis-2 format
G_D213_XX_00151

The mounting device is used to install and remove power units


(Active Line Modules, Motor Modules) of the chassis-2 format in
or from a Rittal TS8 or Rittal VX25 control cabinet.
The mounting height resulting from the use of cabinet bases
or cable marshalling space from Rittal is supported.
The mounting device is placed in front of the power unit and
secured to the upper control cabinet profile.
The adjusting tube and guide rails can be used to adjust the
mounting device to the respective control cabinet and
installation height.
After loosening the mechanical and electrical connections, the
power unit is attached to the crossbar and rolled out of the
control cabinet on the guide rails.
The power unit is then lifted with the rope winch and lowered
to the floor after removing the guide rails.
7

Siemens D 21.3 · 2022 7/23


© Siemens 2022

SINAMICS S120 Cabinet Modules-2

Order-specific integration engineering

■ Overview ■ Selection and ordering data


Just like the SINAMICS S120 buit-in units, SINAMICS S120 The following engineering services can be ordered depending
Cabinet Modules-2 form a modular drive system that consists of on the number of drives/axes included in an order:
various intelligent Drive Objects such as Line Modules, Motor
Modules, Control Units, Sensor Modules, etc. Integration engineering Article No.
For 1 drive 6SL3780-0AA00-0AA0
As a consequence, SINAMICS S120 Cabinet Modules-2 are (also parallel connection)
supplied with documentation that only includes and describes including the associated Line Modules,
the individual Cabinet Modules Sensor Modules, Terminal Modules, etc.
(circuit diagram, layout diagram, terminal diagram and For up to 3 drives 6SL3780-0AC00-0AA0
additional Operating Instructions). (also parallel connection)
including the associated Line Modules,
By selecting option Y11, individual Cabinet Modules are Sensor Modules, Terminal Modules, etc.
assembled at the factory as interconnected units for transport
and are then supplied as such. For up to 5 drives 6SL3780-0AE00-0AA0
(also parallel connection)
Detailed documentation showing features such as the signal including the associated Line Modules,
connections between the individual Cabinet Modules that make Sensor Modules, Terminal Modules, etc.
up the order, is not included in the normal scope of supply. For up to 10 drives 6SL3780-0AJ00-0AA0
(also parallel connection)
In this case, only a collection of the individual documents are including the associated Line Modules,
shipped with the converter. Sensor Modules, Terminal Modules, etc.

If the documentation is to include a complete representation of Engineering services for larger drive systems are also available
the equipment supplied, the equipment and documentation on request.
must be additionally processed. This can be ordered with the
integration engineering.
Integration engineering includes the following:
• Checking the combinations and options ordered, in relation
to the device configurations
• Defining how the individual drive objects are to be connected
and coordinated, with the customer if required.
• Checking the performance of the ordered CompactFlash card
• Installing the required DRIVE-CLiQ cables within the
transport units.
Cables between the transport units are connected at one end
• Higher-level documentation of the scope of supply (layout
diagram, circuit diagram, terminal diagram, dimension
7 drawing, spare parts list).
• Summary of the individual documents included in a shipment,
in conjunction with a delivery address separate from the
equipment
• Customer-specific system and location designations,
coordinated with the customer

7/24 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S120 Cabinet Modules-2

Order-specific integration engineering

■ Options
The table below lists the options available for order-specific
integration engineering (for details, see Description of the
options):
Available options Order code
Customer documentation (circuit diagram, layout diagram, D01
dimension drawing, spare parts list) in EPLAN format.
Customer documentation (circuit diagram, terminal diagram, D02
layout diagram) in DXF format
Preliminary version of customer documentation in PDF for- D14
mat
Documentation in English/French D58
Documentation in English/Spanish D60
Documentation in English/Italian D80
Documentation in English/Chinese D91
Documentation in English/Portuguese (Brazil) D93
Documentation in English/Russian D94

When ordering the order-specific integration engineering,


the required documentation options must always be ordered
together with the order engineering (not with the individual
Cabinet Modules).
Ordering the documentation options for the particular
Cabinet Modules is only required if equipment is ordered
without integration engineering.
Option selection matrix of the order-specific integration
engineering
Certain options are mutually exclusive.
 Possible combination
– Combination not possible

D01 D02 D14 D58 D60 D80 D91 D93 D94 7


D01  –      
D02        
D14 –       
D58    – – – – –
D60    – – – – –
D80    – – – – –
D91    – – – – –
D93    – – – – –
D94    – – – – –

Siemens D 21.3 · 2022 7/25


© Siemens 2022

SINAMICS S120 Cabinet Modules-2

Customized solutions

■ More information
Customized solutions
In addition to the wide range of possibilities of configuring drives
with the available modules and options to address specific plant
and system requirements, for special applications we also offer
customized applications to fully comply with the actual
requirements.
These are based on the standard SINAMICS S120 Cabinet
Modules-2 and are supplied as completely wired units that are
ready to be connected up.
Simply contact us if you are interested or require these or any
other applications.
Notes regarding the addresses of contact persons are provided
in the section "Services and Documentation" under "Partners at
Siemens".
Sonntagskogelbahn Austria

7/26 Siemens D 21.3 · 2022


8
© Siemens 2022

SINAMICS S150 Converter Cabinet Units

8/2 SINAMICS S150


converter cabinet units
8/2 Overview
8/2 Benefits
8/3 Application
8/3 Selection and ordering data
8/4 Design
8/6 Function
8/8 Technical specifications
8/15 Characteristic curves
8/18 Options

8/22 Description of options

8/36 Line-side components –


recommended fuses

8/37 Cable cross-sections and connections

8/39 Supplementary system components


8/39 Mounting device for power blocks

Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S150 Converter Cabinet Units

Converter cabinet units

■ Overview ■ Benefits
The self-commutating, pulsed infeed/regenerative unit uses
IGBT technology and is equipped with a Clean Power Filter.
This combination guarantees extremely line-friendly behavior
which is characterized by the following:
• Negligible line harmonics as a result of the Clean Power
Filter (<<1 %)
• The stringent limit values of IEEE 519 (2014) are typically
complied with. The total harmonic distortion factors of the
current THD(I) and voltage THD(U) are typically in the range
of approx. 3 % for rated current. THD(I) is calculated
according to IEE 519 (2014) and THD(U) according to
IEC 61000-2-4 (2002).
• Regenerative feedback (four-quadrant operation)
• Tolerant to fluctuations in the line voltage
• Operation on weak line supplies
• Reactive power compensation is possible
(inductive or capacitive)
SINAMICS S150 converter cabinet units are particularly suitable • High drive dynamic performance
for all variable-speed single-axis drives with high performance In addition, factors have been considered to ensure easy
requirements, i.e. drives with: handling of the drive from the planning and design phase
• High dynamic requirements through to operation. These factors include:
• Frequent braking cycles and high braking energy levels • Compact, modular design with an optimum degree of service
• Four-quadrant operation friendliness
SINAMICS S150 offers high-performance speed control with • Straightforward configuring and commissioning thanks to
excellent accuracy and a high dynamic response. assistance provided by the SIZER for Siemens Drives
(integrated in the TIA Selection Tool), Startdrive and STARTER
The following voltages and power ratings are available: tools
Line voltage Type rating
• Simple installation, as it is ready to be connected up
• Fast, menu-prompted commissioning with no complex
380 ... 480 V 3 AC 110 ... 800 kW
parameterization
500 ... 690 V 3 AC 75 ... 1200 kW
• Clear and convenient drive monitoring/diagnostics,
Degrees of protection are IP20 (standard) and optionally IP21, commissioning and operation via a user-friendly graphical
IP23, IP43 and IP54. operator panel with measured values displayed in plain text or
in a quasi-analog bar display.
Line and motor-side components as well as additional
monitoring devices can be installed in the converter cabinet • SINAMICS as an integral part of Totally Integrated Automation
units. (TIA). The TIA concept offers an optimized range of products
for automation and drive technology. This concept is
A wide range of electrical and mechanical components enable characterized by configuration, communication, and data
the drive system to be optimized individually to suit customer management that are consistent throughout the product
8 requirements. range. SINAMICS is fully integrated in the TIA concept.
Separate S7/PCS7 blocks and faceplates for WinCC are
available.
• Integration in SIMATIC H systems via Y-Link
• SINAMICS Drive Control Chart (SINAMICS DCC)
SINAMICS DCC is an additional tool for the easy configuration
of process-oriented functions for SINAMICS. The block library
encompasses a large selection of closed-loop, arithmetic and
logic blocks, as well as a more comprehensive range of open-
loop and closed-loop control functions. The user-friendly DCC
editor enables easy graphics-based configuration, allows
control loop structures to be clearly represented and provides
a high degree of reusability of charts that have already been
created. SINAMICS DCC is an add-on to the commissioning
tools SINAMICS Startdrive or STARTER.

8/2 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S150 Converter Cabinet Units

Converter cabinet units

■ Application ■ Selection and ordering data


SINAMICS S150 is especially suitable for use in all applications Type rating Rated output SINAMICS S150
that place the highest demands on process operations with at 400 V current IN converter cabinet unit
dynamic, reproducible processes. These include, for example: or 690 V
• Test stands kW A Article No.
• Centrifuges Line voltage 380 ... 480 V 3 AC
• Elevators and cranes 110 210 6SL3710-7LE32-1AA3
• Cross cutters and shears 132 260 6SL3710-7LE32-6AA3
• Conveyor belts with a high power demand and energy 160 310 6SL3710-7LE33-1AA3
recovery 200 380 6SL3710-7LE33-8AA3
• Presses 250 490 6SL3710-7LE35-0AA3
• Cable winches 315 605 6SL3710-7LE36-1AA3
400 745 6SL3710-7LE37-5AA3
450 840 6SL3710-7LE38-4AA3
560 985 6SL3710-7LE41-0AA3
710 1260 6SL3710-7LE41-2AA3
800 1405 6SL3710-7LE41-4AA3
Line voltage 500 ... 690 V 3 AC
75 85 6SL3710-7LG28-5AA3
90 100 6SL3710-7LG31-0AA3
110 120 6SL3710-7LG31-2AA3
132 150 6SL3710-7LG31-5AA3
160 175 6SL3710-7LG31-8AA3
200 215 6SL3710-7LG32-2AA3
250 260 6SL3710-7LG32-6AA3
315 330 6SL3710-7LG33-3AA3
400 410 6SL3710-7LG34-1AA3
450 465 6SL3710-7LG34-7AA3
560 575 6SL3710-7LG35-8AA3
710 735 6SL3710-7LG37-4AA3
800 810 6SL3710-7LG38-1AA3
900 910 6SL3710-7LG38-8AA3
1000 1025 6SL3710-7LG41-0AA3
1200 1270 6SL3710-7LG41-3AA3

Siemens D 21.3 · 2022 8/3


© Siemens 2022

SINAMICS S150 Converter Cabinet Units

Converter cabinet units

■ Design
The SINAMICS S150 converter cabinet units are characterized
by their compact, modular and service-friendly design.

-X1
Line connection PE
1

2 Main switch1)

3
Fuses 1)

Main contactor 2)

4
Active Interface Module
5
with Clean Power Filter

6 AC
Active Line Module

7 DC

8
G_D213_EN_00001d

DC Link

DC

Motor Module
1 Active Interface Module with Clean Power Filter and AC
main contactor
2 Active Line Module

G_D213_EN_00002b
-X2
PE
3 Motor Module Motor connection

4 Main switch with fuses (option L26)

5 Control Unit

6 Terminal Module TM31 (option G60)

7 Line connection (-X1)

8 Motor connection (-X2)


Option

8
1) Main switch with fuses only with
output current < 800 A
Standard version
2) Main contactor with output current < 800 A
Option
or circuit-breaker with output current > 800 A
available as standard

Design example of a SINAMICS S150 converter cabinet unit Basic design of a SINAMICS S150 converter cabinet unit with
a number of version-specific options

8/4 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S150 Converter Cabinet Units

Converter cabinet units

■ Design
Coated modules Degrees of protection
The following devices are equipped as standard with coated The EN 60529 standard covers the protection of electrical
modules: equipment by means of housings, covers or equivalent,
• Chassis format units and includes:
• Control Units • Protection of persons against accidental contact with live or
moving parts within the housing and protection of the
• Sensor Modules equipment against the ingress of solid foreign bodies
• Terminal Modules (touch protection and protection against ingress of solid
• Advanced Operator Panel (AOP30) foreign bodies)
• Protection of the equipment against the ingress of water
The coating on the modules protects the sensitive (water protection)
SMD components against corrosive gases, chemically active
dust and moisture. • Abbreviations for the internationally agreed degrees
of protection
Nickel-plated busbars
The degrees of protection are specified by abbreviations
All of the copper busbars used in the converter cabinets are comprising the code letters IP and two digits.
nickel-plated in order to achieve the best possible immunity to
environmental effects. Furthermore, there is no need to clean the Degree of First digit Second digit
contacts on the customer terminals as otherwise required for protection (Touch protection (Protection of equipment
and protection against against the ingress of water)
bare copper connections. foreign bodies)
Note: IP20 Protected against No water protection
With some options, parts of the copper busbars cannot be (Standard) solid foreign bodies
nickel-plated for technical reasons. with a diameter  12.5 mm
IP21 Protected against Protected against drip water
(Option M21) solid foreign bodies Vertically falling water drops
with a diameter  12.5 mm shall not have a harmful
effect.
IP23 Protected against Protected against spray
(Option M23) solid foreign bodies water
with a diameter  12.5 mm Water sprayed on both sides
of the vertical at an angle of
up to 60° shall not have a
harmful effect.
IP43 Protected against Protected against spray
(Option M43) solid foreign bodies water
with a diameter  1 mm Water sprayed on both sides
of the vertical at an angle of
up to 60° shall not have a
harmful effect.
IP54 Dust protected Protected against splash
(Option M54) Ingress of dust is not totally water
prevented, but dust must Water splashing onto the
not be allowed to enter in
such quantities that the
enclosure from any direction
shall not have a harmful
8
functioning or safety of the effect.
equipment is impaired.

Siemens D 21.3 · 2022 8/5


© Siemens 2022

SINAMICS S150 Converter Cabinet Units

Converter cabinet units

■ Function
AOP30 Advanced Operator Panel Only 6 motor parameters have to be entered: Power, speed,
current, cos , voltage and frequency of the motor.
This information can be found on the motor rating plate,
and must be entered in the screens on the display by following
1 6 a short, menu-assisted procedure. The motor cooling method
2 must also be specified.
3
Motor data
7 Back
p0304 MOT.U_rated 400.0 V
4 8 p0305 MOT. I_rated 405.0 A

G_D011_EN_00048a
p0307 MOT.P_rated 235.0 kW
p0308 MOT.CosPhi_rated 0.870
9
5 Help Change OK

The next screen contains the parameter values that are used
G_D011_EN_00331
to automatically optimize the control.

1 LED On (green) 6 Display Basic commissioning


Back
2 LED Alarm (yellow) 7 Function keys F1 to F5 p0700 Default BI S/G150 TM 31
3 LED Fault (red) p1000 Default DI n_set TM 31 AIO
8 Selection of local/remote command

G_D011_EN_00049a
p1080 Minimum speed 0.000 rpm
4 Numeric keypad priority
p1082 Maximum speed 1500.000 rpm
5 Keypad disable 9 Keypad for drive control
Help Change Further

An Advanced Operator Panel (AOP30) is installed in the cabinet During operation, the display shows current data, such as
door of the converter for operation, monitoring and setpoints and actual values as absolute values or it is possible
commissioning tasks. to parameterize up to 3 process variables as a quasi-analog
bar display.
The user is guided by interactive menus through the drive
commissioning screens. When the drive is commissioned for the
Operation 12:25:30
first time, only 6 motor parameters (which can be found on the Nact
Nset 1450.00 rpm 1450.0 rpm
motor rating plate) have to be entered on the AOP30. Fout 48.50 Hz Vout 385.3 V
The closed-loop control is then optimized automatically to adapt

G_D011_EN_00011c
M 2700 Nm Imot 748 A
the converter to the motor. Pact 410 kW
The AOP30's two-stage safety concept prevents unintentional Nact:
or unauthorized changes to settings. Operation of the drive from 1450 rpm
the operator panel can be disabled by the keyboard lock and so
that only parameter values and process variables can be
displayed on the operator panel. The OFF key is factory-set to Operation 12:25:30
"active", but can be deactivated by the customer. A password Nset 1465.50 rpm Pact 410 kW
Fout 48.50 Hz Vout 385.3 V
8 can be used to prevent the unauthorized changing of converter

G_D011_EN_00012b
Imot
parameters. 748 A 0% 50 100%
German, English, French, Italian, Spanish and Chinese are Nact
1465 rpm 0% 50 100%
stored on the CU320-2 Control Unit CompactFlash card as
operator panel languages. The desired language must be
downloaded to the AOP30 prior to commissioning. In addition to Any alarms that occur are signaled by flashing of the yellow
these standard operator panel languages, Russian can also be ALARM LED, faults by the red FAULT LED, which is then lit.
retro-installed. Further languages are available on request. There is also an indication of the cause displayed in plain text
Examples of plain-text displays during various phases of on the display's status line (with counter/remedial measures).
operation are shown below.
(3 : Vector) Current fault in
The first commissioning is performed via the operator panel.
G_D011_EN_00050a

Service / Commissioning F 07901 Motor overspeed


Drive commissioning
Device commissioning
AOP settings Help Alt Back Ack.
G_D213_EN_00003a

AOP diagnostics
Motor overspeed
Help Back Select
Fault val = 000000007 00000007 (hex)
Cause:
G_D011_EN_00051a

The maximum permissible positive or


negative speed has been exceeded.
The maximum permissible positive speed
is calculated as follows:
Back

8/6 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S150 Converter Cabinet Units

Converter cabinet units

■ Function
Communication with higher-level controller and customer Open-loop and closed-loop control functions
terminal strip
SINAMICS S150 has a high-dynamic vector control with speed
A PROFIBUS or PROFINET interface on the Control Unit and current control – with and without speed actual value
CU320-2 is provided as standard as the customer control feedback.
interface.
Software and protective functions
This interface can be used to connect the system to the
higher-level controller using analog and digital signals, The software functions available as standard are described
or to connect additional units. below:

The inputs and outputs available as standard can be optionally


expanded by up to two Terminal Modules TM31 (refer to the
description of options, option G60 or G61). To simplify
configuration and commissioning of the drive, the TM31 Terminal
Module can be preset to a variety of factory settings.
For additional information, please refer to the SINAMICS Low
Voltage Engineering Manual.
Software and protective functions Description
Setpoint input The setpoint can be specified both internally and externally; internally as a fixed setpoint, motorized potentiometer setpoint
or jog setpoint, externally via the communications interface or an analog input. The internal fixed setpoint and the
motorized potentiometer setpoint can be switched or adjusted via control commands from any interface.
Motor identification The automatic motor identification function makes commissioning faster and easier and optimizes closed-loop control
of the drive.
Ramp-function generator A user-friendly ramp-function generator with separately adjustable ramp-up and ramp-down times, together with
adjustable rounding times in the lower and upper speed ranges, allows the drive to be smoothly accelerated and braked.
This results in a good speed control response and plays its role in reducing the stress on the mechanical system.
The down ramps can be parameterized separately for quick stop.
Vdc max controller The Vdc max controller automatically prevents overvoltages in the DC link, if the set down ramp is too short, for example.
This may also extend the set ramp-down time.
Kinetic buffering (KIP) For brief line supply failures, the kinetic energy of the rotating drive is used to buffer the DC link and therefore prevents
fault trips. The converter remains operational as long as the drive can provide regenerative energy as a result of its motion
and the DC link voltage does not drop below the shutdown threshold. When the line supply recovers within this time, the
drive is again bumplessly accelerated up to its setpoint speed.
Automatic restart The automatic restart switches the drive on again when the power is restored after a power failure, and ramps up to the
current speed setpoint.
Flying restart The flying restart function allows the converter to be switched to a motor that is still turning. With the voltage sensing
capability provided by the optional VSM10, the flying restart time for large induction motors can be significantly reduced
because the motor does not need to be de-magnetized.
Technology controller The technology controller function module allows simple control functions to be implemented, e.g. level control or
volumetric flow control and complex tension controls. The existing D component can act both on the system deviation as
well as on the actual value (factory setting). The P, I, and D components are set separately.
Free function blocks (FFB) Using the freely programmable function blocks, it is easy to implement logic and arithmetic functions for controlling the
SINAMICS drive. The blocks can be programmed at the operator panel or the commissioning tools SINAMICS Startdrive
or STARTER. 8
SINAMICS Drive Control Chart SINAMICS DCC is an additional tool for the easy configuration of technological functions for SINAMICS. The block library
(SINAMICS DCC) contains a large selection of control, arithmetic and logic blocks as well as extensive open-loop and closed-loop control
functions. The user-friendly DCC editor enables easy graphics-based configuration, allows control loop structures to be
clearly represented and provides a high degree of reusability of charts that have already been created. SINAMICS DCC is
an add-on to the commissioning tools SINAMICS Startdrive or STARTER ( Tools and Engineering).
SINAMICS Technology The SINAMICS TEC are configurable functions or Siemens technologies that can be added to extend firmware functions.
Extensions (SINAMICS TEC) These extensions are designed to allow implementation of highly complex, application-specific tasks for various sectors -
such as storage and retrieval machines.
Additional information about Technology Extensions (TEC) is provided in the "Technology functions" section.
I2t sensing for motor protection A motor model stored in the converter software calculates the motor temperature based on the current speed and load.
More exact sensing of the temperature, which also takes into account the influence of the ambient temperature, is possible
by means of direct temperature sensing using Pt1000/KTY84 sensors in the motor winding.
Motor temperature evaluation Motor protection by evaluating a KTY84, PTC, Pt100 or Pt1000 temperature sensor. When a KTY84 temperature sensor
is connected, the limit values can be set for alarm or shutdown. When a PTC thermistor is connected, the system reaction
to triggering of the thermistor (alarm or trip) can be defined.
Motor blocking protection A blocked motor is detected and protected against thermal overloading by a fault trip.
Brake control "Simple brake control" for control of holding brakes:
The holding brake is used to secure drives against unwanted motion when deactivated.
"Extended brake control" function module for complex brake control, e.g. for motor holding brakes and operational brakes:
When braking with a feedback signal, the brake control reacts to the feedback signal contacts of the brake.
Essential service mode Special converter operating mode that increases the availability of the drive system, e.g. in the event of a fire.
Write protection Write protection to prevent unintentional changing of the setting parameters (without password function).
Know-how protection Know-how protection for encrypting stored data, e.g. to protect configuration know-how, and to protect against changes
and duplication (with password function).
Web server The web server provides information about the drive unit via its web pages. The web server is accessed using an internet
browser via unsecured (http) or secured transmission (https).

Siemens D 21.3 · 2022 8/7


© Siemens 2022

SINAMICS S150 Converter Cabinet Units

Converter cabinet units

■ Function
Power unit protection
Power unit protection Description
Ground fault monitoring at the A ground fault at the output is detected by a total current monitor and results in shutdown in grounded systems.
output
Electronic short-circuit A short-circuit at the output (e.g. at the converter output terminals, in the motor cable or in the motor terminal box)
protection at the output is detected and the converter shuts down with a "fault".
Thermal overload protection An alarm is issued first when the overtemperature threshold responds. If the temperature continues to rise, the unit either
shuts down or independently adjusts the pulse frequency or output current so that thermal load is reduced. Once the
cause of the fault has been eliminated (e.g. cooling has been improved), the original operating values are automatically
resumed.

■ Technical specifications
The most important directives and standards are listed below.
These are used as basis for the SINAMICS S150 converter
cabinet units and they must be carefully observed to achieve an
EMC-compliant configuration that is safe both functionally and
in operation.
European directives
2014/35/EU Low-voltage Directive:
Directive of the European Parliament and Council of February 26, 2014 for the harmonization of the laws of the member
states relating to the provision of electrical equipment designed for use within certain voltage limits on the market (recast)
2014/30/EU EMC Directive:
Directive of the European Parliament and Council of February 26, 2014 on the harmonization of the laws of the member
states relating to electromagnetic compatibility (recast)
2006/42/EC Machinery Directive:
Directive of the European Parliament and Council of May 17, 2006, on machinery and amending Directive 95/16/EC
(recast).
2011/65/EU RoHS II Directive:
Directive of the European Parliament and of the Council of 8 June 2011 on the restriction of the use of certain hazardous
substances in electrical and electronic equipment (recast)
European standards
EN ISO 3744 Acoustics – Determination of the sound power level and sound energy level for noise sources that result from sound
pressure measurements – envelope surface procedure of the accuracy class 2 for a largely free sound field over a reflect-
ing plane
EN ISO 13849-1 Safety of machinery – Safety-related parts of control systems;
Part 1: General principles for design (EN ISO 13849-1: 2006)
EN 60146-1-1 Semiconductor converters – General requirements and line-commutated converters
Part 1-1: Specification of basic requirements
EN 60204-1 Safety of machinery – Electrical equipment of machines;
8 EN 60529
Part 1: General requirements
Degrees of protection provided by enclosures (IP code)
IEC 61508-1 Functional safety of electrical/electronic/programmable electronic safety-related systems
Part 1: General requirements
IEC 61508-2 Functional safety of electrical/electronic/programmable electronic safety-related systems
Part 2: Requirements for electrical/electronic/programmable electronic safety-related systems
IEC 61508-3 Functional safety of electrical/electronic/programmable electronic safety-related systems
Part 3: Software requirements
EN 61800-2 Adjustable speed electrical power drive systems
Part 2: General requirements – rating specifications for low voltage adjustable frequency AC power drive systems
EN 61800-3 Adjustable speed electrical power drive systems
Part 3: EMC requirements and specific test methods
EN 61800-5-1 Adjustable speed electrical power drive systems
Part 5: Safety requirements
Main section 1: Electrical and thermal requirements
EN 61800-5-2 Adjustable speed electrical power drive systems
Part 5-2: Safety requirements – Functional safety (IEC 61800-5-2: 2007)

8/8 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S150 Converter Cabinet Units

Converter cabinet units

■ Technical specifications
General technical specifications
Electrical specifications
Line voltages 380 … 480 V 3 AC, ±10 % (-15 % <1 min)
500 … 690 V 3 AC, ±10 % (-15 % <1 min)
Line supply types Grounded TN/TT systems and non-grounded IT systems
Line frequency 47 ... 63 Hz
Output frequency 1) 0 ... 550 Hz
Line power factor Adjustable (factory-set to cos  = 1)
Efficiency >96 %
Overvoltage category III acc. to EN 61800-5-1
Control method Vector control with and without encoder or V/f control
Fixed speeds 15 fixed speeds plus 1 minimum speed, parameterizable (in the default setting, 3 fixed setpoints plus 1 minimum
speed are selectable using terminal strip/PROFIBUS/PROFINET)
Skippable speed ranges 4, parameterizable
Setpoint resolution 0.001 rpm digital (14 bits + sign)
12 bits analog
Braking operation Four-quadrant operation is possible as standard
(optional via a braking unit if braking is required when power fails)
Mechanical specifications
Degree of protection IP20 (higher degrees of protection up to IP54 optional)
Protection class I acc. to EN 61800-5-1
Touch protection EN 50274/DGUV regulation 3 when used as intended
Cabinet system Rittal TS 8, doors with double-bit key, three-section base plates for cable entry
Paint finish RAL 7035 (indoor requirements)
Cooling method Forced air cooling AF according to EN 60146
Ambient conditions Storage 2) Transport 2) Operation
Ambient temperature -25 ... +55 °C (-13 ... +131 °F) -25 ... +70 °C (-13 ... +158 °F) 0 ... 40 °C (32 ... +104 °F)
from -40 °C (-40 °F) for 24 hours to +50 °C (+122 °F), see derating data
Relative humidity 5 ... 95% 5 ... 95 % at 40 °C (104 °F) 5 ... 95 %
(condensation not permissible) Class 1K4 acc. to IEC 60721-3-1 Class 2K3 acc. to IEC 60721-3-2 Class 3K3 acc. to IEC 60721-3-3
(1997) (1997) (2002)
Environmental class/ Class 1C2 acc. to IEC 60721-3-1 Class 2C2 acc. to IEC 60721-3-2 Class 3C2 acc. to IEC 60721-3-3
harmful chemical substances (1997) (1997) (2002)
Organic/biological influences Class 1B1 acc. to IEC 60721-3-1 Class 2B1 acc. to IEC 60721-3-2 Class 3B1 acc. to IEC 60721-3-3
(1997) (1997) (2002)
Mechanically active substances Class 1S1 acc. to IEC 60721-3-1 Class 2S1 acc. to IEC 60721-3-2 Class 3S1 acc. to IEC 60721-3-3

Degree of pollution
(1997)
2 acc. to EN 61800-5-1
(1997) (2002) 8
Installation altitude Up to 2000 m (6562 ft) above sea level without derating;
> 2000 m (6562 ft) see derating data
Mechanical stability Storage 2) Transport 2) Operation
Vibratory load Class 1M2 acc. to IEC 60721-3-1 Class 2M2 acc. to IEC 60721-3-2 –
(1997) (1997)
• Deflection 1.5 mm (0.06 in) at 5 ... 9 Hz 3.1 mm (0.12 in) at 5 ... 9 Hz 0.075 mm (0.003 in) at 10 ... 58 Hz
• Acceleration 5 m/s² (16.4 ft/s²) at >9 ... 200 Hz 10 m/s² (32.8 ft/s²) at 9 ... 200 Hz 9.8 m/s2 (32.2 ft/s²) at 58 ... 200 Hz
Shock load Class 1M2 acc. to IEC 60721-3-1 Class 2M2 acc. to IEC 60721-3-2 Class 3M4 acc. to IEC 60721-3-3
(1997) (1997) (2002)
• Acceleration 40 m/s² (131 ft/s²) at 22 ms 100 m/s² (328 ft/s²) at 11 ms 100 m/s2 (328 ft/s²) at 11 ms
Compliance with standards
Conformances/certificates of CE (EMC Directive 2014/30/EU and Machinery Directive 2006/42/EC for functional safety)
suitability, according to RCM, RoHS II, UKCA
Radio interference suppression SINAMICS converter systems are not designed for connection to the public grid (first environment). Radio interference
suppression is compliant with the EMC product standard for variable-speed drives EN 61800-3, "Second environment"
(industrial networks). EMC disturbances can occur when connected to the public grid. However, if additional measures
are taken (e.g.  line filter), it can also be operated in the "first environment".

Deviations from the specified classes are underlined.

1) 2)
Please note: In transport packaging.
- The correlation between the maximum output frequency, pulse frequency
and current derating. Higher output frequencies on request.
- The correlation between the maximum output frequency and permissible
output current (current derating).
For additional information, please refer to the SINAMICS
Low Voltage Engineering Manual.

Siemens D 21.3 · 2022 8/9


© Siemens 2022

SINAMICS S150 Converter Cabinet Units

Converter cabinet units

■ Technical specifications
Line voltage 380 ... 480 V 3 AC SINAMICS S150 converter cabinet units
6SL3710- 6SL3710- 6SL3710- 6SL3710- 6SL3710- 6SL3710-
7LE32-1AA3 7LE32-6AA3 7LE33-1AA3 7LE33-8AA3 7LE35-0AA3 7LE36-1AA3
Type rating
• At IL (50 Hz 400 V) 1) kW 110 132 160 200 250 315
• At IH (50 Hz 400 V) 1) kW 90 110 132 160 200 250
• At IL (60 Hz 460 V) 2) hp 150 200 250 300 400 500
• At IH (60 Hz 460 V) 2) hp 150 200 200 250 350 350
Output current
• Rated current IN O A 210 260 310 380 490 605
• Base-load current IL 3) A 205 250 302 370 477 590
• Base-load current IH 4) A 178 233 277 340 438 460
• Maximum current Imax O A 307 375 453 555 715 885
Infeed/regenerative feedback current
• Rated current IN I A 197 242 286 349 447 549
• Maximum current Imax I A 315 390 570 570 735 907
Current demand, max. 5)
• 24 V DC aux. power supply A Internal Internal Internal Internal Internal Internal
Pulse frequency 6)
• Rated frequency kHz 2 2 2 2 2 1.25
• Pulse frequency, max.
- Without current derating kHz 2 2 2 2 2 1.25
- With current derating kHz 8 8 8 8 8 8
Power loss, max. 7)
• At 50 Hz 400 V kW 6.31 7.55 10.01 10.72 13.13 17.69
• At 60 Hz 460 V kW 6.49 7.85 10.45 11.15 13.65 18.55
Cooling air requirement m3/s 0.58 (20.5) 0.7 (24.7) 1.19 (42.0) 1.19 (42.0) 1.19 (42.0) 1.96 (69.2)
(ft3/s)
Sound pressure level LpA dB 71/73 71/73 72/74 72/74 72/74 77/79
(1 m) at 50/60 Hz
Cable length, max.
• Shielded m (ft) 300 (984) 300 (984) 300 (984) 300 (984) 300 (984) 300 (984)
• Unshielded m (ft) 450 (1476) 450 (1476) 450 (1476) 450 (1476) 450 (1476) 450 (1476)
Degree of protection IP20 IP20 IP20 IP20 IP20 IP20
Dimensions
• Width mm (in) 1400 (55.1) 1400 (55.1) 1600 (63.0) 1800 (70.9) 1800 (70.9) 2200 (86.6)
• Height mm (in) 2000 (78.7) 2000 (78.7) 2000 (78.7) 2000 (78.7) 2000 (78.7) 2000 (78.7)
• Depth mm (in) 600 (23.6) 600 (23.6) 600 (23.6) 600 (23.6) 600 (23.6) 600 (23.6)
Weight (without options), approx. kg (lb) 708 (1561) 708 (1561) 892 (1967) 980 (2161) 980 (2161) 1716 (3783)
8 Rated short-circuit current according kA 65 65 65 50 50 50
to IEC 8)
Minimum short-circuit current 9) kA 3 3 4.5 4.5 8 12
Frame sizes
• Active Interface Module FI FI GI GI GI HI
• Active Line Module FX FX GX GX GX HX
• Motor Module FX FX GX GX GX HX

Note:
The power data in hp units is based on the NEC/CEC standards for the North American market.
Information about line supply connections, motor connections and cabinet grounding can be found under Cable cross-sections
and connections.

1) 6)
Rated power of a typical 6-pole standard induction motor based on IL or IH Information regarding the correlation between the pulse frequency and
for 400 V 3 AC 50 Hz. max. output current/output frequency is provided in the SINAMICS
2)
Rated power of a typical 6-pole standard induction motor based on IL or IH Low Voltage Engineering Manual.
7)
for 460 V 3 AC 60 Hz. The specified power losses are the maximum values at 100 % utilization.
3)
The base-load current IL is based on a duty cycle of 110 % for 60 s The values are lower under normal operating conditions.
8)
or 150 % for 10 s with a duty cycle duration of 300 s. In conjunction with the specified fuses or circuit breakers.
4) 9)
The base-load current IH is based on a duty cycle of 150 % for 60 s Current required for reliably triggering protective devices.
or 160 % for 10 s with a duty cycle duration of 300 s.
5)
If the drive closed-loop control is still to remain active when the line supply
fails, the equipment must be provided with an external 24 V DC supply.

8/10 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S150 Converter Cabinet Units

Converter cabinet units

■ Technical specifications
Line voltage 380 ... 480 V 3 AC SINAMICS S150 converter cabinet units
6SL3710- 6SL3710- 6SL3710- 6SL3710- 6SL3710-
7LE37-5AA3 7LE38-4AA3 7LE41-0AA3 7LE41-2AA3 7LE41-4AA3
Type rating
• At IL (50 Hz 400 V) 1) kW 400 450 560 710 800
• At IH (50 Hz 400 V) 1) kW 315 400 450 560 710
• At IL (60 Hz 460 V) 2) hp 600 700 800 900 1150
• At IH (60 Hz 460 V) 2) hp 450 600 700 900 1000
Output current
• Rated current IN O A 745 840 985 1260 1405
• Base-load current IL 3) A 725 820 960 1230 1370
• Base-load current IH 4) A 570 700 860 1127 1257
• Maximum current Imax O A 1087 1230 1440 1845 2055
Infeed/regenerative feedback current
• Rated current IN I A 674 759 888 1133 1262
• Maximum current Imax I A 1118 1260 1477 1891 2107
Current demand, max. 5)
• 24 V DC aux. power supply A Internal Internal Internal Internal Internal
Pulse frequency 6)
• Rated frequency kHz 1.25 1.25 1.25 1.25 1.25
• Pulse frequency, max.
- Without current derating kHz 1.25 1.25 1.25 1.25 1.25
- With current derating kHz 8 8 8 8 8
Power loss, max. 7)
• At 50 Hz 400 V kW 20.63 21.1 27.25 33.05 33.95
• At 60 Hz 460 V kW 21.75 22.25 28.65 34.85 35.85
Cooling air requirement m3/s 1.96 (69.2) 1.96 (69.2) 2.6 (91.8) 2.6 (91.8) 2.6 (91.8)
(ft3/s)
Sound pressure level LpA dB 77/79 77/79 77/79 78/80 78/80
(1 m) at 50/60 Hz
Cable length, max.
• Shielded m (ft) 300 (984) 300 (984) 300 (984) 300 (984) 300 (984)
• Unshielded m (ft) 450 (1476) 450 (1476) 450 (1476) 450 (1476) 450 (1476)
Degree of protection IP20 IP20 IP20 IP20 IP20
Dimensions
• Width mm (in) 2200 (86.6) 2200 (86.6) 2800 (110) 2800 (110) 2800 (110)
• Height mm (in) 2000 (78.7) 2000 (78.7) 2000 (78.7) 2000 (78.7) 2000 (78.7)
• Depth mm (in) 600 (23.6) 600 (23.6) 600 (23.6) 600 (23.6) 600 (23.6)
Weight (without options), approx. kg (lb) 1731 (3816) 1778 (3920) 2408 (5309) 2408 (5309) 2408 (5309)
Rated short-circuit current according kA 50 55 55 55 55 8
to IEC 8)
Minimum short-circuit current 9) kA 15 2 2.5 3.2 3.2
Frame sizes
• Active Interface Module HI HI JI JI JI
• Active Line Module HX HX JX JX JX
• Motor Module HX HX JX JX JX

Note:
The power data in hp units is based on the NEC/CEC standards for the North American market.
Information about line supply connections, motor connections and cabinet grounding can be found under Cable cross-sections
and connections.

1) 6)
Rated power of a typical 6-pole standard induction motor based on IL or IH Information regarding the correlation between the pulse frequency and
for 400 V 3 AC 50 Hz. max. output current/output frequency is provided in the SINAMICS
2)
Rated power of a typical 6-pole standard induction motor based on IL or IH Low Voltage Engineering Manual.
7)
for 460 V 3 AC 60 Hz. The specified power losses are the maximum values at 100 % utilization.
3)
The base-load current IL is based on a duty cycle of 110 % for 60 s The values are lower under normal operating conditions.
8)
or 150 % for 10 s with a duty cycle duration of 300 s. In conjunction with the specified fuses or circuit breakers.
4) 9)
The base-load current IH is based on a duty cycle of 150 % for 60 s Current required for reliably triggering protective devices.
or 160 % for 10 s with a duty cycle duration of 300 s.
5)
If the drive closed-loop control is still to remain active when the line supply
fails, the equipment must be provided with an external 24 V DC supply.

Siemens D 21.3 · 2022 8/11


© Siemens 2022

SINAMICS S150 Converter Cabinet Units

Converter cabinet units

■ Technical specifications
Line voltage 500 ... 690 V 3 AC SINAMICS S150 converter cabinet units
6SL3710- 6SL3710- 6SL3710- 6SL3710- 6SL3710- 6SL3710-
7LG28-5AA3 7LG31-0AA3 7LG31-2AA3 7LG31-5AA3 7LG31-8AA3 7LG32-2AA3
Type rating
• At IL (50 Hz 690 V) 1) kW 75 90 110 132 160 200
• At IH (50 Hz 690 V) 1) kW 55 75 90 110 132 160
• At IL (50 Hz 500 V) 1) kW 55 55 75 90 110 132
• At IH (50 Hz 500 V) 1) kW 45 55 75 90 90 110
• At IL (60 Hz 575 V) 2) hp 75 75 100 150 150 200
• At IH (60 Hz 575 V) 2) hp 75 75 100 125 150 200
Output current
• Rated current IN O A 85 100 120 150 175 215
• Base-load current IL 3) A 80 95 115 142 170 208
• Base-load current IH 4) A 76 89 117 134 157 192
• Maximum current Imax O A 120 142 172 213 255 312
Infeed/regenerative feedback current
• Rated current IN I A 86 99 117 144 166 202
• Maximum current Imax I A 125 144 170 210 253 308
Current demand, max. 5)
• 24 V DC aux. power supply A Internal Internal Internal Internal Internal Internal
Pulse frequency 6)
• Rated frequency kHz 1.25 1.25 1.25 1.25 1.25 1.25
• Pulse frequency, max.
- Without current derating kHz 1.25 1.25 1.25 1.25 1.25 1.25
- With current derating kHz 7.5 7.5 7.5 7.5 7.5 7.5
Power loss, max. 7)
• At 50 Hz 690 V kW 5.12 5.38 5.84 5.75 11.02 11.44
• At 60 Hz 575 V kW 4.45 4.65 5.12 4.97 11.15 11.56
Cooling air requirement m3/s 0.58 (20.5) 0.58 (20.5) 0.58 (20.5) 0.58 (20.5) 1.19 (42.0) 1.19 (42.0)
(ft3/s)
Sound pressure level LpA dB 71/73 71/73 71/73 71/73 75/77 75/77
(1 m) at 50/60 Hz
Cable length, max.
• Shielded m (ft) 300 (984) 300 (984) 300 (984) 300 (984) 300 (984) 300 (984)
• Unshielded m (ft) 450 (1476) 450 (1476) 450 (1476) 450 (1476) 450 (1476) 450 (1476)
Degree of protection IP20 IP20 IP20 IP20 IP20 IP20
Dimensions
• Width mm (in) 1400 (55.1) 1400 (55.1) 1400 (55.1) 1400 (55.1) 1600 (63.0) 1600 (63.0)
• Height mm (in) 2000 (78.7) 2000 (78.7) 2000 (78.7) 2000 (78.7) 2000 (78.7) 2000 (78.7)
8 • Depth mm (in) 600 (23.6) 600 (23.6) 600 (23.6) 600 (23.6) 600 (23.6) 600 (23.6)
Weight (without options), approx. kg (lb) 708 (1561) 708 (1561) 708 (1561) 708 (1561) 892 (1967) 892 (1967)
Rated short-circuit current according kA 65 65 65 65 65 65
to IEC 8)
Minimum short-circuit current 9) kA 1 1 1.3 1.8 2.5 3
Frame size
• Active Interface Module FI FI FI FI GI GI
• Active Line Module FX FX FX FX GX GX
• Motor Module FX FX FX FX GX GX

Note:
The power data in hp units is based on the NEC/CEC standards for the North American market.
Information about line supply connections, motor connections and cabinet grounding can be found under Cable cross-sections
and connections.

1) Rated power of a typical 6-pole standard induction motor based on IL or IH 6) Information regarding the correlation between the pulse frequency and
for 400 V 3 AC 50 Hz. max. output current/output frequency is provided in the SINAMICS
2) Rated power of a typical 6-pole standard induction motor based on IL or IH Low Voltage Engineering Manual.
for 460 V 3 AC 60 Hz. 7) The specified power losses are the maximum values at 100 % utilization.
3) The base-load current IL is based on a duty cycle of 110 % for 60 s The values are lower under normal operating conditions.
or 150 % for 10 s with a duty cycle duration of 300 s. 8) In conjunction with the specified fuses or circuit breakers.
4) The base-load current IH is based on a duty cycle of 150 % for 60 s 9) Current required for reliably triggering protective devices.
or 160 % for 10 s with a duty cycle duration of 300 s.
5) If the drive closed-loop control is still to remain active when the line supply
fails, the equipment must be provided with an external 24 V DC supply.

8/12 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S150 Converter Cabinet Units

Converter cabinet units

■ Technical specifications
Line voltage 500 ... 690 V 3 AC SINAMICS S150 converter cabinet units
6SL3710- 6SL3710- 6SL3710- 6SL3710- 6SL3710- 6SL3710-
7LG32-6AA3 7LG33-3AA3 7LG34-1AA3 7LG34-7AA3 7LG35-8AA3 7LG37-4AA3
Type rating
• At IL (50 Hz 690 V) 1) kW 250 315 400 450 560 710
• At IH (50 Hz 690 V) 1) kW 200 250 315 400 450 630
• At IL (50 Hz 500 V) 1) kW 160 200 250 315 400 500
• At IH (50 Hz 500 V) 1) kW 132 160 200 250 315 450
• At IL (60 Hz 575 V) 2) hp 250 300 400 450 600 700
• At IH (60 Hz 575 V) 2) hp 200 250 350 450 500 700
Output current
• Rated current IN O A 260 330 410 465 575 735
• Base-load current IL 3) A 250 320 400 452 560 710
• Base-load current IH 4) A 233 280 367 416 514 657
• Maximum current Imax O A 375 480 600 678 840 1065
Infeed/regenerative feedback current
• Rated current IN I A 242 304 375 424 522 665
• Maximum current Imax I A 370 465 619 700 862 1102
Current demand, max. 5)
• 24 V DC aux. power supply A Internal Internal Internal Internal Internal Internal
Pulse frequency 6)
• Rated frequency kHz 1.25 1.25 1.25 1.25 1.25 1.25
• Pulse frequency, max.
- Without current derating kHz 1.25 1.25 1.25 1.25 1.25 1.25
- With current derating kHz 7.5 7.5 7.5 7.5 7.5 7.5
Power loss, max. 7)
• At 50 Hz 690 V kW 11.97 12.69 19.98 20.55 24.05 30.25
• At 60 Hz 575 V kW 12.03 12.63 18.86 19.47 22.85 28.75
Cooling air requirement m3/s 1.19 (42.0) 1.19 (42.0) 1.96 (69.2) 1.96 (69.2) 1.96 (69.2) 2.6 (91.8)
(ft3/s)
Sound pressure level LpA dB 75/77 75/77 77/79 77/79 77/79 77/79
(1 m) at 50/60 Hz
Cable length, max.
• Shielded m (ft) 300 (984) 300 (984) 300 (984) 300 (984) 300 (984) 300 (984)
• Unshielded m (ft) 450 (1476) 450 (1476) 450 (1476) 450 (1476) 450 (1476) 450 (1476)
Degree of protection IP20 IP20 IP20 IP20 IP20 IP20
Dimensions
• Width mm (in) 1600 (63.0) 1600 (63.0) 2200 (86.6) 2200 (86.6) 2200 (86.6) 2800 (110)
• Height mm (in) 2000 (78.7) 2000 (78.7) 2000 (78.7) 2000 (78.7) 2000 (78.7) 2000 (78.7)
• Depth mm (in) 600 (23.6) 600 (23.6) 600 (23.6) 600 (23.6) 600 (23.6) 600 (23.6) 8
Weight (without options), approx. kg (lb) 892 (1967) 892 (1967) 1716 (3783) 1716 (3783) 1716 (3783) 2300 (5071)
Rated short-circuit current according kA 65 65 50 50 50 50
to IEC 8)
Minimum short-circuit current 9) kA 3 4.5 4.5 7 9 15
Frame size
• Active Interface Module GI GI HI HI HI JI
• Active Line Module GX GX HX HX HX JX
• Motor Module GX GX HX HX HX JX

Note:
The power data in hp units is based on the NEC/CEC standards for the North American market.
Information about line supply connections, motor connections and cabinet grounding can be found under Cable cross-sections
and connections.

1) 6)
Rated power of a typical 6-pole standard induction motor based on IL or IH Information regarding the correlation between the pulse frequency and
for 400 V 3 AC 50 Hz. max. output current/output frequency is provided in the SINAMICS
2)
Rated power of a typical 6-pole standard induction motor based on IL or IH Low Voltage Engineering Manual.
7)
for 460 V 3 AC 60 Hz. The specified power losses are the maximum values at 100 % utilization.
3)
The base-load current IL is based on a duty cycle of 110 % for 60 s The values are lower under normal operating conditions.
8)
or 150 % for 10 s with a duty cycle duration of 300 s. In conjunction with the specified fuses or circuit breakers.
4) 9)
The base-load current IH is based on a duty cycle of 150 % for 60 s Current required for reliably triggering protective devices.
or 160 % for 10 s with a duty cycle duration of 300 s.
5)
If the drive closed-loop control is still to remain active when the line supply
fails, the equipment must be provided with an external 24 V DC supply.

Siemens D 21.3 · 2022 8/13


© Siemens 2022

SINAMICS S150 Converter Cabinet Units

Converter cabinet units

■ Technical specifications
Line voltage 500 ... 690 V 3 AC SINAMICS S150 converter cabinet units
6SL3710-7LG38-1AA3 6SL3710-7LG38-8AA3 6SL3710-7LG41-0AA3 6SL3710-7LG41-3AA3
Type rating
• At IL (50 Hz 690 V) 1) kW 800 900 1000 1200
• At IH (50 Hz 690 V) 1) kW 710 800 900 1000
• At IL (50 Hz 500 V) 1) kW 560 630 710 900
• At IH (50 Hz 500 V) 1) kW 500 560 630 800
• At IL (60 Hz 575 V) 2) hp 800 900 1000 1250
• At IH (60 Hz 575 V) 2) hp 700 800 900 1000
Output current
• Rated current IN O A 810 910 1025 1270
• Base-load current IL 3) A 790 880 1000 1230
• Base-load current IH 4) A 724 814 917 1136
• Maximum current Imax O A 1185 1320 1500 1845
Infeed/regenerative feedback current
• Rated current IN I A 732 821 923 1142
• Maximum current Imax I A 1218 1367 1537 1905
Current demand, max. 5)
• 24 V DC aux. power supply A Internal Internal Internal Internal
6)
Pulse frequency
• Rated frequency kHz 1.25 1.25 1.25 1.25
• Pulse frequency, max.
- Without current derating kHz 1.25 1.25 1.25 1.25
- With current derating kHz 7.5 7.5 7.5 7.5
Power loss, max. 7)
• At 50 Hz 690 V kW 34.45 34.65 36.15 42.25
• At 60 Hz 575 V kW 32.75 32.85 34.25 39.25
Cooling air requirement m3/s 2.6 (91.8) 2.6 (91.8) 2.6 (91.8) 2.6 (91.8)
(ft3/s)
Sound pressure level LpA dB 77/79 77/79 77/79 77/79
(1 m) at 50/60 Hz
Cable length, max.
• Shielded m (ft) 300 (984) 300 (984) 300 (984) 300 (984)
• Unshielded m (ft) 450 (1476) 450 (1476) 450 (1476) 450 (1476)
Degree of protection IP20 IP20 IP20 IP20
Dimensions
• Width mm (in) 2800 (110) 2800 (110) 2800 (110) 2800 (110)
• Height mm (in) 2000 (78.7) 2000 (78.7) 2000 (78.7) 2000 (78.7)
• Depth mm (in) 600 (23.6) 600 (23.6) 600 (23.6) 600 (23.6)
8 Weight (without options), approx. kg (lb) 2408 (5309) 2408 (5309) 2408 (5309) 2408 (5309)
Rated short-circuit current according kA 85 85 85 85
to IEC 8)
Minimum short-circuit current 9) kA 2 2 2.5 3.2
Frame size
• Active Interface Module JI JI JI JI
• Active Line Module JX JX JX JX
• Motor Module JX JX JX JX

Note:
The power data in hp units is based on the NEC/CEC standards for the North American market.
Information about line supply connections, motor connections and cabinet grounding can be found under Cable cross-sections
and connections.

1) 6)
Rated power of a typical 6-pole standard induction motor based on IL or IH Information regarding the correlation between the pulse frequency and
for 400 V 3 AC 50 Hz. max. output current/output frequency is provided in the SINAMICS
2)
Rated power of a typical 6-pole standard induction motor based on IL or IH Low Voltage Engineering Manual.
7)
for 460 V 3 AC 60 Hz. The specified power losses are the maximum values at 100 % utilization.
3)
The base-load current IL is based on a duty cycle of 110 % for 60 s The values are lower under normal operating conditions.
8)
or 150 % for 10 s with a duty cycle duration of 300 s. In conjunction with the specified fuses or circuit breakers.
4) 9)
The base-load current IH is based on a duty cycle of 150 % for 60 s Current required for reliably triggering protective devices.
or 160 % for 10 s with a duty cycle duration of 300 s.
5)
If the drive closed-loop control is still to remain active when the line supply
fails, the equipment must be provided with an external 24 V DC supply.

8/14 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S150 Converter Cabinet Units

Converter cabinet units

■ Characteristic curves
Derating data the output current, whereby ambient temperatures lower than
40 °C may be offset to compensate.
SINAMICS S150 converter cabinet units and the associated
system components are rated for an ambient temperature of The following table lists the permissible output currents
40 °C and installation altitudes up to 2000 m above sea level. depending on the installation altitude and ambient temperature
for the various degrees of protection. The specified values
At ambient temperatures > 40 °C, the output current must be already include a permitted compensation in respect of
reduced. Ambient temperatures above 50 °C are not installation altitude and ambient temperatures < 40 °C
permissible. (temperature at the air intake of the converter cabinet unit).
At installation altitudes > 2000 m above sea level, it must be The values apply under the precondition that the cooling air flow
taken into account that the air pressure, and therefore air density, stated in the technical specifications is ensured by the way the
decreases as the height increases. As a consequence, devices are installed in the cabinet.
the cooling efficiency and the insulation capacity of the air also
decrease. As additional measure for installation altitudes from 2000 m up
to 5000 m, an isolating transformer is required in order to reduce
Due to the reduced cooling efficiency, it is necessary, on the one transient overvoltages according to EN 60664-1.
hand, to reduce the ambient temperature and on the other hand, For additional information, please refer to the SINAMICS Low
to lower heat loss in the converter cabinet unit by reducing Voltage Engineering Manual.
Current-derating factors for converter cabinet units depending on the ambient/air intake temperature, the installation altitude and the
degree of protection
Degree of protection Installation altitude Current derating factor (as a percentage of the rated current)
above sea level for an ambient/air intake temperature of
m (ft) 20 °C (68 °F) 25 °C (77 °F) 30 °C (86 °F) 35 °C (95 °F) 40 °C (104 °F) 45 °C (113 °F) 50 °C (122 °F)
IP20, IP21, 0 ... 2000 93.3 % 86.7 %
IP23, IP43 (0 ... 6562)
2001 ... 2500 96.3 %
(6565 ... 8202)
2501 ... 3000 100 % 98.7 %
(8205 ... 9843)
3001 ... 3500
(9846 ... 11483)
3501 ... 4000 96.3 %
(11486 ... 13123)
4001 ... 4500 97.5 %
(13127 ... 14764)
4501 ... 5000 98.2 %
(14767 ... 16404)
IP54 0 ... 2000 93.3 % 86.7 % 80.0 %
(0 ... 6562)
2001 ... 2500 96.3 % 89.8 %
(6565 ... 8202)
2501 ... 3000 100 % 98.7 % 92.5 % 8
(8205 ... 9843)
3001 ... 3500 94.7 %
(9846 ... 11483)
3501 ... 4000 96.3 % 90.7 %
(11486 ... 13123)
4001 ... 4500 97.5 % 92.1 %
(13127 ... 14764)
4501 ... 5000 93.0 %
(14767 ... 16404)

Siemens D 21.3 · 2022 8/15


© Siemens 2022

SINAMICS S150 Converter Cabinet Units

Converter cabinet units

■ Characteristic curves
Current derating as a function of the pulse frequency For additional information, please refer to the SINAMICS Low
Voltage Engineering Manual.
To reduce motor noise or to increase output frequency, the pulse
frequency can be increased relative to the factory setting
(1.25 kHz or 2 kHz). When the pulse frequency is increased, the
derating factor of the output current must be taken into account.
This derating factor must be applied to the currents specified in
the technical specifications.
Derating factor of the output current depending on the pulse frequency for devices with a rated pulse frequency of 2 kHz
SINAMICS S150 converter Type rating Output current Derating factor
cabinet unit at 400 V at 2 kHz at pulse frequency
6SL3710-... kW A 2.5 kHz 4 kHz 5 kHz 7.5 kHz 8 kHz
380 ... 480 V 3 AC
7LE32-1AA3 110 210 95 % 82 % 74 % 54 % 50 %
7LE32-6AA3 132 260 95 % 83 % 74 % 54 % 50 %
7LE33-1AA3 160 310 97 % 88 % 78 % 54 % 50 %
7LE33-8AA3 200 380 96 % 87 % 77 % 54 % 50 %
7LE35-0AA3 250 490 94 % 78 % 71 % 53 % 50 %

Derating factor of the output current depending on the pulse frequency for devices with a rated pulse frequency of 1.25 kHz
SINAMICS S150 converter Type rating Output current Derating factor
cabinet unit at 400 V or 690 V at 1.25 kHz at pulse frequency
6SL3710-... kW A 2 kHz 2.5 kHz 4 kHz 5 kHz 7.5 kHz 8 kHz
380 ... 480 V 3 AC
7LE36-1AA3 315 605 83 % 72 % 64 % 60 % 40 % 36 %
7LE37-5AA3 400 745 83 % 72 % 64 % 60 % 40 % 36 %
7LE38-4AA3 450 840 87 % 79 % 64 % 55 % 40 % 37 %
7LE41-0AA3 560 985 92 % 87 % 70 % 60 % 50 % 47 %
7LE41-2AA3 710 1260 92 % 87 % 70 % 60 % 50 % 47 %
7LE41-4AA3 800 1405 97 % 95 % 74 % 60 % 50 % 47 %
500 ... 690 V 3 AC
7LG28-5AA3 75 85 93 % 89 % 71 % 60 % 40 % –
7LG31-0AA3 90 100 92 % 88 % 71 % 60 % 40 % –
7LG31-2AA3 110 120 92 % 88 % 71 % 60 % 40 % –
7LG31-5AA3 132 150 90 % 84 % 66 % 55 % 35 % –

8 7LG31-8AA3
7LG32-2AA3
160
200
175
215
92 %
92 %
87 %
87 %
70 %
70 %
60 %
60 %
40 %
40 %


7LG32-6AA3 250 260 92 % 88 % 71 % 60 % 40 % –
7LG33-3AA3 315 330 89 % 82 % 65 % 55 % 40 % –
7LG34-1AA3 400 410 89 % 82 % 65 % 55 % 35 % –
7LG34-7AA3 450 465 92 % 87 % 67 % 55 % 35 % –
7LG35-8AA3 560 575 91 % 85 % 64 % 50 % 35 % –
7LG37-4AA3 710 735 87 % 79 % 64 % 55 % 25 % –
7LG38-1AA3 800 810 97 % 95 % 71 % 55 % 35 % –
7LG38-8AA3 900 910 92 % 87 % 67 % 55 % 33 % –
7LG41-0AA3 1000 1025 91 % 86 % 64 % 50 % 30 % –
7LG41-3AA3 1200 1270 87 % 79 % 55 % 40 % 25 % –

8/16 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S150 Converter Cabinet Units

Converter cabinet units

■ Characteristic curves
Maximum output frequencies achieved by increasing the pulse
frequency
The adjustable pulse frequencies – and therefore the output
frequencies that can be achieved with the factory-set current
controller clock cycles – are listed below.
Current controller clock cycle Adjustable pulse frequency Max. achievable output frequency fA
TI fp
V/f mode Vector mode
250 µs 1) 2 kHz 166 Hz 166 Hz
4 kHz 333 Hz 333 Hz
8 kHz 550 Hz 480 Hz
400 µs 2) 1.25 kHz 104 Hz 104 Hz
2.5 kHz 208 Hz 208 Hz
5.0 kHz 416 Hz 300 Hz 3)
7.5 kHz 550 Hz 300 Hz 3)

Overload capability
The SINAMICS S150 converter cabinet units are equipped with The base-load current IH for a high overload is based on a load
an overload reserve to deal with breakaway torques, for exam- cycle of 150 % for 60 s or 160 % for 10 s.
ple. If larger surge loads occur, this must be taken into account
in the configuration. For drives with overload requirements, the
Converter current
appropriate base load current must, therefore, be used as a ba-
10 s
sis for the required load.
1.6 x IH Short-time current 160 %
The criterion for overload is that the drive is operated with its
base load current before and after the overload occurs on the 1.5 x IH Short-time current 150 %
basis of a duty cycle duration of 300 s.
Another precondition is that the frequency converter is operated Rated current (continuous)
at its factory-set pulse frequency at output frequencies >10 Hz.
For temporary, periodic duty cycles with high variations of load Base-load current IH for high overload
within the duty cycle, the relevant sections of the SINAMICS Low Irated
Voltage Engineering Manual must be observed.
IH

G_D213_EN_00036
The base-load current for a low overload IL is the basis for a duty 60 s
cycle of 110 % for 60 s or 150 % for 10 s. 300 s

Converter current
10 s t

1.5 x IL

Short-time current 150 %


High overload
8
Short-time current 110 %
Rated current (continuous)
Base-load current IL
1.1 x IL
for low overload
Irated
IL
G_D213_EN_00035

60 s
300 s

Low overload

1) 3)
As factory setting, the following devices have a current controller clock The maximum output frequency is limited to 300 Hz due to the closed-loop
cycle of 250 µs and a pulse frequency of 2 kHz: - 380 ... 480 V 3 AC:  250 control.
kW / 490 A
2)
As factory setting, the following devices have a current controller clock
cycle of 400 µs and a pulse frequency of 1.25 kHz: - 380 ... 480 V 3 AC: 
315 kW / 605 A, 500... 690 V 3 AC: All power ratings

Siemens D 21.3 · 2022 8/17


© Siemens 2022

SINAMICS S150 Converter Cabinet Units

Converter cabinet units

■ Options
When ordering a converter with options, add the suffix "-Z" to the Available options Order code
article number and then the order code(s) for the desired
Other options
option(s).
CBE20 Communication Board G33
Example:
6SL3710-7LE32-1AA3-Z TM150 temperature sensor evaluation unit G51
M07+D60+... TM31 Terminal Module G60
See also ordering examples. Additional TM31 Terminal Module G61
TB30 Terminal Board G62
Available options Order code
SMC10 Sensor Module Cabinet-Mounted K46
Input side
SMC20 Sensor Module Cabinet-Mounted K48
Use in the first environment according to EN 618003, L00
Category C2 (TN-TT line supplies with grounded neutral point) SMC30 Sensor Module Cabinet-Mounted K50
Infeed module one level lower L04 VSM10 Voltage Sensing Module K51
Surge suppression L21 CU320-2 PN Control Unit K95
Main switch incl. fuses or circuit breakers L26 Connection for external auxiliary equipment L19
Line filter monitoring L40 Cabinet lighting with service socket L50
EMC shield bus (cable connection from below) 1) M70 Cabinet anti-condensation heating L55
Output side 25/125 kW braking unit L61
for line voltages of 380 … 480 V (110 … 132 kW)
dv/dt filter plus Voltage Peak Limiter L07 and 660 … 690 V (75 … 132 kW)
Motor reactor L08 50/250 kW braking unit L62
dv/dt filter plus Voltage Peak Limiter L10 for line voltages of 380 … 480 V (160 … 800 kW)
and 660 … 690 V (160 … 1200 kW)
Sine-wave filter (only for the voltage range 380 to 480 V, L15
up to 200 kW) 25/125 kW braking unit L64
for line voltages of 500 … 600 V (110 … 132 kW)
EMC shield bus (cable connection from below) 1) M70
50/250 kW braking unit L65
Motor protection and safety functions for line voltages of 500 … 600 V (160 … 1200 kW)
EMERGENCY OFF pushbutton installed in the cabinet door L45 Marking of all control cable wire ends M91
EMERGENCY OFF category 0 L57 Special cabinet paint finish 2) Y09
EMERGENCY STOP category 1, 230 V AC L59 One-line label for system identification, 40 × 80 mm Y31
EMERGENCY STOP category 1, 24 V DC L60 Two-line label for system identification, 40 × 180 mm Y32
Thermistor motor protection (alarm) L83 Four-line label for system identification, 40 × 180 mm Y33
Thermistor motor protection (trip) L84 Production flowcharts
Pt100 evaluation unit L86 Documentation, production flowchart: one issue B43
Insulation monitoring L87 Documentation, production flowchart: updated every two B44
weeks
Additional touch protection M60
Documentation, production flowchart: updated every month B45
Degree of protection increase
8 Degree of protection IP21 M21
Packaging options
Generation of a preliminary and a final packing list (shipping) B55
Degree of protection IP23 M23
Packed items labeled with a customized label B56
Degree of protection IP43 M43
Photo documentation of the ordered units B57
Degree of protection IP54 M54
Mechanical options
Base 100 mm high, RAL 7022 M06
Cable-marshaling compartment 200 mm high, RAL 7035 M07
Line connection from above M13
Motor connection from above M78
Crane transport assembly for cabinets (top-mounted) M90
Safety Integrated
Safety license Extended Functions for 1 axis K01
Second SMC30 Sensor Module Cabinet-Mounted K52
Terminal module for controlling the Safe Torque Off and Safe K82
Stop 1 safety functions
TM54F Terminal Module K87
Safe Brake Adapter SBA, 230 V AC K88

1) 2)
This option is listed for the input- and output-side options, but is only The order code Y.. requires data in plain text.
required once.

8/18 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S150 Converter Cabinet Units

Converter cabinet units

■ Options
Available options Order code Available options Order code
Documentation (standard: English/German) Options specific to the chemical industry
Documentation in German D00 NAMUR terminal strip B00
Customer documentation (circuit diagram, layout diagram, D01 Protective separation for 24 V supply (PELV) B02
dimension drawing, spare parts list) in EPLAN format.
Outlet for external auxiliary equipment (uncontrolled) B03
Customer documentation (circuit diagram, terminal diagram, D02
layout diagram) in DXF format Options specific to the shipbuilding industry

Customer documentation as hard copy D04 Marine version M66

Preliminary version of customer documentation D14 Individual certificate from Lloyds Register (LR) E21

Documentation in Russian D56 Individual certificate from Bureau Veritas (BV) E31

Documentation in English/French D58 Individual certificate from DNV E51

Documentation in English/Spanish D60 Individual certificate from American Bureau of Shipping (ABS) E61

Documentation in Italian D72 Individual certificate from China Classification Society (CCS) E71

Documentation in English D76 Converter acceptance in presence of customer

Documentation in French D77 Visual acceptance F03

Documentation in Spanish D78 Function test without motor F71

Documentation in English/Italian D80 Function test with test bay motor under no-load conditions F75

Documentation in Chinese D84 Insulation test F77

Documentation in English/Chinese D91 Customer-specific acceptance inspections (on request) F97

Documentation in English/Portuguese (Brazil) D93 Converter acceptance without the customer present

Documentation in English/Russian D94 Function test without motor F72

Rating plate data (standard: English/German) Function test with test bay motor under no-load conditions F74

Rating plate data in English/French T58 Insulation test F76

Rating plate data in English/Spanish T60


Rating plate data in English/Italian T80
Rating plate data in English/Portuguese (Brazil) T83
Rating plate data in English/Russian T85
Rating plate data in English/Chinese T91

Option selection matrix


Certain options can mutually exclude one another  Possible combination
(options that are not involved, are also not shown).
– Combination not possible
8
Electrical options
L07 L08 L10 L15 L57 L59 L60 L61/ L62/ L87 K82 M78
L64 L65
L07 – – –        –
L08 – – –        –
L10 – – –        –
L15 – – –        –
L57     – –     
L59     – –     
L60     – –     
L61/L64        –   
L62/L65        –   
L87          – 1) 
K82          – 1) 
M78 – – – –       

1)
A combination of L87 and K82 is available on request.

Siemens D 21.3 · 2022 8/19


© Siemens 2022

SINAMICS S150 Converter Cabinet Units

Converter cabinet units

■ Options
Mechanical/electrical options
L00 M06 M07 M13 M21 M23 M43 M54 M60 M66 M70 M78
1)
L00          
M06  –         
M07  –         
2)
M13          
M21     – – – – 3) –  –
M23     – – – – –  
M43     – – – –   
M54     – – – –   
M60    – – 3) – – –   –
M66     – –     –
M70 1)   2)       –2)
M78     –    – – –2)

Other options
G20 G33 G62 K46 K48 K50 K51 K52
G20 – –     
G33 – –     
G62 – –     
K46    – – – –
K48    – – – –
K50    – – – 
K51    – – – –
K52    – –  –

Documentation
D00 D01 D02 D14 D56 D58 D60 D72 D76 D77 D78 D80 D84 D91 D93 D94 D99
D00                –
D01   –             –
D02                –
D14  –              –
D56               – –
D58      –  – –  –  – – – –

8 D60
D72









 


 –








 




– –

D76      – –    –  – – – –
D77      –          –
D78       –         –
D80      – – – –    – – – –
D84             –   –
D91      – –  –   – – – – –
D93      – –  –   –  – – –
D94     – – –  –   –  – – –
D99 – – – – – – – – – – – – – – – –

Rating plate data


T58 T60 T80 T83 T85 T91
T58 – – – – –
T60 – – – – –
T80 – – – – –
T83 – – – – –
T85 – – – – –
T91 – – – – –

1) Option L00 includes option M70. 3) Can only be selected for converters in the voltage range 400 V to 250 kW
2) If the line connection (option M13) and the motor connection (option M78) and 690 V to 315 kW. The M60 option is fitted as standard for higher out-
are from above, the EMC shield bus is not required in the lower cabinet puts.
area.

8/20 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S150 Converter Cabinet Units

Converter cabinet units

■ Options
Ordering examples
Example 1 Example 2
Task: Task:
A drive system is required for a vehicle test stand to perform A drive system is required for a conveyor belt in a brown-coal
exhaust gas analysis which can simulate driving profiles and open-cast mine that is capable of both motor and generator
cycles as encountered in everyday traffic situations. This means operation. Since the conveyor belt must be capable of starting
for the drive system that the dynamometer must be operated after a fault when loaded with bulk material, and it is possible for
both in the motoring as well as regenerating modes. peak loads to occur where 1.5 times the power is required for up
to 60 s, the drive system must be designed according to the
A drive with regenerative feedback into the line supply is overload requirements of such a case. The converter is installed
required as regenerative operation is the predominant operating in a climate-controlled container as a result of the environmental
mode and dynamic switching operations are required. conditions typical of an open-cast mine. The installation altitude
The max. regenerative power is 200 kW. The converter must is 320 m above sea level and the maximum ambient temperature
have degree of protection IP54 as a result of the environmental in the container is 35 °C. The drive is powered through a
conditions. An installation altitude of < 1000 m and 45 °C as the converter transformer from the medium-voltage system. The
maximum ambient temperature can be assumed. The windings drive is connected to an isolated-neutral system and must have
must be equipped with Pt100 resistance thermometers and insulation monitoring. A motor with separately-driven fan is
monitored by the converter for alarm and trip. A switch selected here as the motor is subject to a high load torque when
disconnector must be provided to disconnect the converter from starting and in the lower range. The fan supply voltage is 690 V
the 400 V power supply. In addition, the cabinet is to have a and must be drawn from the converter.
special paint finish in RAL 3002. The required motor power is 420 kW.
Solution: Solution:
Taking into account the derating factors for degree of protection Since the converter is installed in an air-conditioned container, it
IP54 and the increased ambient temperature of 45 °C, can be designed with degree of protection IP20. The ambient
a converter with a minimum power rating of 223 kW should be temperature of 35 °C does not necessitate any additional
configured. derating. However, due to the specified overload conditions, the
A converter with a power rating of at least 250 kW and options base load current IH (for high overload) must be applied.
M54 (degree of protection IP54), L26 (main switch including This results in a power of approx. 520 kW for the converter. The
fuses), L86 (Pt100 evaluation unit) and Y09 (special paint finish) converter with article no. 6SL3710-7LG35-8AA3 must be
is selected. selected.
The ordering data are as follows: Option L87 (insulation monitoring) must be selected for
6SL3710-7LE35-0AA3-Z insulation monitoring.
M54+L26+L86+Y09 Option L19 (connection for external auxiliaries) must be
Cabinet color RAL 3002 selected for the controlled outgoing feeder to power the
separately driven fan.
The ordering data are as follows:
6SL3710-7LG35-8AA3-Z
L19+L87

Siemens D 21.3 · 2022 8/21


© Siemens 2022

SINAMICS S150 Converter Cabinet Units

Description of options

■ Options
B00, B02, B03 Terminal Meaning Default Remarks
Options compliant with NAMUR requirements -X2:
Exclusion list with other options: 10 DI ON (dynamic) / The effective mode
ON/OFF (static) can be encoded
The following restrictions and exclusions applicable to the using a wire jumper
NAMUR terminal strip B00 with regard to other available options at terminal -400: 9;
must be taken into account. 10 codable
11 DI OFF (dynamic)
Not permis- Reason
sible with 12 DI Faster
options 13 DI Slower
L45, L57, A Category 0 EMERGENCY OFF is already provided in the 14 DI RESET
L59, L60 NAMUR version.
The forced line supply disconnection is connected at 15 DI Interlock
terminal -X2: 17, 18.
16 DI Counter-clockwise 0 signal for CW
L83, L84 The B00 option already provides a PTC thermistor evaluation rotating field
unit as standard (trip). 1 signal for CCW
rotating field
L19 Alternatively, option B03 can be selected.
This provides a reduced scope for external auxiliaries. 17, 18 Supply disconnec- EMERGENCY OFF
tion circuit
L87 The insulation monitor monitors the complete electrically
coupled network. An insulation monitor must therefore be 30, 31 Ready Relay output (NO
provided on site. contact)
G60 The B00 option already provides a Terminal Module TM31 as 32, 33 Motor is turning Relay output (NO
a standard feature. contact)
34 DO (NO) Fault Relay output
With options L50, L55, L86, the connection is made as (changeover con-
described in the standard. There is no wiring to the NAMUR 35 DO (COM) tact)
terminal strip. 36 DO (NC)
B00 50, 51 AI Speed setpoint
NAMUR terminal strip 0/4 ... 20 mA
60, 61 AO Motor frequency
The terminal strip is designed according to the requirements and 0/4 ... 20 mA
directives of the standards association for measurement and
control in the chemical industry (NAMUR recommendation 62, 63 AO Motor current Motor current is
NE37). I.e. terminals are specifically assigned to particular 0/4 ... 20 mA default setting; can
be reparameter-
device functions. The inputs and outputs connected to the ized for other vari-
terminals fulfill PELV requirements (protective extra-low voltage) ables
with protective separation.
The 24 V supply is provided on the plant side via terminals
The terminal strip and associated functions have been reduced -X2:1-3 (fused in the converter with 1 A). It must be ensured that
to the necessary minimum. Unlike the NAMUR recommendation, the PELV safety requirements are fulfilled (protective extra-low
optional terminals are not available. voltage with protective separation).
Terminal Meaning
8 -X2:
1 M Reference conductor
2 P24 24 V DC supply
3 P24 24 V DC outgoing feeder

For temperature monitoring of explosion-proof motors, option


B00 includes a PTC thermistor.
Exceeding the limit value causes a shutdown. The associated
PTC sensor is connected to terminal -X3: 90, 91.
Terminal Meaning
-X3:
90, 91 AI Connection of PTC sensor

B02
Protective separation for 24 V supply (PELV)
If no protective separation for 24 V supply (PELV) is available at
the customer site, this option is used to provide a second power
supply to guarantee compliance with PELV. (Terminal
assignments as for option B00, 24 V supply at terminals -X1:1,
2, 3 is not required)
Notice:
The option B02 must always be combined with B00.

8/22 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S150 Converter Cabinet Units

Description of options

■ Options
B03 D01
Outgoing feeder for external auxiliaries (uncontrolled) Customer documentation (circuit diagram, layout diagram,
dimension drawing, spare parts list) in EPLAN format
If, for example, a motor fan is to be supplied with power from the
plant, option B03 provides an uncontrolled external outgoing When ordering the option D01, the final version of the cabinet
feeder with a 10 A fuse. As soon as the supply voltage is present circuit diagram, layout diagram, dimension drawing and spare
at the converter input, a voltage is also present at these parts list in EPLAN format will be digitally delivered.
terminals. This corresponds to the converter input voltage
(U = Uline). You must take this into account when configuring an D02
external fan. Customer documentation (circuit diagram, terminal
diagram, layout diagram) in DXF format
Terminal Meaning
-X1:
Option D02 can be used to order documents such as circuit
diagrams, terminal diagrams, layout diagrams, and dimension
1, 2, 3, PE Outgoing feeder for external auxiliary equipment drawings in DXF format, e.g. for further processing in AutoCAD
Notice: systems.

Option B03 must always be combined with B00. D04


Customer documentation as hard copy
B43, B44, B45
Production flowcharts Device documentation is supplied electronically on a CD-ROM
as standard. If the customer also requires a hard copy of the
Production flowcharts are provided with options B43 to B45. documentation and selects option D04, the following documents
After the order has been clarified, these are emailed as a dual will be supplied in a folder with the converter:
language (English/German) PDF file. • Operating instructions
Option Description • Circuit diagram
B43 Documentation – Production flowchart: one issue • Terminal diagram
B44 Documentation – Production flowchart: updated every two • Layout diagram
weeks • Dimension drawing
B45 Documentation – Production flowchart: updated every month • Spare parts list
B55 • Test certificate
Generation of a preliminary and a final packing list Regardless of whether option D04 is selected, hard copies of the
(shipping) safety and transportation guidelines, a check list and
This option provides the electronically editable packing list a registration form are always supplied.
(possibly predefined from the factory) with the following
information in Excel format: D14
Preliminary version of customer documentation
• Number of individual packages
If documents such as circuit diagrams, terminal diagrams,
• Type of package (pallet, crate, etc.) layout diagrams and dimension drawings are required in
• Weight (unpacked and packed) advance for the purpose of system engineering (integration of
• Dimensions (unpacked and packed) drive into higher-level systems, interface definition, installation,
building planning, etc.), it is possible to order a draft copy of the
• Delivery location documentation when ordering the converter cabinet units.
• Label for package item (when option B56 is ordered) These documents are then supplied electronically a few working 8
• Description of what is in the package days following receipt of the order. If the order includes options
that fall outside the scope of standard supply, these will not be
A first packing list is generated after complete technical covered by the documentation due to the obvious time
clarification with preliminary data. When shipped, a final packing constraints.
list is provided with the actual data.
The client is sent the documentation relating to the order by
B56 email. The recipient's email address must be specified with the
Packed items labeled with a customized label order for this purpose. In the email, the recipient will also receive
With this option, customized labels are attached to the a link for downloading order-specific documentation.
unpacked and packed packaged units. Internal customers must With the option D02, the documents are also delivered in DXF
provide two labels at least 2 weeks before the shipping date format.
(printout to the factory logistics department, specifying the
article number).
B57
Photographic documentation of the ordered units
This option provides digital photographic documentation with
the following content:
• 1 photo diagonally from the front
• 1 photo diagonally from the rear (opposite)
• 1 photo with the packed item on which the label is legible
The listed photos of the packed items are taken in both an
unpacked and a packed state in each position (a total of 6
photos per packed item).

Siemens D 21.3 · 2022 8/23


© Siemens 2022

SINAMICS S150 Converter Cabinet Units

Description of options

■ Options
D58, D60, D80, D91, D93, D94 F03, F71, F72, F74, F75, F76, F77, F97
Documentation as language package Converter acceptance inspections
If a documentation option is not selected, the relevant Order code Description
documentation is supplied as standard in English/German.
F03 Visual acceptance
When one of the options specified in the table is selected, the
standard documentation language will be changed from English The inspection includes the following:
/ German to the language combination provided by the option. • Check of degree of protection
• Check of equipment (components)
Order code Language
• Check of equipment identifiers
D58 English/French • Check of clearance and creepage distances
D60 English/Spanish • Check of cables
D80 English/Italian • Check of customer documentation
D91 English/Chinese • Submission of the acceptance report
The tests are carried out with the converter
D93 English/Portuguese (Brazil) de-energized.
D94 English/Russian F71 (witnessed by Function test without connected motor
customer) After the visual acceptance with the converter
D00, D56, D72, D76, D77, D78, D84 F72 (not witnessed by switched off, the converter is connected to rated
Documentation in a single language customer) voltage.
The documentation is also available in a single language, for No current at the converter output end.
example, to be able to order other language combinations. The inspection includes the following:
• Visual acceptance as described for option F03
If a further language is required for standard documentation in • Check of power supply
English/German, the option D74 (documentation • Check of protective and monitoring devices
in English/German) must also be ordered in addition to that (simulation)
• Check of fans
language. • Pre-charging test
• Function test without connected motor
Order code Language • Submission of the acceptance report
D00 German F74 (not witnessed by Function test with test bay motor under no-load
D56 Russian customer) conditions
F75 (witnessed by After the visual acceptance with the converter
D72 Italian customer) switched off, the converter is connected to rated
D76 English voltage.
A small current flows at the converter output end in
D77 French order to operate the test bay motor under no-load
D78 Spanish conditions.
The inspection includes the following:
D84 Chinese • Visual acceptance as described for option F03
• Check of power supply
E21 to E71 • Check of protective and monitoring devices
Individual certification (simulation)
• Check of fans
A type certificate is available for the marine classification • Pre-charging test
institute DNV. • Function test with test bay motor under no-load
8 An additional individual certification of the converter by the
respective certification institute contains the extensions
conditions
• Submission of the acceptance report
described under option M66. F76 (not witnessed by Insulation test
With the respective option, the converter and the documentation customer) The inspection includes the following:
F77 (witnessed by
are certified by an acceptor (certified recipient) for the respec- customer)
• High-voltage test
tive institute and an individual certificate is created. • Measurement of the insulation resistance
• Submission of the acceptance report
• E21 Individual certificate from Lloyds Register (LR)
F97 Customer-specific acceptance inspections
• E31 Individual certificate from Bureau Veritas (BV) (on request)
• E51 Individual certificate from DNV If acceptance inspections that are not covered by
the options F03, F71, F75, or F77 are required,
• E61 Individual certificate from American Bureau of Shipping customer-specific acceptance
(ABS) inspections/supplementary tests can be ordered
• E71 Individual certificate from China Classification Society using order code F97 on request and following
technical clarification.
(CCS)
Note:
Several individual certificates can be combined.

8/24 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S150 Converter Cabinet Units

Description of options

■ Options
G33 G61
CBE20 Communication Board Additional TM31 Terminal Module
The CBE20 Communication Board can be used to connect the With option G61, the number of digital inputs/outputs, as well as
SINAMICS S150 to a PROFINET IO, EtherNet/IP or Modbus TCP the number of analog inputs/outputs in the drive system can be
network via a CU320-2 Control Unit. The CBE Communication expanded using a second TM31 Terminal Module (in addition to
Board plugs into the option slot on the CU320-2 Control Unit. the TM31 Terminal Module that can be selected using option
G60).
It cannot be combined with option G20.
Note:
Note:
Option G61 requires option G60.
Only one communication interface can be used in isochronous
operation when the Communication Board CBE20 is used in a G62
Control Unit CU320-2. TB30 Terminal Board
• CU320-2 DP: Either the DP interface of the Control Unit or the The TB30 Terminal Board supports the addition of digital
PN interfaces of the CBE20 inputs/digital outputs and analog inputs/analog outputs to the
• CU320--2 PN: Either the internal PN interfaces or the external Control Unit. The TB30 Terminal Board plugs into the option slot
PN interfaces of the CBE20 on the Control Unit.
Description of the CBE20 Communication Board  System The following are located on the TB30 Terminal Board:
components  Supplementary system components. • Power supply for digital inputs/digital outputs
G51 • 4 digital inputs
TM150 temperature sensor evaluation unit • 4 digital outputs
The TM150 Terminal Module is a DRIVE-CLiQ component that is • 2 analog inputs
used to acquire and evaluate data from several temperature • 2 analog outputs
sensors. The temperature is measured in a temperature range
from -99 °C to +250 °C for the following temperature sensors: Description of the TB30 Terminal Board  System components
• Pt100 (with monitoring for wire breaks and short-circuits)  Supplementary system components.
• Pt1000 (with monitoring for wire breaks and short-circuits) K01
• KTY84 (with monitoring for wire breaks and short-circuits) Safety license Extended Functions for 1 axis
• PTC (with monitoring for short-circuits) The Safety Integrated Basic Functions do not require a license.
• Bimetallic NC contact (without monitoring) However, the Safety Integrated Extended Functions require a
license for each axis equipped with safety functions. It is
For the temperature sensor inputs, for each terminal block the irrelevant which safety functions are used and how many.
evaluation can be parameterized for 1×2-wire, 2×2-wire, 3-wire Option K01 contains the license for one axis.
or 4-wire. There is no galvanic isolation in the TM150.
Subsequent licensing is possible online via the WEB License
A maximum of 12 temperature sensors can be connected to the Manager by generating a license key:
TM150 Terminal Module.
www.siemens.com/automation/license
Description of the TM150 Terminal Module  System
components  Supplementary system components. K46
SMC10 Sensor Module Cabinet-Mounted
G60
TM31 Terminal Module The SMC10 Sensor Module Cabinet-Mounted can be used to 8
simultaneously sense the speed and the rotor position angle.
The TM31 Terminal Module is used to expand the customer The signals received from the resolver are converted here and
terminal. made available to the closed-loop controller via the DRIVE-CLiQ
interface for evaluation purposes.
The following additional interfaces are available:
• 8 digital inputs The following encoder signals can be evaluated:
• 4 bidirectional digital inputs/outputs • 2-pole resolver
• 2 relay outputs with changeover contact • Multi-pole resolver
• 2 analog inputs The motor temperature can also be measured using
• 2 analog outputs KTY84-130, Pt1000 or PTC thermistors.
• 1 temperature sensor input (KTY84-130/PTC) Description of the SMC10 Sensor Module Cabinet-Mounted 
System components  Encoder system interface.
• 2 DRIVE-CLiQ sockets
• 1 connection for the electronics power supply via the 24 V DC
supply connector
• 1 PE/protective conductor connection
To simplify configuration and commissioning of the drive, the
optional TM31 Terminal Module is already preset with various
factory settings, which can then be selected when
commissioning the system.
Description of the TM31 Terminal Module  System
components  Supplementary system components.
For additional information, please refer to the SINAMICS Low
Voltage Engineering Manual.

Siemens D 21.3 · 2022 8/25


© Siemens 2022

SINAMICS S150 Converter Cabinet Units

Description of options

■ Options
K48 K82
SMC20 Sensor Module Cabinet-Mounted Terminal Module for controlling the Safe Torque Off and Safe
Stop 1 safety functions
The SMC20 Sensor Module Cabinet-Mounted can be used to
simultaneously sense the speed and position. The signals The terminal module controls the Safety Integrated Basic
received from the incremental encoder are converted here and Functions Safe Torque Off (STO) and Safe Stop 1 (SS1)
made available to the closed-loop controller via the DRIVE-CLiQ (time-controlled) over a voltage of 24 V DC/AC (terminology as
interface for evaluation purposes. defined in IEC 61800-5-2). The relays used here are permitted
up to an installation altitude of 2000 m. The use of this option for
The following encoder signals can be evaluated: requirements that go beyond this is possible upon request.
• Incremental encoder sin/cos 1 Vpp
The integrated safety functions, starting from the Safety
• Absolute encoder EnDat 2.1 Integrated (SI) input terminals of the components (Control Unit
• SSI encoder with incremental signals sin/cos 1 Vpp and Power Module), satisfy the requirements of EN 61800-5-2,
EN 60204-1, EN ISO 13849-1 Category 3 for Performance Level
The motor temperature can also be detected using (PL) d and IEC 61508 SIL 2.
KTY84-130, Pt1000 or PTC thermistors.
With option K82, the requirements specified in EN 61800-5-2,
Description of the SMC20 Sensor Module Cabinet-Mounted  EN 60204-1, EN ISO 13849-1 Category 3 for Performance Level
System components  Encoder system interface. (PL) d and IEC 61508 SIL 2 are fulfilled.
K50 The Safety Integrated functions using option K82 are only
SMC30 Sensor Module Cabinet-Mounted available in conjunction with certified components and software
The SMC30 Sensor Module Cabinet-Mounted can be used to versions.
evaluate the encoders of motors without a DRIVE-CLiQ The Safety Integrated functions of SINAMICS are generally
interface. External encoders can also be connected via the certified by independent institutes. An up-to-date list of certified
SMC30. components is available on request from your local Siemens
The following encoder signals can be evaluated: office.
• Incremental encoders TTL/HTL with and without open-circuit K87
detection (open-circuit detection is only available with bipolar TM54F Terminal Module
signals)
The Terminal Module TM54F is a terminal expansion module with
• SSI encoders with TTL/HTL incremental signals safe digital inputs and outputs to control the Safety Integrated
• SSI encoders without incremental signals functions.
The motor temperature can also be measured using The TM54F is directly connected to a Control Unit via
KTY84-130, Pt1000 or PTC thermistors. DRIVE-CLiQ. Each Control Unit can be assigned precisely to
one TM54F.
Description of the SMC30 Sensor Module Cabinet-Mounted 
System components  Encoder system interface. Note:
K51 It is not permissible to connect Motor Modules or Line Modules
VSM10 Voltage Sensing Module to a TM54F.
The VSM10 Voltage Sensing Module is used to measure the The TM54F provides 4 fail-safe digital outputs and 10 fail-safe
voltage characteristic on the motor side, so that the following digital inputs. A fail-safe digital output consists of one 24 V DC
8 function can be implemented:
• Operation of a permanent-magnet synchronous motor without
switching output, one output switching to ground and one digital
input to check the switching state. A fail-safe digital input
encoder with the requirement to be able to connect to a motor consists of two digital inputs.
that is already running (flying restart function) Description of the TM54F Terminal Module  System
• Quick flying restart of large induction motors: The time for the components  Supplementary system components.
demagnetization of the motor is eliminated as a result of the
voltage sensing.
Description of the VSM10 Voltage Sensing Module  System
components  Supplementary system components.
K52
Second SMC30 Sensor Module Cabinet-Mounted
With option K50, the cabinet unit contains an SMC30 Sensor
Module Cabinet-Mounted. An additional SMC30 (option K52)
Sensor Module enables reliable actual-value acquisition when
using Safety Integrated extended functions (requires a license:
option K01).
Detailed and comprehensive instructions and information for the
Safety Integrated functions can be found in the associated
Function Manual.

8/26 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S150 Converter Cabinet Units

Description of options

■ Options
K88 L04
SBA Safe Brake Adapter, 230 V AC Infeed module one level lower
The Safe Brake Control (SBC) is a safety function that is used in With this option, an infeed (Active Line Module/Active Interface
safety-relevant applications, for example in presses or rolling Module) rated one power level lower than the Motor Module
mills. In the no-current state, the brake acts on the drive motor (inverter) is used.
using spring force. The brake is released when current flows in
it (low active). For instance, this option is suitable for the following applications:
• When the Motor Module is operated at pulse frequencies
The Safe Brake Adapter is already installed in the cabinet unit in greater than the rated pulse frequency, which means that the
the factory. A source of power is connected to terminal -X12 on output power is reduced (current derating as a function of the
the Safe Brake Adapter. For control, a connection is established pulse frequency).
between the Safe Brake Adapter and the Control Interface
Module in the factory using a cable harness. • When the rated power is demanded when generating, and the
system losses are covered by the Motor Module.
On the plant side, to control the brake, a connection must be • When using motors with a higher efficiency and/or a lower
established between terminal -X14 on the Safe Brake Adapter power factor when compared to typical standard induction
and the brake. motors.
Description of the SBA Safe Brake Adapter  System • The maximum current of the Motor Module is demanded
components  Supplementary system components. below the maximum power of the unit, e.g. drives with a high
K95 breakaway torque.
CU320-2 PN Control Unit (PROFINET) When using option L04, the following restrictions must always be
Instead of the CU320-2 DP (PROFIBUS) Control Unit provided taken into consideration:
as standard, the converter is delivered with a CU320-2 PN • The rated output current of the Motor Module is only available
Control Unit (PROFINET), including a CompactFlash card. as long as the infeed (Active Line Module) is not loaded with
the rated power.
Description of the CU320-2 Control Unit  System components
 Control Units. • For line undervoltage conditions, the output power is reduced
linearly with the line voltage.
L00 • The unit should be operated with a system power factor
Use in the first environment according to EN 61800-3, cos  = 1 (this is the factory setting) and should only provide
Category C2 the active power. Additional compensation of reactive power
(TN/TT supply systems with grounded neutral point) from the power system is not advisable.
To limit interference emission, the converter includes as Option L04 is available for the following cabinet units:
standard a radio interference suppression filter according to the
EMC product standard EN 61800-3, Category C3 (use in the SINAMICS S150 Type rating Permissible currents
industrial environment or in the second environment). converter cabinet at 400 V
unit
By using the optionally available line filter (option L00), up to a
Output Input
motor cable length of 300 m on grounded line supplies, the
converters are suitable for use according to Category C2 Standard With option
(residential area or first environment). L04
6SL3710-... kW A A A
However, complying with the limit values in the standard means
that all of the relevant installation specifications regarding
grounding and shielding must be strictly observed.
Line voltage 380 … 480 V 3 AC
7LE33-1AA3 160 310 310 260
8
Notes on this are provided in the SINAMICS Low Voltage 7LE35-0AA3 250 490 490 380
Engineering Manual as well as in the appropriate operating 7LE36-1AA3 315 605 605 490
instructions.
7LE37-5AA3 400 745 745 605
To allow the shield of the power cables to be connected in
7LE41-0AA3 560 985 985 840
conformance with EMC requirements, an additional EMC shield
bus (option M70) is installed at the converter input and output.
A separate order is not required in this case.

Siemens D 21.3 · 2022 8/27


© Siemens 2022

SINAMICS S150 Converter Cabinet Units

Description of options

■ Options
L07 Note:
dv/dt filter compact plus Voltage Peak Limiter Option L08 cannot be combined with the following options:
dv/dt filters compact plus VPL (Voltage Peak Limiter) limit the • L07 (dv/dt filter compact plus VPL)
voltage rate of rise dv/dt to values of < 1600 V/s and the typical • L10 (dv/dt filter plus VPL)
peak voltage to the following values in accordance with the limit • L15 (sine-wave filter)
value curve A according to IEC 60034-25: 2007:
• M78 (motor connection from above)
• < 1150 V at Uline < 575 V
• < 1400 V at 660 V < Uline < 690 V L10
dv/dt filter plus Voltage Peak Limiter
The dv/dt filter compact plus VPL functionally consists of two
components that are supplied as a compact mechanical unit, A dv/dt filter plus VPL (Voltage Peak Limiter) limits the voltage
the dv/dt reactor and the voltage limiting network (VPL), which rate of rise dv/dt to values < 500 V/s and the typical peak
limits voltage peaks and feeds back the energy to the DC link. voltage to the following values in accordance with the limit value
curve according to IEC/TS 60034-17: 2006:
It is so compact that it can be completely integrated into the
cabinet, even for high power ratings. An additional cabinet is not • < 1000 V at Uline < 575 V
required. • <1250 V at 660 V < Uline < 690 V
By using a dv/dt filter compact plus VPL, standard motors with The dv/dt filter plus VPL functionally consists of two components,
standard insulation and without insulated bearings can be used the dv/dt reactor and the voltage limiting network (VPL), which
with supply voltages up to 690 V in converter operation. limits voltage peaks and feeds the energy back to the DC link.
The power losses stated in Section System components  Depending on the converter power, option L10 can be
Motor-side components  dv/dt filter compact plus VPL can be accommodated in the converter cabinet unit or an additional
used to determine the total losses for engineering purposes. cabinet is required with a width of 400 mm or 600 mm.
dv/dt filters compact plus VPL are designed for the following Voltage Installation of the dv/dt filter plus VPL
maximum motor cable lengths: range
• Shielded cables 100 m (e.g. Protodur NYCWY) in the converter in the additional cabinet
• Unshielded cables 150 m (e.g. Protodur NYY) (without additional 400 mm wide 600 mm wide
cabinet)
For longer cable lengths (> 100 m shielded, >150 m
380 ... 480 V 110 ... 250 kW 315 ... 450 kW 560 ... 800 kW
unshielded), the dv/dt filter plus VPL (option L10) should be
used. 500 ... 690 V 75 ... 315 kW 400 ... 560 kW 710 ... 1200 kW

Notice: By using a dv/dt filter plus VPL, standard motors with standard
• Operation with output frequencies <10 Hz is permissible insulation and without insulated bearings can be used with
for max. 5 min. supply voltages up to 690 V in converter operation.
• The maximum permissible output frequency is 150 Hz. dv/dt filters plus VPL are designed for the following maximum
motor cable lengths:
When using dv/dt filters, restrictions regarding permissible pulse
frequencies must be observed. • Shielded cables 300 m (e.g. Protodur NYCWY)
• Unshielded cables: 450 m (e.g. Protodur NYY)
For additional information, please refer to the SINAMICS Low
Voltage Engineering Manual. For cable lengths < 100 m shielded or < 150 m unshielded, the
8 Note:
dv/dt filter compact plus VPL (option L07) can be used
advantageously.
Option L07 cannot be combined with the following options:
The power losses stated in Section System components 
• L08 (motor reactor) Motor-side components  dv/dt filter plus VPL can be used to
• L10 (dv/dt filter plus VPL) determine the total losses for engineering purposes.
• L15 (sine-wave filter) Notice:
• M78 (motor connection from above) The maximum permissible output frequency is 150 Hz.
L08 When using dv/dt filters, restrictions regarding permissible pulse
Motor reactor frequencies must be observed.
Motor reactors reduce the voltage load on the motor windings by For additional information, please refer to the SINAMICS Low
reducing the voltage gradients at the motor terminals that occur Voltage Engineering Manual.
during converter operation. At the same time, the capacitive
charge/discharge currents that place an additional load on the Note:
converter output when using long motor cables, are reduced. Parts of option L10 do not have nickel-plated copper busbars.
The maximum permissible output frequency when a motor Option L10 cannot be combined with the following options:
reactor is used is 150 Hz.
• L07 (dv/dt filter compact plus VPL)
The power losses stated in Section System components  • L08 (motor reactor)
Motor-side components  Motor reactors can be used to
determine the total losses for engineering purposes. • L15 (sine-wave filter)
• M78 (motor connection from above)

8/28 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S150 Converter Cabinet Units

Description of options

■ Options
L15 L21
Sine-wave filter Surge suppression
Sine-wave filters are available for converters with a power rating In ungrounded IT systems, the line voltage is not permanently
of up to 250 kW (380 V to 480 V). The sine-wave filter at the connected to the ground potential because of the missing
converter output supplies almost perfect sinusoidal voltages at ground connection of the supply network. Therefore, when a
the motor so that standard motors can be used without special ground fault occurs during operation, a voltage against ground
cables or power derating. Standard cables can be used to increased by a factor of 2 can occur. For this reason,
connect the motor. The max. permissible motor cable length it is recommended that a surge suppression against ground be
is limited to 300 m. installed for operation on IT systems. The surge suppression
option includes the installation of line-side surge arresters and
The power losses stated in Section System components  upstream fuses for each system phase. The signaling contacts
Motor-side components  Sine-wave filter can be used to for monitoring the surge arresters are connected in series and
determine the total losses for engineering purposes. connected to a customer interface.
Note: Note:
In conjunction with the option L15, the pulse frequency of the
converter must be increased. This reduces the power available Option L21 does not include the components required to install
at the converter output (derating factor 0.88). The modulation an insulation monitor for the IT system. An insulation monitor
depth of the output voltage decreases to approx. 85% should always be ordered separately as option L87 when the
(380 V to 480 V). The maximum output frequency is 150 Hz. supplying IT system is not monitored at another position
It should be noted that the reduced voltage at the motor (e.g. at the transformer outgoing feeder). Only one insulation
terminals compared with the rated motor voltage means that the monitor can ever be used within the same electrically connected
motor switches to field weakening mode earlier. network.
Note: Option L21 also does not include removal in the factory of the
metal bracket that makes the connection to ground of the radio
Option L15 cannot be combined with the following options: interference suppression filter installed as standard. The metal
• L07 (dv/dt filter compact plus VPL) bracket should therefore be removed during installation or
• L08 (motor reactor) commissioning of the converter if the device is to be operated on
an ungrounded IT system.
• L10 (dv/dt filter plus VPL)
• M78 (motor connection from above) L26
Main switch incl. fuses or circuit breakers
L19
Connection for external auxiliary equipment Up to 800 A a switch disconnector with fuses is available as the
main switch. For currents greater than 800 A, a circuit breaker
An outgoing feeder fused with max. 10 A for external auxiliary provided as standard is used to isolate the drive system from the
equipment (for example, separately driven motor fan). line supply. The circuit breaker is controlled and supplied within
The voltage is tapped at the converter input upstream of the the converter.
main contactor / circuit breaker and, therefore, has the same Terminal Meaning
level as the supply voltage. -X50:
The outgoing feeder can be switched inside the converter or 1 Checkback contact (NO contact)
externally. Main breaker/circuit breaker closed
2 Checkback contact (NC contact)
Terminal
-X155:
Meaning Range

3
Main breaker/circuit breaker closed
Common potential
8
1 L1 380 ... 690 V AC
2 L2 380 ... 690 V AC L40
Line filter monitoring
3 L3 380 ... 690 V AC
11 Contactor control 230 V AC With option L40, the filter in the Active Interface Module is
monitored for effectiveness against harmonic effects on the
12 Contactor control 230 V AC system.
13 Feedback signal, circuit 230 V AC/0.5 A;
breaker 24 V DC/2 A The capacitance of the filter capacitors of the integrated filter is
continuously calculated and compared with the installed
14 Feedback signal, circuit 230 V AC/0.5 A; nominal capacitance by measuring the current and voltage in
breaker 24 V DC/2 A
the Active Interface Module. If the calculated capacity deviates
15 Feedback signal, con- 230 V AC/6 A by more than the set tolerance, an alarm is triggered.
tactor
16 Feedback signal, con- 230 V AC/6 A
tactor
PE PE –

For more information on configuring, see:


https://support.industry.siemens.com/cs/document/104961375

Siemens D 21.3 · 2022 8/29


© Siemens 2022

SINAMICS S150 Converter Cabinet Units

Description of options

■ Options
L45 L57
EMERGENCY OFF pushbutton, installed in the cabinet door EMERGENCY OFF Category 0
The option L45 only includes the EMERGENCY OFF pushbutton EMERGENCY OFF Category 0 for uncontrolled stopping
which is fitted with a protective collar in the cabinet door of the according to EN 60204-1.
converter. The contacts of the pushbutton are brought out and
connected to a terminal strip. The function includes disconnecting the voltage at the converter
by means of the line contactor and bypassing the microproces-
The EMERGENCY OFF and/or EMERGENCY STOP functions of sor controller using a safety combination according to
Category 0 or 1 can be activated in conjunction with options EN 60204-1. The motor then coasts down.
L57, L59, and L60.
Terminal Meaning
Terminal Meaning -X120:
-X120: 7 Loop in the EMERGENCY OFF pushbutton from the plant
1 Checkback contact of the EMERGENCY OFF pushbutton in side; remove jumper 7-8!
the cabinet door 8 Loop in the EMERGENCY OFF pushbutton from the plant
2 Checkback contact of the EMERGENCY OFF pushbutton in side; remove jumper 7-8!
the cabinet door 15 "ON" for monitored start; remove jumper 15-16!
3 Checkback contact of the EMERGENCY OFF pushbutton in 16 "ON" for monitored start; remove jumper 15-16!
the cabinet door 1)
17 Checkback signal, "Safety combination has tripped"
4 Checkback contact of the EMERGENCY OFF pushbutton in
the cabinet door 1) 18 Checkback signal, "Safety combination has tripped"

Notice: L59
By pressing the EMERGENCY OFF pushbutton, the motor is EMERGENCY STOP Category 1, 230 V AC
stopped either uncontrolled or controlled depending on the
selected stop Category 0 or 1, and the main voltage EMERGENCY STOP Category 1 for controlled stopping
disconnected from the motor, in compliance with IEC 60204-1 according to EN 60204-1.
(VDE 0113). Auxiliary voltages such as the supply for an external The function stops the drive using a fast stop along a down ramp
fan or anti-condensation heating may still be present. Certain that is parameterized by the user. The voltage is then
areas within the converter also remain live (under voltage), such disconnected as described for EMERGENCY OFF Category 0
as the control or auxiliary equipment. If complete disconnection (option L57).
of all voltages is required, the EMERGENCY OFF pushbutton
must be incorporated into a protective system to be In order to maintain the specified stopping times, it may be
implemented by the customer. For this purpose, an NC contact necessary to use a braking unit.
is provided at terminal -X120.
Terminal Meaning
L50 -X120:
Cabinet lighting with service socket 7 Loop in the EMERGENCY OFF pushbutton from the plant
side; remove jumper 7-8!
With option L50, cabinet lighting is included with an additional
service socket for a SCHUKO connector (connector type F) 8 Loop in the EMERGENCY OFF pushbutton from the plant
side; remove jumper 7-8!
according to CEE 7/4. The power supply for the cabinet lighting
and the service socket is external and must be fuse-protected 15 "ON" for manual start; remove jumper 15-16!
for max. 10 A. 16 "ON" for manual start; remove jumper 15-16!
8 The cabinet lighting consists of an LED hand lamp with On/Off
switch and with magnetic fasteners with an approx. 3 m long
17 Checkback signal, "Safety combination has tripped"
18 Checkback signal, "Safety combination has tripped"
connecting cable. The lamp is factory-positioned in the cabinet
door at a defined marking, and the connecting cable is wound
on the associated mount.
L55
Cabinet anti-condensation heating
The anti-condensation heating is recommended at low
ambient temperatures and high levels of humidity to prevent
condensation. A 100 W cabinet heater is installed in each
cabinet section (two heaters are installed per cabinet with
cabinet section widths of between 800 mm and 1200 mm).
The power supply for the anti-condensation heating (110 V to
230 V AC, at terminal strip -X240) must be provided externally
and fused with max. 16 A.
Terminal Meaning
-X240:
1 L1 (110 ... 230 V AC)
2 N
3 PE

1)
For option L57 to L60 is preassigned in the converter.

8/30 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S150 Converter Cabinet Units

Description of options

■ Options
L60 The following braking units are available for SINAMICS S150
EMERGENCY STOP Category 1, 24 V DC converter cabinet units:
EMERGENCY STOP Category 1 for controlled stopping Option SINAMICS Braking Module
according to EN 60204-1. S150
converter
The function stops the drive using a fast stop along a down ramp
that is parameterized by the user. The voltage is then Type rating Rated power Braking power Peak power
PDB P20 P15
disconnected as described for EMERGENCY OFF Category 0
(option L57). kW kW kW kW

In order to maintain the specified stopping times, it may be 380 ... 480 V 3 AC
necessary to use a braking unit. L61 110 ... 132 25 100 125
L62 160 ... 800 50 200 250
Terminal Meaning
-X120: 500 ... 600 V 3 AC
7 Loop in the EMERGENCY OFF pushbutton from the plant L64 75 ... 132 25 100 125
side; remove jumper 7-8!
L65 160 ... 1200 50 200 250
8 Loop in the EMERGENCY OFF pushbutton from the plant
side; remove jumper 7-8! 660 ... 690 V 3 AC

15 "ON" for manual start; remove jumper 15-16! L61 75 ... 132 25 100 125

16 "ON" for manual start; remove jumper 15-16! L62 160 ... 1200 50 200 250

17 Checkback signal, "Safety combination has tripped" PDB = Rated power (continuous braking power)
18 Checkback signal, "Safety combination has tripped" P20 = 4 × PDB: 20 s power referred to a braking interval of 90 s
L61, L62, L64, L65 P15 = 5 × PDB: 15 s power referred to a braking interval of 90 s
Braking units
If more braking power is required than provided by the braking
Braking units may be required for drives in which motors might units listed here, then braking units may be connected in parallel
operate in generator mode, but have no facility for feeding for higher converter outputs (on request). In this case, a Braking
energy back into the supply system. Module is assigned to each braking resistor.
The braking unit comprises two components:
• A Braking Module that can be installed in the air discharge of P/P20 G_D011_EN_00328

the chassis format power units


• A braking resistor to be mounted externally (degree of
protection IP20) 1.50
The braking unit functions as an autonomous unit, and does not 1.25 P15
require an external power supply. During the braking process,
the kinetic energy is converted into heat in the externally 1.00 P20
mounted braking resistor.
0.75
A max. cable length of 100 m is permissible between the
Braking Module and the braking resistor. This allows the braking 0.50 P40
resistor to be mounted externally so that heat losses can be
dissipated outside the converter enclosure. The braking resistor 0.25
PDB
8
is connected directly to the terminal -X5 of the converter. 0
10 15 20 30 40 50 60 70 80 90 100 s t

PDB = Rated power


P15 = 5 x PDB = Power which is permissible every 90 s for 15 s
P20 = 4 x PDB = Power which is permissible every 90 s for 20 s
P40 = 2 x PDB = Power which is permissible every 90 s for 40 s

Load diagram for Braking Modules and braking resistors


Additional notes about possible duty cycles of the braking
resistors and other engineering notes are included in the
SINAMICS Low Voltage Engineering Manual.

Siemens D 21.3 · 2022 8/31


© Siemens 2022

SINAMICS S150 Converter Cabinet Units

Description of options

■ Options
L83 M07
Thermistor motor protection device (alarm) Cable marshaling space 200 mm high, RAL 7035
Thermistor motor protection device for PTC thermistors The cable marshaling space is made of strong sheet steel and
(PTC resistors, type A) for alarm. The thermistor motor protection allows cables to be connected more flexibly (entry from below).
device is supplied with power and evaluated internally in the It also allows routing of cables within the marshaling space.
converter. It is delivered completely assembled with the cabinet.
The height of the operator panel changes accordingly.
Terminal Meaning
-B127: Notice:
T1 Sensor circuit connection
The cable marshaling space is painted as standard with
RAL 7035. If a special color is requested for the cabinet
T2 Sensor circuit connection (option Y09), the cable marshaling space is also painted in
this color.
L84 Combination with option M66 is not possible.
Thermistor motor protection device (trip)
Thermistor motor protection device for PTC thermistors M13
(PTC resistors, type A) for trip. The thermistor motor protection Line connection from above
device is supplied with power and evaluated internally in the The control cabinet is provided with an additional roof section to
converter. allow a line connection from above. The connection lugs for the
power cables, the clamping bar for mechanically securing the
Terminal Meaning cables, an EMC shield bus, and a PE busbar are located within
-B125:
this roof section.
T1 Sensor circuit connection
This increases the cabinet height by 405 mm. The busbars for
T2 Sensor circuit connection the connection from above are delivered completely
L86 pre-installed. For transport reasons, the roof sections are
Pt100 evaluation unit delivered separately and must be fitted on site. Crane transport
assemblies (option M90) can still be used. However, they must
The Pt100 evaluation unit can monitor up to six sensors. be removed on site before the roof sections can be installed.
The sensors can be connected in a two or three-wire system. Use of rope spreaders should be considered in the case of small
The limit values can be freely programmed for each channel. crane hook heights.
In the factory setting, the measuring channels are subdivided An undrilled aluminum mounting plate (5 mm thick) is provided
into two groups, each with 3 channels. With motors, for example, in the roof section for feeding in the cables. Depending on the
this means that three Pt100s in the stator windings and two number of cables and the cross-sections used, holes for
Pt100s in the motor bearings can be monitored. Unused attaching cable glands for feeding in the cables must be drilled
channels can be hidden via parameters. in this mounting plate on site.
The output relays are integrated into the internal fault and Note:
shutdown sequence of the converter. The control cables are still connected from below. Option M13
eliminates the lugs, provided as standard, to connect the line
L87 supply from below.
Insulation monitoring
The degree of protection of the roof sections is IP21. In combi-
An insulation monitor must be used if the converter is connected nation with options M23, M43 and M54, additional plastic
8 to an ungrounded line supply. The device monitors the entire
galvanically coupled circuit for insulation faults.
ventilation grilles and filter elements are provided.
Notice:
An alarm is output in the event of a fault. The roof sections are painted in RAL 7035 as standard. If a
Notice: special color is requested for the cabinet (option Y09), the roof
section is also painted in this color. Ventilation grilles used with
Only one insulation monitor can be used in each galvanically degrees of protection IP23 and IP54 have color RAL 7035 and
coupled network. cannot be painted.
As there are different response strategies when a ground fault The covers provided with option M60 are also included in the
occurs in an ungrounded system, output relays of the insulation scope of supply.
monitor are provided for integration in a plant-side control.
The customer can also choose to integrate the outputs into the
converter monitoring system.
M06
Base 100 mm high, RAL 7022
The additional cabinet base allows larger bending radii for
cables (cable inlet from below) and enables them to be routed
within the cabinet base.
The cabinet base is supplied in RAL 7022 as standard. A special
paint finish is not available for the base. It is delivered completely
assembled with the cabinet. The height of the operator panel
changes accordingly.
Combination with option M66 is not possible.

8/32 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S150 Converter Cabinet Units

Description of options

■ Options
M21 M54
Degree of protection IP21 Degree of protection IP54
Cabinet version in IP20, but with additional top cover or canopy. Converter cabinet units with IP54 degree of protection
This increases the cabinet height by 250 mm. are supplied with additional roof sections as well as plastic
ventilation grilles and a filter medium in the air inlet and outlet.
For transport reasons, the top covers or canopies are delivered This increases the cabinet height by 400 mm. The covers
separately and must be fitted on site. provided with option M60 are also included in the scope of
Notice: supply. They are an integral component of the internal cabinet air
guidance system and are adapted accordingly. The filters must
The top covers or canopies are painted in RAL 7035 as be maintained according to the local environmental conditions.
standard. If a special color is requested for the cabinet
(option Y09), the top covers or canopies are also painted in this For transport reasons, the roof sections are delivered separately
color. and must be fitted on site.
M23 Notice:
Degree of protection IP23 • The roof sections are painted in RAL 7035 as standard.
Converter cabinet units with degree of protection IP23 are If a special color is requested for the cabinet (option Y09),
supplied with additional roof sections as well as plastic the roof section is also painted in this color. The molded plastic
ventilation grilles and a filter medium in the air inlet and outlet. parts (e.g. ventilation grilles) are in RAL 7035 and cannot be
This increases the cabinet height by 400 mm. The covers painted.
provided with option M60 are also included in the scope • For units with IP54 degree of protection, it is important to
of supply. The filter medium must be maintained according to the observe the derating factor for output currents in relation to
local environmental conditions. ambient temperature and installation altitude.
For transport reasons, the roof sections are delivered separately M60
and must be fitted on site. Additional touch protection
Notice: The converter cabinet units are designed as standard according
The roof sections are painted in RAL 7035 as standard. to DGUV regulation 3. Option M60 provides additional covers
If a special color is requested for the cabinet (option Y09), the (outside arm's reach) in the vicinity of the AC busbars and above
roof section is also painted in this color. The molded plastic parts the power unit (can only be selected as an option with
(e.g. ventilation grilles) are in RAL 7035 and cannot be painted. converters up to 250 kW in the 400 V range and with converters
up to 315 kW in the 690 V range with degrees of protection IP20
M43 and IP21; otherwise supplied as standard).
Degree of protection IP43
M66
Converter cabinet units with IP43 degree of protection Marine version
are supplied with additional roof sections as well as plastic ven-
tilation grilles and a wire mesh in the air inlet and outlet. For compliance with the requirements of the classification
This increases the cabinet height by 400 mm. The covers institutes:
provided with option M60 are also included in the scope of • Lloyds Register
supply. They are an integral component of the internal cabinet air
guidance system and are adapted accordingly. • American Bureau of Shipping
• Germanischer Lloyd
For transport reasons, the roof sections are delivered separately
• Bureau Veritas
and must be fitted on site.
Notice: • Det Norske Veritas 8
The roof sections are painted in RAL 7035 as standard. • China Classification Society
If a special color is requested for the cabinet (option Y09), This option includes a strengthened mechanical version of the
the roof section is also painted in this color. The molded plastic cabinet, handles (handrail) below the operator panel and
parts (e.g. ventilation grilles) are in RAL 7035 and cannot mechanical locking of the cabinet doors. The cabinet has
be painted. degree of protection IP23 (option M23) and includes a cabinet
anti-condensation heater (option L55). To secure the converter
to the ship's hull, a welding frame (5 mm high) is supplied
separately.
Note:
Combination with options M21, M23, and L55 is not possible.
Individual certification is additionally required if the converter is
used for a safety-related drive on the ship
(see options E21 to E71).

Siemens D 21.3 · 2022 8/33


© Siemens 2022

SINAMICS S150 Converter Cabinet Units

Description of options

■ Options
M70 M90
EMC shield bus (cable connection from below) Crane transport assembly (top-mounted)
The EMC shield bus is used to connect shielded power cables For single cabinets up to a width of 600 mm, the crane transport
for line and motor supply cables. assembly consists of transport eyebolts. For cabinet widths of
800 mm and wider, transport rails are used.
With the options M13 and M78, the EMC shield bus is already
included as standard for the connection busbars underneath the M91
roof section. Marking of all control cable conductor ends
With the option L00 (RFI suppression filter), the EMC shield bus
is also included as standard. When this option is selected, all control cables or conductor
ends (including all customer-specific options) are labeled
M78 throughout the cabinet.
Motor connection from above
T58, T60, T80, T83, T85, T91
The control cabinet is provided with an additional roof section for Rating plate data
a motor connection from above. The connection lugs for the
power cables, the clamping bar for mechanically securing the The rating plate is provided in English/German as standard.
cables, an EMC shield bus, and a PE busbar are located within A rating plate in another language combination can be selected
this roof section. by specifying the following option order codes.

This increases the cabinet height by 405 mm. The busbars for Option Rating plate language
the connection from above are delivered completely T58 English/French
pre-installed. For transport reasons, the roof sections are
T60 English/Spanish
delivered separately and must be fitted on site. Crane transport
assemblies (option M90) can still be used. However, they must T80 English/Italian
be removed on site before the roof sections can be installed. T83 English/Portuguese (Brazil)
Use of rope spreaders should be considered in the case of small
crane hook heights. T85 English/Russian
T91 English/Chinese
An undrilled aluminum mounting plate (5 mm thick) is provided
in the roof section for feeding in the cables. Depending on the Y09
number of cables and the cross-sections used, holes for Special cabinet paint finish
attaching cable glands for feeding in the cables must be drilled
in this mounting plate on site. The converter cabinet units are delivered in RAL 7035 as
standard. The special paint finish must be specified in plain text
Note: when ordering. All RAL colors which are available as powder
The control cables are still connected from below. Option M78 coatings can be selected. Other special colors on request.
eliminates the lugs, provided as standard, to connect the motor
from below. Notice:
If options such as cable marshaling space (option M07),
The degree of protection of the roof sections is IP21. top covers or canopies (option M21), roof sections
In combination with options M23, M43 and M54, additional (options M23/M43/M54) or cable connection from above
plastic ventilation grilles and filter elements are provided. (options M13/M78) are ordered for the converter cabinet units,
Notice: they will also be supplied in the paint finish specified for the
The roof sections are painted in RAL 7035 as standard. cabinet in the order. The molded plastic parts (e.g. ventilation
If a special color is requested for the cabinet (option Y09), grilles) are in RAL 7035 and cannot be painted.
8 the roof section is also painted in this color. Ventilation grilles
used with IP23, IP43 and IP54 degrees of protection are in
RAL 7035 and cannot be painted.
The covers provided with option M60 are also included in the
scope of supply.
Note:
Option M78 cannot be combined with the following options:
• L07 (dv/dt filter compact plus VPL)
• L08 (motor reactor)
• L10 (dv/dt filter plus VPL)
• L15 (sine-wave filter)

8/34 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S150 Converter Cabinet Units

Description of options

■ Options
Y31
One-line label for system identification, 40 × 80 mm
Resopal labels (white with black lettering) for identifying
the control cabinets are available. The labels are stuck
to the cabinet door.
Dimensions H × W: 40 × 80 mm
The text must be specified in plain text when ordering.
Field 1: Max. 9 characters, font size 10 mm

+D4Z01R04 40

Field 1

80

Y32
Two-line label for system identification, 40 × 180 mm
Resopal labels (white with black lettering) for identifying
the control cabinets are available. The labels are stuck
to the cabinet door.
Dimensions H × W: 40 × 180 mm
The text must be specified in plain text when ordering.
Field 1: Max. 9 characters, font size 10 mm
Field 2: Max. 9 characters, font size 10 mm
Field 3: Max. 20 characters, font size 10 mm

90

+D4Z01R04 -31FA011
Field 1 Field 2
40

Field 3
infeed roller FS
180

Y33
Four-line label for system identification, 40 × 180 mm
Resopal labels (white with black lettering) for identifying
8
the control cabinets are available. The labels are stuck
to the cabinet door.
Dimensions H × W: 40 × 180 mm
The text must be specified in plain text when ordering.
Field 1: Max. 9 characters, font size 10 mm
Field 2: Max. 20 characters, font size 6 mm
Field 3: Max. 20 characters, font size 6 mm
Field 4: Max. 20 characters, font size 6 mm
Field 5: Max. 20 characters, font size 6 mm

80

-31 FA011 Short text 1 Field 2


-31FA012 Short text 2 Field 3
+D4Z01R04 -31FA013 Short text 3 Field 4
40

Field 1 -31FA014 Short text 4 Field 5


180

Siemens D 21.3 · 2022 8/35


© Siemens 2022

SINAMICS S150 Converter Cabinet Units

Line-side components - recommended fuses

■ Overview
The fuses specified below are the recommended types for pro- In this case, a 3NA fuse can be used in the distribution board. If
tecting the unit on the low-voltage distribution panel. If option option L26 has not been selected for units <800 A, we strongly
L26 was selected for SINAMICS S150 with rated input currents advise that 3NE fuses are used 1).
<800 A, then the semiconductor protection is already integrated
in the unit. For units of >800 A, this function is performed by the Catalog LV 10 contains additional information on the listed fuses.
circuit breaker provided as standard.
Type rating SINAMICS S150 Cable protection fuse Cable protection fuse
at 400 V or 690 V converter in systems with a fuse switch disconnector (incl. semiconductor protection)
in systems without fuse switch disconnector
At IL, 50 Hz At IL, 60 Hz Rated current Size according Rated current Size according
400 V, 500 V 460 V to DIN 43620-1 to DIN 43620-1
or 690 V or 575 V
kW hp 6SL3710-... Article No. A Article No. A
Line voltage 380 ... 480 V 3 AC
110 150 7LE32-1AA3 3NA3252 315 2 3NE1230-2 315 1
132 200 7LE32-6AA3 3NA3254 355 2 3NE1331-2 350 2
160 250 7LE33-1AA3 3NA3365 500 3 3NE1334-2 500 2
200 300 7LE33-8AA3 3NA3365 500 3 3NE1334-2 500 2
250 400 7LE35-0AA3 3NA3372 630 3 3NE1436-2 630 3
315 500 7LE36-1AA3 3NA3475 800 4 3NE1438-2 800 3
400 600 7LE37-5AA3 3NA3475 800 4 3NE1448-2 850 3
450 700 7LE38-4AA3 – – – Circuit breaker included as standard
560 800 7LE41-0AA3 – – – Circuit breaker included as standard
710 1000 7LE41-2AA3 – – – Circuit breaker included as standard
800 1000 7LE41-4AA3 – – – Circuit breaker included as standard
Line voltage 500 ... 690 V 3 AC
75 75 7LG28-5AA3 3NA3132-6 125 1 3NE1022-2 125 00
90 75 7LG31-0AA3 3NA3132-6 125 1 3NE1022-2 125 00
110 100 7LG31-2AA3 3NA3136-6 160 1 3NE1224-2 160 1
132 150 7LG31-5AA3 3NA3240-6 200 2 3NE1225-2 200 1
160 150 7LG31-8AA3 3NA3244-6 250 2 3NE1227-2 250 1
200 200 7LG32-2AA3 3NA3252-6 315 2 3NE1230-2 315 1
250 250 7LG32-6AA3 3NA3354-6 355 3 3NE1331-2 350 2
315 300 7LG33-3AA3 3NA3365-6 500 3 3NE1334-2 500 2
400 400 7LG34-1AA3 3NA3365-6 500 3 3NE1334-2 500 2
8 450 450 7LG34-7AA3 3NA3352-6 2 × 315 2 3NE1435-2 560 3
560 600 7LG35-8AA3 3NA3354-6 2 × 355 3 3NE1447-2 670 3
710 700 7LG37-4AA3 3NA3365-6 2 × 500 3 3NE1448-2 850 3
800 800 7LG38-1AA3 – – – Circuit breaker included as standard
900 900 7LG38-8AA3 – – – Circuit breaker included as standard
1000 1000 7LG41-0AA3 – – – Circuit breaker included as standard
1200 1250 7LG41-3AA3 – – – Circuit breaker included as standard

1)
The double-function fuses (3NE1.) for cable and semiconductor protection
are recommended to protect the converter. These fuses are specially
adapted to the requirements of the semiconductors in the input rectifier.
- Super fast
- Lower arc voltage
- Improved current limiting (lower let-through values).

8/36 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S150 Converter Cabinet Units

Cable cross-sections and connections

■ Overview
The following tables list the recommended and maximum at an ambient temperature of 40 °C and individual routing.
connectable line and motor-side cable cross-sections and For deviating conditions (cable routing, cable accumulation,
connections for a single connection. ambient temperature), the appropriate correction factors
according to IEC 60364-5-52 must be taken into account.
The recommended cross-sections are based on the specified
fuses. They are valid for a three-conductor copper cable routed For additional information, please refer to the SINAMICS Low
horizontally in air with PVC insulation and a permissible Voltage Engineering Manual.
conductor temperature of 70 °C (e.g. Protodur NYY or NYCWY)
Type rating at SINAMICS S150 Line supply connection Motor connection Cabinet grounding
400 V converter
or 690 V cabinet unit
Recom- Maximum M12 fixing Recom- Maximum M12 fixing M12 fixing Remarks
mended conductor screw mended conductor screw screw
cross- cross-section cross- cross-section
section 1) section 1)
IEC IEC (Number of IEC IEC (Number of (Number of
holes) holes) holes)
kW 6SL3710-... mm2 mm2 mm2 mm2
380 ... 480 V 3 AC
110 7LE32-1AA3 2 × 70 4 × 240 (2) 2 × 50 2 × 150 (2) (2)
132 7LE32-6AA3 2 × 95 4 × 240 (2) 2 × 70 2 × 150 (2) (2)
160 7LE33-1AA3 2 × 120 4 × 240 (2) 2 × 95 2 × 150 (2) (2)
200 7LE33-8AA3 2 × 120 4 × 240 (2) 2 × 95 2 × 150 (2) (2)
250 7LE35-0AA3 2 × 185 4 × 240 (2) 2 × 150 2 × 240 (2) (2)
315 7LE36-1AA3 2 × 240 4 × 240 (2) 2 × 185 4 × 240 (2) (2)
400 7LE37-5AA3 3 × 185 4 × 240 (2) 2 × 240 4 × 240 (2) (10) Cu bar
450 7LE38-4AA3 4 × 150 8 × 240 (4) 3 × 185 4 × 240 (2) (16) Cu bar
560 7LE41-0AA3 4 × 185 8 × 240 (4) 4 × 185 6 × 240 (3) (18) Cu bar
710 7LE41-2AA3 4 × 240 8 × 240 (4) 4 × 240 6 × 240 (3) (18) Cu bar
800 7LE41-4AA3 6 × 185 8 × 240 (4) 6 × 185 6 × 240 (3) (18) Cu bar
500 … 690 V 3 AC
75 7LG28-5AA3 50 4 × 240 (2) 35 2 × 70 (2) (2)
90 7LG31-0AA3 50 4 × 240 (2) 50 2 × 150 (2) (2)
110 7LG31-2AA3 70 4 × 240 (2) 70 2 × 150 (2) (2)
132 7LG31-5AA3 95 4 × 240 (2) 70 2 × 150 (2) (2)
160 7LG31-8AA3 120 4 × 240 (2) 95 2 × 150 (2) (2)
200 7LG32-2AA3 2 × 70 4 × 240 (2) 120 2 × 150 (2) (2)
250 7LG32-6AA3 2 × 95 4 × 240 (2) 2 × 70 2 × 185 (2) (2) 8
315 7LG33-3AA3 2 × 120 4 × 240 (2) 2 × 95 2 × 240 (2) (2)
400 7LG34-1AA3 2 × 185 4 × 240 (2) 2 × 120 4 × 240 (2) (2)
450 7LG34-7AA3 2 × 185 4 × 240 (2) 2 × 150 4 × 240 (2) (2)
560 7LG35-8AA3 2 × 240 4 × 240 (2) 2 × 185 4 × 240 (2) (2)
710 7LG37-4AA3 3 × 185 8 × 240 (4) 3 × 150 6 × 240 (3) (18) Cu bar
800 7LG38-1AA3 4 × 150 8 × 240 (4) 3 × 185 6 × 240 (3) (18) Cu bar
900 7LG38-8AA3 4 × 150 8 × 240 (4) 4 × 150 6 × 240 (3) (18) Cu bar
1000 7LG41-0AA3 4 × 185 8 × 240 (4) 4 × 185 6 × 240 (3) (18) Cu bar
1200 7LG41-3AA3 4 × 240 8 × 240 (4) 4 × 240 6 × 240 (3) (18) Cu bar

1) The recommendations for the North American market in AWG or MCM


must be taken from the appropriate NEC (National Electrical Code)
and CEC (Canadian Electrical Code) standards.

Siemens D 21.3 · 2022 8/37


© Siemens 2022

SINAMICS S150 Converter Cabinet Units

Cable cross-sections and connections

■ Overview
Cable cross-sections for line and motor connection Cables must be connected in parallel for higher currents.
It is generally recommended to use shielded 3-conductor three- Note:
phase cables between the converter and motor – and for higher The recommendations for the North American market in AWG
power ratings, symmetrical cables where possible. If required, or MCM must be taken from the appropriate NEC (National
several of these cables can be connected in parallel. There are Electrical Code) and CEC (Canadian Electrical Code)
two main reasons for this: standards.
• Only then can the high IP55 degree of protection at the motor Grounding and protective conductor cross-section
terminal box be easily achieved. The reason for this is that
cables are routed into the terminal box through glands, and The protective conductor must be dimensioned taking into
the number of possible glands is restricted by the terminal box account the following data:
geometry. Therefore single cables are less suitable. • In the case of a ground fault, no impermissibly high contact
• With symmetrical 3-wire three-phase cables, the summed voltages resulting from voltage drops on the PE conductor
ampere-turns over the cable outer diameter are equal to zero. caused by the ground fault current may occur (< 50 V AC
They can easily be routed in conductive, metal cable ducts or or < 120 V DC, IEC 61800-5-1, IEC 60364, IEC 60543).
racks without any significant currents (ground current or • The protective conductor must not be excessively loaded
leakage current) being induced in these conductive, metal by any ground fault current it carries.
connections. The danger of induced leakage currents and
thus of increased cable sheath losses is significantly higher • If it is possible for continuous currents to flow through the
with single-conductor cables. protective conductor when a fault occurs, then the protective
conductor cross-section must be dimensioned for this
The cable cross-section required depends on the current being continuous current.
conducted in the cable. The permissible current load capability • The protective conductor cross-section must be selected
of cables is defined, for example in IEC 60364-5-52. It depends according to EN 60204-1, EN 60439-1, IEC 60364.
partly on the ambient conditions such as temperature, but also
on the routing method. It should be taken into account whether Cross-section, line conductor Minimum cross-section, external pro-
cables are individually routed with relatively good cooling, or tective conductor
whether several cables are routed together; in this case, cable mm2 mm2
ventilation is significantly poorer, which can therefore result in
higher cable temperatures. Regarding this topic, reference is up to 16 Minimum cross-section of line
conductor
made to the corresponding correction factors for these
secondary conditions in IEC 60364-5-52. 16 ... 35 16

For 3-conductor copper and aluminum cables with PVC from 35 Minimum half the cross-section of line
conductor
insulation and a permissible conductor temperature of 70 °C
(e.g. Protodur NYY or NYCWY), as well as an ambient tempera- Note:
ture of 40 °C, the cross-sections can be determined from the The recommendations for the North American market in AWG
following table, which is based on IEC 60364-5-52. or MCM must be taken from the appropriate NEC (National
Electrical Code) and CEC (Canadian Electrical Code)
Cross- Copper cable Aluminum cable standards.
section of
3-conductor • Switchgear and motors are usually grounded separately
cable via a local grounding electrode. With this constellation,
Individual Several Individual Several the ground fault current flows via the parallel ground
routing cables next to routing cables next to connections and is divided. In spite of the relatively small
8 mm2 A
one another 1)
A A
one another 1)
A
protective conductor cross-sections used in accordance with
the table above, no inadmissible touch voltages occur with
this grounding system.
3 × 2.5 22 17 17 13
However, from experience gained with different grounding
3 × 4.0 30 23 23 18 constellations, we recommend that the ground cable from the
3 × 6.0 37 29 29 22 motor return directly to the converter. For EMC reasons and to
avoid bearing currents, for large power ratings, it is preferable
3 × 10 52 41 40 31
to use symmetrical 3-conductor, three-phase cables instead
3 × 16 70 54 53 41 of four-conductor cables. For 3-conductor cables, the
3 × 25 88 69 68 53 protective or PE conductor must be routed separately or
arranged symmetrically in the motor cable. Symmetry of the
3 × 35 110 86 84 65 PE conductor is achieved using a conductor surrounding all
3 × 50 133 104 102 79 phase conductors or using a cable with a symmetrical
3 × 70 171 133 131 102 arrangement of the three phase conductors and three ground
conductors.
3 × 95 207 162 159 124 For additional information, please refer to the SINAMICS Low
3 × 120 240 187 184 144 Voltage Engineering Manual.
3 × 150 278 216 213 166 • Through their high-speed control, the converters limit the load
3 × 185 317 247 244 190
current (motor and ground fault currents) to an rms value
corresponding to the rated current. As a result of this fact, we
3 × 240 374 292 287 224 recommend that the cross-section of the protective conductor
Current-carrying capacity according to IEC 60364-5-52 at 40 °C to ground the cabinets is the same as for the outer conductor.

1) A maximum of 9 cables may be routed directly next to one another


horizontally on a cable tray.

8/38 Siemens D 21.3 · 2022


© Siemens 2022

SINAMICS S150 Converter Cabinet Units


Supplementary system components
Mounting device for power blocks

■ Overview ■ Selection and ordering data


Mounting device for power blocks Description Article No.
Mounting device 6SL3766-1FA00-0AA0
for installing and removing power blocks

The mounting device is used for installing and removing


the power blocks.
The mounting device is a mounting aid. It is placed in front of the
module and attached to the module. The telescopic rails allow
the device to be adjusted to the installation height of the power
blocks.
Once the mechanical and electrical connections have been
released, the power block can be removed from the module.
The power block is guided and supported by the guide rails
on the handling device.

Siemens D 21.3 · 2022 8/39


© Siemens 2022

SINAMICS S150 Converter Cabinet Units

Notes

8/40 Siemens D 21.3 · 2022


9
© Siemens 2022

Tools and Engineering

Security information 9/2 Engineering tools


Siemens provides products and solutions with 9/2 SinaSave energy efficiency tool
industrial security functions that support the 9/3 Siemens Product Configurator
secure operation of plants, systems, machines 9/4 SIZER for Siemens Drives
and networks.
engineering tool
In order to protect plants, systems, machines
(integrated in the TIA Selection Tool)
and networks against cyber threats, it is 9/5 STARTER commissioning tool
necessary to implement – and continuously 9/7 SINAMICS DCC (STARTER)
maintain – a holistic, state-of-the-art industrial 9/8 SINAMICS Startdrive commissioning tool
security concept. Siemens’ products and 9/10 SINAMICS DCC (Drive Control Chart)
solutions constitute one element of such in the TIA Portal
a concept.
9/12 SINAMICS Web server for SINAMICS S120
9/13 Drive ES engineering software
Customers are responsible for preventing
unauthorized access to their plants, systems, 9/15 Configuration with EPLAN
machines and networks. Such systems,
9/17 Engineering information
machines and components should only be
connected to an enterprise network or the 9/17 Planning
internet if and to the extent such a connection is 9/18 EMC notes for applying product
necessary and only when appropriate security standard EN 61800-3
measures (e.g. firewalls and/or network 9/21 Engineering Manual
segmentation) are in place.

For additional information on industrial security


measures that may be implemented, please visit
www.siemens.com/industrialsecurity

Siemens’ products and solutions undergo


continuous development to make them more
secure. Siemens strongly recommends that
product updates are applied as soon as they are
available and that the latest product versions are
used. Use of product versions that are no longer
supported, and failure to apply the latest
updates may increase customer’s exposure to
cyber threats.

To stay informed about product updates,


subscribe to the Siemens Industrial Security
RSS Feed under
www.siemens.com/cert

Siemens D 21.3 · 2022


© Siemens 2022

Tools and engineering


Engineering tools
SinaSave energy efficiency tool

■ Overview ■ Function
SinaSave determines the energy saving potential and payback • Determine savings potential for energy, power costs, and CO2
time based on your application setup. SinaSave is a web tool • Estimate expected amortization and Total Costs of Ownership
which is intuitive to operate and supports you in an investment (TCO)
decision: • Output of system power losses for motor inverter systems
• Is it worthwhile to use more energy efficient systems? as per IEC 61800-9-2
• When will my investment pay off? • Calculate possible financing, such as energy performance
SinaSave supports you to find the optimum solution: contracting (EnPC)
technically, economically, and ecologically. • Take government subsidies into account
• Simple design with intuitive usability
• Results presented in graphic form
• Save and load, share a handout e.g with your customer
or decision-maker
• Eight languages, 14 currencies, IEC and NEMA standards
• Direct transfer to next processes, e.g. product configuration

■ More information
Further information about the amortization calculator for
energy-efficient drive systems is available on the internet at:
www.siemens.com/tools-sinasave
Further information about services for energy saving is available
on the internet at:
www.siemens.com/energy-saving
In which cases can SinaSave support you?
• Motors www.siemens.com/energy-efficiency
- Calculate your potential energy savings and
amortization times with SIMOTICS motors
• Pump systems
- Calculate your potential energy and CO2 savings with
our pump drive systems
• Fan systems
- Calculate your potential energy and CO2 savings with
our fan drive systems
Access to the SinaSave energy efficiency tool
SinaSave can be accessed without the need for registration
or logging in:
www.siemens.com/sinasave

■ Benefits
• Transparency of overall savings potential and individual
amortization plan
- SinaSave calculates the expected energy consumption and
the resulting savings of energy, CO2 and energy cost, based
on your individual energy prices, operating times and load
9 profiles.
• Support to find the optimum solution to make easy
decision
- SinaSave directly compares your existing motors with
SIMOTICS motors of various energy efficiency classes, for
new systems and retrofits.
• Ease of use and self-explanatory user guidance to
calculate savings potential on overall system level
- SinaSave compares different drive system configurations for
pump or fan applications. Regardless of greenfield or
brownfield projects, SinaSave offers the flexibility to choose
from different motor types and control modes, including
variable speed drives and softstarters.
• Well-structured SinaSave projects give you transparency
of the savings potential of your entire facility
- SinaSave lets you combine several items in a single project.
That means it’s possible to reflect entire facilities and identify
the savings potential they offer.

9/2 Siemens D 21.3 · 2022


© Siemens 2022

Tools and engineering


Engineering tools
Siemens Product Configurator

■ Overview
The Siemens Product Configurator helps you to configure the Siemens Product Configurator at a glance
optimum drive technology products for a number of • Quick and easy configuration of drive products and
applications. The product portfolio comprises the full drive tech- associated components – gearboxes, motors, converters,
nology range of gearbox, motor, converter and connection controllers, connection systems
system as well as corresponding controller with suitable
software license. The intuitive user interface in conjunction with • Extensive documentation for all products and components,
product-specific preliminary selectors makes it simple, fast and such as
efficient to configure products. The result is a bill of materials - Data sheets in up to 12 languages
with extensive documentation consisting of technical data - Motor characteristic curves
sheets, motor characteristic curves, 2D dimensional drawings / - 2D dimensional drawings / 3D CAD models in different
3D CAD models, EPLAN macros and much more. You can order formats
the products directly by transferring the bill of materials to the - Terminal box drawing and terminal connection diagram
shopping cart of the Industry Mall. - Certificates
- EPLAN macros
• Ability to order products directly through the Siemens Industry
Mall
Access to Siemens Product Configurator
The Siemens Product Configurator can be accessed without the
need for registration or logging in:
www.siemens.com/spc

Siemens D 21.3 · 2022 9/3


© Siemens 2022

Tools and engineering


Engineering tools
SIZER for Siemens Drives engineering tool (integrated in the TIA Selection Tool)

■ Overview The configuration process produces the following results:


• A parts list of the required components (export to Excel,
use of the Excel data sheet for import to SAP)
• Technical specifications of the system
• Characteristic curves
• Comments on line harmonic distortions
• Mounting arrangement of drive and control components and
dimensional drawings of motors
• Energy requirements of the configured application
These results are displayed in a results tree and can be reused
for documentation purposes.
Support is provided by the technological online help menu:
• Detailed technical specifications
• Information about the drive systems and their components
• Decision-making criteria for the selection of components
• Online help in English, French, German, Italian, Chinese
and Japanese
System requirements
• PG or PC, with Pentium III min. 800 MHz
The following drives and controls can be engineered in a user- (recommended > 1 GHz)
friendly way using the SIZER for Siemens Drives engineering • 512 MB RAM (1 GB RAM recommended)
tool:
• At least 2 GB of free hard disk space
• SIMOTICS low-voltage motors, including servo geared motors
• An additional 100 MB of free hard disk space on
• SIMOGEAR geared motors Microsoft Windows system drive
• SINAMICS low-voltage drive systems • Screen resolution 1024 × 768 pixels
• Motor starters • Operating system:
• SINUMERIK CNC - Microsoft Windows 7 (32/64-bit) Professional, Enterprise,
• SIMOTION Motion Control controller Ultimate, Home
- Microsoft Windows 8.1 (32/64-bit) Professional, Enterprise,
• SIMATIC controller Ultimate, Home
It provides support when selecting the technologies involved - Microsoft Windows 365
in the hardware and firmware components required for a drive - Microsoft Windows 10 (64-bit) Professional, Enterprise
task. SIZER for Siemens Drives covers the full range of • Microsoft Office 2003/2007/2010/2013/2016/365
operations required to configure a complete drive system,
from basic single drives to demanding multi-axis applications. • Microsoft Internet Explorer V8.0
• Microsoft .NET Framework 2.0
SIZER for Siemens Drives supports all of the engineering steps
in one workflow: • OpenGL 2.1
• Configuring the power supply
• Designing the motor and gearbox, including calculation
■ More information
of mechanical transmission elements Drive dimensioning in the TIA Selection Tool
• Configuring the drive components Application-specific requirements can be determined using
• Compiling the required accessories drive technology dimensioning in the TIA Selection Tool. This
• Selecting the line-side and motor-side power options, can include motors, gearboxes and converters. The tool
9 e.g. cables, filters, and reactors supports the configuration and dimensioning of control functions
with an open and closed control loop. The technical documen-
When SIZER for Siemens Drives was being designed, particular tation with features of the technical drive system, as well as a
importance was placed on a high degree of usability and product list for ordering via the Industry Mall can also be
a universal, function-based approach to the drive application. compiled.
The extensive user guidance makes it easy to use the tool.
Status information keeps you continually informed about the You can find more information on the SIZER for Siemens Drives
progress of the configuration process. engineering tool at
https://support.industry.siemens.com/cs/ww/en/ps/13434/dl
The drive configuration is saved in a project. In the project, the
components and functions used are displayed in a hierarchical You can find more information about the TIA Selection Tool at:
tree structure. www.siemens.com/tia-selection-tool

The project view permits the configuration of drive systems and


the copying/inserting/modifying of drives already configured.

9/4 Siemens D 21.3 · 2022


© Siemens 2022

Tools and engineering


Engineering tools
STARTER commissioning tool

■ Overview
In addition, the following functions are available for optimization
purposes:
• Self-optimization of the controller settings
(depending on drive unit)
• Setup and evaluation of trace recordings 1)
Tool function for recording 2 × 8 signals with
- Measuring cursor function
- Extensive trigger functions
- Several Y scales
- Sampling times in the current controller cycle clock
Diagnostics functions provide information about:
• Control/status words
• Parameter status
• Operating conditions
• Communication states
Performance features
The user-friendly STARTER commissioning tool can be used for: • User-friendly: Only a small number of settings need to be
• Commissioning made for successful first commissioning: The motor starts to
• Optimization rotate
• Diagnostics • Solution-oriented dialog-based user guidance simplifies
commissioning
This software can be operated as a standalone PC application,
or integrated as a TIA-compatible program in SIMATIC STEP 7, • Self-optimization functions reduce manual effort for
or highly integrated into the SCOUT Engineering System optimization.
(for SIMOTION). The basic functions and handling are the same System requirements
in both cases.
The following minimum requirements must be complied with:
In addition to the SINAMICS drives, STARTER also supports
MICROMASTER 4 devices. • Hardware
- PG or PC with Pentium III min. 1 GHz
The project wizards can be used to create the drives within (recommended >1 GHz)
the structure of the project tree. - Work memory 2 GB (4 GB recommended)
- Screen resolution 1024 × 768 pixels, 16-bit color depth
Beginners are supported by solution-based dialog guidance, - Free hard disk memory: min. 5 GB
whereby a standard graphics-based display maximizes clarity
when setting the drive parameters. • Software
- Microsoft Internet Explorer V6.0 or higher
First commissioning is guided by a wizard which makes all the - 64-bit operating systems:
basic settings in the drive. Therefore, getting a motor up and Microsoft Windows Server 2016
running is merely a question of setting a few of the drive Microsoft Windows Server 2019
parameters as part of the drive configuration process. Microsoft Windows 10 Pro
The individual settings required are made using graphics-based Microsoft Windows 10 Enterprise
parameterization screens, which also precisely visualize the Supported virtualization platforms
principle of operation of the drive.
STARTER (V5.1 SP1 and higher) can be installed on a virtual
Examples of individual settings that can be made include: machine. For this purpose, one of the following virtualization
• Use of terminals platforms in the specified version or a newer version can be
used:
• Bus interface
• Setpoint channel (e.g. fixed setpoints) • VMware vSphere Hypervisor (ESXi) 6.7 9
• Closed-loop speed control • VMware Workstation pro V16.1.x
(e.g. ramp-function generator, limits) • VMware Player V16.1.x
• BICO interconnections • Microsoft Windows Server 2016 Hyper-V
• Diagnostics You can use the following guest operating systems to install
For experts, the expert list can be used to specifically and STARTER within the selected virtualization platform:
quickly access individual parameters at any time. An individual • Microsoft Windows 10 Professional/Enterprise (64 bit)
compilation of frequently used parameters can be saved in
dedicated user lists and watch tables.

1) Depending on drive unit. Not supported for MICROMASTER 4,


SINAMICS G110, SINAMICS G120 <firmware V4.4,
SINAMICS G110D and SINAMICS G120D <firmware V4.5.

Siemens D 21.3 · 2022 9/5


© Siemens 2022

Tools and engineering


Engineering tools
STARTER commissioning tool

■ Integration ■ Accessories
Data can be exchanged (depending on the version) Depending on the version of the Control Unit (CU), the Control
via PROFIBUS or PROFINET/Ethernet or via a serial interface. Unit of the drive unit can communicate with the programming
device (PG) or PC via PROFIBUS or PROFINET/Ethernet or via a
For commissioning and service, a PG/PC can be connected to serial interface. The following accessories are available for the
the CU320-2 Control Unit via PROFIBUS. A PROFIBUS particular drive system as listed in the following table.
connection must be available with a connecting cable at the
PG/PC. Description Recommended
accessories
Further, communication between a CU320-2 Control Unit and
PG/PC can also be established via Ethernet, either via an For communication
between the drive unit
(optional) CBE20 Communication Board or the Ethernet and the programming
interface -X127 on the CU320-2 Control Unit. device or PC
Note: Article No.
The terminal strip -X127 is suitable as a communication link to SINAMICS S120
the PG/PC only for the purposes of servicing and
commissioning. • RS232 SIMATIC S7 connecting cable 6ES7901-1BF00-0XA0
Null modem cable, 6 m (19.69 ft)

■ Selection and ordering data • PROFIBUS CP 5711 communication module 6GK1571-1AA00


USB adapter for connecting
Description Article No. a PG or notebook to
PROFIBUS or MPI
STARTER commissioning tool 6SL3072-0AA00-0AG0
for SINAMICS and MICROMASTER USB cable (2 m (6.56 ft))
included in scope of supply
English, French, German, Italian, Spanish
SIMATIC DP plug-in cable 6ES7901-4BD00-0XA0
Note: 12 MBaud, for PG
In addition to the STARTER commissioning tool, SINAMICS Drive connection, pre-assembled
Control Chart (SINAMICS DCC) can be installed. This allows the with 2 × 9-pin SUB D
device functionality in the SINAMICS drive system to be connector, 3 m (9.84 ft)
expanded with dedicated technology functions as required. • PROFINET/ Standard CAT5 Ethernet –
Ethernet cable or PROFINET cable
Further information about SINAMICS DCC can be found in the
section SINAMICS DCC (Drive Control Chart) with STARTER. SINAMICS S150
• PROFIBUS CP 5711 communication module 6GK1571-1AA00
USB adapter for connecting
a PG or notebook to
PROFIBUS or MPI
USB cable (2 m (6.56 ft))
included in scope of supply
SIMATIC DP plug-in cable 6ES7901-4BD00-0XA0
12 MBaud, for PG
connection, pre-assembled
with 2 × 9-pin SUB D
connector, 3 m (9.84 ft)
• PROFINET/ Standard CAT5 Ethernet –
Ethernet cable or PROFINET cable

■ More information
The STARTER commissioning tool is also available on the
internet under
9 www.siemens.com/starter

9/6 Siemens D 21.3 · 2022


© Siemens 2022

Tools and engineering


Engineering tools
SINAMICS DCC (STARTER)

■ Overview ■ Selection and ordering data


SINAMICS DCC (Drive Control Chart) is a technological SINAMICS DCC consists of a graphic configuration tool
expansion for the SINAMICS S120/S150/G130/G150/ (DCC Editor based on SIMATIC CFC) and the standard library.
MV/DCM/DCP drive systems. This allows the device functions of SINAMICS DCC is installed as an add-on to the STARTER
the SINAMICS drive system to be expanded individually with commissioning tool.
freely available closed-loop control, arithmetic and logic blocks.
SINAMICS DCC for STARTER enables simple, graphic The SINAMICS DCC V3.4 SP2 software package is a component
configuration of these blocks and integrates them in the drive of STARTER V5.4 SP2.
unit. The necessary license key (floating license) for the configuration
of SINAMICS DCC V3.4 SP2 must be ordered separately.
The included DCB standard library of SINAMICS DCC V3.4 SP2
does not require a runtime license. Existing licenses for
SINAMICS DCC V2.1 and higher can also be used for
SINAMICS DCC V3.4 SP2.
An upgrade variant for the application in STARTER V5.4 SP2 and
SINAMICS DCC V3.4 SP2 is available for an existing license key
of SINAMICS DCC V2.0 SPx.
Description Article No.
SINAMICS DCC V3.4 SP2 License Key
for SINAMICS DCC V3.4 and V3.4 SP2
• License key on USB flash drive 6AU1810-1HA34-0XB0
• Upgrade license key on USB flash drive 6AU1810-1HA34-0XF0
SINAMICS DCB Extension license
Runtime license for license upgrading with
firmware version V4.6 or later
(can also be ordered in conjunction with the
CompactFlash card, see CompactFlash card
for CU310-2 and CU320-2 Control Units)
A comprehensive standard library is available for the • Electronic license 6SL3077-0AA00-0AH0
configuration, which can be expanded by additional libraries, SINAMICS DCB Studio V2.3 On request
the so-called DCB Extension. Development tool for programming blocks
that can be imported as an additional library
Via the Siemens application support, a range of example (DCB Extension) for SINAMICS DCC in
applications (winder, synchronous operation, cross-cutter, etc.) STARTER or in the TIA Portal
are available for download on the basis of SINAMICS DCC with
STARTER and can be used as a ready-to-use solution or be Further information about SINAMICS DCB Extension and
individually adapted or expanded. SINAMICS DCB Studio can be found in the section SINAMICS
DCC (Drive Control Chart) in the TIA Portal.
Minimum hardware and software requirements
See STARTER commissioning tool.
Minimum software requirements for existing SIMATIC CFC Editor
The installation of STARTER V5.4 SP2 and SINAMICS DCC
V3.4 SP2 results in the following minimum requirements:
• when using STEP7 OEM V5.7 in the standalone installation:
SIMATIC CFC Editor V9.0 SP5 Upd4
• when using STEP7 V5.7 full version (with monitoring of
application integrity): SIMATIC CFC Editor V9.0 SP5 Upd4
• when using STEP7 V5.7 full version (without monitoring of
application integrity): SIMATIC CFC Editor V9.0 SP3 Upd4
9
• when using STEP7 V5.6 SPx full version:
SIMATIC CFC Editor V9.0 Upd1
Please check the minimum requirements in relation to the
product SIMATIC CFC when installing STEP7 or SIMATIC PCS 7.

Siemens D 21.3 · 2022 9/7


© Siemens 2022

Tools and engineering


Engineering tools
SINAMICS Startdrive commissioning tool

■ Overview SINAMICS Startdrive Advanced


With SINAMICS Startdrive Advanced (available as of V15) you
SINAMICS Startdrive is integrated in the TIA Portal and is a tool benefit from powerful engineering functions that save you con-
for the configuration, commissioning and diagnostics of the siderable time and ultimately costs.
SINAMICS family of converters.
• Advanced functions for SINAMICS Startdrive: Safety
The SINAMICS Startdrive commissioning tool has been acceptance test for SINAMICS G120, SINAMICS S120 and
optimized with regard to user friendliness and consistent use of SINAMICS S210
the TIA Portal benefits of a common working environment for - Safety Activation Test
PLC, HMI and drives. Time-saving and guided step-by-step - Improved optimization options in the drive for
commissioning with maximum flexibility is complemented by CU320-2 PN/DP and CU310-2 PN-based drive units:
user-friendly graphic function views for all drive functions, Extended measuring functions (available as of V5.2 SP3)
including functional safety (Safety Integrated) and drive-based - Prompted acceptance test wizard for all drive-based Safety
technology functions (e.g. EPos). The automatic message Integrated functions (Basic and Extended Safety)
display, the powerful real-time trace and the context-sensitive - Automatic and safety function-specific generation of traces
online help make converter diagnostics very easy. to analyze the machine behavior
- Generation of an acceptance report as Excel file
(xlsx format, can also be used with OpenOffice)
- Available for SINAMICS G120, G120C, G115D, G120D,
G120P, S120 and S210
• Also contains all Startdrive Basic functions
• License key only required, no additional installation
New in V17
Startdrive Basic V17
• Extension for UMAC: Additional function right for drive
parameter changes including DCC
• Extension of the SINAMICS S210 family: Support of the
SINAMICS firmware V5.2 SP3
• Extension of the SINAMICS S120 family: Support of CU320-2
DP (in V4.8 or higher) for SINAMICS S120 Booksize and
The software packages based on the TIA Portal are harmonized Chassis
with each other and offer important benefits, the main advantage • Extension of the SINAMICS MV family: Support of the
being a shared project storage. The TIA Portal enables simple SINAMICS firmware V5.2 SP2
integration of SINAMICS converters in your automation solution.
Thanks to the standardization of operator actions and the • Extensions for CU320-2 PN/DP and CU310-2 PN-based drive
integration in general TIA Portal operating concepts units
(e.g. UMAC, Openness) as well as standard TIA Portal functions - Support of the SINAMICS firmware V5.2 SP3
(e.g. Undo/Redo), familiarization is easy both for drive experts - User-defined parameter list
as well as SIMATIC users. Special focus is placed on the - Data set switchover (drive, motor, encoder and command
interaction between SIMATIC and SINAMICS, especially when data sets)
connecting the SINAMICS drives to SIMATIC technology - Improved optimization option in the drive (Bode diagram)
objects. - Extensions for CU320-2 Integrated in SIMATIC Drive
Controller
■ Integration - EPOS (basic positioner)
- DCC (Drive Control Chart)
Supported frequency converters - Improved interaction between drives and SIMATIC
technology objects
SINAMICS Startdrive Basic enables complete commissioning, - Transfer of optimization parameters from One Button Tuning
diagnostics, parameterization, optimization and connection to (OBT) of the drive to the technology object
the PLC for the following SINAMICS converters integrated in - Display of drive configuration status in the technology object
9 SINAMICS Startdrive:
• SINAMICS G120, G120C, G120D, G120P
- Support of new SINAMICS Technology Extensions (TEC)
function, see
https://support.industry.siemens.com/cs/ww/en/view/
• SINAMICS G115D 109771648
• SINAMICS G130, G150 • Extension of the SINAMICS G120 family:
• SINAMICS S120 *), S150 - Support of the SINAMICS G115D distributed drive
• SINAMICS S210 - Improved AS-i connection for SINAMICS G115D AS-i
(in combination with SIMATIC ET200SP AS-i Master)
• SINAMICS MV
• Extension of technology object "BasicPosControl"
- Physical units
- Entry of mechanical data
• Extension of Openness for drive units
- Support of the SINAMICS G115D distributed drive
- More information on Startdrive Openness can be found at
https://support.industry.siemens.com/cs/ww/en/view/
109763491

*)
Including SINAMICS S220 Smart Line Modules in booksize format as of
SINAMICS Startdrive V17 Update 1.

9/8 Siemens D 21.3 · 2022


© Siemens 2022

Tools and engineering


Engineering tools
SINAMICS Startdrive commissioning tool

■ Integration Supported safety programs


The following safety programs have been tested with SINAMICS
Startdrive Advanced V17 Startdrive V17:
• Extension of safety acceptance test • Virus scanners:
- Safety Activation Test - Symantec Endpoint Protection 14.2
- Support of the SINAMICS G115D distributed drive - Trend Micro OfficeScan 12.0
• Expansion for CU320-2 PN/DP and CU310-2 PN-based drive - McAfee Endpoint Security (ENS) 10.6
units: Improved optimization options in the drive: Extended - Kaspersky Endpoint Security 11.3
measuring functions (available as of V5.2 SP3) - Microsoft Defender
- Qihoo 360 "Safe Guard 12.1" + "Virus Scanner"
Installation versions
• Encryption software:
SINAMICS Startdrive can be installed as an optional package to - Microsoft Bitlocker
SIMATIC STEP 7 or as a stand-alone application (without • Host-based Intrusion Detection System
SIMATIC STEP 7). - McAfee Application Control 8.2
System requirements
The following table shows the recommended hardware and sys- ■ Selection and ordering data
tem equipment for the operation of SINAMICS Startdrive. Description Article No.
Hardware Recommendation SINAMICS Startdrive Basic V17 commissioning
tool
Computer As of SIMATIC FIELD PG M5 Advanced (or comparable PC) Single license and certificate of license
Processor Intel Core i5-8400H (2.5 ... 4.2 GHz; 4 cores + hyper-thread- English, French, German, Italian, Spanish,
ing; 8 MB Smart Cache) Chinese Simplified
RAM 16 GB or more (32 GB for large projects) • On DVD-ROM 6SL3072-4HA02-0XA0
• Software download 6SL3072-4HA02-0XG0
Hard disk SSD with at least 50 GB available memory (email address required for delivery)
Screen reso- 15.6" Full HD display (1920 × 1080 or larger) SINAMICS Startdrive Advanced V17
lution commissioning tool
Operating • Microsoft Windows 10 (64 bit) License key (floating license)
systems - Windows 10 Professional Version 1909, 2004, 2009/20H2 English, French, German, Italian, Spanish, Chinese
- Windows 10 Enterprise 1909, 2004, 2009/20H2 Simplified
- Windows 10 IoT Enterprise 2016 LTSB • On DVD-ROM with license key on USB flash drive 6SL3072-4HA02-0XA5
- Windows 10 IoT Enterprise 2019 LTSC
• Microsoft Windows Server (64 bit) • Software download incl. license key 6SL3072-4HA02-0XG5
- Windows 10 Professional Version 1909, 2004, 2009/20H2 (email address required for delivery)
- Windows 10 Enterprise 1909, 2004, 2009/20H2 Upgrade SINAMICS Startdrive Advanced
- Windows 10 IoT Enterprise 2016 LTSB V15 ... V16 to V17
- Windows 10 IoT Enterprise 2019 LTSC • On DVD-ROM with license key on USB flash drive 6SL3072-4HA02-0XE5
• Software download incl. license key 6SL3072-4HA02-0XK5
Compatibility with other products (email address required for delivery)
• SINAMICS Startdrive V17 operates with STEP 7, Software Update Service with SINAMICS
WinCC and Scout TIA V17 in one framework Startdrive Advanced in the TIA Portal
• SINAMICS Startdrive V17 can be installed on the same Delivery is performed according to the number of
ordered SUS products (e.g. 10 upgrade license
computer as other versions of SINAMICS Startdrive V12 to V16 keys (floating license) with 10 DVD-ROMs, 10 USB
• SINAMICS Startdrive can be installed on the same computer flash drives, etc.)
as SINAMICS MICROMASTER STARTER • On DVD-ROM with upgrade license key on USB 6SL3072-4AA02-0XL8
flash drive
Supported virtualization platforms • Software download incl. license key 6SL3072-4AA02-0XY8
(email address required for delivery)
SINAMICS Startdrive can be installed in a virtual machine.
For this purpose, one of the following virtualization platforms in
the specified version or a newer version can be used: ■ More information
• Microsoft Windows 10 Professional Version 1909, 2004, The SINAMICS Startdrive Basic commissioning tool is available 9
2009/20H2 free on the internet at
• Microsoft Windows 10 Enterprise 1909, 2004, 2009/20H2 www.siemens.com/startdrive
• Microsoft Windows 10 IoT Enterprise 2016 LTSB
• Microsoft Windows 10 IoT Enterprise 2019 LTSC

Siemens D 21.3 · 2022 9/9


© Siemens 2022

Tools and engineering


Engineering tools
SINAMICS DCC (Drive Control Chart) in the TIA Portal

■ Overview
SINAMICS DCC (Drive Control Chart) is a technological Licenses
expansion for the SINAMICS S120/S150/G130/G150/MV drive
systems and for SIMATIC Drive Controller. This allows the device SINAMICS DCC V17 is delivered with a SINAMICS DCC V17
functions of the converter systems to be expanded individually combo floating license. The floating license allows the use of
with freely available closed-loop control, arithmetic and logic software on any number of computers. This allows one user per
blocks and thus opens up a new dimension of adaptation license to use the software independently of the computer being
capabilities for the specific functions of the machine for the user. used or a specific workstation. The number of existing licenses
The user-friendly configuration tool in the TIA Portal enables determines the number of computers on which the software can
simple, graphic configuration of these blocks and integrates be used simultaneously.
them in the drive unit. SINAMICS DCC is available as an option • Existing SINAMICS DCC V15/V16 combo licenses can be
for SINAMICS Startdrive Basic and Advanced in the TIA Portal. upgraded to V17. This requires an upgrade license.
• The combo license enables parallel use of
SINAMICS DCC V3.4 and SINAMICS DCC V17 if both tools
are installed on the same PC.
Installation versions
SINAMICS DCC is an option package for SINAMICS Startdrive
Basic and Advanced.
System requirements
The SINAMICS DCC V17 option package has the same system
requirements and supports the same virtualization platforms and
safety programs as SINAMICS Startdrive V17.?
Compatibility with other products
• SINAMICS DCC V17 operates with Startdrive, STEP 7 and
WinCC in one framework
With the integration into the TIA Portal, the focus is on simple • SINAMICS DCC V17 can be installed on a computer in parallel
usability. For this reason, closed loop control and open loop with SINAMICS MICROMASTER STARTER with
control functions can be graphically interconnected in just a few SINAMICS DCC
steps via drag and drop. Supported languages
The SINAMICS DCC installation contains a comprehensive • Standard installation: English, German, Chinese (simplified)
standard block library. Furthermore, additional libraries can be • Language packages: French, Italian, Spanish
installed as DCB Extension to expand the range of functions of
the blocks. The diagnostics functions allow the program
behavior to be verified and, in the case of a fault, the cause to be
identified.
Via the Siemens application support, a range of example
applications (winder, synchronous operation, cross-cutter, etc.)
are available for download on the basis of SINAMICS DCC and
can be used as a ready-to-use solution or be individually
adapted or expanded.
New in V17
• Know-how protection for charts
• Online engineering of charts
- Change value of a block connection online
9 - Insert blocks into a DCC chart online
- Delete blocks in the DCC chart online
- Insert block connections online
- Delete block connections online
- Change run sequence of blocks online
• Creation of chart partitions
• Improvements relating to handling:
- Switchover between PIN name and parameter text in
the editor
- Zoom in/out by double-clicking in the editor
- Block search in the project library by entering the block
name
- Library update with block assignment
• Support of additional function right for drive parameter
changes with UMAC
• Support of the SINAMICS firmware V5.2 SP3
• Support of SINAMICS Integrated in SIMATIC Drive Controller
• Support of CU320-2 DP

9/10 Siemens D 21.3 · 2022


© Siemens 2022

Tools and engineering


Engineering tools
SINAMICS DCC (Drive Control Chart) in the TIA Portal

■ Selection and ordering data ■ More information


SINAMICS DCC in the TIA Portal, consisting of the graphical TIA Portal highlights
configuration tool and the standard library, is the continuation of www.siemens.com/tiaportal
SINAMICS DCC in the STARTER.
The SINAMICS DCC option package as trial version is available
No runtime license is required for the standard library included free on the internet at
in the scope of supply. www.siemens.com/startdrive
Description Article No.
SINAMICS DCC V17 for TIA Portal incl.
Floating
as an option package for SINAMICS
Startdrive Basic or Advanced V17
Combo license key (floating license)
German, English, French, Italian, Spanish,
Chinese Simplified
• On DVD-ROM with license key on USB 6SL3070-4HA01-0XA5
flash drive
• Software download incl. license key 6SL3070-4HA01-0XG5
(email address required for delivery)
Upgrade SINAMICS DCC V15.1 ... V16 to
V17
• On DVD-ROM with license key on USB flash 6SL3070-4HA01-0XE5
drive
• Software download incl. license key 6SL3070-4HA01-0XK5
(email address required for delivery)
Software Update Service with SINAMICS
DCC in the TIA Portal 1)
Delivery is performed according to the
number of ordered SUS products
(e.g. 10 upgrade license keys with 10
DVD-ROMs, 10 USB flash drives, etc.)
• On DVD-ROM with license key on USB 6SL3070-4AA01-0XL8
flash drive
• Software download incl. license key 6SL3070-4AA01-0XY8
(email address required for delivery)

DCB Extension
With DCB Extension, additional libraries can be added as
specifically programmed blocks to the standard block library. As
a result, complex tasks can be implemented in the drive and the
internal know-how protection can be increased as a Black Box.
These blocks or libraries are programmed with the separate
SINAMICS DCB Studio development tool in the C/C++ high-level
language and can be used as a DCB Extension library for
SINAMICS DCC in the TIA Portal and SINAMICS DCC in
STARTER. The use of these blocks from DCB Extension libraries
requires a SINAMICS DCB Extension runtime license.
SINAMICS DCB Extension license
Runtime license for re-licensing as of firmware V4.6 for the use
of additional blocks/libraries (can also be ordered together with
the CompactFlash card, see CompactFlash card for the Control
Units CU310-2 and CU320-2) 6SL3077-0AA00-0AH0 9
SINAMICS DCB Studio V2.3
Development tool for programming blocks that can be imported
as an additional library (DCB Extension) for SINAMICS DCC in
the TIA Portal or in STARTER (upon request)

1) See Software Update Service section.

Siemens D 21.3 · 2022 9/11


© Siemens 2022

Tools and engineering


Engineering tools
SINAMICS Web server for SINAMICS S120

■ Overview ■ Benefits
Web server for efficient diagnostics and maintenance – Shorter machine downtimes
available everywhere at all times • Efficient diagnostics and maintenance
The SINAMICS drive system can be expanded with the web Direct language selection
server to provide an efficient diagnostics and maintenance
option. The Web server provides access to multi-faceted new • English, German, Chinese, Italian, French, Spanish
options for drive diagnostics and remote maintenance for every Accessibility
network-compatible PC with a Web browser. For example: • Via all LAN or PROFINET interfaces
• Downloading a configuration
Two users with different rights can be configured
• Updating firmware
• e. g. for operators and service personnel
• Providing a status overview of the drive
• Evaluating warnings and fault messages Diagnostic functions
• Monitoring and adapting parameter settings • Quick overview of the current configuration and the state of
the drive
• Saving machine documentation, including notes
• Understandable diagnostic information and messages are
• Setting up of a user administration to provide access displayed in plain text in multiple languages
protection
Freely configurable parameter lists
• Monitoring parameters for diagnostic purposes, for example
for operating personnel
Webbrowser
Remote • Adapting/optimizing existing projects, for example for service
maintenance personnel
Updating functions
VPN • The device functionality can be updated from any network-
compatible PC (locally or by remote access)
Webbrowser Internet • Series commissioning is possible without the STARTER
Local commissioning tool
maintenance
Archiving machine documentation
Intranet • Appropriate documentation and the state of the service and
Machine
maintenance work are available on site to the operating and
service personnel
Access security
PROFINET • Protection against unauthorized access to the drive
Industrial Ethernet information
Integration of customer-specific websites
• Integrating customer know-how into the websites enables
the quick, purposeful diagnostics of the customer application

■ Application
G_D211_EN_00353a

The web server is ideal for applications not requiring any special
software (STARTER) or version dependencies. Easy diagnostics
and maintenance are possible both locally and remotely,
provided appropriate security measures are applied.

9 SINAMICS S120
with CU320-2 PN
SINAMICS S120
with CU310-2 PN
■ More information
Further information about the SINAMICS Web server is available
Integration of the SINAMICS Web server as shown by the example of on the internet at
the SINAMICS S120 and PROFINET communication www.siemens.com/sinamics-webserver
The SINAMICS web server is available from SINAMICS firmware
V4.7 or higher on the CompactFlash card for the Control Units
• CU310-2 DP
• CU310-2 PN
• CU320-2 DP
• CU320-2 PN
For further information, refer to CU310-2 and CU320-2 Control
Units.

9/12 Siemens D 21.3 · 2022


© Siemens 2022

Tools and engineering


Engineering tools
Drive ES engineering software

■ Overview ■ Design
The following software packages are available for selection:
SIMATIC Programs Configuration / Commissioning • STARTER
• Drive ES PCS 7 (APL Style or Classic Style) /
Drive ES PCS 7 / Drive ES PCS neo
STARTER
Drive ES PCS neo
STARTER
The STARTER commissioning tool is for first-time users of the
world of Totally Integrated Automation and the basic software for
setting the parameters of the SINAMICS and MICROMASTER 4
drives online and offline in this environment. The STARTER
integration enables both the automation system and the drives
to be handled using the SIMATIC Manager software. STARTER is
the starting point for common data archiving in complete
projects and for extending the use of the routing and the

G_D211_EN_00275d
SIMATIC teleservice to drives. STARTER provides the
configuration tools for the Motion Control functions – device-to-
device communication, equidistance and isochronous operation
with PROFIBUS DP and ensures that drives with PROFINET IO
are simply integrated into the SIMATIC environment.
Drive ES PCS 7 (APL Style or Classic Style)
Drive ES/STARTER is the engineering system used to integrate
the communication, configuration and data management Drive ES PCS 7 links the drives with a PROFIBUS DP interface
functions of Siemens drive technology into the SIMATIC into the SIMATIC PCS 7 process control system, and it requires
automation world easily, efficiently and cost-effectively. that SIMATIC PCS 7, V6.1 and higher has first been installed.
Drive ES PCS 7 provides a block library with blocks for the
The following software packages are available for selection: drives and the corresponding faceplates for the operator station,
• STARTER which enables the drives to be operated from the PCS 7 process
• Drive ES PCS 7 / Drive ES PCS neo control system. From V6.1 and higher, drives will also be able to
be represented in the PCS 7 Maintenance Station.
The Drive ES (Drive Engineering Software) fully integrates drives
from Siemens into the world of Totally Integrated Automation From Drive ES PCS 7 V8.0 and higher, two versions of the library
(STEP 7 V5.x). are available: The APL (Advanced Process Library) variant and
the previous version in the so-called Classic Style.
Detailed contents of the Drive ES PCS 7
(APL Style or Classic Style)
• Block library for SIMATIC PCS 7 Faceplates and control
blocks for SIMOVERT MASTERDRIVES VC and MC, as well as
MICROMASTER/MIDIMASTER of the third and fourth
generation and SIMOREG DC MASTER and SINAMICS
• STEP 7 V5.x slave object manager for user-friendly
configuration of drives and non-cyclic PROFIBUS DP
communication with the drives
• STEP 7 V5.x device object manager for easy configuration
of drives with PROFINET-IO interfaces (V8.0 SP1 and higher)
• SETUP program for installing the software in the
SIMATIC PCS 7 environment
Drive ES PCS neo
Siemens SINAMICS drives can be controlled via 9
SIMATIC PCS neo and operated and monitored on the OCM
client with the SINAMICS library Drive ES PCS neo. The
drive ES PCS neo faceplates make the data relevant for system
operation available on the OCM client. The STARTER
commissioning tool on the engineering server can also be used
for parameter assignment, commissioning and detailed
diagnostics of the SINAMICS drives.

Siemens D 21.3 · 2022 9/13


© Siemens 2022

Tools and engineering


Engineering tools
Drive ES engineering software

■ Selection and ordering data Description Article No.


Drive ES PCS 7 APL V9.1 SPx *)
Description Article No. Block library for PCS 7 for the integration of drives
Drive ES PCS 7 V8.2 SPx *) in APL Style (Advanced Process Library)
Block library for PCS 7 for the integration of drives Requirement: PCS 7 V9.1 or higher
in Classic Style (as predecessor) Type of delivery: CD-ROM
Requirement: PCS 7 V8.2 and higher Languages: en, de, fr, it, es
With electronic documentation
Type of delivery: CD-ROM
• Single-user license incl. 1 runtime license 6SW1700-2JD01-0AA0
Languages: en, de, fr, it, es
With electronic documentation • Runtime license (without data storage medium) 6SW1700-5JD00-1AC0
• Single-user license incl. 1 runtime license 6SW1700-8JD00-2AA0 • Update service for single-user license 6SW1700-0JD01-0AB2
• Runtime license (without data storage medium) 6SW1700-5JD00-1AC0 • Upgrade of APL V8.x, V9.x to V9.1 SPx *) or 6SW1700-2JD01-0AA4
Drive ES PCS 7 V6.x, V7.x, V8.x, V9.x classic to
• Update service for single-user license 6SW1700-0JD00-0AB2
Drive ES PCS 7 APL V9.1 SPx *)
• Upgrade from V6.x/V7.x/V8.x to V8.2 SPx *) 6SW1700-8JD00-2AA4
Drive ES PCS neo V3.0 / V3.1
Drive ES PCS 7 APL V8.2 SPx *)
Block library for SIMATIC PCS neo for the integra-
Block library for PCS 7 for the integration of drives tion of SINAMICS drives
in APL Style (Advanced Process Library)
Requirement: PCS neo V3.0 or higher
Requirement: PCS 7 V8.2 and higher
Type of delivery V3.0: The SINAMICS library is a
Type of delivery: CD-ROM component of the SIMATIC PCS neo V3.0 prod-
Languages: en, de, fr, it, es uct.
With electronic documentation Type of delivery V3.1: Integration via the import of
• Single-user license incl. 1 runtime license 6SW1700-8JD01-2AA0 a SINAMICS device type file (product support).
• Runtime license (without data storage medium) 6SW1700-5JD00-1AC0 License reference for the license code and the
• Update service for single-user license 6SW1700-0JD01-0AB2 Certificate of License for the Drive ES PCS neo
SINAMICS library via OSD
• Upgrade of APL V8.x to V8.2 SPx *) or 6SW1700-8JD01-2AA4 Languages: de, en
Drive ES PCS 7 V6.x, V7.x, V8.x classic to
Drive ES PCS 7 APL V8.2 SPx *) License for the Drive ES PCS neo SINAMICS 6SW1700-1JE01-0AH0
library (engineering and runtime software)
Drive ES PCS 7 V9.0 SPx *)
Floating license for 1 engineering user on the
Block library for PCS 7 for the integration of drives engineering server
in Classic Style (as predecessor)
A runtime license for a PCS neo Controller (single
Requirement: PCS 7 V9.0 or higher license for 1 installation)
Type of delivery: CD-ROM
Languages: en, de, fr, it, es Runtime license Drive ES PCS neo SINAMICS 6SW1700-1JE00-1AH0
With electronic documentation library
• Single-user license incl. 1 runtime license 6SW1700-1JD00-0AA0 To execute the function blocks for a
• Runtime license (without data storage medium) 6SW1700-5JD00-1AC0 SIMATIC PCS neo Controller
• Update service for single-user license 6SW1700-0JD00-0AB2 Language-neutral, single license for 1 installation
• Upgrade from V6.x/V7.x/V8.x/V9.x to V9.0 SPx *) 6SW1700-1JD00-0AA4 Type of delivery: Electronic Certificate of License
(OSD)
Drive ES PCS 7 APL V9.0 SPx *)
Block library for PCS 7 for the integration of drives
in APL Style (Advanced Process Library) ■ Options
Requirement: PCS 7 V9.0 or higher
Drive ES PCS 7 Software Update Service
Type of delivery: CD-ROM
Languages: en, de, fr, it, es A software update service can also be purchased for the
With electronic documentation Drive ES PCS 7 software. The user will automatically receive the
• Single-user license incl. 1 runtime license 6SW1700-1JD01-0AA0 latest software, service packs and full versions for one year after
• Runtime license (without data storage medium) 6SW1700-5JD00-1AC0 ordering.
• Update service for single-user license 6SW1700-0JD01-0AB2
• Upgrade of APL V8.x, V9.x to V9.0 SPx *) or 6SW1700-1JD01-0AA4 The update service can only be ordered in addition to an existing
Drive ES PCS 7 V6.x, V7.x, V8.x, V9.x classic to (i.e. previously ordered) full version.
Drive ES PCS 7 APL V9.0 SPx *)
• Period of update service: 1 year
9 Drive ES PCS 7 V9.1 SPx *)
The update service is automatically extended by 1 further year
Block library for PCS 7 for the integration of drives
in Classic Style (as predecessor) unless canceled up to 6 weeks prior to expiration.
Requirement: PCS 7 V9.1 or higher Description Article No.
Type of delivery: CD-ROM
Drive ES PCS 7
Languages: en, de, fr, it, es
With electronic documentation • Update service for single-user license 6SW1700-0JD00-0AB2
• Single-user license incl. 1 runtime license 6SW1700-2JD00-0AA0 Drive ES PCS 7 APL
• Runtime license (without data storage medium) 6SW1700-5JD00-1AC0 • Update service for single-user license 6SW1700-0JD01-0AB2
• Update service for single-user license 6SW1700-0JD00-0AB2
• Upgrade from V6.x/V7.x/V8.x/V9.x to V9.1 SPx *) 6SW1700-2JD00-0AA4
■ More information
Further information is available on the internet at:
www.siemens.com/drive-es

*) Orders are automatically supplied with the latest Service Pack (SP).

9/14 Siemens D 21.3 · 2022


© Siemens 2022

Tools and engineering


Engineering tools
Configuration with EPLAN

■ Overview
Configuring with EPLAN

EPLAN is an engineering software for configuring electrical EPLAN user interface


installations. The EPLAN platform combines expert systems
for various disciplines, such as electrical, fluid and EMC The macros are provided in the file format EDZ (EPLAN Data
engineering (EMC = electrical, measuring and control Archived Zipped). An EDZ file is an archive for article master
engineering) as well as control cabinet and plant engineering. data, CAx data and macros. A macro in EDZ format contains
It provides the wiring information required to determine the the following data:
optimal laying routes, connection lengths, bundle diameters, • Internal circuit diagrams
and design of the cable tree. • Wiring diagrams
EPLAN Electric P8 – an EPLAN module – is CAE software • Product master data
specifically for configuring documentation and managing
electrical automation projects for machines and systems. • Product images
EPLAN Electric P8 offers the following functions: • Data sheets
• Creating circuit diagrams for control cabinets EPLAN Electric P8 macros for SINAMICS components are
• Managing article master data available in the following tools:
• Automatic generation of bills of materials, terminal plans, • Siemens Product Configurator
PLC diagrams and overviews (www.siemens.com/spc)
• Preparation of the documentation for the configured system • CAx Onlinemanager
• Design of the mechanical control cabinet configuration • Image database (download)

EPLAN macros for SINAMICS components EPLAN projects for SINAMICS converter cabinet units
EPLAN Electric P8 macros are available as downloads without EPLAN projects are available for SINAMICS converter cabinet
charge, so that SINAMICS components can be easily and units, that simplify the configuration, and save time throughout
cost-effectively integrated into an EPLAN project. Macros are the entire engineering process. EPLAN projects are available for
available for the following components: the following converter cabinet units:
• SINAMICS G120P, PM330 Power Modules • SINAMICS G120P Cabinet
• SINAMICS G130 built-in units • SINAMICS G150
• SINAMICS S120 chassis units • SINAMICS S120 Cabinet Modules
• SINAMICS DCM DC converters • SINAMICS S150
• Line and motor-side components The complete EPLAN project is digitally delivered.
The order is made by selecting the additional option D01.
• DC link components
• Control Units
9
• Supplementary system components
Using EPLAN Electric P8 macros substantially shortens
the configuration time. All the necessary information about a
component is supplied at the press of a button. This ensures
that the data is up-to-date and correct – and mistakes/errors can
be avoided.

Siemens D 21.3 · 2022 9/15


© Siemens 2022

Tools and engineering


Engineering tools
Configuration with EPLAN

■ Overview
The following data are delivered when the option D01 is ordered:
• EPLAN project as a ZW1 file
• A PDF version of the project
The EPLAN project includes the following documentation
components:
• Title sheet
• Table of contents
• List of the structure identifiers used
• General layout, external view
• General layout, internal view
• Circuit diagram
• Terminal diagram
• Spare parts list

EPLAN project: Dimension drawing

EPLAN project: Circuit diagram

9/16 Siemens D 21.3 · 2022


© Siemens 2022

Tools and engineering


Engineering information
Planning

■ Overview
General procedure when engineering Configuration begins with the mechanical interface to the
machine. A suitable motor is selected according to the specified
The function description of the machine provides the basis for torques and speeds. A matching power unit is then also chosen.
the configuration. The definition of the components is based on Depending on the requirements of the machine, the motor is
physical interdependencies and is usually carried out as follows: supplied as a single drive via a Power Module or within
Step Description of configuration activity a multi-motor drive group via a Motor Module. Once the basic
components have been defined, the system components for
1 Clarification of type of drive matching to the electrical and mechanical interfaces are
2 Specification of the supplementary conditions and integration in the selected.
automation system
The SIZER for Siemens Drives engineering tool (integrated in the
3 Definition of the load, calculation of the max. load torque, selection TIA Selection Tool) allows the correct components to be selected
of the motor
quickly and easily. Based on the torque and speed characteris-
4 Definition of the Motor Module tics entered, SIZER for Siemens Drives (integrated in the TIA
5 Repetition of steps 3 and 4 for additional axes Selection Tool) guides the user through the configuring process,
identifying suitable motors and matching SINAMICS power units
6 Calculation of the required DC link power and definition of the
Line Module and other system components.
7 Specification of the required control performance and selection of Important information about SINAMICS S120 components that
the Control Unit, definition of component cabling are needed to create a drive system subject to certain
8 Specification of the line-side power options (main switch, fuses, line supplementary conditions can be found in the SINAMICS Low
filters, etc.) and cable cross-sections for system connection and Voltage Engineering Manual, and in the online help for the SIZER
motor connection for Siemens Drives engineering tool (integrated in the TIA
9 Definition of additional system components Selection Tool).
10 Calculation of the current requirement for the 24 V DC supply for
the components and specification of power supplies
(SITOP devices, Control Supply Modules)
11 Specification of components for connection system
12 Configuration of drive line-up components
13 Thermal design of the control cabinet

Siemens D 21.3 · 2022 9/17


© Siemens 2022

Tools and engineering


Engineering information
EMC notes for applying product standard EN 61800-3

■ Overview
The electromagnetic compatibility describes – according to the Categories
definition of the EMC Directive – the "capability of a device to
work satisfactorily in the electromagnetic environment without Four different categories are defined in EN 61800-3 Ed.2
itself causing electromagnetic interference which is unaccept- depending on the installation site and the output power of the
able for other devices present in this environment". To guarantee drive:
that the appropriate EMC Directives are observed, the devices • Category C1: Drive systems for rated voltages <1000 V for
must demonstrate a sufficiently high noise immunity, and also unlimited use in the first environment.
the emitted interference must be limited to acceptable values. • Category C2: Stationary drive systems for rated voltages
The product standard EN 61800-3 describes the EMC <1000 V for use in the second environment. Use in the first
requirements placed on "Variable-speed drive systems". environment is possible if the drive system is operated and
installed by qualified personnel. The warning information and
A variable-speed drive system (or Power Drive System PDS) installation instructions supplied by the manufacturer must be
consists of the Control Unit and Power Module or Control Unit, observed.
Line Module, and Motor Module plus the relevant electric motors • Category C3: Drive systems for rated voltages <1000 V for
and encoders including connecting cables. The driven machine exclusive use in the second environment.
is not part of the drive system.
• Category C4: Drive systems for rated voltages 1000 V or for
Environments rated currents 400 A for use in complex systems in
EN 61800-3 defines different limit values depending on the site the second environment. An EMC plan must be drawn up.
of installation of the drive system, referred to as the first and The following diagram shows how the four categories are
second environments. assigned to the first and second environments:
Residential buildings or locations at which the drive system
is directly connected to a public low-voltage supply without C1
intermediate transformer are defined as the first environment.
A second environment refers to all locations outside residential
areas, or industrial sites which are supplied from the medium- C2
voltage network via a separate transformer. First Second
environment environment
C3

C4
G_D213_EN_00009a

9/18 Siemens D 21.3 · 2022


© Siemens 2022

Tools and engineering


Engineering information
EMC notes for applying product standard EN 61800-3

■ Configuration
The SINAMICS S120 and SINAMICS S150 drive systems Interference emission – complying with Category C2 second
are basically suitable for operation in the second environment environment
(Categories C3 and C4). The measures necessary for operation
in the first and second environment (Category C2) are listed Regarding interference emission, to comply with the limit values
below. according to EN 61800-3 second environment, Category C2,
the following measures must be applied:
Measures for complying with product standard EN 61800-3 • The drive system must be installed in compliance with EMC
second environment regulations by appropriately trained professionals.
Interference immunity • The drive system requires a radio interference suppression
filter, Category C2 (as optional external line filter with/without
All SINAMICS S120 drive systems, SINAMICS S120 Cabinet line reactor)
Modules, and SINAMICS S150 are suitable for use in the second
environment. • The pulse frequency is less than or equal to the rated pulse
frequency
Regarding interference immunity, they can be used in both the
first and second environments. • The maximum motor cable length is complied with (shielded)
• Line supply with grounded neutral point
(TN/TT supply system)
Device-specific assignment of the measures to comply with product standard EN 61800-3 second environment, Category C2
SINAMICS S120 chassis Measures for
Radio interference Maximum pulse Maximum motor cable
suppression filter, frequency fp length (shielded)
Category C2
Devices Line voltage Frame size kHz m
Active Line Modules 380 ... 480 V 3 AC FX ... JX External line filter required 4 3) 300
GXL ... JXL 1)
500 ... 690 V 3 AC FX ... JX External line filter required 4 3) 300
HXL and JXL 1)
Smart Line Modules 380 ... 480 V 3 AC GX ... JX External line filter required 4 3) 300
500 ... 690 V 3 AC GX ... JX External line filter required 4 3) 300
Basic Line Modules 380 ... 480 V 3 AC FB ... GD External line filter plus line 4 3) 100
FBL and GBL 1) reactor required 2)
500 ... 690 V 3 AC FB ... GD External line filter plus line 4 3) 100
FBL and GBL 1) reactor required 2)
Power Modules 380 ... 480 V 3 AC FX and GX External line filter plus line 2 100
FL and GL 1) reactor required 2)

1) 3)
For liquid-cooled and water-cooled devices on request Refers to the pulse frequency of the Motor Modules.
2)
Selection and ordering data for line filters and line reactors, see sections
Line-side power components.

Siemens D 21.3 · 2022 9/19


© Siemens 2022

Tools and engineering


Engineering information
EMC notes for applying product standard EN 61800-3

■ Configuration
SINAMICS S120 Cabinet Modules, air-cooled 1) Measures for
Radio interference Maximum pulse Maximum motor
suppression filter, frequency fp cable length
Category C2 (shielded)
Cabinet Modules Line voltage Frame size kHz m
Line Connection Modules for 380 ... 480 V 3 AC FX ... JX Option L00 4 3) 300
Active Line Modules (L42)
500 ... 690 V 3 AC FX ... JX Option L00 4 3) 300
Line Connection Modules for 380 ... 480 V 3 AC GX ... JX Option L00 4 3) 300
Smart Line Modules (L44) 3)
500 ... 690 V 3 AC GX ... JX Option L00 4 300
Line Connection Modules for 380 ... 480 V 3 AC FB ... GD Option L00 2) 4 3) 100
Basic Line Modules (L43)
500 ... 690 V 3 AC FB ... GD Option L00 2) 4 3) 100

SINAMICS S150 Measures for


Radio interference Maximum pulse Maximum motor
suppression filter, frequency fp cable length
Category C2 (shielded)
Converter cabinet units Line voltage Frame size kHz m
S150 380 ... 480 V 3 AC FI+FX ... JI+JX Option L00 4 3) 300
500 ... 690 V 3 AC FI+FX ... JI+JX Option L00 4 3) 300

Interference emission – complying with Category C3 second


environment ■ More information
Covered by Active Interface Modules in chassis format in the Converters are equipment used on a professional basis,
standard version of all SINAMICS S120 Cabinet Modules, deployed in certain areas of business and industry – and are not
SINAMICS S150 converter cabinet units, and SINAMICS S120 operated in the general public domain.
Line Modules. A line reactor is required for Power Modules in Further information on SINAMICS S120 components,
chassis format. SINAMICS S120 Cabinet Modules, and SINAMICS S150,
The maximum cable lengths and pulse frequencies which are needed to create a drive system subject to certain
(see previous tables) must be taken into consideration. supplementary conditions can be found in the SINAMICS Low
Voltage Engineering Manual:
Interference emission – complying with Category C4 second https://support.industry.siemens.com/cs/document/83180185
environment
When connected to IT line supplies, only devices without
integrated filter are permissible. To limit symmetrical interference
emission, suitable external filters without capacitors connected
to ground must be used.
Further selected accessories are available from the
"Siemens Product Partner for Drives Options"
www.siemens.com/drives-options-partner
Measures for complying with product standard EN 61800-3
first environment
The SINAMICS S120 drive systems, SINAMICS S120 Cabinet
Modules air-cooled, and SINAMICS S150 are basically suitable
for use in the second environment.
9 Regarding interference immunity, they can be used in both
the first and second environments.
Interference emission – complying with Category C2 first
environment
For use in the first environment, in addition to the requirements
for use in the second environment, device-specific notes to
maintain the harmonic current limits must be taken into
consideration. Here, EMC product standard EN 61800-3
makes reference to the standards pertaining to harmonic
currents: EN 61000-3-2 and EN 61000-3-12.

1) For liquid-cooled Cabinet Modules on request 3) Refers to the pulse frequency of the Motor Modules.
2) Option L22 (scope of supply without line reactor) not permissible for use in
Category C2 second environment.

9/20 Siemens D 21.3 · 2022


© Siemens 2022

Tools and engineering


Engineering information
Engineering Manual

■ Overview
The Engineering Manual is divided into several sections with
different layouts.
The first chapter – Basics and system description – essentially
explains the physical basics of variable-speed electric
AC drives and provides a generally valid system description
of the SINAMICS series devices.
The second chapter – EMC design guideline – discusses the
topic of Electromagnetic Compatibility (EMC) and provides all
the information required to configure and install drives with the
specified SINAMICS devices in compliance with
EMC guidelines.
The following chapters – Configuration of the SINAMICS G130,
G150, S120 built-in units, S120 Cabinet Modules and S150
devices – discuss device-specific topics, which go beyond the
contents of the generally valid system descriptions.
The information provided addresses technically qualified and
trained personnel. It is the responsibility of the configuration
To correctly select and configure the devices listed in this engineer to evaluate the completeness of the information
catalog, we would like to refer to the SINAMICS Low Voltage provided for the respective application. This person also has the
Engineering Manual. This supplements the Catalogs D 11 and final system responsibility for the entire drive or the plant.
D 21.3, and is intended to simplify the handling of SINAMICS
series devices.
This manual is only available in electronic form and only in
German and English. It is available as a PDF in the Information
and Download Center:
https://support.industry.siemens.com/cs/document/83180185
The Engineering Manual contains general information on the
basics of variable-speed electric AC drives, as well as detailed
system descriptions and direct specifications for the following
SINAMICS series devices:
• SINAMICS G130 Drive Converter Chassis Units
(Catalog D 11)
• SINAMICS G150 Drive Converter Cabinet Units
(Catalog D 11)
• SINAMICS S120 Modular Built-in Units
(Catalogs D 21.3 and D 21.4)
• SINAMICS S120 Modular Cabinet Units
(Catalog D 21.3)
• SINAMICS S150 Converter Cabinet Units
(Catalog D 21.3)
As a supplement to the Catalog D 21.3, the SINAMICS Low
Voltage Engineering Manual SINAMICS S120 Chassis-2 and
Cabinet Modules-2 is available for the device-specific topics for
the device range SINAMICS S120 Chassis-2 and SINAMICS
S120 Cabinet Modules-2.
The Engineering Manual contains general information on the
9
basics of variable-speed electric AC drives, as well as detailed
system descriptions and direct specifications for the following
SINAMICS series devices:
• Modular Built-In Units SINAMICS S120 Chassis-2
(Catalog D 21.3)
• Modular Cabinet Units SINAMICS S120 Cabinet Modules-2
(Catalog D 21.3)
The manual is only available as a document in electronic form in
German and English:
https://support.industry.siemens.com/cs/document/109791862

Siemens D 21.3 · 2022 9/21


© Siemens 2022

Tools and engineering

Notes

9/22 Siemens D 21.3 · 2022


10
© Siemens 2022

Services and Documentation

10/2 Partner at Siemens

10/3 Industry Services


10/4 Portfolio overview
10/6 Online Support

10/7 Service & Support


10/7 Extension of the liability for defects

10/9 Training
10/9 SITRAIN - Digital Industry Academy
10/11 Range of training courses

10/13 Spare parts services


10/12 Field and maintenance services
10/13 Spare parts services
10/16 Repair services

10/17 SPARES on Web

10/18 mySupport documentation

10/19 Documentation

Siemens D 21.3 · 2022


© Siemens 2022

Services and Documentation

Partners
Partners at Siemens

At your service locally, around the globe for consulting, sales,


training, service, support, spare parts on the entire portfolio of
Siemens.
Your partner can be found in our Personal Contacts Database at:
www.siemens.com/automation-contact
You start by selecting
• the required competence,
• products and branches,
• a country and a city
or by a
• location search or free text search.

10

10/2 Siemens D 21.3 · 2022


© Siemens 2022

Services and Documentation


Industry Services

■ Overview

Support and Training Digital Industry Service


Consulting Services Services Programs and
Services Agreements

Spare Parts
Services

Repair Field and Retrofit and


Services Maintenance Modernization
Services Services

G_DA65_XX_00272b

Keep your business running and shaping your digital future – with Industry Services
Optimizing the productivity of your equipment and operations You can rely on our highly dedicated team of engineers, techni-
can be a challenge, especially with constantly changing market cians and specialists to deliver the services you need – safely,
conditions. Working with our service experts makes it easier. professionally and in compliance with all regulations. We are
We understand your industry's unique processes and provide there for you, where you need us, when you need us.
the services needed so that you can better achieve your busi-
ness goals. www.siemens.com/industryservices

You can count on us to maximize your uptime and minimize your


downtime, increasing your operations' productivity and reliabil-
ity. When your operations have to be changed quickly to meet a
new demand or business opportunity, our services give you the
flexibility to adapt. Of course, we take care that your production
is protected against cyber threats. We assist in keeping your 10
operations as energy and resource efficient as possible and re-
ducing your total cost of ownership. As a trendsetter, we ensure
that you can capitalize on the opportunities of digitalization and
by applying data analytics to enhance decision making: You can
be sure that your plant reaches its full potential and retains this
over the longer lifespan.

Siemens D 21.3 · 2022 10/3


© Siemens 2022

Services and Documentation


Industry Services
Industry Services – Portfolio overview

■ Overview
Digital Industry Support and
Services Consulting
Services

Digital Industry Services make your industrial processes trans- Industry Online Support site for comprehensive information,
parent to gain improvements in productivity, asset availability, application examples, FAQs and support requests.
and energy efficiency.
Technical and Engineering Support for advice and answers
Production data is generated, filtered and translated with intelli- for all inquiries about functionality, handling, and fault
gent analytics to enhance decision-making. clearance. The Service Card as prepaid support for value added
services such as Priority Call Back or Extended Support offers
This is done whilst taking data security into consideration and the clear advantage of quick and easy purchasing.
with continuous protection against cyber-attack threats.
Information & Consulting Services, e.g. SIMATIC System
www.siemens.com/global/en/products/services/industry/ Audit; clarity about the state and service capability of your auto-
digital-industry-services.html mation system or Lifecycle Information Services; transparency
on the lifecycle of the products in your plants.
https://support.industry.siemens.com/cs/ww/en/sc/2235

Training Spare Parts


Services Services

From the basics and advanced to specialist skills, SITRAIN Spare Parts Services are available worldwide for smooth and
courses provide expertise right from the manufacturer – and fast supply of spare parts – and thus optimal plant availability.
encompass the entire spectrum of Siemens products and Genuine spare parts are available for up to ten years. Logistic
systems for the industry. experts take care of procurement, transport, custom clearance,
storage and order management. Reliable logistics processes
Worldwide, SITRAIN courses are available wherever you need a ensure that components reach their destination as needed.
training course in more than 170 locations in over 60 countries.
Since not all spare parts can be kept in stock at all times,
https://support.industry.siemens.com/cs/ww/en/sc/2226 Siemens offers a preventive measure for spare parts provision-
ing on the customer's premises with optimized Spare Parts
Packages for individual products, custom-assembled drive
components and entire integrated drive trains – including risk
consulting.
Asset Optimization Services help you design a strategy for
parts supply where your investment and carrying costs are
reduced and the risk of obsolescence is avoided.
10 https://support.industry.siemens.com/cs/ww/en/sc/2110

10/4 Siemens D 21.3 · 2022


© Siemens 2022

Services and Documentation


Industry Services
Industry Services – Portfolio overview

■ Overview
Repair Retrofit and
Services Modernization
Services

Repair Services are offered on-site and in regional repair centers Provide a cost-effective solution for the expansion of entire
for fast restoration of faulty devices’ functionality. plants, optimization of systems or upgrading existing products
to the latest technology and software, e.g. migration services for
Also available are extended repair services, which include addi- automation systems.
tional diagnostic and repair measures, as well as emergency
services. Service experts support projects from planning through commis-
sioning and, if desired over the entire extended lifespan, e.g.
https://support.industry.siemens.com/cs/ww/en/sc/2154 Retrofit for Integrated Drive Systems for an extended lifetime of
your machines and plants.
https://support.industry.siemens.com/cs/ww/en/sc/2286

Service
Field and
Programs and
Maintenance
Agreements
Services

Siemens specialists are available globally to provide expert field A technical Service Program or Agreement enables you to easily
and maintenance services, including commissioning, functional bundle a wide range of services into a single annual or multi-
testing, preventive maintenance and fault clearance. year agreement.
All services can be included in customized service agreements
with defined reaction times or fixed maintenance intervals. You pick the services you need to match your unique require-
ments or fill gaps in your organization’s maintenance capa-
https://support.industry.siemens.com/cs/ww/en/sc/2265 bilities.
Programs and agreements can be customized as KPI-based
and/or performance-based contracts.
https://support.industry.siemens.com/cs/ww/en/sc/2275

10

Siemens D 21.3 · 2022 10/5


© Siemens 2022

Services and Documentation


Industry Services
Online Support

■ Overview

Online Support – fast, intuitive, whenever you want,


wherever you need

Web

www.siemens.com/online-support

App

Scan the QR code


for information on
our Online Support
app.

FAQ / Application examples


Information about industrial products, programming and configuration as well as application
examples

Technical information
Videos, documentation, manuals, updates, product notes, compatibility tool, certificates, planning data
such as dimensional drawings, product data, 3D models

Forum
Exchange information and experience with other users and experts

Online Support for Siemens Industry Products


Siemens Industry and Online Support with some 1.7 million visi- In connection with the challenges and opportunities related to
tors per month is one of the most popular web services provided digitalization you can look forward to continued support with
by Siemens. It is the central access point for comprehensive innovative offerings.
10 technical know-how about products, systems and services for
automation and drives applications as well as for process
industries.

10/6 Siemens D 21.3 · 2022


© Siemens 2022

Services and documentation


Service & Support
Extension of the liability for defects

■ Overview
SINAMICS 120 Chassis • 12 months of standard warranty
Service protect • Optional extension via Service Protect
- 6 months free of charge after product registration at:
Service Protect allows our customers to purchase an extended https://myregistration.siemens.com
period of manufacturer liability of up to 5 years. - chargeable for additional 3 or 5 years.
Extended warranty Depending on the hardware product, the correct service MLFB
Siemens offers for SINAMICS S120 chassis units an extended with an assignment list must be chosen.
warranty up to 6½ years: More information is available at:
https://support.industry.siemens.com/cs/ww/en/sc/4842
SINAMICS 120 Cabinet Modules
We provide the option of extending the liability for defects period 2. Extended liability for defects period after the product has
beyond the normal period for our SINAMICS S120 Cabinet already been delivered
Modules and SINAMICS S150 cabinet units. The standard for
defects period, as listed in our standard conditions for the sup- If a product has already been delivered, an extended liability for
ply of services and products, is 12 months. defects period can be ordered if the original liability for defects
period has still not expired. In addition to the article number
1. Extended liability for defects when ordering new products specified on the rating plate, the serial number must also be
stated in the order.
When ordering new products, it is possible to extend the stan-
dard liability for defects period for an additional price. Various The following article numbers are used:
extension periods can be selected.
Extended liability for defects for converters
Extended liability for defects for converters Article No. Text
Additional ordering Additional text 9LD1730-0AA24 Extension of the liability for defects period by
data -Z with 12 months to a total of 24 months (2 years) after
order code being delivered
Q80 Extension of the liability for defects period by 9LD1730-0AA30 Extension of the liability for defects period by
12 months to a total of 24 months (2 years) after 18 months to a total of 30 months (2½ years) after
being delivered being delivered
Q81 Extension of the liability for defects period by 9LD1730-0AA36 Extension of the liability for defects period by
18 months to a total of 30 months (2½ years) after 24 months to a total of 36 months (3 years) after
being delivered being delivered
Q82 Extension of the liability for defects period by 9LD1730-0AA42 Extension of the liability for defects period by
24 months to a total of 36 months (3 years) after 30 months to a total of 42 months (3½ years) after
being delivered being delivered
Q83 Extension of the liability for defects period by 9LD1730-0AA48 Extension of the liability for defects period by
30 months to a total of 42 months (3½ years) after 36 months to a total of 48 months (4 years) after
being delivered being delivered
Q84 Extension of the liability for defects period by 9LD1730-0AA60 Extension of the liability for defects period by
36 months to a total of 48 months (4 years) after 48 months to a total of 60 months (5 years) after
being delivered being delivered
Q85 Extension of the liability for defects period by
48 months to a total of 60 months (5 years) after
being delivered

Overview of the extended liability for defects period

Article No. Z option Extension period, by

for new order 12 months 18 months 24 months 30 months 36 months 48 months


for re-order

9LD1730-0AA24 Q80 12
Standard
9LD1730-0AA30 Q81 period of 18
G_D213_EN_00093a

9LD1730-0AA36 Q82 liability for 24


9LD1730-0AA42
9LD1730-0AA48
Q83
Q84
defects
12 months
30
36
10
9LD1730-0AA60 Q85 48

Total extension period from 1 year to max. 4 years

Product delivery by Siemens Beginning of the extension of liability for defects


following the standard period of liability for defects

Siemens D 21.3 · 2022 10/7


© Siemens 2022

Services and documentation


Service & Support
Extension of the liability for defects

■ Overview
Conditions for an extension of the liability for defects: 6. For all liability of defect extensions, all of the regular mainte-
nance intervals must be complied with according to what is
1. The liability for defects period can be extended only once, i.e. specified in the operating instructions. When ordering the
it is not possible to extend an extension. If a product has appropriate maintenance, this must be carried out by
already been delivered, an extended liability for defects pe- Siemens or by personnel authorized by Siemens. The corre-
riod can only be ordered if the original liability for defects sponding maintenance documentation and history must be
period has still not expired. submitted when making liability for defect claims.
2. The scope of services provided by an extended liability of 7. The operating conditions correspond to the specifications and
defects period includes all material and work expenditure by data provided in the operating instructions, in the engineering
Siemens for rectification of the damage and, where applica- manual or special conditions specified in the specific
ble, all travel costs and expenses. contract.
3. For all extension periods of liability for defects, when ordering 8. The extended liability for defects excludes wearing parts such
a new product and when reordering, the final destination of as fans or filters. This does not apply if it can be clearly proven
the product must be known (region in which the equipment that the failure is a premature one.
will be finally installed). Please contact your Siemens repre-
sentative for the purpose of providing this information. 9. Otherwise, the general conditions regarding liability for
defects applies as agreed in the delivery contract.
4. The general storage conditions described in the operating
instructions must be adhered to, especially the specifications
for long-term storage. These specifications must be
requested separately from Siemens if necessary.
5. Commissioning must be performed by appropriately qualified
personnel. When making liability for defect claims, under
certain circumstances, it may be necessary to submit the
commissioning report to the department making the decision.

10

10/8 Siemens D 21.3 · 2022


© Siemens 2022

Services and Documentation


SITRAIN – Digital Industry Academy

■ Introduction

The Future of Learning starts now


Globalization, digitalization, new work, Internet of Things, new business models – our way of working, living and learning is changing
rapidly. With SITRAIN, the future of learning begins today: SITRAIN stands for a modern learning culture that focuses on the needs
of learners and the demands of innovative companies.
With SITRAIN – Digital Industry Academy, the future of learning is yours.
Face-to-face training or digital training, location-independent, 24/7, on-demand or learning at fixed dates and course times?
With a personal learning consultant, in a team, or on your own responsibility? Everything is possible. SITRAIN offers a wide range of
different learning options with the "Learning Journey", "Learning Membership" and "Learning Event".

The three learning formats of SITRAIN – Digital Industry Academy

Learning Journey Learning Membership Learning Event


The combination for sustainable Securing knowledge through continu- Acquire theoretical and practical
learning success
• The optimal mix of self-study units
ous learning on your own responsibility
• With access to the comprehensive
knowledge in a compact and guided
format 10
and guided live modules and constantly growing range of • You achieve a defined learning goal
• Includes a Learning Membership to self-study units on SITRAIN access, in the shortest possible time
work through the self-study modules the digital learning platform • The learning consultant guides you
and access on-demand content • Search and find specific learning through the practical exercises and
• The SITRAIN learning consultant is content or simply have a look is also exclusively available to you
available for questions and one-on- around – anytime and anywhere during the theoretical sessions for the
one consultations • A modern learning culture through entire duration
• Ideal integration into the daily work continuous learning on your own • Focused learning, outside of the
routine and adaptation to one's own responsibility and transparency daily work routine, in a protected
learning pace. about your learning success in the learning environment – virtually, in the
team or company. training center, or at your company.

Siemens D 21.3 · 2022 10/9


© Siemens 2022

Services and Documentation


SITRAIN – Digital Industry Academy

■ Introduction
The four building blocks of SITRAIN –
Expand your knowledge, apply what you have learned, Digital Industry Academy
develop future skills
Different methods for maximum learning success:
The SITRAIN Digital Industry Academy combines didactically effec-
tive methods and modular options. • Live
• On your own responsibility
• On demand
• Individual
Learn the way you want to learn. For learning success that takes
you further.

Effective Flexible Relevant Continuous

Education and training directly from the manufacturer Training cases catalog
For individual knowledge building, the following topics concern- www.siemens.com/
ing the industrial product and solution portfolio of Siemens are sitrain-catalog-training-cases
available. Experience the new learning culture with SITRAIN.

SITRAIN – Digital Industry Academy


www.siemens.com/sitrain

Find • SITRAIN Learning Journey:


10 your local
offer here
www.siemens.com/sitrain-learning-journey
• SITRAIN Learning Membership:
www.siemens.com/sitrain-learning-membership
SITRAIN – Digital Industry Academy worldwide • SITRAIN Learning Event:
You will find the regional knowledge offer in the country www.siemens.com/sitrain-learning-event
selection. One click will take you to the corresponding website.

10/10 Siemens D 21.3 · 2022


© Siemens 2022

Services and documentation


Training
Range of training courses

■ Overview
Range of training courses for the SINAMICS S120 and The basic and follow-up courses are guaranteed to provide all of
SINAMICS S150 drive systems the technical knowledge that service personnel will need for
commissioning and service.
Here you will find an overview of the training courses available
for SINAMICS S120 and SINAMICS S150. All courses contain as many practical exercises as possible in
order to enable intensive and direct training on the drive system
The courses are modular in design and are directed at a variety and with the tools in small groups.
of target groups as well as individual customer requirements.
You will find further information about course contents and dates
The system overview will acquaint decision-makers and sales on the internet at: www.siemens.com/sitrain-personal.
personnel with the system very quickly.
Title Target group Duration Course code
(all courses are available in English and/or German) Sales personnel, Commissioning Service personnel,
planners, engineers, maintenance
decision-makers programmers technicians
SINAMICS  – – 3 days DR-SYS
System Overview
SINAMICS S120  – – 5 days DR-S12-PL
Designing and Engineering
SINAMICS S120 –  – 5 days DR-S12-PM
Parameterizing and Commissioning with STARTER
SINAMICS S120 –  – 5 days DR-S12-PMT
Parameterizing and Commissioning in the
TIA Portal
SINAMICS S120 –  – 5 days DR-S12-PA
Parameterizing Advanced
SINAMICS S120 –  – 4 days DR-S12-SAF
Parameterizing Safety Integrated
SINAMICS S120 –  – 3 days DR-S12-UP
Switch to TIA-Portal
SINAMICS S120 –  – 5 days DR-S12-OPT
Parameterizing and Optimization
SINAMICS S120 – –  5 days DR-S12-DG
Diagnostics and Service
SINAMICS S120 – –  5 days DR-S12-DGT
Diagnostics and Service in the TIA Portal
SINAMICS S120 –   3 days DR-S12-CHA
Diagnostics on Chassis and Cabinet Units

10

Siemens D 21.3 · 2022 10/11


© Siemens 2022

Services and documentation


Spare parts services
Field and Maintenance Services

■ Overview
Efficient and cost-effective maintenance strategies for the entire product lifecycle
For you as an industry plant operator, maximum system produc-
tivity is your top priority.
Regular machine and plant maintenance performed by qualified
service experts helps you ensure top plant performance for the
long term.
For more information visit us at:
www.siemens.com/field-maintenance-services

General overhaul

■ Overview During the planned general overhaul, wear parts and aging
parts are replaced in accordance with their stated service life so
as to reduce unplanned downtimes. In the case of motors,
Extension of the constant failure rate period replacement of bearings and encoders is also offered in addition
to a general overhaul.
Extension of constant
failure rate period If a fault is detected during a general overhaul, troubleshooting
Operating time of the plant and repair will be performed after requesting confirmation.
In the case of severe wear or major damage, we offer an "as new"
Failure rate

G_NC01_EN_00459a

Ware out spare part instead of a general overhaul for reasons of quality.
failures

■ Benefits
Warranty General overhaul • Preventive replacement of wear parts and aging parts in
accordance with their stated service life
Early
failures Constant failure rate period • Reduction in unplanned plant stoppages
• Enhanced production reliability
Constant failure rate period with general overhaul • Extended availability of your machines/plants
• New liability for defects for 12 months for components which
Extension of phases with a constant failure rate
have undergone a general overhaul
Machines and plants are expected to have a long service life. • Low price
The service life of electronic components and mechanical parts
is, however, limited and normally shorter than the planned
machine/plant operating times. For higher availability of the ■ More information
machines or plants, we offer a general overhaul (preventive You can find more information on the internet at:
maintenance) for electronic components and motors at https://support.industry.siemens.com/cs/sc/2120
favorable conditions.
Contact information for your local Siemens office or national
company is available on the internet at:
www.siemens.com/automation-contact

Function check

10 ■ Overview ■ Benefits
A check is made to ensure that the components function reliably. • The component is checked and can be deployed again
The first step involves cleaning the components. After that, all • The component contains all the known improvements
hardware, software and firmware enhancements are • The customer's own spare parts stock is up-to-date
implemented that are known to the development, production, • Low price
suppliers, service and quality management departments. Using
a comprehensive test concept of series production, all functions
of the software, firmware, ASICs, and complex and less complex ■ More information
function blocks are checked. You can find more information on the internet at:
If a fault is detected during an overhaul, troubleshooting and https://support.industry.siemens.com/cs/sc/2122
repair will be performed after requesting confirmation. In the Contact information for your local Siemens office or national
case of severe wear or major damage, we offer an "as new" company is available on the internet at:
spare part. www.siemens.com/automation-contact

10/12 Siemens D 21.3 · 2022


© Siemens 2022

Services and documentation


Spare parts services
Spare Parts Services

■ Overview
Be safe in an emergency – always the right spare part at hand
Minimum downtimes and optimum use of staff and equipment
are key to long-term success in industry.
But when a failure happens, it can bring the entire plant to a
standstill in the worst case. Since even the best components will
eventually reach the end of their lifecycle, our Spare Parts
Services form the essential basis for smooth operation.
For more information visit us at:
www.siemens.com/spare-parts-services

Delivery of spare parts

■ Overview ■ Benefits
In every sector worldwide, plants and systems are required to • New liability for spare part defects
operate with ever increasing availability. Not having a specific • Long-term spare parts availability
spare part at the right time can result in considerable costs. • Optimum system compatibility
We will provide you with the support you need to prevent a
standstill from occurring in the first place: with a worldwide
network and optimized logistics chains.
■ More information
You can find more information on the internet at:
Order type Logistics service Remark https://support.industry.siemens.com/cs/sc/2112
Standard Cost-optimized: Delivery within the normal national Contact information for your local Siemens office or national
Contracted shipping delivery times by the contracted
company shipping company company is available on the internet at:
www.siemens.com/automation-contact
Plant down- Time-optimized: You choose the shortest possible
time Express, courier, delivery time as it suits you best:
collection • Delivery by means of collection or
courier service
• Delivery by means of express delivery
Emergency Special logistics: Spare parts can be ordered from us 24/7
service Courier – even outside normal working hours, as
well as on weekends or national
holidays.
• Delivery by means of courier service

10

Siemens D 21.3 · 2022 10/13


© Siemens 2022

Services and documentation


Spare parts services
Delivery as exchange product

■ Overview ■ Benefits
With many products, we also offer you the option of an exchange • Price benefits through the option of returning defective parts
in addition to the simple delivery of spare parts. This has the • A spare part is available immediately in the event of failure
advantage that you not only receive the spare part quickly, but • New liability for spare part defects
are able to return the defective device to us for a credit. You
therefore receive our spare part at the lower exchange price. • Long-term spare parts availability
A credit will be awarded on condition that the repair code • Optimum system compatibility
indicates that repurchasing is admissible, a replacement is
obtained from the spare parts store, and that the returned ■ More information
product is repairable.
You can find more information on the internet at:
The order type and logistics service determine the delivery of https://support.industry.siemens.com/cs/sc/2112
spare parts:
Contact information for your local Siemens office or national
Order type Logistics service Remark company is available on the internet at:
www.siemens.com/automation-contact
Standard Cost-optimized: Delivery within the normal national deliv-
Contracted ship- ery times by the contracted shipping
ping company company
Plant down- Time-optimized: You choose the shortest possible deliv-
time Express, courier, ery time as it suits you best:
collection • Delivery by means of collection or cou-
rier service
• Delivery by means of express delivery
Emergency Special logistics: Spare parts can be ordered from us 24/7
service Courier – even outside normal working hours, as
well as on weekends or national holi-
days.
• Delivery by means of courier service

Return
For product returns, we require the following information:
• Reason for return
• If defective: detailed description of the fault
• Machine number
• Machine/system manufacturer
• End user
We will then be able to provide you with additional information in
the repair report/inspection report regarding the diagnosis/
inspection as well as information about the completed repair.

Component upgrade service

■ Overview ■ Benefits
Upgrade service for components: From OLD to NEW • Price benefit through upgrade service
• New liability for new component defects
Machines and plant are expected to have a long service life. The
service life of the electronic components is, however, limited and • Extended availability of your machines/plants
normally shorter than the planned machine/plant operating • Prevention of component failures due to wear and aging
times. To ensure that the required extended availability of the • Prevention of machine stoppages due to unavailability of
machines/plants is achieved, we offer an upgrade service for spare parts
components at an attractive price.
• Reduced spare parts inventories
In the course of their lifecycle, electronic components are
normally redesigned/upgraded several times. With the upgrade • Latest technology
service for components, you will always receive the latest • Easier servicing due to fewer variants
10 technology. • Industry Services through Siemens are assured for the future
A planned component upgrade from OLD to NEW helps to
prevent unplanned machine stoppages and supports a safer ■ More information
and longer machines/plant availability. The upgrade service is
mainly offered for older components that will soon be You can find more information on the internet at:
discontinued. https://support.industry.siemens.com/cs/sc/2112
For information about the latest potential upgrades, please Contact information for your local Siemens office or national
contact your local contact person. The upgrade service for company is available on the internet at:
components can only be offered to machine manufacturers or www.siemens.com/automation-contact
operators.

10/14 Siemens D 21.3 · 2022


© Siemens 2022

Services and documentation


Spare parts services
Return of diagnostic parts

■ Overview ■ More information


Spare parts used for diagnostic purposes from the spare parts You can find more information on the internet at:
store can be returned within 3 months and a credit note for up to https://support.industry.siemens.com/cs/sc/2112
85% is issued.
Contact information for your local Siemens office or national
For unused spare parts in their original packaging, you will company is available on the internet at:
receive a credit of 100% in which case you will be charged a www.siemens.com/automation-contact
fixed price for handling.

■ Benefits
• Can be used for diagnostics
• Reduced spare parts inventories
• Low costs

Stock reduction in spare parts store

■ Overview ■ More information


Fast spare part delivery by Siemens enables manufacturers and You can find more information on the internet at:
plant operators to reduce their spare part stocks. For this pur- https://support.industry.siemens.com/cs/sc/2112
pose, we offer an analysis that shows exactly which parts should
remain in the customer warehouse for a particular machine stock Contact information for your local Siemens office or national
and which can be purchased directly from Siemens. company is available on the internet at:
www.siemens.com/automation-contact
■ Benefits
• Reduced costs
• Stock optimization
• Minimization of fault downtimes

Extended spare part availability

■ Overview ■ More information


We normally retain spare parts for all products and systems for You can find more information on the internet at:
a period of 10 years after discontinuation of product marketing. https://support.industry.siemens.com/cs/sc/2112
In individual cases, when we do not carry spare parts, we will Contact information for your local Siemens office or national
offer a repair. company is available on the internet at:
www.siemens.com/automation-contact
For a wide range of products and systems, spare parts availabil-
ity is extended. We can provide you with the current spare parts
availability for your machines/plants as a service once you have
registered online with identSNAPSHOT.
www.siemens.com/identsnapshot
If you require longer availability of spare parts for your
machines/plants, please contact your local contact person.

■ Benefits
• Higher plant availability
• Security of investment
• Reduction of lifecycle costs

10

Siemens D 21.3 · 2022 10/15


© Siemens 2022

Services and documentation


Repair services

■ Overview ■ Benefits
High quality support in a breakdown – either at your • Short downtimes for machines and plants
premises or at a certified Siemens workshop • Only certified original parts are used
Even the best components eventually reach the end of their life- • Additional services from Siemens:
cycle. The result: downtimes and reduced productivity. - Longer availability of your machine/plant through the early
replacement of wear parts and aging parts
Our Repair Services comprise all service tasks over the entire - Highest standards of quality
product lifecycle, from functional maintenance to increasing - Use of the comprehensive test concept of series production,
performance. In this way, our service experts analyze, repair, including software, firmware, ASICs, complex function
maintain and optimize your components at Siemens blocks, etc.
manufacturer level, so that costly downtimes are minimized. - Implementation of all the hardware and software/firmware
For more information visit us at: enhancements known from development, production,
www.siemens.com/repair-services suppliers, and service and quality management
departments.
Downtimes cause problems in the plant as well as unnecessary • Information supplied by repair report/inspection report
costs. We can help you to reduce both to a minimum – with our
worldwide repair facilities. The advantages for you are: Defects
can be rectified before they cause further harm. ■ More information
Repair is a favorable option when you have specific reasons for You can find more information on the internet at:
not wanting to replace the defective device or part with a new https://support.industry.siemens.com/cs/sc/3098
one (delivery as exchange product).
Contact information for your local Siemens office or national
We maintain a global network of Siemens repair shops and company is available on the internet at:
certified partners to ensure that we will always be able to www.siemens.com/automation-contact
process your repairs quickly.
We can offer you different types of repair depending on your
requirements:
Normal repair
Normal repair at standard conditions normally takes 10 working
days following receipt of the defective item at our repair shop.
Fast repair
In particularly urgent cases, we offer you the option of a fast
repair within 1 or 2 working days for many products at additional
cost.
Mobile repair service
We come to you and perform the required repairs on site, for
example, when the device or component cannot be removed
due to its weight.
Function repair
A function repair is the same as a normal repair but excludes the
repair of cosmetic defects, e.g. scratches, inscriptions, discolor-
ation. The conditions applicable to function repairs should be
observed in this case. The function repair can only be offered to
machine manufacturers or operators. Please contact your local
contact person for more information.
Long Life Repair
As a rule, a spare parts and repair service is offered for electron-
ics products for a period of up to ten years after the period of
active marketing. After this time, these services are generally
only available in the case of acknowledged warranty conditions.
10 Not so at Siemens. The Long Life Repair Service is available for
selected electronic products and standard motors. Siemens
thus offers a complete solution that includes short delivery times,
long availability of original spare parts, economical repairs and
a service availability of up to 25 years.

10/16 Siemens D 21.3 · 2022


© Siemens 2022

Services and documentation

Spares on Web

■ Overview
Spares on Web – online identification of spare parts

Spares on Web is a web-based tool for identifying spare parts.


After you have entered the Article No. and serial number, the
spare parts available for the relevant unit are displayed.
www.siemens.com/sow

10

Siemens D 21.3 · 2022 10/17


© Siemens 2022

Services and documentation

mySupport documentation

■ Overview ■ Benefits
mySupport documentation – • Display
compiling personal documents View, print or download standard documents or personalized
documents
• Configure
Transfer standard documents or parts of them to personalized
documents
• Generate/Manage
Generate and manage personalized documents in the formats
PDF, RTF or XML in all available languages

■ Function
Opening mySupport documentation in the Industry Online
Support portal
• Via the product support, entry type "Manual":
https://support.industry.siemens.com/cs/ww/en/ps/man
By clicking on the required version of the manual and then
mySupport documentation is a web-based system for generat- "Show and configure", the manual opens in a modular view,
ing personalized documentation based on standard documents where you can navigate from topic to topic. Here the direct link
and is part of the Siemens Industry Online Support portal. to a topic can be used and made available to other users. The
selected document can be added to the personal library via
In mySupport, a personal document library can be created in the
"mySupport Cockpit" > "Add to mySupport documentation".
"Documentation" category. This library can be accessed online
in mySupport or also be generated in various formats for offline • Via the direct link
use. https://support.industry.siemens.com/my/ww/en/
documentation/advanced
Previously, this functionality was available in the My Documenta- After logon/registration, the online help is displayed as the
tion Manager for configurable manuals. Due to the integration in current document.
mySupport, all entries of the Industry Online Support can now be
imported into the personal document library, including FAQs or
product notifications. ■ More information
If you have already worked with the My Documentation Manager, More information is available on the internet at
all of the previously created libraries will continue to be available • https://support.industry.siemens.com/my/ww/en/
without restrictions in mySupport. documentation
In addition, the personal library in mySupport can be shared with • https://support.industry.siemens.com/cs/helpcenter/en/
other mySupport users. In this way, a collection of relevant index.htm?#persoenliche_bibliothek_aufbauen.htm
documents can be created very effectively and used together
with other mySupport users all over the world.
You must register/log in for configuring and generating/
managing.

10

10/18 Siemens D 21.3 · 2022


© Siemens 2022

Services and documentation


Documentation

■ Overview ■ Application
SINAMICS S120 Cabinet Modules and Cabinet Modules-2, Explanations for the manuals:
SINAMICS S150 Converter Cabinet Units • Operating Instructions
The documentation is provided as standard in PDF format on contain all the information needed to install the device and
DVD, and comprises the following sections: make electrical connections, information about
commissioning and a description of the converter functions
• Description Phases of use: Control cabinet construction, commissioning,
• Installation instructions operation, maintenance and servicing.
• Commissioning guide • Manuals
• Function description contain all the necessary information about the intended use
of the components of a system, e.g. technical data, interfaces,
• Maintenance information dimension drawings, characteristics and possible
• Configuration manual applications.
• Lists of spare parts Phases of use: Cabinet configuration/setup, circuit diagram
configuration/drawing.
• Equipment-specific documents such as circuit diagrams,
dimensional drawings, layout diagrams, and terminal • Configuration Manuals
diagrams contain all the information needed for EMC-compliant
installation and for the configuration of control cabinets and
Documentation in English/German is supplied as standard with drive systems.
the device. Phases of use: Control cabinet configuration/setup.
The scope of supply also includes a DVD-ROM with the • List Manuals
STARTER commissioning tool. describe all parameters, function diagrams and faults/alarms
for the product/system as well as their meaning and setting
If one of the languages subsequently listed is required, when options. It contains parameter data and fault/warning
ordering this should be specified using the corresponding descriptions with functional correlations.
option order code (see Description of options): Phases of use: Commissioning of components that have
Language Order code already been connected, configuration of system functions,
fault cause/diagnostics.
English/French D58
• Function Manuals
English/Spanish D60 contain all the relevant information about individual drive
English/Italian D80 functions
English/Chinese D91
Phases of use: Commissioning of components that have
already been connected, configuration of system functions.
English/Portuguese (Brazil) D93
English/Russian D94

Configuring documents/documentation available for


downloading at:
For SINAMICS S120 Cabinet Modules and Cabinet Modules-2
https://support.industry.siemens.com/cs/ww/en/ps/13233/man
For SINAMICS S150
https://support.industry.siemens.com/cs/ww/en/ps/13234/man
SINAMICS S120 chassis and chassis-2 units
Comprehensive documentation is available for the
SINAMICS S120 chassis and chassis-2 units, including
Operating Instructions, Equipment Manuals, List Manuals and
the Configuration Manual.
Information is available in the following formats:
• PDF file
• Configuring documents/documentation available for
downloading at:
https://support.industry.siemens.com/cs/ww/en/ps/13231/man
10

Siemens D 21.3 · 2022 10/19


© Siemens 2022

Services and documentation

Notes

10

10/20 Siemens D 21.3 · 2022


11
© Siemens 2022

Appendix

11/2 Certificates of suitability (approvals)

11/4 Software licenses

11/6 Conversion tables

11/8 Conditions of sale and delivery

Siemens D 21.3 · 2022


© Siemens 2022

Appendix

Certificates of suitability (approvals)

■ Overview
Many of the products in this Catalog fulfill requirements, e.g. for components as they are described in the Catalogs and
UL, CSA or FM and are labeled with the corresponding approval Configuration Manuals.
designation.
The certificates are only valid if the products are used with the
All of the certificates of suitability, approvals, certificates, described system components, are installed according to the
declarations of conformity, test certificates, e.g. CE, UL, Safety Installation Guidelines and used for their intended purpose.
Integrated etc. have been performed with the associated system
In other cases, the vendor of these products is responsible for
arranging for the issue of new certificates.
Test code Tested by Device series/ Test standard Product category/
Component File-No.
UL: Underwriters Laboratories
Independent public testing body in North America
UL according to UL standard SINUMERIK Standard UL 508, CSA C22.2 No. 142 NRAQ/7.E164110
NRAQ/7.E217227
SIMOTION Standard UL 508, CSA C22.2 No. 142 NRAQ/7.E164110
SINAMICS Standard UL 508, 508C, 61800-5-1 NRAQ/7.E164110,
UL according to CSA standard CSA C22.2 No. 142, 274 NMMS/2/7/8.E192450,
NMMS/2/7/8.E203250,
NMMS/7.E214113,
NMMS/7.E253831
UL according to NMMS/2/7/8.E121068
UL and CSA standards
NMMS/7.E355661
NMMS/7.E323473
SIMODRIVE Standard UL 508C, CSA C22.2 No. 274 NMMS/2/7/8.E192450
UL according to UL standard
NMMS/7.E214113

UL according to CSA standard SIMOTICS Standard UL 1004-1, 1004-6, 1004-8, PRGY2/8.E227215


CSA C22.2 No. 100 PRHZ2/8.E93429
UL according to PRHJ2/8.E342747
UL and CSA standards PRGY2/8.E253922
PRHZ2/8.E342746
Line/motor reactors Standard UL 508, 506, 5085-1, 5085-2, 1561, XQNX2/8.E257859
CSA C22.2 No. 14, 47, 66.1-06, 66.2-06 NMTR2/8.E219022
NMMS2/8.E333628
XPTQ2/8.E257852
XPTQ2/8.E103521
NMMS2/8.E224872
XPTQ2/8.E354316
XPTQ2/8.E198309
XQNX2/8.E475972
Line filters, dv/dt filters, UL 1283, CSA C22.2 No. 8 FOKY2/8.E70122
sine-wave filters
Resistors UL 508, 508C, CSA C22.2 No. 14, 274 NMTR2/8.E224314
NMMS2/8.E192450
NMTR2/8.E221095
NMTR2/8.E226619
TUV: TUV Rheinland of North America Inc.
Independent public testing body in North America, Nationally Recognized Testing Laboratory (NRTL)
TÜV: TÜV SÜD Product Service
Independent public testing body in Germany, Nationally Recognized Testing Laboratory (NRTL) for North America
TUV according to SINAMICS NRTL listing according to standard UL 508C U7V 12 06 20078 013
UL and CSA standards U7 11 04 20078 009
U7 11 04 20078 010
U7 11 04 20078 011
SIMOTION NRTL listing according to standard UL 508 U7V 13 03 20078 01
SIMODRIVE NRTL listing according to standard UL 508C, CU 72090702
11 Motion Control Encoder
CSA C22.2. No. 14
NRTL listing according to UL 61010-1 U8V 10 06 20196 024
CSA C22.2 No. 61010-1

11/2 Siemens D 21.3 · 2022


© Siemens 2022

Appendix

Certificates of suitability (approvals)

■ Overview
Test code Tested by Device series/ Test standard Product category/
Component File-No.
CSA: Canadian Standards Association
Independent public testing body in Canada
CSA according to CSA standard SINUMERIK Standard CSA C22.2 No. 142 2252-01 : LR 102527

FMRC: Factory Mutual Research Corporation


Independent public testing body in North America
FM according to FM standard SINUMERIK Standard FMRC 3600, FMRC 3611, FMRC 3810, –
ANSI/ISA S82.02.1

EAC: Ivanovo-Certificate
Independent public testing body in the Russian Federation
EAC in accordance with the SINAMICS Standard IEC 61800-5-1/-2, IEC 61800-3 –
EAC Directive SINUMERIK
SIMOTION

RCM: Australian Communications and Media Authority


Independent public testing body in Australia
RCM according to EMC standard SINAMICS Standard IEC AS 61800-3, EN 61800-3 –
SINUMERIK
SIMOTION

KC: National Radio Research Agency


Independent public testing body in South Korea
KC according to EMC standard SINAMICS Standard KN 11 –
SINUMERIK
SIMOTION

BIA
Federal Institute for Occupational Safety
– Functional safety SINAMICS Standard EN 61800-5-2 –
SINUMERIK
SIMOTION
TÜV SÜD Rail
– Functional safety SINAMICS Standard EN 61800-5-2 –
SINUMERIK
SIMOTION

More information about certificates can be found online at:


https://support.industry.siemens.com/cs/ww/en/ps/cert

11

Siemens D 21.3 · 2022 11/3


© Siemens 2022

Appendix

Software licenses

■ Overview
Software types Rental floating license
Software requiring a license is categorized into types. The rental floating license corresponds to the rental license,
The following software types have been defined: except that a license is not required for each installation of the
• Engineering software software. Rather, one license is required per object (for example,
user or device).
• Runtime software
Trial license
Engineering software
A trial license supports "short-term use" of the software in
This includes all software products for creating (engineering) a non-productive context, e.g. for testing and evaluation
user software, e.g. for configuring, programming, purposes. It can be transferred to another license.
parameterizing, testing, commissioning or servicing.
Data generated with engineering software and executable Demo license
programs can be duplicated for your own use or for use by The demo license support the "sporadic use" of engineering
third-parties free-of-charge. software in a non-productive context, for example, use for
testing and evaluation purposes. It can be transferred to another
Runtime software license. After the installation of the license key, the software can
This includes all software products required for plant/machine be operated for a specific period of time, whereby usage can be
operation, e.g. operating system, basic system, system interrupted as often as required.
expansions, drivers, etc. One license is required per installation of the software.
The duplication of the runtime software and executable
programs created with the runtime software for your own use or Demo floating license
for use by third-parties is subject to a charge. The demo floating license corresponds to the demo license,
You can find information about license fees according to use in except that a license is not required for each installation of the
the ordering data (e.g. in the catalog). Examples of categories of software. Rather, one license is required per object (for example,
use include per CPU, per installation, per channel, per instance, user or device).
per axis, per control loop, per variable, etc. Certificate of License (CoL)
Information about extended rights of use for parameterization/ The CoL is the licensee's proof that the use of the software has
configuration tools supplied as integral components of the been licensed by Siemens. A CoL is required for every type of
scope of supply can be found in the readme file supplied with use and must be kept in a safe place.
the relevant product(s).
Downgrading
License types
The licensee is permitted to use the software or an earlier
Siemens Industry Automation & Drive Technologies offers version/release of the software, provided that the licensee owns
various types of software license: such a version/release and its use is technically feasible.
• Floating license
Delivery versions
• Single license
Software is constantly being updated.
• Rental license The following delivery versions
• Rental floating license • PowerPack
• Trial license • Upgrade
• Demo license can be used to access updates.
• Demo floating license Existing bug fixes are supplied with the ServicePack version.
Floating license PowerPack
The software may be installed for internal use on any number of PowerPacks can be used to upgrade to more powerful software.
devices by the licensee. Only the concurrent user is licensed. The licensee receives a new license agreement and CoL
The concurrent user is the person using the program. Use (Certificate of License) with the PowerPack. This CoL, together
begins when the software is started. with the CoL for the original product, proves that the new
A license is required for each concurrent user. software is licensed.
Single license A separate PowerPack must be purchased for each original
license of the software to be replaced.
Unlike the floating license, a single license permits only one
installation of the software per license. Upgrade
The type of use licensed is specified in the ordering data and An upgrade permits the use of a new version of the software on
in the Certificate of License (CoL). Types of use include for the condition that a license for a previous version of the product
example per instance, per axis, per channel, etc. is already held.
One single license is required for each type of use defined. The licensee receives a new license agreement and CoL with
the upgrade. This CoL, together with the CoL for the previous
Rental license product, proves that the new version is licensed.
11 A rental license supports the "sporadic use" of engineering A separate upgrade must be purchased for each original license
software. Once the license key has been installed, the software of the software to be upgraded.
can be used for a specific period of time (the operating hours do
not have to be consecutive).
One license is required for each installation of the software.

11/4 Siemens D 21.3 · 2022


© Siemens 2022

Appendix

Software licenses

■ Overview
ServicePack Software Update Service (SUS)
ServicePacks are used to debug existing products. As part of the SUS contract, all software updates for the respec-
ServicePacks may be duplicated for use as prescribed tive product are made available to you free of charge for a period
according to the number of existing original licenses. of one year from the invoice date. The contract will automatically
be extended for one year if it is not canceled three months
License key before it expires.
Siemens Industry Automation & Drive Technologies supplies The possession of the current version of the respective software
software products with and without license keys. is a basic condition for entering into an SUS contract.
The license key serves as an electronic license stamp and
is also the "switch" for activating the software (floating license, You can download explanations concerning license conditions
rental license, etc.). from
The complete installation of software products requiring license https://mall.industry.siemens.com/legal/ww/en/
keys includes the program to be licensed (the software) and the terms_of_trade_en.pdf
license key (which represents the license).

11

Siemens D 21.3 · 2022 11/5


© Siemens 2022

Appendix

Conversion tables

■ Rotary inertia (to convert from A to B, multiply by entry in table)


B lb-in2 lb-ft2 lb-in-s2 lb-ft-s2 kg-cm2 kg-cm-s2 gm-cm2 gm-cm-s2 oz-in2 oz-in-s2
A slug-ft2
lb-in2 1 6.94 × 10–3 2.59 × 10–3 2.15 × 10–4 2.926 2.98 × 10–3 2.92 × 103 2.984 16 4.14 × 10–2
lb-ft2 144 1 0.3729 3.10 × 10–2 421.40 0.4297 4.21 × 105 429.71 2304 5.967
lb-in-s2 386.08 2.681 1 8.33 × 10–2 1.129 × 103 1.152 1.129 × 106 1.152 × 103 6.177 × 103 16
lb-ft-s2 4.63 × 103 32.17 12 1 1.35 × 104 13.825 1.355 × 107 1.38 × 104 7.41 × 104 192
slug-ft2
kg-cm2 0.3417 2.37 × 10–3 8.85 × 10–4 7.37 × 10–5 1 1.019 × 10–3 1000 1.019 5.46 1.41 × 10–2
kg-cm-s2 335.1 2.327 0.8679 7.23 × 10–2 980.66 1 9.8 × 105 1000 5.36 × 103 13.887
gm-cm2 3.417 × 10–4 2.37 × 10–6 8.85 × 10–7 7.37 × 10–8 1 × 10–3 1.01 × 10–6 1 1.01 × 10–3 5.46 × 10–3 1.41 × 10–5
gm-cm-s2 0.335 2.32 × 10–3 8.67 × 10–4 7.23 × 10–5 0.9806 1 × 10–3 980.6 1 5.36 1.38 × 10–2
oz-in2 0.0625 4.34 × 10–4 1.61 × 10–4 1.34 × 10–5 0.182 1.86 × 10–4 182.9 0.186 1 2.59 × 10–3
oz-in-s2 24.13 0.1675 6.25 × 10–2 5.20 × 10–3 70.615 7.20 × 10–2 7.09 × 104 72.0 386.08 1

■ Torque (to convert from A to B, multiply by entry in table)


B lb-in lb-ft oz-in N-m kg-cm kg-m gm-cm dyne-cm
A
lb-in 1 8.333 × 10–2 16 0.113 1.152 1.152 × 10–2 1.152 × 103 1.129 × 106
lb-ft 12 1 192 1.355 13.825 0.138 1.382 × 104 1.355 × 107
oz-in 6.25 × 10–2 5.208 × 10–3 1 7.061 × 10–3 7.200 × 10–2 7.200 × 10–4 72.007 7.061 × 104
N-m 8.850 0.737 141.612 1 10.197 0.102 1.019 × 104 1 × 107
kg-cm 0.8679 7.233 × 10–2 13.877 9.806 × 10–2 1 10–2 1000 9.806 × 105
kg-m 86.796 7.233 1.388 × 103 9.806 100 1 1 × 105 9.806 × 107
gm-cm 8.679 × 10–4 7.233 × 10–5 1.388 × 10–2 9.806 × 10–5 1 × 10–3 1 × 10–5 1 980.665
dyne-cm 8.850 × 10–7 7.375 × 10–8 1.416 × 10–5 10–7 1.0197 × 10–6 1.019 × 10–8 1.019 × 10–3 1

■ Length (to convert from A to B, multiply by entry in table) ■ Force (to convert from A to B, multiply by entry in table)
B inches feet cm yd mm m B lb oz gm dyne N
A A
inches 1 0.0833 2.54 0.028 25.4 0.0254 lb 1 16 453.6 4.448 × 105 4.4482
feet 12 1 30.48 0.333 304.8 0.3048 oz 0.0625 1 28.35 2.780 × 104 0.27801
cm 0.3937 0.03281 1 1.09 × 10–2 10 0.01 gm 2.205 × 10–3 0.03527 1 1.02 × 10–3 N.A.
yd 36 3 91.44 1 914.4 0.914 dyne 2.248 × 10–6 3.59 × 10–5 980.7 1 0.00001
mm 0.03937 0.00328 0.1 1.09 × 10–3 1 0.001 N 0.22481 3.5967 N.A. 100000 1
m 39.37 3.281 100 1.09 1000 1
■ Mass (to convert from A to B, multiply by entry in table)
■ Power (to convert from A to B, multiply by entry in table) B lb oz gm kg slug
A
B hp Watts
A lb 1 16 453.6 0.4536 0.0311
hp (English) 1 745.7 oz 6.25 × 10–2 1 28.35 0.02835 1.93 × 10–3
(lb-in) (deg./s) 2.645 × 10–6 1.972 × 10–3 gm 2.205 × 10–3 3.527 × 10–2 1 10–3 6.852 × 10–5
(lb-in) (rpm) 1.587 × 10–5 1.183 × 10–2 kg 2.205 35.27 103 1 6.852 × 10–2
(lb-ft) (deg./s) 3.173 × 10–5 2.366 × 10–2 slug 32.17 514.8 1.459 × 104 14.59 1
(lb-ft) (rpm) 1.904 × 10–4 0.1420
Watts 1.341 × 10–3 1 ■ Rotation (to convert from A to B, multiply by entry in table)
B rpm rad/s degrees/s
A
11 rpm 1 0.105 6.0
rad/s 9.55 1 57.30
degrees/s 0.167 1.745 × 10–2 1

11/6 Siemens D 21.3 · 2022


© Siemens 2022

Appendix

Conversion tables

■ Temperature Conversion ■ Material Densities


°F °C °C °F Material lb-in3 gm-cm3
0 –17.8 –10 14 Aluminum 0.096 2.66
32 0 0 32 Brass 0.299 8.30
50 10 10 50 Bronze 0.295 8.17
70 21.1 20 68 Copper 0.322 8.91
90 32.2 30 86 Hard wood 0.029 0.80
98.4 37 37 98.4 Soft wood 0.018 0.48
212 100 100 212 Plastic 0.040 1.11
subtract 32 and multiply by 5/9 multiply by 9/5 and add 32 Glass 0.079–0.090 2.2–2.5
Titanium 0.163 4.51
■ Mechanism Efficiencies Paper 0.025–0.043 0.7–1.2
Acme-screw with brass nut ~0.35–0.65 Polyvinyl chloride 0.047–0.050 1.3–1.4
Acme-screw with plastic nut ~0.50–0.85 Rubber 0.033–0.036 0.92–0.99
Ball-screw ~0.85–0.95 Silicone rubber, without filler 0.043 1.2
Chain and sprocket ~0.95–0.98 Cast iron, gray 0.274 7.6
Preloaded ball-screw ~0.75–0.85 Steel 0.280 7.75
Spur or bevel-gears ~0.90
Timing belts ~0.96–0.98 ■ Wire Gauges1)
Worm gears ~0.45–0.85 Cross-section Standard Wire American Wire
mm2 Gauge (SWG) Gauge (AWG)
Helical gear (1 reduction) ~0.92
0.2 25 24
■ Friction Coefficients 0.3 23 22

Materials  0.5 21 20

Steel on steel (greased) ~0.15 0.75 20 19

Plastic on steel ~0.15–0.25 1.0 19 18

Copper on steel ~0.30 1.5 17 16

Brass on steel ~0.35 2.5 15 13

Aluminum on steel ~0.45 4 13 11

Steel on steel ~0.58 6 12 9


10 9 7
Mechanism  16 7 6
Ball bushings <0.001 25 5 3
Linear bearings <0.001 35 3 2
Dove-tail slides ~0.2++ 50 0 1/0
Gibb ways ~0.5++ 70 000 2/0
95 00000 3/0
120 0000000 4/0
150 – 6/0
185 – 7/0

11

1) The table shows approximate SWG/AWG sizes nearest to standard metric


sizes; the cross-sections do not match exactly.

Siemens D 21.3 · 2022 11/7


© Siemens 2022

Appendix
Conditions of sale and delivery

■ 1. General Provisions ■ 2. Prices


By using this catalog you can purchase products (hardware, The prices are in € (Euro) ex point of delivery, exclusive of
software and services) described therein from Siemens packaging.
Aktiengesellschaft subject to the following Terms and Conditions The sales tax (value added tax) is not included in the prices.
of Sale and Delivery (hereinafter referred to as "T&C"). Please It shall be charged separately at the respective rate according
note that the scope, the quality and the conditions for supplies to the applicable statutory legal regulations.
and services, including software products, by any Siemens
entity having a registered office outside Germany, shall be Prices are subject to change without prior notice. We will charge
subject exclusively to the General Terms and Conditions of the the prices valid at the time of delivery.
respective Siemens entity. The following T&C apply exclusively To compensate for variations in the price of raw materials
for orders placed with Siemens Aktiengesellschaft, Germany. (e.g. silver, copper, aluminum, lead, gold, dysprosium and
neodym), surcharges are calculated on a daily basis using the
1.1 For customers with a seat or registered office in so-called metal factor for products containing these raw
European Union materials.
For customers with a seat or registered office in European Union, A surcharge for the respective raw material is calculated as a
the following terms and conditions apply subordinate to T&C: supplement to the price of a product if the basic official price of
• for products, which include specific terms and conditions in the raw material in question is exceeded.
the description text, these specific terms and conditions shall The metal factor of a product indicates the basic official price
apply and subordinate thereto, (for those raw materials concerned) as of which the surcharges
• for stand-alone software products and software products on the price of the product are applied, and with what method of
forming a part of a product or project, the "General License calculation.
Conditions for Software Products for Automation and Drives An exact explanation of the metal factor can be downloaded at:
for Customers with a Seat or registered Office in Germany"1) https://mall.industry.siemens.com/legal/ww/en/
and/or terms_of_trade_en.pdf
• for consulting services the “Allgemeine Geschäftsbedin- To calculate the surcharge (except in the cases of dysprosium
gungen für Beratungsleistungen der Division DF – and neodym), the official price from the day prior to that on which
Deutschland” (available only in German) and/or the order was received or the release order was effected is used.
• for other services, the „Supplementary Terms and Conditions To calculate the surcharge applicable to dysprosium and
for Services (“BL”)1) and/or neodym ("rare earths"), the corresponding three-month basic
• for other supplies the "General Conditions for the Supply of average price in the quarter prior to that in which the order was
Products and Services of the Electrical and Electronics received or the release order was effected is used with
Industry"1). a one-month buffer (details on the calculation can be found in
In case such supplies should contain Open Source Software, the explanation of the metal factor).
the conditions of which shall prevail over the "General
Conditions for the Supply of Products and Services of the
Electrical and Electronics Industry"1), a notice will be
■ 3. Additional Terms and Conditions
contained in the scope of delivery in which the applicable The dimensions are in mm. In Germany, according to the
conditions for Open Source Software are specified. This shall German law on units in measuring technology, data in inches
apply mutatis mutandis for notices referring to other third party apply only to devices for export.
software components. Illustrations are not binding.
1.2 For customers with a seat or registered office outside Insofar as there are no remarks on the individual pages of this
European Union catalog – especially with regard to data, dimensions and weights
given – these are subject to change without prior notice.
For customers with a seat or registered office outside European
Union, the following terms and conditions apply subordinate to
T&C:
• for products, which include specific terms and conditions in
the description text, these specific terms and conditions shall
apply and subordinate thereto,
• for consulting services the "Standard Terms and Conditions for
Consulting Services of the Division DF for Customers with a
Seat or Registered Office Outside of Germany"1 ) and/or
• for other services the "International Terms & Conditions for
Services"1) supplemented by "Software Licensing
Conditions"1) and/or

for other supplies of hard- and software the "International
Terms & Conditions for Products"1) supplemented by
"Software Licensing Conditions"1)
1.3 For customers with master or framework agreement
11 To the extent our supplies and/or services offered are covered
by an existing master or framework agreement, the terms and
conditions of that agreement shall apply instead of T&C.

1) The text of the Terms and Conditions of Siemens AG can be


downloaded at
https://mall.industry.siemens.com/legal/ww/en/
terms_of_trade_en.pdf

11/8 Siemens D 21.3 · 2022


© Siemens 2022

Appendix
Conditions of sale and delivery

■ 4. Export Regulations
We shall not be obligated to fulfill any agreement if such Prior to any transfer of goods, works and services provided by
fulfillment is prevented by any impediments arising out of us to a third party you shall in particular check and guarantee by
national or international foreign trade or customs requirements appropriate measures that
or any embargoes and/or other sanctions. • there will be no infringement of an embargo imposed by the
Export may be subject to license. We shall indicate in the European Union, by the United States of America and/ or by
delivery details whether licenses are required under German, the United Nations by such transfer, by brokering of contracts
European and US export lists. concerning those goods, works and services or by provision
Our products are controlled by the U.S. Government (when of other economic resources in connection with those goods,
labeled with "ECCN" unequal "N") and authorized for export only works and services, also considering the limitations of domes-
to the country of ultimate destination for use by the ultimate tic business and prohibitions of by-passing those embargos;
consignee or end-user(s) herein identified. They may not be • such goods, works and services are not intended for use in
resold, transferred, or otherwise disposed of, to any other connection with armaments, nuclear technology or weapons,
country or to any person other than the authorized ultimate if and to the extent such use is subject to prohibition or
consignee or end-user(s), either in their original form or after authorization, unless required authorization is provided;
being incorporated into other items, without first obtaining • the regulations of all applicable Sanctioned Party Lists of the
approval from the U.S. Government or as otherwise authorized European Union and the United States of America concerning
by U.S. law and regulations. Products labeled with "AL" unequal the trading with entities, persons and organizations listed
"N" are subject to European / national export authorization. therein are considered.
The export indications can be viewed in advance in the If required to enable authorities or us to conduct export control
description of the respective goods on the Industry Mall, our checks, you, upon request by us, shall promptly provide us with
online catalog system. Only the export labels "AL" and "ECCN" all information pertaining to the particular end customer, the
indicated on order confirmations, delivery notes and invoices particular destination and the particular intended use of goods,
are authoritative. works and services provided by us, as well as any export control
Products without label, with label "AL:N" / "ECCN:N", or label restrictions existing.
"AL:9X9999" / "ECCN: 9X9999" may require authorization from You acknowledge that under the EU embargo regulations
responsible authorities depending on the final end-use, or the against Iran, Syria and Russia respectively the sale of certain
destination. listed goods and related services is subject to authorization by
If you transfer goods (hardware and/or software and/or the competent export control authorities of the European Union.
technology as well as corresponding documentation, regardless If (i) the goods or services ordered by you are destined for Iran,
of the mode of provision) delivered by us or works and services Syria or Russia, and (ii) the contract for our supplies and/or
(including all kinds of technical support) performed by us to services is subject to prior authorization of the competent export
a third party worldwide, you shall comply with all applicable control authorities of the European Union, the contract between
national and international (re-)export control regulations. In any you and us shall come into force in this respect only upon
event of such transfer of goods, works and services you shall granting of such authorization.
comply with the (re-) export control regulations of the Federal The products listed in this catalog may be subject to
Republic of Germany, of the European Union and of the United European/German and/or US export regulations. Any export
States of America. requiring approval is therefore subject to authorization by the
relevant authorities.
Errors excepted and subject to change without prior notice.

11

Siemens D 21.3 · 2022 11/9


© Siemens 2022

Appendix

Notes

11

11/10 Siemens D 21.3 · 2022


© Siemens 2022

Selection and ordering at Siemens


Industry Mall, downloading and ordering catalogs

Easy product selection and ordering: Industry Mall


Industry Mall
The Industry Mall is a Siemens AG Internet ordering platform.
It provides you with online access to a comprehensive product
spectrum that is presented in an informative, well-organized
way.
Powerful search functions help you select the required products,
while configurators enable you to configure complex product
and system components quickly and easily. CAx data are also
available for you to use.
Data transfer allows the entire procedure, from selection through
ordering to tracking and tracing, to be carried out online.
Availability checks, individual customer discounting, and
quotation preparation are also possible.
www.siemens.com/industrymall

Downloading catalogs
Siemens Industry Online Support
You can download catalogs and brochures in PDF format from
Siemens Industry Online Support without having to register.
The filter box makes it possible to perform targeted searches.
www.siemens.com/industry-catalogs

Ordering printed catalogs


Please contact your local Siemens branch if you are interested
in ordering printed catalogs.
Addresses can be found at
www.siemens.com/automation-contact
© Siemens 2022

Get more information Security information


SINAMICS S120 Siemens provides products and solutions with
Chassis Format Converter Units industrial security functions that support the secure
and Cabinet Modules operation of plants, systems, machines and
www.siemens.com/sinamics-s120 networks.
SINAMICS S150 In order to protect plants, systems, machines and
Converter Cabinet Units networks against cyber threats, it is necessary to
www.siemens.com/sinamics-s150 implement – and continuously maintain – a holistic,
The SINAMICS converter family: state-of-the-art industrial security concept. Siemens’
www.siemens.com/sinamics products and solutions constitute one element of
such a concept.
Motion Control Systems and Solutions for
production machine and machine tool Customers are responsible for preventing unautho-
equipment: rized access to their plants, systems, machines and
www.siemens.com/motioncontrol networks. Such systems, machines and components
should only be connected to an enterprise network
Local partners worldwide: or the internet if and to the extent such a
www.siemens.com/automation-contact connection is necessary and only when appropriate
security measures (e.g. firewalls and/or network
Published by segmentation) are in place.
Siemens AG For additional information on industrial security
measures that may be implemented, please visit
Digital Industries https://www.siemens.com/industrialsecurity
Motion Control Siemens’ products and solutions undergo contin-
Postfach 31 80 uous development to make them more secure.
91050 Erlangen, Germany Siemens strongly recommends that product
updates are applied as soon as they are available
For the U.S. published by and that the latest product versions are used. Use
Siemens Industry Inc. of product versions that are no longer supported,
and failure to apply the latest updates may increase
customer’s exposure to cyber threats.
100 Technology Drive
Alpharetta, GA 30005 To stay informed about product updates, subscribe
United States to the Siemens Industrial Security RSS Feed under
https://www.siemens.com/cert

PDF (E86060-K5521-A131-A8-7600)
V6.MKKATA.GMC.530
KG 1122 578 En
Produced in Germany
© Siemens 2022

Subject to changes and errors. The information


given in this document only contains general
descriptions and/or performance features which
may not always specifically reflect those described,
or which may undergo modification in the course
of further development of the products. The
requested performance features are binding only
when they are expressly agreed upon in the
concluded contract.
All product designations may be trademarks or
product names of Siemens AG or other companies
whose use by third parties for their own purposes
could violate the rights of the owners.

You might also like