FLEXONAX FLEX 90 0,6/1 kV

Use:
Flexonax Flex 90 cables are recommended to be applied in
substations, commercial and industrial installations, in wet or dry
locations, on trays, ducts, direct buried, throughs or similar
applications.
1
Construction:
1. Conductor: Soft temper bare copper conductor, class 5
stranding.
2

2. Insulation: Thermoset compound, 90ºC operating


temperature, as per NBR 6251 standard, under the designation of
3 HEPR.

3. Jacket: Thermoplastic PVC/ST2 compound, black color.

Manufacturing Standard:
NBR 7286 - Cabos de potência com isolação extrudada de
borracha Etileno Propileno (EPR) para tensões de 1kV a 35kV -
Requisitos de desempenho.

Conductor Nominal thickness Overall Nominal Max Inductive Ampacity


diameter mass electrical DC reactance
resistance at
20°C
Cross Nominal Insulation Sheath still air,
sectional area diameter amb.30°C
mm² mm mm mm mm kg/km /km /km A
240 20,80 1.7 1,5 27.20 2,338 0.0801 0.0918 607