You are on page 1of 1
‘Technical Specification of Water Bath Heater: 1.0 GENERAL Indirect water bath heater shall be natural yas fired and composed of the following parts: ) i) iv) y) vi) ‘Main dody/shell Coil/tube bundle Water expansion tank Fuel gas feed line Bumer & pilot Fire tube vil) Chimney/stack viii) Burner controlfmanagement system ix) » Skid frame, service ladder & platform Extemal insulation of body shell 2, Design Data: ji) Installation: Outdoor-unprotected skid mounted; ji) The heater shall operate self contained gas without any other auxiliary energy (i) with pneumatic instrumentation). iil) Design pressure of tube bundle: 70 bar. iv) Design Temperature: 100°C. v) Max. allowable drop: 300 mbar. vi) Max. Velocity in the tube bundle= 18M/Sec. vii) Gas temperature at the inlet of the Station: 15 °C-20°C. Required gas temp at the outlet ofthe station: 20°C-25°C ix) Operating temperature of the water bath: 80°C, x) Thermal efficiency : 85% xi) Construction Code: ASME-VIII with 'U' stamp, Welding: As per ASME section-ix xi) Max. Corrosion allowance: 1.6 mm for shell and 2 mm for bundled tube. xiii) Body: Cylindrical vessel with removable flame tube and gas tube bundle. xiv) Flange Connection: 12 "ANSI - 600 RF. xv) Gas Flow Rate: 120 MMSCFD. xvi) Operating Pressure: 250-1000 psig, xvii) Heat duty of the Heater: 2100 KWH. xviii) Maximum Station Inlet Pressure:1000 Psig xix) Minimum Ialet Station Pressure: 250 Psig xx) Station Outlet Pressure: 150-250 Psig xxi) Tube bundle size of the Heater: equivalent to 12"